Trane Xt302C Users Manual 69 1213 Deluxe Programmable Heat Cool Thermostat
xt302c1 614778bd-5448-413a-9b3c-b5a54c28ec8b Trane Thermostat XT302C User Guide |
2015-01-21
: Trane Trane-Xt302C-Users-Manual-236269 trane-xt302c-users-manual-236269 trane pdf
Open the PDF directly: View PDF .
Page Count: 12
Download | ![]() |
Open PDF In Browser | View PDF |
XT302C Deluxe Programmable Heat-Cool Thermostat 18-HD25D7-5 INSTALLER'S GUIDE APPLICATION The XT302C Deluxe Programmable Heat-Cool Thermostat provides electrnic control of 24 Vac single-zone multistage systems. Refer to Table 1 for a general description of the thermostat. This thermostat requires a common wire to supply power. Table 1. Description of XT302C. Model System Changeover System Selection Fan Selection XT302C Multistage Automatic Heat-Off-Cool-Auto On-Auto RECYCLING NOTICE If this thermostat is replacing a thermostat that contains mercury in a sealed tube, do not place your old thermostat in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat. Comments System and fan selections are done by keyboard. Wallplate Installation Position wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box. 1. Position and level the wallplate for appearance only (the thermostat will function properly even when not level). INSTALLATION YES NO When Installing this Thermostat... 1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After completing installation, use these instructions to check out the product operation. Location Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1. Avoid installing the thermostat where it can be affected by the following: • Drafts, or dead spots behind doors and in corners. • Hot or cold air from ducts. • Radiant heat from sun or appliances. • Concealed pipes and chimneys. • Unheated (uncooled) areas such as an outside wall behind the thermostat. ® U.S. Registered Trademark Copyright © American Standard Inc. 1999 NO NO 5 FEET [1.5 METERS] M17106 Fig. 1. Typical location of thermostat. 69-1213-1 XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT COMPRESSOR CONTACTOR 2 COMPRESSOR CONTACTOR 1 WALL ANCHORS (2) G HEAT STAGE 2 HEAT STAGE 1 H R H OT OT RED W2 GREEN W1 BLACK Y2 WHITE BLUE WIRES THROUGH WALL Y1 YELLOW B WALL BROWN THERMOSTAT HUMIDISTAT OPENS ON RISE TAYSTAT253A OUTDOOR TEMPERATURE SENSOR TAYSENS100A L1 (HOT) FAN 1 L2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. TRANSFORMER M17116 Fig. 3. Typical hookup of XT302C in a heat cool system. MOUNTING HOLES MOUNTING SCREWS M15044 FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM). Fig. 2. Mounting the wallplate. FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM). M4826 Fig. 4. Proper wiring technique. 2. Use a pencil to mark the mounting holes. See Fig. 2. 3. Remove the wallplate from the wall and drill two 3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall. 4. Position the wallplate over the holes, pulling wires through the wiring opening. 5. Loosely insert the mounting screws into the holes. 6. Tighten mounting screws. Mounting Thermostat 1. Engage tabs at the top of the thermostat and wallplate. See Fig. 5. 2. Press lower edge of case to close and latch. NOTE: To remove thermostat from wall, first pull out at bottom of thermostat; remove top last. WIRING All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 for typical hookup diagram. A letter code is located near each terminal for identification. A. ENGAGE TABS WARNING AT TOP OF THERMOSTAT AND WALLPLATE. Electronic Shock or Equipment Damage Hazard. Can shock individuals or cause equipment damage. Disconnect power before wiring to prevent electrical shock or equipment damage. 1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 4. NOTE: Use 18 gauge, color-coded thermostat cable for proper wiring. B. PRESS LOWER EDGE OF CASE TO LATCH. 2. Securely tighten each terminal screw. 3. Push excess wire back into the hole. 4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat. Fig. 5. Mounting thermostat on wallplate. Pub. No. 18-HD25D7-5 69-1213—1 (T8624) M17151 2 XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT SET WAKE TIMES AND SETPOINTS DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP AND SYSTEM TEST DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE SET CURRENT DAY AND TIME RETURN TO NORMAL OPERATIONS SET CURRENT OR PROGRAM DAY SET RETURN TIMES AND SETPOINTS Run Program Set Current Day/Time ENTER INDEFINITE OR TIMED HOLD MODE Hold Temp DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME Leave Wake Heat/Cool Settings Day Daylight Time Return Sleep SET SLEEP TIMES AND SETPOINTS Fan SET LEAVE TIMES AND SETPOINTS Set Program Time Filter System Copy COPY ONE PROGRAMMED DAY TO ANOTHER DAY SELECT FAN OPERATION CHANGE BETWEEN HEATING AND COOLING SETPOINTS SELECT FILTER EXPIRATION IN NUMBER OF DAYS SELECT SYSTEM OPERATION (HEAT, COOL, OFF, AUTO) M17118 Fig. 6. XT302C key locations and descriptions. System settings control the thermostat operation as follows: Using Thermostat Keys The thermostat keys are used to: • Set current day and time, • Program times and setpoints for heating and cooling, • Temporarily override program temperatures, • Display present setting, • Configure Installer Setup, • Check Self-Test, • Display outdoor temperature (optional accessory), • Set the system operation, and • Set the fan operation. Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto: The thermostat automatically changes between heating and cooling operation, depending on the indoor temperature. Run Program Set Current Day/Time Wake Leave Heat/Cool Settings Filter Hold Temp Day Daylight Time Return Sleep System Set Program Time See Fig. 6 for keypad explanation. System Fan System Heat Off Cool Auto Copy M12956 Fig.7. System key location and display. SETTINGS Fan settings control the system fan as follows: On: Fan operates continuously. Auto: Fan operates with equipment. System and Fan Settings The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. See Figs. 7 and 8. The fan settings can be set for each program period individually. The system selection is for all the program periods. Run Program Set Current Day/Time Wake Leave Heat/Cool Settings Filter Day Daylight Time Return Sleep Set Program Time Hold Temp System Fan Fan Fan On Auto Copy M12957 Fig. 8. Fan key location and display. NOTE: Always press the keys with your fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard. Pub. No. 18-HD25D7-5 3 69-1213—1 (T8624) XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT INSTALLER SETUP Temperature Settings Refer to Table 2 for the default program. For 7-Day and 24-Hour Operation, the settings are the same for each day of the week. Refer to the Owners Guide, Pub. No. 22-5127-04, for instructions on changing the default settings. The Installer Setup is used to customize the thermostat for specific systems. Some of the options include Comfort-R™ control activation, Fahrenheit vs. Centigrade temperature display, outdoor temperature display (requires outdoor sensor installation), and system changeover. Installer Setup numbers are listed in Table 3. The table includes all the configuration options and the factory-settings for the XT302C Deluxe Programmable Multistage Thermostat . Table 2. Default Program Settings. Period Wake Time 6:00 AM Heat Setpoint Cool Setpoint Fan Setting 70°F (21°C) 78°F (25.5°C) Auto Leave 8:00 AM 62°F (16.5°C) 85°F (29.5°C) Auto Return 5:00 PM 70°F (21°C) 78°F (25.5°C) Auto 62°F (16.5°C) 82°F (28°C) Auto Sleep 10:00 PM NOTE: For most applications, the thermostat factorysettings apply. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer Self-Test section. IMPORTANT The chart Customizing Your Thermostat found in the beginning of the Owners Guide (see Fig. 9) must be completed. The homeowner identifies the options you install by referring to this chart. The Leave, Return and Sleep periods may be cleared. For example, the daytime energy-savings period (from Leave to Return) may not be used by the homeowner. To clear any period, follow the instructions in the Owners Guide in the Clearing Schedule Period section. Comfort-R™ CONTROL OFF ON Adaptive Intelligent Recovery™ CONTROL (A HONEYWELL TRADEMARK) ON OFF (CONVENTIONAL RECOVERY) COOLING DROOP ON OFF TEMPERATURE DISPLAY FARENHEIT (°F) CENTIGRADE (°C) CLOCK FORMAT 24-HOUR CLOCK FORMAT 24-HOUR CLOCK FORMAT SYSTEM SETTING (HEATING AND COOLING SETTING) AUTO/MANUAL (SYSTEM AUTOMATICALLY SELECTS HEAT OR COOL; YOU CAN SELECT HEAT, COOL OR OFF.) MANUAL ONLY (YOU SELECT HEAT, COOL OR OFF.) OUTDOOR TEMPERATURE DISPLAY NO OUTDOOR TEMPERATURE IS DISPLAYED NO OUTDOOR TEMPERATURE IS DISPLAYED PROGRAMMING 7-DAY PROGRAMMING 24-HOUR PROGRAMMING Installer Setup Procedure 1. Press and hold the Information , Increase ▲, and Decrease ▼ keys at the same time until all display segments and the first setup number displays (all display segments appear for approximately three seconds before the setup number displays). See Figs. 11 and 12. Set Program Start Time Set Day/Time Temporary Setting Enrg Sav Hold for AM Em Ht Room PM Aux Ht Outdoor MonTueWedThuFriSatSun Heat Cool WakeLeaveReturnSleep In Recovery Auto Repl Batt System Fan DST On Auto Em Heat OffCool Auto Wait M17111 M17110 AUTO ONLY (SYSTEM AUTOMATICALLY SELECTS HEAT OR COOL) Fig. 10. Display of all the segments of the LCD. INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 3) CONSTANT TEMPERATURE SETPOINT PROGRAMMING Fig. 11. Display of Installer Setup number and option. Figure 9. Customizing Your Thermostat chart, from Owners Guide, Pub. No. 22-5127-04. Pub. No. 18-HD25D7-5 69-1213—1 (T8624) FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 3) M10349 4 XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT IMPORTANT Only configurable numbers display. Example: Installer Setup Number 1 does not display because it is not configurable. Review the factory settings in Table 3 and make any desired changes in the Actual Settings column. When the Installer Setup is complete, review the settings to confirm that they match the system and the boxes you checked in the Customizing Your Thermostat chart located in the Owners Guide. — To advance to the next Installer Setup, press Time ▲ . — To change a setting, press Increase ▲ or Decrease ▼. — To scroll the Installer Setup numbers backwards, press Time ▼ . — To exit the Installer Setup, press Run Program. CAUTION Equipment Damage Hazard. Can cause permanent equipment damage. Electric heat systems must be configured to 1 in Installer Setup number 2 to prevent equipment damage caused by the system running without the fan. Table 3. Installer Setup Options for the XT302C. Press Time ▲ or ▼ Installer Setup Number Select Press Increase ▲ or Decrease ▼ to change setting Factory Setting Display Actual Setting Other Choices Description Display Description Programming 42 0 Press Time ▼ to bypass 2–41 and go directly to setup #42 7-day programming 1 or 2 1—24-hour programming 2—No programming Fan operation 2 0 Conventional applications where equipment controls fan operation in heat mode 1 Applications where thermostat controls fan operation in heat mode Number of heating Stages 3 2 2 heating stages 0 or 1 0—no heating 1—1 heating stage Stage 1 heating 4 cycle rate 3 3—3 cph 5, 6, or 9 5—5 cph recommended 5, 6, or 6—6 cph 9 cph not 9—9 cph recommended Stage 2 heating 5 cycle rate 5 5—5 cph recommended 3, 6, or 9 cph not recommended 3, 6, or 9 3—3 cph 6—6 cph 9—9 cph Number of 8 Cooling Stages 1 1 cooling stage 0 or 2 0—no cooling 2—2 cooling stages Stage 1 cooling 9 cycle rate 3 3—3 cph recommended 2 or 5 cph not recommended 2 or 5 2—2 cph 5—5 cph Stage 2 cooling 10 cycle rate 3 3—3 cph recommended 2 or 5 cph not recommended 2 or 5 2—2 cph 5—5 cph System setting adjustment 0 Auto changeover 1 or 2 1—Manual changeover 2—Auto changeover only 12 (continued) Pub. No. 18-HD25D7-5 5 69-1213—1 (T8624) XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT Table 3. Installer Setup Options for the XT302C (continued). Select Press Time ▲ or ▼ Installer Setup Number Press Increase ▲ or Decrease ▼ to change setting Factory Setting Display Description Other Choices Display Description Adaptive Intelligent Recovery™ control 13 0 1 Adaptive Intelligent Recovery (a Honeywell trademark) control is activated (system starts early so setpoint is reached by start of program period) Conventional recovery (system starts recovery at programmed time) Degree temperature display 14 0 Temperature displays 1 in °F Temperature displays in °C Clock format 16 0 12-hour clock format 24-hour clock format Extended fan operation in heatinga 19 0 No extended fan 1, 2 or 3 operation after the call for heat ends 1—Fan operation extends 30 seconds after the call ends. 2—Fan operation extends 60 seconds after the call ends. 3 —Fan operation extends 90 seconds after the call ends. Extended fan operation in cooling 20 0 No extended fan operation after the call for cool ends 1, 2 or 3 1—Fan operation extends 30 seconds after the call ends. 2—Fan operation extends 60 seconds after the call ends. 3 —Fan operation extends 90 seconds after the call ends. Outdoor temperature display (select models) 24 0 No outdoor temperature displays 1 Outdoor temperature displays. Requires a TAYSENS100A Outdoor Sensor. Comfort-R Enable 28 0 No fan delay 1 or 2 1—30 seconds 2—15 seconds 30 Minimum Deadband Between Heating and Cooling in Auto Changeover Mode 4 Heating and cooling setpoints can be set no closer than 4°F (2°C) 3 thru 10 Heating and cooling setpoints can be set no closer than the chosen value: 3—3°F (1.5°C) 4—4°F (2°C) 5—5°F (2.5°C) 6—6°F (3°C) 7—7°F (3.5°C) 8—8°F (4°C) 9—9°F (4.5°C) 10—10°F (5°C) Minimum On Time (Heat) 5 5-minute minimum on time for compressor 0 thru 15 Minimum number of minutes (0 thru 15) the compressor will be on during call for heat 32 1 Actual Setting (continued) Pub. No. 18-HD25D7-5 69-1213—1 (T8624) 6 XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT Table 3. Installer Setup Options for the XT302C (continued). Select Press Time ▲ or ▼ Installer Setup Number Press Increase ▲ or Decrease ▼ to change setting Factory Setting Display Actual Setting Other Choices Description Display Description Minimum On Time (Cool) 33 10 10-minute minimum on 0 thru 15 Minimum number of minutes time for compressor (0 thru 15) the compressor will be on during call for cool Temperature range stops in heating 34 85 Highest setpoint heating can be set to 55 to 85 Temperature range (1°F increments) heating setpoint can be set to Temperature range stops in cooling 35 65 Lowest setpoint cooling can be set to 65 to 99 Temperature range (1°F increments) cooling setpoint can be set to Temperature display adjustment 37 0 No difference in displayed temperature and actual room temperature 3, 2, 1, -1, 3—Display adjusts to 3°F -2, or higher than actual room -3 temperature 2—Display adjusts to 2°F higher than actual room temperature 1—Display adjusts to 1°F higher than actual room temperature -1—Display adjusts to 1°F lower than actual room temperature -2—Display adjusts to 2°F lower than actual room temperature -3—Display adjusts to 3°F lower than actual room temperature Minimum Off Time (Heat) 38 5 5 minute minimum off time for the compressor 0 thru 15 Minimum number of minutes (0 thru 15) the compressor will be off between calls for heat Minimum Off Time (Cool) 39 5 5 minute minimum off time for the compressor 0 thru 15 Minimum number of minutes (0 thru 15) the compressor will be off between calls for cool Cooling Droop 41 1 Cooling droop activated 0 No cooling droop Programming 42 0 Press Time ▼ to bypass 2–41 and go directly to setup #42 7-day programming 1 or 2 1—24-hour programming 2—No programming Setting Current Day and Time IMPORTANT Review the settings to confirm that they match the system. Press Run Program to exit the Installer Setup. The thermostat saves the Installer Setup changes and initiates a reset in order to operate using the new settings. 1. Press Set Current Day/Time. Set Day/Time PM Set Current Day/Time NOTE: For initial installations only, set the current day and time following the setup reset. Run Program Set Current Day/Time Wake Leave Heat/Cool Settings Filter Day Daylight Time Return Sleep Mon Set Program Time Hold Temp System Fan Copy M12951 NOTE: On initial power up or after an extended power loss, 1:00 pm flashes on the display until a key is pressed. Pub. No. 18-HD25D7-5 7 69-1213—1 (T8624) XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT 2. Press Day until the current day displays. To start the self-test: Press and hold the Increase ▲ and Decrease ▼ keys at the same time until all display segments and the number 10 appears (all displays segments appear for approximately three seconds before the test number displays). See Figs. 12 and 13. Set Day/Time PM Run Program Day Set Current Day/Time Wake Leave Heat/Cool Settings Filter Day Daylight Time Return Tue Sleep Set Program Time Hold Temp System Fan Copy M12952 NOTE: Sun=Sunday, Mon=Monday, Tue=Tuesday, Wed=Wednesday, Thu=Thursday, Fri=Friday, Sat=Saturday. Table 4. Tests Available In The Installer Self-Test. Test Number 3. Press Time ▲ or Time ▼ until the current time displays. Time Self-Test Description 10 Heating Equipment 30 Cooling Equipment 40 Fan Equipment 50 Comfort-R Terminals (H-H) 60 Keyboard Operation 70 Device Information Set Day/Time AM Run Program Set Current Day/Time Leave Wake Hold Temp Heat/Cool Settings Day Daylight Time Return Tue Sleep Set Program Time Filter System Fan Copy M12953 NOTE: Tapping the Set Current Day/Time will change the time in one hour increments. NOTE: If the current time is Daylight Savings Time, press Daylight Time until DST displays. Set Program Start Time Set Day/Time Temporary Setting Enrg Sav Hold for AM Em Ht Room PM Aux Ht Outdoor MonTueWedThuFriSatSun Heat Cool WakeLeaveReturnSleep In Recovery Auto Repl Batt System Fan DST On Auto Em Heat OffCool Auto Wait Set Day/Time AM Daylight Time Run Program Set Current Day/Time Wake Leave Heat/Cool Settings Filter Day Daylight Time Tue Sleep Set Program Time Hold Temp Return System DST Fan Copy M17111 M12954 4. Fig. 12. Display of all the segments of the LCD. Press Run Program. AM Run Program Run Program Set Current Day/Time Wake Hold Temp Heat/Cool Settings Day Daylight Time Leave Return Sleep Set Program Time Filter System Fan Tue Wake System Heat Room DST Fan Auto Copy M12955 INSTALLER SELF-TEST TEST NUMBER M10257A Fig. 13. Display of test number. Use the Installer Self-Test to check the thermostat operation. Refer to Table 4 for a list of the available self-tests. Refer to Table 5 for the directions and results of the specific tests. NOTE: Press Time ▲ to advance to the next test and Time ▼ to go back to the previous test. Press Run Program to exit the self-test. This mode times out 5 minutes after the last key press. CAUTION Equipment Damage Hazard. Equipment damage can occur if the compressor is cycled too quickly. The minimum off time is deactivated during the Installer Self-Test. Perform the test so that the compressor is cycled slowly. NOTE: Press Time ▼ to return to the previous test or Time ▲ to advance to the next test. NOTE: To exit, press Time ▲ or Time ▼ then Run Program. Pub. No. 18-HD25D7-5 69-1213—1 (T8624) 8 XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT Table 5. Installer Self-Test Options. Key to Press Test Number Description Heating Equipment Self-Test (10) Time ▲ 10 Enter heating equipment self-test. Temp ▲ 11 First stage heat turns on. When Installer Setup number 2 is 1, the system fan is also energized. Temp ▲ 12 Second stage heat turns on. Temp ▼ 11 Second stage heat turns off. Temp ▼ 10 First stage heat turns off. Cooling Equipment Self-Test (30) Time ▲ 30 Temp ▲ 31 First stage cool and fan turn on. Temp ▲ 32 Second stage cool turns on. Temp ▲ 31 Second stage cool turns off. Temp ▼ 30 First stage cool and fan turn off. Enter cooling equipment self-test. Fan Equipment Self-Test (40) Time ▲ 40 Enter fan equipment self-test. Temp ▲ 41 Fan turns on. Temp ▼ 40 Fan turns off. Comfort-R Terminals Self-Test (50) Temp ▲ 50 Enter Comfort-R self-test. Temp ▼ 51 Reads HH terminals. If the terminals are open and Comfort-R is enabled, display reads % humidity. If the terminals are closed no % humidity displays. Keyboard Operation Self-Test (60) Time ▲ 60 7 Enter keyboard operation self-test. Temp ▲ 60 9 Increase test number displays. Temp ▼ 60 8 Decrease test number displays. Day 60 11 Day test number displays. Copy 60 12 Copy test number displays. System 60 3 System test number displays. Fan 60 10 Fan test number displays. Set Current Day/Time 60 1 Set Current Day/Time test number displays. Run Program 60 15 Run Program test number displays. Daylight Time 60 19 Daylight Time test number displays. Heat/ Cool 60 5 Settings Heat/Cool Settings test number displays. Wake 60 0 Wake test number displays. Leave 60 14 Leave test number displays. Return 60 16 Return test number displays. Sleep 60 2 Sleep test number displays. Filter 60 17 Filter test number displays. i 60 13 Information test number displays. Device Information Self-Test (70) - Refer to following section. Pub. No. 18-HD25D7-5 9 69-1213—1 (T8624) XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT 4. Press Increase ▲ again to display the software revision number (Example: 001=Revision number 1). DEVICE INFORMATION SELF-TEST (70) 1. Press Temp ▲ and ▼ keys simultaneously, then press Time ▼ to access the thermostat information. M10229 5. Press the Increase ▲ again to display the model identification number. (Example: 314 = Model ID 314) M4934 2. Press Increase ▲ to display the production date code in a 3-digit format. The first two digits represent the month and the third digit represents the last digit of the year (Example: 128=December 1998). M4933A 6. Press Run Program to exit the self-test. The self-test mode times out 5 minutes after the last key press. CHECKOUT M17112 3. Press Increase ▲ again to display the software identification code. (Example: 200 = software ID code 200) Outdoor Temperature Sensor (optional accessory) Expose the outdoor temperature to outdoor air for a minimum of five minutes before reading. M17113 TROUBLESHOOTING GUIDE Symptom Display will not come on. Possible Cause Thermostat is not being powered. Temperature display is Room temperature incorrect. display has been reconfigured. Action Check for 24 Vac between R and W terminals. Check if the circuit breaker is tripped—reset the circuit breaker. Check if the system fuse is blown—replace the fuse. Check if the power switch on the HVAC equipment is in the Off position—set to the On position. Check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections. If 24 Vac is present, proceed with troubleshooting. Enter Installer Setup number 37 and reconfigure the display. Thermostat is configured Enter Installer Setup number 14 and reconfigure the display. for °F or °C display. Bad thermostat location. Relocate the thermostat. Temperature displaying digits as dashes (---). Internal temperature measurement failure. Contact distributor or retailer. Temperature settings will not change. (Example: Cannot set the heating higher or the cooling lower.) The upper or lower temperature limits were reached. Check the temperature setpoints: Heating limits are 55 to 85°F (13 to 29°C). Cooling limits are 65 to 99°F (18 to 37°C). The setpoint temperature Check Installer Setup numbers 34 and 35 and reconfigure the range stops were setpoint stops. configured. (continued) Pub. No. 18-HD25D7-5 69-1213—1 (T8624) 10 XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT TROUBLESHOOTING (Continued). Symptom Possible Cause Action Heating will not come on. No power to the thermostat. Check for 24 Vac between R and W terminals. If missing 24 Vac: Check if the circuit breaker is tripped—reset the circuit breaker. Check if the system fuse is blown—replace the fuse. Check if the power switch on the HVAC equipment is in the Off position—set to the On position. Check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections. If 24 Vac is present, proceed with troubleshooting. Heating will not come on. Thermostat minimum off time is activated. Wait up to five minutes for the system to respond. System selection is not set to Heat. Set system selection to Heat. Heating setpoint is below Check heating setpoint. Set heating setpoint to desired temperature. room temperature. Cooling will not come No power to the on. thermostat. Check for 24 Vac between R and W terminals. If missing 24 Vac: Check if the circuit breaker is tripped—reset the circuit breaker. Check if the system fuse is blown—replace the fuse. Check if the power switch on the HVAC equipment is in the Off position—set to the On position. Check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections. If 24 Vac is present, proceed with troubleshooting. Thermostat minimum off time is activated. Wait up to five minutes for the system to respond. Enter Installer Setup number 39. Reconfigure minimum off time (if required). System selection is not set to Cool. Set system selection to Cool. Cool setpoint is above room temperature. Check cooling setpoint. Set cooling setpoint to desired temperature. Heating or cooling come on momentarily and shut off Heat or cool circuit is opening up or becoming high impedance. Add resistor in parallel with load or install interface relay. System on indicator (flame=heat, snowflake=cool) displays, but no warm or cool air is coming from the registers. Heating equipment turns on the fan when the furnace has warmed up to a setpoint. Wait a minute after seeing the on indicator and then check the registers. Heating or cooling equipment is not operating. Verify operation of heating or cooling equipment in self-test. Outdoor temperature not displayed or is incorrect. Option not activated. Enter Installer Setup number 24 and set to 1. Thermostat must have OT terminals and a TAYSENS100A installed. Outdoor sensor is connected incorrectly. Refer to TAYSENS100A installation instructions and check wiring between the thermostat and sensor. Wrong sensor. Replace sensor with TAYSENS100A sensor. Filter expired. Refer to the Filter Indication section in the Owner’s Guide, Pub. No. 22-5127-04 System on indicator reads Filter and backlight is flashing. Filter expired. Refer to the Filter Indication section. Time displaying digits as three E’s (EEE). Internal memory failure. Contact distributor or retailer. Pub. No. 18-HD25D7-5 11 69-1213—1 (T8624) XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT Pub. No. 18-HD25D7-5 69-1213—1 (T8624) T. C. Rev. 1-99 Printed in Taiwan 12 R.O.C. American Standard Inc. Troup Highway Tyler, TX 75711-9010
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : Yes Create Date : 1999:01:21 08:07:31 Producer : Acrobat Distiller 3.0 for Power Macintosh Subject : Installer's Guide Creator : Adobe PageMaker 6.5 Title : 69-1213 - XT302C Deluxe Programmable Heat-Cool Thermostat Author : H&BC Technical Communications Modify Date : 1999:01:26 08:38:05 Page Count : 12EXIF Metadata provided by EXIF.tools