TRANE Air Conditioner/heat Pump(outside Unit) Manual L0801787
User Manual: TRANE TRANE Air conditioner/heat pump(outside unit) Manual TRANE Air conditioner/heat pump(outside unit) Owner's Manual, TRANE Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF
.
Page Count: 8
| Download | |
| Open PDF In Browser | View PDF |
18-AC41D 16-5
Library
Product Section
It's Hard
Product
To Stop A Trane?
Model
INSTALLER'S
GUIDE
Literature Type
Sequence
Date
File No.
Supersedes
Condensing Units
Model:
TTR018D,TTR025-036C,
& TTR042-60D
IMPORTANT -- This Document is customer
property
and is to remain with this unit. Please return to service infi)rmation pack upon completion of work.
These instructions
do not cover all variations
in systems
nor provide
for every possible
contingency
to be met in
connection
with installation.
All phases of this installation must comply with NATIONAL,
STATE AND LOCAL
CODES.
Should further
information
be desired or should
particular
problems arise which are not covered sufficiently
far
the purchaser's
purposes, the matter should be referred to your
installing
dealer or local distributor.
Q
TOP DISCHARGE --- UNRESTRICTED
5 FT. ABOVE UNIT
GENERAL
NOTICE:
These
units
equipped
outdoor
with
units
may be used
with
indoor
Capillary
Tube,
Thermostatic
Expansion
Valve
Valve
(F.C.C.V.)
or the
assembly
Accutron
TM
Flow
for refrigerant
Check lbr transportation
promptly, to the carrier,
Control
Check
flow control.
damage alter unit is uncrated.
any damage found to the unit.
Report
To determine
the electrical
power requirements
of the u nit, refer
to the nameplate
of the unit. The electrical
power available
must
agree
with
that
B. LOCATION
listed
on the
nameplate.
& PREPARATION
OF THE
1. The unit should be set on a level support
as the unit base pan.
UNIT
pad at least
as large
2. The support
pad must
NOT be in direct
contact
with
any
structure.
The unit must be positioned
a minimum
of 12" Ii'om
any wall or surrounding
shrubbery
to insure
adequ ate airflow.
A
30" clearance
must
be provided
in front of control
box (access
panels)
& any other
side
requiring
service
access
to meet
National
Electrical
Code.
The
from any structure
to prevent
pouring
directly
on the unit.
unit must be lar enough
excess
roof run-off
water
3. The top discharge area must be unrestricted
(5) feet above the unit.
away
from
for at least five
4. When the outdoor unit is mounted on a roof, be sure the roof
will support
the unit's weight.
Properly
selected
vibration
isolators are recommended
to prevent transmission
to the building structure.
5. The maximmn
indoor unit should
© American
length of refrigerant
lines from outdoor
NOT exceed eighty (80) feet.
Standard
Inc. 1998
to
6. If the outdoor unit is mounted
above the air handler, maximum lift should not exceed sixty (60) feet (suction line). If air
handler
is mounted
above the condensing
unit, maximum
lilt
should not exceed sixty (60) feet (liquid line).
NOTE: Refi_r to "Re[i'igerant
Piping
Guide'; Pub. No. 22-3238-01.
7. Locate and install indoor coil or blower coil in accordance
instruction
included with that unit.
with
Since the manufacturer
has a policy of continuous
product improvement,
it reserves the right to change
specifications
and design without notice.
INSTALLER'S GUIDE
C. ACCUTRON
FLOW
TM
CONTROL
VALVE
If the indoor unit System
Refrigerant
Flow control is an
Accutron TM orifice and check valve assembly,
an orifice size
change may be necessary.
@
BRAZE
TYPE
INDOOR
END
SEALING
CAP
ACCUTRON
COMPONENTS
TM
The outdoor model determines
the required orifice size. Check
the listed orifice size on nameplate
of the selected outdoor model.
If the indoor u nit is factory shipped with a different orifice size,
the orifice must be changed to obtain system rated performance.
'_
FLOW CONTROL
IMPORTANT:
The outdoor unit is shipped with the proper size
orifice and a stick-on orifice size label in an envelope attached to
the outdoor unit.
Outdoor unit nameplate
will have correct
orifice size specified as BAYFCCV --- A for rated performance.
D. INSTALLING
Condensing
units
REFRIGERANT
have provisions
lbr braze
unit
The units are Ihctory charged with the system charge required
when using twenty-five
(25) feet of connecting line. Unit nameplate charge is the same. If final refrigerant
charge adjustment
is necessary,
use the Charge Charts in the outdoor unit Service
Facts.
2. Consider
types
of bends
NOTE: Lasce diameter
it has been shaped.
3. Determine
tubing--INSIDE
the tubing
tubing
will be very difficult
to rebend once
point Ibr routing the refrigerant
THE STRUCTURE.
is of sufficient
length.
--- do not kink or dent.
7. Route the tubing making
all required
bends
secure the tubing before making connections.
and properly
8. To prevent
a noise within
the building
structure
due to
vibration transmission
from the refrigerant
lines, the following
precautions
should be taken:
a. When the refrigerant
lines have to be Ihstened
to floor
joists or other framing in a structure,
use isolation type hangers.
b. Isolation hangers
should also be used when
lines are run in stud spaces or enclosed ceilings.
c. Where the refrigerant lines run through
should be insulated
and isolated.
d.
Isolate
PAGE 2
VALVE
OPERATION
AND
GAS
LINE
SERVICE
VALVE
The Service Valves are lhctory shipped in the seated position to
hold ihctory charge.
The pressure
tap service port (when depressed) opens only to the field brazing side of the valve when the
valve is in the seated position. The liquid line valve is not a back
seating valve (see WARNING
below).
way to run the lines.
4. Provide a pull-thru hole of sufficient size to allow both liquid
and gas lines plus fittings to clear. The location of this hole (if
practical) should be just about the wall plate which is resting on
the Ibundation.
6. Uncoil
E. SERVICE
to be made and space limitations.
the best starting
OR OUTSIDE
5. Be sure the tubing
LIQUID LINE
FIELD SUPPLIED
BRASS
LIQUID
OPERATION
be insulated.
the most practical
ORIFICE
connections.
The indoor end of recommended
refrigerant
line sets may be
straight
or with a 90 degree bend, depending
upon situation
requirements.
This should be thoroughly
checked out before
ordering refrigerant
line sets.
1. Determine
VALVE
(F.C.C,V.)
LINES
Pressure taps are provided on the service valves of outdoor
for compressor
suction and liquid pressures.
The gas line must always
CHECK
the lines from all ductwork.
refrigerant
a wall or sill, they
Extreme caution
should be exercised
so the internal steel
stem retaining
ring is not damaged
by backing
out the
valve stem when opening
the valve.
If the valve stem is
forced out past the retaining
ring, system pressure
could
force the valve stem out of the valve body. If the retaining
ring is missing,
do not attempt
to open the valve.
See
Figure 3.
BRASS
GAS LINE
BALL
SERVICE
VALVE
The Brass Gas Line Ball Service Valve is shipped in the closed
position to hold the factory refrigerant
charge. The pressure tap
service port (when depressed) opens only to the field brazing side
when the valve is in the closed position.
The Gas Line Service Valve is full open with a 1/4 turn counterclockwise.
See Figure 4.
BRAZING
REFRIGERANT
LINES
1. Before brazing,
remove plugs
tubes. Clean internal
and external
to brazing.
2. Cut and fit tubing
3. Insulate
4. Do NOT
contact with
the entire
minimizing
li'om external
copper
surfaces of stub tubes
the use of sharp
stub
prior
90 ° bends.
gas line and its fittings.
allow uninsulated
bare gas line.
liquid
line
to come in direct
5. Precautions
should be taken to avoid heat damage to
the pressure
tap valve core during brazing.
It is recommended that the pressure
tap port valve core be removed
and a wet rag wrapped
around
the valve body.
Pub. No. 18-AC41D16-5
INSTALLER'S GUIDE
®
GAS
LIQUID LINE SERVICE VALVE
LINE SERVICE
VALVE
CAP
RETAINING
RING
HEXHEADED
VALVE SYSTEM
UNIT SIDE OF
SERVICE
VALVE
UNtTSIDE OF
SERVICE VALVE_
LIQUID
LIQUID LINE
CONNECTION
LINE
HEX HEADED
VALVE
CONNECTION
CAP'_"_
Notice: Use care to make sure that no moisture
tap port, while wet rag is being used.
enters
pressure
6. Remove braze shield from clear plastic bag. Soak pad in water
and place over suction and liquid lines to protect unit finish. See
figure 5. Discard pad when finished with brazing.
7. Use a Dry Nitrogen
Purge and Brazing Alloy without flux
when brazing the field line to the copper factory connection.
Flow
dry nitrogen into either valve pressure tap port, thru the tubing
and out the other port while brazing.
8. Braze
using accepted
good brazing
techniques.
LEAK CHECK
CAUTION:
tions, dome
compressor,
In scroll compressor
applicamay be hot. Do not touch top of
minor to severe burning.
temperatures
may cause
©
GAS LINE SERVICE
CAP _
J_
VALVE
114TURN ONLY
COUNTERCLOCKWISE
SIDE
#
PRESSURE
SYSTEM
TAP
PORT
/'
/
GAS
LINE
CONNECTION
core before
EVACUATION
NOTE: Since the outdoor unit has a re[?igerant
liquid line vcllves must remain closed.
charde, the gas and
1. Upon completion of leak check, evacuate the refrigerant
lines
and indoor coil before opening the gas and liquid line valves.
2. Attach appropriate
line pressure taps.
hoses from manifold gauge to gas and liquid
NOTE:
Unnecessm'y
switching
of hoses can be avoided and
complete evacuation
of all lines leading to sealed system can be
accomplished
with manifold center hose and connecting branch
hose to a cylinder of HCFC-22 and vacuum pump.
4. Evacuate
microns.
OF VALVE
tap port valve
After brazing operation of refrigerant
lines to both the outdoor and
indoor unit is completed, the field brazed connections must be
checked fbr leaks. Pressmize
through the service valve ports, the
indoor u nit and field refrigerant
lines with dry nitrogen to 200 psi.
Use soap bubbles or other leak-checking
methods to see that all
field joints are leak-free! If not, release
pressure;
then repair!
3. Attach
/
UNIT
IMPORTANT:
Replace pressure
attaching
hoses for evacuation.
center hose of manifold
until
the micron
gauges
to vacuum
gauge reads
pump.
no higher
_
&
350
5. Close offvalve
to vacuum
pump and observe the micron gauge.
If gauge pressure
rises above 500 microns
in one (1) minute,
then
evacuation
is incomplete
or system
has a leak.
6. If vacuum gauge does not rise above 500 microns
minute, the evacuation
should be complete.
CAP
than
in one (1)
7. With a vacuum pump and micron gauge blm_ked off; open valve
on HCFC-22 cylinder and charge refrigerant
lines and indoor coil
with vapor to tank pressure of HCFC-22 supply.
NOTE:
DO NOT
ATMOSPHERE.
VENT
REFRIGERANT
INTO
THE
CORE
Pub. No. 18-AC41D16-5
PAGE 3
INSTALLER'S GUIDE
(_
HEAT SHIELD
1. Power wiring
local codes.
and grounding
2. Power
supply
must
3. Install
a separate
4. Ground
of equipment
agree with equipment
disconnect
the outdoor
switch
must comply with
nameplate.
at the outdoor
unit.
unit per local code requirements.
5. Provide flexible electrical conduit whenever vibration
mission may create a noise problem within the structure.
trans-
6. The use of color coded low voltage wire is recommended
to
simplil_¢ connections
between the outdoor unit, the thermostat,
and the indoor unit.
Table 1 --- NEC Class II Control
Wiring
24 VOLTS
8. Close valve on HCFC-22 supply cylinder.
Close valves on
manifold gauge set and remove refrigerant
charging hoses from
liquid and gas pressure
tap ports.
NOTE:
A 3/16" Allen wrench is required to open liquid line
service valve. A 1/4" Open End or Adjustable
wrench is required
to open gas line valve. An Adjustable
or 3 /4" Open End u._nch
is required to take aff the valve stem cap.
9. The liquid line shut-off valve can now be opened.
Remove
shut-off valve cap. Fully insert hex wrench into the stem and
backou t cou nterclockwise
until valve stem just tou ches retainer
ring (approximately
five (5) turns) observing WARNING
statement. See Figure 3.
10. Replace liquid service pressure tap port cap and valve stem
cap. These caps MUST BE REPLACED
to prevent
leaks.
Replace valve stem and pressure
tap cap finger tight, then
tighten an additional
1/6 turn.
11. The gas valve can now be opened. For a ball type gas valve,
open the valve by removing
the shut-off valve cap and turning
the valve stein 1/4 turn counterclockwise.
See Figure 4. For
brass gas line service valve opening, follow items 9 & 10 above.
See Figure 3.
12. The gas valve is now open for refrigerant
flow. Replace
stem cap to prevent leaks. See Figure 3 & 4.
valve
If may be necessary
to adjust system refi'igerant
charge
completion
of installation.
System
should be operated
checked for proper charge.
upon
and
F. ELECTRICAL
CONNECTIONS
WARN ING:
TO PREVENT
WIRE SIZE
MAX. WIRE LENGTH
*22 AWG
30 FT.
20 AWG
100 FT.
18 AWG
150 FT
16 AWG
225 FT.
14 AWG
300 FT.
*If 22 AWG is used,
OR DEATH
quality
wire.
7. Table I defines maximum total length of low voltage
from outdoor unit, to indoor unit, and to thermostat.
wiring
8. Mount the indoor thermostat
in accordance
with instruction
included with the thermostat.
Wire per appropriate
hook-up
diagram (included in these instructions).
G. ELECTRICAL
HEATERS
Electric heaters,
if used, are to be installed in the air handling
device according to the instructions
accompanying
the air handler and the heaters.
H. OPERATIONAL
ANDCHECKOUTPROCEDURES
Final phases of this installation
are the unit Operational
and
Checkout Procedures
which are Ibund on page 8 of this instruction.
I.
START
KIT
Provisions
are made in these
accessory start kit, as required.
units
for field installed
MODELS
START KIT
TTR018D & TTR025-36C
BAYKSKT250A
TTR042-060D
BAYKSKT252A
The kits are installed
J. OUTDOOR
INJURY
make sure it is high
inside
the control
box of the unit.
THERMOSTAT
An outdoor thermostat
TAYSTAT250A
For data, see wiring diagram attached
sheet packaged with outdoor thermostat.
ETO_
t CT
%%S;O%O OONT TW,T 20
plug4n
may be field installed.
to unit and instruction
POS T ON BEFORE SERV C NG UN T.
PAGE 4
Pub. No. 18-AC41D16-5
INSTALLER'S GUIDE
TTR018D, TTR025-036C,
NOTE:
SERVICE
& TTR042-60D
ALL DIMENSIONS
ARE
OUTLINE
IN MM
DRAWING
INCHES).
PANEL
ELECTRICAL
AND
REFRIGERANT
COMPONENTS
CLEARANCES
PER
PREVAILING
CODES.
q
_TOP
I
=o
248
[95
[7/8)
LOW
.
ii
ii
ii
ii
[5]
DOES
NOT
POUR
DIRECTLY
ON UNIT,
AND SHOULD
BE AT
LEAST
305
(12"}
FROM
WALL
AND
ALL
SURROUNDING
SHRUBBERY
ON TWO SIDES.
OTHER
TWO SIDES
UNRESTRICTED.
22
28.6
(I I/'8}
D[A.
K.O.
22.2
[7/8)
D[A.
HOLE
ELECTRIC
POWER
22.2
HOLE
o.
DISCHARGE
AREA
SHOULD
BE
UNRESTRICTED
FOR
AT LEAST
FiVE
FEET
ABOVE
UNIT.
UNIT
SHOULD
BE
PLACEO
SO ROOF
RUN
OFF
WATER
WITH
II
DiA.
210
(8_
l21
[4
3/41
GAS LINE
SERVICE
VALVE,
"D'0.D.
FEMALE
BRAZED
CONNECTION
WITH
I/4"
SAE
PRESSURE
TAP
FITTING.
SI
LIQUID
LINE
SERVICE
VALVE,
"E"0.D.
FEMALE
BRAZED
CONNECTION
WITH
I/'4"
SAE
PRESSURE
TAP
FITTING.
FIG,
FLARE
FLARE
i
MODELS
FIG.
A
B
C
D
E
TTR018D-A
1
24-3/8
23-5/8
20
5/8
!/4
TTR025C-A
1
24-3/8
23-5t8
20
3/4
5/!6
TTR030C-A
1
24-3/8
28-1/4
24-5/8
3/4
5/!6
TTR036C-A
1
24-3/8
28-1/4
24-5/8
7/8
3/8
TTR042D-A
1
32-3/4
28-1/4
24-5/8
7/8
3/8
TTR048D-A
2
28-5/8
32-7/8
28-3/4
1-118
3/8
TTR060D-A
2
40-5/8
32-7/8
28-3/4
1-1t8
3/8
229
(9]
127
41
(5)
(1_)_
FIG.
2
NOTE: TABLE IN INCHES ONLY
From Dwg. 21D147561,
Pub. No. 18-AC41D16-5
Rev
10
PAGE 5
INSTALLER'S GUIDE
A TYPICAL
FIELD WIRING
DIAGRAM
FOR TTRO18-060
WITH AIR HANDLER
TO POWER SUPPLY PER
LOCAL CODED & AS DEFINED
IN FIELD WIRING TABLE
NOTES:
1
POWER WIRING AND GROUNDING
COMPLY WITH LOCAL CODES.
2
BE SURE POWER
NAMEPLATE.
3
LOW VOLTAGE
CONDUCTOR.
SUPPLY
WIRING
OF EQUIPMENT
ROOM
THERMOSTAT
AY28X092
AGREES
TO BE NO
CONDUCTORS
MUST
18 AWG
OR AY28XI05
SET 'NA" PER CURRENT
THRU Wl, W2, SHOWN
ON WIRING DIAGRAM
o?
WITH EQUIPMENT
_F_q[
MINIMUM
(
F[EL
ADDED
JUMPER
4
USE COPPER
5
POLARIZED
PLUG SECTION
HEATER CONTROL BOX
ONLY.
6
IF ODT IS NOT USED, THEN CONNECT
JUMPER FROM WI TO W2 ON LVTB
PM-A IS ATTACHED
TO
APPROPRIATE
O. O. SECTION
)SINGLE SPEED)
R
SEE NOTE 5
I
I
AIR HANDLER
NOTE 6
INTER COMPONENT WIRING
24 V. "_ FACTORY
LINE V_ WIRING
.......
24 V. "_ FIELD
LINE V_ WIRING
_L
%-
From Dwg. 21B131075,
A TYPICAL
FURNACE
FIELD WIRING
FOR SINGLE
DIAGRAM
STAGE
FOR TTR018-060
HEATING,
SINGLE
Rev2
WITH
STAGE COOLING
NOTES:
1
BE SURE POWER
2
LOW VOLTAGE
SUPPLY
AGREES
3
GROUNDING
4
5
SETTHERMOSTATHEATANTICIPATORPERUNITWIRINGDIAGRAM
THE "Y" TERMINAL
FROM THE THERMOSTAT
MUST BE WIRED TO
THE "Y" TERMINAL OF THE FURNACE CONTROL FOR PROPER
BLOWER OPERATION
DURING COOLING
(24V.) WIRING
OF EQUIPMENT
WITH
TO BE NO
EQUIPMENT
18 A.W.G.
MUST COMPLY
WFH
NAMEPLATE(S).
POWER
SUPPLY
MIN.
_
LOCAL
CODES
N OTE
_
__y
B
l!
_I
ir
iI I
• I I •
I
.....
SWITCH
OUTDOOR
WiTHDUT
HUMIOISTAT
SECTION
TRANSFDRMER
II
I
AY28XII9
4111
TO IIS VOLT
POWER SUPPLY
II
I
I
THERMOSTAT
_
r_
T
_
\
LI4' L /
""
I1_
I I_
LOW VOLTAGE
AIR CONDITIONING
SAiL
5
NOTECOOLING
4
HEATING
I
I
I
I
I
I
i
I
I
I
I_
TERMIN_L'S.
HUMIDIFIER
IDPTIDNALI
_{_
--
h_
LN
j
FURNACE
IMTERGRATEO
I
FURNACE
JUNCTION
FURNACE
BOX
TO
ELECTRONIC
CLEANER
LOCAL
L
AIR
I PH.,
SUPPLY
60
HZ.,
PER
CODES
_OPTIONAL)
INTER
]
RED
115V.,
POWER
OR
ALTERNATE
HOOKUP
3LOR
2R 2OO ELECTRONIC
RELAY KIT I
BAY24X043_
FOR
MODEL
COMPONENT
WIRING
BEFI40
AIR CLEANER
LH
---}TG.
,, VOLT
LM
POWER SUPPLY
ELECTRONIC
AIR
CLEANER ',OPTiON ALI
From Dwg. 21B340432,
PAGE 6
Rev 0
Pub. No. 18-AC41D16-5
INSTALLER'S GUIDE
CHECKOUT
After installation
following list:
1. Refrigerant
has been completed,
it is recommended
that the entire system
be checked
against the
[
]
[
]
[
]
[
]
[
]
[
]
[
]
8. Thermostat thermometer
is accurate. Check against a reliable thermometer.
Adjust
per instructions with thermostat
..........................................................................................................
[
]
9. Is correct speed tap being used? (Indoor
[
]
2. Suction
Line, Leak checked
PROCEDURE
Lines and Fittings properly
3. Have all Refrigerant
4.
..........................................................................................................
insulated ......................................................................................
Lines been secured
and isolated
properly?
........................................................
Have passages through masonry been sealed? If mortar is used, prevent mortar from
coming into direct contact with copper tubing .....................................................................................
5. Indoor coil drain line drains freely.
6. Supply
registers
Pour water into drain pan .............................................................
and return grilles open and unobstructed
7. Return air filter installed
.................................................................
......................................................................................................................
SYSTEM
blower
motor) .....................................................................
OPERATIONAL
CHECK
OPERATING PRESSURES: After the unit has operated in the cooling mode for a short period of time, install
pressure gauges on the gauge ports of the discharge and suction line valves. Check the suction and discharge
pressures and compare them to the normal operating pressures provided in the unit's Service Facts.
NOTE:
Use the pressures from Service Facts to determine the unit refrigerant charge.
To charge the system accurately, use superheat charging, or pressures
depending on flow control.
1. Except as required for safety while servicing:
SUPPLEMENTARY
HEATERS CHECKOUT
DOES HEATER
1. Be sure the fused disconnect
OPERATION
SYSTEM.
Pub. No. 18-AC41D16-5
and grounding
specifications
SWITCH.
IF USED
CIRCUIT?
switch is "OFF," and safety label (if any) is attached
3. Check fuses for proper size per nameplate
4. Check control box panel--
DISCONNECT
PROCEDURES,
REQUIRE A SEPARATE
2. Check on field wiring for sound connections
NOTE:
DO NOT OPEN SYSTEM
according
................................
[
]
to codes .....................................
[
]
[
]
[
]
.....................................................................
in place and secured ..................................................................................
OF HEATERS
MUST BE CHECKED
DURING THE OPERATION
CHECKOF
THE TOTAL
PAGE 7
INSTALLER'S GUIDE
CHECKOUT
PROCEDURE
WITH MAIN POWER DISCONNECTS
INDOOR THERMOSTAT
SWITCH SETTING
1
TO CHECK
Indoor Fan Operation
OFF
(1)
COOL
(1)
HEAT
AUTO
X
ON
INDOOR
BLOWER
RUNS
X
X
OUTDOOR
BLOWER
RUNS
OPERATION
COMPRESSOR
RUNS
Cooling Operation
X
X
X
X
Checking Performance
& Charge (2)
X
X
X
X
Heating (3)
5
COMPONENT
FAN SWITCH
STEP
NO.
CLOSED (ON)
FURNACE
HEAT
COMES
ON
X
Inform owner on how to operate system and what to expect of it. At the same time deliver Owner's Use and Care Booklet.
(1) Also set thermostat dial to call for cooling or heating as necessary,
(2) Use Service Facts attached to outdoor unit,
(3) Check only necessary if heating unit is used for indoor section and wiring has been disturbed
during installation
of cooling equipment,
Technical Literature - Printed in U.S.A.
The Trane Company
Unitary
Products
Group
6200 Troup Highway
Tyler, TX 75707
PAGE 8
Pub. No. 18-AC41D16-5
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 8 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Tue Mar 25 06:25:10 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools