Super Q II Fans
Sizes 16 through 44
Model Q™ Fans
Sizes 16 through 60
FAN-DS-2
August 2000
FAN-DS-2
Super Q II Fans
Sizes 16 through 44
Model Q Fans
Sizes 16 through 60
2
Features
and Benefits
©American Standard Inc. 2000
Q Fan
The Model Q™ fan is a quiet, airfoil, in-
line fan specifically designed for air
conditioning applications. This highly
refined axial flow fan is available in 13
sizes from 1,000 through 80,000 cfm.
Small and compact, the Q fan has
proven to be the ideal air moving
device for standalone applications and
also for custom air handling units. It
can be used for supply, return and
exhaust systems.
Available in arrangement 1 (for floor
mounting of larger units with heavier
motors) and arrangement 9 (horizontal
or vertical mounting), it can be selected
in class 1, 2 and 3. Arrangement 9
permits factory mounting of the motor
on top, bottom, or either side of the fan
— see below.
Benefits
• The Q (Quiet) Fan
The Trane Model Q fan generates less
low frequency noise (more difficult to
attenuate) than any other type of fan in
the HVAC industry. Sound level
comparisons show common vaneaxial
fans produce up to 23 db higher sound
levels than the Model Q — significant
in industrial applications. Being quieter
than centrifugal fans allows for
installations closer to building
occupants.
• Saves Mechanical Room Space
The compact quiet Q fan saves floor
space, which reduces system first cost.
• Easy To Install
Rigging and installation is so much
quicker and easier that total installed
cost savings are typically five percent
or more.
• Low Maintenance
Belt-driven with fixed blades, Model Q
fan has very few moving parts. This
design results in exceptionally low
maintenance requirements. No fan
teardowns need be scheduled. In fact,
Q fans installed 25 years ago are still
operating just as quietly as when they
were installed.
Discharge End View
Arrangement 9 Arrangement 1
AMCA Licensed Ratings
The Trane Company certifies that the
Model Q fans shown herein are
licensed to bear the AMCA Seal. The
ratings shown are based on tests and
procedures performed in accordance
with AMCA Publication 211 and
comply with the requirements of the
AMCA Certified Ratings Program.
• Flexible Installation
The Model Q arrangement 9 can be set
in any position, for horizontal
discharge, angled discharge and
vertical discharge either upblast or
downflow. The only limitations placed
on this arrangement are those dictated
by good fan installation practice.
• Motor slide rails and drive guard are
standard, at no extra cost.
3
Contents
Q Fan Accessories
• Inlet flange — for simplified, rigid
connection of ductwork to inlet end of
fan
• Inlet screen — safety accessory
mounted to fan inlet. Heavy, plated
steel wire
Note: inlet screen and inlet flange are
mutually exclusive.
• Inlet vanes — mechanically modulate
fan capacity
• Inlet bellmouth — used with unducted
or plenum applications. Improves air
flow and reduces noise.
• Inlet silencer (long or short) — flex
connected to Q fan
• Outlet flange — for simplified, rigid
connection of ductwork to outlet end of
fan
• Outlet screen — safety accessory
mounted to fan outlet. Heavy, plated
steel wire
Note: outlet screen and outlet flange
are mutually exclusive.
• Outlet duct diffuser (equalizer) —
makes fan outlet diameter equal to inlet
diameter
• Outlet flow stabilization screen — small
mesh outlet screen. Helps offset effect
of poor outlet airflow conditions
• Outlet silencer (short or long) — flex
connected to Q fan
• Vertical mounting legs — used with
arrangement 9 for vertical discharge
floor and ceiling mounted
• Isolators — to eliminate vibrations for
floor, ceiling and vertical installations
• Special coatings — to protect against
alkyds, acids and corrosive
environments
• Access door — available on sizes 49, 54
and 60 for easier service
• Drain — recommended to drain off the
condensate where moisture-laden air is
exhausted
• Copper grease lines — plastic lines are
standard
• Double acoustic enhancement —
insulation and perforated sheet metal
to attenuate radiated sound
• Fan insulation — self-adhesive foam,
applied on the outside of the fan shell
to protect against moisture
• Variable frequency inverter balancing
and reinforcement (frequency inverter
by others). This option requires
constant pitch drives. Model Q Fan — Arrangement 9
Features and Benefits 2
Model Number Description 12
Application Considerations 13
Selection Procedure 21
Performance Data 22
Dimensional Data and Weights 48
Mechanical Specifications 54
4
This chart shows a typical NC level
comparison between common
vaneaxials, tubular centrifugals, airfoil
centrifugals and the Trane Model Q™
compact fan. The shaded area
represents range of vaneaxials tested.
Trane Model Q fans require up to
85 percent less cubic space than airfoil
centrifugal fans and 40 percent less
than common vaneaxials of equivalent
installed sound level. Floor space
savings can be as much as 65 percent
when compared to the common
vaneaxial and airfoil centrifugal and
40 percent when compared to tubular
centrifugals.
Vaneaxial Fan
Airfoil Centrifugal Fan
Tubular Centrifugal Fan
Trane Model Q Compact Fan
Features
and Benefits
5
Features
and Benefits
Super Q II Plus
More than twenty years after the
introduction of the Model Q™, it still
retains its reputation as one of the
quietest HVAC fans in the world. This
tradition of excellence continues with
the introduction of a new Q fan
acoustical enclosure and duct silencer
so effective and so compact that we
named it the Super Q II.
Super Q II Fan
Available with Model Q fans from 1,000
to 43,000 cfm, the Super Q II enclosure
inhibits radiated fan and motor noise
from entering the surrounding space. It
internally isolates the fan on high
deflection spring isolators so ductwork
can be connected directly to the
enclosure. It is uniquely designed to be
floor or ceiling mounted with ease.
Although the Model Q needs very little
maintenance, future maintenance
requirements were considered by
Super Q II designers. Every unit has the
bearing grease lines extended through
the casing and every unit has two full
size access panels that provide
complete access to all internal
components.
Variable Air Volume Compatible
The Super Q fan is modulated for VAV
with variable frequency drives (by
others), not with inlet vanes. Variable
speed inverter fan modulation offers
exceptional energy saving and
exceptionally quiet part load operation.
VAV variable speed Q fans are
structurally reinforced to handle the
uneven harmonic loadings associated
with variable speed fan operation. In
addition, the factory gives variable
speed Q fans a precise, 10-point
balance to further help assure trouble-
free operation. Only constant pitch
drives should be used with variable
frequency inverters.
Super Q II Accessories
• Inlet screen — safety accessory
mounted to fan inlet. Heavy, plated
steel wire
• Inlet bellmouth — used with unducted
or plenum applications. Improves air
flow and reduces noise.
• Inlet silencer (long or short) — rigid
connection to Super Q fan
• Outlet flow stabilization screen — small
mesh outlet screen. Helps offset effect
of poor outlet airflow conditions
• Outlet silencer (short or long) — flex
connected to Q fan
• Variable frequency inverter balancing
and reinforcement (frequency inverter
by others). This option requires
constant pitch drives.
• Outlet screen — safety accessory
mounted to fan outlet. Heavy, plated
steel wire.
Super Q II
6
Features
and Benefits
Trane Plus Duct Silencer
The Plus option is a high performance
duct silencer. Designed specifically for
the Super Q II and Model Q™, it has
several unique features that reduce
airborne noise and turbulence to
exceptionally low levels. Briefly, the
Plus option develops maximum static
regain while simultaneously limiting
objectionable mid and high frequency
noise. The Plus option should be used
whenever quiet comfort is desired
and the duct system is acoustically
unable to provide it.
Trane’s Plus Silencer provides
significant noise attenuation, up to
32 db at 1,000 Hz, without a significant
increase in fan horsepower
requirements.
Plus Silencer
The modular, component design
approach of the Super Q II air handling
system makes it exceptionally well
suited for renovation, retrofit and
replacement projects. The Super Q II air
handling system components (fan,
silencers, filter/coil module, etc.) fit
through most doors and elevators and
can be easily field-assembled into any
system configuration (blow-thru, draw-
thru, etc.).
By carrying the concept of noise source
attenuation to its economic maximum,
Trane has created a fan system that can
move significant amounts of air
without creating objectionable low
frequency rumble. It provides proven
acoustical performance with less
design risk. In project after project, the
Trane Model Q fan has been the key to
creating NC 15 to NC 35 quiet
comfort jobs.
Beyond quiet, the Super Q II Plus
system is small and compact. In fact, it
is small and quiet enough that it can be
successfully installed in ceiling
plenums. Locating a Super Q II Plus in
the plenum helps reduce and even
eliminate the floor space needed for
the mechanical room.
7
Features
and Benefits
Low Sound Level, High Efficiency
Provided by Unique Aerodynamic
Features
[7] Hub Streamlining Insulation
[9] Airfoil Vanes (stationary)
[10] Stabilizing Pitch
[4] Airfoil Blade Wheel.
[5] Aerodynamic Pitch
[6] Minimum Tip Clearance [2] Aerodynamic Inlet Bell
[12] End Cone
[8] Exact Blade to Vane Spacing
[11] Precise Divergent Angle Diffuser
Discharge Cone
[3] Aerodynamic Inlet Cone
[1] Thin Strut Patented
Bearing Support
Precision cast fan wheel and diffuser
for highly efficient aerodynamic
performance. [8]
Precise divergent angle for maximum
static regain. [11] Aerodynamic inlet provides smooth
airflow. [3]
Note: Call-out numbers shown above are referenced on page 8.
8
Features
and Benefits
The low sound and high performance
of the Trane Model Q™ fan are achieved
by reducing noise-creating, energy-
consuming turbulence within the fan.
Airflow research and development
techniques employed were similar to
those used in perfecting today’s high
performance axial flow jet engine
compressors. The resulting smooth air
path has made the Model Q the first
vaneaxial fan to provide quiet, efficient
operation, suitable for air conditioning
duty.
Aerodynamic Air Path
A component by component analysis
of the Model Q points to 12
aerodynamic features which are keys
to a smooth air path. Starting at the
inlet, the struts [1] of the patented
bearing support are precisely
positioned in relation to the fan blades.
Air passing over the struts strikes the
blades in a pattern that prevents blade
whine.
The aerodynamically shaped inlet bell
[2] and inlet cone [3] provide uniform
axial flow parallel to the fan shaft. Air is
delivered equally to the leading edge of
the fan blades — no crowding toward
the fan tips.
Air separation is reduced by the
precision cast aluminum airfoil cross
section [4] of the fan blades. Blade pitch
[5], using a variable angle of attack in
the radial dimensions, is precisely
controlled to prevent energy loss.
Exceptionally close clearance
[6] between the blade tips and housing
reduces the eddy currents of fan tip
recirculation. The reinforcing ring
rigidizes the housing to maintain the tip
clearance. The interior of the fan wheel
is insulated to prevent hub
strengthening protrusions from
[7] windmilling in the airstream.
A precisely controlled space [8]
between the fan blades and diffuser
vanes is necessary to allow airflow
stabilization ahead of the vanes. The
vanes themselves are precision cast
aluminum and have an airfoil cross
section [9] and a precise radial pitch
[10]. This provides smooth, spiral-free
discharge.
The diffuser section design [11] is
critical. A precisely determined
diffusion angle produces the greatest
possible static regain within the
confines of the fan. An end cone
[12) covers the fan drive assembly,
thereby reducing the turbulence
generated by air passing over exposed
drives.
Precise Manufacturing Assures
Performance — Advanced
manufacturing techniques assure the
same performance characteristics for
each production Model Q fan.
•Fin Struts — The fin struts of the
patented bearing support are precisely
positioned in relation to the fan blade.
Air passing over the struts strikes the
plate in a pattern that prevents the
irritating whine, from blade frequency,
which is characteristic of industrial
vaneaxials.
•Inlet Bell and Cone — The
aerodynamically shaped inlet bell and
inlet cone provide uniform axial flow
into the fan parallel with the fan shaft.
Air is delivered equally to the leading
edge of the fan blades. This prevents
crowding toward the blade tip.
•Wheel — The wheel consists of 8
precision cast blades with a twisted
radially projected shape and airfoil
cross section. This radial projection
utilizes a variable angle of attack in the
radial dimension and prevents radial
movement as the air particles move
through the wheel.
•Tip Clearance — Close clearance
between the blade tips and housing
reduces eddy currents due to tip
recirculation. The reinforcing ring holds
the housing in its precise shape to
maintain proper clearance.
•Vane Spacing — Precise space
between the fan blades and the diffuser
vanes is necessary to allow flow
stabilization ahead of the vanes. The 29
diffuser vanes also have an airfoil cross
section and a twisted, radially projected
shape. This provides smooth, spiral-
free air discharge.
•Precision Cast Aluminum Fan and
Diffuser — Being cast, blade and vane
shapes are permanently and precisely
fixed. They are not subject to
misalignment or distortion as are
welded, sheet metal forms.
•Diffuser Section — The diffuser
section design is critical. A precisely
determined flare angle at the diffuser
end produces the greatest possible
static regain within the confines of the
fan. Thus, externally mounted diffuser
accessories, common for industrial
vaneaxials, are not necessary.
•Hydraulically Expanded Flow-
Formed Housing — In this process,
the cylindrical housing is drawn to its
final form over an expansion die. The
metal, expanded beyond its elastic
limit, permanently retains the precision
form imparted by the die.
•Ductile Weld Technique — This
technique is required for the fan
housing seam to guarantee success of
the expansion forming process. The arc
and “puddle” are submerged in
molten flux that shields the weld
material from oxidation. This prevents
brittleness and also anneals the weld.
The result is a flexible, ductile seam
capable of being drawn and formed —
another example of the advanced
technology used in the Trane Model
Q fan.
9
Features
and Benefits
The Trane Model Q™ and Super Q II
fans can help you maximize your
building’s usable floor space by using
them in place of centrifugal fans. The
smaller the equipment room, the more
space left for tenants, merchandise, etc.
Saving Valuable
Equipment Room Space
Return or Exhaust Applications
Figure F-1 shows a size 44, single
width, low pressure airfoil centrifugal
fan delivering 20,000 cfm of air.
Because of its size and weight, it is floor
mounted and connected to a return air
plenum. In contrast, a 44-inch Model Q
fan is used in Figure F-2 instead of a
centrifugal fan. Its smaller size and
lighter weight permits ceiling
suspension and approximately 75 sq ft
of floor space is freed up for other use.
Draw-Thru Supply Application
(Small Capacity)
The fan system in Figure F-3 is a
27-inch, single width, medium pressure
airfoil centrifugal fan rated at 9,000 cfm.
Even though it is a relatively small fan,
it is floor mounted beside the coil bank
plenum. Figure F-4 shows a 27-inch
Model Q substituted in place of the
centrifugal. The small size and weight,
plus the installation flexibility of the
Model Q, permits mounting in a
vertical position on top of the plenum.
The space savings is about 25 sq ft.
Figure F-1 Figure F-3
Figure F-2 Figure F-4
10
Features
and Benefits
Draw-Thru Supply Application
(Large Capacity)
A 60-inch, single-width, medium
pressure airfoil centrifugal fan is used
in the system illustrated in Figure F-5 to
supply 45,000 cfm of air. This capacity
can be easily achieved by installing a
pair of 40-inch Model Q™ fans in
parallel as shown in Figure F-6. The
resulting floor space savings is
approximately 85 sq ft!
Blow-Thru Supply Application
Figure F-7 shows a typical medium
pressure, built-up, blow-thru system.
The fan, enclosed in a plenum, is a 33-
inch, double width, airfoil centrifugal
that delivers 30,000 cfm of air. The
bulkiness of the plenum is dictated by
the necessary clearances around the
fan. To save floor space, a 44-inch
Model Q replaces the centrifugal in
Figure F-8. The suspended mounting of
the Model Q frees about 70 sq ft for
installation of pumps and other
equipment.
Figure F-6 Figure F-8
Figure F-5 Figure F-7
11
Features
and Benefits
The Trane Model Q™ fan, with all its
precision and quality, is still a cost
effective fan. When all necessary
system components are considered, it
provides substantial installation cost
savings. In addition, its small size and
variable mounting positions allow
more freedom to the designer and
installer.
First Cost Comparisons
True first cost is the total cost of an
operable installation. With the Trane
Model Q, this consists of only the fan,
drive and isolation. By comparison, the
airfoil centrifugal typically requires
these three components, plus an
integral base. In addition, cost of
isolation for the airfoil is greater
because it is typically twice as heavy as
the Model Q.
The common vaneaxial also requires
more components in most
applications. Besides the fan, drive and
isolation, an inlet bell and diffuser are
frequently necessary to meet cataloged
performance. A sound attenuator is
also required to reduce noise to a level
equivalent to a Model Q fan without
attenuation.
Reduce Installed Cost
By Up To 20 Percent
Lower Installation Costs
The Trane Model Q fan has fewer
components to install and the
advantage of lighter weight. With only
half the weight of airfoil and tubular
centrifugals, it requires less manpower
for rigging and setting the fan in place.
The result is reduced labor, with
corresponding dollar savings on the
typical job.
Lighter weight also reduces inertia pad
requirements. With the Model Q, a pad
has to be considered only on large
Table F-1 — Total Installed Cost Comparison
Standard Trane Tubular
Item Required Centrifugal Model Q Centrifugal Vaneaxial
First Cost Requirement
Fan X X X X
Belt Guard X X X
Integral Base X
Inlet Bell X
Attenuation X
Spring Isolators X X X X
Installation Cost Requirements
Rigging X X X X
Install Attenuation X
Mount Motor (Etc.) X X
Install Isolation X X X X
Average Total Installed Cost X –5 +5 +15
Comparison is based on equal size fans of similar capacities. The airfoil centrifugal fan is used as base (100%) for
comparative purposes. Figures are based on estimates by experienced installing contractors.
Arrangement 9 Trane Model Q fan
requires purchase of motor, motor
rails, belt guard and isolation in
addition to the basic fan.
Arrangement 3 airfoil centrifugal fan
requires purchase of motor, belt
guard, motor slide rail, isolation and
subbase in addition to basic fan.
Class III fans. Airfoil and tubular
centrifugals, because of greater weight,
often require pads for Class I and II to
minimize the effect imposed by normal
vibration.
Combined Saving Significant
A comparison of average total installed
cost is shown in Table F-1. Average cost
figures were developed based on
estimates by experienced installing
contractors. In all cases, the Trane
Model Q represents a significant
savings.
12
Model
Number
Description
Valid Select-
Prod. able
Cat. Item Description
CYCLE QSE E-cycle 16-44 arr 9 cl 1&2
w/o mtr mtd
QSE1 E-cycle 16-44 arr 9 cl1&2
w/mtr mtd
QSQ Q-cycle 16-44 arr 9 cl 1,2&3
MTO Std cycle 16-44 arr 1&9
cl 1,2&3 & SQ2
MTO1 Std cycle 16-44 arr 1&9
w/unit coating
MTO2 Std cycle 49-60 arr 9 cl 1&2
MTO3 Std cycle 49-60 arr 9
w/unit coating
MODEL QFNA Q (Quiet) fan
TYPE SQ2 Super Q2 fan
QFAN Q fan
SIZE 16 Fan size 16” (400 mm)
19 Fan size 19” (475 mm)
21 Fan size 21” (525 mm)
24 Fan size 24” (600 mm)
27 Fan size 27” (675 mm)
30 Fan size 30” (750 mm)
33 Fan size 33” (825 mm)
36 Fan size 36” (900 mm)
40 Fan size 40” (1000 mm)
44 Fan size 44” (1100 mm)
49 Fan size 49” (1225 mm)
54 Fan size 54” (1350 mm)
60 Fan size 60” (1500 mm)
ARRG 9 Arrangement 9 fan
1 Arrangement 1 fan
CLASS 1 Class 1 fan
2 Class 2 fan
3 Class 3 fan
UORT UP Upblast discharge
DOWN Downblast discharge
H Horizontal discharge
MTRS TT Trane supplied motor &
Trane mounted
FT Field supplied motor &
Trane mounted
TF Trane supplied motor &
field mounted
FF Field supplied motor &
field •mounted
TRES WB Thrust restraints WB
(direct ship)
NONE No thrust restraints
DUCT YES Duct canvas
WBAL FACT Q fan inverter factory
balancing
FIELD Inverter ready balanced by
customer
Valid Select-
Prod. able
Cat. Item Description
MTHP 1 Motor hp 1 (.7 kW)
1.5 Motor hp 1.5 (1 kW)
2 Motor hp 2 (1.5 kW)
3 Motor hp 3 (2 kW)
5 Motor hp 5 (4 kW)
7.5 Motor hp 7.5 (5.5 kW)
10 Motor hp 10 (7 kW)
15 Motor hp 15 (11 kW)
20 Motor hp 20 (15 kW)
25 Motor hp 25 (18 kW)
30 Motor hp 30 (22 kW)
40 Motor hp 40 (30 kW)
50 Motor hp 50 (37 kW)
60 Motor hp 60 (44 kW)
75 Motor hp 75 (56 kW)
MTYP HEOP18ODP High eff mtr 1800 rpm
1S/1W
ODP12 ODP High eff mtr 1800/
1200 rpm 2S/2W
ODP91 ODP High eff mtr 1800/
900 rpm 2S/1W
ODP92 ODP High eff mtr 1800/
900 rpm 2S/2W
PHOP18ODP Prem Hi E+3 mtr
1800 rpm 1S/1W
HETE18 TEFC High eff mtr 1800 rpm
1S/1W
PHTE18 TEFC Prem Hi E+3 mtr
1800 rpm 1S/1W
VOLT 200 200 Volt 60 hertz 3 ph motor
208 208 Volt 60 hertz 3 ph motor
230 230 Volt 60 hertz 3 ph motor
460 460 Volt 60 hertz 3 ph motor
575 575 Volt 60 hertz 3 ph motor
MOLO R Motor location right hand
drive
L Motor location left hand
drive
T Motor location top drive
B Motor location bottom drive
GRSL N Nylon grease lines
C Copper grease lines
DTYP C1.2 Constant pitch drive with
1.2 DSFT
C1.4 Constant pitch drive with
1.4 DSFT
C1.5 Constant pitch drive with
1.5 DSFT
V1.2 Variable pitch drive with
1.2 DSFT
V1.4 Variable pitch drive with
1.4 DSFT
V1.5 Variable pitch drive with
1.5 DSFT
Valid Select-
Prod. able
Cat. Item Description
INSL F Fan insulation
FA Fan and accessories
insulation
ENHA DBLE Double acoustic
enhancement
COAT BPI Baked phenolic (heresite)
inside
BPIO Baked phenolic (heresite)
in/outside
EI Epoxy inside
EIO Epoxy inside/outside
EPI Epoxy phenolic
(2 components) inside
EPIO Epoxy phenolic (2
components) inside/outside
EPADI Epoxy phenolic (air dry
heresite) inside
EPADIO Epoxy phenolic (air dry
heresite) inside/outside
PEI Polyester (sanitile) inside
PEIO Polyester (sanitile) inside/
outside
IOPT IB Inlet bell
IF Inlet flange
ISC Inlet screen
IBSC Inlet bell with inlet screen
SH Inlet silencer short
L Inlet silencer long
IV Inlet vanes
NONE No inlet options
OOPT OFLG Outlet flange
OSCN Outlet screen
ODEQ Outlet duct equalizer
ODOF Outlet duct equalizer w/
outlet flange
SH Outlet silencer short
L Outlet silencer long
NONE No outlet options
ISOL SLF Free standing spring floor
isolators
C Housed spring floor isolators
ND Dbl deflection neoprene
floor isolators
RSL Spring rail floor isolators
MSL Steel base w/spring floor isol
KSL Concrete inertia base w/spring
floor isolators
HD Dbl deflection neoprene
ceiling isolators
HS Spring ceiling isolators
DNHS Spring & neoprene ceiling isol
WR Neoprene wall isolators
ADOR MS Access door motor side
OS Access door opp. motor side
9R Access door 90° right of motor
9L Access door 90° left of motor
DRAN YES Drain
MTGL IL Inlet mounting legs
OL Outlet mounting legs
13
Application
Considerations
This section assists the system
designer in application and control of
Trane Q and Super Q II fans.
Satisfactory distribution of conditioned
air requires a properly chosen fan and
a well designed duct system.
Abbreviations
sp ...... static pressure (in. of water)
vp ...... velocity pressure (in. of water)
tp ....... total pressure (in. of water)
ov ...... outlet velocity (ft per minute)
rpm ... fan speed (revolutions per min.)
bhp ... brake horsepower
p ........ air density (lbs/ft3)
db...... decibel (sound power or sound
pressure level)
cps .... cycles per second
cfm .... cubic feet of air per min. at any
density
scfm .. cubic feet per min. of standard air
clean, dry air with a density of
0.075 lbs/ft3 at 70 F and a barometer
reading of 29.92- inches Hg)
The System
An air system may consist of a fan,
ductwork, air control dampers, cooling
coils, heating coils, filters, diffusers,
noise attenuation, turning vanes, etc.
The fan is the component in the system
which provides energy to the airstream
to overcome the resistance to flow of
the other components.
System Component Losses
Every system has a combined
resistance to flow which is usually
different from every other system and
is dependent upon the individual
components in the system. The
determination of the “pressure loss” or
“resistance to flow,” for the individual
components can be obtained from the
component manufacturers. The
determination of pressure losses for
ductwork and branch piping design is
well documented in standard
handbooks such as the ASHRAE
Handbook of Fundamentals.
System Curve
At a fixed volume flow rate (cfm)
through a given air system, a
corresponding pressure loss, or
resistance to this flow, will exist. If the
flow rate is changed, the resulting
pressure loss, or resistance to flow, will
also change. The relationship
governing this change for most
systems is:
PRESSUREc/PRESSURE = (CFMc/CFM)2
The characteristic curve of a typical
“fixed system” plots as a parabola in
accordance with the above
relationship. Typical plots of the
resistance to flow versus volume flow
rate are shown with normalized duct
system curves, Figure A-1.
For a fixed system, an increase or
decrease in system resistance results
from an increase or decrease in the
volume flow rate along the given
system curve only.
Refer to Duct System A, Figure A-1.
Assume a system design point at
100 percent volume and 100 percent
resistance. If the volume flow rate is
increased to 120 percent of design
volume, the system resistance will
increase to 144 percent of the design
resistance in accordance with the
system equation. A further increase in
volume results in a corresponding
increase in system pressure. A
decrease in volume flow to 50 percent
results in a 75 percent reduction in
design resistance.
Figure A-1 — Normalized Duct System Curves
14
Application
Considerations
Performance Data Determination
The fan performance section of this
catalog contains a fan performance
table and fan curve for each fan size.
The performance data contained in this
catalog was calculated from tests
conducted in accordance with AMCA
Standard 210 Laboratory Methods of
Testing Fans for Rating.
The AMCA test procedure uses an
open inlet and 10 wheel diameters of
straight discharge ductwork to assure
maximum static regain. The fan is
direct driven by a dynamometer.
The fan performance tables in this
catalog are based upon standard air:
0.075 lbs/ft3 (70 F, barometric pressure
29.92-inches Hg).
Fan Performance Curves
A fan performance curve is a graphical
presentation of the performance of a
fan. Usually it covers the entire range
from free delivery (wide open cfm, no
obstruction to flow) to no delivery
(blocked tight, an airtight system with
no air flowing).
The point of intersection of the system
curve and the fan performance curve
determines the point of operation and
actual flow volume. If the system
resistance has been accurately
determined and the fan properly
selected, their performance curves will
intersect at the design flow rate. Refer
to Figure A-2. The normalized Duct
System A from Figure A-1 has been
plotted with a normalized fan
performance curve.
Temperature and Altitude Corrections
The fan performance values in the
tables and curves of this catalog are
based on standard air (.075 lbs/ft3). If
the airflow requirement for a particular
job is stated in terms of nonstandard
air, a density correction needs to be
made before selecting the fan. It is
important to also note that most air
friction charts for ducts, filters, coils,
etc. are also based on standard air and
corrections must be made to determine
proper losses at other conditions.
Figure A-3 illustrates the ratio of air
densities to standard air at various
temperatures and elevations. A Q fan is
designed for operation between -20 F
and 150 F only.
Figure A-2 — Point of Operation — Interaction of the System Curve
and the Fan Performance Curve
Figure A-3 — Air Density Corrections
15
The following is the procedure to use
when selecting a fan for elevations and
temperatures other than standard:
1
Determine the air density from
Figure A-3.
2
Divide static pressure at the non-
standard condition by the air density
ratio.
3
Use the actual cfm and corrected static
pressure to determine rpm and bhp
from the fan performance tables.
4
The rpm is correct as selected.
5
The bhp must be multiplied by the air
density ratio determined in step one to
get the actual operating bhp.
Option and Installation Kt Corrections
System effect losses due to less than
ideal inlet or outlet configuration can be
expressed in terms of velocity pressure
by the following expression:
Inlet SP Loss =
Kti
(
Inlet Velocity
)
2
4005
Where Kti =
Inlet Option Kt + Inlet Installation Kt
Outlet SP Loss =
Kto
(
Outlet Velocity
)
2
4005
Where Kto = Outlet Option Kt + Outlet
Installation Kt
Kt is the loss factor for the inlet or
discharge condition being considered.
It is necessary to add all of the static
pressure loss determined from the
above equation to the component
static pressure to determine the point
of duty static pressure for selection of
the fan.
Fan Option Kt Corrections
The fan static pressure should be
adjusted for fan options. Option
pressure drops are documented as Kt
losses and are handled the same way
as installation Kt effects (losses). Use
Table A-1, Q Fan/Super Q II Fan Kt
corrections, to determine the Kt values.
Add these values to any installation Kt
values. Use the result to select the fan.
Table A-2 — Q Fan/Super Q II Fan Option Kt Corrections Super Q II Pressure
Options Use Q-Fan Fan Drop (Kt)
Inlet Flange Connects to bolted inlet duct X 0
Inlet Bellmouth* Reduces Unducted Inlet Kt X X -.1
Inlet Plus Silencer Reduces inlet noise X X +.1
Inlet Screen Protects Unducted Inlets X X +.1
Outlet Screen Protects Unducted Outlets X +.5
Outlet Flange Connects to bolted outlet duct X 0
Outlet Equalizer (Diffuser) Improves SE X 0
Outlet Plus Silencer Reduces Outlet Noise X X +.1
Outlet Flow Stabilization Screen Reduces Outlet swirl X X +.8
Outlet Backdraft Damper Isolates fan from duct Special Special +.5
Frequency Drive Modulation Modulates Q Fan quietly Special Special 0
Belt Guard Protects drives/belts X 0
Motor Rails Allows motor to be mounted X Included 0
Standard Isolators Isolates fan X Included 0
Seismic Isolators Isolates fan X Special 0
*Note: Bellmouth effect included in unducted installation Kt correction. Fan sizes 49 through 60 fan curves are cataloged
with inlet bells. For unducted inlets without bells on size 49 through 60 fans add .1 to the inlet Kt given above.
Inlet vane losses are covered in the Selection Procedure with air density corrections (page 20).
Application
Considerations
Table A-1 — Q Fan/Super Q II Fan Installation Kt Corrections
Unducted (Plenum) Inlet*
Draw-Thru Type Design 0.0
Ducted Inlet
Turn > 3 Dia Upstream -1.0
Turn 2 Dia Upstream +.8
Turn 1 Dia Upstream +1.3
Turn < 1 Dia Upstream
Not Recommended
Unducted Outlet
Blow-Thru Type Design +.8
Ducted Outlet
Turn > 2 Dia Downstream 0.0
Turn 1 Dia Downstream +1.3
Turn < 1 Dia Downstream
Not Recommended
Figure A-4 — Ducted Turns Near Q Fan
16
Application
Considerations
Q and Super Q II Fan Modulation —
AC Inverter Capacity Control
Q fans and Super Q II fans can be
modulated with AC frequency drives.
The Trane Company recommends
Magnetek low noise inverter drives and
Century high efficiency motors for
optimum modulation performance.
Operating the Q or Super Q II fan on AC
frequency drives requires the Q fan to
be strengthened and balanced in the
factory. This option “beefs up” the
mechanical bracing of the Q fan inlet
bearing assembly and calls for a
precision factory balance. Precision
balancing covers 10 operating points
on the system curve from 10 percent
load to full load.
Minimum cfm with AC inverters —
Above 1.5” static pressure, the
minimum cfm is the surge (do not
select) line. Below 1.5” static pressure,
it is 1000 cfm.
Q Fan Modulation — Inlet Vanes
Inlet vanes are a widely used form of
fan modulation. As inlet vanes close,
they impart a spin on the incoming air
in the direction of the fan wheel
rotation. This reduces airflow, static
pressure and brake horsepower.
However, inlet vanes do increase
sound levels. If a job is acoustically
sensitive, AC inverters are
recommended for modulation. As
shown in Figure A-5, a separate cfm
static pressure curve (cfm-sp) is
generated per each inlet vane position.
Likewise, the figure shows brake
horsepower curves that apply for
various inlet vane positions.
Inlet vanes are controlled by placing a
static pressure sensor in the
downstream ductwork, typically about
two-thirds of the way down the longest
trunk duct. This sensor is set at a static
pressure that will ensure sufficient
pressure is available to move air from
that point through the remaining duct
work. The sensor will respond to duct
pressure changes and signal the inlet
vane operator to open or close the
vanes to maintain the control setting at
the sensor location.
As VAV terminal units begin to close in
response to a decreasing cooling load,
static pressure in the ductwork
increases. This causes the fan
operating point to temporarily move
upward to the left on a constant rpm
curve as shown in Figure A-5 (point A
to point B). The static pressure sensor
will detect an increase in duct pressure
and signal the inlet vane operator to
begin to close the vanes. The inlet
vanes will close until the static pressure
sensor is again satisfied, moving the
operation point to C (Figure A-5). As the
cooling load continues to decrease, the
modulation curve will be formed
(point C to D, and point D to E) on
Figure A-5. This curve passes through
the design point and through the static
pressure sensor control point. The
static pressure of any point on this
curve can be calculated using the
formula:
Sp = (Cfm/Cfmd)2 x (SPd-SPc) = SPc
SPd = static pressure at design,
SPc = static pressure control setting,
Cfmd = cfm at design.
The VAV system modulation curve can
be drawn using a Trane system
modulation overlay. The axis of the
overlay is placed on a static pressure
control setting. The curve that
intersects the design points is the
system modulation curve.
Because the axes of the inlet vane
performance graph are in terms of
percent wide open cfm (wocfm)
and percent peak static pressure, the
first step in establishing the system
modulation curve is to find the
proper design points. By plotting the
design point on the performance
curve for the fan in question, one can
easily determine the percent wocfm.
Knowing this, plot a point on the
cfm-sp curve (Figure A-6) for inlet
vanes wide open, at the design point
of wocfm. By tracing to the left, one can
determine the percent of peak static
pressure. By knowing the design cfm,
static pressure and the percent of wide
open cfm and percent peak static that
these values represent, one can
calculate wocfm and peak static
pressure.
Figure A-5 – VAV System Modulation Curve
17
Application
Considerations
The control static pressure can then be
expressed as a percent of peak static
pressure and plotted. The system
modulation curve is described by the
curve on the modulation overlay that
passes through the design point when
the axis is placed on the control static
pressure point.
The minimum inlet vane cfm can easily
be determined after the system
modulation has been established. It
will be one of two things, either a) the
point where the system modulation
curve intersects the surge line, or
b) 40 percent wocfm, whichever is
greater. Forty percent wocfm is the
minimum point a Q fan with inlet vanes
can modulate, due to inherent
instability that results when the vanes
close to a certain angle.
A plot of part load cfm versus brake
horsepower can also be made after the
system modulation curve is established.
At each intersection of the system
modulation curve with a cfm-sp curve
for a certain inlet vane opening, a
vertical line is traced to the appropriate
bhp-cfm curve. At each intersection of a
bhp-cfm curve, a horizontal line is
traced to the scale of percent brake
horsepower. This will lead to a percent
wocfm versus percent peak bhp plot.
The design rpm and bhp need to be
corrected to account for performance
losses due to inlet vanes being in the air
stream. A correction of one percent to
the rpm and three percent to the bhp is
made in order to get to design
conditions with the inlet vanes fully
open.
Part load fan power consumption with
inlet vanes can be determined by
entering Figure A-6 at the desired
percent wide open cfm. (Wide open
cfm is found on the fan curve by
following the fan rpm to the right until
it intersects the 0” static pressure axis.)
On Figure A-6, plot a system curve from
the control static pressure through the
point of operation defined as a
calculated percent wide open cfm. Read
vertically upward from the 25, 50 and 75
percent intersections to determine the
percent bhp at part load.
Intermediate operating points are found
by extrapolation. Inlet vanes increase
Q fan sound levels. See Table A-5.
Figure A-6 – Inlet Vane Performance
18
Application
Considerations
Parallel Fan Operation
The Q fan performance curve has a
characteristic shape where two
different cfm’s are possible at the same
static pressure. Therefore, when
selecting fans for multiple installation
connected with either a common inlet,
a common discharge or both, care
must be taken to eliminate the
possibility of fan paralleling.
Figure A-7 shows two typical cfm-sp
performance curves for the Q fan. Fan
paralleling can occur when multiple
fans are selected in the shaded area.
The shaded area is determined by
going straight across from the lowest
point of the fan performance curve at
the left of the surge line (A and A1) to
the same curve to the right of the surge
line (B and B1). Points B and B1 fall on a
constant system curve.
Table A-3 — Maximum Torque For
Operation Of Inlet Vanes
Control Opening Closing
Arm Torque Torque
Size Class (In.) (In.-Lb) (In.-Lb)
1 8 7
16 2 8.75 14 13
3 23 22
1 12 11
19 2 8.75 21 19
3 34 31
1 17 15
21 2 8.75 31 26
3 32 44
1 26 20
24 2 8.75 48 36
3 79 61
1 37 27
27 2 8.75 66 48
3 109 79
1 52 35
30 2 8.75 94 63
3 155 104
1 65 41
33 2 8.75 128 81
3 212 134
1 100 59
36 2 10.81 180 106
3 298 175
1 138 75
40 2 10.81 249 136
3 412 225
1 193 99
44 2 10.81 349 179
3 576 295
Motor and Drive Selection
The Model Q fan has been designed for
use with NEMA “T” Frame
motors. Motor hp limits for Class I, II,
and III construction are listed in the
roughing-in Dimensional Data section
of this catalog.
Minimizing belt tension forces
increases bearing life and reduces fan
noise. The Q fan and Super Q II fan
drive selection is totally computerized
by the factory to achieve quiet, long life
operation. If Trane provides Q fan
drives, all fan motor information must
be made available to the Trane sales
engineer.
Table A-4 defines this constant
system curve as a percent of wide-
open cfm. If fans in parallel are
always operated to the right of this
constant system curve, fan paralleling
will not occur.
Table A-4 — Parallel Operation
Minimum % of WOCFM
For Two Model Q Fans
Fan Size In Parallel
16 80% WOCFM
19-21 81% WOCFM
24-30 83% WOCFM
33-44 73% WOCFM
49-60 85% WOCFM
Figure A-7 — Selecting Model Q Fans in Parallel
Recommended Q Fan Configuration Inside an Air Handler
Side View
19
Recommended Super Q II Quiet (NC35)
Floor-Mounted (Stacked) Configuration
Application
Considerations
Operating Cost/Efficiency
The quiet Q fan is a very efficient fan.
The Q fan mixed-flow type airfoil thrust
blades offer outstanding efficiency and
operating cost savings over such fan
types as plug fans. Designers can
compare the Q fan efficiency with other
fans by using the fan selection program
and the Trane Customer Direct Service
(C.D.S.™) Network FanMod program.
The Trane fan selection program
provides accurate part load energy
consumption no matter what fan
modulation method is selected. The
FanMod program compares two or
more fans economically for one or
more years. FanMod is an easy-to-use
program for equipment life cycle cost
analysis.
When comparing the Q fan
performance with centrifugal fans,
remember to recalculate the fan
external static pressure. The in-line
delivery of the Q fan often eliminates
the need for a 90 degree turn right off
the fan outlet. Turns directly
downstream of the fan outlet consume
energy and generate noise and,
therefore, should be avoided whenever
possible.
Recommended Super Q II (NC40)
Plenum Configuration
Recommended Super Q II Multiple Fan (NC40)
Low Height Plenum Configuration
20
Application
Considerations
Q Fan Sound Data
Trane Q fans are designed to be used in
any installation where a standard airfoil
centrifugal fan can be used. The sound
level of the Q fan in the difficult to
attenuate lower frequencies is lower
than that produced by standard airfoil
centrifugal fans with the same capacity.
Sound levels in the higher octave
bands compare favorably. Therefore,
the Q fan will provide quieter sound
levels in a typical installation.
Designing the system for lower static
pressures and selecting the fan at high
efficiency will result in quieter fan
operation, as well as power savings.
The best method of acoustical design
makes use of unit sound power levels
in all eight octave bands. These sound
power levels for each Trane Q fan can
be obtained from the Trane
computerized fan selection program.
In the past, it has been an industry
practice to test air moving devices
within a reverberating room to
determine total sound power. This has
presented the problem of
distinguishing between inlet and
discharge sound power ratings, where
significant differences do exist.
Trane engineers solved this problem by
locating the fan adjacent to the
reverberating room and ducting to it.
By turning the fan around, inlet and
discharge sound power can be
measured separately and accurately.
By ducting both the inlet and outlet,
radiated shell sound power was
determined. Using this method with
the Trane reverberant room that
conforms to ASHRAE standards,
acoustical data on the Q fan is
substantially more accurate than fan
ratings made using conventional
techniques. Tests covered all sizes and
speeds over the entire performance
range of the line. A computer program
was then used to determine the precise
relationship of speed, size, point of
operation and frequency.
Plus silencer attenuation is shown in
Tables S-1 and S-2. Use the Trane fan
selection program to obtain precise
Plus attenuation with regenerated
noise included.
Trane ASA10B Sound Analyzer
Trane offers a low cost 10 octave
band sound analyzer for sound
measurements. Capable of measuring
noise from 30 to 123 db sound
pressure with flat, dbA and dbC sound
LCb weightings this rugged meter
permits comparative and absolute
sound measurements to be taken.
Ideas On How To Use The ASA10B
The ASA10B can be used on existing
jobs to measure equipment sound
levels by octave bands. Compare this
data with NC charts to determine what
frequencies need to be attenuated and
by how much. The type and cost of
noise control options is a function of
the problem
frequency and amplitude.
On acoustical retrofits, the ASA10B can
accurately compare before and after
noise levels. Real measurements
establish the benefit of the retrofit.
Trane Acoustics Program
Trane has a system level acoustics
computer program that accurately
converts fan sound power to room NC
levels. This program uses ASHRAE
approved algorithms and is the most
complete and accurate sound predictive
program in the HVAC industry. Use of
the Trane acoustics program allows all
sound paths to be checked and
attenuated to achieve the desired room
sound levels without costly
overdesigning. Contact your Trane sales
engineer for more details on this
Customer Direct Service (C.D.S.)
Network program.
Q Fan/Super Q II Plus Silencers
Trane has a unique silencer for the
Q fan. This low turbulence, high
attenuation silencer dramatically
reduces airborne noise from the Q-Fan.
A bulleted cylindrical silencer attenuates
medium and high frequency noise
generated by the Q Fan to a point where
the Q Fan can be successfully installed
in such sound sensitive applications as
ceiling plenums successfully.
Trane’s Plus silencer has a field
repositionable bullet (center body) that
can be relocated close to the Q Fan
outlet. This unique feature eliminates
low frequency turbulence and makes
the Q fan quieter than plug fans or other
axial or mixed flow fans. Pressure drop
through the Plus silencer is
approximately .1-inch sp. The Plus
silencer has been used on many
projects in the last five years to
consistently create NC 15-35 spaces.
Table A-5 — Inlet Vane Sound Data DB Addition For Vane Position Indicated
Octave Mid- Wide 75% 50% 25%
Band Frequency Open W/Open W/Open W/Open
1 63 +4 +8 +12 +14
2 125 +8 +9 +9 +10
3 200 +7 +8 +9 +9
4 500 +4 +5 +6 +6
5 1,000 0 0 0 0
6 2,000 0 0 0 0
7 4,000 0 0 0 0
8 8,000 0 0 0 0
21
Selection
Procedure
Q-Fan Sound Power By Octave Band At Nominal Cfm/SP
Fan Size 63 Hz 125 HZ 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
16 2 3 10 16 19 20 13 12
19 2 3 10 16 19 19 13 12
21 2 4 10 16 19 19 13 11
24 3 4 10 16 19 19 13 10
27 3 5 10 16 19 19 13 9
30 4 5 10 16 19 17 13 9
36 4 6 10 16 19 15 13 9
40 5 6 11 16 19 14 12 9
44 5 6 11 16 19 14 11 9
Table S-2 — Long Plus Silencer Attenuation (2D Length)*
Q-Fan Sound Power By Octave Band At Nominal Cfm/SP
Fan Size 63 Hz 125 HZ 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
16 3 6 19 32 37 39 26 24
19 3 6 19 32 37 37 26 24
21 4 7 19 32 37 37 26 22
24 5 8 19 32 37 37 26 20
27 6 9 19 32 37 37 26 18
30 7 9 20 32 37 34 26 18
36 8 11 20 32 37 30 25 18
40 9 11 21 32 37 28 23 18
44 9 12 21 32 37 28 22 18
*Approximate attenuations. Use the Trane Fan Selection Program for attenuation predictions that include silencer
regenerated self-noise.
NOTE: Super Q II not available with Class III fans.
9
If inlet vane modulation was selected,
increase the rpm by 1 percent and
increase the bhp by 3 percent.
10
If the air density ratio is nonstandard
(different than 1.00), the rpm is correct
and the bhp must be multiplied by the
air density ratio.
11
If the start-up air temperature is lower
than the normal operating
temperature, adjust the fan curve bhp
for the starting temperature. The next
larger nominal hp motor is the correct
motor size.
12
If exceptional quiet is desired, choose a
short or long Q fan plus duct silencer.
The plus silencer is a low turbulence,
low pressure drop, high attenuation
duct silencer. Subtract the attenuations
given in Tables S-1 and S-2 from the
Q fan/Super Q II fan sound power
projections. If silencer regenerated
noise is a concern, contact your local
Trane sales engineer for further
information.
Table S-1 — Short Plus Silencer Attenuation (1D Length)*
7
Input the selection parameters into the
Trane fan selection program and select
the desired Q fan or proceed with a
manual selection.
8
Manual Selection:
a
Determine the air density ratio if non-
standard air is being handled by the
Q fan.
b
Adjust the external sp by the air density
ratio.
c
Use the inlet and outlet area of the fan
to calculate the inlet and outlet
velocities. Use these velocities and the
inlet and outlet Kt to correct the
external static pressure to the right
value. Reselect the fan at the right
value.
d
From the performance table, select the
desired fan.
1
Select the type of fan desired. The
Super Q II should be used where fan
radiation noise needs to be attenuated.
2
Position the Q fan to deliver air to the
system and minimize adverse Kt effects.
Straight-thru flow arrangements are
best.
3
Select the desired Q fan or Super Q II
fan options.
4
Compute the fan external static pressure
and cfm requirements.
5
Determine which Kt effects apply to the
Q fan installation.
6
If the Q fan is serving a VAV system,
select AC frequency drive or inlet vane
modulations. (AC frequency drive
modulation is considerably quieter and
more efficient than Q fan inlet vanes.)
Super Q II fans use AC frequency drive
modulation only.
22
Performance
Data
Fan Size 16”
Wheel Dia. 16.5 inches 419 mm
Inlet Area 2.05 square feet 0.190 m2
Outlet Area 1.70 square feet 0.158 m2
Tip Speed 4.32 x RPM 1.317
ft./minute m/minute
Q Fan and
Super Q II
Size 16
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 486
1200 RPM 324
Pressure Class Limits
Class Maximum RPM
I 2585
II 3460
III 4660
Table P-1 — Size 16 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1000 588 934 0.08 1002 0.11 1068 0.13 1137 0.16 1204 0.19 1344 0.27
1200 705 1071 0.12 1127 0.14 1184 0.17 1239 0.20 1295 0.24 1408 0.31 1523 0.39 1642 0.48
1400 823 1214 0.16 1263 0.20 1311 0.231 1360 0.26 1408 0.29 1502 0.37 1601 0.45 1697 0.54 1796 0.64 1898 0.75
1600 941 1360 0.22 1404 0.26 1447 0.30 1489 0.33 1531 0.37 1617 0.45 1698 0.53 1785 0.62 1870 0.72 1953 0.82
1800 1058 1509 0.30 1548 0.34 1587 0.38 1626 0.42 1662 0.46 1739 0.54 1814 0.63 1886 0.73 1961 0.831 2039 0.93
2000 1176 1660 0.39 1695 0.43 1731 0.48 1766 0.52 1800 0.57 1867 0.65 1936 0.74 2004 0.84 2068 0.95 2135 1.06
2200 1294 1812 0.50 1844 0.54 1877 0.59 1909 0.64 1941 0.69 2002 0.78 2064 0.88 2127 0.99 2188 1.10 2249 1.21
2400 1411 1965 0.62 1995 0.68 2025 0.73 2054 0.78 2084 0.84 2142 0.94 2197 1.04 2254 1.15 2311 1.27 2369 1.38
2600 1529 2120 0.77 2147 0.83 2175 0.89 2202 0.94 2229 1.00 2283 1.12 2337 1.23 2387 1.34 2440 1.46 2493 1.58
2800 1647 2274 0.95 2300 1.01 2326 1.07 2351 1.13 2376 1.19 2427 1.32 2477 1.44 2526 1.57 2573 1.68 2622 1.81
3000 1764 2430 1.15 2454 1.21 2478 1.28 2501 1.34 2525 1.41 2573 1.54 2620 1.67 2666 1.81 2712 1.94 2755 2.06
3200 1882 2586 1.38 2608 1.44 2630 1.51 2653 1.58 2675 1.65 2720 1.79 2764 1.93 2808 2.08 2851 2.22 2894 2.36
3400 2000 2742 1.63 2763 1.70 2784 1.77 2805 1.85 2826 1.92 2868 2.07 2910 2.22 2951 2.37 2993 2.53 3033 2.68
3600 2117 2898 1.92 2918 1.99 2938 2.07 2958 2.15 2978 2.22 3018 2.38 3057 2.54 3096 2.70 3136 2.86 3174 3.02
3800 2235 3055 2.24 3074 2.32 3093 2.40 3112 2.48 3130 2.56 3168 2.72 3206 2.89 3243 3.06 3280 3.23 3317 3.40
4000 2352 3212 259 3230 2.68 3248 2.76 3266 2.84 3284 2.93 3319 3.10 3355 3.28 3391 3.45 3426 3.63 3461 3.81
4200 2470 3369 298 3386 3.07 3403 3.16 3420 3.25 3437 3.34 3471 3.52 3505 3.70 3539 3.88 3573 4.07 3607 4.25
4400 2588 3526 3.41 3543 3.50 3559 3.59 3575 3.69 3591 3.78 3624 3.97 3656 4.16 3689 4.35 3721 4.54 3754 4.74
4600 2705 3684 3.88 3699 3.98 3715 4.07 3730 4.17 3746 4.26 3777 4.46 3808 4.66 3839 4.86 3870 5.06 3901 5.26
4800 2823 3841 4.39 3856 4.49 3871 4.59 3886 4.69 3901 4.79 3931 5.00 3961 5.20 3990 5.41 4020 5.62 4050 5.83
5000 2941 3999 4.95 4013 5.05 4027 5.15 4042 5.26 4056 5.36 4085 5.57 4113 5.79 4142 6.00 4171 6.22 4199 6.44
5200 3058 4157 5.55 4170 5.65 4184 5.76 4198 5.87 4212 5.98 4239 6.20 4267 6.42 4294 6.64 4322 6.87 4349 7.09
5400 3176 4314 6.20 4328 6.31 4341 6.42 4354 6.53 4367 6.64 4394 6.87 4420 7.10 4447 7.33 4473 7.56 4500 7.80
5600 3294 4472 6.89 4485 7.01 4498 7.12 4511 7.24 4523 7.36 4549 7.59 4574 7.83 4600 8.06 4626 8.31 4651 8.55
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1600 941 2040 0.94 2129 1.06
1800 1058 2112 1.04 2188 1.16 2343 1.42 2482 1.66
2000 1176 2205 1.18 2274 1.30 2407 1.54 2546 1.82 2688 2.12
2200 1294 2307 1.33 2369 1.45 2495 1.71 2616 1.98 2741 2.28 2869 2.60 2999 2.94
2400 1411 2425 1.50 2478 1.63 2590 1.90 2705 2.18 2816 2.47 2930 2.78 3046 3.12 3164 3.48 3284 3.85
2600 1529 2546 1.71 2598 1.84 2698 2.11 2801 2.40 2908 2.71 3013 3.02 3114 3.34 3220 3.69 3328 4.07 3438 4.46
2800 1647 2671 1.94 2720 2.07 2817 2.35 2909 2.65 3005 2.97 3104 3.29 3203 3.62 3296 3.96 3393 4.32 3492 4.71
3000 1764 2801 2.20 2846 2.34 2938 2.62 3028 2.93 3114 3.25 3203 3.58 3296 3.92 3387 4.28 3479 4.65 3565 5.01
3200 1882 2935 2.49 2977 2.63 3063 2.93 3149 3.24 3233 3.57 3313 3.91 3396 4.26 3481 4.63 3569 5.00 3655 5.39
3400 2000 3074 2.83 3112 2.96 3192 3.27 3272 3.59 3353 3.92 3433 4.27 3507 4.63 3586 5.00 3665 5.39 3748 5.77
3600 2117 3213 3.18 3251 3.34 3324 3.64 3400 3.97 3477 4.31 3553 4.66 3628 5.03 3698 5.41 3772 5.81 3847 6.21
3800 2235 3354 3.57 3390 3.74 3460 4.05 3532 4.39 3604 4.74 3677 5.10 3748 5.47 3819 5.86 3889 6.26 3955 6.67
4000 2352 3497 3.99 3531 4.17 3601 4.52 3666 4.85 3734 5.21 3803 5.58 3872 5.96 3940 6.35 4008 6.76 4074 7.18
4200 247C 3641 4.44 3674 4.63 3740 5.01 3806 5.38 3868 5.72 3933 6.10 3998 6.50 4064 6.89 4129 7.30 4193 7.72
4400 2588 3786 4.94 3818 5.13 3881 5.53 3944 5.92 4004 6.27 4066 6.67 4128 7.07 4190 7.48 4253 7.89 4315 8.32
4600 2705 3932 5.47 3963 5.67 4024 6.09 4085 6.50 4144 6.91 4201 7.27 4260 7.68 4319 8.11 4379 8.54 4438 8.98
4800 2823 4079 6.04 4109 6.25 4168 6.68 4226 7.12 4284 7.55 4341 7.97 4395 8.35 4452 8.78 4508 9.22 4565 9.67
5000 2941 4228 6.66 4256 6.88 4313 7.33 4369 7.78 4425 8.22 4480 8.67 4535 9.11 4586 9.50 4641 9.95
5200 3058 4377 7.32 4404 7.55 4459 8.01 4513 8.48 4567 8.95 4620 9.41
5400 3176 4526 8.03 4553 8.27 4605 8.75 4658 9.23
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2600 1529 3548 4.86
2700 1588 3568 4.98 3674 5.40
2800 1647 3593 5.11 3694 5.53 3797 5.97
2900 1705 3622 5.25 3719 5.67 3817 6.11 3916 6.55 3980 6.85
3000 1764 3656 5.41 3749 5.82 3843 6.26 3937 6.71 4033 7.17 4091 7.45
3100 1823 3694 5.58 3783 5.99 3872 6.42 3963 6.87 4055 7.33 4147 7.80 4239 8.29
3200 1882 3740 5.78 3821 6.17 3906 6.59 3993 7.04 4081 7.50 4169 7.97 4259 8.46 4348 8.96 4400 9.24
3300 1941 3783 5.98 3866 6.39 3944 6.79 4027 7.23 4111 7.68 4196 8.16 4282 8.64 4368 9.14 4455 9.65 4501 9.92
3400 2000 3829 6.18 3909 6.60 3989 7.02 4065 7.43 4145 7.88 4227 8.35 4309 8.84 4392 9.33 4476 9.85 4560 10.37
3500 2058 3876 6.39 3954 6.81 4032 7.24 4106 7.65 4183 8.10 4261 8.56 4340 9.04 4420 9.54 4501 10.05 4582 10.57
3600 2117 3923 6.62 4001 7.04 4077 7.47 4153 7.91 4224 8.33 4299 8.79 4375 9.27 4452 9.76 4530 10.27 4608 10.79
3700 2176 3973 6.85 4049 7.27 4124 7.71 4198 8.15 4272 8.61 4340 9.04 4414 9.51 4487 10.00 4562 10.50 4637 11.02
3800 2235 4026 7.10 4097 7.53 4171 7.96 4244 8.41 4316 8.86 4388 9.33 4459 9.81 4526 10.26 4598 10.76
3900 2294 4081 7.35 4149 7.78 4219 8.23 4292 8.67 4362 9.13 4433 9.60 4503 10.08 4572 10.57 4637 11.03
4000 2352 4137 7.61 4203 8.05 4271 8.50 4339 8.95 4410 9.41 4478 9.88 4547 10.37 4615 10.86
4100 2411 4198 7.88 4259 8.32 4324 8.78 4390 9.24 4457 9.71 4526 10.17 4593 10.66 4660 11.16
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
23
Performance
Data Q Fan and
Super Q II
Size 16
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 16” Super Q Fan Size 16”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1 - 2 1.5 - 5 5 - 15 1 - 2 1.5 - 5
Arrangement 1 ——5 - 15 NA NA
____ Fan RPM Line
- - - Motor HP Line
24
Performance
Data Q Fan and
Super Q II
Size 19
Fan Size 19”
Wheel Dia. 19.0 inches 483 mm
Inlet Area 2.61 square feet 0.242 m2
Outlet Area 2.30 square feet 0.214 m2
Tip Speed 4.97 x RPM 1.515
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 417
1200 RPM 278
Pressure Class Limits
Class Maximum RPM
I 2345
II 3145
III 4040
Table P-2 — Size 19 Q Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2000 869 907 0.15 962 0.19 1019 0.24 1074 0.29 1124 0.34 1235 0.45 1351 0.57
2200 956 977 0.18 1026 0.23 1078 0.28 1129 0.33 1179 0.38 1272 0.49 1375 0.62 1481 0.75
2400 1043 1049 0.22 1093 0.27 1140 0.32 1187 0.37 1234 0.43 1325 0.55 1409 0.67 1505 0.81 1602 0.95
2600 1130 1123 0.26 1163 0.31 1205 0.36 1248 0.42 1292 0.48 1378 0.60 1456 0.73 1538 0.87 1627 1.02 1717 118
2800 1217 1198 0.31 1234 0.36 1272 0.42 1312 0.48 1352 0.54 1433 0.67 1512 0.80 1583 0.94 1660 1.09 1742 126
3000 1304 1273 0.36 1307 0.42 1342 0.48 1378 0.54 1415 0.60 1491 0.74 1566 0.88 1638 1.03 1704 1.17 1775 133
3200 1391 1350 0.42 1381 0.48 1413 0.54 1446 0.61 1481 0.67 1551 0.82 1622 0.97 1692 1.12 1759 1.27 1820 142
3400 1478 1427 0.49 1456 0.55 1486 0.62 1517 0.69 1548 0.75 1614 0.90 1681 1.06 1747 1.22 1812 1.38 1875 1.55
3600 1565 1504 0.57 1531 0.64 1559 0.70 1588 0.77 1617 0.84 1679 0.99 1741 1.15 1804 1.32 1867 1.49 1928 166
3800 1652 1582 0.66 1608 0.72 1634 0.79 1661 0.86 1688 0.94 1745 1.09 1804 1.26 1864 1.43 1923 1.61 1982 1.79
4000 1739 1660 0.75 1684 0.82 1709 0.89 1734 0.97 1760 1.04 1813 1.20 1868 1.37 1925 1.55 1982 1.74 2038 193
4200 1826 1738 0.86 1761 0.93 1785 1.00 1809 1.08 1833 1.16 1883 1.32 1934 1.50 1988 1.68 2042 1.87 2096 2.07
4400 1913 1817 0.97 1839 1.04 1861 1.12 1884 1.20 1907 1.28 1954 1.45 2002 1.63 2053 1.82 2104 2.01 2156 2.21
4600 1999 1896 1.09 1916 1.17 1938 1.25 1959 1.33 1981 1.42 2026 1.59 2071 1.78 2119 1.97 2168 2.16 2216 2.37
4800 2086 1974 1.23 1994 1.31 2015 1.39 2035 1.48 2056 1.56 2098 1.74 2142 1.93 2186 2.13 2233 2.33 2279 2.54
5000 2173 2053 1.37 2073 1.46 2092 1.54 2111 1.63 2131 1.72 2172 1.91 2213 2.10 2256 2.30 2299 2.51 2344 2.72
5200 2260 2133 1.53 2151 1.62 2169 1.71 2188 1.80 2207 1.89 2246 2.08 2285 2.28 2326 2.48 2367 2.69 2410 291
5400 2347 2212 1.70 2229 1.79 2247 1.88 2265 1.98 2283 2.07 2320 2.27 2358 2.47 2397 2.68 2436 2.90 2476 312
5600 2434 2291 1.88 2308 1.98 2325 2.07 2343 2.17 2360 2.26 2396 2.47 2432 2.67 2469 2.89 2506 3.11 2544 3.34
5800 2521 2371 2.08 2387 2.17 2404 2.27 2420 2.37 2437 2.47 2471 2.68 2506 2.89 2541 3.11 2577 3.34 2614 3.57
6000 2608 2450 2.29 2466 2.39 2482 2.49 2498 2.59 2514 2.69 2547 2.90 2580 3.12 2614 3.35 2649 3.58 2684 3.82
6200 2695 2530 2.51 2545 2.61 2560 2.72 2576 2.82 2592 2.93 2623 3.14 2655 3.37 2688 3.60 2721 3.83 2755 4.08
6400 2782 2610 2.75 2624 2.85 2639 2.96 2654 3.07 2669 3.18 2700 3.40 2731 3.63 2762 3.86 2794 4.10 2826 4.35
6600 2869 2689 3.00 2704 3.11 2718 3.22 2732 3.33 2747 3.44 2777 3.67 2806 3.90 2837 4.14 2868 4.39 2899 4.64
CFM Out- Total Static Pressure
Std. let 2
1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2800 1217 1826 1.42 1908 160
3000 1304 1853 1.52 1930 170
3200 1391 1887 1.60 1959 1.79 2105 2.17
3400 1478 1931 1.70 1994 1.89 2130 2.30 2267 2.70
3600 1565 1987 1.84 2040 2.01 2162 2.41 2290 2.85 2419 3.28
3800 1652 2040 1.97 2096 2.16 2201 2.53 2320 2.98 2442 3.44 2564 3.90
4000 1739 2094 2.11 2149 2.31 2249 2.68 2355 3.11 2470 3.59 2587 4.06 2702 4.56
4200 1826 2150 2.27 2203 2.46 2306 2.87 2399 3.27 2503 3.73 2614 4.25 2725 4.74 2835 5.26
4400 1913 2207 2.42 2259 2.63 2359 3.05 2449 3.46 2544 3.91 2647 4.42 2751 4.95 2858 5.46 2962 6.01
4600 1999 2266 2.58 2316 2.80 2413 3.23 2507 3.68 2592 4.11 2684 4.59 2783 5.14 2883 5.70 2985 6.23 3085 6.80
4800 2086 2327 2.76 2374 2.98 2469 3.44 2561 3.89 2649 4.36 2729 4.81 2819 5.32 2915 5.91 3011 6.49 3108 7.04
5000 2173 2389 2.94 2434 3.17 2525 3.64 2615 4.11 2702 4.60 2786 5.08 2863 5.56 2949 6.10 3042 6.72 3134 7.32
5200 2260 2453 3.14 2496 3.37 2584 3.85 2671 4.35 2756 4.84 2839 5.35 2912 5.82 2992 6.35 3076 6.92 3166 7.57
5400 2347 2518 3.35 2559 3.59 2644 4.08 2728 4.59 2811 5.11 2892 5.61 2971 6.14 3040 6.63 3118 7.19 3199 7.79
5600 2434 2584 3.57 2624 3.81 2704 4.31 2786 4.84 2867 5.37 2946 5.89 3024 6.44 3099 6.99 3166 7.49 3241 8.08
5800 2521 2651 3.81 2690 4.05 2767 4.56 2846 5.10 2924 5.64 3001 6.20 3078 6.74 3152 7.31 3224 7.87 3288 8.40
6000 2608 2720 4.06 2756 4.31 2831 4.83 2906 5.37 2982 5.93 3058 6.50 3132 7.06 3205 7.64 3277 8.22 3339 8.76
6200 2695 2789 4.33 2824 4.58 2896 5.11 2968 5.66 3042 6.23 3115 6.81 3188 7.40 3260 7.98 3330 8.58 3398 9.19
6400 2782 2859 4.61 2893 4.86 2962 5.40 3031 5.96 3102 6.54 3174 7.13 3245 7.74 3315 8.35 3384 8.95 3452 9.57
6600 2869 2930 4.90 2963 5.16 3028 5.71 3096 6.28 3164 6.86 3234 7.47 3303 8.09 3371 8.72 3439 9.35 3505 9.96
6800 2956 3002 5.21 3033 5.48 3096 6.03 3162 6.61 3227 7.21 3294 7.82 3362 8.45 3428 9.10 3494 9.75 3560 10.37
7000 3043 3075 5.54 3104 5.81 3165 6.38 3227 6.96 3292 7.56 3356 8.19 3422 8.83 3487 9.49 3551 10.15 3615 10.82
7200 3130 3147 5.88 3176 6.16 3235 6.73 3295 7.33 3357 7.94 3419 8.57 3482 9.22 3546 9.89 3609 10.57 3672 11.26
7400 3217 3221 6.24 3249 6.53 3305 7.11 3363 7.71 3423 8.33 3483 8.97 3544 9.63 3605 10.31 3668 11.00 3729 11.70
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4800 2086 3205 7.63
5000 2173 3227 7.93 3321 8.50 3412 9.15
5200 2260 3254 8.20 3343 8.83 3434 9.42 3522 10.08
5400 2347 3286 8.46 3371 9.12 3457 9.77 3544 10.38 3629 11.06
5600 2434 3319 8.70 3403 9.40 3485 10.08 3567 10.76 3652 11.38 3734 12.08 3816 12.80
5800 2521 3361 9.01 3436 9.65 3517 10.38 3596 11.08 3676 11.78 3758 12.43 3838 13.14 3916 13.88
6000 2608 3407 9.35 3478 9.98 3551 10.65 3629 11.41 3706 12.13 3782 12.85 3860 13.58 3939 14.24
6200 2695. 3458 9.73 3524 10.35 3593 11.00 3663 11.69 3739 12.47 3813 13.22 3887 13.97 3962 14.72
6400 2782 3518 10.20 3575 10.76 3639 11.40 3705 12.07 3773 12.78 3847 13.58 3918 14.35
6600 2869 3571 10.61 3635 11.26 3689 11.83 3752 12.49 3816 13.18 3882 13.91 3953 14.73
6800 2956 3625 11.03 3688 11.69 3750 12.36 3802 12.95 3863 13.63 3925 14.34
7000 3043 3679 11.47 3741 12.14 3803 12.83 3862 13.52 3913 14.11 3972 14.81
7200 3130 3734 11.95 3796 12.61 3856 13.31 3916 14.01 3974 14.72
7400 3217 3790 12.41 3850 13.12 3910 13.80 3969 14.52
7600 3304 3847 12.89 3906 13.62 3965 14.31
7800 3391 3905 13.38 3963 14.12 4020 14.87
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
25
Performance
Data Q Fan and
Super Q II
Size 19
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 19” Super Q Fan Size 19”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1 - 3 3 - 7.5 7.5 - 15 1 - 3 3 - 7.5
Arrangement 1 ——7.5 - 15 NA NA
____ Fan RPM Line
- - - Motor HP Line
26
Fan Size 21”
Wheel Dia. 21.5 inches 546 mm
Inlet Area 3.31 square feet 0.308 m2
Outlet Area 2.88 square feet 0.268 m2
Tip Speed 5.63 x RPM 1.716
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 380
1200 RPM 253
Performance
Data Q Fan and
Super Q II
Size 21
Pressure Class Limits
Class Maximum RPM
I 2070
II 2780
III 3740
Table P-3 — Size 21 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2600 902 810 0.20 859 0.25 908 0.31 957 0.38 1001 0.44 1096 0.58 1197 0.74
2800 972 859 0.23 903 0.29 949 0.35 995 0.42 1039 0.48 1121 0.62 1214 0.79 1308 0.96
3000 1041 909 0.26 949 0.33 991 0.39 1034 0.46 1077 0.53 1155 0.67 1236 0.83 1323 1.02 1411 1.20
3200 1111 959 0.30 996 0.37 1035 0.44 1075 0.51 1116 0.58 1194 0.74 1265 0.89 1344 1.07 1426 1.27 1507 1.46
3400 1180 1011 0.35 1045 0.41 1081 0.48 1118 0.56 1156 0.64 1231 0.80 1302 0.96 1369 1.13 1445 1.34 1523 1.53
3600 1250 1062 0.40 1094 0.47 1128 0.54 1163 0.61 1198 0.70 1270 0.86 1339 1.04 1401 1.21 1469 1.40 1541 1.62
3800 1319 1115 0.45 1145 0.52 1176 0.60 1208 0.68 1242 0.76 1309 0.93 1376 1.11 1440 1.30 1499 1.48 1564 1.69
4000 1388 1167 0.51 1196 0.59 1225 0.66 1255 0.74 1286 0.83 1350 1.01 1415 1.20 1477 1.39 1537 1.58 1592 1.78
4200 1458 1220 0.58 1247 0.65 1274 0.73 1303 0.82 1332 0.90 1393 1.09 1454 1.28 1515 1.48 1573 1.68 1626 1.88
4400 1527 1273 0.65 1299 0.73 1325 0.81 1352 0.90 1379 0.99 1436 1.17 1495 1.37 1553 1.58 1610 1.79 1665 2.01
4600 1597 1327 0.73 1351 0.81 1376 0.89 1401 0.98 1427 1.07 1481 1.27 1536 1.47 1593 1.69 1648 1.91 1702 2.12
4800 1666 1380 0.81 1403 0.90 1427 0.98 1451 1.07 1476 1.17 1527 1.37 1580 1.58 1633 1.80 1687 2.02 1739 2.25
5000 1736 1434 0.90 1456 0.99 1479 1.08 1502 1.17 1525 1.27 1573 1.47 1624 1.69 1675 1.91 1727 2.15 1778 2.38
5200 1805 1488 1.00 1509 1.09 1531 1.18 1553 1.28 1575 1.38 1621 1.59 1669 1.80 1718 2.03 1767 2.27 1817 2.52
5400 1875 1542 1.11 1562 1.20 1583 1.30 1604 1.39 1625 1.50 1669 1.71 1715 1.93 1762 2.16 1809 2.41 1857 2.66
5600 1944 1596 1.22 1616 1.32 1636 1.41 1656 1.52 1676 1.62 1718 1.84 1761 2.06 1806 2.30 1852 2.55 1898 2.81
5800 2013 1651 1.34 1669 1.44 1688 1.54 1708 1.65 1727 1.75 1768 1.97 1809 2.21 1852 2.45 1895 2.70 1940 296
6000 2083 1705 1.47 1723 1.57 1741 1.68 1760 1.78 1779 1.89 1817 2.12 1857 2.36 1898 2.60 1940 2.86 1982 3.13
6200 2152 1759 1.61 1777 1.71 1795 1.82 1813 1.93 1831 2.04 1868 2.27 1906 2.52 1945 2.77 1986 3.03 2026 3.30
6400 2222 1814 1.76 1831 1.86 1848 1.97 1865 2.09 1883 2.20 1919 2.44 1955 2.68 1993 2.94 2031 3.21 2071 3.48
6600 2291 1869 1.91 1885 2.02 1902 2.14 1918 2.25 1935 2.37 1970 2.61 2005 2.86 2041 3.12 2078 3.39 2116 3.67
6800 2361 1923 2.08 1939 2.19 1955 2.31 1971 2.43 1988 2.55 2021 2.79 2055 3.05 2090 3.32 2125 3.59 2162 3.87
7000 2430 1978 2.25 1993 2.37 2009 2.49 2025 2.61 2041 2.73 2073 2.99 2106 3.25 2139 3.52 2173 3.80 2208 4.09
7200 2500 2033 2.44 2048 2.56 2063 2.68 2078 2.80 2093 2.93 2125 3.19 2156 3.45 2189 3.73 2222 4.01 2256 4.31
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3600 1250 1615 1.83 1687 2.06
3800 1319 1633 1.92 1703 2.14
4000 1388 1656 2.01 1721 2.25 1852 2.73
4200 1458 1682 2.10 1743 2.35 1868 2.85
4400 1527 1715 2.21 1769 2.44 1887 2.97 2007 3.49
4600 1597 1754 2.35 1801 2.56 1910 3.08 2023 3.64 2137 4.19
4800 1666 1791 2.48 1840 2.72 1935 3.19 2043 3.77 2153 4.33 2261 4.94
5000 1736 1828 2.62 1877 2.86 1966 3.34 2067 3.91 2170 4.51 2276 5.09
5200 1805 1866 2.77 1914 3.01 2001 3.50 2092 4.04 2192 4.66 2292 5.29 2394 5.90
5400 1875 1904 2.92 1951 3.17 2042 3.69 2124 4.20 2215 4.80 2312 5.46 2410 6.09 2507 6.76
5600 1944 1944 3.07 1989 3.34 2078 3.87 2158 4.39 2243 4.97 2335 5.63 2428 6.31 2522 6.96 2615 7.66
5800 2013 1984 3.23 2029 3.51 2116 4.06 2199 4.62 2275 5.16 2359 5.79 2449 6.50 2539 7.20 2631 7.87 2720 8.61
6000 2083 2026 3.40 2069 3.68 2153 4.26 2236 4.83 2310 5.38 2388 5.99 2471 6.66 2559 7.41 2646 8.14 2735 8.83
6200 2152 2067 3.58 2109 3.87 2192 4.46 2273 5.04 2351 5.65 2421 6.22 2499 6.88 2582 7.62 2666 8.37 2751 9.12
6400 2222 2111 3.77 2151 4.06 2231 4.66 2311 5.26 2388 5.88 2461 6.51 2529 7.11 2606 7.81 2688 8.60 2769 9.37
6600 2291 2154 3.96 2193 4.26 2272 4.87 2349 5.50 2425 6.12 2498 6.77 2563 7.37 2635 8.05 2710 8.79 2791 9.62
6800 2361 2199 4.17 2236 4.47 2312 5.09 2388 5.74 2462 6.37 2535 7.03 2604 7.70 2667 8.33 2738 9.05 2815 9.87
7000 2430 2244 4.38 2281 4.69 2354 5.32 2428 5.98 2500 6.65 2572 7.31 2641 7.99 2702 8.62 2769 9.33 2839 10.09
7200 2500 2290 4.61 2325 4.92 2396 5.56 2468 6.23 2539 6.91 2609 7.59 2678 8.29 2744 8.99 2803 9.64 2869 10.39
7400 2569 2336 4.85 2371 5.16 2439 5.81 2509 6.49 2579 7.19 2647 7.90 2715 8.59 2780 9.31 2844 10.04 2901 10.71
7600 2638 2384 5.09 2416 5.41 2483 6.07 2550 6.76 2619 7.47 2686 8.20 2752 8.90 2817 9.64 2880 10.38 2936 11.06
7800 2708 2431 5.35 2463 5.67 2528 6.34 2593 7.04 2659 7.76 2725 8.50 2790 9.25 2855 9.98 2917 10.74 2978 11.50
8000 2777 2479 5.62 2510 5.95 2573 6.63 2636 7.33 2701 8.06 2765 8.82 2829 9.58 2892 10.32 2954 11.10 3014 11.88
8200 2847 2528 5.90 2558 6.24 2619 6.92 2680 7.64 2742 8.38 2806 9.14 2868 9.92 2930 10.71 2991 11.47 3051 12.26
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6000 2083 2821 9.60
6200 2152 2836 9.84 2919 10.64
6400 2222 2851 10.15 2934 10.89 3015 11.71
6600 2291 2870 10.42 2951 11.16 3030 11.98 3108 12.83
6800 2361 2891 10.68 2967 11.51 3046 12.27 3123 13.11 3199 13.99
7000 2430 2914 10.95 2988 11.79 3063 12.64 3139 13.43 3214 14.29
7200 2500 2937 11.18 3011 12.08 3083 12.95 3155 13.82 3230 14.62
7400 2569 2966 11.49 3033 12.32 3105 13.25 3175 14.15
7600 2638 2997 11.83 3061 12.64 3127 13.50 3197 14.47
7800 2708 3031 12.19 3092 12.99 3154 13.84 3222 14.80
8000 2777 3073 12.66 3125 13.37 3184 14.21
8200 2847 3110 13.07 3160 13.78 3217 14.60
8400 2916 3146 13.48 3203 14.30
8600 2986 3183 13.90 3239 14.74
8800 3055 3220 14.32
9000 3125 3258 14.76
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
27
Performance
Data Q Fan and
Super Q II
Size 21
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 21” Super Q Fan Size 21”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1 - 5 3 - 10 10 - 15 1 - 5 3 - 10
Arrangement 1 ——10 - 15 NA NA
____ Fan RPM Line
- - - Motor HP Line
28
Fan Size 24”
Wheel Dia. 24.5 inches 622 mm
Inlet Area 4.32 square feet 0.401 m2
Outlet Area 3.73 square feet 0.347 m2
Tip Speed 6.41 x RPM 1.954
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 535
1200 RPM 356
Performance
Data Q Fan and
Super Q II
Size 24
Pressure Class Limits
Class Maximum RPM
I 1772
II 2380
III 3200
Table P-4 — Size 24 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
•Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3000 804 639 0.2 685 0.3 730 0.3 773 0.4 817 0.5 908 0.7
3400 911 703 0.3 741 0.3 782 0.4 822 0.5 861 0.6 937 0.7 1018 0.9
3800 1018 769 0.3 803 0.4 837 0.5 874 0.6 910 0.7 978 0.8 1048 1.0 1120 1.3
4200 1126 836 0.4 867 0.5 897 0.6 929 0.7 962 0.8 1027 1.0 1088 1.2 1151 1.4 1215 1.6 1282 1.9
4600 1233 905 0.5 933 0.6 961 0.7 989 0.8 1018 0.9 1078 1.1 1136 1.3 1192 1.5 1249 1.8 1308 2.0
5000 1340 974 0.6 1000 0.7 1026 0.8 1052 0.9 1077 1.0 1132 1.2 1186 1.4 1240 1.7 1291 1.9 1344 2.2
5400 1447 1044 0.7 1068 0.8 1092 0.9 1116 1.0 1139 1.2 1188 1.4 1239 1.6 1290 1.9 1340 2.1 1387 2.4
5800 1554 1114 0.9 1137 1.0 1159 1.1 1181 1.2 1204 1.3 1248 1.6 1295 1.8 1342 2.1 1389 2.3 1435 2.6
6200 1662 1185 1.0 1206 1.2 1227 1.3 1248 1.4 1269 1.5 1310 1.8 1352 2.0 1397 2.3 1441 2.5 1485 2.8
6600 1769 1256 1.2 1276 1.3 1296 1.5 1315 1.6 1335 1.7 1374 2.0 1413 2.2 1453 2.5 1495 2.8 1537 3.1
7000 1876 1328 1.4 1346 1.6 1365 1.7 1383 1.8 1402 1.9 1439 2.2 1475 2.5 1512 2.8 1551 3.1 1591 3.4
7400 1983 1399 1.7 1417 1.8 1434 1.9 1452 2.1 1470 2.2 1505 2.5 1540 2.8 1574 3.1 1609 3.4 1646 3.7
7800 2091 1471 1.9 1488 2.1 1505 2.2 1521 2.3 1538 2.5 1571 2.8 1605 3.1 1638 3.4 1670 3.7 1704 4.0
8200 2198 1544 2.2 1559 2.3 1575 2.5 1591 2.6 1607 2.8 1639 3.1 1670 3.4 1702 3.7 1732 4.1 1764 4.4
8600 2305 1616 2.5 1631 2.7 1646 2.8 1661 3.0 1676 3.1 1706 3.4 1737 3.8 1767 4.1 1797 4.5 1826 4.8
9000 2412 1688 2.8 1703 3.0 1717 3.2 1731 3.3 1746 3.5 1775 3.8 1804 4.2 1833 4.5 1861 4.9 1890 5.2
9400 2520 1761 3.2 1775 3.4 1788 3.5 1802 3.7 1816 3.9 1844 4.2 1871 4.6 1899 4.9 1927 5.3 1954 5.7
9800 2627 1833 3.6 1847 3.8 1860 4.0 1873 4.1 1886 4.3 1913 4.7 1939 5.0 1966 5.4 1992 5.8 2019 6.2
10200 2734 1906 4.0 1919 4.2 1932 4.4 1944 4.6 1957 4.8 1982 5.1 2008 5.5 2033 5.9 2059 6.3 2084 6.7
10600 2841 1979 4.5 1991 4.7 2003 4.9 2016 5.1 2028 5.2 2052 5.6 2077 6.0 2101 6.4 2126 6.8 2150 7.2
11000 2949 2052 5.0 2064 5.2 2075 5.4 2087 5.6 2099 5.8 2122 6.2 2146 6.6 2170 7.0 2193 7.4 2217 7.8
11400 3056 2125 5.6 2136 5.7 2147 5.9 2159 6.1 2170 6.3 2193 6.7 2216 7.2 2238 7.6 2261 8.0 2284 8.4
11800 3163 2198 6.1 2209 6.3 2220 6.5 2231 6.7 2242 6.9 2264 7.4 2286 7.8 2308 8.2 2330 8.7 2352 9.1
12200 3270 2271 6.7 2281 7.0 2292 7.2 2303 7.4 2313 7.6 2334 8.0 2356 8.4 2377 8.9 2398 9.3 2420 9.8
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5000 1340 1397 2.5 1451 2.8
5400 1447 1435 2.7 1484 3.0 1585 3.6
5800 1554 1479 2.9 1524 3.2 1615 3.8 1710 4.5 1806 5.2
6200 1662 1528 3.1 1571 3.4 1654 4.1 1739 4.8 1828 5.5 1918 6.3
6600 1769 1578 3.4 1619 3.7 1697 4.4 1776 5.1 1857 5.8 1940 6.6 2025 7.4
7000 1876 1630 3.7 1669 4.0 1745 4.7 1818 5.4 1894 6.1 1969 6.9 2048 7.7 2128 8.6
7400 1983 1684 4.0 1721 4.3 1794 5.0 1866 5.8 1935 6.5 2006 7.3 2078 8.1 2152 9.0 2227 9.9 2303 10.8
7800 2091 1740 4.4 1775 4.7 1845 5.4 1914 6.2 1980 6.9 2047 7.7 2114 8.5 2182 9.4 2252 10.3 2324 11.2
8200 2198 1797 4.7 1831 5.1 1898 5.8 1964 6.6 2029 7.4 2091 8.1 2155 9.0 2220 9.9 2284 10.8 2350 11.7
8600 2305 1856 5.1 1887 5.5 1952 6.2 2016 7.0 2079 7.8 2141 8.7 2200 9.5 2260 10.4 2322 11.3 2383 12.2
9000 2412 1918 5.6 1947 5.9 2008 6.7 2069 7.5 2130 8.3 2190 9.2 2249 10.1 2305 10.9 2363 11.8 2421 12.8
9400 2520 1980 6.0 2008 6.4 2064 7.2 2124 8.0 2182 8.8 2240 9.7 2297 10.6 2354 11.6 2407 12.4 2463 13.4
9800 2627 2045 6.6 2070 6.9 2124 7.7 2179 8.6 2236 9.4 2292 10.3 2347 11.2 2402 12.2 2456 13.1 2507 14.1
10200 2734 2110 7.1 2135 7.5 2185 8.3 2237 9.2 2292 10.0 2345 10.9 2399 11.9 2452 12.8 2505 13.8 2557 14.8
10600 2841 2175 7.6 2199 8.1 2247 8.9 2296 9.8 2347 10.7 2400 11.6 2452 12.5 2503 13.5 2554 14.5 2605 15.5
11000 2949 2241 8.2 2264 8.7 2311 9.6 2357 10.4 2405 11.3 2456 12.3 2506 13.2 2556 14.2 2606 15.2 2655 16.3
11400 3056 2307 8.9 2330 9.3 2375 10.2 2419 11.1 2465 12.1 2512 13.0 2562 14.0 2610 15.0 2658 16.0 2705 17.1
11800 3163 2374 9.6 2396 10.0 2440 10.9 2483 11.9 2526 12.8 2571 13.8 2617 14.8 2665 15.8 2711 16.8 2758 17.9
12200 3270 2441 10.3 2462 10.7 2505 11.7 2547 12.7 2588 13.6 2631 14.6 2675 15.6 2721 16.6 2766 17.7 2811 18.8
12600 3378 2509 11.0 2529 11.5 2571 12.5 2612 13.5 2651 14.5 2692 15.5 2734 16.5 2777 17.6 2822 18.6 2865 19.7
13000 3485 2577 11.8 2597 12.3 2637 13.3 2677 14.3 2716 15.4 2754 16.4 2795 17.5 2835 18.5 2877 19.6 2921 20.7
13400 3592 2645 12.7 2664 13.2 2703 14.2 2742 15.2 2781 16.3 2819 17.4 2856 18.4 2895 19.5 2935 20.7 2976 21.8
13800 3699 2714 13.5 2733 14.1 2770 15.1 2808 16.2 2845 17.3 2883 18.4 2919 19.5 2956 20.6 2995 21.7 3033 22.9
14200 3806 2783 14.5 2801 15.0 2838 16.1 2874 17.2 2911 18.3 2947 19.4 2984 20.6 3018 21.7 3055 22.8 3092 24.0
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8600 2305 2446 13.2 2510 14.3 2575 15.3 2640 16.4
9000 2412 2480 13.8 2539 14.8 2600 15.9 2662 16.9 2724 18.0 2787 19.2
9400 2520 2519 14.4 2574 15.4 2631 16.5 2689 17.6 2748 18.7 2808 19.8 2867 21.0 2927 22.2
9800 2627 2561 15.1 2614 16.1 2667 17.2 2722 18.3 2777 19.4 2833 20.5 2890 21.6 2947 22.9 3004 24.1
10200 2734 2605 15.8 2657 16.8 2708 17.9 2760 19.0 2811 20.1 2864 21.3 2917 22.5 2971 23.7 3026 24.8 3081 26.1
10600 2841 2655 16.6 2702 17.6 2751 18.6 2800 19.7 2850 20.9 2899 22.0 2950 23.2 3001 24.5 3052 25.7 3104 27.0
11000 2949 2703 17.4 2752 18.5 2796 19.5 2844 20.6 2891 21.7 2939 22.9 2986 24.1 3035 25.3 3084 26.6 3133 27.8
11400 3056 2753 18.2 2800 19.3 2846 20.4 2890 21.5 2935 22.6 2981 23.8 3027 25.0 3074 26.2 3119 27.4 3166 28.7
11800 3163 2804 19.0 2849 20.2 2895 21.3 2940 22.5 2984 23.6 3026 24.7 3070 25.9 3114 27.2 3159 28.4
12200 3270 2856 19.9 2900 21.1 2945 22.2 2989 23.4 3032 24.6 3075 25.8 3115 26.9 3158 28.2
12600 3378 2909 20.9 2952 22.0 2995 23.2 3038 24.4 3081 25.7 3123 26.9 3165 28.1
13000 3485 2963 21.9 3005 23.0 3047 24.2 3089 25.5 3131 26.7 3172 28.0
13400 3592 3018 22.9 3059 24.1 3100 25.3 3141 26.5 3182 27.8
13800 3699 3073 24.1 3115 25.2 3154 26.4 3194 27.7
14200 3806 3130 25.2 3171 26.4
14600 3914 3189 26.4
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
29
Performance
Data Q Fan and
Super Q II
Size 24
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 24” Super Q Fan Size 24”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1 - 5 5 - 15 15-30 1 - 5 5 - 10
Arrangement 1 ——15 - 30 NA NA
____ Fan RPM Line
- - - Motor HP Line
30
Fan Size 27”
Wheel Dia. 27.0 inches 686 mm
Inlet Area 5.20 square feet 0.483 m2
Outlet Area 4.54 square feet 0.422 m2
Tip Speed 7.07 x RPM 2.155
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 437
1200 RPM 291
Performance
Data Q Fan and
Super Q II
Size 27
Pressure Class Limits
Class Maximum RPM
I 1610
II 2160
III 2908
Table P-5 — Size 27 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3000 660 510 0.2 559 0.3 607 0.3 657 0.4
3500 770 564 0.2 607 0.3 649 0.4 690 0.5 731 0.6
4000 881 623 0.3 658 0.4 697 0.5 734 0.6 769 0.7 842 0.9 918 1.1
4500 991 684 0.4 715 0.5 747 0.6 781 0.7 815 0.8 878 1.0 943 1.2 1011 1.5
5000 1101 746 0.5 775 0.6 803 0.7 832 0.8 863 0.9 923 1.1 979 1.4 1038 1.6 1098 1.9 1160 2.2
5500 1211 810 0.6 836 0.7 862 0.8 887 0.9 914 1.0 970 1.3 1023 1.5 1075 1.8 1127 2.1 1182 2.4
6000 1321 874 0.7 898 0.8 922 1.0 945 1.1 969 1.2 1020 1.4 1070 1.7 1119 2.0 1166 2.3 1214 2.6
6500 1431 939 0.9 961 1.0 983 1.1 1005 1.2 1027 1.4 1072 1.6 1119 1.9 1165 2.2 1210 2.5 1253 2.9
7000 1541 1005 1.1 1026 1.2 1046 1.3 1067 1.4 1087 1.6 1127 1.9 1170 2.2 1214 2.5 1256 2.8 1298 3.1
7500 1651 1071 1.3 1090 1.4 1109 1.5 1129 1.7 1148 1.8 1185 2.1 1224 2.4 1264 2.7 1305 3.1 1345 3.4
8000 1762 1138 1.5 1156 1.6 1174 1.8 1191 1.9 1209 2.1 1245 2.4 1280 2.7 1317 3.0 1355 3.4 1393 3.7
8500 1872 1205 1.7 1221 1.9 1238 2.0 1255 2.2 1272 2.4 1306 2.7 1338 3.0 1372 3.4 1407 3.7 1443 4.1
9000 1982 1272 2.0 1287 2.2 1303 2.4 1319 2.5 1335 2.7 1367 3.0 1399 3.4 1430 3.7 1462 4.1 1495 4.5
9500 2092 1339 2.4 1354 2.5 1369 2.7 1384 2.9 1399 3.0 1429 3.4 1459 3.8 1489 4.1 1518 4.5 1549 4.9
10000 2202 1406 2.7 1420 2.9 1435 3.1 1449 3.2 1463 3.4 1492 3.8 1521 4.2 1549 4.6 1577 5.0 1605 5.4
10500 2312 1474 3.1 1487 3.3 1501 3.5 1515 3.6 1528 3.8 1555 4.2 1583 4.6 1610 5.0 1637 5.5 1663 5.9
11000 2422 1541 3.5 1554 3.7 1567 3.9 1580 4.1 1593 4.3 1619 4.7 1645 5.1 1671 5.5 1697 6.0 1723 6.4
11500 2533 1609 4.0 1622 4.2 1634 4.4 1646 4.6 1659 4.8 1684 5.2 1709 5.6 1734 6.1 1758 6.5 1783 7.0
12000 2643 1677 4.5 1689 4.7 1701 4.9 1713 5.1 1725 5.3 1748 5.8 1772 6.2 1796 6.7 1820 7.1 1844 7.6
12500 2753 1745 5.0 1756 5.3 1768 5.5 1779 5.7 1791 5.9 1813 6.4 1836 6.8 1859 7.3 1882 7.8 1905 8.3
13000 2863 1813 5.6 1824 5.9 1835 6.1 1846 6.3 1857 6.5 1879 7.0 1901 7.5 1923 8.0 1945 8.5 1967 9.0
13500 2973 1881 6.3 1892 6.5 1902 6.7 1913 7.0 1923 7.2 1944 7.7 1966 8.2 1987 8.7 2008 9.2 2029 9.7
14000 3083 1949 7.0 1959 7.2 1969 7.4 1980 7.7 1990 7.9 2010 8.4 2031 8.9 2051 9.4 2072 10.0 2092 10.5
14500 3193 2017 7.7 2027 7.9 2037 8.2 2047 8.4 2057 8.7 2076 9.2 2096 9.7 2116 10.3 2136 10.8 2155 11.3
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6000 1321 1263 3.0 1313 3.3
6500 1431 1298 3.2 1342 3.6 1435 4.3
7000 1541 1338 3.5 1380 3.8 1463 4.6 1549 5.4
7500 1651 1384 3.8 1421 4.1 1498 4.9 1576 5.8 1657 6.6 1740 7.6
8000 1762 1430 4.1 1467 4.5 1538 5.3 1611 6.1 1684 7.0 1760 7.9 1837 9.0
8500 1872 1479 4.5 1514 4.9 1584 5.7 1650 6.5 1718 7.4 1787 8.4 1858 9.4 1931 10.4
9000 1982 1529 4.9 1563 5.3 1629 6.1 1694 7.0 1757 7.9 1821 8.9 1886 9.9 1953 10.9 2021 12.0 2090 13.2
9500 2092 1581 5.3 1613 5.7 1677 6.6 1739 7.5 1799 8.4 1859 9.4 1921 10.4 1982 11.5 2045 12.6 2110 13.7
10000 2202 1635 5.8 1665 6.2 1726 7.1 1786 3.0 1845 9.0 1901 9.9 1959 11.0 2017 12.0 2075 13.2 2135 14.3
10500 2312 1691 6.3 1719 6.7 1777 7.6 1835 8.6 1891 9.6 1948 10.6 2001 11.6 2056 12.7 2111 13.8 2166 14.9
11000 2422 1748 6.9 1774 7.3 1828 8.2 1885 9.2 1939 10.2 1993 11.2 2047 12.3 2097 13.4 2150 14.5 2202 15.7
11500 2533 1808 7.5 1832 7.9 1882 8.9 1936 9.8 1989 10.9 2041 11.9 2092 13.0 2143 14.2 2191 15.2 2241 16.4
12000 2643 1868 8.1 1890 8.5 1938 9.5 1988 10.5 2039 11.6 2090 12.7 2139 13.8 2189 14.9 2238 16.1 2284 17.2
12500 2753 1928 8.8 1951 9.3 1995 10.2 2042 11.3 2091 12.3 2140 13.4 2188 14.6 2236 15.8 2283 17.0 2330 18.2
13000 2863 1989 9.5 2011 10.0 2053 11.0 2098 12.1 2143 13.2 2191 14.3 2238 15.4 2284 16.6 2330 17.9 2375 19.1
13500 2973 2051 10.2 2072 10.8 2114 11.8 2155 12.9 2198 14.0 2242 15.2 2289 16.3 2333 17.5 2378 18.8 2422 20.1
14000 3083 2113 11.0 2133 116 2174 12.7 2213 13.8 2254 14.9 2296 16.1 2341 17.3 2384 18.5 2427 19.8 2470 21.1
14500 3193 2175 11.9 2195 12.5 2234 13.6 2274 14.8 2312 15.9 2352 17.1 2393 18.3 2436 19.5 2477 20.8 2519 22.1
15000 3303 2238 12.8 2257 13.4 2295 14.6 2333 15.8 2370 16.9 2408 18.1 2447 19.4 2487 20.7 2529 21.9 2569 23.3
15500 3414 2301 13.8 2320 14.4 2357 15.6 2394 16.6 2430 18.0 2466 19.2 2503 20.5 2541 21.8 2580 23.1 2620 24.4
16000 3524 2365 14.8 2383 15.4 2419 16.6 2455 17.9 2490 19.2 2524 20.4 2560 21.7 2596 23.0 2633 24.4 2673 25.7
16500 3634 2429 15.9 2446 16.5 2481 17.8 2516 19.0 2550 20.3 2585 21.7 2618 23.0 2653 24.3 2688 25.7 2724 27.1
17000 3744 2493 17.0 2510 17.6 2544 18.9 2578 20.3 2611 21.6 2645 22.9 2677 24.3 2710 25.6 2744 27.0 2779 28.5
17500 3854 2558 18.2 2574 18.9 2607 20.2 2640 21.5 2672 22.9 2705 24.3 2738 25.7 2768 27.0 2801 28.5 2835 29.9
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
10000 2202 2196 15.4 2258 16.7 2319 18.0
10500 2312 2223 16.2 2280 17.4 2339 18.6 2398 19.9
11000 2422 2255 16.9 2309 18.1 2363 19.4 2419 20.6 2475 22.0 2531 23.4
11500 2533 2292 17.6 2342 18.9 2393 20.2 2445 21.5 2498 22.9 2551 24.2 2605 25.6 2659 27.1
12000 2643 2331 18.5 2380 19.7 2428 21.0 2476 22.3 2526 23.7 2576 25.1 2627 26.6 2678 27.9 2730 29.4 2781 31.0
12500 2753 2374 19.3 2420 20.6 2466 21.9 2513 23.3 2558 24.6 2606 26.0 2654 27.5 2702 29.0 2751 30.4 2800 31.9
13000 2863 2420 20.4 2463 21.6 2507 22.9 2551 24.2 2596 25.6 2640 27.0 2685 28.5 2731 30.0 2777 31.5 2823 33.0
13500 2973 2466 21.4 2509 22.7 2552 24.0 2592 25.3 2635 26.7 2678 28.1 2721 29.5 2763 31.0 2807 32.6 2851 34.1
14000 3083 2513 22.4 2555 23.8 2597 25.1 2638 26.5 2677 27.8 2718 29.2 2759 30.7 2801 32.2 2841 33.7 2883 35.3
14500 3193 2561 23.5 2602 24.9 2642 26.3 2683 27.7 2723 29.1 2760 30.4 2800 31.9 2839 33.4 2879 34.9
15000 3303 2609 24.6 2650 26.0 2689 27.5 2729 28.9 2768 30.4 2807 31.9 2842 33.2 2881 34.7
15500 3414 2659 25.8 2698 27.2 2737 28.7 2776 30.2 2814 31.7 2852 33.2 2890 34.7
16000 3524 2711 27.1 2748 28.5 2786 30.0 2824 31.5 2861 33.0 2898 34.6
16500 3634 2763 28.4 2799 29.9 2836 31.4 2873 32.9
17000 3744 2814 29.9 2851 31.3 2887 32.8
17500 3854 2868 31.4 2902 32.9
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
31
Performance
Data Q Fan and
Super Q II
Size 27
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 27” Super Q Fan Size 27”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1 - 7.5 5 -15 15 - 40 1 - 7.5 5-15
Arrangement 1 —5 -15 15 - 40 NA NA
____ Fan RPM Line
- - - Motor HP Line
32
Fan Size 30”
Wheel Dia. 30.0 inches 762 mm
Inlet Area 6.45 square feet 0.599 m2
Outlet Area 5.60 square feet 0.520 m2
Tip Speed 7.85 x RPM 2.393
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 365
1200 RPM 243
Performance
Data Q Fan and
Super Q II
Size 30
Table P-6 — Size 30 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5000 892 566 0.4 597 0.5 631 0.6 664 0.7 696 0.8 761 1.1 828 1.4
5500 982 610 0.5 639 0.6 669 0.7 699 0.8 729 0.9 787 1.2 846 1.5 908 1.8
6000 1071 656 0.6 682 0.7 708 0.8 736 0.9 764 1.1 819 1.3 872 1.6 926 2.0 983 2.3
6500 1160 702 0.7 726 0.8 750 0.9 775 1.0 801 1.2 852 1.5 901 1.8 951 2.1 1001 2.5 1053 2.9
7000 1250 748 0.8 771 0.9 794 1.1 816 1.2 839 1.3 888 1.6 935 2.0 980 2.3 1026 2.7 1072 3.1
7500 1339 796 0.9 817 1.1 838 1.2 859 1.4 880 1.5 925 1.8 969 2.2 1013 2.5 1055 2.9 1098 3.3
8000 1428 843 1.1 863 1.2 883 1.4 903 1.5 922 1.7 963 2.0 1005 2.4 1047 2.7 1088 3.1 1126 3.5
8500 1517 891 1.2 910 1.4 928 1.6 947 1.7 966 1.9 1003 2.2 1042 2.6 1082 3.0 1121 3.4 1159 3.8
9000 1607 939 1.4 957 1.6 974 1.8 992 1.9 1010 2.1 1044 2.5 1081 2.9 1118 3.2 1156 3.7 1192 4.1
9500 1696 987 1.7 1004 1.8 1021 2.0 1038 2.2 1054 2.4 1088 2.7 1121 3.1 1156 3.5 1192 3.9 1227 4.4
10000 1785 1036 1.9 1052 2.1 1068 2.3 1084 2.4 1100 2.6 1131 3.0 1162 3.4 1195 3.8 1229 4.3 1263 4.7
10500 1874 1085 2.2 1100 2.3 1115 2.5 1130 2.7 1145 2.9 1176 3.3 1205 3.7 1235 4.2 1267 4.6 1300 5.1
11000 1964 1134 2.4 1148 2.6 1162 2.8 1177 3.0 1191 3.2 1220 3.7 1249 4.1 1277 4.5 1307 5.0 1338 5.4
11500 2053 1183 2.8 1196 3.0 1210 3.2 1224 3.4 1238 3.6 1266 4.0 1293 4.5 1320 4.9 1348 5.4 1376 5.9
12000 2142 1232 3.1 1245 3.3 1258 3.5 1271 3.7 1285 4.0 1311 4.4 1338 4.9 1364 5.3 1390 5.8 1416 6.3
12500 2232 1281 3.5 1293 3.7 1306 3.9 1319 4.1 1332 4.3 1357 4.8 1383 5.3 1408 5.8 1433 6.3 1458 6.8
13000 2321 1330 3.8 1342 4.1 1354 4.3 1367 4.5 1379 4.8 1403 5.3 1428 5.8 1452 6.3 1477 6.8 1500 7.3
13500 2410 1379 4.3 1391 4.5 1403 4.7 1415 5.0 1426 5.2 1450 5.7 1474 6.2 1497 6.8 1521 7.3 1544 7.8
14000 2500 1429 4.7 1440 5.0 1451 5.2 1463 5.5 1474 5.7 1497 6.2 1520 6.8 1542 7.3 1565 7.8 1588 8.4
14500 2589 1478 5.2 1489 5.5 1500 5.7 1511 6.0 1522 6.2 1544 6.8 1566 7.3 1588 7.9 1610 8.4 1632 9.0
15000 2678 1528 5.7 1538 6.0 1549 6.3 1559 6.5 1570 6.8 1591 7.3 1612 7.9 1634 8.5 1655 9.0 1676 9.6
15500 2767 1577 6.3 1587 6.6 1598 6.8 1608 7.1 1618 7.4 1639 7.9 1659 8.5 1680 9.1 1700 9.7 1721 10.3
16000 2857 1627 6.9 1637 7.2 1647 7.4 1656 7.7 1666 8.0 1686 8.6 1706 9.2 1726 9.8 1746 10.4 1766 11.0
16500 2946 1676 7.5 1686 7.8 1696 8.1 1705 8.4 1715 8.7 1734 9.3 1753 9.9 1773 10.5 1792 11.1 1811 11.7
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8000 1428 1167 3.9 1207 4.4 1291 5.3
8500 1517 1196 4.2 1234 4.7 1310 5.6 1390 6.6
9000 1607 1229 4.5 1263 5.0 1334 5.9 1407 6.9 1483 8.0
9500 1696 1262 4.8 1296 5.3 1362 6.2 1430 7.3 1500 8.4 1572 9.5
10000 1785 1296 5.2 1329 5.7 1392 6.6 1456 7.7 1521 8.8 1588 9.9 1657 11.1
10500 1874 1332 5.5 1363 6.0 1426 7.1 1485 8.1 1547 9.2 1609 10.4 1672 11.6 1738 12.9
11000 1964 1368 5.9 1399 6.4 1459 7.5 1518 8.6 1574 9.6 1633 10.8 1692 12.1 1754 13.4 1816 14.7
11500 2053 1406 6.4 1435 6.9 1493 7.9 1550 9.0 1605 10.1 1660 11.3 1716 12.6 1773 13.9 1832 15.3 1892 16.6
12000 2142 1444 6.8 1473 7.3 1529 8.4 1584 9.6 1638 10.7 1690 11.9 1743 13.1 1797 14.5 1852 15.8 1908 17.2
12500 2232 1484 7.3 1510 7.8 1565 8.9 1618 10.1 1671 11.3 1723 12.5 1772 13.7 1824 15.0 1875 16.4 1928 17.9
13000 2321 1525 7.8 1550 8.4 1602 9.5 1654 10.6 1705 11.9 1755 13.1 1803 14.4 1852 15.7 1902 17.1 1951 18.5
13500 2410 1567 8.4 1590 8.9 1640 10.0 1690 11.2 1740 12.5 1789 13.8 1837 15.1 1882 16.4 1930 17.8 1978 19.2
14000 2500 1609 8.9 1632 9.5 1678 10.7 1727 11.9 1775 13.1 1823 14.5 1870 15.8 1916 17.2 1960 18.5 2006 20.0
14500 2585 1653 9.6 1674 10.1 1719 11.3 1765 12.5 1812 13.8 1858 15.2 1904 16.5 1949 18.0 1994 19.4 2036 20.7
15000 2678 1697 10.2 1718 10.8 1760 12.0 1803 13.3 1849 14.6 1894 15.9 1939 17.3 1982 18.7 2026 20.2 2069 21.7
15500 2767 1741 10.9 1762 11.5 1801 12.7 1843 14.0 1887 15.3 1931 16.7 1974 18.1 2017 19.6 2059 21.1 2101 22.6
16000 2857 1786 11.6 1806 12.3 1844 13.5 1884 14.8 1925 16.2 1968 17.5 2010 18.9 2052 20.4 2093 22.0 2135 23.5
16500 2946 1830 12.4 1850 13.0 1888 14.3 1925 15.7 1965 17.0 2006 18.4 2047 19.8 2088 21.3 2128 22.9 2168 24.5
17000 3035 1876 13.2 1894 13.8 1932 15.2 1968 16.5 2005 17.9 2044 19.3 2085 20.8 2124 22.3 2164 23.8 2203 25.4
17500 3125 1921 14.0 1939 14.7 1975 16.1 2010 17.4 2047 18.9 2084 20.3 2122 21.8 2162 23.3 2200 24.9 2238 26.5
18000 3214 1967 14.9 1984 15.6 2020 17.0 2055 18.4 2089 19.8 2125 21.3 2161 22.8 2200 24.3 2237 25.9 2274 27.5
18500 3303 2013 15.8 2030 16.5 2064 17.9 2098 19.4 2131 20.9 2166 22.4 2201 23.9 2237 25.5 2275 27.0 2311 28.7
19000 3392 2059 16.7 2075 17.5 2109 18.9 2142 20.4 2176 22.0 2208 23.5 2242 25.0 2276 26.6 2313 28.2 2348 29.8
19500 3482 2105 17.7 2121 18.5 2154 20.0 2187 21.5 2219 23.1 2250 24.6 2283 26.2 2316 27.8 2350 29.5 2386 31.1
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
13000 2321 2002 20.0 2054 21.5 2106 23.0 2159 24.7
13500 2410 2025 20.7 2074 22.2 2124 23.8 2174 25.4 2225 27.0 2276 28.8
14000 2500 2052 21.5 2098 23.0 2145 24.6 2192 26.2 2241 27.8 2290 29.5 2339 31.3
14500 2589 2080 22.2 2124 23.8 2168 25.4 2214 27.0 2260 28.7 2306 30.5 2354 32.1 2401 33.9 2448 35.8
15000 2678 2109 23.1 2152 24.7 2195 26.3 2238 27.9 2282 29.6 2326 31.3 2371 33.1 2416 34.8 2462 36.7 2508 38.6
15500 2767 2141 24.0 2182 25.6 2223 27.2 2265 28.8 2306 30.5 2348 32.3 2391 34.1 2434 35.9 2478 37.6 2522 39.5
16000 2857 2175 25.1 2213 26.5 2253 28.2 2293 29.8 2333 31.5 2373 33.3 2414 35.1 2455 36.9 2497 38.8 2539 40.7
16500 2946 2208 26.1 2248 27.7 2284 29.2 2323 30.9 2362 32.6 2401 34.3 2440 36.1 2479 37.9 2519 39.8 2559 41.7
17000 3035 2242 27.1 2280 28.7 2319 30.4 2354 32.0 2391 33.7 2429 35.4 2467 37.2 2505 39.1 2543 40.9 2581 42.9
17500 3125 2276 28.1 2314 29.8 2351 31.5 2388 33.2 2423 34.8 2459 36.6 2496 38.4 2533 40.2 2569 42.1 2606 44.1
18000 3214 231 29.2 2348 30.9 2385 32.7 2421 34.4 2457 36.2 2490 37.8 2526 39.6 2561 41.5 2597 43.4
18500 3303 2347 30.4 2383 32.1 2419 33.9 2455 35.6 2490 37.5 2525 39.3 2557 40.9 2592 42.8
19000 3392 2384 31.6 2419 33.3 2454 35.1 2489 36.9 2523 38.7 2558 40.6 2592 42.5
19500 3482 2421 32.8 2455 34.6 2489 36.4 2523 38.2 2557 40.1 2591 42.0
20000 3571 2458 34.1 2492 35.9 2525 37.7 2559 39.5 2592 41.4
20500 3660 2496 35.5 2529 37.2 2562 39.1 2595 40.9
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
Pressure Class Limits
Class Maximum RPM
I 1448
II 1940
III 2618
33
Performance
Data Q Fan and
Super Q II
Size 30
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 30” Super Q Fan Size 30”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1 - 7.5 7.5 - 20 15 - 50 1 - 7.5 7.5 - 20
Arrangement 1 —7.5 - 20 15 - 50 NA NA
____ Fan RPM Line
- - - Motor HP Line
34
Fan Size 33”
Wheel Dia. 33.0 inches 838 mm
Inlet Area 7.78 square feet 0.723 m2
Outlet Area 6.78 square feet 0.630 m2
Tip Speed 8.64 x RPM 2.633
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 490
1200 RPM 326
Performance
Data Q Fan and
Super Q II
Size 33
Table P-7 — Size 33 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6000 884 521 0.4 554 0.6 588 0.7 620 0.8 651 1.0 713 1.3
6600 973 560 0.5 590 0.6 621 0.8 652 0.9 681 1.1 737 1.4 793 1.8 8.54 2.2
7200 1061 601 0.6 628 0.7 656 0.9 684 1.1 712 1.2 764 1.6 816 1.9 868 2.3 923 2.8
7800 1150 643 0.7 667 0.9 693 1.0 719 1.2 745 1.4 795 1.7 843 2.1 890 2.5 938 2.9 989 3.4
8400 1238 686 0.8 708 1.0 731 1.2 755 1.4 779 1.5 827 1.9 873 2.3 916 2.7 960 3.1 1005 3.6
9000 1327 729 1.0 749 1.2 770 1.3 792 1.5 814 1.7 860 2.1 903 2.5 946 2.9 987 3.4 1027 3.8
9600 1415 772 1.2 791 1.3 810 1.5 830 1.7 851 1.9 893 2.3 936 2.8 976 3.2 1016 3.7 1054 4.1
10200 1504 816 1.3 833 1.5 851 1.7 870 1.9 889 2.1 929 2.6 969 3.0 1008 3.5 1046 3.9 1082 4.4
10800 1592 860 1.6 876 1.7 893 1.9 910 2.1 928 2.3 965 2.8 1003 3.3 1040 3.8 1077 4.3 1113 4.8
11400 1681 904 1.8 920 2.0 935 2.2 952 2.4 968 2.6 1003 3.1 1038 3.6 1074 4.1 1109 4.6 1144 5.1
12000 1769 948 2.0 963 2.2 978 2.4 993 2.7 1009 2.9 1041 3.4 1075 3.9 1108 4.4 1142 5.0 1176 5.5
12600 1858 993 2.3 1007 2.5 1021 2.7 1036 3.0 1050 3.2 1080 3.7 1112 4.2 1144 4.8 1176 5.3 1209 5.9
13200 1946 1038 2.6 1051 2.8 1064 3.1 1078 3.3 1092 3.5 1120 4.0 1150 4.6 1180 5.1 1211 5.7 1242 6.3
13800 2035 1083 3.0 1095 3.2 1108 3.4 1121 3.7 1134 3.9 1161 4.4 1189 4.9 1218 5.5 1247 6.1 1276 6.8
14400 2123 1128 3.3 1140 3.6 1152 3.8 1164 4.0 1177 4.3 1202 4.8 1229 5.4 1256 6.0 1284 6.6 1312 7.2
15000 2212 1173 3.7 1184 4.0 1196 4.2 1208 4.5 1220 4.7 1244 5.2 1269 5.8 1295 6.4 1321 7.1 1348 7.7
15600 2300 1218 4.2 1229 4.4 1240 4.7 1251 4.9 1263 5.2 1286 5.7 1310 6.3 1334 6.9 1359 7.5 1385 8.2
16200 2389 1263 4.6 1274 4.9 1284 5.1 1295 5.4 1306 5.7 1328 6.2 1351 6.8 1375 7.4 1398 8.1 1423 8.8
16800 2477 1308 5.1 1318 5.4 1329 5.6 1339 5.9 1350 6.2 1371 6.8 1393 7.4 1415 8.0 1438 8.6 1461 9.3
17400 2566 1353 5.6 1363 5.9 1373 6.2 1383 6.5 1393 6.7 1414 7.3 1435 8.0 1456 8.6 1478 9.3 1500 10.0
18000 2654 1399 6.2 1408 6.5 1418 6.8 1428 7.1 1437 7.3 1457 7.9 1477 8.6 1498 9.2 1519 9.9 1540 10.6
18600 2743 1444 6.8 1453 7.1 1463 7.4 1472 7.7 1481 8.0 1500 8.6 1520 9.2 1540 9.9 1560 10.6 1580 11.3
19200 2831 1490 7.5 1498 7.7 1507 8.0 1516 8.3 1526 8.7 1544 9.3 1563 9.9 1582 10.6 1601 11.3 1621 12.0
19800 2920 1535 8.1 1544 8.4 1552 8.7 1561 9.1 1570 9.4 1588 10.0 1606 10.7 1624 11.4 1643 12.1 1662 12.8
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
9000 1327 1069 4.3 1112 4.9
9600 1415 1092 4.6 1131 5.1 1212 6.3
10200 1504 1118 4.9 1155 5.5 1228 6.6 1306 7.9
10800 1592 1147 5.3 1181 5.8 1249 6.9 1320 8.2 1394 9.6
11400 1681 1178 5.6 1210 6.2 1275 7.3 1339 8.5 1407 9.9 1478 11.5
12000 1769 1208 6.0 1240 6.6 1302 7.7 1363 9.0 1425 10.3 1490 11.8
12600 1858 1240 6.5 1271 7.0 1332 8.2 1389 9.5 1447 10.8 1508 12.2 1569 13.8 1634 15.5
13200 1946 1273 6.9 1303 7.5 1362 8.7 1417 10.0 1474 11.3 1529 12.7 1587 14.2 1646 15.9 1707 17.7
13800 2035 1306 7.4 1335 8.0 1392 9.2 1448 10.5 1500 11.9 1554 13.3 1607 14.7 1663 16.4 1719 18.1 1778 20.0
14400 2123 1340 7.9 1369 8.5 1424 9.8 1478 11.1 1529 12.5 1581 13.9 1632 15.4 1683 16.9 1736 18.6 1790 20.4
15000 2212 1375 8.4 1403 9.0 1457 10.4 1509 11.7 1560 13.1 1609 14.6 1658 16.1 1706 17.6 1756 19.2 1807 21.0
15600 2300 1411 8.9 1437 9.6 1490 11.0 1541 12.4 1590 13.8 1639 15.3 1686 16.8 1733 18.4 1779 20.0 1827 21.7
16200 2389 1448 9.5 1473 10.2 1523 11.6 1573 13.1 1621 14.5 1669 16.0 1716 17.6 1760 19.2 1806 20.8 1851 22.5
16800 2477 1485 10.1 1509 10.8 1557 12.3 1606 13.8 1654 15.4 1700 16.8 1746 18.4 1789 20.0 1833 21.7 1877 23.4
17400 2566 1523 10.7 1546 11.4 1593 13.0 1640 14.5 1686 16.1 1731 17.6 1776 19.3 1820 20.9 1861 22.5 1904 24.3
18000 2654 1562 11.3 1584 12.1 1629 13.7 1674 15.3 1719 16.9 1764 18.6 1807 20.1 1850 21.8 1892 23.5 1932 25.2
18600 2743 1601 12.1 1622 12.8 1665 14.4 1709 16.1 1753 17.8 1796 19.5 1839 21.2 1881 22.8 1922 24.5 1963 26.3
19200 2831 1641 12.8 1661 13.6 1703 15.2 1744 16.9 1787 18.6 1830 20.4 1871 22.1 1912 23.8 1953 25.6 1993 27.4
19800 2920 1681 13.6 1700 14.4 1740 16.1 1781 17.8 1822 19.5 1863 21.3 1904 23.1 1945 24.9 1984 26.6 2023 28.5
20400 3008 1721 14.4 1740 15.2 1778 16.9 1818 18.7 1857 20.5 1897 22.3 1938 24.1 1977 26.0 2016 27.9 2054 29.6
21000 3097 1762 15.3 1780 16.1 1817 17.8 1855 19.6 1894 21.4 1932 23.3 1971 25.2 2010 27.1 2048 29.0 2085 30.8
21600 3185 1804 16.2 1821 17.1 1856 18.8 1893 20.5 1930 22.5 1968 24.4 2005 26.3 2044 28.2 2081 30.2 2118 32.2
22200 3274 1845 17.2 1862 18.0 1896 19.8 1931 21.6 1968 23.5 2004 25.4 2040 27.4 2078 29.4 2114 31.4 2151 33.5
22800 3362 1887 18.2 1903 19.1 1936 20.8 1970 22.6 2006 24.6 2041 26.6 2076 28.6 2112 30.6 2148 32.7 2184 34.8
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
16000 2359 1890 24.0 1938 25.9 1987 27.9 2037 30.1
16600 2448 1912 24.8 1957 26.7 2004 28.6 2050 30.7 2099 32.9 2148 35.2
17200 2536 1938 25.8 1980 27.5 2024 29.5 2068 31.5 2113 33.6 2159 35.8 2207 38.2
17800 2625 1964 26.7 2006 28.6 2046 30.4 2088 32.4 2131 34.5 2175 36.6 2219 38.9 2264 41.3
18400 2713 1992 27.7 2032 29.6 2072 31.5 2111 33.4 2152 35.4 2193 37.5 2236 39.8 2278 42.1 2321 44.5 2366 47.0
19000 2802 2020 28.8 2059 30.7 2098 32.6 2138 34.6 2175 36.5 2214 38.6 2254 40.8 2295 43.0 2336 45.4 2377 47.9
19600 2890 2052 30.0 2088 31.8 2126 33.7 2164 35.7 2202 37.8 2238 39.7 2276 41.9 2315 44.1 2354 46.4 2394 48.8
20200 2979 2082 31.1 2119 33.1 2154 34.9 2191 36.9 2228 39.0 2265 41.1 2300 43.1 2337 45.3 2374 47.6 2412 49.9
20800 3067 2112 32.3 2149 34.3 2186 36.3 2220 38.2 2255 40.3 2291 42.4 2327 44.5 2362 46.7 2396 48.8 2433 51.1
21400 3156 2143 33.6 2180 35.6 2216 37.6 2251 39.6 2284 41.6 2318 43.8 2353 45.9 2388 48.1 2423 50.4
22000 3244 2176 35.0 2211 36.9 2246 38.9 2281 41.0 2315 43.1 2347 45.2 2381 47.4 2415 49.6 2448 51.8
22600 3333 2208 36.4 2243 38.5 2277 40.4 2311 42.5 2345 44.6 2378 46.8 2409 48.9 2442 51.1
23200 3421 2241 37.8 2275 39.9 2308 41.8 2342 44.0 2375 46.1 2408 48.3 2441 50.6
23800 3510 2274 39.2 2307 41.4 2341 43.5 2373 45.5 2406 47.7 2439 49.9
24400 3598 2307 40.6 2340 42.9 2373 45.1 2406 47.3 2437 49.3
25000 3687 2341 42.1 2374 44.4 2406 46.7 2438 49.0
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
Pressure Class Limits
Class Maximum RPM
I 1358
II 1822
III 2455
35
Performance
Data Q Fan and
Super Q II
Size 33
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 33” Super Q Fan Size 33”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1 - 10 7.5 - 25 20 - 50 1 - 10 7.5 - 20
Arrangement 1 1.5 - 10 7.5 - 25 20 - 60 NA NA
____ Fan RPM Line
- - - Motor HP Line
36
Fan Size 36”
Wheel Dia. 36.5 inches 927 mm
Inlet Area 9.52 square feet 0.884 m2
Outlet Area 8.30 square feet 0.771 m2
Tip Speed 9.56 x RPM 2.914
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 400
1200 RPM 266
Performance
Data Q Fan and
Super Q II
Size 36
Table P-8 — Size 36 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6000 722 409 0.4 446 0.5 481 0.6 515 0.8 550 1.0
6800 819 445 0.5 4.78 0.6 510 0.8 541 0.9 571 1.1 633 1.5
7600 915 483 0.5 512 0.7 542 0.9 570 1.1 598 1.2 651 1.6 708 2.1
8400 1012 523 07 549 08 575 1.0 602 1.2 628 1.4 677 1.8 725 2.2 776 2.8
9200 1108 564 08 586 10 611 1.2 635 1.4 659 1.6 706 2.0 750 2.5 795 3.0 841 3.5
10000 1204 605 1.0 626 1.2 647 1.4 670 1.6 692 1.8 736 2.3 779 2.7 819 3.2 860 3.7 902 4.3
10800 1301 648 1.2 666 1.4 686 1.6 706 1.8 727 2.0 769 2.5 809 3.0 847 3.5 885 4.1 922 4.6
11600 1397 690 1.4 708 1.6 725 1.8 744 2.0 763 2.3 802 2.8 840 3.3 877 3.8 912 4.4 948 5.0
12400 1493 733 1.6 749 1.8 766 2.1 783 2.3 800 2.6 836 3.1 873 3.7 908 4.2 943 4.8 975 5.4
13200 1590 777 1.9 792 2.1 807 2.4 823 2.6 839 2.9 872 3.4 906 4.0 940 4.6 973 5.2 1006 5.8
14000 1686 820 2.2 834 2.4 849 2.7 863 2.9 878 3.2 909 3.8 941 4.4 973 5.0 1005 5.7 1036 6.3
14800 1783 864 2.6 877 2.8 891 3.1 904 3.3 918 3.6 947 4.2 977 4.8 1007 5.5 1038 6.1 1068 6.8
15600 1879 908 2.9 920 3.2 933 3.5 946 3.7 959 4.0 986 4.6 1014 5.3 1042 5.9 1071 6.6 1100 7.3
16400 1975 952 3.4 964 3.6 976 3.9 988 4.2 1000 4.5 1026 5.1 1052 5.7 1079 6.4 1106 7.2 1134 7.9
17200 2072 996 3.8 1008 4.1 1019 4.4 1030 4.7 1042 5.0 1066 5.6 1090 6.3 1116 7.0 1142 7.7 1168 8.5
18000 2168 1041 4.3 1051 4.6 1062 4.9 1073 5.2 1084 5.5 1107 6.2 1130 6.8 1154 7.6 1178 8.4 1203 9.1
18800 2265 1085 4.9 1095 5.2 1106 5.5 1116 5.8 1127 6.1 1148 6.8 1170 7.5 1192 8.2 1215 9.0 1239 9.8
19600 2361 1130 5.5 1139 5.8 1149 6.1 1159 6.4 1169 6.7 1190 7.4 1211 8.1 1232 8.9 1254 9.7 1276 10.5
20400 2457 1174 6.1 1183 6.4 1193 6.8 1202 7.1 1212 7.4 1232 8.1 1251 8.9 1272 9.6 1293 10.4 1314 11.3
21200 2554 1219 6.8 1228 7.1 1237 7.5 1246 7.8 1255 8.2 1274 8.9 1293 9.6 1312 10.4 1332 11.2 1352 12.1
22000 2650 1263 7.6 1272 7.9 1281 8.3 1290 8.6 1298 9.0 1316 9.7 1335 10.5 1353 11.3 1372 12.1 1391 13.0
22800 2746 1308 8.4 1316 8.7 1325 9.1 1333 9.4 1342 9.8 1359 10.6 1377 11.4 1394 12.2 1412 13.0 1431 13.9
23600 2843 1353 9.2 1361 9.6 1369 10.0 1377 10.3 1385 10.7 1402 11.5 1419 12.3 1436 13.1 1453 14.0 1471 14.9
24400 2939 1398 10.2 1405 10.5 1413 10.9 1421 11.3 1429 11.7 1445 12.5 1461 13.3 1478 14.2 1494 15.0 1511 15.9
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
12000 1445 996 5.8 1029 6.4 1100 7.9
12800 1542 1022 6.2 1054 6.9 1118 8.2 1185 9.8
13600 1638 1052 6.7 1081 7.3 1142 8.7 1202 10.2 1266 12.0
14400 1734 1082 7.2 1111 7.9 1167 9.3 1223 10.8 1282 12.4 1342 14.2
15200 1831 1113 7.8 1141 8.4 1195 9.9 1249 11.4 1302 13.0 1358 14.8 1415 16.7
16000 1927 1145 8.4 1172 9.1 1225 10.5 1276 12.1 1327 13.7 1378 15.4 1431 17.3 1485 19.3
16800 2024 1178 9.0 1204 9.7 1256 11.2 1306 12.8 1354 14.4 1403 16.2 1451 18.0 1501 19.9 1553 22.1 1606 24.4
17600 2120 1211 9.6 1237 10.4 1287 12.0 1335 13.6 1382 15.2 1428 17.0 1475 18.8 1521 20.7 1569 22.8 1618 25.0
18400 2216 1245 10.3 1270 11.1 1319 12.8 1366 14.4 1412 16.1 14S6 17.9 1501 19.7 1544 21.6 1589 23.6 1635 25.8
19200 2313 1281 11.0 1304 11.9 1351 13.6 1398 15.3 1442 17.0 1486 18.9 1528 20.7 1571 22.6 1612 24.6 1655 26.7
20000 2409 1317 11.8 1340 12.6 1385 14.4 1430 16.3 1473 18.0 1516 19.9 1558 21.8 1598 23.7 1639 25.7 1679 27.7
20800 2506 1354 12.6 1376 13.5 1419 15.3 1462 17.2 1505 19.1 1546 20.9 1587 22.9 1628 24.9 1666 26.9 1705 29.0
21600 2602 1392 13.4 1412 14.4 1454 16.2 1496 18.2 1537 20.2 1578 22.1 1618 24.0 1657 26.1 1694 28.1 1732 30.2
22400 2698 1430 14.3 1449 15.3 1489 17.2 1529 19.2 1570 21.2 1610 23.3 1648 25.2 1687 27.3 1725 29.4 1760 31.5
23200 2795 1469 15.3 1488 16.2 1526 18.3 1564 20.3 1604 22.4 1642 24.5 1680 26.6 1717 28.6 1754 30.8 1791 33.0
24000 2891 1508 16.3 1526 17.3 1563 19.3 1600 21.4 1637 23.6 1675 25.7 1713 27.9 1749 30.1 1785 32.2 1821 34.4
24800 2987 1548 17.4 1565 18.4 1600 20.4 1636 22.6 1672 24.8 1709 27.0 1745 29.3 1781 31.5 1816 33.8 1851 35.9
25600 3084 1589 18.6 1605 19.6 1638 21.6 1673 23.8 1708 26.1 1743 28.4 1779 30.7 1814 33.0 1848 35.3 1882 37.5
26400 3180 1629 19.8 1645 20.8 1677 22.9 1710 25.1 1744 27.4 1778 29.8 1812 32.1 1847 34.5 1880 36.9 1914 39.3
27200 3277 1670 21.1 1686 22.1 1716 24.2 1748 26.5 1781 28.8 1814 31.2 1847 33.6 1880 36.1 1913 38.5 1946 41.0
28000 3373 1712 22.5 1726 23.5 1756 25.7 1787 27.9 1818 30.3 1850 32.7 1882 35.2 1914 37.7 1947 40.2 1979 42.8
28800 3469 1753 23.9 1767 25.0 1796 27.1 1826 29.4 1856 31.8 1887 34.3 1918 36.8 1949 39.4 198O 42.0 2012 44.5
29600 3566 1795 25.4 1809 26.5 1836 28.7 1865 31.0 1894 33.4 1924 35.9 1954 38.5 1984 41.1 2014 43.8 2045 46.4
30400 3662 1837 27.0 1850 28.1 1877 30.3 1905 32.7 1933 35.1 1961 37.6 1991 40.3 2020 42.9 2049 45.6 2079 48.3
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
19000 2289 16.95 28.7 1740 31.1 1787 33.6
19800 2385 1714 29.6 1757 32.0 1800 34.4 1845 37.0 1891 39.7
20600 2481 1737 30.8 1777 33.0 1818 35.4 1860 37.9 1902 40.6 1946 43.3
21400 2578 1764 32.1 1801 34.2 1839 36.6 1878 39.0 1918 41.6 1958 44.3 2000 47.1 2042 50.1
22200 2674 1790 33.4 1827 35.7 1863 37.9 1900 40.3 1937 42.8 1976 45.4 2014 48.2 2054 51.1 2094 54.0
23000 2771 1818 34.8 1854 37.1 1889 39.4 1925 41.8 1959 44.2 1996 46.8 2032 49.4 2070 52.2 2107 55.2 2145 58.2
23800 2867 1848 36.3 1881 38.6 1916 40.9 1950 43.4 1985 45.8 2018 48.2 2053 50.9 2088 53.6 2124 56.5 2160 59.4
24600 2963 1878 37.9 1912 40.2 1944 42.5 1977 45.0 2011 47.5 2044 50.0 2076 52.5 2109 55.2 2143 58.0 2178 60.8
25400 3060 1908 39.5 1941 41.9 1974 44.3 2005 46.7 2037 49.2 2070 51.8 2102 54.4 2133 56.9 2165 59.6 2198 62.5
26200 3156 1939 41.1 1971 43.6 2004 46.0 2036 48.5 2065 51.0 2097 53.6 2128 56.2 2160 58.9 2191 61.7
27000 3253 1970 43.1 2002 45.3 2034 47.8 2065 50.4 2096 53.0 2125 55.5 2155 58.1 2186 60.9 2216 63.6
27800 3349 2002 44.9 2034 47.4 2064 49.7 2095 52.3 2126 55.0 2156 57.6 2184 60.2 2213 62.9
28600 3445 2035 46.7 2065 49.3 2096 51.9 2126 54.3 2156 57.0 2185 59.7 2215 62.4
29400 3542 2067 48.6 2098 51.3 2128 54.0 2157 56.4 2186 59.1 2215 61.9
30200 3638 2101 50.6 2130 53.3 2160 56.1 2189 58.8
31000 3734 2134 52.6 2164 55.4 2192 58.2
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
Pressure Class Limits
Class Maximum RPM
I 1228
II 1647
III 2217
37
Performance
Data Q Fan and
Super Q II
Size 36
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 36” Super Q Fan Size 36”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1.5 - 15 10 - 30 25 - 50 1.5 - 15 10 - 30
Arrangement 1 1.5 - 15 10 - 30 25 - 75 NA NA
____ Fan RPM Line
- - - Motor HP Line
38
Fan Size 40”
Wheel Dia. 40.3 inches 1022 mm
Inlet Area 11.56 square feet 1.074 m2
Outlet Area 10.09 square feet 0.937 m2
Tip Speed 10.54 x RPM 3.213
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 301
1200 RPM 200
Performance
Data Q Fan and
Super Q II
Size 40
Table P-9 — Size 40 Q Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8000 792 395 0.5 426 0.7 455 0.9 483 1.1 511 1.3 571 1.8
8800 872 422 0.6 450 0.8 478 1.0 505 1.2 530 1.4 582 1.9
9600 951 451 0.7 477 0.9 502 1.1 528 1.3 552 1.6 599 2.1 647 2.6
10400 1030 481 0.8 504 1.1 528 1.3 552 1.5 575 1.7 619 2.2 662 2.8 707 3.4
11200 1110 512 1.0 532 1.2 554 1.4 576 1.7 598 1.9 641 2.5 681 3.0 721 3.6 763 4.3
12000 1189 543 1.1 562 1.4 582 1.6 602 1.9 623 2.2 663 2.7 701 3.2 739 3.9 777 4.5 816 5.2
12800 1268 574 1.3 592 1.6 610 1.8 629 2.1 648 2.4 687 3.0 724 3.5 759 4.1 795 4.8 830 5.5
13600 1347 606 1.5 622 1.8 639 2.0 657 2.3 675 2.6 711 3.2 747 3.8 781 4.5 814 5.1 848 5.8
14400 1427 638 1.8 653 2.0 669 2.3 685 2.6 702 2.9 736 3.5 771 4.2 804 4.8 836 5.5 867 6.2
15200 1506 670 2.0 684 2.3 699 2.5 714 2.8 730 3.1 762 3.8 795 4.5 827 5.2 858 5.9 888 6.6
16000 1585 702 2.3 716 2.6 730 2.8 744 3.1 759 3.5 789 4.1 820 4.9 851 5.6 881 6.3 910 7.0
16800 1665 735 2.6 748 2.9 761 3.2 774 3.5 788 3.8 817 4.5 846 5.2 876 6.0 905 6.8 933 7.5
17600 1744 767 2.9 780 3.2 792 3.5 805 3.8 818 4.2 845 4.9 872 5.6 901 6.4 929 7.2 957 8.0
18400 1823 800 3.3 812 3.6 824 3.9 836 4.2 848 4.6 873 5.3 900 6.1 926 6.9 954 7.7 980 8.5
19200 1902 833 3.7 844 4.0 855 4.3 867 4.7 878 5.0 902 5.7 927 6.5 953 7.4 979 8.2 1005 9.1
20000 1982 866 4.1 876 4.4 887 4.8 898 5.1 909 5.5 932 6.2 956 7.0 980 7.9 1005 8.8 1030 9.7
20800 2061 899 4.6 909 4.9 919 5.3 930 5.6 940 6.0 962 6.7 985 7.5 1008 8.4 1031 9.3 1055 10.3
21600 2140 932 5.1 942 5.4 952 5.8 962 6.1 972 6.5 993 7.3 1014 8.1 1036 9.0 1059 9.9 1081 10.9
22400 2220 965 5.6 974 6.0 984 6.3 994 6.7 1003 7.1 1023 7.9 1044 8.7 1065 9.6 1086 10.6 1108 11.5
23200 2299 998 6.2 1007 6.5 1016 6.9 1026 7.3 1035 7.7 1054 8.5 1074 9.4 1094 10.3 1114 11.2 1136 12.2
24000 2378 1031 6.8 1040 7.2 1049 7.5 1058 7.9 1067 8.3 1085 9.2 1104 10.0 1123 11.0 1143 11.9 1163 13.0
24800 2457 1064 7.4 1073 7.8 1081 8.2 1090 8.6 1099 9.0 1117 9.8 1135 10.8 1153 11.7 1172 12.7 1191 13.7
25600 2537 1098 8.1 1106 8.5 1114 8.9 1123 9.3 1131 9.8 1148 10.6 1165 11.5 1183 12.5 1201 13.5 1220 14.5
26400 2616 1131 8.9 1139 9.3 1147 9.7 1155 10.1 1163 10.5 1180 11.4 1196 12.4 1214 13.3 1231 14.3 1249 15.4
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
15000 1486 913 7.2 942 8.0 1004 9.7 1069 11.7
15800 1565 933 7.7 962 8.5 1019 10.1 1078 12.0
16600 1645 956 8.2 982 9.0 1037 10.7 1091 12.5 1149 14.6
17400 1724 978 8.7 1005 9.5 1056 11.2 1107 13.0 1161 15.0 1216 17.3
18200 1803 1001 9.2 1027 10.1 1076 11.8 1126 13.6 1175 15.6 1227 17.7 1280 20.1
19000 1883 1024 9.8 1049 10.6 1099 12.4 1146 14.3 1192 16.2 1241 18.3 1290 20.7 1342 23.2
19800 1962 1049 10.4 1073 11.3 1121 13.1 1166 15.0 1212 17.0 1257 19.0 1304 21.3 1351 23.7 1401 26.4
20600 2041 1073 11.0 1097 12.0 1143 13.8 1189 15.7 1232 17.7 1276 19.8 1319 22.0 1364 24.4 1410 27.0 1458 29.7
21400 2120 1098 11.7 1121 12.6 1167 14.6 1211 16.5 1253 18.5 1295 20.7 1338 22.9 1379 25.2 1423 27.7 1467 30.4
22200 2200 1124 12.4 1146 13.3 1191 15.4 1234 17.3 1276 19.4 1316 21.5 1357 23.8 1396 26.0 1438 28.5 1480 31.1
23000 2279 1150 13.1 1171 14.1 1215 16.2 1257 18.3 1298 20.3 1338 22.5 1377 24.7 1416 27.1 1454 29.4 1494 32.0
23800 2358 1177 13.8 1198 14.9 1240 17.0 1281 19.2 1321 21.3 1360 23.5 1397 25.7 1436 28.1 1474 30.6 1511 33.0
24600 2438 1204 14.6 1224 15.7 1265 17.8 1305 20.1 1344 22.3 1383 24.5 1420 26.9 1456 29.2 1493 31.7 1530 34.2
25400 2517 1232 15.4 1251 16.5 1290 18.8 1329 21.0 1368 23.4 1405 25.6 1442 28.0 1479 30.4 1513 32.8 1549 35.4
26200 2596 1260 16.2 1279 17.4 1316 19.7 1354 22.0 1392 24.4 1429 26.8 1465 29.1 1501 31.6 1534 34.0 1569 36.6
27000 2675 1288 17.1 1306 18.3 1343 20.6 1379 23.1 1416 25.5 1453 28.0 1488 30.3 1523 32.8 1557 35.4 1590 37.9
27800 2755 1317 18.1 1334 19.2 1370 21.7 1405 24.1 1441 26.6 1477 29.2 1512 31.7 1546 34.1 1579 36.7 1613 39.4
28600 2834 1346 19.1 1363 20.2 1397 22.7 1431 25.2 1466 27.8 1501 30.4 1535 33.0 1569 35.4 1602 38.1 1635 40.8
29400 2913 1376 20.1 1392 21.3 1425 23.8 1458 26.4 1492 29.0 1526 31.6 1560 34.3 1593 37.0 1625 39.5 1657 42.2
30200 2993 1406 21.3 1421 22.4 1453 24.9 1485 27.6 1518 30.2 1551 32.9 1584 35.7 1616 38.4 1649 41.2 1680 43.8
31000 3072 1436 22.4 1451 23.6 1481 26.1 1513 28.8 1544 31.5 1576 34.3 1609 37.0 1641 39.9 1672 42.7 1703 45.4
31800 3151 1466 23.6 1480 24.8 1510 27.4 1541 30.1 1571 32.8 1602 35.6 1634 38.5 1665 41.4 1696 44.3 1727 47.2
32600 3230 1496 24.9 1511 26.1 1539 28.7 1568 31.3 1599 34.2 1629 37.1 1659 40.0 1690 42.9 1720 45.9 1750 48.9
33400 3310 1527 26.2 1541 27.5 1568 30.0 1597 32.7 1626 35.6 1656 38.6 1685 41.5 1715 44.5 1745 47.5 1774 50.6
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
23000 2279 1535 34.8 1576 37.7 1619 40.7
23800 2358 1549 35.7 1589 38.5 1629 41.5 1670 44.7
24600 2438 1566 36.8 1603 39.5 1641 42.5 1680 45.6 1720 48.8
25400 2517 1585 38.1 1619 40.7 1655 43.5 1692 46.6 1730 49.8 1768 53.1 1807 56.6
26200 2596 1604 39.3 1638 42.0 1672 44.7 1707 47.7 1743 50.8 1779 54.1 1816 57.5 1854 61.1
27000 2675 1623 40.6 1657 43.4 1690 46.2 1723 49.0 1757 52.1 1792 55.3 1827 58.6 1862 62.1 1899 65.7
27800 2755 1644 42.0 1677 44.8 1709 47.6 1740 50.4 1773 53.4 1806 56.6 1840 59.8 1874 63.3 1908 66.8 1944 70.5
28600 2834 1667 43.5 1697 46.2 1729 49.1 1760 52.1 1791 54.9 1823 58.0 1855 61.2 1887 64.6 1921 68.1 1954 71.7
29400 2913 1689 45.0 1718 47.8 1749 50.7 1780 53.6 1811 56.7 1840 59.6 1871 62.7 1902 66.1 1934 69.5 1966 73.0
30200 2993 1711 46.6 1742 49.5 1770 52.3 1800 55.3 1830 58.3 1860 61.4 1890 64.6 1919 67.7 1949 71.0 1980 74.5
31000 3072 1733 48.2 1764 51.1 1793 54.1 1821 57.0 1851 60.0 1880 63.2 1909 66.4 1938 69.7 1966 72.8
31800 3151 1756 49.9 1786 52.8 1815 55.8 1844 58.9 1871 61.8 1900 65.0 1928 68.2 1957 71.5 1985 74.9
32600 3230 1780 51.8 1809 54.6 1838 57.6 1866 60.7 1895 63.9 1921 66.9 1949 70.1 1976 73.4
33400 3310 1804 53.6 1832 56.4 1860 59.5 1889 62.6 1916 65.8 1944 69.0 1969 72.1
34200 3389 1828 55.5 1856 58.6 1883 61.5 1911 64.6 1939 67.8 1966 71.1 1993 74.4
35000 3468 1852 57.3 1880 60.5 1907 63.7 1934 66.6 1961 69.9 1988 73.2
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
Pressure Class Limits
Class Maximum RPM
I 1110
II 1492
III 2050
39
Performance
Data Q Fan and
Super Q II
Size 40
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 40” Super Q Fan Size 40”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 1.5 - 15 10 - 40 30 - 50 1.5 - 15 10 - 40
Arrangement 1 1.5 - 15 10 - 40 30 - 75 NA NA
____ Fan RPM Line
- - - Motor HP Line
40
Fan Size 44”
Wheel Dia. 44.5 inches 1130 mm
Inlet Area 14.14 square feet 1.314 m2
Outlet Area 12.33 square feet 1.145 m2
Tip Speed 11.65 x RPM 3.551
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 289
1200 RPM 192
Performance
Data Q Fan and
Super Q II
Size 44
Table P-10 — Size 44 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
9000 729 335 0.5 364 0.7 392 1.0 420 1.2 451 1.5
10000 811 360 0.7 385 0.9 412 1.1 437 1.3 463 1.6 517 2.2
11000 892 386 0.8 409 1.0 433 1.2 457 1.5 480 1.8 526 2.4
12000 973 413 0.9 434 1.2 456 1.4 478 1.7 499 2.0 542 2.6 585 3.3
13000 1054 440 1.1 460 1.3 480 1.6 500 1.9 520 2.2 559 2.8 598 3.5 639 4.2
14000 1135 468 1.2 487 1.5 505 1.8 523 2.1 542 2.4 580 3.0 616 3.7 652 4.5 691 5.4 729 6.3
15000 1216 496 1.4 514 1.7 531 2.0 548 2.4 565 2.7 600 3.3 635 4.0 669 4.8 702 5.6 738 6.5
16000 1297 525 1.7 541 2.0 557 2.3 574 2.6 590 3.0 622 3.7 655 4.4 687 5.2 719 6.0 750 6.8
17000 1378 554 1.9 569 2.2 584 2.6 600 2.9 615 3.3 645 4.0 676 4.7 707 5.5 736 6.4 767 7.3
18000 1459 583 2.2 597 2.5 612 2.9 626 3.2 641 3.6 669 4.4 698 5.2 727 6.0 756 6.8 784 7.7
19000 1540 612 2.5 626 2.9 639 3.2 653 3.6 667 4.0 694 4.8 721 5.6 748 6.4 776 7.3 804 8.2
20000 1622 641 2.9 654 3.2 667 3.6 681 4.0 694 4.4 719 5.2 745 6.1 771 6.9 797 7.8 824 8.7
21000 1703 671 3.2 683 3.6 696 4.0 708 44 721 4.8 745 5.7 770 6.6 794 7.4 819 8.4 844 9.3
22000 1784 701 3.6 712 4.0 724 4.4 736 4.8 748 5.3 772 6.2 795 7.1 818 8.0 842 9.0 866 9.9
23000 1865 730 4.1 742 4.5 753 4.9 764 5.3 776 5.8 798 6.7 821 7.7 843 8.6 865 9.6 888 10.6
24000 1946 760 4.6 771 5.0 782 5.4 793 5.9 804 6.3 825 7.3 847 8.2 869 9.3 890 10.3 911 11.3
25000 2027 790 5.1 800 5.5 811 6.0 821 6.4 832 6.9 853 7.9 873 8.9 894 9.9 915 11.0 935 12.0
26000 2108 820 5.7 830 6.1 840 6.6 850 7.0 860 7.5 880 8.5 900 9.5 920 10.6 940 11.7 960 12.8
27000 2189 850 6.3 860 6.7 869 7.2 879 7.7 889 8.2 908 9.2 927 10.3 947 11.4 966 12.5 985 13.7
28000 2270 880 6.9 889 7.4 899 7.9 908 8.4 917 8.9 936 9.9 955 11.0 973 12.2 992 13.3 1010 14.5
29000 2351 910 7.6 919 8.1 928 8.6 937 9.1 946 9.6 964 10.7 982 11.8 1000 13.0 1018 14.2 1036 15.4
30000 2433 941 8.4 949 8.9 958 9.4 966 9.9 975 10.4 992 11.5 1010 12.7 1027 13.9 1045 15.1 1062 16.3
31000 2514 971 9.2 979 9.7 987 10.2 996 10.7 1004 11.3 1021 12.4 1038 13.6 1055 14.8 1072 16.0 1088 17.3
32000 2595 1001 10.0 1009 10.6 1017 11.1 1025 11.6 1033 12.2 1050 13.4 1066 14.6 1082 15.8 1099 17.1 1115 18.4
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
16000 1297 784 7.8 818 8.9
17000 1378 796 8.2 828 9.2
18000 1459 813 8.7 841 9.6 901 11.9
19000 1540 830 9.2 857 10.2 911 12.3 969 14.8
20000 1622 849 9.7 874 10.7 925 12.8 978 15.2 1033 18.0
21000 1703 869 10.3 893 11.3 942 13.5 990 15.7 1043 18.5 1094 21.3
22000 1784 890 10.9 914 12.0 960 14.1 1005 16.4 1053 18.9 1103 21.9
23000 1865 911 11.6 934 12.6 978 14.9 1023 17.2 1067 19.6 1113 22.4 1161 25.5
24000 1946 933 12.3 955 13.4 999 15.6 1041 18.0 1083 20.5 1126 23.1 1170 26.0 1216 29.4
25000 2027 956 13.1 977 14.2 1019 16.4 1060 18.9 1101 21.4 1141 23.9 1182 26.8 1225 29.9 1270 33.4
26000 2108 979 13.9 999 15.0 1040 17.3 1080 19.8 1119 22.3 1158 25.0 1197 27.7 1237 30.7 1279 34.0 1322 37.6
27000 2189 1004 14.8 1023 15.9 1061 18.3 1101 20.7 1139 23.3 1176 26.0 1214 28.9 1251 31.7 1290 34.8 1331 38.4
28000 2270 1029 15.7 1047 16.8 1084 19.3 1122 21.7 1159 24.4 1195 27.1 1231 30.0 1268 32.9 1304 35.8 1342 39.2
29000 2351 1054 16.6 1072 17.9 1107 20.3 1143 22.9 1180 25.5 1215 28.3 1250 31.1 1285 34.1 1320 37.2 1355 40.3
30000 2433 1079 17.6 1096 18.9 1130 21.4 1165 24.0 1201 26.6 1235 29.4 1270 32.4 1303 35.4 1337 38.5 1370 41.5
31000 2514 1105 18.6 1122 19.9 1154 22.5 1188 25.2 1222 28.0 1256 30.7 1290 33.7 1322 36.7 1355 39.9 1388 43.1
32000 2595 1131 19.7 1147 21.0 1180 23.8 1211 26.4 1244 29.2 1277 32.0 1310 35.0 1342 38.1 1373 41.3 1405 44.5
33000 2676 1157 20.8 1173 22.2 1205 25.0 1235 27.7 1267 30.6 1298 33.5 1331 36.4 1362 39.5 1394 42.8 1424 46.0
34000 2757 1184 22.0 1199 23.4 1230 26.3 1260 29.2 1290 32.0 1321 35.0 1352 37.9 1383 41.1 1414 44.3 1443 47.6
35000 2838 1211 23.2 1226 24.6 1255 27.6 1285 30.6 1314 33.5 1343 36.5 1373 39.6 1404 42.6 1434 45.9 1464 49.3
36000 2919 1238 24.5 1252 25.9 1281 29.0 1310 32.0 1338 35.0 1367 38.1 1396 41.2 1425 44.3 1455 47.6 1484 51.0
37000 3000 1265 25.8 1279 27.3 1307 30.4 1335 33.5 1363 36.7 1390 39.7 1419 42.9 1447 46.2 1476 49.4 1504 52.8
38000 3081 1293 27.2 1306 28.8 1334 31.9 1361 35.1 1388 38.3 1415 41.4 1442 44.7 1469 48.0 1497 51.4 1525 54.7
39000 3163 1320 28.7 1334 30.3 1360 33.4 1387 36.7 1413 40.0 1440 43.3 1466 46.5 1492 49.9 1519 53.4 1547 56.7
CFM Out- Total Static Pressure
Std. let 7”7 1/2”8”8 1/2”9”9 1/2”10”10 1/2”11”11 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
28000 2270 1381 42.9 1420 46.7 1458 50.6
29000 2351 1392 43.7 1430 47.6 1468 51.6 1505 55.6
30000 2433 1405 44.9 1440 48.5 1476 52.3 1514 56.6 1550 60.7
31000 2514 1420 46.2 1453 49.7 1488 53.4 1522 57.4 1559 61.8 1594 66.0
32000 2595 1437 47.9 1468 51.1 1501 54.7 1534 58.6 1568 62.6 1603 67.2 1637 71.5
33000 2676 1455 49.5 1486 52.9 1516 56.2 1547 59.9 1579 63.9 1612 68.1 1646 72.7
34000 2757 1473 51.1 1503 54.6 1533 58.2 1562 61.5 1593 65.4 1624 69.4 1655 73.7
35000 2838 1492 52.7 1521 56.3 1550 59.9 1580 63.6 1608 67.1 1637 71.0
36000 2919 1512 54.5 1540 58.1 1568 61.7 1597 65.5 1625 69.3 1652 72.8
37000 3000 1532 56.3 1560 60.0 1587 63.6 1615 67.4 1642 71.3
38000 3081 1553 58.2 1580 61.9 1607 65.6 1633 69.4 1660 73.3
39000 3163 1574 60.2 1601 63.9 1627 67.7 1652 71.4
40000 3244 1595 62.3 1621 66.0 1647 69.8 1673 73.7
41000 3325 1616 64.7 1642 68.2 1668 72.0
42000 3406 1638 66.9 1664 70.5 1689 74.3
43000 3487 1661 69.3 1685 73.1
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar). Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
Pressure Class Limits
Class Maximum RPM
I 1070
II 1352
III 1922
41
Performance
Data Q Fan and
Super Q II
Size 44
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Minimum and Maximum Motor HP Ranges
Q Fan Size 44” Super Q Fan Size 44”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 3 - 20 15 - 40 40 - 50 3 - 20 15 - 40
Arrangement 1 3 - 20 15 - 40 40 - 75 NA NA
____ Fan RPM Line
- - - Motor HP Line
42
Fan Size 49”
Wheel Dia. 49.0 inches 1245 mm
Inlet Area 14.96 square feet 1.390 m2
Outlet Area 14.96 square feet 1.390 m2
Tip Speed 12.83 x RPM 3.911
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 301
1200 RPM 201
Performance
Data Q Fan
Size 49
Table P-11 — Size 49 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
13000 868 353 1.0 376 1.2 400 1.6 425 1.9 451 2.3
•14000 935 373 1.1 395 1.4 417 1.7 439 2.1 463 2.4
15000 1002 394 1.3 414 1.6 435 1.9 455 2.3 476 2.6 521 3.5
•160001069 415 1.4 434 1.8 453 2.1 472 2.5 492 2.9 532 3.7
17000 1136 437 1.6 454 2.0 472 2.4 490 2.7 508 3.1 545 4.0 585 4.9
18000 1203 458 1.9 475 2.2 492 2.6 509 3.0 525 3.4 560 4.3 596 5.2
19000 1270 480 2.1 496 2.5 511 2.9 528 3.3 544 3.7 576 4.6 610 5.6 645 6.6
20000 1336 503 2.4 517 2.8 532 3.2 547 3.6 563 4.1 593 4.9 624 5.9 657 7.0 691 8.1
21000 1403 525 2.7 539 3.1 552 3.5 567 3.9 582 4.4 611 5.3 640 6.3 671 7.4 702 8.5
22000 1470 548 3.0 560 3.4 574 3.9 587 4.3 601 4.8 629 5.8 657 6.7 685 7.8 715 9.0 745 10.2
23000 1537 570 3.4 582 3.8 595 4.2 608 4.7 621 5.2 648 6.2 674 7.2 701 8.3 729 9.5 757 10.7
•240001604 593 3.7 605 4.2 616 4.6 629 5.1 641 5.6 667 6.7 692 7.7 718 8.8 744 10.0 771 11.2
25000 1671 616 4.2 627 4.6 638 5.1 650 5.6 662 6.1 686 7.2 711 8.3 735 9.3 760 10.5 785 11.8
26000 1737 639 4.6 649 5.1 660 5.6 671 6.1 682 6.6 706 7.7 730 8.8 753 9.9 777 11.1 801 12.4
27000 1804 662 5.1 672 5.6 682 6.1 693 6.6 704 7.1 726 8.2 749 9.4 772 10.6 794 11.8 817 13.0
28000 1871 685 5.6 695 6.1 704 6.6 715 7.1 725 7.7 746 8.8 768 10.0 790 11.3 812 12.5 834 13.7
29000 1938 708 6.1 717 6.6 727 7.2 737 7.7 746 8.3 767 9.5 788 10.7 809 12.0 830 13.2 851 14.5
30000 2005 731 6.7 740 7.2 749 7.8 759 8.3 768 8.9 788 10.1 808 11.4 828 12.7 849 14.0 869 15.3
31000 2072 754 7.3 763 7.9 772 8.4 781 9.0 790 9.6 809 10.8 828 12.1 848 13.5 868 14.8 888 16.2
32000 2139 777 8.0 786 8.6 794 9.1 803 9.7 812 10.3 830 11.6 848 12.9 867 14.2 887 15.6 906 17.1
33000 2205 801 8.7 809 9.3 817 9.9 826 10.5 834 11.1 851 12.4 869 13.7 887 15.1 906 16.5 925 18.0
34000 2272 824 9.4 832 10.0 840 10.6 848 11.2 856 11.9 873 13.2 890 14.5 908 15.9 926 17.4 944 18.9
35000 2339 847 10.2 855 10.8 863 11.4 871 12.1 879 12.7 895 14.1 911 15.4 928 16.9 946 18.4 964 19.9
36000 2406 871 11.0 878 11.7 886 12.3 893 13.0 901 13.6 917 15.0 933 16.4 949 17.8 966 19.3 983 20.9
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
23000 1537 787 12.0
24000 1604 798 12.6 827 13.9
25000 1671 811 13.1 838 14.5
26000 1737 825 13.8 851 15.2 903 18.1
27000 1804 840 14.4 864 15.8 913 18.8
28000 1871 856 15.1 879 16.5 925 19.5 974 22.8
29000 1938 873 15.8 894 17.3 939 20.3 985 23.6
30000 2005 890 16.6 910 18. 1 953 21.2 996 24.4 1042 27.9
31000 2072 907 17.5 927 18.9 968 22.0 1009 25.3 1053 28.8
32000 2139 925 18.4 944 19.8 983 22.9 1023 26.3 1064 29.7 1107 33.5
33000 2205 944 19.4 962 20.8 999 23.9 1038 27.3 1077 30.8 1118 34.5
34000 2272 962 20.4 980 21.9 1016 24.9 1053 28.3 1091 31.9 1129 35.6 1170 39.5
35000 2339 981 21.4 999 23.0 1033 26.0 1069 29.4 1105 33.0 1143 36.8 1181 40.6 1221 44.8
36000 2406 1000 22.5 1017 24.1 1051 27.2 1085 30.5 1120 34.2 1156 38.0 1192 41.9 1230 46.0
37000 2473 1020 23.6 1036 25.2 1069 28.4 1102 31.7 1136 35.4 1171 39.2 1206 43.2 1242 47.3
38000 2540 1039 24.8 1055 26.4 1088 29.8 1120 33.0 1152 36.6 1186 40.5 1220 44.5 1254 48.6
39000 2606 1058 25.9 1075 27.6 1106 31.1 1137 34.4 1169 38.0 1201 41.9 1234 45.9
40000 2673 1078 27.1 1094 28.9 1125 32.4 1155 35.8 1186 39.4 1217 43.3 1249 47.4
41000 2740 1099 28.4 1114 30.2 1144 33.8 1174 37.5 1203 40.9 1234 44.8 1264 48.9
42000 2807 1119 29.8 1133 31.6 1163 35.3 1193 39.0 1221 42.5 1251 46.4
43000 2874 1140 31.2 1154 33.0 1183 36.8 1211 40.6 1240 44.3 1268 48.0
44000 2941 1160 32.6 1174 34.5 1202 38.3 1230 42.2 1258 46.1
45000 3008 1181 34.2 1195 36.0 1222 39.8 1250 43.8
46000 3074 1202 35.7 1215 37.6 1241 41.5 1269 45.5
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar).
Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses.
Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
Pressure Class Limits
Class Maximum RPM
I 949
II 1274
43
Performance
Data Q Fan
Size 49
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Super Q II fans are NOT available in size 49.
Horizontal fans only, for vertical units contact marketing in Lexington.
Minimum and Maximum Motor HP Ranges
Q Fan Size 49” Super Q Fan Size 49”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 2 - 20 20 - 50 —NA NA
Arrangement 1 ——— NA NA
____ Fan RPM Line
- - - Motor HP Line
44
Pressure Class Limits
Class Maximum RPM
I 857
II 1151
Fan Size 54”
Wheel Dia. 54.3 inches 1378 mm
Inlet Area 18.37 square feet 1.707 m2
Outlet Area 18.37 square feet 1.707 m2
Tip Speed 14.20 x RPM 4.328
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 292
1200 RPM 195
Performance
Data Q Fan
Size 54
Table P-12 — Size 54 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
16200 881 323 1.2 344 1.6 365 1.9 387 2.4 410 2.8
17600 958 344 1.4 363 1.8 382 2.2 402 2.6 422 3.1
19000 1034 365 1.7 383 2.1 401 2.5 419 2.9 437 3.4 475 4.4
20400 1110 387 1.9 403 2.3 420 2.8 437 3.2 454 3.7 488 4.8
21800 1186 410 2.2 425 2.7 440 3.1 456 3.6 471 4.1 503 5.2 536 6.3
23200 1262 432 2.6 446 3.0 460 3.5 475 4.0 490 4.5 519 5.6 550 6.8 582 8.1
24600 1339 455 3.0 468 3.4 481 3.9 495 4.5 509 5.0 537 6.1 565 7.3 594 8.6 625 10.0
26000 1415 479 3.4 491 3.9 503 4.4 516 4.9 529 5.5 555 6.6 581 7.8 608 9.2 636 10.6 666 12.1
27400 1491 502 3.8 513 4.3 525 4.9 537 5.4 549 6.0 574 7.2 599 8.4 624 9.8 650 11.2 677 12.7
28800 1567 525 4.3 536 4.9 547 5.4 558 6.0 570 6.6 594 7.9 617 9.1 641 10.5 665 11.9 690 13.5
30200 1643 549 4.9 559 5.5 569 6.0 580 6.6 591 7.2 613 8.6 636 9.9 658 11.2 681 12.7 705 14.2
31600 1720 572 5.5 582 6.1 592 67 602 7.3 612 7.9 633 9.3 655 10.7 676 12.0 698 13.5 720 15.0
33000 1796 596 6.2 605 6.8 615 7.4 624 8.0 634 8.7 654 10.0 675 11.5 696 12.9 716 14.4 737 15.9
34400 1872 620 6.9 629 7.5 638 8.1 647 8.8 656 9.5 675 10.9 695 12.4 715 13.9 734 15.3 754 16.9
35800 1948 644 7.7 652 8.3 661 8.9 669 9.6 678 10.3 696 11.8 715 13.3 734 14.9 753 16.4 772 17.9
37200 2025 668 8.5 676 9.1 684 9.8 692 10.5 701 11.2 718 12.7 736 14.2 754 15.9 773 17.5 791 19.2
38600 2101 691 9.4 699 10.1 707 10.8 715 11.5 723 12.2 740 13.7 757 15.3 775 17.0 792 18.7 810 20.4
40000 2177 715 10.3 723 11.0 731 11.7 738 12.5 746 13.2 762 14.8 778 16.4 795 18.1 812 19.9 829 21.6
41400 2253 739 11.4 747 12.1 754 12.8 761 13.6 769 14.3 784 15.9 800 17.6 816 19.3 833 21.1 849 22.9
42800 2329 763 12.4 770 13.2 778 13.9 785 14.7 792 15.5 807 17.1 822 18.8 837 20.6 853 22.4 869 24.3
44200 2406 788 13.6 794 14.4 801 15.1 808 15.9 815 16.8 829 18.4 844 20.2 858 21.9 873 23.8 889 25.7
45600 2482 812 14.8 818 15.6 825 16.4 831 17.2 838 18.1 852 19.8 866 21.5 880 23.4 894 25.3 909 27.2
47000 2558 836 16.1 842 17.0 849 17.8 855 18.6 862 19.5 875 21.2 888 23.0 902 24.9 916 26.8 930 28.8
48400 2634 860 17.5 866 18.4 872 19.2 879 20.1 885 20.9 898 22.7 911 24.6 924 26.5 937 28.4 951 30.4
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
29000 1578 717 15.2 744 16.9
30400 1654 730 16.0 755 17.7
31800 1731 745 16.8 767 18.5 815 22.2
33200 1807 760 17.7 782 19.5 826 23.1
34600 1883 777 18.7 797 20.5 838 24.2 882 28.2
36000 1959 794 19.8 813 21.6 852 25.3 893 29.3
37400 2035 811 20.9 830 22.7 867 26.5 906 30.5 946 34.8
38800 2112 830 22.2 847 23.9 883 27.7 920 31.8 957 36.1 997 40.6
40200 2188 849 23.6 865 25.2 900 29.0 935 33.2 970 37.5 1007 42.0
41600 2264 868 25.0 884 26.8 917 30.5 950 34.6 985 39.0 1019 43.5 1056 48.3
43000 2340 888 26.4 903 28.3 935 32.0 967 36.1 999 40.6 1033 45.2 1067 49.9 1103 55.0
44400 2416 907 27.9 923 29.8 953 33.6 984 37.7 1015 42.2 1047 46.9 1080 51.6 1113 56.7
45800 2493 927 29.4 942 31.5 972 35.5 1001 39.5 1032 43.9 1062 48.6 1094 53.5 1125 58.5
47200 2569 948 31.1 962 33.1 991 37.3 1019 41.3 1048 45.8 1078 50.5 1108 55.4
48600 2645 968 32.7 982 34.9 1010 39.2 1038 43.3 1066 47.7 1094 52.4 1123 57.4
50000 2721 988 34.5 1002 36.7 1030 41.1 1057 45.5 1084 49.8 1111 54.5 1139 59.5
51400 2798 1010 36.4 1023 38.6 1050 43.1 1076 47.7 1102 52.0 1129 56.7
52800 2874 1031 38.4 1043 40.6 1070 45.2 1095 49.9 1121 54.5 1146 59.0
54200 2950 1052 40.4 1064 42.7 1090 47.4 1115 52.1 1140 56.9
55600 3026 1074 42.6 1086 44.8 1110 49.5 1135 54.5
57000 3102 1096 44.8 1107 47.1 1130 51.9
58400 3179 1118 47.1 1129 49.5 1151 54.3
59800 3255 1140 49.5 1151 51.9
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar).
Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses.
Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
45
Performance
Data Q Fan
Size 54
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Super Q fans are NOT available in size 54.
Horizontal fans only, for vertical units contact marketing in Lexington.
Minimum and Maximum Motor HP Ranges
Q Fan Size 54” Super Q Fan Size 54”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 2 -25 20 - 60 —NA NA
Arrangement 1 ——— NA NA
____ Fan RPM Line
- - - Motor HP Line
46
Pressure Class Limits
Class Maximum RPM
I 775
II 1040
Fan Size 60”
Wheel Dia. 60.0 inches 1524 mm
Inlet Area 22.38 square feet 2.079 m2
Outlet Area 22.38 square feet 2.079 m2
Tip Speed 15.71 x RPM 4.788
ft./minute m/minute
Minimum Fan RPM (Without VFRB Option)
Motor Minimum Fan RPM
1800 RPM 314
1200 RPM 209
Performance
Data Q Fan
Size 60
Table P-13 — Size 60 Q-Fan
CFM Out- Total Static Pressure
Std. let 1/4” 3/8” 1/2” 5/8” 3/4”1”1 1/4”1 1/2”1 3/4”2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
19800 884 291 1.5 311 1.9 330 2.4 350 2.9 370 3.5
21400 956 309 1.7 327 2.2 344 2.6 362 3.2 381 3.7
23000 1027 327 2.0 344 2.5 360 3.0 376 3.5 393 4.1 428 5.3
24600 1099 346 2.3 361 2.8 376 3.3 391 3.9 407 4.4 439 5.7
26200 1170 365 2.6 379 3.2 393 3.7 407 4.3 422 4.9 451 6.2 482 7.6
27800 1242 384 3.0 397 3.6 410 4.1 424 4.7 437 5.3 464 6.7 493 8.1 523 9.7
29400 1313 403 3.4 415 4.0 428 4.6 441 5.2 453 5.9 479 7.2 505 8.7 532 10.3
31000 1385 423 3.9 434 4.5 446 5.1 458 5.7 470 6.4 494 7.8 519 9.3 544 10.9 570 12.6
32600 1456 442 4.4 453 5.0 464 5.6 475 6.3 487 7.0 510 8.5 533 9.9 557 11.6 581 13.3 606 15.1
34200 1528 462 4.9 472 5.6 482 6.2 493 6.9 504 7.7 526 9.2 548 10.6 570 12.3 593 14.1 616 15.9
35800 1599 482 5.5 491 6.2 501 6.9 511 7.6 521 8.3 543 9.9 563 11.4 585 13.1 606 14.9 628 16.8
37400 1671 502 6.2 511 6.9 520 7.6 530 8.3 539 9.1 560 10.7 580 12.3 600 14.0 620 15.7 641 17.7
39000 1742 522 6.9 530 7.6 539 8.3 548 9.1 558 9.9 576 11.5 596 13.2 615 14.9 634 16.7 654 18.6
40600 1814 542 7.7 550 8.4 559 9.1 567 9.9 576 10.7 594 12.4 613 14.2 631 16.0 650 17.7 668 19.6
42200 1885 562 8.5 570 9.2 578 10.0 586 10.8 595 11.6 612 13.4 630 15.2 648 17.1 665 18.8 683 20.8
43800 1957 582 9.4 590 10.1 597 10.9 605 11.8 613 12.6 630 14.4 647 16.2 664 18.2 681 20.1 698 22.0
45400 2028 602 10.3 610 11.1 617 11.9 625 12.8 632 13.7 648 15.5 664 17.4 681 19.3 698 21.3 714 23.3
47000 2100 622 11.3 630 12.2 637 13.0 644 13.9 651 14.8 666 16.6 682 18.5 698 20.6 714 22.6 730 24.7
48600 2171 643 12.4 650 13.3 656 14.1 663 15.0 671 15.9 685 17.8 700 19.8 715 21.8 731 24.0 746 26.0
50200 2243 663 13.6 670 14.4 676 15.3 683 16.2 690 17.2 704 19.1 718 21.1 733 23.2 748 25.4 763 27.6
51800 2314 683 14.8 690 15.7 696 16.6 703 17.5 709 18.5 723 20.5 736 22.5 750 24.7 765 26.9 780 29.2
53400 2386 704 16.1 710 17.0 716 17.9 722 18.9 729 19.9 742 21.9 755 24.0 768 26.2 782 28.4 797 30.8
55000 2457 724 17.5 730 18.4 736 19.4 742 20.4 748 21.4 761 23.4 776 25.6 787 27.8 800 30.1 814 32.4
56600 2529 744 18.9 750 19.9 756 20.9 762 21.9 768 22.9 780 25.0 792 27.2 805 29.5 818 31.8 831 34.2
CFM Out- Total Static Pressure
Std. let 2 1/4”2 1/2”3”3 1/2”4”4 1/2”5”5 1/2”6”6 1/2”
Air Vel. RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
35000 1563 645 18.3
36600 1635 656 19.2 679 21.3
38200 1706 668 20.1 689 22.2
39800 1778 681 21.2 701 23.3 742 27.7
41400 1849 694 22.2 713 24.4 752 28.9
43000 1921 708 23.4 726 25.6 763 30.1 801 35.0
44600 1992 723 24.6 740 26.8 775 31.4 811 36.3
46200 2064 738 26.0 754 28.1 788 32.8 822 37.7 858 42.9
47800 2135 754 27.4 769 29.6 801 34.2 834 39.2 868 44.4 903 50.0
49400 2207 770 29.1 785 31.1 816 35.7 847 40.8 879 46.1 912 51.6
51000 2278 786 30.6 801 32.9 830 37.4 860 42.5 891 47.8 922 53.3 955 59.3
52600 2350 803 32.3 817 34.6 845 39.1 874 44.2 904 49.6 934 55.3 965 61.1 997 67.3
54200 2421 819 34.0 833 36.4 860 41.0 888 46.0 917 51.5 946 57.2 975 63.0 1006 69.2
55800 2493 836 35.8 850 38.2 877 43.1 903 48.0 931 53.4 959 59.2 987 65.2 1016 71.3
57400 2564 853 37.6 866 40.1 893 45.2 918 50.1 945 55.5 972 61.3 999 67.4 1027 73.5
59000 2636 870 39.5 883 42.1 909 47.3 934 52.3 960 57.7 985 63.5 1012 69.6 1039 75.9
60600 2707 888 41.5 900 44.2 925 49.5 950 54.9 974 60.0 1000 65.8 1025 72.0
62200 2779 905 43.6 917 46.3 942 51.8 966 57.3 990 62.5 1014 68.3 1039 74.4
63800 2850 923 45.8 935 48.5 959 54.1 982 59.7 1006 65.1 1029 70.9
65400 2922 941 48.1 952 50.8 976 56.5 999 62.3 1022 68.1
67000 2993 959 50.5 970 53.3 992 59.0 1016 64.9 1038 70.8
68600 3065 978 53.0 988 55.8 1010 61.6 1032 67.6
70200 3136 996 55.6 1006 58.4 1027 64.3
71800 3208 1015 58.3 1025 61.2
Performance based on 0.075 lbs. per cubic foot density (air at 70 F and 29.92 Hg Bar).
Performance shown is for installation Type B: free inlet, ducted outlet.
Power rating (BHP) does not include drive losses.
Performance ratings do not include the effects of appurtenances in the airstream.
When inlet vanes are used increase rpm 1 percent and brake horsepower 3 percent.
Fan tables cover part of fan operating range; fan curves show full operating range.
47
Performance
Data Q Fan
Size 60
Standard fans can be selected ONLY in the shaded area.
Thrust restrains are to be used with fans Class 3 or motors 40 hp and up.
Super Q fans are NOT available in size 60.
Horizontal fans only, for vertical units contact marketing in Lexington.
Minimum and Maximum Motor HP Ranges
Q Fan Size 60” Super Q Fan Size 60”
Min - Max Min - Max Min - Max Min - Max Min - Max
Motor HP Motor HP Motor HP Motor HP Motor HP
Class 1 Class 2 Class 3 Class 1 Class 2
Arrangement 9 3 - 30 25 - 75 —NA NA
Arrangement 1 ——— NA NA
____ Fan RPM Line
- - - Motor HP Line
48
Arrangement 9 Dimensions Drive Unit
In Out H Shaft Net Wt.
Size A B L W Max. Dia. Lbs.
16 Class I 19 3/817 7/828 3/823 5/845 15/16 115
16 Class II 19 3/817 7/828 3/823 5/845 15/16 115
16 Class III 19 3/817 7/828 3/823 5/845 1 3/16 120
19 Class I 21 7/820 1/228 7/826 1/848 1/415/16 135
19 Class II 21 7/820 1/228 7/826 1/848 1/415/16 135
19 Class III 21 7/820 1/228 7/826 1/848 1/41 3/16 140
21 Class I 24 5/823 1/832 3/429 51 3/815/16 175
21 Class II 24 5/823 1/832 3/429 51 3/81 3/16 180
21 Class III 24 5/823 1/832 3/429 51 3/81 3/16 185
24 Class I 28 1/826 3/835 3/832 7/855 1/41 3/16 215
24 Class II 28 1/826 3/835 3/832 7/855 1/41 3/16 220
24 Class III 28 1/826 3/835 3/832 7/855 1/41 11/16 225
27 Class I 30 7/829 38 35 3/458 1/81 3/16 275
27 Class II 30 7/829 38 35 3/458 1/81 7/16 290
27 Class III 30 7/829 38 35 3/458 1/81 15/16 305
30 Class I 34 3/832 1/441 1/839 1/861 5/81 3/16 350
30 Class II 34 3/832 1/441 1/839 1/861 5/81 7/16 360
30 Class III 34 3/832 1/441 1/839 1/861 5/81 15/16 375
33 Class I 37 3/435 1/245 42 5/865 1/81 3/16 440
33 Class II 37 3/435 1/245 42 5/865 1/81 7/16 450
33 Class III 37 3/435 1/245 42 5/865 1/82 3/16 485
36 Class I 41 3/439 1/449 1/247 5/869 5/81 7/16 575
36 Class II 41 3/439 1/449 1/247 5/869 5/81 11/16 580
36 Class III 41 3/439 1/449 1/247 5/869 5/82 7/16 630
40 Class I 46 43 1/453 3/451 7/877 1 7/16 710
40 Class II 46 43 1/453 3/451 7/877 1 11/16 720
40 Class III 46 43 1/453 3/451 7/877 2 15/16 800
44 Class I 50 7/847 3/460 5/856 3/482 1 11/16 830
44 Class II 50 7/847 3/460 5/856 3/482 1 15/16 850
44 Class III 50 7/847 3/460 5/856 3/482 3 7/16 950
Approximate weights are without motor and drive.
Motor position should be determined from the outlet side.
Dimensional
Data and
Weights
Roughing-In Dimensions
Arrangement 9
49
Arrangement 1 Dimensions Drive Unit
In Out H Shaft Net Wt.
Size A B L W Max. Dia. Lbs.
16 Class III 19 3/817 7/828 3/823 5/845 1 3/16 120
19 Class III 21 7/820 1/228 7/826 1/847 1/21 3/16 140
21 Class III 24 5/823 1/832 3/429 52 1/41 3/16 185
24 Class III 28 1/826 3/835 3/832 7/856 1/81 11/16 225
27 Class II 30 7/829 38 35 3/457 1/81 7/16 290
27 Class III 30 7/829 38 35 3/462 3/41 15/16 305
30 Class II 34 3/832 1/441 1/839 1/860 1/21 7/16 360
30 Class III 34 3/832 1/441 1/839 1/866 1/81 15/16 375
33 Class I 37 3/435 1/245 42 5/861 3/81 3/16 440
33 Class II 37 3/435 1/245 42 5/865 7/81 7/16 450
33 Class III 37 3/435 1/245 42 5/873 7/82 3/16 485
36 Class I 41 3/439 1/449 1/247 5/869 1 7/16 575
36 Class II 41 3/439 1/449 1/247 5/870 5/81 11/16 580
36 Class III 41 3/439 1/449 1/247 5/878 7/82 7/16 630
40 Class I 46 43 1/453 3/451 7/873 1/41 7/16 710
40 Class II 46 43 1/453 3/451 7/878 7/81 11/16 720
40 Class III 46 43 1/453 3/451 7/888 5/82 15/16 800
44 Class I 50 7/847 3/460 5/856 3/478 1/81 11/16 830
44 Class II 50 7/847 3/460 5/856 3/483 3/41 15/16 850
44 Class III 50 7/847 3/460 5/856 3/493 1/23 7/16 950
Arrangement 1, Class I and II require an integral base (supplied by others). Class III should be mounted on an inertia pad
(no integral base required with inertia pad).
Approximate weights are without motor and drive.
Roughing-In Dimensions
Arrangement1
Dimensional
Data and
Weights
50
Dimensional
Data and
Weights
Roughing-In Dimensions
Arrangement 9
Arrangement 9 Dimensions Drive Unit
H Shaft Net Wt.
Size A L W Max. Dia. Lbs.
49 Class I 52 3/876 57 1/879 7/81 11/16 1020
49 Class II 52 3/876 57 1/885 1/22 3/16 1075
54 Class I 58 81 7/862 3/485 1/21 15/16 1090
54 Class II 58 81 7/862 3/491 1/42 7/16 1140
60 Class I 64 1/892 69 3/496 1/42 3/16 1730
60 Class II 64 1/892 69 3/4108 1/42 11/16 1830
Approximate weights are without motor and drive.
51
Dimensional
Data and
Weights
Table D-2 — Outlet Diffuser (Equalizer)
Dimensions
Fan Size A B C D E
16 17 7/819 1/431
1/85 1/8
19 20 1/221 5/83 1/215
1/2
21 23 1/424 1/241
1/46 1/8
24 26 3/827 7/84 1/21 1/86 5/8
27 29 1/830 3/451
1/87
30 32 1/434 1/45 1/21 1/47 3/4
33 35 1/237 5/861
1/48 1/4
36 39 1/441 5/86 5/81 1/48 7/8
40 43 1/445 7/87 3/81 1/89 3/8
44 47 3/450 3/48 1/81 1/410 3/8
Figure D-2 — Q Fan Duct Outlet Diffuser, Sizes 16-44
Figure D-1 — Q Fan Inlet Vanes
Table D-1 — Inlet Vane Dimensions
Number Approx.
Fan Size A C of blades Wt. Lbs.
16 19.562 11.625 9 85
19 22.062 12.500 11 110
21 24.875 12.375 11 120
24 28.312 12.000 11 140
27 31.125 12.375 11 150
30 34.562 12.375 11 175
33 38.000 12.813 15 185
36 42.062 14.250 15 245
40 46.312 17.250 15 300
44 51.188 18.438 17 353
49 52.562 18.188 17 391
54 58.250 19.000 17 478
60 64.250 20.750 17 558
Q Fan
Accessory
Dimensions
A
½”
B
1”CD
E
52
Q Fan
Accessory
Dimensions
Dimensional
Data and
Weights
Figure D-3 — Super Q II 16-44 Sizes
Table D-3
Unit Inlet Area Outlet Area Unit
Size A B C D E Sq. Ft. F Sq. Ft. G H L W Weights*
16 11 7/815 1/445 3/828 20 1/82.2 17 7/81.8 24 30 39 1/244 1/4411
19 13 1/816 1/245 7/830 1/222 1/82.6 19 7/82.2 26 32 1/240 46 7/8451
21 14 1/217 7/849 3/433 3/826 1/83.7 22 7/82.9 30 35 3/843 7/850 537
24 16 1/219 3/452 3/837 1/428 1/84.3 25 7/83.7 32 39 1/446 3/855 634
27 17 7/821 1/455 40 1/832 1/85.6 28 7/84.6 36 42 1/849 1/857 7/8742
30 19 7/823 58 1/843 3/434 1/86.3 31 7/85.6 38 45 3/452 1/463 1/2881
33 21 3/824 5/861 7/847 1/838 1/87.9 35 7/87.0 42 49 1/856 70 1/21048
36 24 1/827 1/866 1/253 42 1/89.2 39 7/88.7 46 55 60 5/875 1/41375
40 26 1/429 1/470 3/456 1/246 1/811.6 43 7/810.6 50 58 1/264 7/881 7/81567
44 28 7/831 3/477 5/862 1/452 1/814.9 47 7/812.6 56 64 1/471 3/486 3/41858
* Approximate weights are without motor and drive.
53
Q Fan
Accessory
Dimensions
Dimensional
Data and
Weights
Table D-7 — Long Inlet Plus Silencer
Fan Approx.
Size D B L Weight
16”20”28”40” 97
19”22”30”44” 117
21”26”34”52” 170
24”28”36”56” 196
27”32”40”64” 256
30”34”42”68” 296
33”38”46”76” 370
36”42”50”84” 455
40”46”54”92” 634
44”52”60”104”755
49”52”60”104”888
54”58”66”116”1359
60”64”72”128”1704
Note: Silencer center body is fixed in position.
Table D-6 — Short Inlet Plus Silencer
Fan Approx.
Size D B L Weight
16”20”28”20” 49
19”22”30”22” 59
21”26”34”26” 85
24”28”36”28” 98
27”32”40”32”128
30”34”42”34”148
33”38”46”38”185
36”42”50”42”228
40”46”54”46”317
44”52”60”52”378
49”52”60”52”444
54”58”66”58”680
60”64”72”64”852
Note: Silencer center body is fixed in position.
Table D-4 — Short Outlet Plus Silencer
Fan Approx.
Size D B L Weight
16”18”26”18”68
19”20”28”20” 82
21”23”31”23”102
24”26”34”26”130
27”29”37”29”166
30”32”40”32”182
33”36”44”36”260
36”40”48”40”315
40”44”52”44”426
44”48”56”48”534
49”52”60”52”652
54”58”66”58”850
60”64”72”64”1050
Note: Silencer center body is adjustable. D dimension is
nominal duct size on entering air end and fitting size on
leaving air end.
Table D-5 — Long Outlet Plus Silencer
Fan Approx.
Size D B L Weight
16”18”26”36” 136
19”20”28”40” 164
21”23”31”46” 204
24”26”34”52” 260
27”29”37”58” 332
30”32”40”64” 364
33”36”44”72” 520
36”40”48”80” 630
40”44”52”88” 852
44”48”56”96”1068
49”52”60”104”1304
54”58”66”116”1700
60”64”72”128”2100
Note: Silencer center body is adjustable. D
dimension is nominal duct size on entering air end
and fitting size on leaving air end.
fFigure D-4 — Q Fan/Super Q II Plus Outlet Silencers
Figure D-5 — Q Fan/Super Q II Plus Inlet Silencers
54
Q FAN ASSEMBLY
Housing
Housings are 14-gauge steel
hydraulically expanded to form
integral inlet bell and diffuser sections.
Hydraulically expanded stiffening ring
welded in area of wheel raceway. On
VAV variable speed fan units, fan inlet
supports are structurally reinforced to
handle extra stresses of variable speed
fan modulation and fan is balanced at
ten different fan speeds over the
desired operating range.
Inlet/Outlet Shells
Fan has tapered inlet and outlet
shells over fan hub assembly. Shells
uniformly accelerate air through
blade area. End bell covers fan drive
assembly, thereby reducing flow
turbulence. Eight fan blades are
precision aluminum casting with airfoil
cross sections. Blade to shell clearance
is in the range of 30 mils.
Fan Wheel
Fans size 16-44 have fan wheel of
precision aluminum casting with eight
radially projected blades with air-foil
cross sections.
Fans size 49-60 have fan wheel of
sixteen precision cast and machined
aluminum blades mounted on a steel
wheel plate.
All wheels are dynamically balanced
and keyed to fan shaft.
Diffuser
Cast aluminum diffuser with 29 radially
projected straightening vanes with
airfoil cross sections. Leading edge of
vanes are curved to reduce tone noise
generation. Clips on almost every other
vane eliminate harmonic ring potential.
Shaft
Solid AISI-C1040 hot-rolled steel, turned
and polished. Close tolerances
maintained where shaft makes contact
with bearings.
Bearings
Precision, flange-mounted, self-aligning
ball bearings at inlet and discharge.
Bearings on all sizes are grease
lubricated and selected for a minimum
average life (AFBMA L-50) in excess of
200,000 hours at maximum cataloged
operating conditions. Bearing
greaselines are extended out through
fan shell for easy servicing.
Mechanical
Specifications
Drives
Mechanical drives are computer
selected for low noise, low
maintenance operation. Center
distance and arc of contact is
maintained within prefixed limits.
Constant speed fans use variable or
constant pitch drives; variable speed
modulated fans use fixed drives only.
SUPER QUIET II FANS
Trane Super Quiet II (SQ2) fans include
fan housing, wheel, shaft, bearings,
diffuser section, motor mounting
support, ODP standard or high
efficiency motor, drives, spring
isolation in acoustically-treated casing
in a factory-assembled unit. Fan motors
are outside of airstream.
Constant volume units (SQ2C) are
equipped with variable or constant
pitch drives. Variable air volume units
(SQ2V) use adjustable frequency
inverters for fan capacity modulation
and must have constant pitch drives.
Inlet vanes are NOT available for
Super Q II fans.
ENCLOSURE
Fans are internally isolated on four
height saving spring isolators and
then flex connected inside of an airtight
acoustical enclosure. Walls are
16-gauge steel, internally lined with
two-inch thick three-pound per
square foot density fiberglass. Airside
surface of acoustical lining is coated
with black matte faced lining to prevent
scuffing.
Enclosure has two large full size
side access panels. Access panels are
fully gasketed and mechanically
attached to casing for easy removal.
Enclosure has access panel positioning
feet to insure easy access panel
replacement after removal.
Duct connections in enclosure end
panels slip connect to standard U.S.
round duct sizes.
Fan grease lines are extended through
enclosure for easy servicing of fan.
Optional fan motor leads are extended
through casing for easier installation.
Two rails support the entire enclosure.
Rails can be rested on floor or hung
from the ceiling with steel rods. Ducts
can be directly connected to enclosure
since fan is internally isolated.
Enclosure is rated for four-inch
negative or five-inch positive pressure.
55
ACCESSORIES
Inlet Screen (Q, SQ2)
Heavy-gauge steel wire mesh.
Inlet Bellmouth (Q, SQ2)
On unducted inlets, the radius
bellmouth uniformly accelerates air
into the fan, reducing noise and energy
requirements.
Plus Duct Silencer (Q, SQ2)
Significantly attenuates fan airborne
sound levels. Center body of round
silencer is dimensional matched to
Q-fan hub. Center body is field
adjustable in the direction of airflow.
This allows hub to be located close to
Q-fan, thereby reducing flow
generated turbulence and noise.
Silencers can be on inlet and/or outlet
and come in short and long length
versions. Silencers are flex connected
to Q fans and slip connected directly to
Super Q II enclosures. Silencers are
shipped loose for field installation.
Inlet Flange (Q)
Rolled steel ring, factory-mounted, for
flanged duct connection. Sizes 16 to 21
one-inch flanges, sizes 27 to 44 are
1½-inch flanges.
Adjustable Inlet Vanes
11 steel vanes operated by a positive
peripheral control mechanism located
out of the airstream. Each vane is
supported at both ends by a precision
bronze bearing. The control arm is
suitable for manual or automatic
operation. Inlet vanes are shipped
loose for field installation.
Mechanical
Specifications
Outlet Flange (Q)
Rolled steel ring, factory-mounted, for
flanged duct connection.
Outlet Diffuser (Equalizer) (Q)
Steel spinning with 30 degree included
diffusion angle. Permit same size slip-
duct connection on discharge as inlet.
Outlet Screen (Q)
Heavy-gauge steel wire mesh.
Outlet Flow Stabilization
Screen (Q, SQ2)
Similar to outlet screen, but openings
are much smaller. Designed to act as
an airflow stabilization device on the
outlet of each fan.
Since The Trane Company has a policy of continuous
product improvement, it reserves the right to change
design and specification without notice.
Library Product Literature
Product Section Air Handling
Product Fans
Model 000
Literature Type Data Sales Catalog
Sequence 2
Date August 2000
File No. PL-AH-FAN-000-DS-2-0800
Supersedes FAN-DS-2 597
Ordering No. FAN-DS-2
The Trane Company
An American Standard Company
www.trane.com
For more information contact your
local sales office or e-mail us at
comfort@trane.com