TRANE Air Conditioner/heat Pump(outside Unit) Manual L0905062
User Manual: TRANE TRANE Air conditioner/heat pump(outside unit) Manual TRANE Air conditioner/heat pump(outside unit) Owner's Manual, TRANE Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
18=AC51D6=1 iiI!;!l!i i !I! i iI:i Condensing Units 4TTR4A/B ALL phases of this installation IMPORTANT -- This Document pack upon completion of work. must comply is customer with Models NATIONAL, property STATE and is to remain These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Should further information be desired or should particular problems arise which are not covered sufiieiently for the purchaser's purposes, the matter should be referred to your installing dealer or local distributor. A. GENERAL AND LOCAL with this unit. CODES Please return to service information UNiT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE TO USE PROPER SERVICE TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR PERSONAL INJURY. SERVICE This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and or property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use. The following instructions cover 4TFR4 Condensing USE ONLY R-410A REFRIGERANT APPROVED POE COMPRESSOR © 5 FT. ABOVE AND OIL. UNiT -- UNRESTRICTED Units. NOTE: These outdoor units are designed to be installed with approved/matched Trane indoor systems. These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a "Rose" color to indicate the type of refrigerant and may contain a "dip" tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this "hygroscopic" action, the system should remain sealed whenever possible. Never break a vacuum with air and always change the driers when opening the system for component replacement. Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit. To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power available must agree with that listed on the nameplate. B. LOCATION AND PREPARATION OF THE UNiT 1. When removing unit from the pallet, notice the tabs on the basepan. Remove tabs by cutting with a sharp tool as shown in Figure 2 (see page 2). 2. The unit should be set on a level support pad at least as large as the unit base pan, such as a concrete slab. If this is not the application used please refer to application bulletin "Trane XR-APG**-EN". (*denotes latest revision number) |nstaI|er's @ Guide NOTE: Attach R-410A CAUTION Label (located in documentation package) to access panel of indoor section. BASEPAN TAB REMOVAL IMPORTANT: The outdoor unit is shipped with the proper size orifice and a stick-on orifice size label in an envelope attached to the outdoor unit. Outdoor unit nameplate will have correct orifice size specified as BA YFCCV---A for rated pefformance. 3. The support pad must NOT be in direct contact with any structure. Unit must be positioned a minimum of 12" from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in ff'ont of control box (access panels) & any other side requiring service access to meet National Electrical Code. Also, the unit location must be fhr enough away from any structure to prevent excess roof run-off water from pouring directly on the unit. Do not locate unit(s) close to bedroom(s). 4. The top discharge area must be unrestricted five (5) feet above the unit. fbr at least 5. When the outdoor unit is mounted on a roof! be sure the roof will support the unit's weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure. 6. The maximum length of refrigerant lines ff'om outdoor indoor unit should NOT exceed sixty (60) feet. 7. If outdoor unit is mounted above mum lift should not exceed sixty If air handler is mounted above mmn lift should not exceed sixty NOTE: Refer to "Refrigerant the air handler, maxi(60) feet (suction line). condensing unit, maxi(60) feet (liquid line). Piping Software" Pub. No. 32-3312-02. 8. Locate and install indoor coil or air handler in accordance with instruction included with that unit. C. ACCUTRON to TM FLOW CONTROL VALVE If the indoor unit System Refrigerant Flow control is an Aecutron TM orifice and check valve assembly, an orifice size change may be necessary. The outdoor model determines the required orifice size. Check the listed orifice size on nameplate of the selected outdoor model. If the indoor unit is fhctory shipped with a diffbrent orifice size, the orifice must be changed to obtain system rated perfbrmance. D. iNSTALLiNG If using existing refrigerant are brazed, not soldered. Condensing units TYPE iNDOOR END SEALING CAP LINES lines make certain that all joints have provisions for braze connections. Pressure taps are provided on the service valves of outdoor unit fbr compressor suction and liquid pressures. The indoor end of the recommended refrigerant line sets may be straight or with a 90 degree bend, depending upon situation requirements. This should be thoroughly checked out befbre ordering refrigerant line sets. The gas line must always be insulated. in scroll compressor applications, dome temperatures may be hot. Do not touch top of compressor, may cause minor to severe burning. The units are fhctory charged with the system charge required when using fifteen (15) feet of connecting line. nameplate charge is the same. Final refrigerant charge adjustment is necessary. the Charging Charts in the outdoor unit Service Facts. 1. Determine 2. Consider the most practical Unit Use way to run the lines. types of bends to be made and space limitations. NOTE: Large diameter tubing has been shaped. will be very difficult to rebend once it 3. Determine the best starting point for routing the refrigerant tubing -- INSIDE OR OUTSIDE THE STRUCTURE. 4. Provide a pull-thru hole of sufficient liquid and gas lines. 5. Be sure the tubing 6. Uncoil the tubing BRAZE REFRIGERANT is of sufficient size to allow both length. -- do not kink or dent. 7. Route the tubing making all required bends and properly secure the tubing betbre making connections. 8. To prevent a noise within the building structure due to vibration transmission from the reff'igerant lines, the tbllowing precautions should be taken: a. When the refrigerant lines have to be thstened to floor joists or other ff'aming in a structure, use isolation type hangers. b. Isolation hangers should also be used when reff'igerant lines are run in stud spaces or enclosed ceilings. c. Where the reff'igerant lines run through they should be insulated and isolated. d. Isolate the lines from all ductwork. © 2008 American Standard Heating & Air Conditioning a wall or sill, 18-AC51 D6-1 |nsta||er's Guide LEAK CHECK © LiQUiD LiNE SERVICE VALVE ROLLED CAP KF'_.._ / _ PORT iMPORTANT: Replace pressure tap port valve core before attaching hoses for evacuation. TO / CAPTIVATE STEM sE.%"Ic" s,DE oF SERVICE EDGE After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the indoor unit and field refrigerant lines with dry nitrogen to 350-400 psi. Use soap bubbles or other leak-checking methods to see that all field joints are leak-fi'ee! If not, release pressure; then repair! SYSTEM EVACUATION .EX RE%% k_,Y / -- / LIQUID LINE CONNECTION E. SERVICE VALVE OPERATION BRASS LIQUID LINE SERVICE VALVE The Brass Liquid Line Service Valve is thetory shipped in the seated position to hold thctory charge. The pressure tap service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position. The liquid line valve is not a back seating valve (see WARNING below). Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. (See Figure 4) No torque is required. BRASS GAS LINE SERVICE VALVE The Brass Gas Line Service Valve is shipped in the closed position to hold the rectory refrigerant charge. The pressure tap service port (when depressed) opens only to the field brazing side when the valve is in the closed position. The Gas Line Service Valve is full open with a 1/4 turn. See Figure 5. BRAZING REFRIGERANT LINES 1. Remove lower access cover to access service valves. 2. Before brazing, remove plugs from external copper stub tubes. Clean internal and external surIhces of stub tubes prior to brazing. 3. Cut and fit tubing, minimizing 90 ° bends. 4. Insulate the entire the use of sharp gas line and its fittings. 5. Do NOT allow uninsulated contact with bare gas line. 6. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body. 1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves. 2. Attach appropriate hoses from manifold and liquid line pressure taps. 3. Attach center hose of manifold 4. Evacuate until the micron 350 microns. gauges 7. Use a Dry Nitrogen Puige and Brazing Alloy without flux when brazing the field line to the copper thctory connection. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing. 18-AC51 D6-1 pump. than 6. If vacuum gauge does not rise above 500 microns one (1) minute, the evacuation should be complete. in 7. With vacuum pump and micron gauge blanked off, open valve on R-410A cylinder and charge refrigerant lines and indoor coil with vapor to tank pressure of R-410A supply. 8. Close valve on R-410A supply cylinder. Close valves on manifold gauge set and remove refioigerant charging hoses from liquid and gas pressure tap ports. @ GAS LiNE SERVICE VALVE ,%,%,27L, _..... FOR FULL oP VALVE techniques. no higher 5. Close offvalve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one (1) minute, then evacuation is incomplete or system has a leak. UN,T S,OE /!_ good brazing to vacuum gauge reads tap NOTICE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the baeepan. 8. Braze using accepted gauge to gas NOTE: Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of R-410A and vacuum pump. c,P_ enters pressure charge, the gas and NOTE: DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE. liquid line to come in direct NOTICE: Use care to make sure that no moisture port, while wet rag is being used. NOTE: Since the outdoor unit has a refrigerant liquid line valves must remain closed. TM PRESSURE TAP PORT /# / GAS LINE CONNECTION OPEN |nsta||er's Guide NOTE: A 3/16" Allen wrench is required to open liquid line service valve. A I/4" Open End or Adjustable wrench is required to open gas line valve. A 3/4" Open End wrench is required to take off the valve stem cap. 9. The liquid line shut-offvalve can now be opened. Remove shut-off valve cap. Fully insert hex wrench into the stem and backout counterclockwise until valve stem just touches rolled edge (approximately five [5] turns) observing WARNING statement on page 3. See Figure 4. 10. Replace liquid service pressure tap port cap and valve stem cap. These caps MUST BE REPLACED to prevent leaks. Replace valve stein cap and pressure tap cap finger tight, then tighten an additional 1/6 turn. 11. The gas valve can now be opened. Open the gas valve by removing the shut-off valve cap and turning the valve stem 1/4 turn eounterelockwise, using 1/4" Open End or Adjustable wrench. See Figure 5. 12. The gas valve is now open for refl'igerant flow. Replace valve stem cap to prevent leaks. Again, these caps MUST BE REPLACED to prevent leaks. Replace valve stem cap and pressure tap cap finger tight, then tighten an additional 1/6 turn. See Figure 5. If refl'igerant lines are longer than 15 feet and!or a diff>rent size than recommended, it will be necessary to adjust system refl'igerant charge upon completion of installation. See unit Service Facts. F. ELECTRICAL When installing or servicing this equipment, ALWAYS exercise basic safety precautions to avoid the possibility of electric shock. of equipment 2. Power supply must agree with equipment 3. Install 4. Ground a separate the outdoor disconnect must comply nameplate. switch at the outdoor unit. unit per local code requirements. 5. Provide flexible electrical conduit whenever vibration transmission may create a noise problem within the structure. 6. The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the thermostat and the indoor unit. Table I -- NEC Class II Control Wiring START UP H. OPERATIONAL AND CHECKOUT PROCEDURES Final phases of' this installation are the unit Operational and Checkout Procedures which are found in this instruction (see page 8). To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts. I. ELECTRIC HEATERS Electric heaters, if used, are to be installed in the air handling device according to the instructions accompanying the air handler and the heaters. d. START CONTROL Some models have quick start components which are fhctory installed. For models that do not have fhctory installed start components, provisions are made for a field installed start kit accessory. When adding an accessory, follow the instructions provided with the kit. K. OUTDOOR CONNECTIONS 1. Power wiring and _'ounding with local codes. G. COMPRESSOR After all electrical wiring is complete, SET THE THERMOSTAT SYSTEM SWITCH IN THE OFF POSITION SO COMPRESSOR WILL NOT RUN, and apply power by closing the system main disconnect switch. This will activate the compressor sump heat (where used). Do not change the Thermostat System Switch until power has been applied for one (1) hour. Following this procedure will prevent potential compressor overload trip at the initial start-up. THERMOSTAT An outdoor thermostat TAYSTAT250B may be field installed. For data, see wiring diagram attached to unit and instruction sheet packaged with outdoor thermostat. L. SEACOAST SHIELD Units installed within one mile of salt water, including seacoasts and inland waterways, require the addition of BAYSEAC001 (Seacoast Kit) at the time of installation. IMPORTANT: See Limited Warranty information in Use and Care Manual M. TROUBLESHOOTING TROUBLESHOOTING CHART -- WHAT TO CHECK SYSTEMFAULTS REFRIGERANT CIRCUIT 24 VOLTS WIRE SIZE MAX. WIRE LENGTH 18 AWG 150 FT 16 AWG 225 FT. 14 AWG 300 FT. ELECTRICAL Compressor &OD FanDoNotStart Compressor WillNotStartButOD FanRuns OD FanWon'tStart 7. Table 1 defines maximum tota! length of low voltage wiring from outdoor unit, to indoor unit, and to thermostat. 8. Mount the indoor thermostat in accordance with instruction included with the thermostat. Wire per appropriate hook-up diagram (included in these instructions). 4 Compressor Nt_ms ButWon'tStart Compressor CyclesonIOL ID Blower Won'tStart P PrimaryCauses S Sec0ndaryCauses 18-AC51 D6-1 |nsta||er's TYPICAL T'STAT IR HANDLER AI Guide FIELD HOOK=UP DIAGRAMS CONDITIONER VARIABLE SPEED AIR HANDLER T'STAT AIR CONDITIONER ...... R ...... y _"= === y F_q ODT 0DT A FTq ...... Wl 1233 ISTq JoP_,O ...... o_ i _ ...... B '"B PRINTEDFROM B152901P02 PRINTED FROMBI52gosP03 ÷ CONNECTIONS TO BE MADE FOR OPERATION OF BLOWERWITH HUMIDISTAT IN COOLING T 'STAT I -STAGE OR 2-STAGE FURNACE Fq E3 E3 E3 AI CONDITIONER VARIABLE SPEED 2 STAGE FURNACE T 'STAT i-tS]] _. ..... y Frl [] Fq E3 F8 Fq _-.-y Fq Fq NOTE CONDITIONER r_ Fcl E3 AI prl E] E3 ...... B PRINTEDFROMB152903P02 ] NOTE Fq Fq -kW2 present only on 2 stage thermostat and furnace PRI NTE FRO BI52901P04 Notes: LEGEND 1. Be sure power supply agrees with equipment nameplate. 2. Power wiring and grounding of equipment must comply with local codes. 3. Low voltage wiring to be No. 18 AWG minimum conductor. 4. ODT-B must be set lower than ODT-A. ..... FACTORY WIRING 5. If outdoor thermostats _ FIELD WIRING 18-AC51 D6-1 (ODT) are not used, connect W1 to W2 and W3. 5 |nstaller's Guide 4TTR4 OUTLINE DRAWING NOTE: ALL DIMENSIONS ARE IN MM (INCHES). c SERVICE PANEL.................... ELECTRICAL AND REFRIGERANT COMPONENTCLEARANCES PER PREVAILING CODES TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 1524 {5 FEET) ABOVE UNIT UNIT SHOULDBE PLACED SO ROOF RUN OFF WATER DOEB NOT POUR DIRECTLY ON UNIT, AND SHOULDBE AT LEAST 305 {IR"/ FROM WALL AND ALL SURROUNDINGSHRUBBERYON TWOSIDES OTHER TWOSIDES UNRESTRICTED IbI' _ , //./I \ _ k_\ K ELECTRICAL SERVICE -_ PANEL 222 222 (7/8) DIA LOW VOLTAGE 286 (I I/8) DIA KO (7/8) DIA HOLE IN CONTROL BOX BOTTOM FOR ELECTRICAL POWERSUPPLY LIOUID LINE SERVICE VALVE IIEII ID FEMALE BRAZE CONNECTIONWITH I/4 II SAE FLARE PRESSURETAP FITTINGS FIG.1 FOR _} 6 FIG. ALTERNATE ELECTRICAL ROUTING AS LINE I/4 TURN BALL SERVICE VALVE, ID FEMALE BRAZED CONNECTION WITH I/4" FLARE PRESSURE TAP FITTING "D" SAE MODELS BASE A B C D E F G H 4TTR4018B 3 1 832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 1/2 1/4 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) J 508 (20) K 4TTR4024B 3 1 832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 5/8 5/16 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20) 4TTR4030A 3 1 832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 3/4 5/16 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20) 4TTR4036A 3 1 933 (36-3/4) 829 (32-5/8) 756 (29-3/4) 3/4 3/8 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20) 4TTR4042A 4 1 943 (37-1/8) 946 (37-1/4) 870 (34-1/4) 3/4 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 4TTR4048A 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 4TTR4060B 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 18-AC51 D6-1 Insialler's MOUNTING Guide HOLE LOCATION NOTE: ALL DIMENSIONS ARE IN MM (INCHES). 294 (11 56)_ 1 Ill (6 14) 4 PLACES DRILL (2709) 335 (1319) 221 (8,69) 310 (12 20)_ 158 (624) f _I)RILL 4 PLACES 9' (31 s_8) 717 (2824) NOTE: For model base size, see table on page 6. '99 ' BASE 4 18-AC51 D6-1 (23 bS) ( 2 {i 6 'i ) From Dwg. D152637 Rev. 1 7 |nsta||er's Guide CHECKOUT After installation has 1. Refrigerant 2. Suction been completed, Line, Leak checked Lines and Fittings it is recommended that .................................. properly insulated PROCEDURE ........... 3. Have all Refi'igerant Lines been secured and isolated properly? ........................................................ the entire system be checked registers against the following and return _'illes list: [ ] 8. Supply [ ] unobstructed ................................................................ 9. Return air filter installed ............................................ open and [ [ ] ] [ ] 10. Thermostat thermometer is accurate. Check against a reliable thermometer. Adjust per instructions with thermostat ...................................... [ ] [ ] [ ] 4. Have passages through masonry been sealed? If mortar is used, prevent mortar from coming into direct contact with copper tubing ........................ [ ] 11. Is correct speed tap being used? 5. Verify tightness [ ] (Indoor blower motor) .................................................. 12. Operate complete system in each mode to insure safe operation ................................................... of all electrical connects ................... 6. Observe outdoor fhn during on cycle for clearance and smooth operation .................................................. [ 7. Indoor coil drain line drains freely. Pour water into drain pan .............................................................. [ CHECKOUT PROCEDURE WiTH MAiN P( )WER DISCONNECTS iNDOORTHERMOSTAT SWITCHSETTING Step No. 1 TO CHECK Sump Heat 2 IndoorFan Operation 3 CoolingOperation 4 CheckingPerformance & Charge Off @ Cool @ Heat COMPONENTOPERATION indoor Blower Runs Fan Switch Auto On X CLOSED (ON) Outdoor Fan Runs Compressor Runs X x X Ix Furnace Heat Comes On X X X @ Comp. Sump Heater X X I x I X X X x x X USE CHARTS ATTACHED TO O.D. UNIT 5 Heating@ 6 Informowner on howto operatesystem andwhat to expectof it. At the sametime deliverOwner'sUseand Care Booklet. @ Also set thermostat dial to call for cooling or heating as necessary. @ Check only necessary if heating unit is used for indoor section and wiring has been disturbed during installation of cooling equipment, @ When applicable. ARI Standard 210/240 UAC 05/08 1r]MN£ Trane www.trane.com Trane has a policy of continuous product and product data improvement design and specifications without notice. and it reserves the right to change
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 8 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Wed May 20 04:16:14 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools