Installation, Operation,
and Maintenance

Tracer™ TD-5 Display
for ReliaTel™ Controller

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.

November 2013

RT-SVX49A-EN

Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provided to alert
installing contractors to potential hazards that could result
in death or personal injury. Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughly before operating or servicing
this unit.

ATTENTION: Warnings, Cautions, and Notices appear at

appropriate sections throughout this literature. Read
these carefully:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
CAUTIONs situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
a situation that could result in
NOTICE: Indicates
equipment or property-damage only
accidents.

WARNING

Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.

municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.

WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•

Before installing/servicing this unit, technicians
MUST put on all Personal Protective Equipment (PPE)
recommended for the work being undertaken.
ALWAYS refer to appropriate MSDS sheets and OSHA
guidelines for proper PPE.

•

When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.

•

If there is a risk of arc or flash, technicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.

Failure to follow recommendations could result in death
or serious injury.

Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
© 2013Trane All rights reserved

RT-SVX49A-EN

Table of Contents
Warnings, Cautions and Notices . . . . . . . . . . 2

Sensor Report . . . . . . . . . . . . . . . . . . . . . . . . 20

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Binary Input Report . . . . . . . . . . . . . . . . . . . 20

Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Screen characteristics . . . . . . . . . . . . . . . . 4

Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Creating a Custom Graph . . . . . . . . . . . . . . 22
Standard Graphs . . . . . . . . . . . . . . . . . . . . . . 25

Touchscreen Guidelines . . . . . . . . . . . . . . . . 4

Space Temperature: . . . . . . . . . . . . . . . . . 25

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Compressor Graph: . . . . . . . . . . . . . . . . . . 25

Specifications and Agency Compliance . . . 6

VAV System: . . . . . . . . . . . . . . . . . . . . . . . 26

Supported Languages . . . . . . . . . . . . . . . . . . 6

Economizer Graph: . . . . . . . . . . . . . . . . . . 26

Screen Overview . . . . . . . . . . . . . . . . . . . . . . 7

Outside Air Ventilation: . . . . . . . . . . . . . . 26

Top Display Area . . . . . . . . . . . . . . . . . . . . 7

CO2 Graph: . . . . . . . . . . . . . . . . . . . . . . . . . 26

Main Display Area . . . . . . . . . . . . . . . . . . . 7

Humidity Graph: . . . . . . . . . . . . . . . . . . . . 26

Bottom Display Area . . . . . . . . . . . . . . . . . 7

Heat Pump Graph: . . . . . . . . . . . . . . . . . . . 26

Communication . . . . . . . . . . . . . . . . . . . . . 4

Installing the Tracer™ TD-5 Display . . . . . . . 8
Packaged Contents . . . . . . . . . . . . . . . . . . . . 8
Additional Mounting Parts . . . . . . . . . . . . . 8

Installing the TD-5 Display onto a VESA
Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . 8
Powering up the TD-5 Display for the First
Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Active Alarms . . . . . . . . . . . . . . . . . . . . . . . .
Historic Alarms . . . . . . . . . . . . . . . . . . . . . . .
Viewing Active and Historic Alarms . . . . .
Alarm Icons . . . . . . . . . . . . . . . . . . . . . . . . . .
Sorting Alarms . . . . . . . . . . . . . . . . . . . . . . .

10
10
11
11

Binary Output Report . . . . . . . . . . . . . . . . . . 21

Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Settings Screen . . . . . . . . . . . . . . . .

27
27
28
29

Display Preferences . . . . . . . . . . . . . . . . . 29
Language . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Date and Time . . . . . . . . . . . . . . . . . . . . . . 31
Clean Touchscreen . . . . . . . . . . . . . . . . . . 32

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 33
Identifying and Diagnosing Issues . . . . . . . 33

12
12

Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Custom Reports . . . . . . . . . . . . . . . . . . . . . . 13
Creating a Custom Report . . . . . . . . . . . . 13
Editing a Custom Report . . . . . . . . . . . . . 15

About . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
System Report . . . . . . . . . . . . . . . . . . . . . . . 17
Economizer/Ventilation Report . . . . . . . . . 18
Compressor Report . . . . . . . . . . . . . . . . . . . 18
Heating Report . . . . . . . . . . . . . . . . . . . . . . . 19
Configuration Report . . . . . . . . . . . . . . . . . . 19
RT-SVX49A-EN

3

Introduction
The purpose of this guide is to assist you in installing,
programming, and operating theTracer™TD-5 display,
which operates with the ReliaTel™ Controller.This guide
describes how to access the screens and the types of
information that appear on the screens.
TheTracer™TD-5 display allows you to view data and
make operational changes on the following types of
applications:
•

Voyager™

•

Precedent™

Hardware
TheTracer™TD-5 is a durable touch screen display that is
designed to operate in both indoor or outdoor
environments.TheTD-5 display utilizes a standard 75mm
VESA mounting pattern for installation. Alternatively, it
can be installed with a user-supplied VESA mount.

Power
TheTracer™TD-5 display is powered by 24 VAC or 24 VDC
and requires 21 VA power, which it receives through a
power cable.The display is typically connected to J10 of
the RTRM Module, but it can also be powered from an
alternate power source.

Communication
Communication is provided to theTD-5 through the RTRM
J10 connector.

Screen characteristics
The 5-inch WVGA 800 x 480 resolution touch-sensitive
color screen is LED backlit, which enables viewing in poor
light conditions including outdoor usage (with the
exception of direct sunlight).

Touchscreen Guidelines
The touch screen registers the downward pressure of a
touch. Light, quick, yet deliberate touches are most
effective.Touching with more pressure has no effect.
Recommended tools to use:
•

finger

•

thumb

•

pencil eraser

Do not use:
•

a screwdriver

•

a pen

•

a pencil point

•

any other sharp or pointed object that might scratch
the screen surface

4

RT-SVX49A-EN

Introduction

Dimensions
147,0
[5 . 8 ]

42,1
[1 . 7 ]
32,0
[1 . 3 ]

154,0
[6 . 1 ]

115,3
[4 . 5 ]

106,4
[4 . 2 ]

Note: The power cable is permanently attached
to theTD-5 display.The power connector
provides strain relief and protection from the

RT-SVX49A-EN

5

Introduction

Specifications and Agency
Compliance
Specification
Input power:

24 Vac ± 15%, or 24 Vdc ± 10% 21 VA, 50 or
60 Hz

Storage
temperature:

–67°F to 203°F (–55°C to 95°C)
Humidity: Between 5% to 100% (noncondensing)

Operating
temperature:

Temperature: –40°F to 158°F (–40°C to 70°C)
Humidity: Between 5% to 100% (noncondensing)

Mounting weight:

Mounting surface must support 0.93 lb (422
grams)
Mounting Type: VESA (75 mm x 75 mm)

Environmental
rating
(enclosure):

IP55 (dust and strong water protected)
(PN: X19070632020)

Agency Compliance
•
•
•
•
•

UL916 PAZX, Open Energy Management Equipment
UL94-5V, Flammability
FCC CFR Title 47, Part 15.109: Class A Limit, (30 MHz – 4 GHz)
CE EMC Directive 2004/108/EC
CE EMC Directive 2004/108/EC

Supported Languages
TheTD-5 display supports 26 built-in languages. For help
on how to select a specific language for the display, see
“Language,” p. 31.
Arabic
Chinese (Simplified)
Chinese (Traditional)
Czech
Dutch
English
French
German
Hebrew

6

Hungarian
Indonesian
Italian
Japanese
Korean
Norwegian
Polish
Portuguese (Brazil)
Portuguese (Portugal)

Romanian
Russian
Spanish (Mexico)
Spanish (Spain)
Swedish
Thai
Indonesian
French Canadian

RT-SVX49A-EN

Introduction

Screen Overview

•

Main display area

•

Bottom display area

There are three distinct areas on theTD-5 screens:
•

Top display area

Figure 1.

Tracer™ TD-5 display screen

Top display area

Main display
area

Bottom display
area

Top Display Area

Bottom Display Area
The Back button, when touched, returns
to the previous screen visited.
The Home button, when touched,
navigates to the Home Page. Home can be
configured. See “Display Preferences,”
p. 29.
The Header Data Point is a user-defined
data point that will appear at the top
portion of each display screen. This value
can be the present value of any point in
the TD-5. See “Header Data Point,” p. 29.

The bottom display area contains functional buttons that
provide a link to the appropriate screen.
Screen brightness settings: Touch this
icon to change the display’s brightness.
Touch this button to open the Alarms
screen. When an alarm is present, this
button will flash red.

Touch this button to navigate to the
Reports screen.

Touch this button to open the Data Graphs
screen to view Graphs.
Touch this button to open the Settings
screen, which contains options for
controls, security (if enabled), and
display settings.

Main Display Area
This area serves as the main task area in which you can
view custom graphics, create reports, view and take action
on alarms, and view or change display settings.

RT-SVX49A-EN

Language selection: Touch this icon to
select a language that will be displayed on
all screens.

7

Installing the Tracer™ TD-5 Display
This section describes installation procedures when
mounting theTracer™TD-5 display near the RTRM
module or remotely mounted up to 328 ft (100 m) by using
a field-suppled 75 mm VESA mounting bracket. Read and
observe all warning and caution statements before you
begin the installation procedure.

4. Securely tighten the M-4 screws using a Phillips
screwdriver.

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.

Packaged Contents
•

One (1)Tracer™TD-5 display with permanently
attached 2.6 ft (0.8 m) power cable with male connector

•

Four (4) M-4 screws

•

Four (4) spacer washers

Additional Mounting Parts
•

TD-5 Display Low Profile Mounting Bracket (VESA
75mm) (PN: X05010511010)

Installing the TD-5 Display onto a
VESA Mounting Bracket
TheTracer™TD-5 can be mounted near the RTRM module
in the control panel, or remotely mounted up to 328 ft
(100 m) by using a field-suppled 75 mm VESA mount.
Remote mounting requires the following additional fieldsupplied components:
•

A power source that will supply 24 VAC to the display

•

Power cables

Many commercial 75mm VESA mounting brackets are
available, which range from a simple wall mount to tiltand-swivel mounts such as the one shown in Figure 2, p. 9,
or theTD-5 Display Low Profile Mounting Bracket (VESA
75mm) (PN: X05010511010).
To install onto a VESA mounting bracket:
1. Disconnect power at the circuit breaker and perform
lockout/tagout procedures.
2. Mount the VESA mounting bracket according to
manufacturer’s instructions.
3. Position theTD-5 display 1onto the VESA mounting
bracket 2 and align the four mounting holes with the
bracket while inserting and hand-tightening the four
M-4 screws. (Some brands ofVESA mounting brackets
may require the use of the four spacer washers to allow
the M-4 screws to tighten properly.)
8

RT-SVX49A-EN

Installing the Tracer™ TD-5 Display
Figure 2.

Example VESA mounting

1

2

Powering up the TD-5 Display for
the First Time
After completing the installation instructions in “Installing
theTracer™TD-5 Display,” p. 8,TheTD-5 display can be
powered up.
Before applying power to theTD-5 Display, verify that the
RTRM Module is powered up.
Upon successful power up, theTD-5 Display will default to
the configured home screen.The System Report is the
factory default.
Important:

RT-SVX49A-EN

Do not attempt to update theTD-5 Display
from a connection type other than a USB.

9

Alarms
Alarms appear on theTracer™TD-5 display immediately
upon detection.Touch the Alarms button in the bottom
display area to view the Alarms screen.

Active Alarms
Figure 3, p. 10 shows the Active Alarms screen and
commonly used functions. Configuration is not required in
order for points in alarm to appear in the Active Alarms
Figure 3.

screen. When the alarm clears and the point returns to
normal, the alarm will automatically be removed from the
list.The number of active alarms is displayed in the top
right portion of the screen. When an active alarm is
present, the alarm button at the bottom of the screen will
flash.
The Alarms screen defaults to Active Alarms.The Active
Alarms button has a shaded appearance which indicates
that you are viewing active alarms.

Active alarms screen
Number of active alarms

Sortable
columns
Alarm severity

Active Alarms
button

10

RT-SVX49A-EN

Alarms

Historic Alarms
On the Alarms screen, touch the Historic Alarms button to
view all alarms, commonly referred to as the event log (see
Figure 4, p. 11).
Figure 4.

Historic alarms screen

Number of historic
alarms

Sortable
columns

Alarm severity

Historic Alarms button

Viewing Active and Historic
Alarms
•

Active alarms:These are alarms that require attention.
All alarms that are currently active appear when you
view this category. Active alarms are not reset by way
of the display. Active alarms will clear automatically
when the condition causing the alarm is removed.

•

Historic alarms: Historic alarms appear when you view
this category.The alarms are listed in chronological
order.

Alarm Severity
A color-code icon representing the severity of each alarm
is shown under the severity (!) column. For a description
of the five alarm icons, see Table 1, p. 12.

Sortable Alarms
You can sort active alarms by touching one of the column
headers. Choose to sort by severity (!), date and time,
point name, or description.
RT-SVX49A-EN

11

Alarms

Alarm Icons

Table 2.

Alarms icons appear in the left-most column of the alarms
screen.They are identifiable by their shape and color.
Table 1.

Alarm icons

Active
Alarm Icons

Notification Class
Critical

Service Required

Information
Note: Notifications classes are configured in point alarm settings section
in Tracer TU.

Sorting Alarms
To sort alarms by a category other than date and time,
touch one of the other column headings in the table.The
column heading responds by changing to blue, and the
alarms table re-sorts according to the blue column
heading. By touching the blue column heading again, the
column will change the sort direction.
•

Severity (!): Active alarms are at the top, followed by
the most severe, followed by the most recent.

•

Date andTime (the default sort): Most recent alarms
are at the top.

•

Description: Alarms are sorted alphabetically by
description.

Table 2.

List of alarms

Space Temp Sensor Failure

Outdoor Temp Sensor Fail

Compressor 1 HPC Lockout

Compressor 1 LPC Lockout

Comp 1 Disable Input/LPC

Compressor 2 HPC Lockout

Compressor 2 LPC Lockout

Comp 2 Disable Input/LPC

Smoke Detector

Heat Failure

Dirty Filter

Supply Fan Failure

Emergency Stop

Frostat™ Trip

Mixed Air Temp Sensor Fail

OA Humidity Sensor Failure

Return Air Temp Sensor Fail

Return Air RH Sensor Failure

Coil Temp Sensor #1 Fail

Demand Defrost Fault A

Demand Defrost Fault B

Demand Defrost Fault C

Demand Defrost Fault D

Defrost Default Mode

Local Cool Setpoint Fail

Local Heat Setpoint Fail

Vent Override – Purge

Vent Override – Exhaust

Vent Override – Pressurize

Drain Pan Overflow

Freezestat Tripped

Supply Air Temp Sensor Fail

CO2 Sensor Failure

CO2 Setpoint Failure

Space Humidity Sensor Fail

Dehumid Setpoint Failure

12

List of alarms (continued)

Air Flow Sensor Fail

Min OA Flow Setpoint Fail

Space Pressure Setpoint Fail

Space Pressure Sensor Fail

Heating High Temp Limit Open

Flame Rollout Switch Open

Inducer Proving Switch Fail

No Flame Sensed on heat call

Flame Sensed w/Gas Valve Off

Gas Heat Module Failure

Economizer Actuator Fault

Morning Warmup Setpoint Fail

SA Reset Amount Failure

SA Temp Cool Setpoint Fail

SA Temp Heat Setpoint Fail

SA Reset Setpoint Failure

SA Press Setpoint Fail

SA Pressure Deadband Fail

Supply Air Press Sensor Fail

SA High Press Limit

SA Pressure PWM Fault

Comp 1 Disable Input/HPC

Comp 2 Disable Input/HPC

CO2 Low Limit Setpoint Fault

Exh/Ret Fan Proving Failure

RTOM Comm Fail

RTEM Comm Fail

RTAM Comm Fail

RTVM Comm Fail

RTCM Comm Fail

SA Reheat Setpoint Failure

RTDM Comm Fail

Space Press Deadband Fail

Mod Dehumid Config

Ent Evap Temp Sensor Fail

Coil Temp Sensor #2 Fail

SA Temp Heat Setpoint Fail

Demand Defrost Fault A Ckt 2

Demand Defrost Fault B Ckt 2

Demand Defrost Fault C Ckt 2

Defrost Default Mode Ckt 2

Demand Defrost Fault A Ckt 1

Demand Defrost Fault B Ckt 1

Demand Defrost Fault C Ckt 1

Defrost Default Mode Ckt 1

Exhaust Fan Setpoint Fail

IGN1 Communications Timed out IGN2 Communications Timed out
DCV Min Position Setpoint Fail (@ Design Min Position Setpoint Fail
Full Fan Speed)
(@ Full Fan Speed)
Enthalpy Setpoint Fail

Design Min Position at Minimum
Fan Speed Fail

DCV Min Position at Minimum Fan Design Min Position at Midpoint
Speed Fail
Fan Speed Fail
DA Cool Setpoint Fail

PWM Max Fan Spd Setpt Fail

Compressor 3 HPC Lockout

Compressor 3 LPC Lockout

Comp 3 Disable Input/LPC

Comp 3 Disable Input/HPC

Power on Reset

TD-5 Loss of Comm with RTRM

RT-SVX49A-EN

Reports
You can use theTracer™TD-5 Display to view a variety of
reports and create and edit custom reports.
Touch the Reports button in the bottom display area to
view the Reports screen.The Reports screen contains the
following buttons:
Table 3.

Representation of screen below

Custom Report 1

System Report

About

Custom Report 2

Compressor Report

Sensor Report

Custom Report 3

Operating Modes

Configuration Report

Economizer/
Ventilation Report

Heating Report

Binary Input Report

Figure 5.

Binary Output Report

Reports screen

Custom Reports
You can create up to three custom reports using the
Tracer™TD-5 Display

Creating a Custom Report
1. Navigate to the Reports screen, then touch one of the
three custom report buttons.
The Custom Report (1, 2, or 3) screen appears.
2. Touch the Edit button.
The Edit Custom Report screen appears (Figure 6,
p. 14).

RT-SVX49A-EN

13

Reports
Figure 6.

Creating a custom report

3. Use the up and down arrow buttons to select a point.
Add items by touching the item that is highlighted
blue, then touch the Add button.
4. Continue adding values to your report. When you are
finished, touch the Save button.
The Custom Report screen, populated with your
selected values, appears (Figure 7, p. 14).
Figure 7.

14

To view the items in the selected list, touch a value in
this list and use the up and down arrows to the right of
the list.To change the location of an item in the list,
select the item and then use the up and down arrows
above the table to move the items.

New custom report screen

RT-SVX49A-EN

Reports

Editing a Custom Report
1. Touch Reports to view the Reports screen.
Figure 8.

2. Touch the report that you want to edit.
Follow steps 2 through 4 in “Creating a Custom
Report,” p. 13. to complete your edits.

Editing a custom report

Category
Selector

Buttons that
re-order your
custom
report list
Scroll buttons
to navigate
through the
data list

Scroll buttons
to navigate
through the
data list

Changing the Order of Items in a Custom
Report
Items in a custom report can be rearranged according to
personal preference by using the editing tools as
described in Editing a Custom Report.
For example, you created the custom report shown in
Figure 7, p. 14, but would prefer to move item “Diagnostic:
Space Static Pressure Failure” to the top left portion of the
report.

Figure 9.

Custom report (order of items)

Custom Report
1

2

3

4

5

6

7

8

9

To change the order for the example described above:
1. Touch the Edit button on the Custom Report screen.
2. Use the arrow buttons to locate the item to be
reordered. When located, touch the item which will
then be highlighted blue (see Figure 8, p. 15).
3. Use the arrow buttons to move the highlighted item to
the top of the list (number 1 position).
4. Touch Save.You will be returned to the Custom Report
screen, where the reordering changes now appear.
Note: On theTD-5 display, report items are ordered from
left to right with the first item appearing at the top
left portion of the screen. Up to nine items can
appear on each Custom Report screen.
The model in Figure 9, p. 15 depicts a custom report
screen with the first nine items displayed on the screen.
Use this model to accurately reorder items in your custom
reports.

RT-SVX49A-EN

15

Reports

About

to which it is connected.Touch the arrow button to scroll
to the next screen.

Touch the About button to view the About screen. View
information about the unit controller and theTD-5 display
Figure 10. About screen

Data Area

Unit Name. This is the name that was entered.

The following data are displayed on the About screen.
Unit Name
ABCDEFGHIJKLMNOPQRSTUVWXYZ12456789
RTRM Software Version
6200-XXXX-YY.ZZ

RTVM Software Version
6200-XXXX-YY.ZZ

VSM Software Version
6200-XXXX-YY.ZZ

RTOM Software Version
6200-XXXX-YY.ZZ

RTAM Software Version
6200-XXXX-YY.ZZ

RTEM Software Version
6200-XXXX-YY.ZZ

RTDM Software Version
6200-XXXX-YY.ZZ

BAS Interface Software Version
6200-XXXX-YY.ZZ

Display User Interface Software Version
6200-XXXX-YY.zz

Display Firmware Version
6200-XXXX-YY.zz

16

Display Boot Code Version
6200-XXXX-YY.zz

RT-SVX49A-EN

Reports

System Report
Touch the System Report button to view the System
Report screen.Touch the arrow buttons to move between
screens.
Figure 11.

System report screen

Data Area
The following data can be configured to appear on the
System Report screen. Only configured items will appear.
Unit Application
VAV,CV,SZVAV

Unit Mode
Heat, Cool, Off, Emergency Heat

Setpoint Source
Remote, Local

Supply Fan Output
Energized, De-energized

Supply Fan Speed %
XXX %

Supply Fan Mode
On, Auto

Occupancy
Occupied, Unoccupied

Active Cooling Stages
X

Active Heating Stages
X

Active Space Temp
XXX.X F/C

Active Space Temp Setpoint
XXX.X F/C

Outdoor Air Damper %
XXX % Open

Supply Air Temp
XXX.X F/C

Active Supply Air Temp Setpoint
XXX.X F/C

System Control Mode
Manual, Auto

Economizing
Enabled, Disabled

Ventilation Type
Fixed/DCV
(*DCV = Demand Control Ventilation)

Variable Compressor Speed %
XXX %

Fresh Air Measurement
Installed, Not Installed

Demand Limit
Active/Not Active

Heating Type
None, Electric, Gas, Hydronic

Exhaust Fan Status

Available Cooling Stages
X

Available Heating Stages
X

Supply Fan Starts
XXXXX

Supply Fan Running Time
HHHHH:MM

Space Pressure
X.XX in(H2O)/ mm(H20)

Supply Air Pressure
X.XX in(H2O)/ mm(H20)

Local Space Temp
X XX.X OF/C

Emergency Stop Input

RTOM Low Fan Speed Output

Alarm Indicator Output

VAV Box Output

Thermostat Y1 Input

Thermostat W1/O Input

Thermostat G Input

Thermostat W2 Input

Thermostat Y2 Input

Thermostat X2 Input

Supply Fan Proving Input

Condensate Drain Overflow Input

Frostat™ Input

Clogged Filter Input

Smoke Detector Input

Reheat Humidistat Input

Changeover Switch Input

RT-SVX49A-EN

17

Reports

Economizer/Ventilation Report
Touch the Economizer/Ventilation Report button to view
the Economizer/Ventilation Report screen.Touch the arrow
buttons to move between screens.

Data Area
The following data can be configured to appear on the
Economizer/Ventilation Report screen. Only configured
items will appear.

Outdoor Air Damper %
XXX % Open

Economizing
Enabled, Disabled

Mixed Air Temp
XXX.X F/C

Ventilation Type

Economizing Enable Type
Dry Bulb, Reference Enthalpy, Comparative
Enthalpy

Outdoor Air Temp
XXX.X F/C

Active Min OA Damper Position Target
XXX %

Manual Enthalpy Override
Enabled, Disabled

Return Air Temp
XXX.X F/C

Active Upper CO2 Limit Setpoint
XXXX PPM

Active Lower CO2 Limit Setpoint
XXXX PPM

Space CO2
XXXX PPM

Active Enthalpy Setpoint
XXXXX BTU / LBM

Return Air Humidity
XXX %

Outdoor Air Humidity
XXX %

Outdoor Air Flow
XXXXX CFM / LPM

Min Outdoor Air Flow Target
XXXXX CFM / LPM

Min Outdoor Air Flow Deadband
XXXXX CFM / LPM

Design Min Position High Speed Setpoint
XXX %

Design Min Position Mid Speed Setpoint
XXX %

Design Min Position Low Speed Setpoint
XXX %

DCV Min Position High Speed Setpoint
XXX %

DCV Min Position Low Speed Setpoint
XXX %

Power Exhaust Fan Output
Off, On, Auto

DCV Min OA Flow Setpoint
XXXXX CFM / LPM

Outdoor Air Flow Adjustment Setpoint

Exhaust Fan Starts
XXXXX

Exhaust Fan Running Time
HHHHH:MM

Exhaust Damper Position % Open
XXX %

Space Pressure
XX.XX IWC /cmWC

Active Space Pressure Setpoint
XX.XX IWC /cmWC

Space Pressure Deadband
XX.XX IWC /cmWC

Outdoor Fan A Output

Outdoor Fan B Output

Variable Speed Outdoor Fan %

Ventilation Override Pressurize Input

Ventilation Override Purge Input

Ventilation Override Exhaust Input

Power Exhaust Fan Output

Supply Fan Proving Input

Compressor Report

Data Area

Touch the Compressor Report button to view the
Compressor Report screen.Touch the arrow buttons to
move between screens.
Table 4.

The following data can be configured to appear on the
Compressor Report screen. Only configured items will
appear.

Compressor report - data area

Active Cooling Stages
X

Available Cooling Stages
X

Number of Compressors Installed
X

Outdoor Fan A Output
Energized, De-energized

Outdoor Fan B Output
Energized, De-energized

Variable Speed Outdoor Fan %
XXX.X %

Dehumidification Status
Inactive, Active Reheat, Active Enhanced

Reheat Entering Evap Temp
XXX.X F/C

Variable Compressor Speed %
XXX.X %

Compressor 1 Disable Input
Enabled, Disabled

Compressor 2 Disable Input
Enabled, Disabled

Compressor 3 Disable Input
Enabled, Disabled

Compressor 1 Proving Input
Open, Closed

Compressor 2 Proving Input
Open, Closed

Compressor 3 Proving Input
Open, Closed

Heatsink Refrigerant Temperature
XXX.X F/C

Supply Air Temp
XXX.X F/C

Space Temp
XXX.X F/C

Active Space Cooling Setpoint
XXX.X F/C

Defrost Status Ckt 1
Inactive, Defrosting

Defrost Status Ckt 2
Inactive, Defrosting

Active Supply Air Temp Cooling Setpoint
XXX.X F/C

Switchover Valve (SOV) 1 Output
Heating, Cooling

Switchover Valve (SOV) 2 Output
Heating, Cooling

Outdoor Coil Temp Ckt 1
XXX.X F/C

Outdoor Coil Temp Ckt 2
XXX.X F/C

Compressor 1 Starts
XXXXX

18

RT-SVX49A-EN

Reports
Table 4.

Compressor report - data area (continued)

Compressor 2 Starts
XXXXX

Compressor 3 Starts
XXXXX

Compressor 1 Running Time
HHHHH:MM

Compressor 2 Running Time
HHHHH:MM

Compressor 3 Running Time
HHHHH:MM

Number of Compressors Installed

Variable Speed Compressor

Reheat Pumpout Relay

Defrost Starts Ckt 1
XXXXX
*Phase 2

Heating Report

Data Area

Touch the Heating Report button to view the Heating
Report screen.Touch the arrow buttons to move between
screens.
Table 5.

The following data can be configured to appear on the
Heating Report screen. Only configured items will appear.

Heating report - data area

Heating Type
None, Electric, Gas, Hydronic

Heating Configuration
Staged /Modulating

Available Heating Stages
X

Active Heating Stages
X

Space Temp
XXX.X F/C

Modulating Heat Output %
XXX %

Gas Heating Status

Supply Air Temp
XXX.X F/C

Defrost Status Ckt 1
Inactive, Defrosting

Defrost Status Ckt 2
Inactive, Defrosting

Active Space Heating Setpoint
XXX.X F/C

Outdoor Coil Temp Ckt 1
XXX.X F/C

Outdoor Coil Temp Ckt 2
XXX.X F/C

Active Supply Air Temp Heating Setpoint
XXX.X F/C

Heating Stage 1 Output
Active, Inactive

Heating Stage 2 Output
Active, Inactive

Freezestat Input
Open, Closed

Outdoor Air Temp
XXX.X F/C

Gas Heating Type
IGN Temp Limit Input

IGN Pressure Switch Input
IGN Flame Rollout Input

IGN Inducer High Output

IGN Inducer Low Output

Configuration Report

Data Area

Touch the Configuration Report button to view the
Configuration Report screen.Touch the arrow buttons to
move between screens.
Table 6.

The following data can be configured to appear on the
Configuration Report screen. Only configured items will
appear.

Configuration report - data area

Unit Application
CV, VAV, SZVAV

Refrigeration Type
Cooling Only, Heat Pump

Product Type
Voyager™ Commercial, Precedent™/
Precedent™ 17 Plus/Voyager™ Light
Commercial/Odyssey™

Dehumidification
None, Hot Gas Reheat, Enhanced

Supply Fan Control Type
Fixed, Variable, IGV

Economizer
Installed, Not Installed

Dehumidification Type
Staged, Modulating

Heating Type
None, Electric, Gas, Hydronic

CV Control Type
Zone Sensor, Thermostat

Cooling Stages Configured
X

Cooling Steps Input
3 Step, 2 Step

Number of Compressors Installed
X

Heating Stages Configured
X

Variable Speed Compressor
Installed, Not Installed

Economizer Enable Type
Drybulb, Reference Enthalpy, Comparative
Enthalpy

Supply Fan Motor Type
Fixed, VFD, ECM, ERM

Supply Fan Motor Control
0 to 10VDC, PWM

Heat Pump Type
Single, Independent

Windmill Prevention
Enable, Disable

Gas Ignition Module 1
Staged, Modulating

True Supply Air Reporting
Enable, Disable

Supply Air Tempering Input
Enable, Disable

Gas Ignition Module 2
Installed, Not Installed

RT-SVX49A-EN

19

Reports
Table 6.

Configuration report - data area (continued)

Manual Enthalpy Override
Enable, Disable

Lead Lag Configuration Input
Enable, Disable

OA Flow Compensation
Enable, Disable

Outdoor Fan Cycling Input
Normal, Lower

Programmable Zone Sensor
Installed, Not Installed

Cabinet Type
Horizontal, Downflow

Outdoor Air Flow Compensation
Enable, Disable

Evaporator Defrost Control
Enable, Disable

RTRM Fan Proving Input
Closed, Open

Supply Air Tempering Input
Disable, Enable

Outdoor Fan Cycling Input
Normal, Lower

Exhaust Air Control - StatiTrac™
Installed, Not Installed

Sensor Report

Data Area

Touch the Sensor Report button to view the Sensor Report
screen.Touch the arrow buttons to move between screens.
Table 7.

The following data can be configured to appear on the
Sensor Report screen. Only configured items will appear.

Sensor report - data area

Active Space Temp
XXX.X OF/C

Local Space Temp
XXX.X OF/C

Supply Air Temp
XXX.X OF/C

Outdoor Air Temp
XXX.X OF/C

Mixed Air Temp
XXX.X OF/C

Return Air Temp
XXX.X OF/C

Outdoor Air Humidity
XXX.X%

Return Air Humidity
XXX.X%

Space CO2
XXXX PPM

Outdoor Air Flow
XXXXX CFM/LPM

Space Humidity
XXX%

Outdoor Coil Temp Ckt 1
XXX.X OF/C

Outdoor Coil Temp Ckt 2
XXX.X OF/C

Space Pressure
X.XX in(H2O)/mm(H20)

Reheat Entering Evap Temp
XXX.X OF/C

Supply Air Pressure
X.XX in(H2O)/ mm(H20)

Binary Input Report

Data Area

The Binary Input report provides general Reliatel Unit
operating information.Touch the Binary Input Report
button to view the Binary Input Report screen.
Table 8.

The following data can be configured to appear on the
Configuration Report screen. Only configured items will
appear.

Binary input report - data area
Emergency Stop Input
Auto, Emergency Stop

Occupancy

RTRM Fan Proving Input
Closed, Open

Thermostat Y1 Input
Open, Closed

Thermostat W1/O Input
Open, Closed

Thermostat G Input
Open, Closed

Thermostat W2 Input
Open, Closed

Thermostat Y2 Input
Open, Closed

Thermostat X2 Input
Open, Closed

Compressor 1 Disable Input
Closed, Open

Compressor 1 Proving Input
Operating, Not Operating

Compressor 2 Disable Input
Closed, Open

Supply Fan Proving Input
Open, Closed

Condensate Drain Overflow Input
Open, Closed

Ventilation Override Pressurize Input
Open, Closed

Ventilation Override Purge Input
Open, Closed

Ventilation Override Exhaust Input
Open, Closed

Frostat™ Input
Open, Closed

Clogged Filter Input
Open, Closed

Freezestat Input
Open, Closed

Smoke Detector Input
Open, Closed

Reheat Humidistat Input
Open, Closed

Changeover Switch Input
Cooling, Heating

VSM

Compressor 3 Disable Input
Closed, Open

Compressor 3 Proving Input
Operating, Not Operating

RTVM

Exhaust Fan Proving Input
Open, Closed

RTRM

Compressor 2 Proving Input
Operating, Not Operating
RTOM

20

RT-SVX49A-EN

Reports
Table 8.

Binary input report - data area (continued)
IGN Pressure Switch Input
Open, Closed

IGN

IGN Temp Limit Input
Open, Closed

Binary Output Report

Data Area

The Binary Input report provides general Reliatel Unit
operating information.Touch the Binary Input Report
button to view the Binary Input Report screen.
Table 9.

IGN Flame Rollout Input
Open, Closed

The following data can be configured to appear on the
Configuration Report screen. Only configured items will
appear.

Binary output report - data area

RTRM

RTOM/RTAM/RTVM/
RTEM/RTDM

IGN

Supply Fan Output
Off, On

Compressor 1 Output
Off, On

Compressor 2 Output
Off, On

Heat Stage 1 Output
Off, On

SOV 1 Output
Off, On

Outdoor Fan A Output
Off, On

Heat Stage 2 Output
Off, On

SOV 2 Output
Off, On
or
Low Fan Speed
or
Compressor 3 Output
Off, On

Outdoor Fan B Output
Off, On

RTOM Low Fan Speed Output
Off, On

Alarm Indicator Output
Off, On

VAV Box Output
Off, On

Power Exhaust Fan Output
Off, On

Reheat Pumpout Relay
Off, On

IGN Inducer High Output
Off, On

IGN Inducer Low Output
Off, On

Figure 12. Operating modes report details screen

Note: Operating Modes:The operating Mode page shall
show the user the general operation of the unit, and
what modes it is operating in.

RT-SVX49A-EN

21

Graphs
Graphs allow users to view data in graphical format on the
Display. Four custom graphs and eight standard graphs
are available. Graphs can be created with a maximum of
four lines per graph. Custom graphs are user-defined and
can be edited by changing the scale on the left and rightYaxis and choosing the line color.

Touch the Graphs button in the bottom display area to view
the Graphs screen (Figure 13, p. 22).The Graphs screen
contains twelve buttons that allow you to view and edit a
particular graph.There are four custom graphs and 8
standard graphs.

Figure 13. Graphs screen

Creating a Custom Graph

6. Touch the Edit Graph button.
The Edit Graph screen appears (Figure 14, p. 22).

5. Navigate to the Graphs screen, then touch an available
data graph button.
The Custom Graph screen appears.
Figure 14. Edit graph screen

22

RT-SVX49A-EN

Graphs
7. Touch the Add/Remove button to add values to the
custom data graph.
The Add/Remove screen appears.
8. Use the arrow buttons to select a value.

9. Select the values, then touch theAdd button (up to four
selections are allowed).
10. Touch the Save button.The Edit Graph screen appears,
which reflects the selected values.

Figure 15. Adding data logs to the custom graph

11. Use the Edit Graph screen to modify the graph.Touch
the Edit button that corresponds with the value that

you want to change. Only one value can be edited at a
time.

Figure 16. Edit graph screen (after values have been added)

12. From the Edit screen you can choose whichY-axis to
display the value, a color, and whether or not to show
data samples.Touch the Save button when finished.
Repeat the process with remaining values.
RT-SVX49A-EN

23

Graphs
Figure 17.

Customizing the graph

13. Touch the Save button to display the new graph
(Figure 18, p. 24).
Note: Depending on the sampling rate, the custom graph
may be empty for several hours.

You can make changes to the way data is presented on the
graph at anytime.Touch the zoom-in icon
and zoomout icon
to either increase or decrease the viewable
time frame.This action also enables back and forward
arrows that allow you to view data at various times of the
day.

Figure 18. Viewing the graph

Editing the Y-Axis
The default values on the right and leftY-axes can be
changed according to your specifications.
24

14. Touch the EditY-Axis button located on the top portion
of the Custom Data Graph screen.
The EditY-Axis screen appears (Figure 19, p. 25).
RT-SVX49A-EN

Graphs
15. Touch the Manually Select Range box for either the left
or rightY-axis.

17. Select a new value and then touch Enter to save.

The Keypad screen appears.

16. Touch the edit button next to one of the two value
ranges.

18. Repeat steps 2 through 4 until all preferred changes
have been made.

Figure 19. Editing theY-Axis

Standard Graphs
There shall be 8 standard graphs.The standard graphs are
below:
Table 10.

Standard graphs
Space Temperature

Economizer

Compressor

Outside Air Ventilation

VAV

Humidity

Heat Pump

CO2

Space Temperature:
The table below describes the data in the System Status
graph:
Data Point

Line Color

Active Space Temp Setpoint

Blue

Axis
Left

Active Space Temp

Green

Left

Supply Air Temp

Black

Left

Return Air Temperature

Red

Left

Data Point

Line Color

Axis

Active Supply Air Temp Setpoint

Pink

Left

Variable Compressor Speed %

Green

Left

Supply Air Temp

Black

Left

Active Cooling Stages

Blue

Right

Compressor Graph:
The table below describes the data in the graph:

RT-SVX49A-EN

25

Graphs

VAV System:
The table below describes the data in the System Status
graph:
Data Point

Line Color

Active Supply Air Temp Setpoint

Pink

Axis
Left

Active Space Temp

Green

Left

Supply Air Temp

Black

Left

Return Air Temp

Red

Left

Economizer Graph:
The table below describes the data in the graph:
Data Point

Line Color

Outdoor Air Temp

Purple

Axis
Left

Mixed Air Temp

Grey

Left

Active Min OA Damper Position Target

Pink

Right

Outdoor Air Damper %

Yellow

Right

Data Point

Line Color

Axis

Min Outdoor Air Flow Target

Black

Left

Outdoor Air Flow

Pink

Left

Outdoor Air Damper %

Yellow

Right

Outdoor Air Temp

Purple

Right

Data Point

Line Color

Axis

Active Upper CO2 Limit Setpoint

Red

Left

Active Lower CO2 Limit Setpoint

Black

Left

Space CO2

Green

Left

Outdoor Air Damper %

Yellow

Right

Data Point

Line Color

Axis

Space Dehumidification Setpoint

Yellow

Left

Outdoor Air Humidity

Red

Left

Outside Air Ventilation:
The table below describes the data in the graph:

CO2 Graph:
The table below describes the data in the graph:

Humidity Graph:
The table below describes the data in the graph:

Return Air Humidity

Black

Left

Space Humidity

Green

Left

Data Point

Line Color

Axis

Outdoor Coil Temp Ckt 1

Green

Left

Outdoor Coil Temp Ckt 2

Blue

Left

Outdoor Air Temp

Purple

Left

Discharge Air Temperature

Grey

Left

Heat Pump Graph:
The table below describes the data in the graph:

26

RT-SVX49A-EN

Settings
The Settings screen provides options for display settings,
language, overrides and security.Touch the Settings
button in the bottom display area to view the Settings
screen.

•

Control Settings

•

Display Settings

•

Security Settings

Three categories for settings appear on the screen:
Figure 20. Settings screen

Setpoints
Touch the Setpoints button to view the Setpoints screen.
Touch the arrow buttons to move between screens.
Figure 21.

Setpoints screen

RT-SVX49A-EN

27

Settings
Data Area
The following data can be configured to appear on the
Setpoints screen. Only configured items will appear.
Occupied Space Cooling Setpoint

Unoccupied Space Cooling Setpoint

Space Dehumidification Setpoint

Occupied Space Heating Setpoint

Unoccupied Space Heating Setpoint

Supply Air Reheat Setpoint

Discharge Air Heating Setpoint

Discharge Air Cooling Setpoint

Duct Static Pressure Setpoint

Duct Static Pressure Deadband

Morning Warm-up Setpoint

Supply Air Cooling Setpoint
Space Pressure Setpoint

Supply Air Heating Setpoint

Daytime Warm-up Initiate Setpoint

Space Pressure Deadband

Daytime Warm-up Terminate Setpoint

CO2 Upper Limit Setpoint

CO2 Lower Limit Setpoint

Enthalpy Setpoint

Supply Air Reset Setpoint

Exhaust Fan Enable Setpoint

Supply Fan Adjustment Setpoint

Outdoor Air Flow Adjustment Setpoint

Design Min OA flow Setpoint

DCV Min OA Flow Setpoint

Min OA Flow Deadband

Design Min OA Damper Pos Setpoint 100% Fan Design Min OA Damper Pos Setpoint Mid Fan

Design Min OA Damper Pos Setpoint Min Fan

DCV Min OA Damper Pos Setpoint 100% Fan

Outdoor Air Flow Adjustment Setpoint

DCV Min OA Damper Pos Setpoint Min Fan

Setup
Touch the Setup button to view the Setpoints screen.
Touch the arrow buttons to move between screens.
Figure 22. Setup screen

This Setup screen shows a list of the setup items in button
format.The available setup items are listed below:
Unit Mode
Heat, Cool, Auto

Supply Fan Mode
On, Auto

System Control Mode
Local, Remote

Display Read Only Mode
Read, Write

Supply Air Reset Type
Heat, Cool, Auto

Service Test
Disable, IGV Close, IGV Open,
Fan Only/Min Vent,
Economizer Open, Cool 1, Cool 2, Cool 3,
Dehumid/Reheat, Heat 1, Heat 2, Heat 3,
Defrost, Emergency Heat

28

Emergency Heat Mode Request
Auto, Emergency Heat

RT-SVX49A-EN

Settings

Display Settings Screen

Display Preferences

The selections in this category contain settings that affect
the way in which information is displayed on all of theTD5 display screens. From each screen, the current settings
can be viewed.To change a setting, touch the preferred
value.

Touch the Display Preferences button to open the
associated screen (Figure 23, p. 29). On this screen, all
available options to display information on theTD-5
screens are available.There are two pages on this screen,
accessed by using the arrow button at the bottom of the
screen.

Figure 23. Display preferences screen

Date Format

Backlight Time-out

Touch the Date Format button to open the associated
screen.Three options are available to display the current
date: MMDDYYYY, DDMMYYYY, andYYYYMMDD.

Touch the Backlight Time-out button to open the
associated screen.This value is measured in minutes, with
30 being the maximum limit. Use the keypad to enter a
backlight time-out value.This value is the amount of time
that the display will remain lit without activity. When the
backlight times out, users will be automatically logged off
due to inactivity.

Date Separator
Touch the Date Separator button to open the associated
screen.Three options are available to display separators
in the date format: None, Hyphen (-), or Slash (/).

Time Format
Touch the Time Format button to open the associated
screen.Two options are available: 12-Hour format and 24Hour format (also referred to as “military time”).

Unit System
Touch the Unit System button to open the associated
screen.Two options are available: SI (system
international) or IP (Inch-Pound).

Header Data Point
Use the arrow button on the Display Preferences screen to
advance to page 2.Touch the Header Data Point button to
open the associated screen.The Header Data Point
appears in the top right display area on all screens. Use the
arrow buttons to scroll through the points. Click Add to
move the highlighted point to the right side of the
screen(Figure 24, p. 30). Click Save.

Brightness
Touch the Brightness button, or the brightness icon
(
)located at the bottom left of each screen, to open the
associated screen. Screen brightness is measured in
percentage. Use the keypad to enter a new brightness
number.
RT-SVX49A-EN

29

Settings
Figure 24. Setting the header data point
Header data
point

Collection Frequency

sample rate, the lower the duration.The default of 30
seconds shall provide 3.5 days of data collection.

Collection frequency sets the time interval that the Graph
Data is saved, and displayed on the graph.The faster the
Figure 25. Collection frequency

30

RT-SVX49A-EN

Settings
Home Page
Use the arrow button on the Display Preferences screen to
advance to page 2.Touch the Home Page button to open

the associated screen.This function allows you to choose
what will display when the home button is touched.

Figure 26. Home page screen

Language
Touch the Language button, or the language icon (
)
located at the bottom right of each screen, to open the
Figure 27.

open the Language screen.Twenty-six languages are
available and represented on the selection buttons. Select
a language that you want displayed on eachTD-5 screen
and then touch Save. See “Language,” p. 31.

Language screen

Date and Time
Touch the Date and Time button to open the associated
screen.To enter a new date or time, touch the digit you
RT-SVX49A-EN

want to change. When enabled for editing, the digit will
appeared with a black border. when finished, touch Apply
or Save. Or,
31

Settings
tap the digit twice which opens the keypad screen where
you can make date and time entries. When finished, touch

Enter; you will be returned to the Date andTime screen.
Touch Apply or Save.

Figure 28. Date and time screen

Clean Touchscreen
Touch the CleanTouchscreen button to safely clean theTD5 touchscreen using any brand of common household
glass cleaner. When this button is touched, the screen
background color becomes black, allowing dirt and
fingerprints to become more visible. It also displays a
countdown timer (five to zero seconds).Touch the screen
anytime within the 5-second countdown to begin cleaning
the screen (each touch resets the 5-second countdown).

32

RT-SVX49A-EN

Troubleshooting
This section describes the possible error messages and
other issues that you may encounter while using the
Tracer™TD-5 display.

Important: There are no serviceable parts within the
TD-5 display enclosure. Opening the
enclosure will void the product warranty.

Identifying and Diagnosing Issues
Problem

Possible Cause

Possible Solution

Blank display (TD-5 does not respond
to touch).

No power.

Verify that the TD-5 is connected to a power source,
and that the power source is in working condition.

After powering up, the TD-5 displays
a message that it is not
communicating.

Controller not powered up.

Replace cable if necessary. Power up the controller if
necessary.

No data available in custom report.

Data has not yet been defined for the report.

Add data to report. See “Creating a custom report,”
p. 14.

RT-SVX49A-EN

33

The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments,the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2013Trane All rights reserved
RT-SVX49A-EN 04 Nov 2013

We are committed to using environmentally

(NEW)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Author                          : RT-SVX49*-EN Tracer™ TD-5 Display for ReliaTel™ Controller November 2013
Create Date                     : 2013:10:14 15:14:31Z
Job Ref                         : TD-5
Keywords                        : RT-SVX49*-EN Tracer™ TD-5 Display for ReliaTel™ Controller November 2013, Precedent, ReliaTel, Tracer, Odyssey, Voyager Commercial, Voyager Light Commercial
Marked                          : True
Modify Date                     : 2013:10:14 15:53:04-05:00
Subject                         : RT-SVX49*-EN Tracer™ TD-5 Display for ReliaTel™ Controller November 2013
Language                        : en
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Creator Tool                    : FrameMaker 10.0.2
Metadata Date                   : 2013:10:14 15:53:04-05:00
Format                          : application/pdf
Description                     : RT-SVX49*-EN Tracer™ TD-5 Display for ReliaTel™ Controller November 2013
Title                           : RT-SVX49*-EN Tracer™ TD-5 Display for ReliaTel™ Controller November 2013
Creator                         : RT-SVX49*-EN Tracer™ TD-5 Display for ReliaTel™ Controller November 2013
Producer                        : Acrobat Distiller 10.1.8 (Windows)
Document ID                     : uuid:0bc87f56-9a72-4e35-a426-cf0b3637c96f
Instance ID                     : uuid:f88ba569-bed6-4697-bdeb-91313f3f7e7c
Page Layout                     : OneColumn
Page Mode                       : UseOutlines
Page Count                      : 36
EXIF Metadata provided by EXIF.tools

Navigation menu