Product Catalog

Voyager™ — TS*/YS*/WS*
Packaged Cooling, Gas/Electric & Heat Pump
15–25 Tons, 50 Hz

August 2012

RT-PRC034-EN

Introduction
Packaged Gas/Electric

Packaged Cooling/Heat Pump

Packaged Rooftop Air Conditioners
Through the years, Trane has designed and developed the most complete line of Packaged Rooftop
products available in the market today. Trane was the first to introduce the Micro—microelectronic
unit controls—and has continued to improve and revolutionize this design concept.
The ReliaTel control platform offers the same great features and functionality as the original Micro,
with additional benefits for greater application flexibility.
Voyager continues to provide the highest standards in quality and reliability, comfort, ease of
service, and the performance of Trane light commercial products.
Trane customers demand products that provide exceptional reliability, meet stringent performance
requirements, and are competitively priced. Trane delivers with Voyager.
Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel
controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the
contractor, the engineer, or the owner you can be certain Voyager Products are built to meet your
needs.

Trademarks
and the logo, Frostat, Integrated Comfort, ReliaTel, Tracer, are trademarks of in the United States
and other countries. All trademarks referenced in this document are the trademarks of their
respective owners.

Revision Summary
RT-PRC034-EN (20 August 2012)
•

New configurable model number

•

New optional features: Condensate Overflow Switch, MERV 8 and Filter Removal Tool, Stainless
Steel Drain Pan

•

Updated Features/Benefits, Model Number Description, General Data, Electrical Data,
Mechanical Specifications

© 2012 Trane All rights reserved

RT-PRC034-EN

Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Variety of Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Selection Procedure (SI/IP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SI Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
IP Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

RT-PRC034-EN

3

Features and Benefits
Figure 1.

Factory installed options

J

C

E

F

D
K
B

G
I
M

H

A

A

Foil-Faced Insulation

H Available in R-410A refrigerant

B

Quick Adjust Idler Pulley

I

Hinged Access Doors

C

ReliaTel™ Microprocessor Controls

J

Single Side Service

D Colored and Numbered Wiring

K Smoke Detector

E

Low Ambient Cooling to Zero° F

L

F

High and Low Pressure Switches

M Clogged Filter Switch

G Scroll Compressors (R-410A)

L

N

Fan Failure Switch

N Through-the-Base Gas Piping

Standard Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•

4

2” throwaway filters provided on 15–25 ton units
Anti-Short Cycle Timer
Belt Drive Motors
Colored and Numbered Wiring
Crankcase Heaters
Dedicated Airflow
Discharge Line Thermostat
Easy Access Low Voltage Terminal Board (LTB)
Foil-Faced and Edge Captured Insulation
High Efficiency Drum and Tube Heat Exchanger
High Efficiency Gas Heat with Hot Surface Ignition
High Pressure Cutout
IAQ Sloped Condensate Drain Pan
Liquid Line Refrigerant Drier
Low Ambient Cooling to 0°F
Microchannel Type Condenser Coils (Major Design Sequence F, T and Y Units Only)
Operating Charge of R-410A
Patented Hybrid Condenser Coil for Easy cleaning
Phase Monitor
Provisions for Through-the-Base Gas and Condensate Drain Connections
Quick Access Panels
Quick Adjust Idler Arm Pulley
ReliaTel™ Microprocessor Controls

RT-PRC034-EN

Features and Benefits

•
•
•
•
•

Single Point Power
Single Side Service
Standardized Components
Trane Built Scroll Compressors
U-shaped Airflow Pattern

Options
Factory Installed Options*10
•
•
•
•
•
•
•
•
•
•
•

2" MERV 8 or MERV 13 Filters with Filter Removal Tool
Black Epoxy Pre-Coated Coils4, 11
CO2 Sensor Wiring (Wiring Only)
Complete Coat™ Microchannel Condenser Coil
Condensate Overflow Switch
Hinged Access Doors
Stainless Steel Drain Pan
Stainless Steel Heat Exchanger with 10 year warranty4
Through the Base Electrical Access
Through the Base Electrical with Circuit Breaker8, 9
Through the Base Electrical with Disconnect Switch5, 8, 9

Factory* or Field Installed Options10
Note: *Some Factory Installed Options (FIOPS) available for Downflow Air Discharge units only.
Please verify with ordering system for availability.
Explanation of Notes 1–10 located on page 23 following Model Number Description.
•
•
•
•
•
•
•
•

Clogged Filter/Fan Failure Switch2, 4
Discharge Air Sensing Kit2, 4
Economizer - Downflow
Electric Heaters4, 6, 9
Frostat2, 4
LonTalk® Communications Interface (LCI)4
ReliaTel™ Options Module7
Trane Communications Interface (TCI)1, 4

Field Installed Options
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
RT-PRC034-EN

Barometric Relief
CO2 Sensor
Digital Display Zone Sensor
Economizer - Horizontal
High and Low Static Drive Kits
LP Conversion Kit
Manual Outside Air Damper
Motorized Outside Air Dampers
Oversized Motors
Reference or Comparative Enthalpy3, 4
Remote Potentiometer
Roof Curb (Downflow Only)
Thermostat
Tool-less Hail Guards
Ventilation Override Accessory2
Zone Sensors and Remote Zone Sensors
5

Features and Benefits

Other Benefits
•
•
•
•
•
•
•
•

Cabinet Design Ensures Water Integrity
Ease of Service, Installation and Maintenance
Mixed Model Build Enables “Fastest in the Industry” Ship Cycle Times
Outstanding Airflow Distribution
ReliaTel™ Controls benefits
Rigorous Testing
Unmatched Product Support
Varitrac

Standard Features
Anti-Short Cycle Timer (Standard with ReliaTel™)
Provides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhance
compressor reliability by assuring proper oil return.

Colored And Numbered Wiring
Save time and money tracing wires and diagnosing the unit.

Compressors

Microchannel Condenser Coil
Microchannel Flat Tube

Header
(top removed)

Ribbon Fin

Voyager contains the best
compressor technology
available to achieve the highest
possible performance.
Dual compressors are
outstanding for humidity
control, light load cooling
conditions and system back-up
applications. Dual compressors
are available on all models.

6

Microchannel coils have better heat transfer performance due
to flat streamlined tubes with small ports, and metallurgical
tube-to-fin bond.
Microchannel condenser coil can reduce system refrigerant
charge by up to 50% (potential LEED credit) because of smaller
internal volume, which can lead to better compressor
reliability. Compact all aluminum microchannel coils also help
to reduce the unit weight. All-aluminum construction
improves recyclability. Galvanic corrosion is also minimized
due to all aluminum construction. Strong aluminum brazed
structure provides better fin protection.

RT-PRC034-EN

Features and Benefits

Condenser Coil

Controls—ReliaTel
ReliaTel™ microprocessor controls provide unit control for
heating, cooling and ventilating utilizing input from sensors
that measure indoor and outdoor temperature and other zone
sensors. ReliaTel also provides outputs for building
automation systems and expanded diagnostics.
For a complete list of ReliaTel offerings, refer to “Other
Benefits,” p. 12.

Conversionless Units
Voyager boasts a patentpending 1+1+1 condenser coil,
permanently gapped for easy
cleaning.

The dedicated design units (either downflow or horizontal)
require no panel removal or alteration time to convert in the
field—a major cost savings during installation. Horizontal
units come complete with duct flanges so the contractor
doesn’t have to field fabricate them. These duct flanges are a
time and cost saver.

Crankcase Heaters
These band heaters provide improved compressor reliability by warming the oil to prevent
migration during off-cycles or low ambient conditions. These are standard on all Voyager models.

Discharge Line Thermostat
A bi-metal element discharge line thermostats installed as a standard option on the discharge line
of each system. This standard option provides extra protection to the compressors against high
discharge temperatures in case of loss of charge, extremely high ambient and other conditions
which could drive the discharge temperature higher.

Easy Access Low Voltage Terminal Board

Foil Faced Insulation

Voyager’s Low Voltage Terminal Board is
external to the electrical control cabinet. It is
extremely easy to locate and attach the
thermostat wire and test operation of all unit
functions. This is another cost and time saving
installation feature.

All panels in the evaporator section of the unit
have cleanable foil-faced insulation. All edges
are either captured or sealed to ensure no
insulation fibers get into the airstream.

Heat Exchanger—Drum and Tube
The cabinet (pictured right) features a drum
and tube heat exchanger that is manufactured
using aluminized steel with stainless steel
components for maximum durability.
The requirement for cycle testing of heat
exchangers is 10,000 cycles by ANSI Z21.47.
This is the standard required by both UL and
AGA for cycle test requirements.
RT-PRC034-EN

Forced Combustion Blower
Negative Pressure Gas Valve
Hot Surface Ignitor

7

Features and Benefits

The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times
the current ANSI cycling requirements. The negative pressure gas valve will not allow gas flow
unless the combustion blower is operating. This is one of our unique safety features.
The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner
screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain
than a multiple burner system.
The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a
continuous test to prove the flame. The design is cycle tested at the factory for quality and
reliability. Our gas/electric rooftops exceed all California seasonal efficiency requirements and
perform even better than the California NOx emission requirements.

Low Ambient Cooling
All Voyager microprocessor units have cooling capabilities down to 0°F as standard.

Low Voltage Connections
The wiring of the low voltage connections to the unit
and the zone sensors is as simple as 1-1, 2-2, and 3-3.
This simplified system makes it easy for the installer to
wire.

Motors
All indoor fan motors are belt drive as standard.

Pressure Cutouts
Low and high pressure cutouts are standard on all Voyager models.

Phase Monitor
The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase
reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has
an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are
no field adjustments and the module will automatically reset from a fault condition.

Quick-Access Panels
Remove three or more screws for access to the
standardized internal components and wiring.

Quick-Adjust Slider Plate
With the Quick-Adjust Slider Plate, the belt and
sheaves can be quickly adjusted without moving the
mounted fan motor. The result is a major savings in
time and money.

Single Point Power
A single electrical connection powers the unit.

Single Side Service
Single side service is standard on all units.

Sloped Drain Pans
Every Voyager unit has a non-corrosive, sloped drain pan made of pre-painted steel and standard
on all units.

8

RT-PRC034-EN

Features and Benefits

Standardized Components
Components are placed in the same location on all Voyager units. Familiarize yourself with one
Voyager and you are familiar with every Voyager.
Due to standardized components throughout the Voyager line, contractors/owners can stock fewer
parts.

Through the Base Condensate
Every unit includes provisions for through the base condensate drain connections. This allows the
drain to be connected through the roof curb instead of a roof penetration.

Variety of Options1
Factory Installed Options
Black Epoxy Pre-Coated Coils (W Units Only)
The pre-coated coils are an economical option for protection in mildly corrosive environments.

Circuit Breaker (Required with Through-the-Base Electrical)
This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with
provisions for through the base electrical connections. Available on all models.

CO2 Sensor Wiring
This is the unit wiring for field installed C02 sensors. Factory-installed C02 sensor wiring saves time
and ensures proper unit connections for the field installed C02 sensor kits.

Complete Coat™ Condenser Coil (T/Y Units Only)
The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number
of different types of heat exchangers. The coating is selected to provide excellent resistance and
durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and
corrosive environments. This coating shall be available on microchannel condenser coils.

Condensate Overflow Switch
A condensate overflow switch is available to shut the unit down in the event that the condensate
drain line becomes clogged. This option protects the unit from water overflowing from the drain
pan and entering the base of the units.

Disconnect Switch (Required with
Through-the-Base Electrical)
Factory installed three-pole, molded case, disconnect
switch with provisions for through the base electrical
connections are available. Available on all models.
Codes require a method of assured unit shutdown for
servicing. Field-installed disconnects sometimes
interfere with service access. Factory installation of
unit disconnects reduces costs, assures proper
mounting and provides the opportunity to upgrade to
unit circuit breaker protection.

1

Refer to Model Number Description for option availability.

RT-PRC034-EN

9

Features and Benefits

High Efficiency Filtration
Voyager units offer a variety of high efficiency filtration options. MERV 8 and MERV 13 filters
provide additional filtration beyond the capabilities of typical 2” throwaway filters. Also, when
MERV 8 or MERV 13 filters are ordered, units come equipped with a filter removal tool.

Hinged Access Doors
These doors permit easy access to the filter, fan/heat,
and compressor/control sections. They reduce the
potential roof damage from screws or sharp access
door corners.

Stainless Steel Drain Pan
For excellent corrosion and oxidation resistance, the optional stainless steel drain pan provides a
cleanable surface that complement other IAQ solutions such as high efficiency filtration (MERV 8
or 13), or demand control ventilation (CO2).

Stainless Steel Heat Exchanger
The optional stainless steel heat exchanger is constructed of 304 stainless steel. It is resistant to
corrosion and oxidation and easy to clean. The high strength to weight ratio allows for high
ventilation rates with gas units. With this option, a 10-year stainless steel heat exchanger warranty
is standard.

Through-the-Base Electrical Utility Access
An electrical service entrance shall be provided allowing electrical access for both control and main
power connections inside the curb and through the base of downflow units, and through the front
of horizontal units. Option will allow for field installation of liquid-tight conduit and an external field
installed disconnect switch.
Factory provided through the base openings simplify wiring and piping. Because these utility
openings frequently minimize the number of roof penetrations, the integrity of roofing materials
is enhanced.

Factory or Field Installed Options1
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or
clogged filter indication.
These sensors allow a zone sensor service light or Integrated Comfort System to indicate a dirty
filter or a fan that’s not working. The field installation charges for these valuable feedback devices
often eliminate them from consideration. Factory installation can make such features a good
investment.

Discharge Air Sensing Kit
Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel™
Options Module.

Economizer - Downflow
Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing.
These economizers provide free cooling as the outdoor temperature and/or humidity decreases.
Correctly installed, they offer a valuable energy savings.

1

Refer to Model Number Description for option availability.

10

RT-PRC034-EN

Features and Benefits

Electric Heaters
Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical
option with an Electrical Heater, the heater must be factory installed.

Frostat™
This capillary bulb embedded in the face of the evaporator coil monitors coil temperature to
prevent evaporator icing and protect the compressor. Recommended for applications with low
leaving air temperatures, low airflow and or high latent load applications.

LonTalk® Communications Interface
The LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device
or directly with generic LonTalk Network Building Automation System Controls.

Motors
Factory or field installed oversized motors available for high static applications are available.

Oversized Motors
Factory or field installed oversized motors available for high static applications.

Reference or Comparative Enthalpy
Measures and communicates humidity while maximizing comfort control.

Trane Communication Interface (TCI)
Available factory or field installed. This module when applied with the ReliaTel™ easily interfaces
with Trane’s Integrated Comfort™ System.
*Refer to Model Number Description for option availability.

Field Installed Options1
Barometric Relief
Designed to be used on downflow units, barometric relief is an unpowered means of relieving
excess building pressure.

CO2 Sensor - Demand Control Ventilation (DCV)
Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand
(need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the
building. A CO2 sensor measures the concentration (parts per million, ppm) of CO2 (Carbon
Dioxide) in the air. As the CO2 concentration changes, the outside air damper modulates to meet
the current ventilation needs of the zone. The CO2 sensor kit is available as a field installed
accessory.
Note: Choose factory-installed CO2 sensor wiring option to save time and ensure proper unit
connections for the field installed CO2 sensor kits.

Dampers
0–25 percent manual or 0–50 percent motorized outside air dampers are available.

Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone
sensors. This sensor should be utilized with ReliaTel™ controls.

1

Refer to Model Number Description for option availability.

RT-PRC034-EN

11

Features and Benefits

Economizer - Horizontal
Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing.
These economizers provide free cooling as the outdoor temperature and/or humidity decreases.
Correctly installed, they offer a valuable energy savings.

High Static Drive
Available on many models, this high static drive accessory extends the capability of the standard
motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.

LP Conversion Kit
Provided for field conversion of gas/electric units from Natural gas to Propane.

Remote Potentiometer
When properly installed in the economizer control circuitry, this accessory provides a remote
variable resistance to enable the operator to adjust the minimum damper position.

Roof Curbs
Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb
selection.

Tool-less Hail Guards
Tool-less, hail protection quality coil guards shall be
field-installed for condenser coil protection. This
option protects the condenser coil from vandalism
and/or hail damage.

Ventilation Override Accessory
With the Ventilation Override Accessory installed, the
unit can be set to transition to up to three different preprogrammed sequences for Smoke Purge,
Pressurization, and Exhaust. The transition occurs
when a binary input on the RTOM is closed (shorted).
This would typically be a hard wired relay output from
a smoke detector or fire control panel.

Zone Sensors/Thermostats
Available in programmable, automatic and manual styles.
Note: Zone sensor required for units configured for Single Zone VAV indoor fan system control
to enable Single Zone VAV functionality.

Other Benefits
Airflow Distribution
Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many
cases, improve the comfort through better air distribution. The U-shaped airflow allows for
improved static capabilities.

Cabinet Integrity
For added water integrity, Voyager has a raised 1 1/8” lip around the supply and return of the
downflow units to prevent water from blowing into the ductwork.

12

RT-PRC034-EN

Features and Benefits

Easy to Install, Service and Maintain
Because today’s owners are very cost-conscious when it comes to service and maintenance, the
Trane Voyager was designed with direct input from service contractors. This valuable information
helped to design a product that would get the serviceman off the job quicker and save the owner
money. Voyager does this by offering outstanding standard features enhanced by a variety of
factory and field installed options, multiple control options, rigorously tested proven designs and
superior product and technical support.

Outstanding Airflow Distribution
Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many
cases, improve the comfort through better air distribution.

ReliaTel Controls Benefits
ReliaTel™ controls provide unit control for heating, cooling
and ventilating utilizing input from sensors that measure
outdoor and indoor temperature.

ReliaTel Control Logic Enhances Quality and Reliability
– prevents the unit from short cycling, considerably
improving compressor life.
– ensures that the compressor will run for a specific amount of time which allows oil to return
for better lubrication, enhancing the reliability of the compressor.
Voyager with ReliaTel™ reduces the number of components required to operate the unit, thereby
reducing possibilities for component failure.

ReliaTel Makes Installing and Servicing Easy
ReliaTel™ eliminates the need for field installed antishortcycle timer and time delay relays. ReliaTel™ controls
provide these functions as an integral part of the unit. The
contractor no longer has to purchase these controls as
options and pay to install them. The wiring of the low voltage
connections to the unit and the zone sensors is as easy as 1-1,
2-2, and 3-3. This simplified system makes wiring easier for
the installer.

ReliaTel™

ReliaTel Makes Testing Easy
ReliaTel™ requires no special tools to run the Voyager unit through its paces. Simply place a jumper
between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk
through its operational steps automatically.
The unit automatically returns control to the zone sensor after stepping through the test mode a
single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light
indicates that the controls are functioning properly.
ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™
Systems.
Some zone sensor options have central control panel lights which indicate the mode the unit is in
and possible diagnostic information (dirty filters for example).

Other ReliaTel Benefits
The ReliaTel™ built-in anti-shortcycle timer, time delay relay and minimum “on” time control
functions are factory tested to assure proper operation.

RT-PRC034-EN

13

Features and Benefits

ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters.
Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will
continue to operate at predetermined temperature setpoint.
Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone
sensor(s) work together in harmony to provide much tighter comfort control than conventional
electro-mechanical thermostats.
The same ReliaTel Board fits all Voyager Packaged Gas/Electrics, Cooling, and Heat Pump models.
This provides standardization of parts for contractors. Less money is tied up in inventory with
ReliaTel.

Rigorous Testing
All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. Actual
shipping tests were performed to determine packaging requirements. Units were test shipped
around the country to determine the best packaging. Factory shake and drop tests were used as
part of the package design process to help assure that the unit arrives at the job site in top condition.
Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting
lugs and rails hold up under stress.
The evaporator and condenser coils are leak tested at 225 psig and pressure tested to 450 psig. All
parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected
immediately.
Every unit receives a 100 percent unit run test before leaving the production line to make sure it
lives up to rigorous Trane requirements. Voyager units incorporate either a one piece top or the
Trane-Tite-Top (T3). Each part of the top (either two or three pieces) overlaps in such a way that
water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior
water integrity.

Unmatched Support
Trane Sales Representatives are a Support Group that can assist you with:
• Product
• Application
• Service
• Training
• Special Applications
• Specifications
• Computer Programs and much more

VariTrac—Building Automation
System
When Trane’s changeover VAV System
for light commercial applications is
coupled with Voyager, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.

14

RT-PRC034-EN

Application Considerations
Application of this product should be within the cataloged airflow and cooling considerations.

Barometric Relief
This product line offers an optional barometric relief damper for use in conjunction with
economizer option. This accessory consists of gravity dampers which open with increased
pressure. As the building air pressure increases, the pressure in the unit return air section also
increases, opening the dampers and relieving the conditioned space.
Notes:
•

The effectiveness of barometric relief damper during economizing operation is system related.

•

Pressure drop of the return air system should be considered to control building pressurization.

Black Epoxy Coil
The coils are manufactured with a thermoset, vinyl coating that is bonded to the aluminum fin stock
prior to the fin stamping process. These coils are an economical option for protection in mildly
corrosive environments.
Note: Not to be used where seacoast applications exist.

Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to ensure
adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which
appear inadequate should be reviewed with the local Trane sales personnel.

Complete Coat™ Microchannel Condenser Coil
The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number
of different types of heat exchangers. The coating is selected to provide excellent resistance and
durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salty air and other
corrosive environments. This coating shall be available on microchannel condenser coils.

Condensate Trap
The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the
cooling cycle.

Heating Operation
The heat exchanger is manufactured with aluminized steel. To prevent condensation within the
heat exchanger, do not exceed 50 percent outside air or a minimum mixed air temperature of 40°F.

Optional Stainless Steel Heat Exchanger
The optional stainless steel heat exchanger is manufactured with 304 stainless steel. To prevent
corrosion and prolong heat exchanger reliability, the minimum mixed air temperature allowed
across the heat exchanger is 20°F.

Low Ambient Cooling
The Voyager™ line features, with ReliaTel™ microprocessor controls, low ambient cooling down
to 0°F. The following options need to be included/considered when low ambient applications are
required: continuous fan operation, crankcase heaters (standard), thermal expansion valves,
frostat.
Contact your local Trane Representative for more assistance with low ambient cooling
applications.

Unit Pitch
These units have sloped condensate drain pans. Units must be installed level. Any unit slope must
be toward access side of the unit.

RT-PRC034-EN

15

Selection Procedure (SI/IP)
SI Selection Procedure
Cooling Capacity
Note: Cooling Capacity Procedure is the same for cooling (TS*), gas/electric (YS*) and heat pump
(WS*) units.

Step 1.
Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane
calculation methods or any other standard accepted method.
Factors used in unit selection:
•

Total Cooling Load: 40.0 kW

•

Sensible Cooling Load: 29.0 kW

•

Airflow: 8500 m3/h

•

Electrical Characteristics:
380-415/50/3

•

Summer Design Conditions:

•

Entering Evaporator Coil:
27°C DB, 22°C WB,
35°C Outdoor Ambient

•

External Static Pressure: 127 Pa

•

Rooftop—downflow configuration accessories
• Roof Curb
• Economizer
• Electric Heat

Step 2.
Size the equipment using Table 4, p. 30. Match the cooling loads at design conditions.
Table 4, p. 30 shows that a TSD155F has a gross cooling capacity of 47.5 kW and 35.6 kW sensible
capacity at 8500 m3/h and 35°C DB outdoor ambient with 27°C DB, 19°C WB air entering the
evaporator.

To Find Capacity at Intermediate Conditions Not in the Table:
When the design conditions are between two numbers that are in the capacity table, interpolation
is required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.

16

RT-PRC034-EN

Selection Procedure (SI/IP)

Step 3.
In order to select the correct unit which meets the building’s requirements, the fan motor heat must
be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is
dependent on the effort by the motor, airflow and static pressure. To determine the total unit static
pressure (see Table 48, p. 56 for Static Pressure Drops Through Accessories):
External Static Duct System

127 Pa

Standard Filter 25mm

19 Pa

Economizer (100% OA)

12 Pa

Electric Heater Size 27 kW

11Pa

Total Static Pressure

169 Pa

Notes:
1. Reference “Heating Capacity” section on
this page for determination of heater size.
2. No additional static add for gas/heat
exchanger.

Note: The Evaporator Fan Performance (see Table 20, p. 44) has already accounted for the
pressure drop for standard filters and wet coils (see note below Table 20, p. 44). Therefore,
the actual total static pressure is 169 - 19 (from Table 48, p. 56) = 150 Pa.
With 8500 m3/h and 150 Pa. Table 20, p. 44 shows 1.12 kW for this unit. The formula below can be
used to calculate Fan Motor Heat:
Fan Motor Heat = 1.23 * Fan Power (kW)
1.23 * 1.12 kW = 1.3776 kW
Now subtract the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity =
47.5 - 1.37 = 46.12
Net Sensible Cooling Capacity =
35.6 - 1.37 = 34.22

Step 4.
If the performance will not meet the required load of the building, total or sensible cooling load,
try a selection at the next higher size unit.

Heating Capacity
Note: Heating capacity procedures DIFFER for cooling (TS*), gas/electric (YS*) and heat pump
(WS*) units.

Step 1.
Calculate the building heating load using the Trane calculation form or other standard accepted
method.

Step 2.
Size the system heating capacity to match the calculated building heating load. The following are
building heating requirements:

TS* cooling units:
•

380 volt/three-phase Power Supply

•

Total heating load of 20.5 kW

•

Airflow of 8500 m3/h

The electric heat accessory capacities are listed in Table 52, p. 62. From the table, a 26.9 kW heater
at 415 volts is selected. In order to determine capacity at 380 volts, the heater voltage correction
RT-PRC034-EN

17

Selection Procedure (SI/IP)

factor from Table 53, p. 62 must be used. Therefore, 26.9 kW x 0.84 (voltage correction factor) =
22.59 kW.

YS* gas/electric:
The fuel used is natural gas with a total heating load of 30 kW. Table 2, p. 26 shows 61.1 kW and
85.5 kW input models. The output capacities of these furnaces are 49.6 kW and 69.4 kW,
respectively. The low heat model with 49.6 kW output best matches the building requirements.

WS* heat pumps:
Total heating load of 30.0 kW. Outdoor ambient (Winter) of -9°C DB and indoor return of 21°C DB
and an airflow of 8500 m3/h. The unit is using a 380 V power supply. Use the integrated portion of
Table 16, p. 42 for the WC*155 to determine capacity at winter design conditions. The mechanical
heating portion of the heat pump will provide 20.9 kW.

Step 3.
Note: This step does not apply to TS* and YS* units.

WS* heat pumps:
Because 22.1 kW is less than the building's required heating capacity at winter design condition,
a supplementary heater must be selected.
30.0 - 20.9 = 9.1 kW
From Table 62, p. 64, a 13.4 kW heater at 415 V is selected. To find the capacity at 380 V, the heater
voltage correction factor from Table 63, p. 64 must be used. Therefore, 13.4 kW x 0.84 (voltage
correction factor) = 11.26 kW. This heater will be adequate to do the job.

Air Delivery Selection
Note: Air Deliver procedures is the same for cooling (TS*), gas/electric (YS*) and heat pump
(WS*) units.
External static pressure drop through the air distribution system has been calculated to be 150 Pa.
From Table 48, p. 56, static pressure drop through the economizer is 12 Pa and the 27 kW heater
is 12 Pa (127 + 12 + 12). Enter (Table 20, p. 44) for a TSD155F at 8500 m3/h and 150 Pa static
pressure.
The standard motor at 566 rpm will give the desired airflow at a rated kW of 1.12.

18

RT-PRC034-EN

Selection Procedure (SI/IP)

IP Selection Procedure
Cooling Capacity
Note: Cooling Capacity Procedure is the same for cooling (TS*), gas/electric (YS*) and heat pump
(WS*) units.

Step 1.
Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane
calculation methods or any other standard accepted method.
Factors used in unit selection:
• Total Cooling Load: 140 MBh
• Sensible Cooling Load: 100 MBh
• Airflow: 5000 cfm
• Electrical Characteristics:
380-415/50/3
• Summer Design conditions:
• Entering Evaporator Coil:
80 DB, 73 WB
• Outdoor Ambient: 95 DB
• External Static pressure:
0.50 in. wg
• Rooftop - downflow configuration
• Accessories
• Roof Curb
• Economizer
• Electric Heat

Step 2.
As a starting point, a rough determination must be made of the size of the unit. The final selection
will be made after examining the performance at the given conditions. Divide the total cooling load
by nominal Btu/h per ton (12 MBh per ton); then round up to the nearest unit size.
140 MBh / 12 MBh = 11.6 tons

Step 3.
Table 5, p. 31 shows that a TSD155F has a gross cooling capacity of 162.2 MBh and 121.4 MBh
sensible capacity at 5000 cfm and 95 DB outdoor ambient with 80 DB, 73 WB air entering the
evaporator.

To Find Capacity at Intermediate Conditions Not in the Table:
When the design conditions are between two numbers that are in the capacity table, interpolation
is required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.

RT-PRC034-EN

19

Selection Procedure (SI/IP)

Step 4.
In order to select the correct unit which meets the building’s requirements, the fan motor heat must
be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is
dependent on the effort by the motor, cfm and static pressure. To determine the total unit static
pressure you add the external static pressure to the additional static related by the added features
(see Table 49, p. 57 for Static Pressure Drops Through Accessories):
External Static Duct System

0.50 wg

Standard Filter 1in.

0.08 wg

Economizer (100% OA)

0.05 wg

Electric Heater Size 27 kW

0.05 wg

Total Static Pressure

0.68 wg

Notes:
1. Reference “Heating Capacity” section on
this page for determination of heater size.
2. No additional static add for gas/heat
exchanger.

Note: The Evaporator Fan Performance Table 21, p. 44 has already accounted for the pressure
drop for standard filters and wet coils (see note below Table 21, p. 44). Therefore, the actual
total static pressure is 0.68 - 0.08 (from Table 49, p. 57) = 0.60 wg.
With 5000 cfm and 0.60 wg, Table 21, p. 44 shows 1.50 bhp for this unit. The formula below can be
used to calculate Fan Motor Heat:
Fan Motor Heat = 3.15 * Fan bhp
3.15 * 1.50 = 4.725 MBh
Now subtract the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity =
162.2 - 4.725 = 157.475 MBh
Net Sensible Cooling Capacity =
121.4 - 4.725 = 116.675 MBh

Step 5.
If the performance will not meet the required load of the building, total or sensible cooling load,
try a selection at the next higher size unit.

20

RT-PRC034-EN

Selection Procedure (SI/IP)

Heating Capacity
Note: Heating capacity procedures DIFFER for cooling (TS*), gas/electric (YS*) and heat pump
(WS*) units.

Step 1.
Calculate the building heating load using the Trane calculation form or other standard accepted
method.

Step 2.
Size the system heating capacity to match the calculated building heating load. The following are
building heating requirements:

TS* cooling units:
380 volt/3 phase Power Supply
Total heating load of 75.0 MBh
5000 cfm
The electric heat accessory capacities are listed in Table 52, p. 62. From the table, a 26.9 kW heater
will deliver 91.73 MBh at 415 volts. In order to determine capacity at 380 volts, the heater voltage
correction factor from Table 53, p. 62 must be used. Therefore, 91.73 MBh x 0.84 (voltage correction
factor) = 77.05 MBh.

YS* gas/electric:
Fuel natural gas and a total heating load of 115 MBh. Table 2, p. 26 shows 208.3 MBh and 291.7 MBh
input models. The output capacities of these furnaces are 169.2 MBh and 236.7 MBh respectively.
The low heat model with 169.2 MBh output best matches the building requirements.

WS* heat pumps:
Total heating load of 100 MBh. Outdoor ambient (Winter) of 17 DB and Indoor Return of 70 DB and
an airflow of 5000 cfm. The unit is using a 380 V power supply. Use the integrated portion of
Table 17, p. 42 for the WC*155 to determine capacity at winter design conditions. The mechanical
heating portion of the heat pump will provide 71.2 MBh.

Step 3.
Note: This step does not apply to TS* and YS* units.

WS* heat pumps:
Because 71.2 MBh is less than the building’s required heating capacity at winter design conditions,
a supplementary heater must be selected.
100 MBh - 71.2 MBh = 28.8 MBh
From Table 62, p. 64, a 13.4 kW heater at 415 V is selected. To find the capacity at 380 V, the heater
voltage correction factor from Table 63, p. 64 must be used. Therefore, 13.4 kW x 0.84 (voltage
correction factor) = 11.26 kW. This heater will be adequate to do the job. 38.3 MBh.

Air Delivery Selection
Note: Air Delivery procedures is the same for cooling (TS*), gas/electric (YS*) and heat pump
(WS*) units.
External static pressure drop through the air distribution system has been calculated to by
0.60 inches of water. From Table 49, p. 57, static pressure drop through the economizer is 0.05 and
the 26.9 kW heater is 0.05 inches of water (0.50 + 0.05 + 0.05). Enter (Table 21, p. 44) for a TSD155
at 5000 cfm and 0.60 static pressure. The standard motor at 566 rpm will give the desired airflow
at a rated bhp of 1.50.

RT-PRC034-EN

21

Model Number Descriptions
T

S

D

1

5

1

2

3

4

5

Digit 1 — Unit Type
T =
Y =
W =

Packaged Cooling, Electric Heat
Packaged Gas/Electric
Packaged Heat Pump, Electric
Heat

Digit 2 — Efficiency
S

=

Standard

Digit 3 — Airflow Configuration
D
H

=
=

Downflow
Horizontal

Digit 4, 5, 6 — Nominal Gross
Cooling Capacity (MBh)

5

F

D

R

6

7

8

9

=

Without Communications
Options

6

=

7
8

=
=

Building Automation Control
Network Communications
Interface

9
A

=
=

D

=

E

=

F

=

Digit 16 — Hinged Service
Access / Filters

=
=

380-415/50/3
200/50/311

Digit 9 — Unit Controls
R

=

Reliatel

Digit 10 — Heating Capacity
Note: (Applicable to Digit 1 T/W models
only)
0 = No Heat
G = 18 kW Electric Heat
K = 27 kW Electric Heat
N = 36 kW Electric Heat
P = 54 kW Electric Heat
R = 72 kW Electric Heat
Note: (Applicable to Digit 1 Y models
only)
H = Gas Heat - High
L = Gas Heat - Low
X = Gas Heat - SS Ht Ex - Low
Z = Gas Heat - SS Ht Ex - High

Digit 11 — Minor Design
Sequence
Digit 12, 13 — Service Sequence
Digit 14 — Fresh Air Selection
0
A
B
D

=
=
=
=

F

=

H

=

22

No Fresh Air
Manual Damper
Motorized Damper
Econ Dry Bulb w/ Barometric
Relief
Econ Reference Enthaply w/
Barometric Relief
Econ Comparative Enthaply w/
Barometric Relief

12

0

Standard Motor
Oversized Motor
High Efficiency Motor
Single Zone Variable Air Volume
Standard Motor
Multi-Speed Standard Motor
Single Zone Variable Air Volume
Oversized Motor
Multi-Speed Oversized Motor
Single Zone Variable Air Volume
Standard Motor w/ Shaft Ground
Ring
Multi-Speed Standard Motor w/
Shaft Ground Ring
Single Zone Variable Air Volume
Oversized Motor w/ Shaft Ground
Ring
Multi-Speed Oversized Motor w/
Shaft Ground Ring

Digit 7 — Major Design
Sequence

D
T

11

=
=
=
=

=

Digit 8 — Voltage Selection

10

0
1
3
6

C

Round Tube Plate Fin Type
Condenser Coils
Microchannel Type Condenser
Coils

A

Digit 21 — Communications
Options

=

15 Tons Standard Efficiency
17½ Tons Standard Efficiency
20 Tons Standard Efficiency
25 Tons Standard Efficiency

A

Digit 15 — Supply Fan/Drive
Type/Motor

B

155 =
175 =
200 =
250 =

0

0
A

=
=

Standard Panels/Standard Filters
Hinged Access/Standard Filters

Digit 17 — Condenser Coil
Protection

Digit 22 — Refrigeration System
Option
0

=

0
1

=
=

0
A
B
C

=
=
=
=

D

=

5

=

6

=

Digit 18 — Through The Base
Provisions

7

=

0
A
B
C
D

A

=

B

=

C

=

D

=

E

=

Digit 20 — Convenience Outlet
Option

F

=

0
A
B

G

=

H

=

4
5

=
=

=
=
=
=
=

Standard Coil
Standard Coil With Hail Guard
Black Epoxy Pre-Coated Coil
Black Epoxy Pre-Coated Coil With
Hail guard
CompleteCoat™Condenser Coil
CompleteCoat™Condenser Coil
with Hail Guard

No Through The Base Provisions
Through The Base Electric
Through The Base Gas
Through The Base Electric/Gas
Through The Base Access

Digit 19 — Disconnect Switch/
Circuit Breaker
0
1

=
=

2

=

=
=
=

No Disconnect/circuit break
Unit Mounted Non-Fused
Disconnect Switch
Unit Mounted Circuit Breaker

Without Convenience Outlet
Unpowered Convenience Outlet
Powered Convenience Outlet

Without Smoke Detector
Return Air Smoke Detector
Supply Air Smoke Detector
Return/Supply Air Smoke
Detector
Plenum Smoke Detector

Digit 25 — System Monitoring
Controls
=
=
=
=
=

=
=
=
=

Without Refrigeration Controls
Frostat

Digit 24 — Smoke Detector

0
1
2
3
4

0
1
2
3

Standard refrigeration system

Digit 23 — Refrigeration
Controls

No Monitoring Controls
Clogged Filter Switch
Fan Failure Switch
Discharge Air Sensing
Clogged Filter Switch and Fan
Failure
Clogged Switch and Discharge Air
Sensing
Fan Failure Switch and Discharge
Air Sensing
Clogged Filter Switch, Fan Failure
Switch and Discharge Air Sensing
Condensate Drain Pan Overflow
Switch
Clogged Filter Switch and
Condensate Drain Pan Overflow
Switch
Fan Failure Switch and
Condensate Drain Pan Overflow
Switch
Discharge Air Sensing and
Condensate Drain Pan Overflow
Switch
Clogged Filter Switch, Fan Failure
Switch and Condensate Drain Pan
Overflow Switch
Clogged Filter Switch, Discharge
Air Sensing Tube and Condensate
Drain Pan Overflow Switch
Fan Failure Switch, Discharge Air
Sensing Tube and Condensate
Drain Pan Overflow Switch
Clogged Filter Switch, Fan Failure
Switch, Discharge Air Sensing
and Condensate Drain Pan
Overflow Switch
RT-PRC034-EN

Model Number Descriptions

Digit 26 - System Monitoring
Controls
0
A

No Monitoring Controls
Demand Control Ventilation (CO2)12

Digit 27 - Unit Hardware
Enhancements
0
1

No Enhancements
Stainless Steel Drain Pan

Options
Factory Installed
•
•
•
•
•
•
•
•
•
•
•

•

Black Epoxy Pre-Coated Coils4
CO2 Sensor Wiring (Wiring Only)
Complete Coat Microchannel Coil
Condensate Overflow Switch
Hinged Access Doors
MERV 8 or 13 with Filter Removal Tool
Stainless Steel Drain Pan
Stainless Steel Heat Exchanger with
10 year warranty4
Through the Base Electrical Access
Through the Base Electrical with
Circuit Breaker8, 9
Through the Base Electrical with
Disconnect Switch5, 8, 9

Clogged Filter/Fan Failure Switch2, 4
Discharge Air Sensing Kit2, 4
Economizer - Downflow
Electric Heaters4, 6, 9
Frostat2, 4
LonTalk® Communications Interface
(LCI)4
ReliaTel Options Module7

Field Installed Options
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•

3. Requires Economizer.
4. Available factory installed on
downflow AND horizontal units.
Verify with ordering system.
5. Cannot be fused.
6. Must be factory installed when
using Through-the-Base Options.
7.

Options*10

Factory* or Field Installed
Options10
•
•
•
•
•
•

2. Requires ReliaTel options module.

Barometric Relief
CO2 Sensing
Digital Display Zone Sensor
Dual Thermistor Remote Zone Sensor
Economizer - Horizontal
High and Low Static Drive Kits
LP Conversion Kit
Manual Outside Air Damper
Motorized Outside Air Dampers
Oversized Motors
Reference or Comparative
Enthalpy3, 4
Remote Potentiometer
Roof Curb (Downflow Only)
Thermostat
Tool-less Hail Guards
Trane Communications Interface
(TCI)1, 4
Ventilation Override Accessory2
Zone and Remote Zone Sensors

ReliaTel Options Module is
required when ordering the
following accessories (Factory- or
Field-Installed Options): Clogged
Filter Switch, Fan Fail Switch,
Discharge Air Sensing Kit, Frostat,
Ventilation Override.

8. Unit mounted disconnect and
circuit breakers are mutually
exclusive of each other.
9. Through-the-base electrical
option or Horizontal Side Access
must be ordered with either unit
mounted disconnect or circuit
breaker. When adding heat, must
order Trane Electric Heat.
10. All Factory Installed Options are
Built-to-Order. Check order
services for estimated production
cycle.
11. Available on Heat Pump (W) units
only.
12. Demand Control Ventilation
Option includes wiring only. The
C02 sensor is a field-installed only
option.
Note: *Some Factory Installed Options
(FIOPS) available for Downflow Air
Discharge units only. Please verify
with ordering system for
availability.

Model Number Notes
1. TCI is for use with non-VariTrac
systems and VariTrac systems.

RT-PRC034-EN

23

General Data
Table 1.

TS* general data
15–25 Tons Downflow and Horizontal Units
Model

TS*155FD

TS*175FD

TS*200FD

TS*250FD

ARI Gross Capacity kW (MBh)

44.8 (153)

51.2 (174.8)

62.7 (214.1)

68.3 (233.0)

COP/EER(b)

3.47 / 11.8

3.51 / 12.0

3.14 / 10.7

3.10 / 10.8

7480 (4400)

9000 (5300)

10400 (6125)

12240 (7200)

44.0 (150)

49.8 (170.0)

61.0 (208.2)

66.0 (225.3)

Cooling Performance(a)

Nominal Airflow - m3/h (cfm)
ARI Airflow - m3/h (cfm)
ARI Net Capacity - kW (MBh)
System Power - kW

13

14.6

20.0

21.6

12.9

14.5

19.6

21.0

2/Scroll

2/Scroll

2/Scroll

2/Scroll

Compressor
No./Type

Sound Rating

dB(c)

Outdoor Coil - Type
Coil Width mm (in.)
Face Area -

m2

(sq. ft.)

Rows/Fins per inch

Indoor Coil - Type
Tube Size OD - in.
Face Area - m2 (sq. ft.)

9.0

9.2

9.2

9.2

Microchannel

Microchannel

Microchannel

Microchannel

25.4 (1)

25.4 (1)

25.4 (1)

25.4 (1)

3.27 (35.2)

3.27 (35.2)

3.27 (35.2)

3.27 (35.2)

1 / 20

1 / 20

1 / 20

1 / 20

Hi-Performance

Hi-Performance

Hi-Performance

Hi-Performance

0.3125

0.3125

0.3125

0.3125

(2.42) 26

(2.42) 26

(2.42) 26

(2.42) 26

Rows/Fins per inch

3/ 15

4 / 15

4 / 15

4 / 15

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

Propeller

Propeller

Propeller

Propeller

2 / 660 (26)

2 / 660 (26)

2 / 660 (26)

2 / 710(28)

Drive Type/No. Speeds

Direct / 1

Direct / 1

Direct / 1

Direct / 1

m3/h

15630 (9200)

18860 (11100)

18000 (10600)

19880 (11700)

2 / 250(0.33)

2 / 560(0.75)

2 / 560(0.75)

2 / 560(0.75)

925

950

950

950

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

Drain Connection No./Size - in.

Outdoor Fan - Type
No. Used/Diameter - mm (in.)

Airflow -

(cfm)

No. Motors/Power - W (HP)
Motor RPM

Indoor Fan - Type
No. Used
Diameter x Width - mm (in.)
Drive Type/No. Speeds
No. Motors
Standard/Oversized Motor Power —
W (HP)
Motor RPM - Standard/Oversized

24

1

1

1

1

457x457 (18x18)

457x457 (18x18)

457x457 (18x18)

457x457 (18x18)

Belt / 1

Belt / 1

Belt / 1

Belt / 1

1

1

1

1

1500(2.0) / 2200(3.0)

2200(3.0) / 3700(5.0)

2200(3.0) / 3700(5.0)

3700(5.0) / N/A

1450 / 2850

2850 / 2920

2850 / 2920

2920/N/A

RT-PRC034-EN

General Data
TS* General Data
Table 1.

TS* general data (continued)
15–25 Tons Downflow and Horizontal Units
Model

TS*155FD

TS*175FD

TS*200FD

TS*250FD

Throwaway

Throwaway

Throwaway

Throwaway

(4)508x508x50
(4)508x635x50

(4)508x508x50
(4)508x635x50

(4)508x508x50
(4)508x635x50

(4)508x508x50
(4)508x635x50

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(8)508x635x50

(8)508x635x50

(8)508x635x50

(8)508x635x50

(8)20x25x2

(8)20x25x2

(8)20x25x2

(8)20x25x2

5.2/2.7 (11.4/6)

6.5/3.4 (14.4/7.6)

6.1/3.2 (13.5/7)

4.8/4.8 (10.5/10.5)

Filters—Type/Furnished
Type Furnished
Number Size Recommended
Downflow—mm
Downflow—in
Horizontal—mm
Horizontal—in

Refrigerant Charge
R-410A kg (lb)(d)

(a) Cooling Performance is rated at 35°C (95°F) ambient, 26.7°C (80°F) entering dry bulb, 19.4°C (67°F) entering wet bulb. Gross capacity does not include
the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation ±20% of nominal airflow.
Ratings shown are tested and certified in accordance with ARI Standard 210/240 or 340/360 certification program.
(b) EER is rated at ARI conditions and in accordance with DOE test procedures.
(c) Sound Ratings shown are tested in accordance with ARI Standard 270 or 370.
(d) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC034-EN

25

General Data
YS* General Data
Table 2.

YS* general data
15–25 Tons Downflow and Horizontal Units
Model

YS*155FD

YS*175FD

YS*200FD

YS*250FD

ARI Gross Capacity—kw (MBh))

44.8 (153)

51.2 (174.8)

62.7 (214.1)

68.3 (233.0)

COP/EER(b)

3.47 / 11.8

3.51 / 12.0

3.14 / 10.7

3.10 / 10.8

7480 (4400)

5300

6125

7175

44.0 (150)

49.8 (170.0)

61.0 (208.2)

66.0 (225.3)

13

14.6

20.0

21.6

Cooling Performance(a)

Nominal Airflow—m3/h (cfm)
ARI Airflow—m3/h (cfm)
System Power—kW

Heating Performance(c)
Heating Models

Low

Heating Input—(MBh)

High

Low

High

Low

High

Low

High

61.1(208.3) 85.5(291.7) 61.1(208.3) 85.5(291.7) 61.1(208.3) 97.7(333.3) 61.1(208.3) 97.7(333.3)

1st Stage (2 Stage Only)—(MBh) 42.7(145.8) 61.1(208.3) 42.7(145.8) 61.1(208.3) 42.7(145.8) 73.3(250.0) 42.7(145.8) 73.3(250.0)
Heating Output—(MBh)

49.6(169.2) 69.4(236.7) 49.6(169.2) 69.4(236.7) 49.6(169.2) 79.1(270.0) 49.6(169.2) 79.1(270.0)

1st Stage (2 Stage Only)—(MBh) 34.7(118.3) 49.6(169.2) 34.7(118.3) 49.6(169.2) 34.7(118.3) 59.3(202.5) 34.7(118.3) 59.3(202.5)
Steady State Efficiency %

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

1

1

1

1

1

1

1

1

1/2

3/4

1/2

3/4

1/2

3/4

1/2

3/4

Numbers of Gas Heat
Stages
Number of Gas Burners
Gas Connection Pipe Size—in.

Compressor
Number/Type

Sound Rating

dB(d)

2/Scroll

2/Scroll

2/Scroll

2/Scroll

9.0

9.2

9.2

9.2

Microchannel

Microchannel

Microchannel

Microchannel

Outdoor Coil
Type
Coil Width—mm (in.)

25.4 (1)

25.4 (1)

25.4 (1)

25.4 (1)

3.27 (35.2)

3.27 (35.2)

3.27 (35.2)

3.27 (35.2)

1 / 20

1 / 20

1 / 20

1 / 20

Hi-Performance

Hi-Performance

Hi-Performance

Hi-Performance

0.3125

0.3125

0.3125

0.3125

(2.42) 26

(2.42) 26

(2.42) 26

(2.42) 26

Rows/Fins per inch

3/15

4/15

4/15

4/15

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

Propeller

Propeller

Propeller

Propeller

2/660 (26)

2/660 (26)

2/660 (26)

2/710 (28)

Direct/1

Direct/1

Direct/1

Direct/1

15630 (9200)

18860 (11100)

18000 (10600)

19880 (11700)

2/250(0.33)

2/560(0.75)

2/560(0.75)

2/560(0.75)

925

950

950

950

Face Area—m3 (sq. ft.)
Rows / Fins per inch

Indoor Coil
Type
Tube Size (in.) ID
Face Area—m3 (sq. ft.)

Drain Connection Number/
Size—in.

Outdoor Fan
Type
Number Used/Diameter—mm
(in.)
Drive Type/No. Speeds
Airflow—m3/h

(CFM)

Number Motors/W (HP)
Motor RPM

26

RT-PRC034-EN

General Data
YS* General Data
Table 2.

YS* general data (continued)
15–25 Tons Downflow and Horizontal Units
Model

YS*155FD

YS*175FD

YS*200FD

YS*250FD

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

1

1

1

1

457x457 (18x18)

457x457 (18x18)

457x457 (18x18)

457x457 (18x18)

Belt / 1

Belt / 1

Belt / 1

Belt / 1

Indoor Fan
Type
Number Used
Diameter x Width—mm (in.)
Drive Type/No. Speeds
Number Motors

1

1

1

1

Motor W (HP)
(Standard/Oversized)

1500 (2.0) / 2200 (3.0)

2200 (3.0) / 3700 (5.0)

2200 (3.0) / 3700 (5.0)

3700 (5.0) / N/A

Motor RPM
(Standard/Oversized)

1450 / 2850

2850 / 2920

2850 / 2920

2920/N/A

Throwaway

Throwaway

Throwaway

Throwaway

(4)508x508x50

(4)508x508x50

(4)508x508x50

(4)508x508x50

Filters
Type Furnished
Number Size Recommended
Downflow—mm
Downflow—in.
Horizontal—mm
Horizontal—in.

(4)508x635x50

(4)508x635x50

(4)508x635x50

(4)508x635x50

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(8)508x635x50

(8)508x635x50

(8)508x635x50

(8)508x635x50

(8)20x25x2

(8)20x25x2

(8)20x25x2

(8)20x25x2

5.2/2.7 (11.4/6)

6.5/3.4 (14.4/7.6)

6.1/3.2 (13.5/7)

4.8/4.8 (10.5/10.5)

Refrigerant Charge
R-410A kg (lb)(e)

(a) Cooling Performance is rated at 35°C (95°F) ambient, 26.7°C (80°F) entering dry bulb, 19.4°C (67°F) entering wet bulb. Gross capacity does not include
the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation ±20% of nominal airflow.
Ratings shown are tested and certified in accordance with ARI Standard 210/240 or 340/360 certification program.
(b) EER is rated at ARI conditions and in accordance with DOE test procedures.
(c) Heating performance unit settings and data were established under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 610 meters (2000 ft.). For elevations above 610 meters (2000 ft.), ratings should be reduced at the rate of 4%
for each 305 meters (1000 ft.) above sea level.
(d) Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC034-EN

27

General Data
WS* General Data

Table 3.

WS* general data
15–20 Tons Downflow and Horizontal Units
Model

WS*155ED, ET

WS*200ED, ET

44.1 (150.7)

62.9 (214.8)

Cooling Performance(a)
ARI Gross Capacity—kW (MBh)
COP/EER(b)

3.3 (11.3)

2.9 (9.9)

8500 (5000)

(11890) 7000

ARI Airflow—m3/h (cfm)

8500 (5000)

(11890) 7000

ARI Net Capacity—kW (MBh)

43.2 (147.5)

61.0 (208.5)

13.1

21.0

41.8 (142.7)

61.4 (209.6)

3.8

3.6

11.0

17.2

2 / Scrolls

2 / Scrolls

9.0

9.2

Type

Hi-Performance

Hi-Performance

Refrigerant Control

Expansion Valve

Expansion Valve

Tube Size (in.) OD

0.3125

0.3125

3.3 (35.2)

4.0 (42.53)

3 / 16

3 / 16

Hi-Performance

Hi-Performance

Nominal Airflow—m3/h (cfm)

System Power—kW

Heating Performance(a)
High Temperature Capacity—kW (MBh)
COP
System Power—kW

Compressor
Number/Type

Sound Rating

dB(c)

Outdoor Coil

Face Area-m3 (sq. ft.)
Rows / Fins per inch

Indoor Coil
Type
Tube Size (in.) ID
Face Area-m3 (sq. ft.)
Rows / Fins per inch
Refrigerant Control
Drain Connection Number/Size (in.)

0.3125

0.3125

2.4 (26)

2.9 (31.42)

4 / 15

4 / 15

Short Orifice

Short Orifice

1/1.00 NPT

1/1.00 NPT

Outdoor Fan
Type
Number Used/Diameter—mm (in.)
Drive Type/No. Speeds
Airflow—m3/h

(CFM)

Number Motors/W (HP)
Motor RPM

28

Propeller

Propeller

2 / 660 (26)

2 / 710(28)

Direct / 1

Direct / 1

15300 (9000)

20900 (12300)

2 / 250 (0.33)

2 / 560 (0.75)

925

950

RT-PRC034-EN

General Data
WS* General Data
Table 3.

WS* general data (continued)
15–20 Tons Downflow and Horizontal Units
Model

WS*155ED, ET

WS*200ED, ET

FC Centrifugal

FC Centrifugal

Indoor Fan
Type
Number Used
Diameter x Width—mm (in.)
Drive Type/No. Speeds
Number Motors

1

1

457x457 (18x18)

457x457 (18x18)

Belt / 1

Belt / 1

1

1

1500 (2.0) / 2200 (3.0)

2200 (3.0) / 3700 (5.0)

1450 / 2850

2850 / 2920

Throwaway

Throwaway

Downflow—mm

(4)508x508x50

(8)20x20x2 (4)20x16x2

Downflow

(4)508x635x50

(8)508x508x50

Motor W (HP) (Standard/Oversized)
Motor RPM (Standard/Oversized)

Filters
Type Furnished
Number Size Recommended

Downflow—in
Horizontal—mm
Horizontal—in

(4)20x20x2 (4)20x25x2

(4)508x406x50

(8)508x635x50

(12)508x508x50

(8)20x25x2

(12)20x20x2

6.6 / 6.4 (14.5 / 14.2)

9.0 / 8.2 (19.75 / 18)

Refrigerant Charge
R-410A kg (lb)(d)

(a) Cooling Performance is rated at 35°C (95°F) ambient, 26.7°C (80°F) entering dry bulb, 19.4°C (67°F) entering wet bulb. Heating Performance is rated
at 20°C (68°F) ambient, 8.3°C (47°F) entering dry bulb, 6.1°C (43°F) entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal airflow. Rated in accordance with ARI
Standard 210/240 or 340/360.
(b) EER is rated at ARI conditions and in accordance with DOE test procedures.
(c) Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(d) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC034-EN

29

Performance Data
Table 4.

Gross cooling capacities T/YS*155FD (SI)
Ambient Temperature (°C)
30

Enter
16
Airflow DB
m3/h (°C) TGC SHC

7140

7820

8500

9180

35

40

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

42.3

34.8

46.1

25.1

51.3

17.9

38.7

32.6

42.6

23.7

47.7

16.7

34.7

30.2

38.6

22.0

43.8

15.3

27

44.2

41.1

47.1

33.6

51.3

20.4

41.0

38.8

43.9

32.1

48.1

19.6

37.4

36.3

40.3

30.2

44.5

18.5
27.7

30

46.3

46.3

48.2

41.0

51.4

29.9

43.4

43.4

45.4

39.3

48.6

28.9

40.1

40.1

42.1

37.3

45.3

33

48.5

48.5

49.4

47.2

51.7

38.3

45.9

45.9

46.9

45.4

49.2

37.2

43.0

43.0

44.0

43.3

46.3

35.8

24

43.5

36.1

47.0

26.4

51.9

18.2

39.9

34.0

43.5

25.0

48.4

16.9

35.9

31.6

39.6

23.3

44.5

15.6
19.8

27

45.5

42.6

48.1

35.0

52.0

21.7

42.3

40.3

44.9

33.5

48.9

20.9

38.7

37.8

41.3

31.6

45.3

30

47.7

47.7

49.3

42.4

52.2

31.3

44.8

44.8

46.5

40.8

49.4

30.3

41.5

41.5

43.2

38.8

46.2

29.1

33

49.9

49.9

50.6

48.7

52.6

39.7

47.4

47.4

48.1

46.9

50.1

38.6

44.7

44.5

45.2

44.8

47.2

37.2

24

44.5

37.4

47.8

27.6

52.4

18.3

41.0

35.3

44.3

26.2

48.9

17.1

37.0

32.9

40.4

24.5

45.0

15.8

27

46.6

43.9

49.0

36.3

52.6

22.9

43.4

41.7

45.8

34.7

49.4

22.1

39.8

39.1

42.2

32.9

45.9

21.0

30

48.9

48.9

50.2

43.8

52.9

32.5

46.0

46.0

47.4

42.1

50.1

31.6

42.7

42.7

44.2

40.1

46.9

30.3

33

51.2

51.2

51.6

50.1

53.3

41.0

48.7

48.7

49.1

48.3

50.8

40.0

46.2

46.2

46.2

46.2

48.0

38.6

24

45.4

38.6

48.4

28.7

52.7

18.4

41.8

36.4

44.9

27.3

49.2

17.2

37.9

34.0

41.0

25.6

45.4

15.9

27

47.6

45.2

49.7

37.4

53.0

24.0

44.4

42.9

46.5

35.9

49.9

23.1

40.8

40.4

42.9

34.1

46.3

22.0

30

49.9

49.9

51.0

45.0

53.4

33.7

47.1

47.1

48.2

43.4

50.6

32.7

43.8

43.8

45.0

41.4

47.4

31.5

33

52.3

52.3

52.4

51.5

53.9

42.3

49.5

49.5

50.0

49.7

51.4

41.2

47.1

47.1

47.1

47.1

48.6

39.8

Ambient Temperature (°C)
45
Enter
16
Airflow DB
m3/h (°C) TGC SHC

7140

7820

8500

9180

49

52

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

30.3

27.5

34.3

20.0

39.5

13.8

28.0

26.0

31.9

18.9

37.1

13.0

25.5

24.5

29.5

17.7

34.7

12.1

27

33.3

33.3

36.3

28.1

40.5

17.1

31.1

31.1

34.1

26.9

38.4

16.2

28.9

28.9

31.8

25.7

36.1

15.3
24.3

30

36.4

36.4

38.4

35.1

41.7

26.1

34.4

34.4

36.4

33.8

39.7

25.3

32.3

32.3

34.3

32.5

37.6

33

40.6

40.6

40.6

40.6

43.0

34.1

38.8

38.8

38.8

38.8

41.1

33.1

36.9

36.9

36.9

36.9

39.2

32.1

24

31.6

28.9

35.2

21.3

40.2

14.1

29.2

27.4

32.9

20.2

37.8

13.2

26.8

25.9

30.5

19.0

35.4

12.4
16.6

27

34.6

34.6

37.3

29.5

41.3

18.4

32.5

32.5

35.2

28.3

39.2

17.5

30.2

30.2

32.9

27.1

36.9

30

37.8

37.8

39.6

36.5

42.6

27.5

35.8

35.8

37.6

35.3

40.6

26.6

33.7

33.7

35.5

34.0

38.5

25.7

33

41.9

41.9

41.9

41.9

43.9

35.5

40.0

40.0

40.0

40.0

42.1

34.6

38.1

38.1

38.1

38.1

40.2

33.6

24

32.6

30.2

36.0

22.5

40.7

14.2

30.3

28.7

33.7

21.4

38.4

13.4

27.9

27.2

31.3

20.2

36.0

12.6

27

35.8

35.8

38.2

30.8

41.9

19.6

33.6

33.6

36.1

29.6

39.8

18.7

31.4

31.4

33.8

28.4

37.5

17.8

30

39.1

39.1

40.5

37.9

43.3

28.8

37.1

37.1

38.5

36.7

41.3

27.9

35.0

35.0

36.5

35.3

39.2

27.0

33

42.9

42.9

42.9

42.9

44.7

36.9

41.1

41.1

41.1

41.1

42.9

36.0

39.2

39.2

39.2

39.2

41.0

34.9

24

33.6

31.3

36.7

23.6

41.1

14.4

31.2

29.9

34.4

22.5

38.8

13.6

28.8

28.3

31.9

21.3

36.4

12.7

27

36.8

36.8

39.0

32.0

42.4

20.6

34.7

34.7

36.8

30.8

40.3

19.8

32.4

32.4

34.6

29.5

38.0

18.9

30

40.2

40.2

41.3

39.2

43.8

30.0

38.2

38.2

39.4

37.9

41.8

29.1

36.1

36.1

37.3

36.6

39.8

28.2

33

43.8

43.8

43.8

43.8

45.3

38.2

42.0

42.0

42.0

42.0

43.5

37.2

40.1

40.1

40.1

40.1

41.6

36.2

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

30

RT-PRC034-EN

Performance Data
Gross Cooling Capacities

Table 5.

Gross cooling capacities T/YS*155FD (IP)
Ambient Temperature (°F)
85

Enter
61
Airflow DB
CFM
(°F) TGC SHC
75
4200

4600

5000

5400

5800

95

105

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

144.2 118.6 157.4 85.8 174.9 61.2 132.1 111.3 145.3 81.0 162.9 57.0 118.5 103.0 131.8 75.1 149.4 52.3

80

151.0 140.2 160.8 114.7 175.0 69.7 139.9 132.5 149.9 109.5 164.2 66.9 127.5 123.8 137.5 103.2 151.9 63.0

85

158.0 158.0 164.5 139.8 175.4 102.1 148.2 148.2 154.8 134.1 165.8 98.8 136.9 136.9 143.6 127.3 154.7 94.5

90

165.4 165.4 168.6 161.0 176.2 130.5 156.7 156.7 160.1 154.8 167.8 126.8 146.6 146.6 150.1 147.6 157.9 122.0

75

148.3 123.2 160.5 90.2 177.1 62.0 136.2 116.0 148.5 85.4 165.1 57.8 122.6 107.8 135.0 79.6 151.8 53.1

80

155.3 145.2 164.2 119.4 177.5 74.1 144.3 137.5 153.4 114.1 166.7 71.3 132.0 128.8 141.1 107.9 154.5 67.4

85

162.6 162.6 168.2 144.7 178.2 106.7 152.8 152.8 158.6 139.0 168.6 103.4 141.6 141.6 147.5 132.3 157.6 99.2

90

170.3 170.3 172.6 166.2 179.3 135.4 161.7 161.7 164.1 160.0 170.9 131.7 152.6 151.7 154.2 152.9 161.0 127.0

75

151.8 127.6 163.1 94.2 178.7 62.6 139.8 120.4 151.1 89.4 166.8 58.4 126.3 112.1 137.7 83.6 153.5 53.7

80

159.1 149.8 167.1 123.7 179.4 78.1 148.2 142.1 156.3 118.5 168.7 75.3 135.9 133.5 144.1 112.2 156.6 71.5

85

166.7 166.7 171.4 149.3 180.4 111.0 157.0 157.0 161.8 143.7 170.9 107.8 145.8 145.8 150.7 137.0 159.9 103.5

90

174.6 174.6 176.0 171.1 181.8 140.0 166.1 166.1 167.6 165.0 173.4 136.3 157.7 157.7 157.7 157.7 163.7 131.6

75

154.8 131.5 165.1 97.9 179.8 62.9 142.8 124.3 153.2 93.1 168.0 58.8 129.4 116.1 139.9 87.3 154.8 54.2

80

162.3 154.1 169.4 127.7 180.8 81.7 151.5 146.4 158.7 122.5 170.2 79.0 139.3 137.8 146.5 116.2 158.1 75.2

85

170.2 170.2 174.0 153.6 182.1 115.0 160.6 160.6 164.4 147.9 172.6 111.7 149.5 149.5 153.4 141.3 161.7 107.5

90

178.4 178.4 178.9 175.6 183.8 144.3 168.8 168.8 170.5 169.5 175.4 140.6 160.7 160.7 160.7 160.7 165.7 135.9

75

157.2 135.2 166.6 101.2 180.4 63.1 145.2 128.0 154.8 96.4 168.6 59.0 131.9 119.8 141.5 90.7 155.4 54.4

80

165.0 158.0 171.2 131.3 181.7 85.1 154.3 150.3 160.5 126.1 171.1 82.3 142.1 141.7 148.4 119.9 159.0 78.6

85

173.2 173.2 176.0 157.5 183.2 118.5 163.6 163.6 166.5 151.8 173.8 115.3 152.6 152.6 155.6 145.2 163.0 111.1

90

179.5 179.5 181.3 179.8 185.2 148.2 172.9 172.9 172.9 172.9 176.9 144.5 163.2 163.2 163.2 163.2 167.3 139.8

Ambient Temperature (°F)
115
Enter
61
Airflow DB
CFM (°F) TGC SHC

4200

4600

5000

5400

5800

120

125

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

61

67
SHC

TGC

61

67

SHC

SHC

TGC

SHC

75

103.5 93.8 116.9 68.3 134.6 47.1

95.4

88.8 108.9 64.5 126.7 44.3

87.0

83.5 100.5 60.5 118.4 41.4

80

113.7 113.7 123.8 95.9 138.3 58.2 106.2 106.2 116.4 91.9 130.9 55.4

98.4

98.4 108.6 87.6 123.2 52.3

85

124.2 124.2 131.1 119.6 142.2 89.2 117.4 117.4 124.3 115.4 135.5 86.2 110.2 110.2 117.1 110.9 128.3 82.9

90

138.7 138.7 138.7 138.7 146.5 116.3 132.4 132.4 132.4 132.4 140.4 113.0 125.9 125.9 125.9 125.9 133.8 109.5
93.5 112.2 69.0 129.1 45.2

91.3

TGC

SHC

73

TGC

99.7

TGC

73

SHC

TGC

SHC

75

107.7 98.5 120.2 72.7 137.0 47.9

80

118.2 118.2 127.4 100.6 140.9 62.6 110.8 110.8 120.0 96.6 133.6 59.8 103.0 103.0 112.3 92.4 125.9 56.8

88.3 103.9 64.9 120.8 42.3

85

129.1 129.1 134.9 124.6 145.2 93.9 122.2 122.2 128.2 120.4 138.4 90.9 115.0 115.0 121.0 115.9 131.4 87.6

90

142.8 142.8 142.8 142.8 149.8 121.3 136.6 136.6 136.6 136.6 143.6 118.0 130.1 130.1 130.1 130.1 137.1 114.6

75

111.4 102.9 122.9 76.8 138.8 48.6 103.4 97.9 115.0 73.1 130.9 45.8

80

122.2 122.2 130.4 105.0 143.0 66.7 114.8 114.8 123.1 101.0 135.7 63.9 107.1 107.1 115.4 96.8 128.1 60.9

95.1

92.7 106.7 69.0 122.7 42.9

85

133.3 133.3 138.3 129.3 147.6 98.3 126.5 126.5 131.5 125.1 140.9 95.3 119.4 119.4 124.4 120.6 133.8 92.0

90

146.4 146.4 146.4 146.4 152.5 125.9 140.3 140.3 140.3 140.3 146.3 122.7 133.8 133.8 133.8 133.8 139.9 119.2

75

114.5 106.9 125.1 80.6 140.1 49.0 106.6 102.0 117.2 76.8 132.3 46.3

80

125.6 125.6 132.9 109.0 144.6 70.4 118.2 118.2 125.6 105.0 137.3 67.7 110.5 110.5 118.0 100.8 129.7 64.6

98.3

96.7 109.0 72.8 124.1 43.4

85

137.0 137.0 141.0 133.6 149.4 102.3 130.2 130.2 134.3 129.4 142.8 99.3 123.1 123.1 127.2 124.9 135.7 96.0

90

149.5 149.5 149.5 149.5 154.6 130.2 143.4 143.4 143.4 143.4 148.5 127.0 136.9 136.9 136.9 136.9 142.1 123.6

75

117.1 110.6 126.8 84.0 140.8 49.3 109.2 105.6 118.9 80.2 133.0 46.6 100.9 100.4 110.7 76.2 124.8 43.7

80

128.5 128.5 134.9 112.7 145.6 73.8 121.1 121.1 127.6 108.7 138.4 71.0 113.5 113.5 120.0 104.5 130.8 68.0

85

140.2 140.2 143.3 137.6 150.7 105.9 133.4 133.4 136.6 133.4 144.1 103.0 128.2 128.2 129.5 128.9 137.1 99.7

90

152.0 152.0 152.0 152.0 156.2 134.2 145.9 145.9 145.9 145.9 150.1 131.0 139.4 139.4 139.4 139.4 143.7 127.5

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

RT-PRC034-EN

31

Performance Data
Gross Cooling Capacities

Table 6.

Gross cooling capacities T/YS*175FD (SI)
Ambient Temperature (°C)
30

Enter
16
Airflow DB
m3/h (°C) TGC SHC

7985

8750

9515

10280

11045

35

40

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

46.9

39.4

52.1

29.4

59.4

20.8

42.1

36.6

47.2

27.5

54.5

19.1

36.7

33.4

41.8

25.2

49.0

17.1

27

49.2

46.4

53.1

38.6

59.1

24.9

45.1

43.8

49.0

36.8

54.9

24.0

40.4

40.4

44.2

34.5

50.1

22.7

30

51.8

51.8

54.3

46.4

59.0

34.9

48.4

48.4

50.9

44.8

55.5

34.1

44.4

44.4

46.9

42.6

51.4

32.8

33

54.5

54.5

55.7

53.0

59.0

43.6

51.8

51.8

53.0

51.4

56.3

42.9

49.2

48.6

49.7

49.3

52.9

41.7

24

48.2

40.9

53.2

30.9

60.3

21.1

43.4

38.1

48.3

29.0

55.4

19.4

38.0

34.9

42.9

26.7

49.9

17.5

27

50.6

48.0

54.2

40.1

60.0

26.4

46.5

45.3

50.1

38.3

55.8

25.5

41.8

41.8

45.4

36.1

51.1

24.2

30

53.1

53.1

55.5

48.0

59.9

36.4

49.8

49.8

52.1

46.3

56.5

35.7

45.8

45.8

48.1

44.2

52.4

34.4

33

55.9

55.9

57.0

54.7

60.1

45.2

53.3

53.3

54.3

53.1

57.3

44.5

50.5

50.5

51.0

51.0

54.0

43.3

24

49.4

42.4

54.2

32.4

61.1

21.4

44.6

39.6

49.4

30.5

56.2

19.7

39.3

36.3

44.0

28.1

50.8

17.8

27

51.8

49.5

55.3

41.6

60.9

27.9

47.8

46.8

51.2

39.9

56.7

27.1

43.1

43.1

46.5

37.6

52.0

25.7

30

54.4

54.4

56.6

49.6

60.8

38.0

51.1

51.1

53.2

47.9

57.4

37.2

47.2

47.2

49.3

45.7

53.4

35.9

33

57.3

57.3

58.1

56.3

61.0

46.8

54.7

54.7

55.5

54.7

58.3

46.1

52.2

52.2

52.2

52.2

55.0

44.9

24

50.5

43.8

55.1

33.8

61.8

21.6

45.8

41.1

50.3

32.0

57.0

19.9

40.4

37.8

45.0

29.6

51.5

18.0

27

52.9

51.0

56.2

43.1

61.6

29.4

49.0

48.4

52.2

41.4

57.5

28.6

44.4

44.4

47.6

39.1

52.8

27.2

30

55.6

55.6

57.6

51.2

61.7

39.6

52.4

52.4

54.3

49.5

58.3

38.8

48.5

48.5

50.4

47.3

54.3

37.5

33

58.5

58.5

59.2

57.9

61.9

48.4

56.0

56.0

56.6

56.3

59.2

47.7

53.4

53.4

53.4

53.4

56.0

46.5

24

51.5

45.3

55.9

35.3

62.4

21.8

46.8

42.5

51.2

33.4

57.6

20.2

41.5

39.2

45.9

31.0

52.2

18.3

27

54.0

52.5

57.1

44.6

62.3

30.9

50.1

49.9

53.1

42.8

58.2

30.0

45.5

45.5

48.5

40.6

53.6

28.6

30

56.8

56.8

58.5

52.7

62.4

41.1

53.5

53.5

55.3

51.0

59.0

40.3

49.7

49.7

51.4

48.8

55.1

39.0

33

59.7

59.7

60.2

59.5

62.7

50.0

57.6

57.6

57.6

57.6

60.1

49.3

54.4

54.4

54.4

54.4

56.8

48.1

Ambient Temperature (°C)
45
Enter
16
Airflow DB
m3/h (°C) TGC SHC

7985

8750

9515

10280

11045

49

52

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

30.7

29.6

35.7

22.4

42.8

15.0

27.5

27.5

32.5

20.7

39.6

13.8

24.1

24.1

29.1

19.0

36.1

12.6

27

35.2

35.2

38.9

31.8

44.7

20.8

32.3

32.3

36.0

30.2

41.8

19.7

29.3

29.3

32.9

28.5

38.7

18.4

30

39.8

39.8

42.2

39.9

46.7

31.0

37.3

37.3

39.7

38.4

44.1

29.9

36.6

34.7

37.0

36.7

41.4

28.7

33

45.8

45.8

45.8

45.8

48.9

40.0

43.6

43.6

43.6

43.6

46.7

38.9

41.3

41.3

41.3

41.3

44.4

37.8

24

32.1

31.1

36.9

23.8

43.8

15.3

28.8

28.8

33.7

22.2

40.6

14.2

25.5

25.5

30.3

20.5

37.1

13.0

27

36.6

36.6

40.1

33.3

45.7

22.3

33.7

33.7

37.2

31.7

42.8

21.2

30.7

30.7

34.2

30.0

39.8

19.9

30

41.3

41.3

43.5

41.5

47.8

32.6

38.8

38.8

41.0

39.9

45.2

31.5

38.0

38.0

38.3

38.3

42.6

30.3

33

47.1

47.1

47.1

47.1

50.1

41.6

45.0

45.0

45.0

45.0

47.9

40.5

42.7

42.7

42.7

42.7

45.6

39.4

24

33.3

32.6

38.0

25.3

44.7

15.7

30.2

30.2

34.8

23.6

41.5

14.5

26.8

26.8

31.4

21.9

38.1

13.3

27

37.9

37.9

41.3

34.8

46.7

23.8

35.1

35.1

38.4

33.2

43.8

22.7

32.1

32.1

35.4

31.5

40.7

21.4

30

42.7

42.7

44.7

43.0

48.8

34.1

40.2

40.2

42.2

41.5

46.3

33.1

39.6

39.6

39.6

39.6

43.6

31.8

33

48.4

48.4

48.4

48.4

51.1

43.2

46.2

46.2

46.2

46.2

49.0

42.1

44.0

44.0

44.0

44.0

46.7

41.0

24

34.6

34.0

39.0

26.7

45.5

15.9

31.4

31.4

35.8

25.1

42.3

14.8

28.1

28.1

32.5

23.3

38.9

13.6

27

39.2

39.2

42.3

36.3

47.5

25.3

36.4

36.4

39.5

34.7

44.7

24.2

33.4

33.4

36.5

33.0

41.6

22.9

30

44.0

44.0

45.8

44.6

49.7

35.7

42.9

41.6

43.4

43.0

47.2

34.6

40.7

40.7

40.7

40.7

44.6

33.4

33

49.6

49.6

49.6

49.6

52.1

44.8

47.4

47.4

47.4

47.4

50.0

43.7

45.2

45.2

45.2

45.2

47.7

42.6

24

35.7

35.4

39.9

28.1

46.3

16.2

32.5

32.5

36.8

26.5

43.1

15.1

29.2

29.2

33.4

24.7

39.7

13.9

27

40.4

40.4

43.3

37.8

48.3

26.8

37.6

37.6

40.5

36.2

45.5

25.6

34.6

34.6

37.5

34.4

42.5

24.4

30

45.3

45.3

46.9

46.1

50.6

37.2

44.4

44.4

44.4

44.4

48.1

36.1

41.8

41.8

41.8

41.8

45.4

34.9

33

50.7

50.7

50.7

50.7

53.0

46.4

48.5

48.5

48.5

48.5

50.9

45.3

46.3

46.3

46.3

46.3

48.6

44.1

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

32

RT-PRC034-EN

Performance Data
Gross Cooling Capacities

Table 7.

Gross cooling capacities T/YS*175FD (IP)
Ambient Temperature (°F)
85

Enter
61
Airflow DB
CFM
(°F) TGC SHC
75
4700

5150

5600

6050

6500

95

105

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

160.0 134.4 177.8 100.3 202.7 70.9 143.6 125.0 161.2 94.0 185.9 65.1 125.1 113.9 142.5 86.0 167.0 58.5

80

168.0 158.5 181.2 131.5 201.6 84.8 154.0 149.4 167.1 125.6 187.2 81.9 138.0 138.0 150.9 117.8 170.8 77.3

85

176.6 176.6 185.3 158.4 201.2 118.9 165.0 165.0 173.6 152.7 189.3 116.3 151.5 151.5 159.9 145.3 175.3 111.9

90

185.9 185.9 190.1 180.9 201.4 148.6 176.8 176.8 180.8 175.5 192.0 146.3 167.8 165.7 169.5 168.3 180.5 142.2

75

164.3 139.5 181.4 105.3 205.6 72.0 148.0 130.1 165.0 99.0 189.0 66.1 129.7 119.0 146.4 91.0 170.2 59.6

80

172.5 163.7 185.1 136.8 204.7 90.1 158.6 154.6 171.0 130.8 190.5 87.1 142.7 142.7 154.9 123.0 174.2 82.5

85

181.3 181.3 189.4 163.9 204.5 124.3 169.9 169.9 177.8 158.1 192.7 121.7 156.4 156.4 164.1 150.6 178.9 117.3

90

190.7 190.7 194.3 186.5 205.0 154.2 181.8 181.8 185.2 181.1 195.6 151.8 172.2 172.2 174.0 173.9 184.3 147.7

75

168.4 144.5 184.8 110.4 208.3 72.9 152.2 135.1 168.4 104.1 191.8 67.1 134.0 124.0 150.1 96.0 173.2 60.6

80

176.7 169.0 188.6 142.0 207.6 95.2 163.0 159.8 174.7 136.0 193.5 92.3 147.2 147.2 158.7 128.2 177.4 87.6

85

185.7 185.7 193.1 169.2 207.6 129.7 174.4 174.4 181.6 163.5 195.9 127.0 161.1 161.1 168.1 156.0 182.2 122.6

90

195.3 195.3 198.2 192.1 208.2 159.7 186.5 186.5 189.2 186.6 199.0 157.3 178.2 178.2 178.2 178.2 187.8 153.2

75

172.1 149.5 187.9 115.4 210.7 73.8 156.1 140.1 171.7 109.0 194.3 68.0 138.0 128.9 153.4 100.9 175.8 61.5

80

180.6 174.2 191.9 147.2 210.2 100.4 167.0 165.0 178.1 141.1 196.2 97.4 151.4 151.4 162.3 133.3 180.2 92.7

85

189.8 189.8 196.6 174.6 210.4 135.0 178.7 178.7 185.2 168.8 198.8 132.3 165.5 165.5 171.8 161.3 185.3 127.9

90

199.7 199.7 201.9 197.6 211.2 165.2 191.1 191.1 193.0 192.1 202.1 162.8 182.0 182.0 182.0 182.0 191.0 158.7

75

175.6 154.5 190.7 120.3 212.9 74.5 159.7 145.0 174.6 113.9 196.6 68.8 141.7 133.8 156.4 105.8 178.2 62.4

80

184.3 179.3 194.9 152.3 212.5 105.5 170.8 170.1 181.2 146.2 198.7 102.5 155.3 155.3 165.5 138.4 182.8 97.7

85

193.7 193.7 199.7 179.9 212.9 140.3 182.6 182.6 188.5 174.1 201.5 137.5 169.6 169.6 175.2 166.5 188.0 133.1

90

203.7 203.7 205.3 203.1 213.9 170.7 196.5 196.5 196.5 196.5 204.9 168.2 185.7 185.7 185.7 185.7 193.9 164.1

Ambient Temperature (°F)
115
Enter
61
Airflow DB
CFM (°F) TGC SHC

4700

5150

5600

6050

6500

120

125

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

61

67
SHC

TGC

61

67

73

TGC

SHC

SHC

TGC

SHC

TGC

SHC

75

104.7 101.1 121.9 76.3 146.2 51.2

93.7

93.7 110.8 70.8 135.0 47.2

82.2

82.2

99.2

64.8 123.3 43.1

80

120.0 120.0 132.6 108.4 152.4 70.9 110.2 110.2 122.8 103.0 142.5 67.1

99.9

99.9 112.4 97.2 132.0 62.9

85

135.9 135.9 144.1 136.1 159.3 105.9 127.3 127.3 135.4 130.9 150.6 102.2 125.0 118.3 126.3 125.2 141.4 98.1

90

156.2 156.2 156.2 156.2 166.9 136.4 148.8 148.8 148.8 148.8 159.4 132.8 140.8 140.8 140.8 140.8 151.4 128.9
98.4

TGC

73

SHC

98.4 114.9 75.7 138.4 48.4

87.0

TGC

SHC

75

109.4 106.1 125.9 81.3 149.5 52.3

80

124.8 124.8 136.8 113.6 156.0 76.1 115.1 115.1 127.0 108.2 146.0 72.3 104.9 104.9 116.7 102.4 135.6 68.0

87.0 103.3 69.8 126.7 44.4

85

141.0 141.0 148.5 141.4 163.1 111.2 132.5 132.5 139.9 136.2 154.4 107.5 129.5 129.5 130.8 130.5 145.2 103.4

90

160.8 160.8 160.8 160.8 170.9 141.9 153.4 153.4 153.4 153.4 163.4 138.3 145.5 145.5 145.5 145.5 155.4 134.4

75

113.8 111.1 129.6 86.2 152.6 53.4 102.9 102.9 118.7 80.7 141.5 49.5

80

129.4 129.4 140.8 118.7 159.2 81.2 119.8 119.8 131.0 113.3 149.4 77.4 109.6 109.6 120.8 107.5 139.0 73.1

91.5

91.5 107.2 74.7 129.9 45.5

85

145.7 145.7 152.6 146.8 166.5 116.5 137.3 137.3 144.1 141.5 157.9 112.8 135.0 135.0 135.0 135.0 148.8 108.6

90

165.1 165.1 165.1 165.1 174.5 147.4 157.8 157.8 157.8 157.8 167.1 143.8 150.0 150.0 150.0 150.0 159.2 139.8

75

117.9 116.0 133.1 91.1 155.3 54.4 107.1 107.1 122.2 85.6 144.3 50.5

80

133.7 133.7 144.4 123.8 162.2 86.3 124.1 124.1 134.7 118.4 152.4 82.4 114.0 114.0 124.5 112.5 142.1 78.1

95.8

95.8 110.7 79.6 132.8 46.5

85

150.2 150.2 156.4 152.0 169.7 121.7 146.5 141.9 147.9 146.7 161.1 118.0 139.0 139.0 139.0 139.0 152.0 113.9

90

169.1 169.1 169.1 169.1 177.8 152.8 161.8 161.8 161.8 161.8 170.5 149.2 154.1 154.1 154.1 154.1 162.6 145.2

75

121.7 120.9 136.3 96.0 157.8 55.2 111.0 111.0 125.4 90.4 146.9 51.4

80

137.8 137.8 147.8 128.8 164.9 91.3 128.2 128.2 138.1 123.4 155.1 87.4 118.2 118.2 128.0 117.5 144.9 83.1

99.7

99.7 114.0 84.4 135.4 47.4

85

154.5 154.5 160.0 157.2 172.5 126.9 151.6 151.6 151.6 151.6 164.0 123.2 142.6 142.6 142.6 142.6 155.0 119.0

90

172.8 172.8 172.8 172.8 180.9 158.2 165.6 165.6 165.6 165.6 173.6 154.6 157.9 157.9 157.9 157.9 165.8 150.5

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

RT-PRC034-EN

33

Performance Data
Gross Cooling Capacities

Table 8.

Gross cooling capacities T/YS*200FD (SI)
Ambient Temperature (°C)
30

Enter
16
Airflow DB
m3/h (°C) TGC SHC

9005

9940

10875

11810

12745

35

40

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

57.5

47.4

63.3

35.1

71.6

25.1

52.6

44.6

58.4

33.3

66.6

23.3

47.6

41.6

53.2

31.2

61.3

21.5

27

60.1

55.6

64.7

46.1

71.7

29.7

55.9

52.8

60.3

44.2

67.2

28.8

51.3

49.7

55.7

42.0

62.5

27.6

30

62.7

62.1

65.9

55.3

71.6

41.7

58.9

58.9

62.1

53.4

67.7

40.7

55.0

55.0

58.0

51.2

63.5

39.5

33

65.1

65.1

67.1

62.9

71.4

52.0

61.9

61.9

63.8

60.9

68.0

51.0

58.5

58.5

60.2

58.7

64.4

49.7

24

59.7

49.7

65.2

37.1

73.1

25.6

54.8

46.9

60.2

35.3

68.1

23.8

49.7

43.9

55.0

33.2

62.8

22.0

27

62.4

58.0

66.6

48.2

73.2

31.5

58.0

55.2

62.1

46.3

68.7

30.6

53.5

52.1

57.5

44.1

64.0

29.4

30

64.9

64.6

67.8

57.5

73.2

43.6

61.1

61.1

63.9

55.6

69.2

42.6

57.1

57.1

59.8

53.4

65.0

41.4

33

67.4

67.4

69.0

65.2

73.0

54.0

64.1

64.1

65.6

63.3

69.6

53.0

60.6

60.6

62.1

61.1

65.9

51.8

24

61.5

51.6

66.7

38.7

74.3

26.0

56.6

48.8

61.7

36.9

69.2

24.2

51.5

45.8

56.5

34.8

63.9

22.4

27

64.2

60.1

68.1

49.9

74.4

33.0

59.8

57.2

63.6

48.0

69.8

32.0

55.3

54.2

58.9

45.9

65.1

30.9

30

66.8

66.8

69.3

59.4

74.3

45.2

63.0

63.0

65.4

57.5

70.3

44.2

58.9

58.9

61.3

55.3

66.1

43.0

33

69.2

69.2

70.5

67.2

74.2

55.8

66.0

66.0

67.1

65.3

70.7

54.7

62.9

62.5

63.5

63.1

67.1

53.5

24

63.0

53.2

67.8

40.0

75.0

26.3

58.1

50.4

62.8

38.2

69.9

24.5

52.9

47.4

57.5

36.1

64.6

22.6

27

65.7

61.7

69.2

51.3

75.2

34.1

61.3

58.9

64.7

49.4

70.6

33.1

56.7

55.9

60.0

47.3

65.8

32.0

30

68.3

68.3

70.5

60.9

75.2

46.4

64.4

64.4

66.6

59.0

71.1

45.5

60.4

60.4

62.4

56.9

66.9

44.2

33

70.8

70.8

71.7

68.9

75.0

57.1

67.4

67.4

68.3

66.9

71.5

56.1

64.6

64.6

64.6

64.6

67.8

54.8

24

64.1

54.4

68.6

40.9

75.5

26.4

59.1

51.6

63.5

39.1

70.3

24.6

53.9

48.6

58.2

37.0

64.9

22.7

27

66.8

63.1

70.0

52.4

75.6

34.8

62.4

60.3

65.5

50.5

71.0

33.9

57.7

57.2

60.7

48.4

66.2

32.7

30

69.4

69.4

71.3

62.1

75.6

47.3

65.5

65.5

67.3

60.2

71.5

46.4

61.4

61.4

63.1

58.0

67.3

45.1

33

71.9

71.9

72.5

70.2

75.5

58.1

68.6

68.6

69.1

68.2

72.0

57.1

65.4

65.4

65.4

65.4

68.2

55.9

Ambient Temperature (°C)
45
Enter
16
Airflow DB
m3/h (°C) TGC SHC

9005

9940

10875

11810

12745

49

52

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

42.3

38.3

47.9

28.8

55.9

19.6

39.5

36.6

45.1

27.6

53.0

18.6

36.7

34.8

42.2

26.2

NA

NA

27

46.6

46.4

50.8

39.7

57.6

26.1

44.1

44.1

48.3

38.4

55.0

25.3

41.6

41.6

45.8

37.0

NA

NA

30

50.7

50.7

53.7

48.8

59.1

38.0

48.5

48.5

51.5

47.5

56.8

37.2

46.3

46.3

49.2

46.1

NA

NA

33

55.9

55.9

56.5

56.2

60.6

48.2

54.5

54.5

54.5

54.5

58.6

47.3

52.5

52.5

52.5

52.5

NA

NA

24

44.4

40.6

49.6

30.8

57.3

20.0

41.6

38.8

46.8

29.6

54.4

19.1

38.8

37.0

43.9

28.2

NA

NA

27

48.7

48.7

52.6

41.8

59.0

27.9

46.2

46.2

50.1

40.5

56.4

27.1

43.6

43.6

47.5

39.1

NA

NA

30

52.9

52.9

55.5

51.0

60.6

39.9

50.6

50.6

53.2

49.7

58.3

39.1

48.4

48.4

50.9

48.4

NA

NA

33

58.3

58.3

58.3

58.3

62.0

50.3

56.3

56.3

56.3

56.3

60.0

49.4

54.2

54.2

54.2

54.2

NA

NA

24

46.1

42.5

51.0

32.5

58.3

20.4

43.3

40.8

48.2

31.2

55.5

19.4

40.5

39.0

45.3

29.9

NA

NA

27

50.4

50.4

54.0

43.5

60.0

29.4

47.9

47.9

51.5

42.3

57.5

28.6

45.4

45.4

48.9

40.9

NA

NA

30

54.6

54.6

56.9

52.9

61.6

41.5

52.4

52.4

54.6

51.6

59.3

40.7

50.1

50.1

52.3

50.3

NA

NA

33

59.7

59.7

59.7

59.7

63.1

52.0

57.7

57.7

57.7

57.7

61.1

51.1

55.6

55.6

55.6

55.6

NA

NA

24

47.5

44.1

52.0

33.7

59.0

20.7

44.7

42.4

49.2

32.5

56.1

19.6

41.8

40.6

46.3

31.2

NA

NA

27

51.8

51.8

55.1

44.9

60.7

30.5

49.3

49.3

52.5

43.7

58.1

29.7

46.7

46.7

49.9

42.3

NA

NA

30

56.0

56.0

58.0

54.5

62.4

42.8

53.8

53.8

55.7

53.2

60.0

42.0

51.5

51.5

53.3

51.8

NA

NA

33

60.8

60.8

60.8

60.8

63.9

53.3

58.7

58.7

58.7

58.7

61.8

52.5

56.7

56.7

56.7

56.7

NA

NA

24

48.5

45.3

52.7

34.7

59.3

20.8

45.7

43.6

49.8

33.4

56.4

19.8

42.8

41.8

46.9

32.1

NA

NA

27

52.8

52.8

55.7

46.0

61.1

31.3

50.3

50.3

53.2

44.7

58.5

30.5

47.7

47.7

50.5

43.4

NA

NA

30

57.1

57.1

58.7

55.6

62.7

43.7

54.8

54.8

56.4

54.3

60.4

42.8

52.5

52.5

54.0

53.0

NA

NA

33

61.5

61.5

61.5

61.5

64.2

54.4

59.4

59.4

59.4

59.4

62.1

53.5

NA

NA

NA

NA

NA

NA

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

34

RT-PRC034-EN

Performance Data
Gross Cooling Capacities

Table 9.

Gross cooling capacities T/YS*200FD (IP)
Ambient Temperature (°F)
85

Enter
61
Airflow DB
CFM
(°F) TGC SHC
75
5300

5850

6400

6950

7500

95

105

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

61
TGC

67

SHC

TGC

73

SHC

TGC

SHC

196.1 161.7 216.0 119.8 244.3 85.5 179.6 152.2 199.2 113.5 227.2 79.5 162.3 141.9 181.7 106.4 209.3 73.3

80

205.2 189.7 220.7 157.1 244.5 101.4 190.6 180.1 205.7 150.7 229.3 98.1 175.1 169.6 190.0 143.4 213.2 94.1

85

213.9 211.9 224.9 188.7 244.3 142.3 201.1 201.1 211.8 182.1 230.9 138.9 187.5 187.5 197.9 174.7 216.7 134.7

90

222.1 222.1 228.8 214.5 243.7 177.4 211.2 211.2 217.5 207.8 232.2 173.9 199.4 199.4 205.5 200.3 219.8 169.6

75

203.6 169.5 222.3 126.6 249.4 87.3 187.0 160.0 205.5 120.3 232.2 81.3 169.6 149.6 187.8 113.1 214.2 75.0

80

212.7 197.9 227.1 164.3 249.7 107.5 198.0 188.3 212.0 157.9 234.4 104.3 182.4 177.8 196.2 150.6 218.2 100.3

85

221.5 220.5 231.4 196.3 249.6 148.8 208.6 208.6 218.2 189.7 236.1 145.5 194.9 194.9 204.2 182.4 221.8 141.3

90

229.8 229.8 235.3 222.5 249.0 184.4 218.7 218.7 223.9 215.8 237.4 180.9 206.9 206.9 211.7 208.3 224.9 176.6

75

209.8 176.1 227.4 132.1 253.3 88.7 193.1 166.6 210.4 125.8 236.0 82.6 175.6 156.2 192.6 118.7 217.9 76.3

80

219.0 204.9 232.2 170.3 253.7 112.5 204.2 195.3 217.0 163.9 238.2 109.3 188.5 184.8 201.1 156.6 221.9 105.3

85

227.8 227.8 236.6 202.7 253.6 154.2 214.8 214.8 223.2 196.2 240.0 150.9 201.0 201.0 209.1 188.8 225.6 146.7

90

236.2 236.2 240.5 229.3 253.1 190.2 225.0 225.0 229.0 222.7 241.3 186.8 214.6 213.1 216.8 215.2 228.8 182.5

75

214.9 181.4 231.3 136.5 256.0 89.6 198.1 171.9 214.2 130.2 238.6 83.5 180.4 161.6 196.2 123.1 220.4 77.1

80

224.1 210.7 236.1 175.1 256.4 116.3 209.2 201.1 220.8 168.7 240.8 113.1 193.4 190.6 204.8 161.4 224.4 109.1

85

233.0 233.0 240.5 207.9 256.4 158.4 219.8 219.8 227.1 201.4 242.7 155.1 205.9 205.9 212.9 194.0 228.1 151.0

90

241.4 241.4 244.5 235.0 256.0 194.8 230.1 230.1 232.9 228.3 244.1 191.4 220.6 220.6 220.6 220.6 231.4 187.1

75

218.7 185.6 233.9 139.6 257.5 90.1 201.7 176.1 216.7 133.4 239.9 84.0 184.0 165.8 198.6 126.3 221.6 77.6

80

228.0 215.3 238.8 178.7 257.9 118.9 212.9 205.7 223.4 172.3 242.2 115.7 197.0 195.2 207.2 165.0 225.7 111.7

85

236.9 236.9 243.3 211.9 258.0 161.4 223.6 223.6 229.7 205.4 244.1 158.2 209.6 209.6 215.4 198.0 229.5 154.0

90

245.4 245.4 247.3 239.4 257.6 198.3 234.0 234.0 235.6 232.8 245.6 194.8 223.1 223.1 223.1 223.1 232.8 190.6

Ambient Temperature (°F)
115
Enter
61
Airflow DB
CFM (°F) TGC SHC

5300

5850

6400

6950

7500

120

125

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

61
TGC

67

SHC

TGC

73

SHC

TGC

SHC

75

144.3 130.7 163.3 98.4 190.6 66.7 134.9 124.7 153.8 94.0 180.9 63.3 125.4 118.6 144.1 89.5

NA

NA

80

158.9 158.3 173.5 135.3 196.4 89.1 150.4 150.4 164.9 130.9 187.6 86.4 141.8 141.8 156.1 126.3

NA

NA

85

173.1 173.1 183.2 166.5 201.7 129.7 165.6 165.6 175.6 162.0 193.9 126.8 157.9 157.9 167.7 157.4

NA

NA

90

190.7 190.7 192.6 191.9 206.7 164.4 185.9 185.9 185.9 185.9 199.8 161.5 178.9 178.9 178.9 178.9

NA

NA

75

151.4 138.4 169.3 105.1 195.4 68.4 142.0 132.5 159.7 100.8 185.7 65.0 132.4 126.4 149.9 96.3

NA

NA

80

166.1 166.1 179.5 142.5 201.2 95.3 157.6 157.6 170.9 138.1 192.4 92.6 148.9 148.9 162.0 133.5

NA

NA

85

180.3 180.3 189.3 174.1 206.6 136.3 172.8 172.8 181.6 169.7 198.8 133.4 165.0 165.0 173.7 165.0

NA

NA

90

198.8 198.8 198.8 198.8 211.6 171.5 192.0 192.0 192.0 192.0 204.7 168.6 185.0 185.0 185.0 185.0

NA

NA

75

157.3 145.0 174.0 110.7 199.0 69.6 147.9 139.1 164.4 106.4 189.2 66.2 138.2 133.0 154.6 101.9

NA

NA

80

172.0 172.0 184.3 148.5 204.9 100.4 163.5 163.5 175.6 144.2 196.0 97.6 154.8 154.8 166.7 139.6

NA

NA

85

186.4 186.4 194.2 180.6 210.3 141.7 178.8 178.8 186.4 176.1 202.4 138.9 170.9 170.9 178.4 171.5

NA

NA

90

203.7 203.7 203.7 203.7 215.4 177.3 196.8 196.8 196.8 196.8 208.4 174.4 189.8 189.8 189.8 189.8

NA

NA

75

162.0 150.4 177.5 115.1 201.3 70.5 152.5 144.5 167.8 110.8 191.5 67.0 142.8 138.4 158.0 106.3

NA

NA

80

176.8 176.8 187.9 153.3 207.3 104.2 168.2 168.2 179.1 149.0 198.4 101.4 159.4 159.4 170.2 144.4

NA

NA

85

191.2 191.2 197.8 185.8 212.8 146.0 183.5 183.5 190.0 181.4 204.8 143.1 175.6 175.6 182.0 176.7

NA

NA

90

207.3 207.3 207.3 207.3 217.9 182.0 200.4 200.4 200.4 200.4 210.8 179.1 193.3 193.3 193.3 193.3

NA

NA

75

165.4 154.6 179.8 118.3 202.4 70.9 155.9 148.7 170.1 114.0 192.6 67.4 146.1 142.6 160.1 109.5

NA

NA

80

180.3 180.3 190.2 157.0 208.4 106.8 171.6 171.6 181.4 152.6 199.5 104.0 162.8 162.8 172.4 148.0

NA

NA

85

194.7 194.7 200.2 189.8 214.0 149.0 187.0 187.0 192.3 185.4 205.9 146.2 179.0 179.0 184.2 180.8

NA

NA

90

209.8 209.8 209.8 209.8 219.1 185.4 202.8 202.8 202.8 202.8 212.0 182.6

NA

NA

NA

NA

NA

NA

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

RT-PRC034-EN

35

Performance Data
Gross Cooling Capacities

Table 10. Gross cooling capacities T/YS*250FD (SI)
Ambient Temperature (°C)
30
Enter
16
Airflow DB
m3/h (°C) TGC SHC

11380

12490

13590

14700

15800

35

40

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

66.1

54.9

70.9

39.4

77.7

27.2

61.5

52.4

66.3

38.0

73.0

25.6

56.4

49.4

61.1

36.0

67.7

23.7

27

68.6

64.1

72.3

52.1

77.9

31.6

64.5

61.4

68.1

50.5

73.7

31.1

59.8

58.2

63.4

48.4

68.9

30.1

30

70.8

70.8

73.4

62.7

77.9

45.7

67.2

67.2

69.7

60.9

74.1

45.0

63.0

63.0

65.4

58.6

69.9

43.8

33

72.7

72.7

74.1

71.1

77.5

57.7

69.6

69.6

71.0

69.2

74.3

56.8

66.5

65.9

67.2

66.6

70.5

55.4

24

67.6

56.6

72.1

41.1

78.6

27.5

62.9

54.1

67.4

39.7

73.8

25.8

57.8

51.1

62.2

37.8

68.6

24.0

27

70.1

65.9

73.5

53.9

78.9

33.4

66.0

63.2

69.3

52.3

74.7

32.9

61.4

60.0

64.6

50.2

69.9

31.9

30

72.4

72.4

74.7

64.5

78.9

47.6

68.8

68.8

71.0

62.8

75.2

46.9

64.7

64.7

66.8

60.5

70.9

45.7

33

74.5

74.5

75.6

73.0

78.7

59.6

71.4

71.4

72.4

71.1

75.5

58.8

68.0

68.0

68.7

68.7

71.7

57.4

24

68.8

58.2

73.0

42.7

79.2

27.7

64.2

55.8

68.4

41.4

74.5

26.1

59.1

52.9

63.2

39.5

69.3

24.3

27

71.5

67.6

74.6

55.6

79.7

35.1

67.4

65.0

70.4

54.1

75.5

34.7

62.8

61.9

65.7

52.0

70.7

33.7

30

73.9

73.9

75.9

66.3

79.8

49.3

70.3

70.3

72.2

64.6

76.1

48.8

66.2

66.2

68.0

62.4

71.8

47.6

33

76.1

76.1

76.9

74.9

79.7

61.5

73.0

73.0

73.7

73.0

76.5

60.7

70.0

70.0

70.0

70.0

72.7

59.4

24

69.9

59.8

73.8

44.3

79.7

27.9

65.3

57.5

69.2

43.0

75.1

26.3

60.2

54.6

64.0

41.2

69.8

24.4

27

72.7

69.3

75.5

57.3

80.3

36.7

68.6

66.7

71.4

55.8

76.1

36.4

64.0

63.6

66.7

53.8

71.4

35.5

30

75.2

75.2

76.9

68.1

80.5

51.1

71.6

71.6

73.3

66.4

76.9

50.6

67.5

67.5

69.1

64.3

72.6

49.5

33

77.5

77.5

78.0

76.7

80.5

63.3

74.9

74.9

74.9

74.9

77.3

62.6

71.2

71.2

71.2

71.2

73.6

61.3

24

70.8

61.4

74.5

45.8

80.1

28.0

66.3

59.1

69.9

44.6

75.4

26.4

61.2

56.2

64.7

42.8

70.2

24.6

27

73.8

70.9

76.3

58.9

80.7

38.4

69.7

68.4

72.1

57.5

76.6

38.1

65.1

65.1

67.5

55.5

71.9

37.2

30

76.4

76.4

77.8

69.8

81.1

52.8

72.8

72.8

74.1

68.2

77.4

52.3

68.7

68.7

70.0

66.1

73.2

51.3

33

78.2

78.2

79.0

78.5

81.2

65.1

75.9

75.9

75.9

75.9

78.0

64.4

72.2

72.2

72.2

72.2

74.3

63.2

Ambient Temperature (°C)
45
Enter
16
Airflow DB
m3/h (°C) TGC SHC

11380

12490

13590

14700

15800

49

52

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

50.6

45.8

55.3

33.5

61.9

21.7

47.6

43.7

52.2

32.0

58.8

20.6

44.4

41.6

49.0

30.4

55.6

19.4

27

54.6

54.4

58.1

45.7

63.6

28.5

51.8

51.8

55.3

44.1

60.8

27.5

48.8

48.8

52.3

42.4

57.8

26.3

30

58.3

58.3

60.7

55.7

65.0

42.0

55.7

55.7

58.1

54.1

62.4

40.9

53.0

53.0

55.3

52.3

59.7

39.7

33

62.9

62.9

62.9

62.9

66.2

53.4

60.6

60.6

60.6

60.6

63.8

52.3

58.1

58.1

58.1

58.1

61.3

50.9

24

52.1

47.6

56.4

35.3

62.8

22.0

49.0

45.6

53.4

33.9

59.7

20.9

45.9

43.5

50.2

32.3

56.4

19.8

27

56.2

56.2

59.4

47.6

64.6

30.4

53.4

53.4

56.6

46.0

61.7

29.4

50.4

50.4

53.6

44.4

58.7

28.2

30

60.0

60.0

62.0

57.7

66.1

44.0

57.4

57.4

59.5

56.1

63.5

42.9

54.7

54.7

56.7

54.3

60.8

41.7

33

64.4

64.4

64.4

64.4

67.4

55.5

62.1

62.1

62.1

62.1

65.0

54.3

59.6

59.6

59.6

59.6

62.5

53.0

24

53.4

49.4

57.5

37.1

63.5

22.2

50.3

47.4

54.4

35.7

60.4

21.1

47.2

45.3

51.2

34.1

57.2

20.0

27

57.6

57.6

60.5

49.4

65.4

32.2

54.8

54.8

57.7

47.9

62.6

31.2

51.8

51.8

54.7

46.3

59.6

30.1

30

61.5

61.5

63.3

59.6

67.1

45.9

58.9

58.9

60.7

58.0

64.5

44.9

56.2

56.2

58.0

56.3

61.7

43.7

33

65.8

65.8

65.8

65.8

68.4

57.5

63.4

63.4

63.4

63.4

66.1

56.4

61.0

61.0

61.0

61.0

63.6

55.1

24

54.5

51.1

58.3

38.8

64.1

22.4

51.5

49.2

55.2

37.4

61.0

21.3

48.3

47.1

52.0

35.9

57.7

20.2

27

58.8

58.8

61.5

51.2

66.1

34.0

56.0

56.0

58.6

49.8

63.2

33.1

53.1

53.1

55.7

48.1

60.3

32.0

30

62.8

62.8

64.3

61.5

67.8

47.8

60.3

60.3

61.8

59.9

65.2

46.8

57.6

57.6

59.1

58.2

62.5

45.6

33

67.0

67.0

67.0

67.0

69.3

59.5

64.6

64.6

64.6

64.6

67.0

58.3

62.2

62.2

62.2

62.2

64.5

57.1

24

55.5

52.8

59.0

40.5

64.5

22.6

52.5

50.9

55.9

39.2

61.4

21.5

49.3

48.8

52.8

37.6

58.2

20.4

27

59.9

59.9

62.3

53.0

66.6

35.8

57.1

57.1

59.5

51.6

63.8

34.9

54.2

54.2

56.5

50.0

60.8

33.8

30

64.0

64.0

65.3

63.4

68.5

49.7

61.5

61.5

62.7

61.8

65.9

48.7

60.0

60.0

60.0

60.0

63.2

47.5

33

68.0

68.0

68.0

68.0

70.0

61.4

65.7

65.7

65.7

65.7

67.7

60.3

63.2

63.2

63.2

63.2

65.2

59.1

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

36

RT-PRC034-EN

Performance Data
Gross Cooling Capacities

Table 11. Gross cooling capacities T/YS*250FD (IP)
Ambient Temperature (°F)
85
Enter
61
Airflow DB
CFM
(°F) TGC SHC
75
6700

7350

8000

8650

9300

95

105

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

225.7 187.4 242.0 134.4 265.2 92.8 209.9 178.9 226.1 129.6 249.1 87.2 192.3 168.4 208.3 122.9 231.1 80.9

80

234.1 218.8 246.6 177.8 265.9 107.9 220.0 209.6 232.4 172.4 251.5 106.2 204.1 198.6 216.3 165.1 235.2 102.6

85

241.6 241.6 250.3 213.9 265.7 156.0 229.2 229.2 237.7 207.9 252.9 153.7 215.0 215.0 223.3 199.9 238.3 149.5

90

248.2 248.2 253.0 242.6 264.5 196.8 237.5 237.5 242.1 235.9 253.4 193.9 227.0 224.9 229.3 227.4 240.5 189.0

75

230.5 193.1 245.8 140.1 268.0 93.8 214.7 184.7 230.0 135.4 251.9 88.2 197.2 174.5 212.2 128.9 234.0 81.9

80

239.3 224.8 250.8 183.8 269.1 113.8 225.3 215.8 236.6 178.5 254.7 112.3 209.4 204.9 220.5 171.4 238.5 108.9

85

247.2 247.2 254.8 220.2 269.2 162.3 234.8 234.8 242.3 214.3 256.5 160.1 220.6 220.6 227.9 206.5 242.0 156.0

90

254.1 254.1 257.9 249.1 268.4 203.3 243.5 243.5 247.1 242.6 257.4 200.5 232.0 232.0 234.4 234.2 244.6 195.9

75

234.7 198.7 249.1 145.7 270.3 94.6 219.1 190.5 233.3 141.2 254.3 89.0 201.5 180.4 215.6 134.8 236.4 82.7

80

243.9 230.6 254.5 189.7 271.8 119.7 230.0 221.8 240.3 184.5 257.4 118.3 214.1 211.1 224.3 177.5 241.2 115.0

85

252.2 252.2 258.9 226.3 272.3 168.4 239.9 239.9 246.4 220.5 259.6 166.3 225.7 225.7 232.1 212.9 245.1 162.5

90

259.5 259.5 262.3 255.5 271.9 209.7 248.9 248.9 251.5 249.2 260.9 207.0 238.9 238.9 238.9 238.9 248.1 202.5

75

238.5 204.2 251.9 151.1 272.0 95.2 222.9 196.1 236.1 146.8 256.1 89.6 205.4 186.2 218.4 140.5 238.2 83.4

80

248.1 236.4 257.6 195.4 273.9 125.4 234.1 227.7 243.5 190.4 259.6 124.1 218.3 217.1 227.5 183.6 243.5 121.0

85

256.7 256.7 262.4 232.3 274.8 174.3 244.5 244.5 249.9 226.7 262.2 172.5 230.3 230.3 235.7 219.2 247.8 168.7

90

264.4 264.4 266.2 261.8 274.8 215.9 255.5 255.5 255.5 255.5 263.9 213.4 242.9 242.9 242.9 242.9 251.1 209.1

75

241.7 209.5 254.1 156.4 273.3 95.6 226.1 201.6 238.4 152.2 257.4 90.1 208.7 191.8 220.7 146.2 239.6 83.9

80

251.7 242.0 260.2 201.0 275.5 130.9 237.8 233.4 246.1 196.1 261.3 129.9 222.0 222.0 230.2 189.5 245.2 126.9

85

260.7 260.7 265.3 238.1 276.8 180.2 248.5 248.5 253.0 232.7 264.2 178.5 234.4 234.4 238.7 225.4 249.8 174.9

90

266.9 266.9 269.5 267.9 277.1 222.0 258.9 258.9 258.9 258.9 266.3 219.7 246.3 246.3 246.3 246.3 253.6 215.5

Ambient Temperature (°F)
115
Enter
61
Airflow DB
CFM (°F) TGC SHC

6700

7350

8000

8650

9300

120

125

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

75

172.8 156.1 188.6 114.3 211.3 73.9 162.3 149.2 178.1 109.3 200.7 70.2 151.4 141.9 167.1 103.8 189.6 66.4

80

186.3 185.6 198.3 155.9 217.0 97.1 176.7 176.7 188.6 150.6 207.3 93.7 166.6 166.6 178.5 144.8 197.0 89.8

85

198.9 198.9 207.0 190.1 221.9 143.4 190.1 190.1 198.1 184.5 213.0 139.7 180.9 180.9 188.8 178.4 203.6 135.4

90

214.7 214.7 214.7 214.7 225.8 182.3 206.7 206.7 206.7 206.7 217.7 178.3 198.3 198.3 198.3 198.3 209.1 173.8

75

177.7 162.3 192.6 120.5 214.2 75.0 167.3 155.5 182.1 115.5 203.6 71.3 156.4 148.3 171.1 110.2 192.6 67.4

80

191.6 191.6 202.6 162.3 220.4 103.5 182.0 182.0 193.0 157.1 210.6 100.2 172.0 172.0 182.8 151.4 200.4 96.4

85

204.6 204.6 211.7 196.8 225.6 150.1 195.8 195.8 202.9 191.3 216.7 146.5 186.6 186.6 193.6 185.3 207.3 142.3

90

219.8 219.8 219.8 219.8 229.9 189.3 211.9 211.9 211.9 211.9 221.8 185.3 203.4 203.4 203.4 203.4 213.3 180.9

75

182.1 168.4 196.0 126.5 216.7 75.8 171.8 161.7 185.5 121.7 206.1 72.1 160.9 154.5 174.6 116.4 195.1 68.3

80

196.4 196.4 206.4 168.7 223.2 109.9 186.9 186.9 196.8 163.5 213.5 106.6 176.9 176.9 186.7 157.9 203.3 102.8

85

209.7 209.7 215.9 203.4 228.8 156.7 201.0 201.0 207.1 198.0 219.9 153.1 191.9 191.9 197.8 192.1 210.6 149.1

90

224.4 224.4 224.4 224.4 233.4 196.2 216.4 216.4 216.4 216.4 225.4 192.3 208.0 208.0 208.0 208.0 216.9 187.9

75

186.0 174.3 198.9 132.4 218.6 76.5 175.7 167.7 188.5 127.7 208.0 72.8 164.8 160.6 177.6 122.5 197.0 69.0

80

200.7 200.7 209.7 174.9 225.5 116.0 191.2 191.2 200.1 169.8 215.8 112.8 181.2 181.2 190.0 164.3 205.6 109.2

85

214.4 214.4 219.5 209.9 231.4 163.1 205.7 205.7 210.8 204.5 222.6 159.6 196.6 196.6 201.5 198.7 213.3 155.7

90

228.4 228.4 228.4 228.4 236.5 202.9 220.5 220.5 220.5 220.5 228.5 199.1 212.1 212.1 212.1 212.1 220.0 194.8

75

189.4 180.1 201.3 138.2 219.9 77.0 179.1 173.6 190.9 133.6 209.4 73.3 168.3 166.6 180.0 128.4 198.5 69.5

80

204.4 204.4 212.4 180.9 227.2 122.1 194.9 194.9 202.9 175.9 217.6 119.0 185.0 185.0 192.8 170.5 207.4 115.4

85

218.5 218.5 222.7 216.2 233.6 169.5 209.9 209.9 213.9 210.9 224.8 166.1 204.7 204.7 204.7 204.7 215.5 162.2

90

231.9 231.9 231.9 231.9 239.0 209.5 224.0 224.0 224.0 224.0 231.0 205.8 215.7 215.7 215.7 215.7 222.6 201.6

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

RT-PRC034-EN

37

Performance Data
Gross Cooling Capacities

Table 12. Gross cooling capacities WS*155ED, ET (SI)
Ambient Temperature (°C)
30
Enter
16
Airflow DB
m3/h (°C) TGC SHC

7650

8500

9350

10200

35

40

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

44.4

36.8

47.8

25.6

49.0

12.5

39.5

34.6

46.8

26.1

49.0

14.0

33.5

31.8

43.6

25.3

48.1

14.7

27

45.7

44.0

47.8

33.0

49.1

19.8

42.1

42.1

47.0

33.5

49.3

21.1

37.6

37.6

43.8

32.6

48.4

22.4

30

47.2

47.2

48.1

40.3

49.4

27.3

45.7

45.7

47.3

41.0

49.5

28.2

42.5

42.5

44.4

40.0

48.6

29.8

33

48.5

48.5

48.6

46.3

49.3

34.0

47.9

47.9

48.1

46.7

49.7

35.6

46.3

46.3

46.5

46.4

48.9

37.0

24

45.7

39.4

48.0

26.6

49.2

11.8

41.8

37.4

47.2

27.1

49.4

12.8

35.7

34.5

44.7

26.6

48.5

14.2

27

46.7

45.8

48.2

34.6

49.4

19.7

44.2

44.2

47.5

35.4

49.6

20.7

40.9

40.9

44.9

34.9

48.8

22.5

30

48.1

48.1

48.5

41.7

49.6

27.6

47.3

47.3

48.0

43.2

49.8

28.8

44.9

44.9

46.1

43.0

49.0

30.5

33

49.2

49.2

48.9

47.6

49.8

34.7

48.9

48.9

48.9

48.4

49.8

37.0

47.8

47.8

47.8

47.8

49.3

38.9

24

46.4

41.1

48.3

26.8

49.3

10.7

43.1

39.8

47.7

28.0

49.4

12.5

37.7

37.0

45.5

27.6

48.9

14.3

27

47.2

46.9

48.2

34.7

49.4

18.4

46.2

46.2

48.0

37.0

49.9

21.3

42.8

42.8

45.9

37.0

49.2

23.1

30

48.3

48.6

48.8

43.3

49.9

27.8

48.1

48.1

48.4

44.6

50.0

30.3

46.8

46.8

47.1

45.0

49.4

32.3

33

49.6

49.6

48.9

48.9

50.0

35.0

49.6

49.6

49.4

49.4

50.3

39.2

48.7

48.7

48.7

48.7

49.7

41.0

24

47.1

42.7

48.4

26.6

49.4

9.0

44.5

42.2

48.0

28.5

49.8

12.4

39.6

39.4

46.1

28.7

49.2

13.8

27

47.9

47.9

48.6

36.1

49.6

18.7

47.2

47.2

48.2

38.1

50.1

22.0

44.3

44.3

46.7

38.9

49.5

23.6

30

49.0

49.0

48.8

45.0

49.9

27.8

48.8

48.8

48.7

45.9

50.3

31.7

47.6

47.6

47.8

46.6

49.6

33.3

33

49.8

49.8

49.5

49.5

50.0

36.1

50.1

50.1

50.1

50.1

50.5

40.6

49.4

49.4

49.4

49.4

50.1

42.5

Ambient Temperature (°C)
45
Entering Wet Bulb
Temperature (°C)

Enter
16
Airflow DB
m3/h (°C) TGC SHC

7650

8500

9350

10200

19

22

TGC

SHC

TGC

SHC

24

28.7

28.7

37.5

22.7

45.9

14.6

27

33.3

33.3

38.1

30.4

46.1

22.0

30

38.6

38.6

39.6

37.9

46.4

29.6

33

43.1

43.1

43.2

43.2

46.6

36.9

24

30.7

30.7

38.9

24.2

46.5

14.8

27

36.0

36.0

39.3

32.6

46.7

22.9

30

41.3

41.3

41.8

41.1

47.0

31.3

33

45.4

45.4

45.5

45.5

47.3

39.5

24

32.6

32.6

40.3

25.7

47.0

14.7

27

38.3

38.3

40.8

35.0

47.2

23.7

30

43.3

43.3

43.6

43.4

47.4

32.9

33

46.9

46.9

47.0

47.0

47.7

41.6

24

34.3

34.3

41.5

27.3

47.3

14.5

27

40.1

40.1

42.3

37.4

47.6

24.7

30

45.1

45.1

45.2

45.2

47.8

34.6

33

47.8

47.8

47.8

47.8

48.4

43.5

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

38

RT-PRC034-EN

Performance Data
Gross Cooling Capacities

Table 13. Gross cooling capacities WS*155ED, ET (IP)
Ambient Temperature (°C)
30
Enter
16
Airflow DB
m3/h (°C) TGC SHC
24
7650

8500

9350

10200

35

40

Entering Wet Bulb Temperature (°C)
19
TGC

SHC

22
TGC

SHC

16
TGC

SHC

19
TGC

SHC

22
TGC

SHC

16
TGC

SHC

19
TGC

SHC

22
TGC

SHC

151.6 125.7 163.0 87.3 167.2 42.6 134.7 118.0 159.6 89.1 167.3 47.9 114.5 108.6 148.8 86.3 164.2 50.3

27

155.8 150.2 163.1 112.5 167.6 67.6 143.7 143.7 160.4 114.2 168.2 72.1 128.3 128.3 149.4 111.1 165.1 76.4

30

161.0 161.0 164.2 137.3 168.4 93.0 155.9 155.9 161.4 139.8 168.8 96.1 145.0 145.0 151.6 136.6 165.8 101.6

33

165.3 165.3 165.9 157.8 168.3 115.9 163.5 163.5 164.2 159.2 169.6 121.4 158.1 158.1 158.6 158.2 166.8 126.3

24

156.0 134.3 163.8 90.9 167.8 40.1 142.5 127.7 161.2 92.4 168.4 43.7 121.7 117.6 152.4 90.8 165.5 48.6

27

159.3 156.3 164.4 117.9 168.7 67.3 150.7 150.7 162.2 120.6 169.2 70.8 139.5 139.5 153.3 119.2 166.6 76.8

30

164.0 164.0 165.4 142.2 169.3 94.2 161.4 161.4 163.7 147.5 170.0 98.3 153.1 153.1 157.2 146.8 167.3 104.2

33

167.8 167.8 166.8 162.5 169.9 118.5 166.8 166.8 166.7 165.2 170.0 126.3 163.1 163.1 163.2 163.2 168.2 132.9

24

158.3 140.1 164.6 91.3 168.2 36.6 147.2 135.8 162.7 95.6 168.5 42.7 128.6 126.4 155.1 94.3 167.0 48.9

27

161.2 159.9 164.5 118.5 168.6 62.9 157.7 157.7 163.6 126.2 170.3 72.8 145.9 145.9 156.7 126.1 167.8 78.9

30

164.9 165.7 166.6 147.6 170.2 95.0 164.1 164.1 165.2 152.1 170.7 103.3 159.5 159.5 160.8 153.6 168.4 110.2

33

169.2 169.2 166.8 166.8 170.6 119.4 169.2 169.2 168.7 168.7 171.5 133.7 166.1 166.1 166.2 166.2 169.7 139.7

24

160.6 145.8 165.0 90.9 168.6 30.8 151.9 143.8 163.6 97.2 170.1 42.4 135.1 134.3 157.4 97.9 168.0 46.9

27

163.4 163.4 165.9 123.0 169.4 63.8 161.0 161.0 164.5 130.0 171.1 75.0 151.1 151.1 159.3 132.6 168.8 80.7

30

167.0 167.0 166.5 153.6 170.2 94.8 166.4 166.4 166.3 156.5 171.6 108.2 162.5 162.5 163.2 158.9 169.3 113.6

33

169.9 169.9 169.0 169.0 170.6 123.2 170.9 170.9 170.9 170.9 172.2 138.4 168.5 168.5 168.6 168.6 171.0 144.9

Ambient Temperature (°C)
45
Entering Wet Bulb
Temperature (°C)

Enter
16
Airflow DB
m3/h (°C) TGC SHC
24
7650

8500

9350

10200

97.9

19
TGC

SHC

22
TGC

SHC

97.9 127.9 77.6 156.5 49.9

27

113.7 113.7 129.9 103.7 157.4 75.2

30

131.6 131.6 135.1 129.4 158.3 100.9

33

147.1 147.1 147.3 147.3 159.1 126.0

24

104.7 104.7 132.8 82.6 158.6 50.6

27

122.7 122.7 134.0 111.3 159.3 78.2

30

141.0 141.0 142.7 140.1 160.2 106.9

33

155.0 155.0 155.4 155.4 161.4 134.9

24

111.2 111.2 137.4 87.6 160.2 50.2

27

130.8 130.8 139.0 119.5 161.0 81.0

30

147.9 147.9 148.7 148.0 161.8 112.4

33

160.0 160.0 160.3 160.3 162.8 142.1

24

117.2 117.2 141.7 93.3 161.4 49.4

27

136.7 136.7 144.2 127.5 162.3 84.1

30

153.7 153.7 154.1 154.1 163.2 118.0

33

163.2 163.2 163.1 163.1 165.2 148.4

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

RT-PRC034-EN

39

Performance Data
Gross Cooling Capacities

Table 14. Gross cooling capacities WS*200ED, ET (SI)
Ambient Temperature (°C)
30
Enter
16
Airflow DB
m3/h (°C) TGC SHC

10100

11220

12340

13460

35

40

Entering Wet Bulb Temperature (°C)
19

22

16

19

22

16

19

22

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC

24

56.4

47.3

67.8

36.0

74.3

20.5

49.7

44.6

62.9

34.5

71.1

20.2

43.6

42.2

57.0

32.5

66.8

19.5

27

58.0

57.4

68.2

45.9

75.1

30.6

52.9

52.9

63.4

44.4

71.6

30.2

48.7

48.7

57.4

42.4

67.2

29.5

30

62.9

62.9

68.9

56.0

76.0

40.9

59.2

59.2

64.3

54.5

72.4

40.5

55.3

55.3

58.2

52.6

67.7

39.6

33

68.4

68.4

70.0

66.3

76.9

51.2

64.9

64.9

65.8

64.8

73.0

50.8

60.7

60.7

60.8

60.8

68.3

49.8

24

59.1

50.7

69.3

37.3

75.3

19.9

52.4

48.2

65.0

36.0

72.0

19.4

46.1

45.5

58.7

34.2

67.9

18.8

27

61.0

61.0

69.9

48.4

76.1

30.9

56.8

56.8

65.4

47.1

72.7

30.7

52.4

52.4

59.3

45.2

68.4

30.2

30

66.9

66.9

70.7

59.6

77.1

42.3

62.6

62.6

66.3

58.3

73.6

42.1

58.5

58.5

60.3

56.6

69.1

41.5

33

71.5

71.5

72.3

70.8

78.2

53.7

68.1

68.1

68.3

68.2

74.5

53.5

64.3

64.3

64.4

64.4

69.9

52.9

24

61.1

53.9

70.6

38.4

75.7

18.7

55.0

51.6

66.2

37.3

72.7

18.7

48.3

48.2

60.5

35.8

68.7

18.6

27

63.8

63.8

71.3

50.7

76.9

31.3

59.8

59.8

66.9

49.6

73.6

31.4

55.4

55.4

61.2

48.0

69.4

31.0

30

69.5

69.5

72.3

63.1

78.0

43.8

65.9

65.9

67.9

62.0

74.5

43.7

61.4

61.4

63.0

60.6

70.2

43.3

33

74.1

74.1

74.4

74.1

79.2

56.4

70.6

70.6

70.8

70.8

75.7

56.3

66.8

66.8

66.9

66.9

71.2

55.9

24

62.8

57.0

71.6

39.6

76.3

18.3

57.3

54.9

67.3

38.7

73.3

18.5

50.7

50.7

62.1

37.4

69.3

18.2

27

66.8

66.8

72.5

53.0

77.4

31.8

62.2

62.2

68.0

52.1

74.3

31.9

57.8

57.8

63.0

50.8

70.2

31.8

30

71.6

71.6

73.7

66.4

78.7

45.3

68.0

68.0

69.4

65.5

75.4

45.4

64.1

64.1

64.6

63.8

71.0

45.2

33

76.2

76.2

76.3

76.3

80.0

58.7

72.8

72.8

72.9

72.9

76.7

59.0

68.9

68.9

69.0

69.0

72.2

59.0

Ambient Temperature (°C)
45
Entering Wet Bulb
Temperature (°C)

Enter
16
Airflow DB
m3/h (°C) TGC SHC

10100

11220

12340

13460

19

22

TGC

SHC

TGC

SHC

24

38.3

38.3

50.6

30.4

61.7

18.2

27

44.5

44.5

51.1

40.4

62.0

28.2

30

51.0

51.0

52.4

50.7

62.4

38.3

33

56.5

56.5

56.6

56.6

62.9

48.5

24

41.0

41.0

52.6

32.2

62.8

18.3

27

47.7

47.7

53.1

43.3

63.2

29.2

30

54.2

54.2

54.7

54.3

63.7

40.4

33

59.9

59.9

60.0

60.0

64.4

51.8

24

43.2

43.2

54.0

33.9

63.7

17.9

27

50.6

50.6

54.7

46.1

64.2

30.3

30

56.6

56.6

56.8

56.8

64.8

42.6

33

62.5

62.5

62.6

62.6

65.7

55.1

24

45.6

45.6

55.1

35.5

64.4

17.6

27

53.1

53.1

55.9

48.8

65.0

31.1

30

59.3

59.3

59.4

59.4

65.7

44.6

33

64.5

64.5

64.6

64.6

66.8

58.4

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

40

RT-PRC034-EN

Performance Data
Gross Cooling Capacities

Table 15. Gross cooling capacities WS*200ED, ET (IP)
Ambient Temperature (°F)
85
Enter
61
Airflow DB
CFM
(°F) TGC SHC
75
5950

6600

7250

7900

95

105

Entering Wet Bulb Temperature (°F)
67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

61
TGC

SHC

67
TGC

SHC

73
TGC

SHC

192.6 161.3 231.2 122.7 253.7 69.8 169.6 152.2 214.6 117.5 242.5 68.8 148.6 144.0 194.5 110.8 227.9 66.4

80

197.9 195.8 232.5 156.5 256.4 104.5 180.6 180.6 216.3 151.4 244.4 102.9 166.2 166.2 196.0 144.8 229.2 100.7

85

214.5 214.5 235.0 191.1 259.3 139.6 202.0 202.0 219.3 186.1 246.9 138.0 188.6 188.6 198.6 179.4 231.1 135.1

90

233.2 233.2 238.7 226.2 262.4 174.5 221.5 221.5 224.5 221.1 249.1 173.3 207.0 207.0 207.4 207.4 233.1 169.8

75

201.8 173.1 236.6 127.1 256.8 67.7 178.9 164.4 221.7 122.9 245.6 66.1 157.2 155.3 200.4 116.5 231.6 64.3

80

208.3 208.1 238.5 165.0 259.7 105.4 193.9 193.9 223.3 160.7 248.1 104.9 178.6 178.6 202.4 154.3 233.4 103.1

85

228.3 228.3 241.2 203.4 263.2 144.2 213.7 213.7 226.1 199.0 251.1 143.8 199.6 199.6 205.9 193.0 235.8 141.6

90

243.8 243.8 246.8 241.7 266.9 183.2 232.3 232.3 232.9 232.7 254.1 182.7 219.3 219.3 219.8 219.8 238.6 180.6

75

208.5 183.9 240.9 131.1 258.3 63.7 187.6 176.1 225.8 127.4 248.0 63.9 164.9 164.6 206.3 122.2 234.5 63.5

80

217.7 217.7 243.1 173.0 262.3 106.7 203.9 203.9 228.1 169.3 251.2 107.1 189.0 189.0 208.9 163.9 236.8 105.8

85

237.1 237.1 246.7 215.1 266.2 149.4 224.9 224.9 231.5 211.6 254.3 149.1 209.5 209.5 214.9 206.7 239.4 147.8

90

252.8 252.8 253.7 252.8 270.4 192.3 240.9 240.9 241.5 241.5 258.3 192.1 227.8 227.8 228.2 228.2 242.8 190.7

75

214.3 194.4 244.2 135.0 260.2 62.3 195.5 187.3 229.5 132.1 250.0 63.3 172.9 172.9 212.0 127.7 236.5 62.1

80

228.0 228.0 247.2 180.8 264.0 108.3 212.4 212.4 232.1 177.7 253.5 108.9 197.2 197.2 214.9 173.2 239.4 108.6

85

244.4 244.4 251.4 226.6 268.3 154.5 232.0 232.0 236.6 223.6 257.1 154.8 218.8 218.8 220.6 217.8 242.4 154.2

90

259.9 259.9 260.4 260.4 272.9 200.3 248.4 248.4 248.6 248.6 261.5 201.3 235.2 235.2 235.5 235.5 246.4 201.3

Ambient Temperature (°F)
115
Entering Wet Bulb
Temperature (°F)

Enter
61
Airflow DB
CFM (°F) TGC SHC

5950

6600

7250

7900

67
TGC

SHC

73
TGC

SHC

75

130.5 130.5 172.8 103.7 210.4 62.2

80

152.0 152.0 174.4 137.7 211.4 96.3

85

173.9 173.9 178.7 173.0 212.8 130.6

90

192.8 192.8 193.1 193.1 214.8 165.5

75

139.9 139.9 179.4 109.9 214.3 62.3

80

162.7 162.7 181.3 147.7 215.7 99.8

85

184.8 184.8 186.6 185.3 217.2 137.9

90

204.4 204.4 204.8 204.8 219.6 176.8

75

147.4 147.4 184.2 115.6 217.2 61.2

80

172.5 172.5 186.5 157.3 219.0 103.3

85

193.3 193.3 193.9 193.9 221.1 145.3

90

213.1 213.1 213.5 213.5 224.0 188.0

75

155.5 155.5 188.1 121.1 219.7 60.1

80

181.1 181.1 190.7 166.6 221.7 106.0

85

202.2 202.2 202.8 202.8 224.3 152.3

90

219.9 219.9 220.3 220.3 227.8 199.1

Notes:
1. All capacities shown are gross and have not considered indoor fan heat.
2. TGC = Total gross capacity (kW)
3. SHC = Sensible heat capacity (kW)

RT-PRC034-EN

41

Performance Data
Heating Capacities

Table 16. WS*155ED, ET net heating capacities (kW)—8500 m3/h—(SI)
Outdoor

Peak Net Heating (kW)

Peak Total Power (kW)

Temp (°C)

at Indicated Dry Bulb (°C)

at Indicated Dry Bulb (°C)

70% RH

15

21

24

27

15

21

24

27

-24

13.8

13.4

13.2

13.0

10.5

11.5

12.0

12.5

-21

15.3

14.9

14.7

14.5

10.7

11.7

12.1

12.7

-18

17.0

16.5

16.3

16.0

10.9

11.8

12.4

12.9

-15

18.6

17.4

17.1

17.3

11.1

12.0

12.5

14.0

-12

20.2

17.8

18.8

18.8

12.0

12.1

12.7

13.7

-9

21.5

20.9

20.5

20.2

11.4

12.4

12.9

13.5

-6

23.4

22.7

22.3

21.9

11.6

12.5

13.1

13.7

-3

25.4

24.6

24.2

23.8

11.8

12.7

13.3

13.9

0

27.4

26.6

26.2

25.8

11.9

13.0

13.5

14.1

3

29.5

28.6

28.2

27.8

12.1

13.2

13.8

14.4

6

36.1

35.1

34.5

34.0

12.2

13.3

13.9

14.5

9

43.8

42.4

41.7

41.0

12.6

13.6

14.2

14.8

12

46.6

45.3

44.5

43.7

12.8

13.9

14.4

15.0

15

49.8

48.3

47.4

46.8

13.1

14.1

14.7

15.3

18

53.2

51.4

50.7

49.8

13.4

14.4

15.0

15.6

21

57.0

55.1

54.0

53.0

13.7

14.8

15.4

16.0

24

60.5

58.6

57.5

56.5

14.1

15.2

15.8

16.4

Notes:
1. For other airflow conditions, see heating capacity correction factor
2. Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and 0.35 inch ESP. To obtain net
heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
3. Heating capacities and powers are integrated to include the effects of defrost in the frost region.

Table 17. WS*155ED, ET net heating capacities (MBh)—5000 cfm (IP)
Outdoor

Peak Net Heating (MBh)

Peak Total Power (kW)

Temp (°F)

at Indicated Dry Bulb (°F)

at Indicated Dry Bulb (°F)

70% RH

60

70

75

80

60

70

75

80

-8

46.9

45.7

45.0

44.4

10.5

11.5

12.0

12.5

-3

52.4

51.0

50.2

49.5

10.7

11.7

12.1

12.7

2

57.9

56.3

55.5

54.7

10.9

11.8

12.4

12.9

7

63.5

59.2

58.2

59.0

11.1

12.0

12.5

14.0

12

69.0

60.9

64.1

64.1

12.0

12.1

12.7

13.7

17

73.5

71.2

70.0

68.9

11.4

12.4

12.9

13.5

22

79.9

77.3

76.1

74.9

11.6

12.5

13.1

13.7

27

86.5

83.8

82.4

81.1

11.8

12.7

13.3

13.9

32

93.6

90.8

89.2

87.9

11.9

13.0

13.5

14.1

37

100.6

97.5

96.2

94.7

12.1

13.2

13.8

14.4

42

123.3

119.7

117.8

116.0

12.2

13.3

13.9

14.5

47

149.3

144.8

142.4

140.0

12.6

13.6

14.2

14.8

52

159.0

154.4

151.9

149.2

12.8

13.9

14.4

15.0

57

170.0

164.7

161.8

159.6

13.1

14.1

14.7

15.3

62

181.5

175.5

172.9

169.7

13.4

14.4

15.0

15.6

67

194.6

187.9

184.2

180.8

13.7

14.8

15.4

16.0

72

206.5

199.8

196.2

192.6

14.1

15.2

15.8

16.4

Notes:
1. For other airflow conditions, see heating capacity correction factor
2. Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and 0.35 inch ESP. To obtain net
heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
3. Heating capacities and powers are integrated to include the effects of defrost in the frost region.

42

RT-PRC034-EN

Performance Data
Heating Capacities

Table 18. WS*200ED, ET net heating capacities (kW)—11210 m3/h—(SI)
Outdoor

Peak Net Heating (kW)

Peak Total Power (kW)

Temp (°C)

at Indicated Dry Bulb (°C)

at Indicated Dry Bulb (°C)

70% RH

15

21

24

27

15

21

24

27

-24

21.3

20.7

20.5

20.3

15.1

15.9

16.4

16.9

-21

23.1

22.5

22.3

22.0

15.3

16.0

16.5

17.0

-18

25.4

24.8

24.5

24.2

15.4

16.2

16.7

17.2

-15

28.0

27.2

27.0

26.6

15.5

16.3

16.8

17.3

-12

31.2

30.7

30.5

30.3

15.7

16.5

17.0

17.5

-9

34.6

33.8

33.6

33.3

15.9

16.7

17.2

17.7

-6

37.7

37.0

36.6

36.2

16.1

16.9

17.4

17.9

-3

40.7

39.9

39.6

39.2

16.4

17.3

17.8

18.3

0

43.7

42.8

42.5

42.1

16.5

17.4

17.9

18.4

3

47.7

46.8

46.3

46.0

16.8

17.7

18.2

18.7

6

51.8

50.6

50.1

49.6

17.0

17.9

18.4

18.9

9

56.3

55.2

54.6

54.2

17.1

18.0

18.5

19.0

12

60.4

59.1

58.4

58.0

17.4

18.3

18.8

19.3

15

64.2

62.7

62.1

61.5

17.8

18.8

19.3

19.8

18

69.1

67.5

66.6

65.9

20.0

21.1

21.6

22.1

21

73.8

71.8

70.9

70.0

20.1

21.2

21.7

22.2

24

78.7

76.8

75.9

74.9

20.4

21.5

22.0

22.6

Notes:
1. For other airflow conditions, see heating capacity correction factor
2. Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and 0.35 inch ESP. To obtain net
heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
3. Heating capacities and powers are integrated to include the effects of defrost in the frost region.

Table 19. WS*200ED, ET net heating capacities (MBh)—6600 cfm (IP)
Outdoor

Peak Net Heating (MBh)

Peak Total Power (kW)

Temp (°F)

at Indicated Dry Bulb (°F)

at Indicated Dry Bulb (°F)

70% RH

60

70

75

80

60

70

75

80

-8

72.5

70.6

69.8

69.1

15.1

15.9

16.4

16.9

-3

78.8

76.8

76.1

75.1

15.3

16.0

16.5

17.0

2

86.7

84.5

83.5

82.5

15.4

16.2

16.7

17.2

7

95.4

92.9

92.1

90.9

15.5

16.3

16.8

17.3

12

106.5

104.6

104.0

103.2

15.7

16.5

17.0

17.5

17

118.0

115.4

114.7

113.7

15.9

16.7

17.2

17.7

22

128.6

126.3

124.9

123.5

16.1

16.9

17.4

17.9

27

138.7

136.2

135.0

133.7

16.4

17.3

17.8

18.3

32

149.0

146.2

145.1

143.6

16.5

17.4

17.9

18.4

37

162.8

159.8

158.1

157.1

16.8

17.7

18.2

18.7

42

176.9

172.7

170.8

169.4

17.0

17.9

18.4

18.9

47

192.0

188.2

186.3

184.9

17.1

18.0

18.5

19.0

52

206.0

201.8

199.3

197.8

17.4

18.3

18.8

19.3

57

219.1

213.9

212.0

209.7

17.8

18.8

19.3

19.8

62

235.7

230.1

227.3

225.0

20.0

21.1

21.6

22.1

67

251.6

244.8

242.0

238.8

20.1

21.2

21.7

22.2

72

268.7

262.0

259.1

255.4

20.4

21.5

22.0

22.6

Notes:
1. For other airflow conditions, see heating capacity correction factor
2. Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and 0.35 inch ESP. To obtain net
heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
3. Heating capacities and powers are integrated to include the effects of defrost in the frost region.

RT-PRC034-EN

43

Performance Data
Fan Performance

Table 20. Evaporator fan performance TS*155F downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00
m3/h RPM kW

50.00
RPM

kW

75.00
RPM

kW

100.00
RPM

kW

125.00

150.00

RPM kW RPM

1.49 Nom kW Standard Motor & Low Static
Drive Accessory

kW

175.00
RPM

kW

200.00
RPM

kW

225.00
RPM

250.00

kW

RPM

kW

1.49 Nom kw Standard Motor & High Static
Drive Accessory

7140

—

—

393

0.46

430

0.54

467

0.64

503

0.74

536

0.84

570

0.95

601

1.06

630

1.18

659

1.31

7820

376

0.48

416

0.58

451

0.66

484

0.75

518

0.86

551

0.97

581

1.08

612

1.20

642

1.32

669

1.45

8500

400

0.60

440

0.70

473

0.80

504

0.89

534

1.00

566

1.12

597

1.24

625

1.35

653

1.48

681

1.61

9180

425

0.73

464

0.85

496

0.96

525

1.06

554

1.16

582

1.28

611

1.41

640

1.54

666

1.66

692

1.79

9860

450

0.89

488

1.01

520

1.14

548

1.24

575

1.35

601

1.47

627

1.59

654

1.73

681

1.87

707

2.01

1.49 Nom kw Standard Motor Drive

2.24 Nom kw Oversized Motor & Drive

Continued
External Static Pressure (Pascals)
275.00
m3/h RPM kW

300.00
RPM

kW

325.00
RPM

kW

350.00
RPM

kW

375.00

400.00

RPM kW RPM

kW

1.49 Nom kw Standard Motor & High Static Drive Accessory

425.00
RPM

kW

450.00
RPM

kW

475.00
RPM

500.00

kW

RPM

kW

2.24 Nom kw Oversized Motor & Drive

7140

686

1.44

713

1.56

738

1.69

763

1.82

786

1.95

809

2.08

831

2.21

852

2.34

—

—

—

7820

696

1.58

722

1.72

747

1.86

771

2.00

795

2.14

818

2.28

840

2.42

—

—

—

—

—

—
—

8500

707

1.75

732

1.88

757

2.03

780

2.18

804

2.33

826

2.49

—

—

—

—

—

—

—

—

9180

718

1.93

744

2.08

768

2.22

791

2.37

813

2.53

—

—

—

—

—

—

—

—

—

—

9860

730

2.14

754

2.29

779

2.44

—

—

—

—

—

—

—

—

—

—

—

—

—

—

Note: Data includes pressure drop for filters and wet coil.

Table 21. Evaporator fan performance TS*155F downflow or horizontal (IP)
External Static Pressure (Inches of Water Pressure)
.10
CFM

.20

.30

.40

.50

.60

.70

.80

.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2HP Standard Motor & Low Static Drive Accessory

2HP Standard Motor & High Static Drive Accessory

4000

—

—

382

0.56

420

0.66

459

0.79

496

0.91

531

1.05

564

1.19

595

1.34

625

1.50

654

1.67

4500

—

—

410

0.73

446

0.85

479

0.97

514

1.11

548

1.26

578

1.40

610

1.56

639

1.72

666

1.89

5000

400

0.80

440

0.95

473

1.07

504

1.20

534

1.34

566

1.50

597

1.66

625

1.81

653

1.98

681

2.16

5500

431

1.03

470

1.19

502

1.34

531

1.48

559

1.62

586

1.77

615

1.95

643

2.12

670

2.30

695

2.47

6000

463

1.30

500

1.48

531

1.65

559

1.80

585

1.95

611

2.11

636

2.28

662

2.46

689

2.66

714

2.85

2HP Standard Motor Drive

3HP Oversized Motor & Drive

Continued
External Static Pressure (Inches of Water Pressure)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2HP Standard Motor & High Static Drive Accessory

3HP Oversized Motor & Drive

4000

682

1.83

708

1.99

734

2.16

758

2.32

782

2.49

804

2.66

826

2.83

847

3.01

—

—

—

—

4500

693

2.07

719

2.25

745

2.44

769

2.62

793

2.80

815

2.99

838

3.17

—

—

—

—

—

—

5000

707

2.34

732

2.53

757

2.72

780

2.92

804

3.13

826

3.33

—

—

—

—

—

—

—

—

5500

721

2.66

747

2.86

771

3.05

794

3.26

—

—

—

—

—

—

—

—

—

—

—

—

6000

738

3.04

760

3.22

784

3.43

—

—

—

—

—

—

—

—

—

—

—

—

—

—

Note: Data includes pressure drop for filters and wet coil.

44

RT-PRC034-EN

Performance Data
Fan Performance

Table 22. Evaporator fan performance TS*175F downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00
m3/h RPM kW

50.00
RPM

kW

75.00
RPM

100.00

kW

RPM

kW

125.00
RPM

kW

150.00
RPM

kW

175.00
RPM

2.24 Nom kw Standard Motor & Low Static Drive Accessory

kW

200.00
RPM

kW

225.00
RPM

kW

250.00
RPM

kW

2.24 Nom kw Standard Motor Drive

7985

—

—

429

0.62

463

0.71

496

0.81

529

0.92

562

1.03

592

1.14

622

1.26

652

1.39

679

8750

419

0.67

457

0.78

489

0.88

520

0.98

549

1.09

580

1.21

610

1.33

638

1.45

665

1.58

693

1.52
1.72

9515

449

0.84

485

0.96

516

1.07

545

1.18

572

1.29

599

1.41

628

1.54

656

1.68

682

1.81

707

1.94

10280

478

1.04

513

1.17

544

1.30

571

1.41

597

1.52

623

1.64

648

1.77

674

1.92

700

2.07

725

2.21

11045

508

1.26

542

1.40

572

1.55

598

1.67

623

1.79

647

1.92

671

2.05

694

2.19

718

2.34

743

2.50

2.24 Nom kw Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Pascals)
275.00
m3/h RPM kW

300.00
RPM

kW

325.00
RPM

350.00

kW

RPM

kW

375.00
RPM

kW

400.00
RPM

kW

425.00

450.00

475.00

500.00

RPM

kW

RPM

kW

RPM

kW

RPM

kW

2.24 Nom kw Standard Motor & High Static Drive Accessory
7985

705

1.65

731

1.79

756

1.94

780

2.09

803

2.23

826

2.37

848

2.52

870

2.66

890

2.81

910

2.95

8750

719

1.86

744

2.00

768

2.14

792

2.30

815

2.45

837

2.61

859

2.77

880

2.93

901

3.09

921

3.25

9515

732

2.08

758

2.23

782

2.39

805

2.54

827

2.70

849

2.86

870

3.03

891

3.20

912

3.37

932

3.55

10280

749

2.35

771

2.49

795

2.65

819

2.82

841

2.98

862

3.15

883

3.31

903

3.49

923

3.67

943

3.85

11045

767

2.66

789

2.81

811

2.96

832

3.12

854

3.29

876

3.46

897

3.64

917

3.82

937

4.00

956

4.18

3.73 Nom Oversized Motor & Drive

3.73 Nom Oversized Motor & High Static Drive Accessory

Note: Data includes pressure drop for filters and wet coil.

Table 23. Evaporator fan performance TS*175F downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
cfm

.20

.30

.40

.50

.60

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

.70

.80

.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3HP Standard Motor & Low Static Drive Accessory

3HP Standard Motor Drive

4700

—

—

429

0.84

463

0.96

496

1.08

529

1.23

562

1.38

592

1.53

622

1.69

652

1.86

679

2.04

5150

419

0.90

457

1.05

489

1.18

520

1.31

549

1.46

580

1.62

610

1.79

638

1.95

665

2.12

693

2.30

5600

449

1.13

485

1.29

516

1.44

545

1.58

572

1.73

599

1.88

628

2.07

656

2.25

682

2.43

707

2.60

6050

478

1.39

513

1.56

544

1.74

571

1.89

597

2.04

623

2.20

648

2.38

674

2.57

700

2.77

725

2.96

6500

508

1.69

542

1.88

572

2.07

598

2.24

623

2.40

647

2.57

671

2.75

694

2.93

718

3.14

743

3.35

3HP Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
1.10
cfm

1.20

1.30

1.40

1.50

1.60

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3HP Standard Motor & High Static Drive Accessory
4700

705

2.22

731

2.41

756

2.60

780

2.80

803

2.99

826

3.18

848

3.37

870

3.57

890

3.76

910

3.96

5150

719

2.49

744

2.68

768

2.88

792

3.08

815

3.29

837

3.51

859

3.72

880

3.93

901

4.14

921

4.35

5600

732

2.79

758

3.00

782

3.20

805

3.41

827

3.62

849

3.84

870

4.06

891

4.29

912

4.53

932

4.76

6050

749

3.15

771

3.34

795

3.56

819

3.78

841

4.00

862

4.22

883

4.44

903

4.68

923

4.92

943

5.16

6500

767

3.56

789

3.77

811

3.97

832

4.18

854

4.41

876

4.65

897

4.88

917

5.12

937

5.36

956

5.61

5HP Oversized Motor & Drive

5HP Oversized Motor & High Static Drive Accessory

Note: Data includes pressure drop for filters and wet coil.

RT-PRC034-EN

45

Performance Data
Fan Performance

Table 24. Evaporator fan performance TS*200F downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00
m3/h RPM kW

50.00
RPM

kW

75.00
RPM

kW

100.00
RPM

kW

125.00
RPM

kW

2.24 Nom kw Standard Motor & Low Static Drive Accy

150.00
RPM

kW

175.00
RPM

kW

200.00
RPM

kW

225.00
RPM

250.00

kW

RPM

kW

2.24 Nom kw Standard Motor & High Static Drive Accy

9005

429

0.72

466

0.84

498

0.94

528

1.04

557

1.15

586

1.27

616

1.40

644

1.53

670

1.65

697

1.78

9940

465

0.94

501

1.07

531

1.19

559

1.30

586

1.42

612

1.53

638

1.66

666

1.81

692

1.95

717

2.09

10875

502

1.21

536

1.35

565

1.49

592

1.61

617

1.73

642

1.86

665

1.98

689

2.12

714

2.28

739

2.43

11810

539

1.53

572

1.67

600

1.83

626

1.97

650

2.10

673

2.23

695

2.36

717

2.50

739

2.65

761

2.81

12745

575

1.87

607

2.05

635

2.21

660

2.37

683

2.52

704

2.66

726

2.80

747

2.95

767

3.10

787

3.25

2.24 Nom kw Standard Motor Drive

3.73 Nom kw Oversized Motor & Drive

Continued
External Static Pressure (Pascals)
275.00
m3/h RPM kW

300.00
RPM

kW

325.00
RPM

kW

350.00
RPM

kW

375.00
RPM

kW

400.00
RPM

kW

425.00

450.00

475.00

500.00

RPM

kW

RPM

kW

RPM

kW

RPM

kW

2.24 Nom kw Standard Motor & High Static Drive Accessory
9005

724

1.93

749

2.07

772

2.22

796

2.37

818

2.53

841

2.69

862

2.86

884

3.02

904

3.18

925

3.34

9940

741

2.22

765

2.37

790

2.53

813

2.69

835

2.85

856

3.01

877

3.18

898

3.36

918

3.53

938

3.71

10875

763

2.59

786

2.74

807

2.89

829

3.05

851

3.22

873

3.39

894

3.57

914

3.74

934

3.92

953

4.10

11810

784

2.98

807

3.15

829

3.32

850

3.48

870

3.64

889

3.81

910

3.99

931

4.18

—

—

—

—

12745

808

3.42

829

3.60

850

3.78

871

3.96

892

4.14

—

—

—

—

—

—

—

—

—

—

3.73 Nom kw Oversized Motor & Drive

3.73 Nom kw Oversized Motor & High Static Drive Accessory

Note: Data includes pressure drop for filters and wet coil.

Table 25. Evaporator fan performance TS*200F downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
cfm

.20

.30

.40

.50

.60

.70

.80

.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & Low Static Drive Accessory

3HP Standard Motor & High Static Drive Accessory

5300

429

0.97

466

1.13

498

1.26

528

1.40

557

1.54

586

1.70

616

1.88

644

2.05

670

2.21

697

2.39

5850

465

1.27

501

1.44

531

1.60

559

1.75

586

1.90

612

2.06

638

2.23

666

2.42

692

2.61

717

2.80

6400

502

1.62

536

1.81

565

2.00

592

2.16

617

2.32

642

2.49

665

2.66

689

2.85

714

3.05

739

3.26

6950

539

2.05

572

2.24

600

2.45

626

2.64

650

2.82

673

2.99

695

3.17

717

3.36

739

3.55

761

3.77

7500

575

2.51

607

2.74

635

2.97

660

3.18

683

3.38

704

3.57

726

3.76

747

3.95

767

4.16

787

4.36

3HP Standard Motor Drive

5HP Oversized Motor & Drive

Continued
External Static Pressure (Inches of Water)
1.10
cfm

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & High Static Drive Accessory

5300

724

2.59

749

2.78

772

2.98

796

3.18

818

3.40

841

3.61

862

3.83

884

4.05

904

4.27

925

4.48

5850

741

2.98

765

3.18

790

3.40

813

3.61

835

3.82

856

4.04

877

4.27

898

4.50

918

4.74

938

4.98

6400

763

3.47

786

3.67

807

3.87

829

4.08

851

4.31

873

4.55

894

4.78

914

5.01

934

5.26

953

5.50

6950

784

4.00

807

4.23

829

4.45

850

4.67

870

4.89

889

5.11

910

5.35

931

5.60

—

—

—

—

7500

808

4.59

829

4.82

850

5.07

871

5.31

892

5.56

—

—

—

—

—

—

—

—

—

—

5HP Oversized Motor & Drive

5HP Oversized Motor & High Static Drive Accessory

Note: Data includes pressure drop for filters and wet coil.

46

RT-PRC034-EN

Performance Data
Fan Performance

Table 26. Evaporator fan performance TS*250F downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00
m3/h RPM kW

50.00
RPM

kW

75.00
RPM

100.00

kW

RPM

kW

125.00
RPM

kW

150.00
RPM

175.00

kW

RPM

3.73 Nom kW Standard Motor & Low Static Drive Accessory

kW

200.00
RPM

kW

225.00
RPM

kW

250.00
RPM

kW

3.73 Nom kw Standard Motor and Drive

11380

521

1.37

556

1.52

584

1.67

610

1.80

635

1.93

658

2.05

681

2.19

704

2.32

727

2.47

751

2.63

12485

566

1.78

597

1.94

625

2.11

650

2.26

674

2.41

696

2.54

717

2.68

738

2.82

759

2.97

780

3.13

13590

610

2.26

639

2.43

667

2.61

691

2.79

714

2.96

735

3.11

755

3.26

775

3.41

795

3.56

814

3.72

14695

656

2.84

683

3.02

709

3.20

732

3.40

754

3.58

775

3.76

794

3.93

813

4.09

832

4.25

—

—

15800

701

3.51

725

3.68

750

3.88

773

4.09

—

—

—

—

—

—

—

—

—

—

—

—

3.73 Nom kw Standard Motor & High Static Drive Accessory (1)
Continued
External Static Pressure (Pascals)
275.00
m3/h RPM kW

300.00
RPM

kW

325.00
RPM

kW

350.00
RPM

kW

375.00
RPM

kW

400.00
RPM

425.00

kW

RPM

450.00

475.00

kW

RPM

kW

RPM

kW

500.00
RPM

kW

3.73 Nom kw Standard Motor & High Static Drive Accessory (1)
11380

774

2.80

797

2.96

819

3.12

839

3.27

860

3.44

882

3.61

903

3.79

924

3.98

943

4.16

—

—

12485

801

3.29

823

3.47

844

3.65

865

3.83

886

4.01

905

4.18

—

—

—

—

—

—

—

—

13590

833

3.88

852

4.06

871

4.24

—

—

—

—

—

—

—

—

—

—

—

—

—

—

14695

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

15800

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

3.73 Nom kw Standard Motor & High Static Drive Accessory (2)
Note: Data includes pressure drop for filters and wet coil.

Table 27. Evaporator fan performance TS*250F downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
cfm

.20

.30

.40

.50

.60

.70

.80

.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5HP Standard Motor & Low Static Drive Accessory

5HP Standard Motor and Drive

6700

521

1.84

556

2.04

584

2.23

610

2.42

635

2.58

658

2.75

681

2.93

704

3.11

727

3.31

751

3.53

7350

566

2.39

597

2.60

625

2.82

650

3.03

674

3.23

696

3.40

717

3.59

738

3.78

759

3.98

780

4.19

8000

610

3.03

639

3.26

667

3.50

691

3.74

714

3.97

735

4.17

755

4.37

775

4.57

795

4.78

814

4.99

8650

656

3.81

683

4.06

709

4.30

732

4.56

754

4.80

775

5.05

794

5.27

813

5.48

832

5.70

—

—

9300

701

4.70

725

4.93

750

5.20

773

5.48

—

—

—

—

—

—

—

—

—

—

—

—

5HP Standard Motor & High Static Drive Accessory (1)
Continued
External Static Pressure (Inches of Water)
1.10
cfm

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5HP Standard Motor & High Static Drive Accessory (1)

6700

774

3.75

797

3.97

819

4.18

839

4.39

860

4.61

882

4.84

903

5.09

924

5.33

943

5.58

—

7350

801

4.42

823

4.66

844

4.90

865

5.13

886

5.37

905

5.60

—

—

—

—

—

—

—

—
—

8000

833

5.21

852

5.44

871

5.69

—

—

—

—

—

—

—

—

—

—

—

—

—

—

8650

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

9300

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

5HP Standard Motor & High Static Drive Accessory (2)
Note: Data includes pressure drop for filters and wet coil.

RT-PRC034-EN

47

Performance Data
Fan Performance

Table 28. Evaporator fan performance YS*155F downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00

50.00

m3/h RPM kW

RPM

kW

75.00
RPM

100.00

kW

RPM

kW

125.00
RPM

kW

150.00
RPM

kW

1.49 Nom kW Standard Motor & Low Static
Drive Accessory

175.00
RPM

kW

200.00
RPM

kW

225.00
RPM

kW

250.00
RPM

kW

1.49 Nom kw Standard Motor & High Static
Drive Accessory

7140

—

—

404

0.49

441

0.57

478

0.67

514

0.77

547

0.87

580

0.98

610

1.10

639

1.22

667

1.35

7820

391

0.52

429

0.61

463

0.69

496

0.79

530

0.90

563

1.01

593

1.12

624

1.24

652

1.37

679

1.49

8500

418

0.64

455

0.75

487

0.84

517

0.94

548

1.05

579

1.17

609

1.29

636

1.40

665

1.53

692

1.67

9180

446

0.79

481

0.91

511

1.01

540

1.11

568

1.22

596

1.34

626

1.47

653

1.60

679

1.73

705

1.86

9860

473

0.96

507

1.09

536

1.20

564

1.31

590

1.42

616

1.54

643

1.67

670

1.81

696

1.95

720

2.09

1.49 Nom kw Standard Motor Drive

2.24 Nom kw Oversized Motor & Drive

Continued
External Static Pressure (Pascals)
275.00
m3/h RPM kW

300.00
RPM

kW

325.00
RPM

350.00

kW

RPM

kW

375.00
RPM

kW

400.00
RPM

kW

425.00
RPM

1.49 Nom kw Standard Motor & High Static Drive Accessory

kW

450.00
RPM

kW

475.00
RPM

kW

500.00
RPM

kW

2.24 Nom kw Oversized Motor & Drive

7140

694

1.48

721

1.60

746

1.73

770

1.86

793

1.99

816

2.12

837

2.25

859

2.38

—

—

—

—

7820

705

1.63

731

1.77

756

1.91

780

2.05

803

2.19

826

2.33

848

2.47

—

—

—

—

—

—

8500

718

1.80

743

1.95

767

2.09

790

2.24

813

2.40

836

2.55

—

—

—

—

—

—

—

—

9180

732

2.01

756

2.15

779

2.30

802

2.45

—

—

—

—

—

—

—

—

—

—

—

—

9860

744

2.22

769

2.38

793

2.53

—

—

—

—

—

—

—

—

—

—

—

—

—

—

Note: Data includes pressure drop for filters and wet coil.

Table 29. Evaporator fan performance YS*155F downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
CFM

.20

.30

.40

.50

.60

.70

.80

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2HP Standard Motor & Low Static Drive Accessory

.90

RPM BHP

1.00

RPM BHP RPM BHP

2HP Standard Motor & High Static Drive Accessory

4200

—

—

404

0.65

441

0.77

478

0.90

514

1.03

547

1.17

580

1.32

610

1.47

639

1.63

667

1.80

4600

391

0.69

429

0.81

463

0.93

496

1.06

530

1.21

563

1.36

593

1.50

624

1.67

652

1.83

679

2.00

5000

418

0.86

455

1.00

487

1.13

517

1.26

548

1.41

579

1.57

609

1.73

636

1.88

665

2.06

692

2.24

5400

446

1.06

481

1.22

511

1.35

540

1.49

568

1.63

596

1.80

626

1.97

653

2.15

679

2.31

705

2.49

5800

473

1.28

507

1.46

536

1.61

564

1.75

590

1.90

616

2.06

643

2.24

670

2.43

696

2.62

720

2.80

2HP Standard Motor Drive

3HP Oversized Motor & Drive

Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2HP Standard Motor & High Static Drive Accessory

1.80
RPM BHP

1.90

2.00

RPM BHP RPM BHP

3HP Oversized Motor & Drive

4200

694

1.98

721

2.15

746

2.32

770

2.49

793

2.67

816

2.84

837

3.02

859

3.20

—

—

—

—

4600

705

2.18

731

2.37

756

2.56

780

2.75

803

2.94

826

3.12

848

3.31

—

—

—

—

—

—

5000

718

2.42

743

2.61

767

2.81

790

3.01

813

3.22

836

3.42

—

—

—

—

—

—

—

—

5400

732

2.69

756

2.88

779

3.08

802

3.29

—

—

—

—

—

—

—

—

—

—

—

—

5800

744

2.98

769

3.19

793

3.40

—

—

—

—

—

—

—

—

—

—

—

—

—

—

Note: Data includes pressure drop for filters and wet coil.

48

RT-PRC034-EN

Performance Data
Fan Performance

Table 30. Evaporator fan performance YS*175F downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00

50.00

75.00

100.00

125.00

150.00

175.00

200.00

225.00

250.00

m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kw Standard Motor & Low Static Drive Accy 2.24 Nom kw Standard Motor & High Static Drive Accy
7985

—

—

442

0.66

476

0.75

508

0.85

542

0.96

574

1.07

603

1.19

634

1.31

662

1.44

689

8750

437

0.72

472

0.83

503

0.92

533

1.03

563

1.14

594

1.27

623

1.39

650

1.51

678

1.64

705

1.78

9515

469

0.91

502

1.02

532

1.13

560

1.24

587

1.35

615

1.48

643

1.61

671

1.75

696

1.88

720

2.01

10280

502

1.12

533

1.25

561

1.37

588

1.48

613

1.60

638

1.72

664

1.86

690

2.01

716

2.16

740

2.30

11045

533

1.36

564

1.51

591

1.64

616

1.76

640

1.88

664

2.01

688

2.15

711

2.30

736

2.46

760

2.61

2.24 Nom kw Standard Motor Drive

1.57

3.73 Nom kw Oversized Motor & Drive

Continued
External Static Pressure (Pascals)
275.00

300.00

325.00

350.00

375.00

400.00

425.00

450.00

475.00

500.00

m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kw Standard Motor & High Static Drive Accessory
7985

715

1.71

741

1.85

765

1.99

789

2.14

812

2.28

835

2.43

856

2.57

877

2.72

898

2.86

918

3.01

8750

731

1.92

755

2.06

779

2.21

802

2.37

825

2.53

847

2.69

869

2.85

890

3.00

910

3.16

930

3.32

9515

746

2.16

771

2.32

794

2.47

817

2.62

839

2.78

860

2.95

882

3.12

902

3.30

923

3.47

943

3.64

10280

763

2.44

786

2.59

810

2.75

833

2.92

854

3.08

875

3.25

896

3.42

916

3.60

936

3.78

956

3.97

11045

783

2.77

805

2.92

826

3.07

848

3.24

870

3.42

892

3.59

912

3.77

931

3.95

951

4.13

—

—

3.73 Nom kw Oversized Motor & Drive

3.73 Nom kw Oversized Motor & High Static Drive Accessory

Note: Data includes pressure drop for filters and wet coil.

Table 31. Evaporator fan performance YS*175F downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
CFM

.20

.30

.40

.50

.60

.70

.80

.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & Low Static Drive Accessory

3HP Standard Motor & High Static Drive Accessory

4700

—

—

442

0.88

476

1.00

508

1.14

542

1.29

574

1.44

603

1.59

634

1.76

662

1.93

689

2.10

5150

437

0.97

472

1.11

503

1.24

533

1.38

563

1.53

594

1.70

623

1.86

650

2.02

678

2.20

705

2.39

5600

469

1.22

502

1.37

532

1.51

560

1.66

587

1.81

615

1.98

643

2.16

671

2.35

696

2.52

720

2.70

6050

502

1.50

533

1.68

561

1.83

588

1.99

613

2.14

638

2.31

664

2.50

690

2.70

716

2.89

740

3.08

6500

533

1.82

564

2.02

591

2.20

616

2.36

640

2.53

664

2.70

688

2.88

711

3.08

736

3.29

760

3.50

3HP Standard Motor Drive

5HP Oversized Motor & Drive

Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & High Static Drive Accessory

4700

715

2.29

741

2.48

765

2.68

789

2.87

812

3.06

835

3.25

856

3.45

877

3.64

898

3.84

918

4.03

5150

731

2.58

755

2.77

779

2.97

802

3.18

825

3.39

847

3.60

869

3.82

890

4.03

910

4.24

930

4.45

5600

746

2.90

771

3.11

794

3.31

817

3.52

839

3.73

860

3.96

882

4.19

902

4.42

923

4.65

943

4.88

6050

763

3.27

786

3.48

810

3.69

833

3.91

854

4.14

875

4.36

896

4.59

916

4.83

936

5.07

956

5.32

6500

783

3.71

805

3.92

826

4.12

848

4.35

870

4.58

892

4.82

912

5.05

931

5.29

951

5.54

—

—

5HP Oversized Motor & Drive

5HP Oversized Motor & High Static Drive Accessory

Note: Data includes pressure drop for filters and wet coil.

RT-PRC034-EN

49

Performance Data
Fan Performance

Table 32. Evaporator fan performance YS*200F downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00

50.00

m3/h RPM kW

RPM

kW

75.00
RPM

100.00

kW

RPM

kW

125.00
RPM

kW

2.24 Nom kw Standard Motor & Low Static Drive Accy

150.00
RPM

kW

175.00
RPM

kW

200.00
RPM

kW

225.00
RPM

kW

250.00
RPM

kW

2.24 Nom kw Standard Motor & High Static Drive Accy

9005

448

0.78

482

0.89

513

0.99

542

1.09

571

1.21

601

1.33

630

1.46

657

1.59

683

1.71

710

1.86

9940

487

1.02

519

1.15

548

1.26

575

1.37

601

1.48

627

1.61

655

1.75

682

1.89

707

2.03

731

2.17

10875

527

1.31

557

1.45

584

1.58

610

1.69

634

1.82

658

1.95

682

2.08

707

2.23

732

2.39

756

2.54

11810

566

1.64

595

1.80

622

1.95

646

2.08

668

2.21

691

2.34

713

2.48

735

2.63

757

2.78

780

2.95

12745

607

2.05

634

2.21

659

2.37

682

2.52

704

2.66

725

2.80

746

2.94

767

3.09

787

3.25

807

3.41

2.24 Nom kw Standard Motor Drive

3.73 Nom kw Oversized Motor & Drive

Continued
External Static Pressure (Pascals)
275.00

300.00

m3/h RPM kW

RPM

kW

325.00
RPM

350.00

kW

RPM

kW

375.00
RPM

kW

400.00
RPM

425.00

450.00

475.00

500.00

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

2.24 Nom kw Standard Motor & High Static Drive Accessory
9005

736

2.00

760

2.15

784

2.29

807

2.45

829

2.61

851

2.77

873

2.94

894

3.10

914

3.26

934

3.42

9940

755

2.31

780

2.47

803

2.62

826

2.78

847

2.95

868

3.11

889

3.28

910

3.46

930

3.64

950

3.82

10875

779

2.69

800

2.84

822

3.00

845

3.17

867

3.34

888

3.51

908

3.69

928

3.87

947

4.05

966

4.23

11810

803

3.12

825

3.29

847

3.46

866

3.62

886

3.78

907

3.96

928

4.15

—

—

—

—

—

—

12745

828

3.59

850

3.78

871

3.96

891

4.14

—

—

—

—

—

—

—

—

—

—

—

—

3.73 Nom kw Oversized Motor & Drive

3.73 Nom kw Oversized Motor & High Static Drive Accessory

Note: Data includes pressure drop for filters and wet coil.

Table 33. Evaporator fan performance YS*200F downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
CFM

.20

.30

.40

RPM BHP RPM BHP RPM BHP RPM BHP

.50

.60

.70

.80

RPM BHP RPM BHP RPM BHP

3HP Standard Motor & Low Static Drive Accessory

.90

1.00

RPM BHP RPM BHP RPM BHP

3HP Standard Motor & High Static Drive Accessory

5300

448

1.05

482

1.19

513

1.33

542

1.46

571

1.62

601

1.79

630

1.96

657

2.13

683

2.30

710

2.49

5850

487

1.37

519

1.54

548

1.68

575

1.83

601

1.99

627

2.16

655

2.35

682

2.54

707

2.72

731

2.91

6400

527

1.76

557

1.95

584

2.11

610

2.27

634

2.44

658

2.61

682

2.79

707

2.99

732

3.20

756

3.41

6950

566

2.20

595

2.41

622

2.62

646

2.79

668

2.96

691

3.14

713

3.33

735

3.52

757

3.73

780

3.96

7500

607

2.75

634

2.97

659

3.18

682

3.38

704

3.57

725

3.76

746

3.94

767

4.15

787

4.36

807

4.57

3HP Standard Motor Drive

5HP Oversized Motor & Drive

Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

RPM BHP RPM BHP RPM BHP RPM BHP

1.50

1.60

1.70

RPM BHP RPM BHP RPM BHP

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP

3HP Standard Motor & High Static Drive Accessory
5300

736

2.68

760

2.88

784

3.08

807

3.29

829

3.50

851

3.72

873

3.94

894

4.16

914

4.37

934

4.59

5850

755

3.10

780

3.31

803

3.52

826

3.73

847

3.95

868

4.17

889

4.40

910

4.64

930

4.88

950

5.12

6400

779

3.61

800

3.81

822

4.02

845

4.25

867

4.48

888

4.71

908

4.95

928

5.19

947

5.43

966

5.68

6950

803

4.19

825

4.41

847

4.63

866

4.85

886

5.07

907

5.31

928

5.56

—

—

—

—

—

—

7500

828

4.82

850

5.06

871

5.31

891

5.55

—

—

—

—

—

—

—

—

—

—

—

—

5HP Oversized Motor & Drive

5HP Oversized Motor & High Static Drive Accessory

Note: Data includes pressure drop for filters and wet coil.

50

RT-PRC034-EN

Performance Data
Fan Performance

Table 34. Evaporator fan performance YS*250F downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00

50.00

m3/h RPM kW

RPM

kW

75.00
RPM

100.00

kW

RPM

kW

125.00
RPM

kW

150.00
RPM

175.00

kW

RPM

3.73 Nom kW Standard Motor & Low Static Drive Accessory

kW

200.00
RPM

kW

225.00
RPM

kW

250.00
RPM

kW

3.73 Nom kW Standard Motor and Drive

11380

548

1.48

578

1.64

604

1.77

629

1.90

653

2.02

676

2.15

699

2.29

721

2.44

745

2.60

769

2.76

12485

596

1.93

623

2.09

649

2.25

672

2.39

694

2.53

716

2.67

737

2.81

758

2.96

778

3.12

800

3.28

13590

641

2.44

670

2.64

693

2.80

716

2.97

737

3.12

757

3.27

777

3.42

797

3.58

816

3.74

835

3.90

14695

690

3.07

717

3.27

739

3.45

760

3.64

780

3.81

799

3.97

818

4.13

—

—

—

—

—

—

15800

737

3.76

762

3.98

784

4.20

—

—

—

—

—

—

—

—

—

—

—

—

—

—

3.73 Nom kW Standard Motor & High Static Drive Accessory (1)
Continued
External Static Pressure (Pascals)
275.00

300.00

m3/h RPM kW

RPM

kW

325.00
RPM

kW

350.00
RPM

kW

375.00
RPM

kW

400.00
RPM

425.00

kW

RPM

450.00

kW

RPM

kW

475.00
RPM

kW

500.00
RPM

kW

3.73 Nom kW Standard Motor & High Static Drive Accessory (1)
11380

792

2.92

814

3.08

835

3.24

855

3.40

877

3.57

898

3.75

919

3.93

939

4.12

—

—

—

—

12485

821

3.46

843

3.64

864

3.82

885

3.99

904

4.17

—

—

—

—

—

—

—

—

—

—

13590

853

4.07

873

4.26

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

14695

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

15800

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

3.73 Nom kW Standard Motor & High Static Drive Accessory (2)
Note: Data includes pressure drop for filters and wet coil.

Table 35. Evaporator fan performance YS*250F downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
CFM

.20

.30

.40

.50

.60

.70

.80

.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5HP Standard Motor & Low Static Drive Accessory

5HP Standard Motor and Drive

6700

548

1.98

578

2.19

604

2.37

629

2.54

653

2.71

676

2.89

699

3.07

721

3.27

745

3.48

769

3.70

7350

596

2.59

623

2.81

649

3.02

672

3.21

694

3.39

716

3.58

737

3.77

758

3.97

778

4.18

800

4.40

8000

641

3.27

670

3.54

693

3.76

716

3.99

737

4.19

757

4.39

777

4.59

797

4.80

816

5.02

835

5.24

8650

690

4.12

717

4.39

739

4.63

760

4.89

780

5.11

799

5.32

818

5.54

—

—

—

—

—

—

9300

737

5.04

762

5.34

784

5.63

—

—

—

—

—

—

—

—

—

—

—

—

—

—

5HP Standard Motor & High Static Drive Accessory (1)
Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5HP Standard Motor & High Static Drive Accessory (1)

6700

792

3.92

814

4.13

835

4.34

855

4.55

877

4.79

898

5.03

919

5.28

939

5.52

—

—

—

7350

821

4.64

843

4.88

864

5.12

885

5.36

904

5.59

—

—

—

—

—

—

—

—

—

—
—

8000

853

5.46

873

5.72

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

8650

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

9300

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

5HP Standard Motor & High Static Drive Accessory (2)
Note: Data includes pressure drop for filters and wet coil.

RT-PRC034-EN

51

Performance Data
Fan Performance

Table 36. Evaporator fan performance WS*155E downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00

50.00

m3/h RPM kW

RPM

kW

75.00
RPM

100.00

kW

RPM

kW

125.00
RPM

kW

150.00
RPM

1.49 Nom kW Standard Motor & Low Static
Drive Accessory

kW

175.00
RPM

kW

200.00
RPM

kW

225.00
RPM

250.00

kW

RPM

kW

1.49 Nom kW Standard Motor & High Static
Drive Accessory

6800

346

0.35

388

0.43

426

0.51

465

0.60

502

0.70

537

0.80

570

0.91

601

1.02

631

1.14

660

1.27

7650

377

0.47

417

0.56

452

0.65

486

0.74

521

0.85

554

0.96

585

1.07

617

1.19

646

1.31

673

1.44

8500

409

0.62

448

0.73

480

0.82

512

0.92

542

1.03

574

1.15

604

1.27

632

1.38

661

1.51

689

1.65

9350

442

0.80

479

0.92

510

1.03

539

1.13

567

1.24

595

1.36

624

1.49

652

1.63

678

1.76

703

1.89

10200

475

1.01

510

1.14

541

1.27

568

1.38

594

1.50

620

1.62

645

1.74

672

1.89

698

2.04

723

2.18

1.49 Nom kW Standard Motor Drive

2.24 Nom kW Oversized Motor & Drive

Continued
External Static Pressure (Pascals)
275.00

300.00

m3/h RPM kW

RPM

kW

325.00
RPM

kW

350.00
RPM

kW

375.00
RPM

kW

400.00
RPM

kW

425.00
RPM

450.00

kW

RPM

kW

475.00
RPM

500.00

kW

RPM

kW

1.49 Nom kW Standard Motor & High Static Drive Accessory
6800

687

1.39

714

1.51

739

1.64

763

1.76

787

1.88

809

2.01

831

2.14

851

2.27

—

—

—

—

7650

700

1.57

726

1.71

751

1.85

775

1.99

799

2.13

821

2.27

843

2.40

—

—

—

—

—

—

8500

714

1.78

739

1.93

764

2.07

788

2.22

811

2.38

833

2.54

—

—

—

—

—

—

—

—

9350

730

2.03

755

2.18

779

2.33

802

2.48

—

—

—

—

—

—

—

—

—

—

—

—

10200

747

2.32

770

2.46

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

2.24 Nom kw Oversized Motor & Drive
Notes:
1. Data includes pressure drop for filters and wet coil.
2. For 200 volt, use 50 Hz reference Performance Data Table and Standard Motor & Sheave/Fan Speed (RPM) to determine applicable operating range.

Table 37. Evaporator fan performance WS*155E downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
CFM

.20

.30

.40

.50

.60

.70

.80

.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2HP Standard Motor & Low Static Drive Accessory

2HP Standard Motor & High Static Drive Accessory

4000

346

0.47

388

0.57

426

0.68

465

0.81

502

0.94

537

1.07

570

1.22

601

1.37

631

1.53

660

1.70

4500

377

0.63

417

0.75

452

0.87

486

1.00

521

1.14

554

1.29

585

1.43

617

1.60

646

1.76

673

1.93

5000

409

0.83

448

0.98

480

1.10

512

1.23

542

1.38

574

1.54

604

1.70

632

1.86

661

2.03

689

2.21

5500

442

1.07

479

1.23

510

1.38

539

1.51

567

1.66

595

1.82

624

2.00

652

2.18

678

2.36

703

2.53

6000

475

1.36

510

1.53

541

1.70

568

1.85

594

2.01

620

2.17

645

2.34

672

2.53

698

2.73

723

2.92

2HP Standard Motor Drive

3HP Oversized Motor & Drive

Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2HP Standard Motor & High Static Drive Accessory

3HP Oversized Motor & Drive

4000

687

1.86

714

2.03

739

2.19

763

2.36

787

2.53

809

2.70

831

2.87

851

3.05

—

—

—

—

4500

700

2.11

726

2.30

751

2.48

775

2.67

799

2.85

821

3.04

843

3.22

—

—

—

—

—

—

5000

714

2.39

739

2.58

764

2.78

788

2.98

811

3.19

833

3.40

—

—

—

—

—

—

—

—

5500

730

2.72

755

2.92

779

3.12

802

3.33

—

—

—

—

—

—

—

—

—

—

—

—

6000

747

3.11

770

3.30

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

—

Notes:
1. Data includes pressure drop for filters and wet coil.
2. For 200 volt, use 50 Hz reference Performance Data Table and Standard Motor & Sheave/Fan Speed (RPM) to determine applicable operating range.

52

RT-PRC034-EN

Performance Data
Fan Performance

Table 38. Evaporator fan performance WS*200E downflow or horizontal (SI)
External Static Pressure (Pascals)
25.00

50.00

m3/h RPM kW

RPM

kW

75.00
RPM

100.00

kW

RPM

125.00

kW

2.24 Nom kW Standard Motor Drive

RPM

kW

150.00
RPM

kW

175.00
RPM

kW

200.00
RPM

kW

225.00
RPM

kW

250.00
RPM

kW

2.24 Nom kw Standard Motor Drive & High Static Drive Accessory

8970

—

—

—

—

446

0.80

475

0.91

504

1.03

533

1.15

561

1.28

588

1.42

613

1.56

636

1.69

10090

—

—

449

0.94

481

1.05

510

1.18

536

1.31

561

1.44

587

1.58

611

1.72

636

1.87

660

2.03

11210

451

1.10

486

1.25

517

1.38

545

1.51

570

1.65

593

1.80

616

1.95

639

2.10

661

2.25

684

2.41

12330

491

1.45

525

1.62

554

1.77

581

1.91

605

2.06

628

2.21

649

2.38

670

2.54

691

2.71

711

2.87

13450

531

1.86

563

2.06

592

2.24

617

2.39

641

2.54

663

2.70

684

2.88

704

3.06

723

3.24

742

3.42

3.73 Nom kw Oversized Motor & Low Static Drive Accessory
Continued
External Static Pressure (Pascals)
275.00

300.00

m3/h RPM kW

RPM

kW

325.00
RPM

kW

350.00
RPM

kW

375.00
RPM

kW

400.00
RPM

kW

2.24 Nom kw Standard Motor & High Static Drive Accessory

425.00
RPM

kW

450.00
RPM

kW

475.00
RPM

kW

500.00
RPM

kW

3.73 Nom kw Oversized Motor & Drive

8970

657

1.83

678

1.97

699

2.11

721

2.26

742

2.41

762

2.57

782

2.72

801

2.87

820

3.03

837

3.18

10090

683

2.18

704

2.34

724

2.49

743

2.65

762

2.81

780

2.97

799

3.13

817

3.30

836

3.47

854

3.65

11210

706

2.57

728

2.75

749

2.92

769

3.10

787

3.27

805

3.44

822

3.62

839

3.79

856

3.97

872

4.15

12330

731

3.04

751

3.22

772

3.40

792

3.59

811

3.78

830

3.97

848

4.17

—

—

—

—

—

—

13450

760

3.60

779

3.78

798

3.96

816

4.15

—

—

—

—

—

—

—

—

—

—

—

—

3.73 Nom kw Oversized Motor & Low Static Drive Accessory
Notes:
1. Data includes pressure drop for filters and wet coil.
2. For 200 volt, use 50 Hz reference Performance Data Table and Standard Motor & Sheave/Fan Speed (RPM) to determine applicable operating range.

Table 39. Evaporator fan performance WS*200E downflow or horizontal (IP)
External Static Pressure (Inches of Water)
.10
CFM

.20

.30

.40

.50

.60

.70

.80

.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor Drive

3HP Standard Motor Drive & High Static Drive Accessory

5200

—

—

—

—

446

1.07

475

1.22

504

1.38

533

1.54

561

1.72

588

1.90

613

2.09

636

2.27

5900

—

—

449

1.26

481

1.41

510

1.58

536

1.76

561

1.94

587

2.12

611

2.31

636

2.51

660

2.72

6600

451

1.47

486

1.67

517

1.85

545

2.02

570

2.21

593

2.41

616

2.61

639

2.81

661

3.02

684

3.23

7300

491

1.95

525

2.17

554

2.38

581

2.56

605

2.76

628

2.97

649

3.19

670

3.41

691

3.63

711

3.85

8000

531

2.50

563

2.77

592

3.00

617

3.21

641

3.41

663

3.62

684

3.86

704

4.10

723

4.34

742

4.58

5HP Oversized Motor & Low Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & High Static Drive Accessory

5HP Oversized Motor & Drive

5200

657

2.45

678

2.64

699

2.84

721

3.03

742

3.24

762

3.44

782

3.65

801

3.85

820

4.06

837

4.26

5900

683

2.93

704

3.14

724

3.34

743

3.55

762

3.76

780

3.98

799

4.20

817

4.43

836

4.66

854

4.89

6600

706

3.45

728

3.68

749

3.92

769

4.15

787

4.38

805

4.62

822

4.85

839

5.09

856

5.32

872

5.57

7300

731

4.08

751

4.31

772

4.56

792

4.81

811

5.07

830

5.33

848

5.59

—

—

—

—

—

—

8000

760

4.82

779

5.07

798

5.32

816

5.57

—

—

—

—

—

—

—

—

—

—

—

—

5HP Oversized Motor & Low Static Drive Accessory
Notes:
1. Data includes pressure drop for filters and wet coil.
2. For 200 volt, use 50 Hz reference Performance Data Table and Standard Motor & Sheave/Fan Speed (RPM) to determine applicable operating range.

RT-PRC034-EN

53

Performance Data
Fan Speeds

Table 40. T/YS*155–250 standard motor and drive/fan speed (rpm)
Unit

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1Turns

Model No.

Open

Open

Open

Open

Open

Open

T/YS*155F

466

501

535

570

604

639

N/A

T/YS*175F

500

537

574

611

648

685

N/A

T/YS*200F

500

537

574

611

648

685

N/A

T/YS*250F

587

619

651

682

714

746

N/A

Closed

Notes:
1. * indicates both horizontal and downflow units
2. Factory set at 3 turns open.

Table 41. T/YS*155–250 standard motor and low static fan drive
Unit

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1Turns

Model No.

Open

Open

Open

Open

Open

Open

T/YS*155F

376

404

432

460

488

516

N/A

T/YS*175F

418

442

466

489

513

537

N/A

T/YS*200F

418

442

466

489

513

537

N/A

T/YS*250F

492

524

556

587

619

651

N/A

Closed

Note: * indicates both horizontal and downflow units

Table 42. T/YS*155–250 standard motor and high static drive accessory/fan speed (rpm)
Unit

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1Turns

Model No.

Open

Open

Open

Open

Open

Open

T/YS*155F

600

628

656

683

711

739

N/A

T/YS*175F

685

722

759

796

833

870

N/A

T/YS*200F

685

722

759

796

833

870

N/A

T/YS*250F

702

740

778

815

853

891

N/A

Closed

Note: * indicates both horizontal and downflow units

Table 43. T/YS*155–250 oversized motor and drive/fan speed (rpm)
Unit

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1Turns

Model No.

Open

Open

Open

Open

Open

Open

T/YS*155F

621

667

713

758

804

850

N/A

T/YS*175F

682

714

746

777

809

841

N/A

T/YS*200F

682

714

746

777

809

841

N/A

T/YS*250F

702

740

778

815

853

891

N/A

Closed

Note: * indicates both horizontal and downflow units

54

RT-PRC034-EN

Performance Data
Fan Speeds
\

Table 44. WS*155, 200 standard motor and drive/fan speed (rpm)
Unit

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1Turns

Model No.

Open

Open

Open

Open

Open

Open

WS*155ED, ET

416

447

478

509

540

571

N/A

WS*200ED, ET

574

611

648

685

722

759

N/A

Closed

Note: * indicates both horizontal and downflow units

Table 45. WS*155, 200 standard motor and low static fan drive
Unit

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1Turns

Model No.

Open

Open

Open

Open

Open

Open

Closed

WS*155ED

316

339

363

386

410

433

N/A

WS*200ED

418

449

480

512

543

574

N/A

Note: * indicates both horizontal and downflow units

Table 46. WS*155, 200 standard motor and high static drive accessory/fan speed (rpm)
Unit

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1Turns

Model No.

Open

Open

Open

Open

Open

Open

WS*155ED

571

602

633

663

694

725

N/A

WS*200ED

574

611

648

685

722

759

N/A

Closed

Note: * indicates both horizontal and downflow units

Table 47. WS*155, 200 oversized motor and drive/fan speed (rpm)
Unit

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1Turns

Model No.

Open

Open

Open

Open

Open

Open

WS*155ED

621

667

698

728

759

850

N/A

WS*200ED

702

740

777

814

851

891

N/A

Closed

Note: * indicates both horizontal and downflow units

RT-PRC034-EN

55

Performance Data
Static Pressure Drop

Table 48. T/YS*155–250—static pressure drops through accessories—pascals
Economizer
with OA/RA Dampers(a)

Electric Heater - Nom kW(b)

Unit
Model No.

Airflow
m3/h

Standard
Filters

100% OA

100% RA

5-12

14-27

33-41

D155

7140

6

8

5

7

9

10

—

D155

8500

9

11

7

9

12

15

—

D155

9860

12

15

10

12

16

20

—

H155

7140

6

8

5

7

9

10

—

H155

8500

9

11

7

9

12

15

—

H155

9860

12

15

10

12

16

20

—

D175

7985

7

10

7

8

10

13

—

D175

9515

11

14

9

12

15

18

—

D175

11045

14

18

12

16

20

24

—

H175

7985

7

10

7

8

10

13

—

H175

9515

11

14

9

12

15

18

—

H175

11045

14

18

12

16

20

24

—

D200

9005

12

29

6

—

11

14

16

D200

10875

18

42

9

—

16

21

23

D200

12745

24

57

13

—

22

29

31

H200

9005

10

33

6

—

11

14

16

H200

10875

15

48

9

—

16

21

23

H200

12745

21

66

13

—

22

29

31

D250

11380

20

46

9

—

17

22

25

D250

13590

28

66

13

—

24

31

36

D250

15800

38

89

18

—

33

42

49

H250

11380

16

52

9

—

17

22

25

H250

13590

23

75

13

—

24

31

36

H250

15800

31

101

18

—

33

42

49

45-54

(a) OA = Outside Air, RA = Return Air
(b) Nominal kW ratings are at 415 V. Not all Heater sizes may be available.
* Indicates both horizontal and downflow units.

56

RT-PRC034-EN

Performance Data
Static Pressure Drop

Table 49. T/YS*155–250—static pressure drops through accessories—(inches water column)
Economizer
with OA/RA Dampers(a)

Electric Heater - Nom kW(b)

Unit
Model No.

Airflow
CFM

Standard
Filters

100% OA

100% RA

5-12

14-27

33-41

45-54

D155

4200

0.02

0.03

0.02

0.03

0.03

0.04

—

D155

5000

0.04

0.05

0.03

0.04

0.05

0.06

—

D155

5800

0.05

0.06

0.04

0.05

0.07

0.08

—

H155

4200

0.02

0.03

0.02

0.03

0.03

0.04

—

H155

5000

0.04

0.05

0.03

0.04

0.05

0.06

—

H155

5800

0.05

0.06

0.04

0.05

0.07

0.08

—

D175

4700

0.03

0.04

0.03

0.03

0.04

0.05

—

D175

5600

0.04

0.06

0.04

0.05

0.06

0.07

—

D175

6500

0.06

0.07

0.05

0.06

0.08

0.10

—

H175

4700

0.03

0.04

0.03

0.03

0.04

0.05

—

H175

5600

0.04

0.06

0.04

0.05

0.06

0.07

—

H175

6500

0.06

0.07

0.05

0.06

0.08

0.10

—

D200

5300

0.05

0.11

0.03

—

0.04

0.06

0.06

D200

6400

0.07

0.17

0.04

—

0.06

0.08

0.09

D200

7500

0.10

0.23

0.05

—

0.09

0.11

0.13

H200

5300

0.04

0.13

0.03

—

0.04

0.06

0.06

H200

6400

0.06

0.19

0.04

—

0.06

0.08

0.09

H200

7500

0.08

0.26

0.05

—

0.09

0.11

0.13

D250

6700

0.08

0.19

0.04

—

0.07

0.09

0.10

D250

8000

0.11

0.27

0.05

—

0.10

0.12

0.15

D250

9300

0.15

0.36

0.07

—

0.13

0.17

0.20

H250

6700

0.06

0.21

0.04

—

0.07

0.09

0.10

H250

8000

0.09

0.30

0.05

—

0.10

0.12

0.15

H250

9300

0.13

0.40

0.07

—

0.13

0.17

0.20

(a) OA = Outside Air, RA = Return Air
(b) Nominal kW ratings are at 415 V. Not all Heater sizes may be available.
* Indicates both horizontal and downflow units.

RT-PRC034-EN

57

Performance Data
Static Pressure Drop

Table 50. WS*155, 200—static pressure drops through accessories—pascals
Economizer
with OA/RA Dampers(a)

Electric Heater - Nom kW(b)

Unit
Model No.

Airflow
m3/h

Standard
Filters

100% OA

100% RA

5-14

16-27

33-41

45-54

D155

6800

6

45

5

7

7

10

—

D155

8500

8

62

5

10

12

15

—

D155

10200

11

87

7

17

20

22

—

H155

6800

6

45

5

7

7

10

—
—

H155

8500

8

62

5

10

12

15

H155

10200

11

87

7

17

20

22

—

D200

8970

8

37

5

—

10

12

15

D200

11210

14

57

7

—

17

20

22

D200

13450

19

77

12

—

25

27

35

H200

8970

8

50

7

—

12

15

17

H200

11210

15

75

10

—

22

27

32

H200

13450

24

124

17

—

37

42

52

(a) OA = Outside Air, RA = Return Ai
(b) Nominal kW ratings are at a 415 V
* Indicates both horizontal and downflow units.

Table 51. WS*155, 200—static pressure drops through accessories—(inches water column)
Economizer
with OA/RA Dampers(a)

Electric Heater - Nom kW(b)

Unit
Model No.

Airflow
CFM

Standard
Filters

100% OA

100% RA

5-14

16-27

33-41

45-54

D155

4000

0.02

0.18

0.02

0.03

0.03

0.04

—

D155

5000

0.03

0.25

0.02

0.04

0.05

0.06

—

D155

6000

0.05

0.35

0.03

0.07

0.08

0.09

—

H155

4000

0.02

0.18

0.02

0.03

0.03

0.04

—

H155

5000

0.03

0.25

0.02

0.04

0.05

0.06

—

H155

6000

0.05

0.35

0.03

0.07

0.08

0.09

—

D200

5200

0.03

0.15

0.02

—

0.04

0.05

0.06

D200

6600

0.05

0.23

0.03

—

0.07

0.08

0.09

D200

8000

0.07

0.31

0.05

—

0.10

0.11

0.14

H200

5200

0.03

0.20

0.03

—

0.05

0.06

0.07

H200

6600

0.06

0.30

0.04

—

0.09

0.11

0.13

H200

8000

0.10

0.50

0.07

—

0.15

0.17

0.21

(a) OA = Outside Air, RA = Return Ai
(b) Nominal kW ratings are at a 415 V
* Indicates both horizontal and downflow units.

58

RT-PRC034-EN

Controls
ReliaTel Controlled Units
Note: Zone sensor required for units configured for Single Zone VAV indoor fan system control
to enable Single Zone VAV functionality.
Zone Sensors are the building occupant’s comfort control devices. They replace the conventional
electro-mechanical thermostats. The following zone sensor options are available for Voyager units:

Differential Enthalpy
Differential Enthalphy Replaces the standard dry bulb control with two enthalpy sensors that
compare total heat content of the indoor air and outdoor air to determine the most efficient air
source. This control option offers the highest level of comfort control, plus energy efficiency,
available.

Differential Pressure Switches
This factory or field-installed option allows individual fan failure and dirty filter indication. The fan
failure switch will disable all unit functions and “flash” the Service LED on the zone sensor. The dirty
filter switch will light the Service LED on the zone sensor and will allow continued unit operation.

Manual Changeover

Manual/Automatic
Changeover

Manual/Automatic
Changeover

Heat, Cool or Off System
Switch. Fan Auto or Off Switch.
One temperature setpoint
lever.

Auto, Heat, Cool or Off
System Switch. Fan Auto or
Off Switch. Two temperature
setpoint levers.

Auto, Heat, Cool or Off
System Switch. Fan Auto or
Off Switch. Two temperature
setpoint levers. Status
Indication LED lights, System
On, Heat, Cool, or Service.

RA Remote Sensor & Room Remote Sensor
The RA Remote Sensor is a Return Air Remote Sensor which can be mounted in the return air duct
to report return air temperature. The Room Remote Sensor is a Space Remote Sensor which can
be mounted on the wall to report/control from a remote location in the space.

Wireless Zone Sensor
LCD display that provides heat, cool, auto, or off. Includes
two temperature setpoints and a lockable setting with °F or
°C indicators.

RT-PRC034-EN

59

Controls

60

Manual/Automatic
Changeover

Remote Sensor

Integrated Comfort™
System

Auto, Heat, Cool or Off System
Switch. Fan Auto or Off Switch.
Two temperature setpoint
levers.

Sensor(s) available for all
zone sensors to provide
remote sensing capabilities.

Sensor(s) available with
optional temperature
adjustment and override
buttons to provide central
control through a Trane
Integrated Comfort™
system.

Programmable Night
Setback

CO2 Sensing

Humidity Sensor

Auto or manual changeover
with seven-day programming.
Keyboard selection of Heat,
Cool, Fan, Auto, or On. All
programmable sensors have
System On, Heat, Cool, Service
LED/indicators as standard.
Night Setback Sensors have
one (1) Occupied, one (1) Unoccupied, and one (1) Override
program per day.

The CO2 sensor shall have the
ability to monitor space
occupancy levels within the
building by measuring the
parts per million of CO2
(Carbon Dioxide) in the air. As
the CO2 levels increase, the
outside air damper modulates
to meet the CO2 space
ventilation requirements. The
CO2 accessory shall be
available as field installed.

Field installed, wall-mounted
or duct-mounted humidity
sensor is used to control
activation of the hot gas
reheat dehumidification
option. The humidity sensor
can be set for humidity levels
between 40 percent and
60 percent relative humidity
by adjusting the ReliaTel
Options Module.

RT-PRC034-EN

Controls

Digital Display
Programmable
Thermostat with BuiltIn Relative Humidity
Sensing (3H/2C)

Digital Display
Programmable
Thermostat (3H/2C)

Touchscreen
Programmable
Thermostat (2H/2C)

Tue
MON

TUE

WED

THU

FRI

SAT

FAN
ON
AUTO
CIRC

Three Heat/Two Cool digital
display thermostat with builtin humidity control and
display. This thermostat
combines both humidity and
dry bulb into one. Fully
programmable with night
setback.

Two Heat/Two Cool auto
changeover digital display
thermostat. Seven-day
programmable stat with night
setback shall be available.

SUN

HEAT

SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO

RESET

DONE

EDIT

CANCEL
PERIOD

DEHUMIDIFIER

COOL

PM

WAKE

LEAVE

RETURN

SLEEP

CANCEL

Two Heat/Two Cool
programmable thermostat
with touch screen digital
display. Menu-driven
programming. Effortless setup. Program each day
separately with no need to
copy multiple days. All
programming can be done on
one screen. Easy to read and
use. Large, clear backlit digital
display.

Digital Display Thermostat (3H/2C)
Three Heat, Two Cool auto changeover digital display
thermostat.

Remote Potentiometer
Minimum position setting of economizer can be remotely adjusted with this accessory.

Trane Communication Interface (TCI)
This factory or field-installed micro-processor interface allows the unit to communicate to Trane’s
Integrated Comfort™ system.Economizer Controls
The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two
optional controls, Enthalpy and Differential Enthalpy Control.

Enthalpy Control
Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable
setpoint. Enthalpy control offers a higher level of comfort control, along with energy savings
potential, than the standard dry bulb control. This is due to the additional wet bulb sensing
capability.

RT-PRC034-EN

61

Electrical Data
Table 52. TS* auxiliary electric heat capacity

No. of Stages

Stage 1
heater
kW(1)

Stage 2
heater
kW(1)

2

13.4

13.4

26.9

2

13.4

13.4

40.3

2

26.9

13.4

26.9

2

13.4

13.4

40.3

2

26.9

13.4

53.8

2

26.9

26.9

Unit Model No.

Total heater
kW(1)(2)

TS*155FD

26.9

TS*175FD
TS*200FD
TS*250FD

Notes:
1. Heaters are rated at 415 V. For other than rated voltage, apply the following formula - kW =
(Required Voltage/415)2 x Rated kW.
2. Not all Heater Models are available.
3. To calculate temperature rise across the electric heat use the following formulas:
Temp Rise Across Electric Heater - °C = 2982 * Heater Capacity (kW)/Airflow (m3/h)
Temp Rise Across Electric Heater - °F = 3160 * Heater Capacity (kW)/Airflow (cfm)

Table 53. TS* electric heater voltage correction factors (apply to auxiliary electric heat capacity)
Nominal
Voltage

Distribution
Voltage

Capacity
Multiplier

380

0.84

415

400

0.93

415

1.00

Table 54. TS* unit wiring
Unit Model

Voltage

Standard Indoor
Fan Motor—MCA

Oversize Indoor
Fan Motor—MCA

TS*155FD

380–415

41.0

44.0

TS*175FD

380–415

51.0

54.0

TS*200FD

380–415

56.0

59.0

TS*250FD

380–415

65.0

—

Table 55. TS* unit wiring with electric heat (single point connection)
Unit Model to
Use With

Heater kW
Rating

Unit Supply
Power

Control
Stages

Standard Indoor Oversized Motor
Motor MCA
MCA

TS*155ED

11.3–13.5

380–415/50/3

1

41/41

44/44

TS*155FD

22.6–26.9

380–415/50/3

2

49/53

53/57

TS*155FD

33.8–40.4

380–415/50/3

2

71/77

74/80

TS*175FD

22.6–26.9

380–415/50/3

2

53/57

57/61

TS*175FD

33.8–40.4

380–415/50/3

2

74/80

79/84

TS*200FD

22.6–26.9

380–415/50/3

2

56/57

59/61

TS*200FD

33.8–40.4

380–415/50/3

2

74/80

79/84

TS*200FD

45.1–53.8

380–415/50/3

2

96/104

100/108

TS*250FD

22.6–26.9

380–415/50/3

2

65/65

—

TS*250FD

33.8–40.4

380–415/50/3

2

79/84

—

TS*250FD

45.1–53.8

380–415/50/3

2

100/108

—

Note: * All units to be installed under local codes.

62

RT-PRC034-EN

Electrical Data

Table 56. TS* electric characteristics—evaporator fan motor—50 cycle
Standard Evaporator Motor
Model

No.
Motors

Volts

Ph

Watts

FLA

Oversize Evaporator Motor
Service No.
LRA Factor Motors

Volts

Ph

Watts

FLA

LRA

Service
Factor

TS*155FD

1

380–415

3

1500

4.6

36.4

1.15

1

380–415

3

2200

6.5

57

1.15

TS*175FD

1

380–415

3

2200

6.5

57.0

1.15

1

380–415

3

3700

7.4

71.9

1.15

TS*200FD

1

380–415

3

2200

6.5

57.0

1.15

1

380–415

3

3700

7.0

65.1

1.15

TS*250FD

1

380–415

3

3700

7.4

71.9

1.15

—

—

—

—

—

—

—

Table 57. TS* electric characteristics—compressor motor and condenser motor—50 cycle
Compressor Motors

Condenser Fan Motors
Amps(a)

Ampsa

Unit Model No.

No.

Volts

Ph

Watts

rpm

RLA

LRA

No.

Ph

Watts

FLA

LRA

TS*155FD

2

380–415/50

3

/4610

2900

17

142

2

1

300

1.6

3.8

TS*175FD

2

380–415/50

3

/4460

2900

21.4

142

2

1

560

2.5

5.8

TS*200FD

2

380–415/50

3

2900

22.1

147

2

1

560

2.5

5.8

TS*250FD

2

380–415/50

3

2900

21.4

142

2

1

665

2.5

5.8

(a) For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
*Indicates both downflow and horizontal units.

Table 58. YS* unit wiring
Unit Model

Voltage

YS*155FD

380–415

Standard Indoor Fan Motor—MCA Oversize Indoor Fan Motor—MCA
41.0

44.0

YS*175FD

380–415

51.0

54.0

YS*200FD

380–415

56.0

59.0

YS*250FD

380–415

65.0

—

Table 59. YS* electric characteristics—evaporator fan motor—50 cycle
Standard Evaporator Motor
Model

No.
Motors

Volts

Ph

Watts

FLA

Oversize Evaporator Motor

Service No.
LRA Factor Motors

Volts

Ph

Watts

FLA

LRA

Service
Factor

YS*155FD

1

380–415

3

1500

4.6

36.4

1.15

1

380/415

3

2200

6.5

57

1.15

YS*175FD

1

380–415

3

2200

6.5

57.0

1.15

1

380/415

3

3700

7.4

71.9

1.15

YS*200FD

1

380–415

3

2200

6.5

57.0

1.15

1

380/415

3

3700

7.0

65.1

1.15

YS*250FD

1

380–415

3

3700

7.4

71.9

1.15

—

—

—

—

—

—

—

Table 60. YS* electric characteristics—compressor motor and condenser motor—50 cycle
Compressor Motors

Condenser Fan Motors
Amps(a)

Ampsa

Unit Model No.

No.

Volts

Ph

Watts

rpm

RLA

LRA

No.

Ph

Watts

FLA

LRA

YS*155FD

2

380–415/50

3

/4610

2900

17

142

2

1

300

1.6

3.8

YS*175FD

2

380–415/50

3

/4460

2900

21.4

142

2

1

560

2.5

5.8

YS*200FD

2

380–415/50

3

2900

22.1

147

2

1

560

2.5

5.8

YS*250FD

2

380–415/50

3

2900

21.4

142

2

1

665

2.5

5.8

(a) For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
*Indicates both downflow and horizontal units.

RT-PRC034-EN

63

Electrical Data

Table 61. YS* electrical characteristics—combustion blower motor
Model

Heat

Heating
Stages

Watts

RPM

Volts

Phase

FLA

YS*155FD

Low

2

75

3500/3000

230

1

0.8

2.0

YS*155FD

High

2

75

3500/3000

230

1

0.6

1.5

YS*175FD

Low

2

75

3500/3000

230

1

0.8

2.0

YS*175FD

High

2

75

3500/3000

230

1

0.6

1.5

YS*200FD

Low

2

75

3500/3000

230

1

0.8

2.0

YS*200FD

High

2

75

3500/3000

230

1

0.6

1.5

YS*250FD

Low

2

75

3500/3000

230

1

0.8

2.0

YS*250FD

High

2

75

3500/3000

230

1

0.6

1.5

LRA

Table 62. WS* auxiliary electric heat capacity
Total heater
kW(1)(2)

Unit Model No.

Stage 1
Stage 2
heater kW(1) heater kW(1)

No. of Stages

WS*155ED

40.3

2

26.9

13.4

WS*155ET

37.5

2

25.0

12.5

26.9

2

13.4

13.4

40.3

2

26.9

13.4

53.8

2

26.9

26.9

25.0

1

25.0

—

37.5

2

25.0

12.5

50.0

2

25.0

25.0

WS*200ED

WS*200ET

Notes:
1. Heaters are rated at 415 V. For other than rated voltage, apply the following formula - kW = (Required
Voltage/415)2 x Rated kW.
2. Not all Heater Models are available.
3. To calculate temperature rise across the electric heat use the following formulas:
Temp Rise Across Electric Heater - °C = 2982 * Heater Capacity (kW)/Airflow (m3/h)
Temp Rise Across Electric Heater - °F = 3160 * Heater Capacity (kW)/Airflow (cfm)

Table 63. WS* electric heater voltage correction factors (apply to auxiliary electric heat capacity)
Nominal Voltage

Distribution Voltage

Capacity Multiplier

200

200

1.00

380

0.84

400

0.93

415

1.00

415

Table 64. WS* unit wiring
MCA

64

Standard Indoor
Fan Motor—MCA

Oversize Indoor
Fan Motor—MCA
43.0

Unit Model

Voltage

WS*155ED

380–415/50/3

40.0

WS*155ET

200/50/3

83.0

—

WS*200ED

380–415/50/3

59.0

62.0

WS*200ET

200/50/3

115.0

—

RT-PRC034-EN

Electrical Data

Table 65. WS* unit wiring with electric heat (single point connection)
MCA
Models

Heater kW Rating

Unit Supply Power

Control
Stages

Standard Indoor
Motor MCA

Oversized Motor MCA

22.6–26.9

380–415/50/3

1

60–63

64–66

33.8–40.4

380–415/50/3

2

83–87

86–90

45.1–53.8

380–415/50/3

2

104–110

107–113

12.5

200/50/3

1

128

—

25.0

200/50/3

1

173

—

WS*155ED

WS*155ET

WS*200ED

37.5

200/50/3

2

219

—

22.6–26.9

380–415/50/3

2

102–105

105–109

33.8–40.4

380–415/50/3

2

123–129

126–132

45.1–53.8

380–415/50/3

2

144–152

148–156

25.0

200/50/3

1

206

—

37.5

200/50/3

2

251

—

50.0

200/50/3

2

296

—

WS*200ET

Note: * All units to be installed under local codes.

Table 66. WS* electric characteristics—evaporator fan motor—50 cycle
Standard Evaporator Motor
No.
Motors

Volts

WS*155ED

1

380–415/50/3

3

WS*155ET

1

200/50/3

3

WS*200ED

1

380–415/50/3

3

WS*200ET

1

200/50/3

3

Model

Ph

Watts

Oversize Evaporator Motor
Service No.
Factor Motors

Ph

Watts

FLA

LRA

Service
Factor

380–415/50/3

3

2200

5.7

57.0

1.5

—

—

—

—

—

—

1

380–415/50/3

3

3700

7.4

71.9

1.15

—

—

—

—

—

—

—

FLA

LRA

1500

4.6

36.4

1.15

1

2200

10.8

108

1.5

—

2200

5.7

57.0

1.5

3700

16.6

120

1.15

Volts

Table 67. WS* electric characteristics—compressor motor and condenser motor—50 cycle
Compressor Motors

Condenser Fan Motors
Amps(a)

Unit Model No.

Ph

Watts

rpm

RLA

LRA

Ampsa

No.

Volts

No.

Ph

Watts

FLA

LRA

WS*155ED

2

380–415/50

3

6400

2900

14

101

2

1

300

1.6

3.8

WS*155ET

2

200/50

3

6400

2900

28

179

2

1

300

2.6

8.7

WS*200ED

2

380–415/50

3

2900

19.9

142

2

1

665

2.5

5.8

WS*200ET

2

200/50

3

2900

43

267

2

1

665

4.4

14.8

(a) For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
*Indicates both downflow and horizontal units.

RT-PRC034-EN

65

Typical Wiring
Figure 2. TS*155F–250F

66

RT-PRC034-EN

Typical Wiring

Figure 2. (continued from previous page) TS*155F–250F

**

RT-PRC034-EN

67

Typical Wiring

Figure 3. TS*200F–250F

68

RT-PRC034-EN

Typical Wiring

\

Figure 3. (continued from previous page) TS*200F–250F

**

RT-PRC034-EN

69

70

13

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

2P
(BL)
W6

1P
(RD)
W5

12

L2

2A,
2B,
2C,

L1

HTB1

1B(RD)

2B(BL)

3B(BK)

1A(RD)

2A(BL)

3A(BK)

3A,
3B,
3D
3P
(BK)

L3

LINE VOLTAGE

1A,
1B,
1D,

11

10

9

8

7

6

5

4

3

2

1

1D(RD)

2C(BL)

3D(BK)

1P

2P

3P

PHM

L1

L2

L3

1E(RD)

1D ,E
(RD)

1C(RD)

1B ,C(RD)

BLACK

BLACK

CC1

F

F

CC1
T1

T2

T1

T2

T1

T2
CC2
22 A,B
(RD)

21A(BL)

BLACK

10A ,B(RD)

5A(BL)

9A(RD)

8A(BL)

BLACK

GREEN

CCH2

L1

L2

CC2

GREEN

CCH1

L1

L2

L1

L2

FAILURE TO DO SO MAY CAUSE DAMAGE TO THE
EQUIPMENT.

UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
OTHER TYPES OF CONDUCTORS.

USE COPPER CONDUCTORS ONLY!

CAUTION

22B(RD)

10B(RD)

9A(RD)

8A(BL)

3A(BK)

9

22A(RD)

21A(BL)

3D(BK)

10A(RD)

5A(BL)

3B(BK)

9B(RD)

8B(BL)

3
FTB-C
8
FTB-D

3C(BK)

FTB-B

T1

T2

T3

T1

T2

T3

11

L1

L2

L3

NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.

COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARAIBLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÎNEMENT POUR
DÉCHARGER LES CONDENSATEURS.

DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
AND FOLLOW LOCK OUT AND TAG
PROCEDURES BEFORE SERVICING.
INSURE THAT ALL MOTOR
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
TO DRIVE INSTRUCTIONS FOR
CAPACITOR DISCHARGE.

CPR2

CPR1

IDM

AVERTISSEMENT

EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÍA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.

DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON EJE DE
DIRECCIÓN DE VELOCIDAD VARIABLE,
CONSULTE LAS INSTRUCCIONES PARA LA
DESCARGA DEL CONDENSADOR.

iVOLTAJE PELIGROSO!

ADVERTENCIA

SI NO LO HACE, PUEDE OCASIONAR DAÑO AL EQUIPO.

LAS TERMINALES DE LA UNIDAD NO ESTÁN DISEÑADAS
PARA ACEPTAR OTROS TIPOS DE CONDUCTORES.

TENSION DANGEREUSE!

FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
IN DEATH OR SERIOUS INJURY.

ATTENTION
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!

HAZARDOUS VOLTAGE!

WARNING

L'UTILISATION DE TOUT AUTRE CONDUCTEUR PEUT
ENDOMMAGER L'ÉQUIPEMENT.

LES BORNES DE L'UNITÉ NE SONT PAS CONÇUES
POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS.

N'UTILISER QUE DES CONDUCTEURS EN CUIVRE!

PRECAUCIÓN

LEGEND

OUTDOOR MOTOR CAPACITOR

FAN TERMINAL BLOCK
GAS VALVE

LOW PRESSURE CONTROL
OUTDOOR AIR SENSOR

RETURN HUMIDITY SENSOR

PHASE MONITOR

COMBUSTION FAN MOTOR PLUG

PPF11,PPM11

IGNITION CONTROL PLUG
IGNITER PLUG

PPF4,PPM4

PPF3

ECONOMIZER PLUG

THERMOSTAT DISCHARGE LINE CKT 2

TDL2
PPF6,PPM6

THERMOSTAT DISCHARGE LINE CKT 1

TDL1

ZONE SENSOR MODULE

EXHAUST FAN RELAY
ZSM

XFR

SPACE HUMIDITY SENSOR

SHS

PHM

REHEAT VALVE

CONTROL POWER TRANSFORMER
IGNITION TRANSFORMER
RHV

TNS1
TNS2

FAN FAILURE LIMIT

HIGH LIMIT CUTOUT
TCO2

TIMED OVERIDE

TIOR

TRANE COMMUNICATION INTERFACE

SUPPLY HIGH TEMPERATURE

TCO1

TCI

SHT

REMOTE MINIMUM POSITION
SUPPLY AIR SENSOR

RMP

RETURN HIGH TEMPERATURE
SAS

RHT

RHS

RAS

OUTDOOR FAN MOTOR
OUTDOOR FAN RELAY
RETURN AIR SENSOR

ODF1,ODF2

ODM1,ODM2

OUTDOOR HUMIDITY SENSOR

OAS
OHS

LPC3

50
64

41-46

50

50,75

90-102

80

99

13-15

81

71

41

58

72

72

69

63

66

91

98

66

98

96

69,68,34,38

33,37

100

70

71

78,80

IGNITION PROBE
LOW VOLTAGE TERM BLOCK
LOW PRESSURE CONTROL

LTB

74,50

17

10

64,65

76

16,17,18

17,18

100

93

91

21,26

98

41,42

43

33,37

23,28

64,65

91

LINE
NUMBER

LPC1,LPC2

IP

HI VOLTAGE TERMINAL BLOCK
INDOOR FAN MOTOR
IGNITION CONTROL MODULE

IDM
IGN

HTB1

HIGH PRESSURE CONTROL

GV
HPC1,HPC2

FTB

COMMUNICATION MODULE

RELIATEL REFRIGERATION MODULE

RELIATEL OPTIONS MODULE
COMM

RTRM

RTOM

ECONOMIZER ACTUATOR
FAN FAILURE SWITCH
INDOOR FAN CONTACTOR

DISCHARGE TEMPERATURE SENSOR

DTS
ECA
FFS
F

EXHAUST FAN RELAY

EXF

COMPRESSOR

CLOGGED FILTER SWITCH

CFS
CPR1,CPR2

COMBUSTION FAN RELAY

COMBUSTION FAN MOTOR

CFR

CFM

CF1,CF2

COMPRESSOR CONTACTOR
CRANKCASE HEATER

CC1,CC2

BUILDING MANAGEMENT SYSTEM

DESCRIPTION

CCH1,CCH2

BMS

DEVICE
DESIGNATION

Typical Wiring

Figure 4. YS*155F–250F

RT-PRC034-EN

RT-PRC034-EN

60

59

58

57

56

55

54

53

52

51

50

49

48

47

46

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

W6 (BL)

W5, 6K ,D(RD)

W13(RD)

12B,C(BL)

6D(RD)

12B,

14F (GR)

14G(WH)
14F(GR)

X2

H1

13C
(BK)

X1
115V

12B,C(BL)

Y1
230V

14C
(GR)

14G (WH)

13C (BK)

Y2

CC2
T3

T3

TNS2

L2

L1

IGN

12C(BL)

S2

S1

SPLICE

31A,C,D ,E(RD)

6D(RD), 6E(PR)

24V

460V
400V

LINE 61

COM

17F (RD)

16F (RD)

L1
CBM

TNS1

7

1

ODF1

CF2

CF1

36B,J,W

112A(BK)

CFR

107B(RD)

109A(RD)

W34(PR)

575V

HI

IGN
LO

MARKED TERMINAL FOR
10MFD CAPACITORS ONLY

107A(RD)

26C(BK)

W13, 6K (RD)

W14(RD)

8

(BK)

4C(BK)

W28 ,26C

W28,

415V
H3 575V

L3

L3

CC1

W34(PR)
14C(GR)

(BL)

380V
H2 460V

12J

12B ,J, W6 (BL)

W5, 6K ,D(RD), 6C(PR)

MARKED TERMINAL FOR
10MFD CAPACITORS ONLY

CFR

3

TAN

PPM4-2

TAN

110A(PR)

PPF11-4

PPF11-3

IP

PPF11-1

4

113A(OR)

RED

PURPLE
PPM11-1

BROWN

BROWN

BLACK
PPM11-4

ORANGE
PPM11-3

PPM11-2

ODM2

ODM1

PPF11-2

108A(RD)
CFR

112B(BK)

2

PPM4-1

,36V(GR)

PPF4-2

(BL)

1
112A,B(BK)

PPF4-1

110A,
W34
(PR)

3

15A(BK)

11A(BR)

6E(PR)

4C(BK)

7A(BR)

6C(PR)

CFM

GREEN/YELLOW

F).

BLUE
BROWN
GREEN
ORANGE

BR
GR
OR

BLACK

COLOR

YELLOW
YL

TAN

WHITE
WH
TN

RED

PURPLE
RD

PR

ABBR

WIRE COLOR DESIGNATION

BL

BK

ABBR

COLOR

CONNECTIONS SHOWN ARE FOR 460V/60HZ/3PH OR 380V/
50HZ/3PH. WHEN 575V/60HZ/3PH OR 415V/50HZ/3PH
UNIT OPERATION IS REQUIRED, REMOVE WIRES 12B,C(BL)
FROM H2 TERMINAL ON TNS2, AND CONNECT TO H3
TERMINAL ON TNS2

CONNECTIONS SHOWN ARE FOR 460V/60HZ/3PH OR 380-415V/
50HZ/3PH. WHEN 575V/60HZ/3PH UNIT OPERATION IS
REQUIRED, REMOVE WIRE 12C(BL) FROM 460V/400V
TERMINAL ON TNS1 AND CONNECT TO 575V TERMINAL ON TNS1.

THREE PHASE MOTORS ARE PROTECTED UNDER PRIMARY
SINGLE PHASING CONDITIONS. ALL MOTORS HAVE
INTERNAL OVERLOAD PROTECTION. COMPRESSORS HAVE
INTERNAL THERMAL PROTECTION.

NUMBERS ALONG THE RIGHT SIDE OF THE SCHEMATIC
DESIGNATE THE LOCATION OF CONTACTS BY LINE NUMBER.
AN UNDERLINED NUMBER INDICATES A NORMALLY CLOSED
CONTACT.

DASHED LINES INDICATE RECOMMENDED FIELD WIRING
BY OTHERS. DASHED LINE ENCLOSURES AND/OR DASHED
DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY
THE FIELD. PHANTOM LINE ENCLOSURES INDICATE
ALTERNATE CIRCUITRY OR AVAILABLE SALES OPTIONS.

UNLESS OTHERWISE NOTED ALL SWITCHES ARE SHOWN
AT 25 C (77 F), AT ATMOSPHERIC PRESSURE.
AT 50% RELATIVE HUMIDITY, WITH ALL UTILITIES
TURNED OFF, AND AFTER A NORMAL SHUTDOWN HAS
C (77
OCCURED. ALL THERMISTORS ARE 10K AT 25

11 TERMINALS MAY NOT BE PRESENT.

8

7

4

3

2

1

NOTES:

Typical Wiring

Figure 4. (continued from previous page) YS*155F–250F
11 X 17 METAL PLATE

71

72

13

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

2P
(BL)
W6

1P
(RD)
W5

12

L2

2A,
2B,
2C,

L1

HTB1

1B(RD)

2B(BL)

3B(BK)

1A(RD)

2A(BL)

3A(BK)

3A,
3B,
3D
3P
(BK)

L3

LINE VOLTAGE

1A,
1B,
1D,

11

10

9

8

7

6

5

4

3

2

1

1D(RD)

2C(BL)

3D(BK)

1P

2P

3P

PHM

L1

L2

L3

1E(RD)

1D ,E
(RD)

1C(RD)

1B ,C(RD)

BLACK

BLACK

CC1

F

F

CC1
T1

T2

T1

T2

T1

T2
CC2
22 A,B
(RD)

21A(BL)

BLACK

10A ,B(RD)

5A(BL)

9A(RD)

8A(BL)

BLACK

GREEN

CCH2

L1

L2

CC2

GREEN

CCH1

L1

L2

L1

L2

FAILURE TO DO SO MAY CAUSE DAMAGE TO THE
EQUIPMENT.

UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
OTHER TYPES OF CONDUCTORS.

USE COPPER CONDUCTORS ONLY!

CAUTION

22B(RD)

10B(RD)

9A(RD)

8A(BL)

3A(BK)

9

22A(RD)

21A(BL)

3D(BK)

10A(RD)

5A(BL)

3B(BK)

9B(RD)

8B(BL)

3
FTB-C
8
FTB-D

3C(BK)

FTB-B

T1

T2

T3

T1

T2

T3

11

L1

L2

L3

NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.

COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARAIBLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÎNEMENT POUR
DÉCHARGER LES CONDENSATEURS.

DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
AND FOLLOW LOCK OUT AND TAG
PROCEDURES BEFORE SERVICING.
INSURE THAT ALL MOTOR
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
TO DRIVE INSTRUCTIONS FOR
CAPACITOR DISCHARGE.

CPR2

CPR1

IDM

AVERTISSEMENT

EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÍA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.

DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON EJE DE
DIRECCIÓN DE VELOCIDAD VARIABLE,
CONSULTE LAS INSTRUCCIONES PARA LA
DESCARGA DEL CONDENSADOR.

iVOLTAJE PELIGROSO!

ADVERTENCIA

SI NO LO HACE, PUEDE OCASIONAR DAÑO AL EQUIPO.

LAS TERMINALES DE LA UNIDAD NO ESTÁN DISEÑADAS
PARA ACEPTAR OTROS TIPOS DE CONDUCTORES.

TENSION DANGEREUSE!

FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
IN DEATH OR SERIOUS INJURY.

ATTENTION
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!

HAZARDOUS VOLTAGE!

WARNING

L'UTILISATION DE TOUT AUTRE CONDUCTEUR PEUT
ENDOMMAGER L'ÉQUIPEMENT.

LES BORNES DE L'UNITÉ NE SONT PAS CONÇUES
POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS.

N'UTILISER QUE DES CONDUCTEURS EN CUIVRE!

PRECAUCIÓN

LEGEND

OUTDOOR MOTOR CAPACITOR

FAN TERMINAL BLOCK
GAS VALVE

LOW PRESSURE CONTROL
OUTDOOR AIR SENSOR

RETURN HUMIDITY SENSOR

PHASE MONITOR
EXHAUST FAN RELAY

PPF3
PPF11,PPM11

PPF4,PPM4

COMBUSTION FAN MOTOR PLUG

IGNITER PLUG

IGNITION CONTROL PLUG

ECONOMIZER PLUG

TDL2
PPF6,PPM6

THERMOSTAT DISCHARGE LINE CKT 1
THERMOSTAT DISCHARGE LINE CKT 2

TDL1

ZONE SENSOR MODULE

XFR
ZSM

PHM

REHEAT VALVE
SPACE HUMIDITY SENSOR

RHV
SHS

CONTROL POWER TRANSFORMER
IGNITION TRANSFORMER

TNS2

TNS1

HIGH LIMIT CUTOUT
FAN FAILURE LIMIT

TIMED OVERIDE
TCO2

TIOR

TRANE COMMUNICATION INTERFACE

SUPPLY HIGH TEMPERATURE

TCO1

TCI

SHT

REMOTE MINIMUM POSITION
SUPPLY AIR SENSOR

RMP

RETURN HIGH TEMPERATURE
SAS

RHT

RHS

RAS

OUTDOOR FAN MOTOR
OUTDOOR FAN RELAY
RETURN AIR SENSOR

ODF1,ODF2

ODM1,ODM2

OUTDOOR HUMIDITY SENSOR

OAS
OHS

LPC3

50
64

41-46

50

50,75

90-102

80

99

13-15

81

71

41

58

72

72

69

63

66

91

98

66

98

96

69,68,34,38

33,37

100

70

71

78,80

IGNITION PROBE
LOW VOLTAGE TERM BLOCK
LOW PRESSURE CONTROL

LTB

74,50

17

10

64,65

76

16,17,18

17,18

100

93

91

21,26

98

41,42

43

33,37

23,28

64,65

91

LINE
NUMBER

LPC1,LPC2

IP

HI VOLTAGE TERMINAL BLOCK
INDOOR FAN MOTOR
IGNITION CONTROL MODULE

IDM
IGN

HTB1

HIGH PRESSURE CONTROL

GV
HPC1,HPC2

FTB

COMMUNICATION MODULE

RELIATEL REFRIGERATION MODULE

RELIATEL OPTIONS MODULE
COMM

RTRM

RTOM

ECONOMIZER ACTUATOR
FAN FAILURE SWITCH
INDOOR FAN CONTACTOR

DISCHARGE TEMPERATURE SENSOR

DTS
ECA
FFS
F

EXHAUST FAN RELAY

EXF

COMPRESSOR

CLOGGED FILTER SWITCH

CFS
CPR1,CPR2

COMBUSTION FAN RELAY

COMBUSTION FAN MOTOR

CFR

CFM

CF1,CF2

COMPRESSOR CONTACTOR
CRANKCASE HEATER

CC1,CC2

BUILDING MANAGEMENT SYSTEM

DESCRIPTION

CCH1,CCH2

BMS

DEVICE
DESIGNATION

Typical Wiring

Figure 5. YS*200F–250F

RT-PRC034-EN

RT-PRC034-EN

60

59

58

57

56

55

54

53

52

51

50

49

48

47

46

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

W6 (BL)

W5, 6K ,D(RD)

W13(RD)

12B,C(BL)

6D(RD)

12B,

14F (GR)

14G(WH)
14F(GR)

X2

H1

13C
(BK)

X1
115V

12B,C(BL)

Y1
230V

14C
(GR)

14G (WH)

13C (BK)

Y2

CC2
T3

T3

TNS2

L2

L1

IGN

12C(BL)

S2

S1

SPLICE

31A,C,D ,E(RD)

6D(RD), 6E(PR)

24V

460V
400V

LINE 61

COM

17F (RD)

16F (RD)

L1
CBM

TNS1

7

W34(PR)

575V

HI

IGN
LO

MARKED TERMINAL FOR
10MFD CAPACITORS ONLY

107A(RD)

26C(BK)

W13, 6K (RD)

W14(RD)

8

(BK)

4C(BK)

W28 ,26C

W28,

415V
H3 575V

L3

L3

CC1

W34(PR)
14C(GR)

(BL)

380V
H2 460V

12J

12B ,J, W6 (BL)

1

ODF1

CF2

CF1

36B,J,W

112A(BK)

CFR

107B(RD)

109A(RD)

W5, 6K ,D(RD), 6C(PR)

MARKED TERMINAL FOR
10MFD CAPACITORS ONLY

CFR

3

TAN

PPM4-2

TAN

110A(PR)

PPF11-4

PPF11-3

IP

PPF11-1

4

113A(OR)

RED

PURPLE
PPM11-1

BROWN

BROWN

BLACK
PPM11-4

ORANGE
PPM11-3

PPM11-2

ODM2

ODM1

PPF11-2

108A(RD)
CFR

112B(BK)

2

PPM4-1

,36V(GR)

PPF4-2

(BL)

1
112A,B(BK)

PPF4-1

110A,
W34
(PR)

3

15A(BK)

11A(BR)

6E(PR)

4C(BK)

7A(BR)

6C(PR)

CFM

GREEN/YELLOW

BROWN
GREEN
ORANGE

BR
GR
OR

BLUE

BLACK

COLOR

TN

YL

WH

RD

PR

ABBR

WIRE COLOR DESIGNATION

BL

BK

ABBR

11 TERMINALS MAY NOT BE PRESENT.

TAN

YELLOW

WHITE

RED

PURPLE

COLOR

CONNECTIONS SHOWN ARE FOR 460V/60HZ/3PH OR 380V/
50HZ/3PH. WHEN 575V/60HZ/3PH OR 415V/50HZ/3PH
UNIT OPERATION IS REQUIRED, REMOVE WIRES 12B,C(BL)
FROM H2 TERMINAL ON TNS2, AND CONNECT TO H3
TERMINAL ON TNS2

8

F).

CONNECTIONS SHOWN ARE FOR 460V/60HZ/3PH OR 380-415V/
50HZ/3PH. WHEN 575V/60HZ/3PH UNIT OPERATION IS
REQUIRED, REMOVE WIRE 12C(BL) FROM 460V/400V
TERMINAL ON TNS1 AND CONNECT TO 575V TERMINAL ON TNS1.

THREE PHASE MOTORS ARE PROTECTED UNDER PRIMARY
SINGLE PHASING CONDITIONS. ALL MOTORS HAVE
INTERNAL OVERLOAD PROTECTION. COMPRESSORS HAVE
INTERNAL THERMAL PROTECTION.

NUMBERS ALONG THE RIGHT SIDE OF THE SCHEMATIC
DESIGNATE THE LOCATION OF CONTACTS BY LINE NUMBER.
AN UNDERLINED NUMBER INDICATES A NORMALLY CLOSED
CONTACT.

DASHED LINES INDICATE RECOMMENDED FIELD WIRING
BY OTHERS. DASHED LINE ENCLOSURES AND/OR DASHED
DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY
THE FIELD. PHANTOM LINE ENCLOSURES INDICATE
ALTERNATE CIRCUITRY OR AVAILABLE SALES OPTIONS.

UNLESS OTHERWISE NOTED ALL SWITCHES ARE SHOWN
AT 25 C (77 F), AT ATMOSPHERIC PRESSURE.
AT 50% RELATIVE HUMIDITY, WITH ALL UTILITIES
TURNED OFF, AND AFTER A NORMAL SHUTDOWN HAS
OCCURED. ALL THERMISTORS ARE 10K AT 25
C (77

7

4

3

2

1

NOTES:

Typical Wiring

Figure 5. (continued from previous page) YS*200F–250F
11 X 17 METAL PLATE

73

Typical Wiring

Figure 6. TS*155F–250F

74

RT-PRC034-EN

Typical Wiring

Figure 6. (continued from previous page) TS*155F–250F

**

RT-PRC034-EN

75

76

92

91

90

89

88

87

86

85

84

83

82

81

80

79

78

77

76

75

74

73

72

71

70

69

68

67

66

65

64

63

LTB-3

31B(RD)

LTB-1

31A,B(RD)

31C(RD)

31D(RD)

29

29

LTB-4

LTB-2

31E(RD)

BLUE

YELLOW

30

LPC2

LPC1

(ZTEMP)1

(LED_COMMON)6

(HEAT)7

(COOL)8

(SYS_ON)9

17

(SERVICE)10

(HSP)5

(MODE)4

(CSP)3

(SIGNAL_COMMON)2

ZSM

LTB-6

SHT

19 TYPICAL ZONE SENSOR

118A(PR)

W8(PR)

RHT

31

LTB-5

YELLOW

BLUE

50A(BL)

52

51
LTB-TEST 1
52E(BL)

51B(PR)

117A(PR)

37C(PR)

SPLICE

BLACK

P1-14

P1-13

P3-2

P1-8

P8-1

P8-2

36BX(BlU)

56A(PR)

C

SPLICE

BLACK

Y

P1-1

P3-1
W38(RD)
YOUT
P1-12

PHM

LTB-TEST 2

OAS

136A(RD)

31A,C,D,E (RD)

CPR2

J6-7
(0-30 VDC)

J6-8
(0-30 VDC)

J6-9
(0-30 VDC)

TEST
INPUT

DISABLE

J6-10
(0-30 VDC)

J6-6
(COM)

CPR1

OUTDOOR
AIR
TEMP

DISABLE

ZSM

J6-5
(0-5 VDC)

J6-4
(0-5 VDC)

J6-3
(0-5 VDC)

J6-2
(COM)

J6-1
(0-5 VDC)

J1-14

(COM)

J1-13

J3-2

J1-8

J8-1

J8-2

(EMER
STOP)

J1-12

(24 VAC)

J3-1

(24 VAC)

J1-1

RTRM

J3-7

J1-9

J3-3

J3-4

J1-10

J1-11

J5-3

J1-3

J5-4

24 VAC
J4-1
(MODBUS)

J4-2

+ J4-5
MODBUS
COMM OUT
- J4-4

NON
HEAT PUMP
CONFIG

J3-6

J5-1
(24 VAC)
IGN
COMM
+

K7

LEAD/ J3-8
LAG

LOCKOUT

K10

K6

COMMON

K9

J1-2

P14-1

P14-2

P14-4

P14-5

P1-5

P1-3

P5-4

P5-3

P5-1

P3-6

P3-8

P3-7

P1-9

P3-3

P3-4

P1-10

P1-11

P1-2

24V
LINE 59

P

41A(RD)

40A(BL)

39A(BK)

38A(BK)

59A(PR)

59A(PR)

82A(BK)

81A(BK)

68A(YL)

TC01

80A(YL)

36BY(BL)

61A(YL)

63A(YL)

86A(YL)

84A(YL)

64A(BK)

36A(BL)

33

RED

BLACK

RED

BLACK

TB1

J1-1

J1-2

J1-3

TRANE
BUILDING
MANAGEMENT
SYSTEM

P21-1

P21-2

P21-3

J1-12

J1-10

J1-7

TC02

IGN

RED

BLACK

J1-6

J1-8

HPC2

HPC1

COMM
OUT -

IN

OUT

24 VAC

COMMON

- IN

90A(YL)

87A(YL)

42D(BR)

J2-1

J2-2

J2-4

J2-5

PPF3-6

PPF5-1

PPF5-2

PPF5-4

PPF5-5

83A(BR)
PPF3-8

RED

BLACK

+MODBUS+

TCI/LCI/NCI
J1-4

PPF3-12

PPF3-10

PPF3-7

P21-4

85A(BR)

36BZ(BL)

TDL2

TDL1

P

CC2

3

W66(RD)

W65(BL)

W64(BK)

TH

61A(YL)

W63(BK)

35

63A(YL)

CC1

GV
MAIN

1

TR

2

104A(BL)

DTS

F

P11-1

103A(PR)

P4-4

P4-5

P13-1

P13-2

PPM8-4

P11-4

PPM8-3

P11-3

PPM8-2

P11-2

PPM8-1

36J(BL)

BLACK

PPF8-4

PPF8-3

PPF8-2

PPF8-1

ODF1

64A(BK)

J1-3

J4-4

J4-5

J3-1

J3-2

J1-4

COMMON

COMMON

DISCHARGE AIR
SENSOR

CONFIG
COMMON

SUPPLY AIR
TEMPERING

24 VAC

,36BZ(BL)

RTOM

36AS(BL)

J1-1 +
MODBUS
COMM
J1-2 -

36B(BL)

36A,F,W,AS(BL)

36A(BL)

36B,J,W(BL), 36V(GR)

F-17,18
CC1-21,22,34
CC2-26,27,35

36V(GR)

Figure 7.

62

61

Typical Wiring

YS*155F–250F

RT-PRC034-EN

RT-PRC034-EN

INSET E - PROGRAMMABLE ZONE SENSOR/
REMOTE PANEL W/NSB

120

119

118

117

116

115

114

113

112

111

110

109

15

NOTES:

15

1

OPTIONAL
REMOTE SENSOR

S1

S2

A1

A2
17

10

9

8

7

14

HEAT

OFF

COOL

FAN

COOL 2

COOL 1

AUTO

ON

INSTALL OPTIONAL REMOTE SENSOR TO TERMINALS S1 AND S2
WHEN REQUIRED. SEE PROGRAMMABLE ZONE SENSOR / REMOTE
PANEL W/ NSB LITERATURE FOR OPTION CONFIGURATION.

ALL UNITS SHIP WITH AN OPTIONS HARNESS ROUTED
FROM THE CONTROL BOX TO THE RETURN AIR SECTION.
DO NOT CONNECT THE OPTIONS HARNESS PPF5 TO THE
RTRM IF NO OPTIONS ARE INSTALLED. DO NOT CONNECT
OPTIONS HARNESS PPM8 TO THE RTOM IF NO ECA IS
INSTALLED. REFER TO ACCOMPANYING LITERATURE FOR
CONNECTION / COMBINATION OF OPTIONAL COMPONENTS.

15

28

12

108

A3

11

107

106

105

104

103

102

101

100

99

HEAT

OFF

COOL

97

98

COOL

96

OFF

HEAT

THERMOSTAT

19

W2

HEAT 2

Y2

Y1

THALPY CONTROL.

REQUIRED FOR OPTIONAL REFERENCE ENTH
REQUIRED FOR OPTIONAL COMPARATIVE EN

21

25

28

26

0-10 VDC Duct Mounted Sensor Only.

AUXILIARY RELAY ENERGIZED DURING OCC

UPIED PERIODS.

OPTIONAL MAS, RAS, RHS, OHS AND ASSOCIATED WIRING NOT USED
WITH MOTORIZED OUTSIDE AIR.

T.

ZONE SENSOR.

INSET E IS FOR OPTIONAL PROGRAMMABLE

19
20

WIRE 81B(PR) USED ONLY ON SINGLE HEA

WHEN OPTIONAL REMOTE MINIMUM POSITION POTENTOMETER IS
REQUIRED AND WIRE AS SHOWN.

ALPY CONTROL.

TERMINALS 7,8,9 AND 10 ARE FOR OPTIO

NAL INDICATORS.

122A(RD)

(+

25

17

23

137A(PR)

GND

) 24V

(

)

-

-

LTB 7

LTB 8

ECA

EXF
24VAC
2A
P24-2

P24-1

P1

P

24VAC

COMMON

RED

WHT

P17-4

P17-3

P17-1

+
MODBUS
P17-2
COMM
-

1

24V
32

18

BLU

W57(RD)

W56(BL)

W55(BK)

W54(BK)

RMP

P

CONNECT WIRES 36BY AND 36BZ TO ENABLE 3 STAGE COOLING
ONLY ON HIGH EFFICIENCY SHORT ORIFICE UNITS.

TO ENABLE COMPRESSOR LEAD/LAG OPERAT

35

IED DEVICE.
ION, CUT WIRE 36B.

POWER EXHAUST OUTPUT FOR FIELD SUPPL
33

TO SHUT DOWN THE UNIT FOR EMERGENCY STOP, REMOVE JUMPER AND
INSTALL FIELD SUPPLIED DEVICE.

TO DISABLE COMPRESSORS, REMOVE JUMPERS AND CONNECT FIELD
SUPPLIED CONTROL DEVICE.

36F(BL)

2

DCV
1

OAH
2

(4-20MA)
1

RAH
2

(4-20MA)
1

COMMON
2

RAT
1 0-5VDC

COMMON
2

MAT
1 0-5VC

32

30

29

P28-2

121A(BRN)

P28-1

120A(BK)

P12-2

P12-1

140A(RD)

P9-2

P9-1

138A(RD)

P10-2

P10-1

141A(PR)

P23-2

P23-1

98A(PR)

W44(BL)

LTB 14

h +

OHS

h +

RHS

RAS

97A(PR)

MAS

LTB 13

139A(PR)

142A(PR)

CO2 SENSOR
OUT

26

21

20

21

26

21

26

26

18

J6-10
(0-30 VDC)

J6-9
(0-30 VDC)

J6-8
(0-30 VDC)

J6-7
(0-30 VDC)

J6-14
(24 VAC)

J6-12
(0-40 VDC)

J7-6

J7-2

J7-9

J7-4

J7-5

J7-3

J7-1
(24 VAC)

RTRM
J6-11
(COM)

COM

RH

G

W1

HEAT 1

RC

96A(PR)

FIRE
PANEL

1

3 FOS

LTB9

LTB10

LTB11

PPM6-4

P6-4

124A(BK)

P6-5

125A(BK)

P6-6

126A(BK)

P7-5

P7-6

101A(PR)

P7-3

P7-4

58J(PR)

P7-2

105A(PR)

P7-1

2 106A(RD)

102A(RD)

FFS

100A(RD)

CFS

PPM6-3

PPM6-2

PPM6-1
+

24 VAC
(MODBUS)

- COMMON

J7-2

J7-1

J6-4

J6-5

J6-6

J7-5

J7-6

J7-3

PRESSURIZE

PURGE

EXHAUST

24 VAC

FAN
PROVING

24 VAC

J7-4 CLOGGED
FILTER

J2-4

J2-3

J2-2

J2-1 MODBUS
COMM

Figure 7.

95

94

93

92

Typical Wiring

(continued from previous page) YS*155F–250F

77

Typical Wiring

Figure 8. WS*155E–250E

78

RT-PRC034-EN

Typical Wiring

Figure 8. (continued from previous page) WS*155E–250E

*

RT-PRC034-EN

79

Jobsite Connections
Table 68. Typical number of wires
Zone Sensors
A

Manual Changeover

4

Manual/Auto Changeover

5

Manual/Auto Changeover with Status Indication LED’s

10

Programmable Night Setback with Status Indication LED’s

7

Thermostats
B

3 Power Wires + 1 Ground Wire (three phase)

DISCONNECT
SWITCH
(BY OTHERS)

B
ZONE SENSOR OR
THERMOSTAT

A
ROOFTOP
UNIT

Notes:

80

•

For specific wiring information, see the installation instructions.

•

All wiring except power wire is low voltage.

•

All customer supplied wiring to be copper and must conform to applicable electrical codes
(such as NEC or CEC) and local electric codes. Wiring shown dotted is to be furnished and
installed by the customer.

•

Zone sensor required for units configured for Single Zone VAV indoor fan system control to
enable Single Zone VAV functionality.

RT-PRC034-EN

Dimensional Data
Figure 9. Cooling with optional electric heat and gas/electric models—15–25 tons—downflow unit clearance
* All dimensions are in inches/millimeters.

54”
(1372 mm)

1”
(25 mm)

DOWNFLOW CONDENSATE
DRAIN CONN 1” (25 mm) NPT

26 3/4”
(679 mm)
6”
(152 mm)

(SEE NOTE)

64 11/16”
(1643 mm)

121 11/16”
(3091 mm)

33 3/16”
(843 mm)
8 15/16”
(227 mm)

2 11/16”
(68 mm)

84 3/16”
(2138 mm)

7/8” (22 mm) DIA. HOLE
(UNIT CONTROL WIRE)

3” (76 mm) DIA. HOLE
(UNIT POWER WIRE)

Figure 10. Cooling with optional electric heat and gas/electric models–15–25 tons—unit clearance and horizontal unit
supply/return
* All dimensions are in inches/millimeters.

RT-PRC034-EN

81

Dimensional Data

Figure 11. Heat pump—15 tons—downflow unit clearance
* All dimensions are in inches/millimeters.

(TS*/WS* MODELS ONLY)
2138 MM

Figure 12. Heat pump—15 tons—unit clearance and horizontal unit supply/return
* All dimensions are in inches/millimeters.

82

RT-PRC034-EN

Dimensional Data

Figure 13. Heat pump—20 tons—downflow unit clearance
* All dimensions are in inches/millimeters.

64 1/8”
1629 MM

(TS*/WS* MODELS ONLY)
2138 MM

Figure 14. Heat pump—20 tons—unit clearance and horizontal unit supply/return
* All dimensions are in inches/millimeters.

RT-PRC034-EN

83

Dimensional Data

Figure 15. Cooling and heat pump with optional electric heat and gas/electric models—15–25 tons—roof curb
* All dimensions are in inches/millimeters.

Figure 16. Cooling and heat pump with optional electric heat and gas/electric models 15–25 tons—downflow duct
connections—field fabricated
* Duct flanges mount 7-7/16" (189mm) down inside the curb on the 1.5" (38mm) curb flanges. Roofcurb is intended for downflow use only.
* All dimensions are in inches/millimeters.

9

PERIMETER
CURB FLANGE

84

RT-PRC034-EN

Dimensional Data

Figure 17. Cooling and heat pump with optional electric heat and gas/electric models 15–25 tons—downflow unit
clearance
* All dimensions are in inches/millimeters.

Figure 18. Downflow & horizontal condensate locations

Table 69. Standard efficiency units (cooling and gas/electric)
Condensate
Tons

Downflow Only
A

15–25

RT-PRC034-EN

B

26 7/16” 28 3/4”
672 mm 730 mm

C

D

19 15/16”
506 mm

4 1/4”
108 mm

Drain Size
F

G

H

4 1/4”
76 5/16” 68 11/16”
108 mm 1938 mm 1745 mm

1 NPT

Condensate Drain
Location
Downflow

Horizontal

J

K

26 3/4”
679 mm

5 3/8”
137 mm

85

Dimensional Data

Table 70. Cooling unit—swing diameter & through the base electrical
Unit Model #

A

B

C

D

E

TSD/YSD 155F, 175F, 200F, 250F, WSD155E, 200E

29 1/2

56

38 1/2

18 1/2

N/A

Note: *All dimensions are in inches

TOP VIEW SHOWING THROUGH THE BASE
ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES.

B

6 7/8"
SWING RADIUS (E)
HORIZONTAL FILTER
ACCESS PANEL

SWING RADIUS (A)
ID SECTION
ACCESS PANEL
SWING RADIUS (D)
ID FAN SECTION
ACCESS PANEL

Figure 19. Fresh air hood (horizontal units)

THROUGH THE
BASE ELECTRICAL

SWING RADIUS (C)
OD SECTION
ACCESS PANEL

Figure 20. Fresh air hood (downflow units)

FRESH AIR HOOD (MANUAL)
HORIZONTAL UNITS

495 MM
19 1/2”
495 MM

Figure 21. Economizer - horizontal units

Figure 22. Economizer - downflow units

Note: When applying economizer to horizontal units, connected
ductwork must be run full size to allow proper operation of
economizer damper.

86

RT-PRC034-EN

Weights
Table 71. TS* maximum unit and corner weights (kg) and center of gravity dimensions (mm)
Max Weight (kg)

Corner Weights (kg)

Center of Gravity (mm)

Model

Shipping

Net

A

B

C

D

Length

Width

TS*155F

1022

826

268

226

162

170

149

86

TS*175F

1040

845

268

231

169

176

154

89

TS*200F

1068

873

278

233

170

191

145

90

TS*250F

1060

852

270

231

169

182

153

89

Notes:
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
3. *Indicates both horizontal and downflow units.

Table 72. TS* maximum unit and corner weights (lb) and center of gravity dimensions (inches)
Max Weight (lb)

Corner Weights (lb)

Center of Gravity (in)

Model

Shipping

Net

A

B

C

D

Length

Width

TS*155F

2253

1822

590

498

358

376

59

34

TS*175F

2292

1863

591

510

372

388

61

35

TS*200F

2353

1925

614

514

375

422

57

35

TS*250F

2337

1878

595

510

372

402

60

35

Notes:
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
3. *Indicates both horizontal and downflow units.

RT-PRC034-EN

87

Weights
TS* Accessories

Table 73. TS* accessory net weights (kg/lb)(a), (b), (c)
Economizer
Model

Net

Outside Air Damper
Motorized

Manual

Oversized
Motor
Roof Curb Adder(d)

All Zone
Sensors

High Static Low Static
Drive(d)
Drive(d)

TSD155F, 175F

—

—

—

—

—

—

—

TSD200F

36/79

34/75

15/33

107/236

2/4

0.5/1

1/2

—
—

TSD250F

36/79

34/75

15/33

107/236

—

0.5/1

—

1/2

TSH155F, 175F

—

—

—

—

—

—

—

—

TSH200F

30/66

34/75

15/33

—

2/4

0.5/1

1/2

—

TSH250F

30/66

34/75

15/33

—

—

0.5/1

—

1/2

(a) Net weight should be added to unit weight when ordering factory installed accessories.
(b) For 600V heaters net weights are same as 480 V heaters.
(c) To estimate shipping weight add 2.3 kg (5 lb) to net weight.
(d) Downflow only.

Table 74. TS* accessory net weights (kg)
Electric Heat
5–27 kW

11–14 kW

22–27 kW

22–41 kW

45–54 kW

Models

380–415 kW

380–415 kW

380–415 kW

380–415 kW

380–415 kW

TS*155F, 175F

—

9.5

12.3

14.5

—

TS*200F

—

—

12.3

14.5

15.4

TS*250F

—

—

12.3

14.5

15.4

Notes:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. For 600 V heaters net weights are same as 480 V heaters.
3. Not available on all models (see Fan Performance tables for specific models).
4. To estimate shipping weight add 5 lb (2.27 kg) to net weight.
5. TS*155F-250F factory installed options for economizers, multiply net capacity x 0.99, EER x 0.97. For oversized motors, multiply net
capacity x 0.98, EER x 0.93.
6. * Indicates both downflow and horizontal units

Table 75. TS* accessory net weights (lb)
Electric Heat
5–27 kW

11–14 kW

22–27 kW

22–41 kW

45–54 kW
380–415 kW

Models

380–415 kW

380–415 kW

380–415 kW

380–415 kW

TS*155F, 175F

—

21

27

32

—

TS*200F

—

—

27

32

34

TS*250F

—

—

27

32

34

Notes:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. For 600 V heaters net weights are same as 480 V heaters.
3. Not available on all models (see Fan Performance tables for specific models).
4. To estimate shipping weight add 5 lb (2.27 kg) to net weight.
5. TS*155F-250F factory installed options for economizers, multiply net capacity x 0.99, EER x 0.97. For oversized motors, multiply net
capacity x 0.98, EER x 0.93.
6. * Indicates both downflow and horizontal units

88

RT-PRC034-EN

Weights
YS* Unit & Corner Weights, Center of Gravity

Table 76. YS* maximum unit and corner weights (kg) and center of gravity dimensions (mm)
Max Weight

Corner Weights

Center of Gravity

Model

Shipping

Net

A

B

C

D

Length

Width

YS*155F

1100

888

285

242

175

184

148

86

YS*175F

1119

910

289

248

181

191

153

89

YS*200F

1147

939

299

250

182

206

145

90

YS*250F

1140

932

297

252

183

200

153

89

Notes:
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
3. *Indicates both horizontal and downflow units.

Table 77. YS* maximum unit and corner weights (lb) and center of gravity dimensions (inches)
Max Weight

Corner Weights

Center of Gravity

Model

Shipping

Net

A

B

C

D

Length

Width

YS*155F

2424

1958

628

534

387

406

58

34

YS*175F

2467

2007

637

547

400

421

60

35

YS*200F

2528

2069

659

551

402

455

57

35

YS*250F

2513

2054

655

555

403

442

60

35

Notes:
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
3. *Indicates both horizontal and downflow units.

RT-PRC034-EN

89

Weights
YS* Accessories

Table 78. YS* accessory net weights (kg)(a), (b)
Economizer Outside Air Damper
Manual

Roof
Curb(d)

Oversized
LPG
Motor
Conversion
Adder(c)
Kit

All Zone
Sensors

High
Static
Drive(c)

Low
Static
Drive(c)

Model

Net

Motorized

YSD155F, 175F

—

—

—

—

—

—

—

—

—

YSD200F

36

34

15

107

2

2

0.5

1

—

YSD250F

36

34

15

107

—

2

0.5

—

1

YSH155F, 175F

—

—

—

—

—

—

—

—

—

YSH200F

30

34

15

—

2

2

0.5

1

—

YSH250F

30

34

15

—

—

2

0.5

—

1

(a) Net weight should be added to unit weight when ordering factory installed accessories.
(b) Not available on all models. (See fan performance table for specific models).
(c) YS*155F-250F factory installed options for economizers, multiply net capacity x 0.99, EER x 0.97. For oversize motors, multiply net capacity
x 0.98, EER x 0.93.
(d) Downflow only.

Table 79. YS* accessory net weights (lb)(a), (b)
Economizer Outside Air Damper
Manual

Roof
Curb(c)

Oversized
LPG
Motor
Conversion
Adder(d)
Kit

All Zone
Sensors

High
Static
Drive(d)

Low
Static
Drive(d)

Model No

Net

Motorized

YSD155F, 175F

—

—

—

—

—

—

—

—

—

YSD200F

79

75

33

236

4

4

1

2

—

YSD250F

79

75

33

236

4

1

2

YSH155F, 175F

—

—

—

—

—

—

—

—

—

YSH200F

66

75

33

—

4

4

1

2

—

YSH250F

66

75

33

—

4

1

—

2

(a) Net weight should be added to unit weight when ordering factory installed accessories.
(b) Not available on all models. (See fan performance table for specific models).
(c) Downflow only.
(d) YS*155F-250F factory installed options for economizers, multiply net capacity x 0.99, EER x 0.97. For oversize motors, multiply net capacity
x 0.98, EER x 0.93.

90

RT-PRC034-EN

Weights
WS* Unit & Corner Weights, Center of Gravity

Table 80. WS* maximum unit and corner weights (kg) and center of gravity dimensions (mm)
Max Weight

Corner Weights

Center of Gravity

Model

Shipping

Net

A

B

C

D

Length

Width

WS*155E

1105

899

288

234

171

207

1262

811

WS*200E

1164

956

306

220

181

268

1285

789

Notes:
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
2. *Indicates both horizontal and downflow units.

Table 81. WS* maximum unit and corner weights (lb) and center of gravity dimensions (inches)
Max Weight

Corner Weights

Center of Gravity

Model

Shipping

Net

A

B

C

D

Length

Width

WS*155E

2435

1982

634

515

377

456

56

36

WS*200E

2566

2107

674

485

400

590

57

35

Notes:
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
2. *Indicates both horizontal and downflow units.

RT-PRC034-EN

91

Weights
WS* Accessories

Table 82. WS* accessory net weights (kg)(a), (b), (c), (d)
Economizer(e)

Outside Air Damper

Model

Net

Motorized

Manual

Roof Curb

Oversized
Motor
Adder(e)

WSD155E

—

—

—

—

—

—

WSD200E

36

34

15

107

2

0.5

5

—

WSH155E

—

—

—

—

—

—

—

—

WSH200E

30

34

15

—

—

0.5

7

—

Roof Curb

Oversized
Motor
Adder(e)

All Zone
Sensors

All Zone
Sensors

High Static Low Static
Drive(f)
Drive(f)
—

—

(a) To estimate shipping weight add 2.3 kg to net weight.
(b) Downflow only.
(c) Not available on all models (see fan performance tables for specific models).
(d) D = Downflow unit, H = Horizontal unit.
(e) Net weight should be added to unit weight when ordering factory installed accessories.
(f) Multiply by 1.25 for net weight of 200–230 V rated heaters.

Table 83. WS* accessory net weights (lb)(a), (b), (c), (d)
Economizer(e)
Model

Net

Outside Air Damper
Motorized

Manual

High Static Low Static
Drive(f)
Drive(f)

WSD155E

—

—

—

—

—

—

—

WSD200E

79

75

33

236

4

1

11

—
—

WSH155E

—

—

—

—

—

—

—

—

WSH200E

66

75

33

—

—

1

15

—

(a) To estimate shipping weight add 2.3 kg to net weight.
(b) Downflow only.
(c) Not available on all models (see fan performance tables for specific models).
(d) D = Downflow unit, H = Horizontal unit.
(e) Net weight should be added to unit weight when ordering factory installed accessories.
(f) Multiply by 1.25 for net weight of 200–230 V rated heaters.

Table 84. WS* accessory net weights (kg)
Electric Heat
5–27 kW

11–14 kW

22–27 kW

22–41 kW

45–54 kW

380–415 kW

380–415 kW

380–415 kW

380–415 kW

380–415 kW

WS*155E

—

9.5

12.3

14.5

—

WS*200E

—

—

12.3

14.5

15.4

Models

Notes:
1. Net weight should be added to unit weight when ordering factory installed economizer or oversize motor.
2. Not available on all models (see Fan Performance tables for specific models).
3. To estimate shipping weight add 2.3 kg to net weight.
4. Downflow only.
5. * Indicates both downflow and horizontal units

Table 85. WS* accessory net weights (lb)
Electric Heat
5–27 kW

11–14 kW

22–27 kW

22–41 kW

45–54 kW

Models

380–415 kW

380–415 kW

380–415 kW

380–415 kW

380–415 kW

WS*155E

—

21

27

32

—

WS*200E

—

—

27

32

34

Notes:
1. Net weight should be added to unit weight when ordering factory installed economizer or oversize motor.
2. Not available on all models (see Fan Performance tables for specific models).
3. To estimate shipping weight add 5 lb to net weight.
4. Downflow only.
5. * Indicates both downflow and horizontal units

92

RT-PRC034-EN

Mechanical Specifications
General
The units shall be dedicated downflow or horizontal airflow. The operating range shall be between
115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be
rated in accordance with ARI testing procedures. All units shall be factory assembled, internally
wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and
blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall
be colored and numbered for simplified identification.

Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces
shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's
surface shall be tested 500 hours in a salt spray test in compliance with ASTM B117. Cabinet
construction shall allow for all maintenance on one side of the unit. In order to ensure a water and
air tight seal, service panels shall have lifting handles and no more than three screws to remove.
All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2-inch,
1-pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the
downflow unit shall be insulated with 1/2-inch, 1-pound density foil-faced, closed-cell material. The
downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than
the raised 11/8-inch high supply/return openings to provide an added water integrity precaution,
if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane
lifting.

Discharge Line Thermostat
A bi-metal element discharge line thermostats installed as a standard option on the discharge line
of each system. This standard option provides extra protection to the compressors against high
discharge temperatures in case of loss of charge, extremely high ambient and other conditions
which could drive the discharge temperature higher. Discharge line thermostat is wired in series
with high pressure control. When the discharge temperature raises high above the protection limit,
the bi-metal disc in the thermostat switches to off position to open the 24 Vac circuit. When the
temperature on discharge line cools down, the bi-metal disc closes the contactor circuit to provide
power to compressor. When the thermostat opens the fourth time, the ReliaTel™ control must be
manually reset to resume operation on that stage.

Unit Top
The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to
prevent water leakage.

Filters
Two inch standard filters shall be factory supplied on all units. Optional 2-inch MERV 8 and MERV
13 filters with a filter removal too shall also be available.

Compressors
All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps.
Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus
10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors.
All models shall have crankcase heaters, low and high pressure control as standard.

Crankcase Heaters
These band heaters provide improved compressor reliability by warming the oil to prevent
migration during off-cycles or low ambient conditions. These are standard on all Voyager™
models.

RT-PRC034-EN

93

Mechanical Specifications

Refrigerant Circuits
Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices,
service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall
be provided for replacement suction line driers.

Evaporator and Condenser Coils
Internally finned, 5/16” copper tubes mechanically bonded to a configured aluminum plate fin shall
be standard for evaporator coils. Condenser coils may also be microchannel type (major design
sequence F units only). Coils shall be leak tested at the factory to ensure the pressure integrity. The
evaporator coil and condenser coil shall be leak tested to 225 psig and pressure tested to 450 psig.
All dual compressor units shall have intermingled evaporator coils. Sloped condensate drain pans
are standard. Round tube plate fin type condenser coils are patent-pending 1+1+1 coils,
permanently gapped for easy cleaning.

Gas Heating Section
The heating section shall have a drum and tube heat exchanger design using corrosion resistant
steel components. A forced combustion blower shall supply premixed fuel to a single burner
ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative
pressure gas valve shall be used that requires blower operation to initiate gas flow. On an initial
call for heat, the combustion blower shall purge the heat exchanger 45 seconds before ignition.
After three unsuccessful ignition attempts, the entire heating system shall be locked out until
manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field
installed kit) and shall also comply with California requirements for low NOx emissions. The 15–
25 tons shall have two stage heating (Gas/Electric Only).

Outdoor Fans
The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the
vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have builtin thermal overload protection.

Indoor Fan
Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with
standard motors shall have an adjustable idler-arm assembly for quick-adjustment of fan belts and
motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for
high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).

Controls
Unit shall be completely factory wired with necessary controls and contactor pressure lugs or
terminal block for power wiring. Unit shall provide an external location for mounting a fused
disconnect device. ReliaTel controls shall be provided for all 24-volt control functions. The resident
control algorithms shall make all heating, cooling, and/or ventilating decisions in response to
electronic signals from sensors measuring indoor and outdoor temperatures. The control
algorithm maintains accurate temperature control, minimizes drift from set point, and provides
better building comfort. A centralized control shall provide anti-short cycle timing and time delay
between compressors to provide a higher level of machine protection.

Defrost Controls
Adaptive demand defrost shall be provided to permit defrost wherever coil icing conditions begin
to significantly reduce unit capacity.

94

RT-PRC034-EN

Mechanical Specifications

Factory Installed Options
Black Epoxy Coated Pre-Coated Coils
The black epoxy coils have a thermoset vinyl coating that is bonded to the aluminum fin stock prior
to the fin-stamping process. The pre-coated coils are an economical option for protection in mildly
corrosive environments.

CO2 Sensor Wiring
The unit wiring for field installed C02 sensors. Factory-installed C02 sensor wiring saves time and
ensures proper unit connections for the field installed C02 sensor kits.

Complete Coat™ Microchannel Condenser Coil
The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number
of different types of heat exchangers. The coating is selected to provide excellent resistance and
durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salty air and other
corrosive environments. This coating shall be available on microchannel condenser coils.

Condensate Overflow Switch
This option shall shut the unit down in the event that a clogged condensate drain line prevents
proper condensate removal from the unit.

Hinged Access Doors
Sheet metal hinges are available on the Filter, Evaporator, Fan/Motor and the Compressor/Control
Access Doors. This option is available on all models.

Stainless Steel Drain Pan
This option provides excellent corrosion and oxidation resistance. Drain pan shall be reversible and
constructed of 304 stainless steel.

Stainless Steel Heat Exchanger
Gas heat exchanger shall be of drum and tube design constructed from a minimum 304 Grade
stainless steel. The stainless steel heat exchanger shall have a 10-year warranty as standard (Gas/
Electric Only).

Through the Base Electrical with Circuit Breaker
This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through
the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the
unit with access through a swinging door. Factory wiring will be provided from the switch to the
unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized
per NEC and UL guidelines, and be agency recognized by UL/CSA. This option is available on all
downflow models.

Through the Base Electrical With Disconnect Switch
Three-pole, molded case, disconnect switch with provisions for through the base electrical
connections are available. The disconnect switch will be installed in the unit in a water tight
enclosure with access through a swinging door. Factory wiring will be provided from the switch to
the unit high voltage terminal block. The switch will be UL/CSA agency recognized.
Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place
of unit overcurrent protection. This option is available on all downflow models.

Through the Base Utilities Access
An electrical service entrance shall be provided allowing electrical access for both control and main
power connections inside the curb and through the base of the unit. Option will allow for field
installation of liquid-tight conduit and an external field installed disconnect switch.
RT-PRC034-EN

95

Mechanical Specifications

Two-Inch Pleated Filters
Two-inch MERV 8 and MERV 13 media filters with filter removal tool shall be available on all
models.

Factory or Field Installed Options
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or
clogged filter indication. These indications will be registered with either a zone sensor with status
indication lights or an Integrated Comfort™ System.
These options allow for individual fan failure and dirty filter indication. The fan failure switch will
disable all unit functions and “flash” the Service LED on the zone sensor. The dirty filter switch will
light the Service LED on the zone sensor and will allow continued unit operation.

Discharge Air Sensing Kit
This kit provides true discharge air sensing in heating models. This sensor is a status indicator
readable through Tracer™ or Tracker™. The kit is functional only with the ReliaTel™ Options
Module.

Economizer—Downflow
The assembly includes fully modulating 0–100 percent motor and dampers, barometric relief,
minimum position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring
return actuator. The barometric relief damper shall be standard with the downflow economizer and
shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance
of outside air during the equipment “off” cycle. Solid state enthalpy and differential enthalpy
control shall be field-installed.

Electric Heaters
Electric heat modules shall be available for installation within the basic unit. Electric heater
elements shall be constructed of heavy-duty nickel chromium elements internally delta connected
for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each
heater package shall have automatically reset high limit control operating through heating element
contactors. All heaters shall be individually fused from the factory, where required, and shall meet
all NEC and CEC requirements when properly installed. Power assemblies shall provide singlepoint connection. Electric heat modules shall be UL listed or CSA certified. If ordering the Through
the Base Electrical option with an Electric Heater, the heater must be factory installed.

Frostat
This option is to be utilized as a safety device. The Frostat opens when temperatures on the
evaporator coil fall below 10°F. The temperature will need to rise to 50°F before closing. This option
should be utilized in low airflow or high outside air applications.

LonTalk® Communications Interface
The LonTalk communications interface, when installed in a Voyager unit, allows the unit to
communicate as a Tracer LCI-V device or directly with generic LonTalk Network Building
Automation System Controls.

Trane Communication Interface
This factory or field-installed option shall be provided to interface ReliaTel controlled units with the
Trane Integrated Comfort systems.

96

RT-PRC034-EN

Mechanical Specifications

Field Installed Options
Barometric Relief
Designed to be used on downflow units, barometric relief is an unpowered means of relieving
excess building pressure.

CO2 Sensor
The CO2 sensor shall have the ability to monitor the concentration (parts per million, ppm) of CO2
(Carbon Dioxide) in the air. As the CO2 concentration changes, the outside air damper modulates
to meet the current ventilation needs of the zone.
Note: Choose factory-installed CO2 sensor wiring option to save time and ensure proper unit
connections for the field installed CO2 sensor kits.

Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone
sensors. This sensor includes a digital display of set point adjustment and space temperature in
F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of
the standard sensor). E-squared memory stores last programmed set points. Requires 24 Vac (Volts
AC). This sensor should be utilized with ReliaTel™ controls.

Economizer—Horizontal
The horizontal economizer shall contain the same features as the downflow economizer with the
exception of barometric relief.

High Static Drive
The high static drive option shall allow the standard motor on the 15-, 20-, and 25-ton units to
operate with improved external static capabilities.

Low Static Drive
The low static drive option shall allow the standard motor on the 17½- and 20-ton to operate at low
static conditions.

Manual Outside Air Damper
The rain hood and screen shall provide up to 25 percent outside air.

Motorized Outside Air Dampers
Manually set outdoor air dampers shall provide up to 50 percent outside air. Once set, outdoor air
dampers shall open to set position when indoor fan starts. The damper shall close to the full closed
position when indoor fan shuts down.

Reference or Comparative Enthalpy
Reference Enthalpy is used to measure and communicate outdoor humidity. The unit receives and
uses this information to provide improved comfort cooling while using the economizer.
Comparative Enthalpy measures and communicates humidity for both outdoor and return air
conditions, and return air temperature. The unit receives and uses this information to maximize use
of economizer cooling, and to provide maximum occupant comfort control. Reference or
Comparative Enthalpy option shall be available when a field installed Downflow Economizer is
ordered. This option is available on all models.
The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain
better building pressurization.

RT-PRC034-EN

97

Mechanical Specifications

Roof Curb—Downflow
The roof curb shall be designed to mate with the downflow unit and provide support and a water
tight installation when installed properly. The roof curb design shall allow field-fabricated
rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply
with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include
wood nailer strips.

Economizer—Horizontal
The horizontal economizer shall contain the same features as the downflow economizer with the
exception of barometric relief.

Oversized Motors
Oversized motors shall be available for high static applications.

Remote Potentiometer
The minimum position setting of the economizer shall be adjusted with this accessory.

Tool-less Hail Guards
Tool-less, hail protection quality coil guards are available for condenser coil protection.

Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition up to three
different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition
occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired
relay output from a smoke detector or fire control panel.

Zone Sensors
This option shall be provided to interface with the Micro equipped Voyagers and shall be available
in either manual, automatic, programmable with night setback, with system malfunction lights or
remote sensor options.

98

RT-PRC034-EN

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts.
For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2012 Trane All rights reserved
RT-PRC034-EN 20 Aug 2012

We are committed to using environmentally

Supersedes RT-PRC034-EN (16 Jun 2011)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : TCS - Unitary
Copyright                       : ? 2008 Trane All rights reserved
Create Date                     : 2012:07:20 08:39:50Z
Job Ref                         : RT-PRC034-EN
Keywords                        : Voyager, R-410A, 50Hz, Packaged Cooling, Gas/Electric & Heat Pump Rooftops, ReliaTel
Modify Date                     : 2012:07:20 11:04:37Z
Subject                         : Packaged Cooling, Gas/Electric & Heat Pump Rooftops Catalog
Web Statement                   : www.trane.com
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Format                          : application/pdf
Description                     : Packaged Cooling, Gas/Electric & Heat Pump Rooftops Catalog
Title                           : Voyager™, R-410A 15-25 Tons — 50 Hz
Creator                         : TCS - Unitary
Producer                        : Acrobat Distiller 10.1.3 (Windows)
Creator Tool                    : FrameMaker 10.0.2
Document ID                     : uuid:3975b3e0-333a-4fc0-841d-03a3769de863
Instance ID                     : uuid:def19357-119a-404f-8c13-10dcafc1ba24
Page Mode                       : UseOutlines
Page Count                      : 100
EXIF Metadata provided by EXIF.tools

Navigation menu