TRANE Furnace/Heater, Gas Manual L0903224
User Manual: TRANE TRANE Furnace/Heater, Gas Manual TRANE Furnace/Heater, Gas Owner's Manual, TRANE Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 40
Download | |
Open PDF In Browser | View PDF |
IIIIIIIIIIIIIII IIIIIII IIIII III 1 8- CD1 9 D6- 3 1 Available in French Canadian (FC) i _t'_"ii _ii,! iii"!i_ i,_ii!:':iii ! _ii, i_ !:!:_:,!il ''''_ _iIi i;i Upflow/Horizontal and Downflow/Horizontal Gas-Fired, DirectVent Condensing Furnaces *UX1 *UX1 *UX1 *UX1 *UX1 B040A9241A B060A9241A B060A9361A B080A9241A B080A9421A *UXIC080A9601A *UX1 C100A9361A *UX1 C100A9481A *UXID100A9601A *UXID120A9601A *DX1 B040A9241A *DX1 B060A9361A *DX1 B080A9421A *DXIC100A9481A *DX1 D120A9601A *__First letter may be "A" or "T" ALL phases of this installation must comply with NATIONAL, IMPORTANT -- This Document is customer Please return to service information STATE AND LOCAL CODES property and is to remain with this unit. pack upon completion of work. *UX-1 *DX-1 DOWNFLOW A!R AIR FLOW FLOW UPFLOW o A_ FLOW / UPFLOW/HORIZONTAL \ DOWNFLOW/HORIZONTAL 20% / \ elIID L 0 A341624P06 Installer's Guide SAFETY SECTION The following safety practices and precautions must be followed during the installation, servicing, and operation of this furnace. 1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate. 2. Install this furnace only in a location and position as specified in "Location and Clearances" (page 4), of these instructions. 3. Provide adequate combustion and ventilation air to the furnace space as specified in "Air for Combustion and Ventilation" (pages 8-9), of these instructions. 4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the "Venting" section (starting on page 15), of these instructions. 5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in "Gas Piping" (pages 31-33), of these instructions. 6. Always install the furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace. 7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. 8. A gas-fired furnace for installation in a residential garage must be installed as specified in "Location and Clearances" section (page 4), of these instructions. 9. The furnace may be used for temporary heating of buildings or structures under construction only when the following conditions have been met: a. The furnace venting system must be complete and installed per manufacturers instructions. b. The furnace is controlled only by a room thermostat (no field jumpers). c. The furnace return air duct must be complete and sealed to the furnace and clean air filters d. e. are in place. The furnace input rate and temperature rise must be verified to be within nameplate marking. 100% of the furnace combustion air requirement must come from outside the structure. © 2008 Trane All Rights Reserved f. g. The furnace return air temperature range is between 55 and 80 degrees Fahrenheit. Clean the furnace, duct work, and components upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions. 10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts. CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSIZ223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition. 4. Close fireplace dampers. 5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan. 6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously. 7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149.1 Installation Codes. 8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use. 1 8-CD1 9D6-31 Installer's Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING and CAUTION. a. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. b. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage. FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage. GENERAL INSTALLATION INSTRUCTIONS The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation. It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at altitudes above 2000 ft., remember the gas input may need to be reduced (See High Altitude Installation). Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the delivering agency. Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as CATEGORY IV furnaces in accordance with latest edition of ANSI Z21.47 • CAN/CGA 2.3 standards. 18-CD19D6-31 Guide Contents INSTALLATION INSTRUCTIONS General Installation Instructions Location and Clearances Outline Drawings Upflow Installation Downflow Installation Horizontal Installation Air For Combustion and Ventilation Duct Connections Return Air Filters General Venting Instructions Venting Material VentingTables Horizontal Venting VentingThrough The Wall VentingThrough The Roof Downward Venting Venting Through a Masonry Chimney Condensate Drain Instructions Electrical Connections Field Wiring Diagrams Gas Piping Combustion Input Checks Start Up and Adjustment Preliminary Inspections Lighting Instructions Sequence Of Operation Control And Safety Switch Adjustments Airflow Adjustment Abnormal Conditions IFC Error Flash Code Category IV furnaces operate with positive vent static pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Category IV Direct Vent furnaces are approved for installation in Manufactured/ Mobile housing when used with BAYMFGH100A. 3 Installer's Guide LOCATION AND CLEARANCES To prevent shortening its service life, the furnace should not be used as a "Construction Heater" during the finishing phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger. Do NOT install the furnace in a corrosive or contaminated atmosphere. EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK. NOTE: The manufacturer of your furnace does NOTtest any detectors and makes no representations regarding any brand or type of detector. The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements: 1. Is the location selected as near the vent and as centralized for heat distribution as practical? 2. Do all clearances between the furnace and enclosure equal or exceed Table 1. the minimums shown in the 3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door or panel must permit removal of the largest component. 4. Are there at least 3 inches of clearance between the 5. 6. 7. 8. furnace front panel and any closed panel or door provided? Are the vent pipe and combustion air inlet pipe within vent table lengths? Will the pipes remain unobstructed? Allow sufficient height in supply plenum above or below the furnace to provide for cooling coil installation if the cooling coil is not installed at the time of this furnace installation. A furnace shall be installed so electrical components are protected from water. If the furnace is installed in a residential garage, it must be installed so that the burners and the ignition source are located not less than 18 inches (46 cm) above the floor and the furnace must be located or protected to avoid physical damage from vehicles. IMPORTANT: The furnace must be installed level The only allowable variation would be slightly to the left and/or forward in upflow installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage. 4 18-CD19D6-31 Installer's Guide > co i co © E £ o o _lsl=, _2_ ...... i=_ = = = < _ _ a 3 zs_ ........ LL _8 3 £S ss_ = £ s _\\\\\\\\\\\\\ 2 £ V ' rr_z a ---LU b i Q V _1< T < < < _ < < < < < < < < _ ÷÷÷÷÷÷÷÷÷÷÷÷ < < < < < < ,< ,< _ < < < < < < < , ÷÷÷÷÷÷÷ < < ,< ,< < _ < < < < ,÷÷÷÷÷ ®® I,-LUrr" i 18-CD19D6-31 5 Installer's Guide > ucO © [°ij..... L< L_ E £ ii Z= _ ??,.._ rr r'l LU ZJ = = b _ = s ,_-- o, _-c\ o_ 0 r,l T I-iii "-I,,-,- rr" m 0 L /'// [ _> ra 6 _1 A _ 18-CD19D6-31 Installer's Guide UPFLOW INSTALLATION Standoffs and screws (See Figure 1) are included with the eased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the furnace top flanges. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange. ,iii_liiiiiiii_iii!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!;iiii The coil is always placed downstream of the furnace air- flow. STANDOFFS (4) DRILL SCREWS J (4) FOR VERTICAL INSTALLATIONS: HORIZONTAL INSTALLATION The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% gas furnace. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line). Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the furnace and TXC cased tion. See Figure 4. IMPORTANT: coil in the horizontal posi- The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the 2/4TXC coil Installer's Guide for more details. (BOTH SIDES) STANDOFFS (BOTH DOWNFLOW SIDES) INSTALLATIONS Do NOT install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required. Required floor opening: SUB-BASE FLANGE _ (BENT CABINET_SIDE _ CABINET PLENUM SULATION DUCT ZLOOCOMBL'STFBI,N _ SUB*BASE TABLE 1 RETURN DUCT WIDTH FLOOR OPENING "A.... B .... PLENUM OPENING C .... D" 17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8" 21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8" 24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8" 18-CD19D6-31 ONLY SIDE SUBBASE CROSS SECTION CABINET WIDTH FOR DOWNFLOW IN HORIZONTAL UP) _ IN COIL CONNECTION DOWNFLOW FLANGE UP) SUB-BASE CASED BRACKET FURNACE SUB-BASE (BENT The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the furnace bottom channel (for downflow/ horizontal furnace). Use four of the screws provided to secure the bracket. The upflow furnace, converted to horizontal, aligns and attaches the TXC coil as in Figure 1. However, the coil requires additional support. The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Figure 4 & Clearance Table). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or framing. 7 Installer's Guide © Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1 --CAN/CGA B149.1 or applicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation. OUTSIDE AIR IS RECOMMENDED ,i UPFLOW/ HORIZONTAL SHOWN The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture. The furnace must be supported at both ends and the middle when installed horizontally. The furnace must also be elevated a minimum of 6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position. The horizontal furnace may also be suspended from the joists using 3/8" all-thread rods with pieces of angle iron underneath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The angle iron needs to be at least 32" in length to allow for access to service panels. @ 50 CU. FT. OR MORE PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED FiACE HE;R WATER I _DRYER CLOTHES UNCONFINED AIR FOR COMBUSTION AND VENTILATION If these furnaces are installed in a nondirect vent capacity then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be kept free of obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe operation of the furnace. Keep this in mind should you choose to remodel or change the area which contains your furnace. Furnaces must have a free flow of air for proper performance. 8 The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require the use of outside air for combustion. The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical exposures: * Commercial buildings * Buildings with indoor pools * Furnaces installed in "confined" laundry rooms * Furnaces installed in "confined" hobby or craft rooms * Furnaces installed near chemical storage areas. Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combustion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perehloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials Furnace locations may be in a "confined space" or an "unconfined space". Unconfined space is defined in Figure 5. These spaces may have adequate air by infiltration to provide air for combustion and ventilation. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air to be provided as described for confined space. Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/hr input from all equipment installed. Air for combustion and ventilation requirements can be supplied from inside the building as in Figure 8 or from the outdoors, as in Figure 9. 18-CD1 9D6-31 Installer's _F AREA SPACE IN SQUARE FEET OR MINIMUM UNCONFINED INSTALLATIONS FURNACE MAXIMUM BTUH INPUT RATING WITH 8 FT. CEILING MINIMUM AREA IN SQUARE FEET OF UNCONFINED SPACE 60,000 80,000 100,000 120,000 375 500 625 875 ,, -I CONFINED SPACE LESS THAN 50 CU. FT. PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED ® CONFINED AIR FROM I Furnace Maximum BTUH/INPUT Rating 60,000 80,000 100,000 120,000 Air From Inside 1oo 1oo 1oo 120 SPACE INSIDE BUILDING SPACE PERMANENT OPENINGS _J ® CONFINED AIR FROM 1. All air from inside the building as in Figure 8: The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refer to Table 2 for minimum open areas requirements. 2. All air from outdoors as in Figure 9: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 2, for minimum open areas requirements. TABLE 2 MINIMUM FREE AREA IN SQUARE INCHES EACH OPENING FURNACE ONLY) SPACE OUTDOORS CONFINED SPACE L _///////////////////////L OUTLET l OUTDOOR AIR DUCTS INLET 1 _/z'/////////////J///////z CONFINED SPACE AIR FROM VENTILATED ATTIC/CRAWL SPACE TO OUTDOORS CONFINEDSPACE ALTERNATE INLET AIR Air From Outside CONFINED Vertical Duct 15 20 25 30 Horizontal Duct SPACE AIR FROM VENTILATED ATTIC 30 40 50 60 •"_ SPACECONFINED 18-CD19D6-31 Guide OUTLET lAIR INLET AIR DUCT 9 Installer's Guide DUCT CONNECTIONS Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable. Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat exchanger. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position. On any job, flexible connections of nonflammable material may be used for return air and discharge connections to prevent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly installed, amplify the slightest vibration to the annoyance level. When the furnace is located in a utility room adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the installation of air return remote from the living area (i.e. central hall). When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and terminating outside the space containing the furnace. RETURN AIR DUCT SYSTEMS Where there is no complete the return connection must return duct system, be run full size from the furnace to a location outside the utility room, basement, attic, or crawl space. DoNor install return air through the back of the furnace cabinet Do Not install return air through the side of the furnace cabinet on horizontal applications. 10 NOTE: Minimum return air temperature is 55 ° F. All return air duct systems tion of return air filters. should provide for installa- 1. Set the furnace in place. 2. For upflow side return installations, remove the insulation around the opening in the blower compartment. 3. The side panels of the upflow furnace include locating notches that are used as guides for cutting an opening for return air, refer to Figure 10 and the outline drawing on page 4 for duct connection dimensions for various furnaces. NOTE: On upflow 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom. 4. If a 3/4" flange is to be used for attaching the air inlet duct, add to cut where indicated by dotted lines in Figure 10. Cut corners diagonally and bend outward to form flange. 5. If flanges are not required, and a filter frame is installed, cut between locating notches (See Figure 10). 6. The bottom panel of the upflow furnace must be removed for bottom return air. Lay the furnace on its back. Remove the two 1/4" hex screws securing the bottom front channel to the cabinet. Lower the front edge of the bottom front channel and pull forward to remove the channel. The bottom return air panel will now easily slide out of the cabinet. Reinstall the bottom front channel for upflow bottom return installations. 7. Use the filter retainer on side or bottom if filter is to be used within the furnace cabinet on upflow only installations. 8. The horizontal installation of the upflow furnace requires an external filter section. Filter kits are available for horizontal applications. 9. Connect duct work to furnace. See Outline Drawing for supply and return duet size and location. Flexible duet connectors are recommended to connect both supply and return air duets to the furnace. If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are removable. 18-CD1 9D6-31 Installer's Guide RETURN AIR FILTERS (Filters not supplied with unit) TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS These furnaces require high velocity type air filters. The filters may be located within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM or SIDE (left side or right side) return air inlet. TABLE 3 MODELS NUMBERS CABINET WIDTH *UXl B040A9241A *UXl B060A9241A *UX1B060A9361A *UXl B080A9241A *UXl B080A9421A 17-1/2" *UXlC080A9601A *UXlC100A9361A *UXlC100A9481A 21" *UXl D100A9601A *UX1D120A9601A 24-1/2" FILTER QTY & SIZE 1 - 17"X 25"X 1" 1 - 20" X 25" X 1" 1 -24"X 25"X 1" *First letter may be "A" or "T" *** NOTE - On 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require filters on both sides; OR 1 side and the bottom; OR just the bottom. Blower Door Hinge and Bottom Filter Rack Installation FILTER RACK NOTE: On upflow 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom. The upflow furnace blower door has a hinge at the bottom which allows the door to tilt forward for filter replacement without ® LOCATING PROVIDED FOR NOTCHES SIDE RETURN CUTOUT the door being removed AUTOMATIC ADJUSTMENT (See Figure UPFLOW FURNACE ONLY *"_ b RETAINING PIN (Both Sides) Optional Filter Rack Accessory Kit _. *SEE OUTLINEDRAWING _ BA YRACK960A I///FORCUT SIDE OUT FILTER OPTIONAL BOTTOM FILTER RACK INSTALLATION With the filter removed, the filter rack is compressed and then inserted into the bottom of the furnace. The of Furnace 11). The optional furnace filter in the bottom or side configuration can be removed by simply turning the two latches on the blower door and tilting the door forward. The filter rails are spring loaded for automatic adjustment to allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the required width needed for bottom or side return (See Figure 12). 18-CD19D6-31 -'_ RAILS retaining screw/ pin on each side inserts into engagement holes at the bottom of the furnace cabinet side. OPTIONAL FILTER RACK INSTALLATION FOR SIDE RETURN AIR ON UPFLOW FURNACES (Left or Right) NOTE: The optional filter rack installation right side return on the following A9601. is not allowed for model: *UXICO80- 11 Installer's Guide ® ® BOTTOM ENGAGEMENT Filter Rack Retaining Screw/Pin Furnace Cabinet Side Engagement For Filter Installation Bottom Filter Rack / ) Hole Rack With t Return Bottom Panel ® %..., ENGAGEMENT HOLE DETAIL If side should a. b. c. air return is desired, the following instructions be used: Open or remove the blower door. Leave the bottom panel in place. After the side cutout is made following the directions in the "Return Air Duct Connections" section on pages 8 and 9, compress the optional illter rack and reinstall in the side of the furnace. Confirm that the upper retaining pin!screw locks into the engagement hole in the blower deck and the lower pin/screw rests against the side of the bottom panel. See Figures 14 - 18. d. Install the optional furnace filter on the side insetting the chamfer end first. RETURN AIR FILTERS FOR UPFLOW FURNACE IN HORIZONTAL CONFIGURATION When the Upflow Furnace is installed in the horizontal configuration, the return air filters must be installed exterior to the cabinet. Remote filter grilles may be used for homeowner convenience or the filters may be installed in the duct work upstream of the furnace. See Figure 20. Filter Furnace Cabinet Side Rack Hole For Filter Rack installation With Side Return BLOWER DECK (Typical both sides and blower deck) (_ Engagement Furnace Blower Deck _./ Furnace Cabinet-,,,]_ Side _W___r _k _Filter Retaining Screw/Pin Rack Assembly SIDE CUTOUT RETAINING (B° PIN "_ 1II IU f/ _/ FILTER RACK BOTTOM PANEL INSTALLED RAILS Typical Upflow Left Side Return Filter Rack Installation Filter Rack Retaining Screw/Pin Engagement Hole For Filter Rack installation With Bottom Return 12 18-CD1 9D6-31 Installer's Guide O TYPICAL RETURN AIR FILTER INSTALLATION IN UPFLOW MODEL IN HORIZONTAL POSITION ALTERNATE UPFLOW FILTER CLIP/ BRACKET INSTALLATION 1. Determine the location to be used. Typical Upflow Right Side Return Filter Rack Installation ® The furnace cabinet has dimples for location of the alternate furnace clips (Side return only). Pre-drill clearance holes with a 3/16" drill. Bottom return holes are pre-drilled. 2. Install the clips in front and rear of the desired location using the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet. CHAMFER END OF FILTER INTO RACK GOES FILTER FIRST BLOWER DOOR/HINGE REMOVAL If clearance or other problems create a problem in using the tilting door, the blower door hinge may be removed without creating any problems with the seal of the furnace. To remove the blower door, tilt the door forward 2 to 3 inches and pull up. To remove the tilt feature, simply remove the lower hinge as shown in Figure 21. The bottom of the blower door will catch in the bottom ment. of the 18-CD19D6-31 furnace front channel for door replace- Door Hinge Removed INSTALLING THE FILTER The optional filter may need to be cut to fit the unit depending on the location of the return air filter. A score line and the words "CUT HERE" are located on the end of the filter. If your application requires cutting the filter, do so as indicted by the score mark. 13 Installer's Guide @ TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER INSTALLATIONS Two high velocity type air filters are required for each downflow furnace. Downflow furnace filters must be located outside the furnace cabinet. Typical installations are shown in Figure 23. Tables 5 and 6 provide information for installation of the filter retaining brackets shipped with downflow furnaces. / / TABLE 4 MODELS NUMBERS ALTERNATE FILTER CLIPS LOCATION iiiiiiiiiiii *DX1 B040A9241A *DX1B060A9361A *DX1 B080A9421A RETURN AIR UNIT SIZE BOTTOM SIDE 17-1/2" DO NOT CUT DO NOT CUT 21" DO NOT CUT CUT ON LINE 24-1/2" DO NOT CUT CUT ON LINE CABINET WIDTH FILTER QTY & SIZE 17-1/2" 2 - 14"X 20"X 1" *DX1C100A9481A 21" 2 - 16"X 20"X 1" *DX1D120A9601A 24-1/2" 2 - 16"X 20"X 1" *First letter may be "A" or "T" TABLE 5 LOCATING FILTER RETAINER BRACKETS IN DUCTWORK DIMENSION "A .... DIMENSION B" FILTER BRACKET LOCATION* 16-1/4" 15" 14" 14-3/8" 19-3/4" 19-1/2" 14" 13-1/8" 23-1/4" 22" 14" 13-5/8" CABINET WIDTH RETURN DUCT WIDTH 17-1/2" 21" 24-1/2" * LOCATION DIMENSION IS FROM END OF DUCT AGAINST SCREW HOLES FOR THE BRACKET. THE FURNACE TO THE p 0 Airflow Joow.F,OW, DOWNFLOW HORIZONTAL TABLE 6 MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR UPFLOW/HORIZONTAL AND DOWNFLOW/HORIZONTAL FURNACES UNIT LOCATION FURNACE SURFACE HORIZONTAL CLOSET HORIZONTAL ALCOVE / ATTIC SIDES 0" 1" 0" BACK 0" 3" 6" TOP 1" 1" 1" FRONT 3" 3" 18" VENT 0" 0" 0" NOTE: CLEARANCE 14 VERTICAL CLOSET REQUIRED AT TOP OF PLENUM IS 1" 18-CD19D6-31 Installer's GENERAL VENTING THIS FURNACE MUST BE VENTED TO THE OUTDOORS. THESE FURNACES ARE INDUCED DRAFT VENTED AND MUST NOT BE CONNECTED TO ANY VENT SERVING ANOTHER APPLIANCE. PLEASE NOTE THAT THESE FURNACES USE POSITIVE-PRESSURE VENT SYSTEMS. Proper venting is essential to obtain maximum efficiency from a condensing furnace. Proper installation of the vent system is necessary to assure drainage of the condensate and prevent deterioration of the vent system. American Gas Association has certified the design of condensing furnaces for a minimum of 0" clearance from combustible materials with a single wall plastic vent pipe. The recommended system is assembled from 2", 2-1/2", or 3" plastic pipe and fittings (See Table 7, page 14). Where the system is routed to the outdoors through an existing masonry chimney containing flue products from another gas appliance, or where required by local codes, then 3" venting of Type 29-4C stainless steel must be used in place of PVC material. These furnaces have been classified as CATEGORY IV furnaces in accordance with the latest edition of ANSI Z21.47 • CAN/ CGA-2.3 Standards. Category IV furnaces operate with positive vent pressure and with a vent gas temperature less than 140°F above the dewpoint. These conditions require special venting systerns, which must be gas tight and water tight. NOTE: When an existing furnace is removed from a venting system serving other gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. IMPORTANT: These furnaces may be installed as Direct Vent (sealed combustion) or as Nondirect vent (single pipe). The furnaces are shipped DIRECT VENT with sealed combustion. For DIRECT VENT APPLICATION: The furnaces must be vented to the exterior of the house and combustion air MUST come through the inlet air pipe FROM OUTSIDE AIR. For NONDIRECT VENT APPLICATION: The furnace shall be vented to the exterior of the house, but combustion air may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION) The following steps shall be followed with each appliance remaining connected to the common venting systern placed in operation, while the other appliances remaining connected to the common venting system are not in operation. 1. Seal any unused openings in the common venting system. 2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition. 3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common _iiiliiiiXi__ venting system are located and other spaces of the .................. building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan, close fireplace dampers. 4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance will operate continuously. 5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe. 6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return door, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use. If improper venting is observed during any of the above tests, the remaining common venting system must be corrected. Correction of the remaining common vent system should be done by referring to the latest edition of the National Fuel Gas Code (ANSI Z223.1)° CAN/ CGAB149.1 Installation Codes or "Exhibit J" of ANSI Z21.47 ° CAN/CGA-2.3 Standards. The following are general steps to be used to correct or resize a remaining vent system when a furnace which may not be common vented is removed from the system: a. Determine the Btu per hour input of all remaining appliances attached to the venting system. b. Determine the diameter, rise, and lateral of the existing venting system, as well as quantity and type of bends. c. Use the appropriate tables in the latest edition of the National Fuel Gas Code (ANSI Z223.1 ° CAN/CGA B149.1 Installation Codes or "Exhibit J" of ANSI Z21.47 ° CAN/ CGA-2.3 Standards. "Exhibit J" includes examples typical venting systems. 18-CD19D6-31 Guide and drawings of 15 Installer's Guide PVC VENT FITTING MATERIAL These fittings are available from Distributors. your Gas 2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and outside of pipe. DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING CEMENT. Furnace Straight Pipe Sections, Couplings, 45 ° Elbows, 60 ° Elbows, 90 ° Elbows, Vent or Sanitary Tee, or other necessary fittings may be 2", 2½", 3", or 4" diameter. The allowable materials are shown in Table 7. VENT FITTING MATERIAL - PLASTIC 3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting movement until it bottoms out. 4. Hold the pipe in the fitting for 30 seconds to prevent tapered socket from pushing the pipe out of the fitting. 5. Wipe all excess cement from the joint with a rag. Allow 15 minutes before handling. Cure time varies according to fit, temperature and humidity. Gas and liquid tight single wall vent fittings, designed for resistance to corrosive flue condensate, MUST be used throughout. Listed in Table 8 & 9 are 2", 2½", 3", and 4" size fittings that meet these requirements. The materials listed are various grades of PVC and ABS plastic. PIPE JOINTS: All joints must be fastened and sealed to prevent escape of combustion products into the building. IMPORTANT: NOTE: It is recommended that the first joints from the furnace be connected and sealed with high temperature RTV. This will enable the pipes to be removed later without cutting. Be sure to properly support these joints. BONDING OF PVC Commercially available solvent cement must be used to join the pipe and fittings. Follow instructions on the container carefully. Procedure for Cementing Joints: 1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint area of all dirt, grease, moisture or chips. Products installed in Canada must use vent systems that are certified to the Standard for Type BH Gas Venting Systems (ULC $636) for Class II-A venting systems (up to 65°C). Components of the vent system must not be interchanged with other vent systems or unlisted pipe or fittings. Plastic components, specified primers, and glues must be from a single system manufacturer and not intermixed with other system manufacturer's vent system parts. In addition, the first three feet of the vent pipe must be visible for inspection. TABLE 7 PLASTIC PIPE DESIGNATIONS PVC ASTM STANDARD F891 D2665 D1785 D2241 PIPE TYPE CELLULAR DWV ALLOWABLE CORE PIPE SCH 40, 80, 120 SDR TEMPERATURE "158 SERIES MARKING ASTM F891 *'158 ASTM D2665 *'158 ASTM D1785 *'158 ASTM D2241 CPVC ASTM STANDARD D2846 F441 F442 PIPE TYPE CPVC SCH SDR ALLOWABLE 41 TEMPERATURE *'212 MARKING ASTM D2846 40, 80 *'212 ASTM F441 SERIES *'212 ASTM F442 ABS ASTM STANDARD PIPE TYPE D2661 SCH 40 DWV F628 * ** - Allowable - Allowable *** - Allowable 16 SCH 40 DWV CELLULAR ALLOWABLE TEMPERATURE **'180 CORE **'180 MARKING ASTM D2661 ASTM temperatures temperatures based on classifications based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)] covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)] temperatures based on classifications covered in ASTM D3965 [Deflection F628 Temps Under Load (264 PSI)] 18-CD19D6-31 Installer's @ Connection of the vent pipe to the vent collar should also be accomplished using RTV type sealant. This type sealant provides a connection which remains flexible and can be separated in the future if service needs require the removal of the vent pipe for service or dearance. VENT AND INLET AIR CONNECTIONS Seal VENT with RTV PIPE sealant NOTE: To ensure proper operation at the vent lengths indicated, the combustion air inlet and vent terminals should be in the same pressure zone. Terminating the vent and inlet in different pressure zones will change the maximum vent lengths and may cause nuisance tripping of the pressure switch(es). The amount of change can not be predicted. The selection of the inlet and outlet terminal locations are the responsibility of the designer/installer, ff the installer chooses separate pressure zones for the terminals, the combustion air inlet termination must be in the higher (more positive) pressure zone. Front of Furnace Seal INLET AIR PIPE with RTV sealant NOTE: Follow venting cement. instructions carefully when Guide using PVC IMPORTANT: All joints must be water tight. Flue condensate is somewhat acidic, and leaks can cause equipment damage. Connection of the pipe and collar of the combustion air inlet should just be a friction fit. It is recommended that the inlet air joint be sealed with RTV type sealant to allow the joint to be separated for possible future service. The inlet and vent pipes must be properly supported throughout the entire length. UPFLOW/HORIZONTAL VENTING TABLE TABLE 8 MAXIMUM VENT LENGTH: DIRECT VENT (2 PIPE SYSTEM) MAXIMUM TOTAL EQUIVALENT FEET FOR VENT AND INLET AIR PIPES (See Notes) 2" PIPE & FITTINGS 2-1/2" PIPE & FITTINGS *UXIB040A9241A 60 80 100 130 *UXIB060A9241A 60 80 100 130 *UXIB060A9361A 60 80 100 *UXIB080A9241A 50 80 *UXIB080A9421A 50 *UX1C080A9601A 2" PIPE & FITTINGS TOTAL 3" PIPE & FITTINGS 50 80 80 130 50 80 80 130 130 50 80 80 130 100 130 40 80 80 130 80 100 130 40 80 80 130 NOT ALLOWED 60 100 130 NOT ALLOWED 60 80 130 *UX1C100A9361A NOT ALLOWED 40 100 130 NOT ALLOWED 40 80 130 *UX1C100A9481A NOT ALLOWED 40 100 130 NOT ALLOWED 40 80 130 *UXID100A9601A NOT ALLOWED 40 100 130 NOT ALLOWED 40 80 130 *UXID120A9601A NOT ALLOWED 15 60 130 NOT ALLOWED 25 70 130 NOTES: * - First letter may be "A" or "T" 1. The INLET AIR of one pipe systems require the installation horizontal or vertical straight pipe section connected before 2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH If different inlet and vent pipe sizes are used, the vent pipe The inlet pipe can be of a larger diameter, but never smaller 3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! 4" PIPE & FITTINGS -MAXIMUM 2-1/2" PIPE & FITTINGS MODEL 3" PIPE & FITTINGS NONDIRECT VENT (1 PiPE SYSTEM) EQUIVALENT FEET FOR VENT PIPE ONLY (See Notes) of a 90 ° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot or after the elbow. OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). must adhere te the maximum length limit shown in the table above (See Note 7 below for exception). than the vent pipe. THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes in two pipe systems). 4. One standard radius 90 ° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90 ° elbow is equivalent to 10' equivalent to 6' of 3" pipe. One SHORT/LONG radius 90 ° elbow is equivalent to 71/2' of 21/2 pipe, & 5' of 2" pipe. 5. The termination tee or bend must be included in the total number of elbows. If the BAYVENT100 termination kit There is zero equivalent length for the BAYVENT200. 6. Pipe adapters are field supplied. 7.4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length 18-CD19D6-31 4" PIPE & FITTINGS of 3" pipe and one LONG radius elbow is Two 45 ° elbows equal one 90°elbow. is used, the equivalent length of pipe is 5 feet. restriction. 17 Installer's Guide DOWNFLOW/HORIZONTAL VENTING TABLE TABLE 9 MAXIMUM VENT LENGTH: DIRECT VENT (2 PIPE SYSTEM)MAXIMUM TOTAL EQUIVALENT FEET FOR VENT AND INLET AIR PIPES (See Notes) 2" PIPE & FITTINGS MODEL 2-1/2" PIPE & FITTINGS 3" PIPE & FITTINGS NONDIRECT VENT (1 PIPE SYSTEM)MAXIMUM TOTAL EQUIVALENT FEET FOR VENT PIPE ONLY (See Notes) 4" PIPE & FITTINGS 2" PIPE & FITTINGS 2-1/2" PIPE & FITTINGS 3" PIPE & FITTINGS 4" PIPE & FITTINGS *DX1 B040A9241A 60 80 100 130 50 80 80 130 *DXl B060A9361A 50 80 100 130 50 80 80 130 *DXl B080A9421A 45 80 100 130 40 80 80 130 *DXlC100A9481A NOT ALLOWED 80 100 130 NOT ALLOWED 80 80 130 *DX1D120A9601A NOT ALLOWED 15 60 130 NOT ALLOWED 25 70 130 NOTES: * - First letter may be "A" or "T" 1. The INLET AIR of one pipe systems require the installation of a 90 ° elbow (to prevent dust and debris from falling straight into the furnace) and a 2 foot horizontal or vertical straight pipe section connected before or after the elbow. 2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe. 3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes in two pipe systems). 4. One standard radius 90 ° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90 ° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One SHORT/LONG radius 90 ° elbow is equivalent to 7Y2' of 2Y2" pipe, & 5' of 2" pipe. Two 45 ° elbows equal one 90°elbow. 5. The termination tee or bend must be included in the total number of elbows. If the BAYVENTIO0 termination kit is used, the equivalent length of pipe is 5 feet. There is zero equivalent length for the BAYVENT200. 6. Pipe adapters are field supplied. 7.4" pipe may be reduced to 3" for termination with BAYAIR3OAVENTA or BAYVENT200 without additional length restriction. UPFLOW SINGLE PIPE VENTING FURNACE DOWN FLOW Air Inlet %, I--B--I t- FURNACE A (0-2') or greater B (0-2')or greater A+B = 2' minimum ___ .... = A Air lnle/t _ _ _entu_snldY. ® A = 2' minimum _K_ (_ 18 F_ VENTTERMINAL (_) AIR SUPPLY INLET [] AREAWHERETERMINALISNOTPERMITTED 18-CD19D6-31 Installer's Guide Direct Vent Terminal Clearances A= Clearance above grade, veranda, porch, deck, or balcony B= Clearance to window or door that may be opened C= Clearance to permanently Canadian Installations US Installations 12 inches (30 cm) 12 inches (30 cm) 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000 100,000 Btuh (30 kw) Btuh (15 kw) closed window Vertical clearance to ventilated soffit located above the D= terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal E= Clearance to unventilated soffit F= Clearance to outside corner G= Clearance to inside corner H= Clearance to each side of center line extended above meter/regulator assembly I= Clearance to service regulator vent outlet 3 feet (91 cm) with a height 15 feet (4,5 m) above the meter/regulator assembly 3 feet (91 cm) 6 inches (15 cm) for appliances j= Clearance to nenmechanical air supply inlet to building or the combustion air inlet to any other appliance K= Clearance to a mechanical air supply inlet L= Clearance above a paved sidewalk or paved driveway located on public property M= Clearance under veranda, porch, deck, or balcony =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 35 inches (91 cm) for appliances > 100,000 Btuh (30 kw) 6 feet (1,83m) 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw) 3 feet (91 cm) above if within 10 feet (3m) horizontally 7 feet (2,13 m) t "12 inches (30 cm) _: Notes: 1. 2. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code. t. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings. $. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturar's Installation Instructions, Non-Direct Vent Terminal Clearances Canadian A= Clearance above grade, veranda, porch, deck, or balcony B= Clearance to window or door that may be opened C= Clearance to permanently closed window D= Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal E= Clearance to unventilated soffit F= Clearance to outside corner G= Clearance to inside corner H= Clearance to each side of center line extended above meter/regulator I= assembly Clearance to service regulator vent outlet J= Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance K= Clearance to a mechanical air supply inlet L= Clearance above a paved sidewalk or paved driveway located on public property M= Clearance under veranda, porch, deck, or balcony 12 inches Installations (30 US Installations 12 inches (30 cm) cm) 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw) 4 feet (1,2m) below or to the side of opening; 1 foot (0,3m) above opening. 3 feet (91 cm) with a height 15 feet (4,5 m) above the meter/regulator assembly 3 feet (91 cm) 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw) 6 feet (1,83m) 4 feet (1,2 m) below or to side of opening; 1 foot (300 m) above opening 3 feet (91 cm) 7 feet (2.13 m) 1 above if within 7 feet 10 feet (2,13 (3m) horizontally m) "12 inches (30 cm) _: Notes: 1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code. 2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code. t. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings, $. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions. 18-CD19D6-31 19 Installer's Guide ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE 6" "_ i.= ir i MAX 4 POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS HORIZONTAL NOTE: Vent VENTING termination kit BAYAIR3OAVENTA or BAYVENT2OOB may be used instead of the horizontal and vertical termination options shown in the following figures. When the vent pipe is exposed to temperatures below freezing, i.e., when it passes through unheated spaces, etc., the pipe must be insulated with 112 inch (22.7 mm) thick Armaflex-type insulation or equal. If the space is heated sufficiently to prevent freezing, then the insulation would not be required. If domestic water pipes are not protected from freezing then it is assumed the space meets the condition of a heated space. / VENT CAP MAINTAIN 12" (18' FOR CANADA) P, CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER BAYVENT2OOB "" "" _ HORIZONTAL VENTING THROUGH WALL These furnaces may be installed as direct vent (as shipped) or as nondirect vent. Installation must conform to national, state, and local codes. The vent & inlet terminals must be located at least 12" minimum above normally expected snow accumulation level. Avoid areas where staining or condensate drippage may be a problem. Location of the vent/wind terminal should be chosen to meet the requirements of Figure non-direct vent applications. 20 26 for either direct or 18-CD19D6-31 Installer's PITCH - Venting through the wall must maintain 1/4" per foot pitched upward to insure that condensate drains back to the furnace. FLUE GAS DEGRADATION - The moisture content ® Guide COUPLING ( PLASTIC VENTING II IN. MII of the flue gas may have a detrimental effect on some building materials. This can be avoided by using the roof or chimney venting option. When wall venting is used on any surface that can be affected by this moisture, it is recommended that a corrosion resistant shield (24 inches square) be used behind the vent termi- / [OPTIONAL) ( 0 JOIP @ 12" MIN. ABOVE 1" CLEARANCE (AIR SPACE ) H II NORMALLY EXPECTED _.__ _ snowACCUMULATION VENTINGTHROUGH COMBUSTIBLE WALLS Pitch-- 1/4 InchPer Ft. CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE ) ( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE ) PVC WALL MOUNT / ( PLASTIC VENTING ) 14 6 IN. MIN. BAYAIR30AVENTA (Sidewall) FLANGE (OPTIONAL) APPROVED / TERMINATION m nal. This shield can be wood, plastic, sheet metal, etc. Also, silicone caulk all cracks, seams and joints within 3 feet of the vent terminal. COMBUSTIBLE MATERIAL WALL A minimum clearance of 1" to combustible materials must be maintained when using single wall stainless steel venting. See Figure 30 above. Shield material to be a minimum of 24 gauge stainless or aluminized sheet metal. Minimum dimensions are 12"x12". Shield must be fastened to both inside and outside of wall. Use screws or anchor type fasteners to the outside or inside wall surfaces. NONCOMBUSTIBLE MATERIAL WALL suited The hole through the wall must be large enough to maintain pitch of vent and properly seal. Use cement mortar seal on inside and outside of wall. See Figure 12" MIN. ABOVE NORMALLY EXPECTED INSIDE & I,_ SNOW ACCUMULATION OUTSIDE VENTING THROUGH NON-COMBUSTIBLE WALLS Pitch- 114InchPerFt. @ SUPPORT HORIZONTAL PIPE EVERY 3' 0" WITH THE FIRST SUPPORT AS CLOSE TO THE FURNACE AS POSSIBLE, INDUCED DRAFT BLOWER, HOUSING, AND FURNACE MUST NOT SUPPORT THE WEIGHT OF THE FLUE PIPE, :IRST lACE ;T o_" 31. JE PIPE, .,'F.>---,o,a,r.... n.... coupu_a pL_srlc w_r5 Tc 40" UPFLOVV OR DOtNNFLOW " FURNACE HORIZONIAL ANDVERIICAL 18-CD19D6-31 21 Installer's Guide @ SEE VENTING NOTE: VENT AND INLET MUST BE SUPPORTED AT A MAXIMUM OF 3' INTERVALS TABLE STRAPS OR OTHER SUITABLE SUPPORTS AT MAXIMUM OF 3'-0" INTERVALS USE ONLY APPROVED TERMINATIO_ COMBUSTION AIR INLET 1 40" UPFLOW DOWNFLOW n _X OR MODELS FIRST UPWARD SUPPORT PITCH --SHOULD 1/4" PERBEFOOT AS CLOSE TO FURNACE CONNECTION AS POSSIBLE. NOTE: ANY THROUGH MUST FITTINGS OUTSIDE WALL PASSING AN UNHEATED SPACE BE INSULATED. 45° ELBOW TEE OUTSIDE WALL STUB CUT AT 45 _ANGLE STRAP AIR COMBUSTION (FIELD VENT SUPPLIED) x RAIN CAP _/ T COMBUSTION AIR BA YAIR3OAVENTA 22 (FIELD 1_ BA YVENT2OOB WALL CAVITIES 18-CD19D6-31 Installer's DOWNWARD VENTING @ Furnace may be in vertical or horizontalconfiguration. f f DOWNWARD VENT LENGTH IS LIMITED TO A MAXIMUM OF 15 EQUIVALENT FEET. 40 Inch Guide DIRECTION OF STAINLESS STEEL FITTING All stainless steel fitting must be installed with male end towards the furnace. All horizontal stainless steel sections must be positioned with the seam on top. All long horizontal sections must be supported to prevent sagging. ® __ Upflow or Downflow Furnace 24" MAX. Slope 1/4" per ft. t_ VENT_N_ _ 12' ± l' __N 9"r_,.. MAINIAIRED ABOVE HIGHEST -INCH CL_a'4ANCE MuST BE SNOW LEVEL _12 ANnCIPATED 24 BE 12" ± l" VENTING THROUGH THE ROOF VENTING ROUTED THROUGH A MASONRY CHIMNEY VENT FITTING MATERIAL - STAINLESS STEEL Gas and liquid tight single wall metal vent fitting, designed for resistance to corrosive flue condensate such as Type 29-4C MUST be used throughout. These fittings and fitting accessories are to be supplied locally. I_OOF, ,J ® VENT MAINTAIN 12 IN. 18 IN. FOR CANADA) ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN, ABOVE ROOF. When penetrating roof with a 2" PVC vent pipe, a 2" electrical conduit flashing may be used for a weather tight seal. Lubricate flexible seal on flashing before PVC pipe is pushed through the seal. (Field Supplied) NOTE: No vent cap as shown in Figure 35 is the preferred method for vertical vent termination in extremely cold climates. In extreme climate conditions, insulate the exposed pipe above the roof line with Armaflex type insulation. ABOVE / COMBUSTION All horizontal pipes must be supported at a maximum of 3 foot intervals NOTES: A) Condensate trap for vent pipe must be a minimum of 6 inches in height. B) Condensate trap for vent and inlet pipe must be connected into a condensate drain pump; an open or vented drain; or it can be connected to the outlet hose of the furnace's condensate trap. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants. C) The condensate trap should be primed at initial start up prior to heating season operation. INCHES DISTANCE FROM TOP OF VENT TO BO]TOM OF AIR INLET MUST 6" Min, BAYAIR30AVENTA ® MAINTAIN VENT REMOVE RIBS 12 IN, (18 IN. FOR CANADA) MINIMUM CLEARANCE 4 FROM CAP COMBUSTION AIR I ANTICIPATED SNOW LEVEL. MAXIMUM OF ABOVE HIGHEST 24 IN. ABOVE ROOF ROOFBOOT )) (FIELD SUPPLIED) ELBOW (FIELD SUPPLIED) COMBUSTION 18-CD19D6-31 23 Installer's ® Guide SEAL BETWEEN FLANGE, PIPE, COUPLING AND METAL PANEL, WITH HI TEMP RTV SILICONE SEALANT SEAL BETWEEN FLANGE, PIPE, COUPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT [ J SUPPORT FLANGE _='-_,,.,= ,_RESTOP) FLOOR _ | ........... FLANGE • " FLUE PIPE SUPPORT __ CLEARANCE (0" ACCEPTABLE FOR PVC VENT PIPE ) (1 "ACCEPTABLE FOR TYPE 29-4C STAINLE SS STEEL VENT PIPE ) VENTING THROUGH FLOOR v GALVANIZED FIRESTOP SHOULD BE FABRICATED WITH 3-718" DIA. HOLE FOR SUPPORTFLANGE .... (12 x12 PANEL OR12" CLEARANCE ( 1" ACCEPTABLE (_ TYPE STAINLESS STEEL VENTING USED29-4C THROUGH CHIMNEY THAT VENTS ANOTHER GAS APPLIANCE /I _, ) n CEILING / / (0" ACCEPTABLE FOR PVC VENT PIPE) FOR TYPE 29-4C STAINLESS STEEL VENT PIPE ) VENTING THROUGH CEILING STAINLESSSTEEL VENTCAP (OPTIONAL) SEE CAUTION DIA MIN.) / / PVC PLASTIC VENTING - ONLY THROUGH UNUSED CHIMNEY 6 IN. MIN. STAINLESS STEEL VENTCAP (OPTIONAL)_ SEE CAUTION SUPPORT THE SINGLE WAL STAINLESS STEEL GAS VENTING AND CENTER IT IP THE CHIMNEY OPENING WI' ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER. 6 IN. MIN. FLUE PIPE 3UPLING TO SUPPORT PE FROM ANGLES R OTHER SUITABLE JPPORT METHOD SUPPORT THE SINGLE WALL FLUE PIPE AND CENTER IT IN THE CHIMNEY OPENING WI ANGLES AS SHOWN O ANOTHER EQUlVALEN MANNER. COUPLING AS REQUIRED FLUE PIPE NOTE: HORIZONTAL TO VERTICAL VENTING VENTING NOTE: HORIZONTAL VENTING TO VERTICAL VENTING Do NOT run vent through chimney for wood burning or oil furnaces or incinerators. If remaining free area between single wall flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connected to chimney with separate entry openings. IMPORTANT The single wall flue pipe joints must be sealed. The 90 ° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of masonry chimney. 24 Do NOT run vent through chimney for wood burning or oil furnaces or incinerators or any other gas appliance. IMPORTANTThe single wall flue pipe joints must be sealed. The 90 ° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of masonry chimney. 18-CD19D6-31 Installer's IMPORTANT: The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of through - the - wall vented gas appliances as follows: For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed Guide 4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. This appliance requires a special venting system. If BAYAIR30AVENTA or BAYVENT200B are used, a copy of the installation instructions for the kit shall remain with the appliance or equipment at the completion of installation. The venting system installation instructions can be obtained from the manufacturer by writing to the following address: American Standard, 6200 Troup Highway Tyler, TX 75707 Attention: Manager Inc. of Field Operations Excellence on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed. 2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI!UL 2034 listed and IAS certified. 3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS". 18-CD19D6-31 25 Installer's HORIZONTAL Guide CONDENSATE INSTALLATION (Upflow/Horizontal DRAIN INSTRUCTIONS or Downflow/Horizontal) NOTE: In horizontal venting when the factory supplied "offset" (2X3 reducing coupling) is used for 3" vent pipe installation, make sure the marking "Top" is located on the top side of the pipe. The straight side must be on bottom for proper condensate drainage. This coupling is factory supplied only with the following models: *UC120 & *DC120, *UX120 & *UY120 *UXIO0 & *UYIO0, *UX808C960, and all *DX & *DY models. WHEN THE FACTORY SUPPLIED "OFF-SET" IT IS RECOMMENDEDTHAT A DRAIN PAN BE INSTALLED UNDER THE FURNACETO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH FROM LEAKING CONDENSATE. (2X3 REDUCING COUPLING) IS USED FOR 3" VENT PIPE INSTALLATION, MAKE SURE THE MARKING "TOP" IS LOCATED ON THE TOP SIDE OF THE PIPE. LABEL SAYS "TOP" .... Right side STRAIGHT SIDE MUST BE ON BOTTOM FOR PROPER CONDENSATE DRAINAGE. UPFLOW (VERTICAL) 2"TO 3" COUPLING FACTORY SUPPLIED THE FOLLOWING UC120 & DC120 UX120 ONLY WITH MODELS: & UY120 UXl00 & UY100 UX080C960 ALL DX & DY MODLES UPFLOW VENT HORIZONTAL Use Inducer Drain hose without extension 17" UNITS (Left side only) OUTLET VERTICAL APPLICATIONS All pipe joints must escape of combustion be fastened and sealed to prevent products into the building. NOTE: Both venting methods shown in Figure 39 & 41 must also have the combustion air inlet installed - meeting dimension requirements of Figure 35. 26 Upflow furnace - The connection tubing for left and right side drainage is shipped in the blower compartment. Install the connection tubing from the trap to the side of the unit and trim all excess tubing to avoid kinks. 18-CD19D6-31 Installer's Guide Downflow furnace - The furnace is shipped with the left side drainage setup. To change the right side drain, remove the drain lines from the trap, rotate the trap 180 ° so it exits to the right, reconnect the lines, and run a 1/2" CPVC pipe from the trap out through the right side knock-out. Use RTV silicone sealant to connect the CPVC pipe to the trap for ease of removing trap. to clean the Left side DOWNFLOW (VERTICAL) Left side UPFLOW (VERTICAL) side Use CPVC tubing from Trap outlet, over burner box to cabinet exit DOWNFLOW (VERTICAL) extension hose here UPFLOW HORIZONTAL 21" & 24" UNITS (Left side only) HORIZONTAL APPLICATIONS Upflow and Downflow furnaces - All horizontal applications are left side only. It is always recommended that the auxiliary drain pan be installed under a horizontally installed evaporator and/or 90% gas furnace. Connect the auxiliary drain pan to a separate drain line (no trap is needed in this line). The trap must be repositioned to the exterior of the cabinet. Remove the trap from its present location and reposition the trap outside of the unit, through the long circular hole, next to the secondary recuperated cell. Remove the larger drain line (from the secondary cell) and trim to fit between the secondary cell and the new trap location. On upflow units, plug the hole in the blower deck where the tube went through. Remove the hose from the induced blower and reposition into the other drain tap of the inducer, which is lo- 18-CD19D6-31 Cut off curved end of Inducer drain hose DOWNFLOW (HORIZONTAL) cated 90 ° clockwise around the inducer. Move the cap from that drain tap to the unused drain tap. On upflow units, plug the hole in the blower deck where the tube went through. This tube on downflow units will need to be cut to fit between the inducer and the trap. On upflow units, this tube may need to be extended, using the tubing shipped with the furnace. 27 Installer's Guide IMPORTANT: Connections must be made to an OPEN/ VENTED DRAIN. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants. The condensate drain should be installed with provisions to prevent winter freeze-up of the condensate drain line. Frozen condensate will block drains, resulting in furnace shutdown. If the drain line cannot be installed in a conditioned space, then UL listed heat tape should be applied as required to prevent freezing (per manufacturer's instructions). The heat tape should be rated at 5 or 6 watts per foot at 120volts. Self-regulating (preferred) or thermostatically controlled heat tape is required. NOTE: Use 1/2" or larger PVC or CPVC pipe and fittings as required for drain connections (fittings, pipe and solvent cement not provided). Evaporator and furnace condensate drain piping may be manifolded together as shown in Figure 45. A primary drain vent stack must be installed and terminated below the outlet of the secondary heat exchanger drain connection to prevent water from damaging furnace controls if the primary drain outlet plugs up. Where the furnace is installed above a finished ceiling, the primary drain vent stack must be installed such that overflow from the vent stack opening will flow into an axillary drain pan in order to prevent water damage to the finished ceiling below. NOTE: A corrosion resistant condensate pump must be used if a pump is required for a specific drain system. FIELD WIRING @ USING T "STAT -- SEE NOTE 7 DIAGRAM FOR 1 STAGE FURNACE 1 STAGE HEATING A 1 STAGE HEATING THERMOSTAT NO COOLING FURNACE I 2 3 4 S L_ [] [] [] [] [] if upflow over from stack drain the furnace a finished the ceiling, primary must pan flow overflow drain into ceiling [ vent an auxiliary to prevent finished [] is installed damage to [] :: below. [_()TE:_:: 6 i BE SURE POWERAGREES WITH EOUIPMENT NAMPLATE(S} LOW VOLTAGE (24V WIRING) TO BE NO 18 AW6 MIN GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM THESE LEADS PROVIDE 115 V POWERFOR CONNECTIONOF ELECTRONIC AIR {LEANER AND HUMIDIFIER MAX LOAD I0 AMPS EACH THIS CONNECTION IS ONLY USED FOR THERMOSTATSREOUIRING CONNECTION TO THE 24 V POWER SUPPLY (COMMON) SEE TWINNING CONNECTION DIAGRAMS FOR PROPER CONNECTIONS WHEN USIN(_ THIS FEATURE SEE ] P?_o:tdr=oir._ ........ mM_LI I II secondary condensate ,_ II IdL_ heat drain exchanger outlet, NOTE 6 [] i i b_ ;i ;i ;i ;i ;i ;i ;i INTER (MP ----[l P 24 --LI NENT WIR]N M. FIEL E v'. ]_ WI_I }0 W. "_,. FA( TORY E ',,._)/ "/VI_RIN S From drawing 28 B341437 Rv 1 18-CD19D6-31 Installer's Guide FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE 1 STAGE HEATING, 1 STAGE COOLING USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT (OUTDOOR SECTION WITHOUT TRANSFORMER) T'STAT FURNACE NOTES: OUTDOOR UNIT (NO TRANSFORMER) D D t-q t-q SEE NOTE 6 h BE SURE POWER 2. LOW VOLTAGE{24 3. 4. S. 6. t-q t-q D D D SEE NOTE 8 7. 8. AGREES WITH EQUIPMENT V. WIRING} TO BE NO. 18 NAMEPLATE{S} A.W.G. MIN. GROUNDING OF EQUIPMENT MUST COMPLY SET THERMOSTAT HEAT ANTICIPATOR PER THESE LEADS PROVIDE 115 V. POWER FOR WITH LOCAL UNIT WIRING CONNECTION CLEANER AMPS AND HUMIDIFIER MAX. LOAD 1.0 CODES. DIAGRAM. OF ELECTRONIC AIR EACH. THE "Y" TERMINAL FROM THE THERMOSTAT MUST BE WIRED TO THE "Y" TERMINAL OF THE FURNACE CONTROL FOR PROPER BLOWER OPERATION DURING COOL]NO. IGNITION CONTROL 1S POLARITY SENSITIVE. HOT LEG OF 120 VOLT POWER SUPPLY MUST BE CONNECTED TO THE BLACK LINE POWER LEAD AS INDICATED ON THE WIRING DIAGRAM OR IGNITION LOCKOUT WILL OCCUR. THIS CONNECTION CONNECTION TO IS THE ONLY 24 V USED POWER FOR THERMOSTATS SUPPLY @ 2 ,ill REQUIRING (COMMON) GROUND SCREW JUNCTION BOX BK TO 115V {N•ER 7 7MPONEN• 2d ',.J". ----LINE ,.. F I E L D Yv'IRIN@ 2d --LINE m i ",,/'i]R]NG '/. 'k F£CTORY ....vg"IR IN O 60 HZ., SUPPLY LOCAL 1 PH., POWER PER CODES F l LH L N HUM SEE NOTE5 EAC SEE NOTE 5 _j BK WH From drawing B340388 Rv 2 L ELECTRICAL CONNECTIONS Make wiring connections to the unit as indicated on enclosed wiring diagram. As with all gas appliances using electrical power, this furnace shall be connected into a permanently live electric circuit. It is recommended that furnace be provided with a separate "circuit protection device" in the electric circuit. The furnace must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Electrical Code, if an external electrical source is utilized. 18-CD19D6-31 The integrated furnace control is polarity sensitive. The hot leg of the 120V power supply must be connected to the black power lead as indicated on the wiring diagram. Provision for hooking up an electronic air cleaner and or humidifier is provided on the integrated control. Refer to the SERVICE FACTS literature and unit wiring diagram attached to furnace diagram attached to furnace. 29 1 STAGE HEAT ONLY TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEATING ONLY THERMOSTAT THERMOSTAT (WITH FURNACE FAN SWITCH NO 1 FURNACE BLOWER UNIT NO, 2 OPERATION NO 2 IS /IOT_$ OF SYNCRON]ZED WITHUNITNO 1VIA SIGNALS FROMTWINCONNECTION BOTH FU#)MC_S THE SA74£ 5V MOST BE POF/b9[ ' fRO), LEG OK /ROUT PA#EL IHSUR# 2#Y #Ui!#ACL TRANSFORMERS ARE IN PHASk P_IOR TO COMPLklI#C COHNECTiO#$, CHEC_ FOLTAGF _FFW_N R ¸ T_£_/#Ai$ OF EACH FuRnACE iF VOLTAS_ /$ GR_AT_£ IH4# /OY, REVERSE _H_¸ Bi A# RD $_CO£DARY itADS 0£ O#E OF THL FU£NACE 7RA£SFO£HER$ 3 C<_'H CTiOtl t CTiOt_C FO! iF C_)_RFHT [XCE_DS _H_R#OSTA7 CURR£NT RMiNd, US_ ISOLATIOH RELAYS ('R{') AS SHOW#¸ (DO NOT CONNECT W _0 #) ISOLAT/O_ RELAY _0/ #EED_D fF THE THFRMOST_ CO#TACT$ 4RE R_T£_ AT i OA OR ABOYE SEE NOTE 4 qr< _,!A}' _ R gUHE_) T# Rt/,OSTAT ISOLATIONRELAY (FIELDSUPPLED) SEENOTE4 1 Rll- i ____. iSOLATiON RELAY SEE NOTE 4 INTE i CO['d:)ONENT Y',/]F_INO CLTER_'ATE /IiRM'_ 24 '/. ----kI\E % % SEE NOTE 3 24 v". LI_E -- CONF f_URAT O_' "k FIELD 7.jSYv'IRING i F#CTO:_Y /.S ?-',/',iI _ING iiiiiiiiiiii From Dwg. 21B341422 Rev. 3 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEAT/1 STAGE COOL THERMOSTAT OUTDOOR UNIT WITH TRANSFORMER 1 STAGE HEATING / COOLING THERMOSTAT FURNACE NO. 1 FURNACE NO. 2 BLOWER UNIT NO OPERATION O_ it_SURE 24i' 2 IS SYNORONIZED £URA4CE T_/)_SFOR!_ERS _RE E4C_ ¸ FURt_4CE _F VOLT4_E _S GRE_TE_ THe,', ,¸ _OY , i_V[R$_ THEfiL A_ RO S[20_b_i_ _4_$ , OUTDOO£U#tT H_S ,4 24' A_, ,¸ _OL_T_Ot_ ,_L4_ MUST_ 3g' I_o_o s_ T,Afl FO!t_ _i i_,_ST_LL_D i NOT_ SEE NOTE 4 (NO OUTDOOR TRANSFORMER} UNIT I_ nf,--i _SOLATION RELAy INTER 11 COMPONENT 24 ',/. L ]NE / 24 % ........% % V. --LINE I From Dwg21B341423 TWINNING FURNACES These furnaces may be twinned. Twinning requires that two furnaces with the same configuration, capacity, and airflow must be used. They shall have common returns with equal pressure drops or duets with equivalent lengths and sizes. See Eield Wiring Diagrams for proper hookup. Rev, 2 WIRING _ FIEL /" " x t, FACTOi
Source Exif Data:File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 40 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Mar 23 04:17:40 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools