Viessmann Vitola 200 Technical Manual 5167 403 V1.6

2015-08-26

: Viessmann Viessmann-Vitola-200-Technical-Manual-802291 viessmann-vitola-200-technical-manual-802291 viessmann pdf

Open the PDF directly: View PDF PDF.
Page Count: 16

VITOLA 200
Hot water heating boiler without low limit
83 to 300 MBH / 24 to 88 kW
5167 403 v1.6 04/2008
Vitola 200 with Vitoflame Burner and
Vitocell-H 300 domestic hot water tank
Vitola 200 with Vitoflame Burner, boiler stand
and Vitocell-V 300 domestic hot water tank
Oil-fired
Technical Data Manual
Model Nos. and pricing: see Price List
Vitola 200
VB2 Series
Oil-/Gas-Fired Boiler
for hydronic heating systems
with modulating boiler water temperatures
without low limit
with biferral heating surfaces of cast iron/steel
Heating input: 83 to 300 MBH
24 to 88 kW
Product Information
2
Vitola 200
High quality at an affordable price:
The double-wall sandwiched heat exchanger
surface of the Vitola 200 is a milestone in the
history of heating technology. The Vitola 200
combines comfort with energy savings.
The benefits at a glance:
HBiferral heat exchanger of cast iron and steel
for high operational reliability and a long
service life.
HReduced emissions with the Viessmann
Chassis or Vitoflame Burner.
HSaves energy and preserves the
environment via low boiler water
temperatures; cold start ability; A.F.U.E.
of up to 87.4% (oil-fired version).
HOptimal temperature modulation due to
wide water passageways and a large
water content.
HStraight-forward installation and start-up –
Burners supplied by Viessmann are tested
with a combustion analyzer at operating
temperature and matched to the boiler
input in the factory.
HShort installation times due to the
Viessmann Fastfix Installation System.
Save up to 50% of the installation time
when installing boiler panelling and
control. Simple assembly is achieved with
components which merely snap together,
making special tools unnecessary.
The biferral sandwiched heat exchanger of
cast iron and steel offers high operational
reliability and a long service life
5167 403 v1.6
Product Information
Cut-Away Section
3
Biferral sandwiched heat exchanger surface Viessmann Vitoflame 100 Burner
of cast iron and steel offers high
operational reliability and a long
service life
Removable stainless steel Vitotronic 200 –
combustion chamber indoor/outdoor
digital boiler and heating
system control
3” / 75 mm boiler shell
insulation
5167 403 v1.6
Technical Data
4
Technical data
Boiler Model Model No. VB2-18 VB2-22 VB2-33 VB2-40 VB2-50 VB2-63
CSA gas rating*1 input
output
MBH
kW
MBH
kW
90
26
75
22
116
34
97
28
146
42
122
35
185
54
154
45
238
69
198
57
300
88
249
73
CSA oil rating input
output
MBH
kW
MBH
kW
83
24
72
21
107
31
92
27
135
39
116
34
170
50
146
43
219
64
189
55
300
88
258
76
Net I=B=R rating*2 for gas
for oil
MBH
kW
MBH
kW
65
19
63
18
84
25
80
23
106
31
101
30
134
39
127
37
172
50
164
48
217
64
224
66
A.F.U.E.*3 for NG
for LP
for oil
%
%
%
84.5
86.0
87.1
84.0
85.8
87.2
84.0
85.8
87.2
84.0
85.8
87.3
83.9
85.7
87.4
83.9
85.7
87.1
Dimensions
Length
Width
Height
Overall dimensions *4
Total length
Total width
Total height (operation)
- Height 1 *5 (control unit in
position for operation)
- Height 2 *5 (control unit in
position for servicing)
Height of boiler stand
Height of Vitocell-H under boiler
- 42 to 53 USG / 160 to 200 ltr
-92USG/350ltr
- 120 USG / 450 ltr
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
23¼
589
21¼
537
27¾
706
43¾
1112
25¼
639
32¾
830
37
940
45¾
1160
250
26
658
25¾
655
22¼
565
28½
726
46¼
1178
26¼
667
33½
850
37¾
960
46½
1180
250
26
658
32¼
817
23½
599
29¼
743
52¾
1340
27½
701
34
865
38¼
975
47
1195
250
26
658
31
790
32¼
817
26½
674
32¼
819
53¼
1350
30½
776
37
940
41¼
1050
50
1270
250
26
658
31
790
37¼
947
37¾
956
27¾
702
33½
853
58½
1489
30½
776
38½
975
42¾
1085
51½
1305
250
31
790
37¼
947
42
1070
27¾
702
33½
853
63
1603
30½
776
38½
975
42¾
1085
51½
1305
250
31
790
37¼
947
Weight boiler shell
Total weight (boiler with insulation,
burner and boiler control)
lbs
kg
lbs
kg
287
130
381
173
335
152
434
197
430
195
542
246
573
260
697
316
739
335
866
393
809
367
941
427
Boiler water content USG
ltr
18.5
70
23.2
88
31.2
118
37.0
140
52.6
199
59
223
Max. operating pressure psig 30 30 30 30 30 30
Boiler water connections
Supply and return
Safety supply (Safety Header)
Safety return, drain valve
inches
inches
inches
1
1
1
1
1
1
1
1
1
1
*1Propane burners have same input/output as natural gas burners.
*2Net I=B=R rating based on piping and pick-up allowance of 1.15.
*3Annual Fuel Utilization Efficiency with optional stack damper.
*4Overall dimensions with Viessmann Vitoflame 100 Burner installed.
*5Seepage6.
5167 403 v1.6
Technical Data
5
Technical data
Boiler Model Model No. VB2-18 VB2-22 VB2-33 VB2-40 VB2-50 VB2-63
Flue gas*6, temperature (gross)*7 at
H104°F / 40°C boiler water temp.*9
H167°F / 75°C boiler water temp.
Flue gas mass flow
°F
°C
°F
°C
lbs/h
kg/h
293
145
329
165
68
31
293
145
329
165
84
38
293
145
329
165
123
56
293
145
329
165
150
68
293
145
329
165
187
85
293
145
329
165
236
107
Vent pipe
Boiler vent outer inches 5 5 6 6 7 7
Flue gas volume, boiler USG
ltr
10.3
39
14.0
53
20.6
78
29.1
110
41.5
157
45.7
173
Required flue draft *8 *9 “w.c. -0.02 -0.02 -0.02 -0.02 -0.02 -0.02
*6Combustion results are based on 11.0% to 13.0% CO2with fuel oil #2, 9.5% to 10.2% with natural gas,
or 10.0% to 11.5% CO2with propane, and a hot water heating system supply temperature of 167°F / 75°C, return 140°F / 60°C.
*7Measured flue gas temperature with combustion air temperature of 68°F / 20°C.
*8Ensure compatibility during burner selection.
*9Ensure compatibility with chimney system. The chimney vent system must be suitable for the application (low flue gas temperature with
possible condensation), see page 10.
"For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
5167 403 v1.6
Technical Data
Height 1
Height
Height 2
Overall height
Width
Length
Overall length
Overall width
VB2-18 to -33=161/8” / 410 mm
VB2-40 to -63=175/8” / 448 mm
5¾” / 145 mm
9¾”
250 mm
SS
6” / 154 mm
4” / 100 mm
2¾” /
70 mm
BTS
BWS
BWS
BWR
BWR
FGC
SR/BD
6
Dimensions
Boiler Model VB2 -18 -22 -33 -40 -50 -63
a
b
c
d
e
f
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
30
761
13¼
338
144
195
141
19¼
488
30¾
781
13¼
338
138
210
5
125
19¾
503
31½
797
13¼
338
144
225
110
20
511
34½
874
13½
342
144
10
254
84
21¼
542
35¾
908
14½
370
144
10½
268
85
24½
620
35¾
908
14½
370
143
10½
268
85
24½
620
With DHW tank
under the boiler
USG
ltr
42 and
53
160
and
200
42 and
53
160
and
200
53
200
92
350
53
200
92
350
120
450 *1
92
350
120
450 *1
92
350
120
450 *1
g
h
k
l
m
n
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
61¼
1555
58¾
1490
26
658
31½
799
39¼
996
45
1146
62
1575
59½
1510
26
658
30¾
783
39¼
996
45¾
1161
62½
1590
60
1525
26
658
30¼
768
39¼
996
46
1169
67¾
1720
65¼
1655
31
790
35½
900
44½
1128
51¼
1301
65¼
1665
63
1600
26
658
29¼
742
39¼
1000
47¼
1200
70¾
1795
68
1730
31
790
34½
874
44½
1132
52½
1332
76¾
1952
74¼
1887
37¼
947
40½
1031
50¾
1289
58½
1489
72
1830
69½
1765
31
1790
34½
1875
45¾
1160
55½
1410
78¼
1987
74¼
1932
37¼
947
40½
1031
51¾
1317
61¾
1567
72
1830
69½
1765
31
1790
34½
1875
45¾
1160
55½
1410
78¼
1987
74¼
1932
37¼
947
40½
1031
51¾
1317
61¾
1567
*1Support Bars are necessary for 120 USG / 450 ltr tanks; dimensions “g” through “n”
include 2¼” / 57 mm to account for the height of the Support Bars.
5167 403 v1.6
Technical Data
5¾” /
145 mm
SS
BWS
BWS
BWR
BWR
FGC
SR/BD
7
Legend
BD Boiler Drain
BTS Boiler Temperature Sensor
BWR Boiler Water Return
BWS Boiler Water Supply
FGC Flue Gas Collar
SR Safety Return
SS Safety Supply
Boiler Stand
Vitocell-H
Mounting the Vitola 200 on a Vitocell-H
The Vitola 200 can be mounted on a
Vitocell-H as shown to reduce the
footprint of heating equipment in the
mechanical room. Do not attempt to
install combinations not listed in the
Price List.
Boiler/Tank Compatibility
Support bars may be required when
mounting a Vitola 200 boiler on a
Viessmann Vitocell-H Series tank.
Refer to the following chart to determine
whether support bars are required for your
application.
Order numbers are listed for boiler/tank
combinations requiring support bars.
Certain boilers (listed with a “z”inthe
chart) are directly compatible with the
Vitocell-H tank and thus do not require
additional hardware.
Combinations listed with “n.a.” are
incompatible. Do not attempt to install these
combinations.
For more information see Viessmann Price
List.
Boiler/Tank Compatibility
Vitocell-H 100
DHW storage tank
Vitocell-H 300
DHW storage tank
Vitola 200 CHA-160 CHA-200 EHA-160 EHA-200 EHA-350 EHA-450
VB2-18/-22
VB2-33
VB2-40
VB2-50/-63
z
z
n.a.
n.a.
z
z
z
n.a.
z
z
n.a.
n.a.
z
z
z
n.a.
n.a.
z
z
z
n.a.
n.a.
Z001 060
Z001 060
Order No. = Support bars are required.
z=Support bars are not required. Boiler/tank are directly compatible.
n.a. = Boiler/tank are incompatible. Neither mounting with support bars, nor direct-mounting possible.
5167 403 v1.6
Technical Data
8
Recommended Minimum Clearances for Service
Combustion chamber insert
Boiler
Vitocell-H domestic
hot water storage tank *2
Sensor well for storage tank
Boiler Model VB2 -18 -22 -33 -40 -50 -63
Dim a*1:Necessary clearance in front of the boiler
for maintenance and service
inches
mm
24½
620
26¾
680
33½
850
33½
850
36½
920
43
1090
Dim b: Necessary clearance beside the boiler
Ensure sufficient clearance if installing Divicon
inches
mm
24
600
24
600
24
600
24
600
24
600
24
600
Dim c: Necessary clearance behind a Vitocell-H
installed below the boiler
inches
mm
16¾
425
16¾
425
17¾
450
17¾
450
17¾
450
17¾
450
Dim d: Ensure adequate clearance for Divicon or other accessories; minimum
clearances
(no Vitocell-H installed below the boiler)
inches
mm
24
600
24
600
24
600
24
600
24
600
24
600
Top: inches
mm
24
600
24
600
24
600
24
600
24
600
24
600
*1 This clearance is required for service work. Viessmann strongly recommends maintaining 48” / 1200 mm front clearance on all models.
*2 The Vitola 200 can be mounted on a Vitocell-H as shown to reduce the footprint of heating equipment in the mechanical room.
Do not attempt to install combinations not listed in the Price List.
Minimum Clearances to Combustibles
For typical installations, Viessmann recommends installing the boiler with clearances as
published on page 10 under Recommended Minimum Clearances for Service.
Standard installation
(top view)
Boiler Model VB2 -18 -22 -33 -40 -50 -63
Rear inches
mm
6
150
6
150
6
150
6
150
6
150
6
150
Sides inches
mm
0
0
0
0
0
0
0
0
0
0
0
0
Flue (oil) inches
mm
9
230
9
230
9
230
9
230
9
230
9
230
(gas) inches
mm
6
150
6
150
6
150
6
150
6
150
6
150
5167 403 v1.6
min. 6”
150 mm
min. 0” / 0 mm
service
clearance
48”
1220 mm*
Technical Data
Standard Equipment / Boiler Control Alternatives
9
Waterside Flow (primary circuit)
The Vitola 200 is designed for closed loop, forced circulation
hot water heating systems only.
Legend
VB2-18 to -33
VB2-40 to -63
Standard Equipment
Note:
Boiler controls and burners are purchased
separately. Please see Price List for details.
Boiler shell with combustion chamber door
1 carton with insulating jacket and
1 cleaning brush
1 set of boiler ID hardware (coding card
and technical literature)
1 installation fittings carton with safety
header (c/w 30 psig pressure relief valve,
air vent and pressure gage), drain valve,
and installation fittings
1 carton with boiler control
1 carton with:
Viessmann Vitoflame Burner
(c/w burner hood and barometric damper)
or
Riello Burner (c/w barometric damper)
Boiler Control Alternatives
Vitotronic 100, KK10
standard boiler control for high temperature
heating systems
Vitotronic 100, KW10
standard boiler control for high temperature
heating systems
with indoor/outdoor system control
Vitotronic 200, KW2
for multiple temperature heating systems
with or without a mixing valve
with indoor/outdoor digital boiler and heating
system control
Vitotronic 300, KW3
for multiple temperature heating systems
with up to two mixing valves
with indoor/outdoor digital boiler and heating
system control
5167 403 v1.6
Water flow
Pressure drop
m3/h
GPM
5
22
20 50
“w.c.
mbar
25
3.2 8
410
820
12 30
16 40
0.4 1
0.8 2
1.2 3
1.6 4
0.5
2.2
1
4.4
2
9
3
13
4
18
6
26
7
31
System Design Considerations
10
System Design Considerations
Chimney
For proper operation of the Vitola boiler, all
products of combustion must be safely
vented to the outdoors, while ensuring that
flue gases do not cool prematurely.
It is critical that the chimney system be
properly designed to handle the flue gas
temperatures which the Vitola boiler
produces.
Flue gases which cool too quickly produce
condensation which leads to damages if the
chimney diameter is too large and the
chimney system is not well insulated.
If a calculated chimney diameter lies
between two values, the larger diameter
should be selected.
Intermediate section
The intermediate (vertical and horizontal)
section of venting between the boiler vent
pipe collar and the chimney must be of
identical diameter as the vent connection of
the boiler. Use the shortest possible path
between the boiler and the chimney. A
maximum of two elbows may be installed in
the intermediate section. Avoid the use of
two level 90° elbows.
The intermediate section must be sealed
pressure tight at the boiler vent pipe collar
and at the chimney connection. Ensure any
test port for combustion values is sealed as
well.
The chimney connection length between the
boiler vent pipe collar and the chimney must
be installed with insulation. Viessmann
recommends consulting a reputable chimney
installer for advice in project-specific
circumstances.
Barometric damper must be used!
For Canadian oil installations only, a blocked
vent safety shut-off switch must be
installed.
Warranty
Our warranty does not cover damages
resulting from the following:
installation or service by unqualified and
not licensed personnel
corrosion caused by flue gas condensation
due to low boiler water and/or return
water temperatures
operation with contaminated fill and
supplementary feed water
For detailed warranty information, please
read warranty sheet supplied with product.
Combustion air supply
The boiler must not be located in areas or
rooms where chemicals containing chlorine,
bromine, fluorine, or other corrosive
chemicals are stored. Examples include
refrigerants, bleach, paint, paint thinner, hair
spray, cleaning solvents, water softener
salt, etc. The combustion air must not be
contaminated with the above mentioned, or
other aggressive or corrosive chemicals.
Boiler should never be installed in areas
where excessive dust, high humidity, or risk
of frost exist. Ensure adequate ventilation
and supply of fresh combustion air.
Consult Viessmann with uncertainties in
regard to a suitable boiler installation
location.
This boiler/burner unit needs clean fresh air
for safe operation and must be installed so
that there are provisions for adequate
combustion and ventilation air. For oil-fired
boilers, use the “Installation Code for Oil
Burning Equipment CAN/CSA-B139”
(Canada), or NFPA 31 (USA) and/or
provisions of local codes. For gas or
propane, use the “Natural Gas Installation
Code CAN/CSA-B149.1 or B149.2”
(Canada), or “National Fuel Gas Code ANSI
Z223.1” (USA), and/or provisions of local
codes.
The sizing methods outlined in the above
codes should be used when installing a
round duct to supply combustion air from
the outside. Observe local jurisdictional
requirements.
System layout
The boiler water temperature limit is factory
set to 167°F / 75°C.
The boiler water temperature limit can be
increased by altering the adjustable high
limit to increase the supply water
temperature.
To minimize piping losses of the system,
however, we recommend that the radiation
and domestic hot water production in the
system be designed for a 158°F / 70°C
boiler supply water temperature (new
systems).
Water quality
Treatment for boiler feed water should be
considered in areas of known problems,
such as where a high mineral content and
hardness exist. In areas where freezing
might occur, an antifreeze may be added to
the system water to protect the system.
Please adhere to the specifications given by
the antifreeze manufacturer. Do not use
automotive silicate based antifreeze. Please
observe that an antifreeze/water mixture
may require a backflow preventer within the
automatic water feed and influence
components such as diaphragm expansion
tanks, radiation, etc. A 40% antifreeze
content will provide freeze-up protection to
-10°F / -23°C. Do not use antifreeze other
than specifically made for hot water heating
systems. System also may contain
components which might be negatively
affected by antifreeze. Check total system
frequently when filled with antifreeze.
Advise system operator/ultimate owner that
system is filled with a glycol mix.
The heating contractor must provide an
MSDS (Material Safety Data Sheet) for the
antifreeze used to the system
operator/ultimate owner.
Oxygen diffusion barrier
underfloor tubing
The boiler warranty does not cover leaks
resulting from corrosion caused by the use
of underfloor plastic tubing without an
oxygen diffusion barrier. Such systems must
have the non-oxygen diffusion barrier tubing
separated from the boiler with a heat
exchanger. Viessmann recommends the use
of underfloor plastic tubing with an oxygen
diffusion barrier.
Low water cut-off
A low water cut-off may be required by local
codes. If boiler is installed above the
radiation level, a low water cut-off device of
approved type must be installed in all
instances. An approved type low water
cut-off device must be provided by the
heating contractor. Do not install an
isolation valve between the boiler and the
low water cut-off.
5167 403 v1.6
Installation Examples
11
Installation Examples
Important!
These examples depict possible piping layouts for Viessmann product equipped with Viessmann System Technology. For boiler and tank
combinations, please install only the feasible combinations listed in the Price List.
These are simplified conceptual drawings only! Piping and necessary componentry must be field verified.
Proper installation and functionality in the field is the responsibility of the heating contractor.
Without mixing valve
e.g. with Vitotronic 100, KK10
Heating circuit
Spring-loaded flow check valve
Circulation pump
Safety header
with automatic air vent,
pressure relief valve, and
pressure gage
Expansion tank
Domestic hot water storage tank
(indirect-fired)
DHW Pump Module
The installation of the check valve to restrict
gravity circulation in the heating supply pipe
prevents uncontrolled heat flow to the heating
system by gravity during priority switching of
domestic hot water heating or during summer
operation.
5167 403 v1.6
Installation Examples
12
With one low-temperature circuit with 3-way mixing valve, one high-temperature circuit,
and with domestic hot water production
e.g. with Vitotronic 200, KW2 combined with one Mixing Valve Actuator Accessory Kit
Heating circuit
Spring-loaded flow check valve
Circulation pump
Safety header
with automatic air vent,
pressure relief valve, and
pressure gage
Expansion tank
Domestic hot water storage tank
(indirect-fired)
3-Way mixing valve
4-Way mixing valve
With two low-temperature circuits with mixing valves,
one high-temperature circuit, and with domestic hot water production
e.g. with Vitotronic 300, KW3 combined with two Mixing Valve Actuator Accessory Kits
5167 403 v1.6
Installation Examples
13
Underfloor heating system with one low-temperature circuit with 3-way mixing valve,
and system separation
e.g. with Vitotronic 200, KW2 combined with one Mixing Valve Actuator Accessory Kit
Heating circuit
Spring-loaded flow check valve
Circulation pump for heating circuit
Safety header
with automatic air vent,
pressure relief valve, and
pressure gage
Expansion tank
Heat exchanger
Circulation pump for heat exchanger
Pressure relief valve
5167 403 v1.6
14
5167 403 v1.6
15
5167 403 v1.6
Viessmann Manufacturing Company Inc.
750 McMurray Road
Waterloo, Ontario N2V 2G5 Canada
Tel. (519) 885-6300 Fax (519) 885-0887
www.viessmann.ca info@viessmann.ca
Viessmann Manufacturing Company (U.S.) Inc.
45 Access Road
Warwick, Rhode Island 02886 USA
Tel. (401) 732-0667 Fax (401) 732-0590
www.viessmann-us.com info@viessmann-us.com
16
5167 403 v1.6 Technical information subject to change without notice. Printed on environmentally friendly
(recycled and recyclable) paper.

Navigation menu