TRANE Furnace/Heater, Gas Manual L0702197

User Manual: TRANE TRANE Furnace/Heater, Gas Manual TRANE Furnace/Heater, Gas Owner's Manual, TRANE Furnace/Heater, Gas installation guides

Open the PDF directly: View PDF PDF.
Page Count: 36

IIIIII IIIIIIIIIIIIII IIIIIIIII
18- CD19D8- 1 4
10/30/06
s
Upflow /Horizontal &Downflow /Horizontal,
Gas-Fired, Direct Vent, 2-Stage Condensing
Furnaces with Variable Speed Inducer
*UX2B060A9362A *UX2B080A9422A *UX2C100A9482A
*UX2D120A9602A *DX2B060A9362A *DX2B080A9422A
*DX2C100A9482A *DX2D120A9602A
*__First lettermay be "A" or "T"
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT -- This Document is customer property and is to remain with this unit.
Please return to selwice information pack upon completion of work.
*UX2 *DX2
AiR
FLOW
UPFLOW
DOWNFLOW
A.'_
FLOW
G
AiRFLOW
/
UPFLOW /HORIZONTAL LEFT
\
i
OOWNFLOW,HOR,ZONTALR,GHT_o%_
/\
I
o
A341624P03
Installer's Guide
SAFETY SECTION
The following safety practices and precautions must be
fbllowed during the installation, servicing, and operation of
this furnace.
1. Use only with the type of gas approved for this furnace.
Refbr to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in "Location and Clearances" (page 3), of these
instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in "Air for Combustion and
Ventilation" (pages 7-8), of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as
specified in the "Venting _' section (pages 13-22), of these
instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections, as
specified in "Gas Piping" (page 28), of these instructions.
6. Always install the furnace to operate within the
furnace's intended temperature-rise range with a duct
system which has an external static pressure within the
allowable range, as specified on the unit rating plate.
Airflow with temperature rise for cfm versus static is
shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be
handled by a duct(s) sealed to the furnace casing and
temfinating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in "Location and
Clearances" section (page 3), of these instructions.
9. The furnace may be used fbr temporary heating of
buildings or structures under construction only when the
following conditions have been met:
a. The furnace venting system must be complete and
installed per manufacturer's instructions.
b. The furnace is controlled only by a room thermostat
(no field jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise must be
verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement must
come from outside the structure.
f. The furnace return air temperatm_ range is between
55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components upon
substantial completion of the construction process,
and verify furnace operating conditions including
ignition, input rate, temperature rise and venting,
according to the manufacturer's instructions.
10. This product must be gas piped by a Licensed Plumber or
Gas Fitter in the Commonwealth of Massachusettes.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4.
5.
Close fireplace dampers.
Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149
Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents where
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous conditions of use.
Safety signal words are used to designate a degree or level
of seriousness associated with a particular hazard. The
signal words for safety markings are DANGER, WARNING,
and CAUTION.
a. DANGER indicates an imminently hazardous situation
which, if'not avoided, will i_sult in death or serious injm%
This signal word is limited to the most extreme situations.
b. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious inj ui%
c. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
To prevent shortening its service life, the furnace should
not be used as a "Construction Heater" during the finishing
phases of construction until the requirements listed in item
9, a-g of the safety section of this publication have been
met. Condensate in the presence of chlorides and fluo-
rides from paint, varnish, stains, adhesives, cleaning
compounds, and cement create a corrosive condition which
may cause rapid deterioration of the heat exchanger.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
© 2006 American Standard Inc. All Rights Reserved 1 8-CD19D8-14
Installer's Guide
GENERAL
The manufacturer assumes no responsibility for equipment
installed in violation of any code or regulation.
It is reconunended that Manual J of the Air Conditioning
Contractors Association (ACCA) or A.R.I. 230 be followed in
estimating heating requirements. When estimating heating
requirements fbr installation at Altitudes above 2000 ft.,
remember the gas input must be reduced (See GAS INPUT
ADJUSTMENT).
Material in this shipment has been inspected at the
factory and released to the transportation agency
without known damage. Inspect exterior of carton for
evidence of rough handling in shipment. Unpack
carefully after moving equipment to approximate
location. If damage to contents is found, report the
damage immediately to the delivering agency.
Codes and local utility requirements governing the installa-
tion of gas fired equipment, wiring', plumbing, and flue
connections must be adhered to. In the absence of local
codes, the installation must conform with latest edition of the
National Fuel Gas Code ANSI Z223.1 National Installation
Code, CAN/CGA B149.1. The latest code may be obtained
fl_om the American Gas Association Laboratories,
8501 E. Pleasant Valley Rd., Cleveland, Ohio 44131.
These furnaces have been classified as CATEGORY IV
fhrnaees in aecordanee with latest edition of ANSI Z21.47
standards CAN/CGA 2.3. Category IV furnaces operate
with positive vent static pressure and with a flue loss less
than 17 percent. These conditions require special venting
systems, which must be gas tight and water tight. These
Category IV Direct Vent furnaces are approved for installa-
tion in Manufactured/Mobile housing when used with
BAYMFGH001A.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the
architect, the builder, or the installer. However, before the
furnace is moved into place, be sure to consider the following
requirements:
1. Is the location selected as near the chimney or vent and
as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums stated in Clearance Table
on the Outline Drawings.
3. Is there sufficient space fbr servicing the furnace and
other equipment? A minimum of 24 inches fi'ont accessi-
bility to the furnace must be provided. Any access door
or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the
furnace combustion air openings in the front panel and
any closed panel or door provided?
5. Are the ventilation and combustion air openings large
enough and will they remain unobstructed? If outside
air is used, are the openings set above the highest snow
aceunmlation level? (See the Air for Combustion and
Ventilation section.)
6. Allow sufficient height in supply plenum above the
furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components are
protected fi'om water.
8. If the furnace is installed in a residential garage, it
must be installed so that the burners, and the ignition
Contents
Installation Instructions
General
Location and Clearances
Outline Drawings
Upfiow Installation
Downfiow Installations
Air For Combustion and Ventilation
Duct Connections
Return Air Filters
General Venting
Venting Materials
Vent Tables
Horizontal Venting Through Wall
Venting Through the Roof
Venting Routed Through a Masonry Chimney
Downward Venting
Condensate Drain Instructions
Field Wiring Diagrams
Electrical Connections
Gas Piping
Combustion and Input Check
High Altitude Derate
Start-up and Adjustment
Preliminary Inspections
Lighting Instructions
Sequence of Operation
Control and Safety Switch Adjustments
Abnormal Conditions
IFC Error Flash Codes
Fault Code Recovery
source are located not less than 18 inches above the floor
and the furnace must be located or protected to avoid
physical damage from vehicles.
IMPORTANT:
The furnace must be installed level. The only allowable variation
would be slightly to the left and/or forward in upflow installations
or slightly toward the front in horizontal installations. This is
necessary for proper condensate drainage.
Do not install the furnace in a corrosive or contaminated
atmosphere. Failure to follow this warning could result in
early equipment failure.
Do not install the furnace directly on carpeting, tile or other
combustible material other than wood flooring. For vertical
downflow application, subbase (BAYBASE205) must be
used between the furnace and combustible flooring. When
the downflow furnace is installed vertically with a cased
coil, a subbase is not required.
18-CD19D8-14 3
J_
_o
6
EJ
q_
EJ
,co
4_
.ii
_5/8" 4 I/2 1_
tOUTLET
DIM "C-
i i A,RF;_
5/8" ji /
OUTSIDEAIR
_ 7/8" HOLE_
ELECTR ICAL_
SUPPLY _._'I
i/78" × 7/8"_._, '\'_ ."._ff_
SLOT KNOCKOUT _ _
CONDENSATE DRAIN _ _ _. .
(HORIZONTAL) __._
¢,,/8,,KNOCKOUT__ ._ _'
CONDENSATE DRA N _ _,_
4?
_L .
,8/8_ -_233/4
_28 I/2"_
DIM "D" INLET
AIR °
_24 1/32"_-I _3 7/32"
-_..._D,M"B"
_2"FLUE CONNECT
SEE NOTES I & 2
LDIM "E"
*UX2 UPFLOW /HORIZONTAL OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
_4 1/16"
_HOR I ZONTAL APPLICATION
_3 15/16" \/_,THIS
SIDE ONLY)
-2,/,6,,\_
T'/ _ --_ 40II
T 3os/8" o °I I
| /4,, °/
-,7/8_22,2,, I/I
I __=11
L 5 II _DIM "A"
_ I/2"
5 H
6 I/2"
Model DIM"A" DIM"B" DIM"C" DIM"D" DIM"E" DIM"F"
(See Note 1 & 2)
*UX2BO6OA9362A 17-1/2" 2-1/4" 16-1/4" 16" 7-1/2" 2"
*UX2BO8OA9422A
*UX2C1OOA9482A 21" 2-1/2" 19-3/4" 19-1/2" 9" 3"
*UX2D12OA9602A 24-1/2" 2-15/16" 23-1/4" 23" 10" 3"
* Prefix May Be "A" or "T" Notes:
1, *UX2D120A9602A Requires 3" Diameter Vent Pipe.
*UX20100A9482A Requires 2-1/2" or 3" Diameter Vent Pipe.
2. Diameter of Vent Pipe may be limited to 2-1/2" or 3" on some
models at different altitudes. Refer to the Vent Length Table for
proper application.
_7/8" KNOCKOUT
J ELECTRICAL
/SUPPLY
m2 I/I (ALTERNATE)
(ALTERNATE)
I/8" KNOCKOUT
DRAIN
(ALTERNATE)
I 5/16"
14 7/8"
I 9/16"
MINIMUMCLEARANCETO
COMBUSTIBLEMATERIALS
UPFLOW
SIDES O IN
REAR 0 IN
FRONT 3 IN
TOP I IN
FLUE O IN
HO_ZONTAL (FLUE
DISCHARGEON THE LEFTI
ALCOVE
SIDES
RIGHT O
LEFT 0
REAR 6
FRONT 18
TOP I
FLUE O
CLO_-T
SIDES
RIGHT I
LEFT I
REAR 3
FRONT 3
TOP I
FLUE O
From Dwg. 21 C341884 Rev. 1
m
i-I,
m
m
q
=,
n_
©
E_
r,D
E_
90
4_
5/8"
t
DIM "C"
5/8'
4,,2,d/
INLET
AIR " '
"-- 9-5/8"
4]/[ 6" _"4
HORIZONTAL
DRAIN
I 7/8" x 7/8"
SiO- KNOCKOUT
LECTRICAL
SvPPLY
_i I/2 'I
GAS CONNECTION
(ALTERNATE) KNOCKOUT
" 2 I FLUE
_,ONNECT
SEE NOTE i
DIM "B"
5 I_
3" OPENING
AIR INTAKE
FI/2 I
!
t
3_15/16 ''
t
DIM "D"
3/4" _.........................
3/41'_
OUTLET
AIR t
_T 3/41'
From Dwg. 21C341885 Rev, 1
*DX2 DOWNFLOW /HORIZONTAL OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
HORIZONTAL APPLICATION
(THIS SIDE ONLY)
i/2"] 2-I/8"_
CONNECTION
AIR INTAKE
-',-- DIM "A"
CONDENSATE DRAIN
_i5/16" KNOCKOUT
4
2i/16 ''_'
73/8" J _
Model DIM "A" DIM"B" DIM"C" DIM "D"
(See Note 1)
*DX2BO6OA9362A 17-1/2" 2-1/4" 16-1/4" 16"
*DX2BO8OA9422A
*DX2C100A9482A 21" 2-1/2" 19-3/4" 19-1/2"
*DX2D12OA9602A 24-1/2" 2-15/16" 23-1/4" 23"
* Prefix May Be "A" or "T" Notes:
1, Diameter of Vent Pipe may be limited
to 2-1/2" or 3" on some models at
different altitudes. Refer to the Vent
Length Table for proper application.
ELECTRICAL
CONNECTION (ALTERNATE)
KNOCKOUT
_iI/2" GAS
CONNECTION
¢_-1/8 ,I
CONDENSATE DRAIN
KNOCKOUT
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
OOWNFLOW
S_DES o FN
REAR 0 IN
FRONT 3 IN
TOP I EN
FLUE 0 IN
HORIZONTAL)FLUE
BSCHARGE ON THE LEFT)
ALCOVE
SIDES
R_GHT O IN
LEFT O IN
REAR 6 IN
FRONT 18 IN
TOP IN
FLUE IN
CLOSET
SIDES
RIGHT IN
LEFT IN
REAR IN
FRONT IN
TOP IN
FLUE IN
I
el
I,,,k
I
I
q
€__,
O,
Installer's Guide
UPFLOW INSTALLATION
Standoff5 and screws (See Figure 1) are included with the CABINET RETURN
cased coils for attachment to the furnace. There are clear- WIDTH DUCT WIDTH
ance alignment holes near the bottom of the coil wrapper.
Drill screws are used to engage the furnace top fanges. The 14-1/2" 13-1/4"
standoff is inserted into the cabinet alignment hole. The drill 17-1/2" 16-1/4"
screws are inserted through the standoft_ then screwed into 21" 19-3/4"
the furnace flange. The coil is always placed downstream of 24-1/2" 23-1/4"
the furnace airfow.
iiiiiiiiiiiiiilliliiiiliiiiliiiiliiiiliiiiliiiiliiiili
FOR VERTICAL
STANDOFFS
(BOTH SIDES)
DOWNFLOW INSTALLATIONS
CABINET SIDE_
SUB=BASE
FLANGE -_.
SDB=OASE L
COMllUS,I,IBI,E
FLOOIt
CABINET SIDE
SUB-BASE
FLANGE
(BENT UP)
Do not install the furnace directly on carpeting, tile or other
combustible material other than wood flooring. For
vertical downflow application, subbase (BAYBASE205)
must be used between the furnace and combustible
flooring. When the downflow furnace is installed vertically
with a cased coil, a subbase is not required.
Required floor opening: (DOWNFLOW)
See Figure 3 and Table I
TABLE 1
FLOOR OPENING PLENUM OPENING
"A .... B.... C.... D"
13-5/8" 20-1/8" 12-5/8" 19-3/8"
16-5/8" 20-1/8" 15-5/8" 19-3/8"
20-1/8" 20-1/8" 19-1/8" 19-3/8"
23-5/8" 20-1/8" 22-5/8" 19-3/8"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in
the horizontal position. It is always recommended that an
auxiliary drain pan be installed under a horizontally in-
stalled evaporator coil or 90% gas furnace. Connect the
auxiliary drain line to a separate drain line (no trap is
needed in this line).
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the furnace
and TXC cased coil in the horizontal position. See Fig-
ure 4. The coil is placed downstream of the furnace, with the
apex of the coil pointing in the direction of the airfow for
horizontal installation. The cased coil is secured to the
furnace and both the furnace and the cased coil must be
properly supported. The brackets mount using the rear
screws on the coil case and use the screws provided to secure
the bracket to the furnace. The remaining bracket is placed
as close to center as possible (horizontally)between the coil
case front and the furnace bottom channel (for downflow/
horizontal furnace). Use four of the screws provided to
secure the bracket. The upflow furnace, converted to horizon-
(_) CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
tal, aligns and attaches the TXC coil as in Figure 1. However,
the coil requires additional support.
The furnace may be installed in an attic or crawl space in the
horizontal position by placing the furnace on the left side (as
viewed fl'om the front in the vertical position). The horizon-
tal furnace installation in an attic should be on a service
platform large enough to allow fbr proper clearances on all
sides and service access to the front of the furnace (See
Figure 5 & Clearance Tables, pages 4-5). Line contact is only
permissible between lines formed by intersections of the top
and two sides of the furnace casing and building joists, studs,
or fl'aming.
The furnace may be placed horizontally in a crawl space on a
pad or other noncombustible material which will raise the
unit for sufficient protection fl'om moisture. The furnace
UPFLOW/
HORIZONTAL
SHOWN WITH
DIRECT VENT
6 18-CD19D8-14
Installer's Guide
®
50 CU. FT. OR MORE
UNCONFINED
.... \ /
WATER CLOTHES
must be supported at both ends and the middle when
installed horizontally. The furnace must also be
elevated approximately 4-6 inches to allow clearance
for the condensate drain to exit the cabinet in the
horizontal position.
The horizontal furnace may also be suspended from the joists
using 3/8" all-thread rods with pieces of angle iron under-
neath the furnace to form a hanging rack at both ends and
the midpoint. The rods need to be of sufficient length to
allow fbr proper clearances fi'om combustible materials. The
angle iron needs to be at least 32" in length to allow for
access to service panels.
AIR FOR COMBUSTION AND VENTILATION
If"these furnaces are installed in a nondirect vent capacity
then the adequate flow of combustion and ventilating air
must not be obstructed from reaching the furnace. Air
openings provided for combustion air must be kept fi'ee of
obstructions which restrict the flow of air. Airflow restric-
tions affbct the efficiency and safe operation of the furnace.
Keep this in mind should you choose to remodel or change
the area which contains your furnace. Furnaces must have a
fl'ee flow of air for proper performance.
Provisions for combustion and ventilation air shall be made
in accordance with latest edition of Section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1 -- CAN/CGA B149.1 or applicable provisions of
the local building codes. Special conditions created by
mechanical exhausting of air and fireplaces must be con-
sidered to avoid unsatisfactory furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals or
contamination. Certain types of installation will require
the use of outside air for combustion.
The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in "confined" laundry rooms
* Furnaces installed in "confined" hobby or craft rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air
supply will also require OUTDOORAIR for combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refl'igerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fhbric softeners for clothes dryers
* MasomT acid washing materials
Furnace locations may be in a "confined space" or an
"unconfined space".
Unconfined space is defined in Figure 6. These spaces may
have adequate air by infiltration to provide air for combus-
tion and ventilation. Buildings with tight construction (for
example, weather stripping, heavily insulated, caulked, vapor
barrier, etc.), may need additional air to be provided as
described for confined space.
Confined spaces are installations with less than 50 cu. ft. of
space per 1000 BTU/hr input fl'om all equipment installed.
Air for combustion and ventilation requirements can be
supplied from inside the building as in Figure 9 or fl'om the ..................................................................
outdoors, as in Figure 10.
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE WITH 8 FT. CEILING
MAXIMUM BTUH MINIMUM AREA IN SQUARE FEET
INPUT RATING OF UNCONFINED SPACE
60,000 375
80,000 500
100,000 625
120,000 875
®
CONFINED
SPACE LESS THAN 50 CU. FT.
PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED
1. All air fl'om inside the building as in Figure 9: The
confined space shall be provided with two permanent
openings communicating directly with an additional
room(s) of sufficient volume so that the combined volume
of all spaces meets the criteria for an unconfined space.
The total input of all gas utilization equipment installed
in the combined space shall be considered in making this
determination. Refbr to Table 2 for minimum open areas
requirements.
2. All air fl'om outdoors as in Figure 10: The confined space
shall be provided with two permanent openings, one
commencing within 12 inches of the top and one com-
mencing within 12 inches of the bottom of the enclosure.
The openings shall communicate directly, or by ducts,
with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors. Refbr to Table 2, for
minimum open areas requirements.
TABLE 2
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING
Furnace
Maximum
BTUH/INPUT
Rating
Air
From
Inside
FURNACE ONLY)
Air From Outside
Vertical Horizontal
Duct Duct
60,000 100 15 30
80,000 100 20 40
100,000 100 25 50
120,000 120 30 60
718-CD19D8-14
Installer's Guide
®
CONFINED SPACE
AIR FROM INSIDE BUILDING
CONFINED --
SPACE
PERMANENT
OPENINGS
®
CONFINED SPACE
AIR FROM OUTDOORS
CONFINED
SPACE
IIL
II/ OUTDOOR
AIR DUCTS
INLET
CONFINED SPACE _'_
AIR FROM VENTILATED ATTIC/CRAWL SPACE
_UVERS
TO OUTDOORS
ALTCIN LEETR_II_ E_D _ _ --.OUTLET
AIR
INLET
AiR DUCT
CONFINED SPACE
AIR FR(
TO OUTDOORS
CONFINED.
SPACE
.OUTLET
AIR
INLET
AIR DUCT
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire Protec-
tion Association Pamphlet No. 90. They should be sized in
accordance with ACCA Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling" units,
shall be installed in parallel or on the upstream side of the
cooling coil to avoid condensation in the heat exchanger. With
a parallel flow arrangement, the dampers or other means used
to control flow of air shall be adequate to pi_vent chilled air
fl'om entering the furnace, and if manually operated, must be
equipped with means to prevent operation of either unit
unless the damper is in full heat or cool position.
On any job, flexible connections of"nonflammable material may
be used for retta'n air and discharge connections to prevent
transmission of"vibration. Though these units have been
specifically designed fbr quiet, vibration fi'ee operation, air ducts
can act as sounding boards and could, if poorly installed,
amplify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to the
living area, the system should be carefully designed with
returns to minimize noise transmission through the return
air grille. Although these furnaces are designed with large
blowers operating at moderate speeds, any blower moving a
high volume of air will produce audible noise which could be
objectionable when the unit is located very close to a living
area. It is often advisable to route the return air ducts under
the floor or through the attic. Such design permits the
installation of air return remote fi'om the living area (i.e.
central hall).
When the furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by a duct(s) sealed to the furnace and terminating outside
the space containing the furnace.
RETURN AIR DUCT SYSTEMS
Where there is no complete return duct system, the
return connection must be run full size from the
furnace to a location outside the utility room, base-
ment, attic, or crawl space.
Do Not install return air through the back of the furnace
cabinet.
Do Not install return air through the side of the furnace
cabinet on horizontal applications.
NOTE:
Minimum return air temperature is 50 °F.
All return air duct systems should provide for installation of
return air filters.
1. Set the furnace in place.
2. For upflow side return installations, remove the insula-
tion around the opening" in the blower compartment.
3. The side panels of the upflow furnace include locating"
notches that are used as guides fer cutting" an opening"
for return air, refer to Figure 11 and the outline
drawing" on page 4 for duct connection dimensions for
various furnaces.
NOTE:
On upflow 5 ton airflow models, if the airflow requirement
exceeds 1800 CFM, these models will require return air
openings and filters on both sides; OR I side and the
bottom; OR just the bottom.
8 18-CD19D8-14
Installer's Guide
4. Ifa 3/4" fllange is to be used fbr attaching" the air iMet duct,
add to cut where indicated by dotted lines in Figure 11.
Cut corners diagonally and bend outward to form flange.
5. If flanges are not required, and a filter' fl'ame is installed,
cut between locating" notches (Figure 11).
6. The bottom panel of the upflow furnace must be re-
moved for' bottom return air. Remove the filter and lay
the furnace on its back. Remove the two 1/4" hex screws
securing the bottom front channel to the cabinet. Lower
the fl'ont edge of the bottom front channel and pull
forward to remove the channel. The bottom return air
panel will now easily slide out of the cabinet. Reinstall
the bottom front channel and filter' for upflow bottom
return installations.
7. The filter retainer is factory supplied for upflow bottom
return. Use the filter retainer on side or bottom if filter
is to be used within the furnace cabinet on upflow only
installations.
8. The horizontal installation of the upflow furnace
requires an external filter section. Do NOT use the
bottom return filter within the furnace. Filter kits
are available for horizontal applications.
9. Connect duct work to furnace. See Outline Drawing" for
supply and return duct size and location. Flexible duct
connectors are recommended to connect both supply and
return air ducts to the furnace. If only the fl'ont of the
furnace is accessible, it is recommended that both supply
and return air plenums are removable.
RETURN AIR FILTERS (NOT SUPPLIED)
TYPICAL UPFLOW RETURN AIR FILTER
INSTALLATIONS
Filters are not factory supplied for these furnaces. These
furnaces require high velocity type air filters. The filters may
be located within the furnace blower compartment for
UPFLOW furnaces in either a BOTTOM or SIDE (left side or
right side) return air inlet. Some filters may need to be
trimmed for side or bottom filter use.
TABLE 3
MODELS CABINET FILTER
NUMBERS WIDTH QTY & SIZE
*UX2B060A9362A 17-1/2" 1 - 17" X 25" X 1"
*UX2B080A9422A
*UX2C100A9482A 21" 1 - 20" X 25" X 1"
*UX2D120A9602A 24-1/2" 1 - 24" X 25" X 1"
* First letter may be "A" or "T"
** NOTE - On 5 ton airflow models, if the airflow requirement exceeds
1800CFM,these models will require return air openings and filters
on both sides; OR 1 side and the bottom; ORjust the bottom,
UPFLOW FURNACE ONLY
LOCATING
NOTCHES PRO-
VIDED FOR SIDE
RETURN CUTOUT
*-. t
SEE OUTLINE DRAWING
!
/CUT OUT FOR
SIDE FILTER
RONT
of Furnace
NO TE:
On upflow 5 ton airflow models, if the airflow requirement
exceeds 1800 CFM, these models will require return air
openings and filters on both sides; OR 1 side and the
bottom; OR just the bottom.
The upflow furnace blower door has a hinge at the bottom
which allows the door to tilt forward for filter replacement
without the door being removed (See Figure 12). The furnace
filter in the bottom or side configuration can be removed by
simply turning the two latches on the blower door and tilting
the door forward.
The filter rails are spring loaded for automatic adjustment to @
allow standard size, locally obtainable replacement filters.
The filter rack itself slides to adjust to the required width ..................................................................
needed for bottom or side return (See Figure 13).
BOTTOM FILTER RACK INSTALLATION
With the filter removed, the filter rack is compressed and
then inserted into the bottom of the furnace. The retaining
screw/pin on each side inserts into engagement holes at the
bottom of the furnace cabinet side,
Blower Door Hinge and Bottom Filter Rack Installation
FILTER
RACK "_
RETAINING
PIN
(Both Sides)
Optioinal Filter Rack Accessory Kit - BAYRACK960A
18-CD19D8-14 9
Installer's Guide
Blower Deck __ II Furnace
EogagemeotII " II Cabinet
Hole II _11/II Side
Engagement Hole
For Filter Rack
Installation With
_ "": tl IB°tt°m Return
ENGAGEMENT
HOLE DETAIL
(Typical both sides
and blower deck) BLOWER
OPTIONAL FILTER RACK INSTALLATION FOR SIDE RE-
TURN AIR ON UPFLOW FURNACES (Left or Right)
If side air return is desired, it is necessary to move the filter
rack from the bottom of the furnace and reinstall it on the
side. The fbllowing instructions should be used:
a. Open or remove the blower door.
b. Remove the filter'.
Compress the filter rack to disengage the retaining"
pins/screws from the furnace sides and slide the filter
rack out.
d. Leave the bottom panel in place.
e. After the side cutout is made fbllowing the directions
in the "Return Air Duct Connections" section on
pages 8 and 9, compress the filter rack and reinstall
in the side of the furnace. Confirm that the upper
retaining pit, screw locks into the engagement hole in
the blower deck and the lower pit, screw rests against
the side of the bottom panel. See Figures 15-19.
f. Reinstall the furnace filter on the side inserting the
chamfer end first.
®
Furnace
Cabinet
Side
Engagement Hole
For Filter Rack
Installation With
Bottom Return
Filter
Rack
Filter Rack
Retaining
Screw/Pin
BOTTOM ENGAGEMENT
Filter Rack
Retaining
Screw/Pin Filter
Rack
I
Engagement Hole
For Filter Rack Blower
Installation With
Side Return Deck
Furnace
Cabi net,,,,,]l_
Side
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
Retaining Rack
Screw/Pin Assembly
\
FILTER BOTTOM
RACK PANEL
RAILS INSTALLED
Typical Upflow Left Side Return Filter
Rack Installation
Optional Filter Rack Accessory Kit - BAYRACK960A
10 18-CD19D8-14
Typical Upflow Right Side Return Filter Rack Installation
@
CHAMFER
END OF
FILTER GOES
INTO FILTER
RACK FIRST
RETURN AIR FILTERS FOR UPFLOW FURNACE IN
HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in the horizontal
config'uration, the return air filters must be installed exterior
to the cabinet. Remote filter grilles may be used for home-
owner convenience or the filters may be installed in the duct
work upstream of the furnace. See Figure 21.
O
]
TYPICAL RETURN AIR FILTER INSTALLATION IN
UPFLOW MODEL IN HORIZONTAL POSITION
Installer's Guide
BLOWER DOOR/HINGE REMOVAL
If clearance or other problems create a problem in using the
tilting door, the blower door hinge may be removed without
creating any problems with the seal of the furnace. To remove
the blower door, tilt the door fblnvard 2 to 3inches and pull up.
To remove the tilt feature, simply remove the lower hinge as
shown in Figure 22. The bottom of the blower door will catch
in the bottom of the fm'nace fi'ont channel fbr door' replacement.
Door Hinge Removed
ALTERNATE UPFLOW FILTER CLIP /BRACKET
INSTALLATION (KIT09224)
1. Determine the location to be used. The furnace cabinet
has dimples for location of the alternate furnace clips
(Side return only). Pre-drill clearance holes with a 3/16"
drill. Bottom return holes are pre-drilled.
2. Install the clips in fi'ont and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet.
@
ALTERNATE FILTER
CLIPS LOCATION
FILTER CLIP - KIT09224
18-CD19D8-14 11
Installer's Guide
INSTALLING THE FILTER
The filter may need to be cut to fit the unit depending" on the
location of the return air filter.
A score line and the words "CUT HERE" are located on the
end of the filter. If your application requires cutting the
filter, do so as indicted by the score mark.
UNIT
SIZE
17-1/2"
21"
24-1/2"
RETURN AIR
BOTTOM
DO NOT CUT
DO NOT CUT
DO NOT CUT
SIDE
DO NOT CUT
CUT ON LINE
CUT ON LINE
TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER
INSTALLATIONS
Two filters are factory supplied for each downflow furnace.
These furnaces require high velocity type air filters. Down-
flow furnace filters must be located outside the furnace
cabinet. Typical installations are shown in Figure 24.
Tables 5 and 6 provide information for installation of the
filter retaining" brackets shipped with downflow furnaces.
TABLE 4
MODELS CABINET FILTER
NUMBERS WIDTH QTY & SIZE
*DX060R936 17-1/2" 2- 14"X20"X 1"
*DX080R942
*DX100R948 21" 2- 16"X 20"X 1"
*DX120R960 24-1/2" 2 - 16"X 20"X 1"
*First letter may be "A" or "T"
TABLE 5
LOCATING FILTER RETAINER BRACKETS IN
DUCTWORK
CABINET RETURN DIMENSION DIMENSION FILTER
WIDTH DUCT "A .... B" BRACKET
WIDTH LOCATION'
17-1/2" 16-1/4" 15" 14" 14-3/8"
21" 19-3/4" 19-1/2" 14" 13-1/8"
24-1/2" 23-1/4" 22" 14" 13-5/8"
' LOCATION DIMENSION IS FROM END OF DUCT AGAINSTTHE FURNACE TO THE
SCREW HOLES FOR THE BRACKET.
@Optional
BAYFLTR206
Door Kit
DOWNFLOW
Airflow
TABLE 6
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/HORIZONTAL FURNACES
UNIT LOCATION
VERTICAL HORIZONTAL HORIZONTAL
FURNACE SURFACE CLOSET CLOSET ALCOVE /ATTIC
SIDES 0" 1" 0"
BACK 0" 3" 6"
TOP 1" 1" 1"
FRONT 3" 3" 18"
VENT 0" 0" 0"
NOTE: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
12 18-CD19D8-14
The following warning complies with State of California law, Proposition 65.
Hazardous Gasest
Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to
cause cancer, birth defects, or other reproductive harm.
Carbon monoxide, fire or smoke can cause serious bodily
injury, death, and/or property damage.
A variety of potential sources of carbon monoxide can be
found in a building or dwelling such as gas-fired clothes
dryers, gas cooking stoves, water heaters, furnaces and
fireplaces. The U.S. Consumer Product Safhty Commission
recommends that users of gas-burning appliances install
carbon monoxide detectors as well as fire and smoke detec-
tors per the manufactureffs installation instructions to help
alert dwelling occupants of the presence of fire, smoke or
unsafh levels of carbon monoxide. These devices should be
listed by Underwriters Laboratories, Inc. Standards" for
Single and Multiple Station Carbon Monoxide Alarms',
UL 2034 or CSA International Standard, Residential
Carbon Monoxide Alarming Devices, CSA 6.19
NO TE:
The manufacturer of your furnace does not test any detec-
tors and makes no representations regarding any brand or
type of detector.
GENERAL VENTING
THIS FURNACE MUST BE VENTED TO THE OUTDOORS.
THESE FURNACES ARE INDUCED DRAFT VENTED
AND MUST NOT BE CONNECTED TO ANYVENT SERV-
ING ANOTHER APPLIANCE. PLEASE NOTE THAT
THESE FURNACES USE POSITIVE-PRESSURE VENT
SYSTEMS.
Proper venting is essential to obtain maximum efficiency
fi'om a condensing furnace. Proper installation of the vent
system is necessary to assure drainage of the condensate
and prevent deterioration of the vent system.
American Gas Association has certified the design of con-
densing furnaces for a minimum of 0" clearance from com-
bustible materials with a single wall plastic vent pipe.
The recommended system is assembled fi'om 2", 2-1/2", or 3"
plastic pipe and fittings (See Table 7, page 15). Where the
system is routed to the outdoors through an existing masomT
chimney containing flue products fi'om another gas appliance,
or where required by local codes, then 3" venting of Type 29-4C
stainless steel must be used in place of PVC material
These furnaces have been classified as CATEGORY IV
furnaces in accordance with ANSI Z2L47 "latest edition"
standards. Category IV furnaces operate with positive vent
pressure and with a vent gas temperature less than 140 ° F.
above the dewpoint. These conditions require special venting
systems, which must be gas tight and water tight.
NO TE:
When an existing furnace is removed from a venting
system serving other gas appliances, the venting system is
likely to be too large to properly vent the remainincl
attached appliances.
Installer's Guide
The following steps shall be followed with each appliance
remaining connected to the common venting system placed
in operation, while the other appliances remaining connected
to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion or other deficiencies which
could cause an unsafe condition.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building. Turn
on clothes dryers and any appliances not connected to
the common venting system. Turn on any exhaust fhns,
such as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer
exhaust fan, close fireplace dampers.
4. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance will operate continuously.
5. After it has been determined that each appliance remain-
ing connected to the common venting system properly
vents when tested as outlined above, return door, win-
dows, exhaust fens, fireplace dampers and any other gas-
burning appliance to their previous conditions of use.
If improper venting is observed during any of the above tests,
the remaining common venting system must be corrected.
Correction could require rerouting or resizing the remaining
vent system.
IMPORTANT:
These furnaces may be installed as Direct Vent (sealed com-
bustion) or as Nondirect vent (single pipe). The furnaces are
shipped DIRECT VENT with sealed combustion.
For DIRECT VENTAPPLICATION: The furnaces must be
vented to the exterior of the house and combustion air MUST
come through the inlet air pipe FROM OUTSIDE AIR. The pipes
DO NOT have to exit the exterior of the house together or on the
same side of the house.
For NONDIRECT VENT APPLICATION: The furnace shaft be
vented to the exterior of the house, but combustion air may
enter from the surrounding area as long as combustion air
requirements are met. (See AIR FOR COMBUSTION AND
VENTILATION)
FURNACE VENT/INLET PIPE INSTALLATION
There are many different variations of the vent/inlet air pipe
combination. The vent/inlet air combination used for instal-
lation of these furnaces depends on the needs of the location.
However, these guidelines must be followed:
1. The furnace must vent outside the structure.
2.
3.
Furnace combustion air requirements must be met for
nondirect, single pipe applications (See example on
next page).
For direct vent application of these furnaces, the vent
pipe and air inlet pipe do not have to exit in the same air
space or even on the same surfhce of the structure.
However, the longest individual pipe will decide the value
[br the longest allowable equivalent vent/inlet air length
as shown in the vent length table.
18-CD19D8-14 13
Installer's Guide
NOTE:
BAYVENT200* accessories can be used for inlet and outlet
terminals when the pipes do not exit the structure together.
The following are EXAMPLES ONLY:
Vent
Air
Inlet
EX. 1 i
Furnace
Example I shows that the vent may go vertical while the inlet
air may be on any side of the structure. The vent pipe would
decide the maximum equivalent length for the pipe depending
on the furnace and pipe size.
z2:
Air _ i
Inlet_
(See Note)
EX. 2 1
Example 2 shows the vent pipe exhausting through the roof
and the inlet air coming fi'om the interior of the house (See
Note). The inlet air coming fi'om the interior of the house
must meet combustion requirements for area, etc., as shown
in the section AIR FOR COMBUSTION AND VENTILA-
TION in this Installer's Guide.
Air
Inlet
_ Furnace
Vent
EX. 31
Example 3 shows the vent exiting one side of the house while
the inlet air is on the opposite side of the structure. Here the
vent pipe length must be within the allowable length for the
size offht_ace and size of the vent pipe. This example
demonstrates that the pipes do not have to exit on the same
side of the structure.
Attic
Air J IIII
Furnace U
EX. 41
The inlet air does not have to come It'om outside the structure.
Example 4 shows the inlet air (See Note), may come from the
attic if the requirements for combustion air are met as shown
in the section AIR FOR COMBUSTION AND VENTILATION.
NOTE:
If only the flue gas pipe is to the outside of the structure, a
straight section of pipe (long enough to exit the furnace
cabinet) must be attached to the inlet air side with an elbow
(which is 5 to 10 equiv, ft.) installed on the end to prevent
dust and debris from falling directly into the furnace.
VENT FITTING MATERIAL-PLASTIC
Gas and liquid tight single wall vent fittings, designed for
resistance to corrosive flue condensate, MUST be used
throughout.
Listed in Table 7 are 2", 2-1/2", and 3" size fittings that meet
these requirements. The materials listed are various grades
of PVC and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to
prevent escape of combustion products into the building.
NOTE:
It is recommended that the first joints from the furnace be
connected and sealed with high temperature RTV. This will
enable the pipes to be removed later without cutting.
Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement for PVC must be
used to join PVC pipe fittings. Follow instructions on con-
tainer caretully.
Pipe and Fitting- ASTM D1785, D2466, D2661, & D2665
PVC Primer and Solvent Cement -ASTM D2564
Procedure for Cementing Joints - RefASTM D2855
1. Cut pipe square, remove ragged edges and burrs.
ChamIbr end of pipe, then clean fitting socket and pipe
joint area of all dirt, grease, moisture or chips.
2. Aider checking pipe and socket for proper fit, wipe socket
and pipe with cleaner-primer. Apply a liberal coat of
primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLY-
ING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly
apply a heavy coat of cement to the pipe end and insert
pipe into fitting with a slight twisting movement until it
bottoms out.
14 18-CD19D8-14
Installer's Guide
4. Hold the pipe in the fitting for 30 seconds to prevent
tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement fl'om the joint with a rag. Allow
15 minutes before handling. Cure time varies according
to fit, temperature and humidity.
NO TE:
Follow venting instructions carefully when using PVC
cement.
IMPORTANT:
All joints must be water tight. Flue condensate is somewhat
acidic, and leaks can cause equipment damage.
TABLE7
PVC VENT FITTING MATERIAL These fittings are available from your Gas Furnace Distributors.
i_ 4-1/2" _
WALL MOUNT FLANGE
BAY69X 148
2-3/16"
_5-5/8" -_
WALL MOUNT FLANGE
BAY69X 147
PLASTIC PIPE DESIGNATIONS
PVC
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
F891 CELLULAR CORE "158 ASTM F891
D2665 DWV PIPE *'158 ASTM D2665
D1785 SCH 40, 80, 120 *'158 ASTM D1785
D2241 SDR SERIES *'158 ASTM D2241
CPVC
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
D2846 CPVC 41 *'212 ASTM D2846
F441 SCH 40, 80 *'212 ASTM F441
F442 SDR SERIES *'212 ASTM F442
ABS
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
D2661 SCH 40 DWV **'180 ASTM D2661
F628 SCH 40 DWV CELLULAR CORE **'180 ASTM F628
- Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)]
** - Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)]
*** - Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)]
Connection of the pipe and collar of the combustion air inlet
should just be a fl'iction fit. It is recommended that the inlet
air joint be sealed with RTV type sealant to allow the joint to
be separated for possible future service. The inlet and vent
pipes must be properly supported throughout the entire
length.
Connection of the vent pipe to the vent collar should also be
accomplished using" RTV type sealant. This type sealant
provides a connection which remains flexible and can be
separated in the future if service needs require the removal
of the vent pipe for service or clearance.
NO TE:
Vent termination kit BA YAIR30AVENTA or BA YVENT2OOB
may be used in addition to the horizontal and vertical
termination options shown in the following figures.
VENT AND INLET AIR CONNECTIONS
Seal VENT PIPE
with RTV sealant
FrontofFumace
Seal INLET AIR PiPE
with RTVsealant
18-CD19D8-14 15
Installer's Guide
VENT LENGTH TABLE
MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET
ALTITUDE FOR VENT AND INLET AIR (SEE NOTES)
0-7,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE
UX2/DX2B060A9362A 200 200 200
UX2/DX2B080A9422A 50 120 200
UX2/DX2C100A9482A Not Allowed 60 200
UX2/DX2D120A9602A Not Allowed Not Allowed 200
7,000-9,500 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE
UX2/DX2B060A9362A 100 100 100
UX2/DX2B080A9422A 25 60 100
UX2/DX2C100A9482A Not Allowed 30 100
UX2/DX2D120A9602A Not Allowed Not Allowed 100
9,500-12,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE
UX2/DX2B060A9362A 50 50 50
UX2/DX2B080A9422A Not Allowed 30 50
UX2/DX2C100A9482A Not Allowed Not Allowed 50
UX2/DX2D120A9602A Not Allowed Not Allowed 50
NOTES: * - First letter may be "A" or "T"
1. Minimum vent length for all models: 3' horizontal or 3' vertical.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except
adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the
maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger
diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS
THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
4. One SHORT radius 90 ° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe.
One 90 ° elbow is equivalent to 71/2' of 21/2'' pipe or 5' of 2" pipe. Two 45 ° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is
used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
6. Pipe adapters are field supplied (except 120).
HORIZONTAL INSTALLATION
(Upflow /Horizontal or Downflow /Horizontal)
NO TE:
In horizonal venting when the factory supplied "off-set" (2)(3
reducing coupling) is used for 3"' vent pipe installation, make
sure the marking "Top" is located on the top side of the pipe.
The straight side must be on bottom for proper condensate
drainage. This coupling is factory supplied only with the
followinqmodels: UC120 & DC120, UX120 & UY120
UXIO0_ UYIO0, UX808C960, andall DX & DYmodels.
LABEL
SAYS
"TOP"
2" TO 3" COUPLING
_I_RY SUPPLIED ONLY WITH
THE FOLLOWING MODELS:
UC120 & DC120
120 & UY120
|UXl00 & UYIO0
UX0800960
ALL DX & DY MODLES
VENT
OUTLET
16 18-CD19D8-14
G
Installer's Guide
\6"
MAX
6"
MAX
ELBOW AND TEE MUST BE
AS CLOSE TOGETHER
AS POSSIBLE
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS
@NOTE:
COMBUSTION
AIR INLET
n
STRAPS OR OTHER SUITABLE SUPPORTS
OF 3'-0" INTERVALS USE ONLY
APPROVED
TERMINATION
/"
40" UPFLOW OR
DOWNFLOW MODELS NOTE: ANY FITTINGS PASSING
THROUGH AN UNHEATED SPACE
MUST BE INSULATED.
VENT AND INLET MUST BE SUPPORTED
AT A MAXIMUM OF 3' INTERVALS
VENT
COMBUST]ON AIR
STRAP
(FIELDSUPPLIED)\
ELBOW
(FIELD
SUPPLIED)
COMBUSTION
AIR
RAIN CA[
1" +1/2"
BAYAIR3OAVENTA
45'ELBOW
STUB CUT AT
45 °ANGLE
_/TEE _ FIELD SUPPLIED _J_l" _-::'i!_
r_ [j ,PNEEDED\J_
BA YVENT2OOB _
WALL CAVITIES
18-CD19D8-14 17
Installer's Guide
12" MINIMUM
TO OVERHANG
SCREWS
"(4 req.)
/
VENT
CAP
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
BAYVENT200A/B
®
BAYAIRJOAVENTA
(Sidewall)
When the vent pipe is exposed to temperatures below
freezing, i.e., when it passes through unheated spaces, etc.,
the pipe must be insulated with 112 inch (22.7 mm) thick
Armaflex-type insulation or equal.
If the space is heated sufficiently to prevent freezing, then
the insulation would not be required. If domestic water
pipes are not protected from freezing then it is assumed the
space meets the condition of a heated space.
HORIZONTAL VENTING THROUGH WALL
These furnaces may he installed as direct vent (as
shipped) or as nondirect vent. Installation must
conform to national, state, and local codes.
The vent & inlet terminals must be located at least 12"
minimum above normally expected snow accumulation level.
Avoid areas where staining or condensate drippage may be
a problem.
Location of the vent/wind terminal should be chosen to meet
the requirements of Figure 39 fbr either direct or nondirect
vent applications.
PITCH -- Venting through the wall must maintain 1/4" per
foot pitched upward to insure that condensate drains back to
the furnace.
FLUE GAS DEGRADATION -- The moisture content of
the flue gas may have a detrimental effect on some building
(_ COUPLING PVC WALL MOUNT
(PLASTIC FLANGE
VENTING )
6IN Mli'
,,](TO JOIN
12"MIN. ABOVE
NORMALLY EXPECTED
1" CLEARANCE SNOW ACCUMULATION
( AIR SPACE )
VENTING THROUGH COMBUSTIBLE WALLS
Pitch -- 1/4 Inch Per Ft.
CLEARANCE ( 0"ACCEPTABLEFOR PVCVENT PIPE )
I" ACCEPTABLEFORTYPE 29-4CSTAINLESSSTEELVENT PIPE
@
COUPLING
(PLASTIC
VENTING )
/6IN. MIN.
II(TOJOINT )
PVC WALL MOUNT
FLANGE
90_ELBOW
CEMENT 12"MIN.ABOVE
MORTAR SEAL NORMALLYEXPECTED
INSIDE & SNOWACCUMULATION
OUTSIDE
VENTING THROUGH NON-COMBUSTIBLE WALLS
Pitch - 1/4 Inch Per Ft.
materials. This can be avoided by using the roof or chimney
venting option. When wall venting is used on any surfhce
that can be affbcted by this moisture, it is recommended that
a corrosion resistant shield (24 inches square) be used behind
the vent terminal. This shield can be wood, plastic, sheet
metal, etc. Also, silicone caulk all cracks, seams and joints
within 3 fbet of the vent terminal.
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials must be
maintained when using single wall stainless steel venting.
See Figure 31.
Shield material to be a minimum of 24 gauge stainless or
aluminized sheet metal. Minimum dimensions are 12"x12".
Shield must be fastened to both inside and outside of wall.
Use screws or anchor type fhsteners suited to the outside or
inside wall surthces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to maintain
pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall. See
Figure 32.
18 18-CD19D8-14
@
Installer's Guide
SUPPORT HORIZONTAL PIPE EVERY 3' 0"
WITH THE FIRST SUPPORT AS CLOSE TO
THE FURNACE AS POSSIBLE. INDUCED
DRAFT BLOWER, HOUSING, AND
WEIGHT OF THE FLUE PIPE.
cou__b ,
ff IIII
40" UPFLO_" OR DOWNFLOVV FURNACE
HOPJZONTAL AND VERTICAL VENTICAL
iii7i_7}{i{iiiiiiiii{
®VENT
9" MIN.
M,tO,MUM NOT TO EXCEED
DISTAF4CEFROM TOP _ I I _ 24 INCHESABOVE ROOF
BE 12* _ 1" J
#
COMBUSTION
AIR INLET
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
VENT
REMOVE RIBS 'i
FROM CAP
COMBUSTION AIR
(F,EL2OU%%<_
VENT
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
[
(FIELD SUPPLIED)
[_\ _1_MouST'oN
BAYAIR30AVENTA (VERTICAL)
,PIPE,
COUPLING AND METAL PANEL
WITH HI TEMP RTV SILICONE SEALANT
COUPLING
SUPPORT
CEILING
GALVANIZED FIRESTOP SHOULD
BE FABRICATED WITH 3-7/8" BIA.
HOLE FOR SUPPORT FLANGE
(12" x 12" PANEL OR 12" DIA MIN.)
CLEARANCE (0" ACCEPTABLE FOR PVC VENT PIPE )
(1" ACCEPTABLE FOR TYPE 2B-4C STAINLESS STEEL VENT PIPE )
VENTING THROUGH CEILING
18-CD19D8-14 19
Installer's Guide
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC vent pipe, a 2" electri-
cal conduit flashing" may be used for a weather tight seal.
Lubricate flexible seal on flashing before PVC pipe is pushed
through the seal. (Field Supplied)
NOTE:
No vent cap as shown in Figure 34 is the preferred method
for vertical vent termination in extremely cold climates.
In extreme climate conditions, insulate the exposed pipe
above the roof line with Armaflex type insulation.
VENT FITTING MATERIAL - STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed
for resistance to corrosive flue condensate such as Type
29-4C MUST be used throughout.
These fittings and fitting" accessories are to be supplied
locally.
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting" must be installed with male end
towards the furnace.
All horizontal stainless steel sections must be positioned
with the seam on top.
All long" horizontal sections must be supported to prevent
sagging.
All pipe joints must be fhstened and sealed to prevent escape
of combustion products into the building.
PVC PLASTIC VENTING - ONLY
THROUGH UNUSED CHIMNEY
STAINLESS STEEL
VENT CAP /
(OPTIONAL)_ J |
FLUE PIPE _.__ "_ 6_,_N.
COUPL,NGTO WALLFLUEP,PEAND
PiPE FROM ANGLES _,_z, , _._ _ XJ CENTER IT IN THE
OR OTHER SUITABLE _ q 1/, ,_ CHIMNEY OPENING WITH
SUPPORT METHOD _-_ r_ _J ANGLES AS SHOWN OR
"_L 4 1S ANOTHER EQUIVALENT
COUPLING
__/,,_ AS REQUIRED
u
(/'_" / NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
Do not run vent through chimney for wood burning or
oil furnaces or incinerators or any other gas appliance.
IMPORTANT -
The single wall flue pipe joints must be sealed.
The 90°elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
®SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL
WITH HI TEMP RTV SILICONE SEALANT
N
SUPPORT
FLANGE i
i
FLOOR
I ...........
FLUE PIPE
CLEARANCE
(0" ACCEPTABLE FOR PVC VENT PIPE)
(1" ACCEPTABLE FOR TYPE 2_C STAINLESS STEEL VENT PIPE)
TYPE 29-4C STAINLESS STEEL VENTING -
USED THROUGH CHIMNEY THAT VENTS
ANOTHER GAS APPLIANCE
STAINLESS STEEL
VENT CAP
(OPTIONAL)
SEE CAUTION 6 IN. MIN.
SUPPORT THE SINGLE WALL
STAINLESS STEEL GAS
VENTING AND CENTER IT IN
THE CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
Do not run vent through chimney for wood burning or oil
furnaces or incinerators.
If remaining free area between single wall flue pipe and
masonry chimney is to be used for another gas appliance
venting area must be sufficient to vent that appliance and
that appliance must be connected to chimney with
separate entry openings.
IMPORTANT -
The single wall flue pipe joints must be sealed.
The 90 °elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
VENTING ROUTED THROUGH A MASONRY CHIMNEY
20 18-CD19D8-14
®
Installer's Guide
HORIZONTAL VENT CLEARANCES
J
[] VENTTERMINAL (_ AIR SUPPLY INLET [] AREA WHERE TERMINAL IS NOT PERMITTED
Non-Direct Vent Terminal Clearances
Canadian Installations US Installations
A= Clearance above grade, veranda, porch, deck, or 12 inches (30 cm) 12 inches (30 cm)
balcony
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) 4 feet (1,2m) below or to the side of opening;
B= Clearance to window or door that may be opened and =/< 100,000 Btuh (30 kw), 1 foot (0,3m) above opening.
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
C= Clearance to permanently closed window
Vertical clearance to ventilated soffit located above
D= the terminal within a horizontal distance of 2 feet
(61 cm) from the center line of the terminal
E= Clearance to unventilated soffit
F= Clearance to outside corner
G= Clearance to inside corner
Clearance to each side of center line extended 3 feet (91 cm) with a height 15 feet (4.5 m) above the
H= above meter/regulator assembly meter/regulator assembly
I= Clearance to service regulator vent outlet 3 feet (91 cm)
Clearance to nonmechanical air supply inlet to 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) 4 feet (1,2 m) below or to side of opening;
J= building or the combustion air inlet to any other and =/< 100,000 Btuh (30 kw), 1 foot (300 m) above opening
appliance 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
K= Clearance to a mechanical air supply inlet 6 feet (1.83m) 3 feet (91 cm) above if within
10 feet (3m) horizontally
Clearance above a paved sidewalk or paved
L= driveway located on public property 7 feet (2.13 m) 1- 7 feet (2.13 m)
M= Clearance under veranda, porch, deck, or balcony 12 inches (30 cm)
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2, In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code,
1, A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
:_, Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor,
*Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
18-CD19D8-14 21
Installer's Guide
Direct Vent Terminal Clearances
Canadian Installations US Installations
Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm)
A= deck, or balcony
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
Clearance to window or door that may be 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
B= opened and =/< 100,000 Btuh (30 kw), and =/< 50,000 Btuh (15 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw) 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
C= Clearance to permanently closed window
Vertical clearance to ventilated soffit
located above the terminal within a
D= horizontal distance of 2 feet (61 cm)
from the center line of the terminal
E= Clearance to unventilated soffit
F= Clearance to outside corner
G= Clearance to inside corner
Clearance to each side of center line 3 feet (91 cm) with a height 15 feet (4.5 m) above the
H= extended above meter/regulator assembly meter/regulator assembly
I= Clearance to service regulator vent outlet 3 feet (91 cm)
Clearance to nonmechanical air supply 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
J= inlet to building or the combustion air and =/< 100,000 Btuh (30 kw), and =/< 50,000 Btuh (15 kw),
inlet to any other appliance 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw) 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
K= Clearance to a mechanical air supply inlet 6 feet (1.83m) 3 feet (91 cm) above if within 10 feet (3m) horizontally
L= Clearance above a paved sidewalk or 7 feet (2.13 m) 1
paved driveway located on public property
Clearance under veranda, porch, deck, 12 inches (30 cm) :_
M= or balcony
Notes:
1, In accordance with the current CSA B149,1 Natural Gas and Propane Installation Code.
2, In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
1. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
:_. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
@DOWNWARD VENTING _._Iv
Furnace may be in vertical or horizontal configurat_1 _
All horizontal pipes must be
supported at maximum of 3
foot intervals
Slope 1/4" per ft.
J
Slope 1/4" per ft. -II
L
I I
DOWNWARD VENT LENGTH IS
LIMITED TO A MAXIMUM OF 15
SEQUIVALENT_FEET.
40 Inch
SEE __ Upflow or
NOTES Downflow
Furnace
W-
6" Min.
_t_ ,
NOTES:
A) Condensate trap for vent pipe must be a minimum of 6 inches in height.
B) Condensate trap for vent and inlet pipe must be connected into a condensate drain pump; an open or
vented drain; or it can be connected to the outlet hose of the furnace's condensate trap. Outdoor drain-
ing of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken
to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Exces-
sive draining of condensate may cause saturated ground conditions that may result in damage to plants.
c) The condensate trap should be primed at initial start up prior to heating season operation.
22 18-CD19D8-14
Installer's Guide
CONDENSATE DRAIN INSTRUCTIONS
prT_ [o,T._uluul[o]_I
It is recommended that a drain pan be installed under the
furnace to prevent property damage, personal injury or
death from leaking condensate.
Downflow furnace - The turnace is shipped with the lett
side drainage setup. To change the right side drain, remove
the drain lines from the trap, rotate the trap 180 ° so it exits
to the right, reconnect the lines, and run a 1/2" CPVC pipe
fl'om the trap out through the right side knock-out. Use RTV
silicone sealant to connect the CPVC pipe to the trap for ease
of removing to clean the trap.
VERTICAL APPLICATIONS
Upflow furnace - The connection tubing fbr left and right
side drainage is shipped in the blower compartment. Install
the connection tubing fl'om the trap to the side of the unit and
trim all excess tubing to avoid kinks.
UPFLOW (VERTICAL)
HORIZONTAL APPLICATIONS
Upflow and Downflow furnaces - All horizontal applica-
tions are left side only. It is always recommended that the
auxiliary drain pan be installed under a horizontally in-
stalled evaporator and/or 90% gas furnace, Connect the
Right side
Left side
UPFLOW (VERTICAL)
Use Inducer Drain
hose without
extension
UPFLOW HORIZONTAL 17" UNITS
(Left side only)
Use
extension
hose here
UPFLOW HORIZONTAL 21" & 24" UNITS
(Left side only)
18-CD19D8-14 23
Installer's Guide
auxiliary drain pan to a separate drain line (no trap is needed
in this line).
The trap must be repositioned to the exterior of the cabinet.
Remove the trap from its present location and reposition the
trap outside of the unit, through the long circular hole, next to
the secondary recouperative cell. Remove the larger drain line
(from the secondary cell) and trim to fit between the second-
ary cell and the new trap location. On upflow units, plug" the
hole in the blower deck where the tube went through.
Remove the hose fi'om the induced blower and reposition into
the other drain tap of the inducer, which is located 90 °
clockwise around the inducer. Move the cap fi'om that drain
tap to the unused drain tap. On upflow units, plug" the hole in
Left
side
DOWNFLOW (VERTICAL)
Right
side
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
DOWNFLOW (VERTICAL)
Cut off curved end of
Inducer drain hose
DOWNFLOW (HORIZONTAL)
the blower deck where the tube went through. This tube on
downflow units will need to be cut to fit between the inducer
and the trap. On upflow units, this tube may need to be
extended, using the tubing shipped with the furnace.
Connections must be made to an OPEN/VENTED DRAIN.
Outdoor draining of the furnace and coil condensate is
permissible if allowed by local codes. Caution should be taken
to prevent drains fi'om freezing or causing slippery conditions
that could lead to personal injury. Excessive draining of
condensate may cause saturated ground conditions that may
result in damage to plants.
NO TE:
Use 1/2" or larger PVC or CPVC pipe and fittings as required
for drain connections (fittings, pipe and solvent cement not
provided).
NO TE:
A corrosion resistant condensate pump must be used ffa
pump is required for a specific drain system.
IMPORTANT:
The condensate drain should be installed with provisions to
prevent winter freeze-up of the condensate drain line. Frozen
condensate will block drains, resulting in furnace shutdown. If
the drain line cannot be installed in a conditioned space, then
UL listed heat tape should be applied as required to prevent
freezing (per manufacturer's instructions). The heat tape should
be rated at 5 or 6 watts per foot at 120 volts. Self-regulating
(preferred) or thermostatically controlled heat tape is required.
Evaporator and furnace condensate drain piping may be
manifolded together. A primary drain vent stack must be
installed and terminated below the outlet of the secondary
heat exchanger drain connection to prevent water fi'om
damaging furnace controls if the primary drain outlet plugs
up. Where the furnace is installed above a finished ceiling,
the primary drain vent stack must be installed such that
overflow fi'om the vent stack opening will flow into an
auxiliary drain pan in order to prevent water damage to the
finished ceiling below.
24 18-CD19D8-14
Installer's Guide
If upflow furnace is installed
over a finished ceiling, overflow
from the primary drain vent
the finished ceiling below.
Primary drain vent stack
must terminate below
secondary heat exchanger
condensate drain outlet.
To drain opening
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
2 _TAGE
I STAT FURNACE NOTES:
F.............................7 SEE .............................
NOTE7
L-- _IN I BE SURE POWER AGREES WITH EQUIPMENT NAMPLATE(S}.
2. LOW VOLTAGE 124V WIRING> TO BE NO. 18 A.W.G MIN..
3GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES
4, SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM.
S THESE LEADS PROVIDE llS V, POWER FOR CONNECTION OF ELECTRONIC AIR
CLEANER AND HUMIDIFIER MAN, LOAD l,O AMPS EACH
6 THIS CONNECTION IS ONLY USED FOR THERMOSTATS REQUIRING
CONNECTION TO THE 24 V POWER SUPPLY (COMMON}
SEE 7 SEE TWINNING CONNECTION DIAGRAMS FOR PROPER CONNECTIONS
I _ I_TE_ WHEN UGING THIS FEATURE
8WHEN A HEATING THERMOSTAT IWITHOUT FAN SWITCH} IS USED,
NO WIRING ON "G" TERMINAL OF IFC IS USED.
9 Wl AND W2 MUST BE JUMPERED TOGETHER FOR PROPER OPERATION
SECOND STAGE HEATING WILL BEGIN IO MINUTES AFTER FIRST STAGE
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING
USING A 2 STAGE HEATING THERMOSTAT
NO COOLING
2 STAGE
T'STAT FURNACE
-- SEE --
NOTE 7
L_[_
[] []
[]
[] []
SEE
[] NOTE []
INTER COMPONENT WIRING
24 V. _FIELD----LINE V. WIRING
24 V. _L FACTORY
--LINE V.jr WIRING
NOTES
I.
2.
3.
4.
5.
BE SURE POWER AGREES WITH EQUIPMENT NANPLATE(S)
LOW VOLTAGE (24V. WIRING) TO BE NO. 18 A.W G MIN
GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.
SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM,
THESE LEADS PROVIDE 115 V POWER FOR CONNECTION OF ELECTRONIC AIR
CLEANER AND HUMIDIFIER MAX. LOAD 1.0 AMPS EACH.
THIS CONNECTION IS ONLY USED FOR THERMOSTATS REQUIRING
CONNECTIONTO THE 24 V. POWERSUPPLY. (COMMON)
SEE TWINNING CONNECTIONDIAGRAMSFOR PROPERCONNECTIONS
WHENUSING THIS FEATURE.
N EMROu N D
SC R E '¢;
'll
TO115V1 PH., /_ H
60 HZ,, POWER J
SUPPLY PER /
LOCALCODES / =t N
HUM SEE
NOTE 5 i B_
EAC SEE _ iK --
NOTE 5 LFrom Dwg. 21B342024 Rev. O
18-CD19D8-14 25
Installer's Guide
OUTDOORUNIT
{NOTRANSFORMER)
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING, 1 STAGE COOLING
USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
T'STAT
[]
SEE
] NOTE8
[]
[]
[]
SEE
] NOTE6
(OUTDOOR SECTION WITHOUT TRANSFORMER)
2 STAGE
FURNACE
SEE N01S:
NOTE7 [] _}: SLRF [r,,, i*%R S Jiili [,,,J_" ,/;,[' NAtq_ ,!,IF ', S)
L.--,,- 2 01¢ v01T,,,D (24V i_ RJN{?) T0 _[ 0 8 /', _A _ _ ; N
3GRO NDING 0 EOU PV N1 qUS COY Y W'H LOCt, L CODES
4 S i li;EigOS AI lEA AN I?[l:A OR P RUN i WlF, JKG DJAGPA_d
] S N _i LE,_DS "Rr' _ Dr' R FOR CO'4q[CI ON 0 EiE{ ROqi A R
," :_,NiR ,e'\3 JP I} ::!..... MAX OA} 0 o_" [#('1
6 ' S CONNECilOk S ON Y USE[} 0_ !ERvOS AIS R OU RING
] ,,_, f #,i
_1 a_l uN 10 lie 24 PO',_,;ERSU PLY ,CCqM@,',
] S}E TWINr :/,'5C0r'I' C i0N " A;_&,,S FOI PR('_Ei r_,
kqER US NG l IS E A 8!E
8 Y' E/VlNINA !Oq liE El RMOS A' _,'JSI BE 'gRID
] TO T E 'Y' TERb N,SL OR THE FUR'U, CE CONTRO FOR PROPER BIO'¢_ R
0' RAIION DLJ(IP{ ,.,k/" 1'
[]
[]
@
i
i
IN I FR ( OvlE )ON NT vNi/:,: L_
24 V. let [
24 t,. k FACTORY
--NE /'¢,'_RiNO
/
,ll
L II
TO 115V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES N
GROUND
_ SCREW
BK
FURNACE
JUNC[ iON
BOX
HUM SEE
NOTE 5
EAOSEE::
NOTE 5 From Dwg. B342021 Rev. 0
OUTDOOR UNIT
(NO TRANSFORMER)
[]
[]
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
2 STAGE
T'STAT FURNACE NOTES:
SEE
NOTE 7 1 BE SURE POWER AGREES WITH FOU}PMENT NAMPLATE(S}
2, !OW VOltAGE (24V WIRING) ]0 BE NO 18 AWG M}N,
L._ 3 GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAl CODES
4, SEE TNERMOS]AI HEAl ANTICIPAIOR PER UNI[ WIRING DIAGRAM
5. TIIESE LEADS PROVIDE 115 V. POWER FOR CONNECTION OF ELECTRONIC AIR
r_ CLEANER AND HUMIDIFIER MAX LOAD I0 AMPS EACH
6THIS CONNECTION !S ONLY USED FOR THERMOSTATS REOU!RING
SEE CONNECTION 10 THE 84 V POWER SUPPLY (COMMON)
NOTE8 _ 7SEE TW!NN}NG CONNECTION DIAGRAMS _OR PROPER CONNECTIONS
WHEN USING [HIS EEAIURE
8 TI4E "Y" TERMININAL FROM THE THERMOSTAT MUST BE WIRED
TO THE "Y" TERMINAL QF THE FURNACE CONTROl FOR PROPER BIOWER
OPERAIION DURING COOLING
9 Wl AND W2 MUST BE JUWERED TOGETHER FOR PROPER OPERATION
SECOND STAGE HEATING WILL BEG!N IO MINUTES AFTER FIRST STAGE
[]
i
rq_-
SEE
i
i
N ,, (.#,,P_N N ,R_N
24 V F:IF I)
----LINE V. ,'b_R ] N (_
24 V. FAC ORY
--L]k V, WR NG
FIELD ADDED ............._.........................]_/_ F U R N ACE
JUMPER(NOTE9) ,11 / _ _ gu c 1ON
I_ : Box
704?%% =
LOCAL CODES _ _. wl,
/3
HUM SEE I-- _1 II
NOTE5 _ BK Jr
Wl
EAC SEE / --
NOTE 5 L" BK From Dwg. B342019 Rev. 0
26 18-CD19D8-14
Installer's Guide
OUTDOOR UNIT NO. 1 1 STAGE
(WITH TRANSFORMER) HEATING /COOLING
SEE NOTE 3 THERMOSTAT
OUTDOOR UNIT NO. 1
10 TRANSFORMER)
%
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
1 STAGE HEAT /1 STAGE COOLING THERMOSTAT
FURNACE NO. 1
ON BOTH UNKS
2NDSTAGEWILL FIRE
10M_NUTESAFTBR1ST
SEENOTE5
FURNACE NO. 2
BLOWEROPERATIONOF
UN_NO2 iSSYNCR_q_ZED
W_TNUNITNO 1VIASIGNALS
F_M TWINC_NECTION
SEENOTE4
F _ ,
Rli _ ',
...... i
_SOLAT_ONRELAY
SEENOTE4
tO _S
tfiOTH FCRNACESMUST BE Pg#ERED FROI#
_i_ SAt41 r_SV L_of H_{UfT P4NH
_t_$L'RE24_ FUF2_IA_ TRAt,rSFOR_4E@SAR_'
,W P_ASI¸ _'i_,iO_ 0 CO'@L T_Nd_CO,<_rCNO_,iS,
CH_C_ _IO__A6_ _ _#N_ R f_i_r_,_S O_¸
_AO,¸ FUR4A_,£ _VOLT_G_ _S¸ £:Rr_A_E# T_,_i
Ot_Ot_E OF T_E #U_?t_ACET_At_S_OR;eERS
30t79_0,_ Utf HAS A Z4V _RA_ ORU¢
1_ LD SUi' if US! itLOT ou?f RMA_
(2C SUC A_ R _0975 SE_ _T CO_N[CTtOt
INTER COMPONENT W]R]NG
24 V. "% FIEL D
----LINE V.j WIRING
24 V. "_ FACTORY
--L]NE V.jr WIRING
From Dwg. 21B341336 Rev. 2
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
2 STAGE HEAT /1 STAGE COOLING THERMOSTAT
OUTDOOR UNIT NO. I 2 STAGE HEATING
(WITH TRANSFORMER) 1 STAGE COOLING
SEE NOTE 3 THERMOSTAT
<%
: _ _/'_..............
FURNACE NO. 1
[
OUTDOOR UNIT NO. 1 I _ =:TZ]
_O TRANSFORMER) I
I
i=
..........................I ..........................
(FIE_DSUP_UED)
SEE NOTE4
o
R1 _> ',
, I
_T: ::
R21"> i ;
I
I
I
I
I
....... I
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO 2 IS SYNORONIZED
WITH UNIT NO 1 VIA _GNALB
I
\
\
_o7_ uRt#,tc_s '_us 5_ #o¢,_0 fro!4
;t sJ_d rSV ¢ _ of t{ u #_,,,'f
_FrH_ SdPP_,iE_ dSE P_CT ObT_¸RELAr
_gO_',i _DO NC_ CO!_C_ _ _0 W_
_¢b4HOt_ _,'_Y t,'O_ _,_£_ d¸ T,_¸ N_R_O_
_SOCAT_ONRELAy CO,';T_C_ _?_ RATED 4_ _ "_4 0__A_OVE
SEENOTE4
m T
F'; i INTER COMPONENT WIRING
,, o
iQ i 24 V "_ FIELD
£----LINE' V.j>- WIR IN G
24 V. "_ FACTORY
--LINE V.jr WIRING
From Dwg. 21 B341337 Rev. 2
{ {iiiiiiii
18-CD19D8-14 27
Installer's Guide
OUTOOORUNIT NO 2 2 SaGE HEATENG
(NO TRANSFORMER) 1 STAGE ¢OOUNG
SEE NOTE 3 THERMOSTAT
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
2 STAGE HEAT /2 STAGE COOLING THERMOSTAT
FU_NACENOI
_OTES:
S_ BOT_FUrnACESMUSTBE POWE_E_f_OM
FURNACENO_2 T_E SA_E n_W LEGOFC_Rcwr PANEL.
BLUEROPER_'ONOF
Ji/ _ J o
[ ' ..................
ISOLATIONRE_¥
(FIELDSUPPLIED)
ALTERNATECONNECTION
b I I
B}O INTER COMPONENT WIRING
ALrE_ATE_t_l_6 CO_rI_e_ATSO_
'S[[ _Og 4
24 V. _ FIELDLINE M. WIRING
24 V, _ FACTORY
--LINE V.jr WIRING
I (NO TRANSFORMER)
i i.................................................
,,, 1
i d>
R2; "C,
From Dwg 218341338 Rev 2
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the venting
system being placed into operation could result in carbon
monoxide poisoning or death.
ELECTRICAL CONNECTIONS
Make wiring" connections to the unit as indicated on enclosed
wiring" diagram. As with all gas appliances using electrical
power, this furnace shall be connected into a permanently
live electric circuit. It is recommended that furnace be
provided with a separate "circuit protection device" electric
circuit. The furnace must be electrically grounded in accor-
dance with local codes or in the absence of local codes with
the National Electrical Code, ANSI/NFPA 70 or CSA C22.1
Electrical Code, if an external electrical source is utilized.
The integrated furnace control is polarity sensitive.
The hot leg" of the 120V power supply must be connected to
the black power lead as indicated on the wiring diagram.
Provision _br hooking up an electronic air cleaner and or
humidifier is provided on the integrated control.
Refer to the SERVICE FACTS literature and unit wiring
diagram attached to furnace.
28 18-CD19D8-14
@
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
?
MAIN MANUAL
SHUT-OFF VALVE
GROUND
UNION
JOINT
DRIP
LEG
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
MAIN MANUAL --
SHUT-OFF VALVE
GROUND
UNION
JOINT
DRIP _
LEG
UPFLOW MAY BE LEFT OR
RIGHT HAND GAS PIPING
@
Installer's Guide
io I
THE DOWNFLOW (VERTICAL) MAY BE INSTALLED
LEFT OR RIGHT SIDE GAS PIPING
(_ AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
SH%%_#UL%........................./_"11
GROUND /_DR
UNION JOINT LEG !_
MAIN MANUAL
SHUT-OFF
VALVE
/GROUND UNION JOINT
LEG
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF II
HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE
(Typical UPFLOW Furnacein horizontalconfigurationshown)
18-CD19D8-14 29
Installer's Guide
GAS PIPING
The upflow/horizontal furnace is shipped standard for left
side installation of gas piping. A knockout is provided on the
right side for an alternate gas piping arrangement. See Figure
45.
The installation of piping shall be in accordance with piping
codes and the regulations of the local gas company. Pipe joint
compound must be resistant to the chemical reaction with
liquefied petroleum gases.
Refer to piping Table 8, fbr delivery sizes. Connect gas supply
to the unit, using a ground joint union and a manual shut-off
valve as shown in Figures 44 & 45. National codes require a
condensation drip leg to be installed ahead of the controls as
shown in Figures 45 & 46.
Use a backup wrench on the gas valve when installing gas
piping to prevent damage to the gas valve and manifold
assembly.
The furnace and its individual shut-offvalve must be discon-
nected fi'om the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.5 kPa).
The furnace must be isolated from the gas supply piping by
closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
NOTE:
Maximum pressure to the gas valve for natural gas is 13.8"
1/11.(7,,Minimum pressure is 5,0" VV.C. Maximum pressure to
the gas valve for propane is 13,8" I/1!.(7,,Minimum pressure
is 11,0" W,C.
All gas fittings must be checked for leaks using a soapy
solution before lighting the furnace. DO NOT CHECK
WlTI-I AN OPEN FLAME!
TABLE 8
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE LENGTH OF PIPE
SIZE 10 20 30 40 50 60 70
1_ 132 92 73 63 56 50 46
3/4 278 190 152 130 115 105 96
1 520 350 285 245 215 195 180
1-1/4 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SEGR. gas
TABLE 9
ORIFICE SIZES
INPUT
RATING
BTUH
60,000
80,000
100,000
120,000
NUMBER
OF
BURNERS
3
4
5
6
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GAS LP GAS
45 56
45 56
45 56
45 56
COMBUSTION AND INPUT CHECK
(See also High Altitude Derate)
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (deter-
mine the dial rating of the meter) for one revolution.
3. Match the "See" column in the gas flow (in efh) Table 10
with the time docked.
4. Read the "Flow" column opposite the number of seconds
clocked.
5. Use the following factors if necessary:
For I Cu. Ft. Dial Gas Flow CFH =
Chart Flow Reading + 2
For 1/2 Cu Ft. Dial Gas Flow CFH =
Chart Flow Reading + 4
©CORRECT METHOD OF CHECKING DIRECT VENT MANIFOLD
PRESSURE WITH BURNER BOX REFERENCED
See
inset
]
Separate the tube I
at the unit Tee and H_
reconnect with a F-_ I1"
short piece of field "--) ]]
suppliedtubeand __ Jl
I
anotherTeewith //
the"U"Manometer ,_/,/
attached. _ 2:2:::_.. "_,__-_,_
Besure to reconnect [{ _.=_,:. _.))
unittubing to original -- _ \'\ \
positionaftertesting -- ___\\\
themanifoldpressure! _-.\ "-Jkz_-,
(71
Fieldsu bedbarbtiti'in_ /_
• pp. "g
manometertub:';:° t
attachedto the "OUTLET
PRESSURETAP" onthe
outlet side of the gas valve,
CAUTION: Return all tubing, caps, and/or plugs to original positions when pressure checks are completed.
30 18-CD19D8-14
For 5 Cu. Ft. Dial Gas Flow CFH --
10X Chart Flow Reading + 4
6. Multiply the final figure by the heating value of the gas
obtained fl'om the utility company and compare to the
nameplate rating. This must not exceed the name-
plate rating.
7. Changes can be made by adjusting the manifold pressure
(See Table 11), or changing orifices (orifice change may
not always be required). To adjust the manifold pressure:
a. Turn offall electrical power to the system.
b. Attach a manifbld pressure gauge to the outlet
pressure tap marked "OUT PRESS TAP" on
White-Rodgers gas valve model 36E or boss marked
"OUT P" on White-Rodgers gas valve model 36G. (See
Figure 48 fbr White-Rodgers gas valve model 36E and
Figure 49 for White-Rodgers gas valve model 36G).
For the gas valve model 36E, measurements require
removal of the plug and installation of a barbed
fitting. Attach flexible tubing and a manometer to the
barbed fitting. For the gas valve model 36G, do not
remove the pressure tap test screw. Loosen the
pressure tap test screw one turn and install flexible
tubing and a manometer directly onto the outlet
pressure boss.
c. The other side of the manifold pressure gauge must be
referenced to the burner box as shown in Figure 46.
d. Turn on system power and energize valve.
e. For the White-Rodgers gas valve model 36E:
TABLE 10
GAS FLOW IN CUBIC FEET PER HOUR
2CUBIC FOOT DIAL
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8 900 29 248 50 144 82 88
9 800 30 240 51 141 84 86
10 720 31 232 52 138 86 84
11 655 32 225 53 136 88 82
12 600 33 218 54 133 90 80
13 555 34 212 55 131 92 78
14 514 35 206 56 129 94 76
15 480 36 200 57 126 96 75
16 450 37 195 58 124 98 73
17 424 38 189 59 122 100 72
18 400 39 185 60 120 104 69
19 379 40 180 62 116 108 67
20 360 41 176 64 112 112 64
21 343 42 172 66 109 116 62
22 327 43 167 68 106 120 60
23 313 44 164 70 103 124 58
24 300 45 160 72 100 128 56
25 288 46 157 74 97 132 54
26 277 47 153 76 95 136 53
27 267 48 150 78 92 140 51
28 257 49 147 80 90 144 50
TABLE 11
FINAL MANIFOLD PRESSURE SETTINGS (inches w.c.)
FUEL 2nd Stage Max. 1st Stage Max.
NATURAL GAS 3.5" W.C. 1.7" W.C.
LP GAS 10.5" W.C. 6.0" W.C.
Installer's Guide
1. Adjust low fire by removing the low adjustment
seal screw (See Figure 48).
2. To increase outlet pressure, turn the 3/32" socket
set screw clockwise. To decrease outlet pressure,
turn the set screw counterclockwise. Adjust
regulator until pressure shown on manometer
matches the pressure specified in Table 11.
3. Replace low adjustment seal screw and tighten
securely.
4. Cycle the valve several times to verify regulator
setting.
5. Adjust high fire by removing the high adjustment
seal screw (See Figui_ 48).
6. To increase outlet pressure, turn the 3/32" socket
set screw clockwise. To deci_ase outlet pressure,
turn the set screw counterclockwise. The final
manifold pressure setting shall be as specified in
Table 11 with an input of no more than nameplate
rating and no less than 93_i of the nameplate
rating, unless the unit is derated for high altitude.
7. Replace high adjustment seal screw and tighten
securely.
8. Cycle the valve several times to verify regulator
setting.
HIGH ALTITUDE DERATE
Input ratings (BTUH) of these furnaces are based on sea
level operation and should not be changed at elevations up to
2,000 ft.
If"the installation is 2,000 ft. or above, the furnace input rate
(BTUH) shall be reduced 4% for each 1,000 ft. above sea level.
The furnace input rate shall be checked by clocking the gas
flow rate (CFH) and multiplying by the heating value
obtained from the local utility supplier for the gas being
delivered at the installed altitude. Input rate changes can be
made by adjusting the manifold pressure (min 3.0 - max
3.7 in. W.C. - Natural Gas) or changing orifices (orifice change
may not always be required).
If the desired input rate cannot be achieved with a change in
manifold pressure, then the orifices must be changed. LP
installations will requite an orifice change.
IMPORTANT:
Reinstall the propane orifices to the same depth as the orifices
supplied with the equipment.
See Table 13 fbr help in selecting orifices if orifice change is
required. Furnace input rate and temperature rise should be
checked again after changing orifices to confirm the proper
rate for the altitude.
The vent len_h table on page 16 shows the required vent
lengths for installations at various altitudes. An optional
high altitude kit is available fbr installations above 5000 feet
Installations above 12,000 feet are not allowed).
TABLE 12
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44
45
46
47
48
49
50
PART
NUMBER
ORF00501
ORF00644
ORF00909
ORF00910
ORF01099
ORF00503
ORF00493
DRILL
SIZE
54
55
56
57
58
59
PART
NUMBER
ORF00555
ORF00693
ORF00907
ORF00908
ORF01338
ORF01339
18-CD19D8-14 31
Installer's Guide
TABLE 13
Orifice
Twist Drill ALTITUDE ABOVE SEA LEVEL
Size If
Installed and Orifice Required At Other Elevations
At Sea
Level 200C 3000 4000 5000 6000 7000 8000 9000 10000
42 42 43 43 43 44 44 45 46 47
43 44 44 44 4,5 45 46 47 47 48
44 45 45 45 46 47 47 48 48 50
45 46 47 47 47 48 48 49 49 50
46 47 47 47 48 48 49 49 50 51
47 48 48 49 49 49 50 50 51 52
54 54 55 55 55 55 55 56 56 56
55 55 55 55 56 56 56 56 56 57
56 56 56 57 57 57 58 59 59 60
57 58 59 59 60 60 61 62 63 63
58 59 60 60 61 62 62 63 63 64
From National Fuel Gas Code - Table F-4
White-Rodgers 36E
C>
2nd Stage (HI)
Manifold
Pressure
Adjustment
Gas Valve On /Off
Toggle Switch
1st Stage (LO)
Manifold
Pressure
Adjustment
@White-Rodgers 36G Stage (HI)
Manifold
Pressure
Adjustment
Stage (LO)
Manifold
Pressure
Adjustment
Gas Valve On /Off
Toggle Switch
f. For the White-Rodgers gas valve model 36G:
1. Adjust low fire by removing the low adjustment
regulator cover screw (See Figure 49).
2. To increase outlet pressure, turn the regulator
adjust screw clockwise. To decrease outlet pressure,
tui_ the regulator adjust screw counterclockwise.
Adjust regulator until pressure shown on mano-
meter matches the pressure specified in Table 11.
ROTATE THE FRONT
COVER AS SHOWN
INSERT THE TOP FLANGE
OF THE FRONT COVER
UNDER THE LIP INSIDE
THE BOX
ALL SIDE FLANGES MUST
BE OUTSIDE OF THE BOX
ROTATE THE FRONT
COVER INWARD MAKING
SURE THAT ALL SIDE
FLANGES ARE OUTSIDE
OF THE BOX.
3. Replace and tighten the regulator cover screw
securely.
4. Cycle the valve several times to verify regulator
setting.
5. Adjust high fire by removing the high adjustment
regulator cover screw (See Figure 49).
6. To increase outlet pressure, turn the regulator
adjust screw clockwise. To decrease outlet pressure,
turn the regulator adjust screw counterclockwise.
The final manifold pressure setting shall be as
specified in Table 11 with an input of no more than
nameplate rating and no less than 93% of the
nameplate rating, unless the unit is derated for
high altitude.
7. Replace high adjustment regulator cover screw and
tighten securely.
8. Cycle the valve several times to verify regulator
setting.
g. Turn offall electlical power to the system.
h. Remove the manometer and flexible tubing. Remove
the barbed fitting and replace the plug or tighten the
pressure test screw.
i. Turn on electrical power to the system and energize
valve.
j. Using a leak detection solution or soap suds, check for
leaks at plug or pressure boss screw.
NOTE:
The manifold pressure must be referenced to the burner
box. The burner box pressure tap equalizes the gas valve
pressure regulator. Manifold pressure is checked by
installing a tee (field supplied) in the tubing, between the
tee coming from the burner box tube and the gas valve,
in addition to the regular gas valve pressure tap on the
outlet side of the gas valve. See Figure 47.
32 18-CD19D8-14
Installer's Guide
Replace and/or tighten all plugs removed or loosened
when adjusting gas pressure. Leak check the fittings
before placing the furnace into regular service. Failure
to follow this warning could result in fire, explosion, or
property damage.
Table 12 lists the main burner orifices used with the furnace.
If a change of orifices is required to correct the furnace input
rating refer to Table 13.
REINSTALLATION OF THE BURNER BOX COVER
Figure 49 shows the correct way to reinstall the burner box
cover if adjustment or replacement of the flame sensor, hot
surface igniter, or main burner orifices have required re-
moval of the cover.
START-UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
Disconnect power to the unit before removing the blower
door. Allow a minimum of 10 seconds for IFC power supply
to drain to 0 volts. Failure to follow this warning could
result in property damage, personal injury or death.
With gas and electrical power "OFF"
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Turn the main gas valve toggle switch (See Fig_i_s 48 & 49)
within the unit to the "OFF" position. Turn the external gas
valve to "ON". Purge the air fi'om the gas lines. After purging,
check all gas connections for leaks with a soapy solution --
DO NOT CHECK WITHAN OPEN FLAME. Allow 5 min-
utos fbr any gas that might have escaped to dissipate.
LP Gas being heavier than air may require forced ventilation.
Turn the toggle switch on the gas valve in the unit to the
"ON" position.
LIGHTING INSTRUCTIONS
DO NOT attempt to manually light the burner. Failure to
follow this warning could result in property damage,
personal injury or death.
Lighting instructions appear on each unit. Each installation
must be checked out at the time of initial start up to insure
proper operation of all components. Check out should include
putting the unit through one complete cycle as outlined below.
Turn on the main electrical supply and set the thermostat
above the indicated temperature. The ignitor will automati-
cally heat, then the gas valve is energized to permit the flow
of gas to the burners. After ignition and flame is established,
the flame control module monitors the flame and supplies
power to the gas valve until the thermostat is satisfied.
To shut off
For complete shutdown: Turn the gas cock knob on the main
gas valve to the "OFF" position (See Figure 44). Disconnect
the electrical supply to the unit.
If this is done during the cold weather months, provisions
must be taken to prevent freeze-up of all water pipes and
water receptacles.
Whenever your house is to be vacant, arrange to have
someone inspect your house for proper temperature.
This is very important during freezing weather. If for
any reason your furnace should fail to operate dam-
age could result, such as frozen water pipes.
SEQUENCE OF OPERATION
Thermostat call for heat (2-stage thermostat)
Call for 1st stage only:
Wl thermostat contacts close signaling the control module to
run its self-check routine. After the control module has
verified that the 1st stage pressure switch contacts are open
and the limit switch(es) contacts are closed, the draft blower
will be energized.
As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will
begin. The ignitor will heat for approx. 20 seconds, then the
gas valve is energized in 1st stage to permit gas flow to the
burners.
The flame sensor confirms that ignition has been achieved
within the 4 second ignition trial period.
As the flame sensor confirms that ignition has been achieved,
the delay to fhn ON period begins timing and after approx.
45 seconds the indoor blower motor will be energized at low
speed and will continue to run during the heating cycle.
Call for 2nd stage after 1st stage:
W2 themmstat contacts close signaling a call for 2nd stage
heat. After a 30 second delay, the induced draft blower will
be energized on high speed and the 2nd stage pressure
switch contacts will close. The gas valve is energized in 2nd
stage and the indoor blower motor in high speed.
2nd stage satisfied, 1st stage still called:
W2 thermostat contacts open signaling that 2nd stage
heating requirements are satisfied.
The induced draft blower is reduced to low speed allowing
the 2nd stage pressure switch contacts to open and the gas
valve is reduced to 1st stage. The indoor blower motor is
reduced to low speed.
1st stage satisfied:
W1 thermostat contacts open signaling that 1st stage
heating requirements are satisfied. The gas valve will close
and the induced draft blower will be de-energized. The
indoor blower motor will continue to run for the fan offperiod
(Field selectable at 60, 100, 140 or 180 seconds), then will be
de-energized by the control module.
Thermostat call for heat (1-stage Thermostat)
W1/W2 (jumpered) thermostat contacts close signaling a call
for heat. 1st stage sequence of operation remains the same
as above. 2nd stage heat will energize after the stage delay
timer (field selectable at .5, 5, 10 or 15 minutes) has expired.
Thermostat satisfied:
W1/W2 (jumpered) contacts open signaling the control
module to close the gas valve. The induced draft blower is
switched to low speed and de-energized after the post purge
timer has expired. The indoor blower motor will continue to
operate after the flames are extinguished and then is
switched to low heat speed for the FAN-OFF period.
18-CD19D8-14 33
iiii!ii!iiiiiI
Installer's Guide
CONTROL AND SAFETY SWITCH ADJUSTMENTS
LIMIT SWITCH CHECK OUT
The limit switch is a safbty device designed to close the gas
valve should the furnace become overheated. Since proper
operation of this switch is important to the safety of the unit, it
must be checked out on initial start up by the installer.
To check for proper operation of the limit switches, set the
thermostat to a temperature higher than the indicated
temperature to bring on the gas valve. Restrict the airflow
by blocking the return air (disconnecting the indoor blower
may trip the inducer limit). When the furnace reaches the
maximum outlet temperature as shown on the rating plate,
the burners must shut off. If they do not shut off after a
reasonable time and overheating is evident, a faulty limit
switch is probable and the limit switch must be replaced.
After checking the operation of the limit control, be sure to
remove the paper or cardboard f_om the return air inlet. Refer
to Service Facts for additional instructions.
NOTE TO INSTALLER
Review the following" warnings with the owner. Review con-
tents of USER'S INFORMATION MANUAL with the owner.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they
are within the ranges specified on the furnace rating" name-
plate. If the airflow needs to be increased or decreased, see
the wiring" diagram for information on changing the speed of
the blower motor.
Disconnect power to the unit before removing the blower
door. Allow a minimum of 10 seconds for IFC power supply
to drain to 0 volts. Failure to follow this warning could
result in property damage, personal injury or death.
This unit is equipped with a blower door switch which cuts
power to the blower and gas valve causing" shutdown when
the door is removed. Operation with the door removed or ajar
can permit the escape of dangerous fumes. All panels must be
securely closed at all times for safe operation of the furnace.
INDOOR BLOWER TIMING
Heating: The integrated furnace control module controls the
indoor blower. The blower start is fixed at 45 seconds after
ignition. The FAN-OFF period is field selectable by dip
switches SW-2, #1 and #2 at 60, 100, 140, or 180 seconds.
The factory setting is 100 seconds.
WI-W2 stage delay (jumpered together) is field selectable by
dip switch SW-1, #1 and #2 at .5, 5, 10 or 15 minutes. The
fhctory setting is 10 minutes. (See wiring diagram).
Cooling: The fan delay off period is factory set at 0 seconds.
The option for 80 second delay offis field selectable by dip
switch SW-2, #3 (See wiring" diagi'am).
ROOM AIR THERMOSTAT
HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current
flow measured, or the settings fbund in the notes on the
furnace wixing diagram (found in the SERVICE FACTS or
inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, oi" mechanical failures
occur, the owner should immediately turn the gas
supply off at the manual gas valve, located in the
burner compartment. Also turn off electrical power to
the furnace and contact the service agency designated
by your dealer.
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a manual reset temperature
limit located on the burner box. In case of excessive tempera-
ture, the limit will open and cause the circuit to open which
shuts off all flow of gas.
ABNORMAL CONDITIONS
1. EXCESSIVE COMBUSTION PRESSURE (WIND IN
EXCESS OF 40 MP.H.) VENT OR FLUE BLOCKAGE
On a call fox'heat, the variable speed draft inducer must
first ramp up to speed and close the pressure switch
before the ignition sequence is allowed to begin. If the
pressure switch does not close, the motor will ramp up to
maximum speed and continue to operate there for about
1 minute.
2.
3.
After one minute the integrated furnace control will turn
the motor offfor about 30 seconds then back on in an
attempt to reestablish proper operation. This condition
is indicative of a highly restricted or blocked inlet or
outlet vent pipe or a Ihiled pressure switch.
If pressure against induced draft blower outlet becomes
excessive, the pressure switch will open. If the pressure
switch is open for more than 3.5 seconds, the variable
speed draft inducer will speed up and attempt to reclose
the pressure switch. If the pressure switch is not dosed
within 12 seconds or if the maximum speed of the motor
is reached, the draft inducer sends a Ihult signal to the
integ_'ated furnace control. If the unit is operating in
second stage, an inducer fault will cause the furnace
control to transition the system to first stage and it will
operate there for 10 minutes before attempting to run
again in second stage. If the unit is operating in first
stage, an inducer fault will cause the furnace control to
shut the system down and wait 30 seconds befbre
attempting to reestablish operation in first stage.
LOSS OF FLAME
If loss of flame occurs during a heating cycle, or flame is
not present at the sensor, the flame control module will
close the gas valve. The flame control module will then
recycle the ignition sequence, then if ignition is not
achieved, it will shut off the gas valve and lock out the
system.
POWER FAILURE
If there is a power failure during a heating cycle, the
system will restart the ignition sequence automatically
when power is restored, if the thermostat still calls for
heat.
4. GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle, the system
integrated control module will recycle the ignition sequence,
then if ignition is not achieved, the integrated control
module will shut offthe gas valve and lock out the system.
5. INDUCED DRAFT BLOWER FAILURE
Please refer to the variable speed draft inducer
troubleshooting manual for diagnostic assistance.
6. CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris,
improper draining, or by freezing condensate, the
pressure switch will sense the accumulation of conden-
sate in the furnace drain pan. The unit will not operate
properly until the condensate drain has been cleared, and
the condensate flows freely.
34 18-CD19D8-14
Installer's Guide
INTEGRATED FURNACE CONTROL RED LED "ERROR" FLASH CODES
2 Flashes --- System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems:
3 Flashes --- a) Venting problem
b) Pressure switch problem
c) Inducer problem
4 Flashes --- Open Temperature Limit Switch
5 Flashes --- Flame sensed when no flame should be present
115 volt AC power reversed, ignitor (Triac) fault, poor grounding or
6 Flashes --- system voltage too low
7 Flashes --- Gas valve circuit error
8 Flashes --- Low flame sense
9 Flashes --- Open Inducer Limit switch
10 Flashes --- Inducer communication error
Solid --- Internal GV error or Low TH voltage
Solid Red w/Solid Continuous Reset caused by a blown fuse or internal error.
Green "STATUS" LED
7. RESET AFTER LOCKOUT
When the integrated control module has shut the system
down and gone into lockout, the system must be manu-
ally reset before the unit will restart. The system can be
reset by turning the system power offfbr more than
1 second, or by removing 24VAC from the control for more
than 1 second, or by removing the thermostat call for
heat for more than I second but less than 20 seconds.
8. RESET AFTER BURNER BOX LIMIT SHUTDOWN
If the furnace shuts down, one thing that can be checked
is the burner box temperature limit switch. It is located
on the bottom of the burner box. The vent and combus-
tion air inlet terminations should be checked for block-
age. If blockage exists, clear the problem and then the
reset button may be depressed. If there is no block-
age of the terminations, the limit switch must be
reset by a qualified servicer.
FAULT CODE RECOVERY
On power' up, last 4 fhults, if any, will be flashed on the red
LED. The newest fault detected will flash first and the oldest
last. There will be a 2 second delay between fault code
flashes. Solid red LED error codes will not be displayed.
The Green LED will be on solid during" last fault recovery.
At any other time the control is powered, the Green LED
indicator light will operate as shown in Table 14 and the red
LED will flash LitePort data (one flash) every 20 seconds.
TABLE 14
INTEGRATED FURNACE CONTROL
GREEN "STATUS" LED FLASH CODES
Flashing Slow --- Normal - No call for Heat
Flashing Fast --- Normal - Call for Heat
Green Status LED
*UX /DX Integrated Furnace Control
Fault Code Reset
The last 4 fault codes can be erased fl'om memory by power-
ing up the control with "G" energized and then applying "R"
to the "WI" terminal 3 times within 6 seconds. The control
will acknowledge the reset by turning on the red LED for
2 seconds.
18-CD19D8-14 35
American Standard Inc.
6200 Troup Highway
Tyler, TX75707
10/06
Formore information contact Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to
yourlecal dealer (distributor) change design and specifications without notice.

Navigation menu