Simplex Time Recorder 31032021330 Wireless Alarm Transceiver User Manual 330 fire transmitter

Simplex Time Recorder Company Wireless Alarm Transceiver 330 fire transmitter

Users Manual

P/N 330.MAN Rev. 1.0   2006 Commercial Wireless Systems International, LLC 1  Fire Transmitter Model 330  Description: The model 330 fire transmitter is a UL864 listed device specifically designed for connection to a normally open dry contact output. The input is selectable for two types of supervised wiring configurations referred to as Style 1 or Style 2 in this manual. The transmitter is fully supervised for tamper, low battery, RF signal integrity and wiring faults. The transmitter is powered by a single 3 volt lithium battery as listed under the specifications section of this manual  and  the  label  on  the  product.  The  model  330  is  intended  to  be  used  with Commercial Wireless Systems International, LLC Model CP-3000 Fire Alarm Control Panel. Refer  to  the  CP-3000  FACP  installation  instructions,  part  number  3000.MAN  Rev.  1  for additional details.  Programming: The 330 must be enrolled into the CP-3000 control panel before installing the device. The Model 330 will not report Alarms, Supervisory or trouble signals unless it is enrolled into the CP-3000 control panel. Enrollment must be performed while in front of the CP-3000 FACP. Place  the  CP-3000 FACP in enrollment  mode then install  the  battery in the model  330  transmitter  observing  polarity  marked  on  the  battery  holder.  The  model  330 serial  number  will  be displayed  on  the  CP-3000  FACP along  with programming  options. Refer to the CP-3000 control panel installation instructions for further details on enrollment and transmitter programming options. After the model 330 is enrolled, remove the battery and reinstall it only at the transmitters mounting location.  Installation: Select  an  accessible  location  that  is  not  prone  to  tampering  or  accidental  damage The mounting surface should be relatively flat and capable of accepting screws or anchors. The 330 is to be installed in an indoor dry location. Exposure to weather or corrosive conditions may damage the unit. It must be mounted on a vertical surface so that the CWSI label can be read correctly. Perform the signal test described in this manual prior to and after permanently mounting the unit. An 18 gage copper wire pair should be used to connect the  330 to  the  dry contacts  to  be  monitored.  Wire  runs  should  be  as  short  as  possible, contained within one room and not routed near fluorescent lighting or equipment generating electrical noise such as  generators, air conditioners, etc. The wires should enter the 330 through the hole provided near the screw terminal block. Under no circumstances are the wires to be run near or draped over the printed 330 printed circuit board. Style 1 or Style 2 wiring  can  be  selected  with  SW2  on  the  board.  Refer  to  figure  2  for  proper wiring connection. When Style 2 wiring is selected, the Model TR-3 EOL resistor provided must be connected either as recommended by the manufacturer of the device being monitored or directly  across  the dry  contact  terminals  of  the  of  the  monitored  device.  Multiple  sets  of contacts on the monitored equipment may be wired in parallel and connected to a single 330. Caution: only one monitored device may be connected to a single Model 330.  After  connecting  the wires  to the  terminal block,  install  the battery, mount  the  enclosure back on the wall using the keyholes then push the front portion of the enclosure onto the back until the case snaps closed. Be careful not to bend the transmitter’s antenna. Perform the Signal Test and Alarm Test as outlined in this manual.  P/N 330.MAN Rev. 1.0   2006 Commercial Wireless Systems International, LLC 2 Cautions: 1. Make sure the battery is firmly installed in the battery clip. 2. The unit must be secured tightly to the wall, so as to not be dislodged. 3. Test the unit after any service or battery change or as often as local or national codes dictate.   Following the codes: The Model 330 must be installed and maintained in accordance with the National Fire Protection Association’s Standards (NFPA), the National Electrical Code and all local fire  and  electrical  requirements.  When  connecting  to other equipment,  follow  the instructions and recommendations of that manufacturer.  Alarm Operation: When the wires of the model 330 are shorted:  1. An initial alarm signal is transmitted. 2. A 30 second delay occurs. If during this delay the alarm condition is reset and the alarm cycle is ended. 3. A continued alarm condition causes a repeat alarm transmission. 4. Another 30 second delay as in step 2 occurs. 5. A continued alarm condition causes a repeat alarm transmission. 6. Step 5 repeats at 60 second intervals until reset.  LED: The LED will flash when any signal is sent from the transmitter.  Alarm Test: Before testing, notify the proper authorities that maintenance is being performed  and  the system will be temporarily out of service. Activate the dry contact output being monitored by the Model 330 transmitter or manually short the wires to simulate dry contact closure. Verify an alarm is received at the control panel.  Signal Test: The test must be performed while the transmitter is held in its intended mounting location. Initiate  the test  by placing  a strong  magnet along  the  upper  right  side of  the transmitter case (figure 1). The model 330 piezo sounder will beep twice if the transmitter is located within acceptable  reception range of  a  repeater or CP-3000 FACP. If two beeps  are not heard within 5 seconds of initiating the signal test then relocate the model 310 mounting position closer to the nearest repeater or control panel and perform the test again. Continue this procedure until 2 beeps are achieved. Do not mount the transmitter unless 2 beeps are heard  when  performing  the  signal  test.  This  test must  be  performed  before  and  after transmitter  installation.  Note:  A  CWSI  model  AR-3 repeater  or  Control  Panel  must  be installed and turned on before running this test.             Low battery: The  battery  voltage  is  periodically  tested  under  load.  In  the  event  that  a  low  battery  is detected, a low battery signal will be sent immediately and repeated every 90 seconds for a minimum of seven days. Where more than one type of trouble exists, all will be repeated every 90 seconds.   Battery Installation and Replacement: Warning: Always install a new battery of one of the approved types as listed in the Specifications  section  of  this  manual  and  the  product  label. When  a  battery  is  first inserted, a low battery test is performed. If the battery passes the test, The unit should not send a low battery signal. If the battery does not pass this test, the unit will continue to send a low battery until a good battery is installed.
P/N 330.MAN Rev. 1.0   2006 Commercial Wireless Systems International, LLC 3   To replace the battery:  1. Place the CP-3000 Control Panel in Test mode to prevent any unwanted alarms. (Refer to the CP-3000 manual)  2. Open the transmitter’s case by holding and pulling the front of the case away from the mounting surface. The back will remain on the wall. A tamper signal will be transmitted. The battery will now be exposed. Remove the battery and dispose of properly.   3. To insure proper power down sequence, wait a minimum of 20 seconds before installing a new battery.  4.  Install  a  new  approved  3  volt  lithium battery  in  the  battery  compartment  following  the polarity diagram inside  the compartment.  A  tamper trouble signal  should be indicated on the CP-3000 Control Panel upon installation of the new battery.  5. Close the transmitter case by pushing the front onto the back. Make sure excess wire does not lie onto the transmitter board. There should be no gaps where the front and back case sections meet.   6. Test the Model 330 as described in Alarm Testing section.   7. If the Model 330 does not function for alarm testing as described in item 6 then start over at step 2. If it still doesn’t operate correctly then replace the entire unit.  8. Remove the panel from test mode. (Refer to the CP-3000 manual)  Tamper: The Model 330 has an on board tilt sensor that will cause a tamper signal to be transmitted if  the  330  case  is  opened  or  removed  from  its  mounting  position.  Upon  detection  of  a tamper,  a trouble  signal  is  sent immediately and  repeated  every  90  seconds  until  the condition is restored. Where more than one type of trouble exists, all will be repeated within 90 seconds.   EOL/Wiring Fault Trouble: If the wiring from the Model 330 to the monitored device opens preventing the EOL from being  detected  in  Style  2 wiring configuration  or  if  any  of  the  wires  in  the  Style  1 configuration is disconnected, a trouble signal will be sent and repeated every 90 seconds. Where more than one type of trouble exists, all will be repeated within 90 seconds.                                           P/N 330.MAN Rev. 1.0   2006 Commercial Wireless Systems International, LLC 4 330 MOUNTING   Figure 1
P/N 330.MAN Rev. 1.0   2006 Commercial Wireless Systems International, LLC 5330 WIRING DIAGRAM Figure 2  P/N 330.MAN Rev. 1.0   2006 Commercial Wireless Systems International, LLC 6 Specifications: Battery  Type:  3  Volt  Lithium;  Duracell  DL123A,  Sanyo  CR123A,  Panasonic CR123A. Battery Life: 12 Months Minimum Battery  Replacement:  Upon  Low  battery  report  and/or  during  annual maintenance. Operating Temperature Range: 0C to +49 C. Operating Humidity Range 0 to 95% RH. Testing: Follow this manual and NFPA 72 or local requirements. Transmission:  In  compliance  with  FCC  part  15  for  reception  on  equipment manufactured by Commercial Wireless Systems International, LLC. Test Transmission: Every 90 seconds. Compatibility: Commercial Wireless Systems International, LLC Model CP-3000. Size: 4.75 Inches high, 2.55 Inches wide, 1.58 Inches deep. Weight 6.4 oz. Input Current Rating: 19.1 ua  Normal Supervisory.  25 ua. Alarm. Initiating loop rating: 3 Vdc, 1ma.    FCC Statement  Important: Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment  This device complies with part 15 of the FCC Rules. Operation is subject to the following two  conditions:  (1)  This  device  may  not  cause  harmful  interference,  and  (2)  this  device must  accept  any  interference  received,  including  interference  that  may  cause  undesired operation.
P/N 330.MAN Rev. 1.0   2006 Commercial Wireless Systems International, LLC 7COMMERCIAL WIRELESS SYSTEMS INTERNATIONAL, LLC ONE YEAR LIMITED WARRANTY  Commercial Wireless Systems International, LLC (“Seller”), 10794 N.W. 53 Street, Sunrise, Florida 33351, warrants this product to be free from defects  in  workmanship  for two  years  from  date  of  purchase,  under normal  use  and  service.  Seller’s  obligation  is  limited  to  repairing  or replacing, at it’s option, free of charge for parts and labor any part proven to  be  defective  in  materials  or  workmanship.  Seller  shall  have  no obligation  under  this  warranty  otherwise  if:  (1)  the  product  is  altered, repaired or serviced by anyone other than the seller, (2) the product is damaged from accidents, acts of God, misuse, tampering or abuse, (3) product is not installed and operated in accordance with the instructions provided  by  the  seller.  In  case  of  defect,  contact  the  fire  alarm professional who installed and  maintains  your  fire alarm system or the seller for product repair.  This two year Limited Warranty is in lieu of all other express warranties, obligations,  or  liabilities.  There  are  no  express  warranties  that  extend beyond the face hereof. In no case shall seller  be liable to anyone for any consequential or incidental for breach of this or any other warranty, express or implied, or upon any other basis of liability whatsoever, even if the loss or damage is caused by the seller’s own negligence or fault. Seller shall have no liability for any personal injury, property damage, or other loss based on a claim that the product failed to operate correctly. However, if the seller is held liable, whether directly or indirectly, for any loss or damage arising under this warranty or otherwise, regardless of cause of origin, Seller’s maximum liability shall not in any case exceed the  purchase  price  of  the  product,  and  shall  be  the  complete  and exclusive remedy against the Seller.                  P/N 330.MAN Rev. 1.0   2006 Commercial Wireless Systems International, LLC 8NOTES
P/N 320.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 1  Heat Detector with Transmitter                       Models 320/321  Description: The models 320 and 321 are UL listed combination fixed temperature/rate of-rise sensors with temperature ratings of 135F/57C (Model 320) or 194F/90 (Model 321) and a built in transmitter. These heat detectors are intended for use in property protection applications or for non-life-safety installations where smoke detection is not practical or appropriate. The transmitter  is  fully  supervised  for  tamper, low  battery  and  RF  signal  integrity.  The transmitter is powered by a single 3 volt lithium battery as listed under the specifications section of this manual and the label on the product. The models 320 and 321 are intended to  be  used  with  Commercial  Wireless  Systems  International,  LLC  Model  CP-3000  Fire Alarm  Control  Panel.  Refer  to  the  CP-3000  FACP  installation  instructions,  part  number 3000.MAN  Rev.  1  for  additional  details.  Warning: For  life-safety  installations,  smoke detectors must be used, in lieu of, or in addition to mechanical heat detectors.   Programming: The  320/321  must  be enrolled  into the  CP-3000 FACP  before  installing  the device. The Models 320/321 will not report Alarms or trouble signals unless it is enrolled into the CP-3000  control  panel.  Enrollment  must be  performed  while  in  front  of  the  CP-3000 FACP. Place the CP-3000 FACP in enrollment mode then install the battery in the model 320-321 transmitter observing  polarity marked  on  the battery holder. The model  320/321 serial  number  will  be displayed  on  the  CP-3000  FACP  along  with programming  options. Refer to the CP-3000 control panel installation instructions for further details on enrollment and transmitter programming options. After the model 310 is enrolled, remove the battery and reinstall it only at the transmitters mounting location.   Installation: Select  an  accessible  location  that  is  not  prone  to  tampering  or  accidental  damage. The Model 320-321 must be installed and maintained in accordance with the National Fire Protection Association’s Standards (NFPA), the National Electrical Code and all local fire  and  electrical  requirements.  The  mounting  surface  should  be  relatively  flat  and capable of  accepting screws  or  anchors. The  320-321 is  to  be installed in an  indoor dry location. Exposure to weather or corrosive conditions may damage the unit. Perform the signal test described in this manual prior to and after permanently mounting the unit. It is acceptable to mount the heat detector on a ceiling tile only if the tile is secured with fasteners  and can  not be  removed  or  the  Heat  Detector is  installed  across  a  ceiling  tile metal support where each mounting screw is attached to separate ceiling tiles (figure 1). Mark  the  mounting  location  using  the  keyholes  in  the  back  box.  Install  screws  and  or anchors. Mount the back box on the screws. Install the battery in the battery holder. Place the front of the unit on the back box and install the closing screws. Be careful not to bend the  transmitter’s  antenna.  Perform  the  Signal Test  and  Alarm  Test  as  outlined  in  this manual.     P/N 320.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 2Cautions: 1. Make sure the battery is firmly installed in the battery clip. 2. The unit must be secured tightly to the mounting surface, so as to not be dislodged. 3. Test the unit after any service or battery change or as often as local or national codes dictate.  Alarm Operation: If either the fixed temperature or Rate of Rise Sensor is activated, the following will occur: 1. An initial alarm signal is transmitted. 2. A 30 second delay occurs. The alarm cycle is ended if the heat sensor is restored during the 30 second delay. 3. The continued alarm condition causes a repeat alarm transmission. 4. Another 30 second delay as in step 2 occurs. 5. The continued alarm causes a repeat alarm transmission. 6. Step 5 repeats at 60 second intervals until reset.  LED: The LED will flash when any signal is sent from the transmitter.  Alarm Test: The rate-of-rise mechanism may be subject to reduced sensitivity over time. Annual testing of  the  rate-of-rise  operation  is  therefore  recommended.  Before  testing,  notify  the  proper authorities that maintenance is being performed and the system will be temporarily out of service. Warning: Only  the  Rate  of  Rise  elements  of  320-321  models  are  self-restoring, and may be tested using a hair dryer or heat gun. When testing the ROR element, to prevent the activation of the fixed temperature element, the heat source must not exceed the fixed temperature rating of the detector. If the fixed temperature element is tripped, the heat detector sensor will need replacement. Activate the ROR element and verify an alarm is received at the control panel.  Heat Detector Sensor Replacement If the fixed temperature element is tripped the heat sensor will need replacement. Contact an authorized dealer or Commercial Wireless Systems International, LLC for a replacement sensor. Order p/n 20FR for the model 320 and p/n 21FR for the model 321.   To Replace the Sensor:  1. Place the CP-3000 Control Panel in Test mode to prevent any unwanted alarms. (Refer to the CP-3000 manual)  2. Open the Heat Detector case by removing the four screws holding it closed. A tamper signal will be transmitted. Separate the front from the back to expose the battery. Remove the battery.   3. Turn  the  heat  sensor  ¼  turn  counter-clockwise  to  expose  the  heat  sensor  wires. Disconnect the wires and resistor. Do not discard the resistor.   4. Reattach the wires and resistor to a new temperature sensor. Attach the sensor to its base by turning it ¼ turn clockwise.   5. Replace the battery and close the Heat Detector case with the four screws. Test the unit as described in Alarm Testing.  6. If the Heat Detector does not function for alarm testing as described in item 5 then start over at step 2. If it still doesn’t operate correctly then replace the entire unit.  7. Remove the panel from test mode. (Refer to the CP-3000 manual)
P/N 320.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 3Signal Testing: The  test  must  be  performed  while  the  heat  detector  is  held  in  its  intended  mounting location.  Initiate  the  test  by  placing  a  strong  magnet  along  the  middle  left  side  of  the 320/321 case (figure 2). The model 320/321 piezo sounder will beep twice if the transmitter is located within acceptable range of a repeater  or CP-3000 FACP. If two beeps are not heard within 5 seconds of initiating the signal test then relocate the model 310 mounting position closer to the nearest repeater or control panel and perform the test again. Continue this procedure until 2 beeps are achieved. Do not mount the transmitter unless 2 beeps are heard  when  performing  the  signal  test.  This  test must  be  performed  before  and  after transmitter installation. Note: A CWSI model AR-3 repeater or CP-3000 Control Panel must be installed and turned on before running this test.  Low battery: The  battery  voltage  is  periodically  tested  under  load.  In  the  event  that  a  low  battery  is detected, a low battery signal will be sent immediately and repeated every 90 seconds for a minimum of seven days.  Where more than one type of trouble exists, all will be repeated in increments of 90 seconds.   Battery Installation and Replacement: Warning: Always install a new battery of one of the approved types as listed in the Specifications  section  of  this  manual  and  the  product  label.  When  a  battery  is  first inserted, a low battery test is performed. If the battery passes the test, The unit should not send a low battery signal. If the battery does not pass this test, the unit will continue to send a low battery until a good battery is installed.  To replace the battery:  1. Place the CP-3000 Control Panel in Test mode to prevent any unwanted alarms. (Refer to the CP-3000 manual)  2. Open the Heat Detector case by removing the four screws holding it closed. A tamper signal will be transmitted. Separate the front from the back to expose the battery. Remove the battery and dispose of properly.   3. To insure proper power down sequence, wait a minimum of 20 seconds before installing a new battery.  4.  Install  a  new  approved  3  volt  lithium battery  in  the  battery  compartment  following  the polarity diagram inside  the compartment.  A  tamper trouble signal  should be indicated on the CP-3000 Control Panel upon installation of the new battery.  5. Close the Heat detector case and reinstall the four screws.  6. Test the Heat Detector as described in Alarm Testing section.   7. If the Heat Detector does not function for alarm testing as described in item 6 then start over at step 2. If it still doesn’t operate correctly then replace the entire unit.  8. Remove the panel from test mode. (Refer to the CP-3000 manual)  Tamper: The Model 320-321 contains two tamper switches. One monitors opening of the case and the other one monitors device for removal from its mounting position. Upon detection of a tamper from either switch, a tamper signal is sent and repeated every 90 seconds until the condition is restored. Where more than one type of trouble exists, all will be repeated within 90 seconds. P/N 320.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 4  ACCEPTABLE MOUNTING TO CEILING TILE           Figure 1        Figure 2
P/N 320.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 5       P/N 320.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 6 Specifications: Battery  Type:  3  Volt  Lithium;  Duracell  DL123A,  Sanyo  CR123A,  Panasonic CR123A. Battery Life: 12 Months Minimum Battery  Replacement:  Upon  Low  battery  report  and/or  during  annual maintenance. Operating Temperature Range: 0C to +38 C. Operating Humidity Range 5 to 95% RH non-condensing. Testing: Follow this manual and NFPA 72 or local requirements. Transmission:  In  compliance  with  FCC  part  15  for  reception  on  equipment manufactured by Commercial Wireless Systems International, LLC. Test Transmission: Every 90 seconds. Compatibility: Commercial Wireless Systems International, LLC Model CP-3000. Size: 4.57 Inches high, 4.57 Inches wide, 3.25 Inches deep. Weight 6.4 oz. Maximum Installation Temperature Model 320: 100°F (38°C)         Model 321: 150°F (65.6°C) Alarm Temperature: Model 320: 135°F (57°C)  Model 321: 194°F (90°C) Rate-of-Rise Threshold: 15°F (8.3°C) per minute      FCC Statement  Important: Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment  This device complies with part 15 of the FCC Rules. Operation is subject to the following two  conditions:  (1)  This  device  may  not  cause  harmful  interference,  and  (2)  this  device must  accept  any  interference  received,  including  interference  that  may  cause  undesired operation.
P/N 320.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 7 COMMERCIAL WIRELESS SYSTEMS INTERNATIONAL, LLC ONE YEAR LIMITED WARRANTY  Commercial Wireless Systems International, LLC (“Seller”), 10794 N.W. 53 Street, Sunrise, Florida 33351, warrants this product to be free from defects  in  workmanship  for two  years  from  date  of  purchase,  under normal  use  and  service.  Seller’s  obligation  is  limited  to  repairing  or replacing, at it’s option, free of charge for parts and labor any part proven to  be  defective  in  materials  or  workmanship.  Seller  shall  have  no obligation  under  this  warranty  otherwise  if:  (1)  the  product  is  altered, repaired or serviced by anyone other than the seller, (2) the product is damaged from accidents, acts of God, misuse, tampering or abuse, (3) product is not installed and operated in accordance with the instructions provided  by  the  seller.  In  case  of  defect,  contact  the  fire  alarm professional who installed and  maintains  your  fire alarm system or the seller for product repair.  This two year Limited Warranty is in lieu of all other express warranties, obligations,  or  liabilities.  There  are  no  express  warranties  that  extend beyond the face hereof. In no case shall seller  be liable to anyone for any consequential or incidental for breach of this or any other warranty, express or implied, or upon any other basis of liability whatsoever, even if the loss or damage is caused by the seller’s own negligence or fault. Seller shall have no liability for any personal injury, property damage, or other loss based on a claim that the product failed to operate correctly. However, if the seller is held liable, whether directly or indirectly, for any loss or damage arising under this warranty or otherwise, regardless of cause of origin, Seller’s maximum liability shall not in any case exceed the  purchase  price  of  the  product,  and  shall  be  the  complete  and exclusive remedy against the Seller.
P/N 310.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 1  Fire Pull Station with Transmitter                        Model 310  Description: The  model  310  is  a  self-contained  dual  action  lexan  fire  pull  station  with  a  built  in transmitter. It is a UL38 listed device and meets the ADA requirement of a 5-lbs. Maximum pull force to activate. Operating instructions are molded into the handle along with Braille text. The Model 310 is fully supervised for tamper, low battery and RF signal integrity. The transmitter is powered by a single 3 volt lithium battery as listed under the specifications section of this manual and the label on the product. The model 310 is intended to be used with Commercial Wireless Systems International, LLC Model CP-3000 Fire Alarm Control Panel. Refer to the CP-3000 FACP installation instructions, part number 3000.MAN Rev. 1 for additional details.  Programming: The 310  must be  enrolled into the  CP-3000 FACP  before installation of  the  device. The Model 310 will not report Alarms or trouble signals unless it is enrolled into the CP-3000 control panel. Enrollment must be performed while in front of the CP-3000 control panel. Place the CP-3000 FACP in enrollment mode then install the battery in the model 310  transmitter  observing  polarity  marked  on  the  battery  holder. The  model  310  serial number will be displayed on the CP-3000 FACP along with programming options. Refer to the  CP-3000  control  panel  installation  instructions  for  further  details  on  enrollment  and transmitter programming options. After the model 310 is enrolled, remove the battery and reinstall it only at the transmitters mounting location.   Installation: Select  an  accessible  location  that  is  not  prone  to  tampering  or  accidental  damage. The Model  310  must  be  installed  and  maintained  in  accordance  with  the  National  Fire Protection Association’s Standards (NFPA), the National Electrical Code and within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. For  ADA  compliance,  if  the  clear  floor  space  only  allows  forward approach  to  an  object,  the  maximum  forward  reach  height  allowed  is  48-inches (121.92cm).  If  the  clear  floor  space  allows  parallel  approach  by  a  person  in  a wheelchair, the maximum side reach height allowed is 54-inches (137.16cm). The mounting surface should be relatively flat and capable of accepting screws or anchors. The  310  is  to  be  installed  in  an  indoor  dry  location.  Exposure  to  weather  or  corrosive conditions may damage the unit. The Pull Station must be mounted on a vertical surface so that  the  CWSI  label  can  be  read  correctly. Perform  the  signal  test  described  in  this manual prior to and after permanently mounting the unit. Fasten the back box to the mounting surface using the 4 screws and anchors supplied. Install the battery in the battery holder. Carefully snap the front assembly on to the back box making sure all four clips have been fully inserted (figure 2). Be careful not to bend the transmitter’s antenna. Perform the Signal Test and Alarm Test as outlined in this manual.   P/N 310.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 2   Cautions: 1. Make sure the battery is firmly installed in the battery clip. 2. The unit must be secured tightly to the wall, so as to not be dislodged. 3. Test the unit after any service or battery change or as often as local or national codes dictate.   Alarm Operation: To activate an alarm from the pull station, push in and pull down on the handle. The word ‘ACTIVATED’ appears after the handle is pulled down. The pull station remains in the activated position until reset.  When the pull station handle is pulled: 1. An initial alarm signal is transmitted. 2. A 30 second delay occurs. If during this delay the alarm condition is reset and the alarm cycle is ended. 3. The continued alarm condition causes a repeat alarm transmission. 4. Another 30 second delay as in step 2 occurs. 5. The continued alarm causes a  repeat alarm transmission. 6. Step 5 repeats at 60 second intervals until reset.  To reset the pull station, insert the key into the lock and rotate ¼ turn counterclockwise. Open the door until the handle returns to normal then close and lock the door. Closing the door automatically resets the switch to the normal position. Opening the door with the key will not activate the alarm switch.  LED: The LED will flash when any signal is sent from the transmitter.  Alarm Test: Before testing, notify the proper authorities that maintenance is being performed and the system will be temporarily out of service. To activate an alarm from the pull station, push in and pull down on the handle. The word ‘ACTIVATED’ appears after the handle is pulled down. Verify an alarm is received at the control panel. The pull station remains in the activated position until reset.  To reset the pull station, insert the key into the lock and rotate ¼ turn counterclockwise. Open the door until the handle returns to normal then close and lock the door. Closing the door automatically resets the switch to the normal position. Opening the door with the key will not activate the alarm switch.   Signal Testing: The test must be performed while the pull station is held in its intended mounting location. Initiate the test by placing a strong magnet along the middle left side of the 310 case (figure 1).  The  model  310  piezo  sounder  will  beep  twice  if  the  transmitter  is  located  within acceptable  range  of  a  repeater  or  CP-3000  FACP. If two  beeps  are  not  heard  within  5 seconds of initiating the signal test then relocate the model 310 mounting position closer to the nearest repeater or control panel and perform the test again. Continue this procedure until 2 beeps are achieved. Do not mount the transmitter unless 2 beeps are heard when performing  the  signal  test.  This  test must  be  performed  before  and  after  transmitter installation.  Note:  A CWSI model  AR-3 repeater  or CP-3000 Control  Panel  must  be installed and turned on before running this test.
P/N 310.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 3Low battery: The  battery  voltage  is  periodically  tested  under  load  In  the  event  that  a  low  battery  is detected, a low battery signal will be sent immediately and repeated every 90 seconds for a minimum of seven days. Where more than one type of trouble exists, all will be repeated every 90 seconds.   Battery Installation and Replacement: Warning: Always install a new battery of one of the approved types as listed in the Specifications  section  of  this  manual  and  the  product  label.  When  a  battery  is  first inserted, a low battery test is performed. If the battery passes the test, The unit should not send a low battery signal. If the battery does not pass this test, the unit will continue to send a low battery until a good battery is installed.  To replace the battery:  1. Place the CP-3000 Control Panel in Test mode to prevent any unwanted alarms. (Refer to the CP-3000 manual)  2. Open  the  Pull  Station  door  using  the  key  provided.  This  will  not  cause  an  alarm. Separate the Pull  Station front from the back by releasing  the snap  latches as shown  in figure 2. Remove the battery and dispose of properly.   3. To insure proper power down sequence, wait a minimum of 20 seconds before installing a new battery.  4.  Install  a  new  approved  3  volt  lithium battery  in  the  battery  compartment  following  the polarity diagram inside  the compartment.  A  tamper trouble signal  should be indicated on the CP-3000 Control Panel upon installation of the new battery.  5. Reattach the Pull Station by firmly pushing the front onto the back making sure the snap latches clip into the back box. Close the Pull Station door and lock it with the key.  6. Test the Pull Station for alarm operation.   7. If the Pull Station does not function for alarm operation as described in item 6 then start over at step 2. If it still doesn’t operate correctly then replace the entire unit.   8. Remove the panel from test mode. (Refer to the CP-3000 manual)  Tamper: The Model 310 has an on board tilt sensor that will cause a tamper signal to be transmitted if  the  310  case  is  opened  or  removed  from  its  mounting  position.  Upon  detection  of  a tamper,  a  tamper  signal  is  sent  immediately  and  repeated  every 90  seconds  until  the condition is restored. Where more than one type of trouble exists, all will be repeated within 90 seconds.             P/N 310.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 4MOUNT PULL STATION IN A VERTICAL POSITION ONLY                                Figure 1
P/N 310.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 5     Figure 2             P/N 310.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 6 Specifications: Battery  Type:  3  Volt  Lithium;  Duracell  DL123A,  Sanyo  CR123A,  Panasonic CR123A. Battery Life: 12 Months Minimum Battery  Replacement:  Upon  Low  battery  report  and/or  during  annual maintenance. Operating Temperature Range: 0C to +49 C. Operating Humidity Range 0 to 95% RH. Testing: Follow this manual and NFPA 72 or local requirements. Transmission:  In  compliance  with  FCC  part  15  for  reception  on  equipment manufactured by Commercial Wireless Systems International, LLC. Test Transmission: Every 90 seconds. Compatibility: Commercial Wireless Systems International, LLC Model CP-3000. Size: 5.50 Inches high, 4.12 Inches wide, 2.80 Inches deep. Weight 6.4 oz.   FCC Statement  Important: Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment   This device complies with part 15 of the FCC Rules. Operation is subject to the following two  conditions:  (1)  This  device  may  not  cause  harmful  interference,  and  (2)  this  device must  accept  any  interference  received,  including  interference  that  may  cause  undesired operation.
P/N 310.MAN Rev. 1.0  2006 Commercial Wireless Systems International, LLC 7 COMMERCIAL WIRELESS SYSTEMS INTERNATIONAL, LLC ONE YEAR LIMITED WARRANTY  Commercial Wireless Systems International, LLC (“Seller”), 10794 N.W. 53 Street, Sunrise, Florida 33351, warrants this product to be free from defects  in  workmanship  for two  years  from  date  of  purchase,  under normal  use  and  service.  Seller’s  obligation  is  limited  to  repairing  or replacing, at it’s option, free of charge for parts and labor any part proven to  be  defective  in  materials  or  workmanship.  Seller  shall  have  no obligation  under  this  warranty  otherwise  if:  (1)  the  product  is  altered, repaired or serviced by anyone other than the seller, (2) the product is damaged from accidents, acts of God, misuse, tampering or abuse, (3) product is not installed and operated in accordance with the instructions provided  by  the  seller.  In  case  of  defect,  contact  the  fire  alarm professional who installed and  maintains  your  fire alarm system or the seller for product repair.  This two year Limited Warranty is in lieu of all other express warranties, obligations,  or  liabilities.  There  are  no  express  warranties  that  extend beyond the face hereof. In no case shall seller  be liable to anyone for any consequential or incidental for breach of this or any other warranty, express or implied, or upon any other basis of liability whatsoever, even if the loss or damage is caused by the seller’s own negligence or fault. Seller shall have no liability for any personal injury, property damage, or other loss based on a claim that the product failed to operate correctly. However, if the seller is held liable, whether directly or indirectly, for any loss or damage arising under this warranty or otherwise, regardless of cause of origin, Seller’s maximum liability shall not in any case exceed the  purchase  price  of  the  product,  and  shall  be  the  complete  and exclusive remedy against the Seller.

Navigation menu