4

SQL33.00
SQL83.00

SQK33.00

Electric actuators for
butterfly valves
with 90° angle of rotation

•
•
•
•
•
•
•
•
•

506

SQK33.00
SQL33.0...
SQL83...

SQK33.00
Operating voltage AC 230 V
SQL33.0... Operating voltage AC 230 V
SQL83.00
Operating voltage AC 24 V
3-position control signal
Auxiliary switch and potentiometer for additional functions
Nominal angle of rotation 90°
Reversible electric motor
For mounting on butterfly valves and slipper valves with ASK… mounting kit
With manual adjuster and position indicator

.
.
.
.
.
.
.
.
.
.
.

Use
For use in heating, ventilation and air conditioning systems to operate Siemens butterfly
valves and three-port and four-port slipper valves (mixing valves), types K1i…,
VKF41…, VB… and VC... (see "Equipment combinations") and valves from other
manufacturers.
The actuators can be fitted with additional auxiliary switches and potentiometers

CM1N4506en
07.06.2004

Siemens Building Technologies
HVAC Products

.
.

Functions
If the actuator is driven by a 3-position signal from the controller, it generates a rotary
motion which is transferred to the valve (butterfly, slipper valve, three-port or four-port
mixing valve).
Direction of rotation of the actuator on delivery:
• Voltage at Y1 = Clockwise rotation
• Voltage at Y2 = Anti-clockwise rotation
• No voltage
= No rotation; actuator fixed in relevant position

.
.

The direction of rotation can be reversed if required.
Extending the actuator
functions

• The SQK33.00 actuator can be fitted with an auxiliary switch
• The SQL… actuators can be fitted with an auxiliary switch, a dual auxiliary switch or
an auxiliary switch and a 1000-ohm potentiometer.
If an auxiliary switch and/or potentiometer are fitted, the electrical wiring must take
account of this. Refer to the wiring diagram under the actuator cover and see also the
"Commissioning" and "Connection diagrams" sections in this data sheet.

Types
Type

Operating
voltage

Control
signal

Run-time
for 90° at 50 Hz

SQK33.00

AC 230 V

3-position

125 s

1 x ASC9.5 only 1 auxiliary switch

SQL33.00
SQL33.03
SQL83.00

AC 230 V
AC 230 V
AC 24 V

3-position

125 s
30 s
125 s

1 x ASC9.5 or
1 x ASC9.4 or
1 x ASZ7.4

ASK31
ASK32

Mounting kits

Accessories

Space for
accessories

Accessory function

1 auxiliary switch
1 dual auxiliary switch
1 auxiliary switch and 1000 Ω potentiometer

ASK33
ASK40
ASK41

For slipper valves, type VBF21 … (DN65 ... DN150), Series 01
For slipper valves, type VB… / VC (DN¾"... DN1½") Series 02
or VBF21... (DN40 / 50)
For butterfly valves, type VKF41… (DN40 ... DN200), K1i... (¾”...1¼”)
For slipper valves from other manufacturers, see data sheet N4291
For slipper valves from other manufacturers, see data sheet N4291

ASC9.5
ASC9.4
ASZ7.4

1 auxiliary switch
1 dual auxiliary switch
1 auxiliary switch and one 1000-ohm potentiometer

.
.
.
.
.
.
.
.
.

Ordering
The actuator, slipper valve or butterfly valve, mounting kit and accessories must be
ordered separately.
When ordering, please specify the quantity, product name and type code.
Example:

Delivery

1 actuator, type SQL33.03, 1 mounting kit, type ASK31 and
1 auxiliary switch with ASZ7.4 potentiometer
The actuator, valve or butterfly valve, ASK.. mounting kit and accessories are packed
separately and are not delivered fully assembled.

2/8
Siemens Building Technologies
HVAC Products

.
.

Electric actuators for butterfly valves

CM1N4506en
07.06.2004

.

Equipment combinations
The table below shows which actuators may be used with which slipper valves and
butterfly valves, and indicates the appropriate mounting kits in each case.

PN class
Valves

Data
sheet

SQK33.00

Actuators
SQL33.00
SQL83.00

SQL33.03

Mounting
kits

Nominal size (DN)
Three-port slipper valves

(Mixing)

VBF21...

(40 ... 50)

PN6

N4241

40 / 50

40 / 50

40 / 50

ASK32

(65 ...150)

PN6

N4241

---

65 ...150

65 ...150

ASK31

VBI31...

(¾”...1½”)

PN10

N4232

¾”...1½”

¾”...1½”

¾”...1½”

ASK32

VBG31...

(¾”...1½”)

PN10

N4233

¾”...1½”

¾”...1½”

¾”...1½”

ASK32

PN6...

---

¾”...1½”

¾”... 2"

¾”... 2"

ASK40 *)
ASK41 *)

PN10

N4252

¾”...1½”

¾”...1½”

¾”...1½”

ASK32

PN6...

---

¾”...1½”

¾”...

¾”... 2"

ASK40 *)
ASK41 *)

Other
makes
Four-port valves

(Mixing)

VCI31...

(¾”...1½”)

Other
makes
Butterfly valves
K1i...

(¾”...1¼”)

PN6

N4111

¾”...1¼”

¾”...1¼”

---

ASK33

VKF41...

(40 ... 200)

PN16

N4131

40

40 ... 200

40 ... 200

ASK33

*) Mounting kits ASK40 and ASK41 for non-Siemens actuators: refer to data sheet N42291

Mechanical design
The electric actuators require no maintenance. They have a reversible synchronous
motor and reduction gears with self-lubricating sinter bearings. The housing base and
the console are die-cast aluminium, and the cover is plastic.
"AUTO" and "MANUAL" modes can be selected with a rotary switch on the housing
base. When the switch is set to "MANUAL", the actuator and valve can be operated
with a manual lever. For manual operation, the angle of rotation is mechanically limited
by an end-stop.
The actuators supplied have a 90° angle of rotation suitable for the Siemens valves.
During automatic operation, rotation is limited by two built-in end-switches. For nonSiemens valves, the angle of rotation in the range 70° to 180° can be selected by
repositioning the switching cams.
The direction of operation of the actuator can be reversed (refer to "Commissioning").

3/8
Siemens Building Technologies
HVAC Products

Electric actuators for butterfly valves

CM1N4506en
07.06.2004

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

Rotary "AUTO" / "MAN" switch
Manual lever
Console (e.g. ASK31 mounting kit)
Terminal strip
Dual end-switch (always factory fitted)
Connector for reversal of direction of rotation
(only with SQK33.00, SQL33.0…, SQL83.00)

Accessory ASC9.5

1 auxiliary switch

Accessory ASC9.4

4554Z04

for SQK33.00,
SQL33.0...
SQL83.00

1 auxiliary switch and
1 1000-ohm potentiometer

Accessory ASZ7.4

4554Z05

for SQL33.0...
SQL83.00

4554Z06

1 dual auxiliary switch

for SQL33.0...
SQL83.00

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

Engineering

• Butterfly valves: see data sheets N4100 … N4199.
• Three-port and four-port slipper valves: see data sheets N4200 … N4299.
• Admissible ambient temperatures, see "Technical data".
Electrical installation

.

The actuators must be electrically connected in accordance with local regulations and
with the connection diagrams.

!

Regulations and requirements to ensure the safety of people and property must
be observed at all times.
If additional functions are to be controlled by the actuator, the ASC9.. (auxiliary switch)
or ASZ7.5 (auxiliary switch / potentiometer) must be fitted. The relevant switching
point(s) and zero-ohm position must be noted in the plant documentation.

4/8
Siemens Building Technologies
HVAC Products

Electric actuators for butterfly valves

CM1N4506en
07.06.2004

Mounting
Mounting instructions are enclosed with the mounting kit.
The valve, actuator and mounting kit are packed separately. The valve and actuator
can be assembled easily on site. There is no need for special tools or calibration.
Take care to install the valve the right way up. Refer to the mounting instructions for the
valve concerned (butterfly or slipper valves).
Orientation

.
.
.
.
.
.
.
.
.
.
.

90°

4362Z01

90°

Commissioning
When commissioning the complete motorised valve, consisting of actuator, mounting kit
and (butterfly or slipper) valve, check the wiring and test the functions. This also
applies to any additional components fitted (e.g. auxiliary switch or potentiometer).

Note

Siemens slipper valves up to DN50 can be commissioned without an actuator being
fitted. In this case, the flow rate must be adjusted manually with the standard manual
adjuster fitted to the valve.
For automatic operation, the rotary switch must be set to "AUTO".

Mode of operation
Rotary switch for
mode selection

"AUTO" = Automatic operation

Reversing the
direction of rotation

"MAN" = Manual operation

The actuators are factory-set to rotate in a clockwise direction (as seen from the front).
The direction of rotation can be reversed by repositioning a connector located under the
cover (see "Mechanical design").
The wiring for the OPEN and CLOSE control signal is not affected.

As supplied

Direction of rotation reversed

5/8
Siemens Building Technologies
HVAC Products

Electric actuators for butterfly valves

CM1N4506en
07.06.2004

Setting the angle of
rotation

The angle of rotation is factory-set to 90°. However, the angle can be changed to
between 70° and 180°. This may be necessary when using non-Siemens valves.
Special notes on this subject will be found in the mounting instructions for the ASK40
and ASK41 (mounting kits for non-Siemens valves).

Maintenance

Warning !

Disposal

The actuators require no maintenance.
When servicing the valve and/or actuator: switch OFF the pump and power
supply, close the main shut-off valve in the pipework, release pressure in the
pipes and allow them to cool down completely.
If necessary, disconnect electrical connections from terminals.

.

The device may not be disposed of together with domestic waste. This applies in
particular to the PCB.
Legislation may demand special handling of certain components, or it may be sensible
from an ecological point of view.

Current local legislation must be observed.

Warranty
The technical data given for these applications is valid only in conjunction with the
Siemens valves (butterfly and slipper valves) and third-party valves for use with the
ASK40 / ASK41, as described under "Compatibility". The use of third-party valves
other than those recommended by Siemens invalidates the warranty.

Technical data

Power supply

Operating data

Rated voltage
SQK33.00, SQL33.00, SQL33.03
SQL83.00
Rated frequency
Control signal
Power consumption *)
SQK33.00
SQL33.00, SQL83.00
SQL33.0...
Run-time for rotation through 90°
SQK33.00, SQL33.00
SQL83.00
SQL33.03
Angle of rotation
Factory setting
Adjustment range

.
.
.
.
.
.
.
.
.
.

AC 230 V ± 15 %
AC 24 V ± 20 %
50 / 60 Hz
3-position
3 VA
4 VA
6.5 VA
at 50 Hz
125 s
125 s
30 s

at 60 Hz
105 s
105 s
25 s

90° ± 2°
70° ...180°

6/8
Siemens Building Technologies
HVAC Products

Electric actuators for butterfly valves

CM1N4506en
07.06.2004

Torque *)
SQK33.00
SQL33.03
SQL33.00, SQL83.00
End switch
Switching capacity
Switching differential

AC 250 V, 6 (2) A
Approx. 1°

Materials

Housing base and console
Cover

Die-cast aluminium
Plastic

Dimensions / Weight

Dimensions
Cable glands
Weight
SQK33.00
SQL33.00, SQL83.00
SQL33.03, SQL35.00, SQL85.00

See “Dimensions”
∅ 20,5 (M20) (4x)

Ambient conditions

Industry standards

Accessories

Nominal torque
5 Nm
10 Nm
12.5 Nm

Starting torque
10 Nm
12 Nm
25 Nm

.

1.25 kg
1.35 kg
1.40 kg

Max. admissible temperature of medium in
assembled valve
Operation
– Environmental conditions
– Temperature
– Humidity
Transport
– Environmental conditions
– Temperature
– Humidity
Storage
– Environmental conditions
– Temperature
– Humidity

> 120 °C
To IEC 721-3-3
Class 3K5
–15 ... +55 °C
5 ... 95 % rh
To IEC 721-2-3
Class 3K2
– 30 ... +65 °C
< 95 % rh
To IEC 721-1-3
Class 3K1
–15 ... +55 °C
0 ... 95 % rh

Meets the requirements for CE marking in
EMC Directive
Low Voltage Directive
Housing protection standard

89/336/EEC
73/23/EEC
IP44 to IEC529 / DIN40050

ASC9.5
ASC9.4
Switching capacity
Switching differential
ASZ7.4
Switching capacity
Switching differential
Change in resistance

Auxiliary switch
Dual auxiliary switch
AC 250 V,
10 A resistive / 3 A inductive
Approx. 1°
Auxiliary switch with potentiometer
AC 250 V,
10 A resistive / 3 A inductive
Approx. 1°
0 ... 90° corresponding to
0 ...1000 ohm

*) These values apply at nominal voltage, at an ambient temperature of 20°C and at the
specified nominal running time

7/8
Siemens Building Technologies
HVAC Products

Electric actuators for butterfly valves

.
.
.
.
.

CM1N4506en
07.06.2004

.
.
.
.
.
.
.
.

Connection diagrams
SQK33.00

.
.

SQL33.00, SQL33.03

Cm1
Cm2
c1
c1, c2

SQL83.00

c1, 1000Ω

End switch
End switch
1 auxiliary switch ASC9.5 or
1 dual auxiliary switch ASC9.4
or
1 installable module ASZ7.4
(1 auxiliary switch and
1 potentiometer)

Dimensions
All dimensions in mm

∅ 20,5 (M20)

SQK33.00
Installation height H*
for actuator with mounting kit
ASK31
162 mm
ASK32
132 mm
ASK33
162 mm

∅ 20,5 (M20)

SQL33.0... / SQL83.00
Installation height H*
for actuator with mounting kit
ASK31
188 mm
ASK32
158 mm
ASK33
188 mm

Overall height of valve
and actuator

= Installation height of slipper or butterfly valve from the middle of the pipe
+ Installation height H* of the actuator with mounting kit
+ Minimum clearance from ceiling or wall for mounting, connection,
operation, service etc.
∆
>100 mm
∆ ∆ >200 mm

8/8

 2004 Siemens Building Technologies Ltd.

Siemens Building Technologies
HVAC Products

Electric actuators for butterfly valves

Subject to technical alteration
CM1N4506en
07.06.2004

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Create Date                     : 2004:06:22 10:27:41+02:00
Modify Date                     : 2004:06:22 10:27:41+02:00
Page Count                      : 8
Creation Date                   : 2004:06:22 08:27:41Z
Mod Date                        : 2004:06:22 08:27:41Z
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Author                          : FriesD
Metadata Date                   : 2004:06:22 08:27:41Z
Creator                         : FriesD
Title                           : Microsoft Word - N4506en.doc
EXIF Metadata provided by EXIF.tools

Navigation menu