TRANE Furnace/Heater, Gas Manual L0702197
User Manual: TRANE TRANE Furnace/Heater, Gas Manual TRANE Furnace/Heater, Gas Owner's Manual, TRANE Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 36
Download | |
Open PDF In Browser | View PDF |
IIIIII IIIIIII IIIIIII IIIIIIIII 18- 14 CD19D8- 10/30/06 s Upflow / Horizontal & Downflow / Horizontal, Gas-Fired, Direct Vent, 2-Stage Condensing Furnaces with Variable Speed Inducer *UX2B060A9362A *UX2D120A9602A *DX2C100A9482A *UX2B080A9422A *DX2B060A9362A *DX2D120A9602A *UX2C100A9482A *DX2B080A9422A *__First letter may be "A" or "T" ALL phases of this installation IMPORTANT must comply with -- This Document Please return NATIONAL, is customer to selwice information STATE property AND LOCAL CODES and is to remain pack upon completion *UX2 with this unit. of work. *DX2 DOWNFLOW A.'_ FLOW AiR FLOW G UPFLOW UPFLOW / HORIZONTAL FLOW AiR \ / LEFT OOWNFLOW,HOR,ZONTALR,GHT _o%_ / I \ o i A341624P03 Installer's Guide SAFETY SECTION The following safety practices and precautions must be fbllowed during the installation, servicing, and operation this furnace. of 1. Use only with the type of gas approved for this furnace. Refbr to the furnace rating plate. 2. Install this furnace only in a location and position as specified in "Location and Clearances" (page 3), of these instructions. 3. Provide adequate combustion and ventilation air to the furnace space as specified in "Air for Combustion and Ventilation" (pages 7-8), of these instructions. 4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the "Venting _' section (pages 13-22), of these instructions. 5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in "Gas Piping" (page 28), of these instructions. 6. Always install the furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace. 7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and temfinating outside the space containing the furnace. 8. A gas-fired furnace for installation in a residential garage must be installed as specified in "Location and Clearances" section (page 3), of these instructions. 9. The furnace may be used fbr temporary heating of buildings or structures under construction only when the following conditions have been met: a. The furnace venting system must be complete and installed per manufacturer's instructions. b. The furnace is controlled only by a room thermostat (no field jumpers). c. The furnace return air duct must be complete and sealed to the furnace and clean air filters are in place. d. The furnace input rate and temperature rise must be verified to be within nameplate marking. e. 100% of the furnace combustion air requirement must come from outside the structure. f. The furnace return air temperatm_ range is between 55 and 80 degrees Fahrenheit. g. Clean the furnace, duct work, and components upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions. 10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusettes. To prevent shortening its service life, the furnace should not be used as a "Construction Heater" during the finishing phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger. © 2006 American Standard Inc. All Rights Reserved CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition. 4. Close fireplace dampers. 5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan. 6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously. 7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes. 8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use. Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are DANGER, WARNING, and CAUTION. a. DANGER indicates an imminently hazardous situation which, if'not avoided, will i_sult in death or serious injm% This signal word is limited to the most extreme situations. b. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious inj ui% c. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage. 1 8-CD19D8-14 Installer's GENERAL The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation. It is reconunended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements fbr installation at Altitudes above 2000 ft., remember the gas input must be reduced (See GAS INPUT ADJUSTMENT). Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the delivering agency. Codes and local utility requirements governing the installation of gas fired equipment, wiring', plumbing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained fl_om the American Gas Association Laboratories, 8501 E. Pleasant Valley Rd., Cleveland, Ohio 44131. These furnaces have been classified as CATEGORY IV fhrnaees in aecordanee with latest edition of ANSI Z21.47 standards • CAN/CGA 2.3. Category IV furnaces operate with positive vent static pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Category IV Direct Vent furnaces are approved for installation in Manufactured/Mobile housing when used with BAYMFGH001A. LOCATION AND CLEARANCES The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements: 1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical? 2. Do all clearances between the furnace and enclosure equal or exceed the minimums stated in Clearance Table on the Outline Drawings. 3. Is there sufficient space fbr servicing the furnace and other equipment? A minimum of 24 inches fi'ont accessibility to the furnace must be provided. Any access door or panel must permit removal of the largest component. 4. Are there at least 3 inches of clearance between the furnace combustion air openings in the front panel and any closed panel or door provided? 5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow aceunmlation level? (See the Air for Combustion and Ventilation section.) 6. Allow sufficient height in supply plenum above the furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this furnace installation. 7. A furnace shall be installed so electrical components are protected fi'om water. 8. If the furnace is installed in a residential garage, it must be installed so that the burners, and the ignition 18-CD19D8-14 Guide Contents Installation Instructions General Location and Clearances Outline Drawings Upfiow Installation Downfiow Installations Air For Combustion and Ventilation Duct Connections Return Air Filters General Venting Venting Materials Vent Tables Horizontal Venting Through Wall Venting Through the Roof Venting Routed Through a Masonry Chimney Downward Venting Condensate Drain Instructions Field Wiring Diagrams Electrical Connections Gas Piping Combustion and Input Check High Altitude Derate Start-up and Adjustment Preliminary Inspections Lighting Instructions Sequence of Operation Control and Safety Switch Adjustments Abnormal Conditions IFC Error Flash Codes Fault Code Recovery source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid physical damage from vehicles. IMPORTANT: The furnace must be installed level. The only allowable variation would be slightly to the left and/or forward in upflow installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage. Do not install the furnace in a corrosive or contaminated atmosphere. Failure to follow this warning could result in early equipment failure. Do not install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required. 3 .ii J_ m *UX2 UPFLOW / HORIZONTAL _5/8" 4 I/2 t (ALL 1_ i i A,R F;_ 5/8" ji IN INCHES) i-I, _2"FLUE SEE L / DIM _4 m m CONNECT NOTES I 1/16" _3 ICAL_ _ ._'I i/78" × 7/8"_._, '\'_ SLOT KNOCKOUT CONDENSATE DRAIN _ q 2 _HOR HOLE_ SUPPLY & "E" OUTSIDEAIR ELECTR ARE DRAWING OUTLET -_..._D,M "B" DIM "C- _ 7/8" DIMENSIONS OUTLINE ."._ff_ 15/16" I ZONTAL SIDE _7/8" KNOCKOUT J ELECTRICAL /SUPPLY APPLICATION ONLY) \/_,THIS -2,/,6,,\_ m2 I/I (ALTERNATE) _ _ (HORIZONTAL) _. _ . (ALTERNATE) __._ ¢,,/8,, KNOCKOUT__ ._ _' CONDENSATE DRA N _ I/8" KNOCKOUT DRAIN (ALTERNATE) _,_ T ' T | 4? / _ --_ 3os/8" o /4,, I/2"_ /I L 5 II _ 14 7/8" DIM "A" 5H I 9/16" 6 I/2" _ I/2" MINIMUMCLEARANCETO COMBUSTIBLE MATERIALS Model DIM"A" DIM"B" DIM"C" DIM"D" DIM"E" DIM"F" *UX2BO6OA9362A *UX2BO8OA9422A 17-1/2" 2-1/4" 16-1/4" 16" 7-1/2" 2" *UX2C1OOA9482A 21" 2-1/2" 19-3/4" 19-1/2" 9" 3" *UX2D12OA9602A 24-1/2" 2-15/16" 23-1/4" 23" 10" 3" (See Note 1 & 2) INLET AIR DIM "D" ° * Prefix _24 1/32"_-I _o 6 May Be "A" or "T" From Dwg. 21 C341884 Rev. 1 UPFLOW SIDES REAR FRONT TOP FLUE O 0 3 I O IN IN IN IN IN HO_ZONTAL (FLUE DISCHARGEON THE LEFTI ALCOVE SIDES RIGHT O LEFT 0 REAR 6 FRONT 18 TOP I FLUE O Notes: 1, *UX2D120A9602A *UX20100A9482A proper q_ EJ 4_ 7/32" Requires 3" Diameter Vent Pipe. Requires 2-1/2" or 3" Diameter Vent Pipe. 2. Diameter of Vent Pipe may be limited to 2-1/2" or 3" on some models at different altitudes. Refer to the Vent Length Table for EJ ,co _3 5/16" I __=11 . ,8/8_ -_233/4 _28 I °/ -,7/8_22,2,, I _L 40II °I I application. CLO_-T SIDES RIGHT LEFT REAR FRONT TOP FLUE I I 3 3 I O =, n_ *DX2 DOWNFLOW © E_ 2 I FLUE _,ONNECT SEE NOTE i " r,D E_ 90 4,,2,d/ 5/8" 4_ t / HORIZONTAL OUTLINE DRAWING (ALL DIMENSIONS ARE IN INCHES) DIM "B" INLET DIM "C" AIR "•' 5 I_ "-- 3" OPENING AIR INTAKE 9-5/8" 5/8' ELECTRICAL CONNECTION (ALTERNATE) 4 ] / [ 6" _"4 HORIZONTAL HORIZONTAL DRAIN I 7/8" x 7/8" SiO- KNOCKOUT APPLICATION (THIS SIDE ONLY) ! FI/2 I i/2"] KNOCKOUT 2-I/8"_ t LECTRICAL SvPPLY _iI/2" GAS CONNECTION CONNECTION AIR INTAKE 4 3_15/16 '' 2 i/16 ''_' -',-CONDENSATE DRAIN _i5/16" KNOCKOUT DIM "A" 7 3/8" J ¢_-1/8 ,I _ CONDENSATE DRAIN KNOCKOUT _i I/2 'I GAS CONNECTION (ALTERNATE) KNOCKOUT Model t DIM "D" 3/4" t OUTLET AIR _ ......................... 3/41'_ _T (See Note 1) DIM"B" DIM"C" DIM "D" *DX2BO6OA9362A *DX2BO8OA9422A 17-1/2" 2-1/4" 16-1/4" 16" *DX2C100A9482A 21" 2-1/2" 19-3/4" 19-1/2" *DX2D12OA9602A 24-1/2" 2-15/16" 23-1/4" 23" HORIZONTAL)FLUE BSCHARGE ON THE LEFT) ALCOVE SIDES R_GHT O IN LEFT O IN REAR 6 IN FRONT 18 IN TOP IN FLUE IN I el I,,,k I I q 3/41' * Prefix May Be "A" or "T" From Dwg. 21C341885 Rev, 1 DIM "A" MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS OOWNFLOW S_DES o FN REAR 0 IN FRONT 3 IN TOP I EN FLUE 0 IN Notes: 1, Diameter of Vent Pipe may be limited to 2-1/2" or 3" on some models at different altitudes. Refer to the Vent Length Table for proper application. CLOSET SIDES RIGHT LEFT REAR FRONT TOP FLUE IN IN IN IN IN IN €__, O, Installer's Guide UPFLOW INSTALLATION TABLE Standoff5 and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the furnace top fanges. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoft_ then screwed into the furnace flange. The coil is always placed downstream of the furnace airfow. 14-1/2" 17-1/2" 21" 24-1/2" 13-1/4" 16-1/4" 19-3/4" 23-1/4" HORIZONTAL C .... D" 13-5/8" 20-1/8" 12-5/8" 19-3/8" 16-5/8" 20-1/8" 15-5/8" 19-3/8" 20-1/8" 20-1/8" 19-1/8" 19-3/8" 23-5/8" 20-1/8" 22-5/8" 19-3/8" INSTALLATION Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal position. See Figure 4. The coil is placed downstream of the furnace, with the apex of the coil pointing in the direction of the airfow for horizontal installation. The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as possible (horizontally)between the coil case front and the furnace bottom channel (for downflow/ horizontal furnace). Use four of the screws provided to secure the bracket. The upflow furnace, converted to horizon- FOR VERTICAL STANDOFFS SIDES) (_) DOWNFLOW INSTALLATIONS CABINET SUB=BASE FLANGE CABINET SIDE_ PLENUM OPENING The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% gas furnace. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line). iiiiiiiiiiiiiilliliiiiliiiiliiiiliiiiliiiiliiiiliiiili (BOTH 1 CABINET RETURN FLOOR OPENING WIDTH DUCT WIDTH "A .... B .... SIDE SUB-BASE FLANGE -_. (BENT CASED COIL CONNECTION BRACKET FOR DOWNFLOW FURNACE IN HORIZONTAL DOWNFLOW ONLY UP) SDB=OASE L tal, aligns and attaches the TXC coil as in Figure the coil requires additional support. FLOOIt COMllUS,I,IBI,E Do not install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required. 1. However, The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed fl'om the front in the vertical position). The horizontal furnace installation in an attic should be on a service platform large enough to allow fbr proper clearances on all sides and service access to the front of the furnace (See Figure 5 & Clearance Tables, pages 4-5). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or fl'aming. The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection fl'om moisture. The furnace Required floor opening: (DOWNFLOW) See Figure 3 and Table I UPFLOW/ HORIZONTAL SHOWN WITH DIRECT VENT 6 18-CD19D8-14 Installer's Furnace locations may be in a "confined "unconfined space". ® 50 CU. FT. OR MORE .... \ WATER / CLOTHES Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/hr input fl'om all equipment installed. Air for combustion and ventilation requirements can be supplied from inside the building as in Figure 9 or fl'om the outdoors, as in Figure 10. must be supported at both ends and the middle when installed horizontally. The furnace must also be elevated approximately 4-6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position. The horizontal furnace may also be suspended from the joists using 3/8" all-thread rods with pieces of angle iron underneath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of sufficient length to allow fbr proper clearances fi'om combustible materials. The angle iron needs to be at least 32" in length to allow for access to service panels. If"these furnaces are installed in a nondirect vent capacity then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be kept fi'ee of obstructions which restrict the flow of air. Airflow restrictions affbct the efficiency and safe operation of the furnace. Keep this in mind should you choose to remodel or change the area which contains your furnace. Furnaces must have a fl'ee flow of air for proper performance. Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1 -- CAN/CGA B149.1 or applicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation. OUTSIDE AIR IS RECOMMENDED The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require the use of outside air for combustion. The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical exposures: * Commercial buildings * Buildings with indoor pools * Furnaces installed in "confined" laundry rooms * Furnaces installed in "confined" hobby or craft rooms * Furnaces installed near chemical storage areas. 18-CD19D8-14 air .................... MINIMUM AREA IN SQUARE FEET FOR UNCONFINED SPACE INSTALLATIONS FURNACE MAXIMUM BTUH INPUT RATING WITH 8 FT. CEILING MINIMUM AREA IN SQUARE FEET OF UNCONFINED SPACE 60,000 80,000 100,000 120,000 375 500 625 875 AND VENTILATION Exposure to the following substances in the combustion supply will also require OUTDOORAIR for combustion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refl'igerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fhbric softeners for clothes dryers * MasomT acid washing materials space" or an Unconfined space is defined in Figure 6. These spaces may have adequate air by infiltration to provide air for combustion and ventilation. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air to be provided as described for confined space. UNCONFINED AIR FOR COMBUSTION Guide ® CONFINED SPACE LESS THAN 50 CU. FT. PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED 1. All air fl'om inside the building as in Figure 9: The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refbr to Table 2 for minimum open areas requirements. 2. All air fl'om outdoors as in Figure 10: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refbr to Table 2, for minimum open areas requirements. TABLE 2 MINIMUM FREE AREA IN SQUARE INCHES EACH OPENING FURNACE ONLY) Furnace Maximum BTUH/INPUT Air From Inside Rating 60,000 80,000 100,000 120,000 100 100 100 120 Air From Outside Vertical Duct Horizontal Duct 15 20 25 30 30 40 50 60 7 Installer's Guide DUCT ® CONFINED SPACE AIR FROM INSIDE BUILDING CONFINED SPACE Central furnaces, when used in connection with cooling" units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat exchanger. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to pi_vent chilled air fl'om entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position. -- PERMANENT OPENINGS On any job, flexible connections of"nonflammable material may be used for retta'n air and discharge connections to prevent transmission of"vibration. Though these units have been specifically designed fbr quiet, vibration fi'ee operation, air ducts can act as sounding boards and could, if poorly installed, amplify the slightest vibration to the annoyance level. ® CONFINED SPACE AIR FROM OUTDOORS When the furnace is located in a utility room adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under IIL II/ CONFINED SPACE CONFINED SPACE OUTDOOR AIR the floor or through the installation of air return central hall). DUCTS INLET _'_ _UVERS TO OUTDOORS _ --.OUTLET INLET AiR DUCT return air through the back of the furnace Do Not install return air through cabinet on horizontal applications. the side of the furnace NOTE: Minimum return air temperature is 50 ° F. All return air duct return air filters. 1. Set CONFINED SPACE TO OUTDOORS . OUTLET AIR SPACE • INLET AIR DUCT 8 the furnace 2. For upflow tion around AIR FR( CONFINED. the supply ducts carry outside the space shall also be handled terminating outside RETURN AIR DUCT SYSTEMS Where there is no complete return duct system, the return connection must be run full size from the furnace to a location outside the utility room, basement, attic, or crawl space. Do Not install cabinet. AIR _ attic. Such design permits the remote fi'om the living area (i.e. When the furnace is installed so that air circulated by the furnace to areas containing the furnace, the return air by a duct(s) sealed to the furnace and the space containing the furnace. AIR FROM VENTILATED ATTIC/CRAWL SPACE ALTCI N L EETR_II_ E_D CONNECTIONS Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable. side the systems should provide for installation of in place. return installations, remove the insulaopening" in the blower compartment. 3. The side panels of the notches that are used for return air, refer to drawing" on page 4 for various furnaces. upflow furnace include locating" as guides fer cutting" an opening" Figure 11 and the outline duct connection dimensions for NOTE: On upflow 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR I side and the bottom; OR just the bottom. 18-CD19D8-14 Installer's 4. Ifa add Cut 3/4" fllange is to be used fbr attaching" the air iMet to cut where indicated by dotted lines corners diagonally and bend outward duct, in Figure 11. to form flange. 5. If flanges are not required, and a filter' fl'ame cut between locating" notches (Figure 11). is installed, 6. The bottom panel of the upflow furnace must be removed for' bottom return air. Remove the filter and lay the furnace on its back. Remove the two 1/4" hex screws securing the bottom front channel to the cabinet. Lower the fl'ont edge of the bottom front channel and pull forward to remove the channel. The bottom return air panel will now easily slide out of the cabinet. Reinstall the bottom front channel and filter' for upflow bottom return installations. 7. The filter retainer is factory supplied for upflow bottom return. Use the filter retainer on side or bottom if filter is to be used within the furnace cabinet on upflow only installations. 8. The horizontal installation requires an external filter bottom return filter within are available for horizontal of the upflow furnace section. Do NOT use the the furnace. Filter kits applications. Guide NO TE: On upflow 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom. The upflow furnace blower door has a hinge at the bottom which allows the door to tilt forward for filter replacement without the door being removed (See Figure 12). The furnace filter in the bottom or side configuration can be removed by simply turning the two latches on the blower door and tilting the door forward. The filter rails are spring loaded for automatic adjustment allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the required width needed for bottom or side return (See Figure 13). to @ .................... BOTTOM FILTER RACK INSTALLATION With the filter removed, the filter rack is compressed and then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engagement holes at the bottom of the furnace cabinet side, 9. Connect duct work to furnace. See Outline Drawing" for supply and return duct size and location. Flexible duct connectors are recommended to connect both supply and return air ducts to the furnace. If only the fl'ont of the furnace is accessible, it is recommended that both supply and return air plenums are removable. RETURN AIR FILTERS (NOT SUPPLIED) TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS Filters are not factory supplied for these furnaces. furnaces require high velocity type air filters. The be located within the furnace blower compartment UPFLOW furnaces in either a BOTTOM or SIDE right side) return air inlet. Some filters may need trimmed for side or bottom filter use. These filters may for (left side or to be TABLE 3 MODELS NUMBERS *UX2B060A9362A *UX2B080A9422A *UX2C100A9482A *UX2D120A9602A CABINET WIDTH FILTER QTY & SIZE 17-1/2" 1 - 17" X 25" X 1" 21" 1 - 20" X 25" X 1" 24-1/2" 1 - 24" X 25" X 1" * First letter may be "A" or "T" ** NOTE - On 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom, UPFLOW LOCATING NOTCHES PROVIDED FOR SIDE RETURN CUTOUT *-. FURNACE ONLY t / Blower Door Hinge and Bottom Filter Rack Installation FILTER RACK "_ ! CUT OUT FOR SIDE FILTER RETAINING PIN (Both Sides) SEE OUTLINE DRAWING 18-CD19D8-14 RONT of Furnace Optioinal Filter Rack Accessory Kit - BAYRACK960A 9 Installer's Guide BOTTOM ENGAGEMENT Filter Rack Blower Deck II __ EogagemeotII Hole • II " II II _11 / Retaining Screw/Pin Furnace Cabinet Filter Rack Side Engagement Hole For Filter Rack Installation With I ENGAGEMENT _ "": tl I B°tt°m Return HOLE DETAIL (Typical both sides BLOWER and blower deck) OPTIONAL FILTER RACK INSTALLATION TURN AIR ON UPFLOW FURNACES Engagement Hole For Filter Rack Installation With Side Return FOR SIDE RE- Blower Deck (Left or Right) If side air return is desired, it is necessary to move the filter rack from the bottom of the furnace and reinstall it on the side. The fbllowing a. Open instructions or remove b. Remove be used: door. Furnace the filter'. Compress pins/screws rack out. d. Leave should the blower the filter rack to disengage the retaining" from the furnace sides and slide the filter the bottom panel Cabi net,,,,,]l_ Side in place. Retaining Screw/Pin e. After the side cutout is made fbllowing the directions in the "Return Air Duct Connections" section on pages 8 and 9, compress the filter in the side of the furnace. Confirm retaining pit, screw locks into the the blower deck and the lower pit, the side of the bottom panel. See f. Reinstall chamfer the furnace end first. ® filter on the rack and reinstall that the upper engagement hole in screw rests against Figures 15-19. side inserting the Filter Furnace Cabinet Side SIDE CUTOUT Rack Assembly \ RETAINING PIN (Both Sides) Rack Filter Rack FILTER RACK RAILS Retaining Screw/Pin Engagement Hole For Filter Rack Installation With Bottom Return Typical Upflow Left Side Return Filter Rack Installation Optional 10 BOTTOM PANEL INSTALLED Filter Rack Accessory Kit - BAYRACK960A 18-CD19D8-14 Installer's Guide BLOWER DOOR/HINGE REMOVAL If clearance or other problems create a problem in using the tilting door, the blower door hinge may be removed without creating any problems with the seal of the furnace. To remove the blower door, tilt the door fblnvard 2 to 3 inches and pull up. To remove the tilt feature, simply remove the lower hinge as shown in Figure 22. The bottom of the blower door will catch in the bottom of the fm'nace fi'ont channel fbr door' replacement. Typical Upflow Right Side Return Filter Rack Installation @ Door Hinge Removed ALTERNATE UPFLOW FILTER CLIP / BRACKET INSTALLATION (KIT09224) 1. Determine the location to be used. The furnace cabinet has dimples for location of the alternate furnace clips (Side return only). Pre-drill clearance holes with a 3/16" drill. Bottom return holes are pre-drilled. 2. Install the clips in fi'ont and rear of the desired location using the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet. CHAMFER END OF FILTER GOES INTO FILTER RACK FIRST RETURN AIR FILTERS FOR UPFLOW HORIZONTAL CONFIGURATION FURNACE @ IN When the Upflow Furnace is installed in the horizontal config'uration, the return air filters must be installed exterior to the cabinet. Remote filter grilles may be used for homeowner convenience or the filters may be installed in the duct work upstream of the furnace. See Figure 21. O ALTERNATE FILTER CLIPS LOCATION ] FILTER CLIP - KIT09224 TYPICAL RETURN AIR FILTER INSTALLATION IN UPFLOW MODEL IN HORIZONTAL POSITION 18-CD19D8-14 11 Installer's INSTALLING Guide THE FILTER TABLE The filter may need to be cut to fit the unit location of the return air filter. A score line and the words "CUT HERE" end of the filter. If your application filter, do so as indicted by the score depending" are requires mark. on the located on the cutting the RETURN AIR UNIT SIZE BOTTOM SIDE 17-1/2" DO NOT CUT DO NOT CUT 21" DO NOT CUT CUT ON LINE 24-1/2" DO NOT CUT CUT ON LINE TYPICAL DOWNFLOW INSTALLATIONS FURNACE RETURN CABINET WIDTH *DX060R936 *DX080R942 17-1/2" *DX100R948 *DX120R960 FILTER QTY & SIZE 2- 14"X20"X 1" 21" 2- 16"X 20"X 1" 24-1/2" 2 - 16"X 20"X 1" *First letter may be "A" or "T" TABLE LOCATING 5 FILTER RETAINER DUCTWORK DIMENSION "A .... BRACKETS DIMENSION B" RETURN DUCT WIDTH 17-1/2" 16-1/4" 15" 14" 14-3/8" 21" 19-3/4" 19-1/2" 14" 13-1/8" 24-1/2" 23-1/4" 22" 14" ' LOCATION DIMENSION IS FROM END OF DUCT AGAINSTTHE SCREW HOLES FOR THE BRACKET. cabinet. Typical installations are shown in Figure 24. Tables 5 and 6 provide information for installation of the filter retaining" brackets shipped with downflow furnaces. IN CABINET WIDTH AIR FILTER Two filters are factory supplied for each downflow furnace. These furnaces require high velocity type air filters. Downflow furnace filters must be located outside the furnace @ MODELS NUMBERS 4 FILTER BRACKET LOCATION' 13-5/8" FURNACE TO THE Optional BAYFLTR206 Door Kit Airflow DOWNFLOW TABLE 6 MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR UPFLOW/HORIZONTAL AND DOWNFLOW/HORIZONTAL FURNACES UNIT LOCATION FURNACE SURFACE HORIZONTAL CLOSET HORIZONTAL ALCOVE / ATTIC SIDES 0" 1" 0" BACK 0" 3" 6" TOP 1" 1" 1" FRONT 3" 3" 18" VENT 0" 0" 0" NOTE: CLEARANCE 12 VERTICAL CLOSET REQUIRED AT TOP OF PLENUM IS 1" 18-CD19D8-14 Installer's The following warning complies with State of California law, Proposition 65. Hazardous Gasest Carbon injury, monoxide, fire or smoke can cause death, and/or property damage. serious bodily A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces and fireplaces. The U.S. Consumer Product Safhty Commission recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke detectors per the manufactureffs installation alert dwelling occupants of the presence unsafh levels of carbon monoxide. These instructions to help of fire, smoke or devices should be listed by Underwriters Laboratories, Inc. Standards" for Single and Multiple Station Carbon Monoxide Alarms', UL 2034 or CSA International Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19 NO TE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector. GENERAL THIS FURNACE VENTING MUST BE VENTED TO THE OUTDOORS. THESE FURNACES ARE INDUCED DRAFT VENTED AND MUST NOT BE CONNECTED TO ANYVENT SERVING ANOTHER APPLIANCE. PLEASE NOTE THAT THESE FURNACES USE POSITIVE-PRESSURE VENT SYSTEMS. Proper venting is essential to obtain maximum efficiency fi'om a condensing furnace. Proper installation of the vent system is necessary to assure drainage of the condensate and prevent deterioration of the vent system. American Gas Association has certified the design of condensing furnaces for a minimum of 0" clearance from combustible materials with a single wall plastic vent pipe. The recommended system is assembled fi'om 2", 2-1/2", or 3" plastic pipe and fittings (See Table 7, page 15). Where the system is routed to the outdoors through an existing masomT chimney containing flue products fi'om another gas appliance, or where required by local codes, then 3" venting of Type 29-4C stainless steel must be used in place of PVC material These furnaces have been classified as CATEGORY IV furnaces in accordance with ANSI Z2L47 "latest edition" standards. Category IV furnaces operate with positive vent pressure and with a vent gas temperature less than 140 ° F. above the dewpoint. These conditions require special venting systems, which must be gas tight and water tight. NO TE: When an existing furnace is removed from a venting system serving other gas appliances, the venting system is likely to be too large to properly vent the remainincl attached appliances. 18-CD19D8-14 The following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation. 1. Seal any unused Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm. Guide openings in the common venting system. 2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition. 3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fhns, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan, close fireplace dampers. 4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance will operate continuously. 5. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return door, windows, exhaust fens, fireplace dampers and any other gasburning appliance to their previous conditions of use. If improper venting is observed during any of the above tests, the remaining common venting system must be corrected. Correction could require rerouting or resizing the remaining vent system. IMPORTANT: These furnaces may be installed as Direct Vent (sealed combustion) or as Nondirect vent (single pipe). The furnaces are shipped DIRECT VENT with sealed combustion. For DIRECT VENTAPPLICATION: The furnaces must be vented to the exterior of the house and combustion air MUST come through the inlet air pipe FROM OUTSIDE AIR. The pipes DO NOT have to exit the exterior of the house together or on the same side of the house. For NONDIRECT VENT APPLICATION: The furnace shaft be vented to the exterior of the house, but combustion air may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION) FURNACE VENT/INLET PIPE INSTALLATION There are many different variations of the vent/inlet air pipe combination. The vent/inlet air combination used for installation of these furnaces depends on the needs of the location. However, these guidelines must be followed: 1. The furnace must vent outside the structure. 2. Furnace combustion air requirements must be met for nondirect, single pipe applications (See example on next page). 3. For direct vent application of these furnaces, the vent pipe and air inlet pipe do not have to exit in the same air space or even on the same surfhce of the structure. However, the longest individual pipe will decide the value [br the longest allowable equivalent vent/inlet air length as shown in the vent length table. 13 Installer's Guide Attic NO TE: BAYVENT200* accessories can be used for inlet and outlet terminals when the pipes do not exit the structure together. The following are EXAMPLES ONLY: Vent Air J II II Furnace U Air Inlet EX. 41 The inlet air does not have to come It'om outside the structure. Example 4 shows the inlet air (See Note), may come from the attic if the requirements for combustion air are met as shown in the section AIR FOR COMBUSTION AND VENTILATION. Furnace EX. 1 i Example I shows that the vent may go vertical while the inlet air may be on any side of the structure. The vent pipe would decide the maximum equivalent length for the pipe depending on the furnace and pipe size. Air _ z2: NOTE: If only the flue gas pipe is to the outside of the structure, a straight section of pipe (long enough to exit the furnace cabinet) must be attached to the inlet air side with an elbow (which is 5 to 10 equiv, ft.) installed on the end to prevent dust and debris from falling directly into the furnace. VENT FITTING MATERIAL- PLASTIC Gas and liquid tight single wall vent fittings, designed for resistance to corrosive flue condensate, MUST be used throughout. i Inlet_ (See Note) Listed in Table 7 are 2", 2-1/2", and 3" size fittings that meet these requirements. The materials listed are various grades of PVC and ABS plastic. EX. 2 1 PIPE JOINTS: All joints must be fastened and sealed to prevent escape of combustion products into the building. Example 2 shows the vent pipe exhausting through the roof and the inlet air coming fi'om the interior of the house (See Note). The inlet air coming fi'om the interior of the house must meet combustion requirements for area, etc., as shown in the section AIR FOR COMBUSTION AND VENTILATION in this Installer's Guide. NOTE: It is recommended that the first joints from the furnace be connected and sealed with high temperature RTV. This will enable the pipes to be removed later without cutting. Be sure to properly support these joints. BONDING OF PVC Commercially available solvent cement for PVC must be used to join PVC pipe fittings. Follow instructions on container caretully. Pipe and FittingPVC Primer Procedure Vent Air Inlet _ Furnace EX. 31 Example 3 shows the vent exiting one side of the house while the inlet air is on the opposite side of the structure. Here the vent pipe length must be within the allowable length for the size offht_ace and size of the vent pipe. This example demonstrates that the pipes do not have to exit on the same side of the structure. 14 ASTM D1785, D2466, and Solvent for Cementing Cement Joints D2661, & D2665 -ASTM - RefASTM D2564 D2855 1. Cut pipe square, remove ragged edges and burrs. ChamIbr end of pipe, then clean fitting socket and pipe joint area of all dirt, grease, moisture or chips. 2. Aider checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and outside of pipe. DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING CEMENT. 3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting movement until it bottoms out. 18-CD19D8-14 Installer's 4. Hold the pipe in the fitting for 30 seconds to prevent tapered socket from pushing the pipe out of the fitting. Guide NO TE: Follow venting instructions carefully when using PVC cement. 5. Wipe all excess cement fl'om the joint with a rag. Allow 15 minutes before handling. Cure time varies according to fit, temperature and humidity. IMPORTANT: All joints must be water tight. Flue condensate is somewhat acidic, and leaks can cause equipment damage. TABLE 7 PVC VENT FITTING MATERIAL These fittings are available from your Gas Furnace Distributors. 2-3/16" i_ _ 4-1/2" _ WALL MOUNT FLANGE BAY69X 148 5-5/8" -_ WALL MOUNT FLANGE BAY69X 147 PLASTIC PIPE DESIGNATIONS PVC ASTM STANDARD F891 PIPE TYPE ALLOWABLE TEMPERATURE MARKING CELLULAR CORE "158 ASTM F891 D2665 DWV PIPE *'158 ASTM D2665 D1785 SCH 40, 80, 120 *'158 ASTM D1785 D2241 SDR SERIES *'158 ASTM D2241 CPVC ASTM STANDARD D2846 PIPE TYPE ALLOWABLE TEMPERATURE MARKING CPVC 41 *'212 ASTM D2846 F441 SCH 40, 80 *'212 ASTM F441 F442 SDR SERIES *'212 ASTM F442 ABS ASTM STANDARD PIPE TYPE D2661 SCH 40 DWV **'180 ASTM D2661 F628 SCH 40 DWV CELLULAR CORE **'180 ASTM F628 - Allowable temperatures based on classifications ** - Allowable *** - Allowable temperatures temperatures based on classifications based on classifications Connection should just air joint be be separated pipes must length. covered ALLOWABLE in ASTM D4396 TEMPERATURE [Deflection covered in ASTM D1784 [Deflection covered in ASTM D3965 [Deflection of the pipe and collar of the combustion air inlet be a fl'iction fit. It is recommended that the inlet sealed with RTV type sealant to allow the joint to for possible future service. The inlet and vent be properly supported throughout the entire Temps MARKING Under Load (264 PSI)] Temps Under Load (264 PSI)] Temps Under Load (264 PSI)] VENT AND INLET AIR CONNECTIONS Seal VENT PIPE with RTV sealant Connection of the vent pipe to the vent collar should also be accomplished using" RTV type sealant. This type sealant provides a connection which remains flexible and can be separated in the future if service needs require the removal of the vent pipe for service or clearance. NO TE: Vent termination kit BA YAIR30A VENTA or BA YVENT2OOB may be used in addition to the horizontal and vertical termination options shown in the following figures. 18-CD19D8-14 FrontofFumace Seal INLET AIR PiPE with RTVsealant 15 Installer's Guide VENT ALTITUDE 0-7,000 LENGTH MAXIMUM TABLE TOTAL EQUIVALENT LENGTH IN FEET FOR VENT AND INLET AIR (SEE NOTES) 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE UX2/DX2B060A9362A Feet 200 200 200 UX2/DX2B080A9422A 50 120 200 UX2/DX2C100A9482A Not Allowed 60 200 UX2/DX2D120A9602A Not Allowed Not Allowed 200 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE UX2/DX2B060A9362A 100 100 100 UX2/DX2B080A9422A 25 60 100 UX2/DX2C100A9482A Not Allowed 30 100 UX2/DX2D120A9602A Not Allowed Not Allowed 100 7,000-9,500 9,500-12,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE UX2/DX2B060A9362A Feet 50 50 50 UX2/DX2B080A9422A Not Allowed 30 50 UX2/DX2C100A9482A Not Allowed Not Allowed 50 UX2/DX2D120A9602A Not Allowed Not Allowed 50 NOTES: * - First letter may be "A" or "T" 1. Minimum vent length for all models: 3' horizontal or 3' vertical. 2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe. 3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes). 4. One SHORT radius 90 ° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One 90 ° elbow is equivalent to 71/2' of 21/2'' pipe or 5' of 2" pipe. Two 45 ° elbows equal one 90°elbow. 5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B 6. Pipe adapters are field supplied (except 120). HORIZONTAL (Upflow equivalent length is 0 feet. INSTALLATION / Horizontal or Downflow 2" TO 3" COUPLING / Horizontal) NO TE: In horizonal venting when the factory supplied "off-set" (2)(3 reducing coupling) is used for 3"' vent pipe installation, make sure the marking "Top" is located on the top side of the pipe. The straight side must be on bottom for proper condensate drainage. This coupling is factory supplied only with the followinqmodels: UC120 & DC120, UX120 & UY120 UXIO0_ UYIO0, UX808C960, andall DX & DYmodels. _I_RY THE SUPPLIED ONLY WITH FOLLOWING MODELS: UC120 & DC120 120 & UY120 | LABEL UXl00 & UYIO0 UX0800960 ALL DX & DY MODLES SAYS "TOP" VENT OUTLET 16 18-CD19D8-14 Installer's Guide G \6" MAX ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE 6" MAX POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS @ NOTE: STRAPS OR OTHER SUITABLE SUPPORTS OF 3'-0" INTERVALS VENT AND INLET MUST BE SUPPORTED AT A MAXIMUM OF 3' INTERVALS USE ONLY APPROVED TERMINATION STRAP (FIELDSUPPLIED) /" COMBUSTION AIR INLET COMBUSTION AIR \ RAIN CA[ VENT n 1" + 1/2" ELBOW COMBUST]ON 40" UPFLOW DOWNFLOW OR MODELS NOTE: ANY FITTINGS PASSING THROUGH AN UNHEATED SPACE MUST BE INSULATED. AIR (FIELD SUPPLIED) BA YAIR3OAVENTA 45' ELBOW r_ _/TEE [j _ FIELD SUPPLIED _J_l" ,PNEEDED\ J_ _-::'i!_ BA YVENT2OOB _ STUB CUT AT 45 ° ANGLE 18-CD19D8-14 WALL CAVITIES 17 Installer's Guide (_ COUPLING ( PLASTIC VENTING ) PVC WALL MOUNT FLANGE 6 IN Mli' 12" MINIMUM TO OVERHANG , ,](TO JOIN SCREWS "(4 req.) / VENT CAP 1" CLEARANCE ( AIR SPACE MAINTAIN 12" (18" FOR CANADA) MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER VENTING BAYVENT200A/B 12"MIN. ABOVE NORMALLY EXPECTED SNOW ACCUMULATION ) THROUGH COMBUSTIBLE Pitch -- 1/4 Inch Per Ft. WALLS CLEARANCE ( 0" ACCEPTABLEFOR PVCVENT PIPE ) I" ACCEPTABLEFORTYPE 29-4C STAINLESS STEELVENT PIPE ® @ PVC WALL MOUNT FLANGE COUPLING ( PLASTIC VENTING ) / 90_ELBOW 6 IN. MIN. II(TO JOINT CEMENT MORTAR SEAL INSIDE & OUTSIDE BAYAIRJOAVENTA (Sidewall) When the vent pipe is exposed to temperatures below freezing, i.e., when it passes through unheated spaces, etc., the pipe must be insulated with 112 inch (22.7 mm) thick Armaflex-type insulation or equal. If the space is heated sufficiently to prevent freezing, then the insulation would not be required. If domestic water pipes are not protected from freezing then it is assumed the space meets the condition of a heated space. HORIZONTAL VENTING THROUGH WALL These furnaces may he installed as direct vent (as shipped) or as nondirect vent. Installation must conform to national, state, and local codes. The vent & inlet terminals minimum above normally Avoid areas a problem. where staining ) must be located at least 12" expected snow accumulation level. or condensate drippage may be Location of the vent/wind terminal should be chosen to meet the requirements of Figure 39 fbr either direct or nondirect vent applications. PITCH -- Venting through the wall must maintain 1/4" per foot pitched upward to insure that condensate drains back to the furnace. 12"MIN.ABOVE NORMALLYEXPECTED SNOWACCUMULATION VENTING THROUGH NON-COMBUSTIBLE WALLS Pitch - 1/4 Inch Per Ft. materials. This can be avoided by using the roof or chimney venting option. When wall venting is used on any surfhce that can be affbcted by this moisture, it is recommended that a corrosion resistant shield (24 inches square) be used behind the vent terminal. This shield can be wood, plastic, sheet metal, etc. Also, silicone caulk all cracks, seams and joints within 3 fbet of the vent terminal. COMBUSTIBLE MATERIAL WALL A minimum clearance of 1" to combustible materials must be maintained when using single wall stainless steel venting. See Figure 31. Shield material to be a minimum of 24 gauge stainless or aluminized sheet metal. Minimum dimensions are 12"x12". Shield must be fastened to both inside and outside of wall. Use screws or anchor type fhsteners suited to the outside or inside wall surthces. NONCOMBUSTIBLE MATERIAL WALL The hole through the wall must be large enough pitch of vent and properly seal. Use cement Figure 32. mortar seal on inside and outside to maintain of wall. See FLUE GAS DEGRADATION -- The moisture content of the flue gas may have a detrimental effect on some building 18 18-CD19D8-14 Installer's @ Guide SUPPORT HORIZONTAL PIPE EVERY 3' 0" WITH THE FIRST SUPPORT AS CLOSE TO THE FURNACE AS POSSIBLE. INDUCED DRAFT BLOWER, HOUSING, AND WEIGHT OF THE FLUE PIPE. cou__b , ff 40" UPFLO_" OR DOWNFLOVV IIII FURNACE iii7i_7}{i{iiiiiiiii{ HOPJZONTAL AND VERTICAL VENTICAL ® VENT 9" MIN. M,tO,MUM NOT TO EXCEED DISTAF4CE FROM TOP _ BE 12* _ 1" I I _ 24 INCHESABOVE ROOF REMOVE FROM RIBS ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF. J # COMBUSTION AIR INLET MAINTAIN VENT 'i CAP MAINTAIN 12 IN. (18 IN. FOR CANADA) 12 IN. (18 IN. FOR CANADA) MINIMUM CLEARANCE , PIPE, COUPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT [ COUPLING COMBUSTION AIR (F,EL2OU%%<_ SUPPORT (FIELD SUPPLIED) CEILING GALVANIZED FIRESTOP SHOULD BE FABRICATED WITH 3-7/8" BIA. HOLE FOR SUPPORT FLANGE (12" x 12" PANEL OR 12" DIA MIN.) VENT BAYAIR30AVENTA 18-CD19D8-14 [_\ _1_ MouST'oN (VERTICAL) CLEARANCE (0" ACCEPTABLE FOR PVC VENT PIPE ) ( 1" ACCEPTABLE FOR TYPE 2B-4C STAINLESS STEEL VENT PIPE ) VENTING THROUGH CEILING 19 Installer's Guide VENTING THROUGH THE ROOF When penetrating roof with a 2" PVC vent pipe, a 2" electrical conduit flashing" may be used for a weather tight seal. Lubricate flexible seal on flashing before PVC pipe is pushed through the seal. (Field Supplied) ® SEAL BETWEEN FLANGE, PIPE, COUPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT N SUPPORT FLANGE NOTE: No vent cap as shown in Figure 34 is the preferred method for vertical vent termination in extremely cold climates. ii FLOOR I ........... In extreme climate conditions, insulate the exposed pipe above the roof line with Armaflex type insulation. VENT FITTING MATERIAL - STAINLESS STEEL Gas and liquid tight single wall metal vent fitting, designed for resistance to corrosive flue condensate such as Type 29-4C MUST be used throughout. These fittings locally. and fitting" accessories FLUE PIPE CLEARANCE (0" ACCEPTABLE FOR PVC VENT PIPE) (1" ACCEPTABLE FOR TYPE 2_C STAINLESS STEEL VENT PIPE) are to be supplied DIRECTION OF STAINLESS STEEL FITTING All stainless steel fitting" must be installed with male end towards the furnace. All horizontal stainless with the seam on top. All long" horizontal sagging. steel sections sections must be positioned must be supported All pipe joints must be fhstened and sealed of combustion products into the building. TYPE 29-4C STAINLESS STEEL VENTING USED THROUGH CHIMNEY THAT VENTS ANOTHER GAS APPLIANCE to prevent to prevent STAINLESS STEEL VENT CAP escape (OPTIONAL) SEE CAUTION 6 IN. MIN. PVC PLASTIC VENTING - ONLY THROUGH UNUSED CHIMNEY STAINLESS STEEL VENT CAP (OPTIONAL)_ FLUE PIPE _.__ SUPPORT THE SINGLE WALL STAINLESS STEEL GAS VENTING AND CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER. / J | "_ 6_,_N. COUPL,NG TO PiPE FROM ANGLES OR OTHER SUITABLE SUPPORT METHOD WALL FLUE P,PE AND _,_z, , _._ _ XJ _ q 1/, ,_ _-_ r_ _J "_L 4 1S CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT COUPLING u __/,,_ (/'_" / AS REQUIRED NOTE: HORIZONTAL TO VERTICAL Do not run vent through chimney for wood burning or oil furnaces or incinerators. NOTE: HORIZONTAL TO VERTICAL VENTING VENTING VENTING VENTING Do not run vent through chimney for wood burning or oil furnaces or incinerators or any other gas appliance. If remaining free area between single wall flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connected to chimney with separate entry openings. IMPORTANT The single wall flue pipe joints must be sealed. IMPORTANT The single wall flue pipe joints must be sealed. The 90 ° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of masonry chimney. The 90 ° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of masonry chimney. VENTING ROUTED THROUGH A MASONRY CHIMNEY 20 18-CD19D8-14 Installer's ® HORIZONTAL Guide VENT CLEARANCES J [] VENTTERMINAL (_ AIR SUPPLY INLET [] AREA WHERE TERMINAL Non-Direct Vent Terminal Canadian A= Clearance balcony above grade, B= Clearance to window veranda, porch, or door that deck, or may be opened C= Clearance Vertical D= to permanently clearance the terminal closed soffit a horizontal distance (61 cm) from the center line of the E= Clearance to unventilated F= Clearance to outside G= Clearance to inside H= Clearance to each side of center above meter/regulator assembly I= Clearance building 6 inches (15 cm) for appliances 12 inches (30 cm) for appliances and =/< 100,000 Btuh (30 kw), 12 inches =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) (91 cm) for appliances > 100,000 Btuh (30 cm) 4 feet (1,2m) below or to the side of opening; 1 foot (0,3m) above opening. (30 kw) located above of 2 feet terminal soffit corner regulator to nonmechanical or the combustion line extended vent 3 feet (91 cm) with a height meter/regulator outlet air supply inlet to air inlet to any other 6 inches (15 cm) for appliances 12 inches (30 cm) for appliances and =/< 100,000 Btuh (30 kw), 36 inches K= Clearance to a mechanical air supply L= Clearance above driveway located a paved sidewalk on public property M= Clearance veranda, porch, 15 feet (4.5 m) above assembly the 3 feet (91 cm) appliance under (30 cm) corner to service Clearance J= US Installations window to ventilated within Clearances Installations 12 inches 36 inches IS NOT PERMITTED =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) (91 cm) for appliances inlet > 100,000 Btuh 4 feet (1,2 m) below or to side of opening; 1 foot (300 m) above opening (30 kw) 6 feet (1.83m) 3 feet (91 cm) above if within 10 feet (3m) horizontally or paved 7 feet (2.13 deck, or balcony 12 inches m) 1- 7 feet (2.13 m) (30 cm) Notes: 1. 2, In accordance In accordance with with the current the current 1, :_, A vent shall not terminate Pemitted only if veranda, directly above a sidewalk or paved driveway that is located between two single family porch, deck, or balcony is fully open on a minimum of two sides beneath the floor, * Clearance with in accordance 18-CD19D8-14 CSA B149.1 Natural ANSI Z223.1/NFPA local installation codes Gas and Propane Installation 54 National Fuel Gas Code, and the requirements of the Code. gas supplier and the dwelling manufacturer's and serves Installation both dwellings. Instructions. 21 Installer's Guide Direct Vent Terminal Canadian Clearance above deck, or balcony A= Clearance B= grade, to window veranda, porch, or door that may be opened Clearance Vertical located D= to permanently closed Btuh US Installations (30 cm) 6 inches (15 cm) for appliances 12 inches (30 cm) for appliances 36 inches C= Installations 12 inches and =/< 100,000 Clearances 12 inches =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) (30 kw), 6 inches 9 inches (15 cm) for appliances (23 cm) for appliances and =/< 50,000 (91 cm) for appliances > 100,000 Btuh (30 kw) (30 cm) 12 inches Btuh =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) (15 kw), (30 cm) for appliances > 50,000 Btuh (15 kw) window clearance to ventilated soffit above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal E= Clearance to unventilated F= Clearance to outside G= Clearance to inside H= Clearance extended I= Clearance to service Clearance to nonmechanical J= soffit corner corner to each side of center line above meter/regulator assembly inlet to building regulator vent outlet air supply or the combustion inlet to any other appliance Clearance air supply L= Clearance above a paved sidewalk or paved driveway located on public property M= Clearance or balcony veranda, porch, m) above the 3 feet (91 cm) 36 inches to a mechanical 15 feet (4.5 assembly 6 inches (15 cm) for appliances 12 inches (30 cm) for appliances and =/< 100,000 Btuh (30 kw), air K= under 3 feet (91 cm) with a height meter/regulator (91 cm) for appliances inlet =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) > 100,000 Btuh (30 kw) 6 feet (1.83m) 7 feet (2.13 deck, 12 inches 6 inches (15 cm) for appliances 9 inches (23 cm) for appliances and =/< 50,000 Btuh (15 kw), 12 inches =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) (30 cm) for appliances 3 feet (91 cm) above if within > 50,000 Btuh (15 kw) 10 feet (3m) horizontally m) 1 (30 cm) :_ Notes: 1, 2, In accordance In accordance 1. A vent :_. * Pemitted Clearance with with the current the current shall not terminate only if veranda, in accordance directly CSA B149,1 Natural ANSI Z223.1/NFPA above a sidewalk Gas and Propane Installation 54 National Fuel Gas Code. or paved driveway Code. that is located between two single family dwelling porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. with local installation codes and the requirements of the gas supplier and the manufacturer's and serves Installation both dwellings. Instructions. @ DOWNWARD VENTING _ Furnace may be in vertical or horizontal configurat_1 ._Iv _ All horizontal pipes must be supported at maximum of 3 I I DOWNWARD VENT LENGTH IS LIMITED TO A MAXIMUM OF 15 S EQUIVALENT_FEET. 40 Inch SEE NOTES foot intervals __ Upflow or Downflow Furnace Slope 1/4" per ft. Slope 1/4" per ft. NOTES: _t_ , J -II L W- 6" Min. A) Condensate trap for vent pipe must be a minimum of 6 inches in height. B) Condensate trap for vent and inlet pipe must be connected into a condensate drain pump; an open or vented drain; or it can be connected to the outlet hose of the furnace's condensate trap. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants. c) The condensate trap should be primed at initial start up prior to heating season operation. 22 18-CD19D8-14 Installer's CONDENSATE DRAIN INSTRUCTIONS Guide It is recommended that a drain pan be installed under the furnace to prevent property damage, personal injury or death from leaking condensate. Downflow furnace - The turnace is shipped with the lett side drainage setup. To change the right side drain, remove the drain lines from the trap, rotate the trap 180 ° so it exits to the right, reconnect the lines, and run a 1/2" CPVC pipe fl'om the trap out through the right side knock-out. Use RTV silicone sealant to connect the CPVC pipe to the trap for ease of removing to clean the trap. VERTICAL HORIZONTAL prT_ [o,T._u luul [o]_I APPLICATIONS Upflow furnace - The connection tubing fbr left and right side drainage is shipped in the blower compartment. Install the connection tubing fl'om the trap to the side of the unit and trim all excess tubing to avoid kinks. APPLICATIONS Upflow and Downflow furnaces - All horizontal applications are left side only. It is always recommended that the auxiliary drain pan be installed under a horizontally installed evaporator and/or 90% gas furnace, Connect the Left side Right side UPFLOW (VERTICAL) UPFLOW (VERTICAL) Use extension hose here Use Inducer Drain hose without extension UPFLOW HORIZONTAL 17" UNITS (Left side only) 18-CD19D8-14 UPFLOW HORIZONTAL 21" & 24" UNITS (Left side only) 23 Installer's auxiliary drain in this line). Guide pan to a separate drain line (no trap is needed The trap must be repositioned to the exterior of the cabinet. Remove the trap from its present location and reposition the trap outside of the unit, through the long circular hole, next to the secondary recouperative cell. Remove the larger drain line (from the secondary cell) and trim to fit between the secondary cell and the new trap location. On upflow units, plug" the hole in the blower deck where the tube went through. Remove the hose fi'om the induced blower and reposition into the other drain tap of the inducer, which is located 90 ° clockwise around the inducer. Move the cap fi'om that drain tap to the unused drain tap. On upflow units, plug" the hole in Cut off curved end of Inducer drain hose DOWNFLOW (HORIZONTAL) the blower deck where the tube went through. This tube on downflow units will need to be cut to fit between the inducer and the trap. On upflow units, this tube may need to be extended, using the tubing shipped with the furnace. Connections must be made to an OPEN/VENTED DRAIN. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken to prevent drains fi'om freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants. Left side NO TE: Use 1/2" or larger PVC or CPVC pipe and fittings as required for drain connections (fittings, pipe and solvent cement not provided). NO TE: A corrosion resistant condensate pump must be used ffa pump is required for a specific drain system. DOWNFLOW (VERTICAL) IMPORTANT: The condensate drain should be installed with provisions to prevent winter freeze-up of the condensate drain line. Frozen condensate will block drains, resulting in furnace shutdown. If the drain line cannot be installed in a conditioned space, then UL listed heat tape should be applied as required to prevent freezing (per manufacturer's instructions). The heat tape should be rated at 5 or 6 watts per foot at 120 volts. Self-regulating (preferred) or thermostatically controlled heat tape is required. Right side Use CPVC tubing from Trap outlet, over burner box to cabinet exit Evaporator and furnace condensate drain piping may be manifolded together. A primary drain vent stack must be installed and terminated below the outlet of the secondary heat exchanger drain connection to prevent water fi'om damaging furnace controls if the primary drain outlet plugs up. Where the furnace is installed above a finished ceiling, the primary drain vent stack must be installed such that overflow fi'om the vent stack opening will flow into an auxiliary drain pan in order to prevent water damage to the finished ceiling below. DOWNFLOW (VERTICAL) 24 18-CD19D8-14 Installer's Guide FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 1 STAGE HEATING USING A 1 STAGE HEATING THERMOSTAT NO COOLING 2 _TAGE I STAT FURNACE NOTES: F............................. 7 SEE ............................. NOTE7 L-_IN I BE SURE POWER AGREES WITH EQUIPMENT NAMPLATE(S}. 2. LOW VOLTAGE 124V WIRING> TO BE NO. 18 A.W.G MIN.. 3 GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES 4, SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM. S THESE LEADS PROVIDE llS V, POWER FOR CONNECTION OF ELECTRONIC CLEANER AND HUMIDIFIER MAN, LOAD l,O AMPS EACH 6 THIS CONNECTION IS ONLY USED FOR THERMOSTATS REQUIRING CONNECTION TO THE 24 V POWER SUPPLY (COMMON} SEE 7 SEE TWINNING CONNECTION DIAGRAMS FOR PROPER CONNECTIONS I _ I_TE_ 9 If upflow furnace is installed over a finished ceiling, overflow from the primary drain vent the finished ceiling 8 AIR WHEN UGING THIS FEATURE WHEN A HEATING THERMOSTAT IWITHOUT FAN SWITCH} IS USED, NO WIRING ON "G" TERMINAL OF IFC IS USED. Wl AND W2 MUST BE JUMPERED TOGETHER FOR PROPER OPERATION SECOND STAGE HEATING WILL BEGIN IO MINUTES AFTER FIRST STAGE below. Primary drain vent stack must terminate below secondary heat exchanger condensate drain outlet. To drain opening FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 2 STAGE HEATING USING A 2 STAGE HEATING THERMOSTAT NO COOLING 2 STAGE FURNACE T 'STAT -- SEE -- NOTE 7 NOTES L_[_ [] [] [] [] [] I. 2. 3. 4. 5. BE SURE POWER AGREES WITH EQUIPMENT NANPLATE(S) LOW VOLTAGE (24V. WIRING) TO BE NO. 18 A.W G MIN GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES. SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM, THESE LEADS PROVIDE 115 V POWER FOR CONNECTION OF ELECTRONIC AIR CLEANER AND HUMIDIFIER MAX. LOAD 1.0 AMPS EACH. THIS CONNECTION IS ONLY USED FOR THERMOSTATS REQUIRING CONNECTIONTO THE 24 V. POWERSUPPLY. (COMMON) SEE TWINNING CONNECTIONDIAGRAMSFOR PROPERCONNECTIONS WHENUSING THIS FEATURE. N EMR SC Ou R E N'¢;D 'll SEE [] NOTE [] TO115V1 PH., 60 HZ,, POWER SUPPLY PER INTER ----LINE --LINE COMPONENT 24 V. 24 V. WIRING V. _FIELD WIRING _L V.jr LOCALCODES HUM SEE NOTE 5 / / i H J =t N B_ FACTORY WIRING EAC SEE NOTE 5 18-CD19D8-14 /_ _ L iK -- From Dwg. 21B342024 Rev. O 25 Installer's Guide FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 2 STAGE HEATING, 1 STAGE COOLING USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT (OUTDOOR SECTION WITHOUT TRANSFORMER) 2 STAGE T'STAT FURNACE N01S: SEE NOTE7 L.--,,OUTDOOR UNIT {NOTRANSFORMER) [] [] _}: SLRF [ r,,, i (24V *%R 01¢ v01T,,,D 3 4 GRO NDING 0 S i li;EigOS S N _i LE,_DS "Rr' _ Dr' R FOR CO'4q[CI ON 0 EiE{ ," :_,NiR ,e'\3 JP I} : ..... :! MAX OA} 0 o_" [#('1 ' S CONNECilOk S ON Y USE[} 0_ !ERvOS AIS R OU RING _1 a_l uN 10 lie 24 PO',_,;ERSU PLY ,CCqM@,', ,,_, S}E TWINr f #,i :/,'5C0r'I' C i0N " A;_&,,S FOI PR('_Ei r_, kqER US NG l IS E A 8!E Y' E/VlNINA !Oq liE El RMOS A' _,'JSI BE 'gRID ] 2 SEE ] 6 NOTE8 ] ] 8 [] ] [] [] TO T E 'Y' 0' RAIION S i_ EOU PV AI lEA TERb DLJ(IP{ Jiili [,,,J_" ,/;,[' RJN{?) T0 N1 qUS AN I?[l:A N,SL OR THE ,.,k/" 1' _[ [] 8 ,!,IF ', S) /', _A _ _ ; N LOCt, L CODES i WlF, JKG DJAGPA_d FUR'U, CE CONTRO FOR PROPER GROUND SCREW _ [] NAtq_ 0 COY Y W'H OR P RUN ROqi A R BIO'¢_ R FURNACE JUNC[ iON BOX ,ll SEE ] @ NOTE6 L II TO 115V 1 PH., 60 HZ., POWER SUPPLY PER • LOCAL CODES i i IN I FR ( OvlE NT )ON 24 V. 24 t,. vNi/:,: let k --NE / BK • N L_ HUM SEE NOTE 5 [ EAOSEE :: FACTORY From Dwg. B342021 NOTE 5 / '¢,'_RiNO Rev. 0 FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 2 STAGE HEATING, 1 STAGE COOLING USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT (OUTDOOR SECTION WITHOUT TRANSFORMER) 2 STAGE T'STAT NOTES: FURNACE SEE NOTE 7 L._ OUTDOOR (NO UNIT TRANSFORMER) r_ 1 BE 2, 3 !OW VOltAGE OF (24V WIRING)MUST]0 COMPLY BE NO WITH 18 AWG GROUNDING EQUIPMENT LOCAl 4, 5. SEE TNERMOS]AI HEAl TIIESE LEADS PROVIDE 6 CLEANER AND HUMIDIFIER MAX LOAD THIS CONNECTION !S ONLY USED FOR SEE SURE POWER AGREES CONNECTION NOTE8 _ 7 8 [] [] [] 9 i rq_- 10 THE WITH FOU}PMENT NAMPLATE(S} 84 V DIAGRAM OF ELECTRONIC AIR I0 AMPS EACH THERMOSTATS REOU!RING POWER SUPPLY (COMMON) SEE TW!NN}NG CONNECTION DIAGRAMS _OR PROPER CONNECTIONS WHEN USING [HIS EEAIURE TI4E "Y" TERMININAL FROM THE THERMOSTAT MUST BE WIRED TO THE "Y" TERMINAL QF THE FURNACE CONTROl FOR PROPER BIOWER OPERAIION DURING COOLING Wl AND W2 MUST BE JUWERED SECOND STAGE HEATING WILL FIELD TOGETHER BEG!N IO ADDED FOR PROPER OPERATION MINUTES AFTER FIRST ............. _......................... ]_/_ ,11 JUMPER(NOTE9) / _ _ 704?%% = LOCAL CODES wl, _ _. : STAGE F U R N ACE gu I_ SEE i i M}N, CODES ANTICIPAIOR PER UNI[ WIRING 115 V. POWER FOR CONNECTION c 1ON Box /3 N ,, (.#,,P_N 24 V 24 V. ----LINE --L]k 26 N V. V, , R_N HUM SEE I-- F: IF I) ,'b_R ] N (_ NOTE5 _ FAC EAC SEE / NOTE 5 L" WR ORY NG _1 BK II Jr Wl -BK From Dwg. B342019 Rev. 0 18-CD19D8-14 Installer's TWINNING CONNECTION FOR TWINNING 1 STAGE DIAGRAM UX/DX-R HEAT / 1 STAGE Guide FURNACES COOLING THERMOSTAT tO _S OUTDOOR UNIT NO. 1 (WITH TRANSFORMER) SEE NOTE 3 1 STAGE HEATING / COOLING THERMOSTAT t FURNACE NO. 1 FURNACE fiOTH FCRNACESMUST BE Pg#ERED FROI# _i_ SAt41 r_SV L _ of H_{UfT P4NH NO. 2 BLOWER OPERATION OF UN_NO2 iS SYNCR_q_ZED W_TN UNITNO 1VIASIGNALS F_M TWINC_NECTION _t_$L'RE24_ FUF2_IA_ TRAt,rSFOR_4E@S AR_' ,W P_ASI¸ _'i_,iO_ 0 CO'@L T_Nd_CO,<_rCNO_,iS, CH_C_ _IO__A6_ _ _#N_ R f_i_r_,_S O_¸ _AO,¸ FUR4A_,£ _ VOLT_G_ _S¸ £:Rr_A_E# T_,_i Ot_ Ot_E OF T_E #U_?t_ACET_At_S_OR;eERS 3 0t79_0,_ Utf HAS A Z4V _RA_ ORU¢ 1_ LD SUi' i f US! itLOT ou?f RMA_ ( 2C SUC A_ R _0975 SE_ _ T CO_N[CTtOt SEENOTE4 OUTDOOR UNIT NO. 1 10 TRANSFORMER) ON BOTH UNKS 2NDSTAGEWILL FIRE 10 M_NUTESAFTBR1ST INTER F _ COMPONENT , 24 V. 24 V. ----LINE Rli _ ', ...... i "% FIEL D V.j WIRING "_ --L]NE W]R]NG V.jr FACTORY WIRING _SOLAT_ON RELAY SEENOTE4 { {iiiiiiii % From Dwg. 21B341336 Rev. 2 SEENOTE5 TWINNING CONNECTION DIAGRAM FOR TWINNING UX/DX-R FURNACES 2 STAGE HEAT / 1 STAGE COOLING THERMOSTAT OUTDOOR UNIT NO. I 2 STAGE HEATING (WITH TRANSFORMER) SEE NOTE 3 1 STAGE COOLING THERMOSTAT FURNACE NO. 1 _o7_ uRt#,tc_s '_us 5_ #o¢,_0 ;t sJ_d r SV ¢ _ of t{ u FURNACE NO. 2 <% BLOWER UNIT NO WITH UNIT NO 1 VIA _GNALB : _ _/'_.............. _FrH_ (FIE_DSUP_UED) SEE NOTE4 I I _ =:TZ] o R1 SdPP_,iE_ dSE P_CT ObT_ ¸ RELAr _gO_',i _DO NC_ CO!_C_ _ _0 W_ _¢b4HOt_ _,'_Y t,'O_ _,_£_ d ¸ T,_¸ N_R_O_ _SOCAT_ONRELAy CO,';T_C_ _?_ RATED 4_ _ "_4 0__ A_OVE SEENOTE4 [ _O TRANSFORMER) OUTDOOR UNIT NO. 1 fro!4 #_,,,'f OPERATION OF 2 IS SYNORONIZED m T _> ', F'; • _T: R21"> i ; i INTER I i Q I WIRING o 24 i £ V ----LINE' "_ V.j>- 24 --LINE I I COMPONENT ,, , I :: V. "_ V.jr FIELD WIR IN G FACTORY WIRING \ I ....... I I \ From Dwg. 21 B341337 Rev. 2 i= I .......................... I .......................... 18-CD19D8-14 27 Installer's Guide TWINNING CONNECTION DIAGRAM FOR TWINNING UX/DX-R FURNACES 2 STAGE HEAT / 2 STAGE COOLING THERMOSTAT OUTOOORUNIT NO 2 (NO TRANSFORMER) SEE NOTE 3 I i _OTES: 2 SaGE HEATENG 1 STAGE ¢OOUNG THERMOSTAT FU_NACENOI S_ BOT_FUrnACESMUSTBE POWE_E_ f_OM T_E SA_E n_W LEGOF C_Rcwr PANEL. FURNACENO_2 BLUEROPER_'ON OF ,,, 1 (NO TRANSFORMER) i................................................. i d> R2; " C, Ji/ [ _ J o ' .................. ISOLATION RE_¥ (FIELD SUPPLIED) ALTERNATE CONNECTION b B}O I INTER ' COMPONENT WIRING ALrE_ATE_t_l_6 CO_rI_e_ATSO_ S[[ _Og 4 24 LINE V. From Dwg 218341338 Rev 2 24 --LINE I V, M. _ _ V.jr FIELD WIRING FACTORY WIRING CARBON MONOXIDE POISONING HAZARD Failure to follow the installation instructions for the venting system being placed into operation could result in carbon monoxide poisoning or death. ELECTRICAL CONNECTIONS Make wiring" connections wiring" diagram. As with power, this live electric provided furnace circuit. with to the unit as indicated all gas appliances using shall be connected It is recommended a separate "circuit the National Electrical Code, Electrical Code, if an external into a permanently that furnace be protection circuit. The furnace must be electrically dance with local codes or in the absence on enclosed electrical device" electric grounded in accorof local codes with ANSI/NFPA 70 or CSA C22.1 electrical source is utilized. The integrated furnace control is polarity sensitive. The hot leg" of the 120V power supply must be connected to the black power lead as indicated on the wiring diagram. Provision _br hooking up an electronic air cleaner and or humidifier is provided on the integrated control. Refer to the SERVICE FACTS diagram attached to furnace. 28 literature and unit wiring 18-CD19D8-14 Installer's @ Guide @ AUTOMATIC GAS VALVE WITH MANUAL SHUT-OFF MAIN MANUAL SHUT-OFF VALVE GROUND UNION JOINT ? DRIP LEG AUTOMATIC GAS VALVE WITH MANUAL SHUT-OFF MAIN MANUAL -SHUT-OFF VALVE GROUND i o I JOINT UNION DRIP _ LEG UPFLOW MAY BE LEFT OR RIGHT HAND GAS PIPING (_ THE DOWNFLOW (VERTICAL) MAY BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING MAIN MANUAL SHUT-OFF VALVE AUTOMATIC GAS VALVE WITH MANUAL SHUT-OFF / GROUND UNION JOINT LEG SH%%_#UL% ......................... /_"11 GROUND / UNION JOINT _ DR LEG !_ AUTOMATIC GAS VALVE WITH MANUAL SHUT-OFF II HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE (Typical UPFLOW Furnace in horizontalconfiguration shown) 18-CD19D8-14 29 Installer's Guide GAS PIPING The upflow/horizontal furnace is shipped standard for left side installation of gas piping. A knockout is provided on the right side for an alternate gas piping arrangement. See Figure 45. TABLE 8 NATURAL GAS ONLY TABLE OF CUBIC FEET PER HOUR OF GAS FOR VARIOUS PIPE SIZES AND LENGTHS PIPE The installation of piping shall be in accordance with piping codes and the regulations of the local gas company. Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases. Refer to piping Table 8, fbr delivery sizes. Connect gas supply to the unit, using a ground joint union and a manual shut-off valve as shown in Figures 44 & 45. National codes require a condensation drip leg to be installed ahead of the controls as shown in Figures 45 & 46. LENGTH OF PIPE SIZE 10 20 30 40 50 60 70 1_ 132 92 73 63 56 50 46 3/4 278 190 152 130 115 105 96 1 520 350 285 245 215 195 180 1-1/4 1050 730 590 520 440 400 370 This table is based on pressure drop of 0.3 inch W.C. and 0.6 SEGR. gas TABLE 9 ORIFICE SIZES Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold assembly. INPUT RATING BTUH The furnace and its individual shut-offvalve must be disconnected fi'om the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). 60,000 80,000 100,000 120,000 The furnace must be isolated from the gas supply piping by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa). NO TE: Maximum pressure to the gas valve for natural gas is 13.8" 1/11.(7,, Minimum pressure is 5,0" VV.C. Maximum pressure to the gas valve for propane is 13,8" I/1!.(7,,Minimum pressure is 11,0" W,C. All gas fittings must be checked for leaks using a soapy solution before lighting the furnace. DO NOT CHECK WlTI-I AN OPEN FLAME! © MAIN BURNER ORIFICE DRILL SIZE NUMBER OF BURNERS NAT. GAS LP GAS 3 45 56 4 5 45 45 56 56 6 45 56 COMBUSTION AND INPUT CHECK (See also High Altitude Derate) 1. Make sure all gas appliances are off except the furnace. 2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution. 3. Match the "See" column in the gas flow (in efh) Table 10 with the time docked. 4. Read the "Flow" column opposite the number of seconds clocked. 5. Use the following factors if necessary: For I Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading + 2 For 1/2 Cu Ft. Dial Gas Flow CFH = Chart Flow Reading + 4 CORRECT METHOD OF CHECKING DIRECT VENT MANIFOLD PRESSURE WITH BURNER BOX REFERENCED ] Separate the tube at the unit Tee and reconnect I H_ with a short piece of field suppliedtubeand anotherTeewith the "U"Manometer See inset F-_ I1" "--) ]] __ // JlI ,_/,/ attached. _ 2:2:::_.. "_,__-_,_ Be sure to reconnect unit tubing to original positionafter testing the manifoldpressure! [{ _.=_,:. _.)) \'\ \ -- -- _ ___\\\ _-.\ "-Jkz_-, (71 Fieldsu bedbarb titi'in_ / • pp. "g _ manometer tub:';: ° t attachedto the "OUTLET PRESSURETAP" on the CAUTION: 30 outlet side of the gas valve, Return all tubing, caps, and/or plugs to original positions when pressure checks are completed. 18-CD19D8-14 Installer's For 5 Cu. Ft. Dial Gas Flow CFH -10X Chart Flow Reading 1. Adjust low fire by removing seal screw (See Figure 48). +4 6. Multiply the final figure by the heating value of the gas obtained fl'om the utility company and compare to the nameplate rating. This must not exceed the nameplate rating. 7. Changes can be made by adjusting the manifold pressure (See Table 11), or changing orifices (orifice change may not always be required). To adjust the manifold pressure: a. Turn offall electrical power to the system. b. Attach a manifbld pressure gauge to the outlet pressure tap marked "OUT PRESS TAP" on White-Rodgers gas valve model 36E or boss marked "OUT P" on White-Rodgers gas valve model 36G. (See Figure 48 fbr White-Rodgers gas valve model 36E and Figure 49 for White-Rodgers gas valve model 36G). For the gas valve model 36E, measurements require removal of the plug and installation of a barbed fitting. Attach flexible tubing and a manometer to the barbed fitting. For the gas valve model 36G, do not remove the pressure tap test screw. Loosen the pressure tap test screw one turn and install flexible tubing and a manometer directly onto the outlet pressure boss. c. The other side of the manifold pressure gauge must be referenced to the burner box as shown in Figure 46. d. Turn on system power and energize valve. e. For the White-Rodgers gas valve model 36E: TABLE 10 2 CUBIC FOOT DIAL SEC. FLOW SEC. FLOW 29 248 50 144 30 240 51 141 31 232 52 138 32 225 53 136 FLOW 900 800 720 655 12 13 14 15 16 17 18 19 20 21 22 600 555 514 480 450 424 400 379 360 343 327 33 34 35 36 37 38 39 40 41 42 43 218 212 206 200 195 189 185 180 176 172 167 54 55 56 57 58 59 60 62 64 66 68 23 24 25 26 27 28 313 300 288 277 267 257 44 45 46 47 48 49 164 160 157 153 150 147 70 72 74 76 78 80 SEC. 82 84 86 88 FLOW 88 86 84 82 133 131 129 126 124 122 120 116 112 109 106 90 92 94 96 98 100 104 108 112 116 120 80 78 76 75 73 72 69 67 64 62 60 103 100 97 95 92 90 124 128 132 136 140 144 58 56 54 53 51 50 (inches w.c.) TABLE 11 FINAL MANIFOLD PRESSURE SETTINGS FUEL 2nd Stage Max. 1st Stage Max. NATURAL GAS 3.5" W.C. 1.7" W.C. LP GAS 10.5" W.C. 6.0" W.C. 18-CD19D8-14 low adjustment 2. To increase outlet pressure, turn the 3/32" socket set screw clockwise. To decrease outlet pressure, turn the set screw counterclockwise. Adjust regulator until pressure shown on manometer matches the pressure specified in Table 11. 3. Replace securely. low adjustment 4. Cycle the valve setting. several seal screw times 5. Adjust high fire by removing seal screw (See Figui_ 48). and tighten to verify regulator the high adjustment 6. To increase outlet pressure, turn the 3/32" socket set screw clockwise. To deci_ase outlet pressure, turn the set screw counterclockwise. The final manifold pressure setting shall be as specified in Table 11 with an input of no more than nameplate rating and no less than 93_i of the nameplate rating, 7. Replace securely. unless the unit is derated high adjustment seal 8. Cycle the valve setting. several times for high screw to verify and altitude. tighten regulator HIGH ALTITUDE DERATE Input ratings (BTUH) of these furnaces are based on sea level operation and should not be changed at elevations up to 2,000 ft. If"the installation is 2,000 ft. or above, the furnace input rate (BTUH) shall be reduced 4% for each 1,000 ft. above sea level. GAS FLOW IN CUBIC FEET PER HOUR SEC. 8 9 10 11 the Guide The furnace input rate shall be checked by clocking the gas flow rate (CFH) and multiplying by the heating value obtained from the local utility supplier for the gas being delivered at the installed altitude. Input rate changes can be made by adjusting the manifold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas) or changing orifices (orifice change may not always be required). If the desired input rate cannot be achieved with a change manifold pressure, then the orifices must be changed. LP installations will requite an orifice change. in IMPORTANT: Reinstall the propane orifices to the same depth as the orifices supplied with the equipment. See Table 13 fbr help in selecting orifices if orifice change is required. Furnace input rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude. The vent len_h table on page 16 shows the required vent lengths for installations at various altitudes. An optional high altitude kit is available fbr installations above 5000 feet Installations above 12,000 feet are not allowed). PART NUMBERS TABLE 12 FOR REPLACEMENT ORIFICES DRILL SIZE PART NUMBER DRILL SIZE PART NUMBER 44 45 46 47 48 49 50 ORF00501 ORF00644 ORF00909 ORF00910 ORF01099 ORF00503 ORF00493 54 55 56 57 58 59 ORF00555 ORF00693 ORF00907 ORF00908 ORF01338 ORF01339 31 Installer's Guide TABLE Orifice Twist Drill Size If Installed At Sea Level ALTITUDE and Orifice 13 ABOVE Required SEA LEVEL At Other Elevations 200C 3000 4000 5000 6000 7000 8000 9000 10000 42 43 44 45 46 47 42 44 45 46 47 48 43 44 45 47 47 48 43 44 45 47 47 49 43 4,5 46 47 48 49 44 45 47 48 48 49 44 46 47 48 49 50 45 47 48 49 49 50 46 47 48 49 50 51 47 48 50 50 51 52 54 55 56 57 58 54 55 56 58 59 55 55 56 59 60 55 55 57 59 60 55 56 57 60 61 55 56 57 60 62 55 56 58 61 62 56 56 59 62 63 56 56 59 63 63 56 57 60 63 64 From National ROTATE THE FRONT COVER AS SHOWN INSERT THE TOP FLANGE OF THE FRONT COVER UNDER THE LIP INSIDE THE BOX ALL SIDE FLANGES MUST BE OUTSIDE OF THE BOX Fuel Gas Code - Table F-4 White-Rodgers ROTATE THE FRONT COVER INWARD MAKING SURE THAT ALL SIDE FLANGES ARE OUTSIDE OF THE BOX. 36E 2nd Stage (HI) Manifold Pressure Adjustment C> 3. Replace and tighten securely. the regulator 4. Cycle the valve several setting. 1st Stage (LO) Manifold Pressure Adjustment Gas Valve On / Off Toggle Switch @ White-Rodgers 36G Stage (HI) Manifold Pressure Adjustment Gas Valve On / Off Toggle Switch f. For the White-Rodgers 6. To increase outlet pressure, turn the regulator adjust screw clockwise. To decrease outlet pressure, turn the regulator adjust screw counterclockwise. The final manifold pressure setting shall be as specified in Table 11 with an input of no more than nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude. 1. Adjust low fire by removing the low adjustment regulator cover screw (See Figure 49). 2. To increase outlet pressure, turn the regulator adjust screw clockwise. To decrease outlet pressure, tui_ the regulator adjust screw counterclockwise. Adjust regulator until pressure shown on manometer matches the pressure specified in Table 11. 32 8. Cycle the valve several setting. g. Turn offall electlical regulator cover screw and times to verify regulator power to the system. h. Remove the manometer and flexible tubing. Remove the barbed fitting and replace the plug or tighten the pressure test screw. i. Turn on electrical valve. gas valve model 36G: times to verify regulator 5. Adjust high fire by removing the high adjustment regulator cover screw (See Figure 49). 7. Replace high adjustment tighten securely. Stage (LO) Manifold Pressure Adjustment cover screw power to the system and energize j. Using a leak detection solution or soap suds, check for leaks at plug or pressure boss screw. NOTE: The manifold pressure must be referenced to the burner box. The burner box pressure tap equalizes the gas valve pressure regulator. Manifold pressure is checked by installing a tee (field supplied) in the tubing, between the tee coming from the burner box tube and the gas valve, in addition to the regular gas valve pressure tap on the outlet side of the gas valve. See Figure 47. 18-CD19D8-14 Installer's Replace and/or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service. Failure to follow this warning could result in fire, explosion, or property damage. Table 12 lists the main burner orifices used with the furnace. If a change of orifices is required to correct the furnace input rating refer to Table 13. REINSTALLATION OF THE BURNER BOX COVER Figure 49 shows the correct way to reinstall the burner box cover if adjustment or replacement of the flame sensor, hot surface igniter, or main burner orifices have required removal of the cover. START-UP AND ADJUSTMENT PRELIMINARY INSPECTIONS Disconnect power to the unit before removing the blower door. Allow a minimum of 10 seconds for IFC power supply to drain to 0 volts. Failure to follow this warning could result in property damage, personal injury or death. With gas and electrical power 1. Duct connections are properly 2. Filters 3. Venting 4. Blower are assembled is in place Turn the main gas valve toggle switch (See Fig_i_s 48 & 49) within the unit to the "OFF" position. Turn the external gas valve to "ON". Purge the air fi'om the gas lines. After purging, check all gas connections for leaks with a soapy solution -DO NOT CHECK WITHAN OPEN FLAME. Allow 5 minutos fbr any gas that might have escaped to dissipate. LP Gas being heavier than air may require forced ventilation. Turn the toggle switch on the gas valve in the unit to the "ON" position. LIGHTING INSTRUCTIONS DO NOT attempt to manually light the burner. Failure to follow this warning could result in property damage, personal injury or death. Lighting instructions appear on each unit. Each installation must be checked out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below. Turn on the main electrical supply and set the thermostat above the indicated temperature. The ignitor will automatically heat, then the gas valve is energized to permit the flow of gas to the burners. After ignition and flame is established, the flame control module monitors the flame and supplies power to the gas valve until the thermostat is satisfied. To shut off For complete shutdown: Turn the gas cock knob on the main gas valve to the "OFF" position (See Figure 44). Disconnect the electrical supply to the unit. 18-CD19D8-14 If this is done during the cold weather months, provisions must be taken to prevent freeze-up of all water pipes and water receptacles. Whenever your house is to be vacant, arrange to have someone inspect your house for proper temperature. This is very important during freezing weather. If for any reason your furnace should fail to operate damage could result, such as frozen water pipes. SEQUENCE OF OPERATION Thermostat call for heat (2-stage thermostat) Call for 1st stage only: Wl thermostat contacts close signaling the control module to run its self-check routine. After the control module has verified that the 1st stage pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blower will be energized. As the induced draft blower comes up to speed, the pressure switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approx. 20 seconds, then the gas valve is energized in 1st stage to permit gas flow to the burners. The flame sensor confirms that ignition has been achieved within the 4 second ignition trial period. As the flame sensor confirms that ignition has been achieved, the delay to fhn ON period begins timing and after approx. 45 seconds the indoor blower motor will be energized at low speed and will continue to run during the heating cycle. in place is properly door "OFF" sealed Guide Call for 2nd stage after 1st stage: W2 themmstat contacts close signaling a call for 2nd stage heat. After a 30 second delay, the induced draft blower will be energized on high speed and the 2nd stage pressure switch contacts will close. The gas valve is energized in 2nd stage and the indoor blower motor in high speed. 2nd stage satisfied, 1st stage still called: W2 thermostat contacts open signaling that 2nd stage heating requirements are satisfied. The induced draft blower is reduced to low speed allowing the 2nd stage pressure switch contacts to open and the gas valve is reduced to 1st stage. The indoor blower motor is reduced to low speed. 1st stage satisfied: W1 thermostat contacts open signaling that 1st stage heating requirements are satisfied. The gas valve will close and the induced draft blower will be de-energized. The indoor blower motor will continue to run for the fan offperiod (Field selectable at 60, 100, 140 or 180 seconds), then will be de-energized by the control module. Thermostat call for heat (1-stage Thermostat) W1/W2 (jumpered) thermostat contacts close signaling a call for heat. 1st stage sequence of operation remains the same as above. 2nd stage heat will energize after the stage delay timer (field selectable at .5, 5, 10 or 15 minutes) has expired. Thermostat satisfied: W1/W2 (jumpered) contacts open signaling the control module to close the gas valve. The induced draft blower is switched to low speed and de-energized after the post purge timer has expired. The indoor blower motor will continue to operate after the flames are extinguished and then is switched to low heat speed for the FAN-OFF period. 33 Installer's Guide CONTROL AND SAFETY SWITCH ADJUSTMENTS LIMIT SWITCH CHECK OUT The limit switch is a safbty device designed to close the gas valve should the furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer. To check for proper operation of the limit switches, set the thermostat to a temperature higher than the indicated temperature to bring on the gas valve. Restrict the airflow by blocking the return air (disconnecting the indoor blower may trip the inducer limit). When the furnace reaches the maximum outlet temperature as shown on the rating plate, the burners must shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty limit switch is probable and the limit switch must be replaced. After checking the operation of the limit control, be sure to remove the paper or cardboard f_om the return air inlet. Refer to Service Facts for additional instructions. BURNER BOX TEMPERATURE LIMIT DEVICE All models are equipped with a manual reset temperature limit located on the burner box. In case of excessive temperature, the limit will open and cause the circuit to open which shuts off all flow of gas. ABNORMAL CONDITIONS 1. EXCESSIVE COMBUSTION PRESSURE (WIND IN EXCESS OF 40 MP.H.) VENT OR FLUE BLOCKAGE On a call fox' heat, the variable speed draft inducer must first ramp up to speed and close the pressure switch before the ignition sequence is allowed to begin. If the pressure switch does not close, the motor will ramp up to maximum speed and continue to operate there for about 1 minute. After one minute the integrated furnace control will turn the motor offfor about 30 seconds then back on in an attempt to reestablish proper operation. This condition is indicative of a highly restricted or blocked inlet or outlet vent pipe or a Ihiled pressure switch. NOTE TO INSTALLER Review the following" warnings with the owner. Review contents of USER'S INFORMATION MANUAL with the owner. If pressure against induced draft blower outlet becomes excessive, the pressure switch will open. If the pressure switch is open for more than 3.5 seconds, the variable speed draft inducer will speed up and attempt to reclose the pressure switch. If the pressure switch is not dosed within 12 seconds or if the maximum speed of the motor is reached, the draft inducer sends a Ihult signal to the integ_'ated furnace control. If the unit is operating in second stage, an inducer fault will cause the furnace control to transition the system to first stage and it will operate there for 10 minutes before attempting to run again in second stage. If the unit is operating in first stage, an inducer fault will cause the furnace control to shut the system down and wait 30 seconds befbre attempting to reestablish operation in first stage. AIRFLOW ADJUSTMENT Check inlet and outlet air temperatures to make sure they are within the ranges specified on the furnace rating" nameplate. If the airflow needs to be increased or decreased, see the wiring" diagram for information on changing the speed of the blower motor. Disconnect power to the unit before removing the blower door. Allow a minimum of 10 seconds for IFC power supply to drain to 0 volts. Failure to follow this warning could result in property damage, personal injury or death. This unit is equipped with a blower door switch which cuts power to the blower and gas valve causing" shutdown when the door is removed. Operation with the door removed or ajar can permit the escape of dangerous fumes. All panels must be securely closed at all times for safe operation of the furnace. 2. iiii!ii!iiiiiI INDOOR BLOWER TIMING Heating: The integrated furnace control module controls the indoor blower. The blower start is fixed at 45 seconds after ignition. The FAN-OFF period is field selectable by dip switches SW-2, #1 and #2 at 60, 100, 140, or 180 seconds. The factory setting is 100 seconds. WI-W2 stage delay (jumpered together) is field selectable by dip switch SW-1, #1 and #2 at .5, 5, 10 or 15 minutes. The fhctory setting is 10 minutes. (See wiring diagram). Cooling: The fan delay off period is factory set at 0 seconds. The option for 80 second delay offis field selectable by dip switch SW-2, #3 (See wiring" diagi'am). ROOM AIR THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT Set the thermostat heat anticipator according to the current flow measured, or the settings fbund in the notes on the furnace wixing diagram (found in the SERVICE FACTS or inside the furnace casing). INSTRUCTIONS TO THE OWNERS In the event that electrical, fuel, oi" mechanical failures occur, the owner should immediately turn the gas supply off at the manual gas valve, located in the burner compartment. Also turn off electrical power to the furnace and contact the service agency designated by your dealer. 34 3. LOSS OF FLAME If loss of flame occurs during a heating cycle, or flame is not present at the sensor, the flame control module will close the gas valve. The flame control module will then recycle the ignition sequence, then if ignition is not achieved, it will shut off the gas valve and lock out the system. POWER FAILURE If there is a power failure during a heating cycle, the system will restart the ignition sequence automatically when power is restored, if the thermostat still calls for heat. 4. GAS SUPPLY FAILURE If loss of flame occurs during a heating cycle, the system integrated control module will recycle the ignition sequence, then if ignition is not achieved, the integrated control module will shut offthe gas valve and lock out the system. 5. INDUCED Please refer troubleshooting 6. CONDENSATE DRAFT BLOWER FAILURE to the variable speed draft inducer manual for diagnostic assistance. DRAIN BLOCKAGE If the condensate drain is blocked, either by debris, improper draining, or by freezing condensate, the pressure switch will sense the accumulation of condensate in the furnace drain pan. The unit will not operate properly until the condensate drain has been cleared, and the condensate flows freely. 18-CD19D8-14 Installer's INTEGRATED 2 Flashes --- FURNACE CONTROL System Lockout (Retries RED LED "ERROR" Draft Pressure 3 Flashes --- or Recycles Guide FLASH CODES exceeded) Error - Possible problems: a) Venting problem b) Pressure switch problem c) Inducer problem 4 Flashes --- Open Temperature 5 Flashes --- Flame sensed when no flame should be present 6 Flashes --7 Flashes --- 115 volt AC power reversed, system voltage too low Gas valve circuit error 8 Flashes --- Low flame sense 9 Flashes --10 Flashes --- Open Inducer Limit switch Inducer communication error Solid --Solid Red w/Solid Green "STATUS" LED Internal GV error or Low TH voltage Continuous Limit Switch ignitor (Triac) fault, poor grounding or Reset caused by a blown fuse or internal error. 7. RESET AFTER LOCKOUT When the integrated control module has shut the system down and gone into lockout, the system must be manually reset before the unit will restart. The system can be reset by turning the system power offfbr more than 1 second, or by removing 24VAC from the control for more than 1 second, or by removing the thermostat call for heat for more than I second but less than 20 seconds. 8. RESET AFTER BURNER BOX LIMIT SHUTDOWN If the furnace shuts down, one thing that can be checked is the burner box temperature limit switch. It is located on the bottom of the burner box. The vent and combustion air inlet terminations should be checked for blockage. If blockage exists, clear the problem and then the reset button may be depressed. If there is no blockage of the terminations, the limit switch must be reset by a qualified servicer. Green Status LED FAULT CODE RECOVERY On power' up, last 4 fhults, if any, will be flashed on the red LED. The newest fault detected will flash first and the oldest last. There will be a 2 second delay between fault code flashes. Solid red LED error codes will not be displayed. The Green LED will be on solid during" last fault recovery. At any other time the control is powered, the Green LED indicator light will operate as shown in Table 14 and the red LED will flash LitePort data (one flash) every 20 seconds. *UX / DX Integrated Furnace Control TABLE 14 INTEGRATED GREEN FURNACE "STATUS" CONTROL LED FLASH CODES Flashing Slow --- Normal - No call for Heat Flashing Fast --- Normal - Call for Heat 18-CD19D8-14 Fault Code Reset The last 4 fault codes can be erased fl'om memory by powering up the control with "G" energized and then applying "R" to the "WI" terminal 3 times within 6 seconds. The control will acknowledge the reset by turning on the red LED for 2 seconds. 35 American Standard Inc. 6200 Troup Highway Tyler, TX75707 Formore information contact yourlecal dealer (distributor) 10/06 Since the manufacturer has a policy of continuous product and product data improvement, change design and specifications without notice. it reserves the right to
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 36 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Jun 29 00:14:08 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools