VEGA Grieshaber KG PMT8X External radio communication unit for level sensors and point level detection sensors User Manual Manual

VEGA Grieshaber KG External radio communication unit for level sensors and point level detection sensors Manual

Manual

Operating InstructionsExternal radio unit for HART sensorsPLICSMOBILE T81/B81/S81External GSM/GPRS/UMTS radio unitOptionally with battery/accumulator/solar panelDocument ID: 55234
2ContentsPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Contents1  About this document1.1 Function ........................................................................................................................... 41.2  Target group ..................................................................................................................... 41.3  Symbols used................................................................................................................... 42  For your safety2.1  Authorised personnel ....................................................................................................... 52.2  Appropriate use ................................................................................................................ 52.3  Warning about incorrect use ............................................................................................. 52.4  General safety instructions ............................................................................................... 52.5  Safety label on the instrument .......................................................................................... 52.6  EU conformity ................................................................................................................... 62.7  Radio license for Europe .................................................................................................. 62.8  Radio license for USA ...................................................................................................... 62.9  Radio license for Canada ................................................................................................. 72.10  Environmental instructions ............................................................................................... 73  Product description3.1 Conguration .................................................................................................................... 83.2  Principle of operation........................................................................................................ 93.3 Adjustment ....................................................................................................................... 93.4  Packaging, transport and storage ..................................................................................... 94 Mounting4.1  General instructions ....................................................................................................... 114.2  Installation procedure ..................................................................................................... 115  Connecting to power supply5.1  Preparing the connection ............................................................................................... 145.2  Connection options ........................................................................................................ 145.3  Connection steps sensor connection cable .................................................................... 155.4  Connection steps voltage supply .................................................................................... 155.5  Wiring plan ..................................................................................................................... 176  Battery operation and power saving mode6.1  Battery/accumulator operation ....................................................................................... 196.2  External battery PLICSMOBILE B81 .............................................................................. 196.3  Solar panel PLICSMOBILE S81 ..................................................................................... 206.4  Battery sizing.................................................................................................................. 226.5  Power options ................................................................................................................. 237 Setup7.1  Adjustment system ......................................................................................................... 257.2  Communication via Bluetooth......................................................................................... 257.3  Parameter adjustment with PC and PACTware ............................................................... 267.4  Mobile network and SIM card ......................................................................................... 277.5  Internet connection and measured value transmission ................................................... 298 Maintenanceandfaultrectication8.1 Maintenance .................................................................................................................. 328.2  Rectify faults ................................................................................................................... 328.3  How to proceed if a repair is necessary .......................................................................... 33
3ContentsPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702069 Dismount9.1  Dismounting steps.......................................................................................................... 349.2 Disposal ......................................................................................................................... 3410 Supplement10.1  Technical data ................................................................................................................ 3510.2 Dimensions .................................................................................................................... 3910.3  Industrial property rights ................................................................................................. 4110.4  Hash function acc. to mbed TLS ..................................................................................... 4110.5 Trademark ...................................................................................................................... 41Supplementary documentationInformation:Supplementary documents appropriate to the ordered version come withthedelivery.Youcanndthemlistedinchapter"Product descrip-tion".Editing status: 2017-01-31
41 About this documentPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702061  About this document1.1 FunctionThis operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc-tionsformaintenanceandfaultrectication.Pleasereadthisinforma-tion before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.1.2  Target groupThis operating instructions manual is directed to trained specialist personnel. The contents of this manual should be made available to these personnel and put into practice by them.1.3  Symbols usedInformation, tip, noteThis symbol indicates helpful additional information.Caution: If this warning is ignored, faults or malfunctions can result.Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.Ex applicationsThis symbol indicates special instructions for Ex applications.SIL applicationsThis symbol indicates instructions for functional safety which must be taken into account particularly for safety-relevant applications.•  ListThe dot set in front indicates a list with no implied sequence.→ ActionThis arrow indicates a single action.1  Sequence of actionsNumbers set in front indicate successive steps in a procedure.Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.
52 For your safetyPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702062  For your safety2.1  Authorised personnelAll operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.During work on and with the device the required personal protective equipment must always be worn.2.2  Appropriate useThe PLICSMOBILE T81 is an external mobile network unit for trans-mission of measured values and for remote parameter adjustment of plics® sensors.Operational reliability is ensured only if the instrument is properly usedaccordingtothespecicationsintheoperatinginstructionsmanual as well as possible supplementary instructions.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodicationsareexplicitlyforbidden.2.3  Warning about incorrect useInappropriate or incorrect use of the instrument can give rise to application-specichazards,e.g.vesseloverllordamagetosystemcomponents through incorrect mounting or adjustment.2.4  General safety instructionsThis is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technicallyawlessandreliablecondition.Theoperatorisresponsiblefor the trouble-free operation of the instrument.During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula-tions.The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodicationsareexplicitlyforbidden.The safety approval markings and safety tips on the device must also be observed.2.5  Safety label on the instrumentThe safety approval markings and safety tips on the device must be observed.
62 For your safetyPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702062.6  EU conformityThedevicefullsthelegalrequirementsoftheapplicableEUguide-lines.ByaxingtheCEmarking,weconrmsuccessfultestingoftheproduct.YoucanndtheEUconformitydeclarationonourwebsiteunderwww.vega.com/downloads.2.7  Radio license for EuropeThe instrument was tested according to the latest issues of the har-monized standards:•  EN 300328•  EN 301511•  EN 301908-1•  EN 301908-2•  EN 300440It is hence approved for use inside closed vessels in countries of the EU and EFTA.2.8  Radio license for USAThis approval is only valid for USA. Hence the following text is only available in the English language:This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:•  This device may not cause interference, and•  This device must accept any interference, including interference that may cause undesired operation of the deviceChangesormodicationsnotexpresslyapprovedbythemanufac-turer could void the user’s authority to operate this equipment.This device is approved for unrestricted use only inside closed, sta-tionaryvesselsmadeofmetal,reinforcedberglassorconcrete.This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance of 20 cm cm between the radia-tor and your body. This transmitter must not be co-located or operat-ing in conjunction with any other antenna or transmitter.This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception,whichcanbedeterminedbyturningtheequipmentoandon, the user is encouraged to try to correct the interference by one or more of the following measures:•  Reorient or relocate the receiving antenna
72 For your safetyPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206•  Increase the separation between the equipment and receiver•  Connecttheequipmentintoanoutletonacircuitdierentfromthat to which the receiver is connected•  Consult the dealer or an experienced radio/TV technician for help2.9  Radio license for CanadaThis approval is only valid for Canada. Hence the following texts are only available in the English/French language:This device complies with Industry Canada's license-exempt RSS standard(s). Operation is subject to the following conditions:•  This device may not cause interference, and•  This device must accept any interference, including interference that may cause undesired operation of the deviceThis equipment complies with IC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance of 20 cm cm between the radiator and your body. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.Le présent appareil est conforme aux CNR d’Industrie Canada ap-plicables aux appareils radio exempts de licence. L’exploitation est autorisée aux conditions suivantes:•  L’appareil ne doit pas produire de brouillage; et•  L’utilisateur de l’appareil doit accepter tout brouillage radioélect-rique subi, même si le brouillage est susceptible d’en compromet-tre le fonctionnement.Cet équipement est conforme aux limites d'exposition aux rayonne-ments IC établies pour un environnement non contrôlé. Cet équipe-ment doit être installé et utilisé avec un minimum de 20 cm cm de distance entre la source de rayonnement et votre corps. Ce transmet-teur ne doit pas être place au même endroit ou utilise simultanément avec un autre transmetteur ou antenne.2.10  Environmental instructionsProtection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental pro-tection.Theenvironmentmanagementsystemiscertiedaccordingto DIN EN ISO 14001.Pleasehelpusfullthisobligationbyobservingtheenvironmentalinstructions in this manual:•  Chapter"Packaging, transport and storage"•  Chapter"Disposal"
83 Product descriptionPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702063  Product description3.1 CongurationThe scope of delivery encompasses:•  PLICSMOBILE T81•  Sensor connection cable (optional)•  Documentation – This operating instructions manual – Ifnecessary,furthercerticatesThe PLICSMOBILE T81 consists of the components:25341Fig. 1: PLICSMOBILE T811  Electronics compartment2  Plug connector for connection of the sensor3 Antenna4  Mounting plate5  Sensor connection cableThetypelabelcontainsthemostimportantdataforidenticationanduse of the instrument:•  Instrument type•  Product code•  Approvals•  Technical data•  Serial number of the instrument•  Data matrix code for smartphone appThe type label contains the serial number of the instrument. With it youcanndthefollowingdataonourhomepage:•  Product code of the instrument (HTML)•  Delivery date (HTML)•  Order-specicinstrumentfeatures(HTML)•  Operating instructions at the time of shipment (PDF)Goto"www.vega.com","VEGA Tools"and"Instrument search".Enterthe serial number.Alternatively, you can access the data via your smartphone:•  Downloadthesmartphoneapp"VEGA Tools"fromthe"Apple App Store"orthe"Google Play Store"•  Scan the Data Matrix code on the type label of the instrument orScope of deliveryConstituent partsType labelSerial number
93 Product descriptionPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206•  Enter the serial number manually in the app3.2  Principle of operationThe PLICSMOBILE T81 is a mobile network unit for transmission of measured values and for remote parameter adjustment of plics® sensors. Due to the large operating voltage range and the integrated power saving functions, a mains-independent power supply via bat-tery or accumulator/solar cells is possible. Typical applications are measured value transmission from mobile vessels, battery-operated level measurement and deep well measurement.The measured value and message transmission can be optionally carried out via e-mail or SMS. Furthermore, the measured values can betransmittedviahttpsforvisualisationin"VEGA Inventory System".The use of PLICSMOBILE T81 is particularly suitable for inventory management, VMI (Vendor Managed Inventory) and remote enquiry.The external mobile network unit PLICSMOBILE T81 can be con-nected to any 4 … 20 mA HART two-wire sensor of the plics® series. In HART Multidrop operation up to 15 sensors can be connected to a PLICSMOBILET81(max.vewithExversion).The transmission of measured values, event messages and diagnos-tic information to the user is carried out via the GSM/GPRS network. Thanks to quadband technology, the device can be used virtually anywhere in the world. There is also the option of accessing the con-nected sensor via remote parameter adjustment.Power is supplied via a standard low voltage source (external power supply unit/battery/accumulator/solar panel) or via the optionally availablePLICSMOBILEB81.Youcannddetailedspecicationsonthepowersupplyinchapter"Technical data".The PLICSMOBILE T81 normally supplies power to the connected sensors.3.3 AdjustmentThe device is adjusted via PACTware and the corresponding DTM. The connection is made via the Bluetooth module integrated in PLICSMOBILE T81.3.4  Packaging, transport and storageYour instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.Transport must be carried out in due consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.Application areaFunctional principleVoltage supplyPackagingTransport
103 Product descriptionPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con-cealed defects must be appropriately dealt with.Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.Unless otherwise indicated, the packages must be stored only under the following conditions:•  Not in the open•  Dry and dust free•  Not exposed to corrosive media•  Protected against solar radiation•  Avoiding mechanical shock and vibration•  Storageandtransporttemperatureseechapter"Supplement - Technical data - Ambient conditions"•  Relative humidity 20 … 85 %Transport inspectionStorageStorage and transport temperature
114 MountingPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702064 Mounting4.1  General instructionsIn the standard version, the PLICSMOBILE T81 is designed for wall mounting. Mounting adapters for carrier rail mounting (top hat rail 35 x 7.5 according to DIN EN 50022/60715) as well as for tube mounting are optionally available.Checkbeforemountingifasucientnetworkcoverage(signalstrength) of the mobile network provider is available at the planned location. This can be simply tested by means of a mobile phone. Keep in mind that the SIM cards in the PLICSMOBILE T81 and in the mobile phone are from the same mobile phone provider or work in the same mobile phone network. If the radio reception is too weak, you should search for a better position. In closed rooms this would be, for example, close to a window or at least closer to an outer wall.Note:During operation, a distance of at least 20 cm should be kept between the antenna and persons working nearby. Operation of the instrument with smaller distances is not recommended.Usetherecommendedcables(seechapter"Connecting to power supply")andtightenthecablegland.You can give your instrument additional protection against moisture penetration by leading the connection cable downward in front of the cableentry.Rainandcondensationwatercanthusdraino.Thisap-plies mainly to outdoor mounting as well as installation in areas where high humidity is expected (e.g. through cleaning processes) or on cooled or heated vessels.4.2  Installation procedureThe PLICSMOBILE T81 for wall mounting is supplied with a mounting base for screw mounting.→ Fasten the instrument with four appropriate screws (not included in the delivery) according to the following illustration.Mounting optionsInstallation positionMoistureWall mounting
124 MountingPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-17020662 mm (2.44")12 mm(0.47") 7 mm(0.28")85 mm (3.35")Fig. 2: PLICSMOBILE T81 for wall mounting, bottom view of mounting plate.The PLICSMOBILE T81 for top hat rail mounting is supplied with an already assembled adapter for fastening on a 35 x 7.5 carrier rail.→ Snap the instrument without tools onto the top hat rail. Loosening from the top hat rail is also carried out without tools. Through the integrated spring, you just have to apply slight lateral pressure to the instrument.1 2Fig. 3: PLICSMOBILE T81 for carrier rail mounting1  Adapter plate2  Carrier railThe PLICSMOBILE T81 for tube mounting is supplied with a measur-ing instrument holder and four hexagon socket screws M5 x 12 as unassembled mounting accessory.→ Mount the measuring instrument holder according to the following illustration to the socket of PLICSMOBILE T81. Then you can fasten the instrument with the bent strap to your tube.Carrier rail mountingTube mounting
134 MountingPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702061 23Fig. 4: PLICSMOBILE T81 for tube mounting1  4 screws M5 x 122  Measuring instrument holder3 Tube
145 Connecting to power supplyPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702065  Connecting to power supply5.1  Preparing the connectionAlways keep in mind the following safety instructions:•  Connect only in the complete absence of line voltage•  If overvoltage surges are expected, overvoltage arresters should be installedPower can be supplied optionally via PLICSMOBILE B81 or a sepa-rate power supply unit.When using a power supply unit, the secondary circuit must be separated from the primary circuit by double or reinforced insulation (according to the nationally valid safety standards).The air and creeping distances in PLICSMOBILE T81 meet the requirements of EN IEC61010-1 for secondary circuits with reinforced insulation under overvoltage category III (altitude up to 2000 m).The voltage supply of PLICSMOBILE T81 is connected with standard cable according to the national installation standards.The sensor connection cable included in the delivery is used to con-nect the sensor.Connect the cable screen on the sensor side to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the sensor housing must be connected to the potential equalisation (low imped-ance).Note:WhenconnectingmorethanoneHARTsensor,adierentaddressmust be assigned to each sensor (address range 1-15). Address 0 (mode 4 … 20 mA) may not be used. When assigning an address, only one sensor should be connected to PLICSMOBILE T81. If con-nectionisalreadycompleted,thewiringmustbebrieyundoneforaddressing. Depending on the installation location of the sensors, it can be advantageous to carry out this addressing before installing and connecting the sensors. This can be conveniently carried out e.g. in the workshop. You only need a 24 Volt power supply as well as an indicating and adjustment module PLICSCOM or the adjustment software PACTware with VEGACONNECT.5.2  Connection optionsPower can be supplied to the sensor and PLICSMOBILE in two ways:With this version, only one voltage supply is required for both devices. The voltage supply is connected to the PLICSMOBILE T81. In addition to the measured value, the sensor connection cable also carries the voltage supply of the sensor  via HART. Hence there is no 4 … 20 mA HART signal from the sensor electronics available for processing, e.g. via a PLC. That's why the measured value transmis-Note safety instructionsSelect power supplySelect connection cableCable screening and groundingCommon voltage sup-ply for sensor and PLICSMOBILE
155 Connecting to power supplyPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206sion can only be carried out via radio transmission through e-mail/SMS/VEGA Inventory System.With this version, the sensor and the PLICSMOBILE T81 are each powered via a separate power supply. Here, the measured values can be transmitted via radio communication and the 4 … 20 mA HART signal is available in parallel for processing, e.g. via a PLC.HART communicationIf the internal resistance of the connected power supply for the sensor islessthan230Ω,theHARTsignalisextremelydampedorshort-circuited. Digital communication with PLICSCOM is then no longer possible. With low impedance processing systems, a resistance of approx.230Ωmustbeloopedintothe4…20mAcable.Thisresist-ance is already integrated in PLICSMOBILE T81 and can be looped automatically into the circuit by selecting the appropriate wires (see wiring plan).The connection to power supply is carried out as described in the respective operating instructions manual.5.3  Connection steps sensor connection cableThe sensor connection cable is used for transmission of the meas-ured value from the sensor to the PLICSMOBILE T81. In addition, it can also transmit the voltage supply for the connected sensor.The sensor connection cable is available in Ex version (blue) as well as in non-Ex version (black). It can be ordered in three lengths (5/10/25 m) and can be shortened afterwards to individual lengths. On one end there is a ready-for-use plug for connection to PLICSMOBILE T81. On the other end are free cable ends for direct connection to the sensor.To connect, proceed as follows:1.  Connect the colour coded wire ends to the respective sensor terminals, as described in the wiring plan and the operating instructions of the sensor.2.  Isolate unused wires, depending on connection type and cable version3.  Connect the screen to the internal ground terminal, connect the outer ground terminal on the housing to potential equalisation4.  Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable5.  Insert the plug of the sensor connection cable into the plug con-nection on PLICSMOBILE T816.  Tighten plug connection5.4  Connection steps voltage supplyThe connection of the voltage supply is made via spring-loaded termi-nals in the electronics compartment. A small screwdriver is required toopentheterminals.Solidaswellasexiblecoreswithoutcableendsleeves can be used.Separate voltage sup-ply for sensor and PLICSMOBILEConnection technology
165 Connecting to power supplyPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Proceed as follows:1.  Unscrew the housing lid2.  Loosen compression nut of the cable gland and remove blind plug3.  Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) of insulation from the ends of the individual wires4.  Insert the cable into the cable gland through the cable entryFig. 5: Connection steps 4 and 55.  Lift the opening levers of the terminals with a screwdriver6.  Insert the wire ends into the open terminals according to the wir-ing plan7.  Press down the opening levers of the terminals, you will hear the terminal spring closing8.  Check the hold of the wires in the terminals by lightly pulling on them9.  Connect the screen to the internal ground terminal, connect the external ground terminal to potential equalisation10.  Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable11.  Screw the housing lid back onTheelectricalconnectionisnished.Connection procedure
175 Connecting to power supplyPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702065.5  Wiring plan1PLICSMOBILE4 5263512+-6784...20mASIMStatusSend Off          On123+-Fig. 6: Connection of the voltage supply in the electronics housing1  Power supply PLICSMOBILE and sensor2  Sensor connection cable3  HART sensor from the plics® series4  Brown cable (+) for sensor power supply/HART communication5  Blue cable (-) for sensor power supply/HART communication6  Unused wires that must be insulated (not present on Ex version)Note:If multiple sensors are connected, they are connected in parallel. The sensorsshouldrstbesettoHARTMultidropmode1PLICSMOBILE452763512++--6784...20mASIMStatusSend Off          On123+-Fig. 7: Connection of the voltage supply in the electronics housing1  Power supply PLICSMOBILE2  Sensor connection cable3  HART sensor from the plics® series4  Brown cable (+) for HART communication5  Blue cable (-) with HART resistance, as an alternative white cable (-) without HART resistance6  Voltage supply, sensor7  Unused cores to be insulatedNote:The unused cores of the sensor connection cable must be insulated.Wiring plan with voltage supply of the sensor via PLICSMOBILEWiring plan with external voltage supply of the sensor
185 Connecting to power supplyPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206SIMStatusSend Off          On123+-123+-45+-+-OutputSolar panel input OutputOffOnPLICSMOBILE T81PLICSMOBILE B81321546Fig. 8: Connection of the battery and the solar panel1  Brown cable (+) for sensor power supply2  Blue cable (-) for sensor power supply3  White cable for communication PLICSMOBILE T81 - B814  Brown cable (+) for accumulator charging via solar panel5  Blue cable (-) for accumulator charging via solar panel6  Power supply from the solar panelWiring plan battery/solar panel
196 Battery operation and power saving modePLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702066  Battery operation and power saving mode6.1  Battery/accumulator operationIf no mains voltage is available, PLICSMOBILE can be also powered with batteries. For this purpose, an optional power pack is available in a separate housing (PLICSMOBILE B81). This power pack can be either ordered or equipped with chargeable accumulators or Lithium batteries. As an alternative, an external battery/accumulator can be connectedviathevoltagesupplyterminals.Youcannddetailedinformationofthevoltagesupplyinchapter"Technical data".When battery/accumulator operation and time-controlled measure-ment transmission are activated, the power saving mode should be switchedonandtheBluetoothfunctionswitchedotoincreasetheoperatingtime(detailsseechapter"Power options").Inaddition,theHART Multidrop mode should be switched on.Note:For charging the accumulators the ambient temperature must be in a range of 0 … +45 °C (+32 … +113 °F). Temperatures outside this range are permitted, however due to the protective circuit integrated in the instrument, charging is not possible.6.2  External battery PLICSMOBILE B81The PLICSMOBILE B81 was especially developed for the power supply of PLICSMOBILE T81. It can be optionally equipped with rechargeable accumulators or non-rechargeable batteries of series "D"(Mono).Note:ThereisasafetyinstructionleaetattachedtoeachPLICSMOBILEB81 which must be read before setup and observed.With the Ex version, one of the two following batteries/accumulators must be used. If other batteries/accumulators are used, the approval becomes invalid.If there is no solar panel available at the installation location, then PLICSMOBILE B81 should be equipped with non-chargeable Li-batteries. As an alternative, standard Alkaline batteries can be used, the lifetime is hence shorter. We recommend using  Lithium batter-iesLSH20ofMessrs.Saft(VEGAorderno.2.54970).Youcanndfurther information of this battery type in the technical data.Warning:Whenusingnon-chargeablebatteries,theterminalsofthe"Solar Panel Input"mustnotbeconnected.Ifvoltageisapplied,thebatterieswillbedestroyedandtherewillbearehazard.If a solar panel is used, PLICSMOBILE B81 must be equipped with rechargeable NiMH accumulators. The solar panel is connected di-rectly to terminals 4 and 5,  a charge regulator is integrated in the bat-tery cover. We recommend the use of NiMH accumulators 5030641 Battery operationAccumulator operation
206 Battery operation and power saving modePLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206fromAnsmann(VEGAorderingno.2.54971).Youcanndfurtherinformation about this battery type in the technical data.Note:For charging the accumulators the temperature must be in a range of 0 … +45 °C (+32 … +113 °F). Temperatures outside this range are permitted, however due to the protective circuit integrated in the instrument, charging is not possible.The battery cable joins PLICSMOBILE B81 with PLICSMOBILE T81. It is available with 5/10/25 m length. Connect the cable as shown in the wiring plan. Make sure that the terminals of both instruments are connected 1 : 1 via this cable.1.  Make sure that the switch on the upper side of the cover is set to "OFF"2. Unscrewthecentralxingscrewwithacoin.Thenyoucanre-move the battery cover.3.  Insert the four batteries/accumulators into the battery compart-ment. The respective polarity is printed at the bottom of the compartment but also in the battery cover.4.  Place back the battery cover to the battery compartment. Make sure that the position is correct, the battery cover can only be at-tached in one direction.5.  Push the battery cover slightly downward on the points marked with"PUSH"andscrewinthecentralxingscrew.6.  If all components are connected completely, you can set the switchontheuppersideofthebatterycoverto"ON"6.3  Solar panel PLICSMOBILE S81Via the solar panel PLICSMOBILE S81 you can power the PLICSMOBILE T81, the accumulator pack will also be charged. Two solarpanelswithdierentsize/capacityareavailable:withasunnyenvironment and max. one measured value transmission per day, the small5Wmoduleissucient;withintermittentshadowingand/ormore than one measured value transmission per day, the larger  20 W module should be used. The technical data of both modules and the order information can be found in the supplement of this instruction manual.Orient the solar module in such a way that in sunless seasons its positionisidealtothesunandmaximumeciencyisachieved.Be-cause in these seasons, the sun is very low, a steep installation angle (approx. 60 - 75 degrees) is recommended so that the sunrays reach the module at right angles. A tube holder suitable for the module is available in the scope of delivery. The adjustment range of the inclina-tion is 38 to 75 degrees, the orientation of the direction is individually possible due to the tube mounted. As an option also a holder for mounting on vertical surfaces such as walls is available.ConnectionInsert batteriesMounting
216 Battery operation and power saving modePLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Note:The tube holder of the solar module is suitable for tube diameters of  30 … 60 mm (1.2 … 1.4 in). If the PLCSMOBILE should be mounted to the same tube, a tube with ø 60 mm is required.Fasten the PLICSMOBILE close to the solar module to avoid unnec-essary voltage loss on the cable.12Fig. 9: Tube mounting PLICSMOBILE with solar module1  Tube/mast with ø 60 mm (1.4 in)2  Adjusting screw, inclination angleThe solar cable combines the power pack with the solar panel. It is available in the lengths  5/10/25 m. Connect the cable as shown in the wiring plan.Connection
226 Battery operation and power saving modePLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Note:Make sure that the two cores of the connection cable are energized when the solar module is already connected and not covered. Avoid a short circuit during mounting and connection. Also pay attention to this when shortening the cable, if that should be necessary.6.4  Battery sizingWhen selecting an external battery/accumulator, the following points must be observed:Power consumption in power saving mode:If you use a battery or accumulator that cannot be automatically recharged cyclically, the power saving mode should be activated. With an operating voltage of e.g. 12 V, a standby power consumption of 0.4 mW must be taken into account. With an assumed lifetime of e.g. one year, the requirement is approximately 3.5 Wh, which cor-responds to a battery capacity of 0.29 Ah at 12 V. The standby power consumptionatspecicoperatingvoltagesisstatedinthe"Technical data".Power requirement for a complete measurement cycle incl. measured value transmission:A measurement cycle lasts approximately 60 to 120 seconds (de-pendent on sensor type and network quality) and includes automatic switching on of the sensor (HART multidrop mode with  4 mA), recording of the measured value, measured value transmission and a return to the power saving mode. During this time,  approximately 15 mWh of energy is required. For example, with one measurement per day, this adds up to approx. 7.3 Wh per year, which corresponds to a battery capacity of approx. 0.6 Ah at 12 V.Examples for battery capacity depending on the number of transmission cyclesNumber of mes-sages/dayAnnual consumption PLICSMOBILEStandby energy demandEnergy demand for message transmissionRequired battery capacitance with 12 V13.5 Wh 7.3 Wh 0.6 Ah23.5 Wh 14.6 Wh 1.5 Ah43.5 Wh 29.2 2.7 Ah83.5 Wh 58.4 Wh 5.1 Ah24 3.5 Wh 175.2 Wh 14.9 AhNote:Due to the nature of the system, each battery and accumulator has a self-discharge which can vary considerably dependent on the type. This is very important for the calculation of the required capacitance. In the listed examples, this self-discharge is not taken into accunt. The available capacitance depends also considerably from the tempera-ture.Thespecicationsrefertoatemperatureof20°C(68°F).
236 Battery operation and power saving modePLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Operating times with PLICSMOBILE B81Inthefollowingtableyoucanndexemplarytheoperatingtimeswhen using PLICSMOBILE B81, depending on the number of sensors and messages per day as well as activated/deactivated Bluetooth function.Number of mes-sagesNumber of sen-sorsOperating time of the battery in yearsOperating time of the accumula-tor in years1 1 >10/3.7* 3/0.7*5 5.1/2.5* 0.9/0.5*10 2.9/1.8* 0.3/0.3*24 1.3/1.0* 0.2/0.2*1 2 >10 2.85 4.6 0.910 2.6 0.524 1.1 0.21 5 >10 2.45 3.6 0.710 1.9 0.424 0.9 0.2The values marked with * correspond to the operating time with acti-vated Bluetooth module.6.5  Power optionsIntheDTM(seechapter"Parameter adjustment with PACTware") youcanselectunderthemenuitem"Energy options"betweenthemodes"Continuous operation"and"Power saving mode".In continuous (non-stop) operation PLICSMOBILE and the sensor always remain switched on. Only in this mode can the instrument be used for level monitoring and send an e-mail when a certain level is reached or when an error occurs (measured value/status-controlled transmission). In continuous operation PLICSMOBILE allows remote parameteradjustmentviatheservicedepartment.Congurationchanges on PLICSMOBILE as well as the sensor can thus be carried out remotely from any PC with PACTware via GPRS.In this mode, the integrated GSM modem as well as the sensor connected to PLICSMOBILE are switched on automatically when the time-controlled transmission of a message is pending. After the measured value is recorded, the log-in into the GSM network is car-ried out and the measured value is transmitted. The instrument then returns to power saving mode. The time for this process depends on the network quality and is generally approx. 70 seconds.Permanent operationPower saving mode
246 Battery operation and power saving modePLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Note:Please note that event-controlled transmission (measured value/status-controlled) is not possible in the power saving mode. A dial-in connection for remote parameter adjustment is also not possible dur-ing the inactive time.When using battery operation and a HART sensor with non-required 4 … 20 mA signal, we recommend setting the sensor to multidrop mode. In such case, the sensor consumes constantly only 4 mA independently of the measured level, which increases the battery life considerably. When connecting one or more sensors, the HART multidrop mode is a basic requirement. A description of the activation of multidrop mode can be found in the operating instructions of the display and adjustment module.With activated Bluetooth function, additional energy is needed; this reduces the operating time with battery/accumulator operation con-siderably.Forthatreason,switchotheBluetoothfunctionifitisnotbeing used (via the switch on the electronics module).HART multidropBluetooth
257 SetupPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702067 Setup7.1  Adjustment systemThedial-uptothecongurationofPLICSMOBILET81iscarriedoutvia Bluetooth. For setup, a PC with PACTware and corresponding DTM is required. You also need the VEGA Bluetooth USB adapter; other Bluetooth modules, possibly already built into the PC or note-book, or other USB adapters cannot be used. As an alternative, the VEGA app for smartphones or tablets (iOS or Android) can be used. In such case you can use the Bluetooth module already integrated in the smartphone/tablet.An activated SIM card (Mini-SIM) with data transmission option must be used in PLICSMOBILE T81. The GSM/GPRS network must have good coverage at the installation site.Control elements on the device itself are limited to a test key and two LEDs. With these, operational readiness and the status of the instru-ment can be checked (connection to GSM network, standby …).52431SIMStatusSend Off          OnFig. 10: Display and adjustment elements1  Key for testing operational readiness2  SIM card slot (Mini-SIM format)3  Status indication, mobile network (yellow)4  Status indication, Bluetooth (blue)5  Bluetooth switchInformation:The function description of the key and the status indication is avail-ableinchapter"Mobile phone network and SIM card".7.2  Communication via BluetoothThe parameter adjustment of PLICSMOBILE T81 is only carried out via the integrated Bluetooth interface. Thus a wireless connection to dierentoperatingdevicesispossible.Thesecanbesmartphones/tablets with iOS or Android operating system or PCs/notebooks with Windows operating system and Bluetooth USB adapter.There is a slide switch on the upper side of the electronics module for activating/deactivating the Bluetooth function. With switch position "On",connectioncanbeestablished.AftertheparameteradjustmentSetup requirementsDisplay and adjustment elementsBluetooth switch
267 SetupPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206itisgenerallyrecommendedtosettheswitchto"O".Lesspowerisconsumed this way and the lifetime of the battery is increased.7.3  Parameter adjustment with PC and PACTwareFor adjustment via Windows PC, a Bluetooth USB adapter and the congurationsoftwarePACTwarewiththesuitableinstrumentdriver(DTM) according to FDT standard are required. The up-to-date PACT-ware version as well as all available DTMs are compiled in a DTM Collection. The DTMs can also be integrated in other frame applica-tions according to FDT standard.Note:To ensure that all instrument functions are supported, you should always use the latest DTM Collection. Furthermore, not all described functionsareincludedinolderrmwareversions.Youcandownloadthe latest instrument software from our homepage. A description of the update procedure is also available in the Internet.The basic operation of the software is described in the operating instructionsmanual"DTM Collection/PACTware"attachedtoeachDTM Collection and which can also be downloaded from the Internet. Detailed descriptions are available in the online help of PACTware and the DTMs.All device DTMs are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assistant for simpleprojectcongurationsimpliestheadjustmentconsiderably.Saving/printing the project as well as import/export functions are also part of the standard version.In the full version there is also an extended print function for complete project documentation as well as a save function for measured value and echo curves. In addition, there is a tank calculation program as well as a multiviewer for display and analysis of the saved measured value and echo curves.The VEGA Bluetooth USB adapter is required for communication with PLICSMOBILE T81. A Bluetooth module (possibly already installed in the PC or notebook) or a USB adapter from another manufacturer cannotbeused.Youcanndfurtherinformationintheinstructionsbooklet of the Bluetooth USB adapter.Make sure that the Bluetooth switch on the electronics module is set to"On"andtheBluetoothUSBadapterisinserted.Start the project assistant in PACTware; the Bluetooth USB adapter, the PLICSMOBILE T81 and the connected sensors should then be found and displayed in the project window.The protection against unauthorized access to the PLICSMOBILE T81issetupontwosteps.TherststepistheBluetoothaccessprotection, controlling the general access to the instrument. After this step, reading out the parameters is always possible. Via the second PrerequisitesStandard/Full versionBluetooth USB adapterConnecting via BluetoothAccess protection
277 SetupPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206step, the parameter protection, the change of the instrument settings can be blocked.With activated Bluetooth access, connection to the instrument is only possible if the respective Bluetooth access code is known. This numerical access code (6-digit) is stored in the instrument and can bereadoutandmodiedviaDTM.Inaddition,thecodeislistedinthe accompanying documents available in the scope of delivery. With activated Bluetooth access, the access code must be entered only once per adjustment tool because it is automatically stored with the rstconnectiontotheadjustmenttool.Information:As a default setting, access protection is deactivated. To prevent from unauthorized change of the instrument data, the Bluetooth access protection and the following parameter protection should be activated. As an alternative, the Bluetooth function can be deactivated via the switch in the instrument.Withparameterprotectionactivated,themodicationofdeviceparameters is blocked. By entering a numerical device code (four to ten digits), the device is temporarily unlocked for a parameter change. After 60 minutes without any adjustments being made, the instrument is locked again automatically. Parameter protection is deactivated by default.7.4  Mobile network and SIM cardAn activated SIM card (Mini-SIM format) with data transmission op-tion is required for setup.Information:The SIM card does not belong to the standard scope of delivery of the device. To avoid roaming costs, the card should be bought in the country in which the PLICSMOBILE T81 is installed and operated. If you are using a VEGA Ident Card, you don't have to worry about this because no roaming costs are charged.To make the measured value transmission and remote maintenance assimpleaspossible,VEGAoerstheservicepackage"Wireless data transmission".ThispackageincludesanIdentCard(SIMcardinMini-SIM format) that covers all data transmission costs and provides worldwide 24-hour support.Incoming data connections (PLICSMOBILE) can only be established if the SIM card used supports GPRS. Incoming data connections are used for remote parameter adjustment via VEGA service.Information:When the power saving mode is activated in PLICSMOBILE, it cannot be contacted for remote parameter adjustment during the inactive time. During the active time (during a data transmission), incoming connections are accepted and maintained independent of the power saving mode until the connection is terminated.Bluetooth access protec-tionParameter protectionVEGA-Ident-CardRemote parameter ad-justment
287 SetupPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Data connections outgoing from PLICSMOBILE are established via GPRS (volume-based billing). Outgoing connection are used for measured value transmission via e-mail/SMS/VEGA Inventory System.During the transmission of the measured value via e-mail or Inventory System, approximately 5 KB data are transmitted. With hourly trans-mission, for example, this results in a monthly total net data volume of approximately 4 MB.The mobile network provider carries out a so-called block rounding thatdependsontheselectedtari.WhencheckingoutoftheGPRSnetwork, the values are rounded to next higher billing units. Since PLICSMOBILE checks out of the GPRS network after the transmis-sion of every message (if the energy saving mode is activated), this block rounding applies to each transmission. If, for example, a tariwithblockroundingto100KBisused,anhourlymeasurementtransmission results in a monthly billing volume of over 70 MB. For thatreason,youshouldchooseapuredatatariplan(M2M)withthelowest possible block rounding.Insert the card (beveled side in front) into the card slot until it snaps in. The contact surface must point upward.Note:The PLICSMOBILE T81 must be disconnected from voltage when inserting the SIM card. Keep ESD protection in mind when handling the SIM card. Electrostatic discharges can damage the SIM card or the PLICSMOBILE.Fig. 11: Insert Mini-SIM cardMeasured value transmis-sionInsert SIM card
297 SetupPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206To avoid misuse, the SIM card is generally locked by a PIN. To ensure thatPLICSMOBILEcancontacttheselockedSIMcards,rstofallthePINmustbeentered.Forthispurposetheassistant"Activate SIM card"isavailableintheDTM.EnterherethecorrectPINforthecard.TheassistantalsooerstheoptionofchangingthePIN.Information:When using the VEGA Ident Card, entering or deactivating a PIN is not required.Thencheckifthecardisloggedintothenetworkandifsucientnet-work coverage (signal strength) exists. For a reliable measured value transmission, a signal strength of at least 30 % should be displayed. ThiscanbecheckedintheDTMmenu"Network information"under"Setup - Diagnosis".Youcanalsoseethegeneraldevicestatusviathe status indication.The following operating conditions are signalled via the yellow LED (mobile network status indication):•  LED does not light: no operating voltage or power saving mode active•  Constantashing: Instrument is not logged into the GSM net-work•  Unsteadyashing(longOFF/shortON): instrument is booked into the GSM network•  Continuous light: Transmission or dial-up connection active•  Quicksteadyashingaftercontinuouslight Measured value transmission failedThe following operating conditions are signalled via the blue LED (Bluetooth status indication):•  LED does not light:Bluetoothswitchedoorpowersavingmodeactive•  Unsteadyashing(longOFF/shortON): Bluetooth switched on•  Permanent light: Bluetooth connection is activeInformation:When the PLICSMOBILE T81 is in power saving mode, the LED status indicators are inactive. The LED indicators are active only dur-ing the time when a measurement with subsequent measured value transmission takes place.By pushing this button, a manual measured value transmission will be triggered,independentoftheconguredtimesettings.Thisfunctionsalso if PLICSMOBILE is in power saving mode. Here you can check by means of the yellow status LED if logging into the GSM network is possible.7.5  Internet connection and measured value transmissionThe transmission of measured values via e-mail or to VEGA Inventory System is always based on an internet connection. For GPRS con-Activate SIM cardStatus indication"Send" buttonInternet connection
307 SetupPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206nection, access data (user name/password) and the respective APN (Access Point Name) are required.WhenusingtheVEGAservicepackage"Wireless data transmis-sion"andtheVEGAInventorySystem,youneednoaccessdataoradditional information because the required parameters are already preset.Information:Further information and a list of current mobile network providers along with their access data can be found in the online help of the PLICSMOBILE DTM.Fig. 12: Entering the Internet access dataThe measured values can be transmitted optionally in the following ways:•  Via integrated mail client to any e-mail address•  Via SMS to any mobile phone•  Via http to the VEGA Inventory SystemUndertheDTMmenuitem"Event list"thereisaconvenientassistantfor setting up measured value transmission. The measured values can betransmittedatindividuallydenabletimesorintervals.Amessagecan also be triggered when a certain level is exceeded or underrun. In addition, a status-controlled measured value transmission can be carried out, for example when a fault signal occurs.For this option, an e-mail account with the names of the inbox and outbox servers (POP3/SMTP) as well as the user name/password are required for authentication. These data are available from your e-mail provider. For secure transmission, an encrypted connection via TLS is preset. Please note that for encrypted connections, other server Measured value transmis-sionE-mail transmission
317 SetupPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206namesmustnormallybeused.Youcanndfurtherinformationintheonline help of the PLICSMOBILE DTM.The measurement data can be sent either directly in the e-mail or in anattachedle.TheformatsTXT,CSV,HTMLorXMLareavailable.Note:If you also want to send e-mails while using the Inventory System and a VEGA Ident Card, the following information is required in the con-nection settings:•  Username:"m2m"•  Password:"sim"•  APN:"internet.m2mportal.de"Fig. 13: Input of the e-mail access dataFor measured value transmission via SMS, no additional access data are required because all needed information is already available via the mobile phone contract.Fortheconguration,onlytheURLortheIPaddressoftheInven-tory server are required. When hosting is carried out through VEGA, theserveriscontactedviatheURL:"data-vis.vega.com".IfInventorySystem is hosted in your company, you will get the URL from your IT department.SMS transmissionVEGA Inventory System
328MaintenanceandfaultrecticationPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702068 Maintenanceandfaultrectication8.1 MaintenanceIf the device is used properly, no special maintenance is required in normal operation.8.2  Rectify faultsThe operator of the system is responsible for taking suitable meas-ures to rectify faults.Maximum reliability is ensured. Nevertheless, faults can occur during operation. These may be caused by the following, e.g.:•  Measured value from sensor not correct•  Voltage supply•  Interference in the cablesTherstmeasurestobetakenaretochecktheinput/outputsignalaswell as to evaluate the error messages via the DTM. The procedure is described below. In many cases, the causes can be determined and thefaultsrectiedinthisway.Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550.Thehotlineismanned7daysaweekround-the-clock.Sinceweoerthis service worldwide, the support is only available in the English language. The service is free, only standard call charges are incurred.Error Reason RecticationNo indi-cation of the signal strengthNo GSM network avail-ableCheck network availability via mo-bile phoneE008 Sensor not found Check connection of the sensorE013 Sensor signals error, no valid measured valueCheck sensor parameter adjustmentSend sensor for repairE030 Sensor in boot phaseMeasured value not validCheck sensor parameter adjustmentE034 EEPROM CRC error SwitchtheinstrumentoandonCarry out a resetSend instrument for repairE035 ROM CRC error SwitchtheinstrumentoandonCarry out a resetSend instrument for repairE036 Instrument software not executable (during soft-ware update and after failed update)WaituntilsoftwareupdateisnishedCarry out another software updateReaction when malfunc-tion occursCauses of malfunctionFaultrectication24 hour service hotlineError messages
338MaintenanceandfaultrecticationPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Error Reason RecticationE042 Hardware error with self-checkSend instrument for repairE053 Sensor measuring range is not read correctlyCommunication error: Check sensor cable and screeningE086 Error communication hardware (initialisation of the radio module failed)Initialisation is carried out automatical-ly. If the error exists permanently, send instrument for repairDepending on the reason for the fault and the measures taken, the stepsdescribedinchapter"Set up"mayhavetobecarriedoutagain.8.3  How to proceed if a repair is necessaryYoucanndaninstrumentreturnformaswellasdetailedinforma-tion about the procedure in the download area of our homepage: www.vega.com.By doing this you help us carry out the repair quickly and without hav-ing to call back for needed information.If a repair is necessary, please proceed as follows:•  Printandlloutoneformperinstrument•  Clean the instrument and pack it damage-proof•  Attach the completed form and, if need be, also a safety data sheet outside on the packaging•  Please contact the agency serving you to get the address for thereturnshipment.Youcanndtheagencyonourhomepagewww.vega.com.Note:If a battery-operated instrument is returned for repair, the battery/power pack must be removed. Please send only the instrument, not the battery/power pack.Reaction after fault recti-cation
349 DismountPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-1702069 Dismount9.1  Dismounting stepsTakenoteofchapters"Mounting"and"Connecting to power supply"and carry out the listed steps in reverse order.9.2 DisposalThe instrument consists of materials which can be recycled by spe-cialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable.Materials:seechapter"Technical data"For disposal or recycling within the European Union proceed accord-ingtothe"Electronics recycling"and"Battery/Accumulator recycling"below. Outside the European Union you should take note of the valid national regulations.Electronics recyclingThis instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Hence pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.Battery/accumulator recyclingNote:The disposal is subject to the directive 2006/66/EG on batteries and accumulators.Batteries and accumulators contain some environmentally harm-ful but also some valuable raw materials that can be recycled. For that reason batteries and accumulators must not be disposed of in household waste.All users are legally obligated to bring spent batteries to a suitable collection point, e.g. public collection points. You can also return the batteries and accumulators to us for correct disposal. Due to the very strict transport regulations for lithium-based batteries/accumulators, this is normally not a good idea because shipment is very expensive.Correctdisposalavoidsnegativeeectsonhumansandtheenviron-ment and ensures recycling of useful raw materials.
3510 SupplementPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-17020610 Supplement10.1  Technical dataGeneral data PLICSMOBILE T81Materials ƲPlastic housing plastic PBT (Polyester) ƲAluminium die-cast housing Aluminium die-casting AlSi10Mg, powder-coated - basis: Polyester ƲStainless steel housing 316L ƲCable gland PA ƲSealing, cable gland NBR ƲBlind plug, cable gland PA ƲSeal between housing and housing lid Silicone SI 850 R, NBR silicone-free ƲGround terminal 316LWeight ƲPlastic housing approx. 1.18 kg (2.59 lbs) ƲAluminium housing approx. 1.65 kg (3.65 lbs) ƲStainless steel housing approx. 3 kg (6.61 lbs)Power supply PLICSMOBILE T81Operating voltage1) 9.6 … 32 V DCPower consumption2) ƲPower saving mode (9 V/12 V) 0.18 mW/0.3 mW ƲPower saving mode (24 V/32 V) 1.8 mW/3.7 mW ƲPermanent operation 1.1 W ƲPeak power (measured value trans-mission)5.1 WPower requirement3) ƲMeasurement cycle incl. transmission 15 mWhSensor power supply Ʋ O-loadvoltage 34 V (31 V with Ex version) ƲMax. current 80 mA (26 mA with Ex version)PLICSMOBILE B81Materials ƲAluminium housing Aluminium die-casting ƲCable gland PA ƲSealing, cable gland NBR1)  When the instrument is powered by an external voltage supply, make sure the voltage supply unit has a suf-cientcurrentcarryingcapacity.Withavoltagesupply<9.6V,currentpeaksofupto2Amustbeexpected.2) ThelistedpowerspecicationsincludethevoltagesupplyofaHARTsensorwith20mA.3)  The listed energy requirement includes the voltage supply of a HART sensor (VEGAPULS 61 with 4 mA (multi-drop mode) and 12 V operating voltage.
3610 SupplementPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206 ƲBlind plug, cable gland PA ƲSeal between housing and housing lid Silicone SI 850 R, NBR silicone-free ƲGround terminal 316LWeight ƲAluminium housing approx. 1.66 kg (3.66 lbs)Approved battery types Lithium battery or NiMH accumulatorBattery format Type D (Mono)Necessary power supply for charging NiMH accumulators20 … 32 V DCNiMH accumulatorAccumulator type 4x NiMH series D (Mono)Manufacturer AnsmannVEGA order code 2.54971Capacitance 10 AhNominal voltage 1.2 V DCAmbient temperature (discharging) -20… +60 °C (-4 … +140 °F)Charging temperature 0 … +45 °C (+32 … +113 °F)4)Lithium batteryBattery type 4x Lithium battery series D (Mono)Manufacturer/Type Saft LSH 20VEGA order code 2.54970Capacitance 13 AhNominal voltage 3.6 V DCAmbient temperature -40… +85 °C (-40 … +185 °F)PLICSMOBILES81(solarpanel)Solar module 5 W ƲNominal voltage 17.8 V DC Ʋmax. open circuit voltage 22 V DC ƲNominal current 0.285 A Ʋmax. shortcircuit current 0.315 A ƲDimensions 401 x 176 x 35 mm (15.8 x 6.9 x 1.3 in)Solar module 20 W ƲNominal voltage 17.8 V DC Ʋmax. open circuit voltage 22 V DC ƲNominal current 1.14 A Ʋmax. shortcircuit current 1.27 A ƲDimensions 662 x 299 x 35 mm (26.1 x 11.8 x 1.3 in)4)  Due to a protective circuit, charging outside this temperature range is not possible
3710 SupplementPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Connection cable ƲLength 5/10/25 m (196/393/ in) ƲWire cross-section 2 x 0.5 mm² (AWG 20) ƲMaterial, cable cover PVCSensor inputNumber of sensors 15 x HART sensors (5 x with Ex version)Terminal voltage ƲNon-Ex version approx. 14 V with 15 sensors (60 mA) ƲEx version approx. 14 V with 5 sensors (20 mA)Current limitation approx. 80 mA (26 mA with Ex)Mobile networkSIM card slot Mini-SIM (25 x 15 mm)Radio frequency UMTS Quad-Band GSM (850/900/1800/1900 MHz)Antenna version Isotropic (Omni) antennaBluetoothBluetooth standard Bluetooth Smart (Bluetooth LE)Participants max. 1Max.eectiverange 25 m (82.02 ft)IndicatorsLED displays ƲStatus, mobile network 1 x LED yellow ƲStatus, Bluetooth 1 x LED blueElectromechanical dataCable entry/plug ƲElectronics housing  – 1 x cable gland M20 x 1.5 (cable ø 5 … 9 mm), 1 x plug for sensor connectionSpring-loaded terminals for wire cross-section ƲMassive wire, stranded wire 0.2 … 2.5 mm² (AWG 24 … 14) ƲStranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)Sensor connection cable ƲLength 5/10/25 mAmbient conditionsAmbient temperature -25 … +60 °C (-13 … +140 °F)Storage and transport temperature -25 … +80 °C (-13 … +176 °F)Electrical protective measuresProtection rating IP 665)5)  A suitable cable is required for maintaining the protection rating.
3810 SupplementPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Overvoltage category (IEC 61010-1) Ʋup to 2000 m (6562 ft) above sea level II Ʋup to 5000 m (16404 ft) above sea levelII (only with connected overvoltage protection) Ʋup to 5000 m (16404 ft) above sea levelIProtection rating (IEC 61010-1) IIMeasures for electrical separationReliable separation according to VDE 0106, Part 1, between power supply and input ƲReference voltage 50 V ƲVoltage resistance of the insulation 1.5 kVRadio approvalsRadio approvals GSM modem ƲFCC ID RI7GE865 ƲIC (Industry Canada) 5131 A-GE865Radio approvals Bluetooth module ƲFCC ID P144BL600 ƲIC (Industry Canada) 19318-BL600ApprovalsInstrumentswithapprovalscanhavedierenttechnicalspecicationsdependingontheversion.For that reason the associated approval documents of these instruments have to be carefully noted.Theyarepartofthedeliveryorcanbedownloadedunder"www.vega.com"via"VEGA Tools"and"Instrument search"aswellasvia"Downloads"and"Approvals".
3910 SupplementPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-17020610.2 Dimensions~ 110 mm (4.33")ø 79 mm(3.31")113 mm (4.44") 5 mm (0.20")85 mm (3.35")ø 60 mm  (2.36")16 mm(0.63")~ 113 mm (4.45")ø 86 mm(3.39")120 mm (4.72") 5 mm (0.20")85 mm (3.35")ø 60 mm  (2.36")11 mm(0.43")~ 178 mm (7.01")~ 186 mm (7.32")Fig. 14: Dimensions PLICSMOBILE T81 with plastic housing and StSt/Aluminium housing
4010 SupplementPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-17020657 mm  (2.24") 57 mm  (2.24")62 mm  (2.44")83,5 mm  (3.29")7,5 mm(0.29")25 mm(0.98")107 mm(4.22")35 mm(1.38")ø 6,9 mm(0.27")61,5 mm(2.42")70 mm(2.76")ø 110 mm (4.33")127 mm (5.00")145 mm (5.71")Fig. 15: Dimensions PLICSMOBILE B81 with Aluminium housing
4110 SupplementPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-17020610.3  Industrial property rightsVEGA product lines are global protected by industrial property rights. Further information see www.vega.com.VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.Nähere Informationen unter www.vega.com.Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec-tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus-trial. Para mayor información revise la pagina web www.vega.com.Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте www.vega.com.VEGA系列产品在全球享有知识产权保护。进一步信息请参见网站<www.vega.com。10.4  Hash function acc. to mbed TLSmbedTLS:Copyright(C)2006-2015,ARMLimited,AllRightsReservedSPDX-License-Identier:Apache-2.0LicensedundertheApacheLicense,Version2.0(the"License");youmaynotusethisleexceptincompliancewiththeLicense.YoumayobtainacopyoftheLicenseathttp://www.apache.org/licenses/LICENSE-2.0.Unless required by applicable law or agreed to in writing, software distributed under the License is distributedonan"ASIS"BASIS,WITHOUTWARRANTIESORCONDITIONSOFANYKIND,eitherexpressorimplied.SeetheLicenseforthespeciclanguagegoverningpermissionsandlimitationsunder the License.10.5 TrademarkAll the brands as well as trade and company names used are property of their lawful proprietor/originator.
42INDEXPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206INDEXAAccess data  29, 30Access number  29Accumulator  9, 19Accumulator capacity  22Adjustment  26APN  29Application area  9BBattery  9, 19Battery capacity  22Battery chamber  19Bluetooth  24, 25Bluetooth USB adapter  26CCable – Grounding  14 – Shielding  14Carrier rail  12Causes of malfunction  32Connection procedure  16Connection technology  15CSD  27, 29DData block rounding  28Data matrix code  8Dial-Out  27Dial-up connection  27Documentation  8DTM  9, 25, 26 – DTM Collection  26 – Full version  26EE-mail  9, 30FFault – Rectication32FDT  26GGPRS  9, 27, 28, 29GSM  9HHART  24IInstrument return form  33Inventory System  30LLED displays  29Lithium battery  19MM2M  28Measured value transmission  19, 23, 29, 30Moisture  11Mounting  11 – Carrier rail mounting  12 – Tube  12 – Wall mounting  11Mounting options  30Multidrop  24Multiviewer  26NNetwork coverage  29OOnline help  26Operating instructions  8Orientation, solar module  20PPACTware  9, 25PIN  29Plug  15Power options  23Power saving function  9Power saving mode  19, 22, 23, 27, 28, 29Power supply unit  19QQuadband  9RRemote parameter adjustment  9, 23, 27Repair  33Roaming  27, 28SSelf-discharge  22Sensor connection cable  15Serial number  8Service hotline  32
43INDEXPLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit55234-EN-170206Signal strength  29SIM card  27, 29Smartphone-App  8SMS  9Software update  26Solar module  20Standby  22Status indications  29TTank calculation  26Tube holder  20Type label  8VVEGA Inventory System  9Visualization  9VMI  9Voltage supply  9, 15
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany55234-EN-170206All statements concerning scope of delivery, application, practical use and operat-ing conditions of the sensors and processing systems correspond to the information available at the time of printing.Subject to change without prior notice© VEGA Grieshaber KG, Schiltach/Germany 2017Phone +49 7836 50-0Fax +49 7836 50-201E-mail: info.de@vega.comwww.vega.com