Trane Rtac 140 400 Users Manual SVX01F EN 01/01/2006 IOM Series R Air Cooled Helical Rotary Liquid Chiller. S 500 Ton Units (60 Hz), 1
RTAC 140-400 ton units (50 HZ) to the manual bfc813a7-ad9a-4d5f-9d7a-e7cd3f62b36c
2015-01-21
: Trane Trane-Rtac-140-400-Users-Manual-236136 trane-rtac-140-400-users-manual-236136 trane pdf
Open the PDF directly: View PDF .
Page Count: 252
Download | |
Open PDF In Browser | View PDF |
Preliminary Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chillers Models RTAC 140-500 ton units (60 Hz) RTAC 140-400 ton units (50 Hz) January 2006 © American Standard Inc. 2006 RTAC-SVX01F-EN NOTICE: Warnings and Cautions appear at appropriate sections throughout this literature. Read these carefully. WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. CAUTION: Indicates a situation that may result in equipment or propertydamage only accidents. Important Environmental Concerns! Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants—including industry replacements for CFCs such as and HCFCs and HFCs. Responsible Refrigerant Practices! Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them. WARNING Contains Refrigerant! System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage. 2 RTAC-SVX01F-EN Table of Contents General Information ............................................................................................. 7 Literature History.................................................................................................... 7 Unit Identification - Nameplates ............................................................................. 7 Unit Inspection ....................................................................................................... 8 Inspection Checklist ............................................................................................... 8 Loose Parts Inventory ............................................................................................ 8 Unit Description...................................................................................................... 8 Installation - Mechanical..................................................................................... 28 Installation Responsibilities ................................................................................... 28 Nameplates ........................................................................................................... 28 Outdoor Unit Nameplate ....................................................................................... 28 Compressor Nameplate ........................................................................................ 28 Storage .................................................................................................................. 29 General .................................................................................................................. 29 Location Requirements ......................................................................................... 29 Setting the Unit ..................................................................................................... 29 Isolation and Sound Emission ............................................................................... 36 Noise Considerations ............................................................................................ 37 Foundation............................................................................................................. 38 Clearances ............................................................................................................. 38 Unit Isolation and Leveling .................................................................................... 41 Neoprene Isolator Installation................................................................................ 41 Drainage ................................................................................................................ 41 Evaporator Water Piping........................................................................................ 41 Evaporator Piping .................................................................................................. 41 Entering Chilled Water Piping................................................................................ 42 Leaving Chilled Water Piping................................................................................. 42 Evaporator Drain .................................................................................................... 42 Evaporator Flow Switch......................................................................................... 42 Evaporator Water Pressure Drop RTAC 140 - 250 Ton ......................................... 43 Evaporator Water Pressure Drop RTAC 250 - 500 Ton ......................................... 44 Water Pressure Gauges ........................................................................................ 45 Water Pressure Relief Valves ................................................................................ 46 Freeze Protection .................................................................................................. 46 Low Evaporator Refrigerant Cutout and % Glycol Recommendations ................. 46 Procedure .............................................................................................................. 46 Important ............................................................................................................... 47 Specials ................................................................................................................. 47 Installation - Mechanical Remote Evaporator Option ................................................................................ 49 Line Sizing ............................................................................................................. 53 Liquid Line Sizing Steps ........................................................................................ 54 Example Liquid Line Sizing .................................................................................... 55 Suction Line Sizing Steps ...................................................................................... 56 Example Suction Line Sizing.................................................................................. 56 Suction Accumulator Sizing ................................................................................... 57 Example of Suction Accumulator Line Sizing ........................................................ 57 Piping Installation Procedures ............................................................................... 57 Refrigerant Sensors............................................................................................... 58 Refrigerant Pressure Relief Valve Venting............................................................. 58 RTAC-SVX01F-EN 3 Table of Contents 4 Leak Test and Evacuation ..................................................................................... Refrigerant and Additional Oil Charge .................................................................. Refrigerant Charge Determination........................................................................ Oil Charge Determination ..................................................................................... 58 60 60 61 Installation - Electrical........................................................................................ General Recommendations .................................................................................. Installer-Supplied Components............................................................................. Power Supply Wiring ............................................................................................ Control Power Supply ........................................................................................... Heater Power Supply and Convenience Outlet (Packaged Units Only) ................ Water Pump Power Supply .................................................................................. Interconnecting Wiring ......................................................................................... Chilled Water Flow (Pump) Interlock .................................................................... Chilled Water Pump Control ................................................................................. Alarm and Status Relay Outputs (Programmable Relays)..................................... Relay Assignments Using TechView .................................................................... Low Voltage Wiring .............................................................................................. Emergency Stop ................................................................................................... External Auto/Stop................................................................................................ External Circuit Lockout – Circuit #1 and Circuit #2.............................................. Ice Building Option ............................................................................................... External Chilled Water Setpoint (ECWS) Option................................................... External Current Limit Setpoint (ECLS) Option..................................................... Chilled Water Reset (CWR) .................................................................................. Communications Interface options....................................................................... Optional Tracer Communications Interface .......................................................... LonTalk Communications Interface for Chillers (LCI-C) ........................................ 62 62 75 75 76 76 77 77 77 77 78 79 79 79 80 80 80 81 81 82 84 84 84 Operating Principles ........................................................................................... Refrigeration Cycle ............................................................................................... Refrigerant R134a................................................................................................. Compressor .......................................................................................................... Condenser and Subcooler .................................................................................... Expansion Valve.................................................................................................... Evaporator ............................................................................................................ Oil System ............................................................................................................ 86 86 88 88 88 89 89 89 Controls Interface ............................................................................................... CH530 Communications Overview ...................................................................... Controls Interface ................................................................................................. DynaView Interface .............................................................................................. Key Functions ....................................................................................................... Radio Buttons ....................................................................................................... Spin Value Buttons ............................................................................................... Action Buttons ...................................................................................................... Hot Links .............................................................................................................. File Folder Tabs .................................................................................................... Display Screens .................................................................................................... Basic Screen Format ............................................................................................ Front Panel Lockout Feature ................................................................................ Front Panel Display During Cold Ambients........................................................... 91 91 91 91 92 92 92 92 92 92 93 93 94 94 RTAC-SVX01F-EN Table of Contents Modes Screen ....................................................................................................... 95 Chiller Screen ....................................................................................................... 101 Compressor Screen.............................................................................................. 101 Refrigerant Screen ............................................................................................... 102 Setpoint Screen .................................................................................................... 103 Diagnostic Screen ................................................................................................ 104 Power-Up ............................................................................................................. 105 Display Formats.................................................................................................... 105 Units ..................................................................................................................... 105 Languages ............................................................................................................ 105 TechView ............................................................................................................ 106 Minimum PC requirements to install and operate TechView ............................... 107 Unit View .............................................................................................................. 107 Compressor Service View .................................................................................... 109 Status View .......................................................................................................... 110 Setpoint View ....................................................................................................... 113 Diagnostics View .................................................................................................. 117 Software View ...................................................................................................... 122 Binding View ........................................................................................................ 123 Replacing or Adding Devices................................................................................ 124 Software Download.............................................................................................. 124 Instructions for First Time TechView Users ......................................................... 124 Diagnostics ......................................................................................................... 126 Legend to Diagnostics Table ................................................................................ 126 Pre-Start Checkout ............................................................................................. 137 Installation Checklist............................................................................................. 137 Receiving .............................................................................................................. 137 Unit Location and Mounting ................................................................................. 137 Unit Piping ............................................................................................................ 137 Electrical Wiring.................................................................................................... 138 General ................................................................................................................. 139 Unit Voltage Power Supply................................................................................... 140 Unit Voltage Imbalance ........................................................................................ 141 Unit Voltage Phasing ............................................................................................ 141 Water System Flow Rates.................................................................................... 142 Water System Pressure Drop............................................................................... 142 CH530 Set-Up ...................................................................................................... 143 Unit Start-Up Procedures .................................................................................. 144 Daily Unit Start-Up ................................................................................................ 144 General ................................................................................................................. 144 Seasonal Unit Start-Up Procedure ........................................................................ 145 System Restart After Extended Shutdown .......................................................... 146 Unit Shutdown Procedures ............................................................................... 147 Temporary Shutdown And Restart ....................................................................... 147 Extended Shutdown Procedure ........................................................................... 147 RTAC-SVX01F-EN 5 Table of Contents Periodic Maintenance........................................................................................ 149 Weekly Maintenance ........................................................................................... 149 Maintenance Procedures .................................................................................. Refrigerant and Oil Charge Management ............................................................ R134a Field Charging Procedure ......................................................................... Factory (initial) Refrigerant Charging Procedure .................................................. Field Refrigerant Charging Procedure.................................................................. Adding charge:..................................................................................................... Charge Isolation in the high or low side of system.............................................. High side charge isolation procedure: ................................................................. Returning unit to running condition: .................................................................... Low side charge isolation procedure: .................................................................. Refrigerant Filter Replacement Procedure .......................................................... Lubrication System .............................................................................................. Oil Charging Procedure........................................................................................ Factory (initial) Oil Charging Procedure................................................................ Evaporator tube replacement .............................................................................. Compressor Replacement ................................................................................... 155 155 156 156 156 157 157 157 158 158 159 159 159 161 163 163 Unit Wiring ......................................................................................................... 165 6 RTAC-SVX01F-EN General Information Literature History RTAC-SVX001-EN (December 2000) New manual. RTAC-SVX01B-EN (September 2001) New manual describes installation, operation, and maintenance of RTAC units and the remote evaporator option. RTAC-SVX01C-EN (February 2002) Revised manual includes additional RTAC units to size 500 tons, new installation and maintenance material, and expanded CH530 diagnostics. RTAC-SVX01D-EN (July 2003) Revised manual for new evaporator design for 2 compressor units. Design Sequence H0 and later. RTAC-SVX01E-EN (July 2004) Revised manual for new evaporator design for 3 and 4 compressor units. Design Sequence J0 and later. RTAC-SVX01F-EN (January 2006) Revised manual for new control panel design. Unit Identification - Nameplates When the unit arrives, compare all nameplate data with ordering, submittal, and shipping information. A typical unit nameplate is shown in Figure 1. Figure 1 RTAC-SVX01F-EN Typical Unit Nameplate 7 General information Unit Inspection When the unit is delivered, verify that it is the correct unit and that it is properly equipped. Compare the information which appears on the unit nameplate with the ordering and submittal information. Inspect all exterior components for visible damage. Report any apparent damage or material shortage to the carrier and make a “unit damage” notation on the carrier’s delivery receipt. Specify the extent and type of damage found and notify the appropriate Trane Sales Office. Do not proceed with installation of a damaged unit without sales office approval. Inspection Checklist To protect against loss due to damage incurred in transit, complete the following checklist upon receipt of the unit. • Inspect the individual pieces of the shipment before accepting the unit. Check for obvious damage to the unit or packing material. • Inspect the unit for concealed damage as soon as possible after delivery and before it is stored. Concealed damage must be reported within 15 days. • If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. • Notify the carrier’s terminal of the damage immediately, by phone and by mail. Request an immediate, joint inspection of the damage with the carrier and the consignee. • Notify the Trane sales representative and arrange for repair. Do not repair the unit, however, until damage is inspected by the carrier’s representative. Loose Parts Inventory Check all the accessories and loose parts which are shipped with the unit against the shipping list. Included in these items will be water vessel drain plugs, rigging and electrical diagrams, and service literature, which are placed inside the control panel and/or starter panel for shipment. Unit Description The 140 - 500 ton Model RTAC units are helical-rotary type, air-cooled liquid chillers designed for installation outdoors. The compressor circuits are completely assembled, hermetic packages that are factory-piped, wired, leak-tested, dehydrated, and tested for proper control operation before shipment. NOTE: Packaged units are factory charged with refrigerant and oil. Figure 2 shows a typical RTAC packaged unit and its components. Table 1 through Table 5 contain general RTAC mechanical specifications for all unit sizes. 8 RTAC-SVX01F-EN General Information . Figure 2 Typical RTAC Unit Chilled water inlet and outlet openings are covered for shipment. Each compressor has a separate compressor motor starter. The RTAC series features Trane’s exclusive Adaptive Control ™ logic, which monitors the control variables that govern the operation of the chiller unit. Adaptive Control logic can adjust capacity variables to avoid chiller shutdown when necessary, and keep producing chilled water. The units feature two independent refrigerant circuits. Compressor unloaders are solenoid actuated and oil pressure operated. Each refrigerant circuit is provided with filter, sight glass, electronic expansion valve, and charging valves. The shell-and-tube type evaporator is manufactured in accordance with ASME standards or other international codes. Each evaporator is fully insulated and is equipped with water drain and vent connections. Packaged units have heat tape protection to - 20°F (-28.9°C) as standard. As an option, a convenience outlet can be supplied. RTAC-SVX01F-EN 9 General information Table 1 General Data — 140-250 Ton 60 Hz Units - Standard Efficiency Size Type 140 STD 155 STD (tons) 2 70/70 2 85/70 (gallons) (liters) (gpm) (l/sec) (gpm) (l/sec) 29 111 193 12 709 45 32 121 214 14 785 50 Quantity of Coils Coil Length (inches) (mm) Coil Height (inches) (mm) Fins/Ft Number of Rows 4 156/156 3962/3962 42 1067 192 3 4 180/156 4572/3962 42 1067 192 3 Quantity Diameter (inches) (mm) (cfm) (m3/hr) (rpm) (rps) (ft/min) (m/s) 4/4 30 762 77000 130811 1140 19 8954 45 5/4 30 762 84542 143623 1140 19 8954 45 (Deg F) (Deg C) (Deg F) (Deg C) 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 Quantity Nominal Size 170 STD Compressor 2 85/85 185 STD 200 STD 225 STD 250 STD 2 100/85 2 100/100 2 120/100 2 120/120 35 134 217 14 796 50 39 146 241 15 883 56 38 145 217 14 796 50 42 158 241 15 883 56 4 216/180 5486/4572 42 1067 192 3 4 216/216 5486/5486 42 1067 192 3 4 252/216 6401/5486 42 1067 192 3 4 252/252 6401/6401 42 1067 192 3 6/5 30 762 101296 172086 1140 19 8954 45 6/6 30 762 110506 187732 1140 19 8954 45 7/6 30 762 119725 203394 1140 19 8954 45 7/7 30 762 128946 219059 1140 19 8954 45 25 -3.9 0,0 -17.8 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 HFC-134a 2 HFC-134a 2 HFC-134a 2 15 215/215 15 225/215 15 225/225 98/98 2.1/2.1 8/8 18 102/98 2.1/2.1 8/8 21 102/102 2.1/2.1 8/8 21 Evaporator Water Storage Min. Flow Max. Flow 33 127 202 13 741 47 Condenser 4 180/180 4572/4572 42 1067 192 3 Condenser Fans Total Airflow Nominal Fan Speed Tip Speed 5/5 30 762 92087 156441 1140 19 8954 45 Min Starting/Operating Ambient Std Unit Low Ambient 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 General Unit Refrigerant HFC-134a HFC-134a HFC-134a HFC-134a No. of Independent 2 2 2 2 Refrigerant Circuits % Min. load 15 15 15 15 (lb) 165/165 175/165 175/175 215/210 Refrigerant Charge (kg) 75/75 79/75 79/79 98/95 Oil Charge (gallons) 1.5/1.5 1.5/1.5 1.5/1.5 2.1/1.5 (liters) 6/6 6/6 6/6 8/6 Base Length (feet) 15 15 15 18 1. Data containing information on two circuits shown as follows: CKT1/CKT 2. 2. Minimum start-up/operating ambient based on a 5 mph wind across the condenser. 10 RTAC-SVX01F-EN General Information Table 2 General Data — 275- 500 Ton 60 Hz Units - Standard Efficiency Size Type Quantity Nominal Size 275 STD 300 STD 350 STD Compressor (tons) 3 85/85 100 3 100/100 100 (gallons) (liters) (gpm) (l/sec) (gpm) (l/sec) 60 229 309 20 1134 72 65 245 339 21 1243 78 8 180/108 4572/2743 42 1067 192 3 8 216/108 5486/2743 42 1067 192 3 10/6 30 762 147340 250307 1140 19 8954 45 12/6 30 762 165766 281610 1140 19 8954 45 3 120/120 100 400 STD 450 STD 500 STD 4 100/100 100/100 4 120/120 100/100 4 120/120 120/120 81 306 404 26 1483 94 84 316 422 27 1548 98 89 337 461 29 1690 107 8 216/216 5486/5486 42 1067 192 3 8 252/216 6401/5486 42 1067 192 3 8 252/252 6401/6401 42 1067 192 3 12/12 30 762 221016 375471 1140 19 8954 45 14/12 30 762 239456 406797 1140 19 8954 45 14/14 30 762 257991 438285 1140 19 8954 45 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 HFC-134a 2 HFC-134a 2 HFC-134a 2 15 415/415 188/188 5.0/5.0 19/19 39 15 460/415 209/188 5.0/5.0 19/19 45 15 460/460 209/209 5.0/5.0 19/19 45 Evaporator Water Storage Min. Flow Max. Flow 70 264 375 24 1374 87 Condenser Quantity of Coils Coil Length Coil Height (inches) (mm) (inches) (mm) Fins/Ft Number of Rows 8 252/108 6401/4572 42 1067 192 3 Condenser Fans Quantity Diameter (inches) (mm) Total Airflow (cfm) (m3/hr) Nominal Fan Speed (rpm) (rps) Tip Speed (ft/min) (m/s) 14/6 30 762 184151 312843 1140 19 8954 45 Min Starting/Oper Ambient Std Unit Low Ambient (Deg F) (Deg C) (Deg F) (Deg C) 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 General Unit Refrigerant HFC-134a HFC-134a HFC-134a No. of Independent 2 2 2 Refrigerant Circuits % Min. load 15 15 15 Refrigerant Charge (lb) 365/200 415/200 460/200 (kg) 166/91 188/91 209/91 Oil Charge (gallons) 4.6/2.1 5.0/2.1 5.0/2.1 (liters) 17.4/8 19/8 19/8 Base Length (feet) 30 36 36 1. Data containing information on two circuits shown as follows: CKT1/CKT 2. 2. Minimum start-up/operating ambient based on a 5 mph wind across the condenser. RTAC-SVX01F-EN 11 General information Table 3 General Data — 140-400 Ton 60 Hz Units - High Efficiency Size Type 140 HIGH 155 HIGH 170 HIGH 185 HIGH 2 70/70 2 85/70 2 85/85 2 100/85 Water Storage (gallons) (liters) Min. Flow (gpm) (l/sec) Max. Flow (gpm) (l/sec) 33 127 202 13 741 47 35 134 217 14 796 50 39 146 241 15 883 56 38 145 217 14 796 50 Quantity of Coils Coil Length (inches) (mm) 4 4 4 4 180/180 4572/ 4572 42 1067 192 3 216/180 5486/ 4572 42 1067 192 3 216/216 5486/ 5486 42 1067 192 3 252/216 6401/ 5486 42 1067 192 3 5/5 30 762 91993 156281 1140 19 8954 45 6/5 30 762 101190 171906 1140 19 8954 45 6/6 30 762 110387 187530 1140 19 8954 45 7/6 30 762 119598 203178 1140 19 8954 45 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 Quantity Nominal Size (tons) 200 225 HIGH HIGH Compressor 250 HIGH 275 HIGH 300 HIGH 350 HIGH 400 HIGH 2 120/100 2 120/120 3 85/85 100 3 100/100 100 4 85/85 85/85 4 100/100 100/100 42 158 241 15 883 56 42 158 241 15 883 56 70 264 375 24 1374 87 70 264 375 24 1374 87 81 306 404 26 1483 94 89 337 461 29 1690 107 4 8 8 8 8 8 8 252//252 6401/ 6401 42 1067 192 3 144/144 3658/ 3658 42 1067 192 3 180/108 4572/ 2743 42 1067 192 3 216/144 5486/ 3658 42 1067 192 3 252/144 6401/ 3658 42 1067 192 3 216/216 5486/ 5486 42 1067 192 3 252/252 6401/ 6401 42 1067 192 3 8/8 30 762 147242 250141 1140 19 8954 45 12/6 30 762 173733 295145 1140 19 8954 45 14/6 30 762 192098 326344 1140 19 8954 45 12/12 30 762 220778 375066 1140 19 8954 45 14/14 30 762 257626 437665 1140 19 8954 45 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 2 100/100 Evaporator 42 158 241 15 883 56 Condenser Coil Height (inches) (mm) Fins/Ft Number of Rows Condenser Fans Quantity Diameter (inches) (mm) Total (cfm) Airflow (m3/hr) Nominal (rpm) Fan Speed (rps) Tip Speed (ft/min) (m/s) 7/7 30 762 128812 218831 1140 19 8954 45 8/6 30 762 136958 232670 1140 19 8954 45 Min Starting/Oper Ambient Std Unit Low Ambient (Deg F) (Deg C) (Deg F) (Deg C) 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 25 -3.9 0.0 -17.8 General Unit Refrigerant HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a No. of Independent 2 2 2 2 2 2 Refrigerant Circuits % Min. load 15 15 15 15 15 15 Refrigerant (lb) 175/175 215/205 215/215 225/215 225/225 235/235 Charge (kg) 79/79 98/93 98/98 102/98 102/102 107/107 Oil Charge (gallons) 1.5/1.5 1.5/1.5 1.5/1.5 2.1/1.5 2.1/2.1 2.1/2.1 (liters) 6/6 6/6 6/6 8/6 8/8 8/8 Base (feet) 15 18 18 21 21 30 Length 1. Data containing information on two circuits shown as follows: CKT 1/CKT 2 2. Minimum start-up/operating ambient based on a 5 mph wind across the condenser 12 HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a 2 2 2 2 2 15 235/235 107/107 2.1/2.1 8/8 30 15 415/200 188/91 4.6/2.2 17/8 36 15 460/200 209/91 5.0/2.2 19/8 39 15 415/415 188/188 4.6/4.6 17/17 39 15 460/460 209/209 5.0/5.0 19/19 45 RTAC-SVX01F-EN General Information Table 4 General Data - 120-400 Ton 50 Hz Units-Standard Efficiency Size Type 140 STD 155 STD 170 STD 185 STD 2 70/70 2 85/70 2 85/85 2 100/85 29 110 192 12 702 44 32 120 221 13 778 49 33 126 200 13 735 46 35 133 215 14 789 50 4 4 4 180/156 4512/ 3962 42 1067 192 3 180/180 4572/ 4512 42 1067 192 3 216/180 5486/ 4572 42 1067 192 3 4/4 (inches) 30 (mm) 762 Total (cfm) 63346 Airflow (m3/hr) 107615 Nominal (rpm) 950 Fan Speed (rps) 15.8 Tip Speed (ft/min) 7461 (m/s) 38 5/4 30 762 69507 118081 950 15.8 7461 38 5/5 30 762 75671 128553 950 15.8 7461 38 6/5 30 762 83236 141405 950 15.8 7461 38 Std Unit 25 -3.9 0 -17.8 25 -3.9 0 -17.8 Quantity Nominal Size (tons) 200 250 STD STD Compressor 2 100/100 275 STD 300 STD 350 STD 375 STD 400 STD 3 3 3 70-70/100 85-85/100 100-100/ 100 4 4 85-85/85- 100-100/ 85 85-85 4 100-100/ 100-100 54 203 262 17 962 61 60 227 307 19 1124 72 64 243 336 21 1232 78 73 275 384 22 1275 80 77 291 377 24 1383 87 80 304 401 25 1470 93 4 8 8 8 8 8 8 216/216 5486/ 5486 42 1067 192 3 156/108 3962/ 4512 42 1067 192 3 180/108 4572/ 2743 42 1067 192 3 216/108 5486/ 2743 42 1067 192 3 180/180 4572/ 4572 42 1067 192 3 216/180 5486/ 4572 42 1067 192 3 252/216 6401/ 5486 42 1067 192 3 10/6 30 762 121056 205655 950 15.8 7461 38 12/6 30 762 136210 231399 950 15.8 7451 38 10/10 30 762 151332 257089 950 15.8 7461 38 12/10 30 762 166467 282801 950 15.8 7461 38 12/12 30 762 181611 308528 950 15.8 7461 38 25 -3.9 0 -17.8 25 -3.9 0 -17.8 25 -3.9 0 -17.8 25 -3.9 0 -17.8 25 -3.9 0 -17.8 Evaporator Water Storage (gallons) (liters) Min. Flow (gpm) (l/sec) Max. Flow (gpm) (l/sec) 38 145 239 15 875 55 Condenser Quantity of 4 Coils Coil Length (inches) 156/156 (mm) 3962/ 3962 Coil Height (inches) 42 (mm) 1067 Fins/Ft 192 Number of Rows 3 Condenser Fans Quantity Diameter 6/6 30 762 90803 154260 950 15.8 7461 38 8/6 30 762 108698 184661 950 15.8 7461 38 Min Starting/Oper Ambient Low Ambient (Deg F) (Deg C) (Deg F) (Deg C) 25 -3.9 0 -17.8 25 -3.9 0 -17.8 25 -3.9 0 -17.8 25 -3.9 0 -17.8 General Unit Refrigerant HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a No. of Independent 2 2 2 2 2 2 Refrigerant Circuits % Min. load 15 15 15 15 15 15 Refrigerant (lb) 165/165 175/165 175/175 215/210 215/215 335/200 Charge (kg) 75/75 79/75 79/79 98/95 98/98 152/91 Oil (gallons) 1.5/1.5 1.5/1.5 1.5/1.5 2.1/1.5 2.1/2.1 4.6/2.1 Charge (liters) 6/6 6/6 6/6 8/6 8/8 17.4/8 Base (feet) 15 15 15 18 18 30 Length 1. Data containing information on two circuits shown as follows: CKT 1/CKT 2 2. Minimum start-up/operating ambient based on a 5 mph wind across the condenser RTAC-SVX01F-EN HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a 2 2 2 2 2 15 365/200 166/91 4.6/2.1 17.4/8 30 15 415/200 188/91 5.0/2.1 19.0/8 36 15 365/365 166/166 4.6/4.6 17.4/17.4 39 15 415/365 188/166 5.0/4.6 19.0/17.4 39 15 415/415 188/188 5.0/5.0 19.0/19.0 39 13 General information Table 5 General Data - 120-400 Ton 50 Hz Units-High Efficiency Size Type 140 HIGH 155 HIGH 170 HIGH 185 HIGH 200 250 HIGH HIGH Compressor Quantity Nominal Size (tons) 2 70/70 2 85/70 2 85/85 2 100/85 Water Storage 33 126 200 13 735 46 35 133 215 14 789 50 38 145 239 15 875 55 38 145 215 14 789 50 Qty of Coils 4 Coil Length (inches) 180/180 (mm) 4572/ 4572 Coil Height (inches) 42 (mm) 1067 Fins/Ft 192 Number of Rows 3 4 216/180 5486/ 4572 42 1067 192 3 4 216/216 5486/ 5486 42 1067 192 3 4 252/216 6401/ 5486 42 1067 192 3 Quantity Diameter in. (mm) Total Airflow (cfm) (m3/hr) Nominal Fan (rpm) Speed (rps) Tip Speed (ft/min) (m/s) 5/5 30 (762) 75575 128390 950 15.8 7461 38 6/5 30 (762) 83130 141225 950 15.8 7461 38 6/6 30 (762) 90687 154063 950 15.8 7461 38 7/6 30 (762) 98256 166921 950 15.8 7461 38 Std Unit 25 (-3.9) 25 (-3.9) 25 (-3.9) 25 (-3.9) 25 (-3.9) 0 (-17.8) 0 (-17.8) 0 (-17.8) 0 (-17.8) 0 (-17.8) 2 100/100 3 70-70/ 100 275 HIGH 300 HIGH 350 HIGH 375 HIGH 400 HIGH 3 85-85/ 100 3 100-100/ 100 4 85-85/ 85-85 4 100-100/ 85-85 4 100-100/ 100-100 69 262 371 23 1362 86 69 262 371 23 1362 86 80 304 401 25 1470 93 83 314 419 26 1535 97 89 335 457 29 1675 106 Evaporator Min. Flow Max. Flow (gallons) (liters) (gpm) (l/sec) (gpm) (l/sec) 41 157 239 15 875 55 64 243 336 21 1232 78 Condenser 4 252/252 6401/ 6401 42 1067 192 3 8 180/108 4572/ 2743 42 1067 192 3 8 8 216/144 252/144 5486/3658 6401/ 3658 42 42 1067 1067 192 192 3 3 8 8 8 216/216 252/216 252/252 5486/5486 6401/5486 6401/ 6401 42 42 42 1067 1067 1067 192 192 192 3 3 3 12/6 30 (762) 142969 242881 950 15.8 7461 38 14/6 30 (762) 158112 268607 950 15.8 7461 38 12/12 30 (762) 181371 308120 950 15.8 7461 38 14/12 30 (762) 194731 330817 950 15.8 7461 38 14/14 30 (762) 211648 359556 950 15.8 7461 38 25 (-3.9) 25 (-3.9) 25 (-3.9) 25 (-3.9) 25 (-3.9) 25 (-3.9) 0 (-17.8) 0 (-17.8) 0 (-17.8) 0 (-17.8) 0 (-17.8) 0 (-17.8) Condenser Fans 7/7 30 (762) 105826 179781 950 15.8 7461 38 10/6 30 (762) 120971 205510 950 15.8 7461 38 Min Starting/Oper Ambient Low Ambient Deg F (C) Deg F (C) General Unit Refrigerant HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a No. of Independent 2 2 2 2 2 2 Refrigerant Circuits % Min. load 15 15 15 15 15 15 175/175 215/205 215/215 225/215 225/225 365/200 Refrigerant (lb) Charge (kg) 79/79 98/93 98/98 102/98 102/102 166/91 Oil Charge (gallons) 1.5/1.5 1.5/1.5 1.5/1.5 2.1/1.5 2.1/2.1 4.6/2.1 (liters) 6/6 6/6 6/6 8/6 8/8 17.4/8 Base Length (feet) 15 18 18 21 21 30 1. Data containing information on two circuits shown as follows CKT 1/CKT 2 2. Minimum start-up/operating ambient based on a 5 mph wind across the condenser 14 HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a 2 2 2 2 2 15 415/200 188/91 4.6/2.1 17.4/8 36 15 460/200 209/91 5.0/2.1 19.0/8 39 15 415/415 188/188 4.6/4.6 17.4/17.4 39 15 460/415 209/188 5.0/5.0 19.0/19.0 45 15 460/460 209/209 5.0/5.0 19.0/19.0 45 RTAC-SVX01F-EN General Information Figure 3 Unit Dimensions 185-200 Ton Standard Efficiency, 60 Hz and 155, 170 Ton, High Efficiency, 50 and 60 Hz RTAC-SVX01F-EN 15 Figure 4 16 Unit Dimensions 225-250 Ton Standard Efficiency, 60 Hz and 185-200 Ton, High Efficiency, 50 and 60 Hz RTAC-SVX01F-EN Figure 5 Unit Dimensions 225-250 Ton High Efficiency, 60 Hz RTAC-SVX01F-EN 17 Figure 6 18 Unit Dimensions 250-275 Ton Standard Efficiency, 50 Hz and 250 Ton High Efficiency, 50 Hz and 275 Ton Standard Efficiency, 60 Hz RTAC-SVX01F-EN Figure 7 Unit Dimensions 275 Ton High Efficiency, 50 and 60 Hz; 300 Ton, Standard Efficiency, 50 and 60 Hz and 350 Ton, Standard Efficiency 60 Hz RTAC-SVX01F-EN 19 Figure 8 20 Unit Dimensions 300 Ton High Efficiency, 50 and 60 Hz RTAC-SVX01F-EN Figure 9 Unit Dimensions 350-400 Ton Standard Efficiency, Hz and 400 Ton, Standard Efficiency, 60 Hz and 350 Ton High Efficiency, 50 and 60Hz RTAC-SVX01F-EN 21 Figure 10 22 Unit Dimensions 450-500 Ton Standard Efficiency, 60 Hz and 375-400 Ton, High Efficiency, 50 Hz and 400 Ton High Efficiency, 60 Hz RTAC-SVX01F-EN Figure 11 Unit Dimensions of Condenser/Compressor Unit for Remote Evaporator Option RTAC-SVX01F-EN 23 Figure 12 24 Unit Dimensions for Remote Evaporator 140-170 Ton Standard Efficiency and 140 Ton High Efficiency RTAC-SVX01F-EN Figure 13 Unit Dimensions for Remote Evaporator185-250 Ton Standard Efficiency and 155-200 Ton High Efficiency RTAC-SVX01F-EN 25 Model Number Coding System The model numbers for the unit and the starter are composed of numbers and letters that represent features of the equipment. Shown in the following table is a sample of typical unit model number and the coding system for each. Each position, or group of positions, in the model number is used to represent a feature. For example, in the first table, position 08 of the unit model number, Unit Voltage, contains the number “4”. A 4 in this position means that the unit voltage is 460/ 60/3. Unit Model Number An example of a typical unit model number (M/N) is: RTAC 350A UA0N NAFN N1NX 1TEN NN0N N01N Model number digits are selected and assigned in accordance with the following definitions using the model number example shown above. 26 RTAC-SVX01F-EN Digit 1-4 Unit Model RTAC Air Cooled Series R® chiller Digit 5-7 Unit Nominal Capacity 140 140 Nominal Tons 155 155 Nominal Tons 170 170 Nominal Tons 185 185 Nominal Tons 200 200 Nominal Tons 225 225 Nominal Tons 250 250 Nominal Tons 275 275 Nominal Tons 300 300 Nominal Tons 350 350 Nominal Tons 375 375 Nominal Tons 400 400 Nominal Tons 450 450 Nominal Tons 500 500 Nominal Tons Digit 8 Unit Voltage A 200V/60Hz/3Ph power K 220V/50Hz/3 Ph power C 230V/60Hz/3Ph power J 380V/60Hz/3Ph power D 400V/50Hz/3Ph power 4 460V/60Hz/3Ph power 5 Charmes Digit 10-11 Design Sequence XX Factory/ABU Assigned Digit 12 Unit Type N Std. Efficiency/Performance H High Efficiency/Performance Digit 13 Agency Listing N No agency listing U C/UL listing Digit 14 Pressure Vessel Code A ASME pressure vessel code C Canadian code D Australian code L Chinese code R Vietanamese code S Special Digit 15 Evaporator Temperature Range & Application Type F Standard Temp. with Frz Prot R Rem Evap, Std. Temp, No Frz Prot G Low Temp, with Frz Prot Digit 16 Evaporator Configuration N W Standard pass arrangement, insulated RTAC-SVX01F-EN Wide ambient capability 0-125 deg F Digit 18 Condenser Fin Material 1 Standard aluminum slit fins 2 Copper fins, non-slit fins 4 Complete Coat aluminum fins Digit 19 Condenser Fan/Motor Configuration N Condenser fans with ODP motors W Low Noise fans T Condenser fans with TEAO motors Digit 20 Compressor Motor Starter Type X Across-the-line starters Y 575V/60Hz/3Ph power Digit 9 Manufacturing Location U Pueblo E Digit 17 Condenser Temperature Range N Standard ambient range 25-115 deg F H High ambient capability 25-125 deg F L Low ambient capability 0-115 deg F Wye-delta closed transition starters Digit 21 Incoming Power Line Connection 1 Single point power connection 2 Dual point power connection (1/ ckt) Digit 22 Power Line Connection Type T Terminals only D Non-fused disconnect switch(es) C Circuit Breaker(s), HACR-rated Digit 23 Unit Operator Interface E Easy-View operator interface D Dyna-View operator interface Digit 24 Remote Interface N No remote interface C Tracer Comm 3 interface L Lon Talk Communication interface (LCI) Digit 25 Control Input Accessories/Options N No remote input R Remote leaving water temp stpt C Remote current limit setpoint B Remote lvg. temp.setpoint and remote current limit setpoint Digit 26 COOP 26 Control Output Accessories/Options N No output options A Alarm relay C Icemaking D Icemaking and alarm relay Digit 27 Short Circuit Rating 0 No short circuit withstand rating 5 10000A SCR 4 35000A SCR 6 65000A SCR Digit 28 Electrical Accessories and Export Packing N No flow switches F NEMA-1 flow switch - 150 psi E Vapor Proof FS - 150 psi Digit 29 Control Panel Accessories N No convenience outlet A 15A 115V convenience outlet (60HZ) Digit 30 Refrigerant Service Valves 1 Suction service valves Digit 31 Compressor Sound Attenuator Option 0 No sound attenuator 1 Factory installed sound attenuator Digit 32 Appearance Options N No appearance options A Architectural louvered panels C Half Louvers G Access guards B Access guards and half louvers P Painted unit L Painted unit with full louvered panels H Painted unit with half louvered panels K Painted unit with access guards W Painted w/access guards and half louvers Digit33 Installation Accessories N No installation accessories R Neoprene isolators F Flanged water connection kit G Neoprene isolators and flange wtr conn kit Digit 34 Factory Test 0 No factory run test P Performance test W Witness test Digit 35 Label, and Literature Language E English G Chinese Digit 36 Special Order X Standard catalog configuration S Unit has special order feature Digit 37 Safety Devices N None X Standard 27 Installation - Mechanical Installation Responsibilities Generally, the contractor must do the following when installing an RTAC unit: • Install unit on a flat foundation, level (within 1/4” [6 mm] across the length and width of the unit), and strong enough to support unit loading. • Install unit per the instructions contained in the Installation-Mechanical and Installation-Electrical sections of this manual. • Install any optional sensors and make electrical connections at the CH530. • Where specified, provide and install valves in water piping upstream and downstream of evaporator water connections to isolate the evaporator for maintenance, and to balance/trim system. • Furnish and install flow switch to prove chilled water flow. • Furnish and install pressure gauges in inlet and outlet piping of the evaporator. • Furnish and install a drain valve to the bottom of the evaporator waterbox. • Supply and install a vent cock to the top of the evaporator waterbox. • Furnish and install strainers ahead of all pumps and automatic modulating valves, and at inlet of evaporator. • Provide and install field wiring. • Install heat tape and insulate the chilled water lines and any other portions of the system, as required, to prevent sweating under normal operating conditions or freezing during low ambient temperature conditions. • Install evaporator drain plug. The plug ships in unit control panel. • Start unit under supervision of a qualified service technician. Nameplates The RTAC outdoor unit nameplates (Figure 1) are applied to the exterior of the Control Panel. A compressor nameplate is located on each compressor. Outdoor Unit Nameplate The outdoor unit nameplate provides the following information: – Unit model and size description. – Unit serial number. – Identifies unit electrical requirements. – Lists correct operating charges of R-134a and refrigerant oil (Trane OIL00048). – Lists unit test pressures. – Identifies installation, operation and maintenance and service data literature (Pueblo). – Lists drawing numbers for unit wiring diagrams (Pueblo). Compressor Nameplate The compressor nameplate provides following information: – Compressor model number. – Compressor serial number. – Compressor electrical characteristics. – Utilization range. – Recommended refrigerant. 28 RTAC-SVX01F-EN Installation - Mechanical Storage Extended storage of the outdoor unit prior to installation requires the following precautionary measures: 1. Store the outdoor unit in a secure area. 2. At least every three months (quarterly), check the pressure in the refrigerant circuits to verify that the refrigerant charge is intact. If it is not, contact a qualified service organization and the appropriate Trane sales office. 3. Close the discharge and liquid line isolation valves. General Report any damage incurred during handling or installation to the Trane sales office immediately. Location Requirements Setting the Unit A base or foundation is not required if the selected unit location is level and strong enough to support the unit’s operating weight as listed in Table 1 through Table 5 in the General Information section. See Table 6 for lifting weights and center of gravity (CG) dimensions. 1. Lifting chains/cables will not be the same length. Adjust to keep unit level while lifting. 2. Do not fork lift unit. 3. Weights are typical for units with R-134a charge. Figure 14 Lifting the Unit (Package and Remote) 15-21-foot Base RTAC-SVX01F-EN 29 Installation - Mechanical 1. Lifting chains/cables will not be the same length. Adjust to keep unit level while lifting. 2. Do not fork lift unit. 3. Weights are typical for units with R-134a charge. Figure 15 Lifting the Unit (Package and Remote) 30-36-foot Base 1. Lifting chains/cables will not be the same length. Adjust to keep unit level while lifting. 2. Do not fork lift unit. 3. Weights are typical for units with R-134a charge. Figure 16 30 Lifting the Unit 39-45-foot Base RTAC-SVX01F-EN Installation - Mechanical : Table 6 Lifting Weights and CG Dimensions (Refer to Figure 14 - Figure 15) Unit 140 Ton 50 Hz High Eff 140 Ton 50 Hz Std Eff 140 Ton 60 Hz High Eff 140 Ton 60 Hz Std Eff 155 Ton 50 Hz High Eff 155 Ton 50 Hz Std Eff 155 Ton 60 Hz High Eff 155 Ton 60 Hz Std Eff 170 Ton 50 Hz High Eff 170 Ton 50 Hz Std Eff 170Ton 60 Hz High Eff 170 Ton 60 Hz Std Eff 185 Ton 50 Hz High Eff 185 Ton 50 Hz Std Eff 185 Ton 60 Hz High Eff 185 Ton 60 Hz Std Eff 200 Ton 50 Hz High Eff 200 Ton 50 Hz Std Eff 200 Ton 60 Hz High Eff 200 Ton 60 Hz Std Eff 225 Ton 60 Hz Std Eff 250 Ton 60 Hz Std Eff 250 Ton 50 Hz High Eff 250 Ton 50 Hz Std Eff 275 Ton 50 Hz High Eff RTAC-SVX01F-EN W1 W2 W3 W4 W5 W6 W7 W8 lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg 2499 1134 2488 1128 2495 1132 2484 1127 3281 1488 2601 1180 3168 1437 2493 1131 3308 1501 2598 1179 3186 1445 2498 1133 3650 1655 3342 1516 3526 1600 3296 1495 3778 1714 3370 1529 3719 1687 3340 1515 3711 1683 3778 1714 3360 1526 2951 1340 3403 1545 2874 1303 2859 1297 2869 1301 2855 1295 3588 1628 2882 1307 3562 1616 2862 1298 3721 1688 2990 1356 3586 1627 2873 1303 4199 1905 3763 1707 4117 1867 3635 1649 4252 1928 3789 1719 4187 1899 3756 1704 4229 1918 4252 1928 2930 1330 2522 1145 2997 1361 2686 1218 2668 1210 2680 1216 2662 1208 2747 1246 2794 1267 2604 1181 2675 1213 2760 1252 2838 1287 2623 1190 2684 1218 3113 1412 2745 1245 2990 1356 2707 1228 3175 1440 2828 1283 3110 1411 2796 1268 3114 1413 3175 1440 3390 1539 3238 1470 3689 1675 Aluminum Fins 3019 NA 1369 3000 NA 1361 3013 NA 1367 2994 NA 1358 3055 NA 1386 3033 NA 1376 2998 NA 1360 3004 NA 1362 3173 NA 1439 3177 NA 1441 3024 NA 1371 3018 NA 1369 3662 NA 1661 3166 NA 1436 3581 NA 1624 3047 NA 1382 3649 NA 1655 3247 NA 1473 3578 NA 1623 3212 NA 1457 3632 NA 1648 3649 NA 1655 2959 3430 1344 1557 2809 3430 1275 1557 3283 3977 1491 1805 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 3000 1362 3000 1362 3571 1621 NA NA NA NA NA NA Shipping Weight lbs kg Xcg Ycg in mm in mm 11077 5025 11015 4996 11057 5015 10995 4987 12671 5748 11309 5130 12332 5594 11034 5005 12962 5880 11603 5263 12418 5633 11073 5023 14624 6633 13015 5904 14214 6447 12685 5754 14853 6737 13234 6003 14593 6619 13104 5944 14687 6662 14853 6737 19069 8657 17949 8149 20920 9498 88 2245 88 2245 88 2245 88 2243 106 2695 88 2243 106 2682 88 2245 106 2695 89 2256 106 2685 88 2245 124 3160 106 2682 124 3157 106 2680 124 3147 106 2697 124 3142 106 2697 124 3147 124 3147 177 4483 182 4623 202 5128 45 1140 45 1140 45 1140 45 1140 44 1123 44 1120 45 1140 45 1138 45 1140 45 1138 45 1140 45 1140 45 1153 45 1140 46 1161 44 1128 45 1140 45 1138 45 1140 45 1138 45 1148 45 1140 41 1052 41 1046 42 1064 31 Installation - Mechanical Table 6 Lifting Weights and CG Dimensions (Refer to Figure 14 - Figure 15) Unit 275 Ton 50 Hz Std Eff 275 Ton 60 Hz High Eff 275 Ton 60 Hz Std Eff 300 Ton 50 Hz High Eff 300 Ton 50 Hz Std Eff 300 Ton 60 Hz High Eff 300 Ton 60 Hz Std Eff 350 Ton 50 Hz High Eff 350 Ton 50 Hz Std Eff 350 Ton 60 Hz High Eff 350 Ton 60 Hz Std Eff 375 Ton 50 Hz High Eff 375 Ton 50 Hz Std Eff 400 Ton 50 Hz High Eff 400 Ton 50 Hz Std Eff 400 Ton 60 Hz High Eff 400 Ton 60 Hz Std Eff 450 Ton 60 Hz Std Eff 500 Ton 60 Hz Std Eff 140 Ton 50 Hz High Eff 140 Ton 50 Hz Std Eff 140 Ton 60 Hz High Eff 140 Ton 60 Hz Std Eff 155 Ton 50 Hz High Eff 155 Ton 50 Hz Std Eff 155 Ton 60 Hz High Eff 32 W1 W2 W3 W4 W5 W6 W7 W8 lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg 3668 1665 3251 1476 3345 1518 2955 1342 3328 1511 2955 1342 3456 1569 3278 1488 3018 1370 3140 1426 3374 1532 3393 1541 3328 1511 3345 1519 3299 1498 3345 1519 3299 1498 3423 1554 3363 1527 3194 1450 2863 1300 2936 1333 2628 1193 2917 1394 2628 1193 3074 1396 3258 1479 2998 1361 3123 1418 2998 1361 3372 1531 3296 1496 3271 1485 3279 1488 3271 1485 3279 1489 3402 1544 3289 1493 3478 1579 3571 1621 3351 1521 2892 1313 3564 1618 2892 1313 3615 1641 3179 1443 2933 1332 3038 1379 3772 1712 3278 1488 3116 1414 3377 1533 3201 1453 3377 1533 3201 1453 3307 1501 3395 1541 2877 1306 3505 1591 2947 1338 2495 1133 3393 1540 2495 1133 3393 1540 3055 1387 2824 1282 2912 1322 3767 1710 3086 1401 2859 1298 3350 1521 3077 1397 3350 1521 3077 1397 3116 1414 3368 1529 NA NA NA NA NA NA NA NA 2759 1253 NA 2432 1104 NA 2759 1253 NA 2432 1104 NA 2977 1352 2760 1253 2828 1284 NA 2957 1342 2740 1244 2811 1276 NA 2986 1356 2681 1217 3458 1570 3001 1362 3458 1570 3001 1362 3015 1369 3476 1578 2965 1346 2649 1202 3384 1536 2939 1334 3384 1536 2939 1334 2994 1359 3402 1544 2972 1348 2961 1343 2969 1347 2957 1341 4027 1827 3074 1394 3915 1776 3464 1571 3450 1565 3460 1569 3445 1563 4454 2020 3472 1575 4428 2009 3410 1547 3392 1539 3404 1544 3386 1536 3591 1629 3518 1596 3448 1564 3004 3356 1364 1524 3183 3894 1445 1768 2942 3356 1336 1523 2565 2822 1164 1281 3153 3802 1431 1726 2565 2782 1165 1263 3233 3774 1468 1713 3159 3075 1434 1396 2914 2844 1323 1291 3020 2930 1371 1330 3367 4172 1529 1894 3257 3108 1478 1411 3083 2892 1400 1313 3303 3425 1499 1555 3180 3098 1444 1406 3303 3425 1500 1555 3180 3098 1444 1406 3286 3137 1492 1424 3321 3442 1508 1563 Copper Fins 3805 NA 1726 3786 NA 1717 3799 NA 1723 3780 NA 1715 4018 NA 1823 3819 NA 1732 3961 NA 1797 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA Shipping Weight lbs kg Xcg Ycg in mm in mm 19577 8888 20266 9201 18876 8570 21548 9783 20314 9222 21508 9765 19572 8886 24936 11321 23031 10456 23803 10806 21450 9738 25444 11552 23903 10852 26912 12218 25073 11383 26913 12219 25074 11383 25678 11658 27056 12283 172 4376 203 5159 176 4473 222 5644 201 5100 222 5641 199 5044 234 5951 235 5956 234 5941 205 5197 266 6754 229 5827 274 6957 234 5951 274 6955 234 5951 266 6754 274 6955 41 1046 42 1064 42 1057 42 1059 42 1059 42 1062 42 1067 44 1125 44 1125 44 1125 42 1064 44 1125 44 1123 44 1115 44 1125 44 1118 44 1125 44 1125 44 1115 13651 6192 13589 6164 13631 6183 13569 6155 16091 7299 13883 6297 15752 7145 90 2289 90 2286 90 2289 90 2286 108 2743 90 2286 108 2736 45 1140 45 1140 45 1140 45 1140 44 1128 44 1125 45 1140 RTAC-SVX01F-EN Installation - Mechanical Table 6 Lifting Weights and CG Dimensions (Refer to Figure 14 - Figure 15) Unit 155 Ton 60 Hz Std Eff 170 Ton 50 Hz High Eff 170 Ton 50 Hz Std Eff 170Ton 60 Hz High Eff 170 Ton 60 Hz Std Eff 185 Ton 50 Hz High Eff 185 Ton 50 Hz Std Eff 185 Ton 60 Hz High Eff 185 Ton 60 Hz Std Eff 200 Ton 50 Hz High Eff 200 Ton 50 Hz Std Eff 200 Ton 60 Hz High Eff 200 Ton 60 Hz Std Eff 225 Ton 60 Hz Std Eff 250 Ton 60 Hz Std Eff 250 Ton 50 Hz High Eff 250 Ton 50 Hz Std Eff 275 Ton 50 Hz High Eff 275 Ton 50 Hz Std Eff 275 Ton 60 Hz High Eff 275 Ton 60 Hz Std Eff 300 Ton 50 Hz High Eff 300 Ton 50 Hz Std Eff 300 Ton 60 Hz High Eff 300 Ton 60 Hz Std Eff 350 Ton 50 Hz High Eff RTAC-SVX01F-EN W1 W2 W3 W4 W5 W6 W7 W8 lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg 2967 1346 4055 1839 3071 1393 3932 1784 2972 1348 4585 2080 4088 1854 4462 2024 4042 1834 4713 2138 4116 1867 4654 2111 4087 1854 4646 2108 4713 2138 4303 1954 3534 1605 4366 1982 4611 2093 4214 1913 4287 1946 3836 1742 4360 1980 3799 1725 4488 2038 4173 1895 3453 1566 4587 2081 3581 1624 4452 2019 3463 1571 5283 2396 4629 2100 5201 2359 4501 2042 5336 2420 4654 2111 5271 2391 4622 2097 5313 2410 5336 2420 3872 1758 3104 1409 3959 1797 4136 1878 3877 1760 3877 1760 3508 1592 3948 1792 3508 1593 4105 1864 4152 1885 3399 1542 3604 1635 3562 1616 3467 1573 3409 1546 4161 1888 3589 1628 4039 1832 3551 1611 4223 1916 3672 1666 4158 1886 3640 1651 4163 1888 4223 1916 4188 1901 3918 1779 4618 2097 4276 1941 4501 2043 4149 1884 3689 1675 4476 2032 3689 1675 4527 2055 4053 1840 3790 1719 4136 1876 3963 1798 3987 1808 3804 1725 4860 2204 4129 1873 4778 2167 4010 1819 4846 2198 4211 1910 4775 2166 4175 1894 4830 2191 4846 2198 3756 1705 3488 1583 4211 1912 3801 1725 4111 1866 3739 1698 3360 1526 4064 1845 3360 1525 4144 1881 4032 1830 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 4111 1866 4174 1895 4872 2212 4057 1842 4789 2174 4057 1842 3526 1601 4593 2085 3526 1601 4593 2085 3927 1783 3679 1670 3744 1700 4465 2027 3577 1624 4399 1997 3647 1656 3197 1451 4182 1899 3197 1451 4182 1899 3905 1773 NA NA NA NA NA NA NA NA NA NA NA NA 3379 1534 NA 3050 1385 NA 3379 1534 NA 3050 1385 NA 3808 1729 3787 1719 Shipping Weight lbs kg Xcg Ycg in mm in mm 13608 6173 16382 7431 14177 6431 15838 7184 13647 6190 18889 8568 16435 7455 18479 8382 16105 7305 19118 8672 16654 7554 18858 8554 16524 7495 18952 8597 19118 8672 23909 10855 21962 9971 26492 12027 24458 11104 25891 11754 23758 10786 27544 12505 25623 11633 27508 12489 26039 11822 31836 14453 90 2286 108 2743 90 2296 108 2738 90 2289 126 3211 108 2733 126 3211 108 2733 126 3200 108 2746 126 3198 108 2746 126 3200 126 3200 174 4422 183 4638 200 5070 171 4338 201 5093 174 4415 220 5575 197 4999 219 5573 195 4956 235 5956 45 1140 45 1140 45 1140 45 1140 45 1140 45 1151 45 1140 46 1158 45 1133 45 1140 45 1140 45 1140 45 1140 45 1146 45 1140 42 1067 42 1062 42 1077 42 1062 42 1077 42 1069 42 1074 42 1074 42 1074 43 1080 44 1125 33 Installation - Mechanical Table 6 Lifting Weights and CG Dimensions (Refer to Figure 14 - Figure 15) Unit 350 Ton 50 Hz Std Eff 350 Ton 60 Hz High Eff 350 Ton 60 Hz Std Eff 375 Ton 50 Hz High Eff 375 Ton 50 Hz Std Eff 400 Ton 50 Hz High Eff 400 Ton 50 Hz Std Eff 400 Ton 60 Hz High Eff 400 Ton 60 Hz Std Eff 450 Ton 60 Hz Std Eff 500 Ton 60 Hz Std Eff 140 Ton 50 Hz High Eff 140 Ton 50 Hz Std Eff 140 Ton 60 Hz High Eff 140 Ton 60 Hz Std Eff 155 Ton 50 Hz High Eff 155 Ton 50 Hz Std Eff 155 Ton 60 Hz High Eff 155 Ton 60 Hz Std Eff 170 Ton 50 Hz High Eff 170 Ton 50 Hz Std Eff 170Ton 60 Hz High Eff 170 Ton 60 Hz Std Eff 185 Ton 50 Hz High Eff 185 Ton 50 Hz Std Eff 185 Ton 60 Hz High Eff 34 W1 W2 W3 W4 W5 W6 W7 W8 lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg 3778 1715 4036 1832 4283 1944 4502 2044 4332 1967 4341 1971 4195 1904 4341 1971 4195 1905 4532 2057 4359 1979 3757 1705 4017 1824 3877 1760 4479 2034 4298 1951 4265 1936 4173 1894 4265 1936 4173 1895 4509 2047 4283 1945 2033 922 2030 921 2030 921 2026 919 2725 1236 2139 970 2612 1185 2031 921 2749 1247 2138 970 2626 1191 2033 922 3034 1376 2786 1264 2911 1320 2292 1040 2287 1038 2288 1038 2283 1036 2944 1335 2305 1046 2918 1323 2285 1037 3073 1394 2415 1096 2938 1332 2291 1039 3485 1581 3118 1414 3403 1544 3675 3654 3566 3545 3465 1668 1659 1619 1610 1573 3912 3893 3782 3763 3660 1776 1767 1717 1708 1661 4754 4348 5229 4823 NA 2158 1974 2374 2190 4244 4221 3863 3841 3592 1927 1916 1754 1744 1631 3984 3950 3618 3584 3274 1809 1793 1643 1627 1486 4367 4291 4406 4330 4433 1983 1948 2000 1966 2013 4075 4053 3950 3928 3832 1850 1840 1793 1783 1740 4367 4291 4406 4330 4433 1983 1948 2000 1966 2013 4075 4053 3950 3928 3832 1850 1840 1793 1783 1740 4273 4251 3892 3870 3621 1940 1930 1767 1757 1644 4385 4309 4424 4348 4451 1991 1956 2008 1974 2021 Remote Evaporator Aluminum Fins 1972 2244 NA NA NA 895 1018 1967 2238 NA NA NA 892 1015 1967 2238 NA NA NA 892 1015 1961 2232 NA NA NA 889 1013 2119 2337 NA NA NA 961 1060 2087 2265 NA NA NA 947 1027 1975 2281 NA NA NA 896 1034 1968 2236 NA NA NA 893 1014 2128 2451 NA NA NA 965 1112 2133 2411 NA NA NA 967 1094 1990 2302 NA NA NA 903 1044 1971 2243 NA NA NA 894 1018 2423 2875 NA NA NA 1099 1304 2116 2449 NA NA NA 960 1111 2300 2793 NA NA NA 1043 1267 3444 1563 3641 1653 NA 3569 1620 3240 1471 4357 1978 3810 1730 4357 1978 3810 1730 3598 1633 4375 1986 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA Shipping Weight lbs kg Xcg Ycg in mm in mm 28882 13113 30703 13939 27315 12401 32311 14669 30279 13747 34791 15795 32014 14534 34790 15795 32016 14535 32545 14775 34935 15860 235 5961 234 5949 204 5179 261 6632 227 5761 273 6939 235 5956 273 6939 234 5954 261 6634 273 6939 44 1125 44 1125 43 1080 44 1125 44 1123 44 1118 44 1125 44 1120 44 1125 44 1125 44 1118 8542 3875 8522 3866 8522 3866 8502 3857 10125 4593 8795 3989 9786 4439 8520 3865 10400 4717 9097 4126 9856 4471 8538 3873 11817 5360 10469 4749 11407 5174 86 2179 86 2177 86 2177 86 2177 104 2637 86 2177 103 2619 86 2177 104 2637 87 2197 103 2621 86 2179 122 3106 103 2621 122 3101 45 1138 45 1138 45 1138 45 1138 44 1115 44 1113 45 1138 45 1135 45 1138 45 1135 45 1138 45 1138 45 1153 45 1138 46 1166 RTAC-SVX01F-EN Installation - Mechanical Table 6 Lifting Weights and CG Dimensions (Refer to Figure 14 - Figure 15) Unit 185 Ton 60 Hz Std Eff 200 Ton 50 Hz High Eff 200 Ton 50 Hz Std Eff 200 Ton 60 Hz High Eff 200 Ton 60 Hz Std Eff 225 Ton 60 Hz Std Eff 250 Ton 60 Hz Std Eff 140 Ton 50 Hz High Eff 140 Ton 50 Hz Std Eff 140 Ton 60 Hz High Eff 140 Ton 60 Hz Std Eff 155 Ton 50 Hz High Eff 155 Ton 50 Hz Std Eff 155 Ton 60 Hz High Eff 155 Ton 60 Hz Std Eff 170 Ton 50 Hz High Eff 170 Ton 50 Hz Std Eff 170Ton 60 Hz High Eff 170 Ton 60 Hz Std Eff 185 Ton 50 Hz High Eff 185 Ton 50 Hz Std Eff 185 Ton 60 Hz High Eff 185 Ton 60 Hz Std Eff 200 Ton 50 Hz High Eff 200 Ton 50 Hz Std Eff 200 Ton 60 Hz High Eff RTAC-SVX01F-EN W1 W2 W3 W4 W5 W6 W7 W8 lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg 2740 1243 3156 1432 2811 1275 3097 1405 2781 1262 3096 1404 3156 1432 2991 1357 3531 1602 3140 1424 3466 1572 3108 1410 3516 1595 3531 1602 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 2506 1137 2503 1135 2503 1135 2499 1134 3472 1575 2612 1185 3359 1524 2505 1136 3496 1586 2611 1184 3373 1530 2506 1137 3969 1800 3532 1602 3846 1745 3487 1581 4092 1856 3557 1613 4033 1829 2883 1308 2878 1305 2878 1306 2874 1303 3810 1728 2896 1313 3783 1716 2876 1305 3938 1786 3006 1363 3803 1725 2882 1307 4570 2073 3984 1807 4487 2035 3857 1749 4615 2094 4006 1817 4551 2064 2079 2329 NA NA 943 1057 2478 2853 NA NA 1124 1294 2196 2525 NA NA 996 1146 2413 2782 NA NA 1095 1262 2163 2490 NA NA 981 1129 2425 2845 NA NA 1100 1290 2478 2853 NA NA 1124 1294 Remote Evaporator Copper Fins 2697 3031 NA NA 1223 1375 2691 3025 NA NA 1221 1372 2691 3025 NA NA 1221 1372 2685 3019 NA NA 1218 1369 2963 3301 NA NA 1344 1497 2811 3051 NA NA 1275 1384 2819 3244 NA NA 1279 1471 2692 3022 NA NA 1221 1371 2972 3414 NA NA 1348 1549 2857 3198 NA NA 1296 1450 2834 3265 NA NA 1286 1481 2695 3030 NA NA 1223 1374 3471 4072 NA NA 1575 1847 2960 3412 NA NA 1343 1548 3349 3990 NA NA 1519 1810 2923 3293 NA NA 1326 1494 3527 4050 NA NA 1600 1837 3040 3489 NA NA 1379 1583 3462 3979 NA NA 1570 1805 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA Shipping Weight lbs kg Xcg Ycg in mm in mm 10139 4599 12019 5452 10672 4841 11759 5334 10542 4782 11880 5389 12019 5452 103 2619 122 3091 104 2644 121 3084 104 2639 122 3091 122 3091 44 1123 45 1138 45 1138 45 1138 45 1138 45 1148 45 1138 11116 5042 11096 5033 11096 5033 11076 5024 13545 6144 11369 5157 13206 5990 11094 5032 13820 6269 11671 5294 13276 6022 11112 5040 16082 7295 13889 6300 15672 7109 13559 6150 16284 7386 14092 6392 16024 7269 88 2245 88 2245 88 2245 88 2245 107 2710 88 2243 106 2700 88 2245 107 2708 89 2258 106 2700 88 2245 125 3180 106 2697 125 3178 106 2697 125 3167 107 2713 125 3165 45 1140 45 1140 45 1140 45 1140 44 1123 44 1120 45 1140 45 1138 45 1140 45 1138 45 1140 45 1140 45 1151 45 1140 46 1161 45 1130 45 1140 45 1140 45 1140 35 Installation - Mechanical Table 6 Lifting Weights and CG Dimensions (Refer to Figure 14 - Figure 15) Unit 200 Ton 60 Hz Std Eff 225 Ton 60 Hz Std Eff 250 Ton 60 Hz Std Eff W1 W2 W3 W4 W5 W6 W7 W8 lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg 3528 1600 4031 1828 4092 1856 3974 1802 4600 2086 4615 2094 3007 1364 3473 1575 3527 1600 3453 1566 4042 1833 4050 1837 NA NA NA NA NA NA NA NA NA NA NA NA Table 7 Shipping Weight lbs kg Xcg Ycg in mm in mm 13962 6333 16145 7323 16284 7386 107 2710 125 3167 125 3167 45 1140 45 1148 45 1140 Remote Evaporator Lifting Weights Standard Eff Tonnage lbs Kg Premium Eff 140 155 170 185 200 225 250 140 155 170 185 200 2487 1128 2525 1145 2528 1146 2556 1159 2600 1179 2797 1268 2846 1291 2528 1146 2556 1159 2600 1179 2797 1268 2846 1291 Isolation and Sound Emission The most effective form of isolation is to locate the unit away from any sound sensitive area. Structurally transmitted sound can be reduced by elastomeric vibration eliminators. Spring isolators are not recommended. Consult an acoustical engineer in critical sound applications. For maximum isolation effect, isolate water lines and electrical conduit. Wall sleeves and rubber isolated piping hangers can be used to reduce the sound transmitted through water piping. To reduce the sound transmitted through electrical conduit, use flexible electrical conduit. State and local codes on sound emissions should always be considered. Since the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated. Sound power levels for Trane air-cooled Series R® chillers are available on request. 5NITS WITH #OMPRESSORS 5NITS WITH OR MORE #OMPRESSORS Figure 17 36 Unit Isolator Locations RTAC-SVX01F-EN Installation - Mechanical Table 8 Unit Isolators Tonnage Efficiency Frequency Unit Type Condenser Fin Material Isolator Part Number Quantity 140 140 140 155 155 155 170 170 170 185 185 185 185 185 185 185 185 200 200 200 200 200 200 200 200 225 225 225 225 250 250 250 250 250 250 275 300 350 350 350 375 400 450 500 Std/High Std/High Std/High Std/High Std/High Std/High Std/High Std/High Std/High Std High Std High Std High Std High Std High Std High Std High Std High Std Std Std High Std Std Std High Std High Std/High Std/High Std Std High Std/High Std/High Std/High Std 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 60 50/60 50/60 50/60 60 50 50 50/60 50/60 60 50 50/60 50 50/60 60 60 Packaged Remote Packaged/Remote Packaged Remote Packaged/Remote Packaged Remote Packaged/Remote Packaged Packaged Remote Remote Packaged Packaged Remote Remote Packaged Packaged Remote Remote Packaged Packaged Remote Remote Packaged Remote Packaged/Remote Packaged Packaged Remote Packaged/Remote Packaged Packaged Packaged Packaged Packaged Packaged Packaged Packaged Packaged Packaged Packaged Packaged AL AL Cu AL AL Cu AL AL Cu AL AL AL AL Cu Cu Cu Cu AL AL AL AL Cu Cu Cu Cu AL AL Cu Al/Cu AL AL Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu X10140305620 X10140305610 X10140305620 X10140305620 X10140305610 X10140305620 X10140305620 X10140305610 X10140305620 X10140305620 X10140305620 X10140305610 X10140305610 X10140305620 X10140305620 X10140305620 X10140305620 X10140305620 X10140305620 X10140305610 X10140305610 X10140305620 X10140305620 X10140305620 X10140305620 X10140305620 X10140305610 X10140305620 X10140305620 X10140305620 X10140305610 X10140305620 X10140305620 X10140305630 X10140305640 X10140305640 X10140305640 X10140305640 X10140305640 X10140305640 X10140305640 X10140305640 X10140305640 X10140305640 8 8 8 8 8 8 8 8 8 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Noise Considerations Locate the outdoor unit away from sound sensitive areas. If required, install rubber vibration isolators in all water piping and use flexible electrical conduit. Consult an acoustical engineer for critical applications. Also refer to Trane Engineering Bulletins for application information on RTAC chillers. RTAC-SVX01F-EN 37 Installation - Mechanical Foundation Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the outdoor unit operating weight (i.e., including completed piping, and full operating charges of refrigerant, oil and water). Refer to Table 1 though Table 5 in the General Information section for unit operating weights. Once in place, the outdoor unit must be level within 1/ 4" (6 mm) over its length and width. The Trane Company is not responsible for equipment problems resulting from an improperly designed or constructed foundation. NOTE: To allow for cleaning under the condensing coil, it is recommended that an opening be left between the unit base and the concrete pad. Clearances Provide enough space around the outdoor unit to allow the installation and maintenance personnel unrestricted access to all service points. Refer to submittal drawings for the unit dimensions. A minimum of 4 feet (1.2 m) is recommended for compressor service. Provide sufficient clearance for the opening of control panel doors. Refer to Figure 18 through Figure 19 for minimum clearances. In all cases, local codes which require additional clearances will take precedence over these recommendations. Figure 18 38 Recommended Unit Clearances 15-foot bases RTAC-SVX01F-EN Installation - Mechanical Figure 19 Recommended Unit Clearances 18-21 foot bases Figure 20 Recommended Unit Clearances 30-45 foot bases RTAC-SVX01F-EN 39 Installation - Mechanical Figure 21 Recommended Remote Evaporator Unit Clearances 15-30 foot bases Figure 22 Recommended Evaporator Clearance Unobstructed flow of condenser air is essential to maintain chiller capacity and operating efficiency. When determining unit placement, give careful consideration to assuring a sufficient flow of air across the condenser heat transfer surface. Two detrimental conditions are possible and must be avoided if optimum performance is to be achieved: warm air recirculation and coil starvation. Warm air recirculation occurs when discharge air from the condenser fans is recycled back to the condenser coil inlet. Coil starvation occurs when free airflow to (or from) the condenser is restricted. Both warm air recirculation and coil starvation cause reduction in unit efficiency and capacity due to the increased head pressures. 40 RTAC-SVX01F-EN Installation - Mechanical Debris, trash, supplies etc. should not be allowed to accumulate in the vicinity of the unit. Supply air movement may draw debris into the condenser coil, blocking spaces between coil fins and causing coil starvation. Special consideration should be given to low ambient units. Condenser coils and fan discharge must be kept free of snow or other obstructions to permit adequate airflow for satisfactory unit operation. In situations where equipment must be installed with less clearance than recommended, such as frequently occurs in retrofit and rooftop applications, restricted airflow is common. The Main Processor will direct the unit to make as much chilled water as possible given the actual installed conditions. Consult your Trane sales engineer for more details. NOTE: If the outdoor unit configuration requires a variance to the clearance dimensions, contact your Trane Sales Office Representative. Also refer to Trane Engineering Bulletins for application information on RTAC chillers. Unit Isolation and Leveling For additional reduction of sound and vibration, install the optional neoprene isolators. Construct an isolated concrete pad for the unit or provide concrete footings at the unit mounting points. Mount the unit directly to the concrete pads or footings. Level the unit using the base rail as a reference. The unit must be level within 1/4-in (6 mm) over the entire length and width. Use shims as necessary to level the unit. Neoprene Isolator Installation 1. Secure the isolators to the mounting surface using the mounting slots in the isolator base plate. Do not fully tighten the isolator mounting bolts at this time. 2. Align the mounting holes in the base of the unit with the threaded positioning pins on the top of the isolators. 3. Lower the unit onto the isolators and secure the isolator to the unit with a nut. Maximum isolator deflection should be 1/4 inch (6 mm). 4. Level the unit carefully. Fully tighten the isolator mounting bolts. Drainage Provide a large capacity drain for water vessel drain-down during shutdown or repair. The evaporator is provided with a drain connection. All local and national codes apply. The vent on the top of the evaporator waterbox is provided to prevent a vacuum by allowing air into the evaporator for complete drainage. Evaporator Water Piping Thoroughly flush all water piping to the unit before making the final piping connections to the unit. Evaporator Piping Components and layout will vary slightly, depending on the location of connections and the water source. CAUTION Evaporator Damage! The chilled water connections to the evaporator are to be “victaulic” type connections. Do not attempt to weld these connections, as the heat generated from welding can cause microscopic and macroscopic fractures on the cast iron waterboxes that can lead to premature failure of the waterbox. To prevent damage to chilled water components, do not allow evaporator pressure (maximum working pressure) to exceed 150 psig (10.5 bar). RTAC-SVX01F-EN 41 Installation - Mechanical Provide shutoff valves in lines to the gauges to isolate them from the system when they are not in use. Use rubber vibration eliminators to prevent vibration transmission through the water lines. If desired, install thermometers in the lines to monitor entering and leaving water temperatures. Install a balancing valve in the leaving water line to control water flow balance. Install shutoff valves on both the entering and leaving water lines so that the evaporator can be isolated for service. CAUTION Use Piping Strainers! To prevent evaporator damage, pipe strainers must be installed in the water supplies to protect components from water born debris. Trane is not responsible for equipment-only-damage caused by water born debris. “Piping components” include all devices and controls used to provide proper water system operation and unit operating safety. These components and their general locations are given below. Entering Chilled Water Piping • Air vents (to bleed air from system). • Water pressure gauges with shutoff valves. • Vibration eliminators. • Shutoff (isolation) valves. Thermometers (if desired). • Clean-out tees. • Pipe strainer. Leaving Chilled Water Piping • Air vents (to bleed air from system). • Water pressure gauges with shutoff valves. Vibration eliminators. • Shutoff (isolation) valves. • Thermometers. • Clean-out tees. • Balancing valve. • Flow Switch Evaporator Drain A1/2 inch drain connection is located under the outlet end of the evaporator waterbox. This may be connected to a suitable drain to permit evaporator drainage during unit servicing. A shutoff valve must be installed on the drain line. Evaporator Flow Switch Specific connection and schematic wiring diagrams are shipped with the unit. Some piping and control schemes, particularly those using a single water pump for both chilled and hot water, must be analyzed to determine how and or if a flow sensing device will provide desired operation. Follow the manufacturer’s recommendations for selection and installation procedures. General guidelines for flow switch installation are outlined below 1. Mount the switch upright, with a minimum of 5 pipe diameters of straight horizontal run on each side. Do not install close to elbows, orifices or valves. NOTE: The arrow on the switch must point in the direction of flow. 42 RTAC-SVX01F-EN Installation - Mechanical 2. To prevent switch fluttering, remove all air from the water system. NOTE: The CH530 provides a 6-second time delay after a “loss-of-flow” diagnostic before shutting the unit down. Contact a qualified service representative if nuisance machine shutdowns persist. 3. Adjust the switch to open when water flow falls below the minimum flow rate. Evaporator data is given in the General Information section. Flow switch contacts are closed on proof of water flow. 4. Install a pipe strainer in the entering evaporator water line to protect components from waterborne debris. Evaporator Water Pressure Drop RTAC 140 - 250 Ton Evaporator Water Pressure Drop 100 250S, 200H, 225H, 250H (60Hz) Pressure Drop (ft H2O) 225S, 185H 200S, 170H 10 185S, 155H 170S, 140H 155S 140S 1 100 1000 Flow Rate (GPM) Figure 23 Evaporator Water Pressure Drop RTAC-SVX01F-EN 43 Installation - Mechanical Evaporator Water Pressure Drop RTAC 250 - 500 Ton Water-Side Pressure Drop vs Flow Rate 100.0 250S (50Hz) 275S Pressure Drop (ft H2O) 300S, 250H (50Hz) 350S (60 Hz), 275H, 300H 350S (50Hz) 10.0 375S (50Hz) 400S, 350H 450S (60Hz), 375H (50Hz) 500S (60Hz), 400H 1.0 100 1000 10000 Flow Rate (GPM) Figure 24 Evaporator Water Pressure Drop CAUTION Proper Water Treatment! The use of untreated or improperly treated water in a unit may result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water. If using an acidic commercial flushing solution, construct a temporary bypass around the unit to prevent damage to internal components of the evaporator. Dirt, scale, products of corrosion and other foreign material will adversely affect heat transfer between the water and system components. Foreign matter in the chilled water system can also increase pressure drop and, consequently, reduce water flow. Proper water treatment must be determined locally, depending on the type of system and local water characteristics. 44 RTAC-SVX01F-EN Installation - Mechanical Neither salt nor brackish water is recommended for use in Trane air-cooled Series R® chillers. Use of either will lead to a shortened life to an indeterminable degree. The Trane Company encourages the employment of a reputable water treatment specialist, familiar with local water conditions, to assist in this determination and in the establishment of a proper water treatment program. Using untreated or improperly treated water in these units may result in inefficient operation and possible tube damage. Consult a qualified water treatment specialist to determine whether treatment is needed. The following disclamatory label is provided on each RTAC unit: NOTE: The use of improperly treated or untreated water in this equipment may result in scaling, erosion, corrosion, algae or slime. The services of a qualified water treatment specialist should be engaged to determine what treatment, if any, is advisable. The Trane Company warranty specifically excludes liability for corrosion, erosion or deterioration of Trane equipment. Water Pressure Gauges Install field-supplied pressure components as shown in Figure 25. Locate pressure gauges or taps in a straight run of pipe; avoid placement near elbows, etc. Be sure to install the gauges at the same elevation on each shell if the shells have opposite-end water connections. Figure 25 Suggested Piping for Typical RTAC Evaporator NOTE: Once the unit is installed at a site, one vertical or one diagonal unit support can be permanently removed if it creates an obstruction for water piping. To read manifolded pressure gauges, open one valve and close the other (depending upon the reading desired). This eliminates errors resulting from differently calibrated gauges installed at unmatched elevations. RTAC-SVX01F-EN 45 Installation - Mechanical Water Pressure Relief Valves CAUTION Shell Damage! To prevent shell damage, install pressure relief valves in the evaporator water system. Install a water pressure relief valve in the evaporator inlet piping between the evaporator and the inlet shutoff valve, as shown in Figure 25. Water vessels with close-coupled shutoff valves have a high potential for hydrostatic pressure buildup on a water temperature increase. Refer to applicable codes for relief valve installation guidelines. Freeze Protection If the unit will remain operational at subfreezing ambient temperatures, the chilled water system must be protected from freezing. Heaters are factory-installed on the packaged unit evaporator and will help protect it from freezing in ambient temperatures down to -20°F (-29°C). Install heat tape on all water piping, pumps, water box nozzles and other components that may be damaged if exposed to freezing temperatures. Heat tape must be designed for low ambient temperature applications. Heat tape selection should be based on the lowest expected ambient temperature. Add a non-freezing, low temperature, corrosion inhibiting, heat transfer fluid may also be added to the chilled water system. The solution must be strong enough to provide protection against ice formation at the lowest anticipated ambient temperature. Refer to Table 1 through Table 5 in the General Information section for evaporator water storage capacities. NOTE: Use of glycol type antifreeze reduces the cooling capacity of the unit and must be considered in the design of the system specifications. CAUTION Evaporator Damage! ALL unit chilled water pumps must be controlled by the Trane CH530 to avoid catastrophic damage to the evaporator due to freezing. Refer to RLC-PRB012-EN. Low Evaporator Refrigerant Cutout and % Glycol Recommendations 1. Solution freeze point is 4 deg F below operating point saturation temperature. 2. LRTC is 4 deg F below freeze point. Procedure 1. Is operating condition contained within Table 9? If no see “Special” below. 2. For leaving fluid temperatures greater than 40 deg F, use settings for 40 deg F. 3. Select operating conditions from Table 9. 4. Read off recommended % glycol. 5. Go to Table 10. From the % glycol. 46 RTAC-SVX01F-EN Installation - Mechanical Important 1. Additional glycol beyond the recommendations will adversely effect unit performance. The unit efficiency will be reduced and the saturated evaporator temperature will be reduced. For some operating conditions this effect can be significant. 2. If additional glycol is used, then use the actual % glycol to establish the low refrigerant cutout setpoint. 3. The minimum low refrigerant cutout setpoint allowed is -5 deg F. The minimum is established by the solubility limits of the oil in the refrigerant. Specials The following constitute a special that must be calculated by engineering: 1. Freeze inhibitor other than Ethylene Glycol or Propylene Glycol. 2. Fluid delta T outside the range 4 to 16 deg F. 3. Unit configuration other than Standard, Standard with extra pass, and Premium. 4. % Glycol greater than maximum in column in Table 10. Special should all be calculated by engineering. The purpose of calculating is to make sure that design saturation temperature is greater than 3 deg F. Additionally, the calculation must verify that the fluid freeze point is a minimum of 4 deg. F lower that the design saturation temperature. The low evaporator temperature cutout will be 4 deg F below the freeze point or -5 deg F, whichever is greater. RTAC-SVX01F-EN 47 Installation - Mechanical Table 9 Glycol Recommendations Ethylene Glycol DT 4 6 8 [F] [C] -15 -14 -13 10 12 14 16 Propylene Glycol 4 6 8 10 12 14 16 -12 -11 -10 -9 -15 -11 -10 -9 -14 -13 -12 Leaving Water Temperature (F/C) 38 -5 5 5 5 6 --6 6 7 7 8 -3 34 -11 11 11 12 ---13 13 15 17 --1 30 -15 16 17 18 ---19 21 -----1 28 -18 18 19 ----22 ------2 26 -20 21 22 ----25 ------3 24 -22 23 26 -----------4 22 -24 26 ------------6 20 -26 30 ------------7 18 -29 -------------8 16 ------31 --------9 14 ---30 -----------10 12 ---32 -----------11 10.4 34 --------------12 These tables represent the MINIMUM RECOMMENDED glycol percentages for each operating condition Operation is not recommended at certain operating conditions as some chillers may not satisfy maximum or minimum velocity requirements or minimum performance requirements. Contact Trane Sales Representative for more information regarding the operating limits of a particular chiller. Table 10 Recommended Low Evaporator Refrigerant Cutout and % Glycol % Glycol Ethylene Glycol Low Refrig. Temp Cutout °F °C Propylene Glycol Low Refrig. Temp Cutout °F °C Solution Freeze Point °F °C 0 28.0 -2.2 32 5 25.0 -3.9 29 0 28.0 -2.2 32.0 0 -1.7 25.3 -3.7 29.3 10 21.5 -5.8 -1.5 25.5 -3.6 22.4 -5.3 26.4 15 17.5 -3.1 -8.1 21.5 -5.8 19.1 -7.2 23.1 -4.9 20 25 12.8 -10.7 16.8 -8.4 15.3 -9.3 19.3 -7.1 7.4 -13.7 11.4 -11.4 10.8 -11.8 14.8 30 -9.6 1.1 -17.2 5.1 -15.0 5.3 -14.8 9.3 -12.6 35 -5.0 -20.6 -2.3 -19.1 -1.3 -19.5 2.7 -16.3 40 -5.0 -20.6 -10.8 -23.8 -5.0 -20.6 -5.2 -20.7 45 -5.0 -20.6 -20.7 -29.3 -5.0 -20.6 -14.6 -25.9 50 -5.0 -20.6 -32.1 -35.6 -5.0 -20.6 -25.8 -32.1 54 -5.0 -20.6 -42.3 -41.3 -5.0 -20.6 -36.1 -37.8 Solution Freeze Point °F °C Chilled Water Temperature Cutout should be set to 5°F below the lowest allowable Chilled Water Set Point bases on the %Glycol. 48 RTAC-SVX01F-EN Installation - Mechanical Remote Evaporator Option The RTAC 140-250 ton outdoor unit with the Remote Evaporator option is shipped as two pieces: the outdoor unit (condensing) and the evaporator. Short suction line connections are provided with the outdoor condensing unit. The remote evaporator is shipped complete, with factory-mounted electronic expansion valves, water temperature sensors, suction pressure transducers, liquid level control sensors, all factory wired to a ribbon cable. Solenoid valves and drain valves are wired to a relay board in the terminal box. The installing contractor is required to provide and install the following: • 2-wire, twisted shielded communication line between the remote evaporator terminal box and the Condensing Unit’s control panel • 115 VAC single phase power supply to the remote evaporator terminal box • 2 liquid lines • 2 suction lines • Suction accumulator as specified NOTE: A unit ordered as a remote evaporator must also be ordered with either the wide or low ambient option. The fan inverters are necessary for proper control. System Configuration and Interconnecting Refrigerant Piping The system may be configured in any of the four arrangements shown in Figure 26. The configurations and their associated elevations, along with the total distance between the remote evaporator and the compressor/condenser section, play a critical role in determining suction and liquid line sizes. This will also affect field refrigerant and oil charges. Consequently, there are physical limits which must not be violated if the system is to operate as designed. Please note the following requirements for field installation: 1. The remote evaporator MUST be matched with its respective outdoor condensing unit. 2. The circuit number on the outdoor condensing unit must match the circuit number on the evaporator, i.e. circuit #1 on the outdoor condensing unit must be connected with circuit # 1 on the remote evaporator and likewise for circuit #2. RTAC Circuit Capacities are shown in General Data Tables. CAUTION Equipment Damage! If the circuits are crossed, serious equipment damage may occur. 3. Piping between the evaporator and outdoor unit can not exceed 200 actual feet and/or an equivalent length of 300 feet. NOTE: The latter includes the equivalent length of all associated field installed fittings, valves, accessories and straight lengths of interconnecting piping. 4. Horizontal portions of suction lines must be downward sloping toward the compressor at least 1/2 inch for each 10 feet run. This promotes the movement of oil in the direction of gas flow. 5. Suction lines must be insulated. 6. The line sizes defined are to be used only for 40-60 F leaving water temperature and/or full load ice-making applications. RTAC-SVX01F-EN 49 Installation - Mechanical Remote Evaporator Option 7. Figure 26, drawing 1 depicts an installation where the remote evaporator elevation is the same as that of the outdoor condensing unit. The suction and liquid lines are horizontal or down flowing only. The suction and liquid lines can be put under ground or in a trench. The temperature of the suction lines must never exceed the temperature of the compressor. The line can be below the compressors a maximum of 15 ft. 8. Figure 26, drawing 2 shows a variation to drawing 1. The remote evaporator and outdoor condensing unit are at the same elevation but interconnecting piping may be installed up to 15 feet above the base elevation. Refer to Table 13 to determine the required length of the suction accumulator line. A full size suction accumulator is required at the evaporator and 50% of the value is required at the condensing unit. 9. A refrigerant drain valve is installed at the bottom of the evaporator for freeze protection. This drain valve is a normally open, pilot operated valve which remains closed unless there is a potential freezing situation detected via low evap temperatures or low water temperatures or a power failure. If the drain valve is opened the installed suction accumulator must be capable of holding the entire evaporator charge. Refer to Table 13 for sizing. 10. For installations where the remote evaporator is at a lower elevation than the outdoor condensing unit as shown in Figure 26, drawing 3, the elevation difference is not to exceed 100 feet. An inverted liquid line trap at the condensing unit is required to prevent unwanted free cooling. The apex of the liquid line trap should be at a height above the condenser coils. A suction accumulator must be installed at the evaporator. Refer to Table 13 for sizing. 11. When the elevation of the remote evaporator exceeds that of the outdoor condensing unit as shown in Figure 26, drawing 4, the elevation difference is determined by Table 11. The suction accumulator line must be installed according to Table 13. It is very important, for proper control and operation of the chiller, that the elevation requirements given in Table 11 are not exceeded. It should also be noted that in this configuration the suction accumulator is installed at the condensing section. Note: The height is limited by the available subcooling. 12. Compressor & oil separator heaters must be on at least 24 hours prior to compressor start. 50 RTAC-SVX01F-EN Installation - Mechanical Remote Evaporator Option Figure 26 Remote Evaporator Installations RTAC-SVX01F-EN 51 Installation - Mechanical Remote Evaporator Option Figure 27 52 Circuit Identification RTAC-SVX01F-EN Installation - Mechanical Remote Evaporator Option R TAC 140-250 To n R em o te E vap o rato r L iq u id L in e S izes 25 50 75 100 125 150 175 200 225 250 275 300 Total Equiv. Length (ft) 4 0 -5 0 F L vg . W a te r 25 50 75 100 125 150 175 200 225 250 275 300 Total Equiv. Length (ft) 4 0 -5 0 F L vg . W a te r Table 11 25 50 75 100 125 150 175 200 225 250 275 300 H eig h t (ft) 11 to 15 16 to 20 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.375 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 21 to 25 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 N /A N /A N /A 26 to 30 1.375 1.375 1.625 1.625 1.625 N /A N /A N /A N /A N /A N /A N /A 31 to 35 N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A 0 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1 to 5 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 6 to 10 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 1.625 H eig h t (ft) 11 to 15 16 to 20 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 1.625 2.125 1.625 2.125 1.625 2.125 2.125 2.125 21 to 25 1.375 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 26 to 30 2.125 N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A 31 to 35 N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A 0 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1 to 5 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 6 to 10 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 H eig h t (ft) 11 to 15 16 to 20 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 1.625 2.125 21 to 25 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 26 to 30 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 31 to 35 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 N /A 0 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1 to 5 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 6 to 10 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 2.125 H eig h t (ft) 11 to 15 16 to 20 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 21 to 25 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 26 to 30 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.625 2.625 2.625 31 to 35 2.125 2.125 2.625 2.625 2.625 2.625 2.625 2.625 N /A N /A N /A N /A 5 0 -6 0 F L vg . W a te r Total Equiv. Length (ft) 6 to 10 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 25 50 75 100 125 150 175 200 225 250 275 300 0 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1 to 5 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 6 to 10 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 1.625 H eig h t (ft) 11 to 15 16 to 20 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 1.625 2.125 1.625 2.125 2.125 2.125 2.125 2.125 21 to 25 1.375 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 26 to 30 2.125 2.125 N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A 0 1.375 1.375 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 1.625 2.125 1 to 5 1.375 1.375 1.375 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 6 to 10 1.375 1.375 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 H eig h t (ft) 11 to 15 16 to 20 1.375 2.125 1.625 2.125 1.625 N /A 2.125 N /A 2.125 N /A 2.125 N /A 2.125 N /A 2.125 N /A 2.125 N /A 2.125 N /A 2.125 N /A 2.125 N /A 21 to 25 N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A 26 to 30 N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A 0 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1 to 5 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 6 to 10 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 H eig h t (ft) 11 to 15 16 to 20 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 21 to 25 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 26 to 30 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.625 2.625 2.625 0 1.625 1.625 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 1 to 5 1.625 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 6 to 10 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 H eig h t (ft) 11 to 15 16 to 20 1.625 1.625 1.625 1.625 1.625 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.125 2.625 2.125 2.625 2.125 2.625 2.125 2.625 21 to 25 2.125 2.125 2.625 2.625 2.625 2.625 2.625 2.625 N /A N /A N /A N /A 26 to 30 N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A N /A 85-ton C ircuit 5 0 -6 0 F L vg . W a te r Total Equiv. Length (ft) Total Equiv. Length (ft) 4 0 -5 0 F L vg . W a te r 1 to 5 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 25 50 75 100 125 150 175 200 225 250 275 300 100-ton C ircuit 5 0 -6 0 F L vg . W a te r Total Equiv. Length (ft) 25 50 75 100 125 150 175 200 225 250 275 300 70-ton C ircuit 0 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 25 50 75 100 125 150 175 200 225 250 275 300 120-ton C ircuit 5 0 -6 0 F L vg . W a te r Total Equiv. Length (ft) Total Equiv. Length (ft) 4 0 -5 0 F L vg . W a te r 25 50 75 100 125 150 175 200 225 250 275 300 Liquid Line Sizes for Remote Evaporators (typical type L copper O.D.) Line Sizing To determine the appropriate outside diameter for field installed liquid and suction lines, it is first necessary to establish the equivalent length of pipe for each line. It is also necessary to know the capacity (tons) of each circuit. Circuit capacities for each RTAC unit are listed in the General Data Tables in Section1. RTAC-SVX01F-EN 53 Installation - Mechanical Remote Evaporator Option Table 12 Equivalent Lengths of Non-Ferrous Valves and Fittings (feet) Line Size Inches OD 1-1/8 1-3/8 1-5/8 2-1/8 2-5/8 3-1/8 3-5/8 4-1/8 Globe Valve 87 102 115 141 159 185 216 248 Short Angle Valve 29 33 34 39 44 53 66 76 Short Radius ELL 2.7 3.2 3.8 5.2 6.5 8 10 12 Long Radius ELL 1.9 2.2 2.6 3.4 4.2 5.1 6.3 7.3 Liquid Line Sizing Steps The steps to compute liquid line size are as follows: 1. Compute the actual length of field installed piping. 2. Multiply the length from step # 1 by 1.5 to estimate the equivalent length. 3. Refer to Table 11 to determine the outside diameter that corresponds to the equivalent length computed in step # 2 for the height and leaving water temperature of interest. Note: If the condenser is at the same elevation or above the evap, use the 0 ft. column. 4. With the outside diameter found in step # 3, use Table 12 to determine the equivalent lengths of each fitting in the field installed piping. 5. Sum the equivalent lengths of all the field installed elbows and valves. 6. Add the length found in step # 5 to the actual length from step # 1. This is your new equivalent line length. 7. Using Table 11 again, find the outside diameter that corresponds to the new equivalent line length from step # 6. If it is the same as step #3, this is the final equivalent length. Otherwise, proceed to the next step. 8. Using Table 12 and the new outside diameter found in step # 7, find the equivalent line length of each valve and fitting, and sum them. 9. Add the length found in step # 8 to the actual length from step # 1. This is the new equivalent line length. 10. With the equivalent line length found in step # 9, use Table 11 to select the proper outside diameter for the liquid lines. If the same as in step #7, this is your final equivalent line length. Otherwise, repeat step #7. 54 RTAC-SVX01F-EN Installation - Mechanical Remote Evaporator Option Required Length in Feet of Field Installed Suction Line Accumulator 70 Ton Circuit (1) 85 Ton Circuit 100 Ton Circuit 120 Ton Circuit 1 3/8" O.D. 1 5/8" O.D. 2 1/8" O.D. 1 3/8" O.D. 1 5/8" O.D. 2 1/8" O.D. 1 5/8" O.D. 2 1/8" O.D. 2 5/8" O.D. 1 5/8" O.D. 2 1/8" O.D. 2 5/8" O.D. Field Field Field Field Field Field Field Field Field Field Field Field Installed Installed Installed Installed Installed Installed Installed Installed Installed Installed Installed Installed Actual ft Liquid Line Liquid Line Liquid Line Liquid Line Liquid Line Liquid Line Liquid Line Liquid Line Liquid Line Liquid Line Liquid Line Liquid Line of field Length of 3 5/8" Length of 3 5/8" Length of 4 1/8" Length of 4 1/8" installed Suction Accumulator Suction Accumulator Suction Accumulator Suction Accumulator liquid line 10 43 44 45 52 52 53 43 44 46 52 53 54 20 45 46 49 53 54 57 45 47 50 53 55 58 30 46 48 52 54 56 60 46 49 53 55 58 62 40 48 50 55 56 58 63 48 52 57 56 60 66 50 49 52 59 57 60 67 49 55 61 58 63 70 60 51 54 62 59 62 70 51 57 65 59 66 74 70 52 56 65 60 64 73 53 60 69 61 68 78 80 53 58 69 62 66 77 54 62 73 62 71 81 90 55 60 72 63 68 80 56 65 77 64 73 85 100 56 62 75 64 70 83 57 68 81 66 76 89 110 58 64 79 66 72 87 59 70 85 67 79 93 120 59 66 82 67 74 90 60 73 89 69 81 97 130 61 68 85 69 76 93 62 75 93 70 84 101 140 62 70 89 70 78 97 63 78 97 72 86 105 150 64 72 92 72 80 100 65 81 101 73 89 109 160 65 74 95 73 82 103 67 83 105 75 92 113 170 66 76 99 75 84 107 68 86 108 76 94 117 180 68 78 102 76 86 110 70 88 112 78 97 121 190 69 79 105 77 88 113 71 91 116 80 99 125 200 71 81 109 79 90 117 73 94 120 81 102 129 (1) Note: Circuit 2 (M1) of 155 Ton Premium Unit requires an additional 10 feet of Suction Accumulator length. Table 13 Required Length of Field Installed Suction Accumulator NOTE: Location and quantity of suction accumulator is dependent upon the unit configuration. Example Liquid Line Sizing Figure 28 Liquid Line Sizing Example RTAC-SVX01F-EN 55 Installation - Mechanical Remote Evaporator Option For this example, refer to Table 11, Table 12 and Figure 28. Assume a 70 ton circuit and a leaving water temperature of 49 degrees F. 1. From Figure 28, the actual length of field installed piping is: 80 + 8 + 8 + 21 = 117 feet 2. Estimate equivalent line length: 117 feet x 1.5 = 175 feet 3. From Table 11 for a 70 ton circuit, for 175 equivalent feet the OD is 1.375 inches. Note: use the 0 ft. column since the condenser is above the evap 4. In Figure 28 there are six long-radius elbows. From Table 12, for 1.375 inch elbows, the equivalent feet is: 6 elbows x 2.2 feet = 13.2 feet 5. Adding equivalent feet from step #4 to step #1 gives: 13.2 feet + 117 feet = 130.2 feet 6. From Table 11, for a 70 ton circuit, for 125 equivalent feet (nearest to 130.2), the O.D. is 1- 3/8 inches. Liquid Line size = 1-3/8 inches Suction Line Sizing Steps Table 14 Suction Line Sizes Vertical/Upflow and Horizontal/Downflow Suction Lines O.D. (Type L Copper) LWT (F) 70 ton circuit 85ton circuit 100 ton circuit 120 ton circuit 40 - 60 3 5/8” 3 5/8” 4 1/8” 4 1/8” The steps to compute suction line size are as follows: 1. Break the suction line into it's Vertical/Upflow and Horizontal/Downflow components. 2. From Table 14, select the appropriate Vertical/Upflow suction line outside diameter according to the circuit tonnage. This is the diameter of the upflow suction line and any fittings in the upflow line. 3. From Table 14, select the appropriate Horizontal/Downflow suction line outside diameter according to the circuit tonnage. This is the diameter of the upflow suction line and any fittings in the upflow line. NOTE: The diameters of the upflow, and horizontal or downflow portions of the suction line may differ depending on the application. Example Suction Line Sizing For this example, refer to Table 14 and Figure 28 assume a 70 ton circuit and a leaving water temperature of 49 degrees F. 1. From Table 14, the vertical/upflow suction line is: 3 5/8” O.D. 2. From Table 14, the horizontal/downflow line is: 3 5/8” O.D. NOTE: In this example, the horizontal line is pitched downward in the direction of flow. 56 RTAC-SVX01F-EN Installation - Mechanical Remote Evaporator Option Suction Accumulator Sizing Use Table 13 to calculate length and size of the required suction accumulator(s). Example of Suction Accumulator Line Sizing Use Figure 28 and the same assumptions from the liquid line sizing example to calculate the suction accumulator line size and length. In this case the accumulator is installed at the evaporator. 1. Use the 70 ton circuit column. 2. From the liquid line sizing example, use a field installed liquid line of: 1.375 (1 3/8”) inches 3. The actual feet of liquid line installed is: 117 feet 4. The size of the suction accumulator is: 3 5/8 inches 5. The length of the suction line accumulator is: 59 feet Piping Installation Procedures The outdoor unit and the evaporator are shipped with a 25 psig holding pressure of dry nitrogen. Do not relieve this pressure until field installation of the refrigerant piping is to be accomplished. This will require the removal of the temporary pipe caps. NOTE: Use Type L refrigerant-grade copper tubing only. The refrigerant lines must be isolated to prevent line vibration from being transferred to the building. Do not secure the lines rigidly to the building at any point. All horizontal suction lines should be pitched downward, in the direction of flow, at a slope of 1/2 inch per 10 feet of run. Do not use a saw to remove end caps, as this may allow copper chips to contaminate the system. Use a tubing cutter or heat to remove the end caps. When sweating copper joints, flow dry nitrogen through the system. This prevents scale formation and the possible formation of an explosive mixture of R-134a and air. This will also prevent the formation of toxic phosgene gas, which occurs when refrigerant is exposed to open flame. WARNING Hazardous Gas! To prevent injury or death, due to explosion and/or inhalation of phosgene gas, purge the system thoroughly with dry nitrogen while sweating connections. Use a pressure regulator in the line between the unit and the high pressure nitrogen cylinder to avoid over-pressurization and possible explosion.Failure to use a nitrogen purge and pressure regulator could result in death or serious injury or equipment damage. RTAC-SVX01F-EN 57 Installation - Mechanical Remote Evaporator Option Refrigerant Sensors All necessary refrigerant devices, transducers and solenoids are factory installed and wired to the evaporator terminal box. Refrigerant Pressure Relief Valve Venting WARNING Hazardous Gases! Consult local regulations for any special relief line requirements. Refrigerant vented into a confined equipment room could displace available oxygen to breathe, causing possible asphyxiation or other serious health risks. Failure to follow these recommendations could result in death or serious injury. Vent pipe size must conform to the ANSI/ASHRAE Standard 15 for vent pipe sizing. All federal, state, and local codes take precedence over any suggestions stated in this manual. All relief valve venting is the responsibility of the installing contractor. All RTAC remote evaporator units use evaporator pressure relief valves (Figure 29) that must be vented to the outside of the building. Relief valve connection sizes and locations are shown in the unit submittals. Refer to local codes for relief valve vent line sizing information. Caution Equipment Damage! Do not exceed vent piping code specifications. Failure to comply with specifications may result in capacity reduction, unit damage and/or relief valve damage. Relief valve discharge setpoints and capacities rates are given in Table 12. Once the relief valve has opened, it will re-close when pressure is reduced to a safe level. Once opened, relief valves may have a tendency to leak and must be replaced. Pressure relief valve discharge capacities will vary with shell diameter and length and also compressor displacement. Discharge venting capacity should be calculated as required by ASHRAE Standard 15-94. Do not adjust relief valve setting in the field. Table 15 Pressure Relief Valve Data Valve Location Evap Discharge Setpoint (psi) 200 Number of Valves 2 Rated Capacity per Relief Valve (lba/min.) 28.9 Field Connection Pipe Size (in NPT) 3/4 Factory Shell Side Connection (in) 7/8 - 14 Leak Test and Evacuation After installation of the refrigerant piping, thoroughly test the system for leaks. Pressure test the system at pressures required by local codes. 58 RTAC-SVX01F-EN Installation - Mechanical Remote Evaporator Option WARNING Hazard of Explosion! Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or serious injury or equipment or property-only damage. For field evacuation, use a rotary-type vacuum pump capable of pulling a vacuum of 500 microns or less. Follow the pump manufacturer's instructions for proper use of the pump. The line used to connect the pump to the system should be copper and be the largest diameter that can be practically used. A larger line size with minimum flow resistance can significantly reduce evacuation time. Use the ports on the suction service valves and the liquid line shutoff valves for access to the system for evacuation. Ensure that the suction service valve, the liquid line shutoff valve, the oil line shutoff valve and any field installed valves are open in the proper position before evacuating. Insulate the entire suction line and the suction accumulator line. Where the line is exposed to the weather, wrap it with weatherproof tape and seal with weatherproof compound. Figure 29 Remote Evaporator RTAC-SVX01F-EN 59 Installation - Mechanical Remote Evaporator Option Figure 30 Field Wiring between Remote Evaporator and Condensing Unit Refrigerant and Additional Oil Charge Refrigerant Charge Determination The approximate amount of refrigerant charge required by the system must be determined by referring to Table 16 and must be verified by running the system and checking subcooling. Table 16 Field Installed Piping Charge Pipe O.D. (in) 1-3/8 1-5/8 2-1/8 2-5/8 3-1/8 3-5/8 4-1/8 60 Suction Line lbs of R134a per 100ft N/A N/A N/A N/A 5.0 6.8 8.8 Liquid Line lbs of R134a per 100ft 62.4 88.3 153.6 236.9 N/A N/A N/A RTAC-SVX01F-EN Installation - Mechanical Remote Evaporator Option 1. To determine the appropriate charge, first refer to the General Data Tables in Section 1 to establish the required charge without the field-installed piping. 2. Next, determine the charge required for the field-installed piping by referring to Table 16. 3. Sum the values of step 1 and step 2 to determine the circuit charge. NOTE: The amounts of refrigerant listed in Table 16 are per 100 feet of pipe. Requirements will be in direct proportion to the actual length of piping. Oil Charge Determination The unit is factory charged with the amount of oil required by the system, without the field-installed piping. The amount of the additional oil required is dependent upon the amount of refrigerant that is added to the system for the field installed piping. Use the following formula to calculate the amount of oil to be added: Pints of Oil = [lbs of R-134a added for field-installed piping]/100 RTAC-SVX01F-EN 61 Installation - Electrical General Recommendations All wiring must comply with local codes and the National Electric Code. Typical field wiring diagrams are included at the end of the manual. Minimum circuit ampacities and other unit electrical data are on the unit nameplate and in Table 17 though Table 19. See the unit order specifications for actual electrical data. Specific electrical schematics and connection diagrams are shipped with the unit. WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR CAUTION Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage. Important! Do not allow conduit to interfere with other components, structural members or equipment. Control voltage (115V) wiring in conduit must be separate from conduit carrying low voltage (<30V) wiring. Caution: To prevent control malfunctions, do not run low voltage wiring (<30V) in conduit with conductors carrying more than 30 volts. 62 RTAC-SVX01F-EN Installation - Electrical Table 17 Unit Electrical Data for Std. Efficiency at All Ambient Operation Unit Wiring Max. Fuse, # of HACR Power Breaker or Unit Rated Conns MCA (3) MOP (11) Size Voltage (1) Ckt1/Ckt2 Ckt1/Ckt2 660 800 RTAC 200/60/3 1 140 200/60/3 2 364/364 600/600 230/60/3 1 581 800 230/60/3 2 320/320 500/500 380/60/3 1 348 450 380/60/3 2 192/192 300/300 460/60/3 1 290 400 460/60/3 2 160/160 250/250 575/60/3 1 232 300 575/60/3 2 128/128 200/200 400/50/3 1 333 450 400/50/3 2 184/184 300/300 730 1000 RTAC 200/60/3 1 155 200/60/3 2 433/364 700/600 230/60/3 1 641 800 230/60/3 2 380/320 600/500 380/60/3 1 380 500 380/60/3 2 228/192 350/300 460/60/3 1 319 450 460/60/3 2 189/160 300/250 575/60/3 1 255 350 575/60/3 2 152/128 250/200 400/50/3 1 373 500 400/50/3 2 224/184 350/300 785 1000 RTAC 200/60/3 1 170 200/60/3 2 433/433 700/700 230/60/3 1 691 800 230/60/3 2 380/380 600/600 380/60/3 1 413 500 380/60/3 2 228/228 350/350 460/60/3 1 343 450 460/60/3 2 189/189 300/300 575/60/3 1 275 350 575/60/3 2 152/152 250/250 400/50/3 1 406 500 400/50/3 2 224/224 350/350 874 1200 RTAC 200/60/3 1 185 200/60/3 2 522/433 800/700 230/60/3 1 770 1000 230/60/3 2 459/380 700/600 380/60/3 1 460 600 380/60/3 2 275/228 450/350 460/60/3 1 382 500 460/60/3 2 228/189 350/300 575/60/3 1 306 400 575/60/3 2 183/152 300/250 400/50/3 1 446 600 400/50/3 2 264/224 450/350 RTAC-SVX01F-EN Motor Data Compressor (Each) Rec. Time Delay or RDE (4) Ckt1/Ckt2 800 450/450 700 400/400 400 250/250 350 200/200 300 175/175 400 250/250 1000 600/450 800 450/400 450 300/250 400 225/200 300 200/175 450 300/250 1000 600/600 800 450/450 500 300/300 400 225/225 350 200/200 450 300/300 1000 700/600 1000 600/450 600 350/300 450 300/225 350 225/200 500 350/300 Qty 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 RLA (5) Ckt1/Ckt2 270-270 270/270 235-235 235/235 142-142 142/142 118-118 118/118 94-94 94/94 138-138 138/138 320-270 320/270 278-235 278/235 168-142 168/142 139-118 139/118 111-94 111/94 168-138 168/138 320-320 320/320 278-278 278/278 168-168 168/168 139-139 139/139 111-111 111/111 168-168 168/168 386-320 386/320 336-278 336/278 203-168 203/168 168-139 168/139 134-111 134/111 198-168 198/168 Fans (Each) XLRA (8) Ckt1/Ckt2 1498-1498 1498/1498 1314-1314 1314/1314 801-801 801/801 652-652 652/652 520-520 520/520 774-774 774/774 1845-1498 1845/1498 1556-1314 1556/1314 973-801 973/801 774-652 774/652 631-528 631/528 896-796 896/796 1845-1845 1845/1845 1556-1556 1556/1556 973-973 973/973 774-774 774/774 631-631 631/631 896-896 896/896 2156-1845 2156/1845 1756-1556 1756/1556 1060-973 1060/973 878-774 878/774 705-631 705/631 1089-896 1089/896 YLRA (8) Ckt1/Ckt2 487-487 487/487 427-427 427/427 260-260 260/260 212-212 212/212 172-172 172/172 259-259 259/259 600-701 600/701 506-571 506/571 316-260 316/260 252-212 252/212 205-172 205/172 291-259 291/259 600-600 600/600 506-506 506/506 316-316 316/316 252-252 252/252 205-205 205/205 291-291 291/291 701-600 701/600 571-506 571/506 345-316 345/316 285-252 285/252 229-205 229/205 354-291 354/291 Qty. Ckt1/Ckt2 8 4/4 8 4/4 8 4/4 8 4/4 8 4/4 8 4/4 9 5/4 9 5/4 9 5/4 9 5/4 9 5/4 9 5/4 10 5/5 10 5/5 10 5/5 10 5/5 10 5/5 10 5/5 11 6/5 11 6/5 11 6/5 11 6/5 11 6/5 11 6/5 kW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 FLA 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 Control VA (7) 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 63 Installation - Electrical Table 17 Unit Electrical Data for Std. Efficiency at All Ambient Operation Unit Wiring Max. Fuse, # of HACR Power Breaker or Unit Rated Conns MCA (3) MOP (11) Size Voltage (1) Ckt1/Ckt2 Ckt1/Ckt2 947 1200 RTAC 200/60/3 1 200 200/60/3 2 522/522 800/800 230/60/3 1 834 1000 230/60/3 2 459/459 700/700 380/60/3 1 499 700 380/60/3 2 275/275 450/450 460/60/3 1 414 500 460/60/3 2 228/228 350/350 575/60/3 1 323 450 575/60/3 2 183/183 300/300 400/50/3 1 479 600 400/50/3 2 264/264 450/450 1045 1200 RTAC 200/60/3 1 225 200/60/3 2 620/522 1000/800 230/60/3 1 920 1200 230/60/3 2 545/459 800/700 380/60/3 1 551 700 380/60/3 2 327/275 500/450 460/60/3 1 457 600 460/60/3 2 271/228 450/350 575/60/3 1 367 500 575/60/3 2 218/183 350/300 1124 1200 RTAC 200/60/3 1 250 200/60/3 2 620/620 1000/1000 230/60/3 1 989 1200 230/60/3 2 545/545 800/800 380/60/3 1 594 800 380/60/3 2 327/327 500/500 460/60/3 1 492 600 460/60/3 2 271/271 450/450 575/60/3 1 395 500 575/60/3 2 218/218 350/350 400/50/3 1 563 700 400/50/3 2 333/265 450/450 NA RTAC 200/60/3 1 275 200/60/3 2 785/522 1000/800 230/60/3 1 NA 230/60/3 2 681/459 800/700 380/60/3 1 NA 380/60/3 2 413/275 500/450 460/60/3 1 536 700 460/60/3 2 343/228 450/350 575/60/3 1 430 500 575/60/3 2 275/183 350/300 400/50/3 1 629 800 400/50/3 2 406/265 500/450 64 Motor Data Compressor (Each) Fans (Each) Rec. Time Delay or RDE (4) Ckt1/Ckt2 1200 700/700 1000 600/600 600 350/350 500 300/300 400 225/225 600 350/350 1200 800/700 1200 700/600 700 400/350 600 350/300 450 300/225 1200 800/800 1200 700/700 700 400/400 600 350/350 500 300/300 700 400/350 Qty 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 RLA (5) Ckt1/Ckt2 386-386 386/386 336-336 336/336 203-203 203/203 168-168 168/168 134-134 134/134 198-198 198/198 459-386 459/386 399-336 399/336 242-203 242/203 200-168 200/168 160-134 160/134 459-459 459/459 399-399 399/399 242-242 242/242 200-200 200/200 160-160 160/160 138-138-198 138/138/198 XLRA (8) Ckt1/Ckt2 2156-2156 2156/2156 1756-1756 1756/1756 1060-1060 1060/1060 878-878 878/878 705-705 705/705 1089-1089 1089/1089 2525-2156 2525/2156 2126-1756 2126/1756 1306-1060 1306/1060 1065-878 1065/878 853-705 853/705 2525-2525 2525/2525 2126-2126 2126/2126 1306-1306 1306/1306 1065-1065 1065/1065 853-853 853/853 796-796-1089 796/796/1089 YLRA (8) Ckt1/Ckt2 701-701 701/701 571-571 571/571 345-345 345/345 285-285 285/285 229-229 229/229 354-354 354/354 821-701 821/701 691-571 691/571 424-345 424/345 346-285 346/285 277-229 277/229 821-821 821/821 691-691 691/691 424-424 424/424 346-346 346/346 277-277 277/277 259-259-354 259/259/354 Qty. Ckt1/Ckt2 12 6/6 12 6/6 12 6/6 12 6/6 12 6/6 12 6/6 13 7/6 13 7/6 13 7/6 13 7/6 13 7/6 14 7/7 14 7/7 14 7/7 14 7/7 14 7/7 14 8/6 kW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 FLA 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 1000/700 3 320/320/386 1845/1845/2156 600/600/701 10/6 1.5 6.5 1.2 800/600 3 278/278/336 1556/1556/1756 506/506/571 10/6 1.5 6.5 1.2 500/350 600 400/300 500 350/225 700 450/350 3 3 3 3 3 3 3 168/168/203 139-139-168 139/139/168 111-111-134 111-111/134 168-168-198 168/168/198 973/973/1060 774-774-878 774/774/878 631-631-705 631/631/705 896-896-1089 896/896/1089 316/316/345 252-252-285 252/252/285 205-205-229 205/205/229 291-291-354 291/291/254 10/6 16 10/6 16 10/6 16 10/6 1.5 1.5 1.5 1.5 1.5 0.9 0.9 3.5 3.0 3.0 2.5 2.5 2.8 2.8 Control VA (7) 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 RTAC-SVX01F-EN Installation - Electrical Table 17 Unit Electrical Data for Std. Efficiency at All Ambient Operation Unit Wiring Max. Fuse, # of HACR Power Breaker or Unit Rated Conns MCA (3) MOP (11) Size Voltage (1) Ckt1/Ckt2 Ckt1/Ckt2 NA RTAC 200/60/3 1 300 200/60/3 2 947/522 1200/800 230/60/3 1 NA 230/60/3 2 834/459 1000/700 380/60/3 1 NA 380/60/3 2 499/275 700/450 460/60/3 1 600 700 460/60/3 2 414/228 500/350 575/60/3 1 481 600 575/60/3 2 332/183 450/300 400/50/3 1 694 800 400/50/3 2 480/265 600/450 NA RTAC 200/60/3 1 350 200/60/3 2 1124/522 1200/800 Motor Data Compressor (Each) Fans (Each) Rec. Time Delay or RDE (4) RLA (5) Ckt1/Ckt2 Qty Ckt1/Ckt2 XLRA (8) Ckt1/Ckt2 YLRA (8) Ckt1/Ckt2 Qty. Ckt1/Ckt2 kW Control FLA VA (7) 1200/700 3 386/386/386 2156/2156/2156 701/701/701 12/6 1.5 6.5 1.2 1000/600 3 336/336/336 1756/1756/1756 571/571/571 12/6 1.5 6.5 1.2 600/350 700 500/300 600 400/225 800 600/350 3 3 3 3 3 3 3 203/203/203 168-168-168 168/168/168 134-134-134 134/134/134 198-198-198 198/198/198 1060/1060/1060 878-878-878 878/878/878 705-705-705 705/705/705 1089-1089-1089 1089/1089/1089 345/345/345 285-285-285 285/285/285 229-229-229 229/229/229 354-354-354 354/354/354 12/6 18 12/6 18 12/6 18 12/6 1.5 1.5 1.5 1.5 1.5 0.9 0.9 3.5 3.0 3.0 2.5 2.5 2.8 2.8 1200/700 3 459/459/386 1845/1845/1845/ 1845 821/821/701 14/6 1.5 6.5 1.2 691/691/571 14/6 1.5 6.5 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 230/60/3 1 230/60/3 2 NA 989/459 1200/700 1200/600 3 399/399/336 1556/1556/1556/ 1556 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 1 2 1 2 1 2 1 NA 594/275 678 492/228 544 395/183 770 800/450 800 600/350 700 500/300 800 700/350 800 600/300 600 450/225 800 3 3 3 3 3 4 973/973/973/973 774-774-774-774 774/774/774/774 631-631-631-631 631/631/631/631 896-896-896-896 1.5 1.5 1.5 1.5 1.5 0.9 3.5 3.0 3.0 2.5 2.5 2.8 406/406 500/500 450/450 4 10/10 0.9 2.8 1.59 RTAC 400/50/3 1 375 400/50/3 2 844 1000 1000 4 22 0.9 2.8 1.59 480/406 600/500 600/450 4 424/424/345 346-346-285 346/346/285 277-277-229 277/277/229 291-291-291291 896/896/896/896 291/291/291/ 291 1089-1089-896-896 354-354-291291 1089/1089/896/896 354/354/291/ 291 14/6 20 14/6 20 14/6 20 400/50/3 2 242/242/203 200-200-168 200/200/168 160-160-134 160/160/134 168-168-168168 168/168/168/ 168 198-198-168168 198/198/168/ 168 12/10 0.9 2.8 1.59 RTAC 200/60/3 1 400 200/60/3 2 NA 947/947 1200/1200 1200/1200 4 386/386/386/ 386 2156/2156/2156/ 2156 701/701/701/ 701 14/14 1.5 6.5 1.59 230/60/3 1 230/60/3 2 NA 834/834 1000/1000 1000/1000 4 336/336/336/ 336 1756/1756/1756/ 1756 571/571/571/ 571 14/14 1.5 6.5 1.59 380/60/3 1 380/60/3 2 NA 499/499 700/700 600/600 4 3.5 1.59 800 800 4 28 1.5 3.0 1.59 460/60/3 2 414/414 500/500 500/500 4 14/14 1.5 3.0 1.59 575/60/3 1 630 700 700 4 28 1.5 2.5 1.59 575/60/3 2 332/332 450/450 400/400 4 14/14 1.5 2.5 1.59 400/50/3 1 909 1000 1000 4 28 0.9 2.8 1.59 400/50/3 2 480/480 600/600 600/600 4 345/345/345/ 345 285-285-285285 285/285/285/ 285 229-229-229229 229/229/229/ 229 354-354-354354 354/354/354/ 354 1.5 786 1060/1060/1060/ 1060 878-878-878-878 14/14 460/60/3 1 203/203/203/ 203 168-168-168168 168/168/168/ 168 134-134-134134 134/134/134/ 134 198-198-198198 198/198/198/ 198 14/14 0.9 2.8 1.59 RTAC-SVX01F-EN 878/878/878/878 705-705-705-705 705/705/705/705 1089-1089-10891089 1089/1089/1089/ 1089 1.2 1.2 1.2 1.2 1.2 1.59 65 Installation - Electrical Table 17 Unit Electrical Data for Std. Efficiency at All Ambient Operation Unit Wiring Max. Fuse, # of HACR Power Breaker or Unit Rated Conns MCA (3) MOP (11) Size Voltage (1) Ckt1/Ckt2 Ckt1/Ckt2 NA RTAC 200/60/3 1 450 200/60/3 2 1124/947 1200/1200 Motor Data Compressor (Each) Rec. Time Delay or RDE (4) RLA (5) Ckt1/Ckt2 Qty Ckt1/Ckt2 Fans (Each) XLRA (8) Ckt1/Ckt2 YLRA (8) Ckt1/Ckt2 Qty. Ckt1/Ckt2 kW Control FLA VA (7) 1200/1200 4 459/459/386/ 386 2525/2525/2156/ 2156 821/821/701/ 701 14/12 1.5 6.5 1.59 230/60/3 1 230/60/3 2 NA 989/834 1200/1000 1200/1000 4 399/399/336/ 336 2126/2126/1756/ 1756 691/691/571/ 571 14/12 1.5 6.5 1.59 380/60/3 1 380/60/3 2 NA 594/499 800/700 700/600 4 1.5 3.5 1.59 864 1000 1000 4 26 1.5 3.0 1.59 460/60/3 2 492/414 600/500 600/500 4 14/12 1.5 3.0 1.59 575/60/3 1 693 800 800 4 26 1.5 2.5 1.59 575/60/3 2 395/332 500/450 450/400 4 1306/1306/1060/ 424/424/345/ 1060 345 1065-1065-878-878 346-346-285285 1065/1065/878/878 346/346/285/ 285 853-853-705-705 277-277-229229 853/853/705/705 277/277/229/ 229 14/12 460/60/3 1 242/242/203/ 203 200-200-168168 200/200/168/ 168 160-160-134134 160/160/134/ 134 14/12 1.5 2.5 1.59 NA 1124/1124 1200/1200 1200/1200 4 459/459/459/ 459 2525/2525/2525/ 2525 821/821/821/ 821 14/14 1.5 6.5 1.59 230/60/3 1 230/60/3 2 NA 989/989 1200/1200 1200/1200 4 399/399/399/ 399 2126/2126/2126/ 2126 691/691/691/ 691 14/14 1.5 6.5 1.59 380/60/3 1 380/60/3 2 NA 594/594 800/800 700/700 4 3.5 1.59 1000 1000 4 28 1.5 3.0 1.59 460/60/3 2 490/490 600/600 600/600 4 14/14 1.5 3.0 1.59 575/60/3 1 745 800 800 4 28 1.5 2.5 1.59 575/60/3 2 393/393 500/500 450/450 4 424/424/424/ 424 346-346-346346 346/346/346/ 346 277-277-277277 277/277/277/ 277 1.5 929 1306/1306/1306/ 1306 1065-1065-10651065 1065/1065/1065/ 1065 853-853-853-853 14/14 460/60/3 1 242/242/242/ 242 200-200-200200 200/200/200/ 200 160-160-160160 160/160/160/ 160 14/14 1.5 2.5 1.59 RTAC 200/60/3 1 500 200/60/3 2 853/853/853/853 Notes: 1. As standard, 140-250 ton (60 Hz) units and 140-200 ton (50Hz) units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton (60Hz) units and 250-400 ton (50Hz) units have dual point power connections. Optional single point power connections are available on 380V, 460V 575V/50 Hz and 400V/50 Hz units. 2. Max Fuse or HACR type breaker = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA per NEC 440-22. (Use FLA per circuit, NOT FLA for the entire unit). 3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the condenser fans FLAs per NEC 440-33. 4. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second compressor RLA and the sum of the condenser fan FLAs. 5. RLA - Rated Load Amps - rated in accordance with UL Standard 1995. 6. Local codes may take precedence. 7. Control VA includes operational controls only. Does not include evaporator heaters. 8. XLRA - Locked Rotor Amps - based on full winding (x-line) start units. YLRA for wye-delta starters is ~1/3 of LRA of x-line units. 9. Voltage Utilization Range: Rated Voltage 200/60/3 230/60/3 380/60/3 460/60/3 575/60/3 400/50/3 Use Range 180-220 208-254 342-418 414-506 516-633 360-440 10. A separate 115/60/1, 20 amp or 220/50/1, 15 amp customer provided power connection is required to power the evaporator heaters (1640 watts). 11. If factory circuit breakers are supplied with the chiller, then these values represent Maximum Overcurrent Protection (MOP). 66 RTAC-SVX01F-EN Installation - Electrical Table 18 Unit Size RTAC 140 RTAC 155 RTAC 170 RTAC 185 Unit Electrical Data for High Efficiency at Std. Ambient Operation Rated Voltage 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 Unit Wiring Max. Fuse, # of HACR Power MCA (3) Breaker or Conns Ckt1/ MOP (11) (1) Ckt2 Ckt1/Ckt2 1 648 800 2 356/356 600/600 1 572 700 2 314/314 500/500 1 341 450 2 188/188 300/300 1 285 350 2 157/157 250/250 1 228 300 2 125/125 200/200 1 325 450 2 179/179 300/300 1 712 1000 2 421/356 700/600 1 628 800 2 371/314 600/500 1 376 500 2 222/188 350/300 1 313 400 2 185/157 300/250 1 250 350 2 148/125 250/200 1 363 500 2 217/179 350/300 1 765 1000 2 421/421 700/700 1 675 800 2 371/371 600/600 1 404 500 2 222/222 350/350 1 336 450 2 185/185 300/300 1 269 350 2 148/148 250/250 1 394 500 2 217/217 350/350 1 856 1200 2 512/421 800/700 1 755 1000 2 451/371 700/600 1 452 600 2 270/222 450/350 1 375 500 2 224/185 350/300 1 301 400 2 180/148 300/250 1 433 600 2 256/217 400/350 RTAC-SVX01F-EN Motor Data Compressor (Each) Rec. Time Delay or RDE (4) Ckt1/Ckt 2 800 450/450 700 400/400 400 225/225 350 200/200 250 150/150 400 225/225 800 500/450 700 450/400 416 300/225 350 225/200 300 175/150 450 300/225 1000 500/500 800 450/450 450 300/300 400 225/225 300 175/175 450 300/300 1000 700/500 1000 600/450 500 350/300 450 300/225 350 225/175 500 350/300 Qty 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 RLA (5) Ckt1/Ckt2 259-259 259/259 225-225 225/225 136-136 136/136 113-113 113/113 90-90 90/90 132-132 132/132 305-259 305/259 265-225 265/225 161-136 161/136 133-113 133/113 106-90 106/90 160-132 160/132 305-305 305/305 265-265 265/265 161-161 161/161 133-133 133/133 106-106 106/106 160-160 160/160 373-305 373/305 324-265 324/265 196-161 196/161 162-133 162/133 130-106 130/106 189-160 189/160 XLRA (8) Ckt1/Ckt2 1498-1498 1498/1498 1314-1314 1314/1314 801-801 801/801 652-652 652/652 520-520 520/520 774-774 774/774 1845-1498 1845/1498 1556-1314 1556/1314 973-801 973/801 774-652 774/652 631-528 631/528 896-796 896/796 1845-1845 1845/1845 1556-1556 1556/1556 973-973 973/973 774-774 774/774 631-631 631/631 896-896 896/896 2156-1845 2156/1845 1756-1556 1756/1556 1060-973 1060/973 878-774 878/774 705-631 705/631 1089-896 1089/896 Fans (Each) YLRA (8) Ckt1/Ckt2 487-487 487/487 427-427 427/427 260-260 260/260 212-212 212/212 172-172 172/172 259-259 259/259 600-487 600/487 506-427 506/427 316-260 316/260 252-212 252/212 205-172 205/172 291-259 291/259 600-600 600/600 506-506 506/506 316-316 316/316 252-252 252/252 205-205 205/205 291-291 291/291 701-600 701/600 571-506 571/506 345-316 345/316 285-252 285/252 229-205 229/205 354-291 354/291 Qty. Ckt1/Ckt2 10 5/5 10 5/5 10 5/5 10 5/5 10 5/5 10 5/5 11 6/5 11 6/5 11 6/5 11 6/5 11 6/5 11 6/5 12 6/6 12 6/6 12 6/6 12 6/6 12 6/6 12 6/6 13 7/6 13 7/6 13 7/6 13 7/6 13 7/6 13 7/6 kW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 FLA 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 Control VA (7) 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 67 Installation - Electrical Table 18 Unit Size RTAC 200 RTAC 225 RTAC 250 RTAC 275 68 Unit Electrical Data for High Efficiency at Std. Ambient Operation Rated Voltage 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 Unit Wiring Max. Fuse, # of HACR Power MCA (3) Breaker or Conns Ckt1/ MOP (11) (1) Ckt2 Ckt1/Ckt2 1 931 1200 2 512/512 800/800 1 820 1000 2 451/451 700/700 1 490 600 2 270/270 450/450 1 407 500 2 224/224 350/350 1 328 450 2 180/180 300/300 1 464 600 2 256/256 400/400 1 1023 1200 2 611/506 1000/800 1 900 1200 2 537/544 800/700 1 539 700 2 322/266 500/450 1 447 600 2 267/221 450/350 1 359 500 2 214/178 350/300 1 1110 1200 2 611/611 1000/1000 1 977 1200 2 537/537 800/800 1 585 800 2 322/322 500/500 1 485 600 2 267/267 450/450 1 389 500 2 214/214 350/350 1 546 700 2 325/254 450/400 1 NA 2 765/506 1000/800 1 NA 2 675/444 800/700 1 NA 2 405/266 500/450 1 523 600 2 336/221 450/350 1 420 500 2 269/178 350/300 1 607 700 2 394/254 500/400 Motor Data Compressor (Each) Rec. Time Delay or RDE (4) Ckt1/Ckt 2 1200 700/700 1000 600/600 600 350/350 450 300/300 400 225/225 600 350/350 1200 800/600 1000 700/600 600 400/350 500 350/300 400 300/225 1200 800/800 1200 700/700 700 400/400 600 350/350 450 300/300 600 400/350 Qty 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 RLA (5) Ckt1/Ckt2 373-373 373/373 324-324 324/324 196-196 196/196 162-162 162/162 130-130 130/130 189-189 189/189 447-373 447/373 388-224 388/324 235-196 235/196 194-162 194/162 155-130 155/130 447-447 447/447 388-388 388/388 235-235 235/235 194/-194 194/194 155-155 155/155 132-132-189 132/132/189 XLRA (8) Ckt1/Ckt2 2156-2156 2156/2156 1756-1756 1756/1756 1060-1060 1060/1060 878-878 878/878 705-705 705/705 1089-1089 1089/1089 2525-2156 2525/2156 2126-1756 2126/1756 1306-1060 1306/1060 1065-878 1065/878 853-705 853/705 2525-2525 2525/2525 2126-2126 2126/2126 1306-1306 1306/1306 1065-1065 1065/1065 853-853 853/853 796-796-1089 796/796/1089 1000/600 3 305/305/373 800/600 3 450/350 600 400/300 450 300/225 700 450/350 3 3 3 3 3 3 3 Fans (Each) YLRA (8) Ckt1/Ckt2 701-701 701/701 571-571 571/571 345-345 345/345 285-285 285/285 229-229 229/229 354-354 354/354 821-701 821/701 691-571 691/571 424-345 424/345 346-285 346/285 277-229 277/229 821-821 821/821 691-691 691/691 424-424 424/424 346-346 346/346 277-277 277/277 259-259-354 259/259/354 kW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 FLA 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 Control VA (7) 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 1.2 1.2 1845/1845/2156 600/600/701 12/6 1.5 6.5 1.2 265/265/324 1556/1556/1756 506/506/571 12/6 1.5 6.5 1.2 161/161/196 133-133-162 133/133/162 106-106-130 106/106/130 160-160-189 160/160/189 973/973/1060 774-774-878 77/-774/878 631-631-705 631/631/705 896-896-1089 896/896/1089 1.5 1.5 1.5 1.5 1.5 0.9 0.9 3.5 3.0 3.0 2.5 2.5 2.8 2.8 1.2 1.2 1.2 1.2 1.2 1.2 1.2 316/316/345 252-252-285 252/252/285 205-205-229 205/205/229 291-291-354 291/291/254 Qty. Ckt1/Ckt2 14 7/7 14 7/7 14 7/7 14 7/7 14 7/7 14 7/7 14 8/6 14 8/6 14 8/6 14 8/6 14 8/6 16 8/8 16 8/8 16 8/8 16 8/8 7/4 8/8 16 10/6 12/6 18 12/6 18 12/6 18 12/6 RTAC-SVX01F-EN Installation - Electrical Table 18 Unit Size RTAC 300 RTAC 350 RTAC 375 Unit Electrical Data for High Efficiency at Std. Ambient Operation Rated Voltage 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 Unit Wiring Max. Fuse, # of HACR Power MCA (3) Breaker or Conns Ckt1/ MOP (11) (1) Ckt2 Ckt1/Ckt2 1 NA 2 931/506 1200/800 1 NA 2 820/444 1000/700 1 NA 2 490/266 600/450 1 587 700 2 407/221 500/350 1 473 500 2 328/178 450/300 1 671 800 2 465/254 600/400 1 NA 2 765/765 1000/1000 Motor Data Compressor (Each) 230/60/3 230/60/3 1 2 NA 675/675 800/800 800800 380/60/3 380/60/3 1 2 NA 405/405 500/500 460/60/3 1 638 460/60/3 2 336/336 RLA (5) Qty Ckt1/Ckt2 XLRA (8) Ckt1/Ckt2 1200/600 3 373/373/373 2156/2156/2156 701/701/701 14/6 1.5 6.5 1.2 1000/600 3 324/324/324 1756/1756/1756 571/571/571 14/6 1.5 6.5 1.2 600/350 700 450/300 500 400/225 800 600/350 3 3 3 3 3 3 3 196/196/196 162-162 - 162 162/162/162 130-130-130 130/130/130 189-189-189 189/189/189 1060/1060/1060 878-878-878 878/878/878 705-705-705 705/705/705 1089-1089-1089 1089/1089/1089 1000/1000 4 YLRA (8) Ckt1/Ckt2 Qty. Control Ckt1/Ckt2 kW FLA VA (7) 345/345/345 285-285-285 285/285/285 229-229-229 229/229/229 354-354-354 354/354/354 14/6 20 14/6 20 14/6 20 14/6 1.5 1.5 1.5 1.5 1.5 0.9 0.9 3.5 3.0 3.0 2.5 2.5 2.8 2.8 1.2 1.2 1.2 1.2 1.2 1.2 1.2 305/305/305/ 1845/1845/ 305 1845/1845 600/600/ 600/600 12/12 1.5 6.5 1.2 4 265/265/265/ 1556/1556/ 265 1556/1556 506/506/506/ 12/12 506 1.5 6.5 1.2 450/450 4 3.5 1.2 700 4 1.5 3.0 1.2 450/450 400/400 4 973/973/973/ 316/316/316/ 12/12 973 316 774-774-774-774 252-252-252- 24 252 774/774/774/774 252/252/252/ 12/12 252 1.5 700 161/161/161/ 161 133-133-133133 133/133/133/ 133 1.5 3.0 1.2 631-631-631631 631/631/631/ 631 896-896-896896 896/896/896/ 896 1089-1089896-896 1089/1089/ 896/896 24 1.5 2.5 1.2 12/12 1.5 2.5 1.2 24 0.9 2.8 1.59 12/12 0.9 2.8 1.59 26 0.9 2.8 1.59 14/12 0.9 2.8 1.59 575/60/3 1 511 600 600 4 575/60/3 2 269/269 350/350 300/300 4 400/50/3 1 748 800 800 4 400/50/3 2 394/394 500/500 450/450 4 400/50/3 1 819 1000 1000 4 400/50/3 2 465/394 600/500 600/450 4 RTAC-SVX01F-EN Fans (Each) Rec. Time Delay or RDE (4) Ckt1/Ckt 2 106-106106-106 106/106/ 106/106 160-160160-160 160/160/ 160/160 189-189160-160 189/189/ 160/160 205-205205-205 205/205/ 205/205 291-291291-291 291/291/ 291/291 354-354291-291 254/254/ 291/291 69 Installation - Electrical Table 18 Unit Size RTAC 400 Unit Electrical Data for High Efficiency at Std. Ambient Operation Rated Voltage Unit Wiring Max. Fuse, # of HACR Power MCA (3) Breaker or Conns Ckt1/ MOP (11) (1) Ckt2 Ckt1/Ckt2 Motor Data Compressor (Each) Rec. Time Delay or RDE (4) Ckt1/Ckt 2 RLA (5) Qty Ckt1/Ckt2 Fans (Each) XLRA (8) Ckt1/Ckt2 YLRA (8) Ckt1/Ckt2 Qty. Control Ckt1/Ckt2 kW FLA VA (7) 200/60/3 200/60/3 1 2 NA 931/931 1200/1200 1200/1200 4 373/373/ 373/373 2156/2156/ 2156/2156 701/701/ 701/701 14/14 1.5 6.5 1.59 230/60/3 230/60/3 1 2 NA 820/820 1000/1000 1000/1000 4 324/324/ 324/324 1756/1756/ 1756/1756 571/571/ 571/571 14/14 1.5 6.5 1.59 380/60/3 380/60/3 1 2 NA 490/490 600/600 600/600 4 3.5 1.59 773 800 800 4 28 1.5 3.0 1.59 460/60/3 2 407/407 500/500 450/450 4 14/14 1.5 3.0 1.59 575/60/3 1 623 700 700 4 28 1.5 2.5 1.59 575/60/3 2 328/328 450/450 400/400 4 14/14 1.5 2.5 1.59 400/50/3 1 882 1000 1000 4 28 0.9 2.8 1.59 400/50/3 2 465/465 600/600 600/600 4 345/345/ 345/345 285-285285-285 285/285/ 285/285 229-229229-229 229/229/ 229/229 354-354354-354 354/354/ 354/354 1.5 1 1060/1060/ 1060/1060 878-878-878878 878/878/878/ 878 705-705-705705 705/705/705/ 705 1089-10891089-1089 1089/1089/ 1089/1089 14/14 460/60/3 196/196/ 196/196 162-162162-162 162/162/ 162/162 130-130130-130 130/130/ 130/130 189-189189-189 189/189/ 189/189 14/14 0.9 2.8 1.59 Notes: 1. As standard, 140-250 ton (60 Hz) units and 140-200 ton (50Hz) units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton (60Hz) units and 250-400 ton (50Hz) units have dual point power connections. Optional single point power connections are available on 380V, 460V 575V/50 Hz and 400V/50 Hz units. 2. Max Fuse or HACR type breaker = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA per NEC 440-22. (Use FLA per circuit, NOT FLA for the entire unit). 3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the condenser fans FLAs per NEC 440-33. 4. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second compressor RLA and the sum of the condenser fan FLAs. 5. RLA - Rated Load Amps - rated in accordance with UL Standard 1995. 6. Local codes may take precedence. 7. Control VA includes operational controls only. Does not include evaporator heaters. 8. XLRA - Locked Rotor Amps - based on full winding (x-line) start units. YLRA for wye-delta starters is ~1/3 of LRA of x-line units. 9. Voltage Utilization Range: Rated Voltage 200/60/3 230/60/3 380/60/3 460/60/3 575/60/3 400/50/3 Use Range 180-220 208-254 342-418 414-506 516-633 360-440 10. A separate 115/60/1, 20 amp or 220/50/1, 15 amp customer provided power connection is required to power the evaporator heaters (1640 watts). 11. If factory circuit breakers are supplied with the chiller, then these values represent Maximum Overcurrent Protection (MOP). 70 RTAC-SVX01F-EN Installation - Electrical Table 19 Unit Size RTAC 140 RTAC 155 RTAC 170 RTAC 185 Unit Electrical Data for High Efficiency at High Ambient Operation Rated Voltage 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 Unit Wiring Max. Fuse, # of HACR Power Breaker or Conns MCA (3) MOP (11) (1) Ckt1/Ckt2 Ckt1/Ckt2 1 673 800 2 370/370 600/600 1 594 700 2 327/327 500/500 1 355 400 2 195/195 300/300 1 296 400 2 163/163 250/250 1 237 300 2 130/130 200/200 1 339 450 2 187/187 300/300 1 742 1000 2 439/370 700/600 1 654 800 2 387/327 600/500 1 391 500 2 231/195 350/300 1 325 450 2 192/163 300/250 1 261 350 2 154/130 250/200 1 379 500 2 227/187 350/300 1 798 1000 2 439/439 700/700 1 704 800 2 387/387 600/600 1 420 500 2 231/231 350/350 1 349 450 2 192/192 300/300 1 280 350 2 154/154 250/250 1 412 500 2 227/227 350/350 1 887 1200 2 528/439 800/700 1 783 1000 2 466/387 800/600 1 467 600 2 278/231 450/350 1 388 500 2 231/192 350/300 1 311 450 2 185/154 300/250 1 445 600 2 267/227 450/350 RTAC-SVX01F-EN Motor Data Compressor (Each) Rec. Time Delay or RDE (4) Ckt1/Ckt 2 800 450/450 700 400/400 400 250/250 350 200/200 300 175/175 400 225/225 1000 600/450 800 500/400 450 300/250 400 225/200 300 200/175 450 300/225 1000 600/600 800 500/500 500 300/300 400 225/225 350 200/200 500 300/300 1000 700/600 1000 600/500 600 350/300 450 300/225 350 225/200 500 350/300 Qty 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 RLA (5) Ckt1/Ckt2 270-270 270/270 235-235 235/235 142-142 142/142 118-118 118/118 94-94 94/94 138-138 138/138 320-270 320/270 278-235 278/235 168-142 168/142 139-118 139/118 111-94 111/94 168-138 168/138 320-320 320/320 278-278 278/278 168-168 168/168 139-139 139/139 111-111 111/111 168-168 168/168 386-320 386/320 336-278 336/278 203-168 203/168 168-139 168/139 134-111 134/111 198-168 198/168 XLRA (8) Ckt1/Ckt2 1498-1498 1498/1498 1314-1314 1314/1314 801-801 801/801 652-652 652/652 520-520 520/520 774-774 774/774 1845-1498 1845/1498 1556-1314 1556/1314 973-801 973/801 774-652 774/652 631-528 631/528 896-796 896/796 1845-1845 1845/1845 1556-1556 1556/1556 973-973 973/973 774-774 774/774 631-631 631/631 896-896 896/896 2156-1845 2156/1845 1756-1556 1756/1556 1060-973 1060/973 878-774 878/774 705-631 705/631 1089-896 1089/896 Fans (Each) YLRA (8) Ckt1/Ckt2 487-487 487/487 427-427 427/427 260-260 260/260 212-212 212/212 172-172 172/172 259-259 259/259 600-487 600/487 506-427 506/427 316-260 316/260 252-212 252/212 205-172 205/172 291-259 291/259 600-600 600/600 506-506 506/506 316-316 316/316 252-252 252/252 205-205 205/205 291-291 291/291 701-600 701/600 571-506 571/506 345-316 345/316 285-252 285/252 229-205 229/205 354-291 354/291 Qty. Ckt1/Ckt2 10 5/5 10 5/5 10 5/5 10 5/5 10 5/5 10 5/5 11 6/5 11 6/5 11 6/5 11 6/5 11 6/5 11 6/5 12 6/6 12 6/6 12 6/6 12 6/6 12 6/6 12 6/6 13 7/6 13 7/6 13 7/6 13 7/6 13 7/6 13 7/6 kW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 FLA 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 Control VA (7) 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 71 Installation - Electrical Table 19 Unit Size RTAC 200 RTAC 225 RTAC 250 RTAC 275 72 Unit Electrical Data for High Efficiency at High Ambient Operation Rated Voltage 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 200/60/3 200/60/3 230/60/3 230/60/3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 200/60/3 200/60/3 Unit Wiring Max. Fuse, # of HACR Power Breaker or Conns MCA (3) MOP (11) (1) Ckt1/Ckt2 Ckt1/Ckt2 1 960 1200 2 528/528 800/800 1 847 1000 2 466/466 800/800 1 506 700 2 278/278 450/450 1 420 500 2 231/231 350/350 1 337 450 2 185/185 300/300 1 485 600 2 267/267 450/450 1 1051 1200 2 626/522 1000/800 1 926 1200 2 551/459 800/700 1 555 700 2 331/275 500/450 1 460 600 2 274/228 450/350 1 369 500 2 220/183 350/300 1 1137 1200 2 626/626 1000/1000 1 1002 1200 2 551/551 800/800 1 601 800 2 331/331 500/500 1 498 600 2 274/274 450/450 1 400 500 2 220/220 350/350 1 569 700 2 339/265 450/450 1 NA 2 798/522 1000/800 Motor Data Compressor (Each) Rec. Time Delay or RDE (4) Ckt1/Ckt 2 1200 700/700 1000 600/600 600 350/350 500 300/300 400 225/225 600 350/350 1200 800/700 1200 700/600 700 400/350 600 350/300 450 300/225 1200 800/800 1200 700/700 700 400/400 600 350/350 450 300/300 700 400/350 Qty 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 1000/700 3 320/320/386 1845/1845/ 2156 230/60/3 230/60/3 1 2 NA 704/459 800/700 800/600 3 380/60/3 380/60/3 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 400/50/3 1 2 1 2 1 2 1 2 NA 420/275 542 349/228 435 280/183 634 412/265 500/450 700 450/350 500 350/300 800 500/450 500/350 600 400/300 500 350/225 700 500/350 3 3 3 3 3 3 3 RLA (5) Ckt1/Ckt2 386-386 386/386 336-336 336/336 203-203 203/203 168-168 168/168 134-134 134/134 198-198 198/198 459-358 459/358 399-336 399/336 242-203 242/203 200-168 200/168 160-134 160/134 459-459 459/459 399-399 399/399 242-242 242/242 200-200 200/200 160-160 160/160 138-138-198 138/138/198 Fans (Each) XLRA (8) YLRA (8) Ckt1/Ckt2 Ckt1/Ckt2 2156-2156 701-701 2156/2156 701/701 1756-1756 571-571 1756/1756 571/571 1060-1060 345-345 1060/1060 345/345 878-878 285-285 878/878 285/285 705-705 229-229 705/705 229/229 1089-1089 354-354 1089/1089 354/354 2525-2156 821-701 2525/2156 821/701 2126-1756 691-571 2126/1756 691/571 1306-1060 424-345 1306/1060 424/345 1065-878 346-285 1065/878 346/285 853-705 277-229 853/705 277/229 2525-2525 821-821 2525/2525 821/821 2126-2126 691-691 2126/2126 691/691 1306-1306 424-424 1306/1306 424/424 1065-1065 346-346 1065/1065 346/346 853-853 277-277 853/853 277/277 796-796-1089 259-259-354 796/796/1089 259/259/354 kW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.9 0.9 FLA 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 6.5 6.5 6.5 6.5 3.5 3.5 3.0 3.0 2.5 2.5 2.8 2.8 Control VA (7) 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 1.2 1.2 600/600/701 12/6 1.5 6.5 1.2 278/278/336 1556/1556/ 1756 506/506/571 12/6 1.5 6.5 1.2 168/168/203 139-139-168 139/139/168 111-111-134 111/111/134 168-168-168 168/168/168 316/316/345 252-252-285 252/252/285 205-205-229 205/205/229 291-291-354 291/291/254 1.5 1.5 1.5 1.5 1.5 0.9 0.9 3.5 3.0 3.0 2.5 2.5 2.8 2.8 1.2 1.2 1.2 1.2 1.2 1.2 1.2 973/973/1060 774-774-878 774/774/878 631-631-705 631/631/705 896-896-1089 896/896/1089 Qty. Ckt1/Ckt2 14 7/7 14 7/7 14 7/7 14 7/7 14 7/7 14 7/7 14 8/6 14 8/6 14 8/6 14 8/6 14 8/6 16 8/8 16 8/8 16 8/8 16 8/8 16 8/8 16 10/6 12/6 18 12/6 18 12/6 18 12/6 RTAC-SVX01F-EN Installation - Electrical Table 19 Unit Size RTAC 300 RTAC 350 RTAC 375 Unit Electrical Data for High Efficiency at High Ambient Operation Rated Voltage 200/60/3 200/60/3 Unit Wiring Max. Fuse, # of HACR Power Breaker or Conns MCA (3) MOP (11) (1) Ckt1/Ckt2 Ckt1/Ckt2 1 NA 2 960522 1200/800 Motor Data Compressor (Each) 1200/700 3 230/60/3 230/60/3 1 2 NA 847/459 1000/700 1000/600 380/60/3 380/60/3 1 2 NA 506/275 700/450 460/60/3 460/60/3 575/60/3 575/60/3 400/50/3 1 2 1 2 1 606 420/228 486 337/183 700 400/50/3 2 200/60/3 200/60/3 Rec. Time Delay or RDE (4) RLA (5) Ckt1/Ckt 2 Qty Ckt1/Ckt2 YLRA (8) Ckt1/Ckt2 Qty. Ckt1/Ckt2 kW FLA Control VA (7) 386/386/386 2156/2156/ 2156 701/701/701 14/6 1.5 6.5 1.2 3 336/336/336 1756/1756/ 1756 571/571/571 14/6 1.5 6.5 1.2 600/350 3 345/345/345 14/6 1.5 3.5 1.2 700 500/350 600 450/300 800 700 500/300 600 400/225 800 3 3 3 3 3 285-285-285 285/285/285 229-229-229 229/229/229 354-354-354 20 14/6 20 14/6 20 1.5 1.5 1.5 1.5 0.9 3.0 3.0 2.5 2.5 2.8 1.2 1.2 1.2 1.2 1.2 485/265 600/450 600/350 3 203/203/203 1060/1060/ 1060 168-168-168 878-878-878 168/168/168 878/878/87/ 134-134-134 705-705-705 134/134/134 705/705/705 198-198-198 1089-10891089 198/198/198 1089/1089/ 1089 354/354/354 14/6 0.9 2.8 1.2 1 2 NA 798/798 10001000 10001000 4 320/320/320/ 1845/1845/ 320 1845/1845 600/600/600/ 12/12 600 1.5 6.5 1.2 230/60/3 230/60/3 1 2 NA 704/704 800/800 800/800 4 278/278/278/ 1556/1556/ 278 1556/1556 506/506/506/ 12/12 506 1.5 6.5 1.2 380/60/3 380/60/3 1 2 NA 420/420 500/500 500/500 4 1.5 3.5 1.2 1 663 700 700 4 24 1.5 3.0 1.2 460/60/3 2 349/349 450/450 400/400 4 12/12 1.5 3.0 1.2 575/60/3 1 532 600 600 4 24 1.5 2.5 1.2 575/60/3 2 280/280 350/350 350/350 4 12/12 1.5 2.5 1.2 400/50/3 1 782 800 800 4 24 0.9 2.8 1.59 400/50/3 2 412/412 500/500 500/500 4 12/12 0.9 2.8 1.59 400/50/3 1 855 1000 1000 4 26 0.9 2.8 1.59 400/50/3 2 485/412 600/500 600/500 4 316/316/316/ 316 252-252-252252 252/252/252/ 252 205-205-205205 205/205/205/ 205 291-291-291291 291/291/291/ 291 354-354-291291 254/254/291/ 291 12/12 460/60/3 168/168/168/ 168 139-139-139139 139/139/139/ 139 111-111-111111 111/111/111/ 111 168-168-168168 168/168/168/ 168 198-198-168168 198/198/168/ 168 14/12 0.9 2.8 1.59 RTAC-SVX01F-EN XLRA (8) Ckt1/Ckt2 Fans (Each) 973/973/973/ 973 774-774-774774 774/774/774/ 774 631-631-631631 631/631/631/ 631 896-896-896896 896/896/896/ 896 1089-1089896-896 1089/1089/ 896/896 73 Installation - Electrical Table 19 Unit Size RTAC 400 Unit Electrical Data for High Efficiency at High Ambient Operation Rated Voltage 200/60/3 200/60/3 Unit Wiring Max. Fuse, # of HACR Power Breaker or Conns MCA (3) MOP (11) (1) Ckt1/Ckt2 Ckt1/Ckt2 1 NA 2 960/960 1200/1200 Motor Data Compressor (Each) 12001200 4 386/386/386/ 2156/2156/ 386 2156/2156 701/701/701/ 14/14 701 230/60/3 230/60/3 1 2 NA 847/847 1000/1000 1000/1000 4 336/336/336/ 1756/1756/ 336 1756/1756 380/60/3 380/60/3 1 2 NA 505/506 700/700 600/600 4 460/60/3 1 798 800 800 4 460/60/3 2 420/420 500/500 500/500 4 575/60/3 1 640 700 700 4 575/60/3 2 337/337 450/450 400/400 4 400/50/3 1 920 1000 1000 4 400/50/3 2 485/485 600/600 600/600 4 203/203/203/ 203 168-168-168168 168/168/168/ 16/ 134-134-134134 134/134/134/ 134/ 198-198-198198 198/198/198/ 198 Rec. Time Delay or RDE (4) RLA (5) Ckt1/Ckt 2 Qty Ckt1/Ckt2 XLRA (8) Ckt1/Ckt2 1060/1060/ 1060/1060 878-878-878878 878/878/878/ 878 705-705-705705 705/705/705/ 705 1089-10891089-1089 1089/1089/ 1089 Fans (Each) YLRA (8) Ckt1/Ckt2 Qty. Ckt1/Ckt2 kW FLA Control VA (7) 1.5 6.5 1.59 571/571/571/ 14/14 571 1.5 6.5 1.59 345/345/345/ 345 285-285-285285 285/285/285/ 285 229-229-229229 229/229/229/ 229 354-354-354354 354/354/354/ 354 14/14 1.5 3.5 1.59 28 1.5 3.0 1.59 14/14 1.5 3.0 1.59 28 1.5 2.5 1.59 14/14 1.5 2.5 1.59 28 0.9 2.8 1.59 14/14 0.9 2.8 1.59 Notes: As standard, 140-250 ton (60 Hz) units and 140-200 ton (50Hz) units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton (60Hz) units and 250-400 ton (50Hz) units have dual point power connections. Optional single point power connections are available on 380V, 460V 575V/50 Hz and 400V/50 Hz units. 2. Max Fuse or HACR type breaker = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA per NEC 440-22. (Use FLA per circuit, NOT FLA for the entire unit). 3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the condenser fans FLAs per NEC 440-33. 4. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second compressor RLA and the sum of the condenser fan FLAs. 5. RLA - Rated Load Amps - rated in accordance with UL Standard 1995. 6. Local codes may take precedence. 7. Control VA includes operational controls only. Does not include evaporator heaters. 8. XLRA - Locked Rotor Amps - based on full winding (x-line) start units. YLRA for wye-delta starters is ~1/3 of LRA of x-line units. Voltage Utilization Range: Rated Voltage 200/60/3 230/60/3 380/60/3 460/60/3 575/60/3 400/50/3 Use Range 180-220 208-254 342-418 414-506 516-633 360-440 9. A separate 115/60/1, 20 amp or 220/50/1, 15 amp customer provided power connection is required to power the evaporator heaters (1640 watts). 10. If factory circuit breakers are supplied with the chiller, then these values represent Maximum Overcurrent Protection (MOP). 1. 74 RTAC-SVX01F-EN Installation - Electrical Installer-Supplied Components Customer wiring interface connections are shown in the electrical schematics and connection diagrams that are shipped with the unit. The installer must provide the following components if not ordered with the unit: • Power supply wiring (in conduit) for all field-wired connections. • All control (interconnecting) wiring (in conduit) for field supplied devices. • Fused-disconnect switches or circuit breakers. • Power factor correction capacitors. (optional) Power Supply Wiring All power supply wiring must be sized and selected accordingly by the project engineer in accordance with NEC Table 310-16. WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR All wiring must comply with local codes and the National Electrical Code. The installing (or electrical) contractor must provide and install the system interconnecting wiring, as well as the power supply wiring. It must be properly sized and equipped with the appropriate fused disconnect switches. The type and installation location(s) of the fused disconnects must comply with all applicable codes. CAUTION Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage. Cut holes into the sides of the control panel for the appropriately-sized power wiring conduits. The wiring is passed through these conduits and connected to the terminal blocks, optional unit-mounted disconnects, or HACR type breakers. Refer to Figure 31. To provide proper phasing of 3-phase input, make connections as shown in field wiring diagrams and as stated on the WARNING label in the starter panel. For additional information on proper phasing, refer to “Unit Voltage Phasing.” Proper equipment ground must be provided to each ground connection in the panel (one for each customer-supplied conductor per phase). RTAC-SVX01F-EN 75 Installation - Electrical 115 volt field-provided connections (either control or power) are made through knockouts on the lower left side of the panel (Figure 31). Additional grounds may be required for each 115 volt power supply to the unit. Green lugs are provided for 115V customer wiring. Knockouts for 30 volt Cut holes for power wiring THIS AREA 115 volt field wiring Figure 31 Starter Panel Control Power Supply The unit is equipped with a control power transformer; it is not necessary to provide additional control power voltage to the unit. All units are factory-connected for appropriate labeled voltages except for the 400V/ 50Hz units which need the control power transformer (1T1) reconnected as noted below. NOTE: Important! As shipped, a normal 400 volt unit control power transformer is wired on the 400 volt tap (H3). Reconnect the appropriate transformer wire lead 126A to the tap (H2) for 380V/50Hz power supply or lead 126A to the tap H4 for the 415V/ 50 Hz power supply. It is also necessary to adjust the “unit voltage” setting using TechView (Configuration-Custom Tab). Heater Power Supply and Convenience Outlet (Packaged Units Only) The evaporator shell is insulated from ambient air and protected from freezing temperatures by two thermostatically-controlled immersion heaters and two strip heaters. Whenever the water temperature drops to approximately 37°F (2.8°C), the thermostat energizes the heaters. The heaters will provide protection from ambient temperatures down to -20°F (-29°C). It is required to provide an independent power source (115V 60Hz-20 amp, 220V 50Hz-15 amp), with a fused-disconnect. The heaters are factory-wired back to the unit control panel. 76 RTAC-SVX01F-EN Installation - Electrical CAUTION Heat Tape! Control panel main processor does not check for loss of power to the heat tape nor does it verify thermostat operation. A qualified technician must verify power to the heat tape and confirm operation of the heat tape thermostat to avoid catastrophic damage to the evaporator. A convenience outlet is also optional, which shares the same power supply as the heaters on 140-250 ton units. Be aware that when the heater is operating, the convenience outlet amperage draw will be reduced accordingly. NOTE: The convenience outlet is optional. The heaters are required. Interconnecting Wiring Chilled Water Flow (Pump) Interlock The Model RTAC Series R® chiller requires a field-supplied control voltage contact input through a flow proving switch 5S1 and an auxiliary contact 5K1 AUX. Connect the proving switch and auxiliary contact to 1TB5-8 and 1U11 J3-2. Refer to the field wiring for details. The auxiliary contact can be BAS signal, starter contactor auxiliary. or any signal which indicates the pump is running. A flow switch is still required and cannot be omitted. Chilled Water Pump Control An evaporator water pump output relay closes when the chiller is given a signal to go into the Auto mode of operation from any source. The contact is opened to turn off the pump in the event of most machine level diagnostics to prevent the build up of pump heat. CAUTION Evaporator Damage! IMPORTANT: ALL unit chilled water pumps must be controlled by the Trane CH530 to avoid catastrophic damage to the evaporator due to freezing. Refer to RLC-PRB012-EN. The relay output from 1U10 is required to operate the Evaporator Water Pump (EWP) contactor. Contacts should be compatible with 115/240 VAC control circuit. The EWP relay operates in different modes depending on CH530 or Tracer commands, if available, or service pumpdown (See maintenance section). Normally, the EWP relay follows the AUTO mode of the chiller. Whenever the chiller has no diagnostics and is in the AUTO mode, regardless of where the auto command is coming from, the normally open relay is energized. When the chiller exits the AUTO mode, the relay is timed open for an adjustable (using TechView) 0 to 30 minutes. The non-AUTO modes in which the pump is stopped, include Reset (88), Stop (00), External Stop (100), Remote Display Stop (600), Stopped by Tracer (300), Low Ambient Run Inhibit (200), and Ice Building complete (101). Regardless of whether the chiller is allowed to control the pump on a full-time basis, if the MP calls for a pump to start and water does not flow, the evaporator may be damaged catastrophically. It is the responsibility of the installing contractor and/or the customer to ensure that a pump will start when called upon by the chiller controls. RTAC-SVX01F-EN 77 Installation - Electrical Table 20 Pump Relay Operation Chiller Mode Auto Ice Building Tracer Override Stop Ice Complete Diagnostics Relay Operation Instant close Instant close Close TImed Open Instant Open Instant Open NOTE: Exceptions are listed below. When going from Stop to Auto, the EWP relay is energized immediately. If evaporator water flow is not established in 4 minutes and 15 sec., the CH530 de-energizes the EWP relay and generates a non-latching diagnostic. If flow returns (e.g. someone else is controlling the pump), the diagnostic is cleared, the EWP is re-energized, and normal control resumed. If evaporator water flow is lost once it had been established, the EWP relay remains energized and a non-latching diagnostic is generated. If flow returns, the diagnostic is cleared and the chiller returns to normal operation. In general, when there is either a non-latching or latching diagnostic, the EWP relay is turned off as though there was a zero time delay. Exceptions (see above table) whereby the relay continues to be energized occur with: A Low Chilled Water Temp. diagnostic (non-latching) (unless also accompanied by an Evap Leaving Water Temperature Sensor Diagnostic) or A starter contactor interrupt failure diagnostic, in which a compressor continues to draw current even after commanded to have shutdown or A Loss of Evaporator Water Flow diagnostic (non-latching) and the unit is in the AUTO mode, after initially having proven evaporator water flow. Alarm and Status Relay Outputs (Programmable Relays) A programmable relay concept provides for enunciation of certain events or states of the chiller, selected from a list of likely needs, while only using four physical output relays, as shown in the field wiring diagram. The four relays are provided (generally with a Quad Relay Output LLID) as part of the Alarm Relay Output Option. The relay’s contacts are isolated Form C (SPDT), suitable for use with 120 VAC circuits drawing up to 2.8 amps inductive, 7.2 amps resistive, or 1/3 HP and for 240 VAC circuits drawing up to 0.5 amp resistive. The list of events/states that can be assigned to the programmable relays can be found in Table 21. The relay will be energized when the event/state occurs. Table 21 Alarm and Status Relay Output Configuration Table Alarm - Latching Alarm - Auto Reset Alarm 78 Description This output is true whenever there is any active diagnostic that requires a manual reset to clear, that affects either the Chiller, the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics. This output is true whenever there is any active diagnostic that could automatically clear, that affects either the Chiller, the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics. This output is true whenever there is any diagnostic affecting any component, whether latching or automatically clearing. This classification does not include informational diagnostics RTAC-SVX01F-EN Installation - Electrical Table 21 Alarm and Status Relay Output Configuration Table Description This output is true whenever there is any diagnostic effecting Refrigerant Circuit 1, whether latching or automatically clearing, including diagnostics affecting the entire chiller. This classification does not include informational diagnostics. Alarm Ckt 2 This output is true whenever there is any diagnostic affecting Refrigerant Circuit 2 whether latching or automatically clearing, including diagnostics effecting the entire chiller. This classification does not include informational diagnostics. Chiller Limit Mode This output is true whenever the chiller has been running in one of the Unloading types of limit modes (with a 20 minute fil- (Condenser, Evaporator, Current Limit or Phase Imbalance Limit) continuously for the last 20 minutes. ter) Circuit 1 Running This output is true whenever any compressors are running (or commanded to be running) on Refrigerant Circuit 1, and false when no compressors are commanded to be running on that circuit. Circuit 2 Running This output is true whenever any compressors are running (or commanded to be running) on Refrigerant Circuit 2, and false when no compressors are commanded to be running on that circuit. Chiller Running This output is true whenever any compressors are running (or commanded to be running) on the chiller and false when no compressors are commanded to be running on the chiller. Maximum Capacity This output is true whenever the chiller has reached maximum capacity or had reached its maximum (software 18.0 or capacity and since that time has not fallen below 70% average current relative to the rated ARI current later) for the chiller. The output is false when the chiller falls below 70% average current and, since that time, had not reestablished maximum capacity. Alarm Ckt 1 Relay Assignments Using TechView CH530 Service Tool (TechView) is used to install the Alarm and Status Relay Option package and assign any of the above list of events or status to each of the four relays provided with the option. The relays to be programmed are referred to by the relay’s terminal numbers on the LLID board 1U12. The default assignments for the four available relays of the RTAC Alarm and Status Package Option are: Table 22 Default Assignments Relay Relay 1 Terminals J2 -12,11,10: Relay 2 Terminals J2 - 9,8,7: Relay 3 Terminals J2-6,5,4: Relay 4 Terminals J2-3,2,1: Alarm Chiller Running Maximum Capacity (software 18.0 or later) Chiller Limit If any of the Alarm/Status relays are used, provide electrical power, 115 VAC with fused-disconnect to the panel and wire through the appropriate relays (terminals on 1U12 (EUR=A4-5)). Provide wiring (switched hot, neutral, and ground connections) to the remote annunciation devices. Do not use power from the chiller’s control panel transformer to power these remote devices. Refer to the field diagrams which are shipped with the unit. Low Voltage Wiring The remote devices described below require low voltage wiring. All wiring to and from these remote input devices to the Control Panel must be made with shielded, twisted pair conductors. Be sure to ground the shielding only at the panel. To prevent control malfunctions, do not run low voltage wiring (<30 V) in conduit with conductors carrying more than 30 volts. Emergency Stop CH530 provides auxiliary control for a customer specified/installed latching trip out. When this customer-furnished remote contact 5K14 is provided, the chiller will run normally when the contact is closed. When the contact opens, the unit will trip on a manually resettable diagnostic. This condition requires manual reset at the chiller switch on the front of the control panel. Connect low voltage leads to terminal strip locations on 1U4. Refer to the field diagrams that are shipped with the unit. RTAC-SVX01F-EN 79 Installation - Electrical Silver or gold-plated contacts are recommended. These customer-furnished contacts must be compatible with 24 VDC, 12 mA resistive load. External Auto/Stop If the unit requires the external Auto/Stop function, the installer must provide leads from the remote contacts 5K15 to the proper terminals of the LLID 1U4 on the control panel. The chiller will run normally when the contacts are closed. When either contact opens, the compressor(s), if operating, will go to the RUN:UNLOAD operating mode and cycle off. Unit operation will be inhibited. Closure of the contacts will permit the unit to return to normal operation. Field-supplied contacts for all low voltage connections must be compatible with dry circuit 24 VDC for a 12 mA resistive load. Refer to the field diagrams that are shipped with the unit. External Circuit Lockout – Circuit #1 and Circuit #2 CH530 provides auxiliary control of a customer specified or installed contact closure, for individual operation of either Circuit #1 or #2. If the contact is closed, the refrigerant circuit will not operate 1K15 and 1K16. Upon contact opening, the refrigerant circuit will run normally. This feature is used to restrict total chiller operation, e.g. during emergency generator operations. Connections to 1U5 are shown in the field diagrams that are shipped with the unit. These customer-supplied contact closures must be compatible with 24 VDC, 12 mA resistive load. Silver or gold plated contacts are recommended. Ice Building Option CH530 provides auxiliary control for a customer specified/installed contact closure for ice building if so configured and enabled. This output is known as the Ice Building Status Relay. The normally open contact will be closed when ice building is in progress and open when ice building has been normally terminated either through Ice Termination setpoint being reached or removal of the Ice Building command. This output is for use with the ice storage system equipment or controls (provided by others) to signal the system changes required as the chiller mode changes from “ice building” to “ice complete”. When contact 5K18 is provided, the chiller will run normally when the contact is open. CH530 will accept either an isolated contact closure (External Ice Building command) or a Remote Communicated input (Tracer) to initiate and command the Ice Building mode. CH530 also provides a “Front Panel Ice Termination Setpoint”, settable through TechView, and adjustable from 20 to 31°F (-6.7 to -0.5°C) in at least 1°F (1°C) increments. NOTE: When in the Ice Building mode, and the evaporator entering water temperature drops below the ice termination setpoint, the chiller terminates the Ice Building mode and changes to the Ice Building Complete Mode. CAUTION Evaporator Damage! Freeze inhibitor must be adequate for the leaving water temperature. Failure to do so will result in damage to system components. Techview must also be used to enable or disable Ice Machine Control. This setting does not prevent the Tracer from commanding Ice Building mode. Upon contact closure, the CH530 will initiate an ice building mode, in which the unit runs fully loaded at all times. Ice building shall be terminated either by opening the contact or based on the entering evaporator water temperature. CH530 will not 80 RTAC-SVX01F-EN Installation - Electrical permit the ice building mode to be reentered until the unit has been switched out of ice building mode (open 5K18 contacts) and then switched back into ice building mode (close 5K18 contacts.) In ice building, all limits (freeze avoidance, evaporator, condenser, current) will be ignored. All safeties will be enforced. If, while in ice building mode, the unit gets down to the freeze stat setting (water or refrigerant), the unit will shut down on a manually resettable diagnostic, just as in normal operation. Connect leads from 5K18 to the proper terminals of 1U7. Refer to the field diagrams which are shipped with the unit. Silver or gold-plated contacts are recommended. These customer furnished contacts must be compatible with 24 VDC, 12 mA resistive load. External Chilled Water Setpoint (ECWS) Option The CH530 provides inputs that accept either 4-20 mA or 2-10 VDC signals to set the external chilled water setpoint (ECWS). This is not a reset function. The input defines the set point. This input is primarily used with generic BAS (building automation systems). The chilled water setpoint set via the DynaView or through digital communication with Tracer (Comm3). The arbitration of the various chilled water setpoint sources is described in the flow charts at the end of the section. The chilled water setpoint may be changed from a remote location by sending either a 2-10 VDC or 4-20 mA signal to the 1U6, terminals 5 and 6 LLID. 2-10 VDC and 4-20 mA each correspond to a 10 to 65°F (-12 to 18°C) external chilled water setpoint. The following equations apply: Voltage Signal Current Signal As generated from external source VDC=0.1455*(ECWS)+0.5454 mA=0.2909(ECWS)+1.0909 As processed by CH530 ECWS=6.875*(VDC)-3.75 ECWS=3.4375(mA)-3.75 If the ECWS input develops an open or short, the LLID will report either a very high or very low value back to the main processor. This will generate an informational diagnostic and the unit will default to using the Front Panel (DynaView) Chilled Water Setpoint. TechView Service Tool is used to set the input signal type from the factory default of 2-10 VDC to that of 4-20 mA. TechView is also used to install or remove the External Chilled Water Setpoint option as well as a means to enable and disable ECWS. External Current Limit Setpoint (ECLS) Option Similar to the above, the CH530 also provides for an optional External Current Limit Setpoint that will accept either a 2-10 VDC (default) or a 4-20 mA signal. The Current Limit Setting can also be set via the DynaView or through digital communication with Tracer (Comm 3). The arbitration of the various sources of current limit is described in the flow charts at the end of this section. The External Current Limit Setpoint may be changed from a remote location by hooking up the analog input signal to the 1 U6 LLID terminals 2 and 3. Refer to the following paragraph on Analog Input Signal Wiring Details. The following equations apply for ECLS: RTAC-SVX01F-EN Voltage Signal Current Signal As generated from external source VDC+0.133*(%)-6.0 mA=0.266*(%)-12.0 As processed by UCM %=7.5*(VDC)+45.0 %=3.75*(mA)+45.0 81 Installation - Electrical If the ECLS input develops an open or short, the LLID will report either a very high or very low value back to the man processor. This will generate an informational diagnostic and the unit will default to using the Front Panel (DynaView) Current Limit Setpoint. The TechView Service Tool must be used to set the input signal type from the factory default of 2-10 VDC to that of 4-20 mA current. TechView must be also be used to install or remove the External Current Limit Setpoint Option for field installation, or can be used to enable or disable the feature (if installed). ECLS and ECWS Analog Input Signal Wiring Details: Both the ECWS and ECLS can be connected and setup as either a 2-10 VDC (factory default), 4-20 mA, or resistance input (also a form of 4-2OmA) as indicated below. Depending on the type to be used, the TechView Service Tool must be used to configure the LLID and the MP for the proper input type that is being used. This is accomplished by a setting change on the Custom Tab of the Configuration View within TechView. The J2-3 and J2-6 terminal is chassis grounded and terminal J2- 1 and J2-4 can be used to source 12 VDC. The ECLS uses terminals J2-2 and J2-3. ECWS uses terminals J2-5 and J2-6. Both inputs are only compatible with high-side current sources. Figure 32 Wiring Examples for ECLS and ECWS Chilled Water Reset (CWR) CH530 resets the chilled water temperature set point based on either return water temperature, or outdoor air temperature. Return Reset is standard, Outdoor Reset is optional. The following shall be selectable: • One of three Reset Types: None, Return Water Temperature Reset, Outdoor Air Temperature Reset, or Constant Return Water Temperature Reset. • Reset Ratio Set Points. For outdoor air temperature reset there shall be both positive and negative reset ratio's. 82 RTAC-SVX01F-EN Installation - Electrical • Start Reset Set Points. • Maximum Reset Set Points. The equations for each type of reset are as follows: Return CWS' = CWS + RATIO (START RESET - (TWE - TWL)) and CWS' > or = CWS and CWS' - CWS < or = Maximum Reset Outdoor CWS' = CWS + RATIO * (START RESET - TOD) and CWS' > or = CWS and CWS' - CWS < or = Maximum Reset where CWS' is the new chilled water set point or the "reset CWS" CWS is the active chilled water set point before any reset has occurred, e.g. normally Front Panel, Tracer, or ECWS RESET RATIO is a user adjustable gain START RESET is a user adjustable reference TOD is the outdoor temperature TWE is entering evap. water temperature TWL is leaving evap. water temperature MAXIMUM RESET is a user adjustable limit providing the maximum amount of reset. For all types of reset, CWS' - CWS < or = Maximum Reset. Reset Type Return: Reset Ratio Range 10 to 120% Outdoor 80 to -80% Start Reset Range 4 to 30 F (2.2 to 16.7 C) 50 to 130 F (10 to 54.4 C) Maximum Reset Range 0 to 20 F (0.0 to 11.1 C) 0 to 20 F (0.0 to 11.1 C) Increment English Units 1% Increment SI Units 1% Factory Default Value 50% 1% 1% 10% In addition to Return and Outdoor Reset, the MP provides a menu item for the operator to select a Constant Return Reset. Constant Return Reset will reset the leaving water temperature set point so as to provide a constant entering water temperature. The Constant Return Reset equation is the same as the Return Reset equation except on selection of Constant Return Reset, the MP will automatically set Ratio, Start Reset, and Maximum Reset to the following. RATIO = 100% START RESET = Design Delta Temp. MAXIMUM RESET = Design Delta Temp. The equation for Constant Return is then as follows: CWS' = CWS + 100% (Design Delta Temp. - (TWE - TWL)) and CWS' > or = CWS and CWS' - CWS < or = Maximum Reset When any type of CWR is enabled, the MP will step the Active CWS toward the desired CWS' (based on the above equations and setup parameters) at a rate of 1 degree F every 5 minutes until the Active CWS equals the desired CWS'. This applies when the chiller is running. RTAC-SVX01F-EN 83 Installation - Electrical When the chiller is not running the CWS is reset immediately (within one minute) for Return Reset and at a rate of 1 degree F every 5 minutes for Outdoor Reset. The chiller will start at the Differential to Start value above a fully reset CWS or CWS' for both Return and Outdoor Reset. Communications Interface options Optional Tracer Communications Interface This option allows the Tracer CH530 controller to exchange information (e.g. operating setpoints and Auto/Standby commands) with a higher-level control device, such as a Tracer Summit or a multiple-machine controller. A shielded, twisted pair connection establishes the bi-directional communications link between the Tracer CH530 and the building automation system. To prevent control malfunctions, do not run low voltage wiring (<30 V) in conduit with conductors carrying more than 30 volts. Field wiring for the communication link must meet the following requirements: • All wiring must be in accordance with the NEC and local codes. • Communication link wiring must be shielded, twisted pair wiring (Belden 8760 or equivalent). See the table below for wire size selection: Table 23 Wire Size Wire Size Maximum Length of Communication Wire 14 AWG (2.5 mm2) 16 AWG (1.5 mm2) 18 AWG (1.0 mm2) 5,000 FT (1525 m) 2,000 FT (610 m) 1,000 FT (305 m) • The communication link cannot pass between buildings. • All units on the communication link can be connected in a “daisy chain” configuration. LonTalk Communications Interface for Chillers (LCI-C) CH530 provides an optional LonTalk Communication Interface (LCI-C) between the chiller and a Building Automation System (BAS). An LCI-C LLID shall be used to provide "gateway" functionality between a LonTalk compatible device and the Chiller. The inputs/outputs include both mandatory and optional network variables as established by the LonMark Functional Chiller Profile 8040. Installation Recommendations • 22 AWG Level 4 unshielded communication wire recommended for most LCI-C installations • LCI-C link limits: 4500 feet, 60 devices • Termination resistors are required – 105 ohms at each end for Level 4 wire – 82 ohms at each end for Trane "purple" wire • LCI-C topology should be daisy chain 84 • Zone sensor communication stubs limited to 8 per link, 50 feet each (maximum) • One repeater can be used for an additional 4500 feet, 60 devices, 8 communication stubs RTAC-SVX01F-EN Installation - Electrical Table 24 LonTalk Points List LonTalk Communications Interface Inputs Variable type Chiller Enable/Disable binary start(1)/stop(0) Chilled Water Setpoint analog temperature Current Limit Setpoint analog % current Chiller Mode Note 1 Outputs Variable type Outputs Variable type Chiller On/Off binary on(1)/off(0) Active Chilled Water Setpoint analog temperature Percent RLA analog % current Active Current Limit Setpoint analog % current Leaving Chilled Water Temperature analog temperature Entering Chilled Water Temperature analog temperature Entering Condenser Water Temperature analog temperature Leaving Condenser Water Temperature analog temperature Alarm Description Note 2 Chiller Status Note 3 Note 1: Chiller Mode is used to place the chiller into an alternate mode; Cool or Ice Build Note 2: Alarm Description denotes alarm severity and target. Severity: no alarm, warning, normal shutdown, immediate shutdown Target: Chiller, Platform, Ice Building (Chiller is refrigerant circuit and Platform is control circuit) Note 3: Chiller Status describes Chiller Run Mode and Chiller Operating Mode. Run Modes: Off, Starting, Running, Shutting Down Operating Modes: Cool, Ice Build States: Alarm, Run Enabled, Local Control, Limited, CHW Flow, Cond Flow RTAC-SVX01F-EN SNVT_Type SNVT_switch SNVT_temp_p SNVT_lev_percent SNVT_hvac_mode SNVT_Type SNVT_Type SNVT_switch SNVT_temp_p SNVT_lev_percent SNVT_lev_percent SNVT_temp_p SNVT_temp_p SNVT_temp_p SNVT_temp_p SNVT_str_asc SNVT_chlr_status 85 Operating Principles This section contains an overview of the operation and maintenance of RTAC units equipped with CH530 control systems. It describes the overall operating principles of the RTAC design. Refrigeration Cycle The refrigeration cycle of the RTAC chiller is similar to that of the RTAA air cooled water chiller. The exception is that the evaporating and condensing temperatures have been increased to allow for optimization of the chiller and reduced foot print. The refrigeration cycle is represented in the pressure enthalpy diagram in Figure 33. Key state points are indicated on the figure. The cycle for the full load ARI design point is represented in the plot. R134a 600 500 2 137 F (58 C) P (psia) 3 3b 200 2b 126 F (52 C) 106 F(41 C) 100 50 30 0 20 1 4 4b 39 F (4 C) 40 60 1b 80 100 120 140 h (btu/lb) Figure 33 Pressure Enthalpy (P-h) diagram of RTAC chiller The RTAC chiller uses a shell and tube evaporator design with refrigerant evaporating on the shell side and water flowing inside tubes having enhanced surfaces (states 4 to 1). The suction lines and bolt pads are designed to minimize pressure drop.(states 1 to 1b). The compressor is a twin-rotor helical rotary compressor designed similarly to the compressors offered in other Trane Screw Compressor Based Chillers (states 1b to 2). The discharge lines include a highly efficient oil separation system that virtually removes all oil from the refrigerant stream going to the heat exchangers (states 2 to 2b). De-superheating, condensing and sub-cooling is accomplished in a fin and tube air cooled heat exchanger where refrigerant is condensed in the tube (states 2b to 3b). Refrigerant flow through the system is balanced by an electronic expansion valve (states 3b to 4). 86 RTAC-SVX01F-EN Operating Principles Figure 34 System Schematic RTAC-SVX01F-EN 87 Operating Principles Refrigerant R134a The RTAC chiller uses environmentally friendly R134a. Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them. R134a is a medium pressure refrigerant. It may not be used in any condition that would cause the chiller to operate in a vacuum without a purge system. RTAC is not equipped with a purge system. Therefore, the RTAC chiller may not be operated in a condition that would result in a saturated condition in the chiller of –15°F (-26°C) or lower. R134a requires the use of specific POE oils as designated on the unit nameplate. Important! The RTAC units must only operate with R-134a and Trane Oil 00048. Compressor The compressor is a semi-hermetic, direct-drive rotary type compressor. Each compressor has only four moving parts: two rotors that provide compression and male and female load-control valves. The male rotor is attached to the motor and the female rotor is driven by the male rotor. The rotors and motor are supported by bearings. The helical rotary compressor is a positive displacement device. Refrigerant vapor from the evaporator is drawn into the suction opening of the compressor (state 1b), through a suction strainer screen across the motor (which provides motor cooling) and into the intake of the compressor rotors. The gas is then compressed and discharged through a check valve and into the discharge line (state 2). There is no physical contact between the rotors and the compressor housing. The rotors contact each other at the point where the driving action between the male and female rotors occurs. Oil is injected into the rotors of the compressor, coating the rotors and the compressor housing interior. Although this oil does provide rotor lubrication, its primary purpose is to seal the clearance spaces between the rotors and compressor housing. A positive seal between these internal parts enhances compressor efficiency by limiting leakage between the high pressure and low pressure cavities. Capacity control is accomplished by means of a female step load-control valve and a male control valve. The female step valve is the first stage of loading after the compressor starts and the last stage of unloading before the compressor shuts down. The male control valve is positioned by a piston cylinder along the length of the male rotor. Compressor capacity is dictated by the position of the loading valve relative to the rotors. When the valve slides toward the discharge end of the rotors compressor capacity is reduced. Condenser and Subcooler The condenser and subcooler are similar to the condenser used in RTAA chillers. The heat exchanger consists of 3/8” tubes that contain the refrigerant, large fins that are in the air flow and fans that draw air through the fins. Heat is transferred from the refrigerant through the tubes and fins to the air. High pressure gas from the compressor enters the tubes of the condenser through a distribution header (state 2b). As refrigerant flows through the tubes, the heat of compression and cooling load are rejected to the air. In this process the refrigerant is de-superheated, condensed (states 2b to 3) and finally subcooled (states 3 to 3b) to a temperature slightly above the ambient air temperature. The subcooled liquid refrigerant is collected in the leaving header where it is transferred to the liquid line (state 3b). A controls algorithm always runs as many fans as possible without reducing the differential pressure (discharge minus suction) below the setpoint (60 psid or 4.2 bar). If a warm enough ambient is sensed, all the fans will run. If the ambient is cooler, 88 RTAC-SVX01F-EN Operating Principles some fans are shut off to maintain the pressure differential. Fan staging depends on the chiller load, evaporator pressure, condenser effectiveness, ambient temperature, and numbers and sizes of fans installed on the circuit. The algorithm pre-starts fans (based on ambient and water temperatures) when a circuit starts the compressor. (For rare conditions such as during some pull-downs, a steady fan state would either violate the 60 psid (4.2 bar) setpoint or cause a high pressure cut-out; in those conditions a fan will cycle on and off.) For up to two minutes after chiller start-up, the setpoint is 35 psi (2.45 bar) difference, and then before the controls adjust gradually over half a minute up to 60 psi (4.2 bar). Expansion Valve Pressure drop occurs in an electronic expansion valve. The unit controller (CH530) uses the valve to regulate the flow through the liquid line to match the flow produced by the compressor. The valve has a variable orifice that is modulated by a stepper motor. High pressure, subcooled liquid refrigerant enters the expansion valve from the liquid line. As refrigerant passes through the valve the pressure is dropped substantially, which results in vaporization of some of the refrigerant. The heat of vaporization is supplied by the two phase mixture resulting in low temperature low pressure refrigerant which is supplied to the evaporator (state 4) to provide cooling. Evaporator The evaporator is composed of a liquid-vapor distributor and falling film evaporator. A liquid-vapor refrigerant mixture enters the distributor (state 4). The mixture is distributed over the length of the evaporator tubes (state 4b). Liquid is evenly distributed over the length of the evaporator tubes by the two-phase distribution system. A portion of the liquid boils as it falls by gravity from tube to tube, wetting all the tubes of the evaporator. To ensure that the tubes at the bottom of the evaporator do not experience “dry out,” a liquid pool is maintained in the bottom few inches of the bundle. Tubes located in the bottom of the evaporator will evaporate the liquid refrigerant by boiling (pool boiling). Heat is transferred from the water or glycol inside the tubes to the liquid refrigerant as the film of refrigerant evaporates on the surface of the tube. Thin film heat transfer requires a smaller temperature difference for a given amount of heat transfer than nucleate boiling, which is the heat transfer process used in flooded evaporators. Hence, efficiency is enhanced by the use of falling film evaporation. Additionally, the evaporator requires less refrigerant than a comparable flooded evaporator and the evaporator boils the entire refrigerant supply at constant pressure. Refrigerant vapor exits the evaporator through the suction line (state 1). Oil System Screw compressors require large quantities of oil for lubricating and sealing the rotors and lubricating the bearings. This oil is mixed with refrigerant at the discharge of the compressor. To enhance the performance of the heat exchanger surfaces an oil separation system is placed into the discharge line. The oil separator is located between the compressor and the condenser. It separates oil using highly efficient centrifugal force. Approximately 99.5% of the oil is removed from the refrigerant in the separator. Oil that is removed from the refrigerant falls by gravity into the oil sump. This oil is directed back to the compressor through the oil lines. Internal to the compressor is a high efficiency filter to clean the oil before it is delivered to the rotors and bearings. Once oil is injected into the compressor rotors it mixes with the refrigerant again and is delivered back to the discharge line. RTAC-SVX01F-EN 89 Operating Principles Oil that gets past the oil separators flows through the condenser, subcooler and expansion valve into the evaporator. This oil is collected in the pool of refrigerant that is maintained in the bottom of the evaporator. A small amount of oil and refrigerant from this pool (state 4b) is returned through a line that is connected to the compressor down stream of the motor. This oil and refrigerant mixes with the refrigerant vapor that was drawn out of the evaporator, prior to injection into the compressor rotors. C o n d e n s e r E v a p o ra R e fr ig e r P re s s u T ra n s d u P E to r a n t re c e r E X V E v a p o ra to r C o n R e fr P re T ra n E v a p o ra to r O il R e t u r n L in e F ilte r C o m p re s s o r B e a r in g a n d R o to r R e s t r ic t o r s a n d O il in je c t io n K E Y R e f r ig e r a n t w it h s m a ll a m o u n t o f O il R e f r ig e r a n t & O il M ix t u r e ( r e fr ig e r a n t v a p o r a n d o il) In te r m e d ia t e O il P r e s s u r e T ra n s d u c e r P I d e ig e s s s d P C n s ra u r u c e r n t e e r O il S e p a ra to r C o m p re s s o r H e a te r In te rn a l C o m p re s s o r O il F ilte r M a n u a l S e r v ic e V a lv e C o m p r e s s o r O il T e m p e ra tu re S e n s o r O il S e p a r a to r S u m p H e a te r O p tio n a l O il C o o le r O il R e c o v e r y S y s te m ( liq u id r e f r ig e r a n t a n d o il) P r im a r y O il S y s te m Figure 35 90 RTAC Oil System RTAC-SVX01F-EN Controls Interface CH530 Communications Overview The Trane CH530 control system that runs the chiller consists of several elements: • The main processor collects data, status, and diagnostic information and communicates commands to the starter module and the LLID (for Low Level Intelligent Device) bus. The main processor has an integral display (DynaView). • Higher level modules (e.g. starter) exist only as necessary to support system level control and communications. The starter module provides control of the starter when starting, running, and stopping the chiller motor. It also processes its own diagnostics and provides motor and compressor protection. • Low level intelligent device (LLID) bus. The main processor communicates to each input and output device (e.g. temperature and pressure sensors, low voltage binary inputs, analog input/output) all connected to a four-wire bus, rather than the conventional control architecture of signal wires for each device. • The communication interface to a building automation system (BAS). • A service tool to provide all service/maintenance capabilities. Main processor and service tool (TechView) software is downloadable from www.Trane.com. The process is discussed later in this section under TechView Interface. DynaView provides bus management. It has the task of restarting the link, or filling in for what it sees as “missing” devices when normal communications has been degraded. Use of TechView may be required. The CH530 uses the IPC3 protocol based on RS485 signal technology and communicating at 19.2 Kbaud to allow 3 rounds of data per second on a 64-device network. A typical four-compressor RTAC will have around 50 devices. Most diagnostics are handled by the DynaView. If a temperature or pressure is reported out of range by a LLID, the DynaView processes this information and calls out the diagnostic. The individual LLIDs are not responsible for any diagnostic functions. The only exception to this is the Starter module. NOTE: It is imperative that the CH530 Service Tool (TechView) be used to facilitate the replacement of any LLID or reconfigure any chiller component. TechView is discussed later in this section. Controls Interface Each chiller is equipped with a DynaView interface. The DynaView has the capability to display information to the operator including the ability to adjust settings. Multiple screens are available and text is presented in multiple languages as factory-ordered or can be easily downloaded from www.trane.com. TechView can be connected to either the DynaView module and provides further data, adjustment capabilities, diagnostics information using downloadable software. DynaView Interface The DynaView share the same enclosure design: weatherproof and durable plastic for use as a stand-alone device on the outside of the unit or mounted nearby. The display on DynaView is a 1/4 VGA display with a resistive touch screen and an LED backlight. The display area is approximately 4 inches wide by 3 inches high (102mm x 60mm). RTAC-SVX01F-EN 91 Controls Interface Figure 36 DynaView Key Functions In this touch screen application, key functions are determined completely by software and change depending upon the subject matter currently being displayed. The basic touch screen functions are outlined below. Radio Buttons Radio buttons show one menu choice among two or more alternatives, all visible. (It is the AUTO button in Figure 36.) The radio button model mimics the buttons used on old-fashioned radios to select stations. When one is pressed, the one that was previously pressed “pops out” and the new station is selected. In the DynaView model the possible selections are each associated with a button. The selected button is darkened, presented in reverse video to indicate it is the selected choice. The full range of possible choices as well as the current choice is always in view. Spin Value Buttons Spin values are used to allow a variable setpoint to be changed, such as leaving water setpoint. The value increases or decreases by touching the increment (+) or decrement (-) arrows. Action Buttons Action buttons appear temporarily and provide the user with a choice such as Enter or Cancel. Hot Links Hot links are used to navigate from one view to another view. File Folder Tabs File folder tabs are used to select a screen of data. Just like tabs in a file folder, these serve to title the folder/screen selected, as well as provide navigation to other screens. In DynaView, the tabs are in one row across the top of the display. The folder tabs are separated from the rest of the display by a horizontal line. Vertical lines separate the tabs from each other. The folder that is selected has no horizontal line under 92 RTAC-SVX01F-EN Controls Interface its tab, thereby making it look like a part of the current folder (as would an open folder in a file cabinet). The user selects a screen of information by touching the appropriate tab. Display Screens Basic Screen Format The basic screen format appears as: File folder Tabs Tab navigator Page scroll (down) Line scroll (up/down) Page scroll (up) Radio buttons Auto Contrast control (lighter) Stop Alarms Contrast control (darker) The file folder tabs across the top of the screen are used to select the various display screens. Scroll arrows are added if more file tabs (choices) are available. When the tabs are at the left most position, the left navigator will not show and only navigation to the right will be possible. Likewise when the right most screen is selected, only left navigation will be possible. The main body of the screen is used for description text, data, setpoints, or keys (touch sensitive areas). The Chiller Mode is displayed here. The double up arrows cause a page-by-page scroll either up or down. The single arrow causes a line by line scroll to occur. At the end of the page, the appropriate scroll bar will disappear. A double arrow pointing to the right indicates more information is available about the specific item on that same line. Pressing it will bring you to a subscreen that will present the information or allow changes to settings. The bottom of the screen (Fixed Display) is present in all screens and contains the following functions. The left circular area is used to reduce the contrast/viewing angle of the display. The right circular area is used to increase the contrast/viewing angle of the display. The contrast may require re-adjustment at ambient temperatures significantly different from those present at last adjustment. The other functions are critical to machine operation. The AUTO and STOP keys are used to enable or disable the chiller. The key selected is in black (reverse video). The chiller will stop when the STOP key is touched and after completing the Run Unload mode. Touching the AUTO key will enable the chiller for active cooling if no diagnostic is present. (A separate action must be taken to clear active diagnostics.) The AUTO and STOP keys, take precedence over the Enter and Cancel keys. (While a setting is being changed, AUTO and STOP keys are recognized even if Enter or Cancel has not been pressed.) RTAC-SVX01F-EN 93 Controls Interface The ALARMS button appears only when an alarm is present, and blinks (by alternating between normal and reverse video) to draw attention to a diagnostic condition. Pressing the ALARMS button takes you to the corresponding tab for additional information. Front Panel Lockout Feature Display and Touch Screen are Locked Enter Password to Unlock 1 2 3 4 5 6 7 8 9 Enter 0 Cancel NOTE: The DynaView display and Touch Screen Lock screen is shown below. This screen is used if the Display and touch screen and lock feature is enabled. Thirty minutes after the last keystroke, this screen is displayed and the Display and Touch Screen is locked out until the sequence “159” is pressed. Until the proper password is entered, there will be no access to the DynaView screens including all reports, setpoints, and Auto/Stop/Alarms/Interlocks. The password “159” is not programmable from either DynaView or TechView. Front Panel Display During Cold Ambients Display and Touch Screen are Locked Enter 159 to Unlock 94 1 2 3 4 5 6 7 8 9 Enter 0 Cancel RTAC-SVX01F-EN Controls Interface If the Display and Touch Screen Lock feature is disabled, the following screen is automatically displayed if the DynaView Temperature is below freezing and has been 30 minutes after the last keystroke. Note: This feature is provided to avoid unintended actuations of the keypad, which can occur due to ice build-up on the DynaView’s exterior surfaces. Also be aware that at extremes of temperatures, the LCD display screen will change its contrast from the optimal adjustment made at more normal temperatures. It can appear washed out or blacked out. Simply pressing the lower right contrast control on the screen will return the display to readable condition. NOTE: All screens shown in this section are typical. Some screens show all display options available, only one of which may appear on a line. Modes Screen The Mode Screen is only found on software revisions 18 and later. This screen provides a display for the top level operating mode for each of the components and subcomponents of the chiller (i.e. Chiller, Circuits, and Compressors) that exist on the Chiller as it is configured. The modes are displayed as text only without the hex codes. In software revisions 17.0 and earlier, the top level mode and the sub mode for each component was displayed on the respective component tab on the first two lines. The mode display of the first three lines of the Compressor and Chiller Screen tabs is eliminated with the addition of the Mode Screen Modes Chiller Mode: Compressor Running Circuit 1 Mode: Running - Limit Cprsr 1A Mode: Running Cprsr 1B Mode: Running Circuit 2 Mode: Run Inhibit Cprsr 2A Mode: Stopped Cprsr 2B Mode: Stopped Auto RTAC-SVX01F-EN Chiller Stop 95 Controls Interface Table 25 Chiller Modes Chiller Modes Description Top Level Mode Sub-modes Stopped The chiller is not running and cannot run without intervention. Further information is provided by the submode: Local Stop Chiller is stopped by DynaView Stop button commandcannot be remotely overridden. Panic Stop Chiller is stopped by the DynaView Panic Stop (by pressing Stop button twice in succession) - previous shutdown was manually commanded to shutdown immediately without a run-unload or pumpdown cycle cannot be remotely overridden. Diagnostic Shutdown - Manual Reset The chiller is stopped by a diagnostic that requires manual intervention to reset. Other sub-modes are possible in conjunction with at least one of the above modes - See items below for their descriptions: Diagnostic Shutdown - Auto Reset Start Inhibited by Low Cond Temp Start Inhibited by Low Ambient Temp Start Inhibited by External Source Start Inhibited by BAS Waiting for BAS Communications Ice Building to Normal Transition Ice Building is Complete Design Note: Maximum Capacity was eliminated as a annunciated mode prior to any release Run Inhibit The chiller is currently being inhibited from starting (and running), but may be allowed to start if the inhibiting or diagnostic condition is cleared. Further information is provided by the sub-mode: Diagnostic Shutdown - Auto Reset The entire chiller is stopped by a diagnostic that may automatically clear. Start Inhibited by Low Cond Temp The chiller is inhibited from starting by Low Condenser Temperature- Inhibit is active below either 25°F (can be disabled with proper freeze protection) or 0°F (limit set by design, cannot be disabled). As an exception, this will not stop a chiller already running. Start Inhibited by Low Ambient Temp The chiller is inhibited from starting (and running) by an outdoor air ambient temperature lower than a specified temperature - per user adjustable settings and can be disabled. Start Inhibited by External Source The chiller is inhibited from starting (and running) by the "external stop" hardwired input. 96 RTAC-SVX01F-EN Controls Interface Table 25 Chiller Modes Chiller Modes Description Top Level Mode Sub-modes Start Inhibited by BAS The chiller is inhibited from starting (and running) by command from a Building Automation System via the digital communication link (com 3 or com 5). Waiting for BAS Communications This is a transient mode - 15-min. max, and is only possible if the chiller is in the Auto - Remote command mode. After a power up reset, it is necessary to wait for valid communication from a Building Automation System (Tracer) to know whether to run or stay inhibited. Either valid communication will be received from the Building Automation System (e.g. Tracer), or a communication diagnostic ultimately will result. In the latter case the chiller will revert to Local control. Ice Building to Normal Transition The chiller is inhibited from running for a brief period of time if it is commanded from active ice building mode into normal cooling mode via the ice building hardwired input or Tracer. This allows time for the external system load to "switchover" from an ice bank to the chilled water loop, and provides for a controlled pull down of the loop's warmer temperature. This mode is not seen if the ice making is automatically terminated on return brine temperature per the mode below. Ice Building is Complete The chiller is inhibited from running as the Ice Building process has been normally terminated on the return brine temperature. The chiller will not start unless the ice building command (hardwired input or Building Automation System command) is removed or cycled. Auto The chiller is not currently running but can be expected to start at any moment given that the proper conditions and interlocks are satisfied. Further information is provided by the sub-mode: Waiting For Evap Water Flow The chiller will wait up to 4 minutes in this mode for evaporator water flow to be established per the flow switch hardwired input. Waiting for Need to Cool The chiller will wait indefinitely in this mode, for an evaporator leaving water temperature higher than the Chilled Water Setpoint plus the Differential to Start. Starting The chiller is going through the necessary steps to allow the lead circuit and lead compressor to start. No Sub Modes Running RTAC-SVX01F-EN At least one circuit and one compressor on the chiller are currently running. Further information is provided by the sub-mode: 97 Controls Interface Table 25 Chiller Modes Chiller Modes Description Top Level Mode Sub-modes Unit is Building Ice The chiller is running in the Ice Building Mode, and either at or moving towards full capacity available. Ice mode is terminated either with the removal of the ice mode command or with the return brine temperature falling below the Ice Termination Setpoint. Running - Limited At least one circuit and one compressor on the chiller are currently running, but the operation of the chiller as a whole is being actively limited by the controls. Capacity Limited by High Evap Water Temp This mode will occur if both the OA temperature is above 40°F and the Evap Leaving Water Temperature is above 75°F as is often the case in a high temperature pull-down. While in this mode, no compressors will be allowed to load past their minimum load capacity step, but it will not inhibit compressor staging. This mode is necessary to prevent nuisance trips due to Compressor Overcurrent or High Pressure Cutout. Reasonable pull-down rates can still be expected despite this limit. Table 26 Circuit Modes Circuit Modes Description Top Level Mode Sub-modes Stopped The given circuit is not running and cannot run without intervention. Further information is provided by the sub-mode: Front Panel Lockout The circuit is manually locked out by the circuit lockout setting - the nonvolatile lockout setting is accessible through either the DynaView or TechView. Diagnostic Shutdown - Manual Reset The circuit has been shutdown on a latching diagnostic. Other sub-modes are possible in conjunction with at least one of the above modes - See items below for their descriptions: Diagnostic Shutdown - Auto Reset Start Inhibited by External Source Start Inhibited by BAS Run Inhibit The given circuit is currently being inhibited from starting (and running), but may be allowed to start if the inhibiting or diagnostic condition is cleared. Further information is provided by the sub-mode: Diagnostic Shutdown - Auto Reset The circuit has been shutdown on a diagnostic that may clear automatically. Start Inhibited by External Source The circuit is inhibited from starting (and running) by its "external circuit lockout" hardwired input. Start Inhibited by BAS The circuit is inhibited from starting (and running) by command from a Building Automation System via the digital communication link (com 3 or com 5). 98 RTAC-SVX01F-EN Controls Interface Table 26 Circuit Modes Circuit Modes Description Top Level Mode Sub-modes Auto The given circuit is not currently running but can be expected to start at any moment given that the proper conditions and interlocks are satisfied. No Sub Modes Starting The given circuit is going through the necessary steps to allow the lead compressor on that circuit to start. No Sub Modes Running At least one compressor on the given circuit is currently running. Further information is provided by the sub-mode: Establishing Min. Cap - Low Diff pressure The circuit is experiencing low system differential pressure and is being force loaded, irregardless Chilled Water Temperature Control, to develop pressure sooner. Running - Limited At least one compressor on the given circuit is currently running, but the capacity of the circuit is being actively limited by the controls. Further information is provided by the sub-mode: Capacity Limited by High Cond Press The circuit is experiencing condenser pressures at or near the condenser limit setting. Compressors on the circuit will be unloaded to prevent exceeding the limits. Capacity Limited by Low Evap Rfgt Temp The circuit is experiencing saturated evaporator temperatures at or near the Low Refrigerant Temperature Cutout setting. Compressors on the circuit will be unloaded to prevent tripping. Capacity Limited by Low Liquid Level The circuit is experiencing low refrigerant liquid levels and the EXV is at or near full open. The compressors on the circuit will be unloaded to prevent tripping. Shutting Down The given circuit is still running but shutdown is imminent. The circuit is going through either a compressor run-unload mode or a circuit operational pumpdown to dry out the evaporator (cold OA ambient only). Shutdown is necessary due to one (or more) of the following sub-modes: Operational Pumpdown The circuit is in the process shutting down by performing an operational pumpdown just prior to stopping the last running compressor. The EXV is commanded closed. Pumpdown will terminate when both the liquid level and the evap pressure Front Panel Lockout The circuit has been manually locked out by the circuit lockout setting and is in the process of shutting down - the nonvolatile lockout setting is accessible through either the DynaView or TechView. Diagnostic Shutdown - Manual Reset The circuit is in the process of shutdown due to a latching diagnostic. Diagnostic Shutdown - Auto Reset The circuit is in the process of shutdown due to a diagnostic that may automatically clear. Start Inhibited by External Source The circuit is in the process of shutdown due to a command from the external circuit lockout hardwired input. Start Inhibited by BAS The circuit is in the process of shutdown due to a command from the Building Automation System (e.g. Tracer) Service Override The given circuit is in a Service Override mode Service Pumpdown The circuit is running with fan control, via a manual command to perform a Service Pumpdown. Its respective EXV is being held wide open, but the manual liquid line service valve should be closed. RTAC-SVX01F-EN 99 Controls Interface Table 27 Compressor Modes Compressor Modes Description Top Level Mode Sub-modes Stopped The given compressor is not running and cannot run without intervention. Further information is provided by the sub-mode: Diagnostic Shutdown - Manual Reset The compressor has been shutdown on a latching diagnostic. Service Tool Lockout The compressor has been shutdown due to a command from the TechView Service Tool to be "locked out" and inoperative. This setting is nonvolatile and operation can only be restored by using TechView to "unlock" it. Other sub-modes are possible in conjunction with at least one of the above modes - See items below for their descriptions: Diagnostic Shutdown - Auto Reset Restart Inhibit Run Inhibit The given compressor is currently being inhibited from starting (and running*), but may be allowed to start if the inhibiting or diagnostic condition is cleared. Further information is provided by the submode: Diagnostic Shutdown - Auto Reset The compressor has been shutdown on a diagnostic that may clear automatically. Restart Inhibit The compressor is currently unable to start due to its restart inhibit timer. A given compressor is not allowed to start until 5 minutes has expired since its last start. Auto The given compressor is not currently running but can be expected to start at any moment given that the proper conditions occur. No Sub Modes Starting The given compressor is going through the necessary steps to allow it to start. (This mode is short and transitory) No Sub Modes Running The given compressor is currently running. Further information is provided by the sub-mode: Establishing Min. Capacity - High Oil Temp The compressor is running and is being forced loaded to its step load point, without regard to the leaving water temperature control, to prevent tripping on high oil temperature. Running - Limited The given compressor is currently running, but its capacity is being actively limited by the controls. Further information is provided by the sub-mode: Capacity Limited by High Current The compressor is running and its capacity is being limited by high currents. The current limit setting is 120% RLA (to avoid overcurrent trips) or lower as set by the compressor's "share" of the active current limit (demand limit) setting for the entire chiller. Capacity Limited by Phase Unbalance The compressor is running and its capacity is being limited by excessive phase current unbalance. Shutting Down The given compressor is still running but shutdown is imminent. The compressor is going through either a run-unload mode or is the active compressor in the operational pumpdown cycle for its circuit. Shutdown is either normal (no sub-mode displayed) or due the following sub-modes: Diagnostic Shutdown - Manual Reset The compressor is in the process of shutdown due to a latching diagnostic. 100 RTAC-SVX01F-EN Controls Interface Table 27 Compressor Modes Compressor Modes Description Top Level Mode Sub-modes Diagnostic Shutdown - Auto Reset The compressor is in the process of shutdown due to a diagnostic that may clear automatically. Service Tool Lockout The compressor is in the process of shutdown due to a command from the TechView Service Tool to be "locked out" and inoperative. This setting is nonvolatile and operation can only be restored by using TechView to "unlock" it. Chiller Screen The chiller screen is a summary of the chiller activity. Modes Chiller Compressor Evap Leaving Water Temperature: 44.0 F Evap Entering Water Temperature: 54.0 F Active Chilled Water Setpoint: 44.0 F Active Current Limit Setpoint: 100 % Outdoor Air Temperature: 72.0 F Software Version: Auto Table 28 18.0 Stop Chiller Screen Description Resolution Units Evap Leaving Water Temperature Evap Entering Water Temperature Active Chilled Water Setpoint Active Current Limit Setpoint Out Door Temperature Software Type Software Version X.X X.X X.X X X.X RTA X.XX F/C F/C F/C % RLA F/C Text Text Compressor Screen The compressor screen displays information for the one, two, three, or four compressors in the format shown. The top line of radio buttons allows you to select the compressor of interest. The next three lines show the compressor operating mode. The compressor radio buttons and the compressor operating mode lines don’t change as you scroll down in the menu. The top screen has no upward scroll keys. The single arrow down scrolls the screen one line at a time. As soon as the display is one line away from the top, the upward pointing arrow appears. The last screen has a single arrow to scroll upward one line at a time. When in the last position, the single down arrow disappears. RTAC-SVX01F-EN 101 Controls Interface Each compressor has its own screen depending on which radio key is pressed. When toggling between compressor screens, say to compare starts and run time, the same lines can be seen without additional key strokes. For example, toggling from the bottom of the compressor 1A menu accesses the top of the compressor 2A menu. Modes Chiller 1A 1B Compressor 2A Amps L1 L2 L3: 2B 55.0 56.2 54.3 % RLA: 86.0 88.4 84.3 Unit Volts: 460 Oil Temperature: 95.0 102.9 psig Intermediate Oil Pressure: Suction Pressure: Auto Table 29 F 32.6 psig Stop Compressor Screen Description Resolution Units Amps L1 L2 L3 % RLA L1 L2 L3 Unit Volts Oil Temperature Intermediate Oil Pressure Suction Pressure Starts/ Run Hours XXX X.X XXX X.X X.X X.X X, XX:XX Amps % RLA Volts F/C Pressure Pressure hr:min Refrigerant Screen The refrigerant screen displays those aspects of the chiller related to the refrigerant circuits. Chiller Compressor Rfgt. Ckt 1 Cond Rfgt Pressure: 185.0 185.0 psig Sat Cond Rfgt Temp: 125.0 125.0 F Evap Rfgt Pressure: 30.0 30.0 psig Sat Evap Rfgt Temp: 34.0 34.0 F Evap Approach Temp: 4.0 4.0 F Rfgt Liquid Level: 0.1 -0.1 in Auto 102 Ckt 2 Stop RTAC-SVX01F-EN Controls Interface Table 30 Refrigerant Screen Description Resolution Units Cond Rfgt Pressure Ckt1/Ckt2 Sat Cond Rfgt Temp Ckt1/Ckt2 Evap Rfgt Pressure Ckt1/Ckt2 Sat Evap Rfgt Temp Ckt1/Ckt2 Evap Approach Temp Ckt1/Ckt2 Rfgt Liquid Level Ckt1/Ckt2 X.X X.X X.X X.X X.X X.X Pressure F/C Pressure F/C F/C Height Setpoint Screen The setpoint screen is a two-part screen. Screen 1 lists all setpoints available to change along with their current value. The operator selects a setpoint to change by touching either the verbal description or setpoint value. Doing this causes the screen to switch to Screen 2. In Screen 1 the language setpoint will always be the last setpoint in the list. This will facilitate language changes by placing that control in a standard position across all CH.530 product lines. Screen 2 displays the current value of the chosen setpoint in the upper ½ of the display. It is displayed in a changeable format consistent with its type. Binary setpoints are considered to be simple two state enumeration and will use radio buttons. Analog setpoints are displayed as spin buttons. The lower half of the screen is reserved for help screens. Rfgt Setpoint Diagnostic Auto Local or Remote: Local Front Panel Chilled Water Setpoint: 44.0 F Front Panel Current Limit Setpoint: 100 % Condenser Limit Setpt: Low Ambient Lockout Setpt: 35.0 F Low Ambient Lockout: Enable Auto Table 31 RTAC-SVX01F-EN XXX % HPC Stop Setpoint Screen Description Resolution or Text Units Auto Local or Remote Front Panel Chilled Water Setpoint Front Panel Current Limit Setpoint Differential to Start Differential to Stop Condenser Limit Setpoint Low Ambient Lockout Setpoint Low Ambient Lockout Ice Build Front Panel Ice Termination Setpoint Remote/Local X.X XXX X.X X.X Enable/Disable X.X Enable/Disable Enable/Disable X.X Text F/C % RLA Temperature Temperature Text Temperature Text Text Temperature 103 Controls Interface Table 31 Table 32 Setpoint Screen Description Resolution or Text Units Comp 1A Pumpdown Comp 1B Pumpdown Comp 2A Pumpdown Comp 2B Pumpdown EXV Ckt 1 Open EXV Ckt 2 Open Front Panel Ckt 1 Lockout Front Panel Ckt 2 Lockout Ext Chilled Water Setpoint Ext Current Limit Setpoint Date Format Date Time Format Time of Day Keypad/Display Lockout Display Units Pressure Units Language Selection Pumpdown/Abort Pumpdown/Abort Pumpdown/Abort Pumpdown/Abort Auto/Open Auto/Open Locked Out/Not Locked Out Locked Out/Not Locked Out X.X XXX mmm dd yyyy, dd mm yyyy Text Text Text Text Text Text Text Text F/C % RLA Text Text Text Text Text Text Text Text 12 hr, 24 hr Enable/Disable SI, English Absolute, Gauge Downloaded from TechView Setpoint Options/Conditions Displayed Option Condition(s) Explanation Ice Building Cprsr Pumpdown1 Enable/Disable Avail Not Avail If feature is installed, operation can be initiated or stopped Pumpdown is allowed: only with unit in Stop or when circuit is locked out Pumpdown is not allowed because unit is operating or pumpdown has been completed State is displayed while pumpdown is in progress Indicates EXV is closed but can be opened manually since unit is in Stop or circuit is locked out EXV Ckt Open (For Authorized Service Use Only2) Pumpdown Avail Not Avail Open Ckt Lockout Ext. Chilled Water Setpt Locked Out Not Locked Out Enable/Disable Ext. Current Limit Setpt Enable/Disable EXV is closed but cannot be opened manually since unit is operating State is displayed when EXV is open. Unit will not start with EXV manually set open, but will initiate valve closure first. Circuit is locked out at Front Panel; other circuit may be available to run Circuit is not locked out and is available to run Allows unit to control setpoint; otherwise another loop controller in line will control, as optionally wired. Allows unit to control setpoint; otherwise another loop controller in line will control, as optionally wired. Notes: 1 Pumpdown procedure are discussed in Maintenance section 2 Used for liquid level control or to recover from pumpdown 10. Diagnostic Screen The diagnostic screen (shown following) is accessible by either pressing the blinking ALARMS key or by pressing the Diagnostic tab on the screen tab selection. A hex code and a verbal description appears on the display as shown typically above. This is the last active diagnostic. Pressing the “Reset All Active Diagnostics” will reset all active diagnostics regardless of type, machine or refrigerant circuit. Compressor diagnostics, which hold off only one compressor, are treated as circuit diagnos- 104 RTAC-SVX01F-EN Controls Interface tics, consistent with the circuit to which they belong. One circuit not operating will not shut the chiller down. Viewing the “Compressor” screen will indicate whether a circuit is not operating and for what reason. Rfgt Setpoint Diagnostic Reset Diags [01] 10:59 AM Nov 26, 2001 Evaporator Water Flow Overdue [02] 10:56 AM Nov 26, 2001 Low Chilled Water Temp: Unit Off [03] 10:55 AM Nov 26, 2001 Low Evaorator Temp: Unit Off Auto Stop Alarms A complete listing of diagnostics and codes is included in the Diagnostic Section. Power-Up On Power-Up, DynaView will progress through three screens: First Screen, Version # of the Boot, full version # displayed. This screen will display for 5 seconds and move on to the second screen. The contrast will also be adjustable from this screen. Second Screen, Application or No Application. This screen will display for 5 seconds “A Valid Application Is Present” or “A Valid Application Is Not Present” and move on to the third screen. Third Screen, First screen of the Application, the Chiller Tab. Display Formats Units Temperature settings are in °F or °C, depending on Display Units settings. Settings can be entered in tenths or whole degrees depending on a menu setting at the TechView. Dashes (“-----”) appearing in a temperature or pressure report, indicates that the value is invalid or not applicable. Languages English plus two alternate languages may be installed with DynaView and will reside in the main processor. English will always be available. Alternate languages must be installed using TechView, Software Download View. RTAC-SVX01F-EN 105 TechView Figure 37 TechView TechView is the PC (laptop) based tool used for servicing Tracer CH530. Technicians that make any chiller control modification or service any diagnostic with Tracer CH530 must use a laptop running the software application “TechView.” TechView is a Trane application developed to minimize chiller downtime and aid the technicians understanding of chiller operation and service requirements. NOTE: Important: Performing any Tracer CH530 service functions should be done only by a properly trained service technician. Please contact your local Trane service agency for assistance with any service requirements. TechView software is available via Trane.com. (http://www.trane.com/commercial/software/tracerch530/) This download site provides a user the TechView installation software and CH530 main processor software that must be loaded onto your PC in order to service a CH530 main processor. The TechView service tool is used to load software into the Tracer CH530 main processor. RTAC-SVX01F-EN 106 TechView Minimum PC requirements to install and operate TechView • Pentium II or higher processor • 128Mb RAM • 1024 x 768 resolution of display • 56K modem • 9-pin RS-232 serial connection • Operating system - Windows 2000 • Microsoft Office (MS Word, MS Access, MS Excel) • Parallel Port (25-pin) or USB Port NOTE: TechView was designed for the preceding listed laptop configuration. Any variation will have unknown results. Therefore, support for TechView is limited to only those operating systems that meet the specific configuration listed here. Only computers with a Pentium II class processor or better are supported; Intel Celeron, AMD, or Cyrix processors have not been tested. TechView is also used to perform any CH530 service or maintenance function. Servicing a CH530 main processor includes: • Updating main processor software • Monitoring chiller operation • Viewing and resetting chiller diagnostics • Low Level Intelligent Device (LLID) replacement and binding • Main processor replacement and configuration modifications • Setpoint modifications • Service overrides Unit View Unit view is a summary for the system organized by chiller subsystem. This provides an overall view of chiller operating parameters and gives you an "at-aglance" assessment of chiller operation. The Control Panel tab displays important operating information for the unit and allows you to change several key operating parameters. The panel is divided into four or more sub-panels (depending on the number of circuits in the unit). The Operating Mode tab displays the unit, circuit and compressor top level operating modes. The Hours and Starts tab displays the number a hours (total) a compressor has run and the number of times the compressor has started. This window plays a key role in evaluating maintenance requirements. RTAC-SVX01F-EN 107 TechView Upon successful Local Connect Tech View will display UNIT VIEW. RTAC Unit View is shown below Figure 38 108 Unit View RTAC-SVX01F-EN TechView Compressor Service View The Compressor View provides convenient access to service functions for pumping down circuits and test starting compressors. Various operational lockouts allow operation of the rest of the chiller while some parts are awaiting repair. Figure 39 Compressor Service View Table 33 RTAC-SVX01F-EN Compressor Service View Items Description Settings Front Panel Circuit Lock Out Locked/Unlocked Electronic Expansion Valve Open/Auto Compressor Lockout Locked/Unlocked Compressor test Start Pumpdown (suction pressure is displayed) Start/Abort 109 TechView Status View Status View displays, in real time, all non-setpoint data organized by subsystem tabs. As data changes on the chiller it is automatically updated in Status View. Figure 40 110 Status View RTAC-SVX01F-EN TechView Table 34 Status View Items Tab Text Units Chiller Chiller Top Level Operating Mode Text Chiller Sub Operating Mode Text Operating Mode Text Chiller Sub Operating Mode Text Front Panel Auto/Stop Text Outdoor Air Temperature Temperature External Auto/Stop Auto/Stop External Emergency Stop Auto/Stop Active Chilled Water Setpoint Temperature Compressor RTAC-SVX01F-EN Active Current Limit Setpoint Temperature Active Ice Termination Setpoint Temperature External Current Limit Setpoint % RLA External Chilled Water Setpoint Temperature Evaporator Entering Water Temperature Temperature Evaporator Leaving Water Temperature Temperature Chilled Water Flow Switch Flow/NoFlow Ice Building Status Relay Ice Build/Normal Comm3 Chilled Water Setpoint Temperature BAS Chilled Water Setpoint Temperature BAS Current Limit Setpoint % RLA Comm3 Current Limit Setpoint % RLA Comm3 Ice Termination Setpoint Temperature BAS Communication Text Chilled Water Pump Relay on/off Compressor 1 Operating Mode Text Compressor 1 Sub Mode Text Compressor 1 Top Level Operating Mode Text Run Hours Integer Starts Integer Phase A-B Voltage Volts Average Line Current Amps Line 1 Current Amps Line 2 Current Amps Line 3 Current Amps Line 1 Current % RLA Line 2 Current % RLA 111 TechView Table 34 Tab Text Units Compressor Line 3 Current % RLA Maximum Line Current Amps Supply Oil Temperature Temperature Intermediate Oil Pressure Pressure Female Step Loader Loaded/Unloaded High Pressure Cutout Switch Tripped/Not Tripped Circuit 112 Status View Items Circuit Sub Mode Text Circuit Top Level Operating Mode Text External Hardwired Lockout Locked/Not locked Front Panel Lockout Locked/Not locked Air Flow % Inverter Speed % Full Speed Condenser Refrigerant Pressure Pressure Saturated Condenser Refrigerant Temperature Temperature Differential Refrigerant Pressure Pressure Evaporator Refrigerant Pressure Pressure Saturated Evaporator Refrigerant Temperature Temperature EXV Position % Open Evaporator Refrigerant Liquid Level in RTAC-SVX01F-EN TechView Setpoint View Setpoint view displays the active setpoints and allows you to make changes. Figure 41 Setpoint View Setpoint List The center of the window displays the scrollable list of setpoint panels. Setpoint Enumeration Panel A setpoint numeric panel contains a label with the setpoint description and a pull-down list showing the active value and the other selections. The Default button returns the setpoint to the product's factory setting. The text field is updated when the change is complete. RTAC-SVX01F-EN 113 TechView Setpoint Numeric Panel A setpoint numeric panel contains a label with the setpoint description, a Default button, a text field with a unit label, and a slider. The Default button changes the setpoint to the product's factory setting. The text field and slider are updated when the change is complete. You can change a setpoint with the text field or with the slider. When you click on the entry field, the change setpoint dialog displays to coordinate the setpoint change. You can change the display units for a setpoint by clicking on the unit label next to the entry field. Change Setpoint The change setpoint window allows you to enter a new value for the setpoint into a text field. If the entered value is outside the given range, the background turns red. 114 RTAC-SVX01F-EN TechView Table 35 Setpoints View Items Tab Text Min Value Max Value Default Value Unit Type Chiller Front Panel Display Units English, SI Chiller Front Panel Chilled Water Setpoint 10 (-12.22) 65 (18.33) English Display Units 44 (6.67) Temp Deg F(C) Chiller Front Panel Current Limit Setpoint 60 120 120 Percent Chiller Differential to Stop 0.5 (0.2777) 2.5 (1.388) 2.0 (1.111) Differential Temp Deg F(C) Chiller Differential to Start 1.0 (0.555) 30 (16.666) 2 (1.111) Differential Temp Deg F(C) Chiller Leaving Water Temp Cutout 0.0 (-17.78) 36.0 (2.22) 36.0 (2.22) Temp Deg F(C) Chiller Low Refrigerant Temp Cutout -5.0 (-20.56) 36.0 (2.22) 28.0 (-2.22) Temp Deg F(C) Chiller Front Panel Condenser Limit Setpoint 80 120 90 Percent Chiller Low Ambient Lockout Setpoint -10 (-23.333) 70 (21.111) 25 (-3.89) Temp Deg F(C) Chiller Low Ambient Lockout Enable, Disable Enable Enabled / Disabled Chiller Front Panel Ice Termination Setpoint 20 (-6.67) 31 (-0.56) Temp Deg F(C) Chiller External Ice Building Input Enable, Disable Disable Enabled / Disabled Chiller Under/Over Voltage Protection Enable, Disable Disable Enabled / Disabled Chiller Local Atmospheric Pressure 9.93 (68.5) 16.0 (110.3) 14.7 (101.3) Absolute Pressure psia(Kpa) Chiller Design Delta Temperature 4 (2.22) 30 (16.666) 10 (5.6) Differential Temp Deg F(C) Chiller Reset Type None, Return, Outdoor, Constant Return None RstTyp 31 (-0.56) Chiller Return Reset Ratio 10 120 50 Percent Chiller Return Start Reset 4.0 (2.22) 30.0 (16.666) 10.0 (5.56) Differential Temp Deg F(C) Chiller Return Maximum Reset 0 20 (11.11) 5.0 (2.78) Differential Temp Deg F(C) Chiller Outdoor Reset Ratio -80 80 10 Percent Chiller Outdoor Start Reset 50 (10) 130 (54.44) 90 (32.22) Temp Deg F(C) RTAC-SVX01F-EN 115 TechView Table 35 Setpoints View Items Tab Text Min Value Max Value Default Value Unit Type Chiller Outdoor Maximum Reset 0 20 (11.11) 5 (2.78) Differential Temp Deg F(C) Chiller External Chilled Water Setpoint Enable, Disable Disable Enabled / Disabled Chiller External Current Limit Setpoint Enable, Disable Disable Enabled / Disabled Chiller Evaporator Water Pump Off Delay 0 30 1 Minutes Chiller Chilled Water Setpoint Filter Settling Time 30 1800 200 Seconds Chiller Compressor Staging Deadband 0.4 (0.222) 4.0 (2.222) 0.05 (0.2778) Differential Temp Deg F(C) 116 RTAC-SVX01F-EN TechView Diagnostics View This window lists the active and inactive (history) diagnostics. There can be up to 60 diagnostics, both active and historic. For example, if there were 5 active diagnostics, the possible number of historic diagnostics would be 55. You can also reset active diagnostics here, (i.e., transfer active diagnostics to history and allow the chiller to regenerate any active diagnostics). Resetting the active diagnostics may cause the chiller to resume operation. The Active and History diagnostics have separate tabs. A button to reset the active diagnostics displays when either tab is selected . Figure 42 Diagnostic View RTAC-SVX01F-EN 117 TechView Configuration View This view displays the active configuration and allows you to make changes. Figure 43 Configuration View Configuration View allows you to define the chiller's components, ratings, and configuration settings. These are all values that determine the required installed devices, and how the chiller application is run in the main processor. For example, a user may set an option to be installed with Configuration View, which will require devices to be bound using Binding View. And when the main processor runs the chiller application, the appropriate steps are taken to monitor required inputs and control necessary outputs. Any changes made in the Configuration View, on any of the tabs, will modify the chiller configuration when you click on the Load Configuration button (located at the base of the window). The Load Configuration button uploads the new configuration settings into the main processor. Any changes made to the configuration will change the unit model number number and the confirmation code (CRC). If changes are made to the unit configuration the new model number and CRC should be recorded. 118 RTAC-SVX01F-EN TechView Selecting the Undo All button will undo any configuration setting changes made during the present TechView connection and since the last time the Load Configuration button was selected. . Table 36 Tab Feature Configuration View Items Item Basic Product Line Unit Nominal Capacity Default Unit Voltage Manufacturing Location Design Sequence Unit Type Agency Listing Pressure Vessel Code Evaporator Temperature Range & Application Type Evaporator Configuration Condenser Temperature Range Condenser Fin Material RTAC-SVX01F-EN Description RTAC - Air Cooled Series R Chiller 140 Nominal Tons 155 Nominal Tons 170 Nominal Tons 185 Nominal Tons 200 Nominal Tons 225 Nominal Tons 250 Nominal Tons 275 Nominal Tons 300 Nominal Tons 350 Nominal Tons 375 Nominal Tons 400 Nominal Tons 450 Nominal Tons 500 Nominal Tons A - 200V/60Hz/3Ph power K - 220V/50Hz/3 Ph power C - 230V/60Hz/3Ph power J - 380V/60Hz/3Ph power D - 400V/50Hz/3Ph power 4 - 460V/60Hz/3Ph power 5 - 575V/60Hz/3Ph power U - Water Chiller Business Unit - Pueblo E - Epinal Business Unit -Charmes XX - Factory/ABU Assigned N - Standard Efficiency/Performance H - High Efficiency/Performance N - No agency listing U - C/UL listing A - ASME pressure vessel code C - Canadian code D - Australian code L - Chinese code R - Vietanamese code S - Special F - Standard Temp. with Frz Prot R - Rem Evap, Std Temp, No Frz Prot G - Low Temp, with Frz Prot N - Standard pass arrangement, insulated N - Standard ambient range 25-115 deg F H - High ambient capability 25-125 deg F L - Low ambient capability 0-115 deg F W - Wide ambient capability 0-125 deg F 1 - Standard aluminum slit fins 2 - Copper fins, non-slit fins 4 - Complete Coat aluminum fins 119 TechView Table 36 Tab Feature Configuration View Items Item Default Condenser Fan/Motor Configuration Compressor Motor Starter Type Incoming Power Line Connection Power Line Connection Type Unit Operator Interface Remote Interface Control Input Accessories/Options Control Output Accessories/Options Short Circuit Rating Electrical Accessories and Export Packing Control Panel Accessories Refrigerant Service Valves Compressor Sound Attenuator Option Appearance Options 120 Description N - Condenser fans with ODP motors W - Low Noise fans T - Condenser fans with TEAO motors X - Across-the-line starters Y - Wye-delta closed transition starters 1 - Single point power connection 2 - Dual point power connection (1/ckt) T - Terminals only D - Non-fused disconnect switch(es) C - Circuit Breaker(s), HACR-rated E - Easy-View operator interface D -Dyna-View operator interface N - No remote interface C - Tracer Comm 3 interface L -Lon Talk Communication interface (LCI) N -No remote input R -Remote leaving water temp stpt C -Remote current limit setpoint B -Remote lvg. temp.setpoint and remote current limit setpoint N -No output options A -Alarm relay C -Icemaking D -Icemaking and alarm relay 0 - No short circuit withstand rating 5 -10000A SCR 4 -35000A SCR 6 -65000A SCR N - No flow switches F - NEMA-1 flow switch - 150 psi E - Vapor Proof FS - 150 psi N - No convenience outlet A - 15A 115V convenience outlet (60HZ) 0 - No suction services valves 1 - Suction service valves 0 - No sound attenuator 1 - Factory installed sound attenuator N - No appearance options A - Architectural louvered panels C - Half Louvers G - Access guards B - Access guards and half louvers P - Painted unit L - Painted unit with full louvered panels H - Painted unit with half louvered panels K - Painted unit with access guards W - Painted w/access guards and half louvers RTAC-SVX01F-EN TechView Table 36 Tab Features Configuration View Items Item Installation Accessories Factory Test Control, Label, and Literature Language Special Order Custom Comm 3 ICD address Status Relay #1 J2-10,11,12 Status Relay #2 J2-7,8,9 Status Relay #3 J2-4,5,6 Status Relay #4 J2-1,2,3 Phase Unbalance Trip Phase Unbalance Grace Period Maximum Acceleration Time Starter Feature Default Description N - No installation accessories R - Neoprene Isolators F - Flanged water connection kit G - Neoprene isolators and flange wtr conn kit 0 - No factory run test E - English G - Chinese X - Standard catalog configuration S - Unit has special order feature 55 1-64 REM = C Alarm - Latching None, Alarm - Latching (Active diagnostic persistence latching), Alarm - Auto reset (Active Chiller Running Maximum Capacity diagnostic persistence non-latching), Alarm Chiller Limit Mode (Active diagnostic persistence latching or nonlatching), Alarm Ckt1 (Active diagnostic persistence latching or non-latching), Alarm Ckt2 (Active diagnostic persistence latching or nonlatching), Chiller Limit Mode (With 20 minute filter), Circuit 1 Running, Circuit 2 Running, Maximum Capacity COOP = A, D or X 30 10-50% 90 30-255 Sec 3 1-255 Sec All Enabled Contactor Integrity Test, Phase Reversal Detect, Phase Unbalance Detect External Chilled Water 2-10 VDC 2-10 VDC, 4-20 mA Setpoint Detection CIOP = C or B External Current Limit Water 2-10 VDC 2-10 VDC, 4-20 mA Setpoint Detection CIOP = C or B Custom Unit Voltage 400 380,400,415 VOLT = D Nameplate The Model Number field contains the model number stored in the EasyView or DynaView. The Confirm Code field contains the confirm code stored in the EasyView or DynaView. The confirm code is a four-digit hex value that is a mathematical calculation of the model number. This number has one to one correlation to a specific model number and is used to verify that the model number was entered properly. The Serial Number field contains the serial number stored in the EasyView or DynaView. This model number and confirmation code must be know when the main processor requires replacement. RTAC-SVX01F-EN 121 TechView Software View Software view allows you to verify the version of chiller software currently running on the EasyView or DynaView and download a new version of chiller software to the EasyView or DynaView. You can also add up to two available languages to load into the DynaView. Loading an alternate language file allows the DynaView to display its text in the selected alternate language, English will always be available. Figure 44 122 Software View RTAC-SVX01F-EN TechView Binding View Binding View allows you to assess the status of the network and all the devices connected as a whole, or the status of individual devices by using status icons and function buttons. Binding View is essentially a table depicting what devices and options are actually discovered on the network bus (and their communication status) versus what is required to support the configuration defined by the feature codes and categories. Binding View allows you to add, remove, modify, verify, and reassign devices and options in order to match the configuration requirements. Whenever a device is installed, it must be correctly configured to communicate and to function as intended. This process is called binding. Some features of Binding View are intended to serve a second purpose; that is diagnosing problems with communication among the devices. Figure 45 Binding View RTAC-SVX01F-EN 123 TechView Replacing or Adding Devices If a device is communicating but incorrectly configured, it might not be necessary to replace it. If the problem with the device is related to communication, attempt to rebind it, and if the device becomes correctly configured, it will then communicate properly. If a device that needs to be replaced is still communicating, it should be unbound. Otherwise, it will be necessary to rebuild the CH530 network image for Binding View to discover that it has been removed. An unbound device stops communicating and allows a new device to be bound in its place. It is good practice to turn the power off while detaching and attaching devices to the CH530 network. Be sure to keep power on the service tool computer. After power is restored to the CH530 network, the reconnect function in Binding View restores communication with the network. If the service tool computer is turned off, you must restart TechView and Binding View. If a device is not communicating, the binding function displays a window to request manual selection of the device to be bound. Previously-selected devices are deselected when the function starts. When manual selection is confirmed, exactly one device must be selected; if it is the correct type, it is bound. If the desired device cannot be selected or if multiple devices are accidentally selected, you can close the manual selection window by clicking on No and repeat the bind function. Software Download Instructions for First Time TechView Users This information can also be found at http://www.trane.com/commercial/ software/tracerch530/. 1. Create a folder called “CH530” on your C:\ drive. You will select and use this folder in subsequent steps so that downloaded files are easy to locate. 2. Download the Java Runtime installation utility file onto your PC in the CH530 folder (please note that this does not install Java Runtime, it only downloads the installation utility). – Click on the latest version of Java Runtime shown in the TechView Download table. – Select “Save this program to disk” while downloading the files (do not select “Run this program from its current location”). 3. Download the TechView installation utility file onto your PC in the CH530 folder (please note that this does not install TechView, it only downloads the installation utility). – Click on the latest version of TechView shown in the TechView Download table. – Select “Save this program to disk” while downloading the files (do not select “Run this program from its current location”). 4. Remember where you downloaded the files (the “CH530” folder). You will need to locate them to finish the installation process. 124 RTAC-SVX01F-EN TechView 5. Proceed to “Main Processor Software Download” page and read the instructions to download the latest version of main processor installation files. Note: you will first select the chiller type to obtain the available file versions. 6. Select the product family. A table with the download link will appear for that product family. 7. Download the main processor software onto your PC in the CH530 folder (please note that this does not install the main processor, it only downloads the installation utility). – To do this, click on the latest version of the main processor. – Select “Save this program to disk” while downloading the files (do not select “Run this program from its current location”). 8. Remember where you downloaded the files (the “CH530” folder). You will need to locate them to finish the installation process. 9. To complete the installation process, locate the installation utilities you downloaded into the CH530 folder. If necessary, use your PC’s file manager to locate the downloaded files. 10. Install the applications in the following order by double-clicking on the install program and following the installation prompts: – Java Runtime Environment (JRE_VXXX.exe) Note: During the Java Runtime Environment installation, you may be prompted to “select the default Java Runtime for the system browsers...”. Do not select any system browsers at this step. There should be no default browsers selected for proper operation. – TechView (6200-0347-VXXX.exe) – The main processor (6200-XXXX-XX-XX.exe). – The main processor program will self extract to the proper folder within the TechView program directory, provided the TechView program is properly installed on the C:\ drive. 11. Connect your PC to the CH530 main processor using a standard 9-pin male/9-pin female RS-232 cable. 12. Run the TechView software by selecting the TechView icon placed on your desktop during the installation process. The “Help...About” menu can be viewed to confirm proper installation of latest versions. RTAC-SVX01F-EN 125 Diagnostics The following Diagnostic Table contains all diagnostics possible arranged alphabetically by the name assigned to each diagnostic. Not all diagnostics are available unless TechView is installed. Legend to Diagnostics Table Hex Code: 3-digit code used to uniquely identify diagnostics. Diagnostic Name: Name of the diagnostic as it appears at DynaView and/or TechView displays. Severity: Defines the action of the above effect. Immediate means an instantaneous shutdown of the affected portion. Normal means routine or friendly shutdown of the affected portion. Special Mode means a particular mode of operation is invoked, but without shutdown, and Info means an Informational Note or Warning is generated. Persistence: Defines whether or not the diagnostic and its effects are to be manually reset (Latched), or can be either manually or automatically reset (Nonlatched). Criteria: Quantitatively defines the criteria used in generating the diagnostic and, if nonlatching, the criteria for auto reset. Reset Level: Defines the lowest level of manual diagnostic reset command which can clear the diagnostic. The manual diagnostic reset levels in decreasing order of priority are: Local, Remote and Info. For example, a diagnostic that has a reset level of Remote, can be reset by either a remote diagnostic reset command or by a local diagnostic reset command, but not by the lower priority Info Reset command. Hex Diagnostic Name Code and Source Severity Persistence Criteria Reset Level 398 BAS Communication Lost Special NonLatch Remote 390 BAS Failed to Establish Communication Special NonLatch 2E6 Check Clock Info Latch 8A Chilled Water Flow (Entering Water Temperature) Info NonLatch 5EF Comm Loss: Chilled Water Flow Switch Comm Loss: Cond Rfgt Pressure, Circuit #1 Comm Loss: Cond Rfgt Pressure, Circuit #2 Comm Loss: Electronic Expansion Valve, Circuit #1 Comm Loss: Electronic Expansion Valve, Circuit #2 Comm Loss: Emergency Stop Comm Loss: Evap Oil Return Valve, Cprsr 1A Comm Loss: Evap Oil Return Valve, Cprsr 1B Comm Loss: Evap Oil Return Valve, Cprsr 2A Immediate Latch Immediate Latch The BAS was setup as "installed" at the MP and the Comm 3 LLID lost communications with the BAS for 15 contiguous minutes after it had been established. Refer to Section on Setpoint Arbitration to determine how setpoints and operating modes may be effected by the comm loss. The chiller follows the value of the Tracer Default Run Command which can be previously written by Tracer and stored nonvolatilely by the MP (either use local or shutdown). The BAS was setup as "installed" and the BAS did not communicate with the MP within 15 minutes after power-up. Refer to Section on Setpoint Arbitration to determine how setpoints and operating modes may be effected. Note: The original requirement for this was 2 minutes, but was implemented at 15 minutes for RTAC. The real time clock had detected loss of its oscillator at some time in the past. This diagnostic can be effectively cleared only by writing a new value to the chiller's time clock using the TechView or DynaView's "set chiller time" functions. The entering evaporator water temp fell below the leaving evaporator water temp. by more than 2°F for 100 °F-sec. For RTAC this diagnostic cannot reliably indicate loss of flow, but can warn of improper flow direction through the evaporator, misbound temperature sensors, or other system problems Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period. Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote 5F2 5F3 694 695 5DE 68E 69E 68F 126 Remote Remote Remote Remote RTAC-SVX01F-EN Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria Reset Level 69F Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Special Mode Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Remote 5F1 Comm Loss: Evaporator Rfgt Immediate Pressure, Circuit #2 Latch 5F8 Comm Loss: Evaporator Water Pump Control Comm Loss: External Auto/ Stop Comm Loss: External Chilled Water Setpoint Normal Latch Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period. Note: This diagnostic is replaced by diagnostic 5FB below with Rev 15.0 Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period. Note: This diagnostic is replaced by diagnostic 5FD below with Rev 15.0 Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Special Mode NonLatch 5DF Comm Loss: External Circuit Lockout, Circuit #1 Special Mode Latch 5E0 Comm Loss: External Circuit Lockout, Circuit #2 Comm Loss: External Current Limit Setpoint Special Mode Special Mode Latch Continual loss of communication between the MP and the Functional Remote ID has occurred for a 30 second period. Chiller shall discontinue use of the External Chilled Water Setpoint source and revert to the next higher priority for setpoint arbitration Continual loss of communication between the MP and the Functional Remote ID has occurred for a 30 second period. MP will nonvolatily hold the lockout state (enabled or disabled) that was in effect at the time of comm loss. Same as Comm Loss: External Circuit Lockout, Circuit #1 Remote Comm Loss: Fan Control Circuit #1, Stage #1 Comm Loss: Fan Control Circuit #1, Stage #2 Comm Loss: Fan Control Circuit #1, Stage #3 Comm Loss: Fan Control Circuit #1, Stage #4 Comm Loss: Fan Control Circuit #2, Stage #1 Comm Loss: Fan Control Circuit #2, Stage #2 Comm Loss: Fan Control Circuit #2, Stage #3 Comm Loss: Fan Control Circuit #2, Stage #4 Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, Drive 1 Comm Loss: Fan Inverter Fault, Circuit #1, Drive 2 Comm Loss: Fan Inverter Fault, Circuit #2 or Circuit #2, Drive 1 Comm Loss: Fan Inverter Fault, Circuit #2, Drive 2 Comm Loss: Fan Inverter Power, Circuit #1 or Circuit #1 Drive 1 and 2 Normal Latch Continual loss of communication between the MP and the Functional Remote ID has occurred for a 30 second period. Chiller shall discontinue use of the External Current limit setpoint and revert to the next higher priority for Current Limit setpoint arbitration Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Special Mode Latch Special Mode Special Mode Latch Continual loss of communication between the MP and the Functional Remote ID has occurred for a 30 second period. Operate the remaining fans as fixed speed fan deck. Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, Remote Drive 1 Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, Remote Drive 1 5E4 5E3 6BB 6BC 688 689 5F0 5DD 5E9 5EA 680 681 682 683 684 685 686 687 68C 68D 69A 69B 68A Comm Loss: Evap Oil Return Valve, Cprsr 2B Comm Loss: Evaporator Entering Water Temperature Comm Loss: Evaporator Leaving Water Temperature Comm Loss: Evaporator Rfgt Drain Valve - Ckt 1 Comm Loss: Evaporator Rfgt Drain Valve - Ckt 2 Comm Loss: Evaporator Rfgt Liquid Level, Circuit #1 Comm Loss: Evaporator Rfgt Liquid Level, Circuit #2 Comm Loss: Evaporator Rfgt Pressure, Circuit #1 RTAC-SVX01F-EN Special Mode Normal NonLatch Latch Latch Latch Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, Drive 1 Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, Drive 1 Remote Remote Remote 127 Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria Reset Level 698 Normal Latch Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, Drive 1 Remote Special Mode Latch Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, Drive 1 Remote Special Mode Latch Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, Drive 1 Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Special Mode Latch Remote Special Mode Immediate Latch Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period. Chiller shall revert to normal (non-ice building) mode regardless of last state. Same as Comm Loss: Ice-Machine Control Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch Same as Comm Loss: Chilled Water Flow Switch Remote Special Mode Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote Normal Latch Same as Comm Loss: Chilled Water Flow Switch Remote 68B 699 5D9 5DA 5DB 5DC 5EB 5EC 5ED 5EE 5E1 5FA 5F4 5F5 5F6 5F7 69D 5D2 5D4 5D6 5D8 5D1 5D3 5D5 5D7 5E5 5E6 696 697 128 Comm Loss: Fan Inverter Power, Circuit #2 or Circuit #2 Drive 1 and 2 Comm Loss: Fan Inverter Speed Command, Circuit #1 or Circuit #1 Drive 1 and 2 Comm Loss: Fan Inverter Speed Command, Circuit #2 or Circuit #2 Drive 1 and 2 Comm Loss: Female Step Load Compressor 1A Comm Loss: Female Step Load Compressor 1B Comm Loss: Female Step Load Compressor 2A Comm Loss: Female Step Load Compressor 2B Comm Loss: High Pressure Cutout Switch, Cprsr 1A Comm Loss: High Pressure Cutout Switch, Cprsr 1B Comm Loss: High Pressure Cutout Switch, Cprsr 2A Comm Loss: High Pressure Cutout Switch, Cprsr 2B Comm Loss: Ice-Machine Control Comm Loss: Ice-Making Status Comm Loss: Intermediate Oil Pressure, Cprsr 1A Comm Loss: Intermediate Oil Pressure, Cprsr 1B Comm Loss: Intermediate Oil Pressure, Cprsr 2A Comm Loss: Intermediate Oil Pressure, Cprsr 2B Comm Loss: Local BAS Interface Comm Loss: Male Port Load Compressor 1A Comm Loss: Male Port Load Compressor 1B Comm Loss: Male Port Load Compressor 2A Comm Loss: Male Port Load Compressor 2B Comm Loss: Male Port Unload Compressor 1A Comm Loss: Male Port Unload Compressor 1B Comm Loss: Male Port Unload Compressor 2A Comm Loss: Male Port Unload Compressor 2B Comm Loss: Oil Temperature, Circuit #1 or Cprsr 1A Comm Loss: Oil Temperature, Circuit #2 or Cprsr 2A Comm Loss: Oil Temperature, Cprsr 1B Comm Loss: Oil Temperature, Cprsr 2B Remote RTAC-SVX01F-EN Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria Reset Level 5E2 Comm Loss: Outdoor Air Temperature Normal Latch Remote 690 691 692 693 6AC Comm Loss: Starter 1A Comm Loss: Starter 1B Comm Loss: Starter 2A Comm Loss: Starter 2B Comm Loss: Starter Panel High Temperature Limit Panel 1, Cprsr 1B Comm Loss: Starter Panel High Temperature Limit Panel 1, Cprsr 2A Comm Loss: Starter Panel High Temperature Limit Panel 2, Cprsr 2B Comm Loss: Status/ Annunciation Relays Comm Loss: Suction Pressure Cprsr 1A Immediate Immediate Immediate Immediate Info Latch Latch Latch Latch Latch Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period. Note that if this diagnostic occurs, operational pumpdown will be performed regardless of the last valid temperature Same as Comm Loss: Chilled Water Flow Switch Same as Comm Loss: Chilled Water Flow Switch Same as Comm Loss: Chilled Water Flow Switch Same as Comm Loss: Chilled Water Flow Switch Same as Comm Loss: Chilled Water Flow Switch Info Latch Same as Comm Loss: Chilled Water Flow Switch Local Info Latch Same as Comm Loss: Chilled Water Flow Switch Local Info Latch Same as Comm Loss: Chilled Water Flow Switch Remote Immediate Latch 6AB 6AD 6A0 5FB Local Local Local Local Local 5FC Comm Loss: Suction Pressure Cprsr 1B Immediate Latch 5FD Comm Loss: Suction Pressure Cprsr 2A Comm Loss: Suction Pressure Cprsr 2B Condenser Fan Variable Speed Drive Fault - Circuit 1 (Drive 1) Immediate Latch Continual loss of communication between the MP and the Functional Remote ID has occurred for a 30 second period. Circuit target if no isolation valves, Compressor target if isolation valves or simplex. Design Note: In the case of manifolded compressors w/o isolation valves, the occurrence of this diagnostic will also generate a comm loss with the nonexistent Suction Press Cprsr 2B in order to accomplish circuit shutdown. Continual loss of communication between the MP and the Functional Remote ID has occurred for a 30 second period. Design Note: For circuits with manifolded compressors w/o isolation valve option, this diagnostic will occur with the preceding diagnostic, even though this transducer is not required or installed. Same as Comm Loss: Suction Pressure Cprsr 1A Remote Immediate Latch Same as Comm Loss: Suction Pressure Cprsr 1B Remote Special Mode Latch Remote Special Mode Latch The MP has received a fault signal from the respective condenser fan Variable Speed Inverter Drive, and unsuccessfully attempted (5 times within 1 minute of each other) to clear the fault. The 4th attempt removes power from the inverter to create a power up reset. If the fault does not clear, the MP will revert to constant speed operation without the use of the inverter's fan. The inverter must be manually bypassed, and fan outputs rebound, for full fixed speed fan operation. Same as Condenser Fan Variable Speed Drive Fault Circuit 1 (Drive 1) Special Mode Latch Same as Condenser Fan Variable Speed Drive Fault Circuit 1 (Drive 1) Remote Special Mode Latch Same as Condenser Fan Variable Speed Drive Fault Circuit 1 (Drive 1) Remote Immediate Latch Bad Sensor or LLID Remote Immediate Latch Bad Sensor or LLID Remote Immediate Latch 5FE 2A1 5B4 2A2 5B5 5B8 5B9 FD Condenser Fan Variable Speed Drive Fault - Circuit 1 Drive 2 Condenser Fan Variable Speed Drive Fault - Circuit 2 (Drive 1) Condenser Fan Variable Speed Drive Fault - Circuit 2 (Drive 2) Condenser Refrigerant Pressure Transducer Circuit 1 Condenser Refrigerant Pressure Transducer Circuit 2 Emergency Stop Remote 8E Evaporator Entering Water Temperature Sensor Info Latch AB Evaporator Leaving Water Temperature Sensor Evaporator Liquid Level Sensor - Circuit 1 Evaporator Liquid Level Sensor - Circuit 2 Normal Latch EMERGENCY STOP input is open. An external interlock has tripped. Local Time to trip from input opening to unit stop shall be 0.1 to 1.0 seconds. Bad Sensor or LLID a. Normal operation, no effects on control. Remote b. Chiller shall remove any Return or Constant Return Chilled Water Reset, if it was in effect. Apply slew rates per Chilled Water Reset spec. Bad Sensor or LLID Remote Immediate Latch Bad Sensor or LLID Remote Immediate Latch Bad Sensor or LLID Remote 27D 3F9 RTAC-SVX01F-EN 129 Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria 6B9 Evaporator Rfgt Drain Circuit 1 NA Latch 6BA Evaporator Rfgt Drain Circuit 2 Evaporator Water Flow Lost NA Latch This diagnostic is effective only with Remote Evap units. The liquid Remote level of the respective evaporator was not seen to be below the level of -21.2 mm (0.83 in) within 5 minutes of the commanded opening of its Drain Valve Solenoid. The diagnostic will not be active if the drain valve is commanded closed. Same as Evaporator Rfgt Drain - Circuit 1 Remote Immediate NonLatch ED 384 Evaporator Water Flow Overdue Normal NonLatch 5C4 Excessive Loss of Comm Immediate Latch 87 External Chilled Water Setpoint Info NonLatch 89 External Current Limit Setpoint High Differential Refrigerant Pressure - Circuit 1 High Differential Refrigerant Pressure - Circuit 2 High Evaporator Liquid Level Circuit 1 Info NonLatch Normal Latch Normal Latch Normal Latch 1C6 1C7 584 Reset Level a. The chilled water flow switch input was open for more than 6-10 contiguous seconds. b. This diagnostic does not de-energize the evap pump output c. 6-10 seconds of contiguous flow shall clear this diagnostic. d. Even though the pump times out in the STOP modes, this diagnostic shall not be called out in the STOP modes. Note that this diagnostic will not light the red diagnostic light on the Easy View display. Evaporator water flow was not proven within 4.25 minutes (RTAC Rev 20 and earlier) or 20 minutes (RTAC Rev 21) of the Chilled water pump relay being energized. With SW Rev 17.0 and earlier, the diagnostic will de-energize the Chilled Water Pump output. It will be re-energized if the diagnostic clears with the return of flow and the chiller will be allowed to restart normally (to accommodate external control of pump) With SW Rev 18.0 and later, the pump command status will not be effected. Note that this diagnostic will not light the red diagnostic light on the EasyView display. Loss of comm with 75% or more of the LLIDs configured for the system has been detected. This diagnostic will suppress the callout of all subsequent comm loss diagnostics. Check power supply(s) and power disconnects - troubleshoot LLIDS buss using TechView a. Function Not "Enabled": no diagnostics. b. "Enabled ": Out-Of-Range Low or Hi or bad LLID, set diagnostic, default CWS to next level of priority (e.g. Front Panel SetPoint). This Info diagnostic will automatically reset if the input returns to the normal range. Same as External Chilled Water Setpoint Remote The system differential pressure for the respective circuit was above 275 Psid for 2 consecutive samples or more than 10 seconds. Same as High Differential Refrigerant Pressure - Circuit 1 Remote Remote Remote Remote Remote Remote High Evaporator Liquid Level - Normal Circuit 2 High Evaporator Refrigerant Immediate Pressure Latch 1DE High Oil Temperature Compressor 1A Immediate Latch 1E0 High Oil Temperature Compressor 1B High Oil Temperature Compressor 2A High Oil Temperature Compressor 2B High Pressure Cutout Compressor 1A Immediate Latch The liquid level sensor is seen to be at or near its high end of range for Remote 80 contiguous minutes while the compressor is running. (The diagnostic timer will hold, but not clear when the circuit is off). Design: 80% or more of bit count corresponding to +21.2 mm or more liquid level for 80 minutes) Same as High Evaporator Liquid Level - Circuit 1 . Remote The evaporator refrigerant pressure of either circuit has risen above 190 Remote psig. The evaporator water pump relay will be de-energized to stop the pump regardless of why the pump is running. The diagnostic will auto reset and the pump will return to normal control when all of the evaporator pressures fall below 185 psig. This diagnostic has severity of Immediate because if an evaporator pressure reads high without being invalid, the pump would be shut off but the chiller could keep running. Evap water flow diagnostics are not active if the pump is commanded off, only if the pump is commanded on but flow does not occur as expected. The respective oil temperature as supplied to the compressor, Remote exceeded 200°F for 2 consecutive samples or for over 10 seconds. Note: As part of the Compressor High Temperature Limit Mode (aka Minimum Limit), the running compressor's female load step will be forced loaded when its oil temperature exceeds 190F and returned to normal control when the oil temperature falls below 170°F. Same as High Oil Temperature - Compressor 1A Remote Immediate Latch Same as High Oil Temperature - Compressor 1A Remote Immediate Latch Same as High Oil Temperature - Compressor 1A Remote Immediate Latch Immediate Latch A high pressure cutout was detected on Compressor 1A; trip at 315 ± 5 Local PSIG. Note: Other diagnostics that may occur as an expected consequence of the HPC trip will be suppressed from annunciation. These include Phase Loss, Power Loss, and Transition Complete Input Open. Same as High Pressure Cutout - Compressor 1A Local 5B7 6B8 1DD 1DF F5 F6 130 High Pressure Cutout Compressor 1B NonLatch RTAC-SVX01F-EN Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria Reset Level BE Immediate Latch Same as High Pressure Cutout - Compressor 1A Local Immediate Latch Same as High Pressure Cutout - Compressor 1A Local Immediate Latch Bad Sensor or LLID Remote Immediate Latch Bad Sensor or LLID Remote Immediate Latch Bad Sensor or LLID Remote Immediate Latch Bad Sensor or LLID Remote Special Mode NonLatch The leaving chilled water temp. fell below the leaving water temp cutout setting for 30 degree F seconds while the Chiller is in the Stop mode, or in Auto mode with no compressors running. Energize Evap Water pump Relay until diagnostic auto resets, then return to normal evap pump control. Automatic reset occurs when the temp rises 2°F (1.1°C) above the cutout setting for 30 minutes. The chilled water temp. fell below the cutout setpoint for 30 degree F Seconds while the compressor was running. Automatic reset occurs when the temperature rises 2 °F (1.1°C) above the cutout setting for 2 minutes. This diagnostic shall not de-energize the Evaporator Water Pump Output. The system differential pressure for the respective circuit was below 35 Psid for more than 2000 Psid-sec with either a 1 minute (single cprsr circuit) or 2.5 minute (manifolded cprsr circuit) ignore time from the start of the circuit. Same as Low Differential Refrigerant Pressure - Circuit 1 Remote BF 5BE 5BF 5C0 5C1 C5 High Pressure Cutout Compressor 2A High Pressure Cutout Compressor 2B Intermediate Oil Pressure Transducer - Compressor 1A Intermediate Oil Pressure Transducer - Compressor 1B Intermediate Oil Pressure Transducer - Compressor 2A Intermediate Oil Pressure Transducer - Compressor 2B Low Chilled Water Temp: Unit Off C6 Low Chilled Water Temp: Unit Immediate On and Special Mode NonLatch 1AE Low Differential Refrigerant Pressure - Circuit 1 Immediate Latch 1AF Low Differential Refrigerant Immediate Pressure - Circuit 2 Low Evaporator Liquid Level - Info Circuit 1 Latch Low Evaporator Liquid Level - Info Circuit 2 Low Evaporator Refrigerant Immediate Temperature - Circuit 1 NonLatch 583 5B6 194 195 6B3 6B3 198 199 19A 19B NonLatch Latch Remote Remote Remote The liquid level sensor is seen to be at or near its low end of range for Remote 80 contiguous minutes while the compressor is running. Design: 20% or less of bit count corresponding to -21.2 mm or less liquid level for 80 minutes) Same as Low Evaporator Liquid Level - Circuit 1 Remote a. The inferred Saturated Evap Refrigerant Temperature (calculated from Remote suction pressure transducer(s)) dropped below the Low Refrigerant Temperature Cutout Setpoint for 120°F-sec (8°F-sec max rate) while the circuit was running after the ignore period had expired. The integral is held at zero for the ignore time (which is a function of outdoor air temp) following the circuit startup and the integral will be limited to never trip in less than 15 seconds, i.e. the error term shall be clamped to 8°F. The minimum LRTC setpoint is -5°F (18.7 Psia) the point at which oil separates from the refrigerant. b. During the timeout of the trip integral, the unload solenoid(s) of the running compressors on the circuit, shall be energized continuously. Normal load/unload operation will be resumed if the trip integral is reset by return to temps above the cutout setpoint. Same as Low Evaporator Refrigerant Temperature - Circuit 1 Remote Low Evaporator Refrigerant Temperature - Circuit 2 Low Evaporator Temp Ckt 1: Unit Off Immediate Latch Special Mode NonLatch Low Evaporator Temp Ckt 2: Unit Off Low Oil Flow Compressor 1A Special Mode Immediate NonLatch Latch Low Oil Flow Compressor 1B Low Oil Flow Compressor 2A Low Oil Flow Compressor 2B Immediate Latch The intermediate oil pressure transducer for this compressor was out Local of the acceptable pressure range for 15 seconds, while the Delta Pressure was greater than 35 Psid.: Acceptable range is 0.50 > (PC-PI) / (PC-PE) for the first 2.5 minutes of operation, and 0.25 > (PC-PI) / (PCPE) thereafter, Same as Low Oil Flow - Compressor 1A Local Immediate Latch Same as Low Oil Flow - Compressor 1A Local Immediate Latch Same as Low Oil Flow - Compressor 1A Local RTAC-SVX01F-EN Any of the evap sat temps fell below the water temp cutout setting while the respective evap liquid level was greater than -21.2mm for 30 degree F seconds while Chiller is in the Stop mode, or in Auto mode with no compressors running. Energize Evap Water pump Relay until diagnostic auto resets, then return to normal evap pump control. Automatic reset occurs when either the evap temp rises 2°F (1.1°C) above the cutout setting or the liquid level falls below -21.2mm for 30 minutes Same as Low Evaporator Temp - Ckt 1: Unit Off Remote Remote 131 Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria B5 Low Suction Refrigerant Pressure - Circuit 1 Immediate Latch B6 Low Suction Refrigerant Pressure - Circuit 2 Low Suction Refrigerant Pressure - Cprsr 1B Low Suction Refrigerant Pressure - Cprsr 2B Motor Current Overload Compressor 1A Immediate Latch a. The Suction Refrigerant Pressure (or either of the compressor Local suction pressures) dropped below 10 Psia just prior to compressor start (after EXV preposition). b. The pressure fell below 16 Psia while running after the ignore time had expired, or fell below 10 Psia (or 5 Psia in software prior to Oct'02) before the ignore time had expired. The ignore time is function of outdoor air temperature. Note: Part b. is identical to Low Evaporator Refrigerant Temperature diagnostic except for the trip integral and trip point settings. Same as Low Suction Refrigerant Pressure - Circuit 1 Local Immediate Latch Same as Low Suction Refrigerant Pressure - Circuit 1 Local Immediate Latch Same as Low Suction Refrigerant Pressure - Circuit 1 Local Immediate Latch Local Immediate Latch Compressor current exceeded overload time vs. trip characteristic. For A/C products Must trip = 140% RLA, Must hold=125%, nominal trip 132.5% in 30 seconds Same as Motor Current Overload - Compressor 1A Immediate Latch Same as Motor Current Overload - Compressor 1A Local Immediate Latch Same as Motor Current Overload - Compressor 1A Local Immediate Latch Memory error criteria TBD Remote Info Latch Remote Immediate Info Latch Latch Info Latch Info NonLatch B7 B8 BA BB BC BD 1AD 6A1 Motor Current Overload Compressor 1B Motor Current Overload Compressor 2A Motor Current Overload Compressor 2B MP Application Memory CRC Error MP: Could not Store Starts and Hours MP: Invalid Configuration MP: Non-Volatile Block Test Error MP: Non-Volatile Memory Reformat MP: Reset Has Occurred Reset Level Local 1E1 Oil Flow Fault Compressor 1A Immediate Latch 1E2 Immediate Latch Immediate Latch Same as Oil Flow Fault - Compressor 1A Local Immediate Latch Same as Oil Flow Fault - Compressor 1A Local Normal Latch Bad Sensor or LLID Remote Normal Latch Bad Sensor or LLID Remote Normal Latch Bad Sensor or LLID Remote Normal Latch Bad Sensor or LLID Remote Normal Latch D7 Oil Flow Fault Compressor 1B Oil Flow Fault Compressor 2A Oil Flow Fault Compressor 2B Oil Temperature Sensor - Cprsr 1B Oil Temperature Sensor - Cprsr 2B Oil Temperature Sensor -Cprsr 1A Oil Temperature Sensor -Cprsr 2A Outdoor Air Temperature Sensor Over Voltage MP has determined there was an error with the previous power down store. Starts and Hours may have been lost for the last 24 hours. MP has an invalid configuration based on the current software installed MP has determined there was an error with a block in the Non-Volatile memory. Check settings. MP has determined there was an error in a sector of the Non-Volatile memory and it was reformatted. Check settings. The main processor has successfully come out of a reset and built its application. A reset may have been due to a power up, installing new software or configuration. This diagnostic is immediately and automatically cleared and thus can only be seen in the Historic Diagnostic List in TechView The Intermediate Oil Pressure Transducer for this cprsr is reading a pressure either above its respective circuit's Condenser Pressure by 15 Psia or more, , or below its respective Suction Pressure 10 Psia or more for 30 seconds continuously. Same as Oil Flow Fault - Compressor 1A Normal NonLatch 19C Phase Loss - Compressor 1A Immediate Bad Sensor or LLID. Note that if this diagnostic occurs, operational Remote pumpdown will be performed regardless of the last valid temperature a. Line voltage above + 10% of nominal. [Must hold = + 10 % of Remote nominal. Must trip = + 15 % of nominal. Reset differential = min. of 2% and max. of 4%. Time to trip = minimum of 1 min. and maximum of 5 min.) Design: Nom. trip: 60 seconds at greater than 112.5%, + or - 2.5%, Auto Reset at 109% or less. a) No current was sensed on one or two of the current transformer Local inputs while running or starting (See Nonlatching Power Loss Diagnostic for all three phases lost while running). Must hold = 20% RLA. Must trip = 5% RLA. Time to trip shall be longer than guaranteed reset on Starter Module at a minimum, 3 seconds maximum. Actual design trippoint is 10%. The actual design trip time is 2.64 seconds. b) If Phase reversal protection is enabled and current is not sensed on one or more current xformer inputs. Logic will detect and trip in a maximum of 0.3 second from compressor start. 5FF 6A2 69C D9 5A0 5A1 1E6 1E8 1E5 1E7 A1 132 Latch Remote Remote Remote Remote Local Local RTAC-SVX01F-EN Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria Reset Level 19D 19E 19F 184 Phase Loss - Compressor 1B Phase Loss - Compressor 2A Phase Loss - Compressor 2B Phase Reversal Compressor 1A Immediate Immediate Immediate Immediate Latch Latch Latch Latch Local Local Local Local 185 Phase Reversal Compressor 1B Phase Reversal Compressor 2A Phase Reversal Compressor 2B Power Loss - Compressor 1A Immediate Latch Same as Phase Loss - Compressor 1A Same as Phase Loss - Compressor 1A Same as Phase Loss - Compressor 1A A phase reversal was detected on the incoming current. On a compressor startup the phase reversal logic must detect and trip in a maximum of .3 second from compressor start. Same as Phase Reversal - Compressor 1A Immediate Latch Same as Phase Reversal - Compressor 1A Local Immediate Latch Same as Phase Reversal - Compressor 1A Local Immediate NonLatch Remote 1A1 1A2 1A3 8C Power Loss - Compressor 1B Power Loss - Compressor 2A Power Loss - Compressor 2B Pumpdown Terminated Circuit 1 Immediate Immediate Immediate Info NonLatch NonLatch NonLatch NonLatch 8D Info NonLatch Immediate Latch Immediate 5CD Pumpdown Terminated Circuit 2 Severe Current Imbalance Compressor 1A Severe Current Imbalance Compressor 1B Severe Current Imbalance Compressor 2A Severe Current Imbalance Compressor 2B Starter 1A Comm Loss: MP The compressor had previously established currents while running and then all three phases of current were lost. Design: Less than 10% RLA, trip in 2.64 seconds. This diagnostic will preclude the Phase Loss Diagnostic and the Transition Complete Input Opened Diagnostic from being called out. To prevent this diagnostic from occurring with the intended disconnect of main power, the minimum time to trip must be greater than the guaranteed reset time of the Starter module. Note: This diagnostic prevents nuisance latching diagnostics due to a momentary power loss - It does not protect motor/compressor from uncontrolled power reapplication. See Momentary Power Loss Diagnostic for this protection. This diagnostic is not active during the start mode before the transition complete input is proven. Thus a random power loss during a start would result in either a "Starter Fault Type 3" or a "Starter Did Not Transition" latching diagnostic. Same as Power Loss - Compressor 1A Same as Power Loss - Compressor 1A Same as Power Loss - Compressor 1A The pumpdown cycle for this circuit was terminated abnormally due to excessive time or due to a specific set of diagnostic criteria - but w/o associated latching diagnostics Same as Pumpdown Terminated - Circuit 1 6A7 186 187 1A0 1B2 Local Remote Remote Remote Remote Remote Local Latch A 30% Current Imbalance has been detected on one phase relative to the average of all 3 phases for 90 continuous seconds. Same as Severe Current Imbalance - Compressor 1A Immediate Latch Same as Severe Current Imbalance - Compressor 1A Local Immediate Latch Same as Severe Current Imbalance - Compressor 1A Local Immediate Latch Local Starter 1A Dry Run Test Immediate Latch 5CE Starter 1B Comm Loss: MP Immediate Latch 6A8 Starter 1B Dry Run Test Immediate Latch 5CF Starter 2A Comm Loss: MP Immediate Latch 6A9 Starter 2A Dry Run Test Immediate Latch 5D0 Starter 2B Comm Loss: MP Immediate Latch 6AA Starter 2B Dry Run Test Immediate Latch Starter has had a loss of communication with the MP for a 15 second period. While in the Starter Dry Run Mode either 50 % Line Voltage was sensed at the Potential Transformers or 10 % RLA Current was sensed at the Current Transformers. Starter has had a loss of communication with the MP for a 15 second period. While in the Starter Dry Run Mode either 50 % Line Voltage was sensed at the Potential Transformers or 10 % RLA Current was sensed at the Current Transformers. Starter has had a loss of communication with the MP for a 15 second period. While in the Starter Dry Run Mode either 50 % Line Voltage was sensed at the Potential Transformers or 10 % RLA Current was sensed at the Current Transformers. Starter has had a loss of communication with the MP for a 15 second period. While in the Starter Dry Run Mode either 50 % Line Voltage was sensed at the Potential Transformers or 10 % RLA Current was sensed at the Current Transformers. 1B3 1B4 1B5 RTAC-SVX01F-EN Local Local Local Local Local Local Local Local 133 Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria CC Starter Contactor Interrupt Failure - Compressor 2A Special Mode Latch CA Starter Contactor Interrupt Failure - Compressor 1A Starter Contactor Interrupt Failure - Compressor 1B Starter Contactor Interrupt Failure - Compressor 2B Starter Did Not Transition Compressor 1A Special Mode Special Mode Special Mode Immediate Latch Detected compressor currents greater than 10% RLA on any or all Local phases when the compressor was commanded off. Detection time shall be 5 second minimum and 10 seconds maximum. On detection and until the controller is manually reset: generate diagnostic, energize the appropriate alarm relay, continue to energize the Evap Pump Output, continue to command the affected compressor off, fully unload the effected compressor and command a normal stop to all other compressors. For as long as current continues, perform liquid level and fan control on the circuit effected. Same as Starter Contactor Interrupt Failure - Compressor 2A Local Latch Same as Starter Contactor Interrupt Failure - Compressor 2A Local Latch Same as Starter Contactor Interrupt Failure - Compressor 2A Local Latch Starter Did Not Transition Compressor 1B Starter Did Not Transition Compressor 2A Starter Did Not Transition Compressor 2B Starter Failed to Arm/Start Cprsr 1A Starter Failed to Arm/Start Cprsr 1B Starter Failed to Arm/Start Cprsr 2A Starter Failed to Arm/Start Cprsr 2B Starter Fault Type I Compressor 1A Immediate Latch The Starter Module did not receive a transition complete signal in the Local designated time from its command to transition. The must hold time from the Starter Module transition command is 1 second. The Must trip time from the transition command is 6 seconds. Actual design is 2.5 seconds. This diagnostic is active only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line Starters. Same as Starter Did Not Transition - Compressor 1A Local Immediate Latch Same as Starter Did Not Transition - Compressor 1A Local Immediate Latch Same as Starter Did Not Transition - Compressor 1A Local Info Latch Starter failed to arm or start within the allotted time (15 seconds). Local Info Latch Same as Starter Failed to Arm/Start - Cprsr 1A Local Info Latch Same as Starter Failed to Arm/Start - Cprsr 1A Local Info Latch Same as Starter Failed to Arm/Start - Cprsr 1A Local Immediate Latch Immediate Latch This is a specific starter test where 1M(1K1) is closed first and a check Local is made to ensure that there are no currents detected by the CT's. If currents are detected when only 1M is closed first at start, then one of the other contactors is shorted. Same as Starter Fault Type I - Compressor 1A Local Immediate Latch Same as Starter Fault Type I - Compressor 1A Local Immediate Latch Same as Starter Fault Type I - Compressor 1A Local Immediate Latch Immediate Latch a. This is a specific starter test where the Shorting Contactor (1K3) is Local individually energized and a check is made to ensure that there are no currents detected by the CT's. If current is detected when only S is energized at Start, then 1M is shorted. b. This test in a. above applies to all forms of starters (Note: It is understood that many starters do not connect to the Shorting Contactor.). Same as Starter Fault Type II - Compressor 1A Local Immediate Latch Same as Starter Fault Type II - Compressor 1A Local Immediate Latch Same as Starter Fault Type II - Compressor 1A Local Immediate Latch Immediate Latch As part of the normal start sequence to apply power to the compressor, Local the Shorting Contactor (1K3) and then the Main Contactor (1K1) were energized. 1.6 seconds later there were no currents detected by the CT's for the last 1.2 Seconds on all three phases. The test above applies to all forms of starters except Adaptive Frequency Drives. Same as Starter Fault Type III - Compressor 1A Local Immediate Latch Same as Starter Fault Type III - Compressor 1A Local Immediate Latch Same as Starter Fault Type III - Compressor 1A Local Info Latch Checksum on RAM copy of the Starter LLID configuration failed. Configuration recalled from EEPROM. Local CB CD 180 181 182 183 6A3 6A4 6A5 6A6 1E9 1EA 1EB 1EC 1ED 1EE 1EF 1F0 1F1 1F2 1F3 1F4 5C7 134 Starter Fault Type I Compressor 1B Starter Fault Type I Compressor 2A Starter Fault Type I Compressor 2B Starter Fault Type II Compressor 1A Starter Fault Type II Compressor 1B Starter Fault Type II Compressor 2A Starter Fault Type II Compressor 2B Starter Fault Type III Compressor 1A Starter Fault Type III Compressor 1B Starter Fault Type III Compressor 2A Starter Fault Type III Compressor 2B Starter Module Memory Error Type 1 - Starter 2A Reset Level RTAC-SVX01F-EN Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria Reset Level 5C8 Info Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local Info Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local Info Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local Immediate Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local Immediate Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local Immediate Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local Immediate Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local Special Mode NonLatch Local Starter Panel High Temperature Limit - Panel 1, Cprsr 2A Starter Panel High Temperature Limit - Panel 2, Cprsr 2B Suction Refrigerant Pressure Transducer - Circuit 1, Compressor 1A Special Mode NonLatch Starter Panel High Limit Thermostat (170°F) trip was detected. Note: Other diagnostics that may occur as an expected consequence of the Panel High Temp Limit trip will be suppressed from annunciation. These include Phase Loss, Power Loss, and Transition Complete Input Open for Cprsr 1B Same as Starter Panel High Temperature Limit - Panel 1, Cprsr 1B Special Mode NonLatch Same as Starter Panel High Temperature Limit - Panel 1, Cprsr 1B Local Immediate Latch Suction Refrigerant Pressure Transducer - Circuit 1, Compressor 1B Suction Refrigerant Pressure Transducer - Circuit 2, Compressor 2A Suction Refrigerant Pressure Transducer - Circuit 2, Compressor 2B Transition Complete Input Opened - Compressor 1A Immediate Latch Bad Sensor or LLID Circuit target if no isolation valves, Compressor Remote target if isolation valves. Design Note: In the case of manifolded compressors w/o isolation valves, the occurrence of this diagnostic will also generate a comm loss with the nonexistent Suction Press Cprsr 1B in order to accomplish circuit shutdown. Same as Suction Refrigerant Pressure Transducer - Circuit 1, Remote Compressor 1A Immediate Latch Same as Suction Refrigerant Pressure Transducer - Circuit 1, Compressor 1A Remote Immediate Latch Same as Suction Refrigerant Pressure Transducer - Circuit 1, Compressor 1A Remote Immediate Latch Immediate Latch The Transition Complete input was found to be opened with the Local compressor motor running after a successful completion of transition. This is active only for Y-Delta, Auto-Transformer, Primary Reactor, and XLine Starters. To prevent this diagnostic from occurring as the result of a power loss to the contactors, the minimum time to trip must be greater than the trip time for the power loss diagnostic. Same as Transition Complete Input Opened - Compressor 1A Local Immediate Latch Same as Transition Complete Input Opened - Compressor 1A Local Immediate Latch Same as Transition Complete Input Opened - Compressor 1A Local Immediate Latch Local Immediate Latch The Transition Complete input was found to be shorted before the compressor was started. This is active for all electromechanical starters. Same as Transition Complete Input Opened - Compressor 2B Local Immediate Latch Same as Transition Complete Input Opened - Compressor 2B Local Immediate Latch Same as Transition Complete Input Opened - Compressor 2B Local 5C5 5C6 5C9 5CA 5CB 5CC 6B1 6B0 6B2 5BA 5BB 5BC 5BD 5B0 5B1 5B2 5B3 5AC 5AD 5AE 5AF Starter Module Memory Error Type 1 - Starter 2B Starter Module Memory Error Type 1Starter 1A Starter Module Memory Error Type 1-Starter 1B Starter Module Memory Error Type 2 - Starter 1A Starter Module Memory Error Type 2 - Starter 1B Starter Module Memory Error Type 2 - Starter 2A Starter Module Memory Error Type 2 - Starter 2B Starter Panel High Temperature Limit - Panel 1, Cprsr 1B Transition Complete Input Opened - Compressor 1B Transition Complete Input Opened - Compressor 2A Transition Complete Input Opened - Compressor 2B Transition Complete Input Shorted - Compressor 1A Transition Complete Input Shorted - Compressor 1B Transition Complete Input Shorted - Compressor 2A Transition Complete Input Shorted - Compressor 2B RTAC-SVX01F-EN Local 135 Diagnostics Hex Diagnostic Name Code and Source Severity Persistence Criteria D8 Under Voltage Normal NonLatch 771 Very Low Evaporator Refrigerant Pressure Circuit 1 Immediate Latch 772 Very Low Evaporator Refrigerant Pressure Circuit 2 Immediate Latch a. Line voltage below - 10% of nominal or the Under/Overvoltage Remote transformer is not connected. [Must hold = - 10 % of nominal. Must trip = - 15 % of nominal. Reset differential = min. of 2% and max. of 4%. Time to trip = min. of 1 min. and max. of 5 min.) Design: Nom. trip: 60 seconds at less than 87.5%, + or - 2.8% at 200V or + or - 1.8% at 575V, Auto Reset at 90% or greater. The evaporator pressure dropped below 10 psia (or 5 psia in software Local prior to Oct '02)regardless of whether or not compressors are running on that circuit. This diagnostic was created to prevent compressor failures due to crossbinding by forcing an entire chiller shutdown. If a given compressor or circuit is locked out, the suction pressure transducer(s)associated with it, will be excluded from causing this diagnostic. Same as Very Low Evaporator Refrigerant Pressure - Circuit 1 Local 136 Reset Level RTAC-SVX01F-EN Pre-Start Checkout Installation Checklist Complete this checklist as the unit is installed and verify that all recommended procedures are accomplished before the unit is started. This checklist does not replace the detailed instructions given in the “Installation -Mechanical” and “Installation -Electrical” sections of this manual. Read both sections completely, to become familiar with the installation procedures, prior to beginning the work. Receiving • Verify that the unit nameplate data corresponds to the ordering information. • Inspect the unit for shipping damage and any shortages of materials. Report any damage or shortage to the carrier. Unit Location and Mounting • Inspect the location desired for installation and verify adequate service access clearances. • Provide drainage for evaporator water. • Remove and discard all shipping materials (cartons, etc.) • Install optional rubber isolators, if required. • Level the unit and secure it to the mounting surface. Unit Piping • Flush all water piping before making final connections to the unit. CAUTION Proper Water Treatment! The use of untreated or improperly treated water in the Unit may result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water. If using an acidic commercial flushing solution, construct a temporary bypass around the unit to prevent damage to internal components of the evaporator. • • • • • • • RTAC-SVX01F-EN Connect the chilled water piping to the evaporator. Install pressure gauges and shutoff valves on the chilled water inlet and outlet to the evaporator. Install a water strainer in the entering chilled water line. Install a balancing valve and flow switch (recommended) in the leaving chilled water line. Install a drain with shutoff valve or a drain plug on the evaporator waterbox. Vent the chilled water system at high points in the system piping. Apply heat tape and insulation, as necessary, to protect all exposed piping from freeze-up. 137 Pre-Start Checkout Electrical Wiring WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. CAUTION Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage. • • • • • • • • Connect the unit power supply wiring with fused-disconnect to the terminal block or lugs (or unit-mounted disconnect) in the power section of the control panel. Connect power supply wiring to the evaporator heaters. Connect power supply wiring to the chilled water pump. Connect power supply wiring to any auxiliary heat tapes. Connect the flow switch and then connect to the proper terminals. Connect the chilled water pump to the proper terminals. For the External Auto/Stop function, install wiring from remote contacts (5K14, 5K15) to the proper terminals on the circuit board. Connect the power supply for the convenience outlet, if it is separate from the evaporator heater. CAUTION Information in Interconnecting Wiring! Chilled Water Pump Interlock and External Auto/Stop must be adhered to or equipment damage may occur. 138 RTAC-SVX01F-EN Pre-Start Checkout • • • • • If alarm and status relay outputs are used, install leads from the panel to the proper terminals on circuit board. If the emergency stop function is used, install low voltage leads to terminals on circuit board. Connect separate power for the External Emergency Stop option, if applicable. If the ice making-option is used, install leads on 5K18 to the proper terminals on 1U7. Connect separate power supply for ice making status circuit, if applicable. General When installation is complete, but prior to putting the unit into service, the following pre-start procedures must be reviewed and verified correct: WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR 1. Inspect all wiring connections in the compressor power circuits (disconnects, terminal block, contactors, compressor junction box terminals, etc.). to be sure they are clean and tight. CAUTION Connections! Verify all connections are made. Loose connections can cause overheating and undervoltage conditions at the compressor motor. 2. Open all refrigerant valves in the discharge, liquid, suction, oil and oil return lines. CAUTION Compressor Damage! Catastrophic damage to the compressor will occur if the oil line shut off valve or the isolation valves are left closed on unit start-up. 3. Check the power supply voltage to the unit at the main power fused-disconnect switch. Voltage must be within the voltage utilization range and also stamped on the unit nameplate. Voltage imbalance must not exceed 3%. 4. Check the unit power phasing L1-L2-L3 in the starter to be sure that it has been installed in an “ABC” phase sequence. RTAC-SVX01F-EN 139 Pre-Start Checkout CAUTION Compressor Damage! It is imperative that L1, L2, L3 in the starter be connected in the A-B-C phase sequence to prevent equipment damage due to reverse rotation. 5. Fill the evaporator chilled water circuit. Vent the system while it is being filled. Open the vents on the top of the evaporator waterbox while filling and close when filling is completed. CAUTION Proper Water Treatment! The use of untreated or improperly treated water in the unit may result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water. CAUTION Use Piping Strainers! To prevent evaporator damage, pipe strainers must be installed in the water supplies to protect components from water born debris. Trane is not responsible for equipment-only-damage caused by water born debris. 6. Close the fused-disconnect switch(es) that supplies power to the chilled water pump starter. 7. Start the chilled water pump to begin circulation of the water. Inspect all piping for leakage and make any necessary repairs. 8. With water circulating through the system, adjust water flow and check water pressure drop through the evaporator. 9. Adjust the chilled water flow switch for proper operation. 10. Reapply power to complete procedures. 11. Prove all Interlock and Interconnecting Wiring Interlock and External as described in the Electrical Installation section. 12. Check and set, as required, all CH530 menu items. 13. Stop the chilled water pump. 14. Energize compressor and oil separator heaters 24 hours prior to unit start-up. Unit Voltage Power Supply Voltage to the unit must meet the criteria given in the Installation-Electrical Section. Measure each leg of the supply voltage at the unit's main power fused- disconnect. If the measured voltage on any leg is not within specified range, notify the supplier of the power and correct the situation before operating the unit. 140 RTAC-SVX01F-EN Pre-Start Checkout CAUTION Equipment Damage! Provide adequate voltage to the unit. Failure to do so can cause control components to malfunction and shorten the life of relay contact, compressor motors and contactors. Unit Voltage Imbalance Excessive voltage imbalance between the phases of three-phase system can cause motors to overheat and eventually fail. The maximum allowable imbalance is 3%. Voltage imbalance is determined using the following calculations: % Imbalance = [(Vx - V ave) x 100]/Vave V ave = (V1 + V2 + V3)/3 Vx = phase with the greatest difference from V ave (without regard to the sign) For example, if the three measured voltages are 221, 230, and 227 volts, the average would be: (221+230+227)/3 = 226 The percentage of the imbalance is then: [100(221-226)]/226 = 2.2% This exceeds the maximum allowable (2%) by 0.2 percent. Unit Voltage Phasing CAUTION Compressor Damage! It is imperative that L1, L2, L3 in the starter be connected in the A-B-C phase sequence to prevent equipment damage due to reverse rotation. It is important that proper rotation of the compressors be established before the unit is started. Proper motor rotation requires confirmation of the electrical phase sequence of the power supply. The motor is internally connected for clockwise rotation with the incoming power supply phased A, B, C. Basically, voltages generated in each phase of a polyphase alternator or circuit are called phase voltages. In a three-phase circuit, three sine wave voltages are generated, differing in phase by 120 electrical degrees. The order in which the three voltages of a three-phase system succeed one another is called phase sequence or phase rotation. This is determined by the direction of rotation of the alternator. When rotation is clockwise, phase sequence is usually called "ABC," when counterclockwise, "CBA.” This direction may be reversed outside the alternator by interchanging any two of the line wires. It is this possible interchange of wiring that makes a phase sequence indicator necessary if the operator is to quickly determine the phase rotation of the motor. Proper compressor motor electrical phasing can be quickly determined and corrected before starting the unit. Use a quality instrument, such as the Associated Research Model 45 Phase Sequence Indicator, and follow this procedure. 1. Press the STOP key on the CH530. 2. Open the electrical disconnect or circuit protection switch that provides line power to the line power terminal block(s) in the starter panel (or to the unitmounted disconnect). RTAC-SVX01F-EN 141 Pre-Start Checkout WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR 3. Connect the phase sequence indicator leads to the line Power terminal block, as follows: Phase Seq. Lead Black (Phase A) Red (Phase B) Yellow (Phase C) Terminal L1 L2 L3 4. Turn power on by closing the unit supply power fused-disconnect switch. 5. Read the phase sequence on the indicator. The “ABC” LED on the face of the phase indicator will glow if phase is “ABC.” 6. If the “CBA” indicator glows instead, open the unit main power disconnect and switch two line leads on the line power terminal block(s) (or the unit mounted disconnect). Re-close the main power disconnect and recheck the phasing. CAUTION Compressor Damage! Do not interchange any load leads that are from the unit contactors or the motor terminals. Doing so may damage the equipment. 7. Reopen the unit disconnect and disconnect the phase indicator. Water System Flow Rates Establish a balanced chilled water flow through the evaporator. The flow rates should fall between the minimum and maximum values given on the pressure drop curves. Chilled water flow rates below the minimum values will result in laminar flow, which reduces heat transfer and causes either loss of EXV control or repeated nuisance, low temperature, cutouts. Flow rates that are too high can cause tube erosion in the evaporator. Water System Pressure Drop Measure water pressure drop through the evaporator at the field-installed pressure taps on the system water piping. Use the same gauge for each measurement. Do not include valves, strainers fittings in the pressure drop readings. Pressure drop readings should be approximately those shown in the Pressure Drop Charts in the Mechanical Installation section. 142 RTAC-SVX01F-EN Pre-Start Checkout CH530 Set-Up Use of TechView service tool is required to view and adjust most settings. Refer to the Controls Interface section for instruction on adjustment of the settings. RTAC-SVX01F-EN 143 Unit Start-Up Procedures Daily Unit Start-Up The time line for sequence of operation is shown at the end of this section and depicts the nominal delays and sequences that a chiller would experience during a typical operational cycle. The time line begins with a power up of the main power to the chiller. The sequence assumes a 2 circuit, 2 compressor air-cooled RTAC chiller with no diagnostics or malfunctioning components. External events such as the operator placing the chiller in Auto or Stop, chilled water flow through the evaporator, and application of load to the chilled water loop causing loop water temperature increases are depicted and the chillers responses to those events are shown, with appropriate delays noted. The effects of diagnostics, and other external interlocks other than evaporator water flow proving, are not considered. The response of the EasyView Display is also depicted on the time line. NOTE: Unless the CH530 TechView and building automation system are controlling the chilled water pump, the manual unit start sequence is as follows. Operator actions are noted. CAUTION Compressor Damage! Ensure that the compressor and oil separator heaters have been operating for a minimum of 24 hours before starting. Failure to do so may result in equipment damage. General If the pre-start checkout, has been completed, the unit is ready to start. 1. Press the STOP key on the CH530. 2. As necessary, adjust the setpoint values in the CH530 menus using TechView. 3. Close the fused-disconnect switch for the chilled water pump. Energize the pump(s) to start water circulation. 4. Check the service valves on the discharge line, suction line, oil line and liquid line for each circuit. These valves must be open (backseated) before starting the compressors. CAUTION Compressor Damage! Catastrophic damage to the compressor will occur if the oil line shut off valve or the isolation valves are left closed on unit start-up. 5. Press the AUTO key. If the chiller control calls for cooling and all safety interlocks are closed, the unit will start. The compressor(s) will load and unload in response to the leaving chilled water temperature. 6. Verify that the chilled water pump runs for at least one minute after the chiller is commanded to stop (for normal chilled water systems). 144 RTAC-SVX01F-EN Unit Start-Up Procedures Once the system has been operating for approximately 30 minutes and has become stabilized, complete the remaining start-up procedures, as follows: 1. Check the evaporator refrigerant pressure and the condenser refrigerant pressure under Refrigerant Report on the CH530 TechView. The pressures are referenced to sea level (14.6960 psia). 2. Check the EXV sight glasses after sufficient time has elapsed to stabilize the chiller. The refrigerant flow past the sight glasses should be clear. Bubbles in the refrigerant indicate either low refrigerant charge or excessive pressure drop in the liquid line or a stuck open expansion valve. A restriction in the line can sometimes be identified by a noticeable temperature differential between the two sides of the restriction. Frost will often form on the line at this point. Proper refrigerant charges are shown in the General Information Section. NOTE: Important! A clear sight glass alone does not mean that the system is properly charged. Also check system subcooling, liquid level control and unit operating pressures. 3. Measure the system subcooling. 4. A shortage of refrigerant is indicated if operating pressures are low and subcooling is also low. If the operating pressures, sight glass, superheat and subcooling readings indicate a refrigerant shortage, gas-charge refrigerant into each circuit, as required. With the unit running, add refrigerant vapor by connecting the charging line to the suction service valve and charging through the backseat port until operating conditions become normal. CAUTION Refrigerant! If both suction and discharge pressures are low but sub-cooling is normal, a problem other than refrigerant shortage exists. Do not add refrigerant, as this may result in overcharging the circuit. Use only refrigerants specified on the unit nameplate (HFC 134a) and Trane OIL00048. Failure to do so may cause compressor damage and improper unit operation. Seasonal Unit Start-Up Procedure 1. Close all valves and re-install the drain plugs in the evaporator. 2. Service the auxiliary equipment according to the start-up/maintenance instructions provided by the respective equipment manufacturers. 3. Close the vents in the evaporator chilled water circuits. 4. Open all the valves in the evaporator chilled water circuits. 5. Open all refrigerant valves to verify they are in the open condition. 6. If the evaporator was previously drained, vent and fill the evaporator and chilled water circuit. When all air is removed from the system (including each pass), install the vent plugs in the evaporator water boxes. 7. Check the adjustment and operation of each safety and operating control. 8. Close all disconnect switches. 9. Refer to the sequence for daily unit startup for the remainder of the seasonal startup. RTAC-SVX01F-EN 145 Unit Start-Up Procedures System Restart After Extended Shutdown Follow the procedures below to restart the unit after extended shutdown: 1. Verify that the liquid line service valves, oil line, compressor discharge service valves and suction service valves are open (backseated). CAUTION Compressor Damage! Catastrophic damage to the compressor will occur if the oil line shut off valve or the isolation valves are left closed on unit start-up. 2. Check the oil separator oil level (see Maintenance Procedures section). 3. Fill the evaporator water circuit. Vent the system while it is being filled. Open the vent on the top of the evaporator and condenser while filling and close when filling is completed. CAUTION Proper Water Treatment! The use of untreated or improperly treated water in the unit may result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water. 4. Close the fused-disconnect switches that provides power to the chilled water pump. 5. Start the evaporator water pump and, while water is circulating, inspect all piping for leakage. Make any necessary repairs before starting the unit. 6. While the water is circulating, adjust the water flows and check the water pressure drops through the evaporator. Refer to “Water System Flow Rates” and “Water System Pressure Drop”. 7. Adjust the flow switch on the evaporator piping for proper operation. 8. Stop the water pump. The unit is now ready for start-up as described in “Start-Up Procedures”. 146 RTAC-SVX01F-EN Unit Shutdown Procedures Temporary Shutdown And Restart To shut the unit down for a short time, use the following procedure: 1. Press the STOP key on the CH530. The compressors will continue to operate and, after an unloading period (which may be followed by pumpdown cycle in outdoor ambients below 50oF), will stop when the compressor contactors de-energize. 2. CH530 pump control will turn off the pump (after a minimum 1 min. delay) when the STOP key is pressed and automatically restart the pump when the unit starts normally. 3. The unit will start normally, provided the following conditions exist: – The CH530 receives a call for cooling and the differential-to-start is above the setpoint. – All system operating interlocks and safety circuits are satisfied. Extended Shutdown Procedure The following procedure is to be followed if the system is to be taken out of service for an extended period of time, e.g. seasonal shutdown: 1. Test the unit for refrigerant leaks and repair as necessary. 2. Open the electrical disconnect switches for the chilled water pump. Lock the switches in the “OPEN” position. CAUTION Chilled Water Pump! Lock the chilled water pump disconnects open, to prevent pump damage. 3. Close all chilled water supply valves. Drain the water from the evaporator. 4. With the water drained from evaporator, the "customer provided" power for the 120-volt evaporator heaters (terminated at 1TB4...terminals 1 & 2) must be must disconnect. These heaters consist of 1 well heater in each evaporator end (or water box), and the heat tape, which is wrapped around the bundle itself. They are energized by a klixon temperature control mounted on the side of the evaporator, which energizes at or below 37oF. outside air temp. If there is no liquid in the evaporator and the temp drops below 37 degrees, both of the well heaters will burn up because they have no liquid to transfer their heat into. 5. Open the unit main electrical disconnect and unit-mounted disconnect (if installed) and lock on the “OPEN” position. If the optional control power transformer is not installed, open and lock the 115V disconnect. RTAC-SVX01F-EN 147 Unit Shutdown Procedure CAUTION Disconnect Power! Lock the disconnects in the “OPEN” position to prevent accidental startup and damage to the system when it has been setup for extended shutdown. 6. At least every three months (quarterly), check the refrigerant pressure in the unit to verify that the refrigerant charge is intact. 148 RTAC-SVX01F-EN Periodic Maintenance Perform all maintenance procedures and inspections at the recommended intervals. This will prolong the life of the chiller and minimize the possibility of costly failures. Use an “Operator’s Log”, such as that shown at the end of the section, to record an operating history for the unit. The log serves as a valuable diagnostic tool for service personnel. By observing trends in operating conditions, an operator can anticipate and prevent problem situations before they occur. If the unit does not operate properly during maintenance inspections, refer to “Diagnostics and Troubleshooting”. After the unit has been operating for approximately 30 minutes and the system has stabilized, check the operating conditions and complete the procedures below: Weekly Maintenance While unit is running in stable conditions. 1. Check MP pressure for evaporator, condenser and intermediate oil. 2. Observe liquid line sight glass on EXV. 3. If liquid line sight glass has bubbles measure the subcooling entering the EXV. The subcooling should never be less than 4 °F under any circumstances. A clear sightglass alone does not mean that the system is properly charged. Also check the rest of the system operating conditions. 4. Inspect the entire system for unusual conditions and inspect the condenser coils for dirt and debris. If the coils are dirty, refer to coil cleaning. Monthly Maintenance 1. Perform all weekly maintenance procedures. 2. Record the system subcooling. 3. Make any repairs necessary. Annual Maintenance 1. Perform all weekly and monthly procedures. 2. Check oil sump oil level while unit is off. NOTE: Routine changing of the oil is not required. Use an oil analysis to determine the condition of the oil. 3. Have a qualified laboratory perform a compressor oil analysis to determine system moisture content and acid level. This analysis is a valuable diagnostic tool. 4. Contact a qualified service organization to leak test the chiller, to check operating and safety controls, and to inspect electrical components for deficiencies. 5. Inspect all piping components for leakage and damage. Clean out any inline strainers. 6. Clean and repaint any areas that show signs of corrosion. 7. RTAC-SVX01F-EN Clean the condenser coils. 149 Periodic Maintenance WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR 8. Check and tighten all electrical connections as necessary. 150 RTAC-SVX01F-EN Periodic Maintenance RTAC Start-up Test Log Job Name Model # CRC # Sales Order # Job Location Serial # Job Elevation (ft. above sea level) Ship Date Starter Data: Manufacturer Type: (wye-delta or x-line) Vendor ID #/ Model #: Volts Amps Start-up Only Hz Compressor Data: Chiller Appearance on arrival: Machine gauge pressure: Machine CH.530 pressure Unit R-134a Charge ckt1/ckt2 ckt1/ckt2 lbs gal Unit oil charge (OIL00048) Pressure Test (if required) Compressor A: Model #: Serial # Vacuum after leak test= Standing Vacuum test= RLA KW Volts HZ Compressor B: Model #: Serial # RLA Part number ("X" code and 2-digit extension) X X X X X X KW Volts HZ Compressor C: Model #: Serial # Y Y Y Y Y RLA KW Volts HZ Compressor D: Model #: Serial # RLA KW Volts HZ mm mm rise in hrs Current Transformers Summary of Options Installed N N N N N Tracer Communications Interface Ice Making Other Other Other Evap Design Conditions GPM Entering Water: % Glycol: Type of Glycol: PSID Leaving Water: Evap Actual Conditions GPM Entering Water: % Glycol: Type of Glycol: PSID Leaving Water: Owner Witness Signature: RTAC-SVX01F-EN 151 Periodic Maintenance RTAC Unit Configuration Job Name Model # Serial # Sales Order # Job Location CRC# Job Elevation (ft. above sea level) Ship Date Setpoint View * Front Panel Degree Units (circle one) Front Panel Chilled Water Setpoint Front Panel Current Limit Differential to Stop Differential to Start Leaving Water Temperature Cutout Low Refrigerant Temperature Cutout Condenser Limit Low Ambient Lockout Setpoint Low Ambient Lockout (circle one) Under/Over Voltage Protection Local Atmospheric Pressure Design Delta T Reset Type (circle one) Return Reset Ratio Return Start Reset Return Max Reset Outdoor Reset Ratio Outdoor Start Reset Outdoor Max Reset Chilled Water Pump Delay Time Chilled Water Setpoint Filtering Settling Time Compressor Staging Deadband F or C Enable or Disable Enable or Disable psi F or C None Return Reset Type Outdoor Air Temp. Constant Return % % minutes sec Compressor Service View ** Unit Status: Circuit 1 Control Front Panel Circuit Lockout (circle one) Electronic Expansion Valve (circle one) Circuit 2 Control Front Panel Circuit Lockout (circle one) Electronic Expansion Valve (circle one) Locked or Unlocked Open or Auto Locked or Unlocked Open or Auto Configuration *** Nameplate Model # Confirm Code Serial Number Note: * Using Techview, click on "View" and then click "Setpoint View" Log accordingly. ** Using Techview, click on "View" and then click "Compressor Service View" Log accordingly. *** Using Techview, click on "View" and then click "Configuration" (Nameplate Tab) Log accordingly. 152 RTAC-SVX01F-EN Periodic Maintenance RTAC Chiller Log Job Name Model # Job Location Serial # Status View: * Chiller Tab: Operating Mode Outdoor Air Temperature Active Chill Water Setpoint Active Current Limit Setpoint Evaporator Entering Water Temp. Evaporator Leaving Water Temp. 15 min 30 min 45 min 15 min 30 min 45 min F or C F or C F or C F or C Circuit 1 Tab Not Locked out/ Locked out Not Locked out/ Locked out External Hardwired Lockout Front Panel Lockout 15 min 30 min 45 min Circuit 2 Tab Not Locked out/ Locked out Not Locked out/ Locked out 15 min 30 min 45 min % AirFlow % Inverter Speed psig/kPa Condenser Refrigerant Pressure Saturated Condenser Rfgt. Temp. F or C psid/kPA Differential Refrigerant Pressure Evaporator Refrigerant Pressure psig/kPa F or C Saturated Evaporator Rfgt.Temp. % EXV Position inches/mm Evaporator Rfgt Liquid Level Compressor 1A Tab Compressor 1B Tab Operating Mode Hours Hrs/mins Hrs/mins Starts Phase A - B Voltage Average Line Current Line 1 current Line 2 current Line 3 current Line 1 current Line 2 current Line 3 current Evaporator Oil Return Solenoid Supply Oil Temperature Intermediate Oil Pressure Female Step solenoid High Pressure Cutout switch Comments: RTAC-SVX01F-EN 15 min 30 min 45 min 15 min 30 min 45 min open / closed open / closed open / closed open / closed open / closed open / closed volts %RLA amps amps amps %RLA %RLA %RLA F or C psig/kPa load / unload load / unload Good / Tripped Good / Tripped load / unload load / unload Good / Tripped Good / Tripped load / unload Good / Tripped load / unload Good / Tripped 153 Periodic Maintenance Compressor 2A Tab Operating Mode Hours Starts Phase A - B Voltage Average Line Current Line 1 current Line 2 current Line 3 current Line 1 current Line 2 current Line 3 current Evaporator Oil Return Solenoid Supply Oil Temperature Intermediate Oil Pressure Female Step solenoid High Pressure Cutout switch Comments: 154 Compressor 2B Tab Hrs/mins Hrs/mins 15 min 30 min 45 min 15 min 30 min 45 min open / closed open / closed open / closed open / closed open / closed open / closed volts %RLA amps amps amps %RLA %RLA %RLA F or C psig/kPa load / unload Good / Tripped load / unload Good / Tripped load / unload load / unload Good / Tripped Good / Tripped load / unload Good / Tripped load / unload Good / Tripped RTAC-SVX01F-EN Maintenance Procedures Refrigerant and Oil Charge Management Proper oil and refrigerant charge is essential for proper unit operation, unit performance, and environmental protection. Only trained and licensed service personnal should service the chiller. Some symptoms of a refrigerant under-charged unit: • Low subcooling • Higher than normal discharge superheat • Bubbles in EXV sight glass • Low liquid level diagnostic • Larger than normal evaporator approach temperatures (leaving water temperature - saturated evaporator temperature) • Low evaporator refrigerant temperature limit • Low refrigerant temperature cutout diagnostic • Fully open expansion valve • Possible whistling sound coming from liquid line (due to high vapor velocity) • High condenser + subcooler pressure drop Some symptoms of a refrigerant over-charged unit: • High subcooling • Evaporator liquid level higher than centerline after shut down • Larger than normal condenser approach temperatures (entering condenser saturated temperature – entering air temperature) • Condenser pressure limit • High pressure cutout diagnostic • More than normal number of fans running • Erratic fan control • Higher than normal compressor power • Very low discharge superheat at startup • Compressor rattle or grinding sound at startup Some symptoms of an oil over-charged unit: • Larger than normal evaporator approach temperatures (leaving water temperature - saturated evaporator temperature) • Low evaporator refrigerant temperature limit • Erratic liquid level control • Low unit capacity • Low discharge superheat (especially at high loads) • Low liquid level diagnostics • High oil sump level after normal shut down Some symptoms of an oil under-charged unit: • Compressor rattle or grinding sound RTAC-SVX01F-EN • Lower than normal pressure drop through oil system • Seized or welded compressors 155 Maintenance Procedures • Low oil sump level after normal shut down • Lower than normal oil concentrations in evaporator R134a Field Charging Procedure Be certain that the electrical power to the unit is disconnected before performing this procedure. WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR Factory (initial) Refrigerant Charging Procedure The initial charging procedure should be followed the first time the unit is charged in the factory, as well as for charging any time after the charge has been completely removed from the entire system in the event of repair. 1. As part of automatic vacuum/charge procedure, verify that the EXVs are OPEN. 2. Attach vacuum hoses to evaporator service valves (one per circuit). Open service valves. 3. Attach charging hoses to the charging port on the liquid line filter (one per circuit). The filters contain a port with a ¼” (6mm) flare. 4. Begin semi-automatic vacuum procedure. 5. When vacuum is complete (indicated), manually isolate the unit from vacuum. 6. Charge unit through the filter housing port per Table 1 - Table 5. 7. When charging is complete, shut evaporator service valve and disconnect vacuum and charging hoses. Field Refrigerant Charging Procedure Follow this procedure when the unit is empty of all refrigerant and under a vacuum. Add the charge through the evaporator service valve. CAUTION Evaporator Damage! Water must be flowing through the evaporator during the entire charging process to avoid freezing and rupturing of the evaporator tubes. Charge first with vapor to avoid freezing tubes. 1. 156 Note the weight of the amount of charge removed. Compare it to Table 1 - Table 5. A difference in charge may indicate a leak. RTAC-SVX01F-EN Maintenance Procedures 2. Attach charging hose to evaporator service valve (3/8” (9mm) flare). Open service valve. 3. Add charge to evaporator to bring total circuit charge up to the level indicated in the above chart. 4. Close service valve and disconnect charging hose. Adding charge: This procedure should be followed when adding charge to an undercharged unit. When low charge is indicated by low subcooling in the liquid line, charge should be added until sufficient subcooling is achieved. 1. Attach charging hose to evaporator service valve (3/8” (9mm) flare). Open service valve. 2. Add 10 pounds of refrigerant (R-134a) charge. 3. Close valve, remove charging hose and start unit. Monitor subcooling. 4. If subcooling is still insufficient, return to step #1. NOTE: Proper subcooling can be determined from run log history, service experience, or by contacting Trane technical service. Charge Isolation in the high or low side of system All the refrigerant may be trapped into the high side (condenser) of the unit for maintenance on the compressor or low side. With the suction line service valve option, charge may also be isolated in the evaporator for maintenance on the compressor or the high side. It is preferable to isolate the charge in the evaporator, if this option is available. High side charge isolation procedure: 1. Make sure circuit is off. 2. Shut liquid line service valve. 3. Shut oil return line service valve. 4. Start circuit with the service tool in charge isolation mode: – – – – – – All fans will turn on EXV will open 100% Oil return line solenoid (if included) will open Unit will start at minimum load Unit will run until it cuts out on low pressure (~6 psia) (0.41 bar) Monitor pressure with a suction gauge 5. When unit trips, the discharge check valve will close. 6. Close discharge isolation valve. 7. Close oil line shut off valve. 8. Remove the remainder of the charge with transfer pump. NOTE: Recommendation: Do not pump remaining charge into high side. This may introduce non condensable gasses and other contaminants into the unit. 9. The low side and compressor may be serviced at this time. RTAC-SVX01F-EN 157 Maintenance Procedures Table 37 Charge Holding Capabilities on High Side Nominal Circuit Nominal Circuit Condenser Charge Charge in Oil Capacity Charge Holding Capacity Separator lb @ 60% full lb 90o ambient lb 70 165 118.1 46.9 85 175 134.3 40.7 100 215 163.7 51.3 120 225 187.9 37.1 170 365 203.4 161.6 200 415 282.0 133 240 460 325.6 134.4 Circuit varies slightly with efficiency and unit configuration % Oil Separator Level 97.7 86.0 56.0 41.2 100.0% 86.1 % 86.9 % NOTE: Units with a design sequence of A0 did not have enough capacity in the condenser to hold the entire charge. Table 37 lists the amount of charge that would flood the oil separator if the charge was isolated in the high side. For this reason, when getting the unit back to running condition, care must be taken to drive the refrigerant out of the oil separator using the oil separator heaters. Returning unit to running condition: 1. Open all valves. 2. Manually open EXV for 15 minutes to allow refrigerant to drain to evaporator by gravity (ensure water is flowing in the evaporator prior to opening the EXV). 3. Let unit sit with heaters on to drive refrigerant out of oil and warm up compressor bearings. Depending upon ambient conditions, this may take up to 24 hours.Ensure the UCM is powered so the pump may be energized if it detects a freeze condition. 4. Once the oil level has returned to normal, the unit can be put back into operation. Low side charge isolation procedure: After normal shut down under some conditions most of the charge resides in the evaporator. Running cold water through the evaporator may also drive much of the refrigerant to the evaporator. 1. Make sure circuit is off. 2. Close suction line isolation valve. 3. Close oil return line service valve. 4. Close liquid line service valve. 5. Manually open EXV. 6. Use a liquid pump or vacuum pump to move refrigerant from the condenser to evaporator. The liquid pump will only be effective if there is a lot of charge in the condenser. It may be connected to the condenser drain port on the liquid line isolation valve. NOTE: If a pump is to be used, connect it before closing this valve. This port is only isolated when the valve is back seated. If a vacuum pump is used, then connect it to the discharge line service valve near the oil separator. A vacuum pump will be required for part of the procedure. 158 RTAC-SVX01F-EN Maintenance Procedures The evaporator is large enough to hold all the charge for any unit to below the centerline of the shell. Therefore, no special precautions are required to restart the unit after isolating the charge in the evaporator. Refrigerant Filter Replacement Procedure A dirty filter is indicated by a temperature gradient across the filter, corresponding to a pressure drop. If the temperature downstream of the filter is 8°F (4.4°C) lower than the upstream temperature, the filter should be replaced. A temperature drop can also indicate that the unit is undercharged. Ensure proper subcooling before taking temperature readings. 1. With the unit off, verify that the EXV is closed. Close liquid line isolation valve. On units with remote evaporators or oil cooling circuits, close ball valve on oil cooler liquid line. 2. Attach hose to service port on liquid line filter flange. 3. Evacuate refrigerant from liquid line and store. 4. Remove hose. 5. Depress schrader valve to equalize pressure in liquid line with atmospheric pressure. 6. Remove bolts that retain filter flange. 7. Remove old filter element. 8. Inspect replacement filter element and lubricate o-ring with Trane OIL00048. NOTE: Do not use mineral oil. It will contaminate the system. 9. Install new filter element in filter housing. 10. Inspect flange gasket and replace if damaged. 11. Install flange and torque bolts to 14-16 lb-ft (19-22 n-m). 12. Attach vacuum hose and evacuate liquid line. 13. Remove vacuum hose from liquid line and attach charging hose. 14. Replace stored charge in liquid line. 15. Remove charging hose. 16. Open liquid line isolation valve. On units with remote evaporators or oil cooler circuits, open oil cooler liquid line ball valve. Lubrication System The lubrication system has been designed to keep most of the oil lines filled with oil as long as there is a proper oil level in the oil sump. The total oil charge can be removed by draining the oil system, oil return line from the evaporator, the evaporator, and the compressor. Very small quantities of oil may be found in other components. Like many machines, an excessive oil charge can cause operational problems. Special care should always be taken to avoid adding extra oil. Units that exhibit the symptoms of an oil overcharge at high loads may still run fine at light loads. An oil overcharged unit may result in an evaporator limit warning or even a low liquid level or low evap temp (LRTC) diagnostic. An oil overcharged unit may exhibit increased approach temperatures and decreased overall unit efficiency. Oil Charging Procedure Proper charging of the oil system is critical to the reliability of the compressor and chiller. Too little oil can cause the compressor to run hot and inefficient. When taken to an extreme, low oil level may result in instant failure of the compressor. Too much RTAC-SVX01F-EN 159 Maintenance Procedures oil will result in high oil circulation rates which will foul the condenser and evaporator performance. This will result in inefficient operation of the chiller. Taken to an extreme, high oil levels may result in erratic expansion valve control or shut down of the chiller due to low evaporator refrigerant temperature. Too much oil may contribute to long term bearing wear. Additionally, excessive compressor wear is probable when the compressor is started with the oil lines dry. Figure 46 Oil System Schematic Oil system consists of the following components: • Compressor • Oil separator • Discharge line with service valve • Oil line from separator to compressor • Oil line drain (lowest point in system) • Oil cooler - optional • Oil temperature sensor • Oil line shut off valve with flare service connection • Oil filter (internal to compressor) with flare fitting service connection and schrader valve • Oil flow control valve (internal to the compressor after the filter) • Oil return line from evaporator with shut off valve and strainer Refer to Table 1 - Table 5 for the standard oil charge for each circuit. NOTE: Recommendation: check the oil level in the sump using a sight glass or a manometer, attached to charging hoses. 160 RTAC-SVX01F-EN Maintenance Procedures Table 38 Circuit (Tons) 70 85 100 120 170 200 240 1. Oil Charging Data Approximate sump oil level after running “normal” conditions (in) 7 6 7 7 8 8 8 Normal quantity of oil in refrigeration system (evaporator/condenser) lb (gal) 1.1 (0.14) 1.1 (0.14) 1.8 (0.23) 1.8 (0.23) 3.5 (0.44) 3.5 (0.44) 3.5 (0.44) To measure oil level, use the oil drain valve on the oil line and a service valve on the discharge line. This measurement can only be made when the circuit is not running. Note: The level is measured from the bottom of the separator and 1” must be subtracted for the thickness of the bottom plate. 2. The initial oil charge should be approximately at the level in the above chart. This is the approximate oil level if all the oil is in the oil lines, filter and oil sump and the unit is in vacuum so that there is no refrigerant dissolved in the oil. 3. After the unit has run for a while, the oil level in the sump can vary greatly. However, if the unit has run “normal” conditions for a long time the level should resemble the level in the above chart. (+1” to – 4” (25 to -101mm) is acceptable.) The field charging procedure depends on the circumstances that resulted in the need for oil charge. 1. Some service procedures may result in loss of small quantities of oil which must be replaced (oil analysis, filter replacement, re-tubing the evaporator, etc.). 2. Additionally, some maintenance procedures may result in virtually all of the oil being removed (compressor motor burn or total removal of the charge to trouble shoot a unit). 3. Finally, leaks may result in a loss of oil that must be replaced. Factory (initial) Oil Charging Procedure The initial charging procedure should be followed any time the unit is new or has had all of the oil removed. 4. If the isolation valves is closed, then the charge may be trapped in the evaporator. In either case, the high side of the system should not be pressurized. 5. The oil line shut off valve must be open to allow the oil to pass into the oil lines and the oil separator. 6. The oil charging port is a ¼” (6mm) flare fitting with a schrader valve that is on the side of the oil filter housing. This is the port that must be used to add oil into the compressor so that the filter and lines are full at the first start of the compressor. 7. On single compressor circuits all the oil should be put into the circuit through the oil charging port on the compressor filter housing. On two compressor circuits put approximately ½ of the oil into the unit through each of the two oil charging ports on the two compressors. 8. Oil may be put into the unit using either of two methods: RTAC-SVX01F-EN 161 Maintenance Procedures CAUTION Equipment Damage! Use only Trane OIL00048 in the RTAC units to avoid any catastrophic damage to the compressor or unit. • Have the unit in vacuum. Note that the vacuum connection should be made on the unit at the service valve that is on the discharge line. Hook up the oil charging hose to the oil charging fitting and submerse the other end into the oil container. Let the vacuum draw the required amount of oil into the unit. • Have the unit at the same pressure as the oil. Hook up the oil charging hose to the oil charging fitting and the other end to an oil pump. Use the pump to draw oil out of the oil container and push the required amount of oil into the unit. NOTE: The compressor filter has an internal shut off valve that will prevent oil from entering the compressor while the compressor is not running. Therefore, there is no concern about flooding the compressor with oil. Field Oil Charging Procedure Use the initial charging procedure under the following circumstances: • When virtually all of the oil has been removed. • If the oil charge is removed from the compressor and oil system only but the unit has been run for less than 15 minutes. • If the oil charge is removed from the compressor and oil system only and the unit has been run for more than 15 minutes. However, reduce the amount of oil added to the unit by the normal quantity of oil in refrigeration system. NOTE: This procedure can be followed even with the refrigerant charge isolated in the evaporating section of the unit. If small quantities of oil were removed to service refrigeration components, such as the evaporator, simply replace the oil that was removed into the serviced component prior to vacuum and recharge of the refrigerant. If oil was removed from the compressor only to service a compressor or change the oil filter follow this procedure: 1. If the compressor is a new compressor or has been removed from the system and reworked, add 1 quart (2 lb.) oil to the motor cavity prior to installing the compressor into the chiller. 2. Install the compressor in the system. Make sure that the filter shut off valve is closed. Other compressor isolation valves may also be closed depending upon the service that was completed. For example, changing the oil filter would require the compressor to be isolated and pulled into vacuum. NOTE: Make sure that compressor is not pressurized. 3. Open the flare fitting on the oil line shut off valve. 4. Open the flare fitting on the filter housing. This is the port that must be used to put oil into the compressor. 5. Install charging hose on oil charging port (with schrader valve) and the other on the oil canister. 6. Lift the oil canister, or use a pump, to pour oil into the filter housing. 162 RTAC-SVX01F-EN Maintenance Procedures 7. When oil comes out of the flare fitting on the oil line shut off valve the filter is full. Stop adding oil. 8. Put the cap on the flare on the oil line shut off valve, remove the charging hose and put the cap back on the flare on the filter housing. 9. Vacuum the compressor (low side) and prepare it for inclusion in the system. There is a service valve on the suction line and on the evaporator. Use these valves to vacuum the compressor. 10. Open the oil line shut off valve. Severe damage to the compressor can result if the oil line shut off valve is closed when the compressor is started. CAUTION Compressor Damage! Catastrophic damage to the compressor will occur if the oil line shut off valve or the isolation valves are left closed on unit start-up. 11. Open the other compressor isolation valves. NOTE: This procedure assumes that the oil that is put into the filter housing does not have contaminants such as non-condensable gases. The oil forces these gases out of the filter and oil line shut off valve without the need to pull a vacuum on this small volume. If the oil has been in an open container or is otherwise contaminated, then this small volume must be subject to vacuum as well. However, the filter cavity is full of oil. Therefore, be sure to use a flash tank in line with the vacuum pump to make sure that oil, that is pulled out of the filter cavity, does not slug the vacuum pump. Evaporator tube replacement The units were designed for installation of the tubes from the end of the evaporator opposite the control panel end. The following units will need to have the circuit 2 control panel removed to replace tubes in the evaporator. • 30' Base - 3 compressor units • 36' Base - 3 compressor units CAUTION Evaporator Damage! The tubes are rolled at both ends and in the center. When replacing tubes, take care to ensure that the tube is removed and rolled into the center tube sheet properly. Failure to do so could result in damage to the tubes and improper operation of the system. Compressor Replacement If a compressor needs to be replaced follow the procedures listed below. 1. Isolate the refrigerant charge outside of the compressor and close all four valves leading to the compressor. This includes the oil line service valve located on the oil filter cover of the compressor, the valve on the oil return line from the evaporator, the discharge service valve, and the suction service valve. In the event that the optional suction service valve was not ordered with the unit, insure that the liquid line service valve is closed. RTAC-SVX01F-EN 163 Maintenance Procedures 2. Disconnect power to the chiller. Remove the electrical junction box cover and disconnect the wires. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. 3. Evacuate the compressor through the service fitting provided. If the unit does not have suction service valves, this will include evacuating the low side of the system as well. Disconnect all four lines attached to the compressor, as well as the junction box. Remove three screws from the bottom of the compressor. 4. Remove the compressor by sliding it out of the chiller onto a well supported skid or other platform. The compressor is very heavy, so insure that the support is sturdy. A piece of 1x4 lumber placed between the isolators works well to support the compressor feet as it is pulled from the chiller. 5. Install the new compressor. Reinstall all lines, wires, and screws. Open the service valves, and trim charge as required. 164 RTAC-SVX01F-EN Unit Wiring This section provides field wiring diagrams, electrical schematics and connection diagrams for 140-500 ton RTAC units. Drawing Number 2309-2227 2309-2228 2309-2229 2309-2230 2309-1988 2309-1989 2309-1990 2309-1991 2309-1996 2309-1997 2309-1999 2309-2201 2309-2202 2309-2203 2309-2204 2309-2241 2309-2242 2309-2231 2309-4876 2309-1992 2309-2217 2309-4877 2309-2205 2309-1352 2309-4880 2309-4882 2309-4883 2309-1353 2309-4881 2309-4884 2309-2243 2309-4899 2309-4871 2309-4874 2309-4873 2309-2219 2309-2222 2309-2248 2309-2239 2309-2208 2309-2246 2309-2223 2309-4872 2309-1974 RTAC-SVX01F-EN Description Schematic, M&L, X-L, Ckt 1 Schematic, M&L, X-L, Ckt 2 Schematic, M&L, Y-D, Ckt 1 Schematic, M&L, Y-D, Ckt 2 Schematic, 3&4 Comp, Comp 1A, X-L Schematic, 3&4 Comp, Comp 1B, X-L Schematic, 3&4 Comp, Comp 1A, Y-D Schematic, 3&4 Comp, Comp 1B, Y-D Schematic, 3 Comp, Comp 2A, X-L Schematic, 3 Comp, Comp 2A, Y-D Schematic, Fans, 3 Comp, Ckt2 Schematic, 4 Comp, Comp 2A, X-L Schematic, 4 Comp, Comp 2B, X-L Schematic, 4 Comp, Comp 2A, Y-D Schematic, 4 Comp, Comp 2B, Y-D Schematic, Fans, Medium, 140&155 Std Schematic, Fans, Medium, all others Schematic, Fans, Large (225&250 Prem) Schematic, Fans, 3&4 Comp, Ckt1, Low Volt Schematic, Fans, 3&4 Comp, Ckt1, High Volt Schematic, Fans, 3 Comp, Ckt1, 250T, 50Hz, Std Schematic, Fans, 4 Comp, Ckt2, Low Volts Schematic, Fans, 4 Comp, Ckt2, High Volt Schematic, Control, M&L Schematic, Controls, 3&4 Comp, Ckt1 Schematic, Controls/Legend/Bus, 3 Comp, Ckt2 Schematic, Controls, 4 Compressor, Ckt2 Schematic, Legend/LLID Bus, M&L Schematic, Legend/LLID Bus, 3&4 Comp, Ckt1 Schematic, Legend/LLID Bus, 4 Comp, Ckt2 Schematic, Fans, M&L, Inverters Schematic; Remote Evap Component Location, 2 Comp Component Location, 3 Comp Component Location, 4 Comp Schematic, 3&4 Comp, Single Source Panel Field Wiring, 3&4 Comp, Dual Source Pwr Field Layout, All Field Layout, 3&4 Comp Field Wiring, All Customer Lug Size Field Wiring, 3&4 Comp, Single Source Pwr Component Location, Remte Evap Field Wiring, Remote Evap Page 166 168 170 172 174 176 178 180 182 184 186 188 190 192 194 196 198 200 202 204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 245 246 248 250 165 2227 166 RTAC-SVX01F-EN RTAC-SVX01F-EN 167 2228 168 RTAC-SVX01F-EN RTAC-SVX01F-EN 169 2229 170 RTAC-SVX01F-EN RTAC-SVX01F-EN 171 2230 172 RTAC-SVX01F-EN RTAC-SVX01F-EN 173 1988 174 RTAC-SVX01F-EN RTAC-SVX01F-EN 175 1989 176 RTAC-SVX01F-EN RTAC-SVX01F-EN 177 1990 178 RTAC-SVX01F-EN RTAC-SVX01F-EN 179 1991 180 RTAC-SVX01F-EN RTAC-SVX01F-EN 181 1996 182 RTAC-SVX01F-EN RTAC-SVX01F-EN 183 1997 184 RTAC-SVX01F-EN RTAC-SVX01F-EN 185 1999 186 RTAC-SVX01F-EN RTAC-SVX01F-EN 187 2201 188 RTAC-SVX01F-EN RTAC-SVX01F-EN 189 2202 190 RTAC-SVX01F-EN RTAC-SVX01F-EN 191 2203 192 RTAC-SVX01F-EN RTAC-SVX01F-EN 193 2204 194 RTAC-SVX01F-EN RTAC-SVX01F-EN 195 2241 196 RTAC-SVX01F-EN RTAC-SVX01F-EN 197 2242 198 RTAC-SVX01F-EN RTAC-SVX01F-EN 199 2231 200 RTAC-SVX01F-EN RTAC-SVX01F-EN 201 4876 202 RTAC-SVX01F-EN RTAC-SVX01F-EN 203 1992 204 RTAC-SVX01F-EN RTAC-SVX01F-EN 205 2217 206 RTAC-SVX01F-EN RTAC-SVX01F-EN 207 4877 208 RTAC-SVX01F-EN RTAC-SVX01F-EN 209 2205 210 RTAC-SVX01F-EN RTAC-SVX01F-EN 211 1352 212 RTAC-SVX01F-EN RTAC-SVX01F-EN 213 4880 214 RTAC-SVX01F-EN RTAC-SVX01F-EN 215 4882 216 RTAC-SVX01F-EN RTAC-SVX01F-EN 217 4883 218 RTAC-SVX01F-EN RTAC-SVX01F-EN 219 1353 220 RTAC-SVX01F-EN RTAC-SVX01F-EN 221 4881 222 RTAC-SVX01F-EN RTAC-SVX01F-EN 223 4884 224 RTAC-SVX01F-EN RTAC-SVX01F-EN 225 2243 226 RTAC-SVX01F-EN RTAC-SVX01F-EN 227 4899 228 RTAC-SVX01F-EN RTAC-SVX01F-EN 229 4871 230 RTAC-SVX01F-EN RTAC-SVX01F-EN 231 4874 232 RTAC-SVX01F-EN RTAC-SVX01F-EN 233 4873 234 RTAC-SVX01F-EN RTAC-SVX01F-EN 235 2219 236 RTAC-SVX01F-EN 2247 RTAC-SVX01F-EN 237 2222 238 RTAC-SVX01F-EN RTAC-SVX01F-EN 239 2248 240 RTAC-SVX01F-EN RTAC-SVX01F-EN 241 2239 242 RTAC-SVX01F-EN RTAC-SVX01F-EN 243 2208 244 RTAC-SVX01F-EN 2246 RTAC-SVX01F-EN 245 2223 246 RTAC-SVX01F-EN RTAC-SVX01F-EN 247 4872 248 RTAC-SVX01F-EN RTAC-SVX01F-EN 249 1974 250 RTAC-SVX01F-EN Trane A business of American Standard Companies www.trane.com For more information contact your local district office or e-mail us at comfort@trane.com Literature Order Number RTAC-SVX01F-EN File Number SV-RF-RTAC-SVX01F-EN-0106 Supersedes RTAC-SVX01E-EN Stocking Location Inland Trane has a policy of continuous product data and product improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this bulletin.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Page Count : 252 Page Mode : UseOutlines XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:e19dbcde-3bc7-44c3-9c86-cac54543dd35 Producer : Acrobat Distiller 7.0 (Windows) Abstract : Installation - Operation - Maintenance Acces flag : F Alt order nbr : Alt order nbr type : Bw color : C Date published : 01/01/2006 Dept id : 34 Topic focused id : TRANE|EN Price : 0 Cur flag : T Lit class id : SV Lit length : 252 Lit order nbr : RTAC-SVX01F-EN Lit type id : SVX Media id : PPI Model : RTAC Prod class : RF Prod family id : 2001601 Prod : RLC Restrct flag : F Source date : nulldate Source filename : Stocking loc id : LAXCPY Supceded by : Supceded by date : nulldate Unit flag : T Filename : 801c4380.pdf Branding : Trane Lol language : EN Object id : 090102b1801c4380 Object name : RTAC-SVX01F-EN_01012006 Chronicle id : 090102b18007f052 Hist model : RTAC|RTAC140|RTAC155|RTAC170|RTAC185|RTAC200|RTAC225|RTAC250|RTAC275|RTAC300|RTAC350|RTAC375|RTAC400|RTAC450|RTAC500 Topic related id : TRN-FLD|STARTUP|SERVICER|SERV|RRR|OWN/DEV|OPER|INST|60C|50C Creator Tool : FrameMaker 7.1 Modify Date : 2007:10:17 11:13:44-05:00 Create Date : 2005:12:08 10:05:55Z Metadata Date : 2007:10:17 11:13:44-05:00 Document ID : uuid:bee5f164-9ac6-46a6-a675-69cd047753ff Instance ID : uuid:d752e80a-623a-4e77-8291-ee42feff78e4 N Pages : 252 Format : application/pdf Title : RTAC-SVX01F-EN 01/01/2006 IOM -Series R Air-Cooled Helical Rotary Liquid Chiller. Models RTAC 140-500 ton units (60 Hz), RTAC 140-400 ton units (50 Hz) Creator : laedn Tagged PDF : Yes Author : laedn Acces Flag : F Alt Order Nbr : Alt Order Nbr Type : Bw Color : C Hist Model : RTAC|RTAC140|RTAC155|RTAC170|RTAC185|RTAC200|RTAC225|RTAC250|RTAC275|RTAC300|RTAC350|RTAC375|RTAC400|RTAC450|RTAC500 Date Published : 01/01/2006 Dept Id : 34 Topic Focused Id : TRANE|EN Cur Flag : T Lit Class Id : SV Lit Length : 252 Lit Order Nbr : RTAC-SVX01F-EN Lit Type Id : SVX Media Id : PPI Prod Class : RF Prod Family Id : 2001601 Topic Related Id : TRN-FLD|STARTUP|SERVICER|SERV|RRR|OWN/DEV|OPER|INST|60C|50C Restrct Flag : F Source Date : nulldate Source Filename : Stocking Loc Id : LAXCPY Supceded By : Supceded By Date : nulldate Unit Flag : T Lol Language : EN Object Id : 090102b1801c4380 Object Name : RTAC-SVX01F-EN_01012006 Chronicle Id : 090102b18007f052EXIF Metadata provided by EXIF.tools