Tyco Safety Canada 00LINKS2450 LINKS 2450 Long Range RF Transmitter User Manual Installation manual

Digital Security Controls Ltd. LINKS 2450 Long Range RF Transmitter Installation manual

Installation manual

Download: Tyco Safety Canada 00LINKS2450 LINKS 2450 Long Range RF Transmitter User Manual Installation manual
Mirror Download [FCC.gov]Tyco Safety Canada 00LINKS2450 LINKS 2450 Long Range RF Transmitter User Manual Installation manual
Document ID127081
Application IDIBSG1ZU9TIvY4COWQz1TKA==
Document DescriptionInstallation manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize8.52kB (106522 bits)
Date Submitted2000-11-30 00:00:00
Date Available2001-02-01 00:00:00
Creation Date2000-07-20 10:52:05
Producing SoftwareAcrobat Distiller 3.0 for Windows
Document Lastmod2000-09-29 10:49:20
Document TitleInstallation manual

•WARNING•
Please refer to the System Installation Manual for information on
limitations regarding product use and function and information on
the limitations as to liability of the manufacturer.
How to Contact Us:
Sales
For information about additional products, please call our sales number:
1-888-623-7873, fax us at 1-416-665-4222 or e-mail us at sales@sur-gard.com.
Technical Support
If you have questions or problems when using Sur-Gard products, you can call technical
support. If you are within the United States, Puerto Rico, the U.S. Virgin Islands or Canada,
you can get support by dialing 1-888-623-7873 ext.1. If you are outside these areas,
please call (416) 665-0051 ext.1, or e-mail us at support@sur-gard.com.
Long Range RF Transmitter
Internet
Visit our Sur-Gard WWW site. You can search the Sur-Gard technical information database
and read about our new productsas well as send us your questions on-line. Our World
Wide Web address is http://www.sur-gard.com.
© 2000 SG Wireless Communications
401 Magnetic Drive, Units #24-28
Downsview, Ontario, Canada M3J 3H9
29003619 R001
INSTALLATION MANUAL
Version 1.2
Limited Warranty
SG Wireless Communications warrants that for a period of twelve months from the date of purchase,
the product shall be free from defects in materials and workmanship under normal use and that in
fulfillment of any breech of such warranty, SG Wireless Communications shall, at its option, repair
or replace the defective equipment upon return of the equipment to its repair depot. This warranty
applies only to defects in parts and workmanship and not to damage incurred in shipping or
handling, or damage due to causes beyond the control of SG Wireless Communications, such as
lightning, excessive voltage, mechanical shock, water damage, or damage arising out of abuse,
alteration or improper application of the equipment.
The foregoing warranty shall apply only to the original buyer, and is and shall be in lieu of any and
all other warranties, whether expressed or implied and of all other obligations or liabilities on the part
of SG Wireless Communications. SG Wireless Communications neither assumes, nor authorizes
any other person purporting to act on its behalf to modify or to change this warranty, nor to assume
for it any other warranty or liability concerning this product.
In no event shall SG Wireless Communications be liable for any direct or indirect or consequential
damages, loss of anticipated profits, loss of time or any other losses incurred by the buyer in
connection with the purchase, installation or operation or failure of this product.
WARNING: SG Wireless Communications recommends that the entire system be completely
tested on a regular basis. However, despite frequent testing, and due to but not limited to,
criminal tampering or electrical disruption, it is possible for this product to fail to perform
as expected.
TABLE OF CONTENTS
Section 1: Introduction
1.1 Specifications ........................................................................................ 1
1.2 Antenna ................................................................................................. 2
Section 2: Installing the Links2450
2.1 Unpacking the LINKS2450 .................................................................... 3
2.2 Select a Mounting Location .................................................................. 3
2.3 Connect a Power Supply ....................................................................... 3
2.4 Mount and Wire the LINKS2450 ........................................................... 4
Diagram 2-1: Hook-up For PC5010, PC5015, PC1555/1565,
PC1575/1580 or PC580/585 Panels .................................................... 5
Diagram 2-2: Hook-up for PC4010/4020 v3.0 Panels ........................... 6
Section 3: Programming the LINKS2450
3.1 Programming a LINKS2450 Connected to a PC5015, PC5010,
PC1575/1580, PC1555/1565 PC580/585 Panel ................................... 7
3.2 Programming a LINKS2450 for Use with a
PC4010/PC4020 v3.0 or higher panel. ................................................ 8
Diagram 3-1: Connecting the LINKS2450 to a PC2550RK Keypad ........ 8
Section 4: Programming Descriptions
10
[01] Module Configuration ......................................................................... 10
[10] LINKS 2450 Account Code ................................................................. 10
[20] Maintenance Alarms and Restoral Reporting Codes ......................... 10
[30] Call Direction Options (PC5015, PC5010, PC1575/1580,
PC1555/1565 and PC580/585 panels only) ...................................... 10
[81] Miscellaneous Alarm Reporting Codes (PC1575/1580 panel only) ..... 11
[82] Miscellaneous Restoral Reporting Codes (PC1575/1580 panel only) .... 11
[83] Miscellaneous Alarm Reporting Codes
(PC1555/1565 v2.0 panel only) .......................................................... 11
Section 5: Testing the LINKS2450
12
5.1 Performing a LINKS Test Transmission .............................................. 12
5.2 “On Air” Indication ............................................................................... 12
5.3 Troubleshooting ................................................................................... 12
5.4 Testing Tools ........................................................................................ 12
5.5 Periodic Test Transmission .................................................................. 12
Section 6: Reset LINKS2450 Programming to Factory Default
13
6.1 Reset the LINKS2450 on a PC1575/1580 Panel ................................ 13
6.2 Reset the LINKS2450 on a PC5015 v2.2, PC5010 v2.0,
PC1555/1565 or PC580/585 Panel .................................................... 13
6.3 Perform a Hardware Reset (All panels) ............................................. 13
Programming Worksheets
14
NOTES:
ii
NOTES:
NOTES:
INTRODUCTION
Section 1
The LINKS2450 transmits alarm system information over a long-range radio
network. It may be used with the following DSC alarm control panels:
• PC1575/1580 v1.0
• PC4010/4020 v3.x
• PC1555/1565 v2.x and up
• PC5015 v2.2
• PC580/585 v2.x
• PC5010 v1.0 and up
This manual will describe how to install and program the LINKS2450 for connection
to the above panels.
1.1 Specifications
NOTE: If the panel uses automatic SIA or Contact ID communications formats, the
reporting codes the LINKS2450 will send must still be programmed on the panel.
• Power supply: 11.5-14VDC at 750mA (PS1520, PC5204, PC4204, or powered
from Bell+/Aux- control panel terminals)
• Radio transmitter frequency: range from 440 to 470MHz
• Communication Buffer: 80 Events
• Transmission Range: Approximately 16 Kilometers (10 Miles)
• Cabinet dimensions: 4.17” high × 5.75” wide × 1” deep (104mm × 146mm ×
26mm); color: white
• Module supervision via the alarm control panel
• Protected against static and lightning induced transients
• Programming by keypad or downloading software. The LINKS2450 is complete
with a default program and is operational with a minimum of programming.
• To program via a keypad when connected to PC5015, PC5010, PC1575/1580,
PC1555/1565 or PC580/585 panels, program the LINKS2450 using any
system keypad
• To program via a keypad when connected to PC4010/4020 v3.0 panels,
program the LINKS2450 using a PC2550RK keypad connected directly to the
LINKS2450.
• EEPROM Memory
The LINKS2450 uses EEPROM memory, which will retain all program
information even if AC and battery power, are removed.
1.2 Antenna
NOTE: You must match the antennas to the frequency you will be using.
The antenna for the LINKS2450 is not supplied. For optimum performance of the
LINKS2450, use a quality antenna system, such as model SLA-532, available from
Safe Link Corporation. This 5/8 over 5/8 wave high performance antenna offers
features specifically designed for security radio installations.
• 5db gain two-piece mast with center coil
• Standard frequency range 440-470MHz
• Ten feet of coax with BNC connector attached.
To ensure proper operation, mount the antenna at least ten feet from the LINKS
2450 unit. (See diagram below).
[83] Miscellaneous Alarm Reporting Codes
(PC1555/1565 v2.0 panel only)
Default = FF
I_______I_______I
Police Code
I_______I_______I
Delinquency Code
[96][Installer Code][96]
Restore LINKS2450 Factory Default Programming for PC1575/
1580
[993][Installer Code][993]
Restore LINKS2450 Factory Default Programming for PC5015
v2.2, PC5010 v2.0, PC1555/1565 and PC580/585
PC4010/4020 LINKS2450 Toggle Options
Program these options at a PC4010/4020 system keypad. See section 3.2 for more
information.
Ref # [000405]
LINKS 2XXX (use arrow keys (< >) to scroll to each option)
Option
Default
LINKS 2XXX
N (Y for CF panels)
Alarm/Restore
N (Y for CF panels)
Open/Close
N (Y for CF panels)
All Others
N (Y for CF panels)
15
PROGRAMMING WORKSHEETS
INSTALLING THE LINKS2450
[01] Module Configuration
Before installing the LINKS2450, install and test the security system to which it will
be connected, according to the system’s Installation Manual.
Default
ON
I_______I
Option
ON
Communications
enabled
OFF
Communications
disabled
OFF
I_______I
Serial connection
Keybus connection
[10] LINKS2450 Account Code
Default
FF FF
I_______I_______I
Valid entries are 00-FF
Enter two 2-digit hexadecimal numbers.
I_______I_______I
Keybus/Serial Fault Alarm
I_______I_______I
Keybus/Serial Fault Restoral
I_______I_______I
For future use
OFF
OFF
I_______I
I_______I
I_______I
I_______I
I_______I
I_______I
6-7
•
LINKS2450 circuit board
•
LINKS2450 plastic cabinet
CAUTION: Due to the sensitivity of the RF circuitry, avoid any contact with the coils
and potentiometers on the LINKS2450 circuit board.
The area where you mount the LINKS2450 should be:
• dry
• close to the installed alarm control panel cabinet.
• far from sources of interference, including: electrical noise such as computers,
televisions and electric motors in appliances and heating and air conditioning
units; large metal objects like heating ducts and plumbing which may shield the
antenna. If you must mount the LINKS2450 near such items, you may have to
mount the antenna on a remote bracket away from the LINKS2450.
• close to the power supply. See section 2.3 “Connect a Power Supply”.
[30] Call Direction Options (PC5015, PC5010, PC1575/1580
and PC1555/1565 panels only)
Option
Check that each of these parts is included in your LINKS2450 package.
2.2 Select a Mounting Location
Default = FF
I_______I
2.1 Unpacking the LINKS2450
l_______I_______I
[20] Maintenance Alarms and Restoral Reporting Codes
Default
ON
ON
OFF
ON
ON
Section 2
ON
Alarm/restore reporting enabled
Tamper/restore reporting enabled
Opening/closing reporting enabled
System maintenance reporting enabled
System test transmission reporting
enabled
For future use
Future event Support
OFF
Disabled
Disabled
Disabled
Disabled
Disabled
Enabled
Disabled
[81] Miscellaneous Alarm Reporting Codes (PC1575/1580 panel only)
2.3 Connect a Power Supply
You can use the Bell+ and Aux- terminals from the control panel to power the
LINKS2450. If you will be using a separate power supply, install it near the
LINKS2450. Refer to the power supply’s installation instructions, for more information.
NOTE: The current drawn by the LINKS2450 and the siren(s) connected to the Bell
terminals must not exceed that specified by the rating of the control panel. Refer to
your control panel’s Intallation Manual for more information.
The wiring between the LINKS2450 and the power supply should not be longer than
indicated in the table below:
Wire Gauge (AWG)
Maximum Wire Length (feet / meters)
Default = FF
I_______I_______I
General Zone Fault Alarm
I_______I_______I
General System Tamper Alarm
I_______I_______I
General System Supervisory Alarm
[82] Miscellaneous Restoral Reporting Codes
(PC1575/1580 panel only)
22
15' / 4.5m
20
25' / 7.5m
18
40' / 12.0m
You can double the maximum wire length if you double the conductors and connect
them in parallel. Mount the LINKS2450 as close to the power supply as possible.
Default = FF
14
I_______I_______I
General Zone Fault Restore
I_______I_______I
General System Tamper Restore
I_______I_______I
General System Supervisory Restore
2.4 Mount and Wire the LINKS2450
1. Run the panel wiring and the power supply wiring to the LINKS2450 mounting
location.
2. Remove the four screws that attach the LINKS2450 circuit board to the
plastic cabinet.
3. Pull all wires through the hole at the back of the cabinet.
4. Mount the cabinet securely to the wall. Use the appropriate wall anchors
when securing the panel to drywall, plaster, concrete, brick or similar
surfaces.
5. Reattach the LINKS2450 into the mounted cabinet using the four mounting
screws.
6. Find the antenna connection in the hole at the top of the cabinet. Secure the
antenna to the LINKS2450 antenna connector.
NOTE: Make sure an antenna is always connected to the LINKS2450 whenever it
is operated. The unit will not work and may be damaged if an antenna is not installed.
7. Complete all wiring: If you will be connecting the LINKS2450 to a PC5015,
PC5010, PC1575/1580, PC1555/1565 or PC580/585 panel, go to step 8a. If
you will be connecting the LINKS2450 to a PC4010 or PC4020 panel, go to
step 8b.
8a. Connect the LINKS2450 according to diagram 2-2. Make sure jumper J3
on the LINKS2450 is NOT shorted.
8b. Connect the LINKS2450 to a PC2550RK keypad according to diagram 31. Make sure jumper J3 on the LINKS2450 IS SHORTED. When you have
finished programming, disconnect the power supply and the PC2550RK
keypad from the LINKS2450. Remove the short from jumper J3. Connect
the LINKS2450 to the control panel according to diagram 2-3.
NOTE: Double-check all wiring to ensure that it is correct. Incorrect wiring connections may cause the LINKS2450 to operate improperly, or may damage the unit.
RESET LINKS2450 PROGRAMMING TO FACTORY
DEFAULT
Section 6
If you need to reset the LINKS2450 to factory default programming, follow the
directions in the appropriate sections below.
6.1 Reset the LINKS2450 on a PC1575/1580 Panel
To reset the LINKS2450 on a PC1575/1580 panel, enter [96] [Installer’s Code] [96].
6.2 Reset the LINKS2450 on a PC5015 v2.2, PC5010 v2.0, PC1555/
1565 or PC580/585 Panel
To reset the LINKS2450 on a PC5015 v2.2, PC5010 v2.0 or PC1555/1565 panel,
enter [993] [Installer’s Code] [993].
NOTE: This command is unavailable on PC5010 v1.0. If v1.0 is used, you must
perform a hardware reset (see section 6.3 below).
6.3 Perform a Hardware Reset (All panels)
To reset the LINKS2450 when connected to a PC5010 v1.0 or a PC4010/4020
panel, you must perform a hardware reset. To do this:
1. Remove all power from the LINKS2450
2. Short j umper J3
3. Remove all wires from the YEL and GRN terminals
4. With a piece of wire, short the YEL terminal to the GRN terminal
5. Apply power to the LINKS2450 for 5 seconds.
6. Remove power from the LINKS2450
7. Reconnect all original wiring and re-power the LINKS2450
NOTE: If the LINKS2450 is connected to a PC4010/4020 panel, the programming
done in the panel software will not be reset. See section 3.2, step 5 for information
on re-programming the PC4010/4020 sections.
8. Connect the power: Connect the power terminals (VTX+ and VTX–) to a 11.5 14VDC, 1A power supply.
CAUTION: Do not connect the power supply until all other wiring, including the
antenna connection, has been completed and checked to ensure that it is correct.
13
TESTING THE LINKS2450
Section 5
Before testing the LINKS2450, ensure that the control panel is correctly programmed and operating properly. Refer to your system Installation Manual for
instructions on testing your system. The control panel must be programmed properly
in order for the LINKS2450 to operate.
DIAGRAM 2-1
Hook-up For PC5010, PC5015, PC1555/1565, PC1575/1580 or
PC580/585 Panels
NOTE: Programming section [01], option 2 must be OFF for LINKS2450 to work
with these panels.
To check that the LINKS2450 is working, apply power to the unit after all wiring
connections have been made. When the LINKS2450 is sending a transmission, the
LED on the circuit board will turn on.
5.1 Performing a LINKS Test Transmission
Contact the monitoring station to request a transmission test. Remove the telephone
cord from the RJ31-X jack. Perform a Bell Test as described in the control panel’s
Installation Manual. When the test is complete, contact the monitoring station to
confirm the transmission. Perform additional test transmissions as required by the
central station.
5.2 “On Air” Indication
Whenever the LINKS unit is communicating, the LED on the unit’s circuit board will
turn ON for each round of communications. Each event has 3 rounds. Therefore, if
one reporting code is sent, the LED will activate 3 times to indicate each round.
5.3 Troubleshooting
If the LINKS2450 is not working properly, check that all wiring and all programming
is correct before calling for technical support.
5.4 Testing Tools
The following tools are available from Safe Link:
UHF RF Power Meter - Connects to the antenna jack on the LINKS2450. Indicates
the transmit power of the radio.
UHF Scanner - Checks that the radio is transmitting data.
Frequency Counter - Checks that the LINKS2450 is transmitting on the correct
frequency.
5.5 Periodic Test Transmission
The LINKS 2450 will transmit a periodic test transmission at the time/day/interval
using the Reporting code programmed in the main control panel.
CAUTION: Due to the sensitivity of the RF circuitry, avoid any contact with the coils
and potentiometers on the LINKS2450 circuit board.
*If power supply supervision is required for the LINKS2450 VTX terminals, use the
PC5204. If no supervision is needed, you can use the PS1520 or the control panel
Bell+/Aux- terminals.
12
DIAGRAM 2-2
Hook-up for PC4010/4020 v3.0 Panels
NOTE: Programming section [01], option 2 must be ON for LINKS2450 to work with
these panels.
[81] Miscellaneous Alarm Reporting Codes
(PC1575/1580 panel only)
Program 2 digit reporting codes for the following:
• General Zone Fault Alarm
This code will be sent when the LINKS2450 receives a General Zone Fault
Alarm event from the PC1575/1580.
• General System Tamper Alarm
This code will be sent when the LINKS2450 receives a General System
Tamper Alarm event from the PC1575/1580.
• General System Supervisory Alarm
This code will be sent when the LINKS2450 receives a General System
Supervisory Alarm event from the PC1575/1580.
[82] Miscellaneous Restoral Reporting Codes
(PC1575/1580 panel only)
Program 2 digit reporting codes for the following (see your PC1575/1580 Installation
Manual for more information):
• General Zone Fault Restoral: This code will be sent when the LINKS2450
receives a General Zone Fault Restoral event from the PC1575/1580.
• General System Tamper Restoral: This code will be sent when the
LINKS2450 receives a General System Tamper Restoral event from the
PC1575/1580.
• General System Supervisory Restoral: This code will be sent when the
LINKS2450 receives a General System Supervisory Restoral event from the
PC1575/1580.
NOTE: Sections [81] and [82] apply to the PC1575/1580 only. All other panels will
use the reporting codes that are programmed for these events in the panel.
[83] Miscellaneous Alarm Reporting Codes
(PC1555/1565 v2.0 panel only)
Program 2 digit reporting codes for the following (see your PC1555/1565 Installation
Manual for more information):
• Police Code: This code will be sent when the LINKS2450 receives a Police
Code event from the PC1555/1565.
• Delinquency Code: This code will be sent when the LINKS2450 receives a
Delinquency event from the PC1555/1565.
CAUTION: Due to the sensitivity of the RF circuitry, avoid any contact with the coils
and potentiometers on the LINKS2450 circuit board.
*If power supply supervision is required for the LINKS2450 VTX terminals, use the
PC4204. If no supervision is needed, you can use the PS1520 or the control panel
Bell+/Aux- terminals .
11
PROGRAMMING DESCRIPTIONS
Section 4
[01] Module Configuration
Option 1: Communications Enabled / Disabled
Enable this option to have the LINKS2450 initiate communications for all events that
have reporting codes and call direction options (section [30]) programmed. Disable
this option to test the system.
Option 2: Serial Connection / Keybus Connection
Enable this option if you will use the LINKS2450 with a PC4010/4020 panel. Disable
this option if you will use the LINKS2450 with a PC5015, PC5010, PC1575/1580,
PC1555/1565/1565 or PC580/585 panel.
[10] LINKS2450 Account Code
This 4-digit code is used to identify the system and is transmitted when the
LINKS2450 initiates communications. Program a 4-digit code in this section using
2 two-digit Hexadecimal numbers. Refer to your control panel Installation Manual for
instructions on programming hexadecimal digits.
NOTE: An account number must be entered in this section before the LINKS2450
can send any communications. Programming [FFFF] will disable the LINKS2450.
[20] Maintenance Alarms and Restoral Reporting Codes
Program 2 digit reporting codes for the following:
• Keybus/Serial Fault Alarm: This code will be sent when connection is lost to
the panel for more than 30seconds.
• Keybus/Serial Fault Restoral: This code will be sent when connection is
restored to the panel for more than 30seconds.
• For future use.
[30] Call Direction Options (PC5015, PC5010, PC1575/1580, PC1555/
1565 and PC580/585 panels only)
Program which of the following reporting code types the LINKS2450 will send to the
central station:
• Alarm/restore reporting
• Tamper/restore reporting
• Opening/closing reporting
• System maintenance reporting
• System test transmission reporting
• Future event support
In most installations, you should program the tranmission of alarm/restore
reporting codes only. Your radio network has limited bandwidth and capacity. The
more signals each LINKS2450 transmits, the fewer LINKS2450s you will be able to
install on your network.
The Future Event Support option refers to reporting codes (events) that may be
added to future software versions of DSC control panels. If you turn on the Future
Event Support option, when the new events occur, the LINKS2450 will send
reporting codes for the events to the central station. If you do not turn this option on,
the LINKS2450 will not send reporting codes for events that are not currently
included in one of the call direction groups.
10
PROGRAMMING THE LINKS2450
Section 3
See section 3.1 for programming instructions when connecting the LINKS2450 to
a PC5015, PC5010, PC1575/1580, PC1555/1565 or PC580/585 panel. See section
3.2 for programming instructions when connecting the LINKS2450 to a PC4010 or
PC4020 v3.0 panel.
3.1 Programming a LINKS2450 Connected to a PC5015, PC5010,
PC1575/1580, PC1555/1565 or PC580/585 Panel.
Program the LINKS2450 through Installer’s Programming at a system keypad.
For instructions on using Installer’s Programming sections, please refer to
Section 4 “How to Program” in your control panel Installation Manual.
1. Go to Installer’s Programming by entering [*][8][Installer’s code].
2. For PC5015, PC5010, PC1555/1565 and PC580/585: Go to the LINKS2450
programming section by entering [803]. Program the following sections only
(see section 4 for a description of each section). Record your programming
choices in the worksheets at the end of this manual.
[01] Module Configuration
Option 1: Communications Enabled / Disabled
Option 2: Serial Connection / Keybus Connection
[10] LINKS2450 Account Code
[20] Maintenance Alarms and Restoral Reporting Codes
[30] Call Direction Options
[83] Miscellaneous Alarm Reporting Codes (PC1555/1565 v2.0 panel only)
3. For PC1575/1580: Go to the LINKS2450 programming section by entering
[86]. Program the following sections only. See section 4 for a description of
each section. Record your programming choices in the worksheets at the end
of this manual.
[01] Module Configuration
Option 1: Communications Enabled / Disabled
Option 2: Serial Connection / Keybus Connection
[10] LINKS2450 Account Code
[20] Maintenance Alarms and Restoral Reporting Codes
[30] Call Direction Options
[81] Miscellaneous Alarm Reporting Codes (PC1575/1580 panel only)
[82] Miscellaneous Restoral Reporting Codes (PC1575/1580 panel only)
4.
To exit Installer’s Programming, press [#].
3.2 Programming a LINKS2450 for Use with a PC4010/PC4020 v3.0
or higher panel.
There are two stages in programming the LINKS2450 for a PC4010 or PC4020 panel:
1. Program the LINKS2450 programming sections from a PC2550RK keypad
connected directly to the LINKS2450.
2. Program the LINKS2450 toggle options on the PC4010/4020 control panel.
Program the LINKS2450 from a PC2550RK Keypad:
1. Make sure the LINKS2450 is connected to a PC2550RK keypad (refer to
diagram 3-1). Make sure that jumper J3 is shorted.
2. Program the following sections only. Other programming sections are not
relevant to PC4010/4020 panels. See section 4 for a detailed description of
these sections.
Enter the two-digit number for each section you want to program, then, enter the
data required to complete the section programming. If you enter information into
a section and make a mistake, press [#] to exit the section. Select the section
again, and re-enter the information correctly.
Record your programming choices in the worksheets at the end of this manual.
[01] Module Configuration
Option 1: Communications Enabled / Disabled. Press [1] to alternately
enable or disable the option.
Program the LINKS2450 Toggle Options on the Panel
At a PC4010 or PC4020 system keypad, enter reference # [000405] and [*], or scroll
to the “LINKS2XXX” programming section. (See the “How to Program” section in your
PC4010/4020 Installation Manual for more information.) Use the arrow keys (< >) to
scroll to each of the following toggle options. Press [*] to toggle the option ON or OFF.
Record your programming choices in the worksheets at the end of this manual.
LINKS 2XXX
[20] Maintenance Alarms and Restoral Reporting Codes. Enter two hexadecimal digits for each code.
3. When you have finished programming the above sections, disconnect the
power and the PC2550RK keypad.
4. Connect the LINKS2450 to the panel as in diagram 2-2.
When enabled the PC4010 or PC4020 will send the events
that are programmed to the LINKS 2450. The PC4010/
4020 will only send the events that have reporting codes
programmed and dialer directions enabled for them.
No
The PC4020 will not send events to the LINKS2450.
Default condition is No.
NOTE: The Communications Toggle option “Comms Enabled” must also be set to
Yes for the PC4010/4020 to be able to send events to the LINKS 2XXX.
To disable the PC4010/4020 telephone communications, but still allow the PC4010/
4020 to communicate events through the LINKS 2XXX, set “Comms Enabled” to
Yes, and the Dialer Directions to No for all 3 telephone numbers. Leaving all 3
telephone numbers unprogrammed will also disable telephone communications.
See the “Communications Programming” section in your PC4010/4020 Installation
Manual for more information.
Alarm/Restore Yes
Alarm and Restoral reporting codes are sent to the central
station by the LINKS2450.
No
Alarm and Restoral reporting codes are not sent to the
LINKS2450.
Yes
Opening and Closing reporting codes are sent to the
central station by the LINKS2450.
No
Opening and Closing reporting codes are not sent to the
LINKS2450
Yes
All other reporting codes are sent to the central station by
the LINKS2450.
No
All other reporting codes are not sent to the LINKS2450
Option 2: Serial Connection (Enabled) / Keybus Connection (Disabled).
Press [2] to alternately enable or disable the option.
[10] LINKS2450 Account Code. Enter 2 two-digit hexadecimal numbers.
Refer to your Installation manual for information on Hexadecimal
programming.
Yes
Default: No (Yes on PC4010CF/4020CF panels)
Open/Close
Default: No (Yes on PC4010CF/4020CF panels)
All others
Diagram 3-1
Connecting the LINKS2450 to a
PC2550RK Keypad
Default: No (Yes on PC4010CF/4020CF panels)
To exit the LINKS2XXX programming section, press [#].
Program Panel Supervision for the LINKS2450
Panel supervision of the LINKS2450 is recommended when connected to PC4010/
4020 panels. To have the panel supervise the LINKS2450, make sure the zone that
the LINKS2450 is connected to on the panel is programmed for LINKS Supervisory
(zone type [28]). When the zone is programmed this way, if the YEL terminal is not
grounded (e.g. the wire is cut), the panel will generate a zone trouble and a LINKS
trouble and will send the reporting code for the zone.
See your PC4010/4020 Installation Manual for information on zone programming.
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd.
could void your authority to use this equipment.
This equipment generates and uses radio frequency energy and if not installed and used properly,
in strict accordance with the manufacturer’s instructions, may cause interference to radio and
television reception. It has been type tested and found to comply with the limits for Class B device
in accordance with the specifications in Subpart “B” of Part 15 of FCC Rules, which are designed
to provide reasonable protection against such interference in any residential installation.
However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause interference to television or radio reception, which can be determined
by turning the equipment off and on, the user is encouraged to try to correct the interference by
one or more of the following measures:
• Re-orient the receiving antenna
• Relocate the alarm control with respect to the receiver
• Move the alarm control away from the receiver
• Connect the alarm control into a different outlet so that alarm control and receiver are on
different circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for
additional suggestions. The user may find the following booklet prepared by the FCC helpful:
“How to Identify and Resolve Radio/Television Interference Problems”. This booklet is available
from the U.S. Government Printing Office, Washington, D.C. 20402, Stock # 004-000-00345-4.
Notice to the user:
It is the responsibility of the modem user to ensure that the modem / radio
terminal combination has been aligned by qualified personnel before the
equipment is used. Written proof, with the name of the technician and
address of the service depot, should be available on request for inspection
by representatives / radio inspectors of Industry Canada.

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No