Trane X39640516 01 T Series Climate Changer ® Central Station Air Handlers Installation And Maintenance PDF Manual (CLCH IM 16A) User To The Aa7b2f09 8f06 4c3e 92ee 72770f6ab1fb
User Manual: Trane X39640516-01 to the manual
Open the PDF directly: View PDF .
Page Count: 71
Download | |
Open PDF In Browser | View PDF |
Installation and Maintenance Manual Library Product Section Product Model Literature Type Sequence Date File No. CLCH-IM-16A Service Literature Air Handling Central Station Air Handlers T-Series Climate Changer Installation/Maintenance 2 March 1999 CLCH-IM-16A 3/99 T-Series Climate Changer® Central Station Air Handlers Draw-Thru and Blow-Thru Unit Sizes 3, 6, 8, 10, 12, 14, 17, 21, 25, 30, 35, 40, 50, 66, 80, and 100 Part No. X39640516-01 Since the Trane Company has a policy of continuous product improvement, it reserves the right to change specifications and designs without notice. The installation and servicing equipment referred to into this booklet should be done by qualified experienced technicians. Notice Warning and Cautions WORLD ENVIRONMENTAL SCIENTISTS HAVE CONCLUDED, BASED ON THE BEST CURRENTLY AVAILABLE EVIDENCE, THAT OZONE IN OUR UPPER ATMOSPHERE IS BEING REDUCED DUE TO THE RELEASE OF CFC FULLY HALOGENATED COMPOUNDS. Notice that WARNING and CAUTION appear at appropriate intervals throughout this manual. THE TRANE COMPANY URGES THAT ALL HVAC SERVICERS WORKING ON TRANE EQUIPMENT, OR ANY MANUFACTURER’S PRODUCTS, MAKE EVERY EFFORT TO ELIMINATE, IF POSSIBLE, OR VIGOROUSLY REDUCE THE EMISSION OF CFC, HCFC, AND HFC REFRIGERANTS TO THE ATMOSPHERE RESULTING FROM INSTALLATION, OPERATION, ROUTINE MAINTENANCE, OR MAJOR SERVICE ON THIS EQUIPMENT. ALWAYS ACT IN A RESPONSIBLE MANNER TO CONSERVE REFRIGERANTS FOR CONTINUED USE EVEN WHEN ACCEPTABLE ALTERNATIVES ARE AVAILABLE. REFRIGERANT USED IN ANY TYPE OF AIRCONDITIONING OR REFRIGERATING EQUIPMENT SHOULD BE RECOVERED FOR REUSE, RECOVERED AND /OR RECYCLED FOR REUSE, REPROCESSED (RECLAIMED), OR PROPERLY DESTROYED, WHENEVER IT IS REMOVED FROM EQUIPMENT. NEVER RELEASE TO THE ATMOSPHERE! Literature Change History CLCH-IM-16 (November 1997) Initial Manual covering T-Series Climate Changer, sizes 3, 6, 8, 10, 12, 14, 17, 21, 25, 30, 35,40, 50, 66, 80, and 100. CLCH-IM-16A (March 1999) Revised manual to include new details on shipping, assembly, and installation. WARNING WARNING indicates a potentially hazardous situation that could result in personal injury or death. CAUTION CAUTIONs are designed to alert you to conditions that could result in minor personal injury or equipment damage. Table of Contents General Information ............................................. 1 Unit Description .................................................. Operating Environment ....................................... Unit Nameplates ................................................. Controls .............................................................. 1 1 1 2 Receiving .............................................................. 3 Storage Considerations ...................................... 3 Rigging and Handling .......................................... 4 Determine Unit Weights ...................................... 4 Lifting Instructions ............................................. 12 Installation .......................................................... 15 Unit Assembly .................................................... 16 General ............................................................. Unit Assembly - All Sizes .................................. Component Installation Requirements ............. Fan Section ...................................................... 16 16 22 22 Set-Up ................................................................. 25 Duct Connections ............................................. Drain Pan .......................................................... Coil Piping And Connections ............................ Refrigerant Coil Piping ...................................... General Refrigerant Piping Recommendations Wiring ............................................................... 28 30 32 46 47 49 Installation Checklist ......................................... 51 Prestart-Up Checks .......................................... 51 Start-Up ............................................................... 53 Start-Up Procedures ......................................... 53 Periodic Maintenance ........................................ 59 Drain Pans ........................................................ Air Filters .......................................................... Fans .................................................................. Fan Bearings and Motors ................................. Coil Cleaning .................................................... Coil Winterization .............................................. 60 60 61 61 63 65 Troubleshooting ................................................. 66 T-Series Climate Changer *HQHUDO,QIRUPDWLRQ Trane T-Series Climate Changers ship as complete assemblies or sectional subassemblies. Some assembly is required when the units ship as subassemblies. Unit Description Operating Environment Trane T-Series Climate Changers® are Central Station Air Handlers designed for a variety of air handling applications. The basic unit consists of a fan, heating and/or cooling coils, filters, and dampers. See the sales catalog (CLCH-DS-9) for a list of available options and components. The T-Series Climate Changer (TSC) is an outdoor air handler. When considering the placement of the TSC it is important to consider the operating environment. The acceptable ambient temperature range for unit operation is -40° to +140°F (-40°C to 60°C). The fan is internally isolated. Fans available are double-width, double-inlet Centrifugal types with forward curved, backward inclined, or airfoil blade type design; single-width, single-inlet Plug Fans or Vane-Axial Q Fans®. Fans are available in low, medium, and high pressure classes with or without inlet guide vanes. For heating applications a special motor may be required to withstand the higher temperatures. Motors with Class “B” insulation are acceptable for ambient temperatures up to 104°F while motors with class “F” insulation can withstand ambient temperatures to +140° F (60°C). To insure fan stability, the unit ships with four (4) lockdown devices that prevent the fan from shifting during shipment and installation. These spacers must be removed prior to fan operation to assure proper vibration isolation. The units are available with factory-mounted controls for stand-alone operation or operation with a complete building automation system. This includes factory-mounted starters, DDC controllers, and end devices. NOTE: IT IS RECOMMENDED THAT THE CUSTOMER PROVIDE ADEQUATE FREEZE PROTECTION FOR THE COILS. UNITS WITH UL APPROVAL HAVE A MAXIMUM AMBIENT TEMPERATURE REQUIREMENT OF 104°F. Unit Nameplates Each unit section is provided with a section nameplate (label). See Figure 1 . This nameplate includes type of section, section serial number, customer tagging information, section position and service model number. Figure 1 Unit Nameplate Type of Section Section Serial Number Customer Furnished Tagging Information Section Service Model Number Section Unit Number Sales Order Number Installation and Maintenance 1 Each section of a T-Series Climate Changer is identified with a multi-character model number and serial number. The model number precisely identifies a particular section. Refer to model number and serial number when ordering parts or requesting service. If the unit ships as individual sections or section subassemblies refer to the nameplate for customer tagging information and section position to insure proper placement of the sections during assembly. Controls Wiring Sizes and Connections Entrances are provided for field installation of high and low voltage wiring through a pipe/nipple connection in the base of the unit. The low and high voltage connections are on opposite sides of the unit on sizes 3 - 50 and on the same side for sizes 66 100. CAUTION The high and low voltage wire raceways for the T-series units are intended for factory wiring ONLY. Do not use these raceways for field uses. Failure to follow these instructions can result in damage to the unit. Wiring to the unit must be provided by the installer and must comply with all national and local electrical codes. The motor nameplate includes a wiring diagram. If there are any questions concerning the wiring of the motor be sure to take the motor manufacturer’s name, model number, and serial number and contact your local Trane representative for assistance. Factory Mounted Controls NOTE: FOR MORE IN-DEPTH UNDERSTANDING OF THE PROGRAMMABLE CONTROL MODULE (PCM) REFERENCE INSTALLATION GUIDE EMTX-IN-11A, APPLICATION GUIDE EMTX-AG-1, OPERATORS GUIDE EMTX-OG-4, INSTALLATION, OPERATION AND PROGRAMMING GUIDE CLCH-IOP-1, AND INSTALLATION, OPERATION AND MAINTENANCE MISC-IOM-5. NOTE: THIS SECTION WILL PROVIDE A BRIEF OVERVIEW OF THE OPTIONAL FACTORY MOUNTED CONTROLS. FOR MORE IN-DEPTH UNDERSTANDING OF THE PROGRAMMABLE CONTROL MODULE (PCM), REFERENCE INSTALLATION GUIDE EMTX-IN-11A, APPLICATION GUIDE EMTX-AG-1, OPERATORS’ GUIDE EMTX-OG-4, INSTALLATION OPERATION AND PROGRAMMING GUIDE CLCH-IOP-1 AND INSTALLATION OPERATION AND MAINTENANCE MISC-IOM-5. Most control components are mounted inside the units. Depending on system configuration, these controls may include damper actuators, dirty filter switches, averaging temperature sensors, low limit switches, point temperature switches, and inlet guide vane actuators. Variable frequency drives, starters, PCMs, control transformers, static pressure transducers, DC power supplies, customer interface relays, etc. will be in enclosures mounted on the inside of the unit. Small items that cannot be factory-mounted will ship inside the control enclosures. These controls may include space temperature sensors, outside air temperature sensors, and humidity sensors. All control valves will ship directly to the “ship to address” from the vendor, unless another address was given on the order. All constant volume or variable air volume control systems are provided with 120 to 24 VAC control transformers. Unless ordered with a factorymounted/wired starter or variable frequency drive, the customer must provide 120 VAC control power, 50/60 hz, typically 3 amps for unit sizes 3 - 50, and 5 amps for unit sizes 66 -100. A dedicated 15 amp circuit is recommended. A T-Series Climate Changer unit and/or field-installed accessories that must be stored for a period of time prior to being installed MUST be protected from the elements. The PCM and all other electrical/electronic components should be stored in conditions of -20 120°F and 5 - 95% relative humidity non-condensing. Electrical components ARE NOT moisture-tolerant The warranty will not cover damage to the unit or controls due to negligence during storage. A controlled indoor environment is recommended for proper storage. For further storage considerations, refer to “Storage Considerations” in the next section. The T-Series Climate Changer is available with a wide array of factory mounted controls. They include the Programmable Control Module (PCM), motor starters, and Variable Frequency Drives (VFD). 2 CLCH-IM-16A 5HFHLYLQJ The T-Series Climate Changer can ship as individual sections, section subassemblies, or a complete air handler. Sizes 3 - 100 have an integral base rail. 3 Keep damaged material in the same location as it was received. It is the receiver’s responsibility to provide reasonable evidence that the concealed damage was not incurred after delivery. 4 Notify the Trane sales representative of the damage and arrange for repair. Do not attempt to repair the unit without consulting the sales representative. TRANE IS NOT RESPONSIBLE FOR SHIPPING DAMAGE. Upon receipt of the unit(s) and prior to unloading, inspect the unit for damage and verify that the shipment is complete. Delivery cannot be refused. Storage Considerations Inspection General 1 Visually inspect components for any damage that may have occurred during shipment. The Trane T-Series Climate Changer air handler is an outdoor unit and requires no special protection for storage before installation. Keep the equipment in the original shipping container for protection and ease of handling. The warranty will not cover damages to the unit due to negligence during storage. NOTE: THE TRANE COMPANY IS NOT RESPONSIBLE FOR SHIPPING DAMAGE. 2 Check all access doors to confirm that the latches and hinges are not damaged. 3 Check all coil connections to confirm they are straight and undamaged. 4 Inspect the coils for damage to the fin surface or coil connections. 5 Check all devices attached to the unit exterior and confirm that they are not damaged. 6 Manually rotate the fan wheel to ensure free movement of the shaft, bearings, and drive. Inspect the fan housing for any foreign objects. 7 Inspect the interior of each section for any internal damage as soon as possible after delivery. Concealed damage must be reported within 15 days of receipt. 8 If the unit was ordered with Factory Mounted Controls, locate all sensors. These components will be shipped inside the control enclosure. 9 If the unit shipped in subassemblies, locate assembly hardware. The necessary assembly hardware will be packaged inside the fan section or the mixing section. For longer periods of storage, allow enough clearance around the unit to perform periodic inspection and maintenance of the equipment. In addition, loosen belt tension on drive belts. Long Term Storage Every two weeks, rotate the fan and motor shaft thirty revolutions by hand. Check for free rotation. Every six months, check fan shaft bearings and grease lines. Add grease using a manual grease gun following the lubrication recommendations in the Periodic Maintenance section. Check the motor lubrication; remove and clean grease plugs and check for the presence of moisture in the grease. If moisture is present, remove the motor and send it to an authorized repair shop for bearing inspection/replacement. If no moisture is present, refer to the motor manufacturer’s lubrication recommendation for proper lubrication. Resolving Shipping Damage The T-Series Climate Changer ships FOB. If damage has occurred to the unit sections during shipment, the following instructions should be completed: 1 Make specific notation describing the damage on the freight bill. 2 Report all claims of shipping damage to the delivering carrier immediately. Installation and Maintenance 3 5LJJLQJDQG+DQGOLQJ CAUTION Do NOT lift from the top of the unit. Lift only from lift lugs located at the bottom of the unit. Use all lift lugs provided. Failure to do so can damage the unit. The unit will be shipped (as specified by sales order) as 1) a complete assembly, 2) in sub-assemblies (collection of sections), or 3) as individual sections. Follow appropriate lift warnings as shown on the label affixed to the unit. Determine Unit Weights WARNING Weights in this manual are approximate. Always testlift the unit section to check for proper balance and rigging before hoisting to the desired location. Never bolt (assemble) sections or sub-assemblies together before rigging. Always rig subassemblies or sections as received from the factory. When preparing to lift sections, estimate the equipment’s approximate weight and center of gravity. Refer to the tables listed below and placed on the following pages. Due to placement of internal components, the weight of the unit may be unevenly distributed, with more weight being present in the fan and coil areas) Table 1 T-Series Section Weights (lb) - Unit Sizes 3 - 50 Trane Unit Size 3 6 8 10 12 14 17 21 25 30 35 40 50 Filter / Mixing 225 232 270 367 393 443 490 526 624 687 933 1025 1148 Economizer 314 377 419 582 637 677 740 827 902 1118 1291 1544 1785 Exhaust 88 105 115 134 145 154 167 187 201 219 265 283 399 Air Blender 191 242 279 355 380 399 431 477 562 614 822 888 1080 Flat Filter 71 84 91 109 122 130 140 157 164 177 235 249 365 Angled Filter 154 199 232 242 261 290 312 338 355 389 545 590 684 Bag Filter 189 248 281 285 323 372 426 511 579 632 698 752 852 Cartridge Filter 143 181 213 218 235 266 284 317 334 368 494 538 621 Sm. Blank / Inspection 47 56 61 71 76 80 85 95 100 108 130 139 221 Med Blank / Access 62 75 80 95 101 105 113 125 132 143 169 181 269 M-L Blank / Access N/A N/A N/A 161 171 179 192 212 221 241 334 364 429 Large Blank / Access 105 137 164 218 232 243 261 289 361 393 541 584 662 117 151 170 210 238 255 285 323 353 390 448 487 757 182 250 294 363 431 476 539 641 722 824 897 1017 1444 N/A N/A N/A 649 788 842 967 1142 1298 1483 1759 1982 2550 Weight includes 10 row W 323 439 568 720 864 923 1054 1234 1465 1664 1986 2222 2804 Moisture Eliminator 59 80 93 147 167 182 202 231 254 289 347 385 554 Internal Face/Bypass 98 129 144 185 200 230 252 281 306 343 425 480 645 Face Damper 98 129 144 185 200 230 252 281 306 343 425 480 645 Small Coil Weight includes 2 row UW Med. Coil Weight includes 8 row UW M-L Coil Weight includes 10 row W Large Coil 4 CLCH-IM-16A Table 1 T-Series Section Weights (lb) - Unit Sizes 3 - 50 Trane Unit Size 3 6 8 10 12 14 17 21 25 30 35 40 50 300 444 500 508 599 652 762 905 1022 1277 2010 2168 2560 Weight includes Type A fan 347 500 561 580 676 731 847 1000 1122 1385 2139 2307 2780 Diffuser 74 91 98 114 122 130 143 163 173 192 293 322 445 Discharge Plenum 92 118 135 195 204 209 224 252 318 337 472 511 571 Front Horiz Disch Fan Weight includes Type A fan Bottom Vert Disch Fan Table 2 T-Series Section Weights (lb) - Unit Sizes 66 - 100 Table 2 T-Series Section Weights (lb) - Unit Sizes 66 - 100 Trane Unit Size 66 80 100 1850 2143 2608 3372 3884 4738 Med. Coil Trane Unit Size 66 80 100 Weight includes 8 row UW Filter / Mixing 1367 1511 1817 M-L Coil Economizer 2147 2382 2984 Weight includes 10 row W Exhaust 464 506 572 Large Coil Air Blender 1257 1386 1640 Weight includes 10 row W N/A N/A N/A Flat Filter 432 477 546 Moisture Eliminator 710 786 928 Angled Filter 797 839 964 Internal Face/Bypass 753 852 1002 Bag Filter 1046 1163 1414 Face Damper 753 852 1002 Cartridge Filter 761 798 911 Front Horiz Disch Fan Sm. Blank / Inspection 252 262 288 Weight includes Type A fan 3621 4391 5141 Med Blank / Access 307 319 350 Bottom Vert Disch Fan M-L Blank / Access 472 491 538 Weight includes Type A fan 3621 4391 5141 Large Blank / Access 775 870 1056 Diffuser 913 1029 1257 Discharge Plenum 651 769 928 Small Coil Weight includes 2 row UW 933 1040 1237 . Table 3 Inlet Guide Vane Weights (lb) Fan Type/ Unit Size 3 6 8 10 12 14 17 21 25 30 35 40 50 66 80 100 FC Fan N/A 38 38 43 46 55 57 65 70 70 105 128 155 155 N/A N/A BI Fan N/A N/A N/A 58 63 69 76 89 66 66 N/A N/A N/A N/A N/A N/A AF Fan N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 36 43 54 64 93 111 Plug Fan N/A N/A N/A N/A N/A N/A N/A 25 29 29 40 64 74 100 122 118 Installation and Maintenance 5 Table 4 Approximate Motor Weights (lb) Motor Type/ Horsepower 1/6 1/4 1/3 1/2 3/4 1 1-1/2 General Purpose ODP 16 21 24 26 28 32 35 General Purpose TEFC N/A N/A N/A N/A N/A 50 54 Energy Efficient ODP N/A N/A N/A N/A N/A 35 41 Energy Efficient TEFC N/A N/A N/A N/A N/A 36 46 VAV-ODP N/A N/A N/A N/A N/A 38 42 Motor Type/ Horsepower 2 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 General Purpose ODP 38 70 88 126 151 230 265 329 359 370 508 685 722 970 General Purpose TEFC NA 60 90 111 163 193 253 300 365 409 610 681 872 968 1255 Energy Efficient ODP 41 67 79 107 119 215 260 286 334 372 406 591 765 989 Energy Efficient TEFC 45 75 96 140 160 233 289 332 384 471 536 764 820 1302 VAV-ODP 42 87 91 132 147 230 220 331 352 450 509 796 825 1000 Table 5 Approximate Dry Cooling Coil Weights Type UU, UF, and UW, Fin Series 168 (Weights in lb) Unit Size Rows 3 6 8 10 12 14 17 21 25 30 35 40 50 66 80 100 2 41 58 69 88 110 122 138 175 197 222 247 274 358 458 548 666 4 63 94 114 146 181 203 232 289 329 376 425 475 621 804 956 1175 6 79 121 148 188 236 266 306 381 437 503 573 645 831 1083 1292 1604 8 94 147 182 231 290 329 380 473 545 631 721 814 1042 1362 1628 2032 Table 6 Unit Size 3, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type 6 Rows W 1 44 2 65 K 77 P2 41 P4 44 P8 D DD WD WA WC 44 39 66 TT NS 57 38 CLCH-IM-16A Table 6 Unit Size 3, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 P8 D DD 4 90 127 66 68 83 107 99 6 116 176 95 102 148 157) 123 8 141) 231 189 183 148 10 166 274 231 241 173 12 191 324 272 266 198 122 131 WD WA WC TT NS Table 7 Unit Size 6, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 1 53 2 81 93 56 59 4 119 155 95 96 6 157 217 136 142 8 194) 285 10 232 12 270 P8 D DD WD WC 53 48 81 135 127 189 198 164 243 236 201 341 297 307 238 403 351 345 275 175 WA 111 185 TT NS 73 54 Table 8 Unit Size 8, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 1 71 2 108 124 75 77 4 164 210 130 131 6 217 296 187 194 8 271 382 10 326 12 380 P8 D DD WD 175 259 273 227 334 327 280 469 409 425 334 555 484 480 387 Installation and Maintenance WC 71 66 109 183 244 WA 146 253 TT NS 97 72 7 Table 9 Unit Size 10, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 1 80 2 127 144 94 97 4 197 245 164 166 6 266 346 237 244 8 336 447 10 405 12 475 P8 D DD WD WC 80 75 128 218 209 308 322 275 398 392 344 548 489 505 412 650 579 575 481 308 WA 181 318 TT NS 114 91 Table 10 Unit Size 12, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 1 103 2 165 185 119 122 4 257 316 211 213 6 349 448 306 313 8 441 579 10 533 12 625 P8 D DD WD WC 103 103 166 284 274 402 421 361 521 513 452 710 638 661 542 842 756 75 633 400 WA 228 410 TT NS 142 116 Table 11 Unit Size 14, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type 8 Rows W K P2 P4 1 107 2 173 192 126 129 4 271 330 225 226 6 369 467 326 333 8 467 605 10 565 12 663 P8 D DD WD WC 107 107 173 297 287 42 441 381 547 539 477 742 671 693 574 880 796 426 WA 241 435 TT NS 149 123 CLCH-IM-16A Table 12 Unit Size 17, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 1 123 2 199 221 N/A N/A 4 316 381 N/A N/A 6 434 542 N/A N/A 8 551 703 10 667 12 786 P8 D DD WD WC 123 122 199 345 333 491 513 445 637 630 561 864 782 810 677 1025 928 928 792 N/A WA N/A N/A TT NS 172 145 Table 13 Unit Size 21, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 1 148 2 241 264 191 197 4 379 451 330 333 6 517 637 475 489 8 655 835 10 793 12 931 P8 D DD WD WC 149 139 241 411 396 581 600 528 752 738 664 1009 922 943 800 1195 1092 1081 936 617 WA 364 636 TT NS 214 184 Table 14 Unit Size 25, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K 1 170 2 277 305 219 225 4 440 524 384 386 6 604 743 553 567 8 767 969 10 930 1181 Installation and Maintenance P2 P4 721 P8 D DD WD WA WC 171 161 278 417 739 478 461 678 701 617 878 864 778 1078 1105 939 TT NS 247 213 9 Table 14 Unit Size 25, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K 12 1093 1401 P2 P4 P8 D DD WD 1278 1268 1100 WA WC TT NS WA WC TT NS 191 180 Table 15 Unit Size 30, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 1 190 2 312 340 254 260 4 505 588 448 450 6 697 837 647 661 8 889 1091 10 1082 12 1275 P8 D DD WD 313 542 526 771 794 709 1001 897 899 1333 1230 1257 1088 1582 1459 1450 1278 842 481 862 278 249 Table 16 Unit Size 35, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 P8 N/A N/A N/A D DD WD 1 275 2 379 413 4 616 717 660 642 6 853 1022 943 974 879 8 1091 1333 1224 1211 1116 10 1328 1631 1505 1544 1353 12 1565 1936 1788 1781 1590 WA WC 212 224 340 TT NS 333 298 Table 17 Unit Size 40, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type 10 Rows W 1 306 2 425 K 458 P2 P4 P8 N/A N/A N/A D DD WD WA WC NS 231 247 368 381 CLCH-IM-16A Table 17 Unit Size 40, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K 4 699 6 P2 P4 P8 D DD WD 800 743 724 973 1142 1062 1093 998 8 1247 1489 1381 1368 1273 10 1521 1825 1700 1738 1546 12 1795 2166 2018 2011 1820 WA WC NS WA WC NS 294 322 477 WA WC N NS 387 441 660 648 WA WC NS 453 494 753 Table 18 Unit Size 50, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 P8 N/A N/A N/A D DD WD 1 386 2 551 592 4 920 1044 975 953 6 1289 1496 1399 1440 1323 8 1658 1949 1823 1810 1692 10 2028 2400 2248 2297 2061 12 2397 2853 2672 2666 2431 491 Table 19 Unit Size 66, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 P8 N/A N/A N/A D DD WD 1 521 2 738 789 4 1242 1383 1302 1275 6 1740 1980 1866 1908 1776 8 2241 2577 2430 2409 2277 10 2742 3171 2994 3042 2778 12 3243 3768 3555 3543 3279 660 Table 20 Unit Size 80, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W 1 611 K Installation and Maintenance P2 P4 P8 N/A N/A N/A D DD WD 11 Table 20 Unit Size 80, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 P8 D DD WD 2 873 932 4 1471 1643 1547 1516 6 2068 2355 2219 2275 2114 8 2664 3066 2893 2872 2710 10 3262 3777 3565 3632 3307 12 3859 4490 4268 4228 3904 WA WC NS WA WC NS 546 603 909 778 Table 21 Unit Size 100, Approximate Dry Coil Weights, Fin Series 168 (Weights in lb) Coil Type Rows W K P2 P4 P8 N/A N/A N/A D 1 729 2 1065 1131 4 1815 2010 1900 1866 6 2565 2889 2733 2802 2613 8 3315 3771 3570 3552 3363 10 4062 4653 4404 4488 4113 12 4812 5529 5238 5238 4863 The Trane Company recommends that the contractor use spreader bars and slings to rig units and subassemblies (sections) as shown. q Always assemble the unit at the installation site. q Always rig subassemblies or sections as they ship from the factory. q Make the loop of the sling parallel to the direction of airflow, whenever possible. The following instructions cover lifting the unit as well as inlet and exhaust hoods and external pipe chases. Follow specific instructions. Follow good lifting practices before lifting the unit to include following instructions in this manual, estimating center of gravity, 12 WD 945 Lifting Instructions WARNING DD and test lifting the unit to check balance and stability. Do NOT use fork lifts for handling units. Never lift units in windy conditions or raise units above personnel. Failure to follow all instructions may result in personal injury or equipment damage. 1 Before lifting the unit, estimate the approximate center of gravity and test lift the unit to determine balance and stability. NOTE: PREPARATION OF THE ROOF CURB OR PIER MOUNT AND ROOF OPENINGS SHOULD BE COMPLETED BEFORE LIFTING UNIT TO THE ROOF. SEE THE ASSEMBLY SECTION OF THIS MANUAL. CLCH-IM-16A USE ALL OF THE LIFT LUGS PROVIDED. Lifting the External Pipe Cabinet (Chase) NEVER STACK THE PIPE CABINET AND INLET HOODS ON THE UNIT AS THE UNIT IS BEING LIFTED. 2 Lift all sections individually using all lifting lugs provided and shown in Figure 4 . See specific instructions for handling the inlet and exhaust hoods and pipe chase in paragraphs following. 3 Remove all wooden blocks before installing the unit to the roof curb (see Figure 5 ). 4 After the sections are in place, assemble them (see Unit Assembly). Lifting Inlet and Exhaust Hoods CAUTION Do not attach the hood to the unit prior to lifting the unit. Doing so could damage the equipment. CAUTION Do not attach the pipe chase to the unit prior to lifting the unit. Doing so could damage the equipment. Follow all warnings lifting instructions in the general Lifting section of this manual to include test lifting. Lift the pipe chase section individually as shown in Figure 3 . Attach the cables, chains or straps to lifting lugs as shown. Attach the pipe chase to the unit only after all sections are in place. Figure 3 Pipe Cabinet Lifting Rigging and spreader bar not furnished by Trane Follow all warnings lifting instructions in the general Lifting section of this manual to include test lifting. Lift the hood sections individually as shown in Figure 2 . Attach the cables, chains or straps to lifting lugs as shown. Recommended attachment to lifting lugs Attach the hood to the unit only after all sections are in place. Figure 2 Inlet and Exhaust Hood Lifting Recommended attachment to lift lugs Installation and Maintenance 13 Figure 4 Field Unit Lifting Rigging and spreader bars not furnished by Trane Recommended attachment to lifting lugs Figure 5 Shipping Block Removal Remove ALL wooden blocks before installing unit to roof curb 14 CLCH-IM-16A ,QVWDOODWLRQ 2 Allow sufficient space for the recommended service access. Refer to Figure 6 for FC, BI and AF fan wheels and for plug fans. When preparing the unit site, consider the following: 3 Confirm that the foundation of the mounting platform is large enough to include the unit dimensions. Refer to unit submittals for specific dimensions. 1 Ensure that the site can support the total weight of the unit. Table 1 and Table 2 list approximate section weights. Figure 6 Service Clearances Filter Drive Coil Fan A B C D Table 22 Service Clearances (in inches) Table 22 Service Clearances (in inches) Unit Size Filter A Coil Removal B Unit Size Fan C Starter D 3 48 48 48 60 6 48 60 48 60 8 48 64 48 60 10 48 75 51 60 12 48 79 54 60 14 48 83 58 60 17 48 89 61 60 21 48 91 60 60 25 48 93 66 60 30 48 106 66 60 35 48 110 65 60 40 48 123 70 60 50 48 134 77 60 Installation and Maintenance Filter A Coil Removal B Fan C Starter D 66 52 150 93 60 80 56 150 91 60 100 58 165 101 60 The floor or foundation must be level for proper coil drainage and condensate flow. 4 Allow the proper height for condensate drain requirements. Insufficient height may inhibit condensate drainage and result in flooding the unit. 5 Provide adequate lighting for maintenance personnel to perform maintenance duties. 6 Provide permanent power outlets in close proximity of the unit for installation and maintenance. 15 8QLW$VVHPEO\ The T-Series Climate Changer is extremely versatile and can be assembled in many configurations. Prior to unit assembly, refer to the correct submittals and unit tagging for correct placement of accessory sections. Failure to review the submittal could result in performance or assembly problems. If there are any discrepancies, contact your local Trane representative before proceeding. IMPORTANT: All shipping support screws on the face of the sections and sectional subassemblies must be removed and discarded to permit proper fitup and sealing of the surfaces. General WARNING To avoid personal injury or death keep open flame away from unit exterior or interior. Do not weld or use cutting torch on the exterior or interior of the unit. The unit contains polyurethane insulation. Failure to keep open flame away from unit exterior or interior may result in the production of toxic gas that could result in death or serious injury. piping, ductwork, electrical connections, and coil removal. The building roof must be able to support the entire weight of the unit, roof curb and accessories. See Table 1 thru Table 4 for unit and accessory weights. q Prepare the roof curb or pier mount and roof openings before hoisting the unit to the roof. q Check that the gasketing is intact and provides an airtight seal with the unit base. Refer to the applicable roof curb installation manual. q Complete all ductwork, piping and electrical connections only after mounting the unit. Refer to unit submittals. All T-Series Climate Changer units are identified by a multiple-character model number that identifies each section. It is located on the panel on the inside of the supply fan section access door. Be sure to refer to the information on the nameplate when ordering replacement parts or requesting service Assembly Hardware T-Series Climate Changers ship with all necessary assembly hardware and gasket material. This hardware is packaged in either a clear plastic envelope or cardboard box and can be found inside the Fan section, Access section, or Mixing section. The number of sections to be assembled often makes it necessary to use more than one section to ship the material. Please check all sections thoroughly before contacting your Trane Company Representative to report missing hardware. Unit Assembly - All Sizes CAUTION The internal sections of this unit containing electrical components must not exceed 104o F temperature. Internal sections of the unit not containing electrical components must not exceed 180o F temperature. Failure to comply with temperature requirements may cause equipment damage. Units may be mounted on the roof with a roof curb or pier mount. Refer to submittals for dimensions and roof openings. Provide clearance around the unit to allow adequate free air and necessary service access. Also, allow room for supply and return 16 Mounting If a unit arrives in sections, then each section must be individually hoisted, set on a roof curb or pier mount and assembled. The pipe cabinet must also be mounted as an individual section. Refer to the pipe cabinet assembly section following for specific instructions. When mounting the unit on its roof curb or pier mount make sure that the gasketing between the roof curb or pier mount and unit base provides an airtight seal. See Figure 7 and Figure 8 for suggested pier/rail mounting. CLCH-IM-16A Locate one pier at each corner, as a minimum, directly underneath any shipping split (ensure full support under each side), and then every four feet at equally spaced intervals around the perimeter of the unit. Both the unit and the pipe cabinet should be supported by their base channel around the entire perimeter. Figure 7 Pier Locations (Typical) C C CHECK THAT THE UNIT IS LEVEL TO ENSURE PROPER OPERATION. IMPORTANT: FOR PROPER OPERATION, THE UNIT MUST BE INSTALLED LEVEL (ZERO TOLERANCE) IN BOTH HORIZONTAL AXES. FAILURE TO LEVEL THE UNIT PROPERLY CAN RESULT IN CONDENSATE MANAGEMENT PROBLEMS SUCH AS STANDING WATER INSIDE THE UNIT. STANDING WATER AND WET SURFACES INSIDE AIR HANDLING UNITS CAN RESULT IN MICROBIAL GROWTH (MOLD) IN THE DRAIN PAN THAT MAY CAUSE UNPLEASANT ODORS AND SERIOUS HEALTH-RELATED INDOOR AIR QUALITY PROBLEMS. Piers Figure 8 Side View of Unit with Two Shipping Splits For vertical discharge units, allow space under the unit for supply air ductwork connections. Assembling the Unit Before sections are joined for final assembly, a butyl tape seal must be made at the roof connection and then hardware and sealing metal strips are installed at the base assembly, the roof joint or joints and both side panel seams. 4’ Typ Unit Supports for Pier Mounts NOTE: PIERS BENEATH SHIPPING SPLITS MUST BE STRUCTURALLY SOUND TO SUPPORT THE WEIGHT OF THE UNIT Roof Assembly (for Unit Sizes 50-100 only) Figure 9 Roof Assembly Roof Panels Joint Strip Cross Butyl Tape (2 Rows) Installation and Maintenance 17 NOTE: THE BUTYL TAPE APPLIED THE ROOF PANELS WILL COVER THE DRILLED HOLES. 1 Apply butyl tape along four roof panel seams where they come together. IMPORTANT: FOR PROPER UNIT OPERATION, THE FOAM BLOCKS MUST BE INSTALLED IN THE RACEWAY. FAILURE TO INSTALL THE FOAM BLOCKS CAN RESULT IN CONDENSATE MANAGEMENT PROBLEMS. 2 Join the panels together at the seams and secure them in place with 5/16 X 3/4” screws and nuts. 6 Remove backing from inner access cover tape and replace inner access cover. 3 Apply a strip of butyl tape along the center of the joint and place the cross cover directly over it as shown in Figure 10 . 7 Remove backing from outer access cover tape and replace outer access cover. 4 Slide the three roof joint strips (one long and two short) along the flat flange formed by the joined roof panels in the three directions shown, allowing 4” overhang at the ends. 5 Crimp down the three overhanging ends and secure with #10-16 x 3/4” self-drilling screws. Figure 10 Roof Assembly Joints Roof Joint Strip Cross Cover Butyl Tape Outer Roof Panel Unit Sizes 50-100 Control Wiring Assembly at Section Splits (All Unit Sizes) (Reference Figure 11 ) 1 Sections Must be together 2 Remove outer and inner raceway access covers on both sections adjacent to shipping split. 3 Remove top foam blocks in raceway. 4 Route wire harness(es) under inner roof through raceway and make connection to corresponding wire harness. 5 Replace foam blocks. 18 CLCH-IM-16A Figure 11 Control Wiring Assembly Outer Access Cover Tape Wire Harness Inner Access Cover Foam Block Roof Assembly at Section Splits (All Unit Sizes) Base Assembly 1 Apply two rows of butyl tape at the roof seams, covering the hole pattern. 1 Slide the 1/2” threaded rod through the hole in each of the two joined base sections as shown. 2 Align the roof panels together at the seams and bring the two sections together. Secure the roof panels in place with 5/16 X 3/4” screws and 5/16” nuts. 2 Install two flat washers, lockwasher, and 1/2” nut at each rod end. Tighten both nuts. 3 Slide the roof joint strip along the flat flange formed by the joined roof panels, allowing 4”hang on the ends. 4 (For Unit Sizes 3 - 40 when the roof joint strip is in two pieces): Apply a piece of butyl tape where the strips come together and place a cover directly over the tape. Then slide the two strips on the roof panels as shown in Figure 12 . 3 Install the flashing piece on the base assembly. Secure in place with two #10-16 x 3/4” sheet metal screws. 4 Repeat steps 1 - 3 for the base assembly on the other side of the unit. Figure 13 Joining Base Assembly Flashing 5 Crimp down the two overhanging ends and secure with #10-16 x 3/4” sheet metal screws. Figure 12 Roof Assembly at Section Splits Roof Joint Strip (in 2 Pieces) Threaded Rod Cover Base Sections Flat Washers, Lockwasher and 1/2” Nut Panel Assembly Outer Roof Panel Unit Sizes 3-40 Installation and Maintenance 1 Leaving the paper backing on the tape, apply butyl tape (tape side down) along the length of the panel seam. 19 NOTE: THE SEAM CAP SHOULD BE CUT TO SIZE TO COVER THE SEAM AND TAPE. 2 Install the seam cap directly over the seam and tape. Attach using #10-16 x 3/4” screws through all predrilled holes in the cap. 3 Caulk the gap between the top of the seam cap and the bottom of the raceway. Figure 14 Panel Assembly Raceway Hood (Back and Side) Installation Inlet hoods should be installed after the unit has been set in place. They should not be stacked on the unit as it is being hoisted. Mounting hardware and caulking tape for the inlet hoods are located inside the unit. For installation complete the following: NOTE: THE HOOD ASSEMBLY SHOULD BE SUPPORTED BY CHAINS, SPREADER BAR, OR OTHER MEANS (SEE LIFTING INSTRUCTIONS SECTION) WHEN INSTALLED TO THE UNIT. MOUNTING TAPE AND HARDWARE ARE LOCATED INSIDE THE UNIT. 1 Apply the 1” butyl tape in a strip around the perimeter of the hood. 2 Using the lifting lugs, hoist the hood and center it over the panel opening as shown in. Seam Cap Outer Panel #10 Screw Base Butyl Tape 3 Attach the hood to the unit with the 1/4-20 selfdrilling screws provided. Use ALL holes drilled in the attachment flanges. 4 Attach the two hood angle supports (when provided) to the hood at one end and the bracket on the unit as shown. Secure with 5/16” lock bolts and lock nuts and #10-3/4 self-drilling screws. Figure 15 Hood and Pipe Cabinet Installation Angle Support Butyl Tape Hood #10 Screw 20 CLCH-IM-16A Pipe Cabinet (Chase) Installation to the unit panel with #10 screws. Installation of the cabinet will be different depending on the extent of the piping installation. Follow the appropriate instructions below. 6 If piping is already run through the roof, follow steps 6 through 13. First remove the Z bar from the pipe cabinet. INSTALLATION OF THE PIPE CHASE CABINET REQUIRES ASSEMBLY OF THE CURB AND INSTALLING THE CABINET TO BOTH THE CURB AND THE UNIT AS DESCRIBED BELOW. 7 Remove the paper backing from the butyl tape on the Z bar and set the Z bar on top of the gutter THE PIPE CABINET SHOULD BE SUPPORTED BY CHAINS, SPREADER BAR, OR OTHER MEANS (SEE LIFTING INSTRUCTIONS SECTION) WHEN INSTALLING. MOUNTING TAPE AND HARDWARE ARE LOCATED INSIDE THE UNIT. 9 Attach the Z bar to the gutter with #10 screws. 1 Assemble the pipe cabinet curb and attach to the roof or mounting surface. 2 If piping is not already run through the roof, follow steps 2 through 5 only. First remove the paper backing from the butyl tape on the Z bar and pipe chase side panels. (A gasket should already be in place from the curb installation.) Set the cabinet on top of the curb. 8 Attach the Z bar to the unit side panel with #10 screws. 10 Remove the paper backing from the butyl tape on the pipe chase side panels. Set the cabinet on top of the curb (Figure 17) . Figure 17 Pipe Cabinet Attachment Attachment Flange Panel Removed to Show Z Bar Figure 16 Pipe Cabinet Installation Unit Side Panel Z Bar Attachment Angle Z Bar NOTE: USE ALL HOLES DRILLED IN THE ATTACHMENT FLANGES. Pipe Cabinet Base Rail Gutter Gutter 11 Attach the pipe cabinet side flanges to the unit panel with #10 screws. 12 Attach the pipe cabinet base rail to the Z bar with bolts provided. 13 Apply caulk between the Z bar, the cabinet side flanges, the base and around the drain connection hole. 3 Attach the Z bar to the unit side panel with #10 self-drilling screws (Figure 16) . 4 Attach the Z bar to the gutter with #10 screws. NOTE: USE ALL HOLES DRILLED IN THE ATTACHMENT FLANGES. 5 Attach the pipe cabinet side (attachment) flanges Installation and Maintenance 21 Component Installation Requirements The T-Series Climate Changer is extremely versatile and the assembled unit is a complete air handling system. Each section may have installation requirements that will affect the performance of the unit. High Efficiency Bag and Cartridge Filter Section The Bag and Cartridge Filter sections can be used as either a pre-filter section, a Final Filter section or both. This is determined by placement in relation to the fan. Filter Installation NOTE: CARTRIDGE AND BAG FILTERS PROVIDED BY TRANE ARE FITTED WITH A 7/8” HEADER THAT FITS IN THE FILTER TRACK. IF USING FILTERS SUPPLIED BY ANOTHER MANUFACTURER, FILTERS SHOULD BE PURCHASED WITH A 7/8” HEADER. IN SOME CASES IT MAY BE NECESSARY TO GASKET THE LOCALLY PURCHASED FILTERS TO INSURE A GOOD AIR SEAL. 6 Close the access door and confirm that there is a good seal of the filter track block-off against the access door. Fan Section The Fan section can be configured as either drawthru or blow-thru. Review the submittals and unit tagging prior to assembly. The fan and motor assembly are internally isolated. The fan and motor bases are bolted to four spring isolators (see Figure 19 ). The isolators are secured to the fan section support base. Four (4) shipping tiedowns are bolted adjacent to the isolators between the fan isolation base and the support frame. The shipping tie-downs secure the isolation base to the support assembly to prevent any damage to the fan section during shipment of the air handler. The shipping spacers must be removed prior to unit operation unless the unit is to be externally isolated. FILTERS SHOULD BE INSTALLED WHEN THE UNIT IS SET. THIS WILL PROTECT INTERNAL COMPONENTS SUCH AS THE UNIT’S HEATING AND COOLING COILS. Trane recommends the use of disposable pre-filters with high efficiency filters. Disposable pre-filters slide into the mounting tracks just ahead of the bag/ cartridge filters. WARNING Pressurized Cabinet! Disconnect all electric power before opening door. Failure to disconnect power before servicing can cause severe personal injury. 1 Disconnect the power to the unit. 2 Open the filter section access door. 3 Remove the adjustable block-off from the filter track. 4 Slide the filters into the tracks. Note that bag filters must be installed with the pleats in the vertical plane. 5 Slide the adjustable block-offs into the filter track. The block-off is intended to make a seal when the access door is closed. It is adjustable and may require a few changes to insure a proper seal. 22 CLCH-IM-16A Figure 18 Shipping Spacer Bolt Spring Spacer Tie-Down Bolt Flat Washer Flat Washers Spring Tie-Down Removal, Sizes 3-8 Tie-Down Removal, Sizes 10-50 Unit Isolation Review the mechanical specifications and determine the type of isolation to be used prior to removing the shipping tie-downs. Remove the tie-downs only if the factory provided isolation is to be used. If external isolation is intended, review the portion of this manual titled “External Isolation.” Internal Isolation The T-Series Climate Changer Fan section is internally isolated. The unit ships with the internal isolation base secured to prevent damage to the fan and motor assembly during shipment. To activate the isolation, remove the shipping tie-downs. Shipping Tie-down Removal There are four types of shipping tie-downs used to secure the isolation base: q Sizes 3 - 8 use a 3/8”x1” pipe. (See Figure 18 .) q Sizes 10 - 30, except plug fans, use washers with a bolt. (See Figure 18 .) q Sizes 35 - 50, except plug fans, use a tie-down bolt and shim. (See Figure 18 .) q Size 66 -100 and plug fans use a tie-down angle and bolt. (See Figure 19 .) Installation and Maintenance 23 Figure 19 Shipping Angle and Isolator Tie-down Removal for Unit Sizes 66, 80 and 100 (Includes Plug Fans) Screw, Lockwasher and Hex Nut (Four per Angle) Angle, Isolator Tie-Down (Four Required) Remove the shipping tie-downs per the following instructions: 1 Shipping tie-downs are located at each corner of the isolation base. Access for removal of shipping spacer is available through the fan module access doors. 2 Remove the bolt. This will release the isolator and make it possible to remove the pipe or spacer. Isolator Adjustment Table 23 Isolator Minimum Clearance Adjustments (in) Fan Type Isolator Type Req’d Clearance 3-8 FC Rubber 1.0 3-8 FC Spring 1.0 10-30 FC Rubber 0.5 10-30 FC and BI Spring 0.5 21-50 Plug Spring 0.5 FC & AF Spring 0.5 FC, AF & Plug Spring 1.0 Unit Size 35-50 66-100 Once the shipping tie-downs are removed and the internal isolation is released, it may be necessary to adjust the isolators to achieve the proper operation height of the fan and motor isolation base. The isolators are bolted between the fan and motor isolation base. There are five designs based on unit size and fan type. Specific isolator clearances are listed in Table 23 . The measurement is taken between the top of the floor panel (or support channel on sizes 66-100) and the bottom of the isolation base channel for all sizes. 24 CLCH-IM-16A 6HW8S Figure 21 Typical Internal Face and Bypass Configuration Once the T-Series Climate Changer is assembled and installed, attention must be directed to individual components for proper operation. Dampers Open (Including filter mixing sections, mixing sections, face and bypass dampers and Traq dampers) Before installing the Mixing sections fitted with filter racks, be sure adequate clearance is provided to open the access doors and install the filters. Filter installation is explained in the section titled “Filter Installation.” Figure 20 Typical Mixing Box Configuration (sizes 3-100)s Close actuators. The actuators should be sized according to the torques given in Table 24 . NOTE: MIXING SECTIONS, AND FACE AND BYPASS DAMPERS ARE DESIGNED, FOR THE DAMPER ACTUATORS TO BE DIRECT COUPLED AND INSTALLED IN THE AIR STREAM. IF OTHER PROVISIONS ARE REQUIRED, MODIFICATIONS TO THE SECTION WILL BE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR. Rods, Operators and Settings The T-Series Climate Changer is available with factory mounted controls or end devices. If the unit is not ordered with controls or end devices, it is the responsibility of the installer to provide and install the Dampers are factory installed and adjusted. There are three damper blade configurations available: parallel blade, opposed blade, and Traq dampers. Opposed and Parallel Dampers Opposed and parallel dampers in units size 3 through 100 have an internal jack-shaft. See Figure 21 . A 90° jack shaft rotation gives a 95° blade travel. Installation and Maintenance 25 Table 25 Torque and Force Required to Operate Inlet Vanes (FC, BI, and AF Fans) in lb-in Table 24 Damper Torque at 1 in wg, Air Pressure Drop in lb-in Fan Outlet Velocity Unit Size Mixing Box (Back and Bottom) Internal Face and Bypass Face Damper Economizer Exhaust Side Mixing Box 3 8 10 9 6 6 14 15 14 9 16 24 19 12 10 38 41 25 16 12 43 44 33 19 35 Unit Size 12 8 59 2000 FPM 14 23 Fan Size Open (Torque) Close (Torque) Open (Torque) Close (Torque) 13BI 38.0 N/A 40.0 N/A 15 FC 14.1 5.0 31.9 11.4 16 FC 18.0 6.4 40.5 14.4 15 BI 38.0 N/A 40.0 N/A 16 FC 18.0 6.4 40.5 14.4 18 FC 23.1 8.3 52.2 18.6 16 BI 44.0 N/A 50.0 N/A 18 FC 23.1 8.3 52.2 18.6 20 FC 24.0 9.0 54.0 19.5 18 BI 54.0 N/A 60.0 N/A 14 44 17 65 64 45 26 21 66 79 53 30 25 85 95 62 36 30 101 112 65 44 35 138 90 95 52 40 148 100 106 60 50 162 136 144 76 24 FC 31 7 70 17 30 FC 150 65 220 120 27 FC 115 46 200 104 27 AF 46 11 103 25 17 21 25, 30 35 66 218 201 181 103 80 245 230 224 122 100 307 291 284 151 40 50 Table 25 Torque and Force Required to Operate Inlet Vanes (FC, BI, and AF Fans) in lb-in 66 Fan Outlet Velocity 2000 FPM Unit Size 3000 FPM Fan Size Open (Torque) Close (Torque) Open (Torque) Close (Torque) 3 9 FC N/A N/A N/A N/A 6 12 FC 10.0 3.5 22.5 7.8 10 FC 5.7 2.9 19.6 6.5 13 FC 10.9 3.9 24.5 8.7 12 FC 10.0 3.5 22.5 7.8 13 FC 10.9 3.9 24.5 8.7 15 FC 14.1 5.0 31.9 11.4 8 10 26 3000 FPM 80 100 20 FC 24.0 9.5 54.0 19.5 22 FC 25.0 9.5 56.0 21.0 20 BI 66.0 N/A 74.0 N/A 22 FC 25.0 9.5 56.0 21.0 25 FC 26.5 10.0 59.7 22.5 22 BI 90.0 N/A 100.0 N/A 27 fc 115 46 200 104 25 FC 26 1 59 22 33 FC 215 100 310 180 30 FC 150 65 220 120 30 AF 62 15 142 35 33 FC 215 100 310 180 36 AF 113 27 256 63 33 AF 84 20 189 46 40 AF 100 62 216 140 36 AF 113 27 256 63 33 AF 84 20 189 46 44 AF 124 80 278 181 40 AF 100 62 216 140 36 AF 113 27 256 63 CLCH-IM-16A Traq Dampers Traq dampers are fitted in mixing sections in several possible configurations. These low leak dampers modulate and measure air flow. Each Traq damper section is supplied with a factorymounted ventilation control module (VCM) on the interior of the mixing box. The VCM has an input terminal for power and an output terminal for air velocity. (See Figure 22 .) Figure 22 Traq Damper Terminal Connections. VCM Velocity (2-10 VDC) GND 1TB1-3 1TB1-4 24 VAC 1TB1-5 GND 1TB1-6 The actuators, factory-mounted or field-supplied, are separately wired and controlled by a PCM or other building logic. Figure 23 illustrates the typical quick connect scheme. Figure 23 Typical Quick Connects with Wiring Identification VCM (Transducer) Calibration The VCM has an auto-zero function that recalibrates the transducer once every minute. TSC Size cfm @ 10V L/s @ 10V Input Power Signal 3 2304 1087 The only input signal the VCM needs is the 24 VAC power connected to terminals TB5 and TB6. 6 4609 2175 8 4609 2175 10 6913 3263 12 10900 5145 14 10900 5145 17 10900 5145 21 16650 7859 25 10900 5145 30 24970 11786 35 24970 11786 40 24970 11786 Output Velocity Signal The 2 - 10 VDC linear output signal from the VCM represents air velocity. This voltage can be converted to represent cfm or L/s using the formula and Table 26 following. For example, if the VCM on a Size 21 T-Series Climate Changer has a 10-volt signal, it would represent 16650 cfm (7859 L/s) through the Traq damper. If this voltage is 6 volts, air flow through the Traq damper would be 8325 cfm (3930 L/s). Using the formulas 50 34630 16345 cfm = k (cfm @ 10V) [volts-2/8] 66 46200 21806 L/s = k (L/s @ 10V) [volts-2/8], and tables following 80 57820 27291 100 69270 32695 Installation and Maintenance 27 For Traq Dampers, use the following table. Table 26 VCM Voltage Versus Airflow - Traq Dampers (at Sea Level) Side Installation TSC Size Back Installation cfm @ 10V L/s @ 10V cfm @ 10V L/s @ 10V 3 4609 2175 2304 1088 6 4609 2175 4609 2175 8 4609 2175 4609 2175 10 7400 3493 6913 3263 12 7400 3493 11100 5239 14 7400 3493 11100 5239 17 9218 4351 11100 5239 21 9218 4351 11563 5458 25 14800 6986 16965 8007 30 14800 6986 17344 8186 35 23126 10915 24970 11786 40 23091 10899 25447 12011 50 23126 10915 34636 16348 66 33929 16014 46181 21797 80 46181 21797 57727 27247 100 50894 24022 69272 32696 Altitude can be adjusted for using the following factors: Elevation (ft) “k” Elevation (ft) “k” Sea Level 1.000 6000 0.897 1000 0.982 7000 0.876 2000 0.964 8000 0.860 3000 0.949 9000 0.846 4000 0.930 10000 0.825 5000 0.914 Inlet Guide Vanes Inlet guide vanes can be provided with factory mounted actuator motors when ordered with factory mounted controls or end devices. If actuators are not ordered factory mounted, it is the responsibility of the contractor to provided the actuator and all mounting hardware. The Inlet guide vanes are designed for the actuators to be internally mounted in the fan section. Size the actuators based on operating torque requirements. 28 NOTE: TO PROVIDE EVEN TORQUE DISTRIBUTION AND RELIABLE VANE TRACKING, IT IS RECOMMENDED THAT TWO EQUALLY SIZED ACTUATORS BE MOUNTED ON EACH SIDE OF THE FAN HOUSING FOR UNIT SIZES 35, 50, 66, 80, AND 100. BEFORE OPERATION, INSPECT THE VANE ASSEMBLY FOR FREEDOM OF MOVEMENT. IF RESISTANCE IS ABOVE THE TORQUES GIVEN IN TABLE 25 CHECK THE ASSEMBLY FOR ANY BINDING OR MISALIGNMENT. DO NOT FORCE THE VANES. Duct Connections All duct connections to the T-Series Climate Changer should be installed in accordance with the standards of the National Fire Protection Association(NFPA) for installing of air conditioning and ventilating systems other than residence type (NFPA 90A), and residence type warm air heating and air conditioning systems (NFPA 90B). See unit submittal documentation for additional duct mounting information. To ensure the highest fan efficiency, duct turns and transitions must be made carefully minimizing air friction losses and turbulence. Proper duct work CLCH-IM-16A installation, as outlined by such organizations as SMACNA (Sheet Metal and Air Conditioning Contractors National Association, Inc.) should be adhered to. Figure 24 Typical Section with Duct Flat/Flange Connections Uninsulated Cut Fan Discharge Connections Section When using lined duct, the insulation should not obstruct the discharge opening. (See Figure 24 .) Airflow Connections made directly to the discharge opening of the fan should have a minimum of 3 fan diameters of straight duct before any turns or transitions. The first turn of the connection should be in the same direction as the fan rotation. The air that the fan discharges into the duct is extremely turbulent and requires some length of duct to stabilize. Abrupt changes in duct work directly off the fan discharge will affect fan performance. Flat Connection Insulated Duct Damper Sections Section Standard damper sections include mixing sections, filter mixing sections, face damper sections, internal face and bypass sections, and economizer sections. Airflow Duct work attached to the standard damper sections should be sized to fit the opening of the damper. This information is provided in the submittals. When using lined duct, ensure that the insulation does not obstruct the damper opening. (See Figure 24 .) Flat Connection Traq Dampers Traq dampers are installed in mixing sections. Size the duct connection to attach to the specified portion on the face of the section. (See Figure 25 .) Figure 25 Traq Damper Duct Connections Mitered Corner Radius Elbow (Sweep) Traq Damper Mixing Box Inlet Duct H d Traq Damper Mixing Box W d = 1 hydraulic duct diameter = 2 xWxH ________ W+H Installation and Maintenance 29 Discharge Plenum Discharge plenum sections are available with or without openings. Sections with openings have a framed opening that can be used to secure the duct to the frames. If the duct is lined, it is important that the insulation does not obstruct the opening of the section. NOTES: THE DRAIN CONNECTION SIZE IS 1” NPT EXTERNAL FOR UNIT SIZES 3 THROUGH 30; 1-1/2 NPT EXTERNAL FOR UNIT SIZES 35, 40, 50; 1-1/4” INTERNAL THREADS ON SIZES 66, 80, 100. DRAIN PANS MUST BE PRIMED AT START-UP TO OPERATE PROPERLY. Miscellaneous Sections Miscellaneous sections include access sections, coil sections, fan sections and intake sections. If the duct is lined, it is important that the insulation does not obstruct the opening of the section. Internal Face and Bypass Duct connections for internal face and bypass damper sections are similar to the miscellaneous sections. Duct work can be attached directly to this frame. Drain Pan Piping Condensate Drain Pan Connections CAUTION Failure to provide adequate condensate piping may result in water damage to the equipment and or building. Threaded condensate drain connections are provided on only one side of the coil section. Pitch the connection lines horizontal or downward toward an open drain. Trane recommends installing a plug to facilitate cleaning of the trap. IMPORTANT: PROPER TRAPPING OF THE COOLING COIL CONDENSATE DRAIN LINES IS NECESSARY FOR PROPER CONDENSATE MANAGEMENT. IMPROPER TRAPPING CAN RESULT IN STANDING WATER INSIDE THE UNIT OR WET INTERIOR SURFACES THAT CAN CAUSE UNPLEASANT ODORS AND SERIOUS HEALTH-RELATED INDOOR AIR QUALITY PROBLEMS. It is essential that the drain pan condensate trap be deep enough and of the correct design to ensure a water seal in the trap while allowing the condensate pan to drain. Insufficient depth or incorrect design can cause the drain pan to overflow. 30 CLCH-IM-16A Figure 26 Drain Pan Trapping for Section under Negative Pressure Normal Operation 3C - Normal Operation H H LL JJ H= (1" for each 1" of maximum negative static pressure) + 1" H = (1” for each 1” of maximum negative pressure) + 1” J= half of H L = H + J + Pipe Diameter + Insulation J = 1/2 H L= H + J + Pipe Diameter + Insulation Figure 27 Drain Pan Trapping for Section under Positive Pressure 2C - Normal Operation K H H K= min. 1/2" K = min. 1/2” H= 1/2" plus maximum total static pressure H = 1/2” plus maximum total static pressure Negative Pressure Section Positive Pressure Section Trap the drain pan as illustrated in Figure 26 , which also illustrates the proper piping as well as the operation of the trap. Use the formula given in Figure 26 to determine the correct minimum depth for the condensate trap. The positive pressure section requires a different design than the negative pressure trap. Refer to Figure 27 and the formula provided to determine the minimum trap depth. Installation and Maintenance 31 Units With More Than One Drain Pan the unit. The contractor should supply the pipe nipples, couplings, etc.for installation. With the T-Series Climate Changer, each section can be ordered with or without a drain pan. When more than one section has a drain pan, you must trap each section individually. Connecting all drains to a common line with only one trap will result in condensate retention, and possible water damage to the air handler or adjoining space. If a section has a drain pan for cleaning purposes only, it does not need a trap; however a cap or shut off valve should be installed on the drain connection. Only sections handling condensate, such as a cooling coil section or eliminator section, require a trap. Figure 28 through Figure 37 are examples of typical installations. Coil Piping And Connections See Table 27 through Table 29 for connection sizes. For supply, vent and drain connections, refer to Figure 28 through Figure 37 . NOTE: DRAIN AND VENT CONNECTIONS ARE PROVIDED AS STANDARD ON UW, UU, DD, AND D COILS ONLY. ALL OTHERS, IF REQUIRED, MUST BE FIELD INSTALLED. NOTE: DRAIN AND VENT CONNECTIONS ON THE UU AND UW COILS ARE RECESSED. IF EXTENDED DRAINS AND VENTS ARE REQUIRED, THEY MUST BE FIELD PROVIDED. General Coil Piping Recommendations Proper installation, piping and trapping is necessary to ensure satisfactory coil operation and to prevent operational damage. q Support all piping independently of the coils. NOTE: WHEN USING ELECTRONIC VALVE ACTUATORS ON CHILLED WATER VALVES, THE VALVE SHOULD BE MOUNTED ABOVE THE HORIZONTAL POSITION TO PREVENT COLLECTION OF CONDENSATE IN THE ACTUATOR ELECTRONIC CIRCUITS AND SUBSEQUENT ACTUATOR FAILURE. WHEN USING ELECTRONIC VALVE ACTUATORS ON HOT WATER OR STEAM COILS, THE ACTUATOR SHOULD BE INSTALLED APPROXIMATELY 45 DEGREES FROM VERTICAL. VERTICAL INSTALLATION OF A VALVE ACTUATOR ON A HOT WATER OR STEAM COIL WILL EXPOSE THE ACTUATOR TO HIGH TEMPERATURES, RESULTING IN ACTUATOR FAILURE. THE EXTERNAL CABINET IS ONLY SUFFICIENTLY SIZED FOR HOUSING COIL PIPING. ALL VALVES AND VALVE ACTUATORS MUST BE LOCATED ELSEWHERE. For best results, The Trane Company recommends that a short pipe nipple be used on the coil headers prior to making any welded flange or welded elbow type connections. IMPORTANT: TEFLON TAPE OR PIPING COMPOUND SHOULD NOT BE USED FOR ANY FIELD CONNECTIONS BECAUSE ITS HIGH LUBRICITY MAY ALLOW CONNECTIONS TO BE OVER-TIGHTENED, RESULTING IN DAMAGE TO THE COIL HEADER. NOTE: USE A BACK-UP WRENCH WHEN ATTACHING PIPING TO COILS WITH TUBE HEADER CONSTRUCTION TO PREVENT DAMAGE TO THE COIL HEADER. DO NOT USE BRASS CONNECTORS. BRASS DISTORTS EASILY AND COULD CAUSE CONNECTION LEAKS. When attaching the piping to the coil header, make the connection only tight enough to prevent leaks. Maximum recommended torque is 200 pound-feet. q Provide swing joints or flexible fittings on all connections that are adjacent to heating coils in order to absorb thermal expansion and contraction strains. Use pipe sealer on all thread connections. q If ordered with factory mounted controls, install the control valves. The valves ship separately in After completing the piping connections, use mastic to seal between the pipe and casing before insulating the pipe. Table 27 Shipping Coil Water and Steam Connection Sizes Coil Type Header Height Supply Return Drain/Vent W, WA 18, 24, 30, 33 2-1/2 2-1/2 1/2 W 42, 48, 54 2-1/2 2-1/2 1/2 D, DD, WD, K 18, 24, 30, 33 2-1/2 2-1/2 1/2 P2 18, 24, 30 3/4 3/4 1/2 32 CLCH-IM-16A Table 27 Shipping Coil Water and Steam Connection Sizes Coil Type Header Height Supply Return Drain/Vent P4 18, 24, 30 1 1 1/2 P8 18, 24, 30 1-1/4 1-1/4 1/2 WC 18 1 1 1/2 WC 24 1-1/4 1-1/4 1/2 WC 30, 33 2-1/2 1-1/2 1/2 NS 18 2 1 1 NS 24 2-1/2 1-1/4 1-1/4 NS 30, 33 3 1-1/4 1-1/4 Table 28 UF Refrigerant Coil Connections (Inches) Unit Size Header Height Rows Dist. Tube No. Circuits Circuiting 3 21 4, 6, 8 1/4 16 Full 3/16 16 1/4 8 3/16 8 1/4 4 4, 6 4 6 23 4, 6, 8 4, 6 4 8,10 27 4, 6, 8 4, 6 4 12 32 4, 6, 8 4, 6 4 14 35 4, 6, 8 4, 6 17 37 4, 6, 8 4, 6 Installation and Maintenance 3/16 4 1/4 18 3/16 18 1/4 9 3/16 9 1/4 4 3/16 4 1/4 21 3/16 21 1/4 10 3/16 10 1/4 5 3/16 5 1/4 25 3/16 25 1/4 12 3/16 12 1/4 6 3/16 6 1/4 27 3/16 27 1/4 13 3/16 13 1/4 29 3/16 29 1/4 14 3/16 14 1 Distributor Liquid Half Qtr. 1-1/8 Suction 1-5/8 Qtr. Qtr. Qtr. 1-1/8 1-5/8 7/8 1-3/8 1-5/8 5/8 1-3/8 7/8 1-3/8 5/8 1-3/8 5/8 1-3/8 1-1/8 1-5/8 1-1/8 1-5/8 1-5/8 7/8 1-3/8 1-1/8 1-5/8 Note 1 1-3/8 7/8 1-3/8 7/8 1-3/8 5/8 1-3/8 1-1/8 5/8 1-3/8 Note 2 1-5/8 1 1/8 1-5/8 1-5/8 7/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 7/8 1-3/8 7/8 1-3/8 7/8 1-3/8 1-1/8 5/8 1-3/8 1-3/8 1-5/8 1-1/8 1-5/8 1-3/8 1-5/8 1-1/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 7/8 1-3/8 Full Half 1-5/8 1-3/8 Full Half Suction 1-1/8 7/8 Full Half Liquid 1-1/8 Full Half 2 Distributors 5/8 1-3/8 1-3/8 1-5/8 1 1/8 1-5/8 1-3/8 1-5/8 1 1/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 Full Half 1-1/8 1-3/8 7/8 1-3/8 4 Distributors Liquid Suction 1-1/8 Note 3 Note 4 Note 3 33 Table 28 UF Refrigerant Coil Connections (Inches) Unit Size Header Height Rows 21 45 4, 6, 8 4, 6 25,30 51 4, 6, 8 4, 6 Dist. Tube No. Circuits Circuiting Full 1/4 35 3/16 35 1/4 17 3/16 17 1/4 40 3/16 40 1/4 20 3/16 20 1 Distributor Liquid 2 Distributors Suction Liquid Half Suction Suction 1-1/8 1-5/8 1-1/8 1-5/8 1-1/8 1-5/8 7/8 1-3/8 1-1/8 1-5/8 Note 5 1-3/8 Full Half 4 Distributors Liquid 1-1/8 1-5/8 1 1/8 1-5/8 1-1/8 1-5/8 7/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 Notes: 3. 3-1 3/8 and 1-1 5/8 Number of connections - Size (Inches) 4. 3-7/8 and 1-1 1/8 1. 1- 5/8, 1- 7/8 5. 3-5/8 and 1-7/8 2. 1-1 1/8 and 1-1 3/8 Table 29 UF Refrigerant Coil Connections (Inches) Unit Size Header Height Rows Dist. Tube No. Circuits Circuiting 35,40 57 4, 6, 8 1/4 45 Full 3/16 45 1/4 22 3/16 22 1/4 50 4, 6 50 2-32 4, 6, 8 4, 6 4 66 2-37 4, 6, 8 4 80 2-45 4, 6, 8 4 100 2-51 4, 6, 8 4, 6 3/16 50 1/4 24 3/16 24 1/4 12 3/16 12 1/4 58 3/16 58 1/4 29 3/16 29 1/4 70 3/16 70 1/4 35 3/16 35 1/4 80 3/16 80 1/4 40 3/16 40 Notes: 2 Distributors Liquid Half Suction 1-3/8 1-5/8 1-1/8 1-5/8 Full Half Qtr. 4 Distributors Liquid Suction 1-3/8 1-5/8 1-1/8 1-5/8 Note 1 1-3/8 7/8 1-3/8 1-3/8 1-5/8 1-1/8 1-5/8 1-3/8 1-5/8 1-1/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 1-1/8 1-3/8 7/8 1-3/8 1-1/8 1-3/8 5/8 1-3/8 Full Half 1-1/8 1-3/8 7/8 1-3/8 Full Half Liquid Suction 1-1/8 Note 2 Note 3 Note 2 1-1/8 1-5/8 1-1/8 1-5/8 1-1/8 1-5/8 7/8 1-3/8 1-1/8 1-5/8 Note 4 1-3/8 1-1/8 1-5/8 Full Half 8 Distributors 1-1/8 1-5/8 1-1/8 1-5/8 7/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 4. 6-5/8 and 2-7/8 Number of connections - Size (Inches): 1. 2-7/8, 2-1-1/8 2. 6-1 3/8 and 2-1-5/8 3. 6-7/8 and 2-1-1/8 34 CLCH-IM-16A Figure 28 Coil Type UW 2-Row RH and LH Small Coil Section Connections with Drain and Vent Locations R NPT (EXT) Supply R.H. R NPT (EXT) Return L.H. R NPT (EXT) Return R.H. R NPT (EXT) Supply L.H. 3/8” NPT Ext Vent D Left Hand Right Hand AIR FLOW AIR FLOW F 3/8” NPT Ext Drain B A Base Line C G L Note: External connections fit through casing side . Table 30 2-Row UW Coil Dimensions Unit Size L A B C D F G R 3 11 10-9/16 13-11/16 4-1/2 6-1/2 21-5/8 2-5/8 1-1/2 6 11 12-1/16 14-3/16 4-1/2 6-1/2 24-5/8 2-5/8 1-1/2 8 11 13-15/16 17-1/16 4-1/2 6-1/2 26-3/8 2-5/8 1-1/2 10 11 13-15/16 17-1/16 4-1/2 6-1/2 26-3/8 2-5/8 1-1/2 12 11 16-7/16 19-9/16 4-1/4 6-3/4 33-3/8 2-5/8 2 14 11 13-15/16 20-13/16 4-1/4 6-3/4 25-7/8 2-5/8 2 17 11 18-15/16 22-1/16 4-1/4 6-3/4 38-3/8 2-5/8 2 21 11 20-5/8 25-3/4 3-3/4 7 42-1/8 2-5/8 2-1/2 25 11 25-3/4 26-7/8 3-3/4 7 45-1/4 2-5/8 2-1/2 30 11 25-3/4 26-7/8 3-3/4 7 45-1/4 2-5/8 2-1/2 35 11-1/2 29-7/16 30-9/16 4-3/8 7-1/8 58-3/4 3-5/32 2-1/2 40 11-1/2 29-7/16 30-9/16 4-3/8 7-1/8 58-3/4 3-5/32 2-1/2 Installation and Maintenance 35 Figure 29 Coil Type UW 2-Row RH and LH Medium Coil Section Connections with Drain and Vent Location R NPT (EXT) Supply R.H. R NPT (EXT) Return L.H. 3/8” NPT Ext Vent R NPT (EXT) Return R.H. R NPT (EXT) Supply L.H. D 3/8” NPT Ext Drain AIR FLOW AIR FLOW Right Hand Left Hand M K J F G B A E C 1’7” Table 31 2-Row UW Coil Dimensions Unit Size A B C D E F G J K M R 50 18-7/ 19-3 5-1/2 7-25/32 5-1/8 35-1/2 39-1/8 52-7/8 55-3/4 69-1/2 2 66 27-3/4 30-7/8 5-1/2 7-25/32 11-1/2 47-1/8 50-1/2 66-3/4 69-7/8 96-1/8 2 80 31-1/2 34-5/8 5-1/2 8-1/16 11-1/2 54-5/8 58 78 81-1/8 101-1/8 2-1/2 100 34-5/8 37-3/4 5-1/2 8-1/16 11-1/2 60-7/8 64-1/4 87-3/8 90-1/2 113-5/8 2-1/2 36 CLCH-IM-16A Figure 30 Coil Type UU 4 and 8-Row and UW 4, 6, and 8-Row, RH and LH Medium Coil Connections with Drain and Vent Locations (Unit Sizes 3 - 40). R NPT (EXT) Supply R.H. R NPT (EXT) Return L.H. R NPT (EXT) Return R.H. R NPT (EXT) Supply L.H. 3/8” NPT Ext Vent D Left Hand Right Hand AIR FLOW AIR FLOW F 3/8” NPT Ext Drain B A Base Line C E L Table 32 2-Row UW Coil Dimensions Unit Size L A B C D F G R 3 11 10-9/16 13-11/16 4-1/2 6-1/2 21-5/8 2-5/8 1-1/2 6 11 12-1/16 14-3/16 4-1/2 6-1/2 24-5/8 2-5/8 1-1/2 8 11 13-15/16 17-1/16 4-1/2 6-1/2 26-3/8 2-5/8 1-1/2 10 11 13-15/16 17-1/16 4-1/2 6-1/2 26-3/8 2-5/8 1-1/2 12 11 16-7/16 19-9/16 4-1/4 6-3/4 33-3/8 2-5/8 2 14 11 13-15/16 20-13/16 4-1/4 6-3/4 25-7/8 2-5/8 2 17 11 18-15/16 22-1/16 4-1/4 6-3/4 38-3/8 2-5/8 2 21 11 20-5/8 25-3/4 3-3/4 7 42-1/8 2-5/8 2-1/2 25 11 25-3/4 26-7/8 3-3/4 7 45-1/4 2-5/8 2-1/2 30 11 25-3/4 26-7/8 3-3/4 7 45-1/4 2-5/8 2-1/2 35 11-1/2 29-7/16 30-9/16 4-3/8 7-1/8 58-3/4 3-5/32 2-1/2 40 11-1/2 29-7/16 30-9/16 4-3/8 7-1/8 58-3/4 3-5/32 2-1/2 Installation and Maintenance 37 Table 33 UW 4, 6, and 8-Row, RH and LH Medium Coil Dimensions in inches UW Coil Section D Unit Size L A B C 4 ROW 6 ROW 8 ROW R 3 15-1/2 10-9/16 13-11/16 3-15/16 7-3/16 9-5/16 11-9/16 1-1/2 6 15-1/2 12-1/6 15-3/16 3-15/16 7-3/16 9-5/16 11-9/16 1-1/2 8 15-1/2 13-15/16 17-1/16 3-15/16 7-3/16 9-5/16 11-9/16 1-1/2 10 15-1/2 13-15/16 17-1/16 3-15/16 7-3/16 9-5/16 11-9/16 1-1/2 12 15-1/2 16-7/16 19-9/16 3-15/16 7-3/16 9-5/16 11-9/16 2 14 15-1/2 17-11/16 20-13/16 3-15/16 7-3/16 9-5/16 11-9/16 2 17 15-1/2 18-15/16 22-1/6 3-15/16 7-3/16 9-5/16 11-9/16 2 21 15-1/2 22-5/8 25-3/4 3-15/16 7-3/16 9-5/16 11-9/16 2-1/2 25 15-1/2 25-3/4 28-7/8 3-15/16 7-3/16 9-5/16 11-9/16 2-1/2 30 15-1/2 25-3/4 28-7/8 3-15/16 7-3/16 9-5/16 11-9/16 2-1/2 35 16 32-9/16 29-7/16 4-3/16 7-7/16 9-5/8 11-13/16 2-1/2 40 16 32-9/16 29-7/16 4-3/16 7-7/16 9-5/8 11-13/16 2-1/2 Table 34 UU 4 and 8-Row RH and LH Medium Coil Connection Dimensions in inches UU Coil Section D Unit Size C 4 ROW 8 ROW R E F 3 N/A N/A N/A N/A 2-5/8 21-5/8 6 N/A N/A N/A N/A 2-5/8 24-5/8 8 N/A N/A N/A N/A 2-5/8 28-3/8 10 N/A N/A N/A N/A 2-5/8 28-3/8 12 4-1/2 6-5/8 11 2-1/2 2-5/8 31-3/8 14 4-1/2 6-5/8 11 2-1/2 2-5/8 35-7/8 17 4-1/2 6-5/8 11 2-1/2 2-5/8 38-3/8 21 4-1/2 6-5/8 11 2-1/2 2-5/8 42-1/4 25 4-1/2 6-5/8 11 2-1/2 2-5/8 45-1/4 30 4-1/2 6-5/8 11 2-1/2 2-5/8 45-1/4 35 4-3/4 6-15/16 11-1/4 2-1/2 3-3/16 58-13/16 40 4-3/4 6-15/16 11-1/4 2-1/2 3-3/16 58-13/16 38 CLCH-IM-16A Figure 31 Coil Type UU 4 and 8-Row & UW 4, 6, and 8-Row RH and LH Medium Coil Section Connections (Unit Sizes 50 - 100) with Drain and Vent Location R NPT (EXT) Supply R.H. R NPT (EXT) Return L.H. 3/8” NPT Ext Vent R NPT (EXT) Return R.H. R NPT (EXT) Supply L.H. D 3/8” NPT Ext Drain AIR FLOW AIR FLOW Right Hand Left Hand M K J F G B A E C 1’7” . Table 35 Coil Type UU 4 and 8-Row & UW 4, 6, and 8-Row RH and LH Medium Coil Section Connections Dimensions in inches Unit Size A B E F G J K M R 50 18-3/4 21-7/8 60 35-5/8 39 52-3/4 55-7/8 69-5/8 2 66 27-3/4 30-7/8 11-1/2 47-1/8 50-1/2 66-3/4 69-7/8 74-1/8 2 80 31-1/2 34-5/8 11-1/2 54-5/8 58 42 81-1/8 101-1/8 2-1/2 100 34-11/16 37-3/4 11-1/2 60-11/16 64-1/4 87-3/8 90-7/16 113-5/8 2-1/2 Table 36 Coil Type UU 4 and 8-Row & UW 4, 6, and 8-Row RH and LH Medium Coil Drain and Vent Location Dimensions in inches UW COIL SECTION UU COIL SECTION D D Unit Size C 4 ROW 6 ROW 8 ROW C 4 ROW 8 ROW 50 5-1/8 8-3/8 10-1/2 12-11/16 5-5/8 7-13/16 12-1/8 66 5-1/8 8-3/8 10-1/2 12-11/16 5-5/8 7-13/16 12-1/8 80 5-1/ (130.2) 8-3/8 10-1/2 12-11/16 5-5/8 7-13/16 12-1/8 100 5-1/8 8-3/8 10-1/2 12-11/16 5-5/8 7-13/16 12-1/8 Installation and Maintenance 39 Figure 32 Coil Type WC-24” Headers with Drain and Vent Locations 1-1/4” NPT (INT) Return AIR FLOW 1-1/4” NPT (INT) Supply 25-1/2” 10-1/2” Sq Hd Pipe Plug 1/2” NPT Drain 24-1/8” 12” 2” 4” Figure 33 Coil Type P2, 18, 24” Headers with Drain and Vent Locations 2, 4 Row 6 Row 1/2” NPT Vent 1/2” NPT Vent 6” Water Outlet AIR FLOW A Water Outlet Water Inlet 6” Water Inlet 1/2” NPT Drain Table 37 Coil Type P2, 18, 24” Headers Dimensions (in) 40 Header A 18 16.5 24 22.5 CLCH-IM-16A Figure 34 Coil Type P4, 18, 24” Headers with Drain and Vent Location 2 Row 1/2” NPT Vent 4 Row 1/2” NPT Vent 1.68” 3” Water Outlet Water Outlet AIR B B FLOW Water Inlet A A Water Inlet 0.18” 1/2” NPT Drain Table 38 Coil Type P4, 18, 24” Headers Dimensions (2-Row) in inches 3” Table 39 Coil Type P4, 18, 24” Headers Dimensions (4-Row) in inches Header A B Header A B 18 10.5 6 18 7.5 9 24 13.5 9 24 10.5 12 Figure 35 Coil Type P4, 18, 24” Headers with Drain and Vent Location (6 and 8 Row) 6 Row 8 Row Water Outlet 1/2” NPT Vent 1/2” NPT Vent AIR FLOW A A 1/2” NPT Drain Water Inlet Water Inlet 7-1/2” 1/2” NPT Drain 3” 4-1/2” Water Outlet Table 40 Coil Type P4, 18, 24” Headers with Drain and Vent Location (8 Row) Dimensions in inches Header A 18 16.5 24 22.5 Installation and Maintenance 41 Figure 36 Coil Type P8, 18, 24” Headers with Drain and Vent Locations 4 Row 8 Row 1/2” NPT Vent 1/2” NPT Vent AIR D B FLOW A A Water Inlet Water Outlet Water Inlet C 1/2” NPT Drain 3” Water Outlet Table 41 Coil Type P8, 18, 24” Headers (4-Row) Dimensions in inches Table 42 Coil Type P8, 18, 24” Headers (8-Row) Dimensions in inches Header A B C D Header A 18 7.5 9 1.2 1.2 18 16.5 24 10.5 12 0 4.5 24 22.5 30 13.5 15 1.2 1.2 30 28.5 Figure 37 Coil Type W with 18, 24, 30 and 33” Headers and with Drain and Vent Locations 2-1-2” NPT (INT) Return 1/2” NPT (INT) Vent G D 2-1-2” NPT (INT) Supply G 1/2” NPT (INT) Vent AIR B FLOW D B C A E C A E AIR FLOW 1/2” NPT (INT) Drain 2-1-2” NPT (INT) Supply 1/2” NPT (INT) Drain 2-1-2” NPT (INT) Return H H F Left Hand Coil 42 F Right Hand Coil CLCH-IM-16A Table 43 Coil Type W with 18, 24, 30 and 33” Headers and with Drain and Vent Locations Dimensions in inches 2-Row 4-Row 6-Row 8-Row Coil Size A B C D E H F H F H F H F 18 6-3/4 9-3/4 19-1/2 8-1/4 11-1/4 6-1/2 4 9-1/2 7 12-1/2 10 15-1/2 13 24 9-3/4 12-3/4 25-1/2 11-1/4 14-1/4 6-1/2 4 9-1/2 7 12-1/2 10 15-1/2 13 30 12-3/4 15-3/4 31-1/2 14-1/4 17-1/4 6-1/2 4 9-1/2 7 12-1/2 10 15-1/2 13 33 14-1/4 17-1/4 34-1/2 15-3/4 18-3/4 6-1/2 4 9-1/2 7 12-1/2 10 15-1/2 13 Note: Coil Connections available right or left hand (determined by facing into air flow) Table 44 Coil Type W Coil Connections (Left and Right Hand) in inches Header Steam Coil Piping Figure 38 Typical Piping for Type NS Steam Coils and Horizontal Tubes for Horizontal Airflow G 3 3 4 4.5 6 7.5 8 10.5 NOTE: THE PIPING PENETRATION INTO THE UNIT CASING MUST BE SEALED BEFORE INSULATING. FAILURE TO SEAL THE PENETRATION WILL PERMIT INFILTRATION OF UNCONDITIONED AIR INTO THE SECTION. When subjected to freezing temperatures, provisions must be made to protect coils that are not in use. See section titled “Coil Winterization.” NOTE: IF GLYCOL IS USED IN THE CHILLED WATER OR HOT WATER SYSTEMS, BE SURE TO USE A GLYCOL APPROVED FOR USE WITH COMMERCIAL COOLING SYSTEMS AND COPPER TUBE COILS. FOLLOW THE MANUFACTURER’S RECOMMENDATIONS FOR WATER TREATMENT AND MIX. FAILURE TO DO SO COULD AFFECT COIL PERFORMANCE OR DAMAGE THE TUBES OR BRAZE JOINTS. Coils should be installed with field fitted drains and vents to permit winterization of coils not in use, and to assist in evacuating air from the chilled water system during start-up. CAUTION Failure to properly protect coils not in use during freezing temperatures may result in coil freeze-up damage. Refer to the section titled “Coil Winterization” for specific instructions. Installation and Maintenance Code of System Components (Piping Diagrams FT Float and thermostatic steam trap BT Bucket steam trap GV Gate valve OV Automatic two-position (on-off) control valve TV Automatic three-way control valve VB Vacuum breaker CV Check valve ST Strainer AV Automatic or manual air vent 43 T-Series Climate Changers fitted with steam coils have labeled holes for piping penetrations. Check that the coil is installed correctly and that the unit installation agrees with the submittals. Refer to Figure 38 for typical steam coil piping. CAUTION Condensate must flow freely from the coil to prevent coil damage from water hammer, unequal thermal stresses, freeze-up damage and corrosion. Complete the following recommendations to prevent damage: 1 Install a 1/2” 15 swing-check vacuum breaker in the unused condensate return connection at the top of the coil. This vacuum breaker should be installed as close to the coil as possible. 2 Vent the vacuum breaker to the atmosphere or pipe it to the return main at the discharge side of the steam trap. NOTE: VACUUM BREAKER RELIEF IS MANDATORY WHEN THE COIL IS CONTROLLED BY A MODULATING STEAM SUPPLY OR TWO-POSITION (ON-OFF) AUTOMATIC STEAM SUPPLY VALVE. VACUUM BREAKER RELIEF IS ALSO RECOMMENDED WHEN FACE AND BYPASS CONTROL IS USED. CAUTION The 1/2” 15 swing-check vacuum breaker is recommended because of the low cracking pressure of 3to 5-inches of water. Some other vacuum breakers, such as spring loaded ball-check vacuum breakers, have cracking pressures as high as 17-inches of water. Substitution of the 1/2” 15 swing-check vacuum breaker could result in damage to the coil by preventing proper evacuation of condensate from the coil. The coil condensate return line must be piped full size of the condensate trap connection, except for a short nipple screwed directly into the coil headers condensate return tapping. Do not bush or reduce the coil return tapping size. 44 Proper steam trap selection and installation is necessary for satisfactory coil performance and service life. For installation, use the following steps: 1 Install the steam trap discharge 12 inches below the condensate return connection. 12 inches provides sufficient hydrostatic head pressure to overcome trap losses and ensures complete condensate removal. * Use float and thermostatic traps with atmospheric pressure gravity condensate return, with automatic controls or where the possibility of low pressure supply steam exists. Float and thermostatic traps are recommended because of gravity drain and continuous discharge operation. * Use bucket traps ONLY when the supply steam is not modulated and 25 psig or higher. 2 Trap each coil separately to prevent holding up condensate in one or more of the coils. 3 Install strainers as close as possible to the inlet side of the trap. 4 If installing coils in series airflow, control each coil bank independently with a automatic steam control valve. Size the traps for each coil using the capacity of the first coil in direction of airflow. 5 Use a V-Port modulating valve to obtain gradual modulation of the coil steam supply. 6 Do not modulate systems with overhead or pressurized returns unless the condensate is drained by gravity into a receiver, vented to atmosphere and returned to the condensate pump. 7 Slowly turn the steam on full for at least 10 minutes before opening the fresh air intake on units with fresh air dampers. 8 Pitch all supply and return steam piping down 1inch per 10 feet in the direction of the steam or condensate flow. 9 Do not drain the steam mains or take-offs through the coils. Drain the mains ahead of the coils through a steam trap to the return line. 10 Assure continuous condensate removal. Overhead returns require 1 psig of pressure at the steam trap discharge for each 2-foot elevation. CLCH-IM-16A Hot Water Coil Piping Figure 39 Typical Piping for Type WC Water Coil Figure 40 Typical Piping for Type W Two-Row Water Coil Refer to Figure 39 through Figure 42 for typical hot water coil piping. Code of System Components (Piping Diagrams FT Float and thermostatic steam trap BT Bucket steam trap GV Gate valve OV Automatic two-position (on-off) control valve TV Automatic three-way control valve VB Vacuum breaker CV Check valve ST Strainer AV Automatic or manual air vent Installation and Maintenance q Check the coil for fin damage and straighten if necessary. q Check that the coil is installed correctly with the air flow in the same direction as indicated on the nameplate or coil casing. 45 Figure 41 Typical Piping for Type DD Water Coil 3 Install a drain line and shutoff valve in the supply line near the coil. Type W, D, K, UW and UU water coils are selfventing only if the water velocity exceeds 1.2 fps. Type DD coils are self venting only if the water velocity exceeds 2.5 fps. If water velocity is below these minimums vent by following one of the followings methods: q Install an air vent in the top pipe plug tapping of the return header q Vent from the top return header horizontally to the return piping when the return line rises and is above the top of the coil. Refrigerant Coil Piping Figure 42 Typical Piping for Type W Water Coil Units that are UL listed shall not have refrigerant temperatures and pressures exceeding that listed on the coil nameplate. For unit-installed refrigerant coils, packed elbows are provided. Pipe connections can be made as shown in Figure 43 . Figure 43 Type F Refrigerant Coil with Packed Elbow Panel Type W, WC, UA, UW, and UU hot water coils are self-venting only if the water velocity exceeds 1.5 feet per second (fps). If it is below 1.5 fps, vent by one of the following methods: Perforated Plate (Packed Elbow) Cut Here For Piping Distributor Coil 1 Install an air vent in the top pipe plug tapping of the return header. 2 Vent from the top return header horizontally to the return piping when the return line rises and is above the top of the coil. (See Figure 41 through Figure 42 .) CAUTION Do not throttle or modulate the water flow for coils that are exposed to freezing temperatures. Coil damage may result from coil freeze-up. 46 NOTE: TYPE UF COILS ARE FITTED WITH 5/8” TUBE AND CAP ASSEMBLY TO SEAL VACUUM AND NITROGEN CHARGE. DO NOT USE CAP AND TUBE TO MAKE REFRIGERATION CONNECTIONS. NOTE: TYPE F AND UF COILS HAVE BEEN DEHYDRATED AND CHARGED WITH A HOLDING CHARGE OF DRY NITROGEN. TO PREVENT LEAKS AND SYSTEM CONTAMINATION, DO NOT BREAK THE SEALS UNTIL THE COIL IS INSTALLED. 1 Check that the coil is installed correctly with airflow in the same direction as indicated on the CLCH-IM-16A coil nameplate or casing. The suction connection must be at the bottom of the suction header. 2 Follow accepted refrigeration piping practices and safely precautions for typical refrigerant coil piping and components. See Figure 43 . Specific recommendations are provided with the highside components, including instructions for pressuretesting, evacuation, and system charging. General recommendations for component selection and line sizing follow. 3 Leak-test the entire refrigeration system after all piping is complete. 4 Charge the unit according to approximate weight requirements, operating pressures and superheat/subcooling measurements. 5 Adjust the thermal expansion valve setting if necessary. General Refrigerant Piping Recommendations IMPORTANT: REFER TO THE NOTE ON THE INSIDE FRONT COVER OF THIS MANUAL REGARDING HANDLING OF REFRIGERANTS Liquid Line Components Trane recommends the use of a properly sized liquid line filter-drier installed upstream from the expansion valve and as close to the evaporator coil as possible. Base filter-drier selection on a maximum pressure drop of 2 psi at the design condition. 1 Install moisture indicator/sight glass between the expansion valve and filter-drier. The moisture indicator/sight glass must be sized to match the size of the liquid line at the thermal expansion valve. 2 Size liquid line shutoff valve with an access port using the selected liquid line OD, and install it close to the condenser. 3 Minimize use of other valves, tube bends and reducers since these items tend to increase pressure drop and to reduce subcooling at the expansion valve. Liquid line receivers, other than those factory-installed, are not recommended. 4 The Thermal Expansion Valve (TEV) must be selected for proper size and capacity. The size of the TEV should cover the full range of loadings. Check that the valve will successfully operate at the lightest load condition. Also consider the use of a hot gas bypass valve when sizing the TEV. Select expansion valves with external equalizer connections, and those designed to operate against a back pressure of 20 pounds per square inch higher than actual evaporator pressure. 5 Install the TEV directly on the coil liquid connection (distributor) provided. The liquid distributor must be in a true vertical position. CAUTION Disassemble the thermal expansion valve before completing the brazing connections. If necessary, wrap the valve in a cool, wet cloth while brazing. Failure to protect the valve from high temperatures may result in damage to the internal components. Installation and Maintenance 47 Suction Line Components Install suction line pressure tap on the leaving side of the evaporator coil near the TEV sensing bulb location. Accurate superheat measurement and thermal expansion valve adjustment demands that suction pressure be measured near the evaporator coil. Usually, suction line filter-driers are only necessary on systems that have experienced a severe compressor motor burnout or other failure which results in extremely high refrigerant temperature. Do not leave this filter-drier in the suction line permanently. Liquid Line Sizing All compressors have a Refrigerant Charge Limit (RCL) that must not be exceeded. Since the RCL and pressure drop are in direct conflict with each other, Trane recommends that the liquid line be sized as small as possible, while maintaining a low enough pressure drop to ensure 5°F of subcooling at the expansion valve. Suction Line Sizing Suction line tubes must be sized to maintain refrigerant vapor velocities that are high enough to ensure oil entertainment under all operating conditions. It is not necessary to pitch horizontal suction lines toward the compressor when the refrigerant coil is used with Trane condensing units that are designed with a gas trap in the suction line just prior to the compressor. 48 CLCH-IM-16A 23 . See unit control drawings for specific connection information. Wiring WARNING Disconnect electrical power source before servicing the unit or connecting electrical wires. Failure to do so may result in personal injury or death from electrical shock or entanglement in moving parts. If the unit includes a factorymounted starter, use of the lockout/ tagout on the disconnect is required while servicing the unit. For typical field wiring to units with DDC: q Provide 120 VAC power for control. A dedicated circuit is recommended. Units with a factorymounted starter or VFD do not require this circuit as they are powered by the oversized control transformer in the starter or VFD. q If unit ships in multiple sections, fasten quick connects (Figure 23 ) before sections bolt together. q Field mount and wire outside air sensor and space sensor, if ordered. If the unit does not include a factory-mounted starter, wiring to the unit fan motor must be provided by the installer and must comply with all national and local electrical codes. The installer must also furnish a fused disconnect switch in compliance with national and local electrical codes. Fan motors require overload protective devices rated or selected in compliance with the National Electric Code or Canadian Electric Code. Specific unit and motor connection diagrams are attached to the unit. CAUTION Use copper conductors only for terminal connections. Use of aluminum or other type of wiring may result in galvanic corrosion or overheating and resultant equipment damage. Fan motors require motor overload protective devices that are rated or selected in compliance with the National Electric Code or Canadian Electric Code. Specific unit and motor connection diagrams are provided on the unit. If wiring directly to the motor, a flexible connection at the motor to permit fan belt adjustment should be provided. Fractional horsepower motors may be factory connected to a terminal box on the unit. If this construction is provided, the installer should complete field wiring to this connection box. For a typical high voltage wiring schematic, see Figure 44 following. Connection of junction sections to unit end devices is accomplished using the connections shown in Figure Installation and Maintenance 49 Figure 44 Typical High Voltage Wiring Schematic 50 CLCH-IM-16A ,QVWDOODWLRQ&KHFNOLVW 14 Leave the unit installation and maintenance manual with the unit. Prestart-Up Checks The following is an abbreviated list of the detailed installation information given in this manual and should be used as an aid to ensure proper installation. For complete instructions, refer to the appropriate sections of the manual. Before operating the unit, complete the following checks for safe and efficient operation. WARNING Disconnect electrical power source when connecting or disconnecting electrical wires for test procedures. Do not open service access doors while the unit is operating. Failure to exercise caution when completing test procedures or while inspecting unit operation may result in injury or death from electrical shock, air movement or rotating parts. WARNING Disconnect electrical power source when servicing the unit. Failure to do so may result in injury or death from electrical shock. Secure drive sheaves before servicing the unit to ensure that rotor cannot free-wheel. Failure to secure drive sheaves can cause severe personal injury. 1 Examine the unit and components for material shortage or shipping damage. 2 Check unit location for unit dimensions, weights and clearances. 3 Rig each section properly and hoist it to its final position. 4 For split ship units with factory mounted controls, connect color coded and numbered quick connect plugs (reference Figure 44 ). 5 Check that unit is installed level. 6 Remove fan isolator tie-down bolt, if unit is not externally isolated. See Figure 18 and Figure 19 . q Rotate all fan wheels manually. Fans should turn freely in the proper direction. q Check fan drive belt tension. NOTE: IF T-SERIES CLIMATE CHANGER FAN IS GOING TO OPERATE AT OTHER THAN DESIGN RPM OR WITH A VARIABLE SPEED DRIVE NOT SUPPLIED BY TRANE, THE UNIT VIBRATION LEVELS SHOULD BE CHECKED AT THE NEW RPM AND THROUGHOUT THE SPEED RANGE. RE-BALANCE OR CORRECT VIBRATIONS AS NECESSARY. q Check fan hub set screws, sheave set screws and bearing set screws for proper torque (Table 45 ). Fan sheaves should be tight and aligned. Bearing set screws should be aligned. See section titled “Periodic Maintenance” for alignment instructions. 7 Inspect Inlet Guide Vanes and adjust if necessary. 8 Install damper operator motors and connecting linkage. Check damper operation and linkage alignment. Table 45 Fan Bearing Setscrew Torque Settings (lb-ft) Screw Size Hex Size Torque 9 Install filters, if supplied. 1/4 1/8 5.5-7.5 10 Connect supply and return air ductwork. 5/16 5/32 10.5-13.7 3/8 3/16 19-25 7/16 7/32 29-37.5 1/2 1/4 42-54.2 11 Complete coil and condensate drain piping connections. 12 Reference CLCH-IOP-1 for more details on the installation of units with factory mounted controls. 13 Complete electrical connections to the unit and PCM. Installation and Maintenance q Inspect fan motor and bearings for proper lubrication. Refer to Table 49 for fan grease recommendations. Contact the motor 51 representative for motor lubrication recommendations. q Inspect electrical connections. They should be clean and secure. Compare actual wiring with specific diagrams on the unit. q Check piping and valve for leaks. Open or close the valves to check operation. Drain lines should be open. q If unit has a refrigerant coil, it must be charged, leak-tested, and ready for operation according to instructions provided with the condenser equipment. Adjust superheat setting. q Check that air filters are in place and positioned properly. q Remove all foreign material from the drain pan and check pan opening and condensate line for obstructions. q Check unit for debris. q Close and secure all unit access doors. 52 CLCH-IM-16A 7 Check unit for debris. 6WDUW8S 8 Reference CLCH-IOP-1 for more details on the start-up of units with factory mounted controls. Start-Up Procedures CAUTION Inadequate lubrication of fan motor or bearings may result in premature bearing or motor failure. 1 Inspect electrical connections. They should be clean and secure. Compare actual wiring with specific diagrams provided on the unit. 2 Check piping and valves for leaks. Open or close the valves to check for proper operation. Drain lines should be open. CAUTION The use of untreated or improperly treated water in unit coils may cause scaling, erosion, corrosion, algae, slime or other equipment damage. Consult a qualified water treatment specialist to determine if water treatment is required. The Trane Company assumes no responsibility for equipment damage caused by untreated or improperly treated water. 3 If equipped with a refrigerant coil, charge and leak-test the unit to and ready it for operation according to instructions provided with the condenser equipment. Adjust superheat setting. 4 Check that all air filters are in place and positioned properly. Under Periodic Maintenance, see section titled “Air Filters.” NOTE: UL-LISTED UNITS REQUIRE A “TOOL-ONLY” REMOVABLE LATCH ON ACCESS DOORS. THE HANDLE TIE-DOWN SCREW SHIPPED WITH THE UNIT MEETS THIS REQUIREMENT, AND SHOULD REMAIN IN PLACE WHEN THE ACCESS DOOR IS CLOSED. 5 Close and secure all unit access doors. Check that the latch set screws are tight. 6 Remove all foreign material from the drain pan and check drain pan opening and condensate line for obstructions. Installation and Maintenance After completing all prestart-up checks and procedures, the unit may be started. The following checks and adjustments should be made during initial start-up: WARNING Disconnect electrical power prior to access into a fan or ductwork. Even when locked out electrically, fans may cause injury or damage if the impeller is subject to “windmilling.” The impeller should be secured to physically restrict rotational movement. Failure to secure impeller can cause severe personal injury or death. Disconnect electrical power source when connecting or disconnecting electrical wires for test procedures. Do not open service access doors while the unit is operating. Failure to exercise caution when completing test procedures or while inspecting unit operation may result in injury or death from electrical shock, air movement or rotating parts. If the unit was stored for an extended period of time, the following items should be checked before starting the unit. 1 Inspect motor bearings for moisture and rust. Replace bearings if necessary and repack with new grease. 2 Check motor winding. An acceptable winding resistance reading is from 6 meg-ohms to infinity. If reading is less than 5 meg-ohms, winding should be dried out in an oven or by a blower. 3 Inspect the entire motor for rust and corrosion. 4 Lubricate the motor as instructed in the section titled “Periodic Maintenance,” or as indicated by the maintenance tag on the motor. 53 5 Bump-start unit and observe the fan wheel for proper rotation, as indicated by rotation arrow located on fan housing. 6 Measure the motor voltage and amperage on all phases to ensure proper operation. The readings should fall within the range given on the motor nameplate. Maximum allowable voltage imbalance is two percent. Voltage imbalance is defined as 100 times the sum of the deviation of the three voltages from the average, divided by twice the average voltage. For example, if the three measured voltages are 221, 230 and 227, the average voltage would be 226 volts. sheaves and tighten the sheave set screws to the proper torque given in Table 47 . Figure 45 Proper Drive Alignment Center Lines Must Coincide D Fixed Sheave Fixed Sheave C Straight Edge Straight Edge The percent of voltage imbalance is then calculated: 100 X {[226-221] + [230-226] + [227-226]} 2 X 226 Lines Must Be Parallel B = 2.2% (Unacceptable) A In this example, 2.2 percent imbalance is not acceptable and the power company should be notified to correct it. q Check unit vibration if the fan speed is changed more than 5% from the original designed rpm, or if parts such as shafts, fan wheels, bearings, or other drive components are replaced. Do not exceed max. fan rpm. q Pay particular attention to any vibration, noise or overheating of the motor and fan bearings. (Bearings may run warm during break in.) Excessive Vibration EXCESSIVE VIBRATION MUST BE CORRECTED TO PREVENT BEARING AND SHAFT DAMAGE. SEE THE SECTION TITLED “TROUBLESHOOTING” FOR DETAILS ON THE COMMON CAUSES FOR VIBRATION. Adjustable Sheave WARNING Disconnect electrical power prior to access into a fan or ductwork. Even when locked out electrically, fans may cause injury or damage if the impeller is subject to “windmilling.” The impeller should be secured to physically restrict rotational movement. Failure to secure impeller can cause severe personal injury or death. Determine Fan RPM Fan Belt Alignment Fan rpm can be determined by using a strobe-type tachometer, or revolution counter. Tighten the belts slightly and rotate the drive several times. Sheave Alignment On multiple belt drives, determine that the force of deflection is approximately the same on each belt by pushing each belt in an equal distance at a point halfway from each sheave. If this force is not the same for each belt, the motor and fan shaft are not parallel. Realign as required. Align the fan and motor sheaves by using a straightedge. The straightedge must be long enough to span the distance between the outside edges of the sheaves. When the sheaves are aligned, the straightedge will touch both sheaves at points A through D to confirm that the shaft is parallel. For uneven width sheaves, place a string in the center groove of both sheaves and pull tight. Adjust 54 After realignment, tighten the belts again to the standard belt tensioning specifications. See the following section. CLCH-IM-16A Over-tensioning of belts can cause damage to bearings, shafts, and drive components. Belts should not squeal at start-up. Belt tension should be rechecked after 8 hours, 24 hours, and 100 hours of operation and monthly thereafter. When the belt is in operation, the tight side of the belt should form a straight line from sheave with only a slight bow on the slack side. Figure 47 Fan Sheave Pitch Diameter Fan Belt Tension NOTE: FAN BELT TENSION SHOULD BE CHECKED AT LEAST THREE TIMES DURING THE FIRST DAYS OF OPERATION, SINCE THERE IS A RAPID DECREASE IN TENSION UNTIL BELTS SETTLE IN. REFER TO THE DRIVE STICKER FOR PROPER TENSION. Figure 46 Typical Drive Belt Label Table 46 Values for K-Factor (Belt Cross Section Types) Belt Type A B C D E 3L 4L K Factor 8 13 40 80 95 6 6 Belt Type 5L 3V 5V 8V AX BX CX DX K Factor 6 6 12 25 11 18 54 101 WARNING Disconnect electrical power source and allow all rotating equipment to stop completely before inspecting or servicing the unit. Failure to do so may result in personal injury or death from electrical shock or moving parts. Figure 48 Belt Tension Measurement Disconnect electrical power prior to access into a fan or ductwork. Even when locked out electrically, fans may cause injury or damage if the impeller is subject to “windmilling.” The impeller should be secured to physically restrict rotational movement. Failure to secure impeller can cause severe personal injury or death. Installation and Maintenance 55 Figure 49 Belt Tensioner Proper belt tension is required to ensure maximum bearing and drive component life and is based on fan brake horsepower requirement. Use Table 47 to find the proper belt tension and refer to the inset for an example. To use the table, you must know: q Fan design brake horsepower (bhp) per belt (not motor hp) q Fan rpm q Fan sheave pitch diameter, found by measuring where the middle of the belt rides in the sheave (See Figure 47 ) q Type of belt cross-section (stamped on the belt) 56 CLCH-IM-16A Table 47 Belt Tension Installation and Maintenance 57 As shown in the example of Table 47 , the correct tension (pounds force) is 9.6 pounds, at 1/2-inch deflection. Deflection is determined by dividing the belt span distance by 64, as shown in Figure 48 . To measure belt tension, use a belt tensiometer as shown in Figure 49 . Determine actual deflection by depressing one belt with the belt tensiometer and measuring the deflection relative to the other belts or to belt line. Adjust the belt tension to the correct pounds force and tighten all set screws to the proper torque. (See Table 47 .) For belt cross-section types not given in Table 47 , use the following equations to calculate correct belt tension. NOTE: THERE IS A LABEL LOCATED ON THE BEARING SUPPORT ON THE DRIVE SIDE OF THE UNIT THAT LISTS ALL DRIVE PARTS AND THE PROPER BELT TENSION FOR THE SPECIFIC DRIVE. CAUTION Do not over-tension the belts. Excessive tension will reduce fan and motor bearing life, accelerate belt wear and possibly cause shaft failure. F = (T + K)/16 where F = force measured in pounds at specific deflection. K = constant determined by belt cross-section type. T =24,750 (fan hp per belt)/ belt speed Belt speed = ((fan pitch diameter)/12) X 3.1416 X fan rpm For example, given the following: Motor sheave pitch diameter: 5.7 inches, eight groove Fan sheave pitch diameter: 10.0 inches, eight groove Fan horsepower: 2.4 bhp Fan rpm: 1000 rpm Belt type: C Sheave span: 32 inches Belt speed = (10/12) X 3.14 X 1000 = 2618 T = (24,750 X (24 bhp/2 belts)/2618 = 113.4 lb F = (13.4 + 40)/16 = 9.6 lb. Also, D =(Belt span (inches))/64 = 32/64 =.50 in. Therefore, the belt tensiometer should read 11.5 pounds force at 15/16-inch deflection. This will yield 159.4 pounds force belt tension. Belt tensions determined by using Table 46 are minimum values. The correct operating tension for a V-belt drive is the lowest tension at which the belts will not slip under the peak load conditions. It may be necessary, however, to increase the tension of some drives to reduce excessive belt flopping or to reduce excessive start-up squealing. 58 CLCH-IM-16A 3HULRGLF0DLQWHQDQFH operating conditions include high speeds, moist or dirty air, or high temperatures. q Check and adjust fan belt tension. The following checklist is provided as an abbreviated guide to periodic maintenance. Detailed procedural information is given after this checklist. WARNING Every Three to Six Months q Check fan bearing grease line connections. Lines should be tight to the bearings. q Relubricate fan bearings. Disconnect electrical power and allow rotating parts to stop before servicing the unit. Exercise caution if unit must be on for test or maintenance procedures. Failure to do so may result in injury or death from electrical shock or moving parts. q Check motor lubrication. Recommendations are provided on the motor tag or on a unit sticker. Disconnect electrical power prior to access into a fan or ductwork. Even when locked out electrically, fans may cause injury or damage if the impeller is subject to “windmilling.” The impeller should be secured to physically restrict rotational movement. Failure to secure impeller can cause severe personal injury or death. q Inspect coils for dirt build-up or coil freeze-up. After 48 Hours Operation Belts have acquired their permanent stretch. Readjust but do not over-tighten. See section titled “Fan Belt Tension” for instructions. q Check bearing and motor bracket bolt torque. q Align fan and motor sheaves. Tighten sheave set screws to the proper torque. q Check and adjust fan belt tension. q Tighten electrical connections. Every Year q Inspection the unit casing for corrosion. If damage is found, clean and repaint the surface with a rustresistant primer and vinyl chlorinated lacquer. q Clean the fan wheels and fan shaft. Remove rust with an emery cloth and apply a coat of LPS #3 or an equivalent. q Inspect the condensate drain pan and drain line, remove sludge or foreign materials that might obstruct proper drainage. Remove obstacles. Table 48 Minimum Hex Head Bolt Torque in lb-ft Grade 5 Bolts Weekly Observe unit weekly for any change in running condition and unusual noise. Size (inches*) 1/4, 20 Thread Designation Min. Torque UNC 6 Every Month 1/4, 28 UNF 7 q Check air filters. Clean or replace if clogged or dirty. Coat permanent filters with oil after cleaning. Change bag filters when pressure drop is 1-inch W.G. 5/16, 18 UNC 14 5/16, 24 UNF 16 3/8, 16 UNC 24 3/8, 24 UNF 28 7/16, 14 UNC 42 7/16, 20 UNF 45 1/2, 13 UNC 69 1/2, 20 UNF 83 9/16, 12 UNC 99 q Relubricate fan bearings if operating conditions include high speeds, moist or dirty air, or high temperatures. q Relubricate motor bearings in accordance with motor manufacturer’s recommendations if Installation and Maintenance 59 10 Use a scraper or other tools to remove any solid matter. Remove solid matter with a vacuum device that uses high efficiency particulate arrestance (HEPA) filters with a minimum efficiency of 99.97% at 0.3 micron particle size. Table 48 Minimum Hex Head Bolt Torque in lb-ft Grade 5 Bolts Thread Designation Min. Torque 9/16, 18 UNF 118 5/8, 11 UNC 150 5/8, 18 UNF 176 3/4, 10 UNC 254 3/4, 16 UNF 301 7/8, 9 UNC 358 7/8, 14 UNF 422 1, 8 UNC 500 1, 14 UNF 602 Size (inches*) 11 Thoroughly clean the contaminated area with a mild bleach and water solution or an EPAapproved sanitizer specifically designed for HVAC use. Carefully follow the sanitizer manufacturer’s instructions regarding the use of the product. 12 Immediately rinse the drain pan thoroughly with fresh water to prevent potential corrosion from the cleaning solution of the drain pan and drain line components. 13 Allow the unit to dry thoroughly before putting the system back into service. *NOTE: Soft metric conversions not acceptable for screw and hex sizes 14 Determine and correct the cause of the microbial contamination. q Check damper linkages, set screws and blade adjustment. Clean, but do not lubricate, the nylon damper rod bushings. 15 Be careful that the contaminated material does not contact other areas of the unit or building. Properly dispose of all contaminated materials and cleaning solution. q Clean damper operators. q Inspect the control and power box wiring for secure connections and insulation. q Rotate the fan wheel and check for obstructions in the fan housing. The wheel should not rub on the fan housing. Adjust the center if necessary and tighten wheel set screws to the proper torque. q Check condition of gasketing and insulation around unit, door and dampers. q Examine flex connections for cracks or leaks. Repair or replace damaged material. Drain Pans Inspecting and Cleaning Drain Pans For units with sloped drain pans, if evidence of standing water or condensate overflow exists, identify and remedy the cause immediately. (Refer to the troubleshooting section for possible causes and solutions.) If microbial growth (mold) in the drain pan is observed, clean the pan immediately using the following procedure: 7 Disconnect all electrical power to the unit. 8 Don the appropriate personal protective equipment (PPE). 9 Remove all standing water. 60 IMPORTANT: STANDING WATER IN DRAIN PANS CAN PROMOTE MICROBIAL GROWTH (MOLD) THAT MAY CAUSE UNPLEASANT ODORS AND SERIOUS HEALTH-RELATED INDOOR AIR QUALITY PROBLEMS. IF MOLD IS FOUND, IT MUST BE REMOVED IMMEDIATELY AND THAT PORTION OF THE UNIT PROPERLY CLEANED AND SANITIZED. Air Filters Catalog data tables provide filter size, type and quantity. Throwaway Filters To replace throwaway filters, install new filters with the directional arrows pointing in direction of airflow. NOTE: FILTERS MUST HAVE AN AIRTIGHT SEAL TO PREVENT AIR BYPASS. IF USING OTHER THAN TRANE-SUPPLIED FILTERS, APPLY FOAM GASKETING TO THE VERTICAL EDGES OF THE FILTER. Permanent Filters To clean permanent filters, wash under a stream of water to remove dirt and lint. Remove oil filter with a wash of mild alkali solution. Rinse in clean, hot water and allow to dry. Coat both sides of the filter by immersing or spraying it with Air Maze Filter Lote W or an equivalent. Allow to drain and dry for about 12 hours. CLCH-IM-16A Cartridge or Bag Filters To install cartridge or bag filters, complete the following: WARNING Disconnect electrical power source, and allow all rotating equipment to stop before inspecting or servicing the unit. Failure to do so may result in personal injury or death from electrical shock or rotating parts. 1 Open the filter section access door and remove the filters and block-offs from their installed position. 2 Keeping the bag filters folded, slide each filter into the filter rack, pushing them tightly against the unit. Pleats should be in the vertical position. 3 If using the optional pre-filters, slide them into the appropriate filter rack. 4 If fixed and adjustable block-offs are provided with the unit, slide the fixed block-offs into the filter track before the adjustable block-off. The adjustable block-off should always be installed last, next to the access door. 5 Close and secure the access door. If the door can be closed without compressing the filter, adjust the block-off by loosening its screws and position it to provide an airtight seal. industrial cleaning solution. Carefully follow the cleaning solution manufacturers instructions regarding use of their product. 5 If microbial growth (mold) is present, remove the contamination (Step 2) and thoroughly clean the affected area with an EPA-approved sanitizer specifically designed for HVAC use. Carefully follow the sanitizer manufacturers instructions regarding the use of the product. 6 Rinse the affected surfaces thoroughly with fresh water and a fresh sponge to prevent potential corrosion of metal surfaces. 7 Allow the unit to dry completely before putting it back into service. 8 Use caution to assure that any contaminated material does not contact other areas of the unit or building. Properly dispose of all contaminated materials and cleaning solution. IMPORTANT: IF MICROBIAL GROWTH (MOLD) WAS FOUND, THE CAUSE OF THE CONTAMINATION MUST BE DETERMINED AND ACTION TAKEN TO ASSURE IT DOES NOT RECUR. Fan Bearings and Motors Bearing Set screw Alignment Align bearing set screws as illustrated in Figure 50 . Reference Table 45 for bearing set screw torque. Fans Inspecting and Cleaning Fans Fan sections of air handlers should be inspected every six months at a minimum or more frequently if operating experience dictates. Accumulated dirt and organic matter on the interior surfaces of fans should be cleaned immediately. The suggested procedure for cleaning these surfaces is: 1 Disconnect all electrical power to the unit. 2 Don the appropriate personal protective equipment (PPE). 3 Use a portable vacuum with HEPA filtration to remove the loose dirt and organic matter. The filter should be 99.97% efficient at 0.3 micron particle size. 4 If no microbial growth (mold) exists, thoroughly clean the fan and associated components with an Installation and Maintenance 61 Figure 50 Bearing Setscrew Alignment Set Screws (2) Set Screws (2) recommended lubricants and bearing grease capacities. Fan Bearing Lubrication Table 49 Recommendations for Grease-Lubricated Fan Bearings Greasing Intervals -20°F to +140°F 140°F to 200°F Clean, Dry 3-6 months 1-3 months Dirty, Dry 1-3 months 1-4 weeks Dirty, Wet, High Humid. 1-4 weeks 1-14 days Operating Conditions Recommended Greases Recommended Operating Range Texaco-Multi Fak #2 -20°F to +250°F Shell Alvania #2 -20°F to +250°F Mobil Mobilux #2 -20°F to +250°F Exxon Unirex #2 -20°F to +250°F Texaco Prem. RB -20°F to +250°F Mobil 532 -20°F to +250°F Exxon Beacon -65°F to +250° Keystone 84H -40°F to +225°F Shaft Size (In) Max. Grease Cap. of Bearing (Oz.) 1/2 to 3/4 1/8 7/8 to 1-3/16 3/8 1-1/4 to 1-1/2 5/8 1-11/16 to 1-15/16 7/8 2 to 2-7/16 2-1/2 to 2-15/16 1-1/4 2 Note: Greases used should conform to NLGI No. 2 penetration. Fan bearings should be lubricated with a lithium base grease which conforms to NLGI Number 2 for consistency. See Table 49 and Table 50 for 62 CAUTION Improper lubrication can result in premature bearing failure. Do not mix greases with different bases within the bearing. This can cause an audible squealing noise that may be transmitted through the system ductwork. Premature bearing failure may result. To lubricate the fan bearings, complete the following: WARNING Disconnect electrical power source before servicing the unit. If unit must be on for maintenance procedures, exercise extreme caution. Failure to do so may result in personal injury or death from electrical shock or entanglement in moving parts. Disconnect electrical power prior to access into a fan or ductwork. Even when locked out electrically, fans may cause injury or damage if the impeller is subject to “windmilling.” The impeller should be CLCH-IM-16A secured to physically restrict rotational movement. Failure to secure impeller can cause severe personal injury or death. WARNING Disconnect power source for motor lubrication. Failure to do so may result in injury or death. 1 Disconnect main power switch. 2 Check grease lines for tight connections at the grease fitting. 3 Using a manual low pressure grease gun, add grease until a light bead of grease appears at the bearing grease seal. Turn the fan wheel manually while adding grease. Fan Motors Inspect fan motors periodically for excessive vibration or temperature. Operating conditions will vary the frequency of inspection and lubrication. Table 51 lists recommended motor greasing intervals. Motor lubrication instructions are found on the motor tag or nameplate. For a list of compatible greases, see Table 49 . Table 50 Fan Bearing Maximum Grease Capacity Shaft Size in inches Capacity in fl. oz. 1/2 - 3/4 1/7 7/8 - 1-3/16 3/8 1-1/4 - 1-1/2 5/8 1-11/16 - 1-15/16 7/8 2 - 2-7/16 1-1/4 2-1/2 - 2-15/16 2 Avg. Environment .3 to 7.5 HP Motors 10 to 30 HP Motors Clean and Dry Every 5 years Every 3 years 12-24 Moderate Dirt or Moisture Every 2 years Every year Any Severe (very dirty or high temperatures) Every 6 months Every 3 months 8-16 To relubricate the motor, consult the maintenance tag provided by the vendor. Refer to Table 48 for minimum torque of motor mounting and bearings bolts. Installation and Maintenance Coil Cleaning The frequency of required cleaning is dependent on the operating hours of the system, filter maintenance and efficiency and dirt load. IMPORTANT: COILS BECOME EXTERNALLY FOULED AS A RESULT OF NORMAL OPERATION. DIRT ON THE SURFACE OF THE COIL REDUCES IT’S ABILITY TO TRANSFER HEAT THAT CAN RESULT IN COMFORT PROBLEMS, INCREASED RESISTANCE TO AIR FLOW AND THUS INCREASED OPERATING ENERGY COSTS. IF THE DIRT ON THE SURFACE OF THE COIL BECOMES WET, SUCH AS COMMONLY OCCURS WITH COOLING COILS, MICROBIAL GROWTH (MOLD) CAN RESULT THAT MAY CAUSE UNPLEASANT ODORS AND SERIOUS HEALTH-RELATED INDOOR AIR QUALITY PROBLEMS. Steam, hot water and chilled water coils Table 51 Recommended Motor Greasing Schedule Avg. Daily Operating Hours Disconnect electrical power prior to access into a fan or ductwork. Even when locked out electrically, fans may cause injury or damage if the impeller is subject to “windmilling.” The impeller should be secured to physically restrict rotational movement. Failure to secure impeller can cause severe personal injury or death. Steam, hot water and chilled water coils should be kept clean to maintain maximum performance. If fins become dirty, clean with steam and detergent, hot water spray and detergent, or one of the commercially available chemical coil cleaners. Rinse coils thoroughly after cleaning. WARNING Follow all directions provided with chemical cleaners to avoid personal injury and/or coil damage. Commercially available chemical cleaners may contain caustic or hazardous agents. 63 1 Disconnect all electrical power to the unit. 2 Don the appropriate personal protective equipment (PPE). 3 Gain access to the coil section of the unit (both sides). 4 Use a soft brush to remove loose debris from both sides of the coil. 5 Use a steam cleaning machine, starting from the top of the coil and working downward. Clean the leaving air side of the coil first, then the entering air side. Use a block-off to prevent steam from blowing through the coil and into a dry section of the unit. 6 Repeat step 5 as necessary. 7 Confirm that the drain line is open following the cleaning. 8 Allow the unit to dry thoroughly before putting the system back in service. 9 Straighten any coil fins that may have been damaged during the cleaning process with a fin rake. 10 Replace all panels and parts and restore electrical power to the unit. CAUTION Follow directions provided with the cleaner to avoid coil damage. WARNING Never use steam or hot water to clean a refrigerant coil. Dangerous pressures may be built up by the improper application of heat resulting in equipment damage or personal injury. 1 Follow steps 1-4 from Steam and Water Coil Cleaning procedure preceding. 2 Mix a high quality coil cleaning detergent with water according to the manufacturers instructions. If the detergent is strongly alkaline after mixing (PH 8.5 or higher), it must contain an inhibitor. Carefully follow the detergent manufacturers instructions on the use of the product. 3 Place the mixed solution in a garden pump-up sprayer or high pressure sprayer. If a high pressure sprayer is used, note the following: 11 Use caution to assure that any contaminated material does not contact other areas of the unit or building. Properly dispose of all contaminated materials and cleaning solution. q Maintain a minimum nozzle spray angle of 15 degrees. Type K cooling coils q Protect other areas of the air handler and internal controls from contact with moisture or the cleaning solution. Type K cooling coils have removable headers for cleaning. A small nylon or fiber brush may be used to clean the tubes. After cleaning, flush with water. When removing any header, replace the rubber sealing gasket and be sure that it seats properly when header is installed. If necessary, pull out turbulators, clean the tubes and replace turbulators. When header covers are replaced, apply washers under the bolt heads. Bolts should be evenly tightened to 50 pound-feet of torque. Refrigerant coils Refrigerant coils should be kept clean to maintain maximum performance. If fins become dirty, clean with cold water and detergent, or one of the commercially available chemical coil cleaners. Rinse coils thoroughly after cleaning. q Spray perpendicular to the coil face. q Keep the nozzle at least 6 inches from the coil. q Do not exceed 600 psi. 4 Spray the leaving air side of the coil first, then the entering air side. Use a block-off to prevent spray from going through the coil and into a dry section of the unit and/or system ductwork. Carefully follow the cleaning solution manufactures usage instructions. 5 Thoroughly rinse both sides of the coil and the drain pan with cool, clean water. 6 Repeat steps 4 and 5 as necessary. 7 Straighten any coil fins that may have been damaged during the cleaning process with a fin rake. 8 Confirm that the drain line remains open following the cleaning process. 64 CLCH-IM-16A 9 Replace all panels and parts and restore electrical power to the unit. tightened beginning in the center and working toward the outside. 10 Allow the unit to dry thoroughly before putting the system back into service. 11 Use caution to assure that any contaminated material does not contact other areas of the unit or building. Properly dispose of all contaminated materials and cleaning solution. Coil Winterization Provisions must be made to drain coils that are not in use when subjected to freezing temperatures. Coil type NS may be adequately drained in its pitched position within the unit and the installer must provide appropriate piping for adequate drainage. Coil types UU, D, DD, (provided with drain and vent) K, W, WC, and P can be adequately drained as installed in their level position. CAUTION Failure to properly drain and vent coils when not in use during freezing temperatures may result in coil freeze-up damage. CAUTION Use caution in removing header plugs from P2, P4 and P8 coils. Over torquing may result in twisted tubes. Type UW Coil - (Leveled/pitched— not fully drainable) Remove the vent and drain plugs and blow the coils out as completely as possible with compressed air. The coils should then be filled and drained several times with full strength inhibited ethylene glycol, so that it will mix thoroughly with the water retained in the coil. Drain the coil out as completely as possible. Type K Coils To winterize Type K coils, remove the header covers. If tubes are fouled, clean with nylon or fiber brush. To ensure that no water will remain in the coil, do not replace the header covers until the coils are put back into service. When the coils are put back into service, new gaskets must be used. When header covers are replaced, apply washers under the bolt heads and tighten bolts evenly to 50 pound-feet. Bolts should be Installation and Maintenance 65 before inspecting or servicing the unit. Failure to do so may result in personal injury or death from electrical shock or moving parts. 7URXEOHVKRRWLQJ Use the table in this section to assist in identifying the cause or causes of a malfunction in T-Series Climate Changer operation. The column header “RECOMMENDED ACTION” suggests repair procedures. NOTE: THIS TABLE IS INTENDED AS A DIAGNOSTIC AID ONLY. FOR DETAILED REPAIR PROCEDURES, CONTACT YOUR LOCAL TRANE SERVICE COMPANY. WARNING Disconnect electrical power source and allow all rotating equipment to stop completely Disconnect electrical power prior to access into a fan or ductwork. Even when locked out electrically, fans may cause injury or damage if the impeller is subject to “windmilling.” The impeller should be secured to physically restrict rotational movement. Failure to secure impeller can cause severe personal injury or death. Table 52 T-Series Climate Changer Trouble Analysis SYMPTOM Bearing is excessively hot Motor fails to start Motor stalls Excessive vibration 66 PROBABLE CAUSE RECOMMENDED ACTION First start after relubrication (Grease distribution) Allow machine to cool down and restart. Over-lubrication Clean surface of grease and purge. Over tensioned belts Adjust belt tension. No lubricant Apply lubricant. Check bearings for damage. Misaligned bearing Correct alignment. Check shaft level. Blown fuse or open circuit breaker Replace fuse or reset circuit breaker. Overload trip Check and reset overload. Improper wiring or connections Check wiring with diagram supplied on unit. Improper current supply Compare actual supply power with motor nameplate recommendations. Contact power company for adjustments. Mechanical failure Check that motor and drive rotate freely. Check bearing lubricant. Open phase Check line for an open phase. Overloaded motor Reduce load or replace with larger motor. Low line voltage Check voltage across AC line. Correct voltage if possible. Poor alignment Align bearing set screws (Figure 50 ). Loosen and retighten bearing set screws. Shipping spacers not removed Remove shipping spacers and/or bolts. See Figure 18 and Figure 19 . Over tensioned belts Adjust belt tension. Misaligned drive Align drive. CLCH-IM-16A Table 52 T-Series Climate Changer Trouble Analysis SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION Motor runs and then dies down Partial loss of line voltage Stator shorts when motor warms up Replace stator. Motor does not come up to speed Low voltage at motor terminals Check voltage across AC line and correct voltage loss if possible. Line wiring to motor too small Replace with larger sized wiring. Overloaded motor Reduce load or replace with a larger motor. Motor fan is clogged with dirt preventing proper ventilation Remove fan cover, clean fan and replace cover. Motor overheats Excessive motor noise Rapid motor bearing wear Loose fan belt Shorter belt life Bearing noise Low coil capacity (Chilled water) Low coil capacity (Refrigerant) Installation and Maintenance Check for loose connections. Determine adequacy of main power supply. Motor mounting bolts loose Tighten motor mounting bolts. Rigid coupling connections Replace with flexible connections. Worn motor bearings Replace bearings and seals. Fan rubbing on fan cover Remove interference in motor fan housing. Excessive overhung load due to overtensioned drive Check belt tension and overhung load. Excessive overhung load due to a small diameter motor sheave Replace sheave with larger one. Motor is poorly positioned Adjust belt tension. Worn or damaged belt Replace belt or belt set. Check sheave alignment. Worn sheaves Replace sheaves. Worn sheaves Replace sheaves. Misaligned belt Realign drive with MVP sheave set at mean pitch diameter. Grease or oil on belts Check for leaky bearings. Clean belts and sheaves. Belt slipping Adjust tension. Belts rubbing Remove obstruction or realign drive for clearance. Poor alignment Loosen bearing set screws and realign (See Figure 50 .) Inadequate lubrication Grease bearing(s). Air is bypassing coil Prevent bypass with block-offs. Coil tubes are blocked Clean and unblock tubes. Incorrect airflow Check fan operating conditions. Incorrect gpm Check water pumps, valves and lines for obstructions. Incorrect water temperature Provide proper water temperature. Air is bypassing coil Prevent bypass with block-offs. Coil tubes are blocked Clean and unblock tubes. Incorrect airflow Check fan operating conditions. Expansion valve not operating Check sensing bulb location and TXV operation. 67 Table 52 T-Series Climate Changer Trouble Analysis SYMPTOM Drain pan is overflowing PROBABLE CAUSE RECOMMENDED ACTION Poor refrigerant distribution Check for blockage in distributor and tubes. Plugged drain line Clean drain line. Unit not level Level unit. Standing water in drain pan Improper trap design Design trap for unit. Excess dirt in unit Missing filters Replace filters. Filter bypass Reduce filter bypass. Standing water in drain pan See “Standing water” symptom. Mold inside air handler 68 CLCH-IM-16A
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Encryption : Standard V1.2 (40-bit) User Access : Print, Copy, Annotate, Fill forms, Extract, Assemble, Print high-res Create Date : 1999:06:11 11:04:47 Producer : Acrobat Distiller 3.02 Author : Paul Hatlem Creator : Windows NT 4.0 Title : T-Series Climate Changer ® Central Station Air Handlers Installation and Maintenance PDF Manual (CLCH-IM-16A) Modify Date : 2000:06:12 09:37:15-05:00 Page Count : 71EXIF Metadata provided by EXIF.tools