Trane Big Duct Indoor Installation And Maintenance Manual VRF SVX31A EN 02/01/2013 Variable Refrigerant Flow System Unit Series / Installation, Operation, Maintenan
2015-04-02
: Trane Trane-Big-Duct-Indoor-Installation-And-Maintenance-Manual-684407 trane-big-duct-indoor-installation-and-maintenance-manual-684407 trane pdf
Open the PDF directly: View PDF .
Page Count: 40
Download | |
Open PDF In Browser | View PDF |
Installation, Operation, and Maintenance Variable Refrigerant Flow System Big Duct Indoor Unit Series Models: 4TVA0096B100NB, 4TVA0076B100NB SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. February 2013 VRF-SVX31A-EN Introduction Read this manual thoroughly before operating or servicing this unit. Warnings, Cautions, and Notices Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions. The three types of advisories are defined as follows: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous CAUTIONs situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices. Indicates a situation that could result in NOTICE equipment or property-damage only. WARNING Important Environmental Concerns Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerantsincluding industry replacements for CFCs such as HCFCs and HFCs. Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them. © 2013 Trane All rights reserved WARNING Proper Field Wiring and Grounding Required! Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. WARNING Personal Protective Equipment (PPE) Required! Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below: • Before installing/servicing this unit, technicians MUST put on all PPE recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE. • When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling recommendations. • If there is a risk of arc or flash, technicians MUST put on all PPE in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change. Trademarks All trademarks referenced in this document are the trademarks of their respective owners. VRF-SVX31A-EN Table of Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Warnings, Cautions, and Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Important Environmental Concerns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Important Responsible Refrigerant Practices . . . . . . . . . . . . . . . . . . . . . . . 2 Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Preparing for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Location Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Service Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Unit Insulation for High-Humidity Applications . . . . . . . . . . . . . . . . . . . . . . . . 8 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Mounting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Purging the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Installing Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Leak Testing Pipe Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Installing the Drain System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Centralized Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Testing the Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Refrigerant Pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Drainage Hose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Wiring the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Electronic Expansion Valve (EEV) Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Using the VRF Wireless Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 The 2-Digit Segments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mode 2: Option Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mode 5: Option Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mode A: Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mode d: Specific Digit Changing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 23 24 26 28 29 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Internal Protections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VRF-SVX31A-EN 32 32 33 33 3 Operating Mode for Heat Pump Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Static Pressure Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cleaning the Exterior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Periodic Maintenance Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 33 34 34 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Warranty For Trane Advantage™ VRF Systems and Related Accessories . . . 38 Basic Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Exclusions and Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 4 VRF-SVX31A-EN Model Number Description 4 T V D 0 0 1 8 A 1 0 0 N A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Digit 1: Refrigerant 4 = R410A Digit 2: Brand name T = Trane Digit 3: System type V = Variable Refrigerant Flow Digit 4: Configuration Type (also see separate tab) B = mini 4-way cassette C = 4-way cassette D = MSP duct type (mid-pressure) E = 1-way cassette L = Slim duct type (low pressure) A = HSP duct type high pressure) X = Ceiling W = High-wall Digit 5: Reserved for future use 0 = Not currently used Digit 6, 7, 8: Nominal capacity (Btu/h x 1,000) 007 = 7,000 Btu/h 020 = 20,000 Btu/h 024 = 24,000 Btu/h 009 = 9,000 Btu/h 030 = 30,000 Btu/h 012 = 12,000 Btu/h 018 = 18,000 Btu/h 048 = 48,000 Btu/h 006 = 6,000 Btu/h 036 = 36,000 Btu/h 060 068 076 096 = = = = 60,000 68,000 76,000 96,000 Btu/h Btu/h Btu/h Btu/h Digit 9: Major development sequence B = Second development sequence Digit 10: Electric power supply characteristics 1 = 220/60/1 B = 220–240/50/1 Digit 11: Reserved for future use 0 = Not currently used Digit 12: Controller 0 = None R = Remote control standard W = Wired control standard Digit 13: Region of sale N = North America (UL or ETL) Digit 14: Minor design sequence A = First design sequence B = Second design sequence VRF-SVX31A-EN 5 Preparing for Installation Preparing for Installation Accessories In addition to product literature, the following accessories are supplied with this unit. The type and quantity may differ, depending on the model. Insulation Insulation for for refrigerant refrigerant Drain Template pipe, in pipe, out insulation Cable tie Drain hose insulation Flexible hose Flexible hose clamp Rubber gasket Washer Sleeve Location Considerations When deciding on a location for the indoor unit, the following factors must be considered: 6 • The air inlet and outlet must be unobstructed. • The wall or ceiling must support the weight of the unit. • The wall or ceiling must not be subject to vibration. • Pre-plan for easy and short routing of the refrigerant tubing and wiring to the outdoor unit. • The air must circulate freely in the area to be cooled/heated. • Sufficient clearance must be maintained around the unit. • Condensate must be managed correctly and safety away from the unit. • The unit should be installed in a way that prevents unauthorized access. • The unit must not be installed in an area that is damp or could come into contact with water (such as a laundry room). • The unit must not be exposed to direct sunshine or to other direct heat sources. • The filter must be able to be removed and cleaned easily. • The unit should be placed as far as possible from fluorescent lights so the remote control is not subject to interference. • Care should be taken to prevent harmonics generated by loose or unsupported material in close proximity to a running unit. • The unit must not be installed in an area that is exposed to salt, machine oil, sulfide gas, or corrosive environmental conditions. VRF-SVX31A-EN Preparing for Installation Unit Dimensions Unit: inch (mm) 7 36.0 (914) suspension pos. 41.0 (1040) 51.4 (1306) suspension position 46.8 (1188) air inlet duct flange 5.5 (140) x 8 = 44.1 (1120) A 5.5 (140) x 8 = 44.1 (1120) 46.8 (1188) air outlet duct flange 48.9 (1240) 6 3.9 (100) x 2 = 7.9 (200) B 3.7 (93) C 0.9 (22) D 1.1 (29) E 8.2 (209) F 9.3 (236) 26.0 (660) 15.2 (385) B D E F A 1.8.5 (470) 1.4 (35) OD 1.26 (32) C 25.5 (647) 23.6 (598) Suction side Discharge side No. Item Description 1 Liquid pipe connection 3/8 (9.52) 2 Gas pipe connection 4TVA0076B100NB: 3/4 (19.05) 4TVA0096B100NB: 7/8 (22.22) 3 Drain pipe connection OD 1-1/4 (32), ID 1 (25) 4 Drain pipe connection (option drain pump) OD 1-1/4 (32), ID 1 (25) 5 Power supply/communication connection — 6 Air discharge flange — 7 Air suction flange — 8 Hook 3/8 in. or M10 VRF-SVX31A-EN 7 Preparing for Installation Service Clearances CAUTION Avoid Contact with Fan Motor Blower! Unit depth (D) + 1.97 (50) Install the unit at least 7.54 ft (2.2 m) from the floor to avoid the possibility of contact with the fan motor blower while cleaning the duct. Failure to follow this installation requirement could result in minor to moderate injury. Unit width (W) B = 19.7 (500) A = W + 3.94 (100) 0.78 (20) Unit 0.78 (20) Ceiling Note: If the unit is installed in a ceiling that does not have removable tiles, make allowances for servicing the unit by creating an access hole. If the unit is installed more than 39.4 in. (1 m) above the floor, the access hole must be the size of “B.” If the unit is installed less than 39.4 in. (1 m) above the floor, the access hole must be the size of “A” +“B” both. Unit Insulation for High-Humidity Applications For high-humidity applications, insulate the unit prior to mounting it. Use the following guidelines. D Unit: inch (mm) A and B 48.8 x 18.5 (1240 x 470) B A C and D 18.5 x 41.0 (470 x 1040) C Top and Bottom 48.8 x 41.0 (1240 x 1040) Notes: Use an insulation thickness of at least 3/8 in. (10 mm). Insulate the suction duct and discharge duct at the same time as the sides of the unit. 8 VRF-SVX31A-EN Installation Installation Review “Installation Considerations” before proceeding with installation. Follow the procedures in these sections in the order given. Note: Install the Y-joint before installing the indoor unit. Mounting the Unit If the ceiling is already constructed, piping must be laid into position before placing the unit inside the ceiling. CAUTION Avoid equipment damage and personal injury! Ensure that the ceiling is strong enough to support the weight of the indoor unit. Before hanging the unit, test the strength of each of the attached suspension bolts. To mount the unit: 1. Place the template on the spot where the unit is to be installed and mark the holes. Note: The template may shrink or stretch slightly due to heat or humidity. Before drilling holes, verify proper dimensions between the marks. 2. Determine the appropriate type of suspension bolts and anchors according to the ceiling type. Insert bolt anchors into existing ceiling supports (A) or construct a suitable support (B). A B Concrete Drill hole for anchor Ceiling support Pre-poured anchor Field-supplied suspension bolts (M10 or 3/8 in.) Isolator Bracket 3. Install suspension bolts at all four locations. 4. Screw two nuts to each suspension bolt, leaving space between the nuts for hanging the unit. Note: If the suspension bolts are longer than 59 in. [1.5 m]) or vibrations are a concern, place isolators on the brackets to absorb vibrations. 5. Hang the unit by its support brackets between the two nuts. 6. If pad stoppers or isolators are used to absorb vibrations, place them on the brackets. 7. Tighten the nuts to suspend the unit following the guidelines in the figure below. Threaded rod should not protrude more than 1.2 in (30 mm) below the top of the bracket Washers, isolators, or spacers VRF-SVX31A-EN 9 Installation 8. Maintain proper spacing between the unit and the ceiling; refer to the following figure. 0.78 (20) Unit 0.78 (20) Ceiling 9. Adjust the level of the unit so that it tilts1° to the side of the unit that will be connected to the drain hose. A tilt of 1°is also recommended when a drain pump is installed. Drain hose port 1° Purging the Unit The unit is shipped from the factory with a holding charge of nitrogen. All of this gas must be purged from the unit. To purge the unit, remove the caps from the ends of both gas and liquid refrigerant pipes. Make sure all gas has escaped before connecting the piping. Note: To prevent dirt or foreign objects from getting into the pipes during installation, do not remove the caps completely until you are ready to connect the piping. Wet cloth Liquid refrigerant port Gas refrigerant port Welding flame 10 VRF-SVX31A-EN Installation Installing Refrigerant Piping Connect field-supplied piping using flared connections (not supplied) or by brazing. The large unit port is for gas refrigerant; the small one is for liquid refrigerant. Cut or extend field-supplied piping as needed. Use the following procedures. NOTICE System Failure! If brazing is used for pipe connections, a nitrogen purge is required to prevent the formation of copper oxides inside the piping. Failure to follow this procedure could damage the system. • Before connecting the pipes, make sure they are free of dirt and debris. • Use insulated, unwelded, degreased, and deoxidized copper pipe (Cu-DHP type according to ISO 1337 or UNI EN 12735-1) suitable for an operating pressure of at least 609.15 psi (4200 kPa) and a burst pressure of at least 3002.28 psi (20,700 kPa). Copper pipe for hydro-sanitary applications is unsuitable. • For sizing and limits (height difference, line length, maximum bends, refrigerant charge, and so on) see the outdoor unit installation manual. • All refrigerant connections must be accessible for servicing and maintenance. Pipe Cutting Required tools: • Pipe cutter • Reamer • Pipe holder 1. Using a pipe cutter, cut the pipe so that the cut edge is at 90° to the side of the pipe. 2. Use a reamer to remove all burrs at the cut edge. See examples of correctly and incorrectly cut pipes. Correct: 90º Oblique Rough Burr Flared Pipe Connections Clutch type and wing nut type flare tools are available for flared pipe connections. 1. Slide the flare nut over the pipe to be flared. 2. Slide the end of the pipe into the hole on the flaring bar that fits the pipe, leaving a length of pipe, determined by tool type (see table), extending above the flaring bar. Clamp it down. Length of pipe extending above flare bar Flaring bar Pipe VRF-SVX31A-EN 11 Installation Conventional flare tool R-410A clutch type 0–0.020 in. Clutch type Wing nut type 0.04–0.06 in. 0.06–0.08 in. 3. Attach the yoke to the flaring bar, centering the conical part over the end of the pipe that is extending above the flaring bar. 4. Tighten the yoke securely to flare the end of the pipe. Yoke Flaring bar Copper pipe Flare nut 5. Remove the pipe. The end of the pipe that you flared should look like the end of a trumpet. See examples of correctly and incorrectly flared pipes. Correct Inclined Damaged surface Cracked Uneven thickness 6. Align the pipes and tighten the flare nuts manually and then with a spanner torque wrench, applying the torque according to pipe dimensions: 12 Flare dimension (in.) 1/4 (6.35) 10.3–13.3 ft·lb 0.34–0.36 3/8 (9.52) 25.1–31.0 ft·lb 0.50–0.52 1/2 (12.70) 36.1–45.0 ft·lb 0.64–0.65 5/8 (15.88) 50.2–60.5 ft·lb 0.76–0.78 Flare shape (in.) 45°±2° Connection torque (ft·lb) 90°±2° Outer diameter (in. [mm]) R.016–.031 VRF-SVX31A-EN Installation Leak Testing Pipe Connections WARNING Confined Space Hazards! Do not work in confined spaces where refrigerant or other hazardous, toxic or flammable gas may be leaking. Refrigerant or other gases could displace available oxygen to breathe, causing possible asphyxiation or other serious health risks. Some gases may be flammable and or explosive. If a leak in such spaces is detected, evacuate the area immediately and contact the proper rescue or response authority. Failure to take appropriate precautions or to react properly to such potential hazards could result in death or serious injury. WARNING Explosion Hazard! Never use an open flame to detect gas leaks. It could result in an explosion. Use a leak test solution for leak testing. Failure to follow recommended safe leak test procedures could result in death or serious injury or equipment or property-only-damage. Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or serious injury or equipment or property-only damage. Do not exceed unit nameplate design pressures when leak testing system. Failure to follow these instructions could result in an explosion causing death or serious injury. Notes: • All required piping pressure tests must be completed in accordance with national and/or local codes. • When leak-testing refrigerant systems, observe all safety precautions. • Leak test only one circuit at a time to minimize system exposure to potentially harmful moisture in the air. • Use R-410A refrigerant gas as a tracer for leak detection and use oil-pumped dry nitrogen to develop required test pressures. 1. Close liquid line angle valve. 2. Connect R-410A refrigerant cylinder to high side charging port (at condenser or field supplied discharge line access port). Add refrigerant to reach pressure of 12 to 15 psig. 3. Disconnect refrigerant cylinder. Connect dry nitrogen cylinder to high side charging port and increase pressure to 150 psig. Do not exceed high side (discharge) unit nameplate design pressure. Do not subject low side (suction) components to high side pressure. 4. Check all piping joints, valves, etc. for leaks. Recommend using electronic detector capable of measuring 0.1 oz/year leak rate. 5. If a leak is located, use proper procedures to remove the refrigerant/nitrogen mixture, break connections and make repairs. Retest for leaks. 6. Make sure all service valves are open. VRF-SVX31A-EN 13 Installation Installing the Drain System 1. Push the supplied drain hose as far as possible over the drain hose port. • Do not apply excessive force to the piping on the unit side when connecting the drain hose. • Drain hose port locations differ depending on the unit type. Drain hose Drain hose port Drain hose port 2. Wrap the insulation (supplied) around the drain hose and clamp the connection as tightly as possible until you can see at least 8 holes. Clamp Insulation 3. Install the drain pipe into the drain hose. Secure it with PVC adhesive and clamps as necessary to ensure a tight fit with no leakage. PVC pipe Drain hose 14 VRF-SVX31A-EN Installation 4. Refer to appropriate figure for installing the drain pipe with out without a drain pump. Drain pipe installation with drain pump Air vent Unit: in. (mm) 11.8 (300) 7.87 (200) 39.4–59 (1000–1500) Hanger 0.79 (20) Flexible hose Note: Install a U-trap at the end of the drain pipe to prevent odors. Ceiling Drain pipe installation without drain pump 39.4–59 (1000–1500) Flexible hose Hanger H2 (50) Unit: in. (mm) 1/2H Ceiling VRF-SVX31A-EN Horizontal drain pipe minimum slope: 1/100 slope 15 Installation Centralized Drainage If the installation requires more than three indoor units, install the main air vent at the front of the indoor unit that is farthest from the main drain. It may be necessary to install individual air vents to prevent water flowing back to each indoor unit. For installations without a drain pump, install U-traps at the end of the drain pipe for each unit.See figures below. Drain pipe installation with drain pump 39–59 in. (1–1.5 m) Hanger Main air vent Individual air vent 13 in. (330 mm) maximum Main drain pipe Ceiling Centralized horizontal drainpipe (more than 1/100 slope) Ceiling 16 3.94 in. (100 mm) minimum Drain pipe installation without drain pump VRF-SVX31A-EN Installation Testing the Drainage After completing the installation, test the drainage to make sure there are no leaks: 1. Operate the unit in cool mode. 2. Remove drain pump cover. 3. Squirt water into the drain pan (see figure). 4. Confirm that the water flows out through the drain hose and that no leakage occurs at any of the connections. 5. Reassemble the drain pump cover. VRF-SVX31A-EN 17 Insulation Insulation After determining that there are no leaks in the refrigerant pipes or drainage hose, insulate them as described in these sections. Refrigerant Pipes 1. Use the table below to select the insulation type for each pipe size. Insulation Type Pipe size (in. [mm]) Pipe Liquid pipe Gas pipe(b) High humidity conditions(a) (86°F [30°C], over 85%) Standard conditions (86°F [30°C], 85%) EPDM or NBR 1/4 (6.35) – 3/8 (9.52) 3/8 (9) 3/8 (9) 1/2 (12.70) – 2 (50.80) 1/2 (13) 1/2 (13) 1/4 (6.35) 1/2 (13) 3/4 (19) 3/8 (9.52) – 1 (25.40) 1-1/8 (28.58) – 1-3/4 (44.45) 2 (50.80) 3/4 (19) 1.0 (25) 1.0 (25) 1-1/4 (32) 1-1/2 (38) (a) When installing insulation in any of the following environments, use insulation required for high humidity conditions: Buildings with close proximity to bodies of water or hot springs or on the side of a hill in which the building is partly covered by earth; ceilings frequently exposed to moisture such as in restaurants, saunas, swimming pools, and corridors of dormitories or studios near a frequently-used outdoor exit; buildings with no ventilation system. (b) Internal temperature of gas pipe is higher than 248°F (120°C). 2. Wrap insulation around the entire surface of each pipe, from the indoor unit to the outdoor unit, overlapping insulation to avoid gaps. Clamp insulation tightly to pipe. • Do not wrap the gas and liquid refrigerant pipes together. • Avoid compressing the insulation as much as possible. • Be sure there are no cracks or deformities in the insulation at bends in pipes. • If necessary double the insulation to prevent condensation from forming in warm or humid areas. • Cut off excess insulation. Drainage Hose Insulate (field supplied) the entire surface of the drain pipe that is inside the building, including the connection between the drain hose and drain stub. Clamp tightly. 18 VRF-SVX31A-EN Wiring the Unit Wiring the Unit Observe the following precautions when making electrical connections. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. NOTICE Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage. • • • • • • • • • • • • • • • Make all electrical connections in accordance with electrical codes and ordinances. Select the power cable in accordance with relevant local and national regulations. Wire size must comply with local and national code. Use grade H07RN-F or H05RN-F power cable. Connect the power cable into the power cable terminal and fasten it with a clamp. Unbalanced power must be maintained within 10% of supply rating among whole indoor units. Significantly unbalanced power may shorten the life of the system. If the unbalanced power is greater than 10% of supply rating, the unit will stop and an error code will be generated. Connect the power cable to the auxiliary circuit breaker. An all-pole disconnection from the power supply must be incorporated in the fixed wiring (1/8 in. [3 mm]). All wiring must be protected from weather and damage. Maintain a distance of 2 in. (50 mm) or more between power and communication cables to prevent interference. Maintain a voltage drop of less than 10% between the power source and the unit(s). Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will strip the head and make proper tightening impossible. Over-tightening the terminal screws may break them. Tightening torque for M4 screws: 0.86–1.06 lbf·ft (12.0–14.7 kgf·cm). After making a knockout hole, apply rust-preventive paint to the bare metal around the hole. Secure the cable conduit to the outdoor knockout using the proper connector and bushing. Power Connect the power cable to terminals 1(L) and 2(N) on each indoor unit. Refer to wiring diagram. Communication If installing a wired remote control, connect the communication cable to terminals F3 and F4. Refer to Figure 1. Electronic Expansion Valve (EEV) Kit EEV kits are required for high-wall and convertible units. Refer to the Figure 1. VRF-SVX31A-EN 19 Wiring the Unit Figure 1. Wiring diagram Outdoor unit F1 F2 Wired remote control F3 F4 208–230 V 1(L) 2(N) F1 F2 Indoor unit 1 1(L) 2(N) F1 F2 Indoor unit 2 1(L) 2(N) F1 F2 F3 F4 F2 F1 F1 F2 F1 1(L) 2(N) F1 F2 Indoor unit 4 20 L N Indoor unit 3 F2 F1 F2 1(L) 2(N) F1 F2 Indoor unit 5 EEV kit N L N 1(L) 2(N) L N L F1 F2 Indoor unit 6 VRF-SVX31A-EN Configuration Configuration All VRF indoor units are factory configured. If modifications are required, one of the following control devices can be used: • VRF Wireless Remote Control (instructions follow) • VRF Wired Remote Control • VRF Enterprise Management Software • VRF Auto-Commissioning Tool • VRF System Controller Note: Indoor unit options are configured at the factory; changes are not required for typical installations. Using the VRF Wireless Remote Control To change configurations of the VRF system using the VRF Wireless Remote Control, follow this procedure: 1. Remove the batteries from the remote control, and re-insert them while pressing the Temp+ and Temp- buttons simultaneously (refer to Figure 3). The first 2-digit segment of a 24-digit sequence will appear on the wireless remote control display, as shown: 2. To advance to the next 2-digit segment, press the Mode button (Figure 3). Continue pressing the Mode button until the two-digit segment appears that corresponds to the option setting or address setting you want to view or change. Each 2-digit segment is differentiated from the others by a combination of operation mode (Auto/Cool/Dry...) and ON/OFF icons, as shown below. (See “The 2-Digit Segments,” for more detailed information.) Digits 2 and 3 Digits 4 and 5 Digits 6 and 8 ...and so on, through digits 23 and 24. Note: Digits 1, 7, 13, and 19 do not appear and are not used for configuration. 3. To change the value of the left digit on the display, press the Fan down button. To change the value of the right digit on the display, press the Fan up button. Note: Values and their corresponding settings are listed in the following pages of this section of the manual. 4. To save the setting, press the Power button twice. 5. To restore the wireless remote control to normal operating mode, remove the batteries from the remote control. Then re-insert them. VRF-SVX31A-EN 21 Configuration Figure 2. VRF Wireless Remote Control 2-digit segment Power button Mode button Temp up Temp down 22 Fan up Fan down VRF-SVX31A-EN Configuration The 2-Digit Segments Each 2-digit segment is differentiated from the others by a combination of operation mode and timer on/off icons. See Figure 4. Figure 3. Two-digit segments in the 24-digit sequence Notes: • Digits 1, 7, 13, and 19 (shown in green) are factory set and cannot be changed. They do not appear on the display. • Digit 2 (shown in red) is used to change the configuration mode (see “Configuration Modes” for details). • The digit numbers shown in gray above each digit (D2, D3, etc.) do not appear on the display. Configuration Modes Digit 2 (shown in red in Figure 4) is used to set the configuration mode. The four modes are shown in Figure 5. Figure 4. The four configuration modes Mode “2”: Option setting VRF-SVX31A-EN Mode “5”: Option setting Mode “A”: Addressing Mode “d”: Specific digit changing 23 Configuration Mode 2: Option Setting When digit 2 is set to a value of “2,” the options shown in Table 1 can be set to the values in the right column. Table 1. Option setting mode: Digit 2 = 2 Display screen (mode and On/Off) Digit N/A 1 Factory set to 0 Cannot be changed. Not seen in configuration mode. 2 Option setting mode 2 3 Robot cleaning 0: Disabled 1: Enabled 4 Remote sensor 0: Disabled 1: Enabled 5 Central control 0: Disabled 1: Enabled 6 RPM up 0: Disabled 1: Enabled 7 Factory set to 1 Cannot be changed. Not seen in configuration mode. 8 Drain pump 0: Disabled 1: Enabled (no delay) 2: Enabled (3-min delay)(a) 9 Hot water heater 0: Disabled 1: Enabled 10 Electronic heater 0: Disabled 1: Enabled 11 EEV position when heating is satisfied 0: EEV step is minimum (default) 1: Reduced noise setting 12 Master/Slave unit designation(b) 0: Slave 1: Master 13 Factory set to 2 Cannot be changed. Not seen in configuration mode. N/A D11 D12 N/A 24 Option description Set digit to... VRF-SVX31A-EN Configuration Table 1. Option setting mode: Digit 2 = 2 Display screen (mode and On/Off) N/A Digit Option description Set digit to... 14 External control 0: Disabled 1: On/Off control 2: Off-only control 15 External control output 0: Thermostat control 1: User controlled input 16 S-plasma ion 0: Disabled 1: Enabled 17 Buzzer 0: Enabled 1: Disabled 18 Filter timer (hours of use) 2: 1000 6: 2000 19 Factory set to 3 Cannot be changed. Not seen in configuration mode. 20 Associating wireless remote control with indoor unit(s) 0, 1: Channel 1 2: Channel 2 3: Channel 3 4: Channel 4 21 Heat setting compensation 0: Disabled 1: 3.6°F (2°C) 2: 9°F (5°C) 22 0: EEV step is minimum EEV step of stopped unit during oil return/defrost mode 1: Oil return or reduce noise in defrost mode 23 Motion detection sensor 0: 1: 2: 3: 4: 5: 6: 7: 8: 24 N/A — Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled in in in in in in in in 30 minutes if no motion is detected 60 minutes if no motion is detected 120 minutes if no motion is detected 180 minutes if no motion is detected 30 minutes if no motion is detected and advanced function(c) 60 minutes if no motion is detected and advanced function 120 minutes if no motion is detected and advanced function 180 minutes if no motion is detected and advanced function (a) Cassette-type indoor units are set to “Enabled (3-minute delay)” regardless of digit 8 setting. (b) For heat pump systems, the master indoor unit controls whether the system operates in heating or cooling. If the master indoor unit calls for heating and slave indoor units calls for cooling, the master indoor unit (and any other slave indoor units that call for heating) will operate in heating mode. The slave indoor units that call for cooling will do nothing. (c) Advanced function: Controls heating/cooling or power saving with motion detection. VRF-SVX31A-EN 25 Configuration Mode 5: Option Setting When digit 2 is set to a value of “5,” the options shown in Table 2 can be changed to the values in the right column. Table 2. Option setting mode: Digit 2 = 5 Display screen (mode and On/Off) Digit Option description 1 Factory set to 0 Cannot be changed. Not seen in configuration mode. 2 Option setting mode 5 3 Auto-changeover (HR only) 0: Disabled 1: Enabled (see Figure 6) Heating deadband 4 Note: Applies only when digit 3 is set to “1” (auto-changeover mode is enabled). Cooling deadband 5 Note: Applies only when digit 3 is set to “1” (auto-changeover mode is enabled). Standard for auto-changeover (heating to cooling) 6 Note: Applies only when digit 3 is set to “1” (auto-changeover mode is enabled). 7 Factory set to 1 Standard for auto-changeover (cooling to heating) 8 26 Set digit to... Note: Applies only when digit 3 is set to “1” (autochangeover mode is enabled). 0: 1: 2: 3: 4: 5: 6: 7: Disabled 0.9°F (0.5°C) 1.8°F (1°C) 2.7°F (1.5°C) 3.6°F (2°C) 4.5°F (2.5°C) 5.4°F (3°C) 6.3°F (3.5°C) 0: 1: 2: 3: 4: 5: 6: 7: Disabled 0.9°F (0.5°C) 1.8°F (1°C) 2.7°F (1.5°C) 3.6°F (2°C) 4.5°F (2.5°C) 5.4°F (3°C) 6.3°F (3.5°C) 0: 1: 2: 3: 4: 5: 6: 7: 1.8°F 2.7°F 3.6°F 4.5°F 5.4°F 6.3°F 7.2°F 8.1°F (1°C) (1.5°C) (2°C) (2.5°C) (3°C) (3.5°C) (4°C) (4.5°C) Cannot be changed. Not seen in configuration mode. 0: 1: 2: 3: 4: 5: 6: 7: 1.8°F 2.7°F 3.6°F 4.5°F 5.4°F 6.3°F 7.2°F 8.1°F (1°C) (1.5°C) (2°C) (2.5°C) (3°C) (3.5°C) (4°C) (4.5°C) VRF-SVX31A-EN Configuration Table 2. Option setting mode: Digit 2 = 5 Display screen (mode and On/Off) Digit Option description Set digit to... 0: 1: 2: 3: 4: 5: 6: 7: Time required for mode change 9 10 Note: Applies only when digit 3 is set to “1” (autochangeover mode is enabled). Compensation option for height or pipe length difference between indoor units 5 minutes 7 minutes 9 minutes 11 minutes 13 minutes 15 minutes 20 minutes 30 minutes 0: Use default value 1: Use when height or pipe length difference is as specified in Note 1. 2: Use when height or pipe length difference is as specified in Note 2. Notes: 1. Height difference between the indoor unit being configured and the lowest indoor unit is > 98.4 ft (30 m), or pipe length difference between the outdoor unit and the furthest indoor unit and the outdoor unit and the indoor unit being configured is > 360.9 ft (110 m). 2. Height difference between the indoor unit being configured and the lowest indoor unit is 49.2–98.4 ft (15–30 m), or pipe length difference between the outdoor unit and the furthest indoor unit and the outdoor unit and the indoor unit being configured is 164– 360.9 ft (50–110 m). Example: If the unit being configured is 60 ft away from the outdoor unit, and the furthest in door unit is 300 ft from the outdoor unit, the pipe length difference is 240 ft (300-60=240), so Digit 10 should be set to “2.” Heating On Heating Off Cooling On Cooling Off Figure 5. Heat recovery unit operating in auto-changeover mode Standard temp. for Heating Cooling Temp. C B Standard temp. for Cooling Ts Set temp. for Auto mode A Standard temp. for Heating D Standard temp. for Cooling Heating A : Set with digit 4. B : Set with digit 5. C : Set with digit 6. D : Set with digit 8. Note: Minimum compressor off time for heating or cooling is set by digit 9. VRF-SVX31A-EN 27 Configuration Mode A: Addressing When digit 2 is set to a value of “A,” unit address settings can be changed. See Figure 7, Figure 8, and Table 3. The indoor unit is factory-configured for auto-addressing mode. The factory default address is 0A0000-100000-200000-300000. If the default address is manually changed, the auto-addressing mode is no longer active. If the address has been manually changed, and the installer wants to restore auto-addressing mode, all indoor units in the system must be returned to the initial factory default address. Figure 6. Address setting mode (digit 2 = A): Digits 2–6 Figure 7. 28 Addressing mode for remote control, Digits 9–12 VRF-SVX31A-EN Configuration Table 3. Address setting mode: Digit 2 = A Display screen (Mode and On/Off) Digit Option 1 Factory set to 0 Set digit to... Cannot be changed. Not seen in configuration mode. 2 Addressing mode A 3 Unit/RMC address 0: Automatic address setting (default) 1: Manual address setting 4 Hundreds digit of address Address 5 Tens digit of address Address 6 Ones digit of address Address Mode d: Specific Digit Changing When digit 2 is set to a value of “d,” a single, specific digit can be changed. See Figures 9–11 and Table 4. This mode can be used as a shortcut when only a single digit needs to be changed. Figure 8. Specific digit changing mode The example in Figure 10 shows how to use this mode to change the external control option setting from On/Off control to Off-only control. (For the details on this option, see Table 1.) VRF-SVX31A-EN 29 Configuration Figure 9. Example of using the specific digit changing mode to change an option setting • • • • Digit 2 is set to “d” (the specific digit setting mode). Digit 3 is set to “2” (the option setting mode; refer to “Mode 2: Option Setting”). Digits 4 and 5 are set to “14” (the position of the digit for external control; refer to Table 1). Digit 6 is changed from “1” (On/Off control) to “2” (Off-only control); refer to Table 1. The example in Figure 11 shows how to use this mode to change a unit address from “137” to “134.” Figure 10. Example of using the specific digit changing mode to change a unit address • • • • 30 Digit 2 is set to “d” (the specific digit setting mode). Digit 3 is set to “A” (the addressing mode). Digits 4 and 5 are set to “06” because the 6th digit (“7”) is the digit that is to be changed. Digit 6 is changed from “1” (On/Off control) to “2” (Off-only control). VRF-SVX31A-EN Configuration Table 4. Specific digit changing mode: Digit 2 = d Display screen (Mode and On/Off) Digit Option 1 VRF-SVX31A-EN Factory set to 0 Set digit to... Cannot be changed. Not seen in configuration mode. 2 Specific digit changing mode d 3 Configuration setting mode 4 Position of digit in 24-digit sequence: Tens digit Value that represents position (such as “0” if it is the 9th digit in the sequence) 5 Position of digit in 24-digit sequence: Ones digit Value that represents position (such as “9” if it is the 9th digit in sequence) 6 Setting value The desired setting mode: 1, 2, 5, or A (see Figure 5) Appropriate value for operation, function, or address 31 Operation Operation Familiarize yourself with the unit components and operating tips before operating the unit. Components Air outlet Air intake Note: Your unit and display may look slightly different from the illustration shown above, depending on your model. Operating Tips Follow these tips when using your unit: 32 Cooling If the outside temperature is much higher than the selected indoor temperature, it may take longer than expected to achieve the desired temperature. Avoid making extreme changes in the temperature setting. This practice wastes energy and does not cool the room faster. Heating Because the unit heats the room by removing heat energy from outdoor air, the heating capacity may decrease when outdoor temperatures are extremely low. If the unit provides insufficient heat, use an additional heating source in combination with the unit. Defrost When the unit runs in Heat mode, frost may form due to the temperature difference between the unit and the outside air. If this happens: • The unit stops heating. • The unit will operate automatically in Defrost mode for 10 minutes. • The steam produced on the outdoor unit in Defrost mode is safe. No intervention is required; after about 10 minutes, the unit will resume normal operation. The unit will not operate when it starts to defrost. Fan The fan may not operate for 3–5 minutes after turning on the unit, to prevents cold air from blowing on occupants while the unit is warming up. High indoor and outdoor temperatures If both indoor and outdoor temperatures are high and the unit is running in Heat mode, the outdoor unit fan and compressor may stop at times. This is normal; wait until the unit turns on again. Power failure A power failure will cause the unit to stop operating. When power returns, the unit will automatically resume operation. Minimum Off Timer If the unit has just been turned on, it will not produce cool/warm air for 3 minutes. This delay mechanism protects the outdoor unit compressor. VRF-SVX31A-EN Operation Internal Protections Internal protections operate if an internal fault occurs in the unit. Type Description Cold air dump The internal fan will be off to prevent a cold air dump when the heat pump is in defrost mode. Defrost cycle The internal fan will be off to prevent a cold air dump when the heat pump is in defrost mode. Anti-short cycle timer The compressor observes a 3-minute off time when cycling power to the unit or after an outage. Note: If the heat pump is operating in Heat mode, a defrost cycle is activated to remove frost from an outdoor unit that may have accumulated at low temperatures. The internal fan is switched off automatically and restarted only after the defrost cycle is completed. Operating Ranges For efficient use, operate the unit within the ranges shown in this table. Mode Cooling Outdoor temperature 23°F (-5°C) to 118°F (48°C) Indoor temperature Indoor humidity 64°F (18°C) to 90°F (32°C) 80% or less Heating -4°F (-20°C) to 75°F (24°C) 81°F (27°C) or less — Drying 23°F (-5°C) to 118°F (48°C) 64°F (18°C) to 90°F (32°C) — Note: The standardized temperature for heating is 45˚F (7˚C). If the outdoor temperature drops to 32˚F (0˚C) or below, the heating capacity can be reduced depending on the temperature condition. If the cooling operation is used at over 90˚F (32˚C) (indoor temperature), it does not cool at its full capacity. Operating Mode for Heat Pump Systems For heat pump systems, the main indoor unit controls whether the system operates in heating or cooling. If the main indoor unit calls for heating and sub-indoor units calls for cooling, the main indoor unit (and any other sub-indoor units that call for heating) will operate in heating mode, and the sub-indoor units that call for cooling will do nothing. External Static Pressure Setting The external static pressure configuration settings in the following table are given for each model and static pressure value. Model 4TVA0076B100NB 4TVA0096B100NB VRF-SVX31A-EN Static pressure (inH2O) Configuration setting 0.20 011054-195097-20DCDC-331110 0.4 011054-1950C7-20DCDC-331110 0.6 011054-1950E8-20DCDC-331110(a) 0.8 011054-19544D-20DCDC-331110 1.0 011054-19549F-20DCDC-331110 0.20 011054-195407-231C1C-331110 0.4 011054-195429-231C1C-331110 0.6 011054-19545B-231C1C-331110(a) 0.8 011054-19549E-231C1C-331110 1.0 011054-1955D1-231C1C-331110 1.1 011054-1955F3-231C1C-331110 33 Operation Cleaning the Exterior Use a dry or damp cloth to wipe the surface of the unit as needed. If necessary, use mild soap and water on a damp cloth. Use a soft brush to remove dirt from the coil. NOTICE Avoid equipment damage and risk of fire! Avoid using benzene or other flammable solvents. They may damage the surface of the unit and increase the potential for fire. Periodic Maintenance Checks Refer to the schedule given in Table 5 for proper unit maintenance. Note: If the unit will not be used for an extended period of time, operate it in Fan mode for 3–4 hours to thoroughly dry it and then disconnect the power plug. Moisture left in the components can cause odors and internal damage. Table 5. Maintenance schedule Description Clean the air filter(a) Monthly Every 4 months Once a year Clean the condensate drain pan(b) x Thoroughly clean the heat exchanger(b) Clean the condensate drain pipe(b) Replace remote control batteries (a) As needed x x x x (a) The described operations should be performed more frequently if the area of installation is very dusty. (b) These operations must always be performed by qualified personnel. For more detailed information, see the installation manual for this unit. 34 VRF-SVX31A-EN Troubleshooting Troubleshooting Refer to Table 6 for solutions to common problems and to Table 7 for a list of alarm conditions with corresponding error codes and LED behavior. Table 6. Solutions to common problems Problem Solution The unit does not operate immediately after restarting it. The anti-short cycle timer prevents the unit from operating immediately to keep it from overloading. The unit will start in 3 minutes. The unit does not operate. Verify the following: The power plug is properly inserted into the wall receptacle. There has not been a power failure. The circuit breaker is switched on/fuses are good. The temperature does not change. Verify that the unit is not operating in Fan mode. If it is, select a different mode. The unit is not producing warm/ cool air. Verify the following: Temperature setting on remote control is higher/lower than the current temperature. Air filter is not clogged with dirt. If the unit has just been turned on, wait 3 minutes for the anti-short cycle timer to expire. Air flow is unobstructed. Line size and length is correct and does not exceed factory recommendations. Operating mode is heat/cool. If unit is not producing warm air, is it set to Cool mode? Remote control is not for a cooling-only unit. That the unit has not been installed in direct sunlight. If so, hang curtains or shades on windows to filter the sun and increase unit efficiency. The fan speed does not change. Verify that Auto or Dry mode is selected. Either of these modes automatically adjust the fan speed. Timer function does not work. Press the Power button on the remote control after setting the time. Odors permeate the room during operation. Verify the origin of the odor. Operate the unit in Fan mode or open the windows to air out the room. A bubbling sound may be heard: The unit makes a bubbling sound When the refrigerant is circulating through the compressor. By the drain pump inside the unit when you press the Power button. Water is dripping from the air flow If the unit has been running for an extended period of time with the blades fully blades. open, adjust the blades to mid-position to alleviate condensation formation. Verify that: Batteries are not depleted. Batteries are correctly installed. The remote control is not working. Nothing is blocking the remote control sensor. No strong fluorescent or neon lighting is near the unit, which may interrupt the signal. The unit does not turn on/off with Ensure that the wired remote control is not set for Group Control. the wired remote control. Indicators on the digital display flash. VRF-SVX31A-EN Press the Power button on the remote control to turn the unit off. Then switch the circuit break off and then on again. 35 Troubleshooting If an error occurs, one of more of the LEDs (located in the optional remote control receiver)will flicker. As a protection strategy, the unit stops operating (and the LED turns off). If the unit is turned on before the problem is resolved, the LED will resume flickering and the unit will stop operating again. Table 7. Diagnostic LEDs for duct type indoor units LED display Alarm condition Error code Indoor temperature sensor error (shorted or open) E121 Evap-in sensor error (shorted or open) E122 Evap-out sensor error (shorted or open) E123 Discharge sensor error (shorted or open) E126 Indoor fan error E154 Outdoor temperature sensor error (shorted or open) E221 Condenser sensor error (shorted or open) E237 Discharge sensor error E251 No communication between indoor and outdoor units for 2 minutes E101 Communication error received from outdoor unit E102 3-minute tracking error on outdoor unit E202 Communication error after tracking due to non-matching quantity of installed indoor units E201 Error due to repeated communication address E108 Communication address not confirmed E109 Error due to opened EEV (2nd detection) E151 Error due to closed EEV (2nd detection) E152 Evap-in sensor is loose E128 Evap-out sensor is loose E129 Thermal switch error (open) E198 36 Power Timer Fan Filter Blue Red Off Off Flickering Off Off Flickering Off Flickering Off Off Off Off Off Flickering Off Flickering Off Off Flickering Off Off Off Flickering Flickering Off Off Off Flickering Flickering Flickering VRF-SVX31A-EN Troubleshooting Table 7. Diagnostic LEDs for duct type indoor units LED display Alarm condition Error code Condenser mid-sensor is loose E241 Refrigerant leakage (2nd detection) E554 Abnormally high temperature on condenser (2nd detection) E450 Low pressure switch (2nd detection) E451 Abnormally high discharge air temperature on outdoor unit (2nd detection) E416 Indoor unit operation stopped due to unconfirmed error on outdoor unit E559 Reverse phase detection error E425 Power Blue Red Off Off Off Off Timer Fan Filter Flickering Flickering Flickering Compressor operation stop due to freeze detection(6th detection) E403 High pressure sensor is loose E301 Low pressure sensor is loose E306 Outdoor unit compression ratio error E428 Outdoor sump down_1 prevention control E413 Compressor operation stopped due to low pressure sensor prevention control E410 Simultaneous opening of cooling/heating MCU solenoid valve (1st detection) E180 Simultaneous opening of cooling/heating MCU solenoid valve (2nd detection) E181 Float switch (2nd detection) E153 Off Flickering Flickering EEPROM error E162 Flickering Flickering Flickering Flickering Flickering EEPROM option error E163 Flickering Flickering Flickering Flickering Flickering Incompatible indoor unit error E164 Off Off Flickering VRF-SVX31A-EN Off Off 37 Warranty For Trane Advantage™ VRF Systems and Related Accessories Warranty For Trane Advantage™ VRF Systems and Related Accessories Products Covered. This warranty is extended by Trane, and applies to all Trane Advantage™ VRF systems and accessories for these products which are sold by Trane and applied in accordance with Trane specifications. Basic Warranty The warrantor warrants for a period of 12 months from the initial start-up or 18 months from date of shipment, whichever is less, against failure due to defects in material and manufacture and that it has the capacities and ratings set forth in Company’s catalogs and bulletins (“Warranty”). If the following conditions are met, the warrantor extends this basic warranty period to five (5) years from date of start-up: • The system is designed using an approved application tool (VRF Select). • The system is installed by a contractor who has successfully completed a Trane factory training class. • A verified commissioning report from the Trane VRF Commissioning Tool is submitted. Exclusions and Limitations Exclusions from this Warranty include damage or failure arising from: wear and tear; corrosion, erosion, deterioration; modifications made by others to the Equipment; repairs or alterations by a party other than Company that adversely affects the stability or reliability of the Equipment; vandalism; neglect; accident; adverse weather or environmental conditions; abuse or improper use; improper installation; commissioning by a party other than Company; unusual physical or electrical or mechanical stress; operation with any accessory, equipment or part not specifically approved by Company; refrigerant not supplied by Company; and/or lack of proper maintenance as recommended by Company. Company shall not be obligated to pay for the cost of lost refrigerant or lost product. Company's obligations and liabilities under this Warranty are limited to furnishing replacement equipment or parts, at its option, FCA (Incoterms 2000) factory or warehouse (f.o.b. factory or warehouse for US domestic purposes) at Company-designated shipping point, freight-allowed to Company's warranty agent's stock location, for all nonconforming Company-manufactured Equipment (which have been returned by Customer to Company. Returns must have prior written approval by Company and are subject to restocking charge where applicable. Equipment, material and/or parts that are not manufactured by Company are not warranted by Company and have such warranties as may be extended by the respective manufacturer. COMPANY MAKES NO REPRESENTATION OR WARRANTY, EXPRESS OR IMPLIED, REGARDING PREVENTION OF MOLD/MOULD, FUNGUS, BACTERIA, MICROBIAL GROWTH, OR ANY OTHER CONTAMINATES. No warranty liability whatsoever shall attach to Company until Customer’s complete order has been paid for in full and Company's liability under this Warranty shall be limited to the purchase price of the Equipment shown to be defective. EXCEPT FOR COMPANY’S WARRANTY EXPRESSLY SET FORTH HEREIN, COMPANY DOES NOT MAKE, AND HEREBY EXPRESSLY DISCLAIMS, ANY WARRANTIES, EXPRESS OR IMPLIED CONCERNING ITS PRODUCTS, EQUIPMENT OR SERVICES, INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF DESIGN, MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE, OR OTHERS THAT ARE ALLEGED TO ARISE FROM COURSE OF DEALING OR TRADE. Additional warranty protection is available on an extra-cost basis and must be in writing and agreed to by an authorized signatory of the Company. Additional terms and conditions of warranty coverage are applicable for refrigeration equipment. If you wish further help or information concerning this warranty, contact: Trane—Warrantor, 2701 Wilma Rudolph Blvd., Clarksville, TN 37040. 38 VRF-SVX31A-EN VRF-SVX31A-EN 39 The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com. The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. © 2013 Trane All rights reserved VRF-SVX31A-EN New 01 Feb 2013 We are committed to using environmentally conscious print practices that reduce waste.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Page Count : 40 Page Mode : UseNone Has XFA : No XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:d1a092a8-c445-415b-935b-babe022d0b11 Producer : Acrobat Distiller 10.1.5 (Windows) Acces flag : F Alt order nbr : Alt order nbr type : Bw color : C Hist model : 4TVA0076B100NB|4TVA0096B100NB Date published : 02/01/2013 Dept id : 0 Topic focused id : TRANE|EN Price : 0 Cur flag : T Lit class id : SV Lit length : 40 Lit order nbr : VRF-SVX31A-EN Lit type id : SVX Media id : PPI Model : Prod class : Prod family id : Prod : Topic related id : TRN-FLD|STARTUP|OWN/DEV|OPER|INST Restrct flag : F Source date : nulldate Source filename : Stocking loc id : LAXCPY Supceded by : Supceded by date : nulldate Unit flag : F Branding : Trane Lol language : EN Object id : 090102b1832a9175 Object name : VRF-SVX31A-EN_02012013 Chronicle id : 090102b1832a9175 Filename : 832a9175.pdf Abstract : Variable Refrigerant Flow System - Big Duct Indoor Unit Series / Installation, Operation, and Maintenance Create Date : 2013:03:04 12:56:20Z Creator Tool : FrameMaker 10.0.2 Modify Date : 2013:03:19 07:41:09-05:00 Metadata Date : 2013:03:19 07:41:09-05:00 Document ID : uuid:8a74875f-4d0b-47d9-bf93-a1ed74e90778 Instance ID : uuid:736efa7c-97cf-4125-ad85-7eda0c2b38e5 N Pages : 40 Format : application/pdf Creator : ircwao Title : VRF-SVX31A-EN 02/01/2013 Variable Refrigerant Flow System - Big Duct Indoor Unit Series / Installation, Operation, and Maintenance Tagged PDF : Yes Author : ircwao Acces Flag : F Alt Order Nbr : Alt Order Nbr Type : Bw Color : C Hist Model : 4TVA0076B100NB|4TVA0096B100NB Date Published : 02/01/2013 Dept Id : 0 Topic Focused Id : TRANE|EN Cur Flag : T Lit Class Id : SV Lit Length : 40 Lit Order Nbr : VRF-SVX31A-EN Lit Type Id : SVX Media Id : PPI Prod Class : Prod Family Id : Topic Related Id : TRN-FLD|STARTUP|OWN/DEV|OPER|INST Restrct Flag : F Source Date : nulldate Source Filename : Stocking Loc Id : LAXCPY Supceded By : Supceded By Date : nulldate Unit Flag : F Lol Language : EN Object Id : 090102b1832a9175 Object Name : VRF-SVX31A-EN_02012013 Chronicle Id : 090102b1832a9175EXIF Metadata provided by EXIF.tools