Tyco Safety Canada 06GS30552 Cellular Alarm Communicator User Manual 29007314R001 GS3055 IM EN P65

Digital Security Controls Ltd. Cellular Alarm Communicator 29007314R001 GS3055 IM EN P65

User manual

GSM-GPRS  INTERFACE
2 GS3055-IINTRODUCTION ....................................................................................................................3FEATURES ............................................................................................................................ 3Technical Specifications ....................................................................................................... 3Description ............................................................................................................................ 4IDENTIFICATION OF PARTS ............................................................................................... 4INSTALLING THE DEVICE ................................................................................................... 4CONNECTING THE DEVICE ................................................................................................ 4STATUS  LEDS ....................................................................................................................... 5OPERATING  PRINCIPLES ................................................................................................... 5Simulated Land Line .............................................................................................................5SMS Function ........................................................................................................................ 6ContactID Mode .................................................................................................................... 6Function Priority ..................................................................................................................... 6Simulated Land Line Priority ....................................................................................... 6SMS or Contact ID Priority ........................................................................................... 6ContactID Event Priority .............................................................................................. 6ACTIVATING THE OUTPUTS ................................................................................................ 7Activating/Deactivating Automatic Outputs ......................................................................... 7Activating/Deactivating Remote-control Outputs ................................................................ 7Bistable Outputs (for appliance management) ........................................................ 7Monostable Outputs (for appliance management) .................................................. 7PROGRAMMING THE SIM CARD VIA PC ........................................................................... 8Viewing the Device Settings ...................................................................................... 8Downloading the Device Settings ............................................................................. 8Preliminary operations ................................................................................................ 8Telephone Page .................................................................................................................... 8Telephone Numbers .................................................................................................... 8Prefix ............................................................................................................................ 9Digit to Remove ........................................................................................................... 9SMS Dialler Page ................................................................................................................... 9Main window ............................................................................................................... 9Priority ....................................................................................................................... 10Pay-as-you-go balance message ........................................................................... 10Periodic message .................................................................................................... 10Outputs Page ...................................................................................................................... 10Output Settings ........................................................................................................ 10Access Code ........................................................................................................... 10Contact ID Page .................................................................................................................. 10Telephone numbers to call ....................................................................................... 11Events description ..................................................................................................... 11Send over GPRS ........................................................................................................ 11Periodic Reports ........................................................................................................ 11GPRS page .......................................................................................................................... 11Access Point Name ................................................................................................... 11Receiver IP address and Port ................................................................................... 11APNs User Name and Password ............................................................................... 11Telephone numbers to decode ................................................................................ 11SIM number ............................................................................................................... 11DNIS ........................................................................................................................... 11Account code ........................................................................................................... 11Calls Page ............................................................................................................................ 11Load button ............................................................................................................... 12Received Calls .......................................................................................................... 12Missed Calls ............................................................................................................... 12Dialled Calls ............................................................................................................... 12Status Page ......................................................................................................................... 12Status section ............................................................................................................ 12Inputs section ............................................................................................................ 12Outputs section ......................................................................................................... 12Events section ........................................................................................................... 12Clear call queue ........................................................................................................ 12"C-24 REMOTE" PROGRAMMING ..................................................................................... 1 3INFORMATION FOR THE USER ......................................................................................... 13Remote Programming of the Access Code ....................................................................... 13GSM Network Calls .............................................................................................................. 13Further Information .............................................................................................................. 13APPENDIX .......................................................................................................................... 14
3INTRODUCTION,,,,,This manual provides programming and operating instructions for the GS3055-I wireless alarmcommunicators. Information relating to a specific model will be denoted by the applicable model numberwithin the text. The term "Device" is used to describe functionality that is applicable to both models. Thismanual shall be used in conjunction with the installation manual of the control panel and power supply itis connected to.FEATURESSimulates land lineSwitches automatically to GSM Network in the event land line trouble (line down)Manages and signals Incoming/Outgoing callsGSM signal indicator4 programmable OC OutputsHouses 12V - 1.2 Ah battery (not included)Tamper protectionLand line overvoltage protection (optional)Dual-Band4 Input LinesSMS AlertsContact ID Dialer throughoutDecoding Contact ID protocol from a PSTN interface for communication over the GPRS networkGPRS/Internet communication with Sur-Gard System III / II13 SMS Messages (2 messages per Input Line and 5 Status messages)8  phone numbers (max. 20 digits) programmable for SMS Dialler4  phone numbers programmable for Contact ID DiallerUp to 95 phone numbers (max. 20 digits) can be programmed to manage remote control of the OC OutputsRemote control of the OC Outputs via SMS and/or over-the-phone after caller recognitionPay-As-You-Go Balance message (for pre-paid SIM Cards)Technical SpecificationsThe 13.8 V_ (700 mA max.) power supply voltage to this Device can be drawn from the Control panel or provided by aADP1512 AC/DC adapter (accessory item) or provided by the PS4085 power supply.Description ValuePower Supply voltage 13.8 V_Standby Current Draw 100 mATransmitting Current Draw 700 mAMaximum loop resistance of line between the series deviceand the CPE connected to the device 1 KohmMaximum number of parallel CPE devices 2Operating Temperature +0° to +49° C32 to 120 °FDimensions 138 x 224 x 55 mm5.4 x 8.8 x 2.2 inchWeight (without battery) 900 g3.2 oz.
4 GS3055-IDescriptionThis Device provides total confidence in all security and surveillance applications. It manages SMS  and Central Stationtransmissions and can simulate the land line in the event of trouble (land line down) or even substitute the land line completelyin areas where the GSM service is provided and where the land line is not available.This Device supports CONTACTID, 10 bps and 20 bps protocols and, in places with optimum GSM signal reception, SIA andCESA protocols.The GS3055-I has the added capability of communicating alarm signals via the GPRS data network. The capability enablesa fast reliable path to central stations equipped with a Sur-Gard System III, System II receiver, or with the PC based WinBCSsoftware (version 2.0 or higher).By connecting a GS3055-I to a control panel's standard PSTN interface, telephone based Contact ID signals are decoded andseamlessly routed through the GPRS network to any of the compatible receiver options.The performance of this Device depends greatly on GSM Network coverage, therefore, it should not be mounted without firstperforming placement tests to determine the best location (best reception). This Device has 4 Input lines which can be used toactivate SMS and/or Contact ID transmissions (Trouble alert, Periodic messages or Pay-As-You-Go Balance (for pre-paid SIMCards).This Device has 4 Outputs which can be set up from remote locations or used for status signalling.Due to the characteristics of GSM Networks, this Device can activate only as intended and cannot be used as a modem forfax/data transmissions or for teleservice operations.IDENTIFICATION OF PARTSThe numbers in square brackets [  ] in this manual refer to the main parts of the GS3055-I (see Fig. 1) described in this section.INSTALLING THE  DEVICEThis device shall be installed by qualified SERVICE PERSONS only. This device must be installed indoors in a non-hazardous location. This Device should be located in a dry place away from radio transmitters and similar devices.,,,,,Test the GSM Network reception before mounting this Device in the proposed placement.1. Remove the 4 screws and the metal casing [1].2. Using the back box, mark the 4 screw locations then drill the anchor screw holes.Check for cable conduits and water pipes before drilling.3.  Using anchor screws (not included), mount the back box to the wall.4. Lay the cables, then pull them through the cable entry [14].5. Fit the antenna [2] (ensure that the bolt [3] is fastened tightly).6. Using the connector [5], connect the GSM Module [17].7. Following the arrow on the board, insert the SIM-CARD [6] face down in the SIM holder (see Figure 1).The SIM-CARD PIN must be disabled.8. Complete the connections on the terminal board [12].9. Using the 4 scews and washers, reattach the frontplate [1] securely to the back box.,,,,,   Connect power and TNV circuit only after the cabinet has been secured to the building or structure and hasbeen connected to the protective earth ground.CONNECTING THE DEVICEThis section describes the various terminals. Fig. 2 shows a typical wiring diagram.(1) Earth: This terminal must be connected to the Mains Earth, in order to comply with the Telecommunications NetworkSafety Standards (Overvoltage Protection Requirements).LE (2-3) External telephone line: These terminals can be connected to the land line.LI (4-5) Internal telephone line: These terminals (normally connected to the land line) must be connected to the telephonedevice terminals (for example, terminals L.E.).(6-14) Negative: Power Supply.
5Ox (7-8-9-10) Programmable Open-Collector Outputs: These outputs can be activated either by programmed events(Automatic Mode) or by SMS text messages (Remote Mode), refer to “Activating the Outputs” for details. The maximumcurrent draw of each OC Output must not exceed 70 mA+OC(2-3) Common terminal for Open-Collector Outputs: Common power-supply terminal (12 Vcc-450mA) for all OCOutputs (O1, O2, O3, O4).AS (12-13) Tamper: These terminals are connected in series to the Tamper microswitch [11]. They will be closed when theDevice is properly closed, and will open when the frontplate is removed.Lx (15-16-17-18) Programmable Input line: These terminals can be set up to activate the SMS and Contact ID transmissionfunctions.12V(19-20) Device power supply: These terminals must be connected to a 13.8 V_ power supply, 700 mA minimum —under normal circumtances drawn from a Control panel or ADP1512 Adaptor (accessory item). If the Device powersupply is drawn from a Control panel, ensure that the maximum current draw (700 mA) is protected by aresettable fuse or similar device.Once the connections have been completed, connect the Red and Black wires [13] to a 12V-1, 2Ah battery.,,,,,To ensure proper operation of this Device, the connection of a backup battery is needed to providetemporary additional current during normal operation (see Fig. 2),,,,,This Device must be connected to a 13.8 V power supply and to a backup battery. This device must beconnected to a proper Earth Ground (see Fig. 2).,,,,,When disposing of batteries, follow the instructions and and precautions printed on the batteries, andcontact your municipal offices for information on the disposal of used batteries.STATUS LEDSThe Device Interface has 4 status LEDs.,,,,,All 4 LEDs will blink during the Initializing and Programming phases.The following section describes the Control panel status LEDs.GREEN —  If this LED is OFF and the RED LED is ON, the GSM Network service is unavailable (NO SERVICE).This LED will Blink when the GSM Network reception is bad, if this occurs, only SMS transmissions will be possible.If this LED is ON (glowing), the GS3050-I and GS3055-I Interface will be able to manage all telephone communications.GREEN —  When this LED is ON (glowing), the reception is good. This LED will switch ON only when the other GREENLED is ON (glowing).AMBER — This LED will switch ON (glowing) when the interface switches to the GSM Network (due to land line trouble).This LED will Blink in the event of an incoming or outgoing call (regardless of the operating status of the land line).RED — This LED is Normally OFF, it will blink in the event of power trouble. This LED will switch ON (glowing) in theevent of GSM Module [17] trouble, or when the GSM Network is unavailable (NO SERVICE), or when RemoteProgramming option is enabled. If this LED switches ON (glowing), and the two Green LEDs indicate the availability ofthe GSM Network service, ONLY Emergency calls will be possible.OPERATING PRINCIPLESSimulated Land LineThe Simulated land line provides traditional telephone devices with a backup line in the event of land line trouble (line down). Thisoperating mode will allow calls and data transmissions to be carried on the land line. If the voltage on the land line terminals (LE)drops below 3 V for a period of between 10 to 45 seconds (depending on the device connected to the LI terminals), the Devicewill switch the connected telephone device to the GSM Network for a full 15 minute interval, at the end of this interval, it willcheck the land line:— if the land line has been restored, it will switch the connected telehone device back to the land line;— if the land line is still down, it will continue to simulate the land line until remove it is fully restored.
6 GS3055-IThis Device will not switch during ongoing calls. The simulated line will provide the line ring voltage for incoming calls andwill decode DTMF dialling (this Device is unable to decode Pulse dialling).The Function Priority (to be selected during the programming phase) will determine how this Device manages communications(SMS and ContactID) and calls from the telephone device connected to the LI terminals (e.g. Control panel).SMS functionThis operating mode allows this Device to send text messages to 8 telephone numbers. The messages can be associatedwith the following events:Alarm signals on the 4 Programmable Input lines: 2 preset messages — Alarm and End of Alarm.Land Line Test:  2 preset messages — Line down and Line restored.Power supply Test: 2 preset messages — Trouble and Trouble clearPeriodic message: 1 message to be sent at regular intervals (accepted values 1 through 999999 minutes).,,,,,The SMS messages will be sent to the programmed numbers when the respective events occur.ContactID ModeThis operating mode will allow this Device to send calls to the Central Station:Alarm signals on the 4 Programmable Input lines: require Event Codes and Customer CodesStatus signal, with a Customer CodeLand Line Test:Power supply Test:Call queue fullPeriodic report (to be sent at regular intervals — accepted values 1 through 999999 minutes).,,,,,The Contact ID reports will be sent when the respective events occur.Function PrioritySimulated Land Line PriorityIf the equipment connected to the LI terminals (e.g. Control panel) tries to engage the line, this Device will interrupt anyongoing communications (SMS or ContactID) in order to send the calls generated by the device. This Device will restart theinterrupted communications when the equipment disengages the line.SMS or Contact ID PriorityIf the equipment connected to the LI terminals (e.g. Control panel) is using the GSM Network (through this Device) when anSMS or ContactID associated event occurs, this Device will interrupt the ongoing call and send the respective SMS messageor ContactID report.ContactID Event PriorityIf several events occur contemporarily, the respective messages will be sent in chronological order. If an event is associatedwith a ContactID report and an SMS communication, priority will be given to the ContactID report.
7ACTIVATING THE  OUTPUTSThis Device has 4 OC outputs programmable as Automatic (outputs with this attribute will activate in response to theassociated events) or Remote Control (outputs with this attribute can be activated manually from remote locations bymeans of SMS messages or calls from enabled telephone numbers.Activating/Deactivating Automatic OutputsThe OC outputs can be activated automatically by the following events:Land line trouble (line down)GSM Module troubleGSM trouble (Limited/No Service)Power supply troubleIncoming callOutgoing callContactID digital reportEnablement of remote programming,,,,,Once an OC output has been activated automatically, it will not restore to standby until all the causes ofactivation clear.Activating/Deactivating Remote-control OutputsThe OC outputs can be programmed as BISTABLE (activated/deactivated by means of an SMS text message or RemoteControl number) or MONOSTABLE (activated by means of SMS  text messages or Remote Control numbers). Oncea Monostable output has been activated, it will not deactivate until the programmed ON Time expires. Each output can beset up to provide a feedback signal (ring or SMS text message).,,,,,For further information regarding the terms “Access Code” and “Output Label” (used in the followingsection), refer to the “Outputs Page” in the “Software” section.Bistable Outputs (for appliance management)Bistable OC outputs can be activated in 2 ways.1. By sending a case sensitive SMS text message containing the respective Access Code, placed between pound signs(#), and the Output Label (e.g. GATE) followed by =ON, as follows:#ACCESSCODE#OUTPUTLABEL=ON   (example: #AZ55#GATE=ON)2. By sending a cost-free call from a preset Remote Control number. This Device will activate the respective outputwithout answering the call.,,,,,Bistable OC outputs can be deactivated by sending a case sensitive SMS text message containing the respectiveAccess Code placed between pound (#) signs and Output Label (e.g. GATE) followed by =OFF, as follows:#ACCESSCODE#OUTPUTLABEL=OFF   (example: #AZ55#GATE=OFF)The SIM-CARD can be programmed via PC, using the GS3050 Software Application or via any GSM Cellphone or in "C-24Monostable Outputs (for appliance management)Monostable OC outputs can be activated in 2 ways.1. By sending a case sensitive SMS text message containing the respective Access Code placed between pound (#) signsand Output Label followed by “=ON” or “=OFF”, as follows:#ACCESSCODE#OUTPUTLABEL=ON#ACCESSCODE#OUTPUTLABEL=OFF2. By sending a cost-free call from a preset  Remote Control number. This Device will activate the output concernedwithout answering the call.,,,,,Monostable OC outputs deactivate (switch OFF) automatically when the programmed ON Time expiresProgramming the Device,,,,,If this Device is to manage all the SMS functions, use a 32 K SIM CARD (or higher) which holds at least 20text messages.
8 GS3055-IThe SIM-CARD can be programmed via PC, using any GSM cellphone or in “C-24 Remote” mode, with pre-authorized service.NOTE: The manufacturer shall not assume responsibility for damage arising from improper programming viaGSM Cellphone. Fig. 3 - Null-Modem cable connection for programming via PCPROGRAMMING THE SIM CARD VIA PCThis section contains the programming instructions using the GS3055 Software Application. This programming  methodrequires the connection of a Null-Modem cable (see Fig. 3) to the RS232 input [10] of this Device and the computer COM port.Once the Null-Modem cable has been connected, set the computer COM port through the Settings->Serial Port option fromthe Menu.Viewing the Device SettingsTo view the Device settings on the screen, use the Programming->Load option from the Menu.Downloading the Device SettingsOnce programming has been completed (or an uploaded file containing existing data has been modified), download the datainto this Device, using the Programming->Download option from the Menu.Preliminary operationsWhen the application starts, you will be presented with the Main window showing two sections on the left hand side.zFolders: This section will allow you to click on the various Programming and Control Pages.zCustomers: This section will allow you to delete or retrieve configuration data, as follows:1. Using the right button on the mouse, click on the Customer’s name.2. Click  Load to upload the respective data from the Hard-Disk, or Delete to delete the data configuration.You can load the configuration data by double clicking the respective name field.You can list Customers in alphabetical or code order by clicking the heading of the column concerned.,,,,,To start the configuration of a new Customer, click on File->New Customer then select the device (GS3055-I) from theproduct list in the successive window.The configuration data is presented on 4 pages, a further 2 pages (Calls and Status) are for “Supervisory and Control”purposes. All the pages are described in detail in this section.Telephone PageThe Telephone Page phonebook holds 95 telephone numbers.,,,,,The first eight numbers in the phonebook will also be used for the SMS functions.Telephone NumbersDescription: enter an alphanumeric string of up to 20 characters.Number: enter a telephone number of up to 20 digits (only digits and “+” signs are accepted).Remote Control Numbers: select the telephone numbers which will be able to control Outputs 1, 2, 3 and 4 over thephone. The  telephone numbers cannot be selected in open order, therefore, if telephone numbers 1 and 6 are selected,telephone numbers 2, 3, 4 and 5 will be selected automatically.5 54 49 98 87 76 63 32 21 1DB9 female connector7 wire shielded cableDB9 female connectorto PCto this Device
9Dial.: This memorandum column shows the SMS Dialler telephone numbers (selected on the SMS Dialler Page fromthe first 8 telephone numbers in the phonebook).PrefixIMPORTANT: This Device will prefix the digits entered in this field to all the telephone numbers dialled through the GSMInterface function.If necessary enter a Prefix (maximum 4 digits) in this field. If no Prefix is required, leave this field empty.Digit to RemoveIf this Device is connected downstream to a switchboard, the telephone numbers (programmed on the Control panel) mustbe preceded by the switchboard number (normally one digit). As the switchboard number is not required when calls are sentover the GSM Network, it must be removed from the digits which form the telephone number. Enter the number of digits thatform the switchboard number (e.g. if switchboard number is 01, enter 2 in the ‘Digits to remove’ field, as 2 numbers form theswitchboard number).SMS Dialler PageThis page will allow you to program the SMS Dialler functions and Messages and also set up the ‘Special Functions’ of the3 Input lines.,,,,,The configuration data on on this page concerns the first eight telephone numbers entered on the “Telephone”page.Main windowThe column on the left-hand side of the Main window shows the events which, if duly programmed, will generate two SMStext messages: one for activation and the other for restoral (the ‘Periodic SMS text message can generate the activationmessage only).Polarity: (this column shows the events which unbalance the 4 Input lines), select the Standby polarity of the Inputs—  H-Normally Open or L-Normally Closed.Telephone Numbers:  click (tick) the check boxes of the numbers to be called when the respective event occurs.SMS: write the Activation and/or Restoral message to be sent when the respective event occurs (maximum 100characters). If no message is required, leave the respective box empty.Serv: If this option is enabled, unbalance (on Input Lines 1, 2 and 3) will generate actions instead of calls. Two actionscan be set up for each Input Line, as per the following table.Input line no. Select Special Functions1AEnable/Disable Periodic MessageIf this option is selected — and Input Line 1 is held in a permanent state of Unbalancet his device willsend the Periodic Message at regular intervals (in accordance with the values in thePeriodic Message section). If Input Line 1 restores to standby status (Input Line 1 balance this device will notsend the Periodic MessageBSend Periodic Message nowIf this option is selected this device will send the Periodic Message immediately and start the  intervalbetween messages2AClear Call QueueBRestore Reserved Outputs to Standby3ASwitch to GSMBAlternative Dialling
10  GS3055-IPriorityThis section will allow you to select the operating priority of this Device: Interface (at default) or SMS Dialler/Contact IDCommunicator.Pay-as-you-go Balance message,,,,,NOTE: The Manufacturer shall not assume responsibility for Pay-as-you-go credit services managed byGSM Network Providers.If you enable this option, an SMS text message — containing information provided by the GSM Network regarding the end-user’scredit balance — will be sent to the first number in the Telephone Number list. Enter the number of telephone calls(ContactID reports and/or outgoing SMS text messages) this Device must allow before checking the Pay-as-you-go balance.Pay-As-You-Go Balance message - If you click on this button the application will open a window showing the remaining creditbalance (if this service is managed by your network provider), or a message indicating that this service is not available.The default string in the 'Pay-As-You-Go Balance message' field (*123#) is supported by most major service providers.Periodic messageThis section will allow you to set up the Periodic message options.Date of first Periodic message - Select the Date of the first Periodic message.Time of the first Periodic message - Select the Time of the first Periodic message.Interval  - Enter the interval (DD-HH-MM) between each Periodic message. Accepted DAY values: 0 to 693.,,,,,ATTENTION: If Input Line 1 is assigned to Special functions (Column A), transmission of the Periodicmessage will be subordinate  to ‘Unbalance’ on Input Line 1 (refer to the ‘Special functions’ table). If thisoccurs, the Date and Hour of the Periodic message will be irrelevant.Outputs PageThis page will allow you to set up and control the outputs.Output SettingsPolarity: select the polarity of the output: H-Normally Open L-Normally Closed.For Land Line Trouble, GSM Trouble, etc.: select the events that will activate the outputs.Reserved Output: If this option is selected, all other events assigned to the output in this section will be ignored. Selectthis option, if the output concerned is to be used for Remote control purposes (refer to “Activating and Deactivating andRemote Control Outputs”).The following options will affect Reserved Outputs ONLY.Output Label - Type in the label (max. 8 characters) of the appliance (e.g. Gate) which is to be remote-controlledvia SMS.Output feedback - Select the type of feedback signal (None, Ring or SMS) to be sent when the respective outputactivates. If the Output Label field is empty, the SMS option will not be available.Monostab. - Under normal circumstances, these outputs hold active status until they receive a deactivationcommand. If automatic deactivation is required, it will be necessary to program the ON  Time (i.e. the time the outputwill hold active status).ON Time (sec.) - Enter the required ON Time in seconds (accepted values 2 to 254 seconds). If the output has beenprogrammed as Monostable, this value will determine the amount of time the output will hold active status beforerestoring to standby.Access CodeType in the code (maximum 4 alphanumeric characters) which will allow the user to control the outputs over-the-phone.Contact ID PageThis page will allow you to set up the Contact ID function.
11Telephone numbers to callFour telephone numbers of up to 20 digits (digits and + signs).This Device will try each telephone number 3 times before considering a call unsuccessful and quitting.,,,,,The Contact ID Codes will be sent to the first number (with Contact ID reporting protocol) that answers thecall.Events descriptionCustomer Code - type in a 4 character code (accepted values: digits and the letters  A, B, C, D, E and F).Event Code - type in the Contact ID to be transmitted when the respective event occurs.Send - select (tick) the events to be sent.Send over GPRSIf this option is enabled, the GS3055-I will only communicate Contact ID events via the GPRS network.Periodic ReportsThis Device can be programmed to send Periodic Contact ID reports. This section will allow you to select the Date and Timeof the first periodic report and the Interval between reports.GPRS PageThis page outlines the GPRS configuration options.Access Point NameEnter the Access Point Name of the GPRS service provider being used. (example: ibox.tim.it) Please contact the GPRSservice provider for this information.Receiver IP address and PortEnter the receiver IP address and the port number. Use the same as IP address and Port that is found in the 'Receiver RemotePort' section of the WinBCS software or Sur-Gard SYSTEM III and SYSTEM II.APNs User Name and PasswordSome providers may require a user name and password to validate communication. If needed, enter this information here.Telephone numbers to decodeIn this section you may enter up to two telephone numbers dialed by the panel that will be recognized by the GS3055-I whencalled to trigger GPRS communication. If a number is programmed, any time a number dialed does not match one of thephone number entered, the call will be routed through the voice channel. Leaving it blank will route all calls to GPRS.SIM numberEnter the GPRS SIM number (optional)DNISIf required, enter the Dialled Number Identification Service number.Account codeAn account code is required for communication with WinBCS, Sur-Gard SYSTEM III or SYSTEM II receivers. Enter theAccount Code in this field.Calls PageThis page will allow you to view on the screen the Dialled, Received and Missed calls.,,,,,Each section can store a maximum of 10 calls. If the number of calls exceeds this limit, this Device will makespace automatically by deleting the oldest calls.
12  GS3055-ILoad buttonTo view the Dialled, Received and Missed calls, click the Load button. Depending on programming, some telephonenumbers may not have Caller ID.Received CallsIf this Device is connected to a Control panel or another telephone device, this section will allow you to view the callsreceived by this Device.Missed CallsThis section will allow you to view any unanswered incoming calls.Dialled CallsThis section will allow you to view any calls dialled by this Device whether in Contact ID Communicator mode and/or GSMInterface mode.Status PageThis page will allow you to monitor and control in real-time all the Device functions and, if not previously done, unblock theSIM CARD PIN.,,,,,ATTENTION: This page is updated every 5 seconds.Status sectionThis section shows the GSM Module data. This virtual display shows the GSM Network Provider, the Device battery charge(for the precise level, position the mouse arrow on the battery icon for a several seconds) and GSM signal reception(indicated by 10 bars).The virtual Comunication LED is usually GREEN. It will turn RED in the event of a breakdown in communication betweenthe software and this Device. If it turns AMBER, this Device is either reading the SIM CARD or receiving/making a telephonecall, under these circumstances the status update will be suspended temporarily.Inputs sectionThis section shows the status of each of the 4 Inputs (GREEN LED = Input balanced; RED LED = Input Unbalanced) and anySpecial functions associated with the Inputs.Outputs sectionThis section shows the status of each of the 4 Outputs  (GREEN LED = Output in standby; RED LED = Output activated). Ifany of the Outputs has been set up as “Reserved” (refer to “Outputs page”),  RED LED On, it will be possible to activate/deactivate the Outputs in real-time by right-clicking the respective Polarity option and selecting the Activate/Deactivate sub-option.Events sectionThis section shows the events as they occur (RED LED On).Send next periodic message onThis section shows the Date and Time of the next periodic SMS text message (refer to the SMS dialler page).Send next periodic report onThis section shows the Date and Time of the next periodic Contact ID report  (refer to the Contact ID Communicator page).Clear call queueThis button will allow you to interrupt any ongoing calls and stop the outgoing call queue.,,,,,This option is available ONLY when this Device operates in SMS Dialler/Contact ID Communicator mode.
13"C-24 REMOTE" PROGRAMMINGThe GS3055-I can be remotely programmed via SMS by Connect-24 (C-24) for fast convenient installation without the needof an on-site PC or manual programming of the SIM card.INFORMATION FOR THE USERRemote Programming of the Access CodeTo change the Acess Code, use the following SMS text message:#uuuu#*#nnnn#where:uuuu represents the old Access Code, and nnnn represents the new Access Code.,,,,,The default Access Code is 0001.GSM Network CallsIf this Device is connected to a telephone, it will be possible to make calls on the GSM Network.Further InformationRefer to the following sections for further information:STATUS LEDsOPERATING PRINCIPLESACTIVATING THE OUTPUTS“Remote Programming” in the “PROGRAMMING VIA PC section”
14 GS3055   Fig. 2 - Wiring Diagram541PanelTelephone device23678910 11 14 15 16 17 18 19 20LELI O1O2 O3 O4+OC1312ASL1 L2 L3 L412VTo Tamper Line13.8 V A_700 mFire Panel / Security Panelo1K5BATTERYNO NCCOM+BThis Connection is necessaryO1RelayTIPTIPRINGRINGPGMPGMRJ45APPENDIX
1515196LE LI-O1MO2 O3 O4+OCASML1 L2 L3 L4 +12V-LOCKOPEN44518 3261710118121413161549N. Parts1Metal Casing2G S M  A ntenna3G S M  A ntenna nuts4Anchor Screw holes (Ø 3 mm)5Conne ctor  for G S M  A ntenna6SIM CARD7LE Ds8Reserved Jum per9Reserved Jum per (Jum per m ust be connected as per Fig. 1)10 RS -232 Conne cto r11 F ro n tp la te  Ta m p e r S w itc h12 Term inal B oard13 B a tte ry  C o n n e c to r14 Cable entry15 Earth Cable16 12V-1.2Ah B attery17 GSM Module18 SIM holder   Fig. 1 - Parts
FCC COMPLIANCE STATEMENTCAUTION: Changes or modifications not expressly approved by Digital Security Controls could void yourauthority to use this equipment. This equipment generates and uses radio frequency energy and if notinstalled and used properly, in strict accordance with the manufacturer's instructions, may cause interferenceto radio and television reception. It has been type tested and found to comply with the limits for Class Bdevice in accordance with the specifications in Subpart "B" of Part 15 of FCC Rules, which are designed toprovide reasonable protection against such interference in any residential installation. However, there isno guarantee that interference will not occur in a particular installation. If this equipment does causeinterference to television or radio reception, which can be determined by turning the equipment off andon, the user is encouraged to try to correct the interference by one or more of the following measures:• Re-orient the receiving antenna• Relocate the alarm control with respect to the receiver• Move the alarm control away from the receiver• Connect the alarm control into a different outlet so that alarm control and receiver are on differentcircuits.If necessary, the user should consult the dealer or an experienced radio/television technician for additionalsuggestions. The user may find the following booklet prepared by the FCC helpful: "How to Identify andResolve Radio/Television Interference Problems". This booklet is available from the U.S. GovernmentPrinting Office, Washington, D.C. 20402, Stock # 004-000-00345-4.WARNING: To satisfy FCC RF exposure requirements for mobile transmitting devices, aseparation distance of 20 cm or more must be maintained between the antenna of this deviceand persons during device operation.Industry Canada Compliance StatementThis Class B digital apparatus meets all requirements of the Canadian interference-causing equipmentregulations. Cet appareil numérique de la Classe B respecte toutes les exigences de règlement sur lematériel brouilleur du Canada.The term “IC:” before the radio certification number only signifies that Industry Canada technicalspecifications were met.  This manual is applicable to the following GS3055-I Cellular AlarmCommunicator Models:GS3055-1  FCC ID: F5306GS30551 and IC: 160A-GS30551GS3055-2  FCC ID: F5306GS30552 and IC: 160A-GS30552© 2006 Digital Security ControlsToronto, Canada1-800-387-3630 • www.dsc.comPrinted in Canada29007314R002