Installation
Unit Control Module (UCM) 4.2 Retrofit
Model VAV

Models
“A” and later Design Sequence
VAV

July 2005

VAV-IN-24

Notice
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.

WARNING – Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
CAUTION – Indicates a potentially hazardous situation
which, if not avoided, may result in minor or
moderate injury. It may also be used to alert
against unsafe practices.
CAUTION – Indicates a situation that may result in
equipment or property-damage-only accidents.
General
The purpose of this installation manual is to provide application, functional and
calibration information for the Trane Retrofit package. Examples and charts are
provided to enhance the understanding of this information.
Introduction
The DDC/VAV retrofit kit consists of the UCM control assembly, a Honeywell™ or
Belimo™ actuator (both optional), and various accessories such as zone sensors,
transformers, flow sensors, etc. This manual is intended to show how to apply,
install and configure the DDC/VAV Retrofit kit. It is intended to provide
information specific to the VAV retrofit. Refer to VAV-SVX01C-EN for complete
DDC/VAV system wiring, installation and programming instructions.
Applications
The retrofit kit may be applied to pneumatic terminals by replacing the pneumatic
actuator with an electric actuator or electrically controlled terminals by either
using the existing electric actuator or by replacing it with one provided by Trane.
The kit may be used on existing shutoff, shutoff hot water reheat, shutoff with up
to three stages of electric heat, and fan powered (both parallel and series) cooling
only, hot water, and electric reheat units.
Note: Fan powered units have only two stages of reheat available.
Dual duct units may also be retrofitted using two sets of controllers. The kit has
also been applied to constant volume reheat systems where the retrofit kit is used
to control duct coils.
The kit has been tested on VAV terminals of several major manufacturers. It is
mandatory for unit to have an external shaft to function properly with the direct
coupled actuators offered.

© 2005 American Standard All rights reserved

VAV-IN-24

Contents

Installation/Startup/Commissioning

VAV-IN-24

2

Notice/Introduction

2

Application

2

Hardware

4

Installation

5

Commissioning

6

3

Hardware
UCM 4.2 Retrofit Kit
The UCM 4.2 retrofit kit is available in
three basic kits.
• Retrofit Kit with a Honeywell
actuator
• Retrofit Kit with a Belimo actuator
• Retrofit Kit with no actuator
The kit may also be ordered in a pressure dependent version on a special
basis. Both the Belimo and Honeywell
actuators are direct coupled actuators.

Control Assembly
The actual control assembly consists
of UCM and Delta P transducer mounted in a sheet metal enclosure. The accessories offered with the kit are zone
sensors with the same options as
Trane DDC/VAV: flow bars for use with
units without a flow sensor and control power transformers.

Honeywell Actuator
Key benefits and features of the Honeywell actuator are:
• Selectable 45°, 60°, and 90° angles
of rotation
• 35-inch-pound torque capacity
• 3/8-inch to 1/2-inch shaft size capability
• 90-second drive time over 90° rotation
• Magnetic coupled motor provides
45-inch-pounds stall
• 2 VA at 24-volts power consumption
• Manual clutch to disengage the actuator from the motor
Belimo Actuator
The Belimo actuator’s principle benefit
is flexibility. Belimo is designed with
the following features:
• Direct coupled with universal clamp
fitting shaft sizes, 3/8-inch to 1/2inch shaft size.
• Manual clutch to disengage the actuator from the motor
• Motor reversing switch to change
rotation
• Adjustable mechanical stops
• 35-inch-pounds torque capacity
• 3 VA at 24-volts power consumption
• 95-second run time

4

VAV-IN-24

Installation
WARNING
Hazardous Service
Procedures!
The maintenance and Trouble
Shooting procedures recommended in this section of the manual
could result in exposure to electrical, mechanical or other potential
safety hazards. Always refer to
the safety warnings provided
throughout this manual concerning these procedures. When possible, disconnect all electrical
power including remote disconnects and discharge all motor
start/run capacitors before servicing. Follow proper lockout/tagout
procedures to ensure the power
can not be inadvertently energized. When necessary to work
with live electrical components,
have a qualified licensed electrician or other individual who has
been trained in handling live electrical components perform these
tasks. Failure to follow all of the
recommended safety warnings
provided, could result in death or
serious injury.

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects and
discharge all motor start/run capacitors before servicing. Follow
proper lockout/tagout procedures
to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Pre-Installation
The existing unit controls will require
removal prior to installing the UCM 4.2
retrofit kit. This includes pneumatic actuators, volume regulators and any
miscellaneous auxiliary controls.

CAUTION
Local and N.A.C. electrical codes
should be observed when installing the UCM 4.2 retrofit kit.
Control Box Mounting
The next phase is to begin the installation of the kit. The controller should be
mounted at any convenient location
on the existing unit. Keep in mind the
controller must be mounted in a vertical plane to the flow transducer will
function properly. In a typical installation, the controller is mounted on one
side of the unit, and the actuator on
the other side due to space limitations.
However, Trane’s controller may be
mounted on the ductwork adjacent to
the terminal unit. The only requirement is the flow sensor tubing cannot
exceed 10-feet.
Actuator Installation
When installing the actuator, the convention of the damper rotation is assumed as:
•
•

Clockwise rotation of the damper
shaft will close the damper.
Counterclockwise rotation of the
damper shaft will open the damper

All of the wiring diagrams assume this
convention, Figure 1.

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects and
discharge all motor start/run capacitors before servicing. Follow
proper lockout/tagout procedures
to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Actuator Installation
To install the actuator, slip the actuator
over the shaft of the damper and use a
sheet metal screw to secure the actuator to the base of the terminal unit. Rotate both the actuator and damper
shaft fully clockwise and ensure that
the damper is fully closed. When the
damper is fully closed, tighten the set
screws of the actuator onto the damper shaft.
When following the clockwise-closed
convention, wiring terminations for
the actuator are shown in Table 1.
Table 1:
UCM 4.2

Actuator

Color Code

TB4-1

COM

White

Function
Hot

TB4-2

CCW

Black

Open

TB4-3

CW

Red

Closed

The actuator is now configured for
clockwise operation (with the actuator
closing the damper). If the damper is a
90° rotating damper, the actuator will
close the damper.
Note: If the damper angle of rotation is
counterclockwise to close, follow the
above procedure except reverse the
open and closed wires at the actuator
terminal block.

The communications power and zone
sensor wiring should be pulled to the
unit. The wiring procedures and
guidelines used are outlined in the
VAV-SVX01C-EN manual.

VAV-IN-24

5

Commissioning
Commissioning
For commissioning and configuration,
contact the local Trane service technician, or refer to VAV-SVX01C-EN.

6

Figure 1: UCM 4.2 Wiring Diagram

VAV-IN-24

Commissioning
Figure 2: Sensor signal vs. airflow delivery
5

Flow Sensor DP (In. wg)

1

4"

5"

6"

8"

10"

12" 14" 16"

0.1

0.01
10

100

1,000

10,000

Cfm

Note:
Refer to manufacturer of competitive terminal for Delta P vs. airflow delivery.

VAV-IN-24

7

Trane
A Business of American Standard Companies
www.trane.com
For more information, contact your local district
office or e-mail us at comfort@trane.com

Literature Order Number

VAV-IN-24

File Number

SV-TD-000-VAV-IN-24-0705

Supersedes

SV-TD-000-VAV-IN-24-0693

Stocking Location

Inland

Trane has a policy of continuous product and data improvement and reserves the right to change
design and specifications without notice.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Create Date                     : 2005:07:08 20:54:40Z
Modify Date                     : 2005:07:08 15:56:10-05:00
Page Count                      : 8
Creation Date                   : 2005:07:08 20:54:40Z
Mod Date                        : 2005:07:08 15:56:10-05:00
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Metadata Date                   : 2005:07:08 15:56:10-05:00
Page Layout                     : SinglePage
Page Mode                       : UseOutlines
EXIF Metadata provided by EXIF.tools

Navigation menu