York Pcg4 Packaged Unit Technical Guide 5005562 YTG B 0715

2015-09-09

: York Pcg4-Packaged-Unit-Technical-Guide york-pcg4-packaged-unit-technical-guide-812579 york pdf

Open the PDF directly: View PDF PDF.
Page Count: 20

DownloadYork Pcg4-Packaged-Unit-Technical-Guide 5005562-YTG-B-0715  York-pcg4-packaged-unit-technical-guide
Open PDF In BrowserView PDF
5005562-YTG-B-0715

DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.

FEATURES

TECHNICAL GUIDE
SINGLE PACKAGE
AIR CONDITIONER/GAS HEAT
14 SEER – R-410A
2 THRU 5 NOMINAL TONS
50 - 125 MBH HEAT INPUT

MODELS: PCG4*24 THRU 60

• Operating Efficiency - All PCG4 model gas units provide a
minimum AFUE of 81.0% in heating and 14.0 SEER, 11.0
EER rating for cooling operation. All models meet California
Low-Nox requirements of 40 ng/joule emission level for Air
Quality Management Districts.
• On Site Flexibility - All model sizes use a compact design
cabinet in one of two footprints. This provides installer flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
insure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.

®

Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at

www.upgnet.com and www.york.com
Additional rating information can be found at:

www.ahridirectory.org
WARRANTY SUMMARY*
Extended 10-Years limited parts and compressor warranty
Lifetime gas heat exchanger warranty with registration.
* Extended warranty requires online registration within 90 days of purchase for
replacement or closing for new home purchase. See limited warranty certificate
in User’s Information Manual for details.

• Utility Connections Made Easy - Gas and electric utility
access provided through the bottom or the side of the unit.
Utility connections can be made quickly and with a minimum
amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the evaporator coil to collect
and drain all condensate, preventing build-up of stagnant
condensate. The condensate pan conforms to ASHRAE 6289 standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder
paint finish insure less fading when exposed to sunlight, and
provides superior corrosion resistance (1000 hour salt spray
tested).
Continued on next page.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

5005562-YTG-B-0715
• Full Perimeter Base Rails - The easily removable base rails
provide a solid foundation for the entire unit and protects the
unit during shipment. The rails provide fork lift access from all
sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On
applications where the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications
where height is limited, the base rails may be removed by
removing 2 screws in each corner.
• More Attractive Appearance - A single-piece top cover
containing a top-discharge outdoor fan arrangement requires
less square footage on installation and provides a wider variety of installations. The one-piece design adds greater water
integrity. Rounded corners with water drip edges add to the
attractive appearance.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping. This
allows compact location on multi-unit applications.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design. This design strategically places embossments in the pan for optimum strength
and rigidity.
• Fan System - All models operate over a wide range of
design conditions with a standard ECM indoor fan motor.
These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements.
The cooling speed is factory-set and can be field-adjusted to
a second speed. The heating speed is factory set to maintain
mid point rise at the units heating input, but can be field
adjusted. This allows maximum comfort conditions.
• Simple Control Circuit - A low voltage gas heat printed circuit board contains a status/diagnostic indicator light. Field
thermostat wiring connects to color coded leads using twist
on wire connections. Cooling controls use contactor and
relays for simple application and troubleshooting. Mate-nlock plug connectors are used. The electrical control box is
not located in the compressor compartment. The controls are
mounted to allow the separate access panel to be removed
for trouble shooting and maintenance without affecting the
normal system operating pressures. All wiring internal to the
unit is color/number coded.

sure relief valve and a temperature sensor which protect the
compressor if undesirable operating conditions occur.
• Pressure Switches - A high pressure switch is standard in
all units. When abnormal conditions are sensed through the
pressure switch, the unit will lock out preventing any further
operation until reset or problem is corrected.
• Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat transfer
for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils use tin-coated copper
tubing with aluminum fins for effective heat transfer.
• Heat Exchangers - Gas heat exchangers use corrosionresistant, stainless-steel tubular construction to provide longlife, trouble-free operation. Gas heat exchangers are offered
with lifetime warranties as standard with registration.
• Post Purge Induced Draft Combustion - Exhausts combustion products from the heat exchanger upon completion
of the heating cycle to prolong the heat exchanger life.
• Spark To Burner Ignition - No pilot assembly required,
which provides more consistent ignition in gas heating mode.
This ignition is highly reliable, durable and eliminates nuisance lockouts.
• Multi Port In-shot Burners - No field adjustment is required
to mix the air and gas for natural gas or propane use. These
burners are constructed of high-grade corrosion-resistant,
aluminized steel.
• Low Maintenance - Long life, permanently lubricated outdoor and evaporator fan motor bearings need no annual
maintenance, adding greater reliability to the unit. Slide-out
blower assembly can be easily removed for cleaning.
• Easy Service Access - Individual access panels covering
the electrical and gas controls makes servicing easy. Removing this panel will allow easy removal of the blower assembly
for maintenance and ease of troubleshooting.
• Replacement Parts - The installer requires no special training to replace any of the components of these units and the
number of new components have been reduced to minimize
the inventory of unique parts.
• Loss of Charge Sensor (S1-2LC00024) - Kit provides Loss
of Charge sensor and wiring to provide safe shutdown of
compressor.
• Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PHE4
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PCE4 price pages
for more details.

• Protected Compressor - The compressor is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high pres-

2

Johnson Controls Unitary Products

5005562-YTG-B-0715

NOMENCLATURE
PCG

4

A

24

50

2

X

1

A

1

2

3

4

5

6

7

8

9

1. Model Family
PCG - packaged A/C with gas heat,
PHG - packaged heat pump with gas heat,
PCE - packaged A/C with electric heat,
PHE - packaged heat pump with electric heat

5. Gas Heating Input BTU/Hr x 1000
050 = 50,000 BTU/Hr. input, blank = electric heat

2. Nominal Cooling Efficiency
4 = 14 SEER, 6 = 16 SEER, etc.

7. NOx Approval
X = low-NOx, blank = not low-Nox

3. Cabinet Size
A = small 35 x 51, B = large 45 x 51

8. Generation Level
1 = first generation

4. Nominal Air Conditioning Cooling Capacity BTUx1000
24 = 24,000 BTU, etc.

9. Revision Level
A = original release, B = second release

6. Voltage-Phase-Frequency
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60

Examples:
PCG4B421002X1A is a packaged A/C with gas heat, 14 SEER, 3-1/2 ton, large cabinet, single-stage heat, 100,000 BTU gas heat, 230 volt, single
phase, low-NOx model (first generation, first release)

COMPONENT LOCATION
FAN MOTOR

OUTDOOR FAN

COIL GUARD PANEL
OUTDOOR COIL
(Behind Panel)

CONTROL BOARD
TRANSFORMER

BLOWER MOTOR

HIGH VOLTAGE
CONTACTOR

TXV

PRESSURE SWITCH

INDOOR COIL

DRAFT INDUCER BLOWER

INDOOR BLOWER

GAS VALVE
COMPRESSOR

GAS HEAT
EXCHANGER

REMOVABLE
BASE RAILS

BURNER
ASSEMBLY
A0297-001

Unit Limitations
Unit Limitations
Model

Unit Voltage

Applied Voltage

Outdoor DB Temp

Min

Max

Max (°F)

PCG4A24

208/230-1-60

187

252

125

PCG4A30

208/230-1-60

187

252

125

PCG4A36

208/230-1-60

187

252

125

PCG4A42

208/230-1-60

187

252

125

PCG4B48

208/230-1-60

187

252

125

PCG4B60

208/230-1-60

187

252

125

Johnson Controls Unitary Products

3

5005562-YTG-B-0715

ACCESSORIES
• Propane Conversion Kit (S1-1NP0702, S1-1NP0701) - Kit
includes burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural
gas to propane.
• Economizer for Downflow Applications
(S1-2EE04708424, S1-2EE04708524) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor and relief damper.
Separate field accessories of single enthalpy and dual
enthalpy are also available.
• Economizer for Horizontal Applications
(S1-2EE04708624, S1-2EE04708724) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor and relief damper.
Separate field accessories of single enthalpy and dual
enthalpy are also available.
• Single/Dual Enthalpy Sensor (S1-2EC04700624) - Sensor
replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry
bulb temperature from outdoors plus the enthalpy content of
the outdoor air.
• CO2 Sensor Kit (S1-2AQ04700824) - Sensor kit detects
CO2 levels automatically and overrides the economizer
when CO2 levels rise above the preset limits.
• Outdoor Temp. Sensor Kit
(S1-2EC04700724S1-2EC04700724v) - Additional outdoor
air temp sensor kit used with economizers.
• Filter/Frame Kit (Single Phase Only)
(S1-1FF0602, S1-1FF0601) - Kit contains the necessary
hardware to field install return air filters into the base unit.
The filter rack is suitable for either 1" or 2" filters. (filters not
supplied) This kit is available for single phase horizontal or
vertical duct applications.
• Motorized Fresh Air Damper
(S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/
return applications. Damper capable of providing 0% through
50% of outdoor air (field supplied). Closes on power loss,
includes hood and screen assembly.

4

• Rectangle to Round (Horizontal) Adapter
(S1-1AK0110, S1-1AK0111) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit over current horizontal duct
openings on the base unit. Transition is from rectangle to 12"
round for the 1AK0110 kit and from rectangle to 14" round for
the 1AK0111 kit.
• Rectangle to Round (Downflow) Adapter
(S1-1AK0108, S1-1AK0109) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit into current downflow duct
openings on the roof curb. Transition is from rectangle to 16"
round for the 1AK0108 kit and from rectangle to 18" round for
the 1AK0109 kit.
• Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 8 inch high roof curbs.
• Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 14 inch high roof curbs.
• Manual Outdoor Damper
(S1-1FA0502, S1-1FA0501) - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct
mounted side supply/return applications. Includes hood and
screen assembly.
• Wall Thermostat - The units are designed to operate with
standard, 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat/single
stage cool thermostats - with or without the economizer.
• Low Ambient Kit (S1-2LA04700824) - Kit provides necessary hardware to convert unit to operate in cooling cycle
down to 0º F. Standard unit operation 45º F.
• Transformer Kit (S1-2EC06700124) - Kit provides necessary hardware to provide single phase models from factory
furnished 40 VA transformer capability to 75 VA transformer
capability. (Required on installations with economizer or
motorized damper).
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.

Johnson Controls Unitary Products

5005562-YTG-B-0715

GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. Package units give you the flexibility and
choices you need in today’s market. These packaged cooling/
heating air conditioners are designed for outdoor installation.
Only utility and duct connections are required at the point of
installation. The single-stage gas fired heaters have stainless
steel tubular heat exchangers and spark to burner ignition.
They are available in natural gas with field conversion to
propane.

DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heating units, designed for outdoor installation.
For SEER ratings, refer to technical literature. They shall have
built in, equal size, field convertible duct connections for supply/
return or horizontal supply/return. The units shall be factory
wired, piped, charged with R-410A Refrigerant and factory
tested prior to shipment. All unit wiring shall be both numbered
and color coded. All models shall be rated in accordance with
DOE and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed and classified to ANSI
Z21.47/CAN/ CSA 2.3 standards and UL 1995/CAN/CSA No.
236-M90 standards.

UNIT CABINET
Unit cabinet shall be constructed of G-90 galvanized, powderpainted steel, certified at 1000 hours salt spray test per ASTMB117 standards. The unit top shall be a single piece design,
with drip edges and no-seam corners to provide optimum water
integrity. Unit shall have a rigidly mounted outdoor coil guard to
provide protection from objects and personnel after installation.
Indoor blower section shall be insulated with foil-faced or foam
insulation, fastened to prevent insulation from entering the air
stream. Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, for truck access and proper
sealing on roof curb applications. Base rails shall be easily
removable, when required to lower unit height. Filters shall be
field installed, furnished and be accessible through a removable
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit. Condensate pan shall be internally sloped and
conform to ASHRAE 62-89 self-draining standards, with 3/4”
NPT female ridged mount connection.
Indoor Blower Assembly - Fan shall be direct drive design.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance. Fan assembly
shall be a slide-out design for easy removal and cleaning.
Indoor blower motors shall be equipped with a standard high
efficiency brushless DC motor (constant torque) also known as
a standard ECM motor.

Johnson Controls Unitary Products

Outdoor Fan Assembly - The outdoor fan shall be of the
direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated bearings and internally protected
against overload conditions.

REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas
cooled and have a voltage range of +/- 10% of the unit
nameplate voltage.
b. Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally isolated on a
dedicated, independent mounting.
Coils:
a. Indoor coils shall have aluminum plate fins mechanically
bonded to seamless internally enhanced tin-coated copper tubes with all joints brazed.
b. Indoor coil shall be of the direct expansion, draw through
design.
c. Outdoor coils shall have aluminum plate fins mechanically
bonded to seamless internally enhanced copper tubes
with all joints brazed.
d. Outdoor coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Thermal expansion devices (TXV's) shall be factory
mounted and provided.
b. Filter/strainer to eliminate any foreign matter.

GAS HEATING SECTION
Heat exchanger and exhaust system shall be constructed of
corrosion-resistant materials and shall be designed with
induced draft combustion with post purge logic and redundant
main gas valve. The heat exchanger shall be of the tubular
type, constructed of stainless steel for corrosion resistance and
allowing minimum mixed air entering temperature of 40 ºF.
Burners shall be of the in-shot type, constructed of
aluminumized steel. All gas piping shall enter the unit cabinet at
a single location through either the side or bottom, without any
field modifications. An integrated control board shall provide
timed control of indoor fan functioning and burner ignition.
Heating section shall be provided with the following minimum
protection:
a. Primary high-temperature limit switch.
b. Induced draft pressure switch.
c. Flame roll out switch(s) (manual reset).
d. Flame proving controls.
All gas heat models will meet the California requirement for
emissions of less than 40 nanograms per Joule (California
requirement on single phase models only).

5

5005562-YTG-B-0715

PHYSICAL DATA
COMPONENT
NOMINAL TONNAGE
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
AHRI net capacity (MBH)
EER
SEER
Nominal CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
AHRI Gas Heat Performance
Heating model
Heat input (K Btu)
Heat output (K Btu)
AFUE %
No. burners
No. stages
Temperature Rise Range (°F)
Max. Static Pressure (in. w.c.)
Max. Outlet Air Temp. (°F)
Gas piping connection (in.)
Dimensions (inches)
Length
Width
Height
Operating WT. (lbs.)
Compressors
Type
Condenser Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Evaporator Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
Condenser Fan Data
Fan diameter (Inch)
Type
Drive type
No. speeds
Motor HP each
RPM
Nominal total CFM
Direct Drive Evaporator Fan Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size

PCG4A24
2.0

PCG4A30
2.5

PCG4A36
3.0

23.7
22.8
11.0
14.0
800
2.1
R410A
5-4

30.1
29.0
11.0
14.0
1000
2.6
R410A
9-2

37.2
34.6
11.0
14.0
1200
3.2
R410A
8-3

MODELS
PCG4A42
3.5
43.5
41.0
11.0
14.0
1400
3.8
R410A
9-4

PCG4B48
4.0

PCG4B60
5.0

47.7
45.5
11.0
14.0
1600
4.2
R410A
14-4

55.0
52.5
11.0
14.0
2000
4.8
R410A
14-2

50
75
50.0 75.0
40
60
81.0 81.0
2
3
1
1
40-70
0.5
180
1/2

50
75
50
75
100
75
100
65
100 125
65
100 125
50.0 75.0 50.0 75.0 100.0 75.0 100.0 65.0 100.0 125.0 65.0 100.0 125.0
40
60
40
60
80
60
80
52
80
100
52
80
100
81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0
2
3
2
3
4
3
4
2
3
4
2
3
4
1
1
1
1
1
1
1
1
1
1
1
1
1
40-70
35-65
40-70
40-70
40-70
40-70
0.5
0.5
0.5
0.5
0.5
180
180
180
180
180
1/2
1/2
1/2
1/2
1/2

51-1/4
35-3/4
47
359 366

51-1/4
35-3/4
47
379 386

51-1/4
35-3/4
47
415 422 426

51-1/4
35-3/4
49
442 446

51-1/4
45-3/4
53
495 503 508

51-1/4
45-3/4
55
522 530 535

Recip

Recip

Recip

Scroll

Scroll

Scroll

15.1
2
16
3/8
Interlaced

17.0
3
16
3/8
Interlaced

17.0
3
16
3/8
Interlaced

17.0
3
16
3/8
Interlaced

23.8
3
16
3/8
Interlaced

26.0
3
16
3/8
Interlaced

3.4
2
16
3/8
Interlaced
TXV

3.4
3
16
3/8
Interlaced
TXV

3.4
3
16
3/8
Interlaced
TXV

4.4
3
16
3/8
Interlaced
TXV

4.4
3
16
3/8
Interlaced
TXV

4.4
3
16
3/8
Interlaced
TXV

24
Prop
Direct
1
1/4
850
2400

24
Prop
Direct
1
1/4
850
2400

24
Prop
Direct
1
1/4
850
2400

24
Prop
Direct
1
1/4
850
2400

26
Prop
Direct
1
1/3
850
3200

26
Prop
Direct
1
1/3
850
3200

11 x 8
Centrifugal
1/3
1/2
1200 Max
48

11 x 8
Centrifugal
1/3
1/2
1200 Max
48

11 x 10
Centrifugal
3/4
1200 Max
48

11 x 10
Centrifugal
3/4
1200 Max
48

11 x 10
Centrifugal
1
1200 Max
48

11 x 10
Centrifugal
1/2
3/4
1200 Max
48

Filters
Quantity - Size

6

Field-supplied external filters must be sized so as not to exceed 300 FPM air velocity through disposable
filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. Filter sizes: A=20x20, B=20x30.

Johnson Controls Unitary Products

5005562-YTG-B-0715

COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
ENTERING AIR
IDDB
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.

PCG4A24
80
57
30.0
30.0
1.48
25.9
25.6
1.57
26.9
26.9
1.77
22.0
21.7
1.86
22.1
22.1
2.07
19.3
19.3
2.21
16.6
16.6
2.36
13.9
13.9
2.50

80
62
33.4
28.6
1.47
29.1
23.6
1.58
28.4
25.8
1.78
23.8
20.6
1.87
22.8
22.7
2.07
19.9
19.8
2.21
17.0
17.0
2.35
14.1
14.1
2.49

1000
75
62
33.4
23.8
1.47
28.8
19.9
1.57
28.2
20.9
1.78
23.4
17.1
1.87
22.5
18.3
2.06
19.2
16.4
2.20
16.0
14.6
2.32
12.8
12.8
2.45

80
67
36.7
23.7
1.46
32.1
19.9
1.57
31.4
21.1
1.62
26.5
17.4
1.89
25.5
18.8
2.09
22.0
17.2
2.24
18.5
15.6
2.38
15.1
14.0
2.53

80
72
39.8
18.7
1.44
35.4
16.0
1.56
35.3
16.8
1.61
29.9
13.7
1.95
28.8
14.1
2.21
24.7
11.9
2.34
20.7
9.6
2.47
17.6
9.4
2.59

80
57
27.4
27.4
1.44
25.9
25.7
1.58
24.4
24.0
1.72
22.3
22.1
1.85
20.2
20.1
1.98
17.8
17.8
2.12
15.5
15.4
2.25
13.1
13.1
2.39

80
62
30.9
25.0
1.44
28.7
23.6
1.58
26.6
22.2
1.73
24.1
20.9
1.86
21.6
19.5
2.00
18.8
17.4
2.13
16.1
15.4
2.26
13.4
13.4
2.39

800
75
62
31.2
20.9
1.44
28.7
19.7
1.58
26.2
18.5
1.73
23.7
17.2
1.86
21.3
16.0
2.00
18.3
14.4
2.12
15.4
12.9
2.24
12.4
11.4
2.36

80
67
34.3
21.0
1.42
31.9
19.8
1.54
29.4
18.6
1.65
26.8
17.5
1.84
24.2
16.4
2.03
21.0
14.9
2.17
17.9
13.6
2.31
14.8
12.2
2.45

80
72
37.6
16.9
1.40
35.4
16.0
1.53
33.2
15.1
1.65
30.2
13.8
1.88
27.3
12.6
2.11
23.7
10.8
2.25
20.2
9.1
2.38
17.2
8.4
2.52

80
57
24.9
24.9
1.41
25.9
25.9
1.59
21.9
21.2
1.66
22.6
22.5
1.84
18.3
18.2
1.90
16.3
16.2
2.03
14.3
14.3
2.15
12.3
12.3
2.27

80
62
28.4
21.3
1.41
28.4
23.5
1.59
24.8
18.6
1.68
24.4
21.1
1.86
20.3
16.4
1.94
17.7
15.1
2.06
15.1
13.8
2.17
12.6
12.6
2.29

600
75
62
29.0
18.1
1.40
28.6
19.5
1.59
24.2
16.0
1.67
24.1
17.3
1.86
20.1
13.6
1.94
17.3
12.4
2.05
14.7
11.1
2.17
12.0
9.9
2.28

80
67
31.8
18.2
1.39
31.6
19.7
1.50
27.5
16.1
1.69
27.2
17.5
1.79
22.9
14.0
1.97
20.0
12.7
2.11
17.3
11.5
2.24
14.5
10.3
2.37

80
72
35.4
15.1
1.37
35.3
16.0
1.49
31.1
13.3
1.69
30.5
13.9
1.81
25.8
11.1
2.00
22.7
9.8
2.15
19.7
8.6
2.30
16.7
7.4
2.45

1200
75
62
43.2
32.6
1.71
38.8
30.5
1.89
34.3
28.4
2.08
29.8
26.1
2.24
25.3
23.7
2.41
20.6
19.5
2.56
16.0
15.5
2.71
11.4
11.4
2.86

80
67
44.9
31.1
1.68
41.6
29.8
1.88
38.3
28.5
2.08
34.2
26.7
2.27
30.1
24.8
2.45
25.9
22.4
2.61
21.8
20.1
2.77
17.7
17.7
2.92

80
72
48.3
24.5
1.66
45.6
23.4
1.86
42.9
22.3
2.06
38.6
20.6
2.27
34.3
18.9
2.47
28.7
16.9
2.67
23.3
14.9
2.86
17.8
13.0
3.06

80
57
37.8
36.9
1.67
34.4
34.0
1.83
31.1
31.1
1.99
27.8
27.8
2.15
24.4
24.4
2.32
20.3
20.3
2.49
16.3
16.3
2.66
12.3
12.3
2.83

80
62
41.0
34.5
1.66
37.6
32.5
1.83
34.1
30.5
2.00
30.3
28.1
2.16
26.4
25.7
2.31
22.8
22.3
2.49
19.3
19.0
2.65
15.7
15.7
2.82

1000
75
62
40.8
29.5
1.65
36.9
27.6
1.83
33.0
25.6
2.02
28.8
23.4
2.14
24.5
21.2
2.26
20.0
17.8
2.44
15.6
14.5
2.61
11.2
11.2
2.79

80
67
43.8
28.8
1.65
40.5
27.3
1.83
37.1
25.8
2.02
33.2
24.0
2.19
29.2
22.2
2.37
24.7
20.0
2.50
20.3
17.8
2.62
15.9
15.7
2.73

80
72
47.9
23.6
1.62
44.1
25.2
1.82
40.3
26.9
2.02
36.6
21.9
2.22
32.8
17.0
2.41
27.8
15.2
2.61
23.0
13.5
2.80
18.2
11.7
2.99

80
57
34.5
33.6
1.62
31.4
31.0
1.78
28.4
28.4
1.94
25.5
25.5
2.09
22.6
22.6
2.24
19.2
19.2
2.41
15.9
15.9
2.57
12.6
12.6
2.74

80
62
38.4
30.5
1.61
35.2
28.7
1.77
31.9
26.9
1.93
28.2
25.0
2.08
24.6
23.1
2.24
20.8
19.9
2.40
17.2
16.7
2.56
13.6
13.6
2.72

800
75
62
38.5
26.4
1.60
35.1
24.6
1.78
31.7
22.8
1.95
27.7
20.8
2.03
23.7
18.7
2.11
19.4
16.1
2.32
15.2
13.6
2.52
11.0
11.0
2.72

80
67
42.8
26.5
1.61
39.4
24.8
1.78
36.0
23.2
1.95
32.1
21.3
2.12
28.2
19.5
2.30
23.4
17.5
2.38
18.8
15.6
2.46
14.1
13.7
2.55

80
72
47.5
22.6
1.59
42.6
27.0
1.78
37.7
31.5
1.97
34.5
23.3
2.16
31.3
15.1
2.35
26.9
13.6
2.55
22.7
12.0
2.73
18.5
10.5
2.92

COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
ENTERING AIR
IDDB
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.

PCG4A30
80
57
41.0
40.2
1.71
37.4
37.0
1.88
33.8
33.8
2.04
30.1
30.1
2.22
26.3
26.3
2.39
21.4
21.4
2.57
16.7
16.7
2.74
12.0
12.0
2.91

Johnson Controls Unitary Products

80
62
43.6
38.5
1.71
40.0
36.3
1.89
36.4
34.2
2.06
32.3
31.2
2.23
28.3
28.3
2.39
24.8
24.8
2.57
21.3
21.3
2.74
17.9
17.9
2.91

7

5005562-YTG-B-0715

COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
ENTERING AIR
IDDB
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.

PCG4A36
80
57
45.3
45.3
2.15
42.0
42.0
2.39
38.7
38.7
2.63
35.3
35.3
2.87
31.9
31.9
3.11
26.5
26.5
3.43
21.4
21.4
3.74
16.2
16.2
4.05

80
62
48.1
43.2
2.16
43.7
40.3
2.41
39.3
37.4
2.66
35.4
34.4
2.90
31.5
31.5
3.14
26.8
26.8
3.39
22.3
22.3
3.65
17.7
17.7
3.90

1600
75
62
48.0
36.0
2.16
43.8
34.1
2.40
39.6
32.1
2.64
35.5
30.0
2.88
31.5
28.0
3.12
26.3
24.0
3.35
21.3
20.2
3.57
16.3
16.3
3.79

80
67
53.1
36.5
2.15
48.6
34.5
2.41
44.1
32.4
2.67
39.4
30.1
2.93
34.8
27.8
3.20
29.0
24.4
3.43
23.4
21.1
3.67
17.7
17.7
3.90

80
72
54.6
27.9
2.15
52.4
26.6
2.40
50.1
25.4
2.65
45.0
23.6
2.93
39.8
21.8
3.21
33.7
19.3
3.48
27.7
17.0
3.75
21.7
14.6
4.01

80
57
42.2
42.2
2.07
39.4
39.4
2.30
36.6
36.6
2.52
33.6
33.6
2.75
30.5
30.5
2.99
26.0
26.0
3.27
21.6
21.6
3.54
17.2
17.2
3.81

80
62
46.3
39.5
2.07
42.5
36.9
2.31
38.6
34.3
2.55
34.8
32.0
2.79
31.0
29.7
3.02
26.5
25.7
3.27
22.2
21.8
3.50
17.9
17.9
3.74

1400
75
62
46.2
33.3
2.07
42.4
31.3
2.31
38.5
29.3
2.54
34.8
27.5
2.77
31.0
25.7
3.00
26.2
22.6
3.23
21.4
19.7
3.44
16.7
16.7
3.66

80
67
51.3
33.4
2.06
47.1
31.5
2.32
42.9
29.5
2.57
38.7
27.5
2.83
34.6
25.5
3.08
29.1
22.8
3.32
23.8
20.2
3.54
18.5
17.6
3.77

80
72
53.5
26.1
2.05
51.0
24.9
2.31
48.4
23.6
2.56
43.8
21.9
2.83
39.2
20.2
3.10
33.5
18.0
3.37
28.0
15.9
3.63
22.5
13.8
3.88

80
57
39.2
39.2
1.99
36.8
36.8
2.20
34.5
34.5
2.41
31.9
31.9
2.64
29.2
29.2
2.87
25.5
25.5
3.11
21.8
21.8
3.34
18.2
18.2
3.57

80
62
44.6
35.8
1.99
41.2
33.5
2.22
37.9
31.1
2.45
34.2
29.5
2.68
30.5
27.9
2.91
26.3
24.5
3.14
22.2
21.3
3.36
18.0
18.0
3.58

1200
75
62
44.5
30.6
1.99
41.0
28.6
2.22
37.4
26.6
2.44
34.0
25.0
2.67
30.6
23.4
2.89
26.0
21.2
3.11
21.5
19.1
3.32
17.0
17.0
3.53

80
67
49.5
30.4
1.97
45.6
28.5
2.22
41.7
26.7
2.47
38.0
25.0
2.72
34.3
23.3
2.97
29.2
21.3
3.20
24.2
19.3
3.42
19.2
17.4
3.65

80
72
52.4
24.4
1.95
49.5
23.1
2.21
46.7
21.8
2.46
42.7
20.2
2.73
38.6
18.7
2.99
33.4
16.7
3.25
28.3
14.8
3.50
23.2
13.0
3.76

1600
75
62
50.2
38.5
2.51
47.0
36.4
2.74
43.7
34.3
2.97
40.1
32.8
3.28
36.5
31.3
3.59
31.8
28.4
4.01
27.3
25.6
4.42
22.8
22.8
4.83

80
67
55.5
39.6
2.53
52.1
37.7
2.77
48.7
35.9
3.01
44.9
33.9
3.31
41.1
32.0
3.60
36.1
29.5
4.03
31.1
27.2
4.45
26.2
24.8
4.87

80
72
61.9
32.6
2.56
58.0
30.8
2.80
54.1
29.0
3.04
50.0
27.3
3.36
46.0
25.5
3.67
40.6
23.3
4.09
35.3
21.2
4.50
30.1
19.1
4.91

80
57
46.5
45.5
2.42
44.4
43.7
2.55
42.2
41.9
2.67
39.3
39.2
2.98
36.5
36.5
3.29
32.5
32.5
3.72
28.7
28.7
4.14
24.9
24.9
4.57

80
62
48.6
42.1
2.44
45.6
40.5
2.68
42.6
38.8
2.93
40.0
36.1
3.24
37.4
33.3
3.54
33.0
30.3
3.97
28.8
27.4
4.38
24.5
24.5
4.79

1400
75
62
48.5
36.2
2.43
45.6
34.4
2.66
42.6
32.7
2.89
39.3
31.0
3.20
35.9
29.4
3.51
31.5
26.9
3.94
27.2
24.4
4.35
22.9
22.0
4.76

80
67
53.7
37.0
2.45
50.5
35.3
2.70
47.4
33.6
2.94
43.8
31.2
3.24
40.2
28.9
3.54
35.5
27.0
3.97
30.9
25.2
4.37
26.4
23.3
4.78

80
72
59.6
30.7
2.47
56.1
29.2
2.71
52.5
27.6
2.94
48.8
25.9
3.26
45.1
24.1
3.57
40.0
22.1
3.99
35.0
20.1
4.41
30.1
18.1
4.82

80
57
43.7
43.1
2.35
42.2
41.9
2.36
40.6
40.6
2.38
38.0
38.0
2.69
35.4
35.4
3.00
31.7
31.7
3.44
28.2
28.2
3.86
24.7
24.7
4.29

80
62
46.9
39.2
2.36
44.1
37.7
2.61
41.3
36.3
2.86
38.2
34.5
3.17
35.1
32.7
3.48
31.2
29.6
3.90
27.4
26.7
4.31
23.7
23.7
4.71

1200
75
62
46.8
33.9
2.36
44.1
32.5
2.59
41.4
31.0
2.82
38.4
29.3
3.13
35.4
27.6
3.44
31.2
25.4
3.86
27.1
23.3
4.28
23.0
21.2
4.69

80
67
51.8
34.4
2.38
48.9
32.8
2.62
46.0
31.3
2.87
42.7
28.5
3.18
39.3
25.8
3.48
34.9
24.5
3.90
30.7
23.1
4.30
26.5
21.8
4.70

80
72
57.3
28.7
2.38
54.1
27.5
2.61
51.0
26.2
2.84
47.6
24.5
3.15
44.1
22.8
3.47
39.4
20.9
3.90
34.7
19.0
4.31
30.1
17.2
4.73

COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO. PCG4A42
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
49.4 50.2
55 / 45
S.C.
47.8 45.0
K.W.
2.50 2.52
T.C.
46.6 47.0
65 / 55
S.C.
45.5 43.2
K.W.
2.73 2.76
T.C.
43.8 43.9
75 / 63
S.C.
43.3 41.4
K.W.
2.97 3.00
T.C.
40.7 41.8
85 / 69
S.C.
40.4 37.7
K.W.
3.28 3.30
T.C.
37.6 39.7
95 / 75
S.C.
37.6 33.9
K.W.
3.59 3.60
T.C.
33.3 34.8
105 / 83
S.C.
33.3 31.0
K.W.
4.01 4.03
T.C.
29.2 30.1
115 / 89
S.C.
29.2 28.2
K.W.
4.43 4.45
T.C.
25.1 25.4
125 / 95
S.C.
25.1 25.4
K.W.
4.84 4.86

8

Johnson Controls Unitary Products

5005562-YTG-B-0715

COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
ENTERING AIR
IDDB
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.

PCG4B48
80
57
58.1
57.1
2.21
54.4
54.0
2.46
50.8
50.8
2.71
46.5
46.5
3.05
42.2
42.2
3.39
37.2
37.2
3.85
32.4
32.4
4.31
27.6
27.6
4.76

80
62
61.5
53.6
2.21
56.8
51.5
2.47
52.2
49.5
2.73
47.2
45.8
3.06
42.2
42.2
3.38
37.0
37.0
3.85
31.9
31.9
4.31
26.9
26.9
4.76

1600
75
62
60.2
44.4
2.20
55.7
42.4
2.46
51.2
40.4
2.72
46.2
37.7
3.05
41.2
35.0
3.38
35.3
31.2
3.85
29.6
27.5
4.30
23.9
23.9
4.76

80
67
66.8
44.1
2.23
62.2
42.4
2.49
57.6
40.6
2.75
52.4
38.1
3.08
47.2
35.6
3.41
40.9
33.3
3.88
34.9
31.0
4.33
28.8
28.8
4.79

80
72
70.0
33.9
2.25
66.3
32.4
2.50
62.5
30.9
2.76
57.6
28.7
3.09
52.7
26.5
3.42
46.8
24.7
3.89
41.1
23.0
4.35
35.5
21.2
4.80

80
57
55.6
54.5
2.20
52.1
51.6
2.44
48.7
48.7
2.69
44.6
44.6
3.04
40.6
40.6
3.38
36.1
36.1
3.85
31.7
31.7
4.30
27.3
27.3
4.76

80
62
59.5
49.9
2.21
55.1
48.0
2.46
50.7
46.0
2.72
46.0
42.9
3.05
41.3
39.8
3.38
36.2
35.2
3.85
31.2
30.7
4.31
26.2
26.2
4.77

1400
75
62
58.7
42.1
2.20
54.4
40.1
2.45
50.1
38.2
2.71
45.1
35.5
3.04
40.2
32.9
3.38
35.0
30.1
3.85
30.1
27.3
4.30
25.1
24.6
4.76

80
67
65.1
41.9
2.23
60.9
40.2
2.49
56.6
38.5
2.75
51.5
35.9
3.08
46.4
33.4
3.41
40.6
31.3
3.88
35.1
29.3
4.33
29.6
27.4
4.79

80
72
70.0
33.5
2.24
65.7
31.5
2.49
61.4
29.5
2.75
56.8
27.5
3.09
52.2
25.4
3.42
46.5
23.7
3.89
41.0
22.0
4.34
35.6
20.3
4.80

80
57
53.1
51.9
2.18
49.8
49.2
2.43
46.5
46.5
2.68
42.8
42.8
3.02
39.0
39.0
3.36
34.9
34.9
3.84
30.9
30.9
4.30
27.0
27.0
4.76

80
62
57.5
46.3
2.20
53.4
44.5
2.46
49.3
42.6
2.71
44.9
40.0
3.05
40.5
37.4
3.38
35.4
33.4
3.86
30.5
29.5
4.31
25.5
25.5
4.77

1200
75
62
57.2
39.7
2.19
53.1
37.9
2.45
49.0
36.0
2.70
44.1
33.3
3.03
39.2
30.7
3.37
34.8
28.9
3.84
30.6
27.1
4.30
26.4
25.4
4.76

80
67
63.4
39.6
2.22
59.5
38.0
2.48
55.6
36.3
2.74
50.6
33.8
3.07
45.5
31.2
3.40
40.3
29.4
3.87
35.3
27.6
4.33
30.3
25.9
4.79

80
72
69.9
33.0
2.23
65.1
30.6
2.49
60.3
28.2
2.74
56.0
26.3
3.08
51.7
24.3
3.42
46.2
22.7
3.88
41.0
21.0
4.34
35.7
19.4
4.79

1600
75
62
65.2
49.1
3.43
28.9
23.1
3.74
57.7
46.1
4.05
52.8
43.8
4.45
47.9
41.5
4.84
39.9
35.7
5.41
32.1
30.0
5.97
24.4
24.4
6.53

80
67
68.7
46.2
3.43
32.9
23.1
3.76
65.7
46.2
4.09
60.0
44.0
4.48
54.3
41.8
4.86
46.0
37.8
5.42
38.0
33.9
5.96
30.0
30.0
6.49

80
72
72.9
34.9
3.41
36.7
17.6
3.76
73.2
35.2
4.11
60.4
41.4
4.47
47.5
47.5
4.83
44.7
39.3
5.41
42.0
31.3
5.98
39.3
23.4
6.55

80
57
60.4
60.4
3.28
56.7
56.7
3.57
53.0
53.0
3.87
26.5
26.5
4.26
46.0
46.0
4.66
41.5
41.5
5.23
37.1
37.1
5.79
32.7
32.7
6.35

80
62
64.1
54.7
3.29
60.5
53.5
3.59
56.9
52.3
3.88
52.5
49.3
4.28
48.1
46.3
4.68
42.6
41.4
5.25
37.2
36.6
5.80
31.9
31.9
6.35

1400
75
62
64.4
46.3
3.33
28.4
21.5
3.61
56.7
43.0
3.89
52.2
40.9
4.29
47.8
38.8
4.69
40.0
34.1
5.26
32.5
29.5
5.82
25.0
25.0
6.38

80
67
68.0
44.2
3.34
32.2
21.6
3.63
64.4
43.1
3.92
59.2
41.1
4.31
54.0
39.0
4.71
46.1
35.6
5.26
38.5
32.2
5.81
31.0
28.8
6.35

80
72
71.8
33.9
3.32
36.0
16.8
3.64
72.0
33.6
3.96
63.2
35.7
4.33
54.3
37.9
4.70
49.5
32.5
5.27
44.8
27.4
5.83
40.1
22.2
6.38

80
57
57.6
57.6
3.12
54.3
54.3
3.41
51.0
51.0
3.70
25.5
25.5
4.11
44.4
44.4
4.51
40.0
40.0
5.10
35.6
35.6
5.66
31.2
31.2
6.23

80
62
62.7
51.4
3.14
59.1
49.7
3.43
55.5
48.1
3.72
51.5
46.0
4.12
47.5
43.9
4.52
41.1
38.7
5.09
34.9
33.7
5.64
28.7
28.7
6.19

1200
75
62
63.6
43.4
3.23
27.9
20.0
3.48
55.7
40.0
3.73
51.6
38.0
4.13
47.6
36.1
4.53
40.1
32.5
5.11
32.9
29.1
5.67
25.6
25.6
6.24

80
67
67.2
42.2
3.24
31.6
20.0
3.50
63.1
40.0
3.76
58.4
38.1
4.15
53.6
36.3
4.55
46.2
33.3
5.11
39.0
30.5
5.66
31.9
27.6
6.21

80
72
70.6
32.8
3.23
35.4
16.0
3.52
70.7
32.0
3.80
65.9
30.1
4.19
61.1
28.2
4.57
54.3
25.7
5.13
47.6
23.4
5.67
41.0
21.0
6.21

COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
ENTERING AIR
IDDB
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.

PCG4B60
80
57
63.1
63.1
3.44
59.1
59.1
3.74
55.1
55.1
4.03
27.6
27.6
4.42
47.5
47.5
4.80
43.0
43.0
5.37
38.6
38.6
5.92
34.2
34.2
6.47

Johnson Controls Unitary Products

80
62
65.4
58.0
3.44
61.9
57.3
3.75
58.3
56.5
4.05
53.5
52.6
4.44
48.7
48.7
4.84
44.0
44.0
5.40
39.6
39.6
5.96
35.1
35.1
6.51

9

5005562-YTG-B-0715

DIMENSIONS

COIL GUARD

HIGH VOLTAGE
CONNECTION 7/8”
C
HIGH VOLTAGE
CONNECTION 1-3/32”

COMBUSTION AIR INTAKE
HEAT EXCHANGER ACCESS PANEL

COMPRESSOR
ACCESS PANEL

EXHAUST HOOD

CONDENSATE
DRAIN
BLOWER
ACCESS
PANEL

A

B
LOW VOLTAGE CONNECTION
GAS SUPPLY

CONTROL ACCESS
PANEL

A0296-001

Unit Dimensions
Dimensions

Model

A

B

C

PCG4A24

51-1/4

35-3/4

47

PCG4A30

51-1/4

35-3/4

47

PCG4A36

51-1/4

35-3/4

47

PCG4A42

51-1/4

35-3/4

49

PCG4B48

51-1/4

45-3/4

53

PCG4B60

51-1/4

45-3/4

55

Unit Clearances1 2
Direction

Distance (in.)

Direction

Top3

36

Power Entry (Right Side)

36

Side Opposite Ducts

36

Left Side

24

Duct Panel

0

Bottom4

1

1.
2.
3.
4.

10

Distance (in.)

A 1" clearance must be provided between any combustible material and the supply air duct work.
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.
Units may be installed on combustible floors made from class A, B or C roof covering materials.

Johnson Controls Unitary Products

5005562-YTG-B-0715
Indoor Blower Specifications
Motor

Model

HP

RPM

EFF.

SF

Frame

24050

1/3

Variable

0.8

1.0

48

24075

1/2

Variable

0.8

1.0

48

30050

1/3

Variable

0.8

1.0

48

30075

1/2

Variable

0.8

1.0

48

36050

1/2

Variable

0.8

1.0

48

36075

1/2

Variable

0.8

1.0

48

36100

3/4

Variable

0.8

1.0

48

42075

3/4

Variable

0.8

1.0

48

42100

3/4

Variable

0.8

1.0

48

48065

3/4

Variable

0.8

1.0

48

48100

3/4

Variable

0.8

1.0

48

48125

3/4

Variable

0.8

1.0

48

60065

1

Variable

0.8

1.0

48

60100

1

Variable

0.8

1.0

48

60125

1

Variable

0.8

1.0

48

Sound Performance
Model
(Tons)

Sound Rating1
dB (A)

125

250

500

1000

2000

4000

8000

PCG4A24

75

62.4

61.5

64.2

67.0

61.0

57.3

49.6

PCG4A30

75

60.5

61.6

64.8

66.9

60.9

56.0

49.7

PCG4A36

74

58.5

61.8

65.4

66.5

60.7

54.8

49.8

PCG4A42

74

63.5

63.9

62.3

65.0

64.0

54.1

46.6

PCG4B48

74

63.5

63.9

62.3

65.0

64.0

54.1

46.6

PCG4B60

76

72.3

65.0

63.9

64.0

60.0

55.5

49.0

Octave Band Centerline Frequency (Hz)

1. Rated in accordance with AHRI Standard 270.

Electrical Data
Model

Compressor

Voltage
RLA

LRA

MCC

OD Fan
Motor

Supply
Blower Motor

FLA

FLA

MCA1
(Amps)

Max Fuse2/
Breaker3 Size
(Amps)

24050

208/230-1-60

8.7

45.0

14.4

1.3

2.6

14.8

20

24075

208/230-1-60

8.7

45.0

14.4

1.3

3.8

16.0

20

30050

208/230-1-60

9.8

57.0

15.1

1.3

2.6

16.2

25

30075

208/230-1-60

9.8

57.0

15.1

1.3

3.8

17.4

25
30

36050, 36075

208/230-1-60

13.0

78.0

23.0

1.3

3.8

21.4

36100

208/230-1-60

13.0

78.0

23.0

1.3

5.4

23.0

35

42075, 42100

208/230-1-60

17.9

112.0

28.0

1.3

5.4

29.1

45

48065, 48100, 48125

208/230-1-60

21.8

117.0

34.0

1.7

5.4

34.4

50

60065, 60100, 60125

208/230-1-60

24.4

144.2

38.0

1.7

7.0

39.2

60

1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.

Johnson Controls Unitary Products

11

5005562-YTG-B-0715

WEIGHTS & DIMENSIONS
"D"

CENTER OF
GRAVITY
COMPRESSOR

"C"

"A"

FRONT
OF UNIT
Y

"B"

X

A0295-001-TG

Weights and Dimensions
Model

12

Weight (lbs.)

Center of Gravity

4 Point Load Location (lbs.)

24050

Shipping
372

Operating
367

X
28

Y
15

A
120

B
95

C
81

D
71

24075

382

377

28

15

124

96

81

76

30050

417

412

28

15

139

99

90

84

30075

421

416

28

15

146

93

82

95

36050

425

420

28

15

141

107

94

78

36075

432

427

28

15

135

115

103

74

36100

436

431

28

15

139

113

99

80

42075

446

441

28

15

145

112

99

85

42100

448

443

28

15

148

110

96

89

48065

520

515

28

15

189

116

93

117

48100

528

523

28

15

169

139

115

100

48125

533

528

28

15

164

145

124

95

60065

537

532

29

15

174

142

124

92

60100

541

536

28

15

177

140

117

102

60125

548

543

27

15

151

167

141

84

Johnson Controls Unitary Products

5005562-YTG-B-0715

AIRFLOW PERFORMANCE
Airflow - Side Duct Application
External Static Pressure (Inches WC)
Model

24050

24075

30050

30075

36050

36075

36100

42075

42100

48065

Motor Speed

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

Low (1)

732

667

624

567

517

470

415

369

Low/Medium (2)

818

771

723

674

628

579

530

482

Medium (3)

823

774

721

676

631

583

533

505

Medium/High (4)

994

948

906

865

823

778

739

700

High (5)

1148

1108

1071

1035

996

960

925

901

Low (1)

887

847

802

750

705

664

613

563

Low/Medium (2)

978

941

898

850

803

759

713

667

Medium (3)

1171

1114

1074

1039

993

949

906

864

Medium/High (4)

1349

1297

1265

1224

1185

1146

1107

1063

High (5)

1487

1462

1392

1331

1318

1281

1241

1201

Low (1)

700

657

599

554

512

461

411

365

Low/Medium (2)

906

868

825

779

735

692

650

608

Medium (3)

992

951

911

868

826

787

747

712

Medium/High (4)

1075

1032

1000

958

918

874

837

800

High (5)

1136

1089

1053

1018

978

941

903

869

Low (1)

1076

1020

984

943

903

859

819

779

Low/Medium (2)

1102

1048

1010

974

934

890

850

810

Medium (3)

1191

1140

1112

1076

1038

1000

958

919

Medium/High (4)

1201

1225

1187

1151

1118

1080

1041

1002

High (5)

1370

1329

1283

1271

1209

1176

1143

1109

Low (1)

1003

952

904

851

790

730

674

633

Low/Medium (2)

1180

1133

1085

1042

995

942

889

834

Medium (3)

1259

1209

1166

1126

1084

1032

980

928

Medium/High (4)

1314

1271

1229

1186

1144

1097

1049

998

High (5)

1506

1471

1403

1389

1345

1305

1262

1216

Low (1)

1225

1174

1131

1090

1046

993

941

888

Low/Medium (2)

1259

1209

1166

1126

1084

1032

980

928

Medium (3)

1314

1271

1229

1186

1144

1097

1049

998

Medium/High (4)

1348

1306

1259

1222

1179

1133

1086

1036

High (5)

1506

1471

1403

1389

1345

1305

1262

1216

Low (1)

1342

1302

1260

1217

1178

1134

1082

1034

Low/Medium (2)

1425

1368

1332

1293

1251

1208

1163

1113

Medium (3)

1554

1503

1465

1423

1386

1346

1302

1257

Medium/High (4)

1658

1599

1588

1530

1495

1454

1414

1373

High (5)

1966

1914

1862

1810

1757

1705

1653

1600

Low (1)

1315

1266

1229

1194

1156

1117

1080

1036

Low/Medium (2)

1436

1382

1342

1304

1262

1220

1179

1131

Medium (3)

1458

1406

1365

1327

1286

1244

1203

1155

Medium/High (4)

1573

1523

1484

1445

1408

1367

1327

1279

High (5)

1966

1914

1862

1810

1757

1705

1653

1600

Low (1)

1436

1382

1342

1304

1262

1220

1179

1131

Low/Medium (2)

1544

1492

1455

1416

1376

1336

1294

1248

Medium (3)

1573

1523

1484

1445

1408

1367

1327

1279

Medium/High (4)

1681

1640

1599

1557

1517

1478

1436

1393
1591

High (5)

1935

1887

1834

1788

1743

1701

1651

Low (1)

1046

1009

980

946

915

878

844

779

Low/Medium (2)

1295

1250

1213

1172

1133

1087

1045

964

Medium (3)

1620

1564

1517

1466

1418

1360

1308

1206

Medium/High (4)

1798

1722

1669

1620

1572

1527

1480

1413

High (5)

2146

2085

2025

1960

1872

1862

1798

1735

Continued on next page.

Johnson Controls Unitary Products

13

5005562-YTG-B-0715
Airflow - Side Duct Application (Continued)
External Static Pressure (Inches WC)
Model

48100

48125

60065

60100

60125

1.
2.
3.
4.
5.

14

Motor Speed

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

Low (1)

1620

1564

1517

1466

1418

1360

1308

1206

Low/Medium (2)

1694

1630

1580

1530

1482

1430

1380

1292

Medium (3)

1798

1722

1669

1620

1572

1527

1480

1413

Medium/High (4)

1835

1758

1703

1653

1604

1558

1511

1442

High (5)

2146

2085

2025

1960

1872

1862

1798

1735

Low (1)

1620

1564

1517

1466

1418

1360

1308

1206

Low/Medium (2)

1798

1722

1669

1620

1572

1527

1480

1413

Medium (3)

1922

1863

1804

1754

1724

1658

1612

1559

Medium/High (4)

2001

1952

1890

1839

1820

1742

1696

1651

High (5)

2146

2085

2025

1960

1872

1862

1798

1735

Low (1)

1073

1043

1009

988

963

941

917

892

Low/Medium (2)

1329

1292

1250

1223

1192

1165

1136

1105

Medium (3)

2054

1998

1934

1890

1843

1801

1757

1710

Medium/High (4)

2195

2144

2098

2049

2003

1955

1883

1868

High (5)

2445

2388

2306

2293

2235

2178

2129

2077

Low (1)

1730

1682

1628

1592

1552

1517

1479

1439

Low/Medium (2)

1858

1807

1749

1710

1667

1629

1589

1546

Medium (3)

2054

1998

1934

1890

1843

1801

1757

1710

Medium/High (4)

2195

2144

2098

2049

2003

1955

1883

1868

High (5)

2445

2388

2306

2293

2235

2178

2129

2077

Low (1)

2063

2008

1943

1899

1851

1809

1763

1717

Low/Medium (2)

2130

2084

2032

1983

1927

1951

1860

1815

Medium (3)

2195

2144

2098

2049

2003

1955

1883

1868

Medium/High (4)

2275

2252

2169

2154

2112

2065

1989

1976

High (5)

2445

2388

2306

2293

2235

2178

2129

2077

Airflow tested with dry coil conditions, without air flitters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.

Johnson Controls Unitary Products

5005562-YTG-B-0715
Airflow - Bottom Duct Application
External Static Pressure (Inches WC)
Model

24050

24075

30050

30075

36050

36075

36100

42075

42100

48065

Motor Speed

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

Low (1)

754

710

665

611

560

491

445

391

Low/Medium (2)

867

815

773

720

677

622

559

505

Medium (3)

951

908

868

828

781

735

686

631

Medium/High (4)

1024

982

942

902

861

817

775

721

High (5)

1204

1159

1121

1085

1051

1013

975

938

Low (1)

899

869

827

782

734

685

630

575

Low/Medium (2)

1033

960

924

879

834

787

735

685

Medium (3)

1186

1133

1095

1056

1016

975

935

891

Medium/High (4)

1357

1322

1284

1248

1211

1174

1127

1087

High (5)

1480

1439

1404

1367

1369

1299

1264

1226

Low (1)

726

676

622

575

520

467

410

376

Low/Medium (2)

928

886

841

795

745

706

658

607

Medium (3)

1021

983

942

900

855

811

770

729

Medium/High (4)

1109

1071

1029

995

949

908

864

826

High (5)

1170

1134

1096

1061

1020

978

938

899

Low (1)

1076

1042

1009

969

930

890

849

808

Low/Medium (2)

1104

1063

1025

987

947

908

869

830

Medium (3)

1205

1170

1136

1098

1060

1025

985

943

Medium/High (4)

1285

1251

1213

1179

1141

1104

1065

1027

High (5)

1406

1375

1341

1306

1271

1236

1198

1163

Low (1)

1008

962

916

861

807

757

700

650

Low/Medium (2)

1190

1148

1106

1055

1008

955

914

863

Medium (3)

1262

1223

1181

1137

1091

1044

994

952

Medium/High (4)

1324

1282

1245

1202

1161

1112

1067

1018

High (5)

1517

1475

1447

1400

1357

1318

1275

1232

Low (1)

1231

1186

1146

1103

1069

1030

977

912

Low/Medium (2)

1270

1225

1189

1140

1098

1046

1008

960

Medium (3)

1317

1286

1245

1198

1151

1110

1064

1024

Medium/High (4)

1358

1317

1275

1238

1197

1148

1105

1057

High (5)

1517

1475

1447

1400

1357

1318

1275

1232

Low (1)

1340

1299

1264

1224

1182

1182

1097

1049

Low/Medium (2)

1409

1368

1334

1291

1253

1201

1173

1128

Medium (3)

1527

1492

1470

1419

1385

1343

1299

1250

Medium/High (4)

1663

1585

1594

1601

1521

1480

1440

1400

High (5)

1930

1892

1853

1805

1760

1696

1625

1553

Low (1)

1332

1295

1263

1222

1185

1148

1110

1063

Low/Medium (2)

1457

1419

1376

1340

1299

1253

1215

1160

Medium (3)

1451

1412

1371

1339

1296

1257

1211

1165

Medium/High (4)

1568

1524

1491

1464

1425

1383

1345

1296

High (5)

1978

1937

1891

1837

1785

1725

1656

1604

Low (1)

1455

1414

1379

1335

1294

1254

1212

1160

Low/Medium (2)

1566

1532

1492

1455

1416

1372

1333

1280

Medium (3)

1565

1530

1491

1458

1419

1381

1336

1290

Medium/High (4)

1675

1641

1606

1578

1535

1495

1455

1412

High (5)

1946

1909

1863

1815

1771

1721

1654

1595

Low (1)

1032

999

970

938

910

879

843

808

Low/Medium (2)

1272

1236

1204

1165

1129

1081

1037

968

Medium (3)

1611

1574

1518

1494

1439

1405

1357

1266

Medium/High (4)

1892

1777

1771

1701

1639

1617

1565

1489

High (5)

2131

2058

1998

1949

1892

1840

1788

1728

Continued on next page.

Johnson Controls Unitary Products

15

5005562-YTG-B-0715
Airflow - Bottom Duct Application (Continued)
External Static Pressure (Inches WC)
Model

48100

48125

60065

60100

60125

1.
2.
3.
4.
5.

16

Motor Speed

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

Low (1)

1598

1548

1502

1454

1410

1362

1307

1251

Low/Medium (2)

1663

1612

1568

1522

1476

1422

1370

1297

Medium (3)

1789

1733

1670

1650

1596

1578

1535

1483

Medium/High (4)

1931

1814

1808

1736

1673

1650

1597

1519

High (5)

2131

2058

1998

1949

1892

1840

1788

1728

Low (1)

1598

1548

1502

1454

1410

1362

1307

1251

Low/Medium (2)

1766

1703

1656

1611

1566

1518

1469

1419

Medium (3)

1912

1875

1805

1787

1750

1713

1672

1636

Medium/High (4)

2105

2014

2006

1931

1898

1845

1793

1739

High (5)

2131

2058

1998

1949

1892

1840

1788

1728

Low (1)

1026

999

989

950

907

907

886

862

Low/Medium (2)

1263

1230

1192

1165

1167

1101

1099

1071

Medium (3)

1987

1933

1861

1817

1820

1715

1725

1651

Medium/High (4)

2114

2050

2047

1974

1899

1889

1920

1866

High (5)

2369

2308

2249

2183

2126

2088

2034

1990

Low (1)

1655

1612

1596

1531

1461

1462

1429

1391

Low/Medium (2)

1766

1720

1667

1629

1632

1539

1537

1498

Medium (3)

1987

1933

1861

1817

1820

1715

1725

1651

Medium/High (4)

2114

2050

2047

1974

1899

1889

1920

1866

High (5)

2369

2308

2249

2183

2126

2088

2034

1990

Low (1)

1973

1924

1905

1826

1743

1744

1703

1660

Low/Medium (2)

2024

1983

1937

1889

1886

1843

1799

1759

Medium (3)

2123

2075

2019

1970

1978

1862

1849

1804

Medium/High (4)

2191

2154

2117

2075

2002

1995

2028

1974

High (5)

2369

2308

2249

2183

2126

2088

2034

1990

Airflow tested with dry coil conditions, without air flitters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.

Johnson Controls Unitary Products

5005562-YTG-B-0715

BOTTOM DUCT DIMENSIONS (Inches)

Additional Static Resistance
Size (Tons)

024 (2.0)

030 (2.5)

036 (3.0)

042 (3.5)

048 (4.0)

060 (5.0)

CFM

500
600
700
800
900
1000
1100
1200
700
800
900
1000
1100
1200
1300
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000

Wet Indoor Coil Economizer1

0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09

0.00
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05

Filter/Frame Kit

0.01
0.02
0.04
0.06
0.08
0.10
0.13
0.16
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.18
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11

D

16

C

A

RETURN
AIR DUCT

E
B

A

SUPPLY
AIR DUCT

F

Model
24, 30, 36, 42
48, 60

A
10
14

B
21.5
13.5

A0298-001

C
5
5

D
4.5
3.5

E
47.5
47.5

F
32
42

REAR DUCT DIMENSIONS (Inches)

15.6

SUPPLY
AIR DUCT

RETURN
AIR DUCT

6

A0299-001

Model
24, 30, 36, 42
48, 60

A

B

A
9.6
13.6

A

4.3

B
22
14

1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
2. Filter pressure drop based on standard filter media tested at velocities not to
exceed 300 ft/min.

Johnson Controls Unitary Products

17

5005562-YTG-B-0715

UNIT TYPICAL DUCT APPLICATIONS
ROOF CURB
INSTALLATION
REAR DUCT

ROOF CURB
INSTALLATION
BOTTOM DUCT

SLAB ON
GROUND
INSTALLATION

A0324-001

UNIT TYPICAL SLAB ON GROUND INSTALLATION

TO POWER SUPPLY

RETURN
AIR DUCT

SUPPLY
AIR DUCT

FIELD-SUPPLIED
DISCONNECT
SWITCH
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE
TO GAS
SUPPLY LINE

18

CONTROL WIRING TO
INDOOR THERMOSTAT
A0325-001

Johnson Controls Unitary Products

5005562-YTG-B-0715

UNIT TYPICAL ROOF CURB INSTALLATION

ROOF
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE

ROOF CURB
FIELD-SUPPLIED
DISCONNECT
SWITCH
TO GAS
SUPPLY LINE

TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT

RETURN
AIR DUCT

SUPPLY
AIR DUCT

A0326-001

EXTERNAL STATIC PRESSURE SETUP
To measure external static pressure:
•
•
•
•
•
•

Measure the supply air static pressure
Record this positive number
Measure the return air static pressure
Record this negative number
Treat the negative number as a positive and add the two numbers together
This is total system static

Johnson Controls Unitary Products

19

NOTES

Subject to change without notice. Published in U.S.A.
Copyright © 2015 by Johnson Controls, Inc. All rights reserved.

York International Corp.
5005 York Drive
Norman, OK 73069

5005562-YTG-B-0715
Supersedes: 5005562-YTG-B-0215



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : Yes
Author                          : csardom
Create Date                     : 2015:07:23 10:05:53-05:00
Modify Date                     : 2015:07:23 11:05:35-05:00
XMP Toolkit                     : Adobe XMP Core 5.6-c015 81.157285, 2014/12/12-00:43:15
Producer                        : Acrobat Distiller 15.0 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Metadata Date                   : 2015:07:23 11:05:35-05:00
Format                          : application/pdf
Title                           : 5005562-YTG-B-0715.fm
Creator                         : csardom
Document ID                     : uuid:bc7e2265-c30d-491b-af33-fb091a68bb8e
Instance ID                     : uuid:78cb88a0-ff0b-49bf-87f3-ee320aab8a2b
Page Layout                     : OneColumn
Page Mode                       : UseThumbs
Page Count                      : 20
EXIF Metadata provided by EXIF.tools

Navigation menu