Technical Guide

DESCRIPTION
Sunline™ 2000 series convertible package rooftop models have two independent refrigerant circuits for efficient
part load operation. Although the units are primarily
designed for curb mounting on a roof, they can also be
slab-mounted at ground level or set on steel beams above
a finished roof.
Cooling only, cooling with gas heat and cooling with electric
heat models are available with a wide variety of factorymounted options and field-installed accessories to make
them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead
rigging.
Every unit is completely piped, wired, charged and tested
at the factory to simplify field installation and to provide
years of dependable operation. Powder paint cabinets provide an exceptionally durable finish with the 750 hour salt
spray process per ASTM-B117 test standard.

SINGLE PACKAGE
GAS / ELECTRIC UNITS AND
SINGLE PACKAGE AIR CONDITIONERS
D2CE / D2CG 300 CONSTANT VOLUME
25 NOMINAL TONS
8.5 EER
SUNLINE 2000 ™

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct
connections only. For bottom duct, you remove the sheet
metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you
replace the supply and return air panels on the rear of the
unit with a side duct flange accessory.
All models are available with five different outdoor air
damper options:
• Single enthalpy economizer
• Differential (dual) enthalpy economizer
• Single enthalpy economizer with power exhaust
• Differential (dual) enthalpy economizer with
power exhaust
• Motorized outdoor air damper
A fixed outdoor air intake assembly is shipped in the return
air compartment of all units ordered without an economizer
or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10,
15 or 25% outdoor air. With bottom duct connections, the
intake damper assembly should be mounted over the
opening in the return air panel. With horizontal ductwork, it
should be mounted on the return air duct.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21359-001-B-0302

All supply air blowers are equipped with a belt drive
that can be adjusted to meet the exact requirements of
the job. A high speed drive accessory is available for
applications with a higher CFM and/or static pressure
requirement.
All compressors include internal pressure relief. Every
refrigerant circuit includes an expansion valve, a liquid
line filter-drier, a discharge line high pressure switch
and a suction line with a freezestat and low pressure/
loss of charge switch. The unit control circuit includes
two 75 VA transformers, two 24-volt circuit breakers
and a relay board with two compressor lockout circuits,
a terminal strip for thermostat wiring, plus an additional
set of pin connectors to simplify the interface of additional field controls.
All 208/230 and 460-volt models are ETL approved. All
208/230 and 575-volt models are CGA approved.
All models include a 1-year limited warranty on the
complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized
steel tubular heat exchangers carry an additional 9year warranty.
All gas heat models are built with two heating sections
for two equal stages of capacity control. Each section
includes a durable heat exchanger with aluminized
steel tubes, a redundant gas valve, spark ignition,
power venting, an ignition module for 100% shut-off
and all of the safety controls required to meet the latest
ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
All electric heat models are wired for a single power
source and include a bank of nickel chromium elements mounted at the discharge of the supply air
blower to provide a high velocity and uniform distribution of air across the heating elements. Every element
is fully protected against excessive current and temperature by fuses and two thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base
pan of the unit or through a knockout in the wiring
panel on the front of the unit.
All internal factory wiring is color coded and numbered
for ease in servicing and troubleshooting.

FACTORY-INSTALLED OPTIONS
ECONOMIZERS
Interlocked outdoor and return air dampers are positioned by a fully modulating, spring return damper actuator capable of introducing up to 100% outdoor air with
nominal 1% leakage type dampers. As the outdoor air
intake dampers open, the return air dampers close.
The changeover from compressor to economizer cooling is determined by one or two solid state enthalpy
controls.
On single enthalpy, an outdoor air sensor determines
when the outdoor air is cool and dry enough to provide
“free” cooling. On differential enthalpy, one sensor
monitors the outdoor air while a second sensor monitors the return air. Whenever the outdoor air is cooler
and drier than the return air, the unit will switch to economizer operation. For either option, the first compressor stage can provide additional cooling during
economizer operation if the room thermostat calls for
second stage.
The dampers and controls are installed and wired at
the factory. Only the accessory rain hood needs to be
assembled and installed in the field.
These economizer options can be used on all duct configurations.
POWER EXHAUST
Both the single and differential economizer options are
available with power exhaust. Whenever the outdoor
air intake dampers are opened for free cooling, the
exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and
wired at the factory. Only the back-draft damper
assembly needs to be field installed and the accessory
rain hoods need to be assembled and installed in the
field.
The power exhaust option can only be used on bottom
duct configurations.
MOTORIZED OUTDOOR AIR INTAKE DAMPER
Interlocked outdoor and return air dampers are controlled by a 2-position, spring return damper actuator.
The outdoor damper will open to some pre-set position
whenever the supply air blower is operating and will
drive fully closed when the blower shuts down.
The damper and controls are installed and wired at the
factory. Only the accessory rain hood needs to be
assembled in the field.

2

This damper option can be used on all duct configurations.
Unitary Products Group

036-21359-001-B-0302

FIELD-INSTALLED ACCESSORIES

ANTI-RECYCLE TIMERS

SINGLE INPUT ELECTRONIC ENTHALPY
ECONOMIZERS

Two solid state timers prevent the compressors from
short-cycling. Once a compressor is de-energized, it
will remain de-energized for approximately five minutes.

Includes a slide-in/plug-in damper assembly with fully
modulating spring-return monitor actuator capable of
introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
The enthalpy system contains one sensor that
monitors the outdoor air and determines when the air is
cool enough and dry enough to provide “free” cooling.
The rainhood is painted to match the basic unit and
must be field-assembled before installing.
Power exhaust is not available as a field installed
option.
DUAL INPUT ELECTRONIC ENTHALPY
ECONOMIZERS
Includes a slide-in / plug-in damper assembly with fully
modulating spring-return monitor actuator capable of
introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
This enthalpy system contains one sensor that monitors the outdoor air and one sensor that monitors the
return air. The logic module compares these two values and modulates the dampers providing the maximum efficiency of economizer system.
The rainhood is painted to match the basic unit and
must be field-assembled before installing.
Power exhaust is not available as
option.

a field installed

MOTORIZED OUTDOOR AIR INTAKE DAMPER
Includes a slide-in/plug-in damper assembly with a
2-position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower
is operating and will drive fully closed when the blower
unit shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
Power exhaust is not available as a field installed
option.
ROOF CURBS
Fourteen inch high roof curbs provide a water-tight seal
between the unit and the finished roof. These full
perimeter curbs meet the requirements of the National
Roofing Contractors Association (NRCA) and are
shipped knocked-down for field assembly. They're
designed to fit inside the base rails of the unit and
include both a wood nailing strip and duct hanger supports.
Unitary Products Group

HIGH ALTITUDE NATURAL GAS
Burner orifices and pilot orifices are provided for proper
furnace operation at altitudes up to 6,000 feet.
PROPANE
Burner orifices, pilot orifices and gas valve parts are
provided to convert a natural gas furnace to propane.
HIGH ALTITUDE PROPANE
Burner orifices and pilot orifices are provided for proper
furnace operation at altitudes up to 6,000 feet. This
accessory supplements the basic propane conversion
kit.
SIDE DUCT FLANGES
One inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal
duct connections. These flanges can also be used individually for bottom supply/horizontal return or horizontal supply/bottom return. They cannot be used on units
with power exhaust.
BAROMETRIC RELIEF DAMPER
This damper accessory can be used to relieve internal
air pressure on units with an economizer but no power
exhaust. This accessory includes a rain hood, a bird
screen and a fully assembled damper. With bottom
duct connections, the damper should be mounted over
the opening in the return air panel. With horizontal
ductwork, the accessory should be mounted on the
return air duct.
ECONOMIZER / POWER EXHAUST RAIN HOODS
A rain hood accessory must be used on units with an
economizer, a motorized damper, or a combined economizer with power exhaust option. These accessories
include all the hood panels, the necessary components
and hardware for field assembly.
HIGH SPEED DRIVE
A smaller blower pulley and a shorter belt increase the
speed of the supply air blower for applications with a
higher CFM and/or static pressure requirement.

LOW AMBIENT CONTROLS TO 0°F
An autotransformer and a thermostat maintain stable
system operation by reducing the speed of the condenser fan motor at low outdoor temperatures. The kit
3

036-21359-001-B-0302

also includes a 1-phase motor to replace the unit's
standard 3-phase condenser fan motor. Standard units
can operate down to 45°F.

Provides coil guard and fastners.

COIL GUARD KIT

L O N G L A S T IN G
P O W D E R P A IN T F IN IS H

E C O N O M IZ E R

E L E C T R IC H E A T E R L O C A T IO N
(O P T IO N A L E L E C T R IC /E L E C T R IC

U N IT S )

H IG H E F F IC IE N C Y S C R O L L C O M P R E S S O R S
C O P P E R T U B E /A L U
C O N D E N S E R C O IL
L O
A N

2 0 G A U G E A L U M IN IZ E D S T E E L
T U B U L A R H E A T E X C H A N G E R S

H O O D

S

M IN U M
W

F IN

V O L T A G E R E L A Y B O A R D
D T E R M IA N L S T R IP
E L E C T R IC A L D IS C O N N E C T
M O U N T IN G L O C A T IO N
( F ie ld in s ta lle d )
K N O C K O U T F O R
S ID E C O N T R O L W IR IN G

E N T R Y

K N O C K O U T F O R
S ID E P O W E R W IR IN G
2 " D IS P O S A B L E
F IL T E R S
O U T D O O R A IR O P E N IN G
F O R S L ID E -IN /P L U G -IN
IN T E R N A L E C O N O M IZ E R

T E R
(F o r
w ith
E L E

M IN A L B L
S in g le P o
E le c tr ic H
C T R IC /E L

E N T R Y S ID E

O C K
in t P o w e r S u p p ly
e a t)
E C T R IC U N IT S

B O T T O M P O W E R & C O N T R O L
W IR IN G E N T R Y

(O P T IO N )

S ID E A N D B O T T O M
S U P P L Y & R E T U R N A IR
D U C T O P E N IN G S (S ID E X S ID E )

H O L E F O R B O T T O M
G A S S U P P L Y E N T R Y
1 " N PNTPIT I
C O N D E N S A T E D R A IN

K N O C K O U T S F O R S ID E
G A S S U P P L Y E N T R Y

P O W E R V E N T O R M O T O R
W IT H P O S T P U R G E C Y C L E
B E L T -D R IV E
B L O W E R M O T O R

F U L L P E R IM E T E R 1 4 G U A G E B A S E
R A IL S W IT H L IF T IN G H O L E S

CAPACITY RATINGS - (ARI 360)*
MODEL
MBH EER
COOLING WITH GAS HEAT

IPLV

MODEL
COOLING WITH ELECTRIC HEAT

MBH

EER

IPLV
8.6

D2CG300N240

290

8.5

8.3

D2CE300E018

290

8.5

D2CG300N320

290

8.5

8.3

D2CE300E036

290

8.5

8.6

D2CE300E054

287

8.5

8.2

D2CE300E072

284

8.5

8.2

COOLING ONLY
D2CE300

290

8.5

8.7

*.

Outside the scope of ARI Standard 340/360.
EER=Energy Efficiency Rating at full load-the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per
watt (Btuh/watt).
IPLV - Integrated part load value.
NOTE: All cooling is three stage.

MODEL

GAS HEAT RATINGS
MBH Input
MBH Output
Stage
Stage
Stage 1
Stage 1
1&2
1&2

D2CG300N240

300

150

240

120

D2CG300N320

400

200

320

160

Unit
Size
300
*.

All models are 80% Steady State Efficiency (S.S.E.).

Sound Power (db 10-12 Watts)
Octave Band Centerline Frequency (Hz)
SWL
IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000 db(A)
10,000 1.30 1,160 12.5 108 108 98 91
93
86
81
76
98
CFM
)

ESP

Blower

db(A)
@ 10 Ft.*
65

At a distance of 10 ft.from the blower.

NOTE: These values have been derived using a model of sound propagation,
measuring the indoor ambient sound levels ten feet from the source. The dBA
values provided are for reference only. Calculation of dBA values cover matters
of system design and application. This constitutes an exception to any specifi-

4

Note: All gas units are two-stage heating. First stage is 50% of total.

cation or guarantee requiring a dBA value or sound data in any other form than
sound power level ratings.

Unitary Products Group

036-21359-001-B-0302

COOL ING CAPACI TIES- 25 TON (DCE / DCG300)
Air On
Evaporator
Coil

Total Power
1
Input2
WB Cap.
CFM
KW
?F MBH
86
72
371
27.1 277
67
340
26.1 335
12,000
62
329
25.5 329
57
329
25.5 329
72
365
27.0 260
67
336
25.9 317
11,000
62
324
25.3 324
57
324
25.3 324
72
359
26.8 244
67
332
25.7 298
10,000
62
318
25.2 318
57
318
25.1 318
72
354
26.6 229
67
326
25.5 280
9,000
62
314
25.0 314
57
314
25.0 314
72
349
26.4 215
67
321
25.3 262
8,000
62
310
24.8 310
57
310
24.8 310
72
318
25.2 186
67
290
24.0 226
6,000
62
282
23.7 277
57
282
23.7 281

Air On
Evaporator
Coil

Tem pera ture of Air on Con denser Coil
85?F
Sen si ble Ca pac ity1 , MBH
Total Power
Cap.1 Input2
En ter ing Dry Bulb, ?F
KW
83 80 77 74 71 68 MBH
86
240 203 167 130 354
28.8 268
299 262 226 189 152 116 325
27.7 324
329 329 293 256 219 183 315
27.1 315
329 329 292 256 219 183 314
27.1 314
226 193 159 125 348
28.6 257
283 249 216 182 148 114 321
27.5 312
324 313 279 245 212 178 309
26.9 309
324 315 281 247 214 180 309
26.9 309
213 182 151 120 342
28.5 245
268 237 206 175 144 113 317
27.4 301
318 296 265 235 204 173 304
26.8 304
318 301 270 239 208 177 304
26.7 304
201 173 145 117 338
28.2 228
252 224 196 168 141 113 312
27.1 279
306 282 254 226 198 170 300
26.5 300
308 286 258 230 203 175 300
26.5 300
190 165 140 115 334
28.0 211
237 212 187 162 137 112 307
26.9 257
293 268 243 218 193 168 297
26.3 297
297 272 247 222 197 172 297
26.3 297
167 148 129 110 304
26.8 177
206 187 168 149 130 111 277
25.5 213
258 240 221 201 192 163 270
25.2 262
262 243 224 205 186 167 270
25.2 266

Total Power
1
2
WB Cap. Input
CFM
KW
?F MBH
86
72 337
30.7 264
67 310
29.5 309
12,000
62 300
28.8 300
57 299
28.8 299
72 331
30.5 254
67 306
29.3 302
11,000
62 295
28.5 295
57 294
28.5 294
72 326
30.2 244
67 302
29.0 294
10,000
62 290
28.3 290
57 290
28.2 290
72 322
30.0 228
67 297
28.8 276
9,000
62 286
28.1 286
57 286
28.1 286
72 319
29.8 212
67 293
28.6 259
8,000
62 283
28.0 283
57 283
28.0 283
72 290
28.3 180
67 264
26.9 224
6,000
62 258
26.6 258
57 258
26.6 258

95?F
Sen si ble Ca pac ity 1, MBH
En ter ing Dry Bulb, ?F
83 80 77 74 71
231 195 158 122
288 251 214 178 141
315 315 278 241 205
314 314 278 241 205
223 189 155 122
279 245 211 178 144
309 307 273 239 206
309 309 275 242 208
214 184 153 122
270 239 208 177 146
304 299 268 237 207
304 304 273 242 211
200 172 144 116 251 223 195 167 139
295 280 253 225 197
297 285 257 229 201
186 161 136 111
232 207 182 157 132
287 262 237 212 187
291 266 241 216 191
158 138 119 100
194 175 156 137 118
243 225 206 187 167
247 228 209 190 171

Tem pera ture of Air on Con denser Coil
105?F
Sen si ble Ca pac ity1 , MBH
Total Power
Cap.1 Input2
En ter ing Dry Bulb, ?F
KW
83 80 77 74 71 68 MBH
86
228 191 155 118 320
32.6 261
283 246 210 173 137 100 294
31.3 294
300 300 263 226 190 153 285
30.5 285
299 299 263 226 190 153 285
30.5 285
221 187 153 119 315
32.3 252
276 242 208 174 141 107 291
31.0 291
295 294 260 226 192 159 280
30.3 280
294 294 261 227 193 160 280
30.3 280
213 183 152 121 310
32.1 243
268 237 206 176 145 114 287
30.8 287
290 287 256 226 195 164 276
30.0 276
290 290 259 228 197 166 275
29.9 275
200 172 144 116 306
31.8 228
251 223 195 167 139 111 283
30.5 274
284 271 243 215 187 159 272
29.8 272
285 273 245 217 189 161 272
29.7 272
187 162 137 112 303
31.6 213
234 209 184 159 134 109 278
30.3 260
278 255 230 205 180 155 269
29.6 269
280 257 232 207 182 157 269
29.6 269
161 141 122 103 276
30.0 183
200 181 162 142 123 104 251
28.5 222
241 223 204 184 165 146 245
28.2 245
242 224 205 186 167 148 245
28.2 245

68
105
168
168
110
172
174
115
176
180
111
169
173
107
162
166
99
148
152

115?F
Sen si ble Ca pac ity1 , MBH
En ter ing Dry Bulb, ?F
83 80 77 74 71
224 188 151 114 278 242 205 169 132
285 285 248 212 175
285 285 248 211 175
218 185 151 117 273 239 205 171 138
280 280 246 213 179
280 280 246 213 179
212 181 151 120 267 236 205 174 143
276 276 245 214 183
275 275 244 214 183
200 172 144 116 251 223 195 167 139
272 262 234 206 178
272 261 234 206 178
188 163 138 113 235 210 185 160 135
269 248 223 198 173
269 248 223 198 173
164 145 125 106 203 194 165 146 127
239 220 201 182 163
240 221 202 182 163

1These ca paci ties are gross rat ings. For net ca pac ity, de duct the heat of the sup ply air blower mo tor, MBH = 3.415 x KW. Ref er to the ap pro pri ate Blower
Per form ance Ta ble for the KW of the sup ply air blower mo tor.
2These rat ings in clude the con denser fan mo tors (To tal 2.3 KW) and the com pres sor mo tors but not the sup ply air blower mo tor.

Nomi nal Rat ing

Unitary Products Group

All Sen si ble Ca pac ity

5

68
95
138
138
104
145
145
112
152
152
111
150
150
110
148
148
108
144
144

036-21359-001-B-0302

BLOWER PER FORM ANCE- 25 TON (DCE/DCG300)
DCE300 - BOT TOM DUCT CON NEC TIONS (COOL ING AP PLI CA TIONS)
7500 CFM
OUTPUT INPUT
(bhp)
(kW)

8750 CFM
OUTPUT INPUT
(bhp)
(kW)

10000 CFM
OUTPUT INPUT
(bhp)
(kW)

11250 CFM
OUTPUT INPUT
(bhp)
(kW)

12500 CFM
OUTPUT INPUT
(bhp)
(kW)

BLOWER
SPEED
(rpm)

PULLEY
TURNS
OPEN:

ESP
(iwg)

975
1005
1040
1070
1100
1135
1165

6.0*
5.0
4.0
3.0
2.0
1.0
0.0

1.4
1.6
1.8
2.0
2.1
2.4
2.6

5.9
6.2
6.6
6.9
7.3
7.7
8.0

4.9
5.1
5.4
5.7
6.0
6.3
6.6

1.0
1.2
1.4
1.6
1.8
2.0
2.2

7.3
7.7
8.1
8.5
8.9
9.3
9.7

STANDARD DRIVE:
6.0
0.5
8.8
6.3
0.7
9.2
6.7
0.9
9.7
7.0
1.1
10.2
7.3
1.3
10.6
7.6
1.6
11.1
8.0
1.8
11.6

7.2
7.6
8.0
8.3
8.7
9.1
9.5

0.1
0.3
0.6
0.8
1.0
1.3

10.9
11.4
11.9
12.4
13.0
13.5

8.9
9.4
9.8
10.2
10.6
11.0

0.2
0.4
0.7

14.3
14.9
15.5

11.7
12.2
12.7

1140
1180
1215
1255
1290
1330
1365

6.0
5.0
4.0
3.0
2.0
1.0
0.0

2.4
2.7
2.9
3.2
3.4
3.7
3.9

7.7
8.2
8.6
9.1
9.5
10.0
10.5

6.3
6.7
7.0
7.4
7.8
8.2
8.6

2.1
2.3
2.6
2.9
3.1
3.4
3.7

9.4
9.9
10.4
11.0
11.5
12.0
12.6

ACCESSORY DRIVE:
7.7
1.6
11.2
8.1
1.9
11.8
8.5
2.2
12.3
9.0
2.5
12.9
9.4
2.7
13.5
9.9
3.0
14.1
10.3
3.3
14.7

9.2
9.7
10.1
10.6
11.1
11.6
12.1

1.1
1.4
1.7
2.0
2.2
2.6
2.9

13.1
13.7
14.3
15.0
15.6
16.4
17.0

10.7
11.2
11.7
12.3
12.8
13.4
13.9

0.5
0.8
1.1
1.4
-

15.0
15.8
16.4
17.2
-

12.3
12.9
13.5
14.1
-

ESP
(iwg)

ESP
(iwg)

ESP
(iwg)

ESP
(iwg)

NOTES:

Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING

BLOWER PERFORMANCE

- 25 TON (DCE/DCG300)

DCG300 - BOT TOM DUCT CON NEC TIONS (COOL ING AP PLI CA TIONS)
7500 CFM
OUTPUT INPUT
(bhp)
(kW)

BLOWER
SPEED
(rpm)

PULLEY
TURNS
OPEN:

ESP
(iwg)

975
1005
1040
1070
1100
1135
1165

6.0*
5.0
4.0
3.0
2.0
1.0
0.0

1.2
1.4
1.6
1.8
2.0
2.2
2.4

5.9
6.2
6.6
6.9
7.3
7.7
8.0

4.9
5.1
5.4
5.7
6.0
6.3
6.6

0.5
0.7
0.9
1.1
1.3
1.6
1.8

1140
1180
1215
1255
1290
1330
1365

6.0
5.0
4.0
3.0
2.0
1.0
0.0

2.2
2.5
2.7
3.0
3.2
3.5
3.7

7.7
8.2
8.6
9.1
9.5
10.0
10.5

6.3
6.7
7.0
7.4
7.8
8.2
8.6

1.6
1.9
2.1
2.4
2.7
3.0
3.2

ESP
(iwg)

8750 CFM
10000 CFM
OUTPUT INPUT
ESP
OUTPUT
(bhp)
(kW)
(iwg)
(bhp)
STANDARD DRIVE:
7.3
6.0
7.7
6.3
8.1
6.7
0.2
9.7
8.5
7.0
0.4
10.2
8.9
7.3
0.6
10.6
9.3
7.6
0.8
11.1
9.7
8.0
1.0
11.6
ACCESSORY DRIVE:
9.4
7.7
0.9
11.2
9.9
8.1
1.2
11.8
10.4
8.5
1.4
12.3
11.0
9.0
1.7
12.9
11.5
9.4
2.0
13.5
12.0
9.9
2.3
14.1
12.6
10.3
2.6
14.7

11250 CFM
OUTPUT INPUT
(bhp)
(kW)

ESP
(iwg)

12500 CFM
OUTPUT INPUT
(bhp)
(kW)

INPUT
(kW)

ESP
(iwg)

8.0
8.3
8.7
9.1
9.5

0.2

13.5

11.0

-

-

-

9.2
9.7
10.1
10.6
11.1
11.6
12.1

0.3
0.6
0.9
1.2
1.5
1.8

13.7
14.3
15.0
15.6
16.4
17.0

11.2
11.7
12.3
12.8
13.4
13.9

-

-

-

NOTES:

Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING

6

Unitary Products Group

036-21359-001-B-0302

ELECTRICAL DATA - Units With Elec tric Heat
MODEL
D2CE

POWER
SUPPLY

300A25
300A25
300A25
300A25
300A25
300A25
300A25
300A25
300A46
300A46
300A46
300A46
300A58
300A58
300A58
300A58

208-3-60
208-3-60
208-3-60
208-3-60
230-3-60
230-3-60
230-3-60
230-3-60
460-3-60
460-3-60
460-3-60
460-3-60
575-3-60
575-3-60
575-3-60
575-3-60

1

ELECTRIC HEATER OPTION
MODEL

kW(1)

STAGES

AMPS

E018
E036
E054
E072
E018
E036
E054
E072
E018
E036
E054
E072
E018
E036
E054
E072

13.5
27.0
40.6
54.1
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0

1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2

37.5
75.1
112.6
150.1
43.3
86.6
129.9
173.2
21.7
43.3
65.0
86.6
17.3
34.6
52.0
69.3

NOMI NAL VOLT AGE
208
240
480
600

VOLTAGE
208
230
460
575

MINIMUM
CIRCUIT
AMPACITY

MAXIMUM
OVERCURRENT
DEVICE (1)

(AMPS)
139.5
142.1
189.0
198.4
139.5
156.5
178.2
221.5
68.3
78.3
89.1
110.7
56.1
62.6
71.2
88.5

(AMPS)
175
175
200
225
175
175
200
250
80
80
100
125
70
70
80
100

KW CAP. MUL TI PLIER
1.00
0.92
0.92
0.92

PHYSICAL DATA
BASIC UNITS
DCE/DCG/DCV
MODELS
300
18 x 15
EVAPORATOR CEN TRIFU GAL BLOWER (Dia. x Wd. in.)
BLOWER
FAN MO TOR HP
15
ROWS DEEP
4
EVAPORATOR
FINS PER INCH
13.5
COIL
FACE AREA (Sq. Ft.)
25.0
30
CONDENSER PRO PEL LER DIA. (in.) (Each)
FAN
FAN MO TOR HP
(Each)
1
(Two Per Unit) NOM. CFM TO TAL
(Each)
7200
ROWS DEEP
3
CONDENSER
FINS PER INCH
15
COIL
FACE AREA (Sq. Ft.)
43.3
COMPRESSOR 12.5 TON, SCROLL, HER METIC,
2
(Qty. Per Unit) TAN DEM (2 STAGE, 50% ea.)
QUAN TITY PER UNIT (16" X 20" X 2")
2
QUAN TITY PER UNIT (16" X 25" X 2")
4
AIR
FILTERS
QUAN TITY PER UNIT (14" X 20" X 2")
3
TO TAL FACE AREA (sq. ft.)
21.4
REFRIGERANT
SYS TEM NO. 1
20/8
22 (lbs./oz.)
CHARGE
SYS TEM NO. 2
20/0

Unitary Products Group

OPERATING WEIGHTS
MODEL SIZE (MBH)
DCE (Cool ing only)
DCV (Cool ing only)
Ba sic Unit DCG (Gas / Elec tric)
DCV (Gas / Elec tric)

Options

N240
N320
N240
N320

Economizer
Econo mizer with
Power Ex haust
Mo tor ized Damper
Elec tric Heater
(Elec/Elec only)

300
2730
2795
2930
2970
2995
3035
160
245

18 KW
36 KW
54 KW
72 KW

Roof Curb
Ba ro met ric Damper
Econo mizer/Mo tor ized Damper
Ac ces so- Rain Hood
ries
Econo mizer/Power Ex haust Rain
Hood
Wood Skid

150
25
30
35
40
185
45
55
90
220

7

036-21359-001-B-0302

BLOWER MO TOR AND DRIVE DATA
MOTOR 1
BLOWER
MODEL
SIZE DRIVE RANGE
(RPM) HP FRAME EFF.
(%)
Stan975/1165
dard
25 TON High
15
Speed 1140/1365
Access

254T

91

AD JUST ABLE MO TOR PUL LEY

BELT
(NOTCHED)

FIXED BLOWER PUL LEY

OUTSIDE PITCH BORE DESIG- OUTSIDE PITCH BORE DESIG- PITCH
DIA.
DIA.
DIA.
LENGTH QTY.
(IN.) NATION
(IN.) NATION
DIA.
(IN.)
(IN.)
(IN.)
(IN.)
(IN.)

DESIGNATION

1LVP58B70
A

6.27.4

7.5

1B5V110

11.3

11.1 1-7/16 5VX860

86.0

1

1B5V94

9.7

9.5

84.0

1

1 5/8
1-7/16 5VX840

1All mo tors have a nomi nal speed of 1800 RPM, a 1.15 serv ice fac tor and a solid base. They can op er ate to the limit of their serv ice fac tor be cause they are lo cated in the mov ing air, upstream
of any heat ing de vice.

STATIC RESIS TANCES*
AIRFLOW (CFM)
7500
8750
10000
11250
12500
ESP
ESP
ESP
ESP
ESP
(IWG)
(IWG)
(IWG)
(IWG)
(IWG)
DEDUCTIONS: (SUBTRACT VALUES BELOW FROM UNIT'S AVAILABLE ESP)
ALLOWANCE FOR WET COIL:
0.10
0.10
0.10
0.10
0.10
ECONOMIZER (RETURN DUCT):
0.06
0.09
0.11
0.14
0.18
18kW ELECTRIC HEAT:
0.31
0.43
0.56
0.71
0.87
36kW ELECTRIC HEAT:
0.38
0.52
0.68
0.87
1.07
54kW ELECTRIC HEAT:
0.62
0.84
1.10
1.39
1.72
72kW ELECTRIC HEAT:
0.68
0.93
1.21
1.54
1.90
ADDITIONS: (ADD VALUES BELOW TO UNIT'S AVAILABLE ESP)
HORIZONTAL (SIDE) SUPPLY DUCT:
0.31
0.26
0.27
0.31
0.41
HORIZONTAL (SIDE) RETURN DUCT:
0.05
0.05
0.05
0.05
0.05
DESCRIPTION

POWER EX HAUST PER FORM ANCE
CFM

KW

STATIC RE SIS TANCE OF RE TURN DUCT WORK, IWG
0.3
0.4
0.5
CFM
KW
CFM
KW
CFM
KW

HIGH*

5250

0.83

4500

0.85

4200

0.88

3750

0.93

3000

0.99

MEDIUM

4900

0.77

3900

0.79

3500

0.82

2900

0.85

-

-

LOW

4400

0.72

3700

0.74

3000

0.78

-

-

-

-

MOTOR
SPEED

0.2

0.6
CFM

KW

*Fac tory Set ting
Power Ex haust mo tor is a 3/4 HP, PSC type with sleeve bear ings, a 48 frame and in her ent protection.

ELEC TRI CAL DATA- Cool ing Only Units and Units With Gas Heat
ELECTRICAL DATA - Cooling Only Units & Units With Gas Heat

MODEL NO.

POWER
SUPPLY

D2CE300 208/230-3-60
& D2CG300
460-3-60
575-3-60

COMPRESSORS

COND. FAN

(QTY. 2)

(#1 & #2)

RLA
(ea.)
41.4
20.0
16.4

LRA
(ea.)
312
150
108

HP
(ea.)
1
1
1

FLA
(ea.)
4.2
2.1
2.0

SUPPLY AIR
BLOWER MOTOR
HP

RLA

15
15
15

38.6
19.3
15.4

MINIMUM

MAXIMUM

CIRCUIT

OVERCURRENT

AMPACITY
(AMPS)
139.5
68.3
56.1

DEVICE (1)
(AMPS)
175
80
70

POWER SUP PLY
VOLTAGE
LIMITATIONS**

208/230-3-60
460-3-60
575-3-60

MIN.
187
414
518

VOLTAGE
MAX.
253
506
630

**Rated in ac cor dance with ARI Stan dard 110, utili za tion range “A”.

8

Unitary Products Group

036-21359-001-B-0302

FIELD WIRING - DCE/DCG ELECTRIC/ELECTRIC AND GAS/ELECTRIC UNITS

C O N T R O L W IR IN G
O N L Y (2 4 V O L T T H E R M O S T A T )
C O O L IN G

C O O L IN G

T H E R M O S T A T
T E R M IN A L S

1

T H E R M O S T A T
T E R M IN A L S

R
Y 1
Y 2

R H

R
Y 1

W 1
W 2
G
B
X
A 1
A 2

Y 2
G

1
2

/ H E A T IN G

U N IT T E R M IN A L
B L O C K 1 T B 2

1

R
Y 1
Y 2

/ H E A T IN G

A D D
J U M P E R

Y 2
W 1

2 4 V O L T
T R A N S F O R M E R

W 2
3

2 4 V O L T
T R A N S F O R M E R

G

A D D
J U M P E R

(E L E C T R O N IC T H E R M O S T A T )
U N IT T E R M IN A L
B L O C K 1 T B 2

1

2 4 V o lt T h e r m o s
( w ith s u b b a s e 2 T
2 T e r m in a l b lo c k 1
o f th e u n it c o n tr o
3 S e c o n d s t a g e h e
e le c tr ic h e a te r .

R
Y 1
Y 2

R C
R H
Y 1
Y 2
W 1
W 2
G
B
L E D 1
L E D 2
C O M
A 1
A 2
T
T

4
4

N O T
U S E D

ta t 2 T H 0 4 7
B 0 4 7 0 0 2 2
T B - lo c a te
l b o x .
a tin g is n o

0 1 0 2 4 o r 2 T H 0 4 7 0 1 5 2 4
4 o r 2 T B 0 4 7 0 0 3 2 4 ).
d o n r e la y b o a r d in 2 4 - v o lt s e c tio n
t r e q u ir e d o n u n its w ith a s in g le s ta g e

P O W E R W IR IN G

W 1
W 2
G
B
X
A 1
A 2

3

W 1
W 2
G
B
X
A 1
A 2

Y 1

1

T H E R M O S T A T
T E R M IN A L S

U N IT T E R M IN A L
B L O C K 1 T B 2

R C

2 4 V o lt T h e r m o s ta t 2 T H 0 4 7 0 1 2 2 4 .
T e r m in a l b lo c k 1 T B - lo c a te d o n r e la y b o a r d in 2 4 - v o lt s e c tio n
o f th e u n it c o n tr o l b o x .

C O O L IN G

(2 4 V O L T T H E R M O S T A T )

2 4 V O L T
T R A N S F O R M E R

L IN
T E
B L
IN
C O

E V O
R M IN
O C K
U N IT
N T R

L T A G E
A L
2 T B
O L B O X

G R O U N D L U G

LLL 231
O

R e fe r to th e
E L E C T R IC A L
D A T A
ta b le s to s iz e th e
p o w e r w ir in g , th e
fu s e s a n d th e
d is c o n n e c t
s w itc h .

T O R E M O T E S E N S O R
2 T H 0 4 7 0 2 2 2 4 IF U S E D
E le c tr o n
T e r m in a
3 S e c o n d
4 T e r m in a
w h e n th
1
2

ic p r o
l b lo c
s ta g e
ls A 1
e th e r

g ra m
k 1 T
h e a
a n d
m o s

m a b le T h e
B - lo c a te d
tin g is n o t r
A 2 p r o v id e
ta t s w itc h e s

rm
o n
e q
a
to

o s ta
r e la
u ir e d
r e la y
th e

t 2 E T
y b o a
o n u
o u tp
s e t-b

0 4 7
r d in
n its
u t to
a c k

F a n s w itc h m u s t b e in " O N " p o s itio n fo r m in im u m

Unitary Products Group

0 0 2 2 4
2 4 -v o
w ith a
c lo s e
p o s itio

( in
lt s
s in
th e
n .

c lu d e
e c tio
g le s
o u td

s s
n o
ta g
o o

u b b a
f th e
e e le
r e c o

s e
u n
c tr
n o

).
it c o n tr o l b o x .
ic h e a te r .
m iz e r d a m p e r s

v e n tila tio n d u r in g h e a te r o p e r a tio n .

9

036-21359-001-B-0302

ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
COMPRESSOR
ACCESS
(See detail "X")

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

BLOWER
ACCESS
BLOWER MOTOR
ACCESS

All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.

UTILITIES ENTRY DATA
OPTIONAL COIL
GUARD KIT

BLOWER
COMPARTMENT
ACCESS
(Auxiliary)

DOT PLUG
(For pressure
Drop Reading)

C

OPENING
SIZE
(DIA.)
1-1/8" KO
3/4" NPS (Fem.)
3-5/8" KO
3" NPS (Fem.)
2-3/8" KO

D

1-11/16" Hole

HOLE

48-5/8" (15TON)
52-5/8" (20TON)

A
CONDENSER
COILS

B

21"
5"
125-1/4" (15 TON)
136-1/4" (20 TON)

FRONT
VIEW

9-3/4"

ELECTRIC HEAT
ACCESS

92"

1
(A)
CONTROL WIRING
ENTRY

5-7/8"

CONTROL BOX
ACCESS

11-1/2"

35"

24-1/4" (15 TON)
36-1/4" (20 TON)

USED FOR
Control
Front
Wiring
Bottom
Front
Power
Wiring
Bottom
Gas Pip ing (Front)1
Gas Pip ing (Bottom)1,2

1" pip ing MPT re quired

2 Open ing in the bot tom of the unit can be lo cated by the slice
in the in su la tion.

(B)
POWER WIRING
ENTRY

BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)

RETURN AIR

RETURN
AIR

SUPPLY AIR

3-3/4"

33"
SUPPLY
AIR
2-3/4"

OUTDOOR AIR

21-1/2"

OUTDOOR AIR
(Economizer)
UNIT BASE WITH RAILS
Shown separately to illustrate
Bottom Duct openings and Power
Connection locations

(B)
POWER WIRING
ENTRY
(A)
CONTROL WIRING
ENTRY

8-1/8"

NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.

BLOWER
ACCESS
BLOWER MOTOR
ACCESS

9-1/4"
12-1/2"

9-3/4"

ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
COMPRESSOR
ACCESS
(See detail "X")

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

BLOWER
COMPARTMENT
ACCESS
(Auxiliary)

CLEARANCES
Front
Back

OPTIONAL
COIL GUARD
KIT

DOT PLUG
(For pressure
Drop Reading)

Left Side (Fil ter Ac cess)

52-5/8

Right Side (Cond. Coil)
Be low Unit1

GAS HEAT
ACCESS
CONDENSER
COILS

VENT AIR
OUTLET
HOODS

21"

Above Unit2

5"
COMBUSTION
AIR INLET
HOOD

7-1/8"
136-1/4
6-3/8"
9-3/4"

(C)
GAS SUPPLY
ENTRY

92"

5-7/8"

(A)
CONTROL WIRING
ENTRY

46-5/8"
CONTROL BOX
ACCESS

FRONT
VIEW

11-1/2"

35"

BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)

35-1/4
RETURN
AIR

(B)
POWER WIRING
ENTRY

1U nits (ap pli ca ble in U.S.A. only) may be in stalled on com bus ti ble floors
made from wood or class A, B or C roof cov er ing ma te rial.
2
Units must be in stalled ou doors. Over hang ing struc tures or shrubs should
not ob struct con denser air dis charge out let.
NOTE:
ELEC/ELEC Mod els: Units and duct work are ap proved for zero clear ance to
com bus ti ble ma te ri als when equipped with elec tric heat ers.

RETURN AIR
3-3/4"

33"
SUPPLY
AIR
2-3/4"

36"
24" (Less Econo mizer)
49" (With Econo mizer)
24" (Less Econo mizer)
36" (With Econo mizer)
36"
20"
72" With 36" Maxi mum
Hori zon tal Over hang
(For Con denser Air
Dis charge)

SUPPLY AIRGAS/ELEC Mod els: A 1" clear ance must be pro vided be tween any

com bus ti ble ma te rial and the sup ply air duct work for a dis tance of 3 feet
from the unit.

OUTDOOR AIR

21-1/2"

11-1/8"

OUTDOOR AIR
The prod ucts of com bus tion must not be al lowed to ac cu mu late within a
(Economizer)

con fined space and re cir cu late.

UNIT BASE WITH RAILS
Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations

(B)
POWER WIRING
ENTRY

(D)
GAS SUPPLY
ENTRY
8-1/8"

NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.

10

46-5/8"
9-1/4"
12-1/2"

9-3/4"

(A)
CONTROL WIRING
ENTRY

Lo cate unit so that the vent air out let hood is at least:
? Three (3) feet above any forced air in let lo cated within 10 hori zon tal feet (exclud ing those in te gral to the unit).
? Four (4) feet be low, 4 hori zon tal feet from, or 1 foot above any door or grav ity
air in let into the build ing.

Unitary Products Group

036-21359-001-B-0302

CONDENSER
SECTION

DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is available for
connecting side ducts.
For bottom duct applications:
1 Remove the side panels from the supply and return
air
compartments to gain access to the bottom supply and
return air duct covers.

EVAPORATOR
SECTION

GAUGE LINE
ACCESS

DOT PLUG
(For pressure
drop reading)

40-3/8"

FILTER
ACCESS
SUPPLY
AIR
RETURN
AIR

5-1/2"
COMPRESSOR
ACCESS

SUPPLY AIR
ACCESS

OUTDOOR
AIR

2

Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.)

3

Replace the side supply and return air compartment
panels.

40-1/2"
18-5/8"
1" NPT FEMALE
COND. DRAIN
CONNECTION

27-3/4"
RETURN AIR
ACCESS

5-1/8"

REAR
VIEW

OUTDOOR AIR
COMPARTMENT
ACCESS

29-5/8" (15 TON)
39-5/8" (20 TON)

For side duct applications;
1 Replace the side panels on the supply and return air
compartments with the accessory flange kit panels.
2

S U P P L Y A IR
C O M P A R T M E N T

P O W E R E X H A U S T
R A IN H O O D
( o n R e tu r n A ir C o m p a r tm e n t)

E C O
M O T
D A M
R A IN
(o n O

N O M IZ E R
O R IZ E D
P E R
H O O D
u td o o r A ir C o m p a r tm e n t)

Connect ductwork to the duct flanges on the rear of
unit.

E C O N O M IZ E R / M O T O R IZ E D D A M P E R
A N D P O W E R E X H A U S T R A IN H O O D S

F IX E
O U T
IN T A
( lo c a
R e tu
C o m

3 4 -1 /4 "

D
D O O R A IR
K E H O O D
te d o n
r n A ir
p a rtm e n t)

1 " C O N D E N S T A T E
D R A IN
(M u s t b e tra p p e d )

1 6 -1 /8 "

5 "
3 6 "
6 6 -1 /2 "

R E A R V IE W

Unitary Products Group

2 "

9 2 "

3 6 -1 /4 "

D E T A IL "Y "
U N IT W IT H R A IN H O O D S

L H

V IE W

11

the

036-21359-001-B-0302

B

E
F

C
A

D
A

F R O N T

B
D

4 Point Loads

DCE
UNIT
300

F R O N T
C

6 Point Loads

4 - POINT LOADS (LBS)
A
B
487
619

TOTAL
2,890

C
646

D
508

DCE
DCE
UNIT
300

TOTAL
2,890

6 - POINT LOADS (LBS)
A
B
415
471

C
528

D
551

E
492

F
433

NOTE: These weights are with economizer and 24kW electric heat.

DCG
UNIT
300

DCG
UNIT
300

4 - POINT LOADS (LBS)
TOTAL
3,130

TOTAL
3,130

A
615

6 - POINT LOADS (LBS)
A
B
418
438

B
671

C
533

D
658

C
962

E
603

NOTE: These weights are with economizer, high heat and oversized motor.

12

Unitary Products Group

D
882

F
510

036-21359-001-B-0302

3.69"
3.56"

Unitary Products Group

BASE RAIL

13

036-21359-001-B-0302

14

Unitary Products Group

036-21359-001-B-0302

MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be factory-assembled, single packaged,
(DCG Electric Cooling/Gas Heat, DCE Electric Cooling/
Optional Electric Heat), designed for outdoor mounted
installation. Units shall have minimum EER ratings of
8.5. They shall have built in field convertible duct connections for down discharge supply/return or horizontal
discharge supply/return, and be available with factory
installed options or field installed accessories.

7. Condensate pan shall be internally sloped and
conform to ASHARE 62-89 self-draining standards.
Condensate connection shall be a minimum of 1"
I.D. female and be a ridged mount connection.
8. Unit shall incorporate a fixed outdoor air damper
with an outdoor air intake opening covered with a
bird screen and a rain hood painted to match the
exterior of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY

The units shall be factory wired, piped, charged with R22 refrigerant and factory tested prior to shipment. All
unit wiring shall be both numbered and color coded.
Enclosed in each unit shall be a factory test log sheet
consisting of the unit tested pressures, temperatures
and amps, as tested prior to shipment.

1. Fan shall be a belt drive assembly and include an
adjustable-pitch motor pulley. Job site selected
(B.H.P.) brake horse power shall not exceed the
motors nameplate horse power rating, plus the service factor. Units shall be designed not to operate
above service factor.

All units shall be manufactured in a facility certified to
ISO 9001 standards and the cooling performance shall
be rated in accordance with DOE and ARI test procedures. Units shall be ETL & CGA listed, classified to
ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236M90 conditions.

2. Fan wheel shall be double-inlet type with forwardcurved blades, dynamically balanced to operate
smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.

UNIT CABINET
1. Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a
non-chalking, powered paint finish, certified at 750
hours salt spray test per ASTM-B117 standards.
2. Indoor blower section shall be insulated with up to
1" thick insulation, coated on the air side. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged
fasteners to prevent insulation from entering the air
stream.
3. Cabinet panels shall be “large” size, easily removable for servicing and maintenance.
4. Full perimeter base rails shall be provided to
assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications.

3. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
1. The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have blades
riveted to corrosion resistant steel spider brackets
and shall be dynamically balanced for smooth
operation.
2. The 2 outdoor fan motors shall be totally enclosed
with permanently lubricated bearings, internally
protected against overload conditions and staged
independently.
REFRIGERANT COMPONENTS
1. Compressors:

5. Disposable 2" filters shall be furnished and be
accessible through a removable access door,
sealed air tight. Units filter track shall be designed
to accommodate either 1" or 2" filters.
6. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan
performance without removing panels or creating
air by-pass of the coils.

Unitary Products Group

2

A.

Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.

B.

Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent
mounting.

Coils:
A.

Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
internally-enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
15

036-21359-001-B-0302

B.

Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.

C.

Condenser coils shall be protected with factory
installed coil guards

3. Refrigerant Circuit and Refrigerant Safety Components shall include:
A.

Balance-port thermostatic expansion valve with
independent circuit feed system.

B.

Filter drier/strainer to eliminate any moisture or foreign matter.

C.

Accessible service gage connections on both suction and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.

D.
E.

resistance and allowing minimum mixed air entering temperature of 25 °F.
3. Burners shall be of the in-shot type, constructed of
aluminum coated steel and contain air mixture
adjustments.
4. All gas piping shall enter the unit cabinet at a single
location through either the side or curb, without any
field modifications.
5. An integrated control board shall provide timed
control of evaporator fan functioning and burner
ignition.
6. Heating section shall be provided with the following
minimum protection:

The refrigeration system shall provide at least 15 °F
of sub-cooling at design conditions.

B.

Unit shall be complete with self contained low-voltage control circuit protected by a resetable circuit
breaker on the 24 volt transformer side.
Unit shall incorporate a lock-out circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor:

1. Loss-of-charge/Low-pressure switch.
2. High-pressure switch.
3. Freeze-protection thermostat, evaporator coil.
If any of the above safety devices trip, an LED (lightemitting diode) indicator shall illuminate.

7

auxiliary

high-temperature

B.

Induced draft motor speed sensor.

C.

Flame roll out switch (manual reset).

D.

Flame proving controls.

limit

Unit shall have two independent stages of capacity.

ELECTRIC HEATING (DCE MODELS)
1. Nickel chromium electric heating elements shall be
provided as required by the application with 1 or 2
stage control, as required, from 13.5 KW to 72 KW
capacity.
2. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating
element system from operating at an excessive
temperature.

C.

Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.

3. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing
(where required).

D.

Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.

UNIT OPERATING CHARACTERISTICS

GAS HEATING SECTION (DCG MODELS)
1. Shall be designed with induced draft combustion
with post purge logic and energy saving direct
spark ignition, redundant main gas valve. Ventor
wheel shall be constructed of stainless steel for
corrosion resistance.
2. The heat exchanger shall be of the tubular type,
constructed of T1-40 aluminized steel for corrosion
16

Primary and
switches.

All Models shall have two independent circuits..

4. Unit Controls:
A.

A.

1. Unit shall be capable of starting and running at 125
°F outdoor temperature, exceeding maximum load
criteria of ARI Standard 210/240.
2. The compressor, with standard controls, shall be
capable of operation down to 25 °F outdoor temperature. Accessory low ambient kit shall be available for operation to 0 °F.
3. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms
up. (Gas heat only)
Unitary Products Group

036-21359-001-B-0302

space during normal operation. During economizer
operation, a mixed-air temperature control shall
modulate the outdoor and return air damper
assembly to prevent the supply air temperature
from dropping below 55°F. Changeover from compressor to economizer operation shall be provided
by two integral electronic enthalpy controls - one
that senses outdoor air and one that senses indoor
air. Both enthalpy sensors supply input to the logic
module which modulates both sets of dampers for
maximum economizer savings. The outdoor intake
opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/
filters shall be provided. Simultaneous economizer/
compressor operation is also possible. Dampers
shall fully close on power loss.

ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single
factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit
field modifications. Separate side and bottom openings
shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES
Compressor- 5 Years
Heat Exchanger - 10 Years
Elect. Heat. Elem.- 5 Years
Parts- 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available
by either/or):
1

ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are
interlocked and positioned by a fully-modulating,
spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall
not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5
IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper
assembly to take in CFM of outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer
operation, a mixed-air temperature control shall
modulate the outdoor and return air damper
assembly to prevent the supply air temperature
from dropping below 55°F. Changeover from compressor to economizer operation shall be provided
by an integral electronic enthalpy control that feeds
input into the basic module. The outdoor intake
opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/
filters shall be provided. Simultaneous economizer/
compressor operation is also possible. Dampers
shall fully close on power loss.

2. DUAL INPUT DIFFERENTIAL ELECTRONIC
ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are interlocked
and positioned by a fully-modulating, spring-return
damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed
2% when dampers are fully closed and operating
against a pressure differential of 0.5 IWG. A unit
mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take
in the design CFM of outdoor air to meet the minimum ventilation requirement of the conditioned

Unitary Products Group

3

MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked
and positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed
2% when dampers are fully closed and operating
against a pressure differential of 0.5 IWG. A unitmounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take
in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during
normal operation. Whenever the indoor fan motor
is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor
air enthalpy. Dampers return to the fully closed
position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
1. ROOF CURB - 14" high, full perimeter curb with
wood nailer (shipped knocked-down).
2. BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure
through the unit during economizer operation.
3. PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to
L.P. gas. One per unit required.
4. HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000
feet altitude.

17

036-21359-001-B-0302

5. HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000
feet altitude. Must be used with propane conversion kit.
6. BURGLAR BARS - Designed to work with above
roofcurbs, depending on unit model. Fits duct
openings of curb supply and return air openings.
7. SIDE DUCT FLANGE - Supply and return air duct
flanges for side duct applications. Do not use on
units with power exhaust.
8. HIGH SPEED DRIVE - Includes blower pulley and
belt for higher CFM and/or static pressure requirements.

12. ANTI-RECYCLE TIMER - Assures 5-minute off-time
between compressor cycles.
13. LOW AMBIENT KIT - Provides unit cooling operation down to 0°F.
OTHER FACTORY INSTALLED OPTIONS
1

POWER EXHAUST OPTION - To work in conjunction with economizers.

2. TECHNICOAT PHENOLIC COATED COND. COIL
3. ELECTRONIC ENTHALPY ECONOMIZER
4. DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER

9. WOOD SKID - Allows unit to be handled with 90"
forks.
10. ECONOMIZER/MOTORIZED DAMPER RAIN HOOD
(DCE/CG300 only) - Contains all hood panels and
the hardware for assembling.

11. THERMOSTATS - Multiple models available from
A.C.O., M.C.O., Electronic or Electrical Mechanical
versions.

18

Unitary Products Group

036-21359-001-B-0302

Unitary Products Group

19

036-21359-001-B-0302

20

Unitary Products Group

036-21359-001-B-0302

Unitary Products Group

21

036-21359-001-B-0302

22

Unitary Products Group

036-21359-001-B-0302

Unitary Products Group

23

Subject to change without notice. Printed in U.S.A.
CD: 6-21359
Copyright © by Unitary Products Group 2002. All rights reserved.
Unitary
Products
Group

5005
York
Drive

036-21359-001-B-0302
Supersedes: 036-21359-001-A-0302
Norman
OK
73069



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Create Date                     : 2002:03:20 14:26:00Z
Modify Date                     : 2002:04:30 11:55:42-04:00
Page Count                      : 24
Page Mode                       : UseThumbs
Creation Date                   : 2002:03:20 14:26:00Z
Producer                        : Acrobat Distiller 4.0 for Windows
Mod Date                        : 2002:04:30 11:55:42-04:00
Metadata Date                   : 2002:04:30 11:55:42-04:00
Title                           : single package gas/elec units & air conditioners d2ce-d2cg
EXIF Metadata provided by EXIF.tools

Navigation menu