TRANE Package Units(both Units Combined) Manual L0904648
User Manual: TRANE TRANE Package Units(both units combined) Manual TRANE Package Units(both units combined) Owner's Manual, TRANE Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 24
Download | |
Open PDF In Browser | View PDF |
I STALLATIO OPERATION NTE CE YCZ-|OIVI-1G 18-EB21 D4-8 Library Service Literature Product Section Unitary r°duct_..................................................................................................................... Packaged Gas/E!ect[!c Model YCZ Literature Type Installation, Operation, Maintenance Sequence ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES 1G Date File No. May 2004 SV-UN-RT-YCZ-IOM-1G 5/04 Supercedes New Model" YCZ036Fl/3MOB, YCZ050FI/3HOA, YCZ060FI/3MOB, Single Package Two Stage Gas/Electric 16 SEER Convertible 3, 4, 5 Ton 4MOA 4HOA 4MOA BAYLIFT002A LIFTING LUG KIT IMPORTANT-- This Document is customer property and is to remain with this unit. Please return to service information All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES. tion must conform with National Electric Code -- ANSI/NFPA 70 or "LATEST REVISION." pack upon completion of work. In the absence of local codes, the installa- Since Trane has a policy of continuous product and product data improvement, it reserves the right to change design and specification without notice. © 2004 American Standard Inc. All rights reserved 5/04 GENERAL IMPORTANT: Read this entire beginning kWARNING: manual installation INFORMATION before procedures. BOD,LY ,NJURY CAN RESU'T FROM HIGH VOLTAGE ELECTRICAL COMPONENTS, FAST MOVING FANS, AND COMBUSTIBLE GAS. FOR PROTECTION FROM THESE INHERENT HAZARDS DURING INSTALLATION AND SERVICING, THE ELECTRICAL SUPPLY MUST BE DISCONNECTED AND THE MAIN GAS VALVE MUST BE TURNED OFF. IF OPERATING CHECKS MUST BE PERFORMED WITH THE UNIT OPERATING, IT IS THE TECHNICIANS RESPONSIBILTY TO RECOGNIZE THESE HAZARDS AND PROCEED SAFELY. Read this manual carefully before attempting to install, operate, or perform maintenance on this unit. Installation and maintenance should be performed by qualified service technicians only. As shipped from the factory, this unit is for use with natural gas only, and is listed by Underwriters Laboratory. Model YCY-F heating/cooling units are designed for outdoor mounting with a vertical condenser discharge. They can be located either at ground level or on a roof, in accordance with local codes or National Fuel Gas Code (ANSI-Z223.1A) Latest Revision. Since these units are designed exclusively for outdoor operation, additional flue venting systems are not required. Each unit contains an operating charge of Refrigerant-22 as shipped. IMPORTANT: DO NOT CONNECT GAS PIPING TO THE UNIT UNTIL A LINE PRESSURE TEST HAS BEEN COMPLETED. DAMAGE TO THE GAS VALVE MAY RESULT IN AN UNSAFE CONDITION. THIS UNIT SHOULD NEVER BE EXPOSED TO GAS LINE PRESSURE IN EXCESS OF 14 INCHES WATER COLUMN. (1/2 PSIG) IMPORTANT: RECONNECT ALL GROUNDING DEVICES. ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING WIRES, SCREWS, STRAPS, CLIPS NUTS OR WASHERS USED TO COMPLETE A PATH TO GROUND ARE REMOVED FOR SERVICE, THEY MUST BE RETURNED TO THEIR ORIGINAL POSITION AND PROPERLY FASTENED. IMPORTANT: ALL POWER LEGS MAY NOT BE BROKEN BY CONTACTORS. SEE WIRING DIAGRAM ON UNIT CONTROL BOX COVER. THIS UNIT, AS SHIPPED FROM THE SIGNED FOR NATURAL GAS ONLY. iMPORTANT: when hoisting top). The use of "spreader bars" is required the unit (to prevent damage to sides and warning complies with State of California ,&WARNING: law, Proposition Nazardous Gasses ! This product must be gas piped by a Licensed Plumber Gas Fitter in the Commonwealth of Massachusetts. 3. Check to be sure the refrigerant charge has been retained during shipment. Access to 1/4" flare pressure taps may be gained by removing the furnace compartment access panel. NOTICE _WARNING: and Cautions appear at appropriate locations Read these carefully. Indicates a potentially hazardous throughout this manual. situation which, if not avoided, could result in death or serious injury. _CAUTION" Indicates a potentially hazardous situation which, if not avoided, result in minor or moderate injury. It may also be used to alert against and where property-damage-only accidents could occur. Page 2 65. Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm. 2. Check the unit's nameplate to determine if the unit is correct for the intended application. The power supply must be adequate for both the unit and all accessories. Warnings IS DE- BEFORE STARTING THE COMPRESSOR, THE CRANKCASE HEATER SHOULD BE ENERGIZED FOR EIGHT HOURS The following INSPECTION 1. Checkfor damage after the unit is unloaded. Report promptly, to the carrier, any damage found to the unit. Do not drop the unit. FACTORY, may unsafe practices or I I TYPICAL ROOFTOP iNSTALLATiON (YCZ036,050,060F WiTH FULL PERIMETER CURBS Models) / FIELD SUPPLIED SUPPORTS AT EACH END OF CURB ~ FIELD SUPPLIED CANT STRIP FIELD SUPPLIED RIGIDINSULATION ROOFMOUNTING CURB SUPPLY DUCT @ TYPICAL ROOFTOP AIR _ _ iNSTALLATiON (YCZ036,050,060F RETURN AIR DUCT WiTH BAYCURB030A,038A Models) I .J SEE NOTE1 SEE NOTE 2 FIELD SUPPLIED SUPPORTS AT EACH END OFCURB ROOF iNSULATION I \ CANT STRIP FIELD SUPPLIED RIGID INSULATION ROOF NOTES: 1. The YCZ036F models extend out past this end of the curb ONLY. SUPPLY AIR DUCT MOUNTING CURB RETURN AiR DUCT 2. TheYCZ050F, YCZ060F models extend past both the end and the side of the curb as illustrated. Page 3 DiMENSiONAL CORNER WEIGHT (LBS) MODEL YCZO36F WEIGHT W3 W4 (LBS) 161 106 104 157 528 137 196 626 YCZO50F 172 YCZO60F 195 Page 4 NET UNIT W2 W1 121 129 132 199 DATA 656 A B C D E F 64 36 29-3!16 18-9!16 11-1!16 85-1!8 45 33-3/8 21-1!16 15-1!16 4-15!1_ 6-9!16 G H 11-1!8 17 J K L 18-1!2 25-1!2 17-1!2 24 26-1!2 22-3/4 25-1/2 9-1!8 21-15!16 20 M N P 10 3 8-3/4 14 3-1/2 8-5/16 DiMENSiONAL © YCZ036,050,060F 152 CONTROL ACCESS DATA OUTLINE = FRONT MM /40 BOX PANE MM FlU (FIE[D NSTA I ED) 7COMBUST B/OWR D I ON ACC[ SS GAS ACCESS _CONDENS & 25 MM FOR OAS [1"} DIA. 15 MM [1/2] CONNECTION RIGHT SIDE SIDE Y952 CLEARANCE TO COMBUSTIBLE MATERIAL * 6.0" BOTTOM 30.0" BACK 0.0" 1.0" 24.0" LEFT SIDE 6.0" 42.0" RIGHT SIDE 6.0" 18" WITH FRESH AIR ACCESSORY 30" WITH ECONOMIZER FRONT SIDE 12.0" TOP 36.0" FRONT L NPT RECOMMENDED SERVICE CLEARANCE BACK CO K.O 066 LEFT R GUARD MODEL A B C D YCZ036F-M 64 36 29-3/16 27-1/2 YCZ050F-H YCZ060F-M 65-1!8 45 33-3!8 27-15!16 Page 5 ® CONVERTING HORIZONTAL TO DOWNFLOW NOTE SUPPLY OPENING 1. REMOVE SCREW NEAREST TO THE OPENINGAND PULLTHE PANEL FIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT. RETURN HEATER EXCHANGER TUBES OPENING 2. REMOVE RIGHT HAND SCREW AND MOVE PANEL TO THE RIGHT OR REMOVE BOTH SCREWS. SHEET METAL SCREWS HORIZONTAL RETURN AIR COVER HORIZONTAL SUPPLY AIR COVER ® REQUIRED CLEARANCE FOR UNIT INSTALLATION AND ROOF PENETRATION HOLE SiZE REQUIRED SERVICE CLEARANCE LINES SERVICE CLEARANCE LINES SIDE RAIL / WOOD NAILER _ SERVICE CLEARANCE & PENETRATION DIMENSIONS MODEL NO. A B C D E F YCZ036F 30" 30" "12" 30" 44" 25" YCZ050F YCZ060F 42" 30" "12" 36" 50" 25" * 18" WITH FRESH AIR ACCESSORY * 30" WITH ECONOMIZER Page 6 LOCATIONS HORIZONTAL AND RECOMMENDATIONS AIRFLOW APPLiCATiON 3. See the unit's nameplate for the absolute minimum clearance between the unit and any combustible surface(s). 1. These units are design certified for outdoor installations. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material. The discharge air from the condenser fans must be unrestricted for a minimum of 3 feet above the unit. NOTE: IMPORTANT: 1. Remove the Flue and Air Inlet Hood with gasket from the return air section of the unit. The screws that attach the flue and air inlet hood will be installed in their proper location at the factory. Therefore, they must be removed and then used to attach the flue and the air inlet hood. The unit is shipped for horizontal installation. The Air Inlet Hood in the combustion blower access panel must have adequate clearance around the air opening into the combustion area. See Outline Drawing, Figure 3. 2, Examine all flue product-carrying areas of the furnace, its vent system, and the main burner for safe operation. A periodic inspection of the furnace should be made by a qualified service agency at the start of each heating season. NOTE: Outdoor air or other requirements during heating operation that result m supply air temperatures below 80 degrees F or return air temperatures below 50 degrees F may cause flue gas condensate to form and is to be avoided. Replacement parts tistfor this Gas/ElectricAir Conditioner, may be obtained by contacting your local manufacturer representative. NOTE: If any internal accessories are to be added to the unit, install them at the shop if at all practical. 2. Location of the unit must allow service clearance around it. Clearance of the unit must be given careful consideration. See Figures 2, 3, and 4. DOWNFLOW APPLICATION -= CURB MOUNTING 1. The Roof Mounting Curb, (field assembled BAYCURBO30,O38,033,034A), or a field fabricated curb must be in place before the unit is hoisted to the roof top. 2, IMPORTANT: Air outlet duct must have 1" clearance combustible material downstream from the unit. Remove the packaging material from the components and secure the Flue and Air Inlet Hood with the gasket to the unit with sheet metal screws as illustrated in Figure 5. See "Firing Rate Selection" section for additional information. to 3. Check the handling facilities to ensure the safety of personnel and the unit(s). The Roof Mounting Curb (frame) must be installed on a flat, level section of the roof (maximum of 1/4" per foot pitch) and provide a level mounting surface for the unit. In addition, be sure to provide sufficient height above the roof to prevent water from entering the unit. NOTE: This unit was shipped for horizontal installation. Convert to downflow per instructions: 4 CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID PERSONAL INJURIES AND/OR DAMAGE TO EQUIPMENT Remove covers from the downflow supply and return air openings and place them over the horizontal supply return air openings (painted side out) and secure with sheet metal screws. See Figure 6. 5. The unit must be mounted level for proper drainage of water through the holes in the base pan. 6. The unit must not be exposed to direct roof water runoff. 3, 7. Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes. 8. Holes through exterior walls must be sealed in accordance with local codes. Be sure the mounting curb spans structural members (trusses) of the roof, thereby providing sufficient support for the weight of the unit, the curb, the duct(s), and any factory or field installed accessories. See Figures 1, 7, 8, 9, 10, and 11. 4. Be sure the hole in the structure for the ducts is large enough to accommodate the fabricated ducts and the insulation surrounding them. See Figure 4. 9. All fabricated outdoor ducts should be as short as possible. Note: If any internal accessories are to be added to the unit, install them at the shop if at all practical. CLEARANCES 1. The recommended clearances for single-unit installations are illustrated in Figure 4. These minimum requirements are not only an important consideration when determining unit placement, but they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency. 2. Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be reviewed with a local engineer. 5, These units are design certified for outdoor installation. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material. The discharge air from the condenser fans must be unrestricted for a minimum of 3 feet above the unit. The air inlet hood in the combustion blower access panel must have adequate clearance around air openings into the combustion area. See Outline Drawing, Figure 3. continued on next page Page 7 LOCATIONS AND RECOMMENDATIONS continued from page 7 Examine all flue product-carrying areas of the furnace, its vent system, and the main burner for safe operation. A periodic inspection of the furnace should be made at the start of each heating season. Replacement parts list for this Gas/Electric Air Conditioner may be obtained by contacting your local manufacturer representative. 15. Access and service clearances for the unit must be given careful consideration when locating the duct entrance openings. Figure 4 provides unit dimensions. 16. All fabricated outdoor ducts should be as short as possible. CLEARANCES 1, The recommended clearances for single-unit installations are illustrated in Figure 4. These minimum requirements are not only an important consideration when determining unit placement, but they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency. 2, Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be reviewed with a local sales engineer. 6. Location d the unit must allow for service clearance around it. Clearance of the unit must be given careful consideration. See Figure 4. 7. IMPORTANT: The air outlet duct must have one (1) inch clearance to combustible material downstream from the unit. 8. Exhaust vents or other sources of contaminated air should not be near the unit's air inlet, if outside air is to be introduced as makeup air or a ventilation feature is to be used, 9. Check the handling facilities to ensure the safety of personnel and the unit(s). 10. Caution must injuries and/or be taken at all times to avoid damage to the equipment. IMPORTANT: 1. Remove the Flue and Air Inlet Hood with the gasket from the return air section of the unit. The screws that attach the flue and air inlet hood will be installed in their proper location at the factory. Therefore, they must be removed and then used to attach the flue and air inlet hood. personal 11. The unit must be mounted level for proper drainage of water through the holes in the base pan. 2. Remove the packaging material from the components and secure the Flue and Air Inlet Hood with the gasket to the unit with sheet metal screws as illustrated in Figure 16 on page 14. 12. The unit must not be exposed to direct roof water runoff. NOTE: Outdoor air or other requirements during heating operation that result in supply air temperatures below 80 degrees F or return air temperatures below 50 degrees F may cause flue gas condensate to form and is to be avoided. 13. Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes. 14. Roof flashing must be installed to seal the roof curb cavity and must conform to local building codes. INSTALLATION UNIT SUPPORT If the unit is to be roof mounted, check the appropriate building codes for weight distribution requirements. Refer to the applicable roof curb mounting instruction. Check the unit's nameplate for supply voltage required. Determine if adequate electrical power is available. The furnace may be installed on Class A, B, or C roofing material. PLACING AND RIGGING 1. Before preparing the unit for lifting, check the outline drawing for center of gravity for lifting safety. Because d placement of internal components, the unit's weight may be unevenly distributed. Approximate unit weights are given in Figure 2, page 3. NOTE. Accessory BA YLIFTOO2AA, a kit of four (4) lifting lugs, is ] required for rigging the unit for hoisting. See Figure 7, insert B. l LOCATION AND CLEARANCES 2, Insert the four lifting lugs in the openings provided in the drip lip on the perimeter of the unit. See Figure 7, insert B. Atap or jerk to the lug will overcome the interference that arises due to the nipple on the lug. 3, Before hoisting the unit, be sure that the proper method of rigging is used, with straps or slings and spreader bars for protection during lifting. Always test-lift the unit to determine the exact unit balance and stability before hoisting it to the installation location. Installation d the unit should conform to local building codes or, in the absence of local codes, to the National Fuel Gas Code, ANSlZ223.1, Latest Revision, and the National Electrical Code. Canadian installations must conform to CSA and local codes. Select a location that will permit adequate combustion and ventilation air in accordance with Section 5.3, Air For Combustion and Ventilation, of the National Fuel Gas Code, ANSlZ223.1, Latest Revision, or applicable provisions of the local building code. Page 8 iNSTALLATiON IMPORTANT: Do not lift the unit without test lifting for balance and rigging. Do not lift the unit in windy conditions or above personnel. Do not lift the unit by attaching a clJvus, hooks, pins, or bolts to the unit casing, casing hardware, corner lugs, angles, tabs, or flanges. Failure to observe these warnings may result in equipment damage. 4. When the curb and air ducts have been properly installed, the unit is ready to be hoisted to the roof and set in position. IMPORTANT: ing the unit. "Spreader Bars" must be used when hoist- 5 IMPORTANT: The unit must be lowered into position. The P.V.C. rubber tape on the curb flange permits the unit to be repositJoned if required without destroying the P.V.C. rubber seals affixed to the mounting curb. PLACING THE UNiT ON A MOUNTING CURB 1. The unit is designed with a perimeter drip lip that is lower that the unit base bar, see Figure 7, inset A. 2. Position the unit drip lip down over and in contact with the outside corner of the curb, as illustrated in Figure 8, insert A. Continue to lower the unit on top of the curb, with the unit drip lip astraddle and in contact with both the end and side rail of the curb. The unit should now rest on top of the curb. 3. Take the two (2) hold-down brackets shipped with the curb and secure the unit to the curb with hold-down brackets as illustrated in Figure 8, insert A. © SPREADER BARS OUTDOOR COIL END OF UNIT BASE OF UNIT REST ON TOP OF CURB RAILS iIBn DRIP_ BA_L_OO, DIMPLE LIFTING LUGS DRIP LIP ON PERIMETER OF UNIT A CURB CORNER J NOTE: THE INNER PERIMETER OF THE DRIP LIP ON ALL UNITS SHOULD BE FLUSH WITH THE OUTER PERIMETER OF THE CURB ON THE TWO SIDES SHOWN HERE SEE FIGURE 2 FOR THE LOCATION OF THE UNIT OVERHANG ON THE YCZO36-O60F MODELS ® EXISTING SHEET METAL I SCREW HOLD-DOWN BRACKET WITH CURB ! FLANGE OF CURB Page 9 INSTALLATION ROOFTOP -- UNITS 4. Place the unit on the frame or roof curb. Refer to Figures 9 or 10. For roof top applications using a field fabricated frame and ducts, use the following procedure: 1. The frame must be located and secured by bolting or welding to the roof. Flashing is required. 2. The hole in the roof must be prepared in advance of installing the unit. 5. Secure the unit to the frame or roof curb. 6. Insulate any ductwork outside of the structure with at least two (2) inches of insulation and then weatherproof. There must be a weatherproof seal where the duct enters the structure. 7. Complete the installation according to the instructions following sections of this manual. 3. Secure the ducts to the roof. ® TYPICAL ROOFTOP APPLICATION WITH FRAME (YCZO36,050,O60F) -, , ® TYPICAL ROOFTOP APPLICATION (YCZ036,060F \ WITH FRAME MODELS) _/ ROOF DUCT _< ROOF / Page 10 SUPPLY FLASHING IRON FRAME AIR FLASHING INLET HOOD in the INSTALLATION GROUND LEVEL -= HORIZONTAL UNITS 2. Attach the supply and return air ducts to the unit• For ground level installations, the unit should be positioned on a pad the size of the unit or larger• The unit must be level on the pad. The pad must not come in contact with the structure (See Figure 11 .) Be sure the outdoor portion of the supply and return air ducts are as short as possible• 3. Insulate any ductwork outside of the structure with at least 2 inches of insulation and weatherproof• There must be a weatherproof seal where the duct enters the structure• 4. Complete the installation according to the instructions following sections of this manual• Proceed with the installation as follows: in the 1. Place the unit on the pad and the five (5) rubber isolators provided• ® TYPICAL GROUND LEVEL APPLICATION (YCZ036,050,060F MODELS) OUTDOOR DISCHARGE RETURN AIR AIR SUPPLY DUCT DUCT SIDING /_"_1_ OUTDOOR INTAKE AIR HOOD SUPPORTPAD FOUNDATION EXTERIOR WALL i- :'. INSULATE WEATHERPROOF OR RAIN SHIELD FLEXIBLE DUCT CONNECTORS CONDENSATE A 3/4-inch female NPT condensate drain connection is provided on the evaporator access panel end of the unit. See Figure 4. Provide a trap and fill it with water before starting the unit to avoid air from being drawn through• Follow local codes and standard piping practices when running the drain line. Pitch the line downward away from the unit. Avoid long horizontal runs. See Figure 12. ISOLATORS (1 PER CORNER AND 1 UNDER UNIT CONTROL BOX) DRAIN PiPiNG (_ TYPICAL CONDENSATE DRAIN PiPiNG 3/4" PVC OR COPPER NOTE: Do not use reducing fittings in the drain lines• The condensate drain must be: • Made of 3/4" pipe size. • Pitched 1/4" per foot to provide free drainage to convenient drain system• • Trapped• • Must not be connected to closed drain system• Page 11 DUCTWORK ATTACHING DOWNFLOW DUCTWORKTO ROOF CURB Supply and return air flanges are provided on the roof curb for easy duct installation. All ductwork must be run and attached to the curb before the unit is set into place. ATTACHING HORIZONTAL DUCTWORK TO UNIT All conditioned air ductwork should be insulated to minimize heating and cooling duct losses. Use a minimum of two (2) inches of insulation with a vapor barrier. The outside ductwork must be weatherproofed between the unit and the building. Follow these guidelines for ductwork construction: Connections to the unit should be made with three-inch connectors to minimize noise and vibration transmission. canvas Elbows with turning vanes or splitters are recommended mize air noise and resistance. to mini- When attaching ductwork to a horizontal unit, provide a flexible watertight connection to prevent noise transmission from the unit to the ducts. The flexible connection must be indoors and made out of heavy canvas. NOTE: Do not draw the canvas taut between the solid ducts, i The first elbow in the ductwork leaving the unit should be no closer than two feet from the unit, to minimize noise and resistance. AIR PROOF THIS SEAM _T BASE WEATHERPROOF FIELBDUCT.ql \ JJ UNIT FLANGE 'UNIT DUCT FLANGE _I_ / THIS SEAM FIELD DUCT AIR PROOF UN,TBASE UNIT EXTERIOR " FIELD DUCT UNIT DUCT FLANGE WEATHERPROOF THIS SEAM AIR PROOF _ FIELD THIS SEAM FIELDDucT JL DUCT _TBASE a UNIT DUCT FLANGE UNIT BASE UNIT EXTERIOR / UNIT FLANGE WITH BUTYL SILICONE NOT RECOMMENDED FIELD UNIT DUCT FLANGE SEAM OR / ]I _ - WEATHERPROOF THIS SEAM FIELD DUCT DUCT HORIZONTAL DOWNFLOW The following warning complies with State of California kWARNING: law, Proposition This product 65. contains fiberglass wool insulation! Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inhalation. Glasswool fibers may also cause respiratory, skin, or eye irritation. PRECAUTIONARY MEASURES • Wash clothes separately from other clothing: rinse washer thoroughly. • Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations. FIRST AID MEASURES • Avoid breathing fiberglass dust. • Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention. Skin Contact - Wash affected areas gently with soap and warm water after handling. Use a NIOSH approved dust/mist respirator. • Avoid contact with the skin or eyes. Wear longsleeved, loose-fitting clothing, gloves, and eye protection. Page 12 GAS PiPiNG iNSTALLATiON IMPORTANT: Before making the gas pipe connection give serious consideration to providing the required clearance nec= essary to remove the access panels on the unit (e.g., economizer and filter access panels). 1 NOTE: In the absence of local codes, the installation must_ conform with American National Standard--Z223. 1--National Fuel Gas Code, Latest Revision. The available gas supply must agree with the required gas supply marked on the unit nameplate. Minimum permissible gas supply pressure for purpose of input adjustment must be at least 5.0" W. C. (inches Water Column) for natural gas and 11' W.C. for propane. PIPE DELIVERY SCHEDULE (NATURAL NOTE: Theonly. following procedure Natural Gas 1.Obtain from the gas company gravity of the gas delivered. GAS NOTE: If this is an propane appfication, suppfler for pipe sizes and defiveries. GAS PRESSURE SET-UP i consult your propane | J PRECAUTIONS WARNING: NEVER USE ANOPEN FLAME TO TEST FOR GAS LEAKS: AN EXPLOSION OCCUR, CAUSING INJURY OR DEATH. COULD IMPORTANT: The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures exceeding 1/2 psig (3.48 kPa). ONLY) and tables below apply to The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures less than or equal to 1/2 psig (3.48 kPa). the heating value and specific GAS SUPPLY LINE PRESSURE (ALL FUELS) Before connecting the unit to the gas supply line, be sure to determine the gas pressure in the line. 2.Determine the exact length of pipe needed. 3.Read the BTUH input nameplate on the furnace. 4.Use the multiplier opposite the specific gravity of the gas given in Table 1 below and insert in the following formula: TABLE 1 SPECIFIC GRAVITY .50 .55 .60 .65 MULTIPIERS TO BE USED WHEN THE SPECIFIC GRAVITY OF THE GAS IS OTHER THAN 0.60 CFH = MULTIPIER 1.10 1.04 1.00 .962 NOTE: Maximum pressure to the gas valve for natural gas is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8"W.C. Minimum pressure to the gas valve is 11.0" W.C. If the supply line pressure is below the minimum supply pressure indicated on the unit nameplate, contact the gas supply company. Furnace Input in BTUH Gas Heat Content in BTU/Cu. Ft. X Multiplier Follow these steps to complete the installation of the unit gas piping. See Figure 14. This will give the factor for columns 2 through 6 in Table 2. 5.Using Table 2, select the pipe length nearest to yours. &Follow this line vertically down to the exact CFH found in Step 4 above or the next highest value. 7.Read horizontally to the left of this column for the required pipe size diameter. TABLE If the gas supply pressure is excessive (above 13.8 inches water column or 1/2 psig), install a pressure regulator either at the supply source or in the branch circuit serving the unit. Once the regulator is installed, set it to provide a maximum pressure of 13.8" W.C. to the gas valve for natural gas with a minimum supply pressure of 5.0" W.C. Maximum supply pressure of 13.8" W.C. to the gas valve for propane with a minimum pressure of 11.0" W.C. 1. Install a tapped, Style A (1/8-inch NPT tap) shut-offgas cock at the end of the gas supply line near the unit. Be sure the tapped gas cock is downstream of the pressure regulator, if used. (_ DEALER INSTALLED 2 NATURAL GAS ONLY ACCESS TABLE OF CUBIC FEET PER HOUR OF GAS FOR VARIOUS PIPE SIZES AND LENGTHS FOR TEST GAUGE CONNECTION FROM PIPE SIZE (inch) 10 20 30 40 50 60 70 1/2 132 92 73 63 56 50 46 3/4 278 190 152 130 115 105 96 1 520 350 285 245 215 195 180 1-1/4 1050 730 590 520 440 400 370 I Ir-6"-- _ LENGTH OF PIPE (feet) IS BASED QN PRESSURE DROP OF 0.3 INCH W.C. AND 0.6 SP.GR. TO MAIN CONTROL VALVE GAIS S'-_PPLY F'ELD SUPFLIE'_D D_ THIS TABLE GROUND UNION 1!8" N.P.T.PLUGGED LEG _ UN,T_ GAS VALVE, MUST BE INSTALLED BY DEALER OUTSIDE UNIT. GAS Page 13 GAS PiPiNG iNSTALLATiON 3 1® FLUE AND HOOD ILLUSTRATION the unit and should meet the specifications of all applicable i national NOTE: The gas cock must be installed outside of | and shut-off local codes. F[ i.i CLgT (/ A.%KE J [LE 2.Install a ground union joint downstream of the shut-off cock. This joint must also be installed outside of the unit, 3.Install a drip leg at least six (6) inches in depth next to the union as shown in Figure 14. This drip leg is required to collect any sediment that may be deposited in the line, 4.Before connecting the piping circuit to the unit, bleed the air from the supply line. Then cap or plug the line and test the pressure at the tapped shut-off cock. The pressure reading should not exceed 13.8 inches water column. TOP ACC JE -.. LS P_,NE , 5.Using an appropriate backup wrench on the gas valve inlet boss, connect the gas piping to the unit. Check the completed piping for leaks using a soap and water solution or the equivalent. I N 6.After installation of the gas pipe in the unit, the pipe chase opening should be closed with the fitter/barrier plug provided. MANIFOLD E H(}O} --, \ PRESSURE Check the manifold pressure at the unit gas valve. Do not exceed the recommended pressure shown on the unit nameplate. BURNER & VALVE ILLUSTRATION }ET SET PRESSURE SCREW: 51/32" POST ..... HEX j HEAD \ OUT T PRISSURE POS1 S_F SCI:/IW: 3/32" HrX HrAD / N / n Jl REGOLATORCOVER P/ \ \ 15t STAG" \\ \\ REGULATOR ....... MANUAl "oN/o_" TOP ViEW / SWITCH VIEW BETAIL::A:: I_BI_ _TE CONNECTOR N_LOCK WHITE RODGERS 36G GAS VALVE WITH MANUAL "ON/OFF" SWITCH BRASS SWITCH / SPRING DETAIL_ :At WHITE RODGERS 36E GAS VALVE WITH MANUAL "ON/OFF" SWITCH Page 14 COVER _ // \ }LC ] GAS PiPiNG INSTALLATION INPUT CHECK AND ADJUSTMENT TABLE 1. Make sure all gas appliances are off except the furnace. 2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution. 3. Match the "Sec" column in the gas flow (in cfh) Table 3 with the time clocked. 4. Read the "Flow" column opposite clocked. the number of seconds 5. Use the following factors if necessary. For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading / 2 For 1/2 Cu Ft. Dial Gas Ftow CFH = Chart Flow Reading / 4 For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow Reading / 4 6. Multiply the final figure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the nameplate rating. 7. Changes can be made by adjusting the manifold pressure. Sec. 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 3 GAS FLOW IN CUBIC FEET PER HOUR 2 CUBIC FOOT DIAL Flow Sec. Flow Sec. Flow Sec. 900 29 248 50 144 82 800 30 240 51 141 84 720 31 232 52 138 86 655 32 225 53 136 88 600 33 218 54 133 90 555 34 212 55 131 92 514 35 206 56 129 94 480 36 200 57 126 96 450 37 195 58 124 98 424 38 189 59 122 100 400 39 185 60 120 104 379 40 180 62 116 108 360 41 176 64 112 112 343 42 172 66 109 116 327 43 167 68 106 120 313 44 164 70 103 124 300 45 160 72 100 128 288 46 157 74 97 132 277 47 153 76 95 136 267 48 150 78 92 140 257 49 147 80 90 144 Flow 88 86 84 82 80 78 76 75 73 72 69 67 64 62 60 58 56 54 53 51 50 a. Attach a manifold pressure gauge. b. Remove the slot screw on top of the gas valve for 1st stage manifold pressure adjustment. Remove slot screw on outlet side for 2nd stage adjustment (See Figure 17). ® IMPUT ADJUSTMENT c. Turn the adjustment nut in to increase the gas flow rate, and out to decrease the gas flow rate using a 3/32" hex wrench. HIGH ALTITUDE INSTALLATION ADJUSTMENT Unit nameplate ratings are based on equipment operation from sea level to 2000 feet elevation above sea level. If the unit installation is from 2000 - 4500 feet elevation, it wilt be necessary to change the burner orifices to the noted sizes, (ref. National Fuel Gas Code, sec 8.1.2, Appendix F, Table F4). GAS MAN. PRESS ORIFICE SIZE ORIFICE SIZE TYPE ( in. W.C. ) 0 =2000 ft 2000 = 4G00 ft NATURAL 3.3 PROPANE 10.0 42* 43 54 55 FACTORY SHIPPED LGAS VALVE ON/OFF TOGGLE SWITCH 2rid Stage (Hi) Manifold °@0 Pressure wh,,:::ogo Adjustment 1st Stage (Lo) Manifold Pressure Adjustment Page 15 FILTER INSTALLATION TABLE AIR FILTERS Filters are to be used with the YCZ036,050,060F heating/cooling units. The basic unit does not have filters in it. However, a filter frame accessory is offered that wilt allow filters to be installed within the unit. Otherwise a filter rack must be installed by the installer in the duct work, Affix the filter label supplied with the unit adjacent to the filter area. ELECTRICAL ELECTRICAL CONNECTIONS Electrical wiring and grounding must be installed in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, Latest Revision. ELECTRICAL POWER It is important that proper electrical power be available for the unit. Voltage variation should remain within the limits stamped on the unit nameplate, DISCONNECT SWITCH Provide an approved weatherproof disconnect either on the side of the unit or within close proximity and within sight of the unit. OVER CURRENT PROTECTION The branch circuit feeding the unit must be protected as shown on the unit rating plate. POWER WIRING The power supply lines must be run in weathertight conduit to the disconnect and into the bottom of the unit control box. Provide strain relief for all conduit with suitable connectors. Provide flexible conduit supports whenever vibration transmission may cause a noise problem within the building structure. Be sure all connections are made tight. See Figure 18. NOTES: For branch circuit wiring (mare power supply to unit disconnect), wire size forthe length of run should be determined using the circuit ampacity found on the unit nameplate and the N.E.C. For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor. GROUNDING: THE UNITMUST BE ELECTRICALLYGROUNDED IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL ELECTRIC CODE. Page 16 4 NOMINAL FILTER* FILTER CFM Sq.Ft.- SIZE RESISTANCE YCZ036F 1200 4 0.05 YCZ050F 1600 5.33 0.05 YCZ060F 2000 6.67 0.05 UNIT *Filters must be installed in the return air system. The above square footages are based on 300 F.PM. face velocity. If permanent filters are used, size per mfg. recommendation with clear resistance of 0.05" WC. WIRING NOTE: Unit must be grounded for ignitor to operate properly. Gas pipe to unit is not an adequate ground. Ground the unit internally as provided. See wiring diagram for location. CONTROL WIRING (CLASS II) Low voltage control wiring should not be run in conduit with power wiring unless Class 1 wire of proper voltage rating is used. Route the thermostat cable or equivalent single leads of No. 18 AWG colored wire from the thermostat subbase terminals through the rubber gromment on the unit. See Figures 3 and 4 for the control entry location. Make connections as shown on the unit wiring diagram and in Figure 18. Do not short thermostat transformer. wires since this wilt damage the control Recommended wire sizes and lengths for installing the unit thermostat are provided in Table 5. The total resistance of these low voltage wires must not exceed one (1) ohm. Any resistance in excess of 1 ohm may cause the control to malfunction because of the excessive voltage drop. TABLE 5 THERMOSTAT WIRE SIZE AND MAXIMUM LENGTH WIRE SIZE 18 16 14 MAXIMUM LENTGH (Ft) 75 125 200 THERMOSTAT HEAT ANTICIPATOR The thermostat heat anticipators should be set to .4 amps on single or two stage thermostats. IMPORTANT: Upon completion of wiring check all electrical connections, including factory wiring within the unit, make sure all connections are tight. Replace and secure all electrical box covers and access doors before leaving the unit or turning on the power to the unit. ELECTRICAL After all electrical wiring is complete, set the thermostat system switch in the OFF position so that the compressor will not run and then apply power by closing the system main disconnect switch. This wilt activate the compressor sump heat. Do not change the ® WIRING Thermostat System Switch until power has been applied long enough to evaporate any liquid R-22 in the compressor. It is recommended that the sump heater be energized for eight (8) hours prior to starting. YCZ-F FIELD WIRING DIAGRAM PACKAGED I UNIT GAS-ELECTRIC CONTROL IITHERMOSTAT BOX "" CONNECT IONSI 1 I COMMON B ....... 47A(BK) G FAN /F]_...... 44A(YL) Y COMPRESSOR FIRST 41A[BR) Wl HEAT F_RST STAGE 41C(BR) W2 I HEAT SECOND STAGE '_ Z_ _-----55A(RD) UNIT GROUND_ WIRE l 36(BL ) i____ Q UNIT R LOW VOLTAGE "_ 45A(YL) AREA STAGE I 24V Y2 .. COMPRESSOR SECOND STAGE -yPI ROWER JL )TYPICAL 2 STAGE HEAT THERMOSTAT L_, 3 PH POWER UNIT NOTE ECONOMIZER CONNECT I TO ACCESSORY IONS ECONOMIZER FACTORY PROVIDED F_ELD INSTALLED WIRES I I I I _2!222222!2_ _ I II I I1 LI I I I I ', 36E_(BLI___ 56B(BL) e I I-------i _ f_ , L--.--I--44--ELYL)--_TC ' I ........ 44AIYL) YI ,TA,°K, tF" E (OR) 111 2::::: ON,;LOW III TYPICAL THERMOSTAT -,,c,oR, w2 2-STAGE NOTES: I. FUSED DISCONNECT OF EQUIPMENT MUST 2. BE SURE POWER SUPPLY HEATER NAMEPLATE. 3. LOW VOLTAGE 4. SEE UNIT THE THERMOSTAT 5. A 'G' SIGNAL HEATING MODE 6. WIRING DIAGRAM SIZE, POWER COMPLY WITH AGREES TO BE FOR ON THE WIRING CODES. WITH 18 AND EQUIPMENT AWG MINIMUM ELECTRICAL GAS/ELECTRIC UNiT JUMPER Wt 10 MINUTES INTER-COMPONENT AND WIRING 24V. LINE V. } FACTORY WIRING 24V. LINE V, _ F_ELD WIRING CONDUCTOR, CONNECTION IN THE COOLING MODE ONLY. THE FAN WILL BE ENERGIZED FOR SINGLE STAGE THERMOSTATS SECOND STAGE HEAT WILL BEGIN STAGE. GROUNDING DETAILS. MUST PROVIDE DURING BY THE THE SYSTEM, AND W2 AFTER TOGETHER. FIRST WIRE COLOR ABBR COLOR DESIGNATION ABBR COLOR BK BLACK PR BL BLUE RD PURPLE RED BR BROWN WH WHITE GR GREEN YL YELLOW OR ORANGEi Page 17 START - UP PRE-START QUICK CHECKLIST Is the unit properly located and level with the proper clearance? See Figure 4. Is the duct work correctly sized, run, taped, insulated, and weatherproofed with proper unit arrangement? See Ductwork Installation section. NOTE: Do not use the pressures from the unff's SERVICE FACTS to determine the unit refrigerant charge. The correct charge is shown on the unit nameplate. To charge the system accurately, weigh in the charge according to the unit nameplate. VOLTAGE With the compressor operating, check the line voltage at the unit. The voltage should be within the range shown on the unit nameplate. If tow voltage is encountered, check the size and length of the supply line from the main disconnect to the unit. The line may be undersized for the length of the run. • Is the gas piping correctly sized, run, trapped, and purged d air? See Gas Piping section. • Is the condensate line properly sized, run, trapped, and pitched? • Isthe fitterofthe correct size and number? Is it clean and in place? • Is the wiring properly sized and run according to the unit wiring diagram? Place the system selector in the OFF position or reset thermostat at a setting above room temperature. • Are all the wiring connections, • Has the unit been properly grounded and fused with the recommended fuse size? See Wiring Data. Do not de-energize the main power disconnect except when unit is to be serviced. Power is required to keep the heat pump compressor warm and boil off refrigerant in the compressor. • Is the thermostat level, correctly wired, welt located, and set for the proper heat anticipation? including those in the unit, tight? • Have the air conditioning systems been checked at the service ports for charge and leak tested if necessary? • Does the condenser fan and indoor blower turn free without rubbing, and are they tight on the shafts? • Has the indoor blower speed been determined and the proper speed been set? See the Unit Wiring Diagram. • Has all work been done in accordance with applicable local and national codes? • Are all covers and access panels in place to prevent air loss and safety hazards? COOLING SHUT DOWN HEATING CYCLE NOTE: See Sequence of Heating Operation. These units are equipped with a solid-state ignition control that lights the burners each time the thermostat calls for heat. The burners are extinguished during the OFF cycle. The gas heating section of the unit can be started using the following procedure: 1. Be sure the thermostat is at its lowest setting and the power to the unit is off. a. Turn the main shutoff valve on the gas supply line ON. b. Turn or switch the manual valve on the combination valve ON position. 2, STARTING THE UNIT iN THE COOLING MODE 3, to the highest setting in the heating As the thermostat calls for heat, the system cycles as follows: a. The combustion blower is energized. b. The pressure switch is closed. c. The gas valve opens and the ignitor lights the burner. d. Cycle the thermostat on and off a few times to check out the control system and burner operation characteristics. 4, With the burners operating, check the manifold pressure with a manometer. Do not exceed recommended pressures. 5, Adjust the unit to obtain an air temperature specified on the unit nameplate. 6, NOTE: For manifold pressures and orifice sizes for gas with other BTU ratings, contact the local gas utility. Manifold pressure should be 3.3 inches water column (+0.1). Input must not exceed the value shown on the rating plate. 7, Set the heat anticipator of the thermostat to equal the amperage draw of the gas valve, approximately 0.7. PRESSURES After the unit has operated in the cooling mode for a short period of time, install pressure gauges on the gauge ports of the discharge and suction line valves. Check the suction and discharge pressures and compare them to the normal operating pressures provided in the unit's SERWCE FACTS. Page 18 b. Turn the thermostat cycle. for a To start the unit in the cooling mode, set the thermostat system switch to COOL and move the thermostat COOL indicator to a setting below room temperature. The condenser (outdoor) fan motor compressor and evaporator (indoor) fan motor will operate automatically. OPERATING access panel is in place. a. Turn on the electrical power to the unit. CAUTION: Before starting the system on the cooling cycle, turn the thermostat switch to OFF and close the unit disconnect switch. This procedure energizes the compressor crankcase heater, vaporizing any liquid refrigerant in the crankcase. This is a precaution against foaming at start-up which could damage the compressor bearings. Allow the heater to operate a minimum of eight (8) hours. NOTE: See the section on "Sequence of Operation" description of the cooling operating sequence. Be sure the burner compartment gas rise with that START - UP 8. Set the thermostat at the desired temperature setting and the unit wilt function automatically. STARTING THE UNIT IN THE GAS HEATING MODE 6. Cycle the thermostat OFF and ON a few times at a rate of not more than once every thirty (30) seconds. Check both the control operation and the burner operating conditions. MANIFOLD PRESSURE 1. Check to make sure all grilles and registers are open and all unit access doors are closed before start-up. 2. Purge the gas supply line of air by opening the union ahead of the unit. When the odor of gas is detected, retighten the union and wait five (5) minutes before proceeding. 3. Set the walt thermostat to its lowest position and place the fan switch in the AUTO or ON position. 4. Open the main gas valve(s) and turn on the unit power supply. 1, Connect a manometer to the pressure tap at the outlet side of the unit's gas valve. Read the manifold pressure with the main burners firing. 2, If the manifold pressure reading does not match the value indicated on the unit nameplate, the unit pressure regulator must be adjusted as follows: a. Remove the cover screw on the gas regulator located on the front side of the unit's gas valve. b. Turn the adjusting screw clockwise to increase manifold pressure or counterclockwise to decrease manifold pressure. 5. Reset the heating temperature lever on the room thermostat at the highest value above room temperature. The combustion blower motor should energize. The main burners should light within 20-25 seconds. Initial start may be delayed somewhat if the unit has not been purged and air is trapped in the gas line. 3. Check the temperature rise during furnace operation to insure that it falls within the range specified on the unit nameplate. NOTE: Blue smoke produced by the heat exchanger during the initial burner firing is caused by a thin film of off on the surface of the heat exchanger. This off will burn off quickly. 4. If the temperature rise noted is outside of the specified limits, adjust the indoor air flow to cause the temperature rise d the heat exchanger to fall within the required range. SEQUENCE OF OPERATION Operation of the unit heating or cooling cycles is controlled by the setting of the system switch on the room thermostat. Once the system switch is placed either in the "HEAT" or "COOL" position, unit operation is automatic. Afan switch on the thermostat also provides for it continuous operation of the evaporator fan when desired. The fan switch "ON" position provides continuous operation while the "AUTO" position provides operation during the heating or cooling cycles. HEATING CYCLE Thermostat call for heat ( 2-stage thermostat) Call for 1st stage only: (R) and (W1) thermostat contacts close signaling the control module (IGN) to run its self-check routine. After the control has verified that the pressure switch (PS) contacts are open, the limit switch (TCO) contacts are closed, and the flame rollout (FL) switch is closed, the induced draft blower (CBM) will be energized on high speed for approximately 15 seconds. After the induced draft blower (CBM) has come up to speed, the control will verify that the pressure switch (PS) contacts are closed and switch the induced draft blower to low speed for an additional 5 seconds of prepurge. The gas valve (GV) is energized in the first stage to permit gas flow and the spark ignitor (IP) is energized. The flame detector (FD) confirms that ignition has been achieved within the 7 second trial period. As the flame detector confirms that ignition has been achieved the delay to indoor fan on period begins timing and after approximately 45 seconds, the indoor blower motor (IDM) will be energized at low speed and will continue to run during the heating cycle. Call for 2nd stage after 1st stage: (R) and (W2) thermostat contacts close signaling a call for second stage heat. The induced draft motor (CBM) is energized on high speed and the gas valve on second stage. After approximately 30 seconds the control energizes the indoor blower on high speed. 2rid stage satisfied, 1st stage still called: (R) and (W2) opens, the induced draft blower is reduced to low speed the gas valve is reduced to first stage. After aprox. 30 seconds the indoor blower motor is reduced to low speed. 1st stage satisfied: (R) and (Wl) opens, the gas valve (GV) will close. The induced draft blower (CBM) will be de-energized after approximately 5 seconds postpurge. The indoor btower motor (IDM)witt continue to run for the fan off period (field setectabte 60 or 90 seconds [by jumpers]), then wilt be de-energized by the control module. Thermostat satisfied: (R) and (W1/W2) (jumpered) contacts open signaling the control module to close the gas valve and de-energize the induced draft blower after approximately 5 second postpurge. The I.D. blower motor will continue to operate at the current speed for 60 or 90 seconds after the flames are extinguished. SAFETY SEQUENCES This product is equipped abnormal conditions. with safety devices to protect against The temperature limit switch (TCO) is located in the gas compartment on the vestibule panel above the burner assembly. This automatic reset device protects against excessive leaving air temperature. If this device opens, the gas valve is immediately closed and will not permit operation until the limit switch closes. Page 19 SEQUENCE OF OPERATION The rollout switch (FS) is located in the gas compartment near the inlet of the burners. This is a single use device designed to protect against any form of flame rollout. If this device is opened the gas valve is immediately de-energized and the control (IGN)will lockout the system. The roltout switch (FS) must be replaced before operation is allowed to continue. The pressure switch (PS) is located in the upper right side of the gas compartment. This automatic device assures adequate combustion air pressure. If pressure against the induced draft blower outlet becomes excessive, the pressure switch will react and shut off the gas valve, until acceptable combustion pressure is again available. If the control (IGN) does not sense flame within the first trial for ignition period. The gas valve wilt be de-energized. The control (IGN) will initiate a 60 seconds interpurge. Following the interpurge, on the second trial the gas valve wilt be energized on second stage (high heat input). If the flame is sensed within 10 seconds after the second try and only a call for first stage exists, the gas valve will be reduced to first stage. If the second try is not successful. The control wilt start other 60 second interpurge. After the interpurge, a third attempt will be tried. The gas valve wilt be energized on second stage (high heat input). Ifthe flame is sensed within 10 seconds after the third try and only a call for first stage exists, the gas valve wilt be reduced to first stage. If the third try is not successful. The control will lock out. If loss of flame occurs during a heating cycle, the control (IGN) wilt close the gas valve. The control will than recycle the ignition sequence, then if ignition is not achieved, it will shut off the gas valve and lock out the system. If control lock out occurs, the control (IGN) wilt retry a complete ignition sequence in 1 hour. The control (IGN) can be reset by removing power to the unit or by turning the thermostat from "on" to "off" for approximately three seconds, then back "on." COOLING CYCLE Thermostat call for cool ( 2-stage thermostat) Call for 1st stage only: With the room thermostat system switch in the "COOLING" position and the fan switch in the "AUTO" position, the YI thermostat contacts closes to the micro board, (the board will wait 3 seconds to check ff the Y2 may also be calling) the micro will energize (CCI) and the outdoor fan relay for towspeed and the G thermostat contact to G-IGN and to G1 on the ICMC is energized. (The status light is flashing and the Y1 light is on.) Call for 2rid stage after 1st stage: The Y2 thermostat contact closes to the control board. For 1 minute both compressors are off, (all lights are flashing for 1 minute), than the board will energize the (CC2) compressor contactor, and the outdoor fan relay for high speed then the board (YCZ050 ON LY- will energize the (CC1) and 1 second later the (CC2) compressor contactors) and the indoor fan high to the Y on the ICMC board is energized for indoor high speed fan operation. (The status light is flashing and the Y1 and Y2 lights are on.) 2nd stage satisfied, 1st stage still called:(YCZ036,060F The Y2 thermostat contact opens to the control board. For 1 minute both compressors are off, (the status and Yf light are flashing for I minute), than the board will energize (CC1)tow compressor contactor, and the outdoor fan retay for low speed and indoor fan for low speed. (The status light is flashing and the Y1 light is on.) 2rid stage satisfied, 1st stage still called:( With the thermostat fan switch in the "ON" position, the G thermostat contact is closed to G1 on the ICMC board and the indoor fan motor (IDM) will continue to run on low speed regardless of compressor and condenser fan operation. YCZ050 ONLY) The Y2 thermostat contact opens to the control board. The board wilt de-energize (CC2) second compressor contactor, and energize the outdoor fan relay for low speed and indoor fan for low speed. (The status light is flashh_g and the Y1 light is on.) ICM FAN MOTOR ADJUSTMENTS If the airflow needs to be increased or decreased, see the Indoor Blower Performance Table below. Information on changing the dip switch settings for speed control of the blower motor is in this table. Blower speed changes are made on the ICM Fan Control mounted in the control box. The ICM Fan Control controls the variable speed motor. There is a bank of 8 dip switches, (See Figure below), located at the lower right side of the board. The dip switches work in pairs to select the cooling/heat airflow (CFM/TON), and Fan off-delay options. INDOOR BLOWER TIMING The ICM Fan Control controls the variable speed indoor blower. The FAN-OFF period is set on the ICM Fan Control board by dip switches #5 and #6. ® CFMICM FAN SELECTION CONTROL DIP 21C800796P0 CNT03600 I_ LIGHT/! jjSWITCHES 012345678 CFM FAN z The energized compressor contactor (CCI) completes the circuit to the compressor (CPR1), If the compressor safety controls are closed, the compressor (CPR1) will operate with the outdoor fan motor (ODM) on tow speed. The indoor fan motor (IDM) will operate on tow speed. The thermostat will continue to cycle the compressor and fans to maintain the desired temperature. Y Y L0 ÷ o o12345678 DIP SWITCHES (TYPICAL SETTINGS) Page 20 ONLY) I_ IGN LED DIAGNOSTIC FLASHING SLOW CONTINUOUS CONTINUOUS INDICATOR NORMAL ON CALL FOR HEAT NORMAL OFF CHECK POWER / INTERNAL 2 FLASHES SYSTEM LOCKOUT 3 FLASHES PRESSURE FAILURE ( NO FLAME ) SWITCH PROBLEM 4 FLASHES HIGH LIMIT (TCO) OPEN 5 FLASHES FLAME SENSED WITH GAS VALVE OFF 6 FLASHES FLAME ROLLOUT 7 FLASHES SWITCH (FL) OPEN W1 & W2 SWAPPED CHECKOUT (_ PROCEDURE TROUBLESHOOTING CHART ................. u:7 ........................................... :.... Liquid Pressure Too high P Liquid Pressure Too Low SP Suction Pressure Too High S Suction Pressure Too Low Liquid Refrigerant floodback Liquid Refrig. floodback P S S SS PP S SP S SPS SS (TXV System) P (Cap. Tube System) SS SP P I. D. Coil Frosting Compressor S Runs Inadequate or No Cooling PS SP PS SPS ELECTRICAL Compressor & O.D. fan Do Not Start CompressorWill P Not Start But O.D. Fan Runs P O.D. Fan Won't Start Compressor Hums ButWill Not Start Compressor Cycles on IOL I.D. BIowerWon't P-PRIMARY Start CAUSES CAUSES S S P P P p p P P P S P P P S S S P P P S p p P S-SECONDARY P S P S P S P S S S S S P X66,€590 Page 21 MAINTENANCE ROUTINE MAINTENANCE BY OWNER • You can do some of the periodic maintenance functions for your YCZ-F unit yourself; this includes replacing the disposable or cleaning the permanent air filters, cleaning the unit cabinet, cleaning the condenser coil, and conducting a general unit inspection on a regular basis. Visually inspect the unit to ensure that the airflow required for combustion and condenser coil is not obstructed from the unit. • Inspect the control panel wiring to verify that all electrical connections are tight and that the wire insulation is intact. • Check the operation of the gas ignition system as follows: Turn off the gas supply with the unit operating to verify that the gas valve closes and that a ignition cycle is initiated by the unit. Visually inspect the inside of the burners and the burner ports for deposit buildup and corrosion. Wipe and brush the inside of the burner and the burner ports and then clean with a dry cloth. If the deposit buildup or corrosion is excessive, replace the burners. When the system is in constant operation. In new homes, check the filters every week for the first four (4) weeks. If you have disposable-type filters, replace them with new filters of the same type and size. Do not attempt to clean disposable filters. Permanent-type filters can be cleaned by washing them with a mild detergent and water. Make sure that the filters are thoroughly dry before reinstalling them in the unit (or duct system). • FLUE CLEANING NOTE: It may be necessary to replace permanent filters annually if washing fails to clean the filter or if the filter shows signs of deterioration. Be sure to use the same type and size as was originally installed. Before each heating season, the flue should be inspected for signs of flaking rust and soot deposits. Dirty flues should be cleaned by qualified service personnel ONLY using the following procedure: 1. Turn the room thermostat to the OFF position. Turn the main power disconnect OFF. Turn the manual gas valve OFF. CONDENSER COIL Unfiltered air circulates through the unit's condenser coil and can cause the coil's surface to become clogged with dust, dirt, etc. To clean the coil, vertically (i.e., with the fins) stroke the coil surface with a soft-bristled brush. 2. Remove the flue cap, the lower access panel, and the upper access panel. Be sure to keep all vegetation area. 4. Remove all wires from the gas value while carefully their location. ,&WARNING: away from the condenser coil 3. Remove the combustion blower assembly from the fluebox. Remove the flue box and the flue restrictors. 5. Disconnect TO PREVENT AN EXPLOSION OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE, DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE noting the gas supply line from the valve. 6. Remove the manifold retaining screws and pull the burnermanifold assembly from the heat exchanger. 7. Remove the inlet turbulators damage them. being careful not to break or 8. Wipe the flue box and flue baffles clean with a clean, dry cloth. MAINTENANCE PERFORMED COOLING SEASON BY SERVICEMAN-- 9. CAUTION: Never use combustible any part of the furnace. cleaning To keep your unit operating safely and efficiently, the manufacturer recommends that a qualified serviceman check the entire system at least once each year and any other time that you feel one is needed. Your serviceman should examine these areas of your DCX-F unit: 10. Replace all gaskets with new ones. 11. Replace all damaged • filters (for cleaning • motors and drive system components 13. Check all wires for correct installation unit's electrical wiring diagram. • economizer • safety controls • electrical components and wiring (for possible and connection tightness) • condensate • unit duct connections (to see that they are physically and sealed to the unit casing) or replacement) gaskets cleaning) replacement unit mounting • the unit (for obvious support (for structural sound integrity) unit deterioration) MAINTENANCE PERFORMED BY SERVICEMAN-HEATING SEASON Completethe unitinspectionsand serviceroutinesdescribed below atthebeginningofeachheatingseason. Page 22 with new ones. 15. Reinstall stack. by referring to the with a soap and water the top and bottom access panels and the flue 16. Visually inspect the unit to ensure that the airflow opening for combustion is not obstructed. drain (for cleaning) • on 12. Reassemble the unit by reversing Steps 2 through 7 above. Take care that all gaskets seat properly. 14. Leak test all gas line connections solution or the equivalent. (for possible replacement) (for mechanical or broken turbulators fluids 17. Follow the start-up procedure in service. ,&WARNING: above to place the unit back DO NOT OPERATE THE UNIT WITHOUT THE EVAPORATOR FAN ACCESS PANEL IN PLACE. REINSTALL THE ACCESS PANEL AFTER PERFORMING ANY MAINTENANCE PROCEDURES ON THE FAN. OPERATING THE UNIT WITHOUT THE ACCESS PANEL PROPERLY INSTALLED MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH. LIMITED WARRANTY COMBINATION GAS ELECTRIC AIR CONDITIONER YCZ, YCY AN D YCX Models Less Than 20 Tons for Residential Use* (Parts Only) This limited warranty is extended byAmerican Standard Inc., to the original purchaser and to any succeeding )wner of the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to products purchased and retained for use within the US.A. and Canada. f any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect within _veyears from the date of the original purchase, Warrantor will fumish without charge the required eplacement part. Any local transportation, related service labor, diagnosis calls, air filters, refrigerant and elated items are not included. n addition, if the sealed motor-compressor(s) fail(s) or the outdoor coiF should become defective, either or _oth events occurring because of a manufacturing defect within the sixth through tenth year from the date of _riginal purchase, Warrantor will fumish without charge the required replacement compressor and/or outdoor :oil. Any local transportation, related service labor, diagnosis calls, refrigerant and related items are not ncluded. NOTE: If your Combination Gas Electric Air Conditioner is installed within one mile of salt water, including but _ot limited to seacoasts and inland waterways, your outdoor coil warranty as stated above is limited to five ,ears from the date of original purchase. n addition, ifthe steel heat exchanger fails because of a manufacturing defect within the sixth through .wentieth year •Tomthe date of original purchase, Warrantor will fumish without charge a replacement heat exchanger. Any ocal transportation, related service labor and diagnosis calls are not included. This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged ivhile in your possession, damage caused by unreasonable use of the combination gas electric air _onditioner and/or damage from failure to properly maintain the combination gas electric air conditioner as _et forth in the Use and Care manual (see Proper Maintenance section). This limited warranty applies to product installed on or after 10/1/2001 where product is manufactured after 1/1/2000. This limited warranty is not retroactive to any installations prior to 10/1/2001 or on product produced _rior to 2000. THE LIMITED WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER NARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS DR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF VlERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL NARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES. ;ome states do not allow limitations on how long an implied limited warranty lasts or do not allow the xclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This limited warranty gives you specific legal rights, and you may also have other rights which zary from state to state. _arts will be provided by our factory organization through an authorized service organization in your area isted in the yellow pages. If you wish further help or information concerning this limited warranty, contact: _,merican Standard Inc. Troup Highway Tyler, TX 75711-9010 _,ttention: Manager, After Sales Support GW-631-1802 This limited warranty is for residential usage of this equipment and not applicable when this equipment is Bed for a commercial application. A commercial use is any application where the end purchaser uses the _roduct for other than personal, family or household purposes. Page 23 LiMiTED WARRANTY COMBiNATiON GAS ELECTRIC AiR CONDiTiONER YCZ, YCY, YCX, YCC, YCD, YCH, YCP, YHC and YSC Models Less Than 20 Tons for Commercial Use* (Parts Only) his warranty is extended byAmerican Standard Inc., to the original purchaser and to any succeeding owner of the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to products purchased and retained for use within the USA. and Canada. There is no warranty against corrosion, erosion or deterioration. If any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect within one year from the date of the original purchase, Warrantor will furnish without charge the required replacement )art. n addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through fifth year from the date of original purchase, Warrantor will fumish without charge the required replacement compressor. In addition, if the steel heat exchanger fails because of a manufacturing defect within the second through fifth year from the date of original purchase, Warrantor will fumish without charge a replacement heat exchanger. Warrantor's obligations and liabilities under this warranty are limited to fumishing F.O.B. Warrantor factory or warehouse at Warrantor designated shipping point, freight allowed to Buyer's city, replacement parts for Warrantor's products covered under this warranty. Warrantor shall not be obligated to pay for the cost of lost refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective. THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES. Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. American Standard Inc. Troup Highway Tyler, TX 75711-9010 Attention: Manager, After Sales Support GW-6064800 * This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a residential application. Commercial use is any application where the end purchaser uses the product for other than ersonal famit or household ur oses. Since Trane has a policy of continuous product and product data improvement, it reserves the right to change design and specification without notice. Trane 6200 Troup Highway Tyler, TX 75707-9010 A business of AmericanStandard Page 24 Companies Technical Literature - Printed in U.S.A.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 24 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun May 10 04:14:45 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools