TRANE Package Units(both Units Combined) Manual L0903057

User Manual: TRANE TRANE Package Units(both units combined) Manual TRANE Package Units(both units combined) Owner's Manual, TRANE Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

DownloadTRANE  Package Units(both Units Combined) Manual L0903057
Open PDF In BrowserView PDF
INSTALLATION
OPERATION
MAINTENANCE
Models:
TCH024C1
TCH030C1
TCH036C1

IMPORTANT--

18-AB33D6-7

Packaged Cooling
Electric Heat
Over/Under
2, 2-1/2, 3, 3-1/2, 4, 5 Tons

TCH042C1
TCH048F1
TCH060F1

This Document

is customer

property

and is to remain

with this unit.

Please

return

to service

information

pack upon completion

of work.

ALL phases of this installation must comply with NATIONAL,
STATE, and LOCAL CODES.
These instructions do not purport to cover all variations in
systems nor to provide for every possible contingency to be
met in connection with installation. Should further information be
desired or necessary or should particular problems arise which are
not covered sufficiently for the purchaser's or installer's needs or
purposes, the matter should be referred to the manufacturer.

THIS INFORMATION IS FOR USE BY INDIVIDUALS HAVING
ADEQUATE BACKGROUNDS OF ELECTRICALAND MECHANICAL EXPERIENCE.
ANY ATTEMPT TO REPAIR A CENTRAL
AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL
INJURYAND/OR PROPERTY DAMAGE. THE MANUFACTURER
OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION, NOR CAN IT ASSUME ANY
LIABILITY IN CONNECTION WITH ITS USE.

2, 2-1/2, 3, 3-1/2 Tons Shown

Reconnect
all grounding
devices.
All parts of this product that are capable of conducting electrical current are grounded. If grounding wires, screws, straps,
clips, nuts, or washers used to complete a path to ground are
removed for service, they must be returned to their original
position and properly fastened.

The manufactuter has a policy of continuous
specification without notice.
© 2008 Trane

CONTAINS REFRIGERANT!
SYSTEM CONTAINS OIL AND REFRIGERANT UNDER
HIGH PRESURE. RECOVER REFRIGERANTTO RELIEVE
PRESSURE BEFORE OPENING SYSTEM. Failureto follow
proper procedures can result in personal illness or injury or
severe equipment damage.

product and product data improvement,

and it reserves the right to change design and
01/08

General Information
These instructions
cover installation,
operation,
and maintenance of all single package TCH024-060
air conditioning
units.
For an easy and orderly installation,
follow the sequence
of
instructions
as they are outlined.
Improper
installation
can
result in unsatisfactory
operation
and/or dangerous
conditions
as well as make the related warranty
inapplicable.
Read this
manual
carefully
before installing,
operating,
or performing
maintenance
on this unit. Installation
and maintenance
should
be performed by qualified service technicians.
Locate the unit in
accordance with local codes or the National Electrical Code. Each
unit contained an operating charge of HCFC-22 when shipped.

Power Supply
The power supply must be adequate
for the unit and any
supplementary
electric heaters, if added. Make certain that the
power supply to the unit agrees with the power requirements
specified on the unit nameplate.
Separate
branch circuits are
required for supplementary
electric heaters.

Rigging

Unit Inspection

IMPORTANT:
Check the handling
facilities
to ensure the
safety of both personnel and the unit. Be sure that the proper
method of rigging is used, with straps or slings and spreader bars
for protection
during lifting.

The material in this shipment
has been inspected at the factory
and was released to the transportation
agency without known
damage.
Inspect the exterior of the carton for evidence of rough
handling in shipment.
Check the unit nameplate
to determine
if
the unit is correct for the intended application.
After moving the
equipment
to the approximate
location, unpack it carefully.
If
damage to the unit is found, report the nature of this damage
immediately
to the delivery agency.
Check to be sure that the
refrigerant
charge has been retained
during shipment.

Do not lift the unit without
testing for balance and rigging.
Do not lift the unit in windy conditions
or above personnel.
Do not lift the unit by attaching
a clevis, hooks, pins, or bolts
to the unit casing, casing hardware,
corner lugs, angles,
tabs, or flanges. Failure to observe this warning may result
in equipment
damage.

Locations and Recommendations
This unit was designed for multiple applications:
rooftop, outdoor ground level. For proper installation,
the following recommendations
must be considered:
Installation
of the unit should conform to local building codes or,
in the absence of local codes, to the National
Electrical
Code.
Canadian
installations
must conform to CSA and local codes
Select a location that will permit unobstructed
airflow into the
outdoor coil and away from the fan discharge. The discharge air
from the outdoor fan must be unrestricted
for a minimum of three
(3) feet above the unit. Any reduction
of the unit clearances
recommended
may result in condenser
coil starvation
or the
recirculation
of warm condenser air. Actual clearances which are
inadequate
should be reviewed with a local sales representative.
If the unit is located under an overhang, provisions must be made
to deflect the warm discharge air from under the overhang.
See
Figures 1, 2 and 3. The unit must also be situated to permit easy
and unrestricted
access for service.
Install

internal

accessories

to the unit at the shop if practical.

Position the unit so roof-run-offwater
the unit.
CAUTION
INJURIES

does not pour directly

onto

MUST ALWAYS BE TAKEN TO AVOID PERSONAL
AND/OR

DAMAGE

TO THE EQUIPMENT.

work inside

the structure

should

be adequately

insu-

All duct work outside of the structure
must be insulated
and
weatherproofed
in accordance with local codes. If supplementary
heat is added, the duct connectors should be of a flame retardant
material.

Page 2

All fabricated

outdoor

ducts

should

be as short

as

possible.

Be sure the openings in the structure
are large enough
accommodate
the ducts and the insulation
surrounding
See Figure 1.

to
them.

For outdoor, ground level applications
the unit must be mounted
on a solid, level foundation
that is not adjoined to the structure
because sound and vibration
may be transmitted
to the structure.
Field supplied mounting
to prevent transmission
Select a location
return ducts.
Select a location
around the unit.

that

warning

pads should be placed beneath the unit
of vibration
to the occupied structure.

will minimize

where

Give consideration
The following

Elevation minimums
must be observed for drain line "trap" and
ventilation
to the under side of the unit.
All duct
lated.

Access and service clearances for the unit must be given careful
consideration
when locating
the duct entrance
openings.
Figure 1 provides unit dimensions.

external

to shade,
complies

WARNING:

the length

water

appearance,

of the supply

drainage

cannot

and

collect

and noise.

with State of California

law, Proposition

65.

This product contains

fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.

TCH024, 030, 036, 042C Unit Dimensions and Clearances_

©

,,B,, _

J

R1

3/8

)

212mm
(8 3/8)

CONDENSER

t

/

COIL

/

/
SUPPLY
NG
(2

5/8)

425mm
(16
3/4)

[
gRAIN

INSTALLATION

/ SERVICE

CLEARANCE

BACK

48.0"

LEFT SIDE

24.0"

RIGHT SIDE

36.0"

TOP

36.0"

GERANT
CONNECTIONS

-.
INDOOR

--_

I 5/16
HOLE

]

GUAGE

BLOWER

............ACCESS
DRAIN
19mm

[

PAN
5/4

CONNECTION
II] FEMALE

NPT

19mm
(3/4)

I24mm
(4 I/8)

[

j_

31

803mm
5/8

]

203mm

171mm
(6 3/4}

APPROX.

CORNER

WTS - LBS.

I/4)

260m_n

Wl

I W2

W3

W4

TOTAL
WEIGHT
LBS.

TCH024C

76

I

73

63

68

TCH030C

77

I

71

62

70

TCH036C

79

I

75

66

TCH042C

80

I

79

72

MODEL

Dwg. No. D673590 REV. 0

(10

COIL DIMENSION (IN)
A

B

279

14

16

281

14

16

73

293

14

16

77

308

20

16

Page 3

TCH048, 06F1 Unit Dimensions and Clearances

©
I 143mm
[45]

1473mm
[58]

INSTALLATION

841mm
E33
I/8]

/ SERVICE CLEARANCE

BACK

48.0"

LEFT SIDE

24.0"

RIGHT SIDE

36.0"

TOP

36.0"

2547mm

t
VIEW

E3/43

_DPAIN
336mm
El3
1/43

"X"

E3/4]

19mm
TYP

NOTE:

3/4"

CONNECTION
FEMALE

SUPPORT
RAILS
BASE OF

LOCATED
UNIT

SCHED.

19mm
40

PVC

E3/4]

PIPE

UNDERNEATH

COIL

218.4mm_
E8
I/2]
ONDENSER

VIEW

COIL

"A"
E2

I/4]

SUPPLEMTARY
HEATER-HV
POWER ENTRY

5066mm
19 15/16

REFRIGERANT
CONNECTIONS

11963mm
E4 23/32]
UNIT

POWER

CONTROL

GUAGE

WIRING

WIRING

76mm
E3]

TYP

L,_gmm
E

94ram

APPROX. CORNER WTS - LBS.
Wl

W2

W3

W4

TOTAL
WEIGHT
LBS.

TCHO48F

126

126

95

95

443

TCHO60F

112

112

111

111

450

MODEL

E3

TYP

3/4]

_17714mm

_
[3
VIEW

Page 4

3/4]

E6

X-X

94mm
3/4]
TYP

9/32]

TYP

Installation Applications
Roof Top
For roof top installations,
the roof must have sufficient structural strength
to support the load. FHA approved construction
and local codes are normally adequate
provided the roof joists
and rafters have a proportionally
distributed
load. See Figure 2.
The unit should be positioned
for recommended
clearances
previously outlined under'l, ocation
and Recommendations"

DISCHARGE

®

t

®

as

AIR

PADS
INTAKE
(ALL

f

AIR

PAD

SIDES)

Typical

Gound

Level

Application

Attach the supply and return air ducts to the unit. The portion
of the supply and return ducts located outdoors must be as short
as possible.
Insulate
any ductwork
outside the structure
with at least
2
inches of insulation
and weatherproofing.
Be sure the openings
in the structure are large enough to include ducts and insulation.
RETURN

Typical

Rooftop

Complete
following

AIR

(INSULATED)

(INSULATED)

Use turning vanes inside the supply and return
a square elbow take-off from the unit.

ducts when using

After the unit has been properly positioned, complete the installation according to the instructions
in the following sections of
this manual.
Then follow the Start-Up procedure
on page 6 and
the Checkout procedure
on page 10 of this manual.

Level - Outdoor

in the

proceed

at least
must be
Be sure
as short

Drain Piping

A 3/4-inch female NPT condensate
drain connection is provided
on the evaporator
end of the unit. See Figure 1. Provide a trap
and fill it with water before starting the unit to prevent air from
being drawn through.
Follow local codes and standard
piping
practices when running the drain line Pitch the line downward
away from the unit. Avoid long horizontal
runs. See Figure 4.
Do not use reducing

fittings

in the drain

The condensate
drain must be:
• Made of 3/4" pipe.
• Pitched 1/4" per foot to provide free drainage
drain system
.Trapped
• Not connected to a closed drain system.

TUBING

to a convenient

AND

FITTINGS

QTY. MATERIALS
TEE
90 ° ELL
PLUG

2" MIN.

as follows:

1
2

4" NIPPLE
2" NIPPLE

1

3/4" NPT TO PVC OR
COPPER ADAPTER

2" MIN.
The unit must be isolated with mounting
pads. The mounting
pads must provide a minimum of 1/4" clearance beneath the unit
to permit air circulation
and prevent corrosion of the base. See
Figure 3.

line.

©
3/4" PVC OR COPPER

For ground level installations,
position the unit on a pad
two (2) inches larger than the unit on all sides. The unit
level on the pad. The pad must not contact the structure.
the outdoor portion of the supply and return air ducts are
as possible.
should

m Condensate

NOTE:

Vibration isolators are recommended
to prevent transmission
of
vibration
to the structure.
Isolate with at least four (4) vibration
isolators or equivalent.
The isolators must provide a minimum
clearance of 1/4" beneath the unit to permit air to circulate under
the unit's base.

The installation

to the instructions

Application

If duct hood or supply and return ducts are fabricated
by the
installing
contractor,
be sure that the portion of the supply and
return ducts located outdoors is as short as possible. The supply
duct, return duct, and connectors
should be insulated
with 2
inches of insulation
and weatherproofed.
Be sure the openings
in the structure
for the supply and return ducts are large enough
to include the insulation.

Ground

the installation
according
sections of this manual.

FROM

DWG.

21C128186

FIG 1, R1

Page 5

Electrical Wiring

Electrical Wiring
WARNING

: TO

PREVENT INJURY OR DEATH

DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING
PARTS.
LOCK UNIT DISCONNECT
SWITCH
IN OPEN
POSITION BEFORE SERVICING UNIT.

Recommended
wire sizes and lengths for installing
the unit
thermostat
are provided in Table 1: Thermostat
Wire Size
and Maximum
Length.
The total resistance
of these low
voltage wires must not exceed one (1) ohm. Any resistance
in
excess of one (1) ohm may cause the control to malfunction
because of the excessive voltage drop.

Electrical Connections
Electrical wiring and grounding
must be installed in accordance
with local codes or, in the absence of local codes, with the National
Electrical
Code ANSI!NFPA
70, Latest Revision.

Disconnect

Switch

Provide an approved weather-proof
disconnect either on the side
of the unit or within close proximity
and within
sight of the
unit.

Over Current Protection
The branch circuit feeding
on the unit rating plate.

the unit must

be protected

as shown

The power supply lines must be run in weathertight
conduit to
the disconnect
and into the bottom of the unit control box.
Provide strain relief for all conduit with suitable connectors.
Provide flexible conduit supports whenever vibration transmission may cause a noise problem within the building structure.
all connections
are made
Field Wiring Diagrams.

tight.

See Figures

NOTES:
1. For branch circuit wiring (main power
disconnect),
wire size for the length
determined
using the circuit ampacity
nameplate
and the N.E.C.

supply to the unit
of run should be
found on the unit

on 75 degrees

C rated

wire insulation.

grounded
Electrical

in accordance
Code.

Accessories
All electrical accessories
must be installed and wired
to the instructions
packaged with the accessory.

according

Control Wiring (Class II)
Low voltage control wiring should not be run in the same conduit
with the power wiring unless Class I wire of the proper voltage
rating is used. Route the thermostat
cable or equivalent
single
leads of No. 18 AWG colored wire from the thermostat
subbase
terminals
through the rubber grommet on the unit. See Figure
1 for the control entry location.
Make connections
as shown on
the unit wiring diagram and in Figures 5 and 6.
Do not short thermostat
transformer.

Page 6

wires since this will damage

the control

(8) hours

prior to starting

the unit.

WIRE SIZE
18
16

MAXIMUM LENTGH (Ft)
75
125

14

200

Air Filters
• These units require filters with adequate
filter area be provided in the return air duct. Table 2 below gives filter data. The
specific location of the filters depends on the type of installation
and the layout of the duct system.
Be sure the owner is aware
of the location of the filter and the need to change them as
required.
The Filter Size (Sq.. Ft.) are based on 300 F.P.M. face
velocity. If permanent
filters are used, size per mfg. recommendation with clean resistance
of .05" WC.

Grounding
The unit must
be electrically
with local codes or the National

of eight

Table 1
Thermostat Wire Size and Maximum Length

5 and 6:

2. For more than 3 conductors
in a raceway or cable, see the
N.E.C. for derating the ampacity of each conductor.
3. Wire size is based

After all electrical wiring is complete, set the thermostat
system
switch on the OFF position so that the compressor
will not run
and then apply power by closing the system main disconnect
switch.
This will activate the compressor
sump heat.
Do not
change the Thermostat
System Switch until power has been
applied long enough to evaporate
any liquid HCFC-22 in the
compressor.
It is recommended
that the sump heat be energized
for a minimum

Power Wiring

Ensure
Typical

IMPORTANT:
Upon completion
of wiring
check all electrical connections,
including
factory
wiring
within
the
unit.
Make sure all connections
are tight.
Replace and secure all
electrical box covers and access doors before leaving the unit or
turning on the power to the unit.

NOMINAL

FILTER*

FILTER

TCHO24B

CFM
800

(Sq Ft) SIZE
2.67

RESISTANCE
0.05

TCHO30B

1000

3.33

0.05

TCHO36B

1200

4.00

0.05

TCHO42B

1400

4.67

0.05

TCHO48F

1600

5.20

0.05

TCHO60F

2000

6.67

0.05

UNIT

Table 2. Filter Data

Typical Field Wiring Diagram

®

TCH024, 030,036,042C

and TCH048, 060F Units (Cooling Only)

TYPICAL
MANUAL
THEJRMOSTAT

J

z_

B
G

Z_

56B(BL)

COMMON

47A(BK)

FAN

y

44A(YL)

COMPRESSOR

R

35A(RD)

24V

WRE

\ _FJ
PH.

NOTLS

INTER

COMPONENT

W'I:RIN©

POWER SUPPLY
I.

FJSED
DISCONNECT
SIZE,
GROUNDING
OF EQUIPMENT
WITH
LOCAL
CODES,

2.

BE SURE
NAMEPLATE

5

LOW
VOLTAGE
WIRING
MINIMUM
CONDUCTOR

POWER

S

PPLY
TO

POWLR
WIRING
MUST
COMPLY

AGREES
BE

NO.

AND

24V. V. _. WIRING
FACTORY
LINE

VV]TH

EQUIPMENT

18

W O

A

5
POWER
CIRCUIT

SUPPLY
AND
PROTLC_ON

24V.
LINE V, _) FIELD
W]RINO

/

DISCONNECT
PET,_ LOCAL

®

PH

TCH024, 030,036,042C

and TCH048, 060F Units (With Supplementary Heaters)
AIR CONDITIONER
PACKAGED

_

TYPICAL
MANUAL
THERMOSTAT

B757385

CODES

J

INTER

COMPONENT

24V
"L FACTORY
LINE V.J WIRING

SEE

G

__
NOTE

WIRING

47A(BK)

Y

FAN

44A(YL)

6

24V.
"_. FIELD
LINE V./wIRING

G

COMPRESSOR

41A(SR)
36B(BL)

B

PLU

HEAT
COMMON

i

S

POLARIZED

1/F

l!tPH.
POWER

t

;SE BOX FACTORY
PROVIDED
28 KW I PH. HEATER

/
GROUNDING
WIRE

W
SUPPLY

PH,

_/

SUPPLY
PACKAGED

L_V_J

AIR

CONDITIONER

5PH.
CIRCUIT

PROTECTION/
DISCONNECT

PER

LOCAL

CODES

HEATER
FUSE

BOX

999
_1 _

_

B

56B

G

47A(BK)

I1"......

W
1PH.
POWER SUPPLY
THRU FUSED
DISCONNECT
PER LOCAL CODES

NOTES
TYPICAL
AUTO
CHANGEOVER
THERMOSTAT

#
IFIELD
INSTALLED
JUMPER

1. FUSED
DISCONNECT
SIZE,
GROUNDING
OF EQUIPMENT
WITH LOCAL
CODES,
2, BE SURE POWER SUPPLY
AND HEATER
NAMEPLATE.

POWER
WIRING
MUST COMPLY
AGREES

WITH

AND

EQUIPMENT

5. LOW VOLTAGE
WIRING TO BE NO. 18 A W G
MINIMUM
CONDUCTOR
4. SEE HEATER
NAMEPLATE
FOR CURRENT
RATING
OF HEATER
USED.
5. SEE UNIT AND HEATER
CONNECTION
DETAILS.

DIAGRAM

FOR

6. dUMPER
MUST BE CONNECTED
BETWEEN
FOR UNIT TO OPERATE
IN HEATING.

ELECTRICAL
1 AND

2

Page 7

Start-Up

Sequence of Operation
The unit's operation is controlled by the remote room thermostat.
Once the thermostat
is placed in the COOL position, the unit's
operation
is automatic.
A fan switch on the thermostat
also
provides for continuous operation of the evaporator fan if desired.
This is the ON position.
With the fan switch in the AUTO
position, the fan will only operate with the cooling cycle. Continuous fan mode during cooling operation may not be appropriate
in
humid climates. If the indoor air exceeds 60% relative humidity
or simply feels uncomfortably
humid, it is recommended
that the
fan only be used in the AUTO mode.
Cooling
On a call for cooling, the indoor fan "G" and the compressor
circuit'S'
are energized. The indoor fan circuit"G" energizes the
the fan relay coil this closes the fan relay contacts (FDR-1) and
the indoor fan motor(IDFM)
starts. The compressor circuit '5_"
energizes
the (MS) contactor coil this powers the compressor
(CPR) and the outdoor fan motor (ODFM). When the thermostat determines that further cooling is not required, the contactors
are de-energized.
Short Duration
Shut Down
To shut down the unit for a brief period of time, turn the
thermostat
system switch to OFF and place the fan switch in the
AUTO position.
Heating
On a call for heat, the thermostat
'3Y" is energized,
which
connects to unit'%Y", which energizes the "AH" heater contactor
coil. The"AH" contactor closes powering the heater, provided all
element limits are closed.
Note:
The indoor thermostat
must be configured
for electric
heat to provide a"G" signal to energize the indoor fan relay (FDR1) during the heating mode. The heater control circuit will not be
energized unless the indoor fan relay (FDR-2) is energized.
ICM FAN MOTOR ADJUSTMENTS
(TCH048, 060F ONLY)
If the airflow needs to be increased or decreased, see the Airflow
Table in the Service Facts. Information
on changing the speed of
the blower motor is in the Blower Performance
Table.
Blower speed changes are made on the ICM Fan Control mounted
in the control box. The ICM Fan Control controls the variable
speed motor.
There is a bank of 8 dip switches (See Figure 7), located at the
upper left side of the board. The dip switches work in pairs to
match the cooling/heat
airflow (CFM/TON),
Fan off-delay options, and electric heat airflow adjustment.
The switches appear
as shown in Figure 7.

ICM FAN CONTROL
CFM
SELECTION

LI_/

_CFM

DIP

.SWITCHES

FAN

Y
Y LO
®®B

W3 W2 wI

Page 8

Pre-Start

Quick Check List

• Is the unit properly
proper clearance?
• Is the ductwork
weatherproofed

and securely

located and level with the

correctly sized, run, taped, insulated
with the proper unit arrangement?

• Is the condensate
line properly
pitched? Does it drain freely?

sized, run,

• Is the filter of the correct size and number?
and return registers unobstructed?

trapped,

• Are all wiring
itself, tight?

supply

correct

connections,

for the unit's
including

• Is the thermostat
well located,
accurately
adjusted?

and

Are the supply

• Is the wiring properly sized and run according
Wiring Diagram, Figures 5 and 6?
• Is the power

and

to the Unit

requirements?
those

level, correctly

in the

unit

wired,

and

• Do the outdoor fan and the indoor fan turn free without
rubbing?
Are both fans tight on their shafts?
• Has the indoor blower speed tap been determined
andthe
proper speed set? See the Unit Wiring Diagram,Figures
5
and 6.
• Has all work been done in accordance
local and national codes?

to the applicable

• Are all cover and access panels in place to prevent
and to protect against safety hazards?
• Have all tools and debris
unit been removed?

Starting

around,

air loss

on top of, and under

the Unit In the Cooling

the

Mode

IMPORTANT: Before starting
the system in the cooling
cycle, turn the thermostat
switch
to "OFF" and close the
unit disconnect
switch.
This procedure
energizes
the
compressor
crankcase
heat (if equipped)
thereby
vaporizing any liquid
HICFC-22 in the crankcase.
This is a
precaution
against
foaming
at start-up
which
could
damage
the compressor.
Allow the heat to operate
for a
minimum
of eight (8) hours.
The TCH048-060F
units do not have sump heat as shipped.
NOTE: The crankcase
heater
is a field installed
option on
some models.
NOTE:
See the section on "Sequence
of Operation"
description
of the cooling operating
sequence.
• To start the unit in the cooling mode,
system switch to COOL.
Move the thermostat
COOL indicator

for a

set the thermostat
to a setting

below

Start-Up

Start-Up

room temperature.
The outdoor fan motor, compressor,
evaporator
fan motor will operate automatically.

Operating

and

Starting

Pressures

After the unit has operated in the cooling mode for a short time,
install pressure gauges on the gauge ports of the discharge and
suction line valves. Check the suction and discharge pressures
and compare them to the normal operating pressures
provided in
the unit's SERVICE
FACTS.

Cooling

Mode

NOTE: See the section on "Sequence of Operation"
tion of the heating operating
sequence.

for a descrip-

• Check to make sure that all grilles and registers are
open and all unit access doors are closed before start-up.
• To start the unit in the heating mode, set the thermo-stat
system switch to HEAT.
Move the thermostat
HEAT indicator to a setting above room temperature
and place the fan switch in the AUTO or ON positions.
The indoor fan motor will operate automatically.

Voltage
With the compressor operating, check the line voltage at the
The voltage should be within the range shown on the
nameplate.
If low voltage is encountered,
check the size
length of the supply line from the main disconnect to the
The line may be undersized
for the length of the run.

the Unit in the Heating

unit.
unit
and
unit.

• The thermostat
must provide a "G" signal for fan operation.
If using an auto changeover
thermostat,
see Figures 5 and 6
for the appropriate
connections.

Shut Down

• Place the system selector switch in the OFF position or reset
the thermostat
at a setting above the room temperature.

Heating

Shut-Down

• Place the system selector switch to the OFF position or place
the heating
selector lever at a setting below the room
temperature.

• Do not de-energize
the main power disconnect except when
the unit is to be serviced.
Power is required to keep
the
compressor crankcase heat (if equipped)
energized and boil
off refrigerant
in the compressor.

TROUBLESHOOTING

CHART

\
\

SYSTEM
REFRIGERANT

FAULTS
CIRCUIT
P

Liquid Pressure Too high
Liquid Pressure Too Low

SP

Suction Pressure Too High

S

Suction Pressure Too Low

SPS

S
SS

PP

S

SP

S

SPS

Liquid Refrigerant floodback (TXV System)

SS
P

Liquid Refrig. floodback (Cap, TubeSystem)
I. D. Coil Frosting

SS

SP

P

Compressor Runs Inadequate or No Cooling

PS

SP

PS

SPS

ELECTRICAL
Compressor & O.D. fan Do Not Start

p

P

SPPP

Compressor Will Not Start But O.D. Fan Runs

PSPPP

O.D. Fan Won't Start

P

P

Compressor Hums But Will Not Start

P

PPPS

Compressor Cycles on IOL

P

I.D.Blower Won't Start

p

P-PRIMARY CAUSES S-SECONDARY CAUSES

S

S

S

P

P

S
P

S

P
SP

S

P

S

S

S

S

S

P
X664590

Page 9

Maintenance
Routine

Maintenance

by Owner

You can do some of the periodic maintenance functions for your TCH unit
yourself. These functions include replacing the disposable or cleaning the
permanent air filters, cleaning the unit's cabinet, cleaning the condenser coil,
and conducting a general inspection of the unit on a regular basis.

WARNING:

TO PREVENT INJURY OR DEATH

DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING
PARTS.
LOCK UNIT DISCONNECT
SWITCH
IN OPEN
POSITION BEFORE SERVICING UNIT.

The following

warning

complies

with State of California

,WARNING:

law, Proposition

65.

This product contains

fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.
PRECAUTIONARY

MEASURES

Air Filters
It is very important to keep the central duct system air filters clean. Be sure
to inspect them at least once each month when the system is in constant
operation. In new construction, check the filters every week for the first
four (4) weeks.
•If you have disposable-type filters, replace them with new filters of
the same type and size. Do not try to clean disposable filters.
•Clean permanent-type filters by washing them with a mild detergent
and water. Make sure that the filters are thoroughly dry before reinstalling them in the unit.
•Replace permanent filters annually if washing fails to clean them or
if they show signs of deterioration. Use the same type and size as was
originally installed.

Outdoor

Coil

Unfiltered air circulated through the unit's outdoor coil can cause the
coil's surface to become clogged with dust, dirt, etc. To clean the coil,
stroke the coil surface with a soft-bristled brush vertically, that is, in the
direction of the fins.

• Avoid breathing fiberglass dust.
• Use a NIOSH approved dust/mist respirator.
• Avoid contact with the skin or eyes. Wear longsleeved, loose-fitting clothing, gloves, and eye
protection.
• Wash clothes separately from other clothing: rinse
washer thoroughly.
Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact

Flush eyes with water to remove dust.
If symptoms persist, seek medical
attention.

•Be sure to keep all vegetation away from the outdoor coil area.

Maintenance Performed by Serviceman
To keep your unit operating as designed, the manufacturer recommends
that a qualified serviceman check over the entire system at least once each
year as well as any other time that you feel that one is needed. Your
serviceman should examine and inspect:
•filters (for cleaning or replacement)
•motors and drive system components
•condenser coils (for cleaning)
•safety controls (for mechanical cleaning)
•electrical components and wiring (for possible replacement
and/or connection tightness)
•condensate drain (for cleaning)
In addition, your serviceman should inspect:
•unit duct connections to see that they are physically sound and sealed
to the unit casing
•unit mounting support to see that it is sound
•unit to see that there is no obvious unit deterioration.

Page 10

Skin Contact

-

Wash affected areas gently with soap
and warm water after handling.

Limited
Warranty
Central
Air Conditioner
4TCC3,
TCD, TCH, TCK, TCM,
TCP, THC and TSC (Parts Only)
Models

Less

Than

20 Tons for Residential

Use*

This limited warranty is extended byTrane U.S. Inc., to the original purchaser and to any succeeding owner of the
real property to which the Air Conditioner is originally affixed, and applies to products purchased and retained for use
within the U.S.A. and Canada.
If any part of your Air Conditioner fails because of a manufacturing defect within five years from the date of the original purchase, Warrantor will furnish without charge the required replacement part. Any local transportation, related
service labor, diagnosis calls, refrigerant and related items are not included.
If the sealed motor-compressor fails because of a manufacturing defect within five years from the date of original purchase, Warrantor will furnish without charge the required replacement compressor. Any local transportation, related
service labor, diagnosis calls, refrigerant and related items are not included.
This limited warranty does not cover failure of your Central Air Conditioner if it is damaged while in your possession,
damage caused by unreasonable use of the Central Air Conditioner and/or damage from failure to properly maintain the Central Air Conditioner as set forth in the Use and Care manual (see Proper Maintenance section).
THE LIMITED WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE,
EXPRESS OR IMPLIED,
IN LAW OR IN FACT, INCLUDING BUT NOT SPECIFICALLY LIMITEDTO IMPLIED WARRANTIES
OF
MERCHANTABILITY
AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL
DAMAGES.
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Parts will be provided by our factory organization through an authorized service organization in your area listed in the
yellow pages. If you wish further help or information concerning this limited warranty, contact:
Trane
P.O. Box 9010, Tyler, TX 75711-9010
Attention: Manager, Field Operations Excellence
Or visit our website: www.trane.com/residential
TW- 1002-4707

* This limited warranty is for residential usage of this equipment and not applicable when this equipment is used for a
commercial application. A commercial use is any application where the end purchaser uses the product for other than
personal, family or household purposes.

The limited warranties displayed in this publication and/or on ComfortSite TM
may not accurately reflect the actual limited warranty that shipped with the
product.

26-1000-21

Page

11

Limited
Warranty
Central
Air Conditioner
4TCY4,
TCY, 4TCC3,
4TCX3,
TCD,
TCH, TCK, THC and TSC (Parts Only)
Models

Less

Than

20 Tons

for

Commercial

Use*

This warranty is extended by Trane U.S. Inc., to the original purchaser and to any succeeding owner of the real property to which the Air Conditioner is originally affixed, and applies to products purchased and retained for use within the
U.S.A. and Canada. There is no warranty against corrosion, erosion or deterioration.
If any part of your Air Conditioner fails because of a manufacturing defect within one year from the date of the original
purchase, Warrantor will furnish without charge the required replacement part.
In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through fifth
year from the date of original purchase, Warrantor will furnish without charge the required replacement compressor.
Warrantor's obligations and liabilities under this warranty are limited to furnishing EO.B. Warrantor factory or warehouse replacement parts for Warrantor's products covered under this warranty. Warrantor shall not be obligated to pay
for the cost of lost refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability
shall be limited solely to the purchase price of the equipment under warranty shown to be defective.

THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES
AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW
OR IN FACT, INCLUDING BUT NOT SPECIFICALLY LIMITEDTO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE
LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation
of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives
you specific legal rights, and you may also have other rights which vary from state to state.
Trane
P.O. Box 9010
Tyler, TX 75711-9010
Attention: Manager, Field Operations Excellence
TW-1001-4707
* This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a
residential application. Commercial use is any application where the end purchaser uses the product for other than
personal, family or household purposes.

The limited warranties displayed in this publication and/or on ComfortSite TM
may not accurately reflect the actual limited warranty that shipped with the
product.

Trane
6200 Troup Highway
Tyler,TX 75703
Page 12

26-1000-21



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 12
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Fri Mar 13 04:14:51 2009
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu