Trane TWA PRC001 EN User Manual To The 90d7d7fd C2e1 466d 8c1b 638400af9e7c
User Manual: Trane TWA-PRC001-EN to the manual
Open the PDF directly: View PDF
.
Page Count: 60
| Download | |
| Open PDF In Browser | View PDF |
Split System Heat Pumps Split System Heat Pumps 7 1/2 through 20 Ton - 50 Hz Air Handlers 5 through 20 Ton - 50 Hz July 2000 TWA-PRC001-EN Introduction Split System Heat Pumps… Designed With Your Needs In Mind. The Trane reputation for quality and reliability is reflected in the Odyssey™ Commercial Split System Heat Pumps. Trane’s focused attention on the split system marketplace results in an outstanding heat pump that meets job requirements...and at a very competitive price. ©American Standard Inc. 2000 Efficiency, flexibility and installation ease, coupled with Trane’s reputation for quality and reliability, gives you a system that is “ Simply the Best Value”. TWA-PRC001-EN Contents Introduction Features and Benefits 2 Application Considerations 6 Selection Procedure 7 Model Number Description General Data Performance Data Cool and Heat Performance Fan Performance TWA-PRC001-EN 4 8 9 12 Electric Power 12 24 31 Connection and Wiring 33 Dimension and Weights 39 Mechanical Specifications 55 Features and Benefits Heat Pumps • 3-D® Scroll compressors • ModelTWA155-200B have dual compressors with independent refrigerant circuits • Compressor motor overload protection • Control transformer • High and low pressure cut-out switches • Internal pressure relief valve • Liquid line filter drier, factory installed • Holding charge of dry nitrogen • Copper tube, aluminum plate fin coils • Low ambient cooling to 35° F (1.7° C) as manufactured • Weather resistant baked enamel finish • Heavy gauge steel cabinet • Mounting/lifting rails under base All condensing units offer these optional accessories: • Head Pressure Control — Low Ambient CoolingTo 0° F (-17.8° C) • Coil Guards Kits • Isolators both Rubber-in-Shear and SpringType • Anti-Short-Cycle Kit • Time Delay Relay 4 Air Handlers • Low voltage terminal board • Expansion valve(s) • Convertible • PVC double-sloped, removeable drain pan • Fan relay • Efficient evaporator coil • Baked enamel finish • Filter access panel • 1” (25.4 mm) throwaway filters standard with provisions for field supplied 2” (50.8 mm) filters • Adjustable belt drive motor • Single point power entry to electric heaters • Refrigerant piping and/or electrical connections provided from either side Odyssey™ air handler versatility is further increased by a complete line of optional accessories designed to match and easy to install: • Discharge Plenum and Grille • Return Grille • Subbase • Electric Heaters • High Static Evaporator Motor • Isolators both Rubber-in-Shear and SpringType TWA-PRC001-EN Features and Benefits Heat Pump Options The Odyssey™ split system product line includes heat pumps in both single and dual compressor options. TWA075A andTWA100A single compressor models feature single refrigeration circuitry lowering job installation costs by requiring only one set of refrigerant lines.These units are ideal for either the low cost, new construction jobs as well as renovation and replacement buildings. In addition, Odyssey modelsTWA155B throughTWA200B are dual compressor units that give true standby protection; if one compressor fails, the second will automatically start-up. Also, the first compressor can be serviced without shutting down the unit since refrigerant circuits are independent. Dual compressors are not just for protection, they also save energy costs. Most buildings are designed for the peak load requirements yet the building usually operates at less than peak load. During light load conditions only one compressor functions to maintain the space comfort thus reducing the need for energy. Trane split systems have been specified in thousands of applications and you’ll find Odyssey will win you even more jobs with it’s smaller, more manageable cabinet. Air Handlers Offer More Flexibility Flexibility is a key to meeting changing market requirements. Odyssey split systems offer various compressor options and convertible air handlers. The air handlers can be installed either vertically in a mechanical room or horizontally above a ceiling. And it doesn’t require any removal of panels or reconfiguration of the drain pan to make either airflow application work. All the air handlers feature factory installed belt drive and ball bearing evaporator fans with adjustable sheaves for maximum airflow performance.The standard motor on theTWE100A air handler will deliver 4000 cfm (1888 l/s) at 0.8” (20.32 mm) ESP. Plus oversized motors are available for higher static applications. Odyssey air handler versatility is further increased by a complete line of accessories designed to match and install smoothly: • Discharge Plenum and Grille • Return Grille • Subbase • Electric Heaters • High Static Evaporator Motor • Isolators both Rubber-in-Shear and SpringType • A Full Line of Thermostats Odyssey™ — A Complete Split System Odyssey delivers the flexibility to select a complete system that meets your particular job requirements. Air Handlers are designed, tested and rated with condensing units to let you select the proper match between capacity and load. Condensing units can also be matched withTrane built-up air handlers. These matched systems can be quickly engineered for specific applications. Low Ambient Cooling Operation Each condensing unit can operate to 35° F (1.7° C) as standard. An accessory Head Pressure Control gives you the capability to operate to 0° F (-17.8° C). All condensing units offer these accessories: • Head Pressure Control • Coil Guard Kits • Isolators both Rubber-in-Shear and SpringType • Anti-Short-Cycle Kit • Time Delay Relay TWA-PRC001-EN 5 Application Considerations Application of this product should be within the catalogued airflow and performance considerations.The System Selection Program will simulate product performance for a set of given conditions. It is recommended that the program should be run at the lowest outdoor ambient and supply air flow rates requiring cooling or heating operation for a particular unit. For more information on the System Selection Program contact your localTrane Representative. should be reviewed with the localTrane Representative. Low Ambient Cooling As manufactured, these units can operate to 35° F (1.7° C) in the cooling mode of operation. An accessory head pressure control will allow operation to 0° F (-17.8° C) outdoor ambient. When using these units with control systems such as bypass changeover Variable Air Volume, consider the requirement for a head pressure control to allow low ambient cooling. Clearance Requirements The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances that appear inadequate Typical Horizontal Air Handler Application Typical Vertical Air Handler Application Typical Split System Application 6 TWA-PRC001-EN Selection Procedure Cooling Capacity Step 1 — Calculate the building’s total and sensible cooling loads at design conditions. Use theTrane calculation form or any other standard accepted method. actualTotal Static Pressure is 1.10 - 0.10 = 1.00 in. (27.9 - 2.5 = 25.4 mm) (275 - 25 = 250 Pa) Step 2 — Size the equipment usingTable PD-1. Match the cooling loads at design conditions. Note:The formula below the table can be used to calculate Fan Motor Heat, Constant x Motor Power = Fan Motor Heat 3.5 x Bhp = MBh 3.5 x 1.07 = 3.75 MBh Example:The following are the building cooling requirements a Electrical Characteristics: 380-415/50/3 b Summer Design Conditions: Entering Evaporator Coil: 80 DB/67 WB (27 DB/19 WB° C) Outdoor Ambient: 95° F (35° C) c Total Cooling Load: 75 MBh (22kW) d Sensible Cooling Load: 53 MBh (15.5 kW) e Airflow: 2500 cfm (1,180 l/s) External Static Pressure: 0.77 in. (19.6 mm) w.g. (193 Pa) Table PD-1 shows that aTWA075A matched with aTWE075A has a gross cooling capacity of 82.4 MBh (24.1 kW) and 59.5 MBh (17.4 kW) sensible capacity at 95 DB (35° C) ambient and 2500 cfm (1180 l/s) and 80 DB/67 WB (27 DB/19 WB) air entering the evaporator. To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit static pressure: External Static 0.77 in (19.6 mm) (193 Pa) Standard Filter 0.10 in 1 in. (25.4 mm) (2.5 mm) (25 Pa) Supplementary Electric Heat 0.23 in (5.8 mm) (57 Pa) Total Static Pressure 1.10 in (27.9 mm) (275 Pa) Note:The Evaporator Fan Performance Table has included the effect of a 1 in. (25.4 mm) filter already.Therefore, the TWA-PRC001-EN With 2500 cfm (1180 l/s) and 1.00 inches (250 Pa) (0.8 kW), Table 26-1 shows a 1.07 Bhp. Air Delivery Selection External static pressure drop through the air distribution system has been calculated to be 0.77 inches (19.6 mm) of water gauge. FromTable PD-24 static pressure drop through the electric heater is 0.12 inches (3.0 mm) of water (0.77 + 0.12 = .89 in.) (19.6 + 3.0 = 22.6 mm). EnterTable PD-15 forTWE090A4 at 2500 cfm (1180 l/s) and .90 static pressure.The standard motor at 790 rpm will give the desired airflow. 1.375 x (kW) = kW 1.375 x 0.8 = 1.1 kW NetTotal Cooling Capacity = 79.6 MBh – 3.75 = 75.85 MBh = 23.3 kW - 1.1 = 22.2 kW Net Sensible Cooling Capacity = 57.1 MBh – 3.75 = 53.35 MBh = 16.7 MBh - 1.1 = 15.6 kW Heating Capacity Step 1 — Calculate the building heating load using theTrane calculation form or any other standard accepted method. Step 2 — Size the equipment usingTable PD-9 to match the heating loads at design conditions.The following are building heating requirements: a Total Heating Load: 110 MBh (32.2 kW) b Outdoor Ambient (Winter): 17° F (-8.3° C) DB c Indoor ReturnTemperature: 70° F (21.1° C) DB d Airflow: 2500 cfm (1180 l/s) Table PD-9 indicates the mechanical heating portion of the heat pump will provide 37.5 MBh (11.0 kW) for the winter design conditions. Step 3 — Because 37.5 MBh (11.0 kW) is less than the building’s required heating capacity, a supplementary heater must be selected. 110 - 37.5 = 72.5 MBh (32.2 11.0 = 21.2 kW) minimum heater capacity. FromTable PD-25, the 24.22 kW heater has a capacity of 82,670 Btuh. FromTable 34-1, the 24.22 kW heater at 400V indicates the heater model number is BAYHTRL435A.This heater will be adequate to cover the residual heat capacity needed for the application. 7 Model Number Description Split System Heat Pump Model Nomenclature T W A 0 7 5 A D 0 0 D A 1 2 3 4 5 6 7 8 9 10 11 12 Digits 1, 2, 3 - Product Type Digit 8 - Electrical Characteristics TWA = Split System Heat Pump D = 380-415/3/50 Digits 4, 5, 6 - Nominal Gross Cooling Capacity (MBh) Digit 9, 10 - Factory - Installed Options 00 = Packed Stock 0S = Black Epoxy Coated Coil 075 100 155 200 Digit 11- Minor Design Sequence D = Fourth = = = = 75 100 155 200 Digit 12- Service Digit Digit 7- Major Development Sequence A = First A = Single Compressor B = Dual Compressor Air Handler Model Nomenclature T W E 0 5 0 A D 0 0 C A 1 2 3 4 5 6 7 8 9 10 11 12 Digits 1, 2, 3 - Product Type TWE = Cooling Convertible Digit 8 - Electrical Characteristics D = 380-415/3/50 Digit 9, 10 - Factory - Installed Options Digits 4, 5, 6 - Nominal Gross Cooling Capacity (MBh) 050 075 100 155 200 = = = = = 50 75 100 155 200 00 = Packed Stock Digit 11- Minor Design Sequence C = Third Digit 12- Service Digit A = First Digit 7- Refrigerant Circuit A = Single B = Dual 8 TWA-PRC001-EN General Data (Heat Pumps) Table GD-1 — General Data — Heat Pumps Cooling Performance1 Gross Cooling Capacity, BTUH (KW) Matched Air Handler, BTUH (KW) Heat Pump Only2, BTUH (KW) ARI Net Cooling Capacity3 System Power KW Heat Pump Only Power KW Heating Performance ARI Heating with Matched Air Handler HighTemperature Capacity, BTUH (KW) LowTemperature Capacity, BTUH (KW) Compressor Number Type No. Speeds No. Motors Motor HP (KW) Motor RPM ARI Sound Rating (Bels)4 System Data5 No. Refrigerant Circuits Suction Line, in. (mm) OD Liquid Line, in. (mm) OD Outdoor Coil — Type Tube Size, in. (mm) OD Face Area, sq. ft. (m2) Rows Fins Per Inch (Fins per mm) Outdoor Fan Type No. Used Diameter, in. (mm) DriveType No. Speeds CFM6, (L/S) No. Motors Motor HP (KW) Motor RPM R-22 Refrigerant Charge, Lbs7 (Kg) TWA075A TWA100A 82,000 (23.97) 82,000 (23.97) 80,000 (23.35) 7.36 6.61 109,000 (31.97) 105,000 (30.75) 105,000 (30.75) 10.32 9.22 75,000 (21.82) 47,000 (13.84) 106,000 (31.05) 69,000 (20.29) 1 3D®Scroll 1 1 6.25 (4.7) 2875 8.8 1 3D®Scroll 1 1 8.33 (6.21) 2875 8.8 1 1.375 (34.9) 0.500 (12.7) Plate Fin 0.375 (9.5) 19.2 (1.78) 2 18 (457) Propeller 1 26.00 (660.4) Direct 1 4700 (2218.2) 1 0.33 (.24) 925 18.0 (8.16) 1 1.375 (34.9) 0.500 (12.7) Plate Fin 0.375 (9.5) 24.0 (2.23) 2 18 (457) Propeller 1 28.00 (711) Direct 1 6700 (3161.7) 1 0.75 (.56) 925 24.25 (11.0) Notes: 1. Cooling Performance is rated at 95° F (35° C) ambient, 80° F (26.7° C) entering dry bulb, 67° F (19.4° C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Rated accordance with ARI Standard 210. 2. Condensing Unit Only Gross Cooling Capacity rated at 45° F (7.2° C) saturated suction temperature and at 95° F (35° C) ambient. 3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft. (7.2 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80° F (26.7° C) ambient, 80° F (26.7° C) entering dry bulb, and 67° F (19.4° C) entering wet bulb at ARI rated cfm. 4. ARI Sound Rating is rated in accordance with ARI Standard 270. 5. System Data based on maximum linear length 80 ft. (26.7 m)Maximum lift: suction 60 ft. (18.3 m) liquid 60 ft. (18.3 m) For greater lengths, refer to refrigerant piping applications manual. 6. Outdoor Fan Cfm is rated with standard air-dry coil outdoor. 7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft. (7.6 m) of interconnecting refrigerant lines. TWA-PRC001-EN 9 General Data (Heat Pumps) Table GD-2 General Data — Heat Pumps TWA155B Cooling Performance1 Gross Cooling Capacity, BTUH (KW) Matched Air Handler, BTUH (KW) 166,000 (48.57) Condensing Unit Only2, BTUH (KW) 161,000 (47.04) 3 ARI Net Cooling Capacity 160,000 (46.74) System Power KW 14.98 Condensing Unit Power KW 13.20 Heating Performance ARI Heating with Matched Air Handler HighTemperature Capacity, BTUH (KW) 151,000 (44.27) LowTemperature Capacity, BTUH (KW) 95,000 (27.67) Compressor Number 2 Type 3D®Scroll No. Speeds 1 No. Motors 2 Motor HP 6.25 (4.7) Motor RPM, (KW) 2875 ARI Sound Rating (Bels)4 8.8 System Data5 No. Refrigerant Circuits 2 Suction Line, in. (mm) OD 1.375 (34.9) Liquid Line, in. (mm) OD 0.500 (12.7) Outdoor Coil — Type Plate Fin Tube Size, in. (mm) OD 0.375 (9.5) Face Area, sq. ft. (m2) 38.4 (3.57) Rows 2 Fins Per Inch(mm) 18 (457) Outdoor Fan Type Propeller/Propeller No. Used 2 Diameter, in. (mm) 26.00/26.00 (660.4/660.4) Drive Type Direct/Direct No. Speeds 1 CFM6, (L/S) 9800 (4624.6) No. Motors 2 Motor HP, (KW) 0.33 (.24) Motor RPM 925 R-22 Refrigerant Charge, Lbs7 (Kg) 36.0 (16.32) TWA200B 216,000 (63.24) 209,000 (61.18) 196,000 (61.18) 20.61 18.52 206,000 (60.26) 135,000 (39.66) 2 3D®Scroll 1 2 8.33 (6.21) 2875 8.8 2 1.375 (34.9) 0.500 (12.7) Plate Fin 0.375 (9.5) 48.0 (4.46) 2 18 (457) Propeller/Propeller 2 28.00/28.00 (711/711) Direct/Direct 1 13400 (6323.5) 2 0.75 (.56) 925 48.5 (22.0) Notes: 1. Cooling Performance is rated at 95° F (35° C) ambient, 80° F (26.7° C) entering dry bulb, 67° F (19.4° C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Rated accordance with ARI Standard 210. 2. Condensing Unit Only Gross Cooling Capacity rated at 45° F (7.6° C) saturated suction temperature and at 95° F (35° C) ambient. 3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft. (7.6 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80° F (26.7° C) ambient, 80° F (26.7° C) entering dry bulb, and 67° F (19.4° C) entering wet bulb at ARI rated cfm. 4. ARI Sound Rating is rated in accordance with ARI Standard 270. 5. System Data based on maximum linear length 80 ft. (26.7 m)Maximum lift: suction 60 ft. (18.3 m) liquid 60 ft. (18.3 m) For greater lengths, refer to refrigerant piping applications manual. 6. Outdoor Fan Cfm is rated with standard air-dry coil outdoor. 7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft. (7.6 m) of interconnecting refrigerant lines. 10 TWA-PRC001-EN General Data (Air Handlers) Table GD-3 — General Data — Air Handlers TWE050A TWE075A TWE100A TWE100B System Data1 No. Refrigerant Circuits 1 1 1 2 Suction Line, in. (mm) OD 1.120 (28.4) 1.380 (35.0) 1.380 (35.0) 1.380 (35.0) Liquid Line, in. (mm) OD 0.38 (9.7) 0.50 (12.7) 0.50 (12.7) 0.50 (12.7) Indoor Coil — Type Plate Fin Plate Fin Plate Fin Plate Fin Tube Size, in. (mm) OD 0.375 (9.5) 0.375 (9.5) 0.375 (9.5) 0.375 (9.5) Face Area, sq. ft. (m2) 5.00 (.47) 8.07 (.75) 11.18 (1.0) 11.18 (1.0) Rows 3 3 3 3 Fins Per Inch 12 12 12 12 Refrigerant Control Expansion Valve Expansion Valve Expansion Valve Expansion Valve Drain Connection No. 4 4 4 4 Drain Connection Size, in. (mm) 0.75 (19.0) 0.75 (19.0) 0.75 (19.0) 0.75 (19.0) Drain Connection Type PVC PVC PVC PVC Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used 1 1 1 1 Diameter, in. (mm) 12.0 (304.8) 15.0 (381) 15.0 (381) 15.0 (381) Width, in. (mm) 12.0 (304.8) 15.0 (381) 15.0 (381) 15.0 (381) DriveType Belt Belt Belt Belt No. Speeds 1 1 1 1 CFM, (L/S) 1670 (788.2) 2500 (1179.9) 3325 (1569.2) 3325 (1569.2) No. Motors 1 1 1 1 Motor HP, (KW) — Standard/Oversized 0.75/1.0 (.55/.74) 1.0/1.5 (.74/1.11) 1.5/2.0 (1.11/1.49) 1.5/2.0 (1.11/1.49) Motor RPM (Standard) 1425 1425 1425 1425 Motor Frame Size (Standard) 56 56 56 56 Filters — Type Throwaway Throwaway Throwaway Throwaway Furnished Yes Yes Yes Yes No. 1/1 3 4 4 Recommended Size, in. (mm) 16x20x1/20x20x1 16x25x1 16x25x1 16x25x1 406.4x508x25. 406.4/635/25.4 406.4/635/25.4 406.4/635/25.4 4/508x508x25.4 Table GD-3 — General Data — Continued System Data No. Refrigerant Circuits Suction Line, in. (mm) OD Liquid Line, in. (mm) OD Indoor Coil — Type Tube Size, in. (mm) OD Face Area, sq. ft. (m2) Rows Fins Per Inch Refrigerant Control Drain Connection No. Drain Connection Size, in. (mm) Drain Connection Type Indoor Fan Type No. Used Diameter, in. (mm) Width, in. (mm) DriveType No. Speeds CFM, (L/S) No. Motors Motor HP, (KW) — Standard/Oversized Motor RPM (Standard) Motor Frame Size (Standard) Filters — Type Furnished No. Recommended Size, in. (mm) TWE155B TWE200B 2 1.38 (35.0) 0.500 (12.7) Plate Fin 0.375 (9.5) 16.33 (1.52) 3 12 Expansion Valve 4 1.000 (25.4) PVC FC Centrifugal 2 15.0 (381) 15.0 (381) Belt 1 5000 (2360.0) 1 2 1.38 (35.0) 0.500 (12.7) Plate Fin 0.375 (9.5) 21.63 (2.01) 3 12 Expansion Valve 4 1.000 (25.4) PVC FC Centrifugal 2 15.0 (381) 15.0 (381) Belt 1 6650 (3138.4) 1 2.0/3.0 (1.49/2.24) 1425 145T Throwaway Yes 8 15x20x2 381x508x50.8 3.0/5.0 (2.24/3.72) 1425 184T Throwaway Yes 4/4 16x20x2/16x25x2 406.4x508x50.8/406.4x635x50.8 Notes: 1. ARI certified with various condensing units per ARI Standard 210. Refer to Performance Data section in this catalog. TWA-PRC001-EN 11 Performance Data (System) Table PD-1 — Gross Cooling Capacities (MBh) TWA075A Heat Pump with TWE075A Air Handler 85 Enter. Dry Bulb CFM 2250 2500 2750 3000 ID 61 67 95 73 61 67 Ambient Temperature Entering Wet Bulb 73 61 105 67 115 73 61 67 73 Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 75 75.7 60.5 83.8 50.3 92.4 34.1 73.2 59.2 80.9 49.1 89.1 32.9 70.2 57.7 77.5 47.8 85.3 31.6 66.7 56.0 73.6 46.2 81.1 30.2 80 85 76.2 78.3 70.8 84.0 58.2 92.4 44.8 78.3 84.1 68.4 92.5 55.4 73.7 76.1 69.5 81.1 57.0 89.1 43.6 70.8 68.1 77.6 55.4 85.4 42.2 67.5 66.4 73.8 53.8 81.2 40.7 76.1 81.2 67.1 89.3 54.2 73.6 73.6 77.8 65.6 85.5 52.8 70.6 70.6 74.0 63.9 81.4 51.3 90 82.3 82.3 84.6 78.7 92.7 65.9 80.0 80.0 81.8 77.5 89.4 64.5 77.4 77.4 78.6 76.0 85.6 63.0 74.3 74.3 75.0 74.4 81.5 61.4 75 77.2 63.4 85.3 49.5 93.9 34.7 74.6 62.1 82.3 48.2 90.5 33.6 71.4 60.5 78.8 46.8 86.6 32.2 67.8 58.8 74.8 45.2 82.2 30.6 80 85 77.9 80.9 74.7 85.5 61.0 93.9 46.4 80.9 85.6 72.0 94.1 57.9 75.4 78.6 73.4 82.4 59.5 90.5 45.1 72.4 72.0 78.9 58.0 86.7 43.7 68.9 68.9 75.0 56.3 82.4 42.2 78.6 82.6 70.7 90.7 56.7 75.9 75.9 79.2 69.2 86.8 55.3 72.8 72.8 75.3 67.5 82.6 53.7 90 85.0 85.0 86.4 83.4 94.1 69.1 82.7 82.7 83.6 82.1 90.8 67.8 79.8 79.8 79.9 79.9 87.0 66.3 76.6 76.6 76.7 76.7 82.7 64.7 75 78.5 66.1 86.5 51.2 95.1 35.3 75.7 64.8 83.4 49.9 91.6 34.1 72.5 63.2 79.8 48.4 87.6 32.7 68.9 61.5 75.8 46.8 83.1 31.1 80 85 79.4 83.1 78.5 86.6 63.4 95.2 47.8 83.1 86.9 75.4 95.3 60.3 76.5 80.7 76.5 83.6 62.0 91.7 46.6 73.8 73.8 80.0 60.5 87.7 45.2 70.7 70.7 75.9 58.8 83.3 43.6 80.7 83.9 74.1 91.8 59.0 77.9 77.9 80.4 72.6 87.9 57.6 74.6 74.6 76.5 70.9 83.5 55.8 84.9 85.0 85.0 92.0 71.0 82.0 82.0 82.0 82.0 88.0 69.5 78.6 78.6 78.7 78.7 83.7 67.8 90 87.4 87.4 88.1 87.9 95.4 72.3 84.9 75 79.5 68.8 87.6 52.8 96.1 35.8 76.8 67.4 84.4 51.5 92.5 34.5 73.5 65.9 80.7 50.0 88.4 33.1 69.8 64.1 76.6 48.4 83.9 31.5 80 85 80.7 85.1 80.7 87.7 65.8 96.2 49.2 85.1 88.1 78.8 96.4 62.6 78.3 82.6 78.3 84.6 64.4 92.6 47.9 75.4 75.4 80.9 62.8 88.6 46.5 72.2 72.2 76.8 61.1 84.1 45.0 82.6 85.0 77.4 92.7 61.1 79.6 79.6 81.5 75.9 88.7 59.6 76.3 76.3 77.5 74.2 84.3 58.0 90 89.5 89.5 89.6 89.6 96.5 75.4 86.9 86.9 87.0 87.0 93.0 74.1 83.8 83.8 83.9 83.9 89.0 72.5 80.4 80.4 80.5 80.5 84.6 70.9 Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm. Table PD-1 — Gross Cooling Capacities (KW) TWA075A Heat Pump with TWE075A Air Handler 85 Enter. Dry Bulb 61 67 95 73 61 67 Ambient Temperature Entering Wet Bulb 73 61 105 67 115 73 61 67 73 L/S ID Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 1062 24 22.2 17.7 24.5 14.7 27.1 10.0 21.4 17.3 23.7 14.4 26.1 9.6 20.5 16.9 22.7 14.0 25.0 9.3 19.5 16.4 21.6 13.5 23.7 8.8 27 29 22.3 22.9 20.7 24.6 17.0 27.1 13.1 22.9 24.6 20.0 27.1 16.2 21.6 22.3 20.4 23.7 16.7 26.1 12.8 20.7 19.9 22.7 16.2 25.0 12.4 19.8 19.5 21.6 15.7 23.8 11.9 22.3 23.8 19.6 26.1 15.9 21.5 21.5 22.8 19.2 25.0 15.5 20.7 20.7 21.7 18.7 23.8 15.0 32 24.1 24.1 24.8 23.1 27.1 19.3 23.4 23.4 23.9 22.7 26.2 18.9 22.7 22.7 23.0 22.3 25.1 18.5 21.8 21.8 22.0 21.8 23.9 18.0 24 22.6 18.6 25.0 14.5 27.5 10.2 21.8 18.2 24.1 14.1 26.5 27 29 22.8 23.7 21.9 25.0 17.9 27.5 13.6 23.7 25.1 21.1 27.5 17.0 22.1 23.0 21.5 24.1 17.4 26.5 13.2 21.2 21.1 23.1 17.0 25.4 12.8 20.2 20.2 21.9 16.5 24.1 12.4 23.0 24.2 20.7 26.6 16.6 22.2 22.2 23.2 20.2 25.4 16.2 21.3 21.3 22.1 19.8 24.2 15.7 32 24.9 24.9 25.3 24.4 27.6 20.2 24.2 24.2 24.5 24.0 26.6 19.9 23.4 23.4 23.4 23.4 25.5 19.4 22.4 22.4 22.5 22.5 24.2 18.9 1180 1298 1416 9.8 20.9 17.7 23.1 13.7 25.3 9.4 9.6 19.9 17.2 21.9 13.2 24.1 24 23.0 19.4 25.3 15.0 27.8 10.3 22.2 19.0 24.4 14.6 26.8 10.0 21.2 18.5 23.4 14.2 25.6 27 29 23.3 24.3 23.0 25.4 18.5 27.9 14.0 24.3 25.4 22.1 27.9 17.6 22.4 23.6 22.4 24.5 18.2 26.8 13.6 21.6 21.6 23.4 17.7 25.7 13.2 20.7 20.7 22.2 17.2 24.4 12.8 23.6 24.6 21.7 26.9 17.3 22.8 22.8 23.5 21.3 25.7 16.9 21.9 21.9 22.4 20.8 24.4 16.3 32 25.6 25.6 25.8 25.7 27.9 21.2 24.9 24.9 24.9 24.9 26.9 20.8 24.0 24.0 24.0 24.0 25.8 20.3 23.0 23.0 23.0 23.0 24.5 19.9 24 23.3 20.1 25.6 15.5 28.1 10.5 22.5 19.7 24.7 15.1 27.1 10.1 21.5 19.3 23.6 14.6 25.9 27 29 23.6 24.9 23.6 25.7 19.3 28.2 14.4 24.9 25.8 23.1 28.2 18.3 22.9 24.2 22.9 24.8 18.9 27.1 14.0 22.1 22.1 23.7 18.4 25.9 13.6 21.1 21.1 22.5 17.9 24.6 13.2 24.2 24.9 22.7 27.1 17.9 23.3 23.3 23.8 22.2 26.0 17.5 22.3 22.3 22.7 21.7 24.7 17.0 32 26.2 26.2 26.2 26.2 28.2 22.1 25.4 25.4 25.5 25.5 27.2 21.7 24.5 24.5 24.6 24.6 26.0 21.2 23.5 23.5 23.6 23.6 24.8 20.8 9.7 20.2 18.0 22.2 13.7 24.3 9.0 20.4 18.8 22.4 14.2 24.6 9.1 9.2 Note: All temperatures are in degrees Celsius. Airflow is in liters per second. 12 TWA-PRC001-EN Performance Data (System) Table PD-2 — Gross Cooling Capacities (MBh) TWA100A Heat Pump with TWE100A Air Handler 85 Enter. Dry Bulb CFM 3000 3325 3650 3975 ID 61 67 95 73 61 67 Ambient Temperature Entering Wet Bulb 73 61 105 67 115 73 61 67 73 Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 75 101.6 80.9 111.8 67.1 122.7 45.2 80 85 102.1 94.6 112.0 77.2 122.7 59.2 98.4 92.6 107.8 75.3 118.0 57.5 94.4 90.6 103.4 73.5 113.2 55.7 90.4 88.6 98.8 71.5 108.2 53.8 104.6 104.6 112.1 90.6 122.8 72.8 101.3 101.3 107.9 88.7 118.2 71.1 97.9 97.9 103.5 86.7 113.4 69.3 94.3 94.3 98.9 84.6 108.4 67.4 97.7 90 109.6 109.6 112.7 104.1 122.9 86.4 106.3 106.3 108.6 102.2 118.3 84.6 102.8 102.8 104.4 100.2 113.5 82.8 99.1 99.1 100.1 98.2 108.5 80.7 99.4 79.0 107.6 65.4 118.1 43.6 93.6 76.9 103.2 63.6 113.2 41.9 89.4 74.8 98.6 61.7 108.2 40.1 75 103.4 84.5 113.7 65.6 124.6 46.0 80 85 104.3 99.5 113.9 80.6 124.6 61.1 100.4 97.5 109.5 78.7 119.8 59.3 96.4 95.5 104.8 76.6 114.9 57.5 92.0 92.0 100.2 74.6 109.7 55.6 107.8 107.8 114.0 95.0 124.7 75.9 104.4 104.4 109.6 93.1 120.0 74.1 100.8 100.8 105.2 91.1 115.0 72.3 97.0 97.0 100.6 89.0 109.9 70.4 82.5 109.4 63.8 119.8 44.4 95.2 80.5 104.8 61.9 114.8 42.7 90.9 78.3 100.1 59.9 109.6 40.8 90 113.0 113.0 114.9 109.8 124.8 90.6 109.5 109.5 110.8 107.9 120.0 88.6 105.8 105.8 106.5 105.9 115.1 86.7 102.0 102.0 101.9 101.9 110.0 84.7 75 105.0 88.0 115.3 67.7 126.1 46.8 100.9 85.9 110.8 65.8 121.2 45.0 96.6 83.9 106.1 63.9 116.1 43.2 92.2 81.7 101.3 62.0 110.8 41.3 80 85 106.2 104.2 115.4 83.8 126.1 62.8 102.3 102.3 110.9 81.7 121.3 61.1 98.0 98.0 106.2 79.7 116.2 59.2 94.3 94.3 101.4 77.6 111.0 57.4 110.6 110.6 115.6 99.3 126.3 78.8 107.0 107.0 111.2 97.3 121.4 77.0 103.3 103.3 106.7 95.3 116.4 75.2 99.4 99.4 102.0 93.3 111.1 73.3 90 115.9 115.9 117.0 115.4 126.3 94.4 112.3 112.3 112.2 112.2 121.5 92.5 108.4 108.4 108.4 108.4 116.5 90.5 104.5 104.5 104.4 104.4 111.3 88.5 75 106.3 91.3 116.6 69.7 127.5 47.4 80 85 107.4 107.4 116.7 86.6 127.5 64.5 103.9 103.9 112.1 84.7 122.5 62.7 100.1 100.1 107.4 82.6 117.3 60.9 96.2 96.2 102.5 80.5 112.0 59.0 113.0 113.0 117.1 103.4 127.6 81.6 109.3 109.3 112.7 101.5 122.7 79.8 105.5 105.5 108.1 99.4 117.5 78.0 101.5 101.5 103.3 97.4 112.2 76.1 90 118.5 118.5 118.4 118.4 127.7 98.2 114.8 114.8 114.7 114.7 122.8 96.3 110.8 110.8 110.7 110.7 117.6 94.3 106.6 106.6 106.6 106.6 112.4 92.3 102.2 89.3 112.0 67.8 122.4 45.6 97.9 87.2 107.3 65.9 117.2 43.7 93.4 85.0 102.4 63.9 111.8 41.9 Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm. Table PD-2 — Gross Cooling Capacities (KW) TWA100A Heat Pump with TWE100A Air Handler 85 Enter. Dry Bulb 61 67 95 73 61 67 Ambient Temperature Entering Wet Bulb 73 61 105 67 115 73 61 67 73 L/S ID Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 1416 24 29.7 23.7 32.7 19.7 35.9 13.2 28.6 23.1 31.5 19.1 34.6 12.8 27.4 22.5 30.2 18.6 33.1 12.3 26.2 21.9 28.9 18.1 31.7 11.8 27 29 29.9 30.6 27.7 32.8 22.6 35.9 17.3 30.6 32.8 26.5 35.9 21.3 28.8 29.7 27.1 31.6 22.1 34.6 16.8 27.6 26.5 30.3 21.5 33.2 16.3 26.5 25.9 28.9 20.9 31.7 15.8 29.7 31.6 26.0 34.6 20.8 28.7 28.7 30.3 25.4 33.2 20.3 27.6 27.6 29.0 24.8 31.7 19.7 32 32.1 32.1 33.0 30.5 36.0 25.3 31.1 31.1 31.8 29.9 34.6 24.8 30.1 30.1 30.6 29.3 33.2 24.2 29.0 29.0 29.3 28.8 31.8 23.6 24 30.3 24.7 33.3 19.2 36.5 13.5 29.1 24.2 32.0 18.7 35.1 13.0 27.9 23.6 30.7 18.1 33.6 12.5 26.6 22.9 29.3 17.5 32.1 11.9 27 29 30.5 31.6 29.1 33.3 23.6 36.5 17.9 31.6 33.4 27.8 36.5 22.2 29.4 30.6 28.6 32.1 23.0 35.1 17.4 28.2 28.0 30.7 22.4 33.6 16.8 26.9 26.9 29.3 21.8 32.1 16.3 30.6 32.1 27.2 35.1 21.7 29.5 29.5 30.8 26.7 33.7 21.2 28.4 28.4 29.4 26.1 32.2 20.6 32 33.1 33.1 33.6 32.2 36.5 26.5 32.1 32.1 32.4 31.6 35.1 25.9 31.0 31.0 31.2 31.0 33.7 25.4 29.9 29.9 29.8 29.8 32.2 24.8 1569 1723 1876 24 30.7 25.8 33.8 19.8 36.9 13.7 29.5 25.2 32.4 19.3 35.5 13.2 28.3 24.6 31.1 18.7 34.0 12.7 27.0 23.9 29.7 18.1 32.5 12.1 27 29 31.1 32.4 30.5 33.8 24.5 36.9 18.4 32.4 33.8 29.1 37.0 23.1 30.0 31.3 29.9 32.5 23.9 35.5 17.9 28.7 28.7 31.1 23.3 34.0 17.3 27.6 27.6 29.7 22.7 32.5 16.8 31.3 32.6 28.5 35.6 22.6 30.2 30.2 31.2 27.9 34.1 22.0 29.1 29.1 29.9 27.3 32.5 21.5 32 33.9 33.9 34.3 33.8 37.0 27.6 32.9 32.9 32.8 32.8 35.6 27.1 31.8 31.8 31.7 31.7 34.1 26.5 30.6 30.6 30.6 30.6 32.6 25.9 24 31.1 26.7 34.1 20.4 37.3 13.9 29.9 26.1 32.8 19.9 35.9 13.3 28.7 25.5 31.4 19.3 34.3 12.8 27.3 24.9 30.0 18.7 32.7 12.3 27 29 31.5 33.1 31.5 34.2 25.4 37.3 18.9 33.1 34.3 30.3 37.4 23.9 30.4 32.0 30.4 32.8 24.8 35.9 18.4 29.3 29.3 31.4 24.2 34.4 17.8 28.2 28.2 30.0 23.6 32.8 17.3 32.0 33.0 29.7 35.9 23.4 30.9 30.9 31.6 29.1 34.4 22.8 29.7 29.7 30.3 28.5 32.9 22.3 32 34.7 34.7 34.7 34.7 37.4 28.8 33.6 33.6 33.6 33.6 35.9 28.2 32.4 32.4 32.4 32.4 34.4 27.6 31.2 31.2 31.2 31.2 32.9 27.0 Note: All temperatures are in degrees Celsius. Airflow is in liters per second. TWA-PRC001-EN 13 Performance Data (System) Table PD-3 — Gross Cooling Capacities (MBh) TWA155A Heat Pump with TWE155A Air Handler 85 CFM 4500 5000 5500 6000 Enter. Dry Bulb 61 67 95 73 61 67 Ambient Temperature Entering Wet Bulb 73 61 105 67 115 73 61 67 73 ID Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 75 152.8 121.6 169.0 101.2 186.3 68.7 147.6 119.0 163.1 98.8 179.6 66.4 141.5 116.0 156.2 96.0 171.9 63.7 134.4 112.5 148.4 92.9 163.4 60.8 80 85 153.5 142.2 169.3 117.1 186.4 90.4 148.5 139.6 163.5 114.7 179.7 87.9 142.6 136.6 156.4 111.4 172.1 85.0 135.8 133.3 148.7 108.0 163.7 82.0 157.6 157.6 169.5 137.4 186.6 111.5 153.3 153.3 163.7 134.8 180.0 109.0 148.1 148.1 156.9 131.8 172.5 106.2 142.1 142.1 149.2 128.4 164.1 103.1 90 165.7 165.7 170.4 158.1 186.8 132.2 161.1 161.1 164.8 155.5 180.2 129.6 155.7 155.7 158.2 152.6 172.7 126.6 149.6 149.6 150.9 149.3 164.3 123.4 75 155.8 127.4 172.1 99.7 189.4 70.0 150.4 124.7 166.0 97.1 182.4 67.6 144.0 121.6 158.8 94.2 174.5 64.9 136.7 118.1 150.8 90.9 165.7 61.8 80 85 156.9 150.0 172.2 122.3 189.5 93.4 151.8 147.5 166.1 119.7 182.6 90.9 145.7 144.4 159.1 116.6 174.7 88.1 138.7 138.7 151.1 113.1 166.0 84.9 162.9 162.9 172.7 144.6 189.8 116.5 158.3 158.3 166.6 141.9 182.9 114.0 152.8 152.8 159.6 138.9 175.1 111.2 146.5 146.5 151.8 135.5 166.5 108.0 90 171.3 171.3 174.1 167.4 189.9 138.9 166.4 166.4 168.3 164.8 183.1 136.2 160.7 160.7 160.9 160.9 175.4 133.2 154.3 154.3 154.4 154.4 166.8 129.9 75 158.3 132.9 174.6 103.0 191.8 71.3 152.8 130.2 168.3 100.5 184.7 68.7 146.2 127.0 161.0 97.5 176.5 65.9 138.8 123.5 152.7 94.2 167.5 62.7 80 85 160.1 157.7 174.8 127.4 192.0 96.3 154.1 154.1 168.6 124.6 184.9 93.8 148.6 148.6 161.3 121.5 176.9 90.9 142.3 142.3 153.1 118.0 168.0 87.8 167.4 167.4 175.3 151.5 192.3 121.3 162.6 162.6 169.2 148.8 185.3 118.8 156.8 156.8 162.0 145.7 177.1 115.4 150.3 150.3 154.0 142.3 168.3 112.1 90 176.1 176.1 177.5 176.4 192.6 145.3 171.0 171.0 171.2 171.2 185.6 142.6 165.0 165.0 165.2 165.2 177.6 139.6 158.3 158.3 158.5 158.5 168.9 136.2 75 160.5 138.2 176.8 106.3 193.9 72.2 154.8 135.5 170.3 103.7 186.6 69.6 148.1 132.3 162.8 100.7 178.3 66.7 140.6 128.7 154.4 97.4 169.1 63.6 80 85 162.6 162.5 177.0 132.2 194.1 99.1 157.7 157.7 170.6 129.4 186.9 96.5 151.9 151.9 163.2 126.3 178.7 93.7 145.4 145.4 154.8 122.7 169.7 90.5 171.5 171.5 177.7 158.2 194.3 125.6 166.4 166.4 171.4 155.5 187.1 122.9 160.4 160.4 164.1 152.4 179.0 119.8 153.6 153.6 156.1 148.9 170.1 116.4 90 180.4 180.4 180.6 180.6 194.8 151.5 175.1 175.1 175.2 175.2 187.6 148.8 168.9 168.9 169.0 169.0 179.5 145.7 161.9 161.9 162.1 162.1 170.6 142.3 Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm. Table PD-3 — Gross Cooling Capacities (KW) TWA155A Heat Pump with TWE155A Air Handler 85 Enter. Dry Bulb 61 67 95 73 61 67 Ambient Temperature Entering Wet Bulb 73 61 105 67 115 73 61 67 73 L/S ID Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 2124 24 44.7 35.6 49.5 29.6 54.6 20.1 43.2 34.8 47.8 28.9 52.6 19.4 41.4 34.0 45.7 28.1 50.3 18.7 39.4 32.9 43.5 27.2 47.8 17.8 27 29 44.9 46.1 41.6 49.6 34.3 54.6 26.5 46.1 49.6 40.2 54.6 32.6 43.5 44.9 40.9 47.9 33.6 52.6 25.7 41.7 40.0 45.8 32.6 50.4 24.9 39.8 39.0 43.5 31.6 47.9 24.0 44.9 47.9 39.5 52.7 31.9 43.4 43.4 45.9 38.6 50.5 31.1 41.6 41.6 43.7 37.6 48.0 30.2 32 48.5 48.5 49.9 46.3 54.7 38.7 47.2 47.2 48.2 45.5 52.8 37.9 45.6 45.6 46.3 44.7 50.6 37.1 43.8 43.8 44.2 43.7 48.1 36.1 24 45.6 37.3 50.4 29.2 55.4 20.5 44.0 36.5 48.6 28.4 53.4 19.8 42.2 35.6 46.5 27.6 51.1 19.0 40.0 34.6 44.2 26.6 48.5 18.1 27 29 46.0 47.7 43.9 50.4 35.8 55.5 27.4 47.7 50.6 42.3 55.6 34.1 44.4 46.3 43.2 48.6 35.0 53.5 26.6 42.7 42.3 46.6 34.1 51.2 25.8 40.6 40.6 44.2 33.1 48.6 24.9 46.3 48.8 41.6 53.6 33.4 44.7 44.7 46.7 40.7 51.3 32.5 42.9 42.9 44.4 39.7 48.7 31.6 32 50.1 50.1 51.0 49.0 55.6 40.7 48.7 48.7 49.3 48.3 53.6 39.9 47.1 47.1 47.1 47.1 51.3 39.0 45.2 45.2 45.2 45.2 48.8 38.0 2360 2596 2832 24 46.4 38.9 51.1 30.2 56.2 20.9 44.7 38.1 49.3 29.4 54.1 20.1 42.8 37.2 47.1 28.6 51.7 19.3 40.6 36.2 44.7 27.6 49.0 18.4 27 29 46.9 49.0 46.2 51.2 37.3 56.2 28.2 49.0 51.3 44.4 56.3 35.5 45.1 47.6 45.1 49.4 36.5 54.1 27.5 43.5 43.5 47.2 35.6 51.8 26.6 41.7 41.7 44.8 34.6 49.2 25.7 47.6 49.5 43.6 54.3 34.8 45.9 45.9 47.4 42.7 51.8 33.8 44.0 44.0 45.1 41.7 49.3 32.8 32 51.6 51.6 52.0 51.7 56.4 42.6 50.1 50.1 50.1 50.1 54.3 41.8 48.3 48.3 48.4 48.4 52.0 40.9 46.4 46.4 46.4 46.4 49.4 39.9 24 47.0 40.5 51.8 31.1 56.8 21.1 45.3 39.7 49.9 30.4 54.6 20.4 43.4 38.7 47.7 29.5 52.2 19.5 41.2 37.7 45.2 28.5 49.5 18.6 27 29 47.6 50.2 47.6 51.8 38.7 56.8 29.0 50.2 52.0 46.3 56.9 36.8 46.2 48.7 46.2 50.0 37.9 54.7 28.3 44.5 44.5 47.8 37.0 52.3 27.4 42.6 42.6 45.3 35.9 49.7 26.5 48.7 50.2 45.5 54.8 36.0 47.0 47.0 48.1 44.6 52.4 35.1 45.0 45.0 45.7 43.6 49.8 34.1 32 52.8 52.8 52.9 52.9 57.0 44.4 51.3 51.3 51.3 51.3 54.9 43.6 49.4 49.4 49.5 49.5 52.6 42.7 47.4 47.4 47.5 47.5 50.0 41.7 Note: All temperatures are in degrees Celsius. Airflow is in liters per second. 14 TWA-PRC001-EN Performance Data (System) Table PD-4 — Gross Cooling Capacities (MBh) TWA200A Heat Pump with TWE200A Air Handler 85 Enter. Dry Bulb 61 67 95 73 61 67 Ambient Temperature Entering Wet Bulb 73 61 105 67 115 73 61 67 73 CFM ID Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 6000 75 200.7 159.3220.9132.5242.6 89.4 192.9 155.4212.4129.1233.3 86.1 184.8 151.3 203.6125.5223.6 82.8 176.4 147.1 194.5 121.8 213.6 79.3 80 85 201.5 186.0 221.2 152.1 242.5 117.0 194.0 182.1 212.8 148.5 233.3 113.4 186.2 178.1 204.0 144.7 223.7 109.8 178.1 174.0 194.7 140.4 213.8 106.2 206.2 206.2 221.4 178.3 242.8 143.7 199.7 199.7 213.0 174.4 233.6 140.2 192.9 192.9 204.3 170.5 224.0 136.5 185.8 185.8 195.2 166.4 214.1 132.8 90 216.2 216.2 222.3 204.7 243.0 170.3 209.5 209.5 214.2 200.8 233.8 166.8 202.5 202.5 205.8 196.9 224.1 162.6 195.2 195.2 197.2 193.0 214.3 158.7 6675 7350 8025 75 204.4 166.6 224.8 129.6 246.5 91.1 80 85 205.8 195.9 225.1 159.0 246.5 120.7 198.1 192.0 216.2 154.9 236.9 117.2 190.2 188.0 207.2 151.0 227.1 113.6 181.5 181.5 197.9 146.9 216.8 109.8 212.7 212.7 225.3 187.3 246.7 149.9 205.9 205.9 216.7 183.3 237.2 146.3 198.8 198.8 207.7 179.3 227.4 142.7 191.4 191.4 198.6 175.3 217.2 138.9 196.4 162.6 216.1 125.9 236.9 87.8 188.1 158.5 207.0 122.1 226.9 84.3 179.4 154.2 197.6 118.3 216.6 80.6 90 223.1 223.1 226.9 216.3 246.8 178.4 216.1 216.1 218.7 212.4 237.3 174.6 208.8 208.8 210.2 208.5 227.6 170.8 201.2 201.2 201.0 201.0 217.4 166.8 75 207.6 173.6 228.0 133.8 249.6 92.7 199.4 169.5 219.1 130.1 239.8 89.1 190.8 165.4 209.8 126.3 229.6 85.5 182.1 161.1 200.2 122.4 219.1 81.8 80 85 209.7 205.5 228.1 165.1 249.7 124.3 202.0 201.6 219.3 161.2 239.9 120.8 193.6 193.6 210.0 157.2 229.8 117.1 186.1 186.1 200.5 153.0 219.4 113.4 218.4 218.4 228.6 195.9 250.0 155.8 211.3 211.3 219.9 192.0 240.3 152.2 203.9 203.9 210.8 187.9 230.2 148.5 196.2 196.2 201.5 183.8 219.8 144.8 90 229.1 229.1 231.1 227.5 250.1 186.4 221.9 221.9 221.7 221.7 240.4 182.5 214.3 214.3 214.1 214.1 230.4 178.6 206.3 206.3 206.2 206.2 220.0 174.6 75 210.3 180.3 230.8 137.8 252.3 93.8 202.0 176.2 221.6 134.1 242.3 90.3 193.3 172.0 212.1 130.3 231.9 86.6 184.4 167.7 202.4 126.4 221.1 82.8 80 85 212.4 212.4 231.0 171.2 252.4 127.7 205.3 205.3 221.9 167.2 242.5 124.2 197.8 197.8 212.5 163.1 232.1 120.5 190.1 190.1 202.8 159.0 221.5 116.7 223.4 223.4 231.6 204.3 252.7 161.5 216.1 216.1 222.8 200.3 242.8 157.9 208.4 208.4 213.6 196.2 232.3 153.7 200.5 200.5 204.1 192.1 221.7 149.7 90 234.5 234.5 234.3 234.3 252.9 194.0 227.0 227.0 226.8 226.8 243.1 190.1 219.0 219.0 218.9 218.9 232.8 186.2 210.8 210.8 210.7 210.7 222.2 182.1 Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm. Table PD-4 — Gross Cooling Capacities (KW) TWA200A Heat Pump with TWE200A Air Handler 85 Enter. Dry Bulb 61 67 95 73 61 67 AmbientTemperature Entering Wet Bulb 73 61 105 67 115 73 61 67 73 L/S ID Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 2832 24 58.8 46.7 64.7 38.8 71.0 26.2 56.5 45.5 62.2 37.8 68.3 25.2 54.1 44.3 59.6 36.7 65.5 24.2 51.6 43.1 57.0 35.7 62.5 23.2 27 29 59.0 60.4 54.5 64.8 44.5 71.0 34.2 60.4 64.8 52.2 71.1 42.1 56.8 58.5 53.3 62.3 43.5 68.3 33.2 54.5 52.1 59.7 42.4 65.5 32.2 52.1 50.9 57.0 41.1 62.6 31.1 58.5 62.4 51.1 68.4 41.0 56.5 56.5 59.8 49.9 65.6 40.0 54.4 54.4 57.2 48.7 62.7 38.9 32 63.3 63.3 65.1 59.9 71.2 49.9 61.3 61.3 62.7 58.8 68.5 48.8 59.3 59.3 60.3 57.7 65.6 47.6 57.2 57.2 57.7 56.5 62.7 46.5 24 59.9 48.8 65.8 37.9 72.2 26.7 57.5 47.6 63.3 36.9 69.4 25.7 55.1 46.4 60.6 35.8 66.4 24.7 52.5 45.2 57.9 34.6 63.4 23.6 27 29 60.3 62.3 57.4 65.9 46.6 72.2 35.4 62.3 66.0 54.8 72.2 43.9 58.0 60.3 56.2 63.3 45.4 69.4 34.3 55.7 55.0 60.7 44.2 66.5 33.3 53.1 53.1 57.9 43.0 63.5 32.2 60.3 63.4 53.7 69.5 42.8 58.2 58.2 60.8 52.5 66.6 41.8 56.0 56.0 58.1 51.3 63.6 40.7 32 65.3 65.3 66.4 63.3 72.2 52.2 63.3 63.3 64.0 62.2 69.5 51.1 61.1 61.1 61.6 61.1 66.6 50.0 58.9 58.9 58.9 58.9 63.7 48.8 24 60.8 50.8 66.8 39.2 73.1 27.1 58.4 49.6 64.1 38.1 70.2 26.1 55.9 48.4 61.4 37.0 67.2 25.0 53.3 47.2 58.6 35.8 64.1 23.9 27 29 61.4 64.0 60.2 66.8 48.3 73.1 36.4 64.0 66.9 57.4 73.2 45.6 59.1 61.9 59.0 64.2 47.2 70.3 35.4 56.7 56.7 61.5 46.0 67.3 34.3 54.5 54.5 58.7 44.8 64.2 33.2 61.9 64.4 56.2 70.3 44.6 59.7 59.7 61.7 55.0 67.4 43.5 57.5 57.5 59.0 53.8 64.4 42.4 65.0 64.9 64.9 70.4 53.4 62.7 62.7 62.7 62.7 67.5 52.3 60.4 60.4 60.4 60.4 64.4 51.1 3150 3469 3787 32 67.1 67.1 67.7 66.6 73.2 54.6 65.0 24 61.6 52.8 67.6 40.4 73.9 27.5 59.1 51.6 64.9 39.3 70.9 26.4 56.6 50.4 62.1 38.2 67.9 25.4 54.0 49.1 59.3 37.0 64.7 24.3 27 29 62.2 65.4 62.2 67.6 50.1 73.9 37.4 65.4 67.8 59.8 74.0 47.3 60.1 63.3 60.1 65.0 49.0 71.0 36.4 57.9 57.9 62.2 47.8 68.0 35.3 55.7 55.7 59.4 46.5 64.9 34.2 63.3 65.2 58.6 71.1 46.2 61.0 61.0 62.5 57.5 68.0 45.0 58.7 58.7 59.8 56.3 64.9 43.8 32 68.7 68.7 68.6 68.6 74.1 56.8 66.5 66.5 66.4 66.4 71.2 55.7 64.1 64.1 64.1 64.1 68.2 54.5 61.7 61.7 61.7 61.7 65.1 53.3 Note: All temperatures are in degrees Celsius. Airflow is in liters per second. TWA-PRC001-EN 15 Performance Data (TWA075A) Table PD-5 — Gross Cooling Performance (MBh) TWA075A Heat Pump Only ODTemp Suction ReferenceTemperature °F °F 65 75 85 95 30 35 40 45 50 55 Head press PSIG 165 170 176 182 188 195 Cap. Btuh/1000 OD Unit KW 70.0 4.58 77.4 4.67 85.1 4.78 93.1 4.89 101.3 5.02 109.6 5.14 Head press PSIG Cap. Btuh/1000 191 68.2 197 75.2 203 82.5 209 90.1 215 97.8 222 105.6 OD Unit KW 5.04 5.15 5.27 5.39 5.52 5.65 Head press PSIG Cap. Btuh/1000 219 65.5 225 72.3 231 79.2 238 86.4 245 93.6 252 101.1 OD Unit KW 5.59 5.71 5.84 5.97 6.10 6.24 Head press PSIG Cap. Btuh/1000 250 62.3 256 68.7 263 75.3 270 82.0 277 88.9 284 95.9 OD Unit KW 6.22 6.35 6.48 6.61 6.74 6.88 Head press PSIG 283 289 296 304 311 319 105 Cap. Btuh/1000 OD Unit KW 58.6 6.93 64.6 7.06 70.8 7.18 77.1 7.31 83.7 7.45 90.3 7.59 Head press PSIG 318 325 332 340 347 355 115 Cap. Btuh/1000 OD Unit KW 54.4 7.72 60.0 7.83 65.8 7.95 71.8 8.08 78.0 8.22 84.4 8.36 Table PD-5 — Gross Cooling Performance (KW) TWA075A Heat Pump Only ODTemp Suction ReferenceTemperature °C °C 18.3 23.9 29.4 35.0 40.6 46.1 48.9 16 Head pressure (kPA) Capacity (kW) -1.1 1.7 4.4 7.2 10 12.8 1136 20.5 1173 22.6 1213 24.9 1255 27.2 1298 29.7 1343 32.1 OD Unit Power (kW) 4.58 4.67 4.78 4.89 5.02 5.14 Head pressure (kPA) Capacity (kW) 1315 20.0 1355 22.0 1397 24.2 1440 26.4 1484 28.6 1531 30.9 OD Unit Power (kW) 5.04 5.15 5.27 5.39 5.52 5.65 Head pressure (kPA) Capacity (kW) 1509 19.2 1552 21.2 1596 23.2 1642 25.3 1689 27.4 1738 29.6 OD Unit Power (kW) 5.59 5.71 5.84 5.97 6.10 6.24 Head pressure (kPA) 1721 1766 1812 1860 1909 1959 Capacity (kW) OD Unit Power (kW) 18.3 6.22 20.1 6.35 22.0 6.48 24.0 6.61 26.0 6.74 28.1 6.88 Head pressure (kPA) 1948 1995 2043 2093 2144 2197 Capacity (kW) OD Unit Power (kW) 17.2 6.93 18.9 7.06 20.7 7.18 22.6 7.31 24.5 7.45 26.5 7.59 Head pressure (kPA) 2192 2240 2290 2341 2395 2450 Capacity (kW) OD Unit Power (kW) 15.9 7.72 17.6 7.83 19.3 7.95 21.0 8.08 22.8 8.22 24.7 8.36 Head pressure (kPA) Capacity (kW) OD Unit Power (kW) 2320 15.3 8.13 2369 16.9 8.24 2419 18.5 8.36 2471 20.2 8.49 2526 22.0 8.62 2583 23.8 8.76 TWA-PRC001-EN Performance Data (TWA100A) Table PD-6— Gross Cooling Performance (MBh) TWA100A Heat Pump Only ODTemp Suction ReferenceTemperature °F °F 30 35 40 45 50 55 65 Head press PSIG Cap. Btuh/1000 OD Unit KW 175 94.8 6.26 181 104.0 6.41 187 113.6 6.57 194 123.5 6.74 201 133.7 6.93 208 144.2 7.12 75 Head press PSIG Cap. Btuh/1000 OD Unit KW 200 90.4 6.92 207 99.1 7.08 213 108.1 7.25 220 117.5 7.44 227 127.3 7.64 235 137.3 7.85 85 Head press PSIG Cap. Btuh/1000 OD Unit KW 229 85.7 7.70 235 93.9 7.88 242 102.5 8.07 250 111.5 8.27 257 120.8 8.49 265 130.4 8.71 95 Head press PSIG Cap. Btuh/1000 OD Unit KW 259 80.7 8.60 266 88.6 8.79 274 96.8 9.00 282 105.4 9.22 290 114.2 9.44 298 123.3 9.67 105 Head press PSIG Cap. Btuh/1000 OD Unit KW 293 75.5 9.60 300 83.0 9.82 308 91.0 10.05 316 99.2 10.28 325 107.6 10.51 334 116.2 10.74 115 Head press PSIG Cap. Btuh/1000 OD Unit KW 328 70.0 10.72 337 77.4 10.96 345 85.0 11.21 354 92.9 11.45 363 100.9 11.69 372 109.0 11.92 Table PD-6 — Gross Cooling Performance (MBh) TWA100A Heat Pump Only ODTemp Suction ReferenceTemperature °F °C 18.3 23.9 29.4 35.0 40.6 46.1 TWA-PRC001-EN -1.1 1.7 4.4 7.2 10 12.8 Head pressure (kPA) 1206 1247 1290 1336 1383 1432 Capacity (kW) OD Unit Power (kW) 27.7 6.26 30.4 6.41 33.3 6.57 36.2 6.74 39.2 6.93 42.2 7.12 Head pressure (kPA) 1382 1425 1470 1518 1568 1621 Capacity (kW) OD Unit Power (kW) 26.5 6.92 29.0 7.08 31.7 7.25 34.4 7.44 37.3 7.64 40.2 7.85 Head pressure (kPA) Capacity (kW) 1576 25.1 1622 27.5 1670 30.0 1721 32.7 1774 35.4 1829 38.2 OD Unit Power (kW) 7.70 7.88 8.07 8.27 8.49 8.71 Head pressure (kPA) Capacity (kW) 1788 23.6 1837 25.9 1888 28.3 1941 30.9 1997 33.5 2055 36.1 OD Unit Power (kW) 8.60 8.79 9.00 9.22 9.44 9.67 Head pressure (kPA) Capacity (kW) 2017 22.1 2069 24.3 2124 26.6 2181 29.0 2240 31.5 2300 34.0 OD Unit Power (kW) 9.60 9.82 10.05 10.28 10.51 10.74 Head pressure (kPA) 2265 2321 2379 2440 2502 2565 Capacity (kW) OD Unit Power (kW) 20.5 10.72 22.7 10.96 24.9 11.21 27.2 11.45 29.5 11.69 31.9 11.92 17 Performance Data (TWA155A) Table PD-7 — Gross Cooling Performance (MBh) TWA155A Heat Pump Only OD Temp Suction Reference Temperature °F °F 30 Head press PSIG 65 Cap. Btuh/1000 OD Unit KW Head press PSIG 35 40 45 50 55 165 170 176 182 188 195 137.2 9.13 151.6 9.33 166.8 9.54 182.4 9.77 198.5 10.02 214.9 10.27 191 197 203 209 215 222 133.6 10.06 147.5 10.29 161.8 10.52 176.6 10.77 191.6 11.02 207.0 11.29 75 Cap. Btuh/1000 OD Unit KW 219 225 232 238 245 252 85 Cap. Btuh/1000 OD Unit KW 128.5 11.16 141.7 11.40 155.4 11.65 169.3 11.91 183.6 12.18 198.1 12.46 Head press PSIG Cap. Btuh/1000 250 122.2 256 134.7 263 147.6 270 160.8 277 174.3 284 188.1 OD Unit KW 12.43 12.68 12.94 13.20 13.47 13.75 Head press PSIG Cap. Btuh/1000 283 114.9 289 126.7 296 138.8 304 151.2 311 164.0 319 177.1 OD Unit KW 13.85 14.10 14.35 14.61 14.89 15.17 Head press PSIG Cap. Btuh/1000 318 106.7 325 117.7 332 129.1 340 140.8 347 152.9 355 165.4 OD Unit KW 15.41 15.65 15.89 16.15 16.42 16.70 Head press PSIG 95 105 115 Table PD-7 — Gross Cooling Performance (KW) TWA155A Heat Pump Only OD Temp Suction Reference Temperature °C °C 18.3 23.9 29.4 35.0 40.6 46.1 18 -1.1 1.7 4.4 7.2 10.0 12.8 Head pressure (kPA) 1136 1174 1213 1255 1299 1343 Capacity (kW) OD Unit Power (kW) 40.2 9.13 44.4 9.33 48.8 9.54 53.4 9.77 58.1 10.02 62.9 10.27 Head pressure (kPA) 1315 1355 1397 1440 1485 1532 Capacity (kW) OD Unit Power (kW) 39.1 10.06 43.2 10.29 47.4 10.52 51.7 10.77 56.1 11.02 60.6 11.29 Head pressure (kPA) Capacity (kW) 1510 37.6 1552 41.5 1597 45.5 1642 49.6 1690 53.8 1738 58.0 OD Unit Power (kW) 11.16 11.40 11.65 11.91 12.18 12.46 Head pressure (kPA) Capacity (kW) 1722 35.8 1767 39.5 1813 43.2 1860 47.1 1909 51.0 1960 55.1 OD Unit Power (kW) 12.43 12.68 12.94 13.20 13.47 13.75 Head pressure (kPA) Capacity (kW) 1949 33.6 1996 37.1 2044 40.6 2093 44.3 2145 48.0 2197 51.9 OD Unit Power (kW) 13.85 14.10 14.35 14.61 14.89 15.17 Head pressure (kPA) 2192 2241 2291 2342 2395 2451 Capacity (kW) OD Unit Power (kW) 31.2 15.41 34.5 15.65 37.8 15.89 41.2 16.15 44.8 16.42 48.4 16.70 TWA-PRC001-EN Performance Data (TWA200A) Table PD-8 — Gross Cooling Performance (MBh) TWA200A Heat Pump Only OD Temp Suction Reference Temperature °F °F 30 Head press PSIG 35 40 45 50 55 177 183 189 196 203 210 187.4 12.50 205.7 12.81 224.7 13.14 244.4 13.49 264.7 13.86 285.6 14.25 65 Cap. Btuh/1000 OD Unit KW 75 Cap. Btuh/1000 OD Unit KW 231 238 245 253 260 269 85 Cap. Btuh/1000 OD Unit KW 169.4 15.42 185.8 15.79 203.0 16.18 220.8 16.60 239.3 17.04 258.4 17.49 Head press PSIG Cap. Btuh/1000 262 159.6 269 175.3 277 191.7 285 208.8 293 226.4 302 244.5 OD Unit KW 17.24 17.65 18.08 18.52 18.98 19.44 Head press PSIG Cap. Btuh/1000 296 149.2 304 164.3 312 180.1 320 196.5 329 213.4 338 230.6 OD Unit KW 19.29 19.74 20.20 20.68 21.15 21.62 Head press PSIG Cap. Btuh/1000 332 138.5 340 153.1 349 168.4 358 184.1 367 200.2 377 216.5 OD Unit KW 21.55 22.05 22.55 23.05 23.54 24.01 Head press PSIG Head press PSIG 95 105 115 203 209 216 223 230 238 178.8 13.84 196.0 14.17 213.9 14.53 232.6 14.91 252.1 15.32 272.1 15.75 Table PD-8 — Gross Cooling Performance (KW) TWA200A Heat Pump Only ODTemp Suction ReferenceTemperature °C °C 18.3 23.9 29.4 35.0 40.6 46.1 TWA-PRC001-EN -1.1 1.7 4.4 7.2 10.0 12.8 Head pressure (kPA) 1219 1261 1305 1351 1399 1449 Capacity (kW) OD Unit Power (kW) 54.9 12.50 60.2 12.81 65.8 13.14 71.5 13.49 77.5 13.86 83.6 14.25 Head pressure (kPA) 1397 1441 1487 1536 1588 1642 Capacity (kW) OD Unit Power (kW) 52.3 13.84 57.4 14.17 62.6 14.53 68.1 14.91 73.8 15.32 79.7 15.75 Head pressure (kPA) Capacity (kW) 1593 49.6 1640 54.4 1689 59.4 1741 64.7 1796 70.1 1852 75.7 OD Unit Power (kW) 15.42 15.79 16.18 16.60 17.04 17.49 Head pressure (kPA) Capacity (kW) 1808 46.7 1857 51.3 1910 56.1 1965 61.1 2022 66.3 2081 71.6 OD Unit Power (kW) 17.24 17.65 18.08 18.52 18.98 19.44 Head pressure (kPA) Capacity (kW) 2040 43.7 2093 48.1 2149 52.7 2207 57.5 2268 62.5 2329 67.5 OD Unit Power (kW) 19.29 19.74 20.20 20.68 21.15 21.62 Head pressure (kPA) 2290 2348 2408 2470 2533 2597 Capacity (kW) OD Unit Power (kW) 40.5 21.55 44.8 22.05 49.3 22.55 53.9 23.05 58.6 23.54 63.4 24.01 19 Performance Data (System) Table PD-9 — Gross Heating Capacities (MBh) TWA075A Heat Pump with TWE075A Air Handler At 2500 CFM Outdoor Heating Capacity (BTUH/1000) At Total Power in Kilowatts At Temperature (°F) Indicated Indoor Dry BulbTemperature 60 70 75 80 Indicated Indoor Dry BulbTemperature 60 70 75 80 -18 -13 -8 -3 2 7 12 17 22 27 32 37 42 47 52 57 62 67 72 34.9 35.5 36.5 37.9 39.7 42.0 44.8 48.0 51.7 55.8 60.3 65.0 69.9 75.1 80.6 86.2 92.0 97.8 103.7 30.4 31.5 33.1 35.0 37.5 40.3 43.5 47.1 51.1 55.4 60.1 64.8 69.7 74.8 80.2 85.6 91.2 96.8 102.5 28.5 30.0 31.8 34.0 36.7 39.7 43.1 46.9 51.0 55.3 60.0 64.7 69.6 74.7 79.9 85.3 90.8 96.2 101.9 26.9 28.6 30.6 33.2 36.1 39.3 42.9 46.8 50.9 55.3 60.0 64.7 69.5 74.5 79.6 84.9 90.2 95.6 101.2 5.5 5.5 5.4 5.4 5.4 5.4 5.5 5.5 5.6 5.7 5.8 5.9 6.0 6.2 6.3 6.5 6.7 6.9 7.1 5.6 5.6 5.6 5.6 5.7 5.7 5.8 5.9 6.0 6.2 6.3 6.5 6.6 6.8 7.0 7.1 7.3 7.5 7.7 5.7 5.7 5.8 5.8 5.9 6.0 6.1 6.2 6.3 6.4 6.6 6.8 6.9 7.1 7.3 7.5 7.7 7.9 8.1 5.8 5.9 5.9 6.0 6.1 6.2 6.3 6.5 6.6 6.8 6.9 7.1 7.3 7.5 7.6 7.8 8.0 8.2 8.4 Table PD-9 — Gross Heating Capacities (KW) TWA075A Heat Pump with TWE075A Air Handler At 1180 L/S Outdoor Heating Capacity (KW) At Total Power in Kilowatts At Temperature (°C) Indicated Indoor Dry BulbTemperature 15.6 21.1 23.9 26.7 Indicated Indoor Dry BulbTemperature 15.6 21.1 23.9 26.7 -27.8 -25.0 -22.2 -19.4 -16.7 -13.9 -11.1 -8.3 -5.6 -2.8 0.0 2.8 5.6 8.3 11.1 13.9 16.7 19.4 22.2 10.2 10.4 10.7 11.1 11.6 12.3 13.1 14.1 15.1 16.3 17.7 19.0 20.5 22.0 23.6 25.2 26.9 28.6 30.4 8.9 9.2 9.7 10.3 11.0 11.8 12.7 13.8 15.0 16.2 17.6 19.0 20.4 21.9 23.5 25.1 26.7 28.3 30.0 8.4 8.8 9.3 10.0 10.7 11.6 12.6 13.7 14.9 16.2 17.6 19.0 20.4 21.9 23.4 25.0 26.6 28.2 29.8 Correction Factors - Other Airflows (Table Value x Correction Factor = Value at new airflow) Airflow Heating Capacity Compressor Kw 2250 CFM 1061 L/s x 0.99 x 1.02 2750 CFM 1297 L/s x 1.01 x 0.98 Values at ARI Rating Conditions of: 70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.) 70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond) 20 7.9 8.4 9.0 9.7 10.6 11.5 12.6 13.7 14.9 16.2 17.6 18.9 20.3 21.8 23.3 24.9 26.4 28.0 29.6 5.5 5.6 5.7 5.8 5.9 6.0 6.2 6.3 6.5 6.6 6.8 6.9 7.1 7.3 7.5 7.7 7.9 8.1 8.4 6.0 6.1 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.6 7.8 8.0 8.2 8.4 8.7 8.9 9.2 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.9 8.1 8.4 8.6 8.8 9.1 9.3 9.6 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.9 8.1 8.3 8.5 8.8 9.0 9.2 9.5 9.8 10.0 Airflow = 2500 cfm (1179 L/s) Heating Capacity (High Temp.) = 75,000 (21.82) Heating Capacity (Low Temp.) = 47,000 (13.84) Compressor Power (High Temp) = 5.41 kW Compressor Power (Low Temp) = 4.55 kW Coeff. Of Perf. (High Temp) = 3.2 Coeff. Of Perf. (Low Temp) = 2.3 Outdoor Fan Power = 550 watts Indoor Fan Power = 800 watts Note: 1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line. TWA-PRC001-EN Performance Data (System) Table PD-10 — Gross Heating Capacities (MBh) TWA100A Heat Pump with TWE100A Air Handler At 3325 CFM Outdoor Heating Capacity (BTUH/1000) At Total Power in Kilowatts At Temperature (°F) Indicated Indoor Dry BulbTemperature 60 70 75 80 Indicated Indoor Dry BulbTemperature 60 70 75 80 -18 -13 -8 -3 2 7 12 17 22 27 32 37 42 47 52 57 62 67 72 21.9 33.4 40.8 46.7 52.3 57.7 63.2 68.9 74.8 80.9 87.3 93.6 100.2 107.1 114.4 121.9 129.7 137.7 145.9 39.6 43.6 47.5 51.5 55.7 60.1 64.8 69.8 75.1 80.8 86.8 92.9 99.3 106.0 113.2 120.6 128.3 136.2 144.3 43.0 46.0 49.2 52.8 56.5 60.6 65.1 69.9 75.1 80.6 86.5 92.6 98.9 105.6 112.7 120.1 127.8 135.6 143.7 44.8 47.3 50.2 53.4 57.0 60.8 65.1 69.8 74.9 80.3 86.2 92.2 98.5 105.2 112.3 119.7 127.3 135.1 143.2 5.6 6.2 6.6 6.8 7.0 7.2 7.4 7.5 7.7 7.9 8.0 8.2 8.4 8.6 8.8 9.1 9.3 9.6 9.9 7.3 7.5 7.6 7.8 7.9 8.1 8.2 8.4 8.5 8.7 8.9 9.1 9.3 9.5 9.8 10.1 10.4 10.7 11.0 7.9 8.0 8.1 8.2 8.4 8.5 8.6 8.8 9.0 9.1 9.4 9.6 9.8 10.1 10.3 10.6 10.9 11.2 11.6 8.4 8.5 8.6 8.7 8.8 8.9 9.1 9.2 9.4 9.6 9.8 10.1 10.3 10.6 10.9 11.2 11.5 11.9 12.2 Table PD-10 — Gross Heating Capacities (KW) TWA100A Heat Pump with TWE100A Air Handler At 1570 L/S Outdoor Heating Capacity (KW) At Total Power in Kilowatts At Temperature (°C) Indicated Indoor Dry BulbTemperature 15.6 21.1 23.9 26.7 Indicated Indoor Dry BulbTemperature 15.6 21.1 23.9 26.7 -27.8 -25.0 -22.2 -19.4 -16.7 -13.9 -11.1 -8.3 -5.6 -2.8 0.0 2.8 5.6 8.3 11.1 13.9 16.7 19.4 22.2 6.4 9.8 11.9 13.7 15.3 16.9 18.5 20.2 21.9 23.7 25.6 27.4 29.3 31.3 33.5 35.7 38.0 40.3 42.7 11.6 12.8 13.9 15.1 16.3 17.6 19.0 20.4 22.0 23.7 25.4 27.2 29.1 31.0 33.1 35.3 37.6 39.9 42.3 12.6 13.5 14.4 15.4 16.6 17.8 19.1 20.5 22.0 23.6 25.3 27.1 29.0 30.9 33.0 35.2 37.4 39.7 42.1 Correction Factors - Other Airflows (Table Value x Correction Factor = Value at new airflow) Airflow Heating Capacity Compressor Kw 3000 CFM 1416 L/s x 0.99 x 1.02 3675 CFM 1734 L/s x 1.01 x 0.98 Values at ARI Rating Conditions of: 70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.) 70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond) TWA-PRC001-EN 13.1 13.9 14.7 15.6 16.7 17.8 19.1 20.4 21.9 23.5 25.2 27.0 28.8 30.8 32.9 35.0 37.3 39.6 41.9 5.5 5.6 5.7 5.8 5.9 6.0 6.2 6.3 6.5 6.6 6.8 6.9 7.1 7.3 7.5 7.7 7.9 8.1 8.4 6.0 6.1 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.6 7.8 8.0 8.2 8.4 8.7 8.9 9.2 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.9 8.1 8.4 8.6 8.8 9.1 9.3 9.6 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.9 8.1 8.3 8.5 8.8 9.0 9.2 9.5 9.8 10.0 Airflow = 3325 cfm (1569 L/s) Heating Capacity (High Temp.) = 106,000 (31.05) Heating Capacity (Low Temp.) = 69,000 (20.29) Compressor Power (High Temp) = 7.61 kW Compressor Power (Low Temp) = 6.38 kW Coeff. Of Perf. (High Temp) = 3.30 Coeff. Of Perf. (Low Temp) = 2.4 Outdoor Fan Power = 644 watts Indoor Fan Power = 1,170 watts Note: 1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line. 21 Performance Data (System) Table PD-11 — Gross Heating Capacities (MBh) TWA155B Heat Pump with TWE155B Air Handler At 5000 CFM Outdoor Heating Capacity (BTUH/1000) At Total Power in Kilowatts At Temperature (°F) Indicated Indoor Dry BulbTemperature 60 70 75 80 Indicated Indoor Dry BulbTemperature 60 70 75 80 -18 -13 -8 -3 2 7 12 17 22 27 32 37 42 47 52 57 62 67 72 69.7 71.1 73.1 76.0 79.8 84.5 90.2 96.7 104.2 112.6 121.8 131.3 141.4 151.9 163.0 174.4 186.2 198.0 210.0 60.9 63.2 66.4 70.4 75.4 81.1 87.7 95.1 103.2 111.9 121.4 131.0 140.9 151.3 162.2 173.3 184.6 196.0 207.6 57.2 60.2 63.9 68.4 73.9 80.0 87.0 94.6 102.9 111.8 121.3 130.8 140.7 151.0 161.6 172.5 183.6 194.8 206.2 54.0 57.4 61.6 66.8 72.7 79.3 86.6 94.4 102.8 111.8 121.3 130.7 140.5 150.6 161.0 171.7 182.6 193.5 204.8 11.1 11.0 11.0 10.9 10.9 11.0 11.1 11.2 11.3 11.5 11.7 12.0 12.3 12.6 12.9 13.2 13.6 14.0 14.4 11.4 11.3 11.4 11.4 11.5 11.6 11.8 12.0 12.2 12.5 12.8 13.1 13.4 13.8 14.1 14.5 14.9 15.3 15.7 11.5 11.6 11.6 11.7 11.9 12.1 12.3 12.5 12.8 13.1 13.4 13.8 14.1 14.5 14.8 15.2 15.6 16.0 16.4 11.8 11.8 12.0 12.1 12.3 12.6 12.8 13.1 13.4 13.7 14.1 14.4 14.8 15.2 15.6 15.9 16.3 16.7 17.1 Table PD-11 — Gross Heating Capacities (KW) TWA155B Heat Pump with TWE155B Air Handler At 2360 L/S Outdoor Heating Capacity (KW) At Total Power in Kilowatts At Temperature (°C) Indicated Indoor Dry BulbTemperature 15.6 21.1 23.9 26.7 Indicated Indoor Dry BulbTemperature 15.6 21.1 23.9 26.7 -27.8 -25.0 -22.2 -19.4 -16.7 -13.9 -11.1 -8.3 -5.6 -2.8 0.0 2.8 5.6 8.3 11.1 13.9 16.7 19.4 22.2 20.4 20.8 21.4 22.3 23.4 24.7 26.4 28.3 30.5 33.0 35.7 38.5 41.4 44.5 47.7 51.1 54.5 58.0 61.5 17.8 18.5 19.4 20.6 22.1 23.8 25.7 27.8 30.2 32.8 35.5 38.3 41.3 44.3 47.5 50.7 54.0 57.4 60.8 16.8 17.6 18.7 20.0 21.6 23.4 25.5 27.7 30.1 32.7 35.5 38.3 41.2 44.2 47.3 50.5 53.8 57.0 60.4 Correction Factors - Other Airflows“(Table Value Correction Factor = Value at new airflow) Airflow 4500 CFM 5500 CFM“ 2124 L/s 2596 L/s Heating Capacity Compressor Kw x 0.99 x 1.02 x 1.01 x 0.98 Values at ARI Rating Conditions of: 70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.) 70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond) 22 15.8 16.8 18.0 19.6 21.3 23.2 25.3 27.6 30.1 32.7 35.5 38.3 41.1 44.1 47.2 50.3 53.5 56.7 60.0 5.5 5.6 5.7 5.8 5.9 6.0 6.2 6.3 6.5 6.6 6.8 6.9 7.1 7.3 7.5 7.7 7.9 8.1 8.4 6.0 6.1 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.6 7.8 8.0 8.2 8.4 8.7 8.9 9.2 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.9 8.1 8.4 8.6 8.8 9.1 9.3 9.6 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.9 8.1 8.3 8.5 8.8 9.0 9.2 9.5 9.8 10.0 Airflow = 5000 cfm (2360 L/s) Heating Capacity (High Temp.) = 151,000 (44.27) Heating Capacity (Low Temp.) = 95,000 (27.67) Compressor Power (High Temp) = 10.94 kW Compressor Power (Low Temp) = 9.18 kW Coeff. Of Perf. (High Temp) = 3.2 Coeff. Of Perf. (Low Temp) = 2.3 Outdoor Fan Power = 1100 watts Indoor Fan Power = 1700 watts Note: 1.Rated with 25 feet of 1-3/8"" suction and 1/2"" liquid line." TWA-PRC001-EN Performance Data (System) Table PD-12 — Gross Heating Capacities (MBh) TWA200B Heat Pump with TWE200B Air Handler At 6675 CFM Outdoor Heating Capacity (BTUH/1000) At Total Power in Kilowatts At Temperature (°F) Indicated Indoor Dry BulbTemperature 60 70 75 80 Indicated Indoor Dry BulbTemperature 60 70 75 80 -18 -13 -8 -3 2 7 12 17 22 27 32 37 42 47 52 57 62 67 72 43.5 68.9 82.3 93.2 103.5 113.7 124.2 135.0 146.2 157.9 170.2 182.4 195.1 208.4 222.4 236.9 251.7 266.7 282.3 80.3 87.1 94.2 101.6 109.4 117.8 126.8 136.4 146.7 157.6 169.3 181.2 193.5 206.5 220.3 234.6 249.2 264.0 279.4 85.7 91.0 97.0 103.6 110.8 118.6 127.2 136.5 146.5 157.2 168.8 180.5 192.7 205.7 219.4 233.6 248.2 262.9 278.2 88.4 93.0 98.4 104.5 111.3 118.8 127.1 136.1 146.0 156.6 168.1 179.8 192.0 205.0 218.7 232.9 247.4 262.1 277.2 10.8 12.3 13.0 13.4 13.8 14.1 14.5 14.8 15.1 15.4 15.7 16.0 16.4 16.7 17.2 17.6 18.1 18.5 19.1 14.5 14.8 15.1 15.3 15.6 15.8 16.1 16.4 16.7 17.1 17.4 17.8 18.2 18.6 19.1 19.6 20.1 20.6 21.2 15.6 15.8 16.0 16.2 16.4 16.7 17.0 17.3 17.6 18.0 18.4 18.8 19.2 19.7 20.2 20.7 21.2 21.8 22.4 16.5 16.7 16.8 17.1 17.3 17.6 17.9 18.2 18.5 18.9 19.4 19.8 20.3 20.8 21.3 21.9 22.4 23.0 23.7 Table PD-12 — Gross Heating Capacities (KW) TWA200B Heat Pump with TWE200B Air Handler At 3150 L/S Outdoor Heating Capacity (KW) At Total Power in Kilowatts At Temperature (°C) Indicated Indoor Dry BulbTemperature 15.6 21.1 23.9 26.7 Indicated Indoor Dry BulbTemperature 15.6 21.1 23.9 26.7 27.8 -25.0 -22.2 -19.4 -16.7 -13.9 -11.1 -8.3 -5.6 -2.8 0.0 2.8 5.6 8.3 11.1 13.9 16.7 19.4 22.2 12.7 20.2 24.1 27.3 30.3 33.3 36.4 39.5 42.8 46.2 49.8 53.4 57.1 61.0 65.1 69.4 73.7 78.1 82.7 23.5 25.5 27.6 29.7 32.0 34.5 37.1 39.9 42.9 46.2 49.6 53.0 56.7 60.5 64.5 68.7 73.0 77.3 81.8 25.1 26.6 28.4 30.3 32.4 34.7 37.2 40.0 42.9 46.0 49.4 52.8 56.4 60.2 64.3 68.4 72.7 77.0 81.5 Correction Factors - Other Airflows (Table Value x Correction Factor = Value at new airflow) Airflow 6000 CFM 7325 CFM 2832 L/s 3457 L/s Heating Capacity x 0.99 x 1.01 Compressor Kw x 1.02 x 0.98 Values at ARI Rating Conditions of: 70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.) 70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond) 25.9 27.2 28.8 30.6 32.6 34.8 37.2 39.9 42.7 45.9 49.2 52.6 56.2 60.0 64.0 68.2 72.4 76.7 81.2 5.5 5.6 5.7 5.8 5.9 6.0 6.2 6.3 6.5 6.6 6.8 6.9 7.1 7.3 7.5 7.7 7.9 8.1 8.4 6.0 6.1 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.6 7.8 8.0 8.2 8.4 8.7 8.9 9.2 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.9 8.1 8.4 8.6 8.8 9.1 9.3 9.6 6.5 6.6 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.9 8.1 8.3 8.5 8.8 9.0 9.2 9.5 9.8 10.0 Airflow = 6700 cfm (3162 L/s) Heating Capacity (High Temp.) = 206,000 (60.26) Heating Capacity (Low Temp.) = 135,000 (39.66) Compressor Power (High Temp) = 14.92 kW Compressor Power (Low Temp) = 12.62 kW Coeff. Of Perf. (High Temp) = 3.2 Coeff. Of Perf. (Low Temp) = 2.4 Outdoor Fan Power = 1,100 watts Indoor Fan Power = 2,290 watts Note: 1. Rated with 25 feet of 1-3/8” suction and 1/2" liquid line." TWA-PRC001-EN 23 Performance Data (Air Handler) Table PD-13 — Evaporator Fan Performance —TWE050A External Static Pressure (Inches of Water Gauge) CFM .10" .20" .30" .40" .50" .60" .70" .80" .90" 1.00" 1.10" RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1400 1500 1600 1700 1800 1900 2000 2100 — — — 601 625 642 659 674 — — — 0.35 0.36 0.40 0.44 0.48 0.75 HP — — 607 0.36 625 0.38 648 0.40 671 0.41 687 0.45 703 0.49 722 0.54 Standard Motor and Drive 646 0.37 698 0.42 751 0.47 803 0.52 856 0.56 908 0.61 941 0.65 661 0.40 713 0.45 764 0.50 816 0.54 867 0.59 919 0.64 952 0.67 676 0.43 727 0.48 778 0.52 828 0.57 879 0.62 930 0.67 963 0.70 696 0.44 744 0.49 792 0.54 841 0.59 889 0.64 937 0.69 971 0.73 716 0.46 762 0.51 807 0.56 853 0.61 898 0.66 944 0.71 979 0.76 731 0.50 776 0.55 820 0.60 865 0.66 909 0.71 951 0.75 987 0.80 745 0.54 790 0.60 833 0.65 877 0.70 920 0.75 957 0.80 994 0.84 770 0.60 817 0.65 857 0.70 897 0.75 936 0.80 973 0.85 1009 0.89 1.0 HP Oversized Motor and High Static Drive 973 984 995 1005 — — — — 0.68 1006 0.71 0.71 — — 0.74 — — 0.77 — — — — — — — — — — — — — — Table PD-13— Evaporator Fan Performance —TWE050A External Static Pressure (Pascal) L/S 661 708 755 802 850 897 944 991 25 50 75 100 125 150 174 199 224 249 274 RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM BHP RPM BHP RPM KW RPM KW RPM KW 601 625 642 659 674 0.26 0.27 0.30 0.33 0.36 0.56 Standard Motor 646 0.28 698 607 0.27 661 0.30 713 625 0.28 676 0.32 727 648 0.30 696 0.33 744 671 0.31 716 0.34 762 687 0.34 731 0.37 776 703 0.37 745 0.40 790 722 0.40 770 0.45 817 and Drive 0.31 751 0.35 803 0.39 856 0.42 908 0.45 941 0.48 0.34 764 0.37 816 0.40 867 0.44 919 0.48 952 0.50 0.36 778 0.39 828 0.43 879 0.46 930 0.50 963 0.52 0.37 792 0.40 841 0.44 889 0.48 937 0.51 971 0.54 0.38 807 0.42 853 0.45 898 0.49 944 0.53 979 0.57 0.41 820 0.45 865 0.49 909 0.53 951 0.56 987 0.60 0.45 833 0.48 877 0.52 920 0.56 957 0.60 994 0.67 0.48 857 0.52 897 0.56 936 0.60 973 0.63 1009 0.66 0.75 KW Oversized Motor and High Static Drive 973 984 995 1005 — — — — 0.51 0.53 0.55 0.57 — — — — 1006 0.53 — — — — — — — — — — — — — — Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. Table PD-14 — Blower Speeds Drive Standard High Static 24 6 5 N/A N/A 590 713 Motor DriveTurns Open 4 3 2 639 772 688 832 737 891 1 0 786 951 835 1009 TWA-PRC001-EN Performance Data (Air Handler) Table PD-15 — Evaporator Fan Performance TWE075A External Static Pressure (In. Of Water Column) CFM 2000 2125 2250 2375 2500 2625 2750 2875 3000 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 443 0.44 489 0.49 453 0.46 499 0.52 463 0.49 510 0.55 473 0.51 520 0.57 445 0.47 489 0.54 533 0.60 464 0.50 506 0.57 548 0.63 484 0.53 523 0.59 562 0.66 504 0.56 540 0.62 576 0.68 524 0.59 557 0.65 590 0.71 1.0 HP Standard Motor and Low Static Drive 535 546 556 567 578 589 601 612 624 0.54 0.57 0.61 0.64 0.67 0.69 0.72 0.74 0.77 581 592 602 613 622 631 640 648 657 0.59 627 0.64 673 0.69 0.63 638 0.68 684 0.74 0.67 649 0.73 695 0.79 0.70 660 0.77 706 0.83 0.73 667 0.80 711 0.86 0.76 672 0.82 714 0.88 0.78 678 0.84 717 0.91 0.81 684 0.87 720 0.93 0.83 690 0.89 723 0.95 1.0 HP Standard Motor and High Static Drive Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. 719 730 742 753 756 757 758 759 760 0.74 0.79 0.85 0.90 0.93 0.95 0.97 0.99 1.01 765 771 776 782 784 786 787 789 790 0.79 791 0.83 818 0.89 0.85 798 0.90 825 0.96 0.91 804 0.97 831 1.03 0.97 810 1.03 838 1.10 0.99 813 1.07 842 1.14 1.01 815 1.09 844 1.17 1.03 817 1.12 847 1.21 1.05 819 1.15 850 1.24 1.07 821 1.17 853 1.27 1.5 HP Oversized Motor and High Static Drive Table PD-15— Continued CFM External Static Pressure (In. Of Water Column) 120 1.30 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2000 2125 2250 2375 2500 2625 2750 2875 3000 844 852 859 866 870 874 877 880 884 0.96 1.03 1.10 1.17 1.21 1.25 1.29 1.33 1.37 871 879 886 894 899 903 907 911 915 1.02 1.09 1.17 1.24 1.29 1.33 1.38 1.43 1.48 897 906 914 922 928 932 937 942 946 1.09 1.16 1.23 1.30 1.36 1.42 1.47 1.52 1.58 924 933 942 950 1.15 950 1.21 1.22 1.30 1.37 Table PD-15 — Evaporator Fan Performance TWE075A External Static Pressure (Pascal) 25 50 75 100 125 150 174 199 224 249 274 RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW L/S 944 1003 1062 1121 1180 1239 1298 1357 1416 443 0.33 489 0.37 453 0.34 499 0.39 463 0.37 510 0.41 473 0.38 520 0.43 445 0.35 489 0.40 533 0.45 464 0.37 506 0.43 548 0.47 484 0.40 523 0.44 562 0.49 504 0.42 540 0.46 576 0.51 524 0.44 557 0.48 590 0.53 .75 KW Standard Motor and High Static Drive 535 546 556 567 578 589 601 612 624 0.40 0.43 0.45 0.48 0.50 0.51 0.54 0.55 0.57 581 592 602 613 622 631 640 648 657 0.44 627 0.48 673 0.51 0.47 638 0.51 684 0.55 0.50 649 0.54 695 0.59 0.52 660 0.57 706 0.62 0.54 667 0.60 711 0.64 0.57 672 0.61 714 0.66 0.58 678 0.63 717 0.68 0.60 684 0.65 720 0.69 0.62 690 0.66 723 0.71 .75 KW Standard Motor and High Static Drive Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. Table PD-16 — Blower Speeds 719 730 742 753 756 757 758 759 760 0.55 0.59 0.63 0.67 0.69 0.71 0.72 0.74 0.75 765 0.59 791 0.62 818 0.66 771 0.63 798 0.67 825 0.72 776 0.68 804 0.72 831 0.77 782 0.72 810 0.77 838 0.82 784 0.74 813 0.80 842 0.85 786 0.75 815 0.81 844 0.87 787 0.77 817 0.84 847 0.90 789 0.78 819 0.86 850 0.92 790 0.80 821 0.87 853 0.95 1.12 KW Oversized Motor and High Static Drive Table PD-15 — Continued L/S External Static Pressure (Pascal) 299 324 349 374 398 RPM KW RPM KW RPM KW RPM KW RPM KW 944 1003 1062 1121 1180 1239 1298 1357 1416 844 852 859 866 870 874 877 880 884 0.72 0.77 0.82 0.87 0,90 0.93 0.96 0.99 1.02 871 879 886 894 899 903 907 911 915 0.76 0.81 0.87 0.92 0.96 0.99 1.03 1.07 1.10 897 906 914 922 928 932 937 942 946 0.81 0.87 0.92 0.97 1.01 1.06 1.10 1.13 1.18 924 933 942 950 0.86 950 0.90 0.91 0.97 1.02 Motor Drive Turns Open Drive Standard Low Static High Static 6 5 4 3 2 1 0 N/A N/A N/A 600 428 700 650 464 750 700 499 800 750 535 850 800 571 900 850 606 950 TWA-PRC001-EN 25 Performance Data (Air Handler) Table PD-17 — Evaporator Fan Performance TWE100A,TWE100B External Static Pressure (In. Of Water Column) CFM 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.20 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2600 460 0.32 493 0.39 2775 473 0.37 506 0.45 2950 487 0.43 519 0.50 3125 501 0.49 532 0.56 3300 520 0.58 548 0.65 3475 541 0.69 568 0.76 3650 562 0.82 588 0.88 3825 582 0.96 608 1.03 4000 602 1.11 628 1.17 1.5 HP Standard Motor and Low Static Drive 527 540 552 565 581 600 618 637 656 0.47 0.53 0.58 0.64 0.73 0.84 0.97 1.11 1.26 565 0.55 603 0.63 641 0.71 576 0.61 613 0.69 649 0.77 587 0.67 623 0.75 658 0.83 599 0.72 632 0.81 666 0.89 613 0.81 644 0.89 677 0.98 631 0.93 658 1.00 691 1.08 648 1.05 671 1.11 703 1.19 666 1.20 685 1.26 711 1.31 683 1.35 698 1.40 720 1.43 1.5 HP Standard Motor and Drive 679 686 693 700 710 721 732 739 747 Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. 4. Low Static Drive must be field supplied. 0.79 0.85 0.91 0.97 1.06 1.16 1.27 1.38 1.50 717 723 728 734 740 746 753 763 773 0.87 0.93 0.99 1.05 1.13 1.21 1.31 1.44 1.58 744 748 751 755 759 764 772 787 801 0.94 772 1.01 826 1.16 1.00 775 1.07 830 1.20 1.06 779 1.12 833 1.25 1.11 783 1.18 737 1.30 1.19 787 1.25 841 1.37 1.28 793 1.34 846 1.48 1.38 801 1.45 853 1.59 1.51 815 1.58 862 1.74 1.64 829 1.71 872 1.89 2.0 HP Oversized Motor and High Static Drive Table PD-17— Continued External Static Pressure (In. Of Water Column) 1.40 1.60 CFM RPM BHP RPM BHP 2600 2775 2960 3125 3300 3475 3650 3825 4000 881 884 886 889 892 897 902 912 922 1.30 1.36 1.41 1.47 1.54 1.63 1.73 1.89 2.04 936 938 939 941 945 950 955 960 965 1.45 1.51 1.57 1.64 1.73 1.85 1.99 2.18 2.30 Table PD-17— Evaporator Fan Performance TWE0100A,TWE100B External Static Pressure (Pascal) 25 50 75 100 125 150 174 199 224 249 274 RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW L/S 1227 460 0.24 493 0.29 1310 473 0.28 576 0.34 1392 487 0.32 519 0.37 1475 501 0.37 532 0.42 1557 520 0.43 548 0.48 1640 541 0.51 568 0.57 1723 562 0.61 588 0.66 1805 582 0.72 608 0.77 1888 602 0.83 628 0.87 .75 KW Standard Motor and Low Static Drive 527 613 552 565 581 600 618 637 656 0.35 0.40 0.43 0.48 0.54 0.63 0.72 0.83 0.94 565 649 587 599 613 631 648 666 683 0.41 0.45 0.50 0.54 0.60 0.69 0.78 0.89 1.01 603 0.47 641 0.53 679 686 0.51 723 0.57 748 623 0.56 658 0.62 693 632 0.60 666 0.66 700 644 0.66 677 0.73 710 658 0.75 691 0.80 721 671 0.83 703 0.89 732 685 0.94 711 0.98 739 698 1.04 720 1.07 747 1.12 KW Standard Motor and Drive Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 3.0 turns open. Adjustments are made in 0.5 turn increments. 4. Low Static Drive must be field supplied. Table PD - 18 — Blower Speeds Motor Sheave Turns Open Drive Standard Low Static High Static 26 6 5 4 3 2 1 0 N/A N/A N/A 587 453 606 629 485 641 671 518 677 713 550 713 755 583 748 796 615 784 0.59 0.63 0.68 0.72 0.79 0.87 0.95 1.03 1.12 717 775 728 734 740 746 753 763 773 0.65 0.69 0.74 0.78 0.84 0.90 0.98 1.07 1.18 744 0.70 772 0.75 826 0.87 830 0.75 884 0.80 938 0.89 751 0.79 779 0.84 833 0.93 755 0.83 783 0.88 737 0.97 759 0.89 787 0.93 841 1.02 764 0.95 793 1.00 846 1.10 772 1.03 801 1.08 853 1.19 787 1.13 815 1.18 862 1.30 801 1.22 829 1.28 872 1.41 1.49 KW Oversized Motor and High Static Drive Table PD-17— Continued External Static Pressure (Pascal) 349 398 L/S RPM KW RPM KW 1227 1310 1392 1475 1557 1640 1723 1805 1888 881 506 886 889 892 897 902 912 922 0.97 1.01 1.05 1.10 1.15 1.22 1.29 1.41 1.52 936 540 939 941 945 950 955 960 965 1.08 1.13 1.17 1.22 1.29 1.38 1.48 1.63 1.72 TWA-PRC001-EN Performance Data (Air Handler) Table PD-19 — Evaporator Fan Performance — TWE155B External Static Pressure (Inches of Water Column) CFM .10" .20" .30" .40" .50" .60" .70" .80" .90" 1.00" 1.20" 140 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2.0 HP Standard Motor and Drive 4000 4250 4500 4750 5000 5260 5500 5750 6000 628 633 637 641 645 650 652 653 655 1.34 1.37 1.40 1.42 1.44 1.46 1.47 1.48 1.49 653 658 662 666 670 675 678 680 681 1.38 1.41 1.44 1.50 1.52 1.53 1.55 1.57 1.59 678 683 687 691 695 700 703 706 709 1.43 1.46 1.49 1.53 1.56 1.59 1.63 1.68 1.74 692 697 701 705 710 716 721 726 731 1.48 1.51 1.53 1.61 1.65 1.67 1.71 1.76 1.80 708 713 717 721 725 728 734 743 752 1.52 1.55 1.58 1.63 1.67 1.70 1.75 1.81 1.87 723 728 732 736 739 741 747 761 774 1.57 1.60 1.63 1.65 1.68 1.73 1.78 1.86 1.94 738 743 747 751 758 765 775 789 803 1.60 1.62 1.64 1.66 1.70 1.75 1.83 1.94 2.05 749 751 754 765 777 790 804 817 831 1.61 1.63 1.65 1.67 1.74 1.82 1.92 2.04 2.17 759 770 782 793 806 819 832 846 860 1.62 1.64 1.67 1.72 1.81 1.92 2.03 2.16 2.29 3.0 HP Oversized Motor and High Static Drive 795 1.66 851 1.85 907 2.03 806 1.71 862 1.90 918 2.11 817 1.76 873 1.96 929 2.19 828 1.81 884 2.01 940 2.27 839 1.91 896 2.13 849 2.03 907 2.28 861 2.15 920 2.44 875 2.29 935 2.61 889 2.44 950 2.78 Table PD-19 — Evaporator Fan Performance TWE155B External Static Pressure (Pascal) L/S 25 50 75 100 125 150 174 199 224 249 299 349 RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM BHP RPM BHP RPM KW RPM KW RPM KW RPM KW 1.49 KW Standard Motor and Drive System 1888 2006 2124 2242 2360 2482 2596 2714 2832 628 633 637 641 645 650 652 653 655 1.00 1.02 1.04 1.06 1.07 1.09 1.10 1.10 1.11 653 658 662 666 670 675 678 680 681 1.03 1.05 1.07 1.12 1.13 1.14 1.16 1.17 1.19 678 683 687 691 695 700 703 706 709 1.07 1.09 1.11 1.14 1.16 1.19 1.22 1.25 1.30 692 697 701 705 710 716 721 726 731 1.10 1.13 1.14 1.20 1.23 1.25 1.28 1.31 1.34 708 713 717 721 725 728 734 743 752 1.13 1.16 1.18 1.22 1.25 1.27 1.30 1.30 1.35 723 728 732 736 739 741 747 761 774 1.17 1.19 1.22 1.23 1.25 1.29 1.33 1.39 1.45 738 743 747 751 758 765 775 789 803 1.19 1.21 1.23 1.24 1.27 1.30 1.36 1.45 1.53 749 751 754 765 777 790 804 817 831 1.20 1.22 1.23 1.25 1.30 1.36 1.43 1.52 1.62 759 770 782 793 806 819 832 846 860 1.21 1.22 1.25 1.28 1.35 1.43 1.51 1.61 1.71 2.24 KW Oversized Motor and High Static Drive System 795 1.24 851 1.38 907 1.51 806 1.28 862 1.42 918 1.57 817 1.31 873 1.46 929 1.63 828 1.35 884 1.50 940 1.69 839 1.42 896 1.59 849 1.51 907 1.70 861 1.60 920 1.82 875 1.71 935 1.95 889 1.82 950 2.07 Notes: 1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. Table PD-20— Blower Speeds Motor Sheave Turns Open Drive Standard High Static TWA-PRC001-EN 6 5 4 3 2 1 0 619 777 648 806 677 835 705 863 734 892 763 921 N/A 950 27 Performance Data (Air Handler) Table PD-21— Evaporator Fan Performance TWE200B External Static Pressure (In. Of Water Column) CFM 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.20 140 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5200 5525 5850 6175 473 0.99 6500 492 1.12 6825 510 1.25 7150 528 1.38 7475 550 1.61 7800 572 1.83 3.0 Standard Motor and Low Static Drive 461 0.74 503 0.91 545 479 0.88 521 1.04 563 497 1.01 539 1.18 581 515 1.15 557 1.31 599 534 1.28 576 1.45 618 552 1.42 594 1.59 636 570 1.56 612 1.73 654 594 1.77 640 1.92 683 618 1.97 668 2.10 712 3.0 HP Standard Motor and Field-Supplied Low Static Drive 1.07 1.21 1.34 1.48 1.61 1.75 1.90 2.08 2.27 587 605 623 641 660 678 697 721 746 1.03 1.21 1.39 1.57 1.75 1.91 2.07 2.29 2.52 619 640 661 682 702 723 744 760 776 1.17 1.35 1.53 1.71 1.90 2.10 2.30 2.50 2.69 685 701 717 732 748 763 779 790 802 1.40 1.58 1.76 1.94 2.12 2.30 2.49 2.67 2.84 723 739 755 769 784 794 804 815 826 1.59 1.77 1.95 2.12 2.30 2.47 2.64 2.81 2.99 750 766 782 796 811 820 830 840 851 1.74 1.92 2.10 2.27 2.45 2.62 2.78 2.96 3.13 777 793 809 823 838 846 855 865 876 1.89 2.07 2.25 2.43 2.60 2.77 2.94 3.11 3.27 851 859 868 877 886 894 903 914 926 2.19 2.37 2.55 2.73 2.91 3.09 3.26 3.47 3.67 898 906 915 924 933 941 950 959 969 2.39 2.60 2.81 3.02 3.22 3.42 3.62 3.85 4.08 5 HP Oversized Motor and High Static Drive Notes: 1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. Table PD-21— Continued External Static Pressure (In. Of Water Column) 1.60 1.80 CFM RPM BHP RPM BHP 5200 5525 5850 5175 8500 8825 7150 7475 7800 944 952 961 970 978 986 994 1003 1012 2.75 2.96 3.17 3.38 3.59 3.80 4.01 4.25 4.50 989 997 1006 1015 1023 3.12 3.33 3.54 3.75 3.96 Table PD-21— Evaporator Fan Performance TWE200B External Static Pressure (Pascal) CFM 25 50 75 100 125 150 174 199 224 249 299 349 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2454 2608 2761 2914 473 0.74 3068 492 0.84 3221 510 0.93 3374 528 1.03 3528 550 1.20 3681 572 1.36 Standard Motor 3.0 HP and Low Static Drive 461 0.55 503 0.68 545 479 0.66 521 0.78 563 497 0.75 539 0.88 581 515 0.86 557 0.98 599 534 0.95 576 1.08 618 552 1.06 594 1.19 636 570 1.16 612 1.29 654 594 1.32 640 1.43 683 618 1.47 668 1.57 712 3.0 HP Standard Motor and Field-Supplied Low Static Drive 0.80 0.90 1.00 1.10 1.20 1.30 1.42 1.55 1.69 587 605 623 641 660 678 697 721 746 0.77 0.90 1.04 1.17 1.30 1.42 1.54 1.71 1.88 619 640 661 682 702 723 744 760 776 0.87 1.01 1.14 1.28 1.42 1.57 1.72 1.87 2.01 685 701 717 732 748 763 779 790 802 1.04 1.18 1.31 1.45 1.58 1.72 1.86 1.99 2.12 1.30 1.43 1.57 1.69 1.83 1.95 2.07 2.21 2.33 777 793 809 823 838 846 855 865 876 1.41 1.54 1.68 1.81 1.94 2.07 2.19 2.32 2.44 851 859 868 877 886 894 903 914 926 1.63 1.77 1.90 2.04 2.17 2.30 2.43 2.59 2.74 898 906 915 924 933 941 950 959 969 1.78 1.94 2.10 2.52 2.40 2.55 2.70 2.87 3.04 External Static Pressure (Pascal) 398 448 RPM BHP RPM BHP CFM Motor Sheave Turns Open 28 750 766 782 796 811 820 830 840 851 Table PD-21— Continued Table PD-22 — Blower Speeds Standard Low Static Field-Supplied Low Static High Static 1.19 1.32 1.45 1.58 1.72 1.84 1.97 2.10 2.23 5 HP Oversized Motor and High Static Drive Notes: 1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. Drive 723 739 755 769 784 794 804 815 826 6 5 4 3 2 1 0 706 457 574 N/A 732 478 595 821 758 500 617 862 784 521 638 903 811 542 659 945 837 563 680 986 863 585 702 1027 2454 2608 2761 2914 3068 3221 3374 3528 3681 944 952 961 970 978 941 994 1003 1012 2.05 2.21 2.36 2.52 2.68 2.55 2.99 3.17 3.36 989 997 1006 1015 1023 986 2.33 2.48 2.64 2.80 2.95 2.83 TWA-PRC001-EN Performance Data Table PD-23— Discharge Plenum And Grille AssemblyThrow Distance — Air Handler Unit Louver Angle Deflection Position Model No. CFM L/S Straight 20, Ft. (m) 40, Ft. (m) 55, Ft. (m) 1400 1600 1800 2000 2200 2100 661 755 850 944 1038 991 38 (11.6) 42 (12.8) 46 (14.0) 48 (14.6) 51 (15.5) 49 (14.9) 24 (7.3) 31 (9.4) 37 (11.3) 43 (13.1) 50 (15.2) 38 (11.6) 22 (6.7) 26 (7.9) 29 (8.8) 33 (10.1) 36 (11.0) 31 (9.4) 18 (5.5) 20 (6.1) 22 (6.7) 24 (7.3) 25 (7.6) 27 (8.2) TWE075 2400 2700 3000 3200 3600 1133 1274 1416 1510 1699 52 55 58 56 62 (15.9) (16.8) (17.7) (17.1) (18.9) 43 48 53 46 51 35 (10.7) 38 (11.6) 42 (12.8) 38 (11.6) 42 (12.8) 29 31 32 30 33 TWE100 4000 4400 4800 4300 4900 1888 2077 2265 2029 2313 66 71 76 42 47 (20.1) (21.6) (23.2) (12.8) (14.3) 57 (17.4) 62 (18.9) 67 (20.4) 32 (9.8) 38 (11.6) 47 52 56 29 32 35 (10.7) 38 (11.6) 42 (12.8) 21 (6.4) 25 (7.6) 5400 6000 5600 6400 2549 2832 2643 3020 52 57 50 56 (15.9) (17.4) (15.2) (17.1) 44 49 40 46 (13.4) (14.9) (12.2) (14.0) 37 (11.3) 41 (12.5) 33 (10.1) 38 (11.6) 29 32 27 30 7200 8000 3398 3776 62 (18.9) 66 (20.1) 51 (15.5) 57 (17.4) 42 (12.8) 47 (14.3) 33 (10.1) 35 (10.7) TWE050 TWE155 TWE200 (13.1) (14.6) (16.2) (14.0) (15.5) (14.3) (15.9) (17.1) (8.8) (9.8) (8.8) (9.4) (9.8) (9.1) (10.1) (8.8) (9.8) (8.2) (9.1) Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s). Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by throw factor: Terminal Velocity Throw Factor 50 FPM (.25 m/s) x 1.50 100 FPM (.51 m/s) x .75 150 FPM (.76 m/s) x .50 PD-24 — Static Pressure Drop Through Accessories — Air Handler Unit Model No. Discharge Return Grille Plenum and Grille2 In. W.C.1 Pascal In. W.C.1 Pascal L/S 1400 1600 2000 2100 661 755 944 991 .09 .12 .18 .05 (22.4) (29.9) (44.8) (12.5) .16 .21 .33 .19 (39.8) (52.3) (82.2) (47.3) .06 08 .13 .02 .06 .08 .13 .03 .12 .14 .19 .05 — — — .08 TWE075A 2400 3000 1133 1416 .08 .13 (19.9) (32.4) .27 .40 (67.2) (99.6) .03 .06 .06 .12 .08 .17 .12 .23 TWE100A TWE100B 2800 3200 4300 1321 1510 2029 .04 .07 .07 (10.0) (17.4) (17.4) .34 .43 .18 (84.7) (107.1) (44.8) .03 .06 .02 .04 .13 .02 .14 .19 .04 .20 .26 .05 4800 6000 5600 2265 2832 2643 .09 .15 .07 (22.4) (37.4) (17.4) .23 .34 .32 (57.3) (84.7) (79.7) .03 .06 .04 .03 .06 .04 .06 .12 .10 .08 .17 .15 6400 8000 3020 3776 .11 .17 (27.4) (42.3) .43 .66 (107.1) (164.3) .06 .10 .0-6 .10 .13 .20 .19 .30 TWE050A TWE155B TWE200B 3.5-7 Electric Heaters (Kw) 10-14 17-24 CFM 35 1. Return air filter ESP included in Fan Performance Table data. 2. At louver opening angle of 42° F (5.5° C). For ESP at other angle openings, see accessory Installer’s Guide. Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s). Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by throw factor: Terminal Velocity Throw Factor 50 FPM (.25 m/s) x 1.50 100 FPM (.51 m/s) x .75 150 FPM (.76 m/s) x .50 . TWA-PRC001-EN 29 Performance Data Table PD-25 — Auxiliary Electric Heat Capacity — Air Handler No. Stage 1 Stage 2 Total of KW Stages KW Input Btuh Output KW Output KW Input Btuh Output TWE050, 075,100 3.47 6.92 10.39 17.31 1 1 1 2 3.47 9.92 10.39 10.39 11,851 23,606 35,457 35,457 3.47 6.92 10.39 10.39 — — — 6.92 — — — 23,606 — — — 6.92 11,851 23,606 35,457 59,063 3.47 6.92 10.39 17.31 TWE075, 100A, 100 24.22 2 13.83 47,213 13.83 10.39 35,457 10.39 82,670 24.22 TWE155, 200 6.94 13.83 20.78 34,62 1 1 2 2 6.94 13.83 13.83 20.78 23,701 47,213 47,213 70,915 6.94 13.83 13.83 20.78 — — 6.94 13.84 — — 23,701 47,213 — 23,701 — 47,213 6.94 70,915 13.89 118,128 6.94 13.83 20.78 34.61 *Heaters are rated at 400v. For other than rated voltage, 2 Voltage Voltage Capacity = x Rated Capacity and KW = Rated Voltage Rated Voltage ( 30 Total Unit Model No. ) ( ) KW Btuh Output Output KW Output 2 x Rated KW. TWA-PRC001-EN Electrical Data Table ED-1— Electrical Characteristics — Motors — Air Handler Unit Model No. TWE050 TWE075 TWE100 TWE155 TWE200 Standard Fan Motor Amps Phase FLA 3 1.4 3 3.2 3 3.6 3 4.6 3 7.6 Volts 380/415 380/415 380/415 380/415 380/415 LRA 8.2 19.7 25.5 37.5 39.2 Oversized Fan Motor Amps Phase FLA 3 1.8 3 4.0 3 5.3 3 6.9 3 9.0 LRA 21.6 25.5 37.5 39.2 65.1 Table ED-2 — Unit Wiring — Air Handler Unit Model No. TWE050 TWE075 TWE100 TWE155 TWE200 Minimum Circuit Ampacity 2 4 5 6 10 Unit Operating Voltage Range 380/415 380/415 380/415 380/415 380/415 Maximum Fuse Size or Maximum Circuit Breaker 15 15 15 15 15 Table ED-3— Electrical Characteristics — Motors — 60 Cycle — Heat Pumps Compressor Motor Amps Unit Model No. TWA075AD TWA100AD TWA155BD TWA200BD No. 1 1 2 2 Volts 380/415 380/415 380/415 380/415 Phase 3 3 3 3 RLA (Ea.) 11.0 14.9 11.0 14.9 Condenser Fan Motor Amps LRA (Ea.) 90.0 118.0 90.0 118.0 No. 1 1 2 2 Volts 380/415 380/415 380/415 380/415 Phase 1 1 1 1 FLA (Ea.) 1.6 2.7 1.6 2.7 LRA (Ea.) 3.7 7.0 3.7 7.0 Table ED-4 — Unit Wiring — Heat Pumps Unit Model No. TWA075 TWA100 TWA155 TWA200 TWA-PRC001-EN Unit Operating Voltage Range 380/415 380/415 380/415 380/415 Minimum Circuit Ampacity 18.0 25.6 31.6 45.2 Maximum Fuse Size or Maximum Circuit Breaker 30 40 40 60 31 Electrical Data Table ED-5— Unit Wiring With Electric Heat (Single Point Connection) — Air Handlers Heater Model No. BAYHTRL405A BAYHTRL410A BAYHTRL415A BAYHTRL425A BAYHTRL405A BAYHTRL410A BAYHTRL415A BAYHTRL425A BAYHTRL435A BAYHTRL405A BAYHTRL410A BAYHTRL415A BAYHTRL425A BAYHTRL435A BAYHTRM410A BAYHTRM420A BAYHTRM430A BAYHTRM450A BAYHTRM410A BAYHTRM420A BAYHTRM430A BAYHTRM450A Heater KW Rating1 3.47 6.92 10.39 17.31 3.47 6.92 10.39 17.31 24.22 3.47 6.92 10.39 20.78 24.22 6.94 13.83 20.78 34.62 6.94 13.83 20.78 34.62 To Use with Unit Control Stages 1 1 1 2 1 1 1 2 2 1 1 1 2 2 1 1 2 2 1 1 2 2 TWE050AD TWE075AD TWE100AD, TWE100BD TWE155BD TWE200BD 1. KW ratings are at 400v for 3 phase, 400v air handlers 2 Voltage Voltage For other than rated voltage, ampacity = x Rated Capacity and KW = Rated Voltage Rated Voltage 2. Any power supply and circuits must be wired and protected in accordance with local codes. 3. Field wire must be rated at least 75° C. 4. Field wire must be rated at least 90° C. ( 32 ) ( Minimum Circuit Ampacity 2 9 17 24 39 11 18 26 41 56 12 19 27 42 57 21 36 51 81 25 40 55 85 ) Maximum Fuse Breaker Size 2 15 20 25 40 15 20 30 45 60 15 25 30 45 60 30 40 60 90 40 50 60 90 2 Rated KW. TWA-PRC001-EN Jobsite Connections Wiring shown with dashed lines is to be furnished and installed by the customer. All customer- supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit. NOTE: 1. When electric heater accessory is used single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only. TWA050/TWE050 Field Wiring: A — 3 power wires. Line voltage. B — 3 power wires. Line voltage. C — Heat pump thermostat: 6 wires, 24 volts. — Electric heat: add 2 additional wires, 24 volts. D — 2 wires, 24 volts. — Outdoor thermostat: add 1 additional wire per ODT, 24 volts. — Electric heat: add 1 additional wire, 24 volts. (2) TWA050/TWE100B Field Wiring: A — 3 power wires. Line voltage. B — 3 power wires. Line voltage. C — Heat pump thermostat: 7 wires, 24 volts Electric Heat: add 2 additional wires, 24 volts. D — 5 wires, 24 volts to outdoor section ‘’A’’ 2 wires, 24 volts to outdoor section ‘’B’’ 2 wires, 24 volts between outdoor sections ‘’A’’ ‘’B’’ — Electric heat: add 1 additional wire, 24 volts. — Outdoor thermostat: add 1 additional wire, 24 volt. TWA075A/TWE075A; TWA100A/TWE100A Field Wiring: A — 3 power wires, line voltage. B — 3 power wires, line voltage. C — Heat pump thermostat: 6 wires, 24 volts. — Electric heat: add 2 additional wires, 24 volts. D — 6 wires, 24 volts. — Outdoor thermostat: add 1 additional wire, 24 volts. — Electric heat: add 1 additional wire, 24 volts. (2) TWA075A/TWE155B; (2) TWA100A/TWE200B Field Wiring: A — 3 power wires, line voltage. B — 3 power wires, line voltage. C — Heat pump thermostat: 7 wires, 24 volts. — Electric heat: add 2 additional wires, 24 volts. TWA-PRC001-EN D — 9 wires, 24 volts. — Electric heat: add 4 additional wires, 24 volts. — Outdoor thermostat: add 3 additional wires, 24 volts. TWA155B/TWE155B; TWA200B/TWE200B Field Wiring: A — 3 power wires, line voltage. B — 3 power wires, line voltage. C — Heat pump thermostat: 7 wires, 24 volts. — Electric heat: add 2 additional wires, 24 volts. D — 7 wires, 24 volts. — Electric heat: add 4 additional wires, 24 volts. — Outdoor thermostat: add 1 additional wire, 24 volts. 33 Typical Wiring (Heat Pump) Heat Pump — Single Compressor Typical unit wiring diagram. For specific wiring, see individual Service Facts. 34 TWA-PRC001-EN Typical Wiring TWA-PRC001-EN (Heat Pump) 35 Typical Wiring (Heat Pump) Heat Pump — Dual Compressors Typical unit wiring diagram. For specific wiring, see individual Service Facts. 36 TWA-PRC001-EN Typical Wiring TWA-PRC001-EN (Heat Pump) 37 Typical Wiring (Air Handler) Air Handler Typical unit wiring diagram. For specific wiring, see individual Service Facts. 38 TWA-PRC001-EN Dimensional Data (Heat Pump) Figure DD-1 — TWA075 Heat Pump All dimensions are in inches and millimeters. Note 1 MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES (914 MM) FROM WALLS, SHRUBBERY, PRIVACY FENCES, ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72 INCHES (1828 MM) TWA-PRC001-EN 39 Dimensional Data (Heat Pump) Figure DD-2 — 10 Ton TWA100A Heat Pump All dimensions are in inches and millimeters. Note 1 MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES (914 MM) FROM WALLS, SHRUBBERY, PRIVACY FENCES, ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72 INCHES (1828 MM) 40 TWA-PRC001-EN Dimensional Data (Heat Pump) Figure DD-3 — TWA155B Heat Pump All dimensions are in inches and millimeters. Note 1 MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES (914 MM) FROM WALLS, SHRUBBERY, PRIVACY FENCES, ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72 INCHES (1828 MM) TWA-PRC001-EN 41 Dimensional Data (Heat Pump) Figure DD-4 — TWA200B Heat Pump All dimensions are in inches and millimeters. Note 1 MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES (914 MM) FROM WALLS, SHRUBBERY, PRIVACY FENCES, ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72 INCHES (1828 MM) 42 TWA-PRC001-EN Dimensional Data (Air Handler) Figure DD-5 — TWE050A Air Handlers All dimensions are in inches and millimeters. Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit. TWA-PRC001-EN 43 Dimensional Data (Air Handler) Figure DD-6 — TWE075A Air Handler All dimensions are in inches and millimeters. Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit. 44 TWA-PRC001-EN Dimensional Data (Air Handler) Figure DD-7— TWE100A Air Handler All dimensions are in inches and millimeters. Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit. TWA-PRC001-EN 45 Dimensional Data (Air Handler) Figure DD-8— TWE100B Air Handler All dimensions are in inches and millimeters. Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit. 46 TWA-PRC001-EN Dimensional Data (Air Handlers) Figure DD-9— TWE050A, 075A, 100A and TWE100B Air Handler All dimensions are in inches and millimeters. Table DD-1 — Air Handler Dimensions — in. (mm) Model No. TWE050A TWE075A TWE100A TWE100B TWA-PRC001-EN AA 35 5/8 (905) 45 1/8 (1146.2) 61 1/8 (1552.6) 61 1/8 (1552.6) AB 12 1/16 (306.4) 16 (406.4) 16 (406.4) 16 (406.4) AC 1 5/8 (41.3) 1 11/16 (42.9) 1 11/16 (42.9) 1 11/16 (42.9) AD 32 1/4 (819.2) 41 15/16 (1065.2) 57 15/16 (1471.6) 57 15/16 (1471.6) AE 2 15/16 (74.6) 6 5/8 (168.3) 6 5/8 (168.3) 6 5/8 (168.3) AF 32 1/4 (819.2) 41 3/4 (1060.5) 57 13/16 (1468.4) 57 13/16 (1468.4) AJ 7 13/16 (198.4) 7 (177.8) 7 (177.8) 7 (177.8) AK 12 3/8 (314.3) 16 (406.4) 16 (406.4) 16 (406.4) AL 34 9/16 (878) 36 7/8 (936.6) 36 7/8 (936.6) 36 7/8 (936.6) 47 Dimensional Data (Air Handler) Figure DD-10— TWE155B Air Handler All dimensions are in inches and millimeters. Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit. 48 TWA-PRC001-EN Dimensional Data (Air Handlers) Figure DD-11 — TWE200B Air Handler All dimensions are in inches and millimeters. Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit. TWA-PRC001-EN 49 Dimensional Data (Air Handlers) Figure DD-12— TWE155B and 200B Air Handlers All dimensions are in inches and millimeters. Table DD-2 — Air Handler Dimensions — in. (mm) Model No. TWE155B TWE200B A 77 1/4 (1962.2) 89 1/4 (2267) B 1 3/16 (30.2) 1 11/16 (42.9) C 48 (1219.2) 50 13/16 (1290.6) D 11 7/16 (290.5) 11 1/2 (292.1) E 18 (457.2) 20 1/8 (511.2) F 3 3/8 (85.7) 3 1/16 (77.8) G 35 1/16 (890.6) 39 1/8 (993.8) H 73 7/8 (1876.4) 82 7/8 (2105) J 3 3/4 (95.3) 4 9/16 (115.9) P 2 7/8 (73) 4 13/16 (122.2) Q 35 1/16 (890.6) 39 1/8 (993.8) R 3 3/4 (95.3) 4 9/16 (115.9) S 35 1/16 (890.6) 39 1/8 (993.8) T 73 3/8 (1863.7) 82 7/8 (2105) Table DD-2— Air Handler Dimensions — in. (mm) (Continued) Model No. TWE155B TWE200B 50 K 35 1/16 (890.6) 39 1/8 (993.8) L 2 13/16 (71.4) 4 7/8 (123.8) M 18 (457.2) 20 (508) N 3 9/16 (90.5) 3 (76.2) TWA-PRC001-EN Dimensional Data (Accessories) Figure DD-13— Electric Heater for TWE050, 075, 100 Air Handlers All dimensions are in inches and millimeters. Figure DD-14 — Electric Heater for TWE155 and 200 Air Handlers TWA-PRC001-EN 51 Dimensional Data Table DD-3 — Discharge Plenum And Grille Dimensions — in. (mm) Model TWE050 Model No. BAYPLNM015 TWE075 BAYPLNM016 TWE100 BAYPLNM017 A B C 3715/16 2115/16 28 (963.6) (557.2) (711.2) 471/2 25 28 (1206.5) (635) (711.2) 1 63 /2 25 28 (1612.9) (635) (711.2) (Accessories) Figure DD-15 — Discharge Plenum and Grille All dimensions are in inches and millimeters. Table DD-4 — Discharge Plenum And Grille Dimensions — in. (mm) For Use with Electric Heat Model TWE050 Model No. BAYPLNM025 TWE075 BAYPLNM026 TWE100 BAYPLNM027 TWE155 BAYPLNM028 TWE200 BAYPLNM029 A B 3715/16 2115/16 (963.6) (557.2) 471/2 25 (1206.5) (635) 631/2 25 (1612.9) (635) 791/2 2711/16 (2019.3) (703.3) 921/2 307/16 (2349.5) (773.1) C 29 (736.6) 29 (736.6) 29 (736.6) 35 (889) 35 (889) Table DD-5 — Subbase Dimensions — in. (mm) Model TWE050 Model No. BAYBASE001 TWE075 BAYBASE002 TWE100 BAYBASE003 TWE155 BAYBASE004 TWE200 BAYBASE005 52 A 38 (965.2) 471/2 (1206.5) 631/2 (1612.9) 791/2 (2019.3) 921/2 (2349.5) Figure DD-16 — Subbase B 22 (558.8) 25 (635) 25 (635) 275/8 (701.7) 307/16 (773.1) TWA-PRC001-EN Weights (Heat Pumps) Table W-1 — Unit and Corner Weights — Lbs (Kg) Unit Model No. TWA075A TWA100A TWA155B TWA200B Shipping Net Maximum — lbs (Kg) Maximum — lbs (Kg) 390 343 (176.9) (155.6) 468 414 (212.3) (187.8) 816 740 (370.1) (335.7) 970 885 (440.0) (401.4) 1 112 (50.8) 146 (66.2) 195 (88.5) 253 (114.8) Corner Weights 2 3 89 63 (40.4) (28.6) 106 68 (48.1) (30.1) 186 175 (84.4) (79.4) 250 190 (113.4) (86.2) 4 79 (35.8) 94 (42.6) 184 (83.5) 192 (87.1) Table W-2 — Accessory Weights — Net Lbs (Kg) Unit Model No. TWA075A TWA100A TWA155B TWA200B RIS Isolators 2 (.9) 2 (.9) 2 (.9) 2 (.9) Steel Spring Isolators 12 (5.4) 12 (5.4) 12 (5.4) 12 (5.4) Anti Short Cycle Timer 1 (.5) 1 (.5) 1 (.5) 1 (.5) Coil Guard 8 (3.6) 11 (5) 22 (10) 34 (15.4) Thermostats 1 (.5) 1 (.5) 1 (.5) 1 (.5) Low Ambient 23 (10.4) 23 (10.4) 23 (10.4) 23 (10.4) TWA155B, 200B TWA075A, 100A TWA-PRC001-EN 53 Weights (Air Handlers) Table W-3 — Air Handlers, Coils, And Corner Weights — Lbs (Kg)1 Unit Model No. TWE050 TWE075 TWE100 TWE125 TWE200 Note: 1. Shipping Maximum (lbs) 298 (135) 388 (176) 473 (214.6) 754 (342) 886 (401.9) Net Maximum (lbs) 262 (118.9) 346 (157) 419 (190.1) 690 (313) 820 (372) #1 59 (26.8) 79 (35.9) 107 (48.5) 173 (78.5) 204 (92.5) Corner Weights — Vertical #2 #3 59 59 (26.8) (26.8) 79 79 (35.9) (35.9) 107 107 (48.5) (48.5) 173 173 (78.5) (78.5) 204 204 (92.5) (92.5) #4 59 (26.8) 79 (35.9) 107 (48.5) 173 (78.5) 204 (92.5) A 54 (24.5) 77 (35) 102 (46.3) 174 (79) 185 (84) Corner Weights — Horizontal B C 64 64 (29) (29.03) 84 81 (38.1) (36.7) 113 113 (51.3) (51.3) 156 190 (70.8) (86.2) 228 221 (103.4) (100.3) D 54 (24.5) 73 (33.1) 102 (46.3) 170 (77.1) 179 (81.2) If application requires steam or hot water heating coils, field supplied isolators must be utilized. Vertical TWE050, 075, 100 Vertical TWE155, 200 Horizontal TWE050, 075, 100 Horizontal TWE155, 200 Table W-4— Accessory Weights — Lbs (Kg) Unit Model No. TWE050 TWE075 TWE100 TWE155 TWE200 Note: 1. 2. 54 Discharge Plenum And Grille1 58 (26.3) 73 (33.1) 92 (41.7) 124 (56.3) 145 (65.8) Discharge Plenum And Grill2 93 (42.2) 123 (55.8) 156 (70.8) 230 (104.3) 264 (119.8) Return Air Grille 3 (1.4) 5 (2.3) 7 (3.2) 10 (4.5) 12 (5.4) Electric Heat Min. Max. 32/43 (14.5/19.5) 27/45 (12.3/20.4) 27/45 (12.3/20.4) 79/100 (35.8/45.4) 79/100 (35.8/45.4) Subbase 14 (6.4) 19 (8.6) 23 (10.4) 27 (12.3) 31 (14.06) Oversized Motor 31 (14.1) 48 (21.8) 50 (22.7) 80 (36.3) 88 (40) RIS Isolator Floor Mount 2 (.9) 2 (.9) 2 (.9) 2 (.9) 2 (.9) RIS Isolator Suspended Mount 9 (4) 6 (2.7) 7 (3.2) 7 (3.2) 9 (4) Steel Spring Isolator Floor Mount 12 (5.4) 12 (5.4) 12 (5.4) 12 (5.4) 12 (5.4) Steel Spring Isolator Suspended Mount 6 (2.7) 6 (2.7) 6 (2.7) 6 (2.7) 6 (2.7) For use when no heat is supplied. For use with electric heat. TWA-PRC001-EN Mechanical Specifications Heat Pumps General Unit shall be assembled on heavy gauge steel mounting/lifting rails and shall be weather proofed. Unit shall include a hermetic scroll or reciprocating compressor(s), plate fin condenser coil, fans and motors, controls, and holding charge of nitrogen. Operating Range shall be between 115° F and 35° F in cooling as standard from factory. Unit shall be UL 1995 listed and rated in accordance with ARI Standard 210/240 or 340/360. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit’s surface shall be tested 500 hours in salt spray test. Unit shall have removable end panels which allow access to all major components and controls. Refrigeration System — Single Compressor TWA075A,TWA100A units shall have a single refrigeration circuit. Each refrigeration circuit has an integral subcooling circuit. A refrigeration filter drier, expansion valve, and check valves shall be provided as standard.The unit shall have both a liquid line and suction gas line service valve with gauge port. Unit shall have one direct drive,Trane hermetic scroll compressor with centrifugal oil pump providing positive lubrication to moving parts. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Crankcase heater, discharge line thermostat, internal temperature, and current-sensitive motor overloads shall be included for maximum protection. Scroll type compressor shall provide inherently low vibration and noise by having no suction and discharge valves. External high and low pressure cutout devices shall be provided. Evaporator defrost control provided in indoor blower coil unit shall prevent compressor slugging by temporarily interrupting compressor operation when TWA-PRC001-EN low evaporator coil temperatures are encountered. Refrigeration System — Dual Compressor TWA155B,TWA200B units shall have two separate and independent refrigeration circuits. Each refrigeration circuit shall have an integral subcooling circuit. A refrigeration filter drier shall be provided as standard. Unit shall have both a liquid line and suction gas line service valve with gauge ports. Unit shall have twoTrane direct drive, hermetic scroll compressors with centrifugal oil pump and provide positive lubrication to all moving parts. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Crankcase heater, discharge line thermostat, internal temperature, and current-sensitive motor overloads shall be included for maximum protection. Scroll type compressor shall provide inherently low vibration and noise by having no suction and discharge valves. External high and low pressure cutout devices shall be provided. Evaporator defrost control provided in indoor blower coil shall prevent compressor slugging by temporarily interrupting compressor operation when low evaporator coil temperatures are encountered. Condenser Coil Coils shall be internally finned or smooth bore, 3/8" (10mm) copper tubes mechanically bonded to a configured aluminum plate fin as standard. Coil shall be factory pressure and leak tested to 420 psig (2,930 kPa) air pressure. Metal grilles with PVC coating for coil protection is optional. Condenser Fan And Motor(s) Direct-drive, statically and dynamically balanced, 26 or 28 inch (660 or 711 mm) propeller fan(s) with aluminum blades and electro-coated steel hubs shall be used in draw-through vertical discharge position. Either permanently lubricated totally enclosed or open construction type motors shall be provided and shall have built-in current and thermal overload protection. Motor(s) shall have either ball or sleeve bearing type. Controls Heat pump units shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Control wiring shall be 24-volt control circuit which includes fusing and control transformer. Units shall provide external location for mounting a fused disconnect device. Time delay timers to prevent compressors in dual compressor units from simultaneous start-up and antirecycle timers are available as optional accessories. Defrost Controls Electronic timed initiated, temperature terminated defrost system with choice of 50, 70, or 90 minute cycle shall be included.Timed override limits defrost cycle to 10 minutes. Low Ambient Operation Standard units shall start and operate to approximately 35° F (1.7° C) when matched withTrane air handlers and coils. Optional head pressure control accessory permits operation to 0° F (-17.8° C). ACCESSORIES Low Ambient Head Pressure Control — This accessory shall modulate the RPM of unit outdoor fan motor in response to outdoor ambient temperatures and liquid line temperature. Accessory provides unit cooling operation to outdoor temperatures of 0° F (-17.8° C). Vibration Isolation Packages — This accessory shall reduce transmission of noise and vibration to building structures, equipment, and adjacent spaces. Packages shall be available in either neoprene-in-shear or spring-flex types. Time Delay Relay —This accessory shall prevent compressors in dual compressor unit from coming on line simultaneously.Timer shall be 24-volt, 60 cycle, with four minute timing period. Anti-Short-Cycle Timer —This accessory shall prevent rapid on-off compressor cycling in light load conditions by not allowing compressor to operate for 5-7 minutes upon shutdown.This accessory shall consist of a 24-volt, 60 cycle, solid state timing device with either 5 or 7 minute fixedoff timing period. 55 Mechanical Specifications Condenser Coil Guard — Metal grille with PVC coating shall be provided to alleviate coil damage. Black Epoxy Coated Condenser Coil — This factory installed option is designed to provide corrosion protection of air cooled condenser coils for seacoast application. The black epoxy coil protection is a factory applied thermoset vinyl coating, bonded to normal aluminum fin stock. The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests performed in accordance with ASTM B177. Air Handlers General Air handler units shall be completely factory assembled including coil, condensate drain pan, fan motor(s), filters, and controls in an insulated casing that can be applied in either vertical or horizontal configuration. Unit shall be rated and tested in accordance with ARI standard 210/240 or 340/360. Unit shall be UL listed and labeled in accordance with UL 1995 for indoor blower coil units. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Casing shall be completely insulated with cleanable, foil faced, fire-retardant, permanent, odorless, glass fiber material. All insulation edges shall be either captured or sealed. Knockouts shall be provided for unit electrical power and refrigerant piping connections. Captive screws shall be standard on all access panels. Refrigeration System TheTWE050A,TWE075A,TWE100A units shall have a single refrigeration circuit and the TWE100B,TWE155B,TWE200B units shall have dual refrigeration circuits. Each refrigeration circuit is controlled by a factory installed thermal expansion valve. Evaporator Coil Configured aluminum fin surface shall be mechanically bonded to 3/8" (10 mm) 56 internally enhanced copper tubing and shall be factory pressure and leak tested at 375 psig (2586 kPa). Coil is arranged for draw-through airflow and shall provide a double sloped condensate drain pan constructed of PVC plastic.The drain pan shall be removable for cleaning.The condensate drain pan can be installed in any of four positions allowing for vertical or horizontal application and providing external connections on either side of the unit. Evaporator Fan Double inlet, double width, forward curved, centrifugal-type fan(s) with adjustable belt drive shall be standard. Thermal overload protection shall be standard on motor. Fan and motor bearings shall be permanently lubricated. Oversized motors shall be available as an option for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT) Controls Magnetic evaporator fan contactor, low voltage terminal strip, check valve(s), and single point power entry shall be included. All necessary controls shall be factory-installed and wired. Evaporator defrost control shall be included to prevent compressor slugging by temporarily interrupting compressor operation when low evaporator coil temperatures are encountered. Filters One inch, throw-away filters shall be standard onTWE050A,TWE075A, TWE100A andTWE120B model air handlers. Filters shall be accessible from the side coil access panel. Filter rack can be field converted to two inch capability. Two inch, throw-away filters shall be standard onTWE155B andTWE200B models. ACCESSORIES Electric Heaters — UL and CSA approved electric heat modules shall be available for installation directly on fan discharge. Electric heaters shall be available in a wide range of capacities with one or two stage control, singlepoint electric power connection, and terminal strip connections. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally wye connected on 400 volt, three phase. Each 400 volt heater shall have automatic line break high limit controls. Discharge Plenums and Grilles — Accessory discharge plenums shall be available for vertical, free discharge applications. Plenums shall be constructed of heavy-gauge, zinc coated, galvanized steel finished with baked enamel to match the air handler unit. Grilles shall be satin finished aluminum and have four-way adjustable louvers. Return Air Grilles — Accessory return air grille shall be provided for vertical front, free return applications. Grilles shall be installed in place of the front lower side panel. Grille shall be satin finished aluminum with non-adjustable louvers. Mounting Subbase —The accessory shall be available for vertical floor mount configurations. Subbase shall be constructed of heavy gauge, zinc coated, galvanized steel with baked enamel finish to match air handler unit. Subbase is required in the vertical air flow application for condensate drain trapping and when isolators are required. Vibration Isolators — This accessory shall reduce transmission of noise and vibration to building structures, equipment, and adjacent spaces. Packages shall be available in either neoprene-in shear or spring-flex types in floor or suspended mountings. Oversized Motors — Field installed oversized motors shall be available for high static pressure applications. CONTROL OPTIONS Standard Indoor Thermostats —Two stage heating and cooling operation or one stage heating and cooling thermostats shall be available in either manual or automatic changeover. Programmable Electronic Night Setback Thermostat —The option shall provide heating setback and cooling setup with 7day programming capability. Outdoor Thermostat —This option shall provide staging control of electric heaters based on a set outdoor temperature. TWA-PRC001-EN TWA-PRC001-EN 57 58 TWA-PRC001-EN TWA-PRC001-EN 59 The Trane Company An American Standard Company www.trane.com For more information contact your local distributor (dealer), local district office, or e-mail us at comfort@trane.com Literature Order Number TWA-PRC001-EN File Number PL-UN-TWA-PRC001-EN-07-00 Supersedes TWA-PRC001-EN-05/98 Stocking Location Inland - LaCrosse Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No Create Date : 2000:07:25 12:35:53 Producer : Acrobat Distiller 4.05 for Windows Modify Date : 2000:07:25 12:46:40-05:00 Page Count : 60 Page Mode : UseOutlinesEXIF Metadata provided by EXIF.tools