Trane 80 Users Manual 221682_5.p65

100 to the manual a81820a1-fd56-4c0e-aba9-8636433f3a41

2015-01-21

: Trane Trane-80-Users-Manual-236188 trane-80-users-manual-236188 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 16

DownloadTrane Trane-80-Users-Manual- 221682_5.p65  Trane-80-users-manual
Open PDF In BrowserView PDF
TDD-D-1

Upflow/Horizontal
Two-stage Condensing
Gas-Fired Furnace
XV 90

TUY060,080,100,120R9V
Variable Speed Blower
Variable Speed Inducer

PUB. NO. 22-1682-05-0802 (EN)

General
Features
NATURAL GAS MODELS
Central heating furnace designs are
certified by the International Approval
Services (IAS) for both natural and
L.P. gas. Limit setting and rating data
were established and approved under
standard rating conditions using
American National Standards Institute
standards.

AIR DELIVERY
The variable speed, direct drive blower
motor, has sufficient airflow for most
heating and cooling requirements, will
switch from heating to cooling speeds on
demand from room thermostat. The
blower door safety switch will prevent or
terminate furnace operation when the
blower door is removed.

SAFE OPERATION
The Integrated System Control has solid
state devices, which continuously
monitor for presence of flame, when the
system is in the heating mode of
operation. Dual solenoid combination
gas valve and regulator provide extra
safety.

SECONDARY HEAT EXCHANGER
The XV 90 has a special type 29-4C™
stainless steel secondary heat
exchanger to reclaim heat from flue
gases which would normally be lost
outside.

QUICK HEATING
Durable, cycle tested, heavy gauge
aluminized steel heat exchanger
quickly transfers heat to provide warm
conditioned air to the structure. Low
energy power vent blower, to increase
efficiency and provide a positive
discharge of gas fumes to the outside.
BURNERS
Multi-port In-shot burners will give years
of quiet and efficient service. All models
can be converted to L.P. gas without
changing burners.
INTEGRATED SYSTEM CONTROL
Exclusively designed operational
program provides total control of furnace
limit sensors, blowers, gas valve, flame
control and includes self diagnostics for
ease of service. Also contains
connection points for E.A.C./humidifier.
CONDENSATE DRAIN
Built-in trap which can drain from either
side when the furnace is installed upflow.

© 2002 American Standard Inc. All Rights Reserved

2

STYLING
Heavy gauge steel and “wrap-around”
cabinet construction is used in the
cabinet with baked-on enamel finish for
strength and beauty. The heat exchanger
section of the cabinet is completely lined
with foil faced fiberglass insulation. This
results in quiet and efficient operation
due to the excellent acoustical and
insulating qualities of fiberglass. Built-in
bottom pan and alternate bottom, left or
right side return air connection in vertical
position.
FEATURES AND
GENERAL OPERATION
The XV 90 High Efficiency Gas Furnaces
employ a Hot Surface Ignition system,
which eliminates the waste of a constant
burning pilot. The integrated system
control lights the main burners upon a
demand for heat from the room
thermostat. Complete front service
access.
a. Low energy power venter.
b. Vent proving differential switch.

Pub. No. 22-1682-05-0802 (EN)

Contents
Feature Summary

2

Features and Benefits

4

Standard Equipment
Optional Equipment

General Data

6

TUY060R9V3V
TUY080R9V3V
TUY100R9V4V
TUY120R9V5V

Performance Data

Pub. No. 22-1682-05-0802 (EN)

7

Electrical Data

11

Field Wiring

12

Dimensions

15

3

Features
and Benefits
XV 90 STANDARD EQUIPMENT
• Variable speed indoor blower
• Silicon Nitride Igniter with adaptive
heat up
• Variable speed induced draft blower
• Direct/Non-Direct vent option
• Fused 24 volt control circuit
• Manual reset burner safety switches
• Power supply 115/1/60
• Convertible to horizontal on left side
• 2-stage gas valve
• PVC venting-1 or 2 pipe option
• Accessory hook-up capability
• Integrated solid state control with
self-diagnostics
• Attractive color accents
• Heavy gauge aluminized steel heat
exchanger
• Multi-port In-shot burners

4

• HInged blower door
• Perfect fit door latches
• Insulated blower door
• Gasketed blower door
• Internal filter rack
• Standard filter sizes
• Two tone color
• Complete front service access
• Left/right gas connection
• Adjustable fan off times
• Cleanable high velocity filters
• Optional L.P conversion kit
• Selectable cooling fan off delay
eliminates need for BAY24X045
time delay kit
• Lifetime limited primary heat
exchanger or secondary heat
exchanger warranty to original
owner (Residential use)
• 5 Year limited parts warranty

Pub. No. 22-1682-05-0802 (EN)

Features
and Benefits
OPTIONAL EQUIPMENT
Thermostat, Mechanical 2-Stage Heating/1-Stage Cooling .......................................................................................... TAYSTAT241 [
Thermostat, Heating/Cooling Single Stage (Mounts Horizontally) .................................................................................... AY28X092 [
Thermostat, Heating/Cooling Single Stage (Mounts Vertically) .................................................................................... BAYSTAT305 [
Thermostat, Electronic Programmable 2-Stage Heating/2-Stage Cooling .................................................................. TAYSTAT302C [
Thermostat, Electronic Programmable 1-Stage Heating/1-Stage Cooling .................................................................. TAYSTAT300C [
Propane Conversion Kit ......................................................................................................................................... BAYLPKT210A [
Electronic Air Filter, “Perfect Fit” Super Efficiency (14-1/2" Wide Gas Furnace) ......................................................... TFE145A9FR0 [
Electronic Air Filter, “Perfect Fit” Super Efficiency (17-1/2" Wide Gas Furnace) ......................................................... TFE175A9FR0 [
Electronic Air Filter, “Perfect Fit” Super Efficiency (21" Wide Gas Furnace) ............................................................... TFE210A9FR0 [
Electronic Air Filter, “Perfect Fit” Super Efficiency (24-1/2" Wide Gas Furnace) ......................................................... TFE245A9FR0 [
Electronic Air Filter, “Perfect Fit” High Efficiency (14-1/2" Wide Gas Furnace) .......................................................... TFM145A9FR0 [
Electronic Air Filter, “Perfect Fit” High Efficiency (17-1/2" Wide Gas Furnace) .......................................................... TFM175A9FR0 [
Electronic Air Filter, “Perfect Fit” High Efficiency (21" Wide Gas Furnace) ................................................................ TFM210A9FR0 [
Electronic Air Filter, “Perfect Fit” High Efficiency (24-1/2" Wide Gas Furnace) .......................................................... TFM245A9FR0 [
Electronic Air Filter, “Perfect Fit” Standard Efficiency (14-1/2" Wide Gas Furnace) ..................................................... TFP145A9FR0 [
Electronic Air Filter, “Perfect Fit” Standard Efficiency (17-1/2" Wide Gas Furnace) ..................................................... TFP175A9FR0 [
Electronic Air Filter, “Perfect Fit” Standard Efficiency (21" Wide Gas Furnace) .......................................................... TFP210A9FR0 [
Electronic Air Filter, “Perfect Fit” Standard Efficiency (24-1/2" Wide Gas Furnace) ..................................................... TFP245A9FR0 [
Coil Enclosure (14-1/2" Wide Cabinets) .................................................................................................................. BAYCLE1400C [
Coil Enclosure (17-1/2" Wide Cabinets) .................................................................................................................. BAYCLE1700C [
Coil Enclosure (21" Wide Cabinets) ........................................................................................................................ BAYCLE2100C [
Coil Enclosure (24-1/2" Wide Cabinets) .................................................................................................................. BAYCLE2400C [
Side Filter Rack ........................................................................................................................................................ BAYFLTR200 [
Filter Kit/Horizontal Conversion TUY060, 080-R ......................................................................................................... BAYFLTR203 [
Filter Kit/Horizontal Conversion TUY100-R ................................................................................................................ BAYFLTR204 [
Filter Kit/Horizontal Conversion TUY120-R ................................................................................................................ BAYFLTR205 [
Filter Accessory Kit Upflow 14.5" Furnaces ............................................................................................................... BAYFLTR317 [
Filter Accessory Kit Upflow 21" Furnaces .................................................................................................................. BAYFLTR321 [
Filter Accessory Kit Upflow 24.5" Furnaces ............................................................................................................... BAYFLTR324 [
High Altitude Switch TUY060R .............................................................................................................................. BAYHALT2451 [
High Altitude Switch TUY080, 100R ...................................................................................................................... BAYHALT2461 [
High Altitude Switch TUY120R .............................................................................................................................. BAYHALT2471 [
Concentric Vent Kit ............................................................................................................................................... BAYVENT100A [
Sidewall Vent Termination Kit ................................................................................................................................. BAYVENT200B [
Manufactured/Mobile Home Kit ............................................................................................................................. BAYMFGH100A [
1 Optional kit allows 200 ft. max. vent length from 5,000-12,000 feet above sea level. See installer's guide.

Pub. No. 22-1682-05-0802 (EN)

5

]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]

General
Data
TUY-R9V PRODUCT SPECIFICATIONS1
MODEL
RATINGS2
1st Stage Input BTUH
1st Stage Capacity BTUH (ICS)3
2nd Stage Input BTUH
2nd Stage Capacity BTUH (ICS)3
AFUE (ICS)
Temp. Rise (Min.-Max.) °F.
BLOWER DRIVE
Dia.-Width (In.)
No. Used
Speeds (No.)
CFM vs. in. w.g.
Motor HP
R.P.M.
Volts/Ph/Hz
COMBUSTION FAN - TYPE
Drive - No. Speeds
Motor HP - RPM
Volts/Ph/Hz
FL Amps
FILTER — Furnished?
Type Recommended
Filter (No.-Size-Thk.)
VENT — Size (In.)
HEAT EXCHANGER
Type -Fired
-Unfired
Gauge (Fired)
ORIFICES — Main
Nat. Gas. Qty. — Drill Size
L.P. Gas Qty. — Drill Size
GAS VALVE
DIRECT IGNITION DEVICE
Type

TUY060R9V3V

TUY080R9V3V

TUY100R9V4V

TUY120R9V5V

39000
37000
60000
56000
93.0
35 - 65

52000
49000
80000
73000
92.5
35 - 65

65000
62000
100000
93000
93.0
35 - 65

78000
74000
120000
112000
92.5
40 - 70

DIRECT
10 x 8
1
VARIABLE
SEE FAN PERF. TABLE
1/2
VARIABLE
115/1/60

DIRECT
10 x 8
1
VARIABLE
SEE FAN PERF. TABLE
1/2
VARIABLE
115/1/60

DIRECT
10 x 10
1
VARIABLE
SEE FAN PERF. TABLE
1
VARIABLE
115/1/60

DIRECT
10 x 10
1
VARIABLE
SEE FAN PERF. TABLE
1
VARIABLE
115/1/60

CENTRIFUGAL
DIRECT - VARIABLE
1/15 - 5000
115/1/60
1.1

CENTRIFUGAL
DIRECT - VARIABLE
1/15 - 5000
115/1/60
1.1

CENTRIFUGAL
DIRECT - VARIABLE
1/15 - 5000
115/1/60
1.1

CENTRIFUGAL
DIRECT - VARIABLE
1/25 - 5000
115/1/60
1.1

YES
HIGH VELOCITY
1 X 17 X 25 X 1

YES
HIGH VELOCITY
1 X 17 X 25 X 1

YES
HIGH VELOCITY
1 - 20 X 25 X 1

YES
HIGH VELOCITY
1 - 24 X 25 X 1

2 ROUND

2 ROUND

3 ROUND

3 ROUND

ALUMINIZED STEEL TYPE 1

ALUMINIZED STEEL TYPE 1

ALUMINIZED STEEL TYPE 1

ALUMINIZED STEEL TYPE 1

20

20

20

20

3 - 45
3 - 56

4 - 45
4 - 56

5 - 45
5 - 56

6 - 45
6 - 56

REDUNDANT - TWO STAGE

REDUNDANT - TWO STAGE

REDUNDANT - TWO STAGE

REDUNDANT - TWO STAGE

HOT SURFACE IGNITER

HOT SURFACE IGNITER

HOT SURFACE IGNITER

HOT SURFACE IGNITER

BURNERS — Type
Number

IN-SHOT
3

IN-SHOT
4

IN-SHOT
5

IN-SHOT
6

POWER CONN. — V/Ph/Hz4
Ampacity (In Amps)
Max. Overcurrent Protection (Amps)

115/1/60
8.4
15

115/1/60
8.4
15

115/1/60
11.4
15

115/1/60
11.4
15

PIPE CONN. SIZE (IN.)

0.50

0.50

0.50

0.50

DUCT CONN.

SEE OUTLINE DRAWING

SEE OUTLINE DRAWING

SEE OUTLINE DRAWING

SEE OUTLINE DRAWING

DIMENSIONS
Crated (In.)
Uncrated

HXWXD
41-3/4 X 19-1/2 X 30-1/2
SEE OUTLINE DRAWING

H XW X D
41-3/4 X 19-1/2 X 30-1/2
SEE OUTLINE DRAWING

H XW X D
41-3/4 X 23 X 30-1/2
SEE OUTLINE DRAWING

HXWXD
41-3/4 X 26-1/2 X 30-1/2
SEE OUTLINE DRAWING

158/146

158/148

171/160

205/193

WEIGHT
Shipping (Lbs.)/Net (Lbs.)

1 Central Furnace heating designs are certified by AGA and CSA.
2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applicaitons, above
input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
3 Based on U.S. government standard tests.
4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

6

Pub. No. 22-1682-05-0802 (EN)

Performance
Data

*UY060R9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)

AIRFLOW
SETTING
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)

1.5

2.0

2.5

3

DIP SWITCH SETTING
SW 1

SW 2

SW 3

EXTERNAL STATIC PRESSURE
SW 4

ON

ON

OFF

ON

ON

ON

OFF

OFF

ON

ON

ON

OFF

OFF

ON

OFF

ON

OFF

ON

OFF

OFF

OFF

ON

ON

OFF

ON

OFF

OFF

ON

ON

OFF

OFF

OFF

ON

OFF

ON

OFF

OFF

OFF

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

ON

OFF

CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS

0.1

0.3

0.5

0.7

575
65
640
70
700
85
700
100
800
115
900
140
875
130
1000
175
1125
235
1050
195
1200
275
1325
360

575
90
640
110
700
125
700
130
800
155
900
195
875
180
1000
235
1125
295
1050
260
1200
330
1325
425

575
125
640
140
700
160
700
170
800
200
900
240
875
230
1000
285
1125
345
1050
305
1200
385
1300
460

550
155
630
175
700
200
700
210
800
250
900
290
875
270
1000
335
1100
370
1050
350
1100
385
1175
425

0.9
900
310
925
318
920
315
940
330
1000
365

NOTES: * First letter may be "A" or "T"
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*UY060R9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
1st Stage Capacity =
2nd Stage Capacity =
AIRFLOW
SETTING

HEATING
1ST
STAGE

HEATING
2ND
STAGE

DIP SWITCH SETTING
SW 7

EXTERNAL STATIC PRESSURE

SW 8

LOW

ON

ON

MEDIUM LOW

OFF

ON

NORMAL **

ON

OFF

HIGH

OFF

OFF

LOW

ON

ON

MEDIUM LOW

OFF

ON

NORMAL **

ON

OFF

HIGH

OFF

OFF

0.1

0.3

0.5

0.7

0.9

CFM
TEMP. RISE
WATTS

600
57
85

600
57
110

600
57
155

600
57
190

-

CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS

700
49
90
775
44
105
870
39
135
860
61
140
1000
53
190
1125
47
250

700
49
130
775
44
155
870
39
185
920
57
200
1000
53
255
1125
47
315

700
49
175
775
44
195
870
39
235
920
57
245
1000
53
305
1125
47
370

700
49
210
775
44
240
870
39
290
920
57
300
1000
53
340
1025
51
355

670
79
245
700
75
255
775
68
285

1250
42
340

1250
42
405

1250
42
445

1100
48
390

1000
53
355

NOTES:
* First letter may be "A" or "T"
** Factory setting

Pub. No. 22-1682-05-0802 (EN)

37,000
56,000

7

-

-

-

Performance
Data

TUY080R9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)

AIRFLOW
SETTING
(See Notes)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)

2.0

NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)

2.5

3.0

DIP SWITCH SETTING
SW 1

SW 2

SW 3

EXTERNAL STATIC PRESSURE
SW 4

ON

ON

OFF

ON

ON

ON

OFF

OFF

ON

ON

ON

OFF

OFF

ON

OFF

ON

OFF

ON

OFF

OFF

OFF

ON

ON

OFF

ON

OFF

OFF

ON

ON

OFF

OFF

OFF

ON

OFF

ON

OFF

OFF

OFF

OFF

ON

0.1

0.3

0.5

0.7

0.9

CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS

750
84
840
109
940
136
850
113

750
122
840
146
940
177
850
150

750
154
840
181
940
215
870
200

720
185
840
226
940
274
890
250

710
221
820
264
940
318
890
295

CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS

960
150
1080
195
1020
175
1170
240
1290
310
1170
250

990
200
1110
255
1020
225
1180
300
1320
410
1190
315

1000
230
1120
315
1040
280
1200
365
1350
470
1210
370

1020
305
1120
365
1050
330
1200
415
1340
520
1210
435

1010
350
1080
390
1050
375
1130
420
1150
440
1100
405

1390
445
1390
450

1400
500
1400
520

1360
535
1350
535

1210
475
1180
460

NORMAL
CFM
1360
OFF
OFF
OFF
OFF
(400 CFM/TON)
WATTS
365
HIGH
CFM
1360
OFF
OFF
ON
OFF
(450 CFM/TON)
WATTS
355
NOTES: Continuous Fan is with Thermostat Fan Switch on and Dip Switches 5 and 6 in the "ON" position.
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.
3.5

TUY080R9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
1st Stage Capacity =
2nd Stage Capacity =
AIRFLOW
SETTING

HEATING
1ST
STAGE

HEATING
2ND
STAGE

DIP SWITCH SETTING
SW 7

EXTERNAL STATIC PRESSURE

SW 8

LOW

ON

ON

MEDIUM LOW

OFF

ON

NORMAL **

ON

OFF

HIGH

OFF

OFF

LOW

ON

ON

MEDIUM LOW

OFF

ON

NORMAL **

ON

OFF

HIGH

OFF

OFF

49,000
73,000

0.1

0.3

0.5

0.7

0.9

CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS

800
56
105
860
52
115
960
46
150
1080
41
195

800
56
140
880
51
165
990
45
200
1110
40
255

800
56
180
890
50
215
1000
44
230
1120
40
315

800
56
220
920
48
265
1020
44
310
1120
40
365

800
56
265
910
49
320
1010
44
350
1080
41
390

CFM
TEMP. RISE
WATTS

1100
62
205

1100
62
260

1120
61
320

1120
61
370

1090
63
400

CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS

1210
57
265
1360
50
365
1360
50
355

1240
55
340
1390
49
445
1390
49
450

1260
54
410
1400
49
500

1260
54
470
1360
50
535

1130
61
430
1210
57
475

1400
49
520

1350
51
535

1180
58
465

NOTES:
** Factory setting

8

Pub. No. 22-1682-05-0802 (EN)

Performance
Data

TUY100R9V4V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)

AIRFLOW
SETTING
(See Notes)

3.0

LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 1

SW 2

SW 3

SW 4

ON

ON

OFF

ON

ON

ON

OFF

OFF

ON

ON

ON

OFF

CFM
WATTS
CFM
WATTS
CFM
WATTS

0.1

0.3

0.5

0.7

0.9

1040
165
1210
235
1340
390

1040
220
1210
285
1370
390

1040
270
1230
360
1400
465

1030
320
1230
415
1390
525

1030
375
1230
475
1370
580

1220
280
1430
425
1590
575
1420
415
1640
585
1840
780

1230
365
1430
495
1590
625
1430
490
1640
655
1770
795

1250
425
1430
560
1580
685
1340
550
1590
680
1630
725

1230
485
1400
590
1420
615
1410
595
1420
615
1470
655

LOW
CFM
1200
OFF
ON
OFF
ON
(350 CFM/TON)
WATTS
225
CFM
1390
NORMAL
OFF
ON
OFF
OFF
3.5
(400 CFM/TON)
WATTS
335
HIGH
CFM
1590
OFF
ON
ON
OFF
WATTS
490
(450 CFM/TON)
CFM
1370
LOW
ON
OFF
OFF
ON
(350 CFM/TON)
WATTS
325
NORMAL
CFM
1640
4.0
ON
OFF
OFF
OFF
WATTS
515
(400 CFM/TON)
CFM
1840
HIGH
ON
OFF
ON
OFF
(450 CFM/TON)
WATTS
700
NOTES: Continuous Fan is with Thermostat Fan Switch on and Dip Switches 5 and 6 in the "ON" position.
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

TUY100R9V4V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
1st Stage Capacity =
2nd Stage Capacity =
AIRFLOW
SETTING

HEATING
1ST
STAGE

HEATING
2ND
STAGE

DIP SWITCH SETTING
SW 7

EXTERNAL STATIC PRESSURE

SW 8

LOW

ON

ON

MEDIUM LOW

OFF

ON

NORMAL **

ON

OFF

HIGH

OFF

OFF

LOW

ON

ON

MEDIUM LOW

OFF

ON

NORMAL **

ON

OFF

HIGH

OFF

OFF

CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS

NOTES:
** Factory setting

Pub. No. 22-1682-05-0802 (EN)

62,000
93,000

9

0.1

0.3

0.5

0.7

0.9

920
60
130
1020
54
165
1160
48
220
1350
41
320
1290
67
275
1410
61
3561
1640
53
530
1970
44
855

920
60
180
1020
54
220
1160
48
260
1380
40
400
1290
67
355
1460
59
455
1640
53
590
1920
45
895

920
60
220
1020
54
260
1160
48
325
1400
40
470
1330
65
430
1460
59
520
1640
53
660
1780
48
820

920
60
280
1010
55
310
1160
48
390
1400
40
540
1340
64
490
1460
59
590
1600
54
695
1660
52
760

920
60
320
1000
56
365
1150
48
430
1390
40
585
1320
65
545
1370
63
590
1410
61
620
1520
57
695

Performance
Data

TUY120R9V5V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)

AIRFLOW
DIP SWITCH SETTING
EXTERNAL STATIC PRESSURE
SETTING
SW 1
SW 2
SW 3
SW 4
0.1
0.3
0.5
0.7
(See Notes)
LOW
CFM
1210
1210
1220
1230
OFF
ON
OFF
ON
(350 CFM/TON)
WATTS
220
270
325
400
NORMAL
CFM
1400
1440
1450
1450
3.5
OFF
ON
OFF
OFF
(400 CFM/TON)
WATTS
305
390
465
510
HIGH
CFM
1590
1600
1610
1600
OFF
ON
ON
OFF
(450 CFM/TON)
WATTS
425
520
600
645
LOW
CFM
1390
1400
1430
1440
ON
OFF
OFF
ON
(350 CFM/TON)
WATTS
305
375
445
515
NORMAL
CFM
1620
1650
1670
1640
4.0
ON
OFF
OFF
OFF
WATTS
420
530
595
660
(400 CFM/TON)
HIGH
CFM
1840
1830
1820
1670
ON
OFF
ON
OFF
(450 CFM/TON)
WATTS
600
690
765
700
CFM
1800
1780
1780
1700
LOW
OFF
OFF
OFF
ON
WATTS
570
630
705
695
(350 CFM/TON)
NORMAL
CFM
2050
2010
1860
1710
OFF
OFF
OFF
OFF
5
(400 CFM/TON)
WATTS
845
875
805
735
CFM
2160
2040
1920
1780
HIGH
OFF
OFF
ON
OFF
(450 CFM/TON)
WATTS
995
935
875
805
NOTES: Continuous Fan is with Thermostat Fan Switch on and Dip Switches 5 and 6 in the "ON" position.
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

0.9
1230
445
1410
560
1380
575
1420
565
1480
600
1490
620
1530
615
1530
655
1620
730

TUY120R9V5V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
1st Stage Capacity =
2nd Stage Capacity =
AIRFLOW
SETTING

HEATING
1ST
STAGE

HEATING
2ND
STAGE

DIP SWITCH SETTING
SW 7

EXTERNAL STATIC PRESSURE

SW 8

LOW

ON

ON

MEDIUM LOW

OFF

ON

NORMAL **

ON

OFF

HIGH

OFF

OFF

LOW

ON

ON

MEDIUM LOW

OFF

ON

NORMAL **

ON

OFF

HIGH

OFF

OFF

74,000
112,000

CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS

0.1

0.3

0.5

0.7

0.9

1090
62
165
1210
56
220
1340
50
295
1430
47
390
1660
63
485
1870
56
675
2060
51
880
2200
48
1030

1120
60
225
1200
56
280
1360
50
350
1570
43
490
1690
62
590
1870
56
745
1990
53
890
2090
50
965

1080
63
270
1200
56
330
1370
49
425
1580
43
565
1680
62
640
1810
58
770
1850
57
810
1940
54
895

1070
63
310
1180
57
395
1380
49
495
1570
43
625
1640
64
675
1680
62
715
1710
61
750
1790
58
830

1010
67
380
1160
58
455
1330
51
535
1390
49
565
1460
72
600
1490
70
625
1530
68
665
1640
64
750

NOTES:
** Factory setting

10

Pub. No. 22-1682-05-0802 (EN)

Electrical
Data
SCHEMATIC DIAGRAMS FOR GAS FURNACES
TUY060,080,100,120R9V-V

LEGEND

From Dwg. 21D341111 P03
Pub. No. 22-1682-05-0802 (EN)

11

Field
Wiring

FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING

TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES

HUM SEE
NOTE 5

EAC SEE
NOTE 5

From Dwg. 21B341127 Rev. 0

FIELD WIRING DIAGRAM FOR 2 STAGE HEATING THERMOSTAT

TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES

HUM SEE
NOTE 5

EAC SEE
NOTE 5

From Dwg. 21B341126 Rev. 0

12

Pub. No. 22-1682-05-0802 (EN)

Field
Wiring

FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING/COOLING
(OUTDOOR SECTION WITHOUT TRANSFORMER)

From Dwg. 21B341125 Rev. 1

FIELD WIRING DIAGRAM FOR 2 STAGE HEATING SINGLE STAGE COOLING
(OUTDOOR SECTION WITHOUT TRANSFORMER)

From Dwg. 21B341124 Rev. 1

Pub. No. 22-1682-05-0802 (EN)

13

Field
Wiring

FIELD WIRING DIAGRAM FOR 2 STAGE HEATING TWO STAGE COOLING
(OUTDOOR SECTION WITHOUT TRANSFORMER)

TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES

HUM SEE
NOTE 5

EAC SEE
NOTE 5

From Dwg. 21B341128 Rev. 0

14

Pub. No. 22-1682-05-0802 (EN)

(ALL DIMENSIONS ARE IN INCHES)

TUY-R9V-V OUTLINE DRAWING

Dimensions

Pub. No. 22-1682-05-0802 (EN)

15

Trane
A business of American Standard Companies
www.trane.com

File No.

PL-UN-FURN-TDD-D-1 3/98

Supersedes

TDD-D-1 8/95

P.I.

Since Trane has a policy of continuous product improvement, it reserves the right to change design and
specifications without notice.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Create Date                     : 2003:02:14 14:14:12-06:00
Modify Date                     : 2003:05:07 15:23:57-07:00
Page Count                      : 16
Creation Date                   : 2003:02:14 14:14:12-06:00
Mod Date                        : 2003:05:07 15:23:57-07:00
Producer                        : Acrobat Distiller 5.0 (Windows)
Author                          : fegx
Metadata Date                   : 2003:05:07 15:23:57-07:00
Creator                         : fegx
Title                           : 221682_5.p65
EXIF Metadata provided by EXIF.tools

Navigation menu