VX Series Thermostat
with an Occupancy Sensor
INSTALLATION MANUAL
V.5
MAY 31, 2016
Table of Contents
Introduction..................................................................................................5
Before You Begin...........................................................................................8
Programming a Thermostat with a Network Programmer..........................9
Thermostat Installation.............................................................................. 10
Thermostat Configuration........................................................................... 11
Setting the thermostat clock....................................................................... 12
Entering the room number.......................................................................... 13
Configuring the Equipment Settings - Compressor Type............................14
Configuring the Equipment Settings - Electric Heat...................................15
Configuring the Equipment Settings - Reversing Valve..............................16
Configuring the Energy Saving Settings . ................................................... 17
Testing the thermostat................................................................................18
Accessing the Thermostat Settings.............................................................19
Custom Energy Savings Settings.................................................................19
Using the Thermostat Settings Screens..................................................... 20
01 – FAN CONTROL MODE........................................................................... 21
02 – 1ST STAGE DIFFERENTIAL - HEAT...........................................................22
03 – 2ND STAGE DIFFERENTIAL - HEAT..........................................................23
04 – 1ST STAGE DIFFERENTIAL - COOL........................................................ 24
05 – INCIDENTAL OCCUPANCY THRESHOLD.............................................. 25
06 – NIGHT OCCUPANCY THRESHOLD....................................................... 26
07 – FORCED 2ND STAGE HEATING..............................................................27
08 – NIGHT OCCUPANCY START................................................................. 28
09 – NIGHT OCCUPANCY END.................................................................... 29
10 – TEMPERATURE RECOVERY TIME......................................................... 30
11 – RECOVERY TEMPERATURE - HEAT......................................................... 31
12 – TEMPERATURE SETBACK DELAY - HEAT................................................32
13 – MINIMUM SETBACK TEMPERATURE . ................................................. 33
14 – TEMPERATURE SETBACK DELAY - COOL.............................................. 34
15 – MAXIMUM SETBACK TEMPERATURE................................................... 35
16 – RECOVERY TEMPERATURE - COOL...................................................... 36
17 – MINIMUM SET POINT............................................................................37
Table of Contents
18 – MAXIMUM SET POINT.......................................................................... 38
19 – TEMPERATURE CONTROL MODE......................................................... 39
20 – AUTO CHANGEOVER SET POINT OFFSET............................................40
21 – SETBACK SET POINTS / AUTO-RESTORE...............................................41
22 – AUTOMATIC HUMIDITY CONTROL†...............................................................................................42
22 – TEMPERATURE CALIBRATION.............................................................. 43
Relay Options..............................................................................................44
ACCESSING RELAY OPTIONS....................................................................... 44
1 – REVERSE RELAY OPERATION................................................................. 45
2 – COOLING ONLY “SPDT” VALVE CONTROL.............................................. 46
3 – HEAT PUMP RELAY MODE......................................................................47
Troubleshooting..........................................................................................48
Error Codes.................................................................................................. 48
APPENDIX 1 - Energy Saving Presets...........................................................49
APPENDIX 2 - Glossary.................................................................................50
Warranty Information..................................................................................51
Technical Specifications.............................................................................. 52
Introduction
Verdant VX Series Energy Management Thermostats for the hospitality
industry deliver unprecedented energy savings without compromising
guest comfort.
Integrated occupancy sensor uses a combination of motion and thermal
sensing technologies for accurate occupancy detection. Reliable
occupancy detection allows saving energy when rooms are unoccupied.
Energy saving presets eliminate the guesswork and make it easy to
adjust the energy saving settings. (Patent Pending)
Fully configurable energy saving settings allow customizing the
thermostat energy saving settings to fit any situation.
Comprehensive configuration options ensure full compatibility with
virtually any existing or emerging hospitality HVAC system with up to 2
heat and 1 cool stages.
Built-in wireless mesh-networking enables optional remote management.
6
NOTICE
FOR INSTALLATION OF NETWORKING THERMOSTATS WITH
REMOTE MANAGEMENT, REFER TO THE “VX-TR NETWORK
INSTALLATION” MANUAL.
LOGIN TO THE REMOTE MANAGEMENT WEBSITE TO CONFIRM
THE SERVER IS CONNECTED TO THE INTERNET BEFORE
INSTALLING THERMOSTATS.
DO NOT INSTALL THERMOSTATS IF THE SERVER IS NOT
CONNECTED TO THE INTERNET. STOP THE INSTALLATION AND
CONTACT VERDANT TECHNICAL SUPPORT.
START BY FIRST INSTALLING A THERMOSTAT IN THE ROOM
CLOSEST TO THE SERVER.
LOG IN TO VERDANT’S REMOTE MANAGEMENT WEBSITE
TO CONFIRM THAT THE THERMOSTAT IS ON THE REMOTE
MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER.
CONTINUE BY INSTALLING ADDITIONAL THERMOSTATS IN
ADJACENT ROOMS ONLY AFTER CONFIRMING THAT INSTALLED
THERMOSTAT(S) HAVE CONNECTED TO THE WIRELESS NETWORK
AND THE REMOTE MANAGEMENT WEBSITE .
IF INSTALLED THERMOSTAT(S) ARE NOT CONNECTING TO THE
NETWORK AND DO NOT APPEAR ON THE VERDANT’S REMOTE
MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER,
STOP THE INSTALLATION AND CONTACT VERDANT TECHNICAL
SUPPORT
THE ROOMS FURTHEST AWAY FROM THE SERVER SHOULD BE
INSTALLED LAST.
Before You Begin
➤➤
Determine the appropriate installation location for the thermostat.
THERMOSTAT SHOULD FACE THE BED AREA OF THE ROOM.
THERMOSTAT MUST NOT BE INSTALLED NEAR OR ON METAL
STRUCTURES OR SURFACES INCLUDING METAL AIR DUCTING
THAT MAY BE IN THE WALL.
METAL STRUCTURES AND SURFACES SIGNIFICANTLY REDUCE
THE RANGE OF THE WIRELESS SIGNAL.
➤➤
Set the HVAC unit to “External Thermostat” (Class 2) mode. Consult
the HVAC unit documentation to determine how to set the HVAC
unit to “External Thermostat” mode.
Before You Begin
Programming a Thermostat with a Network Programmer
In case of Network Installation with Remote Management, the
thermostat must be programmed with a Network Programmer
specific to the property before the installation.
Thermostat must not be powered during the programming procedure..
➤➤
Plug one programmer connector into the thermostat;
➤➤
Push the black button on the programmer. The red light on the
programmer should turn on and remain steadily lit;
If the red light on the programmer is blinking or is not steadily lit,
unplug the programmer from the thermostat and repeat the steps
above.
➤➤
Unplug the programmer from the thermostat;
Thermostat Installation
Mounting the thermostat to the wall
➤➤
Power of the HVAC unit;
➤➤
Remove the thermostat cover;
➤➤
Connect the thermostat wires to the supplied Wiring Harness - refer
to the Wiring Table to determine proper connections;
➤➤
Plug in the Wiring Harness into to the thermostat;
➤➤
Use the supplied wall anchors and mounting screws to secure the
thermostat to the wall;
➤➤
Follow the “Thermostat Configuration” instructions;
➤➤
Replace the thermostat cover and screw in the locking screw;
➤➤
Power on the HVAC unit.
Wiring Table - 24V AC
Wire
Color
Wiring Table - 24V DC
Terminal
Letter
Terminal
Connection
Wire
Color
Terminal
Letter
Terminal
Connection
Black
Common
Black
24V
Red
24V
Red
Common
Yellow
Compressor
Yellow
Compressor
White
Heat
White
Heat
Orange
O or B
Reverse Valve
Orange
O or B
Reverse Valve
Green
GH
Fan High
Green
GH
Fan High
Purple
GL
Fan Low
Purple
GL
Fan Low
NOTE: If the PTAC unit has only one (1) fan speed, connect both fan
control wires – Green and Purple – to the fan terminal (G).
10
Thermostat Configuration
Once the thermostat is powered, thermostat configuration settings will
appear on the thermostat screen.
In order to properly operate the PTAC unit:
➤➤
Set the thermostat clock;
➤➤
Enter the room number;
➤➤
Configure the equipment settings;
➤➤
Select Energy Savings Preset;
The thermostat configuration screens have a 3-minute time-out. If
no action is taken within three (3) minutes, the thermostat will exit
configuration settings.
CONFIGURATION
BUTTON
NOTE: You can access Thermostat
Configuration settings at any time by
pressing the “Configuration” button.
NOTE: If the thermostat is connected to a network, the equipment
and the energy saving settings configured on the thermostat will
be ignored and the settings configured on the Remote Management
Website will be applied.
11
Thermostat Configuration
Setting the thermostat clock
HOURS
MINUTES
Set the thermostat clock to current time in 24h (Military Time) format.
➤➤
Use the “Up” and “Down” buttons to set the hours;
➤➤
Press the “Fan” button to advance to the minutes setting;
➤➤
Use the “Up” an “Down” buttons to set the minutes;
➤➤
Press the “F/C” button to advance to the next menu;
Setting the clock correctly is crucial for proper operation of the
thermostat.
12
Thermostat Configuration
Entering the room number
Enter the room number by changing the digits on the screen. Leading
zeros “0” preceding other digits will be ignored, i.e. Room number “123”
should be entered as “00123”.
➤➤
Use the “Up” and “Down” buttons to change the digit;
➤➤
Press the “Fan” button advance to the next digit;
➤➤
Press the “F/C” button to advance to the next menu;
Entering the room number correctly is crucial for proper operation of
remotely managed thermostats.
13
Thermostat Configuration
Configuring the Equipment Settings - Compressor Type
COMPRESSOR TYPE
➤➤
2*
➤➤
Use the “Up” and “Down” buttons to change the compressor type by
changing the first digit;
No Compressor
Heat Pump
Air Conditioner
Press the “Fan” button to advance to the next setting;
Indicates default setting;
CERTAIN HEAT PUMP UNITS REQUIRE ENERGIZING THE
REVERSING (“O/B”) VALVE WHEN (i) “W” IS ENERGIZED IN THE
ELECTRIC HEAT MODE (ii) BETWEEN HEAT PUMP CYCLES.
TO ENABLE THIS FEATURE, REFER TO “RELAY OPTIONS”.
14
Thermostat Configuration
Configuring the Equipment Settings - Electric Heat
ELECTRIC HEAT
➤➤
1*
➤➤
Use the “Up” and “Down” buttons to change the Electric Heat setting
by changing the second digit;
No Electric Heat
Electric Heat
Press the “Fan” button to advance to the next setting;
Indicates default setting;
15
Thermostat Configuration
Configuring the Equipment Settings - Reversing Valve
REVERSING VALVE
➤➤
Use the “Up” and “Down” buttons to change the Reversing Valve
setting by changing the third digit;
1*
O/B contact is energized to cool;
O/B contact is energized to heat;
Refer to the PTAC unit documentation to determine the correct
reversing valve setting. If incorrect reverse valve setting is selected,
the PTAC unit will turn on the heating when air conditioning
is requested and turn on the air conditioning when heating is
requested;
➤➤
Press the “Fan” button to advance to the next setting;
➤➤
Press the “F/C” button to advance to the next menu;
Indicates default setting;
CERTAIN HEAT PUMP UNITS REQUIRE ENERGIZING THE
REVERSING (“O/B”) VALVE WHEN (i) “W” IS ENERGIZED IN THE
ELECTRIC HEAT MODE (ii) BETWEEN HEAT PUMP CYCLES.
TO ENABLE THIS FEATURE, REFER TO “RELAY OPTIONS”.
16
Thermostat Configuration
Configuring the Energy Saving Settings
➤➤
Use the “Up” and “Down” buttons to select the Energy Saving preset:
E-0*
E-1
E-2
E-3
E-4
E-5
Energy Savings Off - No Temperature Setback;
Lowest Energy Savings;
Lower Energy Savings;
Standard Energy Savings;
Higher Energy Savings;
Highest Energy Savings;
Refer to the APPENDIX 1 for Energy Saving Preset details.
E-C
Indicates “Custom Energy Savings Settings” in case the active
thermostat savings settings differ from any Energy Saving preset;
For details, refer to the “Custom Energy Savings Settings” section;
➤➤
Press the “Power” button to save the Thermostat Configuration and
start using the thermostat;
Indicates default setting;
17
Thermostat Configuration
Testing the thermostat
Following the thermostat configuration, test if the thermostat is controlling
the PTAC unit.
➤➤
Press the “Power” button to turn the thermostat ON;
➤➤
Press the “Down” button to change the temperature set point below
the current room temperature to confirm that the thermostat
initiates air conditioning.
➤➤
Press the “Up” button to change the temperature set point above
the current room temperature to confirm that the thermostat
initiates heating.
➤➤
Change the fan speed by touching the “Fan” button to test if the
thermostat is controlling the fan speed.
18
Custom Energy Savings Settings
If you don’t want to use the one of the energy saving presets, you can
enter custom energy savings settings.
Accessing the Thermostat Settings
➤➤
Press and hold the “Configuration” button until the first thermostat
settings screen appears.
The thermostat must be turned on to access the thermostat settings.
CONFIGURATION
BUTTON
NOTE: You can access Thermostat
Settings by pressing and holding
the “Configuration” button.
NOTE: If the thermostat is connected to a network, the equipment
and the energy saving settings configured on the thermostat will
be ignored and the settings configured on the Remote Management
Website will be applied.
19
Custom Energy Savings Settings
Using the Thermostat Settings Screens
SETTING VALUE
SCREEN NUMBER
➤➤
Use the “Up” and “Down” buttons to change the setting;
➤➤
Press the “F/C” button to advance to the next setting;
➤➤
Press the “Fan” button to return to the previous setting;
➤➤
Press the “Power” button to save and exit thermostat settings;
20
Custom Energy Savings Settings
01 – FAN CONTROL MODE
Select Fan Control Mode:
00
01 *
MANUAL - guest can select automatic or continuous fan mode;
AUTOMATIC - fan runs only when there is a demand for
heating or air conditioning;
Indicates default setting;
21
Custom Energy Savings Settings
02 – 1ST STAGE DIFFERENTIAL - HEAT
02-30
22
(0.2°F - 3.0°F; 0.5°F* default setting) Select the number of
degrees the thermostat has to sense between the automatic
changeover temperature for heat and the room temperature
before a call for the 1st stage heating is initiated.
Custom Energy Savings Settings
03 – 2ND STAGE DIFFERENTIAL - HEAT
10-20
(1.0°F - 2.0°F*; 2.0°F* default setting) Select the difference
between 1st stage heating and 2nd stage heating initiation.
23
Custom Energy Savings Settings
04 – 1ST STAGE DIFFERENTIAL - COOL
02-30
24
(0.2°F - 3.0°F; 0.5°F* default setting) Select the number of
degrees the thermostat has to sense between the automatic
changeover temperature for cool and the room temperature
before a call for the 1st stage cooling is initiated.
Custom Energy Savings Settings
05 – INCIDENTAL OCCUPANCY THRESHOLD
00-60
(05* default setting) Select the minimum period of time (in
minutes) for which occupancy needs to be detected to enter
the guest occupancy mode.
When occupancy is detected, thermostat will switch to
occupied mode for a duration of “Incidental Occupancy
Threshold” selected here.
If occupancy is detected for a period of time shorter than the
“Incidental Occupancy Threshold” selected here, the thermostat
will automatically revert to unoccupied mode at the end of
the “Incidental Occupancy Threshold” period and continue to
observe energy saving functions that were in effect before the
room became occupied. This setting allows ignoring incidental
room visits.
If occupancy is detected for a period of time longer than the
“Incidental Occupancy Threshold” selected here, the thermostat
will enter the guest occupancy mode. When the thermostat
is in the guest occupancy mode, it will revert to unoccupied
mode and initiate the setback temperature only when
occupancy is not detected for the duration of the setback delay
(Heat or Cool) period.
25
Custom Energy Savings Settings
06 – NIGHT OCCUPANCY THRESHOLD
00-60
(01* default setting) Select the minimum period of time
(in minutes) for which occupancy needs to be detected
in order to consider the room occupied during the “Night
Occupancy”period.
When occupancy is detected during the “Night Occupancy
Period” for longer than the “Night Occupancy Threshold”
selected here, the thermostat will instantaneously switch to
occupied mode.
If occupancy is detected for a period of time shorter than the
“Night Occupancy Threshold” selected here, the thermostat
will automatically revert to unoccupied mode and continue to
observe energy saving functions that were in effect before the
room became occupied.
If occupancy is detected for a period of time longer than the
“Night Occupancy Threshold” selected here, the thermostat will
disable the occupancy sensor and consider the room occupied
until the end of the “Night Occupancy” period.
This feature ensures that energy saving functions that may
affect guest comfort will not come in effect during the “Night
Occupancy” period.
26
Custom Energy Savings Settings
07 – FORCED 2ND STAGE HEATING
00-60
(30* default setting) Select a number of minutes 1st stage
heating will run before 2nd stage heating is automatically
initiated if the guest set point is not reached and the 2nd stage
heating is not initiated through differential settings.
This feature allows automatically turning on 2nd stage heating
to avoid excessive compressor use.
Set to
00 to disable the feature.
27
Custom Energy Savings Settings
08 – NIGHT OCCUPANCY START
00-23
(21* default setting) Select the start time (in hours - 24-hour
clock) for “Night Occupancy”
If occupancy is detected for a period of time longer than the
“Night Occupancy Threshold” during “Night Occupancy” period,
the thermostat will disable the occupancy sensor and consider
the room occupied until the end of the “Night Occupancy”
period.
This feature ensures that energy saving functions that may
affect guest comfort will not come in effect during the “Night
Occupancy” period if room was occupied for a period of time
longer than “Night Occupancy Threshold”.
28
Custom Energy Savings Settings
09 – NIGHT OCCUPANCY END
00-23
(09* default setting) Select the time (in hours - 24-hour clock)
for “Night Occupancy” to end.
The time of day the “Night Occupancy” ends and the
thermostat switches back to the room sensing settings chosen
in the other occupancy modes.
29
Custom Energy Savings Settings
10 – TEMPERATURE RECOVERY TIME
00-60
(25* default setting) Select the maximum time allowed for a
PTAC unit to attain temperature as defined by Heat and Cool
“Recovery Temperature”.
“Temperature Recovery Time” selected here and the actual
temperature recovery ability of the PTAC unit are used
to calculate setback temperatures. Calculated setback
temperatures maximize energy savings and at the same time
ensure that a comfortable room temperature (defined as Heat
and Cool “Recovery Temperature”) will be restored within the
selected “Temperature Recovery Time”.
Setting the “Temperature Recovery Time” to “00”, disables
temperature recovery. When temperature recovery is disabled,
thermostat will use the Minimum and Maximum Setback
Temperatures as setback set points.
30
Custom Energy Savings Settings
11 – RECOVERY TEMPERATURE - HEAT
62-82
(67°F* default setting) Select the room temperature in °F that a
PTAC unit will have to attain within the selected “Temperature
Recovery Time” when there is a need for heating.
31
Custom Energy Savings Settings
12 – TEMPERATURE SETBACK DELAY - HEAT
00-120
(20* default setting) Select the time delay (in minutes) for
which the room that is in the guest occupancy mode needs to
be unoccupied before the temperature setback is initiated.
This feature prevents initiating temperature setback
prematurely while the guest is still in the room but in an area
where occupancy cannot be detected by the occupancy sensor.
Setting the “Temperature Setback Delay - Heat” to “00”, disables
the setback in the heat mode. Set to “00” to disable EMS.
32
Custom Energy Savings Settings
13 – MINIMUM SETBACK TEMPERATURE
52-72
(64°F* default setting) Select the “Minimum Setback
Temperature” in °F.
Setback temperature is calculated by measuring PTAC unit’s
ability to attain “Recovery Temperature - Heat” within
“Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is set to
“0”) or if setback temperatures have not yet been calculated,
the “Minimum Setback Temperature” value will be used as the
setback temperature for heating.
If calculated setback temperature for heating is lower than
“Minimum Setback Temperature”, then the “Minimum Setback
Temperature” will be used as setback temperature for heating.
This feature allows defining the minimum temperature in a
room when room is unoccupied and the thermostat is in the
setback mode.
33
Custom Energy Savings Settings
14 – TEMPERATURE SETBACK DELAY - COOL
00-120
(20* default setting) Select the time delay (in minutes) for
which the room that is in the guest occupancy mode needs to
be unoccupied before the temperature setback is initiated.
This feature prevents initiating temperature setback
prematurely while the guest is still in the room but in an area
where occupancy cannot be detected by the occupancy sensor.
Setting the “Temperature Setback Delay - Cool” to “00”, disables
the setback in the cool mode. Set to “00” to disable EMS.
34
Custom Energy Savings Settings
15 – MAXIMUM SETBACK TEMPERATURE
72-92
(78°F* default setting) Select the “Maximum Setback
Temperature” in °F.
Setback temperature is calculated by measuring PTAC
unit’s ability to attain “Recovery Temperature - Cool” within
“Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is set to
“0”) or if setback temperatures have not yet been calculated,
the “Maximum Setback Temperature” value will be used as the
setback temperature for cooling.
If calculated setback temperature for air conditioning is higher
than “Maximum Setback Temperature”, then the “Maximum
Setback Temperature” will be used as setback temperature for
air conditioning.
This feature allows defining the maximum temperature in a
room when room is unoccupied and the thermostat is in the
setback mode.
35
Custom Energy Savings Settings
16 – RECOVERY TEMPERATURE - COOL
62-82
36
(74°F* default setting) Select the room temperature in °F that a
PTAC unit will have to attain within the selected “Temperature
Recovery Time” when there is a need for air conditioning.
Custom Energy Savings Settings
17 – MINIMUM SET POINT
64-84
(66°F* default setting) Select the minimum set point in °F that
a guest can select.
37
Custom Energy Savings Settings
18 – MAXIMUM SET POINT
60-82
38
(78°F* default setting) Select the maximum set point in °F that
a guest can select.
Custom Energy Savings Settings
19 – TEMPERATURE CONTROL MODE
Select Temperature Control Mode:
00
01 *
MANUAL - Allows users to select HEAT only or COOL only
temperature control mode to maintain the room temperature;
AUTOMATIC - Thermostat automatically turns on heating or
air conditioning to maintain the room temperature at the
selected temperature set point;
Indicates default setting;
39
Custom Energy Savings Settings
20 – AUTO CHANGEOVER SET POINT OFFSET (DEAD BAND)
00-04
(01°F* default setting) Select the difference between the guestselected set point and the heat and the cool set point when
the thermostat is in the automatic temperature control mode.
This value plus the 1st stage differential defined in steps 02 and
04, defines the temperature at which the thermostat would
automatically change heating/cooling modes.
This feature allows adjusting the dead band between the heat
and the cool set points in automatic changeover mode in order
to avoid the system from bouncing back and forth between
heating and cooling under normal operating conditions.
40
Custom Energy Savings Settings
21 – SETBACK SET POINTS / AUTO-RESTORE
00
01
02
03 *
When room is unoccupied and the thermostat is in the setback
mode or turned off, it will NOT maintain the temperature
between heat and cool setback set points;
When guest enters the room, the thermostat will be turned off it will not automatically restore the most recent guest settings;
When room is unoccupied and the thermostat is in the setback
mode or turned off, it will maintain the temperature between
heat and cool setback set points;
When guest enters the room, the thermostat will be turned off it will not automatically restore the most recent guest settings;
When room is unoccupied and the thermostat is in the setback
mode or turned off, it will NOT maintain the temperature
between heat and cool setback set points;
When guest enters the room, the thermostat will automatically
restore the most recent guest settings;
When room is unoccupied and the thermostat is in the setback
mode or turned off, it will maintain the temperature between
heat and cool setback set points;
When guest enters the room, the thermostat will automatically
restore the most recent guest settings.
41
Custom Energy Savings Settings
22 – AUTOMATIC HUMIDITY CONTROL†
00
01 *
Disable automatic humidity control;
Enable automatic humidity control;
When “Automatic Humidity Control” is enabled, thermostat
will turn on air conditioning in an unoccupied room when
humidity raises above 60% and room temperature is above 72°F
until either room humidity is below 55% or room temperature
is below 72°F;
Indicates default setting;
†
This setting is active only on thermostats with enabled
humidity features. Changing this setting on a non-humidity
thermostat will have no effect on thermostat operation.
Humidity features can be enabled on compatible thermostats
via remote management.
Certain models only. Additional fees apply.
42
Custom Energy Savings Settings
22 – TEMPERATURE CALIBRATION
-5.0 – 5.0
(0.0°F* default setting) Calibrate the temperature display :
-5.0°F - 5.0°F.
43
Relay Options
ACCESSING RELAY OPTIONS
➤➤
Press and hold the “Configuration” button;
➤➤
Release the “Configuration” button when the first thermostat
settings screen appears;
➤➤
Press and release the “Configuration” button again to access the
Relay Settings
The thermostat must be turned on to access the thermostat settings.
CONFIGURATION
BUTTON
NOTE: Use the “Configuration” button to access Relay Settings.
44
Relay Options
1 – REVERSE RELAY OPERATION
O/B
Select Relay Operation for Y, W, O/B outputs:
C*
NORMALLY CLOSED - Thermostat activates the relay to
energize the output when there is a call for it; Output is not
energized when idle.
NORMALLY OPEN - Thermostat de-activates the relay to
de-energize the output when there is a call for it; Output is
energized when idle.
Indicates default setting;
➤➤
Use the “Up” and “Down” buttons to change the setting value;
➤➤
Press the “Fan” button to go to the next setting on the screen;
➤➤
Press the “F/C” button to go to the next setting screen;
➤➤
Press the “Power” button to save and exit thermostat settings;
45
Relay Options
2 – COOLING ONLY “SPDT” VALVE CONTROL
Enable or disable relay control for Single-Pole Double-Throw (SPDT) valve
in a cooling only system that requires separate signals for opening and
closing the valve:
DIS*
ENB
ENABLED
Indicates default setting;
DISABLED
When this mode is enabled, thermostat will energize the “Y” output to
open the valve when there is a request for cooling and energize the “W”
output to close the valve when there is no request for cooling.
IN ORDER TO ENABLE THIS MODE THE THERMOSTAT “EQUIPMENT
SETTINGS” MUST BE SET TO COOL ONLY - “200” OR “201”.
➤➤
Use the “Up” and “Down” buttons to change the setting value;
➤➤
Press the “F/C” button to go to the next setting screen;
➤➤
Press the “Power” button to save and exit thermostat settings;
46
Relay Options
3 – HEAT PUMP RELAY MODE
Select the Heat Pump relay mode:
PTAC *
HP
PTAC MODE - Thermostat will energize the reverse valve
(“O/B”) output only when “Y” output is energized. The
thermostat will energize the “O/B” output in the compressor
heat or cool mode based on the “Reversing Valve” setting in the
“Equipment Settings”.
HEAT PUMP MODE - Thermostat will also energize the
reversing (“O/B”) valve output when “W” is energized in the
electric heat mode and between heat pump heating cycles.
Indicates default setting;
IN ORDER TO ENABLE THIS MODE THE THERMOSTAT
COMPRESSOR TYPE IN THE “EQUIPMENT SETTINGS” MUST BE SET
TO HEAT PUMP - “100”,“101”,“110” OR “111”.
➤➤
Use the “Up” and “Down” buttons to change the setting value;
➤➤
Press the “F/C” button to go to the next setting screen;
➤➤
Press the “Power” button to save and exit thermostat settings;
47
Troubleshooting
Error Codes
ERR 1
Thermostat Temperature Sensor Hardware Defect
ERR 2
Thermostat Radio Hardware Defect
ERR 3
Thermostat Radio Software Defect
ERR 5
Thermostat Memory Defect
48
SCREEN
NUMBER
APPENDIX 1 - Energy Saving Presets
Level
Level
Level
Level
Level
Level
AUTO AUTO AUTO AUTO AUTO AUTO
Fan Control Mode
1st Stage Differential Heat
0.5
0.5
0.5
0.5
0.5
2nd Stage Differential Heat
1st Stage Differential Cool
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Guest Occupancy Threshold
Night Occupancy Threshold
Force 2nd Stage Heating After
30
30
30
30
30
30
Night Occupancy Start
18
19
20
21
22
23
Night Occupancy End
12
11
10
10
Recovery Time
15
20
25
30
11
Recovery Temperature Heat
70
69
68
67
66
65
12
Setback Delay - Heat
30
25
20
15
10
13
Minimum Setback Temperature
67
66
65
64
63
62
14
Setback Delay - Cool
30
25
20
15
10
15
Maximum Setback Tempera-
72
74
76
78
80
82
16
Recovery Temperature Cool
71
72
73
74
75
76
17
Minimum Set point
64
64
65
66
67
68
18
Maximum Set point
82
82
80
78
76
74
19
Temperature Control Mode
20
Auto Changeover Set Point
21
21
AUTO AUTO AUTO AUTO AUTO AUTO
Auto Restore
OFF
ON
ON
ON
ON
ON
Setback Set Points
OFF
ON
ON
ON
ON
ON
22
Automatic Humidity Control
ON
ON
ON
ON
ON
ON
23
Temperature Calibration
49
APPENDIX 2 - Glossary
“Automatic Fan Control Mode” - fan runs only
when there is a demand for heating or cooling;
“Manual Fan Control Mode” - guest can select
between automatic or continuous fan operation;
“Minimum Set point” - minimum temperature
that a guest can request;
“Maximum Set point” - maximum temperature
that a guest can request;
“Incidental Occupancy Threshold” - the minimum
period of time (in minutes) for which occupancy
needs to be detected in order to enter the “Guest
Occupancy” mode;
“Night Occupancy Threshold” - the minimum
period of time during the “Night Occupancy”
period for which occupancy needs to be detected
in order to enter the “Night Occupancy” mode;
“Auto Changeover Set Point Offset” - the
difference between the guest-selected set point
and the heat and cool changeover temperatures;
“Night Occupancy Period” - The period of
time during the day during which the “Night
Occupancy” mode can be activated if occupancy
longer than the “Night Occupancy Threshold”
is detected;
“1st Stage Differential - Heat” - the temperature
that the thermostat has to sense between the
automatic changeover temperature for heat and
the room temperature before a call for the 1st
stage heating is initiated;
“Auto Restore On” - thermostat will restore the
most recent guest settings when new occupancy
is detected;
“2nd Stage Differential - Heat” - difference
between 1st stage heating temperature and
room temperature before the 2nd stage heating
is initiated;
“1st Stage Differential - Cool” - the temperature
that the thermostat has to sense between the
automatic changeover temperature for cool and
the room temperature before a call for the 1st
stage cooling is initiated;
“Forced 2nd Stage Heating” - number of minutes
1st stage heating will run before 2nd stage
heating is automatically initiated if the guest set
point is not reached and the 2nd stage heating is
not initiated through differential settings
“Temperature Recovery Time” - the maximum
period of time allowed for restoring the
“Recovery Temperature”;
“Recovery Temperature” - the room temperature
that needs to be restored within the
“Temperature Recovery Time”;
“Maximum Setback Temperature” - the highest
room temperature allowed when thermostat is
in the setback mode;
“Minimum Setback Temperature” - the lowest
room temperature allowed when thermostat is
in the setback mode;
“Temperature Setback Delay” - the length of
time for which the room that is in the guest
occupancy mode needs to be unoccupied before
the temperature setback is initiated;
50
“Auto Restore Off” - thermostat will NOT restore
the most recent guest and will remain turned off
settings when new occupancy is detected;
“Setback Set points On” - thermostat will
maintain setback temperatures when room is
unoccupied;
“Setback Set points Off” - thermostat will NOT
maintain setback temperatures when room is
unoccupied;
“Incidental Occupancy” - occupancy shorter than
the “Incidental Occupancy Threshold”;
“Guest Occupancy” - occupancy longer than the
“Incidental Occupancy Threshold”;
“Temperature Setback” - thermostat maintains
setback temperatures and not the guest set
point temperature in order to save energy;
“Night Occupancy Mode” - thermostat status
during which setback mode is disabled if
occupancy longer than “Night Occupancy
Threshold” is detected within the “Nigh
Occupancy” period;
“Automatic Temperature Changeover” thermostat automatically activates heating
or cooling to maintain the desired room
temperature;
“External Thermostat” (Class 2) mode - PTAC unit
setting allowing it to be controlled by a remote
thermostat;
Warranty Information
Hardware
Verdant Environmental Technologies Inc. (“Verdant”) warrants the original end user
(“Customer”) that new Verdant branded products will be free from defects in workmanship and
materials, under normal use, for one (1) year from the original purchase date.
Software
Verdant warrants to Customer that the Verdant thermostat software will perform in
substantial conformance to its program specifications for a period of one (1) year from the date
of the original purchase.
Exclusions
This warranty excludes (1) physical damage to the surface of the product, including cracks,
scratches or marks on the screen or outside casing; (2) damage caused by misuse, neglect,
improper installation, unauthorized attempts to open, repair, or modify the product, or any
other cause beyond the range of intended use; (3) damage caused by accident, fire, power
changes, other hazard, or Acts of God; (4) damage caused by water, liquids, or foreign chemicals
including condensation and humidity; or (5) use of the product with any device if such device
causes the problem.
Exclusive Remedies
Should a covered defect occur during the warranty period and Customer notifies Verdant,
Customer’s sole and exclusive remedy will be, at Verdant’s sole option and expense, to repair
or replace the product. Replacement products or parts may be new or reconditioned or
a comparable version of the defective item. Verdant warrants any replaced product or part
for a period of ninety (90) days from shipment, or through the end of the original warranty,
whichever is longer.
Obtaining Warranty Service
To obtain Warranty Service customer must follow Verdant’s “Warranty Service Procedure” and
request a Return Merchandise Authorization (RMA) number by filling out the RMA Request
Form on Verdant’s website.
Warranty Exclusive
THE FORGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY,
FITNESS FOR A PARTICULAR PURPOSE, CORRESPONDENCE WITH DESCRIPTION, AND NONINFRINGEMENT, ALL OF WHICH ARE EXPRESSLY DISCLAIMED BY VERDANT AND ITS SUPPLIERS.
Disclaimer
NEITHER VERDANT NOR ITS SUPPLIERS SHALL BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL,
INDIRECT, SPECIAL, OR PUNITIVE DAMAGES OF ANY KIND, OR FINANCIAL LOSS ARISING OUT
OF OR IN CONNECTION WITH THE SALE OR USE OF THIS PRODUCT, WHETHER BASED IN
CONTRACT, TORT (INCLUDING NEGLIGENCE) OR ANY OTHER THEORY, EVEN IF VERDANT HAS
BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. VERDANT’S ENTIRE LIABILITY SHALL
BE LIMITED TO REPLACEMENT OR REPAIR OF THE PRODUCT.
51
Technical Specifications
Thermostat
Case Dimensions (Imperial)
Case Dimensions (Metric)
Screen Dimensions (Imperial)
Screen Dimensions (Metric)
5.125 x 4.6875” x 1.25”
130mm x 119mm x 32mm
3.625" x 2.125"
92mm x 54mm
24V AC/DC
Operating Voltage
Fan High (GH)
Control Outputs
Fan Low (GL)
Compressor (Y)
Heat Pump (OB)
Electric Heat (W2)
Occupancy Sensor Beam Width
±47° (94°)
Wireless Frequency
900MHz
Temperature Accuracy
±1°F
FCC ID
IC
XEYV
8410A-V
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS
EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES,
INC. MAY VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
COVERED BY ONE OR MORE OF THE FOLLOWING PATENTS. US PATENTS: 8,369,994; 8,141,791; 7,918,406;
7,232,075; 7,185,825; 7,156,318; 7,152,806; 7,145,110; 7,050,026; 7,028,912; 6,902,117; 6,789,739; 6,786,421; 6,619,555;
6,581,846; 6,578,770; 7,838,803; 7,841,542; D556,061; D518,744; RE40,437; CANADIAN PATENTS: 2,633,113;
2,633,200; OTHER PATENTS PENDING.
Verdant Environmental Technologies, Inc. reserves the right to make changes, without notice, in design or
components. Product appearance may vary. © Verdant Environmental Technologies, Inc. 2015.
Printed in Canada.
V.5
MAY 31, 2016
TECHNICAL SUPPORT: support@verdant.info 1-888-440-0991

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03
Create Date                     : 2017:02:08 18:26:44-05:00
Metadata Date                   : 2017:02:17 10:58:29-05:00
Modify Date                     : 2017:02:17 10:58:29-05:00
Creator Tool                    : Adobe InDesign CC 2015 (Macintosh)
Instance ID                     : uuid:e5901c6c-4b65-4bf4-bf29-543c69c1e85a
Original Document ID            : xmp.did:01801174072068118628C033DD9E9BD2
Document ID                     : xmp.id:9f990ab5-d30d-44f6-8135-f17dcf805eb2
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:740e59fe-58e8-417a-b232-ab846c1406d0
Derived From Document ID        : xmp.did:740e59fe-58e8-417a-b232-ab846c1406d0
Derived From Original Document ID: xmp.did:01801174072068118628C033DD9E9BD2
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CC 2015 (Macintosh)
History Changed                 : /
History When                    : 2017:02:08 18:26:45-05:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 15.0
Trapped                         : False
Page Count                      : 52
Creator                         : Adobe InDesign CC 2015 (Macintosh)
EXIF Metadata provided by EXIF.tools
FCC ID Filing: XEYV

Navigation menu