Von Duprin Chexit Wiring Instructions 2016 New Chexitwiringinstructions2016
User Manual: Von Duprin Chexit Wiring Instructions - 2016 Literature
Open the PDF directly: View PDF .
Page Count: 16
Download | |
Open PDF In Browser | View PDF |
*911030-00* 911030-00 Chexit (CX) Wiring and Configuration Installation Instructions General Information The Von Duprin Chexit device is designed for controlled egress applications. It meets both life safety and security needs, as well as the requirements of NFPA101 for “Special Locking Arrangement” and IBC “Special Egress-Control Devices”. All control inputs, auxiliary locking, local alarm and remote signaling outputs are self-contained in the Chexit assembly. Numerous field configurable options allow the device to be customized for the specific code or application requirements. The standard Chexit device sounds an alarm and keeps the door secured for 15 seconds following an exit attempt with immediate release upon fire. Parts Included PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS Security Screw Pack (Install as required) Wire Guard Blocking Device Cable Controlled Egress Device (CX98/99 Rim shown) Module Field Wiring Cable Door Sign Trim Device Cable* *Included when ordering with an E7500, E996L, E360L-BE or RX996L-M. Table of Contents Basic Features........................................................................... 2 Retrofit Wiring............................................................................. 7 Installation Components............................................................. 3 Installation.................................................................................. 8 Electrical Specifications.............................................................. 3 Basic Functional Test................................................................ 11 Typical Wiring Diagrams............................................................. 4 Module Setup........................................................................... 11 Single Door.............................................................................. 4 Onboard Switch Settings Table................................................ 12 Double Door............................................................................ 5 Advanced Function Test........................................................... 13 Double-Egress Door................................................................ 6 Onboard Indicators................................................................... 14 Electrical Trim.......................................................................... 7 Troubleshooting........................................................................ 15 WARNING • • • Do not exceed rated specifications. The Chexit device must be installed in accordance with these instructions by a qualified electrician. Wiring and applications must be in accordance with all local codes and regulations. Customer Service 1-877-671-7011 www.allegion.com/us © Allegion 2016 Printed in U.S.A. 911030-00 Rev. 3/16-c 1 Basic Features Door Position Switch Remote Alarm Key Switch Internal Alarm Status Indicator Inhibit Device (Card Reader) Inputs & Outputs Fire Alarm Input This input releases the door immediately upon a fire alarm, allowing immediate egress. The Internal Alarm can be silenced during a fire input via an onboard switch setting. Inhibit Input (Access Control) This optional input is provided to allow authorized egress or entry when the device is Armed using an external card reader, Key Switch, etc. It also allows remote reset of the Chexit in an alarmed condition. The ability to reset alarms with the inhibit input can be disabled via an onboard switch setting. Door Position Switch Input An optional Door Position Switch (DPS) can provide door position status to Chexit for additional security, ensuring that the door is closed, and can cause alarm when the door is left or forced open. Gang Bus The Gang bus allows a Chexit device to signal other Chexit devices when it enters the Release Delay, allowing multiple doors to release at the same time in an emergency. Up to 8 devices may be connected to the Gang bus. Alarm Relay Contacts The Alarm Relay contacts are provided as a means to control a Remote Alarm, such as a horn or lamp, or signal an external monitor. The contacts can be configured with a jumper as Normally Open or Normally Closed, and become active upon entering an alarmed condition. Secure Relay Contacts The Secure Relay contacts are provided as a means to signal an external monitor. The contacts can be configured as Normally Open or Normally Closed with a jumper, and become active when the DPS indicates the door is closed and the Push Pad is locked. Delays Release Delay When the Push Pad is pushed and the Nuisance Delay expires, the Chexit enters the Release Delay with alarm. During the Release Delay, the Internal Alarm sounds, the Alarm Relay activates, and the Chexit keeps the Push Pad locked for 15 seconds (less any time already elapsed during the Nuisance Delay). Once started, the Release Delay sequence will not stop and the Chexit will unlock. 2 Nuisance Delay When a Chexit is located in a public area, it can be desirable to limit false releases when the Push Pad is accidentally pushed. The Nuisance Delay is the brief time a Push Pad can be accidentally pushed before the Release Delay sequence starts. If the Nuisance Time is set to 0 seconds, the Chexit will enter Release Delay as soon as the Push Pad is pushed (when armed). Setting the Nuisance Time to 1, 2, or 3 seconds allows the Push Pad to be pressed for 1 to 3 seconds before the Chexit goes into Release Delay. If the Nuisance Audio and Nuisance Delay are both on, the Internal Alarm will pulse during the Nuisance Delay. The Alarm Relay does not activate during the Nuisance Delay. If the Push Pad is released before the Nuisance Delay expires, the Chexit will remain armed. Rearm Delay The Rearm Delay is the amount of time after the Key Switch or Inhibit Input is deactivated to when the device rearms. It is designed to give someone time to pass through the door before rearming occurs. The Rearm Time can be changed via the onboard switch settings from 0 to 28 seconds in 2 second increments. If the Rearm Time is set to 30 seconds and a DPS is used, if the door is opened and the Rearm Time expires, there will be no alarm. The Chexit will rearm after the door is closed. If the door never opens, the Chexit will rearm after 30 seconds. If not using a DPS, the Chexit will always rearm in 30 seconds. DPS Delay If the DPS detects that the door closed during the Rearm Delay, the Chexit ends the Rearm Delay and allows 2 seconds for the latch to clear the strike before rearming. Interface Key Switch The Key Switch provides the means to Arm or Disarm/Reset the Chexit. Turning the Key Switch clockwise initiates the Rearm Delay, and turning the Key Switch counter-clockwise Disarms/ Resets the Chexit. The Key Switch allows the key to be removed in either the Arm or the Disarm/Reset position. Status Indicator The red Status Indicator displays the status of the Chexit. The Status Indicator flashes slow if the Chexit is armed, flashes fast in an alarmed mode, is off when inhibited and on solid during Rearm Delay. Internal Alarm The Internal Alarm sounds the status of the Chexit. The Internal Alarm sounds continuously during and after a fire alarm or a Release Delay, pulses fast during the Nuisance Delay or a tamper and pulses slow during Disarmed Powerup mode. Settings Armed Powerup When set to OFF, a power disruption and power return will put the Chexit in a disarmed, unlocked alarm mode. Trim Fail Safe / Fail Secure (FS/FSE) The trim input power can be set to FS (Fail Safe; locked when energized, unlocked when deenergized or during power failure) or FSE (Fail Secure; unlocked when energized, locked when deenergized or during power failure). The trim must be bought or modified to physically function as FS or FSE. This onboard setting only selects the trim input power. 2 Installation Components Picture Component Table 1.1 Installation Components Function 1Z\v" Mortise Cylinder (with straight cam and Z\v” spacer) Optional/Required Provides means to use the Key Switch. Required Provides power to Chexit. Required Power Transfer (EPT10-CON shown) Provides means to transfer electrical power and signals through frame to door. Required Fire Alarm (NC contacts) Provides fire alarm status to Chexit so that it can unblock Push Pad in case of fire alarm. Power Supply PS902, PS904, PS906, or PS914 EPT10-CON Recommended Door loop or electric hinge can also be used. Required Multiple Fire Alarms can be used in series. Optional Inhibit (Access Control) Device Provides additional means (Card Reader, Key Switch, of signaling an authorized Multiple Inhibit Devices can be used in series. etc.) (NC contacts) access to Chexit. If not used, connect green wire to red wire. Provides door position Optional Door Position Switch status to Chexit for (NC contacts) If not used, connect orange wire to red wire. additional security. Provides an additional Optional alarm that may be louder Remote Alarm If not used, insulate blue and brown wires or located in a remote separately. location. 3 Electric Mortise Lock (E7500) (FS or FSE) Provides means for Chexit to control entry through the door. Optional (Included with CXE9975L) Electric Trim (E996L shown, or E360L-BE) (FS or FSE) Provides means for Chexit to control entry through the door. Optional Electrical Specifications Cable Wire Signal Description Signal Type Voltage Color Rating Red 24 VDC 24 VDC 24 VDC Power Input Black Ground GND Ground Yellow Fire Alarm FA NC Input Green Inhibit INH 24 VDC DPS Orange Door Position Switch Gray Gang GNG Active Low Bus Field COM Wiring Blue Alarm Relay ALM Relay Brown NO or NC Contact 24 VDC White COM Output Secure Relay SEC Violet NO or NC Tan Not Used Not Used Pink Yellow 24 VDC 24 VDC 24 VDC Power Output Trim Blue Locking Ground LGND Ground Device Green Request to Enter REN NO Input 24 VDC Black Not Used Not Used Current Rating 390 mA Holding* 1.25 A Inrush* Wire Gauge Minimum 18 AWG 14 AWG 10 mA 22 AWG 1A 22 AWG Wire Length One-Way Measurement Maximum From Power Transfer To 200 feet Power Supply 500 feet Fire Alarm Inhibit Device 1000 feet Door Position Switch Ganged Chexit Device Remote Alarm or External Monitor 100 feet External Monitor Not Used 1A 10 mA Trim Device Cable (Included when ordered with an E7500, E996L, RX996L-M or E360L) *Includes current from Chexit device only (does not include current from optional components such as Inhibit Device, Remote Alarm, or Trim Device) 3 4 • • • • • • Typical Wiring Diagrams Single Door The Chexit is used as a controlled egress device with access control. The Inhibit Device (card reader) provides additional means of signaling an authorized access to Chexit. The Remote Alarm is used as an additional alarm in a remote location. Using a door position switch gives added security in case the door is not closed or is forced open. The Push Pad releases immediately when the Fire Alarm is active. If card readers are required on both sides of the door, the normally closed contacts of the readers should be wired in series. To fire alarm contact 2 x 18 AWG To secure status 2 x 18 AWG Gang group (optional)* 1 x 18 AWG Remote Alarm 2 x 18 AWG 2 x 14 902, 904, 906, or 914 Power supply Junction box 2 x 14 AWG 8 x 18 AWG AC input (See power supply instructions for AC input requirements) 2 x 18 AWG (plus power if required) 2 x 18 AWG DPS EPT10-CON *Gang option: -All Chexits in the gang group must have a common DC GND connecting them. -Up to 8 devices can be ganged together. Chexit Card Reader Figure 1. Riser Diagram, Single Door Door Side EPT10-CON Frame Side AC input 902, 904, 906, or 914 Power Supply GND Black (GND) 24 VDC Red (24VDC) Orange (DPS) Green (lNH) **DPS Contacts (NC) **Card Reader Contacts (NC) Fire Alarm Contacts (NC) Yellow (FA) Gray (GNG) Blue (ALM C) Brown (ALM NO/NC) White (SEC C) Violet (SEC NO/NC) Gang Bus (Insulate wire if not used) External Horn } Secure Relay Contacts Tan (Not Used) Pink (Not Used) **If not used, short across wires Figure 2. Point-To-Point Diagram, Single Door 4 4 • • • • • • Typical Wiring Diagrams, continued Double Door Application - Rim/Vertical Both doors open in the same direction and each is equipped with a Chexit. The two Chexits are connected (ganged) by the gray (GNG) wires. (If not used, insulate these wires separately.) When one Chexit is set into Release Delay (activated by Push Pad), the other also goes into Release Delay and both unlock after the Release Delay. A fire alarm unlocks both doors immediately. An external inhibit device (card reader contacts) also unlocks both doors at the same time. After an inhibit signal from the card reader, the door that was used rearms both doors 2 seconds after closing. To fire alarm contact To secure status 2 x 18 AWG 2 x 18 AWG 4 x 14 AWG 904, 906, or 914 Power supply Gang group (optional)* 1 x 18 AWG Remote Alarm 2 x 18 AWG 2 x 18 AWG (plus power if required) 2 x 14 AWG, 8 x 18 AWG Junction box 2 x 14 AWG 8 x 18 AWG 2 x 18 AWG DPS DPS EPT10-CON EPT10-CON Chexit *Gang option: -All Chexits in the gang group must have a common DC GND connecting them. -Up to 8 devices can be ganged together. AC input (See power supply instructions for AC input requirements) Chexit Card Reader Figure 3. Riser Diagram, Double Door Door Side EPT10-CON Frame Side EPT10-CON Door Side AC input 904, 906, or 914 Power Supply Black (GND) GND Black (GND) 24VDC Red (24VDC) **DPS Contacts (NC) Fire Alarm Contacts (NC) **DPS Contacts (NC) **Card Reader Contacts (NC) Orange (DPS) Red (24VDC) Orange (DPS) Green (INH) Green (INH) Yellow (FA) Yellow (FA) Gray (GNG) Gray (GNG) Blue (ALM C) Brown (ALM NC/NO) White (SEC C) Violet (SEC NC/NO) Blue (ALM C) } Alarm Relay Contacts } Brown (ALM NC/NO) } Secure Relay Contacts } Violet (SEC NC/NO) White (SEC C) Tan (Not Used) Not Used Not Used Tan (Not Used) Pink (Not Used) Not Used Not Used Pink (Not Used) **If not used, short across wires Figure 4. Point-To-Point Diagram, Double Door 5 4 • • • • • • Typical Wiring Diagrams, continued Vertical - Double-Egress Doors Pair of doors open in opposite directions and each is equipped with a Chexit. The two Chexits are connected (ganged) by the gray (GNG) wires. (If not used, insulate these wires separately.) When one Chexit is set into Release Delay (activated by Push Pad), the other also goes into Release Delay and both unlock after the Release Delay. A fire alarm unlocks both doors at the same time immediately. An external inhibit device (card reader contacts) also unlocks each door individually. After an external inhibit, the door that was used rearms 2 seconds after closing. To fire alarm contact To secure status 2 x 18 AWG 2 x 18 AWG 4 x 14 AWG 904, 906, or 914 Power supply Gang group (optional)* 1 x 18 AWG 2 x 18 AWG (plus power if required) 2 x 18 AWG Remote Alarm 2 x 18 AWG (plus power if required) 2 x 14 AWG, 8 x 18 AWG Junction box 2 x 14 AWG 8 x 18 AWG 2 x 18 AWG DPS DPS EPT10-CON *Gang option: - All Chexits in the gang group must have a common DC GND connecting them. - Up to 8 devices can be ganged together. - See section 1, Basic Feature, Gang Bus to determine if this feature is needed for the double egress application. Card Reader (outside) AC input (See power supply instructions for AC input requirements) EPT10-CON Chexit (outside) Card Reader (inside) Chexit (inside) Figure 5. Riser Diagram, Double-Egress Doors Door Side EPT10-CON Frame Side EPT10-CON Door Side AC input 904, 906, or 914 Power Supply 24VDC Red (24VDC) Green (INH) Red (24VDC) **DPS Fire Contacts Alarm (NC) Contacts (NC) **DPS Contacts (NC) Orange (DPS) Black (GND) GND Black (GND) **Card Reader Contacts (NC) **Card Reader Contacts (NC) Orange (DPS) Green (INH) Yellow (FA) Yellow (FA) Gray (GNG) Gray (GNG) Blue (ALM C) Brown (ALM NC/NO) White (SEC C) Violet (SEC NC/NO) } Alarm Relay Contacts } Secure Relay Contacts Blue (ALM C) } Brown (ALM NC/NO) White (SEC C) } Violet (SEC NC/NO) Tan (Not Used) Not Used Not Used Tan (Not Used) Pink (Not Used) Not Used Not Used Pink (Not Used) **If not used, short across wires Figure 6. Point-To-Point Diagram, Double-Egress Doors 6 5 Typical Wiring Diagram for Electric Trim Function This section describes the option of adding an electrical trim function to the Chexit installation. 5a Controlled entry application (E996L Trim – FSE shown) RX trim is not locked and allows entry at all times. The trim inhibits the CX using the REN function during entry. This application is only used on a CX9975 mortise device. RESET RESET STATUS Insulate unused wires Module TRIM TRIM DEVICE REN ACTUATOR REN YEL RED BLU VIO WHT GRY REX REX BLK YEL(24VDC) GRN(REN) BLU(LGND) BLK(GND) BLOCKING Solenoid Module BLK BLOCKING DEVICE BLK BP ACTUATOR E7500 STATUS Controlled entry application (E7500 Mortise Lock) RESET RESET 5b Insulate unused wires TRIM TRIM DEVICE REN ACTUATOR REN Access control to the CX (not shown) inhibits the CX and unlocks the outside FSE (Fail Secure) trim to allow entry. For access control wiring, see previous wiring diagrams. YEL(24VDC) GRN(REN) BLU(LGND) BLK(GND) REX REX Module YEL RED BLU BLOCKING BLOCKING DEVICE BLK BP ACTUATOR STATUS Insulate unused wires RX996L-M TRIM TRIM DEVICE REN ACTUATOR REN Solenoid REX REX YEL(24VDC) GRN(REN) BLU(LGND) BLK(GND) Free entry application (RX996L-M + 98/99 Mortise device) RESET RESET E996L Trim BLOCKING BLOCKING DEVICE BLK BP ACTUATOR NOTE: Set onboard switch setting #12 to OFF position (FSE) 5c NOTE: Set onboard switch setting #12 to OFF(FSE) or ON(FS) position to match the mortise lock function. Access control to the CX (not shown) inhibits the CX and unlocks the E7500 mortise lock to allow entry. The E7500 can be either FS (Fail Safe) or FSE (Fail Secure). For access control wiring, see previous wiring diagrams. 6 Retrofit Wiring On the discontinued Chexit device, the Door Position Switch, Card reader and Fire Alarm contacts were tied to the white SC wire. On the new Chexit device, these contacts are wired to the red 24VDC wire (see wiring diagrams below). LL Caution: Do not connect the gray and violet wires of the discontinued Chexit device to the gray and violet wires of the new Chexit device. The discontinued and new Chexit devices can not be ganged together. DISCONTINUED CHEXIT DEVICE NEW CHEXIT DEVICE EPT10 Black Red (24VDC) EPT10 Black (GND) Red (24VDC) Orange (DPS) Green (EI) Orange (DPS) Card Reader Contacts (NC) Yellow (FA) Green (INH) Gray (CM+) Blue (ALM C) See Notes Brown (ALM NO) White (SC) Violet (CM-) Fire Alarm Contacts (NC) DPS Contacts (NC) DPS Contacts (NC) Card Reader Contacts (NC) Fire Alarm Contacts (NC) Yellow (FA) Gray (GNG) Blue (ALM C) Brown (ALM NC/NO) White (SEC C) See Notes Violet (SEC NC/NO) Tan (Not Used) Pink (Not Used) 7 7 7a Installation Disconnect Power 7e Slide module into exit device case as shown. 7f Install end cap bracket. 7g Connect blocking device cable to motor and to 3-pin connector on module. Connect 2-pin cable from under motor to Request-to-Exit connector labeled “REX” on module. To avoid risk of shock, disconnect AC power from power supply before proceeding with this installation. If using battery backup option, unplug all four wires from battery terminals. 7b If installed, remove end cap, cover plate and end cap bracket. End cap bracket Cover plate 7c Drill 5/8” diameter wire access hole in surface of door. 7/16” 5/8” diameter 7d BLOCKING ACTUATOR End cap Route field wiring cable through hole and connect wires to EPT10 / 10-CON power transfer (see EPT instructions as needed). Cut the connectors if EPT10-CON is not used. EPT10-CON shown If removal is needed, press release tab on connector. BLOCKING ACTUATOR 3-Pin Connector 8 2-Pin Connector 7 Installation, continued 7g (cont) 7j LL If using electric trim (E996L/E360L-BE), install electric trim per instructions included with trim. Route trim wires through the CX device as shown. Use 11/4” mortise cylinder with compression ring K510-406 with straight cam and orient cam as shown. Schlage cylinder 20-001-114 recommended. 1¹⁄₁₆" (27 mm) Maximum X Standard cam configuration (Shown with key removed) Make connections here per the wiring diagram. Compression/Blocking ring shown installed on cylinder Trim Device Cable (included with trim) Schlage 20-001-114 shown CAUTION Trim Device Cable Dimension X as shown above must be no more than 11/16” or damage to product may occur. Keep cables routed to the side of device. LL If using electric mortise lock (E7500 or SS7500 monitor mortise lock), install lock per instructions included with lock. Route lock wires through the door as shown. 7k Remove and discard cylinder plug from key switch assembly. Keep key switch cable routed as shown. Remove Cylinder Plug Routed from E7500/SS7500 Mortise Lock Ensure Key Switch Cable is routed here Trim Device Cable Keep cables routed to the side of device. Make connections here per the wiring diagram. 7h 7i 7l Install mortise cylinder. Verify cylinder cam operates key switch properly. Refer to Section 11, Advanced Function Test table – Electric Trim for trim lock/unlock function. CAUTION Orient cylinder as shown or unit will not operate Push toward motor until module snaps into place. X CAUTION MAXIMUM X DIMENSION TO BE 1¹⁄₁₆" (27 mm) TRIM DEVICE REN Label may be removed now INSTALL CYLINDER POSITIONED AS SHOWN AND CHECK CAM ACTION (CX DEVICE ONLY) STATUS REX If board removal is needed, insert flathead screwdriver between board and motor ONLY in areas shown and pry until board disengages from bracket. INSTALL WIRE GUARD BEFORE INSTALLING KEY CYLINDER RESET BLOCKING DEVICE DO NOT pry in this area. BLK Pry here 97 29 00 -00 Pry here Snap into place 9 7 Installation, continued 7m Connect field wiring cable and key switch cable to module as shown. 7p Place excess wire beneath wire guard. CAUTION Verify cylinder cam moves freely and does not contact module or any wiring. 7q Complete field wiring per wiring diagrams in section 4. 7r Install end cap. LL See pages 11 through 14 before installing end cap 7n Slide wire guard into case end and above key switch cable until making contact with module. If trim is used, cover its cable with wire guard also. www.allegion.com/us Install this bracket after cables are plugged into the CX Module 7o WIRE COLOR CHART RED 24V BLUE AL BLACK GND BROWN AL GREEN INH WHITE SE ORANGE DPS VIOLET SEC YELLOW FA TAN N/A GREY GNG PINK N/A Push excess cable into door. If required use security screws on end cap and centercase. 7s Remove backing from sign and put sign on door above Chexit device (sign is in cardboard tube). PUSH UN TIL AL DOOR CA ARM SOUNDS N BE O IN 15 SEC PENED ONDS While keeping tension on the key switch cable and pushing wires flat against door, slide cover plate fully into place. LL Locate sign per local code. Tension 10 8 Basic Functional Test This test is to be performed with Chexit switches in default settings and with door closed. Follow the instructions below and verify that the Chexit performs as described. Note: If at any time the Internal Alarm sounds and you wish to silence it, turn the Key Switch counter-clockwise. Test Powerup 1. Turn the Key Switch clockwise. Then turn the power supply ON which causes the Chexit to enter Armed Mode (Status Indicator is flashing slow). 2. Turn the Key Switch counter-clockwise to put the Chexit into Disarmed/Reset Mode (Status Indicator is OFF). 3. Turn the Key Switch clockwise which causes the Chexit to enter Rearm Delay Mode (Status Indicator is ON for 10 seconds - this time is adjustable). 4. After Rearm Delay Mode expires, the Chexit will enter Armed Mode (Status Indicator is flashing slow). Test Delayed Egress 5. Confirm that the Chexit is in Armed Mode per step 4. 6. Push the Push Pad and verify that it is locked (it will not push down). Chexit will immediately begin sounding the Internal Alarm and enter Release Delay Mode for 15 seconds (Status Indicator is flashing fast and Internal Alarm is ON). 7. After the Release Delay Mode expires, the Chexit will enter Released Mode (Status Indicator is flashing fast and the Internal Alarm is ON). The Push Pad will be unlocked (you can now push it down and open the door). Mode Push pad Electric Trim Status Indicator Internal Alarm Secure Relay Alarm Relay Armed Locked Locked Slow Flash (2) Off On Off Rearm Delay Unlocked Unlocked On Off Off Off Release Delay Locked Locked Fast Flash (2) On On On Released Unlocked Off (1) Fast Flash (2) On Off On Disarmed/Reset Unlocked Locked Off Off Off Off (1) Trim will be Locked or Unlocked depending on if the Trim is Fail Secure or Fail Safe (and if the Trim Fail Safe onboard switch setting is set to OFF or ON) (2) SLOW FLASH = 1 per second, FAST FLASH = 4 per second 9 Module Setup 9a Remove Cover Plate for access to Module as needed. Set the Relay Jumpers and Onboard Switch Settings for desired device functionality. Position the Alarm Relay Jumper and Secure Relay Jumper to NO or NC. Position each Onboard Switch Setting to ON or OFF. - Refer to Onboard Switch Settings Table on next page for detailed description of each setting. Default factory settings shown Secure Relay (SEC) Jumper 1 2 3 4 5 6 7 8 9 10 11 12 ON NC ON OFF Jumpers Alarm Relay (ALM) Jumper NC OFF RE-ARM TIME: 2 ARMED POWERUP AUDIO HIGH RE-ARM TIME: 4 INH RESET NUISANCE AUDIO RE-ARM TIME: 8 NUISANCE TIME:1 FA AUDIO RE-ARM TIME: 16 NUISANCE TIME:2 TRIM FAILSAFE NO NO PWR PWR FA GNG FIELD WIRING KEY SWITCH DPS DPS KS KEY ALM FA EA ALARM RELAY NO INH NO EI 8 SS RELAY 4 NC SECURE RELAY EA RELAY 12 NC OFF SS ON REN TIME: 2 1 RE-ARMOFF 2 RE-ARM TIME: 4 1 3 RE-ARM 2 TIME: 8 4 RE-ARM 3 TIME: 16 5 6 7 8 TRIM DEVICE TRIM ACTUATOR REN ARMED POWERUP 9 10 INH RESET 5 NUISANCE TIME: 1 11 6 NUISANCE TIME: 2 12 7 STATUS REX REX SEC OFF AUDIO HIGH NUISANCE AUDIO 9 FA 10AUDIO TRIM 11 FAILSAFE ON RESET RESET BLOCKING DEVICE BLOCKING BP ACTUATOR BLK SETTINGS GNG Jumpers shown in Normally Open position ON • • SETTINGS 9b 11 10 Onboard Switch Settings Table Switch Numbers Switch Position Onboard Settings Specifications 1 2 3 4 OFF OFF OFF OFF 0 ON OFF OFF OFF 2 OFF ON OFF OFF 4 ON ON OFF OFF 6 OFF OFF ON OFF 8 ON* OFF* ON* OFF* 10 OFF ON ON OFF 12 1-4 ON ON ON OFF 14 Rearm Time OFF OFF OFF ON 16 ON OFF OFF ON 18 OFF ON OFF ON 20 ON ON OFF ON 22 OFF OFF ON ON 24 ON OFF ON ON 26 OFF ON ON ON 28 ON ON ON ON Chexit powers up into Armed Powerup Mode (locked). ON* 6 INH (Access Control) Reset 7-8 Nuisance Time OFF All alarms reset by KEY only (meaning user must be at the door to manually reset). ON* All alarms reset by KEY OR INH (INH allows any access control user to reset the alarm at the door or remotely). 7 8 OFF* OFF* 0 ON OFF 1 OFF ON 2 ON 9 Audio High 10 Nuisance Audio 11 FA Audio 12 Trim Fail Safe ON 3 Sets Internal Alarm to Low. ON* Sets Internal Alarm to High. OFF Internal Alarm OFF during Nuisance Delay (if Nuisance Delay is enabled). ON* Internal Alarm ON during Nuisance Delay (If Nuisance Delay is enabled). OFF Internal Alarm OFF during Fire Alarm. ON* Internal Alarm ON during Fire Alarm. OFF* Trim is selected to be Fail Secure (FSE). Trim is selected to be Fail Safe (FS). *Default settings Consult AHJ or local building codes for onboard switch settings. 12 Nuisance Time (seconds) OFF ON The delay time initiated after the INH or KEY goes inactive (back to normal position) before the Chexit rearms, allowing a person to exit or enter without an alarm through an unlocked door. 30 (Infinite) Chexit powers up into Disarmed Powerup Mode (unlocked with alarm sounding). OFF 5 Armed Powerup Rearm Time (seconds) Description If the Chexit is Armed and there is a power outage, then upon power restoration, the Chexit will either power up into Armed Mode or Disarmed Powerup Mode with alarm sounding. Selects what action is allowed to reset an alarm condition. The delay time the Push Pad can be pushed without starting the release sequence. It is used to prevent accidental bumps from triggering the alarm. Selects between High and Low audio levels during alarm. Selects whether Internal Alarm is ON or OFF during the Nuisance Delay (if Nuisance Delay is enabled). Selects whether the Internal Alarm ON or OFF during a Fire Alarm. Matches FSE or FS trim to Chexit trim device output. 11 Advanced Function Test Chart below shows the various Modes of the Chexit. Follow the steps below the chart to check each Mode. Mode Push Pad Electric Trim Status Indicator Internal Alarm Secure Relay Alarm Relay Armed Locked Locked Slow Flash (3) Off On Off Disarmed Powerup Unlocked Locked Slow Flash (3) Slow Pulse (4) Off Off Inhibited Unlocked Unlocked Off Off Off Off Rearm Delay Unlocked Unlocked On Off Off Off DPS Delay Unlocked Locked On Off Off Off Nuisance Delay Locked Locked Slow Flash (3) Fast Pulse (2) (4) On Off Release Delay Locked Locked Fast Flash (3) On On On Released Unlocked Off (1) Fast Flash (3) On Off On Tamper Unlocked Locked Fast Flash (3) Fast Pulse (4) Off On Disarmed/Reset Unlocked Locked Off Off Off Off (1) Electric Trim will be Locked or Unlocked based on whether the Trim Fail Safe onboard setting is set to OFF or ON (2) Audio may be turned OFF through Nuisance Audio onboard switch setting (3) SLOW FLASH = 1 per second, FAST FLASH = 4 per second (4) SLOW PULSE = 1 per second, FAST PULSE = 4 per second Test Powerup 1. Ensure that the Key Switch is turned clockwise. Turn the Power Supply ON. -If the Armed Powerup onboard switch setting is ON (default) the Chexit will enter Armed Mode. -Note: If the Armed Powerup onboard switch setting is OFF the Chexit will enter Disarmed Powerup Mode. 2. Turn the Key Switch counter-clockwise to put the Chexit into Disarmed/Reset Mode. 3. Turn the Key Switch clockwise to arm the Chexit. -If the Rearm Time onboard switch setting is ON (default = 10 seconds), the Chexit will enter Rearm Delay Mode. After Rearm Delay Mode expires, the Chexit will enter Armed Mode. -If the Rearm Time onboard switch setting is OFF, the Chexit will enter Armed Mode without a delay. Test Delayed Egress 4. Confirm that the Chexit is in Armed Mode. 5. Push and hold the Push Pad. -If the Nuisance Time onboard switch setting is OFF, the Chexit will immediately enter Release Delay Mode. -The Chexit will release in 15 seconds. -If the Nuisance Time onboard switch setting is ON, the Chexit will enter Nuisance Delay Mode. -If the Nuisance Audio onboard switch setting is ON, the Internal Alarm will pulse fast. -If the Nuisance Audio onboard switch setting is OFF, the Internal Alarm will not sound. -If the Push Pad is released before the Nuisance Delay expires, the Chexit will go back to Armed Mode. -If the Push Pad is held until the Nuisance Time expires, the Chexit will enter Release Delay Mode. After the Release Time expires, the Chexit will enter Released Mode. The Chexit will release in 15 seconds, less the Nuisance Time already elapsed. 6. Repeat Step 2 and Step 3 to make the Chexit return to Armed Mode. Test Access Control 7. Confirm that the Chexit is in Armed Mode. 8. Activate the Inhibit (INH) Input to make the Chexit enter Inhibited Mode. 9. Release the Inhibit (INH) Input. -If the Rearm Time onboard switch setting is ON (default = 10 seconds), the Chexit will enter Rearm Delay Mode. -If the door is opened and closed before the Rearm Time expires, the Chexit will enter DPS Delay Mode. The Chexit will enter Armed Mode in 2 seconds. -If the door is left open and the Rearm Time expires, the Chexit will enter Released Mode. -If the Rearm Time onboard switch setting is OFF. -If the door is closed, the Chexit will go back to Armed Mode. -If the door is left open the Chexit will enter Tamper Mode. Test Fire Alarm 10. Confirm that the Chexit is in Armed Mode. 11. Activate the FA input to make the Chexit enter Released Mode. -If the FA Audio onboard switch setting is ON, the Internal Alarm will sound. -If the FA Audio onboard switch setting is OFF, the Internal Alarm will not sound. 12. Repeat Step 2 and Step 3 to make the Chexit return to Armed Mode. 13 Onboard Indicators KEY GNG FA DPS INH SEC ALM BLK REX REN STATUS MOTOR STATUS 14 GNG FIELD WIRING KEY KEY SWITCH Inhibit (Red) Secure Relay (Green) PWR ALM DPS OFF SETTINGS REN PWR Indication ON TRIM DEVICE Signal FA STATUS REX Request-to-Exit (Red) Request-to-Enter (Red) ALARM RELAY RESET BLOCKING DEVICE Motor Status LED (Green-Armed) (Red-Tamper) SECURE RELAY OFF ON BLK SETTINGS SEC Status (Red) INH Alarm Relay Gang (Red) Fire Alarm (Red) (Red) Power (Green) 5 ARMED POWERUP 9 AUDIO HIGH R 10 NUISANCE AUDIO 6 A 11 FA AUDIO 7 A 12 TRIM FAILSAFE 8 Blocked (Green) 1 REARM TIME: 2 2 REARM TIME: 4 3 REARM TIME: 8 4 REARM TIME:16 12 Key Switch (Red) Door Position Switch (Red) Description OFF Power is OFF ON Power is ON OFF Key Switch turned clockwise (Arm) ON Key Switch turned counter-clockwise (Disarm/Reset) OFF No Gang signal (Inactive) ON Gang signal (Active) OFF Fire Alarm contacts closed (Inactive) ON Fire Alarm contacts open (Active) OFF Door Position Switch closed (Door Closed) ON Door Position Switch open (Door Open) OFF Inhibit contacts closed (Inactive) ON Inhibit contacts open (Active) OFF Chexit not secure (Relay contact state depends on Secure Relay NO/NC jumper setting) ON Chexit secure OFF Chexit not in alarm (Relay contact state depends on Alarm Relay NO/NC jumper setting) ON Chexit in alarm condition OFF Push Pad is unlocked ON Push Pad is locked OFF Push Pad is not pushed (Inactive) ON Push Pad is pushed (Active) OFF Request-to-Enter contacts open (Inactive) ON Request-to-Enter contacts closed (Active) OFF Chexit is in Disarmed/Reset Mode or in Inhibited Mode SLOW FLASH Chexit is in Armed Mode or in Disarmed Powerup Mode FAST FLASH Chexit is in Release Delay Mode or Released Mode ON Chexit is in Rearm Delay Mode or DPS Delay Mode OFF Push pad is not blocked/unlocked GREEN Push pad is blocked/locked SLOW FLASH RED Overvoltage 13 Troubleshooting Normal Chexit operation: -After turning the Key Switch clockwise to Arm, the Chexit will wait the selected Rearm Time (red Status Indicator is ON). -At the end of this delay, the Chexit will lock the Push Pad (red Status Indicator is flashing slow) indicating the Chexit is Armed. -To trigger delayed egress, push the Push Pad in. The Chexit will sound an Internal Alarm (red Status Indicator is flashing fast). -At the end of the Release Delay, the Push Pad will unlock allowing exit. The Internal Alarm will continue until the Chexit is reset with the Key Switch or Inhibit Input (if INH Reset onboard switch setting is ON). Most wiring issues can be diagnosed by observing the Module’s onboard LED indicators (see section 12, Onboard Indicators). An Armed Chexit’s LED’s should appear as: Status LED - flashing slow PWR, SEC and BLK - ON (PWR LED is on when power is applied to the Module and is independent of any switch positions) All other LED’s - OFF Status Indicator flashing fast or Internal Alarm pulsing fast is 4 times per second. Status Indicator flashing slow or Internal Alarm pulsing slow is 1 time per second. Status Indicator ON or Internal Alarm ON means on continuously. With 24VDC applied to the Chexit, turn the Key Switch clockwise to Arm and note the possible symptoms below. Symptoms Module PWR (Power) LED is OFF. Push Pad is NOT locked. Internal Alarm is NOT sounding. Module Status Indicator is ON. Module Status Indicator flashes once. Module Status Indicator is flashing fast. Module FA (Fire Alarm) LED is ON. Push Pad is NOT locked. Internal Alarm is ON. Module ALM (Alarm) LED is ON. Possible Cause Power supply is not supplying any voltage. Solution Check power supply output voltage at the supply and at the Chexit. Power supply voltage is too low. Check power supply output voltage is 24VDC. Field wiring connection is broken. Verify the power wiring has continuity from power supply to the Module. Power supply is reverse polarity. Verify proper color code is used to supply power to Chexit (see section 4, point-topoint diagrams). Rearm Delay is active. Verify proper rearm delay setting (see section 9 and 10, switches 1-4). If set to 30 see section 1, "Rearm Delay". INH (access control) wiring/ connection is open. Verify the INH wiring continuity. Verify the access control device is using INH (access control) is active normally closed contacts (see section 4, (contacts open). point-to-point diagrams). FA wiring/connection is open. Verify the FA wiring has continuity from FA contacts to Module. FA is active (contacts open). Verify the FA contacts are closed when there is no fire alarm. Module Status Indicator is flashing fast. Module GNG (Gang) LED is ON. GNG wire is shorted to the power supply ground. Find and remove short. Insulate any unused GNG wire. Module ALM (Alarm) LED is ON. 15 13 Troubleshooting, continued Symptoms Possible Cause Push Pad is not returning to the full extended position. When Arming, Release Delay starts immediately. Module Status Indicator is flashing fast. Push Pad is first Locked and then releases after 15 seconds. Module REX (Req. to EXIT) REX cable is disconnected LED is ON. REX wiring/connector is Module ALM (Alarm) LED defective. is ON. Internal Alarm is ON. When Arming, Push Pad remains unlocked. Internal Alarm is pulsing fast When Arming, Push Pad remains unlocked. Internal alarm is pulsing fast after 2 seconds. Module Status Indicator is flashing fast. Module DPS (Door Pos. Switch) LED is ON. Module ALM (Alarm) LED is ON. Module Status Indicator is flashing fast after 2 seconds. Module BLK (Blocking) LED is OFF. Motor Status LED is OFF. Module ALM (Alarm) LED is ON. Solution Pull Push Pad out fully and verify this corrected the problem. Check for dirt and rubbing around the Push Pad area. Check for full latch bolt extension (see section 12, REX LED indication). Plug in REX cable (see section 7, step 7g) Check for broken wiring from the REX connector to the REX switch under the Push Pad. REX switch is defective. Verify the REX switch is closed when the Push Pad is fully extended. If still open, replace switch. DPS switch contact is open. Close the door, if open. Verify the DPS contacts are closed when the door is closed. DPS wiring/connection is open. With door closed, verify the DPS wiring has continuity from DPS contacts to Module. CX motor cable is disconnected. Plug in CX motor cable (see section 7, step 7g). CX motor wiring/connection is open. Check for broken wiring in the motor cable. CX motor assembly is defective. Call customer service. On a rim or vertical rod device, the latch bolt can’t extend. Door is not closed enough for proper latching. Make necessary mechanical adjustments to latch properly. If using a vertical rod device and arming with door open, the latch bolts are held retracted. On any device, the Push Pad Verify the Push Pad is extending fully (see is held in. REX) above After a power outage and power is restored, Push Module Status Indicator is Pad remains unlocked (Key flashing slow. Switch is in Armed position Module ALM (Alarm) LED clockwise). is ON. Internal Alarm is pulsing slow. The Chexit is not self arming after a power outage. Chexit onboard switch #5 (Armed Power Up) is set to OFF. Trim is locked when it should be unlocked. Trim switch setting is incorrect. OR Trim is unlocked when it should be locked. 16 Incorrect trim type. Verify if FS (Fail Safe) or FSE (Fail Secure) is being used. Some jurisdictions require the Chexit to be disarmed and alarming to be manually reset only after a power loss. For those jurisdictions, the Module switch #5 is set to OFF (see section 9 and 10, switch 5). Select the correct trim switch setting to match the trim being used (see section 9 and 10, switch 12). Install the correct trim type.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Create Date : 2016:03:08 09:53:48-05:00 Creator : Adobe InDesign CS6 (Windows) Modify Date : 2016:10:18 12:48:27-04:00 XMP Toolkit : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03 Metadata Date : 2016:10:18 12:48:27-04:00 Creator Tool : Adobe InDesign CS6 (Windows) Instance ID : uuid:7c0075f4-7f15-2343-93e8-047c0ddbf443 Original Document ID : xmp.did:516915126ECCE1118A0D8AD340C27D6B Document ID : xmp.id:6F3122883DE5E5118C50A5E285BE6DAF Rendition Class : proof:pdf Derived From Instance ID : xmp.iid:6E3122883DE5E5118C50A5E285BE6DAF Derived From Document ID : xmp.did:41A67EE53ED0E5119B81C766F6AE28E1 Derived From Original Document ID: xmp.did:516915126ECCE1118A0D8AD340C27D6B Derived From Rendition Class : default History Action : converted History Parameters : from application/x-indesign to application/pdf History Software Agent : Adobe InDesign CS6 (Windows) History Changed : / History When : 2016:03:08 09:53:48-05:00 Format : application/pdf Producer : Adobe PDF Library 10.0.1 Trapped : False Page Count : 16EXIF Metadata provided by EXIF.tools