Trane Voyager 12 5 To 25 Tons Installation And Maintenance Manual RT SVX49* EN Tracer™ TD Display For ReliaTel™ Controller November 2013

2015-04-02

: Trane Trane-Voyager-12-5-To-25-Tons-Installation-And-Maintenance-Manual-684205 trane-voyager-12-5-to-25-tons-installation-and-maintenance-manual-684205 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 36

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.
TracerTD-5 Display
for ReliaTel™ Controller
Installation, Operation,
and Maintenance
RT-SVX49A-EN
November 2013
© 2013Trane All rights reserved RT-SVX49A-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provided to alert
installing contractors to potential hazards that could result
in death or personal injury. Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughly before operating or servicing
this unit.
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earths naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
ATTENTION: Warnings, Cautions, and Notices appear at
appropriate sections throughout this literature. Read
these carefully:
WARNING Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTIONsIndicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
NOTICE: Indicates a situation that could result in
equipment or property-damage only
accidents.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians
MUST put on all Personal Protective Equipment (PPE)
recommended for the work being undertaken.
ALWAYS refer to appropriate MSDS sheets and OSHA
guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.
Failure to follow recommendations could result in death
or serious injury.
Table of Contents
RT-SVX49A-EN 3
Warnings, Cautions and Notices .......... 2
Introduction ............................. 4
Hardware ............................. 4
Power ............................. 4
Communication ..................... 4
Screen characteristics ................ 4
Touchscreen Guidelines ................ 4
Dimensions ........................... 5
Specifications and Agency Compliance ... 6
Supported Languages .................. 6
Screen Overview ...................... 7
Top Display Area .................... 7
Main Display Area ................... 7
Bottom Display Area ................. 7
Installing the Tracer™ TD-5 Display ....... 8
Packaged Contents .................... 8
Additional Mounting Parts ............. 8
Installing the TD-5 Display onto a VESA
Mounting Bracket ...................... 8
Powering up the TD-5 Display for the First
Time ................................. 9
Alarms ................................. 10
Active Alarms ........................ 10
Historic Alarms ....................... 11
Viewing Active and Historic Alarms ..... 11
Alarm Icons .......................... 12
Sorting Alarms ....................... 12
Reports ................................ 13
Custom Reports ...................... 13
Creating a Custom Report ............ 13
Editing a Custom Report ............. 15
About ............................... 16
System Report ....................... 17
Economizer/Ventilation Report ......... 18
Compressor Report ................... 18
Heating Report ....................... 19
Configuration Report .................. 19
Sensor Report ........................20
Binary Input Report ...................20
Binary Output Report ..................21
Graphs .................................22
Creating a Custom Graph ..............22
Standard Graphs ......................25
Space Temperature: .................25
Compressor Graph: ..................25
VAV System: .......................26
Economizer Graph: ..................26
Outside Air Ventilation: ..............26
CO2Graph: .........................26
Humidity Graph: ....................26
Heat Pump Graph: ...................26
Settings ................................27
Setpoints ............................27
Setup ................................28
Display Settings Screen ................29
Display Preferences .................29
Language ..........................31
Date and Time ......................31
Clean Touchscreen ..................32
Troubleshooting ........................33
Identifying and Diagnosing Issues .......33
4 RT-SVX49A-EN
Introduction
The purpose of this guide is to assist you in installing,
programming, and operating theTracer™TD-5 display,
which operates with the ReliaTel™ Controller.This guide
describes how to access the screens and the types of
information that appear on the screens.
TheTracer™TD-5 display allows you to view data and
make operational changes on the following types of
applications:
• Voyager™
• Precedent™
Hardware
TheTracer™TD-5 is a durable touch screen display that is
designed to operate in both indoor or outdoor
environments.TheTD-5 display utilizes a standard 75mm
VESA mounting pattern for installation. Alternatively, it
can be installed with a user-supplied VESA mount.
Power
TheTracer™TD-5 display is powered by 24 VAC or 24 VDC
and requires 21 VA power, which it receives through a
power cable.The display is typically connected to J10 of
the RTRM Module, but it can also be powered from an
alternate power source.
Communication
Communication is provided to theTD-5 through the RTRM
J10 connector.
Screen characteristics
The 5-inch WVGA 800 x 480 resolution touch-sensitive
color screen is LED backlit, which enables viewing in poor
light conditions including outdoor usage (with the
exception of direct sunlight).
Touchscreen Guidelines
The touch screen registers the downward pressure of a
touch. Light, quick, yet deliberate touches are most
effective.Touching with more pressure has no effect.
Recommended tools to use:
• finger
• thumb
pencil eraser
Do not use:
a screwdriver
a pen
a pencil point
any other sharp or pointed object that might scratch
the screen surface
Introduction
RT-SVX49A-EN 5
Dimensions
32,0][3.1
42,1][7.1
154,0
][1.6
147,0
][8.5
106,4
][2.4
115,3
][5.4
Note: The power cable is permanently attached
to theTD-5 display. The power connector
provides strain relief and protection from the
Introduction
6 RT-SVX49A-EN
Specifications and Agency
Compliance
Supported Languages
TheTD-5 display supports 26 built-in languages. For help
on how to select a specific language for the display, see
“Language,” p. 31.
Specification
Input power: 24 Vac ± 15%, or 24 Vdc ± 10% 21 VA, 50 or
60 Hz
Storage
temperature:
–67°F to 203°F (–55°C to 95°C)
Humidity: Between 5% to 100% (non-
condensing)
Operating
temperature:
Temperature: –40°F to 158°F (–40°C to 70°C)
Humidity: Between 5% to 100% (non-
condensing)
Mounting weight: Mounting surface must support 0.93 lb (422
grams)
Mounting Type: VESA (75 mm x 75 mm)
Environmental
rating
(enclosure):
IP55 (dust and strong water protected)
(PN: X19070632020)
Agency Compliance
UL916 PAZX, Open Energy Management Equipment
UL94-5V, Flammability
FCC CFR Title 47, Part 15.109: Class A Limit, (30 MHz – 4 GHz)
CE EMC Directive 2004/108/EC
CE EMC Directive 2004/108/EC
Arabic Hungarian Romanian
Chinese (Simplified) Indonesian Russian
Chinese (Traditional) Italian Spanish (Mexico)
Czech Japanese Spanish (Spain)
Dutch Korean Swedish
English Norwegian Thai
French Polish Indonesian
German Portuguese (Brazil) French Canadian
Hebrew Portuguese (Portugal)
Introduction
RT-SVX49A-EN 7
Screen Overview
There are three distinct areas on theTD-5 screens:
Top display area
Main display area
Bottom display area
Top Display Area
Main Display Area
This area serves as the main task area in which you can
view custom graphics, create reports, view and take action
on alarms, and view or change display settings.
Bottom Display Area
The bottom display area contains functional buttons that
provide a link to the appropriate screen.
Figure 1. Tracer™ TD-5 display screen
Main display
area
Top display area
Bottom display
area
The Back button, when touched, returns
to the previous screen visited.
The Home button, when touched,
navigates to the Home Page. Home can be
configured. See “Display Preferences,
p. 29.
The Header Data Point is a user-defined
data point that will appear at the top
portion of each display screen. This value
can be the present value of any point in
the TD-5. See “Header Data Point,” p. 29.
Screen brightness settings: Touch this
icon to change the display’s brightness.
Touch this button to open the Alarms
screen. When an alarm is present, this
button will flash red.
Touch this button to navigate to the
Reports screen.
Touch this button to open the Data Graphs
screen to view Graphs.
Touch this button to open the Settings
screen, which contains options for
controls, security (if enabled), and
display settings.
Language selection: Touch this icon to
select a language that will be displayed on
all screens.
8 RT-SVX49A-EN
Installing the Tracer™ TD-5 Display
This section describes installation procedures when
mounting theTracer™TD-5 display near the RTRM
module or remotely mounted up to 328 ft (100 m) by using
a field-suppled 75 mm VESA mounting bracket. Read and
observe all warning and caution statements before you
begin the installation procedure.
Packaged Contents
One (1)Tracer™TD-5 display with permanently
attached 2.6 ft (0.8 m) power cable with male connector
Four (4) M-4 screws
Four (4) spacer washers
Additional Mounting Parts
TD-5 Display Low Profile Mounting Bracket (VESA
75mm) (PN: X05010511010)
Installing the TD-5 Display onto a
VESA Mounting Bracket
TheTracer™TD-5 can be mounted near the RTRM module
in the control panel, or remotely mounted up to 328 ft
(100 m) by using a field-suppled 75 mm VESA mount.
Remote mounting requires the following additional field-
supplied components:
A power source that will supply 24 VAC to the display
Power cables
Many commercial 75mm VESA mounting brackets are
available, which range from a simple wall mount to tilt-
and-swivel mounts such as the one shown in Figure 2, p. 9,
or theTD-5 Display Low Profile Mounting Bracket (VESA
75mm) (PN: X05010511010).
To install onto a VESA mounting bracket:
1. Disconnect power at the circuit breaker and perform
lockout/tagout procedures.
2. Mount the VESA mounting bracket according to
manufacturers instructions.
3. Position theTD-5 display 1onto the VESA mounting
bracket 2and align the four mounting holes with the
bracket while inserting and hand-tightening the four
M-4 screws. (Some brands ofVESA mounting brackets
may require the use of the four spacer washers to allow
the M-4 screws to tighten properly.)
4. Securely tighten the M-4 screws using a Phillips
screwdriver.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Installing the Tracer™ TD-5 Display
RT-SVX49A-EN 9
Powering up the TD-5 Display for
the First Time
After completing the installation instructions in “Installing
theTracer™TD-5 Display,” p. 8,TheTD-5 display can be
powered up.
Before applying power to theTD-5 Display, verify that the
RTRM Module is powered up.
Upon successful power up, theTD-5 Display will default to
the configured home screen.The System Report is the
factory default.
Important: Do not attempt to update theTD-5 Display
from a connection type other than a USB.
Figure 2. Example VESA mounting
12
10 RT-SVX49A-EN
Alarms
Alarms appear on theTracer™TD-5 display immediately
upon detection.Touch the Alarms button in the bottom
display area to view the Alarms screen.
Active Alarms
Figure 3, p. 10 shows the Active Alarms screen and
commonly used functions. Configuration is not required in
order for points in alarm to appear in the Active Alarms
screen. When the alarm clears and the point returns to
normal, the alarm will automatically be removed from the
list.The number of active alarms is displayed in the top
right portion of the screen. When an active alarm is
present, the alarm button at the bottom of the screen will
flash.
The Alarms screen defaults to Active Alarms.The Active
Alarms button has a shaded appearance which indicates
that you are viewing active alarms.
Figure 3. Active alarms screen
Number of active alarms
Active Alarms
button
Alarm severity
Sortable
columns
Alarms
RT-SVX49A-EN 11
Historic Alarms
On the Alarms screen, touch the Historic Alarms button to
view all alarms, commonly referred to as the event log (see
Figure 4, p. 11).
Viewing Active and Historic
Alarms
Active alarms:These are alarms that require attention.
All alarms that are currently active appear when you
view this category. Active alarms are not reset by way
of the display. Active alarms will clear automatically
when the condition causing the alarm is removed.
Historic alarms: Historic alarms appear when you view
this category.The alarms are listed in chronological
order.
Alarm Severity
A color-code icon representing the severity of each alarm
is shown under the severity (!) column. For a description
of the five alarm icons, see Table 1, p. 12.
Sortable Alarms
You can sort active alarms by touching one of the column
headers. Choose to sort by severity (!), date and time,
point name, or description.
Figure 4. Historic alarms screen
Sortable
columns
Alarm severity
Historic Alarms button
Number of historic
alarms
Alarms
12 RT-SVX49A-EN
Alarm Icons
Alarms icons appear in the left-most column of the alarms
screen.They are identifiable by their shape and color.
Sorting Alarms
To sort alarms by a category other than date and time,
touch one of the other column headings in the table.The
column heading responds by changing to blue, and the
alarms table re-sorts according to the blue column
heading. By touching the blue column heading again, the
column will change the sort direction.
Severity (!): Active alarms are at the top, followed by
the most severe, followed by the most recent.
Date andTime (the default sort): Most recent alarms
are at the top.
Description: Alarms are sorted alphabetically by
description.
Table 1. Alarm icons
Active
Alarm Icons Notification Class
Critical
Service Required
Information
Note: Notifications classes are configured in point alarm settings section
in Tracer TU.
Table 2. List of alarms
Space Temp Sensor Failure Outdoor Temp Sensor Fail
Compressor 1 HPC Lockout Compressor 1 LPC Lockout
Comp 1 Disable Input/LPC Compressor 2 HPC Lockout
Compressor 2 LPC Lockout Comp 2 Disable Input/LPC
Smoke Detector Heat Failure
Dirty Filter Supply Fan Failure
Emergency Stop Frostat™ Trip
Mixed Air Temp Sensor Fail OA Humidity Sensor Failure
Return Air Temp Sensor Fail Return Air RH Sensor Failure
Coil Temp Sensor #1 Fail Demand Defrost Fault A
Demand Defrost Fault B Demand Defrost Fault C
Demand Defrost Fault D Defrost Default Mode
Local Cool Setpoint Fail Local Heat Setpoint Fail
Vent Override – Purge Vent Override – Exhaust
Vent Override – Pressurize Drain Pan Overflow
Freezestat Tripped Supply Air Temp Sensor Fail
CO2 Sensor Failure CO2 Setpoint Failure
Space Humidity Sensor Fail Dehumid Setpoint Failure
Air Flow Sensor Fail Min OA Flow Setpoint Fail
Space Pressure Setpoint Fail Space Pressure Sensor Fail
Heating High Temp Limit Open Flame Rollout Switch Open
Inducer Proving Switch Fail No Flame Sensed on heat call
Flame Sensed w/Gas Valve Off Gas Heat Module Failure
Economizer Actuator Fault Morning Warmup Setpoint Fail
SA Reset Amount Failure SA Temp Cool Setpoint Fail
SA Temp Heat Setpoint Fail SA Reset Setpoint Failure
SA Press Setpoint Fail SA Pressure Deadband Fail
Supply Air Press Sensor Fail SA High Press Limit
SA Pressure PWM Fault Comp 1 Disable Input/HPC
Comp 2 Disable Input/HPC CO2 Low Limit Setpoint Fault
Exh/Ret Fan Proving Failure RTOM Comm Fail
RTEM Comm Fail RTAM Comm Fail
RTVM Comm Fail RTCM Comm Fail
SA Reheat Setpoint Failure RTDM Comm Fail
Space Press Deadband Fail Mod Dehumid Config
Ent Evap Temp Sensor Fail Coil Temp Sensor #2 Fail
SA Temp Heat Setpoint Fail Demand Defrost Fault A Ckt 2
Demand Defrost Fault B Ckt 2 Demand Defrost Fault C Ckt 2
Defrost Default Mode Ckt 2 Demand Defrost Fault A Ckt 1
Demand Defrost Fault B Ckt 1 Demand Defrost Fault C Ckt 1
Defrost Default Mode Ckt 1 Exhaust Fan Setpoint Fail
IGN1 Communications Timed out IGN2 Communications Timed out
DCV Min Position Setpoint Fail (@
Full Fan Speed) Design Min Position Setpoint Fail
(@ Full Fan Speed)
Enthalpy Setpoint Fail Design Min Position at Minimum
Fan Speed Fail
DCV Min Position at Minimum Fan
Speed Fail Design Min Position at Midpoint
Fan Speed Fail
DA Cool Setpoint Fail PWM Max Fan Spd Setpt Fail
Compressor 3 HPC Lockout Compressor 3 LPC Lockout
Comp 3 Disable Input/LPC Comp 3 Disable Input/HPC
Power on Reset TD-5 Loss of Comm with RTRM
Table 2. List of alarms (continued)
RT-SVX49A-EN 13
Reports
You can use theTracer™TD-5 Display to view a variety of
reports and create and edit custom reports.
Touch the Reports button in the bottom display area to
view the Reports screen.The Reports screen contains the
following buttons:
Custom Reports
You can create up to three custom reports using the
Tracer™TD-5 Display
Creating a Custom Report
1. Navigate to the Reports screen, then touch one of the
three custom report buttons.
The Custom Report (1, 2, or 3) screen appears.
2. Touch the Edit button.
The Edit Custom Report screen appears (Figure 6,
p. 14).
Table 3. Representation of screen below
Custom Report 1 System Report About
Custom Report 2 Compressor Report Sensor Report
Custom Report 3 Operating Modes Configuration Report
Economizer/
Ventilation Report Heating Report
Binary Input Report Binary Output Report
Figure 5. Reports screen
Reports
14 RT-SVX49A-EN
3. Use the up and down arrow buttons to select a point.
Add items by touching the item that is highlighted
blue, then touch the Add button.
4. Continue adding values to your report. When you are
finished, touch the Save button.
The Custom Report screen, populated with your
selected values, appears (Figure 7, p. 14).
To view the items in the selected list, touch a value in
this list and use the up and down arrows to the right of
the list.To change the location of an item in the list,
select the item and then use the up and down arrows
above the table to move the items.
Figure 6. Creating a custom report
Figure 7. New custom report screen
Reports
RT-SVX49A-EN 15
Editing a Custom Report
1. Touch Reports to view the Reports screen.
2. Touch the report that you want to edit.
Follow steps 2 through 4 in “Creating a Custom
Report,” p. 13. to complete your edits.
Changing the Order of Items in a Custom
Report
Items in a custom report can be rearranged according to
personal preference by using the editing tools as
described in Editing a Custom Report.
For example, you created the custom report shown in
Figure 7, p. 14, but would prefer to move item “Diagnostic:
Space Static Pressure Failure” to the top left portion of the
report.
To change the order for the example described above:
1. Touch the Edit button on the Custom Report screen.
2. Use the arrow buttons to locate the item to be
reordered. When located, touch the item which will
then be highlighted blue (see Figure 8, p. 15).
3. Use the arrow buttons to move the highlighted item to
the top of the list (number 1 position).
4. Touch Save.You will be returned to the Custom Report
screen, where the reordering changes now appear.
Note: On theTD-5 display, report items are ordered from
left to right with the first item appearing at the top
left portion of the screen. Up to nine items can
appear on each Custom Report screen.
The model in Figure 9, p. 15 depicts a custom report
screen with the first nine items displayed on the screen.
Use this model to accurately reorder items in your custom
reports.
Figure 8. Editing a custom report
Scroll buttons
to navigate
through the
data list
Buttons that
re-order your
custom
report list
Scroll buttons
to navigate
through the
data list
Category
Selector
Figure 9. Custom report (order of items)
Custom Report
123
456
789
Reports
16 RT-SVX49A-EN
About
Touch the About button to view the About screen. View
information about the unit controller and theTD-5 display
to which it is connected.Touch the arrow button to scroll
to the next screen.
Data Area
The following data are displayed on the About screen.
Unit Name. This is the name that was entered.
Figure 10. About screen
Unit Name
ABCDEFGHIJKLMNOPQRSTUVWXYZ12456789
RTRM Software Version
6200-XXXX-YY.ZZ RTVM Software Version
6200-XXXX-YY.ZZ VSM Software Version
6200-XXXX-YY.ZZ
RTOM Software Version
6200-XXXX-YY.ZZ RTAM Software Version
6200-XXXX-YY.ZZ RTEM Software Version
6200-XXXX-YY.ZZ
RTDM Software Version
6200-XXXX-YY.ZZ BAS Interface Software Version
6200-XXXX-YY.ZZ
Display User Interface Software Version
6200-XXXX-YY.zz Display Firmware Version
6200-XXXX-YY.zz Display Boot Code Version
6200-XXXX-YY.zz
Reports
RT-SVX49A-EN 17
System Report
Touch the System Report button to view the System
Report screen.Touch the arrow buttons to move between
screens.
Data Area
The following data can be configured to appear on the
System Report screen. Only configured items will appear.
Figure 11. System report screen
Unit Application
VAV,CV,SZVAV Unit Mode
Heat, Cool, Off, Emergency Heat Setpoint Source
Remote, Local
Supply Fan Output
Energized, De-energized Supply Fan Speed %
XXX % Supply Fan Mode
On, Auto
Occupancy
Occupied, Unoccupied Active Cooling Stages
XActive Heating Stages
X
Active Space Temp
XXX.X F/C Active Space Temp Setpoint
XXX.X F/C Outdoor Air Damper %
XXX % Open
Supply Air Temp
XXX.X F/C Active Supply Air Temp Setpoint
XXX.X F/C System Control Mode
Manual, Auto
Economizing
Enabled, Disabled
Ventilation Type
Fixed/DCV
(*DCV = Demand Control Ventilation)
Variable Compressor Speed %
XXX %
Fresh Air Measurement
Installed, Not Installed Demand Limit
Active/Not Active Heating Type
None, Electric, Gas, Hydronic
Exhaust Fan Status Available Cooling Stages
XAvailable Heating Stages
X
Supply Fan Starts
XXXXX Supply Fan Running Time
HHHHH:MM Space Pressure
X.XX in(H2O)/ mm(H20)
Supply Air Pressure
X.XX in(H2O)/ mm(H20) Local Space Temp
X XX.X OF/C Emergency Stop Input
RTOM Low Fan Speed Output Alarm Indicator Output VAV Box Output
Thermostat Y1 Input Thermostat W1/O Input Thermostat G Input
Thermostat W2 Input Thermostat Y2 Input Thermostat X2 Input
Supply Fan Proving Input Condensate Drain Overflow Input Frostat™ Input
Clogged Filter Input Smoke Detector Input Reheat Humidistat Input
Changeover Switch Input
Reports
18 RT-SVX49A-EN
Economizer/Ventilation Report
Touch the Economizer/Ventilation Report button to view
the Economizer/Ventilation Report screen.Touch the arrow
buttons to move between screens.
Data Area
The following data can be configured to appear on the
Economizer/Ventilation Report screen. Only configured
items will appear.
Compressor Report
Touch the Compressor Report button to view the
Compressor Report screen.Touch the arrow buttons to
move between screens.
Data Area
The following data can be configured to appear on the
Compressor Report screen. Only configured items will
appear.
Outdoor Air Damper %
XXX % Open Economizing
Enabled, Disabled Mixed Air Temp
XXX.X F/C
Ventilation Type Economizing Enable Type
Dry Bulb, Reference Enthalpy, Comparative
Enthalpy
Outdoor Air Temp
XXX.X F/C
Active Min OA Damper Position Target
XXX % Manual Enthalpy Override
Enabled, Disabled Return Air Temp
XXX.X F/C
Active Upper CO2 Limit Setpoint
XXXX PPM Active Lower CO2 Limit Setpoint
XXXX PPM Space CO2
XXXX PPM
Active Enthalpy Setpoint
XXXXX BTU / LBM Return Air Humidity
XXX % Outdoor Air Humidity
XXX %
Outdoor Air Flow
XXXXX CFM / LPM Min Outdoor Air Flow Target
XXXXX CFM / LPM Min Outdoor Air Flow Deadband
XXXXX CFM / LPM
Design Min Position High Speed Setpoint
XXX % Design Min Position Mid Speed Setpoint
XXX % Design Min Position Low Speed Setpoint
XXX %
DCV Min Position High Speed Setpoint
XXX % DCV Min Position Low Speed Setpoint
XXX % Power Exhaust Fan Output
Off, On, Auto
DCV Min OA Flow Setpoint
XXXXX CFM / LPM Outdoor Air Flow Adjustment Setpoint Exhaust Fan Starts
XXXXX
Exhaust Fan Running Time
HHHHH:MM Exhaust Damper Position % Open
XXX % Space Pressure
XX.XX IWC /cmWC
Active Space Pressure Setpoint
XX.XX IWC /cmWC Space Pressure Deadband
XX.XX IWC /cmWC Outdoor Fan A Output
Outdoor Fan B Output Variable Speed Outdoor Fan % Ventilation Override Pressurize Input
Ventilation Override Purge Input Ventilation Override Exhaust Input Power Exhaust Fan Output
Supply Fan Proving Input
Table 4. Compressor report - data area
Active Cooling Stages
XAvailable Cooling Stages
XNumber of Compressors Installed
X
Outdoor Fan A Output
Energized, De-energized Outdoor Fan B Output
Energized, De-energized Variable Speed Outdoor Fan %
XXX.X %
Dehumidification Status
Inactive, Active Reheat, Active Enhanced Reheat Entering Evap Temp
XXX.X F/C Variable Compressor Speed %
XXX.X %
Compressor 1 Disable Input
Enabled, Disabled Compressor 2 Disable Input
Enabled, Disabled Compressor 3 Disable Input
Enabled, Disabled
Compressor 1 Proving Input
Open, Closed Compressor 2 Proving Input
Open, Closed Compressor 3 Proving Input
Open, Closed
Heatsink Refrigerant Temperature
XXX.X F/C Supply Air Temp
XXX.X F/C Space Temp
XXX.X F/C
Active Space Cooling Setpoint
XXX.X F/C Defrost Status Ckt 1
Inactive, Defrosting Defrost Status Ckt 2
Inactive, Defrosting
Active Supply Air Temp Cooling Setpoint
XXX.X F/C Switchover Valve (SOV) 1 Output
Heating, Cooling Switchover Valve (SOV) 2 Output
Heating, Cooling
Outdoor Coil Temp Ckt 1
XXX.X F/C Outdoor Coil Temp Ckt 2
XXX.X F/C Compressor 1 Starts
XXXXX
Reports
RT-SVX49A-EN 19
Heating Report
Touch the Heating Report button to view the Heating
Report screen.Touch the arrow buttons to move between
screens.
Data Area
The following data can be configured to appear on the
Heating Report screen. Only configured items will appear.
Configuration Report
Touch the Configuration Report button to view the
Configuration Report screen.Touch the arrow buttons to
move between screens.
Data Area
The following data can be configured to appear on the
Configuration Report screen. Only configured items will
appear.
Compressor 2 Starts
XXXXX Compressor 3 Starts
XXXXX Compressor 1 Running Time
HHHHH:MM
Compressor 2 Running Time
HHHHH:MM Compressor 3 Running Time
HHHHH:MM Number of Compressors Installed
Variable Speed Compressor Reheat Pumpout Relay Defrost Starts Ckt 1
XXXXX
*Phase 2
Table 4. Compressor report - data area (continued)
Table 5. Heating report - data area
Heating Type
None, Electric, Gas, Hydronic Heating Configuration
Staged /Modulating Available Heating Stages
X
Active Heating Stages
XSpace Temp
XXX.X F/C Modulating Heat Output %
XXX %
Gas Heating Status Supply Air Temp
XXX.X F/C Defrost Status Ckt 1
Inactive, Defrosting
Defrost Status Ckt 2
Inactive, Defrosting Active Space Heating Setpoint
XXX.X F/C Outdoor Coil Temp Ckt 1
XXX.X F/C
Outdoor Coil Temp Ckt 2
XXX.X F/C Active Supply Air Temp Heating Setpoint
XXX.X F/C Heating Stage 1 Output
Active, Inactive
Heating Stage 2 Output
Active, Inactive Freezestat Input
Open, Closed Outdoor Air Temp
XXX.X F/C
Gas Heating Type IGN Pressure Switch Input
IGN Temp Limit Input IGN Flame Rollout Input IGN Inducer High Output
IGN Inducer Low Output
Table 6. Configuration report - data area
Unit Application
CV, VAV, SZVAV Refrigeration Type
Cooling Only, Heat Pump
Product Type
Voyager™ Commercial, Precedent™/
Precedent™ 17 Plus/Voyager™ Light
Commercial/Odyssey™
Dehumidification
None, Hot Gas Reheat, Enhanced Supply Fan Control Type
Fixed, Variable, IGV Economizer
Installed, Not Installed
Dehumidification Type
Staged, Modulating Heating Type
None, Electric, Gas, Hydronic CV Control Type
Zone Sensor, Thermostat
Cooling Stages Configured
XCooling Steps Input
3 Step, 2 Step Number of Compressors Installed
X
Heating Stages Configured
XVariable Speed Compressor
Installed, Not Installed
Economizer Enable Type
Drybulb, Reference Enthalpy, Comparative
Enthalpy
Supply Fan Motor Type
Fixed, VFD, ECM, ERM Supply Fan Motor Control
0 to 10VDC, PWM
Heat Pump Type
Single, Independent Windmill Prevention
Enable, Disable Gas Ignition Module 1
Staged, Modulating
True Supply Air Reporting
Enable, Disable Supply Air Tempering Input
Enable, Disable Gas Ignition Module 2
Installed, Not Installed
Reports
20 RT-SVX49A-EN
Sensor Report
Touch the Sensor Report button to view the Sensor Report
screen.Touch the arrow buttons to move between screens.
Data Area
The following data can be configured to appear on the
Sensor Report screen. Only configured items will appear.
Binary Input Report
The Binary Input report provides general Reliatel Unit
operating information.Touch the Binary Input Report
button to view the Binary Input Report screen.
Data Area
The following data can be configured to appear on the
Configuration Report screen. Only configured items will
appear.
Manual Enthalpy Override
Enable, Disable Lead Lag Configuration Input
Enable, Disable OA Flow Compensation
Enable, Disable
Outdoor Fan Cycling Input
Normal, Lower Programmable Zone Sensor
Installed, Not Installed Cabinet Type
Horizontal, Downflow
Outdoor Air Flow Compensation
Enable, Disable Evaporator Defrost Control
Enable, Disable RTRM Fan Proving Input
Closed, Open
Supply Air Tempering Input
Disable, Enable Outdoor Fan Cycling Input
Normal, Lower Exhaust Air Control - StatiTrac™
Installed, Not Installed
Table 6. Configuration report - data area (continued)
Table 7. Sensor report - data area
Active Space Temp
XXX.X OF/C Local Space Temp
XXX.X OF/C Supply Air Temp
XXX.X OF/C
Outdoor Air Temp
XXX.X OF/C Mixed Air Temp
XXX.X OF/C Return Air Temp
XXX.X OF/C
Outdoor Air Humidity
XXX.X% Return Air Humidity
XXX.X% Space CO2
XXXX PPM
Outdoor Air Flow
XXXXX CFM/LPM Space Humidity
XXX% Outdoor Coil Temp Ckt 1
XXX.X OF/C
Outdoor Coil Temp Ckt 2
XXX.X OF/C Space Pressure
X.XX in(H2O)/mm(H20) Reheat Entering Evap Temp
XXX.X OF/C
Supply Air Pressure
X.XX in(H2O)/ mm(H20)
Table 8. Binary input report - data area
RTRM Emergency Stop Input
Auto, Emergency Stop Occupancy RTRM Fan Proving Input
Closed, Open
Thermostat Y1 Input
Open, Closed Thermostat W1/O Input
Open, Closed Thermostat G Input
Open, Closed
Thermostat W2 Input
Open, Closed Thermostat Y2 Input
Open, Closed Thermostat X2 Input
Open, Closed
Compressor 1 Disable Input
Closed, Open Compressor 1 Proving Input
Operating, Not Operating Compressor 2 Disable Input
Closed, Open
Compressor 2 Proving Input
Operating, Not Operating
RTOM Supply Fan Proving Input
Open, Closed Condensate Drain Overflow Input
Open, Closed Ventilation Override Pressurize Input
Open, Closed
Ventilation Override Purge Input
Open, Closed Ventilation Override Exhaust Input
Open, Closed Frostat™ Input
Open, Closed
Clogged Filter Input
Open, Closed Freezestat Input
Open, Closed Smoke Detector Input
Open, Closed
Reheat Humidistat Input
Open, Closed Changeover Switch Input
Cooling, Heating
VSM Compressor 3 Disable Input
Closed, Open Compressor 3 Proving Input
Operating, Not Operating
RTVM Exhaust Fan Proving Input
Open, Closed
Reports
RT-SVX49A-EN 21
Binary Output Report
The Binary Input report provides general Reliatel Unit
operating information.Touch the Binary Input Report
button to view the Binary Input Report screen.
Data Area
The following data can be configured to appear on the
Configuration Report screen. Only configured items will
appear.
Note: Operating Modes:The operating Mode page shall
show the user the general operation of the unit, and
what modes it is operating in.
IGN IGN Pressure Switch Input
Open, Closed IGN Temp Limit Input
Open, Closed IGN Flame Rollout Input
Open, Closed
Table 8. Binary input report - data area (continued)
Table 9. Binary output report - data area
RTRM Supply Fan Output
Off, On Compressor 1 Output
Off, On Compressor 2 Output
Off, On
Heat Stage 1 Output
Off, On SOV 1 Output
Off, On Outdoor Fan A Output
Off, On
Heat Stage 2 Output
Off, On
SOV 2 Output
Off, On
or
Low Fan Speed
or
Compressor 3 Output
Off, On
Outdoor Fan B Output
Off, On
RTOM/RTAM/RTVM/
RTEM/RTDM RTOM Low Fan Speed Output
Off, On Alarm Indicator Output
Off, On VAV Box Output
Off, On
Power Exhaust Fan Output
Off, On Reheat Pumpout Relay
Off, On
IGN IGN Inducer High Output
Off, On IGN Inducer Low Output
Off, On
Figure 12. Operating modes report details screen
22 RT-SVX49A-EN
Graphs
Graphs allow users to view data in graphical format on the
Display. Four custom graphs and eight standard graphs
are available. Graphs can be created with a maximum of
four lines per graph. Custom graphs are user-defined and
can be edited by changing the scale on the left and rightY-
axis and choosing the line color.
Touch the Graphs button in the bottom display area to view
the Graphs screen (Figure 13, p. 22).The Graphs screen
contains twelve buttons that allow you to view and edit a
particular graph.There are four custom graphs and 8
standard graphs.
Creating a Custom Graph
5. Navigate to the Graphs screen, then touch an available
data graph button.
The Custom Graph screen appears.
6. Touch the Edit Graph button.
The Edit Graph screen appears (Figure 14, p. 22).
Figure 13. Graphs screen
Figure 14. Edit graph screen
Graphs
RT-SVX49A-EN 23
7. Touch the Add/Remove button to add values to the
custom data graph.
The Add/Remove screen appears.
8. Use the arrow buttons to select a value.
9. Select the values, then touch theAdd button (up to four
selections are allowed).
10. Touch the Save button.The Edit Graph screen appears,
which reflects the selected values.
11. Use the Edit Graph screen to modify the graph.Touch
the Edit button that corresponds with the value that
you want to change. Only one value can be edited at a
time.
12. From the Edit screen you can choose whichY-axis to
display the value, a color, and whether or not to show
data samples.Touch the Save button when finished.
Repeat the process with remaining values.
Figure 15. Adding data logs to the custom graph
Figure 16. Edit graph screen (after values have been added)
Graphs
24 RT-SVX49A-EN
13.Touch the Save button to display the new graph
(Figure 18, p. 24).
Note: Depending on the sampling rate, the custom graph
may be empty for several hours.
You can make changes to the way data is presented on the
graph at anytime.Touch the zoom-in icon and zoom-
out icon to either increase or decrease the viewable
time frame.This action also enables back and forward
arrows that allow you to view data at various times of the
day.
Editing the Y-Axis
The default values on the right and leftY-axes can be
changed according to your specifications.
14. Touch the EditY-Axis button located on the top portion
of the Custom Data Graph screen.
The EditY-Axis screen appears (Figure 19, p. 25).
Figure 17. Customizing the graph
Figure 18. Viewing the graph
Graphs
RT-SVX49A-EN 25
15.Touch the Manually Select Range box for either the left
or rightY-axis.
16.Touch the edit button next to one of the two value
ranges.
The Keypad screen appears.
17. Select a new value and then touch Enter to save.
18. Repeat steps 2 through 4 until all preferred changes
have been made.
Standard Graphs
There shall be 8 standard graphs.The standard graphs are
below:
Space Temperature:
The table below describes the data in the System Status
graph:
Compressor Graph:
The table below describes the data in the graph:
Figure 19. Editing theY-Axis
Table 10. Standard graphs
Space Temperature Economizer
Compressor Outside Air Ventilation
VAV Humidity
Heat Pump CO2
Data Point Line Color Axis
Active Space Temp Setpoint Blue Left
Active Space Temp Green Left
Supply Air Temp Black Left
Return Air Temperature Red Left
Data Point Line Color Axis
Active Supply Air Temp Setpoint Pink Left
Variable Compressor Speed % Green Left
Supply Air Temp Black Left
Active Cooling Stages Blue Right
Graphs
26 RT-SVX49A-EN
VAV System:
The table below describes the data in the System Status
graph:
Economizer Graph:
The table below describes the data in the graph:
Outside Air Ventilation:
The table below describes the data in the graph:
CO2Graph:
The table below describes the data in the graph:
Humidity Graph:
The table below describes the data in the graph:
Heat Pump Graph:
The table below describes the data in the graph:
Data Point Line Color Axis
Active Supply Air Temp Setpoint Pink Left
Active Space Temp Green Left
Supply Air Temp Black Left
Return Air Temp Red Left
Data Point Line Color Axis
Outdoor Air Temp Purple Left
Mixed Air Temp Grey Left
Active Min OA Damper Position Target Pink Right
Outdoor Air Damper % Yellow Right
Data Point Line Color Axis
Min Outdoor Air Flow Target Black Left
Outdoor Air Flow Pink Left
Outdoor Air Damper % Yellow Right
Outdoor Air Temp Purple Right
Data Point Line Color Axis
Active Upper CO2 Limit Setpoint Red Left
Active Lower CO2 Limit Setpoint Black Left
Space CO2Green Left
Outdoor Air Damper % Yellow Right
Data Point Line Color Axis
Space Dehumidification Setpoint Yellow Left
Outdoor Air Humidity Red Left
Return Air Humidity Black Left
Space Humidity Green Left
Data Point Line Color Axis
Outdoor Coil Temp Ckt 1 Green Left
Outdoor Coil Temp Ckt 2 Blue Left
Outdoor Air Temp Purple Left
Discharge Air Temperature Grey Left
RT-SVX49A-EN 27
Settings
The Settings screen provides options for display settings,
language, overrides and security.Touch the Settings
button in the bottom display area to view the Settings
screen.
Three categories for settings appear on the screen:
Control Settings
Display Settings
Security Settings
Setpoints
Touch the Setpoints button to view the Setpoints screen.
Touch the arrow buttons to move between screens.
Figure 20. Settings screen
Figure 21. Setpoints screen
Settings
28 RT-SVX49A-EN
Data Area
The following data can be configured to appear on the
Setpoints screen. Only configured items will appear.
Setup
Touch the Setup button to view the Setpoints screen.
Touch the arrow buttons to move between screens.
This Setup screen shows a list of the setup items in button
format.The available setup items are listed below:
Occupied Space Cooling Setpoint Unoccupied Space Cooling Setpoint Space Dehumidification Setpoint
Occupied Space Heating Setpoint Unoccupied Space Heating Setpoint Supply Air Reheat Setpoint
Discharge Air Heating Setpoint Discharge Air Cooling Setpoint Duct Static Pressure Setpoint
Duct Static Pressure Deadband Morning Warm-up Setpoint Supply Air Cooling Setpoint
Supply Air Heating Setpoint Daytime Warm-up Initiate Setpoint Space Pressure Setpoint
Space Pressure Deadband Daytime Warm-up Terminate Setpoint CO2 Upper Limit Setpoint
CO2 Lower Limit Setpoint Enthalpy Setpoint Supply Air Reset Setpoint
Exhaust Fan Enable Setpoint Supply Fan Adjustment Setpoint Outdoor Air Flow Adjustment Setpoint
Design Min OA flow Setpoint DCV Min OA Flow Setpoint Min OA Flow Deadband
Design Min OA Damper Pos Setpoint 100% Fan Design Min OA Damper Pos Setpoint Mid Fan Design Min OA Damper Pos Setpoint Min Fan
DCV Min OA Damper Pos Setpoint 100% Fan DCV Min OA Damper Pos Setpoint Min Fan Outdoor Air Flow Adjustment Setpoint
Figure 22. Setup screen
Unit Mode
Heat, Cool, Auto Supply Fan Mode
On, Auto Emergency Heat Mode Request
Auto, Emergency Heat
System Control Mode
Local, Remote Display Read Only Mode
Read, Write
Supply Air Reset Type
Heat, Cool, Auto
Service Test
Disable, IGV Close, IGV Open,
Fan Only/Min Vent,
Economizer Open, Cool 1, Cool 2, Cool 3,
Dehumid/Reheat, Heat 1, Heat 2, Heat 3,
Defrost, Emergency Heat
Settings
RT-SVX49A-EN 29
Display Settings Screen
The selections in this category contain settings that affect
the way in which information is displayed on all of theTD-
5 display screens. From each screen, the current settings
can be viewed.To change a setting, touch the preferred
value.
Display Preferences
Touch the Display Preferences button to open the
associated screen (Figure 23, p. 29). On this screen, all
available options to display information on theTD-5
screens are available.There are two pages on this screen,
accessed by using the arrow button at the bottom of the
screen.
Date Format
Touch the Date Format button to open the associated
screen.Three options are available to display the current
date: MMDDYYYY, DDMMYYYY, and YYYYMMDD.
Date Separator
Touch the Date Separator button to open the associated
screen.Three options are available to display separators
in the date format: None, Hyphen (-), or Slash (/).
Time Format
Touch the Time Format button to open the associated
screen.Two options are available: 12-Hour format and 24-
Hour format (also referred to as “military time”).
Unit System
Touch the Unit System button to open the associated
screen.Two options are available: SI (system
international) or IP (Inch-Pound).
Brightness
Touch the Brightness button, or the brightness icon
( )located at the bottom left of each screen, to open the
associated screen. Screen brightness is measured in
percentage. Use the keypad to enter a new brightness
number.
Backlight Time-out
Touch the Backlight Time-out button to open the
associated screen.This value is measured in minutes, with
30 being the maximum limit. Use the keypad to enter a
backlight time-out value.This value is the amount of time
that the display will remain lit without activity. When the
backlight times out, users will be automatically logged off
due to inactivity.
Header Data Point
Use the arrow button on the Display Preferences screen to
advance to page 2.Touch the Header Data Point button to
open the associated screen.The Header Data Point
appears in the top right display area on all screens. Use the
arrow buttons to scroll through the points. Click Add to
move the highlighted point to the right side of the
screen(Figure 24, p. 30). Click Save.
Figure 23. Display preferences screen
Settings
30 RT-SVX49A-EN
Collection Frequency
Collection frequency sets the time interval that the Graph
Data is saved, and displayed on the graph.The faster the
sample rate, the lower the duration.The default of 30
seconds shall provide 3.5 days of data collection.
Figure 24. Setting the header data point
Header data
point
Figure 25. Collection frequency
Settings
RT-SVX49A-EN 31
Home Page
Use the arrow button on the Display Preferences screen to
advance to page 2.Touch the Home Page button to open
the associated screen.This function allows you to choose
what will display when the home button is touched.
Language
Touch the Language button, or the language icon ( )
located at the bottom right of each screen, to open the
open the Language screen.Twenty-six languages are
available and represented on the selection buttons. Select
a language that you want displayed on eachTD-5 screen
and then touch Save.See“Language,” p. 31.
Date and Time
Touch the Date andTime button to open the associated
screen.To enter a new date or time, touch the digit you
want to change. When enabled for editing, the digit will
appeared with a black border. when finished, touch Apply
or Save.Or,
Figure 26. Home page screen
Figure 27. Language screen
Settings
32 RT-SVX49A-EN
tap the digit twice which opens the keypad screen where
you can make date and time entries. When finished, touch
Enter; you will be returned to the Date andTime screen.
Touch Apply or Save.
Clean Touchscreen
Touch the CleanTouchscreen button to safely clean theTD-
5 touchscreen using any brand of common household
glass cleaner. When this button is touched, the screen
background color becomes black, allowing dirt and
fingerprints to become more visible. It also displays a
countdown timer (five to zero seconds).Touch the screen
anytime within the 5-second countdown to begin cleaning
the screen (each touch resets the 5-second countdown).
Figure 28. Date and time screen
RT-SVX49A-EN 33
Troubleshooting
This section describes the possible error messages and
other issues that you may encounter while using the
Tracer™TD-5 display.
Important: There are no serviceable parts within the
TD-5 display enclosure. Opening the
enclosure will void the product warranty.
Identifying and Diagnosing Issues
Problem Possible Cause Possible Solution
Blank display (TD-5 does not respond
to touch). No power. Verify that the TD-5 is connected to a power source,
and that the power source is in working condition.
After powering up, the TD-5 displays
a message that it is not
communicating. Controller not powered up. Replace cable if necessary. Power up the controller if
necessary.
No data available in custom report. Data has not yet been defined for the report. Add data to report. See “Creating a custom report,
p. 14.
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments,the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
We are committed to using environmentally
conscious print practices that reduce waste.
© 2013Trane All rights reserved
RT-SVX49A-EN 04 Nov 2013
(NEW)

Navigation menu