UTC Fire and Security AA2 Field disturbance sensor for security systems User Manual 1040656A RCR90 I I P65

UTC Fire & Security B.V. Field disturbance sensor for security systems 1040656A RCR90 I I P65

Contents

Users Manual

1PrecisionLine  RCR-90PrecisionLine     RCR-90Dual Technology Motion SensorInstallation InstructionsDescriptionThe RCR-90 combines range-controlled radar (RCR) technologywith a passive infrared (PIR) system to increase false alarmimmunity by allowing it to sense human-sized objects within aspecified range. Both the RCR and PIR systems must be triggeredto set off an alarm, unless in radar-only mode.The detector is designed to use a 12VDC power supply providedby a UL Listed alarm control panel.Features The detector provides the following features:•High-security (radar-only) mode - Internal jumper allows youto disable the PIR, and use the radar-only mode to detectintruders faster. This mode can be used for covert installations(mounted behind ceiling panels or walls).•Selectable range up to 90 feet (27.4m) - Internal jumperallows radar range selection to optimize coverage.•LED indicator - A multi-color LED provides detector status.•Tamper switch - Activated when the pins on the circuit boardare removed from the terminal sockets on the base.Selecting a Location for theDetectorThe detector can be mounted in a corner or on a flat wall. Use thefollowing guidelines to determine the best location to install thedetector:•Mount the detector so the expected movement of an intruder isacross the detection pattern. See Figure 2.•Mount the detector on a stable surface 8 to 12 feet (2.4 to 3.7m)high.•DO NOT mount the detector within 2 feet (0.6m) of  metallicobjects or within 5 feet (1.5m) of florescent lights.•DO NOT place objects in front of the detector that may preventa clear line of sight. (Not applicable in radar-only mode.)•Avoid locations that expose the detector to possible false alarmsources such as:– Moving or vibrating objects (fans, pulleys, conveyor belts)– Electronic fields (electric motors, high voltage equipment)– Water spray or corrosive environments– Heat sources in the field of view (heaters, radiators)– Windows in the field of view– Strong air drafts on the detector (fans, air conditioners)•When installing multiple detectors:– DO NOT mount detectors facing each other.– Mount detectors at least 20 feet (6.1m) apart.– Use shorter range settings to avoid overlapping radar coverage.Figure 2.  Coverage PatternFigure 1.  Detector (Exploded)BaseFront cover/electronic moduleBracketClosing screw10’(3m)10’(3m) 35’(11m)50’(15m) 90’(27m)80’(24m)90’(27m)70’(12m)50’(15m)50’(15m)90’(27m)80’(24m)70’(12m)60’(18m)60’(18m)PreliminaryAugust 7, 2003
2PrecisionLine RCR-90Installing the DetectorAll wiring must conform to the National Electric Code (NEC) and/or local codes having jurisdiction.Important: DO NOT use this device for safetyinterlock applications.To install the detector:1. Run the security system wiring to the detector location.2. To remove the front cover/electronic module, remove theclosing screw.  See Figure 1. Then pull out on the top of thefront cover and lift off.CAUTIONYou must be free of all static electricity beforehandling sensor circuit boards. Touch agrounded, bare metal surface before touchingcircuit boards or wear a grounding strap.3. If necessary, set the jumpers on the circuit board. See Settingthe Jumpers.4. Remove the appropriate wiring and mounting knockouts fromthe back cover. The detector can be mounted on a flat wall orin a corner. See Figure 4.5. Pull the wires through the knockout holes and strip 1/4 inch(6.4mm) of insulation from each wire.6. Run each wire through the strain relief (see Figure 4) andunder the appropriate screw terminals (see Figure 3) on thebase and tighten the screws.7. Use screws to attach the base to the wall. Use screw anchorsif necessary. See Mounting Adjustments.8. Line up the tabs on the bottom of the front cover/electronicmodule with the corresponding tabs on bottom of the baseand push the front cover/electronic module firmly down ontothe base.9. Tighten the closing screw. See Figure 1.10. Apply power. The green LED should light for approximately25 seconds and then go out.11. Walk test the coverage pattern as follows:– Walk throughout the intended coverage area.– Verify the detector alarms. See Understanding the LED.NoteMost units walk test more accurately if the persontesting waits 10 seconds between tripping the unit andwalking again. This allows the detector to stabilizebetween trips.Figure 4. Detector BaseTerminalsockets Flat wall mountknockoutCorner mountknockoutsStrain reliefWiring knockoutFlatwall mountknockoutCorner mountknockoutsMounting AdjustmentsFigure 5.  Mounting Adjustment BracketFlat Wall MountMount the unit using the two flat wall mount knockouts (seeFigure 4) Use the bracket to adjust the angle of coverage formounting on a flat wall. See Figure 5 for the best initial bracketsetting for the mounting height used. Make sure the mountingscrews are tightened before testing the unit. If you need to makefurther adjustments, loosen the bottom screw, adjust the bracket,tighten the bottom  screw, and test the unit.Corner MountMount the unit using two corner mount knockouts (see Figure 4)on one vertical side of the unit. The top corner mount knockoutsare designed with room to adjust the coverage pattern. Mount andtighten both corner mount screws. Test the unit. If you need tomake further adjustments, loosen the top corner mount screw,adjust the unit, tighten the top corner mount screw, and test theunit.12’ - one notch down        from the top10’ - center8’ - one notch up      from the bottomSPR  TMP   TMP   NO   COM   NC  +12V   GNDFigure 3. Wiring
3PrecisionLine  RCR-90Figure 6. Circuit BoardSetting the JumpersThe detector provides jumpers to select the detection range andPIR and LED operation. See Figure 6.J2 Range - Use the jumper to cover the center pin and the pinindicating the desired range. No jumper = 90 feet (27.4m) andunder.90 feet (27.4m) and under 80 feet (24.4m) and under(factory default)70 feet (21.3m) and under 60 feet (18.3m) and underNoteYou need to set J2 as close to the intendedcoverage range as possible. Overshooting thecoverage area may cause false alarms.J3 LED -ON = LED enabled (factory default)OFF = LED disabledJ4 PIR -ON = Radar only enabledOFF = PIR and Radar enabled(factory default)Understanding the LEDThe multi-color LED located on the bottom of the detectorindicates the status of the unit as described in the following table.In Radar-only mode:LED StatusRed PIR and Radar detection. The detector isin alarm and the relay has switched.Green PIR detection only (no alarm).Yellow Radar detection only (no alarm).LED StatusRed Radar detection.90’(27.4m) 90’(27.4m)60’(18.3m)60’(18.3m)80’(24.4m) 80’(24.4m)70’(21.3m) 70’(21.3m)90’(27.4m) 90’(27.4m)60’(18.3m) 60’(18.3m)80’(24.4m) 80’(24.4m)70’(21.3m) 70’(21.3m)J3 LEDJ4 PIRJ2 RangeJ4J3J2
SpecificationsInput voltage 8.5 to 18VDC (UL: 10 to 16VDC)Typical current 23mA (LEDs off)Maximum current 35mAElectrical configuration Form CRelay rating 28VDC, 100mA max.Tamper 100ma, 40VDCDetection range 90' (37m) x 90°Target velocity 0.5 ft/sec to 5 ft/secAlarm duration 5 sec ± 10%Mounting height 8' to 12' (2.4m to 3.7m)Operating temperature 32° F to 122° F (0° C to 50° C)Relative humidity 5 to 93% non-condensingDimensions: 3.5" (89mm) W6.1" (155mm) H3.1" (79mm) DWeight 6.8 oz (193g)Color whiteField wiring size 12-24 AWGMicrowave frequency 5.8GHz1040656 Rev A  08/03Product OrderingModel Number DescriptionRCR-90 Dual technology, range-controlled radar, passive infrared detector with form C relay, stealthmode, tamper contacts, 90 foot (27.4m) maximum rangewww.GE-Interlogix.com©  2003 GE Interlogix12345 SW Leveton DriveTualatin, OR 97062Phone: 503-692-4052USA & Canada: 800-547-2556Technical Service: 800-648-7424FaxBack: 800-483-2495GE Interlogix Maintaining the DetectorWhen installed and used properly, the detector provides manyyears of service with minimal maintenance. You should walk testthe detector annually to ensure proper operation.Clean the inside of the unit with a soft-bristled brush or com-pressed air. Clean the outside with a damp (water) cloth asneeded to keep it free of dust and dirt. Always test the unitafter cleaning.When the cover is removed, power is interrupted to the sensor.Once the cover has been replaced, the green LED will illuminatefor 25 seconds while the sensor warms up. After the green LEDgoes off, wait one minute and walk test the sensor.

Navigation menu