TRANE Air Conditioner/heat Pump(outside Unit) Manual L0905062

User Manual: TRANE TRANE Air conditioner/heat pump(outside unit) Manual TRANE Air conditioner/heat pump(outside unit) Owner's Manual, TRANE Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadTRANE  Air Conditioner/heat Pump(outside Unit) Manual L0905062
Open PDF In BrowserView PDF
18=AC51D6=1

iiI!;!l!i
i !I!

i iI:i

Condensing Units
4TTR4A/B
ALL phases

of this installation

IMPORTANT
-- This Document
pack upon completion of work.

must

comply

is customer

with

Models

NATIONAL,

property

STATE

and is to remain

These instructions
do not cover all variations
in
systems
nor provide
for every possible
contingency
to
be met in connection
with installation.
All phases
of
this installation
must comply
with NATIONAL,
STATE
AND LOCAL CODES.
Should further information
be
desired or should particular
problems arise which are not
covered sufiieiently for the purchaser's
purposes, the matter
should be referred to your installing dealer or local distributor.

A. GENERAL

AND LOCAL

with this unit.

CODES
Please

return

to service information

UNiT CONTAINS R-410A REFRIGERANT!
R-410A OPERATING
PRESSURE
EXCEEDS THE
LIMIT OF R-22. PROPER SERVICE EQUIPMENT
IS
REQUIRED.
FAILURE TO USE PROPER SERVICE
TOOLS MAY RESULT IN EQUIPMENT
DAMAGE OR
PERSONAL
INJURY.

SERVICE
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical
experience. Any attempt to repair a central air conditioning
product may result in personal injury and or property
damage. The manufacturer or seller cannot be responsible
for the interpretation of this information, nor can it assume
any liability in connection with its use.
The following instructions

cover 4TFR4 Condensing

USE ONLY R-410A

REFRIGERANT

APPROVED POE COMPRESSOR

©

5 FT. ABOVE

AND

OIL.

UNiT -- UNRESTRICTED

Units.

NOTE:
These outdoor units are designed to be installed with
approved/matched Trane indoor systems.

These units use R-410A refrigerant which operates at 50 to
70% higher pressures than R-22. Use only R-410A approved
service equipment. Refrigerant cylinders are painted a
"Rose" color to indicate the type of refrigerant and may
contain a "dip" tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that
readily absorbs moisture from the atmosphere. To limit this
"hygroscopic"
action, the system should remain sealed
whenever possible. Never break a vacuum with air and
always change the driers when opening the system for
component replacement.
Check for transportation
damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.
To determine
the electrical power requirements
of the unit,
refer to the nameplate
of the unit. The electrical power
available must agree with that listed on the nameplate.

B. LOCATION AND PREPARATION
OF THE UNiT
1. When removing unit from the pallet, notice the tabs on
the basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2 (see page 2).
2. The unit should be set on a level support pad at least as
large as the unit base pan, such as a concrete slab. If this
is not the application
used please refer to application
bulletin "Trane XR-APG**-EN".
(*denotes latest
revision number)

|nstaI|er's

@

Guide
NOTE:
Attach R-410A CAUTION Label (located in documentation
package) to access panel of indoor section.

BASEPAN TAB REMOVAL

IMPORTANT:
The outdoor unit is shipped with the proper size orifice and a
stick-on orifice size label in an envelope attached to the outdoor
unit. Outdoor unit nameplate will have correct orifice size
specified as BA YFCCV---A for rated pefformance.

3. The support pad must NOT be in direct contact with any
structure.
Unit must be positioned a minimum of 12"
from any wall or surrounding
shrubbery to insure
adequate airflow. Clearance must be provided in ff'ont of
control box (access panels) & any other side requiring
service access to meet National Electrical Code. Also,
the unit location must be fhr enough away from any
structure
to prevent excess roof run-off water from
pouring directly on the unit. Do not locate unit(s) close
to bedroom(s).
4. The top discharge area must be unrestricted
five (5) feet above the unit.

fbr at least

5. When the outdoor unit is mounted on a roof! be sure the
roof will support the unit's weight. Properly selected
isolation is recommended
to prevent sound or vibration
transmission
to the building structure.
6. The maximum length of refrigerant
lines ff'om outdoor
indoor unit should NOT exceed sixty (60) feet.
7. If outdoor unit is mounted above
mum lift should not exceed sixty
If air handler is mounted above
mmn lift should not exceed sixty
NOTE:
Refer to "Refrigerant

the air handler, maxi(60) feet (suction line).
condensing unit, maxi(60) feet (liquid line).

Piping Software" Pub. No. 32-3312-02.

8. Locate and install indoor coil or air handler in accordance with instruction
included with that unit.

C. ACCUTRON

to

TM

FLOW CONTROL

VALVE

If the indoor unit System Refrigerant
Flow control is an
Aecutron TM orifice and check valve assembly, an orifice size
change may be necessary.
The outdoor model determines
the required orifice size.
Check the listed orifice size on nameplate
of the selected
outdoor model. If the indoor unit is fhctory shipped with a
diffbrent orifice size, the orifice must be changed to obtain
system rated perfbrmance.

D. iNSTALLiNG

If using existing refrigerant
are brazed, not soldered.
Condensing

units

TYPE iNDOOR

END

SEALING

CAP

LINES

lines make certain that all joints

have provisions

for braze connections.

Pressure taps are provided on the service valves of outdoor
unit fbr compressor suction and liquid pressures.
The indoor end of the recommended
refrigerant
line sets may
be straight or with a 90 degree bend, depending upon situation requirements.
This should be thoroughly checked out
befbre ordering refrigerant
line sets.
The gas line must always

be insulated.

in scroll compressor applications, dome temperatures may
be hot. Do not touch top of compressor, may cause minor
to severe burning.
The units are fhctory charged with the system charge
required when using fifteen (15) feet of connecting line.
nameplate
charge is the same.
Final refrigerant
charge
adjustment
is necessary.
the Charging Charts in the outdoor unit Service Facts.
1. Determine
2. Consider

the most practical

Unit
Use

way to run the lines.

types of bends to be made and space limitations.

NOTE:
Large diameter tubing
has been shaped.

will be very difficult

to rebend once it

3. Determine the best starting point for routing the refrigerant tubing -- INSIDE OR OUTSIDE THE STRUCTURE.
4. Provide a pull-thru hole of sufficient
liquid and gas lines.
5. Be sure the tubing
6. Uncoil the tubing

BRAZE

REFRIGERANT

is of sufficient

size to allow both

length.

-- do not kink or dent.

7. Route the tubing making all required bends and properly
secure the tubing betbre making connections.
8. To prevent a noise within the building structure
due to
vibration transmission
from the reff'igerant lines, the
tbllowing precautions
should be taken:
a. When the refrigerant
lines have to be thstened to floor
joists or other ff'aming in a structure,
use isolation
type hangers.
b. Isolation hangers should also be used when reff'igerant lines are run in stud spaces or enclosed ceilings.
c. Where the reff'igerant lines run through
they should be insulated and isolated.
d. Isolate the lines from all ductwork.

© 2008 American Standard Heating & Air Conditioning

a wall or sill,

18-AC51

D6-1

|nsta||er's

Guide

LEAK CHECK

©

LiQUiD

LiNE SERVICE

VALVE
ROLLED

CAP

KF'_.._ /

_

PORT

iMPORTANT:
Replace pressure tap port valve core before attaching hoses
for evacuation.

TO

/ CAPTIVATE
STEM

sE.%"Ic"
s,DE
oF

SERVICE

EDGE

After the brazing operation of refrigerant
lines to both the
outdoor and indoor unit is completed, the field brazed
connections must be checked for leaks. Pressurize
through
the service valve ports, the indoor unit and field refrigerant
lines with dry nitrogen to 350-400 psi. Use soap bubbles or
other leak-checking
methods to see that all field joints are
leak-fi'ee! If not, release
pressure;
then repair!
SYSTEM EVACUATION

.EX
RE%%

k_,Y

/

--

/

LIQUID LINE
CONNECTION

E. SERVICE

VALVE OPERATION

BRASS LIQUID LINE SERVICE VALVE
The Brass Liquid Line Service Valve is thetory shipped in the
seated position to hold thctory charge. The pressure tap
service port (when depressed) opens only to the field brazing
side of the valve when the valve is in the seated position.
The liquid line valve is not a back seating valve (see
WARNING
below).

Extreme caution should be exercised when opening the
Liquid Line Service Valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. (See
Figure 4) No torque is required.
BRASS GAS LINE SERVICE VALVE
The Brass Gas Line Service Valve is shipped in the closed
position to hold the rectory refrigerant
charge. The pressure
tap service port (when depressed) opens only to the field
brazing side when the valve is in the closed position. The Gas
Line Service Valve is full open with a 1/4 turn. See Figure 5.
BRAZING REFRIGERANT LINES
1. Remove lower access cover to access service valves.
2. Before brazing, remove plugs from external copper stub
tubes. Clean internal and external surIhces of stub
tubes prior to brazing.
3. Cut and fit tubing, minimizing
90 ° bends.
4. Insulate

the entire

the use of sharp

gas line and its fittings.

5. Do NOT allow uninsulated
contact with bare gas line.

6. Precautions
should be taken to avoid heat damage
to the pressure
tap valve core during
brazing.
It is
recommended
that the pressure
tap port valve
core be removed
and a wet rag wrapped
around
the valve body.

1. Upon completion of leak check, evacuate the refrigerant
lines and indoor coil before opening the gas and liquid
line valves.
2. Attach appropriate
hoses from manifold
and liquid line pressure taps.

3. Attach

center

hose of manifold

4. Evacuate until the micron
350 microns.

gauges

7. Use a Dry Nitrogen Puige and Brazing Alloy without flux
when brazing the field line to the copper thctory connection. Flow dry nitrogen into either valve pressure tap
port, thru the tubing and out the other port while brazing.

18-AC51 D6-1

pump.
than

6. If vacuum gauge does not rise above 500 microns
one (1) minute, the evacuation should be complete.

in

7. With vacuum pump and micron gauge blanked off, open
valve on R-410A cylinder and charge refrigerant
lines and
indoor coil with vapor to tank pressure of R-410A supply.

8. Close valve on R-410A supply cylinder. Close valves on
manifold gauge set and remove refioigerant charging
hoses from liquid and gas pressure tap ports.

@

GAS LiNE SERVICE

VALVE
,%,%,27L,
_.....
FOR

FULL

oP VALVE

techniques.

no higher

5. Close offvalve to vacuum pump and observe the micron
gauge. If gauge pressure rises above 500 microns in one (1)
minute, then evacuation is incomplete or system has a leak.

UN,T
S,OE
/!_

good brazing

to vacuum

gauge reads

tap

NOTICE:
Precautions should be taken to avoid heat damage to
basepan during brazing. It is recommended to keep the
flame directly off of the baeepan.

8. Braze using accepted

gauge to gas

NOTE:
Unnecessary switching of hoses can be avoided and
complete evacuation of all lines leading to sealed system
can be accomplished
with manifold center hose and
connecting branch hose to a cylinder of R-410A and
vacuum pump.

c,P_
enters pressure

charge, the gas and

NOTE:
DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.

liquid line to come in direct

NOTICE:
Use care to make sure that no moisture
port, while wet rag is being used.

NOTE:
Since the outdoor unit has a refrigerant
liquid line valves must remain closed.

TM

PRESSURE TAP PORT

/#

/
GAS

LINE

CONNECTION

OPEN

|nsta||er's

Guide

NOTE:
A 3/16" Allen wrench is required to open liquid line service
valve. A I/4" Open End or Adjustable wrench is required to
open gas line valve. A 3/4" Open End wrench is required to
take off the valve stem cap.
9. The liquid line shut-offvalve
can now be opened. Remove
shut-off valve cap. Fully insert hex wrench into the stem
and backout counterclockwise
until valve stem just touches
rolled edge (approximately
five [5] turns) observing
WARNING
statement
on page 3. See Figure 4.
10. Replace liquid service pressure tap port cap and valve
stem cap. These caps MUST BE REPLACED
to
prevent leaks. Replace valve stein cap and pressure tap
cap finger tight, then tighten an additional
1/6 turn.
11. The gas valve can now be opened. Open the gas valve by
removing the shut-off valve cap and turning the valve
stem 1/4 turn eounterelockwise,
using 1/4" Open End or
Adjustable wrench. See Figure 5.
12. The gas valve is now open for refl'igerant flow. Replace
valve stem cap to prevent leaks. Again, these caps
MUST BE REPLACED
to prevent leaks. Replace valve
stem cap and pressure tap cap finger tight, then tighten
an additional 1/6 turn. See Figure 5.
If refl'igerant lines are longer than 15 feet and!or a
diff>rent size than recommended,
it will be necessary to
adjust system refl'igerant
charge upon completion of
installation.
See unit Service Facts.

F. ELECTRICAL

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility of
electric shock.
of equipment

2. Power supply must agree with equipment
3. Install
4. Ground

a separate
the outdoor

disconnect

must

comply

nameplate.

switch at the outdoor

unit.

unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration
transmission
may create a noise problem within the
structure.
6. The use of color coded low voltage wire is recommended
to simplify connections between the outdoor unit, the
thermostat
and the indoor unit.
Table I -- NEC Class II Control

Wiring

START UP

H. OPERATIONAL
AND
CHECKOUT PROCEDURES
Final phases of' this installation
are the unit Operational
and
Checkout Procedures which are found in this instruction
(see
page 8). To obtain proper performance,
all units must be
operated and charge adjustments
made in accordance with
procedures found in the Service Facts.

I. ELECTRIC

HEATERS

Electric heaters, if used, are to be installed in the air handling device according to the instructions
accompanying
the
air handler and the heaters.

d. START CONTROL
Some models have quick start components which are fhctory
installed. For models that do not have fhctory installed start
components,
provisions are made for a field installed start kit
accessory. When adding an accessory, follow the instructions
provided with the kit.

K. OUTDOOR

CONNECTIONS

1. Power wiring and _'ounding
with local codes.

G. COMPRESSOR

After all electrical wiring is complete, SET THE THERMOSTAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR
WILL NOT RUN, and apply power by
closing the system main disconnect switch. This will activate
the compressor sump heat (where used). Do not change the
Thermostat
System Switch until power has been applied for
one (1) hour. Following this procedure will prevent potential
compressor overload trip at the initial start-up.

THERMOSTAT

An outdoor thermostat
TAYSTAT250B may be field installed.
For data, see wiring diagram attached to unit and instruction
sheet packaged with outdoor thermostat.

L. SEACOAST

SHIELD

Units installed within one mile of salt water, including
seacoasts and inland waterways,
require the addition of
BAYSEAC001 (Seacoast Kit) at the time of installation.
IMPORTANT:
See Limited Warranty information in Use and Care Manual

M. TROUBLESHOOTING
TROUBLESHOOTING

CHART -- WHAT TO CHECK

SYSTEMFAULTS

REFRIGERANT
CIRCUIT

24 VOLTS
WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

ELECTRICAL
Compressor
&OD FanDoNotStart
Compressor
WillNotStartButOD FanRuns
OD FanWon'tStart

7. Table 1 defines maximum tota! length of low voltage
wiring from outdoor unit, to indoor unit, and to thermostat.
8. Mount the indoor thermostat
in accordance with instruction included with the thermostat.
Wire per appropriate
hook-up diagram (included in these instructions).

4

Compressor
Nt_ms
ButWon'tStart
Compressor
CyclesonIOL
ID Blower
Won'tStart
P PrimaryCauses S Sec0ndaryCauses

18-AC51 D6-1

|nsta||er's
TYPICAL
T'STAT

IR HANDLER

AI

Guide

FIELD HOOK=UP DIAGRAMS
CONDITIONER

VARIABLE
SPEED
AIR HANDLER

T'STAT

AIR

CONDITIONER

...... R

...... y

_"=

=== y

F_q

ODT

0DT

A

FTq

...... Wl

1233
ISTq

JoP_,O
...... o_ i

_ ...... B
'"B
PRINTEDFROM B152901P02
PRINTED FROMBI52gosP03
÷ CONNECTIONS TO BE MADE FOR OPERATION OF
BLOWERWITH HUMIDISTAT IN COOLING

T 'STAT

I -STAGE
OR
2-STAGE
FURNACE

Fq

E3

E3

E3

AI

CONDITIONER

VARIABLE SPEED
2 STAGE FURNACE

T 'STAT

i-tS]]
_. ..... y

Frl
[]

Fq

E3

F8

Fq

_-.-y

Fq

Fq

NOTE

CONDITIONER

r_

Fcl
E3

AI

prl
E]

E3
...... B

PRINTEDFROMB152903P02

]

NOTE

Fq

Fq

-kW2 present only on 2 stage
thermostat and furnace

PRI NTE

FRO

BI52901P04

Notes:

LEGEND

1. Be sure power supply agrees with equipment nameplate.
2. Power wiring and grounding of equipment must comply with local codes.
3. Low voltage wiring to be No. 18 AWG minimum conductor.
4. ODT-B must be set lower than ODT-A.

.....

FACTORY WIRING

5. If outdoor thermostats

_

FIELD WIRING

18-AC51 D6-1

(ODT) are not used, connect W1 to W2 and W3.

5

|nstaller's

Guide
4TTR4 OUTLINE

DRAWING

NOTE: ALL DIMENSIONS ARE IN MM (INCHES).

c
SERVICE PANEL....................

ELECTRICAL AND REFRIGERANT
COMPONENTCLEARANCES
PER PREVAILING CODES

TOP DISCHARGE AREA SHOULD BE
UNRESTRICTED FOR AT LEAST 1524 {5 FEET)
ABOVE UNIT UNIT SHOULDBE PLACED SO ROOF
RUN OFF WATER DOEB NOT POUR DIRECTLY ON UNIT,
AND SHOULDBE AT LEAST 305 {IR"/
FROM WALL AND
ALL SURROUNDINGSHRUBBERYON TWOSIDES
OTHER TWOSIDES UNRESTRICTED

IbI'

_

,

//./I

\ _ k_\

K
ELECTRICAL SERVICE -_
PANEL

222

222

(7/8)

DIA
LOW VOLTAGE

286
(I I/8)
DIA
KO
(7/8)
DIA
HOLE IN CONTROL
BOX BOTTOM FOR ELECTRICAL
POWERSUPPLY

LIOUID LINE SERVICE VALVE
IIEII ID
FEMALE BRAZE
CONNECTIONWITH I/4 II SAE
FLARE PRESSURETAP FITTINGS

FIG.1
FOR

_}

6

FIG.

ALTERNATE

ELECTRICAL
ROUTING
AS LINE
I/4
TURN BALL
SERVICE
VALVE,
ID
FEMALE BRAZED CONNECTION
WITH
I/4"
FLARE
PRESSURE TAP FITTING

"D"
SAE

MODELS

BASE

A

B

C

D

E

F

G

H

4TTR4018B

3

1

832 (32-3/4)

829 (32-5/8)

756 (29-3/4)

1/2

1/4

143 (5-5/8)

92 (3-5/8)

210 (8-1/4)

79 (3-1/8)

J

508 (20)

K

4TTR4024B

3

1

832 (32-3/4)

829 (32-5/8)

756 (29-3/4)

5/8

5/16

143 (5-5/8)

92 (3-5/8)

210 (8-1/4)

79 (3-1/8)

508 (20)

4TTR4030A

3

1

832 (32-3/4)

829 (32-5/8)

756 (29-3/4)

3/4

5/16

143 (5-5/8)

92 (3-5/8)

210 (8-1/4)

79 (3-1/8)

508 (20)

4TTR4036A

3

1

933 (36-3/4)

829 (32-5/8)

756 (29-3/4)

3/4

3/8

143 (5-5/8)

92 (3-5/8)

210 (8-1/4)

79 (3-1/8)

508 (20)

4TTR4042A

4

1

943 (37-1/8)

946 (37-1/4)

870 (34-1/4)

3/4

3/8

152 (6)

98 (3-7/8)

219 (8-5/8)

86 (3-3/8)

508 (20)

4TTR4048A

4

1

1045 (41-1/8)

946 (37-1/4)

870 (34-1/4)

7/8

3/8

152 (6)

98 (3-7/8)

219 (8-5/8)

86 (3-3/8)

508 (20)

4TTR4060B

4

1

1045 (41-1/8)

946 (37-1/4)

870 (34-1/4)

7/8

3/8

152 (6)

98 (3-7/8)

219 (8-5/8)

86 (3-3/8)

508 (20)

18-AC51 D6-1

Insialler's
MOUNTING

Guide

HOLE LOCATION

NOTE: ALL DIMENSIONS ARE IN MM (INCHES).

294 (11

56)_

1
Ill

(6

14)

4 PLACES
DRILL

(2709)

335

(1319)

221

(8,69)

310

(12

20)_

158 (624)

f

_I)RILL
4 PLACES

9'

(31 s_8)

717 (2824)

NOTE: For model base size,
see table on page 6.

'99

'

BASE 4
18-AC51 D6-1

(23

bS)

( 2 {i 6 'i )
From Dwg. D152637 Rev. 1

7

|nsta||er's

Guide
CHECKOUT

After

installation

has

1. Refrigerant
2. Suction

been

completed,

Line, Leak checked

Lines and Fittings

it is recommended

that

..................................

properly

insulated

PROCEDURE

...........

3. Have all Refi'igerant Lines been secured and
isolated properly? ........................................................

the

entire

system

be checked

registers

against

the following

and return

_'illes

list:

[

]

8. Supply

[

]

unobstructed
................................................................
9. Return air filter installed ............................................

open and
[
[

]
]

[

]

10. Thermostat
thermometer
is accurate. Check
against a reliable thermometer.
Adjust per
instructions
with thermostat
......................................

[

]

[

]

[

]

4. Have passages through masonry been sealed?
If mortar is used, prevent mortar from coming
into direct contact with copper tubing ........................

[

]

11. Is correct speed tap being used?

5. Verify tightness

[

]

(Indoor blower motor) ..................................................
12. Operate complete system in each mode to
insure safe operation ...................................................

of all electrical

connects

...................

6. Observe outdoor fhn during on cycle for clearance
and smooth operation ..................................................

[

7. Indoor coil drain line drains freely. Pour water
into drain pan ..............................................................

[

CHECKOUT

PROCEDURE

WiTH MAiN P( )WER DISCONNECTS

iNDOORTHERMOSTAT
SWITCHSETTING
Step
No.
1

TO CHECK
Sump Heat

2

IndoorFan Operation

3

CoolingOperation

4

CheckingPerformance
& Charge

Off

@
Cool

@
Heat

COMPONENTOPERATION
indoor
Blower
Runs

Fan Switch
Auto
On

X

CLOSED (ON)

Outdoor
Fan
Runs

Compressor
Runs

X

x

X

Ix

Furnace
Heat
Comes On

X
X

X

@ Comp.
Sump
Heater

X

X

I

x

I

X

X

X

x

x

X

USE CHARTS ATTACHED TO O.D. UNIT

5

Heating@

6

Informowner on howto operatesystem andwhat to expectof it. At the sametime deliverOwner'sUseand Care Booklet.

@ Also set thermostat dial to call for cooling or heating as necessary.
@ Check only necessary if heating unit is used for indoor section and wiring has been disturbed during installation of cooling equipment,
@ When applicable.

ARI Standard
210/240 UAC

05/08

1r]MN£
Trane
www.trane.com
Trane has a policy of continuous product and product data improvement
design and specifications without notice.

and it reserves the right to change



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 8
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Wed May 20 04:16:14 2009
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu