TRANE Air Conditioner/heat Pump(outside Unit) Manual L0801787

User Manual: TRANE TRANE Air conditioner/heat pump(outside unit) Manual TRANE Air conditioner/heat pump(outside unit) Owner's Manual, TRANE Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadTRANE  Air Conditioner/heat Pump(outside Unit) Manual L0801787
Open PDF In BrowserView PDF
18-AC41D 16-5
Library
Product Section

It's Hard

Product

To Stop A Trane?

Model

INSTALLER'S
GUIDE

Literature Type
Sequence
Date
File No.
Supersedes

Condensing Units

Model:
TTR018D,TTR025-036C,
& TTR042-60D
IMPORTANT -- This Document is customer

property

and is to remain with this unit. Please return to service infi)rmation pack upon completion of work.

These instructions
do not cover all variations
in systems
nor provide
for every possible
contingency
to be met in
connection
with installation.
All phases of this installation must comply with NATIONAL,
STATE AND LOCAL
CODES.
Should further
information
be desired or should
particular
problems arise which are not covered sufficiently
far
the purchaser's
purposes, the matter should be referred to your
installing
dealer or local distributor.

Q

TOP DISCHARGE --- UNRESTRICTED
5 FT. ABOVE UNIT

GENERAL
NOTICE:
These
units
equipped

outdoor
with

units
may be used
with
indoor
Capillary
Tube,
Thermostatic

Expansion
Valve
Valve
(F.C.C.V.)

or the
assembly

Accutron
TM
Flow
for refrigerant

Check lbr transportation
promptly, to the carrier,

Control
Check
flow control.

damage alter unit is uncrated.
any damage found to the unit.

Report

To determine
the electrical
power requirements
of the u nit, refer
to the nameplate
of the unit. The electrical
power available
must
agree

with

that

B. LOCATION

listed

on the

nameplate.

& PREPARATION

OF THE

1. The unit should be set on a level support
as the unit base pan.

UNIT

pad at least

as large

2. The support
pad must
NOT be in direct
contact
with
any
structure.
The unit must be positioned
a minimum
of 12" Ii'om
any wall or surrounding
shrubbery
to insure
adequ ate airflow.
A
30" clearance
must
be provided
in front of control
box (access
panels)
& any other
side
requiring
service
access
to meet
National
Electrical
Code.
The
from any structure
to prevent
pouring
directly
on the unit.

unit must be lar enough
excess
roof run-off
water

3. The top discharge area must be unrestricted
(5) feet above the unit.

away
from

for at least five

4. When the outdoor unit is mounted on a roof, be sure the roof
will support
the unit's weight.
Properly
selected
vibration
isolators are recommended
to prevent transmission
to the building structure.
5. The maximmn
indoor unit should

© American

length of refrigerant
lines from outdoor
NOT exceed eighty (80) feet.

Standard

Inc. 1998

to

6. If the outdoor unit is mounted
above the air handler, maximum lift should not exceed sixty (60) feet (suction line). If air
handler
is mounted
above the condensing
unit, maximum
lilt
should not exceed sixty (60) feet (liquid line).
NOTE: Refi_r to "Re[i'igerant

Piping

Guide'; Pub. No. 22-3238-01.

7. Locate and install indoor coil or blower coil in accordance
instruction
included with that unit.

with

Since the manufacturer
has a policy of continuous
product improvement,
it reserves the right to change
specifications
and design without notice.

INSTALLER'S GUIDE
C. ACCUTRON

FLOW

TM

CONTROL

VALVE

If the indoor unit System
Refrigerant
Flow control is an
Accutron TM orifice and check valve assembly,
an orifice size
change may be necessary.

@

BRAZE

TYPE

INDOOR

END
SEALING

CAP

ACCUTRON
COMPONENTS

TM

The outdoor model determines
the required orifice size. Check
the listed orifice size on nameplate
of the selected outdoor model.
If the indoor u nit is factory shipped with a different orifice size,
the orifice must be changed to obtain system rated performance.

'_

FLOW CONTROL

IMPORTANT:
The outdoor unit is shipped with the proper size
orifice and a stick-on orifice size label in an envelope attached to
the outdoor unit.
Outdoor unit nameplate
will have correct
orifice size specified as BAYFCCV --- A for rated performance.
D. INSTALLING
Condensing

units

REFRIGERANT
have provisions

lbr braze

unit

The units are Ihctory charged with the system charge required
when using twenty-five
(25) feet of connecting line. Unit nameplate charge is the same. If final refrigerant
charge adjustment
is necessary,
use the Charge Charts in the outdoor unit Service
Facts.

2. Consider

types

of bends

NOTE: Lasce diameter
it has been shaped.
3. Determine
tubing--INSIDE

the tubing

tubing

will be very difficult

to rebend once

point Ibr routing the refrigerant
THE STRUCTURE.

is of sufficient

length.

--- do not kink or dent.

7. Route the tubing making
all required
bends
secure the tubing before making connections.

and properly

8. To prevent
a noise within
the building
structure
due to
vibration transmission
from the refrigerant
lines, the following
precautions
should be taken:
a. When the refrigerant
lines have to be Ihstened
to floor
joists or other framing in a structure,
use isolation type hangers.
b. Isolation hangers
should also be used when
lines are run in stud spaces or enclosed ceilings.
c. Where the refrigerant lines run through
should be insulated
and isolated.
d.

Isolate

PAGE 2

VALVE

OPERATION

AND

GAS

LINE

SERVICE

VALVE

The Service Valves are lhctory shipped in the seated position to
hold ihctory charge.
The pressure
tap service port (when depressed) opens only to the field brazing side of the valve when the
valve is in the seated position. The liquid line valve is not a back
seating valve (see WARNING
below).

way to run the lines.

4. Provide a pull-thru hole of sufficient size to allow both liquid
and gas lines plus fittings to clear. The location of this hole (if
practical) should be just about the wall plate which is resting on
the Ibundation.

6. Uncoil

E. SERVICE

to be made and space limitations.

the best starting
OR OUTSIDE

5. Be sure the tubing

LIQUID LINE
FIELD SUPPLIED

BRASS
LIQUID
OPERATION

be insulated.

the most practical

ORIFICE

connections.

The indoor end of recommended
refrigerant
line sets may be
straight
or with a 90 degree bend, depending
upon situation
requirements.
This should be thoroughly
checked out before
ordering refrigerant
line sets.

1. Determine

VALVE

(F.C.C,V.)

LINES

Pressure taps are provided on the service valves of outdoor
for compressor
suction and liquid pressures.

The gas line must always

CHECK

the lines from all ductwork.

refrigerant

a wall or sill, they

Extreme caution
should be exercised
so the internal steel
stem retaining
ring is not damaged
by backing
out the
valve stem when opening
the valve.
If the valve stem is
forced out past the retaining
ring, system pressure
could
force the valve stem out of the valve body. If the retaining
ring is missing,
do not attempt
to open the valve.
See
Figure 3.
BRASS

GAS LINE

BALL

SERVICE

VALVE

The Brass Gas Line Ball Service Valve is shipped in the closed
position to hold the factory refrigerant
charge. The pressure tap
service port (when depressed) opens only to the field brazing side
when the valve is in the closed position.
The Gas Line Service Valve is full open with a 1/4 turn counterclockwise.
See Figure 4.
BRAZING

REFRIGERANT

LINES

1. Before brazing,
remove plugs
tubes. Clean internal
and external
to brazing.
2. Cut and fit tubing
3. Insulate
4. Do NOT
contact with

the entire

minimizing

li'om external
copper
surfaces of stub tubes
the use of sharp

stub
prior

90 ° bends.

gas line and its fittings.

allow uninsulated
bare gas line.

liquid

line

to come in direct

5. Precautions
should be taken to avoid heat damage to
the pressure
tap valve core during brazing.
It is recommended that the pressure
tap port valve core be removed
and a wet rag wrapped
around
the valve body.

Pub. No. 18-AC41D16-5

INSTALLER'S GUIDE

®

GAS

LIQUID LINE SERVICE VALVE

LINE SERVICE

VALVE
CAP

RETAINING

RING

HEXHEADED
VALVE SYSTEM

UNIT SIDE OF
SERVICE
VALVE

UNtTSIDE OF
SERVICE VALVE_

LIQUID

LIQUID LINE
CONNECTION

LINE

HEX HEADED
VALVE
CONNECTION

CAP'_"_

Notice: Use care to make sure that no moisture
tap port, while wet rag is being used.

enters

pressure

6. Remove braze shield from clear plastic bag. Soak pad in water
and place over suction and liquid lines to protect unit finish. See
figure 5. Discard pad when finished with brazing.
7. Use a Dry Nitrogen
Purge and Brazing Alloy without flux
when brazing the field line to the copper factory connection.
Flow
dry nitrogen into either valve pressure tap port, thru the tubing
and out the other port while brazing.
8. Braze

using accepted

good brazing

techniques.

LEAK CHECK

CAUTION:
tions, dome
compressor,

In scroll compressor
applicamay be hot. Do not touch top of
minor to severe burning.

temperatures
may cause

©

GAS LINE SERVICE
CAP _

J_

VALVE
114TURN ONLY
COUNTERCLOCKWISE

SIDE

#
PRESSURE

SYSTEM

TAP

PORT

/'
/
GAS

LINE

CONNECTION

core before

EVACUATION

NOTE: Since the outdoor unit has a re[?igerant
liquid line vcllves must remain closed.

charde, the gas and

1. Upon completion of leak check, evacuate the refrigerant
lines
and indoor coil before opening the gas and liquid line valves.
2. Attach appropriate
line pressure taps.

hoses from manifold gauge to gas and liquid

NOTE:
Unnecessm'y
switching
of hoses can be avoided and
complete evacuation
of all lines leading to sealed system can be
accomplished
with manifold center hose and connecting branch
hose to a cylinder of HCFC-22 and vacuum pump.

4. Evacuate
microns.

OF VALVE

tap port valve

After brazing operation of refrigerant
lines to both the outdoor and
indoor unit is completed, the field brazed connections must be
checked fbr leaks. Pressmize
through the service valve ports, the
indoor u nit and field refrigerant
lines with dry nitrogen to 200 psi.
Use soap bubbles or other leak-checking
methods to see that all
field joints are leak-free! If not, release
pressure;
then repair!

3. Attach

/

UNIT

IMPORTANT:
Replace pressure
attaching
hoses for evacuation.

center hose of manifold
until

the micron

gauges

to vacuum

gauge reads

pump.

no higher

_

&

350

5. Close offvalve
to vacuum
pump and observe the micron gauge.
If gauge pressure
rises above 500 microns
in one (1) minute,
then
evacuation
is incomplete
or system
has a leak.

6. If vacuum gauge does not rise above 500 microns
minute, the evacuation
should be complete.
CAP

than

in one (1)

7. With a vacuum pump and micron gauge blm_ked off; open valve
on HCFC-22 cylinder and charge refrigerant
lines and indoor coil
with vapor to tank pressure of HCFC-22 supply.
NOTE:
DO NOT
ATMOSPHERE.

VENT

REFRIGERANT

INTO

THE

CORE

Pub. No. 18-AC41D16-5

PAGE 3

INSTALLER'S GUIDE
(_

HEAT SHIELD

1. Power wiring
local codes.

and grounding

2. Power

supply

must

3. Install

a separate

4. Ground

of equipment

agree with equipment
disconnect

the outdoor

switch

must comply with
nameplate.

at the outdoor

unit.

unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration
mission may create a noise problem within the structure.

trans-

6. The use of color coded low voltage wire is recommended
to
simplil_¢ connections
between the outdoor unit, the thermostat,
and the indoor unit.
Table 1 --- NEC Class II Control

Wiring

24 VOLTS

8. Close valve on HCFC-22 supply cylinder.
Close valves on
manifold gauge set and remove refrigerant
charging hoses from
liquid and gas pressure
tap ports.
NOTE:
A 3/16" Allen wrench is required to open liquid line
service valve. A 1/4" Open End or Adjustable
wrench is required
to open gas line valve. An Adjustable
or 3 /4" Open End u._nch
is required to take aff the valve stem cap.
9. The liquid line shut-off valve can now be opened.
Remove
shut-off valve cap. Fully insert hex wrench into the stem and
backou t cou nterclockwise
until valve stem just tou ches retainer
ring (approximately
five (5) turns) observing WARNING
statement. See Figure 3.
10. Replace liquid service pressure tap port cap and valve stem
cap. These caps MUST BE REPLACED
to prevent
leaks.
Replace valve stem and pressure
tap cap finger tight, then
tighten an additional
1/6 turn.
11. The gas valve can now be opened. For a ball type gas valve,
open the valve by removing
the shut-off valve cap and turning
the valve stein 1/4 turn counterclockwise.
See Figure 4. For
brass gas line service valve opening, follow items 9 & 10 above.
See Figure 3.
12. The gas valve is now open for refrigerant
flow. Replace
stem cap to prevent leaks. See Figure 3 & 4.

valve

If may be necessary
to adjust system refi'igerant
charge
completion
of installation.
System
should be operated
checked for proper charge.

upon
and

F. ELECTRICAL

CONNECTIONS

WARN ING:

TO PREVENT

WIRE SIZE

MAX. WIRE LENGTH

*22 AWG

30 FT.

20 AWG

100 FT.

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

*If 22 AWG is used,

OR DEATH

quality

wire.

7. Table I defines maximum total length of low voltage
from outdoor unit, to indoor unit, and to thermostat.

wiring

8. Mount the indoor thermostat
in accordance
with instruction
included with the thermostat.
Wire per appropriate
hook-up
diagram (included in these instructions).
G. ELECTRICAL

HEATERS

Electric heaters,
if used, are to be installed in the air handling
device according to the instructions
accompanying
the air handler and the heaters.
H. OPERATIONAL

ANDCHECKOUTPROCEDURES

Final phases of this installation
are the unit Operational
and
Checkout Procedures
which are Ibund on page 8 of this instruction.
I.

START

KIT

Provisions
are made in these
accessory start kit, as required.

units

for field installed

MODELS

START KIT

TTR018D & TTR025-36C

BAYKSKT250A

TTR042-060D

BAYKSKT252A

The kits are installed
J. OUTDOOR

INJURY

make sure it is high

inside

the control

box of the unit.

THERMOSTAT

An outdoor thermostat
TAYSTAT250A
For data, see wiring diagram attached
sheet packaged with outdoor thermostat.

ETO_
t CT
%%S;O%O OONT TW,T 20

plug4n

may be field installed.
to unit and instruction

POS T ON BEFORE SERV C NG UN T.

PAGE 4

Pub. No. 18-AC41D16-5

INSTALLER'S GUIDE
TTR018D, TTR025-036C,
NOTE:

SERVICE

& TTR042-60D

ALL DIMENSIONS

ARE

OUTLINE

IN MM

DRAWING

INCHES).

PANEL

ELECTRICAL
AND
REFRIGERANT
COMPONENTS
CLEARANCES
PER
PREVAILING
CODES.

q

_TOP
I

=o

248

[95

[7/8)
LOW

.

ii

ii

ii

ii

[5]

DOES
NOT
POUR
DIRECTLY
ON UNIT,
AND SHOULD
BE AT
LEAST
305
(12"}
FROM
WALL
AND
ALL
SURROUNDING
SHRUBBERY
ON TWO SIDES.
OTHER
TWO SIDES
UNRESTRICTED.

22

28.6
(I I/'8}
D[A.
K.O.
22.2
[7/8)
D[A.
HOLE
ELECTRIC
POWER
22.2
HOLE

o.

DISCHARGE
AREA
SHOULD
BE
UNRESTRICTED
FOR
AT LEAST
FiVE
FEET
ABOVE
UNIT.
UNIT
SHOULD
BE
PLACEO
SO ROOF
RUN
OFF
WATER

WITH

II

DiA.

210

(8_

l21

[4

3/41

GAS LINE
SERVICE
VALVE,
"D'0.D.
FEMALE
BRAZED
CONNECTION
WITH
I/4"
SAE
PRESSURE
TAP
FITTING.

SI

LIQUID
LINE
SERVICE
VALVE,
"E"0.D.
FEMALE
BRAZED
CONNECTION
WITH
I/'4"
SAE
PRESSURE
TAP
FITTING.

FIG,

FLARE

FLARE

i

MODELS

FIG.

A

B

C

D

E

TTR018D-A

1

24-3/8

23-5/8

20

5/8

!/4

TTR025C-A

1

24-3/8

23-5t8

20

3/4

5/!6

TTR030C-A

1

24-3/8

28-1/4

24-5/8

3/4

5/!6

TTR036C-A

1

24-3/8

28-1/4

24-5/8

7/8

3/8

TTR042D-A

1

32-3/4

28-1/4

24-5/8

7/8

3/8

TTR048D-A

2

28-5/8

32-7/8

28-3/4

1-118

3/8

TTR060D-A

2

40-5/8

32-7/8

28-3/4

1-1t8

3/8

229

(9]

127

41

(5)

(1_)_

FIG.

2

NOTE: TABLE IN INCHES ONLY
From Dwg. 21D147561,

Pub. No. 18-AC41D16-5

Rev

10

PAGE 5

INSTALLER'S GUIDE
A TYPICAL

FIELD WIRING

DIAGRAM

FOR TTRO18-060

WITH AIR HANDLER
TO POWER SUPPLY PER
LOCAL CODED & AS DEFINED
IN FIELD WIRING TABLE

NOTES:
1

POWER WIRING AND GROUNDING
COMPLY WITH LOCAL CODES.

2

BE SURE POWER
NAMEPLATE.

3

LOW VOLTAGE
CONDUCTOR.

SUPPLY

WIRING

OF EQUIPMENT

ROOM

THERMOSTAT

AY28X092

AGREES

TO BE NO

CONDUCTORS

MUST

18 AWG

OR AY28XI05
SET 'NA" PER CURRENT
THRU Wl, W2, SHOWN
ON WIRING DIAGRAM

o?

WITH EQUIPMENT

_F_q[

MINIMUM

(

F[EL
ADDED
JUMPER

4

USE COPPER

5

POLARIZED
PLUG SECTION
HEATER CONTROL BOX

ONLY.

6

IF ODT IS NOT USED, THEN CONNECT
JUMPER FROM WI TO W2 ON LVTB

PM-A IS ATTACHED

TO

APPROPRIATE

O. O. SECTION
)SINGLE SPEED)

R

SEE NOTE 5

I

I

AIR HANDLER

NOTE 6

INTER COMPONENT WIRING
24 V. "_ FACTORY
LINE V_ WIRING

.......

24 V. "_ FIELD
LINE V_ WIRING

_L
%-

From Dwg. 21B131075,

A TYPICAL
FURNACE

FIELD WIRING

FOR SINGLE

DIAGRAM

STAGE

FOR TTR018-060

HEATING,

SINGLE

Rev2

WITH

STAGE COOLING

NOTES:
1

BE SURE POWER

2

LOW VOLTAGE

SUPPLY

AGREES

3

GROUNDING

4
5

SETTHERMOSTATHEATANTICIPATORPERUNITWIRINGDIAGRAM
THE "Y" TERMINAL
FROM THE THERMOSTAT
MUST BE WIRED TO
THE "Y" TERMINAL OF THE FURNACE CONTROL FOR PROPER
BLOWER OPERATION
DURING COOLING

(24V.) WIRING
OF EQUIPMENT

WITH

TO BE NO

EQUIPMENT
18 A.W.G.

MUST COMPLY

WFH

NAMEPLATE(S).

POWER
SUPPLY

MIN.

_

LOCAL

CODES

N OTE

_

__y
B

l!
_I
ir
iI I
• I I •

I

.....

SWITCH

OUTDOOR
WiTHDUT

HUMIOISTAT

SECTION
TRANSFDRMER

II
I

AY28XII9

4111

TO IIS VOLT
POWER SUPPLY

II

I

I

THERMOSTAT
_
r_
T
_
\

LI4' L /
""
I1_
I I_

LOW VOLTAGE
AIR CONDITIONING
SAiL

5

NOTECOOLING
4
HEATING

I
I

I
I

I
I

i
I

I

I

I_

TERMIN_L'S.

HUMIDIFIER

IDPTIDNALI
_{_

--

h_

LN

j

FURNACE

IMTERGRATEO

I

FURNACE
JUNCTION

FURNACE

BOX
TO

ELECTRONIC
CLEANER

LOCAL

L

AIR

I PH.,
SUPPLY

60

HZ.,
PER

CODES

_OPTIONAL)

INTER
]

RED

115V.,
POWER

OR

ALTERNATE

HOOKUP

3LOR
2R 2OO ELECTRONIC
RELAY KIT I
BAY24X043_

FOR

MODEL

COMPONENT

WIRING

BEFI40

AIR CLEANER

LH

---}TG.
,, VOLT
LM

POWER SUPPLY

ELECTRONIC
AIR
CLEANER ',OPTiON ALI

From Dwg. 21B340432,

PAGE 6

Rev 0

Pub. No. 18-AC41D16-5

INSTALLER'S GUIDE
CHECKOUT
After installation
following list:
1. Refrigerant

has been completed,

it is recommended

that the entire system

be checked

against the
[

]

[

]

[

]

[

]

[

]

[

]

[

]

8. Thermostat thermometer
is accurate. Check against a reliable thermometer.
Adjust
per instructions with thermostat
..........................................................................................................

[

]

9. Is correct speed tap being used? (Indoor

[

]

2. Suction

Line, Leak checked

PROCEDURE

Lines and Fittings properly

3. Have all Refrigerant
4.

..........................................................................................................
insulated ......................................................................................

Lines been secured

and isolated

properly?

........................................................

Have passages through masonry been sealed? If mortar is used, prevent mortar from
coming into direct contact with copper tubing .....................................................................................

5. Indoor coil drain line drains freely.
6. Supply

registers

Pour water into drain pan .............................................................

and return grilles open and unobstructed

7. Return air filter installed

.................................................................

......................................................................................................................

SYSTEM

blower

motor) .....................................................................

OPERATIONAL

CHECK

OPERATING PRESSURES: After the unit has operated in the cooling mode for a short period of time, install
pressure gauges on the gauge ports of the discharge and suction line valves. Check the suction and discharge
pressures and compare them to the normal operating pressures provided in the unit's Service Facts.

NOTE:

Use the pressures from Service Facts to determine the unit refrigerant charge.
To charge the system accurately, use superheat charging, or pressures
depending on flow control.

1. Except as required for safety while servicing:

SUPPLEMENTARY

HEATERS CHECKOUT

DOES HEATER
1. Be sure the fused disconnect

OPERATION
SYSTEM.

Pub. No. 18-AC41D16-5

and grounding
specifications

SWITCH.

IF USED

CIRCUIT?

switch is "OFF," and safety label (if any) is attached

3. Check fuses for proper size per nameplate
4. Check control box panel--

DISCONNECT

PROCEDURES,

REQUIRE A SEPARATE

2. Check on field wiring for sound connections

NOTE:

DO NOT OPEN SYSTEM

according

................................

[

]

to codes .....................................

[

]

[

]

[

]

.....................................................................

in place and secured ..................................................................................

OF HEATERS

MUST BE CHECKED

DURING THE OPERATION

CHECKOF

THE TOTAL

PAGE 7

INSTALLER'S GUIDE
CHECKOUT

PROCEDURE

WITH MAIN POWER DISCONNECTS

INDOOR THERMOSTAT
SWITCH SETTING

1

TO CHECK
Indoor Fan Operation

OFF

(1)
COOL

(1)
HEAT

AUTO

X

ON

INDOOR
BLOWER
RUNS

X

X

OUTDOOR
BLOWER
RUNS

OPERATION

COMPRESSOR
RUNS

Cooling Operation

X

X

X

X

Checking Performance
& Charge (2)

X

X

X

X

Heating (3)
5

COMPONENT

FAN SWITCH

STEP
NO.

CLOSED (ON)

FURNACE
HEAT
COMES
ON

X

Inform owner on how to operate system and what to expect of it. At the same time deliver Owner's Use and Care Booklet.

(1) Also set thermostat dial to call for cooling or heating as necessary,
(2) Use Service Facts attached to outdoor unit,
(3) Check only necessary if heating unit is used for indoor section and wiring has been disturbed

during installation

of cooling equipment,

Technical Literature - Printed in U.S.A.

The Trane Company
Unitary

Products

Group

6200 Troup Highway
Tyler, TX 75707

PAGE 8

Pub. No. 18-AC41D16-5



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 8
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Tue Mar 25 06:25:10 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu