WSHP-IOP-2 May 1998 Installation, Operation, and Programming Tracer™ ZN510 Controller Literature History The Trane Company has a policy of continuous product improvement and it reserves the right to change specifications and design without notice. Installation, Operation, WSHP-IOP-2 and Programming Library Service Literature Product Section Unitary Product Water-Source Heat Pumps Model 000 Literature Type Installation, Operation, and Programming Sequence 1 Date April 1998 File No. SL-UN-000-WSHP-IOP-2-0498 Supersedes New Related Literature z WMCA-PD-1 ZN510 Loop Con- troller Product Data sheet z CNT-IOP-1 ZN510 1 Controller: Installation, Operation, and Programing z WSHP-PD-1 Water-Source Heat Pump Controller Product Data Sheet © 1998, American Standard Company z WSHP-IOP-3 ZN510 Water- Source Heat Pump Controller Installation, Operation, and Programming Guide z WMCA-IOP-1 ZN510 Controller Installation, Operation, and Programming Guide Table of Contents Start-up Procedure Power-up Sequence Unit Identification Tag Unit Operation General Information Communication Power Binary Outputs Analog Outputs Binary Inputs Analog Inputs Zone Sensors Heating or Cooling Control Mode Operation Single or Dual Compressor Operation Data Sharing Configuration Troubleshooting Diagnostics ZN510 Controller Replacement Wiring Diagram Hardware Specifications Appendix 4 5 6 7 7 7 8 8 9 9 12 15 18 19 20 21 22 27 28 29 31 33 Start-up Procedure Installation of New Units 1. Follow all instruction for installation of water source heat pumps as detailed in the IOM (Installation Operation Maintenance manual). 5. Verify that water connections have been made to unit, then ensure that water is circulating through the unit. 6. Reapply power. 2. Disconnect power or disable the circuit breaker to unit. 7. Check for STATUS GREEN LED operation to ensure power and communication has been made 3. Run communication link wire to field terminal strips 14 and 16. (See wiring diagram in the unit). 4. Install zone sensor to low voltage control terminals 1 through 6. (See wiring diagram in the unit and zone sensor submittals). Zone Sensor Placement Zone sensor location is an important element of effective room control and comfort. ™ to the ZN510 . Peel IDENTIFICATION TAG from unit and place in the ZN510 IOP, on a copy of Sheet 6 of this document, or on building plans for future location use. The actual room location on the tag may be hand written. The following are typical areas where the zone sensor should not be mounted: z Near drafts or “dead spots” The best sensor location is typically on a wall, remote from the HVAC unit. Readings at this location assure that the desired setpoint is achieved across the space, not just near the unit itself. It may be necessary to subdivide the zone with multiple units to ensure adequate control and comfort. (e.g., behind doors or corners) z Near hot or cold air ducts z Near radiant heat (e.g., heat emitted from appliances or the sun) z Near concealed pipes or chimneys z On outside walls or other non- conditioned surfaces z In air flows from adjacent zones or other units 4 Power Up Sequence Power Up Sequence When 24 VAC power initially is applied to the ZN510 controller, the following sequence occurs: 1. All outputs are controlled off. 2. The controller reads all inputs to determine their initial values. 3. A random start time is hard coded on every board and cannot be disabled. The board generates a random time delay between 0 and 25 seconds. Once this time expires, the power up control wait time (if configured) will wait for 120 seconds. The power up control wait allows ample time for a communicated request to arrive. If the power up control wait time expires, and the controller does not receive a communicated occupancy command, the unit assumes stand alone operation. 4. Normal operation begins. Note: Because the space temperature can be hardwired to the controller or communicated, the controller waits for several minutes to check for the presence of a communicated value. 5 Unit Identification Tag Unit Identification Tag The unit identification tag is factory mounted and provided for easy identification of an installed unit. It contains model number, tagging, and location information. See Figure 1. The top portion of the unit identification tag remains permanently affixed to the unit for identity purposes. The bottom portion of the tag provides pertinent information that is removable to be placed on building plans or in the ZN510 IOP on page 33. This provides identification history about the unit’s location for quick reference. These tags provide information about unit location, unit serial number, and NID (neuron identification number). The NID is similar to the serial number of the unit but is specific to the identification of the ZN510 Board. The location identification is a customer defined, clear English description, of the unit’s physical location. This is a 27 character description of the location. For example, if the location identification for a unit is “Conference Room 101”, the ZN510 and Rover (the Trane Comm 5 service tool) will recognize this clear English description so maintenance can be performed on the appropriate unit. If location identification is not defined, it will default to the unit serial number. This provides some information so the user has multiple references to the unit. The blank location is provided for field modification in case the unit is moved from the initial location. Figure 1: Unit Identification Tag Note: Fold and tear carefully along dashed removable line. 6 Unit Operation General Information The ZN510 controller is a microprocessor-based direct digital controller that controls a variety of water source heat pump equipment including: z Standard efficiency horizontal and vertical units up to 10 tons. z High efficiency horizontal and vertical units. z Console water source heat z Up to two compressors. pumps. z Reversing valve. ZN510 is designed to provide accurate and reliable zone temperature control by using custom proportional integral (PI) algorithms. The controller is factory installed and configured to support: z 2-position outdoor air damper or generic binary output. Peer-to-peer communication across controllers is possible even when a building automation system is not present. ZN510 is also adaptable as a standalone system. z Single fan speed. Figure 2: Communication connections are connected to the field terminal strip (1TB1-5, 1TB1-6) which should be connected to the zone sensor communication jack. This provides direct connect of Rover to the communication link without having to connect directly to the ZN510 board or provided as spare terminals. z Two terminals (TB2-3, TB2-4) are connected to the field terminal strip (1TB1-14, 1TB1-16) for connection to the communication link (daisy chain). z The field terminal strip 1TB1 TB2-6 TB2-5 1TB1-6 COMM 1TB1-5 COMM 1TB1-14 COMM TB2-4 TB2-3 TB2-1 provides screw terminations for all field connections. 1TB1-16 ™ with Trane’s service tool Rover . ZN510 provides a total of six 1/4-inch quick-connect terminals for connection to the Comm5 communication link. These connections include: z Two terminals (TB2-1, TB2-2) z Two terminals (TB2-5, TB2-6) are provided for direct connection of Rover to the ZN510 Board or provided as spare terminals. TB2-2 Communication The ZN510 controller communicates via Trane’s Comm5 protocol. Typically, a communication link is applied between unit controllers and a building automation system. Communication is also possible Space Communication Connection 20 pole low voltage terminal strip screw connections for field hook-up Figure 3: Communication Wiring 7 Communication Zone Sensor Link Unit Operation Power The ZN510 controller is powered by 24 VAC. A total of two 1/4-inch quickconnect terminals are provided for 24 VAC connection to the board. See Figure 4 for ZN510 power requirement. Factory Supplied Transformer Line Voltage 24VAC Note: Power for field installed ancillary devices is not available from the board. It must be tapped at transformer. See Table 21 for excess power available. Note: z During occupied mode, the outdoor air damper is closed when the fan is controlled off. z 2-position damper must not exceed 10 VA power output from board. BOP 7 1TB1-18 J1-7 BOP 6 (Compressor 2) 24VAC 1TB1-17 J1-6 BOP 5 (Compressor 1) J1-5 J1-4 BOP 4 (Not Used) BOP 3 (Not available) Field installed 2 position damper actuator Binary Outputs Figure 5: Binary outputs . Table 1: BOP 6 control of a 2-position outdoor air damper Model Fan Operation Outdoor Air Damper Occupied On or cycling Off Open Closed Occupied warm up or cool down On or cycling Closed Occupied standby On or cycling Closed Unoccupied Cycling Closed Diagnostic present Diagnostic dependent Closed z During unoccupied mode, the outdoor air damper normally remains closed. J1-3 2-Position Damper Actuator or Generic Binary Output Binary output 6 (BOP 6) is factory configured to control a normally closed 2-position outdoor air damper. It may be field modified to control a generic output for control by a building automation system. If set up as a generic output, the controller does not use BOP 6 as part of the normal control. A building automation system must issue commands to control the generic binary output. J1-1 See Figure 5 for the configuration of the five binary outputs. J1-2 BOP 1 (Fan) Binary Outputs The ZN510 uses five of its binary outputs to control heat pump units. Outputs are load side switching triacs. The triac acts as a switch by either making or breaking the circuit between the load (reversing valve, damper, contactor, relay) and ground. BOP 2 (Reversing Valve) Figure 4: Power Connections 8 Unit Operation z Verify output wiring and operation without using Trane’s service tool, Rover. Analog Outputs Binary Inputs The ZN510 controller has three available binary inputs (BI). These inputs are factory-configured for the following functions: z Force compressor operation, allowing the technician to use refrigerant gauges or other test equipment to verify unit operation. manual output test. See Troubleshooting section for Green LED and Testing Heat Pump Configurations on page 21 & 22. The test sequence resets unit diagnostics and attempts to restore normal unit operation prior to testing the outputs. If the diagnostics remains after a reset, the status LED indicates the diagnostic condition is still present and has affected the ZN510 does not use analog outputs. J2-1 Low Temperature Detection (Circuit 2) BI 1 Output Overrides The ZN510 controller includes a manual output test function. Use this feature to manually exercise the outputs in a defined sequence. The purpose of the test sequence, is to verify output and end device operation. Use the manual output test to: J2-2 detection (freezestat) (Circuit 2). z BI 2 = Condensate overflow. z BI 3 = Occupancy or generic Each binary input may be configured as not used depending on options selected. BI 3 is configured as a normally open occupancy input, but may be field modified for generic binary input which is only supported by a building automation system. BI 2 J2-3 Condensate Overflow J2-4 J2-5 Field Wired Occupancy Input BI 3 binary input. Binary Inputs z BI 1= Low temperature J2-6 Figure 6: Binary inputs. Note: The diagnostic functions related to binary inputs such as low temperature detection and condensate overflow are fixed sequences. Each binary input associates an input signal of 0 VAC with open contacts and 24 VAC with closed contacts. See Figure 6 for typical binary input configurations for the heat pump. Table 2: Binary input configurations Binary Input Description Configuratio n Contact Closure Contact Open BI 1 Low Temperature Detection (Cir 2) Normally closed Normal Diagnostic BI 2 Condensate Overflow Normally closed Normal Diagnostic Occupancy Normally open Unoccupied Occupied Generic Normally open Normal Normal BI 3 Note: See Page 10 for specific information concerning BI 1, BI 2 and BI 3. 9 Unit Operation Low Temperature Detection The low temperature detection diagnostic protects the heat exchanger by using an analog leaving water temperature sensor to protect refrigerant circuit 1 and a binary low temperature detection device to protect refrigerant circuit 2. Each individual refrigerant circuit is disabled when the low temperature condition exists for that circuit. outdoor air damper also operates normally. For two compressor units, the controller responds to low temperature detection by allowing the fan to operate, while disabling the compressor for the faulty circuit. The compressor for the normal circuit continues to operate. The All unit operation is disabled when the heat pump shuts down both circuits, due to low temperature conditions. See Table 3 for more information. Table 3: ZN510 response to low temperature detection diagnostic Description Fan Compressor Operation Operation Damper Operation Low Temperature Detection (Circuit 1) Enabled Circuit 1-Disabled Normal Circuit 2-Normal Operation operation Low Temperature Detection (Circuit 2) Enabled Circuit 1-Normal Operation Normal Circuit 2-Disabled operation Low Temperature Detection (Circuits 1 and 2) Disabled Circuit 1-Disabled Circuit 2-Disabled Closed Note: z The low temperature detection device automatically resets when the heat exchanger temperature returns to normal. However, you must manually reset the low temperature detection diagnostic to clear the diagnostic and restart the unit. Refer to page 28 on how to reset a unit. z If BOP 6 is configured as a generic binary output, the state of the output is not affected by the low temperature detection diagnostic or by other diagnostics. Condensate Overflow A condensate overflow switch detects the condensate condition. The condensate overflow switch is a normally closed device. This switch is physically connected to the binary input 2 (BI 2). When the condensation reaches the trip point, the binary input detects the diagnostic condition. A condensate overflow signal generates a diagnostic which disables the fan, disables all compressors, and closes the 2-position outdoor air damper (when present). The condensate overflow diagnostic does not affect the generic binary output (when present). Note: The condensate overflow switch, located in the condensate pan, automatically resets when the condensation returns to normal levels. However, you must manually reset the controller’s condensate overflow diagnostic to clear the diagnostic and restart the unit. Refer to page 28 on how to reset a unit. Occupancy ZN510 uses the occupancy binary input for two occupancy-related functions. For standalone controllers (any unit not receiving a communicated occupancy request, typically from a building automation 10 system), the occupancy binary input determines the unit’s occupancy based on the hardwired signal. Typically, the signal is a dry set of binary contacts which is either connected to a switch or timeclock contacts. When a hardwired occupancy signal is open, the unit switches to occupied mode (if the occupancy input is configured as normally open). When a hardwired occupancy signal is closed, the controller switches to Unoccupied mode. Unit Operation In Occupied mode, the controller operates according to the occupied setpoints. In Occupied Standby Mode, the unit controller operates according to the Occupied Standby setpoints. When the controller receives a communicated unoccupied request, the controller operates according to the unoccupied setpoints regardless of the state of the hardwired occupancy input. If neither the binary input nor the communicated input is used to select the occupancy mode, the controller defaults to occupied mode because the occupancy binary input (if present) typically is configured as normally open without an occupancy device connected. Table 4: Normally open hardwired input configuration (BI 3) Description Communicated Request Hardwired State Result Standalone NA Open = Occupied Occupied Standalone NA Closed = Unoccupied Unoccupied Communicating Occupied Open = Occupied Occupied Communicating Unoccupied Open = Occupied Unoccupied Communicating Occupied Standby Open = Occupied Occupied Standby Communicating Occupied Closed = Occupied Standby Occupied Standby Communicating Unoccupied Closed = Occupied Standby Unoccupied Communicating Occupied Standby Closed = Occupied Standby Occupied Standby Note: If configured for normally closed, all states are opposite of Table 4. Generic Binary Input Building automation systems can monitor the status of the generic binary input. This input does not affect controller operation. High and Low Pressure Switches The high and low pressure cutout switches are wired in series with the compressor contactor in the unit. The ZN510 controller detects the state of each switch circuit by monitoring the controller’s compressor triac outputs. If either the high pressure switch (HPC) or the low pressure switch (LPC) switch opens, a fault condition occurs. This open circuit prevents the compressor contactor from energizing keeping the compressor from running. The controller automatically detects the fault condition by measuring the compressor triac output signal. By default, when the HPC or LPC switches detect a high or low pressure condition in the refrigerant circuit, the special input detects the diagnostic and disables all compressor operation for that circuit. The unit fan continues to operate, if only one circuit is disabled in a two compressor unit. When the HPC/LPC diagnostic is present on both circuits, the ZN510 shuts off the unit fan and disables 11 unit operation. See Figure 7 for high and low pressure switch. When the refrigerant circuit returns to normal, the HPC and the LPC switches automatically reset. The high or low pressure cutout diagnostic may need to be manually reset to clear the diagnostic and enable compressor operation for the fault circuit. Unit Operation 24 VAC Compr 2 HPC Compr 1 LPC Binary Outputs Figure 7: High and low pressure switch Note: The ZN510 controller includes an automatic diagnostic reset function that allows the controller to automatically recover after a high or low pressure cutout diagnostic. After 30 minutes the controller will reset the diagnostics. Most diagnostics occur due to intermittent water temperature or flow problem. The “smart reset” may eliminate many service calls. 1 2 3 4 5 6 7 Analog Inputs The ZN510 controller has five available analog inputs (AI). These inputs are factory-configured for the following functions: z Zone = Space temperature. z Set = Local setpoint. perature (Circuit 1). z AI 2 = Discharge air tem- perature. Zone Sensor TB3-2 TB3-3 TB3-4 Ground (1TB1-2) Setpoint (1TB1-3) Fan (1TB1-4) 12 Leaving Water Sensor (Circuit) J3-3 J3-2 J3-1 TB3-5 TB3-1 Zone (1TB1-1) See Figure 8 for analog inputs. AI 2 Analog Inputs z AI 1 = Leaving water tem- Discharge Air Sensor AI 1 J3-4 z Fan = Fan mode input. Figure 8: Analog inputs. Unit Operation Space Temperature ZN510 controls the space temperature according to the active space temperature, the active heating/cooling setpoint, and the space temperature control algorithm. The ZN510 controller receives the space temperature from either a wired zone sensor or as a communicated value. When neither a zone sensor nor communicated space temperature is present, the ZN510 controller generates a space temperature failure diagnostic. Note: The ZN510 controller cannot operate without a valid space temperature value (either hardwired or communicated). The space temperature input can communicate timed override ON or CANCEL requests to the ZN510 controller. If the ON button is temporarily pressed, the zone sensor sends a signal to the controller. This signal is then interpreted as a timer override request which places the unit into occupied. The controller uses the timed override request (while the zone is unoccupied) as a request to switch to the Occupied Bypass mode (occupied bypass). This Occupied Bypass mode lasts for the duration of the occupied bypass time, typically 120 minutes. or The controller’s Occupancy mode is determined from either a system level controller or another peer controller. The CANCEL button cancels the timed override request and returned the unit to unoccupied mode. If the CANCEL button is temporarily pressed, the zone sensor sends a signal to the controller. This signal is then interpreted as a timed override cancel which places the unit into unoccupied. Local Setpoint The local setpoint analog input is designed as the local (hardwired) setpoint input. This input cannot be used for any other function. The local input is a resistance input intended for use with Trane zone sensors. If neither a hardwired nor communicated setpoint is present, the controller uses the stored default setpoints: z Occupied setpoints: In the occupied mode, the unit attempts to maintain the space temperature at the active occupied heating or cooling setpoint based on the measured space temperature, the active setpoint, and the proportional/ integral control algorithm. z Occupied standby setpoints: In occupied standby mode, the controller uses the occupied standby cooling and heating setpoints. Because the occupied standby setpoints typically cover a wider range than the occupied setpoints, the ZN510 controller reduces the demand for heating and cooling the space. Also, the outdoor air damper is normally closed during occupied standby mode to further reduce the heating and cooling demands. z Unoccupied setpoints: In unoccupied mode, the unit attempts to maintain the space temperature at the stored unoccupied heating or cooling setpoint based on the measured 13 space temperature, the active setpoint, and the proportional/ integral control algorithm, regardless of the presence of a hardwired or communicated setpoint. Once a valid setpoint is established (through the hardwired input or through communication) and when neither a local setpoint or communicated setpoint is present, the controller generates a setpoint failure diagnostic. When a setpoint failure diagnostic occurs, the controller operates using the default heating and cooling setpoints. These setpoints are factory-configured, but may be changed using the Trane service tool, Rover. The ZN510 controller uses the following validation sequence for the setpoints: 1. Check for a communicated setpoint. If present, validate this setpoint. 2. Check for a hardwired setpoint and validate the setpoint. 3. Use the default setpoint and validate this setpoint. Fan Mode Input The fan mode analog input (Fan) is designed to operate as the fan mode switch input. This input cannot be used for any other function. The fan switch on a Trane zone sensor generates the fan mode signal. The ZN510 controller detects the unique resistance corresponding to each position of the fan switch. By measuring the resistance, the controller determines the requested fan mode. Unit Operation Possible Fan Modes Heat Pump (1-speed) OFF Fan Off Continuous: (Field Modified) AUTO z In occupied mode, the fan runs continuously. In unoccupied mode, the fan cycles OFF when no heating or cooling is required. Cycling: (Factory Default) AUTO z The fan cycles ON and OFF with compressor operation. The ZN510 controller receives the fan mode from either a wired zone sensor or as a communicated valve. When neither a zone sensor nor communicated fan mode are present, the ZN510 controller will default unit operation to AUTO. Note: z A building automation system can also generate a fan mode request and communicate this request to the controller. z If the ZN510 controller does not receive a hardwired or communicated request for the fan mode, the unit recognizes the fan input as AUTO and the fan operates according to the default configuration. Fan Off Delay When the heating output is controlled off, the ZN510 automatically runs the fan ON for an additional 30 seconds to give the fan time to blow off any residual heat. Leaving Water Temperature ZN510 uses analog input 1 (AI 1) as the leaving water temperature input for use with a thermistor. This input (AI 1) is automatically assigned as a leaving water temperature input. As explained in the binary input section, the leaving water temperature input protects the heat exchanger (circuit 1) from low temperatures. The second heat exchanger, present in units with two compressors is protected with a binary low temperature detection device. Based on the application of the unit, circuit operation is terminated when the leaving water temperature falls below 35 F or 20 F. This is set when the unit is ordered. The ZN510 controller compares the measured leaving water temperature to the leaving water temperature low limit value to determine a fault condition. When the measured leaving water temperature is less than the leaving water temperature low limit, the controller generates a Low Temp Detect diagnostic. If the Leaving Water Temp Sensor fails to open or close the controller generates a Leaving Water Temp Failure diagnostic. This disables unit operation. Note: A low temperature detection failure diagnostic for compressor 1 may require you to manually reset the unit to restore compressor operation. Similarly, the ZN510 controller uses a binary low temperature detection device (fixed low limit trip point) to lock-out circuit 2 when a fault condition is detected. 14 See the Diagnostics section on page 28 for information about the automatic diagnostic reset function. Filter Maintenance Timer The controller’s filter maintenance timer is based on the unit fan’s cumulative run hours. The controller compares the fan run time against an adjustable fan run hours limit (maintenance required setpoint time, stored in the controller) and recommends unit maintenance (i.e. changing the filter). Use Rover or BAS system to edit the maintenance required setpoint time. Once the setpoint limit is exceeded the controller generates a filter maintenance timer diagnostic. When the maintenance required setpoint time is zero, the controller disables the diagnostic feature. Discharge Air Temperature Analog input 2 (AI 2) is used as the discharge air temperature input for use with a 10,000 ohm thermistor. Typical factory placement of the thermistor is at the discharge area of the unit. The discharge air temperature sensor does not affect unit operation. The measured temperature is for information only to be read by the building automation system or for troubleshooting unit operation with Rover. Once a valid discharge air temperature signal has been established by the thermistor or communicated and the value is no longer present, the controller generates a discharge air temperature failure diagnostic. This will not disable unit operation. If the sensor returns with a valid temperature, the diagnostic automatically clears Zone Sensor Zone Sensor The ZN510 controller accepts the following zone sensor inputs: values exist, the controller ignores the hardwired space temperature input and uses the communicated value. z Space temperature mea- surement. z Local setpoint (internal or external on the zone sensor). z Fan switch. (Optional) z Timed override (ON and CANCEL). z Communication Jack. If both hardwired and communicated space temperature Internal and External Setpoint Adjustment Zone sensors with an internal or external setpoint adjustment provide the ZN510 controller with a local setpoint (50 to 85 F or 10 to 29.4 C). The internal setpoint adjustment is concealed under the zone sensor’s cover. To reveal the adjustable setpoint wheel, remove the zone sensor cover. The external setpoint (when present) is exposed on the zone sensor’s front cover. When the hardwired setpoint adjustment is used to determine the setpoints, all unit setpoints are calculated based on the hardwired setpoint values, the configured setpoints, and the active mode of the controller. Setpoint Operation The controller has three methods of heating and cooling setpoints operation. See Table 5 for the methods of setpoint operation. Table 5: Methods of setpoint operation. Method Situation used Zone Sensor (with an adjustable hardwired setpoint) A hardwired, adjustable setpoint is connected to the controller. Local setpoints are enabled in the unit configuration. No communicated setpoint is present. Communicated source A setpoint is communicated to the unit controller (typically from a building automation system or a peer controller). If both a hardwired setpoint and a communicated setpoint exist, the controller uses the communicated value. The configuration feature for enabling or disabling the local setpoint does not affect the setpoint handling when communicated setpoints are used. The communicated setpoint always takes priority over the hardwired setpoint, even when the local setpoint is enabled. Stored default setpoints The controller uses the locally stored default heating and cooling setpoints when neither a local hardwired setpoint or communicated setpoint is present. When a building automation system is present, the controller uses the default setpoints when no setpoint is communicated to the controller and no hardwired setpoint exists. The controller uses stored default setpoints when only a local setpoint exists, but the local setpoint is disabled in the configuration of the controller. The controller always uses the stored default (unoccupied) setpoints in unoccupied mode. 15 Zone Sensor Zone Sensor Features Fan Switch (Optional) The zone sensor fan switch provides the controller with an occupied (and occupied standby) fan request signal of OFF or AUTO. If the fan control request is communicated to the controller, the controller ignores the hardwired fan switch input and uses the communicated value. The zone sensor fan switch signal can be enabled or disabled through configuration in the ZN510 controller. ON or CANCEL Buttons Momentarily pressing the ON button during unoccupied mode places the controller in occupied bypass mode for 120 minutes. You can adjust the number of minutes in the unit controller configuration using Trane’s service tool, Rover. The controller remains in occupied standby mode until the override timer expires or until the CANCEL button is pressed. controller). By accessing the communication jack via Rover, entrance to all controllers on the link may be gained. Communication Jack Use the RJ-11 communication jack as the connection point from Rover to the communication link (when the communication jack is wired to the communication link at the Table 6: Zone Sensor Options Part Number: X13510628010 Description: ZONE RT1 10K OHM @ 25 °C ± 2°C R7 1K z Space temperature (0.2 C resolution). z Internal setpoint. z Communication jack. z Vertical case with Trane logo 1 SIGNAL (COMMON) VR1 200 ADJ USTABLE SETPOINT 2 CSP 3 COMM HIGH (+ ) 4 COMM LOW (-) MJ 1 ZONE RT1 10K OHM @ 25 °C ± 2°C Part Number: X13510606010 Description: R7 1K z Space temperature (0.2 C resolution). z External setpoint. z Communication jack. z Vertical case with Trane logo ADJ USTABLE SETPOINT SIGNAL (COMMON) VR1 200 CSP COMM HIGH (+ ) COMM LOW (-) MJ 1 16 5 COMMUNICATIONS J ACK COMMUNICATIONS J ACK 1 2 3 4 5 Zone Sensor Specifications Part Number: X13510606020 Description: z Space temperature (0.2 C resolution). z External setpoint. z ON and CANCEL buttons. z Communication jack. z Vertical case with Trane logo. Part Number: X13510635010 Description: z Space temperature (0.2 C resolution). z External setpoint. z Fan Switch (OFF and AUTO). z ON and CANCEL buttons. z Communication jack. z Vertical case with Trane logo. ON 17 Heating or Cooling Control Mode Operation Heating or Cooling Operation For both single and dual compressor operation, the ZN510 controller cycles the compressor(s) on and off to meet heating or cooling zone demands. The controller uses the unit capacity and pulse width modulation (PWM) logic along with minimum on/off timers to determine the operation for compressor 1. With a dual compressor unit, if the desired conditions are not met by controlling only the first compressor, the controller runs compressor 1 continuously and controls compressor 2 according to PWM logic along with the minimum on/off timers. See Table 6 for heat pump heating or cooling operation. Table 7: Heat pump heating or cooling operation* Capacity Unit Between 0 and 50% 0% Single compressor Dual (Two) compressors Between 50 and 100% 100% Compressor OFF continuously. Compressor output is controlled according to pulse width modulation (PWM) logic between 0 and 100%. The controller calculates the compressor on/off times based Compressor ON on PWM logic and heating/cooling capacities. The continuously. compressor is controlled on for longer periods as the capacity increases and shorter periods as the capacity decreases. Both compressors continuously. #1: ON PWM. #2: OFF continuously. OFF #1: ON continuously. #2: ON PWM. Both compressors ON continuously. *Note: No diagnostics present. Certain heat pump configurations may use one or two compressors for cooling control. Heat pumps use reversing valve control to switch between heating and cooling. The controller supports cooling only configurations and heat pump configurations. For heat pump configurations, the unit’s reversing valve is energized in cooling and de-energized in heating. For cooling, the reversing valve output is energized simultaneously with the compressor (compressor 1 in two compressor applications). The reversing valve remains energized until the controller turns on the compressor for heating, simultaneously de-energizing the reversing valve. The reversing valve only changes state when the controller turns on compressor 1. When a power failure occurs, the reversing valve output defaults to the heating (de-energized) state. To reduce noise due to refrigeration migration after compressor shutdown, the controller does not immediately operate the reversing valve. The reversing valve changes state only when the compressor controls on, except when the controller is in off mode. For cooling only configurations, no reversing valve is present and the 18 controller uses the compressor stages for cooling. Compressor Minimum ON/OFF Timers z When fan mode = OFF, Com- pressor minimum ON timers are ignored. z When fan mode = AUTO, Com- pressor minimum OFF timers are observed. z The diagnostic reset ignores the compressor timers ON and OFF. z A communicated compressor disabled or unoccupied signal ignores minimum ON times. Single and Dual Compressor Operation Other Modes Occupancy Operation Unoccupied operation normally is associated with evening hours when the space is vacant. In unoccupied mode, the controller always uses the default unoccupied heating and cooling setpoints stored in the controller. As the unit goes unoccupied, the compressors ON timers are ignored and the compressors are disabled. When ZN510 controls the space to unoccupied mode, the occupant may have the ability to request timed override through the Trane zone sensor’s ON button. Based on the controller or system setup, the controller interprets the request and initiates the occupied setpoint operation. During a timed override, the controller applies the occupied heating and cooling setpoint, but reports the effective occupancy mode as occupied bypass mode. In the occupied bypass mode, a building automation system can detect whether the occupancy mode was overrode. damper normally is open during the occupied mode when the controller turns on the unit fan. The damper is normally closed during: Morning Warm Up The damper (field installed or for the console product) remains closed during morning warm up until the space temperature is within two degrees of the effective heating setpoint. The 2-position outdoor air z certain diagnostic conditions. 19 z occupied mode when the fan is OFF. z warm up/cool down mode. z occupied standby mode. z unoccupied mode. ZN510 keeps the 2-position outside air damper closed on a transition from unoccupied mode to occupied mode as part of the morning warm up sequence. Data Sharing Master Controller ZN510 can send or receive data (such as setpoint, heat/cool mode, fan request and space temperature) to and from other controllers on the communication link, with or without a building automation system. This includes applications where multiple unit controllers share a common space temperature sensor, both for standalone and building automation applications. Master Controller ON CANCEL Zone Sensor Communication Link TB1-2 24V J1 1 2 3 4 5 6 7 TB1-1 COMM GND SET TB3-4 FAN AI 2 J3-3 J3-2 TB3-6 TB3-1 ZONE TB3-3 TB2-5 SW1 COMM J3-4 J3-1 ZONE SEN SOR TB2-6 TB2-4 TB2-3 TB2-2 C OMM MU NICATION TB2-1 TEST SERVICE J2-6 TB3-2 ECHELON FTT-10A C OMM U6 J2-5 ANALOG INPUTS (Actual Size 4.0"x5.5") J2-4 C OMM STATUS ComfortLink 10 X13650607-01 A SW2 J2-2 J2-3 NID: 12-34-56-78-9A-BC J2-1 Com fortLink(tm) 10 BINARY OUTPU TS POWER AI 1 98 0010155 GND BINARY IN PUTS The master controller (the unit controller with the hardwired zone sensor) in peer-to-peer communication can send its zone temperature to one or more slave controllers which allows the slave controllers to track each other’s zone temperature. For these applications, Rover is used in set up of the controller. GND Slave Controller Slave Controller Figure 9: Master/slave setpoint operation for peer-to-peer setup See Figure 9 for Master/Slave setpoint operation for peer-to-peer set up. Setpoint Operation Controllers sharing information peer-to-peer can share a variety of data, including the heating/cooling setpoint (communicated from a master to a slave). The standalone master controller derives its setpoint from either the local hardwired setpoint input or from its default setpoints. Peer-topeer applications often require the use of one hardwired setpoint to be shared across two or more controllers. This can be achieved by wiring the adjustable setpoint (typically included as a part of the Trane zone sensor module) to the controller defined as the master. Trane’s service tool, Rover may be used to set up the master and one or more slaves to share that setpoint. For this application, each communicating controller uses the same setpoint. Note: Each controller derives it’s effective setpoint and default setpoints (including deadbands between setpoints) from the setpoint input (hardwired or communicated). To make sure the peer-to-peer setpoint application results in identical setpoints for each communicating controller, each controller must have exactly the same default setpoints. Simplified Peer-to-Peer (Master/ Slave) Setup To simplify setting up master/slave applications, the controller provides information that groups all necessary shared data into one communication variable. This master/slave variable includes the following information: z Space temperature. z Setpoint. 20 z Heating/cooling mode. z Occupancy. z Fan status. z Unit control algorithm capacity. This information is communicated from the master to the slave to ensure similar unit operation. Use Rover, Trane’s service tool, to set up peer-to-peer applications. Refer to the Rover product literature for more information on setting up applications. Configuration Configurable Parameters Rover, Trane’s service tool, uses the unit type “heat pump” to determine and download unit configuration information, such as the default analog inputs, the default binary inputs, and the default binary output configurations. See Table 7 for default configurations for heat pumps. Table 8: Heat pump heating or cooling operation. Unit Type Heat pump Cooling Source Compressor Heating Source Compressor (none for cooling only units) Compressors 1 (2 for 2-compressor units) Binary Outputs BOP 1: Fan on (normally open) BOP 2: Reversing valve (normally open)* BOP 3: Not used BOP 4: Compressor 1 (normally open) BOP 5: Compressor 2 (normally open)** BOP 6: Outdoor Air Damper (normally open)*** Binary Inputs BI 1: Low temperature detection, circuit 2 (normally closed)* ** BI 2: Condensate overflow (normally closed)† BI 3: Occupancy (normally open) Analog Inputs Zone: Space temperature (0.0 F calibration) Set: Setpoint (0.0 F calibration) Fan: Fan mode AI 1: Leaving water temperature AI 2: Discharge air temperature Fan Fan operation (heating): Cycling Fan operation (cooling): Cycling Fan speed default (heating): On/high Fan speed default (cooling): On/high Fan switch (hardwired): Enabled Setpoints Unoccupied cooling setpoint: 85 F Occupied standby cooling: 78 F Occupied cooling setpoint: 74 F Occupied heating setpoint: 71 F Occupied standby heating: 67 F Unoccupied heating setpoint: 60 F Cooling setpoint high limit: 115 F Cooling setpoint low limit: 40 F Heating setpoint high limit: 115 F Heating setpoint low limit: 40 F Thumbwheel set point: Enabled The heating and cooling setpoint high and low limits only apply to the occupied and occupied standby setpoints. These limits never apply to the unoccupied setpoints. Occupied Bypass Timer 120 minutes Leaving Water Temperature Low Limit Unit specific (20 F ground source or 35 F standard) Location Identifier Unit specific (maximum of 30 characters) The occupied bypass time is used for timed override applications. The timed override timer is maintained in the unit controller. When the timed override is applicable, the controller reports “Occupied Bypass” as its effective occupancy mode. The leaving water temperature low limit is used for freeze protection of circuit 1 on heat pumps. Circuit 2 is protected by a binary low temperature detection device (freezestat) with a fixed trip point. * BOP 2, BI1: Not used on cooling only units. ** BOP 5: Not used on signal compressor unit. *** Configured but not required. † Optional model number dependent 21 Troubleshooting Red Service LED Table 9: Red LED activity Red LED Activity Description LED off continuously when power is applied to the controller. Normal operation. LED on continuously, even when power is applied to the controller. Someone is pressing the service button or the controller has failed. LED flashes once every second. Use Rover, Trane’s service tool, to restore the unit to normal operation or unconfigured. !Warning! Service Button The black Service button on the ZN510 board allows the user to send a service pin message, which allows efficient identification of the unit's location. However, if the Service button is held for more than 10 seconds, the ZN510 will shut down the software application and disable the unit's operation. The only method to restore the unit is through the use of Rover service tool. We strongly suggest that this function only be exercised under the strict direction of factory service personnel. Green Status LED The green LED normally indicates whether the controller is powered on (24 VAC). Table 10: Green LED activity Green LED Activity Description LED on continuously. Power on (normal operation). LED blinks (one blink). Manual output test mode (2-second hold), No diagnostics present. LED blinks (two blinks). Manual output test mode (2-second hold), One or more diagnostics are present. LED blinks (1/4 second on, 1/4 second off for 10 seconds. “Wink” mode. This feature allows the identification of a controller. By sending a request from a device, such as Rover, Trane’s service tool or ZN510 Loop Controller, a request to the controller can be made to “wink” a notification that the controller received the signal. When the zone sensor ON button is held for 10 seconds “Wink” mode is sent from Comfort Link Controller. z Power off. z Abnormal condition. z Test button is pressed. LED off. Yellow Service LED Table 11: Yellow LED activity Yellow LED Activity Description LED off continuously. The controller is not detecting any communication. (Normal for standalone applications). LED blinks. The controller detects communication. (normal for communicating applications, including data sharing). LED on continuously. Abnormal condition. 22 Troubleshooting Manual Output Testing the Heat Pump Configurations The procedure for testing heat pump configurations is: 1. Press and hold the Test button 3. for at least three seconds to start the test mode. 2. The test sequence resets diagnostics and turns off all outputs. Press the Test button several more times (no more than once per second) to advance through the test sequence. Table 12: Test sequence Step Fan BOP 1 Reversing Valve BOP 2 Compr 1 BOP 4 Compr 2 BOP 5 Damper BOP 6 1. Off Off Off Off Off Closed 2. Fan on (At the beginning of step 2, the controller attempts to clear all diagnostics). On Off Off Off Closed 3. Reversing Valve On On Off Off Closed 4. Cool 1 On On On Off Closed 5. Cool 2 On On On On Closed 6. Compressor(s) off This stage helps avoid compressor cooling and heating in sequential steps by turning the On compressors off prior to changing the reversing valve state. Off Off Off Closed 7. Heat 1 On Off On Off Closed 8. Heat 2 On Off On On Closed 9. Outdoor air damper On Off Off Off Open 10. Exit After the outdoor air damper step, the test sequence performs the exit step. This initiates a reset and attempts to return the controller to normal operation. Testing the Heat Pump Configurations The outputs are not subject to minimum times during the test sequence. However, the test sequence only permits one step per second which limits output time. All outputs are exercised regardless what timer they are or are not configured for. For example, single compressor heat pumps function the same as two compressor units. For single compressor units, the cool 2 and heat 2 steps control the appropriate binary outputs, but do not affect unit operation. Reversing valve and damper outputs cycle independent of configuration. Pump Operation for Systems with ZN510 Loop Controller During Unoccupied, the pumps will be OFF but should be energized to test compressor operation. The user must override the pumps either at the ZN510 Loop Controller or by pushing the ON button of the zone sensor. This will send the units to an occupied bypass, which will turn the pumps on prior to operating manual output test. 23 Troubleshooting Questionable Unit Operation Table 13: Fan output does not energize Probable Cause Random start observed. Explanation After power up, the controller always observes a random start from 0 to 25 seconds. The controller remains off until the random start time expires. When power up control wait is enabled (non-zero time), the controller remains off until one of two conditions occurs: Power up control wait. z The controller exits power up control wait once it receives commu- nicated information. z The controller exits power up control wait once the power up control wait time expires. Cycling fan operation. When configured to cycle with capacity, normally the unit fan cycles off with heating or cooling. The heating/cooling sources cycle on or off periodically with the unit fan to provide varying amounts of capacity to the space. Unoccupied operation. Even when the controller is configured for continuous fan operation, the fan normally cycles with capacity during unoccupied mode. While unoccupied, the fan cycles on or off with heating/cooling to provide varying amounts of heating or cooling to the space. Fan mode off. When a local fan mode switch determines the fan operation, the off position controls the unit fan off. Requested mode off. The desired operating mode (such as off, heat and cool) can be communicated to the controller. When off is communicated to the controller, the unit controls the fan off. There is no heating or cooling. Diagnostic present. A specific list of diagnostics affects fan operation. See Diagnostics section on page 27. No power to the controller. If the controller does not have power, the unit fan does not operate. For the ZN510 controller to operate normally, it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have sufficient power or has failed. Unit configuration. The controller must be properly configured based on the actual installed end devices and application. Manual output test. The controller includes a manual output test sequence that may be used to verify output operation and associated output wiring. However, based on the current step in the test sequence, the unit fan may not be on. Refer to the manual output overrides on page 9. Unit wiring. The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal fan operation. 24 Troubleshooting Questionable Unit Operation Table 14: Compressor(s) not running Probable Cause Explanation Normal operation. The controller compressor(s) turn on and off to meet the unit capacity requirements. Requested mode off. The desired operating mode (such as off, heat and cool) can be communicated to the controller. When off is communicated to the controller, the unit shuts off all unit compressor(s). Communicated disable. Numerous communicated requests may disable the compressor, including a compressor enable input. Depending on the state of the communicated request, the unit may disable the compressor. Manual output test. The controller includes a manual output test sequence that may be used to verify output operation and associated output wiring. However, based on the current step in the test sequence, the compressor(s) may not be on. Refer to the manual output overrides on page 9. Diagnostic present. A specific list o f diagnostics affects compressor operation, depending whether the unit is configured as heat pump. For more information, see the Diagnostics section on page 27. Unit configuration. The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does not match the actual end device, the compressor may not work correctly. No power to the controller. If the controller does not have power, the compressor does not operate. For the ZN510 controller to operate normally, a voltage input of 24 VAC must be applied. When the green LED is off continuously, the controller does not have sufficient power or has failed. Unit wiring. The wiring between the controller outputs and the compressor contacts must be present and correct for normal compressor operation. Table 15: Outdoor air damper stays open Probable Cause Explanation Normal operation. The controller opens and closes the outdoor air damper based on the controller’s occupancy mode and fan status. Normally, the outdoor air damper is open during occupied mode when the fan is running and closed during unoccupied mode. Refer to the outdoor air damper section on page 8. Manual output test. The controller includes a manual output test sequence that may be used to verify output operation and associated output wiring. However, based on the current step in the test sequence, the outdoor air damper may not open. Refer to the manual output overrides on page 9. Unit configuration. The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does not match the actual end device, the outdoor air damper may not work correctly. Unit wiring. The wiring between the controller outputs and the compressor contacts must be present and correct for normal damper operation. 25 Troubleshooting Questionable Unit Operation Table 16: Outdoor air damper stays closed Probable Cause Explanation Normal operation. The controller opens and closes the outdoor air damper based on the controller’s occupancy mode and fan status. Normally, the outdoor air damper is open during occupied mode when the fan is running and closed during unoccupied mode. Refer to the outdoor air damper section on page 8. Warm up and cool down. The controller includes both a morning warm-up and cool down sequence to keep the outdoor air damper closed during the transition from unoccupied to occupied. This is an attempt to bring the space under control as quickly as possible. Requested mode off. The desired operating mode (such as off, heat and cool) can be communicated to the controller. When off is communicated to the controller, the unit closes the outside air damper. Manual output test. The controller includes a manual output test sequence that may be used to verify output operation and associated output wiring. However, based on the current step in the test sequence, the outdoor air damper may not be open. Refer to the manual output overrides on page 9. Diagnostic present. A specific list o f diagnostics affects outdoor air damper operation, depending whether the unit is configured as heat pump. For more information, see the Diagnostics section on page 27. Unit configuration. The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does not match the actual end device, the outdoor air damper may not work correctly. No power to the controller. If the controller does not have power, the compressor does not operate. For the ZN510 controller to operate normally, a voltage input of 24 VAC must be applied. When the green LED is off continuously, the controller does not have sufficient power or has failed. Unit wiring. The wiring between the controller outputs and the outdoor air damper must be present and correct for normal outdoor air damper operation. 26 Diagnostics Table 17: ZN510 controller diagnostics Diagnostic Fan Other Outputs Condensate overflow Off Compressors: Off Damper: Closed Low temp detect - Crt 1 Enabled Compressor 1: Off Compressor 2: See note below. Damper: See note below. Low temp detect - Crt 1 Enabled Compressor 1: See note below. Compressor 2: Off Damper: See note below. Low temp detect - Crt 1 and 2 Off Compressor 1: Off Compressor 2: Off Damper: Closed High/low press cutout - Crt 1 Enabled Compressor 1: Off Compressor 2: See note below. Damper: See note below. High/low press cutout - Crt 2 Enabled Compressor 1: See note below. Compressor 2: Off Damper: See note below. High/low press cutout - Crt 1 and 2 Off Compressor 1: Off Compressor 2: Off Damper: Closed Space temperature failure* Off Compressor(s): Off Damper: Closed Leaving water temp failure Enabled Discharge air temp failure* Enabled Compressor(s): No action Damper: No Action Maintenance required (example: Filter Status) Enabled Compressor(s): No action Damper: No Action Local setpoint failure* Enabled Compressor(s): Enabled Damper: Enabled Local fan mode failure* Enabled Compressor(s): Enabled Damper: Enabled Invalid unit configuration Disabled Compressor(s): Disabled Damper: Disabled Compressor 1: Off Compressor 2: See note below. Damper: See note below. High/low pressure cutout and low temperature detection diagnostics for heat pump configurations isolate each circuit and independently disable compressor operation. For single compressor units, these diagnostics cause the compressor to shut down, the unit fan to be controlled off, and the outdoor air damper to be closed (when present). When BOP 6 is configured as a generic binary output, BOP 6’s state is unaffected by all unit diagnostics. * Note: Non-latching diagnostics automatically reset when the input is present and valid. 27 Diagnostics Translating Multiple Diagnostics The controller senses and records each diagnostic independently of the diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they occur. Resetting Diagnostics 1. Automatically by the controller. 2. 3. 4. By initiating a manual output test at the controller. By cycling power to the controller. Through a building automation system such as ZN510 Loop Controller. 5. Through Rover, Trane’s service tool. 6. Through any communicating device with the ability to access the controller’s alarm reset input. Automatic Diagnostic Reset The ZN510 controller includes an automatic diagnostic reset function. This function attempts to automatically recover a unit when the following diagnostics occur: z Low temperature detection, Circuit 1 z Low temperature detection, Circuit 2 z Low temperature detection, Circuit 1 and 2 z High/low pressure cutout, Circuit 1 z High/low pressure cutout, z High/low pressure cutout, Circuit 1 and 2 When one or more of these special diagnostics occurs, the controller responds to the diagnostic as defined in the table 17 on page 27. After the controller detects the first special diagnostic (listed on page 27), the unit waits 30 minutes before invoking the automatic diagnostic reset function. The automatic diagnostic reset function clears all special diagnostics and attempts to restore the controller to normal operation. The controller resumes normal operation until another diagnostic occurs. If a special diagnostic occurs within 24 hours after an automatic diagnostic reset, the diagnostic must be manually reset. Cycling Power When the 24 VAC power to the controller has been turned off, the unit cycles through a power up sequence. By default, the controller attempts to reset all diagnostics at power up. Diagnostics present at power up and those that occur after power up are handled according to the table on page 27. Building Automation System (CLC) Some building automation systems can reset diagnostics in the ZN510 controller. The ZN510 Loop Controller can reset diagnostics in the ZN510 Controller. For complete information, refer to the building automation system product literature. Circuit 2 28 Rover Service Tool Trane’s service tool, Rover, can reset diagnostics in the ZN510 controller. For complete information about Rover, refer to the Rover product literature. Alarm Reset Any device that can communicate alarm reset information can reset diagnostics in the ZN510 controller. ZN510 Controller Replacement Disconnect power or disable the circuit breaker to unit. 1. 2. Remove bad or questionable ZN510 Controller. 3. Install controller in the unit with the heatsink placement at the top of the control box. (See page 32). 4. Connect the power to the ZN510 ONLY. (TB1-1 & TB1-2 on ZN510) 5. Connect Rover and properly configure the controller, unless a previously configured board is purchased. 6. Power down. 7. Connect the remaining input and output wiring to the controller. 8. Reapply power. 9. Complete sequence 7 and 8 above in the installation section of this manual. 10. Refer to BAS manual for instructions on how to install the new ZN510 into BAS system. Wiring Diagram 29 Wiring Diagram 30 Hardware Specifications Specifications Board Dimensions Height: 4” (102 mm) Width: 5-1/2” (140 mm) Depth: 2-1/4” (57mm) Operating Environment 32 to 140 F (0 to 60 C) 5 to 95% non-condensing Storage Environment -40 to 185 F (-40 to 85 C) 5 to 95% non-condensing Power Requirements 18 to 32 VAC (24 VAC nominal) 50 or 60 Hz 300 mA Agency Listings UL and CUL 916 Energy Management System Agency Compliance IEC 1000-4-2 (ESD), IEC 1000-4-4 (EFT), IEC 1000-4-5 (Surge), FCC Part 15, Class A. Input/Output Summary z Three binary inputs. z Six binary outputs only five are used. z Five analog inputs. z Timed override ON and CANCEL. z Comm5 communication. Heat sink is mounted to the top of the control box 4” 5 1/2” Figure 10: ZN510 Circuit Board 31 Hardware Specifications Table 18: Binary Inputs Description Terminals Function Binary Input 1 J2-1 J2-2 Input Binary Input 2 J2-3 24 VAC J2-4 Input J2-5 24 VAC J2-6 Input Binary Input 3 24 VAC Table 19: Binary Outputs Description Terminals Output Rating Load Energized Load De-energized Binary Output 1 J1-1 12 VA 1 VAC RMS (typical) 24 VAC RMS (typical) Binary Output 2 J1-2 12 VA 1 VAC RMS (typical) 24 VAC RMS (typical) Binary Output 3 J1-4 NOT USED Binary Output 4 J1-5 12 VA 1 VAC RMS (typical) 24 VAC RMS (typical) Binary Output 5 J1-6 12 VA 1 VAC RMS (typical) 24 VAC RMS (typical) Binary Output 6 J1-7 12 VA 1 VAC RMS (typical) 24 VAC RMS (typical) Table 20: Analog Inputs Description Terminals Function Range Zone TB3-1 Zone temperature input 5 to 122 F (-15 to 50 C) Ground TB3-2 Analog ground NA Set TB3-3 Setpoint input 40 to 115 F (4.4 to 46.1 C) Fan TB3-4 Fan switch input OFF = 4821 to 4919 Ohms AUTO = 2297 to 2342 Ohms Ground TB3-6 Analog ground NA Analog Input 1 J3-1 Leaving water temperature -40 to 212 F (-40 to 100 C) J3-2 Analog ground NA J3-3 Discharge air temperature -40 to 212 F (-40 to 100 C) J3-4 Analog ground Analog Input 2 NA 32
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Create Date : 2005:02:21 21:50:39Z Modify Date : 2005:02:21 16:08:03-06:00 Page Count : 32 Creation Date : 2005:02:21 21:50:39Z Mod Date : 2005:02:21 16:08:03-06:00 Producer : Acrobat Distiller 5.0.5 (Windows) Metadata Date : 2005:02:21 16:08:03-06:00 Page Mode : UseOutlines Page Layout : SinglePageEXIF Metadata provided by EXIF.tools