York DJ 150 Y TG, Ultra High Eff Sgl Pkg AC And Gas/Elec Units, DJ150 User Manual To The Fe9bc765 Bbfc 4362 A890 29bbf52407f2

User Manual: York DJ 150 to the manual

Open the PDF directly: View PDF PDF.
Page Count: 32

036-21484-003-A-0804
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
ULTRA HIGH EFFICIENCY
SINGLE PACKAGE AIR CONDITIONERS AND
SINGLE PACKAGE GAS/ELECTRIC UNITS
DJ 150
12-1/2 NOMINAL TONS
11.35 EER
TECHNICAL
GUIDE
TECHNICAL
GUIDE
MAGNUM
®
DESCRIPTION
YORK® Predator® Magnum is a convertible single package unit
with a common footprint cabinet and common roof curb for 12-
1/2 ton models. All units have two compressors with indepen-
dent refrigeration circuits to provide 2 stages of cooling. The
units were designed for light commercial applications and can
be easily installed on a roof curb, slab, or frame.
All Predator® Magnum units are self-contained and assembled
on rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely charged,
wired, piped, and tested at the factory to provide a quick and
easy field installation.
All units are convertible between side and down airflow. Inde-
pendent economizer designs are used on side and down dis-
charge applications, as well as all tonnage sizes.
Predator® Magnum units are available in the following configu-
rations: cooling only, cooling with electric heat, and cooling with
gas heat. Electric heaters are available as factory-installed
options or field-installed accessories.
Tested in accordance with:
036-21484-003-A-0804
2Unitary Products
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . . 5
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . . 6
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
MECHANICAL SPECIFICATIONS. . . . . . . . . . . . . . . . . . . 28
LIST OF FIGURES
Fig. # Pg. #
1 PREDATOR® MAGNUM COMPONENT LOCATION . . 3
2 POWER EXHAUST ACCESSORY DOWNFLOW
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3 POWER EXHAUST ACCESSORY HORIZONTAL
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4 UNIT 4 POINT LOAD. . . . . . . . . . . . . . . . . . . . . . . . . . 20
5 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 20
6 UNIT WITH 6 POINT LOAD. . . . . . . . . . . . . . . . . . . . . 20
7 UNIT DIMENSIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8 PREDATOR® MAGNUM ROOF CURB
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9 SUNLINE™ TO PREDATOR® MAGNUM
TRANSITION ROOF CURBS . . . . . . . . . . . . . . . . . . . 22
10 BOTTOM DUCT OPENINGS (FROM ABOVE) . . . . . . 23
11 SIDEFLOW DUCT DIMENSIONS . . . . . . . . . . . . . . . . 23
12 DOWNFLOW ECONOMIZER HOOD DETAIL . . . . . . 24
13 COOLING UNIT WITH GAS HEAT WIRING 230 V.
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
14 COOLING UNIT W/WO ELECTRIC HEAT WIRING
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
15 COOLING UNIT WITH GAS HEAT WIRING 460,
575 & 50 HZ DIAGRAM. . . . . . . . . . . . . . . . . . . . . . . . 27
LIST OF TABLES
Tbl. # Pg. #
1 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3 DJ 150 (12-1/2 TON) CAPACITY RATINGS. . . . . . . . 13
4 UNIT VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . 13
5 DJ 150 (12 1/2 TON) COOLING CAPACITY . . . . . . . 14
6 ELECTRICAL DATA DJ150 (12-1/2 TON) W/O
PWRD CONVENIENCE OUTLET. . . . . . . . . . . . . . . . 15
7 ELECTRICAL DATA DJ150 (12-1/2 TON)
WITH PWRD CONVENIENCE OUTLET. . . . . . . . . . . 15
8 ELECTRIC HEAT MULTIPLIERS . . . . . . . . . . . . . . . . 15
9 BLOWER PERFORMANCE 12-1/2 TON
SIDE DUCT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
10 BLOWER PERFORMANCE 12-1/2 TON
DOWNSHOT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
11 ADDITIONAL STATIC RESISTANCE. . . . . . . . . . . . . 18
12 ELECTRIC HEAT MINIMUM SUPPLY AIR CFM . . . . 18
13 INDOOR BLOWER SPECIFICATIONS . . . . . . . . . . . 18
14 POWER EXHAUST SPECIFICATIONS . . . . . . . . . . . 18
15 4 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . 20
16 6 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . 20
17 UNIT WEIGHT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
18 UNIT CLEARANCES. . . . . . . . . . . . . . . . . . . . . . . . . . 21
036-21484-003-A-0804
Unitary Products 3
FEATURES
High Efficiency – High efficiency units are rated at
11.35 EER. Gas/electric units have electronic spark igni-
tion and power vented combustion with steady state effi-
ciencies of 80%. These efficiencies meet or exceed all
legislated minimum levels and provide low operating
costs.
Service Friendly – The Predator® Magnum incorpo-
rates a number of enhancements which improve service-
ability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged, toolless
panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other unauthorized
persons. It is recommended that the panels be secured
with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access
to the condenser coils for cleaning or inspection.
FIGURE 1 - PREDATOR® MAGNUM COMPONENT LOCATION
“Simplicity” Control
board w/screw
connectors for T-stat
wiring and Network
Connection
Disconnect
location (optional
disconnect switch)
Filter access
(2" throw-away)
Filter drier (solid core)
Condenser Section
Belt-drive blower
motor
Slide out motor
and blower
assembly for easy
adjustment and
service
Power ventor
motor
20-gauge
aluminized steel
tubular heat
exchanger for
long life
(stainless steel
option)
Two-stage gas heating to
maintain warm,
comfortable temperature
Intelligent control
board for safe and
efficient operation
Slide-out drain pan
with brass ¾" FPT
connection
Compressor #1 access
(high-efficiency
compressor w/crankcase
heater)
Side entry power
and control wiring
knockouts
Tool-less door
latch
Roof curbs in eight-and
fourteen-inch heights.
Roof curbs for
transitioning from York
Sunline TM footprint to
the DM/DH/DJ Series
footprint are available
(field-installed accessory)
Base rails w/
forklift slots
( three sides)
and lifting
holes
Compressor #2
access
(high-efficiency
compressor w/
crankcase heater)
Dual stage cooling
for maximum
comfort
Second model
nameplate inside
hinged access panel
036-21484-003-A-0804
4Unitary Products
Both the unit control board and ignition control board uti-
lize flash codes to aid in diagnosis of unit malfunctions.
Unique alarm codes quickly identify the source of the
unit alarm.
All units use the same standard filter size. This standard-
ization removes any confusion on which filter sizes are
needed for replacement.
The non-corrosive drain pan slides out of the unit to per-
mit easy cleaning. The drain pan is accessed by remov-
ing the drain pan cover plate on the rear of the unit. Once
the plate is removed, the drain pan slides out through the
rear of the unit.
All Predator® Magnum units have a second model name-
plate located inside the control access door. This is to pre-
vent deterioration of the nameplate through weathering.
Environmentally Aware For improved Indoor Air
Quality, foil faced insulation is used exclusively through-
out the units.
Balanced Heating – The Predator® Magnum offers
“Ultimate Heating Comfort” with a balance between 1st
and 2nd stage gas heating. The first stage of a gas heat
Predator® Magnum unit provides 60% of the heating
capacity. Balanced heating allows the unit to better main-
tain desired temperatures.
Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two
side duct covers from the outside of the unit and installs
them over the down shot openings. No panel cutting is
required. Convertible airflow design allows maximum
field flexibility and minimum inventory.
System Protection – Suction line freezestats are sup-
plied on all units to protect against loss of charge and coil
frosting when the economizer operates at low outdoor air
temperatures while the compressors are running. Every
unit has solid-core liquid line filter-driers and high and
low-pressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compres-
sors do not require crankcase heaters. Phase monitors
are standard on all units.
Advanced Controls - Simplicity control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
Reliable – From the beginning – All units undergo com-
puter automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term –
All Predator® units are painted with a long lasting, pow-
der paint that stands up over the life of the unit. The paint
used has been proven by a 750 hour salt spray test.
Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, Predator®
Magnum cabinets are designed to fit your roof. With the
optional roof curb, the unit ductwork is designed to fit
around 24” on-center joists or between 48” on-center
joists.
The drain pan can be rotated to drain to either the front
or the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit
and protect the unit during shipment. The rails offer
forklift access from 3 sides, and rigging holes are
available so that an overhead crane can be used to
place the units on a roof.
036-21484-003-A-0804
Unitary Products 5
Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. A clearly identified location is provided to mount a
field supplied electrical disconnect switch. Utility connec-
tions can be made quickly and with a minimum amount
of field labor.
All units are shipped with 2” throw-away filters installed.
Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to han-
dle most airflow requirements. For high static applica-
tions, factory installed alternate indoor fan motors are
available. With the optional indoor fan motor, all units can
supply nominal airflow at a minimum of 1.5” ESP.
Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10-
year warranty.
FACTORY INSTALLED OPTIONS
YORK® offers several equipment options factory installed, for
the Predator® Magnum line.
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The installer needs only to assemble
and mount the outdoor air hood (Provided). The econo-
mizer has spring return, fully modulating damper actua-
tors and is capable of introducing up to 100% outdoor air.
As the outdoor air intake dampers open, the return air
dampers close. The changeover from mechanical refrig-
eration to economizer operation is regulated by the stan-
dard single enthalpy input. There is an optional input
dual dry bulb available. To meet regulated air standards,
the economizer control accepts an optional CO2 input for
demand ventilation. With single enthalpy input, the econ-
omizer control monitors outdoor air. The dual enthalpy kit
provides a second input used to monitor the return air.
With a dual input kit installed, the economizer control
compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maxi-
mum efficiency possible.
Horizontal Economizer - (Without barometric relief) -
All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizers only.
BAS Ready Economizer -(With barometric relief) -
The economizer is provided with a Belimo actuator that
requires a 0-10V DC input from an external source (i.e.,
field installed building automation system controller).
Power exhaust options are available. The economizer is
2% low leakage type with spring return and fully modu-
lating dampers capable of introducing up to 100% out-
side air. Also include 2” pleated filters.
Slab Economizer for Energy Recovery Ventilators-
(With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the standard single enthalpy
input. There is an optional input dual dry bulb available.
To meet regulated air standards, the economizer control
accepts an optional CO2 input for demand ventilation.
With single enthalpy input, the economizer control moni-
tors outdoor air. The dual enthalpy kit provides a second
input used to monitor the return air. With a dual input kit
installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
Aluminized Steel Gas Heat Exchanger - For applica-
tions in non-corrosive environments.
Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
Stainless Steel Drain Pan - An optional rust-proof stain-
less steel drain pan is available to provide years of trou-
ble-free operation in corrosive environments.
Electric Heaters - The electric heaters range from 18kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
Disconnect Switch - For gas heat units and cooling
units with electric heat, an HACR breaker sized to the
unit is provided. For cooling only units, a switch sized to
the largest electric heat available for the particular unit is
provided. Factory installed option only.
Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with
cover, on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source
and wiring. The “Powered” option is powered by a step-
down transformer in the unit. Factory installed option only.
036-21484-003-A-0804
6Unitary Products
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
Phase Monitors - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of
phase condition. (Standard on units with Scroll Com-
pressors.)
Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering
the space between the inner condenser coil and the
main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
BAS - Building Automation System Controls Simplic-
ity™ Intelli-Comfort™ Control - The York® Simplicity
Intelli-Comfort™ control is factory installed. It includes a
supply air sensor, a return air sensor, and an outside air
sensor. There are provisions for a field installed dirty filter
indicator switch, an air-proving switch, an Outside Air
Humidity sensor, a Return Air Humidity sensor, an Inside
IAQ sensor, and an Outside Air IAQ sensor. Construction
mode operation, 365-day real time clock with 7 day pro-
gramming plus holiday scheduling is built-in. Two differ-
ent modes of demand ventilation are achieved through
the Intelli-Comfort™ using CO2 sensors. It uses an
inside CO2 sensor to perform Demand Ventilation. It can
also use an Outside CO2 sensor to perform Differential
Demand Ventilation. It uses a Patented Comfort Ventila-
tion algorithm to provide comfortable ventilation air tem-
perature. The patented economizer-loading algorithm
will protect the equipment when harsh operating condi-
tions exist. Humidity in the occupied space or return duct
can be monitored and controlled via humidity sensors
and the on-board connection for hot gas re-heat system.
It uses the Intelli-Start™ algorithm to maximize energy
savings by recovering the building from the Unoccupied
Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity™ Intelli-
Comfort™ balances space temperature, ventilation air
temperature, CO2 and humidity for ultimate comfort.
Simplicity™ Intelli-Comfort™ with ModLINC
Control - The York® Simplicity™ Intelli-Comfort™ with
ModLINC control is factory installed. It includes all the
features of the Intelli-Comfort™ control with an additional
control to translate communications from MODBUS to
the BACnet MSTP protocol.
Novar® BAS Control - The Novar® ETC-3 building
automation system controller is factory installed. Incudes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
FIELD INSTALLED ACCESSORIES
YORK® offers several equipment accessories for field instal-
lation, for the Predator® Magnum line.
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the econo-
mizer control accepts an optional CO2 input for demand
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit pro-
vides a second input used to monitor the return air. With
a dual input kit installed, the economizer control com-
pares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maxi-
mum efficiency possible
Horizontal Economizer - (Without barometric relief) -
All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizer.
Slab Economizer for Energy Recovery Ventilator-
(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the econo-
036-21484-003-A-0804
Unitary Products 7
mizer control accepts an optional CO2 input for demand
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit pro-
vides a second input used to monitor the return air. With
a dual input kit installed, the economizer control com-
pares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maxi-
mum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood
for field installations without an ERV.
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
Power Exhaust - This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a hori-
zontal flow application.
Manual Outdoor Air Damper - Like the motorized out-
door air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which
installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
accessory only.
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can
be installed to prevent the flue exhaust from entering
nearby fresh air intakes.
-60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
Gas Heat High Altitude Kit - This kit converts a gas
heat unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and pro-
pane.
Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains
the main burner orifices and gas valve replacement
springs.
Gas Piping Kit - Contains pipe nipples, fittings and gas
cock required for gas supply connection with external
shut off.
Electric Heaters - The electric heaters range from 18
kW to 54kW and are available in all the voltage options
of the base units. All heaters are dual staged. Cooling
units include an adapter panel for easy installation of the
electric heaters. Necessary hardware and connectors
are included with the heaters. All heaters are intended
for single point power supply.
Low Limit / Compressor Lockout Kit
1. Compressor Lockout (CLO): To prevent mechani-
cal (compressorized) operation of the unit during
cold outdoor conditions where there is a risk of
returning liquid refrigerant back to the compressors.
2. Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing
the units first stage heating means when there is a
demand for cooling during cold outside conditions.
Metal Frame Filter Kit - Metal frame with polyester filter
medium.
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available
in 8” and 14” heights. For applications with security con-
cerns, burglar bars are available for the duct openings of
the roof curbs.
Roof Curb Transition - Single Piece Adapter (10” High) -
Roof curbs for transitioning from Sunline™ units to Pred-
ator® Magnum. Fits 7.5 to 12.5 Sunline™ roof curbs only.
Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24-
volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with two-
stage heat/two-stage cool or two-stage cooling only ther-
mostats, depending upon unit configuration.
036-21484-003-A-0804
8Unitary Products
TABLE 1: ACCESSORIES
Part Number Description Weight
1RC0470 Roof Curb, 8" Height -
1RC0471 Roof Curb, 14" Height -
1RC0472 Roof Curb, Transition (7.5 T through 12.5 T) -
1BD0408 Burglar Bars, Downflow -
2TP04521825 Electric Heat 18kW 230V -
2TP04522425 Electric Heat 24kW 230V -
2TP04523625 Electric Heat 36kW 230V -
2TP04525425 Electric Heat 54kW 230V -
2TP04521846 Electric Heat 18kW 460V -
2TP04522446 Electric Heat 24kW 460V -
2TP04523646 Electric Heat 36kW 460V -
2TP04525446 Electric Heat 54kW 460V -
2TP04521858 Electric Heat 18kW 575V -
2TP04522458 Electric Heat 24kW 575V -
2TP04523658 Electric Heat 36kW 575V -
2TP04525458 Electric Heat 54kW 575V -
1FA0411 Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief) -
1FA0412 Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief) -
2MD04702724 Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief) -
2MD04703324 Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
2EE04705024 Economizer, Downflow (Incl. Barometric Relief & All Hoods) 124 lbs.
2EE04705124 Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief) 97 lbs.
2EE04705224 Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)
2PE04703225 Power Exhaust, Downflow, 230V (For Units with Economizer only) -
2PE04703246 Power Exhaust, Downflow, 460V (For Units with Economizer only) -
2PE04703258 Power Exhaust, Downflow, 580V (For Units with Economizer only) -
2EC04700924 Dual Enthalpy Control (Use with Single Enthalpy Economizer) -
1EH0407 Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
1RD0411 Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
1EH0408 Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood) 25 lbs.
1EH0409 Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood) -
2AQ04700424 CO2 Detector Unit Mount -
2AQ04700324 CO2 Detector Space Mount -
2SD04700424 Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer) -
2MK04700624 Low Limit / Compressor Lockout Kit
1CG0424 Coil Guard (Electric / Electric & HP models) -
1CG0425 Coil Guard (Gas / Electric models) -
1HG0411 Hail Guard Kit -
1GP0404 Gas Piping Kit -
1NP0441 Propane Conversion Kit -
1HA0442 High Altitude Kit for Natural Gas -
1HA0443 High Altitude Kit for Propane -
1FE0411 Flue Exhaust Extension Kit -
2BC04700106 Gas Heat Kit, -60 deg F, 230V -
2BC04700151 Gas Heat Kit, -60 deg F, 460V -
2BC04700154 Gas Heat Kit, -60 deg F, 575V -
1FL0402 Permanent Filter Kit -
2DF0401 Dirty Filter Switch -
1FF0410 Filter Frame Kit, Metal -
036-21484-003-A-0804
Unitary Products 9
NOMENCLATURE
12½ Ton Predator Model Number Nomenclature
Product Category
D = Air Cond., Single Package
Product Identifier
J = R-22 Ultra High Efficiency
Airflow
Installation Options Additional Options
(See Next Page)
Product Generation
4 = Fourth Generation
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
N 15 = 150 MBH Output Aluminized Steel
N 20 = 200 MBH Output Aluminized Steel
S 15 = 150 MBH Output Stainless Steel
S 20 = 200 MBH Output Stainless Steel
Electric Heat Options
E18 = 18 kW Electric Heat
E24 = 24 kW Electric Heat
E36 = 36 kW Electric Heat
E54 = 54 kW Electric Heat
D J N15 A2A AA 4150
Nominal Cooling Capacity - MBH
150 = 12-½ Ton
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2 & 4
L = Options 1, 3 & 4
M = Options 1, 2, 3 & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3 & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3 & 5
V = Options 1, 4 & 5
W = Options 1, 3, 4 & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr’d Conv Outlet
3 = Smoke Detector S. A.
4 = Smoke Detector R. A.
5 = Pwr’d Conv Outlet
A = Standard Motor
B = Standard Motor/Economizer/Barometric Relief (Downflow only)
C = Standard Motor/Economizer/Power Exhaust (Downflow only)
D = Standard Motor/Motorized Damper (Downflow only)
E = Standard Motor/Horizontal Economizer (No Barometric Relief)
F = Standard Motor/Slab Economizer/Power Exhaust (Downflow only)
G = Standard Motor/Slab Economizer/Barometric Relief (Downflow only)
L = Standard Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)
M = Standard Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)
N = High Static Motor
P = High Static Motor/Economizer/Barometric Relief (Downflow only)
Q = High Static Motor/Economizer/Power Exhaust (Downflow only)
R = High Static Motor/Motorized Damper (Downflow only)
S = High Static Motor/Horizontal Economizer (No Barometric Relief)
T = High Static Motor/Slab Economizer/Power Exhaust (Downflow only)
U =High Static Motor/Slab Economizer/Barometric Relief (Downflow only)
Y = High Static Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)
Z = High Static Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)
036-21484-003-A-0804
10 Unitary Products
NOMENCLATURE ADDITIONAL OPTIONS:
Additional Options
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
AJ SS Drain Pan
AK SS Drain Pan & Phase Monitor
AL SS Drain Pan & Coil Guard
AM SS Drain Pan & Dirty Filter Switch
AN SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
CS CPC Controller, DFS, APS, SS Drain Pan
CT CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
CU CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
CV CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
CW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
CX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
JS Johnson UNT Controller, DFS, APS, SS Drain Pan
JT Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
JU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
JV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
JW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
JX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
036-21484-003-A-0804
Unitary Products 11
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
HS Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
HT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
HU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
HV Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
HW Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
HX Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
WA Intelli-Comfort w/ModLINC Controller
WB Intelli-Comfort w/ModLINC Controller, & Phase Monitor
WC Intelli-Comfort w/ModLINC Controller, & Coil Guard
WD Intelli-Comfort w/ModLINC Controller, Phase Monitor, & Coil Guard
WE Intelli-Comfort w/ModLINC Controller, & Technicoat Cond. Coil
WF Intelli-Comfort w/ModLINC Controller, Technicoat Cond. Coil, & Phase Monitor
WG Intelli-Comfort w/ModLINC Controller, Technicoat Cond. Coil, & Coil Guard
WH Intelli-Comfort w/ModLINC Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
WJ Intelli-Comfort w/ModLINC Controller, & Technicoat Evap. Coil
WK Intelli-Comfort w/ModLINC Controller, Technicoat Evap. Coil, & Phase Monitor
WL Intelli-Comfort w/ModLINC Controller, Technicoat Evap. Coil, & Coil Guard
WM Intelli-Comfort w/ModLINC Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
WN Intelli-Comfort w/ModLINC Controller, & Technicoat Evap. & Cond Coils
WP Intelli-Comfort w/ModLINC Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
WQ Intelli-Comfort w/ModLINC Controller, Technicoat Evap. & Cond Coils, & Coil Guard
WR Intelli-Comfort w/ModLINC Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
WS Intelli-Comfort w/ModLINC Controller, SS Drain Pan
WT Intelli-Comfort w/ModLINC Controller, SS Drain Pan, Phase Monitor, & Coil Guard
WU Intelli-Comfort w/ModLINC Controller, SS Drain Pan, & Technicoat Cond Coils
WV Intelli-Comfort w/ModLINC Controller, SS Drain Pan, & Technicoat Evap Coil
WW Intelli-Comfort w/ModLINC Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
WX Intelli-Comfort w/ModLINC Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Additional Options
036-21484-003-A-0804
12 Unitary Products
NS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
NT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
NU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
NV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
NW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
NX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
LA Simplicity Intelli-Comfort Controller
LB Simplicity Intelli-Comfort Controller, & Phase Monitor
LC Simplicity Intelli-Comfort Controller, & Coil Guard
LD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard
LE Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil
LF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor
LG Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard
LH Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
LJ Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil
LK Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor
LL Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard
LM Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
LN Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils
LP Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
LQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard
LR Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
LS Simplicity Intelli-Comfort Controller, SS Drain Pan
LT Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard
LU Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils
LV Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil
LW Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
LX Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
T1 Technicoat Condenser & SS Drain Pan
T3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
T4 Technicoat Evaporator & SS Drain Pan
T6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
T7 Technicoat Evaporator & Condenser Coils & SS Drain Pan
T9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Additional Options
036-21484-003-A-0804
Unitary Products 13
TABLE 2: PHYSICAL DATA
Component Model
DJ 150 (12-1/2)
Evaporator
Blower
Blower, Centrifugal (Dia. X Wd. in.) 15 x 15
Motor, Standard (HP) 3
Motor, Optional (HP) 5
Evaporator
Coil
Rows 4
Fins per Inch 15
Height (in.) 40
Face Area (ft.2 each) 13.2
Condenser
Fan
(4 per Unit)
Propeller Dia. (in., each) 24
Motor (HP, each) 1/3
CFM, Nominal (each) 3500
Condenser
Coil
(2 per unit)
Rows (each) 2
Fins per Inch 15
Height (in., each) 36
Face Area (ft.2 each) 11.88
Refrigerant
Charge
System 1 (lb./oz.) 2/0
System 2 (lb./oz.) 20/8
Compressors Quantity 2
Type Scroll
Air Filters Size (Wd. x Ht. x Thickness in.) 25x20x2
Number Per Unit 4
TABLE 3: DJ 150 (12-1/2 TON) CAPACITY RATINGS
Size
(Tons) Model
Cooling Capacity
ARI Ratings1
CFM
Sound
Rating
(dB)2
Nominal
Electric
Heat
Capacity3
(kW)
Gas Heat Capacity Gas
Line
Size
(in. OD)
MBH EER IPLV Input
(MBH) Output
(MBH) Seasonal
Efficiency (%) Temp.
Rise (°F)
150
(12-1/2)
Cooling
Only
150 11.35 12.3 3750 86
--- - --
Electric
Heat
18, 24, 36
54 -- - - -
Gas Heat - 180 144 80 10-40 3/4
Gas Heat - 240 192 80 25-55 3/4
1 Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
2 Rated in accordance with ARI 270 standard.
3 See Table 8.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING MIN. MAX.
208/230-3-60 187 252
460-3-60 432 504
575-3-60 540 630
036-21484-003-A-0804
14 Unitary Products
TABLE 5: DJ 150 (12 1/2 TON) COOLING CAPACITY
Air On
Evap. Coil Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
CFM WB
(°F)
Tot.
Cap.1
(MBH)
Tot.
Input2
(kW)
Sensible Capacity (MBH)1
Return Dry Bulb (°F) Tot.
Cap.1
(MBH)
Tot.
Input2
(kW)
Sensible Capacity (MBH)1
Return Dry Bulb (°F)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
3750
72 173 10.9 102 92 81 70 60 49 38 168 11.8 101 90 79 69 58 47 37
67 160 10.6 127 116 105 95 84 73 63 154 11.6 124 114 103 92 81 71 60
62 148 10.5 148 141 131 120 109 99 88 143 11.4 143 138 127 116 106 95 84
57 147 10.5 147 144 133 123 112 101 91 141 11.5 141 137 126 116 105 94 84
4375
72 177 10.91121008774624937 170 11.8 111988573604735
67 163 10.7 138 126 113 101 88 75 63 156 11.7 136 123 110 98 85 72 60
62 151 10.6 151 148 141 128 115 103 90 145 11.5 145 142 136 124 111 98 86
57 150 10.5 150 149 143 131 118 106 93 143 11.5 143 141 136 123 110 98 85
5000
72 180 11.0 122 108 93 79 64 49 35 173 11.9 120 106 91 76 62 47 33
67 167 10.7 150 136 121 107 92 77 63 158 11.8 147 132 118 103 89 74 60
62 154 10.6 154 154 150 136 121 107 92 147 11.6 147 147 146 131 116 102 87
57 154 10.6 154 154 154 139 124 110 95 145 11.6 145 145 145 130 116 101 87
5625
72 184 11.0 133 116 100 83 66 50 33 176 12.0 131 114 98 81 65 48 31
67 170 10.8 162 146 129 113 96 80 63 161 11.8 155 143 127 110 93 77 60
62 157 10.7 157 157 155 139 122 106 89 150 11.7 150 150 149 132 116 99 83
57 157 10.6 157 157 157 140 123 107 90 147 11.7 147 147 147 131 114 98 81
6250
72 188 11.1 143 125 106 87 69 50 32 179 12.1 142 123 105 86 67 49 30
67 173 10.8 173 156 138 119 101 82 63 164 11.9 164 154 135 117 98 79 61
62 161 10.7 161 161 161 142 123 105 86 152 11.7 152 152 152 134 115 96 78
57 160 10.6 160 160 160 141 122 104 85 150 11.8 150 150 150 131 113 94 75
Temperature of Air on Condenser Coil 105°F Temperature of Air on Condenser Coil 115°F
3750
72 158 13.0 99887767564534 148 14.3 96867564544332
67 145 12.9 120 110 99 88 78 67 56 136 14.2 116 106 95 84 74 63 52
62 134 12.7 134 129 119 108 97 87 76 125 14.0 125 121 110 100 89 78 67
57 134 12.8 134 130 119 109 98 87 77 128 14.2 128 123 112 102 91 80 70
4375
72 160 13.1 109 96 83 71 58 45 33 150 14.4 107 94 81 69 56 43 31
67 147 13.0 132 119 107 94 81 69 56 138 14.2 128 116 103 90 78 65 52
62 136 12.8 136 134 128 115 103 90 77 127 14.1 127 125 120 107 94 82 69
57 136 12.9 136 134 129 116 103 91 78 130 14.2 130 127 122 109 97 84 71
5000
72 162 13.2 119 104 89 75 60 46 31 152 14.4 117 102 88 73 58 44 29
67 149 13.0 144 129 114 100 85 71 56 140 14.3 140 126 111 96 82 67 53
62 138 12.8 138 138 137 123 108 93 79 129 14.1 129 129 129 114 100 85 70
57 138 12.9 138 138 138 124 109 94 80 131 14.3 131 131 131 117 102 88 73
5625
72 165 13.2 129 112 96 79 63 46 29 155 14.5 127 111 94 77 61 44 28
67 152 13.1 149 139 123 106 90 73 56 143 14.3 143 135 119 102 86 69 53
62 140 12.9 140 140 140 123 107 90 74 131 14.1 131 131 131 114 98 81 65
57 141 13.0 141 141 141 124 107 91 74 134 14.3 134 134 134 117 100 84 67
6250
72 168 13.3 140 121 102 84 65 47 28 157 14.5 138 119 100 82 63 44 26
67 154 13.1 154 150 131 113 94 75 57 145 14.3 145 145 127 108 90 71 53
62 143 12.9 143 143 143 124 106 87 68 133 14.2 133 133 133 115 96 77 59
57 143 13.0 143 143 143 124 106 87 68 136 14.3 136 136 136 117 99 80 61
Temperature of Air on Condenser Coil 125°F
3750
72 137 15.6 94837362514130
67 127 15.5 112 102 91 80 70 59 48
62 116 15.3 116 113 102 91 81 70 59
57 121 15.5 121 116 105 95 84 73 63
4375
72 139 15.7 105 92 79 67 54 41 29
67 129 15.5 125 112 99 87 74 61 49
62 118 15.3 118 116 111 99 86 73 61
57 123 15.5 123 120 115 102 90 77 64
5000
72 141 15.7 115 100 86 71 57 42 28
67 131 15.5 131 122 108 93 78 64 49
62 120 15.3 120 120 120 106 91 77 62
57 125 15.6 125 125 125 110 95 81 66
5625
72 144 15.7 125 109 92 75 59 42 26
67 133 15.5 133 131 115 99 82 65 49
62 122 15.4 122 122 122 106 89 72 56
57 127 15.6 127 127 127 110 94 77 60
6250
72 146 15.7 135 117 98 80 61 42 24
67 136 15.6 136 136 123 104 86 67 48
62 124 15.4 124 124 124 105 87 68 49
57 129 15.6 129 129 129 110 92 73 54
1 These capacities are gross ratings. For net
capacity, deduct air blower motor, MBh = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
2 These ratings include condensate fan motors
(total 1 kW) and the compressor motors but
not the supply air blower motor.
036-21484-003-A-0804
Unitary Products 15
NOTE: Electric heaters are rated at nominal voltage. Use
this table to determine the electric heat capacity for
heaters supplied at lower voltages.
NOTES FOR TABLES 9 AND TABLE 10:
Blower performance includes dry coil and 2” throwaway
filters.
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
ESP (External Static Pressure) given is that available for the
supply and return air duct system. All internal resistances
have been deducted from the total static pressure of the
blower.
TABLE 6: ELECTRICAL DATA DJ150 (12-1/2 TON) W/O PWRD CONVENIENCE OUTLET
RL
A
LR
A
FL
A
35 3 5 3 5353 5
ea. ea. ea. HP HP HP HP HP HP HP HP HP HP
None -- -- 61.9 67.1 67.4 72.6 80 80 80 90
2TP04521825 13.5 37.5 61.9 67.1 67.4 73.8 80 80 80 90
2TP04522425 18.0 50.0 76.1 82.6 83.0 89.5 80 90 90 90
2TP04523625 25.5 70.8 102.1 108.6 109.0 115.5 110 110 110 125
2TP04525425 40.6 112.7 154.5 161.0 161.4 167.9 175 175 175 175
None -- -- 61.9 67.1 67.4 72.6 80 80 80 90
2TP04521825 18.0 43.3 67.8 74.3 74.6 81.1 80 80 80 90
2TP04522425 24.0 57.7 85.8 92.3 92.7 99.2 90 100 100 100
2TP04523625 34.0 81.8 115.9 122.4 122.7 129.2 125 125 125 150
2TP04525425 54.0 129.9 143.5 150.0 150.4 156.9 175 175 175 175
None -- -- 27.4 30.2 29.6 32.4 35 35 35 40
2TP04521846 18 22.6 33.7 37.2 36.4 39.9 35 40 40 40
2TP04522446 24 30.1 42.7 46.2 45.5 49 45 50 50 50
2TP04523646 34 42.7 57.7 61.2 60.5 64 60 70 70 70
2TP04525446 54 67.8 71.6 75.1 74.3 77.8 80 90 80 90
None -- -- 21.6 23.5 23.4 25.3 25 30 30 30
2TP04521858 18 18.1 26.8 29.2 29 31.4 30 30 30 35
2TP04522458 24 24.1 34 36.4 36.2 38.6 35 40 40 40
2TP04523658 34 34.1 46 48.4 48.3 50.6 50 50 50 60
2TP04525458 54 54.2 57.1 59.5 59.3 61.7 70 70 70 70
1
Pwr
Exh
Motor Electric Heater
Model No.
A
ctual
KW
0.0
5.5 0.0
0.8 5.3 8.1 2.2 0.0
1.5 10.9 16.120.0 146.0
8.4 73.0
10.9 16.1 5.5 0.0
Maximum HACR breaker of the same AMP size is applicable.
6.7 60.0 0.6 4.1 6.0 1.8
MCA
w/Power
Exhaust
(Amps)
Max
Fuse
Size
(Amps)
Max Fuse Size
w/Power
Exhaust
(Amps)
FLA
Pwr
Conv
Outlet Heater
Amps
Min. Circuit
Ampacity
(Amps)
FLA
208 20.0 146.0 1.5
230
460
575
Voltage
Compressors OD Fan
Motors
Supply
Blower
Motor FLA
1
1
TABLE 7: ELECTRICAL DATA DJ150 (12-1/2 TON) WITH PWRD CONVENIENCE OUTLET
RL
LR
FL
A
35 3 5 3 5353 5
ea. ea. ea. HP HP HP HP HP HP HP HP HP HP
None -- -- 71.9 77.1 77.4 82.6 90 90 90 100
2TP04521825 13.5 37.5 73.0 79.5 79.8 86.3 90 90 90 100
2TP04522425 18.0 50.0 88.6 95.1 95.5 102.0 90 100 100 110
2TP04523625 25.5 70.8 114.6 121.1 121.5 128.0 125 125 125 150
2TP04525425 40.6 112.7 167.0 173.5 173.9 180.4 175 175 175 200
None -- -- 71.9 77.1 77.4 82.6 90 90 90 100
2TP04521825 18.0 43.3 80.3 86.8 87.1 93.6 90 90 90 100
2TP04522425 24.0 57.7 98.3 104.8 105.2 111.7 100 110 110 125
2TP04523625 34.0 81.8 128.4 134.9 135.2 141.7 150 150 150 150
2TP04525425 54.0 129.9 156.0 162.5 162.9 169.4 175 175 175 175
None -- -- 32.4 35.2 34.6 37.4 40 40 40 45
2TP04521846 18 22.6 39.9 43.4 42.7 46.2 40 45 45 50
2TP04522446 24 30.1 49 52.5 51.7 55.2 50 60 60 60
2TP04523646 34 42.7 64 67.5 66.7 70.2 70 70 70 80
2TP04525446 54 67.8 77.8 81.3 80.6 84.1 90 90 90 90
None -- -- 25.6 27.5 27.4 29.3 30 30 30 35
2TP04521858 18 18.1 31.8 34.2 34 36.4 35 35 35 40
2TP04522458 24 24.1 39 41.4 41.2 43.6 40 45 45 45
2TP04523658 34 34.1 51 53.4 53.3 55.6 60 60 60 60
2TP04525458 54 54.2 62.1 64.5 64.3 66.7 70 70 70 70
1
2.2 5.0
6.7 60.0 0.6 4.1 6.0 1.8 4.0
8.4
1.5 10.9 16.1 5.5 10.0
1.5 10.9 16.1 5.5 10.0
73.0 0.8 5.3 8.1
460
Maximum HACR breaker of the same AMP size is applicable.
575
Min. Circuit
Ampacity
(Amps)
MCA
w/Power
Exhaust
(Amps)
Max
Fuse
Size
(Amps)
Max Fuse Size
w/Power
Exhaust
(Amps)
Heater
Amps
FLA
208
230
Compressors OD Fan
Motors
20.0 146.0
20.0 146.0
Voltage Electric Heater
Model No.
Actual
KW
Supply
Blower
Motor FLA
Pwr
Exh
Motor
FLA
Pwr
Conv
Outlet
1
1
TABLE 8: ELECTRIC HEAT MULTIPLIERS
VOLTAGE kW Cap. Multiplier
NOMINAL RATING
240 208 0.75
230 0.92
480 460 0.92
600 575 0.92
036-21484-003-A-0804
16 Unitary Products
TABLE 9: BLOWER PERFORMANCE 12-1/2 TON SIDE DUCT
CFM
External Static Pressure
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
3700 ---- ---- ---- ---- ---- ---- ---- ---- ---- 874 1.93 1801 927 2.04 1906 984 2.27 2113 1037 2.41 2245 1089 2.57 2399 1138 2.68 2499 1178 2.82 2628
3800 ---- ---- ---- ---- ---- ---- 840 1.82 1699 888 2.01 1871 941 2.14 1993 997 2.36 2202 1048 2.50 2334 1099 2.67 2485 1146 2.77 2586 1186 2.93 2728
3900 ---- ---- ---- ---- ---- ---- 855 1.92 1786 903 2.09 1947 954 2.24 2085 1009 2.46 2295 1060 2.60 2427 1109 2.76 2576 1155 2.88 2680 1195 3.04 2834
4000 ---- ---- ---- ---- ---- ---- 870 2.01 1877 917 2.18 2028 968 2.34 2182 1022 2.57 2392 1071 2.71 2524 1120 2.87 2672 1163 2.98 2780 1204 3.16 2947
4100 ---- ---- ---- ---- ---- ---- 885 2.12 1973 932 2.27 2115 982 2.45 2283 1035 2.68 2494 1083 2.82 2626 1130 2.98 2774 1171 3.10 2887 1212 3.29 3066
4200 ---- ---- ---- 834 2.11 1970 900 2.22 2072 946 2.37 2207 996 2.56 2390 1048 2.79 2601 1094 2.93 2733 1140 3.09 2881 1179 3.22 3000 1221 3.42 3192
4300 ---- ---- ---- 851 2.19 2042 915 2.33 2175 961 2.47 2305 1009 2.68 2501 1061 2.91 2712 1106 3.05 2844 1150 3.21 2993 1188 3.35 3119 1230 3.57 3324
4400 ---- ---- ---- 868 2.28 2121 931 2.45 2283 975 2.58 2409 1023 2.81 2616 1074 3.03 2828 1117 3.18 2960 1160 3.34 3111 1196 3.48 3245 1239 3.71 3462
4500 822 2.13 1990 885 2.37 2208 946 2.57 2395 990 2.70 2518 1037 2.94 2736 1087 3.16 2948 1129 3.30 3080 1171 3.47 3234 1204 3.62 3377 1247 3.87 3607
4600 838 2.23 2083 901 2.47 2301 961 2.69 2511 1004 2.82 2633 1051 3.07 2862 1099 3.30 3072 1141 3.44 3204 1181 3.61 3362 1212 3.77 3515 1256 4.03 3758
4700 854 2.34 2184 918 2.58 2401 976 2.82 2631 1019 2.95 2753 1064 3.21 2991 1112 3.43 3201 1152 3.58 3333 1191 3.75 3496 1221 3.93 3659 1265 4.20 3916
4800 870 2.46 2291 935 2.69 2508 991 2.96 2755 1033 3.09 2879 1078 3.35 3126 1125 3.58 3335 1164 3.72 3467 1201 3.90 3635 1229 4.09 3810 1273 4.38 4080
4900 887 2.58 2406 952 2.81 2622 1007 3.09 2883 1048 3.23 3011 1092 3.50 3265 1138 3.73 3473 1175 3.87 3605 1211 4.05 3779 1237 4.26 3967 1282 4.56 4250
5000 903 2.71 2527 968 2.94 2744 1022 3.24 3016 1062 3.38 3148 1105 3.66 3409 1151 3.88 3616 1187 4.02 3748 1222 4.21 3929 1245 4.43 4131 1291 4.75 4427
5100 919 2.85 2656 985 3.08 2872 1037 3.38 3152 1077 3.53 3291 1119 3.82 3558 1164 4.04 3763 1198 4.18 3895 1232 4.38 4083 1254 4.61 4301 1300 4.95 4610
5200 936 2.99 2791 1002 3.23 3007 1052 3.53 3293 1091 3.69 3439 1133 3.98 3711 1177 4.20 3914 1210 4.34 4046 1242 4.55 4244 1262 4.80 4477 1308 5.15 4800
5300 952 3.15 2934 1018 3.38 3149 1067 3.69 3438 1106 3.85 3593 1147 4.15 3869 1189 4.37 4070 1221 4.51 4202 1252 4.73 4409 1270 5.00 4660 1317 5.36 4996
5400 968 3.31 3083 1035 3.54 3298 1083 3.85 3587 1120 4.03 3753 1160 4.33 4032 1202 4.54 4231 1233 4.68 4363 1262 4.91 4580 1278 5.20 4848 ---- ---- ----
5500 984 3.48 3240 1052 3.71 3455 1098 4.01 3740 1135 4.20 3918 1174 4.51 4200 1215 4.72 4396 1244 4.86 4528 1273 5.10 4757 1286 5.41 5044 ---- ---- ----
5600 1001 3.65 3403 1069 3.88 3618 1113 4.18 3897 1149 4.39 4089 1188 4.69 4372 1228 4.90 4566 1256 5.04 4698 1283 5.30 4938 ---- ---- ---- ---- ---- ----
5700 1017 3.83 3574 1085 4.06 3788 1128 4.35 4058 1164 4.58 4265 1201 4.88 4549 1241 5.08 4740 1267 5.23 4872 1293 5.50 5125 ---- ---- ---- ---- ---- ----
5800 1033 4.02 3751 1102 4.25 3965 1143 4.53 4224 1178 4.77 4447 1215 5.07 4731 1254 5.28 4918 1279 5.42 5050 ---- ---- ---- ---- ---- ---- ---- ---- ----
5900 1050 4.22 3936 1119 4.45 4149 1159 4.71 4393 1193 4.97 4635 1229 5.27 4917 1267 5.47 5101 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6000 1066 4.43 4127 1136 4.66 4341 1174 4.90 4567 1207 5.18 4828 1243 5.48 5108 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6100 1082 4.64 4326 1152 4.87 4539 1189 5.09 4745 1222 5.39 5027 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6200 1098 4.86 4531 1169 5.09 4744 1204 5.29 4927 1236 5.61 5231 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
High Horsepower Option Required
036-21484-003-A-0804
Unitary Products 17
TABLE 10: BLOWER PERFORMANCE 12-1/2 TON DOWNSHOT
CFM
External Static Pressure
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
3700 ---- ---- ---- ---- ---- ---- 908 1.99 1853 957 2.12 1976 1004 2.27 2112 1050 2.42 2258 1094 2.59 2412 1136 2.76 2571 1177 2.93 2733 1217 3.11 2895
3800 ---- ---- ---- 875 1.96 1831 926 2.09 1946 974 2.23 2077 1020 2.38 2220 1065 2.54 2372 1108 2.71 2530 1151 2.89 2693 1191 3.06 2856 1231 3.24 3021
3900 ---- ---- ---- 893 2.06 1918 943 2.19 2044 990 2.34 2183 1036 2.50 2332 1080 2.67 2489 1123 2.84 2652 1165 3.02 2817 1205 3.20 2983 1244 3.38 3149
4000 ---- ---- ---- 911 2.16 2012 960 2.30 2147 1007 2.46 2294 1052 2.63 2449 1096 2.80 2611 1138 2.98 2777 1179 3.16 2945 1219 3.34 3113 1258 3.52 3280
4100 878 2.13 1984 929 2.27 2113 977 2.42 2256 1023 2.59 2410 1068 2.76 2571 1111 2.94 2737 1153 3.12 2906 1194 3.30 3076 1233 3.48 3245 1271 3.66 3414
4200 897 2.23 2080 947 2.38 2219 995 2.54 2371 1040 2.72 2531 1084 2.89 2697 1127 3.08 2867 1168 3.26 3039 1208 3.44 3211 1247 3.63 3381 1285 3.81 3550
4300 915 2.34 2184 965 2.50 2332 1012 2.67 2491 1056 2.85 2657 1100 3.03 2828 1142 3.22 3001 1183 3.41 3175 1223 3.59 3348 1261 3.78 3520 1298 3.96 3690
4400 934 2.46 2294 983 2.63 2451 1029 2.81 2617 1073 2.99 2788 1116 3.18 2963 1157 3.37 3139 1198 3.56 3315 1237 3.74 3490 1275 3.93 3662 1311 4.11 3832
4500 953 2.59 2411 1001 2.76 2577 1046 2.95 2749 1090 3.14 2925 1132 3.33 3103 1173 3.52 3281 1212 3.71 3459 1251 3.90 3634 1289 4.08 3807 1325 4.27 3977
4600 972 2.72 2536 1019 2.91 2708 1063 3.10 2886 1106 3.29 3066 1148 3.48 3247 1188 3.68 3428 1227 3.87 3606 1266 4.06 3782 1303 4.24 3955 1338 4.43 4125
4700 991 2.86 2667 1036 3.05 2846 1081 3.25 3029 1123 3.45 3212 1164 3.64 3396 1204 3.84 3578 1242 4.03 3758 1280 4.22 3933 1316 4.40 4106 1352 4.59 4275
4800 1009 3.01 2806 1054 3.21 2990 1098 3.41 3177 1139 3.61 3364 1180 3.81 3549 1219 4.00 3732 1257 4.20 3912 1294 4.39 4088 1330 4.57 4260 1365 4.75 4429
4900 1028 3.17 2951 1072 3.37 3141 1115 3.57 3331 1156 3.78 3520 1196 3.98 3707 1234 4.17 3891 1272 4.37 4071 1309 4.56 4246 1344 4.74 4417 1379 4.92 4585
5000 1047 3.33 3103 1090 3.54 3297 1132 3.74 3491 1172 3.95 3682 1211 4.15 3870 1250 4.35 4054 1287 4.54 4233 1323 4.73 4407 1358 4.91 4577 1392 5.09 4744
5100 1066 3.50 3263 1108 3.71 3460 1149 3.92 3656 1189 4.13 3848 1227 4.33 4037 1265 4.53 4221 1302 4.72 4399 1338 4.91 4572 1372 5.09 4740 ---- ---- ----
5200 1084 3.68 3430 1126 3.89 3629 1167 4.11 3827 1205 4.31 4020 1243 4.51 4208 1281 4.71 4391 1317 4.90 4569 1352 5.09 4740 ---- ---- ---- ---- ---- ----
5300 1103 3.87 3603 1144 4.08 3805 1184 4.29 4003 1222 4.50 4196 1259 4.70 4384 1296 4.90 4566 1331 5.09 4742 ---- ---- ---- ---- ---- ---- ---- ---- ----
5400 1122 4.06 3784 1162 4.28 3987 1201 4.49 4185 1238 4.70 4378 1275 4.90 4565 1311 5.09 4745 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
5500 1141 4.26 3971 1180 4.48 4175 1218 4.69 4373 1255 4.90 4564 1291 5.10 4750 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
5600 1160 4.47 4166 1198 4.69 4369 1235 4.90 4566 1271 5.10 4756 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
5700 1178 4.69 4368 1216 4.90 4569 1253 5.11 4765 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
5800 1197 4.91 4576 1234 5.12 4776 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
5900 1216 5.14 4792 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6000 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6200 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
High Horsepower Option Required
Motor Efficiency0.8
Std HP Motor3
036-21484-003-A-0804
18 Unitary Products
TABLE 11: ADDITIONAL STATIC RESISTANCE
CFM Cooling Only1Economizer2 3Electric Heat KW2
18 24 36 54
3700 0.20 0.04 0.18 0.21 0.22 0.26
3900 0.23 0.04 0.20 0.23 0.24 0.28
4100 0.25 0.04 0.22 0.25 0.26 0.31
4300 0.28 0.05 0.24 0.28 0.29 0.34
4500 0.30 0.05 0.26 0.30 0.31 0.37
4700 0.33 0.05 0.29 0.33 0.34 0.40
4900 0.36 0.05 0.31 0.35 0.37 0.43
5100 0.39 0.06 0.34 0.38 0.40 0.46
5300 0.42 0.06 0.37 0.41 0.43 0.49
5500 0.45 0.06 0.40 0.44 0.46 0.53
5700 0.48 0.06 0.43 0.47 0.49 0.56
5900 0.52 0.07 0.46 0.50 0.53 0.59
6100 0.56 0.07 0.49 0.53 0.56 0.62
6300 0.60 0.07 0.53 0.56 0.59 0.65
1 Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2 Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3 The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 12: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM
HEATER UNIT NOMINAL TONS
kW VOLTAGE 12.5
MINIMUM SUPPLY AIR CFM
18
208/230 3750
24
36
54
18
480 3750
24
36
54
18
600 3750
24
36
54
TABLE 13: INDOOR BLOWER SPECIFICATIONS
MODEL MOTOR MOTOR SHEAVE BLOWER SHEAVE BELT
HP RPM Eff. SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model
DJ150 3 1725 80% 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54
5 1725 87% 1.15 184T 4.3 - 5.3 1 1/8 1VP56 6.7 1 BK77 BX55
TABLE 14: POWER EXHAUST SPECIFICATIONS
POWER EXHAUST
MODEL VOLT PHASE MOTOR ELECTRICAL FUSE
SIZE CFM@
0.1 ESP
HP RPM1
1 Motors are multi-tapped and factory wired for high speed.
QTY LRA FLA MCA
2PE0473125 208/230 1
0.75 1075 1
24.9 5.0 6.3 10
3,8002PE0473146 460 1 N/A 2.2 2.8 5
2PE0473158 575 1 1050 1.5 1.9 4
036-21484-003-A-0804
Unitary Products 19
FIGURE 2 - POWER EXHAUST ACCESSORY DOWNFLOW APPLICATION
FIGURE 3 - POWER EXHAUST ACCESSORY HORIZONTAL APPLICATION
22
316
26
58
FRESH AIR HOOD
(FROM ECONOMIZER)
BAROMETRIC RELIEFHOOD
(FROM ECONOMIZER)
POWER CONTROL ACCESS
RETURN DUCT COVER
SUPPLY DUCT COVER
22
316
26
58
FRESH AIR HOOD
(FROM ECONOMIZER)
BAROMETRIC RELIEFHOOD
(FROM ECONOMIZER)
RETURN DUCT COVER
SUP PLY DUCT
(FIELD SUP PLIED)
POWER CONTROL ACCESS
RE TURN DUCT
(FIELD SUP PLIED)
036-21484-003-A-0804
20 Unitary Products
FIGURE 4 - UNIT 4 POINT LOAD
TABLE 15: 4 POINT LOAD WEIGHT
Model Location (lbs.)
ABCD
DJ150 282 359 468 371
FIGURE 5 - UNIT CENTER OF GRAVITY
AB
D
C
LEFT
FRONT
60" 25-½"
LEFT FRONT
FIGURE 6 - UNIT WITH 6 POINT LOAD
TABLE 16: 6 POINT LOAD WEIGHT
Model Locations (lbs.)
ABCDEF
DJ150 184 210 246 323 275 242
TABLE 17: UNIT WEIGHT
Model Shipping Weight (lbs.) Operating Weight (lbs.)
DJ150 1495 1480
AB
C
F
E
D
LEFT
FRONT
036-21484-003-A-0804
Unitary Products 21
FIGURE 7 - UNIT DIMENSIONS
11-1/2
89
27
59
50-3/4
30-11/32
4-1/4
6-3/16
17-3/16
24-3/16
30-3/16
119-7/16
Convenience
Outlet
Convenience
Outlet Power
Entry 7/8
For Gas Pipe Entry
see DETAIL A
For Baserail
Dimensions
see
DETAIL B
FRONT
LEFT
Power
Entry
2-1/2
Control
Entry
7/8
For Drain Dimensions
see DETAIL C
TABLE 18: UNIT CLEARANCES
Top1
1 Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
72” Right 12”
Front 36” Left 36”
Rear2
2 To remove the slide-out drain pan, a rear clearance of 60” is
required. If space is unavailable, the drain pan can be
removed through the front by separating the corner wall.
36” Bottom3
3 Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
0”
5 - 1 / 4 B a s e
P a n
1 7 - 1 3 / 1 6
V i e w o f W a l l A c r o s s f r o m C o i l
G a s P i p e I n l e t
DETAIL A
3 - 3 / 4
3 - 9 / 1 6
2 - 3 / 8
DETAIL B
5 - 3 / 8
DETAIL C
036-21484-003-A-0804
22 Unitary Products
FIGURE 8 - PREDATOR® MAGNUM ROOF CURB DIMENSIONS
8 o r 1 4
5 0 - 1 / 2
3 0
2 0
2 0
8 0 - 5 / 8
6
2 T Y P .
I N S U L A T E D D E C K U N D E R
C O M P R E S S O R S E C T I O N
I N S U L A T E D D E C K U N D E R
C O N D E N S E R S E C T I O N
F R O N T
R I G H T
S U P P L Y
R E T U R N
FIGURE 9 - SUNLINE™ TO PREDATOR® MAGNUM TRANSITION ROOF CURBS
7 6 - 5 / 8
9 4
5 0 - 1 / 2 3 0 - 1 / 2
6 4 - 1 / 4
5 9 - 1 / 4
1 0
2 3 4
2 6 8 0 - 5 / 8
2 T Y P
F R O N T R I G H T
S U P P L Y
R E T U R N
036-21484-003-A-0804
Unitary Products 23
FIGURE 10 - BOTTOM DUCT OPENINGS (FROM ABOVE)
Return
Air
Supply
Air
32-11/16
6-13/16
6-13/16 6-13/16
21-3/16
19-3/16
17-3/16
7-1/8
14-23/32
16-3/8
18-1/16
19-5/8
63-1/2
27-1/2
18
24
21
12-5/16
LEFT
FRONT
Bottom
Condensate
Drain
Bottom
Power, Control and
Convenience Outlet
Wiring Entries
Bottom
Gas Supply Entry
FIGURE 11 - SIDEFLOW DUCT DIMENSIONS
Return
Air
Supply
Air
18-1/4
18-1/4
28-1/4
31-11/16
28-1/4
18-1/16
2-31/32
5-5/32
Dot
Plugs
036-21484-003-A-0804
24 Unitary Products
FIGURE 12 - DOWNFLOW ECONOMIZER HOOD DETAIL
036-21484-003-A-0804
Unitary Products 25
FIGURE 13 - COOLING UNIT WITH GAS HEAT WIRING 230 V. DIAGRAM
036-21484-003-A-0804
26 Unitary Products
FIGURE 14 - COOLING UNIT W/WO ELECTRIC HEAT WIRING DIAGRAM
036-21484-003-A-0804
Unitary Products 27
FIGURE 15 - COOLING UNIT WITH GAS HEAT WIRING 460, 575 & 50 HZ DIAGRAM
036-21484-003-A-0804
28 Unitary Products
MECHANICAL SPECIFICATIONS
SINGLE PACKAGE AIR COOLED GAS/ELECTRIC UNITS FOR 12.5 NOMINAL TONS
PREDATOR® MAGNUM - DJ 150
11.35 EER
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility. YORK®
Predator® Magnum units are convertible single packages
with a common footprint cabinet and common roof curb for all
12-1/2 ton models. All units have two compressors
with independent refrigeration circuits to provide 2 stages of
cooling. The units were designed for light commercial appli-
cations and can be easily installed on a roof curb, slab, or
frame. All Predator® units are self-contained and assembled
on rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely
charged, wired, piped, and tested at the factory to provide a
quick and easy field installation. All units are convertible
between side and down airflow. Independent Predator® Mag-
num Economizer designs are used on side and down
discharge applications, as well as all tonnage sizes. Preda-
tor® Magnum units are available in the following
configurations: cooling only, cooling with electric heat, and
cooling with gas heat. Electric heaters are available as fac-
tory-installed options or field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec,
Gas/Elec), designed for outdoor installation. Units shall have
a minimum EER of 11.35. They shall have built in field con-
vertible duct connections for down discharge supply/return or
horizontal discharge supply/return and be available with fac-
tory installed options or field installed accessories. The units
shall be factory wired, piped and charged with R-22 refriger-
ant and factory tested prior to shipment. All unit wiring shall
be both numbered and color coded. The cooling performance
shall be rated in accordance with DOE and ARI test proce-
dures. Units shall be CSA certified to ANSI Z21.47 and UL
1995/CAN/CSA No. 236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 750 hours salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with
1/2” thick insulation coated on the airside. Aluminum foil
faced insulation shall be used in the unit’s compartments and
be fastened to prevent insulation from entering the air
stream. Cabinet doors shall be hinged with toolless access
for easy servicing and maintenance. Full perimeter base rails
shall be provided to assure reliable transit of equipment,
overhead rigging, fork truck access and proper sealing on
roof curb applications. Disposable 2” filters shall be fur-
nished and be accessible through hinged access door. Fan
performance measuring ports shall be provided on the out-
side of the cabinet to allow accurate air measurements of
evaporator fan performance without removing panels or cre-
ating bypass of the coils. Condensate pan shall be slide out
design, constructed of a non corrosive material, internally
sloped and conforming to ASHRAE 62-B9 standards. Con-
densate connection shall be a minimum of ¾” I.D. female and
be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall
not exceed the motors nameplate horsepower rating plus the
service factor. Units shall be designed to operate within the
service factor. Fan wheel shall be double inlet type with for-
ward curve blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant volume. Bearings shall be sealed
and permanently lubricated for longer life and no
maintenance. Entire blower assembly and motor shall be
slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge
air vertically, have aluminum blades riveted to corrosion
resistant steel spider brackets and shall be dynamically bal-
anced for smooth operation. The outdoor fan motors shall
have permanently lubricated bearings internally protected
against overload conditions and staged independently. A
cleaning window shall be provided on two sides of the units
for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be scroll type, direct drive, internally protected with
internal high-pressure relief and over temperature pro-
tection. The hermetic motor shall be suction gas cooled
and have a voltage range of + or – 10% of the unit name-
plate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
b. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
036-21484-003-A-0804
Unitary Products 29
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice or thermally operated expan-
sion devices.
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resetable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor:
(1) loss-of-charge/Low-pressure switch,
(2) high-pressure switch,
(3) freeze-protection thermostat, evaporator coil.
c. If any of the above safety devices trip, a LED (light-emit-
ting diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
d. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
f. Unit control board shall have on-board diagnostics and
fault code display.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 °F.
h. Control board shall monitor each refrigerant safety
switch independently.
i. Control board shall retain last 5 fault codes in non vola-
tile memory, which will not be lost in the event of a power
loss.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel or optional stainless steel. Shall be designed
with induced draft combustion with post purge logic, energy
saving direct spark ignition, and redundant main gas valve.
The heat exchanger shall be of the tubular type, constructed
of T1-40 aluminized steel (or optional 304 stainless steel) for
corrosion resistance and allowing minimum mixed air enter-
ing temperature of 40 °F. Burners shall be of the in-shot type,
constructed of aluminum-coated steel. All gas piping shall
enter the unit cabinet at a single location, through either the
side or bottom, without any field modifications. An integrated
control board shall provide timed control of evaporator fan
functioning and burner ignition. Heating section shall be pro-
vided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls. Unit shall have two independent
stages of capacity (60% 1st stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two
stages of capacity all sizes. The heating section shall have a
primary limit control(s) (automatic reset) to prevent the heat-
ing element system from operating at an excessive tempera-
ture. The Heating Section assembly shall slide out of the unit
for easy maintenance and service. Units with Electric Heating
Sections shall be wired for a single point power supply with
branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 °F out-
door temperature, exceeding maximum load criteria of ARI
Standard 210/240. The compressor, with standard controls,
shall be capable of operation down to 0 °F outdoor tempera-
ture. Unit shall be provided with fan time delay to prevent cold
air delivery before heat exchanger warms up. (Gas heat
only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
Compressor – 5 Years, Heat Exchanger – 10 Years, Elect.
Heat Elem. – 5 Years, Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall
be made available by either/or):
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER – Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
036-21484-003-A-0804
30 Unitary Products
air damper assembly to take in outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer oper-
ation, a mixed-air temperature control shall modulate the
outdoor and return air damper assembly to prevent the
supply air temperature from dropping below 55 °F.
Changeover from compressor to economizer operation
shall be provided by an integral electronic enthalpy con-
trol that feeds input into the basic module. The outdoor
intake opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/filters
shall be provided. Simultaneous economizer/compressor
operation is also possible. Dampers shall fully close on
power loss. Available with barometric relief or power
exhaust.
2. MOTORIZED OUTDOOR AIR DAMPERS – Outdoor
and return air dampers that are interlocked and posi-
tioned by a 2-position, spring-return damper actuator.
The maximum leakage rate for the outdoor air intake
dampers shall not exceed 2% when dampers are fully
closed and operating against a pressure differential of
0.5 IWG. A unit-mounted potentiometer shall be provided
to adjust the outdoor and return air damper assembly to
take in the design CFM of outdoor air to meet the ventila-
tion requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected posi-
tions – regardless of the outdoor air enthalpy. Dampers
return to the fully closed position when the indoor fan
motor is de-energized. Dampers shall fully close on
power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
ALTERNATE INDOOR BLOWER MOTOR – For appli-
cations with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
CONVENIENCE OUTLET (POWERED/NON-POW-
ERED) – Unit can be provided with an optional 120VAC
GFCI outlet with cover on the corner of the unit housing
the compressors.
PHASE MONITOR - Designed to prevent damage in out-
of-phase condition.
COIL GUARD - Designed to prevent condenser coil
damage.
BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high-
pressure drop across the filters.
BREAKER – An HACR breaker can be factory installed
on the gas heat units or cooling units with electric heater.
DISCONNECT SWITCH - A disconnect can be factory
installed on cooling only units, sized for the largest elec-
tric heat available.
ELECTRIC HEAT - The electric heaters range from 18
kW to 54 kW and are available in all the voltage options
of the base units.
STAINLESS STEEL HEAT EXCHANGER – For applica-
tions in a corrosive environment, this option provides a
full stainless steel heat exchanger assembly.
STAINLESS STEEL DRAIN PAN - Provides years of
trouble free operation in corrosive environments.
SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air com-
partments.
OTHER PRE-ENGINEERED ACCESSORIES AVAIL-
ABLE
ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Sideflow) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
–60 °F GAS HEAT KIT – Provides an electric heat kit for
the gas compartment for use in extreme low ambient
conditions.
ECONOMIZER (Downflow and Sideflow)
POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Sideflow)
DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
036-21484-003-A-0804
Unitary Products 31
Subject to change without notice. Printed in U.S.A. 036-21484-003-A-0804
Copyright © 2004 by Unitary Products. All rights reserved. Supersedes: 036-21484-002-C-0504