Packaged Cooling with
Electric Heat Rooftop Units
Voyager™
12½ - 25 Tons - 60 Hz

October 2004

RT-PRC002-EN

Introduction

Packaged Rooftop
Air Conditioners
Through the years,Trane has designed
and developed the most complete line of
Packaged Rooftop products available in
the market today.Trane was the first to
introduce the Micro—microelectronic unit
controls—and has continued to improve
and revolutionalize this design concept.
The ReliaTel control platform offers the
same great features and functionality as
the original Micro, with additional benefits
for greater application flexibility.
Voyager continues to provide the highest
standards in quality and reliability,
comfort, ease of service, and the
performance of Trane light commercial
products.

© 2004 American Standard Inc. All rights reserved

Trane customers demand products that
provide exceptional reliability, meet
stringent performance requirements, and
are competitively priced. Trane delivers
with Voyager.
Voyager features cutting edge
technologies: reliable compressors,Trane
engineered ReliaTel controls, computeraided run testing, and Integrated
Comfort™ Systems. So, whether you’re
the contractor, the engineer, or the owner
you can be certain Voyager Products are
built to meet your needs.
It’s HardTo Stop ATrane.®

RT-PRC002-EN

Contents

Introduction

2

Features and Benefits

4

Application Considerations

9
10

Selection Procedure

12
13

Model Number Description

General Data

Controls

17
17
31
47
49

Electric Power

50

Dimension and Weights

70

Mechanical Specifications

81

Performance Data
Cooling Performance
Fan Performance
Heat Performance

RT-PRC002-EN

3

Features and
Benefits

Factory Installed Options
• Black Epoxy Pre-Coated Coils
• Dehumidification Option
• High Efficiency Motors
• High Pressure Cutout
• Hinged Access Doors
• Novar Unit Controls
• Novar Return Air Sensor
• Powered or Unpowered Convenience
Outlet
• Supply and/or Return Air Smoke
Detector
• Thermal Expansion Valve/Face-Split
Evaporator Coil Option
• Through the Base Electrical with Circuit
Breaker
• Through the Base Electrical With
Disconnect Switch
• Through the Base Utilities Access
• Two-Inch Pleated Filters

4

Factory or Field Installed Options
• Clogged Filter/Fan Failure Switch
• Differential Pressure Switches
• Discharge Air Sensing Kit
• Downflow – Economizer
• Electric Heaters
• Frostat
• LonTalk® Communications Interface
• Oversized Motors
• Reference or Comparative Enthalpy
• Tool-less Hail Guards
• Trane Communications Interface (TCI)
Field Installed Options
• CO2 Sensing
• Digital Display Zone Sensor
• DualThermistor Remote Zone Sensor
• Low Static Drive
• High Static Drive
• Manual Outside Air Damper
• Motorized Outside Air Dampers
• Powered Exhaust
• Downflow – Roof Curb
• Horizontal – Economizer
• Remote Potentiometer
• Ventilation Override Accessory
• Zone Sensors

RT-PRC002-EN

Features and
Benefits

Easy to Install, Service and
Maintain

Quality and Reliability are enhanced
through ReliaTel control and logic:

Because today’s owners are very costconscious when it comes to service and
maintenance, the Trane Voyager was
designed with direct input from service
contractors.This valuable information
helped to design a product that would get
the serviceman off the job quicker and
save the owner money. Voyager does
this by offering:

—prevents the unit from short cycling,
considerably improving
compressor life.

Quality and Reliability
ReliaTel™ Controls (LCI-R)

—ensures that the compressor will run
for a specific amount of time which
allows oil to return for better
lubrication, enhancing the reliability of
the compressor.
Voyager with ReliaTel reduces the
number of components required to
operate the unit, thereby reducing
possibilities for component failure.
ReliaTel Makes Installing and
Servicing Easy
ReliaTel eliminates the need for field
installed anti-shortcycle timer and time
delay relays. ReliaTel controls provide
these functions as an integral part of the
unit.The contractor no longer has to
purchase these controls as options and
pay to install them.

ReliaTel controls provide unit control for
heating, cooling and ventilating utilizing
input from sensors that measure outdoor
and indoor temperature.

The wiring of the low voltage connections
to the unit and the zone sensors is as
easy as 1-1, 2-2, and 3-3.This simplified
system makes wiring easier for the
installer.

ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run
the Voyager unit through its paces.
Simply place a jumper betweenTest 1
andTest 2 terminals on the Low Voltage
Terminal Board and the unit will walk
through its operational steps
automatically.
—The unit automatically returns
control to the zone sensor after
stepping through the test mode a
single time, even if the jumper is
left on the unit.
As long as the unit has power and the
“system on” LED is lit, ReliaTel is
operational.The light indicates that the
controls are functioning properly.
ReliaTel features expanded diagnostic
capabilities when utilized withTrane
Integrated Comfort™ Systems.
Some zone sensor options have central
control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).
Other ReliaTel Benefits
The ReliaTel built-in anti-shortcycle timer,
time delay relay and minimum “on” time
control functions are factory tested to
assure proper operation.
ReliaTel softens electrical “spikes” by
staging on fans, compressors and
heaters.

ReliaTel™

Intelligent Fallback is a benefit to the
building occupant. If a component goes
astray, the unit will continue to operate at
predetermined temperature setpoint.
Intelligent Anticipation is a standard
ReliaTel feature. It functions continuously
as ReliaTel and zone sensor(s) work
together in harmony to provide much
tighter comfort control than conventional
electro-mechanical thermostats.
The same ReliaTel Board fits all Voyager
Packaged Gas/Electrics, Cooling with
Electric Heat, and Heat Pump models.
This provides standardization of parts for
contractors. Less money is tied up in
inventory with ReliaTel.

RT-PRC002-EN

5

Features and
Benefits

Outstanding Standard and
Optional Components
Black Epoxy Pre-Coated Coils
The pre-coated coils are an economical
option for protection in mildly corrosive
environments.

Condenser Coil
Voyager boasts a patent-pending 1+1+1
condenser coil, permanently gapped for
easy cleaning.

Hinged Access Doors
These doors permit easy access to the
filter, fan/heat, and compressor/control
sections. They reduce the potential roof
damage from screws or sharp access
door corners.

Cabinet Integrity
For added water integrity, Voyager has a
raised 11/8" lip around the supply and
return of the downflow units to prevent
water from blowing into the ductwork.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available to achieve active fan failure
indication and/or clogged filter indication.
CO2 Sensing
The CO2 sensor has the ability to monitor
space occupancy levels within the
building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air.
As the CO2 levels increase, the outside air
damper modulates to meet the CO2
space ventilation requirements.The CO2
sensor kit is available as a field installed
accessory.
Colored And Numbered Wiring
Save time and money tracing wires and
diagnosing the unit.
Compressors
Voyager contains the best compressor
technology available to achieve the
highest possible performance. Dual
compressors are outstanding for
humidity control, light load cooling
conditions and system back-up
applications. Dual compressors are
available on all models.
Refrigerant Circuits
All Voyager 12½-25 ton units shall have
crankcase heaters, low and high pressure
controls as standard.

6

High Static Drive Accessory
Available on many models, this high
static drive accessory extends the
capability of the standard motor. Avoid
expensive motors and operating costs by
installing this optimized sheave
accessory.

Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors. This sensor
should be utilized with ReliaTel™ controls.
Discharge Air Sensing Kit
Provides true discharge air sensing in
heating models. The kit is functional only
with the ReliaTel Options Module.
Downflow And Horizontal Economizers
The economizers come with three control
options — dry bulb is standard, enthalpy
and differential enthalpy are optional.
Dual Thermistor Remote Zone Sensor
This sensor will reduce the total number
of remote sensors to obtain space
temperature averaging. This sensor
should be utilized with ReliaTel controls.

LonTalk® Communications Interface
The LonTalk communications interface
allows the unit to communicate as a
Tracer™LCI-V device or directly with
generic LonTalk Network Building
Automation System Controls.
Power Exhaust Option
This option is available on downflow units
and provides exhaust of the return air,
when using a downflow economizer, to
maintain proper building pressurization.
Great for relieving most building
overpressurization problems.
Quick-Access Panels
Remove three or fewer screws for
access to the standardized internal
components and wiring.
Quick-Adjust Idler Arm
With the Quick-Adjust Idler Arm, the belt
and sheaves can be quickly adjusted
without moving the mounted fan motor.
The result is a major savings in time and
money.

Factory Built Roof Curbs
Available for downflow units. Only two
roof curbs for the entire Voyager line
simplifies curb selection.
Fresh Air
0 - 25% manual or 0 - 50% motorized
outside air hoods are available.

RT-PRC002-EN

Features and
Benefits

Reference or Comparative Enthalpy
Measures and communicates humidity
while maximizing comfort control.
Sloped Drain Pans
Standard on every unit.
Standardized Components
Components are placed in the same
location on all Voyager units. Familiarize
yourself with one Voyager and you are
familiar with every Voyager.
Due to standardized components
throughout the Voyager line, contractors/
owners can stock fewer parts.
Supply and/or Return Air Smoke
Detector
With this option installed, if smoke is
detected, all unit
operation will be shut
down. Reset will be
manual at the unit.
Return Air Smoke
Detectors require
minimum allowable
airflow when used
with certain models.
Tool-less Hail Guards
Tool-less, hail
protection quality coil
guards shall be either
factory or field-installed for condenser
coil protection.This option protects the
condenser coil from vandalism and/or
hail damage.

VariTrac
When Trane’s changeover VAV System
for light commercial applications is
coupled with Voyager, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.

Actual shipping tests were performed to
determine packaging requirements. Units
were test shipped around the country to
determine the best packaging. Factory
shake and drop tests were used as part
of the package design process to help
assure that the unit arrives at the job site
in top condition.

Ventilation Override Accessory
With the Ventilation Override Accessory
installed, the unit can be set to transition
to up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust.The
transition occurs when a binary input on
the RTOM is closed (shorted).This would
typically be a hard wired relay output
from a smoke detector or fire control
panel.The ventilation override kit is
available as a field installed accessory.

Rigging tests include lifting a unit into the
air and letting it drop one foot, assuring
that the lifting lugs and rails hold up under
stress.

Zone Sensors
Available in programmable, automatic
and manual styles.

Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorousTrane
requirements.

Rigorous Testing
The fan and idler arm assembly designs
have been tested to over 300,000 cycles
each. Our combined cycle testing is now
over 7,000,000 cycles.
All of Voyager’s designs were rigorously
rain tested at the factory to ensure water
integrity.

We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
All parts are inspected at the point of final
assembly. Sub-standard parts are
identified and rejected immediately.

Voyager units incorporate either a one
piece top or theTrane-Tite-Top (T3). Each
part of the top (either two or three pieces)
overlaps in such a way that water cannot
leak into the unit.These overlapped edges
are gasketed and sealed to ensure
superior water integrity.

VariTrac™

Trane Communication Interface (TCI)
Available factory or field installed.This
module when applied with the ReliaTel™
easily interfaces with Trane’s Integrated
ComfortTM System.

RT-PRC002-EN

7

Features and
Benefits

Easy to Install and Service
Conversionless Units
The dedicated design units (either
downflow or horizontal) require no panel
removal or alteration time to convert in
the field — a major cost savings during
installation.
Horizontal units come complete with duct
flanges so the contractor doesn’t have to
field fabricate them.These duct flanges
are a time and cost saver.

Powered or Unpowered Convenience
Outlet
This option is a GFCI, 120v/15amp, 2 plug,
convenience outlet, either powered or
unpowered.This option can only be
ordered when theThrough the Base
Electrical with either the Disconnect
Switch, or Circuit Breaker, option is
ordered.This option is available on all
downflow models.

Factory Installed Options
A wide variety of Factory Installed
Options (FIOPs) are available.

Added Efficiency
Airflow
Airflow is outstanding.The Voyager can
replace an older machine with old
ductwork and, in many cases, improve
the comfort through better air
distribution.
High Efficiency Motors
This option is available with efficiency
ratings from 86.5 up to 91.0. It is not
available for all models.

Easy Access Low Voltage Terminal Board
Voyager’s Low Voltage Terminal Board is
external to the electrical control cabinet. It
is extremely easy to locate and attach the
thermostat wire.This is another cost and
time saving installation feature.

U-shaped Airflow
U-shaped airflow allows for improved
static capabilities.
Low Ambient Cooling
Cooling capabilities down to 0°F as
standard.
Oversized Motors
Factory or field installed oversized
motors available for high static
applications.
Single Point Power
A single electrical connection powers the
unit.

Low Voltage Connections
The wiring of the low voltage connections
to the unit and the zone sensors is as
simple as 1-1, 2-2, and 3-3.This simplified
system makes it easy for the installer to
wire.

Single Side Service
Single side service is standard on all
units.
Through the Base Electrical with Circuit
Breaker
This option is a factory installed thermal
magnetic, molded case, HACR Circuit
Breaker with provisions for through the
base electrical connections. This option is
available on all downflow models.
Through the Base Electrical with
Disconnect Switch
Factory installed 3-pole, molded case,
disconnect switch with provisions for
through the base electrical connections
are available. This option is available on
all downflow models.

Electric Heaters
Electric heat modules are available within
the basic unit. If ordering theThrough the
Base Electrical option with an Electrical
Heater, the heater must be factory
installed.

8

One of our Finest Assets:
Trane Sales Representatives are a
Support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and much more
Voyager has the features and benefits
that make it first class in the light
commercial rooftop market. Designed
with input from field contractors and
engineers, its U-shaped airflow
performance is outstanding.

Through the Base Utilities Access
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
installation of liquid-tight conduit and an
external field installed disconnect switch.
RT-PRC002-EN

Application
Considerations

Application of this product should be
within the cataloged airflow and cooling
considerations.
Low Ambient Cooling
This Voyager line features, as standard,
low ambient cooling down to 0°F. The
following options need to be included/
considered when low ambient
applications are required: continuous fan
operation, crankcase heaters, thermal
expansion valves, frostat. Contact your
local Trane Representative for more
assistance with low ambient cooling
applications.
Barometric Relief
This product line offers an optional
barometric relief damper included in the
downflow economizer accessory.This
accessory consists of gravity dampers
which open with increased pressure. As
the building air pressure increases, the
pressure in the unit return air section
also increases, opening the dampers and
relieving the conditioned space.

Power Exhaust Accessory
The power exhaust accessory is available
on all 12½-25 ton downflow units.This
accessory can be field installed and will
assist in relieving building pressurization.
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency. Actual
clearances which appear inadequate
should be reviewed with the localTrane
sales personnel.
Unit Pitch
These units have sloped condensate
drain pans. Units must be installed level,
any unit slope must be toward access
side of unit.

NOTE:THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER DURING
ECONOMIZING OPERATION IS SYSTEM
RELATED.
PRESSURE DROP OF THE RETURN AIR
SYSTEM SHOULD BE CONSIDEREDTO
CONTROL BUILDING PRESSURIZATION.

RT-PRC002-EN

9

Selection
Procedures

Cooling Capacity
Step 1
Calculate the building’s total and sensible
cooling loads at design conditions. Use
theTrane calculation methods or any
other standard accepted method.
Factors used in unit selection:
A
Total Cooling Load: 180 MBh
B
Sensible Cooling Load: 129 MBh
C
Airflow: 6000 cfm
D
Electrical Characteristics: 460/60/3
E
Summer Design Conditions: Entering
Evaporator Coil: 80 DB, 67 WB Outdoor
Ambient: 95 DB
F
External Static Pressure: 0.49 in. wg
G
Rooftop - downflow configuration
H
Accessories
• Roof curb
• Economizer
• Electric Heat
I
Heating
• Capacity 115 MBh
• 460 volt/3 phase Electric Heat —at 6000
cfm
Step 2
As a starting point, a rough determination
must be made of the size of the unit.The
final selection will be made after
examining the performance at the given
conditions. Divide the total cooling load by
nominal BTUH per ton (12 MBh per ton);
then round up to the nearest unit size.
180 MBh / 12 MBh = 15.0Tons
Step 3
Table PD - 2 shows that a TCD180B4 has a
gross cooling capacity of 184 MBh and
130 MBh sensible capacity at 6000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.

To Find Capacity at Intermediate
Conditions Not in the Table
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
Step 4
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount of
heat that the fan motor generates is
dependent on the effort by the motor cfm and static pressure.To determine the
total unit static pressure you add the
external static pressure to the additional
static related by the added features:
External Static (duct system)
0.49 wg
Standard Filter 1 in.
from Table PD-35

0.10 wg

Economizer

0.04 wg

(100% Return Air) from Table PD-35
Electric Heater Size 36 kw 0.07 wg
from Table PD-35

Step 5
If the performance will not meet the
required load of the building -total or
sensible cooling load, try a selection at
the next higher size unit.

Heating Capacity
Step 1
Calculate the building heating load using
theTrane calculation form or other
standard accepted method.
Step 2
Size the system heating capacity to
match the calculated building heating
load.The following are building heating
requirements:
A
Total heating load of 115.0 MBH
B
6000 cfm
C
460 volt/3 phase Power Supply
The electric heat accessory capacities are
listed inTable PD-36. From the table, a 36
kw heater will deliver 122.94 MBH at 480
volts. In order to determine capacity at
460 volts, the heater voltage correction
factor fromTable PD-37 must be used.
Therefore, 122.94 MBH x .94 (voltage
correction factor) = 115.6 MBH.

Air Delivery Selection
Total Static Pressure

0.60 wg

Note: The Evaporator Fan Performance
Table PD-18 has already accounted for
the pressure drop for standard filters and
wet coils (see note belowTable PD-18).
Therefore, the actual total static pressure
is 0.60 -0.10 (from Table PD-35) = 0.50 wg.
With 6000 cfm and 0.50 wg.
Table PD-18 shows 2.56 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
3.15 x bhp = MBH.
3.15 x 2.56 = 8.06 MBH.

External static pressure drop through the
air distribution system has been
calculated to be 0.50 inches of water.
From Table PD-35 static pressure drop
through the economizer is 0.04 and the
36 kw heater is 0.07 inches of water (0.49
+ 0.04 + 0.07). Enter Table PD-18 for a
TCD180B4 at 6000 cfm and 0.50 static
pressure. The standard motor at 777 rpm
will give the desired airflow at a rated bhp
of 2.71.

Now subtract the fan motor heat from
the gross cooling capacity of the unit:
NetTotal Cooling Capacity
= 184 MBH - 8.06 = 175.9 MBH.
Net Sensible Cooling Capacity
= 130 MBH - 8.06 = 121.9 MBH.

10

RT-PRC002-EN

Selection
Procedure

Dehumidification Selection
Determine normal unit cooling and
heating capacities as previously
described in the selection procedures on
prior page.
Typical 20 ton TFD241C
6400 cfmTotal Supply airflow
2560 cfm Outside Air (40%)
3840 cfm Return Air
0.41” External Static Pressure
OA Conditions
Part load day and raining
68°F db
67°F wb
66.5 dp
95% RH
RA’ conditions
75°F db
63°F wb
52% RH
55.9 dp
Step 1: Determine the mixed/
entering air condition (MA’)
MA’ = (% outside air*outside air dry-bulb
temperature) + (% return air*return air
dry-bulb temperature)
MA’ = (0.40*68°F) + (0.60*75°F)
MA’ = 72.20°F db
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
MA’
72.2°F db
64.7°F wb
Step 2: Determine static pressure
drop add for reheat
Table PD-35 shows a static pressure drop
of 0.35” for the reheat coil and an
additional .04 for the mandatory 2”
pleated filters required when ordering the
dehumidification option.Total static
pressure =
1.0+0.035+0.04=1.075
(≅1.1 for manual calculations)
Do not forget to also add any additional
static from other accessories.
Table PD-29 (airflow table for 20 ton
dehumidification units) indicates that a
standard motor and drive is needed for
this airflow and static pressure range.
RT-PRC002-EN

OA

68°F DB,
67°F WB

RA'

75°F DB,
52% RH

MA'

72.2°F DB
65°F WB

SA'

47°F DB

SA

73°F DB

OA
MA'
RA'
SA'

REHEAT

SA

Chart C-1

Step 3a: Determine leaving
evaporator temperature SA’
Leaving Unit Temperature = SA’
Utilizing the manual selection method as
previously described and the formula
∆Temp =

cooling capacity in Bth
(cfm)(1.085)

or using the TOPSS™ program
determine the leaving evaporator
temperature (temperature without the
addition of fan heat).
517.74 db
51.03 wb
Step 3b: Determine leaving unit
temperature in standard cooling
mode
Find the leaving unit temperature
including fan heat as discussed in prior
selection procedures and using the
temperature formula from Step 3a or
refer to yourTOPSS selection.
53.6 db
51 wb
84% RH
49% dp
Step 4: Determine reheat
temperature rise
Using the leaving evaporator temp, go to
PD-39 and find the reheat temperature
rise for that particular cfm: 17.55°F db

Step 5: Determine leaving unit
temperature with reheat active (SA)
Reheat temperature (obtained in step 3)
+ SA’ = SA
17.55°F db + 53.6°F = 71.2°F db
SA’=71.2°F
51 wb
20.8 RH
29.4 dp
Consider Chart C-1. If the space relative
humidity is equal to or above the space
relative humidity setpoint, the
Dehumidification option will:
• Energize compressor or both
compressors (2 stage compressor units).
• Hot gas reheat valve is energized and
hot gas is diverted to the reheat coil.
• Dehumidification/reheat is terminated
when space humidity is reduced to 5%
below relative humidity setpoint.
At MA’, air enters the RTU.The RTU filters,
cools, and dehumidifies the air as it
moves through the evaporator coil. Air
leaves the evaporator coil saturated at
the preset dew point condition (SA’) and
is reheated by the hot gas reheat coil to
deliver 71°F (SA) supply air to the space.

Note: Reheat temperature rise is based
on supply airflow and leaving
evaporator coil temperature.
11

Model
Number
Description

Packaged Cooling with Electric Heat Unit Typical Model Nomenclature
T

C

D

1

5

0

C

3

0

0

A

A

1

2

3

4

5

6

7

8

9

10

11

12

Digits 1, 2 - Product Type
TC = Packaged Cooling, Electric
Heat
TF = With Factory Installed
Options

Digit 7- Major Development Sequence
Digit 8 - Electrical Characteristics

Digit 3 - Airflow Configuration

3 =
4 =
W=
K =

D = Downflow
H = Horizontal

Digit 9, 10 - Factory-Installed Options

Digits 4, 5, 6 - Nominal Gross Cooling
Capacity (MBh)
150
151
180
181
210
211
240
241
300
301

=
=
=
=
=
=
=
=
=
=

12½ Tons Standard Efficiency
12½ Tons High Efficiency
15 Tons Standard Efficiency
15 Tons High Efficiency
17½ Tons Standard Efficiency
17½ Tons High Efficiency
20 Tons Standard Efficiency
20 Tons High Efficiency
25 Tons Standard Efficiency
25 Tons High Efficiency

208-230/60/3
460/60/3
575/60/3
380/60/3

00 =
0A =
0B =
0C =
0F =
0G=
0H =
0J =
0K =
0L =
0M =
0N=
0P =
0R =

No Factory-installed Options
Factory-installed Economizer
Oversized Motor
Downflow Economizer and
Oversized Motor
Trane Communications Interface
(TCI)
Downflow Economizer and TCI
TXV/Face-Split Evaporator
Oversized Motor and TXV/Face-Split
Evaporator
Downflow Economizer, Oversized
Motor, and TXV/Face-Split Evaporator
Downflow Economizer with TXV/FaceSplit Evaporator
Reheat Coil
Downflow Economizer and Reheat
Coil
Oversized Motor and Reheat Coil
Downflow Economizer, Oversized
Motor and Reheat Coil

Digit 11- Minor Design Sequence
Digit 12- Service Digit

12

RT-PRC002-EN

General
Data

(12½, 15 Ton)
Standard Efficiency

Table GD - 1— General Data

Cooling Performance1
Gross Cooling Capacity
EER2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part Load Value3
System Power (KW)
Compressor
No./Type
Sound Rating (BELS)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Indoor Coil —Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan —Type
No. Used
Diameter x Width (in.)
DriveType/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters —Type Furnished6
(No.) Size Recommended (in.)
Downflow
Horizontal
Refrigerant Charge (Lbs of R-22)5

12½Ton Downflow and Horizontal Units
TC*150D3, D4, DW, DK

15Ton Downflow and Horizontal Units
TC*180B3, B4, BW, BK

150,000
9.8
5,000/4,400
142,000
10.5
14.49

182,000
9.9
6,000/5,300
174,000
10.2
17.57

2/Scrolls
9.2
Hi-Performance
.375
24.18
2/16
Hi-Performance
.375
17.5
2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,600
2/.50
1,100
FC Centrifugal
1
15 x 15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway

2/Scrolls
9.2
Hi-Performance
.375
27.12
3/16
Hi-Performance
.375
17.5
2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,200
2/.50
1,100
FC Centrifugal
1
15 x 15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway

(2) 20 x 20 x 2, (4) 20 x 25 x 2
(2) 20 x 20 x 2, (4) 20 x 25 x 2
9.3/9.4/Circuit

(2) 20 x 20 x 2, (4) 20 x 25 x 2
(2) 20 x 20 x 2, (4) 20 x 25 x 2
17.5/9.5/Circuit

Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification
program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filters are also available.
7. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

13

General
Data

(17½, 20, 25 Ton)
Standard Efficiency

Table GD - 2 — General Data
17½Ton
Downflow and Horizontal Units
TC*210C3, C4, CW, CK
Cooling Performance1
Gross Cooling Capacity
210,000
9.8
EER2
Nominal CFM / ARI Rated CFM
7,000/5,800
ARI Net Cooling Capacity
196,000
10.0
Integrated Part Load Value3
System Power (KW)
20.0
Compressor
No./Type
2/Scrolls
Sound Rating (BELS)4
9.4
Outdoor Coil —Type
Hi-Performance
Tube Size (in.) O.D.
.375
Face Area (sq ft)
27.12
Rows/FPI
3/16
Indoor Coil —Type
Hi-Performance
Tube Size (in.)
.375
Face Area (sq ft)
17.50
Rows/FPI
4/15
Refrigerant Control
Short Orifice
Drain Connection No./Size (in.)
1/1.00 NPT
Outdoor Fan —Type
Propeller
No. Used/Diameter (in.)
2/26
DriveType/No. Speeds
Direct/1
CFM
13,400
No. Motors/HP
2/1.0
Motor RPM
1,125
Indoor Fan —Type
FC Centrifugal
No. Used
1
Diameter x Width (in.)
15 x 15
DriveType/No. Speeds
Belt / 1
No. Motors
1
Motor HP (Standard/Oversized)
5.0/7.5
Motor RPM (Standard/Oversized)
3,450/3,470
Motor Frame Size (Standard/Oversized)
145T/184T
Throwaway
Filters —Type Furnished7
(No.) Size Recommended (in.)
Downflow
(2) 20 x 20 x 2, (4) 20 x 25 x 2
Horizontal
(2) 20 x 20 x 2, (4) 20 x 25 x 2
21.0/14.3/Circuit6
Refrigerant Charge (Lbs of R-22)5

20Ton
Downflow and Horizontal Units
TC*240B3, B4, BW, BK

25Ton
Downflow and Horizontal Units
TC*300B3, B4, BW, BK

242,000
9.7
8,000/7,000
232,000
10.0
23.91

290,000
9.7
10,000/8,750
272,000
9.8
28.05

2/Scrolls
9.4
Hi-Performance
.375
35.30
3/16
Hi-Performance
.375
26.00
2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
14,600
2/1.0
1,125
FC Centrifugal
1
18 x 18
Belt / 1
1
5.0/7.5
3,450/3,470
145T/184T
Throwaway

2/Scrolls
9.4
Hi-Performance
.375
36.43
2/16
Hi-Performance
.375
26.00
3/15
Short Orifice
1/1.00 NPT
Propeller
2/28
Direct/1
16,700
2/1.0
1,125
FC Centrifugal
1
18 x 18
Belt / 1
1
7.5/NA
3,470/NA
184T/NA
Throwaway

(4) 20 x 20 x 2, (4) 20 x 25 x 2
(8) 20 x 25 x 2
18.9/21.0/Circuit

(4) 20 x 20 x 2, (4) 20 x 25 x 2
(8) 20 x 25 x 2
17.0/Circuit

Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½ - 20 ton models are certified in accordance with the Unitary Large
Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Refrigerant charge for horizontal models is 21.5/14.5 per circuit.
7. Optional two inch pleated filters are also available.
8. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.

*Indicates both downflow and horizontal units.

14

RT-PRC002-EN

General
Data

(12½, 15 Ton)
High Efficiency

Table GD - 3 — General Data

Cooling Performance1
Gross Cooling Capacity
EER2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part Load Value3
System Power KW
Compressor
No./Type
Sound Rating (BELS)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Indoor Coil —Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan —Type
No. Used
Diameter x Width (in.)
DriveType/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters —Type/Furnished?
(No.) Size Recommended (in.)
Optional Hot Gas Reheat Coil —Type
Tube Size (in.) OD
Face Area (sq. ft.)
Rows/FPI
Refrigerant Charge (Lbs of R-22) 5/Circuit
Standard
Optional Hot Gas Reheat Coil

12½Ton
Downflow and Horizontal
TC*151C3,C4,CW

15Ton
Downflow and Horizontal
TC*181C3,C4, CW

154,000
11.3
5,000/4,400
146,000
11.5
12.92

189,000
11.58
6,000/5,300
180,000
13.3
15.653

2/Scrolls
9.2
Hi-Performance
0.375
27.12
3/16
Hi-Performance
0.375
17.50
3/15
Short Orifice9
1/1.0 NPT
Propeller
2/26
Direct/1
10,400
2/.50
1100
FC Centrifugal
1
15 x 15
BELT/1
1
3.0/5.0
1740/3450
145T/145T
Throwaway/Yes8
(2)20 x 20 x 2
(4)20 x 25 x 2
Hi-Performance
0.375
17.5
1/16

2/Scrolls
9.2
Hi-Performance
0.375
35.30
3/16
Hi-Performance
0.375
26.00
3/15
Short Orifice8
1/1.0 NPT
Propeller
2/26
Direct/1
11,000
2/.50
1100
FC Centrifugal
1
18 x 18
BELT/1
1
3.0/5.0
1740/3450
145T/145T
Throwaway/Yes8
(4) 20 x 20 x 2
(4) 20 x 25 x 2
Hi-Performance
0.375
26
1/16

15.0/13.89
15.3/14.3

25.0/13.08
27.8/11.4

Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification
program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Face area for Indoor Coil on horizontal models is 12.36.
7. Horizontal models have 4 - 20 x 25 x 2 filters.
8. Optional two inch pleated filters are also available for 12½ ton models.
9. TXV/Face-Split Option (Downflow Only) TCD151C3,4,W (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

15

(17½, 20, 25 Ton)

General
Data

High Efficiency

Table GD - 4 — General Data
17½Ton
Downflow and Horizontal
TC*211C3,C4,CW

20Ton
Downflow and Horizontal
TC*241C3,C4,CW

25Ton
Downflow and Horizontal
TC*301C3,C4,CW

220,000
11.0
7,000/6,200
208,000
12.0
18.91

268,0009
10.6
8,000/7,000
250,0009
11.2
23.589

300,00011
10.411
10,000/8,750
278,000
11.011
26.7311

2/Scrolls

2/Scrolls

2/Scrolls

9.4
Hi-Performance
0.375
35.30
3/16
Hi-Performance
0.375
26.00
4/15
Short Orifice9
1/1.0 NPT
Propeller
2/26
Direct/1
13,700
2/1.00
1125
FC Centrifugal
1
18 x 18
BELT/1
1
5.0/7.5
3450/3470
145T/184T
Throwaway
(4/4)20 x 20 x 2/20 x 25 x 26
Hi-Performance
0.375
26
1/16

9.4
Hi-Performance
0.375
3/16
Hi-Performance
0.375
26.00
4/15
Short Orifice11
1/1.0 NPT
Propeller
2/26
Direct/1
13,700
2/1.00
1125
FC Centrifugal
1
18 x 18
BELT/1
1
7.5/NA
3470/NA
184T/NA
Throwaway
(4/4)20 x 20 x 2/20 x 25 x 26
—
—
—
—

21.8/21.89
21.3/21.0

24.5/24.511
—

Cooling Performance1
Gross Cooling Capacity
EER2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part Load Value3
System Power KW
Compressor
No./Type

Sound Rating (BELS)4
9.4
Outdoor Coil —Type
Hi-Performance
Tube Size (in.) O.D.
0.375
Face Area (sq ft)
35.30
Rows/FPI
3/16
Indoor Coil —Type
Hi-Performance
Tube Size (in.)
0.375
Face Area (sq ft)
26.000
Rows/FPI
4/15
Refrigerant Control
Short Orifice
Drain Connection No./Size (in.)
1 /1.0 NPT
Outdoor Fan —Type
Propeller
No. Used/Diameter (in.)
2/26
DriveType/No. Speeds
Direct/1
CFM
12,800
No. Motors/HP
2/1.00
Motor RPM
1125
Indoor Fan —Type
FC Centrifugal
No. Used
1
Diameter x Width (in.)
18 x 18
DriveType/No. Speeds
BELT/1
No. Motors
1
Motor HP (Standard/Oversized)
5.0/7.5
Motor RPM(Standard/Oversized)
3450/3470
Motor Frame Size (Standard/Oversized)
145T/184T
Filters —Type Furnished7
Throwaway
(No.) Size Recommended (in.)
(4/4)20 x 20 x 2/20 x 25 x 26
Optional Hot Gas Reheat Coil —Type
—
Tube Size (in.) OD
—
Face Area
—
Rows/FPI
—
Refrigerant Charge (Lbs of R-22) 5 / Circuit
Standard
25.7/12.510
Optional Hot Gas Reheat Coil
—

Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. 15 - 20 ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI
Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models have 8 - 20 x 25 x 2 filters.
7. Optional two inch pleated filters are also available.
8. TXV/Face-Split Option (Downflow Only) TCD181C3,4,W (EER):11.4; (System Power kW): 15.79; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 26.0/12.0
9. TXV/Face-Split Option (Downflow Only) TCD241C3,4,W (Gross Cooling Capacity):259,000; (ARI Net Cooling Capacity): 244,000; (System Power kW): 23.02;
(Refrigerant Control): Expansion Valve; (Refrigerant Charge): 21.5/22.2
10. TXV/Face-Split Option (Downflow Only) TCD211C3,4,W Refrigerant Charge): 27.0/10.0
11. TXV/Face-Split Option (Downflow Only) TCD301C3,4,W (EER): 10; (Gross Cooling Capacity): 294,000; (ARI Net Cooling Capacity): 272,000; (IPLV): 10.6; System Power kW): 27.2;
Refrigerant Control: Expansion Valve; (Refrigerant Charge): 21.0/23.0

*Indicates both downflow and horizontal units.

16

RT-PRC002-EN

Performance
Data

(12½, 15 Ton)
Standard Efficiency

Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*150D3, D4, DW, DK
AmbientTemperature
85

CFM
Airflow
4500

5000

5500

6000

95

105
115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5
80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6
85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5
90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0
75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6
80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2
85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9
90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0
75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9
80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7
85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0
90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0
75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0
80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5
85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8
90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*180B3, B4, BW, BK
AmbientTemperature
85

CFM
Airflow
5400

6000

6600

7200

95

105
115
Enter.
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 168.0 133.0 188.0 106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0 172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2
80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7
85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0
90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0
75 172.0 140.0 190.0 110.0 199.0 74.3 161.0 134.0 184.0 106.0 195.0 71.7 151.0 129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9
80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9
85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0
90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0
75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1
80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6
85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0
90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0
75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0 109.0 191.0 71.0 142.0 142.0 170.0 103.0 183.0 67.2
80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4
85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0
90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

RT-PRC002-EN

17

Performance
Data

(17½, 20 Ton)
Standard Efficiency

Table PD-3 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase TC*210C3, C4, CW, CK
85

CFM
Airflow
6300

7000

7700

8400

AmbientTemperature
95

105
115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8
80 200.0 200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0 168.0 183.0 147.0 205.0 106.0
85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0 188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0
90 219.0 219.0 220.0 217.0 230.0 164.0 214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0
75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4
80 206.0 206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0 188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0
85 216.0 216.0 220.0 197.0 230.0 144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0
90 224.0 224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0
75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0 126.0 208.0 75.0
80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0
85 220.0 220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0
90 226.0 226.0 226.0 226.0 235.0 176.0 223.0 223.0 222.0 222.0 229.0 179.0 216.0 216.0 216.0 216.0 223.0 184.0 208.0 208.0 208.0 208.0 214.0 186.0
75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5
80 214.0 214.0 221.0 174.0 230.0 120.0 208.0 208.0 214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0
85 222.0 222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0
90 229.0 229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0 220.0 219.0 219.0 225.0 190.0 212.0 212.0 212.0 212.0 216.0 193.0

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-4 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*240B3, B4, BW, BK
AmbientTemperature (F)
85

CFM
Airflow
7200

8000

8800

9600

95

105
115
Enter.
Dry
Entering Wet Bulb (F)
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 223.0 180.0 251.0 143.0 265.0 97.7 209.0 173.0 242.0 137.0 260.0 94.3 195.0 165.0 228.0 130.0 252.0 90.3 180.0 158.0 212.0 135.0 241.0 85.5
80 226.0 214.0 252.0 173.0 267.0 131.0 208.0 208.0 242.0 169.0 261.0 127.0 197.0 197.0 228.0 162.0 253.0 122.0 186.0 186.0 213.0 155.0 242.0 117.0
85 235.0 235.0 253.0 204.0 268.0 158.0 224.0 224.0 242.0 200.0 262.0 156.0 213.0 213.0 229.0 194.0 253.0 153.0 201.0 201.0 214.0 188.0 242.0 149.0
90 248.0 248.0 255.0 234.0 271.0 185.0 239.0 239.0 245.0 232.0 264.0 185.0 228.0 228.0 228.0 228.0 255.0 183.0 217.0 217.0 217.0 217.0 243.0 179.0
75 229.0 190.0 255.0 148.0 267.0 99.4 215.0 183.0 246.0 142.0 262.0 96.1 200.0 175.0 233.0 136.0 254.0 92.2 185.0 168.0 218.0 129.0 244.0 87.1
80 228.0 228.0 256.0 180.0 268.0 134.0 217.0 217.0 246.0 176.0 264.0 131.0 205.0 205.0 233.0 171.0 255.0 127.0 193.0 193.0 218.0 164.0 245.0 121.0
85 243.0 243.0 257.0 212.0 271.0 162.0 233.0 233.0 247.0 210.0 265.0 161.0 222.0 222.0 234.0 206.0 257.0 158.0 210.0 210.0 220.0 199.0 245.0 155.0
90 255.0 255.0 259.0 245.0 273.0 190.0 247.0 247.0 247.0 247.0 267.0 191.0 237.0 237.0 237.0 237.0 258.0 190.0 226.0 226.0 226.0 226.0 247.0 187.0
75 234.0 199.0 257.0 151.0 268.0 101.0 220.0 192.0 249.0 147.0 263.0 97.9 205.0 184.0 237.0 141.0 256.0 93.7 190.0 177.0 222.0 134.0 246.0 88.6
80 236.0 236.0 259.0 185.0 270.0 136.0 224.0 224.0 249.0 183.0 265.0 134.0 212.0 212.0 237.0 178.0 257.0 130.0 200.0 200.0 222.0 172.0 247.0 126.0
85 250.0 250.0 260.0 220.0 273.0 165.0 240.0 240.0 251.0 219.0 267.0 165.0 229.0 229.0 239.0 216.0 259.0 163.0 217.0 217.0 225.0 210.0 248.0 160.0
90 260.0 260.0 263.0 254.0 275.0 194.0 253.0 253.0 253.0 253.0 270.0 196.0 244.0 244.0 244.0 244.0 261.0 196.0 233.0 233.0 233.0 233.0 250.0 194.0
75 238.0 208.0 259.0 154.0 269.0 103.0 224.0 201.0 251.0 151.0 265.0 99.6 209.0 193.0 240.0 146.0 257.0 95.1 194.0 186.0 225.0 139.0 248.0 89.2
80 242.0 242.0 261.0 190.0 271.0 137.0 231.0 231.0 252.0 189.0 266.0 136.0 219.0 219.0 240.0 185.0 259.0 133.0 206.0 206.0 226.0 180.0 249.0 129.0
85 254.0 254.0 263.0 227.0 274.0 167.0 246.0 246.0 254.0 227.0 269.0 168.0 236.0 236.0 243.0 225.0 261.0 167.0 224.0 224.0 229.0 220.0 251.0 165.0
90 264.0 264.0 264.0 264.0 277.0 198.0 258.0 258.0 258.0 258.0 272.0 201.0 249.0 249.0 249.0 249.0 263.0 202.0 239.0 239.0 239.0 239.0 252.0 201.0

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

18

RT-PRC002-EN

Performance
Data

(25 Ton)
Standard Efficiency

Table PD-5— Gross Cooling Capacities (MBH) 25 Ton Three Phase TC*300B3, B4, BW, BK
AmbientTemperature (F)
85

CFM
Airflow

9000

10000

10500

11000

Enter.
Dry
Bulb
61
(F) MBH SHC
75
266 224
80
270 268
85
286 286
90
301 301
75
272 237
80
277 277
85
294 294
90
308 308
75
275 243
80
282 282
85
298 298
90
312 312
75
278 248
80
286 286
85
301 301
90
314 314

67
MBH SHC
299 174
300 215
301 255
304 295
303 180
304 223
306 266
310 309
305 183
306 227
308 272
311 311
306 185
308 231
310 277
314 314

95

73
MBH SHC
319 118
321 161
323 196
326 232
322 120
324 171
327 208
329 239
323 122
325 174
328 216
330 256
324 123
325 160
327 224
330 266

61
MBH SHC
247 215
252 252
272 272
289 289
253 227
262 262
282 282
297 297
256 233
267 267
286 286
301 301
258 239
271 271
289 289
304 304

67
MBH SHC
285 167
285 209
286 250
289 289
290 174
290 219
291 263
297 297
291 177
292 223
294 270
301 301
293 181
294 228
296 276
304 304

105
Entering Wet Bulb (F)
73
61
67
MBH SHC MBH SHC MBH SHC
309 113 228 205 266 172
311 155 237 237 266 200
312 194 256 256 267 242
314 231 275 275 275 275
312 115 234 218 271 165
314 161 246 246 271 211
316 200 266 266 273 257
318 240 284 284 284 284
314 117 236 223 273 188
315 162 250 250 273 216
317 203 270 270 276 264
320 244 288 288 288 288
315 118 239 229 275 172
316 163 254 254 276 221
319 205 274 274 278 271
321 248 291 291 291 291

115

73
MBH SHC
297 108
297 149
298 189
300 229
300 109
301 155
302 197
304 239
301 111
302 157
304 200
306 244
302 113
304 160
305 204
307 249

61
MBH SHC
209 196
221 221
240 240
259 259
214 208
229 229
249 249
268 268
216 214
233 233
253 253
273 273
217 217
237 237
257 257
276 276

67
MBH SHC
244 163
244 190
246 233
259 259
249 156
249 201
253 248
268 268
251 178
251 206
256 255
272 272
253 184
253 212
257 257
276 276

73
MBH SHC
280 99.9
280 142
281 183
282 224
284 102
284 147
285 192
286 235
285 103
286 150
286 196
288 241
286 104
287 153
288 200
289 246

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

19

Performance
Data

(12½ Ton)
High Efficiency

Table PD-6 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*151C3, C4, CW— Standard Refrigeration System
85

CFM
Airflow
4500

5000

5500

6000

95

AmbientTemperature
105

115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8
80 140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6
85 149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0
90 158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0
75 141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7
80 145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5
85 155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0
90 162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0
75 145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6
80 150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1
85 158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0
90 165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0
75 148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6
80 154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2
85 161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0
90 167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

20

RT-PRC002-EN

Performance
Data

(12½ Ton)
High Efficiency

Table PD-7 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase T*D151C3, C4, CW — Dehumidification (Hot Gas Reheat) or TXV Option
85

CFM
Airflow
2500*

3250*

4000*

4500

5000

5500

6000

95

AmbientTemperature
105

115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 123.8 88.0 138.9 73.4 155.2 55.8 118.2 84.4 132.8 70.1 148.6 52.6 112.1 80.7 126.2 66.6 141.5 49.2 105.6 76.8 119.1 62.8 133.8 45.6
80 123.9 100.8 139.0 85.5 155.2 69.8 118.3 97.3 132.9 82.0 148.7 66.4 112.1 93.3 126.3 78.3 141.5 62.8 105.7 89.6 119.2 74.4 133.9 59.0
85 124.0 113.6 139.1 98.3 155.3 82.5 118.5 110.1 133.0 94.7 148.8 79.1 112.5 106.3 126.4 91.0 141.6 75.4 104.3 104.3 119.3 87.1 134.0 71.6
90 126.0 124.6 139.0 110.8 155.4 95.2 120.6 120.6 133.0 107.2 148.8 91.7 115.5 115.5 126.4 103.5 141.7 88.0 110.3 110.3 119.4 99.5 134.1 84.2
75 133.0 99.5 148.7 80.0 165.5 59.1 126.7 95.9 141.9 76.4 158.2 55.7 120.0 91.9 134.7 72.5 150.4 52.2 112.8 87.8 126.9 68.5 142.0 48.5
80 133.1 115.7 148.8 96.0 165.6 76.1 126.9 112.0 142.1 92.4 158.3 72.5 120.2 108.1 134.8 88.6 150.5 68.8 113.2 104.1 127.0 84.5 142.1 64.9
85 132.7 132.7 148.8 111.9 165.7 92.0 128.6 126.0 142.1 108.2 158.4 88.4 122.5 121.6 134.8 104.3 150.6 84.7 116.2 116.2 127.1 100.4 142.3 80.7
90 139.8 139.8 148.9 127.6 165.7 107.7 134.5 134.5 142.2 124.0 158.4 104.1 128.9 128.9 135.0 120.1 150.7 100.5 122.8 122.8 127.5 116.3 142.4 96.5
75 139.3 109.8 155.4 86.2 172.5 61.7 132.6 106.1 148.2 82.5 164.7 58.3 125.4 102.0 140.4 78.6 156.4 54.7 117.8 97.8 132.2 74.5 147.6 50.9
80 139.6 128.9 155.5 105.4 172.6 81.5 133.1 125.4 148.3 101.7 164.8 77.8 126.2 121.5 140.6 97.7 156.5 74.0 119.0 115.2 132.3 93.6 147.7 70.1
85 143.2 143.2 155.5 124.1 172.8 100.5 137.6 137.6 148.3 120.4 165.0 96.8 131.5 131.5 140.7 116.6 156.7 93.0 125.0 125.0 132.4 112.5 147.8 89.0
90 151.0 151.0 156.1 143.3 172.8 119.2 145.3 145.3 149.0 139.6 165.0 115.6 139.0 139.0 141.6 136.1 156.7 111.7 132.4 132.4 134.0 129.4 147.9 107.6
75 142.5 116.0 158.8 90.2 176.0 63.3 135.6 112.2 151.3 86.4 168.0 59.8 128.2 108.3 143.3 82.4 159.5 56.2 120.4 104.1 134.9 78.2 150.4 52.4
80 143.3 137.5 158.8 111.1 176.2 84.8 135.1 135.1 151.4 107.3 168.1 81.1 130.0 127.1 143.5 103.5 159.6 77.3 122.7 122.1 135.0 99.3 150.5 73.3
85 149.0 149.0 159.0 131.9 176.3 105.6 143.1 143.1 151.6 128.2 168.2 101.9 136.7 136.7 143.6 124.2 159.8 98.2 129.9 129.9 135.2 120.1 150.7 94.2
90 157.2 157.2 160.1 153.3 176.4 126.4 151.1 151.1 151.1 151.1 168.3 122.6 144.6 144.6 145.9 142.5 159.7 118.6 137.6 137.6 138.2 137.5 150.8 114.8
75 145.1 121.9 161.6 93.7 179.0 64.7 138.1 118.3 154.0 89.9 170.8 61.2 130.5 114.2 145.8 85.9 162.0 57.3 122.6 110.1 137.1 81.7 152.7 53.3
80 145.6 145.6 161.6 116.5 179.2 87.9 140.4 138.6 154.0 112.8 170.9 84.2 133.1 133.1 145.8 108.8 162.1 80.3 126.2 126.2 137.1 104.5 152.9 76.3
85 154.1 154.1 162.0 139.4 179.3 110.7 147.9 147.9 154.4 135.7 171.0 106.9 141.3 141.3 146.3 131.7 162.2 103.0 134.2 134.2 137.7 127.6 153.1 99.2
90 162.6 162.6 162.5 162.5 179.5 133.2 156.3 156.3 157.1 154.9 171.2 129.5 149.5 149.5 149.4 149.4 162.4 125.5 142.2 142.2 142.2 142.2 153.1 121.5
75 147.5 127.8 164.0 97.2 181.5 66.0 140.3 124.0 156.2 93.3 173.1 62.2 132.6 119.9 147.8 89.3 164.1 58.4 124.6 116.0 138.9 85.1 154.7 54.3
80 150.2 149.4 164.1 121.8 181.7 90.9 143.5 143.5 156.2 117.9 173.2 87.1 136.8 136.8 147.9 114.0 164.3 83.2 129.7 129.7 139.0 109.8 154.8 79.2
85 158.5 158.5 164.6 146.7 181.8 115.5 152.1 152.1 156.8 142.9 173.4 111.8 145.3 145.3 148.6 139.0 164.4 107.8 138.0 138.0 140.0 134.9 154.9 103.7
90 167.4 167.4 167.9 167.1 182.1 139.9 160.8 160.8 160.7 160.7 173.6 136.1 153.8 153.8 153.7 153.7 164.6 132.2 146.3 146.3 146.2 146.2 155.1 128.2
75 149.6 133.5 165.9 100.3 183.7 67.0 142.2 129.6 158.0 96.4 175.1 63.2 134.4 125.6 149.5 92.5 166.0 59.4 126.4 121.7 140.5 88.3 156.4 55.3
80 153.4 153.4 166.1 126.9 183.8 93.6 147.0 147.0 158.1 123.0 175.2 90.0 140.2 140.2 149.6 118.9 166.1 86.1 132.8 132.8 140.6 115.0 156.5 82.0
85 162.5 162.5 166.9 153.7 183.9 120.1 155.9 155.9 159.1 150.0 175.3 116.3 148.8 148.8 148.7 148.7 166.2 112.5 141.3 141.3 142.4 138.6 156.6 108.4
90 171.6 171.6 171.6 171.6 184.3 146.4 164.8 164.8 164.7 164.7 175.7 142.6 157.6 157.6 157.5 157.5 166.5 138.7 149.9 149.9 149.9 149.9 157.0 134.7

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate
airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 4000 CFM
• Electric heaters restricted on applications below 4000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4000 CFM.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

21

Performance
Data

(15 Ton)
High Efficiency

Table PD-8 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*181C3, C4, CW— Standard Refrigeration System
AmbientTemperature
85

CFM
Airflow
5400

6000

6600

7200

Enter.
Dry
Bulb
61
(F) MBH SHC
75
172 144
80
175 169
85
185 185
90
195 195
75
177 153
80
181 180
85
192 192
90
201 201
75
181 162
80
186 186
85
197 197
90
204 204
75
184 170
80
191 191
85
200 200
90
207 207

67
MBH SHC
194 112
195 138
196 164
195 195
197 116
198 144
199 172
200 200
198 123
200 151
202 179
205 202
200 127
202 153
204 185
208 207

95

73
MBH SHC
205 75.2
207 103
209 126
211 149
207 76
209 105
211 129
214 153
208 76.6
210 107
213 131
215 157
209 79.1
211 108
214 134
217 160

61
MBH SHC
159 138
164 162
176 176
188 188
164 147
170 170
183 183
194 194
168 155
177 177
189 189
199 199
168 168
182 182
194 194
203 203

67
MBH SHC
185 107
186 134
186 161
190 184
189 112
189 142
190 171
195 194
191 117
192 148
194 180
199 199
193 121
194 154
194 194
203 203

105
Entering Wet Bulb
73
61
MBH SHC MBH SHC
200 71.9 147 131
202 99.7 153 153
203 124 165 165
204 148 178 178
202 73.2 151 140
204 103 159 159
206 129 173 173
208 155 185 185
204 74.4 152 152
206 105 166 166
208 132 179 179
209 159 191 191
206 76.4 156 156
207 107 171 171
209 136 185 185
211 163 195 195

67
MBH SHC
172 101
173 128
174 156
179 179
176 106
177 136
173 173
185 185
180 111
180 144
183 173
191 191
182 116
183 151
187 181
195 195

115

73
MBH SHC
193 68
194 95.4
195 122
196 147
195 69.3
196 99.4
197 127
199 154
197 70.6
198 102
199 132
201 160
198 71.9
199 105
201 135
203 166

61
MBH SHC
130 130
142 142
155 155
168 168
138 131
148 148
162 162
175 175
142 139
154 154
168 168
181 181
145 145
159 159
174 174
186 186

67
MBH SHC
158 97
158 122
155 155
167 167
162 99.8
162 130
162 162
175 175
165 105
166 137
170 166
181 181
168 110
169 145
174 174
186 186

73
MBH SHC
183 63.4
183 90.5
184 117
184 144
185 64.8
186 94.6
186 124
187 152
187 66.2
188 98.6
189 129
190 160
189 67.4
190 102
191 134
192 167

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

22

RT-PRC002-EN

Performance
Data

(15 Ton)
High Efficiency

Table PD-9 — Gross Cooling Capacities (MBH) 15 Ton Three Phase T*D181C3, C4, CW— Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature
85

CFM
Airflow
3000*

3900*

4800*

5400

6000

6600

7200

95

105
115
Enter.
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 150.0 106.0 168.0 88.9 187.7 68.3 144.0 102.3 161.4 85.3 180.6 64.8 137.5 98.4 154.4 81.6 173.0 61.2 130.8 94.4 147.1 77.8 165.0 57.5
80 150.2 121.0 168.1 103.0 187.8 84.7 144.1 117.3 161.5 99.3 180.7 81.1 137.7 113.4 154.6 95.4 173.1 77.2 131.0 109.3 147.3 91.5 165.1 73.3
85 150.2 135.8 168.2 117.9 187.9 99.5 144.2 132.1 161.7 114.1 180.8 95.8 137.9 128.1 154.8 110.3 173.2 92.0 130.7 122.5 147.5 106.2 165.2 88.0
90 151.8 148.3 168.4 132.7 188.0 114.2 146.3 144.5 161.9 128.9 180.9 110.5 140.5 140.5 155.0 125.0 173.3 106.7 134.9 134.9 147.7 120.9 165.4 102.7
75 161.5 119.8 180.4 96.8 201.0 72.4 154.8 115.8 173.1 93.0 193.0 68.7 147.7 111.8 165.4 89.0 184.6 64.9 140.2 107.5 157.2 84.8 175.7 61.0
80 161.7 138.5 180.6 115.6 201.1 92.3 154.9 134.5 173.3 111.7 193.1 88.5 147.8 130.4 165.6 107.6 184.7 84.5 140.4 126.1 157.4 103.5 175.8 80.4
85 162.6 155.0 180.8 134.3 201.3 110.9 156.3 150.7 173.5 130.3 193.3 107.0 149.8 146.3 165.8 126.3 184.9 103.0 142.9 141.9 157.7 122.0 176.0 98.9
90 168.5 168.5 180.9 152.7 201.5 129.4 162.8 162.8 173.6 148.8 193.5 125.5 156.8 156.8 165.9 144.6 185.1 121.5 150.5 150.5 157.9 140.4 176.2 117.3
75 169.6 132.0 189.0 104.3 210.2 75.6 162.4 127.9 181.2 100.4 201.5 71.8 154.7 123.7 172.8 96.2 192.4 67.9 146.6 119.2 164.1 91.9 182.8 63.9
80 170.0 154.3 189.3 126.8 210.4 98.8 162.9 150.3 181.4 122.7 201.7 94.8 155.4 146.0 173.1 118.6 192.6 90.7 147.5 139.4 164.4 114.3 183.0 86.5
85 173.4 173.4 189.5 149.0 210.6 121.0 166.9 166.9 181.7 145.0 201.9 117.0 160.5 160.5 173.3 140.7 192.8 112.9 153.7 153.7 164.6 136.3 183.3 108.6
90 182.3 182.3 189.9 171.1 210.8 143.1 176.1 176.1 182.2 167.0 202.2 139.1 169.5 169.5 169.3 169.3 193.1 134.9 162.5 162.5 165.7 155.6 183.6 130.6
75 173.7 139.5 193.4 108.9 214.8 77.5 166.2 135.3 185.2 104.9 205.8 73.7 158.3 130.9 176.6 100.7 196.3 69.7 150.0 126.5 167.6 96.4 186.4 65.6
80 174.6 164.4 193.7 133.7 215.0 102.8 164.2 164.2 185.5 129.6 206.0 98.7 159.8 153.0 176.9 125.4 196.5 94.5 152.1 148.0 167.9 121.0 186.6 90.3
85 180.1 180.1 193.9 158.1 215.3 127.3 173.8 173.8 185.8 154.0 206.3 123.2 167.0 167.0 177.2 149.7 196.8 119.0 159.9 159.9 168.2 145.3 186.9 114.7
90 189.8 189.8 189.8 189.8 215.5 151.6 183.3 183.3 183.3 183.3 206.6 147.6 176.4 176.4 179.1 170.7 197.1 143.4 169.1 169.1 170.7 165.6 187.2 139.0
75 177.2 146.6 197.0 113.2 218.7 79.2 169.4 142.4 188.6 109.1 209.4 75.4 161.3 138.0 179.8 104.9 199.6 71.3 152.8 133.5 170.5 100.5 189.4 67.0
80 178.8 171.0 197.4 140.3 218.9 106.5 169.8 169.8 189.0 136.2 209.6 102.4 164.0 161.4 180.1 131.9 199.8 98.2 155.8 155.8 170.9 127.5 189.6 93.9
85 186.4 186.4 197.6 166.9 219.2 133.3 179.8 179.8 189.3 162.7 209.9 129.2 172.8 172.8 180.6 158.4 200.2 125.0 165.3 165.3 171.5 153.9 190.0 120.6
90 196.7 196.7 196.5 196.5 219.4 159.9 189.8 189.8 189.7 189.7 210.2 155.8 182.6 182.6 183.8 180.6 200.5 151.6 174.9 174.9 174.8 174.8 190.2 146.9
75 180.2 153.4 200.2 117.4 221.9 80.8 172.3 149.2 191.5 113.2 212.4 76.8 164.0 144.8 182.5 108.9 202.4 72.6 155.4 140.2 172.9 104.5 191.9 68.2
80 182.9 179.1 200.5 146.6 222.1 110.1 175.6 174.4 191.9 142.5 212.6 105.9 167.6 167.6 182.7 138.0 202.6 101.7 160.2 160.2 173.2 133.4 192.1 97.3
85 192.0 192.0 201.0 175.4 222.5 139.1 185.1 185.1 192.5 171.2 213.0 134.9 177.8 177.8 183.6 166.9 203.0 130.7 170.1 170.1 169.9 169.9 192.5 126.2
90 202.7 202.7 204.3 199.9 222.7 167.8 195.5 195.5 196.3 195.1 213.2 163.5 188.0 188.0 187.9 187.9 203.2 159.2 180.0 180.0 179.9 179.9 192.8 154.7
75 182.8 160.1 202.8 121.3 224.7 82.1 174.8 155.8 194.0 117.1 214.9 78.0 166.4 151.4 184.7 112.8 204.7 73.7 157.7 146.8 175.0 108.4 193.9 69.4
80 186.0 186.0 203.2 152.8 224.9 113.4 179.1 179.1 194.2 148.3 215.2 109.3 171.8 171.8 185.0 143.9 205.0 105.0 164.1 164.1 175.4 139.3 194.3 100.6
85 196.9 196.9 204.0 183.7 225.2 144.5 189.8 189.8 195.4 179.5 215.6 140.5 182.3 182.3 182.1 182.1 205.4 136.2 174.3 174.3 177.1 167.2 194.7 131.7
90 207.9 207.9 207.8 207.8 225.4 175.3 200.6 200.6 200.5 200.5 215.8 171.1 192.8 192.8 192.6 192.6 205.7 166.7 184.5 184.5 184.4 184.4 195.1 162.2

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate
airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 4800 CFM
• Electric heaters restricted on applications below 4800 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4800 CFM.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

23

Performance
Data

(17½ Ton)
High Efficiency

Table PD-10 — Gross Cooling Capacities (MBH)17½ Ton Three Phase TC*211C3, C4, CW — Standard Refrigeration Option
AmbientTemperature
85

CFM
Airflow
6300

7000

7700

8400

95

105
115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2
80 202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0
85 216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0
90 227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0
75 205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0
80 210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0
85 223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0
90 232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0
75 210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7
80 217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0
85 228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0
90 235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0
75 214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2
80 222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0
85 231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0
90 238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

24

RT-PRC002-EN

Performance
Data

(17½ Ton)
High Efficiency

Table PD-11 — Gross Cooling Capacities (MBH)17½ Ton Three Phase T*D211C3, C4, CW— TXV Option
AmbientTemperature
85

CFM
Airflow
3500*

4550*

5600

6300

7000

7700

8400

95

105
115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 178.1 125.2 199.2 102.8 222.1 78.3 170.4 120.6 190.9 98.4 213.1 74.0 162.3 115.7 182.1 93.7 203.6 69.5 153.6 110.7 172.8 88.9 193.6 64.9
80 178.3 143.9 199.4 121.1 222.2 97.7 170.6 139.3 191.1 116.5 213.3 93.4 162.4 134.5 182.3 111.8 203.8 88.8 153.8 129.5 173.1 106.8 193.7 84.0
85 178.6 163.0 199.6 139.7 222.4 116.2 171.0 158.4 191.3 135.0 213.5 111.9 163.0 153.7 182.5 130.2 204.0 107.2 151.7 151.7 173.3 125.2 194.0 102.4
90 181.8 177.2 199.8 158.2 222.6 134.6 175.2 171.7 191.5 153.5 213.7 130.2 168.1 165.8 182.7 148.7 204.2 125.5 160.6 160.1 173.5 143.8 194.2 120.6
75 190.8 142.2 212.7 113.0 236.1 82.3 182.3 137.4 203.5 108.3 226.2 78.0 173.3 132.4 193.9 103.4 215.8 73.4 163.8 127.2 183.7 98.3 204.8 68.6
80 191.2 166.4 213.0 136.6 236.3 106.8 182.8 161.6 203.8 131.8 226.5 102.3 173.9 156.6 194.1 126.9 216.0 97.5 164.7 151.5 184.0 121.8 205.1 92.6
85 193.7 186.8 213.2 160.2 236.6 130.2 186.2 180.5 204.1 155.4 226.8 125.6 178.3 173.9 194.4 150.4 216.3 120.8 169.9 167.2 184.3 145.3 205.3 115.8
90 201.2 201.2 213.6 183.9 236.9 153.5 194.2 194.2 204.7 179.3 227.0 148.9 186.6 186.6 195.2 174.4 216.6 144.0 178.5 178.5 185.2 169.3 205.6 139.0
75 199.5 157.9 221.6 122.1 245.5 85.7 190.5 153.0 212.0 117.4 234.9 81.2 180.9 147.9 201.7 112.4 223.8 76.5 171.0 142.6 190.9 107.3 212.2 71.6
80 200.9 187.5 221.9 150.5 245.8 114.8 192.2 182.6 212.3 145.8 235.3 110.1 179.9 179.9 202.0 140.8 224.1 105.2 173.8 166.9 191.2 135.6 212.5 100.2
85 207.3 204.9 222.5 179.2 246.2 142.9 199.3 198.8 213.0 174.6 235.4 138.1 190.6 190.6 202.7 169.6 224.4 133.3 182.0 182.0 192.0 164.4 212.8 128.2
90 217.4 217.4 224.2 208.4 246.5 171.0 209.5 209.5 214.9 203.9 235.8 166.2 201.4 201.4 201.3 201.3 224.8 161.4 192.6 192.6 195.4 187.3 213.2 156.4
75 203.9 167.7 226.2 127.9 250.3 87.7 194.8 162.9 216.2 123.2 239.2 83.0 185.0 157.7 205.6 118.1 227.8 78.4 174.8 152.4 194.5 112.9 215.8 73.
80 202.9 202.9 226.5 159.5 250.5 119.7 195.2 195.2 216.6 154.8 239.4 114.8 188.9 182.8 206.0 149.7 228.1 110.1 179.6 175.4 194.9 144.5 216.1 105.0
85 214.6 214.6 227.5 191.5 250.9 150.9 206.7 206.7 217.4 186.6 239.8 146.1 198.1 198.1 207.2 181.8 228.5 141.3 189.1 189.1 196.3 176.6 216.5 136.2
90 226.3 226.3 226.2 226.2 251.4 182.3 218.0 218.0 221.1 212.1 240.4 177.4 209.4 209.4 211.9 204.9 228.9 172.4 200.2 200.2 202.0 197.2 217.2 167.6
75 207.8 177.3 229.9 133.4 254.2 89.6 198.5 172.5 219.7 128.6 242.8 84.9 188.5 167.4 208.8 123.5 231.1 80.1 178.2 162.0 197.4 118.3 218.8 75.1
80 212.0 205.1 230.4 168.2 254.5 124.4 203.5 198.3 220.0 163.5 243.1 119.6 194.3 190.9 209.4 158.4 231.4 114.7 184.7 183.5 198.1 153.1 219.2 109.6
85 221.9 221.9 231.8 203.6 254.9 158.8 213.4 213.4 221.6 198.6 243.5 153.8 204.7 204.7 211.2 193.7 231.8 149.0 195.4 195.4 200.2 188.5 219.6 143.9
90 234.1 234.1 236.8 229.0 255.6 193.4 225.4 225.4 227.5 221.6 244.3 188.5 216.5 216.5 217.7 214.0 232.5 183.4 206.9 206.9 207.6 206.7 220.6 178.6
75 211.3 186.8 233.0 138.7 257.4 91.4 201.8 181.9 222.6 133.9 245.7 86.5 191.8 176.7 211.5 128.8 233.8 81.7 181.3 171.3 199.9 123.5 221.3 76.7
80 217.2 212.9 233.7 176.7 257.8 129.0 208.4 206.0 223.3 171.9 246.1 124.1 199.0 198.7 212.3 166.8 234.2 119.3 189.0 189.0 200.8 161.5 221.7 114.1
85 228.2 228.2 235.8 215.3 258.2 166.4 219.5 219.5 225.5 210.3 246.5 161.4 210.4 210.4 210.3 210.3 234.6 156.6 200.8 200.8 200.7 200.7 222.2 151.5
90 241.0 241.0 242.8 238.1 259.2 204.2 231.9 231.9 233.1 230.7 247.7 199.3 222.4 222.4 222.3 222.3 235.7 194.2 212.6 212.6 212.6 212.6 223.5 189.2
75 214.5 195.9 235.7 143.9 260.2 92.9 204.9 191.1 225.0 139.0 248.3 88.0 190.7 190.7 213.7 133.9 236.1 83.2 181.3 181.3 201.9 128.6 223.4 78.2
80 221.9 220.3 236.6 185.0 260.5 133.5 212.1 212.1 225.8 180.0 248.6 128.5 203.1 203.1 214.8 175.0 236.5 123.7 193.4 193.4 203.2 169.7 223.8 118.5
85 233.9 233.9 239.5 226.8 261.0 173.9 224.8 224.8 224.7 224.7 249.2 168.9 215.5 215.5 215.4 215.4 236.9 163.8 205.5 205.5 207.7 200.6 224.4 158.9
90 247.0 247.0 248.0 246.9 262.4 214.8 237.7 237.7 237.6 237.6 250.7 209.8 227.8 227.8 227.8 227.8 238.6 204.7 217.8 217.8 217.7 217.7 226.3 199.7

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 5600 CFM
• Electric heaters restricted on applications below 5600 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 5600 CFM.

RT-PRC002-EN

25

Performance
Data

(20 Ton)
High Efficiency

Table PD-12 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*241C3, C4, CW — Standard Refrigeration Option
AmbientTemperature (F)
85

CFM
Airflow
7200

8000

8800

9600

Enter.
Dry
Bulb
61
(F) MBH SHC
75
246 205
80
250 245
85
263 263
90
274 274
75
253 218
80
257 257
85
270 270
90
280 280
75
258 230
80
264 264
85
276 276
90
285 285
75
262 240
80
270 270
85
280 280
90
288 288

67
MBH SHC
273 158
274 192
275 227
278 262
275 163
277 199
279 236
282 273
278 167
280 204
282 244
286 281
280 169
282 209
284 250
288 288

95

73
MBH SHC
284 105
287 142
290 171
293 201
285 107
289 144
292 174
295 205
287 109
290 155
293 177
297 209
288 110
291 161
295 179
298 212

61
MBH SHC
228 196
232 232
251 251
266 266
234 209
243 243
261 261
274 274
240 221
252 252
268 268
280 280
246 233
260 260
274 274
284 284

67
MBH SHC
263 152
264 190
265 228
268 265
267 159
268 199
270 240
274 274
270 164
271 208
274 250
280 280
273 169
274 215
277 260
284 284

105
Entering Wet Bulb (F)
73
61
67
MBH SHC MBH SHC MBH SHC
280 101 208 186 246 145
283 141 216 216 246 183
285 173 236 236 248 221
288 206 254 254 254 254
282 103 214 199 252 152
285 143 227 227 252 194
288 177 247 247 255 237
291 212 264 264 264 264
284 105 219 211 256 159
287 145 236 236 257 205
290 181 256 256 260 251
293 217 271 271 271 271
285 106 225 223 260 166
288 147 245 245 261 215
291 184 263 263 265 263
294 222 276 276 276 276

115

73
MBH SHC
273 96.5
274 135
275 170
277 205
275 98.3
277 140
278 177
280 214
277 100
279 144
281 182
283 221
278 102
281 147
282 186
285 228

61
MBH SHC
191 176
201 201
219 219
239 239
194 189
210 210
230 230
250 250
199 199
218 218
240 240
258 258
205 205
226 226
248 248
264 264

67
MBH SHC
222 136
223 172
225 211
237 237
228 142
228 184
232 226
248 248
232 149
233 195
238 238
258 258
236 156
237 205
246 246
265 265

73
MBH SHC
261 91.5
261 130
262 168
262 205
266 93.6
266 136
266 177
267 218
269 95.5
269 141
269 185
271 229
271 97.1
271 146
272 193
275 240

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

26

RT-PRC002-EN

Performance
Data

(20 Ton)
High Efficiency

Table PD-13 — Gross Cooling Capacities (MBH) 20 Ton Three Phase T*D241C3, C4, CW— TXV Option
AmbientTemperature (F)
85

CFM
Airflow
4000*

5200*

6400

7200

8000

8800

9600

95

105
115
Enter.
Dry
Entering Wet Bulb (F)
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 208.5 149.1 233.3 122.6 260.1 94.5 199.6 143.8 223.6 117.3 249.8 89.3 190.1 138.1 213.4 111.9 238.6 84.0 180.0 132.3 202.5 105.8 226.9 78.5
80 208.7 171.1 233.4 144.4 260.2 117.1 199.9 165.6 223.8 139.1 249.8 111.8 190.4 159.9 213.6 133.4 238.7 106.3 180.4 153.9 202.7 127.6 226.9 100.7
85 209.5 193.0 233.6 166.3 260.3 138.9 200.8 187.5 224.0 160.9 249.9 133.7 191.4 181.7 213.8 155.2 238.9 128.1 181.6 175.7 203.0 149.3 227.1 122.4
90 212.7 212.7 233.9 188.1 260.5 160.6 205.2 205.2 224.3 182.6 250.1 155.2 197.4 197.4 214.1 176.8 239.1 149.7 189.0 189.0 203.4 170.8 227.3 143.9
75 223.8 169.6 249.5 135.2 277.5 99.6 213.8 163.8 238.8 129.6 265.8 94.2 203.4 157.8 227.5 123.9 253.4 88.6 192.4 151.6 215.6 117.8 240.4 82.9
80 224.5 197.4 249.7 163.1 277.6 128.2 214.8 191.6 239.1 157.5 265.9 122.7 204.4 185.6 227.8 151.6 253.6 117.0 193.5 179.4 215.9 145.6 240.6 111.1
85 226.7 222.0 249.9 190.8 277.9 155.9 217.9 215.9 239.4 185.1 266.2 150.3 208.8 208.8 228.2 179.2 253.8 144.5 199.6 199.6 216.3 173.0 240.8 138.6
90 237.7 237.7 250.8 218.3 278.1 183.4 229.4 229.4 240.3 212.6 266.5 177.8 220.4 220.4 229.2 206.6 254.1 172.0 211.0 211.0 217.5 200.4 241.1 165.9
75 234.3 187.9 260.5 146.4 289.2 103.7 223.9 182.1 249.1 140.7 276.7 98.2 212.8 175.9 237.1 134.8 263.3 92.5 201.1 169.5 224.3 128.7 249.4 86.5
80 235.9 221.8 260.8 180.1 289.4 138.0 225.7 215.9 249.4 174.3 276.9 132.3 214.9 209.8 237.3 168.2 263.6 126.5 202.8 202.8 224.6 161.9 249.6 120.4
85 243.8 243.8 261.4 213.2 289.7 171.3 234.9 234.9 250.1 207.4 277.2 165.6 225.3 225.3 238.2 201.3 264.0 159.7 215.3 215.3 225.7 195.0 250.0 153.6
90 257.1 257.1 263.2 246.7 290.1 204.5 247.9 247.9 252.1 240.8 277.5 198.6 238.1 238.1 240.6 234.8 264.3 192.6 227.7 227.7 228.5 224.2 250.4 186.3
75 239.8 199.6 266.0 153.5 295.0 106.1 229.0 193.6 254.2 147.8 282.1 100.6 217.6 187.4 241.8 141.7 268.2 94.7 205.6 180.9 228.6 138.4 253.8 88.7
80 242.3 237.5 266.3 190.6 295.3 144.0 230.8 230.8 254.6 184.7 282.3 138.3 221.3 221.1 242.2 178.6 268.6 132.4 210.7 210.7 229.2 172.3 254.2 126.2
85 253.7 253.7 267.4 227.6 295.7 181.1 244.3 244.3 255.7 221.6 282.7 175.3 234.3 234.3 243.5 215.5 269.1 169.3 223.6 223.6 230.6 209.1 254.6 163.1
90 267.6 267.6 270.3 265.1 296.0 217.7 257.9 257.9 257.8 257.8 283.2 211.9 247.5 247.5 247.5 247.5 269.6 205.7 236.6 236.6 236.6 236.6 255.3 199.4
75 244.5 210.8 270.7 160.1 299.8 108.3 233.4 204.7 258.5 154.3 286.5 102.8 221.8 198.5 245.8 148.2 272.4 96.9 209.5 191.9 232.3 141.9 257.5 90.8
80 248.1 248.1 271.1 200.8 300.1 149.8 238.5 238.5 259.0 194.8 286.8 144.0 228.4 228.4 246.3 188.7 272.8 138.1 217.6 217.6 232.9 182.3 258.0 131.8
85 262.5 262.5 272.6 241.6 300.5 190.5 252.6 252.6 260.7 235.6 287.3 184.7 242.1 242.1 248.1 229.3 273.3 178.7 231.0 231.0 235.0 222.9 258.3 172.1
90 277.2 277.2 277.0 277.0 301.0 230.6 266.9 266.9 266.8 266.8 288.0 224.7 256.0 256.0 256.0 256.0 274.1 218.5 244.6 244.6 244.5 244.5 259.4 212.1
75 248.5 221.7 274.6 166.6 303.7 110.4 237.3 215.6 262.1 160.6 290.2 104.8 225.4 209.3 249.0 154.6 275.8 98.9 213.0 202.7 235.3 148.3 260.6 92.7
80 255.2 255.2 275.2 210.8 304.0 155.3 245.3 245.3 262.8 204.7 290.6 149.6 234.7 234.7 249.8 198.5 276.2 143.5 223.6 223.6 236.2 192.0 261.1 137.3
85 270.2 270.2 277.2 255.2 304.3 199.4 259.9 259.9 265.1 249.2 291.0 193.6 249.0 249.0 252.3 242.9 276.7 187.4 237.5 237.5 239.1 236.5 261.6 180.9
90 285.5 285.5 285.4 285.4 305.2 243.0 274.8 274.8 274.8 274.8 292.1 237.2 263.5 263.5 263.5 263.5 277.9 231.0 251.5 251.5 251.5 251.5 263.0 224.5
75 252.1 232.3 277.9 172.8 306.9 112.3 240.7 226.2 265.2 166.9 293.3 106.7 228.7 219.9 251.7 160.6 278.6 100.7 216.3 213.3 237.8 154.1 263.2 94.5
80 261.5 261.5 278.7 220.4 307.3 160.6 251.2 251.2 266.1 214.3 293.8 155.0 240.4 240.4 252.8 208.0 279.2 148.9 228.8 228.8 238.9 201.5 263.8 142.6
85 277.0 277.0 281.4 268.6 307.7 208.4 266.4 266.4 269.2 262.5 294.2 202.3 255.1 255.1 254.9 254.9 279.7 196.0 243.1 243.1 243.0 243.0 264.4 189.6
90 292.8 292.8 292.8 292.8 308.7 255.2 281.8 281.8 281.8 281.8 295.6 249.4 270.1 270.1 270.1 270.1 281.3 243.2 257.7 257.7 257.7 257.7 266.2 236.7

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 6400 CFM
• Electric heaters restricted on applications below 6400 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

27

Performance
Data

(20 Ton)
High Efficiency

Table PD-14 — Gross Cooling Capacities (MBH) 20 Ton Three Phase T*D241C3, C4, CW— Dehumidification (Hot Gas Reheat)
AmbientTemperature (F)
85

CFM
Airflow
4000*

5200*

6400

7200

8000

8800

9600

95

105
115
Enter.
Dry
Entering Wet Bulb (F)
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 197.5 138.9 222.3 116.0 249.8 89.2 188.8 133.4 213.0 110.6 239.6 83.8 179.7 127.6 203.1 105.0 228.8 78.3 170.1 121.7 192.6 99.2 217.3 72.5
80 197.7 159.2 222.6 135.8 249.8 111.4 189.0 153.7 213.3 130.3 239.6 105.8 180.0 147.9 203.4 124.6 228.8 100.1 170.4 141.9 193.0 118.7 217.4 94.2
85 198.2 179.3 222.9 156.3 250.0 132.0 189.7 173.8 213.5 150.7 239.8 126.4 180.8 168.1 203.7 145.0 229.0 120.7 171.4 162.2 193.3 139.1 217.7 114.8
90 200.5 196.8 223.1 176.7 250.3 152.5 192.8 190.9 213.7 171.0 240.1 147.0 184.8 184.8 203.8 165.2 229.3 141.2 176.9 176.9 193.5 159.3 217.9 135.3
75 213.1 158.3 239.0 127.6 267.2 94.6 203.5 152.5 228.5 121.8 255.7 88.9 193.2 146.3 217.5 115.8 243.7 83.1 182.7 140.0 206.0 109.6 231.1 77.1
80 213.5 183.8 239.3 153.7 267.4 122.1 204.0 178.0 228.9 147.9 255.9 116.3 194.0 171.9 217.9 141.9 243.9 110.3 183.5 165.7 206.4 135.7 231.3 104.1
85 215.3 209.9 239.7 179.7 267.7 148.3 204.6 204.6 229.1 173.7 256.2 142.4 197.0 194.2 218.1 167.6 244.2 136.4 187.4 187.4 206.7 161.4 231.6 130.3
90 224.3 224.3 240.1 205.2 268.0 174.4 216.2 216.2 229.8 199.4 256.6 168.6 207.6 207.6 218.9 193.3 244.5 162.5 198.7 198.7 207.6 187.1 232.0 156.4
75 223.7 175.3 250.2 138.3 279.0 98.8 213.5 169.3 239.0 132.3 266.6 93.0 202.6 163.0 227.2 126.1 253.7 87.0 191.3 156.4 214.9 119.7 240.2 80.8
80 224.9 206.3 250.6 169.7 279.2 131.4 214.8 200.3 239.4 163.6 266.8 125.3 204.2 194.1 227.7 157.5 253.9 119.2 193.2 187.7 215.2 151.0 240.5 112.9
85 230.5 230.5 251.0 200.6 279.6 162.9 221.7 221.7 239.8 194.5 267.2 156.9 212.5 212.5 228.1 188.2 254.3 150.7 202.8 202.8 215.9 181.8 240.9 144.4
90 243.6 243.6 252.4 231.7 280.0 194.4 234.6 234.6 241.5 225.7 267.7 188.3 225.1 225.1 230.0 219.5 254.6 181.9 215.2 215.2 215.6 215.6 241.2 175.5
75 229.2 185.9 255.7 150.2 284.8 101.3 218.6 179.7 244.1 144.1 272.0 95.4 207.4 173.3 231.9 138.0 258.6 89.4 195.8 166.7 219.1 131.7 244.7 83.2
80 231.1 220.6 256.3 179.6 285.1 137.0 220.8 214.5 244.6 173.3 272.3 130.9 208.4 208.4 232.5 167.0 258.9 124.7 199.2 197.3 219.8 160.4 245.0 118.3
85 240.3 240.3 256.9 213.7 285.5 172.0 231.1 231.1 245.4 207.5 272.7 165.9 221.4 221.4 233.3 201.2 259.4 159.7 211.2 211.2 220.8 194.7 245.5 153.3
90 254.0 254.0 259.2 248.5 286.0 206.7 244.5 244.5 248.0 242.5 273.2 200.5 234.5 234.5 235.0 235.0 259.8 194.1 224.0 224.0 225.1 224.1 246.0 187.6
75 233.9 196.0 260.5 150.9 289.7 103.6 223.0 189.8 248.6 144.8 276.5 97.7 211.5 183.3 236.1 138.4 262.7 91.4 199.6 176.7 223.0 131.9 248.4 85.0
80 234.8 234.8 261.0 188.8 290.0 142.4 225.4 225.4 249.0 182.5 276.9 136.2 215.6 215.6 236.5 176.1 263.1 129.9 205.3 205.3 223.5 169.5 248.8 123.5
85 249.0 249.0 262.0 226.4 290.5 180.8 239.3 239.3 250.1 220.2 277.4 174.6 229.2 229.2 237.8 213.8 263.6 168.3 218.6 218.6 225.1 207.3 249.2 161.7
90 263.3 263.3 263.7 263.7 291.0 218.5 253.3 253.3 254.6 253.1 277.9 212.2 242.9 242.9 243.3 243.3 264.2 205.8 231.9 231.9 232.3 232.3 249.9 199.2
75 237.9 205.8 264.5 156.8 293.8 105.7 226.7 199.5 252.2 150.6 280.3 99.6 215.1 193.0 239.4 144.2 266.1 93.2 202.9 186.3 226.0 137.6 251.5 86.6
80 242.3 242.3 265.0 197.7 294.1 147.5 232.1 232.1 252.7 191.4 280.6 141.3 221.9 221.9 239.9 184.9 266.6 135.0 211.2 211.2 226.6 178.2 251.9 128.4
85 256.5 256.5 266.4 238.7 294.7 189.2 246.5 246.5 254.3 232.4 281.0 182.8 235.9 235.9 241.8 226.0 267.0 176.3 224.9 224.9 228.9 219.4 252.4 169.7
90 271.4 271.4 271.8 271.8 295.2 229.9 261.0 261.0 261.4 261.4 281.8 223.6 250.1 250.1 250.5 250.5 267.9 217.2 238.7 238.7 239.1 239.1 253.4 210.5
75 241.4 215.2 267.8 162.4 297.1 107.4 230.0 208.9 255.3 156.2 283.4 101.2 218.2 202.3 242.2 149.7 269.0 94.8 205.9 195.6 228.4 143.0 254.0 88.2
80 248.0 248.0 268.4 206.4 297.6 152.5 237.9 237.9 255.9 200.0 283.8 146.2 227.5 227.5 242.8 193.4 269.5 139.8 216.4 216.4 229.3 186.7 254.6 133.2
85 263.1 263.1 270.3 250.7 298.0 197.1 252.8 252.8 258.1 244.3 284.3 190.7 241.9 241.9 245.5 237.9 270.0 184.1 230.5 230.5 230.7 230.7 255.1 177.4
90 278.6 278.6 278.9 278.9 298.9 241.1 267.9 267.9 268.3 268.3 285.3 234.7 256.6 256.6 257.0 257.0 271.1 228.2 244.7 244.7 245.1 245.1 256.4 221.5

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 6400 CFM
• Electric heaters restricted on applications below 6400 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM.

28

RT-PRC002-EN

Performance
Data

(25 Ton)
High Efficiency

Table PD-15 — Gross Cooling Capacities (MBH)25 Ton Three Phase TC*301C3, C4, CW - Standard Refrigeration System
85

CFM
Airflow
9000

10000

10500

11000

Enter.
Dry
Bulb
61
(F) MBH SHC
75
277 243
80
284 284
85
300 300
90
312 312
75
284 258
80
294 294
85
307 307
90
318 318
75
286 265
80
297 297
85
310 310
90
320 320
75
289 272
80
300 300
85
312 312
90
322 322

67
MBH SHC
306 187
307 225
309 269
313 312
310 188
310 233
313 280
318 318
311 190
312 237
315 285
320 320
312 192
313 240
316 289
321 321

95

73
MBH SHC
316 117
321 169
325 198
329 236
319 121
323 175
327 202
331 241
320 122
324 178
328 204
332 244
321 123
324 181
329 205
332 246

61
MBH SHC
258 234
269 269
289 289
305 305
264 249
280 280
298 298
312 312
267 256
285 285
302 302
314 314
270 264
289 289
305 305
317 317

67
MBH SHC
295 178
295 225
298 271
305 305
299 185
300 236
303 286
312 312
300 189
302 241
305 293
314 314
302 192
304 246
307 299
317 317

AmbientTemperature (F)
105
Entering Wet Bulb (F)
73
61
67
MBH SHC MBH SHC MBH SHC
314 115 238 224 276 169
317 161 252 252 277 217
320 202 273 273 280 266
321 240 293 293 293 293
316 117 244 239 282 178
319 170 263 263 283 230
322 207 284 284 287 284
324 248 301 301 301 301
316 118 247 246 284 182
320 174 267 267 285 237
323 210 289 289 289 289
325 251 305 305 305 305
317 119 249 249 286 186
321 177 272 272 287 243
324 212 293 293 293 293
326 255 308 308 308 308

115

73
MBH SHC
305 110
307 158
308 201
310 245
308 112
309 163
312 208
314 255
309 113
310 165
313 212
316 260
309 114
311 170
314 215
317 265

61
MBH SHC
218 214
235 235
256 256
277 277
224 224
245 245
267 267
287 287
228 228
249 249
272 272
292 292
231 231
253 253
276 276
295 295

67
MBH SHC
253 163
254 207
259 256
277 277
259 168
260 221
267 267
287 287
261 172
262 227
272 272
292 292
263 176
265 234
276 276
295 295

73
MBH SHC
292 104
293 151
293 198
295 244
295 106
296 158
297 208
299 257
296 107
298 162
299 213
301 264
297 108
299 165
300 217
303 270

Notes
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

RT-PRC002-EN

29

Performance
Data

(25 Ton)
High Efficiency

Table PD-16 — Gross Cooling Capacities (MBH)25 Ton Three PhaseTC*301C3, C4, CW— TXV Option
85

CFM
Airflow
5000*

6500*

8000

9000

10000

11000

12000

95

AmbientTemperature (F)
105

115
Enter.
Dry
Entering Wet Bulb (F)
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 241.0 176.5 269.7 142.7 300.9 107.2 229.7 169.7 257.6 135.9 287.8 100.8 217.8 162.6 244.9 129.0 274.0 94.1 205.5 155.3 231.6 122.0 259.8 87.3
80 241.4 204.6 269.9 170.5 300.9 135.9 230.2 197.7 257.8 163.8 287.8 129.3 218.4 190.5 245.1 156.8 274.1 122.5 206.2 183.2 231.9 149.6 259.8 115.6
85 243.0 233.0 270.1 198.3 301.1 163.7 229.2 229.2 258.1 191.5 288.1 157.0 221.3 216.5 245.4 184.5 274.4 150.1 209.9 208.3 232.2 177.3 260.1 143.1
90 251.2 251.2 270.6 226.1 301.4 191.2 241.6 241.6 258.6 219.2 288.3 184.4 231.6 231.6 246.0 212.1 274.6 177.5 221.2 221.2 233.0 204.8 260.4 170.4
75 256.8 201.4 286.5 157.9 318.8 113.1 244.6 194.3 273.3 150.9 304.2 106.4 231.8 186.9 259.5 143.8 289.2 99.5 218.4 179.4 245.1 136.5 273.6 92.5
80 258.2 237.2 286.8 193.2 318.9 149.3 246.1 230.1 273.6 186.2 304.4 142.3 233.6 222.8 259.8 179.0 289.4 135.3 220.7 215.4 245.4 171.6 273.9 128.1
85 264.6 264.6 287.3 228.5 319.2 184.3 254.2 254.2 274.1 221.4 304.7 177.3 243.2 243.2 260.4 214.1 289.7 170.2 231.7 231.7 246.2 206.6 274.1 162.9
90 279.1 279.1 288.7 263.8 319.5 219.2 268.4 268.4 275.8 256.7 305.0 212.1 257.3 257.3 262.4 249.5 290.0 205.0 245.6 245.6 245.5 245.5 274.5 197.7
75 267.9 224.2 297.7 171.5 330.7 118.0 254.9 216.9 283.7 164.4 315.3 111.1 241.5 209.3 269.2 157.1 299.2 104.0 227.5 201.6 254.0 149.6 282.7 96.8
80 268.8 268.8 298.0 214.0 330.9 161.1 259.3 255.4 284.1 206.8 315.5 154.0 246.8 246.7 269.6 199.5 299.5 146.7 234.0 234.0 254.5 191.9 283.0 139.4
85 284.5 284.5 299.2 256.4 331.2 203.2 273.2 273.2 285.4 249.2 315.9 196.1 261.3 261.3 271.0 241.8 299.8 188.8 248.9 248.9 256.2 234.3 283.3 181.4
90 300.3 300.3 300.2 300.2 331.6 245.2 288.7 288.7 290.5 286.0 316.4 238.0 276.5 276.5 276.4 276.4 300.4 230.6 263.8 263.8 263.7 263.7 284.0 223.1
75 273.6 238.6 303.4 180.1 336.6 120.9 260.4 231.2 289.0 172.8 320.7 114.0 246.7 223.6 273.9 170.7 304.2 106.8 232.5 215.9 258.3 163.2 287.1 99.6
80 279.6 279.5 303.8 227.0 336.8 168.4 267.3 267.3 289.5 219.8 321.0 161.3 255.2 255.2 274.6 212.4 304.5 154.0 242.6 242.6 259.1 204.8 287.5 146.5
85 295.1 295.1 305.6 274.3 337.2 215.2 283.4 283.4 291.5 267.1 321.4 208.1 271.0 271.0 276.9 259.7 304.9 200.7 258.0 258.0 261.9 252.2 287.8 193.1
90 311.9 311.9 311.8 311.8 338.0 261.8 299.6 299.6 299.6 299.6 322.2 254.5 286.9 286.9 286.8 286.8 305.9 247.1 273.5 273.5 273.5 273.5 288.9 239.4
75 278.6 252.6 308.1 188.2 341.5 123.5 265.2 245.2 293.3 180.9 325.3 116.5 251.3 237.6 278.0 173.5 308.4 109.2 234.1 234.1 262.1 165.9 290.8 101.7
80 287.6 287.6 308.7 239.7 341.8 175.5 275.5 275.5 294.0 232.5 325.6 168.3 263.1 263.1 278.8 225.0 308.7 160.9 250.0 250.0 263.1 217.3 291.2 153.4
85 304.6 304.6 311.3 291.9 342.1 226.8 292.3 292.3 297.0 284.7 325.9 219.5 279.4 279.4 279.3 279.3 309.1 212.1 266.0 266.0 267.7 262.9 291.7 204.4
90 322.2 322.2 322.1 322.1 343.3 277.9 309.3 309.3 309.3 309.3 327.2 270.5 295.9 295.9 295.9 295.9 310.6 263.1 282.0 282.0 282.0 282.0 293.3 255.3
75 283.1 266.2 312.0 196.0 345.5 125.9 269.5 258.8 296.9 188.7 329.1 118.9 253.1 253.1 281.2 181.2 311.8 111.5 241.4 237.4 265.1 173.5 293.9 104.0
80 295.1 295.1 312.9 252.1 345.8 182.3 282.8 282.8 297.9 244.7 329.4 175.0 269.9 269.9 282.4 237.2 312.2 167.7 256.4 256.4 266.5 229.4 294.3 160.1
85 312.9 312.9 312.8 312.8 346.2 237.9 300.0 300.0 299.9 299.9 329.9 230.6 286.7 286.7 288.1 285.2 312.8 223.1 272.8 272.8 272.7 272.7 295.0 215.4
90 331.2 331.2 331.1 331.1 347.8 293.5 317.8 317.8 317.8 317.8 331.6 286.2 304.0 304.0 303.8 303.8 314.7 278.6 289.3 289.3 289.3 289.3 297.3 271.0
75 283.8 283.8 315.3 203.6 348.9 128.2 271.5 271.5 299.9 196.2 332.2 121.1 259.9 256.8 284.1 188.6 314.7 113.8 245.2 245.2 267.7 180.9 296.5 106.2
80 301.8 301.8 316.6 264.1 349.2 188.9 289.0 289.0 301.2 256.6 332.6 181.7 275.9 275.9 285.7 249.1 315.2 174.3 262.0 262.0 269.5 241.3 297.0 166.6
85 320.3 320.3 322.4 316.7 349.8 248.8 307.0 307.0 308.0 306.9 333.2 241.5 293.2 293.2 293.1 293.1 315.8 233.9 278.8 278.8 278.8 278.8 297.8 226.2
90 339.1 339.1 339.0 339.0 351.7 308.8 325.4 325.4 325.3 325.3 335.6 301.5 310.9 310.9 310.9 310.9 318.5 294.0 295.9 295.9 295.9 295.9 301.0 286.4

Notes
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 8000 CFM
• Electric heaters restricted on applications below 8000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 8000 CFM.

30

RT-PRC002-EN

Performance
Data

(12½ Ton)
Standard Efficiency

Table PD-17 — Evaporator Fan Performance — 12½Ton — TC*150D
.10
CFM

4000
4500
5000
5500
6000

RPM

—
—
547
595
643

.20
BHP

—
—
1.18
1.55
1.99

RPM

—
—
581
627
673

.30
BHP

—
—
1.30
1.68
2.12

RPM

—
571
613
656
701

BHP

—
1.10
1.42
1.81
2.26

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3 HP Standard Motor & Field
Supplied Low Static Drive
565
0.93
599
1.03
603
1.21
634
1.31
643
1.54
672
1.67
685
1.94
711
2.08
727
2.41
752
2.56

.80
RPM

BHP

.90
RPM BHP

1.00
RPM BHP

727
750
781
813
848

757
778
806
837
871

3 HP Standard Motor & Sheaves
632
665
700
737
777

1.15
1.43
1.78
2.21
2.71

663
694
727
763
801

1.27
1.56
1.91
2.34
2.85

695
723
755
788
825

1.38
1.69
2.05
2.47
2.99

1.48
1.82
2.19
2.62
3.13

1.59
1.94
2.34
2.77
3.27

Table PD-17 — Evaporator Fan Performance — 12½ Ton — TC*150D — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

1.30
RPM
BHP

4000
4500
5000
5500
6000

3 HP Standard Motor & Sheaves
786
1.70
813
1.81
841
806
2.06
834
2.19
861
830
2.48
856
2.62
882
861
2.93
884
3.10
906
894
3.43
916
3.61
938

1.91
2.31
2.76
3.25
3.79

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
867
886
907
930
959

1.90
RPM BHP

3 HP Standard Motor & High Static Drive Accessory
2.02
893
2.12
919
2.22
943
2.32
966
2.41
989
2.43
911
2.56
935
2.67
960
2.79
983
2.90
1005
2.89
931
3.02
955
3.16
977
3.30
1001
3.44 1022
3.41
953
3.56
976
3.70
999
3.86
1021
4.00 1043
3.97
980
4.15
1000
4.31
1019
4.46
1040
4.62 1061
5 HP Oversize Motor & Sheaves

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary.
2. 5 HP Oversized Motor with Field Supplied Motor Sheave IVL40 Required. Field Supplied Belt
may be necessary.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/Fan Speed” tables to determine operating range.

RT-PRC002-EN

1.80
RPM
BHP

2.50
3.02
3.56
4.15
4.78

2.00
RPM BHP
1011
1028
1045
1064
1082

2.60
3.13
3.70
4.31
4.95

5 HP Oversize Motor & Field Supplied Drive
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our
tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.

31

Performance
Data

(15 Ton)
Standard Efficiency

Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B
.10
CFM

4800
5400
6000
6600
7200

RPM

—
585
643
701
760

.20
BHP

RPM

—
1.47
1.99
2.61
3.35

.30
BHP

563
618
673
729
786

1.17
1.60
2.12
2.76
3.52

RPM

BHP

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

3 HP Standard Motor & Field
Supplied Low Static Drive (1)
596
1.29
626
1.41
648
1.72
676
1.86
701
2.26
727
2.41
755
2.91
780
3.07
810
3.69
834
3.85

.80
RPM

BHP

.90
RPM BHP

1.00
RPM BHP

3 HP Standard Motor & Sheaves
656
703
752
804
856

1.52
1.99
2.56
3.23
4.02

(2)

685
1.63
714
1.76
742
729
2.12
756
2.25
782
777
2.71
801
2.85
825
827
3.39
849
3.56
871
878
4.20
899
4.38
919
5 HP Oversized Motor & Sheaves

1.90
2.38
2.99
3.72
4.56

768
807
848
892
939

2.04
2.52
3.13
3.88
4.74

794
832
871
914
959

2.18
2.68
3.27
4.03
4.91

Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B — Continued
CFM

1.10
RPM
BHP

4800
5400
6000
6600
7200

819
855
894
935
979

1.20
RPM
BHP

1.30
RPM
BHP

3 HP Standard Motor & Sheaves
2.30
844
2.43
871
2.84
878
3.00
901
3.43
916
3.61
938
4.18
956
4.34
977
5.08
999
5.25
1018

2.57
3.15
3.79
4.51
5.41

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
898
923
959
997
1038

2.70
3.29
3.97
4.70
5.58

3 HP Standard Motor & High Static Drive Accessory
923
2.83
946
2.96
970
3.09
994
3.23
945
3.43
969
3.58
993
3.73
1016
3.88
980
4.15
1000
4.31
1019
4.46 1040
4.62
1018
4.90
1037
5.10
1056
5.30 1075
5.49
1057
5.77
—
—
—
—
—
—

5 HP Oversized Motor & Sheaves
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt may be necessary.
2. 5 HP Oversized Motor with Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may
be necessary.
3. 5 HP Oversized Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt
may be necessary.
4. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/Fan Speed” tables to determine operating range.

32

1.80
RPM
BHP

1.90
RPM BHP

2.00
RPM BHP

1018
1038
1061
1093
—

1041
1060
1082
—
—

3.39
4.03
4.78
5.67
—

3.54
4.17
4.95
—
—

5 HP Oversized Motor & Field Supplied Drive (3)
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.

RT-PRC002-EN

Performance
Data

(17½Ton)
Standard Efficiency

Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C
.10

.20

.30

CFM

RPM

BHP

RPM

BHP

RPM

BHP

5600
6300
7000
7700
8400

—
765
845
925
1006

—
2.96
4.02
5.32
6.87

—
788
866
944
1024

—
3.10
4.18
5.49
7.06

735
810
886
963
1041

2.34
3.23
4.33
5.66
7.24

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5 HP Standard Motor with Low Static Drive Accessory
759
2.46
783
2.60
807
2.74
830
2.89
831
3.36
852
3.50
874
3.65
895
3.81
906
4.48
925
4.62
944
4.77
963
4.93
982
5.82
999
5.98
1016
6.14
1033
6.30
1058
7.42
1075
7.60
1091
7.78
1107
7.95
7.5 HP Oversize Motor & Sheaves

RPM

.80
BHP

.90
RPM BHP

1.00
RPM BHP

852
917
982
1050
1122

3.03
3.97
5.10
6.47
8.13

875
937
1002
1069
1138

898
956
1021
1086
1154

3.18
4.13
5.29
6.66
8.31

3.33
4.29
5.47
6.86
8.50

5 HP Standard Motor & Sheaves

Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

5600
6300
7000
7700
8400

923
976
1039
1104
—

946
997
1057
1122
—

968
1019
1074
1138
—

989
1040
1092
1154
—

3.50
4.46
5.65
7.06
—

3.68
4.63
5.82
7.26
—

3.85
4.82
6.00
7.46
—

5 HP Standard Motor & Sheaves
4.03
1011
4.21
1033
4.39
5.00
1060
5.19
1079
5.39
6.19
1111
6.39
1130
6.59
7.66
1170
7.84
1186
8.05
—
—
—
—
—

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/
Fan Speed” tables to determine operating range.

1056
1100
1150
1202
—

4.58
5.60
6.80
8.25
—

1.80
RPM
BHP

1.90
RPM BHP

2.00
RPM BHP

1078
1118
1168
1220
—

1099
1138
1186
—
—

1122
1157
1205
—
—

4.77
5.79
7.01
8.47
—

4.96
6.00
7.22
—
—

5.18
6.20
7.46
—
—

7.5 HP Oversive Motor & Sheaves
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

33

Performance
Data

(20 Ton)
Standard Efficiency

Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B
.10
CFM

6400
7200
8000
8800
9600

RPM

—
527
578
629
681

.20
BHP

—
2.08
2.79
3.65
4.67

RPM

.30
BHP

RPM

BHP

RPM

External Static Pressure (Inches of Water)
.40
.50
.60
.70
BHP
RPM
BHP
RPM
BHP
RPM
BHP

5 HP Standard Motor & Field Supplied
Low Static Drive (1)
514
1.69
546
1.88
574
2.05
599
562
2.29
592
2.50
619
2.71
644
610
3.03
639
3.26
666
3.50
690
659
3.93
687
4.18
712
4.43
736
709
4.99
735
5.27
759
5.54
782
5 HP Standard Motor & Sheaves

.80
RPM

BHP

.90
RPM BHP

1.00
RPM BHP

5 HP Standard Motor & Sheaves
2.21
2.91
3.73
4.69
5.82

624
667
712
758
804
(2)

2.37
3.09
3.96
4.96
6.11

648
689
733
778
824

2.54
671
2.71
695 2.90
720
3.26
711
3.45
732 3.64
752
4.16
753
4.35
773 4.55
792
5.20
797
5.43
816 5.65
834
6.39
843
6.67
861 6.92
878
7.5 HP Oversized Motor & Sheaves

3.11
3.83
4.75
5.86
7.16

Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

6400
7200
8000
8800
9600

744
773
811
852
895

768
795
830
869
911

3.32
4.04
4.96
6.08
7.40

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

5 HP Standard Motor & Sheaves
3.52
790
3.72
811
3.91
833
4.27
817
4.50
839
4.74
860
5.18
848
5.40
867
5.64
887
6.30
887
6.53
904
6.77
921
7.63
928
7.86
944
8.11
960
7.5 HP Oversized Motor & Sheaves

4.13
4.96
5.90
7.01
8.36

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt
may be necessary.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/Fan Speed” tables to determine operating range.

855
880
907
938
976

1.80
RPM
BHP

1.90
RPM BHP

2.00
RPM BHP

5 HP Standard Motor & High Static Drive Accessory
4.36
877
4.59
897
4.82
917 5.05
936
5.19
898
5.41
917
5.64
937 5.88
957
6.16
927
6.42
946
6.68
964 6.93
982
7.26
955
7.52
973
7.81
991 8.09
—
8.61
—
—
—
—
—
—
—

5.29
6.14
7.18
—
—

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

*Indicates both downflow and horizontal units.

34

RT-PRC002-EN

Performance
Data

(25 Ton)
Standard Efficiency

Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B
.10

.20

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

.30

CFM

RPM

BHP

RPM

BHP

RPM

BHP

7000
7500
8000
8500
9000
9500
10000
10500
11000

—
—
595
628
661
695
729
762
796

—
—
2.92
3.47
4.08
4.76
5.52
6.35
7.27

—
595
627
659
691
723
755
788
821

—
2.66
3.16
3.73
4.36
5.06
5.84
6.69
7.63

593
624
655
686
717
749
781
812
844

7.5 HP Standard Motor & Low Static Drive Accessory
2.42
619
2.62
643
2.80
667
2.98
690
2.88
649
3.10
673
3.31
695
3.50
717
3.39
679
3.63
702
3.86
724
4.07
745
3.97
710
4.23
732
4.47
754
4.71
774
4.62
741
4.89
763
5.15
784
5.41
803
5.34
772
5.62
794
5.90
814
6.18
833
6.13
804
6.42
825
6.72
844
7.01
863
7.00
835
7.31
856
7.62
875
7.93
894
7.96
867
8.3
887
8.60
—
—
—

3.16
3.68
4.28
4.94
5.66
6.45
7.31
8.24
—

.80
RPM

BHP

.90
RPM BHP

1.00
RPM BHP

7.5 HP Standard Motor & Sheaves
712
3.35
733 3.53
754 3.73
738
3.88
759 4.08
779 4.28
766
4.48
786 4.68
805 4.90
794
5.15
813 5.36
832 5.58
822
5.89
841 6.12
859 6.35
852
6.71
870 6.95
887 7.19
881
7.59
899 7.86
916 8.11
911
8.54
—
—
—
—
—
—
—
—
—
—

7.5 HP Standard Motor & High Static Drive Accessory

7.5 HP Standard Motor & Sheaves

Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

7000
7500
8000
8500
9000
9500
10000
10500
11000

776
798
824
850
877
904
933
—
—

798
818
842
868
894
921
949
—
—

3.95
4.48
5.11
5.81
6.58
7.43
8.36
—
—

External Static Pressure (Inches of Water)
1.30
1.40
1.50
RPM
BHP
RPM
BHP
RPM
BHP

7.5 HP Standard Motor & Sheaves
4.18
820
4.40
841
4.62
4.71
839
4.95
860
5.19
5.32
860
5.55
880
5.80
6.03
885
6.26
902
6.49
6.81
911
7.05
928
7.29
7.67
938
7.92
954
8.17
8.62
—
—
—
—
—
—
—
—
—
—
—
—
—
—

862
880
899
920
944
970
—
—
—

4.84
5.42
6.06
6.74
7.53
8.42
—
—
—

7.5 HP Standard Motor & High Static Drive Accessory
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop
data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan
Speed” tables to determine operating range.

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

35

Performance
Data

(12½ Ton)
High Efficiency

Table PD-22 — Evaporator Fan Performance — 12½Ton — TCD151C — Standard or TXV Refrigeration System
.10
CFM

2500*
3250*
4000
4500
5000
5500
6000

RPM

—
378
430
466
503
540
579

.20
BHP

RPM

.30
BHP

RPM

3 HP Standard Motor & Field
Supplied Low Static Drive (2)
—
402
0.30
460
0.35
447
0.49
503
0.56
495
0.74
549
0.74
528
0.95
580
0.96
562
1.20
612
1.22
597
1.49
645
1.53
633
1.82
680

BHP

0.39
0.62
0.91
1.14
1.42
1.74
2.10

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

510
552
596
627
657
689
722

3 HP Standard Motor & Field
Supplied High Static Drive (2)
0.48
555
0.56
595
0.74
595
0.86
634
1.07
638
1.22
677
1.33
668
1.51
706
1.63
699
1.84
736
1.98
729
2.20
767
2.37
761
2.63
797

.80
RPM

BHP

.90
RPM BHP

1.00
RPM BHP

3 HP Standard Motor & Drive
0.64
0.97
1.37
1.68
2.04
2.44
2.87

633
672
712
742
771
801
832

0.74
1.08
1.52
1.85
2.23
2.66
3.13

667
706
747
776
803
833
864

3 HP Standard Motor & High Static Drive Accessory

0.83
1.19
1.66
2.02
2.41
2.87
3.38

699
739
778
806
835
864
894

0.92
1.30
1.80
2.18
2.61
3.07
3.61

731
769
809
836
865
893
922

1.02
1.40
1.94
2.34
2.80
3.28
3.83

5 HP Oversize Motor & Drive

Table PD-22 — Evaporator Fan Performance — 12½ Ton — TCD151C — Continued
CFM

1.10
RPM
BHP

2500*
3250*
4000*
4500
5000
5500
6000

760
798
839
865
892
922
950

1.20
RPM
BHP

1.30
RPM
BHP

3 HP Standard Motor & Drive
1.11
789
1.21
817
1.52
827
1.64
853
2.07
867
2.21
893
2.50
892
2.66
919
2.97
920
3.15
946
3.49
949
3.70
975
4.05
977
4.29
1002

1.31
1.76
2.33
2.81
3.33
3.90
4.51

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
842
880
919
945
971
999
1028

1.41
1.88
2.47
2.96
3.50
4.09
4.74

868
905
943
970
996
1023
1052

3 HP Standard Motor & High Static Drive Accessory
1.51
892
1.60
916
1.71
939
1.81
2.01
928
2.13
953
2.26
976
2.38
2.59
967
2.73
991
2.88
1013
3.03
3.11
994
3.25
1017
3.40 1039
3.55
3.68
1020
3.85
1043
4.02 1066
4.18
4.28
1047
4.48
1070
4.68 1091
4.87
4.96
1074
5.16
1098
5.38
1120
5.59
5 HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 4000 CFM
• Electric heaters restricted on applications below 4000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary.

36

1.80
RPM
BHP

1.90
RPM BHP
962
998
1036
1061
1088
1114
—

1.91
2.51
3.18
3.70
4.35
5.06
—

2.00
RPM BHP
984
1020
1056.4
1082.3
1109.6
1135.6
—

2.01
2.63
3.33
3.85
4.50
5.24
—

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

RT-PRC002-EN

Performance
Data

(12½ Ton)
High Efficiency

Table PD-23 — Evaporator Fan Performance — 12½Ton — T*D151C — Dehumidification (Hot Gas Reheat) Option
.10
CFM

2500*
3000*
3500*
4000
4500
5000
5500
6000

RPM

—
—
551
618
686
755
824
894

.20
BHP

—
—
0.78
1.11
1.54
2.07
2.71
3.47

RPM

—
534
594
656
720
786
853
921

.30
BHP

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

BHP

RPM

—
0.63
0.90
1.26
1.71
2.26
2.91
3.70

3 HP Standard Motor & Drive w/Field
Supplied Low Static Drive Fan Sheave
526
0.52
570
0.62
609
0.73
578
0.74
618
0.86
656
0.98
633
1.03
670
1.16
706
1.30
692
1.40
727
1.55
759
1.71
753
1.87
785
2.03
815
2.20
816
2.44
846
2.61
874
2.79
881
3.13
908
3.32
935
3.51
947
3.93
972
4.15
996
4.36

.80
RPM

BHP

.90
RPM BHP

1.00
RPM BHP

3 HP Standard Motor & Drive
646
692
739
791
844
902
960
1021

0.83
1.11
1.44
1.86
2.37
2.98
3.70
4.56

681
725
771
821
873
928
985
1044

0.93
1.23
1.58
2.01
2.54
3.17
3.91
4.78

713
756
802
850
901
954
1010
1068

1.03
1.35
1.73
2.17
2.71
3.37
4.13
5.01

744
786
831
878
928
979
1033
1090

1.14
1.48
1.88
2.34
2.89
3.56
4.34
5.24

776
814
859
905
953
1004
1056
1112

1.25
1.60
2.02
2.50
3.07
3.75
4.54
5.47

5 HP Oversized Motor & Drive

3 HP Standard Motor & High Static Drive Accessory

Table PD-23 — Evaporator Fan Performance — 12½ Ton — T*D151C — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

2500*
3000*
3500*
4000
4500
5000
5500
6000

3 HP Standard Motor
& Drive
804
1.36
832
1.48
842
1.73
869
1.85
885
2.17
910
2.31
930
2.67
956
2.85
978
3.25
1002
3.44
1028
3.94
1051
4.14
1079
4.76
1102
4.97
1133
5.70
—
—

5 HP Oversized Motor & Drive

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

1.90
RPM BHP

2.00
RPM BHP

998
1035
1072
1110
1154
1200
—
—

1020
1057
1093
1132
1174
—
—
—

3 HP Standard Motor & High Static Drive Accessory
859
895
935
980
1026
1074
1123
—

1.59
1.98
2.45
3.01
3.63
4.35
5.17
—

883
920
959
1003
1049
1096
1146
—

1.71
2.11
2.59
3.17
3.83
4.55
5.40
—

908
945
983
1026
1071
1118
1166
—

1.83
2.24
2.74
3.34
4.02
4.76
5.62
—

931
968
1006
1047
1093
1140
—
—

1.95
2.38
2.89
3.50
4.21
4.98
—
—

954
991
1029
1069
1113
1159
—
—

2.08
2.51
3.04
3.66
4.38
5.18
—
—

977
1014
1051
1090
1134
1180
—
—

2.21
2.65
3.19
3.82
4.57
5.40
—
—

2.33
2.79
3.34
3.99
4.75
5.61
—
—

2.47
2.94
3.49
4.16
4.94
—
—
—

5 HP Oversized Motor & Drive w/Field Supplied Fan Sheave

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 4000 CFM
• Electric heaters restricted on applications below 4000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary.

RT-PRC002-EN

1.80
RPM
BHP

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

37

Performance
Data

(12½ Ton)
High Efficiency

Table PD-24 — Evaporator Fan Performance — 12½Ton — TCH151C — Standard Refrigeration System
.10

.20

.30

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

CFM

RPM

BHP

RPM

BHP

RPM

BHP

4000
4500
5000
5500
6000

—
—
534
581
628

—
—
1.40
1.83
2.34

—
521
566
611
657

—
1.17
1.54
1.99
2.51

510
551
593
637
682

3 HP Standard Motor & Field Supplied Low Static Drive (1)
0.98
541
1.10
572
1.22
602
1.35
631
1.29
579
1.42
607
1.56
635
1.68
662
1.67
620
1.81
645
1.95
671
2.11
696
2.13
661
2.28
685
2.43
709
2.59
732
2.68
704
2.83
727
3.00
749
3.16
770

1.48
1.82
2.25
2.76
3.33

.80
RPM
659
688
720
754
791

BHP

.90
RPM BHP

1.00
RPM BHP

3 HP Standard Motor & Drive
1.62
687 1.76
714
1.98
713 2.13
738
2.40
744 2.56
767
2.92
777 3.08
799
3.52
812 3.70
833
5 HP Oversized Motor& Drive

1.91
2.28
2.73
3.25
3.87

Table PD-24 — Evaporator Fan Performance — 12½ Ton — TCH151C — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

3 HP Standard Motor & Drive
4000
4500
5000
5500
6000

740
763
790
820
853

2.07
2.44
2.90
3.43
4.04

766
787
812
842
874

2.23
2.61
3.07
3.61
4.23

791
811
835
862
893

2.38
2.78
3.24
3.80
4.43

814
835
857
883
913

2.54
838
2.70
860
2.96
858
3.13
880
3.42
879
3.61
901
3.98
904
4.17
924
4.63
932
4.83
951
5 HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop
due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary.

38

1.80
RPM
BHP

1.90
RPM BHP

3 HP Standard Motor & High Static
Drive Accessory
2.86
883
3.02
905
3.19
926
3.31
901
3.48
922
3.66
943
3.81
922
4.00
942
4.20
962
4.37
944
4.57
964
4.78
984
5.03
970
5.24
988
5.45
1007

3.37
3.84
4.39
4.99
5.66

2.00
RPM BHP

948
963
982
1003
—

3.55
4.02
4.59
5.20
—

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

RT-PRC002-EN

(15 Ton)

Performance
Data

High Efficiency

Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Standard or TXV Refrigeration System
.10
CFM

3000*
3900*
4800
5400
6000
6600
7200

RPM

—
341
399
445
479
519
560

.20
BHP

—
0.45
0.76
1.04
1.38
1.79
2.28

RPM

.30
BHP

RPM

BHP

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

3 HP Standard Motor &
3 HP Standard Motor & Field
Field Supplied Extra
Supplied Low Static Drive (1)
L ow Static Drive (2)
337
0.32
387
0.42
432
0.53
472
0.65
511
0.77
384
0.55
423
0.66
462
0.78
500
0.91
536
1.05
437
0.89
471
1.01
503
1.14
535
1.29
566
1.44
474
1.19
506
1.33
536
1.47
564
1.62
592
1.78
513
1.55
543
1.72
571
1.87
597
2.03
623
2.19
552
1.98
580
2.17
606
2.35
632
2.52
656
2.69
591
2.49
618
2.70
643
2.91
667
3.09
690
3.27
3 HP Standard Motor & Drive

547
569
598
621
648
679
712

0.90
1.19
1.60
1.95
2.36
2.87
3.46

.80
RPM

580
600
629
648
673
702
734

BHP

.90
RPM BHP

1.00
RPM BHP

1.03
611 1.16
640 1.29
1.35
630 1.51
660 1.67
1.77
658 1.94
684 2.11
2.12
676 2.30
704 2.49
2.55
699 2.74
723 2.93
3.05
725 3.25
748 3.46
3.65
755 3.85
776 4.06
5 HP Oversized Motor & Drive

Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

3 HP Standard Motor & Drive
3000*
3900*
4800
5400
6000
6600
7200

667
688
710
730
749
771
797

1.43
1.84
2.29
2.68
3.13
3.67
4.29

693
715
735
755
774
794
818

1.57
2.00
2.48
2.88
3.34
3.88
4.51

717
741
760
778
798
816
839

1.71
2.17
2.68
3.07
3.56
4.09
4.74

740
766
785
800
821
839
860

1.86
2.34
2.88
3.28
3.77
4.32
4.96

763
790
809
823
842
862
881

3 HP Standard Motor & High
Static Drive Accessory
2.01
784
2.16
805
2.31
2.51
812
2.68
834
2.85
3.09
832
3.29
854
3.49
3.49
845
3.71
867
3.94
3.99
863
4.20
884
4.43
4.56
884
4.80
904
5.03
5.20
902
5.45
923
5.70
5 HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 4000 CFM
• Electric heaters restricted on applications below 4000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase
Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/ccessories.
Note:
1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field
Supplied Belt may be necessary.

1.80
RPM
BHP

1.90
RPM BHP

2.00
RPM BHP

825
855
876
889
904
924
—

845
875
898
910
924
943
—

864
895
919
931
944
961
—

2.47
3.03
3.69
4.17
4.66
5.27
—

2.63
3.21
3.90
4.40
4.90
5.51
—

2.80
3.39
4.10
4.62
5.15
5.75
—

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

39

Performance
Data

(15 Ton)
High Efficiency

Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Dehumidification (Hot Gas Reheat) Option
.10
CFM

3000*
3600*
4200*
4800
5400
6000
6600
7200

RPM

.20
BHP

RPM

.30
BHP

3 HP Standard Motor w/Field
Supplied Motor Sheave (2)
295
0.26
346
0.35
333
0.40
379
0.51
373
0.60
415
0.72
414
0.84
452
0.99
455
1.14
491
1.32
497
1.51
531
1.73
540
1.96
572
2.20
583
2.50
613
2.75

RPM

BHP

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

3 HP Standard Motor w/Field
Supplied Motor Sheave (1)
391
0.45
432
0.56
420
0.62
458
0.74
452
0.85
487
0.98
487
1.13
519
1.27
524
1.48
554
1.64
561
1.91
590
2.08
601
2.42
628
2.61
641
3.02
666
3.23
3 HP Standard Motor & Drive

.80
RPM

BHP

.90
RPM BHP

3 HP Standard Motorw/Field Supplied
Low Static Drive Fan Sheave
471
0.68
506
0.80
539
0.92
569
1.04
596 1.17
494
0.87
527
1.00
559
1.14
589
1.28
617 1.43
520
1.12
551
1.26
581
1.41
610
1.57
638 1.73
550
1.43
579
1.59
607
1.74
635
1.91
660 2.08
582
1.80
610
1.98
637
2.15
662
2.33
687 2.51
617
2.26
643
2.44
667
2.63
692
2.83
715 3.02
653
2.80
678
2.99
701
3.20
724
3.41
746 3.61
690
3.44
714
3.65
736
3.86
758
4.08
778 4.30
5 HP Oversized Motor & Drive

1.00
RPM BHP

622
644
664
686
710
739
768
799

1.30
1.57
1.89
2.26
2.70
3.22
3.83
4.53

Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

3 HP Standard Motor & Drive
3000*
3600*
4200*
4800
5400
6000
6600
7200

646
669
690
711
734
761
789
819

1.43
1.72
2.06
2.44
2.89
3.42
4.05
4.76

669
694
715
735
758
782
810
840

1.56
692
1.70
714
1.84
1.88
716
2.02
738
2.18
2.23
737
2.39
760
2.57
2.63
758
2.81
780
3.00
3.09
780
3.29
801
3.49
3.63
804
3.84
824
4.05
4.26
831
4.49
850
4.71
5.00
859
5.23
879
5.47
5 HP Oversized Motor & Drive

734
759
782
802
822
845
870
898

1.98
2.34
2.74
3.19
3.69
4.27
4.94
5.72

755
778
803
823
844
865
889
—

2.13
2.49
2.92
3.38
3.91
4.49
5.18
—

775
798
822
843
864
885
908
—

2.28
2.66
3.09
3.58
4.12
4.72
5.41
—

1.80
RPM
BHP

1.90
RPM BHP

3 HP Standard Motor &
High Static Drive Accessory
793
2.42
813 2.58
817
2.82
835 2.98
842
3.28
861 3.46
864
3.78
882 3.97
883
4.33
903 4.55
904
4.95
923 5.18
927
5.65
—
—
—
—
—
—

2.00
RPM BHP

830
854
878
901
921
941
—
—

2.72
3.16
3.64
4.17
4.76
5.41
—
—

3 HP Standard Motor & High Static Drive Accessory
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 4800 CFM
• Electric heaters restricted on applications below 4800 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4800 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options accessories.
Note:
1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field
Supplied Belt may be necessary.
2. Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may be necessary. Field
Supplied Belt may be necessary.

40

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

RT-PRC002-EN

Performance
Data

(17½ Ton)
High Efficiency

Table PD-27 — Evaporator Fan Performance — 17½ Ton — TC*211C — Standard or TXV Refrigeration System
.10
CFM

3500*
4550*
5600
6300
7000
7700
8400

RPM

—
—
452
499
546
594
642

.20
BHP

—
—
1.14
1.63
2.11
2.75
3.52

RPM

—
—
487
532
578
625
671

BHP

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

RPM

—
0.90
1.45
1.94
2.52
3.21
4.03

5 HP Standard Motor
& Field Supplied Extra
Low Static Drive (2)
448
0.66
488
0.78
490
1.03
524
1.17
547
1.60
575
1.75
588
2.10
614
2.26
631
2.71
655
2.89
675
3.43
698
3.64
720
4.27
741
4.51

590
621
656
687
723
761
802

.30
BHP

—
—
1.30
1.76
2.31
2.98
3.78

RPM

—
457
518
561
606
651
697

.80
BHP

.90
RPM BHP

1.00
RPM BHP

1.20
1.64
2.26
2.79
3.44
4.23
5.16

622
649
683
711
744
782
821

652
676
710
735
766
801
840

5 HP Standard Motor &
Field Supplied Low Static Drive (1)
523
557
602
639
678
720
762

0.91
1.32
1.91
2.43
3.07
3.84
4.73

557
590
629
663
701
741
782

1.05
1.48
2.08
2.60
3.25
4.03
4.95

1.35
1.80
2.43
2.99
3.64
4.44
5.38

1.50
1.97
2.63
3.19
3.85
4.65
5.60

5 HP Standard Motor &
High Static Drive Accessory

Table PD-27— Evaporator Fan Performance — 17½ Ton — TC*211C — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

5 HP Standard Motor & Drive
3500*
4550*
5600
6300
7000
7700
8400

680
703
736
759
788
821
858

1.65
2.15
2.83
3.38
4.07
4.87
5.82

707
729
761
783
810
841
876

1.80
2.34
3.03
3.59
4.29
5.10
6.06

732
754
785
807
831
861
894

1.95
2.54
3.23
3.82
4.51
5.34
6.30

756
779
807
830
852
881
912

2.11
2.73
3.43
4.04
4.74
5.59
6.55

779
803
829
853
874
900
930

2.27
801
2.43
822
2.92
827
3.11
849
3.64
851
3.86
872
4.27
874
4.49
894
4.97
895
5.22
917
5.83
919
6.07
939
6.81
949
7.08
967
7.5 Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 5600 CFM
• Electric heaters restricted on applications below 5600 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 5600 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.

2.60
3.31
4.09
4.72
5.47
6.32
7.34

1.80
RPM
BHP

1.90
RPM BHP

2.00
RPM BHP

5 HP Standard Motor & High
Static Drive Accessory
843
2.77
863 2.94
882
871
3.50
892 3.70
913
893
4.32
914 4.56
935
913
4.95
933 5.19
952
937
5.72
957 5.97
975
958
6.58
978 6.85
997
984
7.60
1002 7.87
—

3.11
3.89
4.80
5.43
6.22
7.12
—

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

41

Performance
Data

(20 Ton)
High Efficiency

Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Standard or TXV Refrigeration System
.10
CFM

4000*
5200*
6400
7200
8000
8800
9600

RPM

.20
BHP

RPM

.30
BHP

RPM

BHP

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

5 HP Standard Motor & Field Supplied
Extra Low Static Drive (3)
—
—
—
—
428
0.69
467
0.82
504
0.95
426
0.94
463
1.09
494
1.22
524
1.35
555
1.51
506
1.64
540
1.84
570
2.03
595
2.19
620
2.34
560
2.28
592
2.50
620
2.72
646
2.92
668
3.10
616
3.07
645
3.31
672
3.56
696
3.80
719
4.02
671
4.04
698
4.29
724
4.55
747
4.83
769
5.10
728
5.19
753
5.46
776
5.74
799
6.04
820
6.34
5 HP Standard Motor & Drive
(2)

.80
RPM

5 HP Standard Motor & Field
Supplied Low Static Drive (1)
538
1.08
572
1.23
603
585
1.67
614
1.83
642
644
2.51
669
2.69
693
690
3.27
711
3.45
733
739
4.22
759
4.41
778
790
5.34
808
5.56
826
840
6.63
859
6.90
876
7.5 HP Oversized Motor & Drive

BHP

.90
RPM BHP

1.00
RPM BHP

1.38
2.00
2.89
3.65
4.60
5.77
7.14

632
670
717
755
797
844
893

660
696
741
777
817
861
909

1.55
2.17
3.09
3.86
4.81
5.98
7.37

1.71
2.35
3.29
4.08
5.03
6.20
7.59

Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

1.80
RPM
BHP

5 HP Standard Motor & Drive
4000*
5200*
6400
7200
8000
8800
9600

688
722
765
799
837
879
925

1.87
2.54
3.49
4.31
5.26
6.43
7.83

714
2.03
739
2.20
747
2.73
771
2.93
788
3.70
810
3.91
820
4.53
841
4.76
857
5.51
876
5.76
897
6.67
915
6.93
941
8.07
958
8.32
7.5 HP Oversized Motor & Drive

764
795
832
862
896
933
974

2.36
3.14
4.12
4.99
6.01
7.19
8.58

787
817
854
883
915
951
—

2.53
3.35
4.34
5.22
6.26
7.46
—

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 6400 CFM
• Electric heaters restricted on applications below 6400 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 6400 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt
may be necessary.
3. Field Supplied Fan Sheave B5V200 and Motor Sheave IVP34 required. Field Supplied Belt may
be necessary.

810
839
875
902
934
969
—

2.70
3.56
4.57
5.46
6.52
7.74
—

831
861
896
922
953
986
—

2.87
3.77
4.80
5.69
6.77
8.01
—

852
882
916
942
971
—
—

1.90
RPM BHP

2.00
RPM BHP

5 HP Standard Motor
& High Static Drive Accessory
3.05
873 3.23
892 3.41
3.98
902 4.19
923 4.41
5.04
936 5.29
955 5.54
5.94
961 6.19
980 6.44
7.03
989 7.29
—
—
—
—
—
—
—
—
—
—
—
—

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

*Indicates both downflow and horizontal units.

42

RT-PRC002-EN

Performance
Data

(20 Ton)
High Efficiency

Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Dehumidification (Hot Gas Reheat) Option
.10
CFM

4000*
4800*
5600*
6400
7200
8000
8800
9600

RPM

—
414
469
525
583
641
699
758

.20
BHP

—
0.84
1.25
1.80
2.50
3.37
4.42
5.67

RPM

—
452
504
558
613
669
725
782

.30
BHP

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

BHP

RPM

—
0.99
1.45
2.03
2.75
3.64
4.72
6.00

5 HP Standard Motor & Field
Supplied Fan Sheave (1)
441
0.77
477
0.90
487
1.13
519
1.27
536
1.61
566
1.78
588
2.24
615
2.42
641
3.02
666
3.23
695
3.93
719
4.21
750
5.03
773
5.35
805
6.32
827
6.68

511
550
594
641
690
742
794
848

.80
RPM

BHP

.90
RPM BHP

1.00
RPM BHP

5 HP Standard Motor & Drive & Field Supplied
5 HP Standard
Low Static Fan Sheave
Motor & Drive
1.03
543
1.17
573
1.32
603
1.47
631 1.63
658
1.43
579
1.59
607
1.74
635
1.91
660 2.08
686
1.95
620
2.12
647
2.30
672
2.49
696 2.67
720
2.61
666
2.80
689
3.00
713
3.20
736 3.41
758
3.44
714
3.65
736
3.86
758
4.08
778 4.30
799
4.45
763
4.67
785
4.91
805
5.14
825 5.38
844
5.65
815
5.91
835
6.15
854
6.41
873 6.66
892
7.04
867
7.35
886
7.63
904
7.90
923 8.18
941
7.5 HP Oversized Motor & Drive
(3)

1.78
2.26
2.87
3.62
4.53
5.62
6.93
8.46

5 HP Standard Motor & High StaticDrive

Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Continued
CFM

1.10
RPM
BHP

4000*
4800*
5600*
6400
7200
8000
8800
9600

684
711
743
779
819
863
909
—

1.20
RPM
BHP

1.30
RPM
BHP

External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

1.80
RPM
BHP

1.90
RPM BHP

753
780
809
841
879
918
961
—

834
864
890
919
952
988
—
—

5 HP Standard Motor
& High Static Drive
852 3.29
870 3.47
882 3.97
901 4.17
910 4.75
929 4.98
938 5.66
956 5.90
968 6.70
987 6.97
—
—
—
—
—
—
—
—
—
—
—
—

5 HP Standard Motor & Drive
1.94
2.44
3.06
3.82
4.76
5.87
7.19
—

708
735
765
800
840
881
927
—

2.10
2.63
3.26
4.04
5.00
6.12
7.46
—

731
758
787
821
859
900
944
—

2.27
2.81
3.46
4.26
5.23
6.38
7.73
—

2.43
3.00
3.67
4.48
5.47
6.64
8.01
—

775
802
830
861
898
936
978
—

2.60
3.19
3.88
4.70
5.72
6.90
8.29
—

795
823
850
881
916
954
994
—

2.77
3.38
4.09
4.93
5.96
7.16
8.56
—

814
843
871
899
933
971
—
—

2.94
3.58
4.31
5.16
6.19
7.42
—
—

3.12
3.78
4.53
5.41
6.46
7.69
—
—

2.00
RPM BHP

7.5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 6400 CFM
• Electric heaters restricted on applications below 6400 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 6400 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Motor Sheave IVP34 Required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
3. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt
may be necessary.

RT-PRC002-EN

Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.

43

Performance
Data

(25 Ton)
High Efficiency

Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Standard Refrigeraton System
.10

.20
RPM

.30
BHP

RPM

BHP

External Static Pressure (Inches of Water)
.40
.50
.60
.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP

CFM

RPM

BHP

5000*
6500*
7000*
7500*
8000
8500
9000
9500
10000
10500
11000

—
—
—
582
616
650
685
721
756
791
827

7.5 HP Standard Motor & Field Supplied Extra Low Static Drive (1)
—
—
—
—
—
—
—
—
—
—
—
—
576
2.11
601
2.27
625
2.43
—
579
2.32
608
2.54
633
2.73
656
2.89
2.59
611
2.78
640
3.02
665
3.24
687
3.43
3.07
645
3.31
672
3.56
696
3.80
719
4.02
3.66
678
3.90
704
4.16
728
4.43
750
4.68
4.31
712
4.56
737
4.83
760
5.12
782
5.39
5.04
746
5.30
770
5.58
792
5.88
814
6.18
5.85
780
6.12
803
6.41
825
6.72
846
7.04
6.74
814
7.03
836
7.33
858
7.64
878
7.98
7.71
849
8.02
870
8.33
891
8.63
—
—
7.5 HP Standard Motor & Drive

576
649
678
708
739
771
802
834
866
898
—

1.56
2.59
3.06
3.61
4.22
4.90
5.65
6.46
7.35
8.31
—

.80
RPM

BHP

.90
RPM BHP

1.00
RPM BHP

7.5 HP Standard Motor & Low Static Drive Accessory
606
1.71
635
1.88
663 2.05
690 2.22
674
2.78
698
2.97
722 3.18
746 3.38
700
3.25
723
3.44
745 3.65
768 3.87
729
3.79
749
3.98
770 4.19
792 4.41
759
4.41
778
4.60
797 4.81
817 5.03
790
5.10
808
5.31
826 5.52
844 5.74
821
5.88
839
6.09
856 6.30
873 6.53
853
6.72
870
6.96
887 7.18
903 7.41
884
7.64
902
7.90
918 8.14
934 8.38
916
8.62
—
—
—
—
—
—
—
—
—
—
—
—
—
—

7.5 HP Standard Motor & Higher Static Drive Accessory

Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Continued
CFM

1.10
RPM
BHP

1.20
RPM
BHP

5000*
6500*
7000*
7500*
8000
8500
9000
9500
10000
10500
11000

716
769
790
813
837
863
890
919
949
—
—

741
792
812
833
857
881
908
936
—
—
—

2.41
3.59
4.09
4.65
5.26
5.97
6.76
7.64
8.62
—
—

External Static Pressure (Inches of Water)
1.30
1.40
1.50
RPM
BHP
RPM
BHP
RPM
BHP

7.5 HP Standard Motor & Drive
2.60
765
2.80
789
3.80
814
4.01
836
4.31
833
4.53
854
4.88
854
5.12
874
5.51
876
5.76
896
6.21
900
6.46
919
7.00
925
7.25
943
7.88
952
8.13
969
—
—
—
—
—
—
—
—
—
—
—
—

3.00
4.22
4.76
5.36
6.01
6.73
7.52
8.40
—
—
—

812
857
875
894
915
937
961
985
—
—
—

3.20
4.44
4.99
5.59
6.26
6.99
7.79
8.67
—
—
—

7.5 HP Standard Motor & High Static Drive Accessory
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM),
reference Table PD-32.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM),
reference Table PD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
*Unit applications below 8000 CFM
• Electric heaters restricted on applications below 8000
CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat
and Crankcase Heaters are required on applications
below 8000 CFM.
Notes:
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to
other options/accessories.

Factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range
of our fan motors as shown in our tabular
data will not result in nuisance tripping or
premature motor failure. Our product’s
warranty will not be affected.

*Indicates both downflow and horizontal units.

44

RT-PRC002-EN

Performance
Data

(12½-25 Ton)

Table PD-31— Standard Motor & Drive/Fan Speed (Rpm)
Tons
12½
15

17½
20
25

Unit
Model No.
TC*150D3,4,W, TC*151C3,4,W
TC*150DK
TC*180B3,4,W
TC*180BK
TC*181C3,4,W
TC*210C3,4,W
TC*210CK
TC*211C3,4,W
TC*240B3,4,W,TC*241C3,4,W
TC*240BK
TC*300B/301C3,4,W
TC*300BK

6Turns
Open
640
705
679
N/A
560
869
869
615
615
590
705
701

5Turns
Open
680
756
721
680
600
923
924
659
659
627
742
738

4Turns
Open
720
806
764
733
640
978
978
703
703
664
779
775

3Turns
Open
760
857
806
785
680
1032
1032
747
747
701
817
812

2Turns
Open
800
907
849
837
720
1087
1087
791
791
738
854
849

1Turn
Open
840
957
891
889
760
1141
1141
835
835
775
891
886

Closed
N/A
N/A
N/A
941
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

Factory set at 3 turns open.

Table PD-32— Standard Motor & High Static Drive Accessory/Fan Speed (Rpm)
Tons
12½
15
17½
20
25

Unit
Model No.
TC*151C3,4,W
TC*180B3,4,W
TC*181B3,4,W
TC*211C3,4,W
TC*240B/241C3,4,W
TC*300B/301C3,4,W

6Turns
Open
807
806
640
835
835
816

5Turns
Open
857
849
680
879
879
853

4Turns
Open
908
891
720
923
923
890

3Turns
Open
958
934
760
967
967
928

2Turns
Open
1009
976
800
1011
1011
965

1Turn
Open
1059
1019
840
1055
1055
1002

Closed
N/A
N/A
N/A
N/A
N/A
N/A

Table PD-33— Oversized Motor & Drive/Fan Speed (Rpm)
Tons
12½
15
17½
20

Unit
Model No.
TC*150D,151C3,4,W
TC*180B3,4,W
TC*181C3,4,W
TC*210C3,4,W
TC*211C3,4,W

6Turns
Open
869
806
705
949
816

5Turns
Open
923
856
755
1008
853

4Turns
Open
978
907
806
1068
890

3Turns
Open
1032
957
856
1127
928

2Turns
Open
1087
1008
907
1187
965

1Turn
Open
1141
1058
957
1246
1002

Closed
N/A
N/A
N/A
N/A
N/A

TC*240B/241C3,4,W

816

853

890

928

965

1002

N/A

Closed

Table PD-34 — Standard Motor & Low Static Fan Drive
Tons

Unit
Model No.

6Turns
Open

5Turns
Open

4Turns
Open

3Turns
Open

2Turns
Open

1Turn
Open

17½

TC*210C3,4,W

705

755

806

856

907

957

25

N/A

TC*300B/301C3,4,W

594

631

668

705

742

779

N/A

*Indicates both downflow and horizontal units.

RT-PRC002-EN

45

Performance
Data

(12½-25 Ton)

Table PD-35 — Static Pressure Drops Through Accessories (Inches Water Column)

Tons

Unit
Model No.
TC*150D, TCH151C

12½
TCD151C

TC*180B

15

TCD181C

TCH181C

TC*210C

17½

TCD211C

TCH211C

TCD240B

20

TCD241C

TCH240B, TCH241C

TCD300B

25

TCD301C

TCH300B, TCH301C

Standard
Through
2 Inch
CFM
Filters1 Reheat Coil Pleated Filters4
4000
0.05
—
0.08
5000
0.07
—
0.11
6000
0.10
—
0.15
2500
0.02
0.01
0.03
4000
0.05
0.03
0.08
5000
0.07
0.05
0.11
6000
0.10
0.06
0.15
4800
0.07
—
0.10
6000
0.10
—
0.15
7200
0.15
—
0.19
3000
0.02/0.01
0.01
0.03/0.02
4800
0.04/0.03
0.02
0.07/0.06
6000
0.06/0.05
0.03
0.10/0.09
7200
0.09/0.07
0.04
0.13/0.11
4800
0.04/0.03
—
0.07/0.06
6000
0.06/0.05
—
0.10/0.09
7200
0.09/0.07
—
0.13/0.11
5600
0.09
—
0.13
7000
0.14
—
0.18
8400
0.20
—
0.24
3500
0.02/0.02
—
0.03/0.03
5600
0.06/0.05
—
0.09/0.08
7000
0.09/0.07
—
0.13/0.11
8400
0.12/0.10
—
0.17/0.14
5600
0.06/0.05
—
0.09/0.08
7000
0.09/0.07
—
0.13/0.11
8400
0.12/0.10
—
0.17/0.14
6400
0.07
—
0.11
8000
0.11
—
0.15
9600
0.16
—
0.20
4000
0.03
0.02
0.04
6400
0.07
0.04
0.11
8000
0.11
0.05
0.15
9600
0.16
0.07
0.20
6400
0.06
—
0.10
8000
0.09
—
0.13
9600
0.13
—
0.17
7000
0.09
—
0.13
9000
0.14
—
0.18
11000
0.21
—
0.25
5000
0.04
—
0.06
7000
0.09
—
0.13
9000
0.14
—
0.18
11000
0.21
—
0.25
7000
0.07
—
0.11
9000
0.11
—
0.15
11000
0.17
—
0.22

Economizer with
OA/RA Dampers2
100% OA
100% RA
0.19
0.02
0.26
0.03
0.33
0.04
0.07
0.01
0.19
0.02
0.26
0.03
0.33
0.04
0.25
0.03
0.33
0.04
0.40
0.05
0.07
0.03
0.14
0.03
0.20
0.04
0.27
0.05
0.14
0.03
0.20
0.04
0.27
0.05
0.30
0.04
0.39
0.05
0.47
0.06
0.09
0.03
0.18
0.04
0.26
0.04
0.35
0.06
0.18
0.04
0.26
0.04
0.35
0.06
0.22
0.04
0.32
0.05
0.44
0.07
0.11
0.03
0.22
0.04
0.32
0.05
0.44
0.07
0.22
0.04
0.32
0.05
0.44
0.07
0.26
0.04
0.40
0.07
0.57
0.10
0.15
0.03
0.26
0.04
0.40
0.07
0.57
0.10
0.26
0.04
0.40
0.07
0.60
0.10

5-12
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

14-27
0.03
0.04
0.06
*
0.03
0.04
0.06
0.04
0.06
0.09
*
0.04
0.06
0.09
0.04
0.06
0.09
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

Electric Heater
Accessory (KW)3
36
54
0.03
0.04
0.05
0.06
0.07
0.09
*
*
0.03
0.04
0.05
0.06
0.07
0.09
0.04
0.05
0.07
0.08
0.10
0.12
*
*
0.04
0.05
0.07
0.08
0.10
0.12
0.04
0.05
0.07
0.08
0.10
0.12
0.06
0.07
0.10
0.11
0.15
0.17
*
*
0.05
0.06
0.08
0.09
0.12
0.13
0.05
0.06
0.08
0.09
0.12
0.13
0.06
0.08
0.10
0.12
0.14
0.17
*
*
0.06
0.08
0.10
0.12
0.14
0.17
0.06
0.08
0.10
0.12
0.14
0.17
0.08
0.10
0.13
0.15
0.18
0.22
*
*
0.08
0.10
0.13
0.15
0.18
0.22
0.08
0.10
0.13
0.15
0.18
0.22

72
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
*
0.07
0.11
0.16
0.07
0.11
0.16
0.09
0.14
0.20
*
0.09
0.14
0.20
0.09
0.14
0.20
0.11
0.18
0.26
*
0.11
0.18
0.26
0.11
0.18
0.26

Notes:
1. Tested with: 2” filters 12½-25 tons
2. OA = Outside Air and RA = Return Air.
3. Nominal KW ratings at 240, 480, 600 volts.
4. Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
*Heaters not permitted at airflows below 320 cfm/ton.

*Indicates both downflow and horizontal units.

46

RT-PRC002-EN

Performance
Data

(12½-25 Ton)

Table PD-36 — Auxiliary Electric Heat Capacity
Unit
Model No.

KW
Input1

Total2
MBH
Output1

No. of
Stages

KW
Input1

MBH
Output1

KW
Input1

Stage 2
MBH
Output1

12½-15

TC*150D3,D4,DW,DK
TC*180B3,B4,BW,BK
TC*151 or 181C3,C4,CW

18.00
27.004
36.00
54.00

61.47
92.15
122.94
184.41

1
2
2
2

18.00
9.00
18.00
36.00

61.47
30.72
61.47
122.94

—
18.00
18.00
18.00

—
61.43
61.47
61.47

17½, 20, 25

TC*210C3,C4,CW,CK
TC*240, 300B3,B4,BW,BK
TC*211, 241, 301C3,C4,CW

36.00
54.00
72.003

122.94
184.41
245.88

2
2
2

18.00
36.00
36.00

61.47
122.94
122.94

18.00
18.00
36.00

61.47
61.47
122.94

Tons

Stage1

Notes:
2
1. Does not include indoor fan power or heat.
Voltage
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =
x rated cap.
Rated Voltage
3. Not available on TC*210C.
4. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.

(

)

Table PD-37 — Electric Heater Voltage
Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal
Voltage

Distribution
Voltage

Capacity
Multiplier

240

208
230
240

0.75
0.92
1.00

480

440
460
480

0.84
0.94
1.00

600

540
575
600

0.81
0.92
1.00

Table PD-38 — Air Temperature Rise Across Electric Heaters (Degree F)

KW
9.00
17.30
18.00
27.00
36.00
54.00
72.002

Stages
1
1
1
2
2
2
2

12½ Ton
5000 CFM

15 Ton
6000 CFM

17½ Ton
7000 CFM

20 Ton
8000 CFM

25 Ton
9000 CFM

Three Phase
TC*150
TC*151
—
—
11.4
—
22.8
34.1
—

Three Phase
TC*180
TC*181
—
—
9.5
14.22
19.0
28.5
—

Three Phase
TC*210
TC*211
—
—
—
12.221
16.3
24.4
32.5

Three Phase
TC*240
TC*241
—
—
—
10.72
14.2
21.3
28.5

Three Phase
TC*300
TC*301
—
—
—
9.52
12.6
19.0
25.3

For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
KW x 3413
Temp. Rise across Elect. Htr =
1.08 x CFM
Notes:
1. Not available on TC*210 model.
2. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.

RT-PRC002-EN

47

Performance
Data

Table PD-39— Hot Gas Reheat Temperature Rise1,2,3
Tons

12½

Tons

15

Tons

20

SCFM
2500
3000
3500
4000
4500
5000
5500
6000
SCFM
3000
3600
4200
4800
5400
6000
6600
7200
SCFM
4000
4800
5600
6400
7200
8000
8800
9600

Leaving Evaporator Dry Bulb [F]1
35
40
45
50
23.4
23.8
25.0
26.9
21.4
21.6
22.5
24.0
19.5
19.7
20.4
21.5
17.8
18.1
18.6
19.6
16.3
16.7
17.3
18.1
14.9
15.5
16.2
17.1
13.5
14.4
15.3
16.2
12.1
13.4
14.6
15.7
35
40
45
50
34.4
36.7
38.9
41.2
29.3
31.2
33.1
35.0
25.4
27.0
28.6
30.2
22.3
23.7
25.1
26.5
19.9
21.2
22.4
23.7
18.0
19.1
20.3
21.4
16.4
17.5
18.6
19.6
15.1
16.1
17.1
18.1
35
40
45
50
22.0
22.5
23.6
25.4
19.1
19.8
20.9
22.3
16.6
17.4
18.4
19.5
14.7
15.5
16.3
17.2
13.5
14.1
14.7
15.4
12.9
13.2
13.7
14.2
12.5
12.9
13.3
13.7
12.4
12.8
13.1
13.5

55
29.5
26.0
23.1
20.9
19.2
18.0
17.2
16.7
55
43.5
36.9
31.9
27.9
24.9
22.5
20.7
19.1
55
27.7
24.0
20.9
18.2
16.2
14.8
14.2
13.9

60
32.9
28.7
25.2
22.5
20.5
19.2
18.1
17.6
60
45.8
38.8
33.5
29.3
26.2
23.7
21.7
20.1
60
30.6
26.1
22.4
19.3
17.0
15.5
14.8
14.5

65
37.0
31.9
27.7
24.5
22.1
20.4
19.1
18.3
65
48.1
40.8
35.1
30.7
27.4
24.8
22.8
21.1
65
34.0
28.5
24.0
20.6
17.9
16.2
15.4
15.0

Notes:
1. Temperature does not account for indoor fan heat.
2. 70 deg OD Ambient Temperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.

48

RT-PRC002-EN

Controls

Field Installed Control Options
Zone Sensors
Zone sensors are the building occupant’s
comfort control devices.They replace the
conventional electro-mechanical
thermostats.The following zone sensor
options are available for Voyager units
with the ReliaTel™ control:
Manual Changeover
Heat, Cool or Off
System Switch. Fan
Auto or Off Switch.
One temperature
setpoint lever.

Manual/Automatic Changeover
Auto, Heat, Cool or Off System Switch.
Fan Auto or Off
Switch.Two
temperature
setpoint levers.
Optional Status
Indication LED lights,
System On, Heat,
Cool, or Service.

Remote Sensor
Sensor(s) available
for all zone sensors to
provide remote
sensing capabilities.

Dual Thermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.

RT-PRC002-EN

Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone
sensors.This
sensor includes a
digital display of
set point
adjustment and
space temperature
in F (Fahrenheit) or
C (Celsius).
Includes FAN and
SYSTEM buttons
(supports the
service functions of
the standard
sensor). E-squared memory stores last
programmed set points. Requires 24 VAC
(Volts AC).This sensor should be utilized
with ReliaTel controls.
Programmable Night Setback
Auto or manual changeover with sevenday programming. Keyboard selection

of Heat, Cool, Fan, Auto, or On. All
programmable sensors have System On,
Heat, Cool, Service LED/indicators as
standard. Night Setback Sensors have
one (1) Occupied, one (1) Un-occupied,
and two (2) Override programs per day.
Integrated
ComfortTM
System
Sensor(s)
available with
optional
temperature
adjustment and
override buttons
to provide central
control through a
Trane Integrated
Comfort system.

CO2 Sensing The CO2 sensor has the
ability to monitor space occupancy levels
within the
building by
measuring the
parts per million
of CO2 (Carbon
Dioxide) in the air.
As the CO2 levels
increase, the
outside air
damper
modulates to
meet the CO2 space ventilation
requirements.The CO2 sensor kit is
available as a field installed accessory.
Economizer Controls
The standard equipment offering is a
fixed dry bulb changeover control. In
addition, there are two optional controls,
Enthalpy and Differential Enthalpy
Control.
Enthalpy Control
Replaces the dry bulb control with a wet
bulb changeover controller which has a
fully adjustable set point. Enthalpy control
offers a higher level of comfort control,
along with energy savings potential, than
the standard dry bulb control. This is due
to the additional wet bulb sensing
capability.
Differential Enthalpy
Replaces the standard dry bulb control
with two enthalpy sensors that compare
total heat content of the indoor air and
outdoor air to determine the most
efficient air source.This control option
offers the highest level of comfort control,
plus energy efficiency, available.
Remote Potentiometer
Minimum position setting of economizer
can be remotely adjusted with this
accessory.
Differential Pressure Switches
This factory or field-installed option
allows individual fan failure and dirty filter
indication. The fan failure switch will
disable all unit functions and “flash” the
Service LED on the zone sensor. The dirty
filter switch will light the Service LED on
the zone sensor and will allow continued
unit operation.
Trane Communication Interface (TCI)
This factory or field-installed microprocessor interface allows the unit to
communicate toTrane’s Integrated
Comfort system.
49

Electrical
Data

(Standard Efficiency)

Table ED-1 — Unit Wiring — Standard Efficiency

Tons
12½

15

17½

20

25

Standard Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size or Maximum
Ampacity2
Circuit Breaker1

Oversize Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size or Maximum
Ampacity2
Circuit Breaker1

Unit
Model No.

Unit
Operating
Voltage Range

TC*150D3
TC*150D4
TC*150DW
TC*150DK
TC*180B3
TC*180B4
TC*180BW
TC*180BK

187-253
414-506
518-633
342-418
187-253
414-506
517-633
342-418

63
33
26
43
78
39
31
50

80
40
30
50
90
50
40
60

69
36
28
–
84
42
33
–

80
40
35
–
100
50
40
–

TC*210C3
TC*210C4
TC*210CW
TC*210CK
TC*240B3
TC*240B4
TC*240BW
TC*240BK

187-253
414-506
517-633
342-418
187-253
414-506
517-633
342-418

88
44
35
57
100
50
40
65

100
50
45
70
125
60
45
80

96
47
38
–
107
54
43
–

125
60
45
–
125
60
50
–

TC*300B3
TC*300B4
TC*300BW
TC*300BK

187-253
414-506
517-633
342-418

118
58
46
70

150
70
50
80

–
–
–
–

–
–
–
–

Notes:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

*Indicates both downflow and horizontal units.

50

RT-PRC002-EN

Electrical
Data

(Standard Efficiency)

Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only)
Control
Stages

Oversize Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

Heater
Model No.

12½

TCD150D3

AYDHTRF318A
AYDHTRF336A
AYDHTRF354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

63/68
108/122
154/176

80/80
110/125
175/200

69/76
115/130
162/184

80/80
125/150
175/200

15

TCD180B3

AYDHTRK318A
AYDHTRK336A
AYDHTRK354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

78/78
108/122
154/176

100/100
110/125
175/200

84/84
115/130
162/184

100/100
125/150
175/200

AYDHTRL336A
AYDHTRL354A

27.0/36.0
40.5/54.0

2
2

115/130
162/184

125/150
175/200

125/139
171/193

125/150
175/200

Tons

Heater
KW Rating1

Standard Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

To Use
With

208/230 Volts Three Phase

17½

TCD210C3

20

TCD240B3

AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

25

TCD300B3

AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

125/139
171/193
218/247

150/150
175/200
225/250

—
—
—

—
—
—

12½

TCD150D4

AYDHTRL418A
AYDHTRK436A
AYDHTRK454A

18.0
36.0
54.0

1
2
2

34
61
88

40
70
90

37
64
91

40
70
100

15

TCD180B4

AYDHTRL418A
AYDHTRK436A
AYDHTRK454A

18.0
36.0
54.0

1
2
2

39
61
88

50
70
90

42
64
91

50
70
100

AYDHTRL436A
AYDHTRL454A

36.0
54.0

2
2

64
91

70
100

68
95

70
100

460 Volts Three Phase

17½

TCD210C4

20

TCD240B4

AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

36.0
54.0
72.0

2
2
2

64
91
118

70
100
125

68
95
123

70
100
125

25

TCD300B4

AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

36.0
54.0
72.0

2
2
2

68
95
123

70
100
125

—
—
—

—
—
—

12½

TCD150DW

AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A

18.0
36.0
54.0

1
2
2

27
49
70

30
50
70

30
51
73

35
60
80

15

TCD180BW

AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A

18.0
36.0
54.0

1
2
2

31
49
70

40
50
70

33
51
73

40
60
80

AYDHTRMW36A
AYDHTRLW54A

36.0
54.0

2
2

51
73

60
80

55
77

60
80

575 Volts Three Phase

17½

TCD210CW

20

TCD240BW

AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A

36.0
54.0
72.0

2
2
2

51
73
95

60
80
100

55
77
98

60
80
100

25

TCD300BW

AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A

36.0
54.0
72.0

2
2
2

55
77
98

60
80
100

—
—
—

—
—
—

Notes:
1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit.
2. HACR type circuit breaker per NEC.

RT-PRC002-EN

51

Electrical
Data

(Standard Efficiency)

Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only), continued

Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Control
Stages

Standard Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

Oversize Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

380 Volts Three Phase
12½

TCD150DK

AYDHTRL418A
AYDHTRK436A
AYDHTRK454A

15

TCD180BK

AYDHTRL418A
AYDHTRK436A
AYDHTRK454A

11.3
22.6
33.8

1
2
2

50
55
76

60
60
80

—
—
—

—
—
—

AYDHTRL436A
AYDHTRL454A

22.6
33.8

2
2

60
81

70
90

—
—

—
—

17½

TCD210CK

11.3
22.6
33.8

1
2
2

43
55
76

50
60
80

—
—
—

—
—
—

20

TCD240BK

AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

22.6
33.8
45.1

2
2
2

65
81
103

80
90
110

—
—
—

—
—
—

25

TCD300BK

AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

22.6
33.8
45.1

2
2
2

70
81
103

80
90
100

—
—
—

—
—
—

Notes:
1. Heater kw ratings are at 380V for 380 unit.
2. HACR type circuit breaker per NEC.

52

RT-PRC002-EN

Electrical
Data

(Standard Efficiency)

Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Horizontal Only)

Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Standard Indoor Motor
Max Fuse Size or
MCA Max Circuit Breaker2

Control
Stages

Oversize Indoor Motor
Max Fuse Size or
MCA Max Circuit Breaker2

208/230 Volts Three Phase
12½

TCH150D3

AYHHTRN318A
AYHHTRN336A
AYHHTRN354A

15

TCH180B3

AYHHTRN318A
AYHHTRP336A
AYHHTRP354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

78/78
108/122
154/176

100/100
110/125
175/200

84/84
115/130
162/184

100/100
125/150
175/200

AYHHTRQ336A
AYHHTRQ354A

27.0/36.0
40.5/54.0

2
2

115/130
162/184

125/150
175/200

125/139
171/193

125/150
175/200

17½

TCH210C3

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

63/68
108/122
154/176

80/80
110/125
175/200

69/76
115/130
162/184

80/80
125/150
175/200

20

TCH240B3

AYHHTRN336A
AYHHTRN354A
AYHHTRN372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

25

TCH300B3

AYHHTRN336A
AYHHTRN354A
AYHHTRN372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

132/139
171/193
218/247

150/150
175/200
225/250

—
—
—

—
—
—

12½

TCH150D4

AYHHTRN418A
AYHHTRN436A
AYHHTRP454A

18.0
36.0
54.0

1
2
2

34
61
88

40
70
90

37
64
91

40
70
100

15

TCH180B4

AYHHTRN418A
AYHHTRP436A
AYHHTRP454A

18.0
36.0
54.0

1
2
2

37
61
88

50
70
90

42
64
91

50
70
100

AYHHTRQ436A
AYHHTRQ454A

36.0
54.0

2
2

64
91

70
100

68
95

70
100

460 Volts Three Phase

17½

TCH210C4

20

TCH240B4

AYHHTRN436A
AYHHTRN454A
AYHHTRN472A

36.0
54.0
72.0

2
2
2

64
91
118

70
100
125

68
95
123

70
100
125

25

TCH300B4

AYHHTRN436A
AYHHTRN454A
AYHHTRN472A

36.0
54.0
72.0

2
2
2

68
95
123

70
100
125

—
—
—

—
—
—

12½

TCH150DW

AYHHTRNW18A
AYHHTRPW36A
AYHHTRPW54A

18.0
36.0
54.0

1
2
2

27
49
70

30
50
70

30
51
73

35
60
80

15

TCH180BW

AYHHTRNW18A
AYHHTRPW36A
AYHHTRPW54A

18.0
36.0
54.0

1
2
2

31
49
70

40
50
70

33
51
73

40
60
80

AYHHTRPW36A
AYHHTRQW54A

36.0
54.0

2
2

51
73

60
80

55
77

60
80

575 Volts Three Phase

17½

TCH210CW

20

TCH240BW

AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A

36.0
54.0
72.0

2
2
2

51
73
95

60
80
100

55
77
98

60
80
100

25

TCH300BW

AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A

36.0
54.0
72.0

2
2
2

55
77
98

60
80
100

—
—
—

—
—
—

Notes:
1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit..
2. HACR type circuit breaker per NEC.

RT-PRC002-EN

53

Electrical
Data

(Standard Efficiency)

Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Horizontal Only) continued
Control
Stages

Oversize Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

Heater
Model No.

12½

TCD150DK

AYDHTRL418A
AYDHTRK436A
AYDHTRK454A

11.3
22.6
33.8

1
2
2

43
55
76

50
60
80

—
—
—

—
—
—

15

TCD180BK

AYDHTRL418A
AYDHTRK436A
AYDHTRK454A

11.3
22.6
33.8

1
2
2

50
55
76

60
60
80

—
—
—

—
—
—

AYDHTRL436A
AYDHTRL454A

22.6
33.8

2
2

60
81

70
90

—
—

—
—

Tons

Heater
KW Rating1

Standard Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

To Use
With

380 Volts Three Phase

17½

TCD210CK

20

TCD240BK

AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

22.6
33.8
45.1

2
2
2

65
81
103

80
90
110

—
—
—

—
—
—

25

TCD300BK

AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

22.6
33.8
45.1

2
2
2

70
81
103

80
90
100

—
—
—

—
—
—

Notes:
1. Heater kw ratings are at 380V for 380 unit.
2. HACR type circuit breaker per NEC.

54

RT-PRC002-EN

Electrical
Data

(Standard Efficiency)

Table ED-4— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency
Compressor Motors
Tons

12½

15

17½

20

25

Unit
Model No.

No.

Volts

Phase

HP2

RPM

Amps1
RLA
LRA

TC*150D3
TC*150D4
TC*150DW
TC*150DK

2
2
2
2

208-230
460
575
380

3
3
3
3

6.00
6.00
6.00
6.0

3450
3450
3450
3450

20.4
10.8
8.3
13.1

TC*180B3
TC*180B4
TC*180BW
TC*180BK

2
2
2
2

208-230
460
575
380

3
3
3
3

9.30/5.10
9.30/5.10
9.30/5.10
9.3/5.1

TC*210C3
TC*210C4
TC*210CW
TC*210CK

2
2
2
2

208-230
460
575
380

3
3
3
3

9.3/6.0
9.3/6.0
9.3/6.0
9.3/6.0

TC*240B3
TC*240B4
TC*240BW
TC*240BK

2
2
2
2

208-230
460
575
380

3
3
3
3

9.30
9.30
9.30
9.3

3450
3450
3450
3450

TC*300B3
TC*300B4
TC*300BW
TC*300BK

2
2
2
2

208-230
460
575
380

3
3
3
3

10.00
10.00
10.00
10.0

3450
3450
3450
3450

No.

Condenser Fan Motors
Amps1
Phase
HP
FLA
LRA

156
75
54
70

2
2
2
2

1
1
1
1

.50
.50
.50
.50

3.2
1.6
1.3
1.9

8.8
3.8
3.2
5.2

3450 31.9/20.7
3450 16.3/10.0
3450 13.1/7.4
3450 19.7/12.1

253/128
113/63
85/49
125/64

2
2
2
2

1
1
1
1

.50
.50
.50
.50

3.2
1.6
1.3
1.9

8.8
3.8
3.2
5.2

3450 31.5/20.8
3450 15.9/10.0
3450 12.8/8.2
3450 19.2/12.1

253/156
113/75
85/54
125/70

2
2
2
2

1
1
1
1

1.00
1.00
1.00
1.00

5.5
2.9
2.0
3.5

18.3
9.3
5.7
8.5

31.7
16.2
13.0
19.6

253
113
85
125

2
2
2
2

1
1
1
1

1.00
1.00
1.00
1.00

5.5
2.9
2.0
3.5

18.3
9.3
5.7
8.5

36.6
17.9
14.9
21.7

278
124
92
137

2
2
2
2

1
1
1
1

1.00
1.00
1.00
1.00

5.5
2.9
2.0
3.5

18.3
9.3
5.7
8.5

Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

55

Electrical
Data

(High Efficiency)

Table ED-5 — Unit Wiring - High Efficiency - Standard Refrigeration System
Standard Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size or Maximum
Ampacity2
Circuit Breaker1

Oversize Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size or Maximum
Ampacity2
Circuit Breaker1

Unit
Model No.

Unit
Operating
Voltage Range

12½

TC*151C3
TC*151C4
TC*151CW

187-253
414-506
517-633

64
31
25

80
40
30

70
34
28

90
40
35

15

TC*181C3
TC*181C4
TC*181CW

187-253
414-506
517-633

74
36
29

90
50
40

80
38
31

100
50
40

17½

TC*211C3
TC*211C4
TC*211CW

187-253
414-506
517-633

91
44
35

110
60
45

98
48
38

125
60
50

20

TC*241C3
TC*241C4
TC*241CW

187-253
414-506
517-633

99
50
40

125
60
50

107
54
43

125
60
50

25

TC*301C3
TC*301C4
TC*301CW

187-253
414-506
517-633

120
58
47

150
70
60

N/A
N/A
N/A

N/A
N/A
N/A

Tons

Notes:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

Table ED-6— Unit Wiring - High Efficiency - TXV/Face-Split Evaporator Coil Option (Downflow Only)

Tons
12½

15

17½

20

25

Unit
Model No.
TCD151C3
TCD151C4
TCD151CW
TCD181C3
TCD181C4
TCD181CW
TCD211C3
TCD211C4
TCD211CW
TCD241C3
TCD241C4
TCD241CW
TCD301C3
TCD301C4
TCD301CW

Unit
Operating
Voltage Range
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633

Standard Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size or Maximum
Ampacity2
Circuit Breaker1
59
70
30
35
24
30
74
90
37
50
30
40
91
125
45
60
36
45
99
125
51
60
40
50
117
150
57
70
46
50

Oversize Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size or Maximum
Ampacity2
Circuit Breaker1
65
80
32
40
26
30
80
90
39
50
32
40
99
125
49
60
39
50
107
125
54
70
43
50
N/A
N/A
N/A
N/A
N/A
N/A

Notes:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

56

RT-PRC002-EN

Electrical
Data

(High Efficiency)

Table ED-7 — Unit Wiring - High Efficiency - Dehumidification (Hot Gas Reheat) Option
(Downflow Only)

Tons
12½

15

20

Unit
Model No.
TCD151C3
TCD151C4
TCD151CW
TCD181C3
TCD181C4
TCD181CW
TCD241C3
TCD241C4
TCD241CW

Unit
Operating
Voltage Range
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633

Standard Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size or Maximum
2
Ampacity
Circuit Breaker1
59
70
30
35
24
30
71
90
36
45
28
35
98
125
50
60
39
50

Oversize Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size or Maximum
2
Ampacity
Circuit Breaker1
65
80
32
40
26
30
77
100
39
50
30
40
105
125
53
60
42
50

Notes:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

RT-PRC002-EN

57

Electrical
Data

(High Efficiency)

Table ED-8 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, Standard Refrigeration System
(Downflow Only)
Control
Stages

Oversize Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

Heater
Model No.

12½

TCD151C3

AYDHTRK318A
AYDHTRK336A
AYDHTRK354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

64/68
108/122
154/176

80/80
110/125
175/200

70/76
115/130
162/184

90/90
125/150
175/200

15

TCD181C3

AYDHTRK318A
AYDHTRK336A
AYDHTRK354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

74/74
108/122
154/176

100/100
110/125
175/200

80/80
115/130
162/184

100/100
125/150
175/200

17½

TCD211C3

AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

20

TCD241C3

AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

25

TCD301C3

AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

125/139
171/193
218/247

150/150
175/200
225/250

—
—
—

—
—
—

TCD151C4

AYDHTRL418A
AYDHTRK436A
AYDHTRK454A

18.0
36.0
54.0

1
2
2

34
61
88

40
70
90

37
64
91

40
70
100

AYDHTRL418A
AYDHTRK427A
AYDHTRK436A
AYDHTRK454A

18.0
27.0
36.0
54.0

1
2
2
2

36
47
61
88

50
50
70
90

38
—
64
91

50
—
70
100

AYDHTRL427A
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

27.0
36.0
54.0
72.0

2
2
2
2

51
64
91
118

60
70
100
125

—
68
95
123

—
70
100
125

AYDHTRL427A
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

27.0
36.0
54.0
72.0

2
2
2
2

51
64
91
118

60
70
100
125

—
68
95
123

—
70
100
125

AYDHTRL436A
AYDHTRL427A
AYDHTRL454A
AYDHTRK472A

36.0
27.0
54.0
72.0

2
2
2
2

68
58
95
123

70
70
100
125

—
—
—
—

—
—
—

Tons

Heater
KW Rating

Standard Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker1

To Use
With

208/230 Volts Three Phase

460 Volts Three Phase
12½

15

17½

20

25

TCD181C4

TCD211C4

TCD241C4

TCD301C4

575 Volts Three Phase

58

12½

TCD151CW

AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A

18.0
36.0
54.0

1
2
2

27
49
70

30
50
70

30
51
73

35
60
80

15

TCD181CW

AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A

18.0
36.0
54.0

1
2
2

29
49
70

40
50
70

31
31
73

40
40
80

17½

TCD211CW

AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A

36.0
54.0
72.0

2
2
2

51
73
95

60
80
100

55
77
98

60
80
100

20

TCD241CW

AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A

36.0
54.0
72.0

2
2
2

51
73
95

60
80
100

55
77
98

60
80
100

25

TCD301CW

AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A

36.0
54.0
72.0

2
2
2

55
77
98

60
80
100

—
—
—

—
—
—

Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.

RT-PRC002-EN

Electrical
Data

(High Efficiency)

Table ED-9 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, Standard Refrigeration System
(Horizontal Only)

Tons

To Use
With

Heater
Model No.

Heater
KW Rating

Control
Stages

Standard Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker1

Oversize Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

208/230 Volts Three Phase
12½

TCH151C3

AYHHTRN318A
AYHHTRP336A
AYHHTRP354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

64/68
108/122
154/176

80/80
110/125
175/200

70/76
115/130
162/184

90/90
125/150
175/200

15

TCH181C3

AYHHTRM318A
AYHHTRM336A
AYHHTRM354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

74/74
108/122
154/176

100/100
110/125
175/200

80/80
115/130
162/184

100/100
125/150
175/200

17½

TCH211C3

AYHHTRN336A
AYHHTRN354A
AYHHTRN372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

20

TCH241C3

AYHHTRN336A
AYHHTRN354A
AYHHTRN372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

25

TCH301C3

AYHHTRN336A
AYHHTRN354A
AYHHTRN372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

125/139
171/193
218/247

150/150
175/200
225/250

—
—
—

—
—
—

12½

TCH151C4

AYHHTRN418A
AYHHTRP436A
AYHHTRP454A

18.0
36.0
54.0

1
2
2

34
61
88

40
70
90

37
64
91

40
70
100

15

TCH181C4

AYHHTRM418A
AYHHTRM436A
AYHHTRM454A

18.0
36.0
54.0

1
2
2

36
61
88

50
70
90

38
64
91

50
70
100

17½

TCH211C4

AYHHTRN436A
AYHHTRN454A
AYHHTRN472A

36.0
54.0
72.0

2
2
2

64
91
118

70
100
125

68
95
123

70
100
125

20

TCH241C4

AYHHTRN436A
AYHHTRN454A
AYHHTRN472A

36.0
54.0
72.0

2
2
2

64
91
118

70
100
125

68
95
123

70
100
125

25

TCH301C4

AYHHTRN436A
AYHHTRN454A
AYHHTRN472A

36.0
54.0
72.0

2
2
2

68
95
123

70
100
125

—
—
—

—
—
—

12½

TCH151CW

AYHHTRNW18A
AYHHTRPW36A
AYHHTRPW54A

18.0
36.0
54.0

1
2
2

27
49
70

30
50
70

30
51
73

35
60
80

15

TCH181CW

AYHHTRMW18A
AYHHTRMW36A
AYHHTRMW54A

18.0
36.0
54.0

1
2
2

29
49
70

40
50
70

31
31
73

40
40
80

17½

TCH211CW

AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A

36.0
54.0
72.0

2
2
2

51
73
95

60
80
100

55
77
98

60
80
100

20

TCH241CW

AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A

36.0
54.0
72.0

2
2
2

51
73
95

60
80
100

55
77
98

60
80
100

25

TCH301CW

AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A

36.0
54.0
72.0

2
2
2

55
77
98

60
80
100

—
—
—

—
—
—

460 Volts Three Phase

575 Volts Three Phase

Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.

RT-PRC002-EN

59

Electrical
Data

(High Efficiency)

Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and
151/181/ 241 Reheat Option(Downflow Only)

Tons

To Use
With

Heater
Model No.

Heater
KW Rating

Standard Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

Control
Stages

Oversize Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker1,2

208/230 Volts Three Phase
12½

TCD151C3

AYDHTRK318A
AYDHTRK336A
AYDHTRK354A

15

TCD181C3

AYDHTRK318A
AYDHTRK336A
AYDHTRK354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

*AYDHTRK318A

13.5/18.0

1

71/71

90/90

77/77

100/100

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

TCD181C3

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

61/68
108/122
154/176

70/70
110/125
175/200

68/76
115/130
162/184

80/80
125/150
175/200

74/74
108/122
154/176

100/100
110/125
175/200

80/80
115/130
162/184

90/90
125/150
175/200

17½

TCD211C3

AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

20

TCD241C3

AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

25

TCD301C3

AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

125/139
171/193
218/247

150/150
175/200
225/250

—
—
—

—
—
—

TCD151C4

AYDHTRL418A
AYDHTRK436A
AYDHTRK454A

18.0
36.0
54.0

1
2
2

34
61
88

35
70
90

37
64
91

40
70
100

TCD181C4

AYDHTRL418A
AYDHTRK427A3
AYDHTRK436A
AYDHTRK454A

18.0
27.0
36.0
54.0

1
2
2
2

37
47
61
88

50
50
70
90

39
—
64
91

50
—
70
100

*AYDHTRL418A

18.0

1

36

45

39

50

AYDHTRL427A3
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

27.0
36.0
54.0
72.0

2
2
2
2

51
64
91
118

60
70
100
125

—
68
95
123

—
70
100
125

AYDHTRL427A3
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

27.0
36.0
54.0
72.0

2
2
2
2

51
64
91
118

60
70
100
125

—
68
95
123

—
70
100
125

AYDHTRL427A3
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

27.0
36.0
54.0
72.0

2
2
2
2

57
68
95
123

70
70
100
125

—
—
—
—

—
—
—
—

460 Volts Three Phase
12½

15

TCD181C4

17½

20

25

TCD211C4

TCD241C4

TCD301C4

Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
3. Do not use with oversized motor.
* Applies only to Dehumidification (Hot Gas Reheat) Models

60

RT-PRC002-EN

Electrical
Data

(High Efficiency)

Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and
151/181/ 241 Reheat Option(Downflow Only), continued

Tons

To Use
With

Heater
Model No.

Heater
KW Rating

Control
Stages

Standard Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker2

Oversize Indoor Motor
Max Fuse Size or
MCA
Max Circuit
Breaker1,2

575 Volts Three Phase
12½

TCD151CW

AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A

15

TCD181CW

AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A

18.0
36.0
54.0

1
2
2

30
49
70

40
50
70

32
51
73

40
60
80

*AYDHTRKW18A
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A

18.0
36.0
54.0
72.0

1
2
2
2

28
51
73
95

35
60
80
100

30
55
77
98

40
60
80
100

TCD181CW

18.0
36.0
54.0

1
2
2

27
49
70

30
50
70

30
51
73

30
60
80

17½

TCD211CW

20

TCD241CW

AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A

36.0
54.0
72.0

2
2
2

51
73
95

60
80
100

55
77
98

60
80
100

25

TCD301CW

AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A

36.0
54.0
72.0

2
2
2

55
77
98

60
80
100

—
—
—

—
—
—

Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
3. Do not use with oversized motor.
* Applies only to Dehumidification (Hot Gas Reheat) Models

RT-PRC002-EN

61

Electrical
Data

(High Efficiency)

Table ED-11 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, Standard
Refrigeration System
Compressor Motors

Condenser Fan Motors

Unit
Model No.

No.

Volts

Phase

HP2

RPM

Amps1
RLA
LRA

12½

TC*151C3
TC*151C4
TC*151CW

2
2
2

208-230
460
575

3
3
3

5.70
5.70
5.70

3450
3450
3450

20.7
10.0
8.2

15

TC*181C3
TC*181C4
TC*181CW

2
2
2

208-230
460
575

3
3
3

17½

TC*211C3
TC*211C4
TC*211CW

2
2
2

208-230
460
575

3
3
3

20

TC*241C3
TC*241C4
TC*241CW

2
2
2

208-230
460
575

3
3
3

9.30
9.30
9.30

3450
3450
3450

25

TC*301C3
TC*301C4
TC*301CW

2
2
2

208-230
460
575

3
3
3

10.00
10.00
10.00

3450
3450
3450

Tons

No.

Phase

HP

Amps1
FLA
LRA

156
75
54

2
2
2

1
1
1

.50
.50
.50

3.2
1.6
1.3

8.8
3.8
3.2

9.30/4.50 3450 31.5/16.9
9.30/4.50 3450 15.1/8.2
9.30/4.50 3450 12.1/6.6

253/124
113/59.6
85/49.4

2
2
2

1
1
1

.50
.50
.50

3.2
1.6
1.3

8.8
3.8
3.2

10.0/5.70 3450 33.3/20.7
10.0/5.70 3450 16.3/10.0
10.0/5.70 3450 13.2/8.2

278/156
124/75
92/54

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

31.6
16.1
12.9

253
113
85

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

37.6
18.3
14.9

278
124
92

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

Table ED-12 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, TXV/Face-Split
Evaporator Coil Option (Downflow Only)
Compressor Motors
Tons
12½

15

17½

20

25

Unit
Model No.

No.

TCD151C3
TCD151C4
TCD151CW
TCD181C3
TCD181C4
TCD181CW
TCD211C3
TCD211C4
TCD211CW
TCD241C3
TCD241C4
TCD241CW
TCD301C3
TCD301C4
TCD301CW

2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

Volts
208-230
460
575
208-230
460
575
208-230
460
575
208-230
460
575
208-230
460
575

2

Phase
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

HP

5.7
5.7
5.7
9.30/4.50
9.30/4.50
9.30/4.50
10.00/5.7
10.00/5.7
10.00/5.7
9.0/9.3
9.0/9.3
9.0/9.3
10.00
10.00
10.00

RPM
3450
3450
3450
3450
3450
3450
3450
3450
3450
3500/3450
3500/3450
3500/3450
3450
3450
3450

Amps1
RLA
LRA
18.6
9.4
7.4
32.1/16.4
15.6/8.7
12.3/7.4
34.8/19.5
17.0/10.3
13.8/8.1
30.4/32.6
16.1/16.8
12.5/13.4
36.2
17.7
14.3

156
75
54
253/124
113/59.6
85/49.4
278/156
124/75
92/54
225/253
114/113
80/85
278
124
92

No.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

Condenser Fan Motors
Amps1
Phase
HP
FLA
LRA
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

.50
.50
.50
.50
.50
.50
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

3.2
1.6
1.3
3.2
1.6
1.3
5.5
2.9
2.0
5.5
2.9
2.0
5.5
2.9
2.0

8.8
3.8
3.2
8.8
3.8
3.2
18.3
9.3
5.7
18.3
9.3
5.7
18.3
9.3
5.7

Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

Table ED-13 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Dehumidification (Hot Gas Reheat)
Option (Downflow Only)
Compressor Motors
Tons
12½

15

20

Unit
Model No.

No.

TCD151C3
TCD151C4
TCD151CW
TCD181C3
TCD181C4
TCD181CW
TCD241C3
TCD241C4
TCD241CW

2
2
2
2
2
2
2
2
2

Volts
208-230
460
575
208-230
460
575
208-230
460
575

Phase
3
3
3
3
3
3
3
3
3

2

HP

5.7/5.7
5.7/5.7
5.7/5.7
8.3/5.7
8.3/5.7
8.3/5.7
9.0/9.3
9.0/9.3
9.0/9.3

RPM
3450
3450
3450
3450
3450
3450
3500/3450
3500/3450
3500/3450

Amps1
RLA
LRA
18.6
9.7
7.6
27.4/19.0
13.8/10.1
10.7/7.9
30.1/31.7
15.6/16.2
12.1/13.0

156
75
54
208/156
100/75
68/54
225/253
114/113
80/85

No.
2
2
2
2
2
2
2
2
2

Condenser Fan Motors
Amps1
Phase
HP
FLA
LRA
1
1
1
1
1
1
1
1
1

.50
.50
.50
.50
.50
.50
1.00
1.00
1.00

3.2
1.6
1.3
3.2
1.6
1.3
5.5
2.9
2.0

8.8
3.8
3.2
8.8
3.8
3.2
18.3
9.3
5.7

Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.
*Indicates both downflow and horizontal units.

62

RT-PRC002-EN

Electrical
Data

Table ED-14 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Standard and Oversized
Standard Evaporator Fan Motor
Unit
Model No.

Tons

Amps
FLA
LRA

No.

Oversized Evaporator Fan Motor
Amps
Volts
Phase
HP
FLA
LRA

No.

Volts

Phase

HP

12½

TC*150D3, TC*151C3
TC*150D4, TC*151C4
TC*150DW, TC*151CW
TC*150DK

1
1
1
1

208-230
460
575
380

3
3
3
3

3.00
3.00
3.00
5.0

10.6
4.8
3.9
9.2

81.0
40.5
31.0
66.5

1
1
1
—

208-230
460
575
—

3
3
3
—

5.00
5.00
5.00
—

16.7
7.6
6.1
—

109.8
54.9
41.6
—

15

TC*180B3, TC*181C3
TC*180B4, TC*181C4
TC*180BW, TC*181CW
TC*180BK

1
1
1
1

208-230
460
575
380

3
3
3
3

3.00
3.00
3.00
5.0

10.6
4.8
3.9
9.2

81.0
40.5
31.0
66.5

1
1
1
—

208-230
460
575
—

3
3
3
—

5.00
5.00
5.00
—

16.7
7.6
6.1
—

109.8
54.9
41.6
—

17½

TC*210C3, TC*211C3
TC*210C4, TC*211C4
TC*210CW, TC*211CW
TC*210CK

1
1
1
1

208-230
460
575
380

3
3
3
3

5.00
5.00
5.00
7.5

16.7
7.6
6.1
13.3

109.8
54.9
41.6
83.5

1
1
1
—

208-230
460
575
—

3
3
3
—

7.50
7.50
7.50
—

24.2
11.0
9.0
—

120.4
74.0
60.0
—

20

TC*240B3, TC*241C3
TC*240B4, TC*241C4
TC*240BW, TC*241CW
TC*240BK

1
1
1
1

208-230
460
575
380

3
3
3
3

5.00
5.00
5.00
7.5

16.7
7.6
6.1
13.3

109.8
54.9
41.6
83.5

1
1
1
—

208-230
460
575
—

3
3
3
—

7.50
7.50
7.50
—

24.2
11.0
9.0
—

120.4
74.0
60.0
—

25

TC*300B3, TC*301C3
TC*300B4, TC*301C4
TC* 300BW, TC*301CW
TC*300BK

1
1
1
1

208-230
460
575
380

3
3
3
3

7.50
7.50
7.50
7.5

24.2
11.0
9.0
13.3

120.4
74.0
60.0
83.5

—
—
—
—

—
—
—
—

—
—
—
—

—
—
—
—

—
—
—
—

—
—
—
—

*Indicates both downflow and horizontal units.

RT-PRC002-EN

63

Electrical
Data

Table ED-15 — Electrical Characteristics — Power Exhaust Accessory
Accessory
Operating
Voltage

Phase

HP

RPM

FLA

\Amps
LRA

12½1, 2

208-230

1

3/4

1040

6.6

13.5

15, 17½

460

1

3/4

1040

3.2

8.4

20, 25

575

1

3/4

1040

2.1

5.2

Tons

Notes:
1. 12½ Ton Standard Unit.
2. 12½ Ton High Efficiency Unit.

64

RT-PRC002-EN

Jobsite
Connections
Zone Sensors —Typical Number Of Wires

DISCONNECT
SWITCH
(BY OTHERS)

A— Manual Changeover ....................................... 4
Manual/Auto Changeover ............................... 5
Manual/Auto Changeover with
Status Indication LED’s ........................... 10
Programmable Night Setback with
Status Indication LED’s ............................. 7

ZONE SENSORS
ROOFTOP
UNIT

B— 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)

For specific wiring information, see the installation instructions.
All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.

RT-PRC002-EN

65

Typical
Wiring

66

(12½-25 Ton)

RT-PRC002-EN

Typical
Wiring

(12½-25 Ton)

Typical wiring diagram. For specific
wiring, see individual Service Facts.

RT-PRC002-EN

67

Typical
Wiring

68

(12½-25 Ton)

RT-PRC002-EN

Typical
Wiring

RT-PRC002-EN

(12½-25 Ton)

69

Dimensional
Data

(12½ Ton) High Efficiency
(12½, 15, 17½ Ton)
Standard Efficiency

All dimensions are in inches.

Note: Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb flanges.
See recommended duct dimensions on
the next page.
Roofcurb is intended for downflow use
only.

Downflow Unit Clearance

70

RT-PRC002-EN

(12½ Ton) High Efficiency
(12½, 15, 17½ Ton)

Dimensional
Data

Standard Efficiency

All dimensions are in inches.
1"
Downflow Duct Connections — Field Fabricated

17 7/8"
59 7/16"
26 5/16"

52 1/2"

1 1\2"
PERIMETER
CURB FLANGE

14 1/16"
7 7/16"

1"

N

UR

T
RE

LY

PP

SU

Note:
Duct flanges mount 7-7/16" down inside
the curb on the 1½" curb flanges.
Roofcurb is intended for downflow use
only.

Horizontal Unit Supply/Return and Unit Clearance

RT-PRC002-EN

71

Dimensional (15-25 Ton) High Efficiency
(20, 25 Ton)
Data
Standard Efficiency

All dimensions are in inches.

Note:
Duct flanges mount 7-7/16" down inside
the curb on the 1½" curb flanges. See
recommended duct dimensions on the
next page.
Roofcurb is intended for downflow use
only.

72

Downflow Unit Clearance

RT-PRC002-EN

Dimensional (15-25 Ton) High Efficiency
(20, 25 Ton)
Data
Standard Efficiency

All dimensions are in inches.

1"

Downflow Duct Connections — Field Fabricated

19 5/16"
73 7/16"
26 5/16"

66 1/2"

1 1\2"
PERIMETER
CURB FLANGE

14 1/16"
7 7/16"

1"

N

UR

T
RE

Y

PL

P
SU

Note: Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb flanges.
Roofcurb is intended for downflow use
only.

Horizontal Unit Supply/Return and Unit Clearance

RT-PRC002-EN

73

Dimensional
Data

(12½-25 Ton)
Accessories

All dimensions are in inches.

Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to
allow proper operation of Economizer Damper.

Table DD-1
Unit
Model #
TC*150, 151-180, 210
TC*181, 211-301

A
1

17 /2
191/2

B1

C2

53¾
64¾

36
39

Notes:
1. Horizontal dimension only. Downflow economizer is width
of end panel.
2. Power exhaust is applied on downflow economizer only.

74

RT-PRC002-EN

Dimensional
Data

Factory Installed
Options (FIOPS)

All dimensions are in inches.

Table DD-2
Unit
Model #

RT-PRC002-EN

A

B

C

TCD150, 151, 180, 210

423/8

483/8

31

TCD181, 211-301

291/2

56

381/2

75

Dimensional
Data

Factory Installed
Options (FIOPS)

Disconnect Switch
or Circuit Breaker

Fan Failure Switch

Clogged Filter Switch

Powered or Unpowered
Convenience Outlet

Trane Communication Interface
Hinged Access Door
Black Epoxy Coated
Outdoor Coils
Hinged Access Door

Through the Base Electrical
High Pressure Cut Out

Supply and/or Return Smoke Detectors

76

RT-PRC002-EN

Dimensional
Data

(12½-25 Ton)

Table DD-3 — Standard Efficiency Units
Condensate
Tons
12½, 15, 17½
20, 25

Downflow Only

Drain Size

A

B

C

D

F

G

H

267/16
267/16

221/2
283/4

1811/16
1915/16

41/4
41/4

41/4
41/4

627/16
765/16

5411/16
6811/16

1 NPT
1 NPT

Condensate Drain Location
Downflow

Horizontal

E

J

E

K

—
—

255/8
263/4

—
—

6
53/8

Table DD-4 — High Efficiency Units
Condensate
Tons
12½
15-25

RT-PRC002-EN

Downflow Only

Drain Size

A

B

C

D

F

G

H

267/16
267/16

221/2
283/4

1811/16
1915/16

41/4
41/4

41/4
41/4

627/16
765/16

5411/16
6811/16

1 NPT
1 NPT

Condensate Drain Location
Downflow

Horizontal

E

J

E

K

—
—

255/8
263/4

—
—

6
53/8

77

(12½-25 Ton)

Weights

Table W-1 — Accessory Net Weights (Lbs)1, 7

Model No.
TCD150D, 180B
TCD121,151C, TCD210C

Economizer
Net

Outside Air Damper
Manual
Motorized

65

32

60

Power
Exhaust4

Roof
Curb4

Oversized
Motor
Adder

High5
Static
Drive

Low5
Static
Drive

95

205

5

2

2

TCD240B
TCD181,211,241C

80

32

75

95

235

5

2

—

TCD300B.301C

80

32

75

95

235

N/A

N/A

2

TCH150D, 180B, 210C
TCH121,151C

50

32

60

—

—

5

2

2

TCH240B
TCH181,211,241C

65

32

75

—

—

5

2

—

TCH300B,301C

65

32

75

—

—

N/A

N/A

2

Table W-1 Continued
All Zone
Sensors

6-23 KW
240/480V2 3

Electric Heaters
27-36 KW
240/480V2 3

54 KW
240/480V2 3

72 KW
240/480V2 3

TCD150D, 180B, 210C
TCD121,151,181C

1

28/216

31/27

38/32

—

TCD240B
TCD211,241C

1

—

33/27

40/32

43/34

Unit
Model No.

TCD300B,301C

1

—

33/27

40/32

43/34

TCH150D, 180B, 210C
TCH121,151,181C

1

28/216

31/27

38/32

—

TCH240B
TCH211, 241C

1

—

33/27

40/32

43/34

TCH300B, 301C

1

—

33/27

40/32

43/34

Notes:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. For 600V heaters net weights are same as 480V heaters.
3. To estimate shipping weight add 5 lbs to net weight.
4. Downflow only.
5. Not available on all models (See Fan Performance tables for specific models).
6. 9 - 23 KW Heaters not available for TC*210C.
7. TC*150-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93.
This is provided in compliance with ARI certification program.

78

RT-PRC002-EN

Weights

Table W-2 — Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
Tons

Unit
Model No.

Maximum Weights (Lbs)
Shipping2
Net

A

Corner Weights (Lbs)1
B
C

D

Center of Gravity (In.)
Length
Width

12½

TC*150D/TC*151C

1687/1820

1319/1452

446/485

339/360

230/259

303/348

46/45

29/30

15

TC*180B/TC*181C

1866/2361

1498/1902

547/643

358/477

234/333

359/447

42/52

28/35

17½

TC*210C/TC*211C

2022/2380

1654/1921

565/643

425/495

285/341

378/442

46/53

29/35

20

TC*240B/TC*241C

2372/2490

1913/2031

679/697

482/528

312/348

440/458

51/53

34/34

25

TC*300B/ TC*301C

2365/2475

1906/2016

661/695

507/524

320/343

418/454

53/53

33/34

Notes:
1. Corner weights are given for information only. 12½-25 ton models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.

*Indicates both downflow and horizontal units.

RT-PRC002-EN

79

Weights

Table W-3 — Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3
Accessory
High Efficiency Motors4

Weight
49
36

Unit Model Number
TC*150-181 standard size motor
TC*210-241 standard size motor
TC*150-181 oversize motor

0

TC*210-241 oversize motor
TC*300-301 standard size motor

Hinged Doors

27

AllTC* units

Powered Convenience Outlet

38

AllTC* units

Through the Base Electrical

23

AllTC* units

Unit Mounted Circuit Breaker

5

AllTC* units except those with 54&72 kW heaters
& 208/230V
All TC* units with 54&72 kW heaters & 208/230V

10
Unit Mounted Disconnect

5
10

Smoke Detectors
Supply/Return

AllTC* units except those with 54&72 kW heaters
& 208/230V
AllTC* units with 54&72 kW heaters & 208/230V

5

AllTC* units

Tool-less Hail Guard

38
43

TC*150,151,180,210
TC*181,211,240,241,300,301

Novar 2024

7

AllTC* units

Novar 3051

5

AllTC* units

Notes:
1. Weights for FIOP accessories not listed are >5 lbs.
2. Net weight should be added to unit weight when ordering factory installed accessories.
3. See Table W-1 for standard factory installed economizer and oversized motors.
4. Standard factory installed motors are already included in unit net and shipping weights. Values shown for high
efficiency motors are in addition to the standard motor weight.

80

RT-PRC002-EN

Mechanical
Specifications

General
The units shall be dedicated downflow or
horizontal airflow.The operating range
shall be between 115°F and 0°F in cooling
as standard from the factory for all units.
Cooling performance shall be rated in
accordance with ARI testing procedures.
All units shall be factory assembled,
internally wired, fully charged with R-22,
and 100 percent run tested to check
cooling operation, fan and blower rotation
and control sequence, before leaving the
factory. Wiring internal to the unit shall be
colored and numbered for simplified
identification. Units shall be UL listed and
labeled, classified in accordance to UL
1995/CAN/CSA No. 236-M90 for Heat
Pumps. Canadian units shall be CSA
Certified.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Unit’s surface shall be tested 500 hours in
a salt spray test in compliance with ASTM
B117. Cabinet construction shall allow for
all maintenance on one side of the unit. In
order to ensure a water and air tight seal,
service panels shall have lifting handels
and no more thatn three screws to
remove. All exposed vertical panels and
top covers in the indoor air section shall
be insulated with a 1/2 inch, 1 pound
density foil-faced, fire-resistant,
permanent, odorless, glass fiber material.
The base of the downflow unit shall be
insulated with 1/2 inch, 1 pound density
foil-faced, closed-cell material.The
downflow unit’s base pan shall have no
penetrations within the perimeter of the
curb other than the raised 11/8 inch high
supply/return openings to provide an
added water integrity precaution, if the
condensate drain backs up.The base of
the unit shall have provisions for forklift
and crane lifting.

RT-PRC002-EN

UnitTop
The top cover shall be one piece, or
where seams exist, double hemmed and
gasket sealed to prevent water leakage.
Filters
Two inch standard filters shall be factory
supplied on all units. Optional two inch
pleated media filters shall be available.
Compressors
All units shall have direct-drive, hermetic,
scroll type compressors with centrifugal
type oil pumps. Motor shall be suction
gas-cooled and shall have a voltage
utilization range of plus or minus 10
percent of nameplate voltage. Internal
overloads shall be provided with the
scroll compressors. All models shall have
crankcase heaters, low and high pressure
controls as standard.
Refrigerant Circuits
Each refrigerant circuit shall have
independent fixed orifice or thermostatic
expansion devices, service pressure
ports, and refrigerant line filter driers
factory installed as standard. An area
shall be provided for replacement suction
line driers.
Evaporator and Condenser Coils
Internally finned, 3/8" copper tubes
mechanically bonded to a configured
aluminum plate fin shall be standard.
Coils shall be leak tested at the factory to
ensure the pressure integrity. The
evaporator coil and condenser coil shall
be leak tested to 200 psig and pressure
tested to 450 psig. All dual compressor
units shall have intermingled evaporator
coils. Sloped condensate drain pans are
standard. Patent-pending 1+1+1
condenser coil, permanently gapped for
easy cleaning is available.

corrosion resistant steel components. A
forced combustion blower shall supply
premixed fuel to a single burner ignited
by a pilotless hot surface ignition system.
In order to provide reliable operation, a
negative pressure gas valve shall be
used that requires blower operation to
initiate gas flow. On an initial call for heat,
the combustion blower shall purge the
heat exchanger 45 seconds before
ignition. After three unsuccessful ignition
attempts, the entire heating system shall
be locked out until manually reset at the
thermostat. Units shall be suitable for use
with natural gas or propane (field
installed kit) and shall also comply with
California requirements for low NOx
emissions.The 12½-25 tons shall have
two stage heating.
Outdoor Fans
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position.The fan motor(s) shall be
permanently lubricated and shall have
built-in thermal overload protection.
Indoor Fan
Units above shall have belt driven, FC
centrifugal fans with adjustable motor
sheaves. Units with standard motors
shall have an adjustable idler-arm
assembly for quick-adjustment of fan
belts and motor sheaves. All motors shall
be thermally protected. Oversized motors
shall be available for high static
application. All indoor fan motors meet
the U.S. Energy Policy Act of 1992
(EPACT).

Gas Heating Section
The heating section shall have a drum
and tube heat exchanger design using

81

Mechanical
Specifications

Controls
Unit shall be completely factory wired
with necessary controls and contactor
pressure lugs or terminal block for power
wiring. Unit shall provide an external
location for mounting a fused disconnect
device. ReliaTel controls shall be provided
for all 24 volt control functions.The
resident control algorithms shall make all
heating, cooling, and/or ventilating
decisions in response to electronic signals
from sensors measuring indoor and
outdoor temperatures.The control
algorithm maintains accurate
temperature control, minimizes drift from
set point, and provides better building
comfort. A centralized control shall
provide anti-short cycle timing and time
delay between compressors to provide a
higher level of machine protection.
Defrost Controls
Adaptive demand defrost shall be
provided to permit defrost wherever coil
icing conditions begin to significantly
reduce unit capacity.

Factory Installed Options
Black Epoxy Coated Pre-Coated Coils
The black epoxy coils have a thermoset
vinyl coating that is bonded to the
aluminum fin stock prior to the finstamping process.The pre-coated coils
are an economical option for protection in
mildly corrosive environments.
Dehumidification Option
The dehumidification (hot gas reheat)
option shall provide increased
dehumidification.The option shall consist
of a hot-gas reheat coil located on the
leaving air side of the evaporator coil
prepiped and circuited. Low pressure
switch(es) and thermostatic expansion
valve(s) TXV are standard. Frostat™,
ReliaTel options module, and 2”pleated
filters are required but not standard.They
must be ordered and configured
separately.

82

Hinged Access Doors
Sheet metal hinges are available on the
Filter/Evaporator Access Door and the
Compressor/Control Access Door.This
option is available on all downflow
models.
High Efficiency Motors
This option is available with efficiency
ratings from 86.5 up to 91.0. It is not
available for all models.
High Pressure Cutout
This option is offered for units that do not
have High Pressure cutout as standard.
Powered or Unpowered Convenience
Outlet
This option is a GFCI, 120v/15amp, 2 plug,
convenience outlet, either powered or
unpowered. When the convenience outlet
is powered, a service receptacle
disconnect will be available.The
convenience outlet is powered from the
line side of the disconnect or circuit
breaker, and therefore will not be
affected by the position of the disconnect
or circuit breaker.This option can only be
ordered when theThrough the Base
Electrical with either the Disconnect
Switch, or Circuit Breaker, option is
ordered.This option is available on all
downflow models.
Supply and/or Return Air Smoke
Detector
With this option installed, if smoke is
detected, all unit operation will be shut
down. Reset will be manual at the unit.
Return Air Smoke Detectors require
minimum allowable airflow when used
with certain models. See the Installation,
Operation, and Maintenance (IOM)
manual for the models affected and the
minimum allowable airflow required.This
option is available on all downflow
models.

Through the Base Electrical with Circuit
Breaker
This option is a thermal magnetic, molded
case, HACR Circuit Breaker with
provisions for through the base electrical
connections.The circuit breaker will be
installed in a water tight enclosure in the
unit with access through a swinging door.
Factory wiring will be provided from the
switch to the unit high voltage terminal
block.The circuit breaker will provide
overcurrent protection, be sized per NEC
and UL guidelines, and be agency
recognized by UL/CSA.This option is
available on all downflow models.
Through the Base Electrical With
Disconnect Switch
Three-pole, molded case, disconnect
switch with provisions for through the
base electrical connections are available.
The disconnect switch will be installed in
the unit in a water tight enclosure with
access through a swinging door. Factory
wiring will be provided from the switch to
the unit high voltage terminal block.The
switch will be UL/CSA agency recognized.
Note:The disconnect switch will be sized
per NEC and UL guidelines but will not be
used in place of unit overcurrent
protection.This option is available on all
downflow models.
Through the Base Utilities Access
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
installation of liquid-tight conduit and an
external field installed disconnect switch.
Two-Inch Pleated Filters
Two inch pleated media filters shall be
available on all models.

RT-PRC002-EN

Mechanical
Specifications
Factory or Field Installed
Options
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available to achieve active fan failure
indication and/or clogged filter indication.
These indications will be registered with
either a zone sensor with status indication
lights or an Integrated Comfort™ System.
Differential Pressure Switches
These options allow for individual fan
failure and dirty filter indication.The fan
failure switch will disable all unit functions
and “flash” the Service LED on the zone
sensor.The dirty filter switch will light the
Service LED on the zone sensor and will
allow continued unit operation.
Discharge Air Sensing Kit
This kit provides true discharge air
sensing in heating models.This sensor is
a status indicator readable through
Tracer™orTracker™.The kit is functional
only with the ReliaTel Options Module.
Economizer - Downflow
The assembly includes fully modulating
0-100 percent motor and dampers,
barometric relief, minimum position
setting, preset linkage, wiring harness
with plug, fixed dry bulb and spring return
actuator.The barometric relief damper
shall be standard with the downflow
economizer and shall provide a pressure
operated damper that shall be gravity
closing and shall prohibit entrance of
outside air during the equipment “off”
cycle. Solid state enthalpy and differential
enthalpy control shall be field-installed

RT-PRC002-EN

Electric Heaters
Electric heat modules shall be available
for installation within the basic unit.
Electric heater elements shall be
constructed of heavy-duty nickel
chromium elements internally delta
connected for 240 volt, wye connected
for 480 and 600 volt. Staging shall be
achieved through ReliaTel. Each heater
package shall have automatically reset
high limit control operating through
heating element contactors. All heaters
shall be individually fused from the
factory, where required, and shall meet
all NEC and CEC requirements when
properly installed. Power assemblies
shall provide single-point connection.
Electric heat modules shall be UL listed or
CSA certified. If ordering theThrough the
Base Electrical option with an Electric
Heater, the heater must be factory
installed.

Reference or Comparative Enthalpy
Reference Enthalpy is used to measure
and communicate outdoor humidity.The
unit receives and uses this information to
provide improved comfort cooling while
using the economizer. Comparative
Enthalpy measures and communicates
humidity for both outdoor and return air
conditions, and return air temperature.
The unit receives and uses this
information to maximize use of
economizer cooling, and to provide
maximum occupant comfort control.
Reference or Comparative Enthalpy
option shall be available when a factory
or field installed Downflow Economizer is
ordered.This option is available on all
downflow models.

Frostat
This option is to be utilized as a safety
device. The Frostat opens when
temperatures on the evaporator coil fall
below 10°F. The temperature will need to
rise to 50°F before closing.This option
should be utilized in low airflow or high
outside air applications.

Trane Communication Interface
This factory or field-installed option shall
be provided to interface ReliaTel™
controlled units with theTrane Integrated
ComfortTM systems.

Tool-less Hail Guards
Tool-less, hail protection quality coil
guards are available for condenser coil
protection.

LonTalk® Communications Interface
The LonTalk communications interface,
when installed in a Voyager unit, allows
the unit to communicate as aTracer™LCIV device or directly with generic LonTalk
Network Building Automation System
Controls.
Oversized Motors
Oversized motors shall be available for
high static applications.

83

Mechanical
Specifications
Field Installed Options
CO2 Sensing
The CO2 sensor has the ability to monitor
space occupancy levels within the
building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air.
As the CO2 levels increase, the outside air
damper modulates to meet the CO2
space ventilation requirements.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors.This sensor
includes a digital display of set point
adjustment and space temperature in F
(Fahrenheit) or C (Celsius). Includes FAN
and SYSTEM buttons (supports the
service functions of the standard sensor).
E-squared memory stores last
programmed set points. Requires 24 VAC
(Volts AC).This sensor should be utilized
with ReliaTel™ controls.
Dual Thermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.

Roof Curb - Downflow
The roof curb shall be designed to mate
with the downflow unit and provide
support and a water tight installation
when installed properly.The roof curb
design shall allow field-fabricated
rectangular supply/return ductwork to be
connected directly to the curb. Curb
design shall comply with NRCA
requirements. Curb shall be shipped
knocked down for field assembly and
shall include wood nailer strips.
Economizer - Horizontal
The horizontal economizer shall contain
the same features as the downflow
economizer with the exception of
barometric relief.
Remote Potentiometer
The minimum position setting of the
economizer shall be adjusted with this
accessory.

Manual Outside Air Damper
The rain hood and screen shall provide
up to 25 percent outside air.

Ventilation Override Accessory
With the Ventilation Override Accessory
installed, the unit can be set to transition
up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust.The
transition occurs when a binary input on
the RTOM is closed (shorted).This would
typically be a hard wired relay output
from a smoke detector or fire control
panel.

Motorized Outside Air Dampers
Manually set outdoor air dampers shall
provide up to 50 percent outside air. Once
set, outdoor air dampers shall open to set
position when indoor fan starts.The
damper shall close to the full closed
position when indoor fan shuts down.

Zone Sensors
This option shall be provided to interface
with the Micro equipped Voyagers and
shall be available in either manual,
automatic, programmable with night
setback, with system malfunction lights or
remote sensor options.

High Static Drive
The high static drive option shall allow the
standard motor on the 12½ and 20 ton
units to operate with improved external
static capabilities.

84

Powered Exhaust
The powered exhaust shall provide
exhaust of return air, when using an
economizer, to maintain better building
pressurization.

RT-PRC002-EN

RT-PRC002-EN

85

86

RT-PRC002-EN

RT-PRC002-EN

87

Trane
A business of American Standard Companies
www.trane.com
For more information contact your local dealer
(distributor), local district office, or e-mail us at
comfort@trane.com

Literature Order Number

RT-PRC002-EN

File Number

PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-10-04

Supersedes

PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-09-04

Stocking Location

09-04 Webb/Mason 10-04 Electronic Only

Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Create Date                     : 2004:09:07 19:40:58Z
Modify Date                     : 2004:10:15 14:19:09-05:00
Subject                         : Packaged Cooling with Electric Heat Rooftop Units Voyager™ 12-25 Tons
Keywords                        : RT-PRC002-EN, (09/04), Packaged, Cooling, with, Electric, Heat, Rooftop, Units, Voyager™, 12-25, Tons
Page Count                      : 88
Creation Date                   : 2004:09:07 19:40:58Z
Mod Date                        : 2004:10:15 14:19:09-05:00
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Author                          : Global Unitary Systems - Clarksville
Metadata Date                   : 2004:10:15 14:19:09-05:00
Title                           : RT-PRC002-EN (10/04) Packaged Cooling with Electric Heat Rooftop Units Voyager™ 12-25 Tons
Description                     : Packaged Cooling with Electric Heat Rooftop Units Voyager™ 12-25 Tons
Creator                         : Global Unitary Systems - Clarksville
Page Mode                       : UseOutlines
Page Layout                     : OneColumn
EXIF Metadata provided by EXIF.tools

Navigation menu