TRANE Furnace/Heater, Gas Manual L0905285

User Manual: TRANE TRANE Furnace/Heater, Gas Manual TRANE Furnace/Heater, Gas Owner's Manual, TRANE Furnace/Heater, Gas installation guides

Open the PDF directly: View PDF PDF.
Page Count: 24

lUlIIIIIUUIIIIIIIIIIIII IIIIIIIIII
1 8- CD2 1 D1 - 4
High Efficiency Single Stage Upflow/Horizontal
and Downflow/Horizontal Gas-Fired Furnaces,
"Fan Assisted Combustion System"
*UDIA040A9H21 B
*UDIB060A9H31 B
*UDIB080A9H31 B
*UDIC080A9H41 B
*__First letter may be "A" or 'q-"
*UD1 B100A9H31 B
*UDIC100A9H51 B
*UD1 D120A9H51 B
*UD1D140A9H51B
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
*DD1 B060A9H31B
*DD1 B080A9H31B
*DD1 C100A9H51B
*DD1 D120A9H51B
IMPORTANT -- This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
For VENT SIZING INFORMATION see:
USA --
National Fuel Gas Code ............. ANSI Z223.1/NFPA 54 (latest version)
CANADA --
Natural Gas Installation Code ........... CAN/CGA-B149.1 (latest version)
Propane Installation Code ................. CAN/CGA-B149.2 (latest version)
USA/CANADA ALTERNATE --
Category I Venting Guide .................................. Pub. No. 18-CH23D1-2
C _
Upflow/Horizontal* Downflow/Horizontal*
*Horizontal Conversion for these furnaces may be left or right side rotation.
A341789P07
Installer's Guide
SAFETY SECTION
The following safety practices and precautions must be
followed during the installation, servicing, and opera-
tion of this furnace.
1. Use only with the type of gas approved for this fur-
nace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in "Location and Clearances" (page 4), of
these instructions.
3. Provide adequate combustion and ventilation air to
the furnace space as specified in "Air for Combus-
tion and Ventilation" (pages 8-9), of these instruc-
tions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system
only, as specified in the "Venting" section (pages 13-
15), of these instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifi-
cally for the detection of leaks to check all connec-
tions, as specified in "Gas Piping" (page 618), of
these instructions.
6. Always install the furnace to operate within the
furnace's intended temperature-rise range with a
duct system which has an external static pressure
within the allowable range, as specified on the unit
rating plate. Airflow with temperature rise for cfm
versus static is shown in the Service Facts accom-
panying this furnace.
7. When a furnace is installed so that supply ducts
carry air circulated by the furnace to areas outside
the space containing the furnace, the return air
shall also be handled by a duct(s) sealed to the fur-
nace casing and terminating outside the space con-
taining the furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in "Location
and Clearances" section (page 4), of these instruc-
tions.
9. The furnace may be used for temporary heating of
buildings or structures under construction only
when the following conditions have been met:
a. The furnace venting system must be complete
and installed per manufacturer's instructions.
b. The furnace is controlled only by a room thermo-
stat (no field jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in
place.
d. The furnace input rate and temperature rise
must be verified to be within nameplate mark-
ing.
e. 100% of the furnace combustion air requirement
must come from outside the structure.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code,
ANSIZ223.1/NFPA 54 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and windows
and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4.
5.
Close fireplace dampers.
Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they are
operating at maximum speed. Do not operate a summer
exhaust fan.
6.
7.
Follow the lighting instructions. Place the appliance be-
ing inspected into operation. Adjust the thermostat so
appliance is operating continuously.
If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149
Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents where
tested as outlined above, return doors, windows, exhaust
fans, fireplace dampers and any other gas-fired burning
appliance to their previous conditions of use.
10.
£The furnace return air temperature range is be-
tween 55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components
upon substantial completion of the construction
process, and verify furnace operating conditions
including ignition, input rate, temperature rise
and venting, according to the manufacturer's in-
structions.
This product must be gas piped by a Licensed
Massachusetts.Plumberor Gas Fitter in the Commonwealth of
© 2008 Trane All Rights Reserved 1 8-CD21 D1-4
Safety signal words are used to designate a degree or
level of seriousness associated with a particular hazard.
The signal words for safety markings are WARNING,
and CAUTION.
a. WARNING indicates a potentially hazardous situa-
tion which, if not avoided, could result in death or
serious injury.
b. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or mod-
erate injury. It is also used to alert against unsafe
practices and hazards involving only property dam-
age.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could re-
sult in serious injury, death or property damage.
Improper servicing could result in dangerous opera-
tion, serious injury, death, or property damage.
Installer's Guide
Contents
Installation Instructions
General Installation Instructions
Location and Clearances
Outline Drawing
Upflow Installation
Downflow Installation
Air For Combustion and Ventilation
Duct Connections
Return Air Filters
Typical Upflow ReturnAir Filter Installations
Alternate Upflow FilterClip /Bracket Installation
Typical Downflow Furnace ReturnAir Filter Installations
General Venting Instructions
Venting Into a Masonry Chimney
Electrical Connections
Field Wiring Diagrams
Gas Piping
Sequence of Operation
Start Up and Adjustment
Preliminary Inspections
Combustion and Input Check
High Altitude Derate
Lighting Instructions
Control and Safety Switch Adjustment
IFC Error Flash Codes
Abnormal Conditions
To prevent shortening its service life, the furnace
should not be used as a "Construction Heater" during
the finishing phases of construction until the require-
ments listed in item 9, a-g of the safety section of this
publication have been met. Condensate in the pres-
ence of chlorides and fluorides from paint, varnish,
stains, adhesives, cleaning compounds, and cement
create a corrosive condition which may cause rapid de-
terioration of the heat exchanger.
These furnaces are not approved or intended for instal-
lation in manufactured (mobile) housing, trailers, or
recreational vehicles.
Failure to follow this warning could result in property
damage, personal injury, or death.
Do NOT install the furnace in a corrosive or contami-
nated atmosphere.
18-CD21 D1-4 3
Installer's Guide
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip-
ment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Condition-
ing Contractors Association (ACCA) or A.R.I. 230 be fol-
lowed in estimating heating requirements. When esti-
mating heating requirements for installation at Alti-
tudes above 2000 ft., remember the gas input must be
reduced (See GAS INPUT ADJUSTMENT).
Material in this shipment has been inspected at
the factory and released to the transportation
agency without known damage. Inspect exterior
of carton for evidence of rough handling in ship-
ment. Unpack carefully after moving equipment
to approximate location. If damage to contents is
found, report the damage immediately to the de-
livering agency.
Codes and local utility requirements governing the
installation of gas fired equipment, wiring, plumbing,
and flue connections must be adhered to. In the ab-
sence of local codes, the installation must conform with
latest edition of the National Fuel Gas Code ANSI
Z223.1 National Installation Code, CAN/CGA B149.1.
The latest code may be obtained from the American Gas
Association Laboratories, 400 N. Capitol St. NW,
Washington D.C. 20001.
1-800-699-9277 or www.aga.org
These furnaces have been classified as Fan Assisted
Combustion system CATEGORY I furnaces as required
by ANSI Z21.47 "latest edition" and CAN/CGA 2.3.
Therefore they do not require any special provisions for
venting other than what is indicated in these instruc-
tions. (Category I defined on page 14).
These furnaces may be twinned. They shall have
common returns with equal pressure drops or
ducts with equivalent lengths and sizes. See Field
Wiring Diagrams for Twinning on page 17 for
proper hookup.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the
architect, the builder, or the installer. However, before
the furnace is moved into place, be sure to consider the
following requirements:
1. Is the location selected as near the chimney or vent
and as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclo-
sure equal or exceed the minimums stated in Clear-
ance Table on the Outline Drawings.
3. Is there sufficient space for servicing the furnace
and other equipment? A minimum of 24 inches
front accessibility to the furnace must be provided.
Any access door or panel must permit removal of
the largest component.
4. Are there at least 3 inches of clearance between the
furnace combustion air openings in the front panel
and any dosed panel or door provided?
5. Are the ventilation and combustion air openings
large enough and will they remain unobstructed? If
outside air is used, are the openings set above the
highest snow accumulation level? (See the Air for
Combustion and Ventilation section.)
6. Allow sufficient height in supply plenum above the
furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components
are protected from water.
8. If the furnace is installed in a residential garage,
it must be installed so that the burners, and the ig-
nition source are located not less than 18 inches
above the floor and the furnace must be located or
protected to avoid physical damage from vehicles.
4 18-CD21 D1-4
Installer's Guide
o
z
.• , , • • ,_ <zz z i
.... _ :>_ _88S_ _o8
co
S S \ z
\L_ C2:C
_ _ CZC,
z zz_
V<_ < " " oo I
z_p< , _9 b h
_ _ _, u b_.l o o.
z_ _
-_[[Eft[[[[[[[[[
[[[[[[[[[[[[ [ [.
[[[[[[[[[[[ [ [ [ o
[[[[[[[[[[ [ [ [ [
[[[[[[[[[[[ [ [ [.
[[[[[[[[[[[ [ [ [
o
+
7
cO
o_
7
<< <<<<<<
7
o_
7
<<<<
7
_o
7
,q-
>
09
8
{.o
©
6_
C3
ii
xxx
LLL
_LL
18-CD21 D1-4 5
Installer's Guide
co
t
U.ll
uJI
Z
1
I:1
I:1
W_
Z<_E
Q
1
11
P
__N
121
P
m
__N
121
121
=
r-u
= = = =
1 1 --
i
<
<
:: ::: .... :--
oo oooooooo ooo
_ _o_ooo _
oo ooo
NN NNNNNNNN NNN
N
_<<<<<<<<<<<<<<
<<<<<<<<<<<<<<
NNNNNN<<NN<<NNNoooo
__o_oo_o_
ooooo--oo
NNNNNN_NN_NNN_ _
_[
9
WCEC
° 1
A
1
0
CC
09
oo
©
n
LL
=
__<_
w_
031"-- N
_o,
w_JW
,,_1.,_ .,_
x _E
_.1L.l.L._.
V'_CO
6 18-CD21 D1-4
!iiiiiiiiii[iHtiii! !ii liii!i/
iiiliiiiXi_iii!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!!i!;iiii
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1 on page 6) are in-
cluded with the cased coils for attachment to the fur-
nace. There are clearance alignment holes near the bot-
tom of the coil wrapper and drill screws are used to en-
gage the furnace top flange. The standoff is inserted
into the cabinet alignment hole. The drill screws are in-
serted through the standoffs then screwed into the fur-
nace flange. The coil is always placed downstream of
the furnace airflow. These instructions apply only if the
coil is on top of an upflow furnace.
(_ STANDOFFS (4) DRILL SCREWS (4)
J
FOR VERTICAL
INSTALLATIONS:
STANDOFFS
(BOTH SIDES)
(BOTH SIDES)
DOWNFLOW INSTALLATION
Do NOT install the furnace directly on carpeting, tile or
other combustible material other than wood flooring.
For vertical downflow application, subbase
(BAYBASE205) must be used between the furnace and
combustible flooring. When the downflow furnace is
installed vertically with a cased coil, a subbase is not
@CABINET SIDE .][.K./ CABINET SIDE
(BENT UP) (BENT UP)
Installer's Guide
required.
REQUIRED FLOOR OPENING:
SEE FIGURE 3 AND TABLE 1
TABLE1
CABINET RETURN FLOOR OPENING PLENUM OPENING
WIDTH DUCT WIDTH "A .... B.... C.... D"
14-1/2" 13-1/4" 13-5/8" 20-1/8" 12-5/8" 19-3/8"
17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used
in the horizontal position.
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the fur-
nace and TXC cased coil in the horizontal position.
See Figure 4.
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See
the 2/4TXC coil Installer's Guide for more details.
©CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
The cased coil is secured to the furnace and both the fur-
nace and the cased coil must be properly supported. The
brackets mount using the rear screws on the coil case
and use the screws provided to secure the bracket to the
furnace. The remaining bracket is placed as close to cen-
ter as possible (horizontally) between the coil case front
and the furnace bottom channel (for downflow/horizontal
furnace). Use four of the screws provided to secure the
bracket.
This furnace may be installed in an attic or crawl space
in the horizontal position by placing the furnace on the
left or right side (as viewed from the front in the up-
right position). The horizontal furnace installation in an
attic should be on a service platform large enough to al-
low for proper clearances on all sides and service access
to the front of the furnace (See Clearance Table on Out-
line Drawings and Figure 5).
18-CD21 D1-4 7
Installer's Guide
If the furnace is suspended using perforated steel strap
(plumber's strap), it must be supported at all four cor-
ners and in the middle at the front of the furnace.
The forward most screw on the side of the furnace
may be used to connect the strapping (See Figure 6).
Line contact is only permissible between lines formed
by the intersection of the top and two sides of the fur-
nace casing and the building joists, studs, or framing.
TYPICAL ATTIC PLATFORM INSTALLATION
(UPFLOW/HORIZONTAL FURNACE SHOWN)
A cutout is provided on both sides of the downflow fur-
nace cabinet to allow a 90 ° elbow to be attached inside
the cabinet and the vent piping to connect there. In
horizontal, the downflow furnace may be vented
through the top of the cabinet if needed. In vertical con-
figuration, the downflow furnace may be vented using
the side cabinet cutouts. This venting configuration
could be used if an electronic air cleaner is installed.
When the downflow furnace is vented through
the left side of the furnace cabinet in horizontal
or vertical configuration, Type B vent pipe must
be used within the cabinet.
Typical Suspended Installation
(Upflow/Horizontal Furnace Shown)
©
UNCONFINED
50 CU. FT. OR MORE
PER 1000 BTU/HR.
INPUT ALL EQUIP-
MENT INSTALLED
0,o(-I
wA,
AIR FOR COMBUSTION AND VENTILATION
Adequate flow of combustion and ventilating air must
not be obstructed from reaching the furnace. Air open-
ings provided in the furnace casing must be kept free of
obstructions which restrict the flow of air. Airflow re-
strictions affect the efficiency and safe operation of the
furnace. Keep this in mind should you choose to re-
model or change the area which contains your furnace.
Furnaces must have a free flow of air for proper perfor-
mance.
Provisions for combustion and ventilation air shall be
made in accordance with "latest edition" of Section 5.3,
Air for Combustion and Ventilation, of the National
Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4
of CAN/ CGA B149 Installation Codes, and applicable
provisions of the local building codes. Special conditions
created by mechanical exhausting of air and fireplaces
must be considered to avoid unsatisfactory furnace op-
eration.
Furnace locations may be in "confined space" or "uncon-
fined space". Unconfined space is defined in Table 2 and
Figure 7. These spaces may have adequate air by infiltra-
tion to provide air for combustion, ventilation, and dilu-
tion of flue gases. Buildings with tight construction (for
example, weather stripping, heavily insulated, caulked,
vapor barrier, etc.), may need additional air provided as
described for confined space.
(_ CONFINED
LESSTHAN 50 CU. FT.
PER 1000 BTU/HR.
INPUTALL EQUIP-
MENT INSTALLED
IFURNACE
Confined spaces are installations with less than 50 cu.
ft. of space per 1000 BTU/hr input from all equipment
installed. Air for combustion and ventilation require-
ments can be supplied from inside the building as in
Figure 9 or from the outdoors, as in Figure 10.
8 18-CD21 D1-4
1. All air from inside the building as in Figure 9: The
confined space shall be provided with two perma-
nent openings communicating directly with an addi-
tional room(s) of sufficient volume so that the com-
bined volume of all spaces meets the criteria for an
unconfined space. The total input of all gas utiliza-
tion equipment installed in the combined space
shall be considered in making this determination.
Refer to Table 3, for minimum open areas required.
2. All air from outdoors as in Figure 10: The confined
space shall be provided with two permanent open-
ings, one commencing within 12 inches of the top
and one commencing within 12 inches of the bot-
tom of the enclosure. The openings shall communi-
cate directly, or by ducts, with the outdoors or
spaces (crawl or attic) that freely communicate with
the outdoors. Refer to Table 3, for minimum open
areas required.
3. The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical expo-
sures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in commercial laundry rooms
* Furnaces installed in hobby or craft rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combus-
tion air supply will also require OUTDOOR AIR for
combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
TABLE2
MINIMUM AREA IN SQUARE FEET FOR
UNCONFINED SPACE INSTALLATIONS
FURNACEMAXIMUM
BTUH/INPUT RATING
40,000
60,000
80,000
100,000
120,000
140,000
WITH 8 FOOT CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
250
375
500
625
750
875
®
®
Installer's Guide
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING FURNACE ONLY)
Furnace Air From Outside
Maximum Air From
BTUH/INPUT Inside Vertical Horizontal
Rating
40,000
60,000
80,000
100,000
120,000
140,000
lOO
lOO
lOO
lOO
12o
14o
Duct
10
15
20
25
30
35
Duct
20
30
40
50
60
70
CONFINED SPACE
AIR FROM OUTDOORS
SPACE
CONFINED SPACE
AIR FROM VENTILATED ATTIC!CRAWL SPACE
1"-_ OUTLETAIR I
INLET
AIR DUCT
18-CD21 D1-4 9
Installer's Guide
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire
Protection Association Pamphlet No. 90. They should
be sized in accordance with ACCA Manual D or which-
ever is applicable. Check on controls to make certain
they are correct for the electrical supply.
Central furnaces, when used in connection with cooling
units, shall be installed in parallel or on the upstream
side of the cooling units to avoid condensation in the
heating element, unless the furnace has been specifi-
cally approved for downstream installation. With a par-
allel flow arrangement, the dampers or other means
used to control flow of air shall be adequate to prevent
chilled air from entering the furnace, and if manually
operated, must be equipped with means to prevent op-
eration of either unit unless the damper is in full heat
or cool position.
On any job, flexible connections of nonflammable ma-
terial may be used for return air and discharge con-
nections to prevent transmission of vibration.
Though these units have been specifically designed
for quiet, vibration free operation, air ducts can act
as sounding boards and could, if poorly installed, am-
plify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent
to the living area, the system should be carefully de-
signed with returns which minimize noise transmission
through the return air grille. Although these winter air
conditioners are designed with large blowers operating
at moderate speeds, any blower moving a high volume
of air will produce audible noise which could be objec-
tionable when the unit is located very close to a living
area. It is often advisable to route the return air ducts
under the floor or through the attic. Such design per-
mits the installation of air return remote from the liv-
ing area (i.e. central hall).
When the furnace is installed so that the supply ducts
carry air circulated by the furnace to areas outside the
space containing the furnace, the return air shall also
be handled by a duct(s) sealed to the furnace and termi-
nating outside the space containing the furnace.
Minimum return air "entering temperature" for
the furnace is 55 ° F.
Where there is no complete return duct system, the re-
turn connection must be run full size from the furnace
to a location outside the utility room, basement, attic,
or crawl space.
DO NOT install return air through the back of the
furnace cabinet.
RETURN AIR DUCT CONNECTION
NOTE:
On upflow 5 or 6 ton airflow models, if the airflow re-
quirement exceeds 1800 CFM, these models will re-
quire return air openings and filters on both sides; OR
1 side and the bottom; OR just the bottom.
All return air duct systems should provide for installa-
tion of return air filters.
1. Set the furnace in place.
2. For side return installations on upflow models, re-
move the insulation around the opening in the
blower compartment.
3. The side panels on upflow furnaces include locating
notches which may be used as guides for cutting an
opening for return air. Refer to Figure 12 and the
outline drawing on page 4 for duct connection di-
mensions for various furnaces.
4. If a 3/4" flange is to be used for attaching the air in-
let duet, add to cut where indicated by solid lines
in Figure 12. Cut corners diagonally and bend out-
ward to form flange.
5. If flanges are not required, and a filter frame is in-
stalled, cut along knockout guidelines.
6. Upflow Furnaces: a filter rack is factory supplied
for bottom or side return. Use the filter rack on ei-
ther side or on the bottom if the filter is to be used
within the furnace cabinet.
IDo NOT install the filter in the return duct directly
above the furnace in horizontal applications. Install
the filter remotely. Installing the filter directly above
the furnace in horizontal applications may cause
property damage, serious injury or death.
TO PREVENT INJURY OR DEATH DUE TO CONTACT
WITH MOVING PARTS, TURN THE POWER TO THE
FURNACE OFF BEFORE SERVICING FILTERS.
When the upflow furnace is installed in the horizon-
tal right or left application and a return duct is at-
tached to the top side as shown in Figure 11, re-
move the filter from the furnace and install in a re-
mote location.
Do not install the filter in the return duct directly
above the furnace in horizontal applications.
When the upflow furnace is installed in the horizon-
tal right or left application and a close coupled (less
than 36") return duct is attached to the bottom side
of the furnace as shown in Figure 11, securely at-
tach a 1/2" mesh metal hardware cloth protective
screen to the inside bottom of the filter grill to pre-
vent personal injury from contacting moving
parts when reaching into the return opening
to replace the filter.
10 18-CD21 D1-4
REMOVE FILTER FROM UPFLOW
FURNACE WHEN RETURN DUCT IS
ATTACHED TO FURNACE TOP SIDE
(HORIZONTAL LEFT OR RIGHT
APPLICATIONS) AS SHOWN.
oooooooooooooo
1oooooooooooooo
IDI_[IID[IIID[IB_DlJ_
I[I#IJHI]BUHlJI]BB
IB[IBDIDDDDDBDDD
I[IH[I[I[IBBII_B[IBII_
Close coupled (less than 36")
return (filter directly beneath bottom
side return) not recommended due to
noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth
protective screen to the inside bottom of
filter grill.
o
Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended
due to noise considerations.
Downflow Furnaces: Brackets are factory sup-
plied to mount filters in the return air duct work.
7. Connect the duct work to the furnace. See Outline
Drawing for supply and return duct size and loca-
tion. Flexible duct connectors are recommended to
connect both supply and return air ducts to the fur-
nace.
If only the front of the furnace is accessible, it is
recommended that both supply and return air ple-
nums are removable.
8. When replacing a furnace, old duct work should be
cleaned out. Thin cloths should be placed over the
registers and the furnace fan should be run for
10 minutes. Don't forget to remove the cloths be-
fore you start the furnace.
RETURN AIR FILTERS
TYPICAL UPFLOW RETURN AIR
FILTER INSTALLATIONS
These furnaces require high velocity type air filters.
The filters may be located within the furnace blower
compartment for UPFLOW furnaces in either a BOT-
TOM or SIDE (left side or right side) return air inlet.
Some filters may need to be trimmed for side or bottom
filter use.
Installer's Guide
NOTE:
On upflow 5 or 6 ton airflow models, if the airflow re-
quirement exceeds 1800 CFM, these models will require
filters on both sides; OR 1 side and the bottom; OR just
the bottom.
@
LOCATING
NOTCHES
PROVIDED
FORSIDE
RETURN
I/
CUTOUT _ I
*SEE OUTLINE DRAWING _""
CUT OUT
/FOR
SIDE
FILTER
._o ,FRuOrNTce
The upflow furnace blower door has a hinge at the bot-
tom which allows the door to tilt forward for filter re-
placement without the door being removed. The fur-
nace filter in the bottom or side configc_ration can be re-
moved by simply turning the two latches on the blower
door and tilting the door forward.
BlowerDoor Hingeand Bottom FilterRack Installation
18-CD21 D1-4 11
Installer's Guide
TABLE 4
UPFLOWFURNACERETURN AIR FILTERS
CABINET CABINET
QTY*
WIDTH BOTTOM FILTER
14-1/2" 1 14" X 25" X 1"
17-1/2" 1 17" X 25" X 1"
21" 1 20" X 25" X 1"
24-1/2" 1 24" X 25" X 1"
CABINET
SIDE FILTER
17-1/2" X 25" X 1"
17-1/2" X 25" X 1"
17-1/2" X 25" X 1"
17-1/2" X 25" X 1"
*NOTE - On 5 ton airflow models, if the airflow
requirement exceeds 1800 CFM, these models will
require return air openings and filters on both sides;
O__RR1 side andthe bottom; O__RRjust the bottom.
RETURN AIR FILTERS FOR UPFLOW FURNACE IN
HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in the horizontal
configuration, the return air filters must be installed
exterior to the cabinet. Remote filter grilles may be
used for homeowner convenience or the filters may be
installed in the duct work upstream of the furnace. See
Figure 14.
@
Typical Filters of Upflow in Horizontal
BLOWER DOOR/HINGE REMOVAL
If clearance or other problems create a problem in us-
ing the tilting door, the blower door hinge may be re-
moved without creating any problems with the seal of
the furnace. To remove the blower door, tilt the door
forward 2 to 3 inches and pull up. To remove the tilt fea-
ture, simply remove the lower hinge as shown in Fig-
ure 15. The bottom of the blower door will catch in the
bottom of the furnace front channel for door replace-
ment.
ALTERNATE UPFLOW FILTER CLIP/BRACKET INSTAL-
LATION
1.Determine the location to be used. The furnace
cabinet has dimples for location of the alternate fur-
nace clips (Side return only). Pre-drill clearance
holes with a 3/16" drill. Bottom return holes are
pre-drilled.
2.Install the clips in front and rear of the desired loca-
tion using the screws provided. The filter clip with
the leaf spring mounts in the rear of the cabinet.
®
/
ALTERNATE FILTER
CLIPS LOCATION
Door Hinge Removed
12 18-CD21 D1-4
TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER
INSTALLATIONS
®
These furnaces require high velocity type air filters.
Downflow furnace filters must be located outside the
furnace cabinet. Typical installations are shown in Fig-
ure 17. Tables 5 and 6 provide information for installa-
tion of the filter retaining brackets shipped with
downflow furnaces.
TABLE 5
CABINET FILTER FILTER BRACKET
WIDTH SIZE LOCATION *
14-1/2" 2 -14X20X1 12-7/8"
17-1/2" 2 - 16X20X1 14-3/8"
21" 2 - 16X20X1 13-1/8"
24-1/2" 2 - 16X20X1 11-5/8"
Location dimension is from end of duct to the screw holes for the bracket.
TABLE 6
CABINET RETURN FILTER ACCESS FILTER ACCESS
DUCT OPENING - OPENING -
WIDTH WIDTH DIMENSION"A" DIMENSION"B"
14-1/2" 13-1/4" 12" 14"
17-1/2" 16-1/4" 15" 14"
21" 19-3/4" 19-1/2" 14"
24-1/2" 23-1/4" 22" 14"
Installer's Guide
GENERAL VENTING INSTRUCTIONS
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon
monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA
B149 Installation Codes and these instructions.
Determine that there is no blockage or restriction,
leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system
are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any
exhaust fans, such as range hoods and bathroom
exhausts, so they are operating at maximum speed.
Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the
thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the
above tests, the venting system must be corrected
in accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149
Installation Codes.
8, After it has been determined that each appliance
connected to the venting system properly vents
where tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and any
other gas-fired burning appliance to their previous
conditions of use.
18-CD21 D1-4 13
Installer's Guide
VENT PIPING
These furnaces have been classified as Fan-Assisted
Combustion System, Category I furnaces under the "lat-
est edition" provisions of ANSI Z21.47 and CAN/CGA
2.3 standards. Category I furnaces operate with a non-
positive vent static pressure and with a flue loss of not
less than 17 percent.
NOTE:
If desired, a side wall termination can be accomplished
through the use of an "add-on" draft inducer. The in-
ducer must be installed according to the inducer
manufacturer's instructions. Set the barometric pres-
sure relief to achieve -0.02 inch water column.
NOTE: When the downflow furnace is vented through
the left side of the furnace cabinet using the provided
cutout, Type B vent piping must be used.
The furnace shaft be connected to a factory built chim-
ney or vent complying with a recognized standard, or a
masonry or concrete chimney lined with a lining mate-
rial acceptable to the authority having jurisdiction.
Furnace venting into an unlined masonry chimney or
concrete chimney is prohibited.
Failure to follow this warning could result in property
damage, personal injury, or death.
VENTING INTO A MASONRY CHIMNEY
If the chimney is oversized, the liner is inadequate, or
flue-gas condensation is a problem in your area, con-
sider using the chimney as a pathway or chase for type
"B" vent or flexible vent liner. If flexible liner material
is used, size the vent using the "B" vent tables, then re-
duce the maximum capacity by 20% (multiply 0.80
times the maximum capacity). Masonry Chimney Kit
BAYVENTS00B may be used with these furnaces
(Upflow model furnaces only) to allow venting into a
masonry chimney. Refer to the BAYVENTS00B
Installer's Guide for application requirements.
INTERNAL MASONRY CHIMNEYS
Venting of fan assisted appliances into a lined, internal
masonry chimney is allowed only if it is common vented
with at least one natural draft appliance; OR, if the
chimney is lined with type "B", double wall vent or suit-
able flexible liner material (See Table 7).
The chimney liner must be thoroughly inspected to in-
sure no cracks or other potential areas for flue gas
leaks are present in the liner. Liner leaks will result in
early deterioration of the chimney.
Failure to follow this warning could result in carbon
monoxide poisoning or death.
NOTE:
The following section does not apply if BAYVENT8OOB
(Masonry Chimney Vent Kit) is used. All instructions
with the kit must be followed.
TABLE 7
MASONRY CHIMNEY VENTING
Type Furnace
Single Fan
Assist
Fan Assist
+
Fan Assist
Fan Assist
+
Natural
Tile Lined Chimney
Internal External
No No
No No
Yes No
Chimney Lining
Flexible
"B" Vent Metal Liner
Yes *Yes
*Yes
*Yes
Yes
Yes
* Flexible chimney liner size is determined by using the type "B" vent size for
the available BTUH input, then reducing the maximum capacity by 20%
(multiply maximum capacity times 0.80). The minimum capacity is the same
as shown in the "B" vent tables.
External Masonry Chimney
Venting of fan assisted appliances into external chim-
neys (one or more walls exposed to outdoor tempera-
tures), requires the chimney be lined with type "B",
double wall vent or suitable flexible chimney liner ma-
terial. This applies in all combinations of common vent-
ing as well as for fan assisted appliances vented alone.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the
venting system being placed into operation could re-
sult in carbon monoxide poisoning or death.
The following installation practices are recommended to
minimize corrosion caused by condensation of flue prod-
ucts in the furnace and flue gas system.
1. Avoid an excessive number of bends.
2. Horizontal runs shotfld pitch upward at least 1/4" per
foot.
3. Horizontal runs should be as short as possible.
4. All vent pipe or connectors should be securely sup-
ported and must be inserted into, but not beyond
the inside wall at the chimney vent.
5. When vent connections must pass through walls or
partitions of combustible material, a thimble must
be used and installed according to local codes.
6. Vent pipe through the roof should be extended to a
height determined by National Fuel Gas Code or
local codes. It should be capped properly to prevent
rain water from entering the vent. Roof exit should
be waterproofed.
7. Use type "B" double wall vent when vent pipe is
routed through cool spaces (below 60° F.).
14 18-CD21 D1-4
TABLE 8
GAS VENT TERMINATION
ROOF PITCH
FLAT TO 7/12
OVER 7/12 TO 8/12
OVER 8/12 TO 9/12
OVER 9/12 TO 10/12
OVER 10/12 TO 11/12
OVER 11/12 TO 12/12
OVER 12/12 TO 14/12
OVER 14/12 TO 16/12
OVER 16/12 TO 18/12
OVER 18/12 TO 20/12
OVER 20/12 TO 22/12
MINIMUM HEIGHT
1.0 FEET *
1.5 FEET
2.o FEET
2.5 FEET
3.25 FEET
4.o FEET
5.0 FEET
6.0 FEET
7.0 FEET
7.5 FEET
8.0 FEET
* THIS REQUIREMENT COVERS MOST INSTALLATIONS
(_ VERTICAL WALL
ff MIN.
LISTED LOWEST DISC HARGE
CAP N OPENING
THE VENT TERMINATION SHOULO NOT BE
LESS THAN 8 FT FROM AVERTICAL WALL
8. Where long periods of airflow are desired for com-
fort, use long fan cycles instead of continuous air-
flow.
9. Apply other good venting practices as stated in the
venting section of the National Fuel Gas Code
ANSI Z223.1 "latest edition".
10. Vent connectors serving appliance vented by
natural draft or non-positive pressure shall
not be connected into any portion of a mecha-
nized draft system operating under positive
pressure.
11. Horizontal pipe runs must be supported by hangers,
straps or other suitable material in intervals at a
minimum of every 3 feet of pipe.
12. A furnace shall not be connected to a chimney or
flue serving a separate appliance designed to burn
solid fuel.
13. The flow area of the largest section of vertical vent
or chimney shall not exceed 7 times the smallest
listed appliance categorized vent area, flue collar
area, or draft hood outlet area unless designed in
accordance with approved engineering methods.
Maximum Vent or Tile = _(D*)2 X 7
Lined Chimney Flow Area 4
*Drafthood outlet diameter, flue collar diameter, or listed appliance cat-
egorized vent diameter.
Installer's Guide
ELECTRICAL CONNECTIONS
The cabinet must have an uninterrupted or unbroken
ground according to National Electrical Code, ANSI/
NFPA70 - "latest edition" and Canadian Electrical
Code, CSA C22.1 or local codes to minimize personal
injury if an electrical fault should occur.
Failure to follow this warning could result in an electri-
cal shock, fire, injury, or death.
The integrated furnace control is polarity sensitive. The
hot leg of the 115 VAC power must be connected to the
BLACK field lead.
To prevent injury or death due to electrical shock or
contact with moving parts, lock unit disconnect switch
in the open position before servicing the unit.
Failure to follow this warning could result in electri-
cal shock, personal injury, or death.
Make wiring connections to the unit as indicated on en-
closed wiring diagram. As with all gas appliances using
electrical power, this furnace shall be connected into a
permanently live electric circuit. It is recommended
that it be provided with a separate "circuit protection
device" electric circuit. The furnace must be electrically
grounded in accordance with local codes or in the ab-
sence of local codes with the National Electrical Code,
ANSI/NFPA 70 "latest edition" or Canadian Electrical
Code, CSA C22.1, if an external electrical source is uti-
lized.
All field supplied wiring must conform with the tem-
perature limitation for Type T wire [63° F. (35 ° C)],
when installed in accordance with these instructions
and wiring diagrams supplied with the furnace. A dis-
connecting means must be located within sight from,
and readily accessible to, the furnace.
Refer to the SERVICE FACTS literature for unit wiring
diagrams in addition to the diagram inside the blower
door.
18-CD21 D1-4 15
Installer's Guide
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING
T'STAT
SEE
NOTE 7
L
FURNACE
--F-q
__t-_- I
D
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
NOTES"
I. BE SURE POWERAGREESWITH EOUIPMENT NAMPLATE(S).
2, LOWVOLTAGE (24V, WIRING) TO BE NO. 18 A.W.G. MIN..
3. GROUNDINGOF EOUIPMENT MUST COMPLYWITH LOCAL CODES.
4. SET THERMOSTATHEAT ANTICIPATOR PER UNIT WIRING DIAGRAM.
5. THESE LEADS PROVIDE 115 V. POWERFOR CONNECTIONOF ELECTRONIC AIR
CLEANER AND HUMIDIFIER MAX. LOAD 1.0 AMPS EACH.
6. THIS CONNECTION IS ONLY USED FOR THERMOSTATSREOUIRING
CONNECTIONTO THE ?4 V. POWERSUPPLY. (COMMON)
7. SEE TWINNING CONNECTIONDIAGRAMS FOR PROPERCONNECTIONS
WHENUSING THIS FEATURE.
_---
E_""
E_--
SEE
,NOTEG_
--D
--E_
__Fc-1
INTER-COMPONENT WIRING
24. V, }FIELD
----LINE V. WIRING
24 V. _FACTORY
--LINE V..j'-WIRING
T_ GROUND
_r_tCR_--_ j ,_ FURNACE
'11 !_ T rJUNCTION
, BOX
r- LH BK I_ w./,'ll
LOCALOOOES/ I
L ! 'I"_ _"_I
rw.l I ,_,
HUM SEE J"** ,_I I: I_ :
NOTE 5 /BK ,_ ....
.-w. /
EACSEE
NOTE 5 L BK ' From Dwg. B341437 Rev. 1
OUTDOOR UNIT
(NO TRANSFORMER /
y._l_,_..........
_--
[_]---
[_]---
E_--
L.............................. II
INTER-COMPONENT WIRING
24 V, }FIELD----LINE V. WIRING
24 V. _FACTORY
--LINE V.jrWIRING
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
T"STAT FURNACE
SEE NOTES:
NOTE7 _ I. BE SURE POWERAGREESWITH EQUIPMENT NAMPLATE(S).
L.__,, 2. LOW VOLTAGE (24V. WIRING) TO BE NO. 18 A.W.G, MIN..
3. GROUNDINGOF EQUIPMENT MUST COMPLYWITH LOCAL CODES.
4. SET THERMOSTATHEAT ANTICIPATOR PER UNIT WIRING DIAGRAM.
......... E_ S. THESE LEADS PROVIDE 115 V. POWERFOR CONNECTION OF ELECTRONIC AIR
CLEANER AND HUMIDIFIER MAX, LOAD 1.0 AMPS EACH.
SEE 6. THIS CONNECTION IS ONLY USED FOR THERMOSTATSREQUIRING
NOTE8 _ CONNECTION TO THE 24 V. POWERSUPPLY. (COMMON)
........ 11 I 7. SEE TWINNING CONNECTION DIAGRAMS FOR PROPER CONNECTIONS
WHEN USING THIS FEATURE.
8. THE "Y" TERMININAL FROM THE THERMOSTATMUST BE WIRED
........ E_ TO THE "Y" TERMINAL OF THE FURNACECONTROL FOR PROPER BLOWER
OPERATION DURING COOLING.
........ _'_ ,r GROUND
SEE ----_I_R--_--I,_ --- FURNAC E
.NOTEG_ __fB"_'1: i _ TrJUNCTION
'," ,- _, _----J/, BOX
TOIISVIPH, I 'M'I "
', soNZPOWERJ IJI
I SUPPLY PER "I I I'-- I
LOCAL CODES |I_N --.--_II_-I--I_ I
L F_'_ ''u "El
,.-_/ /,._1 ,
HUMSEE J"r''_l II1_ :
NOTE 5 I. BK ,_
L---- --t --N3._,2
_. I ,I,
EAC SEE I--- -- --I I I'_ I
BK
NOTES L' _. _ _._1 FrO,TDw'_.E?4143GR,_/.!
16 18-CD21 D1-4
Installer's Guide
TWINNING
These furnaces may be twinned. Twinning requires that
two furnaces with the same configuration, capacity, and
airflow must be used. They shall have common returns
with equal pressure drops or ducts with equivalent
lengths and sizes. See Field Wiring Diagrams below for
proper hookup.
S'fAGE HEA'[
ONLY
THERMOSTA_
(WITH FAN SWITCH
F_ .....
SEE NOTE 3
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEATING ONLY THERMOSTAT
FURNACE NO 1
_ .....
E]
..... _--4_
..... F_
..... F_
ISOLATIONRELAY
(FEELDSUPPUED)
__22E N_O_TE_4___
____.
I
I
I
I
..... I
FURNACE NO, 2
BLOWEROPErATiONOF
UNit NO2 ISSYNCROfqZED
WiTHUNITNO 1WASIGNALS
FROMTWiNCONNECTION
...... F_ 2
4
SEE NOTE 4
Rll 1
SEE NOTE 4
%
NOTES
I BOTH FURNACES MUST Bf ROWfSED fROM
THE SAME IISV LED OF CIRCUIT PANEL
INSURE S4V FURNACE TRANSFORMERS ARE
IN PHASE PRIOR TO COMPLETING CONNECTIONS,
CHECK VOITAUE SET#EEN "R' TERMINALS OF
EACH FURNACE If VOLTAGE IS GREATER THAN
IOV, REVERSE THE SL AN RD SECONDARY IEADS
ON ONE OF THE FURNACE TRANSFORMERS
CONNECTION MAY BE REOUIRED FOR
EIECTRONIC THERMOSTAT
I# CURRENT EXCEEDS THERMOSTAT CURRENT
RATING, USE iSOLATION RELAYS [_RI') AS
SHOWN (DO NOT CONNECT W TO W)
ISOLATION RELAY NOT NEEDED If THE THERMOSTAT
CONTACTS ARE RATED AT IOA OR ABOVE
INTER-COMPONENT WIRING
AITERNAT# #IRIN6 CONFIGURATION
......... SEE NOTE 4
24 V. "_FIELD
----LINE V..! WIRING
24 V. __FACTORY
ILINE V.._ WIRING
From Dwg. 21B341422 Rev. 3
OUTDOOR UNIT
WITH TRANSFORMER
1S_GE
HE_ING/COOLING
THERMOSTAT
i 301
io;
ISOLATIONRELAy
_FIELDSUPPUED)
SEENOTE3
OUTDOOR UNIT
(NO TRANSFORMER)
SEE NOTE 5
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEAT /1 STAGE COOL THERMOSTAT
}
}
I
R1; _> ;
ISOLATIO N RELAY
(FIELD SUPPLIED)
SEE NOTE 4
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO 2 _S SYNCRON]ZED ?
3
SEE NOTE 4
1 1
Rli_ i
%
TH_ S#_W _L S 0 C [2C_¢T p4t,I_[
)S}R 24V F M'NAC_TRAASFORMRSAR_
i_¸ _#_S£ _R_O_ TO COt#PLET_5 _O,_',%CT_Ot_S
C_EC_ VOLT4S__EZ_'_E_ _ T_?_t,,4L5¸Of
_OUTDOOr,_ 7 H45 4 24v TRANSFO_WE#
tSOL/TrO/ ,?_L_YI,_U3T_ _fl_TALLE_
,R(_, SUCH _ R__0"];'5 _ $_ 4_T CO_NCT;O_,
f CURRE&T#XEEDS THER#OSTATCUI_E_T
RAT_!_6 IJ_E IROtATtOt_ RE_AY$ if _l 4S
S_O_ ' _'_0 _OT COt_t_ECTWTO _
T_ER_OST_TS
I N • E R C O M P 0 Ix E N • il/'_'] ] N O
4TiRI_,_TFil'iR td O_ ISUi_AT@/
SEE 'dOTE
24 v. 'k_ FIELD
----LINE /._ '¢,i]RING
24 '/. _ FACTORY
--LINE M.) /WIRING
From Dwg 21 B341423 Rev 2
18-CD21 D1-4 17
Installer's Guide
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could re-
sult in serious injury, death or property damage. Never
test for gas leaks with an open flame. Use a commer-
cially available soap solution made specifically for the
detection of leaks to check all connections. A fire or ex-
plosion may result causing property damage, personal
injury, or loss of life.
@LEFT SIDE PIPING (STANDARD)
MANUAL MAIN
SHUTOFF
UNION JOINT
DRIP LEG
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
RIGHT SIDE PIPING (OPTIONAL)
iSHUTOFF VALVE
UNION JOINT
AUTOMATIC GAS VALVE
WiTH MANUAL _UTOFF
TOP VIEW OF RIGHT SIDE PIPING
TOP VIEW
GAS PIPING
This unit is shipped standard for left side installation of
gas piping. A piping knockout is also provided in the
right side for an alternate piping arrangement. The in-
stallation of piping shall be in accordance with piping
codes and the regulations of the local gas company. Pipe
joint compound must be resistant to the chemical reac-
tion with liquefied petroleum gases.
Refer to piping Table 9 for delivery sizes. Connect gas
supply to the unit, using a ground joint union and a
manual shut-off valve as shown in Figure 19. National
codes require a condensation drip leg to be installed
ahead of the controls as shown in Figure 19.
The furnace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of that system at test pressures in ex-
cess of 1/2 psig.
The furnace must be isolated from the gas supply piping
by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
Use a backup wrench on the gas valve when installing
gas piping to prevent damage to the gas valve and
manifold assembly.
NOTF"
Maximum pressure to the gas valve for natural gas is
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the gas valve for propane is 13.8" W.C.
Minimum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a soapy
solution before lighting the furnace.
DO NOT CHECK WITH AN OPEN FLAME!
The following warning complies with State of California law, Proposition 65.
Hazardous Gases!
Exposure to fuel substances or by-products of
incomplete fuel combustion is believed by the state of
California to cause cancer, birth defects, or other
reproductive harm.
SEQUENCE OF OPERATION
THERMOSTAT CALL FOR HEAT
R and W thermostat contacts close signaling the control
module to run its self-check routine. After the control
module has verified that the pressure switch contacts
are open and the limit switch(es) contacts are closed,
the draft blower will be energized.
TO PREVENT AN EXPLOSION OR POSSIBLE INJURY,
DEATH AND EQUIPMENT DAMAGE, DO NOT STORE
COMBUSTIBLE MATERIALS, GASOLINE OR OTHER
FLAMMABLE VAPORS OR LIQUIDS NEAR THE UNIT.
18 18-CD21 D1-4
As the induced draft blower comes up to speed, the
pressure switch contacts will close and the ignitor warm
up period will begin. The ignitor will heat for approx. 20
seconds, then the gas valve is energized to permit gas
flow to the burners. The flame sensor confirms that ig-
nition has been achieved within the 6 second ignition
trial period.
After the flame sensor confirms that ignition has been
achieved, the delay fan ON period (fixed at 45 seconds)
begins timing. After the delay of 45 seconds, the indoor
blower motor will be energized and will continue to run
during the heating cycle.
When the thermostat is satisfied, R and W thermostat
contacts open, the gas valve will close, the flames will
extinguish, and the induced draft blower will be de-en-
ergized. The indoor blower motor will continue to run
for the fan off period (fixed at 100 seconds), then will be
de-energized by the control module.
test for gas leaks with an open flame. Use a commer-
cially available soap solution made specifically for the
detection of leaks to check all connections. A fire or ex-
plosion may result causing property damage, personal
injury, or loss of life.
START-UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
With gas and electrical power "OFF"
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Turn knob on main gas valve within the unit to the
"OFF" position. Turn the external gas valve to "ON".
Purge the air from the gas lines. After purging, check
all gas connections for leaks with a soapy solution - DO
NOT CHECK WITH AN OPEN FLAME. Allow 5 min-
utes for any gas that might have escaped to dissipate.
LP Gas, being heavier than air, may require forced ven-
tilation. Turn the knob on the gas valve in the unit to
the "ON" position.
COMBUSTION AND INPUT CHECK
1. Make sure all gas appliances are off except the fur-
nace.
2. Clock the gas meter with the furnace operating (de-
termine the dial rating of the meter) for one revolu-
tion.
3. Match the "Sec" column in the gas flow (in cfh)
Table 12 with the time clocked.
4. Read the "Flow" column opposite the number of sec-
onds clocked.
Installer's Guide
5. Use the following factors if necessary:
For 1 Cu. Ft. Dial Gas Flow CFH =
Chart Flow Reading + 2
For 1/2 Cu. Ft. Dial Gas Flow CFH =
Chart Flow Reading + 4
For 5 Cu. Ft. Dial Gas Flow CFH =
10X Chart Flow Reading + 4
6. Multiply the final figure by the heating value of the
gas obtained from the utility company and compare
to the nameplate rating. This must not exceed the
nameplate rating.
7.Changes can be made by adjusting the manifold
pressure or changing orifices (orifice change may
not always be required). To adjust the manifold
pressure:
a.Turn off all electrical power to the system.
b.Attach a manifold pressure gauge to the outlet pres-
sure tap marked "OUT PRESS TAP" on White-
Rodgers gas valve model 36F or boss marked "OUT
P" on White-Rodgers gas valve model 36G. (See Fig-
ure 21) for White-Rodgers gas valve model 36F and
Figure 20 for White-Rodgers gas valve model 36G).
For the gas valve model 36F, measurement re-
quires removal of the plug and installation of a
barbed fitting. Attach flexible tubing and a manom-
eter to the barbed fitting.
For the gas valve model 36G, do not remove the
pressure tap test screw. Using a 3/32" hex wrench,
loosen the pressure tap test screw one turn and in-
stall 5/16" flexible tubing and a manometer directly
onto the outlet pressure boss.
c. Turn on system power and energize valve.
d.Remove the regulator adjustment screw cap on the
gas valve for manifold pressure adjustment.
e.Turn the adjustment nut clockwise to increase the
gas flow rate, and counterclockwise to decrease the
gas flow rate using a 3/32" hex wench.
f. The final manifold pressure setting shall be 3.5"
W.C. with an input of no more than nameplate rat-
ing and no less than 93% of the nameplate rating,
unless the unit is derated for high altitude.
g.Replace the regulator adjustment screw cap and
tighten securely.
h.Turn off all electrical power to the system.
i. Remove the manometer and flexible tubing. Re-
move the barbed fitting and replace the plug or
tighten the pressure test screw.
j. Turn on electrical power to the system and energize
valve.
k. Using a leak detection solution or soap suds, check
for leaks at plug or pressure boss screw.
18-CD21 D1-4 19
Installer's Guide
Replace and/or tighten all plugs removed or loosened
when adjusting gas pressure. Leak check the fittings
before placing the furnace into regular service.
Failure to follow this warning could result in fire, ex-
plosion, or property damage.
For LP gases, the final manifold pressure setting shall
be 10.5" W.C. with an input of no more than the name-
plate rating and no less than 93% of the nameplate rat-
ing, unless the unit is derated for altitude.
Table 10 lists the main burner orifices shipped with the
furnace. If a change of orifices is required to correct the
input rate, refer to Table 11.
TABLE 9
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE LENGTH OF PIPE
SIZE 10 20 30 40 50 60 70
1_ 132 92 73 63 56 50 46
3_ 278 190 152 130 115 105 96
1 520 350 285 245 215 195 180
1-1_ 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SEGR. gas
TABLE 10
ORIFICE SIZES
INPUT
RATING
BTUH
40,000
60,000
80,000
100,000
120,000
140,000
NUMBER
OF
BURNERS
2
3
4
5
6
7
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GAS
45
45
45
45
45
45
LP GAS
56
56
56
56
56
56
TABLE 11
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44
45
46
47
48
49
50
PART
NUMBER
ORFO0501
0RF00644
ORFO0909
ORFO0910
0RF01099
ORFO0503
0RF00493
DRILL
SIZE
54
55
56
57
58
59
PART
NUMBER
0RF00555
0RF00693
ORFO0907
ORFO0908
0RF01338
0RF01339
HIGH ALTITUDE DEBATE
Input ratings (BTUH) of these furnaces are based on
sea level operation and should not be changed at eleva-
tions up to 2,000 ft.
If the installation is 2,000 ft. or above, the furnace input
rate (BTUH) shall be reduced 4% for each 1,000 ft.
above sea level. The furnace input rate shall be checked
by clocking the gas flow rate (CFH) and multiplying by
the heating value obtained from the local utility sup-
plier for the gas being delivered at the installed altitude.
Input rate changes can be made by adjusting the mani-
fold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas)
or changing orifices (orifice change may not always be
required). If the desired input rate cannot be achieved
with a change in manifold pressure, then the orifices
must be changed. LP installations will require an orifice
change.
Installation of this furnace at altitudes above 2,000 ft.
(610m) shall be in accordance with local codes, the Na-
tional Fuel Gas Code, ANSI Z223.1/ NFPA 54 or Na-
tional Standard of Canada, Natural Gas and Propane
Installation Code, CSA B149.1. Installation of this fur-
nace at altitudes above 2,000 ft. (610m) shall be made in
accordance with the listed high Altitude Conversion Kit
available with this furnace.
IMPORTANT:
Re-install the propane orifices to the same depth as the
orifices supplied with the equipment.
See Table 13 for help in selecting orifices if orifice
change is required. Furnace input rate and tempera-
ture rise should be checked again after changing ori-
rices to confirm the proper rate for the altitude.
Installations above 4,000 feet may require a pressure
switch change. If required, use the BAYHALT*** Kit
(High Altitude Accessory Kit) listed in PRODUCT DATA.
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY
COLLECT IN ANY LOW AREAS OR CONFINED
SPACES. IN ADDITION, ODORANT FADE MAY MAKE
THE GAS UNDETECTABLE EXCEPT WITH A WARN-
ING DEVICE. IF THE GAS FURNACE IS INSTALLED
IN A BASEMENT, AN EXCAVATED AREA OR A
CONFINED SPACE, IT IS STRONGLY RECOM-
MENDED TO CONTACT A GAS SUPPLIER TO IN-
STALL A GAS DETECTING WARNING DEVICE IN
CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test
any detectors and makes no representations regarding
any brand or type of detector.
20 18-CD21 D1-4
i_ii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
!!!!!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!i_i!!_
TABLE 12
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8 900 29 248 50 144 82 88
9 800 30 240 51 141 84 86
10 720 31 232 52 138 86 84
11 655 32 225 53 136 88 82
12 600 33 218 54 133 90 80
13 555 34 212 55 131 92 78
14 514 35 206 56 129 94 76
15 480 36 200 57 126 96 75
16 450 37 195 58 124 98 73
17 424 38 189 59 122 100 72
18 400 39 185 60 120 104 69
19 379 40 180 62 116 108 67
20 360 41 176 64 112 112 64
21 343 42 172 66 109 116 62
22 327 43 167 68 106 120 60
23 313 44 164 70 103 124 58
24 300 45 160 72 100 128 56
25 288 46 157 74 97 132 54
26 277 47 153 76 95 136 53
27 267 48 150 78 92 140 51
28 257 49 147 80 90 144 50
(_ Outlet Pressure Boss Regulator
Inlet Pressure
Boss (opt.) On/Off Switch
White-Rod_ers 3613 gas valve
On/Off Switch
White-Rodgers 36F gas valve
Installer's Guide
TABLE 13
Orifice
Twist Drill
Size If
Installed
At Sea
Level
42
43
44
45
46
47
54
55
56
57
58
ALTITUDE ABOVE SEA LEVEL
and Orifice Required At Other Elevations
2000 3000 4000 5000 6006 7000 8000 9000 10000
42 43 43 43 44 44 45 46 47
44 44 44 45 45 46 47 47 48
45 45 45 46 47 47 48 48 50
46 47 47 47 48 48 49 49 50
47 47 47 48 48 49 49 50 51
48 48 49 49 49 50 50 51 52
54 55 55 55 55 55 56 56 56
55 55 55 56 56 56 56 56 57
56 56 57 57 57 58 59 59 60
58 59 59 60 60 61 62 63 63
59 60 60 61 62 62 63 63 64
From National Fuel Gas Code - Table F-4
LIGHTING INSTRUCTIONS
DO NOT attempt to manually light the burner.
Failure to follow this warning could result in property
damage, personal injury or death.
Lighting instructions appear on each unit. Each
installation must be checked out at the time of
initial start up to insure proper operation of all
components. Check out should include putting
the unit through one complete cycle as outlined
below.
Turn on the main electrical supply and set the thermo-
stat above the indicated temperature. The ignitor will
automatically heat, then the gas valve is energized to
permit the flow of gas to the burners. After ignition and
flame is established, the flame control module monitors
the flame and supplies power to the gas valve until the
thermostat is satisfied.
TO SHUT OFF
For complete shutdown: Move the control switch on the
main gas valve to the "OFF" position (See Figures 20
and 21). Disconnect the electrical supply to the unit.
If this is done during the cold weather months, provi-
sions must be taken to prevent freeze-up of all water
pipes and water receptacles.
Failure to follow this warning could result in property
damage.
Whenever your house is to be vacant, arrange to
have someone inspect your house for proper tem-
perature. This is very important in below freez-
ing weather. If for any reason your furnace
should fail to operate damage could result, such
as frozen water pipes.
18-CD21 D1-4 21
Installer's Guide
CONTROL AND SAFETY SWITCH
ADJUSTMENT
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the
gas valve should the furnace become overheated. Since
proper operation of this switch is important to the
safety of the unit, it must be checked out on initial
start up by the installer.
To check for proper operation of the limit switches, set
the thermostat to a temperature higher than the indi-
cated temperature to bring on the gas valve. Restrict
the airflow by blocking the return air or by disconnect-
ing the blower. When the furnace reaches the maxi-
mum outlet temperature as shown on the rating plate,
the burners must shut off. If they do not shut off after a
reasonable time and overheating is evident, a faulty
limit switch is probable and the limit switch must be re-
placed. After checking the operation of the limit control,
be sure to remove the paper or cardboard from the re-
turn air inlet, or reconnect the blower.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure
they are within the ranges specified on the furnace rat-
ing nameplate. If the airflow needs to be increased or
decreased, see the wiring diagram for information on
changing the speed of the blower motor.
Disconnect power to the unit before removing the
blower door.
Failure to follow this warning could result in property
damage, personal injury or death.
This unit is equipped with a blower door switch which
cuts power to the blower and gas valve causing shut-
down when the door is removed. Operation with the
door removed or ajar can permit the escape of danger-
ous fumes. All panels must be securely closed at all
times for safe operation of the furnace.
NOTE:
Direct drive motors have bearings which are perma-
nently lubricated and under normal use, lubrication is
not recommended.
INDOOR BLOWER TIMING
The control module controls the indoor blower. The
blower starts approximately 45 seconds after ignition.
The FAN-OFF period is approximately 100 seconds
from the interruption of gas flow.
ROOM AIR THERMOSTAT HEAT ANTICIPATOR
ADJUSTMENT
Set the thermostat heat anticipator according to the
current flow measured, or the settings found in the
notes on the furnace wiring diagram (found inside the
furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical
failures occur, the owner should immediately
turn the gas supply off at the manual gas valve,
located in the burner compartment (See Figure
19). Also turn off electrical power to the furnace
and contact the service agency designated by
your dealer.
Should overheating occur, or the gas supply fail to
shut off, shut off the gas valve to the unit before shut-
ting off the electrical supply.
Failure to follow this warning could result in property
damage, personal injury or death.
The following warning complies with State of California law, Proposition 65.
This product contains fiberglass wool insulation!
Fiberglass dust and ceramic fibers are believed by the
State of California to cause cancer through inhalation.
Glasswool fibers may also cause respiratory, skin, or
eye irritation.
PRECAUTIONARY MEASURES
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes. Wear long-
sleeved, loose-fitting clothing, gloves, and eye
protection.
Wash clothes separately from other clothing: rinse ..............................................................................................
washer thoroughly.
Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact - Flush eyes with water to remove dust. If
symptoms persist, seek medical attention.
Skin Contact - Wash affected areas gently with soap
and warm water after handling.
OPERATING INFORMATION
FLAME ROLL-OUT DEVICE
All models are equipped with a thermal control device
on the burner cover. In case of flame roll-out, the device
will cause the circuit to open which shuts off all flow of
gas.
22 18-CD21 D1-4
ABNORMAL CONDITIONS
1. EXCESSIVE COMBUSTION VENT PRESSURE OR
FLUE BLOCKAGE
If pressure against the induced draft blower outlet
becomes excessive, the pressure switch will shut off
the gas valve until acceptable combustion pressure
is again available.
2. LOSS OF FLAME OR GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle (when
flame is not present at the sensor), the control mod-
ule will retry the ignition sequence up to two times
after the sensor cools. If ignition is not achieved, it
will lockout the furnace.
3. POWER FAILURE
If there is a power failure during a heating cycle,
the system will restart the ignition sequence auto-
matieally when power is restored, if the thermostat
still calls for heat.
4. INDUCED DRAFT BLOWER FAILURE
If pressure is not sensed by the pressure switch, it
will not allow the gas valve to open, therefore the
unit will not start. If failure occurs during a running
cycle, the pressure switch will cause the gas valve
to close and shut the unit down.
Carbon monoxide, fire or smoke can cause serious
bodily injury, death, and/or property damage.
A variety of potential sources of carbon monoxide can be
found in a building or dwelling such as gas-fired clothes
dryers, gas cooking stoves, water heaters, furnaces and
fireplaces. The U.S. Consumer Product Safety Commis-
sion recommends that users of gas-burning appliances
install carbon monoxide detectors as well as fire and
smoke detectors per the manufacturers installation in-
Installer's Guide
structions to help alert dwelling occupants of the pres-
ence of fire, smoke or unsafe levels of carbon monoxide.
These devises should be listed by Underwriters Labora-
tories, Inc. Standards for Single and Multiple Station
Carbon Monoxide Alarms, UL 2034 or CSA Interna-
tional Standard, Residential Carbon Monoxide Alarming
Devices, CSA 6.19.
NOTE:
The manufacturer of your furnace does not test any de-
tectors and makes no representations regarding any
brand or type of detector.
Failure to follow safety warnings exactly, could
result in a fire or explosion causing property
damage, personal injury or loss of life.
-- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
-- WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch;
do not use any phone in your building.
Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier,
call the fire department.
-- Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
Flashing Slow---
Flashing Fast---
Continuous ON ---
Continuous OFF ---
2 Flashes---
3 Flashes---
4 Flashes---
5 Flashes ---
6 Flashes---
7 Flashes ---
8 Flashes---
9 Flashes---
INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Normal - No call for Heat
Normal - Call for Heat
Replace IFC
Check Power
System Lockout (Retries or Recycles exceeded)
Draft Pressure Error- Possible problems:
a) Venting problem
b) Pressure switch problem
c) Inducer problem
Open Temperature Limit Circuit
Flame sensed when no flame should be present
115 volt AC power reversed, poor grounding or system voltage too low
Gas valve circuit error
Low flame sense signal
Check Ignitor Circuit and Line "N" to 24VAC "Common" voltage (_<2 volts)
[possible grounding problem]
18-CD21 D1-4 23
Installer's Guide
Trane
6200 Troup Highway
Tyler, TX 75707
For more information contact Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right
your local dealer (distributor) to change design and specifications without notice.

Navigation menu