Von Duprin LBR Auxiliary Fire Pin And 499F Strike Installation Instructions 107570

User Manual: Von Duprin LBR Auxiliary Fire Pin and 499F Strike Installation Instructions Installation Instructions

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadVon Duprin LBR Auxiliary Fire Pin And 499F Strike Installation Instructions 107570
Open PDF In BrowserView PDF


LBR

911010-00
Fire Pin/Strike Kit

Installation Instructions

LBR
(Less Bottom Rod)

!

WARNING

For surface vertical rod installations, incorrect strike
installations can result in latching failure in a fire
condition. This can result in severe injury or death.
Installer: Discard installed strikes and replace with
correctly installed 499F strikes supplied with this kit.
Failure to install the 499F strikes on Surface Vertical
Rod LBR-F devices will void the UL Fire Label.

Important:
Read this first!
1. LBR Fire Pin/Strike Kit is for use only with Von Duprin 98/9927-F,
98/9947-F, 33/3547-F, 33/3527A-F, 33/3547A-F, and 2227-F devices.
2. Any door preparation must be performed by an installer that is
certified by the door manufacturer.
3. Installation of device with 499F strike for surface vertical rod
devices, and 338 strike for concealed vertical rod devices is
required to maintain fire listing. For 499F installation, see page
3 of these instructions.

Parts List
Description

Quantity

Auxiliary Fire Pin Assembly

1

#6 x 3/4” Sheet Metal/Wood Flat Head Screw

4

Strike Hole Plug

1

499F Strike Assembly

2

Return Spring

2

Centercase Hole Plug

2

!

NOTE

One (1) auxiliary fire pin assembly is supplied with two LBR devices. It
does not matter which door leaf the auxiliary fire pin is installed on.
However, the pin must be installed to maintain the fire listing. The
purpose of the auxiliary fire pin assembly is to keep the doors in
alignment during a fire. In a fire, the bolt extends from the auxiliary fire
pin into the strike hole in the opposite door leaf. The black cap visible
on the face of the auxiliary fire pin and the strike hole plug must melt in
order for the bolt to extend. If an Edge Guard is used, make sure it is
modified to allow clearance for the Fire Pin and Plastic Cap to be
mounted to the door edge after the Edge Guard is installed. See Edge
Guard Preparation on page 4 for more information.

INSTALLATION
1

Prepare auxiliary fire pin mounting hole, screw holes, and strike hole in door.
1 3/4"
depth of hole

CLdoor

3 3/8"
depth of hole

CLdoor

1/4"
#36 drill
4 places

1/4"
5/8"

7/8" dia.

CL

CL
1" dia.

5/8"
6" from
bottom
of door

Strike Hole Plug
Door Leaf

2

CLdoor

CLdoor

Auxiliary Fire Pin
Door Leaf

Install strike hole plug and auxiliary fire pin.

Install strike hole
plug in strike hole
Mount auxiliary fire pin
with four #6 x 3/4" Type AB
flat head screws
2

3

Install 499F strike.
NOTE
The 499F strike installation is only for 98/9927-F-LBR,
33/3527A-F-LBR, and 2227-F-LBR devices. For concealed
vertical rod LBR devices, skip this procedure.
3.1. Replace 299F strikes with 499F strikes as shown below.
3.2. Adjust 499F strike to position shown in Figure 3-1.
3.3. Install remaining three screws (see Figure 3-2).
3.4. Prepare door for strike hook (see Figure 3-3) and install strike hook. Figure 3-4 shows relative
positions of strike, strike hook, and top latch.

Strike roller

1/16" ref.
#25 drill and
#10-24 tap
(3 places)

Figure 3-1

Figure 3-2

Hole Schedule
Metal door:

#7 drill and #1/4"-20 tap

Wood door:

13/32" dia. drill thru

Remove
299F strike
Strike hook

Face
of stop

Bottom
of stop

1/16"

Face
of door

CL strike
Strike

Center strike hook
on strike, locate to
1/16" dimension,
and mark holes

Figure 3-3

Strike
hook

Figure 3-4
3

EDGE GUARD PREPARATION
If using Edge Guards, clearance holes must be cut into Edge Guards before they are installed on door as
shown in Figure 4-1.
Outer Dimensions
of plug and strike

Edge Guard
clearance holes

1.188"
1.765"

1.000"

Figure 4-1
Edge guard near exit device center case can extend no further than .0625" from edge of door, as shown in
Figure 4-2, or interference with device center case could occur. If Edge Guard is wider than specified, it may
need to be trimmed in that area to clear center case.

Edge of door

Maximum .0625"
from edge of door to
edge of device

Figure 4-2
4

RETURN SPRING REPLACEMENT
!

WARNING

Installation of the wrong spring can result in latching
failure in a fire condition. This can result in severe
injury or death.
Installer: Make sure correct return spring is installed
per instructions below.

1

Determine which spring the device baseplate contains comparing to the following
two springs:

Spring A

!

NOTE

If device contains
Spring "B" skip to
Step 3.

Spring B

9927-F

2

Remove return spring "A" and replace with spring supplied in kit.

3

Repeat steps 1 and 2 for device on other door leaf.

4

Reinstall devices.
5

VERTICAL ROD ADJUSTMENT PROCEDURE
33/3527A-F-LBR, 98/9927-F-LBR, & 2227-F-LBR

1

Screw top vertical rod to top latch case.

2

Push rod upward slowly until it has fully extended top latch bolt to achieve
deadlocking as shown.

3

Adjust top vertical rod until rod snaps into centercase.

3/16"

4

6

Hold
down

Push to check
deadlocking

Check device operation by opening and closing door with outside lever or
thumbpiece.

VERTICAL ROD ADJUSTMENT PROCEDURE
33/3547A-F-LBR & 98/9947-F-LBR
1

Loosen top adjustment lock screw.

2

Rotate adjusting screw clockwise until centercase adjustment block begins to move
down and top latch bolt is fully extended (do not remove retaining clip).

3

Set adjusting screw as shown. Tighten adjustment lock screw.

Top Rod (9947-F shown)

Depress
to check
deadlocking

Centercase

Adjusting
Screw

Retaining
Clip

Depress in hole
with screwdriver
to release latch
bolt

Top rod
assembly

Touch Bar

Adjustment
Lock Screw
on Flat
Centercase
Adjustment Block

4

Rod Actuating Link
(9947-F shown)

Check device operation by opening and closing door with outside lever or
thumbpiece.
7

VERTICAL ROD ADJUSTMENT PROCEDURE
3347F-LBR
1

Loosen top adjustment linkage screw on top connector as shown in the diagram.

2

Fully extend latch bolt. Retighten top adjustment linkage screw.

3

Open door and release pushbar. Top latch bolt should be held retracted.

4

Release latch bolt as shown.

5

Check deadlocking.
Depress to
check deadlocking

Depress in hole with
screwdriver to
release latch bolt

Teeth must mesh
properly
Top Adjustment
Linkage Screw
Touch Bar

6

Check device operation by opening and closing door with outside lever or
thumbpiece.
Customer Service

1-877-671-7011

www.allegion.com/us

© Allegion 2015
Printed in U.S.A.
911010-00 Rev. 06/15-e



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 5.5-c021 79.153613, 2013/07/11-05:21:54
Format                          : application/pdf
Subject                         : 
Description                     : 98/99 Series;exit devices;Exit Device Options;98/9927-F;.98/9947-F;98/9949-F;98/9950WDC-F;33/3547-F;33/3527A-F;.33/3547A-F;33/3549A-F;33/3550AWDC-F;2227-F
Modified                        : 2016:01:04 18:08:16Z
Title                           : Von Duprin LBR Auxiliary Fire Pin and 499F Strike Installation Instructions
Size                            : 154027
Author                          : jtellis
Extracted                       : 2016:12:06 22:24:41Z
Sha 1                           : 0102468aaf4d389a0716bafc825a877fc891d56c
Modify Date                     : 2015:06:08 17:39:37Z
Create Date                     : 2015:06:08 17:39:37Z
Creator Tool                    : PScript5.dll Version 5.2.2
Producer                        : Acrobat Distiller 11.0 (Windows)
Instance ID                     : uuid:55654bd1-6e88-46ce-b8ce-72127ab215c0
Document ID                     : uuid:5e0b1c50-8a56-4484-ab19-d76b35c21acf
Page Count                      : 8
Creator                         : PScript5.dll Version 5.2.2
Keywords                        : 98/99, Series;exit, devices;Exit, Device, Options;98/9927-F;, 98/9947-F;98/9949-F;98/9950WDC-F;33/3547-F;33/3527A-F;, 33/3547A-F;33/3549A-F;33/3550AWDC-F;2227-F
EXIF Metadata provided by EXIF.tools

Navigation menu