TurboChef Technologies Inc.

Tornado and Tornado 2 (NGC) Ventless Submittal Information
1.

Spec Sheets

1.1

2.

UL Ventless Label

2.1

3.

UL Listing

3.1

4.

UL KNLZ Explained

4.1

5.

Test Report

5.1

6.

KNLZ Letter

6.1

7.

Mechanical Code Sections

7.1

8.

Emissions by Product

8.1

9.

Fire and Smoke Statement

9.1

10. Heat Loading Calculations

10.1

11. Sampling of Letters from the Following States/Jurisdictions

11.1

California

11.1

North Carolina Department of Insurance

11.7

Wisconsin

11.9

Minnesota

11.11

Michigan

11.12

City of Saint Louis, MO

11.13

Miami County, OH

11.15

City of Los Angeles

11.17

12. Surface Temperatures

© 2008–2012 TurboChef Technologies, Inc.

12.1

DOC-1122 / Rev F / Nov 2012

Item No. ______________________________________________________
Quantity _______________________________________________________________________

The

Exterior Construction
n
n
n

430 stainless steel front, top, sides and back	
4” (102 mm) adjustable legs
Cool to the touch pull down door with microwave seal

Interior Construction
n
n
n
n

304 stainless steel interior
Fully insulated cook chamber
Removable / variable cooking surfaces
Exposed bottom browning element

Standard Features
n

n

PERFORMANCE

n

n	The

Tornado® evenly and consistently
toasts, browns and crisps food up to 12X
faster than traditional cooking methods,
resulting in a high level of throughput
without compromising quality

n
n
n
n

n

VENTILATION

n
n

n	UL

710B (KNLZ) listed for ventless
	 operation.†

n

n	EPA

202 test (8 hr):
	 - Product: Pepperoni Pizzas
			 - Results: 0.21 mg/m3
		
- Ventless Requirement: <5.00 mg/m3
n	Internal

catalytic filtration to limit smoke,
grease, and odor emissions.

n

Integral recirculating catalytic converter for UL 710B (KNLZ) listed 		
ventless operation
Variable-speed High h recirculating impingement airflow system
Variable cooking surfaces (racks, stones and platters)
Independently-controlled bottom browning element
Smart Voltage Sensor Technology* (U.S. only)
Smart menu system capable of storing up to 128 recipes
Built-in self-diagnostics for monitoring oven components and 	
performance
Stackable design (requires stacking kit)
Manual snooze mode
Includes plug and cord (6 ft. nominal)
Smart card compatible
Warranty – 1 year parts and labor

Comes with standard Accessories
n
n
n
n
n

1 Aluminum Paddle (NGC-1478)
1 Bottle Oven Cleaner (103180)
1 Bottle Oven Guard (103181)
2 Trigger Sprayers (103182)
2 Non-stick Baskets (100011)

2
1

3

5

1. Blower Motor
2. Impingement Heater
3. Impinged Air
4. Bottom Browning Element
5. Microwave Bursts
6. Catalytic Converter

This product conforms to the ventilation recommendations set forth by NFPA96 using
EPA202 test method.

4
6

*	Smart Voltage Sensor Technology does not compensate for lack of or over voltage situations. It is the 		
	 responsibility of the owner to supply voltage to the unit according to the specifications on the back of this sheet.
†
	Ventless certification is for all food items except for foods classified as “fatty raw proteins.” Such foods include
	 bone-in, skin-on chicken, raw hamburger meat, raw bacon, raw sausage, steaks, etc. If cooking these types of
	 foods, consult local HVAC codes and authorities to ensure compliance with ventilation requirements.

	Ultimate ventless allowance is dependent upon AHJ approval, as some jurisdictions may not recognize the 	

1. Blower Motor
	UL certification or application. If you have questions regarding ventless certifications or local codes please
2. Impingement Heater
	 email ventless.help@turbochef.com
3. Impinged Air
4. IR Element
TurboChef reserves the right to make substitutions of components or change specifications without prior notice.
5. Microwave Bursts
6. Catalytic Converter

NGC-1299/Revision M/
October 2012

®

Tornado

®

Tornado

Project _______________________________________________________

26” (660 mm)

25.7” (653 mm)

Tornado

®

19”
(483 mm)

23”
(584 mm)
11.25” (286 mm)

Dimensions
Single Units

Max Circuit Requirement

20 amp

Plug

IEC 309, 5-pin, 32 amp

Height

19”

483 mm

Max Input

10500 watts

on legs

23”

584 mm

Microwave Input Power

3500 watts

Width

26”

660 mm

Depth

25.7”

653 mm

Phase

3 Phase

with handle

28.2”

716 mm

Voltage

230 VAC

190 lbs.

86 kg

Frequency

50 Hz

Weight

NGCED (NGC-1180-1D)

Current

30 amp

38”

965 mm

Max Circuit Requirement

32 amp

Width

26”

660 mm

Plug

IEC 309, 4-pin, 32 amp

Depth

25.7”

653 mm

Max Input

10500 watts

with handle

28.2”

716 mm

Microwave Input Power

3500 watts

380 lbs.

172 kg

Phase

1 Phase

Height

8”

203 mm

Voltage

230 VAC

Width

15.5”

394 mm

Frequency

50 Hz

Depth

14.7”

373 mm

Current

30 amp

Volume

1.05 cu.ft.

29.9 liters

Max Circuit Requirement

32 amp

Wall Clearance	 (Oven not intended for built-in installation)	

Plug

IEC 309, 3-pin, 32 amp

Top

4”

102 mm

Max Input

6700 watts

Sides

2”

51 mm

Microwave Input Power

3500 watts

Stacked Units (Stacking Kit Required)
Height

Weight
Cook Chamber		

NGCUK (NGC-1180-1K)

JAPAN

Electrical Specifications

NGCJD - 50Hz/ 3 Phase (NGC-1180-1D-2005-1)
NGCJD - 60Hz/ 3 Phase (NGC-1180-1D-2005-2)
NGCJK - 50Hz/ 1 Phase (NGC-1180-1K-2005-3)
NGCJK - 60Hz/ 1 Phase (NGC-1180-1K-2005-4)

NORTH AMERICA
NGC (NGC-1180-1)
Phase

1 Phase

Voltage

208/240 VAC

Phase

1 or 3 Phase

Frequency

60 Hz

Voltage

200 VAC

Current

30 amp

Frequency

50 or 60 Hz

Max Circuit Requirement

30 amp

Current

30 amp

3-Phase

1-Phase

Plug/Cord

NEMA 6-30P; 1.5m, H07RN-F

Max Circuit Requirement

30 amp

Max Input

5990/6675 watts

Plug

PSE-marked, 3 or 4-blade, 30 amp

Microwave Input Power

3500 watts

Max Input

10500 or 6700 watts

NGCBK (NGC-1180-1K-2020)

Microwave Input Power

Phase

1 Phase

Voltage

220 VAC

Frequency

60 Hz

Current

30 amp

Max Circuit Requirement

30 amp

Plug

IEC 309, 3-pin, 32 amp

Max Input

6700 watts

Microwave Input Power

3500 watts

U.S.: All ovens shipped within the U.S. are packaged in a double-wall corrugated box banded to a wooden skid.
International: All International ovens shipped via Air or Less than Container Loads are packaged in wooden crates.
Box size: 34” x 30” x 30” (864 mm x 762 mm x 762 mm)
Crate size: 37”x 33” x 34” (940 mm x 838 mm x 864 mm)
Item class: 85 NMFC #26770 HS code 8419.81
Approximate boxed weight: 260 lb. (118 kg)
Approximate crated weight: 320 lb. (145 kg)

EUROPE/ASIA-PACIFIC
NGCEW (NGC-1180-1W for standard)
NGCEW (NGC-1180-1W-2024 for Australia/New Zealand)*
NGCKW (NGC-1180-1W-2004 for South Korea)**
Phase

3 Phase

Voltage

400 VAC

Frequency

50 Hz or 60 Hz**

Current

16 amp

3500 watts

SHIPPING INFORMATION

Minimum entry clearance required for box: 30.5” (775 mm)
Minimum entry clearance required for crate: 33.5” (851 mm)
*All AU-New Zealand ovens with clips allow for 5 pin plug.
Standard

Australia/New Zealand

TurboChef recommends installing a type D circuit breaker for all installations.

TurboChef Global Operations
4240 International Pkwy, Suite 105 / Carrollton, Texas 75007 USA
US: 800.90TURBO (800.908.8726) / International: +1 214.379.6000
Fax: +1 214.379.6073 / turbochef.com

Item No. ______________________________________________________
Quantity ___________________________________________________________________________

TORNADO 2

TM

EXTERIOR CONSTRUCTION
n

n

Stainless steel exterior with powder-coated side panels
4” (102 mm) legs
Cool to the touch pull down door with microwave seal

INTERIOR CONSTRUCTION
n
n
n
n

304 stainless steel interior
Fully insulated cook chamber
Removable / variable cooking surfaces
Exposed bottom browning element

STANDARD FEATURES
n

n

PERFORMANCE
The Tornado 2TM oven evenly and
consistently toasts, browns, and crisps food
up to twelve times faster than traditional
cooking methods, resulting in a high level
of throughput without compromising
quality.

n
n
n
n
n

n
n

VENTILATION
n	 UL 710B (KNLZ) listed for ventless

n
n

	 operation.†
n

n

	 EPA 202 test (8 hr):

	 - Product: Pepperoni Pizzas
		 - Results: 0.21 mg/m 3
		
- Ventless Requirement: <5.00 mg/m3

	 Internal catalytic filtration to limit smoke,

n

grease, and odor emissions.

Integral recirculating catalytic converter for UL 710B (KNLZ) listed
ventless operation
Variable-speed High h recirculating impingement airflow system
Variable cooking surfaces (racks, stones, and platters)
Independently-controlled bottom browning element
Smart Voltage Sensor Technology* (U.S. only)
Smart menu system capable of storing up to 128 recipes
Built-in self-diagnostics for monitoring oven components
and performance
Stackable design (requires stacking kit)
Manual snooze mode
Includes plug and cord (6 ft. nominal)
Smart card compatible
Warranty – 1 year parts and labor

COMES WITH STANDARD ACCESSORIES
n
n
n
n
n

1 Aluminum Paddle (NGC-1478)
1 Bottle Oven Cleaner (103180)
1 Bottle Oven Guard (103181)
2 Trigger Sprayers (103182)
2 Non-stick Baskets (100011)

2

1

3

5

This product conforms to the ventilation recommendations set forth by NFPA96 using
EPA202 test method.

4
6

*	Smart Voltage Sensor Technology does not compensate for lack of or over voltage situations. It is the 		
	 responsibility of the owner to supply voltage to the unit according to the specifications on the back of this sheet.
	Ventless certification is for all food items except for foods classified as “fatty raw proteins.” Such foods include
	 bone-in, skin-on chicken, raw hamburger meat, raw bacon, raw sausage, steaks, etc. If cooking these types of
	 foods, consult local HVAC codes and authorities to ensure compliance with ventilation requirements.
†

1. Blower Motor
2. Impingement Heater
3. Impinged Air
4. Bottom Browning Element
5. Microwave Bursts
6. Catalytic Converter

1. Blower Motor
2. Impingement Heater
3. Impinged Air
4. IR Element
5. Microwave Bursts
6. Catalytic Converter

	 Ultimate ventless allowance is dependent upon AHJ approval, as some jurisdictions may not recognize the 	
	 UL certification or application. If you have questions regarding ventless certifications or local codes please
	 email ventless.help@turbochef.com
TurboChef reserves the right to make substitutions of components or change specifications without prior notice.

DOC-1134/Revision H/
October 2012

TM

n

TORNADO 2

Project _______________________________________________________

TORNADO 2

TM

26” (660 mm)

19”
(483 mm)

25.7” (653 mm)

23”
(584 mm)

11.5”
(292 mm)

DIMENSIONS
Single Units

Plug

IEC 309, 5-pin, 32 amp

Max Input

10,500 watts
3,500 watts

Height

19”

483 mm

Microwave Input Power

on legs

23”

584 mm

NGCED (NGC-1280-1D)

Width

26”

660 mm

Phase

3 Phase

Depth

25.7”

653 mm

Voltage

230 VAC

with handle

28.45”

723 mm

Frequency

50 Hz

Weight

190 lb.

86 kg

Stacked Units (Stacking Kit Required)

Current

30 amps

Max Circuit Requirement

30 amps

Height

38”

965 mm

Plug

IEC 309, 4-pin, 32 amp

Width

26”

660 mm

Max Input

10,500 watts

Depth

25.7”

653 mm

Microwave Input Power

3,500 watts

with handle

28.45”

723 mm

NGCUK (NGC-1280-1K)

Cook Chamber		

Phase

1 Phase

Height

8”

203 mm

Voltage

230 VAC

Width

15.5”

394 mm

Frequency

50 Hz

Depth

14.7”

373 mm

Current

30 amps

Volume

1.05 cu.ft.

29.9 liters

Max Circuit Requirement

32 amps

Wall Clearance	 (Oven not intended for built-in installation)	

Plug

IEC 309, 3-pin, 32 amp

Top

102 mm

Max Input

6,700 watts

51 mm

Microwave Input Power

3,500 watts

4”

Sides

2”

JAPAN

ELECTRICAL SPECIFICATIONS
Phase

1 Phase

Voltage

208/240 VAC

NGCJD - 50Hz/ 3 Phase (NGC-1280-1D-2005-1)
NGCJD - 60Hz/ 3 Phase (NGC-1280-1D-2005-2)
NGCJK - 50Hz/ 1 Phase (NGC-1280-1K-2005-3)
NGCJK - 60Hz/ 1 Phase (NGC-1280-1K-2005-4)

Frequency

60 Hz

Phase

1 or 3 Phase

Current

30 amps

Voltage

200 VAC

Max Circuit Requirement

30 amps

Frequency

50 or 60 Hz

Plug/Cord

NEMA 6-30P; 1.5m, H07RN-F

Current

30 amps

Max Input

5,990 watts (208) / 6,675 watts (240)

Max Circuit Requirement

30 amps

Microwave Input Power

3,500 watts

Plug

PSE-marked, 3 or 4-blade, 30 amp

Max Input

6,700 or 10,500 watts

NORTH AMERICA (NGC-1280-1)

NGCBK (NGC-1280-1K-2020)
Phase

1 Phase

Voltage

220 VAC

Frequency

60 Hz

Current

30 amps

Max Circuit Requirement

30 amps

Plug

IEC 309, 3-pin, 32 amp

Max Input

6,700 watts

Microwave Input Power

3,500 watts

Microwave Input Power

3,500 watts

U.S.: All ovens shipped within the U.S. are packaged in a double-wall
corrugated box banded to a wooden skid.
International: All International ovens shipped via Air or Less than Container
Loads are packaged in wooden crates.
Box size: 34” x 30” x 30” (864 mm x 762 mm x 762 mm)
Crate size: 37”x 33” x 34” (940 mm x 838 mm x 864 mm)
Item class: 85 NMFC #26770 HS code 8419.81
Approximate boxed weight: 260 lb. (118 kg)
Approximate crated weight: 320 lb. (145 kg)

NGCEW (NGC-1280-1W for standard)
NGCEW (NGC-1280-1W-2024 for Australia/New Zealand)*
NGCKW (NGC-1280-1W-2004 for South Korea)**

Minimum entry clearance required for box: 30.5” (775 mm)
Minimum entry clearance required for crate: 33.5” (851 mm)

3 Phase

Voltage

400 VAC

Frequency

50 Hz or 60 Hz**

Current

16 amps

Max Circuit Requirement

20 amps

1-Phase

SHIPPING INFORMATION

EUROPE/ASIA-PACIFIC

Phase

3-Phase

*All AU-New Zealand ovens with clips allow for 5 pin plug.
Standard

Australia/New Zealand

TurboChef recommends installing a type D circuit breaker for all installations.

TurboChef Global Operations
4240 International Pkwy, Suite 105 / Carrollton, Texas 75007 USA
US: 800.90TURBO (800.908.8726) / International: +1 214.379.6000
Fax: +1 214.379.6073 / turbochef.com

© 2009-2010 TurboChef Technologies, Inc.

Page 2.1

KNLZ.E151487 - Commercial Cooking Appliances with Integral Systems for Limiting the Emission of ...

Page 3.1

KNLZ.E151487
Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
Grease-laden Air
Page Bottom

Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
Grease-laden Air
See General Information for Commercial Cooking Appliances with Integral Systems for Limiting the Emission of Grease-laden Air
TURBOCHEF TECHNOLOGIES INC

E151487

SUITE 105
4240 INTERNATIONAL PKY
CARROLLTON, TX 75007 USA
Commercial microwave/convection ovens, Models C3/C, HHB, NGC, i5.
Last Updated on 2008-02-14
Questions?

Notice of Disclaimer

Page Top

Copyright © 2008 Underwriters Laboratories Inc.®
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under
UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always
look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information,
Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings).
2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the
extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2008 Underwriters
Laboratories Inc.®"

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=KNLZ.E151487...

8/26/2008

KNLZ.GuideInfo - Commercial Cooking Appliances with Integral Systems for Limiting the Emission of...

Page 4.1

KNLZ.GuideInfo
Commercial Cooking Appliances with Integral Systems for Limiting the Emission of
Grease-laden Air
View Listings

Page Bottom

[Heaters and Heating Equipment] (Heaters, Cooking Appliances) Commercial
Cooking Appliances with Integral Systems for Limiting the Emission of Grease-laden
Air
See General Information for Heaters, Cooking Appliances
This category covers cooking equipment intended for commercial use, such as pressurized deep fat fryers and other appliances for use in commercial
kitchens, restaurants or other business establishments where food is prepared. Each appliance covered in this category is manufactured with an
integral system feature to limit the emission of grease-laden air from the cooking process to the room ambient.
These appliances have been evaluated for the limit of 5 mg/m 3 for the emission of grease-laden air to the room ambient in accordance with the
recommendations of the National Fire Protection Association Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations,
NFPA 96, using the EPA-202 test method prescribed for cooking appliances provided with integral recirculating air systems.
These products are not intended for connection to a ducted exhaust system.
Appliances in this category are not provided with an integral fire extinguishing system. Authorities having jurisdiction should be consulted as to the
requirements for this equipment with respect to fire extinguishing systems, such as the need for field installed systems in accordance with NFPA 96.
For products with integral recirculating systems including fire extinguishing systems, refer to Commercial, with Integral Recirculating Systems (KNKG).
In cases where the nature or construction of equipment is such that special precautions beyond the requirements of the National Electrical Code must
be observed in installations or use, suitable warning or special instructions are marked on the equipment.
Appliances Listed in this category are suitable for wiring with either copper or aluminum power supply conductors unless marked "Use Copper Wire
Only For Power Supply Connections" .
Commercial cooking appliances of certain types are designed for permanent connections to water supply and sewer lines at the point of installation.
Authorities having jurisdiction should be consulted as to the requirements for this equipment with respect to sanitation and connection to water supply
and waste disposal lines.
Neither the toxicity of coatings nor the physiological effects on persons consuming food products prepared by use of these appliances has been
investigated.
For cooking oil filters that are not an integral part of another appliance, see Commercial Filters for Cooking Oil (KNRF).
For additional information, see Electrical Equipment for Use in Ordinary Locations (AALZ) and Heating, Cooling, Ventilating and Cooking Equipment
(AAHC).
The basic standard used to investigate products in this category is ANSI/UL 197, "Commercial Electric Cooking Appliances".
Appliances Listed in this category with an integral cooking oil filter have been additionally investigated to the requirements in the standard "Commercial
Filters for Cooking Oil", ANSI/UL 1889.
The Listing Mark of Underwriters Laboratories Inc. on the product is the only method provided by UL to identify products manufactured under its Listing
and Follow-Up Service. The Listing Mark for these products includes the name and/or symbol of Underwriters Laboratories Inc. (as illustrated in the
Introduction of this Directory) together with the word "LISTED," a control number and one of the following product names as appropriate: "Commercial
Cooking Appliance," "Cooking Appliance," or other appropriate product identity specified in the individual Listing, along with the words "with integral
system for limiting the emission of grease-laden air. "

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?&name=KNLZ.GuideI...

8/28/2008

KNLZ.GuideInfo - Commercial Cooking Appliances with Integral Systems for Limiting the Emission of...

Page 4.2

Last Updated on 1999-02-19
Questions?

Notice of Disclaimer

Page Top

Copyright © 2008 Underwriters Laboratories Inc.®
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under
UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always
look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information,
Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings).
2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the
extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2008 Underwriters
Laboratories Inc.®"

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?&name=KNLZ.GuideI...

8/28/2008

Page 5.1

Page 5.2

Page 6.1

April 10, 2007
Mr. James Pool
Turbochef Technologies Inc
Suite 105 4240 International Pky
Carrollton, TX 75007
United States

Our Reference:

File

E151487

Subject:

INTEGRAL RECIRCIRCULATING SYSTEM

Dear Mr. Pool:
In reply to your e-mail message received today, I offer the following.
Products in the KNLZ category (as well as KNKG) are evaluated to UL710B. It used to be that UL197
and supplement SB in UL197 was the standard that they were evaluated to. Basically, UL197 and
Supplement SB became UL710B. There is no more Supplement SB in UL197 (9th Ed.).
Any information and documentation involving UL Mark services are provided on behalf of Underwriters
Laboratories Inc. (UL) or any authorized licensee of UL.

Very truly yours,

Fred Zaplatosch
Staff Engineer
3015CNBK
Tel: 847-664-2853
Fax: 847-313-2853
fred.zaplatosch@us.ul.com

Page 7.1
EXHAUST SYSTEMS

EXHAUST SYSTEMS

air from the exhaust outlet discharges away from such
locations.

506.4 Ducts serving Type II hoods. Single or combined Type
II exhaust systems for food-processing operations shall be
independent of all other exhaust systems. Commercial kitchen
exhaust systems serving Type II hoods shall comply with Sections 506.4.1 and 506.4.2.
506.4.1 Type II exhaust outlets. Exhaust outlets for ducts
serving Type II hoods shall comply with Sections 401.4 and
401.4.2. Such outlets shall be protected against local
weather conditions and shall meet the provisions for exterior wall opening protectives in accordance with the International Building Code.
506.4.2 Ducts. Ducts and plenums serving Type II hoods
shall be constructed of rigid metallic materials. Duct construction, installation, bracing and supports shall comply
with Chapter 6. Ducts subject to positive pressure and ducts
conveying moisture-laden or waste-heat-Iaden air shall be
constructed, joined and sealed in an approved manner.
506.5 Exhaust equipment. Exhaust equipment, including
fans and grease reservoirs, shall comply with Sections 506.5.1
through 506.5.5 and shall be of an approved design or shall be
listed for the application.
506.5.1 }:xhaust fans. Exhaust fan housings serving a Type
I hood shall be constructed as required for grease ducts in
accordance with Section 506.3.1.1.
Exception: Fans listed and labeled in accordance with
UI-I762.
506.5.1.1 Fan motor. Exhaust fan motors shall be
located outside of the exhaust airstream.
506.5.2 Exhaust fan discharge. Exhaust fans shall be positioned so that the discharge will not impinge on the roof,
other equipment or appliances or parts of the structure. A
vertical discharge fan shall be manufactured with an
approved drain outlet at the lowest point of the housing to
permit drainage of grease to an approved grease reservoir.
506.5.3 Exhaust fan mounting. An upblast fan shall be
hinged and supplied with a flexible weatherproof electrical
cable to permit inspection and cleaning. The ductwork shall
extend a minimum of 18 inches (457 mm) above the roof
surface.
506.5.4 Clearances. Exhaust equipment serving a Type I
hood shall have a clearance to combustible construction of
not less than 18 inches (457 mm).
Exception: Factory-built exhaust equipment installed in
accordance with Section 304.1 and listed for a l,~sser
clearance.
'
506.5.5 Termination location. The outlet of exhaust equipment serving Type I hoods shall be in accordance with Section 506.3.12.
Exception: The minimum horizontal distance between
vertical discharge fans and parapet-type building structures shall be 2 feet (610 mm) provided that such struc-

I

44

tures are not higher than the top of the fan discharge
opening.
SECTION 507
COMMERCIAL KITCHEN HOODS
507.1 General. Commercial kitchen exhaust hoods shall comply with the requirements of this section. Hoods shall be Type I
or Type II and shall be designed to capture and confine cooking
vapors and residues. Commercial kitchen exhaust hood systems shall operate during the cooking operation.

vapor exhaust systems that are supplied by the
appliance manufacturer and are installed in accordance with the manufacturer's instructions.

I

Exceptions:
1. Factory-built commercial exhaust hoods which are
tested in accordance with UL 710, listed, labeled and
installed in accordance with Section 304.1 shall not
be required to comply with Sections 507.4, 507.7,
507.11,507.12,507.13,507.14 and 507.15.
2. Factory-built commercial cooking recirculating systems which are tested in accordance with UL 710B, I
listed, labeled and installed in accordance with Section 304.1 shall not be required to comply with Sections 507.4,507.5,507.7,507.12,507.13,507.14 and
507.15.
3. Net exhaust volumes for hoods shall be permitted to
be reduced during no-load cooking conditions, where
engineered or listed multispeed or variable-speed
controls automatically operate the exhaust system to
maintain capture and removal of cooking effluents as
required by this section.
507.2 Where required. A Type I or Type II hood shall be
installed at or above all commercial cooking appliances in
accordance with Sections 507.2.1 and 507.2.2. Where any
cooking appliance under a single hood requires a Type I hood, a
Type I hood shall be installed. Where a Type II hood is
required, a Type I or Type II hood shall be installed.
.. 507.2.1 Type I hoods. Type I hoods shall be installed where
cooking appliances produce grease or smoke, such as
occurs with griddles, fryers, broilers, ovens, ranges and wok
ranges.
507.2.1.1 Operation. Type I hood systems shall be
designed and installed to automatically activate the
exhaust fan whenever cooking operations occur. The
activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods.
507.2.2. Type II hoods. Type II hoods shall be installed
where cooking or dishwashing appliances produce heat,
steam, or products of combustion and do not produce grease
or smoke, such as steamers, kettles, pasta cookers and
dishwashing machines.
Exceptions:
1. Under-counter-type commercial dishwashing
machines.
2. A Type II hood is not required for dishwashers and
potwashers that are provided with heat and water

2006 INTERNATIONAL MECHANICAL CODE@

inside the hood shall not be required to be welded or brazed
but shall be otherwise sealed to be grease tight.

Exceptions:
1. Penetrations shall not be required to be welded or
brazed where sealed by devices that are listed for
the application.
2. Internal welding or brazing of seams, joints, and
penetrations of the hood shall not be prohibited
provided that the joint is formed smooth or ground
so as to not trap grease, and is readily cleanable.

.... 3. A single light-duty electric convection, bread,
retherm or microwave oven. The additional heat
and moisture loads generated by such appliances
shall be accounted for in the design of the HVAC
system.
4. A Type II hood is not required for the following
electrically heated appliances: toasters, steam
tables, popcorn poppers, hot dog cookers, coffee
makers, rice cookers, egg cookers, holding/warming ovens. The additional heat and moisture loads
generated by such appliances shall be accounted
for in the design of the HVAC system.

507.2.3 Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for
commercial purposes shall be provided with Type I or Type
II hoods as required for the type of appliances and processes
in accordance with Sections 507.2, 507.2.1 and 507.2.2.
507.2.4 Extra-heavy-duty. Type I hoods for use over
extra-heavy-duty cooking appliances shall not cover other
appliances that require fire extinguishing equipment and
such hoods shall discharge to an exhaust system that is independent of other exhaust systems.
507.3 Fuel-burning appliances. Where vented fuel-burning
appliances are located in the same room or space as the hood,
provisions shall be made to prevent the hood system from interfering with normal operation of the appliance vents.
507.4 Type I materials. Type I hoods shall be constructed of
steel not less than 0.043 inch (1.09 mm) (No. 18 MSG) in thickness, or stainless steel not less than 0.037 inch (0.94 mm) (No.
20 MSG) in thickness.
507.5 Type II hood materials. Type II hoods shall be constructed of steel not less than 0.030 inch (0.76 mm) (No. 22
Gage) in thickness, stainless steel not less than 0.024 inch (0.61
mm) (No. 24 Gage) in thickness, copper sheets weighing not
less than 24 ounces per square foot (7.3 kg/m2 ), or of other
approved material and gage.
507.6 Supports. Type I hoods shall be secured in place by noncombustible supports. All Type I and Type II hood supports
shall be adequate for the applied load of the hood, the unsupported ductwork, the effluent loading, and the possible weight
of personnel working in or on the hood.
507.7 Hood joints, seams and penetrations. Hood joints,
seams and penetrations shall comply with Sections 507.7.1 and
507.7.2.
507.7.1 Type I hoods. External hood joints, seams and penetrations for Type I hoods shall be made with a continuous
external liquid-tight weld or braze to the lowest outermost
perimeter of the hood. Internal hood joints, seams, penetrations, filter support frames, and other appendages attached

2006 INTERNATIONAL MECHANICAL CODE@

507.7.2 Type II hoods. Joints, seams and penetrations for
Type II hoods shall be constructed as set forth in Chapter 6,
shall be sealed on the interior of the hood and shall provide a
smooth surface that is readily cleanable and water tight.
507.8 Cleaning and grease gutters. A hood shall be designed
to provide for thorough cleaning of the entire hood. Grease gutters shall drain to an approved collection receptacle that is fabricated, designed and installed to allow access for cleaning.
507.9 Clearances for Type I hood. A Type I hood shall be
installed with a clearance to combustibles of not less than 18
inches (457 mm).
Exception: Clearance shall not be required from gypsum
wallboard attached to noncombustible structures provided
that a smooth, cleanable, nonabsorbent and noncombustible
material is installed between the h90d and the gypsum wallboard over an area extending not less than 18 inches (457
mm) in all directions from the hood.
507.10 Hoods penetrating a ceiling. Type I hoods or portions
thereof penetrating a ceiling, wall or furred space shall comply
with all the requirements of Section 506.3.10.
507.11 Grease filters. Type I hoods shall be equipped with
listed grease filters designed for the specific purpose.
Grease-collecting equipment shall be provided with access for
cleaning. The lowest edge of a grease filter located above the
cooking surface shall be not less than the height specified in
Table 507.11.
TABLE 507.11
MINIMUM DISTANCE BETWEEN THE LOWEST EDGE OF A
GREASE FILTER AND THE COOKING SURFACE OR THE
HEATING SURFACE
TYPE OF COOKING
APPLIANCES

Without exposed flame
Exposed flame and burners
Exposed charcoal and charbroil type
For SI:

HEIGHT ABOVE COOKING
SURFACE (feet)

0.5
2

3.5

1 foot =304.8 mm.

507.11.1 Criteria. Filters shall be of such size, type and
arrangement as will permit the required quantity of air to
pass through such units at rates not exceeding those for
which the filter or unit was designed or' approved. Filter
units shall be installed in frames or holders so as to be
readily removable without the use of separate tools, unless

45

Page 8.1

UL 710B (KNLZ)
Emissions by Product
275

3

250

2.75
2.5
2.25

200

2
175
1.75
150
1.5
125
1.25
100
1
75

0.75

50

Pizza's Cooked
Emissions

25

0.5
0.25

0

0
C3/C

HHB

i5
TurboChef Model

NGC

PM Emissions [ppm]

Product Cooked per 8 hour period

225

Page 9.1

October 18, 2004
Mr. Mike Denny
Building Services,
224 West Knight St.
City of Sioux Falls,
South Dakota, 57102
Ph: 605-367-8252
Re: Fire and smoke containment
Dear Mr. Denny:
The TurboChef ovens have been extensively tested and conform to UL 923 and UL KNLZ
standards. The UL 923 standard is the electrical/product safety standard and the KNLZ is the low particulate matter
emissions standard to which we conform. While both standards address difference aspects of the oven, they both
have inherent overlap as it relates to grease/smoke/fire handling.
As it relates specifically to fire safety, UL 923 specifies:
Section 57 Cavity Fire Containment Test:
The performance of an appliance subjected to this test shall be considered
acceptable if all of the following conditions are met:
a) There is no emission of fire, flame, or molten metal outside the appliance nor glowing or ignition
of the cheesecloth, tissue paper, or wood surface;
b) The fuse rated 3 A does not open;
c) Following the test, the appliance complies with the requirements of Leakage Current, Section 33,
and Dielectric Voltage-Withstand Test, Section 39, as applicable to primary circuits; and
d) Following the test and following 10 c of operation (opening and closing the door), the
appliance complies with the requirements in 57.12. The radiation emission shall not xceed
5mW/cm2.
Test Method:
Section 57.2 requires that 4 potatoes each weighing between 150g and 200g be placed inside the
oven under test and cooked using full microwave power and hot air (if applicable) until the potatoes
catch fire. Note: The test must be repeated until it catches fire. During this test, pieces of tissue
paper and cheesecloth are placed above, below and around the product to ensure that the fire
and/or excessive heat generated is safely contained within the confines of the appliance.
As it relates to grease handling, UL KNLZ specifies:
UL KNLZ Guide Information Excerpt:
“These appliances have been evaluated for the limit of 5 mg/m3 for the emission of grease-laden
air to the room ambient in accordance with the recommendations of the National Fire Protection
Association Standard for Ventilation Control and Fire Protection of Commercial Cooking
Operations, NFPA 96, using the EPA-202 test method prescribed for cooking appliances provided
with integral recirculating air systems.”

C:\Windows\Temp\Rar$DI00.000\Fire smoke and grease statement v2_11.doc

Page 9.2

Test Method:
The UL KNLZ category requires that products must have less than 5.0 mg/m3 of particulate matter
emissions during 8 continuous hours of cooking a “worst case” food product as measured by EPA
202. Note: Our products were tested using full-fat pepperoni pizzas.
As it pertains specifically to smoke: Smoke typically consists of visible grease particulate that escapes from a product
during operation. Our ovens utilize a recirculating airpath that is catalytic scrubbed, thus the airborne grease is
combusted as it crosses our catalyst. Given this, under typical/normal operating conditions, our product does not emit
smoke.
If you have any issues or specific questions regarding the above, please contact me directly.
Best regards,
James K. Pool III
James K. Pool III
Vice President Engineering,
TurboChef Technologies, Inc.,
Ph: 214.379.6020
Email: james.pool@turbochef.com

C:\Windows\Temp\Rar$DI00.000\Fire smoke and grease statement v2_11.doc

Page 10.1

NGC Energy.xls

NGC Tornado (1 PHASE)
Changeable Parameters
Operating Time
Energy Costs
Snooze Mode
Cook Cycles/Day
Typical Cook Time

12
$0.11
0.00
100

Hours
kWHr
Hours
Cooks/Day

60

Seconds

Time (min)

Power
(Watts)

Cost/Day

Balance of Time (hrs)

15
100
0
605

5277
5000
1100
1400

$0.15
$0.96
$0.00
$1.62

11.75
10.08
10.08
0

$2.72
$81.72

Yearly
$980.62

Do Not Change the following values

Warm up
Cooking
Snooze Idle
Idle
Total/Day
Total/Month

HVAC Requirements Per Operating Time -- Note: Approximations Only

Average Energy Cooking And Idle (J)
80820000

11/6/2008

Warmup Energy (J)
4749300

Total
Total average
Energy (J) Power (W)
85569300
1981

Confidential

Total Environmental
Load kBtu/hr
6.759028

Average
Cooling
Requirement
(ton of AC)
0.563

James K. Pool

Page 11.1

State of California—Health and Human Services Agency

3

Department of Health Services

ARNOLD SCHWARZENEGGER
Governor

SANDRA SHEWRY
Director

July 23, 2004

Ruth Sender
OhCal Foods, Inc.
20501 Ventura Blvd., Suite 375
Woodland Hills, CA 91364
RE:

Exemption from Mechanical Exhaust Ventilation for
TurboChef Model NGC Rapid Cook Oven

Dear Ms. Sender:
Thank you for your application of April 26, 2004, for a review of the TurboChef Model
NGC Rapid Cook Oven for exemption from the mechanical exhaust ventilation
requirements of Section 114140 of the California Uniform Retail Food Facilities Law
(CURFFL). Specifically, you have requested an exemption to allow unventilated NGC
Rapid Cook Ovens to be installed and operated at various Subway locations throughout
California.
You have provided documentation and I have verified that the TurboChef Model NGC
Rapid Cook Oven has been evaluated and listed by UL for conformance with ANSI/NSF
Standard 4.
Under the provisions of CURFFL Section 114140, the Department may exempt heating
and cooking equipment that does not produce toxic gases, grease, smoke, or heat
when properly installed and operated as recommended by the manufacturer. Based on
the information and documentation you have provided, the TurboChef Model NGC
Rapid Cook Oven is granted LIMITED exemption from mechanical exhaust ventilation
under the following conditions:
1. Unless approval is granted by the local enforcement agency, there shall be no
more than one unventilated oven in operation at each Subway location.
2. No other heating or cooking appliances subject to mechanical ventilation
requirements may be operated without mechanical ventilation in the food
facility, unless permission to operate more than one unventilated appliance is
granted by the local enforcement agency.

Food and Drug Branch, MS 7602, P.O. Box 997413, Sacramento, CA 95899-7413
Internet Address: www.dhs.ca.gov/fdb

Page 11.2

Ms. Ruth Sender
July 23, 2004
Page 2

3. The oven shall not be used for cooking meats, poultry, fish, or other foods
that may produce grease laden vapors. Such use will require that mechanical
ventilation be installed over the unit.
4. The oven must be operated and installed in a well-ventilated area approved
for food preparation.
5. The oven must be installed, maintained, operated, and serviced according to
the specifications of the manufacturer and local codes.
6. This exemption shall not be deemed to supersede any local fire or building
code requirements.
This exemption shall be in effect until revoked. However, should any local enforcement
agent find that the operation of the TurboChef Model NGC Rapid Cook Oven without
mechanical ventilation creates a sanitation or safety problem, the local enforcement
agent may require the unit to be used only with mechanical ventilation. These problems
may include, but are not limited to, problems of installation, use, maintenance, cleaning
or other site specific considerations which exceed the above limitations or pose a
discernable health or safety hazard.
This letter may be used as evidence of the evaluation of the TurboChef Model NGC
Rapid Cook Oven. However, it is not to be construed as an endorsement of the subject
item and may not be used for advertising or promotional purposes.
If you have any questions you may call me at (916) 650-6617.
Sincerely,

Susan Strong, REHS
Program Specialist, Retail Food Unit

Cc:

Mike Boian, REHS
Northern California Technical Advisory Committee

Page 11.3

Ms. Ruth Sender
July 23, 2004
Page 3

Virginia Lineberry, REHS
Bay Area Technical Advisory Committee
Donna Fenton, REHS
Central Valley Technical Advisory Committee
Nelson Kerr, REHS
Southern California Technical Advisory Committee
Gary Erbeck, REHS
CCDEH, Food Safety Policy Committee

Page 11.4

State of California—Health and Human Services Agency

Department of Health Services
Food & Drug Branch
DIANA M. BONTÁ, R.N., Dr. P.H.
Director

GRAY DAVIS
Governor

October 25, 2002
Peter J. Ashcraft
TurboChef Technologies, Inc.
10500 Metric Drive, Suite 128
Dallas, Texas 75243
Dear Mr. Ashcraft:
RE: Exemption from External Mechanical Exhaust Ventilation
Thank you for your letter of October 7, 2002 requesting exemption from mechanical
exhaust ventilation requirements specified in Section 114140 of the California Uniform Retail
Food Facilities Law (CURFFL) for the Model C3/C Rapid Cook Oven.
Descriptive materials and cut sheets accompanying your application specify that this
oven is Sanitation Classified by NSF International for compliance with ANSI/NSF Standard 4
for commercial heating and cooking appliances.
Under the provisions of Section 114140, the Department may exempt heating and
cooking equipment that does not produce toxic gases, grease, smoke, or heat when properly
installed and operated as recommended by the manufacturer. Results of tests conducted by the
Pacific Gas & Electric, Food Service Technology Center, indicate that the oven produces no
significant emissions of smoke and grease-laden air while in use. Based on the information you
have provided and the certifications by recognized testing laboratories, the TurboChef
Technologies Model C3/C Rapid Cook Oven is granted LIMITED exemption from mechanical
ventilation requirements under the following conditions:
1. There may be up to two (2) unventilated Model C3/C ovens in Subway sandwich
stores in California.
2. The oven(s) must be installed, maintained, operated, and serviced according to the
specifications of the manufacturer and local codes.
3. Any modification, alteration, or removal of any component of the integral air
filtration system voids this limited exemption.
4. All air filtration components must be installed and operational at all times the
appliance is in use.
5. The oven must be installed in an approved food preparation area with sufficient room
ventilation to maintain acceptable working conditions.
Do your part to help California save energy. To learn more about saving energy, visit the following web site:
www.consumerenergycenter.org/flex/index.html
th

601 N. 7 Street, MS-357, P.O. Box 942732, Sacramento, CA, 94234-7320
(916) 445-2263
Internet Address: www.dhs.ca.gov

Page 11.5

Peter Ashcraft
October 25, 2002

This exemption shall be in effect until revoked. However, should any local enforcement
agent find that the operation of the TurboChef Technologies Model C3/C Rapid Cook Oven
without mechanical ventilation creates a sanitation or safety problem, the local enforcement
agent may require the unit to be used only with external mechanical ventilation. These problems
may include but are not limited to problems of installation, use, maintenance, cleaning or other
site specific considerations which exceed the above limitations or pose a discernable health or
safety problem.
This letter may be used as evidence of the evaluation of the TurboChef Model C3/C
Rapid Cook Oven. However, it is not to be construed as an endorsement of the subject
equipment and may not be used for advertising or promotional purposes.
If you have any questions you may call me at (916) 327-6905.
Sincerely,

Jeffrey C. Lineberry, MPH
Chief, Retail Food Unit
Cc:

Mike Boian, REHS
Northern California Technical Advisory Committee
Butte County Environmental Health
P.O. Box 5364
Chico, CA 95927
Leslie Gentry, REHS
Bay Area Technical Advisory Committee
Solano County Environmental Health
601 Texas Street
Fairfield, CA 94533
Donna Fenton
Central Valley Technical Advisory Committee
Environmental Health Services
2700 “M” Street, Suite 300
Bakersfield, CA 93301

Page 11.6

Peter Ashcraft
October 25, 2002

Elizabeth Quaranta
Southern California Technical Advisory Committee
San Diego County Environmental Health
1255 Imperial Avenue
San Diego, CA 92101
Gary Erbeck, Food Policy Committee
California Conference of Directors of Environmental Health
San Diego County Environmental Health
1255 Imperial Avenue
San Diego, CA 92101

Page 11.7

Page 11.8

Page 11.9

Evaluation #

200424-H Revision 2

Safety & Buildings Division
201 West Washington Avenue
P.O. Box 2658
Madison, WI 53701-2658

Wisconsin
Building Products Evaluation
Material

Manufacturer

Microwave Oven
TurboChef Model NGC

TurboChef Technologies, Inc.
10500 Metric Dr., Suite 128
Dallas, TX 75243

SCOPE OF EVALUATION
Section 507.2.2 of the 2003 and 2004 Supplement of the International Mechanical Code, IMC, regarding exhaust
system requirements where commercial cooking and dishwashing appliances produce grease, smoke, heat or steam have
been evaluated for compliance with certain requirements of the Wisconsin Commercial Building Code (WCBC),
Chapters Comm 61-65. Pursuant to s. Comm 61.61 the TurboChef Models Tornado (NGC), C3/C and High H (HHB)
microwave ovens are approved for use in the State of Wisconsin to satisfy the intent and the provisions of IMC 507.2.2 as
adopted by the Wisconsin Commercial Building Code.
This evaluation does not include the review for compliance to provisions of the current Wisconsin Commercial Building
Code other than those specifically referenced above.
The use of the TurboChef Models Tornado (NGC), C3/C and High H (HHB) microwave ovens are subject to the
description, limitations and conditions described in this evaluation.
DESCRIPTION AND USE

The current Wisconsin Commercial Building Code together with the 2000 edition of the International Mechanical
Code, IMC, does not specifically address, acknowledge or prohibit the utilization of recirculating hoods and vent less
steam removal systems in conjunction with commercial kitchen appliances and their operation where grease, smoke, heat
or steam is produced. The revision under the 2003 edition and 2004 Supplement of the IMC clarify the use of such
appliances.
Section 507.2.2 of the 2003 International Mechanical Code read as follows:
507.2.2 Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce
heat or steam and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing
machines.
SBD-5863 (R. 10/00)

Page 11.10

COMMERCE Product Evaluation No. 200424-H Revision 2
Page 2

Exception:
3. A single light-duty electric convection, bread, retherm or microwave oven designed for installation on a
counter or that is enclosed on five sides in a counter, provided that such appliances do not increase the
ambient temperature more than 10º F at a distance greater than 5 feet away from such appliance during
operation.
LIMITATIONS OF APPROVAL
The evaluation number assigned to this approval is to accompany each plan submitted for projects that utilizes the
TurboChef Models: Tornado (NGC), C3/C and High H (HHB) ovens.
Deviations from this approval shall void the use of the approval.
Pursuant to s. Comm 61.61(7), the department may reexamine an approval and issue a revised approval at any time.

This approval will be valid through December 31, 2009, unless manufacturing modifications are made to the product or a
re-examination is deemed necessary by the department. The product approval is applicable to projects approved under the
current edition of the applicable codes. This approval may be void for project approvals made under future applicable

editions. The Wisconsin Building Product Evaluation number must be provided when plans that include this
product are submitted for review.
DISCLAIMER
The department is in no way endorsing or advertising this product. This approval addresses only the specified applications for the
product and does not waive any code requirement not specified in this document.

Revision Date: March 22, 2006
Approval Date: September 30, 2004 By: __________________________________
Lee E. Finley, Jr.
Product & Material Review
Integrated Services Bureau
200424-H.doc

Page 11.11

Working Together to Promote Food Safety

DATE:

June 11, 2004

TO:

All Local Health Agencies
Minnesota Department of Health (MDH) EHS Sanitarians and Supervisors
Minnesota Department of Agriculture (MDA)

FROM:

Colleen Paulus
Manager, MDH Environmental Health Services Section
Kevin Elfering
Director, MDA Meat, Food and Dairy Division

SUBJECT:

Inter Agency Review Council Document 04-04V
TurboChef Tornado Oven Model NCG

Please distribute the attached information to sanitarians on your staff who work in the Food Program.
Attached please find IARC Guidance Document #04-04V regarding the new TurboChef Tornado
Microwave/Convection Oven Model NCG that is being proposed in Subway Sandwich Shops
throughout Minnesota. This document is very similar, but not exactly the same as IARC Document
#03-01 issued April 9, 2003, which addresses the TurboChef Rapid Cook Oven Model No. C3. The
emissions test for total particulate matter was much lower from the test conducted on the previous oven
(0.5mg/m3 vs. 3.8 mg/m3). However, as you will note in the attached conditions for acceptance, unless
there is a sufficient amount of general ventilation existing in the space, additional cooling capacity may
be needed and verified by a certified testing and balancing contractor.

If you have any questions regarding the TurboChef Tornado Oven Model NCG use, you may
contact the Vent Committee Chair, Lorna Girard, at 651/296-1591 or at lorna.girard@state.mn.us

If you have any questions regarding the IARC, please contact Sue Hibberd at 651/215-0866 or at
sue.Hibberd@health.state.mn.us

Minnesota Department of Health • Environmental Health Services Sec. • P.O. Box 64975 • St. Paul, MN 55164-0975 • (651) 215-0870
Minnesota Department of Agriculture • Dairy and Food Inspection Div. • 90 W. Plato Blvd. • St. Paul, MN 55107-3219 • (651) 296-2627
An equal opportunity employer

Page 11.12

JENNIFER M. GRANHOLM
GOVERNOR

STATE OF MICHIGAN
DEPARTMENT OF AGRICULTURE
LANSING

DAN WYANT
DIRECTOR

April 14, 2004
Mr. James Boyd, Plan Review Specialist
Kent County Health Department
Environmental Health Division
700 Fuller Avenue, N.E.
Grand Rapids, MI 49503
Re: Turbo-Chef Convection / Microwave Oven Models C3/C and NGC
Dear Mr. Boyd:
You requested an evaluation of the Turbo Chef oven model NGC, that is proposed to be
installed in Subway restaurants state-wide. MDA recommends that both model NGC and C3/C
may be installed and used without ventilation in any food establishment as they are UL197SB
listed. These ovens contain an internal filter and vent that has been shown, under proper test
conditions, to emit very little grease (pepperoni pizzas were used in testing).
Preparation in these ovens without additional ventilation should be limited to pizzas, sub
sandwiches, reheating of par-baked or cooked foods, other similar items and baking. Neither
MDA nor the manufacturer recommends cooking raw, fatty protein products (i.e. raw meat) in
these ovens.
Michigan's mechanical code rules (R 408.30935a) specifically exempt from ventilation "listed
factory-built commercial cooking recirculating systems which are tested in accordance with UL
197" and installed per listing and manufacturer's directions. However, a mechanical inspector
may require ventilation if the building has inadequate general ventilation.
If you have any questions please call me at (517) 373-2779.
Sincerely,

Kevin Besey, Supervisor
Food Service Sanitation Section
Food and Dairy Division
cc:

James Pool, Turbo Chef
Dave Adams, Assistant Chief, Mechanical Division, BCC, MDCIS
Michigan local Health Departments / MDA Regions

CONSTITUTION HALL y P.O. BOX 30017 y LANSING, MICHIGAN 48909
www.michigan.gov y (517) 373-1104

Page 11.13

Page 11.14

Page 11.15

Page 11.16

Page 11.17

HI|IFÐtr

BiffLMHG À!*Ð 5AfËTY
€ûÉ{tftssÍ01{,f Rs

C¡rv rF Los ANc=r-=s

IEFX¡*rr
B

C*,LIFORFIIÅ

I'ILE}Ii{G

¡Ë.1

filÅ*sf{i\TÐ,R$w,¡l
FñËffi${T

ì/åù,¡ AldE.É\¡ELt5
VtrPëSS9E¡IIT

ATËE} SÂF:ETV

I{TETH FIG{.EROÅ STFÉET
LWAI,¡GEI-ES. CA Ðtr

ROÊ:f RT R. "EUÐF 01¡.RtM
GEiEtr\¡- IS{HÂGER

VICTÐ'R H. CUEVÀ5
HELEHAJ UB,AT'IY
E LtlJ ûRE ll ì¡"dlLLtALlS

RAY¡,i0t'tÐs. 0HAN, c.E.,

s.Ë..

¡ts4uTir"= C!E:F.

*NTC}NI O R VILLÀR¡.,ITÛSA
!,t.åYoR

James

K Pool

III

File Number: M-100012

TurboChef Technologies
42 40 lnternational Pa rkway

Effective Date:

Carrollton, TX 75034

Expiration Dafe:

Telephone:

21

4-379-6020

Models:

04101 1201 I
04101 12012

Manufacturer: SAME

Item: WARMING OVEN

NGC+, NGO (*new model added),
PLEASE REFER TO THE APPLICATION NUMBER ON ALL CORRESPONDENCE, PHONE CALLS & SAMPLES

The item processed under the above file number has been tested, examined and found to comply with applicable Los Angeles Plumbin¡
Code (LAPC) and/or Los Angeles Mechanical Code (LAMC) and is hereby approved unless revoked for cause.

This letter or the letterhead copy may not be reproduced for use in labeling or advertising, but copies of this letter may be used within
your organization and shown as evidence ofapproval.

CONDITIONS OF APPROVAL:
1. This product shall be used to warm pre-cooked hot food items only. Any other type of cooking shall not be allowed,
2.Installation of this product is not required to have an exhaust system per Sections 95.507.1.1 and 95.507.1.2 of LAMC,
20ll Edition.
3. This product shall be installed, operated, and maintained in accordance with printed instructions from the
manufacturer and LAMC, 2011 Edition.

Each item shall have the name or trademark of nranufacturer and model numbqr'"yherc it

will

be visible for inspection,

In order to renew this approval, an application and reexamination fee must be submitted on or before the expiration date shown above.
Arrangement shall be made to remove any test samples remaining in the Laboratory. Samples remaining after 21 days from the date of
this notice will be shipped collect by the most convenient carrier or disposed of in accordance with applicable regulation,

Jason T Tran
Mechanical Testing Laboratory, Test Engineer

Plumbing / Mechanical Inspection
Inspection Bureau

z
Axorl¡s
a I Couxw
A{.
Prhlio
HeAItlt
r ¡rrrr
\\
oF Los

'

, JONATHAN

E. FIELDING, M.D., M.P,H.
BOARD OF SUPERVISORS

D¡rector and Health Officer

Gloria Molina

JONATHAN E. FREEDMAN

First Distr¡ct

Chief Deputy Director

Mark R¡dley-Thomas

ANGELO BELLOMO, R.E.H.S., Director

Zev Yaroslavsky

Second D¡str¡ct

Environmental Health

Th¡rd Distr¡ct

Don Knabe

VERONICA BAUCHMAN, R.E,H.S.

Fourth Distr¡ct

Act¡ng Director, Bureau of District Surveillance and Enforcement

M¡chaèl D. Antonovich
F¡fth Distr¡ct

PLAN CHECK PROGRAM
5050 Commerce Dr¡ve
Baldwin Park, California 91706
. FAX (626) 813-1444

TEL (626) 430-s560

$¡$¡r¡v:äÍb I iOhèâlf h: Iãcôuntv :¡i:a¡v/éh/

May

3l,20ll

K. Pool III
Senior Vice President, Engineering
TurboChef Technologies, Inc.
4240 International Parkway, Suite 1 0 1
Carrollton, Texas 75007
James

Ventilation Exemption Plan Check No.
Application Type:
Effective Date:
Expiration Date:
Telephone:
Email:

PtâñorECr(mßER:

ItÉ-Paø

'0t/

ME-2010-009
Equipment specific
5t3r/2011
6t1t2016
(2r4) 379-6020
James. Pool @Jurbochef. com

RE: Exemption from mechanical exhaust ventilation for TurboChef Technologies,Inc.
Model Tornado (NGC) and Tornado 2 (NGCD6) ovens
Dear Mr. Pool:
The County of Los Angeles Department of Public Health, Environmental Health, Plan Check has
completed a review of the TurboChef Technologies, Inc. Model: Tornado (NGC) and Tornado 2
(NGCD6) ovens for exemption from the mechanical exhaust ventilation requirements of Section
114149.1(a) of the California Retail Food Code.

You have provided documentation that these ovens have Underwriter's Laboratory KNLZ
approval, and also provided the results of the eight-hour cooking emissions test conducted on the
Tornado (NGC) oven. The test results indicate that the particulate matter concentration produced
was 1.153 ffidfrì', which is below the limit of 5 mg/ m'to be considered a low grease emission
appliance.

Page 11.19

TurboChef Oven
May 3I,20lI
Page2 of3

Therefore, additional mechanical ventilation in the form of a Type I or Type II hood is not
required by the County of Los Angeles Department of Public Health, provided the following
contingencies are met:

L

There shall be no more than two unventilated model Tomado (NGC) or Tornado 2
(NIGCD6) oven per food facility.

2.

No other heat producing food related equipment requiring ventilation shall be
t the addition of mechanicai ventilation.

3.

The equipment must
manufacturer's

4.

Any modification,
of the integral air
and this limited ex
operational at aII ti

maintained accordins to the

uipment, including any component
ANSI certification of the equipment
ponents must be installed and

5. The Tornado or Tomado

used for the cooking or warming of pizza,
bread, bakery products, or similar items only. No raw animal protein products shall
be cooked in the equipment unless mechanical ventilation is provided.
a_!

i;) l.l

6.

No items that generate grease-laden vapors shall be prepared or cooked in the
unventilated Tornado or Tomado 2 oven.

7.

The Tornado or Tornado 2 oven must be operated in a well-ventilated area approved
for food preparation.

8.

If the ownership changes at a food facility that is operating the exempt equipment,
then the new owner/ operator will be informed of the operating conditions.

9.

This exemption from mechanical exhaust ventilation shall not be deemed to
supersede any local building and ltre code requirements pertaining to electrical and
fire safetv.

Page 11.20

TurboChef Oven
May 31,2071
Page 3 of3

This exemption shall be in effect for a period of five years from the date of this letter, or until
revoked. However, this exemption shall not preclude this Department from requiring the
installation of mechanical exhaust ventilation when operation of the Tomado or Tornado 2 oven
at a specific location results in a sanitation or safety violätion. These problems may include, but
are not limited to, problems of installation, use, maintenance, cleaning or other site specific
considerations which exceed the above limitations or pose a discernable health or safety hazard.
This letter may be used as evidence of the evaluation of the TurboChef Model Tomado (NGC) or
Tornado 2 (NGCD6) rapid cooking ovens. However, it is not to be construed as an endorsement
of the subject items and may not be used for advertising or promotional purposes.
Should you have any questions or need additional information, please contact me at
(626) 430-ss60.

geonu, R.E.H.S.

ise Noborio, R.E.H.S.

Chief EHS
Plan Check Program

Environmental Health Specialist IV
Plan Check Program

PLANcHEcxr,¡u

ru^,

14É' 240 -oof

Page 12.1

T URB O C HE F TE C HNOLOGI E S, I N C.

Tornado 2 Oven Surface Temperatures

TM

(271°C) for the duration of the test.

After 4-Hour Idle at 520°F/271°C (Values in °F/°C)

82/28

76/24

75/24

76/24

77/25

85/29

75/24

74/23

77/25

79/26

82/28

88/31

78/26

78/26

79/26

82/28

82/28

81/27

78/26

78/26

81/27

83/28

77/25

75/24

84/29

91/33

103/39

98/37

96/36

93/34

83/28

109/43

133/56

138/59

118/48

92/33

90/32

82/28

123/

146/

148/

130/

90/32

81/27

83/28

125/52

142/61

149/65

128/53

83/28

80/27

84/29

89/32

111/44

108/42

100/38

80/27

80/27

94/34

96/36

98/37

102/39

99/37

92/33

86/30

88/31

92/33

95/35

92/33

90/32

88/31

83/28

88/31

77/25

81/27

83/28

78/26

77/25

78/26

83/28

84/29

88/31

82/28

85/29

77/25

81/27

83/28

83/28

86/30

82/28

84/29

79/26

80/27

72/22

71/22

71/22

84/29

83/28

93/34

99/37

99/37

95/35

90/32

79/26

80/27

79/26

81/27

80/27

80/27

81/27

75/24

77/25

99/37

97/36

98/37

98/37

97/36

97/36

83/28

95/35

80/27

84/29

82/28

86/30

88/31

83/28

76/24

93/34

91/33

95/35

96/36

97/36

97/36

83/28

83/28

83/28

84/29

85/29

93/34

89/32

86/30

84/29

83/28

82/28

89/32

95/35

96/36

91/33

80/27

79/26

78/26

83/28

91/33

102/39

94/34

86/30

92/33

82/28

78/26

81/27

82/28

87/31

78/26

75/24

75/24

76/24

87/31

85/29

90/32

89/32

87/31

86/30

86/30

87/31

91/33

91/33

94/34

93/34

88/31

81/27

76/24

© 2012 TurboChef Technologies, Inc.

DOC-1374 / Rev B / November 2012
Page 1 of 2

Page 12.2

After 4-Hour Idle and 2 Hours of Cooking at 520°F/271°C (Values in °F/°C)

100/38

103/39

109/43

93/34

95/35

106/41

92/33

93/34

105/41

97/36

102/39

113/45

100/38

106/41

110/43

102/39

102/39

93/34

119/48

102/39

88/31

99/37

92/33

131/55

120/49

110/43

111/44

107/42

102/39

103/39

101/38

100/38

114/46

106/41

107/42

106/41

91/33

114/46

135/57

142/61

132/56

110/43

103/39

91/33

130/54

154/68

163/73

148/64

118/48

100/38

89/32

124/51

154/68

162/72

144/62

112/44

102/39

90/32

94/34

118/48

114/46

122/50

112/44

97/36

99/37

106/41

111/44

118/48

126/52

111/44

98/37

97/36

104/40

108/42

110/43

114/46

110/43

102/39

94/34

109/43

110/43

97/36

99/37

113/45

101/38

90/32

101/38

123/51

87/31

90/32

102/39

91/33

92/33

88/31

88/31

87/31

99/37

97/36

98/37

105/41

108/42

106/41

101/38

111/44

106/41

105/41

93/34

93/34

93/34

97/36

88/31

87/31

106/41

104/40

103/39

105/41

108/42

109/43

120/49

118/48

111/44

96/36

96/36

101/38

102/39

96/36

88/31

104/40

98/37

103/39

109/43

110/43

109/43

125/52

114/46

121/49

95/35

97/36

104/40

103/39

97/36

96/36

95/35

90/32

103/39

112/44

113/45

106/41

106/41

103/39

104/40

95/35

103/39

111/44

107/42

100/38

105/41

95/35

90/32

93/34

96/36

100/38

88/31

90/32

90/32

92/33

93/34

99/37

101/38

103/39

102/39

102/39

100/38

97/36

100/38

100/38

104/40

105/41

98/37

93/34

86/30

© 2012 TurboChef Technologies, Inc.

DOC-1374 / Rev B / November 2012
Page 2 of 2



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Author                          : dusty.crumpton
Create Date                     : 2008:11:06 16:23:46Z
Modify Date                     : 2012:12:06 12:01:04-06:00
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Creator Tool                    : PrimoPDF http://www.primopdf.com
Metadata Date                   : 2012:12:06 12:01:04-06:00
Thumbnail Width                 : 212
Thumbnail Height                : 256
Thumbnail Format                : JPEG
Thumbnail Image                 : (Binary data 15150 bytes, use -b option to extract)
Format                          : application/pdf
Creator                         : dusty.crumpton
Title                           : Microsoft Word - NGC Ventless ToC.doc
Producer                        : AFPL Ghostscript 8.13
Document ID                     : uuid:c3ba93e0-126f-451a-a32e-b9cab64cb37f
Instance ID                     : uuid:6d075922-eed9-44dd-923a-fa90bf5f7d6b
Rendition Class                 : proof:pdf
N Pages                         : 1
Has Visible Transparency        : False
Has Visible Overprint           : True
Max Page Size W                 : 8.500000
Max Page Size H                 : 11.000000
Max Page Size Unit              : Inches
Font Name                       : MyriadPro-Regular
Font Family                     : Myriad Pro
Font Face                       : Regular
Font Type                       : Open Type
Font Version                    : Version 2.062;PS 2.000;hotconv 1.0.57;makeotf.lib2.0.21895
Font Composite                  : False
Font File Name                  : MyriadPro-Regular.otf
Plate Names                     : Cyan, Magenta, Yellow, Black
Swatch Group Name               : Default Swatch Group
Swatch Group Type               : 0
Page Count                      : 39
EXIF Metadata provided by EXIF.tools

Navigation menu