Trane Ysc060 120 Owners Manual RT PRC017 EN 10/03
Trane Heat Pump 060E rtprc017en_r4
YSC060-120 to the manual 5c1366c9-157c-4120-807f-70c634fb3b2b
2014-08-26
: Trane Trane-Ysc060-120-Owners-Manual trane-ysc060-120-owners-manual trane pdf
Open the PDF directly: View PDF .
Page Count: 60
Download | |
Open PDF In Browser | View PDF |
Packaged Gas/Electric Rooftop Units Precedent™ YSC060-120 50 Hz February 2004 RT-PRC017-EN Introduction Precedent™ . . . The same Trane quality... with added flexibility. Precedent is a flexible line of packaged units that covers a wide variety of applications. Reliatel™ microprocessor controls provide superior flexibility for the simplest to the most sophisticated applications. In addition to controls, Precedent offers many other outstanding features and option choices. © 2004 American Standard Inc. All rights reserved With its sleek compact cabinet, rounded corners and beveled top, it may just be the most aesthetically pleasing packaged unit on the planet. And, of course, Precedent carries the Trane reputation for excellence, quality, and reliability. It’s hard to stop a Trane. From simple applications, to the most complex, Precedent has the solution. RT-PRC017-EN Contents RT-PRC017-EN Introduction Features and Benefits 2 Application Considerations 9 4 Selection Procedure 10 Model Number Description 12 General Data 13 Performance Data 14 Zone Controls 42 Electrical Data 43 Jobsite Connection 44 Dimensional Data 45 Weights 53 Mechanical Specifications 54 3 Features and Benefits Easy Access Panels Remove two screws for access to the standardized internal components and wiring. Easy-Adjust Idler Arm With the Easy-Adjust Idler Arm, the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money. Patented Condenser Coil Precedent boasts a patented 1+1+1 Hybrid coil, permanently gapped for easy cleaning. Unit Cabinet The compact cabinet with rounded corners takes up less room and is less costly to ship. The beveled and ribbed top is not only aesthetically pleasing, it is designed to prevent water from pooling. Single Point Power A single electrical connection powers the unit. Colored And Numbered Wiring You save time and money tracing wires and diagnosing the unit. Convertible Units • The units ship in a downflow configuration. They can be easily converted to horizontal by simply moving two panels. Compressors Precedent™ contains the best compressor technology available to achieve the highest possible performance. Our compressor line includes Trane built Climatuff™ reciprocating and scrolls. • Units come complete with horizontal duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver. Sloped Drain Pans Every Precedent unit has a noncorrosive, removable, double-sloped drain pan that’s easy to clean and reversible to allow installation of drain trap on either side of the unit. Through the Base Condensate Every unit includes provisions for through the base condensate drain connections. This allows the drain to be connected through the roof curb instead of a roof penetration. Foil-Faced Insulation All panels in the Evaporator section of the unit have cleanable foil-faced insulation. All edges are either captured or sealed to ensure no fibers get into the airstream. Easy Access Panels Easy access panels reduce the number of possible water entry points. Low Ambient Cooling All Precedent units have cooling capabilities down to -18°C (0°F) as standard. Unit Base For added water integrity, Precedent has a raised 29 mm (11/8") lip around the unit’s downflow supply and return to prevent water from blowing into the ductwork. 4 RT-PRC017-EN Features and Benefits Standardized Components • Components are placed in the same location on all Precedent™ units. Familiarize yourself with one Precedent and you are familiar with every Precedent. Easy Access Low Voltage Terminal Board Precedent’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to test operation of all unit functions. This is another cost and time saving installation feature. Progressive Tubular Heat Exchanger The compact cabinet features a tubular heat exchanger in low, medium and high heat capacities. The heat exchanger is fabricated using stainless steel burners and corrosionresistant aluminized steel tubes as standard on all models. It has an induced draft blower to pull the gas mixture through the burner tubes. The heater has a direct spark ignition system which doubles as a safety device to prove the flame. Flexible Applications • Only two roof curbs for the 5-10 ton Precedent line. . .simplifies curb selection. • ReliaTel microprocessor controls to meet either the simple or the more complex application. • Low or high gas heat capacities. • Airflow is outstanding. The Precedent can replace an older machine with old ductwork and, in many cases, improve comfort through better air distribution. • Belt drive —standard or oversized supply fan motors meet a wide airflow range. • Precedent offers ultimate flexibility. Options and components are not prepackaged at the factory. Units are built to order in our standard “shortest in the industry”ship cycle time. Low Voltage Connections The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire. Single-Side Service Single-side service is standard on all Precedent units. RT-PRC017-EN 5 Features and Benefits • Eliminates the need for field-installed components with its built-in anti-shortcycle timer, time delay relay and minimum ‘’on’’ time controls. These controls are factory tested to assure proper operation. Micro Controls Several years ago, Trane was the first to introduce microprocessor controls into the Light Commercial Market. That design, along with immeasurable experience, has provided the technology for Trane’s second-generation ReliaTel™ microprocessor controls. ReliaTel Micro: • Provides unit control for heating, cooling, and ventilating by utilizing input from sensors that measure outdoor and indoor temperature. • As long as the unit has power and the LED is lit, the Micro is operational. The light indicates that the Micro is functioning properly. • Features expanded diagnostic capabilities when used with Trane’s Integrated Comfort™ Systems. • Improves quality and reliability through the use of time-tested microprocessor controls and logic. • As an energy benefit, softens electrical ‘’spikes’’ by staging on fans, compressors and heaters. • Prevents the unit from short cycling, considerably improving compressor life. • The Intelligent Fallback or Adaptive Control is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature set points. • Ensures that the compressor will run for a specific amount of time, which allows oil to return for better lubrication, enhancing the reliability of the compressor. • Reduces the number of components required to operate the unit, thereby reducing possibilities for component failure. 6 • Requires no special tools to run the Precedent unit through its paces during testing. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps. The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit. • Intelligent Anticipation is a standard feature of the Micro. Functioning constantly, the Micro and zone sensors work together in harmony, to provide tight comfort control. RT-PRC017-EN Features and Benefits Factory-installed Options Hinged Access Doors These doors permit easy access to the filter, fan/heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners. The following options round-out the complete line of Precedent™ options: Economizer Equipped with either dry bulb, reference or comparative enthalpy sensing, this feature provides free cooling as the outdoor temperature and/or humidity decreases. Economizers, correctly installed, offer valuable energy savings. Factory-installed economizers save time and ensure proper installation. — Hail Protection Quality Coil Guards Phase Monitor Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. Clogged Filter/Fan Fail Switches These sensors allow a zone sensor service light or Integrated Comfort System to indicate a dirty filter or a fan that’s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment. — 0 - 50% Manual or Motorized Outside Air — Discharge Air Sensor — Wide array of Zone Sensors and Thermostats — Liquid Propane Conversion Kits — Factory built Roof Curb One of Our Finest Assets: Trane Sales Representatives are a Support group that can assist you with: — Product — Application — Service — Training — Special Applications — Specifications — Computer Programs and much more Precedent has the features and benefits that make it first class in the light commercial rooftop market. Designed with input from field contractors and engineers, its airflow performance is outstanding. Precedent…The same Trane quality…with added flexibility. COMM3/4 Communication Interface Available factory or field-installed. This module, when applied with ReliaTel™, easily interfaces with Trane’s Integrated Comfort™ System. RT-PRC017-EN 7 Features and Benefits Quality And Reliability Testing ™ • All Precedent designs were rigorously rain tested at the factory to ensure water integrity. • Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. • Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition. • Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. • We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 1375 kPa (200 psig) and pressure tested to 3100 kPa (450 psig). • All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. • The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47. This is the standard required by both UL and AGA for cycle test requirments. Trane requires the design to be tested to 2½ times this current standard. • Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements. We test designs at our factory not on our customers! VariTrac™ VariTrac When Trane’s changeover VAV System for light commercial applications is coupled with Precedent, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac. 8 RT-PRC017-EN Application Considerations Application of this product should be within the cataloged airflow and cooling considerations. Low Ambient Cooling The Precedent™ line features, as standard, low ambient cooling down to -18°C (0°F). Contact your local Trane Representative for more assistance with low ambient cooling applications. Barometric Relief This product offers an optional barometric relief damper for use in conjunction with economizer option. This option consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space. NOTE: THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED. PRESSURE DROP OF THE RETURN AIR SYSTEM SHOULD BE CONSIDERED TO CONTROL BUILDING PRESSURIZATION. RT-PRC017-EN Heating Operation The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50% outside air. Condensate Trap The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle. Clearance Requirements The recommended clearances identified with unit dimensions should be maintained to assure adequate service, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel. Unit Pitch These units have reversible sloped condensate drain pans. Units must be installed level; any unit slope must be toward side of unit where condensate drain is connected. 9 Selection Procedures - SI Units Cooling Capacity Heating Capacity Step 1 — Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane calculation form or any other standard accepted method. Step 1 — Calculate the building heating load using the Trane calculation form or other standard accepted method. Example: The following are the building cooling requirements: a. Electrical Characteristics: 380-415/50/3 b. Summer Design Conditions: Entering Evaporator Coil: 27° DB/ 19° WB Outdoor Ambient: 35° c. Total Cooling Load: 16.5 kW d. Sensible Cooling Load: 11.8 kW e. Airflow: 3400 m3/h External Static Pressure: 125 Pa f. Downflow Configuration Step 2 — Size the equipment using Table PD-1 to match the cooling loads at design conditions. Table PD-1 shows that a YSC060AD has a gross cooling capacity of 17.8 kW and 14.4 kW sensible capacity at 35 DB ambient and 3400 m3/h with 27 DB/ 19 WB air entering the evaporator. Use the following formula to calculate fan motor heat, which can be found in the notes in Table PD-8: Fan motor heat (kW) = 1.144 x (Fan kW) + 0.132 Step 2 — Size the system heating capacity to match the calculated building heating load. The following are building heating requirements: a. Total heating load of 17.6 kW b. 3400 m3/h c. Fuel - Natural gas For the YSC060AD there are two heating capacities available, 19.6 kW and 29.3 kW input models shown in Table PD-32. The output capacities of these furnaces are 15.7 kW and 23.4 kW respectively. The high heat model with 23.4 kW best matches the building requirements, indicating a YHC060AD* should be selected. Air Delivery Selection External static pressure drop through the air distribution system has been calculated to be 150 Pa. Enter Table PD8 for a YSC060AD*H at 3400 m3/h and 150 Pa static pressure. The standard motor will give the desired airflow. Accessory Selection Select accessories needed to accommodate the application. For example: With 3400 m3/h and 125 Pa, specified by the engineer, Table PD-8 shows 0.73 kW for a high heat model. Fan motor heat = 1.144 x 0.73 + 0.132 = 0.97kW Net Total Cooling = 17.8 kW - 0.97 = 16.8 kW Net Sensible Cooling Capacity 14.4 kW - 0.97 = 13.4 kW. 10 RT-PRC017-EN Selection Procedures - IP Units Cooling Capacity Heating Capacity Step 1 — Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane calculation form or any other standard accepted method. Step 1 — Calculate the building heating load using the Trane calculation form or other standard accepted method. Example: The following are the building cooling requirements: a. Electrical Characteristics: 380-415/50/3 b. Summer Design Conditions: Entering Evaporator Coil: 80° DB/ 67° WB Outdoor Ambient: 95° c. Total Cooling Load: 58 MBh d. Sensible Cooling Load: 42 MBh e. Airflow: 2000 cfm External Static Pressure: .6 in wg f. Downflow Configuration Step 2 — Size the equipment using Table PD-1a to match the cooling loads at design conditions. Table PD-1a shows that a YSC060AD has a gross cooling capacity of 62.0 MBh and 46.4 MBh sensible capacity at 95 DB ambient and 2000 cfm with 80 DB/ 67 WB air entering the evaporator. Use the following formula to calculate fan motor heat, which can be found in the notes in Table PD-8a: Fan motor heat (MBh) = 2.915 x (Fan bhp) + 0.451 For example: With 2000 cfm and 0.60 inches, specified by the engineer, Table PD-8a shows 1.06 bhp for a high heat model. Step 2 — Size the system heating capacity to match the calculated building heating load. The following are building heating requirements: a. Total heating load of 70.0 MBh b. 2000 cfm c. Fuel - Natural gas For the YSC060AD there are two heating capacities available, 67 MBh and 100 MBh input models shown in Table PD32. The output capacities of these furnaces are 54 MBh and 80 MBh respectively. The high heat model with 80 MBh best matches the building requirements, indicating a YSC060AD*H should be selected. Air Delivery Selection External static pressure drop through the air distribution system has been calculated to be 0.6 inches of water. Enter Table PD-8a for a YSC060AD*H at 2000 cfm and 0.60 static pressure. The standard motor will give the desired airflow. Accessory Selection Select accessories needed to accommodate the application. Fan motor heat = 2.915 x 1.06 + 0.451 = 3.5 MBh Net Total Cooling = 62.0 MBh - 3.5 = 58.5 MBh Net Sensible Cooling Capacity 46.4 MBh - 3.5 = 42.9 MBh. RT-PRC017-EN 11 Model Number Description Y S C 060 A D R L 1 3 4,5,6 7 8 9 10 11 12,13 14 15 16 17 2 A ** C 0 0 0 0 0 0 0 18 19 20 21 0 0 0 1 22 23 24 25 Digit 1 - Unit Function Y = DX Cooling, Gas Heat Digits 12, 13 - Service Sequence ** = Factory Assigned Digit 18 - Through the Base Provisions 0 = No Through the Base Provisions Digit 2 - Efficiency S = Standard Efficiency Digit 14 - Fresh Air Selection 0 = No Fresh Air A = Manual Outside Air Damper 0-50% B = Motorized Outside Air Damper 0-50% C = Economizer, Dry Bulb 0-100% without Barometric Relief D = Economizer, Dry Bulb 0-100% with Barometric Relief E = Economizer, Reference Enthalpy 0-100% without Barometric Relief F = Economizer, Reference Enthalpy 0-100% with Barometric Relief G = Economizer, Comparative Enthalpy 0-100% without Barometric Relief H = Economizer, Comparative Enthalpy 0-100% with Barometric Relief Digit 19 - Disconnect/Circuit Breaker/Phase Monitor (3 phase only) 0 = No Disconnect or Circuit Breaker 3 = Phase Monitor Only (No Disconnect, No Circuit Breaker) Digit 3 - Airflow C = Convertible Digits 4,5,6 - Nominal Gross Cooling Capacity (MBh) kW Tons 060 = 17.6 5 072 = 21.1 6 090 = 26.4 7.5 102 = 29.9 8.5 120 = 35.1 10 Digit 7 - Major Design Sequence A = First Digit 8 - Unit Voltage D = 380-415/50/3 Digit 9 - Unit Controls R = ReliaTel™ Microprocessor Digit 10 - Heating Capacity L = Low H = High Digit 11 - Minor Design Sequence A = First Sequence 12 Digit 15 - Supply Fan/Drive Type/Motor 0 = Standard Drive 1 = Oversized Motor Digit 16 - Hinged Service AccessFilters 0 = Standard Panels/Standard Filters A = Hinged Access Panels/Standard Filters B = Standard Panels/50 mm (2”) Pleated Filters C = Hinged Access Panels/50 mm 2” Pleated Filters Digit 17 - Condenser Coil Protection 0 = Standard Coil 1 = Standard Coil with Hail Guard 2 = Epoxy Coated Condenser Coil 3 = Epoxy Coated Condenser Coil with Hail Guard Digit 20 - Convenience Outlet 0 = No Convenience Outlet Digit 21 - Communications Options 0 = No Communications Interface 1 = Comm-3/4 Communications Interface 2 = Comm-5 Communications Interface Digit 22 - Refrigeration System Option 0 = Standard Refrigeration System Digit 23 - Refrigeration Controls 0 = No Refrigeration Control Digit 24 - Smoke Detector 0 = No Smoke Detector Digit 25 - Monitoring Controls 0 = No Monitoring Control 1 = Clogged Filter Switch 2 = Fan Failure Switch 3 = DischargeAir Sensing Tube 4 = Clogged Filter Switch and Fan Fail Switch 5 = Clogged Filter Switch and Discharge Air Sensing Tube 6 = Fan Fail Switch and Discharge Air Sensing Tube 7 = Clogged Filter and Fan Fail Switches and Discharge Air Sensing Tube RT-PRC017-EN General Data Table GD-1 — General Data Cooling Performance 1 Gross Capacity - kW (MBh) COP (EER) 2 Nominal Airflow - m3/h (cfm) Rated Airflow - m3/h (cfm) Net Capacity - kW (MBh) System Power - kW Heating Performance 3 Heating Models Heating Input - kW (MBH) Heating Output - kW (MBH) Steady State Efficiency % No. Burners No. Stages Gas Connection Pipe Size - in. Compressor Number - Type Outdoor Sound Rating dB 4 Outdoor Coil - Type Tube Size in. OD Face Area - m2 (sq ft) Rows / FPI Indoor Coil - Type Tube Size OD - in. Face Area - m2 (sq ft) Rows / FPI Refrigerant Control Drain Connection No. / Size - in. Outdoor Fan - Type No. Used / Diameter - in. Drive Type / No. Speeds CFM No. Motors / kW (HP) Motor RPM Belt Drive Indoor Fan - Type No. Used Fan Diameter x Width - mm (in.) Drvie Type / No. Speeds No. Motors Standard Motor Power - kW (HP) Oversized Motor Power - kW (HP) Motor RPM - Standard / Oversized Motor Frame Size Filters - Type Furnished (No.) Size Reccommended - mm (No.) Size Reccommended - in. Refrigerant Charge - kg (lbs) of R-22 5 Convertible Units YSC060AD Convertible Units YSC072AD Convertible Units YSC090AD Convertible Units YSC102AD Convertible Units YSC120AD 18.2 (62.0) 2.99 (10.2) 3400 (2000) 3400 (2000) 17.3 (59.0) 5.78 23.2 (79.0) 3.08 (10.5) 4080 (2400) 3570 (2100) 22.0 (75.0) 7.14 26.7 (91.0) 3.02 (10.3) 5100 (3000) 4460 (2625) 25.2 (86.0) 8.35 31.1 (106.0) 3.02 (10.3) 5780 (3400) 5100 (3000) 29.9 (102.0) 9.9 34.9 (119.0) 2.99 (10.2) 6800 (4000) 5950 (3500) 33.1 (113.0) 11.08 Low - G80 19.6 (67) 15.7 (54) 90 2 1 3/4 NPT High - G120 29.3 (100) 23.4 (80) 90 3 1 3/4 NPT 1-Climatuff Scroll 80 Lanced 0.3125 1.02 (10.96) 3 / 17 Lanced 0.3125 0.62 (6.68) 3 / 16 Short Orifice 1 / 0.75 NPT Propeller 1 / 22 Direct / 1 2900 1 / 0.30 (0.40) 950 FC Centrifugal 1 280 X 280 (11 x 11) Belt / Variable Speed 1 1.1 (1.5) 1450 / 56 Throwaway (2) 508 X 762 X 25 (2) 20 X 30 X 1 3.7 (8.2) Low - G120 High G-200 29.3 (100) 48.9 (167) 23.4 (80) 39.1 (134) 90 90 3 4 1 2 3/4 NPT 3/4 NPT 1-Trane 3-D Scroll 85 Lanced 0.3125 1.29 (13.88) 2 / 17 Lanced 0.3125 0.92 (9.89) 2 / 16 Short Orifice 1 / 0.75 NPT Propeller 1 / 26 Direct / 1 5100 1 / .56 (0.75) 950 FC Centrifugal 1 305 X 305 (12 x 12) Belt / Variable Speed 1 1.1 (1.5) 1.5 (2.0) 1450 / 1450 56 Throwaway (4) 406 X 635 X 50 (4) 16 X 25 X 2 3.7 (8.2) Low - G120 29.3 (100) 23.4 (80) 90 3 1 3/4 NPT High G-200 48.9 (167) 39.1 (134) 90 4 2 3/4 NPT 1-Trane 3-D Scroll 85 Lanced 0.3125 1.29 (13.88) 2 / 17 Lanced 0.3125 0.92 (9.89) 3 / 16 Short Orifice 1 / 0.75 NPT Propeller 1 / 26 Direct / 1 5200 1 / .56 (0.75) 950 FC Centrifugal 1 305 X 305 (12 x 12) Belt / Variable Speed 1 1.5 (2.0) 2.2 (3.0) 1450 / 2850 56 Throwaway (4) 406 X 635 X 50 (4) 16 X 25 X 2 4.5 (10.0) Low - G150 High G-250 Low - G150 36.7 (125) 60.9 (208) 36.7 (125) 29.3 (100) 48.7 (166) 29.3 (100) 90 90 90 3 5 3 2 2 2 3/4 NPT 3/4 NPT 3/4 NPT 2-Climatuff Scroll 83 Lanced 0.3125 1.75 (18.89) 2 / 17 Lanced 0.3125 1.15 (12.36) 3 / 16 Short Orifice 1 / 0.75 NPT Propeller 1 / 26 Direct / 1 5500 1 / .56 (0.75) 950 FC Centrifugal 1 381 X 381 (15 x 15) Belt / Variable Speed 1 1.5 (2.0) 2.2 (3.0) 1450 / 2850 56 Throwaway (4) 508 X 635 X 50 (4) 20 X 25 X 2 Circuit 1 - 3.8 (8.3) Circuit 2 - 2.0 (4.4) High G-250 60.9 (208) 48.7 (166) 90 5 2 3/4 NPT 2-Climatuff Scroll 79 Lanced 0.3125 2.41 (25.92) 2 / 17 Lanced 0.3125 1.15 (12.36) 4 / 16 Short Orifice 1 / 0.75 NPT Propeller 1 / 26 Direct / 1 5800 1 / .56 (0.75) 950 FC Centrifugal 1 381 X 381 (15 x 15) Belt / Variable Speed 1 2.2 (3.0) 2850 / 56 Throwaway (4) 508 X 635 X 50 (4) 20 X 25 X 2 Circuit 1 - 3.4 (7.5) Circuit 2 - 3.3 (7.3) Notes: 1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to ± 20 % of nominal airflow. 2. EER are rated at ARI conditions. 3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 4. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table "Sound Power Level". 5. Refrigerant charge is an approcimate value. For a more precise value, see unit nameplate and service literature. RT-PRC017-EN 13 Performance Data Table PD-1 — Gross Cooling Capacities (kW) - YSC060AD - (SI) Ambient Temperature (C) m3/h Airflow 3060 3400 3740 4080 Enter. Dry Bulb Temp (C) 24 27 30 33 24 27 30 33 24 27 30 33 24 27 30 33 30 35 40 45 Entering Wet Bulb Temperature (C) 16 19 22 16 19 22 16 19 22 16 19 22 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 16.2 13.9 18.5 11.3 19.9 8.3 15.0 13.3 17.4 11.3 19.3 8.0 13.9 12.7 16.1 10.7 18.4 7.5 12.7 12.1 14.7 9.5 17.3 7.0 16.7 16.7 18.6 14.1 20.0 11.1 15.8 15.8 17.4 13.6 19.4 10.8 14.8 14.8 16.1 13.0 18.5 10.3 13.8 13.8 14.7 12.3 17.3 9.8 18.1 18.1 18.7 16.9 20.2 13.6 17.2 17.2 17.7 16.5 19.5 13.5 16.2 16.2 16.5 15.9 18.5 13.1 15.1 15.1 15.1 15.1 17.3 12.6 19.3 19.3 19.2 19.2 20.3 16.2 18.5 18.5 18.5 18.5 19.6 16.1 17.6 17.6 17.6 17.6 18.7 15.9 16.6 16.6 16.6 16.6 17.5 15.4 16.7 14.8 18.8 11.8 20.1 8.6 15.5 14.2 17.8 11.3 19.5 8.3 14.2 13.5 16.5 11.4 18.7 7.7 13.1 12.9 15.0 10.8 17.6 7.2 17.5 17.5 18.9 14.9 20.2 11.4 16.5 16.5 17.8 14.4 19.6 11.2 15.4 15.4 16.5 13.8 18.8 10.8 14.4 14.4 15.1 13.1 17.6 10.3 18.8 18.8 19.1 17.9 20.4 14.1 17.9 17.9 18.2 17.6 19.7 14.1 16.9 16.9 17.0 17.0 18.8 13.8 15.8 15.8 15.8 15.8 17.7 13.4 19.8 19.8 19.8 19.8 20.6 16.8 19.2 19.2 19.2 19.2 19.9 16.9 18.3 18.3 18.3 18.3 19.0 16.8 17.4 17.4 17.4 17.4 17.9 16.4 17.1 15.6 19.1 12.3 20.2 8.8 15.9 15.0 18.1 11.8 19.7 8.5 14.6 14.3 16.8 11.2 18.9 7.9 13.4 13.4 15.3 11.4 17.8 7.5 18.1 18.1 19.2 15.5 20.4 11.6 17.1 17.1 18.2 15.1 19.8 11.5 16.0 16.0 16.9 14.6 19.0 11.3 14.9 14.9 15.4 13.9 17.9 10.8 19.3 19.3 19.5 18.7 20.6 14.5 18.5 18.5 18.6 18.6 20.0 14.6 17.6 17.6 17.6 17.6 19.1 14.4 16.5 16.5 16.5 16.5 17.9 14.1 20.2 20.2 20.2 20.2 20.8 17.4 19.6 19.6 19.6 19.6 20.2 17.6 18.9 18.9 18.9 18.9 19.3 17.6 18.0 18.0 18.0 18.0 18.3 17.4 17.4 16.4 19.3 12.6 20.3 9.1 16.2 15.8 18.4 12.2 19.8 8.8 14.9 14.9 17.1 11.7 19.0 8.1 13.9 13.9 15.5 12.1 18.0 7.7 18.6 18.6 19.4 16.1 20.5 12.3 17.7 17.7 18.4 15.8 19.9 11.8 16.6 16.6 17.2 15.3 19.1 11.6 15.4 15.4 15.8 14.6 18.1 11.2 19.7 19.7 19.7 19.4 20.7 14.9 19.0 19.0 19.0 19.0 20.1 15.0 18.1 18.1 18.1 18.1 19.3 15.0 17.1 17.1 17.1 17.1 18.2 14.7 20.5 20.5 20.5 20.5 20.9 17.9 20.0 20.0 20.0 20.0 20.4 18.2 19.3 19.3 19.3 19.3 19.5 18.3 18.4 18.4 18.4 18.4 18.6 18.2 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-1a _ Gross Cooling Capacities (MBH) _ YSC060AD _ (IP) Ambient Temperature (F) CFM Airflow 1800 2000 2200 2400 Enter. Dry Bulb Temp (F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90 85 95 105 115 Entering Wet Bulb Temperature (F) 61 67 73 61 67 73 61 67 73 61 67 73 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 56.1 47.1 64.4 37.0 68.8 25.1 51.6 44.7 60.6 36.7 66.9 23.9 47.0 42.4 55.6 34.5 64.0 22.6 42.4 40.1 50.2 30.3 60.0 20.8 57.3 56.5 64.6 45.8 69.3 34.2 53.3 53.3 60.7 43.9 67.3 32.9 49.5 49.5 55.7 41.6 64.2 31.4 45.7 45.7 50.4 39.2 60.1 29.6 61.3 61.3 64.9 54.5 69.7 42.0 57.7 57.7 61.0 52.9 67.6 41.4 53.9 53.9 56.3 50.7 64.4 40.3 50.0 50.0 51.2 48.3 60.2 38.4 65.0 65.0 65.8 63.3 70.4 49.7 62.1 62.1 62.4 62.2 68.0 49.7 58.5 58.5 58.5 58.5 64.6 48.8 54.4 54.4 54.4 54.4 60.3 47.2 57.5 49.8 65.4 38.5 69.3 25.5 53.0 47.5 61.8 38.7 67.5 24.4 48.3 45.1 56.9 36.6 64.7 23.0 43.7 42.8 51.3 34.2 60.9 21.4 59.3 59.3 65.6 47.9 69.8 35.4 55.7 55.7 62.0 46.4 68.0 34.2 51.6 51.6 57.1 44.1 65.0 32.7 47.7 47.7 51.5 41.6 61.0 30.9 63.6 63.6 66.0 57.3 70.5 43.1 60.3 60.3 62.5 56.2 68.3 43.0 56.4 56.4 58.0 54.1 65.2 42.1 52.2 52.2 52.8 51.7 61.2 40.6 66.9 66.9 67.2 66.5 71.1 51.4 64.4 64.4 64.4 64.4 68.9 51.8 61.0 61.0 61.0 61.0 65.6 51.3 57.1 57.1 57.1 57.1 61.5 50.1 58.8 52.5 66.1 39.8 69.6 25.9 54.3 50.2 62.8 38.1 67.9 24.9 49.4 47.8 58.0 38.6 65.3 23.4 44.8 44.8 52.2 36.2 61.6 21.7 61.5 61.5 66.4 49.8 70.3 36.8 57.8 57.8 63.0 48.6 68.3 35.0 53.6 53.6 58.2 46.5 65.6 33.9 49.4 49.4 52.6 44.0 61.8 32.2 65.4 65.4 67.0 59.8 71.0 44.6 62.4 62.4 63.7 59.2 69.0 44.3 58.7 58.7 59.4 57.4 66.0 43.8 54.3 54.3 54.3 54.3 62.0 42.5 68.4 68.4 68.4 68.4 71.7 52.8 66.1 66.1 66.1 66.1 69.6 53.6 63.1 63.1 63.0 63.0 66.4 53.6 59.3 59.3 59.3 59.3 62.4 52.7 60.0 55.1 66.6 40.8 70.0 26.4 55.5 52.8 63.6 39.6 68.3 25.3 50.6 50.4 59.0 37.4 65.7 24.0 46.2 46.2 53.1 38.2 62.2 22.1 63.2 63.2 67.1 51.4 70.7 37.7 59.6 59.6 63.8 50.7 68.8 35.8 55.4 55.4 59.2 48.8 66.2 35.0 51.1 51.1 53.5 46.3 62.4 33.4 66.7 66.7 67.8 62.0 71.5 45.3 64.1 64.1 64.8 61.9 69.5 45.5 60.5 60.5 60.8 60.6 66.6 45.2 56.3 56.3 56.2 56.2 62.7 44.3 69.5 69.5 69.5 69.5 72.1 54.1 67.4 67.4 67.4 67.4 70.2 55.3 64.6 64.6 64.5 64.5 67.1 55.7 61.1 61.1 61.0 61.0 63.2 55.1 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity 14 RT-PRC017-EN Performance Data Table PD-2 - Gross Cooling Capacities (kW) - YSC072AD - (SI) Ambient Temperature (C) m3/h Airflow 3670 4080 4490 4900 Enter. Dry Bulb Temp (C) 24 27 30 33 24 27 30 33 24 27 30 33 24 27 30 33 30 35 40 45 Entering Wet Bulb Temperature (C) 16 19 22 16 19 22 16 19 22 16 19 22 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 20.9 17.5 23.3 14.6 24.6 10.3 19.7 16.8 22.4 13.6 24.0 9.9 18.4 16.1 21.2 12.9 23.2 9.4 17.1 15.4 19.7 12.9 22.0 9.0 21.6 21.2 23.4 17.4 24.8 13.5 20.4 20.4 22.5 17.0 24.1 13.3 19.4 19.4 21.2 16.4 23.3 12.8 18.2 18.2 19.8 15.7 22.1 12.3 22.9 22.9 23.6 20.6 25.0 16.5 22.1 22.1 22.7 20.4 24.3 16.3 21.0 21.0 21.5 19.9 23.5 16.1 19.9 19.9 20.2 19.2 22.2 15.6 24.0 24.0 24.1 23.8 25.2 19.4 23.4 23.4 23.3 23.3 24.5 19.3 22.5 22.5 22.4 22.4 23.6 19.3 21.4 21.4 21.4 21.4 22.3 18.8 21.5 18.5 23.6 15.2 24.8 10.6 20.3 17.9 22.8 14.2 24.2 10.1 19.0 17.2 21.6 13.6 23.4 9.8 17.6 16.4 20.1 12.9 22.3 9.3 22.3 22.3 23.8 18.1 25.1 14.5 21.3 21.3 22.9 17.9 24.3 13.6 20.2 20.2 21.6 17.3 23.6 13.4 19.0 19.0 20.2 16.6 22.4 12.8 23.6 23.6 24.0 21.6 25.3 17.6 22.9 22.9 23.2 21.5 24.6 16.8 21.8 21.8 22.0 21.1 23.7 16.7 20.7 20.7 20.8 20.5 22.5 16.3 24.6 24.6 24.6 24.6 25.5 20.0 23.9 23.9 23.9 23.9 24.8 20.1 23.1 23.1 23.1 23.1 23.9 20.1 22.1 22.1 22.1 22.1 22.7 19.8 22.0 19.5 23.9 15.8 25.0 10.7 20.8 18.9 23.1 14.7 24.4 10.4 19.5 18.2 21.9 14.2 23.5 10.1 18.1 17.4 20.5 13.5 22.5 9.6 22.9 22.9 24.0 18.7 25.3 13.9 22.1 22.1 23.2 18.6 24.5 13.9 20.9 20.9 22.0 18.2 23.7 13.6 19.7 19.7 20.6 17.6 22.6 13.3 24.1 24.1 24.3 22.4 25.5 17.4 23.4 23.4 23.5 22.4 24.8 17.3 22.5 22.5 22.5 22.2 23.9 17.2 21.3 21.3 21.3 21.3 22.8 17.0 25.0 25.0 25.0 25.0 25.7 20.7 24.4 24.4 24.4 24.4 25.1 20.8 23.7 23.7 23.7 23.7 24.2 20.8 22.6 22.6 22.6 22.6 23.1 20.7 22.4 20.3 24.1 16.3 25.2 10.9 21.2 19.8 23.2 15.1 24.5 10.7 19.9 19.1 22.2 14.7 23.6 10.3 18.5 18.4 20.8 14.0 22.7 9.9 23.4 23.4 24.3 19.3 25.5 14.5 22.6 22.6 23.4 19.2 24.7 14.7 21.5 21.5 22.3 19.0 23.8 14.0 20.3 20.3 20.9 18.4 22.8 13.7 24.5 24.5 24.6 23.2 25.6 17.8 23.8 23.8 23.9 23.2 25.0 17.8 23.0 23.0 23.0 23.0 24.1 17.7 21.8 21.8 21.8 21.8 23.0 17.7 25.4 25.4 25.4 25.4 25.9 21.2 24.8 24.8 24.8 24.8 25.3 21.4 24.1 24.1 24.1 24.1 24.4 21.4 23.1 23.1 23.1 23.1 23.4 21.6 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-2a _ Gross Cooling Capacities (MBH) - YSC072AD - (IP) Ambient Temperature (F) CFM Airflow 2160 2400 2640 2880 Enter. Dry Bulb Temp (F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90 85 95 105 115 Entering Wet Bulb Temperature (F) 61 67 73 61 67 73 61 67 73 61 67 73 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 72.2 59.1 80.6 47.1 85.1 31.0 67.5 56.5 77.7 44.1 82.7 29.6 62.6 53.9 73.0 41.8 79.9 28.0 57.4 51.2 67.5 39.2 75.5 26.0 73.8 70.7 81.0 56.1 85.8 42.2 69.4 68.2 77.9 55.0 83.4 40.7 65.0 65.0 73.1 52.6 80.4 39.0 60.6 60.6 67.6 50.0 75.8 36.8 77.7 77.7 81.4 66.3 86.3 51.7 74.3 74.3 78.2 65.6 83.8 50.1 70.3 70.3 73.6 63.5 80.7 49.2 66.0 66.0 68.3 61.0 76.1 47.4 81.3 81.3 82.4 76.3 87.1 59.8 78.8 78.8 79.4 76.0 84.6 59.4 75.1 75.1 75.3 74.6 81.3 59.0 70.8 70.8 70.7 70.7 76.6 57.4 74.2 62.5 81.6 49.2 85.7 31.5 69.3 59.9 78.7 46.0 83.4 30.1 64.4 57.3 74.2 43.7 80.2 28.5 59.1 54.6 68.9 41.1 76.3 26.6 76.1 75.0 82.1 58.2 86.5 43.7 72.1 72.1 79.0 57.4 84.2 42.1 67.9 67.9 74.4 55.4 80.9 40.4 63.3 63.3 69.0 53.0 76.8 38.4 80.0 80.0 82.6 69.1 86.8 52.8 77.1 77.1 79.5 68.7 84.7 51.6 73.1 73.1 75.3 67.3 81.4 50.7 68.7 68.7 70.1 65.0 77.2 49.4 83.3 83.3 83.8 79.7 87.1 61.5 80.7 80.7 80.9 79.4 85.5 61.5 77.5 77.5 77.5 77.5 82.1 61.1 73.3 73.3 73.3 73.3 77.8 60.2 75.8 65.6 82.3 50.7 86.2 32.0 71.0 63.2 79.4 49.8 84.0 30.7 66.0 60.6 75.4 45.6 80.7 29.0 60.6 57.8 70.0 42.9 77.0 27.2 78.1 78.1 82.9 60.1 87.2 44.1 74.6 74.6 79.8 59.4 84.7 44.3 70.3 70.3 75.6 58.1 81.2 41.3 65.7 65.7 70.1 55.7 77.6 39.8 81.7 81.7 83.6 71.6 88.2 54.0 79.1 79.1 80.5 71.3 85.4 53.6 75.4 75.4 76.6 70.7 82.0 52.1 70.9 70.9 71.6 68.7 78.1 51.3 84.8 84.8 85.0 82.5 89.1 62.3 82.3 82.3 82.3 82.3 86.1 61.2 79.4 79.4 79.4 79.4 82.8 63.0 75.2 75.2 75.2 75.2 78.7 62.8 77.0 68.3 82.9 52.2 86.6 32.5 72.5 66.4 80.0 51.4 84.5 31.2 67.5 63.7 76.2 47.1 81.2 29.5 62.1 61.0 70.8 44.7 77.6 27.8 79.6 79.6 83.7 61.8 87.6 44.7 76.6 76.6 80.6 61.3 85.4 44.0 72.4 72.4 76.5 60.5 81.8 42.1 67.7 67.7 71.1 58.2 78.1 40.9 83.0 83.0 84.4 73.9 88.7 54.9 80.4 80.4 81.5 73.9 86.2 54.1 77.1 77.1 77.8 73.8 82.7 53.5 72.7 72.7 72.9 71.9 78.8 53.0 85.9 85.9 86.0 85.0 89.6 65.2 83.6 83.6 83.6 83.6 87.0 63.2 81.0 81.0 81.0 81.0 83.5 65.0 76.8 76.8 76.8 76.8 79.5 65.3 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity RT-PRC017-EN 15 Performance Data Table PD-3 - Gross Cooling Capacities (kW) - YSC090AD - (SI) Ambient Temperature (C) m3/h Airflow 4590 5100 5610 6120 Enter. Dry Bulb Temp (C) 24 27 30 33 24 27 30 33 24 27 30 33 24 27 30 33 30 35 40 45 Entering Wet Bulb Temperature (C) 16 19 22 16 19 22 16 19 22 16 19 22 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 24.5 21.6 26.9 17.1 28.1 12.0 22.7 20.6 25.8 16.3 27.7 11.5 20.8 19.6 24.1 15.4 26.8 11.0 19.0 18.7 22.0 14.8 25.6 10.3 25.4 25.4 27.1 21.1 28.5 15.9 24.1 24.1 25.9 20.8 27.8 15.9 22.5 22.5 24.3 20.0 27.0 15.5 20.9 20.9 22.2 19.0 25.7 14.8 27.0 27.0 27.4 25.3 28.7 19.5 26.0 26.0 26.4 25.3 28.1 19.7 24.8 24.8 25.0 24.8 27.1 19.6 23.2 23.2 23.1 23.1 25.8 19.2 28.1 28.1 28.1 28.1 29.0 23.3 27.5 27.5 27.5 27.5 28.4 23.6 26.5 26.5 26.5 26.5 27.4 23.9 25.3 25.3 25.3 25.3 26.1 23.6 25.1 23.0 27.2 18.1 28.4 12.4 23.4 22.1 26.2 17.1 27.8 11.9 21.4 21.1 24.6 16.8 27.1 11.3 19.7 19.7 22.5 15.3 25.9 10.7 26.3 26.3 27.4 22.0 28.6 16.3 25.1 25.1 26.4 22.0 28.0 16.2 23.6 23.6 24.9 21.4 27.2 16.0 21.9 21.9 22.8 20.4 26.0 15.6 27.6 27.6 27.8 26.4 29.0 20.2 26.8 26.8 27.0 26.8 28.3 20.4 25.7 25.7 25.7 25.7 27.4 20.6 24.3 24.3 24.3 24.3 26.2 20.4 28.6 28.6 28.6 28.6 29.3 24.1 28.1 28.1 28.1 28.1 28.7 24.6 27.3 27.3 27.3 27.3 27.8 25.0 26.2 26.2 26.2 26.2 26.6 25.1 25.6 24.2 27.4 18.4 28.4 12.5 24.0 23.5 26.5 18.3 28.0 12.2 22.0 22.0 25.1 17.1 27.3 11.7 20.4 20.4 22.9 16.2 26.2 11.1 26.9 26.9 27.7 22.8 28.8 16.5 25.9 25.9 26.8 23.0 28.3 16.7 24.5 24.5 25.4 22.7 27.4 16.5 22.8 22.8 23.5 21.8 26.3 16.3 28.0 28.0 28.1 27.3 29.1 20.6 27.4 27.4 27.4 27.4 28.7 21.2 26.5 26.5 26.4 26.4 27.7 21.4 25.2 25.2 25.2 25.2 26.5 21.4 28.9 28.9 28.9 28.9 29.5 24.7 28.5 28.5 28.5 28.5 29.1 25.6 27.8 27.8 27.8 27.8 28.1 26.0 26.8 26.8 26.8 26.8 27.0 26.3 26.1 25.4 27.6 18.5 28.5 12.7 24.5 24.5 26.7 19.1 28.1 12.5 22.8 22.8 25.4 18.0 27.4 12.0 21.1 21.1 23.4 17.0 26.3 11.4 27.3 27.3 27.9 23.4 28.9 16.8 26.5 26.5 27.1 23.9 28.5 17.1 25.3 25.3 25.8 23.8 27.7 17.0 23.6 23.6 24.1 23.1 26.5 16.9 28.3 28.3 28.4 28.1 29.2 21.0 27.8 27.8 27.8 27.8 28.8 21.8 27.0 27.0 27.0 27.0 27.9 22.1 25.8 25.8 25.8 25.8 26.8 22.3 29.1 29.1 29.1 29.1 29.6 25.2 28.8 28.8 28.8 28.8 29.3 26.4 28.2 28.2 28.2 28.2 28.4 26.9 27.3 27.3 27.3 27.3 27.4 27.4 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-3a - Gross Cooling Capacities (MBH) - YSC090AD - (IP) Ambient Temperature (F) CFM Airflow 2700 3000 3300 3600 Enter. Dry Bulb Temp (F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90 85 95 105 115 Entering Wet Bulb Temperature (F) 61 67 73 61 67 73 61 67 73 61 67 73 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 84.4 72.7 92.7 55.2 96.6 35.6 77.7 69.1 89.4 52.6 95.2 34.0 70.4 65.4 83.4 50.6 92.5 32.0 63.7 61.9 75.3 46.9 88.2 29.8 86.5 86.5 93.3 67.5 97.8 48.9 81.2 81.2 89.6 66.8 96.2 48.4 75.1 75.1 83.8 64.0 93.1 46.6 69.4 69.4 75.8 60.3 88.5 44.1 91.5 91.5 94.2 80.6 98.9 59.9 87.7 87.7 90.6 80.8 97.2 60.5 82.5 82.5 85.1 78.8 93.5 59.5 76.4 76.4 77.7 75.2 88.8 58.1 95.1 95.1 95.7 93.2 100.0 71.0 92.6 92.6 92.5 92.5 97.5 71.8 88.7 88.7 88.7 88.7 94.3 72.6 83.7 83.7 83.6 83.6 89.5 71.8 86.5 77.3 93.5 56.9 97.1 36.1 80.0 73.9 90.6 56.4 95.8 34.6 72.6 70.1 85.2 52.3 93.2 32.7 65.6 65.6 76.9 49.9 89.1 30.5 89.4 89.4 94.3 70.0 98.3 52.8 84.9 84.9 91.0 70.2 96.9 49.4 78.8 78.8 85.6 68.2 93.9 48.9 72.7 72.7 77.8 64.5 89.6 46.3 93.6 93.6 95.4 83.8 99.4 61.1 90.6 90.6 92.2 85.2 98.0 62.3 86.1 86.1 87.3 84.2 94.5 61.9 80.1 80.1 80.1 80.1 90.0 61.2 96.8 96.8 97.0 96.7 100.5 72.8 94.8 94.8 94.8 94.8 99.0 75.4 91.5 91.5 91.4 91.4 95.4 75.8 87.0 87.0 87.0 87.0 90.9 75.9 88.1 81.3 94.3 59.1 97.5 36.7 82.1 78.5 91.4 58.6 96.2 35.2 74.1 74.1 86.4 54.8 93.7 33.4 68.1 68.1 78.5 51.2 89.8 31.2 91.4 91.4 95.1 72.1 98.7 50.2 87.6 87.6 92.1 73.3 97.4 50.3 82.2 82.2 87.1 72.0 94.5 49.7 75.6 75.6 79.7 68.7 90.4 48.3 95.1 95.1 96.2 86.6 99.8 62.1 92.7 92.7 93.6 89.0 98.5 63.8 88.8 88.8 89.2 89.1 95.2 64.0 83.5 83.5 83.5 83.5 90.9 63.9 97.9 97.9 97.9 97.9 101.0 74.3 96.4 96.4 96.3 96.3 99.7 77.5 93.5 93.5 93.5 93.5 96.3 78.6 89.4 89.4 89.4 89.4 92.1 79.5 89.5 85.0 95.1 60.6 97.8 37.2 84.0 83.1 92.2 60.7 96.6 35.7 76.7 76.7 87.5 57.3 94.1 34.0 70.4 70.4 80.0 53.8 90.4 31.9 92.9 92.9 95.6 74.0 99.0 50.8 89.7 89.7 93.0 76.0 97.8 51.0 84.8 84.8 88.3 75.6 95.2 50.9 78.1 78.1 81.6 72.8 90.9 49.5 96.2 96.2 96.9 88.9 100.2 63.1 94.2 94.2 94.7 92.3 99.0 65.1 90.7 90.7 90.7 90.7 95.8 65.8 86.0 86.0 86.0 86.0 91.7 66.3 98.7 98.7 98.7 98.7 101.3 75.7 97.5 97.5 97.5 97.5 100.1 79.4 94.9 94.9 94.9 94.9 97.0 81.1 91.2 91.2 91.2 91.2 93.0 82.7 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity 16 RT-PRC017-EN Performance Data Table PD-4 - Gross Cooling Capacities (kW) - YSC102AD - (SI) Ambient Temperature (C) m3/h Airflow 5200 5780 6360 6940 Enter. Dry Bulb Temp (C) 24 27 30 33 24 27 30 33 24 27 30 33 24 27 30 33 30 35 40 45 Entering Wet Bulb Temperature (C) 16 19 22 16 19 22 16 19 22 16 19 22 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 28.0 24.3 31.5 19.5 33.4 14.1 26.0 23.3 30.0 18.7 32.5 13.5 23.9 22.2 27.8 17.7 31.3 12.9 21.6 21.6 25.4 17.3 29.7 12.2 29.0 28.4 31.6 24.3 33.6 18.7 27.4 27.1 30.1 23.6 32.7 18.5 25.6 25.6 28.0 22.7 31.4 17.8 23.9 23.9 25.6 21.6 29.8 17.1 31.0 31.0 31.9 29.0 33.9 23.0 29.7 29.7 30.5 28.6 32.9 22.8 28.1 28.1 28.1 28.1 31.5 22.5 26.3 26.3 26.5 25.7 29.9 22.0 32.6 32.6 32.7 32.1 34.1 27.3 31.6 31.6 31.6 31.4 33.2 27.3 30.4 30.4 30.3 30.3 31.8 27.2 28.9 28.9 28.8 28.8 30.2 26.8 28.8 25.8 31.9 20.4 33.6 14.4 26.8 24.8 30.5 19.6 32.8 13.9 24.2 24.2 28.5 18.7 31.6 13.4 22.5 22.5 26.0 17.6 30.1 12.6 30.1 29.8 32.1 25.4 34.0 19.2 28.6 28.6 30.7 25.0 32.9 19.1 26.8 26.8 28.8 24.2 31.7 18.6 25.0 25.0 26.3 23.1 30.2 17.9 32.0 32.0 32.5 30.5 34.2 23.7 30.9 30.9 30.9 30.9 33.2 23.7 29.4 29.4 29.4 29.4 31.9 23.6 27.6 27.6 27.7 27.2 30.3 23.2 33.4 33.4 33.4 33.2 34.5 28.1 32.6 32.6 32.5 32.5 33.6 28.5 31.4 31.4 31.4 31.4 32.3 28.5 30.0 30.0 30.0 30.0 30.8 28.3 29.5 27.3 32.2 21.1 33.8 14.7 27.6 26.3 31.0 20.5 33.0 14.4 25.1 25.1 29.1 19.6 31.8 13.8 23.5 22.9 26.5 18.5 30.4 12.9 31.0 31.0 32.5 26.5 34.2 19.7 29.7 29.7 31.2 26.3 33.3 19.5 27.9 27.9 29.4 25.6 32.0 19.2 26.0 26.0 27.0 24.5 30.5 18.7 32.7 32.7 33.0 31.7 34.6 24.5 31.7 31.7 31.7 31.7 33.6 24.6 30.4 30.4 30.5 29.9 32.3 24.5 28.8 28.8 28.8 28.6 30.7 24.3 34.0 34.0 34.0 34.0 34.8 28.9 33.2 33.2 33.2 33.2 33.9 29.5 32.1 32.1 32.1 32.1 32.7 29.7 30.9 30.9 30.9 30.9 31.3 29.7 30.1 28.7 32.5 21.7 33.9 15.1 27.9 27.9 31.3 21.4 33.1 14.7 26.0 26.0 29.3 20.4 32.2 14.2 24.2 23.9 27.0 19.4 30.6 13.3 31.7 31.7 32.8 27.4 34.4 20.0 30.5 30.5 31.6 27.4 33.4 20.0 28.8 28.8 29.8 26.9 32.3 19.7 26.9 26.9 27.6 25.9 30.7 19.4 33.2 33.2 33.2 33.2 34.8 25.0 32.3 32.3 32.4 31.7 33.7 25.2 31.2 31.2 31.2 30.9 32.6 25.4 29.7 29.7 29.7 29.7 31.0 25.3 34.4 34.4 34.4 34.4 35.2 30.0 33.7 33.7 33.7 33.7 34.2 30.4 32.9 32.9 32.9 32.9 33.1 30.8 31.5 31.5 31.5 31.5 31.4 31.4 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-4a - Gross Cooling Capacities (MBH) - YSC102AD - (IP) Ambient Temperature (F) CFM Airflow 3060 3400 3740 4080 Enter. Dry Bulb Temp 61 (F) TGC SHC 75 96.7 81.9 80 98.2 98.2 85 105.0 105.0 90 110.4 110.4 75 99.3 87.0 80 102.5 100.4 85 108.4 108.4 90 113.2 113.2 75 101.6 91.8 80 105.4 104.4 85 111.0 111.0 90 115.2 115.2 75 103.5 96.3 80 107.9 107.9 85 112.9 112.9 90 116.7 116.7 85 67 73 TGC SHC TGC SHC 109.1 63.4 115.0 42.2 109.4 78.3 116.1 58.1 110.2 93.1 117.3 70.8 111.6 107.4 118.0 84.0 110.2 65.9 115.6 42.9 110.9 81.6 116.9 59.2 111.9 97.4 118.2 72.7 113.1 113.1 119.5 86.5 111.3 67.8 116.2 43.6 112.1 84.5 117.6 60.0 113.3 101.2 118.9 74.2 115.2 115.2 120.3 88.6 112.1 69.5 116.6 43.8 113.0 87.1 118.1 60.8 114.4 104.5 119.5 75.5 116.7 116.7 120.9 90.6 95 61 TGC SHC 89.1 78.1 92.7 90.8 100.0 100.0 106.5 106.5 91.8 83.2 96.7 95.9 104.1 104.1 109.7 109.7 94.3 88.2 100.3 100.3 107.0 107.0 112.1 112.1 94.9 94.9 103.1 103.1 109.3 109.3 113.9 113.9 105 Entering Wet Bulb Temperature (F) 67 73 61 67 TGC SHC TGC SHC TGC SHC TGC SHC 104.0 60.7 112.1 40.4 81.2 74.1 96.3 59.2 104.2 76.3 113.0 56.2 85.7 85.2 96.6 72.9 105.0 91.8 113.6 70.4 93.6 93.6 98.0 88.8 106.4 106.4 114.4 83.5 101.4 101.4 101.7 99.6 105.8 63.7 112.9 41.1 83.6 79.1 98.7 60.6 106.0 80.4 113.8 58.8 89.7 89.7 99.0 77.4 107.2 97.0 114.6 72.7 98.2 98.2 100.8 94.9 109.9 107.6 115.6 86.6 105.1 105.1 105.1 104.4 107.1 66.5 113.5 41.8 84.7 84.7 100.4 63.0 107.4 84.0 114.7 59.4 93.4 93.4 100.9 81.6 108.9 101.7 116.0 74.8 101.8 101.8 101.8 101.8 112.1 111.1 116.5 89.3 107.8 107.8 107.7 107.7 107.9 68.7 114.0 42.5 87.5 87.5 101.8 65.6 108.6 87.3 115.3 60.3 96.8 96.8 102.5 85.6 110.4 105.7 116.7 76.5 104.5 104.5 104.5 104.5 113.8 113.8 117.9 92.9 109.9 109.9 109.8 109.8 115 73 61 67 73 TGC SHC TGC SHC TGC SHC TGC SHC 107.9 38.3 73.7 70.3 87.0 55.2 102.4 35.8 108.5 53.9 79.3 79.3 87.4 68.8 102.7 51.3 108.9 68.7 86.8 86.8 89.2 84.7 103.1 66.7 109.6 83.1 94.8 94.8 94.9 94.6 103.5 81.6 108.8 39.0 75.2 75.2 89.0 58.6 103.4 36.5 109.6 56.1 82.9 82.9 89.7 73.3 103.9 53.5 110.1 71.5 91.0 91.0 91.0 91.0 104.2 70.0 111.0 86.9 99.4 99.4 99.2 99.2 105.1 86.0 109.5 39.6 78.4 76.4 90.9 59.0 104.2 37.1 110.0 57.9 86.1 86.1 91.7 77.7 104.8 55.6 111.2 73.8 94.9 94.9 94.9 94.9 105.3 72.9 112.1 90.2 102.6 102.6 102.6 102.6 106.4 90.0 110.0 40.3 80.7 79.5 92.4 61.7 104.8 37.8 110.7 59.5 89.1 89.1 93.7 82.0 105.4 57.5 111.9 76.7 98.2 98.2 98.6 96.7 106.2 75.5 113.0 93.2 104.9 104.9 104.9 104.9 107.5 93.5 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity RT-PRC017-EN 17 Performance Data Table PD-5 - Gross Cooling Capacities (kW) - YSC120AD - (SI) Ambient Temperature (C) m3/h Airflow 6120 6800 7480 8160 Enter. Dry Bulb Temp (C) 24 27 30 33 24 27 30 33 24 27 30 33 24 27 30 33 30 35 40 45 Entering Wet Bulb Temperature (C) 16 19 22 16 19 22 16 19 22 16 19 22 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 31.9 28.6 35.3 22.8 37.2 15.9 29.6 27.4 33.6 21.7 36.5 15.4 27.1 26.2 31.0 20.5 35.2 14.8 24.6 24.6 28.4 19.9 33.2 14.0 33.4 33.4 35.5 28.2 37.7 21.4 31.6 31.6 33.9 27.8 36.7 21.4 29.5 29.5 31.3 26.6 35.3 20.7 27.5 27.5 28.9 25.5 33.3 19.9 35.5 35.5 36.0 33.8 38.1 26.5 34.2 34.2 34.5 33.8 37.0 26.7 32.3 32.3 32.2 32.2 35.5 26.6 30.4 30.4 30.4 30.4 33.4 25.9 37.1 37.1 37.1 37.1 38.5 31.6 36.2 36.2 36.2 36.2 37.3 31.9 34.8 34.8 34.8 34.8 35.9 32.3 33.2 33.2 33.2 33.2 34.0 31.8 32.7 30.4 35.7 23.8 37.5 16.3 30.5 29.3 34.2 22.8 36.8 15.9 27.8 27.8 31.9 21.8 35.5 15.3 25.7 25.7 29.0 21.2 33.7 14.5 34.5 34.5 36.0 29.5 38.0 21.9 32.9 32.9 34.5 29.4 37.0 22.0 30.9 30.9 32.3 28.5 35.7 21.7 28.7 28.7 29.7 27.4 33.8 21.0 36.3 36.3 36.6 35.4 38.4 27.4 35.3 35.3 35.3 35.3 37.3 27.6 33.7 33.7 33.7 33.7 35.9 27.8 31.8 31.8 31.7 31.7 34.0 27.5 37.9 37.9 37.8 37.8 38.9 32.8 37.0 37.0 37.0 37.0 37.8 33.3 35.9 35.9 35.9 35.9 36.5 33.9 34.4 34.4 34.4 34.4 34.7 33.8 33.5 32.2 36.0 24.7 37.8 16.9 31.1 31.1 34.7 23.9 37.0 16.3 28.9 28.9 32.4 22.9 35.8 15.7 26.6 26.6 29.6 22.5 34.1 14.9 35.3 35.3 36.4 30.6 38.2 22.4 34.0 34.0 35.0 30.8 37.4 22.7 32.0 32.0 33.0 30.2 36.0 22.5 29.9 29.9 30.5 29.1 34.2 22.0 37.0 37.0 37.0 37.0 38.7 28.1 36.1 36.1 36.1 36.1 37.9 28.9 34.7 34.7 34.7 34.7 36.4 29.1 32.9 32.9 32.9 32.9 34.5 29.0 38.4 38.4 38.3 38.3 39.2 33.7 37.7 37.7 37.7 37.7 38.4 34.9 36.7 36.7 36.7 36.7 37.0 35.4 35.3 35.3 35.3 35.3 35.3 35.3 33.9 33.9 36.3 24.9 37.9 17.3 32.0 32.0 35.0 25.6 37.5 16.1 29.8 29.8 32.8 23.9 36.1 16.2 27.5 27.5 29.8 23.6 34.4 15.3 35.9 35.9 36.7 31.7 38.5 22.8 34.8 34.8 35.5 32.2 37.7 23.2 32.9 32.9 33.6 31.9 36.3 23.2 30.6 30.6 30.6 30.6 34.5 23.0 37.5 37.5 37.5 37.5 38.9 28.8 36.7 36.7 36.7 36.7 38.1 29.8 35.5 35.5 35.5 35.5 36.7 30.2 33.7 33.7 33.7 33.7 34.9 30.5 38.8 38.8 38.7 38.7 39.5 34.6 38.4 38.4 38.2 38.2 38.7 36.1 37.3 37.3 37.3 37.3 37.4 36.7 36.0 36.0 36.0 36.0 36.0 36.0 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity Table PD-5a - Gross Cooling Capacities (MBH) - YSC120AD - (IP) Ambient Temperature (F) CFM Airflow 3600 4000 4400 4800 Enter. Dry Bulb Temp 61 (F) TGC SHC 75 109.9 96.4 80 113.5 113.5 85 120.2 120.2 90 125.4 125.4 75 112.7 102.4 80 117.3 117.3 85 123.2 123.2 90 127.9 127.9 75 115.1 108.2 80 120.1 120.1 85 125.5 125.5 90 130.0 130.0 75 117.1 113.2 80 122.3 122.3 85 127.2 127.2 90 131.3 131.3 85 67 73 TGC SHC TGC SHC 122.1 73.8 128.5 47.6 122.6 90.4 129.9 65.7 123.8 108.0 131.3 80.9 125.4 125.4 132.7 96.3 123.1 75.6 129.3 48.4 124.1 94.1 130.8 66.9 125.6 112.8 132.3 82.9 127.9 127.9 133.8 99.2 124.5 77.5 130.0 49.2 125.3 97.3 131.6 67.9 127.0 116.9 133.1 84.7 129.7 129.7 134.7 101.8 125.5 81.7 130.6 50.0 126.5 100.7 132.2 68.9 128.4 121.1 133.8 86.3 131.5 131.5 135.4 104.2 95 61 TGC SHC 101.2 92.1 106.6 106.6 115.2 115.2 121.8 121.8 104.2 98.3 111.1 111.1 119.0 119.0 124.9 124.9 107.0 104.4 114.9 114.9 121.9 121.9 127.3 127.3 108.8 108.8 117.8 117.8 124.1 124.1 129.3 129.3 105 Entering Wet Bulb Temperature (F) 67 73 61 67 TGC SHC TGC SHC TGC SHC TGC SHC 116.7 70.3 125.9 45.7 91.8 87.5 107.7 67.7 117.1 89.2 127.2 65.0 99.0 99.0 108.4 85.4 118.5 107.9 127.8 81.5 108.1 108.1 110.5 104.9 121.8 121.8 128.7 97.3 116.4 116.4 116.4 116.4 118.5 73.6 126.9 46.6 93.7 93.7 109.9 70.9 119.0 94.0 128.2 66.8 103.5 103.5 110.8 90.8 120.8 114.1 129.5 84.5 112.5 112.5 112.5 112.5 124.9 124.9 130.8 102.4 120.2 120.2 120.2 120.2 119.8 77.6 127.6 47.4 97.3 97.3 111.7 73.2 120.6 98.4 129.0 68.2 107.3 107.3 112.9 96.1 122.8 119.6 130.5 87.0 116.4 116.4 116.3 116.3 127.2 127.2 131.9 105.9 123.0 123.0 123.0 123.0 120.8 80.6 128.3 48.2 100.5 100.5 113.2 76.3 122.0 102.4 129.8 69.5 110.5 110.5 114.9 101.3 124.1 124.1 131.2 89.2 119.0 119.0 119.0 119.0 129.0 129.0 132.8 108.9 125.2 125.2 125.2 125.2 115 73 TGC SHC 121.6 43.4 122.2 62.4 122.6 80.6 123.6 98.2 122.7 44.3 123.5 65.3 124.1 84.2 125.3 103.1 123.6 45.2 124.5 68.1 125.3 88.0 126.7 107.5 124.3 46.1 125.7 69.3 126.5 90.9 127.8 111.4 61 TGC SHC 82.1 82.1 91.0 91.0 100.3 100.3 109.2 109.2 85.6 85.6 95.2 95.2 104.9 104.9 113.9 113.9 88.7 88.7 98.9 98.9 108.7 108.7 117.2 117.2 91.6 91.6 102.2 102.2 112.0 112.0 119.8 119.8 67 TGC SHC 97.2 63.2 98.2 81.0 100.3 100.3 109.2 109.2 99.3 67.2 100.8 86.6 104.8 104.8 113.8 113.8 101.1 71.1 103.1 92.0 108.7 108.7 117.2 117.2 102.7 72.1 105.2 97.3 112.0 112.0 119.8 119.8 73 TGC SHC 115.0 40.9 115.2 59.7 115.4 78.4 116.4 97.0 116.5 41.9 116.8 62.5 117.1 83.0 118.4 102.9 117.6 42.7 118.0 65.1 118.4 87.0 120.2 108.4 118.5 43.6 119.0 67.7 119.7 90.9 121.7 113.3 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity 18 RT-PRC017-EN Performance Data Table PD-6 - Belt Drive Evaporator Fan Performance - YSC060AD*L - Low Heat - Downflow Configuration - (SI) External Static Pressure (Pascals) 25 m3/h RPM kW 2720 3060 3400 3740 4080 716 791 867 944 1022 0.28 0.38 0.51 0.66 0.85 m3/h 2720 3060 3400 3740 4080 50 75 100 125 RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Low Static Drive 768 0.32 816 0.36 863 0.39 909 0.44 840 0.43 884 0.47 927 0.51 969 0.56 914 0.56 955 0.61 994 0.66 1033 0.71 989 0.73 1027 0.78 1063 0.84 1099 0.89 1064 0.92 1101 0.98 1135 1.04 1168 1.10 External Static Pressure (Pascals) 275 300 325 350 RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Drive 1135 0.75 1166 0.80 1198 0.85 1228 0.91 1188 0.90 1218 0.96 1249 1.01 1279 1.07 1244 1.08 1273 1.14 1303 1.20 1332 1.27 1300 1.27 - 150 RPM kW 175 RPM kW 953 1010 1070 1134 1200 993 1049 1107 1168 1233 0.50 0.61 0.76 0.94 1.16 0.55 0.67 0.82 0.99 1.22 200 225 250 RPM kW RPM kW RPM kW 1.12 Nom kW Std Mtr & Drive 1031 0.60 1067 0.65 1101 0.70 1087 0.73 1122 0.79 1156 0.85 1143 0.88 1178 0.95 1212 1.02 1202 1.05 1235 1.12 1267 1.19 - 375 RPM kW 1258 1307 - 0.96 1.13 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 Table PD-6a - Belt Drive Evaporator Fan Performance - YSC060AD*L - Low Heat - Downflow Configuration - (IP) CFM 0.10 RPM BHP 1600 1800 2000 2200 2400 716 791 867 944 1022 CFM 1600 1800 2000 2200 2400 0.37 0.51 0.68 0.89 1.14 0.20 RPM BHP 1-1/2 768 0.43 840 0.57 914 0.76 989 0.97 1064 1.23 External Static Pressure (Inches of Water) 0.30 0.40 0.50 0.60 RPM BHP RPM BHP RPM BHP RPM BHP HP Standard Motor & Low Static Drive 816 0.48 863 0.53 909 0.60 953 0.67 884 0.63 927 0.69 969 0.75 1010 0.82 955 0.82 994 0.89 1033 0.95 1070 1.02 1027 1.05 1063 1.12 1099 1.19 1134 1.26 1101 1.32 1135 1.40 1168 1.48 1200 1.55 External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Drive 1135 1.01 1166 1.07 1198 1.14 1228 1.22 1188 1.21 1218 1.28 1249 1.36 1279 1.44 1244 1.45 1273 1.53 1303 1.61 1332 1.70 1300 1.70 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 RT-PRC017-EN 0.70 RPM BHP 993 1049 1107 1168 1233 0.74 0.90 1.10 1.33 1.63 0.80 0.90 1.00 RPM BHP RPM BHP RPM BHP 1-1/2 HP Std Motor & Drive 1031 0.81 1067 0.87 1101 0.94 1087 0.99 1122 1.06 1156 1.14 1143 1.18 1178 1.27 1212 1.36 1202 1.41 1235 1.51 1267 1.60 - 1.50 RPM BHP 1258 1307 - 1.29 1.51 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 19 Performance Data Table PD-7 - Belt Drive Evaporator Fan Performance - YSC060AD*L - Horizontal Configuration (SI) 25 m3/h RPM 2720 3060 3400 3740 4080 788 871 956 1042 1129 m3/h 2720 3060 3400 3740 4080 External Static Pressure (Pascals) 100 125 150 kW RPM kW RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Std Motor & Low Static Drive 1.12 0.33 850 0.38 911 0.44 964 0.49 1011 0.55 1055 0.61 0.45 927 0.51 983 0.57 1035 0.64 1082 0.70 1124 0.76 0.60 1006 0.67 1057 0.74 1106 0.81 1153 0.88 1195 0.95 0.78 1088 0.85 1133 0.93 1179 1.01 1224 1.09 1266 1.16 1.00 1171 1.08 1213 1.16 1255 1.25 1296 1.33 50 75 External Static Pressure (Pascals) 275 300 325 350 RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Drive 1248 0.91 1282 0.97 1314 1.04 1344 1.11 1310 1.09 1344 1.16 1373 1.30 - 175 200 225 RPM kW RPM kW RPM kW Nom kW Standard Motor & Drive 1097 0.66 1137 0.72 1176 0.78 1164 0.83 1201 0.89 1239 0.95 1233 1.02 1270 1.09 1305 1.16 1305 1.24 1340 1.32 - 250 RPM kW 1213 0.84 1275 1.02 1339 1.23 - 375 RPM kW 1374 - 1.18 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-7a - Belt Drive Evaporator Fan Performance - YSC060AD*L - Horizontal Configuration - (IP) CFM 1600 1800 2000 2200 2400 CFM 1600 1800 2000 2200 2400 0.10 RPM BHP 1-1/2 788 0.44 871 0.60 956 0.80 1042 1.05 1129 1.34 External Static Pressure (Inches of Water) 0.20 0.30 0.40 0.50 0.60 0.70 0.80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP HP Standard Motor & Low Static Drive 1-1/2 HP Standard Motor & Drive 850 0.51 911 0.59 964 0.66 1011 0.74 1055 0.81 1097 0.89 1137 0.97 927 0.68 983 0.77 1035 0.85 1082 0.94 1124 1.02 1164 1.11 1201 1.19 1006 0.89 1057 0.99 1106 1.08 1153 1.18 1195 1.27 1233 1.36 1270 1.46 1088 1.15 1133 1.25 1179 1.35 1224 1.46 1266 1.56 1305 1.66 1340 1.77 1171 1.45 1213 1.56 1255 1.67 1296 1.78 - External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Drive 1248 1.21 1282 1.30 1314 1.39 1344 1.48 1310 1.46 1344 1.55 1373 1.75 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 20 0.90 RPM BHP 1.00 RPM BHP 1176 1.05 1239 1.28 1305 1.55 1375 - 1213 1275 1339 - 1.13 1.37 1.65 - 1.50 RPM BHP 1374 - 1.58 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-8 - Belt Drive Evaporator Fan Performance - YSC060AD*H - High Heat - Downflow Configuration - (SI) 25 m3/h RPM kW 2720 3060 3400 3740 4080 734 813 894 974 1055 0.29 0.40 0.54 0.70 0.90 m3/h 2720 3060 3400 3740 4080 External Static Pressure (Pascals) 100 125 150 RPM kW RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Low Static Drive 784 0.33 833 0.37 879 0.41 924 0.46 967 0.52 859 0.45 903 0.49 945 0.53 987 0.58 1027 0.64 936 0.59 976 0.64 1014 0.69 1052 0.73 1089 0.79 1014 0.76 1051 0.82 1087 0.87 1122 0.92 1156 0.98 1093 0.97 1127 1.03 1160 1.09 1193 1.15 1225 1.20 50 75 External Static Pressure (Pascals) 275 300 325 350 RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Drive 1145 0.77 1177 0.82 1208 0.87 1238 0.93 1202 0.93 1232 0.98 1262 1.04 1290 1.09 1260 1.11 1289 1.17 1319 1.24 1347 1.30 1320 1.32 - 175 RPM kW 1007 1066 1126 1190 1256 0.57 0.70 0.85 1.03 1.26 200 225 250 RPM kW RPM kW RPM kW 1.12 Nom kW Std Mtr & Drive 1043 0.62 1078 0.67 1113 0.72 1103 0.76 1137 0.82 1169 0.87 1162 0.92 1196 0.98 1229 1.05 1224 1.10 1257 1.17 1288 1.24 1288 1.32 - 375 RPM kW 1268 1319 - 0.98 1.15 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-8a - Belt Drive Evaporator Fan Performance - YSC060AD*H - High Heat - Downflow Configuration - (IP) CFM 1600 1800 2000 2200 2400 0.10 0.20 0.30 RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Low Static Drive 734 0.39 784 0.44 833 0.49 813 0.54 859 0.60 903 0.66 894 0.72 936 0.79 976 0.86 974 0.94 1014 1.02 1051 1.10 1055 1.21 1093 1.30 1127 1.38 CFM RPM 1600 1800 2000 2200 2400 1145 1202 1260 1320 - 879 945 1014 1087 1160 0.55 0.72 0.92 1.17 1.46 External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Drive 1.03 1177 1.10 1208 1.17 1238 1.24 1.24 1232 1.32 1262 1.39 1290 1.47 1.49 1289 1.57 1319 1.66 1347 1.74 1.77 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 RT-PRC017-EN External Static Pressure (Inches of Water) 0.40 0.50 0.60 0.70 RPM BHP RPM BHP RPM BHP RPM BHP 924 987 1052 1122 1193 0.62 0.78 0.98 1.24 1.54 967 1027 1089 1156 1225 0.69 0.86 1.06 1.31 1.61 1007 1066 1126 1190 1256 0.76 0.94 1.14 1.38 1.69 0.80 0.90 1.00 RPM BHP RPM BHP RPM BHP 1-1/2 HP Std Motor & Drive 1043 0.83 1078 0.89 1113 0.96 1103 1.02 1137 1.09 1169 1.17 1162 1.23 1196 1.32 1229 1.41 1224 1.47 1257 1.57 1288 1.67 1288 1.77 - 1.50 RPM BHP 1268 1319 - 1.31 1.55 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 21 Performance Data Table PD-9 - Belt Drive Evaporator Fan Performance - YSC060AD*H - High Heat - Horizontal Configuration (SI) 25 External Static Pressure (Pascals) 100 125 150 175 200 225 kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Std Motor & Low Static Drive 1.12 Nom kW Standard Motor & Drive 0.34 871 0.40 930 0.46 980 0.51 1026 0.57 1069 0.63 1111 0.68 1151 0.74 1189 0.80 0.47 951 0.54 1006 0.60 1056 0.66 1100 0.73 1141 0.79 1180 0.85 1218 0.92 1255 0.98 0.63 1033 0.70 1083 0.77 1131 0.84 1176 0.91 1216 0.98 1253 1.05 1289 1.13 1323 1.20 0.83 1117 0.90 1163 0.98 1209 1.06 1251 1.14 1292 1.21 1329 1.29 1.06 1203 1.14 1245 1.23 1287 1.31 50 m3/h RPM 2720 3060 3400 3740 4080 809 895 983 1072 1161 m3/h 275 RPM kW 2720 3060 3400 3740 4080 1260 1324 - 0.93 1.12 - 75 External Static Pressure (Pascals) 300 325 350 RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Drive 1293 0.99 1324 1.06 1355 1.13 1357 1.19 1390 1.26 - 250 RPM kW 1225 1290 1357 - 0.87 1.05 1.27 - 375 RPM kW 1383 - 1.20 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-9a - Belt Drive Evaporator Fan Performance - YSC060AD*H - High Heat - Horizontal Configuration - (IP) CFM 1600 1800 2000 2200 2400 CFM 1600 1800 2000 2200 2400 0.10 RPM BHP 1-1/2 809 0.46 895 0.64 983 0.85 1072 1.11 1161 1.42 External Static Pressure (Inches of Water) 0.20 0.30 0.40 0.50 0.60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP HP Standard Motor & Low Static Drive 871 0.54 930 0.61 980 0.69 1026 0.76 1069 0.84 951 0.72 1006 0.81 1056 0.89 1100 0.97 1141 1.06 1033 0.94 1083 1.04 1131 1.13 1176 1.23 1216 1.32 1117 1.21 1163 1.32 1209 1.42 1251 1.52 1292 1.63 1203 1.53 1245 1.64 1287 1.76 - 1.00 RPM BHP 1225 1290 1357 - 1.16 1.41 1.70 - External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Drive 1260 1.24 1293 1.33 1324 1.42 1355 1.52 1383 1.60 1324 1.50 1357 1.59 1390 1.69 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 22 0.70 0.80 0.90 RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Drive 1111 0.92 1151 1.00 1189 1.08 1180 1.14 1218 1.23 1255 1.32 1253 1.41 1289 1.51 1323 1.60 1329 1.73 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-10 - Belt Drive Evaporator Fan Performance - YSC072AD*L - Low Heat - Downflow Configuration - (SI) 25 m3/h 75 100 RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Low Static Drive 532 0.22 592 0.27 646 0.32 570 0.28 624 0.33 677 0.39 556 0.30 610 0.36 659 0.41 707 0.48 601 0.39 652 0.45 698 0.51 741 0.58 646 0.49 694 0.57 737 0.62 778 0.69 External Static Pressure (Pascals) 125 150 175 200 225 RPM kW RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Drive 695 0.37 740 0.43 783 0.48 824 0.54 864 0.61 725 0.45 768 0.51 809 0.57 848 0.63 886 0.70 755 0.55 798 0.61 838 0.67 876 0.74 912 0.81 786 0.65 828 0.72 868 0.79 905 0.86 939 0.93 818 0.77 859 0.85 898 0.93 936 1.00 970 1.08 250 RPM kW 901 923 947 973 1003 1.12 Nom kW Standard Motor & Hi Static Drive CFM 3260 3670 4080 4490 4890 0.67 0.77 0.88 1.01 1.16 ← 3260 3670 4080 4490 4890 50 External Static Pressure (Pascals) 275 300 325 350 375 RPM kW RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Std Motor 1.12 Nom kW Standard Motor & Drive & Hi Static Drive 937 0.73 970 0.79 1004 0.85 1036 0.91 1067 0.97 957 0.83 992 0.90 1024 0.97 1057 1.04 1086 1.11 981 0.95 1014 1.02 1046 1.10 1077 1.18 1108 1.25 1007 1.08 1038 1.16 1070 1.24 1100 1.32 1130 1.40 1034 1.24 1066 1.32 1095 1.40 1124 1.48 1154 1.57 1.50 Nom kW Over-Sized Motor & High Static Drive Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 Table PD-10a - Belt Drive Evaporator Fan Performance - YSC072AD*L - Low Heat - Downflow Configuration - (IP) CFM External Static Pressure (Inches of Water) .40 .50 .60 .70 .80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Drive 646 0.43 695 0.50 740 0.57 783 0.65 824 0.73 677 0.53 725 0.61 768 0.68 809 0.76 848 0.85 707 0.64 755 0.73 798 0.82 838 0.90 876 0.99 741 0.77 786 0.87 828 0.97 868 1.06 905 1.16 778 0.93 818 1.03 859 1.13 898 1.24 936 1.35 .90 RPM BHP 1.00 RPM BHP 864 886 912 939 970 901 923 947 973 1003 0.81 0.94 1.08 1.25 1.45 1-1/2 HP Standard Motor & Hi Static Drive CFM 1920 2160 2400 2640 2880 External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Std Mtr 1-1/2 HP Standard Motor & & Drive Hi Static Drive 937 0.98 970 1.05 1004 1.13 1036 1.22 1067 1.30 957 1.12 992 1.21 1024 1.30 1057 1.40 1086 1.48 981 1.27 1014 1.37 1046 1.48 1077 1.58 1108 1.68 1007 1.45 1038 1.56 1070 1.66 1100 1.77 1130 1.88 1034 1.66 1066 1.77 1095 1.87 1124 1.99 1154 2.11 2 HP Over-Sized Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 RT-PRC017-EN 0.89 1.03 1.18 1.35 1.55 ← 1920 2160 2400 2640 2880 .10 .20 .30 RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Low Static Drive 532 0.29 592 0.36 570 0.37 624 0.45 556 0.41 610 0.48 659 0.56 601 0.52 652 0.61 698 0.69 646 0.66 694 0.76 737 0.84 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 23 Performance Data Table PD-11 - Belt Drive Evaporator Fan Performance - YSC072AD*L - Horizontal Configuration (SI) 25 50 m3/h RPM 3260 3670 4080 4490 4890 584 640 696 752 CFM 275 RPM kW 3260 3670 4080 4490 4890 990 1012 1038 1067 1103 75 100 RPM kW kW RPM kW RPM kW 1.12 Nom kW Std Mtr & Low Static Drive 586 0.25 645 0.31 695 0.35 0.28 629 0.33 685 0.38 735 0.45 0.38 679 0.43 726 0.48 775 0.55 0.49 732 0.54 770 0.60 816 0.66 0.62 786 0.68 818 0.74 858 0.81 1.12 Nom kW Standard Motor & Drive External Static Pressure (Pascals) 125 150 175 200 RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Drive 741 779 819 860 900 0.41 0.50 0.62 0.74 0.88 785 820 858 899 940 0.47 0.56 0.68 0.82 0.97 225 RPM kW 250 RPM kW 828 0.53 870 0.59 913 0.66 952 860 0.63 898 0.70 937 0.77 976 896 0.74 932 0.81 967 0.89 1002 935 0.88 970 0.95 1004 1.03 1036 977 1.05 1010 1.13 1042 1.20 1072 1.12 Nom kW Standard Motor & Hi Static Drive 0.72 0.84 0.97 1.11 1.27 External Static Pressure (Pascals) 300 325 350 375 RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Hi Static Drive 0.78 1027 0.85 1063 0.92 1096 0.99 1129 1.06 0.90 1048 0.98 1082 1.05 1117 1.12 1149 1.20 1.04 1072 1.12 1106 1.20 1139 1.27 1169 1.35 1.19 1100 1.28 1132 1.36 1164 1.45 1194 1.53 1.36 1134 1.45 1163 1.54 1191 1.63 1221 1.72 1.50 Nom kW Over-Sized Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-11a - Belt Drive Evaporator Fan Performance - YSC072AD*L - Horizontal Configuration - (IP) CFM 1920 2160 2400 2640 2880 External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Standard Motor & Drive 586 0.33 645 0.41 695 0.48 741 0.55 785 0.63 828 0.71 870 0.79 913 0.88 584 0.38 629 0.44 685 0.52 735 0.60 779 0.67 820 0.75 860 0.84 898 0.94 937 1.03 640 0.50 679 0.57 726 0.64 775 0.74 819 0.83 858 0.91 896 0.99 932 1.09 967 1.19 696 0.65 732 0.73 770 0.80 816 0.89 860 1.00 899 1.10 935 1.19 970 1.28 1004 1.38 752 0.83 786 0.92 818 0.99 858 1.08 900 1.18 940 1.30 977 1.41 1010 1.51 1042 1.60 1-1/2 HP Standard Motor & Drive 1-1/2 HP Std Motor & Hi Static Drive CFM 1.10 RPM BHP 1920 2160 2400 2640 2880 990 1012 1038 1067 1103 1.05 1.21 1.40 1.60 1.82 External Static Pressure (Inches of Water) 1.20 1.30 1.40 RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Hi Static Drive 1027 1.14 1063 1.24 1096 1.33 1048 1.31 1082 1.40 1117 1.50 1072 1.50 1106 1.60 1139 1.71 1100 1.71 1132 1.83 1164 1.94 1134 1.94 1163 2.07 1191 2.19 2 HP Over-Sized Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 24 1.00 RPM BHP 952 976 1002 1036 1072 0.96 1.12 1.29 1.49 1.70 1.50 RPM BHP 1129 1149 1169 1194 1221 1.42 1.61 1.81 2.05 2.31 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-12 - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Downflow Configuration - (SI) 25 50 m3/h RPM kW RPM 3260 3670 4080 4490 4890 577 630 684 738 0.29 0.38 0.49 0.63 586 631 678 728 779 External Static Pressure (Pascals) 100 125 150 kW RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Low Static Drive 0.26 641 0.31 690 0.37 735 0.42 779 0.48 0.34 684 0.40 731 0.46 773 0.52 814 0.58 0.44 727 0.50 773 0.57 814 0.64 853 0.70 0.56 772 0.63 815 0.70 857 0.77 894 0.84 0.69 818 0.77 860 0.85 899 0.93 936 1.01 75 175 200 225 250 RPM kW RPM kW RPM kW RPM kW 1.12Nom kW Standard Motor & Drive 820 0.54 859 0.60 896 0.66 932 0.72 854 0.64 891 0.71 928 0.78 963 0.84 890 0.77 926 0.84 961 0.91 994 0.98 929 0.91 963 0.98 996 1.06 1028 1.14 970 1.08 1003 1.16 1035 1.24 1066 1.32 ← 1.50 Nom kW Over-Sized Motor & High Static Drive CFM 3260 3670 4080 4490 4890 External Static Pressure (Pascals) 275 300 325 350 375 RPM kW RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Std Motor 1.12 Nom kW Std Mtr & Drive & Hi Static Drive 968 0.78 1000 0.84 1033 0.90 1063 0.96 1094 1.03 996 0.91 1028 0.98 1061 1.05 1091 1.12 1121 1.18 1027 1.05 1058 1.13 1090 1.21 1118 1.28 1149 1.36 1060 1.22 1090 1.29 1120 1.38 1150 1.46 1178 1.54 1096 1.40 1125 1.48 1155 1.57 1181 1.66 1210 1.75 1.50 Nom kW Over-Sized Motor & High Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-12a - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Downflow Configuration - (IP) CFM External Static Pressure (Inches of Water) .40 .50 .60 .70 .80 .90 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Drive 690 0.49 735 0.56 779 0.64 820 0.72 859 0.80 896 0.88 731 0.62 773 0.69 814 0.78 854 0.86 891 0.95 928 1.04 773 0.77 814 0.85 853 0.94 890 1.03 926 1.12 961 1.22 815 0.94 857 1.04 894 1.13 929 1.22 963 1.32 996 1.42 860 1.14 899 1.24 936 1.35 970 1.45 1003 1.56 1035 1.66 1.00 RPM BHP 932 0.96 963 1.13 994 1.31 1028 1.52 1066 1.77 ← 1920 2160 2400 2640 2880 .10 .20 .30 RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Low Static Drive 586 0.35 641 0.42 577 0.38 631 0.46 684 0.54 630 0.51 678 0.59 727 0.68 684 0.66 728 0.75 772 0.84 738 0.84 779 0.93 818 1.03 2 HP Over-Sized Motor & Hi Static Drive CFM 1920 2160 2400 2640 2880 External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Std Mtr 1-1/2 HP Std Motor & & Drive Hi Static Drive 968 1.05 1000 1.13 1033 1.21 1063 1.29 1094 1.38 996 1.22 1028 1.31 1061 1.41 1091 1.50 1121 1.59 1027 1.41 1058 1.51 1090 1.62 1118 1.72 1149 1.82 1060 1.63 1090 1.74 1120 1.85 1150 1.96 1178 2.07 1096 1.88 1125 1.99 1155 2.11 1181 2.22 1210 2.34 2 HP Over-Sized Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 RT-PRC017-EN Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 25 Performance Data Table PD-13 - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Horizontal Configuration (SI) 25 50 RPM 3260 3670 4080 4490 4890 579 636 696 757 818 CFM 275 RPM kW 3260 3670 4080 4490 4890 1023 1053 1085 1122 1163 External Static Pressure (Pascals) 125 150 175 200 225 250 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Drive 780 0.46 824 0.52 866 0.59 907 0.65 947 0.71 986 0.78 826 0.57 865 0.64 903 0.71 943 0.78 979 0.84 1017 0.91 874 0.70 911 0.77 947 0.84 982 0.92 1017 1.00 1051 1.07 924 0.86 959 0.93 993 1.00 1026 1.08 1058 1.17 1089 1.25 977 1.05 1010 1.13 1042 1.20 1073 1.27 1104 1.36 1133 1.45 1.50 Nom kW Over-Sized Motor & High Static Drive ← 100 kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Low Static Drive 0.24 639 0.30 690 0.35 736 0.40 0.33 692 0.39 741 0.46 784 0.51 0.45 746 0.51 794 0.58 836 0.64 0.58 802 0.64 847 0.72 888 0.80 0.74 858 0.81 900 0.88 940 0.97 1.12 Nom kW Standard Motor & Drive m3/h 75 External Static Pressure (Pascals) 300 325 350 375 RPM kW RPM kW RPM kW RPM kW 1.12 Nom kW Standard Motor & Hi Static Drive 0.84 1059 0.92 1093 0.98 1126 1.06 1156 1.12 0.98 1087 1.06 1121 1.13 1153 1.21 1185 1.29 1.15 1119 1.23 1151 1.30 1182 1.38 1214 1.47 1.34 1153 1.42 1184 1.50 1215 1.59 1.54 1192 1.64 1221 1.72 1.50 Nom kW Over-Sized Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 1.12 Nom kW Std Mtr & Hi Static Drive Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-13a - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Horizontal Configuration - (IP) CFM 1.10 RPM BHP 1920 2160 2400 2640 2880 1023 1053 1085 1122 1163 CFM 1.13 1.32 1.54 1.79 2.07 External Static Pressure (Inches of Water) .20 .30 .40 .50 .60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP HP Standard Motor & Low Static Drive 639 0.40 690 0.47 736 0.54 780 0.62 824 0.70 692 0.53 741 0.61 784 0.68 826 0.76 865 0.85 746 0.68 794 0.78 836 0.86 874 0.94 911 1.03 802 0.86 847 0.96 888 1.07 924 1.16 959 1.25 858 1.08 900 1.18 940 1.30 977 1.41 1010 1.51 1-1/2 HP Standard Motor & Drive External Static Pressure (Inches of Water) 1.20 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Hi Static Drive 1059 1.23 1093 1.32 1126 1.42 1156 1.51 1087 1.42 1121 1.52 1153 1.62 1185 1.72 1119 1.65 1151 1.75 1182 1.85 1214 1.96 1153 1.90 1184 2.01 1215 2.13 1192 2.19 1221 2.31 2 HP Over-Sized Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 26 .70 .80 .90 1.00 RPM BHP RPM BHP RPM BHP RPM BHP 1-1/2 HP Standard Motor & Drive 866 0.79 907 0.87 947 0.95 986 1.04 903 0.95 943 1.04 979 1.13 1017 1.23 947 1.13 982 1.23 1017 1.34 1051 1.44 993 1.35 1026 1.45 1058 1.56 1089 1.68 1042 1.61 1073 1.71 1104 1.82 1133 1.94 2 HP Over-Sized Motor & Hi Static Drive ← 1920 2160 2400 2640 2880 .10 RPM BHP 1-1/2 579 0.33 636 0.45 696 0.60 757 0.78 818 1.00 1-1/2 HP Std Motor & Hi Static Drive Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-14 - Belt Drive Evaporator Fan Performance - YSC090AD*L - Low Heat - Downflow Configuration - (SI) 25 50 RPM kW RPM 4080 4590 5100 5610 6120 693 753 814 0.59 0.77 0.97 682 738 795 853 CFM ← 4080 4590 5100 5610 6120 External Static Pressure (Pascals) 275 300 325 350 RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 996 0.98 1028 1.06 1061 1.14 1092 1.21 1031 1.16 1062 1.24 1093 1.32 1123 1.41 1070 1.38 1099 1.46 1128 1.54 1158 1.63 1110 1.62 1139 1.71 1167 1.80 1195 1.89 1151 1.90 1181 2.00 1208 2.10 1236 2.20 2.24 Nom kW Over-Sized Motor & Hi Static Drive 175 200 225 RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 854 0.70 891 0.77 928 0.84 895 0.86 931 0.94 965 1.01 936 1.05 972 1.13 1006 1.21 978 1.26 1014 1.35 1048 1.44 1023 1.50 1057 1.60 1088 1.70 250 RPM kW 963 998 1038 1080 1121 0.91 1.08 1.29 1.53 1.80 ← m3/h External Static Pressure (Pascals) 100 125 150 kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Low Static Drive 676 0.44 726 0.50 773 0.57 815 0.64 0.50 727 0.57 770 0.64 814 0.71 856 0.79 0.66 780 0.73 819 0.80 858 0.88 898 0.96 0.85 834 0.92 871 1.00 906 1.08 942 1.17 1.07 890 1.15 925 1.23 958 1.31 991 1.40 75 2.24 Nom kW Over-Sized Motor & Hi Static Drive 375 RPM kW 1122 1153 1185 1222 1261 1.29 1.49 1.72 1.98 2.29 ← 1.50 Nom kW Standard Motor & Hi Static Drive Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 1.50 Nom kW Standard Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 Table PD-14a - Belt Drive Evaporator Fan Performance - YSC090AD*L - Low Heat - Downflow Configuration - (IP) CFM .10 RPM BHP 2400 2700 3000 3300 3600 693 753 814 0.79 1.03 1.31 External Static Pressure (Inches of Water) .20 .30 .40 .50 .60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Low Static Drive 676 0.59 726 0.67 773 0.77 815 0.85 682 0.68 727 0.76 770 0.85 814 0.95 856 1.06 738 0.89 780 0.97 819 1.07 858 1.18 898 1.29 795 1.14 834 1.23 871 1.33 906 1.45 942 1.56 853 1.44 890 1.55 925 1.65 958 1.76 991 1.88 .70 .80 .90 RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 854 0.94 891 1.03 928 1.12 895 1.16 931 1.25 965 1.35 936 1.40 972 1.52 1006 1.63 978 1.69 1014 1.81 1048 1.94 1023 2.01 1057 2.14 1088 2.28 1.00 RPM BHP 963 1.22 998 1.45 1038 1.73 1080 2.06 1121 2.41 ← 3 HP Over-Sized Motor & Drive External Static Pressure (Inches of Water) 1.20 1.30 1.40 CFM RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 2400 996 1.32 1028 1.42 1061 1.52 1092 1.63 2700 1031 1.56 1062 1.66 1093 1.78 1123 1.89 3000 1070 1.85 1099 1.95 1128 2.07 1158 2.19 3300 1110 2.18 1139 2.29 1167 2.42 1195 2.54 3600 1151 2.55 1181 2.68 1208 2.81 1236 2.95 3 HP Over-Sized Mtr & Hi Static Drive 2 HP Standard Motor & Hi Static Drive 1.10 RPM BHP ← Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 RT-PRC017-EN 1.50 RPM BHP 1122 1153 1185 1222 1261 1.73 2.00 2.31 2.66 3.07 Standard Motor & ← 2HiHP Static Drive Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 27 Performance Data Table PD-15 - Belt Drive Evaporator Fan Performance - YSC090AD*L - Horizontal Configuration (SI) 25 RPM 4080 4590 5100 5610 6120 725 798 872 946 CFM 4080 4590 5100 5610 6120 75 100 kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Low Static Drive 694 0.44 745 0.50 793 0.58 0.54 760 0.60 801 0.66 847 0.73 0.73 830 0.79 862 0.86 902 0.93 0.96 901 1.03 929 1.10 961 1.17 1.23 973 1.31 1000 1.38 1025 1.45 External Static Pressure (Pascals) 125 150 RPM kW RPM kW 835 889 943 998 1057 0.64 0.82 1.01 1.25 1.54 874 927 981 1036 1091 0.70 0.89 1.10 1.34 1.62 175 200 225 RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 911 0.77 948 0.85 982 0.92 963 0.96 997 1.03 1030 1.11 1017 1.19 1050 1.27 1081 1.34 1071 1.44 1104 1.54 1135 1.63 1125 1.72 1158 1.83 1189 1.95 2.24 Nom kW Over-Sized Motor & Hi Static Drive 1017 1.00 1061 1.19 1111 1.42 1164 1.71 1219 2.05 1.50 Nom kW Std Mtr & Hi Static Drive External Static Pressure (Pascals) 275 300 325 350 375 RPM kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Std Mtr & Drive 1.50 Nom kW Std Mtr & Hi Static Drive 1053 1.08 1087 1.15 1121 1.23 1153 1.31 1185 1.39 1093 1.28 1124 1.37 1156 1.45 1187 1.54 1218 1.63 1141 1.51 1170 1.60 1198 1.70 1227 1.80 1255 1.89 1192 1.79 1220 1.88 1247 1.98 1272 2.07 1299 2.18 1246 2.14 1272 2.23 1298 2.32 1323 2.41 1348 2.52 2.24 Nom kW Over-Sized Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 250 RPM kW ← m3/h 50 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-15a - Belt Drive Evaporator Fan Performance - YSC090AD*L - Horizontal Configuration - (IP) 2400 2700 3000 3300 3600 725 798 872 946 CFM 2400 2700 3000 3300 3600 0.73 0.98 1.28 1.65 External Static Pressure (Inches of Water) .20 .30 .40 .50 .60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Std Motor & Low Static Drive 694 0.59 745 0.67 793 0.77 835 0.86 874 0.94 760 0.80 801 0.88 847 0.98 889 1.09 927 1.19 830 1.06 862 1.15 902 1.24 943 1.35 981 1.48 901 1.38 929 1.47 961 1.56 998 1.67 1036 1.80 973 1.75 1000 1.85 1025 1.95 1057 2.06 1091 2.17 External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 2 HP Standard Motor & Hi Static Drive 1053 1.44 1087 1.55 1121 1.65 1153 1.76 1185 1.86 1093 1.71 1124 1.83 1156 1.95 1187 2.06 1218 2.18 1141 2.02 1170 2.15 1198 2.28 1227 2.41 1255 2.54 1192 2.41 1220 2.52 1247 2.65 1272 2.78 1299 2.92 1246 2.87 1272 2.99 1298 3.11 1323 3.24 1348 3.37 3 HP Over-Sized Motor & High Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 28 .70 .80 .90 RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 911 1.03 948 1.13 982 1.23 963 1.28 997 1.38 1030 1.48 1017 1.60 1050 1.70 1081 1.80 1071 1.93 1104 2.07 1135 2.19 1125 2.31 1158 2.46 1189 2.61 3 HP Over-Sized Motor & Hi Static Drive 1.00 RPM BHP 1017 1.34 1061 1.60 1111 1.90 1164 2.30 1219 2.75 ← CFM .10 RPM BHP 2 HP Std Mtr & Hi Static Drive Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-16 - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Downflow Configuration - (SI) 25 External Static Pressure (Pascals) 100 125 150 RPM kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Low Static Drive 697 0.46 745 0.53 790 0.60 830 0.66 869 0.73 760 0.62 804 0.69 847 0.77 887 0.85 922 0.92 826 0.81 865 0.89 905 0.98 943 1.06 979 1.15 894 1.05 929 1.13 965 1.22 1001 1.32 1036 1.41 963 1.33 995 1.42 1028 1.51 1061 1.61 1093 1.71 50 m3/h RPM kW 4080 4590 5100 5610 6120 717 787 858 930 0.55 0.74 0.97 1.24 75 175 200 225 RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 906 0.80 941 0.87 976 0.94 958 0.99 991 1.07 1024 1.14 1012 1.23 1044 1.31 1075 1.39 1068 1.50 1099 1.59 1129 1.68 1126 1.82 1157 1.92 1185 2.02 250 RPM kW 1009 1055 1105 1157 1212 1.01 1.22 1.47 1.77 2.11 ← CFM 4080 4590 5100 5610 6120 2.24 Nom kW Over-Sized Motor & Hi Static Drive External Static Pressure (Pascals) 275 300 325 350 375 RPM kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Std Mtr & Drive 1.50 Nom kW Std Motor & Hi Static Drive 1042 1.09 1073 1.17 1104 1.24 1134 1.32 1163 1.40 1086 1.30 1117 1.39 1146 1.47 1174 1.56 1203 1.65 1134 1.56 1163 1.65 1191 1.74 1218 1.83 1245 1.92 1185 1.86 1212 1.95 1238 2.04 1265 2.14 1292 2.24 1239 2.21 1265 2.31 1290 2.40 1316 2.51 1340 2.61 2.24 Nom kW Over-Sized Motor & Hi Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-16a - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Downflow Configuration - (IP) CFM .10 RPM BHP 2400 2700 3000 3300 3600 717 787 858 930 CFM 2400 2700 3000 3300 3600 0.74 0.99 1.30 1.66 External Static Pressure (Inches of Water) .20 .30 .40 .50 .60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Low Static Drive 697 0.62 745 0.71 790 0.80 830 0.89 869 0.98 760 0.83 804 0.93 847 1.03 887 1.13 922 1.23 826 1.09 865 1.20 905 1.31 943 1.42 979 1.54 894 1.41 929 1.52 965 1.64 1001 1.77 1036 1.89 963 1.78 995 1.90 1028 2.03 1061 2.16 1093 2.30 .70 .80 .90 RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 906 1.07 941 1.16 976 1.26 958 1.33 991 1.43 1024 1.53 1012 1.64 1044 1.76 1075 1.87 1068 2.01 1099 2.13 1129 2.25 1126 2.43 1157 2.57 1185 2.70 3 HP Over-Sized Motor & Drive 1.00 RPM BHP 1009 1055 1105 1157 1212 1.36 1.64 1.98 2.37 2.83 External Static Pressure (Inches of Water) 1.20 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & 2 HP Standard Motor & Drive Hi Static Drive 1042 1.46 1073 1.56 1104 1.67 1134 1.77 1163 1.87 1086 1.75 1117 1.86 1146 1.97 1174 2.09 1203 2.21 1134 2.09 1163 2.21 1191 2.33 1218 2.45 1245 2.58 1185 2.49 1212 2.61 1238 2.74 1265 2.87 1292 3.01 1239 2.96 1265 3.09 1290 3.22 1316 3.36 1340 3.49 3 HP Over-Sized Mtr & Hi Static Drive 1.10 RPM BHP Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 RT-PRC017-EN Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 29 Performance Data Table PD-17 - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Horizontal Configuration (SI) 25 m3/h 4080 4590 5100 5610 6120 kW 0.61 0.80 1.03 1.30 1.64 External Static Pressure (Pascals) 100 125 150 RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 851 919 989 1058 1130 0.67 0.88 1.12 1.40 1.74 889 955 1023 1092 1162 175 RPM kW 0.73 926 0.80 962 0.94 989 1.01 1022 1.21 1056 1.28 1086 1.51 1124 1.60 1154 1.85 1193 1.96 1222 2.24 Nom kW Over-Sized Motor & Hi Static Drive 0.88 1.09 1.36 1.68 2.06 200 RPM kW 225 RPM kW 250 RPM kW 997 1054 1116 1182 1250 1031 1.03 1086 1.26 1146 1.52 1210 1.85 1276 2.25 1067 1.11 1117 1.35 1175 1.62 1237 1.94 1302 2.34 0.95 1.17 1.43 1.77 2.16 ← CFM RPM kW RPM kW RPM 1.50 Nom kW Standard Motor & Low Static Drive 713 0.46 764 0.53 811 790 0.64 837 0.71 880 869 0.87 910 0.94 950 949 1.14 985 1.22 1023 1029 1.47 1061 1.55 1096 75 ← 4080 4590 5100 5610 6120 50 1.50 Nom kW Std Mtr & Hi Static Drive External Static Pressure (Pascals) 275 300 325 350 375 RPM kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Std Mtr 1.50 Nom kW Standard Motor & Drive & Hi Static Drive 1101 1.19 1134 1.26 1166 1.34 1197 1.42 1229 1.50 1148 1.43 1180 1.52 1210 1.60 1241 1.69 1269 1.78 1204 1.72 1232 1.81 1260 1.91 1287 2.00 1316 2.10 1264 2.04 1290 2.14 1316 2.25 1342 2.36 1367 2.46 1327 2.43 1352 2.53 1376 2.64 1401 2.75 1425 2.87 2.24 Nom kW Over-Sized Motor & Hi Static Drive Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 Table PD-17a - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Horizontal Configuration - (IP) CFM .90 RPM BHP 1.00 RPM BHP 1031 1.38 1086 1.69 1146 2.04 1210 2.48 1276 3.01 1067 1.48 1117 1.80 1175 2.17 1237 2.60 1302 3.13 ← External Static Pressure (Inches of Water) .40 .50 .60 .70 .80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 851 0.89 889 0.97 926 1.07 962 1.17 997 1.28 919 1.17 955 1.26 989 1.36 1022 1.46 1054 1.57 989 1.50 1023 1.62 1056 1.72 1086 1.82 1116 1.92 1058 1.88 1092 2.02 1124 2.15 1154 2.26 1182 2.37 1130 2.33 1162 2.48 1193 2.63 1222 2.77 1250 2.89 3 HP Over-Sized Motor & Hi Static Drive ← 2400 2700 3000 3300 3600 .10 .20 .30 RPM BHP RPM BHP RPM BHP 2 HP Std Motor & Low Static Drive 713 0.62 764 0.71 811 0.81 790 0.86 837 0.96 880 1.07 869 1.16 910 1.26 950 1.38 949 1.53 985 1.63 1023 1.75 1029 1.97 1061 2.07 1096 2.19 2 HP Std Mtr & Hi Static Drive CFM 2400 2700 3000 3300 3600 External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Std Mtr & Drive 2 HP Standard Motor & Hi Static Drive 1101 1.59 1134 1.69 1166 1.80 1197 1.90 1229 2.02 1148 1.92 1180 2.04 1210 2.15 1241 2.27 1269 2.39 1204 2.30 1232 2.43 1260 2.56 1287 2.69 1316 2.82 1264 2.74 1290 2.87 1316 3.02 1342 3.16 1367 3.30 1327 3.26 1352 3.39 1376 3.54 1401 3.69 1425 3.85 3 HP Over-Sized Motor & High Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 30 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-18 - Belt Drive Evaporator Fan Performance - YSC102AD*L - Low Heat - Downflow Configuration - (SI) 25 50 m3/h RPM kW RPM 4620 5200 5780 6350 6930 628 684 740 0.54 0.70 0.89 617 667 719 772 External Static Pressure (Pascals) 100 125 150 kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Low Static Drive 610 0.44 651 0.53 691 0.62 729 0.70 0.49 656 0.56 693 0.65 731 0.75 766 0.84 0.63 704 0.71 739 0.80 772 0.90 806 1.00 0.79 754 0.89 787 0.98 817 1.08 848 1.19 0.99 805 1.09 836 1.20 865 1.30 893 1.41 75 175 RPM kW 766 800 838 879 921 0.80 0.94 1.11 1.31 1.53 200 225 250 RPM kW RPM kW RPM kW 1.50 Nom kW Std Mtr & Drive 799 0.89 831 0.99 861 1.10 834 1.04 865 1.15 895 1.25 870 1.22 900 1.33 931 1.45 908 1.43 937 1.54 966 1.66 949 1.65 977 1.78 1004 1.92 ← 2.24 Nom kW Over-Sized Motor & High Static Drive m3/h 275 RPM kW 4620 5200 5780 6350 6930 890 924 959 993 1030 1.21 1.37 1.56 1.79 2.04 External Static Pressure (Pascals) 300 325 350 375 400 425 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 917 1.31 944 1.43 970 1.54 996 1.66 1022 1.77 1048 1.89 951 1.48 978 1.61 1003 1.73 1027 1.85 1051 1.98 1075 2.11 986 1.68 1012 1.80 1037 1.93 1061 2.06 1084 2.19 1108 2.33 1020 1.91 1046 2.04 1071 2.17 1096 2.30 1119 2.44 1141 2.58 1056 2.18 1082 2.31 1106 2.44 1131 2.58 1154 2.72 1176 2.86 2.24 Nom kW Over-Sized Motor & High Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 450 RPM kW 475 RPM kW 500 RPM kW 1071 1098 1130 1163 1199 1096 1122 1153 1185 1220 1118 2.25 1144 2.49 1174 2.75 1207 3.02 1241 3.31 2.01 2.23 2.46 2.72 3.01 2.13 2.36 2.61 2.87 3.16 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-18a - Belt Drive Evaporator Fan Performance - YSC102AD*L - Low Heat - Downflow Configuration - (IP) CFM .10 RPM BHP .20 RPM BHP 2720 3060 3400 3740 4080 628 684 740 617 667 719 772 0.72 0.94 1.20 0.65 0.84 1.06 1.32 External Static Pressure (Inches of Water) .30 .40 .50 .60 RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Low Static Drive 610 0.59 651 0.71 691 0.83 729 0.94 656 0.76 693 0.87 731 1.00 766 1.13 704 0.96 739 1.07 772 1.20 806 1.35 754 1.19 787 1.32 817 1.45 848 1.59 805 1.47 836 1.61 865 1.74 893 1.89 .70 RPM BHP 766 800 838 879 921 1.07 1.26 1.49 1.75 2.05 .80 .90 1.00 RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 799 1.19 831 1.33 861 1.47 834 1.40 865 1.54 895 1.68 870 1.64 900 1.79 931 1.94 908 1.91 937 2.07 966 2.23 949 2.21 977 2.39 1004 2.57 ← 3 HP Over-Sized Motor & Drive CFM 1.10 RPM BHP 2720 3060 3400 3740 4080 890 924 959 993 1030 1.62 1.84 2.09 2.39 2.74 External Static Pressure (Inches of Water) 1.20 1.30 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 917 1.76 944 1.91 970 2.07 996 2.22 1022 2.38 1048 2.54 951 1.99 978 2.15 1003 2.32 1027 2.48 1051 2.65 1075 2.82 986 2.25 1012 2.42 1037 2.59 1061 2.77 1084 2.94 1108 3.13 1020 2.56 1046 2.73 1071 2.90 1096 3.08 1119 3.27 1141 3.45 1056 2.92 1082 3.10 1106 3.28 1131 3.46 1154 3.65 1176 3.83 3 HP Over-Sized Motor & Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 RT-PRC017-EN 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 1071 1098 1130 1163 1199 1096 1122 1153 1185 1220 1118 3.02 1144 3.34 1174 3.68 1207 4.04 1241 4.44 2.69 2.99 3.31 3.64 4.03 2.86 3.17 3.50 3.84 4.23 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 31 Performance Data Table PD-19 - Belt Drive Evaporator Fan Performance - YSC102AD*L - Horizontal Configuration (SI) 25 m3/h 4620 5200 5780 6350 6930 m3/h 4620 5200 5780 6350 6930 50 75 100 RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Low Static Drive 610 0.44 657 0.52 700 0.60 747 0.70 675 0.61 718 0.70 757 0.78 794 0.87 742 0.82 779 0.91 817 1.01 851 1.10 810 1.07 842 1.16 878 1.27 911 1.38 878 1.37 907 1.47 939 1.58 971 1.70 275 300 325 RPM kW RPM kW RPM kW 1.50 Nom kW Std Mtr & Drive 989 1.36 1015 1.45 1038 1.53 1042 1.64 1067 1.74 1092 1.84 1093 1.97 1118 2.08 1144 2.19 1140 2.31 1169 2.45 1195 2.58 1182 2.66 1213 2.83 1241 2.98 Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 350 RPM kW External Static Pressure (Pascals) 125 150 175 200 225 RPM kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 793 0.80 837 0.91 873 1.00 905 1.09 935 1.18 837 0.98 879 1.10 919 1.22 955 1.34 987 1.44 885 1.21 923 1.33 962 1.46 999 1.59 1033 1.72 941 1.49 972 1.60 1006 1.73 1041 1.87 1076 2.02 1000 1.82 1029 1.94 1056 2.06 1087 2.20 1120 2.35 2.24 Nom kW Over-Sized Motor & High Static Drive External Static Pressure (Pascals) 375 400 RPM kW RPM kW 425 RPM kW 1062 1.62 1085 1.71 1108 1.80 1129 1115 1.94 1138 2.04 1159 2.14 1180 1167 2.30 1190 2.41 1212 2.52 1233 1219 2.70 1242 2.83 1264 2.95 1286 1268 3.14 1292 3.28 2.24 Nom kW Over-Sized Motor & High Static Drive 1.88 2.23 2.63 3.07 - 250 RPM kW 963 1014 1066 1109 1151 1.27 1.54 1.85 2.17 2.50 450 RPM kW 475 RPM kW 500 RPM kW 1152 1200 1253 1307 - 1172 1221 1273 1326 - 1194 1241 1292 - 1.98 2.33 2.74 3.19 - 2.06 2.43 2.85 3.31 - 2.16 2.53 2.96 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-19a - Belt Drive Evaporator Fan Performance - YSC102AD*L - Horizontal Configuration - (IP) CFM 2720 3060 3400 3740 4080 CFM 2720 3060 3400 3740 4080 External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Low Static Drive 610 0.59 657 0.70 700 0.81 747 0.93 793 1.08 837 1.22 675 0.82 718 0.93 757 1.05 794 1.17 837 1.32 879 1.48 742 1.09 779 1.21 817 1.35 851 1.48 885 1.62 923 1.78 810 1.44 842 1.56 878 1.70 911 1.85 941 1.99 972 2.14 878 1.84 907 1.97 939 2.12 971 2.28 1000 2.44 1029 2.60 1.10 1.20 RPM BHP RPM BHP 2 HP Standard Motor & Drive 989 1.82 1015 1.94 1042 2.20 1067 2.34 1093 2.64 1118 2.78 1140 3.10 1169 3.28 1182 3.57 1213 3.79 1.30 RPM BHP 1038 1092 1144 1195 1241 2.05 2.47 2.94 3.46 4.00 Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 32 1.70 1.80 1.90 RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 873 1.35 905 1.47 935 1.58 919 1.64 955 1.79 987 1.94 962 1.96 999 2.13 1033 2.31 1006 2.32 1041 2.51 1076 2.71 1056 2.76 1087 2.95 1120 3.16 3 HP Over-Sized Motor & Drive External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 1.80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Over-Sized Motor & Drive 1062 2.17 1085 2.29 1108 2.41 1129 2.53 1152 2.65 1115 2.60 1138 2.74 1159 2.87 1180 3.00 1200 3.13 1167 3.08 1190 3.23 1212 3.38 1233 3.53 1253 3.67 1219 3.63 1242 3.79 1264 3.96 1286 4.12 1307 4.28 1268 4.21 1292 4.40 3 HP Over-Sized Motor & Drive 2.00 RPM BHP 963 1.70 1014 2.07 1066 2.48 1109 2.90 1151 3.36 1.90 RPM BHP 2.00 RPM BHP 1172 1221 1273 1326 - 1194 1241 1292 - 2.77 3.26 3.82 4.44 - 2.89 3.40 3.97 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-20 - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Downflow Configuration - (SI) 25 m3/h RPM kW 4620 5200 5780 6350 6930 667 726 786 0.62 0.81 1.03 75 175 200 225 RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 787 0.85 819 0.96 850 1.06 827 1.02 859 1.13 890 1.23 869 1.22 900 1.33 929 1.44 914 1.45 943 1.57 971 1.69 961 1.71 988 1.84 1015 1.97 ← External Static Pressure (Pascals) 100 125 150 RPM kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Low Static Drive 636 0.50 676 0.58 716 0.67 752 0.76 648 0.55 686 0.63 723 0.73 759 0.82 794 0.92 704 0.71 738 0.80 772 0.90 805 1.00 837 1.11 761 0.91 792 1.00 823 1.10 854 1.21 884 1.33 818 1.14 848 1.24 877 1.34 905 1.46 933 1.58 50 250 RPM kW 879 918 959 999 1041 1.17 1.34 1.56 1.81 2.10 2.24 Nom kW Over-Sized Motor & High Static Drive m3/h 4620 5200 5780 6350 6930 External Static Pressure (Pascals) 275 300 325 350 375 400 425 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 907 1.27 934 1.39 960 1.50 987 1.62 1013 1.73 1038 1.85 1064 1.97 946 1.46 971 1.58 997 1.70 1023 1.83 1047 1.95 1070 2.08 1094 2.21 986 1.68 1011 1.80 1037 1.93 1061 2.06 1085 2.19 1107 2.33 1130 2.46 1025 1.94 1051 2.06 1077 2.19 1100 2.32 1123 2.46 1147 2.61 1168 2.75 1067 2.23 1092 2.36 1117 2.50 1140 2.64 1164 2.78 1187 2.92 1208 3.07 2.24 Nom kW Over-Sized Motor & High Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 450 RPM kW 475 RPM kW 500 RPM kW 1087 1117 1151 1189 1229 1111 2.21 1140 2.47 1174 2.75 1211 3.04 - 1134 2.34 1163 2.60 1194 2.88 1231 3.19 - 2.09 2.34 2.60 2.89 3.22 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-20a - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Downflow Configuration - (IP) CFM 1.10 RPM BHP 2720 3060 3400 3740 4080 667 726 786 0.84 1.09 1.38 External Static Pressure (Inches of Water) 1.20 1.30 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Low Static Drive 636 0.66 676 0.78 716 0.90 752 1.02 648 0.73 686 0.85 723 0.97 759 1.10 794 1.24 704 0.95 738 1.07 772 1.20 805 1.34 837 1.49 761 1.22 792 1.34 823 1.47 854 1.62 884 1.78 818 1.53 848 1.66 877 1.80 905 1.95 933 2.12 1.70 1.80 1.90 RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 787 1.15 819 1.28 850 1.42 827 1.37 859 1.51 890 1.65 869 1.64 900 1.79 929 1.94 914 1.94 943 2.11 971 2.26 961 2.29 988 2.46 1015 2.64 2.00 RPM BHP 879 1.56 918 1.80 959 2.09 999 2.43 1041 2.82 ← 3 HP Over-Sized Motor & Drive CFM 1.10 RPM BHP 2720 3060 3400 3740 4080 907 946 986 1025 1067 1.71 1.96 2.25 2.60 2.99 1.20 1.30 RPM BHP RPM BHP 2 HP Standard Motor & Drive 934 1.86 960 2.01 971 2.11 997 2.28 1011 2.41 1037 2.59 1051 2.77 1077 2.94 1092 3.17 1117 3.36 Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 RT-PRC017-EN External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 987 1023 1061 1100 1140 1087 1117 1151 1189 1229 1111 2.97 1140 3.31 1174 3.69 1211 4.08 - 1134 3.14 1163 3.49 1194 3.87 1231 4.28 - 2.17 2.45 2.76 3.12 3.54 1013 2.32 1038 2.48 1064 1047 2.62 1070 2.79 1094 1085 2.94 1107 3.12 1130 1123 3.30 1147 3.50 1168 1164 3.73 1187 3.92 1208 3 HP Over-Sized Motor & Drive 2.64 2.96 3.30 3.68 4.12 2.80 3.13 3.48 3.88 4.32 Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 33 Performance Data Table PD-21 - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Horizontal Configuration (SI) 25 m3/h 4620 5200 5780 6350 6930 m3/h 4620 5200 5780 6350 6930 50 75 RPM kW RPM kW RPM kW 1.50 Nom kW Std Mtr & Low Static Drive 651 0.51 694 0.59 740 0.68 722 0.70 761 0.79 798 0.88 793 0.94 830 1.04 863 1.14 865 1.23 899 1.34 930 1.45 937 1.57 970 1.70 999 1.81 275 300 325 RPM kW RPM kW RPM kW 1.50 Nom kW Std Mtr & Drive 1011 1.43 1036 1.52 1059 1.61 1070 1.75 1094 1.85 1117 1.95 1128 2.12 1152 2.23 1176 2.34 1186 2.53 1210 2.65 1233 2.78 1239 2.97 1267 3.13 1291 3.27 Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 100 RPM kW 787 841 898 961 1027 0.79 1.00 1.25 1.56 1.93 350 RPM kW External Static Pressure (Pascals) 125 150 175 200 RPM kW RPM kW RPM kW RPM kW 1.50 Nom kW Standard Motor & Drive 831 0.89 869 0.99 901 1.08 931 1.17 883 1.11 923 1.23 958 1.35 989 1.45 937 1.37 975 1.51 1011 1.64 1045 1.77 994 1.68 1028 1.82 1063 1.96 1097 2.11 1055 2.05 1085 2.19 1118 2.34 1150 2.50 2.24 Nom kW Over-Sized Motor & High Static Drive External Static Pressure (Pascals) 375 400 RPM kW RPM kW 425 RPM kW 1082 1.69 1104 1.78 1127 1.87 1149 1139 2.05 1161 2.15 1182 2.24 1203 1198 2.45 1219 2.56 1241 2.67 1261 1256 2.90 1278 3.03 1298 3.15 1319 2.24 Nom kW Over-Sized Motor & High Static Drive 1.96 2.35 2.78 3.27 - 225 RPM kW 250 RPM kW 959 1017 1075 1129 1181 986 1045 1103 1159 1211 1.26 1.55 1.89 2.26 2.66 1.35 1.65 2.01 2.40 2.82 450 RPM kW 475 RPM kW 500 RPM kW 1170 1222 1280 - 1191 1243 1299 - 1212 1262 1319 - 2.05 2.44 2.88 - 2.14 2.54 2.99 - 2.24 2.64 3.11 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-21a - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Horizontal Configuration - (IP) CFM 2720 3060 3400 3740 4080 CFM 2720 3060 3400 3740 4080 1.10 1.20 1.30 RPM BHP RPM BHP RPM BHP 2 HP Std Motor & Low Static Drive 651 0.69 694 0.79 740 0.92 722 0.94 761 1.06 798 1.18 793 1.26 830 1.40 863 1.53 865 1.65 899 1.80 930 1.94 937 2.11 970 2.27 999 2.43 External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 1.80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Drive 787 1.06 831 1.20 869 1.33 901 1.45 931 1.57 841 1.34 883 1.49 923 1.65 958 1.81 989 1.95 898 1.67 937 1.84 975 2.02 1011 2.20 1045 2.37 961 2.09 994 2.26 1028 2.44 1063 2.63 1097 2.83 1027 2.59 1055 2.75 1085 2.94 1118 3.14 1150 3.35 3 HP Over-Sized Motor & Drive 1.10 1.20 RPM BHP RPM BHP 2 HP Std Motor & Drive 1011 1.92 1036 2.04 1070 2.35 1094 2.48 1128 2.84 1152 2.99 1186 3.40 1210 3.56 1239 3.99 1267 4.20 External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 1.80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Over-Sized Motor & Drive 1082 2.27 1104 2.39 1127 2.51 1149 2.64 1170 2.75 1139 2.75 1161 2.88 1182 3.01 1203 3.15 1222 3.27 1198 3.29 1219 3.43 1241 3.58 1261 3.73 1280 3.87 1256 3.90 1278 4.06 1298 4.22 1319 4.39 3 HP Over-Sized Motor & Drive 1.30 RPM BHP 1059 1117 1176 1233 1291 2.15 2.61 3.14 3.73 4.39 Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 34 1.90 RPM BHP 2.00 RPM BHP 959 1017 1075 1129 1181 986 1045 1103 1159 1211 1.69 2.08 2.54 3.03 3.57 1.81 2.22 2.69 3.22 3.78 1.90 RPM BHP 2.00 RPM BHP 1191 1243 1299 - 1212 1262 1319 - 2.88 3.41 4.02 - 3.00 3.54 4.17 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-22 - Belt Drive Evaporator Fan Performance - YSC120AD*L - Low Heat - Downflow Configuration - (SI) 25 50 External Static Pressure (Pascals) 100 125 150 RPM kW RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Low Static Drive 175 RPM kW 200 RPM kW 691 751 813 876 940 832 879 931 985 1042 863 910 959 1012 1067 75 m3/h RPM kW RPM kW 5440 6120 6800 7480 8160 746 814 883 0.90 1.17 1.50 717 780 845 911 0.77 1.00 1.29 1.62 m3/h 275 RPM kW 300 RPM kW 325 RPM kW 5440 6120 6800 7480 8160 952 996 1041 1088 1139 979 1023 1067 1113 1161 1004 1049 1092 1137 1185 1.50 1.77 2.08 2.43 2.83 1.63 1.89 2.21 2.57 2.99 0.66 0.86 1.11 1.41 1.75 1.75 2.02 2.34 2.72 3.15 Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 727 784 843 905 967 0.75 0.95 1.21 1.52 1.88 763 816 873 932 993 0.85 1.06 1.31 1.63 2.00 798 848 902 959 1018 0.95 1.17 1.43 1.74 2.12 1.06 1.29 1.56 1.87 2.24 1.16 1.41 1.69 2.01 2.38 External Static Pressure (Pascals) 350 375 400 425 450 RPM kW RPM kW RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Drive 1029 1.87 1053 2.00 1078 2.13 1101 2.27 1124 2.41 1073 2.15 1097 2.29 1120 2.43 1142 2.56 1164 2.71 1117 2.48 1141 2.62 1164 2.76 1186 2.91 1208 3.06 1162 2.87 1185 3.01 1207 3.16 1229 3.30 1208 3.30 2.24 Nom kW Standard Motor & High Static Drive 225 250 RPM kW RPM kW 2.24 Nom kW Standard Motor & Drive 895 1.27 924 1.39 940 1.53 968 1.64 986 1.82 1014 1.94 1037 2.14 1063 2.29 1091 2.53 1115 2.68 475 RPM kW 500 RPM kW 1146 1186 1228 - 1169 1207 - 2.54 2.85 3.20 - 3.59 4.02 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-22a - Belt Drive Evaporator Fan Performance - YSC120AD*L - Low Heat - Downflow Configuration - (IP) CFM 1.10 RPM BHP 1.20 RPM BHP 3200 3600 4000 4400 4800 746 814 883 717 780 845 911 1.21 1.57 2.02 1.03 1.35 1.73 2.18 External Static Pressure (Inches of Water) 1.30 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Low Static Drive 691 0.88 727 1.00 763 1.14 798 1.28 751 1.15 784 1.28 816 1.42 848 1.57 813 1.49 843 1.62 873 1.76 902 1.92 876 1.88 905 2.03 932 2.18 959 2.34 940 2.35 967 2.52 993 2.68 1018 2.84 CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP 3200 3600 4000 4400 4800 952 996 1041 1088 1139 979 1023 1067 1113 1161 1004 1049 1092 1137 1185 2.01 2.37 2.79 3.26 3.80 2.18 2.53 2.96 3.45 4.00 2.34 2.71 3.14 3.64 4.22 Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 RT-PRC017-EN 1.70 RPM BHP 1.80 RPM BHP 832 879 931 985 1042 863 910 959 1012 1067 1.42 1.73 2.09 2.51 3.01 1.56 1.89 2.26 2.69 3.20 External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 1.80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 1029 2.51 1053 2.68 1078 2.86 1101 3.04 1124 3.23 1073 2.88 1097 3.07 1120 3.25 1142 3.43 1164 3.63 1117 3.33 1141 3.51 1164 3.7 1186 3.90 1208 4.10 1162 3.84 1185 4.04 1207 4.23 1229 4.43 1208 4.43 3 HP Standard Motor & High Static Drive 1.90 2.00 RPM BHP RPM BHP 3 HP Std Motor & Drive 895 1.71 924 1.86 940 2.05 968 2.20 986 2.43 1014 2.61 1037 2.88 1063 3.07 1091 3.39 1115 3.59 1.90 RPM BHP 2.00 RPM BHP 1146 1186 1228 - 1169 1207 - 3.41 3.83 4.30 - 3.59 4.02 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 35 Performance Data Table PD-23 - Belt Drive Evaporator Fan Performance - YSC120AD*L - Horizontal Configuration (SI) 25 5440 6120 6800 7480 8160 100 RPM kW RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Low Static Drive 719 0.72 761 0.82 798 0.91 834 1.01 799 1.00 836 1.11 872 1.21 904 1.32 881 1.35 913 1.46 947 1.58 977 1.70 963 1.78 992 1.89 1023 2.02 1052 2.16 1045 2.29 1072 2.41 1099 2.54 1127 2.69 m3/h 275 RPM kW 5440 6120 6800 7480 8160 1077 1140 1196 1250 - m3/h 50 1.83 2.25 2.70 3.19 - 75 External Static Pressure (Pascals) 125 150 175 200 225 250 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Drive 875 1.13 916 1.25 955 1.38 991 1.50 1022 1.61 1050 1.72 936 1.43 972 1.56 1009 1.70 1045 1.84 1079 1.98 1111 2.12 1006 1.82 1035 1.94 1066 2.08 1100 2.23 1133 2.38 1165 2.54 1079 2.28 1106 2.41 1132 2.54 1160 2.69 1189 2.85 1219 3.02 1154 2.83 1179 2.97 1203 3.11 1227 3.25 2.24 Nom kW Standard Motor & High Static Drive External Static Pressure (Pascals) 300 325 350 375 400 425 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Drive 1103 1.94 1126 2.04 1150 2.14 1171 2.24 1193 2.35 1214 2.45 1165 2.37 1190 2.49 1214 2.61 1235 2.73 1257 2.85 1279 2.97 1225 2.86 1252 3.00 1276 3.15 1299 3.28 2.24 Nom kW Standard Motor & High Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 450 RPM kW 475 RPM kW 500 RPM kW 1233 1298 - 1253 1317 - 1274 1338 - 2.55 3.08 - 2.65 3.19 - 3.46 4.10 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-23a - Belt Drive Evaporator Fan Performance - YSC120AD*L - Horizontal Configuration - (IP) CFM 1.10 RPM BHP 3200 3600 4000 4400 4800 719 799 881 963 1045 CFM 1.10 RPM BHP 3200 3600 4000 4400 4800 1077 1140 1196 1250 - 0.97 1.35 1.81 2.39 3.07 2.45 3.02 3.62 4.28 - External Static Pressure (Inches of Water) 1.20 1.30 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Low Static Drive 761 1.10 798 1.22 834 1.35 875 1.51 916 1.68 836 1.48 872 1.63 904 1.77 936 1.91 972 2.09 913 1.96 947 2.12 977 2.28 1006 2.44 1035 2.60 992 2.54 1023 2.71 1052 2.89 1079 3.06 1106 3.23 1072 3.23 1099 3.41 1127 3.61 1154 3.80 1179 3.98 External Static Pressure (Inches of Water) 1.20 1.30 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 1103 2.60 1126 2.73 1150 2.87 1171 3.01 1193 3.15 1214 3.29 1165 3.18 1190 3.34 1214 3.51 1235 3.66 1257 3.82 1279 3.98 1225 3.83 1252 4.03 1276 4.22 1299 4.40 3 HP Standard Motor & High Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 36 1.70 1.80 1.90 RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 955 1.85 991 2.01 1022 2.16 1009 2.28 1045 2.47 1079 2.66 1066 2.78 1100 2.99 1133 3.20 1132 3.41 1160 3.61 1189 3.82 1203 4.17 1227 4.36 3 HP Standard Motor & High Static Drive 2.00 RPM BHP 1050 2.31 1111 2.84 1165 3.41 1219 4.05 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 1233 1298 - 1253 1317 - 1274 1338 - 3.42 4.13 - 3.56 4.28 - 3.71 4.45 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-24 - Belt Drive Evaporator Fan Performance - YSC120AD*H - High Heat - Downflow Configuration - (SI) 25 50 External Static Pressure (Pascals) 100 125 150 kW RPM kW RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Low Static Drive 175 RPM kW 0.87 1.15 1.48 1.87 860 913 969 1029 1090 75 m3/h RPM kW RPM 5440 6120 6800 7480 8160 721 793 866 939 0.78 1.04 1.36 1.75 755 824 895 967 m3/h 275 RPM kW 300 RPM kW 5440 6120 6800 7480 8160 976 1025 1076 1129 1184 1001 1052 1101 1153 1207 1.61 1.90 2.26 2.67 3.14 1.73 2.03 2.39 2.81 3.30 723 787 854 923 992 0.74 0.96 1.25 1.59 1.99 759 820 883 949 1017 0.84 1.07 1.36 1.70 2.12 793 851 913 976 1042 0.94 1.18 1.48 1.83 2.24 827 882 941 1003 1066 1.05 1.30 1.60 1.96 2.38 1.15 1.42 1.73 2.10 2.52 External Static Pressure (Pascals) 325 350 375 400 425 RPM kW RPM kW RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Drive 1027 1.86 1051 1.99 1075 2.12 1098 2.25 1120 2.38 1076 2.17 1100 2.30 1122 2.44 1145 2.58 1167 2.73 1126 2.53 1149 2.67 1172 2.81 1194 2.96 1216 3.12 1176 2.96 1200 3.11 1222 3.26 2.24 Nom kW Standard Motor & High Static Drive Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 200 225 250 RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Drive 891 1.26 921 1.37 949 1.49 942 1.54 971 1.66 999 1.78 997 1.86 1024 1.99 1050 2.12 1054 2.24 1079 2.38 1104 2.53 1114 2.67 1138 2.83 1161 2.98 450 RPM kW 475 RPM kW 500 RPM kW 1143 1188 1236 - 1166 1210 - 1189 1230 - 2.52 2.87 3.26 - 2.66 3.02 - 3.59 4.02 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-24a - Belt Drive Evaporator Fan Performance - YSC120AD*H - High Heat - Downflow Configuration - (IP) CFM 1.10 RPM BHP 3200 3600 4000 4400 4800 721 793 866 939 1.04 1.40 1.83 2.34 External Static Pressure (Inches of Water) 1.20 1.30 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Low Static Drive 723 0.99 759 1.12 793 1.26 827 1.40 755 1.17 787 1.29 820 1.44 851 1.59 882 1.75 824 1.54 854 1.67 883 1.82 913 1.98 941 2.15 895 1.98 923 2.13 949 2.28 976 2.45 1003 2.63 967 2.51 992 2.67 1017 2.84 1042 3.01 1066 3.19 CFM 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP 3200 3600 4000 4400 4800 976 1025 1076 1129 1184 1001 1052 1101 1153 1207 1027 1076 1126 1176 - 2.16 2.55 3.03 3.58 4.21 2.32 2.73 3.20 3.77 4.42 2.49 2.90 3.40 3.97 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 RT-PRC017-EN 1.70 RPM BHP 860 913 969 1029 1090 1.55 1.90 2.32 2.81 3.38 External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 1051 2.66 1075 2.84 1098 3.02 1120 3.19 1100 3.09 1122 3.27 1145 3.46 1167 3.66 1149 3.58 1172 3.77 1194 3.97 1216 4.18 1200 4.17 1222 4.37 3 HP Standard Motor & High Static Drive 1.80 1.90 2.00 RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 891 1.69 921 1.84 949 2.00 942 2.06 971 2.22 999 2.39 997 2.50 1024 2.67 1050 2.85 1054 3.00 1079 3.20 1104 3.39 1114 3.58 1138 3.79 1161 4.00 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 1143 1188 1236 - 1166 1210 - 1189 1230 - 3.38 3.85 4.38 - 3.57 4.05 - 3.75 4.25 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. 37 Performance Data Table PD-25 - Belt Drive Evaporator Fan Performance - YSC120AD*H - High Heat - Horizontal Configuration (SI) 25 50 75 m3/h RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Low Static Drive 5440 768 0.84 805 0.93 842 1.03 6120 856 1.16 888 1.27 921 1.37 6800 943 1.57 973 1.68 1002 1.80 7480 1031 2.06 1060 2.19 1086 2.32 8160 1119 2.58 1146 2.79 1171 2.93 m3/h 5440 6120 6800 7480 8160 275 300 325 RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Drive 1107 1.95 1131 2.06 1154 2.16 1178 2.43 1202 2.55 1224 2.67 1249 2.99 1273 3.13 1296 3.26 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 100 RPM kW 884 955 1031 1113 1195 1.15 1.49 1.92 2.45 3.07 350 RPM kW External Static Pressure (Pascals) 125 150 RPM kW RPM kW 924 992 1062 1139 1219 200 225 250 RPM kW RPM kW RPM kW 2.24 Nom kW Standard Motor & Drive 1.28 962 1.40 998 1.52 1028 1.64 1055 1.74 1082 1.85 1.63 1028 1.77 1063 1.91 1096 2.05 1126 2.19 1153 2.31 2.06 1096 2.21 1129 2.36 1161 2.52 1192 2.68 1222 2.84 2.57 1167 2.73 1198 2.90 1228 3.07 1257 3.24 3.21 1243 3.36 2.24 Nom kW Standard Motor & High Static Drive External Static Pressure (Pascals) 375 400 RPM kW RPM kW 175 RPM kW 425 RPM kW 1176 2.27 1197 2.37 1218 2.47 1238 1247 2.79 1268 2.91 1288 3.02 1308 2.24 Nom kW Standard Motor & High Static Drive 2.58 3.14 - 450 RPM kW 475 RPM kW 500 RPM kW 1257 1328 - 1276 - 1296 - 2.68 3.26 - 2.78 - 3.59 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. Table PD-25a - Belt Drive Evaporator Fan Performance - YSC120AD*H - High Heat - Horizontal Configuration - (IP) CFM 3200 3600 4000 4400 4800 CFM 3200 3600 4000 4400 4800 External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Low Static Drive 3 HP Standard Motor & Drive 768 1.12 805 1.25 842 1.38 884 1.54 924 1.71 962 1.88 998 2.04 1028 2.19 856 1.56 888 1.70 921 1.84 955 2.00 992 2.19 1028 2.37 1063 2.57 1096 2.75 943 2.10 973 2.26 1002 2.41 1031 2.58 1062 2.76 1096 2.96 1129 3.17 1161 3.38 1031 2.76 1060 2.94 1086 3.11 1113 3.28 1139 3.45 1167 3.66 1198 3.89 1228 4.11 1119 3.45 1146 3.74 1171 3.93 1195 4.11 1219 4.30 1243 4.50 3 HP Standard Motor & High Static Drive 1.10 1.20 1.30 RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Drive 1107 2.62 1131 2.76 1154 2.90 1178 3.27 1202 3.42 1224 3.58 1249 4.01 1273 4.19 1296 4.38 - Notes: Data Includes Pressure Drop Due To Wet Coils And Filters. 3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 38 1.90 RPM BHP 2.00 RPM BHP 1055 1126 1192 1257 - 1082 1153 1222 - 2.34 2.93 3.59 4.34 - 2.48 3.10 3.81 - External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 RPM BHP RPM BHP RPM BHP RPM BHP 1.80 RPM BHP 1.90 RPM BHP 2.00 RPM BHP 1176 1247 - 1257 1328 - 1276 - 1296 - 3.04 1197 3.17 1218 3.32 1238 3.74 1268 3.90 1288 4.05 1308 3 HP Standard Motor & High Static Drive 3.46 4.21 - 3.59 4.37 - 3.73 - 3.87 - Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected. RT-PRC017-EN Performance Data Table PD-26 - Standard Motor & Sheave/Fan Speed (RPM) Unit 6 Turns Model No. Open YSC060AD N/A YSC072ADRL N/A YSC072ADRH N/A YSC090AD 859 YSC102AD 786 YSC120AD 894 Factory set at 3 turns open 5 Turns Open 1036 698 806 913 836 950 4 Turns Open 1105 751 860 967 885 1006 3 Turns Open 1174 806 913 1021 934 1062 2 Turns Open 1243 859 968 1075 982 1118 1 Turns Open 1312 913 1022 1129 1032 1174 Closed 1381 967 1074 N/A N/A N/A Table PD-27 - Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (RPM) Unit 6 Turns Model No. Open YSC060AD N/A YSC072ADRL N/A YSC090AD N/A YSC102AD N/A YSC120AD N/A Factory set at 3 turns open 5 Turns Open 691 537 671 629 717 4 Turns Open 760 590 714 664 754 3 Turns Open 829 644 757 701 799 2 Turns Open 898 698 800 737 844 1 Turns Open 967 752 843 773 885 Closed 1036 806 886 811 922 Table PD-28 - Standard Motor & High Static Drive Accessory Sheave/Fan Speed (RPM) Unit 6 Turns Model No. Open YSC060AD N/A YSC072AD N/A YSC090AD 1020 YSC102AD 936 YSC120AD 1062 Factory set at 3 turns open 5 Turns Open 1243 967 1073 981 1118 4 Turns Open 1311 1021 1127 1032 1174 3 Turns Open 1379 1075 1181 1083 1229 2 Turns Open 1450 1128 1235 1134 1285 1 Turns Open 1515 1183 1289 1182 1341 Closed 1588 1235 N/A N/A N/A 2 Turns Open 1128 1392 1181 N/A 1 Turns Open 1183 1460 1251 N/A Closed 1235 N/A 1321 N/A 8000 63 63 64 62 60 Overall dBA 80 85 85 83 79 Table PD-29 - Oversized Motor & Drive Sheave/Fan Speed (RPM) Unit 6 Turns Model No. Open YSC072AD N/A YSC090AD 1112 YSC102AD N/A YSC120AD N/A Factory set at 3 turns open 5 Turns Open 967 1182 971 N/A 4 Turns Open 1021 1252 1041 N/A 3 Turns Open 1075 1322 1111 N/A Table PD-30 - Sound Power Level - dB (ref. 10 -12 Watts) Unit Octave Model No. 63 YSC060AD 84 YSC072AD 83 YSC090AD 83 YSC102AD 83 YSC120AD 83 Note: Tests follow ARI 270-95 RT-PRC017-EN 125 91 90 90 89 86 250 79 86 86 84 80 500 77 82 83 81 77 1000 74 79 80 77 73 2000 71 75 75 72 69 4000 68 70 71 69 66 39 Performance Data Table PD-31 - Static Pressure Drops Through Accessories - (Pascals) Unit Model No. YSC060AD YSC072AD YSC090AD YSC102AD YSC120AD Airflow (m3/h) 2720 3400 4080 3260 4080 4890 4080 5100 6120 4620 5780 6930 5440 6800 8160 Standard Filters1 25 37 55 10 15 22 15 25 35 12 20 30 17 27 40 Pleated Filters (50 mm) 37 55 72 17 22 30 22 32 45 20 27 40 25 37 50 Economizer with OA/RA Dampers2 100% OA 100% RA 100% OA 100% RA Downflow Horizontal 30 11 30 4 46 17 46 6 64 26 64 9 25 2 15 5 27 5 20 5 33 10 25 10 27 5 20 5 35 12 30 12 52 17 62 20 31 7 22 10 47 15 45 15 75 17 77 22 42 12 35 12 65 17 75 20 85 22 87 25 Notes: 1. Tested with standard filters. The YSC060AD has 25 mm (1 inch) standard fiters. The YSC072AD - 120AD has 50 mm (2 inch) standard filters. The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters. 2. OA = Outside Air and RA = Return Air 3. Nominal kW ratings at 380 V Table PD-31a - Static Pressure Drops Through Accessories - (Inches of Water Column) Unit Model No. YSC060AD YSC072AD YSC090AD YSC102AD YSC120AD Airflow (CFM) 1600 2000 2400 1920 2400 2880 2400 3000 3600 2720 3400 4080 3200 4000 4800 Standard Filters1 0.10 0.15 0.22 0.04 0.06 0.09 0.06 0.10 0.14 0.05 0.08 0.12 0.07 0.11 0.16 Pleated Filters (2 inch) 0.15 0.22 0.29 0.07 0.09 0.12 0.09 0.13 0.18 0.08 0.11 0.16 0.10 0.15 0.20 Economizer with OA/RA Dampers2 100% OA 100% RA 100% OA 100% RA Downflow Horizontal 0.12 0.04 0.12 0.01 0.18 0.07 0.18 0.02 0.26 0.10 0.26 0.04 0.10 0.01 0.06 0.02 0.11 0.02 0.08 0.02 0.13 0.04 0.10 0.04 0.11 0.02 0.08 0.02 0.14 0.05 0.12 0.05 0.21 0.07 0.25 0.08 0.12 0.03 0.09 0.04 0.19 0.06 0.18 0.06 0.30 0.07 0.31 0.09 0.17 0.05 0.14 0.05 0.26 0.07 0.30 0.08 0.34 0.09 0.35 0.10 Notes: 1. Tested with standard filters. The YSC060AD has 25 mm (1 inch) standard fiters. The YSC072AD - 120AD has 50 mm (2 inch) standard filters. The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters. 2. OA = Outside Air and RA = Return Air 3. Nominal kW ratings at 380 V 40 RT-PRC017-EN Performance Data Table PD-32 — Gas-Fired Heating Capacities for G20,G25, and G31 Unit Furnace Heating Input Heating Output Model No. Model Input kW Input MBH Output kW Output MBH YSC060*DRL G80 19.6 67 15.7 54 YSC060*DRH G120 29.3 100 23.4 80 YSC072*DRL G120 29.3 100 23.4 80 YSC072*DRH G200 48.9 167 39.1 134 YSC090*DRL G120 29.3 100 23.4 80 YSC090*DRH G200 48.9 167 39.1 134 YSC102*DRL G150 36.7 125 29.3 100 YSC102*DRH G250 60.9 208 48.7 166 YSC120*DRL G150 36.7 125 29.3 100 YSC120*DRH G250 60.9 208 48.7 166 Ratings shown are for elevations up to 2,000 ft. For higher elevations, reduce ratings at a rate of 4% per 1,000 ft. elevation. RT-PRC017-EN 41 Zone Controls Zone Sensors Zone Sensors are the building occupant’s comfort control devices for Precedent™ units with ReliaTel™ control: Manual Changeover — Heat, Cool or Off System Switch. Fan Auto or Off Switch. One temperature setpoint lever. Manual/Automatic Changeover — Auto, Heat, Cool or Off System Switch. Fan Auto or Off Switch. Two temperature setpoint levers. Optional Status Indication LED lights, System On, Heat, Cool, or Service. Remote Sensor — Sensor(s) available for all zone sensors to provide remote sensing capabilities. 42 Non-Programmable Manual Auto Changeover with Digital LCD Display — Auto, heat, cool or off mode selection button. Auto or off fan button. Status indication LCD indicators - System on,heat, cool, or service. Conventional Thermostats Conventional Thermostats are the building occupant’s comfort control devices when a generic thermostat is desired. Manual Changeover — One Heat, One Cool Thermostat. Heat, Cool or Off System Switch. Fan Auto or On Switch. Set Point Dial. Adjustable Heat Anticipator. Programmable Night Setback — Auto or manual changeover with seven-day programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. All programmable sensors have System On, Heat, Cool, Service LED/indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and two (2) Override programs per day. Automatic Changeover — One Heat, Two Cool Thermostat. Off, Auto System Switch. Auto/On Fan Switch. Programmable Electronic Night Setback Thermostat — Heating setback and cooling setup with 7-day, programming capability. Available in two-stage heating/cooling or one-stage heating/ cooling versions with automatic changeover. Integrated Comfort™ System — Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane Integrated Comfort™ system. RT-PRC017-EN Electrical Data Table ED-1 — Unit Wiring Standard Indoor Fan Motor Minimum Maximum Fuse Circuit Size Or Maximum Ampacitiy Circuit Breaker1 17.7 25 23.2 35 24.8 35 26.8 35 31.2 40 Unit Operating Voltage Range 342-456 342-456 342-456 342-456 342-456 Unit Model No. YSC060ADR YSC072ADR YSC090ADR YSC102ADR YSC120ADR Oversized Indoor Fan Motor Minimum Maximum Fuse Circuit Size Or Maximum Ampacitiy Circuit Breaker1 17.7 25 24.2 35 26.5 35 28.5 35 31.2 40 Notes: 1. All units to be installed under local codes Table ED-2 — Electrical Characteristics - Evaporator Fan Motor - 50 Hz Standard Evaporator Fan Motor Unit Model No. YSC060AD YSC072AD YSC090AD YSC102AD YSC120AD Oversized Evaporator Fan Motor Amps No. 1 1 1 1 1 Volts 380-415 380-415 380-415 380-415 380-415 Phase 3 3 3 3 3 HP 1.5 1.5 2.0 2.0 3.0 FLA 4.3 4.3 5.3 5.3 7.0 LRA 25.3 25.3 36.4 36.4 57.0 No. 1 1 1 - Volts 380-415 380-415 380-415 - Phase 3 3 3 - Amps FLA 5.3 7.0 7.0 - HP 2.0 3.0 3.0 - LRA 36.4 57.0 57.0 - Table ED-3 — Electrical Characteristics - Compressor Motor and Condenser Motor - 50 Hz Compressor Motor Unit Model No. YSC060AD YSC072AD YSC090AD YSC102AD YSC120AD Condenser Fan Motor Amps No. 1 1 1 2 2 Volts 380-415 380-415 380-415 380-415 380-415 Phase 3 3 3 3 3 HP1 5.7 7.5 8.3 6.0 / 3.8 6.0 / 4.8 RPM 2875 2875 2875 2875 2875 RLA1 9.5 12.7 13.2 9.3 / 6.9 9.9 / 8.5 Amps LRA1 74.00 95.00 100.00 74.0 / 48.0 74.0 / 61.8 No. 1 1 1 1 1 Phase 1 1 1 1 1 HP 0.40 0.75 0.75 0.75 0.75 FLA 1.9 2.8 2.8 2.8 2.8 LRA 2.8 7.1 7.1 7.1 7.1 Note: 1. Comp1/Comp2 Table ED-4 Electrical Characteristics - Inducer Motor Model No. YSC060-090*DRL YSC060*DRH YSC102-120*DRL YSC072-120*DRH RT-PRC017-EN Heat Low High Low High Heating Stages Watts HP RPM Volts Phase LRA 1 21 1/35 2525 208-230 1 0.6 2 50 1/15 2800/2550 208-230 1 0.45 43 Jobsite Connections Typical Number Of Wires DISCONNECT SWITCH (BY OTHERS) Zone Sensors ZONE SENSOR OR THERMOSTAT ROOFTOP UNIT A — Manual Changeover Manual/Auto Changeover Manual/Auto Changeover with Status Indication LED’s Programmable Night Setback with Status Indication LED’s 4 5 10 7 Thermostats A — 4 wires, 24-volts B — 3 Power Wires + 1 Ground Wire (three phase) 2 Power Wires + 1 Ground Wire (single phase) For specific wiring information, see the installation instructions. All wiring except power wires is low voltage. All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer. 44 RT-PRC017-EN Dimensional Data YSC060 All dimensions are in inches/millimeters. YSC060 RT-PRC017-EN 45 Dimensional Data YSC060 All dimensions are in inches/millimeters YSC060 — Downflow Airflow Supply and Return YSC060 — Horizontal Airflow Supply and Return YSC060 — Unit Clearance and Roof Opening 46 RT-PRC017-EN Dimensional Data YSC060 All dimensions are in inches/millimeters. YSC060 — Roof Curb YSC060 — Downflow Duct Connections — Field Fabricated RT-PRC017-EN 47 Dimensional Data YSC072-120 All dimensions are in inches/millimeters. YSC072 and YSC090 YSC102 and YSC120 48 RT-PRC017-EN Dimensional Data YSC072-120 All dimensions are in inches/millimeters. YSC072-120 — Downflow Airflow Supply and Return YSC072-120 — Horizontal Airflow Supply and Return YSC072-120 — Unit Clearance and Roof Opening RT-PRC017-EN 49 Dimensional Data YSC072-120 All dimensions are in inches/millimeters. YSC072-120 — Roof Curb YSC072-120 — Downflow Duct Connections — Field Fabricated ALL FLANGES 1 1/4” (31 MM) 50 RT-PRC017-EN Dimensional Data YSC060 Options/ Accessories YSC060 — Economizer, Manual, or Motorized Damper Hood YSC060 — Barometric Relief Damper Hood YSC060 — Swing Diameter for Hinged Door(s) Option See Page 42 for Through the Base Utilities Information RT-PRC017-EN 51 Dimensional Data YSC072-120 Options/Accessories YSC072-120 — Economizer and Barometric Relief Damper Hoods YSC072-120 — Swing Diameter for Hinged Door(s) Option 52 RT-PRC017-EN Weights Table W-1 - Maximum Unit and Corner Weights and Center of Gravity Dimensions (SI) Maximum Weights(2) (kg) Unit Model No. YSC060AD YSC072AD YSC090AD YSC102AD YSC120AD Shipping(2) 295 398 466 482 528 Net(2) 260 350 419 434 481 Corner Weights(1) (kg) A 81 113 139 141 155 B 64 90 110 114 126 C 54 64 75 79 89 Center of Gravity (mm) D 62 83 95 100 111 Length 810 990 970 1020 1020 Width 510 560 530 560 560 Notes: (1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support. (2) Weights are approximate. Table W-1a - Maximum Unit and Corner Weights and Center of Gravity Dimensions (IP) Corner Weights(1) (lbs) Maximum Weights (lbs) Unit Model No. YSC060AD YSC072AD YSC090AD YSC102AD YSC120AD Shipping(2) 651 877 1028 1062 1165 Net 574 772 923 957 1060 A 179 249 306 310 342 B 140 198 243 252 277 C 119 141 165 175 197 Center of Gravity (in) D 136 184 210 220 245 Length 32 39 38 40 40 Width 20 22 21 22 22 Notes: (1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support. (2) Weights are approximate. Table W-2 - Accessory Net Weights(1) (2) (kg) Accessory(3) Economizer Barometric Relief Motorized Outside Air Damper Manual Outside Air Damper Roof Curb Oversized Motor Coil Guards Hinged Doors Electric Heaters Net Weights(2) YSC060 YSC072-120 12 16 3 5 9 14 7 12 32 52 2 4 5 9 5 5 7 14 Notes: (1) Weights for options not listed are < 3 kg. (2) Net weight should be added to unit weight when ordering factory-installed accessories. (3) Some accessories not available on all units. RT-PRC017-EN Table W-2a - Accessory Net Weights(1) (2) (lbs) Accessory(3) Economizer Barometric Relief Motorized Outside Air Damper Manual Outside Air Damper Roof Curb Oversized Motor Coil Guards Hinged Doors Electric Heaters YSC060 26 7 20 16 70 5 12 10 15 Net Weights(2) YSC072-120 36 10 30 26 115 8 20 12 30 Notes: (1) Weights for options not listed are < 5 lbs. 2) Net weight should be added to unit weight when ordering factory-installed accessories. (3) Some accessories not available on all units. 53 Mechanical Specifications General Units shall be convertible airflow. Operating range in cooling shall be between 46°C and -18°C (115°F and 0°F) cooling as standard from the factory for all units. All units shall be factory assembled, internally wired, fully charged with R-22, and 100 percent runtested before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing only a single fastener while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil faced, fireretardent permanent, odorless glass fiber material. The base of the unit shall be insulated with 13 mm, 16 kg (1/2 inch, 1 pound) density foil-faced, closed-cell material. All insulation edges shall be either captured or sealed. The unit’s base pan shall have no penetrations within the perimeter of the curb other than the raised 29 mm (11/8 inch) high downflow supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit. 54 UnitTop The top cover shall be one piece construction or, where seams exist, it shall be double-hemmed and gasketsealed. The ribbed top adds extra strength and prevents water from pooling on unit top. Filters 25 mm (1 inch), throwaway filters shall be standard on all 5 ton units.. The filter rack can be converted to two inch capability. 50 mm (2 inch) filters shall be factory supplied on all 6-10 ton units. Optional two inch pleated filters shall be available. Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. Low and high pressure switches shall be standard. Refrigerant Circuits Service pressure ports, and refrigerant line filter driers shall be factory-installed as standard. An area shall be provided for replacement suction line driers. Evaporator And Condenser Coils Internally finned, 8 mm (5/16”) copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Coils shall be leak tested at the factory to ensure pressure integrity. The evaporator coil and condenser coil shall be leak tested to 1375 kPa (200 psig) and pressure tested to 3100 kPa (450 psig). The condensate coil shall have a patent pending 1 +1+1hybrid design with slight gaps for ease of cleaning. A removeable, reversible, double-sloped condensate drain pan is standard. Provision for through the base condensate drain is standard. Gas Heating Section The heating section shall have a progressive tubular heat exchanger design using stainless steel burners and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the combustion products through the firing tubes.The heater shall use a direct spark ignition (DSI) system. On initial call for heat, the combusiton blower shall purge the heat exchanger for 20 seconds before ignition After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat/zone sensor. Units shall be suitable for use with natural gas or propane (field-installed kit). Outdoor Fans The outdoor fans shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position.The fan motor shall be permanently lubricated and shall have built-in thermal overload protection. RT-PRC017-EN Mechanical Specifications Indoor Fan All units shall have belt drive motors. Units with belt drive motors shall have an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static operations. Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall have single point power entry as standard. Units shall provide an external location for mounting a fused disconnect device. Microprocessor controls provide for all 24 volt control functions. With the microprocessor controls, the resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized Microprocessor shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. Accessories/Options Roof Curb The roof curb shall be designed to mate with the unit’s downflow supply and return openings and provide support and a watertight installation when installed properly.The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips. Economizer This accessory shall be either field or factory-installed and is available with or without barometric relief.The assembly includes fully modulating 0-100 percent motor and dampers, minimum position setting, preset linkage, wiring harness with plug, spring return actuators and fixed dry bulb control. Optional solid state enthalpy and differential enthalpy control shall be either factory or field-installed. The factory-installed economizer arrives in the shipping position and shall be moved to the operating position by the installing contractor. Phase Monitor Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. Remote Potentiometer Field-installed, the minimum position setting of economizer shall be adjusted with this accessory. Motorized Outside Air Dampers Factory or field-installed manually set outdoor air dampers shall provide up to 50 percent outside air. Once set, outdoor air dampers shall open to set position when indoor fan starts.The damper shall close to the full closed position when indoor fan shuts down. RT-PRC017-EN Manual Outside Air Damper Factory or field-installed rain hood and screen shall provide up to 50 percent outside air. Oversized Motors Factory or field-installed oversized motors shall be available for high static applications. Discharge Air Sensing This factory or field option provides true discharge air sensing in heating models. This sensor is a status indicator readable through Tracer™ or Tracker™. Coil Guards Hail protection quality coil guards shall be either factory or field-installed for condenser coil protection. Fan Failure/Clogged Filter Switches These factory or field-installed options allow for individual fan failure and dirty filter indication.The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor.The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation. High Pressure Cutout All units have High Pressure cutout as standard. Hinged Access Doors Sheet metal hinges are available factoryinstalled on the Filter/Evaporator Access Door, Indoor Fan/Heat Exchanger Door, and the Compressor/Control Access Door. Black Epoxy Coated Condenser Coil The coil provides corrosion protection to condenser coils for seacoast application. The protection is a factory applied thermoset vinyl coating, bonded to normal aluminum fin stock.The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests. 55 Mechanical Specifications Control Options Comm-3/4 Trane Communication Interface This factory or field-installed option shall be provided to interface microprocessor controlled units with theTrane Integrated Comfort™ systems. Comm-5 LonTalk Communication Interface This factory or field-installed option shall be provided to allow the unit to communicate as aTrane Comm-5 device or directly with generic LonTalk Network Building Automation System Controls. Zone Sensor Field-installed, this accessory shall be provided to interface with the Micro equipped units and shall be available in either manual, automatic programmable with night setback, with system malfunction lights or remote sensor options. Thermostats Two stage heating and cooling operation or one stage heating and cooling shall be available, for field installation, in either manual or automatic changeover. Automatic programmable electronic with night set back shall also be available. 56 Reference Enthalpy Control Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable setpoint. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability.This option shall be available for all units. It can be field-installed or factory-installed with the factory-installed economizer. Differential Enthalpy Control Replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source.This control option offers the highest level of comfort control, plus energy efficiency, available.This option shall be available for all units. It can be field-installed or factory-installed with the factory-installed economizer. Low Ambient Cooling All microprocessor units shall have cooling capabilities down to -18°C (0°F) as standard. RT-PRC017-EN RT-PRC017-EN 57 58 RT-PRC017-EN RT-PRC017-EN 59 Literature Order Number RT-PRC017-EN File Number PL-UN-000-RT-PRC017-EN-02-04 Trane A business of American Standard Companies www.trane.com Supersedes PL-UN-000-RT-PRC017-EN-12-03 Stocking Location 03-03 Webb/Mason 02-04 Electronic Only For more information, contact your local district office or e-mail us at comfort@trane.com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Create Date : 2003:10:13 13:28:57Z Modify Date : 2004:03:03 16:20:01-06:00 Subject : Packaged Gas/Electric Rooftop Units Precedent 50 Hz Keywords : Packaged Gas/Electric, Precedent, 50 Hz Page Count : 60 Creation Date : 2003:10:13 13:28:57Z Mod Date : 2004:03:03 16:20:01-06:00 Producer : Acrobat Distiller 5.0.5 (Windows) Author : Global Unitary Systems - Clarksville Metadata Date : 2004:03:03 16:20:01-06:00 Title : RT-PRC017-EN 10/03 Description : Packaged Gas/Electric Rooftop Units Precedent 50 Hz Creator : Global Unitary Systems - Clarksville Page Mode : UseOutlines Page Layout : OneColumnEXIF Metadata provided by EXIF.tools