TRANE Furnace/Heater, Gas Manual L0905285
User Manual: TRANE TRANE Furnace/Heater, Gas Manual TRANE Furnace/Heater, Gas Owner's Manual, TRANE Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 24
Download | |
Open PDF In Browser | View PDF |
lUlIIIIIUU IIIIIIIIIIIII I IIIIIIIII 1 8- CD2 1 D1 - 4 High Efficiency Single Stage Upflow/Horizontal and Downflow/Horizontal Gas-Fired Furnaces, "Fan Assisted Combustion System" *UDIA040A9H21 *UDIB060A9H31 *UDIB080A9H31 *UDIC080A9H41 B B B B *UD1 B100A9H31 B *UDIC100A9H51 B *UD1 D120A9H51 B *UD1D140A9H51B *DD1 *DD1 *DD1 *DD1 B060A9H31B B080A9H31B C100A9H51B D120A9H51B *__First letter may be "A" or 'q-" ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES IMPORTANT -- This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work. For VENT SIZING INFORMATION see: USA -National Fuel Gas Code ............. ANSI Z223.1/NFPA 54 (latest version) CANADA -Natural Gas Installation Code ........... CAN/CGA-B149.1 Propane Installation Code ................. CAN/CGA-B149.2 USA/CANADA ALTERNATE -- Category I Venting Guide .................................. C (latest version) (latest version) Pub. No. 18-CH23D1-2 _ Upflow/Horizontal* Downflow/Horizontal* *Horizontal Conversion for these furnaces may be left or right side rotation. A341789P07 Installer's Guide SAFETY SECTION The following safety practices and precautions must be followed during the installation, servicing, and operation of this furnace. 1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate. 2. Install this furnace only in a location and position as specified in "Location and Clearances" (page 4), of these instructions. 3. Provide adequate combustion and ventilation air to the furnace space as specified in "Air for Combustion and Ventilation" (pages 8-9), of these instructions. 4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the "Venting" section (pages 1315), of these instructions. 5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in "Gas Piping" (page 618), of these instructions. 6. Always install the furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace. 7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. 8. A gas-fired furnace for installation in a residential garage must be installed as specified in "Location and Clearances" section (page 4), of these instructions. 9. The furnace may be used for temporary heating of buildings or structures under construction only when the following conditions have been met: a. The furnace venting system must be complete and installed per manufacturer's instructions. b. The furnace is controlled only by a room thermostat (no field jumpers). c. The furnace return air duct must be complete and sealed to the furnace and clean air filters are in place. d. The furnace input rate and temperature rise must be verified to be within nameplate marking. e. 100% of the furnace combustion air requirement must come from outside the structure. © 2008 Trane All Rights Reserved CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSIZ223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition. 4. Close fireplace dampers. 5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan. 6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously. 7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes. 8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use. £ The furnace return air temperature range is between 55 and 80 degrees Fahrenheit. g. Clean the furnace, duct work, and components upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions. This product must be gas 10. Massachusetts.Plumber or Gas Fitter piped in the by a Licensed Commonwealth 1 8-CD21 of D1-4 Installer's Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING, and CAUTION. a. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. b. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage. FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage. Guide Contents Installation Instructions General Installation Instructions Location and Clearances Outline Drawing Upflow Installation Downflow Installation Air For Combustion and Ventilation Duct Connections Return Air Filters Typical Upflow Return Air Filter Installations Alternate Upflow Filter Clip / Bracket Installation Typical Downflow Furnace Return Air Filter Installations General Venting Instructions Venting Into a Masonry Chimney Electrical Connections Field Wiring Diagrams Gas Piping Sequence of Operation Start Up and Adjustment Preliminary Inspections Combustion and Input Check High Altitude Derate Lighting Instructions Control and Safety Switch Adjustment IFC Error Flash Codes Abnormal Conditions To prevent shortening its service life, the furnace should not be used as a "Construction Heater" during the finishing phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger. These furnaces are not approved or intended for installation in manufactured (mobile) housing, trailers, or recreational vehicles. Failure to follow this warning could result in property damage, personal injury, or death. Do NOT install the furnace in a corrosive or contaminated atmosphere. 18-CD21 D1-4 3 Installer's GENERAL Guide INSTALLATION INSTRUCTIONS The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation. It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at Altitudes above 2000 ft., remember the gas input must be reduced (See GAS INPUT ADJUSTMENT). Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the delivering agency. Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as Fan Assisted Combustion system CATEGORY I furnaces as required by ANSI Z21.47 "latest edition" and CAN/CGA 2.3. Therefore they do not require any special provisions for venting other than what is indicated in these instructions. (Category I defined on page 14). These furnaces may be twinned. They shall have common returns with equal pressure drops or ducts with equivalent lengths and sizes. See Field Wiring Diagrams for Twinning on page 17 for proper hookup. 4 LOCATION AND CLEARANCES The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements: 1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical? 2. Do all clearances between the furnace and enclo- 3. 4. 5. 6. sure equal or exceed the minimums stated in Clearance Table on the Outline Drawings. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door or panel must permit removal of the largest component. Are there at least 3 inches of clearance between the furnace combustion air openings in the front panel and any dosed panel or door provided? Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow accumulation level? (See the Air for Combustion and Ventilation section.) Allow sufficient height in supply plenum above the furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this furnace installation. 7. A furnace shall be installed so electrical components are protected from water. 8. If the furnace is installed in a residential garage, it must be installed so that the burners, and the ignition source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid physical damage from vehicles. 18-CD21 D1-4 Installer's Guide ,q- > o z 1£ 09 8 i • . • , • • , • • ,__ _88S_ _o8 6_ C3 ii o co 7 S z S \ 7 z \ L_ _ C2:C _ CZC, 7 o_ + zz_ _o cO z_p< _V<_ , _9 b 7 o_ h _ < _, u b_.l " o" o. oo I 7 z_ •- _ << _ 7 <<<<<< <<<< [[Eft[[[[[[[[[ [[[[[[[[[[[ [ [ [. [[[[[[[[[[[ [ [ [ [[[[[[[[[[ [ [ [ [ o [[[[[[[[[[ [ [ [ [. [[[[[[[[[[[ [ [ [ xxx LLL _LL 18-CD21 D1-4 5 Installer's Guide 0 CC U.ll 09 oo uJI © n LL = r-u P __N 121 P = = = 1 1 -- = Z m __N i 121 = 121 __<_ < < 1 :: ::: w_ .... :-- 031"-- N _o, I:1 I:1 oo _ oo oooooooo _o_ooo ooo NN ooo _ NNNNNNNN w_JW NNN ,,_1.,_ .,_ N x _<<<<<<<<<<<<<< <<<<<<<<<<<<<< _.1L.l.L._. _E V'_CO NNNNNN< 5 ISOLATIO ; % '/. --LINE ] N O 'k_ FIELD /._ 24 SEE NOTE v. ----LINE il/'_' ] O_ ISUi_AT@/ '¢,i]RING _ M.) / FACTORY WIRING N RELAY (FIELD SUPPLIED) SEE NOTE 4 From Dwg 18-CD21 D1-4 21 B341423 Rev 2 17 Installer's Guide GAS PIPING FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or loss of life. @ LEFT SIDE PIPING (STANDARD) MANUAL MAIN SHUTOFF This unit is shipped standard for left side installation of gas piping. A piping knockout is also provided in the right side for an alternate piping arrangement. The installation of piping shall be in accordance with piping codes and the regulations of the local gas company. Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases. Refer to piping Table 9 for delivery sizes. Connect gas supply to the unit, using a ground joint union and a manual shut-off valve as shown in Figure 19. National codes require a condensation drip leg to be installed ahead of the controls as shown in Figure 19. The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. The furnace must be isolated from the gas supply piping by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. UNION JOINT DRIP LEG AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold assembly. RIGHT SIDE PIPING (OPTIONAL) i SHUTOFF VALVE NOTF" Maximum pressure to the gas valve for natural gas is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C. UNION JOINT All gas fittings must be checked for leaks using a soapy solution before lighting the furnace. DO NOT CHECK WITH AN OPEN FLAME! The following warning complies with State of California law, Proposition 65. AUTOMATIC GAS VALVE WiTH MANUAL _UTOFF Hazardous Gases! TOP VIEW OF RIGHT SIDE PIPING Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm. SEQUENCE OF OPERATION THERMOSTAT CALL FOR HEAT R and W thermostat contacts module to run its self-check TOP VIEW close signaling the control routine. After the control module has verified that the pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blower will be energized. TO PREVENT AN EXPLOSION OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE, DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS NEAR THE UNIT. 18 18-CD21 D1-4 Installer's As the induced draft blower comes up to speed, the pressure switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approx. 20 seconds, then the gas valve is energized to permit gas flow to the burners. The flame sensor confirms that ignition has been achieved within the 6 second ignition trial period. After the flame sensor confirms that ignition has been achieved, the delay fan ON period (fixed at 45 seconds) begins timing. After the delay of 45 seconds, the indoor blower motor will be energized and will continue to run during the heating cycle. When the thermostat is satisfied, R and W thermostat contacts open, the gas valve will close, the flames will extinguish, and the induced draft blower will be de-energized. The indoor blower motor will continue to run for the fan off period (fixed at 100 seconds), then will be de-energized by the control module. test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or loss of life. START-UP AND ADJUSTMENT PRELIMINARY INSPECTIONS With gas and electrical power "OFF" 1. Duct connections are properly sealed 2. Filters are in place 3. Venting is properly assembled 4. Blower door is in place Turn knob on main gas valve within the unit to the "OFF" position. Turn the external gas valve to "ON". Purge the air from the gas lines. After purging, check all gas connections for leaks with a soapy solution - DO NOT CHECK WITH AN OPEN FLAME. Allow 5 minutes for any gas that might have escaped to dissipate. LP Gas, being heavier than air, may require forced ventilation. Turn the knob on the gas valve in the unit to the "ON" position. COMBUSTION AND INPUT CHECK 1. Make sure all gas appliances are off except the furnace. 2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution. 3. Match the "Sec" column in the gas flow (in cfh) Table 12 with the time clocked. 4. Read the "Flow" column opposite onds clocked. 18-CD21 D1-4 the number Guide 5. Use the following factors if necessary: For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading For 1/2 Cu. Ft. Dial Gas Flow CFH = +2 Chart Flow Reading + 4 For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow Reading + 4 6. Multiply the final figure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the nameplate rating. 7.Changes can be made by adjusting the manifold pressure or changing orifices (orifice change may not always be required). To adjust the manifold pressure: a.Turn off all electrical power to the system. b.Attach a manifold pressure gauge to the outlet pressure tap marked "OUT PRESS TAP" on WhiteRodgers gas valve model 36F or boss marked "OUT P" on White-Rodgers gas valve model 36G. (See Figure 21) for White-Rodgers gas valve model 36F and Figure 20 for White-Rodgers gas valve model 36G). For the gas valve model 36F, measurement requires removal of the plug and installation of a barbed fitting. Attach flexible tubing and a manometer to the barbed fitting. For the gas valve model 36G, do not remove the pressure tap test screw. Using a 3/32" hex wrench, loosen the pressure tap test screw one turn and install 5/16" flexible tubing and a manometer directly onto the outlet pressure boss. c. Turn on system power and energize valve. d.Remove the regulator adjustment screw cap on the gas valve for manifold pressure adjustment. e.Turn the adjustment nut clockwise to increase the gas flow rate, and counterclockwise to decrease the gas flow rate using a 3/32" hex wench. f. The final manifold pressure setting shall be 3.5" W.C. with an input of no more than nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude. g.Replace the regulator adjustment screw cap and tighten securely. h.Turn off all electrical power to the system. i. Remove the manometer and flexible tubing. Remove the barbed fitting and replace the plug or tighten the pressure test screw. j. Turn on electrical power to the system and energize valve. k. Using a leak detection solution or soap suds, check for leaks at plug or pressure boss screw. of sec- 19 Installer's Guide HIGH ALTITUDE DEBATE Replace and/or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service. Failure to follow this warning could result in fire, explosion, or property damage. For LP gases, the final manifold pressure setting shall be 10.5" W.C. with an input of no more than the nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for altitude. Table 10 lists the main burner orifices shipped with the furnace. If a change of orifices is required to correct the input rate, refer to Table 11. TABLE 9 NATURAL GAS ONLY TABLE OF CUBIC FEET PER HOUR OF GAS FOR VARIOUS PIPE SIZES AND LENGTHS PIPE LENGTH OF PIPE SIZE 10 20 30 40 50 60 70 1_ 132 92 73 63 56 50 46 3_ 278 190 152 130 115 105 96 1 520 350 285 245 215 195 180 1-1_ 1050 730 590 520 440 400 370 Input ratings (BTUH) of these furnaces are based on sea level operation and should not be changed at elevations up to 2,000 ft. If the installation is 2,000 ft. or above, the furnace input rate (BTUH) shall be reduced 4% for each 1,000 ft. above sea level. The furnace input rate shall be checked by clocking the gas flow rate (CFH) and multiplying by the heating value obtained from the local utility supplier for the gas being delivered at the installed altitude. Input rate changes can be made by adjusting the manifold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas) or changing orifices (orifice change may not always be required). If the desired input rate cannot be achieved with a change in manifold pressure, then the orifices must be changed. LP installations will require an orifice change. Installation of this furnace at altitudes above 2,000 ft. (610m) shall be in accordance with local codes, the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 or National Standard of Canada, Natural Gas and Propane Installation Code, CSA B149.1. Installation of this furnace at altitudes above 2,000 ft. (610m) shall be made in accordance with the listed high Altitude Conversion Kit available with this furnace. This table is based on pressure drop of 0.3 inch W.C. and 0.6 SEGR. gas IMPORTANT: Re-install the propane orifices to the same depth as the orifices supplied with the equipment. TABLE 10 ORIFICE SIZES INPUT RATING BTUH NUMBER OF BURNERS 40,000 60,000 2 3 80,000 100,000 120,000 4 5 6 140,000 7 PART NUMBERS MAIN BURNER ORIFICE DRILL SIZE NAT. GAS LP GAS 45 45 45 56 56 56 45 45 56 56 45 56 TABLE 11 FOR REPLACEMENT See Table 13 for help in selecting orifices if orifice change is required. Furnace input rate and temperature rise should be checked again after changing oririces to confirm the proper rate for the altitude. Installations above 4,000 feet may require a pressure switch change. If required, use the BAYHALT*** Kit (High Altitude Accessory Kit) listed in PRODUCT DATA. ORIFICES DRILL SIZE PART NUMBER DRILL SIZE PART NUMBER 44 45 46 47 48 ORFO0501 0RF00644 ORFO0909 ORFO0910 0RF01099 54 55 56 57 58 49 50 ORFO0503 0RF00493 59 0RF00555 0RF00693 ORFO0907 ORFO0908 0RF01338 0RF01339 EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK. NOTE: The manufacturer of your furnace does NOT test any detectors and makes no representations regarding any brand or type of detector. 20 18-CD21 D1-4 Installer's TABLE 12 TABLE 13 GAS FLOW IN CUBIC FEET PER HOUR SEC. 8 9 10 11 FLOW 900 800 720 655 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 600 555 514 480 450 424 400 379 360 343 327 313 300 288 277 267 257 2 CUBIC FOOT DIAL SEC. FLOW SEC. FLOW 29 248 50 144 30 240 51 141 31 232 52 138 32 225 53 136 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 218 212 206 200 195 189 185 180 176 172 167 164 160 157 153 150 147 54 55 56 57 58 59 60 62 64 66 68 70 72 74 76 78 80 133 131 129 126 124 122 120 116 112 109 106 103 100 97 95 92 90 i_ii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii (_ Outlet Pressure Boss !!!!!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!!_ Inlet Pressure Boss (opt.) On/Off Switch White-Rod_ers 3613 Guide gas valve On/Off Switch SEC. 82 84 86 88 FLOW 88 86 84 82 90 92 94 96 98 100 104 108 112 116 120 124 128 132 136 140 144 80 78 76 75 73 72 69 67 64 62 60 58 56 54 53 51 50 Orifice Twist Drill Size If Installed At Sea Level ALTITUDE ABOVE SEA LEVEL and Orifice Required At Other Elevations 2000 3000 4000 5000 6006 10000 42 43 43 43 44 44 45 46 47 43 44 45 46 44 45 46 47 44 45 47 47 44 45 47 47 45 46 47 48 45 47 48 48 46 47 48 49 47 48 49 49 47 48 49 50 48 50 50 51 47 48 48 49 49 49 50 50 51 52 54 55 54 55 55 55 55 55 55 56 55 56 55 56 56 56 56 56 56 57 56 57 58 56 58 59 56 59 60 57 59 60 57 60 61 57 60 62 58 61 62 59 62 63 59 63 63 60 63 64 From National Fuel Gas Code - Table F-4 LIGHTING INSTRUCTIONS DO NOT attempt to manually light the burner. Failure to follow this warning could result in property damage, personal injury or death. Lighting instructions appear installation must be checked Regulator 7000 8000 9000 42 on each unit. Each out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below. Turn on the main electrical supply and set the thermostat above the indicated temperature. The ignitor will automatically heat, then the gas valve is energized to permit the flow of gas to the burners. After ignition and flame is established, the flame control module monitors the flame and supplies power to the gas valve until the thermostat is satisfied. TO SHUT OFF For complete shutdown: Move the control switch on the main gas valve to the "OFF" position (See Figures 20 and 21). Disconnect the electrical supply to the unit. If this is done during the cold weather months, provisions must be taken to prevent freeze-up of all water pipes and water receptacles. Failure to follow this warning could result in property damage. White-Rodgers 18-CD21 D1-4 36F gas valve Whenever your house have someone inspect perature. This is very ing weather. If for should fail to operate as frozen water pipes. is to be vacant, arrange to your house for proper temimportant in below freezany reason your furnace damage could result, such 21 Installer's Guide CONTROL AND SAFETY ADJUSTMENT SWITCH LIMIT SWITCH CHECK OUT The limit switch is a safety device designed to close the gas valve should the furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer. To check for proper operation of the limit switches, set the thermostat to a temperature higher than the indicated temperature to bring on the gas valve. Restrict the airflow by blocking the return air or by disconnecting the blower. When the furnace reaches the maximum outlet temperature as shown on the rating plate, the burners must shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty limit switch is probable and the limit switch must be replaced. After checking the operation of the limit control, be sure to remove the paper or cardboard from the return air inlet, or reconnect the blower. AIRFLOW ADJUSTMENT Check inlet and outlet air temperatures to make sure they are within the ranges specified on the furnace rating nameplate. If the airflow needs to be increased or decreased, see the wiring diagram for information on changing the speed of the blower motor. INSTRUCTIONS TO THE OWNERS In the event that electrical, fuel, or mechanical failures occur, the owner should immediately turn the gas supply off at the manual gas valve, located in the burner compartment (See Figure 19). Also turn off electrical power to the furnace and contact the service agency designated by your dealer. Should overheating occur, or the gas supply fail to shut off, shut off the gas valve to the unit before shutting off the electrical supply. Failure to follow this warning could result in property damage, personal injury or death. The following warning complies with State of California This unit is equipped with a blower door switch which cuts power to the blower and gas valve causing shutdown when the door is removed. Operation with the door removed or ajar can permit the escape of dangerous fumes. All panels must be securely closed at all times for safe operation of the furnace. NOTE: Direct drive motors have bearings which are permanently lubricated and under normal use, lubrication is not recommended. INDOOR BLOWER TIMING The control module controls the indoor blower. The blower starts approximately 45 seconds after ignition. The FAN-OFF period is approximately 100 seconds from the interruption of gas flow. ROOM AIR THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT 65. This product contains fiberglass wool insulation! Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inhalation. Glasswool fibers may also cause respiratory, skin, or eye irritation. PRECAUTIONARY MEASURES • Avoid breathing fiberglass • Use a NIOSH approved Disconnect power to the unit before removing the blower door. Failure to follow this warning could result in property damage, personal injury or death. law, Proposition • Avoid contact with sleeved, loose-fitting protection. dust. dust/mist respirator. the skin or eyes. Wear longclothing, gloves, and eye • Wash clothes separately washer thoroughly. from other clothing: rinse • Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations. FIRST AID MEASURES Eye Contact - Flush eyes with water to remove symptoms persist, seek medical attention. Skin Contact - Wash affected and warm water after handling. OPERATING dust. If areas gently with soap INFORMATION FLAME ROLL-OUT DEVICE All models are equipped with a thermal control device on the burner cover. In case of flame roll-out, the device will cause the circuit to open which shuts off all flow of gas. Set the thermostat heat anticipator according to the current flow measured, or the settings found in the notes on the furnace wiring diagram (found inside the furnace casing). 22 18-CD21 D1-4 ........................ Installer's ABNORMAL CONDITIONS 1. EXCESSIVE COMBUSTION VENT PRESSURE OR FLUE BLOCKAGE If pressure against the induced draft blower outlet becomes excessive, the pressure switch will shut off the gas valve until acceptable combustion pressure is again available. 2. LOSS OF FLAME OR GAS SUPPLY FAILURE If loss of flame occurs during a heating cycle (when flame is not present at the sensor), the control module will retry the ignition sequence up to two times after the sensor cools. If ignition is not achieved, it will lockout the furnace. 3. POWER FAILURE If there is a power failure during a heating cycle, the system will restart the ignition sequence automatieally when power is restored, if the thermostat still calls for heat. 4. INDUCED DRAFT BLOWER FAILURE If pressure is not sensed by the pressure switch, it will not allow the gas valve to open, therefore the unit will not start. If failure occurs during a running cycle, the pressure switch will cause the gas valve to close and shut the unit down. Carbon monoxide, fire or smoke can cause serious bodily injury, death, and/or property damage. A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces and fireplaces. The U.S. Consumer Product Safety Commission recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke detectors per the manufacturers installation in- structions to help alert dwelling occupants of the presence of fire, smoke or unsafe levels of carbon monoxide. These devises should be listed by Underwriters Laboratories, Inc. Standards for Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19. NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector. Failure to follow safety warnings exactly, could result in a fire or explosion causing property damage, personal injury or loss of life. -- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. -- WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. • If you cannot reach your gas supplier, call the fire department. -- Installation and service must be performed by a qualified installer, service agency or the gas supplier. INTEGRATED FURNACE CONTROL Normal - No call for Heat Flashing Slow--Normal - Call for Heat Flashing Fast--Continuous ON --Replace IFC Continuous OFF --2 Flashes--- 3 Flashes--- ERROR FLASH CODES Check Power System Lockout (Retries or Recycles exceeded) Draft Pressure Error- Possible problems: a) Venting problem b) Pressure switch problem c) Inducer problem 4 Flashes--5 Flashes --- Open Temperature Limit Circuit Flame sensed when no flame should be present 6 Flashes--7 Flashes --- 115 volt AC power reversed, poor grounding Gas valve circuit error 8 Flashes--- Low flame sense signal Check Ignitor Circuit and Line "N" to 24VAC "Common" [possible grounding problem] 9 Flashes--18-CD21 D1-4 Guide or system voltage too low voltage (_<2 volts) 23 Installer's Guide Trane 6200 Troup Highway Tyler, TX 75707 For more information contact your local dealer (distributor) Since the manufacturer has a policy of continuous product and product data improvement, to change design and specifications without notice. it reserves the right
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 24 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Thu Jun 04 04:13:00 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools