Packaged Cooling with Electric Heat Rooftop Units Voyager™ 12½ - 25 Tons - 60 Hz October 2004 RT-PRC002-EN Introduction Packaged Rooftop Air Conditioners Through the years,Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today.Trane was the first to introduce the Micro—microelectronic unit controls—and has continued to improve and revolutionalize this design concept. The ReliaTel control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility. Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products. © 2004 American Standard Inc. All rights reserved Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager. Voyager features cutting edge technologies: reliable compressors,Trane engineered ReliaTel controls, computeraided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner you can be certain Voyager Products are built to meet your needs. It’s HardTo Stop ATrane.® RT-PRC002-EN Contents Introduction 2 Features and Benefits 4 Application Considerations 9 10 Selection Procedure 12 13 Model Number Description General Data Controls 17 17 31 47 49 Electric Power 50 Dimension and Weights 70 Mechanical Specifications 81 Performance Data Cooling Performance Fan Performance Heat Performance RT-PRC002-EN 3 Features and Benefits Factory Installed Options • Black Epoxy Pre-Coated Coils • Dehumidification Option • High Efficiency Motors • High Pressure Cutout • Hinged Access Doors • Novar Unit Controls • Novar Return Air Sensor • Powered or Unpowered Convenience Outlet • Supply and/or Return Air Smoke Detector • Thermal Expansion Valve/Face-Split Evaporator Coil Option • Through the Base Electrical with Circuit Breaker • Through the Base Electrical With Disconnect Switch • Through the Base Utilities Access • Two-Inch Pleated Filters 4 Factory or Field Installed Options • Clogged Filter/Fan Failure Switch • Differential Pressure Switches • Discharge Air Sensing Kit • Downflow – Economizer • Electric Heaters • Frostat • LonTalk® Communications Interface • Oversized Motors • Reference or Comparative Enthalpy • Tool-less Hail Guards • Trane Communications Interface (TCI) Field Installed Options • CO2 Sensing • Digital Display Zone Sensor • DualThermistor Remote Zone Sensor • Low Static Drive • High Static Drive • Manual Outside Air Damper • Motorized Outside Air Dampers • Powered Exhaust • Downflow – Roof Curb • Horizontal – Economizer • Remote Potentiometer • Ventilation Override Accessory • Zone Sensors RT-PRC002-EN Features and Benefits Easy to Install, Service and Maintain Quality and Reliability are enhanced through ReliaTel control and logic: Because today’s owners are very costconscious when it comes to service and maintenance, the Trane Voyager was designed with direct input from service contractors.This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money. Voyager does this by offering: —prevents the unit from short cycling, considerably improving compressor life. Quality and Reliability ReliaTel™ Controls (LCI-R) —ensures that the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor. Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure. ReliaTel Makes Installing and Servicing Easy ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays. ReliaTel controls provide these functions as an integral part of the unit.The contractor no longer has to purchase these controls as options and pay to install them. ReliaTel controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature. The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3.This simplified system makes wiring easier for the installer. ReliaTel Makes Testing Easy ReliaTel requires no special tools to run the Voyager unit through its paces. Simply place a jumper betweenTest 1 andTest 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically. —The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit. As long as the unit has power and the “system on” LED is lit, ReliaTel is operational.The light indicates that the controls are functioning properly. ReliaTel features expanded diagnostic capabilities when utilized withTrane Integrated Comfort™ Systems. Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example). Other ReliaTel Benefits The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation. ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters. ReliaTel™ Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint. Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats. The same ReliaTel Board fits all Voyager Packaged Gas/Electrics, Cooling with Electric Heat, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel. RT-PRC002-EN 5 Features and Benefits Outstanding Standard and Optional Components Black Epoxy Pre-Coated Coils The pre-coated coils are an economical option for protection in mildly corrosive environments. Condenser Coil Voyager boasts a patent-pending 1+1+1 condenser coil, permanently gapped for easy cleaning. Hinged Access Doors These doors permit easy access to the filter, fan/heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners. Cabinet Integrity For added water integrity, Voyager has a raised 11/8" lip around the supply and return of the downflow units to prevent water from blowing into the ductwork. Clogged Filter/Fan Failure Switch A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. CO2 Sensing The CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements.The CO2 sensor kit is available as a field installed accessory. Colored And Numbered Wiring Save time and money tracing wires and diagnosing the unit. Compressors Voyager contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models. Refrigerant Circuits All Voyager 12½-25 ton units shall have crankcase heaters, low and high pressure controls as standard. 6 High Static Drive Accessory Available on many models, this high static drive accessory extends the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory. Digital Display Zone Sensor The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor should be utilized with ReliaTel™ controls. Discharge Air Sensing Kit Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel Options Module. Downflow And Horizontal Economizers The economizers come with three control options — dry bulb is standard, enthalpy and differential enthalpy are optional. Dual Thermistor Remote Zone Sensor This sensor will reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. LonTalk® Communications Interface The LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device or directly with generic LonTalk Network Building Automation System Controls. Power Exhaust Option This option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems. Quick-Access Panels Remove three or fewer screws for access to the standardized internal components and wiring. Quick-Adjust Idler Arm With the Quick-Adjust Idler Arm, the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money. Factory Built Roof Curbs Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection. Fresh Air 0 - 25% manual or 0 - 50% motorized outside air hoods are available. RT-PRC002-EN Features and Benefits Reference or Comparative Enthalpy Measures and communicates humidity while maximizing comfort control. Sloped Drain Pans Standard on every unit. Standardized Components Components are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voyager. Due to standardized components throughout the Voyager line, contractors/ owners can stock fewer parts. Supply and/or Return Air Smoke Detector With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. Tool-less Hail Guards Tool-less, hail protection quality coil guards shall be either factory or field-installed for condenser coil protection.This option protects the condenser coil from vandalism and/or hail damage. VariTrac When Trane’s changeover VAV System for light commercial applications is coupled with Voyager, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac. Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition. Ventilation Override Accessory With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust.The transition occurs when a binary input on the RTOM is closed (shorted).This would typically be a hard wired relay output from a smoke detector or fire control panel.The ventilation override kit is available as a field installed accessory. Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. Zone Sensors Available in programmable, automatic and manual styles. Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorousTrane requirements. Rigorous Testing The fan and idler arm assembly designs have been tested to over 300,000 cycles each. Our combined cycle testing is now over 7,000,000 cycles. All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig. All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Voyager units incorporate either a one piece top or theTrane-Tite-Top (T3). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit.These overlapped edges are gasketed and sealed to ensure superior water integrity. VariTrac™ Trane Communication Interface (TCI) Available factory or field installed.This module when applied with the ReliaTel™ easily interfaces with Trane’s Integrated ComfortTM System. RT-PRC002-EN 7 Features and Benefits Easy to Install and Service Conversionless Units The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them.These duct flanges are a time and cost saver. Powered or Unpowered Convenience Outlet This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered.This option can only be ordered when theThrough the Base Electrical with either the Disconnect Switch, or Circuit Breaker, option is ordered.This option is available on all downflow models. Factory Installed Options A wide variety of Factory Installed Options (FIOPs) are available. Added Efficiency Airflow Airflow is outstanding.The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution. High Efficiency Motors This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models. Easy Access Low Voltage Terminal Board Voyager’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire.This is another cost and time saving installation feature. U-shaped Airflow U-shaped airflow allows for improved static capabilities. Low Ambient Cooling Cooling capabilities down to 0°F as standard. Oversized Motors Factory or field installed oversized motors available for high static applications. Single Point Power A single electrical connection powers the unit. Low Voltage Connections The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3.This simplified system makes it easy for the installer to wire. Single Side Service Single side service is standard on all units. Through the Base Electrical with Circuit Breaker This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. This option is available on all downflow models. Through the Base Electrical with Disconnect Switch Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. This option is available on all downflow models. Electric Heaters Electric heat modules are available within the basic unit. If ordering theThrough the Base Electrical option with an Electrical Heater, the heater must be factory installed. 8 One of our Finest Assets: Trane Sales Representatives are a Support group that can assist you with: — Product — Application — Service — Training — Special Applications — Specifications — Computer Programs and much more Voyager has the features and benefits that make it first class in the light commercial rooftop market. Designed with input from field contractors and engineers, its U-shaped airflow performance is outstanding. Through the Base Utilities Access An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch. RT-PRC002-EN Application Considerations Application of this product should be within the cataloged airflow and cooling considerations. Low Ambient Cooling This Voyager line features, as standard, low ambient cooling down to 0°F. The following options need to be included/ considered when low ambient applications are required: continuous fan operation, crankcase heaters, thermal expansion valves, frostat. Contact your local Trane Representative for more assistance with low ambient cooling applications. Barometric Relief This product line offers an optional barometric relief damper included in the downflow economizer accessory.This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space. Power Exhaust Accessory The power exhaust accessory is available on all 12½-25 ton downflow units.This accessory can be field installed and will assist in relieving building pressurization. Condensate Trap The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle. Clearance Requirements The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the localTrane sales personnel. Unit Pitch These units have sloped condensate drain pans. Units must be installed level, any unit slope must be toward access side of unit. NOTE:THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED. PRESSURE DROP OF THE RETURN AIR SYSTEM SHOULD BE CONSIDEREDTO CONTROL BUILDING PRESSURIZATION. RT-PRC002-EN 9 Selection Procedures Cooling Capacity Step 1 Calculate the building’s total and sensible cooling loads at design conditions. Use theTrane calculation methods or any other standard accepted method. Factors used in unit selection: A Total Cooling Load: 180 MBh B Sensible Cooling Load: 129 MBh C Airflow: 6000 cfm D Electrical Characteristics: 460/60/3 E Summer Design Conditions: Entering Evaporator Coil: 80 DB, 67 WB Outdoor Ambient: 95 DB F External Static Pressure: 0.49 in. wg G Rooftop - downflow configuration H Accessories • Roof curb • Economizer • Electric Heat I Heating • Capacity 115 MBh • 460 volt/3 phase Electric Heat —at 6000 cfm Step 2 As a starting point, a rough determination must be made of the size of the unit.The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size. 180 MBh / 12 MBh = 15.0Tons Step 3 Table PD - 2 shows that a TCD180B4 has a gross cooling capacity of 184 MBh and 130 MBh sensible capacity at 6000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator. To Find Capacity at Intermediate Conditions Not in the Table When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity. Note: Extrapolation outside of the table conditions is not recommended. Step 4 In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity.The amount of heat that the fan motor generates is dependent on the effort by the motor cfm and static pressure.To determine the total unit static pressure you add the external static pressure to the additional static related by the added features: External Static (duct system) 0.49 wg Standard Filter 1 in. from Table PD-35 0.10 wg Economizer 0.04 wg (100% Return Air) from Table PD-35 Electric Heater Size 36 kw 0.07 wg from Table PD-35 Step 5 If the performance will not meet the required load of the building -total or sensible cooling load, try a selection at the next higher size unit. Heating Capacity Step 1 Calculate the building heating load using theTrane calculation form or other standard accepted method. Step 2 Size the system heating capacity to match the calculated building heating load.The following are building heating requirements: A Total heating load of 115.0 MBH B 6000 cfm C 460 volt/3 phase Power Supply The electric heat accessory capacities are listed inTable PD-36. From the table, a 36 kw heater will deliver 122.94 MBH at 480 volts. In order to determine capacity at 460 volts, the heater voltage correction factor fromTable PD-37 must be used. Therefore, 122.94 MBH x .94 (voltage correction factor) = 115.6 MBH. Air Delivery Selection Total Static Pressure 0.60 wg Note: The Evaporator Fan Performance Table PD-18 has already accounted for the pressure drop for standard filters and wet coils (see note belowTable PD-18). Therefore, the actual total static pressure is 0.60 -0.10 (from Table PD-35) = 0.50 wg. With 6000 cfm and 0.50 wg. Table PD-18 shows 2.56 bhp for this unit. Note below the table gives a formula to calculate Fan Motor Heat, 3.15 x bhp = MBH. 3.15 x 2.56 = 8.06 MBH. External static pressure drop through the air distribution system has been calculated to be 0.50 inches of water. From Table PD-35 static pressure drop through the economizer is 0.04 and the 36 kw heater is 0.07 inches of water (0.49 + 0.04 + 0.07). Enter Table PD-18 for a TCD180B4 at 6000 cfm and 0.50 static pressure. The standard motor at 777 rpm will give the desired airflow at a rated bhp of 2.71. Now subtract the fan motor heat from the gross cooling capacity of the unit: NetTotal Cooling Capacity = 184 MBH - 8.06 = 175.9 MBH. Net Sensible Cooling Capacity = 130 MBH - 8.06 = 121.9 MBH. 10 RT-PRC002-EN Selection Procedure Dehumidification Selection Determine normal unit cooling and heating capacities as previously described in the selection procedures on prior page. Typical 20 ton TFD241C 6400 cfmTotal Supply airflow 2560 cfm Outside Air (40%) 3840 cfm Return Air 0.41” External Static Pressure OA Conditions Part load day and raining 68°F db 67°F wb 66.5 dp 95% RH RA’ conditions 75°F db 63°F wb 52% RH 55.9 dp Step 1: Determine the mixed/ entering air condition (MA’) MA’ = (% outside air*outside air dry-bulb temperature) + (% return air*return air dry-bulb temperature) MA’ = (0.40*68°F) + (0.60*75°F) MA’ = 72.20°F db Note: Repeat for wet-bulb temperature (wb). Plot on psychrometric chart. MA’ 72.2°F db 64.7°F wb Step 2: Determine static pressure drop add for reheat Table PD-35 shows a static pressure drop of 0.35” for the reheat coil and an additional .04 for the mandatory 2” pleated filters required when ordering the dehumidification option.Total static pressure = 1.0+0.035+0.04=1.075 (≅1.1 for manual calculations) Do not forget to also add any additional static from other accessories. Table PD-29 (airflow table for 20 ton dehumidification units) indicates that a standard motor and drive is needed for this airflow and static pressure range. RT-PRC002-EN OA 68°F DB, 67°F WB RA' 75°F DB, 52% RH MA' 72.2°F DB 65°F WB SA' 47°F DB SA 73°F DB OA MA' RA' SA' REHEAT SA Chart C-1 Step 3a: Determine leaving evaporator temperature SA’ Leaving Unit Temperature = SA’ Utilizing the manual selection method as previously described and the formula ∆Temp = cooling capacity in Bth (cfm)(1.085) or using the TOPSS™ program determine the leaving evaporator temperature (temperature without the addition of fan heat). 517.74 db 51.03 wb Step 3b: Determine leaving unit temperature in standard cooling mode Find the leaving unit temperature including fan heat as discussed in prior selection procedures and using the temperature formula from Step 3a or refer to yourTOPSS selection. 53.6 db 51 wb 84% RH 49% dp Step 4: Determine reheat temperature rise Using the leaving evaporator temp, go to PD-39 and find the reheat temperature rise for that particular cfm: 17.55°F db Step 5: Determine leaving unit temperature with reheat active (SA) Reheat temperature (obtained in step 3) + SA’ = SA 17.55°F db + 53.6°F = 71.2°F db SA’=71.2°F 51 wb 20.8 RH 29.4 dp Consider Chart C-1. If the space relative humidity is equal to or above the space relative humidity setpoint, the Dehumidification option will: • Energize compressor or both compressors (2 stage compressor units). • Hot gas reheat valve is energized and hot gas is diverted to the reheat coil. • Dehumidification/reheat is terminated when space humidity is reduced to 5% below relative humidity setpoint. At MA’, air enters the RTU.The RTU filters, cools, and dehumidifies the air as it moves through the evaporator coil. Air leaves the evaporator coil saturated at the preset dew point condition (SA’) and is reheated by the hot gas reheat coil to deliver 71°F (SA) supply air to the space. Note: Reheat temperature rise is based on supply airflow and leaving evaporator coil temperature. 11 Model Number Description Packaged Cooling with Electric Heat Unit Typical Model Nomenclature T C D 1 5 0 C 3 0 0 A A 1 2 3 4 5 6 7 8 9 10 11 12 Digits 1, 2 - Product Type TC = Packaged Cooling, Electric Heat TF = With Factory Installed Options Digit 7- Major Development Sequence Digit 8 - Electrical Characteristics Digit 3 - Airflow Configuration 3 = 4 = W= K = D = Downflow H = Horizontal Digit 9, 10 - Factory-Installed Options Digits 4, 5, 6 - Nominal Gross Cooling Capacity (MBh) 150 151 180 181 210 211 240 241 300 301 = = = = = = = = = = 12½ Tons Standard Efficiency 12½ Tons High Efficiency 15 Tons Standard Efficiency 15 Tons High Efficiency 17½ Tons Standard Efficiency 17½ Tons High Efficiency 20 Tons Standard Efficiency 20 Tons High Efficiency 25 Tons Standard Efficiency 25 Tons High Efficiency 208-230/60/3 460/60/3 575/60/3 380/60/3 00 = 0A = 0B = 0C = 0F = 0G= 0H = 0J = 0K = 0L = 0M = 0N= 0P = 0R = No Factory-installed Options Factory-installed Economizer Oversized Motor Downflow Economizer and Oversized Motor Trane Communications Interface (TCI) Downflow Economizer and TCI TXV/Face-Split Evaporator Oversized Motor and TXV/Face-Split Evaporator Downflow Economizer, Oversized Motor, and TXV/Face-Split Evaporator Downflow Economizer with TXV/FaceSplit Evaporator Reheat Coil Downflow Economizer and Reheat Coil Oversized Motor and Reheat Coil Downflow Economizer, Oversized Motor and Reheat Coil Digit 11- Minor Design Sequence Digit 12- Service Digit 12 RT-PRC002-EN General Data (12½, 15 Ton) Standard Efficiency Table GD - 1— General Data Cooling Performance1 Gross Cooling Capacity EER2 Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value3 System Power (KW) Compressor No./Type Sound Rating (BELS)4 Outdoor Coil —Type Tube Size (in.) O.D. Face Area (sq ft) Rows/FPI Indoor Coil —Type Tube Size (in.) Face Area (sq ft) Rows/FPI Refrigerant Control Drain Connection No./Size (in.) Outdoor Fan —Type No. Used/Diameter (in.) DriveType/No. Speeds CFM No. Motors/HP Motor RPM Indoor Fan —Type No. Used Diameter x Width (in.) DriveType/No. Speeds No. Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized) Filters —Type Furnished6 (No.) Size Recommended (in.) Downflow Horizontal Refrigerant Charge (Lbs of R-22)5 12½Ton Downflow and Horizontal Units TC*150D3, D4, DW, DK 15Ton Downflow and Horizontal Units TC*180B3, B4, BW, BK 150,000 9.8 5,000/4,400 142,000 10.5 14.49 182,000 9.9 6,000/5,300 174,000 10.2 17.57 2/Scrolls 9.2 Hi-Performance .375 24.18 2/16 Hi-Performance .375 17.5 2/15 Short Orifice 1/1.00 NPT Propeller 2/26 Direct/1 10,600 2/.50 1,100 FC Centrifugal 1 15 x 15 Belt/1 1 3.0/5.0 1,740/3,450 145T/145T Throwaway 2/Scrolls 9.2 Hi-Performance .375 27.12 3/16 Hi-Performance .375 17.5 2/15 Short Orifice 1/1.00 NPT Propeller 2/26 Direct/1 10,200 2/.50 1,100 FC Centrifugal 1 15 x 15 Belt/1 1 3.0/5.0 1,740/3,450 145T/145T Throwaway (2) 20 x 20 x 2, (4) 20 x 25 x 2 (2) 20 x 20 x 2, (4) 20 x 25 x 2 9.3/9.4/Circuit (2) 20 x 20 x 2, (4) 20 x 25 x 2 (2) 20 x 20 x 2, (4) 20 x 25 x 2 17.5/9.5/Circuit Notes: 1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360. 3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370. 5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 6. Optional 2 inch pleated filters are also available. 7. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data. *Indicates both downflow and horizontal units. RT-PRC002-EN 13 General Data (17½, 20, 25 Ton) Standard Efficiency Table GD - 2 — General Data 17½Ton Downflow and Horizontal Units TC*210C3, C4, CW, CK Cooling Performance1 Gross Cooling Capacity 210,000 9.8 EER2 Nominal CFM / ARI Rated CFM 7,000/5,800 ARI Net Cooling Capacity 196,000 10.0 Integrated Part Load Value3 System Power (KW) 20.0 Compressor No./Type 2/Scrolls Sound Rating (BELS)4 9.4 Outdoor Coil —Type Hi-Performance Tube Size (in.) O.D. .375 Face Area (sq ft) 27.12 Rows/FPI 3/16 Indoor Coil —Type Hi-Performance Tube Size (in.) .375 Face Area (sq ft) 17.50 Rows/FPI 4/15 Refrigerant Control Short Orifice Drain Connection No./Size (in.) 1/1.00 NPT Outdoor Fan —Type Propeller No. Used/Diameter (in.) 2/26 DriveType/No. Speeds Direct/1 CFM 13,400 No. Motors/HP 2/1.0 Motor RPM 1,125 Indoor Fan —Type FC Centrifugal No. Used 1 Diameter x Width (in.) 15 x 15 DriveType/No. Speeds Belt / 1 No. Motors 1 Motor HP (Standard/Oversized) 5.0/7.5 Motor RPM (Standard/Oversized) 3,450/3,470 Motor Frame Size (Standard/Oversized) 145T/184T Throwaway Filters —Type Furnished7 (No.) Size Recommended (in.) Downflow (2) 20 x 20 x 2, (4) 20 x 25 x 2 Horizontal (2) 20 x 20 x 2, (4) 20 x 25 x 2 21.0/14.3/Circuit6 Refrigerant Charge (Lbs of R-22)5 20Ton Downflow and Horizontal Units TC*240B3, B4, BW, BK 25Ton Downflow and Horizontal Units TC*300B3, B4, BW, BK 242,000 9.7 8,000/7,000 232,000 10.0 23.91 290,000 9.7 10,000/8,750 272,000 9.8 28.05 2/Scrolls 9.4 Hi-Performance .375 35.30 3/16 Hi-Performance .375 26.00 2/15 Short Orifice 1/1.00 NPT Propeller 2/26 Direct/1 14,600 2/1.0 1,125 FC Centrifugal 1 18 x 18 Belt / 1 1 5.0/7.5 3,450/3,470 145T/184T Throwaway 2/Scrolls 9.4 Hi-Performance .375 36.43 2/16 Hi-Performance .375 26.00 3/15 Short Orifice 1/1.00 NPT Propeller 2/28 Direct/1 16,700 2/1.0 1,125 FC Centrifugal 1 18 x 18 Belt / 1 1 7.5/NA 3,470/NA 184T/NA Throwaway (4) 20 x 20 x 2, (4) 20 x 25 x 2 (8) 20 x 25 x 2 18.9/21.0/Circuit (4) 20 x 20 x 2, (4) 20 x 25 x 2 (8) 20 x 25 x 2 17.0/Circuit Notes: 1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½ - 20 ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93. 2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360. 3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370. 5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 6. Refrigerant charge for horizontal models is 21.5/14.5 per circuit. 7. Optional two inch pleated filters are also available. 8. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data. *Indicates both downflow and horizontal units. 14 RT-PRC002-EN General Data (12½, 15 Ton) High Efficiency Table GD - 3 — General Data Cooling Performance1 Gross Cooling Capacity EER2 Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value3 System Power KW Compressor No./Type Sound Rating (BELS)4 Outdoor Coil —Type Tube Size (in.) O.D. Face Area (sq ft) Rows/FPI Indoor Coil —Type Tube Size (in.) Face Area (sq ft) Rows/FPI Refrigerant Control Drain Connection No./Size (in.) Outdoor Fan —Type No. Used/Diameter (in.) DriveType/No. Speeds CFM No. Motors/HP Motor RPM Indoor Fan —Type No. Used Diameter x Width (in.) DriveType/No. Speeds No. Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized) Filters —Type/Furnished? (No.) Size Recommended (in.) Optional Hot Gas Reheat Coil —Type Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI Refrigerant Charge (Lbs of R-22) 5/Circuit Standard Optional Hot Gas Reheat Coil 12½Ton Downflow and Horizontal TC*151C3,C4,CW 15Ton Downflow and Horizontal TC*181C3,C4, CW 154,000 11.3 5,000/4,400 146,000 11.5 12.92 189,000 11.58 6,000/5,300 180,000 13.3 15.653 2/Scrolls 9.2 Hi-Performance 0.375 27.12 3/16 Hi-Performance 0.375 17.50 3/15 Short Orifice9 1/1.0 NPT Propeller 2/26 Direct/1 10,400 2/.50 1100 FC Centrifugal 1 15 x 15 BELT/1 1 3.0/5.0 1740/3450 145T/145T Throwaway/Yes8 (2)20 x 20 x 2 (4)20 x 25 x 2 Hi-Performance 0.375 17.5 1/16 2/Scrolls 9.2 Hi-Performance 0.375 35.30 3/16 Hi-Performance 0.375 26.00 3/15 Short Orifice8 1/1.0 NPT Propeller 2/26 Direct/1 11,000 2/.50 1100 FC Centrifugal 1 18 x 18 BELT/1 1 3.0/5.0 1740/3450 145T/145T Throwaway/Yes8 (4) 20 x 20 x 2 (4) 20 x 25 x 2 Hi-Performance 0.375 26 1/16 15.0/13.89 15.3/14.3 25.0/13.08 27.8/11.4 Notes: 1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 2. EER is rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370. 5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 6. Face area for Indoor Coil on horizontal models is 12.36. 7. Horizontal models have 4 - 20 x 25 x 2 filters. 8. Optional two inch pleated filters are also available for 12½ ton models. 9. TXV/Face-Split Option (Downflow Only) TCD151C3,4,W (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0. *Indicates both downflow and horizontal units. RT-PRC002-EN 15 (17½, 20, 25 Ton) General Data High Efficiency Table GD - 4 — General Data 17½Ton Downflow and Horizontal TC*211C3,C4,CW 20Ton Downflow and Horizontal TC*241C3,C4,CW 25Ton Downflow and Horizontal TC*301C3,C4,CW 220,000 11.0 7,000/6,200 208,000 12.0 18.91 268,0009 10.6 8,000/7,000 250,0009 11.2 23.589 300,00011 10.411 10,000/8,750 278,000 11.011 26.7311 2/Scrolls 2/Scrolls 2/Scrolls 9.4 Hi-Performance 0.375 35.30 3/16 Hi-Performance 0.375 26.00 4/15 Short Orifice9 1/1.0 NPT Propeller 2/26 Direct/1 13,700 2/1.00 1125 FC Centrifugal 1 18 x 18 BELT/1 1 5.0/7.5 3450/3470 145T/184T Throwaway (4/4)20 x 20 x 2/20 x 25 x 26 Hi-Performance 0.375 26 1/16 9.4 Hi-Performance 0.375 3/16 Hi-Performance 0.375 26.00 4/15 Short Orifice11 1/1.0 NPT Propeller 2/26 Direct/1 13,700 2/1.00 1125 FC Centrifugal 1 18 x 18 BELT/1 1 7.5/NA 3470/NA 184T/NA Throwaway (4/4)20 x 20 x 2/20 x 25 x 26 — — — — 21.8/21.89 21.3/21.0 24.5/24.511 — Cooling Performance1 Gross Cooling Capacity EER2 Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value3 System Power KW Compressor No./Type Sound Rating (BELS)4 9.4 Outdoor Coil —Type Hi-Performance Tube Size (in.) O.D. 0.375 Face Area (sq ft) 35.30 Rows/FPI 3/16 Indoor Coil —Type Hi-Performance Tube Size (in.) 0.375 Face Area (sq ft) 26.000 Rows/FPI 4/15 Refrigerant Control Short Orifice Drain Connection No./Size (in.) 1 /1.0 NPT Outdoor Fan —Type Propeller No. Used/Diameter (in.) 2/26 DriveType/No. Speeds Direct/1 CFM 12,800 No. Motors/HP 2/1.00 Motor RPM 1125 Indoor Fan —Type FC Centrifugal No. Used 1 Diameter x Width (in.) 18 x 18 DriveType/No. Speeds BELT/1 No. Motors 1 Motor HP (Standard/Oversized) 5.0/7.5 Motor RPM(Standard/Oversized) 3450/3470 Motor Frame Size (Standard/Oversized) 145T/184T Filters —Type Furnished7 Throwaway (No.) Size Recommended (in.) (4/4)20 x 20 x 2/20 x 25 x 26 Optional Hot Gas Reheat Coil —Type — Tube Size (in.) OD — Face Area — Rows/FPI — Refrigerant Charge (Lbs of R-22) 5 / Circuit Standard 25.7/12.510 Optional Hot Gas Reheat Coil — Notes: 1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. 15 - 20 ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93. 2. EER is rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370. 5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 6. Horizontal models have 8 - 20 x 25 x 2 filters. 7. Optional two inch pleated filters are also available. 8. TXV/Face-Split Option (Downflow Only) TCD181C3,4,W (EER):11.4; (System Power kW): 15.79; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 26.0/12.0 9. TXV/Face-Split Option (Downflow Only) TCD241C3,4,W (Gross Cooling Capacity):259,000; (ARI Net Cooling Capacity): 244,000; (System Power kW): 23.02; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 21.5/22.2 10. TXV/Face-Split Option (Downflow Only) TCD211C3,4,W Refrigerant Charge): 27.0/10.0 11. TXV/Face-Split Option (Downflow Only) TCD301C3,4,W (EER): 10; (Gross Cooling Capacity): 294,000; (ARI Net Cooling Capacity): 272,000; (IPLV): 10.6; System Power kW): 27.2; Refrigerant Control: Expansion Valve; (Refrigerant Charge): 21.0/23.0 *Indicates both downflow and horizontal units. 16 RT-PRC002-EN Performance Data (12½, 15 Ton) Standard Efficiency Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*150D3, D4, DW, DK AmbientTemperature 85 CFM Airflow 4500 5000 5500 6000 95 105 115 Enter Dry Entering Wet Bulb Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5 80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6 85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5 90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0 75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6 80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2 85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9 90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0 75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9 80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7 85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0 90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0 75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0 80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5 85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8 90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*180B3, B4, BW, BK AmbientTemperature 85 CFM Airflow 5400 6000 6600 7200 95 105 115 Enter. Dry Entering Wet Bulb Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 168.0 133.0 188.0 106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0 172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2 80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7 85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0 90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0 75 172.0 140.0 190.0 110.0 199.0 74.3 161.0 134.0 184.0 106.0 195.0 71.7 151.0 129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9 80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9 85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0 90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0 75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1 80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6 85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0 90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0 75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0 109.0 191.0 71.0 142.0 142.0 170.0 103.0 183.0 67.2 80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4 85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0 90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. RT-PRC002-EN 17 Performance Data (17½, 20 Ton) Standard Efficiency Table PD-3 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase TC*210C3, C4, CW, CK 85 CFM Airflow 6300 7000 7700 8400 AmbientTemperature 95 105 115 Enter Dry Entering Wet Bulb Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8 80 200.0 200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0 168.0 183.0 147.0 205.0 106.0 85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0 188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0 90 219.0 219.0 220.0 217.0 230.0 164.0 214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0 75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4 80 206.0 206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0 188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0 85 216.0 216.0 220.0 197.0 230.0 144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0 90 224.0 224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0 75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0 126.0 208.0 75.0 80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0 85 220.0 220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0 90 226.0 226.0 226.0 226.0 235.0 176.0 223.0 223.0 222.0 222.0 229.0 179.0 216.0 216.0 216.0 216.0 223.0 184.0 208.0 208.0 208.0 208.0 214.0 186.0 75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5 80 214.0 214.0 221.0 174.0 230.0 120.0 208.0 208.0 214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0 85 222.0 222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0 90 229.0 229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0 220.0 219.0 219.0 225.0 190.0 212.0 212.0 212.0 212.0 216.0 193.0 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity Table PD-4 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*240B3, B4, BW, BK AmbientTemperature (F) 85 CFM Airflow 7200 8000 8800 9600 95 105 115 Enter. Dry Entering Wet Bulb (F) Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 223.0 180.0 251.0 143.0 265.0 97.7 209.0 173.0 242.0 137.0 260.0 94.3 195.0 165.0 228.0 130.0 252.0 90.3 180.0 158.0 212.0 135.0 241.0 85.5 80 226.0 214.0 252.0 173.0 267.0 131.0 208.0 208.0 242.0 169.0 261.0 127.0 197.0 197.0 228.0 162.0 253.0 122.0 186.0 186.0 213.0 155.0 242.0 117.0 85 235.0 235.0 253.0 204.0 268.0 158.0 224.0 224.0 242.0 200.0 262.0 156.0 213.0 213.0 229.0 194.0 253.0 153.0 201.0 201.0 214.0 188.0 242.0 149.0 90 248.0 248.0 255.0 234.0 271.0 185.0 239.0 239.0 245.0 232.0 264.0 185.0 228.0 228.0 228.0 228.0 255.0 183.0 217.0 217.0 217.0 217.0 243.0 179.0 75 229.0 190.0 255.0 148.0 267.0 99.4 215.0 183.0 246.0 142.0 262.0 96.1 200.0 175.0 233.0 136.0 254.0 92.2 185.0 168.0 218.0 129.0 244.0 87.1 80 228.0 228.0 256.0 180.0 268.0 134.0 217.0 217.0 246.0 176.0 264.0 131.0 205.0 205.0 233.0 171.0 255.0 127.0 193.0 193.0 218.0 164.0 245.0 121.0 85 243.0 243.0 257.0 212.0 271.0 162.0 233.0 233.0 247.0 210.0 265.0 161.0 222.0 222.0 234.0 206.0 257.0 158.0 210.0 210.0 220.0 199.0 245.0 155.0 90 255.0 255.0 259.0 245.0 273.0 190.0 247.0 247.0 247.0 247.0 267.0 191.0 237.0 237.0 237.0 237.0 258.0 190.0 226.0 226.0 226.0 226.0 247.0 187.0 75 234.0 199.0 257.0 151.0 268.0 101.0 220.0 192.0 249.0 147.0 263.0 97.9 205.0 184.0 237.0 141.0 256.0 93.7 190.0 177.0 222.0 134.0 246.0 88.6 80 236.0 236.0 259.0 185.0 270.0 136.0 224.0 224.0 249.0 183.0 265.0 134.0 212.0 212.0 237.0 178.0 257.0 130.0 200.0 200.0 222.0 172.0 247.0 126.0 85 250.0 250.0 260.0 220.0 273.0 165.0 240.0 240.0 251.0 219.0 267.0 165.0 229.0 229.0 239.0 216.0 259.0 163.0 217.0 217.0 225.0 210.0 248.0 160.0 90 260.0 260.0 263.0 254.0 275.0 194.0 253.0 253.0 253.0 253.0 270.0 196.0 244.0 244.0 244.0 244.0 261.0 196.0 233.0 233.0 233.0 233.0 250.0 194.0 75 238.0 208.0 259.0 154.0 269.0 103.0 224.0 201.0 251.0 151.0 265.0 99.6 209.0 193.0 240.0 146.0 257.0 95.1 194.0 186.0 225.0 139.0 248.0 89.2 80 242.0 242.0 261.0 190.0 271.0 137.0 231.0 231.0 252.0 189.0 266.0 136.0 219.0 219.0 240.0 185.0 259.0 133.0 206.0 206.0 226.0 180.0 249.0 129.0 85 254.0 254.0 263.0 227.0 274.0 167.0 246.0 246.0 254.0 227.0 269.0 168.0 236.0 236.0 243.0 225.0 261.0 167.0 224.0 224.0 229.0 220.0 251.0 165.0 90 264.0 264.0 264.0 264.0 277.0 198.0 258.0 258.0 258.0 258.0 272.0 201.0 249.0 249.0 249.0 249.0 263.0 202.0 239.0 239.0 239.0 239.0 252.0 201.0 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 18 RT-PRC002-EN Performance Data (25 Ton) Standard Efficiency Table PD-5— Gross Cooling Capacities (MBH) 25 Ton Three Phase TC*300B3, B4, BW, BK AmbientTemperature (F) 85 CFM Airflow 9000 10000 10500 11000 Enter. Dry Bulb 61 (F) MBH SHC 75 266 224 80 270 268 85 286 286 90 301 301 75 272 237 80 277 277 85 294 294 90 308 308 75 275 243 80 282 282 85 298 298 90 312 312 75 278 248 80 286 286 85 301 301 90 314 314 67 MBH SHC 299 174 300 215 301 255 304 295 303 180 304 223 306 266 310 309 305 183 306 227 308 272 311 311 306 185 308 231 310 277 314 314 95 73 MBH SHC 319 118 321 161 323 196 326 232 322 120 324 171 327 208 329 239 323 122 325 174 328 216 330 256 324 123 325 160 327 224 330 266 61 MBH SHC 247 215 252 252 272 272 289 289 253 227 262 262 282 282 297 297 256 233 267 267 286 286 301 301 258 239 271 271 289 289 304 304 67 MBH SHC 285 167 285 209 286 250 289 289 290 174 290 219 291 263 297 297 291 177 292 223 294 270 301 301 293 181 294 228 296 276 304 304 105 Entering Wet Bulb (F) 73 61 67 MBH SHC MBH SHC MBH SHC 309 113 228 205 266 172 311 155 237 237 266 200 312 194 256 256 267 242 314 231 275 275 275 275 312 115 234 218 271 165 314 161 246 246 271 211 316 200 266 266 273 257 318 240 284 284 284 284 314 117 236 223 273 188 315 162 250 250 273 216 317 203 270 270 276 264 320 244 288 288 288 288 315 118 239 229 275 172 316 163 254 254 276 221 319 205 274 274 278 271 321 248 291 291 291 291 115 73 MBH SHC 297 108 297 149 298 189 300 229 300 109 301 155 302 197 304 239 301 111 302 157 304 200 306 244 302 113 304 160 305 204 307 249 61 MBH SHC 209 196 221 221 240 240 259 259 214 208 229 229 249 249 268 268 216 214 233 233 253 253 273 273 217 217 237 237 257 257 276 276 67 MBH SHC 244 163 244 190 246 233 259 259 249 156 249 201 253 248 268 268 251 178 251 206 256 255 272 272 253 184 253 212 257 257 276 276 73 MBH SHC 280 99.9 280 142 281 183 282 224 284 102 284 147 285 192 286 235 285 103 286 150 286 196 288 241 286 104 287 153 288 200 289 246 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity 4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%. *Indicates both downflow and horizontal units. RT-PRC002-EN 19 Performance Data (12½ Ton) High Efficiency Table PD-6 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*151C3, C4, CW— Standard Refrigeration System 85 CFM Airflow 4500 5000 5500 6000 95 AmbientTemperature 105 115 Enter Dry Entering Wet Bulb Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8 80 140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6 85 149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0 90 158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0 75 141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7 80 145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5 85 155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0 90 162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0 75 145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6 80 150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1 85 158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0 90 165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0 75 148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6 80 154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2 85 161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0 90 167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 20 RT-PRC002-EN Performance Data (12½ Ton) High Efficiency Table PD-7 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase T*D151C3, C4, CW — Dehumidification (Hot Gas Reheat) or TXV Option 85 CFM Airflow 2500* 3250* 4000* 4500 5000 5500 6000 95 AmbientTemperature 105 115 Enter Dry Entering Wet Bulb Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 123.8 88.0 138.9 73.4 155.2 55.8 118.2 84.4 132.8 70.1 148.6 52.6 112.1 80.7 126.2 66.6 141.5 49.2 105.6 76.8 119.1 62.8 133.8 45.6 80 123.9 100.8 139.0 85.5 155.2 69.8 118.3 97.3 132.9 82.0 148.7 66.4 112.1 93.3 126.3 78.3 141.5 62.8 105.7 89.6 119.2 74.4 133.9 59.0 85 124.0 113.6 139.1 98.3 155.3 82.5 118.5 110.1 133.0 94.7 148.8 79.1 112.5 106.3 126.4 91.0 141.6 75.4 104.3 104.3 119.3 87.1 134.0 71.6 90 126.0 124.6 139.0 110.8 155.4 95.2 120.6 120.6 133.0 107.2 148.8 91.7 115.5 115.5 126.4 103.5 141.7 88.0 110.3 110.3 119.4 99.5 134.1 84.2 75 133.0 99.5 148.7 80.0 165.5 59.1 126.7 95.9 141.9 76.4 158.2 55.7 120.0 91.9 134.7 72.5 150.4 52.2 112.8 87.8 126.9 68.5 142.0 48.5 80 133.1 115.7 148.8 96.0 165.6 76.1 126.9 112.0 142.1 92.4 158.3 72.5 120.2 108.1 134.8 88.6 150.5 68.8 113.2 104.1 127.0 84.5 142.1 64.9 85 132.7 132.7 148.8 111.9 165.7 92.0 128.6 126.0 142.1 108.2 158.4 88.4 122.5 121.6 134.8 104.3 150.6 84.7 116.2 116.2 127.1 100.4 142.3 80.7 90 139.8 139.8 148.9 127.6 165.7 107.7 134.5 134.5 142.2 124.0 158.4 104.1 128.9 128.9 135.0 120.1 150.7 100.5 122.8 122.8 127.5 116.3 142.4 96.5 75 139.3 109.8 155.4 86.2 172.5 61.7 132.6 106.1 148.2 82.5 164.7 58.3 125.4 102.0 140.4 78.6 156.4 54.7 117.8 97.8 132.2 74.5 147.6 50.9 80 139.6 128.9 155.5 105.4 172.6 81.5 133.1 125.4 148.3 101.7 164.8 77.8 126.2 121.5 140.6 97.7 156.5 74.0 119.0 115.2 132.3 93.6 147.7 70.1 85 143.2 143.2 155.5 124.1 172.8 100.5 137.6 137.6 148.3 120.4 165.0 96.8 131.5 131.5 140.7 116.6 156.7 93.0 125.0 125.0 132.4 112.5 147.8 89.0 90 151.0 151.0 156.1 143.3 172.8 119.2 145.3 145.3 149.0 139.6 165.0 115.6 139.0 139.0 141.6 136.1 156.7 111.7 132.4 132.4 134.0 129.4 147.9 107.6 75 142.5 116.0 158.8 90.2 176.0 63.3 135.6 112.2 151.3 86.4 168.0 59.8 128.2 108.3 143.3 82.4 159.5 56.2 120.4 104.1 134.9 78.2 150.4 52.4 80 143.3 137.5 158.8 111.1 176.2 84.8 135.1 135.1 151.4 107.3 168.1 81.1 130.0 127.1 143.5 103.5 159.6 77.3 122.7 122.1 135.0 99.3 150.5 73.3 85 149.0 149.0 159.0 131.9 176.3 105.6 143.1 143.1 151.6 128.2 168.2 101.9 136.7 136.7 143.6 124.2 159.8 98.2 129.9 129.9 135.2 120.1 150.7 94.2 90 157.2 157.2 160.1 153.3 176.4 126.4 151.1 151.1 151.1 151.1 168.3 122.6 144.6 144.6 145.9 142.5 159.7 118.6 137.6 137.6 138.2 137.5 150.8 114.8 75 145.1 121.9 161.6 93.7 179.0 64.7 138.1 118.3 154.0 89.9 170.8 61.2 130.5 114.2 145.8 85.9 162.0 57.3 122.6 110.1 137.1 81.7 152.7 53.3 80 145.6 145.6 161.6 116.5 179.2 87.9 140.4 138.6 154.0 112.8 170.9 84.2 133.1 133.1 145.8 108.8 162.1 80.3 126.2 126.2 137.1 104.5 152.9 76.3 85 154.1 154.1 162.0 139.4 179.3 110.7 147.9 147.9 154.4 135.7 171.0 106.9 141.3 141.3 146.3 131.7 162.2 103.0 134.2 134.2 137.7 127.6 153.1 99.2 90 162.6 162.6 162.5 162.5 179.5 133.2 156.3 156.3 157.1 154.9 171.2 129.5 149.5 149.5 149.4 149.4 162.4 125.5 142.2 142.2 142.2 142.2 153.1 121.5 75 147.5 127.8 164.0 97.2 181.5 66.0 140.3 124.0 156.2 93.3 173.1 62.2 132.6 119.9 147.8 89.3 164.1 58.4 124.6 116.0 138.9 85.1 154.7 54.3 80 150.2 149.4 164.1 121.8 181.7 90.9 143.5 143.5 156.2 117.9 173.2 87.1 136.8 136.8 147.9 114.0 164.3 83.2 129.7 129.7 139.0 109.8 154.8 79.2 85 158.5 158.5 164.6 146.7 181.8 115.5 152.1 152.1 156.8 142.9 173.4 111.8 145.3 145.3 148.6 139.0 164.4 107.8 138.0 138.0 140.0 134.9 154.9 103.7 90 167.4 167.4 167.9 167.1 182.1 139.9 160.8 160.8 160.7 160.7 173.6 136.1 153.8 153.8 153.7 153.7 164.6 132.2 146.3 146.3 146.2 146.2 155.1 128.2 75 149.6 133.5 165.9 100.3 183.7 67.0 142.2 129.6 158.0 96.4 175.1 63.2 134.4 125.6 149.5 92.5 166.0 59.4 126.4 121.7 140.5 88.3 156.4 55.3 80 153.4 153.4 166.1 126.9 183.8 93.6 147.0 147.0 158.1 123.0 175.2 90.0 140.2 140.2 149.6 118.9 166.1 86.1 132.8 132.8 140.6 115.0 156.5 82.0 85 162.5 162.5 166.9 153.7 183.9 120.1 155.9 155.9 159.1 150.0 175.3 116.3 148.8 148.8 148.7 148.7 166.2 112.5 141.3 141.3 142.4 138.6 156.6 108.4 90 171.6 171.6 171.6 171.6 184.3 146.4 164.8 164.8 164.7 164.7 175.7 142.6 157.6 157.6 157.5 157.5 166.5 138.7 149.9 149.9 149.9 149.9 157.0 134.7 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Unit applications below 4000 CFM • Electric heaters restricted on applications below 4000 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4000 CFM. *Indicates both downflow and horizontal units. RT-PRC002-EN 21 Performance Data (15 Ton) High Efficiency Table PD-8 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*181C3, C4, CW— Standard Refrigeration System AmbientTemperature 85 CFM Airflow 5400 6000 6600 7200 Enter. Dry Bulb 61 (F) MBH SHC 75 172 144 80 175 169 85 185 185 90 195 195 75 177 153 80 181 180 85 192 192 90 201 201 75 181 162 80 186 186 85 197 197 90 204 204 75 184 170 80 191 191 85 200 200 90 207 207 67 MBH SHC 194 112 195 138 196 164 195 195 197 116 198 144 199 172 200 200 198 123 200 151 202 179 205 202 200 127 202 153 204 185 208 207 95 73 MBH SHC 205 75.2 207 103 209 126 211 149 207 76 209 105 211 129 214 153 208 76.6 210 107 213 131 215 157 209 79.1 211 108 214 134 217 160 61 MBH SHC 159 138 164 162 176 176 188 188 164 147 170 170 183 183 194 194 168 155 177 177 189 189 199 199 168 168 182 182 194 194 203 203 67 MBH SHC 185 107 186 134 186 161 190 184 189 112 189 142 190 171 195 194 191 117 192 148 194 180 199 199 193 121 194 154 194 194 203 203 105 Entering Wet Bulb 73 61 MBH SHC MBH SHC 200 71.9 147 131 202 99.7 153 153 203 124 165 165 204 148 178 178 202 73.2 151 140 204 103 159 159 206 129 173 173 208 155 185 185 204 74.4 152 152 206 105 166 166 208 132 179 179 209 159 191 191 206 76.4 156 156 207 107 171 171 209 136 185 185 211 163 195 195 67 MBH SHC 172 101 173 128 174 156 179 179 176 106 177 136 173 173 185 185 180 111 180 144 183 173 191 191 182 116 183 151 187 181 195 195 115 73 MBH SHC 193 68 194 95.4 195 122 196 147 195 69.3 196 99.4 197 127 199 154 197 70.6 198 102 199 132 201 160 198 71.9 199 105 201 135 203 166 61 MBH SHC 130 130 142 142 155 155 168 168 138 131 148 148 162 162 175 175 142 139 154 154 168 168 181 181 145 145 159 159 174 174 186 186 67 MBH SHC 158 97 158 122 155 155 167 167 162 99.8 162 130 162 162 175 175 165 105 166 137 170 166 181 181 168 110 169 145 174 174 186 186 73 MBH SHC 183 63.4 183 90.5 184 117 184 144 185 64.8 186 94.6 186 124 187 152 187 66.2 188 98.6 189 129 190 160 189 67.4 190 102 191 134 192 167 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 22 RT-PRC002-EN Performance Data (15 Ton) High Efficiency Table PD-9 — Gross Cooling Capacities (MBH) 15 Ton Three Phase T*D181C3, C4, CW— Dehumidification (Hot Gas Reheat) or TXV Option AmbientTemperature 85 CFM Airflow 3000* 3900* 4800* 5400 6000 6600 7200 95 105 115 Enter. Dry Entering Wet Bulb Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 150.0 106.0 168.0 88.9 187.7 68.3 144.0 102.3 161.4 85.3 180.6 64.8 137.5 98.4 154.4 81.6 173.0 61.2 130.8 94.4 147.1 77.8 165.0 57.5 80 150.2 121.0 168.1 103.0 187.8 84.7 144.1 117.3 161.5 99.3 180.7 81.1 137.7 113.4 154.6 95.4 173.1 77.2 131.0 109.3 147.3 91.5 165.1 73.3 85 150.2 135.8 168.2 117.9 187.9 99.5 144.2 132.1 161.7 114.1 180.8 95.8 137.9 128.1 154.8 110.3 173.2 92.0 130.7 122.5 147.5 106.2 165.2 88.0 90 151.8 148.3 168.4 132.7 188.0 114.2 146.3 144.5 161.9 128.9 180.9 110.5 140.5 140.5 155.0 125.0 173.3 106.7 134.9 134.9 147.7 120.9 165.4 102.7 75 161.5 119.8 180.4 96.8 201.0 72.4 154.8 115.8 173.1 93.0 193.0 68.7 147.7 111.8 165.4 89.0 184.6 64.9 140.2 107.5 157.2 84.8 175.7 61.0 80 161.7 138.5 180.6 115.6 201.1 92.3 154.9 134.5 173.3 111.7 193.1 88.5 147.8 130.4 165.6 107.6 184.7 84.5 140.4 126.1 157.4 103.5 175.8 80.4 85 162.6 155.0 180.8 134.3 201.3 110.9 156.3 150.7 173.5 130.3 193.3 107.0 149.8 146.3 165.8 126.3 184.9 103.0 142.9 141.9 157.7 122.0 176.0 98.9 90 168.5 168.5 180.9 152.7 201.5 129.4 162.8 162.8 173.6 148.8 193.5 125.5 156.8 156.8 165.9 144.6 185.1 121.5 150.5 150.5 157.9 140.4 176.2 117.3 75 169.6 132.0 189.0 104.3 210.2 75.6 162.4 127.9 181.2 100.4 201.5 71.8 154.7 123.7 172.8 96.2 192.4 67.9 146.6 119.2 164.1 91.9 182.8 63.9 80 170.0 154.3 189.3 126.8 210.4 98.8 162.9 150.3 181.4 122.7 201.7 94.8 155.4 146.0 173.1 118.6 192.6 90.7 147.5 139.4 164.4 114.3 183.0 86.5 85 173.4 173.4 189.5 149.0 210.6 121.0 166.9 166.9 181.7 145.0 201.9 117.0 160.5 160.5 173.3 140.7 192.8 112.9 153.7 153.7 164.6 136.3 183.3 108.6 90 182.3 182.3 189.9 171.1 210.8 143.1 176.1 176.1 182.2 167.0 202.2 139.1 169.5 169.5 169.3 169.3 193.1 134.9 162.5 162.5 165.7 155.6 183.6 130.6 75 173.7 139.5 193.4 108.9 214.8 77.5 166.2 135.3 185.2 104.9 205.8 73.7 158.3 130.9 176.6 100.7 196.3 69.7 150.0 126.5 167.6 96.4 186.4 65.6 80 174.6 164.4 193.7 133.7 215.0 102.8 164.2 164.2 185.5 129.6 206.0 98.7 159.8 153.0 176.9 125.4 196.5 94.5 152.1 148.0 167.9 121.0 186.6 90.3 85 180.1 180.1 193.9 158.1 215.3 127.3 173.8 173.8 185.8 154.0 206.3 123.2 167.0 167.0 177.2 149.7 196.8 119.0 159.9 159.9 168.2 145.3 186.9 114.7 90 189.8 189.8 189.8 189.8 215.5 151.6 183.3 183.3 183.3 183.3 206.6 147.6 176.4 176.4 179.1 170.7 197.1 143.4 169.1 169.1 170.7 165.6 187.2 139.0 75 177.2 146.6 197.0 113.2 218.7 79.2 169.4 142.4 188.6 109.1 209.4 75.4 161.3 138.0 179.8 104.9 199.6 71.3 152.8 133.5 170.5 100.5 189.4 67.0 80 178.8 171.0 197.4 140.3 218.9 106.5 169.8 169.8 189.0 136.2 209.6 102.4 164.0 161.4 180.1 131.9 199.8 98.2 155.8 155.8 170.9 127.5 189.6 93.9 85 186.4 186.4 197.6 166.9 219.2 133.3 179.8 179.8 189.3 162.7 209.9 129.2 172.8 172.8 180.6 158.4 200.2 125.0 165.3 165.3 171.5 153.9 190.0 120.6 90 196.7 196.7 196.5 196.5 219.4 159.9 189.8 189.8 189.7 189.7 210.2 155.8 182.6 182.6 183.8 180.6 200.5 151.6 174.9 174.9 174.8 174.8 190.2 146.9 75 180.2 153.4 200.2 117.4 221.9 80.8 172.3 149.2 191.5 113.2 212.4 76.8 164.0 144.8 182.5 108.9 202.4 72.6 155.4 140.2 172.9 104.5 191.9 68.2 80 182.9 179.1 200.5 146.6 222.1 110.1 175.6 174.4 191.9 142.5 212.6 105.9 167.6 167.6 182.7 138.0 202.6 101.7 160.2 160.2 173.2 133.4 192.1 97.3 85 192.0 192.0 201.0 175.4 222.5 139.1 185.1 185.1 192.5 171.2 213.0 134.9 177.8 177.8 183.6 166.9 203.0 130.7 170.1 170.1 169.9 169.9 192.5 126.2 90 202.7 202.7 204.3 199.9 222.7 167.8 195.5 195.5 196.3 195.1 213.2 163.5 188.0 188.0 187.9 187.9 203.2 159.2 180.0 180.0 179.9 179.9 192.8 154.7 75 182.8 160.1 202.8 121.3 224.7 82.1 174.8 155.8 194.0 117.1 214.9 78.0 166.4 151.4 184.7 112.8 204.7 73.7 157.7 146.8 175.0 108.4 193.9 69.4 80 186.0 186.0 203.2 152.8 224.9 113.4 179.1 179.1 194.2 148.3 215.2 109.3 171.8 171.8 185.0 143.9 205.0 105.0 164.1 164.1 175.4 139.3 194.3 100.6 85 196.9 196.9 204.0 183.7 225.2 144.5 189.8 189.8 195.4 179.5 215.6 140.5 182.3 182.3 182.1 182.1 205.4 136.2 174.3 174.3 177.1 167.2 194.7 131.7 90 207.9 207.9 207.8 207.8 225.4 175.3 200.6 200.6 200.5 200.5 215.8 171.1 192.8 192.8 192.6 192.6 205.7 166.7 184.5 184.5 184.4 184.4 195.1 162.2 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Unit applications below 4800 CFM • Electric heaters restricted on applications below 4800 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4800 CFM. *Indicates both downflow and horizontal units. RT-PRC002-EN 23 Performance Data (17½ Ton) High Efficiency Table PD-10 — Gross Cooling Capacities (MBH)17½ Ton Three Phase TC*211C3, C4, CW — Standard Refrigeration Option AmbientTemperature 85 CFM Airflow 6300 7000 7700 8400 95 105 115 Enter Dry Entering Wet Bulb Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2 80 202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0 85 216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0 90 227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0 75 205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0 80 210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0 85 223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0 90 232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0 75 210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7 80 217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0 85 228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0 90 235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0 75 214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2 80 222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0 85 231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0 90 238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 24 RT-PRC002-EN Performance Data (17½ Ton) High Efficiency Table PD-11 — Gross Cooling Capacities (MBH)17½ Ton Three Phase T*D211C3, C4, CW— TXV Option AmbientTemperature 85 CFM Airflow 3500* 4550* 5600 6300 7000 7700 8400 95 105 115 Enter Dry Entering Wet Bulb Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 178.1 125.2 199.2 102.8 222.1 78.3 170.4 120.6 190.9 98.4 213.1 74.0 162.3 115.7 182.1 93.7 203.6 69.5 153.6 110.7 172.8 88.9 193.6 64.9 80 178.3 143.9 199.4 121.1 222.2 97.7 170.6 139.3 191.1 116.5 213.3 93.4 162.4 134.5 182.3 111.8 203.8 88.8 153.8 129.5 173.1 106.8 193.7 84.0 85 178.6 163.0 199.6 139.7 222.4 116.2 171.0 158.4 191.3 135.0 213.5 111.9 163.0 153.7 182.5 130.2 204.0 107.2 151.7 151.7 173.3 125.2 194.0 102.4 90 181.8 177.2 199.8 158.2 222.6 134.6 175.2 171.7 191.5 153.5 213.7 130.2 168.1 165.8 182.7 148.7 204.2 125.5 160.6 160.1 173.5 143.8 194.2 120.6 75 190.8 142.2 212.7 113.0 236.1 82.3 182.3 137.4 203.5 108.3 226.2 78.0 173.3 132.4 193.9 103.4 215.8 73.4 163.8 127.2 183.7 98.3 204.8 68.6 80 191.2 166.4 213.0 136.6 236.3 106.8 182.8 161.6 203.8 131.8 226.5 102.3 173.9 156.6 194.1 126.9 216.0 97.5 164.7 151.5 184.0 121.8 205.1 92.6 85 193.7 186.8 213.2 160.2 236.6 130.2 186.2 180.5 204.1 155.4 226.8 125.6 178.3 173.9 194.4 150.4 216.3 120.8 169.9 167.2 184.3 145.3 205.3 115.8 90 201.2 201.2 213.6 183.9 236.9 153.5 194.2 194.2 204.7 179.3 227.0 148.9 186.6 186.6 195.2 174.4 216.6 144.0 178.5 178.5 185.2 169.3 205.6 139.0 75 199.5 157.9 221.6 122.1 245.5 85.7 190.5 153.0 212.0 117.4 234.9 81.2 180.9 147.9 201.7 112.4 223.8 76.5 171.0 142.6 190.9 107.3 212.2 71.6 80 200.9 187.5 221.9 150.5 245.8 114.8 192.2 182.6 212.3 145.8 235.3 110.1 179.9 179.9 202.0 140.8 224.1 105.2 173.8 166.9 191.2 135.6 212.5 100.2 85 207.3 204.9 222.5 179.2 246.2 142.9 199.3 198.8 213.0 174.6 235.4 138.1 190.6 190.6 202.7 169.6 224.4 133.3 182.0 182.0 192.0 164.4 212.8 128.2 90 217.4 217.4 224.2 208.4 246.5 171.0 209.5 209.5 214.9 203.9 235.8 166.2 201.4 201.4 201.3 201.3 224.8 161.4 192.6 192.6 195.4 187.3 213.2 156.4 75 203.9 167.7 226.2 127.9 250.3 87.7 194.8 162.9 216.2 123.2 239.2 83.0 185.0 157.7 205.6 118.1 227.8 78.4 174.8 152.4 194.5 112.9 215.8 73. 80 202.9 202.9 226.5 159.5 250.5 119.7 195.2 195.2 216.6 154.8 239.4 114.8 188.9 182.8 206.0 149.7 228.1 110.1 179.6 175.4 194.9 144.5 216.1 105.0 85 214.6 214.6 227.5 191.5 250.9 150.9 206.7 206.7 217.4 186.6 239.8 146.1 198.1 198.1 207.2 181.8 228.5 141.3 189.1 189.1 196.3 176.6 216.5 136.2 90 226.3 226.3 226.2 226.2 251.4 182.3 218.0 218.0 221.1 212.1 240.4 177.4 209.4 209.4 211.9 204.9 228.9 172.4 200.2 200.2 202.0 197.2 217.2 167.6 75 207.8 177.3 229.9 133.4 254.2 89.6 198.5 172.5 219.7 128.6 242.8 84.9 188.5 167.4 208.8 123.5 231.1 80.1 178.2 162.0 197.4 118.3 218.8 75.1 80 212.0 205.1 230.4 168.2 254.5 124.4 203.5 198.3 220.0 163.5 243.1 119.6 194.3 190.9 209.4 158.4 231.4 114.7 184.7 183.5 198.1 153.1 219.2 109.6 85 221.9 221.9 231.8 203.6 254.9 158.8 213.4 213.4 221.6 198.6 243.5 153.8 204.7 204.7 211.2 193.7 231.8 149.0 195.4 195.4 200.2 188.5 219.6 143.9 90 234.1 234.1 236.8 229.0 255.6 193.4 225.4 225.4 227.5 221.6 244.3 188.5 216.5 216.5 217.7 214.0 232.5 183.4 206.9 206.9 207.6 206.7 220.6 178.6 75 211.3 186.8 233.0 138.7 257.4 91.4 201.8 181.9 222.6 133.9 245.7 86.5 191.8 176.7 211.5 128.8 233.8 81.7 181.3 171.3 199.9 123.5 221.3 76.7 80 217.2 212.9 233.7 176.7 257.8 129.0 208.4 206.0 223.3 171.9 246.1 124.1 199.0 198.7 212.3 166.8 234.2 119.3 189.0 189.0 200.8 161.5 221.7 114.1 85 228.2 228.2 235.8 215.3 258.2 166.4 219.5 219.5 225.5 210.3 246.5 161.4 210.4 210.4 210.3 210.3 234.6 156.6 200.8 200.8 200.7 200.7 222.2 151.5 90 241.0 241.0 242.8 238.1 259.2 204.2 231.9 231.9 233.1 230.7 247.7 199.3 222.4 222.4 222.3 222.3 235.7 194.2 212.6 212.6 212.6 212.6 223.5 189.2 75 214.5 195.9 235.7 143.9 260.2 92.9 204.9 191.1 225.0 139.0 248.3 88.0 190.7 190.7 213.7 133.9 236.1 83.2 181.3 181.3 201.9 128.6 223.4 78.2 80 221.9 220.3 236.6 185.0 260.5 133.5 212.1 212.1 225.8 180.0 248.6 128.5 203.1 203.1 214.8 175.0 236.5 123.7 193.4 193.4 203.2 169.7 223.8 118.5 85 233.9 233.9 239.5 226.8 261.0 173.9 224.8 224.8 224.7 224.7 249.2 168.9 215.5 215.5 215.4 215.4 236.9 163.8 205.5 205.5 207.7 200.6 224.4 158.9 90 247.0 247.0 248.0 246.9 262.4 214.8 237.7 237.7 237.6 237.6 250.7 209.8 227.8 227.8 227.8 227.8 238.6 204.7 217.8 217.8 217.7 217.7 226.3 199.7 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Cooling Capacity 3. SHC = Sensible Heat Capacity *Unit applications below 5600 CFM • Electric heaters restricted on applications below 5600 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 5600 CFM. RT-PRC002-EN 25 Performance Data (20 Ton) High Efficiency Table PD-12 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*241C3, C4, CW — Standard Refrigeration Option AmbientTemperature (F) 85 CFM Airflow 7200 8000 8800 9600 Enter. Dry Bulb 61 (F) MBH SHC 75 246 205 80 250 245 85 263 263 90 274 274 75 253 218 80 257 257 85 270 270 90 280 280 75 258 230 80 264 264 85 276 276 90 285 285 75 262 240 80 270 270 85 280 280 90 288 288 67 MBH SHC 273 158 274 192 275 227 278 262 275 163 277 199 279 236 282 273 278 167 280 204 282 244 286 281 280 169 282 209 284 250 288 288 95 73 MBH SHC 284 105 287 142 290 171 293 201 285 107 289 144 292 174 295 205 287 109 290 155 293 177 297 209 288 110 291 161 295 179 298 212 61 MBH SHC 228 196 232 232 251 251 266 266 234 209 243 243 261 261 274 274 240 221 252 252 268 268 280 280 246 233 260 260 274 274 284 284 67 MBH SHC 263 152 264 190 265 228 268 265 267 159 268 199 270 240 274 274 270 164 271 208 274 250 280 280 273 169 274 215 277 260 284 284 105 Entering Wet Bulb (F) 73 61 67 MBH SHC MBH SHC MBH SHC 280 101 208 186 246 145 283 141 216 216 246 183 285 173 236 236 248 221 288 206 254 254 254 254 282 103 214 199 252 152 285 143 227 227 252 194 288 177 247 247 255 237 291 212 264 264 264 264 284 105 219 211 256 159 287 145 236 236 257 205 290 181 256 256 260 251 293 217 271 271 271 271 285 106 225 223 260 166 288 147 245 245 261 215 291 184 263 263 265 263 294 222 276 276 276 276 115 73 MBH SHC 273 96.5 274 135 275 170 277 205 275 98.3 277 140 278 177 280 214 277 100 279 144 281 182 283 221 278 102 281 147 282 186 285 228 61 MBH SHC 191 176 201 201 219 219 239 239 194 189 210 210 230 230 250 250 199 199 218 218 240 240 258 258 205 205 226 226 248 248 264 264 67 MBH SHC 222 136 223 172 225 211 237 237 228 142 228 184 232 226 248 248 232 149 233 195 238 238 258 258 236 156 237 205 246 246 265 265 73 MBH SHC 261 91.5 261 130 262 168 262 205 266 93.6 266 136 266 177 267 218 269 95.5 269 141 269 185 271 229 271 97.1 271 146 272 193 275 240 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. 26 RT-PRC002-EN Performance Data (20 Ton) High Efficiency Table PD-13 — Gross Cooling Capacities (MBH) 20 Ton Three Phase T*D241C3, C4, CW— TXV Option AmbientTemperature (F) 85 CFM Airflow 4000* 5200* 6400 7200 8000 8800 9600 95 105 115 Enter. Dry Entering Wet Bulb (F) Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 208.5 149.1 233.3 122.6 260.1 94.5 199.6 143.8 223.6 117.3 249.8 89.3 190.1 138.1 213.4 111.9 238.6 84.0 180.0 132.3 202.5 105.8 226.9 78.5 80 208.7 171.1 233.4 144.4 260.2 117.1 199.9 165.6 223.8 139.1 249.8 111.8 190.4 159.9 213.6 133.4 238.7 106.3 180.4 153.9 202.7 127.6 226.9 100.7 85 209.5 193.0 233.6 166.3 260.3 138.9 200.8 187.5 224.0 160.9 249.9 133.7 191.4 181.7 213.8 155.2 238.9 128.1 181.6 175.7 203.0 149.3 227.1 122.4 90 212.7 212.7 233.9 188.1 260.5 160.6 205.2 205.2 224.3 182.6 250.1 155.2 197.4 197.4 214.1 176.8 239.1 149.7 189.0 189.0 203.4 170.8 227.3 143.9 75 223.8 169.6 249.5 135.2 277.5 99.6 213.8 163.8 238.8 129.6 265.8 94.2 203.4 157.8 227.5 123.9 253.4 88.6 192.4 151.6 215.6 117.8 240.4 82.9 80 224.5 197.4 249.7 163.1 277.6 128.2 214.8 191.6 239.1 157.5 265.9 122.7 204.4 185.6 227.8 151.6 253.6 117.0 193.5 179.4 215.9 145.6 240.6 111.1 85 226.7 222.0 249.9 190.8 277.9 155.9 217.9 215.9 239.4 185.1 266.2 150.3 208.8 208.8 228.2 179.2 253.8 144.5 199.6 199.6 216.3 173.0 240.8 138.6 90 237.7 237.7 250.8 218.3 278.1 183.4 229.4 229.4 240.3 212.6 266.5 177.8 220.4 220.4 229.2 206.6 254.1 172.0 211.0 211.0 217.5 200.4 241.1 165.9 75 234.3 187.9 260.5 146.4 289.2 103.7 223.9 182.1 249.1 140.7 276.7 98.2 212.8 175.9 237.1 134.8 263.3 92.5 201.1 169.5 224.3 128.7 249.4 86.5 80 235.9 221.8 260.8 180.1 289.4 138.0 225.7 215.9 249.4 174.3 276.9 132.3 214.9 209.8 237.3 168.2 263.6 126.5 202.8 202.8 224.6 161.9 249.6 120.4 85 243.8 243.8 261.4 213.2 289.7 171.3 234.9 234.9 250.1 207.4 277.2 165.6 225.3 225.3 238.2 201.3 264.0 159.7 215.3 215.3 225.7 195.0 250.0 153.6 90 257.1 257.1 263.2 246.7 290.1 204.5 247.9 247.9 252.1 240.8 277.5 198.6 238.1 238.1 240.6 234.8 264.3 192.6 227.7 227.7 228.5 224.2 250.4 186.3 75 239.8 199.6 266.0 153.5 295.0 106.1 229.0 193.6 254.2 147.8 282.1 100.6 217.6 187.4 241.8 141.7 268.2 94.7 205.6 180.9 228.6 138.4 253.8 88.7 80 242.3 237.5 266.3 190.6 295.3 144.0 230.8 230.8 254.6 184.7 282.3 138.3 221.3 221.1 242.2 178.6 268.6 132.4 210.7 210.7 229.2 172.3 254.2 126.2 85 253.7 253.7 267.4 227.6 295.7 181.1 244.3 244.3 255.7 221.6 282.7 175.3 234.3 234.3 243.5 215.5 269.1 169.3 223.6 223.6 230.6 209.1 254.6 163.1 90 267.6 267.6 270.3 265.1 296.0 217.7 257.9 257.9 257.8 257.8 283.2 211.9 247.5 247.5 247.5 247.5 269.6 205.7 236.6 236.6 236.6 236.6 255.3 199.4 75 244.5 210.8 270.7 160.1 299.8 108.3 233.4 204.7 258.5 154.3 286.5 102.8 221.8 198.5 245.8 148.2 272.4 96.9 209.5 191.9 232.3 141.9 257.5 90.8 80 248.1 248.1 271.1 200.8 300.1 149.8 238.5 238.5 259.0 194.8 286.8 144.0 228.4 228.4 246.3 188.7 272.8 138.1 217.6 217.6 232.9 182.3 258.0 131.8 85 262.5 262.5 272.6 241.6 300.5 190.5 252.6 252.6 260.7 235.6 287.3 184.7 242.1 242.1 248.1 229.3 273.3 178.7 231.0 231.0 235.0 222.9 258.3 172.1 90 277.2 277.2 277.0 277.0 301.0 230.6 266.9 266.9 266.8 266.8 288.0 224.7 256.0 256.0 256.0 256.0 274.1 218.5 244.6 244.6 244.5 244.5 259.4 212.1 75 248.5 221.7 274.6 166.6 303.7 110.4 237.3 215.6 262.1 160.6 290.2 104.8 225.4 209.3 249.0 154.6 275.8 98.9 213.0 202.7 235.3 148.3 260.6 92.7 80 255.2 255.2 275.2 210.8 304.0 155.3 245.3 245.3 262.8 204.7 290.6 149.6 234.7 234.7 249.8 198.5 276.2 143.5 223.6 223.6 236.2 192.0 261.1 137.3 85 270.2 270.2 277.2 255.2 304.3 199.4 259.9 259.9 265.1 249.2 291.0 193.6 249.0 249.0 252.3 242.9 276.7 187.4 237.5 237.5 239.1 236.5 261.6 180.9 90 285.5 285.5 285.4 285.4 305.2 243.0 274.8 274.8 274.8 274.8 292.1 237.2 263.5 263.5 263.5 263.5 277.9 231.0 251.5 251.5 251.5 251.5 263.0 224.5 75 252.1 232.3 277.9 172.8 306.9 112.3 240.7 226.2 265.2 166.9 293.3 106.7 228.7 219.9 251.7 160.6 278.6 100.7 216.3 213.3 237.8 154.1 263.2 94.5 80 261.5 261.5 278.7 220.4 307.3 160.6 251.2 251.2 266.1 214.3 293.8 155.0 240.4 240.4 252.8 208.0 279.2 148.9 228.8 228.8 238.9 201.5 263.8 142.6 85 277.0 277.0 281.4 268.6 307.7 208.4 266.4 266.4 269.2 262.5 294.2 202.3 255.1 255.1 254.9 254.9 279.7 196.0 243.1 243.1 243.0 243.0 264.4 189.6 90 292.8 292.8 292.8 292.8 308.7 255.2 281.8 281.8 281.8 281.8 295.6 249.4 270.1 270.1 270.1 270.1 281.3 243.2 257.7 257.7 257.7 257.7 266.2 236.7 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Unit applications below 6400 CFM • Electric heaters restricted on applications below 6400 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM. *Indicates both downflow and horizontal units. RT-PRC002-EN 27 Performance Data (20 Ton) High Efficiency Table PD-14 — Gross Cooling Capacities (MBH) 20 Ton Three Phase T*D241C3, C4, CW— Dehumidification (Hot Gas Reheat) AmbientTemperature (F) 85 CFM Airflow 4000* 5200* 6400 7200 8000 8800 9600 95 105 115 Enter. Dry Entering Wet Bulb (F) Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 197.5 138.9 222.3 116.0 249.8 89.2 188.8 133.4 213.0 110.6 239.6 83.8 179.7 127.6 203.1 105.0 228.8 78.3 170.1 121.7 192.6 99.2 217.3 72.5 80 197.7 159.2 222.6 135.8 249.8 111.4 189.0 153.7 213.3 130.3 239.6 105.8 180.0 147.9 203.4 124.6 228.8 100.1 170.4 141.9 193.0 118.7 217.4 94.2 85 198.2 179.3 222.9 156.3 250.0 132.0 189.7 173.8 213.5 150.7 239.8 126.4 180.8 168.1 203.7 145.0 229.0 120.7 171.4 162.2 193.3 139.1 217.7 114.8 90 200.5 196.8 223.1 176.7 250.3 152.5 192.8 190.9 213.7 171.0 240.1 147.0 184.8 184.8 203.8 165.2 229.3 141.2 176.9 176.9 193.5 159.3 217.9 135.3 75 213.1 158.3 239.0 127.6 267.2 94.6 203.5 152.5 228.5 121.8 255.7 88.9 193.2 146.3 217.5 115.8 243.7 83.1 182.7 140.0 206.0 109.6 231.1 77.1 80 213.5 183.8 239.3 153.7 267.4 122.1 204.0 178.0 228.9 147.9 255.9 116.3 194.0 171.9 217.9 141.9 243.9 110.3 183.5 165.7 206.4 135.7 231.3 104.1 85 215.3 209.9 239.7 179.7 267.7 148.3 204.6 204.6 229.1 173.7 256.2 142.4 197.0 194.2 218.1 167.6 244.2 136.4 187.4 187.4 206.7 161.4 231.6 130.3 90 224.3 224.3 240.1 205.2 268.0 174.4 216.2 216.2 229.8 199.4 256.6 168.6 207.6 207.6 218.9 193.3 244.5 162.5 198.7 198.7 207.6 187.1 232.0 156.4 75 223.7 175.3 250.2 138.3 279.0 98.8 213.5 169.3 239.0 132.3 266.6 93.0 202.6 163.0 227.2 126.1 253.7 87.0 191.3 156.4 214.9 119.7 240.2 80.8 80 224.9 206.3 250.6 169.7 279.2 131.4 214.8 200.3 239.4 163.6 266.8 125.3 204.2 194.1 227.7 157.5 253.9 119.2 193.2 187.7 215.2 151.0 240.5 112.9 85 230.5 230.5 251.0 200.6 279.6 162.9 221.7 221.7 239.8 194.5 267.2 156.9 212.5 212.5 228.1 188.2 254.3 150.7 202.8 202.8 215.9 181.8 240.9 144.4 90 243.6 243.6 252.4 231.7 280.0 194.4 234.6 234.6 241.5 225.7 267.7 188.3 225.1 225.1 230.0 219.5 254.6 181.9 215.2 215.2 215.6 215.6 241.2 175.5 75 229.2 185.9 255.7 150.2 284.8 101.3 218.6 179.7 244.1 144.1 272.0 95.4 207.4 173.3 231.9 138.0 258.6 89.4 195.8 166.7 219.1 131.7 244.7 83.2 80 231.1 220.6 256.3 179.6 285.1 137.0 220.8 214.5 244.6 173.3 272.3 130.9 208.4 208.4 232.5 167.0 258.9 124.7 199.2 197.3 219.8 160.4 245.0 118.3 85 240.3 240.3 256.9 213.7 285.5 172.0 231.1 231.1 245.4 207.5 272.7 165.9 221.4 221.4 233.3 201.2 259.4 159.7 211.2 211.2 220.8 194.7 245.5 153.3 90 254.0 254.0 259.2 248.5 286.0 206.7 244.5 244.5 248.0 242.5 273.2 200.5 234.5 234.5 235.0 235.0 259.8 194.1 224.0 224.0 225.1 224.1 246.0 187.6 75 233.9 196.0 260.5 150.9 289.7 103.6 223.0 189.8 248.6 144.8 276.5 97.7 211.5 183.3 236.1 138.4 262.7 91.4 199.6 176.7 223.0 131.9 248.4 85.0 80 234.8 234.8 261.0 188.8 290.0 142.4 225.4 225.4 249.0 182.5 276.9 136.2 215.6 215.6 236.5 176.1 263.1 129.9 205.3 205.3 223.5 169.5 248.8 123.5 85 249.0 249.0 262.0 226.4 290.5 180.8 239.3 239.3 250.1 220.2 277.4 174.6 229.2 229.2 237.8 213.8 263.6 168.3 218.6 218.6 225.1 207.3 249.2 161.7 90 263.3 263.3 263.7 263.7 291.0 218.5 253.3 253.3 254.6 253.1 277.9 212.2 242.9 242.9 243.3 243.3 264.2 205.8 231.9 231.9 232.3 232.3 249.9 199.2 75 237.9 205.8 264.5 156.8 293.8 105.7 226.7 199.5 252.2 150.6 280.3 99.6 215.1 193.0 239.4 144.2 266.1 93.2 202.9 186.3 226.0 137.6 251.5 86.6 80 242.3 242.3 265.0 197.7 294.1 147.5 232.1 232.1 252.7 191.4 280.6 141.3 221.9 221.9 239.9 184.9 266.6 135.0 211.2 211.2 226.6 178.2 251.9 128.4 85 256.5 256.5 266.4 238.7 294.7 189.2 246.5 246.5 254.3 232.4 281.0 182.8 235.9 235.9 241.8 226.0 267.0 176.3 224.9 224.9 228.9 219.4 252.4 169.7 90 271.4 271.4 271.8 271.8 295.2 229.9 261.0 261.0 261.4 261.4 281.8 223.6 250.1 250.1 250.5 250.5 267.9 217.2 238.7 238.7 239.1 239.1 253.4 210.5 75 241.4 215.2 267.8 162.4 297.1 107.4 230.0 208.9 255.3 156.2 283.4 101.2 218.2 202.3 242.2 149.7 269.0 94.8 205.9 195.6 228.4 143.0 254.0 88.2 80 248.0 248.0 268.4 206.4 297.6 152.5 237.9 237.9 255.9 200.0 283.8 146.2 227.5 227.5 242.8 193.4 269.5 139.8 216.4 216.4 229.3 186.7 254.6 133.2 85 263.1 263.1 270.3 250.7 298.0 197.1 252.8 252.8 258.1 244.3 284.3 190.7 241.9 241.9 245.5 237.9 270.0 184.1 230.5 230.5 230.7 230.7 255.1 177.4 90 278.6 278.6 278.9 278.9 298.9 241.1 267.9 267.9 268.3 268.3 285.3 234.7 256.6 256.6 257.0 257.0 271.1 228.2 244.7 244.7 245.1 245.1 256.4 221.5 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Unit applications below 6400 CFM • Electric heaters restricted on applications below 6400 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM. 28 RT-PRC002-EN Performance Data (25 Ton) High Efficiency Table PD-15 — Gross Cooling Capacities (MBH)25 Ton Three Phase TC*301C3, C4, CW - Standard Refrigeration System 85 CFM Airflow 9000 10000 10500 11000 Enter. Dry Bulb 61 (F) MBH SHC 75 277 243 80 284 284 85 300 300 90 312 312 75 284 258 80 294 294 85 307 307 90 318 318 75 286 265 80 297 297 85 310 310 90 320 320 75 289 272 80 300 300 85 312 312 90 322 322 67 MBH SHC 306 187 307 225 309 269 313 312 310 188 310 233 313 280 318 318 311 190 312 237 315 285 320 320 312 192 313 240 316 289 321 321 95 73 MBH SHC 316 117 321 169 325 198 329 236 319 121 323 175 327 202 331 241 320 122 324 178 328 204 332 244 321 123 324 181 329 205 332 246 61 MBH SHC 258 234 269 269 289 289 305 305 264 249 280 280 298 298 312 312 267 256 285 285 302 302 314 314 270 264 289 289 305 305 317 317 67 MBH SHC 295 178 295 225 298 271 305 305 299 185 300 236 303 286 312 312 300 189 302 241 305 293 314 314 302 192 304 246 307 299 317 317 AmbientTemperature (F) 105 Entering Wet Bulb (F) 73 61 67 MBH SHC MBH SHC MBH SHC 314 115 238 224 276 169 317 161 252 252 277 217 320 202 273 273 280 266 321 240 293 293 293 293 316 117 244 239 282 178 319 170 263 263 283 230 322 207 284 284 287 284 324 248 301 301 301 301 316 118 247 246 284 182 320 174 267 267 285 237 323 210 289 289 289 289 325 251 305 305 305 305 317 119 249 249 286 186 321 177 272 272 287 243 324 212 293 293 293 293 326 255 308 308 308 308 115 73 MBH SHC 305 110 307 158 308 201 310 245 308 112 309 163 312 208 314 255 309 113 310 165 313 212 316 260 309 114 311 170 314 215 317 265 61 MBH SHC 218 214 235 235 256 256 277 277 224 224 245 245 267 267 287 287 228 228 249 249 272 272 292 292 231 231 253 253 276 276 295 295 67 MBH SHC 253 163 254 207 259 256 277 277 259 168 260 221 267 267 287 287 261 172 262 227 272 272 292 292 263 176 265 234 276 276 295 295 73 MBH SHC 292 104 293 151 293 198 295 244 295 106 296 158 297 208 299 257 296 107 298 162 299 213 301 264 297 108 299 165 300 217 303 270 Notes 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units. RT-PRC002-EN 29 Performance Data (25 Ton) High Efficiency Table PD-16 — Gross Cooling Capacities (MBH)25 Ton Three PhaseTC*301C3, C4, CW— TXV Option 85 CFM Airflow 5000* 6500* 8000 9000 10000 11000 12000 95 AmbientTemperature (F) 105 115 Enter. Dry Entering Wet Bulb (F) Bulb 61 67 73 61 67 73 61 67 73 61 67 73 (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 241.0 176.5 269.7 142.7 300.9 107.2 229.7 169.7 257.6 135.9 287.8 100.8 217.8 162.6 244.9 129.0 274.0 94.1 205.5 155.3 231.6 122.0 259.8 87.3 80 241.4 204.6 269.9 170.5 300.9 135.9 230.2 197.7 257.8 163.8 287.8 129.3 218.4 190.5 245.1 156.8 274.1 122.5 206.2 183.2 231.9 149.6 259.8 115.6 85 243.0 233.0 270.1 198.3 301.1 163.7 229.2 229.2 258.1 191.5 288.1 157.0 221.3 216.5 245.4 184.5 274.4 150.1 209.9 208.3 232.2 177.3 260.1 143.1 90 251.2 251.2 270.6 226.1 301.4 191.2 241.6 241.6 258.6 219.2 288.3 184.4 231.6 231.6 246.0 212.1 274.6 177.5 221.2 221.2 233.0 204.8 260.4 170.4 75 256.8 201.4 286.5 157.9 318.8 113.1 244.6 194.3 273.3 150.9 304.2 106.4 231.8 186.9 259.5 143.8 289.2 99.5 218.4 179.4 245.1 136.5 273.6 92.5 80 258.2 237.2 286.8 193.2 318.9 149.3 246.1 230.1 273.6 186.2 304.4 142.3 233.6 222.8 259.8 179.0 289.4 135.3 220.7 215.4 245.4 171.6 273.9 128.1 85 264.6 264.6 287.3 228.5 319.2 184.3 254.2 254.2 274.1 221.4 304.7 177.3 243.2 243.2 260.4 214.1 289.7 170.2 231.7 231.7 246.2 206.6 274.1 162.9 90 279.1 279.1 288.7 263.8 319.5 219.2 268.4 268.4 275.8 256.7 305.0 212.1 257.3 257.3 262.4 249.5 290.0 205.0 245.6 245.6 245.5 245.5 274.5 197.7 75 267.9 224.2 297.7 171.5 330.7 118.0 254.9 216.9 283.7 164.4 315.3 111.1 241.5 209.3 269.2 157.1 299.2 104.0 227.5 201.6 254.0 149.6 282.7 96.8 80 268.8 268.8 298.0 214.0 330.9 161.1 259.3 255.4 284.1 206.8 315.5 154.0 246.8 246.7 269.6 199.5 299.5 146.7 234.0 234.0 254.5 191.9 283.0 139.4 85 284.5 284.5 299.2 256.4 331.2 203.2 273.2 273.2 285.4 249.2 315.9 196.1 261.3 261.3 271.0 241.8 299.8 188.8 248.9 248.9 256.2 234.3 283.3 181.4 90 300.3 300.3 300.2 300.2 331.6 245.2 288.7 288.7 290.5 286.0 316.4 238.0 276.5 276.5 276.4 276.4 300.4 230.6 263.8 263.8 263.7 263.7 284.0 223.1 75 273.6 238.6 303.4 180.1 336.6 120.9 260.4 231.2 289.0 172.8 320.7 114.0 246.7 223.6 273.9 170.7 304.2 106.8 232.5 215.9 258.3 163.2 287.1 99.6 80 279.6 279.5 303.8 227.0 336.8 168.4 267.3 267.3 289.5 219.8 321.0 161.3 255.2 255.2 274.6 212.4 304.5 154.0 242.6 242.6 259.1 204.8 287.5 146.5 85 295.1 295.1 305.6 274.3 337.2 215.2 283.4 283.4 291.5 267.1 321.4 208.1 271.0 271.0 276.9 259.7 304.9 200.7 258.0 258.0 261.9 252.2 287.8 193.1 90 311.9 311.9 311.8 311.8 338.0 261.8 299.6 299.6 299.6 299.6 322.2 254.5 286.9 286.9 286.8 286.8 305.9 247.1 273.5 273.5 273.5 273.5 288.9 239.4 75 278.6 252.6 308.1 188.2 341.5 123.5 265.2 245.2 293.3 180.9 325.3 116.5 251.3 237.6 278.0 173.5 308.4 109.2 234.1 234.1 262.1 165.9 290.8 101.7 80 287.6 287.6 308.7 239.7 341.8 175.5 275.5 275.5 294.0 232.5 325.6 168.3 263.1 263.1 278.8 225.0 308.7 160.9 250.0 250.0 263.1 217.3 291.2 153.4 85 304.6 304.6 311.3 291.9 342.1 226.8 292.3 292.3 297.0 284.7 325.9 219.5 279.4 279.4 279.3 279.3 309.1 212.1 266.0 266.0 267.7 262.9 291.7 204.4 90 322.2 322.2 322.1 322.1 343.3 277.9 309.3 309.3 309.3 309.3 327.2 270.5 295.9 295.9 295.9 295.9 310.6 263.1 282.0 282.0 282.0 282.0 293.3 255.3 75 283.1 266.2 312.0 196.0 345.5 125.9 269.5 258.8 296.9 188.7 329.1 118.9 253.1 253.1 281.2 181.2 311.8 111.5 241.4 237.4 265.1 173.5 293.9 104.0 80 295.1 295.1 312.9 252.1 345.8 182.3 282.8 282.8 297.9 244.7 329.4 175.0 269.9 269.9 282.4 237.2 312.2 167.7 256.4 256.4 266.5 229.4 294.3 160.1 85 312.9 312.9 312.8 312.8 346.2 237.9 300.0 300.0 299.9 299.9 329.9 230.6 286.7 286.7 288.1 285.2 312.8 223.1 272.8 272.8 272.7 272.7 295.0 215.4 90 331.2 331.2 331.1 331.1 347.8 293.5 317.8 317.8 317.8 317.8 331.6 286.2 304.0 304.0 303.8 303.8 314.7 278.6 289.3 289.3 289.3 289.3 297.3 271.0 75 283.8 283.8 315.3 203.6 348.9 128.2 271.5 271.5 299.9 196.2 332.2 121.1 259.9 256.8 284.1 188.6 314.7 113.8 245.2 245.2 267.7 180.9 296.5 106.2 80 301.8 301.8 316.6 264.1 349.2 188.9 289.0 289.0 301.2 256.6 332.6 181.7 275.9 275.9 285.7 249.1 315.2 174.3 262.0 262.0 269.5 241.3 297.0 166.6 85 320.3 320.3 322.4 316.7 349.8 248.8 307.0 307.0 308.0 306.9 333.2 241.5 293.2 293.2 293.1 293.1 315.8 233.9 278.8 278.8 278.8 278.8 297.8 226.2 90 339.1 339.1 339.0 339.0 351.7 308.8 325.4 325.4 325.3 325.3 335.6 301.5 310.9 310.9 310.9 310.9 318.5 294.0 295.9 295.9 295.9 295.9 301.0 286.4 Notes 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Unit applications below 8000 CFM • Electric heaters restricted on applications below 8000 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 8000 CFM. 30 RT-PRC002-EN Performance Data (12½ Ton) Standard Efficiency Table PD-17 — Evaporator Fan Performance — 12½Ton — TC*150D .10 CFM 4000 4500 5000 5500 6000 RPM — — 547 595 643 .20 BHP — — 1.18 1.55 1.99 RPM — — 581 627 673 .30 BHP — — 1.30 1.68 2.12 RPM — 571 613 656 701 BHP — 1.10 1.42 1.81 2.26 External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field Supplied Low Static Drive 565 0.93 599 1.03 603 1.21 634 1.31 643 1.54 672 1.67 685 1.94 711 2.08 727 2.41 752 2.56 .80 RPM BHP .90 RPM BHP 1.00 RPM BHP 727 750 781 813 848 757 778 806 837 871 3 HP Standard Motor & Sheaves 632 665 700 737 777 1.15 1.43 1.78 2.21 2.71 663 694 727 763 801 1.27 1.56 1.91 2.34 2.85 695 723 755 788 825 1.38 1.69 2.05 2.47 2.99 1.48 1.82 2.19 2.62 3.13 1.59 1.94 2.34 2.77 3.27 Table PD-17 — Evaporator Fan Performance — 12½ Ton — TC*150D — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP 4000 4500 5000 5500 6000 3 HP Standard Motor & Sheaves 786 1.70 813 1.81 841 806 2.06 834 2.19 861 830 2.48 856 2.62 882 861 2.93 884 3.10 906 894 3.43 916 3.61 938 1.91 2.31 2.76 3.25 3.79 External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 867 886 907 930 959 1.90 RPM BHP 3 HP Standard Motor & High Static Drive Accessory 2.02 893 2.12 919 2.22 943 2.32 966 2.41 989 2.43 911 2.56 935 2.67 960 2.79 983 2.90 1005 2.89 931 3.02 955 3.16 977 3.30 1001 3.44 1022 3.41 953 3.56 976 3.70 999 3.86 1021 4.00 1043 3.97 980 4.15 1000 4.31 1019 4.46 1040 4.62 1061 5 HP Oversize Motor & Sheaves For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Notes: 1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary. 2. 5 HP Oversized Motor with Field Supplied Motor Sheave IVL40 Required. Field Supplied Belt may be necessary. 3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range. RT-PRC002-EN 1.80 RPM BHP 2.50 3.02 3.56 4.15 4.78 2.00 RPM BHP 1011 1028 1045 1064 1082 2.60 3.13 3.70 4.31 4.95 5 HP Oversize Motor & Field Supplied Drive Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. 31 Performance Data (15 Ton) Standard Efficiency Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B .10 CFM 4800 5400 6000 6600 7200 RPM — 585 643 701 760 .20 BHP RPM — 1.47 1.99 2.61 3.35 .30 BHP 563 618 673 729 786 1.17 1.60 2.12 2.76 3.52 RPM BHP External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Field Supplied Low Static Drive (1) 596 1.29 626 1.41 648 1.72 676 1.86 701 2.26 727 2.41 755 2.91 780 3.07 810 3.69 834 3.85 .80 RPM BHP .90 RPM BHP 1.00 RPM BHP 3 HP Standard Motor & Sheaves 656 703 752 804 856 1.52 1.99 2.56 3.23 4.02 (2) 685 1.63 714 1.76 742 729 2.12 756 2.25 782 777 2.71 801 2.85 825 827 3.39 849 3.56 871 878 4.20 899 4.38 919 5 HP Oversized Motor & Sheaves 1.90 2.38 2.99 3.72 4.56 768 807 848 892 939 2.04 2.52 3.13 3.88 4.74 794 832 871 914 959 2.18 2.68 3.27 4.03 4.91 Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B — Continued CFM 1.10 RPM BHP 4800 5400 6000 6600 7200 819 855 894 935 979 1.20 RPM BHP 1.30 RPM BHP 3 HP Standard Motor & Sheaves 2.30 844 2.43 871 2.84 878 3.00 901 3.43 916 3.61 938 4.18 956 4.34 977 5.08 999 5.25 1018 2.57 3.15 3.79 4.51 5.41 External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 898 923 959 997 1038 2.70 3.29 3.97 4.70 5.58 3 HP Standard Motor & High Static Drive Accessory 923 2.83 946 2.96 970 3.09 994 3.23 945 3.43 969 3.58 993 3.73 1016 3.88 980 4.15 1000 4.31 1019 4.46 1040 4.62 1018 4.90 1037 5.10 1056 5.30 1075 5.49 1057 5.77 — — — — — — 5 HP Oversized Motor & Sheaves For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Notes: 1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt may be necessary. 2. 5 HP Oversized Motor with Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may be necessary. 3. 5 HP Oversized Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt may be necessary. 4. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range. 32 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 1018 1038 1061 1093 — 1041 1060 1082 — — 3.39 4.03 4.78 5.67 — 3.54 4.17 4.95 — — 5 HP Oversized Motor & Field Supplied Drive (3) Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. RT-PRC002-EN Performance Data (17½Ton) Standard Efficiency Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C .10 .20 .30 CFM RPM BHP RPM BHP RPM BHP 5600 6300 7000 7700 8400 — 765 845 925 1006 — 2.96 4.02 5.32 6.87 — 788 866 944 1024 — 3.10 4.18 5.49 7.06 735 810 886 963 1041 2.34 3.23 4.33 5.66 7.24 External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor with Low Static Drive Accessory 759 2.46 783 2.60 807 2.74 830 2.89 831 3.36 852 3.50 874 3.65 895 3.81 906 4.48 925 4.62 944 4.77 963 4.93 982 5.82 999 5.98 1016 6.14 1033 6.30 1058 7.42 1075 7.60 1091 7.78 1107 7.95 7.5 HP Oversize Motor & Sheaves RPM .80 BHP .90 RPM BHP 1.00 RPM BHP 852 917 982 1050 1122 3.03 3.97 5.10 6.47 8.13 875 937 1002 1069 1138 898 956 1021 1086 1154 3.18 4.13 5.29 6.66 8.31 3.33 4.29 5.47 6.86 8.50 5 HP Standard Motor & Sheaves Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 5600 6300 7000 7700 8400 923 976 1039 1104 — 946 997 1057 1122 — 968 1019 1074 1138 — 989 1040 1092 1154 — 3.50 4.46 5.65 7.06 — 3.68 4.63 5.82 7.26 — 3.85 4.82 6.00 7.46 — 5 HP Standard Motor & Sheaves 4.03 1011 4.21 1033 4.39 5.00 1060 5.19 1079 5.39 6.19 1111 6.39 1130 6.59 7.66 1170 7.84 1186 8.05 — — — — — For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Notes: 1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/ Fan Speed” tables to determine operating range. 1056 1100 1150 1202 — 4.58 5.60 6.80 8.25 — 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 1078 1118 1168 1220 — 1099 1138 1186 — — 1122 1157 1205 — — 4.77 5.79 7.01 8.47 — 4.96 6.00 7.22 — — 5.18 6.20 7.46 — — 7.5 HP Oversive Motor & Sheaves Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. *Indicates both downflow and horizontal units. RT-PRC002-EN 33 Performance Data (20 Ton) Standard Efficiency Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B .10 CFM 6400 7200 8000 8800 9600 RPM — 527 578 629 681 .20 BHP — 2.08 2.79 3.65 4.67 RPM .30 BHP RPM BHP RPM External Static Pressure (Inches of Water) .40 .50 .60 .70 BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field Supplied Low Static Drive (1) 514 1.69 546 1.88 574 2.05 599 562 2.29 592 2.50 619 2.71 644 610 3.03 639 3.26 666 3.50 690 659 3.93 687 4.18 712 4.43 736 709 4.99 735 5.27 759 5.54 782 5 HP Standard Motor & Sheaves .80 RPM BHP .90 RPM BHP 1.00 RPM BHP 5 HP Standard Motor & Sheaves 2.21 2.91 3.73 4.69 5.82 624 667 712 758 804 (2) 2.37 3.09 3.96 4.96 6.11 648 689 733 778 824 2.54 671 2.71 695 2.90 720 3.26 711 3.45 732 3.64 752 4.16 753 4.35 773 4.55 792 5.20 797 5.43 816 5.65 834 6.39 843 6.67 861 6.92 878 7.5 HP Oversized Motor & Sheaves 3.11 3.83 4.75 5.86 7.16 Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 6400 7200 8000 8800 9600 744 773 811 852 895 768 795 830 869 911 3.32 4.04 4.96 6.08 7.40 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Sheaves 3.52 790 3.72 811 3.91 833 4.27 817 4.50 839 4.74 860 5.18 848 5.40 867 5.64 887 6.30 887 6.53 904 6.77 921 7.63 928 7.86 944 8.11 960 7.5 HP Oversized Motor & Sheaves 4.13 4.96 5.90 7.01 8.36 For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Notes: 1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary. 2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt may be necessary. 3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range. 855 880 907 938 976 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 5 HP Standard Motor & High Static Drive Accessory 4.36 877 4.59 897 4.82 917 5.05 936 5.19 898 5.41 917 5.64 937 5.88 957 6.16 927 6.42 946 6.68 964 6.93 982 7.26 955 7.52 973 7.81 991 8.09 — 8.61 — — — — — — — 5.29 6.14 7.18 — — Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. *Indicates both downflow and horizontal units. 34 RT-PRC002-EN Performance Data (25 Ton) Standard Efficiency Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B .10 .20 External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP .30 CFM RPM BHP RPM BHP RPM BHP 7000 7500 8000 8500 9000 9500 10000 10500 11000 — — 595 628 661 695 729 762 796 — — 2.92 3.47 4.08 4.76 5.52 6.35 7.27 — 595 627 659 691 723 755 788 821 — 2.66 3.16 3.73 4.36 5.06 5.84 6.69 7.63 593 624 655 686 717 749 781 812 844 7.5 HP Standard Motor & Low Static Drive Accessory 2.42 619 2.62 643 2.80 667 2.98 690 2.88 649 3.10 673 3.31 695 3.50 717 3.39 679 3.63 702 3.86 724 4.07 745 3.97 710 4.23 732 4.47 754 4.71 774 4.62 741 4.89 763 5.15 784 5.41 803 5.34 772 5.62 794 5.90 814 6.18 833 6.13 804 6.42 825 6.72 844 7.01 863 7.00 835 7.31 856 7.62 875 7.93 894 7.96 867 8.3 887 8.60 — — — 3.16 3.68 4.28 4.94 5.66 6.45 7.31 8.24 — .80 RPM BHP .90 RPM BHP 1.00 RPM BHP 7.5 HP Standard Motor & Sheaves 712 3.35 733 3.53 754 3.73 738 3.88 759 4.08 779 4.28 766 4.48 786 4.68 805 4.90 794 5.15 813 5.36 832 5.58 822 5.89 841 6.12 859 6.35 852 6.71 870 6.95 887 7.19 881 7.59 899 7.86 916 8.11 911 8.54 — — — — — — — — — — 7.5 HP Standard Motor & High Static Drive Accessory 7.5 HP Standard Motor & Sheaves Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 7000 7500 8000 8500 9000 9500 10000 10500 11000 776 798 824 850 877 904 933 — — 798 818 842 868 894 921 949 — — 3.95 4.48 5.11 5.81 6.58 7.43 8.36 — — External Static Pressure (Inches of Water) 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Sheaves 4.18 820 4.40 841 4.62 4.71 839 4.95 860 5.19 5.32 860 5.55 880 5.80 6.03 885 6.26 902 6.49 6.81 911 7.05 928 7.29 7.67 938 7.92 954 8.17 8.62 — — — — — — — — — — — — — — 862 880 899 920 944 970 — — — 4.84 5.42 6.06 6.74 7.53 8.42 — — — 7.5 HP Standard Motor & High Static Drive Accessory For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Note: 1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. *Indicates both downflow and horizontal units. RT-PRC002-EN 35 Performance Data (12½ Ton) High Efficiency Table PD-22 — Evaporator Fan Performance — 12½Ton — TCD151C — Standard or TXV Refrigeration System .10 CFM 2500* 3250* 4000 4500 5000 5500 6000 RPM — 378 430 466 503 540 579 .20 BHP RPM .30 BHP RPM 3 HP Standard Motor & Field Supplied Low Static Drive (2) — 402 0.30 460 0.35 447 0.49 503 0.56 495 0.74 549 0.74 528 0.95 580 0.96 562 1.20 612 1.22 597 1.49 645 1.53 633 1.82 680 BHP 0.39 0.62 0.91 1.14 1.42 1.74 2.10 External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP 510 552 596 627 657 689 722 3 HP Standard Motor & Field Supplied High Static Drive (2) 0.48 555 0.56 595 0.74 595 0.86 634 1.07 638 1.22 677 1.33 668 1.51 706 1.63 699 1.84 736 1.98 729 2.20 767 2.37 761 2.63 797 .80 RPM BHP .90 RPM BHP 1.00 RPM BHP 3 HP Standard Motor & Drive 0.64 0.97 1.37 1.68 2.04 2.44 2.87 633 672 712 742 771 801 832 0.74 1.08 1.52 1.85 2.23 2.66 3.13 667 706 747 776 803 833 864 3 HP Standard Motor & High Static Drive Accessory 0.83 1.19 1.66 2.02 2.41 2.87 3.38 699 739 778 806 835 864 894 0.92 1.30 1.80 2.18 2.61 3.07 3.61 731 769 809 836 865 893 922 1.02 1.40 1.94 2.34 2.80 3.28 3.83 5 HP Oversize Motor & Drive Table PD-22 — Evaporator Fan Performance — 12½ Ton — TCD151C — Continued CFM 1.10 RPM BHP 2500* 3250* 4000* 4500 5000 5500 6000 760 798 839 865 892 922 950 1.20 RPM BHP 1.30 RPM BHP 3 HP Standard Motor & Drive 1.11 789 1.21 817 1.52 827 1.64 853 2.07 867 2.21 893 2.50 892 2.66 919 2.97 920 3.15 946 3.49 949 3.70 975 4.05 977 4.29 1002 1.31 1.76 2.33 2.81 3.33 3.90 4.51 External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 842 880 919 945 971 999 1028 1.41 1.88 2.47 2.96 3.50 4.09 4.74 868 905 943 970 996 1023 1052 3 HP Standard Motor & High Static Drive Accessory 1.51 892 1.60 916 1.71 939 1.81 2.01 928 2.13 953 2.26 976 2.38 2.59 967 2.73 991 2.88 1013 3.03 3.11 994 3.25 1017 3.40 1039 3.55 3.68 1020 3.85 1043 4.02 1066 4.18 4.28 1047 4.48 1070 4.68 1091 4.87 4.96 1074 5.16 1098 5.38 1120 5.59 5 HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. *Unit applications below 4000 CFM • Electric heaters restricted on applications below 4000 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4000 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Note: 1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary. 36 1.80 RPM BHP 1.90 RPM BHP 962 998 1036 1061 1088 1114 — 1.91 2.51 3.18 3.70 4.35 5.06 — 2.00 RPM BHP 984 1020 1056.4 1082.3 1109.6 1135.6 — 2.01 2.63 3.33 3.85 4.50 5.24 — Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. RT-PRC002-EN Performance Data (12½ Ton) High Efficiency Table PD-23 — Evaporator Fan Performance — 12½Ton — T*D151C — Dehumidification (Hot Gas Reheat) Option .10 CFM 2500* 3000* 3500* 4000 4500 5000 5500 6000 RPM — — 551 618 686 755 824 894 .20 BHP — — 0.78 1.11 1.54 2.07 2.71 3.47 RPM — 534 594 656 720 786 853 921 .30 BHP External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP BHP RPM — 0.63 0.90 1.26 1.71 2.26 2.91 3.70 3 HP Standard Motor & Drive w/Field Supplied Low Static Drive Fan Sheave 526 0.52 570 0.62 609 0.73 578 0.74 618 0.86 656 0.98 633 1.03 670 1.16 706 1.30 692 1.40 727 1.55 759 1.71 753 1.87 785 2.03 815 2.20 816 2.44 846 2.61 874 2.79 881 3.13 908 3.32 935 3.51 947 3.93 972 4.15 996 4.36 .80 RPM BHP .90 RPM BHP 1.00 RPM BHP 3 HP Standard Motor & Drive 646 692 739 791 844 902 960 1021 0.83 1.11 1.44 1.86 2.37 2.98 3.70 4.56 681 725 771 821 873 928 985 1044 0.93 1.23 1.58 2.01 2.54 3.17 3.91 4.78 713 756 802 850 901 954 1010 1068 1.03 1.35 1.73 2.17 2.71 3.37 4.13 5.01 744 786 831 878 928 979 1033 1090 1.14 1.48 1.88 2.34 2.89 3.56 4.34 5.24 776 814 859 905 953 1004 1056 1112 1.25 1.60 2.02 2.50 3.07 3.75 4.54 5.47 5 HP Oversized Motor & Drive 3 HP Standard Motor & High Static Drive Accessory Table PD-23 — Evaporator Fan Performance — 12½ Ton — T*D151C — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 2500* 3000* 3500* 4000 4500 5000 5500 6000 3 HP Standard Motor & Drive 804 1.36 832 1.48 842 1.73 869 1.85 885 2.17 910 2.31 930 2.67 956 2.85 978 3.25 1002 3.44 1028 3.94 1051 4.14 1079 4.76 1102 4.97 1133 5.70 — — 5 HP Oversized Motor & Drive 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 1.90 RPM BHP 2.00 RPM BHP 998 1035 1072 1110 1154 1200 — — 1020 1057 1093 1132 1174 — — — 3 HP Standard Motor & High Static Drive Accessory 859 895 935 980 1026 1074 1123 — 1.59 1.98 2.45 3.01 3.63 4.35 5.17 — 883 920 959 1003 1049 1096 1146 — 1.71 2.11 2.59 3.17 3.83 4.55 5.40 — 908 945 983 1026 1071 1118 1166 — 1.83 2.24 2.74 3.34 4.02 4.76 5.62 — 931 968 1006 1047 1093 1140 — — 1.95 2.38 2.89 3.50 4.21 4.98 — — 954 991 1029 1069 1113 1159 — — 2.08 2.51 3.04 3.66 4.38 5.18 — — 977 1014 1051 1090 1134 1180 — — 2.21 2.65 3.19 3.82 4.57 5.40 — — 2.33 2.79 3.34 3.99 4.75 5.61 — — 2.47 2.94 3.49 4.16 4.94 — — — 5 HP Oversized Motor & Drive w/Field Supplied Fan Sheave For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 4000 CFM • Electric heaters restricted on applications below 4000 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4000 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Note: 1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary. RT-PRC002-EN 1.80 RPM BHP Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. 37 Performance Data (12½ Ton) High Efficiency Table PD-24 — Evaporator Fan Performance — 12½Ton — TCH151C — Standard Refrigeration System .10 .20 .30 External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP CFM RPM BHP RPM BHP RPM BHP 4000 4500 5000 5500 6000 — — 534 581 628 — — 1.40 1.83 2.34 — 521 566 611 657 — 1.17 1.54 1.99 2.51 510 551 593 637 682 3 HP Standard Motor & Field Supplied Low Static Drive (1) 0.98 541 1.10 572 1.22 602 1.35 631 1.29 579 1.42 607 1.56 635 1.68 662 1.67 620 1.81 645 1.95 671 2.11 696 2.13 661 2.28 685 2.43 709 2.59 732 2.68 704 2.83 727 3.00 749 3.16 770 1.48 1.82 2.25 2.76 3.33 .80 RPM 659 688 720 754 791 BHP .90 RPM BHP 1.00 RPM BHP 3 HP Standard Motor & Drive 1.62 687 1.76 714 1.98 713 2.13 738 2.40 744 2.56 767 2.92 777 3.08 799 3.52 812 3.70 833 5 HP Oversized Motor& Drive 1.91 2.28 2.73 3.25 3.87 Table PD-24 — Evaporator Fan Performance — 12½ Ton — TCH151C — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 4000 4500 5000 5500 6000 740 763 790 820 853 2.07 2.44 2.90 3.43 4.04 766 787 812 842 874 2.23 2.61 3.07 3.61 4.23 791 811 835 862 893 2.38 2.78 3.24 3.80 4.43 814 835 857 883 913 2.54 838 2.70 860 2.96 858 3.13 880 3.42 879 3.61 901 3.98 904 4.17 924 4.63 932 4.83 951 5 HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Note: 1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary. 38 1.80 RPM BHP 1.90 RPM BHP 3 HP Standard Motor & High Static Drive Accessory 2.86 883 3.02 905 3.19 926 3.31 901 3.48 922 3.66 943 3.81 922 4.00 942 4.20 962 4.37 944 4.57 964 4.78 984 5.03 970 5.24 988 5.45 1007 3.37 3.84 4.39 4.99 5.66 2.00 RPM BHP 948 963 982 1003 — 3.55 4.02 4.59 5.20 — Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. RT-PRC002-EN (15 Ton) Performance Data High Efficiency Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Standard or TXV Refrigeration System .10 CFM 3000* 3900* 4800 5400 6000 6600 7200 RPM — 341 399 445 479 519 560 .20 BHP — 0.45 0.76 1.04 1.38 1.79 2.28 RPM .30 BHP RPM BHP External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & 3 HP Standard Motor & Field Field Supplied Extra Supplied Low Static Drive (1) L ow Static Drive (2) 337 0.32 387 0.42 432 0.53 472 0.65 511 0.77 384 0.55 423 0.66 462 0.78 500 0.91 536 1.05 437 0.89 471 1.01 503 1.14 535 1.29 566 1.44 474 1.19 506 1.33 536 1.47 564 1.62 592 1.78 513 1.55 543 1.72 571 1.87 597 2.03 623 2.19 552 1.98 580 2.17 606 2.35 632 2.52 656 2.69 591 2.49 618 2.70 643 2.91 667 3.09 690 3.27 3 HP Standard Motor & Drive 547 569 598 621 648 679 712 0.90 1.19 1.60 1.95 2.36 2.87 3.46 .80 RPM 580 600 629 648 673 702 734 BHP .90 RPM BHP 1.00 RPM BHP 1.03 611 1.16 640 1.29 1.35 630 1.51 660 1.67 1.77 658 1.94 684 2.11 2.12 676 2.30 704 2.49 2.55 699 2.74 723 2.93 3.05 725 3.25 748 3.46 3.65 755 3.85 776 4.06 5 HP Oversized Motor & Drive Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 3000* 3900* 4800 5400 6000 6600 7200 667 688 710 730 749 771 797 1.43 1.84 2.29 2.68 3.13 3.67 4.29 693 715 735 755 774 794 818 1.57 2.00 2.48 2.88 3.34 3.88 4.51 717 741 760 778 798 816 839 1.71 2.17 2.68 3.07 3.56 4.09 4.74 740 766 785 800 821 839 860 1.86 2.34 2.88 3.28 3.77 4.32 4.96 763 790 809 823 842 862 881 3 HP Standard Motor & High Static Drive Accessory 2.01 784 2.16 805 2.31 2.51 812 2.68 834 2.85 3.09 832 3.29 854 3.49 3.49 845 3.71 867 3.94 3.99 863 4.20 884 4.43 4.56 884 4.80 904 5.03 5.20 902 5.45 923 5.70 5 HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. *Unit applications below 4000 CFM • Electric heaters restricted on applications below 4000 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4000 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/ccessories. Note: 1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field Supplied Belt may be necessary. 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 825 855 876 889 904 924 — 845 875 898 910 924 943 — 864 895 919 931 944 961 — 2.47 3.03 3.69 4.17 4.66 5.27 — 2.63 3.21 3.90 4.40 4.90 5.51 — 2.80 3.39 4.10 4.62 5.15 5.75 — Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. *Indicates both downflow and horizontal units. RT-PRC002-EN 39 Performance Data (15 Ton) High Efficiency Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Dehumidification (Hot Gas Reheat) Option .10 CFM 3000* 3600* 4200* 4800 5400 6000 6600 7200 RPM .20 BHP RPM .30 BHP 3 HP Standard Motor w/Field Supplied Motor Sheave (2) 295 0.26 346 0.35 333 0.40 379 0.51 373 0.60 415 0.72 414 0.84 452 0.99 455 1.14 491 1.32 497 1.51 531 1.73 540 1.96 572 2.20 583 2.50 613 2.75 RPM BHP External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor w/Field Supplied Motor Sheave (1) 391 0.45 432 0.56 420 0.62 458 0.74 452 0.85 487 0.98 487 1.13 519 1.27 524 1.48 554 1.64 561 1.91 590 2.08 601 2.42 628 2.61 641 3.02 666 3.23 3 HP Standard Motor & Drive .80 RPM BHP .90 RPM BHP 3 HP Standard Motorw/Field Supplied Low Static Drive Fan Sheave 471 0.68 506 0.80 539 0.92 569 1.04 596 1.17 494 0.87 527 1.00 559 1.14 589 1.28 617 1.43 520 1.12 551 1.26 581 1.41 610 1.57 638 1.73 550 1.43 579 1.59 607 1.74 635 1.91 660 2.08 582 1.80 610 1.98 637 2.15 662 2.33 687 2.51 617 2.26 643 2.44 667 2.63 692 2.83 715 3.02 653 2.80 678 2.99 701 3.20 724 3.41 746 3.61 690 3.44 714 3.65 736 3.86 758 4.08 778 4.30 5 HP Oversized Motor & Drive 1.00 RPM BHP 622 644 664 686 710 739 768 799 1.30 1.57 1.89 2.26 2.70 3.22 3.83 4.53 Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 3000* 3600* 4200* 4800 5400 6000 6600 7200 646 669 690 711 734 761 789 819 1.43 1.72 2.06 2.44 2.89 3.42 4.05 4.76 669 694 715 735 758 782 810 840 1.56 692 1.70 714 1.84 1.88 716 2.02 738 2.18 2.23 737 2.39 760 2.57 2.63 758 2.81 780 3.00 3.09 780 3.29 801 3.49 3.63 804 3.84 824 4.05 4.26 831 4.49 850 4.71 5.00 859 5.23 879 5.47 5 HP Oversized Motor & Drive 734 759 782 802 822 845 870 898 1.98 2.34 2.74 3.19 3.69 4.27 4.94 5.72 755 778 803 823 844 865 889 — 2.13 2.49 2.92 3.38 3.91 4.49 5.18 — 775 798 822 843 864 885 908 — 2.28 2.66 3.09 3.58 4.12 4.72 5.41 — 1.80 RPM BHP 1.90 RPM BHP 3 HP Standard Motor & High Static Drive Accessory 793 2.42 813 2.58 817 2.82 835 2.98 842 3.28 861 3.46 864 3.78 882 3.97 883 4.33 903 4.55 904 4.95 923 5.18 927 5.65 — — — — — — 2.00 RPM BHP 830 854 878 901 921 941 — — 2.72 3.16 3.64 4.17 4.76 5.41 — — 3 HP Standard Motor & High Static Drive Accessory For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 4800 CFM • Electric heaters restricted on applications below 4800 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4800 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options accessories. Note: 1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may be necessary. Field Supplied Belt may be necessary. 40 Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. RT-PRC002-EN Performance Data (17½ Ton) High Efficiency Table PD-27 — Evaporator Fan Performance — 17½ Ton — TC*211C — Standard or TXV Refrigeration System .10 CFM 3500* 4550* 5600 6300 7000 7700 8400 RPM — — 452 499 546 594 642 .20 BHP — — 1.14 1.63 2.11 2.75 3.52 RPM — — 487 532 578 625 671 BHP External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP RPM — 0.90 1.45 1.94 2.52 3.21 4.03 5 HP Standard Motor & Field Supplied Extra Low Static Drive (2) 448 0.66 488 0.78 490 1.03 524 1.17 547 1.60 575 1.75 588 2.10 614 2.26 631 2.71 655 2.89 675 3.43 698 3.64 720 4.27 741 4.51 590 621 656 687 723 761 802 .30 BHP — — 1.30 1.76 2.31 2.98 3.78 RPM — 457 518 561 606 651 697 .80 BHP .90 RPM BHP 1.00 RPM BHP 1.20 1.64 2.26 2.79 3.44 4.23 5.16 622 649 683 711 744 782 821 652 676 710 735 766 801 840 5 HP Standard Motor & Field Supplied Low Static Drive (1) 523 557 602 639 678 720 762 0.91 1.32 1.91 2.43 3.07 3.84 4.73 557 590 629 663 701 741 782 1.05 1.48 2.08 2.60 3.25 4.03 4.95 1.35 1.80 2.43 2.99 3.64 4.44 5.38 1.50 1.97 2.63 3.19 3.85 4.65 5.60 5 HP Standard Motor & High Static Drive Accessory Table PD-27— Evaporator Fan Performance — 17½ Ton — TC*211C — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive 3500* 4550* 5600 6300 7000 7700 8400 680 703 736 759 788 821 858 1.65 2.15 2.83 3.38 4.07 4.87 5.82 707 729 761 783 810 841 876 1.80 2.34 3.03 3.59 4.29 5.10 6.06 732 754 785 807 831 861 894 1.95 2.54 3.23 3.82 4.51 5.34 6.30 756 779 807 830 852 881 912 2.11 2.73 3.43 4.04 4.74 5.59 6.55 779 803 829 853 874 900 930 2.27 801 2.43 822 2.92 827 3.11 849 3.64 851 3.86 872 4.27 874 4.49 894 4.97 895 5.22 917 5.83 919 6.07 939 6.81 949 7.08 967 7.5 Oversize Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. *Unit applications below 5600 CFM • Electric heaters restricted on applications below 5600 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 5600 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Note: 1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary. 2.60 3.31 4.09 4.72 5.47 6.32 7.34 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 5 HP Standard Motor & High Static Drive Accessory 843 2.77 863 2.94 882 871 3.50 892 3.70 913 893 4.32 914 4.56 935 913 4.95 933 5.19 952 937 5.72 957 5.97 975 958 6.58 978 6.85 997 984 7.60 1002 7.87 — 3.11 3.89 4.80 5.43 6.22 7.12 — Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. *Indicates both downflow and horizontal units. RT-PRC002-EN 41 Performance Data (20 Ton) High Efficiency Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Standard or TXV Refrigeration System .10 CFM 4000* 5200* 6400 7200 8000 8800 9600 RPM .20 BHP RPM .30 BHP RPM BHP External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field Supplied Extra Low Static Drive (3) — — — — 428 0.69 467 0.82 504 0.95 426 0.94 463 1.09 494 1.22 524 1.35 555 1.51 506 1.64 540 1.84 570 2.03 595 2.19 620 2.34 560 2.28 592 2.50 620 2.72 646 2.92 668 3.10 616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 671 4.04 698 4.29 724 4.55 747 4.83 769 5.10 728 5.19 753 5.46 776 5.74 799 6.04 820 6.34 5 HP Standard Motor & Drive (2) .80 RPM 5 HP Standard Motor & Field Supplied Low Static Drive (1) 538 1.08 572 1.23 603 585 1.67 614 1.83 642 644 2.51 669 2.69 693 690 3.27 711 3.45 733 739 4.22 759 4.41 778 790 5.34 808 5.56 826 840 6.63 859 6.90 876 7.5 HP Oversized Motor & Drive BHP .90 RPM BHP 1.00 RPM BHP 1.38 2.00 2.89 3.65 4.60 5.77 7.14 632 670 717 755 797 844 893 660 696 741 777 817 861 909 1.55 2.17 3.09 3.86 4.81 5.98 7.37 1.71 2.35 3.29 4.08 5.03 6.20 7.59 Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 1.80 RPM BHP 5 HP Standard Motor & Drive 4000* 5200* 6400 7200 8000 8800 9600 688 722 765 799 837 879 925 1.87 2.54 3.49 4.31 5.26 6.43 7.83 714 2.03 739 2.20 747 2.73 771 2.93 788 3.70 810 3.91 820 4.53 841 4.76 857 5.51 876 5.76 897 6.67 915 6.93 941 8.07 958 8.32 7.5 HP Oversized Motor & Drive 764 795 832 862 896 933 974 2.36 3.14 4.12 4.99 6.01 7.19 8.58 787 817 854 883 915 951 — 2.53 3.35 4.34 5.22 6.26 7.46 — For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. *Unit applications below 6400 CFM • Electric heaters restricted on applications below 6400 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Notes: 1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary. 2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be necessary. 3. Field Supplied Fan Sheave B5V200 and Motor Sheave IVP34 required. Field Supplied Belt may be necessary. 810 839 875 902 934 969 — 2.70 3.56 4.57 5.46 6.52 7.74 — 831 861 896 922 953 986 — 2.87 3.77 4.80 5.69 6.77 8.01 — 852 882 916 942 971 — — 1.90 RPM BHP 2.00 RPM BHP 5 HP Standard Motor & High Static Drive Accessory 3.05 873 3.23 892 3.41 3.98 902 4.19 923 4.41 5.04 936 5.29 955 5.54 5.94 961 6.19 980 6.44 7.03 989 7.29 — — — — — — — — — — — — Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. *Indicates both downflow and horizontal units. 42 RT-PRC002-EN Performance Data (20 Ton) High Efficiency Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Dehumidification (Hot Gas Reheat) Option .10 CFM 4000* 4800* 5600* 6400 7200 8000 8800 9600 RPM — 414 469 525 583 641 699 758 .20 BHP — 0.84 1.25 1.80 2.50 3.37 4.42 5.67 RPM — 452 504 558 613 669 725 782 .30 BHP External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP BHP RPM — 0.99 1.45 2.03 2.75 3.64 4.72 6.00 5 HP Standard Motor & Field Supplied Fan Sheave (1) 441 0.77 477 0.90 487 1.13 519 1.27 536 1.61 566 1.78 588 2.24 615 2.42 641 3.02 666 3.23 695 3.93 719 4.21 750 5.03 773 5.35 805 6.32 827 6.68 511 550 594 641 690 742 794 848 .80 RPM BHP .90 RPM BHP 1.00 RPM BHP 5 HP Standard Motor & Drive & Field Supplied 5 HP Standard Low Static Fan Sheave Motor & Drive 1.03 543 1.17 573 1.32 603 1.47 631 1.63 658 1.43 579 1.59 607 1.74 635 1.91 660 2.08 686 1.95 620 2.12 647 2.30 672 2.49 696 2.67 720 2.61 666 2.80 689 3.00 713 3.20 736 3.41 758 3.44 714 3.65 736 3.86 758 4.08 778 4.30 799 4.45 763 4.67 785 4.91 805 5.14 825 5.38 844 5.65 815 5.91 835 6.15 854 6.41 873 6.66 892 7.04 867 7.35 886 7.63 904 7.90 923 8.18 941 7.5 HP Oversized Motor & Drive (3) 1.78 2.26 2.87 3.62 4.53 5.62 6.93 8.46 5 HP Standard Motor & High StaticDrive Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Continued CFM 1.10 RPM BHP 4000* 4800* 5600* 6400 7200 8000 8800 9600 684 711 743 779 819 863 909 — 1.20 RPM BHP 1.30 RPM BHP External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 1.80 RPM BHP 1.90 RPM BHP 753 780 809 841 879 918 961 — 834 864 890 919 952 988 — — 5 HP Standard Motor & High Static Drive 852 3.29 870 3.47 882 3.97 901 4.17 910 4.75 929 4.98 938 5.66 956 5.90 968 6.70 987 6.97 — — — — — — — — — — — — 5 HP Standard Motor & Drive 1.94 2.44 3.06 3.82 4.76 5.87 7.19 — 708 735 765 800 840 881 927 — 2.10 2.63 3.26 4.04 5.00 6.12 7.46 — 731 758 787 821 859 900 944 — 2.27 2.81 3.46 4.26 5.23 6.38 7.73 — 2.43 3.00 3.67 4.48 5.47 6.64 8.01 — 775 802 830 861 898 936 978 — 2.60 3.19 3.88 4.70 5.72 6.90 8.29 — 795 823 850 881 916 954 994 — 2.77 3.38 4.09 4.93 5.96 7.16 8.56 — 814 843 871 899 933 971 — — 2.94 3.58 4.31 5.16 6.19 7.42 — — 3.12 3.78 4.53 5.41 6.46 7.69 — — 2.00 RPM BHP 7.5 HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 6400 CFM • Electric heaters restricted on applications below 6400 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Notes: 1. Field Supplied Motor Sheave IVP34 Required. Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary. 3. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be necessary. RT-PRC002-EN Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. 43 Performance Data (25 Ton) High Efficiency Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Standard Refrigeraton System .10 .20 RPM .30 BHP RPM BHP External Static Pressure (Inches of Water) .40 .50 .60 .70 RPM BHP RPM BHP RPM BHP RPM BHP CFM RPM BHP 5000* 6500* 7000* 7500* 8000 8500 9000 9500 10000 10500 11000 — — — 582 616 650 685 721 756 791 827 7.5 HP Standard Motor & Field Supplied Extra Low Static Drive (1) — — — — — — — — — — — — 576 2.11 601 2.27 625 2.43 — 579 2.32 608 2.54 633 2.73 656 2.89 2.59 611 2.78 640 3.02 665 3.24 687 3.43 3.07 645 3.31 672 3.56 696 3.80 719 4.02 3.66 678 3.90 704 4.16 728 4.43 750 4.68 4.31 712 4.56 737 4.83 760 5.12 782 5.39 5.04 746 5.30 770 5.58 792 5.88 814 6.18 5.85 780 6.12 803 6.41 825 6.72 846 7.04 6.74 814 7.03 836 7.33 858 7.64 878 7.98 7.71 849 8.02 870 8.33 891 8.63 — — 7.5 HP Standard Motor & Drive 576 649 678 708 739 771 802 834 866 898 — 1.56 2.59 3.06 3.61 4.22 4.90 5.65 6.46 7.35 8.31 — .80 RPM BHP .90 RPM BHP 1.00 RPM BHP 7.5 HP Standard Motor & Low Static Drive Accessory 606 1.71 635 1.88 663 2.05 690 2.22 674 2.78 698 2.97 722 3.18 746 3.38 700 3.25 723 3.44 745 3.65 768 3.87 729 3.79 749 3.98 770 4.19 792 4.41 759 4.41 778 4.60 797 4.81 817 5.03 790 5.10 808 5.31 826 5.52 844 5.74 821 5.88 839 6.09 856 6.30 873 6.53 853 6.72 870 6.96 887 7.18 903 7.41 884 7.64 902 7.90 918 8.14 934 8.38 916 8.62 — — — — — — — — — — — — — — 7.5 HP Standard Motor & Higher Static Drive Accessory Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Continued CFM 1.10 RPM BHP 1.20 RPM BHP 5000* 6500* 7000* 7500* 8000 8500 9000 9500 10000 10500 11000 716 769 790 813 837 863 890 919 949 — — 741 792 812 833 857 881 908 936 — — — 2.41 3.59 4.09 4.65 5.26 5.97 6.76 7.64 8.62 — — External Static Pressure (Inches of Water) 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP 7.5 HP Standard Motor & Drive 2.60 765 2.80 789 3.80 814 4.01 836 4.31 833 4.53 854 4.88 854 5.12 874 5.51 876 5.76 896 6.21 900 6.46 919 7.00 925 7.25 943 7.88 952 8.13 969 — — — — — — — — — — — — 3.00 4.22 4.76 5.36 6.01 6.73 7.52 8.40 — — — 812 857 875 894 915 937 961 985 — — — 3.20 4.44 4.99 5.59 6.26 6.99 7.79 8.67 — — — 7.5 HP Standard Motor & High Static Drive Accessory For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34. Fan motor heat (MBH) = 3.15 x Fan BHP *Unit applications below 8000 CFM • Electric heaters restricted on applications below 8000 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 8000 CFM. Notes: Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. *Indicates both downflow and horizontal units. 44 RT-PRC002-EN Performance Data (12½-25 Ton) Table PD-31— Standard Motor & Drive/Fan Speed (Rpm) Tons 12½ 15 17½ 20 25 Unit Model No. TC*150D3,4,W, TC*151C3,4,W TC*150DK TC*180B3,4,W TC*180BK TC*181C3,4,W TC*210C3,4,W TC*210CK TC*211C3,4,W TC*240B3,4,W,TC*241C3,4,W TC*240BK TC*300B/301C3,4,W TC*300BK 6Turns Open 640 705 679 N/A 560 869 869 615 615 590 705 701 5Turns Open 680 756 721 680 600 923 924 659 659 627 742 738 4Turns Open 720 806 764 733 640 978 978 703 703 664 779 775 3Turns Open 760 857 806 785 680 1032 1032 747 747 701 817 812 2Turns Open 800 907 849 837 720 1087 1087 791 791 738 854 849 1Turn Open 840 957 891 889 760 1141 1141 835 835 775 891 886 Closed N/A N/A N/A 941 N/A N/A N/A N/A N/A N/A N/A N/A Factory set at 3 turns open. Table PD-32— Standard Motor & High Static Drive Accessory/Fan Speed (Rpm) Tons 12½ 15 17½ 20 25 Unit Model No. TC*151C3,4,W TC*180B3,4,W TC*181B3,4,W TC*211C3,4,W TC*240B/241C3,4,W TC*300B/301C3,4,W 6Turns Open 807 806 640 835 835 816 5Turns Open 857 849 680 879 879 853 4Turns Open 908 891 720 923 923 890 3Turns Open 958 934 760 967 967 928 2Turns Open 1009 976 800 1011 1011 965 1Turn Open 1059 1019 840 1055 1055 1002 Closed N/A N/A N/A N/A N/A N/A Table PD-33— Oversized Motor & Drive/Fan Speed (Rpm) Tons 12½ 15 17½ 20 Unit Model No. TC*150D,151C3,4,W TC*180B3,4,W TC*181C3,4,W TC*210C3,4,W TC*211C3,4,W 6Turns Open 869 806 705 949 816 5Turns Open 923 856 755 1008 853 4Turns Open 978 907 806 1068 890 3Turns Open 1032 957 856 1127 928 2Turns Open 1087 1008 907 1187 965 1Turn Open 1141 1058 957 1246 1002 Closed N/A N/A N/A N/A N/A TC*240B/241C3,4,W 816 853 890 928 965 1002 N/A Closed Table PD-34 — Standard Motor & Low Static Fan Drive Tons Unit Model No. 6Turns Open 5Turns Open 4Turns Open 3Turns Open 2Turns Open 1Turn Open 17½ TC*210C3,4,W 705 755 806 856 907 957 25 N/A TC*300B/301C3,4,W 594 631 668 705 742 779 N/A *Indicates both downflow and horizontal units. RT-PRC002-EN 45 Performance Data (12½-25 Ton) Table PD-35 — Static Pressure Drops Through Accessories (Inches Water Column) Tons Unit Model No. TC*150D, TCH151C 12½ TCD151C TC*180B 15 TCD181C TCH181C TC*210C 17½ TCD211C TCH211C TCD240B 20 TCD241C TCH240B, TCH241C TCD300B 25 TCD301C TCH300B, TCH301C Standard Through 2 Inch CFM Filters1 Reheat Coil Pleated Filters4 4000 0.05 — 0.08 5000 0.07 — 0.11 6000 0.10 — 0.15 2500 0.02 0.01 0.03 4000 0.05 0.03 0.08 5000 0.07 0.05 0.11 6000 0.10 0.06 0.15 4800 0.07 — 0.10 6000 0.10 — 0.15 7200 0.15 — 0.19 3000 0.02/0.01 0.01 0.03/0.02 4800 0.04/0.03 0.02 0.07/0.06 6000 0.06/0.05 0.03 0.10/0.09 7200 0.09/0.07 0.04 0.13/0.11 4800 0.04/0.03 — 0.07/0.06 6000 0.06/0.05 — 0.10/0.09 7200 0.09/0.07 — 0.13/0.11 5600 0.09 — 0.13 7000 0.14 — 0.18 8400 0.20 — 0.24 3500 0.02/0.02 — 0.03/0.03 5600 0.06/0.05 — 0.09/0.08 7000 0.09/0.07 — 0.13/0.11 8400 0.12/0.10 — 0.17/0.14 5600 0.06/0.05 — 0.09/0.08 7000 0.09/0.07 — 0.13/0.11 8400 0.12/0.10 — 0.17/0.14 6400 0.07 — 0.11 8000 0.11 — 0.15 9600 0.16 — 0.20 4000 0.03 0.02 0.04 6400 0.07 0.04 0.11 8000 0.11 0.05 0.15 9600 0.16 0.07 0.20 6400 0.06 — 0.10 8000 0.09 — 0.13 9600 0.13 — 0.17 7000 0.09 — 0.13 9000 0.14 — 0.18 11000 0.21 — 0.25 5000 0.04 — 0.06 7000 0.09 — 0.13 9000 0.14 — 0.18 11000 0.21 — 0.25 7000 0.07 — 0.11 9000 0.11 — 0.15 11000 0.17 — 0.22 Economizer with OA/RA Dampers2 100% OA 100% RA 0.19 0.02 0.26 0.03 0.33 0.04 0.07 0.01 0.19 0.02 0.26 0.03 0.33 0.04 0.25 0.03 0.33 0.04 0.40 0.05 0.07 0.03 0.14 0.03 0.20 0.04 0.27 0.05 0.14 0.03 0.20 0.04 0.27 0.05 0.30 0.04 0.39 0.05 0.47 0.06 0.09 0.03 0.18 0.04 0.26 0.04 0.35 0.06 0.18 0.04 0.26 0.04 0.35 0.06 0.22 0.04 0.32 0.05 0.44 0.07 0.11 0.03 0.22 0.04 0.32 0.05 0.44 0.07 0.22 0.04 0.32 0.05 0.44 0.07 0.26 0.04 0.40 0.07 0.57 0.10 0.15 0.03 0.26 0.04 0.40 0.07 0.57 0.10 0.26 0.04 0.40 0.07 0.60 0.10 5-12 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 14-27 0.03 0.04 0.06 * 0.03 0.04 0.06 0.04 0.06 0.09 * 0.04 0.06 0.09 0.04 0.06 0.09 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — Electric Heater Accessory (KW)3 36 54 0.03 0.04 0.05 0.06 0.07 0.09 * * 0.03 0.04 0.05 0.06 0.07 0.09 0.04 0.05 0.07 0.08 0.10 0.12 * * 0.04 0.05 0.07 0.08 0.10 0.12 0.04 0.05 0.07 0.08 0.10 0.12 0.06 0.07 0.10 0.11 0.15 0.17 * * 0.05 0.06 0.08 0.09 0.12 0.13 0.05 0.06 0.08 0.09 0.12 0.13 0.06 0.08 0.10 0.12 0.14 0.17 * * 0.06 0.08 0.10 0.12 0.14 0.17 0.06 0.08 0.10 0.12 0.14 0.17 0.08 0.10 0.13 0.15 0.18 0.22 * * 0.08 0.10 0.13 0.15 0.18 0.22 0.08 0.10 0.13 0.15 0.18 0.22 72 — — — — — — — — — — — — — — — — — — — — * 0.07 0.11 0.16 0.07 0.11 0.16 0.09 0.14 0.20 * 0.09 0.14 0.20 0.09 0.14 0.20 0.11 0.18 0.26 * 0.11 0.18 0.26 0.11 0.18 0.26 Notes: 1. Tested with: 2” filters 12½-25 tons 2. OA = Outside Air and RA = Return Air. 3. Nominal KW ratings at 240, 480, 600 volts. 4. Difference in pressure drop should be considered when utilizing optional 2” pleated filters. *Heaters not permitted at airflows below 320 cfm/ton. *Indicates both downflow and horizontal units. 46 RT-PRC002-EN Performance Data (12½-25 Ton) Table PD-36 — Auxiliary Electric Heat Capacity Unit Model No. KW Input1 Total2 MBH Output1 No. of Stages KW Input1 MBH Output1 KW Input1 Stage 2 MBH Output1 12½-15 TC*150D3,D4,DW,DK TC*180B3,B4,BW,BK TC*151 or 181C3,C4,CW 18.00 27.004 36.00 54.00 61.47 92.15 122.94 184.41 1 2 2 2 18.00 9.00 18.00 36.00 61.47 30.72 61.47 122.94 — 18.00 18.00 18.00 — 61.43 61.47 61.47 17½, 20, 25 TC*210C3,C4,CW,CK TC*240, 300B3,B4,BW,BK TC*211, 241, 301C3,C4,CW 36.00 54.00 72.003 122.94 184.41 245.88 2 2 2 18.00 36.00 36.00 61.47 122.94 122.94 18.00 18.00 36.00 61.47 61.47 122.94 Tons Stage1 Notes: 2 1. Does not include indoor fan power or heat. Voltage 2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP = x rated cap. Rated Voltage 3. Not available on TC*210C. 4. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor. ( ) Table PD-37 — Electric Heater Voltage Correction Factors (Applicable to Auxiliary Heat Capacity) Nominal Voltage Distribution Voltage Capacity Multiplier 240 208 230 240 0.75 0.92 1.00 480 440 460 480 0.84 0.94 1.00 600 540 575 600 0.81 0.92 1.00 Table PD-38 — Air Temperature Rise Across Electric Heaters (Degree F) KW 9.00 17.30 18.00 27.00 36.00 54.00 72.002 Stages 1 1 1 2 2 2 2 12½ Ton 5000 CFM 15 Ton 6000 CFM 17½ Ton 7000 CFM 20 Ton 8000 CFM 25 Ton 9000 CFM Three Phase TC*150 TC*151 — — 11.4 — 22.8 34.1 — Three Phase TC*180 TC*181 — — 9.5 14.22 19.0 28.5 — Three Phase TC*210 TC*211 — — — 12.221 16.3 24.4 32.5 Three Phase TC*240 TC*241 — — — 10.72 14.2 21.3 28.5 Three Phase TC*300 TC*301 — — — 9.52 12.6 19.0 25.3 For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different air flow, use following formula: KW x 3413 Temp. Rise across Elect. Htr = 1.08 x CFM Notes: 1. Not available on TC*210 model. 2. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor. RT-PRC002-EN 47 Performance Data Table PD-39— Hot Gas Reheat Temperature Rise1,2,3 Tons 12½ Tons 15 Tons 20 SCFM 2500 3000 3500 4000 4500 5000 5500 6000 SCFM 3000 3600 4200 4800 5400 6000 6600 7200 SCFM 4000 4800 5600 6400 7200 8000 8800 9600 Leaving Evaporator Dry Bulb [F]1 35 40 45 50 23.4 23.8 25.0 26.9 21.4 21.6 22.5 24.0 19.5 19.7 20.4 21.5 17.8 18.1 18.6 19.6 16.3 16.7 17.3 18.1 14.9 15.5 16.2 17.1 13.5 14.4 15.3 16.2 12.1 13.4 14.6 15.7 35 40 45 50 34.4 36.7 38.9 41.2 29.3 31.2 33.1 35.0 25.4 27.0 28.6 30.2 22.3 23.7 25.1 26.5 19.9 21.2 22.4 23.7 18.0 19.1 20.3 21.4 16.4 17.5 18.6 19.6 15.1 16.1 17.1 18.1 35 40 45 50 22.0 22.5 23.6 25.4 19.1 19.8 20.9 22.3 16.6 17.4 18.4 19.5 14.7 15.5 16.3 17.2 13.5 14.1 14.7 15.4 12.9 13.2 13.7 14.2 12.5 12.9 13.3 13.7 12.4 12.8 13.1 13.5 55 29.5 26.0 23.1 20.9 19.2 18.0 17.2 16.7 55 43.5 36.9 31.9 27.9 24.9 22.5 20.7 19.1 55 27.7 24.0 20.9 18.2 16.2 14.8 14.2 13.9 60 32.9 28.7 25.2 22.5 20.5 19.2 18.1 17.6 60 45.8 38.8 33.5 29.3 26.2 23.7 21.7 20.1 60 30.6 26.1 22.4 19.3 17.0 15.5 14.8 14.5 65 37.0 31.9 27.7 24.5 22.1 20.4 19.1 18.3 65 48.1 40.8 35.1 30.7 27.4 24.8 22.8 21.1 65 34.0 28.5 24.0 20.6 17.9 16.2 15.4 15.0 Notes: 1. Temperature does not account for indoor fan heat. 2. 70 deg OD Ambient Temperature. 3. For units with the Dehumidification (Hot Gas Reheat) option. 48 RT-PRC002-EN Controls Field Installed Control Options Zone Sensors Zone sensors are the building occupant’s comfort control devices.They replace the conventional electro-mechanical thermostats.The following zone sensor options are available for Voyager units with the ReliaTel™ control: Manual Changeover Heat, Cool or Off System Switch. Fan Auto or Off Switch. One temperature setpoint lever. Manual/Automatic Changeover Auto, Heat, Cool or Off System Switch. Fan Auto or Off Switch.Two temperature setpoint levers. Optional Status Indication LED lights, System On, Heat, Cool, or Service. Remote Sensor Sensor(s) available for all zone sensors to provide remote sensing capabilities. Dual Thermistor Remote Zone Sensor This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. RT-PRC002-EN Digital Display Zone Sensor The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors.This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC).This sensor should be utilized with ReliaTel controls. Programmable Night Setback Auto or manual changeover with sevenday programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. All programmable sensors have System On, Heat, Cool, Service LED/indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and two (2) Override programs per day. Integrated ComfortTM System Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane Integrated Comfort system. CO2 Sensing The CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements.The CO2 sensor kit is available as a field installed accessory. Economizer Controls The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two optional controls, Enthalpy and Differential Enthalpy Control. Enthalpy Control Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable set point. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability. Differential Enthalpy Replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source.This control option offers the highest level of comfort control, plus energy efficiency, available. Remote Potentiometer Minimum position setting of economizer can be remotely adjusted with this accessory. Differential Pressure Switches This factory or field-installed option allows individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation. Trane Communication Interface (TCI) This factory or field-installed microprocessor interface allows the unit to communicate toTrane’s Integrated Comfort system. 49 Electrical Data (Standard Efficiency) Table ED-1 — Unit Wiring — Standard Efficiency Tons 12½ 15 17½ 20 25 Standard Indoor Fan Motor Minimum Maximum Fuse Circuit Size or Maximum Ampacity2 Circuit Breaker1 Oversize Indoor Fan Motor Minimum Maximum Fuse Circuit Size or Maximum Ampacity2 Circuit Breaker1 Unit Model No. Unit Operating Voltage Range TC*150D3 TC*150D4 TC*150DW TC*150DK TC*180B3 TC*180B4 TC*180BW TC*180BK 187-253 414-506 518-633 342-418 187-253 414-506 517-633 342-418 63 33 26 43 78 39 31 50 80 40 30 50 90 50 40 60 69 36 28 – 84 42 33 – 80 40 35 – 100 50 40 – TC*210C3 TC*210C4 TC*210CW TC*210CK TC*240B3 TC*240B4 TC*240BW TC*240BK 187-253 414-506 517-633 342-418 187-253 414-506 517-633 342-418 88 44 35 57 100 50 40 65 100 50 45 70 125 60 45 80 96 47 38 – 107 54 43 – 125 60 45 – 125 60 50 – TC*300B3 TC*300B4 TC*300BW TC*300BK 187-253 414-506 517-633 342-418 118 58 46 70 150 70 50 80 – – – – – – – – Notes: 1. HACR breaker per NEC. 2. Values do not include power exhaust accessory. *Indicates both downflow and horizontal units. 50 RT-PRC002-EN Electrical Data (Standard Efficiency) Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only) Control Stages Oversize Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 Heater Model No. 12½ TCD150D3 AYDHTRF318A AYDHTRF336A AYDHTRF354A 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 63/68 108/122 154/176 80/80 110/125 175/200 69/76 115/130 162/184 80/80 125/150 175/200 15 TCD180B3 AYDHTRK318A AYDHTRK336A AYDHTRK354A 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 78/78 108/122 154/176 100/100 110/125 175/200 84/84 115/130 162/184 100/100 125/150 175/200 AYDHTRL336A AYDHTRL354A 27.0/36.0 40.5/54.0 2 2 115/130 162/184 125/150 175/200 125/139 171/193 125/150 175/200 Tons Heater KW Rating1 Standard Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 To Use With 208/230 Volts Three Phase 17½ TCD210C3 20 TCD240B3 AYDHTRL336A AYDHTRL354A AYDHTRK372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 115/130 162/184 209/238 125/150 175/200 225/250 125/139 171/193 218/247 125/150 175/200 225/250 25 TCD300B3 AYDHTRL336A AYDHTRL354A AYDHTRK372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 125/139 171/193 218/247 150/150 175/200 225/250 — — — — — — 12½ TCD150D4 AYDHTRL418A AYDHTRK436A AYDHTRK454A 18.0 36.0 54.0 1 2 2 34 61 88 40 70 90 37 64 91 40 70 100 15 TCD180B4 AYDHTRL418A AYDHTRK436A AYDHTRK454A 18.0 36.0 54.0 1 2 2 39 61 88 50 70 90 42 64 91 50 70 100 AYDHTRL436A AYDHTRL454A 36.0 54.0 2 2 64 91 70 100 68 95 70 100 460 Volts Three Phase 17½ TCD210C4 20 TCD240B4 AYDHTRL436A AYDHTRL454A AYDHTRK472A 36.0 54.0 72.0 2 2 2 64 91 118 70 100 125 68 95 123 70 100 125 25 TCD300B4 AYDHTRL436A AYDHTRL454A AYDHTRK472A 36.0 54.0 72.0 2 2 2 68 95 123 70 100 125 — — — — — — 12½ TCD150DW AYDHTRKW18A AYDHTRMW36A AYDHTRKW54A 18.0 36.0 54.0 1 2 2 27 49 70 30 50 70 30 51 73 35 60 80 15 TCD180BW AYDHTRKW18A AYDHTRMW36A AYDHTRKW54A 18.0 36.0 54.0 1 2 2 31 49 70 40 50 70 33 51 73 40 60 80 AYDHTRMW36A AYDHTRLW54A 36.0 54.0 2 2 51 73 60 80 55 77 60 80 575 Volts Three Phase 17½ TCD210CW 20 TCD240BW AYDHTRMW36A AYDHTRLW54A AYDHTRKW72A 36.0 54.0 72.0 2 2 2 51 73 95 60 80 100 55 77 98 60 80 100 25 TCD300BW AYDHTRMW36A AYDHTRLW54A AYDHTRKW72A 36.0 54.0 72.0 2 2 2 55 77 98 60 80 100 — — — — — — Notes: 1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit. 2. HACR type circuit breaker per NEC. RT-PRC002-EN 51 Electrical Data (Standard Efficiency) Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only), continued Tons To Use With Heater Model No. Heater KW Rating1 Control Stages Standard Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 Oversize Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 380 Volts Three Phase 12½ TCD150DK AYDHTRL418A AYDHTRK436A AYDHTRK454A 15 TCD180BK AYDHTRL418A AYDHTRK436A AYDHTRK454A 11.3 22.6 33.8 1 2 2 50 55 76 60 60 80 — — — — — — AYDHTRL436A AYDHTRL454A 22.6 33.8 2 2 60 81 70 90 — — — — 17½ TCD210CK 11.3 22.6 33.8 1 2 2 43 55 76 50 60 80 — — — — — — 20 TCD240BK AYDHTRL436A AYDHTRL454A AYDHTRK472A 22.6 33.8 45.1 2 2 2 65 81 103 80 90 110 — — — — — — 25 TCD300BK AYDHTRL436A AYDHTRL454A AYDHTRK472A 22.6 33.8 45.1 2 2 2 70 81 103 80 90 100 — — — — — — Notes: 1. Heater kw ratings are at 380V for 380 unit. 2. HACR type circuit breaker per NEC. 52 RT-PRC002-EN Electrical Data (Standard Efficiency) Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Horizontal Only) Tons To Use With Heater Model No. Heater KW Rating1 Standard Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 Control Stages Oversize Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 208/230 Volts Three Phase 12½ TCH150D3 AYHHTRN318A AYHHTRN336A AYHHTRN354A 15 TCH180B3 AYHHTRN318A AYHHTRP336A AYHHTRP354A 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 78/78 108/122 154/176 100/100 110/125 175/200 84/84 115/130 162/184 100/100 125/150 175/200 AYHHTRQ336A AYHHTRQ354A 27.0/36.0 40.5/54.0 2 2 115/130 162/184 125/150 175/200 125/139 171/193 125/150 175/200 17½ TCH210C3 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 63/68 108/122 154/176 80/80 110/125 175/200 69/76 115/130 162/184 80/80 125/150 175/200 20 TCH240B3 AYHHTRN336A AYHHTRN354A AYHHTRN372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 115/130 162/184 209/238 125/150 175/200 225/250 125/139 171/193 218/247 125/150 175/200 225/250 25 TCH300B3 AYHHTRN336A AYHHTRN354A AYHHTRN372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 132/139 171/193 218/247 150/150 175/200 225/250 — — — — — — 12½ TCH150D4 AYHHTRN418A AYHHTRN436A AYHHTRP454A 18.0 36.0 54.0 1 2 2 34 61 88 40 70 90 37 64 91 40 70 100 15 TCH180B4 AYHHTRN418A AYHHTRP436A AYHHTRP454A 18.0 36.0 54.0 1 2 2 37 61 88 50 70 90 42 64 91 50 70 100 AYHHTRQ436A AYHHTRQ454A 36.0 54.0 2 2 64 91 70 100 68 95 70 100 460 Volts Three Phase 17½ TCH210C4 20 TCH240B4 AYHHTRN436A AYHHTRN454A AYHHTRN472A 36.0 54.0 72.0 2 2 2 64 91 118 70 100 125 68 95 123 70 100 125 25 TCH300B4 AYHHTRN436A AYHHTRN454A AYHHTRN472A 36.0 54.0 72.0 2 2 2 68 95 123 70 100 125 — — — — — — 12½ TCH150DW AYHHTRNW18A AYHHTRPW36A AYHHTRPW54A 18.0 36.0 54.0 1 2 2 27 49 70 30 50 70 30 51 73 35 60 80 15 TCH180BW AYHHTRNW18A AYHHTRPW36A AYHHTRPW54A 18.0 36.0 54.0 1 2 2 31 49 70 40 50 70 33 51 73 40 60 80 AYHHTRPW36A AYHHTRQW54A 36.0 54.0 2 2 51 73 60 80 55 77 60 80 575 Volts Three Phase 17½ TCH210CW 20 TCH240BW AYHHTRMW36A AYHHTRNW54A AYHHTRNW72A 36.0 54.0 72.0 2 2 2 51 73 95 60 80 100 55 77 98 60 80 100 25 TCH300BW AYHHTRMW36A AYHHTRNW54A AYHHTRNW72A 36.0 54.0 72.0 2 2 2 55 77 98 60 80 100 — — — — — — Notes: 1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit.. 2. HACR type circuit breaker per NEC. RT-PRC002-EN 53 Electrical Data (Standard Efficiency) Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Horizontal Only) continued Control Stages Oversize Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 Heater Model No. 12½ TCD150DK AYDHTRL418A AYDHTRK436A AYDHTRK454A 11.3 22.6 33.8 1 2 2 43 55 76 50 60 80 — — — — — — 15 TCD180BK AYDHTRL418A AYDHTRK436A AYDHTRK454A 11.3 22.6 33.8 1 2 2 50 55 76 60 60 80 — — — — — — AYDHTRL436A AYDHTRL454A 22.6 33.8 2 2 60 81 70 90 — — — — Tons Heater KW Rating1 Standard Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 To Use With 380 Volts Three Phase 17½ TCD210CK 20 TCD240BK AYDHTRL436A AYDHTRL454A AYDHTRK472A 22.6 33.8 45.1 2 2 2 65 81 103 80 90 110 — — — — — — 25 TCD300BK AYDHTRL436A AYDHTRL454A AYDHTRK472A 22.6 33.8 45.1 2 2 2 70 81 103 80 90 100 — — — — — — Notes: 1. Heater kw ratings are at 380V for 380 unit. 2. HACR type circuit breaker per NEC. 54 RT-PRC002-EN Electrical Data (Standard Efficiency) Table ED-4— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency Compressor Motors Tons 12½ 15 17½ 20 25 Unit Model No. No. Volts Phase HP2 RPM Amps1 RLA LRA TC*150D3 TC*150D4 TC*150DW TC*150DK 2 2 2 2 208-230 460 575 380 3 3 3 3 6.00 6.00 6.00 6.0 3450 3450 3450 3450 20.4 10.8 8.3 13.1 TC*180B3 TC*180B4 TC*180BW TC*180BK 2 2 2 2 208-230 460 575 380 3 3 3 3 9.30/5.10 9.30/5.10 9.30/5.10 9.3/5.1 TC*210C3 TC*210C4 TC*210CW TC*210CK 2 2 2 2 208-230 460 575 380 3 3 3 3 9.3/6.0 9.3/6.0 9.3/6.0 9.3/6.0 TC*240B3 TC*240B4 TC*240BW TC*240BK 2 2 2 2 208-230 460 575 380 3 3 3 3 9.30 9.30 9.30 9.3 3450 3450 3450 3450 TC*300B3 TC*300B4 TC*300BW TC*300BK 2 2 2 2 208-230 460 575 380 3 3 3 3 10.00 10.00 10.00 10.0 3450 3450 3450 3450 No. Condenser Fan Motors Amps1 Phase HP FLA LRA 156 75 54 70 2 2 2 2 1 1 1 1 .50 .50 .50 .50 3.2 1.6 1.3 1.9 8.8 3.8 3.2 5.2 3450 31.9/20.7 3450 16.3/10.0 3450 13.1/7.4 3450 19.7/12.1 253/128 113/63 85/49 125/64 2 2 2 2 1 1 1 1 .50 .50 .50 .50 3.2 1.6 1.3 1.9 8.8 3.8 3.2 5.2 3450 31.5/20.8 3450 15.9/10.0 3450 12.8/8.2 3450 19.2/12.1 253/156 113/75 85/54 125/70 2 2 2 2 1 1 1 1 1.00 1.00 1.00 1.00 5.5 2.9 2.0 3.5 18.3 9.3 5.7 8.5 31.7 16.2 13.0 19.6 253 113 85 125 2 2 2 2 1 1 1 1 1.00 1.00 1.00 1.00 5.5 2.9 2.0 3.5 18.3 9.3 5.7 8.5 36.6 17.9 14.9 21.7 278 124 92 137 2 2 2 2 1 1 1 1 1.00 1.00 1.00 1.00 5.5 2.9 2.0 3.5 18.3 9.3 5.7 8.5 Notes: 1. Amp draw for each motor; multiply value by numbers of motors to determine total amps. 2. HP for each compressor. *Indicates both downflow and horizontal units. RT-PRC002-EN 55 Electrical Data (High Efficiency) Table ED-5 — Unit Wiring - High Efficiency - Standard Refrigeration System Standard Indoor Fan Motor Minimum Maximum Fuse Circuit Size or Maximum Ampacity2 Circuit Breaker1 Oversize Indoor Fan Motor Minimum Maximum Fuse Circuit Size or Maximum Ampacity2 Circuit Breaker1 Unit Model No. Unit Operating Voltage Range 12½ TC*151C3 TC*151C4 TC*151CW 187-253 414-506 517-633 64 31 25 80 40 30 70 34 28 90 40 35 15 TC*181C3 TC*181C4 TC*181CW 187-253 414-506 517-633 74 36 29 90 50 40 80 38 31 100 50 40 17½ TC*211C3 TC*211C4 TC*211CW 187-253 414-506 517-633 91 44 35 110 60 45 98 48 38 125 60 50 20 TC*241C3 TC*241C4 TC*241CW 187-253 414-506 517-633 99 50 40 125 60 50 107 54 43 125 60 50 25 TC*301C3 TC*301C4 TC*301CW 187-253 414-506 517-633 120 58 47 150 70 60 N/A N/A N/A N/A N/A N/A Tons Notes: 1. HACR breaker per NEC. 2. Values do not include power exhaust accessory. Table ED-6— Unit Wiring - High Efficiency - TXV/Face-Split Evaporator Coil Option (Downflow Only) Tons 12½ 15 17½ 20 25 Unit Model No. TCD151C3 TCD151C4 TCD151CW TCD181C3 TCD181C4 TCD181CW TCD211C3 TCD211C4 TCD211CW TCD241C3 TCD241C4 TCD241CW TCD301C3 TCD301C4 TCD301CW Unit Operating Voltage Range 187-253 414-506 517-633 187-253 414-506 517-633 187-253 414-506 517-633 187-253 414-506 517-633 187-253 414-506 517-633 Standard Indoor Fan Motor Minimum Maximum Fuse Circuit Size or Maximum Ampacity2 Circuit Breaker1 59 70 30 35 24 30 74 90 37 50 30 40 91 125 45 60 36 45 99 125 51 60 40 50 117 150 57 70 46 50 Oversize Indoor Fan Motor Minimum Maximum Fuse Circuit Size or Maximum Ampacity2 Circuit Breaker1 65 80 32 40 26 30 80 90 39 50 32 40 99 125 49 60 39 50 107 125 54 70 43 50 N/A N/A N/A N/A N/A N/A Notes: 1. HACR breaker per NEC. 2. Values do not include power exhaust accessory. 56 RT-PRC002-EN Electrical Data (High Efficiency) Table ED-7 — Unit Wiring - High Efficiency - Dehumidification (Hot Gas Reheat) Option (Downflow Only) Tons 12½ 15 20 Unit Model No. TCD151C3 TCD151C4 TCD151CW TCD181C3 TCD181C4 TCD181CW TCD241C3 TCD241C4 TCD241CW Unit Operating Voltage Range 187-253 414-506 517-633 187-253 414-506 517-633 187-253 414-506 517-633 Standard Indoor Fan Motor Minimum Maximum Fuse Circuit Size or Maximum 2 Ampacity Circuit Breaker1 59 70 30 35 24 30 71 90 36 45 28 35 98 125 50 60 39 50 Oversize Indoor Fan Motor Minimum Maximum Fuse Circuit Size or Maximum 2 Ampacity Circuit Breaker1 65 80 32 40 26 30 77 100 39 50 30 40 105 125 53 60 42 50 Notes: 1. HACR breaker per NEC. 2. Values do not include power exhaust accessory. RT-PRC002-EN 57 Electrical Data (High Efficiency) Table ED-8 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, Standard Refrigeration System (Downflow Only) Control Stages Oversize Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 Heater Model No. 12½ TCD151C3 AYDHTRK318A AYDHTRK336A AYDHTRK354A 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 64/68 108/122 154/176 80/80 110/125 175/200 70/76 115/130 162/184 90/90 125/150 175/200 15 TCD181C3 AYDHTRK318A AYDHTRK336A AYDHTRK354A 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 74/74 108/122 154/176 100/100 110/125 175/200 80/80 115/130 162/184 100/100 125/150 175/200 17½ TCD211C3 AYDHTRL336A AYDHTRL354A AYDHTRK372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 115/130 162/184 209/238 125/150 175/200 225/250 125/139 171/193 218/247 125/150 175/200 225/250 20 TCD241C3 AYDHTRL336A AYDHTRL354A AYDHTRK372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 115/130 162/184 209/238 125/150 175/200 225/250 125/139 171/193 218/247 125/150 175/200 225/250 25 TCD301C3 AYDHTRL336A AYDHTRL354A AYDHTRK372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 125/139 171/193 218/247 150/150 175/200 225/250 — — — — — — TCD151C4 AYDHTRL418A AYDHTRK436A AYDHTRK454A 18.0 36.0 54.0 1 2 2 34 61 88 40 70 90 37 64 91 40 70 100 AYDHTRL418A AYDHTRK427A AYDHTRK436A AYDHTRK454A 18.0 27.0 36.0 54.0 1 2 2 2 36 47 61 88 50 50 70 90 38 — 64 91 50 — 70 100 AYDHTRL427A AYDHTRL436A AYDHTRL454A AYDHTRK472A 27.0 36.0 54.0 72.0 2 2 2 2 51 64 91 118 60 70 100 125 — 68 95 123 — 70 100 125 AYDHTRL427A AYDHTRL436A AYDHTRL454A AYDHTRK472A 27.0 36.0 54.0 72.0 2 2 2 2 51 64 91 118 60 70 100 125 — 68 95 123 — 70 100 125 AYDHTRL436A AYDHTRL427A AYDHTRL454A AYDHTRK472A 36.0 27.0 54.0 72.0 2 2 2 2 68 58 95 123 70 70 100 125 — — — — — — — Tons Heater KW Rating Standard Indoor Motor Max Fuse Size or MCA Max Circuit Breaker1 To Use With 208/230 Volts Three Phase 460 Volts Three Phase 12½ 15 17½ 20 25 TCD181C4 TCD211C4 TCD241C4 TCD301C4 575 Volts Three Phase 58 12½ TCD151CW AYDHTRKW18A AYDHTRMW36A AYDHTRKW54A 18.0 36.0 54.0 1 2 2 27 49 70 30 50 70 30 51 73 35 60 80 15 TCD181CW AYDHTRKW18A AYDHTRMW36A AYDHTRKW54A 18.0 36.0 54.0 1 2 2 29 49 70 40 50 70 31 31 73 40 40 80 17½ TCD211CW AYDHTRMW36A AYDHTRLW54A AYDHTRKW72A 36.0 54.0 72.0 2 2 2 51 73 95 60 80 100 55 77 98 60 80 100 20 TCD241CW AYDHTRMW36A AYDHTRLW54A AYDHTRKW72A 36.0 54.0 72.0 2 2 2 51 73 95 60 80 100 55 77 98 60 80 100 25 TCD301CW AYDHTRMW36A AYDHTRLW54A AYDHTRKW72A 36.0 54.0 72.0 2 2 2 55 77 98 60 80 100 — — — — — — Notes: 1. HACR type circuit breaker per NEC. 2. Values do not include power exhaust accessory. RT-PRC002-EN Electrical Data (High Efficiency) Table ED-9 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, Standard Refrigeration System (Horizontal Only) Tons To Use With Heater Model No. Heater KW Rating Control Stages Standard Indoor Motor Max Fuse Size or MCA Max Circuit Breaker1 Oversize Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 208/230 Volts Three Phase 12½ TCH151C3 AYHHTRN318A AYHHTRP336A AYHHTRP354A 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 64/68 108/122 154/176 80/80 110/125 175/200 70/76 115/130 162/184 90/90 125/150 175/200 15 TCH181C3 AYHHTRM318A AYHHTRM336A AYHHTRM354A 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 74/74 108/122 154/176 100/100 110/125 175/200 80/80 115/130 162/184 100/100 125/150 175/200 17½ TCH211C3 AYHHTRN336A AYHHTRN354A AYHHTRN372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 115/130 162/184 209/238 125/150 175/200 225/250 125/139 171/193 218/247 125/150 175/200 225/250 20 TCH241C3 AYHHTRN336A AYHHTRN354A AYHHTRN372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 115/130 162/184 209/238 125/150 175/200 225/250 125/139 171/193 218/247 125/150 175/200 225/250 25 TCH301C3 AYHHTRN336A AYHHTRN354A AYHHTRN372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 125/139 171/193 218/247 150/150 175/200 225/250 — — — — — — 12½ TCH151C4 AYHHTRN418A AYHHTRP436A AYHHTRP454A 18.0 36.0 54.0 1 2 2 34 61 88 40 70 90 37 64 91 40 70 100 15 TCH181C4 AYHHTRM418A AYHHTRM436A AYHHTRM454A 18.0 36.0 54.0 1 2 2 36 61 88 50 70 90 38 64 91 50 70 100 17½ TCH211C4 AYHHTRN436A AYHHTRN454A AYHHTRN472A 36.0 54.0 72.0 2 2 2 64 91 118 70 100 125 68 95 123 70 100 125 20 TCH241C4 AYHHTRN436A AYHHTRN454A AYHHTRN472A 36.0 54.0 72.0 2 2 2 64 91 118 70 100 125 68 95 123 70 100 125 25 TCH301C4 AYHHTRN436A AYHHTRN454A AYHHTRN472A 36.0 54.0 72.0 2 2 2 68 95 123 70 100 125 — — — — — — 12½ TCH151CW AYHHTRNW18A AYHHTRPW36A AYHHTRPW54A 18.0 36.0 54.0 1 2 2 27 49 70 30 50 70 30 51 73 35 60 80 15 TCH181CW AYHHTRMW18A AYHHTRMW36A AYHHTRMW54A 18.0 36.0 54.0 1 2 2 29 49 70 40 50 70 31 31 73 40 40 80 17½ TCH211CW AYHHTRMW36A AYHHTRNW54A AYHHTRNW72A 36.0 54.0 72.0 2 2 2 51 73 95 60 80 100 55 77 98 60 80 100 20 TCH241CW AYHHTRMW36A AYHHTRNW54A AYHHTRNW72A 36.0 54.0 72.0 2 2 2 51 73 95 60 80 100 55 77 98 60 80 100 25 TCH301CW AYHHTRMW36A AYHHTRNW54A AYHHTRNW72A 36.0 54.0 72.0 2 2 2 55 77 98 60 80 100 — — — — — — 460 Volts Three Phase 575 Volts Three Phase Notes: 1. HACR type circuit breaker per NEC. 2. Values do not include power exhaust accessory. RT-PRC002-EN 59 Electrical Data (High Efficiency) Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and 151/181/ 241 Reheat Option(Downflow Only) Tons To Use With Heater Model No. Heater KW Rating Standard Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 Control Stages Oversize Indoor Motor Max Fuse Size or MCA Max Circuit Breaker1,2 208/230 Volts Three Phase 12½ TCD151C3 AYDHTRK318A AYDHTRK336A AYDHTRK354A 15 TCD181C3 AYDHTRK318A AYDHTRK336A AYDHTRK354A 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 *AYDHTRK318A 13.5/18.0 1 71/71 90/90 77/77 100/100 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 115/130 162/184 209/238 125/150 175/200 225/250 125/139 171/193 218/247 125/150 175/200 225/250 TCD181C3 13.5/18.0 27.0/36.0 40.5/54.0 1 2 2 61/68 108/122 154/176 70/70 110/125 175/200 68/76 115/130 162/184 80/80 125/150 175/200 74/74 108/122 154/176 100/100 110/125 175/200 80/80 115/130 162/184 90/90 125/150 175/200 17½ TCD211C3 AYDHTRL336A AYDHTRL354A AYDHTRK372A 20 TCD241C3 AYDHTRL336A AYDHTRL354A AYDHTRK372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 115/130 162/184 209/238 125/150 175/200 225/250 125/139 171/193 218/247 125/150 175/200 225/250 25 TCD301C3 AYDHTRL336A AYDHTRL354A AYDHTRK372A 27.0/36.0 40.5/54.0 54.0/72.0 2 2 2 125/139 171/193 218/247 150/150 175/200 225/250 — — — — — — TCD151C4 AYDHTRL418A AYDHTRK436A AYDHTRK454A 18.0 36.0 54.0 1 2 2 34 61 88 35 70 90 37 64 91 40 70 100 TCD181C4 AYDHTRL418A AYDHTRK427A3 AYDHTRK436A AYDHTRK454A 18.0 27.0 36.0 54.0 1 2 2 2 37 47 61 88 50 50 70 90 39 — 64 91 50 — 70 100 *AYDHTRL418A 18.0 1 36 45 39 50 AYDHTRL427A3 AYDHTRL436A AYDHTRL454A AYDHTRK472A 27.0 36.0 54.0 72.0 2 2 2 2 51 64 91 118 60 70 100 125 — 68 95 123 — 70 100 125 AYDHTRL427A3 AYDHTRL436A AYDHTRL454A AYDHTRK472A 27.0 36.0 54.0 72.0 2 2 2 2 51 64 91 118 60 70 100 125 — 68 95 123 — 70 100 125 AYDHTRL427A3 AYDHTRL436A AYDHTRL454A AYDHTRK472A 27.0 36.0 54.0 72.0 2 2 2 2 57 68 95 123 70 70 100 125 — — — — — — — — 460 Volts Three Phase 12½ 15 TCD181C4 17½ 20 25 TCD211C4 TCD241C4 TCD301C4 Notes: 1. HACR type circuit breaker per NEC. 2. Values do not include power exhaust accessory. 3. Do not use with oversized motor. * Applies only to Dehumidification (Hot Gas Reheat) Models 60 RT-PRC002-EN Electrical Data (High Efficiency) Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and 151/181/ 241 Reheat Option(Downflow Only), continued Tons To Use With Heater Model No. Heater KW Rating Control Stages Standard Indoor Motor Max Fuse Size or MCA Max Circuit Breaker2 Oversize Indoor Motor Max Fuse Size or MCA Max Circuit Breaker1,2 575 Volts Three Phase 12½ TCD151CW AYDHTRKW18A AYDHTRMW36A AYDHTRKW54A 15 TCD181CW AYDHTRKW18A AYDHTRMW36A AYDHTRKW54A 18.0 36.0 54.0 1 2 2 30 49 70 40 50 70 32 51 73 40 60 80 *AYDHTRKW18A AYDHTRMW36A AYDHTRLW54A AYDHTRKW72A 18.0 36.0 54.0 72.0 1 2 2 2 28 51 73 95 35 60 80 100 30 55 77 98 40 60 80 100 TCD181CW 18.0 36.0 54.0 1 2 2 27 49 70 30 50 70 30 51 73 30 60 80 17½ TCD211CW 20 TCD241CW AYDHTRMW36A AYDHTRLW54A AYDHTRKW72A 36.0 54.0 72.0 2 2 2 51 73 95 60 80 100 55 77 98 60 80 100 25 TCD301CW AYDHTRMW36A AYDHTRLW54A AYDHTRKW72A 36.0 54.0 72.0 2 2 2 55 77 98 60 80 100 — — — — — — Notes: 1. HACR type circuit breaker per NEC. 2. Values do not include power exhaust accessory. 3. Do not use with oversized motor. * Applies only to Dehumidification (Hot Gas Reheat) Models RT-PRC002-EN 61 Electrical Data (High Efficiency) Table ED-11 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, Standard Refrigeration System Compressor Motors Condenser Fan Motors Unit Model No. No. Volts Phase HP2 RPM Amps1 RLA LRA 12½ TC*151C3 TC*151C4 TC*151CW 2 2 2 208-230 460 575 3 3 3 5.70 5.70 5.70 3450 3450 3450 20.7 10.0 8.2 15 TC*181C3 TC*181C4 TC*181CW 2 2 2 208-230 460 575 3 3 3 17½ TC*211C3 TC*211C4 TC*211CW 2 2 2 208-230 460 575 3 3 3 20 TC*241C3 TC*241C4 TC*241CW 2 2 2 208-230 460 575 3 3 3 9.30 9.30 9.30 3450 3450 3450 25 TC*301C3 TC*301C4 TC*301CW 2 2 2 208-230 460 575 3 3 3 10.00 10.00 10.00 3450 3450 3450 Tons No. Phase HP Amps1 FLA LRA 156 75 54 2 2 2 1 1 1 .50 .50 .50 3.2 1.6 1.3 8.8 3.8 3.2 9.30/4.50 3450 31.5/16.9 9.30/4.50 3450 15.1/8.2 9.30/4.50 3450 12.1/6.6 253/124 113/59.6 85/49.4 2 2 2 1 1 1 .50 .50 .50 3.2 1.6 1.3 8.8 3.8 3.2 10.0/5.70 3450 33.3/20.7 10.0/5.70 3450 16.3/10.0 10.0/5.70 3450 13.2/8.2 278/156 124/75 92/54 2 2 2 1 1 1 1.00 1.00 1.00 5.5 2.9 2.0 18.3 9.3 5.7 31.6 16.1 12.9 253 113 85 2 2 2 1 1 1 1.00 1.00 1.00 5.5 2.9 2.0 18.3 9.3 5.7 37.6 18.3 14.9 278 124 92 2 2 2 1 1 1 1.00 1.00 1.00 5.5 2.9 2.0 18.3 9.3 5.7 Notes: 1. Amp draw for each motor; multiply value by numbers of motors to determine total amps. 2. HP for each compressor. Table ED-12 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, TXV/Face-Split Evaporator Coil Option (Downflow Only) Compressor Motors Tons 12½ 15 17½ 20 25 Unit Model No. No. TCD151C3 TCD151C4 TCD151CW TCD181C3 TCD181C4 TCD181CW TCD211C3 TCD211C4 TCD211CW TCD241C3 TCD241C4 TCD241CW TCD301C3 TCD301C4 TCD301CW 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Volts 208-230 460 575 208-230 460 575 208-230 460 575 208-230 460 575 208-230 460 575 2 Phase 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 HP 5.7 5.7 5.7 9.30/4.50 9.30/4.50 9.30/4.50 10.00/5.7 10.00/5.7 10.00/5.7 9.0/9.3 9.0/9.3 9.0/9.3 10.00 10.00 10.00 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 3500/3450 3500/3450 3500/3450 3450 3450 3450 Amps1 RLA LRA 18.6 9.4 7.4 32.1/16.4 15.6/8.7 12.3/7.4 34.8/19.5 17.0/10.3 13.8/8.1 30.4/32.6 16.1/16.8 12.5/13.4 36.2 17.7 14.3 156 75 54 253/124 113/59.6 85/49.4 278/156 124/75 92/54 225/253 114/113 80/85 278 124 92 No. 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Condenser Fan Motors Amps1 Phase HP FLA LRA 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 .50 .50 .50 .50 .50 .50 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3.2 1.6 1.3 3.2 1.6 1.3 5.5 2.9 2.0 5.5 2.9 2.0 5.5 2.9 2.0 8.8 3.8 3.2 8.8 3.8 3.2 18.3 9.3 5.7 18.3 9.3 5.7 18.3 9.3 5.7 Notes: 1. Amp draw for each motor; multiply value by numbers of motors to determine total amps. 2. HP for each compressor. Table ED-13 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Dehumidification (Hot Gas Reheat) Option (Downflow Only) Compressor Motors Tons 12½ 15 20 Unit Model No. No. TCD151C3 TCD151C4 TCD151CW TCD181C3 TCD181C4 TCD181CW TCD241C3 TCD241C4 TCD241CW 2 2 2 2 2 2 2 2 2 Volts 208-230 460 575 208-230 460 575 208-230 460 575 Phase 3 3 3 3 3 3 3 3 3 2 HP 5.7/5.7 5.7/5.7 5.7/5.7 8.3/5.7 8.3/5.7 8.3/5.7 9.0/9.3 9.0/9.3 9.0/9.3 RPM 3450 3450 3450 3450 3450 3450 3500/3450 3500/3450 3500/3450 Amps1 RLA LRA 18.6 9.7 7.6 27.4/19.0 13.8/10.1 10.7/7.9 30.1/31.7 15.6/16.2 12.1/13.0 156 75 54 208/156 100/75 68/54 225/253 114/113 80/85 No. 2 2 2 2 2 2 2 2 2 Condenser Fan Motors Amps1 Phase HP FLA LRA 1 1 1 1 1 1 1 1 1 .50 .50 .50 .50 .50 .50 1.00 1.00 1.00 3.2 1.6 1.3 3.2 1.6 1.3 5.5 2.9 2.0 8.8 3.8 3.2 8.8 3.8 3.2 18.3 9.3 5.7 Notes: 1. Amp draw for each motor; multiply value by numbers of motors to determine total amps. 2. HP for each compressor. *Indicates both downflow and horizontal units. 62 RT-PRC002-EN Electrical Data Table ED-14 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Standard and Oversized Standard Evaporator Fan Motor Unit Model No. Tons Amps FLA LRA No. Oversized Evaporator Fan Motor Amps Volts Phase HP FLA LRA No. Volts Phase HP 12½ TC*150D3, TC*151C3 TC*150D4, TC*151C4 TC*150DW, TC*151CW TC*150DK 1 1 1 1 208-230 460 575 380 3 3 3 3 3.00 3.00 3.00 5.0 10.6 4.8 3.9 9.2 81.0 40.5 31.0 66.5 1 1 1 — 208-230 460 575 — 3 3 3 — 5.00 5.00 5.00 — 16.7 7.6 6.1 — 109.8 54.9 41.6 — 15 TC*180B3, TC*181C3 TC*180B4, TC*181C4 TC*180BW, TC*181CW TC*180BK 1 1 1 1 208-230 460 575 380 3 3 3 3 3.00 3.00 3.00 5.0 10.6 4.8 3.9 9.2 81.0 40.5 31.0 66.5 1 1 1 — 208-230 460 575 — 3 3 3 — 5.00 5.00 5.00 — 16.7 7.6 6.1 — 109.8 54.9 41.6 — 17½ TC*210C3, TC*211C3 TC*210C4, TC*211C4 TC*210CW, TC*211CW TC*210CK 1 1 1 1 208-230 460 575 380 3 3 3 3 5.00 5.00 5.00 7.5 16.7 7.6 6.1 13.3 109.8 54.9 41.6 83.5 1 1 1 — 208-230 460 575 — 3 3 3 — 7.50 7.50 7.50 — 24.2 11.0 9.0 — 120.4 74.0 60.0 — 20 TC*240B3, TC*241C3 TC*240B4, TC*241C4 TC*240BW, TC*241CW TC*240BK 1 1 1 1 208-230 460 575 380 3 3 3 3 5.00 5.00 5.00 7.5 16.7 7.6 6.1 13.3 109.8 54.9 41.6 83.5 1 1 1 — 208-230 460 575 — 3 3 3 — 7.50 7.50 7.50 — 24.2 11.0 9.0 — 120.4 74.0 60.0 — 25 TC*300B3, TC*301C3 TC*300B4, TC*301C4 TC* 300BW, TC*301CW TC*300BK 1 1 1 1 208-230 460 575 380 3 3 3 3 7.50 7.50 7.50 7.5 24.2 11.0 9.0 13.3 120.4 74.0 60.0 83.5 — — — — — — — — — — — — — — — — — — — — — — — — *Indicates both downflow and horizontal units. RT-PRC002-EN 63 Electrical Data Table ED-15 — Electrical Characteristics — Power Exhaust Accessory Accessory Operating Voltage Phase HP RPM FLA \Amps LRA 12½1, 2 208-230 1 3/4 1040 6.6 13.5 15, 17½ 460 1 3/4 1040 3.2 8.4 20, 25 575 1 3/4 1040 2.1 5.2 Tons Notes: 1. 12½ Ton Standard Unit. 2. 12½ Ton High Efficiency Unit. 64 RT-PRC002-EN Jobsite Connections Zone Sensors —Typical Number Of Wires DISCONNECT SWITCH (BY OTHERS) A— Manual Changeover ....................................... 4 Manual/Auto Changeover ............................... 5 Manual/Auto Changeover with Status Indication LED’s ........................... 10 Programmable Night Setback with Status Indication LED’s ............................. 7 ZONE SENSORS ROOFTOP UNIT B— 3 Power Wires + 1 Ground Wire (three phase) 2 Power Wires + 1 Ground Wire (single phase) For specific wiring information, see the installation instructions. All wiring except power wires is low voltage. All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer. RT-PRC002-EN 65 Typical Wiring 66 (12½-25 Ton) RT-PRC002-EN Typical Wiring (12½-25 Ton) Typical wiring diagram. For specific wiring, see individual Service Facts. RT-PRC002-EN 67 Typical Wiring 68 (12½-25 Ton) RT-PRC002-EN Typical Wiring RT-PRC002-EN (12½-25 Ton) 69 Dimensional Data (12½ Ton) High Efficiency (12½, 15, 17½ Ton) Standard Efficiency All dimensions are in inches. Note: Duct flanges mount 7-7/16" down inside the curb on the 1½" curb flanges. See recommended duct dimensions on the next page. Roofcurb is intended for downflow use only. Downflow Unit Clearance 70 RT-PRC002-EN (12½ Ton) High Efficiency (12½, 15, 17½ Ton) Dimensional Data Standard Efficiency All dimensions are in inches. 1" Downflow Duct Connections — Field Fabricated 17 7/8" 59 7/16" 26 5/16" 52 1/2" 1 1\2" PERIMETER CURB FLANGE 14 1/16" 7 7/16" 1" N UR T RE LY PP SU Note: Duct flanges mount 7-7/16" down inside the curb on the 1½" curb flanges. Roofcurb is intended for downflow use only. Horizontal Unit Supply/Return and Unit Clearance RT-PRC002-EN 71 Dimensional (15-25 Ton) High Efficiency (20, 25 Ton) Data Standard Efficiency All dimensions are in inches. Note: Duct flanges mount 7-7/16" down inside the curb on the 1½" curb flanges. See recommended duct dimensions on the next page. Roofcurb is intended for downflow use only. 72 Downflow Unit Clearance RT-PRC002-EN Dimensional (15-25 Ton) High Efficiency (20, 25 Ton) Data Standard Efficiency All dimensions are in inches. 1" Downflow Duct Connections — Field Fabricated 19 5/16" 73 7/16" 26 5/16" 66 1/2" 1 1\2" PERIMETER CURB FLANGE 14 1/16" 7 7/16" 1" N UR T RE Y PL P SU Note: Duct flanges mount 7-7/16" down inside the curb on the 1½" curb flanges. Roofcurb is intended for downflow use only. Horizontal Unit Supply/Return and Unit Clearance RT-PRC002-EN 73 Dimensional Data (12½-25 Ton) Accessories All dimensions are in inches. Note: When applying economizer to horizontal units, connecting ductwork must be run full size to allow proper operation of Economizer Damper. Table DD-1 Unit Model # TC*150, 151-180, 210 TC*181, 211-301 A 1 17 /2 191/2 B1 C2 53¾ 64¾ 36 39 Notes: 1. Horizontal dimension only. Downflow economizer is width of end panel. 2. Power exhaust is applied on downflow economizer only. 74 RT-PRC002-EN Dimensional Data Factory Installed Options (FIOPS) All dimensions are in inches. Table DD-2 Unit Model # RT-PRC002-EN A B C TCD150, 151, 180, 210 423/8 483/8 31 TCD181, 211-301 291/2 56 381/2 75 Dimensional Data Factory Installed Options (FIOPS) Disconnect Switch or Circuit Breaker Fan Failure Switch Clogged Filter Switch Powered or Unpowered Convenience Outlet Trane Communication Interface Hinged Access Door Black Epoxy Coated Outdoor Coils Hinged Access Door Through the Base Electrical High Pressure Cut Out Supply and/or Return Smoke Detectors 76 RT-PRC002-EN Dimensional Data (12½-25 Ton) Table DD-3 — Standard Efficiency Units Condensate Tons 12½, 15, 17½ 20, 25 Downflow Only Drain Size A B C D F G H 267/16 267/16 221/2 283/4 1811/16 1915/16 41/4 41/4 41/4 41/4 627/16 765/16 5411/16 6811/16 1 NPT 1 NPT Condensate Drain Location Downflow Horizontal E J E K — — 255/8 263/4 — — 6 53/8 Table DD-4 — High Efficiency Units Condensate Tons 12½ 15-25 RT-PRC002-EN Downflow Only Drain Size A B C D F G H 267/16 267/16 221/2 283/4 1811/16 1915/16 41/4 41/4 41/4 41/4 627/16 765/16 5411/16 6811/16 1 NPT 1 NPT Condensate Drain Location Downflow Horizontal E J E K — — 255/8 263/4 — — 6 53/8 77 (12½-25 Ton) Weights Table W-1 — Accessory Net Weights (Lbs)1, 7 Model No. TCD150D, 180B TCD121,151C, TCD210C Economizer Net Outside Air Damper Manual Motorized 65 32 60 Power Exhaust4 Roof Curb4 Oversized Motor Adder High5 Static Drive Low5 Static Drive 95 205 5 2 2 TCD240B TCD181,211,241C 80 32 75 95 235 5 2 — TCD300B.301C 80 32 75 95 235 N/A N/A 2 TCH150D, 180B, 210C TCH121,151C 50 32 60 — — 5 2 2 TCH240B TCH181,211,241C 65 32 75 — — 5 2 — TCH300B,301C 65 32 75 — — N/A N/A 2 Table W-1 Continued All Zone Sensors 6-23 KW 240/480V2 3 Electric Heaters 27-36 KW 240/480V2 3 54 KW 240/480V2 3 72 KW 240/480V2 3 TCD150D, 180B, 210C TCD121,151,181C 1 28/216 31/27 38/32 — TCD240B TCD211,241C 1 — 33/27 40/32 43/34 Unit Model No. TCD300B,301C 1 — 33/27 40/32 43/34 TCH150D, 180B, 210C TCH121,151,181C 1 28/216 31/27 38/32 — TCH240B TCH211, 241C 1 — 33/27 40/32 43/34 TCH300B, 301C 1 — 33/27 40/32 43/34 Notes: 1. Net weight should be added to unit weight when ordering factory installed accessories. 2. For 600V heaters net weights are same as 480V heaters. 3. To estimate shipping weight add 5 lbs to net weight. 4. Downflow only. 5. Not available on all models (See Fan Performance tables for specific models). 6. 9 - 23 KW Heaters not available for TC*210C. 7. TC*150-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93. This is provided in compliance with ARI certification program. 78 RT-PRC002-EN Weights Table W-2 — Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.) Tons Unit Model No. Maximum Weights (Lbs) Shipping2 Net A Corner Weights (Lbs)1 B C D Center of Gravity (In.) Length Width 12½ TC*150D/TC*151C 1687/1820 1319/1452 446/485 339/360 230/259 303/348 46/45 29/30 15 TC*180B/TC*181C 1866/2361 1498/1902 547/643 358/477 234/333 359/447 42/52 28/35 17½ TC*210C/TC*211C 2022/2380 1654/1921 565/643 425/495 285/341 378/442 46/53 29/35 20 TC*240B/TC*241C 2372/2490 1913/2031 679/697 482/528 312/348 440/458 51/53 34/34 25 TC*300B/ TC*301C 2365/2475 1906/2016 661/695 507/524 320/343 418/454 53/53 33/34 Notes: 1. Corner weights are given for information only. 12½-25 ton models must be supported continuously by a curb or equivalent frame support. 2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly. *Indicates both downflow and horizontal units. RT-PRC002-EN 79 Weights Table W-3 — Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3 Accessory High Efficiency Motors4 Weight 49 36 Unit Model Number TC*150-181 standard size motor TC*210-241 standard size motor TC*150-181 oversize motor 0 TC*210-241 oversize motor TC*300-301 standard size motor Hinged Doors 27 AllTC* units Powered Convenience Outlet 38 AllTC* units Through the Base Electrical 23 AllTC* units Unit Mounted Circuit Breaker 5 AllTC* units except those with 54&72 kW heaters & 208/230V All TC* units with 54&72 kW heaters & 208/230V 10 Unit Mounted Disconnect 5 10 Smoke Detectors Supply/Return AllTC* units except those with 54&72 kW heaters & 208/230V AllTC* units with 54&72 kW heaters & 208/230V 5 AllTC* units Tool-less Hail Guard 38 43 TC*150,151,180,210 TC*181,211,240,241,300,301 Novar 2024 7 AllTC* units Novar 3051 5 AllTC* units Notes: 1. Weights for FIOP accessories not listed are >5 lbs. 2. Net weight should be added to unit weight when ordering factory installed accessories. 3. See Table W-1 for standard factory installed economizer and oversized motors. 4. Standard factory installed motors are already included in unit net and shipping weights. Values shown for high efficiency motors are in addition to the standard motor weight. 80 RT-PRC002-EN Mechanical Specifications General The units shall be dedicated downflow or horizontal airflow.The operating range shall be between 115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-22, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/CAN/CSA No. 236-M90 for Heat Pumps. Canadian units shall be CSA Certified. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit’s surface shall be tested 500 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handels and no more thatn three screws to remove. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch, 1 pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material.The downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8 inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up.The base of the unit shall have provisions for forklift and crane lifting. RT-PRC002-EN UnitTop The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage. Filters Two inch standard filters shall be factory supplied on all units. Optional two inch pleated media filters shall be available. Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models shall have crankcase heaters, low and high pressure controls as standard. Refrigerant Circuits Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. Evaporator and Condenser Coils Internally finned, 3/8" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 200 psig and pressure tested to 450 psig. All dual compressor units shall have intermingled evaporator coils. Sloped condensate drain pans are standard. Patent-pending 1+1+1 condenser coil, permanently gapped for easy cleaning is available. corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative pressure gas valve shall be used that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger 45 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NOx emissions.The 12½-25 tons shall have two stage heating. Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position.The fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection. Indoor Fan Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an adjustable idler-arm assembly for quick-adjustment of fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Gas Heating Section The heating section shall have a drum and tube heat exchanger design using 81 Mechanical Specifications Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be provided for all 24 volt control functions.The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures.The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. Defrost Controls Adaptive demand defrost shall be provided to permit defrost wherever coil icing conditions begin to significantly reduce unit capacity. Factory Installed Options Black Epoxy Coated Pre-Coated Coils The black epoxy coils have a thermoset vinyl coating that is bonded to the aluminum fin stock prior to the finstamping process.The pre-coated coils are an economical option for protection in mildly corrosive environments. Dehumidification Option The dehumidification (hot gas reheat) option shall provide increased dehumidification.The option shall consist of a hot-gas reheat coil located on the leaving air side of the evaporator coil prepiped and circuited. Low pressure switch(es) and thermostatic expansion valve(s) TXV are standard. Frostat™, ReliaTel options module, and 2”pleated filters are required but not standard.They must be ordered and configured separately. 82 Hinged Access Doors Sheet metal hinges are available on the Filter/Evaporator Access Door and the Compressor/Control Access Door.This option is available on all downflow models. High Efficiency Motors This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models. High Pressure Cutout This option is offered for units that do not have High Pressure cutout as standard. Powered or Unpowered Convenience Outlet This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. When the convenience outlet is powered, a service receptacle disconnect will be available.The convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker.This option can only be ordered when theThrough the Base Electrical with either the Disconnect Switch, or Circuit Breaker, option is ordered.This option is available on all downflow models. Supply and/or Return Air Smoke Detector With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required.This option is available on all downflow models. Through the Base Electrical with Circuit Breaker This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections.The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block.The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA.This option is available on all downflow models. Through the Base Electrical With Disconnect Switch Three-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block.The switch will be UL/CSA agency recognized. Note:The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection.This option is available on all downflow models. Through the Base Utilities Access An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch. Two-Inch Pleated Filters Two inch pleated media filters shall be available on all models. RT-PRC002-EN Mechanical Specifications Factory or Field Installed Options Clogged Filter/Fan Failure Switch A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These indications will be registered with either a zone sensor with status indication lights or an Integrated Comfort™ System. Differential Pressure Switches These options allow for individual fan failure and dirty filter indication.The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor.The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation. Discharge Air Sensing Kit This kit provides true discharge air sensing in heating models.This sensor is a status indicator readable through Tracer™orTracker™.The kit is functional only with the ReliaTel Options Module. Economizer - Downflow The assembly includes fully modulating 0-100 percent motor and dampers, barometric relief, minimum position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator.The barometric relief damper shall be standard with the downflow economizer and shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment “off” cycle. Solid state enthalpy and differential enthalpy control shall be field-installed RT-PRC002-EN Electric Heaters Electric heat modules shall be available for installation within the basic unit. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally delta connected for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each heater package shall have automatically reset high limit control operating through heating element contactors. All heaters shall be individually fused from the factory, where required, and shall meet all NEC and CEC requirements when properly installed. Power assemblies shall provide single-point connection. Electric heat modules shall be UL listed or CSA certified. If ordering theThrough the Base Electrical option with an Electric Heater, the heater must be factory installed. Reference or Comparative Enthalpy Reference Enthalpy is used to measure and communicate outdoor humidity.The unit receives and uses this information to provide improved comfort cooling while using the economizer. Comparative Enthalpy measures and communicates humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or Comparative Enthalpy option shall be available when a factory or field installed Downflow Economizer is ordered.This option is available on all downflow models. Frostat This option is to be utilized as a safety device. The Frostat opens when temperatures on the evaporator coil fall below 10°F. The temperature will need to rise to 50°F before closing.This option should be utilized in low airflow or high outside air applications. Trane Communication Interface This factory or field-installed option shall be provided to interface ReliaTel™ controlled units with theTrane Integrated ComfortTM systems. Tool-less Hail Guards Tool-less, hail protection quality coil guards are available for condenser coil protection. LonTalk® Communications Interface The LonTalk communications interface, when installed in a Voyager unit, allows the unit to communicate as aTracer™LCIV device or directly with generic LonTalk Network Building Automation System Controls. Oversized Motors Oversized motors shall be available for high static applications. 83 Mechanical Specifications Field Installed Options CO2 Sensing The CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements. Digital Display Zone Sensor The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors.This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC).This sensor should be utilized with ReliaTel™ controls. Dual Thermistor Remote Zone Sensor This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. Roof Curb - Downflow The roof curb shall be designed to mate with the downflow unit and provide support and a water tight installation when installed properly.The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips. Economizer - Horizontal The horizontal economizer shall contain the same features as the downflow economizer with the exception of barometric relief. Remote Potentiometer The minimum position setting of the economizer shall be adjusted with this accessory. Manual Outside Air Damper The rain hood and screen shall provide up to 25 percent outside air. Ventilation Override Accessory With the Ventilation Override Accessory installed, the unit can be set to transition up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust.The transition occurs when a binary input on the RTOM is closed (shorted).This would typically be a hard wired relay output from a smoke detector or fire control panel. Motorized Outside Air Dampers Manually set outdoor air dampers shall provide up to 50 percent outside air. Once set, outdoor air dampers shall open to set position when indoor fan starts.The damper shall close to the full closed position when indoor fan shuts down. Zone Sensors This option shall be provided to interface with the Micro equipped Voyagers and shall be available in either manual, automatic, programmable with night setback, with system malfunction lights or remote sensor options. High Static Drive The high static drive option shall allow the standard motor on the 12½ and 20 ton units to operate with improved external static capabilities. 84 Powered Exhaust The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better building pressurization. RT-PRC002-EN RT-PRC002-EN 85 86 RT-PRC002-EN RT-PRC002-EN 87 Trane A business of American Standard Companies www.trane.com For more information contact your local dealer (distributor), local district office, or e-mail us at comfort@trane.com Literature Order Number RT-PRC002-EN File Number PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-10-04 Supersedes PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-09-04 Stocking Location 09-04 Webb/Mason 10-04 Electronic Only Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Create Date : 2004:09:07 19:40:58Z Modify Date : 2004:10:15 14:19:09-05:00 Subject : Packaged Cooling with Electric Heat Rooftop Units Voyager™ 12-25 Tons Keywords : RT-PRC002-EN, (09/04), Packaged, Cooling, with, Electric, Heat, Rooftop, Units, Voyager™, 12-25, Tons Page Count : 88 Creation Date : 2004:09:07 19:40:58Z Mod Date : 2004:10:15 14:19:09-05:00 Producer : Acrobat Distiller 5.0.5 (Windows) Author : Global Unitary Systems - Clarksville Metadata Date : 2004:10:15 14:19:09-05:00 Title : RT-PRC002-EN (10/04) Packaged Cooling with Electric Heat Rooftop Units Voyager™ 12-25 Tons Description : Packaged Cooling with Electric Heat Rooftop Units Voyager™ 12-25 Tons Creator : Global Unitary Systems - Clarksville Page Mode : UseOutlines Page Layout : OneColumnEXIF Metadata provided by EXIF.tools