York Maxa Mier Erv Technical Guide
2015-09-09
: York Maxa-Mier-Erv-Technical-Guide york-maxa-mier-erv-technical-guide-811940 york pdf
Open the PDF directly: View PDF
.
Page Count: 48
| Download | |
| Open PDF In Browser | View PDF |
903106-UTG-A-0912 MAXA-MI$ER® TECHNICAL GUIDE V* Series Unitized Energy Recovery Ventilators ERV Unit with 3 - 12.5 Ton Packaged Unit DESCRIPTION • Reduces cooling load at design temperatures up to 4 tons per 1000 cfm of outside air. • Reduces heating load up to 2.5 Tons Btuh per 1000 CFM of outside air. • Dry energy transfer. Moisture in supply (intake) air stream is transferred to exhaust air stream in a vapor state, eliminating condensate plumbing from the UERV. • Attaches directly to the UPG rooftop units. All mounting equipment is provided. • Separate fused power supply. (Except VR74 or VR122) • Filters / mist eliminators are provided on the entering air openings. • Adjustable support legs are provided. (Except for Stand Alone) • Two modes of operation (Pivoting Wheel Models only) • Recovery mode during normal energy recovery operation. • True economizer mode when outside sensor calls for economizer operation (3 - 12.5 ton packaged units equipped with economizers). U. S. Patent 5,548,970. • Pivoting wheel models used with packaged unit with economizer. Sequence of operation controlled by economizer controller. (3- 12.5 Ton Only) • Balancing dampers provided on VR Modules. (Except VR74 and VR122) • Centrifugal blowers (both intake and exhaust for high static capability and low sound levels). (Except VR74 and VR122) • Heavy gauge galvanized steel cabinets corrosion protected with powder paint process that match UPG units. • Fully insulated cabinet. • AHRI certified internal enthalpy wheel is provided. • Internal enthalpy wheel made of polymeric material with silica gel impregnated into the material. The enthalpy wheel has a five year limited warranty. • Internal enthalpy wheels are easily cleanable. Large wheels (25 inch diameter and above) are split into easily removable pie segments. Smaller wheels can be removed from the ERV. • Continuous operation down to 10 ºF (-12 ºC) without defrost at indoor relative humidity up to 40%. For temperatures below 10 ºF (-12 ºC), Optional Low Ambient Control Kit is required. Kit includes temperature sensor to control the ERV before frost build up can occur on recovery wheel. ERV Unit with 15 - 25 Ton Packaged Unit Note: MAXA-MI$ER® UERV’s are designed for use with rooftops using 14” high or greater roof curbs. Note: ZF/ZH/ZJ/XP 037 thru 150 or ZS/ZU/ZW/XA-A3 thru -12, with ERV must use “slab” type economizers and downflow position. ERV Unit with 25 -40 Packaged Unit ETL Certified per UL 1995 and CSA 22.2 Energy recovery COMPONENT rated in accordance with AHRI/ANSI Standard 1060-2005 and certified to AHRI. Actual performance in packaged equipment may vary. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 903106-UTG-A-0912 TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . 2 UPG UERV MODEL NOMENCLATURE . . . . . . . . . . . . 3 APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 PRINCIPLE OF OPERATION . . . . . . . . . . . . . . . . . . . . . 4 AHRI/ANSI STANDARD 1060-2005 FOR AIR-TO-AIR ENERGY RECOVERY VENTILATION EQUIPMENT . . . . . 4 ENERGY RECOVERY WHEEL . . . . . . . . . . . . . . . . . . . . 4 CROSS LEAKAGE IN UERV’S (PURGE SECTORS) . . . 5 OPTIONAL ACCESSORIES - FIELD INSTALLED . . . . 5 OPTIONAL ACCESSORIES - FACTORY INSTALLED 6 HOW TO SELECT THE PROPER AIR CONDITIONING UNIT AND UNITARY ENERGY RECOVERY VENTILATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 UPG UERV STAND ALONE MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 PERFORMANCE - ERV SERIES . . . . . . . . . . . . . . . . . 22 SERVICE CLEARANCES - STAND ALONE SERIES ERVS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 LIST OF FIGURES Fig. # D SERIES STAND ALONE ERV'S FOR DOWN DISCHARGE DUCT ARRANGEMENTS . . . . . . . . . . . . . . 31 FEATURES AND NOTES . . . . . . . . . . . . . . . . . . . . . . . 31 S SERIES STAND ALONE ERV'S FOR SIDE BY SIDE DUCT ARRANGEMENTS . . . . . . . . . . . . . . . . . . . . . . 36 FEATURES AND NOTES . . . . . . . . . . . . . . . . . . . . . . . 36 O SERIES STAND ALONE ERV'S FOR OVER AND UNDER DUCT ARRANGEMENTS . . . . . . . . . . . . . . . . . . 40 FEATURES AND NOTES . . . . . . . . . . . . . . . . . . . . . . . 40 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . 44 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 SEQUENCE OF OPERATION: . . . . . . . . . . . . . . . . . . 45 UERV TROUBLESHOOTING GUIDE . . . . . . . . . . . . . 46 UERV BELOW 600 CFM WITH STATIONARY WHEEL (NO ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 UERV ABOVE 600 CFM WITH STATIONARY WHEEL (NO ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 UERV ABOVE 600 CFM WITH PIVOTING WHEEL (USED WITH ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . 47 13 SPECIFICATIONS AND ELECTRICAL DATA - 600 THROUGH 1700 CFM ERV’S . . . . . . . . . . . . . . . . . . . 12 Pg. # 14 SPECIFICATIONS AND ELECTRICAL DATA - 1500 THROUGH 2800 CFM ERV’S . . . . . . . . . . . . . . . . . . . 13 1 UNITIZED ENERGY RECOVERY VENTILATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 ENERGY RECOVERY WHEEL . . . . . . . . . . . . . . . . . . 4 15 SPECIFICATIONS AND ELECTRICAL DATA - 2800 THROUGH 3600 CFM ERV’S . . . . . . . . . . . . . . . . . . . 14 3 “P” SERIES PIVOTING WHEEL FOR UNITS W/ECONOMIZERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 16 SPECIFICATIONS AND ELECTRICAL DATA - 3400 THROUGH 5600 CFM ERV’S . . . . . . . . . . . . . . . . . . . 15 4 UERV DIMENSIONAL DATA - 036 THROUGH 060 . 18 5 UERV DIMENSIONAL DATA - 037 THROUGH 150 (3 12 1/2 TONS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 17 SPECIFICATIONS AND ELECTRICAL DATA - 5500 THROUGH 6200 CFM ERV’S . . . . . . . . . . . . . . . . . . . 16 6 7 UERV DIMENSIONAL DATA - 180 THROUGH 300 (15 25 TONS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 MODEL UNIT VR074 AND VR122 (25 - 40 TON) . . . 20 Pg. # 8 UERV OUTSIDE AIR CFM SELECTION BY CFM . . . . 5 9 PERFORMANCE - 3 THROUGH 12 1/2 TON UNITS . . 7 10 PERFORMANCE - 15 THROUGH 25 TON UNITS . . . . 8 11 PERFORMANCE - PIVOTING WHEEL MODELS . . . . 9 12 SPECIFICATIONS AND ELECTRICAL DATA - 300 THROUGH 550 CFM ERV’S 11 2 19 BLOWER PERFORMANCE CHART - VR074 . . . . . . 21 20 BLOWER PERFORMANCE CHART - VR122 . . . . . . 21 21 FILTER SIZES - STAND ALONE ERV SERIES . . . . . 23 LIST OF TABLES Tbl. # 18 SPECIFICATIONS AND ELECTRICAL DATA - 6000 THROUGH 13000 CFM UERV’S . . . . . . . . . . . . . . . . 17 22 SPECIFICATIONS AND ELECTRICAL DATA - 300 THROUGH 1100 CFM ERV'S . . . . . . . . . . . . . . . . . . . 24 23 SPECIFICATIONS AND ELECTRICAL DATA - 1200 THROUGH 2000 CFM ERV'S . . . . . . . . . . . . . . . . . . . 25 24 SPECIFICATIONS AND ELECTRICAL DATA - 1200 THROUGH 2800 CFM ERV'S . . . . . . . . . . . . . . . . . . . 26 25 SPECIFICATIONS AND ELECTRICAL DATA - 2000 THROUGH 3600 CFM ERV'S . . . . . . . . . . . . . . . . . . . 27 Unitary Products Group 903106-UTG-A-0912 LIST OF TABLES (CONT.) Tbl. # 32 AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR D080 & D120 . . . . . . . . . . . . . . . . . . . . 35 Pg. # 26 SPECIFICATIONS AND ELECTRICAL DATA - 3000 THROUGH 4600 CFM ERV'S . . . . . . . . . . . . . . . . . . . 28 27 SPECIFICATIONS AND ELECTRICAL DATA - 4600 THROUGH 6200 CFM ERV'S . . . . . . . . . . . . . . . . . . . 29 28 SPECIFICATIONS AND ELECTRICAL DATA - 6000 THROUGH 13000 CFM ERV'S . . . . . . . . . . . . . . . . . . 30 29 AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR D11 & D20 . . . . . . . . . . . . . . . . . . . . . . 32 30 AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR D028 & D036 . . . . . . . . . . . . . . . . . . . . 33 31 AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR D046 & D062 . . . . . . . . . . . . . . . . . . . . 34 33 AIRFLOW PERFORMANCE - SIDE BY SIDE DUCT CONFIGURATION FOR S011 & S020 . . . . . . . . . . . . 37 34 AIRFLOW PERFORMANCE - SIDE BY SIDE DUCT CONFIGURATION FOR S028 & S036 . . . . . . . . . . . . 38 35 AIRFLOW PERFORMANCE - SIDE BY SIDE DUCT CONFIGURATION FOR S046 & S062 . . . . . . . . . . . . 39 36 AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR O011 & O020 . . . . . . . . . . . . . . . . . . . . 41 37 AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR 0028 & O036 . . . . . . . . . . . . . . . . . . . . 42 38 AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR O46 & O62 . . . . . . . . . . . . . . . . . . . . . . 43 UPG UERV MODEL NOMENCLATURE UPG UERV Model Nomenclature V R 028 A12 H 4 A L2 1 Product Generation Product Category 1 = First Generation V = Ventilator Additional Options Wheel Type Voltage R = Rooftop Stationary P = Rooftop Pivoting (036-060 & 078-150 only) CFM* 006 = 300 to 550 011 = 600 to 1000 020 = 1100 to 1700 028 = 2200 to 2800** 1500 to 2200** 036 = 2800 to 3600 046 = 3400 to 4600 062 = 5500 to 6200** 4800 to 5600** 074 = 6000 to 8000 122 = 8000 to 13000 2= 208/230v-3ph 4= 460v-3ph 5= 575v-3ph 9= 208/320v-1ph AA = No Options Installed L1 = Low Ambient Kit (LAK)* L2 = LAK & Motorized Outside Air (MOA)* L3 = LAK, MOA & Stop-Start-Job (SSJ) (not used on P models)* L4 = LAK, MOA, SSJ & Pressure Sensor (PS) (not used on P) L5 = LAK & SSJ (not used on P models)* L6 = LAK, SSJ & PS (not used on P models) L7 = LAK & PS L8 = LAK, MOA and PS M1 = Motorized Outside Air (MOA)* M2 = MOA, and Stop Start-Jog (SSJ) (not used on P models)* M3 = MOA, SSJ and Pressure Sensor (PS) (not used on P models) M4 = MOA and PS S1 = Stop-Start-Job (SSJ) (not used on P models)* S2 = SSJ and Pressure Sensor (PS) (not used on P models) P1 = Pressure Sensor (PS) UPG Rooftop Cabinet A06 = ZF/ZR/XP036-072 & ZS/ZK/XA -03 Thru -A6 A12 = 50” Models ZF/ZH/ZR/XP 102-150, ZJ078-150 & ZS/ZU/ZK/XA -08 Thru -12, ZW-06 Thru -12 B12 = 42” Models ZF/ZR/XP078-090, ZH037-090, ZJ/ZR037-061 ZS/ZK/XA -06 Thru -07, ZU-A3 Thru-07, ZW/ZK-A3 Thru -A5 A15 = Models ZF180 & ZS-15 A25 = Models ZF210-300, ZJ180-300, XP180-240 & ZS-18 Thru -25, ZW-15 Thru -25, XA-15, -20 A40 = Models Z42, Z33, Z34 & X42, X33, X34 25-40 Tons Duct Type A = No Selection on Rooftop Units * CFM is ERV wheel rating. This may vary depending on unit cabinet pressure drop. ** These CFM ranges are dependant upon blower motor selection. Blower Speed H = High Speed** M = Medium Speed** V = Variable Speed L = Constant Volume Unitary Products Group 3 903106-UTG-A-0912 APPLICATIONS Critical Terms for Standard 1060 are as follows: Unitized Energy Recovery Ventilators (UERV) are used with the UPG rooftop packaged units. The internal wheel provides sensible and latent energy exchange between the entering and exhaust air streams of a building. This allows a substantial amount of the energy, which is normally lost in the exhaust air stream to be returned into the entering air. Ideal applications are areas that have cold or hot temperatures, or areas that have high humidity or very low humidity (recover exhaust air from buildings that have humidifiers to add humidity). Application software is available to provide the energy and dollar savings for all areas of the United States and Canada. 1. Effectiveness. The measured energy recovery effectiveness not adjusted to account for that portion of the psychrometric change in the leaving supply air (Station 2) that is the result of leakage of entering exhaust air (Station 3) rather than exchange of heat or moisture between the air streams. 2. Net Effectiveness. The measured recovery effectiveness adjusted to account for that portion of the psychometric change in the leaving supply air (Station 2) that is the result of leakage of the entering exhaust air (Station 3) rather than exchange of heat or moisture between the air streams. 3. Exhaust Air Transfer Ratio (EATR). The tracer gas concentration difference between the leaving supply air (Station 2) and entering supply (outdoor) air stream (Station 1) divided by the tracer gas concentration in the entering exhaust (return) air (Station 3) at the 100% rated air-flow, expressed as a percentage. 4. Outdoor Air Correction Factor (OACF). The entering supply (outdoor) airflow (Station 1) divided by the measured (gross) leaving supply airflow (Station 2). PRINCIPLE OF OPERATION The UERV enthalpy wheel contains parallel layers of a polymeric material that are impregnated with silica gel (desiccant). The wheel is located in the entering (intake) air and exhaust air streams of the ventilation equipment. As the wheel rotates through each air stream, the wheel surface adsorbs sensible and latent energy. In the heating mode, the wheel rotates to provide a constant transfer of heat from the exhaust air stream to the colder intake air stream. During the cooling season, the process is reversed. On units equipped with an economizer (3 - 12.5 tons), the wheel pivots out of the air stream to allow economizer to operate normally for "free cooling" when outdoor temperature and humidity is acceptable. During economizer operation, the UERV exhaust blower continues to run, providing power exhaust for the system. The intake blower is de-energized during economizer operation. AHRI/ANSI STANDARD 1060-2005 FOR AIR-TO-AIR ENERGY RECOVERY VENTILATION EQUIPMENT The Air-Conditioning, Heating and Refrigeration Institute (AHRI) issued Standard 1060-2005 to certify air-to-air energy recovery ventilators. This standard deals specifically with the ratings of the Energy Recovery Wheel that is incorporated into the Energy Recovery Ventilator (ERV). All of the UPG ERV's have an AHRI certified energy recovery wheel. The data shown in the specification charts is the AHRI certified ratings for the wheel. Actual performance in the ERV may vary. ENERGY RECOVERY WHEEL The heart of the Energy Recovery Ventilator is the Energy Recovery Wheel (defined by AHRI as a rotary heat exchanger). The wheel has a patented design of parallel layers of wrapped polymeric material that is impregnated with a silica gel (desiccant). This unique design makes it the only truly cleanable wheel on the market today. The small wheels (30 inch diameter and smaller) are slide out cassettes, and the larger wheels have pie segments that are removable for cleaning. FIGURE 2 - ENERGY RECOVERY WHEEL FIGURE 1 - UNITIZED ENERGY RECOVERY VENTILATOR 4 Unitary Products Group 903106-UTG-A-0912 CROSS LEAKAGE IN UERV’S (PURGE SECTORS) The issue of cross leakage in rotary wheel based UERV's used in space conditioning applications is often misunderstood. As a result, many systems are installed with purge sectors and the additional fan capacity required to allow these sectors to function when in fact they are unnecessary. A better understanding of the rational for the purge sector, and its history, allows us to dispense with the purge sector, its added first cost and continuing cost of operation. A purge sector minimizes the carry over cross leakage from the exhaust into the supply (outside air) air stream by shunting a portion of the supply air back into the exhaust air stream across the seal separating the exhaust and supply. This is required in industrial applications where the exhaust carries contaminants. This typically results in air volume being 15% to 20% higher to get the desired air intake, and the cost associated with it. In space conditioning applications, where the ventilation is operating to maintain acceptable indoor air quality, there are no contaminants in concentrations large enough to cause concern. Cross leakage in the UERV system results in a small amount of the exhaust air, typically less than 5% in balanced airflow, returning to the space. This is not contaminated air, as some would suggest. It is however air that effectively never left the space. The operation cost of moving this air is far less than that required for a purge sector. Do not use the UPG UERV's in applications that have concentrations of contaminants. TABLE 1: UERV OUTSIDE AIR CFM SELECTION BY CFM Unit-Tons 300-550 600-1000 1.5 - 6 1.5 - 6 7.5 - 12.5 1100-1700 1500-2800 2800-3600 3400-4600 4800-5600 5500-6200 6000-8000 8000-13000 25 - 40 30 - 40 Stand Alone type ERV’s are available for all tonnage sizes. 7.5 - 12.5 7.5 - 12.5 Rooftop 15 - 25 15 - 25 15 - 25 15 - 25 15 - 25 Stand Alone ERV’s are available for equipment room applications. OPTIONAL ACCESSORIES - FIELD INSTALLED match the specified unit. See specification pages for required curb. Must be ordered separately from UERV. UERV Equipment Support - 8 inch (203 mm) high base for support of the exhaust and intake end of the UERV. Must be ordered separately from the UERV. Stand Alone Balancing Damper - Balancing dampers are used with VO and VS models when ERV is connected to the rooftop unit, not to ductwork on the roof. UERV VR006 VR/P011 VR/P020 VR/P028 UERV VR036 VR046 VR062 VR074 VR122 Equipment Support Part No. 1ES0401 1ES0402 1ES0402 1ES0402 Equipment Support Part No. 1ES0403 1ES0403 1ES0404 Roof Curb - A 14 or 24 inch (355 or 610 mm) roof curb is required to match supply and exhaust openings of the UERV with the rooftop units. UPG provides a full line of roof curbs to Unitary Products Group 5 903106-UTG-A-0912 OPTIONAL ACCESSORIES - FACTORY INSTALLED L6 - LAK, SSJ, and PS L7 - LAK and PS L8 - LAK, MOA, and PS Low Ambient Control Kit - Prevents frost formation on energy wheel heat transfer surfaces by terminating the intake blower operation when discharge air temperature falls below a field selectable temperature setting. Intake blower operation resumes operation after temperature rises above the adjustable temperature differential. Pressure Sensor - Measurement device on the UERV to determine airflow across the Wheel. M1 - Motorized Outside Air (MOA) * M2 - MOA and Stop-Start-Jog (SSJ) * M3 - MOA, SSJ, and Pressure Sensor (PS) M4 - MOA and PS S1 - Stop-Start-Jog (SSJ) * S2 - SSJ and Pressure Sensor (PS) P1 - Pressure Sensor (PS) NOTE: Motorized Intake Air Damper - Damper mounts in the outdoor air intake hood. It opens when the UERV is energized and closes when de-energized. Stop-Start-Jog - Function that rotates the Enthalpy Wheel (non-pivoting models) on a preset timer to prevent contamination of the wheel during economizer operation. * denotes only options available for VR074 & VR122. HOW TO SELECT THE PROPER AIR CONDITIONING UNIT AND UNITARY ENERGY RECOVERY VENTILATOR 1. Determine the air conditioning load requirements with the required amount of outside air without an UERV. ERV Option Codes (ex.: VR028A12H4AL3 would be an R28 series high speed 460 volt UERV with a Low Ambient kit, Motorized Outside Air, and Stop-Start-Jog kit.) 2. Select the proper UERV for the outside air CFM requirements and calculate the tonnage reduction through the UST or UERV software programs. L1 - Low Ambient Kit (LAK) * 3. Select the air conditioning unit required by reducing the load determined in step 1 by the reduction in step 2. (Example: If the load in Step 1 was 10 tons, and the reduction in Step 2 was 2.5 tons, select a 7.5 ton unit.) 4. Select the proper UERV based on the selected unit. SEE Page 3 UERV Nomenclature for Details L2 - LAK & Motorized. Outside Air (MOA) * L3 - LAK, MOA, & Stop-Start-Jog (SSJ) * L4 - LAK, MOA, SSJ, & Pressure Sensor (PS) L5 - LAK and SSJ * 6 Unitary Products Group 903106-UTG-A-0912 TABLE 2: PERFORMANCE - 3 THROUGH 12 1/2 TON UNITS “R” Series Stationary Wheel for Units without Economizers UPG Unit Size Packaged Unit (Tons) Model No. ZF036-072 ZR036-060 XP036-060 ZS-03-A6 ZK-03-05 XP-03-05 (42”) ZH037-090 ZF078-090 ZJ037-061 ZR037-090 ZU-A3-07 ZS-06-07 ZW-A3-A5 ZK-A3-07 (50”) ZF102-150 ZH102-150 ZJ078-150 XP102-150 ZR102-150 ZS-08-12 ZU-08-12 ZW-06-12 XA-08-12 ZK-08-12 Nominal AHRI Data (Total ERV CFM Range 300-550 Matching ERV Model VR006A06H 3-6 600-1000 300-550 3 - 7.5 600-1000 1100-1700 600-1000 1100-1700 VR011A06H VR006B06H VR011B12H VR020B12H VR011A12H VR020A12H 6.5 - 12.5 1500-2200 2200-2800 VR028A12M VR028A12H Voltage & Phase Voltage Code 110v-1ph 1 208/230v-1ph 9 208/240v-3ph 2 460v-3ph 4 208/230v-1ph 9 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 CFM Net Effectiveness Heating Cooling 500 65% 64% 900 73% 72% 500 65% 64% 900 73% 72% 1600 65% 64% 900 73% 72% 1600 65% 64% 1950 71% 70% 2600 65% 63% Note 1: Complete UPG ERV model number includes the electrical information. Example ZF 060 needing 500 CFM outside of air at 230 volts/3 phase. Model would be a VR006A06H2AAA1. Unitary Products Group 7 903106-UTG-A-0912 TABLE 3: PERFORMANCE - 15 THROUGH 25 TON UNITS Use this table to determine ventilation and size requirements. Table shows UPG packaged units and matching ERV model, Air Flow Range, and AHRI rated Net Effectiveness at 100% of rated CFM. “R” Series Stationary Wheel for Units without Economizers Nominal AHRI Data (Total UPG Unit ERV CFM Matching ERV Voltage & Voltage Packaged Unit Size Net Effectiveness Range Model Phase Code CFM Model No. (Tons) Heating Cooling 208/230v-3ph 2 1500-2200 VR028A25H 460v-3ph 4 1950 71% 70% 575v-3ph 5 208/230v-3ph 2 2200-2800 VR028A25H 460v-3ph 4 2600 65% 63% 575v-3ph 5 ZF180 208/230v-3ph 2 ZJ180 2800-3600 VR036A15H 460v-3ph 4 3100 65% 63% ZR180 575v-3ph 5 XP180 15 ZS-15 208/230v-3ph 2 ZW-15 3400-4600 VR046A15H 460v-3ph 4 3900 65% 63% ZK-15 575v-3ph 5 XA-15 208/230v-3ph 2 4800-5600 VR062A25M 460v-3ph 4 4125 71% 70% 575v-3ph 5 208/230v-3ph 2 5500-6200 VR062A25H 460v-3ph 4 5500 65% 63% 575v-3ph 5 208/230v-3ph 2 2200-2800 VR028A25H 460v-3ph 4 2600 65% 63% 575v-3ph 5 208/230v-3ph 2 2800-3600 VR036A25H 460v-3ph 4 3100 65% 63% ZJ210-300 ZR240-300 575v-3ph 5 ZF210-300 208/230v-3ph 2 XP240 VR046A25H 460v-3ph 4 3900 65% 63% 17.5 - 25 3400-4600 ZW-18-25 575v-3ph 5 ZK-20-25 208/230v-3ph 2 ZF-18-25 XA-20 4800-5600 VR062A25M 460v-3ph 4 4125 71% 70% 575v-3ph 5 208/230v-3ph 4 5500-6200 VR062A25H 460v-3ph 5 5500 65% 63% 575v-3ph 2 208/230v-3ph 2 Z42 6000-8000 VR074A40* 460v-3ph 4 6600 65% 63% Z33 575v-3ph 5 Z34 25-40 X42 208/230v-3ph 2 X33 8000-13000 VR122A40* 460v-3ph 4 10800 65% 63% X34 575v-3ph 5 8 Note 1: Complete UPG ERV model number includes the electrical information. Example: ZJ180 needing 2800 CFM outside of air at 230 volts/3 phase. Model would be a VR028A15H2AAA1. Note 2: For VR074 and VR122 units used with an economizer must have the Start-Stop-Jog (SSJ) option. Unitary Products Group 903106-UTG-A-0912 TABLE 4: PERFORMANCE - PIVOTING WHEEL MODELS “P” Series Pivoting Wheel for Units with Economizers UPG Packaged Unit Model No. ZF036-072 ZR036-060 XP036-060 ZS-03-A6 ZK-03-05 XA-03-05 (42”) ZH037-090 ZF078-090 ZJ037-061 ZR037-090 XP078-090 ZU-A3-07 ZS-06-07 ZW-A3-A5 ZK-A3-07 XA-06-07 Unit Size (Tons) 3-6 ERV CFM Range 6001000 6001000 Max. CFM Power Exhaust 1900 1900 Matching ERV Model VP011A06H VP011B12H 3 - 7.5 11001700 6001000 (50”) ZF102-150 ZH102-150 ZJ078-150 ZR102-150 XP102-150 ZS-08-12 ZU-08-12 ZW-06-12 ZK-08-12 XA-08-12 11001700 3000 1900 3000 22002800 3450 4200 Voltage Code 208/230v-1ph 9 208/240v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 VP020B12H VP011A12H VP020A12H 6.5 12.5 15002200 Nominal AHRI Data (Total Voltage & Phase VP028A12M VP028A12H 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 208/230v-3ph 2 460v-3ph 4 575v-3ph 5 CFM Net Effectiveness Heating Cooling 900 73% 72% 900 73% 72% 1600 65% 64% 900 73% 72% 1600 65% 64% 1950 71% 70% 2600 65% 63% Note 1: Complete UPG ERV model number includes the electrical information. Example ZF 060 needing 800 CFM outside of air at 230 volts/3 phase. Model would be a VP011A06H2AAA1. 2: Models ZF/ZH/ZJ/XP* 037-150 & ZS/ZU/ZW/ZK/XA -A3-12 with ERV must use “slab” type economizers and downflow position. Unitary Products Group 9 903106-UTG-A-0912 Enthalpy Wheel Fresh Air Damper Pivoted out of Intake and Discharge Air Stream (opens during economizer operation) Outside Air Blower (energized) Exhaust Air Blower (energized) Enthalpy Wheel (with removable pie segments) Exhaust Air Blower Unit & UERV Disconnect (provided correct wire size used for both units and local code approval) FIGURE 3 - “P” SERIES PIVOTING WHEEL FOR UNITS W/ECONOMIZERS 10 Unitary Products Group 903106-UTG-A-0912 TABLE 5: SPECIFICATIONS AND ELECTRICAL DATA - 300 THROUGH 550 CFM ERV’S Model Numbers Line Voltage - 60hz Motor - hp / type Wheel Size (dia x width) - in Motor Speed - rpm Fresh Air Motor Speed(s) Blower Bearing Type Full Load Amps Service Factor Motor - hp Wheel Size (dia x width) - in Motor Speed - rpm Exhaust Air Motor Speed(s) Blower Bearing Type Full Load Amps-Stationary Service Factor Potential Volts Wheel Electrical Motor Speed (RPM)/Wheel (RPM) Data Full Load Amps MCA Total Electrical OCPD Wheel Depth Wheel Wheel Diameter Data Construction / Media Type Nominal Airflow CFM EATR - -0.50 H2O EATR - 0.00 H2O Enthalpy Wheel AHRI EATR - +0.50 H2O Rating Data OACF - -0.50 H2O OACF - 0.00 H2O OACF - +0.50 H2O Thermal Ratings @ 0” Pressure Diff. 100% Airflow Heating 75% Airflow Heating Total Effectiveness 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating Net Effectiveness 100% Airflow Cooling 75% Airflow Cooling Curb A/C Unit Curb Height - in Shipping Weight - lbs. Weights Net Weight - lbs. VR006 - Rooftop Stationary 115v-1ph Sensible 68% 73% 68% 73% 68% 73% 68% 73% 208/230v/460-1ph 208/230v/460-3ph 0.25 / PSC 5.5 x 6.3 1780 2 Sleeve 3.8 1.1 0.25 / PSC 5.5 x 6.3 1780 2 Sleeve 3.8 1.1 115 1050/68 0.7 8.7 10 2 19.3 One Piece / Polymeric 500 @ .6 9.90% 0.20% 0.00% 1.02% 1.33 1.59% Latent 60% 65% 60% 65% 60% 65% 60% 65% 14 198 155 Total 65% 70% 64% 69% 65% 70% 64% 69% Note: 1: A stepdown transformer is provided to stepdown high voltage primary to 115 volt secondary. Unitary Products Group 11 903106-UTG-A-0912 TABLE 6: SPECIFICATIONS AND ELECTRICAL DATA - 600 THROUGH 1700 CFM ERV’S VR011 - Rooftop Stationary VP011 - Rooftop Pivoting Model Numbers Line Voltage - 60hz Motor - hp / type Wheel Size (dia x width) - in Motor Speed - rpm Fresh Air Motor Speed(s) Blower Bearing Type Full Load Amps Service Factor Motor - hp Stationary Motor - hp Pivoting Wheel Size (dia x width) - in Exhaust Motor Speed - rpm Air Motor Speed(s) Blower Bearing Type Full Load Amps-Stationary Full Load Amps-Pivoting Service Factor Potential Volts Wheel Motor Speed (RPM)/Wheel Electrical (RPM) Data Full Load Amps MCA - Stationary Total OCPD - Stationary Electrical MCA - Pivoting OCPD - Pivoting Wheel Depth - in Wheel Diameter - in Data Construction / Media Type Nominal Airflow CFM EATR - -1.00 H2O Enthalpy EATR - 0.00 H2O Wheel AHRI EATR - +1.00 H2O Rating OACF - -1.00 H O 2 Data OACF - 0.00 H2O OACF - +1.00 H2O Thermal Ratings @ 0” Pressure Diff. 100% Airflow Heating Total Effec- 75% Airflow Heating tive100% Airflow Cooling ness 75% Airflow Cooling 100% Airflow Heating Net Effec- 75% Airflow Heating tive100% Airflow Cooling ness 75% Airflow Cooling Curb A/C Unit Curb Height - in Shipping Weight - lbs. Weights Net Weight - lbs. 208/ 230v-1ph 3.4 3.4 VR020 - Rooftop Stationary VP020 - Rooftop Pivoting 208/ 230v-3ph 460v- 1ph 460v-3ph .5 / PSC 10 x 6 AT 1120 / 960 / 850 3 Sleeve 3.4 1 .5 / PSC .5 / PSC 10 x 6 AT 1120 / 960 / 850 3 Sleeve 3.4 1.5 1.5 3.4 1.5 1.5 1 208 / 230 208/230v-3ph 460v-3ph 575v-3ph 1.0 / Belt 9x9 1725 Adjustable Sheave Ball 3.8 1.9 1.4 1.15 1.0 / Belt 1.5 / Belt 9x9 1725 Adjustable Sheave Ball 3.8 1.9 1.4 5.6 2.8 2.0 1.15 208 / 230 1050/56 8.25 10 8.25 10 Sensible 76% 81% 76% 81% 76% 81% 76% 81% 1050/46 0.3 8.25 4.4 10 6 8.25 4.4 10 6 3 25.3 Segmented / Polymeric 900 @ 1.0 9.30% 0.70% 0.00% 0.97% 1.19% 1.34% Latent 68% 73% 68% 73% 68% 73% 68% 73% 14 318 245 4.4 6 4.4 6 Total 73% 78% 72% 76% 73% 78% 72% 76% 0.3 4.58 3.45 6 5 5.7 4.2 8 6 3 30.346 Segmented / Polymeric 1600 @ .95 8.85 12 11.1 15 Sensible 68% 72% 68% 72% 68% 72% 68% 72% 7.80% 0.40% 0.00% 0.97% 1.16% 1.29% Latent 61% 67% 61% 67% 61% 67% 61% 67% 14 425 345 Total 65% 71% 64% 70% 65% 71% 64% 70% Note: 1. Pivoting electrical data applies to VP models only. 12 Unitary Products Group 903106-UTG-A-0912 TABLE 7: SPECIFICATIONS AND ELECTRICAL DATA - 1500 THROUGH 2800 CFM ERV’S * VR028 - Rooftop Stationary * VP028 - Rooftop Pivoting Model Numbers Line Voltage - 60hz 208/230v-3ph Motor - hp / type Wheel Size (dia x width) - in Motor Speed - rpm Motor Speed(s) Bearing Type Full Load Amps Service Factor Motor - hp Stationary Motor - hp Pivoting Wheel Size (dia x width) - in Motor Speed - rpm Motor Speed(s) Bearing Type Full Load Amps-Stationary Full Load Amps-Pivoting Service Factor Motor - hp (1 phase) Potential Volts Motor Speed (RPM)/Wheel (RPM) Full Load Amps MCA - Stationary OCPD - Stationary MCA - Pivoting OCPD - Pivoting Wheel Depth x Diameter - in Construction / Media Type Nominal Airflow CFM EATR - -1.00 H2O Fresh Air Blower Exhaust Air Blower Wheel Electrical Data Total Electrical Wheel Data Enthalpy Wheel AHRI Rating Data Total Effectiveness Net Effectiveness Curb Weights EATR - 0.00 H2O EATR - +1.00 H2O OACF - -1.00 H2O OACF - 0.00 H2O OACF - +1.00 H2O Thermal Ratings @ 0” Pressure Diff. 100% Airflow Heating 75% Airflow Heating 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating 100% Airflow Cooling 75% Airflow Cooling A/C Unit Curb Height - in Shipping Weight - lbs. Net Weight - lbs. 5.6 5.6 9 13.2 20 17.5 25 Sensible 68% 74% 68% 74% 68% 74% 68% 74% 460v-3ph 575v-3ph 1.5 / Belt 10 x 10 1725 Adjustable Sheave Ball 2.8 2 1.15 1.5 / Belt 3 / Belt 10 x 10 1725 Adjustable Sheave Ball 2.8 2 4.4 3.6 1.15 0.17 200-208 / 230 825/58 0.6 6.9 5.1 10 7 8.9 7.1 12 10 3 x 37.759 Segmented Pies / Polymeric 2600 @ .95 6.10% 0.40% 0.00% 0.99% 1.13% 1.23% Latent 60% 67% 60% 67% 60% 67% 60% 67% 14 470 395 Total 65% 71% 63% 70% 65% 71% 63% 70% * Electric data is for (A12) ZH/ZF/ZJ 078-150 and XP 078-150 only. ** Electric data is for (A15 and A25) ZH/ZF/ZJ 180-300 and XP 180 and 240 only. Note: Pivoting electrical data applies to VP models only. Unitary Products Group 13 903106-UTG-A-0912 TABLE 8: SPECIFICATIONS AND ELECTRICAL DATA - 2800 THROUGH 3600 CFM ERV’S Model Numbers Line Voltage - 60hz Fresh Air Blower Exhaust Air Blower Wheel Electrical Data Total Electrical Wheel Data VR036 - Rooftop Stationary 208/230v-3ph Motor - hp / type Wheel Size (dia x width) - in Motor Speed - rpm Motor Speed(s) Bearing Type Full Load Amps Service Factor Motor - hp Stationary Wheel Size (dia x width) - in Motor Speed - rpm Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor Motor - hp (1 phase) Potential Volts Motor Speed (RPM)/Wheel (RPM) Full Load Amps MCA - Stationary OCPD - Stationary Wheel Depth x Diameter - in Construction / Media Type Nominal Airflow CFM EATR - -1.00 H2O EATR - 0.00 H2O EATR - +1.00 H2O OACF - -1.00 H2O OACF - 0.00 H2O OACF - +1.00 H2O Thermal Ratings @ 0” Pressure Diff. 100% Airflow Heating 75% Airflow Heating Total Effectiveness 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating Net Effectiveness 100% Airflow Cooling 75% Airflow Cooling Curb A/C Unit Curb Height - in Shipping Weight - lbs. Weights Net Weight - lbs. 7.0 7.0 16.4 25 460v-3ph 575v-3ph 2 / Belt 12 x 9 1725 Adjustable Sheave Ball 3.5 3.2 1.15 3 / Belt 12 x 9 1725 Adjustable Sheave Ball 3.5 3.2 1.15 0.50 200-208 / 230 1725/64 1.2 8.6 6.6 12 9 3 x 41.825 Segmented Pies / Polymeric 3100 @ .9 Enthalpy Wheel AHRI Rating Data 14 Sensible 68% 74% 68% 74% 68% 74% 68% 74% 4.90% 1.30% 0.30% 0.99% 1.07% 1.12% Latent 60% 67% 60% 67% 60% 67% 60% 67% 24 On A15 Or A25 571 475 Total 65% 71% 63% 70% 65% 71% 63% 70% Unitary Products Group 903106-UTG-A-0912 TABLE 9: SPECIFICATIONS AND ELECTRICAL DATA - 3400 THROUGH 5600 CFM ERV’S Model Numbers Line Voltage - 60hz Motor - hp / type Wheel Size (dia x width) - in Motor Speed - rpm Motor Speed(s) Bearing Type Full Load Amps Service Factor Motor - hp Stationary Wheel Size (dia x width) - in Motor Speed - rpm Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor Motor - hp (1 phase) Potential Volts Motor Speed (RPM)/Wheel (RPM) Full Load Amps MCA - Stationary OCPD - Stationary Wheel Depth x Diameter - in Construction / Media Type Nominal Airflow CFM EATR - -1.00 H2O Fresh Air Blower Exhaust Air Blower Wheel Electrical Data Total Electrical Wheel Data Enthalpy Wheel AHRI Rating Data Total Effectiveness Net Effectiveness Curb Weights VR046 - Rooftop Stationary 208/230v-3ph EATR - 0.00 H2O EATR - +1.00 H2O OACF - -1.00 H2O OACF - 0.00 H2O OACF - +1.00 H2O Thermal Ratings @ 0” Pressure Diff. 100% Airflow Heating 75% Airflow Heating 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating 100% Airflow Cooling 75% Airflow Cooling A/C Unit Curb Height - in Shipping Weight - lbs. Net Weight - lbs. Unitary Products Group 9.4 9 22 30 Sensible 68% 73% 68% 73% 68% 73% 68% 73% 460v-3ph 575v-3ph 3 / Belt 12 x 12 1725 Adjustable Sheave Ball 4.3 3.4 1.15 3 / Belt 12 x 12 1725 Adjustable Sheave Ball 4.4 3.6 1.15 0.5 200-208 / 230 1075/57 1.2 11 9.1 15 12 3 x 46.776 Segmented Pies / Polymeric 3900 @ .95 4.40% 1.10% 0.20% 0.99% 1.06% 1.11% Latent 60% 67% 60% 67% 60% 67% 60% 67% 24 On A15 Or A25 920 805 Total 65% 71% 63% 70% 65% 71% 63% 70% 15 903106-UTG-A-0912 TABLE 10: SPECIFICATIONS AND ELECTRICAL DATA - 5500 THROUGH 6200 CFM ERV’S Model Numbers Line Voltage - 60hz Fresh Air Blower Exhaust Air Blower Wheel Electrical Data Total Electrical Wheel Data Motor - hp / type Wheel Size (dia x width) - in Motor Speed - rpm Motor Speed(s) Bearing Type Full Load Amps Service Factor Motor - hp Stationary Wheel Size (dia x width) - in Motor Speed - rpm Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor Motor - hp (1 phase) Potential Volts Motor Speed (RPM)/Wheel (RPM) Full Load Amps MCA - Stationary OCPD - Stationary Wheel Depth x Diameter - in Construction / Media Type Nominal Airflow CFM EATR - -1.00 H2O EATR - 0.00 H2O Enthalpy Wheel AHRI EATR - +1.00 H2O Rating Data OACF - -1.00 H2O OACF - 0.00 H2O OACF - +1.00 H2O Thermal Ratings @ 0” Pressure Diff. 100% Airflow Heating 75% Airflow Heating Total Effectiveness 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating Net Effectiveness 100% Airflow Cooling 75% Airflow Cooling Curb A/C Unit Curb Height - in Shipping Weight - lbs. Weights Net Weight - lbs. 16 VR062 - Rooftop Stationary 208/230v-3ph 460v-3ph 575v-3ph 5 / Belt 12 x 12 1725 Adjustable Sheave Ball 15 7.4 5.8 1.15 5 / Belt 12 x 12 1725 Adjustable Sheave Ball 14.8 7 5.1 1.15 0.5 200-208 / 230 1075/54 1.2 34.8 17.5 13.6 40 25 20 3 x 52.026 Segmented Pies / Polymeric 5500 @ .95 Sensible 68% 73% 68% 73% 68% 73% 68% 73% 4.00% 1.00% 0.20% 0.99% 1.06% 1.10% Latent 60% 67% 60% 67% 60% 67% 60% 67% 24 On A15 Or A25 1250 1075 Total 65% 71% 63% 70% 65% 71% 63% 70% Unitary Products Group 903106-UTG-A-0912 TABLE 11: SPECIFICATIONS AND ELECTRICAL DATA - 6000 THROUGH 13000 CFM UERV’S UERV Series Line Voltage - 60hz Motor - hp Wheel Size (dia x width) - in Motor Speed - rpm Exhaust Air Motor Speed(s) Blower Bearing Type Full Load Amps OCPD Service Factor Motor - hp (3 phase) Motor Speed (RPM)/Wheel Wheel Electrical (RPM) Data Full Load Amps OCPD MCA Total Electrical OCPD Wheel Depth x Diameter - in Wheel Data Construction / Media Type Nominal Airflow CFM EATR - -1.00 H2O Enthalpy EATR - 0.00 H2O Wheel EATR - +1.00 H2O Airflow Data OACF - -1.00 H O 2 OACF - 0.00 H2O OACF - +1.00 H2O Thermal Ratings @ 0” Pressure Diff. 100% Airflow Heating Total 75% Airflow Heating Effective100% Airflow Cooling ness 75% Airflow Cooling 100% Airflow Heating Net 75% Airflow Heating Effective100% Airflow Cooling ness 75% Airflow Cooling Curb A/C Unit Curb Height - in Shipping Weight - lbs. Weights Net Weight - lbs. Unitary Products Group VR074 460v-3ph (2) 5 / Belt (2) 12 x 12 1725 Adjustable Sheave Ball 7 9 1.15 0.25 VR122 208/230v-3ph 575v-3ph 208/230v-3ph 575v-3ph 14.8 20 5 7 22.4 30 7.8 10 0.25 0.25 0.25 460v-3ph (2) 7.5 / Belt (2) 15 x 15 1725 Adjustable Sheave Ball 9.7 15 1.15 0.25 850/49 2.5 3 34.9 50 850/51 1.2 0.95 2 2 16.6 12.7 20 15 3 x 58 Segmented Pies / Polymeric 6600 @ .95 Sensible 68% 73% 68% 73% 68% 73% 68% 73% 4.60% 1.90% 0.90% 0.99% 1.05% 1.09% Latent 60% 67% 60% 67% 60% 67% 60% 67% 14 2800 2600 0.25 Total 65% 71% 63% 70% 65% 71% 63% 70% 2.5 3 52 70 1.2 0.95 2 2 22.6 19 30 25 3 x 74 Segmented Pies / Polymeric 10800 @ .95 Sensible 68% 73% 68% 73% 68% 73% 68% 73% 3.40% 1.20% 0.40% 0.99% 1.04% 1.07% Latent 60% 67% 60% 67% 60% 67% 60% 67% 14 3000 2800 Total 65% 71% 63% 70% 65% 71% 63% 70% 17 903106-UTG-A-0912 Models ZF036-072 ZR036-060 XP036-060 ZS-03-A6 ZK-03-05 XA-03-05 A C D B Intake Air Blower 14" High Curbs Required - -1RC0434 Enthalpy Wheel ERV Model Unit Size VR006A06H 036-072 -03 -A6 A 24.75 (629) B 24.63 (624) C 37.9 6 (964) D 8 (203) CFM VR011A06H 036-072 -03 -A6 32.13 (816) 33.5 (851) 48.75 (1238) 8 (203) 600-1000 VP011A06H 036-072 -03 -A6 32.13 (816) 33.5 (851) 48.75 (1238) 8 (203) 600-1000 Exhaust Blower 300-550 FIGURE 4 - UERV DIMENSIONAL DATA - 036 THROUGH 072 & -03 THROUGH -A6 (3-6 TONS) Models ZH037, 049, 061, 078, 090, 102, 120, 150 ZF078, 090, 102, 120, 150 ZR037, 049, 061, 078, 090, 102, 120, 150 XP078, 090, 102, 120, 150 ZU-A3, -A4, -A5, -06, -07, -08, -10, -12 ZS-06, -07, -08, -10, -12 ZK-A3, -A4, -A5, -06, -07, -08, -10, -12 XA-06, -07, -08, -10, -12 D B 14" High Curbs Required on "VR06" - 1RC0471 14" High Curbs Required on "VR011" & "VP011" - 1RC0471 14" High Curbs Required on "VR020" & "VP020" - 1RC0476 14" High Curbs Required on "VR028" & "VP028" - 1RC0476 Model Number VR006B12H VR011B12H VP011B12H VR020B12H VP020B12H VR011A12H VP011A12H VR020A12H VP020A12H VR028A12M VP028A12M VR028A12H VP028A12H Unit Size 037-061 -A3 -A5 A C Outdoor Air Intake Blower Exhaust Blower 078-102 -06 -08 078-102 -06 -08 090-150 -07 -12 090-150 -07 -12 090-150 -07 -12 A 24.75 (629) 32.13 (816) 37.25 (946) 32.13 (816) B 24.63 (624) 33.5 (851) 37.5 (953) 33.5 (851) C 37.9 (9 44.75 (1137) 60.38 (1533) 44.75 (1137) D 8 (203) 11 (279) 20.32 (516) 11 (279) 37.25 (946) 42.63 (1083) 37.5 (953) 43.56 (1106) 60.38 (1533) 64.25 (1631) 20.32 (516) 18.32 (466) 090-150 -07 -12 42.63 (1083) 43.56 (1106) 64 25 (1631) 18.32 (466) CFM 300-550 Enthalpy Wheel Optional Equipment Support 600-1000 1100-1700 600-1000 1100-1700 1500-2200 2200-2800 FIGURE 5 - UERV DIMENSIONAL DATA - 037 THROUGH 150 & A3 THROUGH -12 (3 - 12 1/2 TONS) 18 Unitary Products Group 903106-UTG-A-0912 Models ZF180, 210, 240, 300 ZR180, 240, 300 ZJ180, 210, 240, 300 XP180, 240 ZS-15, -18, -20, -25 ZK-15, -20, -25 ZW-15, -18, -20, -25 XA-15, -20 Outdoor Air Intake Blower Enthalpy Wheel A C B 14" Roofcurbs Required on "VR028" - 1RC0436 - 437 24" High Curbs Required on "VR036" - 1RC0477 or 1RC0478 24" High Curbs Required on "VR046" - 1RC0477 or 1RC0478 24" High Curbs Required on "VR062" - 1RC0477 or 1RC0478 Model Number VR028A15M VR028A15H VR028A25M VR036A15H VR036A25H VR046A15H VR046A25H VR062A15M VR062A25M VR062A15H VR062A25H NOTE: Exhaust Blower Unit Size A B C D 180, -15 42.63 (1083) 43.56 (1106) 52.13 (1327) 22.50 (572) 46.68 (1186) 52.68 (1338) 58.88 (1496) 58.88 (1496) 57.38 (1457) 57.38 (1457) 57.38 (1457) 57.38 (1457) 60.00 (1524) 60.00 (1524) 60.00 (1524) 60.00 (1524) 30.50 (775) 30.50 (775) 30.50 (775) 30.50 (775) 180-300, -15-25 180, -15 180-300, -15-25 180-300, -15-25 180-300, -15-25 180, -15 180-300, -15-25 180, -15 180-300, -15-25 D CFM 1500-2200 2200-2800 2800-3600 3400-4600 4800-5600 5500-6200 Refer to Unit Price Pages for exact unit, ERV and curb matchup. FIGURE 6 - UERV DIMENSIONAL DATA - 180 THROUGH 300 & -15 THROUGH -25 (15 - 25 TONS) Unitary Products Group 19 903106-UTG-A-0912 Models Z42, X42 Z33, X33 Z34, X34 82.13 74.75 24.59 20.92 61.23 - Designed to meet unit specifications - 14’ High Curbs Required - Rooftop unit blower exceeds the capacity of the ERV Exhaust Blowers Model Number VR074A40L VR074A40V VR122A40L VR122A40V CFM 6000 - 8000 6000 - 8000 8000 - 13000 8000 - 13000 Description Constant Volume Variable Air Volume Constant Volume Variable Air Volume - See blower performance charts for airflow at various external static pressures. FIGURE 7 - MODEL UNIT VR074 AND VR122 (25 - 40 TON) 20 Unitary Products Group 903106-UTG-A-0912 TABLE 12: BLOWER PERFORMANCE CHART - VR074 CFM 6000 6500 7000 7500 8000 Exhaust Blower RPM for VR074, (2) 5HP, Barometric Hood External Static Pressure (in water) 0 0.5 1 1.5 910 1060 1200 1300 955 1095 1225 1360 1000 1130 1260 1380 1040 1170 1290 1400 1080 1200 1315 1425 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only 2 1400 1430 1475 1500 1530 RPM Range Low 910-1320 Standard Unit High 1325-1565 Optional Kit (01-KIT-RH58) TABLE 13: BLOWER PERFORMANCE CHART - VR122 CFM 8000 9000 10000 11000 12000 13000 Exhaust Blower RPM for VR122, 7.5HP, Barometric Hood External Static Pressure (in water) 0 0.5 1 1.5 775 900 1030 1125 825 945 1055 1150 875 985 1090 1190 925 1030 1125 1215 970 1070 1165 1250 1015 1110 1200 1280 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Unitary Products Group 2 1200 1240 1280 1310 1355 1360 RPM Range Low 775-1000 Standard Unit Med 1000-1200 Optional Kit (01-KIT-RM74) High 1175-1375 Optional Kit (01-KIT-RH74) 21 903106-UTG-A-0912 UPG UERV STAND ALONE MODEL NOMENCLATURE UPG UERV Model Nomenclature V D 011 N00 H 4 A AA 2 Product Generation Product Category 2 = Second Generation V = Ventilator Additional Options Wheel Type Voltage D = Stand Alone, Down Discharge O = Stand Alone, Over and Under S = Stand Alone, Side by Side 1 = 110v - 1ph 2 = 208/230v - 3ph 4 = 460v - 3ph 5 = 575v - 3ph 8 = 440v-1ph 9 = 208/320v - 1ph CFM* 011 = 300 to 1100 020 = 1200 to 2000 028 = 1200 to 2800 036 = 2000 to 3600 046 = 3000 to 4600 062 = 4600 to 6200 080 = 6000 to 8000 120 = 8000 to 13000 Stand Alone N00 = None Blower Speed H = High Speed** M = Medium Speed** V = Variable Speed L = Constant Volume AA = No Options Installed L1 = Low Ambient Kit (LAK) L2 = LAK & Motorized Outside Air (MOA) L3 = LAK, MOA & Stop-Start-Job (SSJ) L4 = LAK, MOA, SSJ & Pressure Sensor (PS) L5 = LAK & SSJ L6 = LAK, SSJ & PS (not used on P models) L7 = LAK & PS L8 = LAK, MOA and PS M1 = Motorized Outside Air (MOA) M2 = MOA, and Stop Start-Jog (SSJ) M3 = MOA, SSJ and Pressure Sensor (PS) M4 = MOA and PS S1 = Stop-Start-Job (SSJ) S2 = SSJ and Pressure Sensor (PS) P1 = Pressure Sensor (PS) Duct Type A = No Selection on Rooftop Units * CFM is ERV wheel rating. This may vary depending on unit cabinet pressure drop. ** These CFM ranges are dependant upon blower motor selection. The choice of H and M options are only available on the V*028 and V*062 models. Note: SSJ (Start-Stop-Jog) option is required for economizer equipped units. PERFORMANCE - ERV SERIES Use this table to determine ventilation and size requirements. Table shows ERV Air Flow Range. AHRI certified performance rating provided in specifications and electrical data Effectiveness. "xL", "xM" and "xH" signify low, medium and high speed. ERV CFM Range 300-1100 1200-2000 1200-2800 2000-3600 3000-4600 4600-6200 6000-8000 8000-13000 Series D O S 22 ERV Series D011,O011,S011 D020,O020,S020 D028,O028,S028 D036,O036,S036 D046,O046,S046 D062,O062,S062 D080 D120 ERV Series Descriptions Description Down Discharge Outdoor Application Stand alone outdoor application that attaches to horizontal return air duct in an over and under design. Stand alone outdoor application that attaches to horizontal return air duct in an side by side design. Unitary Products Group 903106-UTG-A-0912 TABLE 14: FILTER SIZES - STAND ALONE ERV SERIES Series D O S Size Return Filter Width Height 14 20 16 20 20 20 16 20 24 24 14 20 18 20 20 20 18 25 16 16 20 20 16 / 14 20 24 24 14 20 14 20 16 20 20 20 16 20 24 24 14 20 Qty 1 2 2 3 2 5 6 8 1 2 2 2/1 2 5 1 2 2 3 2 5 011 020 028 036 046 062 080 120 011 020 028 036 046 062 011 020 028 036 046 062 Type 2" PLT 2" PLT 2" PLT Intake Filter Width Height 16.25 10.375 12.5 20 14.75 32.25 16.5 32.25 20 36 20 / 20 36 / 12.5 32.25 21.5 32.25 20.25 27.5 10 32.25 18.5 40.25 21.5 40.25 21.5 40.25 21.5 40.25 25.5 16.25 10.375 12.5 20 14.75 32.25 16.5 32.25 20 36 20 / 20 36 / 12.5 Qty 1 1 1 1 1 1/1 2 3 1 1 1 1 1 1 1 1 1 1 1 1/1 Type 1" ME 1" ME 1" ME SERVICE CLEARANCES - STAND ALONE SERIES ERVS A A B B D D “O” Series “D” Series C C Dimension (inches) A B C D 11 36 60 48 36 20 36 60 60 36 28 36 60 60 48 "D" Series 36 46 36 36 60 60 60 72 48 60 A B D “S” Series 62 36 60 72 60 80 36 72 72 72 120 36 84 72 84 Dimension (inches) A B C D Dimension (inches) A B C D 11 12 36 48 36 11 12 60 48 36 20 12 36 60 36 20 12 60 60 36 "O" Series 28 36 12 12 36 36 60 60 48 48 "S" Series 28 36 12 12 60 60 60 60 48 48 46 12 36 60 60 46 12 60 72 60 62 12 36 60 60 62 12 60 72 60 C Unitary Products Group 23 903106-UTG-A-0912 TABLE 15: SPECIFICATIONS AND ELECTRICAL DATA - 300 THROUGH 1100 CFM ERV'S D011 Stand Alone Down Discharge 208/230v 208/230v 460v 1ph 3ph 3ph Model Numbers Line Voltage - 60hz Motor - hp Wheel Size (dia x width) -in Motor Speed -rpm Fresh Air Motor Speed(s) Blower Bearing Type Full Load Amps Service Factor Motor - hp Stationary Wheel Size (dia x width) -in Motor Speed -rpm Exhaust Air Motor Speed(s) Blower Bearing Type Full Load Amps-Stationary Service Factor Potential Volts Wheel Electrical Motor Speed -rpm Data Full Load Amps Total MCA - Stationary Electrical OCPD - Stationary Wheel Depth - in Wheel Data Wheel Diameter - in Construction / Media Curb Curb Hgt - in Shipping Weight - lbs. (kg) Weights Net Weight - lbs. (kg) 575v 3ph 1.5 / Belt 9x4 1725 Adjustable Sheave Ball 9.1 5.6 2.8 2.0 1.15 1.5 / Belt 9x4 1725 Adjustable Sheave Ball 9.1 5.6 2.8 2.0 1.15 208 - 230 1050 0.3 20.8 12.9 6.6 4.8 30 15 9 7 3 25.3 Segmented Pies/Polymeric 14 318 245 O011 S/A Over & Under S011 S/A Side by Side 208/230v 208/230v 460v 460v 1ph 3ph 1ph 3ph 1.5 / Belt 9x4 1725 Adjustable Sheave Ball 9.1 5.6 2.8 1.15 1.5 / Belt 9x4 1725 Adjustable Sheave Ball 9.1 5.6 2.8 1.15 208 - 230 1050 0.3 20.8 12.9 6.6 30 15 9 3 25.3 Segmented Pies/Polymeric 14 318 245 2.0 2.0 4.8 7 AHRI Certified Ratings Thermal Ratings @ 0" Pressure Diff. Total Effectiveness Net Effectiveness Sensible Latent Total 100% Airflow Heating 75% Airflow Heating 76% 81% 68% 73% 73% 78% 100% Airflow Cooling 76% 68% 72% 75% Airflow Cooling 81% 73% 76% 100% Airflow Heating 76% 68% 73% 75% Airflow Heating 81% 73% 78% 100% Airflow Cooling 76% 68% 72% 75% Airflow Cooling 81% 73% 76% Enthalpy Wheel AHRI Rating Data Nominal Airflow CFM 900 @ 1.0 EATR - -1.00 H O 9.30% 2 EATR - 0.00 H O 0.70% EATR - +1.00 H O 0.00% OACF - -1.00 H O 0.97 OACF - 0.00 H O 1.19 OACF - +1.00 H O 1.34 2 2 2 2 2 24 Unitary Products Group 903106-UTG-A-0912 TABLE 16: SPECIFICATIONS AND ELECTRICAL DATA - 1200 THROUGH 2000 CFM ERV'S D020 Stand Alone Down Discharge 208/230v 460v 575v 3ph 3ph 3ph Model Numbers Line Voltage - 60hz Motor - hp Wheel Size (dia x width) -in Motor Speed -rpm Fresh Air Motor Speed(s) Blower Bearing Type Full Load Amps Service Factor Motor - hp Stationary Wheel Size (dia x width) -in Motor Speed -rpm Exhaust Air Blower Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor Potential Volts Wheel Electrical Motor Speed -rpm Data Full Load Amps Total MCA - Stationary Electrical OCPD - Stationary Wheel Depth - in Wheel Wheel Diameter - in Data Construction / Media Curb Curb Hgt - in Weights Shipping Weight - lbs. (kg) Net Weight - lbs. (kg) O020 S/A Over and Under S020 S/A Side by Side 208/230v 460v 575v 3ph 3ph 3ph 2 / Belt 9x9 1725 Adjustable Sheave Ball 6.0 2.6 2.4 1.15 2 / Belt 9x9 1725 Adjustable Sheave Ball 6.0 2.6 2.4 1.15 2 / Belt 9x9 1725 Adjustable Sheave Ball 6.0 2.6 2.4 1.15 2 / Belt 9x9 1725 Adjustable Sheave Ball 6.0 2.6 2.4 1.15 208 - 230 1050 0.3 13.8 6.2 5.7 20 9 8 3 30.346 Segmented Pies/Polymeric 14 425 345 208 - 230 1050 0.3 13.8 6.2 5.7 20 9 8 3 30.346 Segmented Pies/Polymeric 14 425 345 AHRI Certified Ratings Thermal Ratings @ 0" Pressure Diff. 100% Airflow Heating 75% Airflow Heating Total Effectiveness 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating Net Effectiveness 100% Airflow Cooling 75% Airflow Cooling Enthalpy Wheel AHRI Rating Data Nominal Airflow CFM EATR - -1.00 H O EATR - 0.00 H O EATR - +1.00 H O OACF - -1.00 H O OACF - 0.00 H O OACF - +1.00 H O 2 2 2 2 2 2 Unitary Products Group Sensible 68% 72% 68% 72% 68% 72% 68% 72% Latent 61% 67% 61% 67% 61% 67% 61% 67% Total 65% 71% 64% 70% 65% 71% 64% 70% 1600 @ .95 7.80% 0.40% 0.00% 0.97 1.16 1.29 25 903106-UTG-A-0912 TABLE 17: SPECIFICATIONS AND ELECTRICAL DATA - 1200 THROUGH 2800 CFM ERV'S D028 Stand Alone Down Discharge 208/230v 460v 575v 3ph 3ph 3ph Model Numbers Line Voltage - 60hz O028S/A Over and Under S028 S/A Side by Side 208/230v 460v 575v 3ph 3ph 3ph Motor - hp / type Wheel Size (dia x width) -in Motor Speed -rpm Motor Speed(s) Bearing Type Full Load Amps Service Factor 3 / Belt 10 x 10 1725 Adjustable Sheave Ball 9.4 4.3 3.2 1.15 3 / Belt 10 x 10 1725 Adjustable Sheave Ball 9.4 4.3 3.2 1.15 Motor - hp Stationary Wheel Size (dia x width) -in Motor Speed -rpm Exhaust Air Blower Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor 3 / Belt 10 x 10 1725 Adjustable Sheave Ball 9.4 4.3 3.2 1.15 3 / Belt 10 x 10 1725 Adjustable Sheave Ball 9.4 4.3 3.2 1.15 0.05 200 / 208 - 230 825 0.6 0.05 200 / 208 - 230 825 0.6 Fresh Air Blower Wheel Electrical Data Total Electrical Wheel Data Curb Weights Motor - hp (1 phase) Potential Volts Motor Speed -rpm Full Load Amps MCA - Stationary OCPD - Stationary 21.8 30 Wheel Depth x Dia - in Construction / Media Type Curb Height - in Shipping Weight - lbs. (kg) Net Weight - lbs. (kg) 10.3 12 7.8 10 21.8 30 3 x 37.759 Segmented Pies/Polymeric 14 470 395 10.3 12 7.8 10 3 x 37.759 Segmented Pies/Polymeric 14 470 395 AHRI Certified Ratings Thermal Ratings @ 0" Pressure Diff. 100% Airflow Heating 75% Airflow Heating Total Effectiveness 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating Net Effectiveness 100% Airflow Cooling 75% Airflow Cooling Enthalpy Wheel AHRI Rating Data Nominal Airflow CFM EATR - -1.00 H O EATR - 0.00 H O EATR - +1.00 H O OACF - -1.00 H O OACF - 0.00 H O OACF - +1.00 H O 2 2 2 2 2 2 26 Sensible 68% 74% 68% 74% 68% 74% 68% 74% Latent 60% 67% 60% 67% 60% 67% 60% 67% Total 65% 71% 63% 70% 65% 71% 63% 70% 2600 @ .95 6.10% 0.40% 0.00% 0.99 1.13 1.23 Unitary Products Group 903106-UTG-A-0912 TABLE 18: SPECIFICATIONS AND ELECTRICAL DATA - 2000 THROUGH 3600 CFM ERV'S Model Numbers Line Voltage - 60hz Motor - hp / type Wheel Size (dia x width) -in Motor Speed -rpm Fresh Air Motor Speed(s) Blower Bearing Type Full Load Amps Service Factor Motor - hp Stationary Wheel Size (dia x width) -in Motor Speed -rpm Exhaust Air Blower Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor Motor - hp (1 phase) Wheel Electrical Potential Volts Data Motor Speed -rpm Full Load Amps MCA - Stationary Total Electrical OCPD - Stationary Wheel Depth x Diameter - in Wheel Data Construction / Media Type Curb Curb Height - in Shipping Weight - lbs. (kg) Weights Net Weight - lbs. (kg) D036 Stand Alone Down Discharge 208/230v 460v 575v 3ph 3ph 3ph 3 / Belt 12 x 9 1725 Adjustable Sheave Ball 9.4 4.3 3.2 1.15 3 / Belt 12 x 9 1725 Adjustable Sheave Ball 9.4 4.3 3.2 1.15 0.17 200 / 208 - 230 1075 1.2 22.4 10.9 8.4 30 15 10 3 x 41.825 Segmented Pies/Polymeric 14 571 475 O036 S/A Over and Under S036 S/A Side by Side 208/230v 460v 575v 3ph 3ph 3ph 3 / Belt 12 x 9 1725 Adjustable Sheave Ball 9.4 4.3 3.2 1.15 3 / Belt 12 x 9 1725 Adjustable Sheave Ball 9.4 4.3 3.2 1.15 0.17 200 / 208 - 230 1075 1.2 22.4 10.9 8.4 30 15 10 3 x 41.825 Segmented Pies/Polymeric 14 571 475 AHRI Certified Ratings Thermal Ratings @ 0" Pressure Diff. Total Effectiveness Net Effectiveness Nominal Airflow CFM EATR - -1.00 H O EATR - 0.00 H O EATR - +1.00 H O OACF - -1.00 H O OACF - 0.00 H O OACF - +1.00 H O 2 2 2 2 2 2 Unitary Products Group Sensible 100% Airflow Heating 75% Airflow Heating 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating 100% Airflow Cooling 75% Airflow Cooling Enthalpy Wheel AHRI Rating Data 68% 74% 68% 74% 68% 74% 68% 74% Latent Total 60% 67% 60% 67% 60% 67% 60% 67% 65% 71% 63% 70% 65% 71% 63% 70% 3100 @ .9 4.90% 1.30% 0.30% 0.99 1.07 1.12 27 903106-UTG-A-0912 TABLE 19: SPECIFICATIONS AND ELECTRICAL DATA - 3000 THROUGH 4600 CFM ERV'S Model Numbers Line Voltage - 60hz Motor - hp / type Wheel Size (dia x width) -in Motor Speed -rpm Fresh Air Motor Speed(s) Blower Bearing Type Full Load Amps Service Factor Motor - hp Stationary Wheel Size (dia x width) -in Motor Speed -rpm Exhaust Air Blower Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor Enthalpy Wheel Electrical Data Total Electrical Wheel Data Curb Weights Motor - hp (1 phase) Potential Volts Motor Speed -rpm Full Load Amps MCA - Stationary OCPD - Stationary D046 Stand Alone Down Discharge 208/230v 460v 575v 3ph 3ph 3ph 5 / Belt 12 x 12 1725 Adjustable Sheave Ball 14.8 7.0 5.1 1.15 5 / Belt 12 x 12 1725 Adjustable Sheave Ball 14.8 7.0 5.1 1.15 34.5 40 Wheel Depth x Diameter - in Construction / Media Type Curb Height - in 0.17 200 / 208 - 230 1075 1.2 17.0 25 12.7 15 O046 S/A Over and Under S046 S/A Side by Side 208/ 230v 460v 575v 3ph 3ph 3ph 5 / Belt 12 x 12 1725 Adjustable Sheave Ball 14.8 7.0 5.1 1.15 5 / Belt 12 x 12 1725 Adjustable Sheave Ball 14.8 7.0 5.1 1.15 34.5 40 0.17 200 / 208 - 230 1075 1.2 17.0 25 12.7 15 3 x 46.776 Segmented Pies/Polymeric 14 3 x 46.776 Segmented Pies/Polymeric 14 Shipping Weight - lbs. (kg) 920 920 Net Weight - lbs. (kg) 805 805 AHRI Certified Ratingss Thermal Ratings @ 0" Pressure Diff. 100% Airflow Heating 75% Airflow Heating Total Effectiveness 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating Net Effectiveness 100% Airflow Cooling 75% Airflow Cooling Enthalpy Wheel AHRI Rating Data Nominal Airflow CFM EATR - -1.00 H O EATR - 0.00 H O EATR - +1.00 H O OACF - -1.00 H O OACF - 0.00 H O OACF - +1.00 H O 2 2 2 2 2 2 28 Sensible 68% 73% 68% 73% 68% 73% 68% 73% Latent 60% 67% 60% 67% 60% 67% 60% 67% Total 65% 71% 63% 70% 65% 71% 63% 70% 3900 @ .95 4.40% 1.10% 0.20% 0.99 1.06 1.11 Unitary Products Group 903106-UTG-A-0912 TABLE 20: SPECIFICATIONS AND ELECTRICAL DATA - 4600 THROUGH 6200 CFM ERV'S Model Numbers CFM Range Line Voltage - 60hz Motor - hp / type Wheel Size (dia x width) -in Motor Speed -rpm Fresh Air Motor Speed(s) Blower Bearing Type Full Load Amps Service Factor Motor - hp Stationary Wheel Size (dia x width) -in Motor Speed -rpm Exhaust Air Blower Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor Motor - hp (1 phase) Enthalpy Wheel Potential Volts Electrical Data Motor Speed -rpm Full Load Amps MCA - Stationary Total Electrical OCPD - Stationary Wheel Depth x Diameter - in Wheel Data Construction / Media Type Curb Curb Height - in Shipping Weight - lbs. (kg) Weights Net Weight - lbs. (kg) D062 Stand Alone Down Discharge 4600-6200 CFM 208/230v 460v 575v 3ph 3ph 3ph 5 / belt 15 x 15 1725 Adjustable Sheave Ball 14.8 7.0 5.1 1.15 5 / Belt 12 x 12 1725 Adjustable Sheave Ball 14.8 7.0 5.1 1.15 0.17 200 / 208 - 230 1075 1.2 34.5 17.0 12.7 40 25 15 3 x 52.026 Segmented Pies/Polymeric 14 1250 1075 O062 S/A Over and Under S062 S/A Side by Side 4600-6200 CFM 208/230v 460v 575v 3ph 3ph 3ph 5 / belt 15 x 15 1725 Adjustable Sheave Ball 14.8 7.0 5.1 1.15 5 / Belt 12 x 12 1725 Adjustable Sheave Ball 14.8 7.0 5.1 1.15 0.17 200 / 208 - 230 1075 1.2 34.5 17.0 12.7 40 25 15 3 x 52.026 Segmented Pies/Polymeric 14 1250 1075 AHRI Certified Ratingss Thermal Ratings @ 0" Pressure Diff. 100% Airflow Heating 75% Airflow Heating Total Effectiveness 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating Net Effectiveness 100% Airflow Cooling 75% Airflow Cooling Enthalpy Wheel AHRI Rating Data Nominal Airflow CFM EATR - -1.00 H O EATR - 0.00 H O EATR - +1.00 H O OACF - -1.00 H O OACF - 0.00 H O OACF - +1.00 H O 2 2 2 2 2 2 Unitary Products Group Sensible 68% 73% 68% 73% 68% 73% 68% 73% Latent 60% 67% 60% 67% 60% 67% 60% 67% Total 65% 71% 63% 70% 65% 71% 63% 70% 5500 @ .95 4.00% 1.00% 0.20% 0.99 1.06 1.10 29 903106-UTG-A-0912 TABLE 21: SPECIFICATIONS AND ELECTRICAL DATA - 6000 THROUGH 13000 CFM ERV'S D080 Stand Alone Down Discharge 208/230v 460v 3ph 575v 3ph 3ph 10 / Belt 15 x 15 1725 Adjustable Sheave Ball 26.8 13.4 10.3 1.15 D120 Stand Alone Down Discharge 208/230v 460v 3ph 575v 3ph 3ph 15 / Belt 22 x 15 1725 Adjustable Sheave Ball 41.0 18.5 15.4 1.15 7.5 / Belt 18 x 18 1725 Adjustable Sheave Ball 22.4 9.7 7.8 1.15 10 / Belt 22 x 22 1725 Adjustable Sheave Ball 32.6 13.4 10.3 1.15 Motor - hp (3 phase) Potential Volts Motor Speed -rpm Full Load Amps 0.25 MCA - Stationary OCPD - Stationary Model Numbers Line Voltage - 60hz Fresh Air Blower Motor - hp Stationary Wheel Size (dia x width) -in Motor Speed -rpm Motor Speed(s) Bearing Type Full Load Amps-Stationary Service Factor Motor - hp / type Wheel Size (dia x width) -in Motor Speed -rpm Exhaust Air Blower Motor Speed(s) Bearing Type Full Load Amps Service Factor Enthalpy Wheel Electrical Data Total Electrical Wheel Data Wheel Depth x Diameter - in Construction / Media Type Curb Weights Curb Height - in Shipping Weight - lbs. (kg) Net Weight - lbs. (kg) 0.33 0.25 2.5 0.25 200 / 208 - 230 1725 1.2 0.33 2.5 0.25 200 / 208 - 230 1725 1.2 1.4 63.2 90 27.7 40 22.1 35 86.2 125 37.7 50 31.0 45 1.4 3 x 58 Segmented Pies/Polymeric 3 x 74 Segmented Pies/Polymeric 14 2800 2600 14 3000 2800 AHRI Certified Ratingss Thermal Ratings @ 0" Pressure Diff. 100% Airflow Heating 75% Airflow Heating Total Effectiveness 100% Airflow Cooling 75% Airflow Cooling 100% Airflow Heating 75% Airflow Heating Net Effectiveness 100% Airflow Cooling 75% Airflow Cooling Enthalpy Wheel AHRI Rating Data Nominal Airflow CFM 6600 @ .95 EATR - -1.00 H O 4.60% EATR - 0.00 H O 1.90% EATR - +1.00 H O 0.90% OACF - -1.00 H O 0.99 OACF - 0.00 H O 1.05 OACF - +1.00 H O 1.09 2 2 2 2 2 2 30 Sensible 68% 73% 68% 73% 68% 73% 68% 73% Latent 60% 67% 60% 67% 60% 67% 60% 67% Total 65% 71% 63% 70% 65% 71% 63% 70% 10800 @ .95 3.40% 1.20% 0.40% 0.99 1.04 1.07 Unitary Products Group 903106-UTG-A-0912 D SERIES STAND ALONE ERV'S FOR DOWN DISCHARGE DUCT ARRANGEMENTS FEATURES AND NOTES 1. 2. 3. 4. 5. 6. Stand alone design allows higher levels of outdoor air to be introduced into the a/c space. Static test ports provided to verify intake and exhaust CFM. Balancing damper(s) field supplied in duct work when connected to ERV. Roof curbs are available for the ERV's. See blower performance charts for airflow at various E.S.P. EXHAUST AIR HOOD Filter rack with 2" pleated filters included. ERV Roof Curbs Series Model No D011 01-2D1-2514 D020 01-2D1-3014 D028 01-2D1-3614 D036 01-2D1-4114 D046 01-2D1-4614 D062 01-2D1-5214 D080 01-201D-5814 D120 01-201D-7414 FRESH AIR HOOD RETURN AIR DUCT (FIELD SUPPLIED) SUPPLY AIR DUCT (FIELD SUPPLIED) A E G J F I B H D K J C ERV Data ERV CFM Range Series D011 D020 D028 D036 D046 D062 D080 D120 300-1100 1200-2000 1200-2800 2000-3600 3000-4600 4600-6200 6000-8000 8000-13000 Unitary Products Group Dimensional Data Duct Size (G x J) A B C 17.00 x 11.38 21.88 x 14.00 20.25 x 17.00 23.38 x 17.38 23.38 x 20.38 29.38 x 30.00 38.75 x 35.38 40.00 x 44.50 44.75 54.38 52.25 60.00 60.00 72.00 101.38 120.38 32.13 37.25 42.63 46.69 52.69 70.88 78.38 88.38 33.50 37.50 43.56 57.37 57.37 63.63 71.34 86.63 ERV D E 14.38 43.00 17.50 52.75 25.50 49.50 25.50 55.75 28.06 55.75 37.75 67.75 21.75 99.75 28.50 118.50 Roof Curb H I F G 39.00 48.75 45.50 51.75 51.75 63.75 95.75 114.50 17.50 22.38 20.75 23.88 23.88 29.88 38.75 44.88 30.25 35.50 41.00 41.81 47.81 66.00 76.75 86.50 26.25 31.50 37.00 37.81 43.81 62.00 72.75 82.50 J K 11.88 14.50 17.50 17.91 20.91 30.50 35.38 40.25 2.50 2.50 2.00 2.00 2.00 2.00 2.00 2.00 31 903106-UTG-A-0912 TABLE 22: AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR D011 & D020 Blower RPM for D011 CFM 300 500 700 900 1100 CFM 300 500 700 900 1100 SUPPLY Mist Eliminator Filter in Intake Hood (1.5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A N/A 1175 1350 1450 N/A 1170 1340 1540 1655 1295 1425 1600 1625 1795 1540 1660 1720 1790 2030 1785 1915 2025 2185 N/A 1.25 1605 1725 1960 2110 N/A 1.5 1730 1840 2035 2195 N/A EXHAUST Barometric Hood, 2" Pleated Filters (1.5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A N/A 1030 1225 N/A N/A 1025 1180 1265 1425 1120 1190 1340 1445 1540 1285 1525 1500 1575 1670 1570 1665 1670 1775 1860 1.25 N/A 1535 1645 1785 1920 1.5 N/A N/A 1720 1865 N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only RPM Range Low 1000-1300 Standard Unit Medium 1300-1565 Optional Kit High 1750-2200 Optional Kit Blower RPM for D020 CFM 1200 1400 1600 1800 2000 CFM 1200 1400 1600 1800 2000 SUPPLY Mist Eliminator Filter in Intake Hood (2HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 1055 1135 1295 1420 1540 1140 1240 1340 1490 1600 1200 1330 1460 1565 1645 1320 1405 1525 1615 1705 1415 1515 1605 1690 1775 1.25 1650 1690 1740 1785 1875 1.5 1725 1795 1830 1885 1960 EXHAUST Barometric Hood, 2" Pleated Filters (2HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 1010 1195 1350 1445 1580 1125 1315 1435 1545 1620 1185 1370 1500 1610 1695 1305 1485 1600 1685 1781 1410 1550 1670 1765 1855 1.25 1685 1730 1790 1955 N/A 1.5 1735 1800 1965 2030 N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only 32 Low Medium High RPM Range 1000-1300 Standard Unit 1300-1700 Optional Kit 1700-2080 Optional Kit Unitary Products Group 903106-UTG-A-0912 TABLE 23: AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR D028 & D036 Blower RPM for D028 CFM 1200 1600 2000 2400 2800 CFM 1200 1600 2000 2400 2800 SUPPLY Mist Eliminator Filter in Intake Hood (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A 790 960 1110 1210 750 900 1005 1145 1230 900 1005 1105 1210 1275 1005 1125 1210 1275 1365 1125 1230 1315 1380 1450 1.25 1315 1365 1400 1450 1535 1.5 1380 1410 1450 1500 1600 EXHAUST Barometric Hood, 2" Pleated Filters (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 750 885 1015 1145 1260 870 1015 1125 1215 1325 1015 1145 1240 1345 1410 1125 1250 1345 1430 1500 1250 1410 1485 1520 1630 1.25 1350 1410 1485 1575 1650 1.5 1485 1500 1560 1630 1675 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only RPM Range Low 750-975 Standard Unit Medium 1008-1314 Optional Kit High 1311-1708 Optional Kit Blower RPM for D036 CFM 2000 2400 2800 3200 3600 CFM 2000 2400 2800 3200 3600 SUPPLY Mist Eliminator Filter in Intake Hood (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 725 825 900 1000 1070 800 900 1000 1070 1160 900 1000 1070 1160 1250 1000 1070 1160 1250 1275 1055 1180 1250 1300 1360 1.25 1180 1250 1275 1340 N/A 1.5 1250 1275 1340 1400 N/A EXHAUST Barometric Hood, 2" Pleated Filters (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 750 865 950 1030 1100 820 950 1035 1100 1200 925 1035 1150 1200 1265 1035 1160 1215 1265 1325 1100 1215 1300 1350 1390 1.25 1200 1265 1315 1350 N/A 1.5 1265 1300 1350 1390 N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Unitary Products Group Low Medium High RPM Range 725-975 Standard Unit 1000-1315 Optional Kit 1215-1425 Optional Kit 33 903106-UTG-A-0912 TABLE 24: AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR D046 & D062 Blower RPM for D046 CFM 3000 3400 3800 4200 4600 CFM 3000 3400 3800 4200 4600 SUPPLY Mist Eliminator Filter in Intake Hood (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 900 1030 1100 1165 1240 975 1085 1175 1240 1290 1070 1175 1240 1290 1350 1165 1240 1320 1350 1430 1240 1320 1375 1430 1500 1.25 1285 1350 1400 1465 1515 1.5 1350 1400 1465 1515 1580 EXHAUST Barometric Hood, 2" Pleated Filters (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 955 1100 1160 1245 1280 1055 1185 1245 1300 1375 1160 1300 1360 1400 1425 1245 1375 1450 1480 1500 1360 1450 1500 1585 1600 1.25 1360 1425 1530 1585 1650 1.5 1425 1480 1585 1650 1700 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only RPM Range Low 780-1020 Standard Unit Medium 1000-1315 Optional Kit High 1315-1700 Optional Kit Blower RPM for D062 CFM 4600 5000 5400 5800 6200 CFM 4600 5000 5400 5800 6200 SUPPLY Mist Eliminator Filter in Intake Hood (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 815 900 975 1045 1085 880 940 1015 1060 1135 915 975 1045 1125 1150 975 1045 1085 1175 1250 1000 1075 1165 1200 N/A 1.25 1125 1175 1195 1260 N/A 1.5 1175 1215 1250 N/A N/A EXHAUST Barometric Hood, 2" Pleated Filters (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 825 915 1000 1025 1100 890 975 1025 1100 1140 925 1000 1085 1140 1170 975 1025 1140 1170 1240 1025 1120 1170 N/A N/A 1.25 1140 1170 1240 N/A N/A 1.5 1170 1240 1280 N/A N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only 34 Low Medium High RPM Range 820-1000 Standard Unit 1000-1200 Optional Kit 1175-1375 Optional Kit Unitary Products Group 903106-UTG-A-0912 TABLE 25: AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR D080 & D120 Blower RPM for D080 CFM 6000 6400 6800 7200 7600 8000 CFM 6000 6400 6800 7200 7600 8000 SUPPLY Mist Eliminator Filter in Intake Hood (10HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 737 794 851 908 961 786 839 893 947 998 836 886 937 987 1036 885 931 979 1027 1074 934 978 1024 1069 1114 983 1025 1068 1111 1154 1.25 1012 1047 1083 1119 1159 1196 1.5 1061 1094 1129 1163 1200 1237 EXHAUST Barometric Hood, 2" Pleated Filters (7.5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 599 660 716 769 818 639 695 748 798 846 679 733 783 831 877 719 769 817 863 907 759 808 854 897 940 799 845 889 931 972 1.25 866 892 921 949 980 1011 1.5 911 935 963 990 1020 1049 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only RPM Range Low Medium High Standard Unit Optional Kit Optional Kit Blower RPM for D120 CFM 8000 8800 9600 10400 11200 12000 CFM 8000 8800 9600 10400 11200 12000 SUPPLY Mist Eliminator Filter in Intake Hood (15HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 427 470 512 552 591 469 509 547 584 621 512 548 583 618 651 555 589 621 653 684 597 629 659 689 718 640 670 698 726 754 1.25 630 656 684 715 747 781 1.5 667 691 717 746 776 808 EXHAUST Barometric Hood, 2" Pleated Filters (15HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 437 480 521 551 600 481 520 558 595 631 525 561 596 630 663 569 602 634 665 657 612 643 674 703 732 656 685 713 741 768 1.25 639 665 696 727 761 795 1.5 676 701 728 758 789 822 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Unitary Products Group RPM Range Low Medium High Standard Unit Optional Kit Optional Kit 35 903106-UTG-A-0912 S SERIES STAND ALONE ERV'S FOR SIDE BY SIDE DUCT ARRANGEMENTS RETURN DUCT FLANGE OPENING SUPPLY DUCT FLANGE OPENING FEATURES AND NOTES 1. 2. 3. 4. 5. 6. Stand alone design allows higher levels of outdoor air to be introduced into the conditioned space. Static test ports provided to verify intake and exhaust CFM. Balancing damper(s) is field provided when connected to ductwork. System may not operate properly without balancing damper. Roof curbs are available for the ERV's. See blower performance charts for airflow at various E.S.P. Filter rack with 2" pleated filters included. Found in return air section. K B A F J C E ERV Roof Curbs Series Model No 01-2D1-2514 S011 01-2D1-3014 S020 01-2D1-3614 S028 01-2D1-4114 S036 01-2D1-4614 S046 01-2D1-5214 S062 I H D G D H ERV Data 36 Dimensional Data ERV Series CFM Range A B C D E F G H I J K S011 S020 S028 S036 S046 300-1100 1200-2000 1200-2800 2000-3600 3000-4600 44.75 54.38 52.25 60.00 60.00 32.13 37.25 42.63 46.69 52.69 33.50 37.50 43.56 57.37 57.37 11.00 12.00 14.00 16.50 16.50 27.00 30.00 32.00 39.50 39.50 4.00 5.87 8.69 12.00 12.00 4.25 5.13 5.25 5.50 8.69 2.88 4.06 4.25 4.05 5.50 2.50 1.63 2.88 5.88 5.88 20.75 20.75 20.75 20.75 20.75 14.38 17.50 25.50 25.50 28.06 Unitary Products Group 903106-UTG-A-0912 TABLE 26: AIRFLOW PERFORMANCE - SIDE BY SIDE DUCT CONFIGURATION FOR S011 & S020 Blower RPM for S011 CFM 300 500 700 900 1100 CFM 300 500 700 900 1100 SUPPLY Mist Eliminator Filter in Intake Hood (1.5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A N/A 1020 1205 1365 N/A 1015 1200 1320 1460 990 1190 1315 1455 1560 1150 1310 1450 1555 1660 1305 1440 1550 1655 1740 1.25 1480 1565 1665 1680 1815 1.5 1590 1670 1715 1795 1895 EXHAUST Barometric Hood, 2" Pleated Filters (1.5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A N/A 1150 1285 1415 N/A 1145 1275 1410 1510 1140 1270 1405 1505 1590 1320 1435 1585 1665 1705 1495 1580 1660 1755 1880 1.25 1515 1545 1715 1810 N/A 1.5 1640 1720 1815 1930 N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Low Medium High RPM Range 100-1300 Standard Unit 1300-1700 Optional Kit 1750-2200 Optional Kit Blower RPM for S020 CFM 1200 1400 1600 1800 2000 CFM 1200 1400 1600 1800 2000 SUPPLY Mist Eliminator Filter in Intake Hood (2HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 1065 1285 1375 1415 1495 1140 1330 1410 1440 1555 1290 1400 1480 1545 1670 1395 1470 1540 1665 1735 1460 1530 1650 1725 1795 1.25 1580 1660 1745 1800 1870 1.5 1685 1760 1835 1880 1960 EXHAUST Barometric Hood, 2" Pleated Filters (2HP) External Static Pressure (in water) 0 0.5 0.75 1 0.25 1175 1290 1430 1520 1680 1245 1425 1515 1675 1755 1400 1505 1670 1750 1825 1495 1660 1740 1820 1900 1645 1730 1815 1895 1965 1.25 1765 1830 1910 1975 2080 1.5 1850 1920 1980 2090 2170 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Unitary Products Group Low Medium High RPM Range 100-1300 Standard Unit 1300-1750 Optional Kit 1750-2200 Optional Kit 37 903106-UTG-A-0912 TABLE 27: AIRFLOW PERFORMANCE - SIDE BY SIDE DUCT CONFIGURATION FOR S028 & S036 Blower RPM for S028 CFM 1200 1600 2000 2400 2800 CFM 1200 1600 2000 2400 2800 SUPPLY Mist Eliminator Filter in Intake Hood (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A 955 1070 1210 1370 N/A 1065 1205 1305 1460 1060 1200 1290 1445 1530 1190 1335 1440 1490 1575 1300 1460 1550 1645 1705 1.25 1465 1540 1585 1670 1750 1.5 1550 1595 1680 1755 1800 EXHAUST Barometric Hood, 2" Pleated Filters (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A N/A 1025 1170 1270 N/A 1020 1155 1240 1330 1015 1150 1235 1325 1380 1140 1285 1365 1420 1510 1280 1345 1455 1540 1575 1.25 1355 1390 1475 1595 1670 1.5 1400 1490 1590 1640 1745 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only RPM Range Low 950-1320 Standard Unit Medium 1325-1565 Optional Kit High 1570-1880 Optional Kit Blower RPM for S036 CFM 2000 2400 2800 3200 3600 CFM 2000 2400 2800 3200 3600 SUPPLY Mist Eliminator Filter in Intake Hood (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 815 925 1020 1105 1155 920 1060 1130 1215 1250 1010 1140 1240 1285 1370 1125 1235 1340 1385 1455 1225 1375 1440 1460 1500 1.25 1255 1355 1425 1465 N/A 1.5 1325 1385 1470 N/A N/A EXHAUST Barometric Hood, 2" Pleated Filters (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 755 890 970 1060 1125 985 1035 1085 1140 1240 1020 1115 1175 1230 1270 1105 1200 1225 1285 1300 1155 1265 1295 1335 1385 1.25 1215 1275 1335 1390 N/A 1.5 1280 1325 1370 1430 N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only 38 Low Medium High RPM Range 700-1025 Standard Unit 1030-1305 Optional Kit 1325-1575 Optional Kit Unitary Products Group 903106-UTG-A-0912 TABLE 28: AIRFLOW PERFORMANCE - SIDE BY SIDE DUCT CONFIGURATION FOR S046 & S062 Blower RPM for S046 CFM 3000 3400 3800 4200 4600 CFM 3000 3400 3800 4200 4600 SUPPLY Mist Eliminator Filter in Intake Hood (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 965 1085 1150 1230 1295 1035 1145 1250 1290 1335 1120 1245 1285 1315 1440 1215 1305 1355 1430 1465 1300 1375 1450 1460 1540 1.25 1345 1415 1470 1530 1590 1.5 1420 1475 1535 1595 1650 EXHAUST Barometric Hood, 2" Pleated Filters (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 1010 1105 1195 1255 1300 1100 1190 1250 1320 1370 1185 1245 1360 1410 1440 1240 1355 1425 1465 1530 1345 1410 1485 1520 1585 1.25 1375 1410 1475 1590 1650 1.5 1415 1480 1540 1630 1700 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only RPM Range Low 780-1020 Standard Unit Medium 1000-1315 Optional Kit High 1315-1700 Optional Kit Blower RPM for S062 CFM 4600 5000 5400 5800 6200 CFM 4600 5000 5400 5800 6200 SUPPLY Mist Eliminator Filter in Intake Hood (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 795 900 1030 1075 1160 855 920 1070 1130 1190 880 950 1095 1155 1245 915 1035 1115 1175 1255 985 1080 1135 1225 1265 1.25 1220 1250 1270 1280 N/A 1.5 1255 1275 1290 N/A N/A EXHAUST Barometric Hood, 2" Pleated Filters (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 705 885 985 1045 1100 825 950 1025 1095 1150 875 980 1080 1140 1190 935 995 1130 1180 1230 985 1095 1165 N/A N/A 1.25 1155 1210 1240 N/A N/A 1.5 1215 1245 1275 N/A N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Unitary Products Group Low Medium High RPM Range 700-900 Standard Unit 900-1100 Optional Kit 1100-1300 Optional Kit 39 903106-UTG-A-0912 O SERIES STAND ALONE ERV'S FOR OVER AND UNDER DUCT ARRANGEMENTS FEATURES AND NOTES 1. Stand alone design allows higher levels of outdoor air to be introduced into the conditioned space. Static test ports provided to verify intake and exhaust CFM. Balancing damper(s) is field provided when connected to ductwork. System may not operate properly without balancing damper. Roof curbs are available for the ERV's. See blower performance charts for airflow at various E.S.P. Filter rack with 2" pleated filters included. Found in return air section. 2. 3. 4. 5. 6. ERV Roof Curbs Series Model No O011 01-2O1-2514 O020 01-2D1-3014 O028 01-2O1-3614 O036 01-2D1-4114 O046 01-2D1-4614 O062 01-2O1-5214 ERV with Horizontal Ductwork (balancing damper(s) field supplied) A J B A C F C D G D 14 I H L E B K H ERV Data ERV Series CFM Range O011 300-1100 O020 1200-2000 O028 1200-2800 O036 2000-3600 O046 3000-4600 O062 4600-6200 40 A 56.75 54.38 60.00 60.00 60.00 72.00 B 32.13 37.25 42.63 46.69 52.69 70.88 C 39.50 37.50 43.56 57.37 57.37 63.63 D 11.00 12.00 14.00 16.50 16.50 19.50 Dimensional Data E F G H 27.00 6.50 10.00 2.56 30.00 8.00 4.00 3.63 32.00 9.56 4.50 5.31 39.50 12.13 6.38 3.59 39.50 12.13 6.38 6.59 39.50 12.13 6.50 15.69 I 1.00 1.50 1.50 5.88 5.88 5.88 J 11.00 20.32 18.32 18.32 18.32 18.32 K 55.00 52.75 49.50 55.75 55.75 67.75 L 30.25 35.50 41.00 41.81 47.81 66.00 Unitary Products Group 903106-UTG-A-0912 TABLE 29: AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR O011 & O020 Blower RPM for O011 CFM 300 500 700 900 1100 CFM 300 500 700 900 1100 SUPPLY Mist Eliminator Filter in Intake Hood (1.5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A N/A 1175 1350 1450 N/A 1170 1340 1540 1655 1295 1425 1600 1625 1795 1540 1660 1720 1790 2030 1785 1915 2025 2185 N/A 1.25 1605 1725 1960 2110 N/A 1.5 1730 1840 2035 2195 N/A EXHAUST Barometric Hood, 2" Pleated Filters (1.5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A N/A 1030 1225 N/A N/A 1025 1180 1265 1425 1120 1190 1340 1445 1540 1285 1525 1500 1575 1670 1570 1665 1670 1775 1860 1.25 N/A 1535 1645 1785 1920 1.5 N/A N/A 1720 1865 N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only RPM Range Low 1000-1300 Standard Unit Medium 1300-1700 Optional Kit High 1750-2200 Optional Kit Blower RPM for O020 CFM 1200 1400 1600 1800 2000 CFM 1200 1400 1600 1800 2000 SUPPLY Mist Eliminator Filter in Intake Hood (2HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 1055 1135 1295 1420 1540 1140 1240 1340 1490 1600 1200 1330 1460 1565 1645 1320 1405 1525 1615 1705 1415 1515 1605 1690 1775 1.25 1650 1690 1740 1785 1875 1.5 1725 1795 1830 1885 1960 EXHAUST Barometric Hood, 2" Pleated Filters (2HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 1010 1195 1350 1445 1580 1125 1315 1435 1545 1620 1185 1370 1500 1610 1695 1305 1485 1600 1685 1781 1410 1550 1670 1765 1855 1.25 1685 1730 1790 1955 N/A 1.5 1735 1800 1965 2030 N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Unitary Products Group Low Medium High RPM Range 1000-1300 Standard Unit 1300-1700 Optional Kit 1700-2080 Optional Kit 41 903106-UTG-A-0912 TABLE 30: AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR O028 & O036 Blower RPM for O028 CFM 1200 1600 2000 2400 2800 CFM 1200 1600 2000 2400 2800 SUPPLY Mist Eliminator Filter in Intake Hood (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 N/A 790 960 1110 1210 750 900 1005 1145 1230 900 1005 1105 1210 1275 1005 1125 1210 1275 1365 1125 1230 1315 1380 1450 1.25 1315 1365 1400 1450 1535 1.5 1380 1410 1450 1500 1600 EXHAUST Barometric Hood, 2" Pleated Filters (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 750 885 1015 1145 1260 870 1015 1125 1215 1325 1015 1145 1240 1345 1410 1125 1250 1345 1430 1500 1250 1410 1485 1520 1630 1.25 1350 1410 1485 1575 1650 1.5 1485 1500 1560 1630 1675 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Low Medium High RPM Range 725-975 Standard Unit 1008-1314 Optional Kit 13115-1708 Optional Kit Blower RPM for O036 CFM 2000 2400 2800 3200 3600 CFM 2000 2400 2800 3200 3600 SUPPLY Mist Eliminator Filter in Intake Hood (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 725 825 900 1000 800 900 1000 1070 900 1000 1070 1160 1000 1070 1160 1250 1055 1180 1250 1300 EXHAUST Barometric Hood, 2" Pleated Filters (3HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 750 865 950 1030 1100 820 950 1035 1100 1200 925 1035 1150 1200 1265 1035 1160 1215 1265 1325 1100 1215 1300 1350 1390 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only 42 1 1070 1160 1250 1275 1360 Low Medium High 1.25 1180 1250 1275 1340 N/A 1.5 1250 1275 1340 1400 N/A 1.25 1200 1265 1315 1350 N/A 1.5 1265 1300 1350 1390 N/A RPM Range 725-975 Standard Unit 1000-1315 Optional Kit 1215-1425 Optional Kit Unitary Products Group 903106-UTG-A-0912 TABLE 31: AIRFLOW PERFORMANCE - DOWNFLOW CONFIGURATION FOR O046 & O062 Blower RPM for O046 CFM 3000 3400 3800 4200 4600 CFM 3000 3400 3800 4200 4600 SUPPLY Mist Eliminator Filter in Intake Hood (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 900 1030 1100 1165 1240 975 1085 1175 1240 1290 1070 1175 1240 1290 1350 1165 1240 1320 1350 1430 1240 1320 1375 1430 1500 1.25 1285 1350 1400 1465 1515 1.5 1350 1400 1465 1515 1580 EXHAUST Barometric Hood, 2" Pleated Filters (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 955 1100 1160 1245 1280 1055 1185 1245 1300 1375 1160 1300 1360 1400 1425 1245 1375 1450 1480 1500 1360 1450 1500 1585 1600 1.25 1360 1425 1530 1585 1650 1.5 1425 1480 1585 1650 1700 Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only RPM Range Low 780-1020 Standard Unit Medium 1000-1315 Optional Kit High 1315-1700 Optional Kit Blower RPM for O062 CFM 4600 5000 5400 5800 6200 CFM 4600 5000 5400 5800 6200 SUPPLY Mist Eliminator Filter in Intake Hood (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 815 900 975 1045 1085 880 940 1015 1060 1135 915 975 1045 1125 1150 975 1045 1085 1175 1250 1000 1075 1165 1200 N/A 1.25 1125 1175 1195 1260 N/A 1.5 1175 1215 1250 N/A N/A EXHAUST Barometric Hood, 2" Pleated Filters (5HP) External Static Pressure (in water) 0 0.25 0.5 0.75 1 825 915 1000 1025 1100 890 975 1025 1100 1140 925 1000 1085 1140 1170 975 1025 1140 1170 1240 1025 1120 1170 N/A N/A 1.25 1140 1170 1240 N/A N/A 1.5 1170 1240 1280 N/A N/A Notes: 1. Drive losses included in the above table 2. Performance can vary depending on ambient conditions 3. Blower RPMs are for reference only Unitary Products Group RPM Range Low 820-1000 Standard Unit Medium 1000-1200 Optional Kit High 11751375 Optional Kit 43 903106-UTG-A-0912 GUIDE SPECIFICATIONS Prepared for the guidance of architects, consulting engineers, and mechanical contractors. GENERAL Furnish and install _____________ mechanical cooling system, complete with a Unitized Energy Recovery Ventilator (UERV). APPROVALS The Unitized Energy Recovery Ventilator will contain an energy recovery component rated in accordance with AHRI/ ANSI Standard 1060-2005 with ratings certified by AHRI. Cabinet UERV shall be designed to attach directly to the a/c (rooftop, upflow, horizontal) unit. It shall be G90 galvanized material with a powdered enamel paint finish electrostatically bonded to the metal. Cabinet panels where conditioned air is handled shall be fully insulated to prevent sweating and minimize sound. Openings shall be provided for power connections. Lifting devices will be provided for rigging. Test ports shall be provided so airflow can be measured across the energy recovery wheel. Intake Air Blower (direct drive) UERV shall contain a centrifugal blower. All UERV's will be equipped with direct drive PSC blower motors. The motor will be multiple speed and will be individually controlled. Airflow will also be adjustable by means of a damper on the intake air opening. Blowers and motors will be removable through means of a connecting plug for ease of servicing. Intake Air Blower (belt drive) UERV shall contain a centrifugal blower. It shall have ball bearings and adjustable belt drive. Motor mount base shall permit ease of motor changeover and belt tension adjustment. On pivoting wheel models, supply blower will be deenergized during economizer operation. (Except for VR074 and VR122.) Exhaust Air Blower (direct drive) UERV shall contain a centrifugal blower. All UERV's will be equipped with direct drive PSC blower motors. The motor will be multiple speed and shall be individually controlled. Blowers and motors will be removable through means of a connecting plug for ease of servicing. On pivoting wheel models, blower shall be sized to provide power exhaust during economizer operation. Exhaust Air Blower (belt drive) UERV shall contain a centrifugal blower. It shall have ball bearings and adjustable belt drive. Motor mount base shall 44 permit ease of motor changeover and belt tension adjustment. On pivoting wheel models, exhaust blowers shall be sized to provide power exhaust during economizer operation. Where single blowers cannot provide adequate exhaust, two blowers will be utilized. One blower is energized during energy recovery mode, and both blowers are energized during economizer mode. Energy Recovery Wheel The energy recovery device shall be a rotary heat exchanger per AHRI Standard 1060 description. The device will be an enthalpy wheel coated with a silica gel desiccant by a patented process without the use of binders or adhesives which may plug the desiccant aperture. The substrate shall be a lightweight polymer. Desiccant shall not dissolve or deliquesce in the presence of water or high humidity. The wheel shall be easily cleanable with standard coil cleaning solution. On UERV's Series 20 and less, the wheel will easily be removable from the cabinet for cleaning. On UERV's Series 20 and above, the wheel will be provided with removable segments for cleaning and maintenance. All diameter and perimeter seals shall be provided. The energy recovery cassette shall be Underwriters Laboratories Recognized Component for electrical and fire safety. Balancing Dampers Balancing dampers will be provided for all VR UERV’s. These dampers will be mounted inside the rooftop air conditioning unit to adjust for the amount of exhaust air on packaged units. On pivoting wheel models, the unit economizer becomes the balancing damper. Upflow and horizontal ERVs' will have the balancing damper provided in the ERV. Optional on VO and VS UERV’s when connected to rooftop units. (Except for VR074 and VR122.) Barometric Relief Dampers Barometric relief dampers will be provided in the exhaust air hood to prevent air infiltration when the UERV is de-energized. ERV Support All UERV's will be provided with support legs attached to the cabinet to support the intake and exhaust end of the ERV unit. Horizontal ERV's will be provided with support brackets for hanging. Filters All units shall be provided with mist eliminator type filters in the intake air hood. Power Connection The UERV shall be provided with a single point power connection for high voltage. Unitary Products Group 903106-UTG-A-0912 OPTIONS 2. The ERV is activated with the supply blower of the RTU. The intake blower, the exhaust blower, and the wheel rotation motor of the ERV are activated. These motors will remain energized as long as the supply blower on the RTU is energized and the RTU is in standard (noneconomizer) mode. 3. If the optional motorized fresh air damper in the outside air intake of the ERV is present, it opens and the ERV is energized. 4. If the optional low ambient kit is present, and the temperature leaving the exhaust side of the wheel drops below the field adjusted set point on the temperature sensor of the low ambient kit, the optional motorized fresh air damper will close and the intake blower will deenergize. The exhaust air blower and wheel rotation motor will continue to operate. When the temperature sensor has a sixteen-degree rise, the wheel is defrosted and the optional motorized damper will open and the fresh air blower will reactivate. Optional UERV Equipment Support Furnish and install the optional equipment support for the intake and exhaust end of the unit. Optional Roof Curb Furnish and install the optional roof mounting frame to maintain proper height above the roof. Optional Low Ambient Kit Furnish and install the optional low ambient kit to prevent frost formation on the energy recovery wheel. Optional Motorized Intake Air Damper Furnish and install the optional motorized intake air damper. Optional Stop-Start-Jog On units without economizers furnish and install the optional stop-start-jog controls. Pivoting Models - Economizer Operation SEQUENCE OF OPERATION: 1. The space thermostat sends a signal to the RTU for cooling operation. Fixed Models - Normal Operation 2. The outdoor air sensor for the RTU senses the outdoor air and determines it is appropriate for economizer operation. 3. As the economizer outside air dampers open, the ERV economizer end switch is activated sending a signal to the ERV that the system is in the economizer mode. 4. The intake blower, the exhaust blower and the wheel rotation motor all deactivate for up to two minutes. The optional motorized fresh air damper (if present) also closes. 5. The ERV enthalpy wheel pivots out of the air stream and the bypass dampers along each side of the intake blower open. 6. After a time delay to allow the wheel to pivot out of the airstream and the bypass dampers to open, the optional motorized fresh air damper opens to allow for full economizer operation, and the exhaust blower is reactivated to provide power exhaust for the system. 1. The space thermostat sends a signal to the RTU for cooling, heating or fan only operation. 2. The ERV is activated simultaneously with the supply blower of the RTU. The intake blower, the exhaust blower, and the wheel rotation motor of the ERV are activated. These motors will remain energized as long as the supply blower on the RTU is energized. The RTU is in standard (non-economizer) mode. 3. 4. If the optional motorized fresh air damper in the outside air intake of the ERV is present, it opens and the ERV is energized. If the optional low ambient kit is present, and the temperature leaving the exhaust side of the wheel drops below the field adjusted set point on the temperature sensor of the low ambient kit, the optional motorized fresh air damper will close and the intake blower will deenergize. The exhaust air blower and wheel rotation motor will continue to operate. When the temperature sensor has a sixteen-degree rise, the wheel is defrosted and the optional motorized damper will open and the fresh air blower will reactivate. Pivoting Models - Normal Operation 1. The space thermostat sends a signal to the RTU for cooling, heating or fan only operation. Unitary Products Group 45 903106-UTG-A-0912 UERV TROUBLESHOOTING GUIDE UERV BELOW 600 CFM WITH STATIONARY WHEEL (NO ECONOMIZER) 4. If all of the above are operational, the exhaust motor is bad. Replace it with new motor. UERV will not operate. UERV has power, but the fresh air blower does not operate. 1. 1. Verify the A130 circuit board switch SW1 Power is in the "on" position. 2. Verify the A130 circuit board terminals Fresh "1” and "3" if in high speed operation, or "1” and "2" if in low speed operation are outputting 110 volts to B27 fresh air blower motor though J/P148 plug assembly. 3. On units equipped with the optional low ambient control, verify that the A130 circuit board TB3 terminals marked "low ambient" are closed. The low ambient control will stop the fresh air motor operation and close the optional outside air damper if it senses conditions for frost on the UERV wheel. The "low ambient" terminals can be jumped together to verify if the low ambient control has the fresh air blower stopped. 4. Verify B27 wheel motor C26 capacitor is good. Replace the capacitor if it is bad. 5. If all of the above are operational, the fresh air motor is bad. Replace it with new motor. Quick check items. a. 2. Verify S51 door switch is closed. The switch must be in the closed position to power the A130 circuit board. b. Verify the A130 circuit board switch SW1 Power is in the “on” position. c. Verify 24 volts to A130 circuit board terminals TB1 “G” and “C” if in the cooling mode, or “W” and “C” if in the heating mode. The terminals must be powered to allow any blower relays / contactors to operate. Verify high voltage power to UERV. a. Verify 110 volts for UERV to L1 and L2 on TB2 on the A130 board. b. Verify the F1 fuse is good. Replace any bad fuses. c. Verify that the T28 step down transformer on 208, 230, and 460 volt units have the voltage correctly applied to the correct transformer terminals. UERV has power, but the enthalpy wheel does not spin. UERV has power, but the optional motorized fresh air damper does not open. 1. Verify 24 volts to A130 circuit board terminals TB1 "G" and "C" if in the cooling mode, or "W" and "C" if in the heating mode. 2. Verify the A130 circuit board terminals Wheel "1" and "2" are outputting 110 volts to B28 wheel motor through J/ P150 plug assembly. Verify the A130 circuit board switch SW1 Power is in the "on" position. 3. Verify 24 volts to B30 motorized outdoor air motor through J/P160 plug assembly. 4. Verify B28 wheel motor C23 capacitor is good. Replace the capacitor if it is bad. 4. If all of the above are operational, replace the outdoor air damper motor. 5. If the optional Stop, Start, Jog (SSJ) feature is installed, verify that the temperature setpoint on the SSJ does not have the wheel stopped. UERV ABOVE 600 CFM WITH STATIONARY WHEEL (NO ECONOMIZER) If all of the above are operational, the wheel motor is bad. Replace it with new motor. UERV will not operate. 1. Check wheel belt is in place and tight. 2. Verify the A130 circuit board switch SW1 Power is in the "on" position. 3. 6. UERV has power, but the exhaust blower does not operate. 1. Verify the A130 circuit board switch SW1 Power is in the "on" position. 2. Verify the A130 circuit board terminals Exhaust "1” and "3” if in high speed operation, or "1” and "2" if in low speed operation are outputting 110 volts to B26 exhaust blower motor though J/P151 plug assembly. 3. 46 Verify B26 wheel motor C25 capacitor is good. Replace the capacitor if it is bad. 1. Quick check items. a. Verify S51 door switch is closed. The switch must be in the closed position to power the A130 circuit board. b. Verify 24 volts to A130 circuit board terminals XFORMER "+" and "-". The terminals must be powered to allow blower contactors to operate. c. Verify 24 volts to A130 circuit board terminals TB 37 numbers "1" and "3". Terminal "1" is the hot and "3" is the common side of the power source from activation power source (a/c unit, energy management Unitary Products Group 903106-UTG-A-0912 control, etc.). Typically, "1" would be from the blower contactor on an a/c unit. 2. Verify high voltage power to UERV. a. b. tactor terminal "A" and "B", and that the contacts are closed. 3. Check for correct voltage for UERV to L1 and L2 on 1-phase units. Verify power to B27 fresh air blower motor though J/ P148 plug assembly. 4. Check for correct voltage for UERV to L1, L2, and L3 on 3-phase units. On direct drive models, verify B27 wheel motor C26 capacitor is good. Replace if necessary. 5. On units equipped with the optional low ambient control, verify that the circuit on the A130 circuit board terminal "5" and "6" is closed. The low ambient control will stop the fresh air motor operation and close the optional outside air damper if it senses frost on the UERV wheel. Terminal "5" and "6" can be jumped together to verify if the low ambient control has the fresh air blower stopped. 6. If all of the above are operational, the fresh air motor is bad. Replace it with new motor. c. Verify the F29 fuses are good. Replace any bad fuses. d. Verify that the T27 transformer has the UERV voltage correctly applied to the correct transformer terminals. UERV has power, but the enthalpy wheel does not spin. 1. Check wheel belt is in place and tight. 2. Verify the A130 circuit board terminals Exhaust "A" (hot) and "B" (common) are outputting 24 volts to K163 contactor terminal "A" and "B" and that the contacts are closed. UERV has power, but the optional motorized fresh air damper does not open. 1. Verify 24 volts to the A130 circuit board terminals XFORMER "+" and "-". 2. Verify 24 volts to A130 circuit board terminals TB 37 numbers "1" and "3". Terminal "1" is the hot and "3" is the common side of the power source from activation power source (a/c unit, energy management control, etc.). Typically, "1" would be from the blower contactor on an a/c unit. 3. Verify power to B28 wheel motor. 4. Verify B28 wheel motor C23 capacitor is good. Replace the capacitor if it is bad. (Except VR074 to VR122) 5. If the optional Stop, Start, Jog (SSJ) feature is installed, verify that the timer on the SSJ does not have the wheel stopped. 3. If all of the above are operational, the wheel motor is bad. Replace it with new motor. Verify 24 volts to B30 motorized outdoor air motor through J/P160 plug assembly. 4. If all of the above are operational, replace the outdoor air damper motor. 6. UERV has power, but the exhaust blower does not operate. 1. 2. Check that the blower belt is in place and tight on belt drive models. If it is loose, tighten it. If it is broken replace it. Verify the A130 circuit board terminals Exhaust "A" (hot) and "B" (common) are outputting 24 volts to K163 contactor terminal "A" and "B", and that the contacts are closed. 3. Verify power to B26 exhaust blower motor. 4. On direct drive models, verify B26 wheel motor C25 capacitor is good. Replace if necessary. 5. If all of the above are operational, the exhaust motor is bad. Replace it with new motor. UERV ABOVE 600 CFM WITH PIVOTING WHEEL (USED WITH ECONOMIZER) UERV will not operate. 1. Quick check items. a. Verify S51 door switch is closed. The switch must be in the closed position to power the A130 circuit board. b. Verify 24 volts to A130 circuit board terminals XFORMER "+" and "-". The terminals must be powered to allow any blower relays / contactors to operate. c. Verify 24 volts to A130 circuit board terminals TB 37 numbers "1" and "3". Terminal "1" is the hot and "3" is the common side of the power source from activation power source (a/c unit, energy management control, etc.). Typically, "1" would be from the blower contactor on an a/c unit. UERV has power, but the fresh air blower does not operate. 1. 2. Check that the blower belt is in place and tight on belt drive models. Tighten it if it is loose. Replace it if it is broken. Verify the A130 circuit board terminals Fresh "A" (hot) and "B" (common) are outputting 24 volts to K164 con- Unitary Products Group 2. Verify high voltage power to UERV. a. Check correct voltage for UERV to L1 and, L2 on 1phase units. 47 b. Check for correct voltage to L1, L2, and L3 on 3phase units. c. Verify the F29 fuses are good. Replace any bad fuses. c. Verify power to B27 fresh air blower motor though J/ P148 plug assembly. d. Verify that the T27 transformer has the UERV voltage correctly applied to the correct transformer terminals. d. On units equipped with the optional low ambient control, verify that the circuit on the A130 circuit board terminal "5" and "6" is made. The low ambient control will stop the fresh air motor operation and close the optional outside air damper if it senses frost on the UERV wheel. Terminal "5" and "6" can be jumped together to verify if the low ambient control has the fresh air blower stopped. e. On direct drive models, verify B27 wheel motor C26 capacitor is good. Replace if necessary. f. If all of the above are operational, the fresh air motor is bad. Replace it with new motor. K164 contactor terminal "A" and "B", and that the contacts are closed. UERV has power, but the enthalpy wheel does not spin. 1. Check wheel belt is in place and tight. 2. Verify the A130 circuit board terminals Exhaust 1 "A" (hot) and "B" (common) are outputting 24 volts to K163 contactor terminal "A" and "B" and that the contacts are closed. 3. Verify power to B28 wheel motor through J/P150 plug assembly. a. If there is no power on the T1 leg of the motor (pivoting models only) verify that the S110 switch located inside the B29 damper motor is in the closed position. 4. Verify B28 wheel motor C23 capacitor is good. Replace the capacitor if it is bad. 5. If all of the above are operational, the wheel motor is bad. Replace it with new motor. UERV has power, but the exhaust blower does not operate. 1. Check that the blower belt is in place and tight. If it is loose, tighten it. If it is broken replace it. 2. Verify the A130 circuit board terminals Exhaust 1 "A" (hot) and "B" (common) are outputting 24 volts to K163 contactor terminal "A" and "B", and that the contacts are closed. 3. Verify power to B26 exhaust blower motor though J/P151 plug assembly. 4. On direct drive models, verify B26 wheel motor C25 capacitor is good. Replace if necessary. 5. If all of the above are operational, the exhaust motor is bad. Replace it with new motor. 2. a. 1. Check the linkage from the B29 damper motor to the UERV wheel. 2. Verify shipping retainers are removed. 3. Verify the S122 economizer end switch is closed. The switch is located on the damper and closes when the damper moves from minimum position to the economizer position (field adjustable). 4. Verify the B29 damper motor has 24 volts to terminals "B" and "T1" through J/P160 plug assembly 5. If all of the above are operational, replace the damper motor. UERV has power, but the optional motorized fresh air damper does not open. 1. Verify 24 volts to the A130 circuit board terminals XFORMER "+" and "-". 2. Check that the blower belt is in place and tight on belt drive models. Tighten it if it is loose. Replace it if it is broken. Verify 24 volts to A130 circuit board terminals TB 37 numbers "1" and "3". Terminal "1" is the "hot" and "3" is the "common" side of the power source from activation power source (a/c unit, energy management control, etc.). Typically, "1" would be from the blower contactor on an a/c unit. 3. Verify 24 volts to B30 motorized outdoor air motor through J/P160 plug assembly. Verify the A130 circuit board terminals Fresh "A" (hot) and "B" (common) are outputting 24 volts to 4. If all of the above are operational, replace the outdoor air damper motor. Energy Recovery Mode of operation. a. b. The fresh air blower is not operational in the economizer mode. UERV has power, but the wheel does not rotate out of airstream during economizer operation. UERV has power, but the fresh air blower does not operate. 1. Economizer Mode of operation. Subject to change without notice. Printed in U.S.A. Copyright © January 24, 2013 by Johnson Controls, Inc. All rights reserved. Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069 903106-UTG-A-0912 Supersedes: 246681-YTG-C-0611
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Create Date : 2000:05:02 11:22:59Z Creator : FrameMaker 11.0.1 Modify Date : 2013:01:24 11:30:39-06:00 Language : en XMP Toolkit : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27 Creator Tool : FrameMaker 11.0.1 Metadata Date : 2013:01:24 11:30:39-06:00 Format : application/pdf Title : untitled Producer : Acrobat Distiller 11.0 (Windows) Document ID : uuid:74082c9e-5ee5-4e88-aa57-eb9d4fd8f7b0 Instance ID : uuid:88969377-aae0-48eb-83f1-34cabda419c6 Page Mode : UseOutlines Page Count : 48EXIF Metadata provided by EXIF.tools