DESCRIPTION

TECHNICAL GUIDE

YORK Sunline Ultra™ units are convertible single package
high efficiency rooftops. All models have independent dual
refrigerant circuits for efficient part load operation. Although
the units are primarily designed for curb mounting on a roof,
they can also be slab-mounted at ground level or set on steel
beams above a finished roof.
All units include:
•

SINGLE PACKAGE GAS/ELECTRIC UNITS

•

AND SINGLE PACKAGE
AIR CONDITIONERS

•

DH 180, 210, 240 & 300

•

15, 17.5, 20 & 25 NOMINAL TONS
10.8 EER (15 TONS), 10.2 EER (17.5 TONS), 9.7 EER (20
TONS) AND 9.6 EER (25 TONS)

•
•
•
•
•
•
•
•
•
•
•
•
•
•

Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high and
low pressure/loss of charge switches and freezestats
Hermetically sealed scroll compressors with crankcase
heaters
Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
Permanently lubricated motors
Bottom or side air discharge configuration capability
(field convertible)
Belt drive blower motor with high static drive options
Constant supply air volume (CV) with optional variable
air volume (VAV)
Manufactured under the quality standards of ISO9001
Twenty-four volt control circuit with compressor lock-out
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Hinged filter access and tool free latched doors optional
Hinged tool free blower, blower motor, filters and electrical panel access optional
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and wired
CSA agency approvals on all units

WARRANTY
•
•
•
•

Factory Limited Parts Warranty
One-year parts warranty
A Five-year parts warranty on the compressor and
electric heat elements.
Ten-year parts warranty on the gas-fired heat
exchangers.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

262260-YTG-E-1008

TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Tbl. #

PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3

10 SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) COOLING ONLY 210 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
11 SUPPLY AIR BLOWER PERFORMANCE (20 TON) COOLING ONLY 240 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
12 SUPPLY AIR BLOWER PERFORMANCE (15 TON) GAS HEAT 180 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
13 SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) GAS HEAT 210 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
14 SUPPLY AIR BLOWER PERFORMANCE (20 TON) GAS HEAT 240 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
15 SUPPLY AIR BLOWER PERFORMANCE (25 TON) GAS HEAT 300 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
16 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . 27
17 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 27
18 POWER EXHAUST PERFORMANCE . . . . . . . . . . . . . 27
19 DH 180, 210 & 240 ELECTRICAL DATA WITHOUT
POWERED CONVENIENCE OUTLET . . . . . . . . . . . . 28
20 DH 300 ELECTRICAL DATA STANDARD MOTOR
WITHOUT POWERED CONVENIENCE OUTLET . . . 29
21 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR
WITHOUT POWERED CONVENIENCE OUTLET . . . 29
22 DH 180, 210 & 240 ELECTRICAL DATA WITH
POWERED CONVENIENCE OUTLET . . . . . . . . . . . . 30
23 DH 300 ELECTRICAL DATA STANDARD MOTOR
WITH POWERED CONVENIENCE OUTLET . . . . . . . 31
24 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR
WITH POWERED CONVENIENCE OUTLET . . . . . . . 31
25 DH VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . 32
26 ELECTRIC HEAT CORRECTION FACTORS . . . . . . . 32
27 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
28 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 33
29 SUPPLY FAN VFD WEIGHTS, IN LBS. . . . . . . . . . . . . 33
30 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . . . . 34
31 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 36
32 DH 180, 210, 240 & 300 4 POINT LOAD WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
33 DH 180, 210, 240 & 300 6 POINT LOAD WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 8
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 41
LIST OF FIGURES
Fig. #
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Pg. #

UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ALTITUDE/TEMPERATURE CONVERSION
FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
TYPICAL DH FIELD WIRING DIAGRAM . . . . . . . . . . . 32
UNIT DIMENSIONS DH180, 210, 240 & 300
(FRONT VIEW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
REAR VIEW DIMENSIONS . . . . . . . . . . . . . . . . . . . . . 35
UNIT DIMENSIONS DH180, 210, 240 & 300
(RAINHOOD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . 37
TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . . . . . . 37
UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . 38
UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . 38
UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . 39
ROOF CURB DUCT OPENINGS DIMENSIONS . . . . . 39
CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . . . . . . 39
TYPICAL ROOFTOP INSTALLATION . . . . . . . . . . . . . 40
TYPICAL SIMPLICITY ® CONTROL WIRING
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

LIST OF TABLES
Tbl. #
1
2
3
4
5
6
7
8
9

2

Pg. #

INDOOR SOUND POWER RATING . . . . . . . . . . . . . . . 9
CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . . . . . . 9
GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
DH 180 COOLING CAPACITIES (15 TON) . . . . . . . . . 10
DH 210 COOLING CAPACITIES (17.5 TON) . . . . . . . . 12
DH 240 COOLING CAPACITIES (20 TON) . . . . . . . . . 14
DH 300 COOLING CAPACITIES (25 TON) . . . . . . . . . 16
ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . . 18
SUPPLY AIR BLOWER PERFORMANCE (15 TON) COOLING ONLY 180 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Pg. #

Johnson Controls Unitary Products

262260-YTG-E-1008

PRODUCT NOMENCLATURE

15-25 Ton Sunline Ultra™ Model Number Nomenclature
D H 180 N24 A 2 A AA 1 0 1 2 4 A
Product Category

Product Style

D = A/C, Single Pkg., R-22

A = Style A

Product Identifier

Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.

H = 10.0-11.0 EER A/C

SS Drain Pan
CPC Controller, DFS, APS

Nominal Cooling Capacity

Johnson Controller UNT 1126 (N2 protocol), DFS, APS
Honeywell Controller, DFS, APS

180 = 15 Ton
210 = 17.5 Ton
240 = 20 Ton
300 = 25 Ton

Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
York Commercial Comfort System (YCCS) Rtu Controller

Heat Type and Nominal Heat Capacity

Hot Gas Bypass (Standard on VAV, Optional on CV)
C00 = Cooling Only. No field installed
electric heat

Variable Air Volume, VFD (not available with factory installed BAS options)
Variable Air Volume, VFD with ModLINC (not available with factory installed BAS options)
Variable Air Volume, VFD and Manual Bypass (not available with factory installed BAS options)

Gas Heat Options

Variable Air Volume, VFD and Manual Bypass with ModLINC (not available with factory installed BAS options)
Variable Air Volume, VFD (BAS ready)

N24 = 240 MBH Output Aluminized Steel
N32 = 320 MBH Output Aluminized Steel
S24 = 240 MBH Output Stainless Steel
S32 = 320 MBH Output Stainless Steel

Variable Air Volume, VFD and Manual Bypass (BAS ready)
Variable Air Volume, VFD Ready (for customer provided, field installed drive)
Variable Air Volume, VFD Ready with ModLINC (for customer-provided, field-installed drive)
2" Pleated filters

Electric Heat Options

4" Pleated filters
E18 = 18 KW
E36 = 36 KW
E54 = 54 KW
E72 = 72 KW

BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)
Double Wall Construction
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation

Airflow
A = Std. Motor
B = Std. Motor/Economizer
C = Std. Motor/Economizer/Power Exhaust
(Downflow Only)
D = Std. Motor/Motorized Damper
E = Std. Motor/Motorized Damper/Barometric Relief
J = Std. Motor/Economizer/Barometric Relief
N = Hi Static
P = Hi Static/Economizer
Q = Hi Static/Economizer/Power Exhaust
(Downflow Only)
R = Hi Static/Motorized Damper
K = Hi Static/Motorized Damper/Barometric Relief
S = Hi Static/Economizer/Barometric Relief

Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60

1 = First Generation
2 = Second Generation
Additional Options
Standard Cabinet

Hinged Filter Door & Tool Free Access Cabinet

AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils

BA = Hinged Filter Door & Tool Free Access Panels
BB = Phase Monitor, Hinged Filter Door & Tool Free
Access Panels
BC = Coil Guard, Hinged Filter Door & Tool Free
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Tool Free Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Tool Free Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Tool Free Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Tool Free Access Panels
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Tool Free Access Panels

ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4

N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5

Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.

Johnson Controls Unitary Products

4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet

3

262260-YTG-E-1008

FEATURES

•

All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers,
phase monitor, dirty filter switch, and coil guard to make them
suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
All models are available with these “factory mounted” outdoor
air damper options:
•

Single enthalpy economizer with or without power
exhaust

•

BAS-ready economizer with or without power exhaust

•

Motorized outdoor air damper

•

Barometric Relief Damper

A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake
damper assembly should be mounted over the opening in the
return air panel. With horizontal ductwork, it should be
mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
static drive option is available for applications with a higher
CFM and/or static pressure requirement. A variable air volume
(VAV) option using a variable frequency drive is available for
applications requiring a constant supply duct pressure. A differential pressure transducer is used to monitor supply duct
static pressure and return a speed reference signal to the VFD
to control the output of the indoor blower motor.
All compressors include scroll compressors and internal pressure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. A hot
gas bypass option, consisting of an adjustable compressor
discharge bypass valve, is available for low cooling load
applications.
•

4

Simplicity ® Controls - Simplicity ® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.

Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.

•

The Simplicity® control board used in this product will
effectively operate the cooling system down to 0°F
when this product is applied in a comfort cooling
application for people. An economizer is typically
included in this type of application. When applying this
product for process cooling applications (computer
rooms, switchgear, etc.), please reference applications
bulletin AE-011-07 or call the applications department
for Unitary Products @ 1-877-UPG-SERV for
guidance. Additional accessories may be needed for
stable operation at temperatures below 30°F.
•

Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.

•

Lead-Lag - An integrated Lead-Lag option allows
equal run time hours on all compressors, thereby
extending the life of all compressors. This option is
selectable on the unit control board.

•

Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.

•

Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.

•

Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.

•

On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
Johnson Controls Unitary Products

262260-YTG-E-1008

ELECTRIC HEATER LOCATION
(OPTIONAL ELECTRIC/ELECTRIC UNITS)

LONG LASTING
POWDER PAINT FINISH

20 GAUGE ALUMINIZED STEEL
TUBULAR HEAT EXCHANGERS

HIGH EFFICIENCY COMPRESSORS
WITH CRANKCASE HEATERS
COPPER TUBE/ALUMINUM FIN
CONDENSER COILS
LOW VOLTAGE RELAY BOARD
AND TERMINAL STRIP

ECONOMIZER HOOD

ELECTRICAL DISCONNECT
MOUNTING LOCATION
(Field installed)
KNOCKOUT FOR
SIDE CONTROL WIRING ENTRY
KNOCKOUT FOR
SIDE POWER WIRING ENTRY SIDE

2" DISPOSABLE
FILTERS

TERMINAL BLOCK
(For Single Point Power Supply
with Electric Heat)
ELECTRIC\ELECTRIC UNITS

OUTDOOR AIR OPENING
FOR SLIDE-IN/PLUG-IN
INTERNAL ECONOMIZER(OPTION)

BOTTOM POWER & CONTROL
WIRING ENTRY
KNOCKOUTS FOR SIDE
GAS SUPPLY ENTRY

SIDE AND BOTTOM
SUPPLY & RETURN AIR
DUCT OPENINGS(SIDE X SIDE)
1" NPTI
CONDENSATE DRAIN

BELT-DRIVE
BLOWER MOTOR

FULL PERIMETER 14 GAUGE BASE
RAILS WITH LIFTING HOLES

HOLE FOR BOTTOM
GAS SUPPLY ENTRY
POWER VENTOR MOTOR
WITH POST PURGE CYCLE

GAS/ELECTRIC
UNIT SHOWN

LOCATION OF VFD (Optional)
LOCATION OF VFD BYPASS (Optional)

FIGURE 1 - UNIT CUTAWAY
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.

•

All models are CSA approved.
•

Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.

FACTORY-INSTALLED OPTIONS
•

Gas Heat Operation - All gas heat units are built with
two heating sections for two equal stages of capacity
control. Each section includes a durable heat exchanger
with aluminized steel or optional stainless steel tubes, a
redundant gas valve, spark ignition, power venting, an
ignition module for 100% shut-off and all of the safety
controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•

Electric Heat Operation - All electric heat models (factory installed only) are wired for a single power source
and include a bank of nickel chromium elements
mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across
the heating elements. Every element is fully protected
against excessive current and temperature by fuses and
two thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan
of the unit or through a knockout in the wiring panel on
the front of the unit.

Johnson Controls Unitary Products

BAS Controls - York’s Sunline™ series units offer factory
mounted BAS controls such as Simplicity ® IntelliComfort ™, Novar®, Honeywell, Johnson, York Commercial Comfort System (YCCS) and CPC.

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.

•

BAS-READY ECONOMIZER - Includes a slide-in / plugin damper assembly with fully modulating spring-return
motor actuator with zero to 95-degree rotation capable of
introducing up to 100% outdoor air with nominal 1% leakage type dampers.
Actuator requires 2-10 VDC input from an external
source, such as a field-installed or factory-installed BAS
controller. BAS-ready actuators have an adjustable auxiliary end-switch for optional power exhaust control.
For units with optional VAV or Simplicity® Intelli-Comfort™ control, a factory-installed, dry bulb sensor determines if outdoor air temperature is low enough to provide
free-cooling operation. (Field-installed humidity sensors
for either outdoor air or outdoor & return air streams are

5

262260-YTG-E-1008

available for single enthalpy and differential enthalpy
configurations, respectively).

Blower Motor Access compartment. The switch can be
used to either route power to the VFD for modulating
control of the blower motor, to bypass the drive and operate the motor at full speed, or to power the drive (and not
the motor) for diagnostic purposes.

The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•

POWER EXHAUST - Our economizer options are available with power exhaust. Whenever the outdoor air intake
dampers are opened for free cooling, the exhaust fan will
be energized to prevent the conditioned space from being
over-pressurized during economizer operation. BASready economizer actuators have an adjustable auxiliary
end-switch to provide a range of damper positions available
to energize power exhaust. For units with optional VAV,
power exhaust is energized by means of a binary output
signal from the unit's VAV control board.

Due to space limitations, VAV is not available with any of
the factory-installed BAS options described below, but is
available with ‘BAS-ready’ models. Terminal blocks are
provided in the control box for field wiring of the customer-installed BAS.
A ‘VFD-ready’ option provides the provisions for a customer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment
which may accommodate other vendor’s drives depending on their size. In order to utilize the unit’s mounting
bracket, the maximum recommended drive dimensions
are as follows:

The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood must be assembled
and installed in the field.

For 5-hp motor applications ........................10” H x 6” W x 7” D

The power exhaust option can only be used on bottom duct configurations.
•

For 7.5 thru 15-hp motor applications .........13” H x 8” W x 8” D

If the drive will not fit in the allotted space, then it will
have to be mounted elsewhere; either within the building
on a perpendicular wall which is not subjected to excessive temperature, vibration, humidity, dust, corrosive
gas, explosive gas, etc., or within an appropriate enclosure rated for outside installation to safeguard against
moisture, dust and excessive heat.

MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.

•

•

•

•

BAROMETRIC RELIEF DAMPER - This damper option
can be used to relieve internal building air pressure on
units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1" processes. Coating is applied by total
immersion of the complete coil for maximum protection.
ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
VARIABLE AIR VOLUME (VAV) - A factory-installed
variable frequency drive (VFD), mounted in the Blower
Access compartment, is used to control the speed of the
indoor blower motor in order to maintain a constant static
pressure in the supply duct. A pressure transducer and
VAV control board are mounted inside the control box.
The drive comes completely wired and pre-programmed
from the factory.
An optional, factory-installed manual bypass switch
available with factory-installed VFD can be found in the

6

A terminal block located in the control box is provided for
field connection of the VFD controls.
•

HOT GAS BYPASS - To allow for low cooling load operation, a direct-acting pressure-modulating bypass control
valve installed on the system #1 discharge line is used to
divert high temperature, high pressure refrigerant around
the TXV in order to maintain a desired minimum evaporator pressure. HGBP is standard on all units with VAV
and optional with CV units.

•

FILTER OPTIONS - Standard units are shipped with 2”
throw-away filters installed. 2” pleated and 4” pleated filters are offered as a factory installed option.

•

CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or
you may order the unit with a “non-powered” convenience outlet that can be wired in the field.

•

DISCONNECT SWITCH - A HACR breaker sized to the
unit max fuse size is provided. Factory installed option
only.

•

BAS - Building Automation System Controls (available on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York®
Simplicity® INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving

Johnson Controls Unitary Products

262260-YTG-E-1008

switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2
sensor to perform Differential Demand Ventilation. It
uses a Patented Comfort Ventilation algorithm to provide
comfortable ventilation air temperature. The patented
economizer-loading algorithm will protect the equipment
when harsh operating conditions exist. Humidity in the
occupied space or return duct can be monitored and
controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLIStart™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the
Occupied Setpoints just in time for the Occupied Time
Period to begin. The Simplicity® INTELLI-Comfort™ balances space temperature, ventilation air temperature,
CO2 and humidity for ultimate comfort.
Simplicity® INTELLI-Comfort™ with ModLINC CONTROL - The York® Simplicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® building automation system controller is factory installed. Includes supply
air sensor, return air sensor, dirty filter indicator switch,
and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system
controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air
proving switch.
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.

Johnson Controls Unitary Products

YORK COMMERCIAL COMFORT SYSTEM (YCCS) Provides rooftop system integration for YCCS single
zone, change-over bypass and VAV systems.
•

SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.

Factory installed smoke detectors in the return air,
may be subjected to freezing temperatures during
“off” times due to out side air infiltration. these smoke
detectors have an operational limit of 32°F to 131°F.
smoke detectors installed in areas that could be out
side those limitations will have to be moved to prevent
having false alarms.
•

COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.

•

STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.

•

STAINLESS STEEL DRAIN PAN- An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.

•

PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.

•

HIGH STATIC DRIVE - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower performance.

•

DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.

•

HINGED FILTER DOOR/”TOOL FREE” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.

NOTE: Knobs are shipped separately within the unit to prevent shipping damage. These must be field installed
for tool free operation.

7

262260-YTG-E-1008

•

HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR,
FILTER AND ELECTRIC ACCESS PANELS - This
option allows for complete hinged and tool free access to
the unit's blower, blower motor, filters and electrical panel
sections.

tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•

SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.

•

BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.

•

HIGH STATIC DRIVE - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower performance.

•

ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.

•

BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.

•

FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.

•

WOOD SKID - Allows unit to be handled with 90” forks.

•

CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.

•

COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.

•

PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.

FIELD-INSTALLED ACCESSORIES
•

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.

•

MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.

•

ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit
and include both a wood nailing strip and duct hanger
supports.

•

HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.

•

PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.

•

HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-

8

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 1: INDOOR SOUND POWER RATING1
ESP

UNIT
SIZE

SOUND POWER (db 10-12 Watts)

BLOWER

Octave Band Centerline Frequency (Hz)

CFM
IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

SWL
dB(A)

dB(A)
@
10Ft.2

180

6,000

1.00

1,080

4.60

99

99

89

82

84

77

72

67

89

56

210, 240

8,000

1.00

1,120

6.65

102

102

92

85

87

80

75

70

92

59

300

10,000

1.30

1,160

12.5

108

108

98

91

93

86

81

76

98

65

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no
way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or
sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)1
MODEL

MBH

EER

2

TABLE 3: GAS HEAT RATINGS1
IPLV

3

COOLING ONLY
1784
205
223
271

DH180C00
DH210C00
DH240C00
DH300C00

10.8
10.2
9.7
9.6

11.3
10.8
10.2
9.6

COOLING WITH GAS HEAT
DH180N/S
DH210N/S
DH240N/S
DH300N/S

1784
205
223
271

10.8
10.2
9.7
9.6

11.3
10.8
10.2
9.6

COOLING WITH ELECTRIC HEAT
DH180E18
10.8
1784

11.3

1784

10.8

DH180E54

1764

10.5

11.0

DH180E72

1764
205
205
203
203
223
223
221
219
271
271
269
269

10.5
10.2
10.2
10.0
10.0
9.6
9.6
9.5
9.5
9.6
9.6
9.5
9.5

11.0
10.8
10.8
10.6
10.6
10.1
10.1
9.7
9.7
9.6
9.6
9.4
9.4

DH180E36

DH210E18
DH210E36
DH210E54
DH210E72
DH240E18
DH240E36
DH240E54
DH240E72
DH300E18
DH300E36
DH300E54
DH300E72

11.3

1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. IPLV = Integrated part load value.
4. Deduct 2 MBH @ 208V.

Johnson Controls Unitary Products

MODEL

MBH INPUT

MBH OUTPUT

DH180N/S24

300

240

DH180N/S32

400

320

DH210N/S24

300

240

DH210N/S32

400

320

DH240N/S24

300

240

DH240N/S32

400

320

DH300N/S24

300

240

DH300N/S32

400

320

1. All units are two-stage heating. First stage is 50% of total.

SSE = Steady State Efficiency (80%) - Output divided by Input

For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to be
controlled by duct static pressure via the VAV control board.
If there are VAV boxes present in the duct system,
the boxes must be driven to the full-open position
using a customer-supplied power source to assure
adequate airflow across electric heating elements or
gas heat exchanger tubes.

9

262260-YTG-E-1008

TABLE 4: DH 180 COOLING CAPACITIES (15 TON)
AIR ON
EVAPORATOR
COIL
CFM

4500

5250

6000

6750

7500

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

AIR ON
EVAPORATOR
COIL
CFM

4500

5250

6000

6750

7500

10

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

223.0
211.0
199.0
181.3
178.5
231.5
219.0
206.5
188.1
185.3
240.0
227.0
214.0
195.0
192.0
226.4
213.5
194.5
191.5
225.8
213.0
194.0
191.0

11.3
11.2
11.1
10.8
10.5
11.3
11.2
11.2
10.9
10.6
11.4
11.3
11.2
10.9
10.6
11.2
11.2
10.8
10.5
11.2
11.1
10.8
10.5

100.4
133.1
165.8
181.3
178.5
107.2
148.2
189.2
188.1
185.3
114.0
163.3
212.6
195.0
192.0
178.0
212.8
194.5
191.5
192.8
213.0
194.0
191.0

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

213.2
195.1
177.0
164.6
161.8
218.6
200.0
181.5
168.8
165.9
224.0
205.0
186.0
173.0
170.0
208.9
189.5
176.3
173.2
212.7
193.0
179.5
176.4

14.5
14.0
13.5
13.4
13.7
14.5
14.0
13.6
13.5
13.7
14.6
14.1
13.6
13.5
13.8
14.3
13.8
13.6
14.0
14.4
13.9
13.8
14.1

98.2
128.0
157.8
164.6
161.8
117.4
144.7
171.9
168.8
165.9
136.6
161.3
186.0
173.0
170.0
173.9
189.5
176.3
173.2
186.4
193.0
179.5
176.4

TEMPERATURE OF AIR ON CONDENSER COIL
75°F
SENSIBLE CAPACITY, MBH
TOTAL
POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

75

70

65

79.0
111.7
144.4
178.6
179.1
87.6
122.9
158.3
186.8
185.5
96.2
134.2
172.2
195.0
192.0
144.8
185.2
194.5
191.5
155.5
198.3
194.0
191.0

77.9
109.2
140.4
169.9
170.1
87.0
121.2
155.3
177.0
175.6
96.2
133.2
170.2
184.0
181.0
142.7
181.7
185.4
182.4
152.3
193.3
186.8
183.7

56.5
87.8
119.0
148.5
151.1
61.8
95.9
130.0
162.3
165.0
67.0
104.0
141.0
176.0
179.0
109.5
148.5
181.4
181.4
115.1
156.0
186.8
183.7

66.4
97.6
127.2
129.7
70.6
104.7
137.0
139.8
74.8
111.8
146.8
149.8
76.3
115.3
148.2
148.1
77.8
118.7
149.5
146.5

76.2
105.8
108.3
79.5
111.7
114.5
82.7
117.7
120.7
82.1
115.0
114.9
81.5
112.2
109.2

84.4
86.9
86.5
89.2
88.5
91.5
81.8
81.7
75.0
71.9

57.7
90.3
123.0
157.3
162.3
62.3
97.7
133.0
170.1
175.7
67.0
105.0
143.0
183.0
189.0
111.6
152.0
188.5
190.0
118.2
161.0
194.0
191.0

68.9
101.6
135.9
140.9
72.4
107.7
144.9
150.4
75.8
113.8
153.8
159.8
78.4
118.8
155.3
156.8
81.0
123.7
156.7
153.8

80.2
114.5
119.6
82.5
119.6
125.1
84.7
124.7
130.7
85.6
122.1
123.6
86.5
119.5
116.5

93.1
98.2
94.3
99.8
95.5
101.5
88.9
90.4
82.2
79.3

218.1
203.0
188.0
173.0
170.1
225.0
209.5
194.0
178.5
175.6
232.0
216.0
200.0
184.0
181.0
217.6
201.5
185.4
182.4
219.2
203.0
186.8
183.7

12.9
12.6
12.3
12.1
12.1
12.9
12.6
12.4
12.2
12.2
13.0
12.7
12.4
12.2
12.2
12.8
12.5
12.2
12.2
12.8
12.5
12.3
12.3

99.3
130.5
161.8
173.0
170.1
112.3
146.4
180.5
178.5
175.6
125.3
162.3
199.3
184.0
181.0
176.0
201.2
185.4
182.4
189.6
203.0
186.8
183.7

TEMPERATURE OF AIR ON CONDENSER COIL
95°F
SENSIBLE CAPACITY, MBH
TOTAL
POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

76.8
106.6
136.4
161.2
161.2
86.5
119.4
152.3
167.1
165.6
96.2
132.2
168.2
173.0
170.0
140.7
178.2
176.3
173.2
149.2
188.3
179.5
176.4

75.6
103.7
131.9
153.8
151.9
84.6
115.5
146.3
158.7
156.0
93.7
127.2
160.7
163.5
160.0
137.0
170.1
166.8
163.2
146.8
179.6
170.0
166.4

54.2
82.4
110.5
135.7
134.0
59.4
90.2
121.0
148.6
146.8
64.5
98.0
131.5
161.5
159.5
103.8
139.3
165.8
163.0
109.6
147.0
170.0
166.4

55.4
85.2
115.0
139.8
139.8
61.2
94.1
127.0
154.4
154.4
67.0
103.0
139.0
169.0
169.0
107.4
145.0
174.3
172.7
111.9
151.0
179.5
176.4

63.8
93.6
118.4
118.4
68.8
101.7
129.1
129.1
73.8
109.8
139.8
139.8
74.2
111.8
141.0
139.5
74.6
113.7
142.3
139.1

72.2
97.1
97.1
76.5
103.9
103.9
80.7
110.7
110.7
78.6
107.8
106.3
76.5
105.0
101.9

75.7
75.7
78.6
78.6
81.5
81.5
74.6
73.1
67.7
64.6

198.8
182.7
166.5
155.6
152.2
203.9
187.3
170.8
159.5
156.1
209.0
192.0
175.0
163.5
160.0
195.8
178.5
166.8
163.2
199.7
182.0
170.0
166.4

16.1
15.4
14.8
14.7
15.0
16.2
15.5
14.8
14.8
15.1
16.3
15.6
14.9
14.9
15.2
15.7
15.0
15.0
15.3
15.9
15.2
15.1
15.5

97.0
125.1
153.3
155.6
152.2
117.3
140.7
164.1
159.5
156.1
137.6
156.3
175.0
163.5
160.0
170.2
178.5
166.8
163.2
184.1
182.0
170.0
166.4

75

70

61.0
89.1
67.7
114.3 93.0
112.6 91.3
64.9
95.7
70.5
123.3 98.1
121.5 96.2
68.8
102.3 73.2
132.3 103.2
130.3 101.2
70.6
106.0 72.8
132.6 99.4
129.7 96.5
72.3
109.7 72.5
132.8 95.5
129.1 91.9

65
71.6
69.9
72.8
70.9
74.0
72.0
66.1
63.3
58.3
54.6

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 4: DH 180 COOLING CAPACITIES (15 TON) (CONTINUED)
AIR ON
EVAPORATOR
COIL
CFM

4500

5250

6000

6750

7500

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

TEMPERATURE OF AIR ON CONDENSER COIL
115°F
SENSIBLE CAPACITY, MBH
TOTAL POWER
ENTERING DRY BULB, °F
INPUT2
CAP.1
MBH
KW
90
85
80
75
70
184.5
170.3
156.0
146.5
142.7
189.3
174.6
160.0
150.2
146.3
194.0
179.0
164.0
154.0
150.0
182.8
167.5
157.3
153.2
186.6
171.0
160.6
156.4

17.8
16.9
16.0
16.1
16.4
17.9
17.0
16.1
16.2
16.5
18.0
17.1
16.2
16.3
16.6
17.2
16.3
16.4
16.7
17.3
16.4
16.5
16.8

95.8
122.3
148.8
146.5
142.7
117.2
136.8
156.4
150.2
146.3
138.6
151.3
164.0
154.0
150.0
166.5
167.5
157.3
153.2
181.8
171.0
160.6
156.4

74.4
100.9
127.4
146.5
142.7
82.8
111.5
140.3
150.2
146.3
91.2
122.2
153.2
154.0
150.0
133.3
162.1
157.3
153.2
144.5
171.0
160.6
156.4

53.0
79.5
106.0
131.6
128.2
57.5
86.3
115.0
142.8
139.1
62.0
93.0
124.0
154.0
150.0
100.1
133.5
157.3
153.2
107.3
143.0
160.6
156.4

58.1
84.6
110.3
106.8
61.0
89.7
117.6
113.8
63.8
94.8
124.8
120.8
66.9
100.3
124.1
120.0
70.0
105.7
123.3
119.1

63.2
88.9
85.5
64.5
92.3
88.6
65.7
95.7
91.7
67.1
90.9
86.8
68.5
86.1
81.9

65
67.5
64.1
67.0
63.3
66.5
62.5
57.7
53.6
48.8
44.6

1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating

Johnson Controls Unitary Products

11

262260-YTG-E-1008

TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON)
AIR ON
EVAPORATOR
COIL
CFM

5250

6125

7000

7875

8750

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

AIR ON
EVAPORATOR
COIL
CFM

5250

6125

7000

7875

8750

12

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

241.5
232.2
223.0
204.4
200.4
250.1
240.5
231.0
211.7
207.6
258.7
248.8
238.9
219.0
214.7
253.0
243.0
222.7
218.3
257.2
247.0
226.4
222.0

13.9
13.2
12.6
12.4
12.6
14.5
13.8
13.1
12.9
13.1
15.1
14.4
13.7
13.5
13.7
14.5
13.8
13.6
13.8
14.6
13.9
13.7
13.9

119.5
159.7
199.9
204.4
200.4
136.3
177.8
219.4
211.7
207.6
153.0
195.9
238.9
219.0
214.7
214.9
243.0
222.7
218.3
233.8
247.0
226.4
222.0

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

238.9
219.9
201.0
182.6
182.0
247.5
235.0
215.5
195.8
195.1
256.1
235.8
215.5
195.8
195.1
240.9
220.2
200.0
199.3
246.0
224.8
204.2
203.5

17.4
16.9
16.5
16.3
16.1
17.6
17.2
16.7
16.5
16.3
17.7
17.2
16.7
16.5
16.3
17.3
16.8
16.6
16.4
17.4
16.9
16.7
16.5

120.0
152.9
185.9
182.6
182.0
144.4
172.5
200.7
189.2
188.5
168.8
192.1
215.5
195.8
195.1
210.4
220.2
200.0
199.3
228.7
224.8
204.2
203.5

TEMPERATURE OF AIR ON CONDENSER COIL
75°F
SENSIBLE CAPACITY, MBH
TOTAL
POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

75

70

65

94.6
134.8
174.9
204.4
200.4
104.8
148.3
191.9
211.7
207.6
115.0
161.9
208.8
219.0
214.7
176.1
227.9
222.7
218.3
190.3
247.0
226.4
222.0

94.8
131.4
167.9
193.5
191.2
105.8
145.7
185.6
200.5
198.0
116.7
160.0
203.3
207.4
204.9
173.9
219.6
211.4
208.8
187.8
235.9
215.3
212.7

69.9
106.4
143.0
170.5
171.8
76.3
116.2
156.2
186.1
187.6
82.7
126.0
169.3
201.8
203.4
135.2
181.6
208.6
208.1
144.3
193.9
215.3
212.7

81.5
118.1
145.5
146.9
86.7
126.7
156.6
158.1
92.0
135.3
167.8
169.4
96.4
142.9
169.8
169.3
100.8
150.4
171.9
169.3

93.1
120.6
121.9
97.2
127.2
128.6
101.3
133.8
135.4
104.1
131.1
130.6
107.0
128.4
125.8

95.6
97.0
97.7
99.1
99.7
101.3
92.3
91.8
84.9
82.3

69.6
109.8
150.0
182.1
183.1
75.3
118.9
162.4
197.2
198.3
81.0
127.9
174.8
212.3
213.5
137.4
187.8
219.4
217.7
146.9
200.7
226.4
222.0

84.9
125.1
157.1
158.2
89.4
132.9
167.7
168.8
93.9
140.8
178.3
179.5
98.6
149.0
180.6
179.0
103.4
157.2
183.0
178.5

100.1
132.2
133.2
103.4
138.2
139.3
106.8
144.3
145.5
110.3
141.9
140.2
113.8
139.5
135.0

107.2
108.3
108.7
109.9
110.2
111.4
103.1
101.5
96.0
91.6

240.2
226.1
212.0
193.5
191.2
248.8
234.2
219.6
200.5
198.0
257.4
242.3
227.2
207.4
204.9
246.9
231.6
211.4
208.8
251.6
235.9
215.3
212.7

15.6
15.1
14.5
14.3
14.3
16.0
15.4
14.9
14.7
14.7
16.4
15.8
15.2
15.0
15.0
15.9
15.3
15.1
15.1
16.0
15.4
15.2
15.2

119.7
156.3
192.9
193.5
191.2
140.3
175.2
210.0
200.5
198.0
160.9
194.0
227.2
207.4
204.9
212.6
231.6
211.4
208.8
231.2
235.9
215.3
212.7

TEMPERATURE OF AIR ON CONDENSER COIL
95°F
SENSIBLE CAPACITY, MBH
TOTAL
POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

75

70

65

95.0
128.0
160.9
182.6
182.0
106.7
143.1
179.4
189.2
188.5
118.4
158.1
197.8
195.8
195.1
171.7
211.3
200.0
199.3
185.2
224.8
204.2
203.5

91.2
123.0
154.8
176.2
176.4
102.8
138.0
173.3
181.8
182.1
114.4
153.1
191.7
187.5
187.8
166.5
202.2
191.6
191.9
180.0
212.8
195.7
196.0

66.2
98.1
129.9
152.7
153.3
73.3
108.6
143.8
169.1
169.7
80.4
119.1
157.7
185.5
186.1
127.8
169.3
190.6
191.0
136.5
180.9
195.7
196.0

73.1
105.0
127.8
128.3
79.1
114.3
139.6
140.2
85.0
123.7
151.4
152.0
89.0
130.5
151.8
152.3
93.1
137.4
152.2
152.5

80.0
102.9
103.4
84.8
110.1
110.7
89.7
117.4
118.0
91.8
113.1
113.5
93.9
108.7
109.1

77.9
78.4
80.6
81.2
83.4
84.0
74.3
74.8
65.3
65.6

70.1
103.0
136.0
158.8
160.5
77.2
124.0
163.8
191.3
193.3
84.4
124.1
163.8
191.3
193.3
132.9
175.5
197.8
198.4
141.8
187.1
204.2
203.5

78.1
111.1
133.9
135.5
84.1
120.4
145.6
147.4
90.1
129.8
157.3
159.3
94.2
136.7
159.0
159.7
98.3
143.6
160.8
160.0

86.1
108.9
110.6
90.9
116.1
117.9
95.8
123.3
125.3
98.0
120.3
120.9
100.2
117.3
116.6

84.0
85.6
86.6
88.4
89.2
91.2
81.5
82.2
73.8
73.1

228.3
209.9
191.5
176.2
176.4
235.7
223.4
203.8
187.4
187.8
243.0
223.4
203.8
187.5
187.8
228.3
208.3
191.6
191.9
233.2
212.8
195.7
196.0

15.0
14.6
14.2
14.0
13.9
17.2
19.0
18.5
18.2
18.1
19.5
19.0
18.5
18.2
18.1
19.1
18.6
18.3
18.2
19.2
18.7
18.4
18.3

116.1
148.0
179.8
176.2
176.4
143.3
167.5
191.8
181.8
182.1
170.4
187.1
203.8
187.5
187.8
205.3
208.3
191.6
191.9
223.5
212.8
195.7
196.0

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON) (CONTINUED)
AIR ON
EVAPORATOR
COIL
CFM

5250

6125

7000

7875

8750

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

217.8
199.9
182.0
169.7
170.9
223.9
205.5
187.1
174.4
175.7
229.9
211.0
192.1
179.1
180.4
215.7
196.4
183.1
184.4
220.4
200.7
187.1
188.5

12.5
12.2
12.0
11.8
11.8
16.9
16.5
16.1
15.8
15.8
21.2
20.7
20.2
19.9
19.9
20.8
20.3
20.0
20.0
20.9
20.4
20.1
20.1

112.3
143.0
173.7
169.7
170.9
142.1
162.5
182.9
174.4
175.7
172.0
182.0
192.1
179.1
180.4
200.1
196.4
183.1
184.4
218.2
200.7
187.1
188.5

TEMPERATURE OF AIR ON CONDENSER COIL
115°F
SENSIBLE CAPACITY, MBH
TOTAL POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

125°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

87.3
62.4
118.0 93.1
68.1
148.7 123.8 98.9
73.9
169.7 146.7 121.7 96.8
170.9 146.0 121.1 96.1
98.9
69.4
133.0 103.5 74.1
167.2 137.7 108.2 78.7
174.4 163.1 133.6 104.2
175.7 162.4 132.9 103.4
110.4 76.4
148.0 114.0 80.0
185.6 151.6 117.6 83.6
179.1 179.6 145.6 111.6
180.4 178.8 144.8 110.8
161.4 122.6 83.9
193.2 163.1 124.4 85.6
183.1 183.4 144.6 105.9
184.4 183.6 144.9 106.1
174.8 131.3 87.8
200.7 174.6 131.1 87.7
187.1 187.1 143.6 100.2
188.5 188.5 145.0 101.5

83.5
113.1
142.6
163.2
165.4
95.0
128.0
161.1
167.0
169.2
106.4
143.0
179.5
170.8
173.1
156.3
184.1
174.7
177.0
169.5
188.7
178.6
181.0

58.5
88.1
117.7
140.6
138.8
65.5
98.5
131.6
157.2
155.2
72.4
109.0
145.5
170.8
171.6
117.5
156.9
174.7
176.3
126.1
168.4
178.6
181.0

71.8
71.2
74.7
74.0
77.5
76.7
67.1
67.4
56.7
58.1

207.3
189.9
172.5
163.2
165.4
212.0
194.2
176.5
167.0
169.2
216.8
198.6
180.4
170.8
173.1
203.1
184.5
174.7
177.0
207.7
188.7
178.6
181.0

10.1
9.9
9.7
9.5
9.6
16.5
16.2
15.8
15.6
15.7
23.0
22.5
22.0
21.6
21.7
22.6
22.1
21.7
21.8
22.7
22.2
21.8
21.9

108.4
138.0
167.6
163.2
165.4
141.0
157.5
174.0
167.0
169.2
173.6
177.0
180.4
170.8
173.1
195.0
184.5
174.7
177.0
207.7
188.7
178.6
181.0

75

70

63.2
92.8
67.8
115.6 90.7
113.8 88.9
69.1
102.1 72.6
127.7 98.2
125.7 96.2
74.9
111.5 77.5
139.7 105.7
137.5 103.5
78.8
118.2 79.4
137.4 98.7
137.5 98.8
82.6
124.9 81.4
135.1 91.6
137.5 94.0

65
65.7
63.9
68.7
66.7
71.7
69.5
59.9
60.0
48.1
50.5

1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance
Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating

Johnson Controls Unitary Products

13

262260-YTG-E-1008

TABLE 6: DH 240 COOLING CAPACITIES (20 TON)
AIR ON
EVAPORATOR
COIL
CFM

6000

7000

8000

9000

10000

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

AIR ON
EVAPORATOR
COIL
CFM

6000

7000

8000

9000

10000

14

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

277.0
263.0
249.0
240.6
237.8
287.0
272.5
258.0
249.3
246.4
297.0
282.0
267.0
258.0
255.0
295.2
279.5
270.1
266.9
308.4
292.0
282.2
278.9

19.1
18.6
18.0
17.9
17.7
17.9
17.4
16.9
16.7
16.5
16.7
16.2
15.7
15.6
15.4
13.7
13.3
13.2
13.0
11.2
10.8
10.7
10.6

159.2
196.1
233.0
240.6
237.8
189.9
219.9
250.0
249.3
246.4
220.5
243.8
267.0
258.0
255.0
275.1
279.5
270.1
266.9
306.4
292.0
282.2
278.9

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

247.1
235.0
223.0
216.5
215.6
257.0
244.5
236.0
225.3
224.3
267.0
254.0
241.0
234.0
233.0
266.1
252.5
245.2
244.1
278.2
264.0
256.3
255.2

21.9
21.5
21.2
20.9
20.6
20.8
20.5
20.1
19.8
19.6
19.7
19.4
19.1
18.8
18.6
16.9
16.7
16.4
16.2
14.4
14.2
14.0
13.8

148.1
184.6
221.0
216.5
215.6
185.3
208.2
231.0
225.3
224.3
222.5
231.8
241.0
234.0
233.0
255.0
252.5
245.2
244.1
278.2
264.0
256.3
255.2

TEMPERATURE OF AIR ON CONDENSER COIL
75°F
SENSIBLE CAPACITY, MBH
TOTAL
POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

75

70

65

130.7
167.6
204.5
240.6
237.8
145.8
186.3
226.7
249.3
246.4
160.9
204.9
248.9
258.0
255.0
228.1
270.4
270.1
266.9
251.2
292.0
282.2
278.9

125.2
161.8
198.5
228.6
226.7
140.0
180.4
220.7
237.3
235.4
154.9
198.9
242.9
246.0
244.0
220.8
260.4
257.6
255.5
242.6
278.0
269.2
267.1

96.7
133.3
170.0
204.2
203.3
106.3
146.7
187.0
224.6
223.7
116.0
160.0
204.0
245.0
244.0
176.5
225.0
257.1
255.5
192.9
246.0
269.2
267.1

104.8
141.5
175.7
174.8
113.0
153.3
190.9
190.0
121.1
165.1
206.1
205.1
132.2
180.7
212.8
211.2
143.3
196.3
219.6
217.4

113.0
147.1
146.3
119.6
157.2
156.3
126.2
167.2
166.2
136.4
168.6
167.0
146.6
169.9
167.7

118.6
117.8
123.5
122.6
128.4
127.4
124.3
122.7
120.2
118.0

102.2
139.1
176.0
215.3
213.7
112.1
152.6
193.0
236.2
234.3
122.0
166.0
210.0
257.0
255.0
183.8
232.5
269.6
266.9
201.5
255.0
282.2
278.9

110.6
147.5
186.8
185.2
118.9
159.3
202.5
200.6
127.1
171.1
218.1
216.1
139.5
188.2
225.3
222.7
151.9
205.3
232.5
229.2

119.0
158.3
156.7
125.6
168.8
166.9
132.2
179.2
177.2
143.9
181.0
178.4
155.6
182.8
179.5

129.8
128.1
135.1
133.3
140.4
138.4
136.7
134.1
133.1
129.8

262.0
249.0
236.0
228.6
226.7
272.0
258.5
245.0
237.3
235.4
282.0
268.0
254.0
246.0
244.0
280.7
266.0
257.6
255.5
293.3
278.0
269.2
267.1

20.5
20.1
19.6
19.4
19.1
19.4
18.9
18.5
18.3
18.1
18.2
17.8
17.4
17.2
17.0
15.3
15.0
14.8
14.6
12.8
12.5
12.4
12.2

153.7
190.4
227.0
228.6
226.7
187.6
214.1
240.5
237.3
235.4
221.5
237.8
254.0
246.0
244.0
265.0
266.0
257.6
255.5
292.3
278.0
269.2
267.1

TEMPERATURE OF AIR ON CONDENSER COIL
95°F
SENSIBLE CAPACITY, MBH
TOTAL
POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

75

70

65

119.6
156.1
192.5
216.5
215.6
134.3
174.5
214.7
225.3
224.3
148.9
192.9
236.9
234.0
233.0
213.4
250.4
245.2
244.1
234.0
264.0
256.3
255.2

115.5
151.5
187.5
205.4
204.0
132.6
169.4
206.2
213.7
212.2
149.8
187.4
224.9
222.0
220.5
208.0
237.5
233.3
231.7
228.5
250.0
244.5
242.8

87.0
123.0
159.0
183.0
182.6
96.0
135.7
175.5
202.0
201.6
105.0
148.5
192.0
221.0
220.5
163.7
211.6
232.8
231.7
178.9
231.3
244.5
242.8

94.5
130.5
154.5
154.1
102.0
141.8
168.3
167.9
109.6
153.1
182.1
181.6
119.4
167.3
188.5
187.4
129.2
181.6
194.8
193.2

102.0
126.0
125.6
108.1
134.6
134.2
114.2
143.2
142.7
123.1
144.2
143.1
131.9
145.1
143.5

97.5
97.1
100.9
100.5
104.4
103.9
99.9
98.8
95.5
93.8

91.1
127.6
164.0
193.0
193.0
100.6
140.8
182.0
213.0
213.0
110.0
154.0
198.0
233.0
233.0
169.2
217.5
244.7
244.1
184.3
237.0
256.3
255.2

99.0
135.5
164.5
164.5
107.1
147.3
179.3
179.3
115.1
159.1
194.1
194.1
124.9
173.2
200.4
199.8
134.7
187.3
206.7
205.6

107.0
136.0
136.0
113.6
145.6
145.6
120.2
155.2
155.2
128.9
156.1
155.6
137.6
157.0
155.9

107.5
107.5
111.9
111.9
116.4
116.4
111.8
111.3
107.3
106.2

232.2
221.1
210.0
205.4
204.0
241.6
230.1
218.5
213.7
212.2
251.0
239.0
227.0
222.0
220.5
251.1
238.5
233.3
231.7
263.2
250.0
244.5
242.8

23.3
22.9
22.6
22.2
21.9
22.3
21.9
21.6
21.2
21.0
21.3
20.9
20.6
20.2
20.0
18.4
18.1
17.8
17.6
16.0
15.7
15.4
15.3

144.0
180.0
209.0
205.4
204.0
184.7
203.1
218.0
213.7
212.2
225.5
226.3
227.0
222.0
220.5
244.7
238.5
233.3
231.7
263.2
250.0
244.5
242.8

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 6: DH 240 COOLING CAPACITIES (20 TON) (CONTINUED)
AIR ON
EVAPORATOR
COIL
CFM

6000

7000

8000

9000

10000

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

TEMPERATURE OF AIR ON CONDENSER COIL
115°F
SENSIBLE CAPACITY, MBH
TOTAL POWER
ENTERING DRY BULB, °F
INPUT2
CAP.1
MBH
KW
90
85
80
75
70
217.3
207.2
197.0
194.2
192.4
226.2
215.6
205.0
202.1
200.2
235.0
224.0
213.0
210.0
208.0
236.1
224.5
221.3
219.2
248.2
236.0
232.7
230.5

24.8
24.3
23.9
23.5
23.2
23.8
23.4
23.0
22.5
22.3
22.8
22.4
22.0
21.6
21.4
20.0
19.6
19.2
19.1
17.5
17.2
16.9
16.7

139.8
175.4
197.0
194.2
192.4
184.2
198.1
205.0
202.1
200.2
228.5
220.8
213.0
210.0
208.0
234.5
224.5
221.3
219.2
248.2
236.0
232.7
230.5

111.3
146.9
182.5
194.2
192.4
131.0
164.4
197.8
202.1
200.2
150.8
181.9
213.0
210.0
208.0
202.5
224.5
221.3
219.2
223.0
236.0
232.7
230.5

82.8
118.4
154.0
173.0
172.2
91.4
130.7
170.0
191.0
190.1
100.0
143.0
186.0
209.0
208.0
158.2
205.8
220.8
219.2
173.4
225.5
232.7
230.5

89.9
125.5
144.5
143.7
97.0
136.3
157.3
156.4
104.1
147.1
170.1
169.1
113.9
161.5
176.6
175.0
123.7
175.8
183.0
180.8

97.0
116.0
115.2
102.6
123.6
122.7
108.2
131.2
130.2
117.2
132.3
130.7
126.1
133.3
131.1

65
87.5
86.7
89.9
89.0
92.4
91.4
88.0
86.4
83.6
81.4

1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating

Johnson Controls Unitary Products

15

262260-YTG-E-1008

TABLE 7: DH 300 COOLING CAPACITIES (25 TON)
AIR ON
EVAPORATOR
COIL
CFM

7500

8750

10000

11250

12500

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

AIR ON
EVAPORATOR
COIL
CFM

7500

8750

10000

11250

12500

16

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

371.3
334.4
297.6
290.9
281.0
373.9
336.8
299.7
293.0
282.9
376.6
339.1
301.7
295.0
284.9
341.5
303.7
297.0
286.8
343.8
305.7
299.1
288.7

19.7
19.3
18.8
18.3
18.2
19.7
19.3
18.9
18.3
18.2
19.8
19.3
18.9
18.4
18.3
20.3
19.8
19.3
19.2
21.3
20.8
20.2
20.1

191.8
233.0
274.2
290.9
281.0
219.7
253.8
288.0
293.0
282.9
247.6
274.6
301.7
295.0
284.9
290.9
303.7
297.0
286.8
307.1
305.7
299.1
288.7

TOTAL
CAP.1
MBH

POWER
INPUT2
KW

90

326.6
302.9
279.2
264.2
263.7
332.8
308.6
284.4
269.2
268.7
338.9
314.3
289.7
274.2
273.7
320.0
294.9
279.2
278.6
325.7
300.2
284.1
283.6

23.2
23.0
22.8
22.0
22.0
23.5
23.3
23.1
22.3
22.3
23.8
23.6
23.4
22.6
22.6
24.1
23.9
23.0
23.0
24.6
24.3
23.5
23.5

179.1
220.1
261.1
264.2
263.7
208.2
241.8
275.4
269.2
268.7
237.3
263.5
289.7
274.2
273.7
285.6
294.9
279.2
278.6
307.8
300.2
284.1
283.6

TEMPERATURE OF AIR ON CONDENSER COIL
75°F
SENSIBLE CAPACITY, MBH
TOTAL
POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

75

70

65

156.2
197.4
238.6
284.9
281.0
168.5
211.7
254.9
290.0
282.9
180.9
226.0
271.2
295.0
284.9
235.5
281.3
297.0
286.8
245.0
291.5
299.1
288.7

149.8
190.9
232.0
274.6
272.4
162.4
205.7
249.0
279.6
275.8
175.0
220.4
265.9
284.6
279.3
232.9
279.9
288.1
282.7
245.4
293.9
291.6
286.1

114.2
155.3
196.4
238.9
249.6
120.3
163.6
206.9
251.7
262.9
126.4
171.8
217.3
264.4
276.2
177.6
224.5
273.2
281.2
183.3
231.8
282.0
286.1

119.7
160.8
203.3
214.0
121.5
164.7
209.5
220.8
123.2
168.7
215.8
227.6
122.2
169.2
217.8
225.8
121.2
169.7
219.9
224.0

125.1
167.7
178.3
122.6
167.4
178.7
120.1
167.2
179.0
113.8
162.5
170.5
107.6
157.8
161.9

132.0
142.7
125.3
136.5
118.6
130.4
107.1
115.1
95.7
99.8

120.6
161.8
203.0
246.4
261.8
126.4
169.6
212.8
258.3
274.5
132.3
177.4
222.6
270.2
287.2
180.2
226.0
275.0
287.9
182.9
229.4
279.8
288.7

126.1
167.3
210.8
226.1
127.5
170.7
216.2
232.4
128.8
174.0
221.6
238.6
124.8
170.6
219.7
232.6
120.8
167.3
217.7
226.6

131.7
175.1
190.5
128.5
174.1
190.3
125.4
173.0
190.0
115.3
164.3
177.2
105.2
155.6
164.5

139.5
154.9
132.0
148.1
124.4
141.4
109.0
121.9
93.5
102.4

348.9
318.7
288.4
277.6
272.4
353.3
322.7
292.0
281.1
275.8
357.7
326.7
295.7
284.6
279.3
330.7
299.3
288.1
282.7
334.8
303.0
291.6
286.1

21.5
21.1
20.8
20.1
20.1
21.6
21.3
21.0
20.3
20.3
21.8
21.5
21.1
20.5
20.4
22.2
21.8
21.2
21.1
22.9
22.6
21.8
21.8

185.5
226.6
267.7
277.6
272.4
214.0
247.8
281.7
281.1
275.8
242.4
269.0
295.7
284.6
279.3
288.3
299.3
288.1
282.7
307.5
303.0
291.6
286.1

TEMPERATURE OF AIR ON CONDENSER COIL
95°F
SENSIBLE CAPACITY, MBH
TOTAL
POWER
ENTERING DRY BULB, °F
CAP.1
INPUT2
MBH
KW
85
80
75
70
65
90

105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
85

80

75

70

65

143.5
184.5
225.5
264.2
263.7
156.3
199.7
243.0
269.2
268.7
169.1
214.9
260.6
274.2
273.7
230.3
278.4
279.2
278.6
245.7
296.2
284.1
283.6

127.7
173.5
219.4
253.6
251.0
139.8
188.5
237.2
257.8
255.2
151.9
203.4
254.9
261.9
259.3
215.9
266.7
266.1
263.4
228.4
278.5
270.3
267.6

92.0
137.9
183.7
225.7
222.7
97.6
146.3
195.0
239.6
236.4
103.3
154.8
206.3
253.5
250.0
160.6
213.9
261.9
257.0
166.3
221.4
270.3
263.9

102.2
148.1
190.1
187.1
104.2
152.9
197.5
194.2
106.2
157.7
204.9
201.4
105.2
158.5
206.5
201.6
104.2
159.3
208.2
201.8

112.5
154.5
151.4
110.8
155.4
152.1
109.1
156.3
152.8
103.2
151.2
146.3
97.2
146.1
139.7

118.8
115.8
113.3
110.0
107.7
104.2
95.8
90.9
84.0
77.6

107.9
148.8
189.8
231.5
237.4
114.2
157.5
200.9
245.0
251.3
120.5
166.3
212.0
258.6
265.2
174.9
223.1
271.4
274.4
183.6
234.1
284.1
283.6

113.2
154.2
195.8
201.8
115.4
158.8
202.9
209.2
117.7
163.4
210.0
216.6
119.6
167.7
216.0
219.0
121.5
172.0
222.0
221.5

118.5
160.2
166.1
116.7
160.8
167.1
114.8
161.4
168.0
112.4
160.7
163.7
109.9
159.9
159.4

124.6
130.5
118.7
124.9
112.8
119.4
105.3
108.3
97.8
97.3

314.3
288.7
263.1
253.6
251.0
319.5
293.5
267.5
257.8
255.2
324.6
298.2
271.8
261.9
259.3
303.0
276.2
266.1
263.4
307.8
280.5
270.3
267.6

26.2
25.8
25.3
24.5
24.6
26.4
25.9
25.4
24.7
24.8
26.6
26.1
25.6
24.9
24.9
26.5
26.0
25.2
25.3
26.8
26.3
25.6
25.6

163.3
209.2
254.1
253.6
251.0
197.7
230.6
263.0
257.8
255.2
232.2
252.0
271.8
261.9
259.3
271.3
276.2
266.1
263.4
290.5
280.5
270.3
267.6

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 7: DH 300 COOLING CAPACITIES (25 TON) (CONTINUED)
AIR ON
EVAPORATOR
COIL
CFM

7500

8750

10000

11250

12500

WB
°F
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

TEMPERATURE OF AIR ON CONDENSER COIL
115°F
SENSIBLE CAPACITY, MBH
TOTAL POWER
ENTERING DRY BULB, °F
INPUT2
CAP.1
MBH
KW
90
85
80
75
70
302.0
274.5
247.1
242.9
238.3
306.2
278.4
250.5
246.3
241.6
310.4
282.2
254.0
249.7
244.9
286.0
257.4
253.1
248.2
289.8
260.9
256.4
251.5

29.3
28.5
27.7
27.1
27.2
29.3
28.5
27.8
27.1
27.3
29.4
28.6
27.8
27.2
27.3
28.9
28.1
27.4
27.6
29.1
28.3
27.7
27.8

147.5
198.2
247.1
242.9
238.3
187.3
219.4
250.5
246.3
241.6
227.1
240.5
254.0
249.7
244.9
256.9
257.4
253.1
248.2
273.3
260.9
256.4
251.5

111.8
162.6
213.3
242.9
238.3
123.2
177.3
231.3
246.3
241.6
134.6
191.9
249.2
249.7
244.9
201.6
255.1
253.1
248.2
211.2
260.9
256.4
251.5

76.2
126.9
177.7
220.0
208.0
81.1
135.1
189.2
234.2
221.4
86.0
143.3
200.6
248.4
234.9
146.2
204.7
252.4
239.6
149.1
208.7
256.4
244.3

91.3
142.0
184.3
172.3
93.0
147.0
192.1
179.3
94.7
152.0
199.8
186.3
90.9
149.3
197.1
184.2
87.0
146.6
194.3
182.2

106.4
148.7
136.7
104.9
150.0
137.2
103.4
151.2
137.7
94.0
141.7
128.9
84.5
132.2
120.1

65
113.1
101.1
107.8
95.1
102.6
89.1
86.4
73.5
70.1
58.0

1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.1 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating

Johnson Controls Unitary Products

17

262260-YTG-E-1008

CFM, STATIC PRESSURE, AND POWER - ALTITUDE AND TEMPERATURE CORRECTIONS

order to use the indoor blower tables for high altitude applications, certain corrections are necessary.

The information below should be used to assist in application
of product when being applied at altitudes at or exceeding
1000 feet above sea level.

A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
generated and less power will be required than a similar
application at sea level. Air density correction factors are
shown in Table 8 and Figure 2.

The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude
or temperature increases, the density of air decreases. In

TABLE 8: ALTITUDE CORRECTION FACTORS
AIR TEMP
40
50
60
70
80
90
100

0
1.060
1.039
1.019
1.000
0.982
0.964
0.946

1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912

2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880

3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848

ALTITUDE (FEET)
4000
5000
0.916
0.882
0.898
0.864
0.880
0.848
0.864
0.832
0.848
0.817
0.833
0.802
0.817
0.787

6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758

7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730

8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703

9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676

10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651

The examples below will assist in determining the airflow performance of the product at altitude.

blower tables to select the blower speed and the BHP
requirement.

Example 1: What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower performance
data is 6,000 CFM, 1.5 IWC and 4.0 BHP?

Solution: As in the example above, no temperature information is given so 70°F is assumed.

Solution: At an elevation of 5,000 ft the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, Table
8 must be used to determine the static pressure and BHP.
Since no temperature data is given, we will assume an air
temperature of 70°F. Table 8 shows the correction factor to be
0.832.

The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.

Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to
deliver 6,000 CFM at a static pressure of 1.5". Use the unit

18

Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
BHP at 5,000 ft = 3.2 x .832 = 2.66

Johnson Controls Unitary Products

262260-YTG-E-1008

	

  

	  	






 









	







 






FIGURE 2 -

	





	 	 







ALTITUDE/TEMPERATURE CONVERSION FACTOR

Johnson Controls Unitary Products

19

262260-YTG-E-1008

TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY
180 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)

MOTOR
PULLEY
(TURNS
OPEN)*

CFM
4500
ESP

BHP

5250
KW

ESP

BHP

6000
KW

ESP

BHP

6750
KW

ESP

BHP

7200
KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE
850

6.0**

0.9

2.4

2.2

0.7

3.0

2.7

0.5

3.2

2.9

-

-

-

-

-

-

870

5.5

1.0

2.5

2.3

0.8

3.1

2.8

0.6

3.5

3.1

0.2

4.1

3.7

-

-

-

915

4.5

1.1

2.6

2.4

0.9

3.4

3.0

0.7

3.7

3.3

0.3

4.4

3.9

0.2

4.5

4.0

965

3.5

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

4.9

4.4

980

3.0

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8.

4.3

0.5

5.1

4.6

1010

2.0

1.4

3.1

2.8

1.2

3.8

3.4

1.0

4.2

3.8

0.7

5.0

4.5

0.6

5.4

4.8

1040

1.0

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.2

4.7

0.7

5.7

5.1
4.4

208 VOLT AND HIGH STATIC DRIVE
965

6.0

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

5.0

980

5.5

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1025

4.5

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.8

5.1

4.6

0.7

5.6

5.0

1065

3.5

1.6

3.4

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

1095

3.0

1.7

3.5

3.1

1.5

4.2

3.8

1.3

4.9

4.4

1.2

5.7

5.1

-

-

-

1130

2.0

1.9

3.7

3.3

1.7

4.5

4.0

1.5

5.1

4.6

-

-

-

-

-

-

1170

1.0

2.1

3.9

3.5

2.0

4.7

4.2

1.8

5.5

4.9

-

-

-

-

-

-

230/460/575 VOLT AND STANDARD DRIVE
870

6.0**

1.0

2.4

2.2

0.8

3.1

2.8

0.6

3.5

3.1

0.2

4.1

3.7

-

-

-

915

5.0

1.1

2.6

2.4

0.9

3.3

3.0

0.7

3.7

3.3

0.3

4.4

3.9

0.2

4.5

4.0

965

4.0

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

5.0

4.4

980

3.5

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1040

2.0

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.3

4.7

0.7

5.7

5.1

1065

1.0

1.6

3.3

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

230/460/575 VOLT AND HIGH STATIC DRIVE
980

6.0

1.3

2.9

2.6

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1040

4.5

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.3

4.7

0.7

5.7

5.1

1065

4.0

1.6

3.4

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

1095

3.5

1.7

3.5

3.1

1.5

4.2

3.8

1.3

4.9

4.4

1.2

5.7

5.1

-

-

-

1130

2.5

1.9

3.7

3.3

1.7

4.5

4.0

1.5

5.1

4.6

-

-

-

-

-

-

1170

1.5

2.1

3.9

3.5

2.0

4.7

4.2

1.8

5.5

4.9

-

-

-

-

-

-

1190

1.0

2.2

4.0

3.6

2.1

4.8

4.3

2.0

5.7

5.1

-

-

-

-

-

-

NOTES:

20

1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2. Refer to Table 11 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY
210 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)

MOTOR
PULLEY
(TURNS
OPEN)*

CFM
6000
ESP

7000

BHP

KW

ESP

BHP

8000
KW

ESP

BHP

9000
KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE
870

6.0**

0.4

2.1

1.8

0.1

2.3

2.0

-

-

-

-

-

-

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

-

-

-

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

950

3.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

980

2.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

1015

1.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5
5.0

208 VOLT AND HIGH STATIC DRIVE
950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

1010

4.0

1.8

5.8

4.9

1.7

6.3

5.3

1.5

6.9

5.8

1.0

7.5

6.3

1020

3.5

1.9

6.1

5.1

1.8

6.5

5.5

1.6

7.1

6.0

1.1

7.8

6.6

1035

3.0

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

1050

2.5

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

1075

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

1100

1.0

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

-

-

-

230/460/575 VOLT AND STANDARD DRIVE
870

6.0**

0.4

2.1

1.8

0.1

2.3

2.0

-

-

-

-

-

-

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

-

-

-

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

950

3.5

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

980

2.5

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

1015

1.5

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

1025

1.0

2.0

6.1

5.1

1.8

6.6

5.6

1.6

7.3

6.1

1.1

7.9

6.7
5.0

230/460/575 VOLT AND HIGH STATIC DRIVE
950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

1015

4.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

1035

3.5

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

1050

3.0

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

1080

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

1100

1.5

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

-

-

-

1120

1.0

2.5

6.8

5.7

2.3

7.4

6.2

2.2

8.1

6.8

-

-

-

NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 13 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.

Johnson Controls Unitary Products

21

262260-YTG-E-1008

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY
240 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)

MOTOR
PULLEY
(TURNS
OPEN)*

CFM
6000
ESP

7000

8000

BHP

KW

ESP

BHP

KW

ESP

BHP

9000

9400

KW

ESP

BHP

KW

ESP

BHP

KW
-

208 VOLT AND STANDARD DRIVE
870

6.0**

0.4

2.1

1.8

0.1

2.3

2.0

-

-

-

-

-

-

-

-

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

-

-

-

-

-

-

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

-

-

-

950

3.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

2.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

1.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

208 VOLT AND HIGH STATIC DRIVE
950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1010

4.0

1.8

5.8

4.9

1.7

6.3

5.3

1.5

6.9

5.8

1.0

7.5

6.3

0.5

7.9

6.7

1020

3.5

1.9

6.1

5.1

1.8

6.5

5.5

1.6

7.1

6.0

1.1

7.8

6.6

0.6

8.3

7.0

1035

3.0

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

0.7

8.6

7.3

1050

2.5

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

-

-

-

1075

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

-

-

-

1100

1.0

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

-

-

-

-

-

-

230/460/575 VOLT AND STANDARD DRIVE
870

6.0**

0.4

2.1

1.8

0.1

2.3

2.0

-

-

-

-

-

-

-

-

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

-

-

-

-

-

-

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

-

-

-

950

3.5

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

2.5

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

1.5

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

1025

1.0

2.0

6.1

5.1

1.8

6.6

5.6

1.6

7.3

6.1

1.1

7.9

6.7

0.7

8.6

7.3

230/460/575 VOLT AND HIGH STATIC DRIVE
950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

4.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

1035

3.5

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

0.7

8.6

7.3

1050

3.0

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

-

-

-

1080

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

-

-

-

1100

1.5

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

-

-

-

-

-

-

1120

1.0

2.5

6.8

5.7

2.3

7.4

6.2

2.2

8.1

6.8

-

-

-

-

-

-

NOTES:

22

1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2. Refer to Table 11 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT
180 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)

MOTOR
PULLEY
(TURNS
OPEN)*

CFM
4500
ESP

BHP

5250
KW

6000

6750

7200

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW
-

208 VOLT AND STANDARD DRIVE
850

6.0**

0.9

2.4

2.1

0.6

2.9

2.6

0.3

3.4

3.0

-

-

-

-

-

870

5.5

1.0

2.5

2.2

0.7

3.0

2.7

0.4

3.5

3.1

-

-

-

-

-

-

915

4.5

1.1

2.6

2.4

0.8

3.1

2.8

0.5

3.6

3.2

0.2

4.1

3.7

-

-

-

965

3.5

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.0

0.2

5.0

4.5

980

3.0

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1010

2.0

1.4

3.0

2.7

1.1

3.6

3.2

0.8

4.0

3.6

0.6

4.7

4.2

0.4

5.4

4.8

1040

1.0

1.6

3.2

2.9

1.3

3.8

3.4

1.0

4.4

3.9

0.8

5.0

4.5

0.6

5.6

5.0
4.5

208 VOLT AND HIGH STATIC DRIVE
965

6.0

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

980

5.5

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1025

4.5

1.4

3.1

2.8

1.2

3.6

3.2

0.9

4.1

3.7

0.7

4.8

4.3

0.4

5.5

4.9

1065

3.5

1.6

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

1125

2.0

1.9

3.6

3.2

1.7

4.4

3.9

1.4

5.0

4.5

1.2

5.8

5.2

-

-

-

1170

1.0

2.1

3.9

3.5

1.9

4.7

4.2

1.6

5.5

4.9

-

-

-

-

-

-

230/460/575 VOLT AND STANDARD DRIVE
870

6.0**

1.0

2.5

2.2

0.7

3.0

2.7

0.4

3.5

3.1

-

-

-

-

-

-

915

5.0

1.1

2.6

2.4

0.8

3.1

2.8

0.5

3.6

3.2

0.2

4.1

3.7

-

-

-

965

4.0

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

980

3.5

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1015

2.5

1.4

3.0

2.7

1.1

3.6

3.2

0.8

4.0

3.6

0.6

4.7

4.2

0.4

5.4

4.8

1050

1.5

1.5

3.1

2.8

1.2

3.7

3.3

0.9

4.2

3.8

0.7

4.9

4.4

0.5

5.7

5.1

1065

1.0

1.6

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

230/460/575 VOLT AND HIGH STATIC DRIVE
980

6.0

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1045

4.5

1.6

3.2

2.9

1.3

3.8

3.4

1.0

4.4

3.9

0.8

5.0

4.5

0.6

5.6

5.0

1065

4.0

1.7

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

1125

2.5

1.9

3.6

3.2

1.7

4.4

3.9

1.4

5.0

4.5

1.2

5.8

5.2

-

-

-

1170

1.5

2.1

3.9

3.5

1.8

4.7

4.2

1.6

5.5

4.9

-

-

-

-

-

-

1190

1.0

2.2

4.0

3.6

1.9

4.8

4.3

1.7

5.6

5.0

-

-

-

-

-

-

NOTES:

1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.

Johnson Controls Unitary Products

23

262260-YTG-E-1008

TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT
210 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)

MOTOR
PULLEY
(TURNS
OPEN)*

CFM
6000
ESP

7000

8000

9000

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW
-

208 VOLT AND STANDARD DRIVE
870

6.0**

1.3

3.6

3.0

0.7

4.3

3.7

0.2

5.1

4.3

-

-

900

5.0

1.4

3.8

3.2

0.9

4.7

4.0

0.4

5.6

4.7

-

-

-

930

4.0

1.6

4.1

3.4

1.1

5.0

4.2

0.6

5.9

5.0

0.1

6.7

5.7

950

3.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

980

2.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

995

1.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

1015

1.0

2.2

4.8

4.0

1.7

4.7

4.8

1.2

6.6

5.6

0.7

7.8

6.6

208 VOLT AND HIGH STATIC DRIVE
950

6.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

980

5.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

995

4.5

2.1

4.5

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

1025

3.5

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

1050

2.5

2.5

5.1

4.3

2.0

6.1

5.1

1.4

7.1

6.0

0.9

8.4

7.0

1065

2.0

2.6

5.3

4.4

2.1

6.3

5.3

1.5

7.3

6.2

1.0

8.6

7.2

1100

1.0

2.9

5.6

4.7

2.3

6.8

5.7

1.8

7.9

6.6

-

-

-

230/460/575 VOLT AND STANDARD DRIVE
870

6.0**

1.3

3.6

3.0

0.7

4.3

3.7

0.2

5.1

4.3

-

-

900

5.0

1.4

3.8

3.2

0.9

4.7

4.0

0.4

5.6

4.7

-

-

-

930

4.0

1.6

4.1

3.4

1.1

5.0

4.2

0.6

5.9

5.0

0.1

6.7

5.7

950

3.5

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

965

2.5

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

995

2.0

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

1015

1.5

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.6

7.8

6.6

1025

1.0

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

230/460/575 VOLT AND HIGH STATIC DRIVE
950

6.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

980

5.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

995

4.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

1015

4.0

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.6

7.8

6.6

1025

3.5

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

1050

3.0

2.5

5.1

4.3

2.0

6.1

5.1

1.4

7.1

6.0

0.9

8.4

7.0

1065

2.5

2.6

5.3

4.4

2.1

6.3

5.3

1.5

7.3

6.2

1.0

8.6

7.2

1100

1.5

2.9

5.6

4.7

2.3

6.8

4.7

1.8

7.9

6.6

-

-

-

1120

1.0

3.1

5.8

4.9

2.5

7.0

5.9

1.9

8.3

6.9

-

-

-

NOTES:

24

1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT
240 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)

MOTOR
PULLEY
(TURNS
OPEN)*

CFM
6000
ESP

BHP

7000
KW

8000

9000

9400

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW
-

208 VOLT AND STANDARD DRIVE
870

6.0**

1.3

3.6

3.0

0.7

4.3

3.7

0.2

5.1

4.3

-

-

-

-

-

900

5.0

1.4

3.8

3.2

0.9

4.7

4.0

0.4

5.6

4.7

-

-

-

-

-

-

930

4.0

1.6

4.1

3.4

1.1

5.0

4.2

0.6

5.9

5.0

0.1

6.7

5.7

-

-

-

950

3.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

-

-

-

980

2.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

1.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

1.0

2.2

4.8

4.0

1.7

4.7

4.8

1.2

6.6

5.6

0.7

7.8

6.6

-

-

-

208 VOLT AND HIGH STATIC DRIVE
950

6.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

-

-

-

980

5.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

4.5

2.1

4.5

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1025

3.5

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

-

-

-

1050

2.5

2.5

5.1

4.3

2.0

6.1

5.1

1.4

7.1

6.0

0.9

8.4

7.0

-

-

-

1065

2.0

2.6

5.3

4.4

2.1

6.3

5.3

1.5

7.3

6.2

1.0

8.6

7.2

-

-

-

1100

1.0

2.9

5.6

4.7

2.3

6.8

5.7

1.8

7.9

6.6

-

-

-

-

-

-

230/460/575 VOLT AND STANDARD DRIVE
870

6.0**

1.3

3.6

3.0

0.7

4.3

3.7

0.2

5.1

4.3

-

-

-

-

-

900

5.0

1.4

3.8

3.2

0.9

4.7

4.0

0.4

5.6

4.7

-

-

-

-

-

-

930

4.0

1.6

4.1

3.4

1.1

5.0

4.2

0.6

5.9

5.0

0.1

6.7

5.7

-

-

-

950

3.5

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

-

-

-

965

2.5

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

2.0

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

1.5

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.6

7.8

6.6

-

-

-

1025

1.0

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

-

-

-

230/460/575 VOLT AND HIGH STATIC DRIVE
950

6.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

-

-

-

980

5.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

4.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

4.0

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.6

7.8

6.6

-

-

-

1025

3.5

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

-

-

-

1050

3.0

2.5

5.1

4.3

2.0

6.1

5.1

1.4

7.1

6.0

0.9

8.4

7.0

-

-

-

1065

2.5

2.6

5.3

4.4

2.1

6.3

5.3

1.5

7.3

6.2

1.0

8.6

7.2

-

-

-

1100

1.5

2.9

5.6

4.7

2.3

6.8

4.7

1.8

7.9

6.6

-

-

-

-

-

-

1120

1.0

3.1

5.8

4.9

2.5

7.0

5.9

1.9

8.3

6.9

-

-

-

-

-

NOTES:

1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.

Johnson Controls Unitary Products

25

262260-YTG-E-1008

TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT
300 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)

MOTOR
PULLEY
(TURNS
OPEN)*

CFM
7500
ESP

BHP

8750
KW

ESP

BHP

10000
KW

ESP

BHP

11250
KW

ESP

BHP

12500
KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE
975

6.0

1.2

5.9

4.9

5.0

7.3

6.0

-

-

-

-

-

-

-

-

-

1005

5.0

1.4

6.2

5.1

0.7

7.7

6.3

-

-

-

-

-

-

-

-

-

1040

4.0

1.6

6.6

5.4

0.9

8.1

6.7

0.2

9.7

8.0

-

-

-

-

-

-

1070

3.0

1.8

6.9

5.7

1.1

8.5

7.0

0.4

10.2

8.3

-

-

-

-

-

-

1100

2.0

2.0

7.3

6.0

1.3

8.9

7.3

0.6

10.6

8.7

-

-

-

-

-

-

1135

1.0

2.2

7.7

6.3

1.6

9.3

7.6

0.8

11.1

9.1

-

-

-

-

-

-

1165

0.0

2.4

8.0

6.6

1.8

9.7

8.0

1.0

11.6

9.5

0.2

13.5

11.0

-

-

-

208 VOLT AND HIGH STATIC DRIVE
1140

6.0

2.2

7.7

6.3

1.6

9.4

7.7

0.9

11.2

9.2

-

-

-

-

-

-

1180

5.0

2.5

8.2

6.7

1.9

9.9

8.1

1.2

11.8

9.7

0.3

13.7

11.2

-

-

-

1215

4.0

2.7

8.6

7.0

2.1

10.4

8.5

1.4

12.3

10.1

0.6

14.3

11.7

-

-

-

1255

3.0

3.0

9.1

7.4

2.4

11.0

9.0

1.7

12.9

10.6

0.9

15.0

12.3

-

-

-

1290

2.0

3.2

9.5

7.8

2.7

11.5

9.4

2.0

13.5

11.1

1.2

15.6

12.8

-

-

-

1330

1.0

3.5

10.0

8.2

3.0

12.0

9.9

2.3

14.1

11.6

1.5

16.4

13.4

-

-

-

1365

0.0

3.7

10.5

8.6

3.2

12.6

10.3

2.6

14.7

12.1

1.8

17.0

13.9

-

-

-

230/460/575 VOLT AND STANDARD DRIVE
975

6.0*

1.4

5.9

4.9

1.0

7.3

6.0

0.5

8.8

7.2

-

-

-

-

-

-

1005

5.0

1.6

6.2

5.1

1.2

7.7

6.3

0.7

9.2

7.6

0.1

10.9

8.9

-

-

-

1040

4.0

1.8

6.6

5.4

1.4

8.1

6.7

0.9

9.7

8.0

0.3

11.4

9.4

-

-

-

1070

3.0

2.0

6.9

5.7

1.6

8.5

7.0

1.1

10.2

8.3

0.6

11.9

9.8

-

-

-

1100

2.0

2.1

7.3

6.0

1.8

8.9

7.3

1.3

10.6

8.7

0.8

12.4

10.2

0.2

14.3

11.7

1135

1.0

2.4

7.7

6.3

2.0

9.3

7.6

1.6

11.1

9.1

1.0

13.0

10.6

0.4

14.9

12.2

1165

0.0

2.6

8.0

6.6

2.2

9.7

8.0

1.8

11.6

9.5

1.3

13.5

11.0

0.7

15.5

12.7

230/460/575 VOLT AND HIGH STATIC DRIVE
1140

6.0

2.4

7.7

6.3

2.1

9.4

7.7

1.6

11.2

9.2

1.1

13.1

10.7

0.5

15.0

12.3

1180

5.0

2.7

8.2

6.7

2.3

9.9

8.1

1.9

11.8

9.7

1.4

13.7

11.2

0.8

15.8

12.9

1215

4.0

2.9

8.6

7.0

2.6

10.4

8.5

2.2

12.3

10.1

1.7

14.3

11.7

1.1

16.4

13.5

1255

3.0

3.2

9.1

7.4

2.9

11.0

9.0

2.5

12.9

10.6

2.0

15.0

12.3

1.4

17.2

14.1

1290

2.0

3.4

9.5

7.8

3.1

11.5

9.4

2.7

13.5

11.1

2.2

15.6

12.8

-

-

-

1330

1.0

3.7

10.0

8.2

3.4

12.0

9.9

3.0

14.1

11.6

2.6

16.4

13.4

-

-

-

1365

0.0

3.9

10.5

8.6

3.7

12.6

10.3

3.3

14.7

12.1

2.9

17.0

13.9

-

-

-

NOTES:

1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.

15 HP Motor is required.

26

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 16: BLOWER MOTOR AND DRIVE DATA
MODEL
SIZE

DRIVE

MOTOR1
BLOWER
RANGE
(RPM) HP FRAME EFF.
(%)

ADJUSTABLE MOTOR PULLEY
DESIGNATION

OUTSIDE
DIA.
(IN.)

PITCH
DIA.
(IN.)

17.5 &
20 TON

High
Static

965/1190

5

184 T

83

1VP56

5.35

4.3-5.32

1-1/8

7.5

213 T

89

1VP68

6.75

5.5-6.52

1-3/8

950/1120

2

Standard 950/1120 10
25 TON

High
Static

1140/1365 15

215 T

89.5

1VP68

6.75

5.5-6.5

254 T

91

1VP75X

7.5

6.2-7.4

PITCH
BORE DESIGLENGTH QTY.
(IN.) NATION
(IN.)

BK90

8.75

8.4

1

BX70

82.8

1

BK80

7.75

7.4

1

BX68

69.8

1

BK120

11.75

11.4

1-3/16

BX83

84.8

1

BK110

10.75

10.4

1-3/16

BX81

82.8

1

1-3/8 1B5V110

11.3

11.1

1-7/16

BX81

82.8

1

1-5/8

9.7

9.5

1-7/16 5VX840

84.0

1

Standard 870/1025
High
Static

OUTSIDE PITCH
DIA.
DIA.
(IN.)
(IN.)

BORE DESIG(IN.) NATION

Standard 850/1065
15 TON

BELT
(NOTCHED)

FIXED BLOWER PULLEY

1B5V94

1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because
they are located in the moving air, upstream of any heating device.
2. Do NOT close this pulley below 1 turn open.

TABLE 17: STATIC RESISTANCES1
RESISTANCE, IWG
CFM
DESCRIPTION
15 TON

25 TON

6000

7200

6000

8000

9000

6000

7000

9400

7500

10000

12500

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

18kW

0.3

0.4

0.4

0.4

0.4

0.5

0.4

0.4

0.5

0.4

0.6

0.6

36kW

0.3

0.4

0.5

0.4

0.5

0.5

0.4

0.5

0.5

0.5

0.5

0.6

54kW

0.4

0.5

0.5

0.5

0.5

0.6

0.5

0.5

0.6

0.5

0.6

0.7

72kW

0.4

0.5

0.5

0.5

0.5

0.6

0.5

0.5

0.6

0.5

0.6

0.7

0.1

0.1

0.1

0.1

0.1

0.2

0.1

0.1

0.2

0.1

0.2

0.3

0.1

0.2

0.3

0.2

0.3

0.5

0.2

0.3

0.5

0.3

0.5

0.6

ECONOMIZER OPTION
HORIZONTAL DUCT

20 TON

4500
WET COIL

ELECTRIC HEAT
OPTIONS
(DH models only)

17.5 TON

CONNECTIONS2

1. Deduct theses resistance values from the available unit ESP values listed in the respective blower performance table except for
Horizontal Duct Connections.
2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures
to the ESP values on the respective unit’s blower performance table.

TABLE 18: POWER EXHAUST PERFORMANCE
STATIC RESISTANCE OF RETRUN DUCTWORK, IWG

MOTOR
SPEED1

0.2

0.3

0.4

0.5

0.6

CFM

kW

CFM

kW

CFM

kW

CFM

kW

CFM

kW

HIGH

5250

0.83

4500

0.85

4200

0.88

3750

0.93

3000

0.99

MEDIUM

4900

0.77

3900

0.79

3500

0.82

2900

0.85

-

-

LOW

4400

0.72

3700

0.74

3000

0.78

-

-

-

-

2

1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
2. The factory setting.

Johnson Controls Unitary Products

27

262260-YTG-E-1008

TABLE 19: DH 180, 210 & 240 ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TONNAGE)

VOLTAGE

RLA
EACH

LRA
EACH

ID
CONV
OD FAN
BLOWER
OUTLET
MOTORS
MOTOR
MODEL
AMPS
FLA EACH
FLA

208-3-60

21.8

184

4.5

12.8

0.0

230-3-60

21.8

184

4.3

12.8

0.0

460-3-60

11.0

90

2.2

6.4

0.0

575-3-60

9.6

73

1.7

5.2

0.0

208-3-60

25.6

190

4.5

20.0

0.0

230-3-60

25.6

190

4.3

20.0

0.0

460-3-60

12.8

95

2.2

10.0

0.0

575-3-60

10.2

75

1.7

7.5

0.0

208-3-60

32.1

237

4.5

20.0

0.0

230-3-60

32.1

237

4.3

20.0

0.0

460-3-60

14.3

130

2.2

10.0

0.0

575-3-60

12.9

85

1.7

7.5

0.0

DH180
(15)

DH210
(17 1/2)

DH240
(20)

None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72

HEATER OPTION
KW

STAGES

AMPS

-13.5
27
40.6
54.1
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-13.5
27
40.6
54.1
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-13.5
27
40.6
54.1
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0

-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2

-37.5
74.9
112.7
150.2
-43.3
86.6
129.9
173.2
-21.7
43.3
65.0
86.6
-17.3
34.6
52.0
69.3
-37.5
74.9
112.7
150.2
-43.3
86.6
129.9
173.2
-21.7
43.3
65.0
86.6
-17.3
34.6
52.0
69.3
-37.5
74.9
112.7
150.2
-43.3
86.6
129.9
173.2
-21.7
43.3
65.0
86.6
-17.3
34.6
52.0
69.3

MAX.
MIN.
FUSE/
CIRCUIT
1
AMPACITY BRKR
SIZE
(AMPS)
(AMPS)
70.9
70.9
109.7
156.9
166.2
70.5
70.5
124.3
145.9
189.2
35.6
35.6
62.1
73.0
94.6
30.2
30.2
49.8
58.5
75.8
86.6
86.6
118.7
165.9
175.2
86.2
86.2
133.3
154.9
198.2
43.2
43.2
66.6
77.5
99.1
33.9
33.9
52.7
61.3
78.7
101.2
101.2
118.7
165.9
175.2
100.8
100.8
133.3
154.9
198.2
46.6
46.6
66.6
77.5
99.1
39.9
39.9
52.7
61.3
78.7

90
90
110
175
200
90
90
125
175
225
45
45
70
80
110
35
35
50
70
90
110
110
125
175
200
110
110
150
175
225
50
50
70
90
110
40
40
60
70
90
125
125
125
175
200
125
125
150
175
225
60
60
70
90
110
50
50
60
70
90

NOTE 1: HACR Type per NEC.

28

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 20: DH 300 ELECTRICAL DATA STANDARD MOTOR WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TONNAGE)

VOLTAGE

RLA
EACH

LRA
EACH

ID
CONV
OD FAN
BLOWER
OUTLET
MOTORS
MOTOR
MODEL
AMPS
FLA EACH
FLA

208

37.1

239

4.5

28.0

0.0

230

37.1

239

4.3

26.0

0.0

460

17.2

125

2.2

13.0

0.0

575

12.4

80

1.7

10.0

0.0

300
(25)

None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72

HEATER OPTION
KW

STAGES

AMPS

13.5
27.0
40.6
54.1
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0

1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2

37.5
74.9
112.7
150.2
43.3
86.6
129.9
173.2
21.7
43.3
65.0
86.6
17.3
34.6
52.0
69.3

MAX.
MIN.
FUSE/
CIRCUIT
1
AMPACITY BRKR
SIZE
(AMPS)
(AMPS)
120.5
120.5
128.7
175.9
185.2
118.1
118.1
140.8
162.4
205.7
56.1
56.1
70.4
81.2
102.9
41.3
41.3
55.8
64.5
81.8

150
150
150
200
200
150
150
150
175
225
70
70
80
90
110
50
50
60
70
90

NOTE 1: HACR Type per NEC.

TABLE 21: DH 300 ELECTRICAL DATA HIGH STATIC MOTOR WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TONNAGE)

VOLTAGE

RLA
EACH

LRA
EACH

ID
CONV
OD FAN
BLOWER
OUTLET
MOTORS
MOTOR
MODEL
AMPS
FLA EACH
FLA

208

37.1

239

4.5

38.6

0.0

230

37.1

239

4.3

38.6

0.0

460

17.2

125

2.2

19.3

0.0

575

12.4

80

1.7

15.4

0.0

300
(25)

None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72

HEATER OPTION
KW

STAGES

AMPS

13.5
27.0
40.6
54.1
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0

1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2

37.5
74.9
112.7
150.2
43.3
86.6
129.9
173.2
21.7
43.3
65.0
86.6
17.3
34.6
52.0
69.3

MAX.
MIN.
FUSE/
CIRCUIT
1
AMPACITY BRKR
SIZE
(AMPS)
(AMPS)
131.5
131.5
141.9
189.1
198.4
131.1
131.1
156.5
178.2
221.5
62.9
62.9
78.3
89.1
110.7
47.5
47.5
62.6
71.2
88.5

150
150
150
200
225
150
150
175
200
250
80
80
80
100
125
60
60
70
80
100

NOTE 1: HACR Type per NEC.

Johnson Controls Unitary Products

29

262260-YTG-E-1008

TABLE 22: DH 180, 210 & 240 ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TONNAGE)

VOLTAGE

RLA
EACH

LRA
EACH

ID
CONV
OD FAN
BLOWER
OUTLET
MOTORS
MOTOR
MODEL
AMPS
FLA EACH
FLA

208-3-60

21.8

184

4.5

12.8

10.0

230-3-60

21.8

184

4.3

12.8

10.0

460-3-60

11.0

90

2.2

6.4

5.0

575-3-60

9.6

73

1.7

5.2

4.0

208-3-60

25.6

190

4.5

20.0

10.0

230-3-60

25.6

190

4.3

20.0

10.0

460-3-60

12.8

95

2.2

10.0

5.0

575-3-60

10.2

75

1.7

7.5

4.0

208-3-60

32.1

237

4.5

20.0

10.0

230-3-60

32.1

237

4.3

20.0

10.0

460-3-60

14.3

130

2.2

10.0

5.0

575-3-60

12.9

85

1.7

7.5

4.0

DH180
(15)

DH210
(17 1/2)

DH240
(20)

None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72

HEATER OPTION
KW

STAGES

AMPS

-13.5
27
40.6
54.1
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-13.5
27
40.6
54.1
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-13.5
27
40.6
54.1
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0
-18.0
36.0
54.0
72.0

-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2
-1
2
2
2

-37.5
74.9
112.7
150.2
-43.3
86.6
129.9
173.2
-21.7
43.3
65.0
86.6
-17.3
34.6
52.0
69.3
-37.5
74.9
112.7
150.2
-43.3
86.6
129.9
173.2
-21.7
43.3
65.0
86.6
-17.3
34.6
52.0
69.3
-37.5
74.9
112.7
150.2
-43.3
86.6
129.9
173.2
-21.7
43.3
65.0
86.6
-17.3
34.6
52.0
69.3

MAX.
MIN.
FUSE/
CIRCUIT
1
AMPACITY BRKR
SIZE
(AMPS)
(AMPS)
80.9
80.9
122.2
169.4
178.7
80.5
82.6
136.8
158.4
201.7
40.6
41.3
68.4
79.2
100.9
34.2
34.2
54.8
63.5
80.8
96.6
96.6
131.2
178.4
187.7
96.2
96.2
145.8
167.4
210.7
48.2
48.2
72.9
83.7
105.4
37.9
37.9
57.7
66.3
83.7
111.2
111.2
131.2
178.4
187.7
110.8
110.8
145.8
167.4
210.7
51.6
51.6
72.9
83.7
105.4
43.9
43.9
57.7
66.3
83.7

100
100
125
175
200
100
100
150
175
225
50
50
70
90
110
40
40
60
70
90
110
110
150
200
200
110
110
150
175
225
60
60
80
90
110
45
45
60
70
90
125
125
150
200
200
125
125
150
175
225
60
60
80
90
110
50
50
60
70
90

NOTE 1: HACR Type per NEC.

30

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 23: DH 300 ELECTRICAL DATA STANDARD MOTOR WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TONNAGE)

VOLTAGE

RLA
EACH

LRA
EACH

ID
CONV
OD FAN
BLOWER
OUTLET
MOTORS
MOTOR
MODEL
AMPS
FLA EACH
FLA

208

37.1

239

4.5

28.0

10.0

230

37.1

239

4.3

26.0

10.0

460

17.2

125

2.2

13.0

5.0

575

12.4

80

1.7

10.0

4.0

300
(25)

None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72

HEATER OPTION
KW

STAGES

AMPS

13.5
27.0
40.6
54.1
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0

1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2

37.5
74.9
112.7
150.2
43.3
86.6
129.9
173.2
21.7
43.3
65.0
86.6
17.3
34.6
52.0
69.3

MAX.
MIN.
FUSE/
CIRCUIT
1
AMPACITY BRKR
SIZE
(AMPS)
(AMPS)
130.5
130.5
141.2
188.4
197.7
128.1
128.1
153.3
174.9
218.2
61.1
61.1
76.6
87.5
109.1
45.3
45.3
60.8
69.5
86.8

150
150
150
200
200
150
150
175
175
225
70
70
80
90
110
50
50
70
70
90

NOTE 1: HACR Type per NEC.

TABLE 24: DH 300 ELECTRICAL DATA HIGH STATIC MOTOR WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TONNAGE)

VOLTAGE

RLA
EACH

LRA
EACH

ID
CONV
OD FAN
BLOWER
OUTLET
MOTORS
MOTOR
MODEL
AMPS
FLA EACH
FLA

208

37.1

239

4.5

38.6

10.0

230

37.1

239

4.3

38.6

10.0

460

17.2

125

2.2

19.3

5.0

575

12.4

80

1.7

15.4

4.0

300
(25)

None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72

HEATER OPTION
KW

STAGES

AMPS

13.5
27.0
40.6
54.1
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0

1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2

37.5
74.9
112.7
150.2
43.3
86.6
129.9
173.2
21.7
43.3
65.0
86.6
17.3
34.6
52.0
69.3

MAX.
MIN.
FUSE/
CIRCUIT
1
AMPACITY BRKR
SIZE
(AMPS)
(AMPS)
141.5
141.5
154.4
201.6
210.9
141.1
141.1
169.0
190.7
234.0
67.9
67.9
84.5
95.3
117.0
51.5
51.5
67.6
76.2
93.5

175
175
175
225
225
175
175
175
225
250
80
80
90
110
125
60
60
70
90
100

NOTE 1: HACR Type per NEC.

Johnson Controls Unitary Products

31

262260-YTG-E-1008

TABLE 26: ELECTRIC HEAT CORRECTION
FACTORS

TABLE 25: DH VOLTAGE LIMITATIONS1
VOLTAGE

POWER SUPPLY
MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

575-3-60

518

506

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTIPLIER

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

1. Utilization Range “A” in accordance with ARI Standard
110.

CONTROL WIRING
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
UNIT TERMINAL
RC
BLOCK 1 TB2
RH
R
Y1
Y1
ADD
Y2
Y2
JUMPER
W1
W1
G
B
LED1
LED2
ADD
JUMPER

COM
A1
A2
T

W2
G
B
X

3

W2

NOT USED

4
4

24 VOLT
A1 TRANSFORMER
A2

COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT1
UNIT TERMINAL
TERMINALS
BLOCK 1TB2
RH
RC

ADD
JUMPER

Y1
Y2
W1
W2
G

FIGURE 3 -

32

24 VOLT
TRANSFORMER

24 Volt Thermostat 2TH04701024 or 2TH04701524
(with Subbase 2TB04700324).
2Terminal strip 1TB - located on relay board in 24-volt section
of the unit control box.
3Second stage heating is not required on units with a single stage
electric heater.
1

POWER WIRING

T
TO REMOTE SENSOR
2THO4702224 IF USED
1Electronic programmable thermostat 2ET04700224 (includes subbase).
2Terminal block 1TB- located on relay board in 24-volt section of the unit control box.
3Second stage heating is not required on units with a single stage electric heater.
4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers
when the thermostat switches to the set-back position.
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.

3

R
Y1
Y2
W1
W2
G
B
X
A1
A2
Y3

L1
LINE VOLTAGE
TERMINAL
L2
BLOCK 2TB
L3
IN CONTROL BOX

Refer to the
ELECTRICAL DATA
tables to size the
power wiring, the
fuses and the
disconnect switch.

GROUND LUG

TYPICAL DH FIELD WIRING DIAGRAM

Johnson Controls Unitary Products

262260-YTG-E-1008

TABLE 27: PHYSICAL DATA
DH

MODELS
EVAPORATOR
BLOWER

180

210

240

300

Centrifugal Blower (Dia. x Wd. in.)

15 x 15

18 x 15

18 x 15

18 x 15

Fan Motor HP Standard/Hi Static

5

7.5

7.5

10/15

Rows Deep

4

4

4

4

Fins Per Inch

13.5

13.5

13.5

13.5

EVAPORATOR
COIL
CONDENSER
FANS
(Two Per Unit)

Face Area (Sq. Ft.

15.5

20.0

20.0

25.0

Propeller Dia. (in.) (Each)

30

30

30

30

Fan Motor Hp (Each)

1

1

1

1

Nom. CFM (Each)

5765

7000

7000

7200

Rows Deep (Each)

3

3

3

2

Fins Per Inch (Each)

13

15

15

20

Face Area (Sq. Ft.) (Total)

36.0

43.3

43.3

43.3

7.5 Ton Scroll

2

2

-

-

10 Ton Scroll

-

-

2

-

12.5 Ton Scroll

-

-

-

2

Quantity Per Unit (16” X 20” X 2” or 4“)

-

4

4

4

Quantity Per Unit (16” X 25” X 2” or 4“)

-

4

4

4

Quantity Per Unit (18” X 24” X 2” or 4“)

5

-

-

-

Total Face Area (sq. ft.)

15.0

20.0

20.0

20.0

System #1

23/10

24/0

24/2

21/1

System #2

21/10

24/8

27/2

21/1

CONDENSER
COILS
(Two Per Unit)
COMPRESSOR
(Qty. Per Unit)

AIR
FILTERS

Refrigerant 22
(lbs./oz.)

CHARGE

TABLE 28: OPERATING WEIGHTS (LBS.)
MODEL SIZE

15 TON

17.5 TON

20 TON

25 TON

1900

1950

2100

2345

240Mbh

2100

2150

2300

2545

320Mbh

2140

2190

2340

2585

DH (Cooling Only)

BASIC
UNIT

DH
(Gas/Electric)
Economizer

160

Economizer with
Power Exhaust

245

Motorized Damper

OPTIONS

150

Electric Heater
(DH only)

18kW

25

36kW

30

54kW

35

72kW

40

Hot Gas Bypass
Supply Fan VFD

10
See Table 29

Roof Curb

ACCY.

175

185

185

Barometric Damper

45

Economizer/Motorized Damper Rain Hood

55

Economizer/Power Exhaust Rain Hood

90

Wood Skid

220

185

TABLE 29: SUPPLY FAN VFD WEIGHTS, IN LBS.
SUPPLY FAN MOTOR

230V

460V

575V

W/O MANUAL BYPASS
5.0 hp
7.5 hp
10.0 hp
15.0 hp

25
30
30
30

25
30
30
30

30
30
35
40

W/MANUAL BYPASS
5.0 hp
7.5 hp
10.0 hp
15.0 hp

30
35
35
40

30
35
35
35

35
35
40
45

Johnson Controls Unitary Products

33

262260-YTG-E-1008

ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE A IR A ND
POWER EXHAUST RAIN HOODS
(See detail "Y")
COMPRESSOR
ACCESS
(See detail "X")

BLOWER ACCESS
(Location Of
FIELD-SUPPLIED
BLOWER MOTOR ACCESS Optional VFD)
DISCONNECT SWITCH
(Location Of Optional
LOCATION
VFD Bypass)
BLOWER
COMPARTMENT
ACCESS
(Auxiliary)

OPTIONAL COIL
GUARD KIT

DOT PLUG
(For pressure
Drop Reading)

48-5/8" (15 Ton)
52-5/8" (17.5 thru 25 Ton)

ELECTRIC
GAS HEAT
ACCESS
CONDENSER
COILS

VENT A IR
OUTLET
HOODS

21"
n)
To
5
(1 7.5 on)
"
1
4 ( 5T
1/
5- /4" 2
12 6-1 thru
6-3/8"
3
1

COMBUSTION
AIR INLET
HOOD

5"
7-1/8"

9-3/4"
(C)
GAS SUPPLY
ENTRY

(A)
CONTROL WIRING
ENTRY

46-5/8"
CONTROL BOX
ACCESS

FRONT
VIEW

92"

5-7/8"

11-1/2"

35"

n)
To
5
(1 7.5 n)
"
/4 (1 To
-1 /4" 5
24 5-1 ru 2
3 th

BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
RETURN
AIR

(B)
POWER WIRING
ENTRY

RETURN A IR
3-3/4"

33"
SUPPLY
AIR
2-3/4"

OUTDOOR A IR

21-1/2"

11-1/8"

UNIT BASE WITH RAILS
Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations

OUTDOOR A IR
(Economizer)
(B)
POWER WIRING
ENTRY

(D)
GAS SUPPLY
ENTRY
8-1/8"

NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.

FIGURE 4 -

SUPPL Y A IR

(A)
CONTROL WIRING
ENTRY

All dimensions are in inches. They are
subject to change without notice. Certified dimensions will be provided upon
request.

46-5/8"
9-1/4"
12-1/2"

9-3/4"

UNIT DIMENSIONS DH180, 210, 240 & 300 (FRONT VIEW)

TABLE 30: UTILITIES ENTRY DATA
HOLE
A
B

OPENING SIZE
(DIA.)
1-1/8” KO
3/4” NPS (Fem.)
3-5/8” KO
3” NPS (Fem.)

C

2-3/8” KO

D

1-11/16” Hole

USED FOR
Control Wiring
Power Wiring

Side
Bottom
Side
Bottom

Gas Piping (Front)1
Gas Piping (Bottom)1,

2

1. One-inch gas piping NPT required.
2. Opening in the bottom of the unit can be located by the slice in
the insulation.
NOTE: All entry holes should be field sealed to prevent rain

water entry into the building.

34

Johnson Controls Unitary Products

262260-YTG-E-1008

EVAPORATOR
SECTION

DOT PLUG
(For pressure
drop reading)

40-3/8"

FILTER
ACCESS
SUPPLY
AIR
RETURN
AIR
COMPRESSOR
ACCESS

OUTDOOR
AIR
40-1/2"

SUPPLY AIR
ACCESS

Dimensions listed are for side
duct flange openings; see
Field Accessories for Side
Duct Flange Kit.

FIGURE 5 -

18-5/8"
1" NPT FEMALE
COND. DRAIN
CONNECTION

27-3/4"
RETURN AIR
ACCESS

5-1/8"
28-5/8” (15 TON)
39-5/8"
(17.5 thru 25 TON)

REAR
VIEW

OUTDOOR AIR
COMPARTMENT
ACCESS

REAR VIEW DIMENSIONS

NOTE:Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for
connecting side ducts.
For bottom duct applications:

For side duct applications:

1.

Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and
return air duct covers.

1.

Replace the side panels on the supply and return air
compartments with the side duct flange accessory kit
panels.

2.

Remove and discard the bottom duct covers. Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.

2.

Connect ductwork to the flanges on those panels.

3.

Replace the side supply and return air compartment
panels.

Johnson Controls Unitary Products

35

262260-YTG-E-1008

NOTE: ELEC / ELEC Models: Units and ductwork are
approved for zero clearance to combustible material
when equipped with electric heaters.

TABLE 31: MINIMUM CLEARANCES
LOCATION

CLEARANCE

Front

36”

Rear

24” (Less Economizer)
49” (With Economizer)

Left Side (Filter Access)

24” (Less Economizer)
36” (With Economizer)3

Right Side (Cond. Coil)

36”

Below
Above

GAS / ELEC Models: A 1” clearance must be
provided between any combustible material and the
supply air ductwork for a distance of 3 feet from the
unit.

Unit1

0”

Unit2

72” With 36” Maximum
Horizontal Overhang (For
Condenser Air Discharge)

The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:

1. Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hood
must be removed from its ride along position in front of evaporator coil, or in the outdoor air compartment, prior to final installation.

• Three (3) feet above any force air inlet located
within 10 horizontal feet (excluding those integral to
the unit).
• Four (4) feet below, four horizontal feet from, or one
foot above any door or gravity air inlet into the
building.
• Four (4) feet from electric and gas meters,
regulators and relief equipment.

SUPPLY AIR
COMPARTMENT

POWER EXHAUST
RAIN HOOD
(on Return Air Compartment)

ECONOMIZER
MOTORIZED
DAMPER
RAIN HOOD
(on Outdoor Air Compartment)

ECONOMIZER / MOTORIZED DAMPER
AND POWER EXHAUST RAIN HOODS

FIXED
OUTDOOR AIR
INTAKE HOOD
(located on
Return Air
Compartment)
36-5/8”
1“ CONDENSATE
DRAIN
(Must be trapped)

16-1/8”

5”
28-3/16”

REAR VIEW

92”

LH VIEW
DETAIL “Y”
UNIT WITH RAIN HOODS

FIGURE 6 -

36

UNIT DIMENSIONS DH180, 210, 240 & 300 (RAINHOOD)

Johnson Controls Unitary Products

262260-YTG-E-1008

(17.5, 20 & 25 Ton)

FIGURE 7 -

UNIT CENTER OF GRAVITY

FIGURE 8 -

TYPICAL UNIT APPLICATIONS

Johnson Controls Unitary Products

37

262260-YTG-E-1008

B

E
F

C
A

D
A

F R O N T

C
F R O N T

D

FIGURE 9 -

B

UNIT 4 POINT LOAD

FIGURE 10 - UNIT 6 POINT LOAD

TABLE 32: DH 180, 210, 240 & 300 4 POINT LOAD WEIGHT DISTRIBUTION
UNIT MODEL

OPERATING
WEIGHT
(lb)

A

B

C

D

DH180C00

1900

445

484

506

465

DH180N24

2100

492

535

559

514

DH180N32

2140

501

545

570

524

DH210C00

1950

457

497

519

477

DH210N24

2150

504

548

572

526

DH210N32

2190

513

558

583

536

DH240C00

2100

492

535

559

514

DH240N24

2300

539

586

612

563

DH240N32

2340

548

596

623

573

DH300C00

2345

461

502

720

662

DH300N24

2545

501

545

781

718

DH300N32

2585

509

553

794

729

TABLE 33: DH 180, 210, 240 & 300 6 POINT LOAD WEIGHT DISTRIBUTION

38

UNIT MODEL

OPERATING
WEIGHT
(lb)

A

B

C

D

E

F

DH180C00

1900

293

306

323

342

327

309

DH180N24

2100

324

338

357

378

362

342

DH180N32

2140

330

344

364

385

369

348

DH210C00

1950

300

314

332

351

336

317

DH210N24

2150

331

346

366

387

370

350

DH210N32

2190

337

352

372

394

377

357

DH240C00

2100

324

338

357

378

362

342

DH240N24

2300

354

370

391

414

396

374

DH240N32

2340

360

377

398

421

403

381

DH300C00

2345

303

321

339

487

460

435

DH300N24

2545

329

348

368

528

499

472

DH300N32

2585

334

353

374

537

507

479

Johnson Controls Unitary Products

262260-YTG-E-1008

(17.5 thru
25 Ton)

(17.5 thru
25 Ton)

FIGURE 11 - UNIT ROOF CURB DIMENSIONS

(17.5 & 20 Ton)

FIGURE 12 - ROOF CURB DUCT OPENINGS
DIMENSIONS
1.
2.

FIGURE 13 - CUT AWAY OF ROOF CURB

The 2” space between the ducts allows for “jumping” an
existing roof joist.
The 58-1/2” overall dimension of the ducts allows
ductwork penetration between roof joists that are
spaced on 72” centers.

NOTE: Ducts can be installed into the curb from the roof. All
electrical and gas line connections can be made
inside the curb.

Johnson Controls Unitary Products

39

262260-YTG-E-1008

FIGURE 14 - TYPICAL ROOFTOP INSTALLATION

THERMOSTAT
TERMINALS

CONTROL
TERMINAL
BLOCK

W1

W1

W2

1

W2
Y1

Y1
Y2

G
2

OCC
P

G

P1
R

Y2

Smoke
Detector

X

C

R
4

SD

RC
OCC
X

5

C

R

Jumper

SD
SD

6

3

C

24 VAC
Class 2

TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS

1

Second stage heating not required on single stage heating units.

2

Second stage cooling not required on single stage cooling units.

3

Jumper is required if there is no Smoke Detector circuit.

4

Jumper is required for any combination of R, RC, or RH.

5

OCC is an output from the thermostat to indicate the Occupied condition.

6

X is an input to the thermostat to display Error Status conditions.

FIGURE 15 - TYPICAL SIMPLICITY ® CONTROL WIRING DIAGRAM

40

Johnson Controls Unitary Products

262260-YTG-E-1008

GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility.
York's Sunline Ultra™ units are convertible single package
units. All models have dual independent refrigerant circuits
for efficient part load operation and maximum comfort control. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at
ground level or set on steel beams above a finished roof.
Cooling only, cooling with gas heat and cooling with electric
heat models are available with a wide variety of factorymounted options and field-installed accessories to make
them suitable for almost every application. All units are selfcontained and assembled on full perimeter base rails with
holes in the four corners for overhead rigging. Every unit is
completely piped, wired, charged and tested at the factory
to simplify the field installation and to provide years of
dependable operation. All models (including those with an
economizer) are suitable for either bottom or horizontal duct
connections. Models with power exhaust are suitable for
bottom duct connections only. For bottom duct, remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, replace the
supply and return air panels on the rear of the unit with a
side duct flange accessory. All supply air blowers are
equipped with a belt drive that can be adjusted to meet the
exact requirements of the job. A high static drive option is
available for applications with a higher CFM and/or static
pressure requirement.
Each unit shall have 2 condenser fan motors. All compressors include crankcase heat and internal pressure relief.
Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and
a suction line with a freezestat and low pressure/loss of
charge switch. The unit control circuit includes a 75 VA
transformer, a 24-volt circuit breaker and a relay board with
two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All models are
CSA approved. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel
tubular heat exchangers carry an additional 9-year warranty.

DESCRIPTION
Units shall be factory-assembled, single packaged, DH***N
Electric Cooling/Gas Heat, DH***C/E Electric Cooling/
Optional Electric Heat, designed for outdoor mounted installation. The 15 ton units shall have minimum EER ratings of
10.8, the 17.5 ton units shall have minimum EER ratings of
10.2, the 20 ton units shall have minimum EER ratings of 9.7
and the 25 ton units shall have minimum EER ratings of 9.6.
They shall have built-in field convertible duct connections
for down discharge supply/return or horizontal discharge

Johnson Controls Unitary Products

supply/return, and be available with factory installed options
or field installed accessories. The units shall be factory
wired, piped, charged with R-22 refrigerant and factory
tested prior to shipment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a
facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI
test procedures. Units shall be CSA listed, classified to
ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236-M90
conditions.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel, with
exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hour salt spray test per ASTMB117 standards. Indoor blower section shall be insulated
with a minimum 1/2" thick insulation, coated on the airside.
Aluminum foil faced insulation shall be used in the furnace
compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels
shall be "large" size, easily removable for servicing and
maintenance. Full perimeter base rails shall be provided to
assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 2" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be
designed to accommodate either 2" or 4" filters. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air
by-pass of the coils. Condensate pan shall be internally
sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 1" I.D.
female and be a ridged mount connection. Unit shall incorporate a fixed outdoor air damper with an outdoor air intake
opening covered with a bird screen and a rain hood painted
to match the exterior of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustablepitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower
rating, plus the service factor. Units shall be designed not to
operate above service factor. Fan wheel shall be double-inlet
type with forward-curved blades, dynamically balanced to
operate smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.
A variable air volume (VAV) option using a variable frequency
drive (VFD) is available for applications requiring a constant
supply duct static pressure. Units equipped for VAV shall be
controlled by a duct pressure transducer with a 0 - 5” WC pressure range. The pressure transducer shall provide a 0 - 5 VDC
output signal to a VAV control board which, in turn shall provide
a 2 - 10 VDC speed reference signal to the VFD. The VAV
control board shall operate using factory-installed Supply
Air, Return Air and Outside Air Temperature Sensors. Units
equipped with VFD’s shall have factory-installed manual
bypass as an option.

41

262260-YTG-E-1008

2.

OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The 2 outdoor fan
motors shall be totally enclosed with permanently lubricated
bearings, internally protected against overload conditions and
staged independently.

d.

Unit shall incorporate "AUTO RESET" compressor
over temperature, over current protection.

e.

Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.

REFRIGERANT COMPONENTS
Compressors:
a.

b.

f.

Shall be Scroll compressors internally protected with
internal high-pressure relief and over temperature
protection.

Unit control board shall have on-board diagnostics
and fault code display.

g.

Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.

Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0 °F.

h.

Control board shall monitor each refrigerant safety
switch independently.

i.

Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.

Coils:
a.

b.

Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.

Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.

Balance-port thermostatic expansion valve with
independent circuit feed system.

b.

Filter drier/strainer to eliminate any moisture or foreign matter.

c.

Accessible service gage connections on both suction and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.

d.

The refrigeration system shall provide at least 15° F
of sub-cooling at design conditions.

e.

All models shall have two independent circuits.

f.

Hot gas bypass option shall be factory-installed on
compressor #1 discharge line to provide cooling in
low-load applications. HGBP shall be a standard
feature on VAV models and an optional feature on
CV models.

UNIT CONTROLS
a.

Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.

b.

Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.

c.

Loss-of-charge/Low-pressure switch.
1.

42

Freeze-protection thermostat, evaporator coil. If
any of the above safety devices trip, a LED
(light-emitting diode) indicator shall flash a
diagnostic code that indicates which safety
switch has tripped.

High-pressure switch.

GAS HEATING SECTION (DH***N MODELS)
Shall be designed with induced draft combustion with post
purge logic and energy saving direct spark ignition, redundant main gas valve. Ventor wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25° F. Burners shall be of the inshot type, constructed of aluminum coated steel and contain
air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a.

Primary and auxiliary high-temperature limit switches.

b.

Induced draft motor speed sensor.

c.

Flame roll out switch (automatic reset).

d.

Flame proving controls. Unit shall have two independent stages of capacity.

ELECTRIC HEATING (DH***C/E MODELS)
Nickel chromium electric heating elements shall be provided
as required by the application with 1 or 2 stage control, as
required, from 13.5 KW to 72 KW capacities. The heating
section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating
at an excessive temperature. Units with Electric Heating shall
be wired for a single point power supply with branch circuit
fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125° F
outdoor temperature, exceeding maximum load criteria of
ARI Standard 340/360. The compressor, with standard

Johnson Controls Unitary Products

262260-YTG-E-1008

controls, shall be capable of operation down to 0° F outdoor
temperature. Unit shall be provided with fan time delay to
prevent cold air delivery before heat exchanger warms up
(Gas heat only).

cooling shall modulate the economizer in order to maintain a supply air temperature (SAT) programmable setpoint. With the use of a field-installed indoor air quality
sensor, the controller shall provide Demand Ventilation
by modulating the economizer dampers to allow more
outside airflow upon detection of elevated indoor CO2
concentrations above a programmable set-point. With an
additional field-installed outdoor air quality sensor, Differential Demand Ventilation shall be provided.

ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.

The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water eliminator/filters shall be provided.

STANDARD LIMITED WARRANTIES
•

Compressor 5 Years

•

Heat Exchanger 10 Years

•

Electric Heat Element 5 Years

•

Other Parts 1 Year

Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
•

OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•

•

ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, springreturn damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
BAS-READY ECONOMIZER - Outdoor and return air
dampers that are interlocked and positioned by a fullymodulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG.
For units with optional VAV or Simplicity® Intelli-Comfort™ control, free-cooling shall be available while the
outdoor dry bulb temperature (OAT) remains below a
programmable set-point of the controller. Field-installed
humidity sensors for either outdoor air or outdoor &
return air streams are available to provide free-cooling
based on single-enthalpy or dual-enthalpy configurations, respectively. If free-cooling is available, a call for

Johnson Controls Unitary Products

MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall
not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unitmounted potentiometer shall be provided to adjust the
outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation.
Whenever the indoor fan motor is energized, the dampers
open up to one of two pre-selected positions - regardless
of the outdoor air enthalpy. Dampers return to the fully
closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•

ROOF CURB - 14" high, full perimeter curb with wood
nailer (shipped knocked-down).

•

100% BAROMETRIC RELIEF DAMPER - Contains a
rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure
through the unit.

•

PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.

•

HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.

•

HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.

•

BURGLAR BARS - Designed to work with above roof
curbs, depending on unit model. Fits duct openings of
curb supply and return air openings.

•

SIDE DUCT FLANGE - Supply and return air duct
flanges for side duct applications. Do not use on units
with power exhaust.

43

•

HIGH STATIC DRIVE - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower performance.

•

WOOD SKID - Allows unit to be handled with 90" forks.

•

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.

•

ANTI-RECYCLE TIMER - Assures 5-minute off time
between compressor cycles.

•

COIL GUARD KIT - Guard for cooling coil.

OTHER FACTORY INSTALLED OPTIONS
•

POWER EXHAUST OPTION - To work in conjunction
with economizers.

•

STAINLESS STEEL HEAT EXCHANGER

•

STAINLESS STEEL DRAIN PAN

•

TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL

•

ELECTRONIC SINGLE ENTHALPY ECONOMIZER

•

DIRTY FILTER SWITCH

•

PHASE MONITOR

•

COIL GUARD

•

POWERED GFI CONVENIENCE OUTLET

•

NON-POWERED GFI CONVENIENCE OUTLET

•

BAS CONTROLS - Simplicity ® Intelli-Comfort ™, CPC,
JOHNSON, HONEYWELL, NOVAR, YORK COMMERCIAL COMFORT SYSTEM (YCCS)

•

HINGED FILTER DOOR ACCESS AND TOOL FREE
ACCESS PANELS

•

HINGED TOOL FREE BLOWER, BLOWER MOTOR,
FILTER AND ELECTRICAL ACCESS PANELS

•

HIGH STATIC DRIVE

•

2" THROW AWAY FILTERS

•

4" PLEATED FILTERS

•

DISCONNECT SWITCH

•

SUPPLY AIR SMOKE DETECTOR

•

RETURN AIR SMOKE DETECTOR

Subject to change without notice. Printed in U.S.A.
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069

262260-YTG-E-1008
Supersedes: 262260-YTG-D-0708



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Tagged PDF                      : Yes
Page Mode                       : UseThumbs
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Creator Tool                    : FrameMaker 8.0
Modify Date                     : 2008:11:23 20:31:43-06:00
Create Date                     : 1999:12:07 14:27:40Z
Metadata Date                   : 2008:11:23 20:31:43-06:00
Format                          : application/pdf
Title                           : Y-TG, Single Package Gas/Elec Units and Sgl Pkg AC, Models: DH180, 210, 240 & 300
Creator                         : 
Producer                        : Acrobat Distiller 8.0.0 (Windows)
Document ID                     : uuid:c93ba6b6-6e79-4157-98ac-cb226c2946a2
Instance ID                     : uuid:3da03c2f-064a-490c-b880-d00d1b36761c
Page Count                      : 44
Page Layout                     : OneColumn
EXIF Metadata provided by EXIF.tools

Navigation menu