Trane Tsd Users Manual
TSD to the manual b9b675a7-eb83-4c1a-93bb-815447702fe1
2015-01-21
: Trane Trane-Tsd-Users-Manual-236129 trane-tsd-users-manual-236129 trane pdf
Open the PDF directly: View PDF .
Page Count: 68
Download | |
Open PDF In Browser | View PDF |
Installation Operation Maintenance Voyager™ I Rooftop Units Cooling-only TSD/TSH 060 072 102 120 Reversible WSD/WSH 060 072 090 Gas-fired YSD/YSH 060 072 090 102 120 RT-SVX20A-E4 General information Foreword Warnings and cautions These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane TSD/TSH, WSKD/WSH and YSD/YSH units. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up. Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel. TSD/TSH units are designed to operate in cooling mode only, with optional auxiliary heat (electric heater or hot water coil). WSD/WSH can operate in cooling mode or heating mode by reversing the refrigeration cycle with or without auxiliary heat. WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents. YSD/YSH units are designed to operate In cooling mode and equipped with a gas fired heating module. TSD/TSH, WSD/WSH and YSD/YSH units are assembled, pressure tested, dehydrated, charged and run tested before shipment. 2 RT-SVX20A-E4 General information Reception Refrigerant Maintenance contract On arrival, inspect the unit before signing the delivery note. In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery. The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer warranty could be cancelled. It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty. Reception in France only: Concealed damage must be looked for at delivery and immediately treated as visible damage. Reception in all countries except France: In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team. Warranty Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer. RT-SVX20A-E4 Storage Take precautions to prevent condensate formation inside the unit's electrical components and motors when: 1. The unit is stored before it is installed; or, 2. The unit is set on the roof curb and temporary auxiliary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for start-up. Do not use the unit's heater as temporary heat without completing the start-up procedures detailed under "Unit Start-Up". The Trane Company will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit electrical components. Training To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown. 3 Contents General information 2 Foreword Warnings and Cautions Reception Warranty Refrigerant Maintenance contract Storage Training 2 2 3 3 3 3 3 3 Installation 6 Reception of units Roof curb installation Dimensions/Weights/Clearances Installing the unit Connection of duct network Condensate drain piping Gas pipework installation Filter installation Supply fan adjustment Component air pressure drops Supply fan performances Electrical connection 6 6 7 9 10 12 13 14 14 16 17 30 Controls 33 Control wiring CO2 sensors Remote potentiometer Fire thermostat Clogged filter detector Smoke detector High temperature safety thermostat Remote fault relay Thermostats Communication Interfaces 4 33 35 39 40 41 41 41 41 42 43 RT-SVX20A-E4 Contents Unit Options 44 Hot water coil Electric Heater Soft Starter 0 - 25% fresh air hood Barometric relief Operation 44 45 45 46 47 48 Operation with a conventional thermostat Setting the economizer Test procedures Test modes Unit Start-up Cooling without an Economizer Low Ambient Operation Cooling with an Economizer Economizer Set-Up ReliaTel™ Control Heating Operation Ignition Module Final installation checklist Maintenance 48 50 52 53 54 56 57 57 58 58 58 59 60 End user routine maintenance Service technician maintenance Troubleshooting RT-SVX20A-E4 60 61 62 5 Installation General information: The installation must conform to all local standards and regulations. Reception of units Rooftop unit There are two ways to handle the unit: 1. Use the openings in the base to handle the machine using a forklift, in accordance with applicable safety regulations. 2. Use a lifting beam correctly adjusted to fit the unit (Figure 1). Unit handling The units are supplied on the truck but are not unloaded. An opening is provided on each corner of the unit base to facilitate handling. Four shackles and four slings are required. Use a lifting beam to prevent the cables pressing too hard on top of the unit during lifting. The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. (Refer to Figures 1 and 2 and Tables 2 and 3.) Important: For unit to fit on the roof curb the fork lift pockets must be removed. Figure 1 - Unit handing 6 Roof curb (accessory) Roof curbs are available as an accessory for downflow units. The curbs can be adjustable and supplied pre-assembled on wooden pallets, packed under plastic film. Two types of self-adhesive seals are provided to ensure the roof curb seal is leak-tight (40 mm wide for the perimeter, 20 mm wide for the crosspieces). Roof curb Installation (TSD-WSD-YSD accessories) Roof curbs are available as an accessory for "downflow" units to support the unit and ensure the water tightness between the rooftop and the roof. The curbs can be adjustable and supplied pre-assembled on wooden pallets, packed under plastic film. Two types of self-adhesive seals are provided separate. (40 mm wide for the perimeter, 20 mm wide for the cross pieces). Make sure they are properly installed where indicated to assure an adequate curb to unit seal. Figure 2 - Rigging 1 2 1 = Remove 2 fork lift brackets 2 = Remove 2 metal runners and 3 wooden boards Lift the unit enough to allow the removal of two Fork Lift brackets and hardware. Remove the two Fork Lift brackets, two metal runners and three wooden boards as shown in Figure 2. Instructions for the roof curb assembly and installation with curb dimensions are provided with each roof curb kit. RT-SVX20A-E4 Installation Dimensions/Weights/ Clearances Figure 3 - Minimum clearances The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. Refer to Table 2 and the space requirement plan. Table 1 - Minimum recommended clearances Unit size Mimum clearances (mm) 1 2 3 4 5 TSD/TSH 060 1829 1219 914 914 914 TSD/TSH 072 1829 1219 914 914 914 TSD/TSH 090 1829 1219 914 914 914 TSD/TSH 102 1829 1219 914 914 914 TSD/TSH 120 1829 1219 914 914 914 YSD/YSH 060 1829 1219 914 914 914 YSD/YSH 072 1829 1219 914 914 914 YSD/YSH 090 1829 1219 914 914 914 YSD/YSH 102 1829 1219 914 914 914 YSD/YSH 120 1829 1219 914 914 914 WSD/WSH 060 1829 1219 914 914 914 WSD/WSH 072 1829 1219 914 914 914 WSD/WSH 090 1829 1219 914 914 914 Table 2 - Unit weights and center of gravity Maximum weight Unit Size Shipping (kg) Net (kg) Corner weight (1) A (kg) B (kg) C (kg) Center of gravity D (kg) Length (mm) Width (mm) TSD/TSH 060 259 235 75 56 48 56 790 480 TSD/TSH 072 365 326 107 83 58 78 970 560 TSD/TSH 090 428 389 131 101 67 89 970 530 TSD/TSH 102 445 405 133 106 72 94 990 560 560 TSD/TSH 120 485 445 147 115 81 104 990 YSD/YSH 060 285 260 81 64 54 62 810 510 YSD/YSH 072 390 350 113 90 64 83 990 560 YSD/YSH 090 458 419 139 110 75 95 970 530 YSD/YSH 102 474 434 141 114 79 100 1020 560 YSD/YSH 120 520 481 155 126 89 111 1020 560 WSD/WSH 060 266 241 77 58 49 58 790 480 WSD/WSH 072 408 368 122 93 66 87 970 560 WSD/WSH 090 418 378 128 95 67 88 970 530 Notes: (1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support. RT-SVX20A-E4 7 Installation Figure 4 A Center of gravity length B Center of gravity width C D Center of gravity Table 3 - Factory-installed options and accessories net weights (kg) Motorized Outside Air Damper Manual Outside Air Damper Economizer Barometric Relief TSD/TSH 060 11,8 3,2 9,1 7,3 31,8 TSD/TSH 072 16,3 4,5 13,6 11,8 52,2 TSD/TSH 090 16,3 4,5 13,6 11,8 52,2 3,6 13,6 17,0 TSD/TSH 1020 16,3 4,5 13,6 11,8 52,2 3,6 13,6 19,0 TSD/TSH 120 16,3 4,5 13,6 11,8 52,2 3,6 13,6 19,0 YSD/YSH 060 11,8 3,2 9,1 7,3 31,8 - 6,8 YSD/YSH 072 16,3 4,5 13,6 11,8 52,2 3,6 13,6 YSD/YSH 090 16,3 4,5 13,6 11,8 52,2 3,6 13,6 YSD/YSH 102 16,3 4,5 13,6 11,8 52,2 3,6 13,6 YSD/YSH 120 16,3 4,5 13,6 11,8 52,2 3,6 13,6 WSD/WSH 060 11,8 3,2 9,1 7,3 31,8 - 6,8 14,0 WSD/WSH 072 16,3 4,5 13,6 11,8 52,2 3,6 13,6 17,0 WSD/WSH 090 16,3 4,5 13,6 11,8 52,2 3,6 13,6 17,0 Unit size Roof Curb Oversized Motor Electric Heaters Hot water coil - 6,8 14,0 3,6 13,6 17,0 Notes: (1) Weights for options not listed are < 3 kg. (2) Net weight should be added to unit weight when ordering factory-installed accessories. (3) Some accessories are not available on all units. 8 RT-SVX20A-E4 Installation Installing the unit Discharge Conversion If a unit is to be converted to Vertical discharge, a panel must be acquired from Trane. If a unit is to be converted to Horizontal discharge, the following conversion must be performed: 1. Remove the return and supply duct covers. 2. Apply gasket to the return duct cover. 3. Position duct covers as shown in Figure 4. The supply duct cover is installed (insulation side down) over the downflow return opening by engaging one side of the panel under a retaining angle and securing the other side with 3 screws. 4. Slide return duct cover (insulation side up) into supply openings until outer edge of the duct cover engages with the two retaining clips on the duct flanges. Secure the outer edge of the each duct cover with two screws. Figure 5 - Conversion to horizontal discharge 3 1 2 1 = Supply duct cover, insulation side down 2 = Return duct cover with gasket installed, insulation side up 3 = Edge of duct cover goes under retaining angle Unit mounting on roof Fix the rooftop curb on the joint beam of the building's structure. Make the rooftop curb's sealing surface level using angle brackets adjusted by screw bolts, located around its perimeter. Place the adhesive seals on the curb's sealing surface (perimeter and cross pieces). Make the rooftop leak-tight around the curbs before installing the unit, in compliance with current construction standards. Figure 6 - Unit mounting on roof Note: The unit must be installed perfectly level to ensure condensates flow from the condensate tray. The rooftop unit nests into the curb and is supported by it. Position the unit, taking care to comply with the indicated directions: the unit's discharge and intake openings must match those of the curb. 1 1 = Frame RT-SVX20A-E4 9 Installation Installing the unit on the ground To install the unit on the ground, its base must be level and supported securely. For horizontal discharge units, a support is required such as a metal or concrete slab whose height must be determined according to the amount of snow cover, to prevent problems with condensation drainage and obstruction of the external coil. If necessary use an anti-vibration material between the rooftop unit's base and the support. Note: Unit installation must comply to local codes Connection of duct network 1) Downflow discharge units (TSD,WSD,YSD) Using the rooftop curb • The rooftop curb must be insulated on the outside walls at the discharge and intake openings to prevent condensation in the ducts. • The rims around the discharge and intake openings make it possible to attach the flanges on the ends of the ducts. If you are using rigid duct ends recommended on the rooftop curb plan, it is essential to fix these components before installing the unit. • For the design of the duct network, comply with recommendations currently applicable on the market, in particular: . Installation of a section of flexible ducts to limit transmission of the unit's vibrations . Use of movable vanes or deflectors to reduce the sound level. 2) Horizontal discharge units (TSH,WSH,YSH) • The intake and discharge ducts must be insulated (thermal insulation). • The duct section located outside must be leak-tight. • Provide a flexible connector to prevent transmission of the unit vibrations. This flexible duct must be installed inside the building. Note: In case of use of units with economizer option, temperature and humidity sensors must be installed in return duct. Economizer linkage is factory mounted but the damper position must be adjusted on site. Figure 7 - Unit installation on the ground 1 = Concrete slab 10 RT-SVX20A-E4 Installation Table 4 - Duct dimensions for downflow units (mm) Unit size A B C D E Flanges TSD 060 619 357 411 459 356 32 YSD 060 610 356 394 457 356 32 WSD 060 819 357 411 459 356 32 TSD/WSD 072/090 875 451 451 875 356 31 TSD 102/120 875 451 451 875 356 31 YSD 072/090/102/120 816 444 444 838 356 31 Table 5 - Duct dimensions for downflow units (mm) Unit size A B C D TSH/WSH 060 591 337 375 438 YSH 060 591 337 375 438 TSH/WSH/YSH 072/090 832 425 606 489 TSH/YSH 102/120 832 425 606 489 Figure 8 - Duct dimensions for downflow units Figure 9 - Duct dimensions for horizontal units B A C D A R S R S C B E D S = Supply R = Return RT-SVX20A-E4 S = Supply R = Return 11 Installation Condensate drain piping Figure 10 - Condensate drain location A 3/4" condensate drain connection with P-trap is provided. Follow local codes and standard piping practices when running the drain line. Install a trap and be sure to fill with water before starting the unit. Pitch the line downward, away from the unit to avoid long, level, horizontal runs. Refer to Figure 11. The condensate drain is reversible to allow installation of a drain tap on either side of the unit. 1 1 = Main condensate drain location Figure 11 - Condensate drain line location 1 2 3 4 12 = = = = Static pressure drain pan Panel enclosure ¾ " drain Cleanout plug RT-SVX20A-E4 Installation The installation must conform to all standards and regulations. CAUTION! Should the pressure at the unit valve gas inlet be higher than 0.035 bar, an expansion valve must be installed. The gas supply pipework and gas stop valve to be installed near the unit must be sized so as to ensure the gas pressure is sufficient at the unit inlet when operating at full load. The pipework must be selfsupporting and the final connection to the burner must be made by a flexible pipe. Provide a dust protection (filter) upstream the unit connection. Gas pipework installation CAUTION! The gas pipework must not exert any stress on the burner gas connection. Note: Expansion valve must be adapted to the type of gas used: • G 20: 20 mb • G 25: 25 mb • G 31 (Propane): 37 or 50 mb Table 6 - Gas burner models Unit Burner size YSD/YSH 060 G120 YSD/YSH 072 G200 YSD/YSH 090 G200 YSD/YSH 102 G250 YSD/YSH 120 G250 See Table 51 for burner performance. Figure 12 - Typical gas supply pipework Gas leak check procedure 1. Vent the gas line 2. Gas supply line pressure test: close valve 4 and open valve 2 3. Leak-check the gas pipe. Look for gas pipe leaks using "Typol", "1000 bulles" or a similar product. Do not use soapy water. WARNING! Never use an open flame to check for gas leaks. Required gas pressure at the unit inlet connection are given in Table 50. Note: To operate with propane gas, the burner is fitted with a pressure limiter (supplied by Trane) 1 = Evaporator section 2 = Gas burner section 3 = Condenser section 4 = Gas supply connection 5 = Gas supply line 6, 8 = Gas stop valve (Field supplied) 7 = Expansion valve (Field supplied) 9 = Filter (Field supplied) RT-SVX20A-E4 13 Installation Filter installation Supply fan adjustment To gain access to filters, remove the supply fan access panel on downflow units and the filter access panel on the end for horizontal units. Use the following procedure to determine the proper adjustment of the supply fan for a specific application. 1. Determine total external static pressure about system and accessories. • Obtain the design airflow rate and the design external static pressure drop through the distribution system. • Add static pressure drop of the accessories installed on the unit. (Table 9) • Add the total accessory static pressure drop (from step 1b) to the design external static pressure (from step 1a). The sum of these two values is the total system external static pressure. 2. Using the Tables 10 through 35 to find the external static pressure that most closely approximates total system external static pressure. Then locate the appropriate airflow rate for your unit. The value obtained represents the brake horsepower for the supply fan motor and the fan RPM. 3. Adjust motor sheave according to Table 8. Number and size of filters is determined by size and configuration of the unit. If disposable filters were chosen as an option, they are shipped in the supply fan section. CAUTION! Do not operate unit without filters in place. The maximum pressure drops allowable on filters are: EU2/G2: 120 Pa EU4/G4: 150 Pa Table 7 - Filter arrangement EU2/G2 EU4/G4 Unit Quantity Size Quantity Size TSD/TSH/YSD/YSH/WSD/WSH 060 2 (508x762x25) 2 (500x750x25) TSD/TSH/YSD/YSH/WSD/WSH 072 4 (406x635x50) 4 (395x625x50) TSD/TSH/YSD/YSH/WSD/WSH 090 4 (406x635x50) 4 (395x625x50) TSD/TSH/YSD/YSH 102 4 (508x635x50) 4 (500x625x50) TSD/TSH/YSD/YSH 120 4 (508x635x50) 4 (500x625x50) 14 RT-SVX20A-E4 Installation To increase airflow To adjust belt Loosen variable sheave set screw and turn sheave clockwise. The fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn. To decrease airflow Loosen variable sheave set screw and turn sheave counter-clockwise. Units with dual belts require a matched set of belts to ensure equal belt length. When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base. Once the new belts are installed, adjust the belt tension. Table 8 - Motor sheave / Fan speed Fan speed (RPM) Standard drive & motor 6 turns Open 5 turns Open 4 turns Open 3 turns Open 2 turns Open 1 turns Open Closed TSD/TSH 060 N/A 898 967 1036 1105 1174 1243 TSD/TSH 072 N/A 698 751 806 859 913 967 TSD/TSH 090 N/A 752 806 860 914 968 1020 TSD/TSH 102 N/A 688 737 786 835 885 934 TSD/TSH 120 N/A 782 838 894 950 1006 1062 YSD/YSH 060 N/A 1036 1105 1174 1243 1312 1381 YSD/YSH 072 N/A 806 860 913 968 1022 1074 YSD/YSH 090 859 913 967 1021 1075 1129 N/A YSD/YSH 102 786 836 885 934 982 1032 N/A YSD/YSH 120 894 950 1006 1062 1118 1174 N/A WSD/WSH 060 N/A 898 967 1036 1105 1174 1243 WSD/WSH 072 N/A 698 751 806 859 913 967 WSD/WSH 090 N/A 752 806 860 914 968 1020 Closed Unit Fan speed (RPM) Oversized drive & motor 6 turns Open 5 turns Open 4 turns Open 3 turns Open 2 turns Open 1 turns Open TSD/TSH 060 N/A TSD/TSH 072 N/A 1243 1311 1379 1450 1515 1588 967 1021 1075 1128 1183 1235 TSD/TSH 090 TSD/TSH 102 1112 1182 1252 1322 1392 1460 N/A N/A 971 1041 1111 1181 1251 1321 TSD/TSH 120 1062 1118 1174 1229 1285 1341 N/A YSD/YSH 060 - - - - - - - YSD/YSH 072 N/A 967 1021 1075 1128 1183 1235 YSD/YSH 090 1112 1182 1252 1322 1392 1460 N/A YSD/YSH 102 N/A 971 1041 1111 1181 1251 1321 YSD/YSH 120 1062 1118 1174 1229 1285 1341 N/A WSD/WSH 060 N/A 1243 1311 1379 1450 1515 1588 Unit WSD/WSH 072 N/A 967 1021 1075 1128 1183 1235 WSD/WSH 090 1112 1182 1252 1322 1392 1460 N/A RT-SVX20A-E4 15 Installation Component air pressure drops Table 9 - Pressure drop through accessories Unit size 060 072 090 102 120 16 Filter EU4/G4 Economizer 100% outside air Airflow (m3/h) Filter EU2/G2 Electric heater Hot water coil 3060 31 50 38 17 49 3400 38 55 46 21 55 3740 46 61 55 25 62 4080 55 66 64 30 68 3670 13 37 27 7 46 4080 16 42 29 9 52 4490 19 46 31 11 58 4900 23 50 33 13 64 66 4590 19 47 33 12 5100 24 52 39 15 74 5610 29 57 45 20 83 6120 35 62 52 25 92 64 5200 16 42 40 8 5780 20 47 50 10 72 6360 25 52 62 12 81 6940 30 57 75 15 90 84 6120 22 50 52 11 6800 27 55 62 14 95 7480 33 61 73 17 106 8160 40 66 85 20 117 RT-SVX20A-E4 Installation Supply fan performances Table 10 - TSD 060 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 225 250 275 300 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW Fan RPM kW Fan RPM kW 2720 - - - - - - - - - - 899 0.43 944 0.49 985 0.54 1023 0.59 1060 0.64 1093 0.69 1126 0.74 3060 - - - - - - - - 904 0.49 947 0.54 988 0.58 1028 0.64 1067 0.70 1104 0.76 1138 0.82 1171 0.87 3400 - - - - - - 918 0.57 958 0.62 998 0.67 1036 0.71 1073 0.76 1111 0.82 1147 0.89 1182 0.96 1215 1.02 3740 - - - - 930 0.65 977 0.71 1016 0.77 1053 0.82 1089 0.88 1124 0.93 1158 0.98 1191 1.03 1226 1.10 1258 1.17 4080 909 0.71 950 0.76 990 0.80 1034 0.87 1074 0.93 1110 1.00 1143 1.06 1177 1.12 1209 1.17 1241 1.23 1272 1.29 - - 325 350 375 m3/h Fan RPM kW Fan RPM kW Fan RPM kW 2720 1160 0.79 1190 0.84 1222 0.90 3060 1203 0.93 1232 0.98 1262 1.04 3400 1246 1.09 1276 1.15 1306 1.21 3740 1290 1.25 - - - - 4080 - - - - - - Table 11 - TSH 060 Available static pressure External Static Pressure (Pa) 25 50 75 m3/h RPM kW RPM kW 2720 - - - - 3060 - - - - 3400 - - 908 0.54 3740 923 0.63 978 4080 997 0.80 1049 325 100 RPM 125 kW RPM kW - - 898 897 0.48 953 961 0.60 0.69 1028 0.87 1096 350 150 RPM kW 0.43 953 0.54 1008 1012 0.67 0.76 1075 0.94 1140 175 200 225 250 275 300 RPM kW Fan RPM kW Fan RPM kW 0.71 1168 0.77 1206 0.83 1241 0.89 0.85 1219 0.92 1256 0.99 1291 1.05 1237 1.02 1274 1.09 1309 1.16 1343 1.24 1.14 1294 1.22 1330 1.29 - - - - - - - - - - - - - RPM kW RPM kW RPM kW RPM kW 0.48 1001 0.54 1045 0.59 1087 0.60 1058 0.67 1102 0.73 1143 0.65 1129 0.79 1181 1062 0.74 1111 0.81 1157 0.88 1198 0.95 0.83 1120 0.91 1166 0.99 1211 1.06 1254 1.02 1183 1.10 1223 1.18 1266 1.27 - 375 m3/h Fan RPM kW Fan RPM kW Fan RPM 2720 1275 3060 1326 0.96 1306 1.02 1338 1.09 1.12 1359 1.19 1390 1.26 3400 1376 1.31 - - - - 3740 - - - - - - 4080 - - - - - - kW Standard drive Oversize drive RT-SVX20A-E4 Note : Data includes pressure drops for standard filters and wet coils 17 Installation Table 12 - TSD 072 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 225 m3/h RPM kW RPM kW RPM kW RPM kW 3260 - - - - - - - - - - 726 0.41 769 0.47 811 0.52 851 3670 - - - - - - - - 706 0.43 751 0.49 792 0.55 832 0.61 871 4080 - - - - - - - - 732 0.51 777 0.58 818 0.64 856 0.71 893 4490 - - - - - - 715 0.54 758 0.60 802 0.68 845 0.75 883 0.82 919 4890 - - - - 706 0.58 749 0.64 789 0.71 830 0.79 870 0.87 909 0.95 945 325 350 kW RPM kW RPM kW RPM kW RPM kW 275 Fan RPM kW 300 Fan RPM RPM kW kW 0.58 889 0.65 925 0.71 960 0.77 0.67 908 0.74 944 0.81 978 0.87 0.77 930 0.84 964 0.91 998 0.99 0.89 953 0.96 986 1.04 1019 1.11 1.02 979 1.10 1011 1.18 1043 1.26 375 Fan RPM kW Fan RPM kW Fan RPM kW 3260 994 0.83 1026 0.89 1057 0.95 3670 1010 0.94 1043 1.01 1073 1.08 4080 1030 1.06 1063 1.14 1092 1.21 4490 1051 1.19 1082 1.27 1112 1.35 4890 1073 1.34 1103 1.42 1133 1.51 m3/h RPM 250 Table 13 - TSH 072 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 kW RPM kW Fan RPM 0.45 814 0.51 857 0.57 899 0.63 939 0.70 978 0.54 843 0.60 883 0.67 922 0.74 960 0.81 996 839 0.65 877 0.71 914 0.78 950 0.85 984 0.93 1020 1.00 1055 1.08 875 0.77 914 0.85 949 0.91 984 0.98 1016 1.06 1049 1.14 1081 1.23 0.91 950 0.99 986 1.07 1019 1.14 1051 1.22 1081 1.30 1112 1.38 RPM kW 3260 - - - - - - 3670 - - - - - - 4080 - - - - 701 0.45 751 0.51 798 0.59 4490 - - 710 0.51 745 0.56 788 0.62 833 0.69 4890 726 0.58 762 0.64 795 0.70 828 0.76 869 0.82 911 325 350 0.42 300 RPM kW - 275 kW RPM 716 250 RPM kW RPM 225 kW RPM kW 200 RPM m3/h RPM 175 kW RPM kW 726 0.39 771 762 0.48 804 Fan RPM kW 0.76 1015 0.83 0.87 1034 0.95 kW 375 m3/h Fan RPM kW Fan RPM kW Fan RPM kW 3260 1051 0.90 1086 3670 1069 1.02 1103 0.97 1118 1.04 1.09 1136 1.17 4080 1089 1.16 4490 1113 1.31 1122 1.23 1154 1.31 1144 1.40 1176 1.48 4890 1141 1.47 1170 1.57 1199 1.66 Standard drive Oversize drive 18 Note : Data includes pressure drops for standard filters and wet coils RT-SVX20A-E4 Installation Table 14 - TSD 090 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 225 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 4080 - - - - - - - - 750 0.54 794 0.60 834 0.67 873 0.73 909 4590 - - - - - - - - 787 0.66 830 0.74 871 0.82 908 0.89 943 5100 - - - - 747 0.68 789 0.74 827 0.82 867 0.90 906 0.98 944 1.06 980 RPM kW RPM kW RPM 250 kW 275 Fan RPM kW 0.87 980 1.04 1010 1013 1.23 RPM kW 0.80 945 0.96 977 1.15 300 Fan RPM kW 0.95 1013 1.02 1.11 1043 1.19 1045 1.31 1076 1.39 5610 - - 755 0.77 797 0.85 836 0.92 873 1.00 908 1.08 944 1.17 980 1.26 1016 1.35 1050 1.45 1081 1.54 1111 1.63 6120 771 0.88 809 0.96 848 1.06 885 1.14 921 1.22 954 1.30 986 1.39 1019 1.49 1052 1.58 1085 1.69 1116 1.79 1148 1.89 325 m3/h Fan RPM 4080 4590 350 375 kW Fan RPM 1046 1.10 1076 1.17 1106 1.25 1074 1.27 1105 1.36 1134 1.44 5100 1105 1.47 1134 1.56 1163 1.65 5610 1141 1.72 1168 1.80 1197 1.90 6120 1177 1.99 1204 2.08 1232 2.18 kW Fan RPM kW Table 15 - TSH 090 Available static pressure External Static Pressure (Pa) 25 50 75 m3/h RPM kW RPM kW 4080 - - - - - 4590 - - - - 773 5100 771 0.68 805 0.74 837 5610 842 0.89 873 0.96 903 6120 913 1.14 942 1.22 970 325 m3/h Fan RPM 350 100 RPM kW 125 RPM kW - 769 0.62 817 0.81 870 1.03 930 1.30 996 150 175 200 225 RPM kW RPM kW RPM kW RPM kW 0.54 814 0.61 855 0.67 893 0.73 929 0.68 862 0.76 904 0.85 941 0.92 975 0.87 912 0.94 951 1.03 989 1.12 1.10 963 1.17 1000 1.25 1037 1.34 1.37 1021 1.45 1052 1.52 1086 1.61 250 275 300 RPM kW Fan RPM kW Fan RPM 0.88 999 0.96 1035 1.04 1070 1.12 1.06 1041 1.14 1073 1.22 1104 1.31 1056 1.28 1088 1.36 1117 1.44 1146 1.53 1106 1.55 1136 1.63 1165 1.72 1194 1.80 1153 1.82 1184 1.93 1215 2.04 1242 2.13 RPM kW 0.81 965 0.98 1009 1025 1.21 1073 1.45 1121 1.71 kW 375 kW Fan RPM kW Fan RPM kW 4080 1104 1.19 1137 1.27 1168 1.35 4590 1136 1.40 1167 1.48 1198 1.57 5100 1176 1.62 1205 1.72 1233 1.82 5610 1220 1.88 1248 1.98 1275 2.08 6120 1269 2.22 1295 2.31 1319 2.40 Standard drive Oversize drive RT-SVX20A-E4 Note : Data includes pressure drops for standard filters and wet coils 19 Installation Table 16 - TSD 102 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 m3/h RPM kW RPM kW RPM kW RPM kW 4620 - - - - - - - - 5200 - - - - - - - - 5780 - - - - - - 689 0.68 RPM 150 175 200 225 250 275 RPM kW RPM kW RPM kW Fan RPM 0.71 769 0.81 802 0.90 833 1.00 0.83 796 0.93 828 1.03 861 1.13 0.96 825 1.07 856 1.18 887 kW RPM kW RPM kW - - 695 0.62 733 688 0.64 725 0.73 761 724 0.76 759 0.86 792 300 kW Fan RPM kW 863 1.11 892 1.21 891 1.24 919 1.35 1.28 917 1.40 946 1.51 6350 - - - - 693 0.72 729 0.82 764 0.92 795 1.01 826 1.11 857 1.22 887 1.34 916 1.46 945 1.58 974 1.70 6930 - - 706 0.80 738 0.89 770 0.98 804 1.09 834 1.19 864 1.30 892 1.40 920 1.52 948 1.64 976 1.78 1002 1.91 325 m3/h Fan RPM 350 kW Fan RPM 375 kW Fan RPM 400 kW Fan RPM kW 425 Fan RPM 450 kW Fan RPM kW 475 Fan RPM 500 kW Fan RPM kW 4620 920 1.33 946 1.44 973 1.55 999 1.67 1025 1.79 1050 1.90 1073 2.02 1098 2.14 5200 946 1.46 973 1.58 999 1.71 1024 1.83 1048 1.96 1072 2.09 1096 2.22 1119 2.34 5780 974 1.63 1001 1.75 1026 1.88 1051 2.01 1074 2.14 1099 2.27 1121 2.41 1143 2.55 6350 1001 1.82 1028 1.95 1054 2.08 1079 2.20 1103 2.34 1126 2.48 1148 2.62 1170 2.76 6930 1029 2.04 1055 2.17 1081 2.30 1105 2.43 1130 2.58 1154 2.72 1176 2.85 1199 3.01 Table 17 - TSH 102 Available static pressure External Static Pressure (Pa) 25 m3/h 50 RPM kW 75 RPM kW 100 RPM kW RPM 125 kW RPM 150 kW RPM kW 175 200 RPM kW 225 RPM kW RPM 250 kW RPM 275 kW Fan RPM kW 300 Fan RPM kW 4620 - - - - - - 689 0.58 734 0.67 781 0.77 826 0.88 865 0.98 898 1.07 928 1.16 956 1.25 982 1.33 5200 - - - - 693 0.64 735 0.73 773 0.82 812 0.92 855 1.03 897 1.15 934 1.27 969 1.38 999 1.49 1026 1.58 5780 - - 711 0.75 743 0.82 781 0.91 819 1.01 853 1.11 886 1.21 925 1.34 964 1.47 1000 1.60 1034 1.73 1067 1.86 6350 735 0.89 770 0.97 799 1.04 830 1.12 865 1.23 899 1.34 930 1.45 960 1.56 994 1.68 1028 1.82 1063 1.96 1098 2.11 6930 796 1.14 828 1.23 857 1.31 883 1.39 913 1.48 945 1.60 977 1.72 1006 1.84 1034 1.96 1061 2.08 1093 2.23 1125 2.38 325 350 400 m3/h Fan RPM 4620 1008 1.42 5200 1052 1.68 5780 1094 1.97 1120 2.08 1145 6350 1129 2.26 1158 2.40 1185 6930 1157 2.53 1188 2.70 1218 2.86 kW Fan RPM 375 425 kW Fan RPM 1033 1.51 1056 1.60 1079 1.69 1102 1.78 1125 1.87 1146 1078 1.78 1101 1.88 1124 1.98 1146 2.08 1168 2.18 1188 2.20 1168 2.31 1191 2.42 1213 2.53 1234 2.63 1254 2.74 2.53 1210 2.66 1234 2.78 1256 2.90 1278 3.03 1299 3.15 1245 3.01 1273 3.16 1297 3.31 - - - - kW Fan RPM 500 Fan RPM kW Fan RPM 475 kW kW Fan RPM 450 Fan RPM kW 1.95 1168 2.04 2.27 1209 2.37 kW Standard drive Oversize drive 20 Note : Data includes pressure drops for standard filters and wet coils RT-SVX20A-E4 Installation Table 18 - TSD 120 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW 5440 - - - - - - - - - - 6120 - - - - - - - - - - RPM 175 200 225 kW RPM kW RPM kW RPM - - 789 0.93 822 1.03 797 0.99 829 1.10 860 1.22 250 275 Fan RPM kW 300 Fan RPM kW RPM kW kW 856 1.14 887 1.25 917 1.36 945 1.47 892 1.34 922 1.46 951 1.57 979 1.69 6800 - - - - - - 782 1.01 814 1.11 844 1.21 874 1.32 903 1.44 932 1.56 960 1.69 988 1.82 1015 1.95 7480 - - - - 803 1.14 834 1.24 864 1.36 894 1.48 922 1.59 948 1.70 975 1.82 1001 1.95 1028 2.09 1053 2.23 8160 803 1.21 833 1.31 861 1.42 887 1.52 916 1.64 945 1.77 972 1.90 997 2.02 1022 2.14 1046 2.27 1071 2.41 1095 2.55 325 m3/h Fan RPM 350 kW Fan RPM 375 kW Fan RPM 400 kW Fan RPM 425 kW Fan RPM 450 475 kW Fan RPM kW 500 Fan RPM kW Fan RPM kW 5440 973 1.60 999 1.72 1024 1.84 1048 1.97 1072 2.10 1095 2.23 1117 2.37 1140 2.51 6120 1007 1.82 1033 1.94 1059 2.07 1082 2.20 1107 2.34 1130 2.49 1152 2.63 1173 2.77 6800 1042 2.08 1068 2.21 1093 2.35 1117 2.48 1142 2.63 1164 2.76 1187 2.91 1209 3.06 7480 1078 2.38 1103 2.52 1128 2.66 1152 2.81 1176 2.95 1198 3.10 1221 3.25 - - 8160 1119 2.70 1142 2.86 1166 3.02 1189 3.17 1212 3.33 - - - - - - Table 19 - TSH 120 Available static pressure External Static Pressure (Pa) 25 m3/h 50 RPM kW 75 RPM kW 100 RPM kW RPM 125 kW 150 RPM kW 175 RPM kW RPM 200 225 kW RPM kW 250 275 300 RPM kW RPM kW Fan RPM kW Fan RPM kW 5440 - - - - - - - - 807 0.94 844 1.04 886 1.16 926 1.28 965 1.41 1000 1.53 1029 1.64 1057 1.75 6120 - - - - 792 0.99 829 1.08 865 1.19 898 1.30 930 1.41 965 1.53 1002 1.67 1038 1.81 1072 1.95 1106 2.10 6800 802 1.13 833 1.22 860 1.29 890 1.38 923 1.50 956 1.62 986 1.73 1015 1.85 1044 1.98 1077 2.12 1111 2.28 1143 2.43 7480 876 1.49 905 1.58 931 1.67 955 1.75 983 1.86 1014 1.99 1045 2.12 1072 2.25 1098 2.37 1125 2.51 1152 2.65 1182 2.81 8160 950 1.91 977 2.02 1002 2.11 1025 2.20 1048 2.30 1074 2.42 1102 2.56 1131 2.71 1156 2.84 1181 2.98 1205 3.12 1229 3.27 325 350 Fan RPM 5440 1084 1.86 1108 1.96 1132 2.06 1155 6120 1134 2.22 1160 2.35 1185 2.47 1209 6800 1174 2.58 1204 2.74 1232 2.90 1260 7480 1211 2.97 1241 3.14 1270 3.31 - 8160 - - - - - - - kW Fan RPM 400 m3/h kW Fan RPM 375 kW Fan RPM 425 450 Fan RPM kW 2.17 1177 2.59 1231 3.05 - kW 475 500 Fan RPM kW Fan RPM kW Fan RPM kW 2.27 1198 2.37 1219 2.48 1239 2.58 2.70 1252 2.82 1274 2.94 1295 3.06 1283 3.18 1306 3.32 - - - - - - - - - - - - - - - - - - - - Standard drive Oversize drive RT-SVX20A-E4 Note : Data includes pressure drops for standard filters and wet coils 21 Installation Table 20 - YSD 060 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 2720 - - - - - - - - - - - - 3060 - - - - - - - - - - - - 3400 - - - - - - - - 1052 0.73 1089 0.79 3740 - - - - 1051 0.82 1087 0.87 1122 0.92 1156 4080 1055 0.90 1093 0.97 1127 1.03 1160 1.09 1193 1.15 1225 325 350 m3/h Fan RPM kW 2720 1208 3060 1262 3400 RPM 200 225 250 275 300 Fan RPM kW 0.72 1145 0.87 1202 1229 1.05 1.17 1288 - - kW RPM kW RPM kW - - 1043 0.62 1078 1066 0.70 1103 0.76 1137 1126 0.85 1162 0.92 0.98 1190 1.03 1224 1.20 1256 1.26 1288 Fan RPM kW 0.77 1177 0.82 0.93 1232 0.98 1260 1.11 1289 1.17 1.24 1320 1.32 - - - - - - - RPM kW 0.67 1113 0.82 1169 1196 0.98 1.10 1257 1.32 - 375 Fan RPM kW Fan RPM kW 0.87 1238 0.93 1268 0.98 1.04 1290 1.09 1319 1.15 1319 1.24 1347 1.30 - - 3740 - - - - - - 4080 - - - - - - Table 21 - YSH 060 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 m3/h RPM kW RPM kW RPM kW 2720 - - - - - - - - 3060 - - - - - - 1056 0.66 RPM kW RPM 150 175 kW RPM 200 kW RPM 225 kW RPM kW RPM - - 1069 0.63 1111 0.68 1151 0.74 1189 1100 0.73 1141 0.79 1180 0.85 1218 0.92 1255 250 kW 275 300 Fan RPM kW 0.87 1260 1.05 1324 RPM kW 0.80 1225 0.98 1290 Fan RPM kW 0.93 1293 0.99 1.12 1357 1.19 - 3400 - - 1033 0.70 1083 0.77 1131 0.84 1176 0.91 1216 0.98 1253 1.05 1289 1.13 1323 1.20 1357 1.27 - - - 3740 1072 0.83 1117 0.90 1163 0.98 1209 1.06 1251 1.14 1292 1.21 1329 1.29 - - - - - - - - - - 4080 1161 1.06 1203 1.14 1245 1.23 1287 1.31 - - - - - - - - - - - - - - - - 325 350 375 m3/h Fan RPM kW Fan RPM kW Fan RPM kW 2720 1324 1.06 1355 1.13 1383 1.20 3060 1390 1.26 - - - - 3400 - - - - - - 3740 - - - - - - 4080 - - - - - - Standard drive Oversize drive 22 Note : Data includes pressure drops for standard filters and wet coils RT-SVX20A-E4 Installation Table 22 - YSD 072 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 225 250 275 300 RPM kW RPM kW RPM kW RPM kW Fan RPM kW Fan RPM kW - - 820 0.54 859 0.60 896 0.66 932 0.72 968 0.78 1000 0.84 814 0.58 854 0.64 891 0.71 928 0.78 963 0.84 996 0.91 1028 0.98 853 0.70 890 0.77 926 0.84 961 0.91 994 0.98 1027 1.05 1058 1.13 0.77 894 0.84 929 0.91 963 0.98 996 1.06 1028 1.14 1060 1.22 1090 1.29 0.93 936 1.01 970 1.08 1003 1.16 1035 1.24 1066 1.32 1096 1.40 1125 1.48 RPM kW RPM kW RPM kW RPM kW RPM kW 3260 - - - - - - - - - - 3670 - - - - - - - - - - 4080 - - - - - - - - 814 0.64 4490 - - - - - - 815 0.70 857 4890 - - - - 818 0.77 860 0.85 899 350 200 kW m3/h 325 175 RPM 375 m3/h Fan RPM kW Fan RPM kW Fan RPM kW 3260 1033 0.90 1063 0.96 1094 1.03 3670 1061 1.05 1091 1.12 1121 1.18 4080 1090 1.21 1118 1.28 1149 1.36 4490 1120 1.38 1150 1.46 1178 1.54 4890 1155 1.57 1181 1.66 1210 1.75 Table 23 - YSH 072 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 225 250 275 Fan RPM Fan RPM kW 0.84 1059 0.92 0.98 1087 1.06 1.15 1119 1.23 1.34 1153 1.42 1192 1.64 m3/h RPM kW RPM kW RPM kW RPM kW 3260 - - - - - - - - - - 824 0.52 866 0.59 907 0.65 947 0.71 986 0.78 1023 3670 - - - - - - - - 826 0.57 865 0.64 903 0.71 943 0.78 979 0.84 1017 0.91 1053 4080 - - - - - - 836 0.64 874 0.70 911 0.77 947 0.84 982 0.92 1017 1.00 1051 1.07 1085 4490 - - - - 847 0.72 888 0.80 924 0.86 959 0.93 993 1.00 1026 1.08 1058 1.17 1089 1.25 1122 4890 818 0.74 858 0.81 900 0.88 940 0.97 977 1.05 1010 1.13 1042 1.20 1073 1.27 1104 1.36 1133 1.45 1163 1.54 325 350 Fan RPM RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 300 kW 375 m3/h Fan RPM kW 3260 1093 0.98 1126 1.06 1156 1.12 3670 1121 1.13 1153 1.21 1185 1.29 kW Fan RPM kW 4080 1151 1.30 1182 1.38 1214 1.47 4490 1184 1.50 1215 1.59 - - 4890 1221 1.72 - - - - Standard drive Oversize drive RT-SVX20A-E4 Note : Data includes pressure drops for standard filters and wet coils 23 Installation Table 24 - YSD 090 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 m3/h RPM kW RPM kW RPM kW RPM kW 4080 - - - - - - - - - - 869 0.73 906 4590 - - - - - - - - 887 0.85 922 0.92 958 RPM kW RPM kW RPM 200 kW 225 RPM kW 0.80 941 0.99 991 250 275 RPM kW RPM kW 0.87 976 0.94 1009 1.01 1.07 1024 1.14 1055 1.22 Fan RPM 300 kW Fan RPM 1042 1.09 1073 1.17 1086 1.30 1117 1.39 1.65 kW 5100 - - - - 865 0.89 905 0.98 943 1.06 979 1.15 1012 1.23 1044 1.31 1075 1.39 1105 1.47 1134 1.56 1163 5610 858 0.97 894 1.05 929 1.13 965 1.22 1001 1.32 1036 1.41 1068 1.50 1099 1.59 1129 1.68 1157 1.77 1185 1.86 1212 1.95 6120 930 1.24 963 1.33 995 1.42 1028 1.51 1061 1.61 1093 1.71 1126 1.82 1157 1.92 1185 2.02 1212 2.11 1239 2.21 1265 2.31 325 m3/h Fan RPM 350 kW Fan RPM 375 kW Fan RPM kW 4080 1104 1.24 1134 1.32 1163 1.40 4590 1146 1.47 1174 1.56 1203 1.65 5100 1191 1.74 1218 1.83 1245 1.92 5610 1238 2.04 1265 2.14 1292 2.24 6120 1290 2.40 1316 2.51 1340 2.61 Table 25 - YSH 090 Available static pressure External Static Pressure (Pa) 25 50 75 100 m3/h RPM kW RPM kW 4080 - - - - 4590 - - - - 5100 869 0.87 910 0.94 950 1.03 5610 949 1.14 985 1.22 1023 1.30 6120 1029 1.47 1061 1.55 1096 1.64 1130 325 m3/h Fan RPM 350 kW Fan RPM RPM 125 150 kW RPM kW RPM kW RPM kW - - 851 0.67 889 0.73 926 880 0.80 919 0.88 955 0.94 989 989 1.12 1023 1.21 1058 1.40 1092 1.51 1.74 1162 1.85 175 200 225 250 275 kW Fan RPM RPM kW 0.80 962 1.01 1022 1056 1.28 1086 1.36 1116 1.43 1146 1.52 1175 1.62 1124 1.60 1154 1.68 1182 1.77 1210 1.85 1237 1.94 1193 1.96 1222 2.06 1250 2.16 1276 2.25 1302 2.34 1327 300 Fan RPM kW 1.19 1134 1.26 1.43 1180 1.52 RPM kW RPM kW RPM kW 0.88 997 0.95 1031 1.03 1067 1.11 1101 1.09 1054 1.17 1086 1.26 1117 1.35 1148 1204 1.72 1232 1.81 1264 2.04 1290 2.14 2.43 1352 2.53 375 kW Fan RPM kW 4080 1166 1.34 1197 1.42 1229 1.50 4590 1210 1.60 1241 1.69 1269 1.78 5100 1260 1.91 1287 2.00 1316 2.10 5610 1316 2.25 1342 2.36 1367 2.46 6120 1376 2.64 1401 2.75 1425 2.87 Standard drive Oversize drive 24 Note : Data includes pressure drops for standard filters and wet coils RT-SVX20A-E4 Installation Table 26 - YSD 102 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW 4620 - - - - - - - - - - 5200 - - - - - - - - - - 5780 - - - - - - - - 805 1.00 6350 - - - - 792 1.00 823 1.10 854 1.21 6930 786 1.03 818 1.14 848 1.24 877 1.34 905 1.46 933 325 m3/h Fan RPM 350 kW Fan RPM 375 kW Fan RPM 400 kW Fan RPM RPM Fan RPM 200 kW RPM kW - - 787 794 0.92 827 837 1.11 884 1.33 1.58 425 kW 175 Fan RPM kW 275 Fan RPM kW Fan RPM 0.85 819 0.96 1.02 859 1.13 869 1.22 900 1.33 929 1.44 959 1.56 986 1.68 1011 1.80 914 1.45 943 1.57 971 1.69 999 1.81 1025 1.94 1051 2.06 961 1.71 988 1.84 1015 1.97 1041 2.10 1067 2.23 1092 2.36 Fan RPM kW 300 kW 475 RPM 250 RPM 450 kW 225 kW RPM kW 850 1.06 879 1.17 907 1.27 934 1.39 890 1.23 918 1.34 946 1.46 971 1.58 500 kW Fan RPM kW 4620 960 1.50 987 1.62 1013 1.73 1038 1.85 1064 1.97 1087 2.09 1111 2.21 1134 2.34 5200 997 1.70 1023 1.83 1047 1.95 1070 2.08 1094 2.21 1117 2.34 1140 2.47 1163 2.60 5780 1037 1.93 1061 2.06 1085 2.19 1107 2.33 1130 2.46 1151 2.60 1174 2.75 1194 2.88 6350 1077 2.19 1100 2.32 1123 2.46 1147 2.61 1168 2.75 1189 2.89 1211 3.04 1231 3.19 6930 1117 2.50 1140 2.64 1164 2.78 1187 2.92 1208 3.07 1229 3.22 - - - - Table 27 - YSH 102 Available static pressure External Static Pressure (Pa) 25 m3/h 50 RPM kW 75 RPM kW 100 RPM kW 125 RPM kW 150 RPM kW 175 RPM kW RPM 200 kW RPM 225 kW 250 RPM kW 275 RPM kW Fan RPM kW 300 Fan RPM kW 4620 - - - - - - 787 0.79 831 0.89 869 0.99 901 1.08 931 1.17 959 1.26 986 1.35 1011 1.43 1036 1.52 5200 - - - - 798 0.88 841 1.00 883 1.11 923 1.23 958 1.35 989 1.45 1017 1.55 1045 1.65 1070 1.75 1094 1.85 5780 793 0.94 830 1.04 863 1.14 898 1.25 937 1.37 975 1.51 1011 1.64 1045 1.77 1075 1.89 1103 2.01 1128 2.12 1152 2.23 6350 865 1.23 899 1.34 930 1.45 961 1.56 994 1.68 1028 1.82 1063 1.96 1097 2.11 1129 2.26 1159 2.40 1186 2.53 1210 2.65 6930 937 1.57 970 1.70 999 1.81 1027 1.93 1055 2.05 1085 2.19 1118 2.34 1150 2.50 1181 2.66 1211 2.82 1239 2.97 1267 3.13 325 m3/h Fan RPM 4620 5200 350 375 1.61 1082 1.69 1104 1.78 1127 1.87 1149 1.96 1170 2.05 1191 2.14 1212 2.24 1.95 1139 2.05 1161 2.15 1182 2.24 1203 2.35 1222 2.44 1243 2.54 1262 2.64 kW Fan RPM 500 1117 kW Fan RPM 475 1059 kW Fan RPM 450 Fan RPM kW Fan RPM 425 kW kW Fan RPM 400 kW Fan RPM kW 5780 1176 2.34 1198 2.45 1219 2.56 1241 2.67 1261 2.78 1280 2.88 1299 2.99 1319 3.11 6350 1233 2.78 1256 2.90 1278 3.03 1298 3.15 1319 3.27 - - - - - - 6930 1291 3.27 - - - - - - - - - - - - - - Standard drive Oversize drive RT-SVX20A-E4 Note : Data includes pressure drops for standard filters and wet coils 25 Installation Table 28 - YSD 120 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 5440 - - - - - - - - - - - - 6120 - - - - - - - - - - - - 6800 - - - - - - - - 913 1.48 941 1.60 969 1.73 7480 - - 895 1.48 923 1.59 949 1.70 976 1.83 1003 1.96 1029 2.10 8160 939 1.75 967 1.87 992 1.99 1017 2.12 1042 2.24 1066 2.38 1090 2.52 1114 325 m3/h Fan RPM 5440 6120 350 kW Fan RPM 1027 1.86 1076 2.17 6800 1126 7480 8160 375 kW Fan RPM 1051 1.99 1100 2.30 2.53 1149 1176 2.96 - - 400 425 Fan RPM kW 1.49 976 1.61 1001 1.73 1.78 1025 1.90 1052 2.03 1050 2.12 1076 2.26 1101 2.39 1104 2.53 1129 2.67 1153 2.81 1161 2.98 1184 3.14 1207 3.30 RPM kW RPM kW - - 891 1.26 921 1.37 949 913 1.42 942 1.54 971 1.66 999 997 1.86 1024 1.99 1054 2.24 1079 2.38 2.67 1138 2.83 Fan RPM 300 Fan RPM kW 475 Fan RPM kW 500 Fan RPM 1075 2.12 1098 2.25 1120 2.38 1143 2.52 1166 1122 2.44 1145 2.58 1167 2.73 1188 2.87 1210 2.67 1172 2.81 1194 2.96 1216 3.12 1236 3.26 - - - - 1200 3.11 1222 3.26 - - - - - - - - - - - - - - - - - - - - - - - - kW 275 RPM 450 kW 250 kW kW kW Fan RPM RPM 225 Fan RPM kW 2.66 1189 2.80 3.02 1230 3.17 kW Table 29 - YSH 120 Available static pressure External Static Pressure (Pa) 25 m3/h 50 RPM kW 75 RPM kW 100 RPM kW RPM 125 kW RPM 150 kW RPM 175 kW RPM 200 kW RPM 225 kW RPM 250 kW RPM 275 kW Fan RPM 300 kW Fan RPM kW 5440 - - - - - - - - 924 1.28 962 1.40 998 1.52 1028 1.64 1055 1.74 1082 1.85 1107 1.95 1131 2.06 6120 - - - - 921 1.37 955 1.49 992 1.63 1028 1.77 1063 1.91 1096 2.05 1126 2.19 1153 2.31 1178 2.43 1202 2.55 6800 943 1.57 973 1.68 1002 1.80 1031 1.92 1062 2.06 1096 2.21 1129 2.36 1161 2.52 1192 2.68 1222 2.84 1249 2.99 1273 3.13 7480 1031 2.06 1060 2.19 1086 2.32 1113 2.45 1139 2.57 1167 2.73 1198 2.90 1228 3.07 1257 3.24 - - - - - - 8160 1119 2.58 1146 2.79 1171 2.93 1195 3.07 1219 3.21 1243 3.36 - - - - - - - - - - - - 325 m3/h Fan RPM 350 kW 375 Fan RPM kW 400 Fan RPM kW 425 450 475 500 Fan RPM kW Fan RPM kW Fan RPM kW Fan RPM kW Fan RPM kW 5440 1154 2.16 1176 2.27 1197 2.37 1218 2.47 1238 2.58 1257 2.68 1276 2.78 1296 2.89 6120 1224 2.67 1247 2.79 1268 2.91 1288 3.02 1308 3.14 1328 3.26 - - - - 6800 1296 3.26 - - - - - - - - - - - - - - 7480 - - - - - - - - - - - - - - - - 8160 - - - - - - - - - - - - - - - - Standard drive Oversize drive 26 Note : Data includes pressure drops for standard filters and wet coils RT-SVX20A-E4 Installation Table 30 - WSD 060 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 m3/h RPM kW RPM kW RPM kW RPM kW 2720 - - - - - - - - - - 3060 - - - - - - - - 892 0.48 3400 - - - - - - 904 0.55 945 0.60 3740 - - - - 913 0.63 959 0.68 1001 4080 - - 933 0.74 972 0.78 1014 0.84 1056 325 m3/h Fan RPM 350 kW Fan RPM RPM kW RPM 175 200 225 250 275 300 RPM kW RPM kW Fan RPM kW 0.53 1014 0.58 1050 0.63 1085 0.62 1056 0.68 1093 0.74 1128 1061 0.75 1098 0.80 1135 0.86 0.85 1109 0.90 1143 0.96 1177 1.03 1160 1.09 1193 1.15 1225 kW RPM kW RPM kW - - 933 935 0.52 976 0.47 975 0.57 1016 985 0.65 1023 0.70 0.74 1038 0.80 1074 0.90 1094 0.97 1128 Fan RPM kW 0.68 1118 0.72 0.80 1160 0.86 1170 0.93 1203 1.00 1.01 1212 1.07 1244 1.14 1.20 1256 1.26 1287 1.32 375 kW Fan RPM kW 2720 1151 0.78 1183 0.83 1214 0.88 3060 1192 0.91 1223 0.97 1252 1.02 3400 1235 1.06 1265 1.12 1295 1.19 3740 1276 1.21 1308 1.29 - - 4080 - - - - - - Table 31 - WSH 060 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 m3/h RPM kW RPM kW RPM kW 2720 - - - - - - - - 941 0.47 990 0.52 3060 - - - - - - 937 0.52 992 0.58 1043 0.65 RPM kW RPM kW RPM kW 175 RPM 200 225 kW RPM 250 kW RPM 275 kW Fan RPM kW RPM 1034 0.58 1077 0.64 1119 0.70 1158 0.75 1196 1088 0.71 1130 0.77 1169 0.83 1207 0.90 1244 300 Fan RPM kW 0.82 1231 0.88 0.96 1280 1.03 kW 3400 - - - - 945 0.58 995 0.65 1045 0.72 1094 0.79 1141 0.86 1185 0.93 1224 1.00 1260 1.07 1295 1.14 1330 1.21 3740 901 0.60 958 0.67 1009 0.73 1057 0.80 1101 0.88 1146 0.95 1192 1.03 1235 1.11 1277 1.18 1314 1.26 - - - - 4080 973 0.76 1026 0.84 1075 0.91 1120 0.98 1163 1.06 1204 1.14 1245 1.23 - - - - - - - - - - 325 350 375 m3/h Fan RPM kW Fan RPM kW Fan RPM kW 2720 1265 0.94 1298 1.00 1330 1.07 3060 1314 1.10 1346 1.16 1380 1.24 3400 1363 1.28 - - - - 3740 - - - - - - 4080 - - - - - - Standard drive Oversize drive RT-SVX20A-E4 Note : Data includes pressure drops for standard filters and wet coils 27 Installation Table 32 - WSD 072 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 225 250 kW Fan RPM kW 0.62 912 0.68 948 0.75 982 0.81 0.72 936 0.79 971 0.86 1004 0.93 0.83 961 0.91 995 0.98 1027 1.06 0.97 987 1.04 1021 1.12 1053 1.20 1018 1.20 1050 1.28 1081 1.36 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 3260 - - - - - - - - 705 0.38 751 0.44 794 0.50 835 3670 - - - - - - - - 736 0.47 779 0.53 821 0.59 860 4080 - - - - - - 720 0.50 768 0.56 810 0.63 850 0.70 888 0.76 925 4490 - - - - 709 0.53 753 0.60 799 0.67 843 0.75 882 0.82 919 0.89 954 4890 - - 705 0.58 749 0.64 791 0.72 832 0.79 874 0.88 914 0.96 950 1.04 985 1.12 350 Fan RPM kW 3260 1015 3670 1037 4080 RPM kW 0.56 874 0.65 898 Fan RPM kW 375 Fan RPM kW 0.87 1047 1.00 1069 1060 1.13 1091 4490 1085 1.28 4890 1112 1.44 m3/h 300 RPM m3/h 325 275 Fan RPM kW 0.93 1079 0.99 1.07 1099 1.14 1.21 1121 1.29 1115 1.36 1145 1.45 1140 1.53 1170 1.62 Table 33 - WSH 072 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 225 m3/h RPM kW RPM kW 3260 - - - - - - - - 750 0.42 794 0.48 3670 - - - - 695 0.40 745 0.46 789 0.51 830 0.58 4080 - - - - 737 0.49 787 0.57 831 0.64 870 0.70 908 0.76 944 4490 - - 740 0.55 781 0.61 828 0.68 872 0.77 911 0.84 948 0.91 983 4890 761 0.64 795 0.70 828 0.76 871 0.83 913 0.91 953 1.00 990 1.08 1023 1.15 325 350 Fan RPM RPM kW RPM kW RPM kW RPM kW RPM kW RPM 250 kW 275 300 kW Fan RPM 963 0.73 1002 987 0.86 1025 1051 1.07 1085 1.15 1081 1.23 1113 1.31 1.40 1147 1.49 kW RPM RPM 838 0.55 882 0.61 923 0.67 871 0.65 910 0.72 950 0.79 0.84 980 0.92 1015 0.99 0.98 1016 1.06 1049 1.14 1055 1.23 1086 1.31 1117 Fan RPM kW 0.80 1038 0.87 0.93 1060 1.00 kW 375 m3/h Fan RPM kW 3260 1073 0.94 1107 1.01 1140 1.09 3670 1096 1.07 1129 1.15 1162 1.23 4080 1118 1.23 1152 1.31 1185 1.39 4490 1146 1.40 1178 1.49 1208 1.57 4890 1178 1.59 1206 1.68 1236 1.77 kW Fan RPM kW Standard drive Oversize drive 28 Note : Data includes pressure drops for standard filters and wet coils RT-SVX20A-E4 Installation Table 34 - WSD 090 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 225 m3/h RPM kW RPM kW RPM kW 4080 - - - - - - - - 768 0.56 810 0.63 850 0.70 888 4590 - - - - - - 763 0.63 807 0.70 850 0.78 889 0.85 926 5100 - - - - 770 0.71 810 0.78 849 0.86 890 0.95 929 1.03 967 5610 - - 782 0.83 823 0.90 861 0.97 897 1.05 933 1.12 969 1.23 1006 6120 798 0.94 838 1.04 876 1.12 913 1.20 947 1.28 980 1.37 1013 1.47 1047 1.57 325 m3/h Fan RPM 4080 4590 350 RPM kW RPM kW RPM kW RPM kW RPM kW 250 RPM kW 0.76 925 0.93 961 1.12 1.33 275 300 Fan RPM kW 0.91 995 0.98 1027 1.06 1.08 1027 1.15 1059 1.23 1034 1.28 1065 1.36 1095 1.45 1074 1.52 1104 1.60 1134 1.70 1113 1.77 1144 1.88 1173 1.98 RPM kW 0.83 961 1.00 995 1000 1.20 1041 1.42 1080 1.67 Fan RPM kW 375 kW Fan RPM 1060 1.13 1091 1.21 1121 1.29 1091 1.32 1121 1.40 1151 1.49 5100 1125 1.53 1154 1.62 1183 1.71 5610 1163 1.79 1191 1.88 1217 1.97 6120 1202 2.08 1229 2.17 1256 2.27 kW Fan RPM kW Table 35 - WSH 090 Available static pressure External Static Pressure (Pa) 25 50 75 100 125 150 175 200 m3/h RPM kW 4080 - - - - - - 787 0.57 831 0.64 870 0.70 908 4590 - - 753 0.59 792 0.65 839 0.72 882 0.80 922 0.88 958 5100 789 0.71 822 0.78 853 0.84 892 0.91 935 0.99 974 1.08 1011 5610 862 0.93 892 1.01 921 1.08 951 1.15 988 1.22 1026 1.31 1062 6120 934 1.20 963 1.28 990 1.35 1016 1.43 1045 1.51 1079 1.59 1115 1.69 325 kW 350 Fan RPM kW 4080 1118 4590 1153 5100 5610 6120 1291 m3/h RPM RPM kW RPM kW RPM kW RPM kW RPM kW 225 RPM kW 0.76 944 0.95 992 1.18 1.42 250 275 RPM kW 0.92 1015 0.99 1.10 1058 1.18 Fan RPM 300 kW Fan RPM 1051 1.07 1085 1.15 1090 1.27 1122 1.36 1.49 1165 1.59 1.78 1214 1.86 1266 2.21 RPM kW 0.84 980 1.02 1026 1044 1.25 1076 1.33 1106 1.41 1136 1096 1.52 1129 1.61 1158 1.69 1187 1148 1.80 1180 1.91 1210 2.02 1239 2.12 kW 375 Fan RPM kW Fan RPM kW 1.23 1152 1.45 1185 1.31 1185 1.39 1.53 1216 1.62 1194 1.68 1242 1.96 1223 1.78 1251 1.88 1269 2.06 1296 2.17 2.30 1317 2.39 1343 2.49 Standard drive Oversize drive RT-SVX20A-E4 Note : Data includes pressure drops for standard filters and wet coils 29 Installation Electrical connection Over current protection The electric panel is located in the unit compressor section. Remove the compressor access panel. The unit is designed to run with 400 V +/- 5%/50 Hz/ 3 ph. The branch circuit feeding the unit must be protected in accordance with national or local codes and maximum unit amps indicated in Table 36. Factory supplied disconnect switch (option) Power wiring The disconnect switch is factory mounted. It is located in the compressor section. Mount the disconnect switch onto the exterior of the unit, between the condenser coil and the electrical panel (near the unit top corner). Wire the disconnect switch from the power terminal block in the panel to the disconnect switch with the wire bundle provided by following the electrical diagram found in the unit. The unit's power supply must be provided by 4-wire cable with crosssectional areas complying with legislation. The power supply cables must be laid in leak-tight pipes and pass through the bottom of the electric panel for units without electric heaters and through the heat section when electric heater option is selected. The cables must not be taut. Appropriate connectors must be provided. Flexible pipe supports are required to prevent noise transmission in the building's structure. Ensure all the connections are tightened. Note: 1. Earthing must be executed in compliance to national and local legislation. 2. The machines are designed for a short-circuit current of 10 kA. In the event of a higher application, contact your local sales office. Compressor electrical phasing Proper phasing of the electrical power wiring is critical for proper operation and reliability of the scroll compressor and fans. Proper rotation of the scroll compressor must be established before the unit is started. This is accomplished by confirming that the electrical phase sequence of the power supply is correct. The motor is internally connected for clockwise rotation with the inlet power supply phased A,B,C. The direction of rotation may be reversed by interchanging any two of the line wires. It is this possible interchange of wiring that makes a phase sequence indicator necessary if the operator is to quickly determine the phase rotation of the compressor motor. Figure 13 - Power supply 1 1 = Power supply 30 RT-SVX20A-E4 Installation The "ABC" indicator on the face of the phase indicator will glow if phase is ABC for terminals L1, L2, L3. WARNING! Disconnect all power, including remote disconnects, and discharge all capacitors before servicing. IMPORTANT! After completion of wiring, check all electrical connections, and ensure all connections are tight. Replace and secure all electrical box covers and access doors before leaving unit or connecting power to circuit supplying the unit. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. After power is removed, allow 4 minutes for capacitors to discharge. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and/or discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see Trane Service Bulletin PROD-SVB06A. CAUTION! Units with scroll compressors are not equipped with crankcase heaters. Table 36 - Unit wiring Standard Supply Fan Motor Unit Model and size Main power supply (V/Ph/Hz) Oversized Supply Fan Motor Minimum Circuit Ampacity (A) Maximum Overcurrent Protective Device (Fuse or Circuit Breaker) (A) Minimum circuit ampacity (A) Maximum Overcurrent Protective Device (Fuse or Circuit Breaker) (A) 32 Without Electric heat option TSD/TSH 060 400/3/50 18,2 32 19,3 TSD/TSH 072 400/3/50 24,4 32 25,5 32 TSD/TSH 090 400/3/50 26,2 40 27,2 40 TSD/TSH 102 400/3/50 28,3 40 29,3 40 TSD/TSH 120 400/3/50 32,6 40 32,6 40 YSD/YSH 060 400/3/50 18,2 32 - - YSD/YSH 072 400/3/50 24,4 32 25,5 32 YSD/YSH 090 400/3/50 26,2 40 27,2 40 YSD/YSH 102 400/3/50 28,3 40 29,3 40 YSD/YSH 120 400/3/50 32,6 40 32,6 40 WSD/WSH 060 400/3/50 20,1 32 21,2 32 WSD/WSH 072 400/3/50 23,1 32 24,2 32 WSD/WSH 090 400/3/50 26,2 40 27,2 40 TSD/TSH 060 400/3/50 26,4 50 27,5 50 TSD/TSH 072 400/3/50 37,8 50 38,9 50 TSD/TSH 090 400/3/50 39,2 50 40,2 50 TSD/TSH 102 400/3/50 50,1 63 51,1 63 With Electric heat TSD/TSH 120 400/3/50 51,8 63 51,8 63 WSD/WSH 060 400/3/50 40,8 50 41,9 50 WSD/WSH 072 400/3/50 55,2 63 56,3 63 WSD/WSH 090 400/3/50 58,3 63 59,3 63 RT-SVX20A-E4 31 Installation Table 37 - Compressor and condenser motors Compressor motor Condensor fan motor Number of motors Main power supply (V) Number of phases Motor HP (kW) TSD/TSH 060 1 400 3 4,2 10,3 74 1 400 1 TSD/TSH 072 1 400 3 5,6 13,7 95 1 400 1 TSD/TSH 090 1 400 3 6,2 14,3 100 1 400 1 TSD/TSH 102 2 400 3 4.5 / 2.8 10 / 7.5 74 / 48 2 400 TSD/TSH 120 2 400 3 4.5 / 3.5 10.7 / 9.2 74 / 62 2 YSD/YSH 060 1 400 3 4,2 10,3 74 YSD/YSH 072 1 400 3 5,6 13,7 YSD/YSH 090 1 400 3 6,2 14,3 YSD/YSH 102 2 400 3 4.5 / 2.8 10 / 7.5 Unit Model and size Rated amps (A) Locked rotor amps (A) Rated amps (A) Locked rotor amps (A) 0,3 1.0 2,8 0,56 3.0 7,1 0,56 3.0 7,1 1 0,56 3.0 7,1 400 1 0,56 3.0 7,1 1 400 1 0,3 1.0 2,8 95 1 400 1 0,56 3.0 7,1 100 1 400 1 0,56 3.0 7,1 74 / 48 2 400 1 0,56 3.0 7,1 Number of motors Main power supply (V) Number of phases Motor HP (kW) YSD/YSH 120 2 400 3 4.5 / 3.5 10.7 / 9.2 74 / 62 2 400 1 0,56 3.0 7,1 WSD/WSH 060 1 400 3 4,5 11,8 74 1 400 1 0,3 1 2,8 WSD/WSH 072 1 400 3 5 12,6 101 1 400 1 0,56 3 7,1 WSD/WSH 090 1 400 3 6,2 14,3 100 1 400 1 0,56 3 7,1 Rated amps (A) Locked rotor amps (A) Table 38 - Supply fan motor Standard supply fan motor Unit Model and size Number of motors Main power supply (V) Number of phases Motor HP (kW) Oversized supply fan motor Rated amps (A) Locked rotor amps (A) Number of motors Main power supply (V) Number of phases Motor HP (kW) TSD/TSH 060 1 400 3 1,1 3,2 25,3 - - - - - - TSD/TSH 072 1 400 3 1,1 3,2 25,3 1 400 3 1,5 4,3 36,4 TSD/TSH 090 1 400 3 1,5 4,3 36,4 1 400 3 2,2 5,3 57.0 TSD/TSH 102 1 400 3 1,5 4,3 36,4 1 400 3 2,2 5,3 57.0 TSD/TSH 120 1 400 3 2,2 5,3 57.0 - - - - - - YSD/YSH 060 1 400 3 1,1 3,2 25,3 - - - - - - YSD/YSH 072 1 400 3 1,1 3,2 25,3 1 400 3 1,5 4,3 36,4 YSD/YSH 090 1 400 3 1,5 4,3 36,4 1 400 3 2,2 5,3 57.0 YSD/YSH 102 1 400 3 1,5 4,3 36,4 1 400 3 2,2 5,3 57.0 YSD/YSH 120 1 400 3 2,2 5,3 57.0 - - - - - - WSD/WSH 060 1 400 3 1,1 3,2 25,3 - - - - - - WSD/WSH 072 1 400 3 1,1 3,2 25,3 1 400 3 1,5 4,3 36.4 WSD/WSH 090 1 400 3 1,5 4,3 36,4 1 400 3 2,2 5,3 57.0 32 RT-SVX20A-E4 Controls Control wiring The control circuit is 24 V AC. Unit includes a 400/24 V transformer. WARNING! The unit disconnect switch must be opened and locked open. Risk of injury and electrocution. CAUTION! The unit 24 V transformer must not be used to power accessories mounted on site, other than those proposed by Trane. Unit controlled by thermostat Figure 14 - Thermostat wiring J7 J6 RT-SVX20A-E4 33 Controls Trane THS01,THS02, THP01 and THP02 Thermostats are directly connected to RTRM board (J7 connector). Trane THS03 and THP03 thermostats are directly connected to RTRM board (J6 connector). Install the electrical link between the thermostat (thermostat terminal strip) and the unit (J6 or J7 connector) in compliance with the interconnection diagram. The low voltage wiring must not be laid in the same pipes as the power cables. The sizes and lengths of the thermostat connection wires are given in Table 39. The total resistance of these control cables must not exceed 5 ohms. If the resistance exceeds this value the thermostat may not operate with the same precision. Table 39 - Zone sensor wire and maximum length 34 Wire size (mm²) Maximum wire lengh (m) 0,33 45 0,5 76 0,75 115 1,3 185 2 300 Unit controlled by BAS Each unit must be equipped with a TCI-R board. A communication bus (twisted shielded pair) must link each TCI-R to the Trane Roof Top Manager (RTM) or to the communication gateway (in the case of an external BAS). Connect one temperature sensor to each unit. LonTalk® communication interface LTCl-R board allows ICS communication between a ReliaTel™ unit and LonTalk® communication applications. Unit controlled by Tracker™ supervisor The units must also be equipped with the TCI-R communication board. One remote sensor is required on each unit for a constant flow volume. In the case of a variable flow installation (VariTrac™) these sensors must not be installed. A twisted shielded pair must be used for the communication link. The main functions of the Tracker™ supervisor are control of setpoints, timetable management (Programming) and display of faults. For more details refer to the supervisor documentation. RT-SVX20A-E4 Controls CO2 sensors Wall-mounted and duct-mounted CO2 sensors The CO2 sensor is designed to operate with a nominal 24 Vac supply. The power supply should maintain the voltage between 20 to 26 Vac. Power supply requirements CAUTION! Make sure that you connect the power wire only to the 24V terminal. Connecting the power wire to the output terminal may result in equipment damage. Table 41 - CO2 sensor wire size Wire size (mm²) Maximum wire lengh (m) 0,25 50 0,5 100 1 200 Table 40 - Specifications Wall-mounted 0-2000 ppm Measuring range CO2 Accuracy at 25°C Duct-mounted < +/- [40 ppm CO2 + 3% of reading] (included repeatability and calibration uncertainty) < +/- [30 ppm CO2 + 2% of reading] (included repeatability and calibration uncertainty) Non-linearity < 1.0% full scale Temperature dependence of output 0.3% full scale/°C Long-term stability < 5.0% full scale/ 5 years Recommended calibration interval 5 years Response time Operating temperature 1 minute (0-63%) 15-35°C Storage temperature -5-45°C -20-70°C Humidity range 0-85% relative humidity Airflow range 0-10 m/s) Output signals (jumper selectable) 0-10 Vdc Resolution of analog outputs 10 ppm CO2 Recommended external load Current output: max 500 Voltage output: min. 1000 Power supply Nominal 24 Vac Power consumption < 5 VA Warm-up time Dimensions (mm) RT-SVX20A-E4 < 15 minutes 108 x 80 x 36 80 x 80 x 200 35 Controls Wiring the wall-mounted CO2 sensor DVC setpoint potentiometer on economizer module can be adjusted as follows: 0% - 500ppm, 50% - 1000 ppm, 100% - 1500ppm The outside air damper will modulate from minimum position setting to up to 100% while attempting to maintain the CO2 setpoint. Wiring the duct-mounted CO2 sensor 1. Connect the common wire from the controller to the ground terminal (terminal 0) (Figure 16). 2. For voltage output, connect the signal wire to terminal V. 3. Connect the power according to the guidelines in Power supply requirements. Figure 15 - Wall-mounted CO2 sensor wiring Figure 16 - Terminal connections and LED locations 2 3 1 1 2 3 4 36 = = = = 4 Outer jumper Power terminal Ground terminal Output terminals RT-SVX20A-E4 Controls Mounting the wall-mounted sensor 1. Select a proper location in the room to mount the CO2 sensor. Look for an interior wall with good air circulation, approximately 1.4 m from the floor. 2. Remove the back plate from the sensor and thread the power wires and output signal wire through the hole in the back plate (Figure 17). For surface wiring, make cutouts with pliers to the thinner section of the upper or lower edge of the back plate and to thread the wires through. 3. Mount the back plate to the wall with screws. Note that the arrow on the back plate shows the mounting direction. 4. On the circuit board, use the two jumpers next to the terminal block to set up the type of output (0-10 Vdc) (Figure 18). 5. Insert the circuit board in the back plate. (Figure 18.) Do not press the metal tube while inserting the circuit board. 6. Connect the power and signal wires to the screw terminals of the circuit board. Figure 16 shows the terminal locations. Figure 17 - Wall-mounted CO2 sensor 1 1 = Thinner section for cut-out Figure 18 - Jumper settings RT-SVX20A-E4 37 Controls Mounting the duct-mounted CO2 sensor 1. Select a proper location on the duct to mount the CO2 sensor. 2. Drill a 22-25 mm hole in the mounting surface for sensor insertion (Figure 19). 3. Attach the mounting plate to the duct wall with four screws. 4. Insert the sensor through the mounting plate, adjusting the depth for optimal air sensing. Figure 19 - Duct-mounted CO2 sensor diameter 15/8 in. (42 mm) 7 /8 in. (22 mm) CO2 sensor maintenance This CO2 sensor has excellent This CO2 sensor has excellent stability and requires no maintenance. In most environments the recommended calibration interval is five years. A trained service technician can use a portable CO2 meter to certify sensor calibration. If, when checking the sensor, the reading differs too much from the reference value, the sensor can be recalibrated in the field. A calibration kit, software, and calibration gases are required. If certified accuracy is required, the sensor must be calibrated against accurate and traceable calibration gases in a laboratory. Consult Trane BAS for further details. 15/8 in. (42 mm) Figure 20 - Duct-mounted CO2 sensor insertion depth 21/2 in. (64 mm) 38 31/8 - 51/2 in. (80 - 140 mm ) RT-SVX20A-E4 Controls Remote potentiometer To install the remote potentiometer, cut the jumper WL on the economizer ECA board, and connect the wires to J11 and J12. Note: This potentiometer allows to adjust the permanent fresh air intake from 0 to 50%. 0 W corresponds to closed fresh air damper. 270 W corresponds to 50% open fresh air damper. Figure 21 - Remote potentiometer dimensions Figure 22 - Remote potentiometer wiring 1 = Remote potentiometer 2 = ECA Board WH = White wire RD = Red Wire BU = Blue wire _____ Factory wiring ------- Field wiring RT-SVX20A-E4 39 Controls Fire thermostat There are two sensors in the fire thermostat Kit: Sensor X1310004001 is factory-set to open at 57°C, Sensor X13100040-02 is set to open at 115°C. Sensors are mounted directly in the ductwork. They should be installed where elements can respond quickly to air temperature changes. If not possible, the sensor may be installed on a suitable bracket so the air is drawn across the element. Sensor X13100040-01 has to be mounted in the return air duct. Sensor X13100040-02 has to be mounted in the supply air duct. Note: Do not permit element guard to touch internal parts. Do not locate sensor where the air circulation is restricted by baffles. At the selected location, cut a hole to clear element guard and drill holes for mounting screws according to Figure 23. Connect wires according to Figure 24. Figure 23 - Duct mounting of fire thermostat Figure 24 - Connection of fire thermostat with TCI board 1 2 1 = Field-supplied emergency stop device 2 = Remove factory-supplied jumper 1 = Fire thermostat 2 = Hole in the duct 40 RT-SVX20A-E4 Controls Clogged filter detector Smoke detector This device is mounted in the indoor fan section. The sensor measures the difference in pressure before and after the filter section. The information is sent to the THP03 thermostat, to a Tracker™ or to a BMS. The setting range is 40 to 300 Pa. This device is used to detect smoke in the air stream. It includes a factory mounted detector connected to a central panel, both fitted in the fan section. When smoke is detected, it shuts off the unit. A dry contact is available on the control panel for a remote default. High temperature safety thermostat This additional safety device is a manual reset thermostat for gas fired units (YKD/YKH), required mainly by the French ERP regulation. It is located in the gas burner section. It stops the gas burner and the supply air fan when the supply air temperature rises to 120°C. Figure 25- Clogged filter sensor Remote fault relay 2 1 3 This is a factory mounted relay used to send alarm signals (dry contact) to a local BMS or a local control panel. With this relay, the compressor, heating, fan and power supply alarm output signals from the controller are reported to a single dry contact. 4 1 2 3 4 = = = = Secure with one screw Route wire harness between coil blockoff and roof rib Secure with pop-in wire tie Remove filter if necessary RT-SVX20A-E4 41 Controls "THS" are non programmable thermostats, "THP" are programmable. Thermostats 6 thermostats are available: THS01/THP01, THS02/THP02 and THS03/THP03. 01 and 02 series are conventional thermostat, 03 series are dedicated to the controller. Table 42 - Thermostat features THS01 THP01 THS02 THP02 THS03 THP03 non-programmable X - X - X - programmable - X - X - X electronic X X X X X X Reliatel Reliatel unit control type design electromech. electromech. electromech. electromech. interface card needed - - - - - - for Cooling Only units X X - - X X for Heat Pump units - - X X X X for Gas Fired units X X - - X X Cooling stages 2 2 2 2 2 2 auxiliary heating stages (elec. heater, HWC ) 2 2 1 1 2 2 none none 1 1 1 1 X X X X - X heating stages (heat pump mode) liquid crystal display Note: thermostats are powered up by the rooftop control (24V) 42 RT-SVX20A-E4 Controls Other accessories available Remote temperature sensor to be used with THS/THP 01-02. TZS01: Remote room temperature sensor to be used with THS/THP 03, Tracker or Varitrac systems. DTS: Duct temperature sensor to be used with THS/THP 03. TZS02: Remote room temperature sensor with adjustable thumwheel setpoint to be used with Tracker or Varitrac systems. TZS04: Room temperature sensor with adjustable thumbwheel and override button, to be used with Tracker or Varitrac systems. Refer to separate documentation for more information. RT-SVX20A-E4 Communication Interfaces TRANE Communication Interface (TCI-R) board This is an electronic board, factorymounted in the main control panel, needed to allow communication between a TRANE Integrated Comfort system (TRACKER or Varitrac CCP2) and the unit. (COM3COM4) LON Communication Interface (LCI-R) board This is an electronic board, factorymounted in the main control panel, needed to allow communication on a LonTalk® Network at the unit level. LonTalk® Communication Interface (LCI-R) board allows Voyager units to communicate on a LonTalk® Network at the unit level. Network variables are based on the LonMark®. Space Comfort Controller Functional Profile Template. The LCIV uses a Free Topology transceiver FTT-10A. The FTT-10A transceiver supports non-polarity sensitive, free topology wiring, allowing the system installer to use star, bus, and loop architecture. The LCI-V can also be connected to an optional High Temperature Limit Switch if installed with the rooftop unit. For more information, see attached manual LTCI-IN-1. 43 Unit Options Hot water coil (Down flow units only) In order to prevent water to freeze up in the coil during unoccupied period or shutdown limited period, a thermostat opens when there is a risk of freeze-up. The services of a water treatment specialist are recommended if water used can cause scaling deposits or erosion. Insulate all the water piping likely to be exposed to freezing temperatures in order to avoid freeze up of the coil and heat losses. The water distribution network must be fitted with vents in places where air is likely to be trapped. The hot water coil is factory mounted in the discharge section. Two holes are provided to connect the hot water coil. They are located at the base of the unit. Remove the central panel to access the coil, using an 8 mm wrench (the bolts are located on the bottom part of the panels). The tubes for entering and leaving water are equipped with a threaded female connector. Water connection inlet/outlet: 1 ¼" ISO R7. Installation and connection In order to prevent water to freeze up in the coil during unoccupied period or shutdown limited period, it is recommended to use ethylene glycol. The services of a water treatment specialist are recommended if water used can cause scaling deposits or erosion. Insulate all the water piping likely to be exposed to freezing temperatures in order to avoid freeze up of the coil and heat losses. The water distribution network must be fitted with vents in places where air is likely to be trapped. Table 43 - Ethylene glycol percentage Figure 26 - Hot water coil connections 44 Ethylene glycol percentage Freezing point (%) (°C) 10 -4 20 -10 RT-SVX20A-E4 Unit Options Electric Heater Soft Starter Electric heaters are fitted on the fan discharge. The soft starter is used to achieve a progressive supply fan start and a reduced starting current as well as the motor starting torque. This option is well adapted for textile duct applications. It is factory installed in the main control panel. Heaters have two heating stages and provided with two types of overheat thermostats: • Automatic reset thermostats which stop the electric heater when the air temperature rises to 76°C. Automatic reset at 60°C. No alarm output available. • The manual reset thermostat which stop the unit when the air temperature rises to 120°C. No alarm output available. The soft starter gradually increases the voltage of the supply fan motor until it reaches full line voltage. The starting time can be adjusted from 0 to 40 seconds but the soft starter is factory set to the maximum starting time value, 40 seconds. Figure 27 - Soft starter 1 6 5 4 3 1 2 3 4 5 6 RT-SVX20A-E4 2 = Three phase mains connections = Motor connections = Settings = Status outputs = Controls = LEDs 45 Unit Options This option includes for the hood itself, a wire mesh and a slidable damper. 0 - 25% fresh air hood The 0-25% fresh air hood allows to introduce fresh air into the unit. The slidable damper has to be adjusted manually by removing the screws and sliding it off up or down (Figure 28). This is a manual device fitted on the back of the unit, sized for a maximum of 25% of the nominal rooftop air flow. The amount of fresh air introduced is then permanently fixed. 210 H Figure 28 - 0-25% manual fresh air hood 5 58 1 3 485 2 1 = Intake hood 2 = Wire mesh 3 = Slidable damper 46 RT-SVX20A-E4 Unit Options Barometric relief This option includes exhaust hoods and gravity dampers located in the return air section. When the pressure of the building increase, the gravity dampers open and relieve air to the outside. The barometric relief allows to minimize overpressure in the building caused by the introduction of fresh air. This option is typically installed when fresh air intake is below 25% of the nominal air flow and when the return air pressure drop is below 25Pa. If the return air duct pressure drop is higher than the building overpressure, the gravity dampers will not open. If the return air duct pressure drop is lower than the building overpressure, the gravity dampers will open and relieve air outside of the building. Figure 29 - Economizer flow chart with barometric relief S R S E R F Downflow version F Horizontal flow version R = return S = supply F = fresh air E = exhaust RT-SVX20A-E4 47 Operation Operation with a conventional thermostat The ReliaTel module has conventional thermostat connections as well as Zone Sensor Module connections. When a conventional thermostat is controlling the unit, operation differs as follows: • Supply Air Tempering feature is not available. If outdoor air is being introduced through the equipment, discharge air temperature may be cold when not actively heating. • Proportional Integral (PI) control is not available. • Zone Sensor Diagnostics are only available on the RTRM module on the J6 terminals, instead of at the Zone Sensor in the space. • Intelligent Fall-Back is not available. If a failure occurs in the device controlling the equipment, operation will cease. • Heat Pump Smart Recovery and Smart Staging is not available. Heat Pump operation becomes more costly unless the generic control being applied can accomplish this. • Remote Sensing Capabilities are not available on most mechanical thermostats. • Space Temperature Averaging capabilities are not available on most mechanical thermostats. • 27½ to 50 VAV - Conventional thermostat input terminals are inactive. • Built in Night Set Back and Unoccupied Functions function differently with a conventional mechanical thermostat. • A built-in algorithm which allows for automatic reset of the discharge air temperature while economizing is not available. 48 The terminal strip for attaching the thermostat wires is located on the RTRM module in the control compartment. When the unit is operating from a conventional thermostat or other binary input, the economizer setpoint feature, relative to the cooling and heating setpoints, is lost. The economizer control is based strictly on a signal from the thermostat, but still maintains mixed air temperature control of 53°±3°F when in the economizer mode. The economizer enable and disable function is still determined by the outside air sensor through the RTRM. If a single-stage thermostat is used, only the economizer (if enabled) or the compressor (if economizer is disabled) will operate on a call for cooling. A twostage thermostat is required to achieve economizer operation and compressor operation at the same time. With economizer enabled, a Y1 call for 1st stage cooling will be the economizer. The damper will modulate between minimum position and 100% to maintain mixed air temperature at 53°±3°. At 50°F the damper will be at minimum position. If the economizer is enabled, a Y2 call for 2nd stage cooling will start the first compressor if required. If the economizer is disabled, 1st stage (Y1) will be the first compressor. If the unit has two compressors, a call for 2nd stage cooling (Y2) will start the second compressor. When using a conventional thermostat, or other binary input, the ReliaTel controls will only allow two stages of cooling. Figure 30 - Terminal strip COM T X2 Y2 W2 G W1/0 Y1 R Customers occasionally require operation with a conventional thermostat rather than a zone sensor. In some cases there is a preference for a specific thermostat model, and in others there is reluctance to adopt newer technology that may not be as well understood as conventional thermostats. In addition, non-Trane Building Controllers typically provide an interface to HVAC equipment based on a conventional thermostat interface. Units applied with this type of controller need to accept conventional thermostat inputs. RT-SVX20A-E4 Operation Conventional thermostat signals represent direct calls for unit functions. In their simplest applications, thermostat contacts directly control contactors or other load switching devices. This function provides inputs for the thermostat signals and processing to enhance reliability and performance. Compressor protection and reliability enhancement functions (HPC, LPC, Minimum On/Off timers, etc.). All operate the same whether applied with zone sensors or a conventional thermostat. Logic is also provided to cause appropriate unit functions when inappropriate thermostat signals are provided. Simultaneous calls for heating and cooling will be ignored, and the fan will be turned on with a call for heating or cooling even if the fan request is not detected. If the thermostat is immediately changed from a heating to a cooling call, or vice versa, there will be a five minute delay before the new call will initiate. Thermostat signals are as follows: R 24VAC power to thermostat Y1 Call for compressor 1 or first stage cooling Y2 Call for compressor 2 or 2nd stage cooling G Call for supply fan W1 Call for heat 1 W2 Call for heat 2 Heat pump only: X2 Call for emergency heat O Switchover valve On = cooling, Off = heating T Bias for heat anticipation for those mechanical thermostats that use this function Table 44 Conventional thermostat Gas / Electric, Electric Heat Input / connection Function when energized G (fan) Fan runs continuously except during unoccupied mode (see next page) Y1 (compressor 1 or economizer) Compressor #1 runs or economizer operates Y2 (compressor 2 or compressor 1 while economizing) Compressor #2 also runs, or #1 compressor runs while economizing W1 (gas / electric heat first stage) 1st stage heat W2 (gas / electric heat 2nd stage) 2nd stage heat (if available) Table 45 Conventional thermostat Heat pump Input / connection Function when energized Cooling mode G (fan) Fan runs continuously except during unoccupied mode (see next page) O (reversing valve during cooling) Reversing valve in cool mode Y1 + O (first cooling stage) Compressor #1 runs or economizer operates Y1 + Y2 + O (2nd cooling stage) Compressor #2 also runs, or #1 compressor runs while economizing Heating mode G (fan) Fan runs continuously except during unoccupied mode (see next page) Y1 (both compressors 1st heating stage) Both compressors run Y2 (during heating nothing happens) No change W2 (electric heat 2nd stage) 2nd stage (electric) heat X2 (electric heat only) Electric heat only - no compressors T (provides heat anticipation signal for those mechanical thermostats that use this feature. If the thermostat used does not have a "T" terminal, disregard this terminal.) RT-SVX20A-E4 49 Operation Unoccupied mode If the thermostat being used is programmable, it will have its own strategy for unoccupied mode and will control the unit directly. If a mechanical thermostat is being used, a field applied time clock with relay contacts connected to J6-11 and J6-12 can initiate an unoccupied mode as follows: • Contacts open: Normal occupied operation. • Contacts closed: Unoccupied operation as follows - Fan in auto mode regardless of fan switch position. Economizer closes except while economizing regardless of minimum position setting. Cooling/Economizer Operation If unit does not have an economizer, the Cool/Econ Stage 1 and Stage 2 will call directly for mechanical cooling (compressor) stages. If the unit has an economizer, the Cool/Econ stages will function as shown in Table 46. Setting the economizer or 0-50% motorized hood (option) The ECA board is mounted on the damper actuator. To access the ECA board on economizers: • Remove the filter access panel of the unit. • The electrical power must be disconnected to set the minimum position and check the economizer. • Disconnect the power supply, put the thermostat fan selector to "ON" and the "HEAT/COOL" selector to "OFF". This puts the damper in the minimum ventilation position. • To set the required minimum ventilation air position, turn the dial on the ECA clockwise to increase ventilation, or anticlockwise to decrease ventilation. The damper will open at this setting whenever the fan circuit is powered up (see Figure 25). • When the arrow on the dial's adjustment screw is pointing to 8 o'clock, the minimum position is roughly 0%. When the dial is pointing to 12 o'clock it is roughly 25%, and when the dial is pointing to 4 o'clock it is roughly 50% (see figure 25). Table 46 - Cooling/Economizer Operation with Thermostat OK to Thermostat Thermostat Call for Economizer Economize? Y1 Y2 Cooling Compressor Staging Request No On Off Inactive Compressor Output 1 No Off On Inactive Compressor Output 2 No On On Inactive Compressor Outputs 1 & 2 Yes On Off Active Off Yes Off On Active Compressor off Yes On On Active Compessor Notes: 40 to 50 ton CV only This unit has 3 stages of cooling if using a zone sensor. If using a conventional thermostat it has 2 stages as follows: Y1 = 1st stage Y1 + Y2 = 3rd stage VAV Thermostat inputs are ignored on VAV units. 50 RT-SVX20A-E4 Operation To check the damper is functioning correctly, the ECA is equipped with an indicator light in the middle of the board. This light operates as in Table 42. Figure 31 - Minimum fresh air adjustment + 1 EXF 2 MIXED AIR SENSOR INPUT COMMON 1 MAT 2 COMMON OHS INPUT 1 OAH/ 2 OAE NOT USED-OAT IS CONNECTED TO RTRM 1 OAT 2 RA INPUT COMMON 1 RAT 2 COMMON RHS INPUT 1 RAH/ 2 RAE CO2 SENSOR INPUT COMMON 1 DCV 2 P P1 2-10 VDC + FEEDBACK INPUT 2-10 VDC + CONTROL OUTPUT MIN POS. SETPOINT 0-50% ABCD SETTINGS GREEN LED CO2 "PURGE" SETPOINT ADJUSTMENT 500-1500 PPM 4 321 POWER EXHAUST CONTACTS Table 47 - ECA board LED OFF: No Power or Failure ON: Normal, OK to Economize Slow Flash: Normal, Not OK to Economize Fast Flash: Communications Failure Pulse Flash: Error Code 1 Flash: Actuator Fault 2 Flashes: CO2 Sensor 3 Flashes: RA Humidity Sensor 4 Flashes: RA Temp Sensor 5 Flashes: OA Quality Sensor 6 Flashes: OA Humidity Sensor 7 Flashes: OA Temp Sensor 8 Flashes: MA Temp Sensor 9 Flashes: RAM Fault 10 Flashes: ROM Fault 11 Flashes: EEPROM Fault 1 While setting the minimum position the damper may move towards the new setting in several small steps. Once the damper has remained in the same position for 10 to 15 seconds it can be assumed it is in the new position. - MODBUS + COMMON 24VAC SHORTED=CLOSED OPEN=ON BOARD POT. 270 omega = 50% REMOTE MINIMUM POTENTIOMETER WHT RED BLUE 1 = ECA board RT-SVX20A-E4 51 Operation Test procedures Operating checklist before start-up • Unit is level, with sufficient clearance all round • Duct network is correctly sized according to the unit configuration, insulated, and water-tight • Condensate drainage line is correctly sized, equipped with a trap, and sloped • Filters are in position, of correct size and quantity and clean • Wiring is correctly sized and connected in accordance with wiring diagrams • Power supply lines are protected by recommended fuses and correctly earthed • Thermostat is correctly wired and positioned • Unit is checked for refrigerant charge and leaks • Indoor and outdoor fans rotate freely and are fixed on shafts • Supply fan rotation speed is set • Access panels and doors are replaced to prevent air entering and risks of injury • Checking of the gas heating section, in accordance with above procedure 52 WARNING! If any operating checks must be performed with the unit operating, it is the technician's responsibility to recognize any possible hazards and proceed in a safe manner. Failure to do so could result in severe personal injury or death due to electrical shock or contact with moving parts. Test mode procedure at the ReliaTel™ control board Power-up initialization CAUTION! Use one of the following "Test" procedures to bypass some time delays and to start the unit at the control panel. CAUTION! Before proceeding with any test procedure or operation, make sure that crankcase heaters have been energized for at least 8 hours. Units equipped with Scroll compressors do not have crankcase heaters. Note: Upon power initialization, the RTRM performs self-diagnostic checks to insure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system. The Liteport LED located on the RTRM module is turned "On" within 1 second of power-up if internal operation is okay. Operating the unit from the roof using the test mode at the ReliaTel™ control board. CAUTION! Before proceeding with the following test procedures, make sure that thermostat or zone sensor is off. Each step of unit operation can be activated individually by temporarily shorting across the "Test" terminals for two to three seconds. The Liteport LED located on the RTRM module will blink when the test mode has been initiated. The unit can be left in any "Test" step for up to one hour before it will automatically terminate, or it can be terminated by opening the main power disconnect switch. Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the "System" control. RT-SVX20A-E4 Operation Outdoor Fan Motor 1 Heat 2 Heat 1 Compressor 2 Compressor 1 Economizer Mode Min Off Off Off Off Off Off Open Off Off Off Off Off Off 3 Cool 1 On Min On Off Off Off On ** 4 Cool 2 On Min On On Off Off On ** 5* Heat 1 On Min Off Off On Off Off Off 6* Heat 2 On Min Off Off On On Off Off * With Optional Accessory ** "Off" If temperature falls below 16° (±1°C), "On" if temperature rises above 18° (±1°C). Note: Steps for optional accessories and modes not present in unit will be skipped. Outdoor Fan Motor 1 Heat 2 Heat 1 Compressor 2 Compressor 1 Table 49 - Service Test Guide for Component Operation on Heat Pump Units Economizer For unit test steps and test modes, values to cycle the various components, refer to Tables 48 and 49. On On Indoor Fan motor This method is not recommended for start-up due to the short timing between individual component steps. This method initiates the different components of the unit, one at a time, when a jumper is installed across the test terminals. The unit will start the first test step and change to the next step every 30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied "System" control method. Fan On Economizer Mode 2. Auto Test Mode 1 2* Step This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds. For the initial startup of the unit, this method allows the technician to cycle a component "On" and have up to 1 hour to complete the check. Step 1. Step Test Mode Indoor Fan motor There are 2 methods in which the "Test" mode can be cycled with the test button: Outdoor Fan Motor 1 Table 48 - Service Test Guide for Component Operation on cooling only units Outdoor Fan Motor 1 Test modes 1 Fan On On Min Off Off Off Off Off Off 2* Economizer On Open Off Off Off Off Off Off 3 Cool 1 On Min On Off Off Off On ** 4 Cool 2 On Min On On Off Off On ** 5* Heat 1 On Min Off Off On Off Off Off 6* Heat 2 On Min Off Off On On Off Off * With Optional Accessory ** "Off" If temperature falls below 16° (±1°C), "On" if temperature rises above 18° (±1°C). Note: Steps for optional accessories and modes not present in unit will be skipped. RT-SVX20A-E4 53 Operation Figure 32 - Gas valve Unit start-up Verification of gas valve settings (Reserved for the qualified gas technician) Note: Unit to be installed outside only. G20 - 7.5mbar G25 -10.5mbar 1 WARNING! Improper gas valve setting may lead to burner destruction and people injury. Note: Expansion valve must be adapted to the type of gas used: • G 20: 20 mb • G 25: 25 mb • G 31 (Propane): 37 or 50 mb 3/32" Note: Unit factory-set for G20. 1 = Screw to set gas valve Table 50 - Gas type designation per country Destination countries FR DE-LU-PL CH-ES-GB-IE-PT-CZ-GR NL IT-AT-NO-FI-SE-EE-LT-LV IT BE DK-SK-SI-TR BE-PL AT-DE-LU-HU-SK HU Pressure in mbar 20/25 37 20 20 37 25 30 20 28-30/37 20/25 20 37 50 25 Category II2E+3P I2E II2H3P II2L3P I2H I3+ I2E I2H I3P I3P I2H Table 51 - Gas burner data Burner G120 G200 G250 Gas Type G20 G25 G31 G20 G25 G31 G20 G25 Heating Input (kW) 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Heating Output (kW) 24,6 25 25,1 41,3 41,7 41,9 51,9 52,3 52,6 Efficiency 93% 93% 93% 93% 93% 93% #DIV/0! #DIV/0! 93% 2,8 3,3 2,1 4,7 5,5 3,5 5,9 6,9 4,4 34,02 29,3 46,34 34,02 29,3 46,34 34,02 29,3 46,34 17 / 20 / 25 20 / 25 / 30 25 / 37 / 45 17 / 20 / 25 20 / 25 / 30 25 / 37 / 45 17 / 20 / 25 20 / 25 / 30 Low pressure switch setting (mbar) 15 15 20 15 15 20 15 15 20 Manifold pressure (mbar) 7,5 10,5 24,9 7,5 10,5 24,9 7,5 10,5 24,9 Gas Flow rate (Nm3/h) Specific Heating Capacity (MJ/kg) Heating Output per stage (1st/2nd) (%) Inlet pressure Min/Nominal/Max (mbar) 0%-100% No of injectors Injector size (Drill / mm) 0%-70%-100% 3 (33) / 2.87mm 0%-70%-100% 4 (51) / 1.70mm (1/8") / 3.175mm G31 25 / 37 / 45 5 (49) / 1.85mm (1/8") / 3.175mm (49) / 1.85mm Smoke analysis Gas / Voltage G20 - 20mbar G25 - 25mbar G31 - 37mbar G20 - 20mbar G25 - 25mbar G31 - 37mbar G20 - 20mbar G25 - 25mbar G31 - 37mbar 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 CO % 0.0012% 0.0017% 0.0003% 0.0020% 0.0015% 0.0011% 0.0020% 0.0015% 0.0011% Nox ppm 59 ppm 44 ppm 8.7 ppm 10 ppm 10 ppm 11 ppm 10 ppm 10 ppm 11 ppm CO2 % 8,29% 9,20% 8,90% 7,10% 7,10% 8,28% 7,10% 7,10% 8,28% Notes: (1) G20 heating output given for 34,02 MJ/m3 (15°C-1013) (2) G25 heating output given for 29,30 MJ/m3 (15°C-1013) (3) G31 heating output given for 46.34 MJ/kg 54 RT-SVX20A-E4 Operation Starting the unit in cooling mode Operating pressures Before start-up, ensure that all power cables are tightened. After the unit has operated in cooling mode for a short period of time, install pressure gauges on the gauge ports of the discharge and suction line valves. Verify that the unit airflow rate is adjusted according to the information provided in the "Supply fan adjustment" section of this manual. To start the unit in cooling mode: • Place the zone sensor system switch in the "COOL" position. • Position the cooling setpoint approximately 10° below room temperature and place the fan switch in the "AUTO" or "ON" position. • Turn on unit main power supply. The condenser fan motor, compressor and supply fan motor should operate automatically. There will be a delay of up to 5 minutes before the unit starts in cooling mode. Note: To bypass time delays and verify the operation of this unit from the roof, use the "Test procedure" section in this manual. Check the suction and discharge pressures. Note: Always route refrigerant hoses through the port hole provided and ensure that the compressor access panel is in place. Cooling shutdown To exit the test mode, disconnect unit power for 3-5 seconds and reapply. When running the unit using the zone sensor as the control, position the selector switch to "OFF". There may be a delay of up to 3 minutes before compressors shut down and an additional one minute before the fan shuts down in this setting. Final installation checklist • Are all power cables tightened? Check torque of power cables contact ! • Is the condenser fan and indoor blower operating correctly, i.e. correct rotation and without undue noise? • Are the compressors operating correctly and has the system been checked for leaks? • Have the voltage and running currents been checked to determine if they are within limits? • Have the air discharge grilles been adjusted to balance the system? • Has the ductwork been checked for air leaks and any condensation? • Has the air temperature rise been checked? • Has the indoor airflow been checked and adjusted if necessary? • Has the unit been checked for tubing and sheet metal rattles or any unusual noises? • Are all covers and panels in place and properly fastened? Do not de-energize main power disconnect except when unit is to be serviced. Power is required to keep the compressor crankcase warm and boil off refrigerant in the oil (except on units with Scroll compressors). RT-SVX20A-E4 55 Operation ReliaTel™ is a microelectronic control feature, which provides operating functions that are significantly different from conventional electro-mechanical units. The master module is the ReliaTel™ Refrigeration Module (RTRM). The RTRM provides compressor antishort cycle timing functions through minimum "Off" and "On" timing to increase reliability, performance and to maximize unit efficiency. Upon power initialization, the RTRM performs self-diagnostic checks to insure that all internal controls are functioning. It checks the configuration parameters against the components connected to the system. The LED located on the RTRM module is turned "On" within one second after power-up if all internal operations are okay. 56 Cooling without an Economizer When the system switch is set to the "Cool" position and the zone temperature rises above the cooling setpoint controlband, the RTRM energizes the (K9) relay coil located on the RTRM. When the K9 relay contacts close, the compressor contactor (CC1) coil is energized provided the low pressure control (LPC1) and high pressure control (HPC1) are closed. When the CC1 contacts close, compressor (CPR1) and the outdoor fan motor (ODM) start to maintain the zone temperature to within ± 2 F of the sensor setpoint at the sensed location. If the first stage of cooling can not satisfy the cooling requirement, the RTRM energizes the (K10) relay coil located on the RTRM. When the (K10) relay contacts close, the compressor contactor (CC2) coil is energized provided the low pressure control (LPC2) and high pressure control (HPC2) are closed. When the CC2 contacts close, compressor (CPR2) starts to maintain the zone temperature to within ± 2 F of the sensor setpoint at the sensed location. Evaporator Fan Operation When the fan selection switch is set to the "Auto" position, the RTRM energizes the (K6) relay coil approximately one second after energizing the compressor contactor coil (CC1) in the cooling mode. In heating mode, the RTRM energizes the (K6) relay coil approximately 45 seconds after gas ignition. Closing the K6 contacts on the RTRM energizes the supply fan relay (F) coil to start the supply fan motor (IDM). The RTRM de-energizes the fan relay (F) approximately 60 seconds after the cooling requirement has be satisfied to enhance unit efficiency. When the heating cycle is terminated, the supply fan relay (F) coil is de-energized approximately 90 seconds after the heating requirement. When the fan selection switch is set to the "On" position, the RTRM keeps the supply fan relay coil (F) energized for continuous fan motor operation. When the unit is equipped with the optional clogged filter switch, wired between terminals J7-3 and J7-4 on the ReliaTel™ Options Module (RTOM), the RTRM produces an analog output if the clogged filter switch (CFS) closes for two minutes after a request for fan operation. When the system is connected to a remote panel, the "SERVICE" LED will be turned on when this failure occurs. RT-SVX20A-E4 Operation Low Ambient Operation During low ambient operation, outside air temperature below 13ºC, the RTRM will cycle the compressor and outdoor fan motor "Off" for approximately three minutes after every 10 minutes of accumulated compressor run time. The supply fan motor (IDM) will continue to operate during this evaporator defrost cycle (EDC) and the compressor and outdoor fan will return to normal operation once the defrost cycle has terminated and the compressor "Off" time delay has been satisfied. RT-SVX20A-E4 Cooling with an Economizer The economizer is utilized to control the zone temperature providing the outside air conditions are suitable. Outside air is drawn into the unit through modulating dampers. When cooling is required and economizing is possible, the RTRM sends the cooling request to the unit economizer actuator (ECA) to open the economizer damper. The RTRM tries to cool the zone utilizing the economizer to slightly below the zone temperature setpoint. If the mixed air sensor (MAS) senses that the mixed air temperature is below 53ºF, the damper modulates toward the closed position. If the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is full open, the RTRM energizes the compressor contactor (CC1). If the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open, the RTRM energizes the compressor contactor (CC2). The ECA continues to modulate the economizer damper open/closed to keep the mixed air temperature that is calculated by the RTRM. If economizing is not possible, the ECA drives the damper to the minimum position setpoint when the supply fan relay (F) is energized and allows mechanical cooling operation. When the unit is equipped with the optional fan failure switch, wired between terminals J7-5 and J7-6 on the RTOM, the RTRM will stop all cooling functions and produce an analog output if the fan failure switch (FFS) does not open within 40 seconds after a request for fan operation. When the system is connected to a remote panel, the "SERVICE" LED will flash when this failure occurs. 57 Operation Economizer Set-Up Adjusting the minimum position potentiometer located on the unit economizer Actuator (ECA) sets the required amount of ventilation air. Two of the three methods for determining the suitability of the outside air can be selected utilizing the enthalpy potentiometer on the ECA, as described below: 1. Ambient Temperature controlling the economizing cycle by sensing the outside air dry bulb temperature. The Table below lists the selectable dry bulb values by potentiometer setting. 2. Reference Enthalpy - controlling the economizer cycle by sensing the outdoor air humidity. The Table below lists the selectable enthalpy values by potentiometer setting. If the outside air enthalpy value is less than the selected value, the economizer is allowed to operate. 3. Comparative Enthalpy - By utilizing a humidity sensor and a temperature sensor in both the return air stream and the outdoor air stream, the unit control processor (RTRM) will be able to establish which conditions are best suited for maintaining the zone temperature, i.e. indoor conditions or outdoor conditions. The potentiometer located on the ECA is non-functional when both the temperature and humidity sensors are installed. Table 52 - Potentiometer Setting Potentiometer Dry BuIb Setting (°C) Enthalpy (KJ/kg) A 23* 63 B 21 58 C 19 53 D 17 51 *Factory Setting ReliaTel™ Control Heating Operation When the system switch is set to the "Heat" position and the zone temperature falls below the heating setpoint controlband, a heat cycle is initiated when the RTRM communicates ignition information to the Ignition module (IGN). 58 Ignition Module Two Stage (IGN) runs self-check (including verification that the gas valve is de-energized). (IGN) checks the high-limit switches (TC01 & TC02) for normally closed contacts. With 115 VAC power supplied to the ignition module (IGN), the hot surface ignition probe (IP) is preheated for approximately 45 seconds. The gas valve (GV) is energized for approximately 7 seconds for trial for ignition, to ignite the burner. Once the burner is ignited, the hot surface ignition probe (IP) is deenergized by the ignition module (IGN) and functions as the flame sensing device. If the burner fails to ignite, the ignition module will make two more attempts before locking out. The green LED will indicate a lock out by two fast flashes. An ignition lockout can be reset by: 1. Opening for 3 seconds and closing the main power disconnect switch 2. By switching the "Mode" switch on the zone sensor to "OFF" and then to the desired position 3. Allowing the ignition control module to reset automatically after one hour. RT-SVX20A-E4 Operation Refer to the ignition control module diagnostics section for the LED diagnostic definitions. When the fan selection switch is set to the "Auto" position, the RTRM energizes the supply fan relay (F) coil approximately 30 second after initiating the heating cycle to start the supply fan motor (IDM). The automatic reset high limit (TCO1), located in the bottom right corner of the burner compartment, protects against abnormally high leaving air temperatures. The automatic reset fan fail limit (TCO2), located in the upper middle section of the supply fan board, protects against abnormally high heat buildup which could occur because of extended cycling of the high limit (TCO1) or if the supply fan motor (IDM) fails to operate. Should TCO2 open, the RTRM will energize the supply fan relay (F) in an attempt to start the fan motor. The RTRM signals that a heat failure has occurred by flashing the "Heat" LED on the zone sensor. There is a Green LED located in the Ignition Control Module. The table below lists the diagnostics and the status of the LED during the various operating states. Final installation checklist • Is the condenser fan and indoor blower operating correctly, i.e.: correct rotation and without undue noise? • Are the compressors operating correctly and has the system charge been checked? • Has the gas module been installed as per the procedure in this manual? • Have the voltage and running currents been checked to determine if they are with in limits? • Have the air discharge grilles been adjusted to balance the system? • Has the ductwork been checked for air leaks and any condensation? • Has the heating air temperature rise been checked? • Has the indoor airflow been checked and adjusted if necessary? • Has the unit been checked for tubing and sheet metal rattles orany unusual noises? • Are all covers and panels in placeand properly fastened? To keep the unit operating safely and efficiently, the manufacturer recommends that a qualified service technician check the entire system at least once each year, or more frequently if conditions warrant. Table 53 - LED status Diagnostics 1. Powered but no heat dernand 2. Heat demand without fault 3. No flame detection on ignition - or signal detected and then lost 4. Gas unit incorrectly wired or flame signal detected on a heat demand 5. Internal fault RT-SVX20A-E4 Green LED Red LED Off Off Flash ing Off Off Flashing Steady Flashing Off Steady 59 Maintenance End user routine maintenance To keep the unit operating safely and efficiently, the manufacturer recommends that a qualified service technician check the entire system at least once each year, or more frequently if conditions warrant it. Some of the periodic maintenance functions for the unit can be undertaken by the end user. This includes replacing (disposable) or cleaning (permanent) air filters, cleaning unit cabinet, cleaning the condenser coil, and carrying out a general unit inspection on a regular basis. WARNING! Disconnect the power supply before removing access panels to service the unit. Failure to disconnect power before attempting any servicing can result in severe injury or death. Air filters It is very important for the central duct system air filters to be kept clean. These should be inspected at least once a month when the system is in constant operation (in new buildings, the filters should be checked every week for the first four weeks). If disposable-type filters are used, they should only be replaced with ones of the same type and size. Table 54 - Refrigerant charge Unit model and size Number of circuits Refrigerant charge (kg) (R22/R407C) YSD/YSH 060 1 3.5 YSD/YSH 072 1 3.7 YSD/YSH 090 1 4.5 YSD/YSH 102 2 3.7/2.1 YSD/YSH 120 2 3.5/3.0 Note: Refrigerant charges are given for information only. Check unit nameplate for exact values. 60 RT-SVX20A-E4 Maintenance Note: Do not attempt to clean disposable filters. Permanent filters can be cleaned by washing with a mild detergent and water. Ensure that the filters are thoroughly dry before reinstalling them in the unit (or duct system). Note: Replace permanent filters annually if washing fails to clean them, or they show signs of deterioration. Be sure to use the same type and size as were originally installed. Condenser coil Unfiltered air circulates through the unit's condenser coil and can cause the coil's surface to become clogged with dust, dirt, etc. To clean the coil, brush the coil surface in the direction of the fins with a soft bristled brush. Keep all vegetation away from the condenser coil area. Hot water coil (option) Stop the unit. Do not disconnect the main supply to the unit. This will permit the anti-frost protection to continue to operate, and avoid water to freeze-up in the coil. RT-SVX20A-E4 Service technician maintenance Before the cooling season, your service technician may examine the following areas of your unit: • Filters, for cleaning or replacement • Motors and drives system components • Economizer gaskets, for replacement if necessary • Condenser coils, for cleaning • Safety controls, for mechanical cleaning • Electrical components and wiring, for replacement and tightening of connections as necessary • Condensate drain, for cleaning • Unit duct connections, to ensure they are physically sound and sealed to the unit casing • Unit mounting support, to ensure that it is sound • The unit, to ensure there is no obvious deterioration Before the heating season, your service technician may examine the following areas of your unit: • The unit, to ensure that the condenser coil can receive the required airflow (that the condenser fan grille is not obstructed) • The control panel wiring, to verify that all electrical connections are tight, and that wire insulation is intact • Clean burner area, verify the gas heat system operates properly. 61 Maintenance Troubleshooting The RTRM has the ability to provide the service personnel with some unit diagnostics and system status information. Before turning the main power disconnect switch "Off", follow the steps below to check the ReliaTel™ Refrigeration Module (RTRM). All diagnostics & system status information stored in the RTRM will be lost when the main power is turned "Off". 1. Verify that the Liteport LED on the RTRM is burning continuously. If the LED is lit, go to Step 3. 2. If the LED is not lit, verify that 24 VAC is present between J1-1 and J1-2. If 24 VAC is present, proceed to Step 3. If 24 VAC is not present, check the unit main power supply, check transformer (TNS1). Proceed to Step 3 if necessary. 3. Utilizing "Method 1" or "Method 2" in the system status diagnostic section, check the following: System status, Heating status, Cooling status. If a System failure is indicated, proceed to Step 4. If no failures are indicated, proceed to Step 5. 4. If a System failure is indicated, recheck Steps 1 and 2. If the LED is not lit in Step 1, and 24 VAC is present in Step 2, the RTRM has failed. Replace the RTRM. 62 5. If no failures are indicated, use one of the TEST mode procedures described in the unit "Start-Up" section to start the unit. This procedure will allow you to check all of the RTRM outputs, and all of the external controls (relays, contactors, etc.) that the RTRM outputs energize, for each respective mode. Proceed to Step 6. 6. Step the system through all of the available modes, and verify operation of all outputs, controls, and modes. If a problem in operation is noted in any mode, you may leave the system in that mode for up to one hour while troubleshooting. Refer to the sequence of operations for each mode, to assist in verifying proper operation. Make the necessary repairs and proceed to Steps 7 and 8. 7. If no abnormal operating conditions appear in the test mode, exit the test mode by turning the power "Off" at the main power disconnect switch. 8. Refer to the individual component test procedures if other microelectronic components are suspect. System Status Checkout Procedure "System Status" is checked by using one of the following two methods: Method 1 If the Zone Sensor Module (ZSM) is equipped with a remote panel with LED status indication, you can check the unit within the space. If the ZSM does not have LED's, use Method 2. THS/P03 have the remote panel indication feature. The LED descriptions are listed below: LED 1 (System) "On" during normal operation. "Off" if a system failure occurs or the LED fails. "Flashing" indicates test mode. LED 2 (Heat) "On" when the heat cycle is operating. "Off" when the heat cycle terminates or the LED fails. "Flashing" indicates a heating failure. LED 3 (Cool) "On" when the cooling cycle is operating. "Off" when the cooling cycle terminates or the LED fails. "Flashing" indicates a cooling failure. LED 4 (Service) "On" indicates a clogged filter. "Off" during normal operation. "Flashing" indicates an supply fan failure. RT-SVX20A-E4 Maintenance Below is the complete listing of failure indication causes: System failure Check the voltage between terminals 6 and 9 on J6, it should read approximately 32 VDC. If no voltage is present, a system failure has occurred. Refer to Step 4 in the previous section for the recommended troubleshooting procedure. Heating Failure Verify Heat Failure by Ignition Module (IGN) LED indicator: OFF: No Power or Failure ON: Normal Slow Flash: Normal, Heat Call Fast Flash: Error Code: 1 Flash: Communication Failure 2 Flashes: System Lockout 3 Flashes: Pressure Switch Fail 4 Flashes TC01 or TC02 Open 5 Flashes: Flame w/o Gas Valve 6 Flashes: Flame Rollout Open Cooling Failure 1. Cooling and heating set point (slide pot) on the zone sensor has failed. Refer to the "Zone Sensor Test Procedure" section. 2. Zone temperature thermistor ZTEMP on ZTS failed. Refer to the "Zone Sensor Test Procedure" section. 3. CC1 or CC2 24 VAC control circuit has opened, check CC1 & CC2 coils, and any of the controls below that apply to the unit (HPC1, HPC2). 4. LPC1 has opened during the 3 minute minimum "on time" during 4 consecutive compressor starts, check LPC1 or LPC2 by testing voltage between the J1-8 & J3-2 terminals on the RTRM and ground. If 24 VAC is present, the LPC's has not tripped. If no voltage is present, LPC's has tripped. Service Failure 1. If the supply fan proving switch has closed, the unit will not operate (when connected to RTOM), check the fan motor, belts, and proving switch. 2. Clogged filter switch has closed, check the filters. Simultaneous Heat and Cool Failure 1. Emergency Stop is activated Method 2 The second method for determining system status is done by checking voltage readings at the RTRM (J6). The system indication descriptions and the approximate voltages are listed below. System Failure Measure the voltage between terminals J6-9 & J6-6. Normal Operation = approximately 32 VDC System Failure = less than 1 VDC, approximately 0.75 VDC Test Mode = voltage alternates between 32 VDC & 0.75 VDC Heat Failure Measure the voltage between terminals J6-7 & J6-6. Heat Operating = approximately 32 VDC Heat Off = less than 1 VDC, approximately 0.75 VDC Heating Failure = voltage alternates between 32 VDC & 0.75 VDC Cool Failure Measure the voltage between terminals J6-8 & J6-6. Cool Operating = approximately 32 VDC Cool Off = less than 1 VDC, approximately 0.75 VDC Cooling Failure = voltage alternates between 32 VDC & 0.75 VDC RT-SVX20A-E4 63 Maintenance Service Failure Measure the voltage between terminals J6-10 & J6-6. Clogged Filter = Approximately 32 VDC. Normal = Less than 1 VDC, approximately 0.75 VDC Fan Failure = voltage alternates between 32 VDC & 0.75 VDC. To use LED's for quick status information at the unit, purchase a ZSM and connect wires with alligator clamps to terminals 6 through 10. Connect each respective terminal wire (6 through 10) from the Zone Sensor to the unit J6 terminals 6 through 10. Note: If the system is equipped with a programmable zone sensor THS03, the LED indicators will not function while the ZSM is connected. Resetting Cooling and Ignition Lockouts Zone Temperature Sensor (ZTS) Service Indicator Cooling Failures and Ignition The ZSM SERVICE LED is a generic indicator that will signal the closing of a Normally Open switch at any time, providing the Indoor Motor (IDM) is operating. This indicator is usually used to indicate a clogged filter, or an air side fan failure. Lockouts are reset in an identical manner. Method 1 explains resetting the system from the space, Method 2 explains resetting the system at the unit. Note: Before resetting Cooling Failures and Ignition Lockouts, check the Failure Status Diagnostics by the methods previously explained. Diagnostics will be lost when the power to the unit is disconnected. Method 1 To reset the system from the zone, turn the "Mode" selection switch at the zone sensor to the "Off" position. After approximately 30 seconds, turn the "Mode" selection switch to the desired mode, i.e. Heat, Cool or Auto. Method 2 To reset the system at the unit, cycle the unit power by turning the disconnect switch "Off" and then "On". Lockouts can be cleared through the building management system. Refer to the building management system instructions for more information. 64 The RTRM will ignore the closing of this Normally Open switch for 2 (±1) minutes. This helps prevent nuisance SERVICE LED indications. The exception is the LED will flash 40 seconds after the fan is turned "On" if the Fan Proving Switch is not made. Clogged Filter Switch This LED will remain lit the entire time that the Normally Open switch is closed. The LED will be turned off immediately after resetting the switch (to the Normally Open position), or any time that the IDM is turned "Off". If the switch remains closed, and the IDM is turned "On", the SERVICE LED will be turned "On" again after the 2 (±1) minute ignore delay. This LED being turned "On", will have no other affect on unit operation. It is an indicator only. Fan Failure Switch When the "Fan Failure" switch is wired to the RTOM, the LED will remain flashing the entire time the fan proving switch is closed, indicating a fan failure, and it will shut the unit operations down. RT-SVX20A-E4 Maintenance Zone Temperature Sensor (ZTS) Test Note:These procedures are not for programmable or digital models and are conducted with the Zone Sensor Module electrically removed from the system. Test 1 Zone Temperature Thermistor (ZTEMP) This component is tested by measuring the resistance between terminals 1 and 2 on the Zone Temperature Sensor. RT-SVX20A-E4 Table 55 - Thermistor Resistance / Temperature Chart Temperature/resistance coefficient is negative. Temperature Resistance (°C) (kOhms) -21 103 -15 74.65 -9 54.66 -7 46.94 -4 40.4 -1 34.85 2 30.18 4 26.22 7 22.85 10 19.96 13 17.47 16 15.33 18 13.49 21 11.89 24 10.5 27 9.297 29 8.247 32 7.33 35 6.528 38 5.824 65 Maintenance To Test Humidity Sensors Return Air Humidity Sensor ECA RAH/RAE Outdoor Humidity Sensor ECA OAH/OAE To test this circuit, place a DC milliamp meter in series with either of the leads to the humidity sensor. If the reading is 0ma, polarity may be reversed. Reverse + & - and retest. If the reading does not correspond to the table below, check the output voltage from the ECA with the sensor disconnected. It should be approximately 20VDC. If so, and all connections are intact, replace the sensor. If 20VDC is not present, yet the ECA green LED is on, the ECA module has failed.Humidity sensor accuracy : +/-10% RH. Table 56 - Humidity sensor test 66 RH% DCma RH%D 100% 20.000 52.6 97.7 19.636 51.7 95.5 19.286 50.8 93.4 18.947 Cma RH% DCma 12.414 31.2 9.000 12.273 30.8 8.926 12.135 30.3 8.852 50.0 12.000 29.9 8.780 91.4 18.621 49.2 11.868 29.4 8.710 89.4 18.305 48.4 11.739 29.0 8.640 87.5 18.000 47.6 11.613 28.6 8.571 85.7 17.705 46.8 11.489 28.1 8.504 83.9 17.419 46.1 11.368 27.7 8.438 82.1 17.143 45.3 11.250 27.3 8.372 80.5 16.875 44.6 11.134 26.9 8.308 78.8 16.615 43.9 11.020 26.5 8.244 8.182 77.3 16.364 43.2 10.909 26.1 75.7 16.119 42.5 10.800 25.8 8.120 74.3 15.882 41.8 10.693 25.4 8.060 72.8 15.652 41.2 10.588 25.0 8.000 71.4 15.429 40.5 10.485 24.6 7.941 70.1 15.211 39.9 10.385 24.3 7.833 68.8 15.000 39.3 10.286 23.9 7.826 67.5 14.795 38.7 10.189 23.6 7.770 66.2 14.595 38.1 10.093 23.2 7.714 65.0 14.400 37.5 10.000 22.9 7.660 63.8 14.211 36.9 9.908 22.5 7.606 62.7 14.026 36.4 9.818 22.2 7.552 61.5 13.846 35.8 9.730 21.9 7.500 60.4 13.671 35.3 9.463 21.6 7.448 59.4 13.500 34.7 9.558 21.2 7.397 58.3 13.333 34.2 9.474 20.9 7.347 57.3 13.171 33.7 9.391 20.6 7.297 56.3 13.012 33.2 9.310 20.3 7.248 20.0 7.200 55.4 12.857 32.7 9.231 54.4 12.706 32.2 9.153 53.5 12.558 31.7 9.076 RT-SVX20A-E4 Notes RT-SVX20A-E4 67 Literature Order Number RT-SVX20A-E4 Date 0606 Supersedes RT-SVX20A-E4_1105 Literature Stocking Location Europe www.trane.com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication. For more information, contact your local sales office or e-mail us at comfort@trane.com American Standard Europe BVBA Registered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Create Date : 2006:01:19 13:16:44Z Modify Date : 2006:07:04 11:05:09+03:00 Page Count : 68 Creation Date : 2006:01:19 13:16:44Z Mod Date : 2006:07:04 11:05:09+03:00 Producer : Acrobat Distiller 5.0 (Windows) Metadata Date : 2006:07:04 11:05:09+03:00EXIF Metadata provided by EXIF.tools