Siemens Tps3 11 Users Manual
TPS3 11 to the manual e8d0af4a-8230-4236-b766-d129153b96f5
2015-02-05
: Siemens Siemens-Tps3-11-Users-Manual-410521 siemens-tps3-11-users-manual-410521 siemens pdf
Open the PDF directly: View PDF .
Page Count: 12
Download | |
Open PDF In Browser | View PDF |
TPS3 11 Surge Protective Device User Manual - USA V WARNING - Hazardous Voltage & Shock Hazard Failure to Follow These Instructions Could Result in Death or Serious Injury • • • • • • Only qualified licensed electricians should install or service SPDs Hazardous voltages exist within SPDs SPDs should never be installed or serviced when energized Use appropriate safety precautions including Personal Protection Equipment Failure to follow these instructions can result in death, serious injury, and/or equipment damage. This manual shall be read in entirety prior to installing Bonding and Grounding Hazard Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electrical Code (NEC®) and all applicable codes. Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground in accordance with the NEC® and all applicable codes. During installation into an electrical system the SPD must not be energized until the electrical system is completely installed, inspected and tested. All conductors must be connected and functional including the neutral (if required). The voltage rating of the SPD and system must be verified before energizing the SPD. Failure to follow these guidelines can lead to abnormally high voltages at the SPD. This may cause the SPD to fail. The warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC®. Do Not Hi-Pot Test SPDs Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing highpotential testing and then reconnected after test completion. Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void the warranty. Table of Contents Failure to Follow These Instructions Could Result in Death or Serious Injury............................... 2 Do Not Hi-Pot Test SPDs.............................................................................................................................................................................2 Introduction.................................................................................................................................................... 4 Warning and Safety Information................................................................................................................................................................4 Qualified Person........................................................................................................................................................................................4 Danger......................................................................................................................................................................................................4 Warning....................................................................................................................................................................................................4 Caution.....................................................................................................................................................................................................4 Do Not Hi-Pot Test SPDs.............................................................................................................................................................................4 Industry Standards Changes - 2009...........................................................................................................................................................4 Simplified Explanation of Operation...........................................................................................................................................................5 Parts List and Inspection ...........................................................................................................................................................................5 Voltage Rating & Application.....................................................................................................................................................................5 SPDs on Ungrounded Systems...................................................................................................................................................................6 Optional Flush Mount Installation Instructions...........................................................................................................................................6 TPS3 11 Installation Instructions............................................................................................................... 7 Common Problems to Avoid......................................................................................................................................................................7 Operation.......................................................................................................................................................... 9 Diagnostic Indication.................................................................................................................................................................................9 Phase indicator LEDs (Green).....................................................................................................................................................................9 Service LED (Red)......................................................................................................................................................................................9 Audible Alarm Option................................................................................................................................................................................9 Dry Contact Option...................................................................................................................................................................................9 Remote Monitor Accessory Option.............................................................................................................................................................9 Maintenance.................................................................................................................................................. 10 Troubleshooting & Service ......................................................................................................................................................................10 Please contact us for any service related issues. ......................................................................................................................................10 Warranty and Customer Service............................................................................................................... 10 Limited Warranty.....................................................................................................................................................................................10 Technical Support....................................................................................................................................................................................10 Figures Figure 1: SPD Types..................................................................................................................................................................................5 Figure 2: DIMENSIONS AND WEIGHT.........................................................................................................................................................5 Figure 3: Optional Flush Mount Installation...............................................................................................................................................6 Figure 4: Conduit Installation....................................................................................................................................................................7 Figure 5: Typical Panel Installation............................................................................................................................................................7 Figure 6: Installation Wiring Diagrams.......................................................................................................................................................8 Figure 7: Diagnostic Display......................................................................................................................................................................9 Figure 8: Dry Contact Pin Configuration....................................................................................................................................................9 Tables 1: Specifications .Table ...............................................................................................................................................................................................................5 Table 2: Model number decoder...............................................................................................................................................................6 Introduction Thank you for choosing Siemens TPS3 Surge Protective Device (SPD). This is a high quality, high energy surge suppressor designed to protect sensitive equipment from damaging transient overvoltages. Proper installation is important to maximize performance. Please follow the steps outlined herein. This entire user manual should be read prior to beginning installation. These instructions are not intended to replace national or local codes. Follow all applicable electrical codes to ensure compliance. Installation of this SPD should only be performed by qualified electrical personnel. All Siemens SPDs are extensively tested in accordance with industry standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62, C62.72, UL 1449, UL 1283, IEC 61643, etc. Warning and Safety Information This equipment contains hazardous voltages. Death, serious injury, or property damage can result if safety instructions are not followed. Only qualified personnel should work on or around this equipment after becoming thoroughly familiar with all warnings, safety notices, and maintenance procedures contained herein. The successful and safe operation of this equipment is dependent upon proper handling, installation, operation, and maintenance. Qualified Person For the purposes of this manual and product labels, a QUALIFIED PERSON is one who is familiar with the installation, construction, and operation of this equipment, and the hazards involved. In addition, he or she has the following qualifications: (a) Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices. (b) Is trained in the proper care and use of personal protective equipment (PPE) such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc. in accordance with established safety practices. (c) Is trained in rendering first aid. Danger For the purposes of this manual and product labels, DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury. Warning For the purposes of this manual and product labels, WARNING indicates failure to following these instructions can result in death, serious injury, or equipment damage. Caution For the purposes of this manual and product labels, CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. These instruction do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be required by the user, please call Siemens TPS Tech Support at 1.888.333.3545 for assistance. Do Not Hi-Pot Test SPDs Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high-potential testing and then reconnected after test completion. Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void the warranty. Industry Standards Changes - 2009 UL 1449 Third Edition and 2008 NEC® Article 285 generated substantial changes. • The term TVSS changed to SPD • Types 1, 2, 3 & 4 SPDs are created • UL 1449 clamping voltage performance testing changed from 500A to 3,000A • UL 1449 added new I nominal testing (In), which consists of more rigorous duty-cycle testing The SPD Type category is important to understand before installing any SPD. Type 1 and 2 SPDs are fully UL Listed devices whereas Type 4 SPDs are UL Recognized devices. Type 1 – Installed on line or load side of the Main Overcurrent Protection (OCP), similar to what you knew as SSA, except now includes rigorous safety testing. Includes all OCP & safety disconnectors inside the SPD Type 2 – Installed on load side of the Main OCP, similar to what you know as hardwired SPD, and it may require external OCP. Type 3 – Point of Utilization, direct plug in type devices, similar to what you know as surge strips. Theses devices are intended for installation 10 meters from the panel (rational based on IEEE Cat. A location). Type 4 – Surge suppression components, could be a basic component or a complete module. Type 4 components can be tested for Type 1, Type 2 or Type 3 applications. Figure 1: SPD Types 2008 NEC Art 285 & UL 1449-3 SPD Types: Types 1, 2, 3, & 4 Based on Location within electrical distribution system (also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B &A) For further information, please review latest editions of NEC® Art. 285, UL 1449, contact your local Siemens sales office or contact Siemens TPS Tech Support at 1.888.333.3545. This device features internal overcurrent and overtemperature protection that will disconnect effected surge suppression components at the end of their useful life, but will maintain power to the load – now unprotected. If this situation is undesirable for the application, follow these instructions for replacing the device. TPS3 11 is ultrasonically welded closed and contains no user serviceable parts. The TPS3 11 is a Type 1 SPD. The TPS3 11 is suitable for use almost anywhere (not as a plug-in SPD). Type 1 SPDs are evaluated more rigorously by UL 1449 for 2008 NEC® Article 285 compliance. Type 1 SPDs and their connecting leads have been evaluated for line side Table 1: Specifications applications without need for supplemental overcurrent protection. Specifications Type 1 SPDs include internal overcurrent protection. As a generalization, there are practical maintenance reasons for installing on the load side of Temperature Operating the main overcurrent device (i.e. Type 2 installation). When connected Temperature Storage on load side of main disconnect, we recommend connecting via a 30A circuit breaker due to 10 AWG conductors. The circuit breaker serves as Wire Size & Installation Torque a disconnect switch and provides NEC® imposed short circuit protection Appropriate Circuit Breaker to the conductors in Type 2 or 4 applications. based on conductor size Simplified Explanation of Operation NEMA 250 Enclosure Rating -40oC (-40oF) to 60oC (+140oF) -55oC (-67oF) to 65oC (+149oF) 10 AWG; 18 inch-pounds 30A (SPD includes internal OCP) Type 4X with appropriate sealing & sealing condulets SPDs sense overvoltage and create a momentary short circuit to redirect Voltage Rating & Application harmful surge energy to earth ground. SPD’s are not a one time device. They reset automatically and wait for the next surge. SPDs are capable Before installing SPD, verify by nameplate voltage or model number of repeating this function thousands of times. that it has the same voltage rating as the power distribution system. If unsure call Siemens TPS Tech Support at 1.888.333.3545 before Parts List and Inspection proceeding. The SPDs specifier or user should be familiar with the configuration and arrangement of the power distribution system. The Items included in the package consist of the following: system is defined by how the secondary windings of the transformer • 1 TPS3 11 SPD including 3’ (~1m) conductors supplying the service entrance main or load are configured. This • 1 User’s Manual (this document) includes whether or not the transformer windings are referenced to earth via a grounding conductor. The system configuration is not based If the Flush Mount Kit was ordered, additional parts are supplied as on how any specific load or equipment is connected to a particular follows: power distribution system. SPDs should be installed per the distribution • 1 Flush Mount Plate system, not per a load or motor’s wiring connection. • 1 Flush Mount Installation Instructions • 4 Mounting Screws For example, suppose a 480V three phase motor appears to be Carefully inspect each item in the package for signs of damage. If damage is found, please contact Siemens TPS Technical Support: 1.888.333.3545. For more information about this product or other Siemens products, visit www.sea.siemens.com. Figure 2: DIMENSIONS AND WEIGHT connected as a 480V Delta. In actuality, the serving distribution system might be a 480Y/277V grounded Wye, with or without a neutral pulled to the motor or MCC. The system is still a 480Y/277V Wye, even though the load is connected as a Delta. A grounded Wye has a defined reference to ground (i.e., neutral is bonded to ground). In contrast, some Delta systems are ungrounded, which have no reference to ground. Table 2: Model number decoder TPS3 11’s have demonstrated 200kA Short Circuit Current Ratings (SCCR) including leads (120/240V Split phase models have 100kA SCCRs). See UL Label markings on SPD or see Data Sheet for specs.) Supplemental overcurrent protection is not required to protect this SPD. However, NEC® convention requires that connecting conductors have overcurrent protection in Type 2 or 4 applications. Follow applicable codes. Model Voltage Code Service Voltage TPS3A11 TPS3B11 TPS3C11 TPS3D11 TPS3E11 TPS3F11 TPS3G11 TPS3K11 TPS3L11 TPS3S11 A B C D E F G K L S 240/120V 1Ø, 3W Plus Ground, 240/120V 3Ø, 4W Plus Ground High Leg Delta 208Y/120V 3Ø, 4W Plus Ground 240v 3Ø, 3W Plus Ground 480Y/277V 3Ø, 4W Plus Ground 480v 3Ø, 3W Plus Ground 600v 3Ø, 3W Plus Ground 380Y/220V 3Ø, 4W Plus Ground 600Y/347V 3Ø, 4W Plus Ground 400Y/230V 3Ø, 4W Plus Ground SPDs on Ungrounded Systems Caution – Ungrounded systems are inherently unstable and can produce excessively high line-to-ground voltages during certain fault conditions. During these fault conditions, any electrical equipment including an SPD, may be subjected to voltages which exceed their designed ratings. This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an ungrounded power system. Alternate Installation - Front Flange Mounting: This method is not preferred for installation as servicing is substantially more difficult. Extra care should be taken to NOT DROP the TPS3 unit into the wall. Mount as close as possible to the protected panel. Create a wall opening approximately 6 3/4” tall by 6 1/16” wide. See drawing. (Rotate dimensions 90o as appropriate depending on orientation.) Preplan and pre-connect electrical conductor and conduit connections such that they are completed prior to fastening the TPS3 unit to the wall. Note that removing the four screws attaching the front faceplate to the unit chassis will cause the unit to fall inside the wall. Optional Flush Mount Installation Instructions UL 1283 required language concerning the installation of EMI Filters Caution: The chassis of the TPS3 11 unit can fall into the wall cavity if the four screws attaching the faceplate to the chassis are removed. Use caution not to drop the TPS3 11 unit into the wall during installation or service. The TPS3 11 unit is approximately 4.0” deep. The unit will not mount flush unless there is at least 3.75” of clearance. The unit is designed to mount flush on a typical “2 x 4” stud wall with drywall. Depending on the depth of the wall cavity, there are two installation procedures. The preferred installation utilizes Back Flange Mounting. The back flange supports the weight of the TPS3 unit and service procedures are greatly simplified. If this can not be accomplished, an alternate Front Flange Mount is possible. Please note that the front flange installation may create servicing difficulties in the future. Preferred Installation - Back Flange Mounting: Mount as close as possible to the protected panel. Create a wall opening approximately 6 3/4” tall by 6 1/16” wide. See drawing. (Rotate dimensions 90o as appropriate depending on orientation.) Configure an appropriate backing plate inside the wall cavity 3 7/8” from the wall face such that the unit will be supported from its back. Note the mounting holes on the back flange attachments. Be careful not to drop the unit into the wall. Configure electrical conductor and conduit connection consistent with the installation instructions on page 5. Preplan connections such that they are completed prior to fastening the unit to the backing plate. Install faceplate/cover prior to energizing and testing the unit. a) An insulated grounding conductor that is identical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors, except that it is green with or without one or more yellow stripes, is to be installed as part of the circuit that supplies the filter. Reference should be made to Table 250-122 of the National Electrical Code regarding the appropriate size of the grounding conductor. b) The grounding conductor mentioned in item a is to be grounded to earth at the service equipment or other acceptable building earth ground such as the building frame in the case of a high-rise steel-frame structure. c) Any attachment-plug receptacles in the vicinity of the filter are to be of a grounding type, and the grounding conductors serving these receptacles are to be connected to earth ground at the service equipment or other acceptable building earth ground such as the building frame in the case of a high-rise steel-frame structure. d) Pressure terminal or pressure splicing connectors and soldering lugs used in the installation of the filter shall be identified as being suitable for the material of the conductors. Conductors of dissimilar metals shall not be intermixed in a terminal or splicing connector where physical contact occurs between dissimilar conductors unless the device is identified for the purpose and conditions of use. Figure 3: Optional Flush Mount Installation Supplemental Instructions for Deep Wall Mounting (Walls over 4” thick) Using the Enclosed Mounting Feet Flush Mount “F Option” (Preferred Installation) Supplemental Installation Instructions for Deep Wall Mounting (Walls over 4” thick) Using the Enclosed Mounting Feet Wall Cutout Front View Step 1 Prepare Wall and SPD 6 Step 2 Insert into Wall Step 3 Mount the SPD Step 4 Mount the Lid 6 1/16” Wide 6 3/4” Tall V DANGER V CAUTION Hazardous voltage. Will cause death or serious injury. CONDUCTING DIELECTRIC AND/OR HI-POTENTIAL TESTING WILL CAUSE INTERNAL DAMAGE TO TPS3 UNIT. Keep Out. Qualified personnel only. Disconnect and lock off all power before working on this equipment. Do not perform dielectric or high potential tests with the TPS3 unit installed. TPS3 11 Installation Instructions Figure 4: Conduit Installation Common Problems to Avoid • Confirm System voltage to SPD voltage (120V SPD will fail instantly on 240V, 277V, etc.) • Locate SPD close so leads are short & straight as possible (or will seriously hurt performance) • Make sure N-G or XO bonding meets NEC® (or will prematurely fail SPD) • Energize SPD AFTER system is stabilized & checked (inadvertent system problem may fail SPD) • SPDs are regulated by NEC®Article 285 and UL 1449 • Never Hi-Pot test any SPD (will prematurely fail SPD) Pre-Plan your installation. You will need to accomplish the following: • Meet all National and Local codes (NEC® Article 285 addresses SPDs) • Mount SPD as close to panel or equipment as possible to keep leads short • Ensure leads are as short and straight as possible, including neutral and ground. Consider a breaker position that is closest to the SPD and the panel’s neutral & ground • Suggested breaker & conductor size is 50A-30A with 8 AWG • Make sure system is grounded per NEC® and clear of faults before energizing SPD. INCORRECT INSTALLATIONS OVERTIGHTENED Stresses box, ONLY 6 full turns required POOR ENGAGEMENT Conduit needs to be threaded in farther Figure 5: Typical Panel Installation To Protected Loads A B C BREAKER N Use closest breaker to SPD Locate SPD close to intended breaker • • Keep Leads Short as Possible Avoid Sharp Bends V DANGER Hazardous Voltage will cause severe injury or death. WWW.SIEMENS.COM • TYPE 1 SURGE PROTECTIVE DEVICE 1-888-333-3545 Turn off power before removing cover. Note that any conduits must be installed correctly. CAUTION Conducting dielectric and/or hi-potential testing will cause internal damage to the unit. Do not perform any tests while installed. A sealing O-ring is provided. SPD can be chase-nipple mounted (nut is provided). • • G SERVICE 1. Use a voltmeter to check all voltages to ensure correct SPD 2. If unit has Flush Mount option refer to Flush Mount Installation Instructions following 3. If SPD has Dry Contact pre-plan its installation 4. Remove power for panel. Confirm panel is deenergized. 5. Identify breaker location and SPD location 6. Remove an appropriately sized knockout from panel 7. Mount SPD, use appropriate weatherproofing equipment as needed 8. Connect conductors as appropriate – short and straight as possible (Note that Hi-Legs are Phase B) 9. Label or mark conductors as appropriate (neutral: white, ground: green, energized: black, hi-leg: orange) 10. Make sure system is bonded per NEC® and is clear of hazards or faults before energizing (N-G bonding not per NEC® will fail SPDs: #1 cause of SPD failures) 11. Energize and confirm proper operation of indicators and/or options CORRECT INSTALLATION Threaded 6 Full Turns • Rotate TPS3 11 such that LED indicator is most visible Outdoor installation requires appropriate weather sealing at nipple (o-ring, sealing conduit, etc.) 7 Figure 6: Installation Wiring Diagrams THREE POLE TWO POLE DRY CONTACTS DRY CONTACTS }V }V NO Hot (BLK) C NO NC A Phase A (BLK) C Neutral (WHT) Hot (BLK) Ground (GRN) SPLIT 2 Hots, 1 Neu, 1 Grnd A N SERVICE N C G A B Phase B (BLK) A C } Neutral (WHT) V Phase C (BLK) A N Ground (GRN) SERVICE WYE 3 Hots, 1 Neu, 1 Grnd } NO A G DRY CONTACTS NO NC } C V Phase C (BLK) Neutral (WHT) Ground (GRN) HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd 8 C B A SERVICE N B C C B DRY CONTACTS V NC THREE POLE THREE POLE Phase A (BLK) Phase B (ORNG) C B C Phase A (BLK) Phase B (BLK) Phase C (BLK) G Ground (GRN) A A SERVICE DELTA & HRG WYE 3 Hots, 1 Grnd C B N B NC C C G Operation Dry Contact Option Diagnostic Indication Two sets of Form C dry contacts are included with the Dry Contact option. Dry Contacts change state during inoperative conditions, including loss of power. Any status change can be monitored elsewhere via Dry Contacts. Phase indicator LEDs (Green) Each phase is equipped with a Green LED. Should complete loss of surge protection occur on each phase, the Green LED will extinguish and the Red Service LED will flash. Every suppression element is monitored. Note that the Green LED indicators will drop out due to loss of power or severe under voltage. A Terminal Block includes two sets of Normally Open (N.O.) and Normally Closed (N.C.) contacts. Both sets of contacts operate the same. This is shown in Figure 8. Figure 8: Dry Contact Pin Configuration Service LED (Red) Flashes in the event of a problem. The Red Service LED is slaved to the Green LEDs via logic and will illuminate when any Green LED extinguishes. Audible Alarm Option If equipped with optional Dry Contact and Audible Alarm, these options are slaved via logic to the Green LEDs. In the event of a problem, the dry contacts will chage state and the audible alarm will sound. The audible alarm may be silenced by deenergizing the SPD. A typical application using a Normally Closed configuration would connect to one set of the N.C. and Common terminals. During an inoperative condition, the SPDs dry contact would change state from normally closed to open. We generally suggest the Normally Closed configuration because it will detect a wiring defect, such as cut wire(s), where N.O. will not. Figure 7: Diagnostic Display Please note: Dry Contacts are designed for low voltage or control signals only. TYPE 1 SURGE PROTECTIVE DEVICE 1-888-333-3545 SERVICE CAUTION Conducting dielectric and/or hi-potential testing will cause internal damage to the unit. Do not perform any tests while installed. WWW.SIEMENS.COM V DANGER Hazardous Voltage will cause severe injury or death. Turn off power before removing cover. Maximum switching current is 5A Maximum switching voltage is 240V DC or AC. Higher energy applications require additional relay implementation outside the SPD. An optional Remote Monitor accessory is available to provide visual and audible status. The Remote Monitor will consume one of the two sets of Dry Contacts. Remote Monitor Accessory Option A Remote Monitor is available for remote annunciation. It requires a standalone 120V power source (wall plug transformer) and uses one set of Form C dry contacts. The Remote Monitor can be configured to monitor several Siemens TPS3 SPDs simultaneously. Installation is detailed in a separate document. Contact factory as appropriate. 9 V DANGER V CAUTION Hazardous voltage. Will cause death or serious injury. CONDUCTING DIELECTRIC AND/OR HI-POTENTIAL TESTING WILL CAUSE INTERNAL DAMAGE TO TPS3 UNIT. Keep Out. Qualified personnel only. Disconnect and lock off all power before working on this equipment. Do not perform dielectric or high potential tests with the TPS3 unit installed. Maintenance Warranty and Customer Service SPDs require minimal maintenance. Periodic inspection of diagnostic indicators is recommended to ensure proper operation. Limited Warranty Troubleshooting & Service Please contact us for any service related issues. Quality SPDs withstand severe duty and attempt to protect their load until failure. There are electrical anomalies that SPDs cannot protect against. These are generally Sustained Overvoltages also known as Temporary Overvoltages (TOVs). In this context, Sustained Overvoltages may be only a few cycles. Failed SPDs tend to be symptoms, not root causes. A failed SPD is usually a sign of other problems within the electrical distribution system. As a generalization, the single largest cause of SPD failures is reference to ground issues. If the SPD shows problems on startup, there is reasonable chance of bonding/grounding/misapplication issue. This permanently damages the unit. If not corrected, it will happen again. Siemens warrants its AC Panel protection products against defective workmanship and materials for 10 years. Liability is limited to the repair or replacement of the defective product at Siemens’ option. A Return Material Authorization number (RA#) must be given by the company prior to the return of any product. Returned products must be sent to the factory with the transportation charges prepaid. In addition, the company also warranties unlimited replacement of modular and component parts within the warranty period previously described. The company specifically disclaims all other warranties, expressed or implied. Additionally, the company is not be responsible for incidental or consequential damages resulting from any defect in any product or component thereof. The sales contract contains the entire obligation of Siemens. This instruction manual shall not become part of or modify any prior existing agreement, commitment or relationship. Technical Support 1.888.333.3545 Prior to calling Siemens TPS3 Technical Support for assistance or ordering parts, please have the following information available: TPS3 model number: ________________________________ Manufacture date: _________________________________ Date of Purchase: ___________________________________ Your order number: _______________________________ Return Shipment Address: Siemens - Attn: RA #___________ 14550 58th Street North Clearwater, FL 33760 10 11 Siemens Industry, Inc. Building Technologies Division 5400 Triangle Parkway Norcross, GA 30092 888-333-3545 info.us@siemens.com 8.9.10.al #8174
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes XMP Toolkit : Adobe XMP Core 5.0-c060 61.134777, 2010/02/12-17:32:00 Create Date : 2010:08:09 12:19:04-04:00 Metadata Date : 2010:08:09 12:19:19-04:00 Modify Date : 2010:08:09 12:19:19-04:00 Creator Tool : Adobe InDesign CS5 (7.0) Page Image Page Number : 1, 2 Page Image Format : JPEG, JPEG Page Image Width : 256, 256 Page Image Height : 256, 256 Page Image : (Binary data 7517 bytes, use -b option to extract), (Binary data 10156 bytes, use -b option to extract) Instance ID : uuid:b58f91f9-5fb7-44a7-b88c-e1f7f95cf0bd Document ID : adobe:docid:indd:0e099ab3-b27d-11de-b080-f21c1f6c4951 Original Document ID : adobe:docid:indd:0e099ab3-b27d-11de-b080-f21c1f6c4951 Rendition Class : proof:pdf Derived From Instance ID : 0e099ab2-b27d-11de-b080-f21c1f6c4951 Derived From Document ID : adobe:docid:indd:7292db27-ae8f-11de-9f30-876077c84e3c History Action : saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved History Instance ID : xmp.iid:76C0C40FF4E4DE1192F4C878A158702F, xmp.iid:77C0C40FF4E4DE1192F4C878A158702F, xmp.iid:78C0C40FF4E4DE1192F4C878A158702F, xmp.iid:79C0C40FF4E4DE1192F4C878A158702F, xmp.iid:9E2BD321F6E4DE1192F4C878A158702F, xmp.iid:9F2BD321F6E4DE1192F4C878A158702F, xmp.iid:A02BD321F6E4DE1192F4C878A158702F, xmp.iid:A32BD321F6E4DE1192F4C878A158702F, xmp.iid:A42BD321F6E4DE1192F4C878A158702F, xmp.iid:19BE80E2E9FEDE119D28DD46906072DD, xmp.iid:1ABE80E2E9FEDE119D28DD46906072DD, xmp.iid:1712C03D580CDF11A2E3EF7518F816F3, xmp.iid:C70DA52EBE1FDF119343A3DF5B0C8014, xmp.iid:4E2DCF7DCFA3DF11B91ADA954BFDD125, xmp.iid:4F2DCF7DCFA3DF11B91ADA954BFDD125, xmp.iid:D11D32D0D1A3DF11B91ADA954BFDD125 History When : 2009:12:09 13:53:30-05:00, 2009:12:09 13:53:30-05:00, 2009:12:09 13:55:45-05:00, 2009:12:09 13:57:48-05:00, 2009:12:09 14:21:34-05:00, 2009:12:09 14:21:57-05:00, 2009:12:09 14:23:55-05:00, 2009:12:09 14:42:50-05:00, 2009:12:09 14:44:21-05:00, 2010:01:11 15:50:06-05:00, 2010:01:11 15:51:32-05:00, 2010:01:28 17:00:34-05:00, 2010:02:22 09:29-05:00, 2010:08:09 12:02:20-04:00, 2010:08:09 12:02:20-04:00, 2010:08:09 12:18:58-04:00 History Software Agent : Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0 History Changed : /, /metadata, /, /, /, /, /, /, /, /, /, /, /, /;/metadata, /metadata, /;/metadata Doc Change Count : 176 Format : application/pdf Producer : Adobe PDF Library 9.9 Trapped : False Page Count : 12 Creator : Adobe InDesign CS5 (7.0)EXIF Metadata provided by EXIF.tools