Trane Rtaa 70 Installation Manual ManualsLib Makes It Easy To Find Manuals Online!
2014-12-11
: Trane Trane-Rtaa-70-Installation-Manual-121671 trane-rtaa-70-installation-manual-121671 trane pdf
Open the PDF directly: View PDF
.
Page Count: 178
| Download | |
| Open PDF In Browser | View PDF |
Installation
Operation
Maintenance
Series R®
Air-Cooled Rotary Liquid Chillers
Packaged Air-Cooled Chiller,
RTAA 70-125
Remote Evaporator
Air-Cooled Chiller,
RTAA 70-125
Models RTAA
RTAA-70
RTAA-80
RTAA-90
September 2005
© American Standard Inc. 2005
RTAA-100
RTAA-110
RTAA-125
RTAA-SVX01A-EN
NOTICE: Warnings and Cautions appear at appropriate sections throughout this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
CAUTION: Indicates a situation that may result in equipment or propertydamage only accidents.
Important
Environmental Concerns!
Scientific research has shown that certain man-made chemicals
can affect the earth’s naturally occurring stratospheric ozone layer
when released to the atmosphere. In particular, several of the
identified chemicals that may affect the ozone layer are
refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and Carbon
(HCFCs). Not all refrigerants containing these compounds have
the same potential impact to the environment. Trane advocates
the responsible handling of all refrigerants—including industry
replacements for CFCs such as and HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important
to the environment, our customers, and the air conditioning
industry. All technicians who handle refrigerants must be
certified. The Federal Clean Air Act (Section 608) sets forth the
requirements for handling, reclaiming, recovering and recycling of
certain refrigerants and the equipment that is used in these
service procedures. In addition, some states or municipalities
may have additional requirements that must also be adhered to
for responsible management of refrigerants. Know the applicable
laws and follow them.
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover
refrigerant to relieve pressure before opening the system. See
unit nameplate for refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non-approved
refrigerants, refrigerant substitutes, or refrigerant additives could
result in death or serious injury or equipment damage.
2
RTAA-SVX01A-EN
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Identification - Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Loose Parts Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Model Number Coding System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation — Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unit Leveling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Evaporator Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Evaporator Piping Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Entering Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Evaporator Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Chilled Water Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Installation — Remote Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
System Configuration and Interconnecting Refrigerant Piping . . . . . . . . . 31
Line Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Example Liquid Line Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Suction Line Sizing Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Piping Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Refrigerant Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Leak Test and Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Refrigerant and Additional Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Relief Valve Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Installation — Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
General Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Installer-Supplied Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Interlock Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Low Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Remote Clear Language Display Installation Procedure . . . . . . . . . . . . . . 62
Operating Principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Refrigeration (Cooling) Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Oil System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Controls Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Clear Language Display Keypad Overview . . . . . . . . . . . . . . . . . . . . . . . . 72
Select Report Group and Select Settings Group Flowcharts . . . . . . . . . . 74
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Operational Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
RTAA-SVX01A-EN
3
Table of Contents
DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
IPC Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Pre-Start Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Unit Voltage Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Unit Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Unit Voltage Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Water System Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Water System Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Clear Language Display Set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
System Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
System Subcooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Unit Shutdown Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Temporary Shutdown and Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Extended Shutdown Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
System Restart After Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . 113
Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Weekly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Monthly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Annual Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Chemically Cleaning The Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Oil Separator Level Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Oil Filter Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Refrigerant Charging and Recovery . . . . . . . . . . . . . . . . . . . . . . . . . 125
Low Side Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
High Side Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Adding Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Pump Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Temporary Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Pre-Start Review and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Control Panel Features and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Connection Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Pump Checkout Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Control Panel Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
System Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Planned Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Unit Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
4
RTAA-SVX01A-EN
General Information
Unit Identification - Nameplates
When the unit arrives, compare all nameplate data with ordering, submittal,
and shipping information. A typical unit nameplate is shown in Figure 1.
Figure 1
Standatd Unit Nameplate
Figure 2
Pump Package Unit Nameplate
Nameplates
The RTAA outdoor unit nameplates are applied to the exterior of the Control
Panel. A compressor nameplate is located on each compressor.
Outdoor Unit Nameplate
The outdoor unit nameplate provides the following information:
Unit model and size description.
Unit serial number.
Identifies unit electrical requirements.
Lists correct operating charges of R-22 and oil.
RTAA-SVX01A-EN
5
General Information
Lists unit test pressures.
Identifies installation, operation and maintenance and service data
literature.
Lists drawing numbers for unit wiring diagrams.
Pump Package Information - Optional
Compressor Nameplate
The compressor nameplate provides following information:
Compressor model number.
Compressor serial number.
Compressor electrical characteristics.
Utilization range.
Recommended refrigerant.
Unit Inspection
When the unit is delivered, verify that it is the correct unit and that it is
properly equipped. Compare the information which appears on the unit
nameplate with the ordering and submittal information.
Inspect all exterior components for visible damage. Report any apparent
damage or material shortage to the carrier and make a “unit damage”
notation on the carrier's delivery receipt. Specify the extent and type of
damage found and notify the appropriate Trane Sales Office.
Do not proceed with installation of a damaged unit without sales office
approval.
NOTE: If the Remote Evaporator Option is ordered, the remote evaporator
will be shipped in a separate crate.
Inspection Checklist
To protect against loss due to damage incurred in transit, complete the
following checklist upon receipt of the unit.
• Inspect the individual pieces of the shipment before accepting the unit.
Check for obvious damage to the unit or packing material.
•
Inspect the unit for concealed damage as soon as possible after delivery
and before it is stored. Concealed damage must be reported within 15
days after receipt.
•
If concealed damage is discovered, stop unpacking the shipment. Do not
remove damaged material from the receiving location. Take photos of the
damage. The owner must provide reasonable evidence that the damage
did not occur after delivery.
•
Notify the carrier’s terminal of the damage immediately, by phone and by
mail. Request an immediate, joint inspection of the damage with the carrier and the consignee.
•
Notify the Trane sales representative and arrange for repair. Do not repair
the unit, however, until damage is inspected by the transportation representative.
Loose Parts Inventory
Check all the accessories and loose parts which are shipped with the unit
against shipping list. Included in these items will be water vessel drain plugs,
isolators, rigging and electrical diagrams, and service literature, which are
placed inside the control panel and/or starter panel for shipment.
6
RTAA-SVX01A-EN
General Information
Unit Description
The 70 through 125-ton Model RTAA units are helical-rotary type, air-cooled
liquid chillers designed for installation outdoors. The unit has two
compressors and the compressor circuits are completely assembled,
hermetic packages. They are factory-piped, wired, leak-tested, de-hydrated,
and tested for proper operation before shipment. The units are factory
charged with refrigerant and oil.
The RTAA series features Trane's exclusive Adaptive Control™ logic with
Clear Language Display. It monitors the control variables that govern the
operation of the chiller unit. Adaptive Control logic can adjust these variables,
when necessary, to optimize operational efficiencies, avoid chiller shutdown,
and keep producing chilled water. An optional remote display is available to
monitor unit operation from a remote location.
These dual-compressor units feature two independent circuits, one for each
compressor. Compressor unloaders are solenoid actuated. Each refrigerant
circuit is provided with filter drier, sight glass, electronic expansion valve, and
charging valves.
The shell-and-tube type evaporator is manufactured in accordance with ASME
standards. The evaporator is fully insulated and is equipped with water drain
and vent connections. Packaged units have heat tape protection to
-20 F.
NOTE: Packaged units are factory charged with refrigerant and oil. Remote
evaporator units are shipped with a holding charge of nitrogen and a partial
charge of oil.
RTAA-SVX01A-EN
7
General Information
Table 1
General RTAA Mechanical Specifications
70
80
Size
90
100
110
125
2
35/35
2
40/40
2
50/40
2
50/50
2
60/50
2
60/60
(Gallons)
39.8
37.8
34.4
32.1
(Liters)
150.6
143.1
130.2
121.5
Min. Flow
(GPM)
84
96
108
120
(L/Sec)
5.3
6.1
6.8
7.6
Max. Flow
(GPM)
252
288
324
360
(L/Sec)
15.9
18.2
20.4
22.7
Refer to Pump Package Section for water storage of Pump and accocated piping.
53.4
202.1
132
8.3
396
25.0
45.8
173.4
150
9.5
450
28.4
Compressor
Quantity
Nominal Size (Tons)(1)
Evaporator
Water Storage
Condenser
Qty of Coils
Coil Length (Ft)(1)
Coil Height (In)
Number of Rows
4
13/13
42
2
4
13/13
42
2
4
14/13
42
2
4
14/14
42
2
4
17/14
42
2
4
17/17
42
2
4/4
30
68,380
855
6715
1.1
4/4
30
68,380
855
6715
1.1
5/4
30
73,365
855
6715
1.1
5/5
30
78,355
855
6715
1.1
5/5
30
82,950
855
6715
1.1
5/5
30
87,550
855
6715
1.1
15
-10
15
-10
15
-10
15
-10
15
-10
15
-10
HCFC-22
HCFC-22
HCFC-22
HCFC-22
HCFC-22
HCFC-22
2
10
58/58
26/26
10/10
10.6/10.6
2
10
61/61
27/27
10/10
10.6/10.6
2
10
73/61
33/27
12/10
12.7/10.6
2
10
73/73
33/33
12/12
12.7/12.7
2
10
98/73
44/33
12/12
12.7/12.7
2
10
98/98
44/44
12/12
12.7/12.7
Condenser Fans
Quantity (1)
Diameter (In)
Total Airflow (CFM)
Nominal RPM
Tip Speed (Ft./Min.)
Motor HP (Ea.)
Min. Starting/Oper. Ambient
Std Unit (Deg. F)
Low Amb. (Deg. F)
General Unit
Refrigerant
No. of Independent
Refrigerant Circuits
% Min. Load (3)
Refrig Charge
(Lb) (1)
(Kg)
Oil Charge
(Qts) (1.4)
(L)
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2
2. Minimum start-up/operating ambient based on a 5 mph wind across the condenser.
3. Percent minimum load is for total machine, not each individual circuit.
4. Trane Part Change # Oil-31 (see service bulletin SCOM-SB-1)
8
RTAA-SVX01A-EN
General Information
Model Number Coding System
The model number for the unit is comprised of numbers and letters which
represent features of the equipment. Shown on the chart in Figure 3 are
samples of typical unit model numbers, followed by the coding system.
Each position, or group of positions, in the number is used to represent a
feature. For example, in Figure 3, position 8 of the unit model number, Unit
Voltage, contains the number “4”. From the chart, it can be seen that a “4” in
this position means that the unit voltage is 460/60/3.
.
Figure 3
Model Number Coding System:
Model Number
RTA
Digit Number
0
Digit Position
123
A
4
Rotary Chiller
Digit 3
Unit Type
A
Air Cooled
Digit 4
Development Sequence
A
First Sequence
Digit 5,6,7
Nominal Capacity
070
70 Nominal Tons
080
80 Nominal Tons
090
90 Nominal Tons
100
100 Nominal Tons
110
110 Nominal Tons
125
125 Nominal Tons
Digit 8
Unit Voltage
D
380/60/3
A
200/60/3
C
230/60/3
K
400/50/3
4
460/60/3
5
575/60/3
Digit 9
Compressor Starter Type
Y
Y -Delta Closed Transition
X
X-Line (Across the Line)
Digit 10, 11
Design Sequence
AO
First Sequence (Factory Input)
Digit12
Evaporator Leaving Temperature
1
Standard 40 to 65 F
2
Low 0 to 39 F
3
Ice-Making 20 to 65 F
Digit 13
Condenser Coil Fin Material
A
Aluminum
2
CompleteCoat dipped coils
4
RTAA-SVX01A-EN
4
Y
A0
1
B
1
D
A
1
Digit 1-2
Unit Model
RT
070
567
8
9
01
0
2
2
3
4
5
6
0
Digit 14
Agency Listing
0
No Agency Listing
3
C-UL Listed
Digit 15
Control Interface
C
Deluxe without Communication
D
Deluxe with Communication
L
LCI-C (LonTalk)
Digit 16
Chilled Water Reset
0
No Chilled Water Reset
1
Based on Return Water Temp
2
Based on Outside Air Temp
Digit 17
Miscellaneous Factory Installed
Options
A
Architectural Louvered Panels
B
Control Power Transformer
C
Convenience Outlet
D
Low Ambient Lockout Sensor
F
Power Disconnect
G
Low Ambient Operation
H
Sound Attenuator
J
Remote Evaporator
K
Coil Protection
M
Access Guard
N
Neoprene Isolators
P
Circuit Breaker
R
Remote Display Panel
0
Size C 2 HP Pump Package
1
Size D 3 HP Pump Package
2
Size D 5 HP Pump Package
3
Size E 2 HP Pump Package
4
Size E 3 HP Pump Package
5
Size F 5 HP Pump Package
6
Size F 7 HP Pump Package
7
Size G 3 HP Pump Package
8
Size G 5 HP Pump Package
copper fins
9
Installation — Mechanical
Installation Responsibilities
Generally, the contractor must do the following when installing an RTAA unit:
• Install unit on a flat foundation, level (within 1/4” [6 mm] across the
length and width of the unit), and strong enough to support unit loading.
•
Install unit per the instructions contained in the Installation-Mechanical
and Installation-Electrical sections of this manual.
•
Where specified, provide and install valves in water piping upstream and
downstream of evaporator water connections to isolate the evaporator
for maintenance, and to balance/trim system.
•
Furnish and install flow switch to prove chilled water flow.
•
Furnish and install pressure gauges in inlet and outlet piping of the evaporator.
•
Furnish and install a drain valve to the bottom of the evaporator.
•
Supply and install a vent cock to the top of the evaporator.
•
Furnish and install strainers ahead of all pumps and automatic modulating
valves.
•
Provide and install field wiring.
•
Install heat tape and insulate the chilled water lines and any other portions of the system, as required, to prevent sweating under normal operating conditions or freezing during low ambient temperature conditions.
•
Start unit under supervision of a qualified service technician.
For remote evaporator units only
Furnish and install refrigerant piping, liquid line isolation valves, refrigerant,
and oil, per instructions outlined in this manual.
Storage
Extended storage of the outdoor unit prior to installation requires the
following precautionary measures:
Store the outdoor unit in a secure area.
At least every three months (quarterly), check the pressure in the refrigerant
circuits to verify that the refrigerant charge is intact. If it is not, contact a
qualified service organization and the appropriate Trane sales office.
Close the discharge and liquid line isolation valves.
Location Requirements
Noise Considerations
• Refer to Trane Engineering Bulletins for application information on RTAA
chillers.
10
•
Locate the outdoor unit away from sound-sensitive areas.
•
If required, install rubber vibration isolators in all water piping and use
flexible electrical conduit.
•
Refer to “Unit Isolation”.
•
Consult an acoustical engineer for critical applications.
RTAA-SVX01A-EN
Installation — Mechanical
Foundation
Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the outdoor unit operating weight (i.e.,
including completed piping, and full operating charges of refrigerant, oil and
water). Refer to Figure 13 for unit operating weights. Once in place, the
outdoor unit must be level within 1/4” (6.4 mm) over its length and width. The
Trane Company is not responsible for equipment problems resulting from an
improperly designed or constructed foundation.
RTAA-SVX01A-EN
11
Installation — Mechanical
Figure 4
12
RTAA Rigging and Lifting Weights – Packaged Unit
RTAA-SVX01A-EN
Installation — Mechanical
Figure 5
RTAA Rigging and Lifting Weights – Remote Evaporator
RTAA-SVX01A-EN
13
Installation — Mechanical
Figure 6
14
RTAA Rigging and Lifting Weights –Pump Package Aluminum Fins
RTAA-SVX01A-EN
Installation — Mechanical
Figure 7
RTAA Rigging and Lifting Weights –Pump Package Copper Fins
RTAA-SVX01A-EN
15
Installation — Mechanical
Clearances
Provide enough space around the outdoor unit to allow the installation and
maintenance personnel unrestricted access to all service points. Refer to
submittal drawings for the unit dimensions, to provide sufficient clearance for
the opening of control panel doors and unit service. Refer to Figure 8, Figure
9 and Figure 12 for minimum clearances. In all cases, local codes which
require additional clearances will take precedence over these recommendations.
NOTE: If the outdoor unit configuration requires a variance to the clearance
dimensions, contact your Trane Sales Office Representative. Also refer to
Trane Engineering Bulletins for application information on RTAA chillers.
Additional Location Requirements for Remote Evaporator Only
The Remote evaporator must be installed in a conditioned space, unless:
• The ambient temperature is always greater than 32 F.
•
The system circulating liquid is a non-freezing glycol-type solution,
selected for the prevailing ambient temperature. The evaporator is
protected from freezing by properly installed and applied insulation and
heat tape.
CAUTION
Freezing Equipment Damage!
To prevent damage due to freezing, do not install the unit outside
without adequate freeze protection.
The remote evaporator should be mounted on a base of suitable strength to
support the operating weight. Remote evaporator weights and mounting
locations are shown in Figure 10 and Figure 11.
The remote evaporator must be level when installed. Be sure to allow
adequate clearance for water and refrigerant piping connection, performance
of service procedures, reading of gauges and thermometers, and operation
of valves. Space must be allowed at one end of the evaporator to pull tubes,
if required.
Rigging
The Model RTAA chiller should be moved by lifting. Refer to Figure 4 for
typical unit lifting and weights. Refer to the rigging diagram that ships with
each unit for specific “per unit” weight data.
WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown. Each of the
cables (chains or slings) used to lift the unit must be capable of
supporting the entire weight of the unit. Lifting cables (chains or
slings) may not be of the same length. Adjust as necessary for
even unit lift. Other lifting arrangements may cause equipment or
property-only damage. Failure to properly lift unit may result in
death or serious injury. See details below.
16
RTAA-SVX01A-EN
Installation — Mechanical
Lifting Procedure
CAUTION
Equipment Damage!
To prevent damage do not use a forklift to lift or push the unit.
Position lifting beam so that cables do not contact the unit.
RTAA-SVX01A-EN
•
Install chains and safety chains through the six lifting plates provided on
the unit.
•
Attach lifting chains or cables to the chains installed above. Each cable
alone must be strong enough to lift the chiller.
•
Attach cables to lifting beam. Total lifting weight, lifting weight distribution
and required lifting beam dimensions are shown in Figure 4 and Figure 5
and on the rigging diagram shipped with each unit. Lifting beam crossbars must be positioned so lifting cables do not contact the sides of the
unit.
17
Installation — Mechanical
Figure 8
18
Dimensions and Clearances for RTAA Packaged Unit 70 – 125 Tons
RTAA-SVX01A-EN
Installation — Mechanical
Figure 9
Dimensions and Clearances for RTAA with Remote Evaporator 70 – 125 Tons
RTAA-SVX01A-EN
19
Installation — Mechanical
Figure 10
20
Remote Evaporator Dimensions, RTAA 70 – 125 Tons
RTAA-SVX01A-EN
Installation — Mechanical
Figure 11
Remote Evaporator Dimensions, RTAA 110 – 125 Tons
RTAA-SVX01A-EN
21
Installation — Mechanical
Figure 12
22
Dimensions and Clearances for RTAA with Pump Package 70 – 125 Tons
RTAA-SVX01A-EN
Installation — Mechanical
Unit Isolation
There are two mounting methods that will minimize sound and vibration
problems. They are the direct-mount method and the isolator-mount method.
Direct Mounting
The unit can be direct-mounted on an isolated concrete pad or on isolated
concrete footings at each mounting location. Refer to Figure 13 for unit
operating weights. A mounting hole is provided in the base of the unit frame
at each mounting location. Provide a means of securely anchoring the unit to
the mounting surface. Level the unit carefully. Refer to “Unit Leveling”.
Neoprene Isolators
Install the optional neoprene mounting isolators at each mounting location.
Refer to Figure 13 for isolator selection, placement and loading information.
Isolators are identified by color and by the isolator part number.
Bolt the isolators to the mounting surface. Do not fully tighten the mounting
bolts. Mount the unit on the isolators and install a 1/2”nut on each isolator
positioning pin. Maximum isolator deflection should be approximately 1/4inch. Level the unit carefully. Refer to “Unit Leveling”. Now fully tighten
isolator mounting bolts.
Unit Leveling
Before snugging down the mounting bolts, level the unit carefully. Check unit
level end-to-end by placing a level on the top surface of the unit frame. Unit
should be level to within 1/4-inch (6.35 mm) over its length. Place the level on
the unit frame to check front-to-back level. Adjust to within 1/4” (35 mm) of
level front-to-back. Use the adjustable spring isolators or shims to level
the unit.
Water Piping
Thoroughly flush all water piping to the unit before making the final piping
connections to the unit.
CAUTION
Use Piping Strainers!
To prevent evaporator damage, pipe strainers must be installed in
the water supplies to protect components from water born
debris. Trane is not responsible for equipment-only-damage
caused by water born debris.
CAUTION
Proper Water Treatment!
The use of untreated or improperly treated water in a RTAA may
result in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water treatment
specialist be engaged to determine what water treatment, if any,
is required. Trane assumes no responsibility for equipment
failures which result from untreated or improperly treated water,
or saline or brackish water.
RTAA-SVX01A-EN
23
Installation — Mechanical
Figure 13
24
Isolator Placement for Typical RTAA Packaged Unit 70 – 125 Tons
RTAA-SVX01A-EN
Installation — Mechanical
Figure 14
Isolator Placement for RTAA with Remote Evaporator
RTAA-SVX01A-EN
25
Installation — Mechanical
Evaporator Water Piping
Figure 15 illustrates typical evaporator piping components. Components and
layout will vary slightly, depending on the location of connections and the
water source.
CAUTION
Evaporator Damage!
The chilled water connections to the evaporator are to be
“victualic” type connections. Do not attempt to weld these
connections, as the heat generated from welding can cause
internal damage to the evaporator.
The chilled water connections are on the left side of the unit (when facing the
control panel). If it is necessary for the chilled water piping to enter the unit
from the right side, elbows can be used to route the piping 180° over the top
of the evaporator.
A vent is provided on the top of the evaporator at the leaving water end. Be
sure to provide additional vents at high points in the piping to bleed air from
the chilled water system. Install necessary pressure gauges to monitor the
entering and leaving chilled water pressures.
CAUTION
Chilled Water Components Damage!
To prevent damage to chilled water components, do not allow
evaporator pressure (maximum working pressure) to exceed
215 psig.
Provide shutoff valves in lines to the gauges to isolate them from the system
when they are not in use. Use rubber vibration eliminators to prevent
vibration transmission through the water lines.
If desired, install thermometers in the lines to monitor entering and leaving
water temperatures. Install a balancing valve in the leaving water line to
control water flow balance. Install shutoff valves on both the entering and
leaving water lines so that the evaporator can be isolated for service.
A pipe strainer must be installed in the entering water line to prevent waterborne debris from entering the evaporator.
26
RTAA-SVX01A-EN
Installation — Mechanical
6ALVED
0RESSURE
'AUGE
6ENTS
2ELIEF
6ALVE
5NION
$RAIN
Figure 15
5NION
6IBRATION
%LIMINATOR
&LOW
3WITCH
/PTIONAL
6IBRATION
%LIMINATOR
7ATER
3TRAINER
'ATE 6ALVE
'ATE 6ALVE
"ALANCING 6ALVE
Suggested Piping for Typical RTAA Evaporator
Evaporator Piping Components
“Piping components” include all devices and controls used to provide proper
water system operation and unit safety. These components and their general
locations are given below.
Entering Chilled Water Piping
•
Air vents (to bleed air from system).
•
Water pressure gauges with shutoff valves.
•
Vibration eliminators.
•
Shutoff (isolation) valves.
•
Thermometers (if desired).
•
Cleanout tees.
•
Relief valve.
•
Pipe strainer.
Leaving Chilled Water Piping Air vents (to bleed air from system).
• Air vents (to bleed air from system).
RTAA-SVX01A-EN
•
Water pressure gauges with shutoff valves.
•
Vibration eliminators. Shutoff (isolation) valves.
•
Thermometers.
•
Cleanout tees.
•
Balancing valve.
•
Flow Switch (If desired).
27
Installation — Mechanical
CAUTION
Evaporator Damage!
To prevent evaporator damage, do not exceed 215 psig (14.6 bar)
evaporator water pressure.
Evaporator Drain
A 3/4” drain connection is located under the outlet end of the evaporator. This
may be connected to a suitable drain to permit evaporator drainage during
unit servicing. A shutoff valve must be installed on the drain line.
Chilled Water Flow Switch
Chilled water flow protection is provided by the UCM without the need for a
chilled water flow switch. A flow switch for chilled water is strictly discretionary but if not installed, a signal must be sent to the chiller to indicate that
water flow has been established, eg. chilled water pump motor starter
auxiliary contacts, building automation system, etc.
If additional chilled water flow protection is desired, use a field-installed flow
switch or differential pressure switch with the pump motor starter auxiliary
contacts to sense system water flow. Install and wire the flow switch in
series with the chilled water pump motor starter auxiliaries (refer to
“Interlock Wiring”).
Specific connection and schematic wiring diagrams are shipped with the unit.
Some piping and control schemes, particularly those using a single water
pump for both chilled and hot water, must be analyzed to determine how and
or if a flow sensing device will provide desired operation.
Follow the manufacturer's recommendations for selection and installation
procedures. General guidelines for flow switch installation are outlined below:
1. Mount the switch upright, with a minimum of 5 pipe diameters of straight
horizontal run on each side. Do not install close to elbows, orifices or
valves.
NOTE: The arrow on the switch must point in the direction of flow.
2. To prevent switch fluttering, remove all air from the water system.
NOTE: The UCM provides a 6-second time delay after a “loss-of flow”
diagnostic before shutting the unit down. Contact a qualified service
representative if nuisance machine shutdowns persist.
3. Adjust the switch to open when water flow falls below nominal. Evaporator data is shown in Figure 16 Refer to Table 1 for minimum flow recommendations. Flow switch contacts are closed on proof of water flow.
4. Install a pipe strainer in the entering evaporator water line to protect
components from water-borne debr‘is.
28
RTAA-SVX01A-EN
Installation — Mechanical
Figure 16
RTAA Evaporator Water Pressure Drop
Water Treatment
Using untreated or improperly treated water in these units may result in
inefficient operation and possible tube damage. Consult a qualified water
treatment specialist to determine whether treatment is needed.
Customer Note
The use of improperly treated or untreated water in this equipment may
result in scaling, erosion, corrosion, algae or slime. The services of a qualified
water treatment specialist should be engaged to determine what treatment,
if any, is advisable. The Trane Company warranty specifically excludes liability
for corrosion, erosion or deterioration of Trane equipment. Trane assumes no
responsibilities for the results of the use of untreated or improperly treated
water, or saline or brackish water.
Water Pressure Gauges
Install field-supplied pressure gauges (with manifolds, whenever practical) as
shown in Figure 15. Locate pressure gauges or taps in a straight run of pipe;
avoid placement near elbows, etc. Be sure to install the gauges at the same
elevation.
To read manifolded pressure gauges, open one valve and close the other
(depending upon the reading desired). This eliminates errors resulting from
differently calibrated gauges installed at unmatched elevations.
RTAA-SVX01A-EN
29
Installation — Mechanical
Water Pressure Relief Valves
Install a water pressure relief valve in the evaporator inlet piping between the
evaporator and the inlet shutoff valve, as shown in Figure 15. Water vessels
with close-coupled shutoff valves have a high potential for hydrostatic
pressure buildup on a water temperature increase. Refer to applicable codes
for relief valve installation guidelines.
Freeze Protection
If the unit will remain operational at subfreezing ambient temperatures, the
chilled water system must be protected from freezing, following the steps
listed below:
1. Heat tape is factory-installed on the packaged unit evaporator and will
protect it from freezing in ambient temperatures down to -20 F.
2. Install heat tape on all water piping, pumps, and other components that
may be damaged if exposed to freezing temperatures. Heat tape must be
designed for low ambient temperature applications. Heat tape selection
should be based on the lowest expected ambient temperature.
3. Add a non-freezing, low temperature, corrosion inhibiting, heat transfer
fluid to the chilled water system. The solution must be strong enough to
provide protection against ice formation at the lowest anticipated ambient
temperature. Refer to Table 1 for evaporator water storage
capacities.
NOTE: Use of glycol type antifreeze reduces the cooling capacity of the unit
and must be considered in the design of the system specifications.
30
RTAA-SVX01A-EN
Installation — Remote Evaporator
The RTAA outdoor unit with the remote evaporator option is shipped as two
pieces: the outdoor unit (condenser) and the evaporator. Short suction line
connections are provided with the outdoor condensing unit. The liquid line
connections are at the end opposite the control panel.
The remote evaporator is shipped complete with factory-mounted
refrigeration specialties (electronic expansion valves, sight-glasses and
removable core filter-dryers). All evaporator refrigerant line connections are at
one end of the evaporator. The installing contractor need only provide and
install the inter-connecting refrigerant piping between the remote evaporator
and the outdoor condensing unit and liquid line isolation valves. In some
instances, the installing contractor may also need to lengthen the factory
installed suction accumulator.
System Configuration and Interconnecting Refrigerant
Piping
The system may be configured in any of the four arrangements shown in
Figure 17 through Figure 20. The configurations and their associated
elevations, along with the total distance between the remote evaporator and
the compressor/condenser section, play a critical role in determining suction
and liquid line sizes. This will also affect field refrigerant and oil charges.
Consequently, there are physical limits which must not be violated if the
system is to operate as designed. Please note the following requirements for
field installation:
RTAA-SVX01A-EN
31
Installation — Remote Evaporator
&RQGHQVHU&RLO
(;9
6LJKW
*ODVV
5HPRWH(YDSRUDWRU
/LTXLG/LQH
6XFWLRQ/LQH
&RPSUHVVRU
)LOWHU
'ULHU
Figure 17
Remote Evaporator Installation
No Elevation Difference, Rise of Suction and Liquid Lines not to exceed 20 inches or Less
&RQGHQVHU&RLO
(;9
6LJKW
*ODVV
/LTXLG/LQH
6XFWLRQ/LQH
&RPSUHVVRU
)LOWHU
'ULHU
Figure 18
32
5HPRWH(YDSRUDWRU
Remote Evaporator Installation
No Elevation Difference, Rise of Suction and Liquid Lines no to exceed 15 feet or Less
(Suction accumulator may be required)
RTAA-SVX01A-EN
Installation — Remote Evaporator
/LTXLG7UDS
+HLJKWHTXDOWR
7RSRI&RQGHQVHU
&RQGHQVHU&RLO
/LTXLG/LQH
6XFWLRQ/LQH
&RPSUHVVRU
¶
0D[LPXP
(;9
6LJKW
*ODVV
Figure 19
)LOWHU
'ULHU
Remote Evaporator Installation
Condensing Unit Above Evaporator – 100 Feet or Less
(;9
6LJKW
*ODVV
5HPRWH(YDSRUDWRU
5HPRWH(YDSRUDWRU
)LOWHU
'ULHU
¶
0D[LPXP
Figure 20
&RQGHQVHU&RLO
/LTXLG/LQH
6XFWLRQ/LQH
&RPSUHVVRU
Remote Evaporator Installation
Condensing Unit Below Evaporator – 15 Feet or Less
(Suction accumulator may be required)
RTAA-SVX01A-EN
33
Installation — Remote Evaporator
1.
The remote evaporator MUST be matched with its respective outdoor
condensing unit.
2. The circuit number on the outdoor condensing unit must match the
circuit number on the evaporator, i.e. circuit #1 on the outdoor
condensing unit must be connected with circuit # 1 on the remote
evaporator and likewise for circuit # 2.
See Figure 21 for circuit number identification. RTAA Circuit Capacities are
shown in Table 2.
CAUTION
Equipment Damage!
If the circuits are crossed, serious equipment damage may occur.
&RQWURO3DQHO
&RPSUHVVRU
&NW
&NW
&NW
&RPSUHVVRU
&NW
:DWHU
,QOHW
5HPRWH(YDSRUDWRU
:DWHU
2XWOHW
Figure 21
34
Refrigerant Circuit Identification
RTAA-SVX01A-EN
Installation — Remote Evaporator
Table 2
RTAA Circuit Capacities (nominal tons)
Model
Circuit 1
Circuit 2
70
35
35
80
40
40
90
50
40
100
50
50
110
60
50
125
60
60
Table 3
Equivalent Lengths of Non-Ferrous Valves and Fittings (feet)
Line Size
Inches OD
Globe
Valve
Short Angle
Valve
Short Radius Long Radius
ELL
ELL
1-1/8
87
29
2.7
1.9
1-3/8
102
33
3.2
2.2
1-5/8
115
34
3.8
2.6
2-1/8
141
39
5.2
3.4
2-5/8
159
44
6.5
4.2
3-1/8
185
53
8
5.1
Reproduced by permission of Air Conditioning and Refrigeration Institute
3. Piping between the evaporator and outdoor unit is not to exceed 200
actual feet and/or an equivalent length of 300 feet. (The latter includes the
equivalent length of pressure drops of all associated field installed
fittings, valves, accessories, and straight lengths of interconnecting
piping including the suction accumulator.)
4. Horizontal portions of suction lines must be downward sloping toward
the compressor at least 1/2 inch for each 10 feet of run. This promotes
the movement of oil in the direction of gas flow.
5. Suction lines must be insulated.
6. The line sizes defined in Table 4, 5, and 6 are to be used only for 40-50 F
leaving water temperature and/or full-load ice-making applications.
NOTE: The factory must size piping for leaving water temperatures other
than 40-50 F.
RTAA-SVX01A-EN
35
Installation — Remote Evaporator
.
Table 4
Liquid Line Sizes
Total
Equiv.
Length
(ft.)
35 Ton Circuit
Liquid Line Size (OD”)
Horizontal
or
Upflow Upflow
Downflow 1-5 ft.
6-10 ft.
25
50
75
100
125
150
175
200
225
250
275
300
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.375
Total
Equiv.
Length
(ft.)
50 Ton Circuit
Liquid Line Size (OD”)
Horizontal
or
Upflow Upflow
Downflow 1-5 ft.
6-10 ft.
25
50
75
100
125
150
175
200
225
250
275
300
1.125
1.125
1.125
1.125
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.375
1.375
1.375
1.125
1.125
1.125
1.125
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.125
1.125
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.375
1.375
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.625
1.625
1.625
1.625
Table 5
36
Upflow
11-15 ft.
Total
Equiv.
Length
(ft.)
40 Ton Circuit
Liquid Line Size (OD”)
Horizontal
or
Upflow Upflow
Downflow 1-5 ft.
6-10 ft.
Upflow
11-15 ft.
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.625
1.625
1.625
1.625
25
50
75
100
125
150
175
200
225
250
275
300
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.125
1.375
1.375
1.375
1.375
1.125
1.375
1.375
1.375
1.375
1.375
1.625
1.625
1.625
1.625
1.625
1.625
Upflow
11-15 ft.
Total
Equiv.
Length
(ft.)
60 Ton Circuit
Liquid Line Size (OD”)
Horizontal
or
Upflow Upflow
Downflow 1-5 ft.
6-10 ft.
Upflow
11-15 ft.
1.125
1.375
1.375
1.375
1.625
1.625
1.625
1.625
1.625
2.125
2.125
2.125
25
50
75
100
125
150
175
200
225
250
275
300
1.125
1.125
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.375
1.375
1.375
1.375
1.625
1.625
1.625
1.625
1.625
2.125
2.125
2.125
2.125
2.125
1.125
1.125
1.125
1.125
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.125
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.625
1.625
1.625
1.125
1.125
1.125
1.125
1.375
1.375
1.375
1.375
1.375
1.375
1.375
1.375
1.125
1.375
1.375
1.375
1.375
1.375
1.625
1.625
1.625
1.625
1.625
1.625
Suction Line Sizes (“O.D.”)
for Upflow Lines
Circuit Size
(nominal tons)
Outside Diameter
(inches)
35
2-1/8
40
2-1/8
50
2-5/8
60
2-5/8
RTAA-SVX01A-EN
Installation — Remote Evaporator
.
Table 6
Suction Line Sizes (“O.D.”) for
Horizontal and/or Downflow Lines
Circuit Size:
Total Equiv.
Length (ft.)
35 Ton 40 Ton 50 Ton 60 Ton
25
50
75
100
125
150
175
200
225
250
275
300
2.125
2.125
2.125
2.125
2.125
2.625
2.625
2.625
2.625
2.625
2.625
2.625
7.
2.125
2.125
2.125
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
2.625
3.125
3.125
2.625
2.625
2.625
2.625
2.625
2.625
3.125
3.125
3.125
3.125
3.125
3.125
Figure 17 depicts an installation where the remote evaporator elevation is
the same as that of the outdoor condensing unit. The suction and liquid
line are horizontal or down flowing only.
8. Figure 18 shows a variation to Figure 17. The remote evaporator and outdoor condensing unit are at the same elevation but interconnecting piping
may be installed up to 15 feet above the base elevation. In this case a
suction line trap is required to assure oil return, and the suction accumulator line must be extended at least by the amount determined from Table
7.
9. For installations where the remote evaporator is at a lower elevation than
the outdoor condensing unit as shown in Table 4, the elevation difference
is not to exceed 100 feet. An inverted liquid line trap to prevent unwanted
free cooling modes and a suction line trap to assure oil return from the
evaporator must be included on both circuits as shown. The apex of the
liquid line trap should be at a height above the condenser coils. The highest point of the suction line piping must not exceed 4 inches above the
outdoor condensing unit suction line connection point.
10. When the elevation of the remote evaporator exceeds that of the outdoor
condensing unit as shown in Figure 20, the elevation difference may not
exceed 15 feet. The suction accumulator line must be extended at least
by the amount determined from Table 7. This line must not exceed 4
inches above the outdoor unit suction line connection point. An inverted
suction line trap whose apex is 3 to 15 feet above the elevation of the
remote evaporator is required in both circuits.
11. Compressor and oil separator heaters must be on at least 24 hours prior
to compressor start.
RTAA-SVX01A-EN
37
Installation — Remote Evaporator
Line Sizing
To determine the appropriate outside diameter for field installed liquid and
suction lines, it is first necessary to establish the equivalent length of pipe for
each line. It is also necessary to know the capacity (tons) of each circuit.
Circuit capacities for each RTAA unit are listed in Table 2.
Liquid Line Sizing Steps
Line sizing is an iterative process. While iterating to determine the proper
equivalent line length use the “Horizontal or Downflow” column of Table 4.
After the final equivalent line length has been determined in step # 9, then
break down the piping into it's “Horizontal or Downflow” and “Upflow”
components and select the proper outside diameter. Note that “Upflow” has
a column for one to five, six to ten, and eleven to fifteen feet.
The steps to compute liquid line size are as follows:
1. Compute the actual length of field installed piping.
2. Multiply the length from step # 1 by 1.5 to estimate the equivalent length.
3. Using Table 4 for the proper tonnage circuit, look in the “Horizontal or
Downflow” column. Find the outside diameter that corresponds to the
equivalent length computed in step # 2.
4. With the outside diameter found in step # 3, use Table 3 to determine the
equivalent lengths of each fitting in the field installed piping.
5. Sum the equivalent lengths of all the field installed elbows.
6. Add the length found in step # 5 to the actual length from step # 1. This is
your new equivalent line length.
7.
Using Table 4 again, find the new outside diameter that corresponds to
the new equivalent line length from step # 6.
8. Using Table 2b and the new outside diameter found in step # 7, find the
equivalent line length of each elbow, and sum them.
9. Add the length found in step # 8 to the actual length from step # 1. This is
your final equivalent line length.
10. With the final equivalent line length found in step # 9, use Table 4 to
select the proper outside diameter for horizontal or downflow lines, and
any upflow lines.
38
RTAA-SVX01A-EN
Installation — Remote Evaporator
Table 7
Additional Suction Accumulator Line
Required Length in Feet of Field Installed Suction Line Accumulator
35 Ton Circuit
40 Ton Circuit
50 Ton Circuit
60 Ton Circuit
Liquid Line 2 1/8" O.D. 2 5/8" O.D. 2 1/8" O.D. 2 5/8" O.D. 2 5/8" O.D. 3 1/8" O.D. 2 5/8" O.D. 31/8"O.D.
Length in Suction
Suction
Suction
Suction
Suction
Suction
Suction
Suction
Actual Ft. Line
Line
Line
Line
Line
Line
Line
Line
20
1
1
5
3
9
6
14
10
40
7
5
14
9
15
11
21
15
60
14
9
23
15
21
15
27
19
80
20
13
32
21
28
19
33
23
100
26
17
N/A
26
34
24
40
28
120
32
21
N/A
32
40
28
46
32
140
N/A
25
N/A
38
46
33
52
37
160
N/A
29
N/A
43
53
37
N/A
41
180
N/A
33
N/A
49
59
41
N/A
45
200
N/A
37
N/A
55
65
46
N/A
50
Example Liquid Line Sizing
For this example, refer to Table 2, 3, 4, and Figure 22, and assume a 50 ton
circuit.
1. From Figure 22, the actual length of field installed piping is:
80+8+8+21 =117 feet
2. Estimate equivalent line length:
117 feet x 5=175 feet
3. From Table 4 for a 50 ton circuit, for 175 equivalent feet the OD is
1-3/8 inches.
4. In Figure 22 there are six long-radius elbows. From Table 3, for
1-3/8 inch elbows, the equivalent feet is:
6 elbows x 2.2 feet = 13.2 feet
5. Adding equivalent feet from step #4 to step #1 gives:
13.2 feet + 117 feet = 130.2 feet
6. From Table 4, for a 50 ton circuit, for 125 equivalent feet (nearest to
130.2), the OD is 1-1/8 inches
7.
From Table 3, for 1-1/8" OD long-radius elbows, the equivalent feet is:
6 elbows x 1.9 feet = 11.4 feet
8. Adding equivalent feet from step #7 to step #1 gives:
11.4 feet + 117 feet = 128.4 feet
RTAA-SVX01A-EN
39
Installation — Remote Evaporator
9. From Table 4, for a 50 ton circuit, for 125 equivalent feet (also nearest to
128.2 feet), the OD is still:
Horizontal or Downflow = 1 1/8 inches
10. From 22, there is 8 feet of up-flow on the liquid line inverted trap. Therefore, select:
Upflow = 1-3/8 inches
¶
/LTXLG7UDS
&RQGHQVHU&RLO
¶
/LTXLG/LQH 6XFWLRQ
&RPSUHVVRU
$FFXPXODWRU/LQH
µ
¶
¶
(;9
¶
87XEH
¶
5HPRWH(YDSRUDWRU
6LJKW
*ODVV
)LOWHU
'ULHU
Figure 22
6XFWLRQ/LQH7UDS
Liquid Line Sizing Example
Suction Line Sizing Steps
The steps to compute suction line size are as follows:
1. Break the suction line into it's “Upflow” and “Horizontal or Downflow”
components. The horizontal or downflow length should include that
portion of field-installed suction line within the condensing unit's base.
See Figure 22.
2. From Table 5, select the appropriate “Upflow” suction line outside diameter according to the circuit tonnage. This is the diameter of the upflow
suction line and any fittings in the upflow line.
3. With the diameter found in step #2, use Table 3 to find the equivalent
length of each fitting in the upflow line. Sum the equivalent lengths of all
the fittings in the upflow line.
4. Sum the final length found in step #3 with the actual length of the upflow
line. This is the final equivalent length of the upflow portion of the suction
line.
5. Multiply by 1.5, the actual length of the horizontal or downflow portion of
the suction line.
6. Add the length from step #5 to the length from step # 4. This is the first
estimate of the equivalent line length.
7.
40
In Table 6 find the column for the circuit tonnage you are sizing. In that
RTAA-SVX01A-EN
Installation — Remote Evaporator
column find the outside diameter that corresponds to the equivalent
length computed in step #6.
8. Use Table 3 and the diameter found in step #7 to determine the equivalent lengths of each fitting.
9. Sum the following: equivalent lengths of the fittings from step #8, the
actual length of the horizontal or downflow suction line, and the equivalent length of the upflow line found in step # 4. This is the new estimate
of the equivalent length of the entire suction line.
10. With the new length found in step #9, go back to Table 6 and find the
new diameter for the circuit you are sizing.
11. Repeat steps #8-10 with the new diameter found in step # 10.
12. The diameter found in step #11 is the horizontal or downflow suction line
diameter.
13. The diameter found in step #2 is the diameter of the upflow suction line
and any fittings in the upflow line.
NOTE: The diameters of the upflow, and horizontal or downflow portions of
the suction line may differ depending on the application.
Example Suction Line Sizing
For this example, refer to Table 3, 5, 6, and 23, and assume a 50 ton circuit on
a 100 ton chiller.
1. From 23, the actual length of upflow, and horizontal or downflow is:
upflow (20 + 5) = 25 feet
horizontal or downflow (75+8) = 83 ft.
2. Table 5 for a 50 ton circuit shows: Upflow suction line outside diameter
= 2-5/8 inches
3. According to Figure 23, there are 6 long radius ELLs. From Table 2b for a
diameter of 2-5/8 inches:
6 elbows x 3.4 feet = 20.4 feet
4. Final equivalent length of upflow suction line:
20.4 + 25 = 45.4 feet
5. There are no fittings in the horizontal portion. Therefore, the final
equivalent line length is:
45.4 + 83 = 128.4 feet
6. From Table 6, for a 50 ton circuit, and 125 equivalent feet
(nearest to 128.4):
Horizontal or downflow suction line
diameter = 2-5/8 inches
NOTE: In this example, the horizontal line is pitched downward in the
direction of flow.
RTAA-SVX01A-EN
41
Installation — Remote Evaporator
Suction Accumulator Sizing
Installations similar to those in Figure 18 and 20 will require that the suction
accumulator be extended at least by the amount shown in 7. The suction
accumulator length in feet is dependent upon: circuit tonnage, suction line
O.D., and actual liquid line length.
The following example uses Figure 23 and assumes a 50 ton circuit with a
2-5/8 inch O.D. suction line. Figure 23 illustrates an installation where the
remote evaporator is 11 feet above the outdoor condensing unit. A liquid line
at the same elevation as the evaporator runs horizontally 25 feet. Then it
drops 11 feet to the same elevation as the suction line connecting points on
the outdoor condensing unit, and runs horizontally 5 feet to the outdoor
condensing unit. From Figure 23, the actual length of liquid line is 41 feet (25
+ 11+5). With the previously mentioned assumptions, Table 7 indicates 15
feet of 2-5/8 inch O.D. suction accumulator needs to be added. Figure 24
shows one method of piping the additional 15 feet.
NOTE: In this example, if the liquid and suction lines had dropped the 11
feet from the evaporator and then run the 25 feet horizontal at the outdoor
condensing unit's elevation, the 15 feet of suction accumulator would not be
required.
NOTE: When sizing suction line diameters, the length of the suction
accumulator should be included in any computations.
The height of the suction accumulator, specified in Table 7, may not exceed 4
inches above the suction line connecting point at the outdoor condensing
unit. In addition, the suction accumulator must be pitched toward the
compressor 1/2 inch per 10 feet of horizontal run.
42
RTAA-SVX01A-EN
Installation — Remote Evaporator
7239,(:
&RQGHQVHU&RLO
¶´
IHHWRIKRUL]RQWDOVXFWLRQ
DFFXPXODWRUDWDKHLJKWQRWWR
H[FHHGLQFKHVDERYHWKHVXFWLRQ
OLQHFRQQHFWLQJSRLQWV
IHHWKRUL]RQWDOUXQDWWKHVDPH
HOHYDWLRQDVWKHUHPRWHHYDSRUDWRU
2XWGRRUFRQGHQVLQJXQLW¶V
HOHYDWLRQLVIHHWORZHUWKDQ
WKDWRIHYDSRUDWRUIHHWKRUL]RQWDO
UXQDWWKHVDPHHOHYDWLRQDVWKH
RXWGRRUFRQGHQVLQJXQLW
5HPRWH(YDSRUDWRU
6,'(9,(:
¶
µ
&RQGHQVHU&RLO
/LTXLG/LQH
6XFWLRQ/LQH
Figure 23
&RPSUHVVRU
Suction Accumulator Sizing Example
RTAA-SVX01A-EN
43
Installation — Remote Evaporator
Piping Installation Procedures
The outdoor unit and the evaporator are shipped with a 25 psig holding
pressure of dry nitrogen. Do not relieve this pressure until field installation of
the refrigerant piping is to be accomplished. This will require the removal of
the temporary pipe caps.
NOTE: Use Type L refrigerant-grade copper tubing only.
The refrigerant lines must be isolated to prevent line vibration from being
transferred to the building. Do not secure the lines rigidly to the building at
any point.
All horizontal suction lines should be pitched downward, in the direction of
flow, at a slope of 1/2 in. per 10 feet of run. This allows for larger line size,
which will improve unit efficiency.
Important: Relieve nitrogen pressure before removing end caps.
Do not use a saw to remove end caps, as this may allow copper chips to
contaminate the system. Use a tubing cutter or heat to remove the end caps.
WARNING
Prevent Injury!
When sweating line connections, always provide a sufficient
purge of dry nitrogen through the tubing to prevent the formation
of oxides/scaling cause by high temperature from brazing. Use a
pressure regulator in the line between the unit and the high
pressure nitrogen cylinder to avoid over pressurization and
possible explosion. If any refrigerant or refrigerant vapors are
present a thorough purge with dry nitrogen will prevent the
possible formation of toxic phosgene gas. Failure to follow these
recommendations could result in death or serious injury.
Refrigerant Sensors
The suction line refrigerant sensors must be installed by the contractor
installing the refrigerant piping. The sensors are prewired and each is
“wire-tied” to its respective liquid line. Fittings and adapters for mounting of
the sensors are located in the remote evaporator terminal box. See
Figure 24 for mounting instructions.
44
RTAA-SVX01A-EN
Installation — Remote Evaporator
Figure 24
Refrigerant Sensor Mounting and Wiring
RTAA-SVX01A-EN
45
Installation — Remote Evaporator
Leak Test and Evacuation
After installation of the refrigerant piping, thoroughly test the system for
leaks. Pressure test the system at pressures required by local codes.
Immediately before evacuation, install the liquid line filter cores. These will be
shipped with the evaporator.
NOTE: Do not install these before the circuit is ready for evacuation, as the
cores will absorb moisture from the atmosphere.
For field evacuation, use a rotary-type vacuum pump capable of pulling a
vacuum of 100 microns or less. Follow the pump manufacturer's instructions
for proper use of the pump. The line used to connect the pump to the system
should be copper and be the largest diameter that can be practically used. A
larger line size with minimum flow resistance can significantly reduce
evacuation time.
Use the ports on the compressor suction service valves and the liquid line
shutoff valves for access to the system for evacuation. Insure that the
compressor suction service valve, the liquid line shutoff valve, the oil line
shutoff valve and any field installed valves are open in the proper position
before evacuating.
Insulate the entire suction line and the suction accumulator line. Where the
line is exposed to the weather, wrap it with weatherproof tape and seal with
weather-proof compound.
Table 8
System Refrigerant Charge
Circuit Size
Lbs. of R- 22
35
58
40
61
50
73
60
98
Refrigerant and Additional Oil Charge
Refrigerant Charge Determination
The approximate amount of refrigerant charge required by the system must
be determined by referring to Table 8 and must be verified by running the
system and checking the liquid line sightglasses.
To determine the appropriate charge, first refer to Table 8 to establish the
required charge without the field-installed piping. Next, determine the charge
required for the field-installed piping by referring to Table 9.
NOTE: The amounts of refrigerant listed in Table 9 are based on 100 feet of
pipe. Actual requirements will be in direct proportion to the actual length of
piping.
NOTE: Table 9 assumes:
Liquid Temperature = 100 F
Suction Temperature = 35 F
Suction Superheat Temperature = 4 F
The approximate amount of refrigerant is therefore the sum of the values
determined from Table 8 and Table 9.
46
RTAA-SVX01A-EN
Installation — Remote Evaporator
Oil Charge Determination
The unit is factory charged with the amount of oil required by the system,
without the field-installed piping. The amount of additional oil required is
dependent upon the amount of refrigerant that is added to the system for the
field-installed piping.
Use the following formula to calculate the amount of oil to be added:
Pints of Oil (Trane Oil-31) =
lbs of refrigerant added for field-installed piping
100
From the example above, in which the weight of the additional refrigerant
added for the field-installed piping was 34.0 lbs (30.6 + 3.4), the amount of oil
to be added equals 0.34 pints (34.0/100) per circuit.
Example: Refrigerant Charge Computation
Determine the approximate amount of charge required for an RTAA 100 ton
unit with a remote evaporator that is located 75 feet away (i.e the actual
length of field-installed pipe is 75 feet for each suction line and liquid line).
Assume that the suction lines have been previously determined to be in.,
O.D. and the liquid lines are in. 1-1/8 O.D.
1. From Table 2g for a 50 ton
circuit requires:
= 73 lbs. R-22
2. From Table 2h for a 2-518
inch OD suction line:
75 feet x 4.5 feet
= 3.4 lbs. R-22
3. From Table 2h for a 1 118
inch OD liquid line:
75 feet x 40.8 feet
= 30.6 Ibs. R-22
4. Total R-22 charge per circuit:
Sum results of steps
1,2, and 3
= 107 Ibs. R-22 per circuit
5. Total R-22 charge per machine:
2 circuits x 107 Ibs.
= 214 Ibs. R-22 per machine
Table 9
Field-Installed Piping Charge
Lbs. R-22 per 100 ft.
Pipe O.D.
(inches)
Suction Line Liquid Line
1-1/8
0.78
40.8
1-3/8
1.2
62.2
1-5/8
1.7
88
2-1/8
2.9
153.1
2-5/8
4.5
236.1
3-1/8
6.4
—
Relief Valve Venting
All relief valve venting is the responsibility of the installing contractor.
The remote evaporators on chillers sold with this option utilize relief valves
installed in each circuit of the evaporator head. There is one relief valve per
circuit, and they must be vented to the outside of the building.
RTAA-SVX01A-EN
47
Installation — Remote Evaporator
The relief valves are 3/8” SAE flare connections. They have a 300 psig relief
setpoint, and relieve at 10.21 lba/min. The connection size and locations are
shown in the chiller's submittals. Refer to local codes for relief valve vent line
sizing information.
48
RTAA-SVX01A-EN
Installation — Electrical
General Recommendations
All wiring must comply with local and National Electric Codes. Minimum
circuit capacities and other unit electrical data is on the unit nameplate. See
the unit order specifications for actual electrical data. Electrical schematics
are shipped with the unit.
Typical wiring diagrams are in the back of this manual.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects
before servicing. Follow proper lockout/tagout procedures to
ensure the power cannot be inadvertently energized. For variable
frequency drives or other energy storing components provided by
Trane or others, refer to the appropriate manufacturer’s literature
for allowable waiting periods for discharge of capacitors. Verify
with an appropriate voltmeter that all capacitors have discharged.
Failure to disconnect power and discharge capacitors before
servicing could result in death or serious injury.
Note: For additional information regarding the safe discharge of
capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of
conductors. Failure to use copper conductors may result in
equipment damage.
Important!
Do not allow conduit to interfere with other components, structural
members or equipment. Control voltage (115V) wiring in conduit must
be separate from conduit carrying low voltage (<30V) wiring.
Caution: To prevent control malfunctions, do not run low voltage wiring
(<30V) in conduit with conductors carrying more than 30 volts.
RTAA-SVX01A-EN
49
Installation — Electrical
Table 10
Electrical Data
Unit Wiring
Unit Size
RTAA 70
RTAA 80
RTAA 90
RTAA 100
RTAA 110
RTAA 125
Motor Data
Rec Time
Rotated
Compressor
Fans (Ea)
Control
Delay or
Voltage MCA (2) MOP (1) RDE (3) Qty. (Ea) RLA (4) LRA (7) Qty. KW
FLA KW (6)
200/60
230/60
460/60
575/60
346/50
400/50
200/60
230/60
460/60
575/60
346/50
400/50
200/60
230/60
460/60
575/60
346/50
400/50
200/60
230/60
460/60
575/60
346/50
400/50
200/60
230/60
460/60
575/60
346/50
400/50
200/60
230/60
460/60
575/60
346/50
400/50
300
265
133
108
153
133
361
319
160
131
184
160
428
378
190
154
243
214
483
426
214
173
243
214
536
471
235
191
270
236
576
507
253
205
291
253
400
350
175
125
200
175
500
400
200
175
250
200
600
500
250
200
300
250
600
500
250
225
300
250
700
600
300
250
350
300
800
700
350
250
400
350
350
300
150
125
175
150
400
350
175
150
225
175
600
500
225
175
250
225
600
500
250
200
300
250
600
600
300
225
300
300
700
600
300
225
350
300
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
115/115
100/100
50/50
40/40
58/58
50/50
142/142
124/124
62/62
50/50
72/72
62/62
192/142
167/124
84/62
67/50
96/72
84/62
192/192
167/167
84/84
67/67
96/96
84/84
233/192
203/167
101/84
81/67
117/96
101/84
233/233
203/203
101/101
81/81
117/117
101/101
800/800
690/690
330/330
270/270
390/390
325/325
800/800
760/760
380/380
304/304
430/430
375/375
990/880
820/760
410/380
328/304
485/430
402/375
990/990
820/820
410/410
328/328
485/485
402/402
1190/990
1044/820
522/410
420/328
585/485
512/402
1190/990
1044/1044
522/522
420/420
585/585
512/512
8
8
8
8
8
8
8
8
8
8
8
8
9
9
9
9
9
9
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.1
5.0
2.5
2.2
2.7
2.5
5.1
5.0
2.5
2.2
2.7
2.5
5.1
5.0
2.5
2.2
2.7
2.5
5.1
5.0
2.5
2.2
2.7
2.5
5.1
5.0
2.5
2.2
2.7
2.5
5.1
5.0
2.5
2.2
2.7
2.5
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
(1) MOP - Maximum Overcurrent Protection - may be either type breaker (UL/CSA) or with circuit breakers (CSA only). MOP = 225 percent of the largest
compressor RLA plus 100 percent of the second compressor plus the sum of the condenser fans FLAs per NEC 440-22.
(2) MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of second compressor plus the sum of the condenser
fans FLAs per NEC 440-33.
(3) RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the
second compressor RLA and the sum the condenser fan FLAs.
(4) RLA -Rated Load Amps -rated in accordance with UL Standard 465.
(5) Local codes may take precedence.
(6) Control kw includes operational controls only. Does not include heat tapes.
(7) LRA - Locked Rotor Amps -based on full winding start units.
(8) VOLTAGE UTILIZATION RANGE:
Rated Voltage
Utilization Range
200/60
180-220
230/60
208-254
460/60
414-506
575/60
516-633
400/50
340-460
(9) 60 HZ UNITS - A 115/60/1, 15 amp. customer provided power connection is required to power the evaporator heat tape 420 watts
(10) 50 HZ UNITS - A separate 220/50/1 15 amp. customer provided power connection is needed to power evaporator heat tape 420 watts @ 220 volts.
50
RTAA-SVX01A-EN
Installation — Electrical
Table 11
Electrical Data - Pump Package Option
Unit Wiring
Motor Data
Rec Time
Fans
Rotated Pump Pump
Delay or
Comp(Ea)
(Ea)
Control
Unit Size Voltage HP
LRA (7) Qty KW FLA KW (6)
FLA MCA (2) MOP (1) RDE (3) Qty RLA (4)
3.1
136
175
150
2
50/50
330/330 8
1.0
2.5 0.75
RTAA 70 460/60 2
460/60
460/60
RTAA 80 460/60
460/60
460/60
460/60
RTAA 90 460/60
460/60
460/60
RTAA 100 460/60
460/60
460/60
RTAA 110 460/60
460/60
460/60
RTAA 125 460/60
460/60
460/60
3
5
2
3
5
7.5
3
5
7.5
3
5
7.5
3
5
7.5
3
5
7.5
4.1
6.6
3.1
4.1
6.6
10.3
4.1
6.6
10.3
4.1
6.6
10.3
4.1
6.6
10.3
4.1
6.6
10.3
137
139
163
164
166
170
194
196
200
218
221
224
239
242
246
256
259
263
175
175
200
225
225
225
250
250
250
300
300
300
300
300
300
350
350
350
150
175
200
200
200
200
225
225
225
250
250
350
300
300
300
300
300
300
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
50/50
50/50
62/62
62/62
62/62
62/62
84/62
84/62
84/62
84/84
84/84
84/84
101/84
101/84
101/84
101/101
101/101
101/101
330/330
330/330
380/380
380/380
380/380
380/380
410/380
410/380
410/380
410/410
410/410
410/410
522/410
522/410
522/410
522/522
522/522
522/522
8
8
8
8
8
8
9
9
9
10
10
10
10
10
10
10
10
10
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
(1) MOP - Maximum Overcurrent Protection - may be either type breaker (UL/CSA) or with circuit breakers (CSA only). MOP = 225 percent of the largest
compressor RLA plus 100 percent of the second compressor plus the sum of the condenser fans FLAs per NEC 440-22.
(2) MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of second compressor plus the sum of the condenser
fans FLAs per NEC 440-33.
(3) RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the
second compressor RLA and the sum the condenser fan FLAs.
(4) RLA -Rated Load Amps -rated in accordance with UL Standard 465.
(5) Local codes may take precedence.
(6) Control kw includes operational controls only. Does not include heat tapes.
(7) LRA - Locked Rotor Amps -based on full winding start units.
(8) VOLTAGE UTILIZATION RANGE:
Rated Voltage
Utilization Range
200/60
180-220
230/60
208-254
460/60
414-506
575/60
516-633
400/50
340-460
(9) 60 HZ UNITS - A 115/60/1, 15 amp. customer provided power connection is required to power the evaporator heat tape 420 watts
(10) 50 HZ UNITS - A separate 220/50/1 15 amp. customer provided power connection is needed to power evaporator heat tape 420 watts @ 220 volts.
Installer-Supplied Components
All wiring must comply with local codes and the National Electrical Code. The
installing (or electrical) contractor must provide and install the system interconnecting wiring, as well as the power supply wiring. It must be properly
sized and equipped with the appropriate fused-disconnect switches. The type
and installation location(s) of the fused-disconnects must comply with all
applicable codes.
The installer must provide the following components if not ordered with the
unit:
• Power supply wiring (in conduit) for all field-wired connections.
•
All control (interconnecting) wiring (in conduit) for field supplied devices.
•
Fused-disconnect switches.
Remote Evaporator Only:
• Control wiring between the outdoor unit and the evaporator terminal box.
RTAA-SVX01A-EN
51
Installation — Electrical
Power Supply Wiring
All power supply wiring must be sized and selected accordingly by the project
engineer in accordance with the National Electrical Code.
All wiring must comply with local codes and the National Electrical Code. The
installing (or electrical) contractor must provide and install the system interconnecting wiring, as well as the power supply wiring. It must be properly
sized and equipped with the appropriate branch circuit protection. The type
and installation location(s) must comply with all applicable codes.
Cut holes for the appropriately-sized wiring conduits in the lower right side of
the power connection panel. The wiring is passed through these conduits and
connected to the terminal blocks or optional unit-mounted disconnect or
circuit breaker.
To provide proper phasing of 3-phase input, make connections as shown in
the Field Wiring diagrams and as stated on the yellow WARNING label in the
starter panel. For additional information on proper phasing, refer to “Unit
Voltage Phasing”. Proper equipment ground must be provided to each ground
connection in the panel.
Control Power Supply
The unit is equipped with the control power transformer. It is not necessary
to provide control power voltage to the unit.
Heat Tape Power Supply (Packaged Units Only)
NOTE: Units with the Remote Evaporator option do not have heat tape.
The evaporator shell is insulated from ambient air and protected from freezing
temperatures by a thermostatically-controlled heat tape. Whenever the
chilled water temperature drops to approximately 37 F, the thermostat
energizes the heat tape. The heat tape will protect the evaporator from
ambient temperatures down to -20 F
Provide an independent power source (115V, 15 amp), with a fuse disconnect.
The heat tape is factory wired back to the unit control panel. Customer
connections are made on terminal strip 1TB3, terminals 16 and 17.
Water Pump Power Supply
Provide power supply wiring with fused-disconnect for the chilled water
pump(s) unless unit is equipped with optional pump package.
Interlock Wiring
CAUTION
Evaporator Damage!
The chiller water pump must operate for a minimum of one
minute after the UCM receives a command through the external
Auto/Stop input to shut down the chilled water system. Do not
use the proof of chiller water flow interlock (1U1 TB3-1 and -2) by
itself as the normal means of terminating chiller operation. Failure
to continue pump operation for one minute after unit shut down
may result in evaporator freeze up.
Normally, when the compressors are terminating a cycle (when chiller Stop
key, loss of load, low ambient run inhibit, or external Auto/Stop), the controller
will initiate the “Run: UNLOAD” mode. This operating mode commands the
compressors to their complete unloaded position, which takes about 1/2
52
RTAA-SVX01A-EN
Installation — Electrical
minute. This will allow the compressor to be totally unloaded for the next
start-up. If only the proof of chilled water flow interlock is used, the chiller will
shut down on an immediate (non-friendly) shutdown and initiate an automatic
reset diagnostic.
Figure 25 shows a typical interlock of an RTAA chiller. There are three points
(six wires) on the chiller that are required to be connected.
1. External Auto/Stop (Terminals 1U1 TB3-3 and -4). This input would be
supplied by the field. A contact closure would start the chiller water pump
and chiller, via the UCM pump control contacts. Opening the contact
would put the operating compressors into the “RUN:UNLOAD” mode
and initiate a timing period (1 to 30 minutes, adjustable through the Clear
Language Display). This will delay termination of chilled water pump operation via the UCM pump control contacts. Examples of the input at terminals 1U1 TB3-3 and -4 would be a time clock, ambient
thermostat, building automation system, etc.
2. UCM Pump Control Contacts (Terminals 1U1 TB4-8 and -9). This output is
a set of contacts that will close and start the chilled water pump when
the external auto/stop contacts are closed. When the contacts are
opened, 1 to 30 minutes later (adjustable through the Clear Language
Display) the UCM pump contacts open.
3. Proof of Chilled Water Flow Interlock (Terminals 1U1 TB3-1 and -2). Contact closure between the terminals indicates proof of chilled water flow.
Examples of this would be a pump starter auxiliary contact, flow switch,
differential pressure switch, or a contact from a building automation system (see Chilled Water Flow Switch in the Water Piping section of this
manual). Opening of this contact would shutdown the chiller and initiate
an automatic reset diagnostic indicating loss of chilled water flow.
NOTE: Steps 2 and 3 are completed at the factory if unit is equipped with
optional pump package.
Figure 25
Typical RTAA Chiller Interlock
RTAA-SVX01A-EN
53
Installation — Electrical
Alarm/Running/Maximum Capacity Outputs
Terminals 1 to 7 on terminal strip TB4 of the 1U1 board provide a variety of
contact outputs. These are dependent upon the setting of Programmable
Relay Setup (“Service Setting Menu”) and its relationship to diagnostics,
compressors operating and the system operating at full capacity.
As shown in Figure 26, there are three relays. Relay 1 has SPDT contacts.
Relays 2 and 3 have SPST normally-open contacts. The relays can provide
three different output configurations, as shown in Table 12, and each configuration offers four choices as to how the alarm relay is to respond to a set of
diagnostics.
Table 13 shows the twelve settings available in Programmable Relay Setup
(“Service Settings Menu”) and the diagnostics which are issued for each set
of conditions.
Table 12
Alarm/Running/Maximum Capacity Relay Output Configurations
Relay Output Configuration
1:
RLY 1
RLY 2
RLY 3
= Alarm
= Compressor Running
= Maximum Capacity
2:
RLY 1
RLY 2
RLY 3
= Circuit 1 Alarm
= Circuit 2 Alarm
= Maximum Capacity
3:
RLY 1
RLY 2
RLY 3
= Alarm
= Circuit 1 Running
= Circuit 2 Running
Alarm/Running/Maximum Capacity Indicator Wiring
If the optional remote Alarm/Running/ Maximum Capacity contacts are used,
provide electrical power, 115 VAC (contact load not to exceed 1150 VA inrush,
115 VA sealed), with fused-disconnect to a customer-furnished remote
device. Also provide proper remote device ground connections.
To install the available remote running and alarm indication, the installer must
provide leads 525 thru 531 from the panel to the proper terminals of terminal
strip 1U1 TB4 on the UCM. Refer to the field diagrams which are shipped
with the unit.
54
RTAA-SVX01A-EN
Installation — Electrical
7%8
5HOD\
.
5HOD\
.
5HOD\
.
+ 1
&XVWRPHUSURYLGHG
9$&SRZHU
0D[IXVHVL]H
DPSV
Figure 26
Alarm/Running/Maximum Capacity Contact Outputs
Table 13
Alarm/Running/Maximum Capacity Menu Settings
Diagnostics that the Alarm
Relay(s) is Active
Programmable
Relay Setup
Setting (Service
Setting Menu)
Relays Output
Configuration
(Table 12)
MMR/
CMR diag.
MAR/
CAR diag.
IFW
1
1
YES
NO
NO
2
1
YES
YES
NO
3
1
YES
YES
YES
4
1
YES
NO
YES
5
2
YES
NO
NO
6
2
YES
YES
NO
7
2
YES
YES
YES
8
2
YES
NO
YES
9
3
YES
NO
NO
10
3
YES
YES
NO
11
3
YES
YES
YES
12
3
YES
NO
YES
Notes:
MMR = Machine Manual Reset
CMR = Circuit Manual Reset
MAR = Machine Auto Reset
CAR = Circuit Auto Reset
IFW = Informational Warnings
RTAA-SVX01A-EN
55
Installation — Electrical
Low Voltage Wiring
The remote devices described below require low voltage wiring. All wiring to
and from these remote input devices to the UCM must be made with
shielded, twisted-pair conductors. Be sure to ground the shielding only at the
Clear Language Display. See Wiring Section for the recommended conductor
sizes.
Emergency Stop (Normal Trip)
The Clear Language Display provides auxiliary control for a customer
specified/ installed latching tripout. When this customer-furnished remote
contact (5K18) is provided, the chiller will run normally when the contact is
closed. When the contact opens, the unit will trip off on a manually resettable
diagnostic. This condition requires manual reset at the chiller switch on the
front of the Clear Language Display.
To connect, first remove the jumper located between terminals 3 and 4 of
1U1TB1 Connect low voltage leads 513 and 514 to those terminals. Refer to
the field diagrams which are shipped with the unit.
Silver or gold-plated contacts are recommended. These customer-furnished
contacts must be compatible with 12 VDC, 45 mA resistive load.
External Circuit Lockout — Circuit #1
The UCM provides for auxiliary control via a customer specified or installed
contact closure, for individual operation of Circuit #1. If the contact is closed,
the refrigerant circuit will not operate. The refrigerant circuit will run normally
when the contact is opened. This feature is used to restrict total chiller
operation, eg. during emergency generator operations.
External circuit lockout will only function if External Circuit Lockout (Service
Setting Menu) is enabled.
These customer-supplied contact closures must be compatible with 12 VDC,
45 mA resistive load. Silver or gold plated contacts are recommended.
To install, cut, strip and wire-nut existing wire loop #W7 on the P43 connector
of the 1U4 module to low voltage leads 45A and 45B. Connections are shown
in the field diagrams which are shipped with the unit.
External Circuit Lockout — Circuit #2
The UCM provides for auxiliary control via a customer specified or installed
contact closure, for individual operation of Circuit #2. If the contact is closed,
the refrigerant circuit will not operate. The refrigerant circuit will run normally
when the contact is opened. This feature is used to restrict total chiller
operation, eg. during emergency generator operations.
External circuit lockout will only function if External Circuit Lockout (Service
Setting Menu) is enabled.
These customer-supplied contact closures must be compatible with 12 VDC,
45 mA resistive load. Silver or gold plated contacts are recommended.
To install, cut, strip and wire-nut existing wire loop #4 on the P53 connector
of the 1U5 module to low voltage leads 46A and 46B. Connections are shown
in the field diagrams which are shipped with the unit.
Ice Making Option
Ice Machine Control (Operator Settings Menu) must be Enabled. The UCM
provides auxiliary control for a customer specified/installed contact closure
for ice making. When contact (5K20) is provided, the chiller will run normally
when the contact is open. Upon contact closure, the UCM will initiate an icebuilding mode, in which the unit runs fully loaded at all times. Ice-building
shall be terminated either by opening the contact or based on the entering
evaporator water temperature setting under Active Ice Termination Set-point
(Chiller Report Menu). The UCM will not permit the ice-building mode to be
56
RTAA-SVX01A-EN
Installation — Electrical
reentered until the unit has been switched out of ice-building mode (open
5K20 contacts) and then switched back into ice building mode (close 5K20
contacts).
In ice-building, the current setpoint will be set at 120%. For example, if the
Front Panel or External Current Limit setpoint is set to 80%, in ice-building
the Active Current Limit is 120%.
If, while in ice-building mode, the unit gets down to the freezestat setting
(water or refrigerant), the unit will shut down on a manually resettable
diagnostic, just as in normal operation.
Connect leads 501 and 502 from 5K20 to the proper terminals 1U2TB1 -1 and
-2. Refer to the field diagrams which are shipped with the unit.
Silver or gold-plated contacts are recommended. These customer furnished
contacts must be compatible with 12 VDC, 45 mA resistive load.
External Chilled Water Setpoint (CWS)
This option allows the external setting of the Chilled Water Setpoint,
independent of the Front Panel Chilled Water Setpoint, by one of three
means:
1. A remote resistor/potentiometer input (fixed or adjustable).
2. An isolated voltage input 2-10 VDC.
3. An isolated current loop input 4-20 mA.
To enable external setpoint operation, “External Chilled Water Setpoint
“(Operator Settings Menu) should be set to “E” using the Clear Language
Display.
7%
0RGXOH8
3RWHQWLRPHWHU
5HVLVWRU
7%
0RGXOH8
Figure 27
1.
Resistor and Potentiometer
Arrangement External Chilled Water Setpoint
Remote Resistor/Potentiometer Input (fixed or adjustable).
Connect the remote resistor and/or potentiometer to terminals 1TB1-3 and
TB1-5 of Options Module 1U2, as shown in Figure 27.
For units with 40 to 60 F LCWS range, a field-furnished 25 Kohm linear taper
potentiometer (±10%) and a fixed 5.6 Kohm (±10%) 1/4 Watt resistor should
be used.
For units with 20 F to 39 F LCWS range, a field-furnished 25 Kohm linear
taper potentiometer (±10%) and a fixed 15 Kohm (±10%) 1/4 Watt resistor
should be used.
If the potentiometer is to be remotely mounted, it and the resistor must be
connected to the UCM prior to mounting. Then, with the Clear Language
Display showing “Active Chilled Water Setpoint” (Chiller Report Menu), the
Clear Language Display can be used to calibrate the positions of the potentiometer to correspond with the desired settings for the leaving water temperature. External resistor input values for various chilled water setpoints are
shown in Table 14.
RTAA-SVX01A-EN
57
Installation — Electrical
2. Isolated 2-10 VDC Voltage Source Input.
Set DIP Switch SW1-1 of Options Module 1U2 to “OFF”. Connect the voltage
source to terminals TB1-4 (+) and TB1-5 (-) on Options Module IU2. CWS is
now based on the following equation:
CW Setpoint °F = (VDC x 125) - 16.25
Sample values for CWS vs. VDC signals are shown in Table 14.
Minimum setpoint =
Maximum setpoint =
Maximum continuous input voltage =
Input impedance (SW1-1 on) =
0 F(2.0 VDC input)
65 F (9.4 VDC input)
15 VDC
40.1 Kohms
3. Isolated 4-20 mA Current Source Input.
Set DIP Switch SW1-1 of Options Module 1U2 to “ON”. Connect the current
source to terminals TB1-4 (+) and TB1-5 (-). CWS is now based on the
following equation:
Setpoint °F = (mA x 4.0625) - 16.25
Sample values for CWS vs., mA signals are shown in Table 14.
Minimum setpoint =
Maximum setpoint =
Maximum continuous input voltage =
Input impedance (SW1-1 off) =
0F(40mA)
65 F (18.8 mA)
30 mA
499 ohms
NOTE: The negative terminal TB1 -5 is referenced to the UCM chassis
ground. To assure correct operation, 2-10 VDC or 4-20 mA signals must be
isolated or “floating” with respect to the UCM chassis ground.
Table 14
Input Values Vs. External Chilled Water Setpoint
Inputs
58
Resistance (Ohms)
Current (ma)
Voltage (Vdc)
Resulting Chilled
Water Setpoint (F)
944330
4.0
2.0
0.0
686092
5.2
2.6
5.0
52946
6.5
3.2
10.0
42434
7.7
3.9
15.0
34889
8.9
4.5
20.0
29212
10.2
5.1
25.0
24785
11.4
5.7
30.0
21236
12.6
6.3
35.0
18327
13.8
6.9
40.0
15900
15.1
7.6
45.0
13844
16.3
8.2
50.0
12080
17.5
8.8
55.0
10549
18.8
9.4
60.0
9050
20.0
10.0
65.0
RTAA-SVX01A-EN
Installation — Electrical
External Current Limit Setpoint (CLS)
This option allows the external setting of the Current Limit Setpoint,
independent of the Front Panel Current Limit Setpoint, by one of three
means:
1. A remote resistor/potentiometer input (fixed or adjustable).
2. An isolated voltage input 2-10 VDC.
3. An isolated current loop input 4-20 mA.
To enable external Current Limit Setpoint operation, “External Current Limit
Setpoint” (Operator Settings Menu), should be set to “E” using the Clear
Language Display.
1. Remote Resistor/Potentiometer Input.
To cover the entire range of Current Limit Setpoints (40 to 120%), a field
furnished 50 Kohm log taper potentiometer (±10%) and a fixed 820 ohm
(±10%) 1/4 Watt resistor should be wired in series and connected to
terminals TB1-6 and TB1-8 of options module 1U2, as shown in Figure 28.
If the potentiometer is to be remotely mounted, it and the resistor must be
connected to the UCM prior to mounting. Then, with the Clear Language
Display showing “Active Current Limit Setpoint” (Chiller Report Menu), the
Clear Language Display can be used to calibrate the positions of the potentiometer to correspond with the desired settings for the current limits. External
resistor input values for various current limit setpoints are shown in Table 15.
.2KP/RJ&&:3RWHQWLRPHWHU
&&:
2KPVî:
7%
0RGXOH8
7%
0RGXOH8
Figure 28
RTAA-SVX01A-EN
Resistor and Potentiometer Arrangement for External Current
Limit Setpoint
59
Installation — Electrical
Table 15
Input Values Vs. External Current Limit Setpoint
Inputs
Resistance (Ohms)
Current (ma)
Voltage (Vdc)
Resulting Chilled
Water Setpoint (%RLA)
49000
4.0
2.0
40
29000
6.0
3.0
50
19000
8.0
4.0
60
13000
10.0
5.0
70
9000
12.0
6.0
80
6143
14.0
7.0
90
4010
16.0
8.0
100
2333
18.0
9.0
110
1000
20.0
10.0
120
2. 2-10 VDC Voltage Source Input.
Set DIP Switch SW1-2 of Options Module 1U2 to “OFF”. Connect the voltage
source to terminals TB1-7 (+) and TB1-8 (-) of Options Module 1U2. CLS is
now based on the following equation:
CL Setpoint% = (VDC x 10) + 20
Sample values for CLS vs. VDC signals are shown in Table 15.
Minimum setpoint =
Maximum setpoint =
Maximum continuous input voltage =
Input impedance (SW1-1 on) =
40% (2.0 VDC input)
120% (10.0 VDC input)
15 VDC
40.1 Kohms
3. 4-20 mA Current Source Input.
Set DIP Switch SW1-2 of Options Module 1U2 to “ON”. Connect the current
source to terminals TB1-7 (+) and T131-8 (-) of Options Module 1U2. CLS is
now based on the following equation:
CL Setpoint% = (mA x 5) + 20
Sample values for CLS vs. mA signals are shown in Table 15.
Minimum setpoint =
Maximum setpoint =
Maximum continuous input voltage =
Input impedance (SW1-1 on) =
40% (0 mA)
120% (20.0 mA)
30 mA
499 ohms
NOTE: The negative terminal TB1-8 is referenced to the UCM chassis
ground. To assure correct operation, 2-10 VDC or 4-20 mA signals must be
isolated or “floating” with respect to the UCM chassis ground.
Optional Bidirectional Communications Link (BCL)
This option allows the Clear Language Display in the control panel to
exchange information (eg. operating setpoints and Auto/Standby commands)
with a higher level control device, such as a Tracer, a multiple-machine
60
RTAA-SVX01A-EN
Installation — Electrical
controller or a remote display panel. A shielded, twisted-pair connection
establishes the bidirectional communications link between the unit control
panel and the Tracer, multiple-machine controller or remote display panel.
NOTE: The shielded, twisted-pair conductors must run in a
separate conduit.
Field wiring for the communication link must meet the following
requirements:
1. All wiring must be in accordance with the NEC and local codes.
2. Communication link wiring must be shielded, twisted-pair wiring (Belden
8760, or equivalent).
3. The maximum total wire length for each communication link is 5,000 feet.
4. The communication link cannot pass between buildings.
5. All UCM's on the communication link can be connected in a “daisy chain”
configuration.
Communication Link Connection Procedure
1.
Refer to the Tracer installation literature to determine proper communication link termination connections at the Tracer unit.
2. Refer to the Remote Clear Language Display installation procedure in
this manual.
3. Connect the shield of the communication link wiring to the designated
shield terminal at the Tracer unit.
4. Connect leads 561 and 562 from the proper terminals of 1U2TB2 on the
UCM to the Tracer. There is no polarity requirement for this connection.
5. At the UCM, the shield should be cut and taped to prevent any contact
between the shield and ground.
NOTE: On multiple-unit installations, splice the shielding of the two twistedpairs that come into each UCM in the “daisy chain” system. Tape the spliced
connections to prevent any contact between the shield and ground. At the
last UCM in the chain, the shield should be cut and taped off.
6. For unit ICS address selection, see ICS Address (Service Settings Menu).
LonTalk Communication Interface (LCI-C)
The Tracer LCI-C interface acts as a translator between Trane's IPC (InterProcessor Communication) and Echelon's LonTalk® communications protocol
(ANSI/EIA/CEA 709.1). This allows the chiller to communicate with building
automation systems which also communicate using the LonTalk® protocol.
The LonTalk® communications protocol also allows for peer to peer communications between controllers so they can share information. Communicated
setpoints have priority over locally wired inputs to the controller unless the
controller is set to the "Local" control mode.
The LCI-C module provides connectivity to Trane's Rover® service tool for
proper configuration of the LCI-C module.
NOTE: LonTalk® communication links are not polarity sensitive.
1.
RTAA-SVX01A-EN
Connect BAS leads to J3-1,2 or J3-3,4.
61
Installation — Electrical
Remote Clear Language Display Installation Procedure
The Remote CLD is intended for indoor use and is not weatherproof. It is
mounted in a molded-plastic display box with a molded rubber keypad.
Although this is not the same as the membrane keypad of the unit's CLD, the
key locations and labels are identical.
Field wiring for the communication link must meet the following requirements:
1. All wiring must be in accordance with NEC and all local codes.
2. Communication link wiring must be 14 AWG shielded, twisted pair wire
(Belden 8760, or equivalent).
3. The communication link must not exceed 5,000 feet for each link.
4. The communication link must not pass between buildings.
Remote CLD Mounting
All mounting hardware (tools, screws, etc.) is to be field supplied. Figure 29
shows the mounting holes in the back of the Remote OLD panel. Also shown
are the electrical access knockouts at the bottom and top of the panel.
Remove the knockouts that will be used for wire entry, prior to mounting the
panel.
NOTE: On the back of the panel is a knockout for an electrical outlet box, if
one is to be used.
Prior to mounting the panel, the actual microprocessing board needs to be
carefully removed and set aside. To remove the board, open the protective
door that covers the keypad. Remove the cover plate at the bottom of the
keypad, by loosening the screw on the cover plate.
After removing the cover plate, remove the four screws that secure the
keypad (one in each corner). The keypad can now be lifted out of the display
box.
Attach the display box to the mounting surface with screws through the
mounting hole and two mounting slots, shown in Figure 30.
NOTE: If an electrical box is to be used, attach the display box with screws
through the four mounting slots around the knockout.
The top of the display box is marked “TOP”. Note the position of the box
before mounting it to the surface. With the box in the desired position against
the mounting surface, mark the location of the mounting holes.
Remove the box and drill the necessary holes in the surface. Put the display
box back in position and secure it to the mounting with the required screws.
62
RTAA-SVX01A-EN
Installation — Electrical
The microprocessing board can now be replaced in the display box with its
four attaching screws.
Figure 29
Remote CLD Panel Mounting Holes and Electrical Access Knockouts
Remote CLD Panel Wiring
The Remote CLD requires a 24 VAC power source and a shielded, twistedpair wire between the panel and the Clear Language Display. See Figure 30.
As shown in Figure 31, the wire runs from terminals J3A-1(+) and J3A-2(-) in
the unit's buffer module (1U7) to terminals J1(+) and J1(-) in the Remote CLD.
Be sure that one lead is connected to the (+) terminal at each end and the
other lead is connected to the (-) terminal at each end.
For units #2, #3 and #4 wire similarly as shown in Figure 31.
Do not run the shielded, twisted-pair wire in a conduit that also contains
circuits of greater than 30 volts. Attach the shield to a grounding lug in the
unit's control panel. Cut and tape the shield at the Remote CLD panel, as
shown in Figure 30.
RTAA-SVX01A-EN
63
Installation — Electrical
-AX
#UT BACK BARE
SHIELD WIRE
7RAP TAPE AROUND
EXPOSED FOIL SHIELD
AND BARE SHIELD WIRE
Figure 30
#ONNECT LEADS TO
2EMOTE #,$ 0ANEL
Shielded, Twisted Pair Communication LInk at the
Remote CLD Panel
Connect the 24 VAC power supply to terminals J2A and J2B in the Remote
CLD panel. The polarity of the power source is not a concern, but the power
source must be grounded to terminal J2Gnd.
NOTE: A field-supplied Class 2, 24 VAC, 40 VA transformer can be used as a
power supply for the Remote CLD panel.
NOTE: Both a Remote CLD and a Tracer unit can be connected to the UCM.
ICS Address Setting
The setting of the ICS address for the Remote CLD is not necessary.
Multiple Unit Operation
In a multiple unit configuration, the Remote CLD Panel has the capability to
communicate with up to four units. Each unit requires a separate communication link with the Remote CLD panel.
Terminal strip TB4 is used to wire in the second, third and fourth units to the
Remote CLD. TB4 is labeled as shown below:
Terminals 1-3 are for the second unit.
Terminals 4-6 are for the third unit.
Terminals 7-9 are for the fourth unit.
64
RTAA-SVX01A-EN
Installation — Electrical
Figure 31
RTAA-SVX01A-EN
Remote Display Panel Interconnecting Wiring
65
Operating Principles
This section describes the mechanical operating principles of Series R
air-cooled chillers equipped with microcomputer-based control systems.
The 70 - 125-ton Model RTAA units are dual-compressor, helical-rotary type
air-cooled liquid chillers. The basic components of an RTAA unit are:
• Clear Language Display.
•
Unit Control Modules (UCM).
•
Unit-mounted panel.
•
Helical-rotary compressor.
•
Direct Expansion evaporator.
•
Air-cooled condenser.
•
Oil supply system (hydraulic and lubrication).
•
Interconnecting piping.
Refrigeration (Cooling) Cycle
Cycle Description
Figure 32 represents the refrigeration system and control components.
Vaporized refrigerant leaves the evaporator and is drawn into the compressor.
Here it is compressed and leaves the compressor as a mixture of hot gas and
oil (which was injected during the compression cycle).
The mixture enters the oil separator at the in/out cap. The separated oil flows
to the bottom of the separator, while the refrigerant gas flows out the top and
passes on to the tubes in the condensing coils. Here circulating air removes
heat from the refrigerant and condenses it.
The condensed refrigerant passes through the electronic expansion valve and
into the tubes of the evaporator. As the refrigerant vaporizes, it cools the
system water that surrounds the tubes in the evaporator.
66
RTAA-SVX01A-EN
Operating Principles
&RQGHQVHU
(YDSRUDWRU
Figure 32
1.
RTAA Refrigeration System and Control Components
Discharge Service Valve
2. Oil Separator
3. 1/4" Angle Valve
9. Subcooler
10. Low Pressure Switch
11. Liquid Line Service Valve
(Backseat Port Upstream)
12. Schrader Valve
13. Filter/Dryer
4. Oil Cooler
5. Quick Connect Shutoff
Valve or Angle Valve
6. Oil Temperature Sensor
14. Sight Glass
7. Condenser
8. Saturated Condenser Rfgt.
Temp Sensor
15. Electronic Expansion Valve
16. 1/4" Angle Valve
17. Saturated Evaporator Rfgt.
Temp. Sensor
18. Relief Valve
19. Compressor Suction Rfgt. Temp
Sensor
20. Suction Service Valve
21. Evaporator Entering Water
Temp. Sensor
22. Evaporator Leaving Water
Temp. Sensor
23. Entering Water Connection
24. Leaving Water Connection
Compressor Description
The compressors used by the Model RTAA Series “R” Air-cooled chiller
consists of two distinct components: the motor and the rotors.
Compressor Motor
A two-pole, hermetic, squirrel-cage induction motor (3600 rpm) directly drives
the compressor rotors. The motor is cooled by suction refrigerant gas from
the evaporator, entering the end of the motor housing through the suction
line.
RTAA-SVX01A-EN
67
Operating Principles
Compressor Rotors
The compressor is a semi-hermetic, direct-drive helical rotary type
compressor. Each compressor has two rotors - “male” and “female” - which
provide compression. See Figure 33 The male rotor is attached to, and driven
by, the motor, and the female rotor is, in turn, driven by the male rotor.
Separately housed bearing sets are provided at each end of both rotors.
The helical rotary compressor is a positive displacement device. The refrigerant from the evaporator is drawn into the suction opening at the end of the
motor barrel, through a suction strainer screen, across the motor, and into the
intake of the compressor rotor section. The gas is then compressed and
discharged directly into the discharge line.
There is no physical contact between the rotors and compressor housing.
The rotors contact each other at the point where the driving action between
the male and female rotors occurs. Oil is injected along the top of the
compressor rotor section, coating both rotors and the compressor housing
interior. Although this oil does provide rotor lubrication, its primary purpose is
to seal the clearance spaces between the rotors and compressor housing.
A positive seal between these internal parts enhances compressor efficiency
by limiting leakage between the high pressure and low pressure cavities.
Capacity control is accomplished by means of two unloader valve assemblies
in the rotor section of the compressor. The female rotor valve is a twoposition valve and the male valve is an infinitely variable position valve. See
Figure 33.
6FKUDGHU9DOYH
0DOH8QORDG
6ROHQRLG9DOYH
0DOH/RDG
6ROHQRLG
9DOYH
)URP2LO&RROHU
4XLFN&RQQHFW6KXWRII
9DOYHRU$QJOH9DOYH
6XFWLRQ
6FKUDGHU
9DOYH
6XFWLRQ
0RWRU
'LVFKDUJH
3UHVVXUH
0DOH
0DVWHU
2LO9DOYH
)HPDOH
6XFWLRQ
,QWHJUDWHG
2LO)LOWHU
7R5RWRU
2LO,QVSHFWLRQ
'LVFKDUJH
3UHVVXUH
6FKUDGHU
9DOYH
Figure 33
68
)HPDOH
8QORDGHU
6ROHQRLG9DOYH
6FKUDGHU
9DOYH
RTAA Refrigerant and Oil Diagram
RTAA-SVX01A-EN
Operating Principles
Compressor load capacity is determined by the positions of the unloader
valves. They divert refrigerant gas from the rotors to the compressor suction,
thus unloading the compressor. This varies the compressor capacity to match
the load and reduces the KW draw of the compressor motor.
The two-position female unloader will fully open or fully close a port on the
rotor housing, at the discharge end of the female rotor. This relieves the
refrigerant gas to suction and unloads the compressor. The female unloader
valve is the first stage of loading after the compressor starts and the last
stage of unloading before the compressor shuts down.
The modulating male unloader valve opens or closes ports in the rotor
housing along the side of the male rotor. It can move to a more loaded
(closed) position after the female unloader valve is in the loaded position or
can relieve refrigerant gas to suction to unload the compressor.
Compressor Loading Sequence
When there is a call for chilled water, the UCM will start the compressor
which has the least number of starts. If the first compressor cannot satisfy
the demand, the UCM will start the other compressor and then balance the
load on both compressors by pulsing the load/unload solenoids.
The load on the compressors will be kept in balance, as load fluctuates, until
the demand for chilled water is reduced to a level that can be handled by one
compressor. At this time, the UCM will drop off the compressor that has the
greatest number of operating hours and will adjust the load on the other
compressor, as required.
Oil System Operation
Overview
Oil that collects in the bottom of the oil separator is at condensing pressure
during compressor operation; therefore, oil is constantly moving to lower
pressure areas. Refer to Figure 33.
As the oil leaves the separator, it passes through the oil cooler at the top of
the condensing coils. It then goes through the service valve and filter. At this
point, some of the oil is used to control the slide valve movement in the
compressor, via the male load/unload solenoids. The remaining oil passes
through the master oil valve and performs the functions of compressor
bearing lubrication and compressor oil injection.
If the compressor stops for any reason, the master oil valve closes, isolating
the oil charge in the separator and oil cooler during “off” periods. The master
oil valve is a pressure activated valve. Discharge pressure off the rotors, that
is developed when the compressor is on, causes the valve to open.
To ensure proper lubrication and minimize refrigerant condensation in the
compressor, a heater is mounted on the bottom of the compressor housing.
A signal from the UCM energizes this heater during the compressor “Off”
cycle to keep refrigerant from condensing in the compressor. The heater
element is continuously energized when the compressor is not running.
Oil Separator
The oil separator consists of a vertical tube, joined at the top by the refrigerant discharge line from the compressor. The discharge line is essentially
tangential to the tube. This causes the refrigerant to swirl in the tube and
throws the oil to the outside, where it collects on the walls and flows to the
bottom. The compressed refrigerant vapor, stripped of oil droplets, exits out
the top of the oil separator and is discharged into the condensing coils.
The oil separators on chillers with the remote evaporator option incorporate
heaters to prevent refrigerant migration when the machine is off.
RTAA-SVX01A-EN
69
Operating Principles
Compressor Bearing Oil Supply
Oil is injected into the bearing housings located at each end of both the male
and female rotors. Each bearing housing is vented to compressor suction, so
that oil leaving the bearings returns through the compressor rotors to the oil
separator.
Compressor Rotor Oil Supply
Oil flows through this circuit directly from the master oil valve, through the oil
filter to the top of the compressor rotor housing. There it is injected along the
top of the rotors to seal clearance spaces between the rotors and the
compressor housing and to lubricate the rotors.
Female Unloader Valve
The position of the female unloader valve determines compressor capacity.
Its position is dependent on whether the backside of the female unloader
valve is exposed to the compressor discharge or suction pressure. See
Figure 33.
The female unloader valve solenoid receives a constant signal from the UCM,
based on system cooling requirements. To load the compressor, the female
unloader valve solenoid is energized and discharge pressure is passed
through the normally-closed port and into the cylinder. This pushes the female
unloader valve closed.
To unload the compressor, the female unloader valve solenoid is de-energized
and the discharge pressure is relieved to the suction of the compressor. The
female unloader valve retracts into the cylinder and the compressor is
unloaded.
Just prior to a normal compressor shut-down, the male unload valve solenoid
is energized and the slide valve moves to the fully-unloaded position, so the
unit always starts fully unloaded.
Oil Filter
Each compressor is equipped with a replaceable-element oil filter. The filter
removes any impurities that could foul the solenoid valve orifices and
compressor internal oil supply galleries. This also prevents excessive wear of
compressor rotor and bearing surfaces. Refer to the maintenance portion of
this manual for recommended filter element replacement intervals.
Condenser Fan Staging
The fans on the RTAA 70 -125 Ton units are staged by logic in the UCM. The
UCM takes several different pressures and temperatures into account, to
determine when fans should be added or subtracted. Input from the outside
air temperature sensor, the saturated condensing refrigerant temperature
sensor, and the saturated evaporator refrigerant temperature sensor are
monitored to determine fan staging.
The number of fans activated at startup is dependant upon the outdoor air
temperature. Figure 34 shows fan activation at different temperatures.
During normal operation, the micro uses PID control to maintain a 70±5 psid
between the condensing pressure and the evaporator pressure. Through the
use of algorithm logic, a fan will be added if the pressure differential is greater
than 75 psid and the fan inverter is at maximum speed.
A “Low Differential Pressure” diagnostic will take the circuit off-line if the
pressure differential falls below 40 psid for more than two minutes.
A “High Differential Pressure” diagnostic will take the circuit off-line if the
pressure differential increases to 350 psid or greater. This diagnostic can also
be produced if the pressure differential increases to the range between 320
70
RTAA-SVX01A-EN
Operating Principles
B
!
&21752/3$1(/
psid and 349 psid. The UCM will allow the unit to remain on-line if there is no
increase in pressure for a one hour period. Otherwise, the unit will trip off-line
and display the “High Differential Pressure” diagnostic.
)$1&,5&8,7
127(6
)DQ2Q
)$1&,5&8,7
&21752/3$1(/
!
B
)$1&,5&8,7
)$1&,5&8,7
!
B
&21752/3$1(/
287'225$,57(03)
)DQ2II
)$1&,5&8,7
!
B
&21752/3$1(/
)$1&,5&8,7
)$1&,5&8,7
&21752/3$1(/
)$1&,5&8,7
)$1&,5&8,7
)$1&,5&8,7
Figure 34
Fan State at Circuit Startup
RTAA-SVX01A-EN
71
Controls Interface
The exclusive Trane Adaptive Control logic with the Clear Language Display is
comprised of a system of individual modules located in the control panel. The
system consists of six different microprocessor-based components. The
processors are:
• Clear Language Display - 1U6.
•
Chiller Module - 1U1.
•
Communication and Setpoint Reset Option Module - 1U2.
•
Expansion Valve Module - 1U3.
•
Compressor Module (one per compressor) - 1U4, 1U5.
•
Remote Display Buffer Option Module - 1U7.
•
LCI-C Option Module - 1U8.
The Clear Language Display has various functions that allow the operator to
read unit information and adjust setpoints. The following is a list of the
available functions:
• Operating and Diagnostic descriptions.
•
Settings of local setpoints and adjustments.
•
Actual controlling setpoints.
•
Specific temperatures.
•
Specific Pressures.
•
Enable/Disable status of features and options.
•
Selection status of SI units or English units.
•
Under/Over voltage protection.
•
Display of% line voltage.
•
Alarm/Running/Maximum Capacity contacts.
•
Display Starts and Hours.
Clear Language Display Keypad Overview
Local operator interface with the system is accomplished using the 16 keys
on the front of the Clear Language Display panel. The readout screen is a two
line, 40 character liquid crystal with a backlight. The backlight allows the
operator to read the display in low-light conditions. The depression of any key
will activate the backlight. The backlight will stay activated for 10 minutes
after the last key is pressed. At 10 F or below the backlight will stay activated
continuously.
The keys are grouped on the keyboard by the following functions (refer to
Figure 35):
• Select Report Group.
72
•
Select Settings Group.
•
Selection Keys.
•
Stop & Auto Keys.
RTAA-SVX01A-EN
Controls Interface
Figure 35
Operator Interface Adaptive Control
Select Report Group
This group of four keys allows the operator to select and view the following
reports:
• Custom Report.
•
Chiller Report.
•
Refrigerant Report.
•
Compressor Report.
The Custom Report is the only report of the four that is defined by the
operator. Any display under the other three reports can be added to the
Custom Report by pressing the plus
key while the desired read-out is on
the display. A maximum of 20 entries can be contained under the Custom
Report. Items can be deleted from the Custom Report by pressing the
minus
key when the desired read-out is on the display. The operator must
be in the Custom Report menu to delete the desired item.
The Chiller Report, Refrigerant Report and Compressor Report are informational reports that give current status. Each report and its contents are
discussed in detail on the following pages.
When any of the four report keys are pressed, the first readout on the display
will be the header. The header identifies the title of the report and summarizes the items in the report.
RTAA-SVX01A-EN
73
Controls Interface
The Next key and Previous key allow the operator to scroll up and down
through the display items listed under the report menus. When the last item
of a report is displayed and the Next key is pressed, the display will wrap
around to the header of the report. When the first item of a report is
displayed and the Previous key is pressed, the display will wrap around to the
last item.
Select Settings Group
The first three keys on the second row – Operator Settings, Service Settings
and Service Tests – allow the operator to adjust various setpoints and perform
various tests. Certain items in these groups are password protected. Refer to
the Password section for additional information.
When a setpoint key is pressed, a header will be displayed. The setpoint
headers identify the available items and setpoint functions.
The Next and Previous keys function in the same manner as that described in
Selected Report Group, above.
Setpoint values are incremented by pressing the plus
key and decremented by pressing the Minus
key. Once a setpoint is changed, the Enter
key must be pressed to save the new setpoint. If the Cancel key is pressed,
the setpoint value on the display will be ignored and the original setpoint will
remain.
Passwords
Passwords are needed to enter into the Service Setup Menu and the
Machine Configuration Menu. Both of these menus are accessed through the
Service Settings key. If access into these menus is necessary, follow the list
of steps below:
1. Press Service Settings.
2. Press Next until the readout in the display is:
Password Required For Further Access
“Please enter Password”
3. To enter into the Service Setup Menu, press:
Enter
4. To enter into the Machine Configuration Menu, press:
Enter
Select Report Group and Select Settings Group Flowcharts
The first block of the flowchart is the header which is shown on the display
after the menu key is pressed. For example:
Press Chiller Report and the readout on the display will be:
CHILLER RPRT:STATUS, WTR TEMPS & SETPTS
“PRESS (NEXT) (PREVIOUS) TO CONTINUE”
Press Next to move down through the Chiller Report. As shown in the
figures, the flowchart explains the conditions that the UCM looks at to
determine which readout is to be displayed next. For example:
74
RTAA-SVX01A-EN
Controls Interface
Press Chiller Report to display the header Press Next to display
MODE:
OPERATING MODE]
REQUESTED SETPOINT SOURCE:
[SETPT SOURCE]
Press Next to display
COMPRESSOR ON
CIRCUITS LOCKED OUT
Press Next to display
ACTIVE ICE TERMINATION SETPOINT
Or
ACTIVE CHILLED WATER SETPOINT
The UCM will determine which screen will be displayed after looking at the
current Operating Mode. If the Operating Mode is “Ice Making” or “Ice
Making Complete”, ACTIVE ICE TERMINATION SETPOINT will be displayed.
Otherwise, ACTIVE CHILLED WATER SETPOINT will be shown.
The flowcharts also list the setpoint ranges, default options and a brief
description of the item, when necessary. This information is shown in the
lefthand column of the page, adjacent to the appropriate display.
Auto/Stop Keys
The chiller will go through a “STOPPING” mode when the Stop key is
pressed if a compressor is running. This key has a red background color
surrounding it, to distinguish it from the others.
If the chiller is in the Stop mode, pressing the Auto key will cause the UCM to
go into the Auto/Local or Auto/Remote mode, depending on the Setpoint
Source setting. The Auto key has a green background color.
When either the Auto or Stop key is pressed, Chiller Operating Mode
(Chiller Report Menu) will be shown on the display.
Power Up
When power is first applied to the control panel, the Clear Language Display
goes through a self-test. For approximately five seconds, the readout on the
display will be:
SELF TEST IN PROGRESS
During the self-test, the backlight will not be energized. When the tests are
successfully complete, the readout on the display will be
6200 xxxx-xx
[TYPE] configuration
Updating Unit Data, Please Wait
When updating is successfully completed, the system will default to the first
display after the Chiller Report header:
MODE:
REQUESTED SETPOINT SOURCE:
OPERATING MODE]
[SETPT SOURCE]
and the backlight will be activated.
RTAA-SVX01A-EN
75
Controls Interface
&KLOOHU
5HSRUW
&+,//(5535767$786:757(036 6(7376
35(661(;735(9,28672&217,18(
1H[W
;/0%2!4).' -/$%=
2ESET
3TOPPED BY ,OCAL $ISPLAY
3TOPPED BY 2EMOTE $ISPLAY
3TOPPED BY 4RACER
3TOPPED BY %XT 3OURCE
!UTO
7AITING 2ESTART )NHIBIT
3TARTING
2UNNING
2UNNING #URRENT ,IMIT
2UNNING #ONDENSER ,IMIT
2UNNING %VAPORATOR ,IMIT
3TOPPING
-AKING )CE
)CE -AKING #OMPLETE
,OW !MBIENT 4EMP ,OCKOUT
%86 4EST
-ANUFACTURING 4EST
3ERVICE 0UMPDOWN
1H[W
;3%404 3/52#%=
,OCAL
4RACER
02'(
>23(5$7,1*02'(@
5(48(67('6(732,176285&(
>6(7376285&(@
1H[W
&2035(6625621
&,5&8,76/2&.('287
$%&'121(
&.7&.7121(
1H[W
;/PERATING -ODE=
-!+).' )#%
)#% -!+).' !,,
#/-0,%4% /4(%23
$&7,9(,&(7(50,1$7,216(732,17
(9$3(17(5,1*:$7(57(03
;;;)
;;;;)
$&7,9(&+,//(':$7(56(732,17
(9$3/($9,1*:$7(57(03
;;;)
;;;;)
1H[W
(9$3(17(5,1*:$7(57(03
(9$3/($9,1*:$7(57(03
;;;;)
;;;;)
1H[W
&AN