MX4428
MXP ENGINEERING / TECHNICAL MANUAL
MX4428 PRODUCT MANUAL
VOLUME 11
Document Number: LT0273

Issue 1.5; 24 March 2006

- APPROVALS AUSTRALIAN STANDARD AS4428.1
- SSL Listing Number ....................................................................................... afp1446
NEW ZEALAND STANDARD NZS4512-1997 (INCL AMDT 1 & 2)
- FPA (NZ) Listing number ................................................................................. VF/117
AS/NZS 3548 1995 CLASS A

The 4100MXP is a product of
Tyco Safety Products
211 Maces Road
Christchurch 8030
NEW ZEALAND
Phone +64-3-389 5096
Fax +64-3-389 5938

COPYRIGHT (C) 2003,2004
Information contained in this document is subject to copyright, and shall not be reproduced in any
form whatsoever, without the written consent of Tyco Services Fire & Safety.
Information contained in this document is believed to be accurate and reliable, however Tyco
Services Fire & Safety reserves the right to change the content without prior notice.

MX4428 MXP Engineering /Technical Manual

Document: LT0273

NON-DISCLOSURE AGREEMENT
Tyco (THE COMPANY) and the User of this/these document(s) desire to share proprietary technical information
concerning electronic systems.
For this reason the company is disclosing to the User information in the form of this/these document(s). In as
much as the company considers this information to be proprietary and desires that it be maintained in confidence,
it is hereby agreed by the User that such information shall be maintained in confidence by the User for a period of
TEN YEARS after the issue date and only be used for the purpose for which it was supplied.
During this period, the User shall not divulge such information to any third party without the prior written consent
of the company and shall take reasonable efforts to prevent any unauthorised disclosure by its employees.
However, the User shall not be required to keep such information in confidence if it was in their possession prior
to its receipt from the company; if it is or becomes public knowledge without the fault of the User; or the
information becomes available on an unrestricted basis from a third party having a legal right to disclose such
information.
The User's receipt and retention of this information constitutes acceptance of these terms.
This information is copyright and shall not be reproduced in any form whatsoever.

END USER LIABILITY DISCLAIMER
The MX4428 Fire Indicator Panel provides a configuration programming facility, which may be accessed via a
programming terminal using a password. Because this programming facility allows the user to define in detail the
operation of the MX4428 System being customised, changes may be made by the user that prevent this
installation from meeting statutory requirements.
The Company, therefore cannot accept any responsibility as to the suitability of the functions generated by the
user using this programming facility.

AMENDMENT LOG
21 March 01
24 April 03

Issue 1.0
Issue 1.1

11 March 04

Issue 1.2

28 January 05

Issue 1.3

28 October 05

Issue 1.4

24 March 06

Issue 1.5

Original
Updated DIM800 Compatibility, added VLC800, LPS800, Alarm
Tests
DIM800 with s/c fault option. Added "specs", noted source of
MXPPROG, updated MXP software version history.
Added requirements for AS1670.1. Noted DIM800 supply
supervision threshold is not adjustable. Added MIM800 max cable
length on inputs to its specs. Updated Table 3-2. Added 5B,
replaced 814IB with 5BI.
Noted MkII Sounder Base has AS2220 and ISO tones. Added note
re acceptable type mismatches. Added reference to software
version 1.12.
Added 614CH, 614I, 614P, System Sensor 885WP-B detectors to
Table 3-4.
Added 614T Section 3.20.3. Added 814P Section 3.9, etc. Added
Loop Filter Board, Chapter 10.

TRADEMARKS
VESDA is a registered trademark of Vision Systems.

Page ii

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual

TABLE OF CONTENTS
NON-DISCLOSURE AGREEMENT....................................................................................................... II
END USER LIABILITY DISCLAIMER .................................................................................................... II
AMENDMENT LOG .............................................................................................................................. II
TRADEMARKS ..................................................................................................................................... II

CHAPTER 1 INTRODUCTION ...............................................................................1-1
1.1
1.2
1.2.1
1.2.2
1.3
1.4

ABOUT THIS MANUAL......................................................................................................... 1-2
ASSOCIATED DOCUMENTATION....................................................................................... 1-2
PRODUCT RELATED .................................................................................................... 1-2
STANDARD RELATED .................................................................................................. 1-3
SPECIFICATIONS ................................................................................................................. 1-3
TERMINOLOGY..................................................................................................................... 1-4

CHAPTER 2 RESPONDER LOOP DESIGN CONSIDERATIONS .........................2-1
2.1
2.2
2.2.1
2.2.2
2.2.3
2.3

MXP APPLICATION CONSIDERATIONS ............................................................................ 2-2
"LOGICAL" RESPONDERS ................................................................................................. 2-3
THEORY......................................................................................................................... 2-3
LOGICAL RESPONDERS.............................................................................................. 2-3
POINT TO CIRCUIT TO ZONE MAPPING .................................................................... 2-5
IMPLICATIONS TO SYSTEM DESIGN................................................................................. 2-6

CHAPTER 3 DEVICE INFORMATION AND PROGRAMMING..............................3-1
3.1
DEVICE TYPES ..................................................................................................................... 3-2
3.1.1
MX DEVICES.................................................................................................................. 3-2
3.2
DEVICE HANDLING CAPABILITY ....................................................................................... 3-7
3.2.1
OVERVIEW .................................................................................................................... 3-7
3.2.2
DC LOAD........................................................................................................................ 3-8
3.2.3
AC LOADING.................................................................................................................. 3-8
3.2.4
ISOLATOR BASE LOADING.......................................................................................... 3-9
3.2.5
EXAMPLE....................................................................................................................... 3-9
3.3
OUTPUT CONTROL............................................................................................................ 3-10
3.3.1
PROGRAMMING.......................................................................................................... 3-11
3.3.2
OUTPUT STATE UNDER EXCEPTIONAL CIRCUMSTANCES ................................. 3-11
3.4
DETECTOR PARAMETER SETTINGS SUMMARY........................................................... 3-12
3.5
DEVICE INSTALLATION..................................................................................................... 3-13
3.5.1
PRECAUTIONS............................................................................................................ 3-13
3.5.2
MOUNTING .................................................................................................................. 3-13
3.5.3
ADDRESS & LED BLINK PROGRAMMING ................................................................ 3-13
3.6
MX4428 PROGRAMMING................................................................................................... 3-14
3.7
814H HEAT DETECTOR ..................................................................................................... 3-15
3.7.1
GENERAL..................................................................................................................... 3-15
3.7.2
814H SPECIFICATIONS .............................................................................................. 3-15
3.7.3
MX4428 PROGRAMMING OPTIONS - 814H .............................................................. 3-15
3.8
814I IONISATION SMOKE DETECTOR ............................................................................. 3-17
3.8.1
GENERAL..................................................................................................................... 3-17
3.8.2
814I SPECIFICATIONS................................................................................................ 3-17
3.8.3
MX4428 PROGRAMMING OPTIONS - 814I................................................................ 3-17
3.9
814PH PHOTOELECTRIC SMOKE & HEAT DETECTOR & 814P PHOTOELECTRIC
SMOKE ONLY DETECTOR ............................................................................................................ 3-19
3.9.1
GENERAL..................................................................................................................... 3-19
3.9.2
814PH & 814P SPECIFICATIONS............................................................................... 3-19
3.9.3
MX4428 PROGRAMMING OPTIONS - 814PH/814P .................................................. 3-19
3.10
814CH CARBON MONOXIDE + HEAT DETECTOR.......................................................... 3-23
3.10.1
GENERAL..................................................................................................................... 3-23
3.10.2
814CH SPECIFICATIONS ........................................................................................... 3-23
3.10.3
MX4428 PROGRAMMING OPTIONS - 814CH ........................................................... 3-23

Issue 1.5

24 March 2006

Page iii

MX4428 MXP Engineering /Technical Manual
3.11
3.11.1
3.11.2
3.11.3
3.12
3.12.1
3.12.2
3.12.3
3.13
3.13.1
3.13.2
3.13.3
3.14
3.14.1
3.14.2
3.14.3
3.15
3.15.1
3.15.2
3.15.3
3.16
3.16.1
3.16.2
3.16.3
3.16.4
3.16.5
3.17
3.17.1
3.17.2
3.17.3
3.17.4
3.18
3.18.1
3.18.2
3.19
3.19.1
3.19.2
3.20
3.20.1
3.20.2
3.20.3
3.20.4
3.21
3.21.1
3.21.2
3.21.3
3.21.4
3.22
3.22.1
3.22.2
3.22.3
3.22.4
3.23
3.23.1
3.23.2
3.23.3
3.24
3.24.1
3.24.2
3.24.3
3.25
3.25.1

Document: LT0273

MUB UNIVERSAL BASE .................................................................................................... 3-25
GENERAL..................................................................................................................... 3-25
MUB AND 5B WIRING ................................................................................................. 3-25
REMOTE INDICATOR WIRING ................................................................................... 3-25
5BI ISOLATOR BASE ......................................................................................................... 3-26
GENERAL..................................................................................................................... 3-26
SPECIFICATIONS........................................................................................................ 3-26
WIRING ........................................................................................................................ 3-26
814RB RELAY BASE .......................................................................................................... 3-28
GENERAL..................................................................................................................... 3-28
SPECIFICATIONS........................................................................................................ 3-28
WIRING ........................................................................................................................ 3-28
814SB SOUNDER BASE .................................................................................................... 3-30
GENERAL..................................................................................................................... 3-30
SPECIFICATIONS........................................................................................................ 3-30
WIRING ........................................................................................................................ 3-30
MKII SOUNDER BASE........................................................................................................ 3-31
GENERAL..................................................................................................................... 3-31
SPECIFICATIONS........................................................................................................ 3-31
WIRING ........................................................................................................................ 3-31
MIM800 AND MIM801 MINI INPUT MODULES.................................................................. 3-32
GENERAL..................................................................................................................... 3-32
MIM800 / MIM801 SPECIFICATIONS ......................................................................... 3-32
FIELD WIRING ............................................................................................................. 3-33
MX4428 PROGRAMMING OPTIONS - MIM800 / MIM801 ......................................... 3-33
MX4428 PROGRAMMING OPTIONS - MIM801.......................................................... 3-34
CIM800 CONTACT INPUT MODULE.................................................................................. 3-35
GENERAL..................................................................................................................... 3-35
CIM800 SPECIFICATIONS .......................................................................................... 3-35
FIELD WIRING ............................................................................................................. 3-36
MX4428 PROGRAMMING OPTIONS - CIM800 .......................................................... 3-36
CP820 MANUAL CALL POINT ........................................................................................... 3-38
GENERAL..................................................................................................................... 3-38
MX4428 PROGRAMMING OPTIONS - CP820............................................................ 3-38
FP0838 / FP0839 MANUAL CALL POINTS ....................................................................... 3-39
GENERAL..................................................................................................................... 3-39
MX4428 PROGRAMMING OPTIONS - FP0838 / FP0839 .......................................... 3-39
DIM800 DETECTOR INPUT MONITOR .............................................................................. 3-40
GENERAL..................................................................................................................... 3-40
DIM800 SPECIFICATIONS .......................................................................................... 3-41
DIM800 DETECTOR COMPATIBILITY........................................................................ 3-42
MX4428 PROGRAMMING OPTIONS - DIM800 .......................................................... 3-42
RIM800 RELAY INTERFACE MODULE ............................................................................. 3-43
GENERAL..................................................................................................................... 3-43
RIM800 SPECIFICATIONS .......................................................................................... 3-43
RIM800 FIELD WIRING ............................................................................................... 3-43
MX4428 PROGRAMMING OPTIONS - RIM800 .......................................................... 3-44
SNM800 SOUNDER NOTIFICATION MODULE................................................................. 3-45
GENERAL..................................................................................................................... 3-45
SNM800 SPECIFICATIONS......................................................................................... 3-45
SNM800 FIELD WIRING .............................................................................................. 3-46
MX4428 PROGRAMMING OPTIONS - SNM800......................................................... 3-46
LPS800 LOOP POWERED SOUNDER MODULE.............................................................. 3-47
GENERAL..................................................................................................................... 3-47
LPS800 SPECIFICATIONS.......................................................................................... 3-47
MX4428 PROGRAMMING OPTIONS - LPS800.......................................................... 3-47
VLC-800MX VESDA LASERCOMPACT............................................................................. 3-49
GENERAL..................................................................................................................... 3-49
VLC800 SPECIFICATIONS.......................................................................................... 3-49
MX4428 PROGRAMMING OPTIONS - VLC800.......................................................... 3-50
AVF / RAD / SAD / FLOWSWITCH DELAYS ..................................................................... 3-51
AVF/RAD ...................................................................................................................... 3-51

Page iv

24 March 2006

Issue 1.5

Document: LT0273
3.25.2
3.25.3
3.25.4

MX4428 MXP Engineering / Technical Manual

SAD .............................................................................................................................. 3-51
AVF/SAD ...................................................................................................................... 3-51
FLOWSWITCH ............................................................................................................. 3-51

CHAPTER 4 ANALOGUE LOOP DESIGN CONSIDERATIONS ...........................4-1
4.1
4.1.1
4.1.2
4.1.3
4.1.4
4.2
4.2.1
4.2.2
4.2.3
4.2.4
4.3
4.4
4.4.1
4.5
4.5.1
4.6
4.7

ANALOGUE LOOP CONFIGURATION SELECTION .......................................................... 4-2
LINES & LOOPS ............................................................................................................ 4-2
LOOP FAULT TOLERANCE .......................................................................................... 4-2
AS1670.1 DESIGN REQUIREMENTS........................................................................... 4-2
NZS4512 DESIGN REQUIREMENTS ........................................................................... 4-2
ANALOGUE LOOP/LINE LAYOUTS .................................................................................... 4-3
LINE MODE .................................................................................................................... 4-3
LOOP DESIGN WITH SHORT CIRCUIT ISOLATORS.................................................. 4-3
STAR CONNECTION OF ANALOGUE LINES .............................................................. 4-5
SPURS ........................................................................................................................... 4-5
CABLE SELECTION CONSIDERATIONS............................................................................ 4-6
AC REQUIREMENTS ............................................................................................................ 4-7
GENERAL....................................................................................................................... 4-7
DC CONSIDERATIONS......................................................................................................... 4-7
GENERAL....................................................................................................................... 4-7
MECHANICAL CONSIDERATIONS ..................................................................................... 4-7
NOISE CONSIDERATIONS .................................................................................................. 4-8

CHAPTER 5 MXP CURRENT CONSUMPTION.....................................................5-1
5.1
5.1.1
5.1.2
5.1.3

THEORY ................................................................................................................................ 5-2
ALARM CURRENT......................................................................................................... 5-2
QUIESCENT CURRENT ................................................................................................ 5-3
HEAT LOSS.................................................................................................................... 5-3

CHAPTER 6 EVENT LOG AND STATUS AT MX4428 ..........................................6-1
6.1
6.2

RETURNED ANALOG VALUES ........................................................................................... 6-2
FAULT AND ALARM EVENT LOG....................................................................................... 6-3

CHAPTER 7 MXP TECHNICAL DESCRIPTION ....................................................7-1
7.1
7.2
7.2.1
7.2.2
7.2.3
7.2.4
7.2.5
7.3
7.3.1
7.3.2
7.3.3
7.4
7.5

GENERAL.............................................................................................................................. 7-2
CIRCUIT DESCRIPTION ....................................................................................................... 7-3
BLOCK DIAGRAM.......................................................................................................... 7-3
MICROPROCESSOR & LOGIC CIRCUITRY ................................................................ 7-3
MXP POWER SUPPLY .................................................................................................. 7-4
MX4428 LOOP INTERFACE.......................................................................................... 7-6
ANALOGUE LOOP INTERFACE ................................................................................... 7-7
MXP ADJUSTMENTS.......................................................................................................... 7-10
40V ISO SUPPLY VOLTAGE ADJUSTMENT ............................................................. 7-10
TX DATA VOLTAGE ADJUSTMENT ........................................................................... 7-10
40V ISO SUPPLY CURRENT LIMIT ADJUSTMENT................................................... 7-10
MXP LED INDICATIONS ..................................................................................................... 7-11
PARTS LIST ........................................................................................................................ 7-12

CHAPTER 8 MXP DIAGNOSTIC TERMINAL ........................................................8-1
8.1
8.1.1
8.1.2
8.1.3
8.1.4
8.1.5
8.1.6
8.1.7
8.1.8

MXP DIAGNOSTIC TERMINAL OPERATION...................................................................... 8-2
INTRODUCTION ............................................................................................................ 8-2
MENU OF COMMANDS................................................................................................. 8-2
SELECTING POINTS FOR MONITORING.................................................................... 8-2
DISPLAYING DEVICE ANALOGUE VALUES - CV, TV, ETC ....................................... 8-3
ST (STATUS COMMAND) ............................................................................................. 8-5
ANALOG LOOP DIAGNOSTICS.................................................................................... 8-6
ADVANCED COMMANDS ............................................................................................. 8-8
MX4428 DIAGNOSTICS ................................................................................................ 8-8

Issue 1.5

24 March 2006

Page v

MX4428 MXP Engineering /Technical Manual
8.1.9
8.2
8.2.1
8.2.2

Document: LT0273

MXP EVENT LOG .......................................................................................................... 8-9
FLASH PROGRAMMING .................................................................................................... 8-10
FILES REQUIRED........................................................................................................ 8-10
PROCEDURE............................................................................................................... 8-10

CHAPTER 9 DEVICE PROCESSING.....................................................................9-1
9.1
9.2
9.3
9.3.1
9.4
9.4.1
9.4.2
9.4.3
9.5
9.5.1
9.5.2
9.5.3
9.6
9.7
9.7.1
9.7.2
9.8
9.8.1
9.8.2
9.8.3
9.8.4
9.9
9.9.1
9.10
9.10.1
9.10.2
9.10.3
9.11
9.11.1
9.12
9.12.1
9.13
9.14
9.15
9.16
9.17
9.18
9.19
9.20
9.21
9.22
9.23
9.23.1
9.23.2
9.23.3
9.23.4
9.24
9.25

EXPONENTIAL FILTER ........................................................................................................ 9-2
STEP LIMITING FILTER........................................................................................................ 9-2
HEAT PROCESSING............................................................................................................. 9-4
CONVERSION OF DETECTOR READING TO °C ........................................................ 9-4
PHOTO PROCESSING.......................................................................................................... 9-6
SMARTSENSE PROCESSING...................................................................................... 9-6
SMARTSENSE ENHANCEMENT .................................................................................. 9-6
FASTLOGIC PROCESSING .......................................................................................... 9-7
CO PROCESSING ................................................................................................................. 9-8
CALIBRATION AND TEMPERATURE COMPENSATION ............................................ 9-8
“ENHANCEMENT” ......................................................................................................... 9-8
CO PROCESSING ......................................................................................................... 9-8
IONISATION PROCESSING ................................................................................................. 9-9
MIM800 / CIM800 / MIM801 PROCESSING........................................................................ 9-10
ALGORITHM - MIM800, CIM800 ................................................................................. 9-11
ALGORITHM - MIM801 ................................................................................................ 9-11
DIM PROCESSING.............................................................................................................. 9-12
LOAD GRAPH .............................................................................................................. 9-12
DIM MODEL ................................................................................................................. 9-12
ALGORITHM - DIM800 ................................................................................................ 9-12
SUPPLY MONITORING - DIM800 ............................................................................... 9-13
RIM PROCESSING.............................................................................................................. 9-13
POSITION MONITORING ............................................................................................ 9-13
SNM PROCESSING ............................................................................................................ 9-13
PROGRAMMING.......................................................................................................... 9-13
SUPPLY FAULT DETERMINATION ............................................................................ 9-13
EOL AND POSITION MONITORING ........................................................................... 9-13
LPS PROCESSING ............................................................................................................. 9-14
ELD AND POSITION MONITORING ........................................................................... 9-14
VLC800 PROCESSING ....................................................................................................... 9-14
GENERAL..................................................................................................................... 9-14
FILTER STEP LIMITS.......................................................................................................... 9-15
ZONE ALARM TEST ........................................................................................................... 9-15
ZONE FAULT TEST ............................................................................................................ 9-15
AUTOTEST AND SYSTEM TEST ....................................................................................... 9-15
NON LATCHING TEST MODE............................................................................................ 9-16
COMMISSION MODE .......................................................................................................... 9-16
FAST POINT TEST.............................................................................................................. 9-16
SLOW POINT TEST ............................................................................................................ 9-16
SUMMARY OF ALL TEST MODES .................................................................................... 9-16
ANCILLARY FILTERING..................................................................................................... 9-17
RESET ................................................................................................................................. 9-18
RESET OF ADDRESSABLE DETECTOR ................................................................... 9-18
RESET OF DIM MODULE............................................................................................ 9-18
RESET OF ANCILLARY INPUT DEVICE .................................................................... 9-18
RESET OF ANCILLARY OUTPUT DEVICE ................................................................ 9-18
DEVICE INITIALISATION AND POLLING.......................................................................... 9-19
SOFTWARE VERSIONS ..................................................................................................... 9-20

CHAPTER 10 MXP LOOP FILTER BOARD ........................................................10-1
10.1
10.2
10.3

USE OF MXP LOOP FILTER BOARD ................................................................................ 10-2
FITTING ............................................................................................................................... 10-2
DIAGNOSTICS .................................................................................................................... 10-3

Page vi

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Introduction

CHAPTER 1
INTRODUCTION

Issue 1.5

24 March 2006

Page 1-1

MX4428 MXP Engineering / Technical Manual
Introduction

1.1

Document: LT0273

ABOUT THIS MANUAL

This manual (MX4428 Product Manual Volume 11) is intended to provide all information and
procedures required to incorporate one or more MXPs within an MX4428 system. It
predominantly covers the function and engineering associated with the MXP itself, its impact
on the MX4428 Responder Loop and the analogue loop/line(s) to which the compatible
devices are connected. It does not duplicate basic MX4428 system engineering information,
except at the point of interface (i.e. at the MX4428 Responder Loop), or for clarification as
required. It is therefore a supplement to the F4000 Engineering Manual (F4000 Product
Manual, Vol 3), to which the reader is referred for further information.

1.2
1.2.1

ASSOCIATED DOCUMENTATION
PRODUCT RELATED

The following MX4428/F4000 product manuals are available:
Volume 1,
F4000 Operator's Manual, provides a complete guide to the operation and
maintenance of the F4000 FIP and RDU panels, with Version 1.X software, according to
Australian Standards AS1603 Part 4. This manual is provided as standard with non-LCD
F4000 FIP panels (LT0057). See Volume 10 for AS4428.1 compliant systems.
Volume 2,
F4000 Technical Manual, provides complete technical details on the F4000
system and Hardware/Software components, according to Australian Standards AS1603
Part 4, for servicing purposes (LT0069).
Volume 3,
F4000 Engineering Manual, provides complete design details for correctly
engineering the F4000/MX4428 system to meet customer and standard specifications
(LT0071).
Volume 4,
F4000 Installation Manual, provides complete details for correctly installing
and placing into operation the F4000/MX4428 system (LT0070).
Volume 5,
F4000 Programming Manual, provides details for correctly programming the
F4000/MX4428 system to meet the system engineering specifications (LT0072).
Volume 6,
F4000 AAR Technical & Engineering Manuals, Volume 6-1 provides
Technical details on the AAR and Addressable Devices, and Volume 6-2 provides
Engineering Design information for correctly engineering the AAR loop (LT0095/LT0096).
Volume 7,
F4000 LCD Operator's Manual, provides a complete guide to the operation
and maintenance of F4000 LCD FIP panels with Version 2.X software, according to
Australian Standards AS1603 Part 4, AS4050(INT), and New Zealand Standard NZS4512.
From Issue 2.35A onwards LT0117 includes networked operation, previously covered in a
separate manual LT0150 (LT0117/LT0118). See Volume 10 for AS4428.1 compliant
systems.
Volume 8,
F4000 NZ Fire Indicator Panel Technical Manual, provides additional
installation and technical information regarding the application of F4000/MX4428 Analogue
Addressable Fire Alarm Systems in New Zealand (LT0126).

Page 1-2

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Introduction

Volume 9,
F4000 MPR Technical & Engineering Manuals, Volume 9-1 provides
technical details on the MPR and Addressable devices, and Volume 9-2 provides
Engineering Design information for correctly engineering the MPR loop (LT0139/LT0140).
Volume 10, MX4428 AS4428.1 LCD Operator’s Manual, provides a guide to the
operation and maintenance of MX4428 AS4428.1 LCD FIP panels with Version 3.10
software, according to Australian Standard AS4428.1, and New Zealand Standard NZS4512.
This manual (LT0249) is provided as standard with MX4428 panels.
Volume 11, MX4428 MXP Technical / Engineering Manual, (LT0273) provides technical
details on the MXP and its addressable devices, and provides engineering design
information for correctly engineering the MXP loop.
F4000 Point Text Installation & Operation Manual (LT0228) provides details of the Point
Text expansion option.
SmartConfig User Manual (LT0332) provides details on programming an MX4428
database using the SmartConfig program.

1.2.2

STANDARD RELATED

This manual makes reference to the following Australian Standards –
AS1603.4

Automatic Fire Detection and Alarm Systems
Part 4 - Control and Indicating Equipment

AS1670.1

Automatic Fire Detection and Alarm SystemsSystem Design, Installation, and Commissioning.

AS1851.8

Maintenance of Fire Protection Equipment
Part 8 - Automatic Fire Detection and Alarm Systems.

AS4428.1

Automatic Fire Detection and Alarm Systems. Control and Indication
Equipment.

This manual makes reference to the following New Zealand Standard –
NZS4512

Automatic Fire Alarm Systems in Buildings.

1.3
Inputs / Outputs

Card Size
Supply Voltage
Current Consumption
Operating Temperature Range

Issue 1.5

SPECIFICATIONS
1. Standard F4000 / MX4428 Responder Loop.
2. Analogue Loop for up to 200 MX devices, with a
maximum output current = 400mA.
3. RS232 Diagnostics Port.
194mm * 140mm * 35mm.
17.0VDC to 30.0VDC.
50mA to 1.3A depending on the number and type of
devices connected. Refer to section 5.1.
-5°C to +50°C, 10% to 93% RH non condensing.

24 March 2006

Page 1-3

MX4428 MXP Engineering / Technical Manual
Introduction

1.4
AAR
AC
ACZ
ADR
Analogue Loop
ARR
AVF
AZF
CO
CV
DC
Detector
EOL
Evacuation Device
FIP
GLOBAL
HH
HL
LCD
LED
MAF
MIC X
MPR
MXP
MCP
Module
NA
NC
NLR
NO
PCB
Point
PSU
Responder

Responder Loop
ROR
RF
RRM
RZDU
Sensor
SLV
Zone
Page 1-4

Document: LT0273

TERMINOLOGY
Analogue Addressable Responder.
Alternating Current.
Ancillary Control Zone.
Advanced Detector Responder.
The wiring that allows an MXP to communicate with and
supply power to the addressable devices it is to monitor.
Advanced Relay (and Detector) Responder, which is an ADR
fitted with an RRM.
Alarm Verification Facility, or alarm check.
Alarm Zone Facility, previously referred to as "GROUP".
Carbon Monoxide
Current Value (Filtered reading from detector)
Direct Current.
Addressable device used to detect fires that interfaces to the
MXP via the Analogue Loop. It contains one or more sensors.
End of Line device.
Sounder for warning of evacuation.
Fire Indicator Panel, as defined by standards.
A function that may affect more than one zone.
History High - the highest value a variable has reached
History Low - the lowest value a variable has reached.
Liquid Crystal Display (usually alphanumeric)
Light Emitting Diode (Visual Indicator).
FIP Master Alarm Facility.
Measure of smoke density used with ionisation smoke
detectors.
Multi Protocol Responder.
MX Protocol Responder
Manual Call Point (break glass switch).
Addressable I/O device that interfaces to the MXP via the
Analogue Loop.
Not Applicable.
Normally Closed.
Number of logical responders.
Normally Open.
Printed Circuit Board.
Any addressable device (detector or module) with a unique
address that is connected to the analogue addressable loop.
Power Supply Unit.
A general term for all responder types, e.g. ADR, ARR, MPR,
MXP, AAR and IOR that may be connected to the MX4428
Loop.
A 4 core cable for communication and power to all responders
connected to an MX4428 FIP.
Rate of Rise.
Radio Frequency.
Responder Relay Module.
Remote Zone Display Unit.
Part of a detector which senses the environment - smoke or
temperature or CO.
Step limited (or slope limited) value.
Fire searchable area of Building.
24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Responder Loop Design Considerations

CHAPTER 2
RESPONDER LOOP DESIGN
CONSIDERATIONS

Issue 1.5

24 March 2006

Page 2-1

MX4428 MXP Engineering / Technical Manual
Responder Loop Design Considerations

2.1

Document: LT0273

MXP APPLICATION CONSIDERATIONS

The inclusion of one or more MXPs in an MX4428 system requires consideration of .....
(i)

The definition of zones throughout the area to be protected.

(ii)

Assessment of the detectors and other addressable device types and positions
required to monitor each zone and interface to external equipment. This will indicate
if and where the MXP's addressable devices are most appropriate, for purely
functional reasons or for reducing system cost through reduced wiring.
The Design Engineer should be fully familiar with the concept of logical responders,
as described in Section 2.2, before allocating an MXP to monitor multiple alarm
zones.
This process should result in an initial system design defining .....
-

(iii)

(iv)

Number and location of all Responders including MXPs.
Number and location of all addressable devices.
Planned cable route for MX4428 Responder Loop.
Planned cable route(s) for MXP Analogue Loop(s).

Using the design rules given in this manual, analyse each MXP Analogue Loop/Line
to confirm .....
-

the MXP's current capability is adequate for the proposed devices (see
Section 3.2).

-

the proposed cable has the correct AC characteristics (see Section 4.4).

-

the proposed cable has the correct DC characteristics (see Section 4.5).

Using Section 5 of this manual, in conjunction with the MX4428 Engineering Manual
(LT0071), analyse the MX4428 responder Loop. This should result in.....
-

the type and size of cable to be used for the power and signal portions of the
MX4428 Responder Loop.

-

the number and position of Loop Boosters required (if necessary).

(v)

The results of (iii) and (iv) indicate whether or not the proposed system design is
practical and/or cost-effective. If not, analyse what factors have contributed to the
design being impractical, re-design these areas or consider the use of loop boosters
and return to step (i).

(vi)

Assess and document the programming of the MX4428 Master to support the system
design. Programming of the MX4428 is covered in the MX4428 Programming Manual
LT0072, with additional details of using SmartConfig in the SmartConfig user manual
LT0332. The following data must be entered to support MXPs.
-

Page 2-2

information which, when downloaded to the MXP, defines how the MXP is to
process the data received from addressable devices on the Analogue
Loop/Line(s),
information retained at the Master which defines how it is to process data
received from configured MXPs on the MX4428 Loop.
24 March 2006

Issue 1.5

Document: LT0273

2.2
2.2.1

MX4428 MXP Engineering / Technical Manual
Responder Loop Design Considerations

"LOGICAL" RESPONDERS
THEORY

The MX4428 Master Panel can transfer data to and from up to 127 uniquely addressed
Responders distributed around the MX4428 Responder Loop. Its database is structured to
support the 4 circuit inputs and 4 relay outputs associated with the most common responder
type, the ADR. Incorporating an MXP, which supports up to 200 input, output, or input /
output points, represents a departure from the original ADR / AAR structure, but it is similar
to that used for the MPR multiprotocol responder.
To incorporate the MXP, while still preserving the original 1 x MX4428 LOOP ADDRESS
SUPPORTS 4 INPUTS (“CIRCUITS”) AND 4 OUTPUTS (“RELAYS”) database assumption,
the concept of "logical responders" is used. A logical responder refers to a single responder
loop number, supporting 4 inputs and 4 outputs. An ADR/ARR therefore represents a single
logical responder. A responder that supports more than 4 inputs and outputs, such as the
MXP, must therefore occupy multiple responder loop numbers. That is, it is a "multiple
logical responder" unit. One MXP may in fact be configured at the MX4428 FIP to be
between 1 and 50 logical responders.
Since an MXP can support up to 200 points irrespective of how many logical responders it
has been configured to represent, it may be necessary to allocate multiple points to each
logical responder circuit input or relay output. This has certain implications described below,
the most significant being that it is a logical responder “circuit” which is mapped to a zone,
not a point, and it is a logical responder “relay” which is mapped to an ACZ, not a single
output point. Thus if multiple devices are allocated to a circuit, they must all be in the same
zone, and if multiple outputs are allocated to a relay, they will generally be controlled as one.

2.2.2

LOGICAL RESPONDERS

Points map to logical responder circuits and relays as shown in Table 2-1 for different
numbers of logical responders.
Basically the 200 points are evenly distributed across the number of logical responder
circuits/relays (= number of logical responders * 4), with the remainder allocated to the last
circuit.
Input devices are map to the circuit. Output devices usually map to the relay, but may map to
the circuit by programming.
The 50 logical responder option is the only one that allows unique monitoring and full front
panel indication of all 200 individual points without using the MX4428 Point Text expansion
option. The 50 logical responder option however, uses 50 of the 127 available MX4428
responder loop addresses and therefore limits the remainder of the MX4428 system.
Figure 2.1 shows an example 3 logical responder MXP, which has a capability of 3 X 4 = 12
circuits (C1/1-1/4, C2/1-2/4, C3/1-3/4) and 12 relays (R1/1-1/4 ..... R3/4).
Splitting up the possible 200 addressable devices equally among the 12 circuits results in
each circuit being able to service 200/12 = 16 devices, with 8 left over. Thus devices 1-16
are associated with circuit C1/1, devices 17-32 are associated with C1/2, etc, up to C3/4,
which not only handles its own 16 points but also the extra 8 device addresses (193-200)
otherwise not catered for. Input devices are mapped to circuits, and output devices are
usually mapped to relays but may alternatively be mapped to the circuit.
Issue 1.5

24 March 2006

Page 2-3

MX4428 MXP Engineering / Technical Manual
Responder Loop Design Considerations

Document: LT0273

Number of Logical
Responders
(NLR)

Number of Circuits (Relays)
available
(NC = 4 * NLR)

Number of Points per circuit
(relay)
PC = 200/NC

Total Quantity of Points
in Last Circuit

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

4
8
12
16
20
24
28
32
36
40
44
48
52
56
60
64
68
72
76
80
84
88
92
96
100
104
108
112
116
120
124
128
132
136
140
144
148
152
156
160
164
168
172
176
180
184
188
192
196
200

50
25
16
12
10
8
7
6
5
5
4
4
3
3
3
3
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

50
25
24
20
10
16
11
14
25
5
28
12
47
35
23
11
66
58
50
42
34
26
18
10
2
97
93
89
85
81
77
73
69
65
61
57
53
49
45
41
37
33
29
25
21
17
13
9
5
1

Table 2-1 Point Allocation For Various Numbers of Logical Responders

Page 2-4

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Responder Loop Design Considerations
F4000 LOOP
ANALOG LOOP
MAPPED
TO

TOTAL OF
200 DEVICES

DEVICE 1-16

C1/1 R1/1

DEVICE 17-32

C1/2 R1/2

DEVICE 33-48

C1/3 R1/3

DEVICE 49-64

C1/4 R1/4

DEVICE 65-80

C2/1 R2/1

DEVICE 81-96

C2/2 R2/2

DEVICE 97-112

C2/3 R2/3

DEVICE 113-128

C2/4 R2/4

DEVICE 129-144

C3/1 R3/1

DEVICE 145-160

C3/2 R3/2

DEVICE 161-176

C3/3 R3/3

DEVICE 177-200

C3/4 R3/4

LOGICAL
RESPONDER
#1

LOGICAL
RESPONDER
#2

F4000
MASTER

LOGICAL
RESPONDER
#3

ANALOG LOOP

F4000 LOOP

3 LOGICAL RESPONDER MXR

Figure 2.1 Device To Circuit Mapping For 3 Logical Responder MXP

2.2.3

POINT TO CIRCUIT TO ZONE MAPPING

Taking the 3 logical responder example in the previous sections, assume that of the 16
possible device addresses that belong to C1/1, only 10 of these are in fact used, and that 7
are input devices, and the remaining 3 are output devices. Further, assume that the
MX4428 FIP is configured to map C1/1 to ZONE 1.
In this case, an alarm sensed by any of the 7 input devices would put C1/1 into alarm, which
in turn would put ZONE 1 into alarm, a condition indicated on the MX4428 Master front
panel. However, the MXP also generates what is referred to as an extended event,
indicating precisely which of the 7 input devices caused the alarm. This is transmitted to the
MX4428 Master where it is presented on the front panel LCD, entered in the history log and
printed on the logging printer (if programmed).
If, for instance, in this example it was input device 6 that caused the ALARM then the
extended event would take the form .....
"P1/6 ALARM" where .....
..... P = POINT
1 = BASE ADDRESS OF RESPONDER
6 = DEVICE NUMBER
If the Point Text expansion option is fitted at the MX4428 Master, the event will be
associated with a text description of the point.
Issue 1.5

24 March 2006

Page 2-5

MX4428 MXP Engineering / Technical Manual
Responder Loop Design Considerations

Document: LT0273

So far only input devices have been considered. To continue our example for output
devices, if the MX4428 Master generated an output command, via output logic, to turn on
R1/1, then the MXP would activate all output devices associated with that relay, that is, in
this case, all 3.

2.3

IMPLICATIONS TO SYSTEM DESIGN

The System Designer should be aware of the following MX4428 characteristics before
proceeding with the design .....
(i)

While the MX4428 with MXP capability can support up to 16 x 200 (3,200) points (i.e.
addressable devices), the Master unit has a maximum of 528 zones with which to
indicate the status of the system.
The 528 zones may be used to display the status of either an "alarm zone",
representing the status of a particular sub-section of the area to be monitored, or an
"ancillary control zone" (ACZ), representing the status of an output controlled by the
MX4428 system.
The Point Text expansion option can be used to extend this capability. Refer to the
F4000 Point Text Installation and Operation Manual (LT0228) for further information.

(ii)

FIP zone indicators are controlled according to the zone’s status, which is generated
from the mapped circuit status. That is, the 4 circuits monitored by each of the 127
logical responders can control a maximum of 4 x 127 = 508 unique zones.
The point handling capability of an MX4428 system requiring individual LED
indicators per monitored point is therefore reduced to 508.
Therefore, the more individual LED indications that the FIP must show for each MXP
the more logical responders that MXP must represent.
Every additional 4 zones that must be indicated for the addressable devices on an
MXP incurs a cost of 1 additional logical responder (i.e. MX4428 responder loop
address).

(iii)

For the same reasons as given in (ii) above, the more individually controllable output
devices the MXP must drive and control from logic, the more logical responders the
MXP must represent.

Page 2-6

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

CHAPTER 3
DEVICE INFORMATION AND PROGRAMMING

Issue 1.5

24 March 2006

Page 3-1

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.1

Document: LT0273

DEVICE TYPES

The MXP can communicate with a mix of up to 200 addressable devices, within limits
defined by loop size.

3.1.1

MX DEVICES

MX devices fall into three basic types:
(a)

Sensors

-

Detectors (814PH, 814CH, 814I, 814H, VLC800)

(b)

Ancillaries

-

Input (Monitor) (MIM800, MIM801, CIM800, DIM800)
MCP (CP820, FP0838, FP0839)
Output (Control) (RIM800, SNM800, LPS800)

(c)

Bases

-

Standard Base (MUB, 5B)
Short Circuit Isolator (5BI)
Relay Base (814RB)
Sounder Base (814SB, MkII Sounder Base)

In addition non-addressable smoke, thermal or flame detectors may be connected to the
MXP loop by means of the DIM800 Detector Input Module.

Code
814PH
814CH
814I
814H
VLC800
MIM800
MIM801
CP820
FP0838
FP0839
CIM800
DIM800
RIM800
SNM800
LPS800

Description

Input /
Output
Photoelectric Smoke + Heat Detector I/O
Carbon Monoxide + Heat Detector
I/O
Ionisation Smoke Detector
I/O
Heat Detector
I/O
Vesda Aspirating smoke detector
I/O
Mini Input Module
Input
Mini Input Module normally closed
Input
interrupt (FP0837)
Manual Call Point
Input
NZ Manual Call Point
Input
Contact Input Module
Detector Input Module
Relay Interface Module (unsupervised
load wiring)
Sounder Notification Module (relay
output with supervised load wiring)
Loop Powered Sounder

Remote
LED
Y
Y
Y
Y
Y

Input
Input
Output
Output
Output

The devices above are addressed by the

801AP

Service Tool

or by command from the diagnostics terminal of an MXP.

Page 3-2

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

The standard base for use with the 814 detectors is:

MUB
5B

Minerva Universal Base (4”)
Minerva Universal Base (5”)

The following special purpose bases may also be used.

5BI
814RB
814SB
MkII Sounder Base
(802SB, 812SB, 901SB,
and 912SB)

Isolator Base
Relay Base
Sounder Base
Sounder Base

The 814RB and 814SB may be plugged into an MUB, 5B or a 5BI, or mounted directly on a
wall / ceiling.
Note that none of the bases are addressable devices. The functional bases (814RB, 814SB,
and MkII Sounder Base) are controlled by the MXP via the detector which is plugged into
them.
The devices above marked as “Input/Output” are always inputs, but may also be used as
outputs via the Remote Indicator output and the signal to the 814RB, 814SB, and MkII
Sounder Base functional bases. The output functionality is programmable and not
necessarily related to the input status.
The devices which have a remote LED output may drive a Tyco E500Mk2 remote LED. The
functionality of this LED is programmable and it does not necessarily follow the local LED.
A brief description of the capabilities of each device follows:
a)

814I Analogue Ionisation Smoke Detector

This unit uses an ionisation chamber (with a small radioactive source) to detect airborne
particles of combustion products.
b)

814H Analogue Heat Detector

This detector incorporates a temperature sensor. The temperature sensor processing may
be programmed as Type A (rate of rise plus fixed temperature = 63°C), Type B (fixed
temperature only = 63°C), Type C (rate of rise plus fixed temperature = 93°C), or Type D
(fixed temperature only = 93°C). Type A, B, C or D operation is programmable at the
MX4428 panel.
c)

814PH Analogue Photoelectric Smoke Detector + Heat Detector

This unit uses light scattering to detect airborne particles of combustion products, and in
addition incorporates a temperature sensor. The heat function may be programmed in the
same way as for the 814H detector.
d)

814P Analogue Photoelectric Smoke Detector

This unit uses light scattering to detect airborne particles of combustion products.

Issue 1.5

24 March 2006

Page 3-3

MX4428 MXP Engineering / Technical Manual
Device Information and Programming
e)

Document: LT0273

814CH Analogue CO (Carbon monoxide) Detector + Heat Detector

This unit uses a special sensor to detect carbon monoxide, and in addition incorporates a
temperature sensor. The heat function may be programmed in the same way as for the
814H detector.
f)

Mini Input Module MIM800

This unit has a single input for monitoring clean contacts (e.g. MCPs, flow switches
conventional detectors with hard contact outputs, relay contacts, switches). As well as
monitoring the state of the contacts the MIM800 can supervise the wiring for open circuit
fault and (optionally) short circuit fault.
g)

Mini Input Module MIM801

This unit has a single input for monitoring clean contacts (e.g. MCPs, flow switches,
conventional detectors with hard contact outputs, relay contacts, switches). As well as
monitoring the state of the contacts the MIM801 can supervise the wiring for short circuit
fault and (optionally) open circuit fault. The MIM801 is very similar to the MIM800, however it
is optimised for normally closed applications and can generate an interrupt on an open
circuit. (Interrupt is only used when a fast response is required.) (The MIM800 and CIM800
can also generate interrupts, but only in response to closing contacts.)
h)

Contact Input Module CIM800

This unit has two separate inputs for monitoring switch or relay contacts (e.g. MCPs, flow
switches, conventional detectors with hard contact outputs, relay contacts, switches). As well
as monitoring the state of the contacts the CIM800 can supervise the wiring for open circuit
fault and (optionally) short circuit fault. Although there are two separate inputs, both belong
to the same point. Either input in alarm will put the point into alarm, and either input in fault
will put the point into fault. Unused inputs must be terminated with a 200Ω resistor.
i)

Detector Input Module DIM800

This unit has two separate inputs for monitoring conventional detectors. As well as
monitoring the state of the detectors they can supervise the wiring for open circuit faults.
Although there are two separate inputs, both belong to the same point. Either input in alarm
will put the point into alarm, and either input in fault will put the point into fault. An external
power supply is required. The voltage requirements for some conventional detector types
are very specific. (Refer to section 3.20).
j)

Australian Call Point Module CP820

This unit consists of a MIM800 complete with a call point switch and break-glass housing.
k)

New Zealand Call Point Module FP0838, FP0839

This unit consists of a MIM801 complete with a call point switch and break-glass housing.
FP0838 is flush mounting while FP0839 is surface mounting.
l)

Relay Interface Module RIM800

This unit has voltage free changeover relay contacts rated at 2A 30Vdc for external loads.
No supervision of load wiring is provided. However the relay position is supervised and a
“relay checkback fail” fault will be generated if it does not operate.

Page 3-4

24 March 2006

Issue 1.5

Document: LT0273
m)

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Sounder Notification Module SNM800

This unit has a relay rated at 2A 30Vdc for switching external loads. Supervision of load
wiring and the load supply is provided. The relay position is supervised and a “relay
checkback” fault will be generated if it does not operate.
n)

Short Circuit Isolator 5BI

This detector base is designed for isolating short circuited sections of the analog loop. For
instance it can be used where the loop wiring crosses zone boundaries and it will prevent a
short circuit from affecting more than one zone. As well as housing a detector it can be used
with no detector inserted.
o)

Sounder Base 814SB and MkII Sounder Base

These detector bases are designed as low cost warning devices. The MkII Sounder Base is
a newer version of the 814SB. Some variants are loop powered while others are powered by
an external supply. The sounder is controlled by the detector which is plugged into the base,
but the operation of the sounder can be quite separate from the operation of the detector.
The 814SB can be setup to generate a number of tones (none of which are AS2220 or
ISO8201 compliant), and three sound levels are selectable.
The MkII Sounder Base models can be setup to generate a number of tones including
AS2220 and ISO8201 compliant evacuation tones, and on some models the sound level is
continuously adjustable. Currently none of the MkII Sounder Base models are SSL listed.
Note that the current taken by a loop powered sounder base is very much higher than any of
the other loop devices (except the LPS800), and the number of sounder bases on a loop is
limited by the available current.
p)

Relay Base 814RB

This detector base is designed for a low cost output device. It is controlled by the detector
which is plugged into it, but the operation of the relay can be quite separate from the
operation of the detector. A voltage two pole changeover relay is provided, rated at 1A 30V
dc.
q)

Loop Powered Sounder LPS800

This device is similar to the SNM800, in that it drives one or more external sounders,
however the sounder power comes from the loop rather than an external power supply. The
available output current is much lower than that of a SNM800, and as all this current comes
from the loop, the number of LPS800s and their load is limited by the available loop current.
r)

Vesda VLC800

The Vision Systems VLC800-MX VESDA Laser COMPACT is an aspirating smoke detector.
It samples the smoke from air which is extracted via piping from a large area of a building.
The sensitivity is adjustable over a wide range at the VLC800 by PC software programme.
The VLC800 requires a 24V power supply.
A summary of the electrical specifications of the various devices is shown in Table 3-1.

Issue 1.5

24 March 2006

Page 3-5

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Document: LT0273

All loop devices are rated at a loop voltage of 20Vdc - 40Vdc and a signalling voltage of 2V
p-p – 6V p-p. Alarm Currents specified do not include remote indicators. Add 7mA for each
remote indicator.
DEVICE
814I
814H
814PH
814P
814CH

FUNCTION
Ionisation Smoke Detector
Heat Detector
Photo Smoke + Heat
Detector
Photo Smoke Detector
CO + Heat Detector
Mini Input Module

MIM800

MIM801

Mini Input Module
(normally closed interrupt)

Contact Input Module
CIM800
DIM800
CP820
FP0838, FP0839
RIM800
SNM800
LPS800
MUB
5BI
814SB
802SB
812SB
MkII
Sounder
Bases

901SB

912SB
814RB
VLC800

(Conventional) Detector
Interface Monitor
Call Point
NZ Call Point
Relay Interface Module
Sounder Notification
Module (Supervised relay
output)
Loop Powered Sounder
Module
Standard Base
Isolator Base
Loop Powered Sounder
Base
Loop Powered Sounder
Base
Loop Powered Sounder
Base
Externally Powered
Sounder Base

Externally Powered
Sounder Base
Relay Base
Vesda aspirating smoke
detector

Comments
Requires base
Requires base
Requires base
Requires base
Requires base
EOL 200Ω
Alarm R (if used) 100Ω
Max Wiring R 10Ω
N/O mode - as MIM800
N/C EOL 200Ω
Max wiring R 50Ω
EOL 200Ω
Alarm R (if used) 100Ω
Max Wiring R 10Ω
EOL 4k7
Requires separate supply.

2A 30Vdc
2A 30Vdc.
Requires external supply.
Provides 24V at up to 75mA

Selectable tone (not AS2220 or ISO8201)
Adjustable sound level
Selectable tone (Including AS2220 and ISO
8201 Evacuation tone)
Adjustable sound level
Selectable tone (Including AS2220 and ISO
8201 Evacuation tone)
Selectable tone (Including AS2220 and ISO
8201 Evacuation tone)
Adjustable Sound Level.
Requires external 24V
Selectable tone (Including AS2220 and ISO
8201 Evacuation tone)
Requires external 24V
1A 30Vdc
2 pole changeover
Requires external supply. Requires PC to
set up.

Table 3-1 Compatible Device Summary
The MXP will allow some alternative devices to be used without generating a fault, where the
inserted device can provide all the features of the configured device. This includes an 814PH
or 814CH used where an 814H was programmed, a CIM800 used where a MIM800 was
programmed, and an 814PH used where an 814P was programmed.
Page 3-6

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.2
3.2.1

DEVICE HANDLING CAPABILITY
OVERVIEW

The parameters which determine the maximum number of each device type that can be put
on a loop are as follows. The column “MAX NO. DEVICES” assumes that all devices are of
the same type. If this is not the case, it is necessary to perform the calculations described
below.
Quiescent
Current

DEVICE

MAX NO.
DEVICES

814I
814H
814PH
814P
814CH
MIM800

200
200
200
200
200
200

330uA
250uA
275uA
275uA
275uA
275uA

MIM801

200

275uA

CIM800
DIM800

200
200

CP820
RIM800

200
200

275uA
100uA
(Loop)
275uA
285uA

SNM800

200

450uA

LPS800

33 or less,
depends on
load
N/A
40(Quiet)
30(Medium)
24(Loud)
200(Quiet)
50 (Loud)
18
200
200
200
125

450uA

5BI
814SB

802SB*
812SB*
901SB*
912SB*
814RB
VLC800

80uA
400uA

200uA
200uA
200uA
200uA
50uA
300uA

Alarm
Current

AC Units
(max 250
total)

3.0mA
3.0mA
3.0mA
3.0mA
3.0mA
2.8mA (with LED)
275uA (no LED)
2.8mA (with LED)
275uA (no LED)
2.8mA
100uA (Loop)

1
1
1
1
1
1

IB Units
(max 100 IB
units between
Isolator Bases)
1.4
1
1.2
1.2
1
1.5

1

1.5

1
1

1
1

2.8mA
2.8mA (with LED)
285uA (no LED)
3.0mA (with LED)
450uA (no LED)
Load current +
4mA, with
minimum of 12mA

1
1

1.5
5

1

5

1.5

1

0.2
2.4

N/A
2.5

0.5

2.5

0.5
0.5
0.5
0.3
2

2.5
2.5
2.5
1.6
1

9mA(Quiet)
12mA(Medium)
15mA(Loud)
1.2mA (Quiet)
6.8mA (Loud)
21mA
200uA (Loop)
200uA( Loop)
100uA
300uA (no LED)
2.8mA (with LED)

*Models of MkII Sounder Base
Table 3-2 Device Quantities and Loading
The particular combination of device types, external loads, cable length and type may limit
the total number of devices. This is calculated in the following sections.
There are two types of load which must be considered - DC and AC. Also if isolator bases
are used, the loading between each isolator base must be considered.

Issue 1.5

24 March 2006

Page 3-7

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Document: LT0273

It is recommended that the PC program F4000CAL is used for conducting the loop loading
calculations. However note that it does not include the isolator base loading, this must be
done manually.

3.2.2

DC LOAD

The total current available from the MX Loop terminals on the MXP is 400mA DC.
This must supply operating current to all addressable devices an the loop. This not only
includes the quiescent current required to power the device electronics, but also the
additional current drawn by devices in the ALARM state or by associated ALARM LEDs and
other loop powered outputs.
The sum of currents for all devices connected to the loop is calculated using the “alarm
current” values shown in Table 3-2. Note –
1)
2)

3)

4)

The MXP limits the number of Alarm LEDs turned on at any one time to 5
(programmable at MX4428).
Remote LEDs must be allowed for at 7mA each. Remote LEDs programmed to follow
the detector LED will be limited by the number of alarm LEDs. However remote LEDs
programmed to operate on “Circuit Alarm” or “Relay” will not be limited in any way.
LEDs on relay output devices (SNM800, RIM800, LPS800) will operate when the
relay is activated, if the MXP is configured at the MX4428 to flash the LED on Poll
“Global Blink Mode”.
The 814RB, RIM800 and SNM800 relay load current must not be supplied from the
analogue loop.

The sum of all currents must not exceed 400mA.
Furthermore, the voltage drop in the cable must not exceed 16.0V, regardless of which end
of the loop the cable is driven from. This is in order to ensure that with the minimum 36V
voltage available from the MX Loop terminals on the MXP, the minimum voltage at any
device will be at least 20V.
If you have any LPS800 devices on the loop, you may need to design for a higher minimum
loop voltage and a lower voltage drop. Refer to section 3.23.2.

3.2.3

AC LOADING

Calculate the total of the “AC Units” shown in Table 3-2. The total must not exceed 250.
Also ensure that the cable length does not exceed the values in Table 3-3.
Cable type
MICC 2L1.5, 2L2.5, 1H1.5, 2H2.5
Steel Wire Armour (SWA)
Fire resistant ‘foil and drain wire’, e.g.
Radox FR3013, FP200, Lifeline, Firetuff
BS6883 marine cable

Cable length
1.8 km*
1.8 km*
2 km
2 km

Table 3-3 Maximum Cable Lengths
* Up to 2km of these cable types may be used on condition that the maximum AC loading is
restricted to less than 220 AC units per loop.

Page 3-8

24 March 2006

Issue 1.5

Document: LT0273

3.2.4

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

ISOLATOR BASE LOADING

If isolator bases are being used, calculate the sum of the “IB Units” from Table 3-2 for each
section of cable between isolator bases (or between the last isolator base and the end of a
cable spur). Include only one of the detectors at the ends of the section. The sum for any
section must not exceed 100.
See also section 4.1.3 for details of AS1670 requirements and section 4.1.4 for details of
NZS4512 requirements.

3.2.5

EXAMPLE

Consider an MXP monitoring 200 * 814PH detectors with 10 814SB Sounder Bases set to
High, on a 1300 metre long loop, using 1.5mm2 wire. The cable is divided (with 9 Isolator
Bases) into 10 segments with 1 Sounder Base and 20 detectors on each segment.
(i)

Calculate DC Load
IA = 195 x 275uA
+ 5 x 3.0mA

(No. of detectors in NORMAL)
(No. of detectors with Alarm LEDs turned on, assume limited to
5 max by MXP)
+ 10 x 15mA
(Number of 814SB Sounder Bases)
+ 9 x 80uA
(Number of Isolator Bases)
(Ref Table 3-2. Note 1mA = 1000uA)
= 220mA which is well under 400mA

For the voltage drop calculation, assume the worst case in the first instance, i.e. that
2
all devices are at the far end of 1300 metres. The loop resistance of 1.5mm wire is
25Ω per 1000m and the isolator base resistance is 0.25Ω.
Total R
= 25Ω x 1.3 + 9 x 0.25Ω
= 34.75Ω.
Voltage drop = 34.75 x 0.220 = 7.7V, which is well under the maximum allowable of
16V.
(ii)

Calculate AC Load
AC Units

=

=

200 x 1 (detectors)
+ 10 x 2.4 (Sounder Bases)
+ 10 x 0.1 (Isolator Bases)
225 which is less than the maximum allowable of 250.

Cable length is well under the limits specified in Table 3-3.
(iii)

Calculate IB Load
IB Units for each section

= 20 * 1.2 (814PH) + 1 * 2.5 (814SB)
= 26.5 which is less than 100.

As all parameters are within the specified limits, the design is satisfactory.

Issue 1.5

24 March 2006

Page 3-9

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.3

Document: LT0273

OUTPUT CONTROL

The following “outputs” are available on the Analogue loop –
• Output modules – RIM800, SNM800, and LPS800
• Functional Base outputs of detectors (controlling 814SB, MkII Sounder Base or 814RB)
• Remote LED output of detectors.
Each of these is programmable at the MX4428 for which of 3 sources controls the output.
In all cases the outputs are turned off if the point is isolated.
The 3 selectable sources are as follows –
1. Relay output
The output is controlled by the state of the corresponding relay output as sent to the
responder. The relay output state can be controlled directly with a logic equation, be
controlled by the state of the ACZ that the relay is mapped to (this also allows supervision
fault states on the SNM800 and LPS800 output to be indicated), or be controlled by the test
state of the flow switch zone it is mapped to.
The functional bases and remote LED outputs for detectors mapped to circuit X of logical
responder R will be controlled by the state of relay X of logical responder R, i.e. the relay
with the same number as the detector circuit.
2. Circuit alarm
The output will turn on when the corresponding circuit goes into alarm. If the circuit maps to
a latching zone then the output will turn off when the zone alarm is reset. If the circuit does
not map to a latching zone the output will turn off when the circuit goes out of alarm. The
circuit alarm state is determined by the MXP and so can’t include other responder circuits,
nor the state of the zone(s) the circuit maps to. (Use “relay output” if these are needed.)
The functional bases and remote LED outputs for detectors will be controlled by the circuit
the detector is mapped to. Output modules mapped to relay X of logical responder R will be
controlled by circuit X of logical responder R, i.e. the circuit with the same number as the
relay.
WARNING - the output will not be disabled by zone isolate.
3. Point alarm
The output will turn on when that point goes into alarm. If the point maps to a latching zone
then the output will stay on until the zone alarm is reset. If the point does not map to a
latching zone the output will turn off when the point goes out of alarm.
This option is not available on output modules (RIM800, SNM800, and LPS800).
WARNING - the output will not be disabled by zone isolate.

Page 3-10

24 March 2006

Issue 1.5

Document: LT0273

3.3.1

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

PROGRAMMING

The programming of the output functions is done by setting the “mode” value for the RIM800,
SNM800, and 814I, and by one of the 7 device parameters for the 814H, 814PH, and
814CH. The LPS800 is programmed as an SNM800.
For example the following are the settings for the 814I.
Mode
0
1
2
4
5
6
8
9
10

Functional Base Control
Circuit Alarm
Circuit Alarm
Circuit Alarm
Relay
Relay
Relay
Point Alarm
Point Alarm
Point Alarm

Remote LED Control
Circuit Alarm
Relay
Point Alarm
Circuit Alarm
Relay
Point Alarm
Circuit Alarm
Relay
Point Alarm

The value must be chosen from the above table to give the desired settings for controlling
the functional base and the remote LED.
For the 814PH and 814CH, programming of the “enhancement multiplier” is included in the
same parameter. The desired enhancement multiplier must be multiplied by 16 and the
result added to the above numbers. The tables in the sections for these detectors (3.9.3 and
3.10.3) include the result when the default enhancement multiplier is used.
For the 814H detector and for an 814PH or 814CH with enhancement disabled, the
“enhancement multiplier” is irrelevant and therefore the above numbers may be entered
directly if desired. The global defaults for parameter 6 for all these detector types should
always include the desired enhancement multiplier * 16.
For the SNM800, other options are also included in the mode. Refer to section 3.22.4 for
details.

3.3.2

OUTPUT STATE UNDER EXCEPTIONAL CIRCUMSTANCES

All outputs retain their state if the MX4428 stops polling the responder (e.g. processing is
stopped), or if the MXP stops polling the devices (e.g. due to a new configuration download
from the MX4428). If a detector is removed from a relay or sounder base, the relay or
sounder output turns off.
If power to the MXP is lost, loop powered sounder bases turn off. RIM800 and SNM800
outputs, relay bases and possibly externally powered sounder bases usually retain their
state until MXP power is restored, then turn off when polling resumes (which may take some
minutes if the MXP has been off for some hours and lost its configuration), then revert to ON
after a few seconds if this is the correct state.

Issue 1.5

24 March 2006

Page 3-11

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.4

Document: LT0273

DETECTOR PARAMETER SETTINGS SUMMARY

The following table gives a summary of the MX4428 default and alternate settings, and
approved range, for each detector type.
Detector
814PH
Smoke
814PH
Smoke
FastLogic

Default
12%
(80 det units)
Medium

Alternate
8%
(37 det units)
N/A

Range
8% - 12%

814PH Heat
component

63

N/A

814CH
CO

38ppm
(0.3 MIC X)
(93 det units)

66ppm(1)
(0.6 MIC X)
(160 det units)

23 - 66ppm(1)

814CH Heat
component

63

N/A

60 - 65

814I
814H

0.39 MIC X
(66 det units)
63

0.22 MIC X
(23 det units)
N/A

0.2 - 0.4 (Aus)
0.2 - 0.6 (NZ)
60 - 93 (Aus)
50 - 80 (NZ)

VLC800

Fixed at 100

Low, Medium,
High (all
approved with
nominal
sensitivity =
8%)
60 - 65

0.005% / m to
20% / m

Comments
Enhancement is optional,
default off.
Enhancement is optional,
default off.

Type B default.
Type A is option
Off is option.
Enhancement is optional,
default off.
(23ppm = 0.15 MIC X
= 60 det units)
Type A default.
Type B is option
Off is option.
0.59 MIC X =130 det
units
Type A default. Type B
option.
Types C/D by changing
temperature to 93.
Note that actual
sensitivity is adjusted by
PC connected to the
VLC800.

(1)

66ppm is outside the approved range of the 814CH as an ionisation detector. However it
is an accepted value as a CO detector.
Prealarm

The Prealarm default and alternate sensitivities will generally be about 70% - 80% of the
corresponding alarm level. Note that Prealarm will also be more sensitive to rapidly changing
conditions as it does not go through the step limiting filter.
Conversion
Det Units = Detector Units.
Temperatures are already converted by the MXP to degrees C and do not require
conversion.

Page 3-12

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Conversion from detector units to displayed values is by imagining a graph with a series of
joined straight lines from (0,0) and passing through each of the above defined points (e.g.
814PH 37 det units = 8%) and extrapolated in a continuing straight line past the highest
point if necessary.
For the 814PH detector the displayed values bear little resemblance to the static sensitivity
of the detector. They are valid only for the tests done in the SSL smoke room.

3.5
3.5.1

DEVICE INSTALLATION
PRECAUTIONS

Observe ESD precautions when installing an MXP responder, or connecting any devices to
it. Refer to Product Bulletin PBG0025.

3.5.2

MOUNTING

Detector Bases
Detectors attach to a circular, plastic base which has holes for screw mounting to a flat
surface, and screw terminals for connecting the loop wiring. There are various different
bases available. Most of the bases may only be mounted as just described, but the 814SB
sounder base and the 814RB relay base may be mounted as just described, or may
themselves be plugged into one of the other bases, to interpose between it and the detector.
Modules
The Modules are normally mounted within the enclosure of the equipment to which they
connect, or in a cabinet, junction box or switch box. They may be mounted on plastic
standoffs (4 x HW0130 required) on a gearplate or cabinet, or to a face plate that mounts on
a double flush or surface box. A hole may be required for the on-board LED. A standard
plate with a hole for the LED and three holes for the Service Tool is available (Ancillary
Cover M520). This fits a plastic surface box K2142.
The MIM800/801 is smaller than the other modules, and is supplied in a plastic housing
which has a lug for screw mounting.

3.5.3

ADDRESS & LED BLINK PROGRAMMING

Addresses for MX detectors and modules, and options such as LED blink on poll, are most
easily set using the MX Service Tool. These are set by placing the detector onto the Service
Tool, or connecting the module to the Service Tool with the supplied interface lead, and
programming as per the MX Service Tool Instructions. (Be careful not to leave the pins in the
module when removing the lead).
For all input devices, including detectors, the LED turns on steady when in alarm. For output
devices (RIM800, etc) the LED turns on when the device is activated (if Global Blink Mode is
enabled for the MXP). To enable a device’s LED to blink on poll, the MXP must have Global
Blink Mode enabled at the MX4428 panel, and the device must have LED Blink enabled.
For a mixed system, i.e. some devices are to blink on poll and some are not, then turn off
blink on those devices that are not to blink using the Service Tool, and enable Global Blink
Mode at the MX4428 panel for the MXP.

Issue 1.5

24 March 2006

Page 3-13

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.6

Document: LT0273

MX4428 PROGRAMMING

In the following sections information is given about the programming of each device in the
MX4428. An explanation of the mode and the various parameters is given for each device
type, along with the global parameters that affect that device type. It is critical that only the
listed mode values are used for each device type, as in many cases the mode value is used
to define the actual device type. An incorrect mode value may cause a POINT TYPE
MISMATCH to be generated, or it may just render a device not able to work.
In some of the following sections descriptions are given about changing the sensitivity for a
detector by altering the specific parameter for that detector. This is correct (it sets the value
for just that individual detector), but in many cases it may be better to adjust the global
sensitivity for that device type so that all detectors of that type take on the new value. For
example, in NZ mode it is recommended that the global heat alarm temperature be set to
57°C for both 814PH and 814CH, rather than setting each specific detector to this value.
Details for NZ mode settings are contained in the F4000 NZ Technical Manual (LT0126).
These details are most relevant when programming the MX4428 from a (dumb)
programming terminal. Alternatively you can program with "SmartConfig", which displays
and edits functional parameters and takes care of mapping the functional parameters into
the appropriate mode and parameter bytes for each device type.

Page 3-14

24 March 2006

Issue 1.5

Document: LT0273

3.7
3.7.1

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

814H HEAT DETECTOR
GENERAL

The 814H is an analogue thermal detector. The detector senses the air temperature and
sends this value to the MXP. The MXP makes any decisions as to whether this is an alarm,
fault, normal or whatever. The MXP can be programmed (at the MX4428 panel) to interpret
the values to implement a Type A, Type B, Type C, or Type D Heat Detector. The integral
LED is turned on by the MXP when an alarm is detected.
The 814H has a temperature sensing range of -25°C to 95°C. The approved operating
temperature range is -10°C to +70°C. The accuracy of the 814H (as interpreted by the
MXP), within the range 0°C to 70°C, is typically + / - 2°C.
The remote LED and functional base outputs are programmable for their functionality (refer
to section 3.3).

3.7.2

814H SPECIFICATIONS

Line Connections

L(–), L1(+)

Supply Voltage:

20Vdc - 40Vdc

Supply Current:

250uA (typical quiescent)

Alarm Current:

3.0mA (typical)

Remote LED Current:

7mA (Tyco E500Mk2)

Dimensions:

110mm (diameter) x 55mm (including MUB base)

Weight

79g

Base

MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

3.7.3

MX4428 PROGRAMMING OPTIONS - 814H

The programming values for the 814H are described in the following tables.
“Mode” enables or disables rate of rise processing. Mode = 4 selects type A/C (heat rate of
rise enabled), and mode = 5 selects type B/D (heat rate of rise disabled). Only select one of
these two values. (Note that when rate of rise is disabled, the parameters relating to rate of
rise are ignored - there is no need to adjust them.)
For type C and D operation set the heat fixed temperature alarm threshold (Parameter 1) to
93 (°C).
Parameter 0 may be adjusted to select a different Pre-Alarm temperature.
For special purposes, the fixed temperature alarm threshold may be set to any value
between 60 and 93 for Australia, and between 50 and 80 for New Zealand. In New Zealand
also set the global parameter “8XX HEAT SL1” to (the highest alarm temperature - 20) / 10
(rounded up if the result is fractional).
For functional base and remote LED programming set Parameter 6 as per the table. Refer
to section 3.3 for further details.
The remaining parameters should not need changing.
Issue 1.5

24 March 2006

Page 3-15

MX4428 MXP Engineering / Technical Manual
Device Information and Programming
Parameter
Mode

P0
P1

P4

Document: LT0273

Description
Value
Heat Type
4
A/C – rate of rise enabled.
5
B/D – rate of rise disabled
Heat fixed temperature pre-alarm threshold °C
Heat fixed temperature alarm threshold °C
57
New Zealand
63
Australian Types A / B
93
Australian Types C / D
b3:b0
ROR Pre alarm Threshold
Number + 5 gives the
Threshold in °C/min
b7:b4
ROR Alarm Threshold

Default
4

56 (°C)
63 (°C)

7 (12°C/min)
9 (14°C/min)

P5
P6

Enhancement multiplier (default 12) * 16 plus code below
192
Code
Functional Base
Remote LED
Final value
Control
Control
with default
enh multiplier
0
Circuit Alarm
Circuit Alarm
192
1
Circuit Alarm
Relay
193
2
Circuit Alarm
Point Alarm
194
4
Relay
Circuit Alarm
196
5
Relay
Relay
197
6
Relay
Point Alarm
198
8
Point Alarm
Circuit Alarm
200
9
Point Alarm
Relay
201
10
Point Alarm
Point Alarm
202
Note – enhancement multiplier is unused for individual 814H detector settings, but must be
retained in MX4428 default settings, as the same defaults are used for the 814H and
814PH.
The following global parameters, which may be set at the MX4428, affect all applicable
points on all MXPs.
MX4428 Reference
8XX HEAT FD1
8XX HEAT FD2
8XX HEAT SL1
8XX HEAT SL2

Page 3-16

Description
Heat FD1 (CV Filter)
Heat FD2 (ROR determination)
Heat SL1 (Fixed temp step limit, °C/5sec)
Heat SL2 (ROR step limit, °C/min/5sec)

24 March 2006

Default
4
7
2
3

Issue 1.5

Document: LT0273

3.8
3.8.1

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

814I IONISATION SMOKE DETECTOR
GENERAL

The 814I is an ionisation smoke detector. The detector senses the amount of smoke present
and sends this value to the MXP. The MXP makes any decisions as to whether this is an
alarm, fault, normal or whatever. The integral LED is turned on by the MXP when an alarm is
detected.
The remote LED and functional base outputs are programmable for their functionality (refer
to section 3.3).

3.8.2

814I SPECIFICATIONS

Line Connections

L(–), L1(+)

Supply Voltage

20Vdc - 40Vdc

Supply Current

330uA (typical quiescent)

Alarm Current

3.0mA (typical)

Remote LED Current

7mA (Tyco E500Mk2)

Dimensions

110mm (diameter) x 55mm (including MUB base)

Weight

81g

Base

MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

3.8.3

MX4428 PROGRAMMING OPTIONS - 814I

The programmable values for the 814I are explained in the following table.
Normally only the mode needs to be programmed, and then only if a functional base or
remote LED is required and its operation is different from the default. Refer to section 3.3.
In some cases the alarm sensitivity (Parameter 1) may need to be changed from the default.
The approved range for Australia is 0.22 MIC X (23) to 0.39 MIC X ( 66). The available range
is 0.22 MIC X (23) to 0.59 MIC X (130). If the alarm sensitivity is changed, the pre-alarm
sensitivity (Parameter 0) should normally be changed to about 75% of the alarm sensitivity.
The remaining parameters should not need changing.

Issue 1.5

24 March 2006

Page 3-17

MX4428 MXP Engineering / Technical Manual
Device Information and Programming
Parameter
Mode

P0
P1

P2
P3
P4
P5
P6

Document: LT0273

Description
Value
Functional Base Control
Remote LED Control
0
Circuit Alarm
Circuit Alarm
1
Circuit Alarm
Relay
2
Circuit Alarm
Point Alarm
4
Relay
Circuit Alarm
5
Relay
Relay
6
Relay
Point Alarm
8
Point Alarm
Circuit Alarm
9
Point Alarm
Relay
10
Point Alarm
Point Alarm
Pre Alarm Threshold
Alarm Threshold
Value
Threshold
23
0.22 MICX (Alternate)
66
0.39 MICX (Default)
130
0.59 MICX
Fault Limit (i.e. values below this are assumed to indicate a
detector fault)
Dirty Alert Limit (i.e. a “dirty alert” will be raised if the
tracked “clean air” value reaches this limit)
b3:b0
Filter Divisor
b7:b4
Step Limit
Tracking Interval i.e. the interval at which the tracked “clean
air” value is adjusted.
Tracking adjustment - fixed at 1 in MXP

Default
0

50
66

10
120
3
5
30 (minutes)
1

The following global parameters which may be set at the MX4428 affect all applicable points
on all MXPs.
MX4428 Reference
8XXI UPPER
TRACKING LIMIT

Page 3-18

Description
Ionisation Upper Tracking Limit
(i.e. the maximum assumed value for
clean air)

24 March 2006

Default
120 (MXP
Default)

Issue 1.5

Document: LT0273

3.9

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

814PH PHOTOELECTRIC SMOKE & HEAT
DETECTOR & 814P PHOTOELECTRIC SMOKE
ONLY DETECTOR

3.9.1

GENERAL

The 814PH is a photoelectric smoke detector which also includes a temperature sensor. The
detector senses the amount of smoke present and the temperature and sends these values
to the MXP. The MXP makes any decisions as to whether this is an alarm, fault, normal or
whatever, based on the smoke level, temperature, or rate of rise of temperature, and/or a
combination of these. The integral LED is turned on by the MXP when an alarm is detected.
Refer to the specifications of the 814H for more details on the heat sensing element of the
814PH.
The 814P is the same as the 814PH, except that it has no temperature sensor.
The remote LED and functional base outputs are programmable for their functionality (refer
to section 3.3).

3.9.2

814PH & 814P SPECIFICATIONS

Line Connections

L(–), L1(+)

Supply Voltage

20Vdc - 40Vdc

Supply Current

275uA (typical quiescent)

Alarm Current

3.0mA (typical)

Remote LED Current

7mA (Tyco E500Mk2)

Dimensions

110mm (diameter) x 55mm (including MUB base)

Weight

76g

Base

MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

3.9.3

MX4428 PROGRAMMING OPTIONS - 814PH/814P

In the MX4428 programming there are two different device types that use the 814PH/814P
detector. Type 16 814PH is used when the 814PH is used with the SmartSense algorithm
and type 27 814PHFL is used when the FastLogic algorithm is required. These different
device types allow the MX4428 to have separate sensitivity settings for the algorithms and
for the sensitivities to be displayed correctly.
However, the mode value actually defines to the MXP which algorithm is to be used.
Mode values 0 – 7 must only be used with a device type of 814PH, and mode values 8 – 15
must only be used with a device type of 814PHFL. Do not use an incorrect mode, as the
values displayed at the MX4428 will not match those being used or generated at the MXP.
The 814P must be programmed as an 814PH, with no heat. I.e. only modes 7 and 13 are
allowed. The MX4428 will display the point type as 814PH.
The programmable values for the 814PH and 814P are described in the following tables.

Issue 1.5

24 March 2006

Page 3-19

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Document: LT0273

The mode selects the detection mode for the detector - smoke only, enhanced smoke, heat
enabled or disabled, heat rate of rise enabled or disabled, smoke detection algorithm is
SmartSense or FastLogic, etc. Note that when a particular function is disabled by the setting
of the mode, the parameters relating to that function are not used and should therefore be
left with their default settings.
Parameter 1 selects the smoke alarm threshold.
With the SmartSense algorithm, the actual alarm threshold is selected as per the table. The
approved range is 8%/m (Parameter 1 = 37) to 12%/m (Parameter 1 = 80).
With the FastLogic algorithm Parameter 1 values of 0, 1, or 2 will select Low, Medium, or
High sensitivity respectively. Any other value will select the sensitivity defined in the global
parameter 8XXPH FUZZY ALGORITHM. Parameter 1 can usually be left at its default
setting for all detectors and those detectors with their mode set to FastLogic will then use the
setting in the global parameter 8XXPH FUZZY ALGORITHM. All three FastLogic sensitivities
are SSL approved and all have a nominal sensitivity of 8% / m.
Parameter 3 may be adjusted to vary the fixed temperature alarm threshold. It may be set to
any value between 60 and 65 in Australia, and between 50 and 65 in New Zealand.
Parameter 2 may be adjusted to select a different Pre-Alarm temperature.
Parameter 6 selects the functional base and remote LED output operation (refer to section
3.3) and the “enhancement multiplier” which should normally be left at the default value (12).
The remaining parameters should not need changing.

Page 3-20

24 March 2006

Issue 1.5

Document: LT0273
Parameter
Mode

P0
P1

P2
P3

P4
P5
P6

Description
Value
Smoke
Algorithm

MX4428 MXP Engineering / Technical Manual
Device Information and Programming
Enhance smoke
sensitivity with
heat Rate of
Rise.

Heat Type
A – rate of rise
enabled
B – rate of rise
disabled
A
B
A
B
A
B
No heat alarm
No heat alarm *
A
B
A
B
No heat alarm
No heat alarm *

0
SmartSense
Yes
1
SmartSense
Yes
2
SmartSense
No
3
SmartSense
No
4
None
5
None
6
SmartSense
Yes
7
SmartSense
No
8
FastLogic
Yes
9
FastLogic
Yes
10
FastLogic
No
11
FastLogic
No
12
FastLogic
Yes
13
FastLogic
No
SmartSense smoke Pre Alarm Threshold
SmartSense smoke Alarm Threshold
Value
Threshold
37
8% / m (alternate)
80
12% / m (default)
FastLogic Sensitivity
Value
Sensitivity
0
Low
1
Medium
2
High
Any other
Global Parameter
“8XXPH Fuzzy Algorithm”
Heat fixed temperature pre-alarm threshold °C
Heat fixed temperature alarm threshold °C
Value
Usage
57
New Zealand
63
Australian Types A / B
b3:b0
ROR Pre alarm Threshold
Number + 5 gives the
Threshold in °C/min
b7:b4
ROR Alarm Threshold
b3:b0
Smoke Filter Divisor
b7:b4
Smoke Step Limit
Enhancement multiplier (default 12) * 16 plus value below
Value
Functional Base
Remote LED
Result with
Control
Control
default enh
multiplier
0
Circuit Alarm
Circuit Alarm
192
1
Circuit Alarm
Relay
193
2
Circuit Alarm
Point Alarm
194
4
Relay
Circuit Alarm
196
5
Relay
Relay
197
6
Relay
Point Alarm
198
8
Point Alarm
Circuit Alarm
200
9
Point Alarm
Relay
201
10
Point Alarm
Point Alarm
202

Default
3

68
80

56 (°C)
63 (°C)

7 (12°C/min)
9 (14°C/min)
3
4
192

* These are the only modes allowed with the 814P detector.

Issue 1.5

24 March 2006

Page 3-21

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Document: LT0273

The following global parameters which may be set at the MX4428 affect all applicable points
on all MXPs.
MX4428 Reference
8XXPH UPPER
TRACKING LIMIT
8XXPH DIRTY
ALERT LIMIT
8XXPH TRACK
INTERVAL
8XXPH FUZZY
ALGORITHM

Page 3-22

Description
Photo Upper Tracking Limit (i.e. the
maximum assumed value for clean
air)
Photo Dirty Alert Limit (i.e. a “dirty
alert” will be raised if the tracked
“clean air” value reaches this limit)
Photo Tracking Interval
i.e. the interval at which the tracked
“clean air” value is adjusted.
Fuzzy Sensitivity if Device Parameter
1 is not 0, 1, or 2
0 = low
1 = medium
2 = high

24 March 2006

Default
56 (MXP Default)

56

30 (minutes)

1 (medium)
(MXP also chooses
Medium if this
parameter is not 0,
1, or 2)

Issue 1.5

Document: LT0273

3.10

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

814CH CARBON MONOXIDE + HEAT DETECTOR

3.10.1

GENERAL

The 814CH is a carbon monoxide (CO) detector which also includes a temperature sensor.
The detector senses the amount of CO present and the temperature and sends these values
to the MXP. The MXP makes any decisions as to whether this is an alarm, fault, normal or
whatever, based on the CO level, temperature, or rate of rise of temperature, and/or a
combination of these. The integral LED is turned on by the MXP when an alarm is detected.
Refer to the specifications of the 814H for more details on the heat sensing element of the
814CH.
The remote LED and functional base outputs are programmable for their functionality (refer
to section 3.3).

3.10.2

814CH SPECIFICATIONS

Line Connections

L(–), L1(+)

Supply Voltage

20Vdc - 40Vdc

Supply Current

275uA (typical quiescent)

Alarm Current

3.0mA (typical)

Remote LED Current

7mA (typical Tyco E500Mk2)

Dimensions

110mm (diameter) x 55mm (including MUB base)

Weight

88g

Base

MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

3.10.3

MX4428 PROGRAMMING OPTIONS - 814CH

The programmable values for the 814CH are described in the following tables.
The mode selects the detection mode for the detector - CO only, enhanced CO, heat
enabled or disabled, heat rate of rise enabled or disabled, etc. Note that when a particular
function is disabled by the setting of the mode, the parameters relating to that function are
not used and should therefore be left with their default settings.
Parameter 1 selects the CO alarm threshold. Some possible settings are shown in the table.
Note the alternate setting of 66ppm is not an SSL listed setting for an ionisation detector (the
814CH was SSL tested using the tests for an ionisation detector under AS1603.2, as at the
time there was no approved standard for CO detector). Although this setting is acceptable
for a CO detector it should only be used for special applications where installation conditions
exclude other smoke detectors and yet the background CO level may be higher than normal.
At this sensitivity the background CO level should not exceed 30ppm.
Parameter 3 may be adjusted to vary the fixed temperature alarm threshold. It may be set to
any value between 60 and 65 in Australia.
Parameter 2 may be adjusted to select a different Pre-Alarm temperature.
Parameter 6 selects the functional base and remote LED output operation (refer to section
3.3) and the “enhancement multiplier” which should normally be left at the default value (12).
Issue 1.5

24 March 2006

Page 3-23

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Document: LT0273

The remaining parameters should not need changing.
Parameter
Mode

P0
P1

P2
P3

P4
P5
P6

Page 3-24

Description
Heat Type
Value
Enhance CO
sensitivity with heat A – rate of rise enabled
B – rate of rise disabled
Rate of Rise
0
Yes
A
1
Yes
B
2
No
A
3
No
B
6
Yes
No heat alarm
7
No
No heat alarm
CO Pre Alarm Threshold
CO Alarm Threshold
Value
Threshold
60
23ppm
93
38ppm (default)
160
66ppm (alternate)
Heat fixed temperature pre-alarm threshold °C
Heat fixed temperature alarm threshold °C
Value
Usage
57
New Zealand
63
Australian Types A / B
b3:b0
ROR Pre alarm Threshold
Number + 5 gives the
Threshold in °C/min
b7:b4
ROR Alarm Threshold
b3:b0
CO Filter Divisor
b7:b4
CO Step Limit
Enhancement multiplier (default 12) * 16 plus value below
Value
Functional Base Remote LED
Result with
Control
Control
default enh
multiplier
0
Circuit Alarm
Circuit Alarm
192
1
Circuit Alarm
Relay
193
2
Circuit Alarm
Point Alarm
194
4
Relay
Circuit Alarm
196
5
Relay
Relay
197
6
Relay
Point Alarm
198
8
Point Alarm
Circuit Alarm
200
9
Point Alarm
Relay
201
10
Point Alarm
Point Alarm
202

24 March 2006

Default
2

80
93

56 (°C)
63 (°C)

7 (12°C/min)
9 (14°C/min)
3
3
192

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.11

MUB UNIVERSAL BASE

3.11.1

GENERAL

The MUB accommodates any of the MX 814 series detectors, and may also have an 814RB,
814SB, or MkII Sounder Base plugged into it.

3.11.2

MUB AND 5B WIRING

Figure 3.1 shows the wiring for a MUB and 5B, including optional wiring of a remote
indicator.
AR

+

MXP
AL

+
L
R

L

L1

L1

L1

TYCO MUB (M614)
MINERVA
UNIVERSAL
BASE

TYCO 5B
5“ UNIVERSAL
BASE

L2

L

L2
M

L2

+

-

Tyco E500Mk2
Remote Indicator

R

+

Figure 3.1 MUB and 5B Wiring

3.11.3

REMOTE INDICATOR WIRING

A remote indicator may be wired to an MUB, Relay Base, or Sounder Base as shown for
example in Figure 3.1.
A single Remote Indicator may be wired up to a number of detector bases, so that it turns on
if any one of the detectors turns it on. The R terminals of the detectors involved should be
looped together.
This common group must not include an isolator base or extend across an isolator base.
The brightness may increase slightly if more than one detector turns on the remote indicator.

Issue 1.5

24 March 2006

Page 3-25

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.12
3.12.1

Document: LT0273

5BI ISOLATOR BASE
GENERAL

The 5BI base is designed for isolating short circuited sections of the analog loop. For
instance it can be used where the loop wiring crosses zone boundaries to prevent a short
circuit from affecting more than one zone. When isolator bases are used, it is strongly
recommended that two additional isolator bases (possibly with no detectors inserted) be
installed at the start and end of the loop, close to the MXP.
Isolator bases may also be used to join multiple lines together in a single star arrangement,
for example when a number of conventionally wired zones are being converted to MX and a
loop cannot be wired.
Refer to section 4.1 for more details on the analog loop configuration.
There is a limit to the number of other devices which may be connected on the section of
cable between isolator bases. Calculate the sum of the “IB Units” from Table 3-2 for each
section of cable. The sum for each section must not exceed 100.
A section of cable is the portion between isolator bases or between an isolator base and the
MXP, or if a star configuration or tee is being used, between an isolator base and the end of
the cable.

3.12.2

SPECIFICATIONS

Line Connections IN

M(–), L1(+)

Line Connections OUT

L2(–), L1(+)

Remote LED Connection

R(–), L1(+)

Supply Voltage

20Vdc - 40Vdc

Supply Current

80uA (typical quiescent)

Dimensions

110mm (diameter) x 22mm (excluding detector)

Weight

80g

3.12.3

WIRING

Figure 3.2 shows wiring for an 5BI, including connection of an external remote indicator.
Note that a common remote indicator may not be wired to a set of bases which are on
different sides of an isolator base.

Page 3-26

24 March 2006

Issue 1.5

Document: LT0273

AR

+

AL

+

MXP

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

L

L

L

L1

L1

L

L1

L1

L1

L1
R

L

L

L2
M

L2
M

L2

L2

L2

M

M

R

R

+
TYCO 5BI
ISOLATOR
BASE

+

-

Tyco E500Mk2
Remote Indicator
(controlled by MX4428)

TYCO MUB
UNIVERSAL
BASE

TYCO 5BI
ISOLATOR
BASE

+

-

M and L2 connections to Isolator Base are symmetrical and can be transposed without affecting operation

Figure 3.2 5BI Wiring

Issue 1.5

24 March 2006

Page 3-27

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.13

Document: LT0273

814RB RELAY BASE

3.13.1

GENERAL

The 814RB detector base is designed as a low cost output device. The relay is controlled by
the detector which is plugged into the base, but the operation of the relay can be quite
separate from the operation of the detector. (Refer to section 3.3.)
The 814RB Relay Base provides two sets of volt-free, change-over contacts capable of
switching ancillary equipment rated at up to 1A resistive @ 30Vdc. One set is labelled NO,
C, NC (for normally open, common, and normally closed.) The other set is labelled 1 for NC,
2 for C, and 3 for NO. The terminals accept a single cable of up to 2.5 sqmm. Relay
operation is controlled by the MX4428 via an output from the detector. Hence, a detector
must be fitted to the base in order for the relay to operate as the relay base does not have
its own address.
The 814RB may be plugged into a MUB standard base, 5B standard base, or 5BI isolator
base, or mounted directly on the ceiling or wall.

3.13.2

SPECIFICATIONS

Line Connections

L(–), L1(+)

Remote LED Connection

R(–), L1(+)

Supply Voltage

20Vdc - 40Vdc

Supply Current

50uA (typical quiescent)
100uA (output active)

Relays

Two changeover volt-free contacts
Switching current: 1A @ 30V dc
Resistance: On: 50mΩ Off: > 1 x 109Ω .
Switching time: <10ms
Life expectancy: 100,000 operations

Dimensions

110mm (diameter) x 37mm (excluding detector)

Weight

153g

3.13.3

WIRING

Refer to Figure 3.3 for details of the relay terminals. Loop wiring and remote LED wiring is
the same as the MUB, refer to Figure 3.1. Contact wiring connects to the following terminals

First Pole

Second Pole

Page 3-28

NC
C
NO
1
2
3

Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Figure 3.3 Relay Base

Issue 1.5

24 March 2006

Page 3-29

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.14
3.14.1

Document: LT0273

814SB SOUNDER BASE
GENERAL

The 814SB detector base is designed as a low cost warning device. One of three different
tones may be selected (none of which are AS2220 compliant), and three sound levels are
selectable. Note that the current taken by a sounder base is very much higher than most
other loop devices, and the number of sounder bases on a loop is limited by the available
current.
The sounder is controlled by the detector which is plugged into the base, but the operation of
the sounder can be quite separate from the operation of the detector. (Refer to section 3.3.)
The tone switch allows selection of one of three different tones –
1 - continuous tone (825Hz)
2 - fast sweep (saw tooth envelope at 15Hz)
3 - slow sweep (saw tooth envelope at 5Hz) (Factory Setting)
The volume switch provides three different levels of loudness:
1 - 70dB(A) (quiet)
2 - 80 dB(A) (medium)
3 - 90 dB(A) (loud) (Factory Setting)
The 814SB may be plugged into a MUB standard base, 5B standard base, or 5BI isolator
base, or mounted directly on the ceiling or wall.

3.14.2

SPECIFICATIONS

Line Connections

L(–), L1(+)

Remote LED Connection

R(–), L1(+)

Supply Voltage

20Vdc - 40Vdc

Supply Current

400uA (typical quiescent)
9mA (active in QUIET setting)
12mA (active in MEDIUM setting)
15mA (active in LOUD setting)

Dimensions

110mm (diameter) x 37mm (excluding detector)

Weight

163g

3.14.3

WIRING

Wiring is the same as the MUB, refer to Figure 3.1.

Page 3-30

24 March 2006

Issue 1.5

Document: LT0273

3.15
3.15.1

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

MKII SOUNDER BASE
GENERAL

The MkII Sounder Base is a range of detector bases which are designed as low cost warning
devices, some of which are loop powered and others are externally powered. The sounder is
controlled by the detector which is plugged into the base, but the operation of the sounder
can be quite separate from the operation of the detector. (Refer to section 3.3.)
The MkII Sounder Bases cannot be plugged into other bases. They must be mounted
directly on the ceiling or wall.
At the time of writing, the MkII Sounder Bases are not SSL approved to AS4428. However
they may be used for supplementary local sounders.

3.15.2

SPECIFICATIONS

Line Connections

L(–), L1(+)

Remote LED Connection

R(–), L1(+)

Supply Voltage

20Vdc - 40Vdc

Quiescent Supply Current

200uA (ex MX loop)

Dimensions

110mm (diameter) x 37mm (excluding detector)

Weight

186g

Power Source
Adjustable volume
Volume
Minimum Volume Current
Consumption
Maximum Volume Current
Consumption
Tone 1
Tone 2
Tone 3
Tone 4
Tone 5
Tone 6
Tone 7
Tone 8

3.15.3

802SB
Loop
Yes
68-90dBA
1.2mA (loop)

901SB
24VDC

812SB
Loop
No
100dBA
N/A

1.2mA (ext
supply)
6.8mA (loop) 6.8mA (ext
21mA (loop)
supply)
Dutch Slow Sweep (AS2220 Evacuate)
Temporal 4
Slow Sweep
March Time Beep
Fast Sweep
Temporal 3 (ISO8201 Evacuate)
Alternating
Continuous

912SB
24VDC

21mA (ext
Supply)

WIRING

Wiring for the 802SB and 812SB is the same as the MUB, refer to Figure 3.1. The 901SB
and 912SB wiring is similar, but they also require a 24V connection. Refer to the installation
sheet supplied with these bases.
For the 901SB and 912SB, it is recommended that the external supply covers only one zone,
or the power wiring be arranged so that an open circuit in the power feed cannot affect more
than one zone. A loop arrangement with supervision and a reverse-feed relay can be used to
achieve this - refer to Product Bulletin PBF0200.
Issue 1.5

24 March 2006

Page 3-31

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Document: LT0273

3.16

MIM800 AND MIM801 MINI INPUT MODULES

3.16.1

GENERAL

The MIM800 and MIM801 Mini Input Modules are suitable for interfacing voltage free
contacts such as switches, relay contacts, flow switches, or non-indicating detectors.
Dedicated Manual Call Point products are available that have the MIM800 or MIM801
mounted on the back of an MCP. Refer to sections 3.18 and 3.19.
Both the MIM800 and MIM801 may be used in normally open or normally closed
configurations, and the normally open configuration may or may not include short circuit fault
monitoring. Refer to Figure 3.4 for wiring topology.
The normal response time to an input change of state is 0 – 5 seconds, as each device is
polled at 5 second intervals by the MXP. If faster operation is required, interrupt operation
can be enabled. Interrupt operation allows a change to be signalled by the device so that the
MXP detects the change immediately, rather than waiting for the next poll of the device.
To interrupt on closing contacts, the MIM800 is required. To interrupt on opening contacts,
the MIM801 is required. An interrupt can be generated on only the transition from normal to
alarm, transitions from alarm to normal will always require up to 5 seconds to be recognised.
Fault supervision is provided by a 200Ω EOL resistor - open circuit fault in a normally open
configuration and short circuit fault in a normally closed configuration. In addition the
normally open configuration can be programmed to also generate fault on short circuit. In
this case only one alarm contact is allowed, a 100Ω resistor must be wired in series with the
alarm contacts, and the fault threshold must be specially programmed. (Set Parameter 2 to
176 for a MIM800 and parameter 5 to 40 for a MIM801).
The input wiring should be limited to less than 10m in length and located well away from all
electrical noise sources.
Recognition of a fault condition takes about 30 seconds.
The MIM800 and MIM801 have screw terminals for an Alarm Indicator LED. No series
resistor is required. A current of about 2.5mA will be supplied when the LED is on.
WARNING
DO NOT JOIN INPUT WIRING BETWEEN MODULES OR CONNECT TO ANYTHING
OTHER THAN VOLTAGE FREE CONTACTS

3.16.2

MIM800 / MIM801 SPECIFICATIONS

Dimensions
Weight
Line Connections
Supply Voltage
Supply Current
Contact Inputs

Page 3-32

Height: 13mm Width: 48mm Depth: 57mm
22g
L-, L+
20V – 40V
Standby Current : 275uA (typical)
LED on : 2.8mA (typical)
Monitoring Voltage
5V
Line Resistance (MIM800 and all N/O)
10Ω max
Line Resistance (MIM801 N/C)
50Ω max
24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming
Maximum input cable length
EOL
Alarm Resistance

3.16.3

10m
200Ω + / - 5%.
100Ω + / - 5%. (if used)

FIELD WIRING
Sh L- L+ L- L+

TB1

TB1
PREVIOUS
DEVICE

Requires Param_2 = 176 (MIM800),
Param_5 = 40 (MIM801)

Sh L- L+ L- L+

MIM800
Mini Module

NEXT
DEVICE

PREVIOUS
DEVICE

NEXT
DEVICE

MIM800
Mini Module

ANALOG LOOP

IN- IN+ O- O+

ANALOG LOOP

TB2

TB2

IN- IN+ O- O+

200
ohm
EOL

200
ohm
EOL

LED

Normally Open

100
ohm
LED

N/O with S/C fault

(default for MIM800, option for MIM801.)

(for MIM800 or MIM801)

Inputs must be voltage free.

TB1

Sh L- L+ L- L+

PREVIOUS
DEVICE

MIM801
Mini Module

NEXT
DEVICE

ANALOG LOOP

TB2

IN- IN+ O- O+

200
ohm
EOL

LED

Normally Closed
(default for MIM801,option for MIM800)

Figure 3.4 CLEAN CONTACT DEVICE CONNECTION TO MIM800 / MIM801

3.16.4

MX4428 PROGRAMMING OPTIONS - MIM800 / MIM801

The mode sets the operating configuration.
For the MIM800 the default value of 4 selects normally open operation with no interrupt. A
mode of 6 selects normally open with interrupt on alarm. Changing parameter 2 to 176
enables short circuit fault detection. Setting the mode to 5 enables normally closed
operation.

Issue 1.5

24 March 2006

Page 3-33

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Document: LT0273

For the MIM801 the default value of 15 selects normally closed operation with interrupt on
alarm (e.g. for New Zealand callpoints). Setting the mode to 13 disables interrupt on alarm
(e.g. for heat circuits or other non-immediate alarm conditions). Setting the mode to 12
enables normally open operation and then changing parameter 5 to 40 enables short circuit
fault detection.
Normally Open
Parameter
Mode
P0
P1
P2

Description
4
No interrupt
6
Interrupt
Normal to alarm threshold
Normal to o/c threshold
Alarm to s/c threshold
0
No alarm resistor
176
100 ohm alarm resistor

Default
4
122
50
0

P3
P4
P5
P6

Normally Closed
Parameter
Mode
P0
P1
P2
P3
P4
P5

Description
Change to 5 to select normally closed operation
Normal to s/c threshold
Normal to alarm threshold

Default
4
122
50

P6

3.16.5

MX4428 PROGRAMMING OPTIONS - MIM801

Normally Open
Parameter
Mode
P0
P1
P2
P3
P4
P5

Description
Change to 12 to select normally open operation

Default
15

Normal to alarm threshold
Normal to o/c threshold
Alarm to s/c threshold
0
No alarm resistor
40
100 ohm alarm resistor

110
170
0

P5
P6

Normally Closed
Parameter
Mode

P0
P1
P2
P3
P4
P5
P6

Page 3-34

Description
Value
Description
13
No interrupt
15
Interrupt, does not use AVF even if enabled

Default
15

Normal to s/c threshold
Normal to alarm threshold

110
170

24 March 2006

Issue 1.5

Document: LT0273

3.17
3.17.1

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

CIM800 CONTACT INPUT MODULE
GENERAL

The CIM800 Contact Input Module is suitable for interfacing voltage free contacts, e.g.
switches, relay contacts, flow switches, or non-indicating detectors. It has two inputs, the
state of which are ORed together to generate the point status. Therefore unused inputs must
be terminated with the EOL resistor.
The CIM800 may be used in normally open or normally closed configurations, and the
normally open configuration may or may not include short circuit fault monitoring. Refer to
Figure 3.5 for wiring topology.
The normal response time to an input change of state is 0 – 5 seconds, as each device is
polled at 5 second intervals by the MXP. If faster operation is required, interrupt operation
can be enabled. Interrupt operation allows a change to be signalled by the device so that the
MXP detects the change immediately, rather than waiting for the next poll of the device.
The CIM800 can only interrupt on “closing” contacts, and interrupt operation is only
applicable for normally open contacts. Transitions from closed to open will always require up
to 5 seconds to be recognised. Therefore it cannot be used for callpoints on NZ systems.
Fault supervision is provided by default with a 200Ω EOL resistor - open circuit fault in a
normally open configuration and short circuit fault in a normally closed configuration. In
addition the normally open configuration can be programmed to also generate fault on short
circuit. In this case only one alarm contact is allowed, a 100Ω resistor must be wired in
series with the alarm contacts, and the fault threshold must be specially programmed - set
Parameter 2 to 176.
Recognition of a fault condition takes about 30 seconds.
WARNING
DO NOT JOIN INPUT WIRING BETWEEN INPUTS OR MODULES OR TO ANYTHING
OTHER THAN VOLTAGE FREE CONTACTS

3.17.2

CIM800 SPECIFICATIONS

Dimensions

Height: 61mm

Weight

100g

Line Connections

L-, L+

Supply Voltage

20V – 40V

Supply Current

Standby Current : 275uA (typical)
LED on : 2.8mA (typical)

Contact Inputs

Monitoring Voltage
Line Resistance
EOL
Alarm Resistance

Issue 1.5

Width: 84mm

24 March 2006

Depth: 25mm

5V
10Ω max
200Ω + / - 5%.
100Ω + / - 5% (if used).

Page 3-35

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.17.3

Document: LT0273

FIELD WIRING
Requires Param_2 = 176

ANALOG LOOP

PREVIOUS
DEVICE

200
ohm
EOL

200
ohm
EOL

200
ohm
EOL

PREVIOUS
DEVICE

200
ohm
EOL

NEXT
DEVICE

TB1 TB2

TB1 TB2

A+ A- B+ B-

L+ L- L+ L-

CIM800 CONTACT MODULE

200
ohm
EOL

A+ A- B+ B-

CIM800 CONTACT MODULE

Normally Open

Normally Open, S/C = Fault

200
ohm
EOL

ANALOG LOOP

PREVIOUS
DEVICE

100
ohm

ANALOG LOOP

NEXT
DEVICE

L+ L- L+ L-

100
ohm

NEXT
DEVICE

Unused inputs (A or B) must be terminated with
a 200 ohm EOL resistor.
A and B inputs must be voltage free.

TB1 TB2
L+ L- L+ L-

A+ A- B+ B-

CIM800 CONTACT MODULE

Normally Closed

Figure 3.5 CLEAN CONTACT DEVICE CONNECTION TO CIM800

3.17.4

MX4428 PROGRAMMING OPTIONS - CIM800

The mode sets the operating configuration. The default value of 8 selects normally open
with no interrupts, whereas a value of 10 enables interrupt on alarms.
A mode of 9 selects normally closed operation. Interrupt is not available.

Page 3-36

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Normally Open
Parameter Description
Mode
8
No interrupt
10
Interrupt
P0
Normal to alarm threshold
P1
Normal to o/c threshold
P2
Alarm to s/c threshold
0
No alarm resistor
176
100 ohm alarm resistor
P3
P4
P5
P6
Normally Closed
Parameter Description
Mode
Change to 9 to select normally closed operation
P0
Normal to s/c threshold
P1
Normal to alarm threshold
P2
P3
P4
P5
P6

Issue 1.5

24 March 2006

Default
8
122
50
0

Default
8
122
50

Page 3-37

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.18
3.18.1

Document: LT0273

CP820 MANUAL CALL POINT
GENERAL

The CP820 Manual Call Point consists of a MIM800 mounted on a Break Glass Switch
assembly. The MIM800 is factory programmed with a different type-id to allow the CP820 to
be distinguished from a generic MIM800.
The normal response time to an input change of state is 0 – 5 seconds, as each device is
polled at 5 second intervals by the MXP. If faster operation is required, interrupt operation
can be enabled. Interrupt operation allows a change to be signalled by the device so that the
MXP detects the change immediately, rather than waiting for the next poll of the device.
The CP820 is made without an EOL resistor and no wiring fault monitoring is provided as all
the wiring is internal.
The CP820 device processing will not use AVF, even if it is enabled for the circuit the CP820
is allocated to.

3.18.2

MX4428 PROGRAMMING OPTIONS - CP820

The mode determines whether interrupt operation is enabled or not. A value of 0 (default)
means interrupt is disabled, while a value of 2 enables interrupt operation.
Parameter
Mode
P0
P1
P2
P3
P4
P5
P6

Page 3-38

Description
0
No interrupt
2
Interrupt
Normal to alarm threshold

24 March 2006

Default
0
122

Issue 1.5

Document: LT0273

3.19
3.19.1

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

FP0838 / FP0839 MANUAL CALL POINTS
GENERAL

The FP0838 and FP0839 Manual Call Points consist of a MIM801 mounted on an 1841
Break Glass Switch assembly. They are designed for normally closed contacts as is required
in New Zealand.
The normal response time to an input change of state is 0 – 5 seconds, as each device is
polled at 5 second intervals by the MXP. As faster operation is required in New Zealand,
interrupt operation should be enabled for the MIM801. Interrupt operation allows a change
to be signalled by the device so that the MXP detects the change immediately, rather than
waiting for the next poll of the device. Default programming of the MIM801 selects open
circuit alarm and interrupt operation.
The FP0838 and FP0839 Call Points include a LED visible from the front. This lights on
alarm and can be programmed to blink when the MIM801 is polled. Operation is otherwise
as for the MIM801.

3.19.2

MX4428 PROGRAMMING OPTIONS - FP0838 / FP0839

These Call Points are programmed as MIM801s. Refer to section 3.16.5.

Issue 1.5

24 March 2006

Page 3-39

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.20
3.20.1

Document: LT0273

DIM800 DETECTOR INPUT MONITOR
GENERAL

The DIM800 Detector Input Module is suitable for interfacing conventional non-addressable
detectors e.g. heat detectors, smoke detectors, beam detectors, etc, onto the MXP loop.
Alarm and o/c fault conditions are determined by the MXP. An alarm can be recognised
within 5 seconds if AVF is not enabled for the circuit, or 15-20 seconds if AVF is enabled.
Recognition of a fault condition takes about 30 seconds.
The DIM800 has two inputs, the state of which are ORed to generate the point status.
Therefore unused inputs must be terminated with the correct EOL.
The DIM800 provides electrical isolation of the detector circuit(s) from the MXP loop.
The DIM800 requires an external supply to power the detector circuit and the module itself. If
external power is not provided the DIM800 will not respond to polls and a NODE FAIL fault
will be indicated. The voltage of the external supply at the DIM800 is critical to ensure
compatibility with particular detectors. Refer to Table 3-4.
The external supply cannot be derived from the MXP loop or the MX4428 responder loop,
and in some cases cannot be taken from the MX4428 main power supply. Where the voltage
range is critical, it is recommended that a dedicated power supply and battery be used. The
voltage drop in the wiring from the power supply to the DIM800 must be calculated to ensure
the supply voltage at the DIM800 is within specification. If multiple DIM800s are on the same
cable, then the maximum current drawn by each DIM800 (e.g. input short circuit) must be
used.
The external supply must comply with AS4428.1 and AS4428.5 and should be set to 27.3V
by default. The wiring from a common PSU to multiple DIM800 modules must be arranged
so that a single open circuit does not prevent alarms from being generated in more than one
zone. A loop arrangement with supervision and a reverse-feed relay can be used to achieve
this - refer to Product Bulletin PBF0200.
If the detector itself requires a 24V power supply that needs to be switched off to reset the
detector, e.g. some beam detectors, refer to Product Bulletin PBF0213 for a suitable
arrangement. Do not use the SW+ and SW- terminals available on early DIM800 models.
Field wiring of the DIM800 is shown in Figure 3.6. The wiring instructions for the particular
detector/base must be referred to as some detectors break the negative line, and others the
positive line, when the detector is removed.

Page 3-40

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming
Unused inputs (A or B) must be
terminated with 4k7 EOL.
4k7 EOL

4k7 EOL

Refer text for
voltage
requirements

EXT
PSU
+

Conventional
Detectors
(refer appropriate
wiring diagrams)

ANALOG LOOP

ANALOG LOOP

PREVIOUS
DEVICE

NEXT
DEVICE

COM

+24V

L+ L- L+ L- A+ A- B+ B-

DIM800 DETECTOR
INPUT MONITOR

Figure 3.6 DIM800 Field Wiring

3.20.2

DIM800 SPECIFICATIONS

Dimensions

Height: 61mm

Width: 84mm

Depth: 25mm

Weight

100g

Line Connections

L-, L+

Loop Supply Voltage

20V – 40V

Loop Supply Current

Standby/Alarm Loop Current : 100uA (typical)

EOL

4k7 + / - 1%.

Detector Load

3.0mA max per circuit

External Current (normal)

7.5mA (excluding detectors)

External Current (shorted)

30 - 50mA (depends on supply voltage)

External Supply Voltage

Refer to Table 3-4 for each detector.

Maximum Line Resistance

50Ω (with detectors)
1750Ω (with hard contacts only)

Short Circuit Fault Option

Maximum line resistance 34Ω
Minimum Detector Alarm Voltage 5.0V

Issue 1.5

24 March 2006

Page 3-41

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.20.3
Series

Document: LT0273

DIM800 DETECTOR COMPATIBILITY
Model

Max Qty

External Supply
Voltage at DIM
20.0V – 28.7V
20.0V – 28.7V
20.0V – 28.7V
20.7 – 28.7V
20.7V - 28.7V
20.7V - 28.7V
20.7V - 28.7V
20.7V - 28.7V
20.7V - 28.7V
20.7V - 28.7V
20.0V - 28.7V
20.0V - 28.7V
20.0V - 28.7V

614P Photo Detector
25
614I Ionisation Detector
38
614CH Carbon Monoxide + Heat Detector
32
614T Heat Type A, B, C, D
23
MD614 Heat Detector
40
Minerva
MR614 Photo Detector
22
MR614T HPO Detector
21
MU614 CO Detector
40
MF614 Ionisation Detector
30
T614 Heat Type A, B, C, D
23
4098 – 9603EA Ionisation Detector
24
4098 – 9601EA Photo Detector
24
Simplex
4098 – 9618EA,-9619EA,-9621EA Heat
24
Detectors
P24B Photoelectric Detector
24
20.7V - 24.7V
P29B Photoelectric Detector
20
20.7V - 26.7V
C24B Ionisation Detector
40
20.7V - 26.7V
C29B (Ex) Ionisation Detector
40
20.7V - 26.7V
R23B Flame Detector*
20
20.7V - 24.7V
R24B Flame Detector
3
22.7V - 28.7V
DO1101 Photo Detector*
16
21.7V - 27.7V
Olsen
DLO1191 Beam Detector*
1
22.7V - 28.7V
P136 Duct Sampling Unit
5
20.0V - 28.7V
T56B Heat Detector
40
20.0V - 28.7V
All above Olsen Detectors with Z52B, Z54B,
Z54B Mk2, Z56, Z500 base as appropriate
40
20.0V - 28.7V
T56B Heat Detector with
Z52B, Z55B, Z56N, Z500N Base
System
885WP-B Weatherproof Heat Detector
40
20.0V – 28.7V
Sensor
Type B *@
Hard Contact Devices (T54B, B111, etc)
40
20.0V - 28.7V
Hard contact devices must be rated for at least 30V and currents up to 50mA.
*
Not an SSL Listed combination
@
Remote indicator output cannot be used in common with Tyco 614 series or the
Minerva M614 series (and most other Tyco/Olsen) detectors.

Table 3-4 Conventional Detector Compatibility

3.20.4
Parameter
Mode

MX4428 PROGRAMMING OPTIONS - DIM800

P1
P2
P3

Description
Value
Description
0
Short = Alarm
1
Short = Fault
Normal to Alarm Threshold
Normal to Fault Threshold
Supply Fault Threshold

P4

Alarm to Short Threshold

Page 3-42

24 March 2006

Default
0

51
22
60 (this is MXP default used if
MX4428 value = 0).
On the latest revision of
DIM800, the threshold cannot
be usefully varied by changing
this parameter.
225 (this is MXP default used
if MX4428 value = 0)

Issue 1.5

Document: LT0273

3.21

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

RIM800 RELAY INTERFACE MODULE

3.21.1

GENERAL

The RIM800 Relay Interface Module is suitable for relay outputs which require clean voltage
free contacts and no supervision. For example it can be used to signal states to other
systems (e.g. BMS or security systems), or to energise loads that do not need to be
supervised, e.g. Door Holders.

3.21.2

RIM800 SPECIFICATIONS

Dimensions:

Height: 61mm

Width: 84mm

Weight

100g

Line Connections

L-, L+

Supply Voltage

20V – 40V

Supply Current

Standby Current : 285uA (typical)

Depth: 25mm

LED on : 2.8mA (typical)
Contact Rating

3.21.3

2A 30Vdc
0.6A 120Vac (not permitted by AS / NZS standards)
0.3A 240Vac (not permitted by AS / NZS standards)

RIM800 FIELD WIRING

The field wiring is shown in Figure 3.7.

PSU
Normally
DeEnergised
Load

Normally
Energised
Load

ANALOG LOOP

PREVIOUS
DEVICE

NEXT
DEVICE

TB2

TB1
L+ L- L+ L- O+ O-

N/O COM N/C
RIM800 RELAY MODULE

Make no connection to O+ and O- terminals

Figure 3.7 RIM800 Field Wiring

Issue 1.5

24 March 2006

Page 3-43

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.21.4

Document: LT0273

MX4428 PROGRAMMING OPTIONS - RIM800

The mode selects the control source for the RIM800 output. By default (mode = 4) the
output follows the logical relay. However if the mode is 0 then the output is controlled by the
corresponding circuit alarm state.

Parameter
Mode

Description
Value
0
4

Description
Controlled by Circuit Alarm
Controlled by Relay

Default
4

P0
P1
P2
P3
P4
P5
P6

Page 3-44

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.22

SNM800 SOUNDER NOTIFICATION MODULE

3.22.1

GENERAL

The SNM800 Sounder Notification Module is suitable for relay outputs which require
supervision of the load wiring and optional supervision of the DC power supply (if any).
When inactive, a reverse polarity supervision voltage is applied to the load wiring. The load
devices must therefore have internal or external reverse blocking diodes.
The load supervision can detect short and open circuit states on the load wiring only when
the relay is inactive.
The 24V DC supply may be supervised.
The load must be isolated from ground and all voltage sources. All inductive loads (e.g. bells
or relays) must have back-emf diodes or other noise clamping devices fitted.
Recognition of a fault condition takes about 30 seconds.

3.22.2

SNM800 SPECIFICATIONS

Dimensions

Height: 61mm

Width: 84mm

Weight

100g

Line Connections

L-, L+

Supply Voltage

20V – 40V

Supply Current

Standby Current : 450uA (typical)
LED On : 3.0mA (typical)

Output Circuit EOL

27k ohms, 0.5 watt

Contact Rating

2A 30Vdc

Depth: 25mm

Load must be isolated from ground and all supplies.

Issue 1.5

24 March 2006

Page 3-45

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.22.3

Document: LT0273

SNM800 FIELD WIRING
+ Power
- Supply
27k
0.5W
EOL

+

+

+

-

-

Power to
next
device

ANALOG LOOP

ANALOG LOOP

PREVIOUS
DEVICE

NEXT
DEVICE

L+ L- L+ L- S+ S- R+ R- I+ I- I+ I-

SNM800 SOUNDER
NOTIFICATION MODULE

Figure 3.8 SNM800 Field Wiring
It is recommended that the external supply covers only one zone, or the power wiring be
arranged so that an open circuit in the power feed cannot affect more than one zone. A loop
arrangement with supervision and a reverse-feed relay can be used to achieve this - refer to
Product Bulletin PBF0200.

3.22.4

MX4428 PROGRAMMING OPTIONS - SNM800

The mode selects the control source for the SNM800 output, load supervision, and EOL
supervision. By default (mode = 15) the output follows the logical relay, the external supply is
supervised, and the EOL is supervised.
Parameter
Mode

Description
Mode
Output Control
8
9
10
11
12
13
14
15

P0
P1
P2
P3
P4
P5
P6
Page 3-46

Cct Alarm
Cct Alarm
Cct Alarm
Cct Alarm
Relay
Relay
Relay
Relay

Monitor
Supply ?
No
No
Yes
Yes
No
No
Yes
Yes

Normal to o/c fault threshold
Normal to s/c fault threshold
Supply fault threshold

24 March 2006

Monitor
EOL ?
No
Yes
No
Yes
No
Yes
No
Yes

Default
15

221
20
200

Issue 1.5

Document: LT0273

3.23

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

LPS800 LOOP POWERED SOUNDER MODULE

3.23.1

GENERAL

The LPS800 Loop Powered Sounder Module is suitable for 24V DC outputs powered by the
MX Loop. It can supply up to 75mA at 24VDC.
When inactive, a reverse polarity supervision is applied to the load wiring. The load devices
must therefore have reverse blocking diodes.
The load supervision can detect short and open circuit states on the load wiring only when
the output is inactive.
The load must be isolated from ground and all voltage sources. All inductive loads (e.g. bells
or relays) must have back-emf diodes or other noise clamping devices fitted.
Recognition of a fault condition takes about 30 seconds.

3.23.2

LPS800 SPECIFICATIONS

Dimensions

Height: 87mm

Width: 148mm

Depth: 14mm

Weight

100g

Line Connections

L-, L+

Supply Voltage

20V – 40V

Supply Current

Standby Current : 450uA (typical)
Operated with load up to 8mA : 12mA.
Operated with load over 8mA : Load current + 4mA

Output Circuit ELD

22k ohms, 0.5 watt

Output Current Rating

75mA@24V nominal.

Voltage Drop

2V max

Note that the LPS800 has a minimum voltage drop of 2V between the line voltage and the
output terminals. When the loop voltage is less than 26V, the output voltage may be less
than 24V. At the minimum loop voltage of 20V, only 18V will be available for the sounder
devices. From this you must subtract the voltage drop in the wiring to the sounder devices to
obtain the voltage at the sounder device terminals. You must ensure the sounder devices
operate correctly at this voltage.
Alternatively you must design the loop so that the minimum voltage is higher than 20V and
sufficient to give the required voltage at the sounder terminals. Refer to section 3.2.2 for loop
voltage drop calculations.
The load must be isolated from ground and all supplies.

3.23.3

MX4428 PROGRAMMING OPTIONS - LPS800

The LPS800 is programmed as an SNM800. Refer to section 3.22.4.

Issue 1.5

24 March 2006

Page 3-47

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

22k
0.5W
ELD

+

+

+

-

-

-

MX LOOP

Document: LT0273

MX LOOP

PREVIOUS
DEVICE

NEXT
DEVICE

L+ L- L+ L- S+ S- R+ R-

LPS800 LOOP POWERED
SOUNDER MODULE

Figure 3.9 LPS800 Field Wiring

Page 3-48

24 March 2006

Issue 1.5

Document: LT0273

3.24
3.24.1

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

VLC-800MX VESDA LASERCOMPACT
GENERAL

The VLC800 is a derivative of the standard VESDA LaserCOMPACT product family, with the
primary difference that it communicates directly on the MX loop.
VESDA LaserCOMPACT detectors provide very early warning of potential fire conditions by
drawing air samples through 25mm pipe up to 80m long. Smoke is sampled through holes in
the pipe and transported to the detector by an integrated aspirator or fan. Holes are
positioned according to the application and often follow the spacing of standard conventional
point detectors. Where necessary, sampling points can be constructed using capillary
extensions.
The VLC800 alarm sensitivity can be set to between 0.005% obscuration / m and 20%
obscuration / m. A PC plugged into the VLC800 is required to set the sensitivity, to normalise
the airflow, and perform other setup functions. The sensitivity is NOT controlled at the
MX4428.
Refer to Tyco Safety Products UK publication 17A-03-VLC for further details on installing,
commissioning and servicing the VLC-800.

3.24.2

VLC800 SPECIFICATIONS

Environment:
IP Rating:
Operating Temperature:
Detector Ambient:
Sampled Air:
Relative Humidity:
Dimensions:
Height:
Width:
Depth:
Weight:
Sampling Network:
Maximum Area Coverage:
Maximum Pipe length:

Indoor Application only
IP30
-10°C to +39°C
-20°C to +60°C
10-95% non-condensing
225mm
225mm
85mm
1.9kg

800m2
80m with up to 15* holes,
or 2 x 50m with up to 9* holes per pipe
Pipe Size:
ID15 - 21mm
OD 25mm
‘*’ more holes may be used on networks designed using the VESDA Aspire
pipe modelling software.

External 24V dc:
Supply Voltage:
Current Consumption:

18 to 30V dc
Standby: 225mA
Alarm: 245mA

MX Loop:
Normal:
Non operational (VLC off):
Alarm:
Alarm with external relay:
Alarm with external LED:
Onboard relay: rated 2A @ 30V dc
Issue 1.5

300uA
300uA
300uA
dependant on the relay
3.3mA

24 March 2006

Page 3-49

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

3.24.3

Document: LT0273

MX4428 PROGRAMMING OPTIONS - VLC800

The only programmable items for the VLC800 are
1. The pre alarm threshold.
2. The source of the remote LED output.
3. The source of the onboard relay output and external relay output (they operate
together).
The VLC800 shares default values with the 814H, 814PH, and 814PHFL. However the alarm
threshold is fixed at 100 regardless of any default setting. The default pre alarm setting of 68
translates to 68% of the alarm value which although a suitable value, can be changed if
required.
Parameter

Description

Default

P0
P6

Pre Alarm Threshold
192 plus value below
Value
Relay Control

68
192

0
1
2
4
5
6
8
9
10

Circuit Alarm
Circuit Alarm
Circuit Alarm
Relay Logic
Relay Logic
Relay Logic
Point Alarm
Point Alarm
Point Alarm

Remote LED
Control
Circuit Alarm
Relay Logic
Point Alarm
Circuit Alarm
Relay Logic
Point Alarm
Circuit Alarm
Relay Logic
Point Alarm

Resulting
parameter
192
193
194
196
197
198
200
201
202

AVF may be applied to the circuit the VLC800 point maps to.

Page 3-50

24 March 2006

Issue 1.5

Document: LT0273

3.25

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

AVF / RAD / SAD / FLOWSWITCH DELAYS

AVF/RAD or SAD or FLOWSWITCH or AVF/SAD may be configured for a “circuit” and will
apply to all input devices on the circuit except CP820 devices, and MIM801 devices with
“interrupt” enabled.

3.25.1

AVF/RAD

Note that AVF is usually unnecessary on the addressable detectors as the built in filtering
already provides significant protection against false alarms. AVF provides an additional time
delay to verify that the alarm is still present at the end of the AVF delay. It operates as
follows –
Time
0
5 seconds
10 seconds
15 seconds
15 – 135
seconds
135 seconds

3.25.2

Action
Alarm detected at detector or module - not sent to MX4428.
Reset detectors (remove power) on DIM module.
Do nothing on other modules.
Remove reset to detectors on DIM module (re-apply power), and set alarm
count to 0 for DIM module (requiring count up to 6 for alarm recognition).
Resample detector or module, if still in alarm condition then alarm is
transmitted to MX4428 immediately.
Immediate recognition of alarm condition and transmission to MX4428.
If no alarm start again.

SAD

All devices on circuits set up as “SAD” at the MX4428 have the “return to normal” signalled
to the MX4428 delayed by 60 seconds. If the state goes back into alarm during this time, the
timer will be reset.

3.25.3

AVF/SAD

All devices on circuits set up as “AVF/SAD” at the MX4428 delay into alarm as per AVF/RAD
and delay out of alarm as per SAD.

3.25.4

FLOWSWITCH

All devices on circuits set up as “Flowswitch” at the MX4428 have the alarm signalled to the
MX4428 delayed by 15, 30, or 60 seconds (depending on the MX4428 programming). If the
state goes out of alarm during the delay time, the timer will be reset.

Issue 1.5

24 March 2006

Page 3-51

MX4428 MXP Engineering / Technical Manual
Device Information and Programming

Document: LT0273

THIS PAGE INTENTIONALLY LEFT BLANK

Page 3-52

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Analog Loop Design Considerations

CHAPTER 4
ANALOGUE LOOP DESIGN CONSIDERATIONS

Issue 1.5

24 March 2006

Page 4-1

MX4428 MXP Engineering / Technical Manual
Analog Loop Design Considerations

4.1
4.1.1

Document: LT0273

ANALOGUE LOOP CONFIGURATION SELECTION
LINES & LOOPS

The interface between the MXP and its addressable devices requires two wires.
The MXP has two lines (“left” and “right”) which are designed to be connected in a loop.
The LOOP configuration is generally preferred and indeed will often be mandatory for
compliance with standards as discussed below.
However the MXP can be used to connect to multiple lines in a star configuration. Dual line
mode is not supported.

4.1.2

LOOP FAULT TOLERANCE

Standards require that a line/loop fault condition cause minimal disruption to the system's
ability to detect and transmit alarms to the Fire Panel. The MXP achieves this in the
following way .....
The MXP has access to each device from both ends of the loop. The loop is normally
sourced from “left” and monitored at the “right” terminals. Disappearance of 40V power at the
“right” end, due to an open circuit FAULT on either the + or – wires, can be detected
(causing a FAULT event to be sent to the MX4428 Master) and corrected by switching the
Line driver onto the “right” terminals. The LOOP mode is therefore inherently fault tolerant to
any one open circuit on any one of the 2 wires.
However, a short circuit on the loop will, in general, cause the MXP to loose communication
with all devices. Thus it is recommended that isolator bases be used to minimise the loss
due to a short.
When designing fire alarm systems, the designer should be aware of any local statutory
requirements, as well as those of AS1670.1 and NZS4512.

4.1.3

AS1670.1 DESIGN REQUIREMENTS

Australian Standard AS1670.1 sections 3.1 and 3.2 require the analogue loop to comply with
the following:
•
•

The maximum number of actuating devices (i.e. detectors and input modules) in an
alarm zone shall not exceed 40.
A single short circuit shall not disable more than 40 devices connected to the MXP
loop/line. This means than if more than 40 devices are to be connected to an MXP, short
circuit isolators must be used. The count of 40 includes conventional detectors
connected to a DIM800 or other ancillary input device

4.1.4
•
•

NZS4512 DESIGN REQUIREMENTS

Isolator Bases must be fitted between zones (or on the first device either side of a zone
boundary) so that a single short circuit or break will affect no more than one zone.
In many cases the tones produced by the 814SB sounder base are not acceptable.
Refer to NZS4512 for detailed requirements.

Page 4-2

24 March 2006

Issue 1.5

Document: LT0273

4.2

MX4428 MXP Engineering / Technical Manual
Analog Loop Design Considerations

ANALOGUE LOOP/LINE LAYOUTS

4.2.1

LINE MODE

The MXP is designed to run in LOOP mode only. The dual line mode of the MPR is not
supported. However a star configuration can be used, refer to section 4.2.3.

4.2.2

LOOP DESIGN WITH SHORT CIRCUIT ISOLATORS

There are two main reasons for using isolator bases on the analogue loop.
(i)

When the MXP powers up a line/loop, it will only have to power up one section of the
line/loop at a time, reducing the power required by the MXP from the MX4428 supply
loop during startup.

(ii)

If the loop is shorted then the MXP will loose communication with only those devices
on the shorted section between 2 isolators. If every detector was mounted on an
isolator base, then all detectors would remain functional in the event of a single short
circuit.

Refer to Figure 4.1 for an example of loop wiring with Isolator Bases.

Issue 1.5

24 March 2006

Page 4-3

MX4428 MXP Engineering / Technical Manual
Analog Loop Design Considerations

Document: LT0273

MXP

+VE -VE +VE -VE
AL
AR
MX DETECTOR LOOP

M

L2

L1

L2

IB

L

L1 L2

L

L1

M
L

L

L

L

L

M
L2

L1

L1

M

IB

L

L1

L

L1

L

L1

L

L1

L

L1

L

L1

IB
L1 L

L1

L1
L

L1 L

L1

L

L1 L

L1

L

L1 L

L1

L1

L1

L1
L

L1 L

L1

L

L1 L

L1

L1

IB

L2

L1

M

IB

Figure 4.1 Loop with Isolator Bases
Note 1: Although it is not essential to have Isolator Bases between the MXP and the first /
last device on the loop, greater protection is provided by doing so. It is recommended that
the cable between the MXP line terminals and the adjacent Isolator Bases should be kept as
short as possible, and have no devices attached to it. These Isolator Bases could be located
at the MXP without detectors plugged into them.
Note 2: The maximum number of devices between Isolator Bases is 100 or less depending
on the devices. Refer to section 3.2.4.
Note 3: The M and L2 connections are interchangeable.

Page 4-4

24 March 2006

Issue 1.5

Document: LT0273

4.2.3

MX4428 MXP Engineering / Technical Manual
Analog Loop Design Considerations

STAR CONNECTION OF ANALOGUE LINES

It is not always necessary to connect addressable systems as loops, especially if an existing
conventional detector system is being converted to addressable detectors. As the existing
detector zone cables probably already terminate at the main panel, it is possible to connect
these in a star connection to the MXP as shown in Figure 4.2.
The two line terminals should be joined together as shown in Figure 4.2. The total length of
cable connected to the MXP should not exceed 2000m.
Because shorting the cable in one line will short out all the other lines connected to the same
MXP, it is recommended that 5BI Isolator Bases be fitted at the start of each line and then
placed every 20 - 40 devices along each line. (Refer to section 3.2.4 for the calculations to
determine where the isolator bases must be positioned.) The cabling from the MXP to the
initial Isolator Bases should be as short as possible. In fact 5BI Isolator bases without
detectors can be used at the star junction point.
Note: The Star Connection is not recommended for new installations. A loop configuration
should be used as it offers open circuit fault protection and with Isolator Bases, short circuit
protection.

4.2.4

SPURS

Both the loop topography described in section 4.2.2 and the star topography described in
section 4.2.3 can have "spurs" attached. (Spurs on a spur for the star topography.)
Any such spur should be connected to the loop or its parent spur with an isolator base.
However spurs are not recommended for new installations as an open circuit will disconnect
all detectors further away from the MXP than the open circuit, and a short circuit on a spur
will disconnect the whole spur.
In any case, to comply with standards, all the detectors on a spur should be in the same
zone.

Issue 1.5

24 March 2006

Page 4-5

MX4428 MXP Engineering / Technical Manual
Analog Loop Design Considerations

Document: LT0273

MXP

+VE -VE +VE -VE
AL
AR
MX DETECTOR LOOP

M

L1 M

L2

L2

L1

M

L1

L2

M

L1

L2

L

L1 L

L1 L

L1 L

L1

L

L1 L

L1 L

L1 L

L1

L

L1 L

L1 L

L1 L

L1

L

L1 L

L1 L

L1 L

L1

L

L1 L

L1 L

L1 L

L1

L

L1 L

L1 L

L1 L

L1

SPUR1

SPUR2

SPUR3

4 Isolator
Bases
(with or without
detectors)
Universal Bases,
Sounder Bases,
Relay Bases

SPUR4

NOTE : Total cable length < 2000m
Figure 4.2 STAR CONNECTION ON MXP

4.3

CABLE SELECTION CONSIDERATIONS

Selection of cable to implement the Analogue Loop requires specification of .....
(i)

CABLE TYPE
(i.e. construction and choice of materials)
This is determined from consideration of .....
MECHANICAL REQUIREMENTS

Page 4-6

For instance, does the application
specification, or prevailing standards, call for
fire rated, armoured, etc.
24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Analog Loop Design Considerations

ELECTRICAL REQUIREMENTS
(ii)

Different construction/materials give different
AC characteristics, noise immunity, etc.

CABLE WEIGHT
(i.e. gauge of wire used)
MECHANICALREQUIREMENTS

Does the application
specification, or prevailing standards, call for a minimum gauge
(AS1670.1 specifies a minimum of .75mm² standard, for
instance).

ELECTRICAL REQUIREMENTS

What is the minimum gauge wire that can be
used without exceeding the maximum voltage drop for the
number of devices over the required loop length.

The four areas to be considered therefore are
• AC requirements
• DC requirements
• Mechanical requirements
• Noise immunity

4.4
4.4.1

AC REQUIREMENTS
GENERAL

All common types of wiring with a total length of up to 2000m may be used. Refer to section
3.2.3.

4.5
4.5.1

DC CONSIDERATIONS
GENERAL

A maximum voltage drop of 17V is allowed on the cable from the MXP to the most distant
device. This applies both where
• the cable is driven from the “left” end only.
• the cable is driver from the “right” end only.
Refer to the calculations in section 3.2.2.

4.6

MECHANICAL CONSIDERATIONS

Electrical considerations aside, the system design should take into account mechanical
aspects such as .....
• Need for fire rated cable.
• Need for mechanical protection.

Issue 1.5

24 March 2006

Page 4-7

MX4428 MXP Engineering / Technical Manual
Analog Loop Design Considerations

4.7

Document: LT0273

NOISE CONSIDERATIONS

Although the MXP loop has been designed for minimum electrical interference, it is still
capable of both picking up and generating electrical interference. The longer the loop the
greater the potential problems. Each analogue loop must be considered on its own merits,
taking into account possible noise sources along the loop's proposed routing. Normal
engineering practice applies, such as keeping the loop wiring separate from other wiring,
especially power cables, speaker cables, leaky coaxial cable and noise sensitive cables for
audio systems.
In extreme cases it may be necessary to implement the analogue loop as a screened pair,
with the screen connected to the metal case at the MXP only.

Page 4-8

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering /Technical Manual
MXP Current Consumption

CHAPTER 5
MXP CURRENT CONSUMPTION

Issue 1.5

24 March 2006

Page 5-1

MX4428 MXP Engineering / Technical Manual
MXP Current Consumption

5.1

Document: LT0273

THEORY

The MXP current consumption is considerably higher than that of the other responders (even
higher than the MPR, in fact it can be considerably higher than the MPR depending on the
sounder load). It must be carefully considered when engineering the MX4428 responder
loop.
Use of the F4000CAL PC program is strongly recommended as it performs the following
calculations automatically.
A formula for predicting the MXP current is.....
I(mA) = (ITOT(mA) * (40V / VIN) * ( 1 / PCE) ) + (IQ(mA) * (24V / VIN))
Where .....
PCE

=

Power converter efficiency = 0.80

IQ

=

MXP quiescent current at 24V = 50mA.

ITOT

=

Total current sourced into the AL and AR terminals, which can
be calculated as shown in Section 3.2.2

VIN

=

MX4428 Responder Loop voltage

5.1.1

ALARM CURRENT

The alarm current calculated for all responders can be calculated and used to ensure that
1)
The total current to be sourced from the MX4428 does not exceed 2.0A
2)
No responder will see a supply voltage of less than 17V, allowing for the minimum
battery voltage at the MX4428 and voltage drops in the responder loop wiring.
Once MXP currents are calculated, the voltage drops around the responder loop can be
calculated. This will give a more accurate figure for the operating voltage of each MXP which
will result in a slightly different current consumption. The full calculation is an iterative
process when performed manually, and it is recommended that the PC program F4000CAL
is used.
Taking the example from section 3.2.5, where the alarm current was calculated at 221mA,
the MXP supply current at (22V) will be
I(mA) = (ITOT(mA) * (40V / VIN) * ( 1 / PCE) ) + (IQ(mA) * (24V / VIN))
= (221 * (40 / 22) * (1 / 0.8)) + (50 * (24 / 22))
= 502mA + 55mA
= 557mA.
This current, together with the load of other responders on the MX4428 responder loop, can
be used to calculate the voltage drops on the responder loop power wiring, and possibly
refine the value used for the MXP supply voltage (22V above). The calculations can be
performed iteratively until little change is evident.

Page 5-2

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering /Technical Manual
MXP Current Consumption

It is of interest to recalculate the current consumption assuming for example the supply
voltage is only 17.0V (the minimum operating voltage of the MXP). In this case the
consumption is increased to 721mA. It can be seen that if the responder loop power wiring
has too much resistance, the voltage to the responders is reduced by their current
consumption, which results in them requiring even more current and compounding the
problem.

5.1.2

QUIESCENT CURRENT

The quiescent current of all responders can be calculated and used to ensure there is
enough battery capacity and supply current at the MX4428.
The quiescent current for the MX loop is calculated as in section 3.2.2, but using the
quiescent current instead of the alarm current. Then the MXP supply current can be
calculated as described in section 5.1. Once again iterative calculations may be required to
adjust for the responder loop voltage drop.

5.1.3

HEAT LOSS

The heat loss from the MXP PCB can be calculated as follows –
W = ITOT(mA) * 40V * ( 1 - PCE) / PCE + IQ(mA) * 24V
Where .....
W

=

Heat loss in milliwatts

PCE

=

Power converter efficiency = 0.80

IQ

=

MXP quiescent current = 50mA at 24V.

ITOT

=

Total current sourced into the AL and AR terminals, which can
be calculated as shown in Section 3.2.2

Using the above figures, the equation simplifies to
W(mW) = ITOT(mA) * 10V + 1200mW
This can be calculated separately for quiescent and alarm conditions, depending on whether
quiescent or alarm figures are used to calculate IQ.
The maximum possible heat loss is 5.2 watts.

Issue 1.5

24 March 2006

Page 5-3

MX4428 MXP Engineering / Technical Manual
MXP Current Consumption

Document: LT0273

THIS PAGE INTENTIONALLY LEFT BLANK

Page 5-4

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Event Log and Status at MX4428

CHAPTER 6
EVENT LOG AND STATUS AT MX4428

Issue 1.5

24 March 2006

Page 6-1

F4000 MXP Engineering / Technical Manual
Event Log and Status at MX4428

6.1

Document: LT0273

RETURNED ANALOG VALUES

The MXP returns up to 4 different analog values per device - CV, TV, HH, and HL. The
following table details what each value means for each device type.
Type
814H

TV
ROR

814PH

CV
Temperature
Current Value
Smoke CV

814CH

CO CV

CO TV

814I

Current Value

Tracked Value

HH
History High
of Temperature SLV
HH percent*
(max% of Temp SLV,
Temp ROR SLV,
Smoke SLV)
HH percent*
(max% of Temp SLV,
Temp ROR SLV,
CO SLV)
History High of SLV

MIM800
MIM801
CP820
CIM800
DIM800
SNM800

analog i/p
analog i/p
analog i/p
analog i/p 1
analog i/p 1
EOL Supervision

LPS800

Analog i/p 0
(while not
operated)
–
Current Value

–
–
–
analog i/p 2
analog i/p 2
Supply
Supervision
Analog i/p 1
(while not
operated)
–
Fixed at 12

History High
History High
History High
Hist High (both)
Hist High (both)
History High EOL
Supervision
History High of analog
i/p 0 (while not
operated)
–
History High %*

RIM800
VLC800

Smoke TV

HL
History High of
ROR SLV
Temp CV

Temp CV

History Low of
SLV
History Low
History Low
History Low
Hist Low (both)
Hist Low (both)
History Low EOL
Supervision
History Low of
analog i/p 0 (while
not operated)
–
0

*HH percent will indicate whichever of Temperature, Rate of Rise, or Smoke/CO has been
highest, in terms of the percentage of its alarm threshold. It will be rounded to the nearest
5%, and the last digit will indicate which type it represents. A last digit of 0 or 5 indicates
smoke or CO. A last digit of 1 or 6 indicates temperature, and a last digit of 2 or 7 indicates
temperature rate of rise.
For example, 51 will indicate that temperature has been highest at 48-52% of the alarm
threshold. 65 will indicate smoke/CO has been highest, at 63-67% of the alarm threshold.
For temperature 20°C will be 0% and the alarm limit 100%.
All History High and History Low values (where used as maximum and minimum) will be
based on Step Limited values i.e. the same values as are used for alarm comparison.
However note that PreAlarm comparisons are performed using “CV”, i.e. values without Step
Limited filtering. Therefore a PreAlarm may occur even though the “History High” value is
less than the PreAlarm Threshold.

Page 6-2

24 March 2006

Issue 1.5

Document: LT0273

6.2

MX4428 MXP Engineering / Technical Manual
Event Log and Status at MX4428

FAULT AND ALARM EVENT LOG

The table below lists examples of event log items which are produced at the MX4428 panel.
Circuit / point event logging must be enabled to see the events listed below. Zone events are
not shown.
Event on MXP

Event Logged

Database tx from F4000
to MXP
Point Alarm

RSP

1

CCT
PNT
CCT
PNT
PNT
RLY
PNT

1/1
1/30
1/1
1/20
1/3
1/1
1/26

SNM800 Supply Fail

RLY
PNT

1/1
1/26

SNM800 / RIM800
checkback fail

RLY
PNT

1/1
1/24

Point Fault
Point Pre-Alarm
SNM800 wiring o/c or
s/c

DIM800 Supply Low

CCT
PNT
PNT

1/1
1/25
1/25

Point scan fail
Detector calibration fault

PNT
CCT
CCT
PNT
PNT

1/22
1/1
1/1
1/2
1/2

Loop o/c

RSP

1

Loop line A or B short or
overload
Type Mismatch

RSP

1

PNT

1/1

Event Logged on return to
normal
DATABASE TX
START
ALARM
ALARM
FAULT
FAULT
PRE-ALARM
FAULT
SUPERVISION
FAULT
FAULT
LOAD SUPPLY
FAIL
FAULT
CONTROL CB
FAIL

RSP

1

CCT
PNT
PNT
CCT
PNT
PNT
RLY

1/1
1/30
1/20
1/1
1/3
1/26
1/1

DATABASE TX
COMPLETE
ALARM CLR
ALARM CLR
FAULT CLR
NORMAL
ALARM CLR
NORMAL OFF
NORMAL

PNT
RLY

1/26
1/1

NORMAL OFF
NORMAL

PNT
1/24
(RIM800)
PNT
1/26
(SNM800)
RLY
1/1
PNT
1/25
CCT
1/1

CONTROL CB NML
NORMAL ON (or OFF)

NORMAL
FAULT
FAULT CLR
FAULT
NORMAL
LOAD SUPPLY
FAIL
NODE FAIL
PNT
1/22
NODE FAIL CLR
FAULT
CCT
1/1
NORMAL
CCT
1/1
NORMAL
FAULT
PNT
1/2
FAULT
FAULT
PARAMETER
ERROR
LOOP OPEN
RSP
1
LOOP OPEN CIRCUIT
CIRCUIT
CLEARED
LOOP SHORT
RSP
1
LOOP SHORT CIRCUIT
CIRCUIT
CLEARED
POINT TYPE
PNT
1/1
POINT TYPE OK
MISMATCH
FOREIGN DEVICE (note- re-logged after DP command)
TEST START NOT NML
FAIL SELF TEST 3 1

Foreign Device
PNT
1/3
PNT
1/2
System Test or autotest
CCT
1/1
- device not normal at
start
PNT
1/1
ALARM TEST FAIL
System Test or autotest
CCT
1/1
FAIL SELF TEST 3 1
- device alarm test fail
PNT
1/1
ALARM TEST FAIL
Zone alarm test device
fail
P1/22
LINE
Diagnostic Pollscan result -Correct point found
TYPE
P1/100
LINE
Diagnostics Pollscan result - point not found
OFF
P1/20
LINE
Diagnostic Pollscan result -Type mismatch
TYPE

1 OK LINE 2 OK LED OFF
OK
1 FAULT LINE 2 FAULT
LED
TYPE OK
1 OK LINE 2 OK LED OFF
BAD

Note “Type Mismatch” means a different device type was found at an address, from the type
programmed in the panel configuration for that address. An example of this would be a
MIM800 found at an address that is configured to have an 814PH. Refer to section 3.1.1 for
details of some device substitutions that are accepted without generating a fault.

Issue 1.5

24 March 2006

Page 6-3

F4000 MXP Engineering / Technical Manual
Event Log and Status at MX4428

Document: LT0273

THIS PAGE INTENTIONALLY LEFT BLANK

Page 6-4

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Technical Description

CHAPTER 7
MXP TECHNICAL DESCRIPTION

Issue 1.5

24 March 2006

Page 7-1

MX4428 MXP Engineering /Technical Manual
MXP Technical Description

7.1

Document: LT0273

GENERAL

The MXP has two major functions:
(i)

To provide an interface to an MX4428 responder (communications/power) loop, via
which data gathered by the MXP may be transferred to the MX4428 Master for
display, annunciation, and processing as appropriate.

(ii)

To provide an interface to the Analogue Loop. Data retrieved from the devices
connected to the Analogue Loop is processed to determine the ALARM/NORMAL/
FAULT status of each device, and this data is passed on to the MX4428 Master via
the MX4428 Loop Interface. The Analogue Loop interface also allows outputs to be
sent to those devices that support them, to initiate device tests, activate relays, etc.

The MXP is implemented as one printed circuit board (1901-213).

Page 7-2

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Technical Description

7.2

CIRCUIT DESCRIPTION

7.2.1

BLOCK DIAGRAM

A block diagram of the MXP is given in Figure 7.1.
The MXP can be divided into 4 sections:
(i)

The microprocessor and memory. This is the "heart" of the MXP.

(ii)

The power supply. The power supply produces the 40V isolated supply for the
Analogue Loop and also the 5V isolated supply for the microprocessor.

(iii)

The MX4428 Loop Interface. The Loop Interface contains the connect, disconnect
circuitry for the MX4428 Loop Power Supply and also the serial data driver circuits.

(iv)

The Analogue Loop Interface. This section contains the Loop Driver/ Receiver circuit
and the Loop Isolator circuits.

7.2.2

MICROPROCESSOR & LOGIC CIRCUITRY

The MXP is controlled by the 68302 Microprocessor CPU (U1). Connected to the CPU bus
is the FLASH (U2) which contains the MXP software, and the RAM (U3 and U4) which is
used for storing parameters and data associated with devices on the Analogue Loop.
The 68302 includes a communications processor with 3 serial ports. These are used for the
2 responder loop ports and a diagnostic port.
To reduce the number of components on the PCB, a PAL (Programmable Array Logic) (U5)
is used to generate bus signals such as RD-, L WR-, and U WR-. It also drives the status
LED and is used to read some of the DIP switches.
Both the FLASH (U2) and PAL (U5) are factory programmed for use in the MXP. However
the FLASH (U2) can easily be reprogrammed in the field.
7.2.2.1

Power On Reset & Watchdog Circuits

The power on reset consists of the DS1232 (U6), which drives the RST signal to the CPU
low when the 5V supply is below 4.6 Volts. This ensures that the CPU does not corrupt the
RAM when the 5V supply collapses, and the CPU starts up reliably when the 5V supply turns
on. The DS1232 also includes a Watchdog circuit inside, to produce a RESET if the CPU
stops running properly.
7.2.2.2

Memory

Memory addresses are decoded by the MC68302. When first powered up the FLASH
occupies the bottom 8k bytes. However the software relocates the FLASH so that the
memory addressing is as follows 000000
400000
800000
f00000

-

03ffff
47ffff
80000f
f00fff

RAM
FLASH
LED and SWITCHES via PAL
INTERNAL RAM AND PERIPHERALS

The RAM memory and PAL chip are powered by the +5VB supply, which has a supercap
(C68) to supply power when the MXP is powered down. This allows the MXP to retain its
RAM memory contents for typically 10 hours on MXP power down.
Issue 1.5

24 March 2006

Page 7-3

MX4428 MXP Engineering /Technical Manual
MXP Technical Description

Document: LT0273

Switching PSU
POWER SUPPLY
24V IN

Q22

+V

+5V ISO

U11

U10
Q17

+VS

+40V ISO

0V ISO

D36

RL3

C65.C66

0V
0V IN
0V OUT

opto
coupler

D44

24V OUT

R90
0V
0V

Connect / Disconnect

D37

RESPONDER
LOOP

U7C, U7D

MIN V

D35

RESPONDER LOOP INTERFACE
OC1

Q18, Q20

Line Drivers /
Receivers

opto
coupler

Isolation Barrier

OC5

Watchdog /
Reset
Generator

OC3
U8

U7B

OC2
opto
coupler

Q19, Q20

opto
coupler

CHNL2

opto
coupler

RL3

opto
coupler

U7A

CHNL1

Feedback

OC6

Latching
Relay
Drive

U6

Disconn In -

Data / Address

OC4

RAM
64kb / 256kb

Diagnostic
Port

68302 CPU /
Comms Processor

Pseudo RS232
Interface

U3, U4

FLASH
256kb / 512kB
U2

MICROPROCESSOR and MEMORY

U1

Nosex RX
AD1..5

Overload -

40VReset

5 bit D/A
Convertor

RL1

Relay
Drive

RL2

Q5, Q6

R76-R82

RL1

40V ISO

Overcurrent
Detector /
Shutdown
Q12, Q2, Q1,
Q4, Q13

Left

Modulator

0V ISO

Analog
(NOSEx)
Loop

Q14, Q15

RL2

ANALOG LOOP INTERFACE
Receive
Discriminator

Right
0V ISO

Q3, U13A

Sense
OC7

Return Fault

Figure 7.1 MXP Block Diagram

7.2.3

MXP POWER SUPPLY

The raw power to the board is supplied from the 24VIN terminal (via D36) or the 24VOUT
terminal (via D34), or both, depending on the Loop conditions.
This voltage "+V" is smoothed and maintained by reservoir capacitors C65, C66, and C71,
which store sufficient charge to maintain the circuitry under transient loop fault conditions.
From "+V" the following supplies are derived:

Page 7-4

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Technical Description

(i)

+VS

This is a switched version of "+V", which is switched OFF
when the loop supply falls below the voltage required for
correct operation of the MXP.

(ii)

40V ISO

A regulated, isolated 40V supply used to drive the Analogue
Loop circuitry and addressable devices.

(iii)

24V ISO

Derived from 40V ISO to power 24V relays.

(iv)

5V

Used to power the CPU and logic circuitry.

(v)

5VB

Used to power the RAM and PAL. Backed up by supercap
(C68).

Descriptions of the circuitry required to generate these power supplies follow.
7.2.3.1

+VS Circuitry

The MXP is specified to operate over an MX4428 loop supply range of 17.0V to 30.0V. The
MX4428 loop fault clearing technique relies on the fact that responders that are not powered
up "look like" a high impedance (see Section 7.2.4 for details). The circuitry is therefore
divided up into two sections, a (relatively) high current portion which becomes active only
when adequate voltage is available, and a low current portion that is continuously powered
up and whose sole purpose is to sense the loop voltage and control the enabling/disabling of
the high current circuitry. Loop voltage sensing is performed by comparator U7:C and
associated components which, in turn, operate power switch Q22 to feed +VS. Since the
voltage regulator draws peak currents up to around 5A, a FET is used for Q22, which gives a
low voltage drop for minimal control (gate) current.
D39, R12, R35, R113 ensure that +VS becomes active if the loop supply exceeds 17.0V,
with R28, R110, D38 providing about 4V of hysteresis (i.e. once switched on +VS will stay
switched on until the supply voltage drops below 13V).
7.2.3.2

40V ISO

The 40V ISO and 5V ISO supplies are produced using the switch mode power supply
controller IC U10, FET Q17, and associated components. The circuit configuration is such
that the circuit operates in flyback mode, energy being stored in L1 primary during Q17's ON
period and transferred to the two secondary windings during the OFF period.
The current into the diode of optocoupler OC6 increases rapidly as the 40V ISO voltage
passes through 40V (adjustable by means of VR1). The optocoupler OC6 controls the
feedback to U10 pin 2 which adjusts the duty cycle of the current pulses into L1's primary
and maintains regulation of 40V ISO.
R6 and C63 provide stability, essentially coupling the sawtooth from the internal oscillator to
the comparator – input, thereby making the + input a much lower gain pulse width control
than it would otherwise be. R107, R65, C38 provide over-current protection, while C34
defines the frequency of oscillation (approximately 80KHz). D41 and C77 provide a “soft
start” circuit to reduce the current taken during the startup time.
7.2.3.3

24V ISO

The 40V ISO voltage is regulated by a linear regulator consisting of Q23, D40 and
associated components. This supply is only required to supply a low current (about 30mA
max) to drive relays. The reference diode (D40) used for the 24V supply is also used as the
reference for the 40V supply.
Issue 1.5

24 March 2006

Page 7-5

MX4428 MXP Engineering /Technical Manual
MXP Technical Description
7.2.3.4

Document: LT0273

+5V ISO & +5V Batt

A second L1 secondary winding is used to produce an 8V supply, This 8V supply is poorly
regulated and may vary from 7.5V to 10V depending on the 40V ISO load. The 8V supply is
regulated by U11 to 5.2V.
This supply is then passed through D32 to produce the 5V supply for the CPU and logic
circuitry. The 5.2V supply also passes through D31, to produce +5V Batt, and this supply
contains a supercap (C68) which is used to keep this supply up after the power supply has
shutdown. R66 is used to limit the charge current to the supercap. This supply is used to
power the RAM on the MXP, and retain its contents during short (up to a few hours) power
downs.

7.2.4

MX4428 LOOP INTERFACE

7.2.4.1

Loop Disconnect Circuitry

The MXP, like all MX4428 compatible Responders, includes a DISCONNECT relay (RL3)
which is used to isolate shorts on the power supply loop.
Normally 24V power passes from one Responder to the next via the 24VIN terminal /
DISCONNECT relay / 24 VOUT terminal path, supplying power to the Responder on the way
through. D35, D37, R90 form a diode gate such that a loop short on either 24VIN or
24VOUT applies a low voltage to comparator U7:D. This generates a DISCON IN- signal to
the microprocessor which then opens the DISCONNECT relay to isolate the fault.
Depending on the time taken for the shorted section to be isolated, the power output of the
MX4428 panel may collapse completely, removing power from all responders. Therefore it is
necessary for them to respond rapidly to the DISCON IN signal and open the DISCONNECT
relay in their last dying gasps before their power supplies collapse to zero.
Generally, all Responders on the loop respond in like fashion and break the loop supply.
(Depending on the position of the short, and loop resistances, some may not open their
DISCONNECT relays.) Starting from the Responder nearest the MX4428 Master, each
Responder then makes a decision, based on the value of “MIN V” (refer to Figure 7.1)
whether to re-connect the relay or not. If MIN V is less than +V/2, the loop fault is on one of
its 24V terminals, so it will not re-close its DISCONNECT relay. If, however, MIN V is
greater than +V/2 the fault lies beyond the next Responder and it can therefore apply power
to that Responder.
The newly powered up Responder then makes a similar decision, followed by each
successive Responder up to the Responder with the loop fault on its far side which will not
close its DISCONNECT relay.
Similarly Responders on the other end of the Responder loop will close their DISCONNECT
relays, up to the Responder connecting to the section of the loop with the short circuit.
With a single short circuit, all responders will eventually be powered up (receiving power
from one end of the loop or the other), however the two responders on either side of the
short will have their DISCONNECT relays open.
7.2.4.2

Disconnect Relay Driver

U8A and U8B with Q10 and Q11 form a bridge circuit to drive DISCONNECT relay RL3.
This is a magnetically latched relay to save power consumption. Its position can be switched
by providing a short pulse of voltage, with the polarity of the voltage controlling the position.

Page 7-6

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Technical Description

In response to DISCON IN– going low, the microprocessor outputs a 10 msec pulse to
DISCON OUT+, which applies “0V” to RL3 pin 16 through D5 and U8 pin 2, and “+24V”
through Q11 to RL3 pin 1, thereby setting the relay contacts to their open state. When
DISCON IN+ goes low the microprocessor outputs a 10 msec pulse to CONOUT, which
applies “0V” to RL3 pin 1 through D6 and U8 pin 1, and “+24V” through Q10 to RL3 pin 16,
thereby re-setting the relay contacts to the closed state.
The DISCON IN– signal is configured as an interrupt signal to the CPU. This allows a very
fast response to it going low and ensures the relay is opened immediately. This is necessary
as a short anywhere on the responder loop will often result in the responder power
collapsing completely and the relay must be opened while sufficient charge remains in
capacitors C64, C65, C66, and C59-C62.
When neither DISCON OUT+ nor CONOUT is high, no power is applied to the coil of RL3.
7.2.4.3

MX4428 Communications Circuitry

The duplicated MX4428 communications channels are implemented using serial ports 1 and
2 of the 68302 CPU. The two transmit lines are isolated with optocouplers and buffered with
Darlington drivers. The receive circuits are protected with series resistors and shunt
diodes/capacitors, digitised with comparators, and isolated with optocouplers.
Passing messages around the loop is done entirely with software. For details of the MX4428
responder protocol and loop operation, refer to “F4000 Technical Manual - Appendix C,
Responder Communication Protocol”.

7.2.5

ANALOGUE LOOP INTERFACE

The Analog Loop (also known as MXP loop or NOSEx loop) is a two-wire circuit with the
MXP being the master and up to 200 addressable devices which are slaves.
The MXP supplies the loop power (36 - 39V dc) which powers the addressable devices and
sounder outputs. The loop + voltage is modulated with a 4V p-p dual frequency sinewave in
order to transmit data using the power wire.
Both the MXP and the addressable devices transmit and receive in the same way. The
addressable devices normally only transmit immediately after they have been polled by the
MXP, however in special circumstances they can transmit interrupt messages when they
have something urgent to send.
An example of a message on the loop is shown in Figure 7.2.

Issue 1.5

24 March 2006

Page 7-7

MX4428 MXP Engineering /Technical Manual
MXP Technical Description

Document: LT0273

Figure 7.2 Analog Loop Typical DC Level and Data Waveform
7.2.5.1

Over-Current Protection

The current drawn by the analog loop passes through current sense resistors R22 - R26.
When the voltage across these resistors exceeds approximately 0.65 volts (corresponding to
a current of just over 400mA), the collector of Q2 begins to conduct. Thermistor RV3 and
resistor R119 compensate for the fact that the VBE threshold voltage of Q2 varies with
temperature. Q2 conducting pulls the gate of Q12 to +40V and switches off Q12. The drain
of Q12 then drops to around 5V or less depending on the load on the analog loop. Q13 is
then turned on by the current through R5. Q13 then holds Q12 off even though the overload
is now gone and Q2 is no longer conducting.
This “latched” over-current situation can only be reset by the CPU. The CPU senses the
absence of 40V through the sense resistors R68 and R67 and the signal OVERLOAD–
going to a logic low. The CPU (periodically) tries to reset the over-current latch by applying a
short (approx 5 ms) pulse to “40V RESET”. This pulse turns on Q4 and Q1, which turns off
Q13. Q12 will then turn back on and stay hard on as long as there is no over-current.
For the duration of this 5 ms pulse, the latching action of the circuit is disabled, and Q12 will
act as a linear current limiter. During this time the dissipation in Q12 can be up to 40V *
400mA i.e. 16 watts. This will be an excessive dissipation for Q12 if it continues indefinitely,
which is why the reset pulse is limited to 5 ms, and indeed why the latching action is required
in the first place.

Page 7-8

24 March 2006

Issue 1.5

Document: LT0273
7.2.5.2

MX4428 MXP Engineering / Technical Manual
MXP Technical Description

Data Transmission

Each bit transmitted consists of single cycle of a sinewave of one frequency for a ‘0’ and
another frequency for a ‘1’. Each cycle is made up from a number of discreet samples, with a
5uS spacing between samples. For each sample the digitised value is output on the 68302
CPU onto signals AD1, AD2, AD3, AD4, and AD5. These signals are converted to an analog
voltage “TXDATA” by resistors R72, R73, R74, R75, R76, R77, R82, R81, R80, and R79,
which form a conventional R/2R ladder. Resistor R78 adds a DC offset of about 1.5V to the
TXDATA voltage.
Transistor Q14 is a current sink with the current controlled by the TXDATA voltage. The
varying current develops an AC voltage of 4V p-p across R85. This AC voltage is coupled
onto the gate of Q15 through C53. Q15 provides the DC power for the loop (R85 is too high
a resistance for this purpose). Q15 is a source follower, and its source follows the voltage on
its gate. The circuit of R85, Q15 and associated components can be viewed as a circuit with
about 2 - 4 volts DC drop (at 0 - 400mA load), but which has a high AC impedance
determined by R85. (Somewhat like an inductor in that it has a low DC resistance but high
AC impedance.) This supplies power to the loop but at the same time allows the MXP
transmitter (Q14) and the transmitters in the addressable devices to modulate the voltage for
data transmission.
7.2.5.3

Data Reception

The data on the analog loop is filtered by L9, L10, C30, R32, R33 and C39. C37 provides
DC blocking. D2 and D3 with C40 clamp the incoming voltage to 1.2V p-p. The filtered,
clamped voltage is amplified by Q3 and then sliced by U13A to form a 0 - 5V square wave
from the incoming sinewave. The received data is decoded into 0s and 1s by timing and
software within the CPU. Note that the slice level is about 0.6V from the peaks of the AC
voltage on the loop and not at the mid point of the AC component.
7.2.5.4

Open Circuit Fault Handling

The loop is normally driven from the AL terminals, and not driven by the AR terminals.
Optocoupler OC7 checks that power is reaching the far end of the loop i.e. the AR terminals.
If this is not the case, the CPU will close relay RL2 so that the loop is driven (power and
data) from both ends. Thus a single open circuit will result in all addressable devices still
receiving power and still being able to communicate with the MXP. Two open circuits may
result in loss of power and communications with some devices.
Periodically (every 30 seconds) when the loop is driven from both ends, the CPU will open
the right end relay to check whether the open circuit fault has gone away.
7.2.5.5

Short Circuit Fault Handling

If the CPU finds that the over-current detector described in section 7.2.5.1 is unable to be
reset or is operating repeatedly in a short time, it will try to drive the loop from one end at a
time in case the short is present only when driving from one end of the loop. In this case it
will drive the loop from the other end only. However it will try the faulty end very briefly once
every 30 seconds to see if the fault has gone away.
Note that if there are no isolator bases in the loop, the short will appear from both ends and
all devices will be effectively disconnected.
If there are isolator bases, then after an initial overload which will be reset, the isolators will
isolate the section of the loop with the short. The loop will then appear to have an open
circuit and will be driven by both ends simultaneously as described in section 7.2.5.4. Only
those devices connected to the shorted section will be disconnected.

Issue 1.5

24 March 2006

Page 7-9

MX4428 MXP Engineering /Technical Manual
MXP Technical Description

Document: LT0273

In the event that there are isolator bases installed, but there is a short on the section of loop
between the MXP and the first (or last) isolator, the MXP will detect the short and drive the
loop only from the opposite end. Every 30 seconds it will very briefly try reconnecting the
faulty end to see if the fault has gone away. This reconnection must be very brief (if the short
is still present), as it will cause the loop voltage to collapse, and the voltage must be restored
quickly enough so that the addressable devices retain enough charge in their power supply
filter capacitors and do not reset.

7.3

MXP ADJUSTMENTS

None of these adjustments should require changing in the field, unless PCB components
have been changed.

7.3.1

40V ISO SUPPLY VOLTAGE ADJUSTMENT

Disconnect all circuits from the analog loop terminals. Connect 24V to the responder loop
power terminals. Adjust VR1 so that the voltage measured between TP16 “40V ISO” and
TP15 “0V ISO” is 40.0V + / – 0.5V.

7.3.2

TX DATA VOLTAGE ADJUSTMENT

Disconnect all circuits from the analog loop terminals. Adjust VR2 so that the AC signal
voltage measured with an oscilloscope between TP3 “LINE” and TP15 “0V ISO” is 4.0V 4.8V p-p.
Refer to Figure 7.2 for an example waveform. Note that that waveform was captured with an
analog loop and some addressable devices connected and so the measured voltage is
slightly less than that specified.
Note that the MXP will need to be connected to an MX4428 FIP, or standalone mode
activated, for any data to be transmitted.

7.3.3

40V ISO SUPPLY CURRENT LIMIT ADJUSTMENT

Disconnect all circuits from the analog loop terminals. Connect 24V to the responder loop
power terminals. Apply a slowly increasing load current to the loop terminals and check at
what current the overload circuit operates (i.e. current and voltage drop to zero before being
restored by the software - this may happen repeatedly). The overload should occur at a
current of 415mA to 430mA. If it is over this range snip out one of the resistors R22 - R25. If
it is under this range, re-insert one of these resistors (R22 and R23 are 22Ω and R24 and
R25 are 47Ω). Repeat the procedure as required.

Page 7-10

24 March 2006

Issue 1.5

Document: LT0273

7.4

MX4428 MXP Engineering / Technical Manual
MXP Technical Description

MXP LED INDICATIONS

The status LED (LD1) on the MXP board indicates the following conditions –
Indication
2 quick flashes every 2
seconds
1 quick flash every 2
seconds
7 flashes then a pause,
repeating.
Each of the 7 flashes
indicates a particular fault
is present when the flash is
long, or not present when
the flash is short.
Continuous very rapid
flashes

Issue 1.5

Condition
The MXP is normal and polled by the MX4428 panel.
The MXP is normal apart from NOT being polled by the
MX4428 panel.
1st flash : Device polling is stopped due to a configuration
download from the MX4428 panel.
2nd flash : One or more configured devices is not responding.
3rd flash : The MXP is not being polled by the MX4428 panel.
4th flash : The responder loop power relay has been opened
due to a short on one side of the MXP.
5th flash : The detector loop is open circuit.
6th flash : The detector loop is shorted on "left" terminals.
7th flash : The detector loop is shorted on "right" terminals.
The MXP has just powered up. This phase should only last a
couple of seconds.

24 March 2006

Page 7-11

MX4428 MXP Engineering /Technical Manual
MXP Technical Description

7.5
PART NUMBER.
PA0893
CA0001
CA0002
CA0004
CA0005
CA0009
CA0010
CA0013
CA0016
CA0021

Document: LT0273

PARTS LIST
DESCRIPTION
PCB ASSY,1901-213,F4000 MXP RESPONDER
CAP,CERAMIC,10P,50V
CAP,CERAMIC,15P,50V
CAP,CERAMIC,68P,50V
CAP,CERAMIC,100P,50V
CAP,CERAMIC,2N2,50V
CAP,CERAMIC,4N7,50V
CAP,CERAMIC,22N,40V
CAP,CERAMIC,47P,50V
CAP,CERAMIC,1N,100V,P2.54MM

QTY/ASSY REF DESIG
1.0000
2.0000
1.0000
1.0000
1.0000
2.0000
2.0000
1.0000
6.0000

CA0022
CA0023

CAP,CERAMIC,10N,63V,P2.54MM
CAP,CERAMIC,MONOLITHIC,100N,50V,P2.54MM

CA0201
CA0202
CA0206
CA0211
CA0218
CA0235
CA0327
CA0328
CA0330
CA0331
CA0630
CA0634
CA0635
CL0453
CN0063
CN0151
CN0360
CN0475
CN0476
CN0543
CR0019
DD0003
DD0004
DD0005

CAP,ELECTRO,RADIAL,1U,50V,D5mm,H12mm,P2mm
CAP,ELECTRO,RADIAL,2U2,50VMIN,DXL 6.5 X12MM MAX
CAP,ELECTRO,RADIAL,10U,63V MIN,6.5 x 12 MAX
CAP,ELECTRO,RADIAL,100U,16V
CAP,ELECTRO,RADIAL,220U,63V,D10.5MM,H22M,P5MM
CAP,ELECTRO,RADIAL,470U,35V,D10.5mm,H20mm,P5mm
CAP,POLYESTER,10%,P5mm,L7.5xT2.5xH6.5mm,10N,100V
CAP,POLYESTER,10%,P5mm,L7.5xT2.5xH6.5mm,100N,63V
CAP,POLYESTER,10%,P5mm,L7.5xT2.5xH6.5mm,47N,63V
CAP,POLYESTER,10%,P5mm,L7.5xT2.5xH6.5mm,1N,100V
CAP,SUPER CAP,0.22F,5.5V
CAP,POLYESTER,10%,P5mm,L7.5xT3.5xH8.0mm,10N,400V
CAP,ELECT,330U,35V,LOW ESR,D10mm,P5mm,H16mm
COIL,L453,F4000 MXP,ISOLATED PSU,RM8 CORE
CONNECTOR,IC SOCKET,20 PIN
CONNECTOR,MOLEX,41761-4,MALE
CONNECTOR,TERMI-BLOCK,VERT,4.0sqmm,5mm,4 WAY
CONNECTOR,HEADER,0.1",SIL,6mm PIN,2 WAY
CONNECTOR,HEADER,0.1",SIL,6mm PIN,3 WAY
CONNECTOR,MINI JUMP WITH TAG,3 AMP
CRYSTAL,16.000MHz,30pF,HC49/4H
DIODE,1N4004
DIODE,1N5404
DIODE,1N4148

1.0000
1.0000
5.0000
1.0000
4.0000
3.0000
3.0000
3.0000
1.0000
1.0000
1.0000
1.0000
1.0000
1.0000
1.0000
1.0000
3.0000
1.0000
1.0000
2.0000
1.0000
5.0000
2.0000
8.0000

DD0027
DD0030
DD0042
DD0059
DD0060
DD0061
DD0062
DD0065
DD0073
DD0080
DD0087
DD0100

DIODE,ZENER,0W5,D2.5mm,P10mm,5%,8V2
DIODE,ZENER,0W5,D2.5mm,P10mm,5%,12V
DIODE,ZENER,1W0,D3.0mm,P10mm,5%,6V2
DIODE,SCHOTTKY,BYV10-40,1A,40V
DIODE,BAT85,SCHOTTKY,200MA,30V
DIODE,ZENER,HIGH SURGE,3W2,D3.8mm,P10mm,5%,33V
DIODE,ZENER,1W0,D3mm,P10mm,5%,24V
DIODE,ZENER,HIGH SURGE,3W2,D3.8mm,P10mm,5%,36V
DIODE,ZENER,HIGH SURGE,3W2,D3.8mm,P10mm,5%,7V5
DIODE,BIDIRECTIONAL SUPPRESSOR,BZW04-28B (OR -31B)
DIODE,MUR115
DIODE,ZENER,HIGH SURGE,3W2,D3.8mm,P10mm,5%,47V

1.0000
1.0000
1.0000
2.0000
4.0000
4.0000
1.0000
1.0000
1.0000
3.0000
2.0000
6.0000

HW0237

HARDWARE,TRACK PIN,T1565-01

IC0135
IC0258
IC0305
IC0319
IC0413
IC0447
IC0500

IC,7805CT,VOLTAGE REGULATOR,5V 4%,1.5A,TO220
IC,LM393,OP AMP,DUAL,PRECIS VOLTAGE COMPAR,LOW PWR
IC,LM385BZ 2.5,MICROPOWER VOLT REF DIODE,2.5V,TO92
IC,LP339,QUAD COMPARATOR,ULTRA LOW POWER,DIL
IC,DS1232LP,LOW POWER MICROMONITOR
IC,LM3578AN,750mA SWITCHING REGULATOR,DIL
IC,OPTOCOUPLER,SFH608-4,CTR 160% @ 1mA,DIL

1.0000
1.0000
1.0000
2.0000
1.0000
1.0000
7.0000

LD0021
NT0007
PA0899
PT0020
PT0045
RL0051

LED,3MM,RED,HIGH BRIGHT
NUT,HEX,M3,ZP
PCB ASSY,1901-213,F4000 MXP RESPONDER SMD CMP ONLY
POT,CERMET,100E,TOP ADJ,1 TURN,SPECTROL,63P
POT,CERMET,20K,TOP ADJ,1 TURN,SPECTROL,63P
RELAY,OMRON G6BU-1114C,12VDC,LATCHING

1.0000
1.0000
1.0000
1.0000 VR2
1.0000 VR1
1.0000 RL3

Page 7-12

24 March 2006

2.0000
23.0000

C45
C1 C2
C63
C39
C37
C69 C70
C41 C42
C43
C30 C31 C32 C35 C36
C38
C47 C48
C3 C5 C6 C7 C8 C9
C10 C11 C12 C13 C14
C15 C16 C17 C18 C19
C20 C21 C22 C23 C24
C25 C26
C40
C53
C49 C50 C51 C52 C77
C67
C59 C60 C61 C62
C64 C65 C66
C44 C54 C57
C27 C28 C29
C46
C34
C68
C72
C76
L1
U5
J5
J1 J2 J3
LK1
LK3
LK1 LK3
XT1
D7 D8 D9 D35 D37
D34 D36
D2 D3 D4 D5 D6 D38
D41 D43
D15
D42
D33
D31 D32
D27 D28 D29 D30
D20 D21 D22 D23
D40
D50
D19
D16 D17 D18
D24 D25
D10 D11 D12 D13 D14
D26
TP1 TP2 TP3 TP4 TP5
TP6 TP7 TP8 TP9 TP10
TP11 TP12 TP13 TP14
TP15 TP16 TP17
U11
U13
D39
U7 U8
U6
U10
OC1 OC2 OC3 OC4 OC5
OC6 OC7
LD1
Q17

17.0000

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Technical Description

RL0052
RR0001
RR0013
RR0016
RR0017
RR0022
RR0023
RR0027
RR0029
RR0032
RR0033
RR0034
RR0037
RR0038
RR0041
RR0043
RR0044
RR0045

RELAY,OMRON G6A-274P-24VDC
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1E00
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,22E0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,39E0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,47E0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,120E
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,150E
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,330E
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,470E
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,820E
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1K00
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1K20
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,2K20
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,2K70
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,4K70
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,6K8
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,8K20
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,10K0

2.0000
1.0000
2.0000
1.0000
2.0000
2.0000
1.0000
2.0000
1.0000
1.0000
4.0000
3.0000
3.0000
2.0000
1.0000
2.0000
3.0000
23.0000

RR0047
RR0048
RR0049
RR0051
RR0053
RR0054
RR0056
RR0057

RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,15K0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,18K0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,22K0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,33K0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,47K0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,56K0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,82K0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,100K

1.0000
3.0000
2.0000
5.0000
1.0000
2.0000
1.0000
10.0000

RR0058
RR0059
RR0060
RR0061
RR0062
RR0065
RR0069
RR0071
RR0072
RR0077
RR0085
RR0740

RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,120K
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,150K
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,180K
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,220K
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,270K
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,470K
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1M00
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1M50
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1M80
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,10M0
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1E80
RESISTOR,0.25W,1%,100PPM,D2.5mm,P10mm,20K

3.0000
5.0000
2.0000
3.0000
1.0000
3.0000
4.0000
1.0000
2.0000
1.0000
1.0000
6.0000

RR0767
RR0775
RR0802
RR0803
RR0810
RR0862
RR0865
RR0887
RR0918
RR0926
SC0041
SF0243
SU0198
SU0204
SW0005
SW0155
TR0029

RESISTOR,0.25W,1%,100PPM,D2.5mm,P10mm,62K0
RESISTOR,0.25W,1%,330K
***** USE RR0063 *****
RESISTOR,NETWORK,0.125W,5%,0.1" SIP,9 PIN,8+C,10K
RESISTOR,NETWORK,0.125W,5%,0.1" SIP,9 PIN,8+C,100K
RESISTOR,2W,5%,D4mm,P15mm,PR02,330E
RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1M21
RESISTOR,0.25W,1%,2M20
***** USE RR0073 *****
RESISTOR,THERMISTOR,NTC,0.5W,4K7,-4.9%/K,10%
RESISTOR,VARISTOR,130VAC,0.25W
RESISTOR,2.5W,10%,200ppm,D6.0mm,P22.5mm,0E03
SCREW,MACHINE,PH POZI,M3 X 6MM,ZP
SOFTWARE, F4000 MXP RESPONDER, V1.00 PAL
SUNDRY,CHOKE,RF,10%,D4.0mm,P15mm,2U2H,1A
SUNDRY,CHOKE,RF,10%,D4.0mm,P15mm,4U7H,820mA
SWITCH,DIL,8P1T
SWITCH,PUSHBUTTON,PCB MOUNT,NO,6mm x 6mm,L=5mm
TRANSISTOR,BC550

1.0000
2.0000
1.0000
1.0000
2.0000
1.0000
1.0000
1.0000
1.0000
1.0000
1.0000
1.0000
2.0000
7.0000
1.0000
1.0000
8.0000

TR0031
TR0049
TR0074
TR0075
TR0083
TR0084
TR0085
TR0094
TR0095
WA0026
IC0392
IC0429
PB0893
SF0242

TRANSISTOR,BC557B,PNP,50V,100mA,TO92
TRANSISTOR,MPSA13/14,NPN DARL,30V,0.5A,0.5W,TO92
TRANSISTOR,MPSA63
TRANSISTOR,MTP2955E,MOSFET,P CH,60V,8A,40W,TO220
TRANSISTOR,BST72A,MOSFET,N CH,80V,300MA,.83W,TO92
TRANSISTOR,TIP110,NPN DARL,60V,2A,TO220
TRANSISTOR,HEATSINK,TO220,VERTICAL,17degC/W
TRANSISTOR,MTP12N10,MOSFET,N CH,100V,12A,79W,TO220
TRANSISTOR,RFP15N05L,MOSFET,N CH,15A,50V,60W,TO220
WASHER,CRINKLE,STAINLESS STEEL,M3
IC,MC68302FC16,uP,132 P PQFP,16MHz,68000+SERIAL PR
IC,62256,32K X 8 SRAM,70ns,SMT 28PIN SOP,LOW POWER
PCB BARE,1901-213,F4000 MXP RESPONDER
SOFTWARE, F4000 MXP RESPONDER, V1.00 FLASH BOOT

5.0000
2.0000
2.0000
2.0000
1.0000
2.0000
1.0000
1.0000
1.0000
1.0000
1.0000
2.0000
1.0000
1.0000 U2

Issue 1.5

24 March 2006

RL1 RL2
R84
R22 R23
R92
R24 R25
R66 R85
R93
R32 R33
R64
R119
R16 R47 R63 R65
R100 R102 R120
R88 R89 R90
R8 R10
R91
R99 R101
R7 R9 R98
R48 R49 R50 R51 R52
R53 R56 R57 R58 R59
R60 R61 R62 R70 R71
R79 R80 R81 R82 R87
R115 R116 R117
R43
R67 R78 R94
R95 R104
R17 R18 R19 R20 R118
R54
R31 R86
R103
R3 R4 R5 R6 R12 R14
R15 R21 R34 R69
R112 R121 R122
R27 R28 R29 R30 R36
R68 R83
R11 R123 R124
R111
R40 R41 R42
R45 R46 R125 R127
R126
R37 R38
R1
R26
R72 R73 R74 R75 R76
R77
R113
R35 R110
RN1
RN2
R108 R109
R39
R44
RV3
RV2
R107
Q17
U5
L9 L10
L2 L3 L4 L5 L6 L7 L8
SW1
SW2
Q3 Q4 Q5 Q6 Q7 Q9
Q10 Q11
Q1 Q2 Q8 Q13 Q16
Q18 Q19
Q20 Q21
Q12 Q22
Q24
Q14 Q23
Q17
Q17
Q15
Q17
U1
U3 U4

Page 7-13

MX4428 MXP Engineering /Technical Manual
MXP Technical Description

Document: LT0273

THIS PAGE INTENTIONALLY LEFT BLANK

Page 7-14

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Diagnostic Terminal

CHAPTER 8
MXP DIAGNOSTIC TERMINAL

Issue 1.5

24 March 2006

Page 8-1

MX4428 MXP Engineering /Technical Manual
MXP Diagnostic Terminal

8.1
8.1.1

Document: LT0273

MXP DIAGNOSTIC TERMINAL OPERATION
INTRODUCTION

The MXP provides diagnostic functions via its serial port (J5) with a terminal or PC
connected. Commands may be entered which :
•
•
•
•
•
•

Display the analogue values (Raw values, Filtered values, etc) of selected devices.
Select devices for such display.
Display and reset error counters.
Determine all the devices and their types, as seen from each end of the loop.
Change an addressable device’s address.
Perform advanced diagnostics.

The MXP diagnostic serial port operates at 19200 baud, 8 data bits, no parity, 1 stop bit. A
3-wire cable is needed and it is wired the same as the MX4428 FIP programming terminal
cable. This needs either a DB9 or DB25 connector and can be ordered as fully assembled
cables using part numbers LM0042 (DB25) and LM0041 (DB9).
To utilise the colour logging facility an ANSI terminal emulator mode is required. Hyperterm
and Accuterm are suitable for Windows and Procomm is suitable for DOS. For simple
applications where logging to disk and scroll-back are not required mxpprog32 can be used
with Windows and mxpprog can be used with DOS – these are included in SF0250.

8.1.2

MENU OF COMMANDS

To see the menu of commands available, type H  HE or HELP .
Currently, this will produce the following***
MXP monitor version 1.02 (c)2000
***
H
: this help
AH
: advanced help
-------- Point Logging Commands ------------CO
: Colour toggle (requires ANSI terminal emulation)
SP n m : select points n to m, n&m optional
SP
: show selected points
SPA
: select all points
CP n m : clear points n to m, n&m optional
CPA
: clear all points
P
: alternate for SP
-------- General Diagnostic Commands -------ST
: Display General Status
STANDALONE n : standalone operation, heat threshold=n
-------- NOSEx loop diagnostics ------------TC
: NOSEx comms error count display
EC n m : NOSEx comms detailed error count display
RS
: NOSEx comms error count reset
DP
: Do diagnostics poll
CA x y : Change address of device old address x to new address y

8.1.3

SELECTING POINTS FOR MONITORING

Before the MXP can display analog values received from points, the user must select the
points to be monitored (i.e. include in the monitoring list). This is done using the following
commands –
Page 8-2

24 March 2006

Issue 1.5

Document: LT0273
SPA
SP nnn
P nnn
SP nnn mmm
P nnn mmm
CPA
CP nnn
CP nnn mmm
SP

MX4428 MXP Engineering / Technical Manual
MXP Diagnostic Terminal
Adds all points to the list of points to be monitored.
Adds point nnn to list.
Adds point nnn to list
Adds points nnn to mmm.
Adds points nnn to mmm.
Clears all points from monitoring list.
Clears point nnn from list.
Clears points nnn to mmm from list.
Displays all points selected to be monitored (i.e. in monitoring list)

The values nnn and mmm must be in the range of 1-200.
Note that if more than about 50 points are monitored at once, the serial output may not be
fast enough and some data may be discarded.
If it is not required to monitor any points be sure to deselect all points (CPA).
Monitoring a large number of points may have a detrimental effect on processing
time. Therefore enter the CPA command before disconnecting the laptop after
monitoring points.

8.1.4

DISPLAYING DEVICE ANALOGUE VALUES - CV, TV, ETC

Once points have been selected for display, the MXP will display at least one line for each
selected point, each time the point replies to a poll (or sends an interrupt message).
For those devices with two sensors (814PH, 814CH) with both sensors configured, two lines
will be displayed – one line for temperature and another line for smoke or CO.
Colour logging may be selected with the “CO” command to make the displayed log clearer.
Green is used for heat sensors, yellow for photo sensors, magenta for CO sensors, cyan for
ionisation sensors, and white for ancillaries. A brown/yellow background is used for values in
fault, green background for values in pre-alarm, red background for values in alarm.
An example line of the displayed values is
T=165; P= 2; HEAT= 20; Fl= 20; SL= 20; RoR= 0; SLRoR= 0
T=xxxx refers to the time in seconds. It recycles back to 0 after 4290 seconds.
P=xxx refers to the point number (1 .. 200).
The format is designed to be both human readable and suitable for capturing and importing
into a spreadsheet. In the latter case, it is suggested that “delimited” text import is used, with
“=” and “;” being used as delimiters.
The following paragraphs describe the parts of the log specific to each device type.
8.1.4.1

Heat Sensor of 814H, 814PH, and 814CH

T=165; P=

2; HEAT= 20; Fl= 20; SL= 20; RoR= 0; SLRoR= 0

HEAT=xxx gives the raw value received from the detector converted to °C.
Fl=xxx gives the filtered temperature (CV) in °C. This is the value which is compared with the
threshold to decide if a pre-alarm exists.
SL=xxx gives the filtered and slope limited temperature (SLV) in °C. This is the value which
is compared with the threshold to decide if an alarm exists. This item will not be displayed if
there is no fixed temperature alarm configured, e.g. if the heat sensor is used only to
enhance the smoke or CO.

Issue 1.5

24 March 2006

Page 8-3

MX4428 MXP Engineering /Technical Manual
MXP Diagnostic Terminal

Document: LT0273

RoR=xx gives the rate of rise in °C/minute. This is the value which is compared with the
threshold to decide if a rate of rise pre-alarm exists, and the value which is used to
“enhance” smoke or CO processing. This item will not be displayed if there is no rate of rise
alarm configured and there is no enhancement of smoke or CO.
SLRoR=xx gives the slope limited rate of rise in °C/minute. This is the value which is
compared with the threshold to decide if a rate of rise alarm exists. This item will not be
displayed if there is no rate of rise alarm configured.
8.1.4.2

Photo Sensor of 814PH

T=165; P= 1; OPT= 26; Cal= 32; TV= 23; CV-TV= 3; SL-TV= 3
OPT=xxx gives the raw value received from the detector (0 .. 255).
Cal=xxx gives the “calibrated” value (i.e. the raw value adjusted to compensate for the
varying outputs of different detectors with the same smoke level).
TV=xxx gives the tracked value (or long term average pedestal), i.e. the value which is
assumed to be the output of the detector in clean air.
CV-TV=xxx gives the filtered calibrated value less the clean air value (TV). CV-TV is the
value which is compared with the threshold to decide if a pre-alarm exists.
SL-TV=xxx gives the filtered and slope limited value less the clean air value (TV). SL-TV is
the value which is compared with the threshold to decide if an alarm exists.
8.1.4.3

Carbon Monoxide Sensor of 814CH

T=165; P= 2;
CO= 25; Cal= 25; TV= 30; CV-TV= -4; SL-TV= -4
CO=xxx gives the raw value received from the detector (0 .. 255).
Cal=xxx gives the “calibrated” value (i.e. the raw value adjusted to compensate for the
varying outputs of different detectors with the same CO level).
TV=xxx gives the tracked value (or long term average pedestal), i.e. the value which is
assumed to be the output of the detector with no CO present. (Note that as this value is
measured in the factory and stored in the detector then not subsequently adjusted, it is a
constant for each detector.)
CV-TV=xxx gives the filtered calibrated value less the zero CO value(TV). CV-TV is the
value which is compared with the threshold to decide if a pre-alarm exists.
SL-TV=xxx gives the filtered and slope limited value less the zero CO value (TV). SL-TV is
the value which is compared with the threshold to decide if an alarm exists.
8.1.4.4

814I Ionisation Detector

T=165; P= 20; ION= 74; TV= 74; CV-TV= 0; SL-TV= 0
ION=xxx gives the average of the two raw values received from the detector (0 .. 255).
TV=xxx gives the tracked value (or long term average pedestal), i.e. the value which is
assumed to be the average of the two detector sensors in clean air.
CV-TV=xxx gives the filtered calibrated value less the clean air value(TV). CV-TV is the
value which is compared with the threshold to decide if a pre-alarm exists.
SL-TV=xxx gives the filtered and slope limited value less the clean air value (TV). SL-TV is
the value which is compared with the threshold to decide if an alarm exists.
8.1.4.5

MIM800 Mini Input Module

T=165; P= 21; MIM=100
MIM=xxx gives the raw value received from the module.
8.1.4.6

MIM801 Mini Input Module

T=165; P= 30; MIM801=131
MIM801=xxx gives the raw value received from the module.

Page 8-4

24 March 2006

Issue 1.5

Document: LT0273
8.1.4.7

MX4428 MXP Engineering / Technical Manual
MXP Diagnostic Terminal

CP820 Manual Callpoint

T=165; P= 22;
CP=0
CP=xxx gives the raw value received from the callpoint.
8.1.4.8

CIM800 Contact Input Module

T=165; P= 23; CIM A= 90, B= 91
CIM A=xxx; B=yyy. xxx gives the raw value relating to the module input A and yyy gives the
raw value relating to the module input B.
8.1.4.9

DIM800 Detector Input Module

T=1334; P= 25; DIM A= 26;B= 26; Supply=198
DIM A=xxx;B=yyy; Supply=zzz. xxx gives the raw value relating to the module input A, yyy
gives the raw value relating to the module input B, and zzz gives that raw value from supply
monitoring.
8.1.4.10

RIM800 Relay Interface Module

T=1334; P= 24; RIM=224
RIM=xxx gives the digital inputs to the module ASIC, converted to a integer. The only bit of
use is the least significant bit - the number should be odd if the relay is activated, even
otherwise.
8.1.4.11

SNM800 Sounder Notification Module

T=1334; P= 26; SNM=255, 3
SNM=xxx, yyy. xxx gives the raw value relating to the EOL monitoring (when the relay is deactivated), and yyy gives the raw value relating to the power supply monitoring.
8.1.4.12

LPS800 Sounder Notification Module

T=1334; P= 27; LPS=151, 78
LPS=xxx, yyy. xxx relates to the voltage at the + terminal. yyy relates to the voltage at the –
terminal.
8.1.4.13

VLC800 Vesda Laser Compact

T=1334; P= 28; VLC= 17; DI=0xe0; Cal= 17; TV= 12; CV-TV= 5; SL-TV=5
VLC=xx gives the analog value received from the VLC800. DI=0xaa : aa gives the digital
inputs coded in hexadecimal, where bit 0 = "urgent fault", bit 1 = "any fault", bit 2 = "all faults
serviceable", bit 3 = "filter fault", bit 4 = "walk test". Bits 6 and 7 appear to be always 1s.

8.1.5

ST (STATUS COMMAND)

The ST command gives a self explanatory synopsis of the status of the MXP, including the
version number and details of the software programmed into the Flash IC.
>>ST
MXP Version 1.02, compiled 15:31:03 May 07 2001
Polling Running
All NOSEx devices responding
Being polled by F4000
Responder Loop Disconnect Relay : Connected (Normal)
NOSEx loop OK
1309 polling cycles since power-up / database load
0 detector/ device leds on

Issue 1.5

24 March 2006

Page 8-5

MX4428 MXP Engineering /Technical Manual
MXP Diagnostic Terminal

8.1.6

ANALOG LOOP DIAGNOSTICS

8.1.6.1

TC Command (Total Counts)

Document: LT0273

This command gives totals of node failures and powerups on the analog loop. See the EC
command to get values broken down to individual devices.
>>tc
Transmit echo reception fail count 5
Total reply fail count 191
Total device powerups 0
“Transmit echo reception fail count” indicates the number of times the MXP has been unable
to receive its own transmission on the analog loop. This should normally increment only
when the loop is subjected to abnormal events, e.g. shorts. This value is not cleared when
the MXP powers up, it is only cleared by the RS command.
“Total reply fail count” increments when a device does not reply to a poll, but has not already
been deemed to have failed. When a device is removed this value will increment by 12. This
value is not cleared when the MXP powers up, it is only cleared by the RS command.
“Total device powerups” increments when a device powers up. This should normally
increment by one for each device when the loop first powers up, and by one each time a
detector is plugged into a base with the loop powered up. If it increments at other times it is
indicative of a problem which requires investigation. This value is set to zero when the MXP
powers up.
8.1.6.2

EC Command (Error Counts)

This command gives total error counts as per the TC command, and then also gives the
reply fail counts for individual devices, and an indication of whether each device is deemed
to be in “scan fail”. These individual counts are not cleared when the MXP powers up, but
are reset by the RS command.
This command is also useful to determine which points are configured and what their type is.
>>ec
Transmit echo reception fail count 5
Total reply fail count 191
Total device powerups 0
Individual reply fail counts...
Point
1
Photo/Heat,
17 Scan Fail
Point
2
CO/Heat,
0
Point
3
Heat Only,
0
Point 20
Ionisation,
0
Point 21
MIM,
0
Point 22
CP,
0
Point 23
CIM,
54
Point 24
RIM,
54
Point 25
DIM,
24
Point 26
SNM,
54
8.1.6.3

RS Command (Reset)

This command resets (sets to zero) all the counters displayed by the TC and EC commands.

Page 8-6

24 March 2006

Issue 1.5

Document: LT0273
8.1.6.4

MX4428 MXP Engineering / Technical Manual
MXP Diagnostic Terminal

DP Command (Diagnostic Poll)

This command lists all the devices found (irrespective of the MX4428 programming) by
issuing a command to each side of the loop (left and right) which requests all devices to
identify themselves. Thus it can be used to find what devices are present on the loop and
which devices are found from each end, if the loop is broken or isolator bases have opened.
This can help identify which section of the loop cable is broken or shorted.
It will list devices found with any address including addresses above 200. If two or more
devices are present with the same address they will usually be detected, however their
replies may collide resulting in neither being detected. Therefore a second attempt is made
on each line in order to maximise the chance of locating multiple devices with the same
address. On the second attempt, only devices not found on the first attempt are displayed.
This command is a local version of the MX4428 DP command.
>>dp
>>Diagnostic Pollscan line 1
Scan attempt 1
Adr 2 : CO/Heat
Adr 3 : Heat Only
Adr 20 : Ionisation Foreign (not programmed)
Adr 21 : MIM
Adr 22 : CP
Adr 23 : CIM
Adr 24 : RIM
Adr 25 : DIM
Adr 26 : SNM
Scan attempt 2
Diagnostic Pollscan line 2
Scan attempt 1
Adr 2 : CO/Heat
Adr 3 : Heat Only
Adr 20 : Ionisation
Adr 21 : MIM
Adr 22 : CP
Adr 23 : CIM
Adr 24 : RIM
Adr 25 : DIM
Adr 26 : SNM
Scan attempt 2
Diagnostic pollscan complete
The DP command will note as “foreign” any devices which are found but not currently
programmed. However it will not display devices which are programmed but not found.
Other messages may be given, e.g. “Duplicate Device”, “Unknown Type”, “Used as Heat
only”, “Used as MIM”, “Type Mismatch”.
8.1.6.5

CA Command (Change address)

The change address command may be used to change the address of a single device (the
first number) on the analog loop to a new address (the second number). If devices are
added one at a time, this command may be used to assign their addresses instead of using
the programming tool. New devices from the factory normally have an address of 255.
Both new and old addresses may be any number greater than 0 and up to 255. Addresses
between 201 and 255 will be inaccessible to the MX4428.
Issue 1.5

24 March 2006

Page 8-7

MX4428 MXP Engineering /Technical Manual
MXP Diagnostic Terminal

Document: LT0273

>>ca 20 100
Re-address device 20 to 100 ?y
Verify OK
The MX4428 configuration is not altered by this command.
If there is no device with the old address, or if there is already a device with the new
address, an error message will be displayed and the change will not be made.
Normal polling resumes when the command is completed.

8.1.7

ADVANCED COMMANDS

The following commands are available for specialised purposes. Use these commands only
as instructed by Tyco Safety Products Christchurch.
>>ah
Advanced diagnostic commands.
Use these commands only as instructed by Tyco Safety Products
Chrsitchurch
------RD
MEM
TASK
STACK

General ----------------------------------: relay diagnostics toggle
: memory diagnostics menu
: display task times
: display stack free space

STANDALONE a b : standalone operation, heat threshold=a, step limit=b

------- Point Record diagnostics -----------------PR n
: show point n record
NR
: show next record
LR
: show last record
AR
: show next assigned record
SR
: show selected point records
DD
: point record description
-------- NOSEx loop/device diagnostics ------------NC
: NOSEx comms log toggle
DR d e : Read eeprom address e from device address d
DW d e x: Write x to eeprom address e of device address d
: d is in decimal, e and x in hexadecimal
FP a b x y: force points a to b analog values x,y

8.1.8

MX4428 DIAGNOSTICS

Several commands are available on the MX4428 “Analog Diagnostics” (DG then DA) menu
which affect the MXP.
These commands are as follows
FP r p
LN r p
L1 r

Set the LED of point p on responder r to flash when polled.
Turn on steady the LED of point p of responder r.
Poll all points of responder r using line 1 (“left”) only. Any failures to respond
will be treated as usual i.e. will generate “node fail” events.
L2 r
Poll all points of responder r using line 2 (“right”) only. Any failures to respond
will be treated as usual i.e. will generate “node fail” events.
P1 r p
Poll point p only of responder r using line 1 (“left”) only.
P2 r p
Poll point p only of responder r using line 2 (“right”) only.
FO, LO, or PO Any of these commands cancels all the above special functions.

Page 8-8

24 March 2006

Issue 1.5

Document: LT0273

DP r

DR r
GH r
GT r
RH r p
RT r p

MX4428 MXP Engineering / Technical Manual
MXP Diagnostic Terminal

Perform a “diagnostic poll” on responder r. This command initiates a
diagnostic poll, similar to that described in section 8.1.6.4. The results are
displayed automatically on the MXP but not the MX4428. To see the results
on the MX4428 use the DR command.
Display the results from the last DP command on responder r. (Use this
command at least 30 seconds after a DP command.)
Reset history of all points on responder r.
Reset tracked values (clean air values) of all points on responder r.
Reset history of point p on responder r.
Reset tracked value (clean air value) of point p on responder r.

The above commands are described in more detail in the F4000 Programming manual.
The remaining commands on the DA menu may display returned values from the MXP, but
have no direct affect on the MXP.

8.1.9

MXP EVENT LOG

Some events at the MXP are logged to the diagnostic terminal regardless of whether any
points are selected for display or commands entered at the MXP. These events are
generally self explanatory, and include –
• MXP Powering up (logs message and displays diagnostic help menu.)
• MXP Major state change including Initial Powerup state, Sending Learn Information,
Acquiring Database, Normal Running.
• System test and Autotest initiated from MX4428, and result thereof.
• Diagnostic Pollscan initiated from MX4428.
• Pollscan to “Learn” system configuration initiated from MX4428.

Issue 1.5

24 March 2006

Page 8-9

MX4428 MXP Engineering /Technical Manual
MXP Diagnostic Terminal

8.2

Document: LT0273

FLASH PROGRAMMING

On occasion, Tyco Safety Products Christchurch may provide a new version of the MXP
software. This software is stored in the Flash IC, U2. It can be updated in the field as
described below.

8.2.1

FILES REQUIRED

The following files will be supplied for a Flash software version update –
MXP.MXP
Flash contents in special format
FLASHPGM.S19
Flash programming program to run in MXP
MXPPROG.EXE
Flash programming program to run in PC (for DOS)
MXPPROG32.EXE
Flash programming program to run in PC (for WIN32)
All of these files should be in the same drive / directory, on a floppy disk or the hard disk.

8.2.2

PROCEDURE

1. The MXP must be powered up either from the responder loop or an external 24V power
supply.
2. Make a note of the current DIP switch settings on the MXP, then set all DIP switches
OFF.
3. Connect the PC to the MXP programming port with an F4000 programming lead.
4. If the PC is running DOS or Windows 3.x run the program MXPPROG from a DOS
prompt in the directory with the files. If you are using a COM port other than COM1
include the name of the port on the command line e.g. “MXPPROG COM2”.
5. If the PC is running any 32 bit Windows variant (95, 98, NT, ME, 2000, XP etc) run the
program MXPPROG32. (You can do this by typing MXPPROG32 from a command
prompt in the directory with the files, or by double clicking MXPPROG32.EXE in
Windows Explorer or My Computer. If you are using a COM port other than COM1 you
will need to include the port name on the command line, the easiest way to do this is
from a command prompt.)
6. Insert the WRITE ENABLE link (LK1) on the MXP.
7. Press the RESET button on the MXP.
8. The programming procedure is now automatic. A typical screen log of this automatic
procedure is shown below –
MXP Terminal / Flash Programmer. Type ESC at any time to exit
To program flash with new version ...
Switch all MXP DIP switches OFF, insert FLASH WRITE ENABLE LINK and press reset
Don't type keys while program is running (except ESC to exit if needed)
To use as a terminal ...
Just type your commands, HE for help
=====================================================
MXR Boot ROM V1.01. Address = 127, Switch 8 = 0
Valid application program in flash
BOOT : Waiting for load
********************************************************************************
********************************************************************************
********************************************************************************
***************************************************************
Loaded OK
Running from Start address (8000)
=====================================================
MXR Flash Programmer V1.11.
1 : Erase Entire Flash (all unprotected blocks)
3 : Load MXR Binary File and Program into Flash

Page 8-10

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Diagnostic Terminal

4 : Flash Information
1
Erasing, wait
Erase OK
1 : Erase Entire Flash (all unprotected blocks)
3 : Load MXR Binary File and Program into Flash
4 : Flash Information
3
FlashPgm : Waiting for load
0134d0 bytes
000000
001000
002000
003000
004000
005000
006000
007000
008000
009000
00a000
00b000
00c000
00d000
00e000
00f000
010000
011000
012000
013000
Loaded
Checksum is correct
Done, Switch MXP DIP switches normal,
remove FLASH WRITE ENABLE LINK and press reset
MXR Flash Programmer V1.11.
1 : Erase Entire Flash (all unprotected blocks)
3 : Load MXR Binary File and Program into Flash
4 : Flash Information

9. If the above does not happen, check that all the required files are present, check the DIP
switch settings and WRITE ENABLE link and try starting again from the beginning - exit
from the program MXPPROG.EXE or MXPPROG32.exe by typing  and restart it,
the press the MXP RESET button again. If there is still a problem obtain a fresh copy of
the files and try again. If the problem persists, note carefully exactly what is displayed on
the screen and contact Tyco Safety Products Christchurch.
10. Remove the WRITE ENABLE link, or insert it onto one pin only.
11. Reset the DIP switches to the original settings noted in step 2.
12. Press the reset button.

Issue 1.5

24 March 2006

Page 8-11

MX4428 MXP Engineering /Technical Manual
MXP Diagnostic Terminal

Document: LT0273

13. Check the display on the terminal emulator to ensure the program runs and the new
version is installed. An example of the output on power up is shown below. Note that
some of this may scroll off the screen, however the “MXP Monitor version x.xx ...” line
should be visible and will enable you to verify the new version. If necessary type ST
 to see the version.
=====================================================
MXR Boot ROM V1.01. Address = 99, Switch 8 = 1
Valid application program in flash
Jumping to application program

**************************************************************
MXP Version 1.02 Powered Up
Address 99
Initial Power Up State

***

MXP monitor version 1.02 (c)2000

***

(menu follows)
14. Write the new software version (1.02 in this example) on the label of the Flash IC, U2.

Page 8-12

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Processing

CHAPTER 9
DEVICE PROCESSING

Issue 1.5

24 March 2006

Page 9-1

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

9.1

Document: LT0273

EXPONENTIAL FILTER

An “exponential filter” is used to smooth values received from all detector types and remove
“noise”.
Value

IN

OUT

Time

This is a kind of moving average of recent samples, with the most recent samples given the
most weighting. The output of the filter will exponentially approach the input (like an
electronic RC filter).
OUTn = OUTn-1 + (IN - OUTn-1) / FD.
FD is the filter divisor. The bigger FD, the slower the filter.
This filter usually requires calculation using units much smaller than the units being filtered.
For instance it could use floating point arithmetic or integer arithmetic using units of 1/256 of
the “detector units”. Conversion from the calculation units back to detector units should use
rounding rather than truncation.

9.2

STEP LIMITING FILTER

“Step Limiting” is used after the exponential filter on all detector types, to reduce sensitivity
to large short term changes in input values which may represent false alarms.
Value

IN

OUT

Time

Page 9-2

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Processing

The output of the filter approaches the input with a maximum slope, or maximum step on
each sample.
ADJ = IN - OUTn-1
IF ADJ > SL THEN ADJ = SL
IF ADJ < -SL THEN ADJ = -SL
OUTn = OUTn-1 + ADJ
SL is the step limit for each sample period. The smaller SL the slower the filter.

Issue 1.5

24 March 2006

Page 9-3

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

9.3

Document: LT0273

HEAT PROCESSING
CONVERSION OF DETECTOR READING TO °C

9.3.1

The temperature readings from the detector (814H or the temperature element of an 814PH
or 814CH) are returned from input AI1 of the MX ASIC. These are converted to °C according
to the following table. This gives the closest temperature for each reading.
Rdg
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39

°C
Fault
Fault
Fault
Fault
Fault
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
3
4
5
5
6

Rdg
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79

°C
7
7
8
8
9
9
10
10
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
20
21
21
22
22
23
23
24
24
25
25
25
26

Rdg
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119

°C
26
27
27
28
28
28
29
29
30
30
30
31
31
32
32
32
33
33
34
34
34
35
35
35
36
36
37
37
37
38
38
39
39
39
40
40
40
41
41
42

Rdg
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159

°C
42
42
43
43
44
44
44
45
45
45
46
46
47
47
48
48
48
49
49
50
50
50
51
51
52
52
53
53
53
54
54
55
55
55
56
56
57
57
58
58

Rdg
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199

°C
59
59
60
60
60
61
61
62
62
63
63
64
64
65
65
66
67
67
68
68
69
69
70
70
71
72
72
73
73
74
74
75
75
76
77
77
78
79
79
80

Rdg
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239

°C
80
81
82
83
84
85
85
86
87
88
89
90
90
91
92
93
94
95
95
97
98
99
100
102
103
104
105
107
108
109
110
112
114
115
117
119
120
120
120
120

Rdg
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255

°C
120
120
120
120
120
120
120
120
120
120
120
Fault
Fault
Fault
Fault
Fault

The temperature is then processed according to Figure 9.1 to generate the various alarm
and pre-alarm conditions. The RORCV value is also used for enhancement of the smoke or
CO values when this is enabled.

Page 9-4

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Processing
PreAlarm
Threshold

Comparator
Fixed Temp PreAlarm

+

Exponential
Filter

Slope
Limiter

Raw°C

Raw
Reading

Table
Lookup

Alarm
Threshold

CV

SLV

FD1
Slower
Exponential
Filter

SL1

Subtractor

ROR
PreAlarm
Threshold

Comparator
Fixed Temp Alarm

+

Comparator

Slope
Limiter

Multiplier

+
-

ROR PreAlarm

+

RORCV
(°C/min)

FD2

ROR
Alarm
Threshold
RORSLV

Comparator
+

ROR
Alarm

SL2
PollsPerMinute
FD2-FD1

Figure 9.1 Heat Processing Diagram

Issue 1.5

24 March 2006

Page 9-5

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

9.4

Document: LT0273

PHOTO PROCESSING

9.4.1

SMARTSENSE PROCESSING

The smoke reading of the detector is returned as input AI0 from the device ASIC. Figure 9.2
shows a general view of the processing of the values received from the photoelectric sensor.
It is of interest that the value is multiplied by a factor (between 1 and 4) depending on the
factory calibration of the sensor, and again multiplied by a factor depending on the
temperature rate of rise (when “enhanced” operation is selected). In both cases the “tracked
value” is subtracted, the multiplication applied, and the “tracked value” added back in. This is
so that all scaling occurs relative to the clean air value.
When the MXP or detector powers up the clean air value or “tracked value” is initially set to
the average of the reading from the detector after about 30 seconds and the value stored in
the detector EEPROM, and then may continue to track up or down by 1 each poll for the
next 3 minutes.
When the “tracked value” is reset manually by command from the MX4428, it is set to a
value which will make CV equal to TV. Unless the calibration factor is exactly 1.0, the new
TV is not simply the same as the previous CV.
Subtractor
+
-

Enhancement Factor
derived from Heat RORCV
(1 if no enhancement)

Comparator
+
-

PreAlarm

PreAlarm Threshold
CVEnh
(CV to FIP)

Calibration

Subtractor
Raw
Value

Adder

Exponential
Filter

Subtractor

Slope
Limiter

Adder

+
-

+
Smoke Filter
Divisor

Smoke Step
Limit

Multiplier

SLV
TV = Tracked Value = Assumed Clean Air Value
Subtractor

CV

+
Very Slow Slope
Limiter
(1 step per Photo Tracking Interval)

Comparator
Alarm

+
-

Alarm Threshold

Figure 9.2 Photo Processing Diagram - SmartSense

9.4.2

SMARTSENSE ENHANCEMENT

Figure 9.3 shows the amount by which smoke readings are increased depending on the
temperature rate of rise.
The default enhancement multiplier parameter is 12. The graph (Figure 9.3) shows the effect
of this factor and also the effect of an alternative parameter of 6.
If enhancement is disabled, (or less efficiently if the enhancement multiplier parameter is set
to 0) the multiplier is exactly 1.

Page 9-6

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Processing

Enhancement Multiplier
3

Multiplier

2.5
2
Param=12

1.5

Param=6

1
0.5
0
0

5

10

15

Temperature Rate of Rise (°C/min)

Figure 9.3 Enhancement of smoke reading for temperature rate of rise

9.4.3

FASTLOGIC PROCESSING

When “FastLogic” is selected, most processing is done within the proprietary “FastLogic”
module. The internals of that module are beyond the scope of this manual.
Raw heat value
(direct from detector)
PreAlarm

Calibration

Subtractor
Raw Smoke
Value

Fuzzy Logic Module

Adder
Calibrated
Value

+
-

TV = Tracked Value = Assumed Clean Air Value
(Average of 1st reading and factory stored pedestal)

Alarm

Mode

Figure 9.4 Photo Processing Diagram - FastLogic

Issue 1.5

24 March 2006

Page 9-7

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

9.5

Document: LT0273

CO PROCESSING

9.5.1

CALIBRATION AND TEMPERATURE COMPENSATION

The CO reading of the detector is returned as input AI0 of the device ASIC. The CO
readings are adjusted depending on a calibration factor set at the factory and stored in
EEPROM.

9.5.2

“ENHANCEMENT”

Figure 9.3 shows the amount by which CO readings are increased depending on the
temperature rate of rise. (This is the same for the CO detector as the Photo detector.)
The default enhancement multiplier parameter is 12. The graph (Figure 9.3) shows the effect
of this factor and also the effect of an alternative parameter of 6.
If enhancement is disabled, (or less efficiently if the enhancement multiplier parameter is set
to 0) the multiplier is exactly 1.

9.5.3

CO PROCESSING
Subtractor

Enhancement Factor
derived from Heat RORCV
(1 if no enhancement)

Calibration

+
-

Comparator
+
-

PreAlarm

PreAlarm Threshold
CVEnh
(CV to FIP)
Subtractor
Raw
Value

Adder

Exponential
Filter

Subtractor

Slope
Limiter

Adder

+
-

+
CO Filter
Divisor

CO Step Limit

Multiplier

SLV
TV = Tracked Value = Zero CO Value
Subtractor
Constant stored
in detector eeprom

+
-

Comparator
Alarm

+
-

Alarm Threshold

Figure 9.5 CO Processing Diagram

Page 9-8

24 March 2006

Issue 1.5

Document: LT0273

9.6

MX4428 MXP Engineering / Technical Manual
Device Processing

IONISATION PROCESSING

The smoke reading of the detector is returned in two parts as inputs AI0 and AI1 of the
device ASIC. In the MXP the average value of AI0 and AI1 is used for all calculations, so
that all returned values to the MX4428 lie within the range of 0 – 255. (Note that TEPG
literature refers to the sum of the two inputs.)
The processing is shown in Figure 9.6. The tracked value is initialised by setting it to a high
value (100) when the MXP or detector powers up, and allowing the tracked value to
increment / decrement by 1 for each of the first 4 minutes.
Subtractor

Comparator

+
-

+
-

PreAlarm

PreAlarm Threshold

Exponential
Filter
Raw
Value

Slope
Limiter

Subtractor
SLV

CV

Filter Divisor

+
-

Comparator
+
-

Alarm

Step Limit
Alarm Threshold

TV = Tracked Value
= Assumed Clean Air Value
Very Slow Slope
Limiter
(1 step per Tracking Interval)

Figure 9.6 Ionisation Detector Processing

Issue 1.5

24 March 2006

Page 9-9

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

9.7

Document: LT0273

MIM800 / CIM800 / MIM801 PROCESSING

The MIM800 and CIM800 return a value which depends on the external resistance across
the contact terminals and which can be modelled by the equation –
VALUE = 226 * (150 + 3) / (150 + Rext + 3)

The MIM801 returns a value which depends on the external resistance across the contact
terminals and which can be modelled by the equation –
VALUE = 226 * (Rext + 3) / (150 + Rext + 3)
(unless Rext is open circuit, then value = 255)
(Note 150 represents an internal 150Ω resistor, 3 represents a 3Ω FET on resistance, and
226 represents (3.3V - DIODEV) / 3.3V * 255
Graphs of these values are show in Figure 9.7. Also shown are the default thresholds, and
the interpretations of the input ranges between the thresholds.
240
220

N/O : Optional S/C Fault

200
176

180

MIM801

160

N/C:
O/C Fault

Reading

140

170

N/O : Alarm

N/O :
O/C Fault
N/C :
Alarm

Normal

122

120
100

N/O :
Alarm

80

110

Normal

N/O :
O/C
50
Fault
N/C :
Alarm

N/C : S/C Fault

60

MIM800

40

40

N/O :
Optional S/C Fault

20
0
0

50

100

150

200

250

300

350

400

450

500

550

600

R

Figure 9.7 MIM800 / MIM801 Reading versus resistance
The usual parameters are as follows –

No alarm resistor
(Default)
With alarm
resistor

Page 9-10

P0
122

MIM800 / CIM800
P1
P2
50
0
176

24 March 2006

P3
110

MIM801
P4
170

P5
0
40

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
Device Processing

These are designed for the following configurations–
Device
MIM800
CIM800

MIM801

Mode
N/O
N/O
N/C
N/O
N/O
N/C

Contact R
Not used
100Ω
Not used
100Ω

EOL R
200Ω
200Ω
200Ω
200Ω
200Ω
200Ω

Max Wiring R
50Ω
10Ω
50Ω
50Ω
10Ω
50Ω

Parameters for alternative contact and EOL resistors could be derived from the graphs in
Figure 9.7.

9.7.1

ALGORITHM - MIM800, CIM800

The unverified input condition is evaluated according to the following table, depending on the
mode (N/O or N/C) and the values of parameters P0, P1, and P2.
P2=0
P0<=reading<=255
P1<=reading P3
AI1 <= P3

Condition
Supply Fault
Supply OK

Note that Parameter 3 cannot reliably be adjusted to monitor supplies of different voltages.

9.10.3

EOL AND POSITION MONITORING

Correct Relay Position
Not activated

AI0
P1 < AI0 <= 255
P2 <= AI0 <= P1
0 <= AI0 < P2
Any
Any

Activated
P1 <= AI0 < 255
0 <= AI0 < P1

Condition
Open circuit fault
Normal
Short circuit fault
No Position Fault
No Open Circuit Fault
No Short Circuit Fault
No Relay Stuck Fault
Relay Stuck Fault

Changes in these states are verified as described in section 9.22.
Issue 1.5

24 March 2006

Page 9-13

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

Document: LT0273

Both short circuit faults and open circuit faults will be logged as SUPERVISION FAULT, and
relay stuck faults will be logged as CONTROL CB FAIL. Only the first fault will be logged.
When all relay faults go away, the event logged at the MX4428 will be NORMAL OFF or
NORMAL ON as the case may be, regardless of the original fault logged.

9.11

LPS PROCESSING

9.11.1

ELD AND POSITION MONITORING

Correct Relay Position
Not activated

Activated

AI0, AI1
AI0 > 200 AND AI1 < 50
50 < AI0 <= 110
0 <= AI0 <=50
Otherwise
AI0 > 50
AI0 <= 50 AND AI1 <= 50
AI0 <= 50 AND 50 < AI1 <= 200
Otherwise

Condition
Open circuit fault
Short circuit
Relay fault
Normal
Relay Fault
Short circuit
Relay Fault
Normal

Changes in these states are verified as described in section 9.22.
Both short circuit faults and open circuit faults will be logged as SUPERVISION FAULT, and
relay stuck faults will be logged as CONTROL CB FAIL. Only the first fault will be logged.
When all relay faults go away, the event logged at the MX4428 will be NORMAL OFF or
NORMAL ON as the case may be, regardless of the original fault logged.

9.12
9.12.1

VLC800 PROCESSING
GENERAL

The VLC800 is processed like an 814PH, with the following parameters.
Tracked Value is fixed at 12.
Alarm Threshold is fixed at 100. (Corresponding to a raw value of 112).
Filter Divisor is fixed at 3.
Step Limit is 255 (so essentially there is no step limit).
PreAlarm is adjustable at the MX4428.
So the only filtering is the exponential filter with a filter divisor of 3. This gives some filtering,
but with a minimal delay.
As the alarm threshold is always 100, the current level (CV-TV) is an indication of the smoke
level in terms of % of the alarm threshold programmed into the VLC800 itself.

Page 9-14

24 March 2006

Issue 1.5

Document: LT0273

9.13

MX4428 MXP Engineering / Technical Manual
Device Processing

FILTER STEP LIMITS

Note that Step Limits are always expressed as “Units per 5 seconds”. This differs from MPR
where heat units are “units per 10 seconds”, but smoke limits are “time to alarm” (the
inverse). The MXP change results in
• Heat and smoke being consistent with each other.
• Using a constant slope, rather than a constant time to alarm, as the threshold is varied,
means that increasing the alarm threshold also means that the minimum time to alarm
will be increased which is generally what would be expected. This gave better results
with the various sensitivities of the photo detector in the SSL test room, i.e. a constant
Step Limit could be used for all sensitivities.

9.14

ZONE ALARM TEST

A zone alarm test performs a test in the detector for all detectors in a zone which are
capable of supporting it viz 814PH, 814CH, and 814I. The Detector LEDs do not operate. No
filtering is applied during remote tests and the fuzzy logic is replaced by a simple comparison
test. Any devices already in alarm, prealarm or fault, or isolated, do not partake in the test.
Failure of a capable detector to produce the expected output generates an immediate fault.
The actual alarm returned to the MX4428 goes through AVF if programmed.
The MXP does not return “Test Pass” until all alarm-capable devices in the circuit go into
alarm.

9.15

ZONE FAULT TEST

No MX detectors are capable of a remote fault test. Therefore with all detectors and devices
a fault is simulated in polling software.
“Test Pass” requires all devices in the circuit to pass.

9.16

AUTOTEST AND SYSTEM TEST

The Flash Checksum is checked. (Note also, a checksum fail on power up will result in the
MXP application software not even starting, but the MXP will await a program load via its
diagnostic port.)
Specific checking of the configuration RAM is not required as it is being continually checked
(with anomalies resulting in a download request from the MX4428).
For an autotest where remote device testing is enabled in the MX4428, and for all system
tests, all detectors which are capable of a remote alarm test are tested. The LEDs do not
operate and no alarms caused only by the remote test are returned to the MX4428. A device
with an external wiring fault or which is isolated, or in alarm or pre-alarm, is not subject the
test and is not reported. A device with a fault, other than external wiring, or which is in scan
fail scan fail, or relay checkback fail, or type mismatch, results in failure of the test (abnormal
at start). No filtering is applied during remote tests.

Issue 1.5

24 March 2006

Page 9-15

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

9.17

Document: LT0273

NON LATCHING TEST MODE

In this mode no alarms are latched, and all filtering is bypassed, however detector and
device LEDs follow the alarm status. About 10 seconds after a device goes into alarm it is
automatically “held in reset” for about 10 seconds, and then sampling starts again from the
beginning.

9.18

COMMISSION MODE

Filtering is speeded up or bypassed. AVF is bypassed.

9.19

FAST POINT TEST

A point which supports remote test is put into alarm by its remote test facility. A point which
does not support remote test is put into alarm by simulating a high reading. Filtering is
speeded up or bypassed. AVF is bypassed.

9.20

SLOW POINT TEST

A point which supports remote test is put into alarm by its remote test facility. A point which
does not support remote test is put into alarm by simulating a high reading. Filtering and
AVF operate normally.

9.21

SUMMARY OF ALL TEST MODES

Table 9-1 shows the features of the various alarm tests which may be applied to detectors
and input ancillary devices.
Note that there is no remote test facility on a 8xxH heat detector or on the heat component of
a 8xxPH or 8xxCH detector. On MX4428 there is no way to specify an alarm test on the heat
component of an 8xxPH or 8xxCH detector.

Page 9-16

24 March 2006

Issue 1.5

Document: LT0273

Fast
System
Point
test.
Test
Auto test
with test
fire
Yes on smoke / CO
(Alarm result simulated on 8xxH
No
ie Heat only detector and on
ancillary input modules)
Switches to SmartSense
2 on Smoke / CO
1 (bypassed)
As cfgd on heat
None
None
Bypassed
Bypassed
As cfgd
on DIM.
Bypassed
Bypassed
N/A
Bypassed
on analog
detectors

AutoReset

Detector test
applied
FastLogic
Filter Divisor
Enhancement
Step Limit

AVF

Detector / Anc
LED operates
Circuit / zone
goes into
alarm
Point alarm
generates
event
History high,
low updated
Tracking
updated
FIP CV
Updated
Reset
terminates test

MX4428 MXP Engineering / Technical Manual
Device Processing
Commission
Mode

Yes

Slow Point Test

Zone
Alarm
Test

Normal

Yes on smoke / CO.
Simulated 100°C on 8xxH.
Simulated alarm on
ancillaries.
As cfgd

As cfgd

As cfgd

As cfgd

None
As cfgd

As cfgd
As cfgd

As cfgd

As cfgd

No

No

No

Yes

Yes

Yes

Yes - but
zone
isolated at
FIP

Yes

When
ALL
points in
alarm

No

Yes

Yes

When alarm
condition
reached

Yes

Yes

No

No

Yes

Yes

Yes

No

Yes

No

No

No

No

Yes

No

Yes

No

No

No

No

Yes

Yes

Yes

No

No

No

Yes

Yes

Yes

Yes

N/A

No effect at MXP

Table 9-1 Test Modes Summary

9.22

ANCILLARY FILTERING

If a poll returns the alarm state, then up to 5 immediate re-polls are made. If all these are still
in the alarm state then an alarm is generated. If one of the succeeding polls is not in the
alarm state, then immediate re-polling stops, but an up-down counter will be retained for the
next poll. This counter counts up when an alarm condition is measured, and down when a
non-alarm condition is measured. So if there are 5 polls in the alarm state then 1 non alarm
the counter will be left at 4. On the next scheduled poll the counter starts from the value it
had previously, so only 2 successive polls returning the alarm condition will be required to
reach the alarm condition.
The up-down counter always counts up and down (between 0 and 6) depending on whether
an alarm condition or not is read from the detector. When the counter reaches 6 a filtered
alarm state is generated. When the counter reaches 0 a filtered non-alarm condition is
determined. An immediate re-poll is done if the last poll is in the opposite state to the filtered
state.
Ancillary faults are filtered in the same way, except that only 4 polls are needed rather than
6, and there is no immediate re-polling, 4 polls 5 seconds apart are required.

Issue 1.5

24 March 2006

Page 9-17

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

9.23
9.23.1

Document: LT0273

RESET
RESET OF ADDRESSABLE DETECTOR

For about 20 seconds after reset is applied to an addressable detector, the exponential filter
and slope limiting filter are disabled if their input values are less than their output values. In
other words their outputs will follow their inputs downwards with no filtering. However
increases in input values will be filtered as usual.
If the LED is latched on due to a previous alarm it will be turned off.
The state of any AVF applied to the detector is reset to the “no-alarm” quiescent state.
RESET has no effect on 814PH detectors operating in “FastLogic” mode.

9.23.2

RESET OF DIM MODULE

Power is removed from the attached conventional detectors for about 5 seconds. Then
power is re-applied, and sampling resumes 5 seconds later.
If the DIM module LED is latched on due to a previous alarm it will be turned off.
The state of any AVF applied to the detector is reset to the “no-alarm” quiescent state.

9.23.3

RESET OF ANCILLARY INPUT DEVICE

If the LED is latched on due to a previous alarm it will be turned off.
The state of any AVF applied to the detector is reset to the “no-alarm” quiescent state.

9.23.4

RESET OF ANCILLARY OUTPUT DEVICE

No action.

Page 9-18

24 March 2006

Issue 1.5

Document: LT0273

9.24

MX4428 MXP Engineering / Technical Manual
Device Processing

DEVICE INITIALISATION AND POLLING

The following actions are taken for each device when it powers up or when the MXP powers
up. One action is performed on (or instead of) each 5 second poll.
• If fault bit was received, use HEALTH command to verify that fault was caused by
powerup.
• Use READEE command to check type.
• Send SETALL command to select which values are returned, to set the interrupt
thresholds (if any), set the Digital Outputs required for correct operation and set the
status register for LED blink if required.
• Use READEE command to get factory calibration value for Photo and CO devices.
• Use READEE command to get factory “clean air” value for Photo and CO devices.
• Use READEE command to get the stored LED blink bit. This may require the SETALL
command to be sent again.
Once this is complete FASTAV commands will be used to read the analog inputs (FASTDI
command for RIM) on each poll, except for the occasional use of the SETOUT command to
Reset / unreset the DIM detectors and as a background refresh of digital outputs.
SETOUT commands to set changed digital outputs will be interspersed between polls, with
no request to return data.
GLOBADR commands are used to find all devices during a “Learn” initiated by the MX4428
and “Diagnostic Pollscan” initiated by the MX4428 or MXP diagnostic terminal.
(Refer to the “NOSEx SPECIFICATION” document for more details of the above
commands.)

Issue 1.5

24 March 2006

Page 9-19

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

9.25

Document: LT0273

SOFTWARE VERSIONS

The following software versions have been released for general use.
Version
1.03
1.04
(Limited
Release)
1.05
(Limited
Release)
1.06

1.07

1.09

1.10

1.11

1.12

Page 9-20

Features
First full release
Fixed failure of photo self test when using fuzzy logic with some detectors.
Fixed standalone mode did not work if no valid database.
Added "typewrite" command to easily reprogram CO self test pulse length.
Fixed failure of CO self test with new detectors, and subsequent other faults
due to the detector powering down.
Fixed failure of photo self test when using fuzzy logic with some detectors.
Fixed standalone mode did not work if no valid database.
Added "typewrite" command to easily reprogram CO self test pulse length.
Fixed failure of CO self test with new detectors, and subsequent other faults
due to the detector powering down.
Added automatic detection of CO detectors with insufficient self test pulse
length (as stored in detector eeprom), and correction thereof.
Fixed threshold used for remote test of photo detector using fuzzy logic with
individual sensitivity.
Fixed reporting of scan-fail (problem introduced in 1.05).
Changed version returned to MX4428 from c0 to c6.
Implemented fast and slow point test, commission mode.
Fixed no scan fail fault on CH detector (introduced in V1.06)
Added support for LPS800. (Programmed as SNM800)
Changed version returned to MX4428 to c7.
Added support for Vesda VLC800.
Amended 814I remote test decision to prevent some detectors from
incorrectly failing a remote test.
Changed version returned to MX4428 to c9.
Fixed CO detector processing. Versions 1.07 to 1.09 inclusive did not apply
the "calibration factor" stored in the detector eeprom, meaning that most
detectors were less sensitive than they should have been (possibly outside
the SSL limits of +/- 50%).
VLC800 self test - moved decision point to the third poll after the "stimulus".
(The data at the previous decision point was not necessarily valid.)
Reprogrammed the eeprom containing the pulse length to the length required
for the self test
MX4428 Analog diagnostics AO command did not always cancel AS and AQ
commands. (PR was workaround.) AO now fixed.
Changed version returned to MX4428 to $ca.
DIM800 now has an option for short circuit fault
Fixed the problem that where there was only one DIM800 on the loop, and it
was the only device on the loop, it did not get processed.
Fixed the 814PHFL Fastlogic modes, in particular smoke only actually
selected heat only.
Changed version returned to MX4428 to $cb.
Fixed continual transmission of global maintenance alert on then off when a
“dirty” point was isolated. Changed version returned to MX4428 to $cc.

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

CHAPTER 10
MXP LOOP FILTER BOARD

Issue 1.5

24 March 2006

Page 10-1

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

10.1

Document: LT0273

USE OF MXP LOOP FILTER BOARD

Some field problems have occurred with the MXP detector loop picking up interference from
adjacent or nearby wiring, resulting in faults and possibly prealarms. The “MXP Loop Filter
board” (part number PA1038) is now available and it can easily be fitted to an MXP in order
to remove the interference and restore normal operation.
One or more of the following symptoms may be evident –
1. Intermittent “scan fail” faults.
2. Intermittent unexpected Prealarms.
3. The MXP diagnostic port “Total reply fail count” is much higher than expected
(normally you should get less than 1 per hour).
4. The above problems occur in time with some external event e.g. lift motors running,
radio transmitters operating etc.
Note that symptoms 1 – 3 above can also be caused by other factors e.g. the loop has too
many devices connected or is too long. The MXP Loop Filter board will not help if this is the
case.

10.2

FITTING

Remove the loop wiring from the MXP. Fit the filter board in the loop wiring terminals of the
MXP. Then fit the loop wiring to the filter board. Refer to Figure 10.1.

Figure 10.1 MXP Loop Filter Board Fitted to an MXP
Page 10-2

24 March 2006

Issue 1.5

Document: LT0273

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

Note – if you are fitting the board to an MXP in a responder box, you may need to tip the
underside of the plastic standoffs inwards to get the board to fit into the MXP board
connector easily – it will help if you rotate each standoff so that its plastic latch is pointing
away from the edge of the board. Once the board is inserted you can straighten the
standoffs before tightening the screws on the MXP loop wiring terminals.
Be sure to check that the system is operating normally, and that the problem you started with
is solved.

10.3

DIAGNOSTICS

Connect a terminal or laptop running a terminal emulator program to the MXP diagnostics
port using LM0041. Select baud 19200, no parity, 8 databits, 1 stop bit.
Enter the command RS. This will reset the error counters. Wait a few minutes. Enter TC. The
“Total reply fail count” count should be zero. Keep checking it periodically. It should not
increase by more than about 1 per hour. If there is a problem the count may increase every
few seconds. To try to correlate the errors/retries with other events you can keep typing TC
(or Control-R to repeat the last command) and see when the errors are occurring.
Alternatively to try to correlate the errors/retries with other external events you can enter the
command NC (Nosex comms log toggle) so that the Nosex comms log is enabled. Then you
will see activity on the screen in real time every time a device does not reply. (Note - one
device that should not be present is polled every 5 seconds, it should not reply and this lack
of reply is displayed on the screen). Be sure to type NC again so that the Nosex Comms log
is disabled before disconnecting the terminal.

Issue 1.5

24 March 2006

Page 10-3

MX4428 MXP Engineering / Technical Manual
MXP Loop Filter Board

Document: LT0273

THIS PAGE INTENTIONALLY LEFT BLANK

Page 10-4

24 March 2006

Issue 1.5



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0 (Windows)
Create Date                     : 2006:05:11 11:35:17+12:00
Creator Tool                    : Acrobat PDFMaker 7.0 for Word
Modify Date                     : 2006:05:30 09:44:20+12:00
Metadata Date                   : 2006:05:30 09:44:20+12:00
Format                          : application/pdf
Title                           : LT0273 MX4428 MXP ENGINEERING/TECHNICAL MANUAL
Creator                         : 
Document ID                     : uuid:07d5140e-aa0e-4e67-a4a7-5e9e52edc9e5
Instance ID                     : uuid:343b1149-d86c-4a41-a2af-8dd3d27d03f6
Has XFA                         : No
Page Count                      : 134
Page Layout                     : OneColumn
Author                          : 
EXIF Metadata provided by EXIF.tools

Navigation menu