TVS Electronics SU-CLASSIC500 Uninterruptible Power Supply User Manual service manual

TVS Electronics Limited Uninterruptible Power Supply service manual

user manual

Download: TVS Electronics SU-CLASSIC500 Uninterruptible Power Supply User Manual service manual
Mirror Download [FCC.gov]TVS Electronics SU-CLASSIC500 Uninterruptible Power Supply User Manual service manual
Document ID182188
Application IDHQvznVgB35vnI4Ictf41zw==
Document Descriptionuser manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize16.87kB (210820 bits)
Date Submitted2001-12-05 00:00:00
Date Available2001-12-05 00:00:00
Creation Date0000-00-00 00:00:00
Producing SoftwareAcrobat Distiller 3.0 for Windows
Document Lastmod2001-10-06 09:48:09
Document Titleservice manual
Document CreatorAdobe PageMaker 6.5
Document Author: guest

EXHIBIT C
User Manual
UNINTERRUPTIBLE POWER SUPPLY
USER MANUAL STARTUPS
LITE 500
REV 1.0
User Manual Power UPS 500
Page 1
User Manual Power UPS 500
Dear Customer,
Congratulations on having made an intelligent choice. This product is designed and manufactured with utmost care to give you high quality trouble-free performance in the years to come. Please
register your product by filling the enclosed Business Reply Card and Mailing it to us. This will
enable you to avail free warranty services, in the unlikely requirement of any service assistance.
This registration will also entitle you to receive free mailers on product upgrades, service campaigns, etc. in case you do not find the Business Reply Card in this manual, please write to us for a
new registration card:
Customer support,
TVS Electronics Limited,
No. 34, Developed plots, South Phase,
Industrial Estate, Guindy,
Chennai 600 032.
Please note that it is mandatory to register your product with us. The warranty applicable for
this product is likely to be rejected in case of non-registration of your product with us.
For any queries on our product and/or services you can contact either our branch office or our
authorised service provider. List of service providers are available in this CD.
For any on-line support, please contact your nearest call center, an exclusive Tele-solution
desk available for all TVS-E customers. The contact details are:
E-Mail: careline @esa.tvse.co.in
Carecentre-Chennai
:9622012012
Carecentre-Bangalore :6565010/6561679
Carecentre-Mumbai
:7905717/7668496
Carefax (Fax on demand):+91-44-2327588
Website
:www.tvse.com
OR
TVS Electronics Limited.
No.35:Developed plots, South phase
Guindy industrial Estate
Guindy
Chennai - 600 032.
User Manual Power UPS 500
Page 2
TVS ELECTRONICS LIMITED HARDWARE WARRANTY
What the warranty covers
TVS Electronics Limited, warrants the buyer, that its hardware product sold is free from defective workmanship or material under normal use and service. If a product proves to be defective in
material or workmanship during the warranty period, we will at our sole option repair or replace the
product with a like product.
How long is the warranty
Power UPS 500 is warranted for 3 years without battery for all manufacturing defects. The
battery is warranted for 1 year. During the warranty TVSE will repair or replace the unit and return
to the Dealer/Distributor/Customer.
Whom the Warranty protects
This warranty is only valid for the first consumer/purchaser.
What the warranty does not cover:
1. Any product on which the serial number has been defaced, modified or removed.
2. Damage, deterioration or malfunction resulting from:
a) Accident, misuse, neglect, fire, water, lightning or other acts of nature. Unauthorised
product modification or failure to follow instruction supplied with the product.
b) Repair or attempted repair by anyone not authorised by TVSE.
c) Repair or attempted repair using components not specified/recommended.
d) Damage due to unauthorised shipment.
e) Removal or installation of the product by unauthorised personnel.
f) Operation not maintained with TVSE specification.
g) Causes external to the product, such as electric power fluctuation or failure, improper
earthing.
h) Use of suppliers or products not meeting our specification.
i) Normal wear and tear due to usage.
j) Any other cause that does not relate to product defects.
3. Reinstallation and Preparation of site for installing the UPS.
User Manual Power UPS 500
Page 3
User Manual Power UPS
We thank you for selecting a TVSE Uninterruptible Power Supply (UPS) and recommend
that you read these instructions carefully before installation and start-up of the Power UPS
500.
Please keep this manual in a safe place for future reference.
Contents
1.
Introduction ....................................................................... 6
2.
Safety................................................................................ 7
3.
Outlook And Function ........................................................ 8
4.
Installation ....................................................................... 11
5.
Operation ........................................................................ 12
6.
Alarms ............................................................................. 13
7.
Specifications ...……………………………………………..14
8.
On-Battery Run Time Table ............................................. 15
9.
Troubleshooting ............................................................... 16
10. About The Battery ........................................................... 17
11.
Storage.......................................................................18
12.
Communications Port......…...........................................18
13.
Frequently asked questions...........................................19
13.
How to get service........................................................20
User Manual Power UPS 500
Page 4
1
Introduction
The Power UPS will help you to protect your sensitive equipment like computers and
telecommunication installations against malfunctioning due to non-reliable or distorted mains/
utility/line - voltage
This modern, microprocessor controlled UPS protects the connected equipment against
Surges, Sags, Spikes, etc. by means of an internal filter that works all the time.
During electrical power failures, the unit employs its internal maintenance-free battery to
supply back-up power without any interruption. The UPS is equipped with many features
that will make your equipment to operate more reliable.
The packing kit contains UPS Power UPS 500VA, Output power cable and CD-ROM.
Built-in-Automatic Voltage Regulator: Provides regulated output voltage even under worst
power conditions.
Wide Input voltage range : Minimises calls on battery. Prolongs battery life.
No load shutdown: Avoids unnecessary draining of batteries and increases the battery
life.
User friendly output socket: 3 Indian and 1 European sockets eliminate the need of an
additional power strip.
Surge protected Cyber jack: Protects Modem / Telephone / Network nodes from Lightning (High voltage) surges.
Short circuit protection: Protects connected loads from damages due to short circuits
Cold start: Makes it possible to start the UPS and use battery power in the absence of
power.
User Manual Power UPS 500
Page 5
2
Safety
This UPS can be operated by anyone, without any special training, after reading this
manual
WARNING: RISK OF ELECTRICAL SHOCK:
HIGH-VOLTAGE AND HIGH-CURRENT CIRCUITS INSIDE, even if disconnected from the
mains voltage
Do not remove cover, no user serviceable parts inside
Refer servicing to qualified service personnel
CAUTION: THIS EQUIPMENT MUST BE EARTHED AT ALL TIMES WHILST IN USE
Replace batteries only with the same type and rating
Disconnect batteries during maintenance
Do not dispose the batteries in fire. They will explode. Do not open or mutilate the battery.
The content is toxic and harmful to skin and eyes.
Proper disposal or recycling of the battery is required. Refer to the local codes
User Manual Power UPS 500
Page 6
3. Outlook And Function
3.1 Front panel
LINE BAT.
ON
OFF
Power UPS
500VA
St at u s
Ev en t
Co n d it io n
UPS on mains
Battery fully charged
Mains as well as output is
available
Over load
mains
Output power>105% of
the rated capacity
Battery
Mains and output ON and
charging output
Battery not fully charged
ON
RED/GREEN- RED /YEL L OW
(L ED1)
(L ED2)
User Manual Power UPS 500
Res et
Bu zzer
Green ON
Continuos
Red continuos
Buzzer
continuos
Not
possible
Green ON
continuos
Yellow blinking
1x4 secs
Yellow Blinking
1x4 secs
Red ON
Continuos
Not
possible
Battery
Mains ON and Battery not Green blinking
charging output
fully charged
1x4 secs
off
Abnormal
output Voltage
Bu zzer
Red ON
Page 7
St at u s
Ev en t
UPS ON
Battery
Co n d it io n
Red /Gr een Red /Yello w
L ED1
L ED2
Bu zzer
Res et
Bu zzer
Yellow ON
continuous
Beeps 1x4
Sec.
Pressing
ON button
Battery low
A l a r m s t a r t s w he n b a t t e r y
voltage is 10.5V DC and the unit
s hall t r ip at 10V DC. The UPS
s ho ul d no t g e t O N w he n t he
Battery voltage is less than 10V
Yellow ON
continuos
Beeps 1x2
Sec.
Not
possible
Self test
A f t e r 2 s e c o nd s p r e s s o f O N
sw it ch, Unit shall go t o inver t er
s t a t e f o r 6 S e c . t o c he c k t he Green ON
Battery condition and come back
to mains
Yellow ON
OFF
--
Red
Continuos
Beep
Continuos
Not
possible
O ut p ut p o w e r > 1 0 5 % o f t he
O v e r l o a d rated Capacity. The unit shall trip
inverter
if output power >150% of rated
capacity for more than 500ms
Replace
UPS fails to pass the self test
Battery
Standby
Battery fully charged output
OFF
Green ON
G r e e n
Blinking 1x4
secs
RED Blinks Beeps 1x15
1x15 secs
secs
Off
Not
possible
--
After ‘End Autonomy’ automatic restart possible during 8 hours. After 8 hours restart must
be done manually: press button ‘ON’
User Manual Power UPS 500
Page 8
3.2 Rear Panel
To modem
DB 9 port
(Serial port)
LAN/FAX/MODEM surge protect
From Telephone line
OUT
IN
UPS output without Power
back-up
UPS output
with Power back-up
Input
Power cable
Rating Label
Resettable fuse
Fuse thermal 5A.
StartUPS LITE
Fuse used is a resettable 5A. Reset the fuse in case it is open.
User Manual Power UPS 500
Page 9
4. Installation
4.1 Inspection
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The
packaging is recyclable; save it for re-use or dispose of it properly.
4.2 Placement
Install the UPS in a protected area with adequate air flow and free of excessive dust.
Do not operate the UPS if the temperature and humidity are not within the specified limits.
In colder territories allow the UPS to come to room temperature before operating.
4.3 Connect to Utility
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using
extension cords and adapter plugs.(Ensure proper grounding if you are using extension
cords).
4.4 Connect the Loads
Plug the loads into the output connectors of the UPS. To use the UPS as a master on-off
switch, make sure that all of the loads are switched on.
4.5 Mains connection
UPS can be always connected to the mains, which will allow UPS batteries charging and this
will not damage the UPS. Even when the output is switched off, the input to the UPS should
be ON.
4.6 Charging the Battery
The UPS charges its battery whenever it is connected to utility power. For best results,
charge the battery for 8 hours before use. It is acceptable to use the UPS without first
charging the battery, but run time may be reduced.
4.7 RJ 45 Connection
Connect the telephone line to RJ 45 connector of UPS-IN and UPS-OUT RJ 45 is connected
to the modem input. It protects from Lightning surges.
CAUTION:
1. The UPS output can be used only for electronic loads such as computers and telecom
munications equipment. Please donot connect laser printer to the power backed up
output. It can be connected to the surge protected socket. A laser printer periodically
draws significantly more power than when idle, and will overload the UPS
2. Please ensure more than 5% of the rated total load is connected.
User Manual Power UPS 500
Page 10
5.
Operation
5.1 To reset the UPS microprocessor, in case of an unknown situation:
With the UPS unplugged from the wall outlet, press the OFF button for 2 sec. This will
reset the internal microprocessor.
5.2 Turn off UPS Output Power
To turn off the UPS’s output power, press the OFF button longer than 2 sec.
5.3 Turn on UPS Output Power
Press the ON button 2 sec to switch the UPS on and to supply power to the loads.
NOTE: The UPS is always on (CPU is operating) whenever it is plugged in and mains is
present. Even when the UPS is off it maintains the battery and will respond to commands
received through the computer interface port.
5.4 UPS Self-test
Use the self-test to verify both the operation of the UPS and the condition of the battery.
With the UPS plugged in to normal mains voltage, activate the self-test by pressing the
ON button.
5.5 Auto Voltage Regulation
The UPS automatically corrects high and low utility voltages so that the loads receive
voltage within the normal range.
5.6 DC (Cold) Start
When the UPS is off and there is no utility power, use the cold start feature to apply power
to the loads from the UPS‘s battery. Press the ON button until the red BAT-Led illuminates. Release the button when the loads are powered within 4 seconds.
5.7 Shutdown Mode on 500VA model
In the shutdown mode the UPS stops supplying power to the load, waiting for the return of
mains voltage. If there is no mains voltage present, external devices (e.g. servers) connected to the computer interface can command the UPS to shut down. This is normally
done to preserve battery capacity after the controlled shutdown of protected servers. The
UPS will flash the front panel BAT LED in shutdown mode.
User Manual Power UPS 500
Page 11
6.
Alarms
6.1 On Battery
During on-battery operation, the on-BAT Led comes on and the UPS gives an audible
alarm consisting of one beep every 4 seconds. The alarm stops when the UPS returns to
on-line operation.
Press the ON button during on-battery operation to stop the beeping. This mutes the
current alarm only, the next on-battery alarm will be audible. Shutting off the audible
alarm in this way does not affect the computer interface alarm.
6.2 Overload
When the UPS is overloaded (when the connected loads exceed maximum load) the UPS
gives a continuous audible alarm (beep). The alarm remains on until the overload is
removed. Disconnect nonessential load equipment from the UPS to eliminate the overload.
6.3 Weak Battery
The UPS beeps for 1x30 Sec. and the BAT Led flashes every 30 seconds, if the battery
fails the self-test. The UPS repeats the alarm every 30 sec. Perform the self-test procedure again to confirm the replace battery condition. The alarm stops when the battery
passes the self-test.
User Manual Power UPS 500
Page 12
7. Specifications
Input frequency
Input voltage window
Output frequency
Output voltage mains mode
Output voltage inverter mode
Wave form
Transfer time
Power factor
Battery type
Recharge time
Temperature
Relative humidity
50 ±5 Hz
140-300V AC
50Hz ± 0.1 Hz in battery mode
190-255V
230V±5% output load variation of 0-100%
Quasi sine wave
4msec typical
0.6
Maintenance-free lead acid (12V-7Ah)
8 hours typical from total discharge (UPS may
be used immediately after discharge, but will
Provide shorter backup time.
-10 to 40 °C: operating
-20 to 55 °C: transport/storage for limited time
0 to 95%, non-condensing
Mechanical:
Weight (kg)
Model
Power UPS LITE
500VA
Dimension (h x w x d in mm)
150 x 103 x 295
User Manual Power UPS 500
Net
Gross
7.5
Page 13
8.
On-Battery Run Time Table
Typical battery backup time:
run time (in minutes) as a function of load
L o ad VA/Wat t s
B ac k u p t i m e
Typical UPS load (75%)
100/60
33
300/180
10
500/300
4.5
After ‘End Autonomy’ automatic restart possible during 8 hours. After 8 hours restart must
be done manually: press button ‘ON’
User Manual Power UPS 500
Page 14
9. Trouble shooting
P r o b l em
U P S w i l l no t t ur n
on.
P o s s i b l e C au s e
P r e s s t he O N b ut t o n t o
T he O N b ut t o n w a s no t
p o we r the UP S a nd the
pressed
load
UPS input circuit fuse
open
UPS will not turn on
A nd B AT LE D
flashes
So l u t i o n
Re d uc e the lo a d o n the
UP S b y unp lug g i ng
e q ui p m e nt a nd r e p l a c e
t he f us e b y o ne o f t he
same type and rating
UP S i s i n p r o g r a m m e d
Normal situation
shut-down mode
D i sconnect the computer
i nterface. If the UPS now
U P S w i l l no t t ur n C o m p u t e r i n t e r f a c e
works normally. Check the
ON or OFF.
problem
i nt e r f a c e c a b l e a nd t he
attacehed computer.
U P S c a n no t t r un
ON B AT LE D and S o f t w a r e c o nf i g ur a t i o n
L I N E L E D a r e error
flashing.
D i s c o nne c t t he m a i ns ,
press the OFF button for 4
s e c o nd s . Thi s wi ll re s e t
the internal processor.
UP S o p e r a t e s o n
Test if the input voltage is
b a t t e r y e v e n Very high, low or distorted
too high or low or has too
though line voltage line voltage
much distortion.
exists.
No r m a l UP S o p e r a ti o n,
U P S b e e p s
None. The UPS i s
b ut no m a i ns vo l t a g e
occasionally.
protecting the load.
present
User Manual Power UPS 500
Page 15
P r o b l em
P o s s i b l e C au s e
U P S b uzze r ha s
constant tone, and
UPS overloaded
m a i n s vo l t a g e i s
present
So l u t i o n
Remove the excessive
load
U P S b uzze r ha s
R e m o ve m a i ns p o w e r
constant tone, and UPS overloaded or short
cord Push ’OFF’ button for
m a i ns vo l t a g e i s circuit in battery mode
2 se c.
not present
C ha rg e the b a tte ry. The
U P S ’ s b a t t e r y r e q ui r e s
re c ha rg i ng a fte r a n
extened outage. Batteries
wear out faster when they
a r e us e d o f t e n a nd / o r
The UPS’s battery is weak
w he n o p e r a t e d a t hi g h
UP S d o e s no t
due to recent outage and
t e m p e r a t u r e s . If t h e
p ro vi d e e xp e c te d
a short recharge ti me or
battery is near the end of
back up time
its life-time is ending
i t s s e r vi c e l i f e a nd t he
b a c k u pt i m ei s
i ns uf f i c i e nt , c o ns i d e r
replacing the battery even
i f t he r e p la c e b a t t e r y
indicator is not yet active
The B a t t e r y lo w
Weak battery
Led flashes
User Manual Power UPS 500
A llo w the b a tte ry to
re cha rg e fo r a t le a st te n
h o u r s . If t h e p r o b l e m
persi sts after rechargi ng,
replace the battery.
Page 16
10 About the Battery
1. Life of the battery depends on operating temperature and on the number of discharge
cycles.
2. “WHEN DOES THE BATTERY NEED REPLACING?”
If the BAT Led on the front of the UPS flashes 1x30sec and buzzer sounds, it implies that the
battery will no longer hold a full charge. Under this circumstances, if a power failure occurs,
the UPS runs less than half its normal length of time when compared to a good battery.
Perform the following steps to make sure the battery needs replacing:
1) make sure the UPS is plugged into a live wall outlet
2) charge the UPS for at least 8 hours
3) turn the UPS off and then back on
4) press ON switch to force a self-test
After step 4, if the BAT Led still flashes, there might be something wrong with the battery.
Since the battery will eventually wear out and needs to be replaced, please contact your
local dealer and ask for the battery replacement services
3. Extendability of battery is not possible in this UPS. Please do not add external battery to
the UPS. This will void the Warranty.
User Manual Power UPS 500
Page 17
12 Storage
Store the UPS covered and placed upright in a cool place, with its battery fully charged.
Before storing charge the batteries for at least 24 hours. Disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery.
Make sure that the UPS is switched off.
Storing the unit for longer than 3 months can reduce the life of the batteries. To
maintain the normal life expectancy, recharge the battery. For chargeing the battery refer
section 4.7.
13 Communications Port
The UPS to send information concerning power levels and UPS condition to the computer
The Software can monitor the following.
1.
2.
3.
4.
5.
6.
7.
8.
Mains Input voltage
Mains Input frequency
UPS Output voltage
UPS Output frequency
UPS Load %
Battery voltage
Backup time
Alarms
In the event of batteries near exhaustion, the UPS can send commands for unattended
controlled shutdown of computer systems. UPS can also receive shutdown command
from the computer. All these functions can be realised using host software such as “Safeware”/
”Rakshak” available from TVSE.
Safeware can be installed in IBM PC compatible and works in Windows platform. The
safeware can be down loaded from www.tvse.com
UPS should be connected to the host only through cables supplied by TVS-E. In the cable,the
label indicates which side requires to be connected to the UPS and which one to the PC.The
cable should be connected to the UPS DB9 port and PC comport.
Caution: Do not use any other serial interface cable, other than the one supplied along with the
UPS.
User Manual Power UPS 500
Page 18
SafeWare Program:
Each time the Windows 95 program is started , SafeWare for windows 95 will
automatically start and run unless the user deletes the SafeWare Icon from the Windows
95 Startup folder. By default, SafeWare will start in “Minimized” mode.
Once the SafeWare application has been closed, clicking on the SafeWare icon in
either the SafeWare folder or the Startup folder will once again start SafeWare.
Main SafeWare Screen
The safeWare screen makes a variety of AI-UPS status and control information available
to the user. The left portion of the SafeWare screen displays six large gauges that are
labeled:
Input Voltage
Output voltage
Input Frequency
Output Frequency
Battery Level
Load Level.
These gauges are similar in appearance to automative gauges and graphically indicate
the current values of the specific labeled AI-UPS categories. A text box below each
gauge also shows the exact value or percentage of the specific category.
The top right hand portion of the SafeWare screen has indicators for the input power and
AI-UPS status. The indicators will turn on, off or flash to indicate the current input Power
and AI-UPS condition. they include:
Power Normal
Battery Low
UPS Fault
Power Failure
Battery Weak
UPS Overload
Just below the Power and AI-UPS Status indicators is the Countdown Time display box.
This box will indicate the countdown time that has been entered by the user in the
SafeWare Settings. In case of a loss of utility power, the value in the box will decrease
until it reaches zero at which time SafeWare will cause the Windows 95 save/exit routine
to begin. At any time during the countdown, the user may click on the box to the left of
the Abort Countdown box at which time the countdown will resume, or 2) the AI-UPS
reaches a battery low condition. If a battery low condition occurs, SafeWare will override
the abort command and automatically run the Windows 95 safe/exit routine and cause
the computer system and AI-UPS to shutdown.
The lower right hand portion of the SafeWare screen displays the Waveform chart which
is a graphical waveform representation of the AI-UPS operational parameters. there are
three AI-UPS categories that can be displayed on the Waveform chart:Input/Output
Voltage Waveform, Input/Output Frequency Waveform, and Battery/Load Level Waveform. By clicking on the Toggle Waveform button user can display the different waveforms.
The Waveform chart displays information in a time based format. Time markings below
the chart will inform the user of the time that a power event occurred. Buttons to the right
User Manual Power UPS 500
Page 19
of the chart can be used to view different time periods. They include:Current View, Previous View, Previous Page, Next Page, Scan Left and Scan right. The waveform information can be viewed at any time and will continue to be updated as long as SafeWare is
running. however, if the user terminates the SafeWare program, all waveform information
will be erased unless the user has recorded the information using the Recode button
located under the Toggle Waveform button. If the waveform information is recorded, it is
saved in a DAT file that can later be accessed and viewed using the SafeWare
UPSWave program in the SafeWare folder. The Min/Max levels of the selected waveform
are also shown in boxes under the chart.
The SafeWare screen also has several elements that the user can use to facilitate AIUPS operation, control and diagnosis:
Menu Bat -
Allows access to File, Diagnostic, Option, View, and Help topics.
ToolbarMenu
Allows direct access to all diagnostic and Option topics without using the
Status Bar- Displays current date, time and Next scheduled shutdown information.
User Manual Power UPS 500
Page 20
13. Frequently asked questions:
Q:What is the warranty of the UPS?
A: One year on the Battery, Three years on the unit, against registration of the unit.
Q:Where can I get UPS serviced?
A:UPS required to be carry-in to the nearest TVS-E Authorised Service Provider for
serviceing.
Q:What is the life of the battery?
A:Battery life is 3-5 years depending on the usuage.It depends on the operating temperature and number of discharge cycles.
Q:What is the use of cyber jack?
A:Protects Modem/Telephone/Network nodes from lighting (High voltage)surges.
Q:Can an any RS232 cable be connected?
A:You are required to connect the TVS-E supplied RS232 cable
Q:Can a laser printer be connected to the backed up socket?
A:No. You are required to coneected to the surge protected socket.
Q:Can I keep the mains input switch always ON?
A:Yes. You can keep the input switch always ON. This will enable the UPS to charge the
battery if required. More ever if the mains fails the UPS will automatically shut down.
Q:How much time the battery needs to be charged?
A:It depends on the charge level of the battery. If it is fully discharged, it required around
6 hours to charge to 90% level.
Q:What is no load shutdown?
A:Conditions for no load shutdown.
a) Less than 5% of the rated load.
b) No mains available.
Then UPS will shutdown itself, there by protecting the battery life.
User Manual Power UPS 500
Page 21
How to get Service
As soon as the installation is completed, you are requested to fill up the Warranty Registration
Card. to get your name registered with us. To avail warranty service, please contact the nearest
TVS-E Authorised Dealer/Authorised service centre/Regional office. While registering your call,
please mention/produce (a) Serial no. of the unit (b) date of purchase as mentioned in the invoice of
the product. (c) The problem you are facing with the unit d) Your Tel. no./FAX no./Postal Address/
E-mail address for contact (e) Model name of the product.
Limitation of Implied Warranties.
THERE ARE NO WARRANTIES, EXPRESSED OR IMPLIED, WHICH EXTEND BEYOND
THE DESCRIPTION CONTAINED HEREIN INCLUDING THE IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Exclusion of Damages
Our liability is limited to the cost of repair or replacement of the product. Wherein TVSE may use
reconditioned parts/units or new parts/units. We shall not be liable for:
1. Damage to other products caused by any defects in the product, damages based upon
inconvenience, loss of business opportunity, loss of goodwill, loss of data, loss of software, cost of
substitute equipment, interference with business relationship, claims by third parties or other commercial loss, even if advised of the possibility of such damages.
2. Any other damages whether incidental, consequential or otherwise.
3. Any claim against the customer by any other party.
Life support
We do not recommend the use of our UPS products for life support equipment or direct care
where failure of UPS product could cause failure of or diminished effectiveness of the life support
equipment or the patient care.
Information on this manual is subject to change without notice. This product could include
technical inaccuracies or typographical errors. Changes are periodically made to the information
herein. These changes may be included in the new editions of this product.
User Manual Power UPS 500
Page 22
TVS ELECTRONICS LIMITED
Plot No.34. Developed plots, South phase, Industrial estate
Guindy Chennai-600 032.
Visit us at www.tvse.com
Copyright & Regulatory Information
This manual and software described in it are copyrighted with all rights reserved. This manual may
not be copied, in whole or in part, without written consent. All product names are trademarks and or
registered trademarks of their respective companies.
FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following
measure:
- Reorient or relocated the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into a different outlet circuit from than the receiver.
- Consult an experienced radio/TV technician for help.
CAUTION: Any changes of modifications not expressly approved by the grantee of this
device could void the users authority to operate the equipment.

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
Create Date                     : 1910:10:72 40:94:11
Producer                        : Acrobat Distiller 3.0 for Windows
Subject                         : service manual
Author                          : guest
Creator                         : Adobe PageMaker 6.5
Title                           : service manual
Modify Date                     : 2001:10:06 09:48:09+08:00
Page Count                      : 25
EXIF Metadata provided by EXIF.tools
FCC ID Filing: OSCSU-CLASSIC500

Navigation menu