INSTALLATION
OPERATION
MAINTENANCE
18-AB33D6-7
Models:
TCH024C1
TCH030C1
TCH036C1
TCH042C1
TCH048F1
TCH060F1
Packaged Cooling
Electric Heat
Over/Under
2, 2-1/2, 3, 3-1/2, 4, 5 Tons
IMPORTANT-- This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
ALL phases of this installation must comply with NATIONAL,
STATE, and LOCAL CODES.
These instructions do not purport to cover all variations in
systems nor to provide for every possible contingency to be
met in connection with installation. Should further information be
desired or necessary or should particular problems arise which are
not covered sufficiently for the purchaser's or installer's needs or
purposes, the matter should be referred to the manufacturer.
THIS INFORMATION IS FOR USE BY INDIVIDUALS HAVING
ADEQUATE BACKGROUNDS OF ELECTRICALAND MECHANI-
CAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL
AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL
INJURYAND/OR PROPERTY DAMAGE. THE MANUFACTURER
OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRE-
TATION OF THIS INFORMATION, NOR CAN IT ASSUME ANY
LIABILITY IN CONNECTION WITH ITS USE. 2, 2-1/2, 3, 3-1/2 Tons Shown
Reconnect all grounding devices.
All parts of this product that are capable of conducting electri-
cal current are grounded. If grounding wires, screws, straps,
clips, nuts, or washers used to complete a path to ground are
removed for service, they must be returned to their original
position and properly fastened.
CONTAINS REFRIGERANT!
SYSTEM CONTAINS OIL AND REFRIGERANT UNDER
HIGH PRESURE. RECOVER REFRIGERANTTO RELIEVE
PRESSURE BEFORE OPENING SYSTEM. Failureto follow
proper procedures can result in personal illness or injury or
severe equipment damage.
The manufactuter has a policy of continuous product and product data improvement, and it reserves the right to change design and
specification without notice.
© 2008 Trane 01/08
General Information
These instructions cover installation, operation, and mainte-
nance of all single package TCH024-060 air conditioning units.
For an easy and orderly installation, follow the sequence of
instructions as they are outlined. Improper installation can
result in unsatisfactory operation and/or dangerous conditions
as well as make the related warranty inapplicable. Read this
manual carefully before installing, operating, or performing
maintenance on this unit. Installation and maintenance should
be performed by qualified service technicians. Locate the unit in
accordance with local codes or the National Electrical Code. Each
unit contained an operating charge of HCFC-22 when shipped.
Unit Inspection
The material in this shipment has been inspected at the factory
and was released to the transportation agency without known
damage. Inspect the exterior of the carton for evidence of rough
handling in shipment. Check the unit nameplate to determine if
the unit is correct for the intended application. After moving the
equipment to the approximate location, unpack it carefully. If
damage to the unit is found, report the nature of this damage
immediately to the delivery agency. Check to be sure that the
refrigerant charge has been retained during shipment.
Power Supply
The power supply must be adequate for the unit and any
supplementary electric heaters, if added. Make certain that the
power supply to the unit agrees with the power requirements
specified on the unit nameplate. Separate branch circuits are
required for supplementary electric heaters.
Rigging
IMPORTANT: Check the handling facilities to ensure the
safety of both personnel and the unit. Be sure that the proper
method of rigging is used, with straps or slings and spreader bars
for protection during lifting.
Do not lift the unit without testing for balance and rigging.
Do not lift the unit in windy conditions or above personnel.
Do not lift the unit by attaching a clevis, hooks, pins, or bolts
to the unit casing, casing hardware, corner lugs, angles,
tabs, or flanges. Failure to observe this warning may result
in equipment damage.
Locations and Recommendations
This unit was designed for multiple applications: rooftop, out-
door ground level. For proper installation, the following recom-
mendations must be considered:
Installation of the unit should conform to local building codes or,
in the absence of local codes, to the National Electrical Code.
Canadian installations must conform to CSA and local codes
Select a location that will permit unobstructed airflow into the
outdoor coil and away from the fan discharge. The discharge air
from the outdoor fan must be unrestricted for a minimum of three
(3) feet above the unit. Any reduction of the unit clearances
recommended may result in condenser coil starvation or the
recirculation of warm condenser air. Actual clearances which are
inadequate should be reviewed with a local sales representative.
If the unit is located under an overhang, provisions must be made
to deflect the warm discharge air from under the overhang. See
Figures 1, 2 and 3. The unit must also be situated to permit easy
and unrestricted access for service.
Install internal accessories to the unit at the shop if practical.
Access and service clearances for the unit must be given careful
consideration when locating the duct entrance openings.
Figure 1 provides unit dimensions.
All fabricated outdoor ducts should be as short as possible.
Be sure the openings in the structure are large enough to
accommodate the ducts and the insulation surrounding them.
See Figure 1.
For outdoor, ground level applications the unit must be mounted
on a solid, level foundation that is not adjoined to the structure
because sound and vibration may be transmitted to the struc-
ture.
Field supplied mounting pads should be placed beneath the unit
to prevent transmission of vibration to the occupied structure.
Select a location that will minimize the length of the supply and
return ducts.
Position the unit so roof-run-offwater does not pour directly onto
the unit.
Select a location where external water drainage cannot collect
around the unit.
CAUTION MUST ALWAYS BE TAKEN TO AVOID PERSONAL
INJURIES AND/OR DAMAGE TO THE EQUIPMENT.
Elevation minimums must be observed for drain line "trap" and
ventilation to the under side of the unit.
All duct work inside the structure should be adequately insu-
lated.
All duct work outside of the structure must be insulated and
weatherproofed in accordance with local codes. If supplementary
heat is added, the duct connectors should be of a flame retardant
material.
Give consideration to shade, appearance, and noise.
The following warning complies with State of California law, Proposition 65.
WARNING: This product contains
fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.
Page 2
©
TCH024, 030, 036, 042C Unit Dimensions and Clearances_
,,B,, _
J
212mm
(8 3/8)
t
425mm
(16 3/4)
INSTALLATION /SERVICE CLEARANCE
BACK 48.0"
LEFT SIDE 24.0"
RIGHT SIDE 36.0"
TOP 36.0"
R1 3/8 )
SUPPLYNG
19mm
(3/4)
(2 5/8)
CONDENSER COIL
/
/
/
[ I 5/16 ]
gRAIN HOLE
GERANT GUAGE
-. CONNECTIONS
INDOOR BLOWER
--_ ............ACCESS
DRAIN PAN CONNECTION
19mm [ 5/4 II] FEMALE NPT
I24mm
(4 I/8)
803mm
[ 31 5/8 ]
j_ 203mm
260m_n
171mm (10 I/4)
(6 3/4}
Dwg. No. D673590 REV. 0
MODEL
TCH024C
TCH030C
TCH036C
TCH042C
APPROX. CORNER WTS - LBS.
Wl I W2 W3 W4
76 I 73 63 68
77 I 71 62 70
79 I 75 66 73
80 I 79 72 77
TOTAL
WEIGHT
LBS.
279
281
293
308
COIL DIMENSION (IN)
A B
14 16
14 16
14 16
20 16
Page 3
TCH048, 06F1 Unit Dimensions and Clearances
©
I 143mm
1473mm [45]
[58]
841mm
E33 I/8]
INSTALLATION /SERVICE CLEARANCE
BACK 48.0"
LEFT SIDE 24.0"
RIGHT SIDE 36.0"
TOP 36.0"
t
VIEW "X"
COIL
19mm
E3/4] TYP
2547mm
E3/43
336mm
El3 1/43
_DPAIN CONNECTION 19mm E3/4]
FEMALE SCHED. 40 PVC PIPE
NOTE: 3/4" SUPPORT RAILS LOCATED UNDERNEATH
BASE OF UNIT
218.4mm_
E8 I/2]
VIEW "A"
E2 I/4]
SUPPLEMTARY HEATER--
HV POWER ENTRY 5066mm
19 15/16
ONDENSER COIL
MODEL
Page 4
TOTAL
WEIGHT
LBS.
APPROX. CORNER WTS - LBS.
Wl W2 W3 W4
126 126 95 95
112 112 111 111
TCHO48F 443
TCHO60F 450
REFRIGERANT GUAGE
11963mm CONNECTIONS
E4 23/32]
UNIT POWER WIRING
CONTROL WIRING
VIEW X-X
76mm
E3] TYP
L,_gmm
E 9/32] TYP
94ram
E3 3/4] TYP
_17714mm
E6 3/4]
_ 94mm
[3 3/4] TYP
Installation Applications
Roof Top
For roof top installations, the roof must have sufficient struc-
tural strength to support the load. FHA approved construction
and local codes are normally adequate provided the roof joists
and rafters have a proportionally distributed load. See Figure 2.
The unit should be positioned for recommended clearances as
previously outlined under'l, ocation and Recommendations"
DISCHARGE AIR
® t
INTAKE AIR
(ALL SIDES)
RETURN AIR
(INSULATED)
Typical Rooftop Application
(INSULATED)
If duct hood or supply and return ducts are fabricated by the
installing contractor, be sure that the portion of the supply and
return ducts located outdoors is as short as possible. The supply
duct, return duct, and connectors should be insulated with 2
inches of insulation and weatherproofed. Be sure the openings
in the structure for the supply and return ducts are large enough
to include the insulation.
Use turning vanes inside the supply and return ducts when using
a square elbow take-off from the unit.
Vibration isolators are recommended to prevent transmission of
vibration to the structure. Isolate with at least four (4) vibration
isolators or equivalent. The isolators must provide a minimum
clearance of 1/4" beneath the unit to permit air to circulate under
the unit's base.
After the unit has been properly positioned, complete the instal-
lation according to the instructions in the following sections of
this manual. Then follow the Start-Up procedure on page 6 and
the Checkout procedure on page 10 of this manual.
Ground Level - Outdoor
For ground level installations, position the unit on a pad at least
two (2) inches larger than the unit on all sides. The unit must be
level on the pad. The pad must not contact the structure. Be sure
the outdoor portion of the supply and return air ducts are as short
as possible.
The installation should proceed as follows:
The unit must be isolated with mounting pads. The mounting
pads must provide a minimum of 1/4" clearance beneath the unit
to permit air circulation and prevent corrosion of the base. See
Figure 3.
®
PADS f
PAD
Typical Gound Level Application
Attach the supply and return air ducts to the unit. The portion
of the supply and return ducts located outdoors must be as short
as possible.
Insulate any ductwork outside the structure with at least 2
inches of insulation and weatherproofing. Be sure the openings
in the structure are large enough to include ducts and insulation.
Complete the installation according to the instructions in the
following sections of this manual.
mCondensate Drain Piping
A 3/4-inch female NPT condensate drain connection is provided
on the evaporator end of the unit. See Figure 1. Provide a trap
and fill it with water before starting the unit to prevent air from
being drawn through. Follow local codes and standard piping
practices when running the drain line Pitch the line downward
away from the unit. Avoid long horizontal runs. See Figure 4.
NOTE: Do not use reducing fittings in the drain line.
The condensate drain must be:
Made of 3/4" pipe.
Pitched 1/4" per foot to provide free drainage to a convenient
drain system
.Trapped
Not connected to a closed drain system.
©
3/4" PVC OR COPPER
TUBING AND FITTINGS
2" MIN.
2" MIN.
QTY. MATERIALS
TEE
90° ELL
PLUG
1 4" NIPPLE
2 2" NIPPLE
1 3/4" NPT TO PVC OR
COPPER ADAPTER
FROM DWG. 21C128186 FIG 1, R1
Page 5
Electrical Wiring
WARNING :TO PREVENT INJURY OR DEATH
DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING
PARTS. LOCK UNIT DISCONNECT SWITCH IN OPEN
POSITION BEFORE SERVICING UNIT.
Electrical Connections
Electrical wiring and grounding must be installed in accordance
with local codes or, in the absence of local codes, with the National
Electrical Code ANSI!NFPA 70, Latest Revision.
Disconnect Switch
Provide an approved weather-proof disconnect either on the side
of the unit or within close proximity and within sight of the
unit.
Over Current Protection
The branch circuit feeding the unit must be protected as shown
on the unit rating plate.
Power Wiring
The power supply lines must be run in weathertight conduit to
the disconnect and into the bottom of the unit control box.
Provide strain relief for all conduit with suitable connectors.
Provide flexible conduit supports whenever vibration transmis-
sion may cause a noise problem within the building structure.
Ensure all connections are made tight. See Figures 5 and 6:
Typical Field Wiring Diagrams.
NOTES:
1. For branch circuit wiring (main power supply to the unit
disconnect), wire size for the length of run should be
determined using the circuit ampacity found on the unit
nameplate and the N.E.C.
2. For more than 3 conductors in a raceway or cable, see the
N.E.C. for derating the ampacity of each conductor.
3. Wire size is based on 75 degrees C rated wire insulation.
Grounding
The unit must be electrically grounded in accordance
with local codes or the National Electrical Code.
Accessories
All electrical accessories must be installed and wired according
to the instructions packaged with the accessory.
Control Wiring (Class II)
Low voltage control wiring should not be run in the same conduit
with the power wiring unless Class I wire of the proper voltage
rating is used. Route the thermostat cable or equivalent single
leads of No. 18 AWG colored wire from the thermostat subbase
terminals through the rubber grommet on the unit. See Figure
1 for the control entry location. Make connections as shown on
the unit wiring diagram and in Figures 5 and 6.
Do not short thermostat wires since this will damage the control
transformer.
Electrical Wiring
Recommended wire sizes and lengths for installing the unit
thermostat are provided in Table 1: Thermostat Wire Size
and Maximum Length. The total resistance of these low
voltage wires must not exceed one (1) ohm. Any resistance in
excess of one (1) ohm may cause the control to malfunction
because of the excessive voltage drop.
IMPORTANT: Upon completion of wiring check all elec-
trical connections, including factory wiring within the
unit.
Make sure all connections are tight. Replace and secure all
electrical box covers and access doors before leaving the unit or
turning on the power to the unit.
After all electrical wiring is complete, set the thermostat system
switch on the OFF position so that the compressor will not run
and then apply power by closing the system main disconnect
switch. This will activate the compressor sump heat. Do not
change the Thermostat System Switch until power has been
applied long enough to evaporate any liquid HCFC-22 in the
compressor. It is recommended that the sump heat be energized
for a minimum of eight (8) hours prior to starting the unit.
Table 1
Thermostat Wire Size and Maximum Length
WIRE SIZE MAXIMUM LENTGH (Ft)
18 75
16 125
14 200
Air Filters
• These units require filters with adequate filter area be pro-
vided in the return air duct. Table 2 below gives filter data. The
specific location of the filters depends on the type of installation
and the layout of the duct system. Be sure the owner is aware
of the location of the filter and the need to change them as
required. The Filter Size (Sq.. Ft.) are based on 300 F.P.M. face
velocity. If permanent filters are used, size per mfg. recommen-
dation with clean resistance of .05" WC.
NOMINAL FILTER* FILTER
UNIT CFM (Sq Ft) SIZE RESISTANCE
TCHO24B 800 2.67 0.05
TCHO30B 1000 3.33 0.05
TCHO36B 1200 4.00 0.05
TCHO42B 1400 4.67 0.05
TCHO48F 1600 5.20 0.05
TCHO60F 2000 6.67 0.05
Table 2. Filter Data
Page 6
®TYPICAL
MANUAL
THEJRMOSTAT
Typical Field Wiring Diagram
TCH024, 030,036,042C and TCH048, 060F Units (Cooling Only)
J
®
NOTLS
TYPICAL
AUTO CHANGEOVER
THERMOSTAT
#
IFIELD
INSTALLED
JUMPER
TYPICAL
MANUAL
THERMOSTAT
I. FJSED DISCONNECT SIZE, POWLR WIRING AND
GROUNDING OF EQUIPMENT MUST COMPLY
WITH LOCAL CODES,
2. BE SURE POWER S PPLY AGREES VV]TH EQUIPMENT
NAMEPLATE
5 LOW VOLTAGE WIRING TO BE NO. 18 A W O
MINIMUM CONDUCTOR
z_ B
G
Z_ y
R
56B(BL) COMMON
47A(BK) FAN
44A(YL) COMPRESSOR
35A(RD) 24V
\ _FJ
PH.
POWER SUPPLY
5 P H
POWER SUPPLY AND
CIRCUIT PROTLC_ON /
DISCONNECT
PET,_ LOCAL CODES
WRE
INTER COMPONENT W'I:RIN©
24V. _. FACTORY
LINE V. WIRING
24V. _) FIELD
LINE V, W]RINO
B757385
SEE
NOTE 6
TCH024, 030,036,042C and TCH048, 060F Units (With Supplementary Heaters)
_ PACKAGED
AIR CONDITIONER
J
B 36B(BL) COMMON i POLARIZED
G 47A(BK) FAN PLU G
__ Y 44A(YL) COMPRESSOR
41A(SR) HEAT
l!t- GROUNDING
WIRE
PH. W
POWER SUPPLY PH,
_/ SUPPLY
L_V_J
5PH.
CIRCUIT PROTECTION/
DISCONNECT
PER LOCAL CODES
_1 _ B 56B
_ G 47A(BK)
INTER COMPONENT WIRING
24V "L FACTORY
LINE V.J WIRING
24V. "_. FIELD
LINE V./wIRING
S
1/F t 28 KW I PH. HEATER
;SE BOX FACTORY PROVIDED
/
PACKAGED
AIR CONDITIONER
HEATER
FUSE BOX
999
I1"..........
NOTES
W
1PH. POWER SUPPLY
THRU FUSED
DISCONNECT
PER LOCAL CODES
1. FUSED DISCONNECT SIZE, POWER WIRING AND
GROUNDING OF EQUIPMENT MUST COMPLY
WITH LOCAL CODES,
2, BE SURE POWER SUPPLY AGREES WITH EQUIPMENT
AND HEATER NAMEPLATE.
5. LOW VOLTAGE WIRING TO BE NO. 18 A W G
MINIMUM CONDUCTOR
4. SEE HEATER NAMEPLATE FOR CURRENT RATING
OF HEATER USED.
5. SEE UNIT AND HEATER DIAGRAM FOR ELECTRICAL
CONNECTION DETAILS.
6. dUMPER MUST BE CONNECTED BETWEEN 1 AND 2
FOR UNIT TO OPERATE IN HEATING.
Page 7
Sequence of Operation
The unit's operation is controlled by the remote room thermostat.
Once the thermostat is placed in the COOL position, the unit's
operation is automatic. A fan switch on the thermostat also
provides for continuous operation of the evaporator fan if desired.
This is the ON position. With the fan switch in the AUTO
position, the fan will only operate with the cooling cycle. Continu-
ous fan mode during cooling operation may not be appropriate in
humid climates. If the indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid, it is recommended that the
fan only be used in the AUTO mode.
Cooling
On a call for cooling, the indoor fan "G" and the compressor
circuit'S' are energized. The indoor fan circuit"G" energizes the
the fan relay coil this closes the fan relay contacts (FDR-1) and
the indoor fan motor(IDFM) starts. The compressor circuit '5_"
energizes the (MS) contactor coil this powers the compressor
(CPR) and the outdoor fan motor (ODFM). When the thermo-
stat determines that further cooling is not required, the contactors
are de-energized.
Short Duration Shut Down
To shut down the unit for a brief period of time, turn the
thermostat system switch to OFF and place the fan switch in the
AUTO position.
Heating
On a call for heat, the thermostat '3Y" is energized, which
connects to unit'%Y", which energizes the "AH" heater contactor
coil. The"AH" contactor closes powering the heater, provided all
element limits are closed.
Note: The indoor thermostat must be configured for electric
heat to provide a"G" signal to energize the indoor fan relay (FDR-
1) during the heating mode. The heater control circuit will not be
energized unless the indoor fan relay (FDR-2) is energized.
ICM FAN MOTOR ADJUSTMENTS (TCH048, 060F ONLY)
If the airflow needs to be increased or decreased, see the Airflow
Table in the Service Facts. Information on changing the speed of
the blower motor is in the Blower Performance Table.
Blower speed changes are made on the ICM Fan Control mounted
in the control box. The ICM Fan Control controls the variable
speed motor.
There is a bank of 8 dip switches (See Figure 7), located at the
upper left side of the board. The dip switches work in pairs to
match the cooling/heat airflow (CFM/TON), Fan off-delay op-
tions, and electric heat airflow adjustment. The switches appear
as shown in Figure 7.
ICM FAN CONTROL
CFM
SELECTION DIP
LI_/ .SWITCHES
_CFM FAN Y Y LO
®®B
W3 W2 wI
Start-Up
Pre-Start Quick Check List
Is the unit properly and securely located and level with the
proper clearance?
Is the ductwork correctly sized, run, taped, insulated and
weatherproofed with the proper unit arrangement?
Is the condensate line properly sized, run, trapped, and
pitched? Does it drain freely?
Is the filter of the correct size and number? Are the supply
and return registers unobstructed?
Is the wiring properly sized and run according to the Unit
Wiring Diagram, Figures 5 and 6?
Is the power supply correct for the unit's requirements?
Are all wiring connections, including those in the unit
itself, tight?
Is the thermostat well located, level, correctly wired, and
accurately adjusted?
Do the outdoor fan and the indoor fan turn free without
rubbing? Are both fans tight on their shafts?
Has the indoor blower speed tap been determined andthe
proper speed set? See the Unit Wiring Diagram,Figures 5
and 6.
Has all work been done in accordance to the applicable
local and national codes?
Are all cover and access panels in place to prevent air loss
and to protect against safety hazards?
Have all tools and debris around, on top of, and under the
unit been removed?
Starting the Unit In the Cooling Mode
IMPORTANT: Before starting the system in the cooling
cycle, turn the thermostat switch to "OFF" and close the
unit disconnect switch. This procedure energizes the
compressor crankcase heat (if equipped) thereby vapor-
izing any liquid HICFC-22 in the crankcase. This is a
precaution against foaming at start-up which could
damage the compressor. Allow the heat to operate for a
minimum of eight (8) hours.
The TCH048-060F units do not have sump heat as shipped.
NOTE: The crankcase heater is a field installed option on
some models.
NOTE: See the section on "Sequence of Operation" for a
description of the cooling operating sequence.
To start the unit in the cooling mode, set the thermostat
system switch to COOL.
Move the thermostat COOL indicator to a setting below
Page 8
Start-Up Start-Up
room temperature. The outdoor fan motor, compressor, and
evaporator fan motor will operate automatically.
Operating Pressures
After the unit has operated in the cooling mode for a short time,
install pressure gauges on the gauge ports of the discharge and
suction line valves. Check the suction and discharge pressures
and compare them to the normal operating pressures provided in
the unit's SERVICE FACTS.
Starting the Unit in the Heating Mode
NOTE: See the section on "Sequence of Operation" for a descrip-
tion of the heating operating sequence.
Check to make sure that all grilles and registers are
open and all unit access doors are closed before start-up.
Voltage
With the compressor operating, check the line voltage at the unit.
The voltage should be within the range shown on the unit
nameplate. If low voltage is encountered, check the size and
length of the supply line from the main disconnect to the unit.
The line may be undersized for the length of the run.
Cooling Shut Down
• Place the system selector switch in the OFF position or reset
the thermostat at a setting above the room temperature.
To start the unit in the heating mode, set the thermo-stat
system switch to HEAT. Move the thermostat
HEAT indicator to a setting above room temperature
and place the fan switch in the AUTO or ON positions.
The indoor fan motor will operate automatically.
The thermostat must provide a "G" signal for fan operation.
If using an auto changeover thermostat, see Figures 5 and 6
for the appropriate connections.
Heating Shut-Down
• Do not de-energize the main power disconnect except when
the unit is to be serviced. Power is required to keep the
compressor crankcase heat (if equipped) energized and boil
off refrigerant in the compressor.
Place the system selector switch to the OFF position or place
the heating selector lever at a setting below the room
temperature.
TROUBLESHOOTING CHART
P SPS S
SP SS S
S PP SP
S SPS
SS
P SS SP
P PS
SP PS SPS
P SPPP
PSPPP S
P P
P PPPS S
P S P P P S P S P S S S S S
S SP P
X664590
\
\
SYSTEM FAULTS
REFRIGERANT CIRCUIT
Liquid PressureToohigh
Liquid Pressure TooLow
Suction PressureTooHigh
Suction PressureTooLow
Liquid Refrigerant floodback (TXV System)
Liquid Refrig. floodback (Cap, TubeSystem)
I. D.Coil Frosting
Compressor Runs Inadequate or No Cooling
ELECTRICAL
Compressor & O.D. fan Do Not Start p
Compressor Will Not Start ButO.D. Fan Runs
O.D. FanWon't Start
Compressor Hums But Will Not Start
Compressor Cycles on IOL
I.D.Blower Won't Start p
P-PRIMARY CAUSES S-SECONDARY CAUSES
Page 9
Maintenance
Routine Maintenance by Owner
You can do some of the periodic maintenance functions for your TCH unit
yourself. These functions include replacing the disposable or cleaning the
permanent air filters, cleaning the unit's cabinet, cleaning the condenser coil,
and conducting a general inspection of the unit on a regular basis.
WARNING: TO PREVENT INJURY OR DEATH
DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING
PARTS. LOCK UNIT DISCONNECT SWITCH IN OPEN
POSITION BEFORE SERVICING UNIT.
Air Filters
It is very important to keep the central duct system air filters clean. Be sure
to inspect them at least once each month when the system is in constant
operation. In new construction, check the filters every week for the first
four (4) weeks.
•If you have disposable-type filters, replace them with new filters of
the same type and size. Do not try to clean disposable filters.
•Clean permanent-type filters by washing them with a mild detergent
and water. Make sure that the filters are thoroughly dry before re-
installing them in the unit.
•Replace permanent filters annually if washing fails to clean them or
ifthey show signs of deterioration. Use the same type and size as was
originally installed.
Outdoor Coil
Unfiltered air circulated through the unit's outdoor coil can cause the
coil's surface to become clogged with dust, dirt, etc. To clean the coil,
stroke the coil surface with a soft-bristled brush vertically, that is, in the
direction of the fins.
•Be sure to keep all vegetation away from the outdoor coil area.
Maintenance Performed by Serviceman
To keep your unit operating as designed, the manufacturer recommends
that a qualified serviceman check over the entire system at least once each
year as well as any other time that you feel that one is needed. Your
serviceman should examine and inspect:
•filters (for cleaning or replacement)
•motors and drive system components
•condenser coils (for cleaning)
•safety controls (for mechanical cleaning)
•electrical components and wiring (for possible replacement
and/or connection tightness)
•condensate drain (for cleaning)
In addition, your serviceman should inspect:
•unit duct connections to see that they are physically sound and sealed
to the unit casing
•unit mounting support to see that it is sound
•unit to see that there is no obvious unit deterioration.
The following warning complies with State of California law, Proposition 65.
,WARNING: This product contains
fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.
PRECAUTIONARY MEASURES
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes. Wear long-
sleeved, loose-fitting clothing, gloves, and eye
protection.
Wash clothes separately from other clothing: rinse
washer thoroughly.
Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact Flush eyes with water to remove dust.
If symptoms persist, seek medical
attention.
Skin Contact - Wash affected areas gently with soap
and warm water after handling.
Page 10
Limited Warranty
Central Air Conditioner
4TCC3, TCD, TCH, TCK, TCM,
TCP, THC and TSC (Parts Only)
Models Less Than 20 Tons for Residential Use*
This limited warranty is extended byTrane U.S. Inc., to the original purchaser and to any succeeding owner of the
real property to which the Air Conditioner is originally affixed, and applies to products purchased and retained for use
within the U.S.A. and Canada.
If any part of your Air Conditioner fails because of a manufacturing defect within five years from the date of the origi-
nal purchase, Warrantor will furnish without charge the required replacement part. Any local transportation, related
service labor, diagnosis calls, refrigerant and related items are not included.
If the sealed motor-compressor fails because of a manufacturing defect within five years from the date of original pur-
chase, Warrantor will furnish without charge the required replacement compressor. Any local transportation, related
service labor, diagnosis calls, refrigerant and related items are not included.
This limited warranty does not cover failure of your Central Air Conditioner if it is damaged while in your possession,
damage caused by unreasonable use of the Central Air Conditioner and/or damage from failure to properly main-
tain the Central Air Conditioner as set forth in the Use and Care manual (see Proper Maintenance section).
THE LIMITED WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WAR-
RANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED,
IN LAW OR IN FACT, INCLUDING BUT NOT SPECIFICALLY LIMITEDTO IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRAN-
TOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This lim-
ited warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Parts will be provided by our factory organization through an authorized service organization in your area listed in the
yellow pages. If you wish further help or information concerning this limited warranty, contact:
Trane
P.O. Box 9010, Tyler, TX 75711-9010
Attention: Manager, Field Operations Excellence
Or visit our website: www.trane.com/residential
TW- 1002-4707
* This limited warranty is for residential usage of this equipment and not applicable when this equipment is used for a
commercial application. A commercial use is any application where the end purchaser uses the product for other than
personal, family or household purposes.
The limited warranties displayed in this publication and/or on ComfortSite TM
may not accurately reflect the actual limited warranty that shipped with the
product. 26-1000-21
Page 11
Limited Warranty
Central Air Conditioner
4TCY4, TCY, 4TCC3, 4TCX3, TCD,
TCH, TCK, THC and TSC (Parts Only)
Models Less Than 20 Tons for Commercial Use*
This warranty is extended by Trane U.S. Inc., to the original purchaser and to any succeeding owner of the real prop-
erty to which the Air Conditioner is originally affixed, and applies to products purchased and retained for use within the
U.S.A. and Canada. There is no warranty against corrosion, erosion or deterioration.
If any part of your Air Conditioner fails because of a manufacturing defect within one year from the date of the original
purchase, Warrantor will furnish without charge the required replacement part.
In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through fifth
year from the date of original purchase, Warrantor will furnish without charge the required replacement compressor.
Warrantor's obligations and liabilities under this warranty are limited to furnishing EO.B. Warrantor factory or ware-
house replacement parts for Warrantor's products covered under this warranty. Warrantor shall not be obligated to pay
for the cost of lost refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability
shall be limited solely to the purchase price of the equipment under warranty shown to be defective.
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES
AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW
OR IN FACT, INCLUDING BUT NOT SPECIFICALLY LIMITEDTO IMPLIED WARRANTIES OF MER-
CHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE
LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation
of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives
you specific legal rights, and you may also have other rights which vary from state to state.
Trane
P.O. Box 9010
Tyler, TX 75711-9010
Attention: Manager, Field Operations Excellence
TW-1001-4707
* This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a
residential application. Commercial use is any application where the end purchaser uses the product for other than
personal, family or household purposes.
The limited warranties displayed in this publication and/or on ComfortSite TM
may not accurately reflect the actual limited warranty that shipped with the
product.
Trane
6200 Troup Highway
Tyler,TX 75703
Page 12
26-1000-21
Page 1 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 2 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 3 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 4 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 5 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 6 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 7 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 8 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 9 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 10 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 11 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057
Page 12 of 12 - TRANE  Package Units(both Units Combined) Manual L0903057