VERDANT ENVIRONMENTAL TECHNOLOGIES V THERMOSTAT User Manual

VERDANT ENVIRONMENTAL TECHNOLOGIES THERMOSTAT

User Manual

VVX Series Thermostat  with an Occupancy SensorINSTALLATION MANUALV.5   MAY 31, 2016
3Table of ContentsIntroduction .................................................................................................5Before You Begin ..........................................................................................8Programming a Thermostat with a Network Programmer .........................9Thermostat Installation ............................................................................. 10Thermostat Configuration .......................................................................... 11Setting the thermostat clock ...................................................................... 12Entering the room number ......................................................................... 13Configuring the Equipment Settings - Compressor Type ...........................14Configuring the Equipment Settings - Electric Heat ..................................15Configuring the Equipment Settings - Reversing Valve .............................16Configuring the Energy Saving Settings  .................................................... 17Testing the thermostat ...............................................................................18Accessing the Thermostat Settings ............................................................19Custom Energy Savings Settings ................................................................19Using the Thermostat Settings Screens .................................................... 2001 – FAN CONTROL MODE ..........................................................................2102 – 1ST STAGE DIFFERENTIAL - HEAT ..........................................................2203 – 2ND STAGE DIFFERENTIAL - HEAT .........................................................2304 – 1ST STAGE DIFFERENTIAL - COOL ....................................................... 2405 – INCIDENTAL OCCUPANCY THRESHOLD ............................................. 2506 – NIGHT OCCUPANCY THRESHOLD ...................................................... 2607 – FORCED 2ND STAGE HEATING .............................................................2708 – NIGHT OCCUPANCY START ................................................................ 2809 – NIGHT OCCUPANCY END ................................................................... 2910 – TEMPERATURE RECOVERY TIME ........................................................ 3011 – RECOVERY TEMPERATURE - HEAT ........................................................3112 – TEMPERATURE SETBACK DELAY - HEAT ...............................................3213 – MINIMUM SETBACK TEMPERATURE  .................................................. 3314 – TEMPERATURE SETBACK DELAY - COOL ............................................. 3415 – MAXIMUM SETBACK TEMPERATURE .................................................. 3516 – RECOVERY TEMPERATURE - COOL ..................................................... 3617 – MINIMUM SET POINT ...........................................................................37
4Table of Contents18 – MAXIMUM SET POINT ......................................................................... 3819 – TEMPERATURE CONTROL MODE ........................................................ 3920 – AUTO CHANGEOVER SET POINT OFFSET ...........................................4021 – SETBACK SET POINTS / AUTO-RESTORE ..............................................4122 – AUTOMATIC HUMIDITY CONTROL† ..............................................................................................4222 – TEMPERATURE CALIBRATION ............................................................. 43Relay Options .............................................................................................44ACCESSING RELAY OPTIONS ...................................................................... 441 – REVERSE RELAY OPERATION ................................................................ 452 – COOLING ONLY “SPDT” VALVE CONTROL ............................................. 463 – HEAT PUMP RELAY MODE .....................................................................47Troubleshooting .........................................................................................48Error Codes ................................................................................................. 48APPENDIX 1 - Energy Saving Presets ..........................................................49APPENDIX 2 - Glossary ................................................................................50Warranty Information .................................................................................51Technical Specifications ............................................................................. 52
5IntroductionVerdant VX Series Energy Management Thermostats for the hospitality industry deliver unprecedented energy savings without compromising guest comfort.Integrated occupancy sensor uses a combination of motion and thermal sensing technologies for accurate occupancy detection. Reliable occupancy detection allows saving energy when rooms are unoccupied. Energy saving presets eliminate the guesswork and make it easy to adjust the energy saving settings. (Patent Pending)Fully configurable energy saving settings allow customizing the thermostat energy saving settings to fit any situation.Comprehensive configuration options ensure full compatibility with virtually any existing or emerging hospitality HVAC system with up to 2 heat and 1 cool stages.Built-in wireless mesh-networking enables optional remote management.
6
7NOTICEFOR INSTALLATION OF NETWORKING THERMOSTATS WITH REMOTE MANAGEMENT, REFER TO THE “VX-TR NETWORK INSTALLATION” MANUAL.LOGIN TO THE REMOTE MANAGEMENT WEBSITE TO CONFIRM THE SERVER IS CONNECTED TO THE INTERNET BEFORE INSTALLING THERMOSTATS. DO NOT INSTALL THERMOSTATS IF THE SERVER IS NOT CONNECTED TO THE INTERNET. STOP THE INSTALLATION AND CONTACT VERDANT TECHNICAL SUPPORT. START BY FIRST INSTALLING A THERMOSTAT IN THE ROOM CLOSEST TO THE SERVER. LOG IN TO VERDANT’S REMOTE MANAGEMENT WEBSITE TO CONFIRM THAT THE THERMOSTAT IS ON THE REMOTE MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER.CONTINUE BY INSTALLING ADDITIONAL THERMOSTATS IN ADJACENT ROOMS ONLY AFTER CONFIRMING THAT INSTALLED THERMOSTAT(S) HAVE CONNECTED TO THE WIRELESS NETWORK AND THE REMOTE MANAGEMENT WEBSITE . IF INSTALLED THERMOSTAT(S) ARE NOT CONNECTING TO THE NETWORK AND DO NOT APPEAR ON THE VERDANT’S REMOTE MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER, STOP THE INSTALLATION AND CONTACT VERDANT TECHNICAL SUPPORTTHE ROOMS FURTHEST AWAY FROM THE SERVER SHOULD BE INSTALLED LAST.
8Before You Begin ➤Determine the appropriate installation location for the thermostat.  ➤Set the HVAC unit to “External Thermostat” (Class 2) mode. Consult the HVAC unit documentation to determine how to set the HVAC unit to “External Thermostat” mode. THERMOSTAT SHOULD FACE THE BED AREA OF THE ROOM. THERMOSTAT MUST NOT BE INSTALLED NEAR OR ON METAL STRUCTURES OR SURFACES INCLUDING METAL AIR DUCTING THAT MAY BE IN THE WALL.  METAL STRUCTURES AND SURFACES SIGNIFICANTLY REDUCE THE RANGE OF THE WIRELESS SIGNAL.
9Programming a Thermostat with a Network ProgrammerIn case of Network Installation with Remote Management, the thermostat must be programmed with a Network Programmer specific to the property before the installation. Thermostat must not be powered during the programming procedure..  ➤Plug one programmer connector into the thermostat;  ➤Push the black button on the programmer. The red light on the programmer should turn on and remain steadily lit;   If the red light on the programmer is blinking or is not steadily lit, unplug the programmer from the thermostat and repeat the steps above. ➤Unplug the programmer from the thermostat;Before You Begin
10Thermostat InstallationMounting the thermostat to the wall  ➤Power of the HVAC unit;  ➤Remove the thermostat cover; ➤Connect the thermostat wires to the supplied Wiring Harness - refer to the Wiring Table to determine proper connections; ➤Plug in the Wiring Harness into to the thermostat; ➤Use the supplied wall anchors and mounting screws to secure the thermostat to the wall;  ➤Follow the “Thermostat Configuration” instructions; ➤Replace the thermostat cover and screw in the locking screw; ➤Power on the HVAC unit.NOTE: If the PTAC unit has only one (1) fan speed, connect both fan control wires – Green and Purple – to the fan terminal (G). Wiring Table - 24V ACWire  Color Terminal Letter Terminal  ConnectionBlack C CommonRed R 24VYellow Y CompressorWhite W HeatOrange O or B Reverse ValveGreen GH Fan HighPurple GL Fan LowWiring Table - 24V DCWire  Color Terminal Letter Terminal  ConnectionBlack R 24VRed C CommonYellow Y CompressorWhite W HeatOrange O or B Reverse ValveGreen GH Fan HighPurple GL Fan Low
CONFIGURATION BUTTONNOTE: You can access Thermostat Configuration settings at any time by pressing the “Configuration” button. 11Thermostat ConfigurationOnce the thermostat is powered, thermostat configuration settings will appear on the thermostat screen.In order to properly operate the PTAC unit: ➤Set the thermostat clock; ➤Enter the room number; ➤Configure the equipment settings; ➤Select Energy Savings Preset;The thermostat configuration screens have a 3-minute time-out. If no action is taken within three (3) minutes, the thermostat will exit configuration settings.NOTE: If the thermostat is connected to a network, the equipment and the energy saving settings configured on the thermostat will be ignored and the settings configured on the Remote Management Website will be applied.
12Thermostat ConfigurationSetting the thermostat clockSet the thermostat clock to current time in 24h (Military Time) format.  ➤Use the “Up” and “Down” buttons to set the hours; ➤Press the “Fan” button to advance to the minutes setting; ➤Use the “Up” an “Down” buttons to set the minutes; ➤Press the “F/C” button to advance to the next menu;Setting the clock correctly is crucial for proper operation of the thermostat.HOURS MINUTES
13Thermostat ConfigurationEntering the room numberEnter the room number by changing the digits on the screen. Leading zeros “0” preceding other digits will be ignored, i.e. Room number “123” should be entered as “00123”.  ➤Use the “Up” and “Down” buttons to change the digit; ➤Press the “Fan” button advance to the next digit; ➤Press the “F/C” button to advance to the next menu;Entering the room number correctly is crucial for proper operation of remotely managed thermostats.
14Thermostat ConfigurationConfiguring the Equipment Settings - Compressor Type ➤Use the “Up” and “Down” buttons to change the compressor type by changing the first digit; 0  No Compressor 1  Heat Pump 2 *  Air Conditioner ➤Press the “Fan” button to advance to the next setting; *  Indicates default setting; COMPRESSOR TYPECERTAIN HEAT PUMP UNITS REQUIRE ENERGIZING THE REVERSING (“O/B”) VALVE WHEN (i) “W” IS ENERGIZED IN THE ELECTRIC HEAT MODE (ii) BETWEEN HEAT PUMP CYCLES. TO ENABLE THIS FEATURE, REFER TO “RELAY OPTIONS”.
15Thermostat ConfigurationConfiguring the Equipment Settings - Electric Heat ➤Use the “Up” and “Down” buttons to change the Electric Heat setting by changing the second digit; 0  No Electric Heat 1 *  Electric Heat ➤Press the “Fan” button to advance to the next setting; *  Indicates default setting;ELECTRIC HEAT
16Thermostat ConfigurationConfiguring the Equipment Settings - Reversing Valve ➤Use the “Up” and “Down” buttons to change the Reversing Valve setting by changing the third digit;  0  O/B contact is energized to cool;  1 *  O/B contact is energized to heat;  Refer to the PTAC unit documentation to determine the correct reversing valve setting. If incorrect reverse valve setting is selected, the PTAC unit will turn on the heating when air conditioning is requested and turn on the air conditioning when heating is requested;  ➤Press the “Fan” button to advance to the next setting; ➤Press the “F/C” button to advance to the next menu;  *  Indicates default setting;REVERSING VALVECERTAIN HEAT PUMP UNITS REQUIRE ENERGIZING THE REVERSING (“O/B”) VALVE WHEN (i) “W” IS ENERGIZED IN THE ELECTRIC HEAT MODE (ii) BETWEEN HEAT PUMP CYCLES. TO ENABLE THIS FEATURE, REFER TO “RELAY OPTIONS”.
17Thermostat ConfigurationConfiguring the Energy Saving Settings  ➤Use the “Up” and “Down” buttons to select the Energy Saving preset: E-0*   Energy Savings Off - No Temperature Setback; E-1   Lowest Energy Savings;E-2    Lower Energy Savings;E-3   Standard Energy Savings; E-4    Higher Energy Savings;E-5    Highest Energy Savings;  Refer to the APPENDIX 1 for Energy Saving Preset details. E-C  Indicates “Custom Energy Savings Settings” in case the active thermostat savings settings differ from any Energy Saving preset;   For details, refer to the “Custom Energy Savings Settings” section;  ➤Press the “Power” button to save the Thermostat Configuration and start using the thermostat;  *  Indicates default setting;
18Testing the thermostatFollowing the thermostat configuration, test if the thermostat is controlling the PTAC unit. ➤Press the “Power” button to turn the thermostat ON; ➤Press the “Down” button to change the temperature set point below the current room temperature to confirm that the thermostat initiates air conditioning. ➤Press the “Up” button to change the temperature set point above the current room temperature to confirm that the thermostat initiates heating. ➤Change the fan speed by touching the “Fan” button to test if the thermostat is controlling the fan speed.Thermostat Configuration
CONFIGURATION BUTTONNOTE: You can access Thermostat Settings by pressing and holding the “Configuration” button.19Custom Energy Savings SettingsIf you don’t want to use the one of the energy saving presets, you can enter custom energy savings settings. Accessing the Thermostat Settings ➤Press and hold the “Configuration” button until the first thermostat settings screen appears.   The thermostat must be turned on to access the thermostat settings.NOTE: If the thermostat is connected to a network, the equipment and the energy saving settings configured on the thermostat will be ignored and the settings configured on the Remote Management Website will be applied.
20Using the Thermostat Settings Screens ➤Use the “Up” and “Down” buttons to change the setting; ➤Press the “F/C” button to advance to the next setting; ➤Press the “Fan” button to return to the previous setting; ➤Press the “Power” button to save and exit thermostat settings; Custom Energy Savings SettingsSCREEN NUMBERSETTING VALUE
2101 – FAN CONTROL MODESelect Fan Control Mode: 00   MANUAL - guest can select automatic or continuous fan mode; 01 *  AUTOMATIC - fan runs only when there is a demand for heating or air conditioning; *   Indicates default setting;         Custom Energy Savings Settings
2202 – 1ST STAGE DIFFERENTIAL - HEAT 02-30   (0.2°F - 3.0°F; 0.5°F* default setting) Select the number of degrees the thermostat has to sense between the automatic changeover temperature for heat and the room temperature before a call for the 1st stage heating is initiated. Custom Energy Savings Settings
2303 – 2ND STAGE DIFFERENTIAL - HEAT 10-20   (1.0°F - 2.0°F*; 2.0°F* default setting) Select the difference between 1st stage heating and 2nd stage heating initiation.Custom Energy Savings Settings
2404 – 1ST STAGE DIFFERENTIAL - COOL 02-30   (0.2°F - 3.0°F; 0.5°F* default setting) Select the number of degrees the thermostat has to sense between the automatic changeover temperature for cool and the room temperature before a call for the 1st stage cooling is initiated. Custom Energy Savings Settings
2505 – INCIDENTAL OCCUPANCY THRESHOLD 00-60   (05* default setting) Select the minimum period of time (in minutes) for which occupancy needs to be detected to enter the guest occupancy mode.   When occupancy is detected, thermostat will switch to occupied mode for a duration of “Incidental Occupancy Threshold” selected here.   If occupancy is detected for a period of time shorter than the “Incidental Occupancy Threshold” selected here, the thermostat will automatically revert to unoccupied mode at the end of the “Incidental Occupancy Threshold” period and continue to observe energy saving functions that were in effect before the room became occupied. This setting allows ignoring incidental room visits.  If occupancy is detected for a period of time longer than the “Incidental Occupancy Threshold” selected here, the thermostat will enter the guest occupancy mode. When the thermostat is in the guest occupancy mode, it will revert to unoccupied mode and initiate the setback temperature only when occupancy is not detected for the duration of the setback delay (Heat or Cool) period. Custom Energy Savings Settings
2606 – NIGHT OCCUPANCY THRESHOLD 00-60   (01* default setting) Select the minimum period of time (in minutes) for which occupancy needs to be detected in order to consider the room occupied during the “Night Occupancy”period.  When occupancy is detected during the “Night Occupancy Period” for longer than the “Night Occupancy Threshold” selected here, the thermostat will instantaneously switch to occupied mode.   If occupancy is detected for a period of time shorter than the “Night Occupancy Threshold” selected here, the thermostat will automatically revert to unoccupied mode and continue to observe energy saving functions that were in effect before the room became occupied.  If occupancy is detected for a period of time longer than the “Night Occupancy Threshold” selected here, the thermostat will disable the occupancy sensor and consider the room occupied until the end of the “Night Occupancy” period.  This feature ensures that energy saving functions that may affect guest comfort will not come in effect during the “Night Occupancy” period.Custom Energy Savings Settings
2707 – FORCED 2ND STAGE HEATING 00-60   (30* default setting) Select a number of minutes 1st stage heating will run before 2nd stage heating is automatically initiated if the guest set point is not reached and the 2nd stage heating is not initiated through differential settings.  This feature allows automatically turning on 2nd stage heating to avoid excessive compressor use.  Set to 00 to disable the feature. Custom Energy Savings Settings
2808 – NIGHT OCCUPANCY START 00-23   (21* default setting) Select the start time (in hours - 24-hour clock) for “Night Occupancy”   If occupancy is detected for a period of time longer than the “Night Occupancy Threshold” during “Night Occupancy” period, the thermostat will disable the occupancy sensor and consider the room occupied until the end of the “Night Occupancy” period.  This feature ensures that energy saving functions that may affect guest comfort will not come in effect during the “Night Occupancy” period if room was occupied for a period of time longer than “Night Occupancy Threshold”. Custom Energy Savings Settings
2909 – NIGHT OCCUPANCY END 00-23   (09* default setting) Select the time (in hours - 24-hour clock) for “Night Occupancy” to end.   The time of day the “Night Occupancy” ends and the thermostat switches back to the room sensing settings chosen in the other occupancy modes.Custom Energy Savings Settings
3010 – TEMPERATURE RECOVERY TIME 00-60   (25* default setting) Select the maximum time allowed for a PTAC unit to attain temperature as defined by Heat and Cool “Recovery Temperature”.  “Temperature Recovery Time” selected here and the actual temperature recovery ability of the PTAC unit are used to calculate setback temperatures. Calculated setback temperatures maximize energy savings and at the same time ensure that a comfortable room temperature (defined as Heat and Cool “Recovery Temperature”) will be restored within the selected “Temperature Recovery Time”.  Setting the “Temperature Recovery Time” to “00”, disables temperature recovery. When temperature recovery is disabled, thermostat will use the Minimum and Maximum Setback Temperatures as setback set points. Custom Energy Savings Settings
3111 – RECOVERY TEMPERATURE - HEAT 62-82   (67°F* default setting) Select the room temperature in °F that a PTAC unit will have to attain within the selected “Temperature Recovery Time” when there is a need for heating.   Custom Energy Savings Settings
3212 – TEMPERATURE SETBACK DELAY - HEAT 00-120  (20* default setting) Select the time delay (in minutes) for which the room that is in the guest occupancy mode needs to be unoccupied before the temperature setback is initiated.  This feature prevents initiating temperature setback prematurely while the guest is still in the room but in an area where occupancy cannot be detected by the occupancy sensor.  Setting the “Temperature Setback Delay - Heat” to “00”, disables the setback in the heat mode. Set to “00” to disable EMS.   Custom Energy Savings Settings
3313 – MINIMUM SETBACK TEMPERATURE  52-72   (64°F* default setting) Select the “Minimum Setback Temperature” in °F.  Setback temperature is calculated by measuring PTAC unit’s ability to attain “Recovery Temperature - Heat” within “Temperature Recovery Time”.   If recovery is disabled (“Temperature Recovery Time” is set to “0”) or if setback temperatures have not yet been calculated, the “Minimum Setback Temperature” value will be used as the setback temperature for heating.  If calculated setback temperature for heating is lower than “Minimum Setback Temperature”, then the “Minimum Setback Temperature” will be used as setback temperature for heating.  This feature allows defining the minimum temperature in a room when room is unoccupied and the thermostat is in the setback mode. Custom Energy Savings Settings
3414 – TEMPERATURE SETBACK DELAY - COOL 00-120  (20* default setting) Select the time delay (in minutes) for which the room that is in the guest occupancy mode needs to be unoccupied before the temperature setback is initiated.  This feature prevents initiating temperature setback prematurely while the guest is still in the room but in an area where occupancy cannot be detected by the occupancy sensor.  Setting the “Temperature Setback Delay - Cool” to “00”, disables the setback in the cool mode. Set to “00” to disable EMS.   Custom Energy Savings Settings
3515 – MAXIMUM SETBACK TEMPERATURE 72-92   (78°F* default setting) Select the “Maximum Setback Temperature” in °F.  Setback temperature is calculated by measuring PTAC unit’s ability to attain “Recovery Temperature - Cool” within “Temperature Recovery Time”.   If recovery is disabled (“Temperature Recovery Time” is set to “0”) or if setback temperatures have not yet been calculated, the “Maximum Setback Temperature” value will be used as the setback temperature for cooling.  If calculated setback temperature for air conditioning is higher than “Maximum Setback Temperature”, then the “Maximum Setback Temperature” will be used as setback temperature for air conditioning.  This feature allows defining the maximum temperature in a room when room is unoccupied and the thermostat is in the setback mode.  Custom Energy Savings Settings
3616 – RECOVERY TEMPERATURE - COOL 62-82   (74°F* default setting) Select the room temperature in °F that a PTAC unit will have to attain within the selected “Temperature Recovery Time” when there is a need for air conditioning. Custom Energy Savings Settings
3717 – MINIMUM SET POINT 64-84   (66°F* default setting) Select the minimum set point in °F that a guest can select. Custom Energy Savings Settings
3818 – MAXIMUM SET POINT 60-82   (78°F* default setting) Select the maximum set point in °F that a guest can select.Custom Energy Savings Settings
3919 – TEMPERATURE CONTROL MODESelect Temperature Control Mode: 00   MANUAL - Allows users to select HEAT only or COOL only temperature control mode to maintain the room temperature; 01 *  AUTOMATIC - Thermostat automatically turns on heating or air conditioning to maintain the room temperature at the selected temperature set point; *   Indicates default setting;Custom Energy Savings Settings
4020 – AUTO CHANGEOVER SET POINT OFFSET (DEAD BAND) 00-04   (01°F* default setting) Select the difference between the guest-selected set point and the heat and the cool set point when the thermostat is in the automatic temperature control mode.   This value plus the 1st stage differential defined in steps 02 and 04, defines the temperature at which the thermostat would automatically change heating/cooling modes.  This feature allows adjusting the dead band between the heat and the cool set points in automatic changeover mode in order to avoid the system from bouncing back and forth between heating and cooling under normal operating conditions..Custom Energy Savings Settings
4121 – SETBACK SET POINTS / AUTO-RESTORE 00   When room is unoccupied and the thermostat is in the setback mode or turned off, it will NOT maintain the temperature between heat and cool setback set points;   When guest enters the room, the thermostat will be turned off - it will not automatically restore the most recent guest settings; 01   When room is unoccupied and the thermostat is in the setback mode or turned off, it will maintain the temperature between heat and cool setback set points;   When guest enters the room, the thermostat will be turned off - it will not automatically restore the most recent guest settings; 02   When room is unoccupied and the thermostat is in the setback mode or turned off, it will NOT maintain the temperature between heat and cool setback set points;  When guest enters the room, the thermostat will automatically restore the most recent guest settings; 03 *  When room is unoccupied and the thermostat is in the setback mode or turned off, it will maintain the temperature between heat and cool setback set points;   When guest enters the room, the thermostat will automatically restore the most recent guest settings.Custom Energy Savings Settings
4222 – AUTOMATIC HUMIDITY CONTROL† 00  Disable automatic humidity control;  01 *  Enable automatic humidity control;   When “Automatic Humidity Control” is enabled, thermostat will turn on air conditioning in an unoccupied room when humidity raises above 60% and room temperature is above 72°F until either room humidity is below 55% or room temperature is below 72°F;*   Indicates default setting;†   This setting is active only on thermostats with enabled humidity features. Changing this setting on a non-humidity thermostat will have no effect on thermostat operation.   Humidity features can be enabled on compatible thermostats via remote management.   Certain models only. Additional fees apply.Custom Energy Savings Settings
4322 – TEMPERATURE CALIBRATION-5.0 – 5.0   (0.0°F* default setting) Calibrate the temperature display : -5.0°F - 5.0°F.Custom Energy Savings Settings
CONFIGURATION BUTTONNOTE: Use the “Configuration” but-ton to access Relay Settings.44ACCESSING RELAY OPTIONS ➤Press and hold the “Configuration” button;  ➤Release the “Configuration” button when the first thermostat settings screen appears; ➤Press and release the “Configuration” button again to access the Relay Settings  The thermostat must be turned on to access the thermostat settings.Relay Options
W O/BY45Relay Options1 – REVERSE RELAY OPERATIONSelect Relay Operation for Y, W, O/B outputs:C *  NORMALLY CLOSED - Thermostat activates the relay to energize the output when there is a call for it; Output is not energized when idle. O    NORMALLY OPEN - Thermostat de-activates the relay to de-energize the output when there is a call for it; Output is energized when idle.  *   Indicates default setting;  ➤Use the “Up” and “Down” buttons to change the setting value; ➤Press the “Fan” button to go to the next setting on the screen; ➤Press the “F/C” button to go to the next setting screen; ➤Press the “Power” button to save and exit thermostat settings;
IN ORDER TO ENABLE THIS MODE THE THERMOSTAT “EQUIPMENT SETTINGS” MUST BE SET TO COOL ONLY - “200” OR “201”.46Relay Options2 – COOLING ONLY “SPDT” VALVE CONTROLEnable or disable relay control for Single-Pole Double-Throw (SPDT) valve in a cooling only system that requires separate signals for opening and closing the valve: DIS*  DISABLEDENB    ENABLED *   Indicates default setting; When this mode is enabled, thermostat will energize the “Y” output to open the valve when there is a request for cooling and energize the “W” output to close the valve when there is no request for cooling. ➤Use the “Up” and “Down” buttons to change the setting value; ➤Press the “F/C” button to go to the next setting screen; ➤Press the “Power” button to save and exit thermostat settings;
IN ORDER TO ENABLE THIS MODE THE THERMOSTAT COMPRESSOR TYPE IN  THE “EQUIPMENT SETTINGS” MUST BE SET TO HEAT PUMP - “100”,“101”,“110” OR “111”.47Relay Options3 – HEAT PUMP RELAY MODESelect the Heat Pump relay mode:PTAC *  PTAC MODE - Thermostat will energize the reverse valve (“O/B”) output only when “Y” output is energized. The thermostat will energize the “O/B” output in the compressor heat or cool mode based on the “Reversing Valve” setting in the “Equipment Settings”.HP    HEAT PUMP MODE - Thermostat will also energize the reversing (“O/B”) valve output when “W” is energized in the electric heat mode and between heat pump heating cycles.  *   Indicates default setting;  ➤Use the “Up” and “Down” buttons to change the setting value; ➤Press the “F/C” button to go to the next setting screen; ➤Press the “Power” button to save and exit thermostat settings;
48Error CodesERR 1   Thermostat Temperature Sensor Hardware Defect ERR 2   Thermostat Radio Hardware Defect ERR 3   Thermostat Radio Software Defect ERR 5   Thermostat Memory DefectTroubleshooting
49APPENDIX 1 - Energy Saving PresetsSCREEN NUMBERLevel  0Level  1Level  2Level  3Level  4Level  51Fan Control Mode AUTO AUTO AUTO AUTO AUTO AUTO21st Stage Differential Heat 0.5 0.5 0.5 0.5 0.5 0.532nd Stage Differential Heat 11 1 2 2 241st Stage Differential Cool 0.5 0.5 0.5 0.5 0.5 0.55Guest Occupancy Threshold0555556Night Occupancy Threshold 1111117Force 2nd Stage Heating After 30 30 30 30 30 308Night Occupancy Start 18 19 20 21 22 239Night Occupancy End 12 11 10 9 8 710 Recovery Time 015 20 25 30 011 Recovery Temperature Heat 70 69 68 67 66 6512 Setback Delay - Heat  030 25 20 15 1013 Minimum  Setback  Temperature 67 66 65 64 63 6214 Setback Delay - Cool  030 25 20 15 1015 Maximum  Setback Tempera- 72 74 76 78 80 8216 Recovery Temperature Cool 71 72 73 74 75 7617 Minimum Set point 64 64 65 66 67 6818 Maximum Set point 82 82 80 78 76 7419 Temperature Control Mode AUTO AUTO AUTO AUTO AUTO AUTO20 Auto Changeover Set Point  11111121 Auto Restore OFF ON ON ON ON ON21 Setback Set Points OFF ON ON ON ON ON22 Automatic Humidity Control ON ON ON ON ON ON23 Temperature Calibration 000000
50“Automatic Fan Control Mode” - fan runs only when there is a demand for heating or cooling;“Manual Fan Control Mode” - guest can select between automatic or continuous fan operation; “Minimum Set point” - minimum temperature that a guest can request;“Maximum Set point” - maximum temperature that a guest can request;“Auto Changeover Set Point Offset” - the difference between the guest-selected set point and the heat and cool changeover temperatures;“1st Stage Differential - Heat” - the temperature that the thermostat has to sense between the automatic changeover temperature for heat and the room temperature before a call for the 1st stage heating is initiated;“2nd Stage Differential - Heat” - difference between 1st stage heating temperature and room temperature before the 2nd stage heating is initiated;“1st Stage Differential - Cool” - the temperature that the thermostat has to sense between the automatic changeover temperature for cool and the room temperature before a call for the 1st stage cooling is initiated;“Forced 2nd Stage Heating” - number of minutes 1st stage heating will run before 2nd stage heating is automatically initiated if the guest set point is not reached and the 2nd stage heating is not initiated through differential settings“Temperature Recovery Time” - the maximum period of time allowed for restoring the “Recovery Temperature”; “Recovery Temperature” -  the room temperature  that needs to be restored within the “Temperature Recovery Time”;“Maximum Setback Temperature” -  the highest room temperature allowed when thermostat is in the setback mode;“Minimum Setback Temperature” - the lowest room temperature allowed when thermostat is in the setback mode;“Temperature Setback Delay” - the length of time for which the room that is in the guest occupancy mode needs to be unoccupied before the temperature setback is initiated;“Incidental Occupancy Threshold” - the minimum period of time (in minutes) for which occupancy needs to be detected in order to enter the “Guest Occupancy” mode;“Night Occupancy Threshold” - the minimum period of time during the “Night Occupancy” period for which occupancy needs to be detected in order to enter the “Night Occupancy” mode;“Night Occupancy Period” - The period of time during the day during which the “Night Occupancy” mode can be activated if occupancy longer than the “Night Occupancy Threshold” is detected;“Auto Restore On” - thermostat will restore the most recent guest settings when new occupancy is detected;“Auto Restore Off” - thermostat will NOT restore the most recent guest and will remain turned off settings when new occupancy is detected;“Setback Set points On” - thermostat will maintain setback temperatures when room is unoccupied; “Setback Set points Off” - thermostat will NOT maintain setback temperatures when room is unoccupied; “Incidental Occupancy” - occupancy shorter than the “Incidental Occupancy Threshold”; “Guest Occupancy” - occupancy longer than the “Incidental Occupancy Threshold”; “Temperature Setback” - thermostat maintains setback temperatures and not the guest set point temperature in order to save energy; “Night Occupancy Mode” - thermostat status during which setback mode is disabled if occupancy longer than “Night Occupancy Threshold” is detected within the “Nigh Occupancy” period;“Automatic Temperature Changeover” - thermostat automatically activates heating or cooling to maintain the desired room temperature;“External Thermostat” (Class 2) mode - PTAC unit setting allowing it to be controlled by a remote thermostat;APPENDIX 2 - Glossary
51Warranty InformationHardwareVerdant  Environmental  Technologies  Inc.  (“Verdant”)  warrants  the  original  end  user (“Customer”) that new Verdant branded products will be free from defects in workmanship and materials, under normal use, for one (1) year from the original purchase date.SoftwareVerdant  warrants  to  Customer  that  the  Verdant  thermostat  software  will  perform  in substantial conformance to its program specifications for a period of one (1) year from the date of the original purchase.ExclusionsThis  warranty  excludes (1)  physical  damage  to  the  surface of  the  product,  including  cracks, scratches  or marks  on  the  screen or  outside  casing;  (2) damage  caused  by  misuse,  neglect, improper installation, unauthorized  attempts to open, repair,  or  modify the product, or  any other  cause  beyond  the  range  of  intended  use;  (3)  damage  caused  by  accident,  fire,  power changes, other hazard, or Acts of God; (4) damage caused by water, liquids, or foreign chemicals including condensation and humidity; or (5) use of the product with any device if such device causes the problem.Exclusive RemediesShould  a  covered  defect  occur  during  the  warranty  period  and  Customer  notifies  Verdant, Customer’s sole and exclusive remedy will be, at Verdant’s sole option and expense, to repair or  replace  the  product.  Replacement  products  or  parts  may  be  new  or  reconditioned  or a  comparable version  of  the  defective  item. Verdant  warrants  any  replaced product  or  part for a period of ninety (90) days from shipment, or through the end of the original warranty, whichever is longer.Obtaining Warranty ServiceTo obtain Warranty Service customer must follow Verdant’s “Warranty Service Procedure” and request a  Return Merchandise  Authorization (RMA) number  by filling  out the RMA  Request Form on Verdant’s website.Warranty ExclusiveTHE  FORGOING WARRANTIES  AND  REMEDIES  ARE EXCLUSIVE  AND  IN LIEU  OF  ALL  OTHER WARRANTIES,  EXPRESS  OR  IMPLIED,  INCLUDING  WARRANTIES  OF  MERCHANTABILITY, FITNESS FOR  A PARTICULAR PURPOSE,  CORRESPONDENCE WITH DESCRIPTION,  AND NON-INFRINGEMENT, ALL OF WHICH ARE EXPRESSLY DISCLAIMED BY VERDANT AND ITS SUPPLIERS.DisclaimerNEITHER VERDANT NOR ITS SUPPLIERS SHALL BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, INDIRECT, SPECIAL, OR PUNITIVE DAMAGES OF ANY KIND, OR FINANCIAL LOSS ARISING OUT OF  OR  IN  CONNECTION  WITH  THE  SALE  OR  USE  OF  THIS  PRODUCT,  WHETHER  BASED  IN CONTRACT, TORT (INCLUDING NEGLIGENCE) OR ANY OTHER THEORY, EVEN IF VERDANT HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. VERDANT’S ENTIRE LIABILITY SHALL BE LIMITED TO REPLACEMENT OR REPAIR OF THE PRODUCT.
Technical SpecificationsCOVERED BY ONE OR MORE OF THE FOLLOWING PATENTS. US PATENTS: 8,369,994; 8,141,791; 7,918,406; 7,232,075; 7,185,825; 7,156,318; 7,152,806; 7,145,110; 7,050,026; 7,028,912; 6,902,117; 6,789,739; 6,786,421; 6,619,555; 6,581,846; 6,578,770; 7,838,803; 7,841,542; D556,061; D518,744; RE40,437; CANADIAN PATENTS: 2,633,113; 2,633,200; OTHER PATENTS PENDING. Verdant Environmental Technologies, Inc. reserves the right to make changes, without notice, in design or components. Product appearance may vary. © Verdant Environmental Technologies, Inc. 2015. Printed in Canada.   V.5   MAY 31, 2016TECHNICAL SUPPORT:  support@verdant.info  1-888-440-0991THIS  DEVICE  COMPLIES  WITH  PART  15  OF  THE  FCC  RULES.  OPERATION  IS  SUBJECT TO  THE  FOLLOWING  TWO  CONDITIONS:  (1)  THIS  DEVICE  MAY  NOT  CAUSE  HARMFUL INTERFERENCE,  AND  (2)  THIS  DEVICE  MUST  ACCEPT  ANY  INTERFERENCE  RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION. PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.ThermostatCase Dimensions (Imperial)  5.125 x 4.6875” x 1.25”Case Dimensions (Metric) 130mm x 119mm x 32mmScreen Dimensions (Imperial)  3.625" x 2.125"Screen Dimensions (Metric)  92mm x 54mmOperating Voltage24V AC/DCControl Outputs Fan High (GH)Fan Low (GL)Compressor (Y)Heat Pump (OB)Electric Heat (W2)Occupancy Sensor Beam Width±47° (94°)Wireless Frequency 900MHzTemperature Accuracy ±1°FFCC ID XEYVIC 8410A-V

Navigation menu