Installation Operation Maintenance Packaged Heat Pump Model Number WC*150B***G* WC*200B***G* December 2004 WC*155B***G* WC*240B***G* WC*180B***G* WC-IOM-7 Warnings and Cautions Warnings and Cautions appear at appropriate sections throughout this literature. Read these carefully. NOTICE: WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. Indicates a situation that may result in equipment or property-damage only accidents. NOTICE: Overview of Manual Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel. This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment. Model Number Description All products are identified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided below. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit. When ordering replacement parts or requesting service, be sure to refer to the specific model number and serial number printed on the unit nameplate. © 2008 Trane All rights reserved WC-IOM-7 WARNING Contains Refrigerant! System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage. WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. NOTICE Equipment Damage From Ultraviolet (UV) Lights! The manufacturer does not recommend field installation of ultraviolet lights in its equipment for the intended purpose of improving indoor air quality. High intensity C-band ultraviolet light is known to severely damage polymer (plastic) materials and poses a personal safety risk to anyone exposed to the light without proper personal protective equipment. Polymer materials commonly found in HVAC equipment that may be susceptible include insulation on electrical wiring, fan belts, thermal insulation, various fasteners and bushings. Degradation of these materials can result in serious damage to the equipment. The manufacturer accepts no responsibility for the performance or operation of our equipment in which ultraviolet devices were installed outside of the manufacturer’s factory or its approved suppliers. WC-IOM-7 • Packaged Heat Pump 3 Contents Contents Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compressor Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Economizer Control Actuator ReliaTel™ Control . . . . . . . . . . . . . . . . . . . . . . . RTCI -- ReliaTel™ Trane Communication Interface (Optional) . . . . . . . . . . . . . RLCI - ReliaTel™ LonTalk Communication Interface (Optional) . . . . . . . . . . . . RTOM – ReliaTel™ Options Module (Optional) . . . . . . . . . . . . . . . . . . . . . . . . 7 7 7 7 7 8 8 System Input Devices & Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Supply Fan Failure Input (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Clogged Filter Switch (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Low Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 High Pressure Control (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Horizontal Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Unit Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Factory Installed Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electric Heat Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Low Voltage Wiring (AC & DC) Requirements . . . . . . . . . . . . . . . . . . . . . . . . Condensate Drain Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Filter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Installed Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main Unit Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Smoke Detector Customer Low Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . Space Temperature Averaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compressor Crankcase Heaters (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . ReliaTel Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 21 21 21 22 22 22 22 23 23 23 24 28 30 32 33 34 Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Test Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Verifying Proper Air Flow (Units with Belt Drive Indoor Fan) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Economizer Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compressor Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heating Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Final System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 38 39 40 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Fan Belt Adjustment - Belt Drive Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Monthly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 4 WC-IOM-7 Contents Cooling Season . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Heating Season . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Final Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 ReliaTel Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Status Checkout Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Method 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Resetting Cooling and Heating Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable & Digital Zone Sensor Test . . . . . . . . . . . . . . . . . . . . . . . . . . ReliaTel Refrigeration Module (RTRM) Default Chart . . . . . . . . . . . . . . . . . . . 47 48 49 49 50 53 54 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Heat Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WCZ, WCY, WCX, WCC, WCD, WCH, WCM, WCP and WSC (Parts Only). . . . Models Less Than 20 Tons for Commercial Use* . . . . . . . . . . . . . . . . . . . . . . Heat Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard Equipment Warranty Terms and Conditions . . . . . . . . . . . . . . . . . . Commercial Equipment Warranty and Liability . . . . . . . . . . . . . . . . . . . . . . . Models Larger that 20 Tons for Commercial Use* . . . . . . . . . . . . . . . . . . . . WC-IOM-7 57 57 57 58 58 58 58 5 Model Number Description W C D 1 5 0 C 3 0 0 B A 1 2 3 4 5 6 7 8 9 10 11 12 Digits 1, 2 - Product Type Digit 8 - Electrical characteristics WC = Packaged cooling, electric heat 3 = 208-230/60/3 WF = With factory installed options 4 = 460/60/3 D = 400/50/3 Digit 3 - Airflow Configuration T = 380/60/3 D = Downflow W = 575/60/3 H = Horizontal Digit 9, 10 - Factory installed options Digit 4, 5, 6 - Nominal gross cooling capacity (MBh) 00 = No factory installed options 150 = 12 1/2 tons standard efficiency 0A = Factory-installed economizer 180 = 15 tons standard efficiency 0B = Oversized motor 240 = 20 tons standard efficiency 0C = Downflow economizer/oversized motor 0F = Trane communications interface (TCI) Digit 7 - Major development sequence 0G = Downflow economizer/TCI Digit 11 - Minor design sequence Digit 12 - Service digit 6 WC-IOM-7 General Information Unit Nameplate A Mylar unit nameplate is located on the unit’s corner support next to the control box. It includes the unit model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent unit data. Compressor Nameplate The nameplate for the compressors are located on the side of the compressor. Unit Description Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation. The condenser coils are aluminum fin, mechanically bonded to copper tubing. Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection. The ReliaTel™ Control Module is a microelectronic control system that is referred to as “Refrigeration Module” (RTRM). The acronym RTRM is used extensively throughout this document when referring to the control system network. This module through Proportional/Integral control algorithms perform specific unit functions that governs unit operation in response to; zone temperature, supply air temperature, and/or humidity conditions depending on the application. The stages of capacity control for these units are achieved by starting and stopping the compressors. The RTRM is mounted in the control panel and is factory wired to the respective internal components. The RTRM receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for cooling. Economizer Control Actuator ReliaTel™ Control The ECA monitors the mixed air temperature, return air temperature, minimum position setpoint (local or remote), power exhaust setpoint, CO2 setpoint, CO2, and ambient dry bulb/enthalpy sensor or comparative humidity (return air humidity against ambient humidity) sensors, if selected, to control dampers to an accuracy of +/- 5% of stroke. The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch pounds of torque and is powered by 24 VAC. RTCI -- ReliaTel™ Trane Communication Interface (Optional) This module is used when the application calls for an ICSTM building management type control system. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or WC-IOM-7 • Packaged Heat Pump 7 General Information ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary. RLCI - ReliaTel™ LonTalk Communication Interface (Optional) This module is used when the application calls for an ICSTM building management type control system that is LonTalk. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary. RTOM – ReliaTel™ Options Module (Optional) The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, supply air tempering, Frostat™ and smoke detector. Refer to system input devices and functions for operation. System Input Devices & Functions The RTRM must have a zone sensor or thermostat input in order to operate the unit. The flexibility of having several mode capabilities depends upon the type of zone sensor or thermostat selected to interface with the RTRM. The descriptions of the following basic Input Devices used within the RTRM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit’s electrical schematic for the specific module connections. The following controls are available from the factory for field installation. Supply Fan Failure Input (Optional) The Fan Failure Switch can be connected to sense indoor fan operation: FFS (Fan Failure Switch) If air flow through the unit is not proven by the differential pressure switch connected to the RTOM (factory set point 0.07 “ w.c.) within 40 seconds nominally, the RTRM will shut off all mechanical operations, lock the system out, send a diagnostic to ICS, and the SERVICE output will flash. The system will remain locked out until a reset is initiated either manually or through ICS. Clogged Filter Switch (Optional) The unit mounted clogged filter switch monitors the pressure differential across the return air filters. It is mounted in the filter section and is connected to the RTOM. A diagnostic SERVICE signal is sent to the remote panel if the pressure differential across the filters is at least 0.5" w.c. The contacts will automatically open when the pressure differential across the filters decreases to approximately 0.4" w.c. The clogged filter output is energized when the supply fan is operating and the clogged filter switch has been closed for at least 2 minutes. The system will continue to operate regardless of the status of the filter switch. 8 Packaged Heat Pump • WC-IOM-7 General Information Compressor Disable (CPR1/2) This input incorporates the low pressure control (LPC) of each refrigeration circuit and can be activated by opening a field supplied contact installed on the LTB. If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close. If four consecutive open conditions occur during the first three minutes of operation, the compressor for that circuit will be locked out, a diagnostic communicated to the remote panel (if installed), and a manual reset will be required to restart the compressor. Low Pressure Control ReliaTel Control When the LPC is opened for 1 continuous second, the compressor for that circuit is turned off immediately. The compressor will not be allowed to restart for a minimum of 3 minutes. If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, a diagnostic communicated to ICSTM if applicable, and a manual reset will be required to restart the compressor. High Pressure Control (Optional) ReliaTel Control The high pressure controls are wired in series between the compressor outputs on the RTRM and the compressor contactor coils. If the high pressure control switch opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out. On dual circuit units, if the high pressure control opens, the compressor on the affected circuit is locked out. A manual reset for the affected circuit is required. Power Exhaust Control (Optional) The power exhaust fan is started whenever the position of the economizer dampers meets or exceed the power exhaust setpoint when the indoor fan is on. The setpoint panel is located in the return air section and is factory set at 25%. WC-IOM-7 • Packaged Heat Pump 9 General Information Lead/Lag Control (Dual Circuit Only) Lead/Lag is a selectable input located on the RTRM. The RTRM is configured from the factory with the Lead/Lag control disabled. To activate the Lead/Lag function, simply cut the wire connected to J3-8 at the RTRM. When it is activated, each time the designated lead compressor is shut off due to the load being satisfied, the lead compressor or refrigeration circuit switches. When the RTRM is powered up, i.e. after a power failure, the control will default to the number one circuit compressor. Zone Sensor Module (ZSM) (BAYSENS007B) This electronic sensor features three system switch settings (Heat, Cool, and Off) and two fan settings (On and Auto). It is a manual changeover control with single setpoint. (Cooling Setpoint Only) Zone Sensor Module (ZSM) (BAYSENS009B) This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS017B. Zone Sensor (BAYSENS011B) This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LED’s. It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS017B. Programmable Zone Sensor - BAYSENS019B This 7 day programmable sensor features 2, 3 or 4 periods for Occupied or Unoccupied programming per day. If the power is interrupted, the program is retained in permanent memory. If power is off for an extended period of time, only the clock and day may have to be reset. The Zone Sensor allows selection of 2, 3 or 4 system modes (Heat, Cool, Auto, and Off), two fan modes (On and Auto). It has dual temperature selection with programmable start time capability. The occupied cooling set point ranges between 45 and 98 degrees Fahrenheit. The heating set point ranges between 43 and 96 degrees Fahrenheit. A liquid crystal display (LCD) displays zone temperature, temperature set points, day of the week, time, and operational mode symbols. The Option Menu is used to enable or disable applicable functions, i.e.; Morning Warm-up, Economizer minimum position override during unoccupied status, Fahrenheit or Centigrade, Supply air tempering, Remote zone temperature sensor, 12/24 hour time display, Smart fan, and Computed recovery. 10 Packaged Heat Pump • WC-IOM-7 General Information Remote Zone Sensor (BAYSENS013C) This electronic sensor features remote zone sensing and timed override with override cancellation. It is used with a Trane Integrated ComfortTM building management system. Remote Zone Sensor (BAYSENS014C) This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated ComfortTM building management system. Remote Zone Sensor (BAYSENS016A) This bullet type temperature sensor can be used for; outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered. Wiring procedures vary according to the particular application and equipment involved. Refer to the unit’s wiring diagrams for proper connections. Remote Zone Sensor (BAYSENS017B) This electronic sensor can be used with BAYSENS006B, 008B, 010B, 019B Remote Panels. When this sensor is wired to a BAYSENS019B Remote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details. High Temperature Sensor (BAYFRST001A) This sensor connects to the RTRM Emergency Stop Input on the LTB and provides high limit “shutdown” of the unit. The sensor is used to detect high temperatures due to fire in the air conditioning or ventilation ducts. The sensor is designed to mount directly to the sheet metal duct. Each kit contains two sensors. The return air duct sensor (X1310004001) is set to open at 135°F. The supply air duct sensor (X1310004002) is set to open at 240°F. The control can be reset after the temperature has been lowered approximately 25°F below the cutout setpoint. Evaporator Frost Control This input incorporates the Frostat™ control (FOS) mounted in the indoor coil and can be activated by closing a field supplied contact installed in parallel with the FOS. If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 5 continuous seconds during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the FOS close. WC-IOM-7 • Packaged Heat Pump 11 General Information Smoke Detector Sensor (Optional) This sensor is only applicable on units equipped with a RTOM. It provides high limit “shutdown” of the unit and requires a manual reset. The sensor is used to detect smoke due to fire in the air conditioning or ventilation ducts. Important: The supply and return air smoke detectors are designed to shut off the unit if smoke is sensed in the supply air stream or return air stream. This function is performed by sampling the airflow entering the unit at the return air opening. Follow the instructions provided below to assure that the airflow through the unit is sufficient for adequate sampling. Failure to follow these instructions will prevent the smoke detectors from performing it's design function. Important: Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required. Note: Important! Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit. In order for the supply air smoke detector or return air smoke detector to properly sense smoke in the supply air stream or return air stream, the air velocity entering the smoke detector unit must be between 500 and 4000 feet per minute. Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables. Unit Inspection As soon as the unit arrives at the job site: • Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data). • Verify that the power supply complies with the unit nameplate specifications. • Visually inspect the exterior of the unit, including the roof, for signs of shipping damage. • Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans. • If concealed damage is discovered, notify the carrier’s terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days. Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. 12 Packaged Heat Pump • WC-IOM-7 General Information Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. • Notify the appropriate sales representative before installing or repairing a damaged unit. WARNING Fiberglass Wool Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation. Precautionary Measures • Avoid breathing fiberglass dust. • Use a NIOSH approved dust/mist respirator. • Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection. • Wash clothes separately from other clothing: rinse washer thoroughly. • Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations. First Aid Measures • Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention. • Skin Contact - Wash affected areas gently with soap and warm water after handling. Storage Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if: 1. the unit is stored before it is installed; or, 2. the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for start-up. Note: Do not use the unit’s heater for temporary heat without first completing the start-up procedure detailed under “Starting the Unit”. WC-IOM-7 • Packaged Heat Pump 13 General Information The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components. Unit Clearances Figure 1 illustrates the minimum operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency. Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust and economizer airflows, or recirculation of hot condenser air. 14 Packaged Heat Pump • WC-IOM-7 Unit Dimensions Figure 1. Typical Installation Clearances for Single & Multiple Unit Applications WC-IOM-7 • Packaged Heat Pump 15 Unit Dimensions 16 Figure 2. Unit Dimensional Data 12 1/2 Ton, 15 Ton Figure 3. Roof Curb Dimensional Data 12 1/2 Ton, 15 Ton Packaged Heat Pump • WC-IOM-7 Unit Dimensions Figure 4. Unit Dimensional Data 20 Ton Figure 5. Roofcurb Dimensional Data 20 Ton WC-IOM-7 • Packaged Heat Pump 17 Unit Dimensions 18 Figure 6. Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Figure 7. Horizontal Duct Dimensional Data 20 Ton Packaged Heat Pump • WC-IOM-7 Unit Dimensions WARNING Heavy Objects! Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property-only damage. Failure to properly lift unit may result in death or serious injury. See details below. WARNING Improper Unit Lift! Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage. Table 1. Typical weights and point loading data Corner Weights (lbs.) Unit Description Center of Gravity (in.) Net Weight A B C D Length Width WC*150B 1375 465 344 231 311 46 29 WC*155B 1412 547 638 231 343 43 27 WC*180B 1412 547 638 231 343 43 27 WC*200B 1916 640 497 340 438 51 34 WC*240B 1916 640 497 340 438 51 34 Note: Corner weights are given for information only. Unit is to be supported continuously by a curb or equivalient frame support. Figure 8. WC-IOM-7 • Packaged Heat Pump Rigging and center of gravity data 19 Unit Dimensions Rigging Refer to Figure 8 and Table 1 for typical unit operating weights riffing before proceeding. 1. Remove the shipping crate from around the unit. Do not remove the crating from the top of the unit. 2. Rig the unit as shown in Figure 8. Attach adequate strength lifting slings to all four lifting brackets in the unit base rail. Do not use cables, chains, or slings except as shown. 3. Install a lifting bar, as shown in Figure 8, to protect the unit and to facilitate a uniform lift. The minimum distance between the lifting hook and the top of the unit should be 7 feet. 4. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments. 5. Lift the unit and position it into place. 6. Downflow units; align the base rail of the unit with the curb rail while lowering the unit onto the curb. Make sure that the gasket on the curb is not damaged while positioning the unit. 20 Packaged Heat Pump • WC-IOM-7 Installation Foundation Horizontal Units If the unit is installed at ground level, elevate it above the snow line. Provide concrete footings at each support location with a “full perimeter” support structure or a slab foundation for support. Refer to Table 1 on page 19 for the unit’s operating and point loading weights when constructing a footing foundation. If anchoring is required, anchor the unit to the slab using hold down bolts or isolators. Isolators should be installed to minimize the transmission of vibrations into the building. For rooftop applications, ensure the roof is strong enough to support the combined unit and support structural weight. Refer to Table 1 on page 19 for the unit operating weights. If anchoring is required, anchor the unit to the roof with hold-down bolts or isolators. Check with a roofing contractor for proper waterproofing procedures. Ductwork Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure. When attaching the ductwork to the unit, provide a water- tight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork. All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed. Note: For sound consideration, cut only the holes in the roof deck for the ductwork penetrations. Do not cut out the entire roof deck within the curb perimeter. If a Curb Accessory Kit is not used: 1. The ductwork can be attached directly to the factory-provided flanges around the unit’s supply and return air openings. Be sure to use flexible duct connections at the unit. 2. For “built-up” curbs supplied by others, gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges. General Unit Requirements The checklist listed below is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint the installing WC-IOM-7 • Packaged Heat Pump 21 Installation personnel with what is required in the installation process. It does not replace the detailed instructions called out in the applicable sections of this manual. • Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representative. • Verify correct model, options and voltage from nameplate. • Verify that the installation location of the unit will provide the required clearance for proper operation. • Assemble and install the roof curb (if applicable). Refer to the latest edition of the curb installers guide that ships with each curb kit. • Fabricate and install ductwork; secure ductwork to curb. • Rigging the unit. • Set the unit onto the curb; check for levelness. • Ensure unit-to-curb seal is tight and without buckles or cracks. • Install and connect a condensate drain line to the evaporator drain connection. Factory Installed Economizer • Ensure the economizer has been pulled out into the operating position. Refer to the economizer installers guide for proper position and setup. • Install all access panels. Main Electrical Power Requirements • Verify that the power supply complies with the unit nameplate specifications. • Inspect all control panel components; tighten any loose connections. • Connect properly sized and protected power supply wiring to a fieldsupplied/installed disconnect switch and to the main power terminal block (HTB1) in the unit control panel. • Install proper grounding wires to an earth ground. Note: All field-installed wiring must comply with NEC and applicable local codes. Electric Heat Requirements • Verify that the power supply complies with the electric heater specifications on the unit and heater nameplate. • Inspect the heater junction box and control panel; tighten any loose connections. • Check electric heat circuits for continuity. Low Voltage Wiring (AC & DC) Requirements • 22 Install the zone thermostat, with or without switching subbase. Packaged Heat Pump • WC-IOM-7 Installation • Connect properly sized control wiring to the proper termination points between the zone thermostat and the unit control panel. Condensate Drain Configuration An evaporator condensate drain connection is provided on each unit. Refer to Unit Dimensions for the appropriate drain location. A condensate trap must be installed at the unit due to the drain connection being on the “negative pressure” side of the fan. Install the P-Trap using the guidelines in Figure 9. A condensate drain line must be connected to the P-Trap. Pitch the drain lines at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible double-trap condition which could result in condensate backup due to “air lock”. Figure 9. Condensate Trap Installation Filter Installation Each unit ships with 2 inch filters installed. The quantity of filters is determined by unit size. Access to the filters is obtained by removing the indoor fan access panel. Refer to the unit Service Facts (shipped with each unit) for filter requirements. Note: Do not operate the unit without filters. Field Installed Power Wiring An overall dimensional layout for the standard field installed wiring entrance into the unit is illustrated in Unit Dimensions. To insure that the unit’s supply power wiring is properly sized and installed, follow the guidelines outlined below. WC-IOM-7 • Packaged Heat Pump 23 Installation Note: All field installed wiring must conform to NEC guidelines as well as State and Local codes. Verify that the power supply available is compatible with the unit’s nameplate ratings. The available supply power must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the power supply to the unit. NOTICE Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage. Failure to do so may cause damage to the equipment. Note: If the unit is not equipped with an optional factory installed nonfused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). Main Unit Power Standard Wiring The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate. 1. If the unit is not equipped with an optional factory installed nonfused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). 2. Location of the applicable electrical service entrance is illustrated in Unit Dimensions. Complete the unit’s power wiring connections onto either; the main terminal block HTB1 inside the unit control panel, the factory mounted nonfused disconnect switch (UCD) or circuit breaker (UCB), or the electric heat terminal block. Refer to the customer connection diagram that shipped with the unit for specific termination points. 3. Provide proper grounding for the unit in accordance with local and national codes. Optional TBUE Wiring (Through the Base Electrical Option) 1. 24 Location of the applicable electrical service is illustrated in the following illustration. Refer to the customer connection diagram that is shipped with the unit for specific termination points. The termination points, depending on the customer option selected would be a factory mounted nonfused disconnect switch (UDC) or circuit breaker (UCB). Packaged Heat Pump • WC-IOM-7 Installation 2. Provide proper grounding for the unit in accordance with local and national codes. Figure 10. Field Installed Control Wiring An overall layout of the various control options available with the required number of conductors for each control device is illustrated in Figure 8. Note: All field wiring must conform to NEC guidelines as well as state and local codes. Control Power Transformer The 24 volt control power transformers are to be used only with the accessories called out in this manual. Transformers rated greater than 50 VA are equipped with internal circuit breakers. If a circuit breaker trips, turn “Off” all power to the unit before attempting to reset it. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. WC-IOM-7 • Packaged Heat Pump 25 Installation The transformer is located in the control panel. The circuit breaker is located on the left side of the transformer and can be reset by pressing in on the black reset button. Controls using 24 VAC Before installing any connecting wiring, refer to Unit Dimensions for the electrical access locations provided on the unit and Table 2 for AC conductor sizing guidelines, and; 1. Use copper conductors unless otherwise specified. 2. Ensure that the AC control wiring between the controls and the unit’s termination point does not exceed three (3) ohms/conductor for the length of the run. Note: Resistance in excess of 3 ohms per conductor may cause component failure due to insufficient AC voltage supply. 3. Be sure to check all loads and conductors for grounds, shorts, and miswiring. 4. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring. 5. Route low voltage wiring per illustrations on Figure 11. Table 2. Electromechanical Thermostat 24V AC conductors with ReliaTel™ Distance from Unit to Control Recommended Wire Size 000 - 460 feet 18 gauge 000 - 140 m .75 mm2 461 - 732 feet 16 gauge 141 - 223 m 1.3 mm2 733 - 1000 feet 14 gauge 224 - 305 m 2.0 mm2 Controls using DC Analog Input/Outputs (Standard Low Voltage Multiconductor Wire) Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to Unit Dimensions for the electrical access locations provided on the unit. 1. 26 Table 3 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a DC analog input\output signal to the unit. Packaged Heat Pump • WC-IOM-7 Installation Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls. 2. Ensure that the wiring between controls and the unit’s termination point does not exceed two and a half (2.5) ohms/conductor for the length of the run. 3. Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires. Table 3. DC Conductors Zone Sensor Module wiring Distance from Unit to Control Recommended Wire Size 0 - 150 feet 22 gauge 0 - 45.7 m .33 mm2 151 - 240 feet 20 gauge 46 - 73.1 m .50 mm2 241 -385 feet 18 gauge 73.5 - 117.3 m .75 mm2 386 - 610 feet 16 gauge 117.7 - 185.9 m 1.3 mm2 611 - 970 feet 14 gauge 186.2 - 295.7 m 2.0 mm2 Figure 11. Reliatel conventional thermostat field wiring diagram RTRM WC-IOM-7 • Packaged Heat Pump 27 Installation Smoke Detector Customer Low Voltage Wiring When interlocking System Sensor smoke detectors together, all of the detectors must be powered from the same power supply. If multiple smoke detectors are required, all detectors must be disconnected from the HVAC unit power supply and connected together from another single source supply. Note: Do not interconnect smoke detectors together that have separate power supplies. Do not exceed ten smoke detectors on one power supply. Note: Multiple System Sensor smoke detectors are connected together using terminals 1 and 12 on each detector. If you have supply and return smoke detectors in all HVAC units, you can connect a maximum of 5 HVAC units (10 detectors) up to one power supply. See the following field wiring example. If you have more than 5 HVAC units, you can connect all the supply detectors together on one power supply (up to 10 HVAC units), and all the return detectors together (up to 10 HVAC units) on another power supply. See the following field wiring example. Figure 12. Smoke detector wiring Up to 5 HVAC units More than 5 HVAC units 28 Packaged Heat Pump • WC-IOM-7 Installation Figure 13. Typical field wiring diagrams for optional controls (ReliaTel™ only) WC-IOM-7 • Packaged Heat Pump 29 Installation Space Temperature Averaging Space temperature averaging is accomplished by wiring a number of remote sensors in a series/parallel circuit. Using the BAYSENS016* or BAYSENS017*, at least four sensors are required to accomplish space temperature averaging. Example #1 illustrates two series circuits with two sensors in each circiut wired in parallel. The square of any number of remote sensors is required. Example #2 illustrates three sensors squared in a series/parallel circuit. Using BAYSENS032*, two sensors are required to accomplish space temperature averaging. Example #3 illustrates the circuit required for this senor. Table 4 lists the temperature versus resistance coefficient for all sensing. Figure 14. 30 Packaged Heat Pump • WC-IOM-7 Installation Table 4. Temperature vs. Resistance Temperature Degrees F° Degrees C° Nominal Resistance -20° -28.9° 170.1 K - Ohms -15° -26.1° 143.5 K - Ohms -10° -23.3° 121.4 K - Ohms -5° -20.6° 103.0 K - Ohms 0° -17.8° 87.56 K - Ohms 5° -15.0° 74.65 K - Ohms 10° -12.2° 63.80 K - Ohms 15° -9.4° 54.66 K - Ohms 20° -6.7° 46.94 K - Ohms 25° -3.8° 40.40 K - Ohms 30° -1.1° 34.85 K - Ohms 35° 1.7° 30.18 K - Ohms 40° 4.4° 26.22 K - Ohms 45° 7.2° 22.85 K - Ohms 50° 10.0° 19.96 K - Ohms 55° 12.8° 17.47 K - Ohms 60° 15.6° 15.33 K - Ohms 65° 18.3° 13.49 K - Ohms 70° 21.1° 11.89 K - Ohms 75° 23.9° 10.50 K - Ohms 80° 26.7° 9.297 K - Ohms 85° 29.4° 8.247 K - Ohms 90° 32.2° 7.330 K - Ohms 95° 35.0° 6.528 K - Ohms 100° 37.8° 5.824 K - Ohms Use the checklist provided below in conjunction with the “General Unit Requirements” checklist to ensure that the unit is properly installed and ready for operation. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. • Check all electrical connections for tightness and “point of termination” accuracy. • Verify that the condenser airflow will be unobstructed. • Verify that the condenser fan and indoor blower turn freely without rubbing and are properly tightened on the shafts. WC-IOM-7 • Packaged Heat Pump 31 Installation • Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the maintenance section of this manual for instructions. • Verify that a condensate trap is installed and the piping is properly sized and pitched. • Verify that the correct size and number of filters are in place. • Inspect the interior of the unit for tools and debris and install all panels in preparation for starting the unit. Voltage Imbalance Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure each leg (phase-to-phase) of the power supply. Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit. Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows: % Voltage Imbalance = AV – VD 100 ⎛ -----------------------⎞ ⎝ AV ⎠ where Average Voltage (AV); Volt1 + Volt2 + Volt3 AV = ⎛ -----------------------------------------------------------------⎞ ⎝ ⎠ 3 V1, V2, V3 = Line Voltage Readings VD = Line Voltage reading that deviates the farthest from the average voltage. Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be: 221 + 230 + 227- = 2.2percent ---------------------------------------------3 VD (reading farthest from average) = 221 The percentage of Imbalance equals: 226 – 221 100 ⎛⎝ ----------------------------⎞⎠ = 2.2percent 226 The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment. 32 Packaged Heat Pump • WC-IOM-7 Installation Electrical Phasing (Three Phase Motors) The compressor motor(s) and the supply fan motor are internally connected for the proper rotation when the incoming power supply is phased as A, B, C. Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following the steps below: • Turn the field supplied disconnect switch that provides power to the main power terminal block or to the “Line” side of the optional factory mounted disconnect switch to the “Off” position. • Connect the phase sequence indicator leads to the terminal block or to the “Line” side of the optional factory mounted disconnect switch as follows; Black (phase A) to L1 Red (phase B) to L2 Yellow (phase C) toL3 • Close the field supplied main power disconnect switch or circuit protector switch that provides the supply power to the unit. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized. • Observe the ABC and CBA phase indicator lights on the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, open the disconnect switch or circuit protection switch and reverse any two power wires. • Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect switch or circuit protection switch and remove the phase sequence indicator. Compressor Crankcase Heaters (Optional) Each compressor can be equipped with a crankcase heater. The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor WC-IOM-7 • Packaged Heat Pump 33 Installation starts. Oil foaming occurs when refrigerant condenses in the compressor and mixes with the oil. In lower ambient conditions, refrigerant migration to the compressor could increase. When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures. Before starting the unit in the “Cooling” mode, set the system switch to the “Off” position and turn the main power disconnect to the “On” position and allow the crankcase heater to operate a minimum of 8 hours. Before closing the main power disconnect switch, insure that the “System” selection switch is in the “Off” position and the “Fan” selection switch is in the “Auto” position. Close the main power disconnect switch and the unit mounted disconnect switch, if applicable. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized. ReliaTel Controls Upon power initialization, the RTRM performs self-diagnostic checks to insure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system. The Liteport LED located on the RTRM module is turned “On” within one second of power-up if internal operation is okay. Use one of the following “Test” procedure to bypass some time delays and to start the unit at the control panel. Each step of unit operation can be activated individually by temporarily shorting across the “Test” terminals for two to three seconds. The Liteport LED located on the RTRM module will blink when the test mode has been initiated. The unit can be left in any “Test” step for up to one hour before it will automatically terminate, or it can be terminated by opening the main power disconnect switch. Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the “System” control. 34 Packaged Heat Pump • WC-IOM-7 Pre-Start Test Modes There are three methods in which the “Test” mode can be cycled at LTB-Test 1 and LTB-Test 2. 1. Step Test Mode - This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds. For the initial start-up of the unit, this method allows the technician to cycle a component “On” and have up to one hour to complete the check. 2. Resistance Test Mode - This method can be used for start-up providing a decade box for variable resistance outputs is available. This method initiates the different components of the unit, one at a time, when a specific resistance value is placed across the two test terminals. The unit will remain in the specific test mode for approximately one hour even though the resistance is left on the test terminals. 3. Auto Test Mode - This method is not recommended for start-up due to the short timing between individual component steps. This method initiates the different components of the unit, one at a time, when a jumper is installed across the test terminals. The unit will start the first test step and change to the next step every 30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied "System" control method. For unit test steps, test modes, and step resistance values to cycle the various components, refer to Table 5. Table 5. Service test guide for component operation TEST STEP MODE Fan 1 Fan On Minimum Ventilation 2 3 Econ (Note 2) Comp 1 Comp 2 Heat 1 Heat 2 Ohms Minimum Position Off Setpoint 0% Off Off Off 2.2K On Selectable Off Off Off Off Economizer Test Open On Open Off Off Off Off 3.3K Cool Stage 1 On Minimum Position (Note 1) On Off Off Off 4.7K 4 (Note 3) Cool Stage 2 On Minimum Position (Note 1) On (Note 1) On Off Off 6.8K 5 (Note 3) Reheat On Minimum On On Off Off 33K 6 (Note 3) Heat Stage 1 On Minimum Off Off On Off 10K 7 (Note 3) Heat Stage 2 On Minimum Off Off On On 15K Notes: 1 - The condenser fans will operate any time a compressor is "On" providing the outdoor air temperatures are within the operating values. 2 - The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. 3 - Steps for optional accessories and non-applicable modes in unit will be skipped. WC-IOM-7 • Packaged Heat Pump 35 Pre-Start Verifying Proper Air Flow (Units with Belt Drive Indoor Fan) Much of the systems performance and reliability is closely associated with, and dependent upon having the proper airflow supplied both to the space that is being conditioned and across the evaporator coil. The indoor fan speed is changed by opening or closing the adjustable motor sheave. Before starting the SERVICE TEST, set the minimum position setpoint for the economizer to 0 percent using the setpoint potentiometer located on the Economizer Control (ECA), if applicable. ReliaTel Control Using the Service Test Guide in Table 5, momentarily jump across the Test 1 & Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test. Once the supply fan has started, check for proper rotation. The direction of rotation is indicated by an arrow on the fan housing. With the fan operating properly, determine the total system airflow (CFM) by; 1. Measuring the actual RPM, 2. Measure the amperage at the supply fan contactor and compare it with the full load amp (FLA) rating stamped on the motor nameplate. a. Calculate the theoretical BHP Actual Motor Amps X Motor HP Motor Nameplate Amps b. Using the fan performance tables in the unit Service Facts, plot the actual RPM (step 1) and the BHP (step 2a) to obtain the operating CFM. 3. If the required CFM is too low, (external static pressure is high causing motor HP output to be below table value), a. Relieve supply and/or return duct static. b. Change indoor fan speed and repeat steps 1 and 2. 36 • To Increase Fan RPM; Loosen the pulley adjustment set screw and turn sheave clockwise. • To Decrease Fan RPM; Loosen the pulley adjustment set screw and turn sheave counterclockwise. • If the required CFM is too high, (external static pressure is low causing motor HP output to be above table value), change indoor fan speed and repeat steps 1 and 2. • To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable). Packaged Heat Pump • WC-IOM-7 Pre-Start Return Air Smoke Detector The return air smoke detector is designed to shut off the unit if smoke is sensed in the return air stream. Sampling the airflow entering the unit at the return air opening performs this function. In order for the smoke detector to properly sense smoke in the return air stream, the air velocity entering the unit must be between 500 and 4000 feet per minute. Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables. WC-IOM-7 • Packaged Heat Pump 37 Start Up Economizer Start-Up ReliaTel Control Using the Service Test Guide in Table 5, p. 35, momentarily jump across the Test 1 & Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test. 1. Set the minimum position setpoint for the economizer to the required percentage of minimum ventilation using the setpoint potentiometer located on the Economizer Control (ECA). The economizer will drive to its minimum position setpoint, exhaust fans (if applicable) may start at random, and the supply fan will start when the SERVICE TEST is initiated. WARNING Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury. The Exhaust Fan will start anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. 2. Verify that the dampers stroked to the minimum position. 3. Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started. 4. Verify that the dampers stroked to the full open position. 5. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable). Compressor Start-Up 1. Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer to the refrigerant circuit illustration in the Service Facts. Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST start-up procedure for each compressor circuit. Momentarily jump across the Test 1 & Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired start-up component Test is started. WC-IOM-7 • Packaged Heat Pump 38 Start Up Scroll Compressors a. Once each compressor has started, verify that the rotation is correct. If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed. b. If the electrical phasing is correct, before condemning a compressor, interchange any two leads (at the compressor Terminal block) to check the internal phasing. Refer to the following illustration for the compressor terminal/phase identification. If the compressor runs backward for an extended period (15 to 30 minutes), the motor winding can overheat and cause the motor winding thermostat to open. Figure 15. c. Check the compressor oil levels. The oil level in each compressor sight glass should be 1/2 to 3/4 full when they are “Off”. Note: The scroll compressor uses Trane OIL-42 without substitution. The appropriate oil charge for a 9 and 10 Ton scroll compressor is 8 pints. For a 14 and 15 Ton scroll compressor, use 14 pints. 2. After the compressor and condenser fan have started and operated for approximately 30 minutes, observe the operating pressures. Compare the operating pressures to the operating pressure curve in the Service Facts. 3. Check system superheat. Follow the instruction listed on the superheat charging curve in the Service Facts. Superheat should be within ±5 F of the superheat chart value. 4. Repeat steps 1 through 4 for each refrigerant circuit. 5. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable). Heating Start-Up 1. WC-IOM-7 • Packaged Heat Pump Clamp an amp meter around one of 1st stage heater power wires at the heater contactor. 39 Start Up 2. ReliaTel Control Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST start-up procedure for each compressor circuit. Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started. 3. Verify that the heater stage is operating properly. 4. Clamp an amp meter around one of 2nd stage heater power wires at the heater contactor (if applicable). 5. ReliaTel Control Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST start-up procedure for each compressor circuit. Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started. 6. Verify that the heater stage is operating properly 7. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Final System Setup After completing all of the pre-start and start-up procedures outlined in the previous sections (i.e., operating the unit in each of its Modes through all available stages of cooling & heating), perform these final checks before leaving the unit: 40 • Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel. • Verify that the Remote panel “System” selection switch, “Fan” selection switch, and “Zone Temperature” settings for automatic operation are correct. • Inspect the unit for misplaced tools, hardware, and debris. • Verify that all exterior panels including the control panel doors and condenser grilles are secured in place. • Close the main disconnect switch or circuit protector switch that provides the supply power to the unit’s terminal block or the unit mounted disconnect switch. Packaged Heat Pump • WC-IOM-7 Maintenance WARNING Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury. Make sure all personnel are standing clear of the unit before proceeding. The system components will start when the power is applied. Fan Belt Adjustment - Belt Drive Units The fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length. When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base. Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent) illustrated in Figure 16; adjust the belt tension as follows; 1. To determine the appropriate belt deflection; a. Measure the center-to-center shaft distance (in inches) between the fan and motor sheaves. b. Divide the distance measured in Step 1a by 64; the resulting value represents the amount of belt deflection that corresponds to the proper belt tension. 2. Set the large O-ring on the belt tension gauge at the deflection value determined in Step 1b. 3. Set the small O-ring at zero on the force scale of the gauge plunger. 4. Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large O-ring is even with the top of the next belt or even with a straightedge placed across the fan and motor sheaves. Refer to Figure 16. 5. Remove the belt tension gauge. The small O-ring now indicates a number other than zero on the plunger’s force scale. This number represents the force (in pounds) required to give the needed deflection. 6. Compare the “force” scale reading (Step 5) with the appropriate “force” value listed in Table 6. If the “force” reading is outside the range, readjust the belt tension. WC-IOM-7 • Packaged Heat Pump 41 Maintenance Note: Actual belt deflection “force” must not exceed the maximum “force” value shown in Table 6. Table 6. Belt tension measurement and deflection ranges Deflection Force (Lbs.) Belts Cross Section A B 7. Small P.D Super Gripbelts Gripnotch Steel Cable Gripbelts Range Min. Max. Min. Max. Min. Max 3.0 - 3.6 3 4 1/2 3 7/8 5 1/2 3 1/4 4 3.8 - 4.8 3 1/2 5 4 1/2 6 1/4 3 3/4 4 3/4 5.0 - 7.0 4 5 1/2 5 6 7/8 4 1/4 5 1/4 3.4 - 4.2 4 5 1/2 5 3/4 8 4 1/2 5 1/2 4.4 - 5.6 5 1/8 7 1/8 6 1/2 9 1/8 5 3/4 7 1/4 5.8 - 8.8 6 3/8 8 3/4 7 3/8 10 1/8 7 8 3/4 Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension may decrease until the new belts are “run in”. Figure 16. Belt tension gauge Monthly Maintenance WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open. Failure to disconnect power before servicing can cause severe personal injury or death. 42 Packaged Heat Pump • WC-IOM-7 Maintenance Filters • Inspect the return air filters. Clean or replace them if necessary. Refer to the unit Service Facts for filter information. Return Air Smoke Detector Maintenance Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required. Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit. Cooling Season • Check the unit’s drain pans and condensate piping to ensure that there are no blockages. • Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Coil Cleaning” later in this section. • Manually rotate the condenser fan(s) to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight. • Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary. • Verify that all damper linkages move freely; lubricate with white grease, if necessary. • Check supply fan motor bearings; repair or replace the motor as necessary. • Check the fan shaft bearings for wear. Replace the bearings as necessary. • Check the supply fan belt. If the belt is frayed or worn, replace it. Refer to the “Fan Belt Adjustment” section for belt replacement and adjustments. • Verify that all wire terminal connections are tight. • Remove any corrosion present on the exterior surfaces of the unit and repaint these areas. • Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.) • Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete. WC-IOM-7 • Packaged Heat Pump 43 Maintenance • With the unit running, check and record the: ambient temperature; compressor suction and discharge pressures (each circuit); superheat (each circuit); Record this data on an “operator’s maintenance log” like the one shown in Table 7 on page 46. If the operating pressures indicate a refrigerant shortage, measure the system superheat. For guidelines, refer to the “Compressor StartUp” section. Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws. Heating Season • Inspect the unit’s air filters. If necessary, clean or replace them. • Check supply fan motor bearings; repair or replace the motor as necessary. • Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs. • Verify that the electric heat system operates properly. Coil Cleaning Regular coil maintenance, including annual cleaning, enhances the unit’s operating efficiency by minimizing: compressor head pressure and amperage draw; evaporator water carryover; fan brake horsepower, due to increase static pressure losses; airflow reduction. At least once each year, or more often if the unit is located in a “dirty” environment, clean the evaporator and condenser coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils. To clean refrigerant coils, use a soft brush and a sprayer (either a garden pumpup type or a high-pressure sprayer). A high-quality detergent is also required; suggested brands include “SPREX A.C.”, “OAKITE 161”, “OAKITE 166” and “COILOX”. If the detergent selected is strongly alkaline (ph value exceeds 8.5), add an inhibitor. 1. Remove enough panels from the unit to gain access to the coil. Remove the access panel from the roof located next to the rear condenser fan. 2. Protect all electrical devices such as motors and controllers from any over spray. 3. Straighten any bent coil fins with a fin comb. 4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution to 150° F maximum to improve its cleansing capability. 44 Packaged Heat Pump • WC-IOM-7 Maintenance WARNING Hazardous Pressures! Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution temperature under 150°F to avoid excessive pressure in the coil. Failure to follow these safety precautions could result in coil bursting, which could result in death or serious injury. Do not heat the detergent-and-water solution above 150° F. Hot liquids sprayed on the exterior of the coil will raise the coil’s internal pressure and may cause it to burst. Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. 5. 5. Pour the cleaning solution into the sprayer. If a high-pressure sprayer is used: a. do not allow sprayer pressure to exceed 600 psi. b. the minimum nozzle spray angle is 15 degrees. c. maintain a minimum clearance of 6" between the sprayer nozzle and the coil. d. spray the solution perpendicular (at 90 degrees) to the coil face. 6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for five minutes. 7. Rinse both sides of the coil with cool, clean water. 8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7. 9. Reinstall all of the components and panels removed in Step 1 and any protective covers installed in step 2. 10. Restore the unit to it’s operational status and check system operation. Final Process For future reference, you may find it helpful to record the unit data requested below in the blanks provided. (1) Complete Unit Model Number: _______________________________________________________________________ (2) Unit Serial Number: _______________________________________________________________________ (3) Wiring Diagram Numbers (from unit control panel): — schematic(s) _______________________________________________________________________ _______________________________________________________________________ WC-IOM-7 • Packaged Heat Pump 45 Maintenance _______________________________________________________________________ _______________________________________________________________________ — connection(s) _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ Table 7. Sample maintenance log Refrigerant Circuit #1 Date 46 Current Compr. Oil Suction Ambient Level Pressure temp F/C Psig/kPa Dischcharge Pressure Psig/kpa Refrigerant Circuit #2 Super heat Sub coolF/ Compr. Oil Suction F/C C Level Pressure Psig/kPa Dischcharge Pressure Psig/kpa Super heat Sub coolF/ F/C C Packaged Heat Pump • WC-IOM-7 Troubleshooting ReliaTel Control The RTRM has the ability to provide the service personnel with some unit diagnostics and system status information. WARNING Hazardous Service Procedures! The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concerning these procedures. When possible, disconnect all electrical power including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury. Before turning the main power disconnect switch “Off”, follow the steps below to check the ReliaTel Refrigeration Module (RTRM). All diagnostics & system status information stored in the RTRM will be lost when the main power is turned “Off”. To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized. 1. Verify that the Liteport LED on the RTRM is burning continuously. If the LED is lit, go to Step 3. 2. If the LED is not lit, verify that 24 VAC is presence between J1-1 and J1-2. If 24 VAC is present, proceed to Step 3. If 24 VAC is not present, check the unit main power supply, check transformer (TNS1). Proceed to Step 3 if necessary. 3. Utilizing “Method 1” or “Method 2” in the “System Status Checkout Procedure ” section, check the following: System status Heating status Cooling status If a System failure is indicated, proceed to Step 4. If no failures are indicated, proceed to Step 5. 4. If a System failure is indicated, recheck Steps 1 and 2. If the LED is not lit in Step 1, and 24 VAC is present in Step 2, the RTRM has failed. Replace the RTRM. 5. If no failures are indicated, use one of the TEST mode procedures described in the “Unit Start-Up” section to start the unit. This procedure will allow you WC-IOM-7 • Packaged Heat Pump 47 Troubleshooting to check all of the RTRM outputs, and all of the external controls (relays, contactors, etc.) that the RTRM outputs energize, for each respective mode. Proceed to Step 6. 6. Step the system through all of the available modes, and verify operation of all outputs, controls, and modes. If a problem in operation is noted in any mode, you may leave the system in that mode for up to one hour while troubleshooting. Refer to the sequence of operations for each mode, to assist in verifying proper operation. Make the necessary repairs and proceed to Steps 7 and 8. 7. If no abnormal operating conditions appear in the test mode, exit the test mode by turning the power “Off” at the main power disconnect switch. 8. Refer to the individual component test procedures if other microelectronic components are suspect. System Status Checkout Procedure “System Status” is checked by using one of the following two methods: Method 1 If the Zone Sensor Module (ZSM) is equipped with a remote panel with LED status indication, you can check the unit within the space. If the ZSM does not have LED’s, use Method 2. BAYSENS010B, BAYSENS011B, BAYSENS019B, BAYSENS020B, BAYSENS021A & BAYSENS023A all have the remote panel indication feature. The LED descriptions are listed below. LED 1 (System) “On” during normal operation. “Off” if a system failure occurs or the LED fails. “Flashing” indicates test mode. LED 2 (Heat) “On” when the heat cycle is operating. “Off” when the heat cycle terminates or the LED fails. “Flashing” indicates a heating failure. LED 3 (Cool) “On” when the cooling cycle is operating. “Off” when the cooling cycle terminates or the LED fails. “Flashing” indicates a cooling failure. 48 Packaged Heat Pump • WC-IOM-7 Troubleshooting LED 4 (Service) “On” indicates a clogged filter. “Off” during normal operation. “Flashing” indicates an evaporator fan failure Below is the complete listing of failure indication causes. System Failure Check the voltage between terminals 6 and 9 on J6, it should read approximately 32 VDC. If no voltage is present, a System failure has occurred. Refer to Step 4 in the previous section for the recommended troubleshooting procedure. Cooling Failure 1. Cooling and heating set point (slide pot) on the zone sensor has failed. Refer to the “Zone Sensor Test Procedure” section. 2. Zone temperature thermistor ZTEMP on ZTS failed. Refer to the “Zone Sensor Test Procedure” section. 3. CC1 or CC2 24 VAC control circuit has opened, check CC1 & CC2 coils, and any of the controls below that apply to the unit (HPC1, HPC2). 4. LPC1 has opened during the 3 minute minimum “on time” during 4 consecutive compressor starts, check LPC1 or LPC2 by testing voltage between the J1-8 & J3-2 terminals on the RTRM and ground. If 24 VAC is present, the LPC’s has not tripped. If no voltage is present, LPC’s has tripped. Service Failure 5. If the supply fan proving switch has closed, the unit will not operate (when connected to RTOM), check the fan motor, belts, and proving switch. 6. Clogged filter switch has closed, check the filters. Simultaneous Heat and Cool Failure 1. Emergency Stop is activated. Method 2 The second method for determining system status is done by checking voltage readings at the RTRM (J6). The system indication descriptions and the approximate voltages are listed below. System Failure Measure the voltage between terminals J6-9 & J6-6. Normal Operation = approximately 32 VDC System Failure = less than 1 VDC, approximately 0.75 VDC WC-IOM-7 • Packaged Heat Pump 49 Troubleshooting Test Mode = voltage alternates between 32 VDC & 0.75 VDC Heat Failure Measure the voltage between terminals J6-7 & J6-6. Heat Operating = approximately 32 VDC Heat Off = less than 1 VDC, approximately 0.75 VDC Heating Failure = voltage alternates between 32 VDC & 0.75 VDC Cool Failure Measure the voltage between terminals J6-8 & J6-6. Cool Operating = approximately 32 VDC Cool Off = less than 1 VDC, approximately 0.75 VDC Cooling Failure = voltage alternates between 32 VDC & 0.75 VDC Service Failure Measure the voltage between terminals J6-10 & J6-6. Clogged Filter = Approximately 32 VDC. Normal = Less than 1 VDC, approximately 0.75 VDC Fan Failure = voltage alternates between 32 VDC & 0.75 VDC. To use LED’s for quick status information at the unit, purchase a BAYSENS010B ZSM and connect wires with alligator clamps to terminals 6 through 10. Connect each respective terminal wire (6 through 10) from the Zone Sensor to the unit J6 terminals 6 through 10. Note: If the system is equipped with a programmable zone sensor, (BAYSENS019A, BAYSENS020A or BAYSENS023A), the LED indicators will not function while the BAYSENS010A is connected. Resetting Cooling and Heating Lockouts Cooling Failures and Heating Lockouts are reset in an identical manner. Method 1 explains resetting the system from the space; Method 2 explains resetting the system at the unit. Note: Before resetting Cooling Failures and Heating Lockouts check the Failure Status Diagnostics by the methods previously explained. Diagnostics will be lost when the power to the unit is disconnected. Method 1 To reset the system from the space, turn the “Mode” selection switch at the zone sensor to the “Off” position. After approximately 30 seconds, turn the “Mode” selection switch to the desired mode, i.e. Heat, Cool or Auto. 50 Packaged Heat Pump • WC-IOM-7 Troubleshooting Method 2 To reset the system at the unit, cycle the unit power by turning the disconnect switch “Off” and then “On”. Lockouts can be cleared through the building management system. Refer to the building management system instructions for more information. Zone Temperature Sensor (ZTS) Service Indicator The ZSM SERVICE LED is a generic indicator, that will signal the closing of a Normally Open switch at any time, providing the Indoor Motor (IDM) is operating. This indicator is usually used to indicate a clogged filter, or an air side fan failure. The RTRM will ignore the closing of this Normally Open switch for 2 (±1) minutes. This helps prevent nuisance SERVICE LED indications. The exception is the LED will flash 40 seconds after the fan is turned “On” if the Fan Proving Switch is not made. Clogged Filter Switch This LED will remain lit the entire time that the Normally Open switch is closed. The LED will be turned off immediately after resetting the switch (to the Normally Open position), or any time that the IDM is turned “Off”. If the switch remains closed, and the IDM is turned “On”, the SERVICE LED will be turned “On” again after the 2 (±1) minute ignore delay. This LED being turned “On”, will have no other affect on unit operation. It is an indicator only. Fan Failure Switch When the “Fan Failure” switch is wired to the RTOM, the LED will remain flashing the entire time the fan proving switch is closed, indicating a fan failure, and it will shut the unit operations down. WC-IOM-7 • Packaged Heat Pump 51 Troubleshooting Zone Temperature Sensor (ZTS) Test Note: These procedures are not for programmable or digital models and are conducted with the Zone Sensor Module electrically removed from the system. Test 1 Zone Temperature Thermistor (ZTEMP) This component is tested by measuring the resistance between terminals 1 and 2 on the Zone Temperature Sensor. Below are some typical indoor temperatures, and corresponding resistive values. Table 8. Zone Temperature Nominal ZTEMP Resistance Nominal CSP or HSP Resistance 50 F° 10.0 C° 19.9 K-Ohms 889 Ohms 55 F° 12.8 C° 17.47 K-Ohms 812 Ohms 60 F° 15.6 C° 15.3 K-Ohms 65 F° 18.3 C° 13.49 K-Ohms 597 Ohms 70 F° 21.1 C° 11.9 K-Ohms 75 F° 23.9 C° 10.50 K-Ohms 403 Ohms 80 F° 26.7 C° 9.3 K-Ohms 305 Ohms 85 F° 29.4 C° 8.25 K-Ohms 208 Ohms 90 F° 32.2 C° 7.3 K-Ohms 110 Ohms 695 Ohms 500 Ohms Test 2 Cooling Set Point (CSP) and Heating Set Point (HSP) The resistance of these potentiometers are measured between the following ZSM terminals. Refer to the chart above for approximate resistances at the given setpoints. Cool SP = Terminals 2 and 3 Range = 100 to 900 Ohms approximate Heat SP = Terminals 2 and 5 Range = 100 to 900 Ohms approximate 52 Packaged Heat Pump • WC-IOM-7 Troubleshooting Test 3 System Mode and Fan Selection The combined resistance of the Mode selection switch and the Fan selection switch can be measured between terminals 2 and 4 on the Zone Sensor. The possible switch combinations are listed on the following page with their corresponding resistance values. Test 4 LED Indicator Test, (SYS ON, HEAT, COOL & SERVICE) Method 1 Testing the LED using a meter with diode test function. Test both forward and reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts, depending on your meter. Reverse bias will show an Over Load, or open circuit indication if LED is functional. Method 2 Testing the LED with an analog Ohmmeter. Connect Ohmmeter across LED in one direction, then reverse the leads for the opposite direction. The LED should have at least 100 times more resistance in reverse direction, as compared with the forward direction. If high resistance in both directions, LED is open. If low in both directions, LED is shorted. Method 3 To test LED’s with ZSM connected to unit, test voltages at LED terminals on ZSM. A measurement of 32 VDC, across an unlit LED, means the LED has failed. Note: Measurements should be made from LED common (ZSM terminal 6 to respective LED terminal). Refer to the Zone Sensor Module (ZSM) Terminal Identification table at the beginning of this section. Programmable & Digital Zone Sensor Test Testing serial communication voltage 1. Verify 24 VAC is present between terminals J6-14 & J6-11. 2. Disconnect wires from J6-11 and J6-12. Measure the voltage between J6-11 and J6-12, should be about 32 VDC. 3. Reconnect wires to terminals J6-11 and J6-12. Measure voltage again between J6-11 and J6-12, voltage should flash high and low every 0.5 seconds. The voltage on the low end will measure about 19 VDC, while the voltage on the high end will measure from approximately 24 to 38 VDC. WC-IOM-7 • Packaged Heat Pump 53 Troubleshooting 4. Verify all modes of operation, by running the unit through all of the steps in the “Test Modes” section discussed in “Unit Start-Up”. 5. After verifying proper unit operation, exit the test mode. Turn the fan on continuously at the ZSM, by pressing the button with the fan symbol. If the fan comes on and runs continuously, the ZSM is good. If you are not able to turn the fan on, the ZSM is defective.\ Table 9. System mode and fan selection chart Resistance Valves (Ohms) Zone Sensor Unit/Fan Mode Local Unit Mode Local Fan Mode 2.32K Off/ Auto Off Auto 4.87K Cool/Auto Cool Auto 7.68K Auto/Auto Auto Auto 10.77K Off/On Off On 13.32K Cool/On Cool On 16.13K Auto/On Auto On 19.48K Heat/Auto Heat Auto 27.93K Heat/On Heat On 35.0K Emergency Heat/Auto Emergency Heat Auto 43.45K Emergency Heat/On Emergency Heat On Out of Range (Short) INVALID/Short Invalid (CV), Auto (VAV) Invalid Out of Range (Open) INVALID/Open Invalid (CV), Off (VAV) Invalid ReliaTel Refrigeration Module (RTRM) Default Chart If the RTCI loses input from the building management system, the RTRM will control in the default mode after approximately 15 minutes. If the RTRM loses the Heating and Cooling setpoint input, the RTRM will control in the default mode instantaneously. The temperature sensing thermistor in the Zone Sensor Module is the only component required for the “Default Mode” to operate. Unit Operation without a Zone Sensor This procedure is for temporary operation only. The economizer and condenser fan cycling functions are disabled. 1. Open and Lock the unit disconnect switch. 2. Remove the Outside Air Sensor (OAS) from the condenser section of unit. 3. Use two (2) wire nuts, to individually cap the wires. 4. Locate the RTRM (J6). Connect two (2) wires to terminals J6-1 and 2. 5. Connect the sensor (OAS) using two wire nuts to the two (2) field supplied wires that were connected to terminals 1 and 2 on J6. 54 Packaged Heat Pump • WC-IOM-7 Troubleshooting Unit Economizer Control (ECA) Troubleshooting ReliaTel Control Table 10. Verify economizer status by economizer actuator (ECA) LED indicator: OFF: No Power or Failure ON: Normal, OK to Economize Slow Flash: Normal, Not OK to Economize 1/2 Second On / 2 Seconds Off: Fast Flash - Error Code: Communications Failure Pulse Flash: 2 Second On / 1/2 Second Off: Error Code: 1 Flash: Actuator Fault 2 Flashes: CO2 Sensor 3 Flashes: RA Humidity Sensor 4 Flashes: RA Temp Sensor 5 Flashes: OA Quality Sensor 6 Flashes: OA Humidity Sensor 7 Flashes: OA Temp Sensor 8 Flashes: MA Temp Sensor 9 Flashes: RAM Fault 10 Flashes: ROM Fault 11 Flashes: EEPROM Fault WC-IOM-7 • Packaged Heat Pump 55 Wiring Diagrams For easier access, after 2007, published unit wiring diagrams (individual, separate diagrams for unitary product lines) will become available via e-Library instead of through wiring manuals. Diagrams prior to 2008 will be located in wiring diagram books RT-SVE03A-EN and RT-SVE06A-EN. Drawing Number Description 2309-3105 Diagram; Novar ETM-3051 2309-3108 Diagram; CONTROL WC_150 WC_240 400-575/60/3 2309-3115 Diagram; Power Electrical WC 150-240 2309-3116 Diagram; Power Electrical WC 240 2309-3140 Diagram; Master Stacked Layer Model 2309-3149 Diagram; Connection Electrical WC 180 2309-3170 Diagram; Connection Electrical WC 240 2309-3171 Diagram; Connection Electrical WC 240 2309-3172 Diagram; Connection Electrical WC 150 2309-3173 Diagram; Connection Electrical WC 150 2309-3174 Diagram; Connection Electrical WC 180 2309-3194 INSTRUCTIONAL DIAGRAM FOR CONVETNIONAL THERMOSTAT (Home Depot) 23093195 Diagram;Novar 3051 2309-3352 MICRO INTERCONNECTION DIAGRAM 2309-3358 Diagram; Crankcase Heater Kits for Voyager 2 2309-3360 SCHEMATICS; CONNECTION DIAGRAM--VOY2 208-230V WC180 2309-3361 SCHEMATICS; CONNECTION DIAGRAM--VOY2 460/575V WC 180 2309-3364 Diagram 14 position plug 2309-3377 MASTER DRAWING; CONNECTION DIAGRAMS--VOY2 2309-3382 Schematic; Power 200-230V WC 150-240 2309-3383 Schematic; Power 400-575V WC 150-240 2309-3392 Schematic, Control 200-575V 2309-3393 Diagram, Connection 208-230V WC 150 2309-3394 Diagram, Connection 400-575V WC 150 2309-3183 Diagram; Electric Heat 2309-3184 Diagram; Electric Heat 2309-3185 Diagram; Electric Heat 2309-3186 Diagram; Electric Heat 2309-3187 Diagram; Electric Heat 2309-3188 Diagram; Electric Heat 2309-3189 Diagram; Electric Heat 2309-3190 Diagram; Electric Heat 2309-3191 Diagram; Electric Heat 2309-3192 Diagram; Electric Heat WC-IOM-7 • Packaged Heat Pump WC 150-240 56 Warranty Heat Pump WCZ, WCY, WCX, WCC, WCD, WCH, WCM, WCP and WSC (Parts Only) Models Less Than 20 Tons for Commercial Use* This warranty is extended by Trane, to the original purchaser and to any succeeding owner of the real property to which the Heat Pump is originally affixed, and applies to products purchased and retained for use within the U.S.A. and Canada. There is no warranty against corrosion, erosion or deterioration. If any part of your Heat Pump fails because of a manufacturing defect within one year from the date of the original purchase, Warrantor will furnish without charge the required replacement part. In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through fifth year from the date of original purchase, Warrantor will furnish without charge the required replacement compressor. Warrantor’s obligations and liabilities under this warranty are limited to furnishing F.O.B. Warrantor factory or warehouse replacement parts for Warrantor’s products covered under this warranty. Warrantor shall not be obligated to pay for the cost of lost refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective. THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES. Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Trane 2701 Wilma Rudolph Blvd. Clarksville, TN 37040-1008 Attention: Manager, Product Service GW-604-4800 * This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a residential application. Commercial use is any application where the end purchaser uses the product for other than personal, family or household purposes. WC-IOM-7 • Packaged Heat Pump 57 Warranty Heat Pump Standard Equipment Warranty Terms and Conditions Commercial Equipment Warranty and Liability Models Larger that 20 Tons for Commercial Use* The Company warrants for a period of 12 months from initial start-up or 18 months from date of shipment, whichever is less, that the Company products covered by this order (1) are free from defects in material and workmanship and (2) have the capacities and ratings set forth in the Company’s catalogs and bulletins, provided that no warranty is made against corrosion, erosion or deterioration. The Company’s obligations and liabilities under this warranty are limited to furnishing f.o.b. factory or warehouse at Company designated shipping point, freight allowed to Buyer’s city (or port of export for shipment outside the conterminous United States) replacement equipment (or at the option of the Company parts therefore) for all Company products not conforming to this warranty and which have been returned to the manufacturer. The Company shall not be obligated to pay for the cost of lost refrigerant. No liability whatever shall attach to the Company until said products have been paid for and then said liability shall be limited to the purchase price of the equipment shown to be defective. The Company makes certain further warranty protection available on an optional extra-cost basis. Any further warranty must be in writing, signed by an officer of the Company. The warranty and liability set forth herein are in lieu of all other warranties and liabilities, whether in contract or in negligence, express or implied, in law or in fact, including implied warranties of merchantability and fitness for particular use. In no event shall the Company be liable for any incidental or consequential damages. Trane 2701 Wilma Rudolph Blvd. Clarksville, TN 37040-1008 Attention: Manager,Product Service 58 Packaged Heat Pump • WC-IOM-7 Literature Order Number WC-IOM-7 Date 12/04 Supersedes WC-IOM-7 (04/03) The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Page Mode : UseOutlines XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0.5 (Windows) Create Date : 2008:02:27 08:14:38Z Creator Tool : FrameMaker 7.2 Modify Date : 2008:02:27 08:14:38Z Format : application/pdf Title : WC-IOM-7_.book Creator : clkahi Document ID : uuid:ad815736-7c03-4dfb-a1f9-69f231314ec2 Instance ID : uuid:b457aacb-7885-4f82-9abe-39254bf2c162 Page Count : 60 Author : clkahiEXIF Metadata provided by EXIF.tools