VX-TWVX Series Wireless Thermostat with an Occupancy SensorINSTALLATION MANUAL V.1   JUNE 26, 2017
3Table of ContentsIntroduction .................................................................................................4Thermostat Installation ...............................................................................6Pairing the Thermostat and the Control Card ............................................. 7Installing the Wireless Control Card ............................................................8Mounting the thermostat to the wall .........................................................9Thermostat Configuration ......................................................................... 10Setting the thermostat clock .......................................................................11Entering the room number ......................................................................... 12Configuring the Equipment Settings - Compressor Type ........................... 13Configuring the Equipment Settings - Electric Heat ..................................14Configuring the Equipment Settings - Reversing Valve .............................15Configuring the Energy Saving Settings  ....................................................16Testing the thermostat ............................................................................... 17Thermostat Maintenance ............................................................................18Replacing Thermostat Batteries .................................................................18Troubleshooting ..........................................................................................19Error Codes ..................................................................................................19Thermostat is not controlling the HVAC unit. .......................................... 20APPENDIX 1 - Energy Saving Presets ...........................................................21APPENDIX 2 - Glossary ................................................................................ 22Warranty Information ................................................................................ 23Technical Specifications ............................................................................. 24
4 5IntroductionVerdant VX Series Energy Management Thermostats for the hospitality industry deliver unprecedented energy savings without compromising guest comfort.An integrated occupancy sensor uses a combination of motion and thermal sensing technologies for accurate occupancy detection. Reliable occupancy detection allows for energy savings when rooms are unoccupied. Energy saving presets eliminate the guesswork and make it easy to adjust the energy saving settings. (Patent Pending)Fully configurable energy saving settings allow for customization of the thermostat energy saving settings to fit any situation. Large buttons with international symbols make it easy to adjust the temperature in ±1° °F or °C and control the fan speed.Comprehensive configuration options ensure full compatibility with virtually any existing or emerging hospitality HVAC system with up to 2 heat and 1 cool stages.Built-in wireless mesh-networking enables optional remote management. NOTICEFOR INSTALLATION OF NETWORKING THERMOSTATS WITH REMOTE MANAGEMENT, REFER TO THE “VX-TW NETWORK INSTALLATION” MANUAL.LOGIN TO THE REMOTE MANAGEMENT WEBSITE TO CONFIRM THE SERVER IS CONNECTED TO THE INTERNET BEFORE INSTALLING THERMOSTATS. DO NOT INSTALL THERMOSTATS IF THE SERVER IS NOT CONNECTED TO THE INTERNET. STOP THE INSTALLATION AND CONTACT VERDANT TECHNICAL SUPPORT. START BY FIRST INSTALLING A THERMOSTAT IN THE ROOM CLOSEST TO THE SERVER. LOG IN TO VERDANT’S REMOTE MANAGEMENT WEBSITE TO CONFIRM THAT THE THERMOSTAT IS ON THE REMOTE MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER.CONTINUE BY INSTALLING ADDITIONAL THERMOSTATS IN ADJACENT ROOMS ONLY AFTER CONFIRMING THAT INSTALLED THERMOSTAT(S) HAVE CONNECTED TO THE WIRELESS NETWORK AND THE REMOTE MANAGEMENT WEBSITE . IF INSTALLED THERMOSTAT(S) ARE NOT CONNECTING TO THE NETWORK AND DO NOT APPEAR ON THE VERDANT’S REMOTE MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER, STOP THE INSTALLATION AND CONTACT VERDANT TECHNICAL SUPPORTTHE ROOMS FURTHEST AWAY FROM THE SERVER SHOULD BE INSTALLED LAST.
6 7Before You Begin  ➤Determine the appropriate installation location for the thermostat.  ➤Set the HVAC unit to “External Thermostat” (Class 2) mode. Consult the HVAC unit documentation to determine how to set the HVAC unit to “External Thermostat” mode.  ➤Consult HVAC manufacturer’s documentation or use a voltmeter to determine if the HVAC unit outputs AC or DC power (24V).  If the HVAC unit outputs AC power, make sure that the jumper on the Wireless Control Card is in the AC position - jumper is connecting “R” and “COM” pins (Default).  If the HVAC unit outputs DC power, make sure that the jumper on the Wireless Control Card is in the DC position - jumper is connecting “COM” and “C” pins.THE THERMOSTAT SHOULD FACE THE BED AREA OF THE ROOM. THE THERMOSTAT AND CONTROL CARD MUST NOT BE INSTALLED NEAR OR ON METAL STRUCTURES OR SURFACES INCLUDING METAL AIR DUCTING THAT MAY BE IN THE WALL.WIRELESS CONTROLS CARDS MUST BE MOUNTED AWAY FROM METAL AND METAL ENCLOSURES.  VTAC INSTALLATIONS SHOULD MOUNT THE CONTROL CARD ABOVE THE UNIT’S METAL ENCLOSURE.  METAL STRUCTURES AND SURFACES SIGNIFICANTLY REDUCE THE RANGE OF THE WIRELESS SIGNAL.Before You Begin Pairing the Thermostat and the Control CardThe Thermostat and Control Card must be paired in order to operate together. Once paired, the thermostat cannot be used with another wireless control card without repeating the pairing procedure. In case of Network Installation with Remote Management, the thermostat and the Control Card must be paired with a Network Programmer specific to the property before the installation. The Thermostat and Control Card must not be powered during the pairing procedure - remove batteries from the thermostat and unplug the control card from the HVAC unit during the pairing procedure.  ➤Plug one programmer connector into the thermostat;  ➤Plug the other programmer connector into the control card;  ➤Push the black button on the programmer. The red light on the programmer should turn on and remain steadily lit;   If the red light on the programmer is blinking or is not steadily lit, unplug the programmer from the thermostat and the control card and repeat the steps above. ➤Unplug the programmer from the thermostat and the control card;
8 9Thermostat InstallationNOTE: If the PTAC unit has only one (1) fan speed, connect both fan control wires – Green and Purple – to the fan terminal (G). Wiring Table - 24V ACWire  Color Terminal Letter Terminal  ConnectionBlack C CommonRed R 24VYellow Y CompressorWhite W HeatOrange O or B Reverse ValveGreen GH Fan HighPurple GL Fan LowWiring Table - 24V DCWire  Color Terminal Letter Terminal  ConnectionBlack R 24VRed C CommonYellow Y CompressorWhite W HeatOrange O or B Reverse ValveGreen GH Fan HighPurple GL Fan LowInstalling the Wireless Control Card ➤Power Off the HVAC unit;  ➤Connect the control card to the thermostat terminals on the HVAC unit - refer to the Wiring Table to determine proper connections.  ➤Mount the control card inside of the HVAC unit.   THE WIRELESS CONTROL CARD ANTENNA MUST NOT BE TOUCHING ANY METAL COMPONENTS OF THE HVAC UNIT.  THE WIRELESS CONTROL CARD ANTENNA MUST FACE THE THERMOSTAT ON THE WALL AND BE ORIENTED SO THAT ANY METAL PARTS OF THE HVAC UNIT DO NOT OBSTRUCT THE WIRELESS COMMUNICATION TO THE THERMOSTAT AND, IN CASE OF A NETWORK INSTALLATION, TO OTHER WIRELESS CONTROL CARDS AND THE SERVER.  THE WIRELESS CONTROL CARD MUST NOT BE PLACED IN THE HVAC UNIT CONDENSATION PAN AND MUST BE MOUNTED SO IT CANNOT FALL INTO THE HVAC UNIT CONDENSATION PAN. ➤Power On the HVAC unit.Mounting the thermostat to the wall  ➤Remove the thermostat cover; ➤Use the supplied wall anchors and mounting screws to secure the thermostat to the wall;  ➤Insert two (2) AA-cell batteries (not supplied) into the thermostat battery compartment; ➤Follow the “Thermostat Configuration” instructions; ➤Replace the thermostat cover and screw in the locking screw;Thermostat Installation
CONFIGURATION BUTTONNOTE: You can access Thermostat Configuration settings at any time by pressing the “Configuration” button. 10 11Thermostat ConfigurationOnce the thermostat is powered, thermostat configuration settings will appear on the thermostat screen.In order to properly operate the HVAC unit: ➤Set the thermostat clock; ➤Enter the room number; ➤Configure the equipment settings; ➤Select Energy Savings Preset;The thermostat configuration screens have a 30-second time-out. If no action is taken within three (30) seconds, the thermostat will exit configuration settings.NOTE: If the thermostat is connected to a network, the equipment and the energy saving settings configured on the thermostat will be ignored and the settings configured on the Remote Management Website will be applied.Thermostat ConfigurationSetting the thermostat clockSet the thermostat clock to current time in 24h (Military Time) format.  ➤Use the “Up” and “Down” buttons to set the hours; ➤Press the “Fan” button to advance to the minutes setting; ➤Use the “Up” an “Down” buttons to set the minutes; ➤Press the “F/C” button to advance to the next menu;Setting the clock correctly is crucial for proper operation of the thermostat.HOURS MINUTES
12 13Thermostat ConfigurationEntering the room numberEnter the room number by changing the digits on the screen. Leading zeros “0” preceding other digits will be ignored, i.e. Room number “123” should be entered as “00123”.  ➤Use the “Up” and “Down” buttons to change the digit; ➤Press the “Fan” button advance to the next digit; ➤Press the “F/C” button to advance to the next menu;Entering the room number correctly is crucial for proper operation of remotely managed thermostats.Thermostat ConfigurationConfiguring the Equipment Settings - Compressor Type ➤Use the “Up” and “Down” buttons to change the compressor type by changing the first digit; 0  No Compressor 1  Heat Pump 2*   Air Conditioner ➤Press the “Fan” button to advance to the next setting; *  Indicates default setting; COMPRESSOR TYPE
14 15Thermostat ConfigurationConfiguring the Equipment Settings - Electric Heat ➤Use the “Up” and “Down” buttons to change the Electric Heat setting by changing the second digit; 0  No Electric Heat 1 *  Electric Heat ➤Press the “Fan” button to advance to the next setting; *  Indicates default setting;ELECTRIC HEATThermostat ConfigurationConfiguring the Equipment Settings - Reversing Valve ➤Use the “Up” and “Down” buttons to change the Reversing Valve setting by changing the third digit;  0  OB contact is energized to cool;  1 *  OB contact is energized to heat;  Refer to the HVAC unit documentation to determine the correct OB VALVE setting.   If the incorrect OB VALVE Setting is selected, the HVAC unit will turn on the heating when air conditioning is requested and turn on the air conditioning when heating is requested; ➤Press the “Fan” button to advance to the next setting; ➤Press the “F/C” button to advance to the next menu; *  Indicates default setting;REVERSING VALVE
16 17Thermostat ConfigurationConfiguring the Energy Saving Settings  ➤Use the “Up” and “Down” buttons to select the Energy Saving preset: E-0*   Energy Savings Off - No Temperature Setback; E-1   Lowest Energy Savings;E-2    Lower Energy Savings;E-3  Standard Energy Savings; E-4    Higher Energy Savings;E-5    Highest Energy Savings;  Refer to the APPENDIX 1 for Energy Saving Preset details. E-C  Indicates “Custom Energy Savings Settings” in case the active thermostat savings settings differ from any Energy Saving preset;   For details, refer to the “Custom Energy Savings Settings” section;  ➤Press the “Power” button to save the Thermostat Configuration and start using the thermostat;  *  Indicates default setting;Testing the thermostatFollowing the thermostat configuration, test if the thermostat is controlling the HVAC unit. ➤Press the “Power” button to turn the thermostat ON; ➤Press the “Down” button to change the temperature set point below the current room temperature to confirm that the thermostat initiates air conditioning. ➤Press the “Up” button to change the temperature set point above the current room temperature to confirm that the thermostat initiates heating. ➤Change the fan speed by touching the “Fan” button to test if the thermostat is controlling the fan speed.Thermostat Configuration
18 19Thermostat MaintenanceReplacing Thermostat BatteriesThe low battery indicator will be displayed on the thermostat screen when it is necessary to replace batteries in the thermostat.Under normal operating conditions, new brand-name alkaline batteries will last for a period of approximately one (1) year. Please replace batteries every twelve (12) months to ensure continuous thermostat operation.To replace thermostat batteries:  ➤Unscrew the fixing screw and remove the thermostat cover; ➤Replace the two (2) AA-cell batteries (not-supplied); ➤Replace the thermostat cover and screw in the fixing screw; ➤Follow the “Thermostat Configuration” instructions to set the thermostat clock; ➤Press the “Power” button to start using the thermostat;NOTE: The thermostat maintains all the “Thermostat Configuration” settings in a non-volatile memory. There is no need to configure the thermostat again after battery replacement.Error CodesERR 1   Thermostat Temperature Sensor Hardware Defect ERR 2   Thermostat Radio Hardware Defect ERR 3   Thermostat Radio Software Defect ERR 4   No link with the Wireless Control Card ERR 5   Thermostat Memory DefectTroubleshooting
20 21The Thermostat is not controlling the HVAC unit.Check if the HVAC unit is set to “External Thermostat” (Class 2) mode.   Verify the status of the red light on the Wireless Control Card; ➤The red light is off  The Wireless Control Card is not powered. Verify that the Wireless Control Card is properly wired to the HVAC unit - specifically make sure that the RED and the BLACK wires are properly connected;  ➤If the red light is blinking with one (1) flash  The Wireless Control Card is powered but it is not communicating with the thermostat, turn the thermostat off and on to re-initiate the linking procedure.  In case of a Network Installation, re-link the thermostat and the Wireless Control Card with the Network Programmer.  ➤The red light is blinking with three (3) flashes.  The Wireless Control Card is communicating with the thermostat. Verify that the Wireless Control Card is properly wired to the HVAC unit and that equipment settings on a thermostat - compressor type, electric heat and reversing valve - are properly configured. Troubleshooting APPENDIX 1 - Energy Saving PresetsSCREEN NUMBERLevel  0Level  1Level  2Level  3Level  4Level  51Fan Control Mode AUTO AUTO AUTO AUTO AUTO AUTO21st Stage Differential Heat 0.5 0.5 0.5 0.5 0.5 0.532nd Stage Differential Heat 11 1 2 2 241st Stage Differential Cool 0.5 0.5 0.5 0.5 0.5 0.55Guest Occupancy Threshold0555556Night Occupancy Threshold 1111117Force 2nd Stage Heating After 30 30 30 30 30 308Night Occupancy Start 18 19 20 21 22 239Night Occupancy End 12 11 10 9 8 710 Recovery Time 015 20 25 30 011 Recovery Temperature Heat 70 69 68 67 66 6512 Setback Delay - Heat  030 25 20 15 1013 Minimum  Setback  Temperature 67 66 65 64 63 6214 Setback Delay - Cool  030 25 20 15 1015 Maximum  Setback Tempera- 72 74 76 78 80 8216 Recovery Temperature Cool 71 72 73 74 75 7617 Minimum Set point 64 64 65 66 67 6818 Maximum Set point 82 82 80 78 76 7419 Temperature Control Mode AUTO AUTO AUTO AUTO AUTO AUTO20 Auto Changeover Set Point  11111121 Auto Restore OFF ON ON ON ON ON21 Setback Set Points OFF ON ON ON ON ON22 Automatic Humidity Control ON ON ON ON ON ON23 Temperature Calibration 000000
22 23“Automatic Fan Control Mode” - fan runs only when there is a demand for heating or cooling;“Manual Fan Control Mode” - guest can select between automatic or continuous fan operation; “Minimum Set point” - minimum temperature that a guest can request;“Maximum Set point” - maximum temperature that a guest can request;“Auto Changeover Set Point Offset” - the difference between the guest-selected set point and the heat and cool changeover temperatures;“1st Stage Differential - Heat” - the temperature that the thermostat has to sense between the automatic changeover temperature for heat and the room temperature before a call for the 1st stage heating is initiated;“2nd Stage Differential - Heat” - difference between 1st stage heating temperature and room temperature before the 2nd stage heating is initiated;“1st Stage Differential - Cool” - the temperature that the thermostat has to sense between the automatic changeover temperature for cool and the room temperature before a call for the 1st stage cooling is initiated;“Forced 2nd Stage Heating” - number of minutes 1st stage heating will run before 2nd stage heating is automatically initiated if the guest set point is not reached and the 2nd stage heating is not initiated through differential settings“Temperature Recovery Time” - the maximum period of time allowed for restoring the “Recovery Temperature”; “Recovery Temperature” -  the room temperature  that needs to be restored within the “Temperature Recovery Time”;“Maximum Setback Temperature” -  the highest room temperature allowed when thermostat is in the setback mode;“Minimum Setback Temperature” - the lowest room temperature allowed when thermostat is in the setback mode;“Temperature Setback Delay” - the length of time for which the room that is in the guest occupancy mode needs to be unoccupied before the temperature setback is initiated;“Incidental Occupancy Threshold” - the minimum period of time (in minutes) for which occupancy needs to be detected in order to enter the “Guest Occupancy” mode;“Night Occupancy Threshold” - the minimum period of time during the “Night Occupancy” period for which occupancy needs to be detected in order to enter the “Night Occupancy” mode;“Night Occupancy Period” - The period of time during the day during which the “Night Occupancy” mode can be activated if occupancy longer than the “Night Occupancy Threshold” is detected;“Auto Restore On” - thermostat will restore the most recent guest settings when new occupancy is detected;“Auto Restore Off” - thermostat will NOT restore the most recent guest and will remain turned off settings when new occupancy is detected;“Setback Set points On” - thermostat will maintain setback temperatures when room is unoccupied; “Setback Set points Off” - thermostat will NOT maintain setback temperatures when room is unoccupied; “Incidental Occupancy” - occupancy shorter than the “Incidental Occupancy Threshold”; “Guest Occupancy” - occupancy longer than the “Incidental Occupancy Threshold”; “Temperature Setback” - thermostat maintains setback temperatures and not the guest set point temperature in order to save energy; “Night Occupancy Mode” - thermostat status during which setback mode is disabled if occupancy longer than “Night Occupancy Threshold” is detected within the “Nigh Occupancy” period;“Automatic Temperature Changeover” - thermostat automatically activates heating or cooling to maintain the desired room temperature;“External Thermostat” (Class 2) mode - PTAC unit setting allowing it to be controlled by a remote thermostat;APPENDIX 2 - Glossary Warranty InformationHardwareVerdant  Environmental  Technologies  Inc.  (“Verdant”)  warrants  the  original  end  user (“Customer”) that new Verdant branded products will be free from defects in workmanship and materials, under normal use, for one (1) year from the original purchase date.SoftwareVerdant  warrants  to  Customer  that  the  Verdant  thermostat  software  will  perform  in substantial conformance to its program specifications for a period of one (1) year from the date of the original purchase.ExclusionsThis  warranty  excludes  (1)  physical  damage  to  the  surface  of  the  product,  including  cracks, scratches  or  marks  on  the  screen  or  outside  casing;  (2)  damage  caused  by  misuse,  neglect, improper installation,  unauthorized  attempts to open, repair,  or modify the product,  or any other  cause  beyond  the  range  of  intended  use;  (3)  damage  caused  by  accident,  fire,  power changes, other hazard, or Acts of God; (4) damage caused by water, liquids, or foreign chemicals including condensation and humidity; or (5) use of the product with any device if such device causes the problem.Exclusive RemediesShould  a  covered  defect  occur  during  the  warranty  period  and  Customer  notifies  Verdant, Customer’s sole and exclusive remedy will be, at Verdant’s sole option and expense, to repair or  replace  the  product.  Replacement  products  or  parts  may  be  new  or  reconditioned  or a  comparable  version  of  the  defective  item.  Verdant  warrants  any  replaced  product  or  part for a period of ninety (90) days from shipment, or through the end of the original warranty, whichever is longer.Obtaining Warranty ServiceTo obtain Warranty Service customer must follow Verdant’s “Warranty Service Procedure” and request a Return Merchandise Authorization (RMA) number by filling out the RMA Request Form on Verdant’s website.Warranty ExclusiveTHE  FORGOING  WARRANTIES  AND  REMEDIES  ARE  EXCLUSIVE  AND  IN  LIEU  OF  ALL  OTHER WARRANTIES,  EXPRESS  OR  IMPLIED,  INCLUDING  WARRANTIES  OF  MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, CORRESPONDENCE  WITH  DESCRIPTION,  AND  NON-INFRINGEMENT, ALL OF WHICH ARE EXPRESSLY DISCLAIMED BY VERDANT AND ITS SUPPLIERS.DisclaimerNEITHER VERDANT NOR ITS SUPPLIERS SHALL BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, INDIRECT, SPECIAL, OR PUNITIVE DAMAGES OF ANY KIND, OR FINANCIAL LOSS ARISING OUT OF  OR  IN  CONNECTION  WITH  THE  SALE  OR  USE  OF  THIS  PRODUCT,  WHETHER  BASED  IN CONTRACT, TORT (INCLUDING NEGLIGENCE) OR ANY OTHER THEORY, EVEN IF VERDANT HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. VERDANT’S ENTIRE LIABILITY SHALL BE LIMITED TO REPLACEMENT OR REPAIR OF THE PRODUCT.
ENGLISHThis  device  complies  with  Industry  Canada  license-exempt  RSS  standard(s).  Operation  is subject  to  the  following  two  conditions:  (1)  this  device  may  not  cause  interference,  and  (2) this  device  must  accept  any  interference,  including  interference  that  may  cause  undesired operation of the device.FRENCHLe  présent  appareil  est  conforme  aux  CNR  d’Industrie  Canada  applicables  aux  appareils radio  exempts  de  licence.  L’exploitation  est  autorisée  aux  deux  conditions  suivantes  :  (1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage  radioélectrique  subi,  même  si  le  brouillage  est  susceptible  d’en  compromettre  le fonctionnement.Technical SpecificationsThermostat Wireless Control CardCase Dimensions (Imperial)  4.015 x 5.5118” x 0.925” 3.875” x 2.125” x 0.75”Case Dimensions (Metric) 102mm x 140mm x 23.5mm 98mm x 54mm x 19mmScreen Dimensions (Imperial)  3.625" x 2.125" N/AScreen Dimensions (Metric)  92mm x 54mm N/AOperating Voltage3V DC - 2 "C" Cell Batteries24V AC/DCControl Outputs Fan High (GH)Fan Low (GL)Compressor (Y)Heat Pump (OB)Electric Heat (W)Occupancy Sensor Beam Width±47° (94°) N/AWireless Frequency 900MHz 900MHzTemperature Accuracy ±1°F N/AFCC ID XEYWX XEYV8ACCCIC 8410A-WX 8410A-V8ACCCCOVERED BY ONE OR MORE OF THE FOLLOWING PATENTS. US PATENTS: 8,369,994; 8,141,791; 7,918,406; 7,232,075; 7,185,825; 7,156,318; 7,152,806; 7,145,110; 7,050,026; 7,028,912; 6,902,117; 6,789,739; 6,786,421; 6,619,555; 6,581,846; 6,578,770; 7,838,803; 7,841,542; D556,061; D518,744; RE40,437; CANADIAN PATENTS: 2,633,113; 2,633,200; OTHER PATENTS PENDING. Verdant Environmental Technologies, Inc. reserves the right to make changes, without notice, in design or components. Product appearance may vary. © Verdant Environmental Technologies, Inc. 2017. Printed in Canada.   V1   June 26, 2017TECHNICAL SUPPORT:  support@verdant.info  1-888-440-0991THIS  DEVICE  COMPLIES  WITH  PART  15  OF  THE  FCC  RULES.  OPERATION  IS  SUBJECT TO  THE  FOLLOWING  TWO  CONDITIONS:  (1)  THIS  DEVICE  MAY  NOT  CAUSE  HARMFUL INTERFERENCE,  AND  (2)  THIS  DEVICE  MUST  ACCEPT  ANY  INTERFERENCE  RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION. PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY  VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.