TRANE Air Handler (indoor Blower&evap) Manual L0905036
User Manual: TRANE TRANE Air Handler (indoor blower&evap) Manual TRANE Air Handler (indoor blower&evap) Owner's Manual, TRANE Air Handler (indoor blower&evap) installation guides
Open the PDF directly: View PDF
.
Page Count: 12
| Download | |
| Open PDF In Browser | View PDF |
18-GE02D2=4 Convertible Air Handlers 1=1/2- 5 Ton for R-410A 4TEP3F18A1000A 4TEP3F24A1000A 4TEP3F30A1000A ALL phases of this installation IMPORTANT -- This Document information pack upon completion A. GENERAL 4TEP3F36A1000A 4TEP3F42A1000A 4TEP3F48A1000A must comply is customer of work. with 4TEP3F48B1000B 4TEP3F63A1000A 4TEP3F63B1000B NATIONAL, property and is to remain AND LOCAL with this unit. CODES Please return to service Contents iNFORMATiON THIS iNFORMATiON iS FOR USE BY iNDiViDUALS HAVING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AiR CONDiTiONiNG PRODUCT MAY RESULT iN PERSONAL iNJURY AND/OR PROP= ERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETATION OF THiS iNFORMATiON, NOR CAN iT ASSUME ANY LiABiLiTY iN CONNECTION WiTH iTS USE. To prevent shortening its service life, the air handler should not be used during the finishing phases of construction. The low return air temperaturescan lead to the formation of condensate. Condensat_ ;i_;;;the presence of chlorides and fluorides from pai;!i _ish, stains, adhesives, cleaning ...... creates acorrosive deterioration of the cabinet _;_ int_ _al _p STATE General information installationLimitations& These instructions cover 811v_ i ;_ns in systems or provide for Should further _formation e_ _ed o} particular problems ar_ _ :are_ _ sufficiently by this manual, co ;t No lo ::_ distributor or the manufacturer as handler nameplate. Thes_:_r Ha_lers are shipped from the factory in the upflow horizontal right configuration and are fully convertible to downflow or horizontal left. Refer to Section B beginning on page 3 for additional information. iNSPECTiON Check carefully for any shipping damage. This must be reported to and claims made against the transportation company immediately. Check to be sure all major components are in the unit. Any missing parts should be reported to your supplier at once, and replaced with authorized parts only. ........... Unit Installation Upflow Downflow Horizontal Left Horizontal Right Drain Piping Eh Control .........Checkout ;_ents. ........... Hook-up Outline -- Power Wiring Wiring Procedure Diagrams Drawings Cardboard packing material must be removed from inside the blower assembly before starting the unit. Failure to do so may cause indoor blower motor failure. INSTALLATION LIMITATIONS & RECOMMENDATIONS The general location of the air handler is normally selected by the architect, contractor and/or home owner for the most effective application and satisfaction. These air handlers are suitable for installation in a closet, alcove or utility room with free, non-ducted, air return, using the area space as a return air plenum. With ducted supply air, if the minimum clearances to combustible materials and service access are observed, the above installations are suitable. |nsta||er's Guide This area may also be used for other purposes, including an electric hot water heater - but in no case shall a fossil fuel device be installed and/or operated in the same closet, alcove or utility room. 6. If supplementary heat is to be added, power supply must be sufficient to carry the load. In addition, minimum air flow settings, unit and duct clearances to combustible material must be maintained as stated on the air handler rating nameplate. In addition, these air handlers are suitable for installation in an attic, garage or crawl space with ducted supply and return air. Eo o) For air handlers not equipped with a factory installed electric heater, a field installed heater is available from American Standard inc. Only heaters built by American Standard inc. are approved for use in the air handler. These heaters have been designed and tested in accordance with UL standards to provide safe and reliable operation. A list of approved heaters is provided on the air handler rating nameplate. Heaters that are not factory approved could cause damage and are not covered under equipment warranty. This equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280 or the equivalent. "SUITABLE FOR MOBILE HOME USE." For proper installation considered: !. the following items must be If adequate power is available and correct according to nameplate specifications. 2. Insulate all ducts, particularly if unit is located outside of the conditioned space. NOTE: 3. To ensure maximum efficiency and system performance, the existing supply and return duct system static pressures must not exceed the total available static pressure of the air handler. ReferenceACCA Manual D, Manual S and Manual RS along with the air handler Product Data and Service Facts for additional information. ff air handier is used WITHOUT a supplementary electric heater, a sheetmeta] plate is required to cover the open hole in the airflow system. See Figure 2. Also seal the cabinet air tight where the wire enters. 7. If field installed electric heaters are applied, minimum air flow settings, unit and duct clearances to combustibles must be maintained as stated on the air handler rating nameplate. 4. It is recommended that the outline drawing be studied and dimensions properly noted and checked against selected installation site. By noting in advance which knockouts are to be used, proper clearance allowances can be made for installation and possible future service. 8. If the unit is installed without a return air duct, applicable local codes may limit this air handler to installation only in a single story residence and within conditioned space. 5. When air handler with supplementary heater is to be installed in the downflow position on combustible flooring an accessory subbase (TAYBASE101 for 4TEP3F18-36A, TAYBASE 100 for 4TEP3F42A, 4TEP3F48-63B and TAYBASE102 on 4TEP3F48-63A) must be used. See Figure 1. © 9. If the outdoor unit is to be installed later, or by others, then installation of the air handler must be made to allow access for refrigerant lines, or attach refrigerant lines to air handler when installing. AiR HANDLER JOISTS _ l SUBBASE JOIST HEADER_._ m m m A m =..,,,,,.,_ I APPROX, JL HEADER JOISTS _ 3/4" FLANGES ON FIELD SUBBASE JOIST F_" FLOOR OPENING - SIZE MODEL NO. A B TAYBASE 100 23-3/4 14-13/16 TAYBASE 101 21-3/4 14-13/16 TAYBASE 102 26-3/4 14-13/16 MATERIAL. © 2004 American Standard Inc. All Rights Reserved 2 18-GE02D2-4 |nstaller's Replace this baffle with the factory supplied narrow coil baffle using the screws removed previously (See Figure 3). @ IF AIRHANDLER IS USED WITHOUT A FACTORY FURNISHED SUPPLEMENTARY HEATER, A PLATE IS REQUIRED TO COVER THE OPEN HOLE IN THE AIR FLOW SYSTEM _L I" I'T 17" Guide C. b] Position unit on Pedestal or other suitable foundation. If Pedestal is not used, a frame strong enough to support the total weight must be provided. Provide a minimum height of 14 inches for proper unrestricted airflow. 1/4" HOLES (4) _o .± ACCESSORY d. If a return air duct is connected to the air handler, it must be the same dimensions as shown in the outline drawing. BAY99X123 _-- 3/8" From Dwg. 21 B140413 !0. Make sure there are provisions for installing sate drain lines. conden- !1. If side, front or rear return is required, air handler must be elevated or placed on a plenum (TAYPLNM100 or 101). Connecting return duct directly to the side, front or rear of the cabinet is not approved. 12. Route refrigerant and condensate drain lines away from air handler so they do not interfere with access panels and filters. 13. When external accessories are used, the additional height and width requirements must be considered the overall space needed. in e. Pedestal and unit should be isolated from the foundation using a suitable isolating material. DOWNFLOW a. For maximum efficiency, the horizontal drip tray should be removed. Tray removal requires that the coil be removed by sliding the coil out on the coil channel supports. The tray is detached by removing the two screws at the drain pan and the two screws holding the two brackets at the top of the coil. b. Remove the factory installed baffle assembly from the apex of the coil by removing the 5/16" hex head screws. Replace this baffle with the factory narrow coil baffle using the screws previously (See Figure 3). 14. These units are not approved for outdoor installation. 15. These units are approved tion only. for draw-through applica- B. UNIT INSTALLATION UPFLOW a. For maximum efficiency, the horizontal drip tray should be removed. Tray removal requires that the coil be removed by sliding the coil out on the coil channel supports. The tray is detached by removing the two screws at the drain pan and the two screws holding the two brackets at the top of the coil. supplied removed NOTE: INSTALLATION OF THE DOWNFLOW BAFFLE KIT INCLUDED WITH UNIT IS REQUIRED ON DOWNFLOW APPLICATIONS. SEE FIGURE 4. © DOWNFLOW BAFFLE KiT DISCARD HORIZONTAL SCREWSTO REMOVE b. Remove the factory installed baffle assembly from the apex of the coil by removing the 5/16" hex head screws. ® FOR MAXIMUM EFFICIENCY ON HORIZONTAL LEFT, UPFLOW AND DOWNFLOW Remove and Discard 7/8"GASKET- Replace with Narrow Baffle 1/2" GASKET INSIDE SURFACE OF BAFFLE SECT. X-X (TYP. BOTH SIDES) ATER ....... oh% DIVERTER \ _,/"-BoO "_ o%0 . ,.AFF WITH 7-.J,_%o/f 15TON ONLY/ _CREWS TO REMOVE COIL oo ooo ooo ooo BLOW-OFF WATER BAFFLES ATTACH 2SCREWS ...... o°° EACH SIDE I _ " "_ / _LL 18-GE02D2-4 _\%o_'_, J o '-_-"-' WITH SEALANT 3 |nsta||er's Guide c. Detach the coil from the drain pan by removing 4 screws as shown in Figure 4. f. Cage nuts are not provided for horizontal left suspension. However, if the unit is suspended, it must be supported from the bottom near both ends as well as the middle to prevent sagging. The service access must remain unobstructed. d. Remove the front triangular baffle from the coil and install the 1/2" wide gasket provided per Figure 4. Trim the gasket length to fit the baffle. Reinstall the bane to coil, with gasket material compressed against the coil. e. Install the water blow-offbaffles provided on each side of the coil with the flange at the top as shown in Figure 4. The bottom of the baffle is to be as close to the bottom of the coil as possible. f. Install the 7/8" wide gasket in each side of the drain pan as shown in Figure 4 (sect. X-X). g. It is always recommended that an auxiliary drain pan be installed under a horizontal air handler (See Condensate Piping) to prevent possible damage to ceilings. h. Isolate the auxiliary drain pan from the unit or from the structure. h. The unit is then placed with the blower side down and the coil is replaced on the coil channel supports with the drain connections at the bottom. The unit is now in downflow position with front access. HORIZONTAL RIGHT a. For maximum e_iciency and Customer ease of filter maintenance, it is recommended that a properly sized remote filter grille be installed for horizontal applications. Airflow should not exceed the face velocity of the filter being used. The factory installed filter should then be removed from the unit. HORIZONTAL LEFT a. For maximum efficiency and Customer ease of filter maintenance, it is recommended that a properly sized remote filter and grille be installed for horizontal applications. Airflow should not exceed the face velocity of the filter being used. The factory installed filter should then be removed from the unit. b. To convert the unit to horizontal left, front access, slide the coil out on the coil channel supports and rotate the complete coil 180 degrees. c. Remove the factory installed bane assembly from the apex of the coil by removing the 5/16" hex head screws. Replace this baffle with the factory supplied narrow coil bane using the screws removed previously (See Figure 3). d. The coil is then inserted back into the cabinet on the opposite side coil channel supports. The unit is now horizontal left with front access. e. Openings where field wiring enters the cabinet must be completely sealed. Location power entry is shown on the Outline Drawing. 4 must be supported as carefully to prevent isolators (purchased the unit. g. Place the 2 water diverter baffles (5 ton model only) underneath the coil on the inside edge of the drain pan, Figure 4. Fill the bend in the baffle which fits the inner edge of the drain pan with RTV type adhesive/sealant before installing the baffle. i. When air handler with supplementary heater is to be installed in the downflow position on combustible flooring an accessory subbase (TAYBASE101 for 4TEP3F18-36A, TAYBASE100 for 4TEP3F42A, 4TEP3F48-63B and TAYBASE102 on 4TEP3F4863A) must be used. See Figure 1. iiiiiiiiiiii If the unit is not suspended it mentioned above and isolated sound transmission. Vibration locally) must be placed under of i. Connect the auxiliary drain pan to a separate drain line (no trap is needed in this line) or route outside the structure to a conspicuous location in accordance with national and local codes. b. Unit is shipped from the factory in the upflow or horizontal right configuration. Unit conversion is not required. c. The unit is designed for suspension using 1/4" 20 threaded rods. Other means of suspension are allowed as long as the unit is supported from both ends as well as the middle to prevent sagging and service access is not obstructed. d. If the unit is not suspended it must be isolated carefully to prevent sound transmission. Vibration isolators (purchased locally) must be placed under the unit. e. It is always recommended that an auxiliary drain pan be installed under a horizontal air handler (See Condensate Drain Piping) to prevent possible damage to ceilings. f. Isolate the auxiliary drain pan from the unit or from the structure. g. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line) and terminate according to local codes. h. If a return duct is connected to the Air Handler, it must be the same dimensions as the return opening shown in the outline drawings. 18-G E02D2-4 |nsta||er's C. DUCT CONNECTIONS The supply and return air ducts should be connected the unit with flame retardant duct connectors. to @ BRAZE Guide SHIELD Convertible duct flanges are provided on the discharge opening to provide a "flush fit" for 3/4" or 1-1/2" duct board applications. See the Outline drawing on page 9 for sizes of the duct connections. After the duct is secured, seal around the supply duct to prevent air leakage. ///- NOTE: If the convertible duct flanges are not used, they must be removed and discarded for proper airflow. D. REFRIGERANT PiPiNG IMPORTANT: Refrigerant piping must be routed to maintain service access to blower compartment and provide easy removal of filter access panel and filter. i. Refrigerant connections are made outside 2. Installation of refrigerant lines is covered in the installation instructions packaged with the outdoor unit. Evacuation, leak testing and brazing procedures are included in those instructions. Read those instructions before starting installation of refrigerant lines. TO EVAPORATOR SECTION NOTE: A brazing shield is provided in the information pack accompanying this unit. This shield fits over the refrigerant fittings while brazing. Wet the shield before brazing. See Figure 5. IMPORTANT: Do not unseal refrigerant tubing until ready to cut and fit refrigerant lines. E. CONDENSATE sealing caps from indoor coil field 2. Field supplied tubing should be cut square, round and free of burrs at the connecting end. Clean the tubing to prevent contaminants from entering the system. 3. Run refrigerant unit coil. tubing into the stub sockets of indoor 4. Braze and evacuate according to indoor and outdoor installation instructions. PAINTED AREAS OF UNIT MUST DURING BRAZING. BE SHIELDED DRAIN PiPiNG NOTE: Make certain that the unit has been installed in a level position to ensure proper draining. The indoor blower is downstream of the evaporator coil which creates a negative pressure at the condensate drain connections during operation. The condensate drain connections in front of the indoor coil are 3/4" NPT. The lower connection is the primary drain. See Figure 6. Two secondary drain connections are provided for the different orientations (See Figure 6). The lower of the two should be connected as a backup to prevent condensate overflow by a blocked primary drain. For proper drainage should be followed: !. !. Remove the connections. i the cabinet. Note: TXV bulb MUST be protected (wrapped with wet rag) or removed, while brazing the tubing. Overheating of the sensing bulb will affect the functional characteristics and performance of the air handler. BRAZING i of condensate, the following steps The primary drain line must be trapped with a minimum of 2" water seal as shown in Figures 7 & 8. Do not use preformed 3/4" PVC running traps. The use of Field fabricated or manufactured traps as shown in Figures 7 & 8 is acceptable. The manufactured trap shown in Figure 7 allows for a float switch option to be added. Refer to the manufacturer's for details. data and instructions 2. The trap must be located within 4 feet of the air handler drain outlet connection. 3. It is recommended that a clean-out tee or cross be installed in the primary drain line for future maintenance (See Figures 7 & 8). 4. Do not use reducing fittings in the condensate lines. 18-GE02D2-4 drain 5 |nsta||er's Guide 5. Slope the drain per foot. ® 6. Insulate 7. Provide freeze-up the primary 3/4 NPT Secondary 3/4" NPT Primary drain connection MANUFACTURED to prevent the drain sweating. winter system. drain line compound or It is always recommended that an auxiliary drain pan be installed under a horizontally installed air handler. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line) and terminate according to local codes. NOTE: DO NOT use a torch or flame near the plastic coupling. TRAPS of 1/4" line to a closed drain 9. Use Teflon ® tape on the air handler connections! Do Not Use pipe joint PVC/CPVC cement! drain connection © drain a minimum means for drainage to prevent of condensate line. 8. Do not connect i lines downward drain pan NOTE: DO NOT tighten the drain pipe excessively. Support the condensate piping and traps outside the unit to prevent strain on the drain coupling. 2" MINIMUM r = 2" MINIMUM F= ELECTRICAL m POWER WIRING 1. These Air Handlers are shipped from the factory wired for 230 volts. The units may be wired for 208 volts. Follow instructions on unit wiring diagram located on blower housing and in the Service Facts document included with the unit. EZT-105 (_ TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING PARTS, LOCK UNIT DISCONNECT SWITCH IN OPEN POSITION [BEFORE SERV C NG UN T. FIELD FABRICATED 2. The selection of wire and fuse sizes should be made according to the Minimum Branch Circuit Ampacity and the Maximum Overcurrent Device listed on the unit nameplate. TRAP 3. Field wiring diagrams for electric heaters and unit accessories are shipped with the accessory. 4. Wiring must conform to National and Local codes. Ground unit per Local codes with good safety procedures. 2" lVllN. I m I =, I 2" Mid ,I I I I I If an electric heater is not installed, connections are made through the 7/8" knockout into the air handler junction box to the two power leads and ground wire connections which are located near the discharge of the blower. NOTE: ff air handler is used with or without a heater, the 7/8" electrical entry hole as weft as any other cabinet penetrations must be sealed air ti hghL. I Close as possible Trap must be within 4' of air handler condensate drain connection. 6 [ J 18-G E02D2-4 Installer's G. CONTROL WIRING Guide NOTE: !. Connect wiring between indoor unit, outdoor unit and thermostat. The use of color-coded low-voltage wires is recommended. Direct drive motors have bearings which are permanently lubricated and under normal use lubrication is not recommended. 2. A low voltage terminal board is provided for control wiring, and is located on the left side of the cross brace in the center of the unit. H. CHECKOUT 3. Field wiring diagrams are provided which show the low voltage wiring hook-up for a single speed cooling only system (with supplementary heaters) and a heat pump system (with supplementary heaters). Plug in type electrical connectors with supplementary heaters. Cardboard packing material must be removed from inside the blower assembly before starting the unit. Failure to do so may cause indoor blower motor failure. 4TEP3F AIR HANDLER [Z] WITH HEAT PUMP HEAT PUMP O.D. SECTION (SINGLE SPEED) AIR HANDLER _NOTE in are provided for use When supplementary heaters are installed, inspect to insure that all packaging material has been removed. J and installation on page 12, 2, "Operational Procedure" for the system installation can be found in the outdoor unit installer guide and will be compatible with this Air Handler. IMPORTANT: T'STAT PROCEDURE !. Check the Air Handler operation accordance with this instruction 5 [Z] _--R NOTES: I. [Z] _--.y WHEN FIELD-INSTALLED HEATERS ARE USED, DISCARD POWER LEADS WITH POLARIZED PLUG I-PM AND CONNECT I-PF TO MATING PLUG iN THE HEATER CONTROL BOX AS SHOWN. _--0 [Z] [] BR/X2 OR BK % i i J ODT" LOW VOLTAGE WIRING TO BE NO. 18 A.W.G. MINIMUM CONDUCTORS. I ___ 3. IF OUTDOORTHERMOSTAT(ODT) IS NOT USED, CONNECTWl TO W2 TO W3 ON LVTB. 4. CONNECT IN THIS MANNER IF O.D. UNIT HAS "F" CONNECTION. 5. SEE HEATER WIRING DIAGRAM FOR HEATING ANTICIPATOR SETTINGS. i ODT-2 INTER-COMPONENT NOTE3 % WIRING -24 V. FACTORY = LINE v.jWIRING % 24 LINEV V. )FIELD WIRING [] BR(T NOTE 4 SEE NOTE 2 IPF_:],,,,/PM-A CONTROL BOX SUPPL HTR. ] RED FOR /3 PH I f TO POWER SUPPLY PER LOCAL CODES & AS DEFINED IN FIELD WIRING TABLE 18-GE02D2-4 IlIP | H | H TO POWER SUPPLY __ PER LOCAL CODES From Dwg. 21 B801082 Rev. 1 7 |nsta||er's Guide 4TEP3F AiR HANDLERS WiTH SINGLE SPEED COOLING COO AIR T 'STAT HANDLER UNIT, 1 STAGE HEAT I NG O,D, SECTION (SINGLE SPEED) I.................................................... _NOTE4 NO1ES: I ..y LOW VOI1AGE WiRiNG 10 BE NO. 18 AWG MiNiMUM CONDUCTOR WHEN FIELD-INSTALLED HEATERS ARE USED, DISCARD POWERLEADS W}TH POLARIZED PLUG PN-A AND CONNECT I-PF TO MATING PLUG }N THE HEATER CONTROL BOX AS SHOWN [] 3 IF OUTDOOR THERMOSTAT (ODT) }S NOT USED, CONNECT Wl TO W2 TO WB ON IVTB 4 SEE HEAIER WIRING DIAGRAM FOR HEATING ANTiCiPATOR SETTING [] _E3 INTER-COMPONENT WIRING [] SEE NOT_ 2 IW P_ A RED FOR From Dwg. 21B801083 4TEP3F AIR HANDLER WITH SINGLE SPEED COOLING UNIT, 2 STAGE HEAT COOLING O,D. SECTION (SINGL SPEED) T'STAT 2-STAGE HEAT/ I-STAGE COOL Rev. 1 IR HANDLER _--NOTE 3 [] _, IPNV "_-FIELD ADDED JUMPER [] [] --y NOTES: [] [] [] I. LOW VOLTAGE WIRING TO BE NO. 18 A.W,G. MINIMUM CONDUCTOR. [] WHEN FIELD-INSTALLED HEATERS ARE USED, DISCARD POWERLEADS WITH POLARIZED PLUG PM-A AND CONNECT I_PF TO MATING PLUG IN THE HEATER CONTROL BOX AS SHOWN, [] [] [] 3. SEE HEATER WIRING DIAGRAM FOR HEATING ANTICIPATOR SETTING, [] SEE NOTE 2 '"RF_pN.A INTER-COMPONENT ...... WIRING 124 v _FACTORY LINEIv_WlRING 24 V LiNE V _Bo_SUPPL_ _ NTR FoRREO3 PN TO POWERSUPPLY PER LOCALCODES & ASDEFINEDIN FIELDWIRINGTABLE 8 FIELD WIRING TO POWERSUPPLY PER LOCALCODES From Dwg. 21B801081 Rev. 1 18-G EO2D2-4 Installer's OUTLINE DRAWING FOR 4TEP3F18-63A, Guide 48-63B AIRFLOW CIRCUIT BREAKER 114 7 T K TOP VIEW 114 _ s s7,,,d FIG.I FILTER ACCESS I 64_ VERTICAL UPFLOW FIG.I o MODELNO. 4TEP3FI8, 24, S0, d 41EPSF42,41EP3F48,418P3F63B 4TFP3F48A FIG.2 K , _9,22 & 36 12.02 2122 K 18.22 }102 2372 4TEP3FO63A _j_ 2022 K 2272 : OPENINGDISCHARQE_/I 'i / SIDE VIEW i O0 88 _ ................... I 00_ FIG.2 OPENING C I" FOR THE FIRST 3 FT OF OUTLET DUC( WHEN ELECTRIC HEALERS ARE HqS[AL/ED EXCEPT MODELS BAYHTRI405, 1408, AND 1410 ARF APPROVED FO_ 0" PLENUM AND DUCT CLFARAHCE IN [HE UPFLOW CONFIGUI_ATIO_ ONLY ON TWEP MODELS¸ oo } BOTTOM VIEW MODELNO. A B C D E 4]EP3FSO 43 21.50 19.50 15.51 3.65 4fEP3F48A 57.90 4TEP3F63A 62.75 26 24 27.12 19.50 15.57 4TEP3FIS,4TEP3F24 45 4TEP3F42 51.75 4TEP3F63B 57.90 FLOW CONTROL 23.50 23.50 21.50 21.50 18.33 30.47 LIO. LINE BRAZE H 5.1! 3.62 1.89 3/4 5/}6 5.90 8.02 3.21 1.48 11/8 5/8 I/2 I/4 3,65 5,77 3.62 1.89 5/8 5/16 TXV/NB 21.50 GAS LINE BRAZE G 43 4]EPSF36 4TEP3F48, F 4.65 4.65 6.77 6.77 3.62 3,62 1.89 5/4 1,89 I-I/8 5/8 From Dwg. 21D8OO664 Rev. 18-GEO2D2-4 9 |nsta||er's Guide CAGE NUT MOUNTING iNSTRUCTiON FOR 4TEP3F AiR HANDLERS 1.50 H B A 19.50 * FOR 4TEP3F63B WITH TWO PIECE CABINET ONLY. _".50 Model No. H W A B f 4TEP3F18A 4TE P3 F24A 1.00 21.00 43.00 21.50 17.00 39.00 4TEP3F36A 45.00 21.50 19.00 41.00 4TEP3F42A 51.75 23.50 23.80 47.75 4TEP3F48A 57.90 26.00 29.00 53.90 4TEP3F63A 62.75 26.00 31.20 58.75 4TEP3F48B 57.90 23.50 31.20 58.75 4TEP3F63B 57.90 23.50 31.20 58.75 W 4TEP3F30A From Dwg. 21 B800400 Rev. 1 10 18-GE02D2-4 |nsta||er's Guide NOTES 18-GEO2D2-4 11 |nsta||er's Guide CHECKOUTPROCEDURES After installation checklist. has been completed, it is recommended !. Make sure power is "OFF" at power disconnect switch ................................................... that the Air Handler 6. [ ] be checked against the following Make sure secondary drain pan is installed .......... [ 7. Check power supply for correct requirements per unit nameplate ................................................ 2. Check all field wiring for tight connections. See that grounding of unit is in accord with code ........ [ ] 3. Make sure unit suspension (if used) is secure and that there are no tools or loose debris in, around or on top of the unit ................................... [ ] 4. Check all duct outlets; they must be open and unrestricted ..................................................... [ ] !0. Instruct owner, engineer (if possible) on proper 5. Check drain lines and be sure all joints are tight .................................................. [ ] operating procedure and leave Use and Care Manual with owner ................................................ ] [ ] [ ] 9. Energize the system and carefully observe its operation; make any necessary adjustment .......... [ ] 8. Check filters for proper size. Inform owner of proper procedure for removal and reinstallation ......................................................... [ ] SUPPLEMENTARY HEATERS CHECKOUT PROCEDURES, iF USED DOES HEATER REQUIRE A SPECIAL CiRCUiT? SEE "LiMiTATiONS AND RECOMMENDATIONS" !. Be sure the disconnect switch is "OFF", and safety label (if any) is attached 2. Check on field wiring for tight connections 3. Check circuit protection and grounding for proper size per nameplate ............................................... [ ] according to codes ............................................. [ ] [ ] [ ] specifications ........................................................... 4. Check control box panel -- in place and secured ........................................................................................... NOTE: OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL SYSTEM. American Standard Inc. 6200 Troup Highway Tyler, TX 75711 For more information contact your loca! dealer(distributor) 8/04 Since the manufacturer has a policy of continuous product and product data improvement, to change design and specifications without notice. it reserves the right
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 12 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Wed May 20 04:15:36 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools