UTC Fire and Security AA2 Field disturbance sensor for security systems User Manual 1040656A RCR90 I I P65

UTC Fire & Security B.V. Field disturbance sensor for security systems 1040656A RCR90 I I P65

Contents

Users Manual

1
PrecisionLine RCR-90
PrecisionLine
RCR-90
Dual Technology Motion Sensor
Installation Instructions
Description
The RCR-90 combines range-controlled radar (RCR) technology
with a passive infrared (PIR) system to increase false alarm
immunity by allowing it to sense human-sized objects within a
specified range. Both the RCR and PIR systems must be triggered
to set off an alarm, unless in radar-only mode.
The detector is designed to use a 12VDC power supply provided
by a UL Listed alarm control panel.
Features
The detector provides the following features:
High-security (radar-only) mode - Internal jumper allows you
to disable the PIR, and use the radar-only mode to detect
intruders faster. This mode can be used for covert installations
(mounted behind ceiling panels or walls).
Selectable range up to 90 feet (27.4m) - Internal jumper
allows radar range selection to optimize coverage.
LED indicator - A multi-color LED provides detector status.
Tamper switch - Activated when the pins on the circuit board
are removed from the terminal sockets on the base.
Selecting a Location for the
Detector
The detector can be mounted in a corner or on a flat wall. Use the
following guidelines to determine the best location to install the
detector:
Mount the detector so the expected movement of an intruder is
across the detection pattern. See Figure 2.
Mount the detector on a stable surface 8 to 12 feet (2.4 to 3.7m)
high.
DO NOT mount the detector within 2 feet (0.6m) of metallic
objects or within 5 feet (1.5m) of florescent lights.
DO NOT place objects in front of the detector that may prevent
a clear line of sight. (Not applicable in radar-only mode.)
Avoid locations that expose the detector to possible false alarm
sources such as:
– Moving or vibrating objects (fans, pulleys, conveyor belts)
– Electronic fields (electric motors, high voltage equipment)
– Water spray or corrosive environments
– Heat sources in the field of view (heaters, radiators)
– Windows in the field of view
– Strong air drafts on the detector (fans, air conditioners)
When installing multiple detectors:
– DO NOT mount detectors facing each other.
– Mount detectors at least 20 feet (6.1m) apart.
– Use shorter range settings to avoid overlapping radar coverage.
Figure 2. Coverage Pattern
Figure 1. Detector (Exploded)
BaseFront cover/electronic module
Bracket
Closing screw
10’
(3m)
10’
(3m) 35’
(11m)
50’
(15m) 90’
(27m)
80’(24m)
90’(27m)
70’(12m)
50’(15m)
50’(15m)
90’(27m)
80’(24m)
70’(12m)
60’(18m)
60’(18m)
Preliminary
August 7, 2003
2PrecisionLine RCR-90
Installing the Detector
All wiring must conform to the National Electric Code (NEC) and/
or local codes having jurisdiction.
Important: DO NOT use this device for safety
interlock applications.
To install the detector:
1. Run the security system wiring to the detector location.
2. To remove the front cover/electronic module, remove the
closing screw. See Figure 1. Then pull out on the top of the
front cover and lift off.
CAUTION
You must be free of all static electricity before
handling sensor circuit boards. Touch a
grounded, bare metal surface before touching
circuit boards or wear a grounding strap.
3. If necessary, set the jumpers on the circuit board. See Setting
the Jumpers.
4. Remove the appropriate wiring and mounting knockouts from
the back cover. The detector can be mounted on a flat wall or
in a corner. See Figure 4.
5. Pull the wires through the knockout holes and strip 1/4 inch
(6.4mm) of insulation from each wire.
6. Run each wire through the strain relief (see Figure 4) and
under the appropriate screw terminals (see Figure 3) on the
base and tighten the screws.
7. Use screws to attach the base to the wall. Use screw anchors
if necessary. See Mounting Adjustments.
8. Line up the tabs on the bottom of the front cover/electronic
module with the corresponding tabs on bottom of the base
and push the front cover/electronic module firmly down onto
the base.
9. Tighten the closing screw. See Figure 1.
10. Apply power. The green LED should light for approximately
25 seconds and then go out.
11. Walk test the coverage pattern as follows:
– Walk throughout the intended coverage area.
– Verify the detector alarms. See Understanding the LED.
Note
Most units walk test more accurately if the person
testing waits 10 seconds between tripping the unit and
walking again. This allows the detector to stabilize
between trips.
Figure 4. Detector Base
Terminal
sockets Flat wall mount
knockout
Corner mount
knockouts
Strain
relief
Wiring knockout
Flatwall mount
knockout
Corner mount
knockouts
Mounting Adjustments
Figure 5. Mounting Adjustment Bracket
Flat Wall Mount
Mount the unit using the two flat wall mount knockouts (see
Figure 4) Use the bracket to adjust the angle of coverage for
mounting on a flat wall. See Figure 5 for the best initial bracket
setting for the mounting height used. Make sure the mounting
screws are tightened before testing the unit. If you need to make
further adjustments, loosen the bottom screw, adjust the bracket,
tighten the bottom screw, and test the unit.
Corner Mount
Mount the unit using two corner mount knockouts (see Figure 4)
on one vertical side of the unit. The top corner mount knockouts
are designed with room to adjust the coverage pattern. Mount and
tighten both corner mount screws. Test the unit. If you need to
make further adjustments, loosen the top corner mount screw,
adjust the unit, tighten the top corner mount screw, and test the
unit.
12’ - one notch down
from the top
10’ - center
8’ - one notch up
from the bottom
SPR TMP TMP NO COM NC +12V GND
Figure 3. Wiring
3
PrecisionLine RCR-90
Figure 6. Circuit Board
Setting the Jumpers
The detector provides jumpers to select the detection range and
PIR and LED operation. See Figure 6.
J2 Range - Use the jumper to cover the center pin and the pin
indicating the desired range. No jumper = 90 feet (27.4m) and
under.
90 feet (27.4m) and under 80 feet (24.4m) and under
(factory default)
70 feet (21.3m) and under 60 feet (18.3m) and under
Note
You need to set J2 as close to the intended
coverage range as possible. Overshooting the
coverage area may cause false alarms.
J3 LED -
ON = LED enabled (factory default)
OFF = LED disabled
J4 PIR -
ON = Radar only enabled
OFF = PIR and Radar enabled
(factory default)
Understanding the LED
The multi-color LED located on the bottom of the detector
indicates the status of the unit as described in the following table.
In Radar-only mode:
LED Status
Red PIR and Radar detection. The detector is
in alarm and the relay has switched.
Green PIR detection only (no alarm).
Yellow Radar detection only (no alarm).
LED Status
Red Radar detection.
90’
(27.4m) 90’
(27.4m)
60’
(18.3m)
60’
(18.3m)
80’
(24.4m) 80’
(24.4m)
70’
(21.3m) 70’
(21.3m)
90’
(27.4m) 90’
(27.4m)
60’
(18.3m) 60’
(18.3m)
80’
(24.4m) 80’
(24.4m)
70’
(21.3m) 70’
(21.3m)
J3 LED
J4 PIRJ2 Range
J4
J3
J2
Specifications
Input voltage 8.5 to 18VDC (UL: 10 to 16VDC)
Typical current 23mA (LEDs off)
Maximum current 35mA
Electrical configuration Form C
Relay rating 28VDC, 100mA max.
Tamper 100ma, 40VDC
Detection range 90' (37m) x 90°
Target velocity 0.5 ft/sec to 5 ft/sec
Alarm duration 5 sec ± 10%
Mounting height 8' to 12' (2.4m to 3.7m)
Operating temperature 32° F to 122° F (0° C to 50° C)
Relative humidity 5 to 93% non-condensing
Dimensions: 3.5" (89mm) W
6.1" (155mm) H
3.1" (79mm) D
Weight 6.8 oz (193g)
Color white
Field wiring size 12-24 AWG
Microwave frequency 5.8GHz
1040656 Rev A 08/03
Product Ordering
Model Number Description
RCR-90 Dual technology, range-controlled radar, passive infrared detector with form C relay, stealth
mode, tamper contacts, 90 foot (27.4m) maximum range
www.GE-Interlogix.com
© 2003 GE Interlogix
12345 SW Leveton Drive
Tualatin, OR 97062
Phone: 503-692-4052
USA & Canada: 800-547-2556
Technical Service: 800-648-7424
FaxBack: 800-483-2495
GE Interlogi
x
Maintaining the Detector
When installed and used properly, the detector provides many
years of service with minimal maintenance. You should walk test
the detector annually to ensure proper operation.
Clean the inside of the unit with a soft-bristled brush or com-
pressed air. Clean the outside with a damp (water) cloth as
needed to keep it free of dust and dirt. Always test the unit
after cleaning.
When the cover is removed, power is interrupted to the sensor.
Once the cover has been replaced, the green LED will illuminate
for 25 seconds while the sensor warms up. After the green LED
goes off, wait one minute and walk test the sensor.

Navigation menu